Project Name: Document Description: Location:
Substation
Equipment Description:
HV Over Current & Earth Fault Relay of Transformer - 1
INSPECTION [ √ QIP Item No. (viii)
Document1
]
TEST [
√
]
Description of Inspection / Test Activities
DATE: Ref. Doc. No.
Testing of Over Current Protection Relay Testing
Page 1 of 6
General Data:
Line/Feeder
Power Transformer T-1
Serial Number
Relay Type
HV Over Current & Earth Fault
Relay Model/Make
CT Ratio
System Voltage
Relay Checks: Items
Status
Visual Inspection Relay Damaged Rating Information Case Earth Installed Test Block connection checked
Relay Energized Relay Auxiliary Supply Relay Healthy LED Working Alarm LED Working Trip LED Working
Measurement Checks Input
CT Ratio
Injected Current (A)
Calculated Current (A)
Measured Current (A)
A
Document1
Page 2 of 6
B C
Over Current (Low Set) I > Curve: IEC S Inverse
Pick Up Test
Phase
Set Pick Up Current (A)
Observed Pick Up (A)
Drop Off Current (A)
AB BC CA ABC
Trip Time Test (2X) TMS = Phase
Injected Current (A)
Calculated Time (Sec)
Observed Time (Sec)
AB BC CA ABC
Document1
Page 3 of 6
Over Current (High Set) I >> Curve Type: Instantaneous Trip
Trip Time Test (x1.2) Phase
Set Pick Up Current (A)
Injected Current (A)
Set Trip Time
Observed Time (Sec)
AB BC CA ABC
Earth Fault (Low Set) Ie > Curve: IEC S Inverse
Pick Up Test Phase
Set Pick Up Current (A)
Observed Pick Up (A)
Drop Off Current (A)
Injected Current (A)
Calculated Time (Sec)
Observed Time (Sec)
A B C
Trip Time Test (X2) TMS = Phase
Document1
Page 4 of 6
A B C
Earth Fault (High Set) Ie >> Curve Type: Instantaneous trip
Trip Time Test (x1.25) Phase
Set Pick Up Current (A)
Injected Current (A)
Set Trip Time
Observed Time (Sec)
A B C
Testing Equipment Data: Name of Equipment: Model/ Type: Manufacturer: Serial No: Calibration Expiry Date: