A AAV AC AD AFF ATF
DOUBLE LINE DUCT
O AUTOMATIC AIR VENT AIR COMPRESSOR AIR DRYER, AUTOMATIC DRAIN ABOVE FINISHED FLOOR AUTOMATIC TRANSMISSION FLUID
OA ORD
OUTSIDE AIR OVERFLOW ROOF DRAIN
OR
P P
OR PUMP
PIPING
DUCT SECTION (EXHAUST OR RETURN)
THESE NOTES APPLY TO ALL M, FP & P DRAWINGS UNLESS NOTED OTHERWISE SLOPE (DN TOWARD ARROW DIRECTION) DIRECTION OF FLOW
SEE SPECIFICATION DIVISION 15 FOR INSTALLATION AND OTHER REQUIREMENTS FOR MECHANICAL WORK SHOWN ON "M", "FP" AND "P" SERIES DRAWINGS. 1.
THE DESIGN SHOWN ON THE DRAWINGS IS BASED ON THE EQUIPMENT MANUFACTURERS LISTED IN THE MECHANICAL EQUIPMENT SCHEDULES. EQUIPMENT PROPOSED BY THE CONTRACTOR THAT IS NOT LISTED IN THE SCHEDULES SHALL BE SUBMITTED TO CITY/BOROUGH OF JUNEAU AS A REQUEST FOR SUBSTITUTION IN ACCORDANCE WITH DIVISION 1.
2.
PROVIDE ALL MECHANICAL SYSTEMS IN ACCORDANCE WITH THE FIRE WALL, FIRE BLOCKING AND FIRE STOP PROVISIONS SHOWN ON THE ARCHITECTURAL DRAWINGS.
3.
COORDINATE SUPPLY AIR DIFFUSERS AND RETURN/EXHAUST AIR GRILLE LOCATIONS WITH ARCHITECTURAL DRAWINGS. COORDINATE DUCT ROUTING WITH LIGHT FIXTURE LOCATIONS.
4.
MECHANICAL WORK SHOWN IS DIAGRAMMATIC. PROVIDE OFFSETS, TRANSITIONS, AND OTHER DUCTWORK, PIPING AND ASSOCIATED CONSTRUCTION WHERE REQUIRED TO AVOID BUILDING STRUCTURAL ELEMENTS OR THE WORK OF OTHER TRADES.
5.
DUCTWORK DIMENSIONS SHOWN ARE NET INSIDE DIMENSIONS. ENLARGE DUCT DIMENSIONS AS REQUIRED FOR INTERNALLY LINED DUCTWORK, SEE SPECIFICATIONS.
6.
INDICATES LIQUID/GAS TRANSPORTATION BY PIPE, CHWR: CHILLED WATER RETURN CHWS: CHILLED WATER SUPPLY HWR: HEATING WATER RETURN HWS: HEATING WATER SUPPLY
PAINT EXTERIOR PIPING, DUCTWORK, FANS, CURBS AND SHEET METAL WITH URETHANE FINISH, COLOR AS SELECTED BY ARCHITECT. PAINT UNFINISHED STEEL, GALVANIZED, ALUMINUM OR SST EXTERIOR SURFACES, MATERIALS OR EQUIPMENT, PROVIDED UNDER DIVISION 15, COLOR AS SELECTED BY ARCHITECT.
7.
TEMPERATURE SENSORS SHALL BE LOCATED WHERE SHOWN 48 INCHES ABOVE FINISHED FLOOR.
8.
PROVIDE BIRDSCREENS FOR ALL LOUVERS AND ALL OUTSIDE AIR INTAKES.
45° OR 90° OFF BOTTOM
9.
PENETRATE ROOF DECKS AS REQUIRED TO INSTALL MECHANICAL WORK. PROVIDE BLOCKING AROUND PENETRATIONS AND AS NOTED ON STRUCTURAL DRAWINGS. SEAL ALL PENETRATIONS AIR AND WATER TIGHT.
DUCT SECTION (SUPPLY) REDUCER
B B BFF BTUH BW
BOILER BELOW FINISHED FLOOR BRITISH THERMAL UNITS PER HOUR BOOT WASH
C CA CW CFM CO
COMPRESSED AIR, LOW PRESSURE, 100PSIG COLD DOMESTIC WATER CUBIC FEET PER MINUTE CLEANOUT
D E E EA EB EC EF EO1 EO2 EVP EWC EXH EXST EW
EXHAUST EXHAUST AIR ELECTRIC BASEBOARD ELECTRIC CEILING PANEL EXHAUST FAN ENGINE OIL, 15W40 ENGINE OIL, 5W20 EVAPORATOR ELECTRIC WATER COOLER EXHAUST EXISTING EYEWASH
Q R RA RETURN AIR RPBP REDUCED PRESSURE BACKFLOW PREVENTOR RD ROOF DRAIN RF RETURN FAN RG RETURN GRILLE
FCO FD FTU FRL
FLOOR CLEANOUT FLOOR DRAIN FAN TERMINAL UNIT FILTER, REGULATOR, LUBRICATOR
G GPM GR
GALLONS PER MINUTE GREASE
S SA SCF SD SF SHR SL SR SS
SINK SUPPLY AIR SOURCE CAPTURE FAN SUPPLY DIFFUSER SUPPLY FAN SHOWER SLOPE SUPPLY REGISTER STAINLESS STEEL
T T TD TYP
TANK TRENCH DRAIN TYPICAL
UH UR
UNIT HEATER URINAL
H HB HC HW HF HP HWR HWS HV HX
HEADER HOSE BIBB HEATING COIL HOT DOMESTIC WATER HYDRAULIC FLUID HIGH PRESSURE COMPRESSED AIR, 150PSIG HEATING WATER RETURN HEATING WATER SUPPLY HEATING AND VENTILATION UNIT HEAT EXCHANGER
V VFD VL VTR
W WC WH WM
IA IW
INTAKE AIR INDUSTRIAL WATER (NON-POTABLE)
DUCT WITH LINING/INSULATION
STRAINER CHECK VALVE
TURNING VANES WCO WALL CLEANOUT FCO/ FLOOR CLEANOUT/ YARD CLEANOUT YCO COLD DOMESTIC WATER (CW)
SUPPLY DIFFUSER OR GRILLE. THE NUMBER OF ARROWS AND DIRECTION INDICATES 1, 2, 3, OR 4-WAY DEFLECTION
HOT DOMESTIC WATER (HW) HOT DOMESTIC WATER RECIRC (HDWR) VENT
RETURN GRILLE OR REGISTER MOUNTED IN A VERTICAL POSITION
WASTE BELOW SLAB
SUPPLY GRILLE OR REGISTER MOUNTED IN A VERTICAL POSITION
POWER OR GRAVITY ROOF VENTILATOR- EXHAUST
45° OR 90° OFF TOP BALL VALVE
VENT VARIABLE FREQUENCY DRIVE VEHICLE LIFT VENT THRU ROOF
HOSE BIBB PRESSUR GAUGE WITH ISOLATION VALVE
DUCT SECTION DUCT BEND DOWN
PUMP DUCT TEE DOWN
Y Y
YARD CLEANOUT
IN-LINE PUMP
INCLINED DROP IN RESPECT TO AIR FLOW
COMPRESSED AIR STATION, LOW PRESSURE
INCLINED RISE IN RESPECT TO AIR FLOW
COMPRESSED AIR STATION, HIGH PRESSURE
TRANSITION DOUBLE LINE TO SINGLE LINE
M MAXIMUM THOUSAND BRITISH THERMAL UNITS PER HOUR MINIMUM MIXING STATION MOP SERVICE BASIN MAKE UP
14. PROVIDE ALL FLOOR DRAINS, FLOOR SINKS, INDIRECT WASTE CONNECTIONS, AND OPEN HUB DRAINS WITH VENTS AND TRAP PRIMERS, EXCLUDING THE MAINTENANCE AREAS AND FUEL BAY. 15. SURVEY AND FIELD VERIFY ALL INVERT ELEVATIONS SHOWN ON PLUMBING DRAWINGS. INVERT ELEVATIONS SHOWN ARE APPROXIMATE, PROVIDE BUILDING WASTE PLUMBING TO PROPERLY INTERCONNECT WITH SITE WASTE PLUMBING. SEE CIVIL DRAWINGS. 16. T-PULL BRANCH PIPING NOT ALLOWED. ALL CHANGES IN DIRECTION SHALL BE MADE WITH FITTINGS.
VOLUME DAMPER
LAVATORY
12. COORDINATE FLOOR AND WALL CLEANOUT LOCATIONS WITH OFFICE CASEWORK VENDOR DRAWINGS AND OTHER FURNISHINGS, RELOCATE AS REQUIRED. 13. PROVIDE FINAL LOCATIONS FOR ROUGH-IN AND FINISH OF WASTE, VENT, AND WATER SUPPLY. CONNECTIONS AND LOCATIONS PER CASEWORK VENDOR DRAWINGS.
THERMOMETER
L
MAX MBH MIN MS MSB MU
11. INSTALL DUCTWORK TO MAINTAIN SERVICE CLEARANCES, ACCESS DOOR CLEARANCES AND COIL PULL CLEARANCES AT ALL HVAC EQUIPMENT.
CONTROL VALVE
(DUCTWORK LESS THAN 12"WIDE)
K
L
10. PROVIDE ACCESS PANELS FOR ALL MECHANICAL EQUIPMENT OR VALVES ENCLOSED IN PERMANENT CONSTRUCTION OR DUCTWORK.
GATE VALVE FLOW
SINGLE LINE DUCT DUCT END
WASTE WATER CLOSET, WATER COLUMN WATER HEATER WASH MACHINE
X
Z I
WALL CLEANOUT
FAN
V
W H
45° TEE
DUCT SIZE IN INCHES
S
U F
SIZE OF SIDE SHOWN SIZE OF SIDE NOT SHOWN 12x20
T
THERMOSTAT
S
SWITCH
M
MOTOR
P
PRESSURE SENSOR
DM
MOTORIZED DAMPER
MS
MOTOR STARTER
17. ALL PENETRATIONS AND SLEEVES THRU FLOORS/ WALLS SHALL BE SEALED WEATHERTIGHT. 18. ALL CONDENSATE DRAINS SHALL BE ROUTED FULLSIZE TO NEAREST WASTE LINE OR APPROVED EXTERIOR LOCATION. 19. ALL UNDER BUILDING PIPING SHALL BE SLOPED AT 2%, FOR YARD PIPING SLOPES SEE CIVIL DRAWINGS. 20. EXTEND VTR PIPING AS REQUIRED TO MAINTAIN 10' MINIMUM CLEARANCE TO OUTSIDE AIR INTAKE LOUVERS.
SD
SMOKE DETECTOR
AQ
AIR QUALITY SENSOR
DP
DIFFERENTIAL PRESSURE SENSOR
ONE INCH AT FULL SIZE
N IF NOT ONE INCH, SCALE ACCORDINGLY
www.tetratech.com 230 South Franklin, Suite 212 Juneau, Alaska 99801 Phone: 907-586-6400 Fax: 907-463-3677
CONSOLIDATED PUBLIC WORKS FACILITY STREETS WING ADDITION, E10-273
MECHANICAL ABBREVIATIONS & SYMBOLS
M0.01 31 - 72
NOTES:
L
M
N
O
1.
DRAWINGS SHOW GENERAL INTENT OF THE DEMOLITION WORK. DEMOLITION OF EQUIPMENT AND COMPONENTS SHALL INCLUDE ALL SUPPORTS, PADS, HANGERS, INSULATION, CONTRLS, STARTERS, ACCESSORIES AND APPURTENANCES NOT REQUIRED FOR THE INSTALLATION OF THE NEW SYSTEM.
2.
SEE DWG M1.02 FOR LOCATION OF RELOCATED EQUIPMENT.
3.
ALL OPENINGS CREATED BY THE ABANDONMENT OR REMOVAL OF EXISTING SYSTEMS SHALL BE PATCHED TO MATCH EXISTING.
-
KEY NOTES:
1.
RELOCATE EF-3, LOUVER AND ALL RELATED APPURTENANCES AND PATCH 14E DUCTWORK FOR CONTINUITY. PATCH WALL OPENING TO MATCH EXISTING.
2.
COMPLETELY REMOVE INDICATED DUCTWORK AND RELATED APPURTENANCES AND COORDINATE WITH INSTALLATION OF NEW WORK INDICATED IN DWG M1.02.
P
1
36x28E EXHAUST LOUVER
1
T
2
T
2
26x42S T
RG-1 12x8 275CFM
T
3
T
4
T
150CFM TYP 4
T
T
T
220CFM
5
HVAC DEMOLITION PLAN 8'
0
8'
1 16'
N ONE INCH AT FULL SIZE
SCALE: 1/8"=1'-0"
IF NOT ONE INCH, SCALE ACCORDINGLY
www.tetratech.com 230 South Franklin, Suite 212 Juneau, Alaska 99801 Phone: 907-586-6400 Fax: 907-463-3677
CONSOLIDATED PUBLIC WORKS FACILITY STREETS WING ADDITION, E10-273
MECHANICAL HVAC DEMOLITION PLAN
M1.01 32 - 72
L
M
O
N
Q
P
NOTES: 5E
AQ
1.
RELOCATE EF-3, LOUVER AND RELATED APPURTENANCES. BALANCE EF-3 TO 1325CFM.
2.
SEE P1.02 FOR RADIANT FLOOR ZONING.
3.
PROVIDE WALL SPEED CONTROLLER WITH 300CFM IN LOW SPEED POSITION AND 500CFM IN HIGH SPEED POSITION.
4.
PROVIDE RIGID GALVANIZED DRYER DUCT WITH MAXIMUM NUMBER OF BENDS TO NOT EXCEED TWO 90° ELBOWS. USE TYPE A VENT HOOD WITH NO MESH SCREEN.
5.
REBALANCE FTU-A2 TO 400CFM
6.
PER ADDITIVE ALTERNATE #1, INSTALL PARALLELOGRAM VEHICLE LIFT IN ROOM 117, BAY 2 OF THE EXISTING MAINTENANCE BAYS AREA.
AQ
4E
AQ
3E FLUID HOSE REEL, TYP 4 BAY 3
12S UP
UH-2, SEE NOTE 3
RG-1 12x8 12E 275CFM
10R 12S
8S
6S
SD-1 8x8 LOCKER 200CFMROOM TYP 2
EC-3
T
BAY 2
7S 16S CORRIDOR 18X12R 22X12R
22X12S
OST LIFT MODULE
RELOCATED EF-3, SEE NOTE 1
10S
EB-1 RG-1 200CFM RG-1 200 CFM
RG-2 300CFM TYP 2
T
SR-1 8x6 150CFM TYP 2 MACHINE
6" DN TO EXHAUST HOSE REEL, TYP
SHOP 2
PARALLELOGRAM LIFT CONTROL MODULE
FTU-6
AQ
RG 240
1
LUBE STORAGE
EF-2
8E
EF-6
5
2
SD-1 8x8 200CFM
CONNECT TO EXST DUCT
G
J
H
K
3
8S
1ST FLOOR HVAC PLAN
4
RG-1 250CFM
H-3
WALL EXH VENT CAP
EB-2 TYP 3
8S
RG-1 12x8 275CFM
12S 8S UP
12X10S
OFFICE
OFFICE
VAV-7 12S 22X12S
6S
EB-2
8S
JAN
FTU-A2
6S
T
10"E
SD-1 8x8 200CFM
EC-1 TYP
VAV-4 6S RG-2 6x6 10S 50CFM
SD-1 8x8 200CFM TYP 2
EC-2
EC-1, TYP 4 SD-2 6x6 150CFM MEN'S TYP 2 RESTROOM
SEE M1.02 FOR HWS/R CONTINUATIONS
EB-1 T
14E CONNECT 14E TO EXST DUCT
FTU-5
Q'D CE TYP
16E FTU-3
12R
T
8x8 FM
RG-3 150CFM SECURE STORAGE SR-1 8x6 150CFM 10E
BAY 4
1E
SD-1, 6x6 100CFM CONNECT TO EXST DUCT
12S
8S OFFICE
8S
9E
AQ
SD-1, 8X8 300CFM, TYP2
6S
14X12S
NT NG
2E
PARALLELOGRAM LIFT 6E 8S
RG-2 10X6 175CFM ELECTRICAL TYP 3 ROOM RG-1 200CFM
VP-1
AQ
AQ
DRYER VENT CAP
RG-2, 12X12 300CFM/500CFM 12X12E UP TO EF-5 ON MEZZANINE COMP GAS
AQ
MAINTENANCE BAYS
T
12X10S
K
BAY 1
4"Ø DRYER VENT
RG-2, 6X6 50CFM
12S
HC-1 SD-2, 8X8 300CFM
EF-5 SPEED CONTROLLER, SEE NOTE 3
AQ
SD-1 8x8 H-2MACHINE200CFM SHOP 1 MAINTAIN REQ'D WORKING SPACE TYP 10R
SD-2, 6X6 100CFM, TYP2
10E UP
3
6" DIA. EXH UP THROUGH ROOF
AQ
14X12S
ADD. ALTERNATE #1
1
2
ONE INCH AT FULL SIZE
IF NOT ONE INCH, SCALE ACCORDINGLY
www.tetratech.com 230 South Franklin, Suite 212 Juneau, Alaska 99801 Phone: 907-586-6400 Fax: 907-463-3677
CONSOLIDATED PUBLIC WORKS FACILITY STREETS WING ADDITION, E10-273
MECHANICAL FIRST FLOOR HVAC PLAN
M1.02 33 - 72
L
N
M
O
Q
P
5E SG-1 687 CFM TYP 8
RG-4 1375 CFM TYP 4
4E
22S
28E
22S
OPEN TO BELOW
3E
12S DN
10E DN
36x20IA BELOW
2E
22S 72x48 INTAKE LOUVER
J
H
203D
203C
203B
K
AHU-3
72x48x18 PLENUM
49x15E EF-5 BELOW AHU-3 EXH DUCT
203A
12x12E DN
26x26S RISER 36x26S BELOW
WH-2
B-2
1E
T-3 P-4
1 60x48 EXHAUST LOUVER 24x24 EXHAUST LOUVER
2
MECH ROOM 202
3 2ND FLOOR HVAC PLAN
1
4 201B
ONE INCH AT FULL SIZE
IF NOT ONE INCH, SCALE ACCORDINGLY
www.tetratech.com 230 South Franklin, Suite 212 Juneau, Alaska 99801 Phone: 907-586-6400 Fax: 907-463-3677
CONSOLIDATED PUBLIC WORKS FACILITY STREETS WING ADDITION, E10-273
MECHANICAL SECOND FLOOR HVAC PLAN
M1.03 34 - 72
SA
EA
OA
EA/RA
DM
EXHAUST AIR BYPASS DAMPER HEAT RECOVERY WHEEL
PLAN VIEW - LOWER LEVEL
VFD
7
6
3
3
EXHAUST/RETURN AIR TEMP
PLAN VIEW - UPPER LEVEL
1
DP
T
SD
9 EA
EA/RA EF
1 2 EA
EA/RA
RECIRCULATION BYPASS DAMPER
DM OUTSIDE AIR TEMP
3
P H
SF
4
6
T
H
OA
5
DISCHARGE AIR TEMP
DM
SA
C VFD
DP
DM
7 FILTER DIFFERENTIAL PRESSURE SWITCH, TYPICAL
8 OA
SA
9
SUPPLY AIR BYPASS DAMPER DM
AHU-3 CONTROL SCHEMATIC
AHU-3
2
NTS
DETAIL 9
3
4
6
8
-
1
NTS
5
2
M1.03
ELEVATION VIEW RETURN AIR FROM CEILING PLENUM H
C
H
TO ROOM DIFFUSERS
C PRIMARY AIR
H C
TO ROOM DIFFUSERS
HEATING COIL FTU
HEATING COIL
TERMINAL UNIT CONTROL BOX
THERMOSTAT
NOTES: 1. CONTINUOUS OPERATION
SPEED CONTROLLER IN ROOM LOW (300CFM)/HIGH(500CFM)
EF-3 CONTROL SCHEMATIC NTS
EF-5 CONTROL 3 M1.02
SCHEMATIC NTS
LOCAL VARIABLE SPEED CONTROL
EF-6 CONTROL 4 M1.03
SCHEMATIC NTS
ROOM SENSOR
NOTES: 1. INTERLOCK WITH FTU AS SECOND STAGE OF HEATING
DUCT HEATER CONTROL 5 M1.02
SCHEMATIC NTS
ROOM SENSOR
ELECTRIC BASEBOARD CONTROL 6 M1.02
SCHEMATIC NTS
7 M1.02
FAN TERMINAL UNIT CONTROL SCHEMATIC NTS
8
ONE INCH AT FULL SIZE
M1.02 IF NOT ONE INCH, SCALE ACCORDINGLY
www.tetratech.com 230 South Franklin, Suite 212 Juneau, Alaska 99801 Phone: 907-586-6400 Fax: 907-463-3677
CONSOLIDATED PUBLIC WORKS FACILITY STREETS WING ADDITION, E10-273
MECHANICAL HVAC DETAILS AND SCHEMATICS
M5.01 35 - 72
DRY WALL VERTICAL SUPPLY DUCT
BRANCH CONNECTION FOR ROUND MAIN CONNECTION USE CONICAL TEE FOR RECTANGULAR MAIN CONNECTION USE SPIN IN
FSD
SHEET METAL SCREW, 10"OC (TYP)
FRAMING, STEEL STUD RUNNER 22 GA SHEET CLOSURE COLLAR
DRY WALL SHEET METAL SCREW, 10"OC (TYP)
FRAMING, STEEL STUD RUNNER
MAIN DUCT
SUPPLY AIRFLOW
WALL OPENING REGISTER OR GRILLE AS SHOWN ON DRAWING
CONCRETE WALL VD
VD
L 2"x4"x1/8" CLOSURE COLLAR
NOTE: 1. CLOSURE COLLAR SHALL BE OF SAME MATERIAL AS DUCT.
PACK OPENING AROUND W/ FIBERGLASS 1/2"MAX CLEARANCE
45° CLINCH COLLAR PER
VERTICAL RETURN DUCT
DETAIL
SEAL ALL AROUND ROUND SHEET METAL DUCT, SIZE SHOWN ON PLAN DRAWINGS
3/8"x4" SST CONCRETE ANCHOR 6"OC MAX
L 2"x4"x1/8" CLOSURE COLLAR
TYP FTU SUPPLY DUCT TAKE OFF
NEOPRENE GASKET ALL AROUND (AIR TIGHT)
WALL PENETRATION
8° VD
ADJUSTABLE ELBOW RINGS
DUCTWORK
AD
TRANSITIONS
1" MIN. ON TOP AND BOTTOM
DETAIL
NTS
4
NTS
2 TYP
TYP
NOTES: 1. SIMILAR INSTALLATION FOR: BACK TO BACK GRILLE, DUCTWORK ATTACHED TO WALL OPENING, AND SINGLE WALL OPENING.
OFF SETS
2. PROVIDE FIRE DAMPERS AND VOLUME DAMPERS WHERE SHOWN ON FLOOR PLANS.
VD
24 GAUGE SHEETMETAL DIFFUSER CAN WITH 1" SOUND LINING FLEX DUCT 7' MAX LENGTH
HANGER
TAP IN
3. CLOSURE COLLAR SHALL BE OF SAME MATERIAL AS DUCT. SUPPLY RETURN
WALL MOUNTED GRILLE AND REGISTER 3
DETAIL NTS
TYPICAL SUPPLY OR RETURN DUCT DETAIL NTS
TYP
ADJUSTABLE DAMPER
1 TYP
PERFORATED METAL DIFFUSER PLATE
CEILING DIFFUSER
TYP CEILING MOUNTED SQUARE NECK DIFFUSER
SUPPLY OUTLET GRIDS AND DAMPERS MUST NOT DAMAGE LINERS
DETAIL
8
NTS
HANGER
EQUALIZING GRID
FLEX DUCT 7' MAX LENGTH
TYP
24 GAUGE SHEETMETAL CAN W/ 1" SOUND LINING TAP IN
ADJUSTABLE DAMPER WHERE NOTED
VOLUME DAMPER
NOTES: 1. REFER TO PLAN DRAWINGS FOR MOUNTING ANGLE ON ROUND DUCT.
TYPICAL DUCT MOUNTED DIFFUSERS TRANSFER GRILLE DETAIL NTS
5
DETAIL
6
NTS
TYP
SUPPLY GRILLE (SG-1) DETAIL NTS
7 TYP
TYP CEILING MOUNTED RETURN/EXHAUST GRILLE DETAIL NTS
8
ONE INCH AT FULL SIZE
TYP IF NOT ONE INCH, SCALE ACCORDINGLY
TYP
www.tetratech.com 230 South Franklin, Suite 212 Juneau, Alaska 99801 Phone: 907-586-6400 Fax: 907-463-3677
CONSOLIDATED PUBLIC WORKS FACILITY STREETS WING ADDITION, E10-273
MECHANICAL TYPICAL DETAILS DUCTWORK
M5.02 36 - 72
TABLE A A
B
CONC ANCHOR BOLTS
STEEL I BEAM, MAX FLANGE 15" WIDE x 1.031" THICK
CAPACITY: 3/8" PIPE THROUGH 12" PIPE MAXIMUM ALLOWABLE LOAD 3/8"ROD 1/2"ROD 5/8"ROD 3/4"ROD 7/8"ROD
JAMB NUT
610 LBS 1130 LBS 1810 LBS 2550 LBS 2630 LBS
SUPPORT ROD OR BOLT. SIZE AS REQUIRED
BEAM CLAMP W/ EYE NUT
CAPACITY: 3/8" PIPE THROUGH 12" PIPE
JAMB NUT
MAXIMUM ALLOWABLE LOAD MINIMUM SPACING: A=EDGE DISTANCE B=CENTER TO CENTER 3" 4" 4" 5" 6"
3/8"ROD 1/2"ROD 5/8"ROD 3/4"ROD 7/8"ROD
4" 5" 6" 7" 8"
SEE TABLE A AND TYP SUPPORT ROD FOR PIPES SUBJECT TO HORIZONTAL MOVEMENT DETAIL
3/8"ROD 1/2"ROD 5/8"ROD 3/4"ROD 7/8"ROD
SUPPORT ROD SIZE AS REQUIRED
TYPE B DETAIL 1
DETAIL NTS
NTS
TYP
STL PLATE, SEE TABLE B FOR THICKNESS
STRUCTURAL STEEL
WELDED BEAM ATTACHMENT W/ BOLT AND NUT. WELD TO STRUC STEEL PER MFRS RECOMMENDATIONS
MAXIMUM ALLOWABLE LOAD WELDED EYE ROD SIZE AS REQUIRED
PIPE STANCHION, SIZE AS SPECIFIED IN TABLE B
7. AT LEAST ONE PIPE HANGER OR SUPPORT SHALL BE LOCATED IMMEDIATELY ADJACENT TO THE JOINT OF ANY CONCENTRATED LOAD OR BEND IN THE PIPE SUCH AS VALVES, FITTINGS, ETC., IN ADDITION TO THE MAXIMUM SPANS LISTED ABOVE.
SS ANCHOR BOLT OR CONCRETE ANCHOR WITH FULL THREADED STUDS, TYP., SEE TABLE B
8. TYPICAL DETAILS SHOWN ON THIS DRAWING ARE FOR REFERENCE ONLY. REFER TO SPECIFICATION SECTION 15071 FOR SEISMIC DESIGN REQUIREMENTS. GROUT AFTER LEVELING WITH NON-SHRINK GROUT
FINISH FLOOR
1" T0 4" EMBED DEPTH, SEE TABLE B
LEVELING NUTS NOTE: 1.
TYPE C NTS
2. WHERE MODULARLY SPACED INSERTS ARE REQUIRED SUPPORT PIPES AT INSERT MODULE. NO SPECIAL INSERTS WILL BE ALLOWED FOR INDIVIDUAL PIPE SUPPORTS UNLESS SPECIFICALLY DETAILED OR AUTHORIZED BY THE PROJECT REP.
6. DESIGN WEIGHTS REFER TO THE PIPE SIZE SHOWN SUPPORTED AT THE SPACING LISTED AND SHALL BE USED FOR DESIGN OF ALL SPECIAL HANGER SYSTEMS.
1/4
DETAIL
NOTES: (TABLE A)
5. IN ADDITION TO SUPPORTING DUCTS AND PIPES FOR GRAVITY LOADS, DUCTS AND PIPES SHALL BE SUPPORTED TO RESIST VERTICAL, LATERAL AND LONGITUDINAL SEISMIC FORCES. FORCES ARE TO BE DETERMINED ACCORDING TO 2006 INTERNATIONAL BUILDING CODE. SEISMIC BRACE DESIGN SHALL BE ACCORDING TO THE LATEST "SEISMIC RESTRAINT MANUAL GUIDELINES FOR MECHANICAL SYSTEMS" BY SMACNA. THE DESIGN FOR SEISMIC SUPPORTS SHALL BE STAMPED AND SEALED BY A PROFESSIONAL STRUCTURAL ENGINEER REGISTERED IN THE STATE OF ALASKA.
1" TYP
610 LBS 1120 LBS 1810 LBS 2710 LBS 3770 LBS
275 LBS 275 LBS 300 LBS 300 LBS 325 LBS 375 LBS 575 LBS 600 LBS 750 LBS 950 LBS
4. INSTALL AT LEAST ONE HANGER PER PIPE LENGTH. LOCATE AS NEAR THE JOINT OR FITTING AS POSSIBLE.
D + 6"SQ
3/8"ROD 1/2"ROD 5/8"ROD 3/4"ROD 7/8"ROD
3/8"TO 3/4" 1" 1-1/4" 1-1/2" 2" 2-1/2" 3" 4" 6" 8"
3. SPACING BASED ON SCHEDULE 80 PIPE AT 100°F. SCHEDULE 40 PIPE OR HIGHER TEMPERATURE REQUIRE SHORTER SPANS. SEE MANUFACTURER'S RECOMMENDATIONS.
2
TYP
CAPACITY: 3/8" PIPE THROUGH 12" PIPE
DESIGN WEIGHT
1. ROD SIZE IS BASED ON CARRYING SINGLE PIPE. WHEN MORE THAN ONE PIPE IS TO BE SUPPORTED. RODS SHALL BE SIZED USING DESIGN WEIGHTS TO DETERMINE TOTAL LOAD.
610 LBS 1130 LBS 1810 LBS 2710 LBS 3770 LBS
TYPE A
PIPE SIZE
SUPPORT MAXIMUM SPAN, IN FEET, FOR PIPES ROD SIZE NOT IN RACKS SEE NOTE 2. BASED ON PLASTIC CAST IRON SINGLE ROD STEEL COPPER SEE NOTE SEE NOTE SEE NOTE1 3 4 CONTINUOUS 5 5 3/8" 6 5 7 3/8" 7 5 7 3/8" 8 5 9 3/8" 10 8 6 3/8" PRESSURE 10 9 6 1/2" PIPE 12 FT 7 10 10 1/2" SOIL PIPE 5/8" 10 10 7 10 FT. 10 9 3/4" 10 " 10 9 " 7/8" 10
SPACING SHALL BE AS REQUIRED, BUT SHALL NOT EXCEED SPANS SHOWN IN TABLE A.
TYPICAL STRUCTURAL ATTACHMENT
3 TYP
DETAIL NTS
4 TYP
TABLE B - PIPE STANCHION PIPE SIZE
NOMINAL PIPE STANCHION DIA (SCHEDULE 40)
PLATE THICKNESS
BOLT SIZE
BOLT EMBED
2"
1 1/2"
1/4"
3/8"
5"
2 1/2"
1 1/2"
1/4"
3/8"
5"
3"
2"
3/8"
1/2"
5"
4"
3"
3/8"
1/2"
5"
6"
3"
3/8"
1/2"
5"
8"
4"
3/8"
5/8"
8"
10"
4"
3/8"
5/8"
8"
12"
6"
3/8"
5/8"
8"
14"
6"
1/2"
3/4"
8"
16"
6"
1/2"
3/4"
8"
18"
8"
5/8"
7/8"
8"
20"
8"
5/8"
7/8"
8"
24"
8"
3/4"
1"
8"
ONE INCH AT FULL SIZE
10" IF NOT ONE INCH, SCALE ACCORDINGLY
www.tetratech.com 230 South Franklin, Suite 212 Juneau, Alaska 99801 Phone: 907-586-6400 Fax: 907-463-3677
CONSOLIDATED PUBLIC WORKS FACILITY STREETS WING ADDITION, E10-273
MECHANICAL HVAC DETAILS AND SCHEMATICS
M5.03 37 - 72
SUPPORT ROD SIZE AND SPACING AS SPECIFIED IN TABLE A ON M5.03
SUPPORT ROD SIZE AND SPACING AS SPECIFIED IN TABLE A ON M5.03
NOTE: 1. USE MSS TYPE 4 SINGLE BOLT PIPE CLAMP FOR UNINSULATED PIPE.
SUPPORT ROD SIZE AND SPACING AS SPECIFIED IN TABLE A ON M5.03
SUPPORT ROD SIZE AND SPACING AS SPECIFIED IN TABLE A ON M5.03
JAM NUT JAM NUT
JAM NUT
JAM NUT
ADJUSTABLE STEEL CLEVIS, MSS TYPE 1
ADJUSTABLE STEEL CLEVIS, MSS TYPE 1
NTS
THERMAL SHIELD MSS TYPE 39 SEE NOTE 1
VARIES
TYPE 1
TYPE 1A 1
ADJUSTABLE ROLLER HANGER, MSS TYPE 43
THERMAL SHIELD
DOUBLE-BOLT PIPE CLAMP MSS TYPE 3, SEE NOTE 1
"J" HANGER, MSS TYPE 5
PROTECTIVE INSULATION SHIELD, MSS TYPE 40
DETAIL
JAM NUT
WELDLESS EYE NUT MSS TYPE 17
THERMAL SHIELD
NOTE: 1. WITH COPPER PIPE REPLACE MSS 39 SADDLES WITH CALCIUM SILICATE OR WOOD BLOCKS AND MSS TYPE 40 SHIELDS.
SUPPORT ROD SIZE AND SPACING AS SPECIFIED IN TABLE A ON M5.03
DETAIL
TYP
TYPE 2 2
NTS
DETAIL
TYP
TYPE 3 3
NTS
TYP
TYPE 4
DETAIL
4
NTS
DETAIL
TYP
5
NTS
TYP DESIGN LOADS:
PIPE CLAMP, FRAMING CHANNEL TYPE
DESIGN LOADS:
SUPPORT ROD SIZE AND SPACING AS SPECIFIED IN TABLE A ON M5.03
PIPE STRAP, FRAMING CHANNEL TYPE
SIZE
LOAD (LBS)
3/4"-1 1/2" 2"-3" 4"-5" 6"-12"
190 420 610 870
DOUBLE-BOLT PIPE CLAMP MSS TYPE 3
NOTES: 1.
FRAMING CHANNEL 1-5/8"SQ. X 12 GAGE MIN., GALVANIZE AFTER FABRICATION
DO NOT USE FOR HORIZONTAL PIPES LARGER THAN 2" WHEN FRAMING CHANNEL IS MOUNTED VERTICALLY.
TYPE 5 NTS
3/4" THROUGH 30" PIPE
3/4" THROUGH 12" PIPE FOR VERTICAL PIPE ONLY
TYPE 7
TYPE 8
TYPE 6 6
DETAIL
"Z" SHAPED STEEL STRAP FITTING, TYP 2 SS EXPANSION ANCHORS EACH CLAMP
7
DETAIL
TYP
NTS
8
DETAIL
TYP
NTS
TYP
1/2" THROUGH 30" PIPE
NTS
1 1/2"
FORGED STEEL ELBOW OR PIPE
STEEL CLEVIS MSS TYPE 14 3"
WELDING LUG STEEL PLATE THICKNESS TO MATCH CLEVIS GRIP
PIPE STANCHION, SIZE AS SPECIFIED IN TABLE ON B/M5.03
PLATE TO MATCH BASE ELBOW OR TEE 1/4
4 1/2"
2" THROUGH 12" PIPE 1. 4" THROUGH 8" PIPE
TYPE 10 DETAIL NTS
LUG SHALL BE WELDED TO PIPE BEFORE INTERNAL LINING IS APPLIED.
TYPE 11 11 TYP
2. PIPE HANGERS SHALL BE OVERSIZED AS REQUIRED TO ACCOMMODATE THICKNESS OF INSULATION SPECIFIED. HANGER SHALL NOT COME INTO CONTACT WITH THE INSULATION DIRECTLY, EITHER AT THE VERTICAL YOKE OR AT THE POINT OF SUPPORT. SEE SPECIFICATIONS.
REQUIRED FOR PIPE ATTACHMENTS 1 AND 2 NOTE:
2 1/2" THROUGH 30" PIPE
1. WITH COPPER PIPE PROVIDE A FULL 360° WRAP OF 1/16 INCH THICK NEOPRENE BONDED TO PIPE WITH A COMPATIBLE WATERPROOF ADHESIVE. FOR REQUIREMENTS ON INSULATION USED WITH PIPE HANGERS.
3. REFER TO SPECIFICATION SECTION 15071 FOR SEISMIC DESIGN REQUIREMENTS.
STRUCTURAL ATTACHMENT, 6/M5.03
STRUCTURAL ATTACHMENT, 6/M5.03
TYP
GENERAL NOTES:
2" DRILL 1/8" DIA HOLE BEFORE WELDING
NTS
WELDED LINKED EYE RODS REQUIRED FOR STRUC ATTACHMENTS
TURNBUCKLE
PIPE STANCHION, SIZE AS SPECIFIED IN TABLE B ON M5.03
10
DETAIL
TYP
AS REQUIRED
JAM NUT BASE ELBOW OR BASE TEE
RISER CLAMP, MSS TYPE 8
TYPE 9
SUPPORT ROD SIZE AND SPACING AS SPECIFIED IN TABLE A ON M WELD TO PIPE BEFORE ANY LINING IS APPLIED TO PIPE
390 530 810 1160 1570 2500 2700 2900
FOR VERTICAL PIPE ONLY
9
DETAIL
LOAD (LBS)
4 1/2"
FRAMING CHANNEL 1-5/8"SQ. X 12 GAGE MIN., GALVANIZE AFTER FABRICATION
SIZE 2 1/2" 3" 4" 5" 6" 8"-10" 12"-14" 16"-30"
DETAIL NTS
TYPE 12 12
DETAIL
TYP
NTS
www.tetratech.com 230 South Franklin, Suite 212 Juneau, Alaska 99801 Phone: 907-586-6400 Fax: 907-463-3677
TYP SUPPORT ROD 13 TYP
DETAIL NTS
ONE INCH AT FULL SIZE
14 IF NOT ONE INCH, SCALE ACCORDINGLY
TYP
CONSOLIDATED PUBLIC WORKS FACILITY STREETS WING ADDITION, E10-273
MECHANICAL TYPICAL DETAILS PIPE HANGERS
M5.04 38 - 72
AIR HANDLING UNIT (AHU) SCHEDULE SUPPLY FAN - DRAW THRU
RETURN FAN
ELECTRIC HEATING COIL
HEAT EXCHANGER FILTERS
SYMBOL
AHU-3
LOCATION
WEIGHT (LBS)
SERVICE
STREET WING
VARIABLE VOLUME
4500
AIRFLOW (CFM)
TOTAL STATIC PRESSURE (IN W.C.)
EXTERNAL STATIC PRESSURE (IN W.C.)
2.7
2.1
6000
ELECTRICAL AIRFLOW (CFM) BHP
HP
VOLT-P-HZ
4.9
7.5
460-3-60
TOTAL STATIC PRESSURE (IN W.C.)
EXTERNAL STATIC PRESSURE (IN W.C.)
2.1
1.0
5550
AIR TEMP (°F)
ELECTRICAL
CAPACITY (KW) BHP
HP
VOLT-P-HZ
ENT.
LVG.
3.8
5
460-3-60
28
70
SELECTION BASED ON MANUFACTURER/MODEL (OR APPROVED EQUAL)
MOTOR VOLT-P-HZ
80
460-3-60
TYPE
WHEEL
MIN. SENSIBLE EFF. (%)
63
HP
FLA
VOLT-P-HZ
M E R V
QTY.
SIZE (IN)
PD (IN)
DEPTH (IN)
0.25
0.4
460-3-60
7
4 8
24x20 16x20
0.08
2
YORK SOLUTIONS AIR HANDLING UNIT
NOTES: NOTES: 1.HEAT HEATRECOVERY RECOVERYPERFORMANCE PERFORMANCEIS ISBASED BASEDON ONCOIL COILEAT EAT28°F 28°FWITH WITH29% 29%RH RHON ONBOTH BOTHSA SAAND ANDRA. RA. 1. VFD'SSHALL SHALLBE BEPROVIDED PROVIDEDBY BYDDC DDCCONTRACTOR CONTRACTORAND ANDINSTALLED INSTALLEDINAT FIELD ON AHU CASING. 2.2.VFDs THE FIELD.
