7209 1700 - 12/2001 GB
Operating instructions for the ERC controller for Buderus wall-hung gas boilers
Read carefully before operation
For the user
Preface
Preface Important general application instruction Dear reader, This operating manual provides vital information concerning the "ERC" 1 controller and the operation of your Buderus wall-hung gas boiler. We reserve the right to make technical changes. Due to ongoing further developments, figures, functional steps and technical data may show slight deviations. With your support Our documents are regularly updated. Your suggestions for enhancements will help us keep the design and the documents user-friendly. Please feel free to contact us. Storage This operating manual includes important information concerning the safe, professional and economical use of Buderus wall-hung gas boilers. Always keep this manual near your installation. Imprint Manufacturer: Address:
Buderus Heiztechnik GmbH Justus-Kilian-Str. 1 D - 35573 Wetzlar Document type: Operating manual Production date: 01.12.2001
1. (Ecomatic room controller) We reserve the right to make changes based on technical enhancements.
2
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Document guide for the ERC controller • version 12/2001
Table of contents 1
Conformities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.1 Standards, directives and regulations . . . . . . . . . . . . . . . . . . . . . . . 5 1.2 Designation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2
Concerning this manual . . . . . . . . . . . . . . . . . . . . . . . . . 6 2.1 2.2 2.3 2.4
3
Safety instructions . . . . . . . . . Application instructions . . . . . . Tips concerning economical heating Definitions . . . . . . . . . . . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
6 7 7 8
Basic instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 3.1 Guarantee and liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 3.2 Obligations of buyer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 3.3 Allowable users . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4
Product description . . . . . . . . . . . . . . . . . . . . . . . . . . 11 4.1 4.2 4.3 4.4 4.5 4.6 4.7
5
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
11 11 11 12 14 14 15
Operating the basic functions . . . . . . . . . . . . . . . . . . . . . 16 5.1 5.2 5.3 5.4 5.5 5.6 5.7
6
Functions of the ERC controller . . . Intended use . . . . . . . . . . . . . Unprofessional use . . . . . . . . . . Operating elements, operating levels Default adjustment . . . . . . . . . . Danger zones. . . . . . . . . . . . . Technical data . . . . . . . . . . . .
Commission . . . . . . . . . . . . . . . . . . . . Adjusting the current day of the week and the time Selecting the operating mode . . . . . . . . . . . Programming the heating switchpoints . . . . . . Adjusting the target room-temperature . . . . . . Adjusting the water temperature . . . . . . . . . . Resetting to the default values . . . . . . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
. . . . . . .
16 17 18 19 21 23 24
Operating the special functions . . . . . . . . . . . . . . . . . . . . 25 6.1 6.2 6.3 6.4 6.5
Adjusting summer/winter time . . . . . . Holiday programme. . . . . . . . . . . . Heating pause . . . . . . . . . . . . . . Party mode . . . . . . . . . . . . . . . . Adjusting the summer/winter conversion
We reserve the right to make changes based on technical enhancements.
Document guide for the ERC controller • version 12/2001
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
. . . . .
25 25 26 27 28
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
3
Table of contents 7
Operating the plug-in modules . . . . . . . . . . . . . . . . . . . . . 29 7.1 7.2 7.3 7.4
8
Outdoor-temperature module AM 1.0 On-line module OM 1.0 . . . . . . . Hygrometer module HM 1.0 . . . . . Barometer module BM 1.0 . . . . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
. . . .
29 31 31 32
Calibrating the sensors . . . . . . . . . . . . . . . . . . . . . . . . . 33 8.1 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 8.2 Example of calibrating the room-temperature sensors . . . . . . . . . . . . . . 33
9
Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
10 Operating and display elements . . . . . . . . . . . . . . . . . . . . 35 11 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
We reserve the right to make changes based on technical enhancements.
4
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Document guide for the ERC controller • version 12/2001
Conformities 1
Conformities
1.1
Standards, directives and regulations
1
The construction and operating behaviour of the Buderus ERC controller as well as Buderus wall-hung gas boilers meet the ‘basic requirements for gas units directive 90/396/EEC’ and the standards DIN 4702-6, EN 483, EN 676 and EN 677. For an extensive list of all standards and directives taken into account, please see the installation and maintenance instructions of the subject wall-hung gas boiler.
1.2
Designation
F
The Buderus ERC controller and wall-hung gas boiler meet the basic requirements of the relevant standards and directives. Their conformity has been proven. The relevant documents have been deposited with the manufacturer.
We reserve the right to make changes based on technical enhancements.
Document guide for the ERC controller • version 12/2001
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
5
2
Concerning this manual
2
Concerning this manual
2.1
Safety instructions
2.1.1
Clarification of the symbols used in the safety instructions
This operating manual uses the following symbols as safety instructions for the user: a WARNING! This symbol indicates a threat to the health or life of personnel. Non-observance of such an instruction may lead to death or serious injury. ACAUTION! This symbol indicates risk of injury to the user. It provides important information concerning the professional handling of the wall-hung gas boiler. If these instructions are not observed, such may lead to functional faults in the wall-hung gas boiler and injury to the user. 2.1.2
Concerning the safety instructions
All the safety instructions in this installation and maintenance manual must observed. 2.1.3
Procedure if gas can be smelled
ADANGER! If gas is smelled near your wall-hung gas boiler or in your house, there is a risk of explosion and the occupants are in mortal danger. If you smell gas, follow the procedure below: - Extinguish any fires, open flames and/or cigarettes! - Avoid creating sparks! Do not use any electrical devices - not even your phone, wall sockets or doorbell! - Close the main gas shut-off valve! - Open all windows and doors! - Alert all other occupants and have them leave the building! - Go to a telephone far from the building concerned and call the gas company or specialized wall-hung gas boiler company!
We reserve the right to make changes based on technical enhancements.
