ABB
Analog signal converters CC range
Content Benefits and advantages.................................................................................................. 200 Application......................................................................................................................... 201 Approvals and marks........................................................................................................ 201 Ordering details Analog standard signal converters CC-E/STD, CC-E x/x.................................................................................................... CC-E I/I......................................................................................................................... CC-U/STD..................................................................................................................... CC-U/STDR.................................................................................................................. Temperature signal converters for RTD sensors CC-E/RTD..................................................................................................................... CC-U/RTD..................................................................................................................... CC-U/RTDR.................................................................................................................. Temperature signal converters for thermocouples CC-E/TC....................................................................................................................... CC-U/TC....................................................................................................................... CC-U/TCR..................................................................................................................... Measuring converters for currents (E/I) and (U/I) and voltages (U/V) CC-E/I........................................................................................................................... CC-E IAC / ILPO............................................................................................................. CC-U/I........................................................................................................................... CC-U/V.......................................................................................................................... Accessories................................................................................................................... Technical data CC-E/STD, CC-E x/x, CC-E/RTD, CC-E/TC................................................................. CC-E I/I......................................................................................................................... CC-U/STD, CC-U/RTD, CC-U/TC................................................................................ CC-U/STDR, CC-U/RTDR, CC-UTCR.......................................................................... CC-E/I, CC-E IAC / ILPO................................................................................................ CC-U/I, CC-U/V............................................................................................................ Technical diagrams.............................................................................................................. Dimensional drawings.........................................................................................................
ABB
202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 223
199 2CDC110004C0205
5
Analog signal converters CC range
2CDC 285 001 F0b05
Benefits and advantages
CC-U range
CC-E range
J J J J J J
J Universally configurable devices and single-function devices
8 different standard signal outputs on one device Input and output side universally configurable Also available with 2 threshold relay outputs Adjustment and operating elements on the front side Safe operation by electrical 3-way isolation Plug-in connecting terminals, unambiguously and clearly marked
Conversion, measurement and separation of J J J J
standard signals signals of RTD sensors (PT10, PT100, PT1000) thermocouple signals RMS values of currents and voltages
Characteristics J The required input and output ranges can be configured for all devices by means of directly accessible DIP switches positioned on the side. J Due to the wide input range of the gain and offset stages all input signals between the minimum and the maximum input value can be universally converted to all common output signals. J Devices for DC or AC (50/60 Hz) supply available.
J Adjustment and operating elements on the front side J Safe operation by electrical 3-way isolation J Unambiguous and clear connecting terminal markings Conversion, measurement and separation of J J J J
standard signals (0-5 V, 0-10 V, 0-20 mA, 4-20 mA) temperature signals of RTD sensors (PT 100) thermocouple signals (types J and K) current measurement signals (0-5 A, 0-20 A AC/DC)
Characteristics of single-function devices J No adjustment or balancing necessary. Characteristics of universal devices J The required input and output ranges can be configured by means of directly accessible DIP switches positioned on the side J Gain adjustment of ± 5 % by means of an adjustment potentiometer on the front-side J Offset adjustment of ±5 % by means of adjustment potentiometers on the front-side
2CDC 283 016 F0b03
5
Product range for analog signal processing
200 2CDC110004C0205
ABB
Analog signal converters CC range
Application, Approvals and marks Applications for analog signal processing and correct solution using CC-E and CC-U converters
0-10 V
Nearly every process includes a control system that receives data by means of analog signals and then evaluates the data and sets the respective parameters correspondingly.
0-10 V
Controller e.g. AC500 1. Analog signal converter (e.g. CC-E or CC-U)
2. Analog signal converter (e.g. CC-E or CC-U)
When transmitting analog signals numerous problems may arise which can disturb or even block an ideal behavior of the process. 100 m
0-20 mA
100 m
Below we have listed some processing problems together with the
4-20 mA Actuator
respective solutions to solve these problems:
Measuring sensor
2CDC 282 013 F0206
Signal conversion Sometimes the available signals cannot be processed by the controller or the actuator. In this case, signal converters are required to convert the input signal (or different input signals) to the desired output signal.
Signal amplification
Signal separation
If long lines or high burdens have to be operated, it may be necessary to amplify the signal. CC analog signal converters require only low input power and provide high output power.
J Protection against overvoltage The increased use of micro-electronics make controls much more sensitive against overvoltages, resulting from lightning discharges or switching processes. Suppression diodes are incorporated in the input of the CC analog signal converters which enable the converters to arrest overvoltages with low energy level (resulting from switching processes) by themselves. The products furthermore provide electrical isolation between input, output and supply circuit for protection of the controller connected to the output.