FAN POWER TERMINAL UNIT SCHEDULE SIZE
CFM
NC LEVELS
ELECTRIC HEATING COIL
FAN
SYMBOL
FTU-3
ELECTRICAL MFR/MODEL
UNIT
INLET
OUTLET
MAX
MIN
RAD
DISCH
CFM
ESP
HP
KW
EAT/LAT
VOLT
PH
HZ
C
08
14.1x1.1
600
350
19
13
600
0.20
0.33
5.0
55/95
277
1
60
TITUS/DTFS-F
REMARKS
FTU-3 IS AN OWNER FURNISHED CONTRACTOR INSTALLED ITEM
NOTES: 1. ROOM NC LEVEL SHOWN INCLUDES ATTENUATION TRANSFER FUNCTIONS FROM TABLES IN ARI STANDARD 885-89. 2. SOUND DATA SHALL BE OBTAINED FROM TESTS CONDUCTED IN ACCORDANCE WITH ARI STANDARD 880-94.
FAN SCHEDULE
SYMBOL
LOCATION
TYPE
EF-5
STREET WINGS MEZZANINE
EF-6
KITCHEN HOOD FAN
INLINE INLINE
AIRFLOW (CFM)
STATIC PRESSURE (IN W.C.)
300/ 500
0.3
600
0.5
DRIVE
DIRECT DIRECT
FAN RPM
MOTOR
SOUND POWER (dBA)
1521
54
-
-
CONTROL
MFR/MODEL
GREENHECK SQ-90-D
HP
RPM
VOLT-P-HZ
ENCLOSURE
1/10
1550
115-1-60
TEAO
TWO SPEED SWITCH
-
VARIABLE SPEED CONTROL
1/6
-
120-1-60
FABER INCA PRO 30
FEATURES
WEIGHT (LBS)
ADJUSTABLE SPEED FAN
41
REMOTE SWITCH W/ SPEED CONTROL
-
NOTES: 1. KITCHEN HOOD SHALL INCLUDE TRIM WITH BAFFLE TYPE FILTERS AND LIGHTS.
ELECTRIC HEATER SCHEDULE SYMBOL
TYPE
LOCATION
CAPACITY (KW)
LENGTH (IN)
VOLT-P-HZ
SELECTION BASED ON MANUFACTURER/MODEL (OR APPROVED EQUAL)
AMPS
REMARKS
EB-1
BASEBOARD
LUNCH/TRAINING
1.0
48
277-1-60
3.6
MARKEL 3900 HYDRONIC ELECTRIC
REMOTE T'STAT
EB-2
BASEBOARD
LUNCH/TRAINING
1.5
72
277-1-60
5.4
MARKEL 3900 HYDRONIC ELECTRIC
REMOTE T'STAT
HC-1
DUCT HEATER
SIGN SHOP
4
-
277-1-60
8.3
NAILOR DH
SPACE THERMOSTAT
DIFFUSER/GRILLE/REGISTER SCHEDULE
SYMBOL
TYPE
SELECTION BASED ON MANUFACTURER/MODEL (OR APPROVED EQUAL)
MAX NC
MAX APD (IN WC)
REMARKS
SD-1
CEILING MOUNT
TITUS MCD
30
0.1
-
SD-2
DUCT MOUNT
TITUS MCD
30
0.1
-
SG-1
DUCT MOUNT
TITUS 272RL
30
0.1
WITH OPPOSED BLADE DAMPER
RG-1
CEILING MOUNT
TITUS 350ZRL
30
0.1
-
RG-2
DUCT MOUNT
TITUS 350ZRL
30
0.1
-
RG-4
DUCT MOUNT
TITUS 350ZRL
30
0.1
-
NOTES: 1. CEILING MOUNT TYPE SHALL BE MOUNTED ACCORDINGLY FOR 24" x 24" CEILING MODULE OR GYPBOARD CEILING PER REFLECTED CEILING PLAN. INCLUDE ANY ADDITIONAL APPURTENANCES AS NEEDED.
ONE INCH AT FULL SIZE
IF NOT ONE INCH, SCALE ACCORDINGLY
www.tetratech.com 230 South Franklin, Suite 212 Juneau, Alaska 99801 Phone: 907-586-6400 Fax: 907-463-3677
CONSOLIDATED PUBLIC WORKS FACILITY STREETS WING ADDITION, E10-273
MECHANICAL HVAC EQUIPMENT SCHEDULES
M6.01 39 -- 72
L
M
O
N
Q
P
NOTES:
5E
1.
FIELD VERIFY EXACT SIZE AND LOCATION OF STUB OUT.
2.
RADIANT FLOOR HEATING SYSTEM UNDER SLAB IS NOT SHOWN. DESIGN SHALL BE PROVIDED BY CONTRACTOR IN COMPLIANCE WITH SECTION 15772.
3.
PROVIDE TRAP PRIMERS FOR ALL FLOOR DRAINS.
4.
PROVIDE ACCESS PANELS FOR ALL IN WALL TRAP PRIMERS.
FCO, TYP 3"W
FCO, TYP UP TO FD-1, TYP 5
4E 6"RD, SEE CIVIL FOR CONNECTION, TYP 4
6"W 3"W
3E FD, UP TO EYEWASH TD-1, TYP 3
3"W 4"W, TYP OIL WATER SEPARATOR SEE 4/P5.01
2E
3"V
FCO 3"W
3"V
FCO
4"W FD-1
4"W FD-1
4"W
2"W
FCO
OFFICE
BAY64CONDUITS FOR FUTURE LIFT INSTALLATION, SEE NOTE 2
FD-1
FD-1
FD-2 WITHOUT TRAP AND VENT
LOCKER ROOM
DN
2
4"W MEN'S RESTROOM 2"W
OFFICE
DN
S-2
2"W JAN
N OFFICE
3"W
3
3"W
FOUNDATION PIPING PLAN
CORRIDOR 6"W
MAINTENANCE BAYS
FD-2
FD-2
2"V
6"W
BAY 6
BAY 1
2"V
UP
BAY 2
PARTS INVENTORY
WOMEN'S LOCKER
FILES/ XEROX 4"W
MACHINEFD-1
1
4 OFFICE
8'
0
8'
16' ONE INCH AT FULL SIZE
SCALE: 1/8"=1'-0"
WC0
"W
3"W
BAY 3
3"W
6"W
BAY 5 FD-2 WITHOUT TRAP AND VENT
FD-2 2"W
WC0
SECURE WC0 STORAGE
MACHINE SHOP 1
1 FCO
2"W
FD-1
FD-1
1E
3"W STUB OUT FOR FUTURE CONNECTION (IE=36" BFF)
TD-2
ELECTRICAL ROOM
4"W
3"W
CORRIDOR
4"W
4"W
FCO
3/4"CA 3/8"CA
COMP GAS
TD-1 4"W
SL SL
CONNECT 6"W TO EXST 6"W STUB OUT, SEE NOTE 1
3"W
6"W
TD-1
TD-1
TD-1
K
6"W
3"RD, SEE CIVIL FOR CONNECTION, TYP 6
J
TRENCH FOR CA PIPING AND ELECTRICAL CONDUIT SEE 12/S5.01 FOR DETAIL AND NOTE 3
4"W
H
www.tetratech.com 230 South Franklin, Suite 212 Juneau, Alaska 99801 Phone: 907-586-6400 Fax: 907-463-3677
IF NOT ONE INCH, SCALE ACCORDINGLY
CONSOLIDATED PUBLIC WORKS FACILITY STREETS WING ADDITION, E10-273
MECHANICAL FOUNDATION PIPING PLAN
P1.01 40 - 72
L
M
O
N
Q
P
NOTES: 1.
5E
HB-1
RADIANT FLOOR HEATING SYSTEM UNDER SLAB DESIGN (NOT SHOWN) SHALL BE PROVIDED BY CONTRACTOR IN COMPLIANCE WITH SECTION 15772.
HB-2, TYP 3 FD-1, TYP 5
RADIANT FLOOR HEATING SYSTEM ZONE 2 SEE NOTE 1
RADIANT FLOOR HEATING SYSTEM ZONE 1 SEE NOTE 1
6"RD, TYP 4
4E 6"RD, TERMINATE TO DAYLIGHT, SEE CIVIL DWGS
ZONE 2 RADIANT HEATING SYSTEM MANIFOLD P-6 1/2"CA UP AT COMPRESSED AIR STATION, TYP 8
3E
3/4"IW UP, TYP 3
ZONE 1 RADIANT HEATING SYSTEM MANIFOLD 3"V UP 2"IW, 1"CA, 1"HP UP
P-5
J
3"RD, TYP 6
S-2
1/2"IW TO BOOT WASH BW-1
COMP GAS
3/4"IW DN TO HB-2, TYP
3/4" HW 3/4" CW 3"V
2"IW 1"CA 1"HP 3/4"CA
K
1/2" CW 1/2" HW
2E
WASHER SERVICE BOX
H
EW-1
FD-2
6"RD, TERMINATE TO DAYLIGHT, SEE CIVIL DWGS 3"V
3"W FROM FD-2 ABOVE
1E 2"V 3"VTR
2"V 3"V 3/4" CW 3/4" HW
2"IW 3/4"HW 3/4"CW
ELECTRICAL ROOM
6"E UP THROUGH ROOF
BAY 3 3/4"CW
BAY 1 EMERGENCY EYEWASH-2
welding MACHINE table SCF-1 SHOP 1
3/4"HW MEN'S RESTROOM
OFFICE
3/4"IW DN TO HB-1
2"CW
3/4"HW 3/4"CW
OFFICE
JAN
3 2"V RISER
BAY 6
2
1"CW
3"VENT RISER
MAINTENANCE BAYS
EMERGENCY BAY 4 EYEWASH-1
3/4"CW, HW UP TO MEZZANINE
UP
BAY 2 3/4"CA ALONG TOP OF 7' WALL
MACHINE 1"CA SHOP 2
2"IW 1-1/2"HP 1-1/2"CA UP TO UPPER LEVEL PARTS INVENTORY
CORRIDOR WOMEN'S LOCKER 1"HW 2"CW
3"VENT RISER 3/4"CA DN TO
FILES/ XEROX
CORRIDOR
BAY 5
OFFICE
SECURE STORAGE 1-1/2"CW
1
S-1
LOCKER ROOM
1-1/2"CW
WELDING EXHAUST SYSTEM 3/4"CA UP
POINT OF CONNECTIONS AT POINT OF CAPPED CONNECTION LOCATION
N
4 OFFICE
FIRST FLOOR PIPING PLAN
ONE INCH AT FULL SIZE
8'
WH-1
1
1-1/2"HP 1-1/2"CA
www.tetratech.com 230 South Franklin, Suite 212 Juneau, Alaska 99801 Phone: 907-586-6400 Fax: 907-463-3677
SEE
OFFICE
0
8'
16'
SCALE: 1/8"=1'-0"
CONSOLIDATED PUBLIC WORKS FACILITY STREETS WING ADDITION, E10-273
MECHANICAL FIRST FLOOR PIPING PLAN
IF NOT ONE INCH, SCALE ACCORDINGLY
P1.02 41 - 72
L
M
N
O
Q
P
NOTES: 1.
5E
SLOPE HP AND CA PIPING DOWN TOWARD DRAIN LEG AND PROVIDE DRAIN VALVE AT 3' AFF.
3/4"IW
PROVIDE DRAIN VALVE AT BOTTOM OF RISER, SEE NOTE 1 1/2"CA DN, TYP 8 3/4"CA
3/4"CA
4E
3"RD, TYP 4 1/2"HP DN, TYP 3
OPEN TO BELOW 3/4"HP
DN TO ZONE 2 RADIANT HEATING SYSTEM MANIFOLD
PROVIDE DRAIN VALVE AT BOTTOM OF RISER, SEE NOTE 1
3E 3/4"IW DN, TYP 4 3/4"HP 1"CA 3"VTR
1"HWS 1"HWR
DN TO ZONE 1 RADIANT HEATING SYSTEM MANIFOLD
1"IW
1"CA 3/4"HP
2E
J
H
1"HP PROVIDE DRAIN VALVES AT BOTTOM OF DRAIN LEG, SEE NOTE 1
K
1-1/4"HWS 1-1/4"HWR 1-1/2"HWS 1-1/2"HWR 3"VTR FD-2
3/4"IW DN TO HB-2, TYP
WH-2
3/4"CA DN TO CA STATION, TYP
3"RD, TYP
B-2
T-3
P-4 1/2" MAKE UP WATER TO B-2
1E 1
3/4"CW, HW DN 3"VTR VEHICLE EXHAUST HOSE REEL MOUNTED ON SWING ARM, TYP 2
FOLLOW ROOF SLOPE FOR MAXIMUM CLEARANCE, TYP
MECH ROOM
3/4"CA 1"HP 3/4"IW 3/4"CA
3/4"CA 3/4"IW
FLUID HOSE REELS CA, HF, E01, EO2, ATF, GR, TYP. SEE P5.04 FOR PIPING DETAILS
BRIDGE CRANE TRACKS 2"VTR 3/4"CA
3/4"CA 3/4"IW
2
3"VTR
2"IW 1-1/2"HP 1-1/2"CA UP FROM 1st FLOOR
BALL VALVE, TYP
3 2"IW 1-1/2"HP 1-1/2"CA
SECOND FLOOR PIPING PLAN
1
1"CA 1"HP 1"CA 1"HF 1"EO1 1"EO2 1"ATF 1"GR
3/4"IW 1"CA 1"HF 1"EO1 1"EO2 1"ATF 1"GR
2'IW 1-1/2"HP 1-1/2"CA 1-1/2"HF 1-1/2"EO1
4
ONE INCH AT FULL SIZE
3"VTR
1-1/2"EO2 1-1/2"ATF
IF NOT ONE INCH, SCALE ACCORDINGLY
www.tetratech.com 230 South Franklin, Suite 212 Juneau, Alaska 99801 Phone: 907-586-6400 Fax: 907-463-3677
CONSOLIDATED PUBLIC WORKS FACILITY STREETS WING ADDITION, E10-273
MECHANICAL SECOND FLOOR PIPING PLAN
P1.03 42 - 72
L
M
N
O
P
Q
5E
4E OVERFLOW TYP 4
3"Ø RD TYP 4
3E
2E 3"VTR
J
H
K 1E 3"VTR
SLOPE
SLOPE
1
2 SLOPE
SLOPE
SLOPE
3 ROOF PIPING PLAN
1
4
OPE
OPE
OPE
ONE INCH AT FULL SIZE
SLOPE
www.tetratech.com 230 South Franklin, Suite 212 Juneau, Alaska 99801 Phone: 907-586-6400 Fax: 907-463-3677
SLOPE
IF NOT ONE INCH, SCALE ACCORDINGLY
CONSOLIDATED PUBLIC WORKS FACILITY STREETS WING ADDITION, E10-273
MECHANICAL ROOF PIPING PLAN
P1.04 43 - 72
1" POC TO EXISTING 2" IW
POC TO EXISTING 1" CW
WATER PIPING SCHEMATIC NTS 3"
2 -
2"
2"
1-1/2" 1-1/2"
1-1/2"
3"
3"
3"
3" 3"
4"
3"
4"
3"
4"
6"
CONNECTION TO EXST 6"W
SANITARY PIPING SCHEMATIC NTS
1 -
ONE INCH AT FULL SIZE
IF NOT ONE INCH, SCALE ACCORDINGLY
www.tetratech.com 230 South Franklin, Suite 212 Juneau, Alaska 99801 Phone: 907-586-6400 Fax: 907-463-3677
CONSOLIDATED PUBLIC WORKS FACILITY STREETS WING ADDITION, E10-273
MECHANICAL PIPING SCHEMATICS
P2.01 44 - 72
AIR SEPARATOR
1/2" MAKEUP WATER
MEZZANINE
MAINTENANCE AREA
NOTES: 1. SEE PLAN DWGS FOR VENT PIPING CONNECTION AND ROUTING.
RPBP
AAV
TO FD 1-1/2"HWR
TO FD
1-1/4"HWR
1"HWR
1-1/4"HWS
1"HWS
2. PROVIDE AIR TIGHT COVERS AND REQUIRED HARDWARE FOR INDOOR INSTALLATION. 3. TOP AND ACCESS PANEL SHALL HAVE H20 VECHICLE LOADING CAPABILITY.
1-1/2"HWS TO FD
NORTH ZONE MANIFOLD
CHEMICAL FEEDER
AAV
SOUTH ZONE MANIFOLD
P-5
P-6 6'-0"
M
B-2
TO FD
HOUSEKEEPING PAD
P-4
M
4" OPENING FOR VENT CONNECTION
NC
T-3
CLEAR ACCESS OPENINGS
A
TO FD
RADIANT HEATING WATER PIPING SCHEMATIC
4'-0"
TO FD
SLAB TEMPERATURE SENSOR IN NORTH ZONE SLAB TEMPERATURE SENSOR IN SOUTH ZONE
1 -
NTS
AIR TIGHT ACCESS COVER, TYP
SLOT FOR BAFFLE AND WEIR PLATES, TYP
OIL WATER SEPARATOR DETAIL
4 -
NTS
1/2" 1/2"CA
T-4
1-1/2" DIA LIFT HOLE, 1 EACH SIDE, BOTH SIDES. CONTRACTOR TO PLUG AFTER INSTALLATION
FRL
1'-0"
WH-2
SEISMIC STRAP
3" VENT PIPE, SEE NOTE 1
1'-0"
3/4"HW
CAP 1'-6"
3/4"CW
CAP
POTABLE WATER HEATER PIPING DETAIL NTS
GRIT/SLUDGE RETAINER WEIR
9"
3/8" QUICK DISCONNECT
1'-4"
TO FD
11"
FLOW DIFFUSER BAFFLE
DRAIN PAN
CA STATIONS 3 -
DETAIL
3
NTS
1'-4"
1'-0"
1'-9"
450 Gallons @ 3'6" Water Depth
6" OUTLET PIPING
1'-11"
5-1/2"
OIL RETAINER BAFFLE
1/2" QUICK DISCONNECT
1'-0"
6" INLET PIPING
TYP
OIL WATER SEPARATOR SECTION NTS
A ONE INCH AT FULL SIZE
IF NOT ONE INCH, SCALE ACCORDINGLY
www.tetratech.com 230 South Franklin, Suite 212 Juneau, Alaska 99801 Phone: 907-586-6400 Fax: 907-463-3677
CONSOLIDATED PUBLIC WORKS FACILITY STREETS WING ADDITION, E10-273
MECHANICAL PIPING DETAILS
P5.01 45 - 72
FORM 2' DIA DISH
HEAVY DUTY FLOOR DRAIN
1'-0"
SANITARY TEE OR COMBINATION WYE 1/8 BEND FOR VENT LINE WHERE SPECIFIED
3" CLEAR
4"
1" MIN
FINISHED FLOOR
2-#3 EW CAST IRON FRAME AND COVER
90° ELBOW
HEAVY DUTY FLOOR DRAIN (FD-1) DETAIL
PROVIDE SMOOTH TRANSITION TO ADJACENT PAVEMENT
2'-0" SQ CLASS E CONCRETE
FLOOR DRAIN
P-TRAP
YARD CLEANOUT
FLOOR DRAIN (FD-2) DETAIL
DETAIL
2
NTS
PACK ANNULAR SPACE WITH JUTE
NTS
TYP
3 TYP
1
NTS
TYP FINISHED WALL SURFACE
FLOOR LEVEL CLEANOUT W/ROUND ACCESS COVER
FLOOR THREADED CLEANOUT PLUG WITH ACCESS COVER
FLOOR CLEANOUT DETAIL NTS
4 TYP
WALL CLEANOUT DETAIL NTS
5 TYP
ONE INCH AT FULL SIZE
IF NOT ONE INCH, SCALE ACCORDINGLY
www.tetratech.com 230 South Franklin, Suite 212 Juneau, Alaska 99801 Phone: 907-586-6400 Fax: 907-463-3677
CONSOLIDATED PUBLIC WORKS FACILITY STREETS WING ADDITION, E10-273
MECHANICAL PIPING DETAILS
P5.02 46 - 72
PLUMBING FIXTURE SCHEDULE CONNECTION SIZES FIXTURE NO.
DESCRIPTION
MODEL
FLUSH VALVE
TRIM CW
REMARKS
HW
TRAP & DRAIN
VENT
S-1
KITCHEN SINK
KOHLER K-3346-3
-
KOHLER 15171-FL
3/8"
3/8"
1-1/2"
1-1/2"
S-2
SERVICE SINK
KOHLER K-6714
-
K-8905
1/2"
1/2"
3"
3"
PROVIDE 3-INCH IRON PIPE TRAP FOR SERVICE SINK
-
HB-1
HOSE BIBB
ZURN Z1300
-
-
3/4"
-
-
-
NON-FREEZE IN-WALL HYDRANT
HB-2
HOSE BIBB
ZURN 195 SERIES
-
-
3/4"
-
-
-
16"X16" HEAVY DUTY DRAIN WITH SLOTTED GRATE
FD-1
FLOOR DRAIN
JOSAM 37840
-
-
-
-
4"
-
FD-2
FLOOR DRAIN
ZURN ZS400B
-
-
-
-
3"
1-1/2"
ROUND WITH SLOTTED OPENINGS
TD-1
TRENCH DRAIN
ZURN Z886
-
-
-
-
4"
1-1/2"
-
TD-2
TRENCH DRAIN
ZURN Z886
-
K-973 SHOWER HEAD
1/2"
-
3"
1-1/2"
BOOT WASH WITH 6' HAND HELD SHOWER HEAD
EW-1
EYE WASH
GUARDIAN G1814
-
-
1/2"
1/2"
-
-
PROVIDE GUARDIAN G3600 THERMOSTATIC MIXING VALVE
BW-1
BOOT WASH
SYMMONS 1-25-FSB
-
-
1/2"
1/2"
-
-
-
ELECTRIC POTABLE WATER HEATER SCHEDULE SYMBOL
LOCATION
INPUT CAPACIT Y (KW)
WH-2
STREET WING MEZZANINE
1.5
STORAGE (GAL)
RECOVERY RATE (GPH)/ TEMP. RISE (°F)
TEMPERATURE RISE (°F)
VOLT-P-HZ
FLA
SELECTION BASED ON MANUFACTURER/MODEL (OR APPROVED EQUAL)
SHIPPING WEIGHT (LBS)
30
21/90
90
120-1-60
-
BRADFORD WHITE M-2-30R6DS
85
ELECTRIC BOILER SCHEDULE
SYMBOL
LOCATION
INPUT CAPACITY (KW)
OUTLET WATER TEMP (°F)
B-2
STREET WING MEZZANINE
54
140
ELEMENTS
QTY
KW
STEPS@KW
3
18
1@18, 1@36
VOLT-P-HZ
SELECTION BASED ON MANUFACTURER/MODEL (OR APPROVED EQUAL)
SHIPPING WEIGHT (LBS)
480-3-60
LOCHINVAR BW 1-054C
600
PUMP SCHEDULE
SYMBOL
LOCATION
TYPE
FLOW (GPM)
SERVICE
MOTOR
TDH (FT H O)
SELECTION BASED ON MFR/MODEL HP
RPM
REMARKS
VOLT-P-HZ
P-4
STREET WING MEZZANINE
INLINE
BOILER
24
15
0.33
1750
115-1-60
P-5
ZONE 1 MANIFOLD
INLINE
RADIANT FLOOR
13
33
0.25
1750
115-1-60
-
P-6
ZONE 2 MANIFOLD
INLINE
RADIANT FLOOR
7
35
0.25
1750
115-1-60
-
BELL & GOSSETT 60 1-1/2x5-1/4
-
RADIANT FLOOR HEATING SCHEDULE SYMBOL
TYPE
ZONE
MIN OUTPUT (BTUH)
NO OF LOOPS
FLOW RATE (GPM)
HEAD LOSS (FT. H20)
SELECTION BASED ON MANUFACTURER/MODEL (OR APPROVED EQUAL)
REMARKS
-
MANIFOLD
1
107000
6
12.9
33.1
HEATLINK
-
-
MANIFOLD
2
55000
3
6.6
35.4
HEATLINK
-
TANK SCHEDULE LENGTH (IN)
TANK VOLUME (GAL)
WEIGHT (LBS)
SELECTION BASED ON MANUFACTURER/MODEL (OR APPROVED EQUAL)
SYMBOL
LOCATION
SERVICE
TYPE
DIAMETER (IN)
T-3
STREET WING MEZZANINE
RADIANT HEATING
EXPANSION TANK
16
34
22
270
BELL AND GOSSETT B-85LA
T-4
STREET WING MEZZANINE
DOMESTIC WATER HEATING
EXPANSION TANK
10
10-3/8
2
21
BELL AND GOSSETT PTA-5 ONE INCH AT FULL SIZE
IF NOT ONE INCH, SCALE ACCORDINGLY
www.tetratech.com 230 South Franklin, Suite 212 Juneau, Alaska 99801 Phone: 907-586-6400 Fax: 907-463-3677
CONSOLIDATED PUBLIC WORKS FACILITY STREETS WING ADDITION, E10-273
MECHANICAL PLUMBING EQUIPMENT SCHEDULES
P6.01 47 - 72
L L
M
O
N
P
M
N
O
Q
P
Q
NOTES: 1.
SPRINKLER SYSTEM SHALL BE DESIGNED BY LICENSED FIRE PROTECTION ENGINEER.
2.
SPRINKLER DESIGN AND INSTALLATION SHALL BE IN ACCORDANCE WITH NFPA 13 AND APPROVED BY CITY/BOROUGH OF JUNEAU FIRE DEPARTMENT.
5E 3E
4E
MEZZANINE AREA
2E MAINTENANCE BAYS
1E 3E TOOL REPAIR
1 MEZZANINE FP PLAN
2 N
8'
8'
0
SECURE STORAGE
16'
SCALE: 1/8"=1'-0"
2E SIGN SHOP J
H
K
SPRINKLER PIPE POINT OF CONNECTION
LUNCH/TRAINING 1E CORRIDOR 1 CAP PIPE FOR FUTURE CONNECTION
2
FIRST FLOOR FP PLAN
1 N
FIRE SPRINKLER ZONE 8'
0
8'
16'
ZONE
CLASSIFICATION
DENSITY
MAINTENANCE BAYS/ SIGN SHOP
ORDINARY HAZARD GROUP 2
0.25 GPM/SF PER FM GLOBAL STANDARDS
LUNCH/TRAINING/ CORRIDOR
LIGHT HAZARD
0.10 GPM/SF OR PER NFPA 13
TOOL REPAIR/ SECURE STORAGE
ORDINARY HAZARD GROUP 2
0.20 GPM/SF OR PER NFPA 13
MEZZANINE
ORDINARY HAZARD GROUP 2
0.20 GPM/SF OR PER NFPA 13
SCALE: 1/8"=1'-0"
ONE INCH AT FULL SIZE
IF NOT ONE INCH, SCALE ACCORDINGLY
www.tetratech.com 230 South Franklin, Suite 212 Juneau, Alaska 99801 Phone: 907-586-6400 Fax: 907-463-3677
CONSOLIDATED PUBLIC WORKS FACILITY STREETS WING ADDITION, E10-273
FP1.01 FIRE PROTECTION PLAN
48 - 72
GENERAL NOTES
ABBREVIATION MAX MC MFR MIN NIC NTS PC PSIG RPM SHT TOB TOS VEL VFD
DESCRIPTION MAXIMUM MECHANICAL CONTRACTOR MANUFACTURER MINIMUM NOT IN CONTRACT NOT TO SCALE PLUMBING CONTRACTOR POUNDS PER SQUARE INCH GUAGE REVOLUTIONS PER MINUTE SHEET TOP OF BEAM TOP OF STEEL VELOCITY VARIABLE FREQUENCY DRIVE
HVAC ABBREVIATIONS
ABBREVIATION A AAP CA CO EOC HE HP IA LA LV MAC
DESCRIPTION MEDICAL COMPRESSED AIR AREA ALARM PANEL COMPRESSED AIR (NON-MEDICAL) MEDICAL CARBON DIOXIDE EMERGENCY OXYGEN CONNECTION MEDICAL HELIUM HORSEPOWER INSTRUMENT AIR LABORATORY AIR LABORATORY VACUUM MEDICAL AIR COMPRESSER
PC PRV PSC R RA REFL REFS RF RH RTU SA SD SF SP STM TEMP TR UH VAV VTR WB WC WPD WSHPR WSHPS
PUMPED CONDENSATE PRESSURE REDUCING VALVE PUMPED STEAM CONDENSATE REGISTER RETURN AIR REFRIGERANT DX LIQUID REFRIGERANT DX SUCTION GAS RETURN FAN RELATIVE HUMIDITY ROOF TOP UNIT SUPPLY AIR SMOKE DAMPER SUPPLY FAN STATIC PRESSURE STEAM TEMPERATURE TRANSFER UNIT HEATER VARIABLE AIR VOLUME BOX VENT THROUGH ROOF WET BULB TEMPERATURE WATER COLUMN WATER PRESSURE DROP WATER SOURCE HEAT PUMP RETURN WATER SOURCE HEAT PUMP SUPPLY
PLUMBING ABBREVIATIONS DESCRIPTION ACID VENT ACID WASTE BOTTLE/GLASS FILLER BACK FLOW PREVENTOR BATH TUB COMPRESSED AIR (NON-MEDICAL) CONDENSATE DRAIN CLEANOUT CONDENSATE PUMP CLINICAL SINK COLD WATER DRINKING FOUNTAIN DOUBLE GRADE CLEANOUT DEIONIZED WATER DEIONIZED WATER CIRCULATING DEIONIZED HOT WATER DEIONIZED HOT WATER CIRCULATING DISTILLED WATER DISTILLED WATER CIRCULATING DIALYSIS WATER RETURN DIALYSIS WATER SUPPLY DRAIN TILE EMERGENCY EYE WASH EMERGENCY SHOWER EMERGENCY SHOWER AND EYE WASH COMBO EXPANSION TANK ELECTRIC WATER COOLER ENTERING WATER TEMPERATURE FILTER FLOOR CLEANOUT FLOOR DRAIN FLOOR SINK NATURAL GAS GRADE CLEANOUT HOSE BIB HUB DRAIN HORSEPOWER
ABBREVIATION HW HWC L LPG LWT MBH MS NC NO NON-POT PIV PRV RD RO RPZ S SAN SCW SHW SHWC SE SH SO SP SS ST TEMP UR V VTR WB WC WCO WH WS WPD YCO
DESCRIPTION HOT WATER HOT WATER CIRCULATION LAVATORY PROPANE LEAVING WATER TEMPERATURE BTU (1000'S) MOP SINK NORMALLY CLOSED NORMALLY OPEN NON-POTABLE WATER POST INDICATOR VALVE PRESSURE REDUCING VALVE ROOF DRAIN REVERSE OSMOSIS WATER REDUCED PRESSURE ZONE (BACK FLOW PREVENTOR) SINK SANITARY SEWER DOMESTIC SOFT COLD WATER DOMESTIC SOFT HOT WATER DOMESTIC SOFT HOT WATER CIRCULATING SEWAGE EJECTOR SHOWER STORM OVERFLOW SUMP PUMP SERVICE SINK STORM SEWER TEMPERATURE URINAL VENT VENT THROUGH ROOF WALL BOX WATER CLOSET WALL CLEANOUT WATER HEATER WATER SOFTENER WATER PRESSURE DROP YARD CLEANOUT
SYMBOL
DESCRIPTION
ADDITIONAL REMARKS
#
SHEET NOTE
DENOTES SPECIFIC REQUIREMENT FOR THE SHEET ON WHICH THE NOTE APPEARS AND IS USED TO DESCRIBE WORK THAT IS TOO LENGHTY TO PLACE ON PLAN.
PIPING - SOLID LINE INDICATES SYSTEM SUPPLY -- DASHED LINE INDICATES SYSTEM RETURN
NUMBER INDICATES NOMINAL DIAMETER IN INCHES, LETTER(S) INDICATES SYSTEM. REFER TO ABBREVIATIONS FOR SYSTEM TYPE.
ABBREVIATION FS PIV SPR
DESCRIPTION FLOW SWITCH POST INDICATOR VALVE SPRINKLER
COORDINATE INTERFACE WITH FIRE ALARM SYSTEM CONTRACTOR
UPRIGHT SPRINKLER PENDANT SPRINKLER CONCEALED SPRINKLER SIDEWALL SPRINKLER
#
#
DUCT, PIPE, OR CEILING MOUNTED CONTROL SENSOR
AUTOMATIC CONTROL VALVE (2-WAY)
F/S
REFER TO SPECIFICATIONS FOR TYPE. REFER TO SEQUENCES AND SCHEMATICS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.
FLOW MEASURING STATION
REFER TO SPECIFICATIONS FOR TYPE BASED ON SIZE AND SYSTEM
FIRE PROTECTION GENERAL NOTES
CHECK VALVE ARROW INDICATES DIRECTION OF NORMAL FLOW
REFER TO SPECIFICATIONS FOR TYPE BASED ON SIZE AND SYSTEM
A.
FIRE PROTECTION WORK SHALL INCLUDE, BUT NOT LIMITED TO, THE FOLLOWING: REMOVAL OF EXISTING STANDARD RESPONSE HEADS AND BRANCH PIPING AND INSTALLATION OF NEW QUICK RESPONSE HEADS AND ASSOCIATED BRANCH PIPING WITHIN ALL RENOVATED SPACES.
PIPE IN SLEEVE
REFER TO SPECIFICATIONS FOR TYPE BASED ON SIZE AND SYSTEM
B.
BALANCING DEVICE # INDICATES FLOW TO BE BALANCED IN GPM
CIRCUIT SETTER, AUTOFLOW, ETC. REFER TO SPECIFICATIONS FOR TYPE BASED ON SIZE AND SYSTEM
ALL AREAS OF THE BUILDING INDICATED SHALL BE SPRINKLERED ACCORDING TO THE CURRENTLY ADOPTED EDITION OF NFPA STANDARD 13 AND OTHER NFPA STANDARDS AS REQUIRED. ENTIRE SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF THE STATE FIRE MARSHAL OFFICE, OWNER'S INSURANCE COMPANY AND AUTHORITIES HAVING JURISDICTION.
C.
FIRE SPRINKLER DESIGN SHALL BE BASED ON HYDRAULIC CALCULATIONS ACCORDING NFPA 13, WITH SHOP DRAWINGS PREPARED ACCORDING TO THE REQUIREMENTS OF THE STATE FIRE MARSHAL AND AUTHORITIES HAVING JURISDICTION.
D.
SPRINKLER CONTRACTOR SHALL OBTAIN STATIC AND RESIDUAL WATER PRESSURE AND FLOW PRIOR TO SYSTEM DESIGN AND SHALL SUBMIT RECENT HYDRANT FLOW TEST DATA WITH SHOP DRAWING SUBMITTALS.
E.
DRAWINGS ARE SCHEMATIC IN NATURE, INTENDED TO CONVEY THE SCOPE OF WORK AND GENERAL ARRANGEMENT OF THE SYSTEM. SPRINKLER SYSTEM INSTALLING CONTRACTOR SHALL COORDINATE SYSTEM ARRANGEMENT WITH ARCHITECTURAL, STRUCTURAL, MECHANICAL AND ELECTRICAL COMPONENTS. SPRINKLER PIPING SHALL NOT BE INSTALLED BELOW MECHANICAL EQUIPMENT OR WITHIN CLEARANCE SPACES FOR MECHANICAL EQUIPMENT. PROVIDE SPRINKLER PROTECTION BELOW ALL DUCTS GREATER THAN 48 INCHES IN WIDTH. INSTALLING CONTRACTOR SHALL BE RESPONSIBLE FOR ANY MODIFICATIONS TO THE SYSTEM REQUIRED TO AVOID CONFLICTS.
INDICATES POINT WHERE PIPING CHAGES FROM ONE SIZE TO ANOTHER. SMALL POINT OF ARROW INDICATES SMALLER SIZE SIDE OF TRANSITION. F.
AREAS IDENTIFIED INDICATE THE RECOMMENDED MINIMUM OCCUPANCY CLASSIFICATION, SPRINKLER TEMPERATURE CHARACTERISTIC OR SPRINKLER TYPES TO BE INSTALLED. SPRINKLER SYSTEM SHALL BE DESIGNED TO MEET OR EXCEED THESE RECOMMENDATIONS AND SHALL BE SUBJECT TO APPROVAL BY THE AUTHORITY HAVING JURISDICTION.
G.
A PRE-DESIGN MEETING SHALL BE COORDINATED WITH THE ARCHITECT PRIOR TO SUBMITTAL OF PIPING LAYOUT DRAWINGS. ARCHITECT SHALL ISSUE COMMENTS CONCERNING SUBMITTAL PACKAGE PRIOR TO COMMENCEMENT OF WORK.
H.
REFER TO ARCHITECTURAL PLANS FOR SPECIFIC CEILING TYPES AND HEIGHTS, AND AREAS OF EXPOSED STRUCTURE.
I.
COORDINATE PIPING AND SPRINKLERS IN EXPOSED AREAS TO MINIMIZE APPEARANCE. INSTALL SPRINKLERS A MINIMUM OF SIX INCHES FROM DIFFUSERS, GRILLES AND LIGHT FIXTURES. INSTALL SPRINKLERS IN LAY-IN CEILINGS WITHIN THREE INCHES OF THE CENTER OF CEILING TILE.
J.
COORDINATE INSTALLATION OF SPRINKLERS AND PIPING SYSTEMS TO AVOID FREEZING CONDITIONS. NOTIFY ARCHITECT OF AREAS FOR WHERE SYSTEM MAY BE EXPOSED TO FREEZING. INSTALL DRY SIDEWALL SPRINKLERS IN ROOMS INDICATED WHERE ROOMS MAY BE UNCONDITIONED OR EXPOSED TO FREEZING CONDITIONS. PROVIDE AUXILIARY DRAINS WHERE REQUIRED.
K.
EXPOSED SPRINKLER PIPING, EXCEPT IN MECHANICAL AND STORAGE ROOMS, SHALL BE CLEANED, PRIMED AND PREPARED FOR PAINTING.
REFER TO SPECIFICATIONS FOR TYPE AND ACCESSORIES
PRESSURE GUAGE
REFER TO SPECIFICATIONS FOR TYPE AND ACCESSORIES
THERMOMETER
REFER TO SPECIFICATIONS FOR TYPE AND ACCESSORIES
FIRST SYMBOL APPLIES TO ROUND DUCT AND PIPING. SECOND SYMBOL APPLIES TO RECTUANGULAR AND OVAL DUCT.
CONTINUATION SYMBOLS
HVAC SYMBOLS DESCRIPTION
ADDITIONAL REMARKS
RECTANGULAR DUCTWORK W = DIMENSION IN VIEW (INCHES) H = DIMENSION PERPENDICULAR TO VIEW (INCHES)
REFER TO DUCT CONSTRUCTION SCHEDULE AND SPECIFICATIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.
ROUND DUCTWORK D = DUCT DIAMETER
REFER TO DUCT CONSTRUCTION SCHEDULE AND SPECIFICATIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.
TURNING VANES
REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.
DUCT CROSS SECTION - SUPPLY
L. M.
WHERE SPRINKLER PIPING SYSTEM PENETRATES FIRE RESISTIVE RATED ASSEMBLIES, SEAL OPENINGS WITH APPROVED CONSTRUCTION METHODS AND MATERIALS. AVOID ROUTING SPRINKLER PIPING ABOVE ELECTRICAL, DATA, IT AND COMMUNICATION PANELS.
THERMOSTAT/ HUMIDISTAT (ADA)
CROSS SECTION INDICATES DUCT EXTENDING PERPENDICULAR TO THE PAGE. IN PLAN VIEW THIS INDICATES A DUCT RISE OR DROP TO ANOTHER LEVEL. SOLID INTERIOR LINE INDICATES EXTENSION UP. DASHED INTERIOR LINE INDICATES EXTENSION DOWN.
DUCT CROSS SECTION - RETURN DUCT CROSS SECTION - EXHAUST MANUAL BALANCE DAMPER
REFER TO SPECIFICATIONS FOR TYPE. LOCATE MANUAL BALANCE DAMPERS IN AN ACCESSIBLE LOCATION AND AS CLOSE TO THE MAIN DUCT AS POSSIBLE.
FIRE DAMPER
REFER TO SPECIFICATIONS FOR TYPE. LOCATE DAMPERS IN AN ACCESSIBLE LOCATION AND PROVIDE ACCESS DOORS/PANELS IN DUCT AND CEILING/WALL.
FIRE/SMOKE DAMPER
REFER TO SPECIFICATIONS FOR TYPE. LOCATE DAMPERS IN AN ACCESSIBLE LOCATION AND PROVIDE ACCESS DOORS/PANELS IN DUCT AND CEILING/WALL.
DIFFUSER BLANK OFF
SHADED AREA INDICATES QUADRANT OF DIFFUSER TO BE PROVIDED WITH BLANK OFF PANEL.
FLOW ARROW
ARROW INDICATES DIRECTION OF AIRFLOW FROM DIFFUSERS WITH ADJUSTABLE THROWS.