6
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Document guide for the ERC controller • version 12/2001
Concerning this manual 2.2 2.2.1
Application instructions Clarification of the symbols used in the application instructions
This operating manual uses the following symbols as instructions for the user: J NOTE! This symbol provides general application tips and especially useful information. Such will help you to make optimal use of all device functions, save energy and be friendly to the environment. N EXCLUSION OF LIABILITY! This symbol refers to an exclusion from manufacturer liability that can be caused by faults or omissions on the part of the operating company or operator. GRECYCLING! This symbol refers to the correct reuse of the packing material and worn assemblies (divided into metal, plastic, etc.). D LITERATURE! This symbol provides information concerning further literature. V TOOL! This symbol refers to the use of the supplied special tools or provides other information concerning the correct use of tools and/or measuring devices.
2 2.3
Tips concerning economical heating
Money can be saved by employing well-considered and exact heating procedures that take into account when heating is actually required. Modern control technology guarantees optimal comfort at minimal energy consumption levels while its operation remains simple despite a multitude of technical options. Observe the following instructions to save energy and care for the environment. z Always ask for extensive instructions from your specialized heating professional. Inform yourself about anything that is not clear.
z Ask for the adjustment of an optimum heating characteristic for the special conditions in your house. z Use the operating manual of your wall-hung gas boiler installation. z Make sure your heating installation receives regular service. z In cold seasons, ventilation must be brief but copious. Prevent rooms from becoming cold. z Check the adjustment levels of the thermostat valves in the individual rooms. z Do not set the living room or water temperatures higher than required. z Check whether the factory programme (switching times and room temperatures) and the hot-water facility correspond to your usual way of life. If necessary, adapt the factory programme to your individual desires. z Use the adjustment possibilities of the summer/ winter conversion for the transition periods. z A comfortable room climate depends not only on the room temperature but also on the relative air humidity. The dryer the air is, the cooler the room will feel. Keep plants in the room to increase the relative air humidity. z Protect against frost. Deactivate the installation for longer standstill periods. Drain the water from the wall-hung gas boiler, the storage tank and the pipes of the wall-hung gas boiler installation. Frost will not pose a danger if the entire system is dry.
We reserve the right to make changes based on technical enhancements.
Document guide for the ERC controller • version 12/2001
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
7
2 2.4
Concerning this manual Definitions
Concept
Definition
Day mode/ operation
Target room temp. above 16 °C
Night mode
Target room temp. not above 16 °C, preset in the factory
Night reduction
See night mode
Reduced mode
See night mode
Winter mode
Room- and hot-water heating active
Summer mode
Only hot-water heater active
factory programme
Preset heating-mode week sequence with various heating periods and temperatures
Standard programme
See factory programme
Heating programme
Standard programme adapted to individual circumstances
UBA
Universal Burner Automatic unit; 'control centre' of the burner; installed directly at the heating installation
We reserve the right to make changes based on technical enhancements.
8
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Document guide for the ERC controller • version 12/2001
Basic instructions 3
Basic instructions
3.1
Guarantee and liability
Guarantee claims are conditional upon correct functional operation and maintenance. The manufacturer guarantees that all parts on delivery were faultless as far as material and workmanship were concerned. In principal, our General Terms and Conditions of Sale and Delivery shall apply. These will be available to the operating company as from the conclusion of the agreement or earlier. Guarantee and maintenance claims for personal and material injury shall be excluded if they can be traced back to one or more of the following causes: - Non-intended use of the wall-hung gas boiler
3
3.2
Obligations of buyer
J Observe the instructions in the operating manual! A basic condition for the safe handling and faultless operation of the wall-hung gas boiler is knowledge of the basic safety instructions and safety regulations. - The operating instructions and especially the safety instructions must be observed by all persons operating the wall-hung gas boiler Logamax. - Additionally observe all accident prevention rules and regulations that apply at the installation site.
- Unprofessional installation, commission, operation or maintenance of the wall-hung gas boiler
- The buyer must make sure that the operator is instructed in the operation and all safety-relevant aspects of the wall-hung gas boiler.
- Operation of the wall-hung gas boiler while safety devices are faulty or safety and protective devices have not been correctly installed or are non-operable
- The instructing party must establish and keep a protocol of the instructions carried out.
- Non-observation of the instructions in the technical documents with regard to transportation, storage, installation, operation, service and preparation of the wall-hung gas boiler and the ERC controller - Non-authorized structural changes to the wall-hung gas boiler - Faulty supervision of machine parts that are subject to wear - Repairs carried out unprofessionally - Catastrophic events due to the effects of foreign bodies and force majeure
N LIABILITY EXCLUSION! The manufacturer cannot be held liable for damaged caused by omissions from the instruction duties of the purchaser. AWARNING! The buyer is responsible for seeing that competent professional personnel have at their disposal the operating manual of the wall-hung gas boiler when handling the wall-hung gas boiler
N LIABILITY EXCLUSION! The manufacturer cannot be held liable for damage caused by operating failures or non-observance of the operating manual or inadequate service, maintenance or care.
We reserve the right to make changes based on technical enhancements.
Document guide for the ERC controller • version 12/2001
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
9
3
Basic instructions
3.3
Allowable users
3.3.1
Specialized personnel
‘Specialized personnel’ are persons: - who are familiar with the wall-hung gas boiler installation based on their professional occupation and experience, - who are familiar with the relevant official work-safety regulations, directives and generally recognized technical rules (for example VDE stipulations, DIN sheets) so that they can judge whether the relevant installation is in a work-safe condition. Specialized personnel should be asked to give their objective opinion as seen from the viewpoint of safety on the job, unaffected by commercial or economic conditions. 3.3.2
Lay personnel
‘Lay persons’ are persons who are not a specialized professional. Lay persons may use the Buderus wallhung gas boiler without limitation; however, they may not carry out any activities connected with the wall-hung gas boiler’s installation, ignition, maintenance or removal.
We reserve the right to make changes based on technical enhancements.
10
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Document guide for the ERC controller • version 12/2001
Product description 4
Product description
4.1
Functions of the ERC controller
4
The ERC controller is suitable for controlling the room or outdoor temperatures of wall-hung gas boilers provided with UBA, modulating burner, and a heating circuit without mixer and for preparing hot water. The ERC controller has the following functions: z One-channel switching clock with week programme;
z Automatic summer/winter conversion (only possible if supplied with outdoor-temperature model AM 1.0); z Hot-water preparation 30 minutes before and after the heating operation; z Hot-water priority circuit; z Holiday programme; z Heating pause; z Heating-period extension (party function); z Frost-protection function; z factory basic adjustments (standard or default). In case of power failure, the time and day of the week remain stored for a certain period. All other adjustments have been permanently stored.