Thus, there are no restrictions for the converter's position on the line, i.e. it can be used J for signal refreshing at the end of the line (low input power) J or for signal amplification at the beginning of the line (high output power).
J Protection against ground loops Signal filtering If components are used which refer to ground, the measuring signals can be falsified by a so-called ground loop. In this case, Particularly on long lines or in rough industrial environments the signals certain parts of the signal are transmitted via earth and not via the are exposed to high electromagnetic interferences. The frequency of analog transmission line, thus causing incorrect evaluation of the the coupled interference signals may be in the range of the common signal. The electrical isolation between the input and the output mains frequency (50 Hz) or even much higher (in case of frequency disconnects these ground loops and thus enables correct signal converters). According to the specific requirements, analog signal transmission. converters are available which provide reliable suppression of those interferences by means of an input low-pass filter.
J
J
J
G
J
J
J
J
A
UL 1604 (Class I, Div 2, hazardous locations), CAN/CSA C22.2 No.213
G
K
CB scheme
J
J
J
E
CCC
J
J
J
J
CC-U/V
CC-E/I
J
UL 508, CAN/CSA C22.2 No.14
CC-U/I
CC-U/TCR
J
A
Approvals
CC-E IAC/ILPO
CC-U/TC
J
CC-E/TC
CC-U/RTD
G
CC-U/RTDR
CC-E/RTD
J
CC-U/STD
J
CC-E I/I
J
CC-E/STD
CC-U/STDR
J existing G existing for some devices j pending
J
J
J
J
J
G
Marks a
CE
J
J
J
J
J
J
J
J
J
J
J
J
J
J
b
C-Tick
J
J
J
J
J
J
J
J
J
J
J
J
J
J
ABB
201 2CDC110004C0205
5
Analog standard signal converters CC-E/STD, CC-E x/x Ordering details
J 2 universally configurable devices (type CC-E/STD) J 2x10 single-function devices J "Plug and Work", no adjustment of single-function devices required Wiring instruction
DIP switch settings (universal devices)
�
Input
�
0...5 V
Burden R � 500 �
CC-E/STD supply 24 V DC or 110-240 V AC
2CDC 282 006 F0206
Burden R � 1.0 k�
�
0...10 V
0...20 mA
2CDC 281 014 F0t04
4...20 mA
Type �
CC-E V/V
5
Input signal
Output
Switch 1 2 3 4 5 6 7 8
0...5 V 0...10 V 0...20 mA 4...20 mA 0...5 V 0...10 V 0...20 mA 4...20 mA 0...5 V 0...10 V 0...20 mA 4...20 mA 0...5 V 0...10 V 0...20 mA 4...20 mA
Output signal
Order code
Pack. unit piece
0-5 V, 0-10 V 0-20 mA, 4-20 mA
1SVR 011 700 R00001)
1
Legend ON OFF
2CDC 282 002 F0204
�
2CDC 282 001 F0204
2CDC 281 001 F0t03
CC-E/STD analog signal converter with 3-way electrical isolation
Price 1 piece
Supply voltage: 24 V DC universal CC-E/STD
0-5 V, 0-10 V 0-20 mA, 4-20 mA
single-function 1 U: green LED - supply voltage 2 Gain adjustment 3 Offset adjustment DIP switch for input and output configuration (only available on universal devices)
CC-E V/V CC-E V/I CC-E V/I
0-10 V
0-10 V 0-20 mA 4-20 mA
1SVR 011 710 R2100 1SVR 011 711 R1600 1SVR 011 712 R1700
1 1 1
CC-E I/V CC-E I/I CC-E I/I
0-20 mA
0-10 V 0-20 mA 4-20 mA
1SVR 011 713 R1000 1SVR 011 714 R1100 1SVR 011 715 R1200
1 1 1
CC-E I/V CC-E I/I CC-E I/I
4-20 mA
0-10 V 0-20 mA 4-20 mA
1SVR 011 716 R1300 1SVR 011 717 R1400 1SVR 011 718 R2500
1 1 1
CC-E V/V
-10...+10 V
-10...+10 V
1SVR 011 719 R2600
1
0-5 V, 0-10 V 0-20 mA, 4-20 mA
1SVR 011 705 R2100
1
Supply voltage: 110-240 V AC universal CC-E/STD
0-5 V, 0-10 V 0-20 mA, 4-20 mA
single-function
B 1604 Class I, Div.2 (universal device)
CC-E V/V CC-E V/I CC-E V/I
0-10 V
0-10 V 0-20 mA 4-20 mA
1SVR 011 720 R2300 1SVR 011 721 R1000 1SVR 011 722 R1100
1 1 1
CC-E I/V CC-E I/I CC-E I/I
0-20 mA
0-10 V 0-20 mA 4-20 mA
1SVR 011 723 R1200 1SVR 011 724 R1300 1SVR 011 725 R1400
1 1 1
CC-E I/V CC-E I/I CC-E I/I
4-20 mA
0-10 V 0-20 mA 4-20 mA
1SVR 011 726 R1500 1SVR 011 727 R1600 1SVR 011 728 R2700
1 1 1
CC-E V/V
-10...+10 V
-10...+10 V
1SVR 011 729 R2000
1
1)
202 2CDC110004C0205
• Technical data .......................................................................... 217
• Dimensional drawings ...............................................................223
ABB
Current/current isolator CC-E I/I-1 and CC-E I/I-2
2CDC 281 001 F0b06
Ordering details
Loop-powered current/current isolator without external power supply for analog current signals of 0-20 mA and 4-20 mA J J J J
Electrical isolation between input and output Very low internal voltage drop 2.5 V Available with one or two independent channels Width only 18 mm (1 and 2 channels)
Wiring instructions CC-E I/I-1 input 0-20 mA or 4-20 mA
Channel 1 IN
OUT C
F
D
E
output 0-20 mA or 4-20 mA UL
2CDC 281 041 F0b03
IN
OUT 100 � � RL � 500 �
2CDC 282 003 F0205
Channel 1
CC-E I/I-1
CC-E I/I-2 Channel 1 input 0-20 mA or 4-20 mA
Channel 1 IN
OUT C
F
D
E
output 0-20 mA or 4-20 mA UL
IN
OUT 100 � � RL � 500 �
input 0-20 mA or 4-20 mA
Chanel 2 IN
A
H
B
G
OUT
output 0-20 mA or 4-20 mA UL
IN
OUT 100 � � RL � 500 �
Type
5
2CDC 282 004 F0205
CC-E I/I-2
Channel 2
Input signal
Output signal
Order code
Pack. unit piece
0-20 mA, 4-20 mA
0-20 mA, 4-20 mA
1SVR 010 200 R1600
1
0-20 mA, 4-20 mA
0-20 mA, 4-20 mA
1SVR 010 201 R0300
1
Price 1 piece
1 channel CC-E I/I-1 2 channel CC-E I/I-2
• Technical data .......................................................................... 218
ABB
• Dimensional drawings ...............................................................223
203 2CDC110004C0205
Analog standard signal converter CC-U/STD Ordering details
2CDC 281 002 F0t03
CC-U/STD universal signal converter with 3-way electrical isolation � � �
J J J J J J
More than 120 configurations possible Configurable output signal response on input voltage signal interruption (low fail safe / high fail safe) Adjustment and operating elements on the front Short-circuit proof signal outputs Plug-in connecting terminals for inputs, outputs and supply Very fast signal transmission enables use in control systems
� �
Adjustment range
� CC-U/STD
Continuously variable adjustment range: Example ➀: Input configuration: 0...10 V Output configuration: -5...5 V
Wiring instruction
OUT [%] 100 Gain “gain-coarse” und “gain-fine”
90 80
Plug-in terminals
70 60
Gain: Coarse adjustment
50 40
Offset adjustment U: green LED - supply voltage
30
Burden R � 4.7 k�
J
Burden R � 600 �
H
Marker label
supply
�
20 10
IN [%] 10 20 30 40 50 60 70 80 90 100
Offset remote poti SW1.6 = +22.5 % SW1.4 = +100 %
2CDC 282 018 F0203
Gain: Fine adjustment
G Pot.
2CDC 282 015 F0206
+ 2.5 V
SW1.5 = +50 %
5
DIP switch settings Coarse Type C C 5 1 8 3 0 6 2 8 3 0 3 3 D 0 6 4 2 5 B 3 4 1 4 3 D 5 -
Output
*) Detection of input voltage signal interruptions: If the input signal circuit is interrupted, the output signal changes to the adjusted minimum value (low fail safe) or maximum value (high fail safe). If "No fail safe" is configured, input signal interruptions are not detected.
Type CC-U/STD
2CDC110004C0205
Legend ON OFF no influence
Rated supply voltage
Order code
Pack. unit pieces
24-48 V DC 110-240 V AC
1SVR 040 000 R1700 1SVR 040 001 R0400
1 1
• Accessories . ............................................................................ 216 • Dimensional drawings .............................................................. 223
204
Switch 2 1 2 3 4 5 6
