SYSTEM PANELCONTROL SYSTEM PANELCONTROL PROVIDES. -AUDIBLE & VISUAL INDICATIONS OF ALARMS & ADVISORIES ON SYPD & SYSD . -DISPLAYS C.P. LOAD. -DISPLAYS EXTERNAL ALARMS -IN EWSD SYSTEM FAULT DETECTION, FAULT ANALYSIS AND SIGNALLING IS DONE BY THE SYSTEM . -THEN ALARM CONFIRMATION AND FAULT CLEARANCE IS THEN PERFORMED BY THE MAINTENANCE STAFF. .
1
TOPICS FOR DISCUSSION A. OVERVIEW OF SYSTEM PANEL CONTROL C. SYSTEM PANEL CONTROL MODULE D. ALARM LEVELS. E. FUNCTIONS OF KEYS & LEDS OF SYPD. E. SUPERVISION OF SYP. F. OPERATING STATUS OF SYP. G. ADMINISTRATION OF SYP ALARMING 2
Subs
LTG:B
DLU
Dig: Trunks
LTG:C CCNC
SYPD
SN MB
SYPC
CP CCG
SYSD
OMT MDD
MTU ALARAM CONSOLE
PRINTER
3
LED of System Panel Display
Month
Day
Time Fire
Line/trunk
Switching network SN
4
groups LTG 3
:
-
2
5
1
Maintnance Service External alarm equipm alarm
Coordination porcessor CPCentral units ERL
Processor load System Panel SYP Update
External alarms
16
32
DC power supply 17 Air conditioning 18
Message 8 9
Text Accept
31
supervision
33
Power failure
7
Common channel buffer signalling 6
Trunk group alarm Line lockout Sinnaling links Call idnentification
11 12 13 14
Trunk group External 27 DLU alarms blocked Cat.1 28 AdministraCat.2 tive alarm 29 Recovery System operator 30 Time insecure
SYSTEM PANEL
34 35
19
Clock
10
Entry 15
36
20 21
37
22
38
23 HW units
39
Signalling
24 links blocked 40 Alarm
25 Indications 41 26
Suppressed
42
4
Type of
Horn R L 2 LEDs
1 LED
signalalarm Critical
Alternating flashing at
unaccepted
f=2.5 Hz
Continuous f=488 Hz off
accepted at SYPD
f=2.5 Hz
off
accepted by MML command Major alarm unaccepted accepted at SYPD by command
--------
f=1.25 Hz
Flashing at f=2.5 Hz f=2.5 Hz
accepted f=1.25 Hz MML
off
Flashing at Hz
Clocked tone
f=2.5 800/800 ms off
f=2.5 Hz
off
f=1.25 Hz 5
Minor alarm
off
unaccepted
Continu Continuous -ous
accepted at SYPD
Pulse * 800 ms
Continuous
accepted by MML command Indication
Continu- Continuous ous
off
ContinuContinuous ous
Off
6
ALARM LEVELS. THERE ARE THREE LEVELS OF ALARMS:A. CRITICAL ALARMS - REPRESENTS SERIOUS DEGRADATION OF SERVICE. B. MAJOR ALARMS -
NO DIRECT INFULENCE ON SERVICE.
C. MINOR ALARMS -
NO EFFECT ON SERVICE.
-
ALARM WITH HIGHEST PRIORITY FOR A FUNCTIONAL UNIT DISPLAY FIRST AT SYPD.
-
CRITICAL ALARM IF NOT ACCEPTED WITHIN 5 MINUTES, THE HORN SOUNDS AT MAXIMUM 7 VOLUME.
CRITICAL ALARMS IT REPRESENTS SERIOUS DEGRADATION OF SERVICE REQUIRES IMMEDIATE ACTION FROM O & M PERSONAL. THIS ALARM APPEARS WHEN ACTIVE & REDUNDANT EQUIPMENT HAVE FAILED . IN THIS TWO LEDS FLASH ALTERNATELY AND HORN SOUNDS CONTINUOUSLY. EXAMPLES: •
SN0 / SN1 HAVE FAILED & ONE OF THEM IS IN OPERATING STATE UNA.
•
BOTH DLU SYSTEM 0 & 1 HAVE FAILED & ONE OF THEM IS IN OPERATING STATE UNA.
•
CP TO SYPC INTERFACE IS FAULTY . 8
MAJOR ALARM •MAJOR ALARM HAS NO DIRECT INFULENCE ON SERVICE. •BUT THIS KIND OF ALARMS HAS TO BE TREATED IMMEDIATELY SINCE REDUNDANT SYSTEM UNIT HAS FAILED. •
IN THIS CASE LEFT LED OUT OF TWO LEDS AND SINGLE LED FLASH AND HORN GIVES A CLOCKED TONE OF 800/800 ms .
EXAMPLES. •
SN0 OR SN1 IS IN OPERATING STATE UNA.
•
ONE CCG IS IN OPERATING STATE UNA.
•
ONE SYPD IS FAULTY. 9
MINOR ALARM ON
MINOR ALARM HAS LITTLE OR NO INFLUENCE SERVICE.
