Supervisor de Temperatura para Transformadores com Óleo TS
Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10
1
Supervisor de Temperatura para Transformadores com Óleo TS SUMÁRIO
1
ASSISTÊNCIA TÉCNICA .................................................................................. 3
2 HISTÓRICO DE REVISÕES............................................................................... 3 3
PROTOCOLO MODBUS RTU ............................................................................. 4
4 PROTOCOLO DNP 3.0 .................................................................................... 9
Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10
2
Supervisor de Temperatura para Transformadores com Óleo TS 1
Assistência Técnica
As informações deste documento permitem que todas as leituras, seleções e comandos do TS sejam efetuados por meio da porta de comunicação serial RS485 (opcional). Estão disponíveis os protocolos Modbus RTU e DNP3.0 nível 1. Para obter assistência técnica para o TS ou qualquer outro produto Treetech, entre em contato através do endereço abaixo: Treetech Sistemas Digitais Ltda. – Assistência Técnica Rua José Alvim, 100 – Salas 03 e 04 – Centro Atibaia – São Paulo – Brasil CEP: 12.940-800 CNPJ: 74.211.970/0002-53 IE: 190.159.742.110 TEL: +55 (11) 2410-1190 x201 FAX: +55 (11) 2410-1190 x702 Email:
[email protected] Site: http://www.treetech.com.br
2
Histórico de Revisões
Revisão
Data
Descrição
1.00
31/07/2015
Emissão Inicial
1.10
03/11/2015
Atualização para o firmware 1.13
Feito por João Victor Miranda João Victor Miranda
Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10
3
Supervisor de Temperatura para Transformadores com Óleo TS 3
Protocolo Modbus RTU
Protocolo: Modo: Taxa de transmissão: Bits de dados: Bits de parada: Paridade: Tipo de variável de memória:
Modbus RTU (binário) 4.800, 9.600, 19.200 ou 38.400, 57.600 ou 115.200bps 8 2 Nenhuma Holding Registers 03 (Leitura, em blocos ou individualmente)
Comandos implementados:
06 (Escrita em um único registrador)
Base de Endereçamento: Aplicável à versão de firmware:
16 (Escrita em um bloco de registradores) Base 1 (PLC Address): O endereço dos dados inicia em 1 1.13
Registrador
Bit
01
-
02
-
03
-
04
-
05
Mapa de Registradores TS (Versão 1.13) Descrição Faixa de Medição ou Estado
Passo
Escrita ou Leitura
-55...200
1
E/L
-55...200
1
E/L
0...20
0,1
E/L
-55...200
1
E/L
-
Parâmetro ALMO Parâmetro DSLO Parâmetro RDSO Parâmetro ALME Parâmetro DSLE
-55...200
1
E/L
06 07
-
Parâmetro RDSE Parâmetro IDI
0,1 1
E/L E/L
08 09
-
Parâmetro RTDS Parâmetro DISP
1 1
E/L E/L
10 11 12
-
Parâmetro ALO Parâmetro DSO Parâmetro ALE
0...20 0= Português 1= Inglês 2= Espanhol 1...3 0= Fixo 1= rolagem 2= Máxima 0...4 0...4 0...4
1 1 1
E/L E/L E/L
13 14
0
Parâmetro DSE Parâmetro RL1
-
E/L E/L
1
Parâmetro RL2
-
E/L
2
Parâmetro RL3
-
E/L
3
Parâmetro RL4
0...4 0 = Normal 1 = Invertido 0 = Normal 1 = Invertido 0 = Normal 1 = Invertido 0 = Normal 1 = Invertido
-
E/L
Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10
4
Supervisor de Temperatura para Transformadores com Óleo TS 15
-
Parâmetro VSAN
16
-
Parâmetro FSAN
17 18 19 20 21 22 23
-
Parâmetro FESA Parâmetro IESA Parâmetro GEO Parâmetro TE Parâmetro HS+ Parâmetro HS* Parâmetro 2*M
24 25 26 27 28 29
-
Parâmetro CNT Parâmetro CNS Parâmetro RF1 Parâmetro RF2 Parâmetro HIS Parâmetro ALT
30 31 32 33 34 35 36
-
37
-
38
-
39 40 41 42
-
43 44
-
45
-
Parâmetro CV1 Parâmetro CV2 Parâmetro HIC Parâmetro EVH Parâmetro EVM Parâmetro TEV Parâmetro HLOG Parâmetro TLOG Parâmetro RLOG Parâmetro MES Parâmetro DIA Parâmetro ANO Parâmetro HORA Parâmetro MIN Modo de operação do grupo de resfriamento RF1 Modo de operação do grupo de
-