4.2
Intended use
Ask your specialized heating company to provide you
with extensive information on how to operate the installation. The ERC controller has been designed as an entry, control and regulation unit mainly for use with Buderus wall-hung gas boilers for detached and terraced houses. The ERC controller can be used for two different applications: z Room-temperature control;
z Outdoor-temperature-dependent control. J NOTE! The latter application requires the outdoortemperature module AM 1.0 and an outdoortemperature sensor.
4.3
Unprofessional use
A CAUTION! Only enter or change the operating values indicated in this operating manual. Other entries will change the control programme of the heating installation and can lead to faulty operation.
We reserve the right to make changes based on technical enhancements.
Document guide for the ERC controller • version 12/2001
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
11
4 4.4
Product description Operating elements, operating levels
All functions and adjustment values are indicated or adjusted in the clear operating field. 4.4.1
First operating level
At the first operating level (fig. 1) there is a temperature rotating knob for adjusting the room temperature. If the mark on the temperature rotating knob points down towards the auto push-button, the wall-hung gas boiler installation will be in automatic heater mode in accordance with the adjusted programme. Using the push-button ‘- Auto +’, room-temperature changes of short duration can be adjusted in automatic mode (see “Provisional adjustment for short duration” on page 21). Such short-duration room-temperature adjustments will be later cancelled by the next switching time. The display shows the standard value of the current day of the week, the time and the measured room temperature.
Temperature rotating knob
Key “- Auto +” Fig. 1
4.4.2
first operating level
Second operating level
Open the upper cover (fig. 2).
The display shows the standard value of the current day of the week, the time and the measured room temperature. Turn the rotating knob.
You can change the default in the adjustment and adjust another heating programme that corresponds to your wishes: see “Operating the basic functions” on page 16 . At the second operating level, adjustments are made by pressing keys or rotating the programme rotating knob.
The display will change and show consecutively the day of the week with the switching times and the target room-temperature values.
Set time Enter day of the week
Enter temperatures
Enter holiday Enter switching point programme rotating Enter heating pause Enter party time and temperature Fig. 2
Delete switching point
Second operating level
We reserve the right to make changes based on technical enhancements.
12
Set mode and hot water
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Document guide for the ERC controller • version 12/2001
Product description 4.4.3
4
Third operating level
The third operating level see “Third operating level” on page 13 can be accessed by opening the lower cover. Depending on the version, the following plug-in modules will be found there: 1. On-line module OM 1.0 2. Outdoor-temperature module AM 1.0 3. Barometer module BM 1.0 4. Hygrometer module HM 1.0 For operating see “Operating the plug-in modules” on page 29.
On-line module
Barometer module Hygrometer module
Outdoor-temperature module Fig. 3
We reserve the right to make changes based on technical enhancements.
Document guide for the ERC controller • version 12/2001
Third operating level
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
13
4.5
Product description Default adjustment
In the ERC controller a standard programme (‘factory programme’, fig. 4) has been installed. This programme will be active after its commission, when the big rotating knob points to AUTO and the indicator lamp ‘Auto’ is active. Day of the week
Time
Roomtemperature
Mon. - Fri.
5:30
21 °C
9:00
19 °C
17:00
21 °C
22:00
16 °C
7:00
21 °C
23:00
16 °C
Sat. and Sun.
Room temperature ˚C
4
Monday to Friday Saturday + Sunday
Fig. 4
Hours
Standard programme (‘factory programme’)
Explanation: Each adjusted room temperature is specified as a target value of the listed times: for instance, as from Monday at 05:30 hrs the installation will heat to a room temperature of 21 °C, after which it will reduce the temperature to 19 °C as of 09.00 hrs, etc. Should the factory programme not correspond to your heating habits, you may adapt the heating programme to your wishes at any time.
4.6
Danger zones
AWARNING! There is a danger of scalding if the hot water is too hot. Always open the cold-water faucet first and then ad hot water as required. Frost protection J NOTE! If the wall-hung gas boiler is active, the frost protection is active. Before deactivating the wall-hung gas boiler installation using the operating switch on the wall-hung gas boiler, check whether frost is expected.
We reserve the right to make changes based on technical enhancements.
14
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Document guide for the ERC controller • version 12/2001
Product description 4.7
4
Technical data
Electrical data Supply . . . . . . . . . . . . . . . .max. 12 V DC; max. 80 mA Signal connection . . . . . . . . . . . . . via the supply cable, . . . . . . . . . . . . . . . . . . . . . . . . . . . . max. 1 mm² Device protection . . . . . . . . . . . . . . IP 20 acc. IEC 529 Dimensions (w x h x d) ERC including installation plate. . . . 192 x 120 x 40 mm Environmental conditions Ambient temperature. . . . . . . . . . . 0 °C through +50 °C Storage temperature . . . . . . . . . .-25 °C through +70 °C EMC compatibility . . . . . . . . . . . acc. EN 50081-2: 1999
We reserve the right to make changes based on technical enhancements.
Document guide for the ERC controller • version 12/2001
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
15
5
Operating the basic functions
5
Operating the basic functions
5.1
Commission
On commissioning the ERC controller, observe the extensive instructions in the operating manual: z for the wall-hung gas boiler;
z for the controller (these instructions). J NOTE! Your professional heating specialist will provide you with extensive information concerning operation. Activate the heating-room emergency heating
switch. J NOTE! If a hot-water facility has been installed on your heating installation, then hot water will be heated with priority. When there’s no longer a demand for hot water, then the living area will be heated
We reserve the right to make changes based on technical enhancements.
16
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Document guide for the ERC controller • version 12/2001
Operating the basic functions 5.2
5
Adjusting the current day of the week and the time
The heating programme is based on the day of the week and the time. The heating installation must therefore be set to the current day of the week and the current time. The following table indicates the abbreviations used for the days of the week: abbreviation
meaning
MO
Monday
DI
Tuesday
MI
Wednesday
DO
Thursday
FR
Friday
SA
Saturday
SO
Subday
Assume it is 16:30 hrs on a Monday. Then proceed to adjust as follows: Open the cover (second operating level). Press the ‘Tag’ key (fig. 5) and keep it pressed. Turn the rotating knob until ‘MO’ for Monday is shown
on the display. Release the ‘Tag’ key to store the day. Press the ‘Zeit’ key and keep it pressed. Turn the rotating knob until the correct time is shown
on the display (e.g. 16:30). Release the ‘Zeit’ key. The time is stored.