IN THIS CASE HORN SOUNDS FOR 800 ms ONLY, SINGLE LED LIGHTS AND RIGHT LED OF THE TWO LEDS LIGHTS.
EXAMPLES: • -
ONE OF THE FOLLOWING FAULT HAS OCCURRED ON A PCM LINK OR IN A DLU. ALARM INDICATION SIGNAL IN MULTIFRAME. -ALARM INDICATION SIGNAL IN PULSE FRAME
10
FUNCTIONAL OVERVIEW OF SYSTEM PANEL SYSTEM PANEL CONSISTS OF :(I)
SYSTEM PANEL CONTROL (SYPC), WHICH IS HOUSED IN R:MB/ CCG
(II)
SYSTEM PANEL DISPLAY (SYPD) / (SYSD). THERE CAN BE A MAXIMUM OF 8 SYPDs. ONE IS CONFIGURED AS MASTER. HOWEVER SEVERAL OR ALL CAN BE CONFIGURED AS MASTER IN EXCEPTIONAL CASES. ALARMS AND INDICATIONS APPEAR SIMULTANEOUSLY ON ALL SYPDs. GENERALLY ONLY ONE SYPD IS PROVIDED 11
D C C
I O C S Y P C
C O M S Y P C
R M E A
T/ T/ T RM RM X A S S S Y Y Y
C D E X 0
C D E X 1
C C C C C D D D D D E E E E E X X X X X 2 3 4 5 6
C D E X 7
C C D D D E E C X X C 8 9
P P P C C C Module frame 0 A1for system panel control, F:SYPC
12
SYP SYPD0
7-segment displays
LEDs
Display
Pushbutton Panel
External horn*)
Internal horn
•• •
To up 24 to external signaling units*) Tofault up 24 to external SYPC
supervisory units
IOP:MB0
•• • • ••
SYPD 1 TO 3
SYPD 1 TO 7
IOP:MB1
Structure of the system panel
13
FUNCTION OF KEYS & LEDs OF SYPD PUSH BUTTON KEYS 1.
UPDATE KEY
2.
TEST KEY
3.
ACCEPT KEY
PRESSING ACCEPT KEY SWITCHES OFF HORN, BUT DOES NOT ACTULLY ACCEPT ALARM.
7-SEGMENT DISPLAY -TIME -MONTH-DAY -PROCESSOR LOAD (UPDATED EVERY 4 SEC. )
SYSTEM DISPLAYS
14
ACCEPT KEY IS PROVIDED ON EACH SYPD. PRESSING OF ACCEPT KEY STOPS THE AUDIBLE SIGNAL OF PARTICULAR SYPD. PRESSING ACCEPT KEY Of MASTER SYPD CAUSES AUDIBLE SIGNAL TO BE SWITHCED OFF CENTRALLY BY THE CO-ORDINATION PROCESSOR . IN CASE OF ALARM AT SYPD DUE TO FAULT, THE OBJECT CAN BE LISTED WITH
DISP ALARM IN CASE OF INDICATIONS, CAUSED BY CONFIGURATION OF HW UNIT TO STATE MBL OR CBL , THE LIST OF HWUNITS CAN BE DISPLAYED BY
DISP INDIC: 15
LEDS & DIGITAL DISPLAYS SYSTEM PANEL DISPLAY IS DIVIDED INTO SIX FUNCTIONAL AREAS. 1.
LINE/TRUNK GROUP
2.
SWITCHING NETWORK
3.
CO-ORDINATION PROCESSOR
4.
SYSTEM PANEL
5.
EXTERNAL ALARMS
6.
MISCELLANEOUS FUNCTIONS
THERE IS DIGITAL DISPLAY OF MONTH, DAY, TIME & PROCESSOR LOAD. 16
SUPERVISION OF SYP CP (IOP: MB) SUPERVISED BY CP & SYPC I.E. CP SUPERVISES SYPC & SYPC SUPERVISES QP SELFSUPERVISION
SYPCO
SYPC
SYPCN
MODULE ALARMS & ITS MEANING
SUPERVISED BY CP & SYPC I.E. CP SUPERVISES SYPD & SYPD SUPERVISES SYPC
LEP - SYP IS FLASHING - > SYPC HAS DETECTED THE UNAVAILABILITY OF ONE SYPD & INDICATES THIS ON17 ALL OTHER SYPD.
LED - SYD & LED – CP ARE FLASHING AT ALL SYPD SYPC HAS NO CONNECTION TO CP . (INTERFACE OR CP PROBLEM)
LED- SYP IS FLASHING & CP- LOAD SEGMENT IS OFF THIS SYPD HAS POWER BUT NO CONNECTION TO SYPC. (IF THIS HAPPENS TO ALL SYPD, THEN SYPC IS FAULTY).
18
SYSTEM PANEL CONTROL MODULES SYPC IS NOT DUPLICATED & IS INSTALLED IN F: SYPC
IOC: SYPC IT IS USED TO CONNECT SYPC TO CP . ON THIS INTERFACE IT RECEIVES NECESSARY DATA FROM CP. IT USES THESE DATAS TO DETERMINE SIGNALS I.E. CRITICAL /MAJOR OR MINOR ALARMS / DAY /TIME OR PROCESSOR LOAD.
