Analog Signal Converters Cc Range

  • Uploaded by: Elias
  • 0
  • 0
  • October 2019
  • PDF

This document was uploaded by user and they confirmed that they have the permission to share it. If you are author or own the copyright of this book, please report to us by using this DMCA report form. Report DMCA


Overview

Download & View Analog Signal Converters Cc Range as PDF for free.

More details

  • Words: 9,399
  • Pages: 25
ABB

Analog signal converters CC range

Content Benefits and advantages.................................................................................................. 200 Application......................................................................................................................... 201 Approvals and marks........................................................................................................ 201 Ordering details Analog standard signal converters CC-E/STD, CC-E x/x.................................................................................................... CC-E I/I......................................................................................................................... CC-U/STD..................................................................................................................... CC-U/STDR.................................................................................................................. Temperature signal converters for RTD sensors CC-E/RTD..................................................................................................................... CC-U/RTD..................................................................................................................... CC-U/RTDR.................................................................................................................. Temperature signal converters for thermocouples CC-E/TC....................................................................................................................... CC-U/TC....................................................................................................................... CC-U/TCR..................................................................................................................... Measuring converters for currents (E/I) and (U/I) and voltages (U/V) CC-E/I........................................................................................................................... CC-E IAC / ILPO............................................................................................................. CC-U/I........................................................................................................................... CC-U/V.......................................................................................................................... Accessories................................................................................................................... Technical data CC-E/STD, CC-E x/x, CC-E/RTD, CC-E/TC................................................................. CC-E I/I......................................................................................................................... CC-U/STD, CC-U/RTD, CC-U/TC................................................................................ CC-U/STDR, CC-U/RTDR, CC-UTCR.......................................................................... CC-E/I, CC-E IAC / ILPO................................................................................................ CC-U/I, CC-U/V............................................................................................................ Technical diagrams.............................................................................................................. Dimensional drawings.........................................................................................................

ABB

202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 223

199 2CDC110004C0205

5

Analog signal converters CC range

2CDC 285 001 F0b05

Benefits and advantages

CC-U range

CC-E range

J J J J J J

J Universally configurable devices and single-function devices

8 different standard signal outputs on one device Input and output side universally configurable Also available with 2 threshold relay outputs Adjustment and operating elements on the front side Safe operation by electrical 3-way isolation Plug-in connecting terminals, unambiguously and clearly marked

Conversion, measurement and separation of J J J J

standard signals signals of RTD sensors (PT10, PT100, PT1000) thermocouple signals RMS values of currents and voltages

Characteristics J The required input and output ranges can be configured for all devices by means of directly accessible DIP switches positioned on the side. J Due to the wide input range of the gain and offset stages all input signals between the minimum and the maximum input value can be universally converted to all common output signals. J Devices for DC or AC (50/60 Hz) supply available.

J Adjustment and operating elements on the front side J Safe operation by electrical 3-way isolation J Unambiguous and clear connecting terminal markings Conversion, measurement and separation of J J J J

standard signals (0-5 V, 0-10 V, 0-20 mA, 4-20 mA) temperature signals of RTD sensors (PT 100) thermocouple signals (types J and K) current measurement signals (0-5 A, 0-20 A AC/DC)

Characteristics of single-function devices J No adjustment or balancing necessary. Characteristics of universal devices J The required input and output ranges can be configured by means of directly accessible DIP switches positioned on the side J Gain adjustment of ± 5 % by means of an adjustment potentiometer on the front-side J Offset adjustment of ±5 % by means of adjustment potentiometers on the front-side

2CDC 283 016 F0b03

5

Product range for analog signal processing

200 2CDC110004C0205

ABB

Analog signal converters CC range

Application, Approvals and marks Applications for analog signal processing and correct solution using CC-E and CC-U converters

0-10 V

Nearly every process includes a control system that receives data by means of analog signals and then evaluates the data and sets the respective parameters correspondingly.

0-10 V

Controller e.g. AC500 1. Analog signal converter (e.g. CC-E or CC-U)

2. Analog signal converter (e.g. CC-E or CC-U)

When transmitting analog signals numerous problems may arise which can disturb or even block an ideal behavior of the process. 100 m

0-20 mA

100 m

Below we have listed some processing problems together with the

4-20 mA Actuator

respective solutions to solve these problems:

Measuring sensor

2CDC 282 013 F0206

Signal conversion Sometimes the available signals cannot be processed by the controller or the actuator. In this case, signal converters are required to convert the input signal (or different input signals) to the desired output signal.

Signal amplification

Signal separation

If long lines or high burdens have to be operated, it may be necessary to amplify the signal. CC analog signal converters require only low input power and provide high output power.

J Protection against overvoltage The increased use of micro-electronics make controls much more sensitive against overvoltages, resulting from lightning discharges or switching processes. Suppression diodes are incorporated in the input of the CC analog signal converters which enable the converters to arrest overvoltages with low energy level (resulting from switching processes) by themselves. The products furthermore provide electrical isolation between input, output and supply circuit for protection of the controller connected to the output.

Thus, there are no restrictions for the converter's position on the line, i.e. it can be used J for signal refreshing  at the end of the line (low input power) J or for signal amplification  at the beginning of the line (high output power).

J Protection against ground loops Signal filtering If components are used which refer to ground, the measuring signals can be falsified by a so-called ground loop. In this case, Particularly on long lines or in rough industrial environments the signals certain parts of the signal are transmitted via earth and not via the are exposed to high electromagnetic interferences. The frequency of analog transmission line, thus causing incorrect evaluation of the the coupled interference signals may be in the range of the common signal. The electrical isolation between the input and the output mains frequency (50 Hz) or even much higher (in case of frequency disconnects these ground loops and thus enables correct signal converters). According to the specific requirements, analog signal transmission. converters are available which provide reliable suppression of those interferences by means of an input low-pass filter.

J

J

J

G

J

J

J

J

A

UL 1604 (Class I, Div 2, hazardous locations), CAN/CSA C22.2 No.213

G

K

CB scheme

J

J

J

E

CCC

J

J

J

J

CC-U/V

CC-E/I

J

UL 508, CAN/CSA C22.2 No.14

CC-U/I

CC-U/TCR

J

A

Approvals

CC-E IAC/ILPO

CC-U/TC

J

CC-E/TC

CC-U/RTD

G

CC-U/RTDR

CC-E/RTD

J

CC-U/STD

J

CC-E I/I

J

CC-E/STD

CC-U/STDR

J existing G existing for some devices j pending

J

J

J

J

J

G

Marks a

CE

J

J

J

J

J

J

J

J

J

J

J

J

J

J

b

C-Tick

J

J

J

J

J

J

J

J

J

J

J

J

J

J

ABB

201 2CDC110004C0205

5

Analog standard signal converters CC-E/STD, CC-E x/x Ordering details

J 2 universally configurable devices (type CC-E/STD) J 2x10 single-function devices J "Plug and Work", no adjustment of single-function devices required Wiring instruction

DIP switch settings (universal devices)



Input



0...5 V

Burden R � 500 �

CC-E/STD supply 24 V DC or 110-240 V AC

2CDC 282 006 F0206

Burden R � 1.0 k�



0...10 V

0...20 mA

2CDC 281 014 F0t04

4...20 mA

Type �

CC-E V/V

5

Input signal

Output

Switch 1 2 3 4 5 6 7 8

0...5 V 0...10 V 0...20 mA 4...20 mA 0...5 V 0...10 V 0...20 mA 4...20 mA 0...5 V 0...10 V 0...20 mA 4...20 mA 0...5 V 0...10 V 0...20 mA 4...20 mA

Output signal

Order code

Pack. unit piece

0-5 V, 0-10 V 0-20 mA, 4-20 mA

1SVR 011 700 R00001)

1

Legend ON OFF

2CDC 282 002 F0204



2CDC 282 001 F0204

2CDC 281 001 F0t03

CC-E/STD analog signal converter with 3-way electrical isolation

Price 1 piece

Supply voltage: 24 V DC universal CC-E/STD

0-5 V, 0-10 V 0-20 mA, 4-20 mA

single-function 1 U: green LED - supply voltage 2 Gain adjustment 3 Offset adjustment  DIP switch for input and output configuration (only available on universal devices)