DIFFUSER TAG D = TYPE # = TYPE NUMBER ### = AIRFLOW IN CFM
REFER TO DIFFUSER SCHEDULE FOR TYPE DESCRIPTIONS AND SIZING. BALANCE TO AIRFLOW LISTED. WHEN TYPE IS NOT GIVEN AND ONLY CFM IS DESIGNATED, PROVIDE D-1 FOR SUPPLY OR G-1 FOR RETURN/EXHAUST. REFER TO SPECIFICATIONS FOR TYPE. REFER TO DETAILS FOR INSTALLATION REQUIREMENTS. MAXIMUM LENGTH SHALL BE 48 INCHES UNLESS NOTED OTHERWISE ON THE PLANS OR IN THE SPECFICATIONS.
FLEXIBLE DUCT
VB-# #.# GPM
DAMPER SHALL BE SAME SIZE AS DUCT UNLESS NOTED OTHERWISE. REFER TO SEQUENCES, SCHEMATICS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.
ISOLATION VALVE
REQUIRED SERVICE CLEARANCE FOR EQUIPMENT
VB-# ### CFM
REFER TO SPECIFICATIONS FOR TYPE. REFER TO SEQUENCES AND SCHEMATICS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.
WHERE PIPING IS NOT MARKED, REFER TO SPECIFICATIONS FOR REQUIREMENTS
STRAINER WITH BLOW-OFF VALVE
D-# ###
D. REFER TO THE SPECIFICATIONS AND ARCHITECTURAL PLANS FOR PHASING REQUIREMENTS. DURING EACH PHASE THE CONTRACTOR SHALL COMPLETE ALL WORK LOCATED WITHIN THE BOUNDARY OF THAT PHASE. ANY WORK AND THAT MUST BE COMPLETED IN THE AREA AFTER THAT AREA HAS BEEN TURNED OVER TO THE OWNER SHALL BE IDENTIFIED AT THE BEGINNING OF THE PHASE FOR EVALUATION AND ACCEPTANCE OF THE OWNER.
PRESSURE/TEMPERATURE TEST PORT
UNION
FS.D.
REFER TO ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION. WHEN SENSOR IS NOT SHOWN ON ELECTRICAL DRAWINGS IT SHALL BE PROVIDED AND INSTALLED BY THE TEMPERATURE CONTROLS CONTRACTOR. REFER TO SPECIFICATIONS FOR TYPE. REFER TO SEQUENCES AND SCHEMATICS FOR ADDITIONAL INFORMATION AND REQUIREMENTS. T = THERMOSTAT H = HUMIDISTAT S = SENSOR (CARBON DIOXIDE, ETC.)
ARROW INDICATES DOWNWARD PIPE SLOPE #/# INDICATES SLOPE IN INCHES PER FOOT
PIPE REDUCER
FR.D. FR.D.
REFER TO MOUNTING HEIGHTS DETAIL FOR MOUTING ELEVATION. T = THERMOSTAT H = HUMIDISTAT S = SENSOR (CARBON MONOXIDE, ETC.)
M
TEE HORIZONTAL
D"Ø
WALL MOUNTED CONTROL DEVICE # INDICATES TYPE
PROTECT EXISTING SYSTEM FROM ENTRANCE OF FOREIGN DEBRIS DURING WORK.
TEE UP TEE DOWN
W/H
ADDITIONAL REMARKS
AUTOMATIC CONTROL VALVE (3-WAY)
ELBOW UP ELBOW DOWN
SYMBOL
DESCRIPTION
OCCUPANCY SENSOR
#
FLEXIBLE PIPING
REFER TO SPECIFICATIONS FOR TYPE.
VARIABLE AIR VOLUME BOX - NO COIL
REFER TO SCHEDULE, DETAILS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION AND INSTALLATION REQUIREMENTS.
VARIABLE AIR VOLUME BOX - HOT WATER COIL
REFER TO SCHEDULE, DETAILS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION AND INSTALLATION REQUIREMENTS.
VAV BOX TAG # = REFERENCE NUMBER IN SCHEDULE ### = AIRFLOW IN CFM VAV BOX TAG # = REFERENCE NUMBER IN SCHEDULE #.# = WATER FLOW RATE IN GPM
REFER TO DIFFUSER SCHEDULE FOR TYPE DESCRIPTIONS AND SIZING. BALANCE TO AIRFLOW LISTED. WHEN TYPE IS NOT GIVEN AND ONLY CFM IS DESIGNATED, PROVIDE D-1 FOR SUPPLY OR G-1 FOR RETURN/EXHAUST. REFER TO DIFFUSER SCHEDULE FOR TYPE DESCRIPTIONS AND SIZING. BALANCE TO AIRFLOW LISTED. WHEN TYPE IS NOT GIVEN AND ONLY CFM IS DESIGNATED, PROVIDE D-1 FOR SUPPLY OR G-1 FOR RETURN/EXHAUST.
B. CONTRACTOR SHALL VERIFY THE EXISTING CONDITIONS AT THE PROJECT SITE BEFORE SUBMITTING COST PROPOSAL. CONTRACTOR IS ADVISED THAT ALL LOCATIONS ARE APPROXIMATE. AN ATTEMPT HAS BEEN MADE TO SHOW ALL PIPING, FIXTURES, DUCTWORK, AND OUTLETS. THIS CONTRACTOR SHALL VISIT THE SITE TO VERIFY COMPONENTS, LOCATIONS AND SIZES SHOWN OR NOT SHOWN. ALL COMPONENTS NEED TO BE REMOVED IN THE DEMOLITION AREA UNLESS NOTED ON THE DRAWINGS. IF DEVIATION BETWEEN EXISTING CONDITIONS AND NEW WORK IS FOUND, CONTRACTOR SHALL NOTIFY ENGINEER. C. IT IS MANDATORY THAT THE EXISTING BUILDING REMAIN IN CONTINUOUS AND NON-INTERRUPTED OPERATION DURING THE CONSTRUCTION OF THE ADDITIONS AND REMODELING/ALTERATION OF THE EXISTING BUILDING. SERVICES TO THE EXISTING BUILDING SHALL BE KEPT ON CONTINUOUS OPERATION EXCEPT DURING SCHEDULED SHUTDOWNS FOR EXTENSION OR MODIFICATION. ALL SHUTDOWNS SHALL BE PLANNED TO BE COMPLETED DURING OFF HOURS TO MINIMIZE IMPACT TO THE OWNER. ALL SHUTDOWNS SHALL BE COORDINATED WITH THE OWNER A MINIMUM OF 14 DAYS PRIOR TO WORK. THE CONTRACTOR SHALL PROVIDE TEMPORARY SERVICES WHERE NECESSARY TO ACCOMPLISH ANY SHUTDOWN. THIS INCLUDES BUT IS NOT LIMITED TO STAFFING AND EQUIPMENT FOR FIRE WATCHES, PROVISIONS FOR BOTTLED WATER, AND TEMPORARY HEATING OR COOLING EQUIPMENT. TEMPORARY MEASURES SHALL NOT BE REMOVED UNTIL THE PERMANENT SYSTEMS ARE OPERATIONAL AND HAVE PASSED ALL REQUIRED TESTING.
TEMPERATURE CONTROL SYMBOLS
ARROW INDICATES DIRECTION OF FLOW IN PIPING #/#
REFER TO SPECIFICATIONS FOR TYPES AND FINISHES. PENDANT REFERES TO FULL, SEMI-RECESSECT AND RECESSED TYPES. LOCATIONS FOR EACH ARE INDICATED IN THE SPECIFICATIONS OR ON THE PLANS.
MOTORIZED CONTROL DAMPER
DENOTES CONNECTION OF NEW WORK TO EXISTING SYSTEM
MEDICAL GAS OUTLETS
PLUMBING SYMBOLS SYMBOL
C.O. C.O.
DESCRIPTION
ADDITIONAL REMARKS
PIPING - SINGLE DASH INDICATES DOMESTIC COLD WATER - DOUBLE DASH INDICATES DOMESTIC HOT WATER - TRIPLE DASH INDICATES HOT WATER CIRCULATING - SOLID INDICATES SANITARY ABOVE FLOOR - CONTINUOUS DASHED INDICATES VENT - LONG DASHED LINES INDICATE SANITARY BELOW FLOOR
NUMBER INDICATES NOMINAL DIAMETER IN INCHES, LETTER(S) INDICATES SYSTEM. REFER TO ABBREVIATIONS FOR SYSTEM TYPE.
CLEANOUT
CIRCLE INDICATES UP TO FLOOR OR WALL CLEANOUT. LINE INDICATES END OF PIPE CLEANOUT LOCATED ABOVE A CEILING.
AVERA FACILITY DEVELOPMENT
E. CONTRACTOR SHALL BE RESPONSIBLE FOR THEIR OWN DEMOLITION, REMOVAL, CAPPING, STORING, ABANDONING, DISCONNECTING, RELOCATING AND RECONNECTION OF EXISTING EQUIPMENT AND MATERIAL. ALL CUTTING, PATCHING, REPAIRING, REPLACEMENT AND REFINISHING SHALL MATCH THE EXISTING CONSTRUCTION AS NEARLY AS POSSIBLE. F. EXCEPT WHERE OTHERWISE SHOWN OR NOTED ON THE DRAWINGS, "TO BE RETAINED, RELOCATED" OR HEREINAFTER NOTED, ALL EXISTING EQUIPMENT AND MATERIAL IN AREAS TO BE REMODELED/ALTERED SHALL BE REMOVED WHERE THEY INTERFERE WITH PROPOSED NEW CONSTRUCTION AND/OR WITH PROPOSED USAGE OF SPACE BY OWNER AS FOLLOWS: 1. REMOVE ANY PIPING PROTRUDING ABOVE FINISHED FLOOR OR THROUGH WALL AND CAP AT THE NEAREST ACTIVE MAIN WITH MATERIAL TO MATCH EXISTING 2. REMOVE ALL FIXTURES, CARRIERS, SUPPLY AND WASTE AND VENT PIPING, STEAM, HEATING HOT WATER, HVAC SUPPLY, RETURN AND EXHAUST AS NOTED. CAP AT NEAREST ACTIVE MAIN. SUPPLY AND RETURN MAINS ON PIPING SYSTEMS CONVEYING WATER OR GASES SHALL BE VALVED AND CAPPED. 3. IN REMODELED/ALTERED AREAS, ANY PIPING OR DUCTWORK PASSING THROUGH THE REMODELED AREAS TO SERVE (OR BEING SERVED FROM EXISTING ADJACENT, REMOTE, OR SURROUNDING AREAS THAT ARE TO REMAIN) SHALL BE RETAINED AND KEPT OPERATIONAL AND SHALL BE REROUTED IN ALL CASES WHERE THEY INTERFERE WITH ANY NEW WORK OR USAGE TO BE ACCOMPLISHED IN THE REMODELED AREA. 4. REMOVE UNUSED OR ABANDONED HANGERS AND PATCH ABANDONED PENETRATIONS TO MATCH EXISTING. 5. PENETRATIONS THROUGH EXISTING WALLS AND FLOORS FORMERLY OCCUPIED BY REMOVED PIPING OR DUCTWORK SHALL BE PATCHED TO MATCH EXISTING CONSTRUCTION. 6. RE-SUPPORT ANY PIPING AND DUCTWORK WHICH WAS SUPPORTED FROM ELEMENTS OF THE BUILDING WHICH WERE REMOVED AS A PART OF THE WORK REQUIRED UNDER THESE DOCUMENTS. 7. RECONNECT ANY CONTROL WIRING OR PNEUMATIC TUBING THAT WAS CONNECTED TO REMOVED EQUIPMENT AND WHICH IS REQUIRED FOR THE CONTINUED PROPER OPERATION OF THE BUILDING AUTOMATION SYSTEM. G. ALL EXISTING EQUIPMENT BEING REMOVED WILL BE HANDED OVER TO OWNER FOR FIRST RIGHT OF SALVAGE. IF OWNER REFUSES SALVAGE ITEMS, REMOVING CONTRACTOR SHALL BE RESPONSIBLE FOR DISPOSAL. H. CONTRACTOR SHALL REFER TO THE DRAWINGS OF ALL TRADES TO FAMILIARIZE THEMSELVES WITH EXTENT OF WORK INCLUDING BUT NOT LIMITED TO WHERE NEW PARTITIONING IS BEING INSTALLED, WHERE EXISTING PARTITIONING IS BEING REMOVED, WHERE CEILINGS ARE BEING REMOVED AND/OR REPLACED, ETC. I. THESE DRAWINGS ARE NECESSARILY DIAGRAMMATIC IN NATURE. NOT ALL FITTINGS, OFFSETS, VENTS OR DRAINS ARE SHOWN. THE CONTRACTOR SHALL INCLUDE ALL FITTINGS, OFFSETS, VENTS, DRAINS, AND DEVICES REQUIRED TO PROVIDE A COMPLETE AND FUNCTIONING SYSTEM. J. PERFORM AIR AND FLUID BALANCE PRE-TEST ON ALL DISTRIBUTION EQUIPMENT AND ALL AIR OUTLETS IN THE AREA PRIOR TO COMMENCING WORK. SUBMIT PRE-TEST INFORMATION TO OWNER/ENGINEER. K. PROVIDE ACCESS DOORS IN DUCTWORK AND/OR ARCHITECTURAL ELEMENTS WHERE REQUIRED TO ACCESS ALL EQUIPMENT REQUIRING MAINTENANCE AND ADJUSTMENT. THIS EQUIPMENT INCLUDES BUT IS NOT LIMITED TO SENSORS, DAMPERS, ACTUATORS, CONTROL DEVICES, VALVES, ETC. ACCESS DOORS SHALL BE SIZED TO PROVIDE APPROPRIATE ACCESS BASED ON HEIGHT OF ACCESS REQUIRED AND ACTIVITY. INSTALL SUCH THAT ACCESS DOOR IS FULLY OPERABLE WITHOUT THE REMOVAL OF ARCHITECTURAL ELEMENTS SUCH AS CEILING RUNNERS, SUPPORTS, ETC. INSTALL IN A LOCATION SUCH THAT STEPPING OR LEANING OVER PERMANENT EQUIPMENT OR FURNITURE IS NOT REQUIRED. WHERE ACCESS DOORS ARE REQUIRED IN ARCHITECTURAL ELEMENTS THAT PROVIDE A FIRE AND/OR SMOKE RATING, ACCESS DOOR SHALL MAINTAIN THE REQUIRED RATING. L. SEAL ALL WALL PENETRATIONS (DUCTWORK, PIPING, CONTROLS, CONDUITS, ETC.) INTO ROOMS THAT REQUIRE PRESSURE CONTROL OR SOUND ISOLATION. M. PIPING AND DUCTWORK SHALL NOT BE ROUTED OVER ELECTRICAL AND TELECOM ROOMS. WHERE ROUTING OVER SUCH ROOMS IS UNAVOIDABLE, CONTRACTOR SHALL COORDINATE WITH OWNER, DESIGN TEAM, AHJ, AND OTHER TRADES REGARDING LOCATION OF PANELS AND UTILITY ROUTING AND SHALL PROVIDE DRIP PANS UNDER ALL UTILITIES WITH MOISTURE SENSORS OR DRAIN PIPING AS REQUIRED BY THE SPECIFICATIONS.
ED
FESSION PRO AL REG
. NO.
10229 ERIC G. SHERMAN U
T H
K D A
O
11/25/14
No.
Description
Date
N. REMOVAL AND REINSTALLATION OF CEILINGS IN AREAS NOT PART OF THE REMODEL AREA OR NOT INDICATED BY THE ARCHITECTURAL PLANS TO BE REMOVED IS THE RESPONSIBILITY OF THIS CONTRACTOR. CONTRACTOR SHALL REPAIR OR REPLACE ALL DAMAGED CEILING COMPONENTS TO MATCH EXISTING. WHERE AN IDENTICAL MATCH IS NO LONGER AVAILABLE, CONTRACTOR SHALL PROVIDE A SIMILAR REPLACEMENT UPON APPROVAL FROM THE OWNER.
60" 48"
1
O. REGARDLESS OF THE LENGTH SHOWN ON THE DRAWINGS, THE MAXIMUM LENGTH OF 60" SHALL NOT BE EXCEEDED FOR FLEXIBLE DUCTWORK. FLEX DUCT INSTALLATION SHALL BE AT TERMINAL ENDS ONLY. CONNECTIONS AT VAV BOX INLETS SHALL BE SOLID HARD DUCT. THE DUCTWORK AT ANY FIRE AND/OR FIRE SMOKE DAMPER SHALL BE HARD DUCT.
A. COORDINATE ELEVATION OF DEVICES WITH ALL ADJACENT DEVICES INCLUDING THOSE WITH OTHER TRADES. ALL DEVICES WHICH HAVE ADA AND NON-ADA HEIGHTS LISTED SHALL BE MOUNTED TO COMPLY WITH ADA EXCEPT WHERE NOTED ON THE PLANS AS NON-ADA. B. GROUP DEVICES IN AN ORGANIZED AND UNIFORM MANNER.
P. LOCATE PIPING AND DUCTWORK IN EXTERIOR BUILDING WALLS ON THE WARM SIDE IF THE BUILDING AND VAPOR BARRIER. COORDINATE INSTALLATION OF BUILDING INSULATION TO RUN CONTINUOUS BETWEEN PIPING AND BUILDING WALL.
C. REFER TO ARCHITECTURAL ELEVATIONS FOR ADDITIONAL REQUIREMENTS. WHERE THESE REQUIREMENTS DIFFER FROM THE ARCHITECTURAL PLANS, THE ARCHITECTURAL PLANS SHALL TAKE PRECEDENCE. D. REFER TO ARCHITECTURAL ELEVATIONS FOR ALL PLUMBING FIXTURES. E. ALL DEVICES SHALL BE COORDINATED SO AS NOT TO INTERRUPT A BACK SPLASH OR MATERIAL TRANSITIONS. REFER TO ARCHITECTURAL ELEVATION TO CONFIRM DEVICE IS NOT LOCATED WITHIN TRANSITION AREA. F. PROVIDE BACKING IN WALLS WHERE WALL MOUNTED DEVICES OR EQUIPMENT ARE INSTALLED. REFER TO ARCHITECTURAL SPECIFICATIONS.
Q. SUPPORT ALL DUCTWORK, PIPING AND EQUIPMENT FROM BUILDING STRUCTURE MEMBERS. HOLD PIPING TIGHT TO BOTTOM OF STRUCTURAL MEMBERS OR RUN THROUGH JOIST WEBS IF POSSIBLE. DO NOT USE WIRE OR PERFORATED METAL TO SUPPORT PIPING. DO NOT SUPPORT PIPING FROM OTHER PIPING, DUCTWORK AND/OR ELECTRICAL CONDUITS. DO NOT SUPPORT FROM WOOD TONGUE AND GROOVE ROOF DECK. SUPPORT FROM BOTTOM CHORD OF BAR JOISTS ONLY AT PANEL POINTS.
MECHANICAL EQUIPMENT MOUNTING HEIGHTS DETAIL NONE
R. PROVIDE CONSTRUCTION FILTERS ON AHUS SERVING THE CONSTRUCTION AREA AS WELL AS ALL RETURN/EXHAUST DUCT PENETRATIONS COMING FROM THE CONSTRUCTION AREA. AT THE COMPLETION OF WORK, REMOVE ALL TEMPORARY AND CONSTRUCTION FILTERS AND PROVIDE NEW FILTERS FOR ALL AHUS. S. PROTECT ALL DUCTWORK AND PIPING DURING CONSTRUCTION. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION. AT A MINIMUM, DUCTWORK AND PIPING ENDS SHALL BE COVERED AND SEALED TO PREVENT THE COLLECTION OF DUST AND DEBRIS. CLEAN ALL INTERIOR SURFACES PRIOR TO INSTALLATION AND PROTECT ONCE INSTALLED. MEDICAL GAS PIPING SHALL BE PROTECTED IN ACCORDANCE WITH NFPA 99 REQUIREMENTS. T. AT THE COMPLETION OF WORK, CLEAN ALL STRAINERS LOCATED PROVIDED AS A PART OF THE WORK AS WELL AS PRIMARY SYSTEM STRAINERS LOCATED AT PUMPS WHERE SYSTEMS WERE EXTENDED. ON EXISTING EQUIPMENT, COORDINATE WORK WITH OWNER. U. PROVIDE INTERMEDIATE TESTING AND BALANCING AT THE COMPLETION OF EACH PHASE AND AS REQUIRED TO MAINTAIN PROPER OPERATION OF SYSTEMS SERVING OCCUPIED AREAS OF THE FACILITY. V. REFER TO SHEETS M500 THROUGH M502 FOR GENERAL CONSTRUCTION DETAILS. 2014
NOT ALL ABBREVIATIONS APPLY TO THIS SET OF DOCUMENTS.
DESCRIPTION BACK FLOW PREVENTOR FIRE PROTECTION FIRE DEPARTMENT CONNECTION
FLOW SWITCH
DIAMETER
FIRE PROTECTION ABBREVIATIONS ABBREVIATION BFP F FDC
F
GENERAL MECHANICAL SYMBOLS
NOT ALL ABBREVIATIONS APPLY TO THIS SET OF DOCUMENTS.
ABBREVIATION AV AW BF BFP BT CA CD CO CP CS CW DF DGCO DI DIC DIH DIHC DIS DISC DR DS DT EEW ES ESEW ET EWC EWT F FCO FD FS G GCO HB HD HP
ADDITIONAL REMARKS
R GINEE EN
DESCRIPTION HEATING COIL HORSEPOWER HIGH PRESSURE STEAM CONDENSATE HIGH PRESSURE STEAM SUPPLY (86 PSIG AND ABOVE) HEAT RECOVERY CHILLER HUMIDIFIER HYDRONIC HOT WATER RETURN HYDRONIC HOT WATER SUPPLY LOW PRESSURE STEAM CONDENSATE LOW PRESSURE STEAM SUPPLY (0-12 PSIG) LOUVER LEAVING WATER TEMPERATURE BTU (1000'S) MANUAL DAMPER MOTOR OPERATED DAMPER MEDIUM PRESSURE STEAM CONDENSATE MEDIUM PRESSURE STEAM SUPPLY (13-85 PSIG) NORMALLY CLOSED NORMALLY OPEN OUTDOOR AIR PUMP
DESCRIPTION
O
ABBREVIATION HC HP HPC HPS HRC HUM HWR HWS LPC LPS LV LWT MBH MD MOD MPC MPS NC NO OA P
SYMBOL
S
DESCRIPTION AIR BLENDER AIR CONDITIONING UNIT (SPLIT SYSTEM INDOOR UNIT) AIR HANDLING UNIT BOILER FEED UNIT BOILER CONSTANT AIR VOLUME BOX COOLING COIL CONDENSATE DRAIN CUBIC FEET PER MINUTE CHILLER CONDENSATE PUMP CONDENSER WATER RETURN CONDENSER WATER SUPPLY COOLING TOWER CONDENSING UNIT CABINET UNIT HEATER CHILLED WATER RETURN CHILLED WATER SUPPLY DIFFUSER DUAL DUCT DIRECT EXPANSION EXHAUST AIR ENTERING AIR TEMPERATURE EXHAUST FAN EFFICIENCY ENERGY RECOVERY COIL ENERGY RECOVERY WHEEL EXPANSION TANK ENTERING WATER TEMPERATURE FILTER BANK (CONSISTING OF ONE OR MORE FILTERS) FAN COIL UNIT FLOW MEASURING STATION FUEL OIL RETURN FUEL OIL SUPPLY FUEL OIL VENT FIRE DAMPER FIRE SMOKE DAMPER FINNED TUBE RADIATOR GRILLE GLYCOL CHILLED WATER RETURN GLYCOL CHILLED WATER SUPPLY GRAVITY EXHAUST GLYCOL HOT WATER RETURN GLYCOL HOT WATER SUPPLY GRAVITY INTAKE
DESCRIPTION MASTER ALARM PANEL MEDICAL VACUUM PUMP MEDICAL NITROGEN MEDICAL NITROUS OXIDE MEDICAL OXYGEN PRESSURE REDUCING VALVE MEDICAL VACUUM VALVE BOX MEDICAL WASTE ANESTHESIA GAS DISPOSAL WATER COLUMN
SYMBOL
NOT ALL ABBREVIATIONS APPLY TO THIS SET OF DOCUMENTS.
ABBREVIATION AB AC AHU BFU BLR CAV CC CD CFM CH CP CR CS CT CU CUH CWR CWS D DD DX EA EAT EF EFF ERC ERW ET EWT FB FCU FMS FOR FOS FOV FRD FSD FTR G GCWR GCWS GE GHWR GHWS GI
ABBREVIATION MAP MVP N NO O PRV VAC VB WAGD WC
A
DESCRIPTION ACCESS DOOR/PANEL ABOVE FINISHED FLOOR AMBIENT BOTTOM OF BEAM DIAMETER DOWN EXISTING ELECTRICAL CONTRACTOR EFFICIENCY FEET PER MINUTE FEET PER SECOND GENERAL CONTRACTOR GALLONS PER MINUTE LENGTH LINEAR FEET
A. THESE NOTES APPLY TO ALL SHEETS CONTAINING HVAC, PIPING, PLUMBING, TEMPERATURE CONTROLS, AND FIRE PROTECTION WORK.
T
ABBREVIATION AD AFF AMB BOB DIA DN E EC EFF FPM FPS GC GPM L LF
FIRE PROTECTION SYMBOLS
NOT ALL ABBREVIATIONS APPLY TO THIS SET OF DOCUMENTS.
NOT ALL ABBREVIATIONS APPLY TO THIS SET OF DOCUMENTS.
REGIST ER
LABORATORY AND MEDICAL GAS ABBREVIATIONS
GENERAL ABBREVIATIONS
C
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SACRED HEART 4TH & 5TH MECHANICAL COVER SHEET
Date
SES PROJECT # 14041
11/25/2014 4:37:13 PM
M000 Scale
NONE
1.3
2.4
3.4
3.6 AVERA FACILITY DEVELOPMENT
GENERAL NOTES
A
A. REFER TO MECHANICAL COVER SHEET M000 FOR GENERAL REQUIREMENTS, SYMBOLS, ABBREVIATIONS, AND MOUNTING ELEVATION REQUIREMENTS.
SHEET NOTES 1 REMOVE EXISTING FAN COIL LOOP PUMP AND APPURTANCES. REMOVE HWS/R AND CWS/R TO MAIN AND CAP. PUMPS SERVING 2ND FLOOR SHALL REMAIN IN SERVICE. COORDINATE REMOVAL WITH PHASE OF CONSTRUCTION FOR FAN COILS SERVED. 2 REMOVAL OF AHU-10 INCLUDING ASSOCIATED DUCTWORK, CONTROLS, PIPING CONNECTIONS, COILS, HUMIDIFIERS AND REHEAT COILS TO BE COMPLETED BY OWNER.
A1 B B.0
P-13
P-15
3 REMOVE EXISTING SUPPLY DUCT SERVING NEGATIVE AIR ROOMS DURING PHASE 2. CAP DUCT AT MAIN.
1
4 REMOVE EXISTING SUPPLY DUCT SERVING ISOLATION ROOMS DURING PHASE 3. CAP DUCT AT MAIN.
2
1.7
2.1
5 REMOVE EXISTING SUPPLY DUCT BETWEEN NEW AHU 10 AND EXISTING SUPPLY MAIN DURING PHASE 1. PROVIDE TEMPORARY CONNECTION TO SERVE EXISTING ROOMS UNTIL PHASE 3.
3
B1.1
6 REMOVE PORTION OF EXISTING DUCT TO ALLOW FOR INSTALLATION OF NEW WORK. REFER TO SHEET M131 FOR NEW WORK SCOPE.
1 2
C
2
2
P-16
2
C1
P-14 1
2
1
2 2
3
6
D
1 P-12
FESSION PRO AL . NO.
10229 ERIC G. SHERMAN
O
U
A
S
D1
REG
T
ED
R GINEE EN
REGIST ER
1
T H
K D A
O
11/25/14
E
No.
Description
Date
5
E1
1
5
4
1 P-11
P-18
F F1
1b 1
99
1
1c
2b
3c
3A
4 4a
5
5.1
6
B1.2 7
SACRED HEART
8
THIRD LEVEL DEMOLITION - HVAC AND PIPING 1/8" = 1'-0" 2014
C
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
4TH & 5TH THIRD LEVEL DEMOLITION - HVAC AND PIPING Date
SES PROJECT # 14041
11/25/2014 4:37:17 PM
M031 Scale
1/8" = 1'-0"
1.3
2.4
3.4
3.6 AVERA FACILITY DEVELOPMENT
GENERAL NOTES
A
A. REFER TO MECHANICAL COVER SHEET M000 FOR GENERAL REQUIREMENTS, SYMBOLS, ABBREVIATIONS, AND MOUNTING ELEVATION REQUIREMENTS.
SHEET NOTES 1 REMOVE FAN COIL UNIT AND ALL ASSOCIATED PIPING, CONDENSATE DRAIN, ACCESSORIES, CONTROLS AND APPURTANENCES. COORDINATE REMOVAL WITH WORK ON 3RD AND 5TH FLOORS. COORDINATE WORK WITH PHASING TO ENSURE CONTINUOUS SYSTEM OPERATION FOR EQUIPMENT OUTSIDE OF CURRENT PHASE.
PHASE 4 1
1
3 6"x6"
1.7
3
3
1
1
1 1/2"ø 1 1/2"ø
2"ø 2"ø
1
1
3
2 PATCH PIPING PENETRATIONS THROUGH FLOOR. PATCH METHOD SHALL MAINTAIN EXISTING FIRE RESISTANCE RATING OF FLOOR. 3
RAD CONTROLLER (ABOVE CEILING)
3 3
3
3
3 4
2.1
3
3 REMOVE DIFFUSER/GRILLE AND ALL ASSOCIATED DUCTWORK, ACCESSORIES, AND APPURTANENCES. COORDINATE WORK WITH PHASING TO ENSURE CONTINUOUS SYSTEM OPERATION FOR ROOMS OUTSIDE OF CURRENT PHASE.
4
4 REMOVE EXISTING FINNED TUBE RADIATION. REMOVE ALL ASSOCIATED PIPING AND CONTROLS.
3 2
T
B1.1
T
T
T
T
T
3 6"x4"
10"x4"
12"x8"
T
T
T
3
12"x10"
1
16"x10" 3
3
3
3
3
3
3
3
3
3
T
T
3
1
18"x10" 18"x10"
T
26"x8" SA
1
1 1/2"ø 2"ø
3
3 3
1
T
B
1
FS.D.
1
FS.D.
A1
3
3
CAP PIPING AT ACTIVE MAINS
3/4" HWS/R
8"x6" 3
3
32"x12"
16"x8"
1 1/2"ø 1 1/2"ø
2
2"ø 2"ø
3 1
16"x8" 10"x12"
3 T
1 1/4"ø 1 1/4"ø PHASE 2
3 16"x8"
10"x8"
1
1 1/2"ø 1 1/2"ø
2"ø 2"ø
2
1
3
3
3 REGIST ER
22"x10"
16"x8"
3
ED
FESSION PRO AL
S O
1
D1
1
3
E
10229 ERIC G. SHERMAN U
T H
K D A
O
CAP PIPING AT ACTIVE MAINS
No.
Description
Date
T
T
3/4" HWS/R
. NO.
11/25/14
T
T
3
REG
R GINEE EN
26"x8" SA
16"x8"
A
32"x12"
12"x14" SA
T
T
12"x14" 3
T
D
1 1/4"ø 1 1/4"ø
PHASE 3
3 10"x12"
T
3 1
1
26"x8" SA
1
24"x10"
C1
20"x10"
T
T
C
3
3 3
12"x8"
12"x8"
3
3
3
14"x8"
1
3
3
T
T
3
16"x10"
3
18"x10"
20"x10"
22"x10"
T
T
T
2
T
1
T T
RAD CONTROLLER (ABOVE CEILING)
3 3
4
3
3
3
26"x8" SA
T
3
16"x8"
3
E1
3
3
3
2"ø 2"ø
3
3
3
1
3
T
3
3
2"ø 1 1/2"ø
T
4
3
3
1 1/2"ø 1 1/2"ø
F 1
F1
1
1
1
1
1
1
1
1
PHASE 1
1b 1
99
1
1c
2b
3c
3A
4 4a
5
5.1
6
B1.2 7
SACRED HEART
8
FOURTH LEVEL DEMOLITION - HVAC AND PIPING 1/8" = 1'-0" 2014
C
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
4TH & 5TH FOURTH LEVEL DEMOLITION - HVAC AND PIPING Date
SES PROJECT # 14041
11/25/2014 4:37:21 PM
M041 Scale
1/8" = 1'-0"
98.5
1.3
2.4
3.4
3.6 AVERA FACILITY DEVELOPMENT
GENERAL NOTES
A
A. REFER TO MECHANICAL COVER SHEET M000 FOR GENERAL REQUIREMENTS, SYMBOLS, ABBREVIATIONS, AND MOUNTING ELEVATION REQUIREMENTS.
SHEET NOTES 1
REMOVE EXISTING PLUMBING TO FIXTURES ABOVE INCLUDING ALL APPURTENANCES. REMOVE ASSOCIATED COLD WATER, HOT WATER, SANITARY, AND VENT PIPING TO ABOVE CEILING AND EXTEND TO NEW FIXTURES. COMPLETE WORK WITHIN ASSOCIATED PHASE. MAINTAIN PROPER SYSTEM OPERATION TO ALL EXISTING AREAS AND COMPLETED PHASES. REFER TO NEW WORK SHEETS FOR ADDITIONAL INFORMATION.
2
REMOVE EXISTING PLUMBING FIXTURE INCLUDING ALL APPURTENANCES. REMOVE ASSOCIATED COLD WATER, HOT WATER, SANITARY, AND VENT PIPING TO NEAREST ACTIVE MAIN AND CAP. COMPLETE WORK WITHIN ASSOCIATED PHASE. MAINTAIN PROPER SYSTEM OPERATION TO ALL EXISTING AREAS AND COMPLETED PHASES.
3
EXISTING PIPING IS LOCATED IN VICINITY OF NEW DUCT MAINS. ADJUST PIPE HANGERS AND LOCATION AS REQUIRED TO ACCOMMODATE NEW WORK INSTALLATION.
PHASE 4
A1 B B.0
3
3
3
3
1/2"ø
3
1
1
2 1 1/2"ø 2
3/4"ø
1.7
1
2.1 3/4"ø 3/4"ø 1 1/2"ø
3
B1.1 1
1 1
1
1
1
1
1
1
1
1
1 1
3
1
1
1 1
1
3
1
1 1
C
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
C1
1
3 3
1
1
1
1
1
1
1
1
1
1
PHASE 2
1
FESSION PRO AL
S O
D1
1
1
REG
. NO.
10229 ERIC G. SHERMAN U
A
3
ED
R GINEE EN
REGIST ER
3
T
D
PHASE 3
1
T H
K D A
O
11/25/14
E
1
1
1
1
1
1
1
1
No.
1
1
1
1
1
1
1
1
Date
1
1
3
Description
1 1
1
1
1 1
1
1
1 1
1 1
1
1
1 1
1
1
1
E1 3/4"ø
3
3/4"ø 3/4"ø 1 1/2"ø 1/2"ø
1
1 1/2"ø
T
1 1/2"ø 3/4"ø 1
F
1 1/2"ø
3
3
3
3
3
F1 PHASE 1
1b 1
99
1
1c
2b
3c
3A
4 4a
5
5.1
6
B1.2 7
SACRED HEART
8
FOURTH LEVEL DEMOLITION - PLUMBING AND MED GAS 1/8" = 1'-0"
2014
C
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
4TH & 5TH FOURTH LEVEL DEMOLITION PLUMBING AND MED GAS Date
SES PROJECT # 14041
11/25/2014 4:37:24 PM
M042 Scale
1/8" = 1'-0"
1.3
2.4
3.4
3.6 AVERA FACILITY DEVELOPMENT
GENERAL NOTES
A
A. REFER TO MECHANICAL COVER SHEET M000 FOR GENERAL REQUIREMENTS, SYMBOLS, ABBREVIATIONS, AND MOUNTING ELEVATION REQUIREMENTS.
SHEET NOTES 1 REMOVE FAN COIL UNIT AND ALL ASSOCIATED PIPING, CONDENSATE DRAIN, ACCESSORIES, CONTROLS AND APPURTANENCES. COORDINATE REMOVAL WITH WORK ON 3RD AND 4TH FLOORS. COORDINATE WORK WITH PHASING TO ENSURE CONTINUOUS SYSTEM OPERATION FOR EQUIPMENT OUTSIDE OF CURRENT PHASE.
PHASE 4
1
1
4
1
4
1
1
4
2
1
4
2
2
2
RAD CONTROLLER (ABOVE CEILING)
2
2
2
1
2
2
2
4 PATCH PIPING PENETRATIONS THROUGH FLOOR. PATCH METHOD SHALL MAINTAIN EXISTING FIRE RESISTANCE RATING OF FLOOR.
5 2
T T
T
T
T
T
T
4
T
5 REMOVE EXISTING EXHAUST DUCT AND FAN. PREPARE EXISTING CURB FOR NEW FAN. 6
2 6"x4"
6
10"x4"
2
2
12"x10"
2
2
2
16"x10" 2
2
6 REMOVE EXISTING GRILLES AND DIFFUSERS IN CORRIDOR, CLEAN AND REINSTALL IN NEW CEILING GRID. REFER TO EXISTING DRAWINGS ISSUED FOR REFERENCE.
18"x10" 2
2
2
2
T
T
6"x6"
12"x8"
1
2
18"x10"
T
26"x8"
T
1
3 REMOVE EXISTING FINNED TUBE RADIATION. REMOVE ALL ASSOCIATED PIPING AND CONTROLS.
3
2.1
4
B1.1
2
3
2
1.7
2 REMOVE DIFFUSER/GRILLE AND ALL ASSOCIATED DUCTWORK, ACCESSORIES, AND APPURTANENCES. COORDINATE WORK WITH PHASING TO ENSURE CONTINUOUS SYSTEM OPERATION FOR ROOMS OUTSIDE OF CURRENT PHASE.
1
2
2
2
1
T
B B.0
4
FS.D.
1
FS.D.
A1
C T
T
6 6
CAP PIPING AT ACTIVE MAINS
C1 2
8"x6"
2
1
26"x8"
1
2
3/4" HWS/R
20"x10"
6
2
4 1
2
4 32"x12"
16"x8"
1
2
T
10"x6"
PHASE 3
6
PHASE 2
6
6
T
12"x14"
T
D
10"x12"
T
2
2
24"x10"
16"x8"
2
2
32"x12" 16"x8"
22"x10"
2
1 4
26"x8"
1
2
6
1 2
ED
FESSION PRO AL
S O
D1 2
2 6
E 12"x8"
No.
2
6
6
2
2
2
2
14"x8"
2
2
2
16"x8"
2
2
4
T
16"x10"
18"x10"
20"x10"
2
T
T
T
T
T
T
T
5
2 2
FS.D.
FS.D.
3
2
2
2
2
2
1
4
1
1
4
4
1
2
1
F1
1
2
2
1
1
2
1
4
1
1
4
1
PHASE 1
1
1c
2b
3c
3A
4 4a
5
5.1
6
B1.2 7
SACRED HEART
8
FIFTH LEVEL DEMOLITION - HVAC AND PIPING 1/8" = 1'-0"
Date
RAD CONTROLLER (ABOVE CEILING)
F
1b
Description
2
T
3
O
4
T
2 2
K D A
22"x10"
T
2
T H
2
2
26"x8"
E1
U
6
CAP PIPING AT ACTIVE MAINS
12"x8"
1
10229 ERIC G. SHERMAN
T
T
3/4" HWS/R
. NO.
11/25/14
T
T
6
REG
R GINEE EN
4
16"x8"
A
16"x8"
T
10"x8"
REGIST ER
2
1
2014
C
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
4TH & 5TH FIFTH LEVEL DEMOLITION - HVAC AND PIPING Date
SES PROJECT # 14041
11/25/2014 4:37:28 PM
M051 Scale
1/8" = 1'-0"
1.3
2.4
3.4
3.6 AVERA FACILITY DEVELOPMENT
GENERAL NOTES
A
A. REFER TO MECHANICAL COVER SHEET M000 FOR GENERAL REQUIREMENTS, SYMBOLS, ABBREVIATIONS, AND MOUNTING ELEVATION REQUIREMENTS.
SHEET NOTES 1
REMOVE EXISTING PLUMBING FIXTURE INCLUDING ALL APPURTENANCES. REMOVE ASSOCIATED COLD WATER, HOT WATER, SANITARY, AND VENT PIPING TO NEAREST ACTIVE MAIN AND CAP. COMPLETE WORK WITHIN ASSOCIATED PHASE. MAINTAIN PROPER SYSTEM OPERATION TO ALL EXISTING AREAS AND COMPLETED PHASES.