0...5 V 0...10 V 1...5 V 2...10 V -10...+10 V -5...+5 V -10...0 V -5...0 V 0...6.66 V -10...+3.33 V -5...+1.66 V 0...8 V 0...4 V -10...-2 V -5...-1 V 1.25...6.25 V -7.5...+2.5 V -3.75...+1.25 V 1.66...8.33 V -6.66...+6.66 V -3.33...+3.33 V -8...0 V -4...0 V 0...1 mA 0...20 mA 4...20 mA 0...10 mA 0...0.5 mA 0...13.33 mA 0...666 µA 0...16 mA 0...800 µA 0...8 mA 0...400 µA 2.5...12.5 mA 125...625 µA 3.33...16.66 mA 166...833 µA 0.2...1 mA 2...10 mA 100...500 µA
2CDC 282 003 F0204
Gain A...D A...D 4...5 0...1 7...9 3...4 0 5...7 2 7...9 2...4 0 3...4 3...4 B...F 0 5...7 3...4 2 4...5 A...D 2...4 4...5 0...1 4...5 4...2 B...F 4...6 -
2CDC 282 020 F0203
Switch 1 1 2 3 4 5 6 7 8
2CDC 282 019 F0203
Input Potentiometer 0...50 mV 0...100 mV 0...250 mV 0...500 mV 0...1 V 0...2.5 V 0...5 V 0...10 V 1...5 V 2... 10 V -10...+10 V 0...125 mV 0...8 V -22.5...+22.5 mV -11...+11 V 2.5...7.5 V 3.33...9.99 V 10...0 V 100...0 mV 0...1 mA 0...20 mA 4...20 mA 10...50 mA 20...4 mA 20...0 mA -0.45...+0.45 mA -55...+55 mA High fail safe *) Low faile safe *) No fail safe *)
Price 1 piece
• Technical data ...........................................................................219
ABB
Analog standard signal converter CC-U/STDR with relay output
2CDC 281 003 F0t03
Ordering details
CC-U/STDR universal signal converter for standard signals, with 2 threshold relay outputs and with 3-way electrical isolation � � � � � � � � �
J Standard signal converter with 7 setting ranges J 2 threshold relay outputs with one c/o contact each (threshold and respective hysteresis can be adjusted independently from each other) J Open-circuit or closed-circuit principle configurable by means of a DIP switch J 2 yellow LEDs for clear status indication of the output relays J Plug-in connecting terminals for inputs, outputs and supply Wiring instruction
Function diagrams Value R1 Closed-circuit principle R1 Threshold value
CC-U/STDR
Threshold
R1 Hysteresis
Hysteresis
Temperature
Value R2
Threshold value for R1 supply
Hysteresis for R1
R2: yellow LED - Relay 2 energized R1: yellow LED - Relay 1 energized Marker label
11-14 R1 11-12 21-24 R2 21-22
Open-circuit principle
Input
R1 Threshold value
Switch 1 1 2 3 4 5 6
0...0 V 0...5 V 0...1 V -10...+10 V 1...5 V 0...20 mA 4...20 mA Output Closed-circuit principle Open-circuit principle
R1 Hysteresis Temperature R2 Hysteresis
Legend ON OFF no influence
2CDC 282 046 F0203
U: green LED - supply voltage
R2 Threshold value
DIP switch settings
2CDC 282 003 F0204
Hysteresis for R2
2CDC 282 005 F0204
Threshold value for R2
2CDC 282 044 F0203
Plug-in connecting terminals
2CDC 282 016 F0206
R2 Hysteresis
R2 Threshold value
11-14 R1 11-12 21-24 R2 21-22
Switching points Switching points of the output relay depending on the input range, configuration open-circuit principle IN [%]
tu al va l
ue
100
Ac
90 Threshold value R1 2-100 % of input range
80
Hysteresis R1 5-50 % of threshold value R1
70 60 50 40 Threshold value R2 2-100 % of input range
30 20
Hysteresis R2 5-50 % of threshold value R2
0
Type CC-U/STDR
R1
11-14 11-12
R2
21-24 21-22
OUT
Rated supply voltage
Order code
Pack. unit pieces
24-48 V DC 110-240 V AC
1SVR 040 010 R0000 1SVR 040 011 R2500
1 1
• Accessories . ............................................................................ 216 • Technical diagrams .................................................................. 223
ABB
2CDC 282 021 F0203
10
Price 1 piece
• Technical data ...........................................................................220 • Dimensional drawings ...............................................................223
205 2CDC110004C0205
5
Temperature signal converter for RTD sensors CC-E/RTD CC-E/RTD temperature signal converter for RTD sensors, linearized with 3-way electrical isolation
� � �
2 universally configurable devices (type CC-E/RTD) 2x12 single-function devices "Plug and Work", no adjustment of single-function devices required Temperature signal converter for PT100 sensors 2- or 3-wire connection DIP switch settings (universal devices)
Wiring instruction
Input 0...100 °C 0...300 °C G H
Burden R � 500 �
J
Gain adjustment Offset adjustment
supply 24 V DC or 110-240 V AC
U: green LED - supply voltage DIP switch for input and output configuration (only available on universal devices)
-50...+50 °C
-50...+250 °C
-50...+450 °C
Switch 1 1 2 3 4 5 6
0...10 V 0-20 mA 4-20 mA 0-10 V 0-20 mA 4-20 mA 0-10 V 0-20 mA 4-20 mA 0-10 V 0-20 mA 4-20 mA 0-10 V 0-20 mA 4-20 mA 0-10 V 0-20 mA 4-20 mA
High fail safe Low fail safe
Type
Output signal
Order code
Pack. unit piece
refer to table
0-10 V, 0-20 mA, 4-20 mA
1SVR 011 701 R25001)
1
CC-E RTD/V CC-E RTD/I CC-E RTD/I
PT100 0...100 °C
0-10 V 0-20 mA 4-20 mA
1SVR 011 730 R2500 1SVR 011 731 R1200 1SVR 011 732 R1300
1 1 1
CC-E RTD/V CC-E RTD/I CC-E RTD/I
PT100 -50...+50 °C
0-10 V 0-20 mA 4-20 mA
1SVR 011 733 R1400 1SVR 011 734 R1500 1SVR 011 735 R1600
1 1 1
CC-E RTD/V CC-E RTD/I CC-E RTD/I
PT100 0...300 °C
0-10 V 0-20 mA 4-20 mA
1SVR 011 736 R1700 1SVR 011 737 R1000 1SVR 011 738 R2100
1 1 1
CC-E RTD/V CC-E RTD/I CC-E RTD/I
PT100 -50...+250 °C
0-10 V 0-20 mA 4-20 mA
1SVR 011 739 R2200 1SVR 011 740 R0700 1SVR 011 741 R2400
1 1 1
refer to table
0-10 V, 0-20 mA, 4-20 mA
1SVR 011 706 R2200
1
CC-E RTD/V CC-E RTD/I CC-E RTD/I
PT100 0...100 °C
0-10 V 0-20 mA 4-20 mA
1SVR 011 788 R2400 1SVR 011 789 R2500 1SVR 011 790 R2200
1 1 1
CC-E RTD/V CC-E RTD/I CC-E RTD/I
PT100 -50...+50 °C
0-10 V 0-20 mA 4-20 mA
1SVR 011 791 R1700 1SVR 011 792 R1000 1SVR 011 793 R1100
1 1 1
CC-E RTD/V CC-E RTD/I CC-E RTD/I
PT100 0...300 °C
0-10 V 0-20 mA 4-20 mA
1SVR 011 794 R1200 1SVR 011 795 R1300 1SVR 011 796 R1400
1 1 1
CC-E RTD/V CC-E RTD/I CC-E RTD/I
PT100 -50...+250 °C
0-10 V 0-20 mA 4-20 mA
1SVR 011 797 R1500 1SVR 011 798 R2600 1SVR 011 799 R2700
1 1 1
Input signal
Legend ON OFF no influence
Price 1 piece
Supply voltage: 24 V DC universal CC-E/RTD
5
0...500 °C 2CDC 282 007 F0206
CC-E/RTD
Burden R � 1.0 k�
Output
2CDC 282 003 F0204
�
J J J J J
2CDC 282 006 F0204
2CDC 281 004 F0t03
Ordering details
single-function
Supply voltage: 110-240 V AC universal CC-E/RTD single-function
B 1604 Class I, Div.2 (universal device)
1)
206 2CDC110004C0205
• Technical data .......................................................................... 217
• Dimensional drawings ...............................................................223
ABB
Temperature signal converter for RTD sensors CC-U/RTD CC-U/RTD universal signal converter for PT10, PT100, PT1000 temperature sensors (acc. to IEC 751 and JIS C 16041), linearized with 3-way electrical isolation � � � � � �
J Configurable output signal response on input signal interruption (low fail safe / high fail safe) J Adjustment and operating elements on the front-side J Short-circuit proof signal outputs J Plug-in connecting terminals for inputs, outputs and supply 1) Japanese standard
Wiring instruction G Burden R � 4.7 k�
J
Burden R � 600 �
H
supply 24 V DC or 110-240 V AC
2CDC 282 017 F0206
2CDC 281 005 F0t03
Ordering details
Characteristic curves Resistance of PT10, PT100 and PT1000 sensors depending on the temperature
CC-U/RTD
PT1000
Plug-in connecting terminals Gain: Fine adjustment Offset adjustment U: green LED - supply voltage
Resistance [�]
Gain: Coarse adjustment PT100
Marker label
2CDC 282 022 F0203
PT10
Temperature [°C]
*) Detection of input signal interruptions: If the input signal circuit is interrupted, the output signal changes to the adjusted minimum value (low fail safe) or maximum value (high fail safe).