J After a power failure, both day and time will blink. Once the blinking indication corresponds to the current day of the week and time, push the ‘Zeit’ button once.
Fig. 5
Adjusting the day of the week and time
If the blinking indication does not respond to the current day of the week and time, repeat the adjustment procedure. Once you have carried out all operating steps and the temperature rotating knob is on ‘Auto’, the heating operation is started on the basis of the factory programme.
We reserve the right to make changes based on technical enhancements.
Document guide for the ERC controller • version 12/2001
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
17
5 5.3
Operating the basic functions Selecting the operating mode
Use the ‘heating’ key to adjust the wall-hung gas boiler installation to the following operating modes: An = winter mode (room and water heating activated) Aus = summer mode (only water heating activated) Auto = Automatic conversion between the summer/ winter modes. The heating installation automatically recognizes when the room-heating function can be deactivated (see “Adjusting the summer/winter conversion” on page 28). J NOTE! The position ‘Auto’ is only possible if the controller has been provided with an outdoor temperature module AM 1.0 (Fig. 6) and if on the module AM 1.0 a selection has been made for heating operation with outdoor temperature guidance.
Fig. 6
Outdoor temperature module
Fig. 7
Adjusting heating An / Aus / Auto
Press the ‘heating’ key (fig. 7) and keep it pressed. Turn the rotor button until the desired adjustment
(An, Aus, Auto) is shown on the display.
We reserve the right to make changes based on technical enhancements.
18
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Document guide for the ERC controller • version 12/2001
Operating the basic functions 5.4
5
Programming the heating switchpoints
The section “Default adjustment” on page 14 presents the standard programme and clarifies it. This programme can be tailored to your personal requirements. The programme is made up of several heating switchpoints per day for all days of the week. These heating switchpoints can be recorded by fully arbitrary ‘switching points’. It is also possible to specify individual room temperatures; for this, see “Adjusting the target room-temperature” on page 21. 5.4.1
Changing a switching point
For instance, from Saturday 07:00 hrs to Saturday 08:30 hrs Open the cover. Turn the rotating knob (fig. 8) until the display shows
‘SA 07:00 21.0 °C’. Press the ‘Zeit’ button and keep it pressed.
The time display will blink. Turn the rotating knob until the desired time (08:30)
is displayed. Release the ‘Zeit’ button.
The value has been stored. After 10 seconds the standard display will automatically reappear.
5.4.2
Inserting a switching point at present time
Fig. 8
Changing the switching point
.
For instance, Monday (MO)14:00 hrs 17.0 °C Press the ‘INS’ key (fig. 9) and keep it pressed. The temperature indication will blink. Turn the rotating knob until 17.0 °C is displayed. Release the ‘INS’ key.
The switching point has been stored and will be active at 14.00 hrs every Monday.
Fig. 9
We reserve the right to make changes based on technical enhancements.
Document guide for the ERC controller • version 12/2001
Inserting a switching point at the present time
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
19
5 5.4.3
Operating the basic functions Inserting a switching point at any time
For instance, Tuesday (DI)13:10 22.0 °C. Press the ‘INS’ key (fig. 10) and release it. The displayed temperature will blink. Press the ‘Tag’ key and keep it pressed.
The displayed day and temperature will blink. Turn the rotating knob until ‘Di’ is displayed. Release the ‘Tag’ button. Press the ‘Zeit’ button and keep it pressed.
The displayed time and temperature will blink. Turn the rotating knob until 13:10 is displayed. Release the ‘Zeit’ button. Press the ‘Temp’ button and keep it pressed.
The displayed temperature will blink. Turn the rotating knob until 22.0 is displayed. Release the ‘Temp’ button. The switching point has
now been stored. After 10 seconds, the standard display will automatically reappear.
5.4.4
Fig. 10
Inserting a switching point at any time
Fig. 11
Deleting a switching point
Deleting a switching point
Use the rotating knob to select the switching point
you would like to delete. Press the ‘C’ button (fig. 11) and keep it pressed until
all numbers on the display have disappeared. ACAUTION! If you release the ‘C’ button before all numbers have disappeared, the switching point will not have been deleted.
We reserve the right to make changes based on technical enhancements.
20
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Document guide for the ERC controller • version 12/2001
Operating the basic functions 5.5
5
Adjusting the target roomtemperature
You can choose between various possibilities for adjusting the target room-temperature: z Provisional adjustment for short duration;
z Changing the default adjustment for permanent adjustment. 5.5.1
Provisional adjustment for short duration
Changing the room temperature using the ‘-/Auto/+’ -key The temperature rotating knob must point to ‘Auto’. The indicator lamp ‘Auto’ will be active. Use the ‘-/Auto/+’ -key (fig. 12) to provisionally change the room temperature. Press the ‘+’ or ‘-’ key. The display will show the changed room temperature. You can increase or reduce the room temperature by a maximum of 2.5 °C. The change will be cancelled when passing the next automatic switching point. J NOTE! If all indicator lamps are off, the control will be in summer mode.
Fig. 12
Changing the room temperature using the ‘-/Auto/+’ key
Fig. 13
Manually adjusting the room temperature
Manually adjusting the room temperature J NOTE! Use the manual adjustment to deactivate automatic mode. Adjust the temperature rotating knob (fig. 13) to the
desired room temperature (above 6 °C). The indicator light ‘Man’ will become active. The wallhung gas boiler is now carrying out its heating operation in winter mode (room and water heating) continuously using the adjusted room temperature. If you set the room temperature lower than 16 °C, operation will go down to night level. In addition to the ‘Man’ indicator lamp also the ‘Nacht’ indicator lamp will become active. The water heating will then be off. Back to auto mode: Turn the temperature rotating knob to ‘Auto’.
We reserve the right to make changes based on technical enhancements.