2
DISCONNECT MEDICAL GASES FROM EXISTING HEADWALL UNIT. SALVAGE EXISTING OUTLETS FROM HEADWALL FOR REINSTALLATION. PROVIDE NEW MOUNTING BRACKETS AND HARDWARE AS REQUIRED. REMOVE PIPING TO NEAREST ACTIVE MAIN AND CAP. COMPLETE WORK WITHIN ASSOCIATED PHASE. MAINTAIN PROPER SYSTEM OPERATION TO ALL EXISTING AREAS AND COMPLETED PHASES. COORDINATE WORK TO MINIMIZE OUTAGES. COORDINATE WORK TO CONSOLIDATE NUMBER OF CERTIFICATION VISITS.
3
CAP MEDICAL GAS PIPING AT MAIN. COORDINATE CAPPING ACTIVITIES WITH PHASE 0 NEW WORK MEDICAL GAS PIPING. WORK SHALL BE COORDINATED SUCH THAT ONE MEDICAL GAS CERTIFICATION IS REQUIRED.
4
CAP MEDICAL GAS PIPING AT MAIN. COORDINATE CAPPING ACTIVITIES WITH PHASE 1 NEW WORK MEDICAL GAS PIPING. WORK SHALL BE COORDINATED SUCH THAT ONE MEDICAL GAS CERTIFICATION IS REQUIRED.
5
CAP MEDICAL GAS PIPING AT MAIN. COORDINATE CAPPING ACTIVITIES WITH PHASE 3 NEW WORK MEDICAL GAS PIPING. WORK SHALL BE COORDINATED SUCH THAT ONE MEDICAL GAS CERTIFICATION IS REQUIRED.
6
REMOVE EXISTING PLUMBING FIXTURE AND PREPARE EXISTING PIPING FOR ACCEPTANCE AND INSTALLATION OF NEW FIXTURE.
PHASE 4
A1 B B.0
1/2"ø 2
6
1 2
3/4"ø 1
2
1.7
2
2
2
2
2
2
B1.1
1 1/2"ø
2
2.1
6
3/4"ø 3/4"ø 1 1/2"ø 1
1
1
1
1
1
1
6
2
4
1 1/2"ø
1/2"ø
3/4"ø
1 1
1 2
1
C
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1 1
1
1 5
1
2
1
1
2
1 2
C1
2
1
1
1
1
1
1
2
1
1
PHASE 3
PHASE 2 1 1
2
1
1
2
ED
FESSION PRO AL
S O
D1
1 2
1
. NO.
10229 ERIC G. SHERMAN U
T H
K D A
O
1 2
1
1
1
11/25/14
3
E
REG
R GINEE EN
REGIST ER
1
A
1
T
D
1
1
No.
Description
Date
1
1
1
2
1 2 1
1
1 1
1
1
E1 3/4"ø
1
1 1
1
1
2
2
1
1
1
1 1
1 1
1
1
1 1
1
1
1
1
1
1
1
2
2
2
2
2
3/4"ø 3/4"ø 1 1/2"ø
3
1/2"ø 6 6 2
1 1/2"ø 6
1 1/2"ø 3/4"ø
2
F
2
1/2"ø
F1 PHASE 1
1b 1
99
1
1c
2b
3c
3A
4 4a
5
5.1
6
B1.2 7
SACRED HEART
8
FIFTH LEVEL DEMOLITION - PLUMBING AND MED GAS 1/8" = 1'-0" 2014
C
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
4TH & 5TH FIFTH LEVEL DEMOLITION PLUMBING AND MED GAS Date
SES PROJECT # 14041
11/25/2014 4:37:32 PM
M052 Scale
1/8" = 1'-0"
1.3
2.4
3.4
3.6 AVERA FACILITY DEVELOPMENT
GENERAL NOTES
A
A. REFER TO MECHANICAL COVER SHEET M000 FOR GENERAL REQUIREMENTS, SYMBOLS, ABBREVIATIONS, AND MOUNTING ELEVATION REQUIREMENTS.
SHEET NOTES 1 REMOVE EXISTING SPRINKLER AND BRANCH PIPING TO MAIN AND CAP. COMPLETE WORK WITHIN ASSOCIATED PHASE. MAINTAIN PROPER SYSTEM OPPERATION TO ALL EXISTING AREAS AND COMPLETED PHASES.
PHASE 4
A1
2 CLEAN EXISTING SPRINKLER HEAD AND CENTER IN NEW CEILING GRID. REFER TO EXISTING DRAWINGS ISSUED FOR REFERENCE.
T
B B.0
1.7
1
1 1/4"ø
2.1
1 1
B1.1
1
1
1
1
1
1
1
1
1
1
1
2
1
1 1/4"ø
1
1 1/4"ø
1
1 1/4"ø
1
1 1/4"ø
1 1/4"ø
1
1 1/4"ø
1
1 1/4"ø
1
1 1/4"ø
1
1 1/4"ø
1
1 1/4"ø
1 1/4"ø
1 1/4"ø
1
1
C 2
C1
1
2
2
2
2
2
2
2
2
1 1/4"ø
2
1
1 1
1
6" STANDPIPE
ZONE 13W
1 INSPECTOR'S TEST CONNECTIONS
1 1/4"ø 2
D
1
1 1/4"ø
2 2
PHASE 3
PHASE 2
2 1
2
1
ZONE 14W
6" STANDPIPE
1 1
1
FESSION PRO AL
S
1
1 1/4"ø
1
1 1/4"ø
2
2
2
2
2
2
2
2
2
O
D1
E1
1
2
1
1
1
1
1
1
10229 ERIC G. SHERMAN U
T H
K D A
O
Description
Date
1 1/4"ø
1 1/4"ø
1 1/4"ø
1 1/4"ø
1 1/4"ø
1 1/4"ø
1 1/4"ø
1 1/4"ø
1 1/4"ø
No.
1 1/4"ø
. NO.
11/25/14
2
E
1
REG
R GINEE EN
2
ED
A
1 1/4"ø
T
2
REGIST ER
1 1/4"ø
1
1
1
1
1 1/4"ø
2
1
1 1
1
1
1
1
1
1
1
1
1 1
1
1 1/4"ø
1 1"ø
1
T
1
F F1 PHASE 1
1b 1
99
1
1c
2b
3c
3A
4 4a
5
5.1
6
B1.2 7
SACRED HEART
8
FIFTH LEVEL DEMOLITION - FIRE PROTECTION 1/8" = 1'-0" 2014
C
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
4TH & 5TH FIFTH LEVEL DEMOLITION - FIRE PROTECTION Date
SES PROJECT # 14041
11/25/2014 4:37:36 PM
M053 Scale
1/8" = 1'-0"
98.5
1.3
2.4
3.4
3.6 AVERA FACILITY DEVELOPMENT
GENERAL NOTES
A
A. REFER TO MECHANICAL COVER SHEET M000 FOR GENERAL REQUIREMENTS, SYMBOLS, ABBREVIATIONS, AND MOUNTING ELEVATION REQUIREMENTS.
SHEET NOTES 1 PROVIDE TEMPORARY CONNECTION TO EXISTING SUPPLY DUCT. PROVIDE BALANCING DAMPER FOR CONTROLLED OPERATION UNTIL PHASE 3 WHEN DUCTWORK IS REMOVED. 2 REMOVE EXISTING PLENUM WALL AND DOOR FOR INSTALLATION OF AHU. REINSTALL PLENUM WALL AND DOOR TO MATCH ORIGINAL INSTALLATION.
A1 7
P-15 EF-17
38"x38" EA
HX-CW1 UP
EF-14
44"x24" SA
48"x24"
9
24"x30" RA UP 10"x20" RA UP
20"x10" 24"x12" 88"x24" SA
9
9
9
30"x26"
30"x32" SA UP
20"x18"
60"x24" AHU-09
32"x20" EA 16"x12" RA 26"x22" RA UP 32"x20" EA UP 16"x12" RA UP
26"x22" RA
O
36"x22" SA DN
9
48"x18"
24"x30" RA
AHU-06
44"x20" SA
E 54"x14" RA
AHU-02
60"x22" RA
P-18
72"x22" RA
72"x12" RA DN
K D A
O
Description
Date
44"x20" RA
9 30"x18"
P-17
2 48"x18"
9
F
T H
20"x18" 70"x16"
4
5 1
AHU-04
110"x20"
48"x24"
VFD-RF-10B
9 AHU-08
18"x18"
48"x18"
VFD-RF-10A
U
9
24"x30" RA AHU-07
112"x30"
E1
10229 ERIC G. SHERMAN
30"x32" SA
24"x30" RA
9
. NO.
110"x20"
AHU-05
REG
11/25/14
No. 30"x32" SA
FESSION PRO AL
S
44"x24" SA UP
ED
R GINEE EN
AHU-10
D1
12"x26" RA 9
VFD-SF-10A VFD-SF-10B
30"x32" SA
20"x18"
26"x22" RA
60"x22" RA 6
32"x20" EA
30"x24" SA
44"x20" RA ABOVE 44"x24" SA BELOW
10
48"x24"
D
12"x24" RA UP
10"x14" EA 30"x14" EA DN
10 RELOCATE EXISTING SANITARY WASTE PIPING, CONTROL TUBING, WIRING, CONDUITES, AND HANGERS TO ACCOMMODATE INSTALLATION OF DUCT THROUGHT WALL.
9
9
44"x20" RA DN 26"x14" EA DN 22"x10" EA DN 16"x10" EA DN 44"x24" SA DN
9 AREA IS CONGESTED WITH EXISTING DUCTWORK AND PIPING WHICH MAY NOT ALLOW FOR DIRECT INSTALLATION. PROVIDE ADDITIONAL OFFSETS AND RELOCATE EXISTING DUCTWORK AND PIPING AS REQUIRED TO FACILITATE INSTALLATION OF NEW WORK.
P-16
REGIST ER
30"x26"
9
30"x14" EA 44"x24" RA DN 44"x24" SA DN 30"x24" SA UP
44"x20" SA DN
20"x10" 24"x12"
10"x14" EA
20"x18"
BELOW DN
60"x12" RA
20"x10" RA
60"x22" RA DN 60"x26" SA BELOW DN
DN
8 CONNECT TO EXISTING 24x14 SUPPLY DUCT.
44"x24" SA
20"x10" RA
44"x24" SA
54"x12"
AHU-11
AHU-03
24"x12" RA
44"x24" RA
30"x26"
C1
24"x12" RA
16"x20" EA DN 10"x20" EA DN 24"x24" EA DN
6 EXTEND CONCRETE HOUSEKEEPING PAD TO ACCOMMODATE NEW AHU. 7 DUCT UP TO 4TH FLOOR. SAW CUT FLOOR TO ALLOW FOR INSTALLATION OF NEW DUCT. COORDINATE LOCATION WITH STRUCTURAL CONCRETE TEES.
28"x10" RA
C
5 RELOCATE EXISTING PLENUM ACCESS DOOR TO THIS LOCATION.
9
20"x10" EA 44"x24" RA
44"x20" SA ABOVE 44"x24" RA BELOW
30"x12" RA
10"x22" EA
20"x10" EA
26"x14" EA
10"x16" EA
EF-20
VB-3-1 1500 CFM COOLING ONLY
EF-07 EF-18
30"x32" SA
22"x14" SA
12"x26"
22"x16" SA
12"x16"
24"x16" SA
16"x16"
32"x20" EA
28"x28" EA
38"x16" SA
B1.1
4 106"x26" RELIEF AIR DUCT BELOW. TOP OF DUCT TO BE ALIGNED WITH TOP OF RELIEF AIR PLENUM (APPROX. 9' A.F.F.). 106"x24" OUTDOOR AIR DUCT ABOVE. BOTTOM OF DUCT TO BE ALLIGNED WITH BOTTOM OF OUTDOOR AIR PLENUM (APPROX 9'-6" A.F.F.).
9
20"x20"
2.1
28"x16" SA
38"x16" SA
8
22"x22"
10"x14" EA
1.7
24"x14"
EF-16 EF-15
A
9
3 REMOVE EXISTING LOUVER AND DOOR FOR INSTALLATION OF AHU. REINSTALL LOUVER AND DOOR TO MATCH ORIGINAL INSTALLATION.
T
EF-21
30"x14" EA
B B.0
9
9 9
7
3
F1
1b 1
99
1
1c
2b
3c
3A
4 4a
5
5.1
6
B1.2 7
SACRED HEART
8
4TH & 5TH THIRD LEVEL - HVAC
THIRD LEVEL- HVAC 1/8" = 1'-0" 2014
C
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
Date
SES PROJECT # 14041
11/25/2014 4:37:39 PM
M131 Scale
1/8" = 1'-0"
98.5
1.3
2.4
3.4
3.6 AVERA FACILITY DEVELOPMENT
GENERAL NOTES A. REFER TO MECHANICAL COVER SHEET M000 FOR GENERAL REQUIREMENTS, SYMBOLS, ABBREVIATIONS, AND MOUNTING ELEVATION REQUIREMENTS.
6"ø GCWS
6"ø GCWR
A
SHEET NOTES 1 ROUTE PIPING UP TO NEW VAV TERMINAL UNITS ON FLOORS 4 AND 5 DURING PHASE 1.
5
6"ø GCWR 6"ø GCWS
A1
2 ROUTE PIPING UP TO NEW VAV TERMINAL UNITS ON FLOORS 4 AND 5 DURING PHASE 3.
4 6
6 6"ø GCWR
1.7
6
HX-CW1
B1.1 1"ø HWR
3/4"ø
2 1/2"ø CWR 2 1/2"ø CWS
2"ø HWR
3/4"ø HWS
6 RELOCATE EXISTING HANGERS, SUPPORTS AND CONDUIT TO ALLOW FOR INSTALLATION OF NEW CHILLED WATER PIPING.
4"ø HWS
1"ø HWR
1"ø HWS
1"ø HWR
5 PROVIDE OFFSETS REQUIRED TO MAKE CONNECTIONS. HALLWAY OUTSIDE MECHANICAL ROOM IS CONGESTED AND WILL REQUIRE ADDITIONAL OFFSETS TO ACCOMMODATE INSTALLATION.
6"ø CWS
6"ø CWR
2"ø CWS 2"ø CWR
3/4"ø HWR
4
M502
PROVIDE DRAIN PAN WITH MOISTURE SENSOR TIED TO BAS FOR NEW PIPING.
2.1
4 PROVIDE 3-WAY DIVERTER VALVE AT PIPE JUNCTION. REFER TO CHILLED WATER CONTROL DETAIL FOR ADDITIONAL REQUIREMENTS.
2
6"ø CWS
6
6"ø CWS
3
6"ø CWS
2
6"ø GCWS
6"ø CWR
6
8"ø CWS
B B.0
3 CORE DRILL PENETRATIONS IN STRUCTURAL SLAB. COORDINATE LOCATIONS WITH EXISTING STRUCTURAL TEES.
2 1/2"ø CWS 2 1/2"ø CWR
AHU-03
1"ø HWR 1"ø HWS
4"ø HWR
4"ø HWR
AHU-11
4"ø HWR 6"ø HWR 3"ø MPC DN
2"ø CWS DN 2"ø CWR DN
8"ø CR DN 8"ø CS DN
2 1/2"ø HWR 2 1/2"ø HWS
1 1/2"ø CWS 1 1/2"ø CWR
2"ø MPS
2 1/2"ø HWS 2 1/2"ø HWR 3"ø MPS
AHU-09
1 1/2"ø CWS 1 1/2"ø CWR
4"ø HWR
1 1/2"ø CWS 1 1/2"ø CWR 4
EXISTING PRV
O
M501 2
2"ø LPS
AHU-05
E1
2 1/2"ø HWS 3"ø HWS 3"ø HWS
2"ø HWS
M501 2
6"ø HPS 4"ø HWR 3"ø HWR
1 1/4"ø HWR 1 1/4"ø HWS
1 4"ø HWR 3"ø HWR
6"ø CWS
1 1/4"ø HWS 1 1/4"ø HWR
6
1 1/2"ø HWS 1 1/2"ø HWR 1"ø HPC
6"ø CWR 2"ø HWR
2 1/2"ø HWS 3"ø HWR 1 1/4"ø LPS
3"ø CWR 3"ø CWS
2 1/2"ø HWR 2 1/2"ø HWS 2"ø HWS 4"ø HWR 2"ø HWS 4"ø HWR 6"ø CWR 6"ø CWS
2"ø LPS
3"ø HWS
3"ø HWR 1 1/4"ø HWR 1 1/4"ø HWS
1 1/4"ø HWS 1 1/4"ø HWR AHU-07 3"ø CWS 3"ø CWR
AHU-08
No.
1"ø CWR 1"ø CWS
3"ø CWS
2 1/2"ø 2 1/2"øCWR CWS
10229 ERIC G. SHERMAN U
T H
K D A
O
Description
Date
2"ø CWR 2"ø CWS
AHU-02
AHU-04
M501
. NO.
11/25/14
3"ø HWS
2 1/2"ø HWR 6"ø CWR 4"ø CWS
REG
2 1/2"ø HWS
5 M501
FESSION PRO AL
S
AHU-10
1"ø HPC
ED
A
2
3"ø CWS 3"ø CWR
T
2"ø HWR
1
6"ø HPS REGIST ER
STEAM RELIEF VENT UP 6"ø 6"ø STEAM RELIEF VENT UP
2"ø HWS
M501
4"ø CWR 4"ø CWS
E
6"ø MPS
4"ø HWS DN
6"ø MPS 4"ø HWS
1 1/2"ø MPC DN
2"ø HWS
1 1/2"ø HWS
8"ø CWS
1 1/2"ø MPC 1 1/4"ø HPC DN
6"ø HPS
2"ø HWS 2"ø HWR
AHU-06
2"ø HWR
6"ø MPS
M502
D1
3"ø MPC DN
R GINEE EN
3"ø CWR
4"ø HWR
2 1/2"ø HWS 2 1/2"ø HWR 8"ø CWS 3"ø CWR 4"ø HWR 1 1/2"ø HWS 4"ø HWR 1"ø HWS
D
8"ø CR 8"ø CS
1"ø HWS DN 4"ø HWR DN 6"ø HPS DN
1 1/2"ø CWR 1 1/2"ø CWS
1 1/4"ø HWR 1 1/4"ø HWS
2 1/2"ø HWR
C1
8"ø CWS
4"ø HWS
2 1/2"ø CWR 4"ø HWR 1"ø HWS
8"ø CR 8"ø CWS 8"ø CS
4"ø HWS
C
1 3
2"ø HDTS 2"ø HDTR
F F1
1b 1
99
1
1c
2b
3c
3A
4 4a
5
5.1
6
B1.2 7
SACRED HEART
8
4TH & 5TH THIRD LEVEL PIPING
THIRD LEVEL- PIPING 1/8" = 1'-0" 2014
C
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
Date
SES PROJECT # 14041
11/25/2014 4:37:43 PM
M132 Scale
1/8" = 1'-0"
1.3
2.4
3.4
3.6 AVERA FACILITY DEVELOPMENT
GENERAL NOTES
A
A. REFER TO MECHANICAL COVER SHEET M000 FOR GENERAL REQUIREMENTS, SYMBOLS, ABBREVIATIONS, AND MOUNTING ELEVATION REQUIREMENTS. B. PIPING TO INDIVIDUAL VAV BOXES SHALL BE 3/4" UNLESS NOTED OTHERWISE. ELEVATOR LINK 4900
SHEET NOTES 1 SEAL EXISTING AND NEW PENETRATIONS WITHIN ROOM AIR TIGHT.
PHASE 4 D-3 100 CFM
D-3 100 CFM
D-3 100 CFM
D-3 100 CFM
26"x12" SA
G-1 200 CFM
1 1/2"ø 1 1/2"ø
1.7
2.1
D-1 200 CFM
12"x8" SA
12"x8" SA
12"x8" SA
VB-4-26 300PATIENT CFM RM
VB-4-25 PATIENT 300 RM CFM
400
1 1/2"ø VB-4-23 PATIENT RM 300 CFM
VB-4-24 PATIENT 300 CFM RM
402
404
1"ø VB-4-22 PATIENT RM 300 CFM
1 1/2"ø
406
12"x8" 1 1/2"ø VB-4-28 200 CFM
G-1 125 CFM
OFFICE 460
410
G-2 100 CFM
MECH 459
G-1 200 CFM
G-1 200 CFM
10"x4"
12"x8" G-1 200 CFM G-2 100 CFM
G-2 100 CFM
G-2 100 CFM
G-1 200 CFM
12"x8"
18"x10" G-2 100 CFM
G-2 100 CFM
G-2 100 CFM
G-2 100 CFM
D-3 100 CFM
PATIENT RM D-1 422
100 CFM
26"x8" RA
VB-4-15 200 CFM 1"ø 1"ø
20"x10"
G-1 125 CFM
8"x16" RA UP 16"x12" RA DN
16"x8"
OMNI CELL 545
6"ø 6"ø STEAM RELIEF VENTS TO ROOF
1"ø
D-1 100 CFM
G-1 125 CFM
G-2 100 CFM
D-3 100 CFM
D-3 100 CFM
D-1 100 CFM
12"x8"
G-1 125 CFMANTERIOR RM
12"x8"
450
16"x8" RA
26"x8"
12"x8"
12"x8" VB-4-34 550 CFM
M500
G-2 100 CFM
TYP
16"x10"
18"x10" G-1 200 CFM
G-1 200 CFM 26"x8" RA
G-1 200 CFM
G-1 200 CFM
12"x8"
12"x8"
G-2 100 CFM
20"x10" G-1 200 CFM
22"x10"
1
16"x8"
G-2 200 CFM
G-2 G-2 200 CFM 100 CFM
FS.D.
16"x8"
4
D-1 12"x8" SA 200 CFM
1"ø 12"x8" SA
12"x8" SA D-1 200 CFM
VB-4-4
VB-4-5
PATIENT300 RM CFM 1"ø 442
PATIENT300 RMCFM 440
1 1/2"ø
438
12"x8" SA
12"x8" SA
12"x8" SA D-1 200 CFM
D-1 200 CFM
1 1/2"ø
VB-4-6 300PATIENT CFM RM
VB-4-7
434
12"x8" SA
12"x8" SA
D-1 200 CFM
D-1 200 CFM
D-1 200 CFM
VB-4-8 300PATIENT CFM RM
PATIENT RM 300 CFM 436
VB-4-9
PATIENT 300 RM CFM 432
12"x8" SA
D-1 200 CFM
26"x12" RAD-2
2b
D-3 100 CFM
D-3 100 CFM
3c
D-3 100 CFM
D-3 100 CFM
3A
4 4a
D-3 100 CFM
PHASE 1
5
U
T H
K D A
O
Description
Date
D-3 100 CFM
D-1 100 CFM
5.1
D-3 100 CFM
M500
6 M500
TYP D-3 100 CFM
6
D-3 100 CFM
D-1 100 CFM
1 1/2"ø 1 1/2"ø
3 D-3 100 CFM
G-1 125 CFM
2
D-1 200 CFM
RESTROOM 429
STORAGE 431
10"x10" SA
G-2 200 CFM
M500
1c
3/4"ø
VB-4-3 PATIENT RM 300 CFM 3/4"ø 444
16"x12" SA 10"x8"
F1
1 RESTROOM D-1 451 150 CFM
VB-4-2
PATIENT RM 300 CFM 446
10229 ERIC G. SHERMAN
7
D-3 100 CFM
M501
B1.2 7
12"x8" 16"x12"
3
FS.D.
D-3 100 CFM
VB-4-1 RM PATIENT 300 CFM 448
. NO.
G-1 125 CFM
22"x8"
FS.D.
10"x10"
No.
12"x8"
G-2 100 CFM
REG
16"x12"
2
G-2 100 CFM 16"x8" G-1 200 CFM
G-2 100 CFM
1
D-1 300 CFM
1
G-1 200 CFM
G-2 100 CFM
VB-4-11 200 CFM
G-2 100 CFM
14"x8"
E1
F
G-1 G-1 200 CFM 200 CFM
G-2 100 CFM
VB-4-10 200 CFM
12"x8" EA
G-2 100 CFM
26"x8"
VB-4-33 200 CFM
D-1 100 CFM
D-3 100 CFM
G-2 100 CFM
FESSION PRO AL
11/25/14
3/4" HWS/R G-2 100 CFM
ED
A
12"x8" 3/4"ø VB-4-32 200 CFM
16"x8" RA
TYP
E
12"x8"
G-2 100 CFM
5 M500
3/4"ø
32"x12" EA
16"x8"
O
10"x8" EA G-2 100 CFM
D-1 100 CFM
S
12"x8"
1"ø
G-1 125 CFM
LOCKER ROOM 547
546
14"x26" RA UP 26"x22" RA DN 32"x12" EA UP 32"x20" EA DN
NUTRITION 543
12"x8"
R GINEE EN
SOILED 542
D-3 100 CFM
PHASE 2 26"x14" RA CONFERENCE
G-1 125 CFM CLEAN UTILITY 541
G-2 100 CFM
30"x24" SA DN
30"x16" SA
WAITING ROOM 538
G-1 125 CFM
30"x16" SA UP
PATIENT RM 424
T
VB-4-31 200 CFM
12"x14" RA
EQUIPMENT 540
32"x12"
REGIST ER
STORAGE 539
12"x14" RA
1"ø
26"x8" RA UP 12"x26" RA DN
18"x30" RA UP 24"x30" RA DN 10"x12" RA UP DIET 10"x20" RA DN 12"x14" RA544UP 12"x24" RA DN 30"x20" SA UP 30"x32" SA DN
24"x18" RA 10"x12" RA
G-2 100 CFM
10"x10"
DIRTY UTILITY 549 TOILET 548
10"x12"
D-3 100 CFM
1"ø
VB-4-30 200 CFM
CLEAN UTILITY 550
D-1 100 CFM
12"x8"
VB-4-14 200 CFM
16"x12"
16"x8" RA
G-2 100 CFM
G-1 125 CFM
OFFICE 537
TOILET 535
RESTROOM 455
D-1 100 CFM
G-2 100 CFM
VB-4-13 200 CFM 1"ø 1"ø
HSKG 536
10"x6" EA
10"x10"
G-1 125 CFM
VB-4-12 200 CFM
1"ø
1"ø
G-1 125 CFM
12"x8"
PHASE 3
D-1 100 CFM
G-1 200 CFM
16"x10"
ELEC 534
12"x8"
D-1 100 CFM
D1
G-2 100 CFM
D-1 250 CFM
3/4" HWS/R
16"x8"
D-3 100 CFM
G-2 100 CFM
12"x8" RA
G-1 200 CFM
420
VB-4-18 300 CFM
16"x8"
D-3 100 CFM
16"x8" EA 10"x10" NEGATIVE AIR
24"x10"
12"x8"
G-2 100 CFM 16"x8" 8"x6" G-1 125 CFM
D-3 100 CFM
D-3 100 CFM
G-1 200 CFM
12"x10"
100
G-2 200 CFM 1
16"x8" EA
22"x10"
VB-4-29 200 CFM
D-3 100 CFM
D
G-1 200 CFM
1
PATIENT RM 416
414
G-2 200 CFM
G-2 100 CFM
RESTROOM 421
D-1 100 CFM
C1
6"x4"
26"x8" RA
12"x8" SA
VB-4-19 PATIENT 300 CFM RM
412
RESTROOM 418 G-2
26"x8" RA
C
G-2 100 CFM
1 1/2"ø
D-1 100 CFM
G-1 200 CFM
12"x8"
12"x8" SA 3/4"ø 3/4"ø VB-4-20 PATIENT RM 300 CFM
RAD-1
D-1 200 CFM 12"x8" SA
1"ø
VB-4-21 300PATIENT CFM RM
408
22"x8" D-3 100 CFM
12"x8" SA 1"ø
1"ø
D-1 200 CFM
D-1 200 CFM
12"x8" SA
12"x8" SA
1 1/2"ø
1 1/2"ø
D-1 200 CFM
D-1 200 CFM
D-1 200 CFM
D-1 200 CFM
26"x8"
16"x12"
D-1 100 CFM
FS.D.
FS.D.
B1.1
2
1 1/2"ø
D-1 200 CFM
16"x12" SA
26"x8" RA
18"x16"
3 26" x 18" SA DUCT UP TO FIFTH FLOOR. 26" x 30" SA DUCT DOWN TO THIRD FLOOR.
M500
M500
10"x10" SA
16"x12"
OFFICE VB-4-27 200 CFM 4621 1/2"ø
4
6
3
D-3 100 CFM
2 2" HWS/HWR UP TO FIFTH FLOOR. 2-1/2" HWS/HWR DOWN TO THRID FLOOR.
M501
M500
B B.0
1
7
D-3 100 CFM
D-3 100 CFM
VB-4-16 200 CFM 3/4"ø 3/4"ø
D-3 100 CFM
18"x10"
4
D-3 100 CFM
FS.D.
A1
D-3 100 CFM
4 M500 REBALANCE TO 75 CFM
SACRED HEART
8
4TH & 5TH FOURTH LEVEL HVAC AND PIPING
FOURTH LEVEL - HVAC AND PIPING 1/8" = 1'-0" 2014
C
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
Date
SES PROJECT # 14041
11/25/2014 4:37:54 PM
M141 Scale
1/8" = 1'-0"
1.3
2.4
3.4
3.6 AVERA FACILITY DEVELOPMENT
GENERAL NOTES
A
A. REFER TO MECHANICAL COVER SHEET M000 FOR GENERAL REQUIREMENTS, SYMBOLS, ABBREVIATIONS, AND MOUNTING ELEVATION REQUIREMENTS. B. PIPING TO INDIVIDUAL VAV BOXES SHALL BE 3/4" UNLESS NOTED OTHERWISE.
SHEET NOTES 1 SEAL EXISTING AND NEW PENETRATIONS WITHIN ROOM AIR TIGHT.
PHASE 4 D-3 100 CFM
4
D-3 100 CFM
M500
D-3 100 CFM
D-3 100 CFM
D-3 100 CFM
D-3 100 CFM
D-3 100 CFM
2 REBALANCE EXISTING EXHAUST GRILLE TO 75 CFM.
D-3 100 CFM
4
3 2" HWS/HWR DOWN TO 4TH FLOOR.
M500 26"x12"
1 1/2"ø
1.7
1 1/2"ø
2.1
VB-5-26 300 CFM
VB-5-25 300 CFM
12"x8"
1 1/2"ø VB-5-23 300 CFM
VB-5-24 300 CFM
12"x8"
12"x8"
1 1/2"ø
12"x8"
1"ø VB-5-22 300 CFM
G-1 200 CFM
G-1 200 CFM
12"x8"
G-1 200 CFM
10"x4"
1"ø
1 1/2"ø 1 1/2"ø VB-5-28 200 CFM
G-2 100 CFM
D-1 200 CFM
12"x8"
1
D-1 200 CFM
G-1 200 CFM
G-1 200 CFM
12"x10"
G-2 100 CFM
G-2 100 CFM
G-2 100 CFM
12"x8"
12"x8" G-1 200 CFM
G-1 125 CFM
G-1 200 CFM
16"x10"
G-2 100 CFM
12"x8"
16"x8" 10"x12"
G-2 100 CFM
G-2 100 CFM 10"x12"
20"x10"
VB-5-15 200 CFM 1"ø 1"ø
D-3 100 CFM
12"x8"
PHASE 2 16"x8"
G-2 100 CFM
26"x8" RA
12"x8"
G-2 100 CFM
G-2 75 CFM
12"x8"
G-1 200 CFM
G-1 125 CFM
14"x8" G-1 200 CFM
G-1 200 CFM 12"x8"
16"x8" 12"x8"
10"x10"
14"x10"
1
D-3 100 CFM
D-1 150 CFM
FS.D.
18"x10" 1 G-2 200 CFM
G-2 200 CFM
1
G-2 100 CFM
12"x8"
VB-5-1 300 CFM
D-1 200 CFM
G-2 200 CFM
12"x8" VB-5-2 300 CFM 3/4"ø D-1 200 CFM
G-2 100 CFM
G-2 100 CFM
16"x8"
VB-5-34 550 CFM
D-1 300 CFM
G-2 100 CFM
G-2 100 CFM
12"x8"
E1
F
12"x8"
26"x8"
VB-5-33 200 CFM
G-2 100 CFM
M500
VB-5-3 300 CFM 3/4"ø
1"ø
G-1 200 CFM 26"x8"
12"x8"
G-2 100 CFM
G-1 200 CFM
12"x8" VB-5-5 300 CFM 1 1/2"ø
1 1/2"ø
12"x8"
D-1 200 CFM
12"x8"
VB-5-6 300 CFM
G-2 100 CFM
VB-5-9 300 CFM D-1 200 CFM
VB-5-13 200 CFM 1"ø 1"ø D-1 100 CFM
D-1 100 CFM
G-1 125 CFM
3
D-1 200 CFM
2b
D-3 100 CFM
3c
D-3 100 CFM
D-3 100 CFM
3A
4 4a
D-3 100 CFM
PHASE 1
5
10229 ERIC G. SHERMAN U
T H
K D A
O
Description
Date
D-3 100 CFM
5.1
D-3 100 CFM
3 M500
D-3 100 CFM
16"x12"
26"x12" 6
4
M500 D-3 100 CFM
. NO.
12"x8"
2
D-1 200 CFM RAD-3
D-3 100 CFM
1c
22"x10"
12"x8"
VB-5-8 300 CFM
D-1 200 CFM
16"x12"
M500
1
12"x8"
G-1 200 CFM
G-1 200 CFM
4
F1
No.
G-2 100 CFM 20"x10"
12"x8" VB-5-7 300 CFM
D-1 200 CFM
D-1 200 CFM
REG
G-1 125 CFM
12"x8"
1"ø
10"x10"
G-2 100 CFM
22"x8"
VB-5-4 300 CFM
FESSION PRO AL
11/25/14
12"x8"
18"x10"
G-1 200 CFM
ED
TYP
16"x10"
G-1 200 CFM
12"x8"
VB-5-11 200 CFM
2
D-3 100 CFM
D-1 100 CFM
VB-5-10 200 CFM
3/4"ø
G-2 100 CFM
D-3 100 CFM
TYP
6
D-3 100 CFM
7
D-3 100 CFM
M501
B1.2 7
4 M500
FS.D.
M500
G-2 100 CFM
TYP
3/4" HWS/R CAPPED
D-1 100 CFM
G-1 125 CFM
5
E D-3 100 CFM
16"x8"
FS.D.
1"ø
10"x8" G-1 125 CFM
3/4"ø VB-5-32 200 CFM
1"ø
6"ø 6"ø STEAM RELIEF VENTS TO ROOF
D-1 100 CFM
R GINEE EN
10"x10"
G-1 125 CFM
G-1 125 CFM
22"x10"
12"x8"
16"x8"
12"x8"
O
D-1 100 CFM
G-2 100 CFM
S
D1
32"x12"
16"x12"
VB-5-31 200 CFM
D-1 100 CFM
D-3 100 CFM
1
D-3 100 CFM
10"x6"
D-3 100 CFM
99
VB-5-14 200 CFM 1"ø 1"ø
VB-5-30 200 CFM
D-1 100 CFM
G-1 125 CFM
12"x14"
1b
D-1 100 CFM
D-1 100 CFM
24"x10"
1"ø 1"ø 16"x12"
12"x8"
PHASE 3
D-3 100 CFM
32"x12"
16"x8"
D-1 100 CFM
14"x10" D-1 250 CFM
G-2 100 CFM
G-1 125 CFM
8"x6" G-1 125 CFM
D-3 100 CFM
D
3/4" HWS/R CAPPED
16"x8" G-1 125 CFM
12"x8"
D-3 100 CFM
12"x8"
18"x10" G-2 100 CFM
G-2 100 CFM
G-2 100 CFM 12"x8"
D-3 100 CFM
1
16"x8"
26"x8" RA
C1
VB-5-29 200 CFM
D-1 100 CFM
G-2 200 CFM
10"x10" VB-5-17 350 CFM
D-1 100 CFM
C
G-2 200 CFM
G-2 100 CFM
16"x8"
VB-5-18 300 CFM 12"x8"
G-1 200 CFM G-2 100 CFM
G-2 100 CFM
G-2 100 CFM
VB-5-19 300 CFM
12"x8"
26"x8" G-1 200 CFM
3/4"ø 3/4"ø VB-5-20 300 CFM
1"ø
VB-5-21 300 CFM
12"x8" G-2 6"x4" 100 CFM
D-1 200 CFM
A
12"x8"
G-1 125 CFM
1"ø
12"x8"
22"x8" D-3 100 CFM
D-1 200 CFM
G-2 100 CFM
1 1/2"ø
1 1/2"ø
D-1 200 CFM
REGIST ER
G-1 200 CFM
D-1 200 CFM
D-1 200 CFM
VB-5-12 200 CFM
B1.1
16"x12"
D-3 100 CFM
VB-5-27 200 CFM 1 1/2"ø 1 1/2"ø D-1 100 CFM
D-1 200 CFM
10"x10"
3
FS.D.
16"x12"
D-1 200 CFM
VB-5-16 200 CFM 3/4"ø 3/4"ø
18"x16"
FS.D.
4
26"x8"
FS.D.
B B.0
4 26" x 18" SA DUCT DOWN TO 4TH FLOOR.
T
A1
D-3 100 CFM
NOTE BACKGROUND IS SHOW CORRECTLY ON ARCHITECTURALS. FEILD VERIFY.
SACRED HEART
8
FIFTH LEVEL - HVAC AND PIPING 1/8" = 1'-0" 2014
C
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
4TH & 5TH FIFTH LEVEL - HVAC AND PIPING
Date
SES PROJECT # 14041
11/25/2014 4:38:02 PM
M151 Scale
1/8" = 1'-0"
AVERA FACILITY DEVELOPMENT
GENERAL NOTES
2.4
3.4
A. REFER TO MECHANICAL COVER SHEET M000 AND ELECTRICAL COVER SHEET E000 FOR GENERAL REQUIREMENTS, SYMBOLS, ABBREVIATIONS, AND MOUNTING ELEVATION REQUIREMENTS.
3.6
A1 B B.0 EF-1
1.7
2.1
8 M501
B1.1
C C1
FESSION PRO AL . NO.
10229 ERIC G. SHERMAN
O
U
A
S
D1
REG
T
ED
R GINEE EN
REGIST ER
D
T H
K D A
O
11/25/14
E
No.
Description
Date
E1 EF-2 8 M501
F F1
1 1
1c
2b
3c
3A
4 4a
5
5.1
6
B1.2 7
8
SACRED HEART
MECHANICAL ROOF PLAN 1/8" = 1'-0"
2014
C
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
4TH & 5TH MECHANICAL ROOF PLAN
Date
SES PROJECT # 14041
11/25/2014 4:38:04 PM
M161 Scale
1/8" = 1'-0"
AVERA FACILITY DEVELOPMENT
GENERAL NOTES
2.4
3.4
A. REFER TO MECHANICAL COVER SHEET M000 FOR GENERAL REQUIREMENTS, SYMBOLS, ABBREVIATIONS, AND MOUNTING ELEVATION REQUIREMENTS.
3.6
ELEVATOR LINK 4900
SHEET NOTES 1 CONNECT TO EXISTING PIPING SERVING REMOVED FIXTURE. 2 OFFSET EXISTING WASTE AND VENT STACK AND DOMESTIC WATER RISERS SERVING 5TH FLOOR TO EXISTING CHASE AS REQUIRED (TYPICAL PATIENT RESTROOM GROUPS). COORDINATE ROUTING OF PIPING WITH NEW AND EXISTING DUCTWORK.
PHASE 4
A1
4"ø V 4"ø SAN
B B.0
RESTROOM 418
2"ø SAN
OFFICE 462
B1.1
1.7
PATIENT RM 2400
PATIENT RM 402
PATIENT RM 2 404
2
PATIENT RM 408
PATIENT RM 2 410
2
PATIENT RM 412
PATIENT RM 2 414
2
2
1"ø CW
PATIENT RM 416
NEGATIVE AIR 420
1/2"ø
3/4"ø
1 1/2"ø
T
T
OFFICE 460 2
7&8
7&8
7&8
7&8
7&8
7&8
7&8
7&8
7&8
M500
M500
M500
M500
M500
M500
M500
M500
M500
PATIENT RM 422
2"ø V 2
MECH 459
C
2
2
2
2
2
2
2
2 RESTROOM 421
2
2
ELEC 534
T
T
6"ø ST UP/DN
2 RESTROOM 455
PHASE 3
OFFICE 537
TOILET 535
3/4"ø O 3/4"ø A 1 1/2"ø VAC
3/4"ø O 3/4"ø A 1 1/2"ø VAC
STORAGE 539
2
T
PHASE 2
2 CONFERENCE 546
LOCKER ROOM 547
5"ø ST
2
T
CLEAN UTILITY 541
SOILED 542
OMNI CELL 545
NUTRITION 543
T
ED
FESSION PRO AL
S O
D1 2
REG
. NO.
