Supervisor de Temperatura para Transformadores com Óleo TS

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10

1

Supervisor de Temperatura para Transformadores com Óleo TS SUMÁRIO

1

ASSISTÊNCIA TÉCNICA .................................................................................. 3

2 HISTÓRICO DE REVISÕES............................................................................... 3 3

PROTOCOLO MODBUS RTU ............................................................................. 4

4 PROTOCOLO DNP 3.0 .................................................................................... 9

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10

2

Supervisor de Temperatura para Transformadores com Óleo TS 1

Assistência Técnica

As informações deste documento permitem que todas as leituras, seleções e comandos do TS sejam efetuados por meio da porta de comunicação serial RS485 (opcional). Estão disponíveis os protocolos Modbus RTU e DNP3.0 nível 1. Para obter assistência técnica para o TS ou qualquer outro produto Treetech, entre em contato através do endereço abaixo: Treetech Sistemas Digitais Ltda. – Assistência Técnica Rua José Alvim, 100 – Salas 03 e 04 – Centro Atibaia – São Paulo – Brasil CEP: 12.940-800 CNPJ: 74.211.970/0002-53 IE: 190.159.742.110 TEL: +55 (11) 2410-1190 x201 FAX: +55 (11) 2410-1190 x702 Email: [email protected] Site: http://www.treetech.com.br

2

Histórico de Revisões

Revisão

Data

Descrição

1.00

31/07/2015

Emissão Inicial

1.10

03/11/2015

Atualização para o firmware 1.13

Feito por João Victor Miranda João Victor Miranda

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10

3

Supervisor de Temperatura para Transformadores com Óleo TS 3

Protocolo Modbus RTU

Protocolo: Modo: Taxa de transmissão: Bits de dados: Bits de parada: Paridade: Tipo de variável de memória:

Modbus RTU (binário) 4.800, 9.600, 19.200 ou 38.400, 57.600 ou 115.200bps 8 2 Nenhuma Holding Registers 03 (Leitura, em blocos ou individualmente)

Comandos implementados:

06 (Escrita em um único registrador)

Base de Endereçamento: Aplicável à versão de firmware:

16 (Escrita em um bloco de registradores) Base 1 (PLC Address): O endereço dos dados inicia em 1 1.13

Registrador

Bit

01

-

02

-

03

-

04

-

05

Mapa de Registradores TS (Versão 1.13) Descrição Faixa de Medição ou Estado

Passo

Escrita ou Leitura

-55...200

1

E/L

-55...200

1

E/L

0...20

0,1

E/L

-55...200

1

E/L

-

Parâmetro ALMO Parâmetro DSLO Parâmetro RDSO Parâmetro ALME Parâmetro DSLE

-55...200

1

E/L

06 07

-

Parâmetro RDSE Parâmetro IDI

0,1 1

E/L E/L

08 09

-

Parâmetro RTDS Parâmetro DISP

1 1

E/L E/L

10 11 12

-

Parâmetro ALO Parâmetro DSO Parâmetro ALE

0...20 0= Português 1= Inglês 2= Espanhol 1...3 0= Fixo 1= rolagem 2= Máxima 0...4 0...4 0...4

1 1 1

E/L E/L E/L

13 14

0

Parâmetro DSE Parâmetro RL1

-

E/L E/L

1

Parâmetro RL2

-

E/L

2

Parâmetro RL3

-

E/L

3

Parâmetro RL4

0...4 0 = Normal 1 = Invertido 0 = Normal 1 = Invertido 0 = Normal 1 = Invertido 0 = Normal 1 = Invertido

-

E/L

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10

4

Supervisor de Temperatura para Transformadores com Óleo TS 15

-

Parâmetro VSAN

16

-

Parâmetro FSAN

17 18 19 20 21 22 23

-

Parâmetro FESA Parâmetro IESA Parâmetro GEO Parâmetro TE Parâmetro HS+ Parâmetro HS* Parâmetro 2*M

24 25 26 27 28 29

-

Parâmetro CNT Parâmetro CNS Parâmetro RF1 Parâmetro RF2 Parâmetro HIS Parâmetro ALT

30 31 32 33 34 35 36

-

37

-

38

-

39 40 41 42

-

43 44

-

45

-

Parâmetro CV1 Parâmetro CV2 Parâmetro HIC Parâmetro EVH Parâmetro EVM Parâmetro TEV Parâmetro HLOG Parâmetro TLOG Parâmetro RLOG Parâmetro MES Parâmetro DIA Parâmetro ANO Parâmetro HORA Parâmetro MIN Modo de operação do grupo de resfriamento RF1 Modo de operação do grupo de