CC-E V/V CC-E V/I CC-E V/I

0-10 V

0-10 V 0-20 mA 4-20 mA

1SVR 011 710 R2100 1SVR 011 711 R1600 1SVR 011 712 R1700

1 1 1

CC-E I/V CC-E I/I CC-E I/I

0-20 mA

0-10 V 0-20 mA 4-20 mA

1SVR 011 713 R1000 1SVR 011 714 R1100 1SVR 011 715 R1200

1 1 1

CC-E I/V CC-E I/I CC-E I/I

4-20 mA

0-10 V 0-20 mA 4-20 mA

1SVR 011 716 R1300 1SVR 011 717 R1400 1SVR 011 718 R2500

1 1 1

CC-E V/V

-10...+10 V

-10...+10 V

1SVR 011 719 R2600

1

0-5 V, 0-10 V 0-20 mA, 4-20 mA

1SVR 011 705 R2100

1

Supply voltage: 110-240 V AC universal CC-E/STD

0-5 V, 0-10 V 0-20 mA, 4-20 mA

single-function



B 1604 Class I, Div.2 (universal device)

CC-E V/V CC-E V/I CC-E V/I

0-10 V

0-10 V 0-20 mA 4-20 mA

1SVR 011 720 R2300 1SVR 011 721 R1000 1SVR 011 722 R1100

1 1 1

CC-E I/V CC-E I/I CC-E I/I

0-20 mA

0-10 V 0-20 mA 4-20 mA

1SVR 011 723 R1200 1SVR 011 724 R1300 1SVR 011 725 R1400

1 1 1

CC-E I/V CC-E I/I CC-E I/I

4-20 mA

0-10 V 0-20 mA 4-20 mA

1SVR 011 726 R1500 1SVR 011 727 R1600 1SVR 011 728 R2700

1 1 1

CC-E V/V

-10...+10 V

-10...+10 V

1SVR 011 729 R2000

1

1)

202 2CDC110004C0205

• Technical data .......................................................................... 217

• Dimensional drawings ...............................................................223

ABB

Current/current isolator CC-E I/I-1 and CC-E I/I-2

2CDC 281 001 F0b06

Ordering details

Loop-powered current/current isolator without external power supply for analog current signals of 0-20 mA and 4-20 mA J J J J

Electrical isolation between input and output Very low internal voltage drop  2.5 V Available with one or two independent channels Width only 18 mm (1 and 2 channels)

Wiring instructions CC-E I/I-1 input 0-20 mA or 4-20 mA

Channel 1 IN

OUT C

F

D

E

output 0-20 mA or 4-20 mA UL

2CDC 281 041 F0b03

IN

OUT 100 � � RL � 500 �

2CDC 282 003 F0205

Channel 1

CC-E I/I-1

CC-E I/I-2 Channel 1 input 0-20 mA or 4-20 mA

Channel 1 IN

OUT C

F

D

E

output 0-20 mA or 4-20 mA UL

IN

OUT 100 � � RL � 500 �

input 0-20 mA or 4-20 mA

Chanel 2 IN

A

H

B

G

OUT

output 0-20 mA or 4-20 mA UL

IN

OUT 100 � � RL � 500 �

Type

5

2CDC 282 004 F0205

CC-E I/I-2

Channel 2

Input signal

Output signal

Order code

Pack. unit piece

0-20 mA, 4-20 mA

0-20 mA, 4-20 mA

1SVR 010 200 R1600

1

0-20 mA, 4-20 mA

0-20 mA, 4-20 mA

1SVR 010 201 R0300

1

Price 1 piece

1 channel CC-E I/I-1 2 channel CC-E I/I-2

• Technical data .......................................................................... 218

ABB

• Dimensional drawings ...............................................................223

203 2CDC110004C0205

Analog standard signal converter CC-U/STD Ordering details

2CDC 281 002 F0t03

CC-U/STD universal signal converter with 3-way electrical isolation � � �

J J J J J J

More than 120 configurations possible Configurable output signal response on input voltage signal interruption (low fail safe / high fail safe) Adjustment and operating elements on the front Short-circuit proof signal outputs Plug-in connecting terminals for inputs, outputs and supply Very fast signal transmission enables use in control systems

� �

Adjustment range

� CC-U/STD

Continuously variable adjustment range: Example ➀: Input configuration: 0...10 V Output configuration: -5...5 V

Wiring instruction

OUT [%] 100 Gain “gain-coarse” und “gain-fine”

90 80

 Plug-in terminals

70 60

 Gain: Coarse adjustment

50 40

 Offset adjustment  U: green LED - supply voltage

30

Burden R � 4.7 k�

J

Burden R � 600 �

H

 Marker label

supply



20 10

IN [%] 10 20 30 40 50 60 70 80 90 100

Offset remote poti SW1.6 = +22.5 % SW1.4 = +100 %

2CDC 282 018 F0203

 Gain: Fine adjustment

G Pot.

2CDC 282 015 F0206

+ 2.5 V

SW1.5 = +50 %

5

DIP switch settings Coarse Type C C 5 1 8 3 0 6 2 8 3 0 3 3 D 0 6 4 2 5 B 3 4 1 4 3 D 5 -

Output

*) Detection of input voltage signal interruptions: If the input signal circuit is interrupted, the output signal changes to the adjusted minimum value (low fail safe) or maximum value (high fail safe). If "No fail safe" is configured, input signal interruptions are not detected.

Type CC-U/STD

2CDC110004C0205

Legend ON OFF no influence

Rated supply voltage

Order code

Pack. unit pieces

24-48 V DC 110-240 V AC

1SVR 040 000 R1700 1SVR 040 001 R0400

1 1

• Accessories . ............................................................................ 216 • Dimensional drawings .............................................................. 223

204

Switch 2 1 2 3 4 5 6

0...5 V 0...10 V 1...5 V 2...10 V -10...+10 V -5...+5 V -10...0 V -5...0 V 0...6.66 V -10...+3.33 V -5...+1.66 V 0...8 V 0...4 V -10...-2 V -5...-1 V 1.25...6.25 V -7.5...+2.5 V -3.75...+1.25 V 1.66...8.33 V -6.66...+6.66 V -3.33...+3.33 V -8...0 V -4...0 V 0...1 mA 0...20 mA 4...20 mA 0...10 mA 0...0.5 mA 0...13.33 mA 0...666 µA 0...16 mA 0...800 µA 0...8 mA 0...400 µA 2.5...12.5 mA 125...625 µA 3.33...16.66 mA 166...833 µA 0.2...1 mA 2...10 mA 100...500 µA

2CDC 282 003 F0204

Gain A...D A...D 4...5 0...1 7...9 3...4 0 5...7 2 7...9 2...4 0 3...4 3...4 B...F 0 5...7 3...4 2 4...5 A...D 2...4 4...5 0...1 4...5 4...2 B...F 4...6 -

2CDC 282 020 F0203

Switch 1 1 2 3 4 5 6 7 8

2CDC 282 019 F0203

Input Potentiometer 0...50 mV 0...100 mV 0...250 mV 0...500 mV 0...1 V 0...2.5 V 0...5 V 0...10 V 1...5 V 2... 10 V -10...+10 V 0...125 mV 0...8 V -22.5...+22.5 mV -11...+11 V 2.5...7.5 V 3.33...9.99 V 10...0 V 100...0 mV 0...1 mA 0...20 mA 4...20 mA 10...50 mA 20...4 mA 20...0 mA -0.45...+0.45 mA -55...+55 mA High fail safe *) Low faile safe *) No fail safe *)

Price 1 piece

• Technical data ...........................................................................219

ABB

Analog standard signal converter CC-U/STDR with relay output

2CDC 281 003 F0t03

Ordering details

CC-U/STDR universal signal converter for standard signals, with 2 threshold relay outputs and with 3-way electrical isolation � � � � � � � � �

J Standard signal converter with 7 setting ranges J 2 threshold relay outputs with one c/o contact each (threshold and respective hysteresis can be adjusted independently from each other) J Open-circuit or closed-circuit principle configurable by means of a DIP switch J 2 yellow LEDs for clear status indication of the output relays J Plug-in connecting terminals for inputs, outputs and supply Wiring instruction

Function diagrams Value R1 Closed-circuit principle R1 Threshold value

CC-U/STDR

Threshold

R1 Hysteresis

Hysteresis

Temperature

Value R2

 Threshold value for R1 supply

 Hysteresis for R1

 R2: yellow LED - Relay 2 energized  R1: yellow LED - Relay 1 energized  Marker label

11-14 R1 11-12 21-24 R2 21-22

Open-circuit principle

Input

R1 Threshold value

Switch 1 1 2 3 4 5 6

0...0 V 0...5 V 0...1 V -10...+10 V 1...5 V 0...20 mA 4...20 mA Output Closed-circuit principle Open-circuit principle