R GINEE EN
EQUIPMENT 540
5"ø ST UP/DN
WAITING ROOM 538
1 1/2"ø VAC 3/4"ø A 3/4"ø O
T
T
PATIENT RM 424
TOILET 548
1 1/2"ø VAC 3/4"ø A 3/4"ø O DN
DIET 544
2
DIRTY UTILITY 549
2
DN
5"ø ST UP/DN
CLEAN UTILITY 550
10229 ERIC G. SHERMAN U
A
HSKG 536
T
T
REGIST ER
C1
D
PATIENT RM 406 2
T H
K D A
O
2 11/25/14
E
2
2
2
2
3/4"ø 3/4"ø 1 1/2"ø
7&8 M500
E1
2
2
2
7&8
7&8
7&8
7&8
7&8
7&8
7&8
7&8
M500
M500
M500
M500
M500
M500
M500
M500
No.
1"ø HW
2
1"ø CW 1 1/2"ø CW 3/4"ø HW 4"ø4"ø SAN 2"ø 2"øV
Date
T
T
PATIENT RM 448
2
Description
2
ANTERIOR RM 450
T
F
2
2
2
2
PATIENT RM 446
PATIENT RM 444
2
2
PATIENT RM 442
2
PATIENT RM 440
2
PATIENT RM 438
2
PATIENT RM 436
PATIENT RM 434
T
2 PATIENT RM 432
RESTROOM 451
2"ø HW 2"ø V 2"ø CW STORAGE 2"ø V 431 4"ø SAN
2
RESTROOM 429
F1 PHASE 1
1 1
1c
2b
3c
3A
4 4a
5
5.1
6
B1.2 7
SACRED HEART
8
FOURTH LEVEL - PLUMBING AND MED GAS 1/8" = 1'-0"
2014
C
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
4TH & 5TH FOURTH LEVEL PLUMBING AND MED GAS Date
SES PROJECT # 14041
11/25/2014 4:38:12 PM
M241 Scale
1/8" = 1'-0"
1.3
2.4
3.4
3.6 AVERA FACILITY DEVELOPMENT
GENERAL NOTES
A
A. REFER TO MECHANICAL COVER SHEET M000 FOR GENERAL REQUIREMENTS, SYMBOLS, ABBREVIATIONS, AND MOUNTING ELEVATION REQUIREMENTS.
ELEVATOR LINK 5900
SHEET NOTES 1 REINSTALL EXISTING MEDICAL GAS OUTLETS IN ARCHITECTURAL HEADWALL. REFER TO ARCHITECTURAL HEADWALL ELEVATIONS FOR ARRANGEMENT AND DIMENSIONAL INFORMATION. PROVIDE ONE VACUUM SLIDE FOR EACH VACUUM OUTLET LOCATION. PROVIDE ADDITIONAL OUTLETS AS REQUIRED TO MEET QUANTITY SHOWN.
SH-1
L-1
SH-1
L-1
L-1
L-1
VS O
WC-2 5
FD-2 L-1
CORRIDOR 5901
SH-1
1
C
V
O
O
A
V
7&8
7&8
M500
M500
VS
WC-1
L-1
L-1
WC-1 FD-2
VS
FD-1 FD-1
WC-1 WC-1
4
V
O
O
A
V
VS
FD-2
SH-1
1
7&8
7&8
M500
M500
FD-1 FD-1 7&8 M500
WC-1
L-1
L-1
L-1
4
4 VS
FD-1
WC-1 WC-1
4
7&8
M500
M500 L-1
L-1
WC-1 WC-1
4
A
O
O
V
VS
SH-1
1 1/2"ø O 1"ø VAC 1/2"ø A
V
A
5
L-1
L-1
3 VALVES AND PIPING TO EXISTING MAINS SHALL BE DONE PRIOR TO BEGINNING DEMOLITION OF EXISTING MEDICAL GAS. COORDINATE CONNECTION TO EXISTING MAINS WITH PHASE 1 DEMOLITION WORK. WORK SHALL BE COORDINATING SUCH THAT ONE MEDICAL GAS CERTIFICATION IS REQUIRED.
SH-1
FD-2 7&8
7&8
M500
M500 2"ø V 4"ø SAN
4
WC-1
4
WC-1 2
2
5 CONNECT TO EXISTING PIPING SERVING REMOVED FIXTURE.
2"ø V
L-1 WC-1
L-1
L-1
4 ROUTE NEW VENT STACK TO EXISTING VENT THROUGH ROOF. COORDINATE ROUTE WITH OTHER UTILITIES.
3/4"ø O 1 1/4"ø VAC L-2 1/2"ø A
WC-1
FD-2
FD-2
2"ø V 4"ø SAN
1 1/2"ø SAN SH-1 2"ø SAN
1
VS
V
A
O
O
V
VS
VS
V
A
O
O
V
VS
2"ø SAN SH-1 1 1/2"ø SAN
1
4
C1
L-1
L-1
2"ø V L-2
L-2
5"ø ST UP/DN
L-1
O
O
A
V
VS
WC-1 4
VS
V
O
O
A
V
VS
FD-2
SH-1
1
3/4"ø O 3/4"ø A 1 1/2"ø VAC
WC-1
5"ø ST UP/DN
1 1/2"ø VAC 3/4"ø A 3/4"ø O DN
4"ø SAN WC-1
FD-2
1
VS
V
A
O
O
V
VS
VS
V
A
O
O
V
VS
PHASE 2
4 WC-1
4"ø SAN
FD-2
5"ø ST L-1
1 1/2"ø SAN SH-1 2"ø SAN
L-1
2"ø SAN SH-1
1
1 1/2"ø SAN 2"ø V
L-1 L-2
L-2
O
D1
S
L-2
FESSION PRO AL
L-1 SH-1
4
VS
V
A
O
M500 FD-1
M500 FD-1
VS
FD-2
V
SH-1
A
O
U
T H
K D A
O
11/25/14
O
V
VS
O
V
VS
No.
Description
Date
1
WC-1 7&8
L-1
M500 FD-2
L-2
L-1
SH-1
V
VS
O
1
V
O V
O
O
A
A
A O
1
O
1
L-1
V
V
VS A O O
SH-1
VS
SH-1 VS
L-1
VS
1
L-1
V
V
O
O
O
A
A
V
VS
1
1
SH-1 VS
SH-1
V
L-1
SH-1
O
L-1
V
V
1
WC-1
T
L-1
M500 FD-1
4
10229 ERIC G. SHERMAN
SH-1
VS
SH-1
A
A O
O
1/2"ø A
1
L-1
VS
VS
M500 FD-1
V
V
M500 FD-1
L-1 7&8 WC-1 WC-1 7&8
VS
A
L-1 7&8 WC-1 WC-1 7&8
V
O
5 WC-2
L-1
A
1"ø VAC 1/2"ø O
VS O
M500 FD-1
SH-1
V
V
5
1 1/2"ø CW 3/4"ø HW 4"ø SAN 2"ø V
VS
F
SH-1
4
L-1
V
L-1
5
L-1 7&8
L-1 L-1
1
SH-1
. NO.
1
VS
FD-2
SH-1
1/2"ø O 1"ø VAC 1/2"ø A
L-1
M500 FD-1
4
4 WC-1
7&8 WC-1 WC-1 7&8
M500
L-2 3/4"ø O 1 1/2"ø VAC 1/2"ø A
VS
4
L-1
7&8
L-1
2"ø V
1
4
WC-1 L-1
E1
3
V
FD-2
SH-1
1
3
4
WC-1
FD-2
O
VS
VS
WC-1
O
V
WC-1
O
A
VS
V
O
V
VS
O
A
VS
V
O
O
VS
O
O
E
V
V
VS
VS
FD-2
VS
1
L-1
REG
R GINEE EN
L-2
1/2"ø A 1 1/2"ø VAC 1/2"ø O
ED
A
V
2"ø V
T
VS
2"ø V
L-1
REGIST ER
FD-2
L-2
3/4"ø O 3/4"ø A 1 1/2"ø VAC DN
SH-1
1 PHASE 3
3/4"ø O 3/4"ø A 1 1/2"ø VAC
6"ø ST UP/DN
L-2
D
V
VS
SH-1
FD-1 FD-1 7&8
VS
L-1
B1.1 L-2
5
O
O V VS
SH-1
2 VALVES AND PIPING TO EXISTING MAINS SHALL BE DONE PRIOR TO BEGINNING DEMOLITION OF EXISTING MEDICAL GAS. COORDINATE CONNECTION TO EXISTING MAINS WITH PHASE 2 DEMOLITION WORK. WORK SHALL BE COORDINATING SUCH THAT ONE MEDICAL GAS CERTIFICATION IS REQUIRED.
V
V
1
A
V
A
SH-1
1
O
V O O
O A V VS
SH-1
VS
VS
VS
1
O
V O O V VS
A
L-1
SH-1
1
V
VS
VS O O VS
V
A
A V VS
1
V
VS O
O O A
L-1
V
VS
L-1
SH-1
VS
2.1 V
1.7
1
O
V
V O O A
OFFICE 5902
1
V
VS
VS
B B.0
1
1
VS
PHASE 4
A1
F1 PHASE 1
1 1
1c
2b
3c
3A
4 4a
5
5.1
6
B1.2 7
SACRED HEART
8
FIFTH LEVEL - PLUMBING AND MED GAS 1/8" = 1'-0" 2014
C
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
4TH & 5TH FIFTH LEVEL PLUMBING AND MED GAS Date
SES PROJECT # 14041
11/25/2014 4:38:21 PM
M251 Scale
1/8" = 1'-0"
1.3
2.4
3.4
3.6 AVERA FACILITY DEVELOPMENT
GENERAL NOTES
A
A. REFER TO MECHANICAL COVER SHEET M000 FOR GENERAL REQUIREMENTS, SYMBOLS, ABBREVIATIONS, AND MOUNTING ELEVATION REQUIREMENTS. B. REFER TO ARCHITECTURAL CEILING PLANS FOR CEILING LAYOUT.
PHASE 4
A1
AREA DESIGN REQUIREMENTS
B B.0 1
1
1
1
1
1
1
1
1
1
SPR-3 1 SPR-3
1
1.7
2.1
MARK
CLASSIFICATION
COVERAGE DENSITY
1
LIGHT HAZARD
0.10 GPM OVER 1500 SQ. FT.
2
ORDINARY HAZARD GROUP 1
0.15 GPM OVER 1500 SQ. FT.
3
ORDINARY HAZARD GROUP 2
0.20 GPM OVER 1500 SQ. FT.
B1.1 1
1
1
1
1
1
1
1
1
1
1
FIRE SPRINKLER HATCHING LEGEND
1 1
C
EXISTING SPRINKLER COVERAGE TO REMAIN 1
1
EXISTING SPRINKLER SYSTEM TO BE REVISED TO ACCOMMODATE NEW WORK
1
1
C1
F
FLOW SWITCH
FIRE SPRINKLER FINISH LEGEND ALL SPRINKLERS SHALL BE RECESSED, CHROME PLATED UNLESS NOTED OTHERWISE. SPR-1 CONCEALED, WHITE 1
6"ø F 1 1 PHASE 3
CONCEALED, BRUSHED COPPER
SPR-3
CONCEALED, GASKETED, WHITE
SPR-4
CONCEALED, MRI RATED, WHITE
SPR-5
UPRIGHT, ROUGH BRONZE, PROTECTIVE WIRE CAGE
PHASE 2 1
1 1
1
O
D1
FESSION PRO AL REG
. NO.
10229 ERIC G. SHERMAN U
A
S
1
ED
R GINEE EN
REGIST ER
6"ø F
T
D
1
SPR-2
T H
K D A
O
1 11/25/14
1
1
E
No.
Description
Date
1
1
1
1 1
1
1
1
1
1
1
1
1
E1
1 1
SPR-3
SPR-3 1
1
1
1
1
1
1
1
1
1
1
1
SPR-3
F W
F F1 PHASE 1
1b 1
99
1
1c
2b
3c
3A
4 4a
5
5.1
6
B1.2 7
SACRED HEART
8
FIFTH LEVEL FIRE PROTECTION 1/8" = 1'-0"
2014
C
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
4TH & 5TH FIFTH LEVEL - FIRE PROTECTION
Date
SES PROJECT # 14041
11/25/2014 4:38:28 PM
M351 Scale
1/8" = 1'-0"
WALL OPENING SHALL BE 1/8" LARGER THAN DAMPER PER LINEAR FOOT IN HEIGHT AND WIDTH. (NOT LESS THAN 1/4" LARGER.)
WALL
MAIN RETURN AIR DUCT
MAIN SUPPLY AIR DUCT
BREAKAWAY CONNECTION
ACOUSTIC LINING WHERE INDICATED
AVERA FACILITY DEVELOPMENT
INSULATION WHEN DUCT IS LINED OR WRAPPED. (ALL AROUND DUCT ON BOTH SIDES OF WALL.)
DUCTWORK AIR FLOW AIR FLOW SUPPLY DUCT COLLAR FLEX DUCT
FUSIBLE LINK
MAX. 5'-0" 45°
FLEX DUCT SIZE SHALL MATCH NECK SIZE
*
HIGHEFFICIENCY TAKE-OFF
HIGHEFFICIENCY TAKE-OFF L.P. BRANCH DUCT HAND VOLUME DAMPER
SLEEVE THRU WALL. EXTEND SLEEVE 3" MIN. TO 6" MAX. ON THIS SIDE OF WALL
*
45°
*-EQUALS WIDTH OF BRANCH DUCT UP TO 12" 12" FOR ALL BRANCH DUCTS LARGER THAN 12"
CEILING
SUPPLY AIR
CEILING DIFFUSER
TYPICAL DIFFUSER CONNECTION DETAIL
3
2
NONE
OPERATING SPRING SLEEVE THRU WALL. EXTEND SLEEVE 3" MIN. TO 16" MAX. ON ACCESS DOOR SIDE OF WALL.
RETURN AIR BRANCH DUCT
SEE SPECIFICATIONS FOR CONNECTION
DUCTWORK
HAND VOLUME DAMPER 1 1/2" x 1 1/2" MINIMUM 14 GAUGE ANGLE ON ALL SIDES OF OPENING AND BOTH SIDES OF WALL. ANGLES SHALL OVERLAP OPENING BY 1" MINIMUM AND COVER CORNERS OF OPENING
HAND DAMPER OPPOSED BLADE DAMPER
AIR FLOW
*-EQUALS WIDTH OF BRANCH DUCT UP TO 12" 12" FOR ALL BRANCH DUCTS LARGER THAN 12"
ANCHOR DAMPER AND ANGLES TO SLEEVE IN ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS. DO NOT FASTEN ANGLES TO WALL.
EXHAUST/RETURN AIR
TYPE "B"
TYPICAL BRANCH DUCT TAKE-OFF DETAIL
1
NONE
NOTE: PROVIDE ACCESS DOORS FOR ALL FIRE DAMPERS AND LABEL WITH 1/2" HIGH LETTERING "FIRE DAMPER".
FIRE DAMPER THROUGH WALL DERTAIL NONE
INSULATE RADIANT CEILING PANEL WITH 3" FIBERGLASS INSULATION WITH FOIL SKRIM FACING UP. OVERLAP ALL SIDES AT LEAST THREE INCHES. SUPPORT INDEPENDENTLY FROM CEILING (TYP.)
3" MINIMUM
WALL OPENING SHALL BE 1/8" LARGER THAN DAMPER PER LINEAR FOOT IN HEIGHT AND WIDTH. (NOT LESS THAN 1/4" LARGER.)
3" MINIMUM WALL OR FLOOR.
1
1
INSULATION WHEN DUCT IS LINED OR WRAPPED. (ALL AROUND DUCT ON BOTH SIDES OF WALL.)
1/2" DEEP 10 GAUGE MINIMUM GALVANIZED CHANNEL IF DUCT IS TIGHT TO STRUCTURE.
METAL NOSING. (IF DUCT IS LINED.)
CROSS CHANNEL BRACE
NORMALLY CLOSED ELECTRIC OPERATOR AND LINKAGE OUTSIDE OF AIRSTREAM. BREAKAWAY CONNECTION TILE
TILE
PANEL PIPING
NOTE: PROVIDE ACCESS DOORS FOR ALL FIRE AND SMOKE DAMPERS. LABEL WITH 1/2" HIGH LETTERING:
WALL ANGLE MOLDING
"FIRE/SMOKE DAMPER"
CEILING GRID "T" VARIES
WIRING BY A.T.C. A.T.C. SHALL PROVIDE TRANSFORMER IF REQUIRED.
ANCHOR DAMPER AND ANGLES TO SLEEVE IN ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS. DO NOT FASTEN ANGLES TO WALL.
NONE
O
RADIANT CEILING PANEL DETAIL
REG
. NO.
10229 ERIC G. SHERMAN U
T H
K D A
O
ARD
1-1/2" x 1-1/2" MINIMUM 14 GAUGE ANGLE ON ALL SIDES OF OPENING AND BOTH SIDES OF WALL. ANGLES SHALL OVERLAP OPENING BY 1" MINIMUM AND COVER CORNERS OF OPENING.
ROUTE NEW VENT STACK TO EXISTING VENT THROUGH ROOF. COORDINATE ROUTE WITH OTHER UTILITIES.
FESSION PRO AL
S
6
INSULATE RADIANT PANEL WITH 3" FIBERBLASS INSULATION WITH FOIL SKRIM FACING UP. OVERLAP ALL SIDES AT LEAST THREE INCHES.
ED
R GINEE EN
1
TO FIRE SMOKE DAMPERS AS REQUIRED.
M
A
NOTE:
T
SLEEVE THRU WALL. EXTEND SLEEVE 3" MIN. TO 6" MAX. ON THIS SIDE OF WALL.
REGIST ER
24" GRID CEILING OPENING
SLEEVE THRU WALL. EXTEND SLEEVE 3" MIN. TO 16" MAX. ON ACTUATOR SIDE OF WALL.
11/25/14 WIRING BY E.C.
TEMPERATURE CONTROLS RELAY
No.
Description
Date
4"ø V JUNCTION BOX BY E.C.
1 1/2"ø V
NOTES: 1. CONNECTION OF DAMPER TO SLEEVE SHALL BE AS SHOWN IN FIGURE 1 OF SMACNA "FIRE DAMPER AND HEAT STOP GUIDE FOR AIR HANDLING SYSTEMS", SECOND EDITION.
1 1/2"ø V 2 1/2"ø V
SH-1
1/2"ø CW 1/2"ø HW
SH-1
2 1/2"ø V L-(1)(2)
L-1
L-(1)(2)
DAMPER CLOSES BY SPRING ACTION IN EVENT OF HIGH TEMPERATURE.
3.
FLOOR MOUNTED DAMPER SIMILAR WITH ACTUATOR ON SIDE WITH ACCESS DOOR.
4.
WHERE DUCT SMOKE DETECTORS CANNOT BE ACCESSED BY THE DAMPER ACCESS DOOR THE ELECTRICAL CONTRACTOR SHALL FURNISH A DUCT ACCESS DOOR FOR THE DETECTOR. THE MECHANICAL CONTRACTOR SHALL INSTALL THE DOOR IN THE DUCT.
5.
SEE SMOKE DAMPER CONTROLLER SCHEMATIC DETAIL ON ELECTRICAL DRAWINGS FOR WIRING DETAILS. A.T.C. SHALL PROVIDE RELAYS TO CLOSE FIRE SMOKE DAMPERS IN NON-FIRE EVENTS. REFER TO ELECTRICAL DRAWINGS FOR LOCATIONS.
L-1
1 1/2"ø CW WC-1 1"ø CW 1"ø HW
2. 1 1/2"ø V
WC-1
FD-(1)(2)
FD-(1)(2)
4
COMBINATION FIRE AND SMOKE DAMPER THROUGH WALL DERTAIL NONE
MAINTAIN MIN. 3 DUCT DIAMETERS OF STRAIGHT RIGID DUCT MATCHING INLET SIZE
NOTE: REFER PLUMBING FIXTURE SCHEDULE FOR PIPE SIZES TO INDIVIDUAL FIXTURES
4"ø SAN
HI-EFFICIENCY DUCT TAKEOFF
AIR TERMINAL UNIT BUILT WITH INSULATED FIBER FREE LINER
1 1/2"ø V
SACRED HEART
FLOW SENSOR GRID VAV CONTROLLER BY CONTROLS CONTRACTOR
4TH & 5TH MECHANCIAL DETAILS
AUTOMATIC FLOW CONTROL VALVE NOTE: REFER PLUMBING FIXTURE SCHEDULE FOR PIPE SIZES TO INDIVIDUAL FIXTURES
1 1/2"ø CW
REHEAT COIL
2014 BALL VALVE (TYP)
2"ø SAN
UNOBSTRUCTED ACCESS LOCATED AT ACCESS PANEL OR ABOVE CEILING TILE
STRAINER WITH BLOW-DOWN VALVE 2-WAY CONTROL VALVE UNION WITH P/T PLUG
7
DOMESTIC WATER ISOMETRIC NONE
8
WASTE AND VENT ISOMETRIC NONE
5
C
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS.
TERMINAL UNIT DETAIL
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520
NONE www.specializedeng.com
Date
SES PROJECT # 14041
11/25/2014 4:38:31 PM
M500 Scale
NONE
FULL SIZE CONDENSATE DRAIN, CONNECT TO DRAIN PAN AS RECOMMENDED BY MANUFACTURER.
RISER CLAMP
INSTALL CLAMP ON ALL PIPES LESS THAN 4"Ø
CLEANOUT PLUG (TYP.)
THREADED ROD CLEVIS HANGER INSULATION
PIPE INSULATION. (TYP.)
INSULATION AND NEOPRENE MOUNTS.
THREADED ROD. (TYP.)
INSULATION HIGH DENSITY INSULATION INSERT.
HIGH DENSITY INSULATION INSERT. H
INSULATION SHIELD. (TYP.)
1
H/2
OVERSIZE HANGER TO ALLOW LONGITUDINAL PIPE EXPANSION AND PIPE INSULATION TO PASS THROUGH UNBROKEN. (TYP.)
UNI-STRUT OR EQUIVALENT
TRAPEZE HANGER ROUTE DIRECTLY ABOVE FLOOR DRAIN
LUG, COUPLING, OR HUB
STRUT CLAMP HANGERS
INSULATION SHIELD
CLEVIS HANGER
AVERA FACILITY DEVELOPMENT
FLOOR
STEEL PIPE SADDLE, TACK WELDED TO PIPE, FILL SADDLE WITH INSULATION.
INSULATION
ROLLER SUPPORT
VERTICAL PIPE SUPPORT
PIPE SUPPORT DETAIL NONE
NOTE: 1. FOR DRAW-THROUGH SYSTEMS, DIMENSION FOR EVERY UNIT. H= FAN INLET PRESSURE (IN W.C.) + 1 INCH. (2" MIN.)
WALL WITH INSULATION SUPPORT
2
CONDENSATE TRAP DETAIL (NEGATIVE PRESSURE SECTION) NONE
FLANGES ON EACH SIDE OF WALL. CAULK AT WALL AND SLEEVE.
PACK AROUND PIPE WITH FIBERGLASS INSULATION
4" TO 8"
CLEANOUT PLUG (TYP.)
FULL SIZE CONDENSATE DRAIN, CONNECT TO DRAIN PAN AS RECOMMENDED BY MANUFACTURER.
ESCUTCHEON PLATES ON BOTH SIDES
TYP. ON BOTH SIDES
PIPE
1" +/- 1/4" 1/4" FOR ITEMS LESS THAN 4"
SHEET METAL SLEEVE, 2" LARGER THAN PIPE OVERALL DIAMETER.
PENETRATING ITEM
H
ESCUTCHEON (TYP. ON BOTH SIDES.)
12" ROUTE DIRECTLY ABOVE FLOOR DRAIN
ACOUSTICAL SEALANT FOAM BACKER ROD SLEEVE
SAFING BATT INSULATION
NOT REQUIRED FOR ITEMS LESS THAN 4" DIAMETER
WALL
NOTE: 1. FOR BLOW-THROUGH SYSTEMS, DIMENSION FOR EVERY UNIT. H= FAN OUTLET PRESSURE (IN W.C.) + 1 INCH. (2" MIN.)
CONDENSATE TRAP DETAIL (POSITIVE PRESSURE SECTION) NONE
NOTES: 1. THIS DETAIL APPLIES TO ALL PIPES. THE INTENTIONS ARE TO CONTINUE THE INSULATION AND VAPOR BARRIER THROUGH ALL PENETRATIONS, PERMIT THERMAL EXPANSION WITHOUT DAMAGING THE INSULATION, AND SEAL AIRTIGHT AROUND INSULATED AND UNINSULATED PIPES FOR NOISE TRANSMISSION CONTROL.
REGIST ER
NONE
FESSION PRO AL
S O
FULL SIZE BYPASS WITH MANUAL THROTTLING VALVE
FULL SIZE BYPASS WITH MANUAL THROTTLING VALVE 2-WAY MODULATING VALVE (TYP)
. NO.
10229 ERIC G. SHERMAN U
T H
K D A
O
11/25/14
2-WAY MODULATING VALVE (TYP)
ISOLATION VALVE (TYP)
REG
R GINEE EN
3
NOISE CONTROL WALL PENETRATION DETAIL
ED
A
2. METHODS THAT ARE LISTED FOR THE REQUIRED HOURLY RATINGS MUST BE USED FOR FIRE RATED WALLS. ALL OF THE INTENTIONS IN NOTE 1 MUST BE MET BY THE SYSTEM SELECTED.
T
4
CONCRETE/MASONARY WALL CONSTRUCTION
GYPSUM WALL CONSTRUCTION
No.
Description
Date
ISOLATION VALVE (TYP)
AIRFLOW
MANUAL AIR VENT (TYP)
PIPE WELLS FOR CONTROLS (TYP)
ROOF FAN HEATING COIL
SECURE FAN BASE TO CURB MIN. 2 LOCATIONS EACH SIDE AND ON 6" CENTERS FOR CURBS OVER 18"x18"
STRAINER WITH BLOW-DOWN VALVE (TYP)
MANUAL AIR VENT (TYP)
PIPE WELLS FOR CONTROLS (TYP)
STRAINER WITH BLOW-DOWN VALVE (TYP)
COOLING COIL AUTOFLOW BALANCING VALVE
AUTOMATIC BALANCING VALVE INTERMEDIATE DRAIN PAN MANUAL AIR VENT (TYP)
MANUAL AIR VENT (TYP)
P/T PLUG (TYP) CONDENSATE DRAIN PIPE. REFER TO PIPING MATERAL SCHEDULE AND SPECIFICATIONS FOR MATERIAL REQUIREMENTS
HEATING COIL
EXISTING FAN CURB
3/4 DRAIN VALVE (TYP) 12" MIN.
SEE SPECIFICATIONS/ SCHEDULE FOR DAMPER TYPE
8
UNION WITH P/T PLUG (TYP)
6
AHU HEATING COIL PIPING DETAIL
5
NONE
P/T PLUG (TYP)
COOLING COIL 3/4 DRAIN VALVE (TYP) PRIMARY DRAIN PAN
UNION WITH P/T PLUG (TYP)
AHU COOLING COIL PIPING DETAIL NONE
SACRED HEART
Exhaust Fan Detail
4TH & 5TH MECHANICAL DETAILS
STRAINER
NONE
3/4" HWS TO RADIANT PANEL 2014
AUTOFLOW VALVE 3/4" HWR FROM RADIANT PANEL 2-WAY CONTROL VALVE
7
C
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520
RADIANT PANEL CONNECTION DETAIL
Date
SES PROJECT # 14041
M501
NONE www.specializedeng.com
11/25/2014 4:38:32 PM
Scale
NONE
CONTROL VALVE FOR BMS SHUTOFF DUCTWORK OR IN UNIT AS SHOWN ON PLAN
AVERA FACILITY DEVELOPMENT
RETURN DISPERSION TUBE DISCHARGE AGAINST AIRFLOW. MANUAL AIR VENT (TYP)
UNION (TYP.) DRIP TRAP
PLATE AND FRAME HEAT EXCHANGER SUPPLY CONTROL VALVE ISOLATION VALVE
HUMIDIFIER SEPARATOR
AIR FLO W
2-WAY MODULATING VALVE (TYP).
HOUSEKEEPTING PAD THERMOMETER (TYP) UNION (TYP) PTT PORT (TYP)
PROVIDE MULTIPLE TUBES AND MANIFOLD IF REQUIRED TO SUPPLY CAPACITY SPECIFIED.
DRAIN (TYP) PIPE WELLS FOR CONTROLS (TYP)
TRAP FURNISHED WITH HUMIDIFIER
FULL SIZE DIRT LEG 10" LONG. (TYP.)
PRESSURE GAUGE (TYP)
TEMPERATURE SWITCH FURNISHED WITH HUMIDIFIER.
RETURN
NONE
1
HUMIDIFIER DETAIL (DIRECT INJECTION) NONE
FESSION PRO AL REG
. NO.
R GINEE EN
ED
S
10229 ERIC G. SHERMAN
O
U
A
PLATE AND FRAME HEAT EXCHANGER CONNECTION DETAIL
REGIST ER
2
T
SUPPLY
T H
K D A
O
11/25/14
No.
Description
Date
SACRED HEART
2014
C
4TH & 5TH MECHANICAL DETAILS
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
Date
SES PROJECT # 14041
11/25/2014 4:38:33 PM
M502 Scale
NONE
SECTION 23 73 13 2.4 FAN SECTION A. Fan-Section Construction: Belt-driven centrifugal fans consisting of housing, wheel, fan shaft, bearings, motor and disconnect switch, drive assembly, and support structure and equipped with formed-steel channel base for integral mounting of fan, motor, and casing panels. Mount fan with spring vibration isolation. B. Centrifugal Fan Housings: Formed- and reinforced-steel panels to make curved scroll housings with shaped cutoff, spun-metal inlet bell, and access doors or panels to allow entry to internal parts and components. 1. Panel Bracing: Steel angle- or channel-iron member supports for mounting and supporting fan scroll, wheel, motor, and accessories. 2. Performance Class: AMCA 99-2408, all Classes. 3. Horizontal Flanged Split Housing: Bolted construction. 4. Plug Fans: With steel cabinet. Fabricate without fan scroll and volute housing. C. Fan Assemblies: Statically and dynamically balanced and designed for continuous operation at maximum rated fan speed and motor horsepower. D. Airfoil-Fan Wheels: Steel construction with smooth-curved inlet flange, heavy backplate, and hollow die-formed airfoil-shaped blades continuously welded at tip flange and backplate; cast-iron or cast-steel hub riveted to backplate and fastened to shaft with set screws. E. Shafts: Statically and dynamically balanced and designed for continuous operation at maximum rated fan speed and motor horsepower, with final alignment and belt adjustment made after installation. 1. Turned, ground, and polished hot-rolled steel with keyway. Ship with a protective coating of lubricating oil. 2. Designed to operate at no more than 70 percent of first critical speed at top of fan's speed range. F. Grease-Lubricated Shaft Bearings: Self-aligning, pillow-block-type, ball or roller bearings with adapter mount and two-piece, cast-iron housing. 1. Ball-Bearing Rating Life: ABMA 9, L10 of 100,000 hours. 2. Roller-Bearing Rating Life: ABMA 11, L10 of 100,000 hours. G. Vibration Control: Install fans on open-spring vibration isolators having a minimum of 1-inch static deflection and side snubbers. H. Fan-Section Source Quality Control: 1. Sound Power Level Ratings: Comply with AMCA 301, "Methods for Calculating Fan Sound Ratings from Laboratory Test Data." Test fans according to AMCA 300, "Reverberant Room Method for Sound Testing of Fans." Fans shall bear AMCA-certified sound ratings seal. 2. Factory test fan performance for flow rate, pressure, power, air density, rotation speed, and efficiency. Establish ratings according to AMCA 210, "Laboratory Methods of Testing Fans for Rating." 2.5 MOTORS A. Motors shall be NEMA Design B; T -FRAME mounted on an adjustable steel base. All motors shall be tested to IEEE standard 112 test method B and rated per NEMA MG1, Part 31 "Inverter Fed Motors, premium efficiency. All motors shall be specifically designed to meet or exceed all (EPAct) requirements for energy efficiency and include Class F insulation. Motors shall be as manufactured by Baldor, Toshiba, Reliance, or equal. All motors shall include shaft grounding: Aegis or equal. Provide NEMA premium efficiency motors. 2.6 COILS A. Coil Sections: Common or individual, insulated, stainless steel casings for cooling and galvanized steel casings for heating. Design and construct to facilitate removal and replacement of coil for maintenance and to ensure full airflow through coils. B. Water Coils: Self-draining coil fabricated according to ARI 410. 1. Piping Connections: Threaded, on same end, Red Brass. 2. Tubes: Copper. 3. Fins: Aluminum. 4. Headers: Carbon-steel with drain and air vent tappings. 5. Frames: Galvanized-steel channel frame for heating coils, 0.052 inch. 6. Frames: Stainless steel, 0.0625 inch for cooling coils. 7. Ratings: Design tested and rated according to ASHRAE 33 and ARI 410. a. Working-Pressure Ratings: 200 psig, 325 deg F. 8. Source Quality Control: Test to 300 psig and to 200 psig underwater. 2.7 DAMPERS A. General: Leakage rate, according to AMCA 500, "Laboratory Methods for Testing Dampers for Rating," shall not exceed 2 percent of air quantity at 2000-fpm face velocity through damper and 4-inch wg pressure differential. B. Supply and Return Isolation Dampers: Heavy-duty steel assembly with channel frame and sealed ball bearings, and parallel blades constructed of two plates formed around and welded to shaft, with blades linked out of airstream to single control lever. Install on supply and return duct openings of unit. C. Low-Leakage, Outdoor-Air and Relief-Air Dampers: Double-skin, airfoil-blade galvanized-steel dampers with compressible jamb seals and extruded-vinyl blade edge seals, in opposed-blade arrangement with steel operating rods rotating in stainless-steel sleeve bearings mounted in a single galvanized-steel frame, and with operating rods connected with a common linkage. Leakage rate shall not exceed 5 cfm/sq. ft. at 1-inch wg and 9 cfm/sq. ft. at 4-inch wg. D. Mixing Boxes: Parallel-blade galvanized-steel dampers mechanically fastened to steel operating rod in reinforced, galvanized-steel cabinet. Connect operating rods with common linkage and interconnect linkages so dampers operate simultaneously. E. Provide damper actuators for all dampers listed above, including supply, return, outdoor, relief, and mixing dampers. F. Provide backdraft dampers on fan inlet on units with multiple fans in parallel. 2.8 FILTER SECTION A. Filters: Comply with NFPA 90A. B. Filter Section: Provide filter holding frames arranged for flat or angular orientation, with access doors on both sides of unit. Filters shall be removable from one side. C. Extended-Surface, Disposable Panel Filters: Factory-fabricated, dry, extended-surface filters with holding frames. 1. Media: Fibrous material formed into deep-V-shaped pleats and held by self-supporting wire grid. 2. Media and Media-Grid Frame: Nonflammable cardboard. 3. Duct-Mounting Frames: Welded, galvanized steel with gaskets and fasteners, suitable for bolting together into built-up filter banks. D. Final Filters: Factory-fabricated filters with holding casing. 1. Media: UL 586, fibrous glass, constructed of continuous sheets with closely spaced pleats with aluminum separators. 2. Frame Material: Aluminum. 3. Media to Frame Side Bond: Neoprene adhesive. 4. Face Gasket: Neoprene expanded rubber. 5. Duct-Mounting Frames: Construct downstream corners of holding device with cushion pads to protect media. Provide bolted filtersealing mechanism to mount and continuously seal each individual filter. 2.9 BLANK SECTIONS A. Provide an 18 inch blank section for future humidifier grid. Provide knock out holes in cabinet to accept future humidifier grid. 2.10 ELECTRICAL A. Fan Motors 1. Each fan motor shall be separately wired to a junction box mounted on the outside of the unit. Wiring shall include separate ground for each motor. 2. VFDs will be furnished and installed by the Temperature Controls Contractor. B. Lighting Circuits 1. Each section shall be provided with a vapor proof LED light fixture with a guard and mounted not to interfere with service including filter replacement. Wiring shall include separate ground for each motor. 2. All lighting rigid, not flexible, conduit to be installed by manufacturer and terminated to a switch location at the front of the unit. Provide empty junction box next to switch for receptacle furnished and installed by Electrical Contractor. 3. Wiring sizing shall be determined, and installed, in accordance with applicable NEC standard. 4. Furnish small flexible metal conduit splices for Electrical Contractor to install at shipping splits for lighting circuit. C. UV Lights 1. All UV lights shall be separately wired to a junction box mounted on the outside of the unit. Wiring shall include separate ground for each motor. 2. VFDs will be furnished and installed by the Temperature Controls Contractor. D. Duct Detectors 1. Duct smoke detectors for supply and return sections will be furnished and installed by AHU manufacturer. Electrical Contractor will wire up to detectors for fire alarm interface.
2.11 ULTRAVIOLET LIGHTS A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Steril-aire. 2. UV Resources. 3. Ultraviolet Devices, Inc. B. Provide UV-C emitters/lamps downstream of all cooling coils and above all drain pans to control airborne and surface microbial growth and transfer. C. Lamps shall be manufactured, selected, and installed specific for the unit. Provide all safety interlocks including on/off switch(es), external fusing, ETL listing to UL 1598, and lamp monitor. D. Voltage shall be 120V. Electrical wiring shall be separately wired to a junction box mounted on the outside of the unit. Furnish and install separate disconnect and associated wiring outside of each applicable section. E. Provide UV protected glass in applicable sections for access doors with integral window PART 3 - EXECUTION 3.1 EXAMINATION A. Examine areas and conditions for compliance with requirements for installation tolerances and other conditions affecting performance. B. Examine roughing-in of steam, hydronic, and condensate drainage piping systems and electrical services to verify actual locations of connections before installation. C. Proceed with installation only after unsatisfactory conditions have been corrected. 3.2 FIELD TESTING A. Field-Leak Testing. The Mechanical Contractor shall provide a field leak test on units at 1.5 times design total static pressure (minimum 8 inches w.g.) across the cabinet exterior walls and L/240 deflection at 8 inch w.g. Cabinet leakage is not to exceed 1 percent of specified airflow on the operating side of the unit. A written test report shall be prepared by the Mechanical Contractor submitted for review by the Engineer prior to placement into service, and be included with the operation and maintenance manual. 3.3 FIELD QUALITY CONTROL A. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect field-assembled components and equipment installation, including piping and electrical connections. Report results in writing. 1. Leak Test: After installation, fill water and steam coils with water and test coils and connections for leaks. Repair leaks and retest until no leaks exist. 2. Fan Operational Test: After electrical circuitry has been energized, start units to confirm proper motor rotation and unit operation. Remove malfunctioning units, replace with new units, and retest. 3. Final Filter Operational Test: Pressurize housing to a minimum of 3-inch wg or to designed operating pressure, whichever is higher; test housing joints, door seals, and sealing edges of filter for air leaks according to ASME N510, pressure-decay method. 4. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment. 3.4 STARTUP SERVICE A. Engage a factory-authorized service representative to perform startup service. B. Final Checks before Startup: Perform the following: 1. Verify that shipping, blocking, and bracing are removed. 2. Verify that unit is secure on mountings and supporting devices and that connections to piping, ducts, and electrical systems are complete. Verify that proper thermal-overload protection is installed in motors, starters, and disconnect switches. 3. Perform cleaning and adjusting specified in this Section. 4. Disconnect fan drive from motor, verify proper motor rotation direction, and verify free fan wheel rotation and smooth bearing operations. Reconnect fan drive system, align belts, and install belt guards. 5. Lubricate bearings, pulleys, belts, and other moving parts with factory-recommended lubricants. 6. Set face-and-bypass dampers to full face flow. 7. Comb coil fins for parallel orientation. 8. Install clean filters. C. Starting procedures for modular indoor air-handling units include the following: 1. Energize motor; verify proper operation of motor, drive system, and fan wheel. Adjust fan to indicated rpm. Replace fan and motor pulleys as required to achieve design conditions. 2. Measure and record motor electrical values for voltage and amperage. 3. Manually operate dampers from fully closed to fully open position and record fan performance. 3.5 DEMONSTRATION A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain modular indoor air-handling units. END OF SECTION 23 73 13
HUM-10
5
FESSION PRO AL REG
. NO.
U
A
10229 ERIC G. SHERMAN
T
O
MARK
ED
R GINEE EN
REGIST ER
FOR REFERENCE ONLY
T H
K D A
O
11/25/14
STEAM FLOW [#/HR]
DISPERSION TUBE SPACING [IN]
MAXIMUM NOT-WETTING DISTANCE [IN]
CASING DIMENSIONS (WxH) [IN]
MAXIMUM PRESSURE DROP [IN.W.C.]
108
12
24
86x94
0.01
No.