-

0= Óleo 1= Enrol. 2= RTD2 3= RTD3 4= Máxima 0= 0-1mA 1= 0-5mA 2= 0-10mA 3= 0-20mA 4= 4-20mA -55...200 -55...200 -50...50 1...999 0...20 1...1,50 0=1.6 1=1.8 2=2.0 0...99,98 0...10 -55...200 -55...200 0...9 0 = desligado 1 = ligado 10...200 10...200 1...9 0...23 0...59 1...100 1...20

1

E/L

1

E/L

1 1 1 1 0,1 0,01 -

E/L E/L E/L E/L E/L E/L E/L

0,01 0,01 1 1 1

E/L E/L E/L E/L E/L E/L

1 1 1

E/L E/L E/L E/L

1 1

E/L E/L

1...120

1

E/L

0= Sem ação 1=Resetar log 1...12 1...31 05...99 0..23

-

E/L

-

E/L E/L E/L E/L

0...59 0=automático 1 =manual

-

E/L E/L

0=automático 1 =manual

-

E/L

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10

5

Supervisor de Temperatura para Transformadores com Óleo TS

46

-

47

-

resfriamento RF2 Reset memória de erros Parâmetro TCR1

48

-

Parâmetro TCR2

49

-

Parâmetro ATIV

50 51 52 53

-

54

-

55 56 57 58…69 1001

-

1002

-

1003

-

1004

-

1005

-

1006

-

1007

-

1008

-

1009

-

1010

-

1011

-

Parâmetro VIDA Parâmetro BALI Parâmetro ABAL Parâmetro LMAX Parâmetro LMIN Parâmetro KP Parâmetro KI Parâmetro KD Reservado Temperatura óleo Temperatura enrolamento Temperatura RTD2 Temperatura RTD3 Temperatura máxima atingida pelo óleo Temperatura máxima atingida pelo enrolamento Temperatura máxima atingida pelo RTD2 Temperatura máxima atingida pelo RTD3 Gradiente Final de Temperatura (GFN) Percentual de carga (%) Corrente lida nosecundário do TC (AMP)

0=off 1=reset 0=óleo 1=enrolamento 0=óleo 1=enrolamento 0=off 1=on 2=automático 1…60 -999…999 0…999 0…200

-

E/L

-

E/L

-

E/L

-

E/L

1 1 1 1

E/L E/L E/L E/L

0…200

1

E/L

0…9,999 0…9,999 0…9,999 -55...200

0,001 0,001 0,001 0,1

E/L E/L E/L E/L L

-55...200

0,1

L

-55...200

0,1

L

-55...200

0,1

L

-55...200

0,1

L

-55...200

0,1

L

-55...200

0,1

L

-55...200

0,1

L

-55...55

0,01

L

0...100

0,1

L

0...10

0,01

L

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10

6

Supervisor de Temperatura para Transformadores com Óleo TS 1012

-

4

Corrente do transformador (kA) Estado do Relé da R.F.1 Estado do Relé da R.F.2 Estado do Relé de Autodiagnóstico Estado do Relé 1

1013

0

5

Estado do Relé 2

6

Estado do Relé 3

7

Estado do Relé 4

1014

-

1015

0

Variável de erros Opcional RTDs adicionais Opcional Saída Analógica Opcional Comunicação Serial RS485 Não utilizado Opcional Memória de Massa Opcional Préresfriamento Opcional Exercício de ventiladores Não utilizado Alarme temperatura do enrolamento Alarme temperatura do óleo Desligamento temperatura do enrolamento Desligamento temperatura do óleo Não utilizado Não utilizado Não utilizado Não utilizado Ponteiro do LOG Reservado

1 2

1 2

3 4

5 6

1016

7 0

1

2

3

1017 1018

4 5 6 7 -

0...99,98

0,01

L

0 = desligado 1 = ligado 0 = desligado 1 = ligado 0 = desligado 1 = ligado

-

L

-

L

-

L

0 = desligado 1 = ligado 0 = desligado 1 = ligado 0 = desligado 1 = ligado 0 = desligado 1 = ligado *