RM : FA RECEIVES EXTERNAL ALARMS DIRECTLY VIA THE EXCHANGE OR MDF. IT SUPPLIES DATAS TO SYPC, THE OST OF EXTERNAL EQUIPMENT. 19
COM : SYPC PROCESSOR OF SYSTEM PANEL CONTROL
TXA : SYPC ALLOWS SYPD SIGNALLING TO BE FORWARDED TO EXTERNAL FAULT DEVICE
T/RM: SYPC TRANS / RECEIVES MODULE T/RM0 : SYPC --- > SYPD0 ---- SYPD3 T/RM1 : SYPC ----> SYPD4 ---- SYPD7
20
Administration of External Alarm Lines and Texts EAL DLU EXCH DLU A L E DLUC X
LTG
GP SYPD
EAL EXCH
SN
SYPC RM:EA
OMT
CP
SGC 21
Administration of External Alarm Lines (FOR EXCH SITE) SYPC 0 • Contect • RM: •
(e.g• EA door) 23
CP
COM: SYPC
User EPROM
SYPD
OMT 22
ASSIGNMENT OF INDIVIDUAL EXTERNAL ALARM LINES (EAL) TO THE PINS OF THE MODULE RM:EA
EDL No.
1 2 3 4 5 6 7 8 9 10 11 12
PIN No.
SYPD- LED
EDL No.
RE:EA
34567891011121314-
15 16 17 18 19 20 21 22 31 32 33 34
13 14 15 16 17 18 19
PIN No.SYPD- LED
4344454647 48 49 50 51 52 53 54
35 36 37 38
23
OPERATING STATUS OF SYP
STAT SYP ; UNA MBL ACT HOW TO CONTROL REPORT/ALARM MESSAGES ON OMT-0
ACTOUTSUP; DACTOUT SUP:DEVICE = SYSTEMDEVICE-FUOMT; . 24
ADMINISTRATION OF SYP ALARMING I. ALARM PRIORITIES DISP ALPRIO ; ENTR ALPRIO II. ALARM MODE USED FOR TWO SERVICE FEATURES
STATUS AND HLIM
DISP ALMODE ; ENTR ALMODE III. ALARM DISPLAYS DACT ALDISP; ACT ALDISP;
25
LEVELS FOR EXTERNAL DLU ALARMS
DISP EAL LVL : DLU=-----, EAL= ---; CR EAL LVL : DLU = -------
(910 TO 2550)
EAL = -------
(! TO 16)
LVL = -------
(HIGH /LOW )
26
ALARM AND ARCHIVE FILES HF ARCHIVE
(SYSTEM ARCHIVE FILE)
- STORES ALL MAINTENANCE MESSAGES OF THE SYSTEM - CONTAINS ADDITIONAL INFORMATION ALSO WHICH IS REQUIRED FOR SPECIAL FAULT CLEARANCE BY THE SYSTEM SPECIALIST E.G RECOVERY MESSAGE, AUDIT MESSAGES. -HF ALARM IS A DUIPLICATED CYCLIC FILE. HOW TO READ THE CONTENTS OF ANY ARCHIVE FILE
DISP AENTRY: AFILE=--- , [AENTRY] = ,[TOC]= ; SEL AENTRY : AFILE = , [TIME]= ,[ DATE] = MSG = , [ALPRIP] =---; [ DIR= ]!
27
CR A FILE
AM . ALARM
ALARM FILE
- CONTAINS ALL FAULT MESSAGES WHICH BELONG TO NOT YET CLEARED SYPD ALARMS - CAN ONLY BE READ BY THE OPERATOR WITH COMMAND DISP/SRCH ALARM
THE
- IS A DUPLICATED SYSTEM FILE AUTOMATICALLY CREATED BY THE SYSTEM. - TO READ THE CONTENTS OF AM. ALARM FIL; DISP ALARM : [OBJECT = ] [ ALSTAT=] [ ALPRIO=] SRCH ALARM: [OBJECT=] [ ALSTAT=] [ALPRIO=] [MSGNO=]
28
ASSIGN ALARM TEXT AND ALARM PRIORITY DLU CR EAL SITE = ------
( EXCH / DLU )
EAL = ----- (1 TO 24 FOR EXCH OR 1 TO 16 FOR DLU ) TEXTNO. =
---- (1 TO 40)
ALPRIO = ------( CRITICAL / MAJOR / MINOR )
DISP / CAN EAL SITE = ------
( EXCH / DLU )
EAL = ----- (1 TO 24 FOR EXCH OR 1 TO 16 FOR DLU )
29
ENTER / CANCEL ALARM TEXT ASSIGNMENT DISP AL TEXT : TEXTNO =XX; ENTR AL TEXT : TEXTNO =XX (1 TO 40 ), TEXT=“--”; CAN AL TEXT : TEXTNO =XX;
30