Document guide for the ERC controller • version 12/2001
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
21
5.5.2
Operating the basic functions Changing the default adjustment for permanent adjustment
Auto mode The room temperature will be automatically controlled in accordance with the factory programmes (see chapter “4.5 Default adjustment” on page 14 and fig. 14) or using a time programme entered by you.
Room temperature ˚C
5
Monday to Friday Saturday + Sunday
Hours
Fig. 14
Default programme
Fig. 15
Changing the room temperature
Changing the room temperature of the default programme For instance Monday to Friday 05:30 hrs from 21 °C to 22.0 °C room temperature. Open the cover. Turn the rotating knob (Fig. 15) until the display
shows ‘MO 05:30 21.0’. Press the ‘Temp’ key and keep it pressed.
The display temperature will blink. Turn the rotating knob until the desired temperature
of 22 °C is indicated. Release the ‘Temp’ button. The value has been
stored. Repeat these steps accordingly for Tuesdays to
Fridays. After approx. 10 seconds, the standard display will automatically reappear.
We reserve the right to make changes based on technical enhancements.
22
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Document guide for the ERC controller • version 12/2001
Operating the basic functions 5.6
Adjusting the water temperature
5.6.1
Buderus wall-hung gas boiler with built-in hot-water tank
5
Using the ERC controller you can adjust the hot-water facility to the following operating modes: An = The hot water is continuously heated. You will have hot water available at all times, even during low-operation periods. Aus = Water is not heated. Auto = Hot water is prepared only in day mode. In night mode and during the holiday programme, the hot-water facility is deactivated. Press the ‘faucet’ key (fig. 16) and keep it pressed. Turn the rotating knob until the desired adjustment is
shown on the display. The factory adjustment of the water temperature is 60 °C. Fig. 16
Adjusting the water temperature
J NOTE! In the case of a built-in tank, the water temperature has been permanently adjusted. It is not possible to change it.
5.6.2
Buderus wall-hung gas boiler with separate hot-water tank
D LITERATURE! In the case of a separate tank or built-in direct water heater, the water temperature can be adjusted at the second level of the UBA automatic ignition device (see the documentation of the wall-hung gas boiler).
We reserve the right to make changes based on technical enhancements.
Document guide for the ERC controller • version 12/2001
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
23
5 5.7
Operating the basic functions Resetting to the default values
To reactivate the standard programme: Simultaneously press the ‘INS’ and ‘C’ keys (fig. 17) and keep them pressed until all numbers have disappeared from the display.
Zeit
Once the keys are released, all previously entered switching points will have been deleted. The factory programme will have been reactivated. J NOTE! If you release the keys before all numbers have disappeared, the switching points will not have been deleted.
We reserve the right to make changes based on technical enhancements.
24
Fig. 17
Resetting to the default adjustments
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Document guide for the ERC controller • version 12/2001
Operating the special functions
6
6
Operating the special functions
6.1
Adjusting summer/winter time
Open the cover.
The display will show the day of the week, the current time and the actual room-temperature value. Press the ‘Zeit’ button (fig. 18) and keep it pressed. Turn the rotating knob clockwise or anticlockwise,
depending on what you want to set: winter or summer time. Realise the further adjustments as listed in “Adjusting
the current day of the week and the time” on page 17.
6.2 6.2.1
Holiday programme Fig. 18
Adjusting summer/winter time
Fig. 19
Adjusting the ‘holiday’ function
Adjustment
During your holiday you might set the room temperature lower. Let’s assume you have 15 days of holiday: in this period the room temperature should be 10 °C day and night. Press the ‘Urlaub’ button (fig. 19) and keep it
pressed. Use the rotating knob to set the number of holidays
to 15. The day of adjustment is regarded as the first day of the holiday. Press the ‘Temp’ key and keep it pressed. The default room temperature is 16 °C. Use the rotating knob to adjust the room temperature
to the value that must be observed during your holiday, in this case 10 °C. Release the ‘Temp’ key. Your holiday and the room
temperature have been stored. If the warm-water preparation ‘WW-Auto’ is set, then in the holiday period no warm water will be prepared since a room temperature lower than 16 °C has been entered see “Adjusting the water temperature” on page 23.
6.2.2
Cancelling the holiday programme
Press the ‘Urlaub’ key and keep it pressed. Use the rotating knob and continue to turn the button
anticlockwise until ‘00’ is shown on the display. Release the ‘Urlaub’ button.
The automatic programme will be active again.
We reserve the right to make changes based on technical enhancements.
Document guide for the ERC controller • version 12/2001
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
25
6
Operating the special functions
6.3
Heating pause
6.3.1
Alignment
In order to save energy you can set the ‘heating pause’ if a low room temperature will be adequate for the next brief period, until the next switching point. J NOTE! If the hot-water preparation has been adjusted to ‘Auto’, during the heating pause also the heating of hot water will be deactivated. Press the ‘Pause’ key (fig. 20) and keep it pressed. Turn the rotating knob until the desired time for the
end of the pause is indicated, e.g. 15:30 hrs. The display will show blinking time alternated by the ending time of the pause and the day-night conversion temperature of 16 °C.
6.3.2
Fig. 20
Terminating the heating pause
Fig. 21
Adjusting the heating pause
Cancellation
If you want to prematurely terminate the heating pause: Press the ‘Pause’ key (fig. 21) and keep it pressed. Turn the rotating knob anticlockwise, until the current
time is displayed, or Keep the ‘C’ button pressed until all numbers on the
display have disappeared, or Briefly turn the temperature rotating knob away from
‘Auto’ and then return it to ‘Auto’.
We reserve the right to make changes based on technical enhancements.
26
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Document guide for the ERC controller • version 12/2001
Operating the special functions 6.4
Party mode
6.4.1
Adjustment
6
Using the party function you can provisionally extend the day mode, e.g. up to 01:50 hrs. J NOTE! You can set a provisional extension of the heating period. Once the extension period has ended. the system will automatically return to the previous programme. Press the ‘Party’ button (fig. 22) and keep it pressed. Turn the rotating knob until the desired end of the
party is displayed, e.g. 01:50 hrs. Release the ‘Party’ button.
The display will show the blinking time alternated with the time when the party ends. The room temperature of the last switching point will be shown. If you desire a different room temperature: Press the ‘Temp’ key and use the rotating knob to adjust the desired room temperature.