FILTER SCHEDULE
STEAM HUMIDIFIER SCHEDULE STEAM PRESSURE IN [PSIG]
AVERA FACILITY DEVELOPMENT
S
MODULAR INDOOR AIR-HANDLING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. This Section includes variable-volume, modular air-handling units with coils for indoor installations. 1.3 SUBMITTALS A. Product Data: For each type of modular indoor air-handling unit indicated. Include the following: 1. Certified fan-performance curves with system operating conditions indicated. 2. Certified fan-sound power ratings. 3. Certified coil-performance ratings with system operating conditions indicated. 4. Motor ratings, electrical characteristics, and motor and fan accessories. 5. Material gages and finishes. 6. Filters with performance characteristics. 7. Dampers, including housings, linkages, and operators. 8. Ultraviolet lights. B. Shop Drawings: Signed and sealed by a qualified professional engineer. 1. Design Calculations: Calculate requirements for selecting vibration isolators and seismic restraints and for designing vibration isolation bases. 2. Vibration Isolation Base Details: Detail fabrication including anchorages and attachments to structure and to supported equipment. Include auxiliary motor slides and rails, and base weights. 3. Wiring Diagrams: Power, signal, and control wiring. C. Field Quality-Control Test Reports: From manufacturer. 1.4 QUALITY ASSURANCE A. Source Limitations: Obtain modular indoor air-handling units through one source from a single manufacturer. B. Product Options: Drawings indicate size, profiles, and dimensional requirements of modular indoor air-handling units and are based on the specific system indicated. Refer to Division 01 Section "Product Requirements." C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use. D. NFPA Compliance: Modular indoor air-handling units and components shall be designed, fabricated, and installed in compliance with NFPA 90A, "Installation of Air Conditioning and Ventilating Systems." E. ARI Certification: Modular indoor air-handling units and their components shall be factory tested according to ARI 430, "Central-Station AirHandling Units," and shall be listed and labeled by ARI. F. Comply with NFPA 70. 1.5 EXTRA MATERIALS A. Furnish extra materials described below that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. 1. Filters: One set for each modular indoor air-handling unit, to be installed at time of project completion. 1.6 WARRANTY A. Air Handling Unit Warranty: Manufacturer's standard form in which manufacturer agrees to replace any component of AHUs that fail in materials or workmanship within specified warranty period. 1. Warranty Period: Manufacturer's standard, but not less than two years from date of shipment from factory. PART 2 - PRODUCTS 2.1 MANUFACTURERS A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Carrier. 2. Daikin/McQuay. 3. Huntair. 4. Trane. 2.2 MANUFACTURED UNITS A. Modular indoor air-handling units shall be factory assembled and consist of fans, motor and drive assembly, coils, dampers, plenums, filters, condensate pans, mixing dampers, dehumidification wheels, and ultraviolet lights. 2.3 CABINET A. Materials: Formed and reinforced double-wall insulated panels, fabricated to allow removal for access to internal parts and components, with joints between sections sealed. 1. Outside Casing: Galvanized steel, 0.0299 inch or 22 gauge thick. 2. Inside Casing (fan sections and discharge plenums): Galvanized steel, 0.0299 inch or 22 gauge thick, perforated. 3. Inside Casing (all other sections): Galvanized steel, 0.0299 inch or 22 gauge thick, solid. 4. Floor Plate: Aluminum, 0.1382 inch thick with tread plate flooring. 5. Factory Base Rail: 6 inch on low/medium pressure units. B. Cabinet Insulation: Comply with NFPA 90A or NFPA 90B. 1. Cabinets will have 2” foam insulation (minimum R-13 insulation value). 2. Materials: ASTM C 1071 with coated surface exposed to airstream to prevent erosion of glass fibers. 3. Thickness: 2 inches. 4. Thermal Conductivity (k-Value): 0.26 at 75 deg F mean temperature. 5. Fire-Hazard Classification: Maximum flame-spread index of 25 and smoke-developed index of 50, when tested according to ASTM C 411. 6. Liner Adhesive: Comply with NFPA 90A or NFPA 90B and ASTM C 916. 7. Mechanical Fasteners: Galvanized steel, suitable for adhesive attachment, mechanical attachment, or welding attachment to duct without damaging liner when applied as recommended by manufacturer and without causing leakage in cabinet. 8. Location and Application: Factory applied with adhesive and mechanical fasteners to the internal surface of section panels downstream from and including the cooling coil section. 9. Location and Application: Encased between outside and inside casing. C. Access Panels and Doors: Same materials and finishes as cabinet, complete with hinges, latches, handles, and gaskets. Access panels and doors shall be sized and located to allow periodic maintenance and inspections. All sections with access doors shall have viewing windows. Provide access panels and doors in the following locations: 1. Fan Sections: Access door on main access side of unit, access panels on other two (2) sides. 2. Access Sections: Access door on both sides of unit. 3. Coil Sections: Access panel on both sides of unit. 4. Damper Sections: Access door on main access side, access panel on other side of unit. 5. Surgery Dehumidification Sections: Access door on main access side, access panel on other side of unit. 6. UV Lights Sections: Access door on main access side, access panel on other side of unit. 7. Filter Sections: Access door on main access side, access panel on other side of unit. D. Condensate Drain Pans: Formed sections of stainless-steel sheet complying with requirements in ASHRAE 62. Fabricate pans with slopes in two planes to collect condensate from cooling coils (including coil piping connections and return bends) and humidifiers when units are operating at maximum catalogued face velocity across cooling coil. 1. Double-Wall Construction: Fill space between walls with foam insulation and seal moisture tight. 2. Pan-Top Surface Coating: Elastomeric compound. 3. Units with stacked coils shall have an intermediate drain pan or drain trough to collect condensate from top coil. 5. Duct-Mounting Frames: Construct downstream corners of holding device with cushion pads to protect media. Provide bolted filtersealing mechanism to mount and continuously seal each individual filter.
MANUFACTURER DRI-STEEM
MODEL
REMARKS
ULTRA-SORB
(1)(2)
MARK
LOCATION
TYPE
THICKNESS
MAX. FACE VELOCITY [FPM]
FB-10A
PRE FILTER
PLEATED
2"
437
MERV 8
RIGID
12"
437
MERV 14
FB-10B FINAL FILTER
EFFICIENCY/ QUANTITY MERV
SIZE
12 3 12 3
INITIAL PRESSURE LOSS [IN.W.C.]
MANUFACTURER
MODEL
REMARKS
0.20
CAMFIL FARR
30/30
(1)(2)
0.47
CAMFIL FARR
RIGA-FLO
(1)(2)
24x24 20x24 24x24 20x24
Description
Date
REMARKS (1) PROVIDE MAGNAHELIC GAUGE ACROSS HOUSING. (2) PROVIDE FILTER BANK HOLDING FRAME, BASIS OF DESIGN: CAMFIL FARR TYPE 8.
REMARKS (1) CONTRACTOR TO PIPE UNIT AS INDICATED FROM FACTORY. (2) DISPERSION SYSTEM SHALL BE REMOVABLE FROM AHU THROUGH ACCESS DOORS OR REMOVABLE PANEL WITHOUT REMOVAL OF OTHER EQUIPMENT.
AIR HANDLING UNIT SCHEDULE MARK
EXH
SUPPLY AIR PLENUM
FILTER BANK #2 (FB-10B)
SUPPLY FANS
UV LIGHTS
COOLING COIL (CC-10)
HUMIDIFIER (HUM-10)
HEATING COIL (HC-10)
FILTER BANK #1 (FB-10A)
AIR BLENDER
MIXING CHAMBER
RETURN FANS
RETURN AIR PLENUM
AHU-10
OA SA
LOCATION 3RD FLOOR
TYPE VAV
TYPE
# FANS
CFM
S.P. [IN.]
HP
VOLTS/Ø
TYPE
# FANS
CFM
S.P. [IN.]
HP
VOLTS/Ø
CHILLED WATER COIL MARK
PLENUM ARRAY
2
24,000
6.57
40
460/3
PLENUM ARRAY
2
16,150
2.87
20
460/3
CC-1
SUPPLY FAN
MIN. OA [CFM] 7,850
RETURN FAN
FILTER DATA BANK #1
FILTER DATA BANK #2
MANUFACTURER
REMARKS
HC-1
MERV 7
MERV 14
MCQUAY
(1)(2)(3)(4)(5)(6)(7)(8)
REMARKS (1) PROVIDE WITH UV LIGHTS ON DOWN STREAM FACE OF COOLING COIL WITH EXTERIOR CONRTOL SWITCH AND DOOR INTERLOCK SWITCH. (2) PROVIDE WITH INTEGRAL VFD WITH CONTROL CENTER. (3) MOUNT ON 4" HOUSEKEEPING PAD. (4) PROVIDE WITH STRUCTURAL BASE RAIL. (5) PROVIDE WITH PRESSURE RELIEF DOORS. (6) PROVIDE MAGNAHELIC GAUGE ACROSS HOUSING AT FILTERS. (7) PROVIDE WITH AIR BLENDER. (8) AHU SELECTION SHALL ALLOW FOR 70% AIRFLOW WITH ONE FAN NOT OPERATING. AHU MUST BE CAPABLE OF STABLE OPERATION AT 15% OF TOTAL AIRFLOW.
RA
SACRED HEART
HYDRONIC COIL SCHEDULE MARK
1
HEATING WATER COIL MARK
AHU-10 DETAIL NONE
SERVES
FLUID TYPE
2014
AIR FLOW [CFM]
MIN. ROWS
MAX. FINS PER INCH
MAX. VELOCITY [FPM]
MAX. AIR P.D. [IN. WC.]
ENTERING DB/WB [°F]
LEAVING DB/WB [°F]
TOTAL CAPACITY [MBH]
SENS. CAPACITY [MBH]
FLOW [GPM]
EWT/LWT [°F]
MAX. P.D. [FT.]
FLUID DATA MANUFACTURER
REMARKS
CC-10
AHU-10
WATER
24,000
8
10
489
0.51
82/68
52/52
1,185
785
186.0
44/56
18.8
MCQUAY
(1)(2)(3)(4)
HC-10
AHU-10
WATER
24,000
2
8
503
0.16
45
95
1,359
-
87.5
180/150
7.3
MCQUAY
(1)(3)(4)
C
4TH & 5TH MECHANICAL PRE-PURCHASED EQUIPMENT
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS.
REMARKS (1) MAINTAIN COIL PULL SPACE ON INSTALLATION. (2) PROVIDE DOUBLE SLOPED DRAIN PAN. (3) CONTRACTOR TO PIPE UNIT AS INDICATED FROM FACTORY, COUNTERFLOW. (4) VALUES GIVEN ARE FOR ENTIRE BANK. COIL BANK SHALL CONSIST OF 2 COILS.
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
Date
SES PROJECT # 14041
11/25/2014 4:38:35 PM
M503 Scale
NONE
PLATE AND FRAME HEAT EXCHANGER SCHEDULE EWT
LWT
PD [PSI]
PLATE FRAME
HX-CW1
30% PROP. GLYCOL
456
55
45
9.94
6
FLUID
GPM
EWT
LWT
PD [PSI]
WATER
430
57
47
6.96
NUMBER OF PASSES
MFGR
MODEL
2
BELL AND GOSSETT
GPX P62 BY5432
2,162
6
OPERATING TEMPERATURE RANGE (DEG F)
SYSTEM DESCRIPTION
MATERIAL (1)
SIZE RANGE
TYPE L COPPER
0" TO 2" REMARKS (1) PROVIDE INSULATED JACKET FOR HEAT EXCHANGER ASSEMBLY.
HEATING WATER SUPPLY AND RETURN
DUCT CONSTRUCTION SCHEDULE
ASTM A53 SCHEDULE 40 , TYPE E, GRADE B STEEL PIPE
SYSTEM DESCRIPTION
DUCT FUNCTION
DESCRIPTION
SUPPLY SUPPLY SUPPLY RETURN RETURN RELIEF EXHAUST
AHU-10
EF-1,2
MATERIAL (1)
LOCATION
FAN DISCHARGE TO VAV BOX FAN DISCHARGE TO VAV BOX VAV BOX TO DIFFUSER GRILLE TO FAN INLET GRILLE TO FAN INLET LOUVER TO AHU/FAN HOUSING GRILLE TO FAN INLET
ABOVE CEILING EXPOSED ABOVE CEILING ABOVE CEILING EXPOSED EXPOSED ABOVE CEILING
INSULATION (2)
GALVANIZED STEEL GALVANIZED STEEL GALVANIZED STEEL GALVANIZED STEEL GALVANIZED STEEL GALVANIZED STEEL GALVANIZED STEEL
FINISH (3)
2" EXTERNAL WRAP 2" EXTERNAL WRAP 2" EXTERNAL WRAP 2" EXTERNAL WRAP 2" EXTERNAL WRAP 2" EXTERNAL WRAP 2" EXTERNAL WRAP
FSK JACKET FSK JACKET FSK JACKET FSK JACKET FSK JACKET FSK JACKET FSK JACKET
DUCT CLEANLINESS LEVEL (6)
REMARKS
6" 6" 2" -3" -3" +/-6" -1"
A A A A A A B
ADVANCED ADVANCED ADVANCED ADVANCED ADVANCED ADVANCED INTERMEDIATE
-
REMARKS (1) REFER TO PROJECT SPECIFICATIONS FOR MATERIAL REQUIREMENTS. (2) REFER TO PROJECT SPECIFICATIONS FOR INSULATION MATERIAL DESCRIPTIONS AND REQUIREMENTS. PROVIDE INSULATION WITHIN 10 FEET OF EXTERIOR PENETRATIONS FOR ALL DUCT SYSTEMS. (3) REFER TO PROJECT SPECIFICATIONS FOR FINISH DESCRIPTIONS AND REQUIREMENTS. (4) REFER TO SMACNA DUCT CONSTRUCTION STANDARDS, CURRENT EDITION FOR CONSTRUCTION REQUIREMENTS. (5) REFER TO SMACNA HVAC AIR DUCT LEAKAGE TEST MANUAL FOR REQUIREMENTS. (6) REFER TO SMACNA DUCT CLEANLINESS FOR NEW CONSTRUCTION GUIDELINES FOR REQUIREMENTS.
MAX. S.P. [IN. W.C.]
DESCRIPTION
LOUVERED FACE STYLE SUPPLY DIFFUSER
D-1
LOUVERED FACE STYLE SUPPLY DIFFUSER
D-2
LINEAR SLOT STYLE SUPPLY DIFFUSER
D-3
DUCTED PERFORATED RETURN GRILLE
G-1
DUCTED PERFORATED RETURN GRILLE
G-3
DUCTED PERFORATED RETURN GRILLE
0.1
0.1
0.1
0.1
0.1
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
FINISH
FACE SIZE
WHITE
24"x24"
WHITE
12"x12"
24"x4" 2 SLOTS @ 1"
WHITE
WHITE
24"x12"
WHITE
AIRFLOW
6" 8" 10" 12" 14" 6" 8" -
0-185 186-290 291-410 411-540 541-685 0-155 156-230 -
8"
0-100
6"x6" 8"x8" 10"x10" 12"x12" 14"x14" 6"x6" 8"x8" 10"x10" 12"x12" 6"x6" 8"x8" -
24"x24"
WHITE
NECK SIZE
12"x12"
0-195 196-290 291-400 401-500 500-730 0-195 196-290 291-400 401-500 0-195 196-290 -
REMARKS
TITUS KRUEGER PRICE
TDX SH SMD
(1)(2)(3)
TDX SH SMD
0-80 PSIG 2-1/2" AND ABOVE
0-80 PSIG
PAR 6490 PFR
TITUS KRUEGER PRICE
PAR 6490 PFR
125
150
125
150
45-60
ALL
TYPE L COPPER
125
DOMESTIC HOT WATER AND HOT WATER RECIRCULATING
110-120
0" TO 4"
ASTM B88 TYPE L COPPER
125
DOMESTIC COLD WATER SOFT COLD WATER
40-60
0" TO 4"
ASTM B88 TYPE L COPPER
125
GRAVITY SOIL AND WASTE AND VENT
AMBIENT
ALL SIZES
PVC DWV
N/A
0" TO 2"
STANDARD WEIGHT BLACK STEEL PIPE
125
2-1/2" AND ABOVE
STANDARD WEIGHT BLACK STEEL PIPE OR SCHEDULE 10 BLACK STEEL PIPE WITH ROLLGROOVED ENDS
125
FIRE PROTECTION
AMBIENT
(1)(2)(3)
(1)(2)(3)
(1)(2)(3)
INSULATION (1)
FINISH (1)(3)
REMARKS
2" PREFORMED FIBERGLASS 2" PREFORMED FIBERGLASS 2" PREFORMED FIBERGLASS 2" PREFORMED FIBERGLASS 2" PREFORMED FIBERGLASS 2" PREFORMED FIBERGLASS 1-1/2" PREFORMED FIBERGLASS 1-1/2" PREFORMED FIBERGLASS 1-1/2" PREFORMED FIBERGLASS 1-1/2" PREFORMED FIBERGLASS 1-1/2" PREFORMED FIBERGLASS 1-1/2" PREFORMED FIBERGLASS 4.5" PREFORMED FIBERGLASS 4.5" PREFORMED FIBERGLASS 4.5" PREFORMED FIBERGLASS 4.5" PREFORMED FIBERGLASS 4.5" PREFORMED FIBERGLASS 4.5" PREFORMED FIBERGLASS 2.5" PREFORMED FIBERGLASS 2.5" PREFORMED FIBERGLASS 2.5" PREFORMED FIBERGLASS 3" PREFORMED FIBERGLASS 3" PREFORMED FIBERGLASS 3" PREFORMED FIBERGLASS 1" PREFORMED FIBERGLASS 1" PREFORMED FIBERGLASS 1" PREFORMED FIBERGLASS 1.5" PREFORMED FIBERGLASS 1.5" PREFORMED FIBERGLASS 1.5" PREFORMED FIBERGLASS 1" PREFORMED FIBERGLASS 1" PREFORMED FIBERGLASS 1" PREFORMED FIBERGLASS NONE NONE NONE NONE NONE NONE
ASJ JACKET PAINT TO MATCH ASJ JACKET ASJ JACKET PAINT TO MATCH ASJ JACKET NONE PAINT TO MATCH NONE NONE PAINT TO MATCH NONE ASJ JACKET PAINT TO MATCH ASJ JACKET ASJ JACKET PAINT TO MATCH ASJ JACKET ASJ JACKET PAINT TO MATCH ASJ JACKET ASJ JACKET PAINT TO MATCH ASJ JACKET NONE PAINT TO MATCH NONE ASJ JACKET PAINT TO MATCH ASJ JACKET NONE PAINT TO MATCH NONE NONE NONE NONE NONE PAINT TO MATCH NONE
5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 -
ABOVE CEILING
NONE
NONE
-
EXPOSED - FINISHED SPACE
NONE
PAINT TO MATCH
-
EXPOSED - UNFINISHED SPACE
NONE
NONE
-
ABOVE CEILING WROUGHT-COPPER, CLEANED, EXPOSED - FINISHED SPACE PURGED AND BAGGED FOR OXYGEN SERVICE EXPOSED - UNFINISHED SPACE ABOVE CEILING EXPOSED - FINISHED SPACE WROUGHT-COPPER EXPOSED - UNFINISHED SPACE
NONE NONE NONE NONE NONE NONE
NONE NONE NONE NONE NONE NONE
5 5 5 5 5 5
FITTINGS
LOCATION (2)
ABOVE CEILING EXPOSED - FINISHED SPACE EXPOSED - UNFINISHED SPACE ABOVE CEILING THREADED/FLANGED CAST IRON OR OR EXPOSED - FINISHED SPACE GROOVED MECHANICAL-JOINT GROOVED MECHANICAL-JOINT EXPOSED - UNFINISHED SPACE ABOVE CEILING 95/5 SOLDER WROUGHT COPPER OR OR EXPOSED - FINISHED SPACE PRESSURE SEAL PRESSURE SEAL EXPOSED - UNFINISHED SPACE ABOVE CEILING THREADED/FLANGED CAST IRON OR OR EXPOSED - FINISHED SPACE GROOVED MECHANICAL-JOINT GROOVED MECHANICAL-JOINT EXPOSED - UNFINISHED SPACE ABOVE CEILING THREADED CAST IRON EXPOSED - FINISHED SPACE EXPOSED - UNFINISHED SPACE ABOVE CEILING WELDED OR WROUGH STEEL EXPOSED - FINISHED SPACE FLANGED EXPOSED - UNFINISHED SPACE ABOVE CEILING THREADED CAST IRON EXPOSED - FINISHED SPACE EXPOSED - UNFINISHED SPACE ABOVE CEILING WELDED OR WROUGH STEEL EXPOSED - FINISHED SPACE FLANGED EXPOSED - UNFINISHED SPACE ABOVE CEILING 95/5 SOLDER WROUGHT COPPER OR OR EXPOSED - FINISHED SPACE PRESSURE SEAL PRESSURE SEAL EXPOSED - UNFINISHED SPACE ABOVE CEILING 95/5 SOLDER WROUGHT COPPER OR OR EXPOSED - FINISHED SPACE PRESSURE SEAL PRESSURE SEAL EXPOSED - UNFINISHED SPACE ABOVE CEILING 95/5 SOLDER WROUGHT COPPER OR OR EXPOSED - FINISHED SPACE PRESSURE SEAL PRESSURE SEAL EXPOSED - UNFINISHED SPACE ABOVE CEILING SOLVENT CEMENT PVC DRAINAGE FITTINGS EXPOSED - FINISHED SPACE EXPOSED - UNFINISHED SPACE ABOVE CEILING THREADED GRAY -IRON THREADED EXPOSED - FINISHED SPACE EXPOSED - UNFINISHED SPACE 95/5 SOLDER OR PRESSURE SEAL
WROUGHT COPPER OR PRESSURE SEAL
THREADED GRAY -IRON THREADED OR OR GROOVED MECHANICAL-JOINT GROOVED-MECHANICAL JOINT
(1)(2)(3)
PAR 6490 PFR
TITUS KRUEGER PRICE
125
CONDENSATE DRAIN
(1)(2)(3)
ML 1900 SDS
TITUS KRUEGER PRICE
ASTM A53 SCHEDULE 40, TYPE S, GRADE B STEEL PIPE ASTM A53 SCHEDULE 40, TYPE E, GRADE B STEEL PIPE ASTM A53 SCHEDULE 80, TYPE S, GRADE B STEEL PIPE ASTM A53 SCHEDULE 80, TYPE E, GRADE B STEEL PIPE
2-1/2" AND ABOVE
MODEL
TITUS KRUEGER PRICE
ASTM A53 SCHEDULE 40 , TYPE E, GRADE B STEEL PIPE
0" TO 2"
CONDENSATE
MANUFACTURER
TITUS KRUEGER PRICE
45-60 2-1/2" AND ABOVE
STEAM AND RELIEF VENT
125
CONNECTIONS (4)
MEDICAL COMPRESSED AIR, OXYGEN
AMBIENT
ALL
ASTM B819 TYPE K COPPER CLEANED FOR OXYGEN SERVICE
150
BRAZED
MEDICAL VACUUM
AMBIENT
ALL
ASTM B819 TYPE L
150
BRAZED
AVERA FACILITY DEVELOPMENT
REMARKS (1) REFER TO PROJECT SPECIFICATIONS FOR REQUIREMENTS. (2) FINISHED SPACES INCLUDE BUT ARE NOT LIMITED TO NORMALLY OCCUPIED SPACES, STORAGE ROOMS WITHOUT CEILINGS, LOADING AREAS, ETC. UNFINSHED SPACES INCLUDE BUT ARE NOT LIMITED TO SHELL SPACES, UTILITY ROOMS, EQUIPMENT ROOMS, ETC. (3) PROVIDE PVC JACKET FOR FITTINGS AND ELBOWS. PROVIDE REMOVABLE JACKETS ON VALVES AND CONTROL DEVICES. (4) WHERE MORE THAN ONE TYPE IS LISTED, THE CONTRACTOR HAS THE OPTION OF UTILIZING ONE OR A COMBINATION OF THE TYPES LISTED. USE OF MULTIPLE TYPES WITHIN THE SAME SYSTEM SHALL BE APPROVED BY THE ENGINEER. PRESSURE SEAL SYSTEM BASED ON VIEGA PROPRESS. OTHER SYSTEMS WILL BE CONSIDERED THROUGH THE APPROVAL PROCESS. GROOVED MECHANICAL-JOINT SYSTEM BASED ON VICTAULIC AGS. OTHER SYSTEMS WILL BE CONSIDERED THROUGH THE APPROVAL PROCESS. (5) FOR PIPE CONNECTIONS REQUIRING HOT WORK, CONTRACTOR SHALL FOLLOW OWNER'S HOT WORK PROCEDURES AND PROVIDE ALL NECESSARY EQUIPMENT AND PERSONNEL REQUIRED.
ED
FESSION PRO AL
S O
REMARKS (1) COORDINATE EXACT MODEL AND FRAME WITH CEILING/WALL TYPE. (2) PROVIDE REMOTE DAMPER ACTUATION IN HARD CEILINGS. (3) PROVIDE BLACKOUT PANELS ON TRANSFER GRILLES.
TYPE
. NO.
10229 ERIC G. SHERMAN U
T H
K D A
O
11/25/14
MAX. WEIGHT [LBS.]
AIR FLOW [CFM]
TOTAL S.P. [IN.W.C.]
MAX. FAN RPM
MAX. FAN BHP
No.
VARIABLE FREQUENCY DRIVE SCHEDULE
FAN SCHEDULE MARK
REG
R GINEE EN
G-2
0.1
CONST. MATERIAL
CHILLED WATER SUPPLY AND RETURN
125
TYPE K COPPER
0" TO 2"
DIFFUSER, REGISTER, AND GRILLE SCHEDULE MARK (1)
TYPE L COPPER
0" TO 2" SMACNA DUCT SEAL CLASS (5)
125
TYPE K COPPER
110-180 2-1/2" AND ABOVE
DUCT PRESSURE CLASS (4)
SYSTEM PRESSURE CLASS (PSI)
A
GPM
HEAT CONNECTION EXCHANGER SIZE [INCHES] [MBH]
HOT SIDE
T
FLUID
CONNECTION SIZE [INCHES]
TYPE
REGIST ER
COLD SIDE MARK
HVAC PIPE CONSTRUCTION SCHEDULE
ELECTRICAL DATA HP
VOLTS/PHASE
MANUFACTURER
MODEL
REMARKS
EF-1
UPBLAST
110
1000
0.75
1504
0.25
1/2
115/1
TWIN CITY
DCRU-110BE
(1)(2)(3)(4)(5)
EF-2
UPBLAST
114
1400
1.00
1539
0.43
3/4
115/1
TWIN CITY
DCRU-120BE
(1)(2)(3)(4)(5)
REMARKS (1) PROVIDE DISCONNECT. (2) PROVIDE ECM MOTOR WITH SPEED CONTROLLER. (3) PROVIDE AUTOMATIC BACKDRAFT DAMPER INTERLOCKED WITH MOTOR. (4) PROVIDE BIRDSCREEN. (5) PROVIDE VIBRATION ISOLATION.
ELECTRICAL DATA CONNECTED VOLTS/PHASE MOTOR HP
MARK
SERVES
VFD-SF-10A
SF-10A
480/3
20
(1)
VFD-SF-10B
SF-10B
480/3
20
(1)
VFD-RF-10A
RF-10A
480/3
10
(1)
VFD-RF-10B
RF-10B
480/3
10
(1)
Description
Date
REMARKS
REMARKS (1) REMOVE FACTORY PROVIDED VFD AND CONNECT NEW VFDS. REFER TO ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION. PATCH ALL CASING PENETRATIONS. PROVIDE NEW UNISTRUT STAND FOR NEW VFDS. STAND SHALL BE SUPPORTED FROM THE FLOOR.
RADIANT PANEL SCHEDULE MARK
SIZE [IN]
MAX. BTU PER FLOW RATE NUMBER OF PRESSURE LINEAL FT. [GPM] TUBES DROP [FT]
MEAN WATER MANUFACTURER TEMP. [DEG F]
MODEL
REMARKS
RAD-1 24 x 48
375
2
4
3
170
AIRTEX
HPH
(1)(2)(3)(4)
RAD-2 24 x 48
375
2
4
3
170
AIRTEX
HPH
(1)(2)(3)(4)
RAD-3 24 x 48
375
2
4
3
170
AIRTEX
HPH
(1)(2)(3)(4)
REMARKS (1) COORDINATE PANEL WITH CEILING SYSTEM. (2) INSULATE BACK OF RADIANT PANEL. (3) PROVIDE TRIM RING IN HARD CEILINGS. (4) COLOR TO BE SELECTED BY ARCHITECT FROM MANUFACTURER STANDARD FINSIHES.
SACRED HEART
2014
C
4TH & 5TH MECHANICAL SCHEDULES
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
Date
SES PROJECT # 14041
11/25/2014 4:38:37 PM
M600 Scale
NONE
PLUMBING FIXTURE SCHEDULE
HYDRONIC VARIABLE VOLUME BOX SCHEDULE
COLD WATER WATER HAMMER ARRESTERS - PROVIDE BELLOWS OR PISTON TYPE WATER HAMMER ARRESTERS AT EACH FIXTURE GROUP. SIZE AND INSTALL IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS AND PDI STANDARD WH 201. INSTALL IN AN ACCESSIBLE LOCATION AND PROVIDE ACCESS DOOR IN CEILING AND/OR WALL WHERE REQUIRED FOR PROPER ACCESS.
PDI# / SFU
PDI# / SFU
AA / 1-3 A / 1-11 B / 12-32 C / 33-60 D / 61-113 E / 114-154 F / 155-330
AA / 1-3 A / 1-11 B / 12-32 C / 33-60 D / 61-113 E / 114-154 F / 155-330
FLOOR DRAIN - 3.75" WIDE BY 60" LONG STAINLESS STEEL CHANNEL DRAIN WITH MEMBRANE CLAMP, 2" BOTTOM OUTLET, FRAMELESS TILEABLE GRATE ASSEMBLY. SCHLUTER KERDI-LINE KLV 60 E 150 WITH KLDRE 150 OR APPROVED EQUAL.
-
FLOOR DRAIN - 3.75" WIDE BY 36" LONG STAINLESS STEEL CHANNEL DRAIN WITH MEMBRANE CLAMP, 2" BOTTOM OUTLET, FRAMELESS TILEABLE GRATE ASSEMBLY. SCHLUTER KERDI-LINE KLV 60 E 90 WITH KLDRE 90 OR APPROVED EQUAL.
PRE-CHARGED, BELLOWS TYPE, ALL STAINLESS STEEL CONSTRUCTION, ASSE 1010 APPROVED, PDI CERTIFIED.
NONE WATER HAMMER ARRESTER
FD-1 SHOWER DRAIN
FD-2 SHOWER DRAIN
HOT WATER
PRE-CHARGED WITH 60 PSIG AIR, COPPER BODY, BRASS OR HIGH HEAT POLYPROPYLENE PISTON WITH DUAL EDPM O-RING SEALS LUBRICATED WITH FDA APPROVED SILICONE LUBRICANT. PDI CERTIFIED, A.S.S.E. 1010 APPROVED FOR SEALED WALL INSTALLATION.
WASTE
VENT
-
-
-
2"
1-1/2"
-
-
2"
1-1/2"
1/2"
1/2"
1-1/2"
1-1/4"
1/2"
1/2"
1-1/2"
1-1/4"
3/4"
3/4"
-
-
BOWL - SINGLE COMPARTMENT SINK INTEGRAL TO COUNTERTOP BY ARCHITECT.
BOWL L-1
TRIM - TWO HANDLE MIXING FAUCET, CHROME PLATED, SWING GOOSENECK SPOUT WITH 5" REACH AND PRESSURE COMPENSATING LAMINAR FLOW OUTLET IN FAUCET BASE, WITHOUT INLET SCREEN, 4" WRIST BLADE HANDLES AT 4" CENTERS, PERFORATED DRAIN GRATE WITH 1-1/2" 17 GAUGE TAILPIECE, CHROME PLATED CAST BRASS "P" TRAP WITH CLEANOUT, 3/8" CHROME PLATED HEAVY BRASS ANGLE SUPPLIES AND LOOSE KEY STOPS WITH CHROME PLATED SOFT COPPER RISERS. MAXIMUM FLOW TO BE 1.5 GPM IN COMPLIANCE WITH ENERGY POLICY ACT OF 1992 AND ASME/ANSI STANDARD A112.18.1M. PROVIDE RESTRICTIVE DEVICE AS REQUIRED. MOEN MODEL 8279SM WITH 52652 INSERT OR APPROVED EQUAL.
TRIM
BOWL L-2
TRIM
BOWL - WALL MOUNTED, WHITE VITREOUS CHINA, 4" HIGH CONTOURED BACKSPLASH, 20" X 18", 4" CENTERS, DRILLED FOR CONCEALED ARM CARRIER. FURNISH SUPPORT CARRIER BOLTED SECURELY TO FLOOR. PROVIDE 29" MINIMUM CLEARANCE FROM FLOOR TO BOTTOM OF APRON IN COMPLIANCE WITH ANSI A117.1-1986 AND ADA SECTION 4.19. TOP OF BASIN RIM TO BE MAXIMUM OF 34" ABOVE FLOOR IN COMPLIANCE WITH ADA SECTION 4.19. PROVIDE OFFSET DRAIN AND TAILPIECE. PRE-MANUFACTURED P-TRAP, STOP VALVE AND SUPPLY LINE INSULATION KIT. AMERICAN STANDARD MODEL 0355.012 OR APPROVED EQUAL. TRIM - TWO HANDLE MIXING FAUCET, CHROME PLATED, SWING GOOSENECK SPOUT WITH 5" REACH AND PRESSURE COMPENSATING LAMINAR FLOW OUTLET IN FAUCET BASE, WITHOUT INLET SCREEN, 4" WRIST BLADE HANDLES AT 4" CENTERS, PERFORATED DRAIN GRATE WITH 1-1/2" 17 GAUGE TAILPIECE, CHROME PLATED CAST BRASS "P" TRAP WITH CLEANOUT, 3/8" CHROME PLATED HEAVY BRASS ANGLE SUPPLIES AND LOOSE KEY STOPS WITH CHROME PLATED SOFT COPPER RISERS. MAXIMUM FLOW TO BE 1.5 GPM IN COMPLIANCE WITH ENERGY POLICY ACT OF 1992 AND ASME/ANSI STANDARD A112.18.1M. PROVIDE RESTRICTIVE DEVICE AS REQUIRED. MOEN MODEL 8279SM WITH 52652 INSERT OR APPROVED EQUAL. ENCLOSURE - BY ARCHITECT. TRIM - SINGLE HANDLE COMBINATION PRESSURE BALANCED AND THERMOSTATIC MIXING FAUCET, BRASS OR BRONZE CONSTRUCTION, WASHERLESS DESIGN, OFFCOLDHOT TEMPERATURE RANGE INDICATOR DIAL, POLISHED CHROME CAST METAL LEVER HANDLE, INTEGRAL CHECK STOPS, ADJUSTABLE TEMPERATURE LIMIT STOP SET TO 110 DEGREE F DISCHARGE. ASSE 1016 LISTED. INSTALL ALL CONTROLS BETWEEN 38" AND 48" ABOVE FINISHED FLOOR IN COMPLIANCE WITH ADA.
SH-1
TRIM
ACCESSORIES - ADJUSTABLE SPRAY HAND HELD SHOWER, CHROME PLATED 36" MOUNTING RAIL, SWIVEL CONNECTOR, 60" CHROME PLATED METAL HOSE, CHROME PLATED BRASS SUPPLY ELBOW WITH FLANGE, CHROME PLATED ELEVATED VACUUM BREAKER WITH CHROME PLATED PIPING AND FLANGES. MAXIMUM FLOW TO BE 1.5 GPM IN COMPLIANCE WITH ENERGY POLICY ACT OF 1992 AND ASME/ANSI STANDARD A112.18.1M. LAWLER MODEL M7800 SC1-RB HS3 EVB OR APPROVED EQUAL.
1"
-
3"
HEATING
12" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6"
55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F 55 °F
55 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F 110 °F
0 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F 180 °F
0.0 GPM 1.8 GPM 1.8 GPM 1.8 GPM 1.8 GPM 1.8 GPM 1.8 GPM 1.8 GPM 1.8 GPM 1.8 GPM 1.2 GPM 1.2 GPM 1.2 GPM 1.2 GPM 1.2 GPM 1.2 GPM 1.2 GPM 1.8 GPM 1.8 GPM 1.8 GPM 1.8 GPM 1.8 GPM 1.8 GPM 1.8 GPM 1.8 GPM 1.8 GPM 1.8 GPM 1.2 GPM 1.2 GPM 1.2 GPM 1.2 GPM 1.2 GPM 1.2 GPM 3.3 GPM 1.8 GPM 1.8 GPM 1.8 GPM 1.8 GPM 1.8 GPM 1.8 GPM 1.8 GPM 1.8 GPM 1.8 GPM 1.2 GPM 1.2 GPM 1.2 GPM 1.2 GPM 1.2 GPM 1.2 GPM 1.2 GPM 2.1 GPM 1.8 GPM 1.8 GPM 1.8 GPM 1.8 GPM 1.8 GPM 1.8 GPM 1.8 GPM 1.8 GPM 1.8 GPM 1.8 GPM 1.2 GPM 1.2 GPM 1.2 GPM 1.2 GPM 1.2 GPM 1.2 GPM 3.3 GPM
0 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger Krueger
MODEL
REMARKS
LMHS-12 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06 LMHS-06
(1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4) (1)(2)(3)(4)
AVERA FACILITY DEVELOPMENT
ED
FESSION PRO AL
1-1/2"
REG
. NO.
R GINEE EN
FLUSH VALVE
FLUSH VALVE - EXPOSED, CHROME PLATED 1" I.P.S. SCREWDRIVER STOP-CHECK VALVE, CHEMICAL RESISTANT MATERIAL, VACUUM BREAKER, WALL AND SPUD FLANGES, BED PAN WASHER DIVERTER, 1.6 GALLONS PER FLUSH. 3 YEAR WARRANTY. FLUSH HANDLE SHALL BE LOCATED ON THE WIDE SIDE OF THE TOILET STALL AND SHALL BE 12" MAXIMUM ABOVE BOWL RIM AND OPERATE WITH NO GREATER THAN 5 LB FORCE, IN COMPLIANCE WITH ADA SECTION 4.16.5 AND 4.27.4. CONTRACTOR TO VERIFY EQUIPMENT REQUIREMENTS AND ROUGH-IN LOCATIONS. SLOAN MODEL BPW-1150 OR APPROVED EQUAL.
WC-1
1500 CFM 300 CFM 300 CFM 300 CFM 300 CFM 300 CFM 300 CFM 300 CFM 300 CFM 300 CFM 200 CFM 200 CFM 200 CFM 200 CFM 200 CFM 200 CFM 200 CFM 300 CFM 300 CFM 300 CFM 300 CFM 300 CFM 300 CFM 300 CFM 300 CFM 300 CFM 200 CFM 200 CFM 200 CFM 200 CFM 200 CFM 200 CFM 200 CFM 550 CFM 300 CFM 300 CFM 300 CFM 300 CFM 300 CFM 300 CFM 300 CFM 300 CFM 300 CFM 200 CFM 200 CFM 200 CFM 200 CFM 200 CFM 200 CFM 200 CFM 350 CFM 300 CFM 300 CFM 300 CFM 300 CFM 300 CFM 300 CFM 300 CFM 300 CFM 300 CFM 200 CFM 200 CFM 200 CFM 200 CFM 200 CFM 200 CFM 200 CFM 550 CFM
COOLING
O
WATER CLOSET
SEAT - WHITE EXTRA HEAVY OPEN FRONT INJECTION MOLDED SOLID PLASTIC SEAT WITH CHECK HINGE AND STAINLESS STEEL OR PLATED STEEL POSTS AND NUTS AND ANTIMICROBIAL COATING. BEMIS MODEL 2155C OR APPROVED EQUAL.
VB-3-1 VB-4-1 VB-4-2 VB-4-3 VB-4-4 VB-4-5 VB-4-6 VB-4-7 VB-4-8 VB-4-9 VB-4-10 VB-4-11 VB-4-12 VB-4-13 VB-4-14 VB-4-15 VB-4-16 VB-4-18 VB-4-19 VB-4-20 VB-4-21 VB-4-22 VB-4-23 VB-4-24 VB-4-25 VB-4-26 VB-4-27 VB-4-28 VB-4-29 VB-4-30 VB-4-31 VB-4-32 VB-4-33 VB-4-34 VB-5-1 VB-5-2 VB-5-3 VB-5-4 VB-5-5 VB-5-6 VB-5-7 VB-5-8 VB-5-9 VB-5-10 VB-5-11 VB-5-12 VB-5-13 VB-5-14 VB-5-15 VB-5-16 VB-5-17 VB-5-18 VB-5-19 VB-5-20 VB-5-21 VB-5-22 VB-5-23 VB-5-24 VB-5-25 VB-5-26 VB-5-27 VB-5-28 VB-5-29 VB-5-30 VB-5-31 VB-5-32 VB-5-33 VB-5-34
BOX INLET
NUMBER OF HEATING ROWS MANUFACTURER
S
ACCESSIBLE WATER CLOSET - FLOOR MOUNTED, REAR DISCHARGE FLUSH VALVE TYPE, WHITE VITREOUS CHINA, SIPHON JET, WATER SAVING, ELONGATED BOWL, 1-1/2" TOP SPUD, BEDPAN LUGS BOLT CAPS. TOP OF SEAT AT 17" TO 19" ABOVE FINISHED FLOOR. INTERFACE WITH FLOOR AND WALL SHALL FORM A STRAIGHT EDGE FOR EASY CLEANING. AMERICAN STANDARD MODEL 3313.001 OR APPROVED EQUAL.