0= Óleo 1= Enrol. 2= RTD2 3= RTD3 4= Máxima 0= 0-1mA 1= 0-5mA 2= 0-10mA 3= 0-20mA 4= 4-20mA -55...200 -55...200 -50...50 1...999 0...20 1...1,50 0=1.6 1=1.8 2=2.0 0...99,98 0...10 -55...200 -55...200 0...9 0 = desligado 1 = ligado 10...200 10...200 1...9 0...23 0...59 1...100 1...20
1
E/L
1
E/L
1 1 1 1 0,1 0,01 -
E/L E/L E/L E/L E/L E/L E/L
0,01 0,01 1 1 1
E/L E/L E/L E/L E/L E/L
1 1 1
E/L E/L E/L E/L
1 1
E/L E/L
1...120
1
E/L
0= Sem ação 1=Resetar log 1...12 1...31 05...99 0..23
-
E/L
-
E/L E/L E/L E/L
0...59 0=automático 1 =manual
-
E/L E/L
0=automático 1 =manual
-
E/L
Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10
5
Supervisor de Temperatura para Transformadores com Óleo TS
46
-
47
-
resfriamento RF2 Reset memória de erros Parâmetro TCR1
48
-
Parâmetro TCR2
49
-
Parâmetro ATIV
50 51 52 53
-
54
-
55 56 57 58…69 1001
-
1002
-
1003
-
1004
-
1005
-
1006
-
1007
-
1008
-
1009
-
1010
-
1011
-
Parâmetro VIDA Parâmetro BALI Parâmetro ABAL Parâmetro LMAX Parâmetro LMIN Parâmetro KP Parâmetro KI Parâmetro KD Reservado Temperatura óleo Temperatura enrolamento Temperatura RTD2 Temperatura RTD3 Temperatura máxima atingida pelo óleo Temperatura máxima atingida pelo enrolamento Temperatura máxima atingida pelo RTD2 Temperatura máxima atingida pelo RTD3 Gradiente Final de Temperatura (GFN) Percentual de carga (%) Corrente lida nosecundário do TC (AMP)
0=off 1=reset 0=óleo 1=enrolamento 0=óleo 1=enrolamento 0=off 1=on 2=automático 1…60 -999…999 0…999 0…200
-
E/L
-
E/L
-
E/L
-
E/L
1 1 1 1
E/L E/L E/L E/L
0…200
1
E/L
0…9,999 0…9,999 0…9,999 -55...200
0,001 0,001 0,001 0,1
E/L E/L E/L E/L L
-55...200
0,1
L
-55...200
0,1
L
-55...200
0,1
L
-55...200
0,1
L
-55...200
0,1
L
-55...200
0,1
L
-55...200
0,1
L
-55...55
0,01
L
0...100
0,1
L
0...10
0,01
L
Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10
6
Supervisor de Temperatura para Transformadores com Óleo TS 1012
-
4
Corrente do transformador (kA) Estado do Relé da R.F.1 Estado do Relé da R.F.2 Estado do Relé de Autodiagnóstico Estado do Relé 1
1013
0
5
Estado do Relé 2
6
Estado do Relé 3
7
Estado do Relé 4
1014
-
1015
0
Variável de erros Opcional RTDs adicionais Opcional Saída Analógica Opcional Comunicação Serial RS485 Não utilizado Opcional Memória de Massa Opcional Préresfriamento Opcional Exercício de ventiladores Não utilizado Alarme temperatura do enrolamento Alarme temperatura do óleo Desligamento temperatura do enrolamento Desligamento temperatura do óleo Não utilizado Não utilizado Não utilizado Não utilizado Ponteiro do LOG Reservado
1 2
1 2
3 4
5 6
1016
7 0
1
2
3
1017 1018
4 5 6 7 -
0...99,98
0,01
L
0 = desligado 1 = ligado 0 = desligado 1 = ligado 0 = desligado 1 = ligado
-
L
-
L
-
L
0 = desligado 1 = ligado 0 = desligado 1 = ligado 0 = desligado 1 = ligado 0 = desligado 1 = ligado *
-
L
-
L
-
L
-
L
-
L
0 =não disp. 1 =disponível 0 =não disp. 1 =disponível 0 =não disp. 1 =disponível
-
L
-
L
-
L
0 =não disp. 1 =disponível
-
L L
0 =não disp. 1 =disponível 0 =não disp. 1 =disponível
-
L
-
L
0= não atuado 1= atuado
-
L L
0= não atuado 1= atuado
-
L
0= não atuado 1= atuado
-
L
0= não atuado 1= atuado
-
L
2000...16384 -
-
L L L L L L
Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10
7
Supervisor de Temperatura para Transformadores com Óleo TS 1019
-
1020
-
1021
-
1022
-
1023
-
1024 1025
-
1026
-
1027
-
1028
-
Memória de autodiagnóstico Valor de carga em relação ao parâmetro CMIN Valor novo para acionamento do primeiro estágio Balanço de vida – parte alta Balanço de vida - parte baixa Reservado Número de série 1 Número de série 2 Tempo de retardo para desligamento de enrolamento Tempo de retardo para desligamento de óleo
Em dias na tela de consulta, em segundos no registrador Em dias na tela de consulta, em segundos no registrador
-
L
-
L
-
L
-
L
-
L
-
L
-
L
-
L
-
L
Observações: * O valor informado corresponde ao mesmo código de erro apresentado no display do TS em formato hexadecimal.
Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10
8
Supervisor de Temperatura para Transformadores com Óleo TS 4
Protocolo DNP 3.0
DNP V3.0 DEVICE PROFILE DOCUMENT
This document is accompanied by table 1, Supported DNP 3.0 Objects, Function Codes, and Qualifiers, and table 2, Point List.
Vendor Name: TreeTech Sistemas Digitais
Device Name: Supervisor de Temperatura TS Highest DNP Level Supported:
For Requests: Level 1
Device Function:
Master
Remote
For Responses: ______
Notable Objects, functions, and/or qualifiers supported in addition to highest DNP Levels Supported:
Reads of Binary Inputs (Object 01, Variation 01, Qualifier 00, 01 and 06)
Reads of 16-bit Analog Inputs (Object 30, Variation 04, Qualifier 00, 01 and 06)
GENERAL INFORMATION: Maximum Data Link Frame Size (octets):
Maximum Application Frame Size (octets):
Transmitted: 292
Transmitted: 500
Received: (must be 292)
Received: 200
Maximum Data Link Re-tries:
Maximum Application Layer Re-tries:
None
None
Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10
9
Supervisor de Temperatura para Transformadores com Óleo TS Fixed at ___
Configurable, range ___ to ___
Configurable, range 0 to 255
(Fixed is not permitted)
Requires Data Link Layer Confirmation:
Never Always Sometimes If Sometimes, when? ______________________________ Configurable as: __________________________________________ Requires Application Layer Confirmation:
Never Always (Not recommended) When reporting Event Data (Slave devices only) When sending mult-fragment responses (Slave devices only) Sometimes: If ‘Sometimes’, when? __________________________________________ Configurable: If ‘Configurable’, how? _________________________________________ Timeouts while waiting for:
Fixed at _____
Variable
Configurable*
None
Fixed at _____
Variable
Configurable*
Application Confirm:
None
Fixed at _____
Variable
Configurable*
Complete Appl. Response:
None
Fixed at _____
Variable
Configurable*
Data link confirm:
None
Complete Appl. Fragment:
Others: ______________________________________________________________________ *Attach explanation if ‘Variable’ or ‘Configurable’ was checked for any timeout
Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10
10
Supervisor de Temperatura para Transformadores com Óleo TS Sends/Executes Control Operations:
WRITE Binary Outputs:
Never
Always
Sometimes
Configurable
SELECT/OPERATE:
Never
Always
Sometimes
Configurable
DIRECT OPERATE:
Never
Always
Sometimes
Configurable
DIRECT OPERATE-No ACK:
Never
Always
Sometimes
Configurable
Count > 1:
Never
Sometimes
Configurable
Pulse On:
Never
Sometimes
Configurable
Pulse Off:
Never
Sometimes
Configurable
Latch On:
Never
Always
Sometimes
Configurable
Latch Off:
Always
Sometimes
Configurable
Never
Queue:
Never
Always
Sometimes
Configurable
Clear Queue:
Never
Always
Sometimes
Configurable
Always Always Always
Attach explanation if 'Sometimes' or 'Configurable' was checked for any operation. FILL OUT THE FOLLOWING ITEM FOR MASTER DEVICES ONLY: Expects Binary Input Change Events:
Either time-tagged or non-time-tagged for a single event. Both time-tagged and non-time-tagged for a single event. Configurable (Attach explanation)
FILL OUT THE FOLLOWING ITEMS FOR REMOTE DEVICES ONLY: Default Status Object/Variation:
Default Analog Object/Variation:
No Status objects reported
No Analog objects reported
Configurable (attach explanation)
Configurable (attach explanation)
Default Static Object_____________
Default Static Object______________
Default Static Variation __________
Default Static Variation ___________
Default Event Object_____________
Default Event Object______________
Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10
11
Supervisor de Temperatura para Transformadores com Óleo TS Default Event Variation __________
Default Event Variation ___________