6.4.2
Fig. 22
Adjusting the party mode
Fig. 23
Terminating party mode
Termination
If you want to prematurely terminate the party mode: Press the ‘Party’ key and keep it pressed. Turn the rotating knob anticlockwise until the current
time is displayed, or Keep the ‘C’ key pressed until all numbers on the
display have disappeared, or Briefly turn the temperature button away from ‘Auto’
and then return it to ‘Auto’.
We reserve the right to make changes based on technical enhancements.
Document guide for the ERC controller • version 12/2001
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
27
6
Operating the special functions
6.5
Adjusting the summer/winter conversion
6.5.1
General
J NOTE! The summer/winter conversion is only possible if an AM 1.0 has been installed and adjusted to outdoor-temperature-driven heating operation. The ERC controller takes into account the residual heat of the building and in case of outdoor-temperature fluctuations activates and deactivates the heater system after a certain delay. Example for spring: In spring, when the building is still cold, the controller will not deactivate the wall-hung gas boiler until the outdoor temperature has been above the conversion temperature for a certain time. Example for autumn: In autumn when the building has still retained heat, the residual heat will be taken into account and the wall-hung gas boiler will not be deactivated until the outdoor temperature has been below the conversion temperature for some time.
6.5.2
Adjusting the automatic conversion
The factory adjustment for the summer/winter conversion temperature is 17 °C. Proceed as follows to change it: Press the ‘heating’ key (fig. 24) and keep it pressed. The display will show ‘auto’, the conversion temperature and the room temperature. Turn the rotating knob until the outdoor temperature
is displayed below which your wall-hung gas boiler should heat, e.g. 20 °C. Release the ‘heating’ key.
The value has been stored.
Fig. 24
We reserve the right to make changes based on technical enhancements.
28
Adjusting the automatic summer/winter conversion
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Document guide for the ERC controller • version 12/2001
Operating the plug-in modules 7
7
Operating the plug-in modules
The ERC controller may have been provided with or can be expanded with four plug-in modules: 1. Outdoor-temperature module AM 1.0 2. On-line module OM 1.0 3. Barometer module BM 1.0 4. Hygrometer module HM 1.0
7.1
Outdoor-temperature module AM 1.0
The outdoor-temperature module is required if you want to operate your wall-hung gas boiler using outdoortemperature-driven heating operation. You have the following three different operating possibilities: z Room-temperature-driven heating operation;
z Outdoor-temperature-driven heating operation; z Outdoor-temperature-driven heating operation with room-temperature activation. The selection of these adjustments is made using the ‘Control’ key on the outdoor-temperature module.
7.1.1
Room-temperature-driven heating operation
In this position the outdoor-temperature module (fig. 25) serves only to indicate the outdoor temperature.
7.1.2
Fig. 25
AM 1.0: room-temperature-driven heating operation
Fig. 26
AM 1.0: outdoor-temperature-driven heating operation
Outdoor-temperature-driven heating operation
Only select this operation mode if your house does not accommodate a suitable reference room for the roomtemperature measurement, e.g. it is a multifamily house or you have floor heating. The right-hand large indication on the display (fig. 26) represents the room temperature of the room where the controller is located, e.g. heating-room temperature in the heating room rather than the living-room temperature.
We reserve the right to make changes based on technical enhancements.
Document guide for the ERC controller • version 12/2001
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
29
7
Operating the plug-in modules
Function The heating system’s water will not be heated further than necessary for the room temperature. z Lower outdoor temperature = higher heating system’s water temperature
z Higher outdoor temperature = lower heating system’s water temperature or deactivation of the heating system. If the room temperature is too low, it can be corrected using the temperature rotating knob using manual adjustment (see “Manually adjusting the room temperature” on page 21). If you want to remain in automatic mode (temperature rotating knob in ‘auto’ position) in order to correct the room temperature, you must change the individual switching points (see “Adjusting the target room-temperature” on page 21).
7.1.3
Outdoor-temperature-driven heating operation with room-temperature activation
Select this operating mode if your house accommodates a suitable reference room for the room-temperature measurements; e.g. it is a single-family or multilevel house. Function In principal as in ‘outdoor-temperature-driven heating operation’. However, the room-temperature activation also registers the effects of such heat sources as incoming sunrays, lights, TV sets, etc. If the measured room temperature (fig. 27) deviates from the adjusted value, the controller will calculate a new heating temperature. This allows for an even more accurate determination of the heating-water temperature. A CAUTION! The heating-body valves in the reference room accommodating the controller device must have been fully opened.
Fig. 27
We reserve the right to make changes based on technical enhancements.
30
AM 1.0: outdoor-temperature-driven heating operation with room-temperature activation
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Document guide for the ERC controller • version 12/2001
Operating the plug-in modules 7.2
7
On-line module OM 1.0
Using the on-line module (fig. 28) you can follow the wall-hung gas boiler operation from your living room. z Use the ‘Funktion’ key to select the indications.
z In the ‘Service’ position the operating and service codes are displayed. These indications are intended for the service activities carried out by the heating specialist. Should your heating installation not function correctly, you can read out the error code and let your heating specialist know by telephone. D LITERATURE! There is an error-code table in the service manual.
Fig. 28
OM 1.0: ‘Service’ position
Fig. 29
OM 1.0: ‘Info’ position
Fig. 30
Hygrometer module HM 1.0
In the ‘Info’ position the wall-hung gas boiler-water temperature is shown. J NOTE! The horizontal line (fig. 29) near ‘radiator icon’ or ‘warm water icon’ indicates whether it is the room or the hot-water heating that is active.
7.3
Hygrometer module HM 1.0
The hygrometer module (fig. 30) is a display instrument and shows the relative air humidity in the living room as a percentage.
We reserve the right to make changes based on technical enhancements.
Document guide for the ERC controller • version 12/2001
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
31
7 7.4
Operating the plug-in modules Barometer module BM 1.0
The barometer module (fig. 31) is a display instrument and shows the air pressure in millibars.
Fig. 31
We reserve the right to make changes based on technical enhancements.