-

L

-

L

-

L

-

L

-

L

0 =não disp. 1 =disponível 0 =não disp. 1 =disponível 0 =não disp. 1 =disponível

-

L

-

L

-

L

0 =não disp. 1 =disponível

-

L L

0 =não disp. 1 =disponível 0 =não disp. 1 =disponível

-

L

-

L

0= não atuado 1= atuado

-

L L

0= não atuado 1= atuado

-

L

0= não atuado 1= atuado

-

L

0= não atuado 1= atuado

-

L

2000...16384 -

-

L L L L L L

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10

7

Supervisor de Temperatura para Transformadores com Óleo TS 1019

-

1020

-

1021

-

1022

-

1023

-

1024 1025

-

1026

-

1027

-

1028

-

Memória de autodiagnóstico Valor de carga em relação ao parâmetro CMIN Valor novo para acionamento do primeiro estágio Balanço de vida – parte alta Balanço de vida - parte baixa Reservado Número de série 1 Número de série 2 Tempo de retardo para desligamento de enrolamento Tempo de retardo para desligamento de óleo

Em dias na tela de consulta, em segundos no registrador Em dias na tela de consulta, em segundos no registrador

-

L

-

L

-

L

-

L

-

L

-

L

-

L

-

L

-

L

Observações: * O valor informado corresponde ao mesmo código de erro apresentado no display do TS em formato hexadecimal.

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10

8

Supervisor de Temperatura para Transformadores com Óleo TS 4

Protocolo DNP 3.0

DNP V3.0 DEVICE PROFILE DOCUMENT

This document is accompanied by table 1, Supported DNP 3.0 Objects, Function Codes, and Qualifiers, and table 2, Point List.

Vendor Name: TreeTech Sistemas Digitais

Device Name: Supervisor de Temperatura TS Highest DNP Level Supported:

For Requests: Level 1

Device Function:

Master

Remote

For Responses: ______

Notable Objects, functions, and/or qualifiers supported in addition to highest DNP Levels Supported: 

Reads of Binary Inputs (Object 01, Variation 01, Qualifier 00, 01 and 06)



Reads of 16-bit Analog Inputs (Object 30, Variation 04, Qualifier 00, 01 and 06)

GENERAL INFORMATION: Maximum Data Link Frame Size (octets):

Maximum Application Frame Size (octets):

Transmitted: 292

Transmitted: 500

Received: (must be 292)

Received: 200

Maximum Data Link Re-tries:

Maximum Application Layer Re-tries:

None

None

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10

9

Supervisor de Temperatura para Transformadores com Óleo TS Fixed at ___

Configurable, range ___ to ___

Configurable, range 0 to 255

(Fixed is not permitted)

Requires Data Link Layer Confirmation:

Never Always Sometimes If Sometimes, when? ______________________________ Configurable as: __________________________________________ Requires Application Layer Confirmation:

Never Always (Not recommended) When reporting Event Data (Slave devices only) When sending mult-fragment responses (Slave devices only) Sometimes: If ‘Sometimes’, when? __________________________________________ Configurable: If ‘Configurable’, how? _________________________________________ Timeouts while waiting for:

Fixed at _____

Variable

Configurable*

None

Fixed at _____

Variable

Configurable*

Application Confirm:

None

Fixed at _____

Variable

Configurable*

Complete Appl. Response:

None

Fixed at _____

Variable

Configurable*

Data link confirm:

None

Complete Appl. Fragment:

Others: ______________________________________________________________________ *Attach explanation if ‘Variable’ or ‘Configurable’ was checked for any timeout

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10

10

Supervisor de Temperatura para Transformadores com Óleo TS Sends/Executes Control Operations:

WRITE Binary Outputs:

Never

Always

Sometimes

Configurable

SELECT/OPERATE:

Never

Always

Sometimes

Configurable

DIRECT OPERATE:

Never

Always

Sometimes

Configurable

DIRECT OPERATE-No ACK:

Never

Always

Sometimes

Configurable

Count > 1:

Never

Sometimes

Configurable

Pulse On:

Never

Sometimes

Configurable

Pulse Off:

Never

Sometimes

Configurable

Latch On:

Never

Always

Sometimes

Configurable

Latch Off:

Always

Sometimes

Configurable

Never

Queue:

Never

Always

Sometimes

Configurable

Clear Queue:

Never

Always

Sometimes

Configurable

Always Always Always

Attach explanation if 'Sometimes' or 'Configurable' was checked for any operation. FILL OUT THE FOLLOWING ITEM FOR MASTER DEVICES ONLY: Expects Binary Input Change Events:

