Generator Under Voltage setting (1) values: Set point Time Delay Enable Fail class
Minimum value 40.0% 0.0 Sec Off Alarm
Maximum value 100.0% 100 Sec On Trip
Trip Set point 93.0%(10230 V) 15 sec On Alarm
Maximum value 100.0% 100 Sec On Trip
Trip Set point 90.0%(9900 V) 15 sec On Trip
Maximum value 120.0% 100 Sec On Trip
Trip Set point 106.0%(116600 V) 5 sec On Alarm
Maximum value 120.0% 100 Sec On Trip
Trip Set point 109.0%(11990 V) 5 sec On Trip
Generator Under Voltage setting (2) values: Set point Time Delay Enable Fail class
Minimum value 40.0% 0.0 Sec Off Alarm
Generator High Voltage setting (1) values: Set point Time Delay Enable Fail class
Minimum value 100.0% 0.0 Sec Off Alarm
Generator High Voltage setting (2) values: Set point Time Delay Enable Fail class
Minimum value 100.0% 0.0 Sec Off Alarm
Generator Under Frequency setting (1) values: Set point Time Delay Enable Fail class
Minimum value 100.0% 0.0 Sec Off Alarm
Maximum value 80.0% 100 Sec On Trip
Trip Set point 93.0%(46.5Hz) 10 sec On Alarm
Generator Under Frequency setting (2) values: Set point Time Delay Enable Fail class
Minimum value 100.0% 0.0 Sec Off Alarm
Maximum value 80.0% 100 Sec On Trip
Trip Set point 90.0%(45.0 Hz) 10 sec On Trip
Generator Over Frequency setting (1) values: Set point
Minimum value 100.0%
Maximum value 120.0%
Trip Set point 105.0%(52.5Hz)
Time Delay Enable Fail class
0.0 Sec Off Alarm
100 Sec On Trip
5 sec On Alarm
Maximum value 120.0% 100 Sec On Trip
Trip Set point 107.0%(53.5 Hz) 5 sec On Trip
Maximum value 200.0% 100 Sec On Trip
Trip Set point -3.0 %(780KW) 10 sec On Alarm
Maximum value 200.0% 100 Sec On Trip
Trip Set point -5.0 %(1300KW) 10 sec On Trip
Maximum value 200.0% 3200 Sec On Trip
Trip Set point 100.0% 5 sec On Alarm
Maximum value 200.0% 3200 Sec On Trip
Trip Set point 110.0% 5 sec On Trip
Maximum value 350.0% 3200 Sec On Trip
Trip Set point 200.0% 5 sec On Alarm
Generator Over Frequency setting (2) values: Set point Time Delay Enable Fail class
Minimum value 100.0% 0.0 Sec Off Alarm
Reverse Power setting (1) values: Set point Time Delay Enable Fail class
Minimum value 0.0% 0.0 Sec Off Alarm
Reverse Power setting (2) values: Set point Time Delay Enable Fail class
Minimum value 0.0% 0.0 Sec Off Alarm
Generator over current setting (1) values: Set point Time Delay Enable Fail class
Minimum value 50.0% 0.0 Sec Off Alarm
Generator over current setting (2) values: Set point Time Delay Enable Fail class
Minimum value 50.0% 0.0 Sec Off Alarm
Generator Short Circuit setting (1) values: Set point Time Delay Enable Fail class
Minimum value 150.0% 0.0 Sec Off Alarm
Generator Short Circuit setting (2) values
Set point Time Delay Enable Fail class
Minimum value 150.0% 0.0 Sec Off Alarm
Maximum value 350.0% 3200 Sec On Trip
Trip Set point 250.0% 1 sec On Trip
Maximum value 200.0% 3200 Sec On Trip
Trip Set point 100.0% 10 sec On Alarm
Maximum value 200.0% 3200 Sec On Trip
Trip Set point 110.0% 5 sec On Trip
Maximum value 150.0% 100 Sec On Trip
Trip Set point 50.0% 5 sec On Alarm
Maximum value 100.0% 100 Sec On Trip
Trip Set point 80.0% 5 sec On Trip
Generator Overload setting (1) values: Set point Time Delay Enable Fail class
Minimum value -200.0% 0.0 Sec Off Alarm
Generator Overload setting (2) values: Set point Time Delay Enable Fail class
Minimum value -200.0% 0.0 Sec Off Alarm
Loss of Excitation setting values: Set point Time Delay Enable Fail class
Minimum value 0.0% 0.0 Sec Off Alarm
Over Excitation setting values: Set point Time Delay Enable Fail class
Minimum value 0.0% 0.0 Sec Off Alarm
Negative Phase Sequence Current setting values: Set point Time Delay Enable Fail class
Minimum value 0.0% 0.2 Sec Off Alarm
Maximum value 100.0% 100 Sec On Trip GB
Trip Set point 10.0%In (0.28A) I sec 0.5 sec On Trip GB
Negative Phase Sequence Voltage setting values: Set point Time Delay Enable Fail class
Minimum value 1.0% 0.2 Sec Off Alarm
Bus Bar over Voltage setting (1) values:
Maximum value 100.0% 100 Sec On Trip GB
Trip Set point 5.0%(550V) 0.5 sec On Trip GB
Set point Time Delay Enable Fail class
Minimum value 100.0% 0.0 Sec Off Alarm
Maximum value 120.0% 100 Sec On Trip
Trip Set point 105.0%(11550 V) 5 sec On Alarm
Maximum value 120.0% 100 Sec On Trip
Trip Set point 107.0%(11770 V) 5 sec On Trip
Bus Bar over Voltage setting (2) values: Set point Time Delay Enable Fail class
Minimum value 100.0% 0.0 Sec Off Alarm
Differential relay setting values: Differential Current Set point: Minimum setting Maximum setting 4% 40 %
Trip Set point 10.2 %(0.53 A) I sec
Differential Current Time Delay Set point: Minimum setting Maximum setting Time delay 0 Sec 10 Sec 6.547 Sec
Stator Earth Fault relay setting values: Stator Earth Fault Set point: Minimum setting Maximum setting 10 % 110 %
Trip Set point 26 %(1.3 A) In
Stator Earth Fault Time Delay Set point: Minimum setting Maximum setting Time delay 0 Sec 5 Sec 1 Sec