R1 Hysteresis Temperature R2 Hysteresis

Legend ON OFF no influence

2CDC 282 046 F0203

 U: green LED - supply voltage

R2 Threshold value

DIP switch settings

2CDC 282 003 F0204

 Hysteresis for R2

2CDC 282 005 F0204

 Threshold value for R2

2CDC 282 044 F0203

 Plug-in connecting terminals

2CDC 282 016 F0206

R2 Hysteresis

R2 Threshold value

11-14 R1 11-12 21-24 R2 21-22

Switching points Switching points of the output relay depending on the input range, configuration open-circuit principle IN [%]

tu al va l

ue

100

Ac

90 Threshold value R1 2-100 % of input range

80

Hysteresis R1 5-50 % of threshold value R1

70 60 50 40 Threshold value R2 2-100 % of input range

30 20

Hysteresis R2 5-50 % of threshold value R2

0

Type CC-U/STDR

R1

11-14 11-12

R2

21-24 21-22

OUT

Rated supply voltage

Order code

Pack. unit pieces

24-48 V DC 110-240 V AC

1SVR 040 010 R0000 1SVR 040 011 R2500

1 1

• Accessories . ............................................................................ 216 • Technical diagrams .................................................................. 223

ABB

2CDC 282 021 F0203

10

Price 1 piece

• Technical data ...........................................................................220 • Dimensional drawings ...............................................................223

205 2CDC110004C0205

5

Temperature signal converter for RTD sensors CC-E/RTD CC-E/RTD temperature signal converter for RTD sensors, linearized with 3-way electrical isolation

� � �

2 universally configurable devices (type CC-E/RTD) 2x12 single-function devices "Plug and Work", no adjustment of single-function devices required Temperature signal converter for PT100 sensors 2- or 3-wire connection DIP switch settings (universal devices)

Wiring instruction

Input 0...100 °C 0...300 °C G H

Burden R � 500 �

J

 Gain adjustment  Offset adjustment

supply 24 V DC or 110-240 V AC

 U: green LED - supply voltage  DIP switch for input and output configuration (only available on universal devices)

-50...+50 °C

-50...+250 °C

-50...+450 °C

Switch 1 1 2 3 4 5 6

0...10 V 0-20 mA 4-20 mA 0-10 V 0-20 mA 4-20 mA 0-10 V 0-20 mA 4-20 mA 0-10 V 0-20 mA 4-20 mA 0-10 V 0-20 mA 4-20 mA 0-10 V 0-20 mA 4-20 mA

High fail safe Low fail safe

Type

Output signal

Order code

Pack. unit piece

refer to table

0-10 V, 0-20 mA, 4-20 mA

1SVR 011 701 R25001)

1

CC-E RTD/V CC-E RTD/I CC-E RTD/I

PT100 0...100 °C

0-10 V 0-20 mA 4-20 mA

1SVR 011 730 R2500 1SVR 011 731 R1200 1SVR 011 732 R1300

1 1 1

CC-E RTD/V CC-E RTD/I CC-E RTD/I

PT100 -50...+50 °C

0-10 V 0-20 mA 4-20 mA

1SVR 011 733 R1400 1SVR 011 734 R1500 1SVR 011 735 R1600

1 1 1

CC-E RTD/V CC-E RTD/I CC-E RTD/I

PT100 0...300 °C

0-10 V 0-20 mA 4-20 mA

1SVR 011 736 R1700 1SVR 011 737 R1000 1SVR 011 738 R2100

1 1 1

CC-E RTD/V CC-E RTD/I CC-E RTD/I

PT100 -50...+250 °C

0-10 V 0-20 mA 4-20 mA

1SVR 011 739 R2200 1SVR 011 740 R0700 1SVR 011 741 R2400

1 1 1

refer to table

0-10 V, 0-20 mA, 4-20 mA

1SVR 011 706 R2200

1

CC-E RTD/V CC-E RTD/I CC-E RTD/I

PT100 0...100 °C

0-10 V 0-20 mA 4-20 mA

1SVR 011 788 R2400 1SVR 011 789 R2500 1SVR 011 790 R2200

1 1 1

CC-E RTD/V CC-E RTD/I CC-E RTD/I

PT100 -50...+50 °C

0-10 V 0-20 mA 4-20 mA

1SVR 011 791 R1700 1SVR 011 792 R1000 1SVR 011 793 R1100

1 1 1

CC-E RTD/V CC-E RTD/I CC-E RTD/I

PT100 0...300 °C

0-10 V 0-20 mA 4-20 mA

1SVR 011 794 R1200 1SVR 011 795 R1300 1SVR 011 796 R1400

1 1 1

CC-E RTD/V CC-E RTD/I CC-E RTD/I

PT100 -50...+250 °C

0-10 V 0-20 mA 4-20 mA

1SVR 011 797 R1500 1SVR 011 798 R2600 1SVR 011 799 R2700

1 1 1

Input signal

Legend ON OFF no influence

Price 1 piece

Supply voltage: 24 V DC universal CC-E/RTD

5

0...500 °C 2CDC 282 007 F0206

CC-E/RTD

Burden R � 1.0 k�

Output

2CDC 282 003 F0204



J J J J J

2CDC 282 006 F0204

2CDC 281 004 F0t03

Ordering details

single-function

Supply voltage: 110-240 V AC universal CC-E/RTD single-function



B 1604 Class I, Div.2 (universal device)

1)

206 2CDC110004C0205

• Technical data .......................................................................... 217

• Dimensional drawings ...............................................................223

ABB

Temperature signal converter for RTD sensors CC-U/RTD CC-U/RTD universal signal converter for PT10, PT100, PT1000 temperature sensors (acc. to IEC 751 and JIS C 16041), linearized with 3-way electrical isolation � � � � � �

J Configurable output signal response on input signal interruption (low fail safe / high fail safe) J Adjustment and operating elements on the front-side J Short-circuit proof signal outputs J Plug-in connecting terminals for inputs, outputs and supply 1) Japanese standard

Wiring instruction G Burden R � 4.7 k�

J

Burden R � 600 �

H

supply 24 V DC or 110-240 V AC

2CDC 282 017 F0206

2CDC 281 005 F0t03

Ordering details

Characteristic curves Resistance of PT10, PT100 and PT1000 sensors depending on the temperature

CC-U/RTD

PT1000

 Plug-in connecting terminals  Gain: Fine adjustment  Offset adjustment  U: green LED - supply voltage

Resistance [�]

 Gain: Coarse adjustment PT100

 Marker label

2CDC 282 022 F0203

PT10

Temperature [°C]

*) Detection of input signal interruptions: If the input signal circuit is interrupted, the output signal changes to the adjusted minimum value (low fail safe) or maximum value (high fail safe).

Type CC-U/RTD

Rated supply voltage

Order code

Pack. unit pieces

24-48 V DC 110-240 V AC

1SVR 040 002 R0500 1SVR 040 003 R0600

1 1

• Accessories . ............................................................................ 216 • Dimensional drawings .............................................................. 223

ABB

Legend ON OFF no influence

2CDC 282 003 F0204

Gain Coarse F E D C B A 9 8 F E B A 9 8 3 2 1 0 8 3 2 1 0 0 -

2CDC 282 023 F0203

Switch 1 Switch 2 Input Range 1 2 3 4 5 6 1 2 3 4 5 6 0...500 °C 0...550 °C 0...600 °C 0...650 °C PT10 0...700 °C 0...750 °C 0...800 °C 0...850 °C 0...50 °C 0...60 °C 0...70 °C 0...80 °C 0...90 °C PT100 0...100 °C 0...200 °C 0...300 °C 0...400 °C 0...500 °C 0...10 °C 0...20 °C 0...30 °C PT1000 0...40 °C 0...50 °C 0...60 °C Low fail safe *) High fail safe *) Type

Switch 3 1 2 3 4 5 6

0...5 V 0...10 V 1...5 V 2...10 V -10...+10 V -5...+5 V -10...0 V -5...0 V 0...6.66 V -10...+3.33 V -5...+1.66 V 0...8 V 0...4 V -10...-2 V -5...-1 V 1.25...6.25 V -7.5...+2.5 V -3.75...+1.25 V 1.66...8.33 V -6.66...+6.66 V -3.33...+3.33 V -8...0 V -4...0 V 0...1 mA 0...20 mA 4...20 mA 0...10 mA 0...0.5 mA 0...13.33 mA 0...666 µA 0...16 mA 0...800 µA 0...8 mA 0...400 µA 2.5...12.5 mA 125...625 µA 3.33...16.66 mA 166...833 µA 0.2...1 mA 2...10 mA 100...500 µA