Point-by-point list attached
Point-by-point list attached
Default Counter Object/Variation:
Counters Roll Over at:
No Counters reported
No Counters Reported
Configurable (attach explanation)
Configurable (attach explanation)
Default Static Object____________
16 Bits
Default Static Variation__________
32 Bits
Default Event Object____________
Other Value _________
Default Event Variation _________
Point-by-point list attached
Point-by-point list attached
Default Frozen Counter Object/Variation:
Counters frozen by means of:
No Frozen Counters reported
No Frozen Counters reported
Configurable (attach explanation)
Remote device time based
Default Static Object____________
Fixed time
Default Static Variation__________
Configurable; range _____ to _____
Default Event Object____________
Master Request (see implementation table)
Default Event Variation __________
Both
Point-by-point list attached
Analog Deadbands:
Configuring Analog Deadbands:
Fixed
Not Applicable
Configurable: ____
Configuration Software
Per Point
Using Object 34 from the master station
Per Analog Type
Both configuration software and Object 34
Global
Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10
12
Supervisor de Temperatura para Transformadores com Óleo TS
Are the updated deadband values preserved through a device reset:
YES NO
The number of multiple objects allowed in a single read request message:
Number of multiple objects allowed: 3
Ability to DISABLE/ENABLE DNP database points:
IIN 1-6 Device Trouble Bit:
Not Applicable
Never used
Per point
Reason for setting:
Per object Global
Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10
13
Supervisor de Temperatura para Transformadores com Óleo TS Time Sync Information:
Time Sync Period:
Never Fixed at ______ seconds Configurable, range ______ to _______ seconds Only at IED startup
a) Maximum time base drift over a 10 minute interval:
_________ ms
b) Maximum Internal Time Reference Error when set via DNP: _________ ms c) Maximum Delay Measurement error:
_________ ms
d) Maximum Response time:
_________ ms
e) Event data time-tag error – if different than ( c ) : Binary Input Change Events
_________ ms
Counter Change Events
__________ ms
Frozen Counter Change Events
__________ ms
Analog Change Events
__________ ms
Frozen Analog Change Events
__________ ms
Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10
14
Supervisor de Temperatura para Transformadores com Óleo TS Sends/Executes Digital Control Operations:
SELECT/OPERATE*
Never
Always
Sometimes
Configurable
DIRECT OPERATE*
Never
Always
Sometimes
Configurable
DIRECT OPERATE – NO ACK*
Never
Always
Sometimes
Configurable
*Attach explanation if ‘Sometimes’ or ‘Configurable’ was checked for any operation. *To support control operations and conform to the Subset Definitions, either ‘Always’ or ‘Configurable’ must be selected.
Count > 1
Never
Always
Sometimes
Configurable
Pulse On
Never
Always
Sometimes
Configurable
Pulse Off
Never
Always
Sometimes
Configurable
Latch On
Never
Always
Sometimes
Configurable
Latch Off
Never
Always
Sometimes
Configurable
Trip/Close
Never
Always
Sometimes
Configurable
Raise/Lower
Never
Always
Sometimes
Configurable
Queue
Never
Always
Sometimes
Configurable
Clear Queue
Never
Always
Sometimes
Configurable
Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10
15
Supervisor de Temperatura para Transformadores com Óleo TS Sends/Executes Analog Control Operations:
SELECT/OPERATE*
Never
Always
Sometimes
Configurable
DIRECT OPERATE*
Never
Always
Sometimes
Configurable
DIRECT OPERATE – NO ACK*
Never
Always
Sometimes
Configurable
*Attach explanation if ‘Sometimes’ or ‘Configurable’ was checked for any operation. *To support control operations and conform to the Subset Definitions, either ‘Always’ or ‘Configurable’ must be selected.