Type CC-U/RTD
Rated supply voltage
Order code
Pack. unit pieces
24-48 V DC 110-240 V AC
1SVR 040 002 R0500 1SVR 040 003 R0600
1 1
• Accessories . ............................................................................ 216 • Dimensional drawings .............................................................. 223
ABB
Legend ON OFF no influence
2CDC 282 003 F0204
Gain Coarse F E D C B A 9 8 F E B A 9 8 3 2 1 0 8 3 2 1 0 0 -
2CDC 282 023 F0203
Switch 1 Switch 2 Input Range 1 2 3 4 5 6 1 2 3 4 5 6 0...500 °C 0...550 °C 0...600 °C 0...650 °C PT10 0...700 °C 0...750 °C 0...800 °C 0...850 °C 0...50 °C 0...60 °C 0...70 °C 0...80 °C 0...90 °C PT100 0...100 °C 0...200 °C 0...300 °C 0...400 °C 0...500 °C 0...10 °C 0...20 °C 0...30 °C PT1000 0...40 °C 0...50 °C 0...60 °C Low fail safe *) High fail safe *) Type
Switch 3 1 2 3 4 5 6
0...5 V 0...10 V 1...5 V 2...10 V -10...+10 V -5...+5 V -10...0 V -5...0 V 0...6.66 V -10...+3.33 V -5...+1.66 V 0...8 V 0...4 V -10...-2 V -5...-1 V 1.25...6.25 V -7.5...+2.5 V -3.75...+1.25 V 1.66...8.33 V -6.66...+6.66 V -3.33...+3.33 V -8...0 V -4...0 V 0...1 mA 0...20 mA 4...20 mA 0...10 mA 0...0.5 mA 0...13.33 mA 0...666 µA 0...16 mA 0...800 µA 0...8 mA 0...400 µA 2.5...12.5 mA 125...625 µA 3.33...16.66 mA 166...833 µA 0.2...1 mA 2...10 mA 100...500 µA
2CDC 282 024 F0203
Output
DIP switch settings
Price 1 piece
• Technical data ...........................................................................219
207 2CDC110004C0205
5
Temperature signal converter for RTD sensors CC-U/RTDR with relay output CC-U/RTDR universal signal converter for temperature and resistance signals, with 2 threshold relay outputs and 3-way electrical isolation J Temperature signal converter for PT100 signals (5 ranges up to 800 °C) and variable resistances from 0-380 q J 2 threshold relay outputs with one c/o contact each (threshold and respective hysteresis can be adjusted independently from each other) J Open-circuit or closed-circuit principle configurable by means of a DIP switch J 2 yellow LEDs for clear status indication of the output relays J Plug-in connecting terminals for inputs, outputs and supply Wiring instruction Value R1
G
υ
Threshold
J
Value R2
K
Threshold value for R2
M
supply 24 V DC or 110-240 V AC
Hysteresis for R2
R1 Threshold value R1 Hysteresis Temperature R2 Hysteresis R2 Threshold value
11-14 R1 11-12 21-24 R2 21-22
DIP switch settings
Open-circuit principle R1 Threshold value
R2: yellow LED - Relay 2 energized
R1 Hysteresis
Switch 1 1 2 3 4 5 6
Input PT100 0...100 °C 0...200 °C 0...400 °C 0...600 °C 0...800 °C
R2 Hysteresis
Output Closed-circuit principle Open-circuit principle
Legend ON OFF no influence
2CDC 282 046 F0203
Marker label
Temperature
2CDC 282 007 F0204
R1: yellow LED - Relay 1 energized
R2 Threshold value
11-14 R1 11-12 21-24 R2 21-22
Switching points Switching points of the output relay depending on the input range, configuration open-circuit principle IN [%]
va lu e
100
800
Ac tu
Threshold value R1 2-100 % of input range
600
al
90
700
80
Hysteresis R1 5-50 % of threshold value R1
70
500
60 50
400 300
40
Threshold value R2 2-100 % of input range
200
30 20
100
Hysteresis R2 5-50 % of threshold value R2
10 0 50
100
150
200
250
300
350
Resistance [�]
Type CC-U/RTDR
R1
11-14 11-12
R2
21-24 21-22
Rated supply voltage
Order code
Pack. unit pieces
24-48 V DC 110-240 V AC
1SVR 040 012 R2600 1SVR 040 013 R2700
1 1
• Accessories . ............................................................................ 216 • Technical diagrams .................................................................. 223
208 2CDC110004C0205
OUT
400
2CDC 282 025 F0203
Temperature υ [°C]
5
B (22) C (21) A (24)
R2
Hysteresis for R1
Closed-circuit principle
Hysteresis
H
Threshold value for R1
U: green LED - supply voltage
E (12) F (11) D (14)
R1
2CDC 282 044 F0203
CC-U/RTDR Plug-in connecting terminals
Function diagrams
2CDC 282 045 F0203
� � � � � � � � �
2CDC 282 003 F0204
2CDC 281 006 F0t03
Ordering details
Price 1 piece
• Technical data ...........................................................................220 • Dimensional drawings ...............................................................223
ABB
Temperature signal converter for thermocouples CC-E/TC
2CDC 281 007 F0t03
Ordering details
CC-E/TC analog signal converter for thermocouple signals of the types J and K with 3-way electrical isolation J 2 universally configurable devices (type CC-E/TC) J 2x6 single-function devices J "Plug and Work", no adjustment of single-function devices required � � �
Wiring instruction
DIP switch settings (universal devices)
�
supply 24 V DC or 110-240 V AC
Gain adjustment
TC-J: 0...600 °C TC-K: 0...1000 °C
Output
Switch 1 1 2 3 4 5 6
0...10 V 0...20 mA 4...20 mA 0...10 V 0...20 mA 4...20 mA
High fail safe Low fail safe
Legend ON OFF no influence
2CDC 282 003 F0204
CC-E/TC
Input 2CDC 282 008 F0206
Burden R � 500 �
2CDC 282 009 F0204
Burden R � 1.0 k�
Offset adjustment U: green LED - supply voltage DIP switch for input and output configuration (only available on universal devices)
Type
Input signal
Output signal
Order code
Pack. unit piece
0-10 V, 0-20 mA, 4-20 mA
1SVR 011 702 R26001)
1
Price 1 piece
Supply voltage: 24 V DC universal CC-E/TC
thermocouple types J and K
5
single-function CC-E TC/V CC-E TC/I CC-E TC/I
type J 0...600 °C
0-10 V 0-20 mA 4-20 mA
1SVR 011 750 R0100 1SVR 011 751 R2600 1SVR 011 752 R2700
1 1 1
CC-E TC/V CC-E TC/I CC-E TC/I
type K 0...1000 °C
0-10 V 0-20 mA 4-20 mA
1SVR 011 753 R2000 1SVR 011 754 R2100 1SVR 011 755 R2200
1 1 1
0-10 V, 0-20 mA, 4-20 mA
1SVR 011 707 R2300
1
Supply voltage: 110-240 V AC universal CC-E/TC
thermocouple types J and K
single-function
B 1604 Class I, Div.2 (universal device)
CC-E TC/V CC-E TC/I CC-E TC/I
type J 0...600 °C
0-10 V 0-20 mA 4-20 mA
1SVR 011 760 R0300 1SVR 011 761 R2000 1SVR 011 762 R2100
1 1 1
CC-E TC/V CC-E TC/I CC-E TC/I
type K 0...1000 °C
0-10 V 0-20 mA 4-20 mA
1SVR 011 763 R2200 1SVR 011 764 R2300 1SVR 011 765 R2400
1 1 1
1)
ABB
• Technical data .......................................................................... 217
• Dimensional drawings ...............................................................223
209 2CDC110004C0205
Temperature signal converter for thermocouples CC-U/TC Ordering details
� � � � � �
J Temperature signal converter for thermo- couples of the types K, J, T, S, E, N, R, B J Continuously adjustable voltage signal input 0-10 mV and 0-50 mV J Differential temperature meas. possible 1) J Configurable output signal response on input signal interruption (low fail safe / high fail safe) J Adjustment and operating elements on the front-side J Short-circuit proof signal outputs J Plug-in connecting terminals for inputs, outputs and supply
Wiring instruction Burden R � 4.7 k� Burden R � 600 �
supply
2CDC 282 018 F0206
2CDC 281 008 F0t03
CC-U/TC universal signal converter for thermocouples with 3-way electrical isolation
1)
Plug-in connecting terminals
without cold-junction compensation:
DIP switch settings
switch SW2.2 = OFF
Gain: Fine adjustment
Switch 1 Switch 2 Input Range 1 2 3 4 5 6 1 2 3 4 5 6 0-100...900 °C K 0-250...1350 °C J 0-100...750 °C 0-100...400 °C T -150-0...400 °C S 0-250...1550 °C 0-100...700 °C E 0-200...1000 °C 0-100...650 °C N 0-200...1300 °C 0-250...1350 °C R 0-450...1700 °C B 0-700...1750 °C 0-2...10 mV mV 0-10...50 mV Low fail safe *) High fail safe *)
Type
Offset adjustment
*) Detection of input signal interruptions: If the input signal circuit is interrupted, the output signal changes to the adjusted minimum value (low fail safe) or maximum value (high fail safe).
Characteristic curves Thermocouple voltages depending on the temperature 80000
Typ E
75000
Typ J
70000 65000 60000
Typ K
55000 50000
Typ N
45000 40000 35000 30000 25000
Typ R Typ T
20000
Typ S
15000
Legend ON OFF no influence
2CDC 282 003 F0204
10000
Typ B
5000 0 -5000 -10000
1800
1750
1700
1650
1600
1550
1500
1450
1400
1350
1300
1250
1200
1150
1100
1050
1000
950
900
850
800
750
700
650
600
550
500
450
400
350
300
250
200
150
0
50
100
-50
-100
-150
-200
-250
-15000
Temperatur [°C]
Type CC-U/TC
Rated supply voltage
Order code
Pack. unit pieces
24-48 V DC 110-240 V AC
1SVR 040 004 R0700 1SVR 040 005 R0000
1 1
• Accessories . ............................................................................ 216 • Dimensional drawings .............................................................. 223
210 2CDC110004C0205
2CDC 282 026 F0103
5
0...5 V 0...10 V 1...5 V 2...10 V -10...+10 V -5...+5 V -10...0 V -5...0 V 0...6.66 V -10...+3.33 V -5...+1.66 V 0...8 V 0...4 V -10...-2 V -5...-1 V 1.25...6.25 V -7.5...+2.5 V -3.75...+1.25 V 1.66...8.33 V -6.66...+6.66 V -3.33...+3.33 V -8...0 V -4...0 V 0...1 mA 0...20 mA 4...20 mA 0...10 mA 0...0.5 mA 0...13.33 mA 0...666 µA 0...16 mA 0...800 µA 0...8 mA 0...400 µA 2.5...12.5 mA 125...625 µA 3.33...16.66 mA 166...833 µA 0.2...1 mA 2...10 mA 100...500 µA
2CDC 282 020 F0203
Marker label
Switch 2 1 2 3 4 5 6
Output
Thermoelement-Spannung [µV]
U: green LED - supply voltage
2CDC 282 010 F0204
Gain: Coarse adjustment
2CDC 282 019 F0206
CC-U/TC
Price 1 piece
• Technical data ...........................................................................219
ABB
Temperature signal converter for thermocouples CC-U/TCR with relay output
2CDC 281 009 F0t03
Ordering details
CC-U/TCR universal signal converter for thermocouples, with 2 threshold relay outputs and 3-way electrical isolation � � � � � � � � �
J Temperature signal converter for thermocouples of the types K, J, T, S J 2 threshold relay outputs with one change-over contact each (threshold and respective hysteresis can be adjusted independently from each other) J Open-circuit or closed-circuit principle configurable by means of a DIP switch J 2 yellow LEDs for clear status indication of the output relays J Plug-in connecting terminals for inputs, outputs and supply Wiring instruction
Function diagrams Value R1 Closed-circuit principle R1 Threshold value
CC-U/TCR
R1 Hysteresis
Threshold
Hysteresis
Temperature
2CDC 282 044 F0203
R2 Hysteresis
2CDC 282 020 F0206
R2 Threshold value
Plug-in connecting terminals
Value R2
Threshold value for R1 Hysteresis for R1
supply
11-14 R1 11-12 21-24 R2 21-22
Threshold value for R2
R1: yellow LED - Relay 1 energized Marker label
Open-circuit principle R1 Threshold value R1 Hysteresis
Switch 1 Input Type Range 1 2 3 4 5 6 0...240 °C J 0...480 °C 0...1200 °C 0...250 °C 0...500 °C K 0...1350 °C -150...+120 °C 0...220 °C T 0...400 °C 0...210 °C 0...380 °C S 0...860 °C 0...1550 °C Output Closed-circuit principle Open-circuit principle
Temperature R2 Hysteresis 2CDC 282 046 F0203
R2: yellow LED - Relay 2 energized
DIP switch settings
R2 Threshold value
11-14 R1 11-12 21-24 R2 21-22
2CDC 282 003 F0204
U: green LED - supply voltage
2CDC 282 004 F0204
Hysteresis for R2
Legend ON OFF no influence
Switching points Switching points of the output relay depending on the input range, configuration open-circuit principle IN [%] 100
7000
Threshold value R1 = 1000 °C
Typ J
6500 6000
Thermocouple voltage [µV]
5500 5000
Typ K Release hysteresis
4500 4000 3500
Threshold value R2 = 400 °C
3000 2500
Typ T
Release hysteresis
2000 1500
Typ S
1000 500
0
0
OUT
-1000
Temperature [°C]
Type CC-U/TCR
R2
21-24 21-22
Rated supply voltage
Order code
Pack. unit pieces
24-48 V DC 110-240 V AC
1SVR 040 014 R2000 1SVR 040 015 R2100
1 1
• Accessories . ............................................................................ 216 • Technical diagrams .................................................................. 223
ABB
R1 1825
1725
1625
1525
1425
1325
1225
1125
925
1025
825
725
625
525
425
325
225
25
125
-75
-175
-275
-1500
11-14 11-12
2CDC 282 027 F0203
-500
Price 1 piece
• Technical data ...........................................................................220 • Dimensional drawings ...............................................................223
211 2CDC110004C0205
5
Measuring converter for sinusoidal and DC currents CC-E/I
2CDC 281 010 F0t03
Ordering details
CC-E/I current measuring converter for current signals 0-5 A, 0-20 A, AC/DC with 3-way electrical isolation J 2 universally configurable devices (type CC-E/I) J 2x6 single-function devices J "Plug and Work", no adjustment of single-function devices required � �
Wiring instruction
� �
Burden R � 500 �
CC-E/I supply 24 V DC or 110-240 V AC
2CDC 282 009 F0206
Burden R � 1.0 k�
Gain adjustment Input range selection DIP switch settings (universal devices) Select input range by terminals
DIP switch for input and output configuration (only available on universal devices)
Connected lines Used terminals Terminal marking Input range 20 A Connected lines Used terminals Terminal marking
Input I - DC I - AC I - DC I - AC I - DC I - AC
Output
Switch 1 1 2 3 4 5 6
0...10 V 0...20 mA 4...20 mA
Legend ON OFF
2CDC 282 002 F0204
Input range 5 A 2CDC 282 008 F0204
U: green LED - supply voltage
2CDC 282 011 F0204
Offset adjustment
5 Type
Input signal
Output signal
Order code
Pack. unit pieces
Price 1 piece
Supply voltage: 24 V DC universal CC-E/I
0-5 A, 0-20 A, AC/DC
0-10 V, 0-20 mA, 1SVR 011 703 R27001) 4-20 mA
1
single-function CC-E IAC/V CC-E IAC/I 0-5 A, 0-20 A, AC CC-E IAC/I
0-10 V 0-20 mA 4-20 mA
1SVR 011 770 R0500 1SVR 011 771 R2200 1SVR 011 772 R2300
1 1 1
CC-E IDC/V CC-E IDC/I 0-5 A, 0-20 A, DC CC-E IDC/I
0-10 V 0-20 mA 4-20 mA
1SVR 011 773 R2400 1SVR 011 774 R2500 1SVR 011 775 R2600
1 1 1
0-10 V, 0-20 mA, 4-20 mA
1SVR 011 708 R0400
1
CC-E IAC/V CC-E IAC/I 0-5 A, 0-20 A, AC CC-E IAC/I
0-10 V 0-20 mA 4-20 mA
1SVR 011 780 R1100 1SVR 011 781 R0600 1SVR 011 782 R0700
1 1 1
CC-E IDC/V CC-E IDC/I 0-5 A, 0-20 A, DC CC-E IDC/I
0-10 V 0-20 mA 4-20 mA
1SVR 011 783 R0000 1SVR 011 784 R0100 1SVR 011 785 R1100
1 1 1
Supply voltage: 110-240 V AC universal CC-E/I
0-5 A, 0-20 A, AC/DC
single-function
B 1604 Class I, Div.2 (universal device)
1)
212 2CDC110004C0205
• Technical data .......................................................................... 221
• Dimensional drawings ...............................................................223
ABB
Measuring converter for sinusoidal currents CC-E IAC/ILPO
2CDC 281 018 F0t04
Ordering details
CC-E IAC/ILPO current measuring without auxiliary power for sinusoidal currents 0-1 A, 0-5 A, output 4 - 20 mA
