DAFTAR SPESIFIKASI PENGADAAN INSTALASI GAS MEDIS, PADA RSUD NAGAN RAYA, MELALUI DANA APBA TAHUN ANGGARAN 2014 NO

I.

Nama Barang dan Spesifikasi Teknis

Vol.

1 Set

Central Medical Gas.

Included : A. Oxygen Generator Plant Qty:

Consist of: a. Compressor

1 ut

Power

: 5.5 kW/7.5 HP 400V/50Hz

Free Air Delivery

: 15 l/s 4 31.8 cfm

Max. Working Pressure

: 7.5 Bar / 109 psig

Sound Level b. Air Drier

: 60 dB(A), tolerance 3 dB(A) 1 ut

Max. Working Pressure

: 13 Bar / 189 psig

Outlet Pressure Dewpoint

: +5 o C/41 o F

Inlet Capacity

: 45 l/s bar/95 cfm

Pressure Drop

: 0.42 Bar / 6.14 psi

c. Gas Filter Package

1 Set 1 ut

Filter. 1 Nominal Capacity

: 17 l/s / 36 cfm

Maximal Capacity

: 21 l/s / 45 cfm 1 ut

Filter. 2 Nominal Capacity

: 20 l/s / 42 cfm

Maximal Capacity d. Air Receiver Vessel

: 21 l/s / 45 cfm

Capacity

1 ut : 500 liter

Testing Pressure

: 15 bar

Working Pressure

: 10 bar

Iron Plate thickness e. Oxygen Generator

: 6 mm 1 ut

Product flow

: 4.2 Nm3/h – 3.8 Nm3/h

Product purity

: 99.5 %

Outlet Pressure

: 4 Bar

Inlet Pressure Requirements : 7.5 Bar : Included Oxygen Monitor f. Oxygen Buffer Vessel Capacity

1 ut : 500 liter

Testing Pressure

: 15 bar

Working Pressure

: 10 bar

Iron Plate thickness

: 6 mm 1 Set

B. Oxygen Filling Station for Cylinders Consist of: a. Oxygen High Pressure Compressor 150 Bar(g) Max. Discharge

: 2200 psig

Cooling

: Air Cooled

Gas outlet : ¼” FPT b. Filling Ramp with 4 outlets BS 5/8”

Qty: 1 ut

1 ut

Page 1 of 4

Ket.

NO

Nama Barang dan Spesifikasi Teknis

C. Central N2O (Nitrous Oxide Automatic Changeover Manifold)

Vol.

1 Set

Specification: Manifold System : Full Automatic Changeover Manifold, Capacity : 500 LPM, Air Presssure: 70 to 106 kPa Provided with monitoring to detect and display: 1. Duty Bank Operating 2. Duty Bank Empty, Standby Bank Operating 3. Standby Bank below 10% when the Duty Bank is empty 4. Reserve Bank Low 5. Pipeline Pressure Fault 6. Alarm warning System Complete with : Symetrical Header with Automatic System Non Return Valve (NRV) to each Pig Tailpipe Bullnose/ Pig Tailpipe Cylinder Rack Kit with Restraining Chains Cylinder Rack Capacity: 2 x 2 Cylinder. D. Central Vacuum Pump: Consist of: a. Medical Vacuum Pumps (Duplex rotary vane type ) b. Duplex baterials filtration system c. Vacuum Receiver Tank, capacity 500Lt.

2 ut 2 ut 1 ut

E. Main Cooper Pipe, Type L, ASTM-B 88/819:

II.

1 Set Qty:

1 Ls Qty:

Consist of: a. Oxygen, Cooper Pipe size Ø 1 1/8" b. Nitrous Oxide, Cooper Pipe size Ø 3/4"

77 mtr

c. Vacuum, Cooper Pipe size Ø 1 1/8"

53 mtr

53 mtr

Instalasi Ruang Operasi (OK), Pre & Post Op:

1 Set Qty:

Consist of: A. Oxygen Terminal Wall Outlet

6 Unit

Specification: Complies with BS EN 737-1, BS 5682:1984, HTM 2022 and C11 Accept medical gas probes to BS 5682:1984 CE marked Individually pressure and leak tested Integral check valve - allow removal of housing and socket assemblies for maintenance without closing down the intire pipeline Construction of the terminal unit shall be of machined brass and injection moulded polymer with stainless steel Teflon coated rolling pins Each of the gas specific components will have the gas service onto it to ensure safety and compliance with the standard. Wall mounted terminal units will incorporate an anti-swivel pin to privent rotation of installed equipment. The unit will be enclose in a white ABS decorative mounting box and the fascia shall have rounded corners to avoid the possibility

Page 2 of 4

Ket.