Queue
Never
Always
Sometimes
Configurable
Clear Queue
Never
Always
Sometimes
Configurable
The maximum number of objects supported in a single control request for objects 12 and 41.
Number of objects allowed for object 12: 1 Number of objects allowed for object 41: 1
Control Points per address:
Configurable 1 control point per address 2 control points per address
Maximum Select/Execute Delay Time:
Do all indices support the same control codes:
YES – Controls codes 3 and 4 NO – attached points list stating configuration ability and supported control codes per point or group of points
Ability for REMOTE/LOCAL control mode:
Not Applicable
Not Applicable
Fixed at _____ seconds
Per point
Configurable, range ______ to ______ seconds
Per object
Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10
16
Supervisor de Temperatura para Transformadores com Óleo TS Global
Sends Unsolicited Responses:
Sends Static Data in Unsolicited Responses:
Never
Never
Configurable (attach explanation)
When Device Restarts
Only certain objects
When Status Flags Change
Sometimes (attach explanation) *No other options permitted. ENABLE/DISABLE Unsolicited:
Minimum number of events and/or minimum time before transmission of an unsolicited message.
Not Supported Configurable
# of events:__________
Function codes 20,21 supported
min. amount of time(msec) :___________
Assign Class Function code supported:
Is the Event Buffer size configurable:
NO
NO fixed size: _______
YES
YES: range: _________to_________
Per Object Per Point
Configurable Per Class buffer:
Configurable NO YES Are the updated ENABLE/DISABLE unsolicited settings Are the updated Assign Class settings saved through a saved through a device reset: device reset:
YES
YES
NO
NO
Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10
17
Supervisor de Temperatura para Transformadores com Óleo TS Supports Collision Avoidance:
Never Always (attach explanation) Configurable (attach explanation)
Source Address Filtering:
Not Supported Configurable (attach explanation)
Supports Multi-drop communications:
Yes
No
Sends Multi-Fragment Responses:
Yes
No
Tabela 1: Supported DNP 3.0 Objects, Function Codes, and Qualifiers REQUESTS
RESPONSES
(slave will parse)
(master must parse)
OBJECTS
Object
Variation
Function
Qualifier
Function
Qualifier
Codes
Codes(hex)
Codes
Codes(hex)
Description
01
02
Binary Input with flag
01
00, 06
00, 129
00, 01
10
02
Binary Output
01, 02
00, 06
00, 129
00, 01
12
01
Control Relay Output Block
05, 06
17, 28
00, 129
Echo
30
02
16 bit Analog Input with flag
01
06
00, 129
00, 01
40
02
16 bit Analog Output Status
01
06
00, 129
00, 01
41
02
16-bit Analog Output Block
05, 06
17, 28
00, 129
Echo
50
01
Time and Date – Absolute time
01, 02
07
01, 02
07
60
01
Class 0 Data
01
06
129
00, 01
60
02
Class 1 Data
01
06
129
00, 01
Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10
18
Supervisor de Temperatura para Transformadores com Óleo TS 60
03
Class 2 Data
01
06
129
00, 01
60
04
Class 3 Data
01
06
129
00, 01
80
01
Internal Indications
02
00, index=7
129
-
-
-
Cold Restart
13
-
129
-
Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10
19
Supervisor de Temperatura para Transformadores com Óleo TS
Table 2: Point List
Description Binary output
Index 0…2
Default Static / Event Variation
Scale
Point Name
Object
Var.