SUPPLY MARK AIR FLOW
ENTERING WATER COIL TEMP FLOW
10229 ERIC G. SHERMAN U
A
DESCRIPTION
T
TYPE
REGIST ER
LEAVING AIR TEMP.
PIPING CONNECTIONS MARK
T H
K D A
O
11/25/14 REMARKS (1) (2) (3) (4)
No.
MAXIMUM FULL FLOW AIR PRESSURE DROP ACROSS THE BOX ASSEMBLY INCLUDING HEATING COIL SHALL BE 0.75 IN. W.C. MAXIMUM FULL FLOW WATER PRESSURE DROP THROUGH THE COIL SHALL BE 5 FT. MAXIMUM RADIATED SOUND LEVEL BASED ON ARI 880-98 AT 1.0 IN.W.C. DIFFERENTIAL PRESSURE SHALL NOT EXCEED NC 30. MAXIMUM DISCHARGE SOUND LEVEL BASED ON ARI 880-98 AT 1.0 IN.W.C. DIFFERENTIAL PRESSURE SHALL NOT EXCEED NC 25.
Description
Date
ACCESSIBLE WATER CLOSET - FLOOR MOUNTED, BOTTOM DISCHARGE FLUSH VALVE TYPE, WHITE VITREOUS CHINA, SIPHON JET, WATER SAVING, ELONGATED BOWL, 11/2" TOP SPUD, BEDPAN LUGS BOLT CAPS. TOP OF SEAT AT 17" TO 19" ABOVE FINISHED FLOOR. INTERFACE WITH FLOOR AND WALL SHALL FORM A STRAIGHT EDGE FOR EASY CLEANING. AMERICAN STANDARD MODEL 3043.001 OR APPROVED EQUAL.
WATER CLOSET WC-2
FLUSH VALVE
SEAT - WHITE EXTRA HEAVY OPEN FRONT INJECTION MOLDED SOLID PLASTIC SEAT WITH CHECK HINGE AND STAINLESS STEEL OR PLATED STEEL POSTS AND NUTS AND ANTIMICROBIAL COATING. BEMIS MODEL 2155C OR APPROVED EQUAL.
1"
-
3"
1-1/2"
FLUSH VALVE - EXPOSED, CHROME PLATED 1" I.P.S. SCREWDRIVER STOP-CHECK VALVE, CHEMICAL RESISTANT MATERIAL, VACUUM BREAKER, WALL AND SPUD FLANGES, BED PAN WASHER DIVERTER, 1.6 GALLONS PER FLUSH. 3 YEAR WARRANTY. FLUSH HANDLE SHALL BE LOCATED ON THE WIDE SIDE OF THE TOILET STALL AND SHALL BE 12" MAXIMUM ABOVE BOWL RIM AND OPERATE WITH NO GREATER THAN 5 LB FORCE, IN COMPLIANCE WITH ADA SECTION 4.16.5 AND 4.27.4. CONTRACTOR TO VERIFY EQUIPMENT REQUIREMENTS AND ROUGH-IN LOCATIONS. SLOAN MODEL BPW1150 OR APPROVED EQUAL.
SACRED HEART
2014
C
4TH & 5TH MECHANICAL SCHEDULES
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
Date
SES PROJECT # 14041
11/25/2014 4:38:40 PM
M601 Scale
NONE
98.5
1.3
2.4
3.4
3.6 AVERA FACILITY DEVELOPMENT
GENERAL NOTES
A
A. REFER TO MECHANICAL COVER SHEET M000 FOR GENERAL REQUIREMENTS, SYMBOLS, ABBREVIATIONS, AND MOUNTING ELEVATION REQUIREMENTS.
A1 B B.0
1.7
2.1
2 M991 HX-CW1
B1.1
C
MODIFY EXISTING FAN COIL CHANGE OVER PANEL TO REFLECT REMOVAL OF 4TH AND 5TH FLOOR SYSTEMS.
C1
FESSION PRO AL . NO.
10229 ERIC G. SHERMAN
O
U
A
S
D1
REG
T
ED
R GINEE EN
REGIST ER
D
T H
K D A
O
11/25/14 AHU-10
E
No.
Description
Date
1 M990
E1
F F1
1b 1
99
1
1c
2b
3c
3A
4 4a
5
5.1
6
B1.2 7
SACRED HEART
8
4TH & 5TH THIRD LEVEL CONTROLS
THIRD LEVEL- CONTROLS 1/8" = 1'-0" 2014
C
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
Date
SES PROJECT # 14041
11/25/2014 4:38:42 PM
M931 Scale
1/8" = 1'-0"
1.3
2.4
3.4
3.6 AVERA FACILITY DEVELOPMENT
GENERAL NOTES
A
A. REFER TO MECHANICAL COVER SHEET M000 FOR GENERAL REQUIREMENTS, SYMBOLS, ABBREVIATIONS, AND MOUNTING ELEVATION REQUIREMENTS.
ELEVATOR LINK 4900
SHEET NOTES
PHASE 4
A1
1 REPLACE EXISTING THERMOSTAT.
B B.0 RAD-1 RESTROOM 418
M991
OFFICE 462
1.7
2.1
T
1
B1.1
1
T
VB-4-27
1
1 PATIENT RM M991 400 VB-4-26
1
1
M991 PATIENT RM VB-4-25
PATIENT RM M991 404 VB-4-24
402
1
1
M991 PATIENT RM 406
VB-4-23
1
M991 PATIENT RM 408 VB-4-22
PATIENT RM M991 410 VB-4-21
1
1
M991 PATIENT RM 412 VB-4-20
PATIENT RM M991 414 VB-4-19
T
1 M991 PATIENT RM VB-4-18 416
3
2
M991
M992
NEGATIVE AIR 420
T
1
1
T
T
T
T
T
T
T
T
T
T
VB-4-16
1
PATIENT RM 422
VB-4-28
M991 OFFICE
1
460
1
M991 MECH 459
C
RESTROOM 421
1 M991
VB-4-15
VB-4-29
C1
1 1
ELEC 534
T
1
T
M991 HSKG 536
1 M991
1
T CLEAN UTILITY 550
OFFICE 537
DIRTY UTILITY 549
1
TOILET 535
T
PATIENT RM M991 424
TOILET 548
1
VB-4-14
VB-4-30
STORAGE 539
PHASE 2
DIET 544
CONFERENCE 546
LOCKER ROOM 547
1 M991
1
VB-4-13
VB-4-31 1 T T
CLEAN UTILITY 541
SOILED 542
OMNI CELL 545
NUTRITION 543
T
1
1
O
D1
FESSION PRO AL
S
VB-4-32
ED
1
REG
. NO.
R GINEE EN
EQUIPMENT 540
1
T
10229 ERIC G. SHERMAN U
A
WAITING ROOM 538
T
M991
REGIST ER
D
RESTROOM 455
PHASE 3
T H
K D A
O
VB-4-12
M991
1
11/25/14
M991
E
No. 1
M991
VB-4-33
1
VB-4-1
1
PATIENT RM 448
M992
T
T
T
T
T
T
T
T
T
VB-4-34
T
T
E1
VB-4-11 ANTERIOR RM 450
T
Date
1
M991
1
Description
RESTROOM 451
VB-4-2
1
1
M991
M991
VB-4-3 PATIENT RM 446
PATIENT RM 444
VB-4-4
1
1
M991
M991
VB-4-5 PATIENT RM 442
1
VB-4-6 PATIENT RM 440
PATIENT RM 438
M991
VB-4-7
1
1
M991
M991
VB-4-8 PATIENT RM 436
PATIENT RM 434
T
VB-4-9
1
1
M991
M991
1
1
PATIENT RM 432
1 M991
T
VB-4-10
3 M991
STORAGE 431 RAD-2
RESTROOM 429
F F1 PHASE 1
99 1
1
1c
2b
3c
3A
4 4a
5
5.1
6
B1.2 7
SACRED HEART
8
4TH & 5TH FOURTH LEVEL CONTROLS
FOURTH LEVEL - CONTROLS 1/8" = 1'-0" 2014
C
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
Date
SES PROJECT # 14041
11/25/2014 4:38:45 PM
M941 Scale
1/8" = 1'-0"
1.3
2.4
3.4
3.6 AVERA FACILITY DEVELOPMENT
GENERAL NOTES
A
A. REFER TO MECHANICAL COVER SHEET M000 FOR GENERAL REQUIREMENTS, SYMBOLS, ABBREVIATIONS, AND MOUNTING ELEVATION REQUIREMENTS.
ELEVATOR LINK 5900
SHEET NOTES
PHASE 4
A1
1 REPLACE EXISTING THERMOSTAT.
B B.0
1 1
T
M991 VB-5-27
M991
1
PATIENT RM VB-5-23 506
M991
M991
M991
PATIENT RM VB-5-22 508
PATIENT RM VB-5-21 510
T
T
SHOWER
SHOWER
PATIENT RM VB-5-20 512
SHOWER
1
1
M991
M991
PATIENT RM 514 VB-5-19
SHOWER
3
NEGATIVE EF-1 AIR M992 520
2
PATIENT RM 516
VB-5-18
SHOWER
ON ROOF
M992
VB-5-17
SHOWER
T
M991
SHOWER
1
T
SHOWER
T
M991 PATIENT RM 504 VB-5-24
M991 PATIENT RM VB-5-25 502
SHOWER
1
1
T
B1.1
M991 PATIENT RM VB-5-26 500
1
T
T
1
2.1
1
T
1.7
1
T
1
OFFICE 5902
VB-5-16 RESTROOM 501
RESTROOM 503
RESTROOM 505
RESTROOM 507
RESTROOM 509
RESTROOM 511
RESTROOM 513
RESTROOM 515
1
RESTROOM 517
M991
C
1 T
1
T
MECH. 565
1
T
T
SHOWERSHOWER
1
SHOWERSHOWER
VB-5-28
1
M991 VB-5-29
1 M991
VB-5-15
ELEC 551 HSKG 552
EQUIPMENT 553
VB-5-14
M991
CLEAN UTILITY 558
1 M991
STORAGE 554
T
1 M991
M991
PATIENT RM 1 548
PATIENT RM 546 1
M991
M991
PATIENT RM 542
PATIENT RM 1 544
VB-5-7
PATIENT RM 540 1
1
M991
VB-5-6
M991
M991
RESTROOM 535
T
T
VB-5-5
VB-5-4
RESTROOM 537
T
10229 ERIC G. SHERMAN U
T H
K D A
O
11/25/14
Description
Date
T
1
VB-5-8
VB-5-9
PATIENT RM 1 538
PATIENT RM 536 1
M991
M991
M991
T
1
PATIENT RM 1 534
1
M991
554
M991 VB-5-10
T
1
. NO.
1
T
EF-2 ON ROOF ISOLATION
VB-5-3
T
SHOWER
SHOWER
PATIENT RM 1 550
SHOWER
M992
T
T
T
T
VB-5-2
T
T
SHOWERSHOWER
VB-5-1
SHOWER
1 M992
SHOWER
3
SHOWER
VB-5-34
RESTROOM 539 SHOWER
E1
REG
VB-5-11 RESTROOM 541
VB-5-33
1
No.
RESTROOM 543
T
RESTROOM 545
SHOWER
RESTROOM 547
SHOWER
T
CORRIDOR 5901
1 M991
O
1
SHOWERSHOWER
E
FESSION PRO AL
S
VB-5-12
M991 1
ED
R GINEE EN
SOILED UTILITY 555
VB-5-32
1
M991
VB-5-13 NUTRITION 556
1 1
VB-5-31
STOREROOM 557
D1
SOILED UTILITY 559
PHASE 2
A
T
1
1
T
T
PHASE 3
SHOWERSHOWER
1
SHOWERSHOWER
M991
REGIST ER
1
D
1
VB-5-30
T
C1
RAD-3
F 3
F1
M991 PHASE 1
1b 1
99
1
1c
2b
3c
3A
4 4a
5
5.1
6
B1.2 7
SACRED HEART
8
4TH & 5TH FIFTH LEVEL CONTROLS
FIFTH LEVEL - CONTROLS 1/8" = 1'-0" 2014
C
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
Date
SES PROJECT # 14041
11/25/2014 4:38:48 PM
M951 Scale
1/8" = 1'-0"
42
RELIEF AIR
12 13
44
ACTUATOR
CO2
CO2 BLENDER
H
C
AVERA FACILITY DEVELOPMENT
RETURN FAN
ACTUATOR
ACTUATOR
C
01
03
02
04
VFD
06
CO2 43
07 08 09 10 11
18
16 17
05
C
19
20
VFD
21
14 ACTUATOR 15
24
25
22
26
23
27
ACTUATOR
SMOKE DETECTOR
DP 41
DP HWR
DP
MOTOR
LPS
MOTOR
CWS
SMOKE DETECTOR
CWR
DP
SUPPLY FAN
HWS
RETURN AIR
29
30 31 32 33 34
DP
DP
35
36
37 38
39
40
28
OUTDOOR AIR
SEQUENCE OF OPERATION
DIRECT DIGITAL CONTROL POINTS LIST POINT ID
POINT DESCRIPTION
SOURCE (1)
TYPE (2)
I/O (3)
SETPOINT ADJUSTMENT
ALARMS (4)
APPLICATIONS (5)
UNITS
01
RETURN DUCT DIFFERENTIAL STATIC PRESSURE
E
A
I
YES
-
T, A, G
INCHES W.C.
02
AHU RETURN AIR ISOLATION DAMPER POSITION
E
B
I
NO
-
E, A, G
OPEN/CLOSED
03
RETURN AIR TEMPERATURE
E
A
I
NO
-
T, A, G
DEGREES F
04
RETURN AIR HUMIDITY
E
A
I
NO
-
T, A, G
05
RETURN AIR HUMIDITY SETPOINT
E
A
O
YES
-
T, A, G
06
RETURN FAN SUCTION STATIC PRESSURE SWITCH
E
B
I
YES
C, H
E, A, G
INCHES W.C.
07
RETURN FAN VFD STATUS
E
B
I
NO
G, F
E, A
-
08
RETURN FAN VFD START/STOP
E
B
0
NO
-
-
-
09
RETURN FAN VFD SPEED CONTROL
E
A
O
YES
-
T, A, G
% SPEED
10
RETURN FAN CURRENT STATUS SWITCH
E
B
I
NO
G, F
E, A, G
ON/OFF
11
RETURN FAN AIRFLOW VOLUME
E
A
I
NO
-
T, A, G
CFM
12
RELIEF AIR DAMPER ACTUATOR
E
A
O
NO
-
-
-
13
RELIEF AIR DAMPER POSITION
E
A
I
NO
-
T, A, G
% OPEN
14
OUTDOOR AIR DAMPER ACTUATOR
E
A
O
NO
-
-
-
15
OUTDOOR AIR DAMPER POSITION
E
A
I
NO
-
T, A, G
% OPEN
16
RETURN AIR DAMPER ACTUATOR
E
A
O
NO
-
-
-
17
RETURN AIR DAMPER POSITION
E
A
I
NO
-
T, A, G
% OPEN
18
OUTDOOR AIRFLOW
E
A
I
NO
-
T, A, G
CFM
19
MIXED AIR TEMPERATURE
E
A
I
NO
-
T, A, G
DEGREES F
DESCRIPTION:
THE AIR HANDLING UNIT IS A VARIABLE AIR VOLUME UNIT AND CONSISTS OF A SUPPLY FAN WITH VFD, RETURN FAN WITH VFD, OUTDOOR AIR DAMPER, RETURN AIR DAMPER, RELIEF AIR DAMPER, BLENDER, PRE-FILTER BANK, HOT WATER HEATING COIL, CHILLED WATER COOLING COIL, STEAM HUMIDIFIER, FINAL FILTER BANK AND UNIT ISOLATION DAMPERS.
SUPPLY FAN CONTROL:
START/STOP: THE DDC SYSTEM SHALL START THE SUPPLY FAN VIA THE VFD WITH A TIME DELAY TO ALLOW ALL FIRE/SMOKE AND SMOKE DAMPERS IN THE AIR HANDLING SYSTEM TO OPEN PRIOR TO SUPPLY FAN OPERATION. VFD RESET: IN CASE OF VFD FAULT DETECTION, THE DDC SYSTEM SHALL WAIT 30 SECONDS (ADJUSTABLE) AND THEN CALL THE VFD TO START. IF THE VFD DOES NOT START, THE DDC SYSTEM SHALL CALL A SECOND TIME. IF THE VFD STILL HAS NOT STARTED, AN ALARM SHALL BE SENT TO THE OPERATOR INTERFACE. CURRENT STATUS SWITCH: IF THE CURRENT STATUS SWITCH DOES NOT PROVE OPERATION IN VFD OR BYPASS MODE, THE UNIT SHALL SHUT DOWN AND SEND AN ALARM TO THE OPERATOR INTERFACE. SPEED CONTROL: THE PURPOSE OF THE SUPPLY FAN CONTROL IS TO MAINTAIN A MINIMUM STATIC PRESSURE IN THE SUPPLY DUCTWORK TO INSURE PROPER TERMINAL AIR BOX OPERATION. THE DDC SYSTEM SHALL CONTROL THE SUPPLY FAN VFD FROM THE SUPPLY DUCT DIFFERENTIAL PRESSURE TRANSMITTER SIGNAL. INITIAL SETPOINT SHALL BE +1.0" W.C. (ADJUSTABLE). FINAL SETPOINT SHALL BE OPTIMIZED BY THE BALANCING CONTRACTOR. ON A DECREASE IN SYSTEM LOAD, THE DDC SYSTEM SHALL UTILIZE FEEDBACK FROM ALL TERMINAL AIR BOX POSITIONS TO RESET AND REDUCE THE SUPPLY DUCT DIFFERENTIAL STATIC PRESSURE UNTIL ONE TERMINAL AIR BOX DAMPER IS 95% OPEN. ON AN INCREASE IN SYSTEM LOAD, THE DDC SYSTEM SHALL UTILIZE FEEDBACK FROM ALL TERMINAL AIR BOX POSITIONS TO INCREASE THE SUPPLY DUCT DIFFERENTIAL STATIC PRESSURE (NOT-TO-EXCEED THE FINAL SETPOINT) UNTIL ONE TERMINAL AIR BOX DAMPER IS 95% OPEN.
% RELATIVE HUMIDITY % RELATIVE HUMIDITY
HIGH PRESSURE LIMIT: DIFFERENTIAL PRESSURE SWITCH SHALL BE A MANUAL RESET TYPE AND WIRED IN SERIES WITH THE START/STOP CONTROL OF THE SUPPLY FAN. THE DDC SYSTEM SHALL MONITOR THE STATUS OF THE DIFFERENTIAL PRESSURE SWITCH. INITIAL SETPOINT SHALL BE +3.0" W.C. (ADJUSTABLE). RETURN FAN CONTROL:
START/STOP: THE DDC SYSTEM SHALL START THE RETURN FAN VIA THE VFD WITH A TIME DELAY TO ALLOW ALL FIRE/SMOKE AND SMOKE DAMPERS IN THE AIR HANDLING SYSTEM TO OPEN PRIOR TO RETURN FAN OPERATION. VFD RESET: IN CASE OF VFD FAULT DETECTION, THE DDC SYSTEM SHALL WAIT 30 SECONDS (ADJUSTABLE.) AND THEN CALL THE VFD TO START. IF THE VFD DOES NOT START, THE DDC SYSTEM SHALL CALL A SECOND TIME. IF THE VFD STILL HAS NOT STARTED, AN ALARM SHALL BE SENT TO THE OPERATOR INTERFACE. CURRENT STATUS SWITCH: IF THE CURRENT STATUS SWITCH DOES NOT PROVE OPERATION IN VFD OR BYPASS MODE, THE UNIT SHALL SHUT DOWN AND SEND AN ALARM TO THE OPERATOR INTERFACE. SPEED CONTROL: THE PURPOSE OF THE RETURN FAN CONTROL IS TO MAINTAIN A SLIGHTLY POSITIVE BUILDING PRESSURE, +0.05 W.C. (ADJUSTABLE). THE RETURN FAN VFD SHALL MODULATE TO MAINTAIN A CONSTANT CFM OFFSET FROM THE SUPPLY FAN BASED ON AIRFLOW MEASUREMENT TO ACCOUNT FOR TOTAL EXHAUST FROM THE BUILDING WHILE MAINTAINING A SLIGHTLY POSITIVE PRESSURE. IN THE EVENT OF A SENSOR FAILURE, PROVIDE AN ADJUSTABLE FREQUENCY OFFSET ALGORITHM FOR THE RETURN FAN RELATIVE TO THE SUPPLY FAN. WORK WITH THE BALANCER TO ESTABLISH THE CORRECT RETURN FAN VFD SPEED RELATIVE TO THE SUPPLY FAN SPEED TO ACHIEVE CORRECT AIRFLOW BALANCE AT 100% OF THE MAXIMUM SUPPLY CFM AND AT 50% OF THE MAXIMUM SUPPLY CFM. A LINEAR EQUATION SHALL THEN BE DEVELOPED FOR THE RETURN FAN SPEED. LOW PRESSURE LIMIT: DIFFERENTIAL PRESSURE SWITCH SHALL BE A MANUAL RESET TYPE AND WIRED IN SERIES WITH THE START/STOP CONTROL OF THE RETURN FAN. INITIAL SETPOINT SHALL BE -2.0" W.C. (ADJUSTABLE).
DISCHARGE AIR CONTROL:
WHENEVER THE DISCHARGE AIR TEMPERATURE IS ABOVE THE SETPOINT, THE FOLLOWING SHALL OCCUR IN SEQUENCE: 1. THE HEATING COIL CONTROL VALVE(S) SHALL MODULATE CLOSED. 2. IF THE OUTSIDE AIR ENTHALPY IS BELOW THE RETURN AIR ENTHALPY, THE OUTSIDE AIR DAMPER SHALL MODULATE OPEN. THIS SHALL CONTINUE UNTIL THE SETPOINT IS ACHIEVED OR THE DAMPER IS IN THE 100% OUTSIDE AIR POSITION. 3. IF THE OUTSIDE AIR ENTHALPY IS ABOVE THE RETURN AIR ENTHALPY, THE OUTSIDE AIR DAMPER(S) SHALL CLOSE TO THEIR MINIMUM OUTSIDE AIR POSITION(S). 4. IF THE SETPOINT CANNOT BE ACHIEVED BY MODULATION OF THE OUTSIDE AIR DAMPER, THE DDC SYSTEM SHALL MODULATE THE CHILLED WATER CONTROL VALVE(S) OPEN. 5. IF THE SETPOINT CANNOT BE ACHIEVED BY MODULATION OF THE OUTSIDE AIR DAMPER, THE DDC SYSTEM SHALL ENABLE THE ASSOCIATED CONDENSING UNIT CONTROLS TO MAINTAIN THE DISCHARGE AIR TEMPERATURE SETPOINT. 6. IF THE DISCHARGE AIR TEMPERATURE IS MORE THAN 10ºF (ADJUSTABLE) ABOVE THE SETPOINT, SEND AN ALARM TO THE OPERATOR INTERFACE.
I
NO
-
T, A, G
21
PRE-FILTER DIFFERENTIAL PRESSURE
E
A
I
YES
G, H
T, E, A, G
22
HEATING WATER COIL CONTROL VALVE
E
A
O
NO
-
-
-
23
HEATING WATER TEMPERATURE - RETURN
E
A
I
NO
-
T, A, G
DEGREES F
24
HEATING COIL DISCHARGE AIR TEMPERATURE
E
A
I
NO
G, H, L
T, A, G
DEGREES F
E
B
I
NO
F
E, A, G
NORMAL/ALARM
26
CHILLED WATER COIL CONTROL VALVE
E
A
O
NO
-
-
-
27
CHILLED WATER TEMPERATURE - RETURN
E
A
I
NO
-
T, A, G
DEGREES F
28
HUMIDIFIER CONTROL VALVE
E
A
O
NO
-
-
-
29
HUMIDITY HIGH LIMIT ALARM
E
B
I
NO
F
E, A, G
-
30
SUPPLY FAN VFD STATUS
E
B
I
NO
G, F
E, A
-
31
SUPPLY FAN VFD START/STOP
E
B
0
NO
-
-
-
32
SUPPLY FAN VFD SPEED CONTROL
E
A
O
YES
-
T, A, G
% SPEED
33
SUPPLY FAN CURRENT STATUS SWITCH
E
B
I
NO
G, F
E, A
ON/OFF
34
SUPPLY FAN AIRFLOW VOLUME
E
A
I
NO
-
T, A, G
CFM
35
SUPPLY FAN DISCHARGE STATIC PRESSURE SWITCH
E
B
I
YES
C, H
E, A, G
INCHES W.C.
36
FINAL FILTER DIFFERENTIAL PRESSURE
E
A
I
YES
G, H
T, E, A, G
INCHES W.C.
37
SUPPLY AIR TEMPERATURE
E
A
I
NO
-
T, A, G
DEGREES F
38
SUPPLY AIR TEMPERATURE SETPOINT
E
A
O
YES
-
T, A, G
DEGREES F
39
SUPPLY AIR HUMIDITY
E
A
I
NO
-
T, A, G
% RELATIVE HUMIDITY
40
AHU SUPPLY AIR ISOLATION DAMPER POSITION
E
B
I
NO
-
E, A, G
OPEN/CLOSED
41
SUPPLY DUCT DIFFERENTIAL STATIC PRESSURE
E
A
I
YES
-
T, A, G
42
CARBON DIOXIDE LEVEL - RETURN AIR
E
A
I
NO
C, H
T, A, G
43
CARBON DIOXIDE LEVEL - OUTDOOR AIR
E
A
I
NO
C, H
T, A, G
44
CARBON DIOXIDE LEVEL - SUPPLY AIR
E
A
I
NO
C, H
T, A, G
-
OUTDOOR AIR REFERENCE TEMPERATURE
S
A
I
NO
-
T, A, G
DEGREES F
-
OUTDOOR AIR REFERENCE HUMIDITY
S
A
I
NO
-
T, A, G
% RELATIVE HUMIDITY
-
HEATING WATER TEMPERATURE - SUPPLY
S
A
I
NO
-
T, A, G
DEGREES F
-
CHILLED WATER TEMPERATURE - SUPPLY
S
A
I
NO
-
T, A, G
DEGREES F
-
FIRE ALARM STATUS
S
B
I
NO
C, F
E, A
NORMAL/ALARM
VENTILATION AIR CONTROL:
O
FREEZESTAT ALARM
FESSION PRO AL
S
25
HUMIDIFIER CONTROL: THE RETURN AIR RELATIVE HUMIDITY SETPOINT SHALL BE 30% (ADJUSTABLE). THE HUMIDIFIER CONTROL VALVE SHALL MODULATE TO MAINTAIN THE RETURN AIR RELATIVE HUMIDITY SETPOINT. THE DDC SYSTEM SHALL OVERRIDE THE SIGNAL TO THE HUMIDIFIER CONTROL VALVE TO LIMIT THE SUPPLY AIR RELATIVE HUMIDITY TO A MAXIMUM OF 70% (ADJUSTABLE). IF THE SUPPLY AIR RELATIVE HUMIDITY EXCEEDS 75% (ADJUSTABLE) AN ALARM SHALL BE SENT TO THE OPERATOR INTERFACE. WHENEVER THE OUTDOOR AIR DRY BULB REFERENCE TEMPERATURE IS ABOVE 40ºF (ADJUSTABLE), THE DDC SYSTEM SHALL CLOSE THE HUMIDIFIER CONTROL VALVE AND DISABLE THE ALARM.
ED
REG
. NO.
10229 ERIC G. SHERMAN U
A
A
T
E
REGIST ER
MIXED AIR HUMIDITY
R GINEE EN
WHENEVER THE DISCHARGE AIR TEMPERATURE IS BELOW THE SETPOINT, THE FOLLOWING SHALL OCCUR IN SEQUENCE: 1. THE CHILLED WATER CONTROL VALVE(S) SHALL MODULATE CLOSED. 2. IF THE OUTSIDE AIR ENTHALPY IS BELOW THE RETURN AIR ENTHALPY, THE OUTSIDE AIR DAMPER SHALL MODULATE CLOSED. THIS SHALL CONTINUE UNTIL THE SETPOINT IS ACHIEVED OR THE DAMPER IS IN THE MINIMUM OUTSIDE AIR POSITION. 3. IF THE SETPOINT CANNOT BE ACHIEVED BY DAMPER MODULATION, THE HEATING COIL CONTROL VALVE SHALL MODULATE OPEN TO MAINTAIN SETPOINT. 4. IF THE SETPOINT CANNOT BE ACHIEVED BY DAMPER MODULATION, THE HEATING COIL CONTROL VALVE SHALL MODULATE OPEN TO MAINTAIN SETPOINT. THE HEATING COIL PUMP SHALL START ON A CALL FOR HEAT IF THE OUTDOOR AIR REFERENCE TEMPERATURE IS BELOW 40° F (ADJUSTABLE). IF THE CURRENT STATUS SWITCH ON THE PUMP DOES NOT PROVE OPERATION, SEND AN ALARM TO THE OPERATOR INTERFACE. 5. IF THE SETPOINT CANNOT BE ACHIEVED BY DAMPER MODULATION, THE HEATING COIL CONTROL VALVE SHALL BE FULLY OPEN AND THE FACE AND BYPASS DAMPERS SHALL MODULATE TO MAINTAIN SETPOINT. 6. IF THE DISCHARGE AIR TEMPERATURE IS MORE THAN 10ºF (ADJUSTABLE) BELOW THE SETPOINT, SEND AN ALARM TO THE OPERATOR INTERFACE.
% RELATIVE HUMIDITY INCHES W.C.
20
DISCHARGE AIR TEMPERATURE SETPOINT SHALL BE 55ºF (ADJUSTABLE).
T H
K D A
O
11/25/14
MINIMUM OUTSIDE AIR: WHENEVER THE AIR HANDLING UNIT IS IN OCCUPIED MODE, THE OUTSIDE AIR DAMPER SHALL BE OPEN TO AT LEAST ITS MINIMUM POSITION. MIXED AIR TEMPERATURE: MONITOR THE MIXED AIR TEMPERATURE.
No.
Description
Date
AIRFLOW STATION: THE RETURN AIR DAMPER AND THE RELIEF AIR DAMPER SHALL MODULATE IN OPPOSITION TO MAINTAIN THE MINIMUM SCHEDULED OUTSIDE AIR CFM.
INCHES W.C. PARTS PER MILLION PARTS PER MILLION PARTS PER MILLION
CARBON DIOXIDE: THE OUTSIDE AIR DAMPER SHALL HAVE A MINIMUM POSITION THAT CORRESPONDS TO 5% (ADJUSTABLE) OF FULL AIRFLOW. THE OUTSIDE AIR DAMPER SHALL MODULATE TO MAINTAIN A RETURN AIR CARBON DIOXIDE LEVEL OF 700 PPM (ADJUSTABLE) ABOVE THE OUTSIDE AIR REFERENCE CARBON DIOXIDE LEVEL. THE MIXED AIR TEMPERATURE SHALL NOT BE ALLOWED TO FALL BELOW 40° F (ADJUSTABLE). AN ALARM SHALL BE SENT TO THE OPERATOR INTERFACE IF THE RETURN AIR CARBON DIOXIDE LEVEL EXCEEDS 1800 PPM. THE RETURN AIR DAMPER SHALL MODULATE IN OPPOSITION TO THE OUTSIDE AIR DAMPER AND THE RELIEF AIR DAMPER SHALL MODULATE IN UNISON WITH THE OUTSIDE AIR DAMPER. THE OUTSIDE AIRFLOW QUANTITY SHALL BE THE MAXIMUM OF THE DISCHARGE AIR CONTROL OR CARBON DIOXIDE CONTROL. UNIT SHUTDOWN:
THE SUPPLY, AND RETURN, AND RELIEF FANS SHALL STOP. THE OUTSIDE AIR DAMPERS AND RELIEF AIR DAMPERS SHALL CLOSE AND THE RETURN DAMPERS SHALL OPEN. THE CHILLED WATER CONTROL VALVE(S) SHALL CLOSE. THE ASSOCIATED CONDENSING UNIT SHALL BE DISABLED. THE HUMIDIFIER CONTROL VALVE AND THE HUMIDIFIER SHUT-OFF VALVE SHALL CLOSE. THE HEATING COIL CONTROL VALVE(S) SHALL CLOSE. FREEZESTAT SHALL OVERRIDE HEATING CONTROL VALVE(S) AS REQUIRED. ALL FIRE/SMOKE AND SMOKE DAMPERS ASSOCIATED WITH THE AIR HANDLING SYSTEM SHALL CLOSE.
UNOCCUPIED CONTROL:
OCCUPIED/UNOCCUPIED SCHEDULE SHALL BE SET AT THE OPERATOR INTERFACE. THE SUPPLY AND RETURN FANS SHALL SHUTDOWN. WHEN USING CONSTANT VOLUME OFFSET FOR RETURN AIR FAN CONTROL, THE OFFSET SHALL GO TO ZERO AND SUPPLY FAN SHALL BE LIMITED TO THE MAXIMUM RETURN FAN AIRFLOW. THE MINIMUM OUTSIDE AIR, OUTSIDE AIR, AND RELIEF AIR DAMPERS SHALL CLOSE AND THE RETURN AIR DAMPER SHALL OPEN. ECONOMIZER CYCLE SHALL TAKE PRECEDENCE OVER DAMPER POSITION. IF ANY OF THE SPACE TEMPERATURES FALL BELOW 60ºF (ADJUSTABLE), THE DDC SYSTEM SHALL RESTART THE SUPPLY AND RETURN FANS AND COOLING CAPABILITIES SHALL BE DISABLED. THE FANS SHALL CONTINUE RUNNING UNTIL THE SPACE TEMPERATURE RISES 5ºF (ADJUSTABLE). IF ANY OF THE SPACE TEMPERATURES RISE ABOVE 80ºF (ADJUSTABLE), THE DDC SYSTEM SHALL RESTART THE SUPPLY AND RETURN FANS AND MAINTAIN THE DISCHARGE AIR TEMPERATURE SETPOINT. THE FANS SHALL CONTINUE RUNNING UNTIL THE SPACE TEMPERATURE FALLS 5ºF (ADJUSTABLE). HEATING OPTIMUM START-UP: THIS CYCLE SHALL OVERRIDE THE UNOCCUPIED CYCLE. IF THE SYSTEM WAS OPERATING AS A RESULT OF THE UNOCCUPIED CYCLE, THE SYSTEM SHALL CONTINUE TO OPERATE. THE DDC SYSTEM SHALL MEASURE EACH OF THE SPACE TEMPERATURES AND THE OUTSIDE AIR DRY BULB REFERENCE TEMPERATURE TO DETERMINE THE MINIMUM RUN TIME TO WARM THE SPACES TO THEIR SETPOINT. WHEN THE COMPUTED START TIME IS REACHED, THE DDC SYSTEM SHALL START THE AIR HANDLING SYSTEM AND OPERATE WITH THE OUTSIDE AIR AND RELIEF AIR DAMPERS CLOSED AND THE RETURN AIR DAMPER OPEN. THE AIR HANDLING UNIT DISCHARGE AIR TEMPERATURE SHALL BE MAINTAINED AT A SETPOINT OF 85ºF (ADJUSTABLE). THE SYSTEM SHALL CONTINUE TO OPERATE IN THIS MODE UNTIL ALL TEMPERATURES EXCEED A SETPOINT OF 65ºF (ADJUSTABLE). AT THAT TIME, THE DDC SYSTEM SHALL SWITCH TO OCCUPIED CONTROL. THE VENTILATION AIR CONTROL SHALL BE INACTIVE. COOLING OPTIMUM START-UP: THE DDC SYSTEM SHALL MEASURE EACH OF THE SPACE TEMPERATURES AND THE OUTSIDE AIR DRY BULB REFERENCE TEMPERATURE TO DETERMINE THE MINIMUM RUN TIME TO COOL THE SPACES TO THEIR SETPOINT. WHEN THE COMPUTED START TIME IS REACHED, THE DDC SYSTEM SHALL START THE AIR HANDLING SYSTEM AND OPERATE WITH OUTSIDE AIR AND RELIEF AIR DAMPERS CLOSED AND THE RETURN AIR DAMPER OPEN. THE AIR HANDLING UNIT DISCHARGE AIR TEMPERATURE SHALL BE MAINTAINED AT A SETPOINT OF 55ºF (ADJUSTABLE). THE SYSTEM SHALL CONTINUE TO OPERATE IN THIS MODE UNTIL ALL SPACE TEMPERATURES ARE LESS THAN A SETPOINT OF 78ºF (ADJABLE). AT THAT TIME, THE DDC SYSTEM SHALL SWITCH TO OCCUPIED CONTROL. THE ECONOMIZER CYCLE SHALL TAKE PRECEDENCE OVER THIS MODE OF CONTROL. THE VENTILATION AIR CONTROL SHALL BE INACTIVE.
FILTER MONITORING:
FOR EACH FILTER BANK WITH RATING OF MERV 8 AND BELOW, PROVIDE AN ALARM TO THE OPERATOR INTERFACE WHEN THE DIFFERENTIAL STATIC PRESSURE EXCEEDS 0.75" W.C. (ADJUSTABLE). FOR EACH FILTER BANK WITH RATING OF MERV 14 AND ABOVE, PROVIDE AN ALARM TO THE OPERATOR INTERFACE WHEN THE DIFFERENTIAL STATIC PRESSURE EXCEEDS 1.25" W.C. (ADJUSTABLE).
ALARM MONITORING:
FREEZESTAT: INSTALL AN ELECTRIC FREEZESTAT, LOCATED DOWNSTREAM OF THE HEATING COIL PER MANUFACTURER'S RECOMMENDATION, TO SHUT DOWN THE UNIT IF THE TEMPERATURE DOWNSTREAM OF THE HEATING COIL DROPS BELOW 35ºF (ADJUSTABLE). THE ELECTRIC FREEZESTAT SHALL ACT INDEPENDENTLY OF THE DDC SYSTEM VIA RELAYS AND SHALL OVERRIDE THE DDC SYSTEM TO SHUT DOWN THE AIR HANDLING UNIT. A SECOND SET OF CONTACTS SHALL NOTIFY THE DDC SYSTEM THAT SHALL SEND AN ALARM TO THE OPERATOR INTERFACE (MANUAL RESET TYPE). FIRE ALARM INTERFACE: UPON ACTUATION OF THE FIRE ALARM SYSTEM, THE UNIT SHALL BE SHUT DOWN AND ALL FIRE/SMOKE AND SMOKE DAMPERS WITHIN THIS SYSTEM SHALL CLOSE. THE FIRE ALARM SYSTEM SHALL NOTIFY THE OPERATOR INTERFACE WHENEVER AN ALARM CONDITION IS EXPERIENCED.
GENERAL NOTES REMARKS (1) E = ELECTRIC (2) A = ANALOG (3) I = INPUT (4) G = GENERAL (5) T = TRENDING
1
P = PNEUMATIC B = BINARY O = OUTPUT C = CRITICAL E = EVENT HISTORY
S = REFERENCED POINT FROM HARDWARE ELSEWHERE ON DDC NETWORK
H = HIGH LIMIT A = ARCHIVE
L = LOW LIMIT TT=TOTALIZATION
O = BY OTHERS
F = FAILURE G = GRAPHICAL POINT
1. 2. 3. 4. 5.
SERVICE DISCONNECT PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR SHALL BE LOCATED WITHIN 6 FEET OF CONTROLLER. CONTROLLER SHALL HAVE A MINIMUM SERVICE CLEARANCE OF 24 INCHES AND MUST BE WITHIN 3 FEET OF CEILING. WIRE ALL SENSORS AND CONTROL DEVICES BACK TO CONTROLLER. COORDINATE ALL CASING AND DUCT PENETRATIONS WITH FURNISHING CONTRACTOR. ENSURE ALL PENETRATIONS ARE PROPERLY SEALED. DUCT STATIC PRESSURE SENSORS SHALL BE LOCATED APPROXIMATELY 2/3 OF THE DUCT RUN AWAY FROM THE AIR HANDLING EQUIPMENT. REFER TO FLOOR PLANS FOR LOCATIONS.