2CDC 282 024 F0203

Output

DIP switch settings

Price 1 piece

• Technical data ...........................................................................219

207 2CDC110004C0205

5

Temperature signal converter for RTD sensors CC-U/RTDR with relay output CC-U/RTDR universal signal converter for temperature and resistance signals, with 2 threshold relay outputs and 3-way electrical isolation J Temperature signal converter for PT100 signals (5 ranges up to 800 °C) and variable resistances from 0-380 q J 2 threshold relay outputs with one c/o contact each (threshold and respective hysteresis can be adjusted independently from each other) J Open-circuit or closed-circuit principle configurable by means of a DIP switch J 2 yellow LEDs for clear status indication of the output relays J Plug-in connecting terminals for inputs, outputs and supply Wiring instruction Value R1

G

υ

Threshold

J

Value R2

K

 Threshold value for R2

M

supply 24 V DC or 110-240 V AC

 Hysteresis for R2

R1 Threshold value R1 Hysteresis Temperature R2 Hysteresis R2 Threshold value

11-14 R1 11-12 21-24 R2 21-22

DIP switch settings

Open-circuit principle R1 Threshold value

 R2: yellow LED - Relay 2 energized

R1 Hysteresis

Switch 1 1 2 3 4 5 6

Input PT100 0...100 °C 0...200 °C 0...400 °C 0...600 °C 0...800 °C

R2 Hysteresis

Output Closed-circuit principle Open-circuit principle

Legend ON OFF no influence

2CDC 282 046 F0203

 Marker label

Temperature

2CDC 282 007 F0204

 R1: yellow LED - Relay 1 energized

R2 Threshold value

11-14 R1 11-12 21-24 R2 21-22

Switching points Switching points of the output relay depending on the input range, configuration open-circuit principle IN [%]

va lu e

100

800

Ac tu

Threshold value R1 2-100 % of input range

600

al

90

700

80

Hysteresis R1 5-50 % of threshold value R1

70

500

60 50

400 300

40

Threshold value R2 2-100 % of input range

200

30 20

100

Hysteresis R2 5-50 % of threshold value R2

10 0 50

100

150

200

250

300

350

Resistance [�]

Type CC-U/RTDR

R1

11-14 11-12

R2

21-24 21-22

Rated supply voltage

Order code

Pack. unit pieces

24-48 V DC 110-240 V AC

1SVR 040 012 R2600 1SVR 040 013 R2700

1 1

• Accessories . ............................................................................ 216 • Technical diagrams .................................................................. 223

208 2CDC110004C0205

OUT

400

2CDC 282 025 F0203

Temperature υ [°C]

5

B (22) C (21) A (24)

R2

 Hysteresis for R1

Closed-circuit principle

Hysteresis

H

 Threshold value for R1

 U: green LED - supply voltage

E (12) F (11) D (14)

R1

2CDC 282 044 F0203

CC-U/RTDR  Plug-in connecting terminals

Function diagrams

2CDC 282 045 F0203

� � � � � � � � �

2CDC 282 003 F0204

2CDC 281 006 F0t03

Ordering details

Price 1 piece

• Technical data ...........................................................................220 • Dimensional drawings ...............................................................223

ABB

Temperature signal converter for thermocouples CC-E/TC

2CDC 281 007 F0t03

Ordering details

CC-E/TC analog signal converter for thermocouple signals of the types J and K with 3-way electrical isolation J 2 universally configurable devices (type CC-E/TC) J 2x6 single-function devices J "Plug and Work", no adjustment of single-function devices required � � �

Wiring instruction

DIP switch settings (universal devices)



supply 24 V DC or 110-240 V AC

 Gain adjustment

TC-J: 0...600 °C TC-K: 0...1000 °C

Output

Switch 1 1 2 3 4 5 6

0...10 V 0...20 mA 4...20 mA 0...10 V 0...20 mA 4...20 mA

High fail safe Low fail safe

Legend ON OFF no influence

2CDC 282 003 F0204

CC-E/TC

Input 2CDC 282 008 F0206

Burden R � 500 �

2CDC 282 009 F0204

Burden R � 1.0 k�

 Offset adjustment  U: green LED - supply voltage  DIP switch for input and output configuration (only available on universal devices)

Type

Input signal

Output signal

Order code

Pack. unit piece

0-10 V, 0-20 mA, 4-20 mA

1SVR 011 702 R26001)

1

Price 1 piece

Supply voltage: 24 V DC universal CC-E/TC

thermocouple types J and K

5

single-function CC-E TC/V CC-E TC/I CC-E TC/I

type J 0...600 °C

0-10 V 0-20 mA 4-20 mA

1SVR 011 750 R0100 1SVR 011 751 R2600 1SVR 011 752 R2700

1 1 1

CC-E TC/V CC-E TC/I CC-E TC/I

type K 0...1000 °C

0-10 V 0-20 mA 4-20 mA

1SVR 011 753 R2000 1SVR 011 754 R2100 1SVR 011 755 R2200

1 1 1

0-10 V, 0-20 mA, 4-20 mA

1SVR 011 707 R2300

1

Supply voltage: 110-240 V AC universal CC-E/TC

thermocouple types J and K

single-function



B 1604 Class I, Div.2 (universal device)

CC-E TC/V CC-E TC/I CC-E TC/I

type J 0...600 °C

0-10 V 0-20 mA 4-20 mA

1SVR 011 760 R0300 1SVR 011 761 R2000 1SVR 011 762 R2100

1 1 1

CC-E TC/V CC-E TC/I CC-E TC/I

type K 0...1000 °C

0-10 V 0-20 mA 4-20 mA

1SVR 011 763 R2200 1SVR 011 764 R2300 1SVR 011 765 R2400

1 1 1

1)

ABB

• Technical data .......................................................................... 217

• Dimensional drawings ...............................................................223

209 2CDC110004C0205

Temperature signal converter for thermocouples CC-U/TC Ordering details

� � � � � �

J Temperature signal converter for thermo- couples of the types K, J, T, S, E, N, R, B J Continuously adjustable voltage signal input 0-10 mV and 0-50 mV J Differential temperature meas. possible 1) J Configurable output signal response on input signal interruption (low fail safe / high fail safe) J Adjustment and operating elements on the front-side J Short-circuit proof signal outputs J Plug-in connecting terminals for inputs, outputs and supply

Wiring instruction Burden R � 4.7 k� Burden R � 600 �

supply

2CDC 282 018 F0206

2CDC 281 008 F0t03

CC-U/TC universal signal converter for thermocouples with 3-way electrical isolation

1)

 Plug-in connecting terminals

without cold-junction compensation:

DIP switch settings

switch SW2.2 = OFF

 Gain: Fine adjustment

Switch 1 Switch 2 Input Range 1 2 3 4 5 6 1 2 3 4 5 6 0-100...900 °C K 0-250...1350 °C J 0-100...750 °C 0-100...400 °C T -150-0...400 °C S 0-250...1550 °C 0-100...700 °C E 0-200...1000 °C 0-100...650 °C N 0-200...1300 °C 0-250...1350 °C R 0-450...1700 °C B 0-700...1750 °C 0-2...10 mV mV 0-10...50 mV Low fail safe *) High fail safe *)

Type

 Offset adjustment

*) Detection of input signal interruptions: If the input signal circuit is interrupted, the output signal changes to the adjusted minimum value (low fail safe) or maximum value (high fail safe).