Description
12
01
No status
Reservado
Binary output
3
12
01
No status
-
Modo de operação do Relé programável 1. 0=Normal / 1=Invertido
Binary output
4
12
01
No status
-
Modo de operação do Relé programável 2. 0=Normal / 1=Invertido
Binary output
5
12
01
No status
-
Modo de operação do Relé programável 3. 0=Normal / 1=Invertido
Binary output
6
12
01
No status
-
Modo de operação do Relé programável 4. 0=Normal / 1=Invertido
Binary output
7
12
01
No status
-
Reservado
Binary output
8
12
01
No status
-
Parâmetro ALT. 0=Desliga / 1= Liga
Binary output
9…15
12
01
No status
-
Reservado
Binary output
16
12
01
No status
-
Modo de operação do grupo RF1 0=Automático / 1=Manual
Binary output
17…23
12
01
No status
-
Reservado
Binary output
24
12
01
No status
-
Modo de operação do grupo RF2 0=Automático / 1=Manual
Binary output
25…31
12
01
No status
-
Reservado
Binary output
32
12
01
No status
-
Reset Memória de erros
Binary output
33…39
12
01
No status
-
Reservado
Binary output
40
12
01
No status
-
Reset temperatura máxima óleo
Binary output
41
12
01
No status
-
Reset temperatura máxima Enrolamento
Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10
20
Supervisor de Temperatura para Transformadores com Óleo TS Binary output
42
12
01
No status
-
Reset temperatura máxima RTD2
Binary output
43
12
01
No status
-
Reset temperatura máxima RTD3
Analog output block
0
41
02
16-bit
-
Parâmetro ALMO
Analog output block
1
41
02
16-bit
-
Parâmetro DSLO
Analog output block
2
41
02
16-bit
1x10
Parâmetro RDSO
Analog output block
3
41
02
16-bit
-
Parâmetro ALME
Analog output block
4
41
02
16-bit
-
Parâmetro DSLE
Analog output block
5
41
02
16-bit
1x10
Parâmetro RDSE Parâmetro IDI
Analog output block
0= Português 6
41
02
16-bit
1= Inglês 2= Espanhol
Analog output block
7
41
02
16-bit
-
Parâmetro RTDS Parâmetro DISP
Analog output block
0= Fixo 8
41
02
16-bit
1= rolagem 2= Máxima
Analog output block
9
41
02
16-bit
-
Parâmetro ALO
Analog output block
10
41
02
16-bit
-
Parâmetro DSO
Analog output block
11
41
02
16-bit
-
Parâmetro ALE
Analog output block
12
41
02
16-bit
-
Parâmetro DSE
Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10
21
Supervisor de Temperatura para Transformadores com Óleo TS Parâmetro VSAN 0= Óleo Analog output block
1= Enrolamento 13
41
02
16-bit
2= RTD2 3= RTD3 4= Máxima Parâmetro FSAN 0= 0-1mA
Analog output block
1= 0-5mA 14
41
02
16-bit
2= 0-10mA 3= 0-20mA 4= 4-20mA
Analog output block
15
41
02
16-bit
-
Parâmetro FESA
Analog output block
16
41
02
16-bit
-
Parâmetro IESA
Analog output block
17
41
02
16-bit
1x10
Parâmetro GEO
Analog output block
18
41
02
16-bit
-
Analog output block
19
41
02
16-bit
1x10
Parâmetro HS+
Analog output block
20
41
02
16-bit
1x100
Parâmetro HS*
Parâmetro TE
Parâmetro 2*M Analog output block
0=1.6 21
41
02
16-bit
1=1.8 2=2.0
Analog output block
22
41
02
16-bit
1x100
Parâmetro CNT
Analog output block
23
41
02
16-bit
1x100
Parâmetro CNS
Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10
22
Supervisor de Temperatura para Transformadores com Óleo TS Analog output block
24
41
02
16-bit
-
Parâmetro RF1
Analog output block
25
41
02
16-bit
-
Parâmetro RF2
Analog output block
26
41
02
16-bit
-
Parâmetro HIS
Analog output block
27
41
02
16-bit
-
Parâmetro CV1
Analog output block
28
41
02
16-bit
-
Parâmetro CV2
Analog output block
29
41
02
16-bit
-
Parâmetro HIC
Analog output block
30
41
02
16-bit
-
Parâmetro EVH
Analog output block
31
41
02
16-bit
-
Parâmetro EVM
Analog output block
32
41
02
16-bit
-
Parâmetro TEV
Analog output block
33
41
02
16-bit
-
Parâmetro HLOG
Analog output block
34
41
02
16-bit
-
Parâmetro TLOG Parâmetro RLOG
Analog output block
35
41
02
16-bit
-
0= Sem ação 1=Resetar log
Analog output block
36
41
02
16-bit
-
Parâmetro MES
Analog output block
37
41
02
16-bit
-
Parâmetro DIA
Analog output block
38
41
02
16-bit
-
Parâmetro ANO
Analog output block
39
41
02
16-bit
-
Parâmetro HORA
Analog output block
40
41
02
16-bit
-
Parâmetro MIN
Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10
23
Supervisor de Temperatura para Transformadores com Óleo TS Analog output block
41
41
02
16-bit
-
Parâmetro TCR1
Analog output block
42
41
02
16-bit
-
Parâmetro TCR2
Analog output block
43
41
02
16-bit
-
Parâmetro ATIV
Analog output block
44
41
02
16-bit
-
Parâmetro VIDA
Analog output block
45
41
02
16-bit
-
Parâmetro BALI
Analog output block
46
41
02
16-bit
-
Parâmetro ABAL
Analog output block
47
41
02
16-bit
-
Parâmetro LMAX
Analog output block
48
41
02
16-bit
-
Parâmetro LMIN
Analog output block
49
41
02
16-bit
-
Parâmetro KP
Analog output block
50
41
02
16-bit
-
Parâmetro KI
Analog output block
51
41
02
16-bit
-
Parâmetro KD
Analog output block
52
41
02
16-bit
-
Parâmetro CMIN
Analog output block
53…58
41
02
16-bit
-
Reservado
Analog output block
59
41
02
16-bit
-
Parâmetro PWD
Analog output block
60
41
02
16-bit
-
Parâmetro LINT
Analog output block
61
41
02
16-bit
-
Parâmetro STEP
Analog output block
62
41
02
16-bit
-
Parâmetro TREF
Analog output block
63
41
02
16-bit
-
Parâmetro VREF
Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10
24
Supervisor de Temperatura para Transformadores com Óleo TS Analog output block
64
41
02
16-bit
-
Analog input
0
30
04
Without flag
1x10
Temperatura óleo
Analog input
1
30
04
Without flag
1x10
Temperatura enrolamento
Analog input
2
30
04
Without flag
1x10
Temperatura RTD2
Analog input
3
30
04
Without flag
1x10
Temperatura RTD3
Analog input
4
30
04
Without flag
1x10
Temperatura máxima atingida pelo óleo
Analog input
5
30
04
Without flag
1x10
Temperatura máxima atingida pelo enrolamento
Analog input
6
30
04
Without flag
1x10
Temperatura máxima atingida pelo RTD2
Analog input
7
30
04
Without flag
1x10
Temperatura máxima atingida pelo RTD3
Analog input
8
30
04
Without flag
1x100
Gradiente Final de Temperatura GFN
Analog input
9
30
04
Without flag
1x10
Percentual de carga
Analog input
10
30
04
Without flag
1x100
Corrente lida no TC (A)
Analog input
11
30
04
Without flag
1x100
Corrente do transformador (kA)
Analog input
12
30
04
Without flag
1x100
Memória de erro
Analog input
13
30
04
Without flag
1x100
Ponteiro do Log
Analog input
14
30
04
Without flag
1x100
Reservado
Analog input
15
30
04
Without flag
1x100
Temperatura final do setpoint do primeiro estágio de resfriamento
Analog input
16
30
04
Without flag
1x100
Balanço de vida
Analog input
17
30
04
Without flag
1x100
Balanço de vida
Analog input
18
30
04
Without flag
1x100
Reservado
Analog input
19
30
04
Without flag
1x100
Reservado
Analog input
20
30
04
Without flag
1x100
Número de série 1
Analog input
21
30
04
Without flag
1x100
Número de série 2
Parâmetro HLV
Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10
25
Supervisor de Temperatura para Transformadores com Óleo TS Analog input
22
30
04
Without flag
1x100
Versão de firmware
Analog input
23
30
04
Without flag
1x100
Tempo de retardo de desligamento de enrolamento
Analog input
24
30
04
Without flag
1x100
Tempo de retardo de desligamento de óleo
Binary input
0
01
01
No status
-
Estado do Relé da R.F.1*
Binary input
1
01
01
No status
-
Estado do Relé da R.F.2*
Binary input
2
01
01
No status
-
Estado do Relé de Autodiagnóstico*
Binary input
3
01
01
No status
-
Estado do Relé programável 1*
Binary input
4
01
01
No status
-
Estado do Relé de programável 2*
Binary input
5
01
01
No status
-
Estado do Relé programável 3*
Binary input
6
01
01
No status
-
Estado do Relé de programável 4*
Binary input
8
01
01
No status
-
Erro de EEPROM*
Binary input
11
01
01
No status
-
Erro de overflow nas medições*
Binary input
12
01
01
No status
-
Não utilizado
Binary input
13
01
01