32
Barometer module BM 1.0
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Document guide for the ERC controller • version 12/2001
Calibrating the sensors 8
Calibrating the sensors
8.1
Function
You can calibrate the displayed values against the values measured by the sensors. Press the ‘Cal’ key using a pointed object (e.g. a ballpoint pen) and keep the key pressed. The display (fig. 32) will on the left-hand side always show the current measured value of the sensor and on the right-hand side the blinking value that you are adjusting. Press the ‘Cal’ key, release it briefly and press it once again to display in consecutive order the following sensor values (if the relevant module is present): z Room temperature;
z Temperature rotating knob;
8
Room temperature
Temperature rotating knob
Outdoor temperature
z Outdoor temperature; z Relative air humidity; z Air pressure.
Relative air humidity
Air pressure
Fig. 32
8.2
Indicating and calibrating sensor values
Example of calibrating the roomtemperature sensors
Use a thermometer to measure the room tempera-
ture at the spot where the ERC controller has been fastened.
Cal
Press the ‘Cal’ key and keep it pressed.
On the left the actual measure value will appear (fig. 33) and on the right the blinking value that you want to adjust. Turn the rotating knob until the temperature on the display is the same as the room temperature you just measured. Release the ‘Cal’ key.
Fig. 33
Calibrating the room temperature sensors
After 10 seconds, the standard value will automatically reappear. Calibrate the other values in the same manner.
We reserve the right to make changes based on technical enhancements.
Document guide for the ERC controller • version 12/2001
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
33
9 9
Faults Faults
Faults are indicated by LED indicators on the ERC controller.
ACAUTION! Immediately report any fault to your professional heating specialist
. Indication The LEDs ‘Man’ and ‘Auto’ are active alternately.
No communication with the UBA automatic ignition device.
In the on-line module OM 1.0, four horizontal dashes appear.
Fault in the UBA automatic ignition device.
At the spot of the temperature value, dashes appear.
Room-temperature sensor faulty.
At the spot of the outdoor temperature, four horizontal dashes appear in the outdoor-temperature module AM 1.0.
Outdoor-temperature sensor faulty.
Table 1
Faults and their meaning
We reserve the right to make changes based on technical enhancements.
34
Cause
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Document guide for the ERC controller • version 12/2001
Operating and display elements 10
10
Operating and display elements
Operating level 1: For short-term temperature changes
Operating level 2: For exact adjustments of the heating programme
Operating level 3: For recording the operating modes in installations with an outdoor-temperature sensor AND for reading out the display of the plug-in module
We reserve the right to make changes based on technical enhancements.
Document guide for the ERC controller • version 12/2001
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
35
Notes
We reserve the right to make changes based on technical enhancements.
36
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Document guide for the ERC controller • version 12/2001
Index 11
11
Index
A
P
adjusting party mode . . . . . . . . . . . . . . . . . . . 27 adjusting the automatic conversion . . . . . . . . 28 adjusting the target room-temperature . . . . . . 21 adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 alignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 application instructions . . . . . . . . . . . . . . . . . . . 7 automatic mode . . . . . . . . . . . . . . . . . . . . 12, 22
party mode . . . . . . . . . . . . . . . . . . . . . . . . . . .27 procedure if gas can be smelled . . . . . . . . . . . .6
R resetting to the default values . . . . . . . . . . . . .24
S B basic functions . . . . . . . . . . . . . . . . . . . . . . . . 16
C
safety instructions . . . . . . . . . . . . . . . . . . . . . . .6 standard programme . . . . . . . . . . . . . . . . . . . .14 suitable reference room . . . . . . . . . . . . . . . . .29 summer/winter conversion . . . . . . . . . . . . . . .28 summer/winter time . . . . . . . . . . . . . . . . . . . . .25
cancelling the heating pause . . . . . . . . . . . . . 26 cancelling the holiday programme . . . . . . . . . 25 changing a switching point . . . . . . . . . . . . . . . 19 changing the room temperature . . . . . . . . . . . 21 comfortable room temperature . . . . . . . . . . . . 30 commission . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
technical data . . . . . . . . . . . . . . . . . . . . . . . . .15 terminating party mode . . . . . . . . . . . . . . . . . .27 tips concerning economical heating . . . . . . . . .7
D
W
danger zones . . . . . . . . . . . . . . . . . . . . . . . . . 14 deleting a switching point . . . . . . . . . . . . . . . . 20
F
T
wall-hung gas boiler with built-in hot-water tank . . . . . . . . . . . . . . . . . . .23 wall-hung gas boiler with separate hot-water tank . . . . . . . . . . . . . . . . .23
factory programme . . . . . . . . . . . . . . . . . . . . . 14 frost protection . . . . . . . . . . . . . . . . . . . . . . . . 14
H heating pause . . . . . . . . . . . . . . . . . . . . . . . . . 26 higher outdoor temperature . . . . . . . . . . . . . . 30 holiday programme . . . . . . . . . . . . . . . . . . . . . 25 hot water heated with priority . . . . . . . . . . . . . 16
I inserting a switching point . . . . . . . . . . . . . . . . 20
L lower outdoor temperature . . . . . . . . . . . . . . . 30
M manually adjusting the room temperature . . . 21
O outdoor-temperature module am 1.0 . . . . . . . 29 We reserve the right to make changes based on technical enhancements.
Document guide for the ERC controller • version 12/2001
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
37
Notes
We reserve the right to make changes based on technical enhancements.
38
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Document guide for the ERC controller • version 12/2001
04/0004/00
Notes
We reserve the right to make changes based on technical enhancements.
Document guide for the ERC controller • version 12/2001
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
39
Buderus is always near. High-quality heating technology requires professional installation and maintenance. Buderus therefore supplies the complete programme exclusively via professional heating specialists. Ask for Buderus heating technology. Or contact one of our 45 establishments.