NO

Nama Barang dan Spesifikasi Teknis

Vol.

of injury The box can be supplied with a flush mounting bezel as a plaster finish. B. Nitrous Oxide (N2O) Terminal W Outlet

4 Unit

Specification: Accept medical gas probes to BS 5682:1984 CE marked Individually pressure and leak tested Integral check valve - allow removal of housing and socket assemblies for maintenance without closing down the intire pipeline Construction of the terminal unit shall be of machined brass and injection moulded polymer with stainless steel Teflon coated rolling pins Each of the gas specific components will have the gas service onto it to ensure safety and compliance with the standard. Wall mounted terminal units will incorporate an anti-swivel pin to privent rotation of installed equipment. The unit will be enclose in a white ABS decorative mounting box and the fascia shall have rounded corners to avoid the possibility of injury The box can be supplied with a flush mounting bezel as a plaster finish. C. Vacuum/ Suction Terminal Wall Outlet Complete Regulator and J

6 Unit

Specification: Accept medical gas probes to BS 5682:1984 CE marked Individually pressure and leak tested Integral check valve - allow removal of housing and socket assemblies for maintenance without closing down the intire pipeline Construction of the terminal unit shall be of machined brass and injection moulded polymer with stainless steel Teflon coated rolling pins Each of the gas specific components will have the gas service onto it to ensure safety and compliance with the standard. Wall mounted terminal units will incorporate an anti-swivel pin to privent rotation of installed equipment. The unit will be enclose in a white ABS decorative mounting box and the fascia shall have rounded corners to avoid the possibility of injury The box can be supplied with a flush mounting bezel as a plaster finish. D. Single Plastic Box Area Valve Service Unit (AVSU) : Oxygen, 22mm, Single AVSU

1 Unit

Nitrous Oxide, 22mm, Single AVSU

1 Unit

Vacuum 22mm, Single AVSU

1 Unit

Area Alarm, 4 Gas,

1 Unit

Designed to monitor high and low pressure from local pressure switches. E. Distribution Cooper Pipe, Type L, ASTM-B 88/819: Oxygen, Cooper Pipe, Type L, ASTM-B 88/819: Size Ø 3/8"

18 mtr

Size Ø 1/2"

30 mtr

Page 3 of 4

Ket.

NO

Nama Barang dan Spesifikasi Teknis

Vol.

Size Ø 5/8"

23 mtr

Size Ø 3/4"

12 mtr

Size Ø 7/8"

15 mtr

Ket.

6 mtr

Size Ø 1" Nitrous Oxide, Cooper Pipe, Type L, ASTM-B 88/819: Size Ø 3/8"

12 mtr

Size Ø 1/2" Size Ø 5/8"

18 mtr 15 mtr

Size Ø 3/4"

38 mtr

Vacuum, Cooper Pipe, Type L, ASTM-B 88/819: Size Ø 1/2" Size Ø 5/8"

36 mtr 23 mtr

Size Ø 3/4"

12 mtr

Size Ø 7/8"

15 mtr 6 mtr

Size Ø 1"

III. PEMBANGUNAN GEDUNG SEMI PERMANEN UNTUK CENTRAL GENERATOR

1 Lot

Specification: Dimensi gedung PxLxT: 10 m x 8 m x 4 m Konstruksi rangka atap: baja ringan Dinding: bata dan berventilasi 4 sisi. Lantai: beton/keramik tahan gores Listrik 3 phasa, Cap. Min. 30 kVA, dgn panel Induk dan Lampu Penerangan Minimal 1 buah Wastafel

Banda Aceh,

2014

Kuasa Pengguna Anggaran