Characteristic curves Thermocouple voltages depending on the temperature 80000

Typ E

75000

Typ J

70000 65000 60000

Typ K

55000 50000

Typ N

45000 40000 35000 30000 25000

Typ R Typ T

20000

Typ S

15000

Legend ON OFF no influence

2CDC 282 003 F0204

10000

Typ B

5000 0 -5000 -10000

1800

1750

1700

1650

1600

1550

1500

1450

1400

1350

1300

1250

1200

1150

1100

1050

1000

950

900

850

800

750

700

650

600

550

500

450

400

350

300

250

200

150

0

50

100

-50

-100

-150

-200

-250

-15000

Temperatur [°C]

Type CC-U/TC

Rated supply voltage

Order code

Pack. unit pieces

24-48 V DC 110-240 V AC

1SVR 040 004 R0700 1SVR 040 005 R0000

1 1

• Accessories . ............................................................................ 216 • Dimensional drawings .............................................................. 223

210 2CDC110004C0205

2CDC 282 026 F0103

5

0...5 V 0...10 V 1...5 V 2...10 V -10...+10 V -5...+5 V -10...0 V -5...0 V 0...6.66 V -10...+3.33 V -5...+1.66 V 0...8 V 0...4 V -10...-2 V -5...-1 V 1.25...6.25 V -7.5...+2.5 V -3.75...+1.25 V 1.66...8.33 V -6.66...+6.66 V -3.33...+3.33 V -8...0 V -4...0 V 0...1 mA 0...20 mA 4...20 mA 0...10 mA 0...0.5 mA 0...13.33 mA 0...666 µA 0...16 mA 0...800 µA 0...8 mA 0...400 µA 2.5...12.5 mA 125...625 µA 3.33...16.66 mA 166...833 µA 0.2...1 mA 2...10 mA 100...500 µA

2CDC 282 020 F0203

 Marker label

Switch 2 1 2 3 4 5 6

Output

Thermoelement-Spannung [µV]

 U: green LED - supply voltage

2CDC 282 010 F0204

 Gain: Coarse adjustment

2CDC 282 019 F0206

CC-U/TC

Price 1 piece

• Technical data ...........................................................................219

ABB

Temperature signal converter for thermocouples CC-U/TCR with relay output

2CDC 281 009 F0t03

Ordering details

CC-U/TCR universal signal converter for thermocouples, with 2 threshold relay outputs and 3-way electrical isolation � � � � � � � � �

J Temperature signal converter for thermocouples of the types K, J, T, S J 2 threshold relay outputs with one change-over contact each (threshold and respective hysteresis can be adjusted independently from each other) J Open-circuit or closed-circuit principle configurable by means of a DIP switch J 2 yellow LEDs for clear status indication of the output relays J Plug-in connecting terminals for inputs, outputs and supply Wiring instruction

Function diagrams Value R1 Closed-circuit principle R1 Threshold value

CC-U/TCR

R1 Hysteresis

Threshold

Hysteresis

Temperature

2CDC 282 044 F0203

R2 Hysteresis

2CDC 282 020 F0206

R2 Threshold value

 Plug-in connecting terminals

Value R2

 Threshold value for R1  Hysteresis for R1

supply

11-14 R1 11-12 21-24 R2 21-22

 Threshold value for R2

 R1: yellow LED - Relay 1 energized  Marker label

Open-circuit principle R1 Threshold value R1 Hysteresis

Switch 1 Input Type Range 1 2 3 4 5 6 0...240 °C J 0...480 °C 0...1200 °C 0...250 °C 0...500 °C K 0...1350 °C -150...+120 °C 0...220 °C T 0...400 °C 0...210 °C 0...380 °C S 0...860 °C 0...1550 °C Output Closed-circuit principle Open-circuit principle

Temperature R2 Hysteresis 2CDC 282 046 F0203

 R2: yellow LED - Relay 2 energized

DIP switch settings

R2 Threshold value

11-14 R1 11-12 21-24 R2 21-22

2CDC 282 003 F0204

 U: green LED - supply voltage

2CDC 282 004 F0204

 Hysteresis for R2

Legend ON OFF no influence

Switching points Switching points of the output relay depending on the input range, configuration open-circuit principle IN [%] 100

7000

Threshold value R1 = 1000 °C

Typ J

6500 6000

Thermocouple voltage [µV]

5500 5000

Typ K Release hysteresis

4500 4000 3500

Threshold value R2 = 400 °C

3000 2500

Typ T

Release hysteresis

2000 1500

Typ S

1000 500

0

0

OUT

-1000

Temperature [°C]

Type CC-U/TCR

R2

21-24 21-22

Rated supply voltage

Order code

Pack. unit pieces

24-48 V DC 110-240 V AC

1SVR 040 014 R2000 1SVR 040 015 R2100

1 1

• Accessories . ............................................................................ 216 • Technical diagrams .................................................................. 223

ABB

R1 1825

1725

1625

1525

1425

1325

1225

1125

925

1025

825

725

625

525

425

325

225

25

125

-75

-175

-275

-1500

11-14 11-12

2CDC 282 027 F0203

-500

Price 1 piece

• Technical data ...........................................................................220 • Dimensional drawings ...............................................................223

211 2CDC110004C0205

5

Measuring converter for sinusoidal and DC currents CC-E/I

2CDC 281 010 F0t03

Ordering details

CC-E/I current measuring converter for current signals 0-5 A, 0-20 A, AC/DC with 3-way electrical isolation J 2 universally configurable devices (type CC-E/I) J 2x6 single-function devices J "Plug and Work", no adjustment of single-function devices required � �

Wiring instruction

� �

Burden R � 500 �

CC-E/I supply 24 V DC or 110-240 V AC

2CDC 282 009 F0206

Burden R � 1.0 k�

 Gain adjustment Input range selection DIP switch settings (universal devices) Select input range by terminals

 DIP switch for input and output configuration (only available on universal devices)

Connected lines Used terminals Terminal marking Input range 20 A Connected lines Used terminals Terminal marking

Input I - DC I - AC I - DC I - AC I - DC I - AC

Output

Switch 1 1 2 3 4 5 6

0...10 V 0...20 mA 4...20 mA

Legend ON OFF

2CDC 282 002 F0204

Input range 5 A 2CDC 282 008 F0204

 U: green LED - supply voltage

2CDC 282 011 F0204

 Offset adjustment

5 Type

Input signal

Output signal

Order code

Pack. unit pieces

Price 1 piece

Supply voltage: 24 V DC universal CC-E/I

0-5 A, 0-20 A, AC/DC

0-10 V, 0-20 mA, 1SVR 011 703 R27001) 4-20 mA

1

single-function CC-E IAC/V CC-E IAC/I 0-5 A, 0-20 A, AC CC-E IAC/I

0-10 V 0-20 mA 4-20 mA

1SVR 011 770 R0500 1SVR 011 771 R2200 1SVR 011 772 R2300

1 1 1

CC-E IDC/V CC-E IDC/I 0-5 A, 0-20 A, DC CC-E IDC/I

0-10 V 0-20 mA 4-20 mA

1SVR 011 773 R2400 1SVR 011 774 R2500 1SVR 011 775 R2600

1 1 1

0-10 V, 0-20 mA, 4-20 mA

1SVR 011 708 R0400

1

CC-E IAC/V CC-E IAC/I 0-5 A, 0-20 A, AC CC-E IAC/I

0-10 V 0-20 mA 4-20 mA

1SVR 011 780 R1100 1SVR 011 781 R0600 1SVR 011 782 R0700

1 1 1

CC-E IDC/V CC-E IDC/I 0-5 A, 0-20 A, DC CC-E IDC/I

0-10 V 0-20 mA 4-20 mA

1SVR 011 783 R0000 1SVR 011 784 R0100 1SVR 011 785 R1100

1 1 1

Supply voltage: 110-240 V AC universal CC-E/I

0-5 A, 0-20 A, AC/DC

single-function



B 1604 Class I, Div.2 (universal device)

1)

212 2CDC110004C0205

• Technical data .......................................................................... 221

• Dimensional drawings ...............................................................223

ABB

Measuring converter for sinusoidal currents CC-E IAC/ILPO

2CDC 281 018 F0t04

Ordering details

CC-E IAC/ILPO current measuring without auxiliary power for sinusoidal currents 0-1 A, 0-5 A, output 4 - 20 mA



J J J J

Measuring converter for sinusoidal AC currents (0-1 A, 0-5 A) Measuring range selection by front-face sliding switch 4-20 mA output current in propotion to input current no additional power supply required

� �

Wiring instruction

CC-E IAC/ILPO  Gain adjustment 2CDC 282 010 F0b06

 Offset adjustment  Selection of measuring range

5 Type CC-E IAC/ILPO

Input signal

Order code

Pack. unit pieces

0-1 A, 0-5 A, AC

1SVR 010 203 R0500

1

• Technical data .......................................................................... 221

ABB

Price 1 piece

• Dimensional drawings ...............................................................223

213 2CDC110004C0205

Measuring converter for current RMS values CC-U/I

2CDC 281 012 F0t03

Ordering details

CC-U/I universal current measuring converter for RMS values of 0-1 A and 0-5 A, with 3-way electrical isolation � � �

J RMS converter for current signals up to 1 A and up to 5 A of any wave form (DC, DC with superimposed AC components, pure sinusoidal, triangular, phase-angle controlled, etc. in a measuring range of 0-600 Hz) J Adjustment and operating elements on the front J Short-circuit proof signal outputs J Plug-in connecting terminals for inputs, outputs and supply

� DIP switch settings Output

Burden R � 600 �

 Plug-in connecting terminals supply 24 V DC or 110-240 V AC

 Gain adjustment

2CDC 282 021 F0206

Burden R � 4.7 k�

CC-U/I

 Offset adjustment  U: green LED - supply voltage  Marker label

Input range selection

Select input range by terminals Input range 1 A

5

J 5A

H 1A

G C

Input range 5 A Connected lines Used terminals Terminal marking

J 5A

H 1A

G C

2CDC 282 033 F0203

Connected lines Used terminals Terminal marking

Switch 1 1 2 3 4 5 6

0...5 V 0...10 V 1...5 V 2...10 V -10...+10 V -5...+5 V -10...0 V -5...0 V 0...6.66 V -10...+3.33 V -5...+1.66 V 0...8 V 0...4 V -10...-2 V -5...-1 V 1.25...6.25 V -7.5...+2.5 V -3.75...+1.25 V 1.66...8.33 V -6.66...+6.66 V -3.33...+3.33 V -8...0 V -4...0 V 0...1 mA 0...20 mA 4...20 mA 0...10 mA 0...0.5 mA 0...13.33 mA 0...666 µA 0...16 mA 0...800 µA 0...8 mA 0...400 µA 2.5...12.5 mA 125...625 µA 3.33...16.66 mA 166...833 µA 0.2...1 mA 2...10 mA 100...500 µA

Legend ON OFF no influence

2CDC 282 003 F0204

Wiring instruction

2CDC 282 029 F0203



Example of application RMS measurement and conversion of a current signal

IN [%]

Gain �15 %

I(t) [A] 5 4 3 2 1

resulting RMS value

0 t

-1

0

50

OUT [%]

100

-2 2CDC 282 028 F0203

Offset �20 %

-3 -4 -5

Type CC-U/I

Rated supply voltage

Order code

Pack. unit pieces

24-48 V DC 110-240 V AC

1SVR 040 006 R0100 1SVR 040 007 R0200

1 1

• Accessories . ............................................................................ 216 • Dimensional drawings .............................................................. 223

214 2CDC110004C0205

Price 1 piece

• Technical data ...........................................................................222

ABB

Measuring converter for voltage RMS values CC-U/V

2CDC 281 013 F0t03

Ordering details

CC-U/V universal voltage measuring converter for RMS values of 0-600 V, with 3-way electrical isolation � � � � �

J RMS converter for voltage signals up to 600 V of any wave form (DC, DC with superimposed AC components, pure sinusoidal, triangular, phase-angle controlled, etc. in a measuring range of 0-600 Hz) J Adjustment and operating elements on the front J Short-circuit proof signal outputs J Plug-in connecting terminals for inputs, outputs and supply Wiring instruction

DIP switch settings



Burden R � 600 �

 Input voltage range selection

supply 24 V DC or 110-240 V AC

 Gain adjustment

2CDC 282 022 F0206

Burden R � 4.7 k�

 Offset adjustment  U: green LED - supply voltage Input range selection

Selecting input range by front-face rotary switch 0...100 V 0...150 V 0...250 V 0...300 V 0...400 V 0...450 V 0...550 V 0...600 V

Switch position 1 2 3 4 5 6 7 8

2CDC 282 012 F0204

 Marker label

5 2CDC 282 029 F0203

CC-U/V  Plug-in connecting terminals

Switch 1 1 2 3 4 5 6

0...5 V 0...10 V 1...5 V 2...10 V -10...+10 V -5...+5 V -10...0 V -5...0 V 0...6.66 V -10...+3.33 V -5...+1.66 V 0...8 V 0...4 V -10...-2 V -5...-1 V 1.25...6.25 V -7.5...+2.5 V -3.75...+1.25 V 1.66...8.33 V -6.66...+6.66 V -3.33...+3.33 V -8...0 V -4...0 V 0...1 mA 0...20 mA 4...20 mA 0...10 mA 0...0.5 mA 0...13.33 mA 0...666 µA 0...16 mA 0...800 µA 0...8 mA 0...400 µA 2.5...12.5 mA 125...625 µA 3.33...16.66 mA 166...833 µA 0.2...1 mA 2...10 mA 100...500 µA

Legend ON OFF no influence

2CDC 282 003 F0204

Output

Example of application RMS measurement and conversion of a phase-angle controlled voltage signal L1 = 230 V

INUeff [V] U(t) [V] resulting RMS value

Gain �15 %

OUT [%]

0 0

50

100

Offset �20 % -300 operating angle

Type CC-U/V

Rated supply voltage

Order code

Pack. unit pieces

24-48 V DC 110-240 V AC

1SVR 040 008 R1300 1SVR 040 009 R1400

1 1

• Accessories . ............................................................................ 216 • Dimensional drawings .............................................................. 223

ABB

2CDC 282 030 F0203

300

Price 1 piece

• Technical data ...........................................................................222

215 2CDC110004C0205

Analog signal converters Accessories for CC-U range Ordering details

2CDC 252 187 F0005

62,5 2.46”

10 .394” 22,5 .886”

4,5 .177”

11,5 .453”

Accessories Adapter for screw mounting Type

ADP.01

60 2.36”

for type

Width in mm

Order code

Pack. unit pieces

CC-U

22.5

1SVR 430 029 R0100

1

for type

Order code

Pack. unit pieces

CC-U

1SVR 366 017 R0100

1

Price 1 piece

Weight 1 piece kg / lb

Price 1 piece

Weight 1 piece kg / lb

Price 1 piece

Weight 1 piece kg / lb

20 .787”

MAR.01

Marker label

2CDC 252 186 F0005

3A11

8 .315”

ADP.01

Type

7 .275” 3,5 .138”

68,5 2.70 ”

22,5 .886”

5

2CDC 252 185 F0005

MAR.01

Sealable transparent cover Type

COV.01

for type

Width in mm

Order code

Pack. unit pieces

CC-U

22.5

1SVR 430 005 R0100

1

front-to-back size 107

Sealable cover COV.01

216 2CDC110004C0205

ABB

Analog signal converters CC-E/STD, CC-E x/x, CC-E/RTD, CC-E/TC Technical data Type Input circuits - Analog inputs

CC-E/STD J-G-H

Input signal Rated input range

Current

Voltage

1 M

50  -

Output circuits - Analog outputs Output signal Output burden Accuracy 1) Residual ripple Response time Transmission frequency Reaction to input circuit interruption

D-F, A-C

Supply circuits Supply voltage Supply voltage tolerance Power consumption

K-M

-50...+500 °C

< 0.01 %/ ± 5 % (universal devices) ± 5 % (universal devices) 100 dB

TC.K: 0...1000 °C, TC.J: 0...600 °C < 0.5 % / 100 

> 35 dB

DC versions 24 V DC -15...+15 % 1.5 W typ.

AC versions 110-240 V AC - 50/60 Hz -15...+10 % 1.5 VA typ.

5

U: green LED

General data Ambient temperature range

operation storage

0...+60 °C -20...+80 °C ± 500 ppm/°C IP20 ventilation slots on top and bottom DIN rail, snap-on mounting

rigid fine-strand

4 mm2 (10 AWG) 2.5 mm2 (14 AWG)

Temperature coefficient Degree of protection (DIN 40050) Mounting position Mounting Electrical connection Wire size

EN 61000-6-2 Level 3 (±6 kV / ±8 kV)

IEC/EN 61000-4-2

10 V/m

IEC/EN 61000-4-3 IEC/EN 61000-4-4 IEC/EN 61000-4-5 IEC/EN 61000-4-6 EN 61000-6-4

Isolation data Test voltage between all isolated circuits Rated insulation voltage

2)

PT100

CC-E/TC Thermocouples (IEC 584-1 and 2) TC.K, TC.J

Current Voltage 0-20 mA, 4-20 mA 0-5 V, 0-10 V m 500   1.0 K ± 0.5 % of full-scale < 0.5 % 200 µs 10 ms 2 kHz 80 Hz 2 Hz (up to -3 dB) Low fail safe: Output voltage > 15 % of measuring range 2) Low fail safe: Output voltage < -0.6 V, output current = 0 mA

Indication of operational states Rated control supply voltage US

1)

Temperature sensors

Standard signals 0...5 V / 0...20 mA / 0...10 V / 4...20 mA -10...+10 V +55 mA ± 11 V -

Limitation of input signals Influence of line resistance Gain adjustment range Offset adjustment range Input impedance Suppression at 50 Hz Common-mode rejection