Establishment
City
Address
Telephone
Telefax
Aachen Augsburg Berlin Bielefeld Bremen Dortmund Dresden Düsseldorf Erfurt Essen Esslingen Frankfurt/ Main Freiburg Gießen Goslar Hamburg Hannover Karlsruhe Kassel Kempten Kiel Koblenz Köln Kulmbach Leipzig Ludwigshafen Magdeburg Mainz Meschede München Münster/Westf. Neubrandenburg Neu-Ulm Nürnberg Osnabrück Regensburg Rostock Schwenningen Schwerin Saarbrücken Trier Velten Wesel Würzburg Zwickau
52080 Aachen 86156 Augsburg 15831 Berlin 33605 Bielefeld 28816 Stuhr 44319 Dortmund 01458 Ottendorf-Okrilla 40231 Düsseldorf 99195 Mittelhausen 45307 Essen 73730 Esslingen 63110 Rodgau 79108 Freiburg 35394 Gießen 38644 Goslar 21035 Hamburg 30916 Isernhagen 76185 Karlsruhe 34134 Kassel 87437 Kempten 24109 Kiel-Melsdorf 56220 Bassenheim 50858 Köln-Marsdorf 95326 Kulmbach 04420 Makranstädt 67069 Ludwigshafen 39116 Magdeburg 55129 Mainz 59872 Meschede 81379 München 48159 Münster 17034 Neubrandenburg 89231 Neu-Ulm 90425 Nürnberg 49078 Osnabrück 93092 Barbing 18182 Bentwisch 78056 Villingen-Schwenningen 19075 Pampow 66130 Saarbrücken 54343 Föhren 16727 Velten 46485 Wesel 97228 Rottendorf 08129 Crossen
Hergelsbendenstraße 30 Werner-Heisenberg-Str. 1 Am Lückefeld Reichenberger Straße 39 Industriestraße 22 Zeche-Norm-Straße 28 Jakobsdorfer Straße 4 – 6 Höher Weg 268 Erfurter Straße 57a Eckenbergstraße 8 Wolf-Hirth-Straße 8 Hermann-Staudinger-Str. 2 Stübeweg 47 Rödgener Straße 47 Magdeburger Kamp 7 Wilhelm-Iwan-Ring 15 Stahlstraße 1 Hardeckstraße 1 Glockenbruchweg 113 Heisinger Straße 21 Am Ihlberg (Gewerbegebiet) Am Gülser Weg 15 – 17 Toyota-Allee 97 Aufeld 2 Handelsstraße 22 Kreuzholzstraße 11 Sudenburger Wuhne 63 Carl-Zeiss-Straße 16 Zum Rohland 1 Boschetsrieder Straße 80 Haus Uhlenkotten 10 Feldmark 9 Böttgerstraße 6 Kilianstraße 112 Am Schürholz 4 Von-Miller-Straße 16 Hansestraße 5 Albertistraße 15 Fährweg 10 Kurt-Schumacher-Straße 38 Europaallee, Postfach 11 64 Berliner Straße 1 Am Schornacker 119 Edekastraße 8 Berthelsdorfer Straße 12
(02 41) 9 68 24 - 0 (08 21) 4 44 81 - 0 (0 30) 7 54 88 - 0 (05 21) 20 94 - 0 (04 21) 89 91 - 0 (02 31) 92 72 - 0 (03 52 05) 55 - 0 (02 11) 7 38 37 - 0 (03 61) 7 79 50 - 0 (02 01) 5 61 - 0 (07 11) 93 14 - 5 (0 61 06) 8 43 - 0 (07 61) 5 10 05 - 0 (06 41) 4 04 - 0 (0 53 21) 5 50 - 0 (0 40) 7 34 17 - 0 (05 11) 77 03 - 0 (07 21) 9 50 85 - 0 (05 61) 94 08 - 0 (08 31) 5 75 26 - 0 (04 31) 6 96 95 - 0 (0 26 25) 9 31 - 0 (0 22 34) 92 01 - 0 (0 92 21) 9 43 - 0 (03 41) 9 45 13 - 00 (06 21) 66 06 - 0 (03 91) 60 86 - 0 (0 61 31) 92 25 - 0 (02 91) 54 91 - 0 (0 89) 7 80 01 - 0 (02 51) 7 80 06 - 0 (03 95) 45 34 - 0 (07 31) 7 07 90 - 0 (09 11) 36 02 - 0 (05 41) 94 61 - 0 (0 94 01) 8 88 - 0 (03 81) 60 96 90 (0 77 20) 69 14 - 0 (0 38 65) 78 03 - 0 (06 81) 8 83 38 - 0 (0 65 02) 9 34 - 0 (0 33 04) 3 77 - 0 (02 81) 9 52 51 - 0 (0 93 02) 9 04 - 0 (03 75) 44 10 - 0
(02 41) 9 68 24 - 99 (08 21) 4 44 81 - 50 (0 30) 7 54 88 - 160 (05 21) 20 94 - 228 (04 21) 89 91 - 235 (02 31) 92 72 - 280 (03 52 05) 55 - 222 (02 11) 7 38 37 - 21 (03 61) 73 54 45 (02 01) 5 61 - 279 (07 11) 93 14 - 669 (0 61 06) 8 43 - 203 (07 61) 5 10 05 - 45 (06 41) 4 04 - 221 (0 53 21) 5 50 - 114 (0 40) 7 34 17 - 267 (05 11) 77 03 - 242 (07 21) 9 50 85 - 33 (05 61) 94 08 - 106 (08 31) 5 75 26 - 50 (04 31) 6 96 95 - 95 (0 26 25) 9 31 - 224 (0 22 34) 92 01 - 237 (0 92 21) 9 43 - 292 (03 41) 9 42 00 - 89 (06 21) 66 06 - 107 (03 91) 60 86 - 215 (0 61 31) 92 25 - 92 (02 91) 66 98 (0 89) 7 80 01 - 258 (02 51) 7 80 06 - 121 (03 95) 4 22 87 32 (07 31) 7 07 90 - 92 (09 11) 36 02 - 274 (05 41) 94 61 - 222 (0 94 01) 8 88 - 92 (03 81) 6 86 51 70 (0 77 20) 69 14 - 31 (0 38 65) 32 62 (06 81) 8 83 38 - 33 (0 65 02) 9 34 - 151 (0 33 04) 3 77 - 199 (02 81) 9 52 51 - 20 (0 93 02) 9 04 - 111 (03 75) 47 59 96
Buderus Heiztechnik GmbH, 35573 Wetzlar http://www.heiztechnik.buderus.de e-mail:
[email protected]
720.917A - 3410 - 12/2001
Professional heating specialist: