3.1 Description of faults
3.1.1
Frequency of disturbances in electrical networks
R: Total number per 100 km line-length 24.08.2006
VEO
VDEW
3.1 Description of faults
3.1.2
Causes for disturbances in electrical networks
lightning stroke other atmospherical effects external effects other effects non-identified effects
R: Total number per 100 km line-length
24.08.2006
VEO
VDEW
3.1 Description of faults
Causes for disturbances in electrical networks (1) Natural Phenomena • • • • • • • •
Lightning Wind, Tornado Ice Snow Galloping conductors Insulator contamination Earthquake, Fire, Flood Other
Human, Foreign Objects, Animals • • • • •
Sabotage Vehicles, Airplanes Trees Animals Others
24.08.2006
3.1.3
3.1 Description of faults
Causes for disturbances in electrical networks (2) System Operation • Switching surge • Overvoltage • Instability (steady-state, transient) • Undesired relay operation • Overload trip • Personal error • other Line or Equipment Failure • Tower structure • Conductor • Ground wire • Insulator assembly (mech. failure) • Terminal equipment • Other Non identified causes
24.08.2006
3.1.3
3.1 Description of faults
3.1.3 /1
Isokeraunic level ares of Untied States and Canada for line outage study
24.08.2006
3.1 Description of faults
Transmission line with galloping conductors
24.08.2006
3.1.3 /2
3.1 Description of faults
Tree-to-Line Contact
24.08.2006
3.1.3 /3
3.1 Description of faults
3.1.4
Causes for disturbances, RWE network 1990 Natural Phenomena Lightning Wind Ice Galloping conductors Human, Foreign Objects, Animals Vehicles Trees Animals Other System Operation Switching surge Undesired relay operation Line or equipment Failure Insulator assembly (mech. failure) Terminal equipment Non identified causes Total sum
24.08.2006
220 kV
380 kV
87 82 0 4
63 33 1 3
3 4 3 6
0 1 0 4
1 2
1 10
1 4 35
1 2 18
232
127
0
3.1 Description of faults
3.1.5
Data of the electrical network of RWE Network data 31.12.1990 220 kV
380 kV
Circuit length Overhead line Cable
6247 km 5 km
4124 km -
Total length
6252 km
4124 km
238
136
116 699 673 2976
42 293 241 1645
Transformers Substations Bays Circuit breakers Isolators and earthing switches
24.08.2006
3.1 Description of faults
3.1.6
Causes for disturbances in power stations Natural Phenomena
System Operation
• • • • •
• • • •
Lightning Extreme coldness Draught Earthquake, Flood Other
Human, Foreign Objects, Animals • Sabotage • Airplanes • Others
Instability (steady-state, transient) Undesired relay operation Personal error Other
Equipment Failure • Coal mills • Boiler • Turbine • Generator • Transformer • Other Non identified causes
24.08.2006
3.1 Description of faults
3.1.7
Faults in power stations
Hydro generation units Thermal generation units
24.08.2006
1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20.
Construction, buildings Pelton turbines Kaplan turbines Steam turbines Additional turbine equipment Boilers Economizer Pipes and collectors Other parts of boilers Additional boiler equipment Subordinary systems Monitoring devices Generator stator winding Generator rotor winding Generator exciter circuit Other parts of generator Drives Transformer Other electrical subsystems External effects
3.1 Description of faults
3.1.8
Annual values of non-availabilities on workdays at 8 a.m. (Thermal power plants within UCPTE countries 1978 - 1990)
Year 1978 1979 1980 1981 1982 1983 1984 1985 1986 1987 1988 1989 1990 Mean value 24.08.2006
Planned outages [%] 8,2 8,5 9,2 9,0 8,3 8,6 8,7 9,4 10,8 10,7 11,3 10,2 9,2 9,5
Forced outages [%] 12,0 10,4 9,5 10,8 11,8 10,9 9,0 9,6 8,7 8,0 6,7 7,7 8,5 9,4
Total [%] 20,2 18,9 18,7 19,8 20,1 19,5 17,7 19,0 19,5 18,7 18,0 17,9 17,7 18,9
3.1 Description of faults
3.1.9
Annual values of non-availabilities on workdays at 8 a.m.
Non-availability [%]
(Thermal power plants within UCPTE countries 1978 - 1990)
Mean Planned outages 24.08.2006
Forced outages