Electromagnetic compatibility Interference immunity electrostatic discharge (ESD) electromagnetic field (HF radiation resistance) fast transients (Burst) powerful impulses (Surge) HF line emission Interference emission

CC-E/RTD

Level 3 (±2 kV / 5 kH) ±2 kV / ±1 kV 10 V class B

-

2.5 kV AC -

-

includes: non-linearity, factory setting, drift of temperature, supply voltage and output load Only -/RTD and -/TC: Single-function devices respond with Low fail safe to input signal interruptions

ABB

217 2CDC110004C0205

Analogsignal converter CC-E I/I-1, CC-E I/I-2 Technical data Type Input circuits - Analog inputs Input current IIN Min. input current Max. input current Input voltage UIN Input voltage drop Ui Max. input voltage

CC-E I/I channel 1: A (+), B (-), channel 1 or 2: C (+), D (-)

Output circuits Output current IOUT Output load RL Output voltage UOUT Residual ripple Response time (0-100 %)

channel 1: H (+), G (-), channel 2: F (+), E (-) 0-20 mA, 4-20 mA 0-500  IOUT x RL < 20 mVpp (500 , 20 mA) < 15 ms (0-500 , 20 mA), < 5 ms (500 , 20 mA, 25 °C)  0.1 % of full-scale (20 mA)  0.05 % / 100 ,  -0.1 % / 100  (25 °C)

Accuracy Load influence (0-500 ) General data Width of the enclosure Weight

5

Current 0-20 mA, 4-20 mA < 100 µA 50 mA1) (VIN < 18 V) < 2.5 V + (IIN x RL) < 2.5 V (20 mA, RL = 0 ) 18 V1) (IIN < 50 mA)

Temperature coefficient Mounting

18 mm approx. 0.037 kg (0.082 lb) approx. 0.044 kg (0.097 lb) any IP20 / IP20 -25...+60 °C -40...+85 °C < 50 ppm / °C DIN rail (EN 50022)

Electrical connection Wire size

max. 2.5 mm2 (14 AWG)

Standards Product standard Low Voltage Directive EMC Directive

EN 50178 2006/95/EC 2004/108/EC

Mounting position Degree of protection Ambient temperature range

1 channel 2 channel enclosure / terminals operation storage

Electromagnetic compatibility Interference immunity electrostatic discharge (ESD) electromagnetic field (HF radiation resistance) fast transients (Burst) powerful impulses (Surge) HF line emission magnetisches Feld Interference emission Radiated noise Operational reliability (EN 68-2-6) Mechanical resistance (EN 68-2-6) Environmental testing (IEC 68-2-30 Db) Isolation data Insulation voltage input / output Insulation voltage between channels Pollution category Overvoltage category

1)

EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-6 EN 61000-4-8 EN 55011

EN 61000-6-2 Level 3 (±6 kV / ±8 kV) 10 V/m Level 3 (±2 kV / 5 kH) ±2 kV / ±1 kV 10 V 30 A/m EN 61000-6-4 class B 4g 10 g 24 h cycle, 55 °C, 93 % rel., 96 h 500 Veff / 50 Hz

(device with 2 channels)

5 kVeff / 50 Hz 2 II

The input parameters have to be limited to the indicated maximum values.

218 2CDC110004C0205

ABB

Analog signal converters CC-U/STD, CC-U/RTD, CC-U/TC Technical data Type Input circuits - Analog inputs

CC-U/STD J-G-H

Input signal

Current 0-20 mA 4-20 mA 10-50 mA 0-1 mA

Limitation of input signals Rated input range

± 55 mA -

Influence of line resistance Gain adjustment range (universal devices) Offset adjustment range (universal devices) Input impedance without detection of input signal interruption with detection of input signal interruption Suppression at 50 Hz Common-mode rejection Output circuits - Analog outputs Output signal Output burden Accuracy 1) Residual ripple Response time Transmission frequency Supply circuits Rated supply voltage Supply voltage range Supply voltage tolerance Rated frequency Power consumption

D-F, A-C

CC-U/RTD

PotentioVoltage meter 0-100 mV 470  0-1 V 1 M 2) 0-5 V 1-5 V 0-10 V 2-10 V ± 10 V ± 11 V -

-

0.945 mV 110 mA 22 V -137.5...+62.5 % for different ranges 51  6 M 3 G 51  3.5 M 9.5 G



< 0.01 % / 100 

±5% 120 dB

± 10 % > 40 dB 105 dB

5

24-48 V DC 110-240 V AC 24-48 V DC / 24 V AC 110-240 V AC / 100-300 V DC DC: -15...+15 % AC: -15...+10 % 0 Hz or 50/60 Hz 2 W at 24 V DC 4.5 VA at 230 V AC

operation storage

-20...+60 °C -40...+80 °C ±150 ppm/°C

±250 ppm/°C

±200 ppm/°C at min. offset ±400 ppm/°C at max. offset

any DIN rail, snap-on mounting / screw mounting with adapter rigid fine-strand

IEC/EN 61000-4-2 IEC/EN 61000-4-3 IEC/EN 61000-4-4 IEC/EN 61000-4-5 IEC/EN 61000-4-6 EN 61000-6-4

plug-connector with screw terminals 1.5 mm2 (16 AWG) plug-connector with screw terminals 2.5 mm2 (14 AWG) EN 61000-6-2 Level 3 (±6 kV / ±8 kV) 10 V/m Level 3 (±2 kV / 5 kH) 2 kV / 1 kV 10 V Class B 1.5 kV

Test voltage (between all isolated circuits)

1.5 kV / 50 Hz

2)

refer to temperature specs. of individual thermocouples

see DIP switch settings

Isolation data Isolation test (between all isolated circuits)

1)

-

U: green LED

Mounting position Mounting

Electromagnetic compatibility Interference immunity electrostatic discharge (ESD) electromagnetic field (HF radiation resistance) fast transients (Burst) powerful impulses (Surge) HF line emission Interference emission

Max. temperature adjustable: 6-60 °C for PT1000 50-500 °C for PT100 500-850 °C for PT10 0.015 °C/

K-M

Temperature coefficient

Electrical connection Wire size

PT10, PT100, PT1000 (IEL 751 and JICC 1604)

Current Voltage 0-20 mA, 4-20 mA 0-5 V, 1-5 V, 0-10 V, 2-10 V, ± 10 V  600   4.7 K ±0.1 % of full-scale ±0.2 % of full-scale ±0.1 % of full-scale < 0.15 % 200 µs 10 ms 200 ms 1 kHz 80 Hz 2 Hz (to -3 dB)

Indication of operational states Supply voltage General data Ambient temperature range

Temperature sensors

CC-U/TC Thermocouples (IEC 584-1 and 2) TC.K TC.J TC.T TC.S TC.E TC.N TC.R TC.B

includes: non-linearity, factory setting, drift of temperature, supply voltage and output load Detection of an input signal break (fail safe) and resistance > 10 kq results in a linearity of w0,2 %.

ABB

219 2CDC110004C0205

Analog signal converters with relay output CC-U/STDR, CC-U/RTDR, CC-U/TCR Technical data Type Input circuits - Analog inputs

CC-U/STDR J-H

Measuring signal / input range

Minimum switching voltage Minimum switching current / Response time Mechanical lifetime Electrical lifetime

5

E-D-F, B-C-A

at AC12, 230 V, 4 A

operation storage

-20...+60 °C -40...+80 °C ±300 ppm/°C any DIN rail (EN 50 022), snap-on mounting / screw mounting with adapter

rigid fine-strand

plug-connector with screw terminals 1.5 mm2 (16 AWG) plug-connector with screw terminals 2.5 mm2 (14 AWG)

IEC/EN 61000-4-2 IEC/EN 61000-4-3 IEC/EN 61000-4-4 IEC/EN 61000-4-5 IEC/EN 61000-4-6 EN 61000-6-4

Isolation data Insulation voltage (between all isolated circuits) Test voltage (between all isolated circuits)

220 2CDC110004C0205

24-48 V DC 110-240 V AC 24-48 V DC / 24 V AC 110-240 V AC / 100-300 V DC DC: -15...+15 % AC: -15...+10 % 0 Hz or 50/60 Hz 2 W at 24 V DC 4.5 VA at 230 V AC U: green LED R1: yellow LED / R2: yellow LED

Temperature coefficient Mounting position Mounting

Electromagnetic compatibility Interference immunity electrostatic discharge (ESD) electromagnetic field (HF radiation resistance) fast transients (Burst) powerful impulses (Surge) HF line emission Interference emission