Either time-tagged or non-time-tagged for a single event. Both time-tagged and non-time-tagged for a single event. Configurable (Attach explanation)

FILL OUT THE FOLLOWING ITEMS FOR REMOTE DEVICES ONLY: Default Status Object/Variation:

Default Analog Object/Variation:

No Status objects reported

No Analog objects reported

Configurable (attach explanation)

Configurable (attach explanation)

Default Static Object_____________

Default Static Object______________

Default Static Variation __________

Default Static Variation ___________

Default Event Object_____________

Default Event Object______________

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10

11

Supervisor de Temperatura para Transformadores com Óleo TS Default Event Variation __________

Default Event Variation ___________

Point-by-point list attached

Point-by-point list attached

Default Counter Object/Variation:

Counters Roll Over at:

No Counters reported

No Counters Reported

Configurable (attach explanation)

Configurable (attach explanation)

Default Static Object____________

16 Bits

Default Static Variation__________

32 Bits

Default Event Object____________

Other Value _________

Default Event Variation _________

Point-by-point list attached

Point-by-point list attached

Default Frozen Counter Object/Variation:

Counters frozen by means of:

No Frozen Counters reported

No Frozen Counters reported

Configurable (attach explanation)

Remote device time based

Default Static Object____________

Fixed time

Default Static Variation__________

Configurable; range _____ to _____

Default Event Object____________

Master Request (see implementation table)

Default Event Variation __________

Both

Point-by-point list attached

Analog Deadbands:

Configuring Analog Deadbands:

Fixed

Not Applicable

Configurable: ____

Configuration Software

Per Point

Using Object 34 from the master station

Per Analog Type

Both configuration software and Object 34

Global

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10

12

Supervisor de Temperatura para Transformadores com Óleo TS

Are the updated deadband values preserved through a device reset:

YES NO

The number of multiple objects allowed in a single read request message:

Number of multiple objects allowed: 3

Ability to DISABLE/ENABLE DNP database points:

IIN 1-6 Device Trouble Bit:

Not Applicable

Never used

Per point

Reason for setting:

Per object Global

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10

13

Supervisor de Temperatura para Transformadores com Óleo TS Time Sync Information:

Time Sync Period:

Never Fixed at ______ seconds Configurable, range ______ to _______ seconds Only at IED startup

a) Maximum time base drift over a 10 minute interval:

_________ ms

b) Maximum Internal Time Reference Error when set via DNP: _________ ms c) Maximum Delay Measurement error:

_________ ms

d) Maximum Response time:

_________ ms

e) Event data time-tag error – if different than ( c ) : Binary Input Change Events

_________ ms

Counter Change Events

__________ ms

Frozen Counter Change Events

__________ ms

Analog Change Events

__________ ms

Frozen Analog Change Events

__________ ms

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10

14

Supervisor de Temperatura para Transformadores com Óleo TS Sends/Executes Digital Control Operations:

SELECT/OPERATE*

Never

Always

Sometimes

Configurable

DIRECT OPERATE*

Never

Always

Sometimes

Configurable

DIRECT OPERATE – NO ACK*

Never

Always

Sometimes

Configurable

*Attach explanation if ‘Sometimes’ or ‘Configurable’ was checked for any operation. *To support control operations and conform to the Subset Definitions, either ‘Always’ or ‘Configurable’ must be selected.

Count > 1

Never

Always

Sometimes

Configurable

Pulse On

Never

Always

Sometimes

Configurable

Pulse Off

Never

Always

Sometimes

Configurable

Latch On

Never

Always

Sometimes

Configurable

Latch Off

Never

Always

Sometimes

Configurable

Trip/Close

Never

Always

Sometimes

Configurable

Raise/Lower

Never

Always

Sometimes

Configurable

Queue

Never

Always

Sometimes

Configurable

Clear Queue

Never

Always

Sometimes

Configurable

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10

15

Supervisor de Temperatura para Transformadores com Óleo TS Sends/Executes Analog Control Operations:

SELECT/OPERATE*

Never

Always

Sometimes

Configurable

DIRECT OPERATE*

Never

Always

Sometimes

Configurable

DIRECT OPERATE – NO ACK*

Never

Always

Sometimes

Configurable

*Attach explanation if ‘Sometimes’ or ‘Configurable’ was checked for any operation. *To support control operations and conform to the Subset Definitions, either ‘Always’ or ‘Configurable’ must be selected.