�
J J J J
Measuring converter for sinusoidal AC currents (0-1 A, 0-5 A) Measuring range selection by front-face sliding switch 4-20 mA output current in propotion to input current no additional power supply required
� �
Wiring instruction
CC-E IAC/ILPO Gain adjustment 2CDC 282 010 F0b06
Offset adjustment Selection of measuring range
5 Type CC-E IAC/ILPO
Input signal
Order code
Pack. unit pieces
0-1 A, 0-5 A, AC
1SVR 010 203 R0500
1
• Technical data .......................................................................... 221
ABB
Price 1 piece
• Dimensional drawings ...............................................................223
213 2CDC110004C0205
Measuring converter for current RMS values CC-U/I
2CDC 281 012 F0t03
Ordering details
CC-U/I universal current measuring converter for RMS values of 0-1 A and 0-5 A, with 3-way electrical isolation � � �
J RMS converter for current signals up to 1 A and up to 5 A of any wave form (DC, DC with superimposed AC components, pure sinusoidal, triangular, phase-angle controlled, etc. in a measuring range of 0-600 Hz) J Adjustment and operating elements on the front J Short-circuit proof signal outputs J Plug-in connecting terminals for inputs, outputs and supply
� DIP switch settings Output
Burden R � 600 �
Plug-in connecting terminals supply 24 V DC or 110-240 V AC
Gain adjustment
2CDC 282 021 F0206
Burden R � 4.7 k�
CC-U/I
Offset adjustment U: green LED - supply voltage Marker label
Input range selection
Select input range by terminals Input range 1 A
5
J 5A
H 1A
G C
Input range 5 A Connected lines Used terminals Terminal marking
J 5A
H 1A
G C
2CDC 282 033 F0203
Connected lines Used terminals Terminal marking
Switch 1 1 2 3 4 5 6
0...5 V 0...10 V 1...5 V 2...10 V -10...+10 V -5...+5 V -10...0 V -5...0 V 0...6.66 V -10...+3.33 V -5...+1.66 V 0...8 V 0...4 V -10...-2 V -5...-1 V 1.25...6.25 V -7.5...+2.5 V -3.75...+1.25 V 1.66...8.33 V -6.66...+6.66 V -3.33...+3.33 V -8...0 V -4...0 V 0...1 mA 0...20 mA 4...20 mA 0...10 mA 0...0.5 mA 0...13.33 mA 0...666 µA 0...16 mA 0...800 µA 0...8 mA 0...400 µA 2.5...12.5 mA 125...625 µA 3.33...16.66 mA 166...833 µA 0.2...1 mA 2...10 mA 100...500 µA
Legend ON OFF no influence
2CDC 282 003 F0204
Wiring instruction
2CDC 282 029 F0203
�
Example of application RMS measurement and conversion of a current signal
IN [%]
Gain �15 %
I(t) [A] 5 4 3 2 1
resulting RMS value
0 t
-1
0
50
OUT [%]
100
-2 2CDC 282 028 F0203
Offset �20 %
-3 -4 -5
Type CC-U/I
Rated supply voltage
Order code
Pack. unit pieces
24-48 V DC 110-240 V AC
1SVR 040 006 R0100 1SVR 040 007 R0200
1 1
• Accessories . ............................................................................ 216 • Dimensional drawings .............................................................. 223
214 2CDC110004C0205
Price 1 piece
• Technical data ...........................................................................222
ABB
Measuring converter for voltage RMS values CC-U/V
2CDC 281 013 F0t03
Ordering details
CC-U/V universal voltage measuring converter for RMS values of 0-600 V, with 3-way electrical isolation � � � � �
J RMS converter for voltage signals up to 600 V of any wave form (DC, DC with superimposed AC components, pure sinusoidal, triangular, phase-angle controlled, etc. in a measuring range of 0-600 Hz) J Adjustment and operating elements on the front J Short-circuit proof signal outputs J Plug-in connecting terminals for inputs, outputs and supply Wiring instruction
DIP switch settings
�
Burden R � 600 �
Input voltage range selection
supply 24 V DC or 110-240 V AC
Gain adjustment
2CDC 282 022 F0206
Burden R � 4.7 k�
Offset adjustment U: green LED - supply voltage Input range selection
Selecting input range by front-face rotary switch 0...100 V 0...150 V 0...250 V 0...300 V 0...400 V 0...450 V 0...550 V 0...600 V
Switch position 1 2 3 4 5 6 7 8
2CDC 282 012 F0204
Marker label
5 2CDC 282 029 F0203
CC-U/V Plug-in connecting terminals
Switch 1 1 2 3 4 5 6
0...5 V 0...10 V 1...5 V 2...10 V -10...+10 V -5...+5 V -10...0 V -5...0 V 0...6.66 V -10...+3.33 V -5...+1.66 V 0...8 V 0...4 V -10...-2 V -5...-1 V 1.25...6.25 V -7.5...+2.5 V -3.75...+1.25 V 1.66...8.33 V -6.66...+6.66 V -3.33...+3.33 V -8...0 V -4...0 V 0...1 mA 0...20 mA 4...20 mA 0...10 mA 0...0.5 mA 0...13.33 mA 0...666 µA 0...16 mA 0...800 µA 0...8 mA 0...400 µA 2.5...12.5 mA 125...625 µA 3.33...16.66 mA 166...833 µA 0.2...1 mA 2...10 mA 100...500 µA
Legend ON OFF no influence
2CDC 282 003 F0204
Output
Example of application RMS measurement and conversion of a phase-angle controlled voltage signal L1 = 230 V
INUeff [V] U(t) [V] resulting RMS value
Gain �15 %
OUT [%]
0 0
50
100
Offset �20 % -300 operating angle
Type CC-U/V
Rated supply voltage
Order code
Pack. unit pieces
24-48 V DC 110-240 V AC
1SVR 040 008 R1300 1SVR 040 009 R1400
1 1
• Accessories . ............................................................................ 216 • Dimensional drawings .............................................................. 223
ABB
2CDC 282 030 F0203
300
Price 1 piece
• Technical data ...........................................................................222
215 2CDC110004C0205
Analog signal converters Accessories for CC-U range Ordering details
2CDC 252 187 F0005
62,5 2.46”
10 .394” 22,5 .886”
4,5 .177”
11,5 .453”
Accessories Adapter for screw mounting Type
ADP.01
60 2.36”
for type
Width in mm
Order code
Pack. unit pieces
CC-U
22.5
1SVR 430 029 R0100
1
for type
Order code
Pack. unit pieces
CC-U
1SVR 366 017 R0100
1
Price 1 piece
Weight 1 piece kg / lb
Price 1 piece
Weight 1 piece kg / lb
Price 1 piece
Weight 1 piece kg / lb
20 .787”
MAR.01
Marker label
2CDC 252 186 F0005
3A11
8 .315”
ADP.01
Type
7 .275” 3,5 .138”
68,5 2.70 ”
22,5 .886”
5
2CDC 252 185 F0005
MAR.01
Sealable transparent cover Type
COV.01
for type
Width in mm
Order code
Pack. unit pieces
CC-U
22.5
1SVR 430 005 R0100
1
front-to-back size 107
Sealable cover COV.01
216 2CDC110004C0205
ABB
Analog signal converters CC-E/STD, CC-E x/x, CC-E/RTD, CC-E/TC Technical data Type Input circuits - Analog inputs
CC-E/STD J-G-H
Input signal Rated input range
Current
Voltage
1 M
50 -
Output circuits - Analog outputs Output signal Output burden Accuracy 1) Residual ripple Response time Transmission frequency Reaction to input circuit interruption
D-F, A-C
Supply circuits Supply voltage Supply voltage tolerance Power consumption
K-M
-50...+500 °C
< 0.01 %/ ± 5 % (universal devices) ± 5 % (universal devices) 100 dB
TC.K: 0...1000 °C, TC.J: 0...600 °C < 0.5 % / 100
> 35 dB
DC versions 24 V DC -15...+15 % 1.5 W typ.
AC versions 110-240 V AC - 50/60 Hz -15...+10 % 1.5 VA typ.
