Isea Family Grease/sand Trap - Pre-treatment Of Gray Water Sewage

  • Uploaded by: AG-Metal /Tretman Otpadnih Voda/Wastewater Treatment
  • 0
  • 0
  • June 2020
  • PDF

This document was uploaded by user and they confirmed that they have the permission to share it. If you are author or own the copyright of this book, please report to us by using this DMCA report form. Report DMCA


Overview

Download & View Isea Family Grease/sand Trap - Pre-treatment Of Gray Water Sewage as PDF for free.

More details

  • Words: 697
  • Pages: 2
FAMILY

PRODUCT CATEGORY

GREASE TRAP PRODUCT NAME

FAMILY APPLICATION

PRE-TREATMENT OF GRAY WATER SEWAGE CAPACITY

NT E D AM

C E NC

AM P L

LI

E N TO G MA

Certified Quality System

E

I

TE

AM

PA

FROM 5 TO 180 INHABITANTS EQUIVALENT

DESCRIPTION FAMILY is a grease trap entirely made of high density polyethylene and suitable for private residences or small buildings installation. Grease traps are important components in wastewater treatment and are utilized for the preliminary treatment of gray water sewage coming from kitchen sinks, washing machines, wash tubs and showers. The volume of a grease trap tank is designed to provide an adequate residence time of the incoming wastewater. During this period fats, oils and greases (FOG) are separated from the water by the physical process known as flotation which takes place because the specific weight of these substances is equal or less than the one of the water, therefore in non turbulent conditions, they float on the surface of the tank from where they can be easily removed. Inside grease trap also sand, debris and other suspended solids are separated from the water and having a greater specific weight they settle on the bottom of the tank. ISEA’s grease trap FAMILY is provided with PVC inlet and outlet piping. Access to the plant is by two inspections portholes, one in the flotation chamber and the other by the outlet pipe. Both ports are protected by screw-on covers.

INSTALLATION

USE

EXCAVATION

Dig a hole of appropriate dimensions. The bottom of the excavation must be leveled and compacted with a 10 cm layer of fine sand (grain size 0-5 mm).

BACKFILLING

Fill the tank with clean water before backfilling to avoid collapse of the polyethylene structure during backfilling. Once the tank is full, dump sand around the tank and level it. For a walk-onsolution build a 5 cm thick light concrete layer on top of the tank and finish with a 40 cm thick soil. For a drive-on solution a reinforced concrete slab is required to protect the tank. Accessible manholes are required for inspection and maintenance.

PIPING AND FITTINGS

PVC pipes and fittings are utilized for connecting the grease trap to the inlet and outlet lines.

PERIODIC CHECKS Periodically verify that no large bodies obstruct the sewage inlet or outlet by opening the AND MAINTENANCE inspection ports.

Also, check that no sand obstructs the outlet pipe. At least once a month check that the grease is not lower than the outlet pipe. Floating material must be removed periodically using a specialized company and disposed in appropriate sites.

68

ØE

ØE

ØU

grease

HE

ØU

H

grease

HE

H

DIMENSIONS & DESIGN

Mod. 400 Mod. 800 Mod. 1200 Mod. 1500 Mod. 2000 Mod. 3000 Mod. 4000 Mod. 5000

Mod. 125 Mod. 250 Mod. 350

HU

HU inert material inert material

grease chamber inspection

grease chamber inspection

outlet inspection

outlet pipe inspection

L L

a

b

a b

l

l

FAMILY - Grease trap Code

0513 0514 0515 0511/1 0511/2 0511/3 0511/4 0511/5 0511/6 0511/7 0511/8

Item

"Family" "Family" "Family" "Family" "Family" "Family" "Family" "Family" "Family" "Family" "Family"

E.I.

125 250 350 400 800 1200 1600 2000 3000 4000 5000

5 10 15 20 25 35 50 80 100 150 180

Seats

___ ___ ___ ___ ___ 100 200 300 400 600 750

Capacity

D/LxP

H

HE

HU

øE

øU

a

b

(litri)

(cm)

(cm)

(cm)

(cm)

(mm)

(mm)

(mm)

(mm)

100 200 300 400 600 1200 1600 2000 3000 4000 5000

60x68 60x68 60x68 80x80 80x80 120x120 120x120 120x120 160x160 160x160 160x160

62 82 100 80 120 120 160 200 160 200 240

43 63 83 62 102 95 125 175 125 175 215

40 60 80 58 97 92 120 170 120 170 210

110 110 110 110 110 110 125 140 140 160 160

100 100 100 100 100 100 125 140 140 160 160

100 100 100 100 100 100 100 100 100 100 100

200 200 200 400 400 400 400 400 400 400 400

INFO Performance Grease trap FAMILY is designed in accordance with DIN 4040 and ISEA guarantees the removal of 90% of the floating materials. 69