Queue

Never

Always

Sometimes

Configurable

Clear Queue

Never

Always

Sometimes

Configurable

The maximum number of objects supported in a single control request for objects 12 and 41.

Number of objects allowed for object 12: 1 Number of objects allowed for object 41: 1

Control Points per address:

Configurable 1 control point per address 2 control points per address

Maximum Select/Execute Delay Time:

Do all indices support the same control codes:

YES – Controls codes 3 and 4 NO – attached points list stating configuration ability and supported control codes per point or group of points

Ability for REMOTE/LOCAL control mode:

Not Applicable

Not Applicable

Fixed at _____ seconds

Per point

Configurable, range ______ to ______ seconds

Per object

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10

16

Supervisor de Temperatura para Transformadores com Óleo TS Global

Sends Unsolicited Responses:

Sends Static Data in Unsolicited Responses:

Never

Never

Configurable (attach explanation)

When Device Restarts

Only certain objects

When Status Flags Change

Sometimes (attach explanation) *No other options permitted. ENABLE/DISABLE Unsolicited:

Minimum number of events and/or minimum time before transmission of an unsolicited message.

Not Supported Configurable

# of events:__________

Function codes 20,21 supported

min. amount of time(msec) :___________

Assign Class Function code supported:

Is the Event Buffer size configurable:

NO

NO fixed size: _______

YES

YES: range: _________to_________

Per Object Per Point

Configurable Per Class buffer:

Configurable NO YES Are the updated ENABLE/DISABLE unsolicited settings Are the updated Assign Class settings saved through a saved through a device reset: device reset:

YES

YES

NO

NO

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10

17

Supervisor de Temperatura para Transformadores com Óleo TS Supports Collision Avoidance:

Never Always (attach explanation) Configurable (attach explanation)

Source Address Filtering:

Not Supported Configurable (attach explanation)

Supports Multi-drop communications:

Yes

No

Sends Multi-Fragment Responses:

Yes

No

Tabela 1: Supported DNP 3.0 Objects, Function Codes, and Qualifiers REQUESTS

RESPONSES

(slave will parse)

(master must parse)

OBJECTS

Object

Variation

Function

Qualifier

Function

Qualifier

Codes

Codes(hex)

Codes

Codes(hex)

Description

01

02

Binary Input with flag

01

00, 06

00, 129

00, 01

10

02

Binary Output

01, 02

00, 06

00, 129

00, 01

12

01

Control Relay Output Block

05, 06

17, 28

00, 129

Echo

30

02

16 bit Analog Input with flag

01

06

00, 129

00, 01

40

02

16 bit Analog Output Status

01

06

00, 129

00, 01

41

02

16-bit Analog Output Block

05, 06

17, 28

00, 129

Echo

50

01

Time and Date – Absolute time

01, 02

07

01, 02

07

60

01

Class 0 Data

01

06

129

00, 01

60

02

Class 1 Data

01

06

129

00, 01

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10

18

Supervisor de Temperatura para Transformadores com Óleo TS 60

03

Class 2 Data

01

06

129

00, 01

60

04

Class 3 Data

01

06

129

00, 01

80

01

Internal Indications

02

00, index=7

129

-

-

-

Cold Restart

13

-

129

-

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10

19

Supervisor de Temperatura para Transformadores com Óleo TS

Table 2: Point List

Description Binary output

Index 0…2

Default Static / Event Variation

Scale

Point Name

Object

Var.

Description

12

01

No status

Reservado

Binary output

3

12

01

No status

-

Modo de operação do Relé programável 1. 0=Normal / 1=Invertido

Binary output

4

12

01

No status

-

Modo de operação do Relé programável 2. 0=Normal / 1=Invertido

Binary output

5

12

01

No status

-

Modo de operação do Relé programável 3. 0=Normal / 1=Invertido

Binary output

6

12

01

No status

-

Modo de operação do Relé programável 4. 0=Normal / 1=Invertido

Binary output

7

12

01

No status

-

Reservado

Binary output

8

12

01

No status

-

Parâmetro ALT. 0=Desliga / 1= Liga

Binary output

9…15

12

01

No status

-

Reservado

Binary output

16

12

01

No status

-

Modo de operação do grupo RF1 0=Automático / 1=Manual

Binary output

17…23

12

01

No status

-

Reservado

Binary output

24

12

01

No status

-

Modo de operação do grupo RF2 0=Automático / 1=Manual

Binary output

25…31

12

01

No status

-

Reservado

Binary output

32

12

01

No status

-

Reset Memória de erros

Binary output

33…39

12

01

No status

-

Reservado

Binary output

40

12

01

No status

-

Reset temperatura máxima óleo

Binary output

41

12

01

No status

-

Reset temperatura máxima Enrolamento

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10

20

Supervisor de Temperatura para Transformadores com Óleo TS Binary output

42

12

01

No status

-

Reset temperatura máxima RTD2

Binary output

43

12

01

No status

-

Reset temperatura máxima RTD3

Analog output block

0

41

02

16-bit

-

Parâmetro ALMO

Analog output block

1

41

02

16-bit

-

Parâmetro DSLO

Analog output block

2

41

02

16-bit

1x10

Parâmetro RDSO

Analog output block

3

41

02

16-bit

-

Parâmetro ALME

Analog output block

4

41

02

16-bit

-

Parâmetro DSLE

Analog output block

5

41

02

16-bit

1x10

Parâmetro RDSE Parâmetro IDI

Analog output block

0= Português 6

41

02

16-bit

1= Inglês 2= Espanhol

Analog output block

7

41

02

16-bit

-

Parâmetro RTDS Parâmetro DISP

Analog output block

0= Fixo 8

41

02

16-bit

1= rolagem 2= Máxima

Analog output block

9

41

02

16-bit

-

Parâmetro ALO

Analog output block

10

41

02

16-bit

-

Parâmetro DSO

Analog output block

11

41

02

16-bit

-

Parâmetro ALE

Analog output block

12

41

02

16-bit

-

Parâmetro DSE

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10

21

Supervisor de Temperatura para Transformadores com Óleo TS Parâmetro VSAN 0= Óleo Analog output block

1= Enrolamento 13

41

02

16-bit

2= RTD2 3= RTD3 4= Máxima Parâmetro FSAN 0= 0-1mA

Analog output block

1= 0-5mA 14

41

02

16-bit

2= 0-10mA 3= 0-20mA 4= 4-20mA

Analog output block

15

41

02

16-bit

-

Parâmetro FESA

Analog output block

16

41

02

16-bit

-

Parâmetro IESA

Analog output block

17

41

02

16-bit

1x10

Parâmetro GEO

Analog output block

18

41

02

16-bit

-

Analog output block

19

41

02

16-bit

1x10

Parâmetro HS+

Analog output block

20

41

02

16-bit

1x100

Parâmetro HS*

Parâmetro TE

Parâmetro 2*M Analog output block

0=1.6 21

41

02

16-bit

1=1.8 2=2.0

Analog output block

22

41

02

16-bit

1x100

Parâmetro CNT

Analog output block

23

41

02

16-bit

1x100

Parâmetro CNS

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10

22

Supervisor de Temperatura para Transformadores com Óleo TS Analog output block

24

41

02

16-bit

-

Parâmetro RF1

Analog output block

25

41

02

16-bit

-

Parâmetro RF2

Analog output block

26

41

02

16-bit

-

Parâmetro HIS

Analog output block

27

41

02

16-bit

-

Parâmetro CV1

Analog output block

28

41

02

16-bit

-

Parâmetro CV2

Analog output block

29

41

02

16-bit

-

Parâmetro HIC

Analog output block

30

41

02

16-bit

-

Parâmetro EVH

Analog output block

31

41

02

16-bit

-

Parâmetro EVM

Analog output block

32

41

02

16-bit

-

Parâmetro TEV

Analog output block

33

41

02

16-bit

-

Parâmetro HLOG

Analog output block

34

41

02

16-bit

-

Parâmetro TLOG Parâmetro RLOG

Analog output block

35

41

02

16-bit

-

0= Sem ação 1=Resetar log

Analog output block

36

41

02

16-bit

-

Parâmetro MES

Analog output block

37

41

02

16-bit

-

Parâmetro DIA

Analog output block

38

41

02

16-bit

-

Parâmetro ANO

Analog output block

39

41

02

16-bit

-

Parâmetro HORA

Analog output block

40

41

02

16-bit

-

Parâmetro MIN

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10

23

Supervisor de Temperatura para Transformadores com Óleo TS Analog output block

41

41

02

16-bit

-

Parâmetro TCR1

Analog output block

42

41

02

16-bit

-

Parâmetro TCR2

Analog output block

43

41

02

16-bit

-

Parâmetro ATIV

Analog output block

44

41

02

16-bit

-

Parâmetro VIDA

Analog output block

45

41

02

16-bit

-

Parâmetro BALI

Analog output block

46

41

02

16-bit

-

Parâmetro ABAL

Analog output block

47

41

02

16-bit

-

Parâmetro LMAX

Analog output block

48

41

02

16-bit

-

Parâmetro LMIN

Analog output block

49

41

02

16-bit

-

Parâmetro KP

Analog output block

50

41

02

16-bit

-

Parâmetro KI

Analog output block

51

41

02

16-bit

-

Parâmetro KD

Analog output block

52

41

02

16-bit

-

Parâmetro CMIN

Analog output block

53…58

41

02

16-bit

-

Reservado

Analog output block

59

41

02

16-bit

-

Parâmetro PWD

Analog output block

60

41

02

16-bit

-

Parâmetro LINT

Analog output block

61

41

02

16-bit

-

Parâmetro STEP

Analog output block

62

41

02

16-bit

-

Parâmetro TREF

Analog output block

63

41

02

16-bit

-

Parâmetro VREF

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10

24

Supervisor de Temperatura para Transformadores com Óleo TS Analog output block

64

41

02

16-bit

-

Analog input

0

30

04

Without flag

1x10

Temperatura óleo

Analog input

1

30

04

Without flag

1x10

Temperatura enrolamento

Analog input

2

30

04

Without flag

1x10

Temperatura RTD2

Analog input

3

30

04

Without flag

1x10

Temperatura RTD3

Analog input

4

30

04

Without flag

1x10

Temperatura máxima atingida pelo óleo

Analog input

5

30

04

Without flag

1x10

Temperatura máxima atingida pelo enrolamento

Analog input

6

30

04

Without flag

1x10

Temperatura máxima atingida pelo RTD2

Analog input

7

30

04

Without flag

1x10

Temperatura máxima atingida pelo RTD3

Analog input

8

30

04

Without flag

1x100

Gradiente Final de Temperatura GFN

Analog input

9

30

04

Without flag

1x10

Percentual de carga

Analog input

10

30

04

Without flag

1x100

Corrente lida no TC (A)

Analog input

11

30

04

Without flag

1x100

Corrente do transformador (kA)