No status
-
Erro de leitura do TC externo*
Binary input
14
01
01
No status
-
Erro de leitura do AD*
Binary input
15
01
01
No status
-
Erro de salto na leitura de RTD’s*
Binary input
16
01
01
No status
-
Erro de calibração RTD1*
Binary input
17
01
01
No status
-
Erro de calibração RTD2*
Binary input
18
01
01
No status
-
Erro de calibração RTD3*
Binary input
19
01
01
No status
-
Não utilizado
Binary input
20
01
01
No status
-
Erro de leitura RTD1*
Binary input
21
01
01
No status
-
Erro de leitura RTD2*
Binary input
22
01
01
No status
-
Erro de leitura RTD3*
Binary input
23
01
01
No status
-
Não utilizado
Binary input
24
01
01
No status
-
Opcional RTDs adicionais*
Binary input
25
01
01
No status
-
Opcional Saída Analógica*
Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10
26
Supervisor de Temperatura para Transformadores com Óleo TS Binary input
26
01
01
No status
-
Opcional Porta Serial RS485*
Binary input
27
01
01
No status
-
Não utilizado
Binary input
28
01
01
No status
-
Opcional Memória de Massa*
Binary input
29
01
01
No status
-
Opcional Pré-resfriamento*
Binary input
30
01
01
No status
-
Opcional Exercício de ventiladores*
Binary input
31
01
01
No status
-
Opcional PID
Binary input
32
01
01
No status
-
Alarme de enrolamento
Binary input
33
01
01
No status
-
Alarme de óleo
Binary input
34
01
01
No status
-
Desligamento de enrolamento
Binary input
35
01
01
No status
-
Desligamento de óleo
Binary input
36
01
01
No status
-
Alarme por envelhecimento acumulado
Binary input
37...39
01
01
No status
-
Reservado
Binary input
40
01
01
No status
-
Erro de EEPROM**
Binary input
41...42
01
01
No status
-
Reservado
Binary input
43
01
01
No status
-
Erro de overflow nas medições**
Binary input
44
01
01
No status
-
Reservado
Binary input
45
01
01
No status
-
Erro de leitura do TC externo**
Binary input
46
01
01
No status
-
Erro de leitura do AD**
Binary input
47
01
01
No status
-
Erro de salto na leitura de RTD’s**
Binary input
48
01
01
No status
-
Erro de calibração RTD1**
Binary input
49
01
01
No status
-
Erro de calibração RTD2**
Binary input
50
01
01
No status
-
Erro de calibração RTD3**
Binary input
51
01
01
No status
-
Não utilizado
Binary input
52
01
01
No status
-
Erro de leitura RTD1**
Binary input
53
01
01
No status
-
Erro de leitura RTD2**
Binary input
54
01
01
No status
-
Erro de leitura RTD3**
Binary input
55
01
01
No status
-
Não utilizado
Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10
27
Supervisor de Temperatura para Transformadores com Óleo TS Binary input
56
01
01
No status
-
Ativo energizado
* Os itens marcados com um asterisco (*) estão disponíveis no objeto Class 1 ** Encontrados na memória de erros do equipamento
Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10
28
Supervisor de Temperatura para Transformadores com Óleo TS
BRASIL Treetech Sistemas Digitais Ltda Praça Claudino Alves, 141, Centro CEP 12.940-000 - Atibaia/SP + 55 11 2410-1190
[email protected] www.treetech.com.br
REPRESENTANTES/ DISTRIBUIDORES INTERNACIONAIS AMÉRICA DO SUL
AMÉRICA DO NORTE
CHILE - Santiago INMOHA +56 2531-7986
[email protected]
ESTADOS UNIDOS DA AMÉRICA - Portland
PARAGUAI - Asunción Enertec +595 21 214 814
[email protected]
MÉXICO - Hidalgo MCT +52 779 796 4286
[email protected]
PERU - Lima Logytec +511 452 3111
[email protected] COLÔMBIA - Medellín Enersafe S.A +57 4 604 32 72
[email protected]
TechSales +1 503 345 9710
[email protected]
ÁSIA ÍNDIA - Raipur Global Technology +91 98261 22000
[email protected]
OCEANIA AUSTRÁLIA/NOVA ZELÂNDIA - Melbourne Martec Asset Solutions +61 (0)430 149 665
[email protected] EUROPA PORTUGAL - Linda a Velha Trafotech +351 214 146 740
[email protected] NORUEGA - Hokksund EB Elektro +47 31 01 37 00
[email protected]
Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10