(IEC 584-1 and 2) TC.K, TC.J TC.T, TC.S

K-M

Indication of operational states Supply voltage 1st / 2nd output relay energized

Electrical connection Wire size

Temperature sensors

CC-U/TCR Thermocouples

Relay, 2 c/o contacts 250 V AC 4A 3A 4A 2A 12 V 10 mA / 0.6 VA (W) 10 ms 30 x 106 switching cycles 0.1 Mio. switching cycles

AC12 (resistive) 230 V AC15 (inductive) 230 V DC12 (resistive) 24 V DC13 (inductive) 24 V

Supply circuits Rated supply voltage Supply voltage range Supply voltage tolerance Rated frequency Power consumption

General data Ambient temperature range

Voltage

0-20 mA 0-1 V / 1-5 V PT100 4-20 mA 0-10 / ±10 V approx. 50  approx. 1,5 M 2-100 % of selected input range 5-50 % of threshold ±0.5 % of full-scale

Input resistance Adjustable threshold Adjustable hysteresis Repeat accuracy (constant parameters) Output circuits - Relay outputs Rated switching voltage Rated switching current

Current

CC-U/RTDR

EN 61000-6-2 Level 3 (±6 kV / ±8 kV) 10 V/m Level 3 (±2 kV / 5 kH) 2 kV / 1 kV 10 V Class B 2.5 kV 2.5 kV

ABB

Analog signal converters CC-E/I, CC-E IAC/ILPO Technical data Type

CC-E/I J-G-H

Input circuits - Analog inputs Rated input range Measuring frequency Overload capacity of inputs

input range 1 input range 2

Gain adjustment range Offset adjustment range Input impedance / resistance Output circuits - Analog outputs

Accuracy 1) Offset adjustment range Gain adjustment range Residual ripple Response time Transmission frequency Reaction to input circuit interruption Supply circuits Supply voltage Supply voltage tolerance Power consumption

K-M

Indication of operational states Supply voltage General data Ambient temperature range

operation storage

Temperature coefficient Degree of protection (DIN 40050) Mounting position Mounting

DC current

2 meas. ranges selectable

0-5 A / 0-20 A

0-1 A / 0-5 A / sinusoidal 50/60 Hz 10 x INom (50 A) for max. 2 s 10 x INom (200 A) for max. 2 s 5 m

10 x INom (50 A) for max. 1 s 10 x INom (200 A) for max. 1 s ±5 % (universal devices) ±5 % (universal devices) 20 A : 2.5 m 5A : 65 m D-F Current

A-C Voltage

DC versions 24 V DC -15...+15 % typ 1.5 W

AC versions 110-240 V AC 50/60 Hz -15...+10 % typ 1.5 VA

5

12-30 V DC -

U: green LED

-

0...+60 °C -20...+80 °C ± 500 ppm/°C

-20...+60 °C -40...+80 °C 300 ppm/°C

IP20 ventilation slots on top and bottom DIN rail, snap-on mounting

Electrical connection Wire size

rigid fine-strand

4 mm2 (12 AWG) 2.5 mm2 (14 AWG)

1x2.5 mm2 (1x14 AWG)

EN 61000-6-2 Level 3 (±6 kV / ±8 kV)

IEC/EN 61000-4-2

10 V/m

IEC/EN 61000-4-3 IEC/EN 61000-4-4 IEC/EN 61000-4-5 IEC/EN 61000-4-6 EN 61000-6-4

Isolation data Test voltage (between all isolated circuits) Rated insulation voltage

1)

AC current 0-5 A / 0-20 A

F-E passive current output in proportion to input current 0-20 mA / 4-20 mA 0-10 V 4-20 mA 12 V DC: 150 ,  500   1.0  24 V DC: 750  30 V DC: 1050  ± 2 % of full-scale ±5 % (universal device) ±5% ±5 % (universal device) ± 20 % < 0.5 % 0.5 s 0.6 s DC or 50/60 Hz AC: 50/60 Hz Low fail safe: output voltage < 200 mA, output current < 400 µA

Output signal Output burden / load

Electromagnetic compatibility Interference immunity electrostatic discharge (ESD) electromagnetic field (HF radiation resistance) fast transients (Burst) powerful impulses (Surge) HF line emission Interference emission

CC-E IAC/ILPO C-D

Level 3 (±2 kV / 5 kH) ±2 kV / ±1 kV 10 V Class B 2.5 kV AC -

250 V AC

includes: non-linearity, factory setting, drift of temperature, supply voltage and output load

ABB

221 2CDC110004C0205

Analog signal converters CC-U/I, CC-U/V Technical data Type Input circuits - Analog inputs

J-G-H

Rated input range Measuring frequency Overload capacity of inputs

0-600 Hz input range 1 input range 2

10 x INom (10 A) for max. 2 s 10 x INom (50 A) for max. 2 s

D-F, A-C

Current 0-20 mA, 4-20 mA  600 

Voltage 0-5 V, 1-5 V, 0-10 V, 2-10 V, ± 10 V  4.7 K ±0.5 % of full-scale ±250 ppm/°C max. ±300 ppm/°C max. < 0.15 % 150 ms

K-M 24-48 V DC 24-48 V DC, 24 V AC DC: -15...+15 % 2 W at 24 V DC

110-240 V AC 110-240 V AC, 100-300 V DC AC: -15...+10 % 0 Hz or 50/60 Hz 4.5 VA at 230 V AC U: green LED

operation storage

-20...+60 °C -40...+80 °C any DIN rail (EN 50022), snap-on mounting / screw mounting with adapter

rigid fine-strand

plug-connector with screw terminals 1.5 mm2 (16 AWG) plug-connector with screw terminals 2.5 mm2 (14 AWG)

Mounting position Mounting Electrical connection Wire size

±15 % ±20 % > 800 k

Indication of operational states Supply voltage General data Ambient temperature range

-

1A: 60 m, 5 A: 12 m

Supply circuits Rated supply voltage Supply voltage range Supply voltage tolerance Rated frequency Power consumption

5

CC-U/V any voltage signals, RMS measurement 0-100 V, 0-200 V 0-300 V, 0-400 V 0-500 V, 0-600 V

0-1 A 0-5 A

Gain adjustment range Offset adjustment range Input impedance / resistance Output circuits - Analog outputs Output signal Output load Accuracy1) Temperature coefficient Residual ripple Response time

CC-U/I any current signals, RMS measurement

Standards Product standard Low Voltage Directive EMC Directive RoHS Directive Electromagnetic compatibility Interference immunity electrostatic discharge (ESD) electromagnetic field (HF radiation resistance) fast transients (Burst) powerful impulses (Surge) HF line emission Interference emission

IEC/EN 61000-4-2 IEC/EN 61000-4-3 IEC/EN 61000-4-4 IEC/EN 61000-4-5 IEC/EN 61000-4-6 EN 61000-6-4

EN 61000-6-2 Level 3 (±6 kV / ±8 kV) 10 V/m Level 3 (±2 kV / 5 kH) 2 kV / 1 kV 10 V Class B

Isolation data Insulation voltage (between all isolated circuits) Test voltage (between all isolated circuits)

1)

1.5 kV 1.5 kV / 50 Hz

includes: non-linearity, factory setting, drift of temperature, supply voltage and output load

222 2CDC110004C0205

ABB

Analog signal converters CC-E, CC-U

Technical diagr., Connection diagr., Dimensional drawings Technical diagrams

Connection diagram CC-U/x Width 22.5 mm (0.89 in)

Load limit curves CC-U/xxR Resistive DC load

L

K

J

H

G

1.0 0.9

D

E

F

A

B

C

0.8

2CDC 282 023 F0b06

Derating curve

M

2CDC 282 026 F0b06

2CDC 282 025 F0b06

Resistive AC load

F 0.7

0.5

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

cos

1.0

2CDC 282 014 F0b06

0.6

5 Dimensional drawnings

Dimensions in mm

2CDC 282 011 F0b06

22.5 0,88 "

18 0.71"

2CDC 282 012 F0b06

CC-E IAC/ILPO, CC-E I/I

CC-E/x

.039

ABB

2CDC 282 024 F0b06

CC-U/x , CC-U/xR

223 2CDC110004C0205

Related Documents


More Documents from "Sonia Eloued"

Abb Price Book 303
June 2020 3
Abb Price Book 687
June 2020 2
Abb Price Book 329
June 2020 4
Abb Price Book 259
June 2020 3
Abb Price Book 355
June 2020 6
Abb Price Book 483
June 2020 4