TEST CERTIFICATE - Cement SSBC REGD. NO. 041909004 & VUDA REGD NO. UDA/PLAN-05/233/2005
Ref.No.: GES/CM/GHD/8349/48
Date : 03 -12-2008
Client
: ADANI POWER LTD.
Name of Work
: Construction of 5 X 660 MW TPP at Mundra Adani Power Limited
Refrence No.
: APL / 660 / Civil FQA / Mundra / SEPCO 3 / 011 Dated : 12.11.08
Material Recd.
: Grouting Material - Sika - 104
Batch No.
: G 40720 B
Shelf Life
: 6 Months
PHYSICAL TESTS 1 Flowability : Maximum Flow Distance in mm Grout Consistancy
Gap Width in mm
Flowability
Under 250 mm head
20
1465
40
2775
2 Shrinkage : Nil 3 Un - Restrained Expansion :
2.52 %
4 Compressive Strength : 1-Days Strength :
29.59 N/mm2
3-Days Strength :
46.16 N/mm2
7-Days Strength :
50.00 N/mm2
Conclusion : The sample tested in Accordance with ASTM - C - 939 - 02 & ASTM - C - 940 - 98 NOTE : 1.This certificate / report shall not be published for commercial purpose except in full unless permited for the publication of an approved abstract by the Director, GEO ENGINEERING SERVICES, Adipur. 2.This test certificate applies only to the samples received in the laboratory.
Authorized Signatory D:\Documents\Reports-2009\Cement - 09\[cement 20-41.xls]48-adani-grout
TEST CERTIFICATE - Cement SSBC REGD. NO. 041909004 & VUDA REGD NO. UDA/PLAN-05/233/2005
Ref.No.: GES/CM/GHD/8349/48
Date : 03 -12-2008
Client
: ADANI POWER LTD.
Name of Work
: Construction of 5 X 660 MW TPP at Mundra Adani Power Limited
Refrence No.
: APL / 660 / Civil FQA / Mundra / SEPCO 3 / 011 Dated : 12.11.08
Material Recd.
: Grouting Material - BASF - Master Flow 915
Batch No.
: M 149408
Shelf Life
: 6 Months
PHYSICAL TESTS 1 Flowability : Maximum Flow Distance in mm Grout Consistancy
Gap Width in mm
Flowability
Under 250 mm head
20
1570
40
2830
2 Shrinkage : Nil 3 Un - Restrained Expansion :
2.90 %
4 Compressive Strength : 1-Days Strength :
25.58 N/mm2
3-Days Strength :
31.60 N/mm2
7-Days Strength :
33.25 N/mm2
Conclusion : The sample tested in Accordance with ASTM - C - 939 - 02 & ASTM - C - 940 - 98 NOTE : 1.This certificate / report shall not be published for commercial purpose except in full unless permited for the publication of an approved abstract by the Director, GEO ENGINEERING SERVICES, Adipur. 2.This test certificate applies only to the samples received in the laboratory.
Authorized Signatory D:\Documents\Reports-2009\Cement - 09\[cement 20-41.xls]48-adani-grout