Analog input

12

30

04

Without flag

1x100

Memória de erro

Analog input

13

30

04

Without flag

1x100

Ponteiro do Log

Analog input

14

30

04

Without flag

1x100

Reservado

Analog input

15

30

04

Without flag

1x100

Temperatura final do setpoint do primeiro estágio de resfriamento

Analog input

16

30

04

Without flag

1x100

Balanço de vida

Analog input

17

30

04

Without flag

1x100

Balanço de vida

Analog input

18

30

04

Without flag

1x100

Reservado

Analog input

19

30

04

Without flag

1x100

Reservado

Analog input

20

30

04

Without flag

1x100

Número de série 1

Analog input

21

30

04

Without flag

1x100

Número de série 2

Parâmetro HLV

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10

25

Supervisor de Temperatura para Transformadores com Óleo TS Analog input

22

30

04

Without flag

1x100

Versão de firmware

Analog input

23

30

04

Without flag

1x100

Tempo de retardo de desligamento de enrolamento

Analog input

24

30

04

Without flag

1x100

Tempo de retardo de desligamento de óleo

Binary input

0

01

01

No status

-

Estado do Relé da R.F.1*

Binary input

1

01

01

No status

-

Estado do Relé da R.F.2*

Binary input

2

01

01

No status

-

Estado do Relé de Autodiagnóstico*

Binary input

3

01

01

No status

-

Estado do Relé programável 1*

Binary input

4

01

01

No status

-

Estado do Relé de programável 2*

Binary input

5

01

01

No status

-

Estado do Relé programável 3*

Binary input

6

01

01

No status

-

Estado do Relé de programável 4*

Binary input

8

01

01

No status

-

Erro de EEPROM*

Binary input

11

01

01

No status

-

Erro de overflow nas medições*

Binary input

12

01

01

No status

-

Não utilizado

Binary input

13

01

01

No status

-

Erro de leitura do TC externo*

Binary input

14

01

01

No status

-

Erro de leitura do AD*

Binary input

15

01

01

No status

-

Erro de salto na leitura de RTD’s*

Binary input

16

01

01

No status

-

Erro de calibração RTD1*

Binary input

17

01

01

No status

-

Erro de calibração RTD2*

Binary input

18

01

01

No status

-

Erro de calibração RTD3*

Binary input

19

01

01

No status

-

Não utilizado

Binary input

20

01

01

No status

-

Erro de leitura RTD1*

Binary input

21

01

01

No status

-

Erro de leitura RTD2*

Binary input

22

01

01

No status

-

Erro de leitura RTD3*

Binary input

23

01

01

No status

-

Não utilizado

Binary input

24

01

01

No status

-

Opcional RTDs adicionais*

Binary input

25

01

01

No status

-

Opcional Saída Analógica*

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10

26

Supervisor de Temperatura para Transformadores com Óleo TS Binary input

26

01

01

No status

-

Opcional Porta Serial RS485*

Binary input

27

01

01

No status

-

Não utilizado

Binary input

28

01

01

No status

-

Opcional Memória de Massa*

Binary input

29

01

01

No status

-

Opcional Pré-resfriamento*

Binary input

30

01

01

No status

-

Opcional Exercício de ventiladores*

Binary input

31

01

01

No status

-

Opcional PID

Binary input

32

01

01

No status

-

Alarme de enrolamento

Binary input

33

01

01

No status

-

Alarme de óleo

Binary input

34

01

01

No status

-

Desligamento de enrolamento

Binary input

35

01

01

No status

-

Desligamento de óleo

Binary input

36

01

01

No status

-

Alarme por envelhecimento acumulado

Binary input

37...39

01

01

No status

-

Reservado

Binary input

40

01

01

No status

-

Erro de EEPROM**

Binary input

41...42

01

01

No status

-

Reservado

Binary input

43

01

01

No status

-

Erro de overflow nas medições**

Binary input

44

01

01

No status

-

Reservado

Binary input

45

01

01

No status

-

Erro de leitura do TC externo**

Binary input

46

01

01

No status

-

Erro de leitura do AD**

Binary input

47

01

01

No status

-

Erro de salto na leitura de RTD’s**

Binary input

48

01

01

No status

-

Erro de calibração RTD1**

Binary input

49

01

01

No status

-

Erro de calibração RTD2**

Binary input

50

01

01

No status

-

Erro de calibração RTD3**

Binary input

51

01

01

No status

-

Não utilizado

Binary input

52

01

01

No status

-

Erro de leitura RTD1**

Binary input

53

01

01

No status

-

Erro de leitura RTD2**

Binary input

54

01

01

No status

-

Erro de leitura RTD3**

Binary input

55

01

01

No status

-

Não utilizado

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10

27

Supervisor de Temperatura para Transformadores com Óleo TS Binary input

56

01

01

No status

-

Ativo energizado

* Os itens marcados com um asterisco (*) estão disponíveis no objeto Class 1 ** Encontrados na memória de erros do equipamento

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10

28

Supervisor de Temperatura para Transformadores com Óleo TS

BRASIL Treetech Sistemas Digitais Ltda Praça Claudino Alves, 141, Centro CEP 12.940-000 - Atibaia/SP + 55 11 2410-1190 [email protected] www.treetech.com.br

REPRESENTANTES/ DISTRIBUIDORES INTERNACIONAIS AMÉRICA DO SUL

AMÉRICA DO NORTE

CHILE - Santiago INMOHA +56 2531-7986 [email protected]

ESTADOS UNIDOS DA AMÉRICA - Portland

PARAGUAI - Asunción Enertec +595 21 214 814 [email protected]

MÉXICO - Hidalgo MCT +52 779 796 4286 [email protected]

PERU - Lima Logytec +511 452 3111 [email protected] COLÔMBIA - Medellín Enersafe S.A +57 4 604 32 72 [email protected]

TechSales +1 503 345 9710 [email protected]

ÁSIA ÍNDIA - Raipur Global Technology +91 98261 22000 [email protected]

OCEANIA AUSTRÁLIA/NOVA ZELÂNDIA - Melbourne Martec Asset Solutions +61 (0)430 149 665 [email protected] EUROPA PORTUGAL - Linda a Velha Trafotech +351 214 146 740 [email protected] NORUEGA - Hokksund EB Elektro +47 31 01 37 00 [email protected]

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10

29