5
U: green LED
General data Ambient temperature range
operation storage
0...+60 °C -20...+80 °C ± 500 ppm/°C IP20 ventilation slots on top and bottom DIN rail, snap-on mounting
rigid fine-strand
4 mm2 (10 AWG) 2.5 mm2 (14 AWG)
Temperature coefficient Degree of protection (DIN 40050) Mounting position Mounting Electrical connection Wire size
EN 61000-6-2 Level 3 (±6 kV / ±8 kV)
IEC/EN 61000-4-2
10 V/m
IEC/EN 61000-4-3 IEC/EN 61000-4-4 IEC/EN 61000-4-5 IEC/EN 61000-4-6 EN 61000-6-4
Isolation data Test voltage between all isolated circuits Rated insulation voltage
2)
PT100
CC-E/TC Thermocouples (IEC 584-1 and 2) TC.K, TC.J
Current Voltage 0-20 mA, 4-20 mA 0-5 V, 0-10 V m 500 1.0 K ± 0.5 % of full-scale < 0.5 % 200 µs 10 ms 2 kHz 80 Hz 2 Hz (up to -3 dB) Low fail safe: Output voltage > 15 % of measuring range 2) Low fail safe: Output voltage < -0.6 V, output current = 0 mA
Indication of operational states Rated control supply voltage US
1)
Temperature sensors
Standard signals 0...5 V / 0...20 mA / 0...10 V / 4...20 mA -10...+10 V +55 mA ± 11 V -
Limitation of input signals Influence of line resistance Gain adjustment range Offset adjustment range Input impedance Suppression at 50 Hz Common-mode rejection
Electromagnetic compatibility Interference immunity electrostatic discharge (ESD) electromagnetic field (HF radiation resistance) fast transients (Burst) powerful impulses (Surge) HF line emission Interference emission
CC-E/RTD
Level 3 (±2 kV / 5 kH) ±2 kV / ±1 kV 10 V class B
-
2.5 kV AC -
-
includes: non-linearity, factory setting, drift of temperature, supply voltage and output load Only -/RTD and -/TC: Single-function devices respond with Low fail safe to input signal interruptions
ABB
217 2CDC110004C0205
Analogsignal converter CC-E I/I-1, CC-E I/I-2 Technical data Type Input circuits - Analog inputs Input current IIN Min. input current Max. input current Input voltage UIN Input voltage drop Ui Max. input voltage
CC-E I/I channel 1: A (+), B (-), channel 1 or 2: C (+), D (-)
Output circuits Output current IOUT Output load RL Output voltage UOUT Residual ripple Response time (0-100 %)
channel 1: H (+), G (-), channel 2: F (+), E (-) 0-20 mA, 4-20 mA 0-500 IOUT x RL < 20 mVpp (500 , 20 mA) < 15 ms (0-500 , 20 mA), < 5 ms (500 , 20 mA, 25 °C) 0.1 % of full-scale (20 mA) 0.05 % / 100 , -0.1 % / 100 (25 °C)
Accuracy Load influence (0-500 ) General data Width of the enclosure Weight
5
Current 0-20 mA, 4-20 mA < 100 µA 50 mA1) (VIN < 18 V) < 2.5 V + (IIN x RL) < 2.5 V (20 mA, RL = 0 ) 18 V1) (IIN < 50 mA)
Temperature coefficient Mounting
18 mm approx. 0.037 kg (0.082 lb) approx. 0.044 kg (0.097 lb) any IP20 / IP20 -25...+60 °C -40...+85 °C < 50 ppm / °C DIN rail (EN 50022)
Electrical connection Wire size
max. 2.5 mm2 (14 AWG)
Standards Product standard Low Voltage Directive EMC Directive
EN 50178 2006/95/EC 2004/108/EC
Mounting position Degree of protection Ambient temperature range
1 channel 2 channel enclosure / terminals operation storage
Electromagnetic compatibility Interference immunity electrostatic discharge (ESD) electromagnetic field (HF radiation resistance) fast transients (Burst) powerful impulses (Surge) HF line emission magnetisches Feld Interference emission Radiated noise Operational reliability (EN 68-2-6) Mechanical resistance (EN 68-2-6) Environmental testing (IEC 68-2-30 Db) Isolation data Insulation voltage input / output Insulation voltage between channels Pollution category Overvoltage category
1)
EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-6 EN 61000-4-8 EN 55011
EN 61000-6-2 Level 3 (±6 kV / ±8 kV) 10 V/m Level 3 (±2 kV / 5 kH) ±2 kV / ±1 kV 10 V 30 A/m EN 61000-6-4 class B 4g 10 g 24 h cycle, 55 °C, 93 % rel., 96 h 500 Veff / 50 Hz
(device with 2 channels)
5 kVeff / 50 Hz 2 II
The input parameters have to be limited to the indicated maximum values.
218 2CDC110004C0205
ABB
Analog signal converters CC-U/STD, CC-U/RTD, CC-U/TC Technical data Type Input circuits - Analog inputs
CC-U/STD J-G-H
Input signal
Current 0-20 mA 4-20 mA 10-50 mA 0-1 mA
Limitation of input signals Rated input range
± 55 mA -
Influence of line resistance Gain adjustment range (universal devices) Offset adjustment range (universal devices) Input impedance without detection of input signal interruption with detection of input signal interruption Suppression at 50 Hz Common-mode rejection Output circuits - Analog outputs Output signal Output burden Accuracy 1) Residual ripple Response time Transmission frequency Supply circuits Rated supply voltage Supply voltage range Supply voltage tolerance Rated frequency Power consumption
D-F, A-C
CC-U/RTD
PotentioVoltage meter 0-100 mV 470 0-1 V 1 M 2) 0-5 V 1-5 V 0-10 V 2-10 V ± 10 V ± 11 V -
-
0.945 mV 110 mA 22 V -137.5...+62.5 % for different ranges 51 6 M 3 G 51 3.5 M 9.5 G
< 0.01 % / 100
±5% 120 dB
± 10 % > 40 dB 105 dB
5
24-48 V DC 110-240 V AC 24-48 V DC / 24 V AC 110-240 V AC / 100-300 V DC DC: -15...+15 % AC: -15...+10 % 0 Hz or 50/60 Hz 2 W at 24 V DC 4.5 VA at 230 V AC
operation storage
-20...+60 °C -40...+80 °C ±150 ppm/°C
±250 ppm/°C
±200 ppm/°C at min. offset ±400 ppm/°C at max. offset
any DIN rail, snap-on mounting / screw mounting with adapter rigid fine-strand
IEC/EN 61000-4-2 IEC/EN 61000-4-3 IEC/EN 61000-4-4 IEC/EN 61000-4-5 IEC/EN 61000-4-6 EN 61000-6-4
plug-connector with screw terminals 1.5 mm2 (16 AWG) plug-connector with screw terminals 2.5 mm2 (14 AWG) EN 61000-6-2 Level 3 (±6 kV / ±8 kV) 10 V/m Level 3 (±2 kV / 5 kH) 2 kV / 1 kV 10 V Class B 1.5 kV
Test voltage (between all isolated circuits)
1.5 kV / 50 Hz
2)
refer to temperature specs. of individual thermocouples
see DIP switch settings
Isolation data Isolation test (between all isolated circuits)
1)
-
U: green LED
Mounting position Mounting
Electromagnetic compatibility Interference immunity electrostatic discharge (ESD) electromagnetic field (HF radiation resistance) fast transients (Burst) powerful impulses (Surge) HF line emission Interference emission
Max. temperature adjustable: 6-60 °C for PT1000 50-500 °C for PT100 500-850 °C for PT10 0.015 °C/
K-M
Temperature coefficient
Electrical connection Wire size
PT10, PT100, PT1000 (IEL 751 and JICC 1604)
Current Voltage 0-20 mA, 4-20 mA 0-5 V, 1-5 V, 0-10 V, 2-10 V, ± 10 V 600 4.7 K ±0.1 % of full-scale ±0.2 % of full-scale ±0.1 % of full-scale < 0.15 % 200 µs 10 ms 200 ms 1 kHz 80 Hz 2 Hz (to -3 dB)
Indication of operational states Supply voltage General data Ambient temperature range
Temperature sensors
CC-U/TC Thermocouples (IEC 584-1 and 2) TC.K TC.J TC.T TC.S TC.E TC.N TC.R TC.B
includes: non-linearity, factory setting, drift of temperature, supply voltage and output load Detection of an input signal break (fail safe) and resistance > 10 kq results in a linearity of w0,2 %.
ABB
219 2CDC110004C0205
Analog signal converters with relay output CC-U/STDR, CC-U/RTDR, CC-U/TCR Technical data Type Input circuits - Analog inputs
CC-U/STDR J-H
Measuring signal / input range
Minimum switching voltage Minimum switching current / Response time Mechanical lifetime Electrical lifetime
5
E-D-F, B-C-A
at AC12, 230 V, 4 A
operation storage
-20...+60 °C -40...+80 °C ±300 ppm/°C any DIN rail (EN 50 022), snap-on mounting / screw mounting with adapter
rigid fine-strand
plug-connector with screw terminals 1.5 mm2 (16 AWG) plug-connector with screw terminals 2.5 mm2 (14 AWG)
IEC/EN 61000-4-2 IEC/EN 61000-4-3 IEC/EN 61000-4-4 IEC/EN 61000-4-5 IEC/EN 61000-4-6 EN 61000-6-4
Isolation data Insulation voltage (between all isolated circuits) Test voltage (between all isolated circuits)
220 2CDC110004C0205
24-48 V DC 110-240 V AC 24-48 V DC / 24 V AC 110-240 V AC / 100-300 V DC DC: -15...+15 % AC: -15...+10 % 0 Hz or 50/60 Hz 2 W at 24 V DC 4.5 VA at 230 V AC U: green LED R1: yellow LED / R2: yellow LED
Temperature coefficient Mounting position Mounting
Electromagnetic compatibility Interference immunity electrostatic discharge (ESD) electromagnetic field (HF radiation resistance) fast transients (Burst) powerful impulses (Surge) HF line emission Interference emission
(IEC 584-1 and 2) TC.K, TC.J TC.T, TC.S
K-M
Indication of operational states Supply voltage 1st / 2nd output relay energized
Electrical connection Wire size
Temperature sensors
CC-U/TCR Thermocouples
Relay, 2 c/o contacts 250 V AC 4A 3A 4A 2A 12 V 10 mA / 0.6 VA (W) 10 ms 30 x 106 switching cycles 0.1 Mio. switching cycles
AC12 (resistive) 230 V AC15 (inductive) 230 V DC12 (resistive) 24 V DC13 (inductive) 24 V
Supply circuits Rated supply voltage Supply voltage range Supply voltage tolerance Rated frequency Power consumption
General data Ambient temperature range
Voltage
0-20 mA 0-1 V / 1-5 V PT100 4-20 mA 0-10 / ±10 V approx. 50 approx. 1,5 M 2-100 % of selected input range 5-50 % of threshold ±0.5 % of full-scale
Input resistance Adjustable threshold Adjustable hysteresis Repeat accuracy (constant parameters) Output circuits - Relay outputs Rated switching voltage Rated switching current
Current
CC-U/RTDR
EN 61000-6-2 Level 3 (±6 kV / ±8 kV) 10 V/m Level 3 (±2 kV / 5 kH) 2 kV / 1 kV 10 V Class B 2.5 kV 2.5 kV
ABB
Analog signal converters CC-E/I, CC-E IAC/ILPO Technical data Type
CC-E/I J-G-H
Input circuits - Analog inputs Rated input range Measuring frequency Overload capacity of inputs
input range 1 input range 2
Gain adjustment range Offset adjustment range Input impedance / resistance Output circuits - Analog outputs
Accuracy 1) Offset adjustment range Gain adjustment range Residual ripple Response time Transmission frequency Reaction to input circuit interruption Supply circuits Supply voltage Supply voltage tolerance Power consumption
K-M
Indication of operational states Supply voltage General data Ambient temperature range
operation storage
Temperature coefficient Degree of protection (DIN 40050) Mounting position Mounting
DC current
2 meas. ranges selectable
0-5 A / 0-20 A
0-1 A / 0-5 A / sinusoidal 50/60 Hz 10 x INom (50 A) for max. 2 s 10 x INom (200 A) for max. 2 s 5 m
10 x INom (50 A) for max. 1 s 10 x INom (200 A) for max. 1 s ±5 % (universal devices) ±5 % (universal devices) 20 A : 2.5 m 5A : 65 m D-F Current
A-C Voltage
DC versions 24 V DC -15...+15 % typ 1.5 W
AC versions 110-240 V AC 50/60 Hz -15...+10 % typ 1.5 VA
5
12-30 V DC -
U: green LED
-
0...+60 °C -20...+80 °C ± 500 ppm/°C
-20...+60 °C -40...+80 °C 300 ppm/°C
IP20 ventilation slots on top and bottom DIN rail, snap-on mounting
Electrical connection Wire size
rigid fine-strand
4 mm2 (12 AWG) 2.5 mm2 (14 AWG)
1x2.5 mm2 (1x14 AWG)
EN 61000-6-2 Level 3 (±6 kV / ±8 kV)
IEC/EN 61000-4-2
10 V/m
IEC/EN 61000-4-3 IEC/EN 61000-4-4 IEC/EN 61000-4-5 IEC/EN 61000-4-6 EN 61000-6-4
Isolation data Test voltage (between all isolated circuits) Rated insulation voltage
1)
AC current 0-5 A / 0-20 A
F-E passive current output in proportion to input current 0-20 mA / 4-20 mA 0-10 V 4-20 mA 12 V DC: 150 , 500 1.0 24 V DC: 750 30 V DC: 1050 ± 2 % of full-scale ±5 % (universal device) ±5% ±5 % (universal device) ± 20 % < 0.5 % 0.5 s 0.6 s DC or 50/60 Hz AC: 50/60 Hz Low fail safe: output voltage < 200 mA, output current < 400 µA
Output signal Output burden / load
Electromagnetic compatibility Interference immunity electrostatic discharge (ESD) electromagnetic field (HF radiation resistance) fast transients (Burst) powerful impulses (Surge) HF line emission Interference emission
CC-E IAC/ILPO C-D
Level 3 (±2 kV / 5 kH) ±2 kV / ±1 kV 10 V Class B 2.5 kV AC -
250 V AC
includes: non-linearity, factory setting, drift of temperature, supply voltage and output load
ABB
221 2CDC110004C0205
Analog signal converters CC-U/I, CC-U/V Technical data Type Input circuits - Analog inputs
J-G-H
Rated input range Measuring frequency Overload capacity of inputs
0-600 Hz input range 1 input range 2
10 x INom (10 A) for max. 2 s 10 x INom (50 A) for max. 2 s
D-F, A-C
Current 0-20 mA, 4-20 mA 600
Voltage 0-5 V, 1-5 V, 0-10 V, 2-10 V, ± 10 V 4.7 K ±0.5 % of full-scale ±250 ppm/°C max. ±300 ppm/°C max. < 0.15 % 150 ms
K-M 24-48 V DC 24-48 V DC, 24 V AC DC: -15...+15 % 2 W at 24 V DC
110-240 V AC 110-240 V AC, 100-300 V DC AC: -15...+10 % 0 Hz or 50/60 Hz 4.5 VA at 230 V AC U: green LED
operation storage
-20...+60 °C -40...+80 °C any DIN rail (EN 50022), snap-on mounting / screw mounting with adapter
rigid fine-strand
plug-connector with screw terminals 1.5 mm2 (16 AWG) plug-connector with screw terminals 2.5 mm2 (14 AWG)
Mounting position Mounting Electrical connection Wire size
±15 % ±20 % > 800 k
Indication of operational states Supply voltage General data Ambient temperature range
-
1A: 60 m, 5 A: 12 m
Supply circuits Rated supply voltage Supply voltage range Supply voltage tolerance Rated frequency Power consumption
5
CC-U/V any voltage signals, RMS measurement 0-100 V, 0-200 V 0-300 V, 0-400 V 0-500 V, 0-600 V
0-1 A 0-5 A
Gain adjustment range Offset adjustment range Input impedance / resistance Output circuits - Analog outputs Output signal Output load Accuracy1) Temperature coefficient Residual ripple Response time
CC-U/I any current signals, RMS measurement
Standards Product standard Low Voltage Directive EMC Directive RoHS Directive Electromagnetic compatibility Interference immunity electrostatic discharge (ESD) electromagnetic field (HF radiation resistance) fast transients (Burst) powerful impulses (Surge) HF line emission Interference emission
IEC/EN 61000-4-2 IEC/EN 61000-4-3 IEC/EN 61000-4-4 IEC/EN 61000-4-5 IEC/EN 61000-4-6 EN 61000-6-4
EN 61000-6-2 Level 3 (±6 kV / ±8 kV) 10 V/m Level 3 (±2 kV / 5 kH) 2 kV / 1 kV 10 V Class B
Isolation data Insulation voltage (between all isolated circuits) Test voltage (between all isolated circuits)
1)
1.5 kV 1.5 kV / 50 Hz
includes: non-linearity, factory setting, drift of temperature, supply voltage and output load
222 2CDC110004C0205
ABB
Analog signal converters CC-E, CC-U
Technical diagr., Connection diagr., Dimensional drawings Technical diagrams
Connection diagram CC-U/x Width 22.5 mm (0.89 in)
Load limit curves CC-U/xxR Resistive DC load
L
K
J
H
G
1.0 0.9
D
E
F
A
B
C
0.8
2CDC 282 023 F0b06
Derating curve
M
2CDC 282 026 F0b06
2CDC 282 025 F0b06
Resistive AC load
F 0.7
0.5
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
cos
1.0
2CDC 282 014 F0b06
0.6
5 Dimensional drawnings
Dimensions in mm
2CDC 282 011 F0b06
22.5 0,88 "
18 0.71"
2CDC 282 012 F0b06
CC-E IAC/ILPO, CC-E I/I
CC-E/x
.039
ABB
2CDC 282 024 F0b06
CC-U/x , CC-U/xR
223 2CDC110004C0205