SACRED HEART
2014
C
4TH & 5TH CONTROL SCHEMATICS
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520
AHU-10 CONTROL NONE www.specializedeng.com
Date
SES PROJECT # 14041
11/25/2014 4:38:49 PM
M990 Scale
NONE
LOOP #1
LOOP #2
5
TO/FROM SECONDARY PUMPS
10
TO/FROM PRIMARY PUMPS
TO/FROM LOAD
SPACE BOUNDARY
TO/FROM LOAD
AVERA FACILITY DEVELOPMENT H
4
9
T 8
06
6
02
1
3
04
05
HWR
ACTUATOR CHILLED WATER SYSTEM INTERCONNECTION HEAT EXCHANGER
T
C CONTROLLER
HWS
2
S
03
08
01
07 7 TEMPERATURE CONTROL WIRING (TYP.)
DIRECT DIGITAL CONTROL POINTS LIST
DIRECT DIGITAL CONTROL POINTS LIST POINT ID
SPACE BOUNDARY
SOURCE (1)
TYPE (2)
I/O (3)
SETPOINT ADJUSTMENT
ALARMS (4)
APPLICATIONS (5)
UNITS
POINT ID
SOURCE (1)
TYPE (2)
I/O (3)
SETPOINT ADJUSTMENT
ALARMS (4)
APPLICATIONS (5)
UNITS
01
LOOP #1 HEAT EXCHANGER ENTERING TEMPERATURE
E
A
I
NO
-
T, A, G
DEGREES F
01
TERMINAL AIR BOX DISCHARGE AIR TEMPERATURE
E
A
I
NO
-
T, A, G
DEGREES F
02
LOOP #1 HEAT EXCHANGER LEAVING TEMPERATURE
E
A
I
NO
-
T, A, G
DEGREES F
02
SPACE TEMPERATURE SETPOINT
E
A
I
YES
-
T, A, G
DEGREES F
03
LOOP #1 HEAT EXCHANGER CONTROL VALVE
E
A
O
NO
-
G
100% OPEN
03
SPACE TEMPERATURE
E
A
I
NO
G, H, L
T, A, G
DEGREES F
04
LOOP #1 DIVERTER VALVE
E
A
O
NO
-
G
SUPPLY/RETURN
04
TERMINAL AIR BOX DAMPER ACTUATOR
E
A
O
NO
-
-
-
05
LOOP #1 SELECTOR VALVE
E
A
O
NO
-
G
HX/LOOP
05
TERMINAL AIR BOX DAMPER POSITION
E
A
I
NO
-
T, A, G
% OPEN
1.
SERVICE DISCONNECT PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR SHALL BE LOCATED WITHIN 6 FEET OF CONTROLLER.
06
LOOP #2 HEAT EXCHANGER ENTERING TEMPERATURE
E
A
I
NO
-
T, A, G
DEGREES F
06
AIRFLOW VOLUME
E
A
I
NO
-
T, A, G
CFM
2.
CONTROLLER SHALL HAVE A MINIMUM SERVICE CLEARANCE OF 24 INCHES AND MUST BE WITHIN 3 FEET OF CEILING.
07
LOOP #2 HEAT EXCHANGER LEAVING TEMPERATURE
E
A
I
NO
-
T, A, G
DEGREES F
07
REHEAT COIL CONTROL VALVE
E
A
O
NO
-
-
-
3.
WHERE MULTIPLE SPACES ARE SEVERED BY A SINGLE TERMINAL AIR BOX, WIRE ALL OCCUPANCY SENSORS TO TERMINAL AIR BOX CONTROLLER.
08
LOOP #2 HEAT EXCHANGER CONTROL VALVE
E
A
O
NO
-
G
100% OPEN
08
OCCUPANCY SENSOR
E
B
I
NO
-
T, A, G
OCC/UNOCC
09
LOOP #2 DIVERTER VALVE
E
A
O
NO
-
G
SUPPLY/RETURN
10
LOOP #2 SELECTOR VALVE
E
A
O
NO
-
G
HX/LOOP
SEQUENCE OF OPERATION H
T PERIMETER RADIATION
02
REMARKS (1) E = ELECTRIC (2) A = ANALOG (3) I = INPUT (4) G = GENERAL (5) T = TRENDING
CONTROLLER TEMPERATURE CONTROL WIRING (TYP.)
ON A FALL IN SPACE TEMPERATURE THE PERIMETER RADIATION CONTROL VALVE SHALL MODULATE OPEN IN UNTIL SETPOINT IS MAINTAINED.
HWS
WHEN THE OUTDOOR REFERENCE TEMPERATURE IS ABOVE 65°F (ADJUSTABLE) THE PERIMETER RADIATION CONTROL VALVE SHALL BE CLOSED. WHEN THE OUTDOOR REFERENCE TEMPERATURE IS BELOW 65°F (ADJUSTABLE) THE PERIMETER RADIATION CONTROL VALVE SHALL BE ALLOWED TO OPERATE BASED ON THE FOLLOWING:
HWR
C
03
DESCRIPTION
DIRECT DIGITAL CONTROL POINTS LIST
O = BY OTHERS
HEAT EXCHANGER CONTROL:
SOURCE (1)
TYPE (2)
I/O (3)
SETPOINT ADJUSTMENT
ALARMS (4)
APPLICATIONS (5)
UNITS
E
A
I
YES
-
T, A, G
DEGREES F
02
SPACE TEMPERATURE
E
A
I
NO
G, H, L
T, A, G
DEGREES F
03
PERIMETER RADIATION CONTROL VALVE
E
A
O
NO
-
-
-
04
OUTDOOR REFERENCE DRY BULB TEMPERATURE
S
A
I
NO
-
-
-
SEQUENCE OF OPERATION H = HIGH LIMIT A = ARCHIVE
L = LOW LIMIT TT=TOTALIZATION
F = FAILURE G = GRAPHICAL POINT
EACH ZONE HAS A TERMINAL AIR BOX WITH A HOT WATER REHEAT COIL, REHEAT COIL CONTROL VALVE, AND DIRECT DIGITAL CONTROLLER. INSTALL A SINGLE POINT TEMPERATURE SENSOR 2'-0" DOWNSTREAM OF THE REHEAT COIL. INSTALL A WALL MOUNTED TEMPERATURE SENSOR TO MAINTAIN SPACE TEMPERATURE OF 72°F (ADJUSTABLE) WITH A DEAD BAND RANGE OF 5°F WITHIN WHICH THE SUPPLY OF HEATING AND COOLING ENERGY TO THE ZONE IS REDUCED TO A MINIMUM. SEE DRAWINGS FOR TEMPERATURE SENSOR REQUIREMENTS.
THE SYSTEM CONSISTS OF A PLATE AND FRAME HEAT EXCHANGER INTERCONNECTING TWO EXISTING CHILLED WATER LOOPS. LOOP #1 IS A CONSTANT PRIMARY, VARIABLE SECONDARY ARRANGEMENT CONSISTING OF TWO WATER COOLED CHILLERS. LOOP #2 IS A VARIABLE PRIMARY ARRANGMENT CONSISTING OF ONE AIR COOLED CHILLER.
WHEN THE SENSOR INDICATES THAT THE ROOM IS OCCUPIED, THE TERMINAL AIR BOX SERVING THE ROOM WILL OPERATE IN ITS NORMAL MODE. WHEN THE SENSOR INDICATES THAT THE ROOM IS UNOCCUPIED, THE TERMINAL AIR BOX SERVING THE ROOM WILL GO TO UNOCCUPIED MODE. IN UNOCCUPIED MODE, THE TERMINAL AIR BOX WILL INITIALLY CLOSE, OVERRIDING THE MINIMUM AIRFLOW SETTING. THE TERMINAL AIR BOX WILL THEN OPERATE TO MAINTAIN THE SPACE TEMPERATURE ABOVE 55 DEGREES (ADJUSTABLE) AND BELOW 85 DEGREES (ADJUSTABLE). WHERE MULTIPLE ROOMS ARE SERVED BY A SINGLE TERMINAL AIR BOX, THE TERMINAL AIR BOX WILL OPERATE IN THE OCCUPIED MODE WHENEVER ANY ONE OF THE ROOMS BEING SERVED IS DETERMINED TO BE OCCUPIED. ALL ROOMS MUST BE DETERMINED TO BE UNOCCUPIED TO INITIATE THE UNOCCUPIED MODE.
THE PRIMARY FUNCTION OF THE INTERCONNECTION IS TO PROVIDE SWING SEASON CHILLED WATER TO THE EQUIPMENT SERVED BY LOOP #1. THE SECONDARY FUNCTION IS TO PROVIDE EMERGENCY BACKUP TO THE EQUIPMENT SERVED BY LOOP #2.
AT FULL COOLING, THE TERMINAL AIR BOX SHALL BE OPEN TO MAXIMUM CFM POSITION. THE REHEAT COIL CONTROL VALVE SHALL BE CLOSED.
WHEN ALL CHILLERS ARE ENABLED AND AVAILABLE, THE CONTROL VALVES FOR THE HEAT EXCHANGER SHALL BE CLOSED AND NO HEAT TRANSFER SHALL OCCUR.
ON A FALL IN SPACE TEMPERATURE, THE TERMINAL AIR BOX SHALL MODULATE CLOSED UNTIL SPACE SETPOINT IS MAINTAINED OR UNTIL IT REACHES ITS MINIMUM CFM POSITION. THE REHEAT COIL CONTROL VALVE SHALL BE CLOSED.
WHEN THE AIR COOLED CHILLER IS ENABLED AND AVAILABLE AND THE WATER COOLED CHILLERS ARE DISABLED, THE FOLLOWING SHALL OCCUR:
ON A FURTHER FALL IN SPACE TEMPERATURE THE TERMINAL AIR BOX AND REHEAT COIL CONTROL VALVE SHALL MODULATE OPEN IN UNISON UNTIL SETPOINT IS MAINTAINED OR UNTIL SPECIFIED MAXIMUM HEATING CFM POSITION IS REACHED.
1. 2. 3. 4. 5.
THE LOOP #1 CONTROL VALVE SHALL BE 100% OPEN. THE LOOP #2 CONTROL VALVE SHALL MODULATE TO MAINTAIN LOOP #1 SUPPLY WATER TEMPERATURE SETPOINT. THE LOOP #1 DIVERTER VALVE SHALL BE SET TO SEND RETURN WATER TO FROM THE HEAT EXCHANGER TO THE SUPPLY MAIN. THE LOOP #2 DIVERTER VALVE SHALL BE SET TO SEND RETURN WATER TO FROM THE HEAT EXCHANGER TO THE RETURN MAIN. THE LOOP #1 SELECTOR VAVLE SHALL BE 50% OPEN (ADJUSTABLE). BALANCER SHALL DETERMIN %OPEN REQUIRED FOR PROPER OPERATION AND VALUE SHALL BE RECORDED WITHIN THE BAS. 6. THE LOOP #2 SELECTOR VALVE SHALL BE 100% OPEN.
RADIANT PANEL CONTROL NONE
H = HIGH LIMIT A = ARCHIVE
L = LOW LIMIT TT=TOTALIZATION
1. 2. 3. 4. 5. 6.
O = BY OTHERS
F = FAILURE G = GRAPHICAL POINT
2
OCCUPANCY OPTIMUM RECOVERY: THIS CYCLE SHALL OVERRIDE THE OCCUPIED CONTROL CYCLE. IF THE SPACE TEMPERATURE IS MORE THAN 3 DEGREES (ADJUSTABLE) BELOW THE OCCUPIED SETPOINT AND ANY OCCUPANCY SENSOR INDICATES OCCUPANCY, THE VAV BOX AND REHEAT COIL CONTROL VALVE SHALL MODULATE TO FULLY OPEN AND SHALL REMAIN FULLY OPEN UNTIL SETPOINT IS REACHED. ONCE SETPOINT IS REACHED, CONTROL SHALL RETURN TO NORMAL OPERATION. IF THE SPACE TEMPERATURE IS MORE THAN 3 DEGREES (ADJUSTABLE) ABOVE THE OCCUPIED SETPOINT AND ANY OCCUPANCY SENSOR INDICATES OCCUPANCY, THE VAV BOX SHALL MODULATE TO FULLY OPEN AND THE REHEAT COIL CONTROL VALVE SHALL MODULATE TO FULLY CLOSED AND THEY SHALL REMAIN AT THESE OPERATING POINTS UNTIL SETPOINT IS REACHED. ONCE SETPOINT IS REACHED, CONTROL SHALL RETURN TO NORMAL OPERATION.
FESSION PRO AL REG
. NO.
10229 ERIC G. SHERMAN U
T H
K D A
O
11/25/14
No.
Description
Date
THE DDC SYSTEM SHALL UTILIZE FEEDBACK FROM ALL TERMINAL AIR BOX POSITIONS TO RESET THE SUPPLY DUCT DIFFERENTIAL STATIC PRESSURE.
THE LOOP #1 CONTROL VALVE SHALL MODULATE TO MAINTAIN LOOP #1 SUPPLY WATER TEMPERATURE SETPOINT. THE LOOP #2 CONTROL VALVE SHALL BE 100% OPEN. THE LOOP #1 DIVERTER VALVE SHALL BE SET TO SEND RETURN WATER TO FROM THE HEAT EXCHANGER TO THE RETURN MAIN. THE LOOP #2 DIVERTER VALVE SHALL BE SET TO SEND RETURN WATER TO FROM THE HEAT EXCHANGER TO THE SUPPLY MAIN. 5. THE 5. THE LOOP #1 SELECTOR VAVLE SHALL BE 100% OPEN. THE LOOP #2 SELECTOR VALVE SHALL BE 100% CLOSED.
CHILLED WATER SYSTEM INTERCONNECTION CONTROL NONE
ED
IF HEATING WATER SYSTEM TEMPERATURE IS 5°F (ADJUSTABLE) BELOW SETPOINT ON A CALL FOR HEATING THE TERMINAL AIR BOX SHALL REMAIN AT ITS MINIMUM CFM POSITION.
WHEN THE AIR COOLED CHILLER IS DISABLED AND THE WATER COOLED CHILLERS ARE ENABLED AND AVAILABLE, THE FOLLOWING SHALL OCCUR: S = REFERENCED POINT FROM HARDWARE ELSEWHERE ON DDC NETWORK
F = FAILURE G = GRAPHICAL POINT
L = LOW LIMIT TT=TOTALIZATION
O
SPACE TEMPERATURE SETPOINT
P = PNEUMATIC B = BINARY O = OUTPUT C = CRITICAL E = EVENT HISTORY
H = HIGH LIMIT A = ARCHIVE
S
01
REMARKS (1) E = ELECTRIC (2) A = ANALOG (3) I = INPUT (4) G = GENERAL (5) T = TRENDING
O = BY OTHERS
R GINEE EN
POINT DESCRIPTION
S = REFERENCED POINT FROM HARDWARE ELSEWHERE ON DDC NETWORK
S = REFERENCED POINT FROM HARDWARE ELSEWHERE ON DDC NETWORK
SEQUENCE OF OPERATION
IF HEATING WATER SYSTEM TEMPERATURE IS 5°F (ADJUSTABLE) BELOW SETPOINT ON A CALL FOR HEATING AN ALARM SHALL BE SENT TO THE OPERATOR INTERFACE.
POINT ID
P = PNEUMATIC B = BINARY O = OUTPUT C = CRITICAL E = EVENT HISTORY
P = PNEUMATIC B = BINARY O = OUTPUT C = CRITICAL E = EVENT HISTORY
A
01
REMARKS (1) E = ELECTRIC (2) A = ANALOG (3) I = INPUT (4) G = GENERAL (5) T = TRENDING
T
EACH ZONE HAS A DIRECT DIGITAL CONTROLLER AND PERIMETER RADIATION WITH PERIMETER RADIATION CONTROL VALVE. INSTALL A WALL MOUNTED TEMPERATURE SENSOR TO MAINTAIN SPACE TEMPERATURE OF 68°F (ADJUSTABLE) WITH A DEAD BAND RANGE OF 5°F WITHIN WHICH THE SUPPLY OF HEATING AND COOLING ENERGY TO THE ZONE IS REDUCED TO A MINIMUM. SEE DRAWINGS FOR TEMPERATURE SENSOR REQUIREMENTS.
3
POINT DESCRIPTION
REGIST ER
GENERAL NOTES
POINT DESCRIPTION
GENERAL NOTES 1. SERVICE DISCONNECT PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR SHALL BE LOCATED WITHIN 6 FEET OF CONTROLLER. 2. CONTROLLER SHALL HAVE A MINIMUM SERVICE CLEARANCE OF 24 INCHES AND MUST BE WITHIN 3 FEET OF CEILING. 3. WHERE MULTIPLE SPACES ARE SEVERED BY A SINGLE TERMINAL AIR BOX, WIRE ALL OCCUPANCY SENSORS TO TERMINAL AIR BOX CONTROLLER.
1
VAV BOX CONTROL - TYPICAL NONE
SACRED HEART
2014
C
4TH & 5TH CONTROL SCHEMATICS
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
Date
SES PROJECT # 14041
11/25/2014 4:38:51 PM
M991 Scale
NONE
ROOM EXHAUST BALANCED TO 12 ACH.
ROOM EXHAUST BALANCED TO 12 ACH.
NEGATIVE AIR ROOM
H MECHANICAL AIRFOW INDICATOR
CONTROLLER
06
T
C
03
02
ACTUATOR
01
04
05
CONTROLLER
07
MECHANICAL AIRFOW INDICATOR
03
01
07
TEMPERATURE CONTROL WIRING (TYP.)
TOILET ROOM
ROOM EXHAUST BALANCED TO 10 ACH.
TEMPERATURE CONTROL WIRING (TYP.)
DIRECT DIGITAL CONTROL POINTS LIST POINT ID
POINT DESCRIPTION
DIRECT DIGITAL CONTROL POINTS LIST
SOURCE (1)
TYPE (2)
I/O (3)
SETPOINT ADJUSTMENT
ALARMS (4)
APPLICATIONS (5)
UNITS
POINT ID
POINT DESCRIPTION
SOURCE (1)
TYPE (2)
I/O (3)
SETPOINT ADJUSTMENT
ALARMS (4)
APPLICATIONS (5)
UNITS
01
TERMINAL AIR BOX DISCHARGE AIR TEMPERATURE
E
A
I
NO
-
T, A, G
DEGREES F
01
TERMINAL AIR BOX DISCHARGE AIR TEMPERATURE
E
A
I
NO
-
T, A, G
DEGREES F
02
SPACE TEMPERATURE SETPOINT
E
A
I
YES
-
T, A, G
DEGREES F
02
SPACE TEMPERATURE SETPOINT
E
A
I
YES
-
T, A, G
DEGREES F
03
SPACE TEMPERATURE
E
A
I
NO
G, H, L
T, A, G
DEGREES F
03
SPACE TEMPERATURE
E
A
I
NO
G, H, L
T, A, G
DEGREES F
04
TERMINAL AIR BOX DAMPER ACTUATOR
E
A
O
NO
-
-
-
04
TERMINAL AIR BOX DAMPER ACTUATOR
E
A
O
NO
-
-
-
05
TERMINAL AIR BOX DAMPER POSITION
E
A
I
NO
-
T, A, G
% OPEN
05
TERMINAL AIR BOX DAMPER POSITION
E
A
I
NO
-
T, A, G
% OPEN
06
AIRFLOW VOLUME
E
A
I
NO
-
T, A, G
CFM
06
AIRFLOW VOLUME
E
A
I
NO
-
T, A, G
CFM
07
REHEAT COIL CONTROL VALVE
E
A
O
NO
-
-
-
07
REHEAT COIL CONTROL VALVE
E
A
O
NO
-
-
-
REMARKS (1) E = ELECTRIC (2) A = ANALOG (3) I = INPUT (4) G = GENERAL (5) T = TRENDING
P = PNEUMATIC B = BINARY O = OUTPUT C = CRITICAL E = EVENT HISTORY
S = REFERENCED POINT FROM HARDWARE ELSEWHERE ON DDC NETWORK
O = BY OTHERS
H = HIGH LIMIT A = ARCHIVE
F = FAILURE G = GRAPHICAL POINT
L = LOW LIMIT TT=TOTALIZATION
REMARKS (1) E = ELECTRIC (2) A = ANALOG (3) I = INPUT (4) G = GENERAL (5) T = TRENDING
P = PNEUMATIC B = BINARY O = OUTPUT C = CRITICAL E = EVENT HISTORY
S = REFERENCED POINT FROM HARDWARE ELSEWHERE ON DDC NETWORK
O = BY OTHERS
H = HIGH LIMIT A = ARCHIVE
F = FAILURE G = GRAPHICAL POINT
L = LOW LIMIT TT=TOTALIZATION
EACH ZONE HAS A TERMINAL AIR BOX WITH A HOT WATER REHEAT COIL, REHEAT COIL CONTROL VALVE, AND DIRECT DIGITAL CONTROLLER. INSTALL A SINGLE POINT TEMPERATURE SENSOR 2'-0" DOWNSTREAM OF THE REHEAT COIL. INSTALL A WALL MOUNTED TEMPERATURE SENSOR TO MAINTAIN SPACE TEMPERATURE OF 72°F (ADJUSTABLE) WITH A DEAD BAND RANGE OF 5°F WITHIN WHICH THE SUPPLY OF HEATING AND COOLING ENERGY TO THE ZONE IS REDUCED TO A MINIMUM. SEE DRAWINGS FOR TEMPERATURE SENSOR REQUIREMENTS.
EACH ZONE HAS A TERMINAL AIR BOX WITH A HOT WATER REHEAT COIL, REHEAT COIL CONTROL VALVE, AND DIRECT DIGITAL CONTROLLER. INSTALL A SINGLE POINT TEMPERATURE SENSOR 2'-0" DOWNSTREAM OF THE REHEAT COIL. INSTALL A WALL MOUNTED TEMPERATURE SENSOR TO MAINTAIN SPACE TEMPERATURE OF 72°F (ADJUSTABLE) WITH A DEAD BAND RANGE OF 5°F WITHIN WHICH THE SUPPLY OF HEATING AND COOLING ENERGY TO THE ZONE IS REDUCED TO A MINIMUM. SEE DRAWINGS FOR TEMPERATURE SENSOR REQUIREMENTS.
AT FULL COOLING, THE TERMINAL AIR BOX SHALL BE OPEN TO MAXIMUM CFM POSITION. THE REHEAT COIL CONTROL VALVE SHALL BE CLOSED.
AT FULL COOLING, THE TERMINAL AIR BOX SHALL BE OPEN TO MAXIMUM CFM POSITION. THE REHEAT COIL CONTROL VALVE SHALL BE CLOSED.
ON A FALL IN SPACE TEMPERATURE THE REHEAT COIL CONTROL VALVE SHALL MODULATE OPEN IN UNISON UNTIL SETPOINT IS MAINTAINED.
ON A FALL IN SPACE TEMPERATURE THE REHEAT COIL CONTROL VALVE SHALL MODULATE OPEN IN UNISON UNTIL SETPOINT IS MAINTAINED.
IF THE SPACE TEMPERATURE VARIES MORE THAN 5°F (ADJUSTABLE) FROM SETPOINT, SEND ALARM TO THE OPERATOR INTERFACE.
IF THE SPACE TEMPERATURE VARIES MORE THAN 5°F (ADJUSTABLE) FROM SETPOINT, SEND ALARM TO THE OPERATOR INTERFACE.
THE DDC SYSTEM SHALL UTILIZE FEEDBACK FROM ALL TERMINAL AIR BOX POSITIONS TO RESET THE SUPPLY DUCT DIFFERENTIAL STATIC PRESSURE.
THE DDC SYSTEM SHALL UTILIZE FEEDBACK FROM ALL TERMINAL AIR BOX POSITIONS TO RESET THE SUPPLY DUCT DIFFERENTIAL STATIC PRESSURE.
GENERAL NOTES 1. SERVICE DISCONNECT PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR SHALL BE LOCATED WITHIN 6 FEET OF CONTROLLER. 2. CONTROLLER SHALL HAVE A MINIMUM SERVICE CLEARANCE OF 24 INCHES AND MUST BE WITHIN 3 FEET OF CEILING. 3. WHERE MULTIPLE SPACES ARE SEVERED BY A SINGLE TERMINAL AIR BOX, WIRE ALL OCCUPANCY SENSORS TO TERMINAL AIR BOX CONTROLLER. 4. SEAL ALL SPACE BOUNDARY PENETRATIONS AIR TIGHT. PENETRATION SEALS MUST INCLUDE EXTERIOR AND INTERIOR OF CONDUITS.
GENERAL NOTES 1. SERVICE DISCONNECT PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR SHALL BE LOCATED WITHIN 6 FEET OF CONTROLLER. 2. CONTROLLER SHALL HAVE A MINIMUM SERVICE CLEARANCE OF 24 INCHES AND MUST BE WITHIN 3 FEET OF CEILING. 3. WHERE MULTIPLE SPACES ARE SEVERED BY A SINGLE TERMINAL AIR BOX, WIRE ALL OCCUPANCY SENSORS TO TERMINAL AIR BOX CONTROLLER. 4. SEAL ALL SPACE BOUNDARY PENETRATIONS AIR TIGHT. PENETRATION SEALS MUST INCLUDE EXTERIOR AND INTERIOR OF CONDUITS.
REGIST ER
SEQUENCE OF OPERATION
ED
FESSION PRO AL
S O
2
NEGATIVE AIR ROOM CONTROL
1
NONE
ISOLATION ROOM CONTROL NONE
REG
. NO.
R GINEE EN
SEQUENCE OF OPERATION
10229 ERIC G. SHERMAN U
A
05
HWR
04
HWS
02
ACTUATOR
T
T
C
MECHANICAL AIRFOW INDICATOR
TOILET ROOM
T
06
AVERA FACILITY DEVELOPMENT
ANTEROOM
H
HWS
T
ROOM SUPPLY AIR BALANCED TO MAINTAIN -0.01IN W.C. DIFFERENTIAL PRESSURE BETWEEN ROOM AND CORRIDOR.
HWR
ROOM SUPPLY AIR BALANCED TO MAINTAIN -0.01IN W.C. DIFFERENTIAL PRESSURE BETWEEN ROOM AND CORRIDOR.
NEGATIVE AIR ROOM
ROOM EXHAUST BALANCED TO 10 ACH.
ANTIROOM EXHAUST BALANCED TO 12 ACH.
T H
K D A
O
11/25/14
No.
Description
Date
GENERAL NOTES 1.
SERVICE DISCONNECT PROVIDED AND INSTALLED BY ELECTRICAL CONTRACTOR SHALL BE LOCATED WITHIN 6 FEET OF CONTROLLER.
2.
CONTROLLER SHALL HAVE A MINIMUM SERVICE CLEARANCE OF 24 INCHES. THE TERMINAL BOX CONTROLLER MUST BE WITHIN 3 FEET OF CEILING.
FAN
MOTOR CONTROLLER 01 02
SEQUENCE OF OPERATION EACH FAN HAS AN ISOLATION DAMPER WITH END SWITCH TO PROVE DAMPER OPEN AND CURRENT STATUS SWITCH TO PROVE FAN OPERATION. IF THE END SWITCH DOES NOT PROVE OPEN, SEND AN ALARM TO THE OPERATOR INTERFACE. IF THE CURRENT STATUS SWITCH DOES NOT PROVE OPERATION, SEND AND ALARM TO THE USER INTERFACE.
ACTUATOR 03
04
FAN SHALL RUN CONTINUOUSLY. MOTORIZED DAMPER SHALL CLOSE ON LOSS OF POWER TO FAN.
DIRECT DIGITAL CONTROL POINTS LIST POINT ID
POINT DESCRIPTION
TYPE (2)
I/O (3)
SETPOINT ADJUSTMENT
ALARMS (4)
APPLICATIONS (5)
UNITS
01
EXHAUST FAN STATUS
E
B
I
NO
G, F
E, A, G
ON/OFF
02
EXHAUST FAN START/STOP
E
B
0
NO
-
-
-
03
EXHAUST FAN ISOLATION DAMPER ACTUATOR
E
A
O
NO
-
T, A, G
-
04
EXHAUST FAN ISOLATION DAMPER POSITION
E
B
I
NO
F
T, A, G
OPEN/CLOSED
REMARKS (1) E = ELECTRIC (2) A = ANALOG (3) I = INPUT (4) G = GENERAL (5) T = TRENDING
3
SOURCE (1)
P = PNEUMATIC B = BINARY O = OUTPUT C = CRITICAL E = EVENT HISTORY
S = REFERENCED POINT FROM HARDWARE ELSEWHERE ON DDC NETWORK
H = HIGH LIMIT A = ARCHIVE
L = LOW LIMIT TT=TOTALIZATION
SACRED HEART
2014
C
4TH & 5TH CONTROL SCHEMATICS
COPYRIGHT
O = BY OTHERS
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW.
F = FAILURE G = GRAPHICAL POINT
DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520
EXHAUST FAN CONTROL NONE www.specializedeng.com
Date
SES PROJECT # 14041
11/25/2014 4:38:52 PM
M992 Scale
NONE
ELECTRICAL SYMBOLS LIGHTING AND POWER
CEILING TROFFER FIXTURE
X
STRIP FIXTURE
LINEAR WALL FIXTURE
X
WALL FIXTURE
DOWN LIGHT FIXTURE SHADED FIXTURES REPRESENT BATTERY PACKS OR EMERGENCY CIRCUIT
WALL MOUNTED EXIT SIGN WITH DIRECTIONAL ARROW X
CEILING MOUNTED EXIT SIGN WITH DIRECTIONAL ARROW
X X
3 D
4
SWITCH - 4-WAY
SWITCH - 3-WAY WALL BOX DIMMER
MC
SWITCH - MOMENTARY CONTACT
Z
CEILING OCCUPANCY SENSOR (CONTROL PANEL RELAY - ZONE) RECEPTACLE - SINGLE RECEPTACLE - DOUBLE DUPLEX
G
RECEPTACLE - DUPLEX - GFCI
* T
RECEPTACLE - DUPLEX - EXTRA HEAVY DUTY RECEPTACLE - DUPLEX - SAFETY TYPE (TAMPER RESISTANT)
RECEPTACLE - DOUBLE DUPLEX - EMERGENCY (RED)
RECEPTACLE - DUPLEX - EMERGENCY (RED) RECEPTACLE - DUPLEX - CEILING MOUNTED
RECEPTACLE - SPECIAL PURPOSE - (NEMA CONFIG. AS NOTED) MULTI-OUTLET ASSEMBLY - LENGTH AS INDICATED
3
RACO 697
3-1/2"
CONDUIT SIZE 1"
CONDUIT STUB LOCATION DOME LIGHT
REMARKS NOTE 1
AVERA FACILITY DEVELOPMENT
DOME LIGHT
352000
1
RACO 695
3-1/2"
1"
CABLE TRAY
NOTE 1
RACO 695
3-1/2"
1"
CABLE TRAY
NOTE 1
RACO 695
3-1/2"
1"
DOME LIGHT
NOTE 1
RACO 695
3-1/2"
1"
DOME LIGHT
NOTE 1
RACO 695
3-1/2"
1"
DOME LIGHT
NOTE 1
VERIFY
3-1/2"
VERIFY
VERIFY
--
RACO 695
3-1/2"
NOTE 4
CABLE TRAY
NOTE 1
VERIFY
VERIFY
VERIFY
VERIFY
--
COORDINATE ROUGH-IN REQUIREMENTS WITH FINAL NURSE CALL EQUIPMENT SELECTION. NC ZONE
ZONE LIGHT
352000
1
COORDINATE ROUGH-IN REQUIREMENTS WITH FINAL NURSE CALL EQUIPMENT SELECTION. NC PULL
BRANCH CIRCUIT CONCEALED IN CEILING OR WALL
TELEVISION OUTLET: REFER TO SUPPLEMENTAL SYMBOL LEGENDS AND DETAILS FOR FURTHER REQUIREMENTS.
TV
J J J PHOTOCELL
PULL CORD
354001
1
CIRCUIT UP CONDUIT STUB-OUT
SPECIAL PURPOSE HOMERUN AS INDICATED
CIRCUIT BREAK
SAFETY SWITCH - FUSED UNLESS OTHERWISE NOTED
COMBINATION MAGNETIC STARTER/DISCONNECT SWITCH & FUSE FLOOR SLEEVE DESIGNATION
"W" INDICATES WALL MOUNTED UNLESS NOTED OTHERWISE
AUTOMATIC SMOKE DETECTOR - CEILING
F
STROBE - CEILING
AUTOMATIC HEAT DETECTOR - CEILING
F
SAMPLING TUBE TYPE SMOKE DETECTOR
F
HORN - CEILING HORN & STROBE COMBINATION - CEILING
F
SPEAKER - CEILING
F
MAGNETIC DOOR HOLDER
F
SPEAKER & STROBE COMBINATION - CEILING CHIME - CEILING
F
FIRE SPRINKLER VALVE TAMPER SWITCH
F
CHIME & STROBE COMBINATION - CEILING
F F
FIRE SPRINKLER FLOW SWITCH
F CM
CONTROL MODULE
MANUAL STATION
F MM
MONITORING MODULE
CEILING SPEAKER
IC
INTERCOM STATION
IC
INTERCOM CONTROL PANEL
F1
SOUND EXAMPLE C5 C5S
FLOOR COMMUNICATIONS FIRE RATED PATHWAY: PROVIDE "EZ-PATH" FIRE RATED PATHWAY THROUGH FLOOR. INSTALL PER MANUFACTURERS RECOMMENDATIONS. SLEEVE DESIGNATIONS PER PLANS. PROVIDE SLEEVES AS FOLLOWS: (F1) - CATALOG NO. EZDP144FK. (1-4"x4" PATHWAY) (F2) - PROVIDE EZ-PATH GRID SYSTEM CATALOG NO. EZDG444 AND (1) PATHWAY MODULE CATALOG NO. EZD444MB. (4-4"x4" PATHWAYS) (F3) - PROVIDE EZ-PATH GRID SYSTEM CATALOG NO. EZG844 AND (1) PATHWAY MODULE CATALOG NO. EZD444MB. (4-4"x4" PATHWAYS AND 4-4"x4" SPACES) (F4) - PROVIDE EZ-PATH GRID SYSTEM CATALOG NO. EZG844 AND (2) PATHWAY MODULES CATALOG NO. EZD444MB. (8-4"x4" PATHWAYS) (F5) - PROVIDE EZ-PATH GRID SYSTEM CATALOG NO. EZG1644 AND (2) PATHWAY MODULES CATALOG NO. EZD444MB. (8-4"x4" PATHWAYS AND 8-4"x4" SPACES) (F6) - PROVIDE EZ-PATH GRID SYSTEM CATALOG NO. EZG1644 AND (3) PATHWAY MODULES CATALOG NO. EZD444MB. (12-4"x4" PATHWAYS AND 4-4"x4" SPACES) (F7) - PROVIDE EZ-PATH GRID SYSTEM CATALOG NO. EZG1644 AND (4) PATHWAY MODULES CATALOG NO. EZD444MB. (16-4"x4" PATHWAYS)
NC PB
DOOR CONTACT CR
CARD READER
DO
DOOR OPENER
SC DP
SECURITY CONTROL PANEL DOOR PLATE
C5E
MISCELLANEOUS
12x4
RT
SUBSCRIPT "RT" APPLIED TO ANY SYMBOL INDICATES RAINTIGHT NEMA 3R OR EQUIVALENT
E
SUBSCRIPT "E" ADDED TO ANY SYMBOL INDICATES EXISTING
P
SUBSCRIPT "P" ADDED TO ANY SYMBOL INDICATES PILOT LIGHT
V
SUBSCRIPT "V" ADDED TO ANY SYMBOL INDICATES VOICE
SUBSCRIPT "W" ADDED TO ANY SYMBOL INDICATES WALL PHONE
D
SUBSCRIPT "D" ADDED TO ANY SYMBOL INDICATES DATA
W #
R
SUBSCRIPT "R" ADDED TO ANY SYMBOL INDICATES REUSED
C
SUBSCRIPT "C" ADDED TO ANY SYMBOL INDICATES CEILING
PART
12x4
SHEET NOTE SUBSCRIPT "PART" ADDED TO ANY SYMBOL INDICATES PARTIAL
NC BED
EXTENSION MODULE: PROVIDE EXTENSION MODULE "EZ-PATH" CATALOG NO. EZD33E AT FIRE RATED PATHWAYS INDICATED WITH A SUBSCRPT 'E'. PROVIDE (1) EXTENSION MODULE PER SLEEVE. VERIFY QUANTITIES PER PLAN. WHERE FIRE RATED PATHWAY IS INDICATED WITH (2) 'E', PROVIDE (1) EXTENSION MODULES ON EACH END. VERTICAL CABLE MANAGEMENT: DIMENSIONS ARE INDICATED IN INCHES. FIRST NUMBER INDICATES WIDTH, SECOND NUMBER INDICATES DEPTH. REFER TO SPECIFICATIONS FOR FURTHER REQUIREMENTS. CABLE TRAY: TYPE INDICATED PER SPECIFICATION. DIMENSIONS ARE INDICATED IN INCHES. FIRST NUMBER INDICATES WIDTH, SECOND NUMBER INDICATES DEPTH. REFER TO SPECIFICATIONS FOR FURTHER REQUIREMENTS.
CONDUIT SLEEVE(S) WITH BUSHINGS: LOCATE ABOVE CEILING. SIZE AND QUANTITY AS INDICATED. REFER TO SPECIFICATIONS FOR FURTHER REQUIREMENTS.
NC MASTER
NC CP
C. THESE DRAWINGS DO NOT IDENTIFY EACH INDIVIDUAL ITEM TO BE REMOVED. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING ITEMS WHICH MUST BE REMOVED TO FACILITATE NEW CONSTRUCTION. SEE ARCHITECTURAL PLANS FOR EXACT LIMITS OF DEMOLITION AND CONSTRUCTION. THESE PLANS ARE BASED ON PAST PROJECT DRAWINGS AND SITE OBSERVATIONS. THE DRAWINGS ARE PROVIDED TO THE CONTRACTOR AS AN AID IN DETERMINING THE EXTENT OF WORK REQUIRED FOR DEMOLITION AND TO PROVIDE GENERAL INFORMATION ABOUT EXISTING SYSTEMS. THESE DRAWINGS MAY NOT BE ACCURATE IN ALL AREAS. THE CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH EXISTING CONDITIONS AND IS ENCOURAGED TO REVIEW FACILITY DRAWINGS PRIOR TO THE BID DATE. D. THE OWNER SHALL HAVE FIRST SALVAGE RIGHTS TO ALL ITEMS REMOVED. IF OWNER REFUSES SALVAGE, CONTRACTOR IS RESPONSIBLE FOR DISPOSAL. E.
WHERE EXISTING WALLS ARE TO BE REMOVED, ALL ASSOCIATED ELECTRICAL EQUIPMENT SHALL BE REMOVED. DISCONNECT POWER SO THAT DEVICES AND EQUIPMENT MAY BE REMOVED WITH WALLS. SEE ARCHITECTURAL DRAWINGS FOR WALLS TO BE REMOVED. ABANDON CONCEALED CONDUITS WHERE WALLS ARE NOT REMOVED. CONCEALED CONDUITS MAY BE REUSED WHERE AVAILABLE. WHERE EXISTING CIRCUITING/CABLING IS TO BE DEMOLISHED AND NOT REUSED, REMOVE CONDUCTORS AND ASSOCIATED ACCESSIBLE RACEWAYS/CONDUIT BACK TO THE SOURCE. WHERE EXISTING ELECTRICAL CONDUITS SERVING CIRCUITS TO BE DEMOLISHED ARE EMBEDDED IN CONCRETE FLOORS OR WALLS, CONDUITS MAY BE ABANDONED IN PLACE. EXISTING CONDUCTORS SHALL BE REMOVED BACK TO SOURCE AND CONDUITS SHALL BE CUT AT SURFACE OF CONCRETE AND FILLED. EXISTING BACK BOXES AND CONDUITS REMAINING FROM DEVICES BEING REMOVED MAY BE UTILIZED FOR NEW DEVICES WHERE LOCATIONS PERMIT. REMOVE AND PATCH WHERE BOXES ARE NOT REUSED.
MASTER STATION
351200
1
CONTROL PANEL
NC2828
VERIFY
GENERAL NOTES: 1. PROVIDE NURSE CALL DEVICE ROUGH-IN PER THE SCHEDULE. COORDINATE MOUNTING DEPTH (OR PLASTER RING WHERE APPLICABLE) TO ACCOMMODATE WALL FINISH. PROVIDE CONDUIT STUBBED FROM BOX TO ASSOCIATED NURSE CALL CORRIDOR DOME LIGHT. WHERE AN ASSOCIATED NURSE CALL CORRIDOR DOME LIGHT IS NOT AVAILABLE, STUB CONDUIT TO NEAREST CORRIDOR J-HOOK. PROVIDE DEVICE BOX WITH BACK-SIDE SUPPORT. ROUGH-INS SHALL NOT BE MOUNTED BACK-TO-BACK AND SHALL NOT SHARE CONDUITS, UNLESS SPECIFICALLY NOTED OR APPROVED BY THE MANUFACTURER. ROUTE CONDUITS CONCEALED IN WALLS AND CEILINGS. REFER TO ARCHITECTURAL INTERIOR ELEVATIONS FOR EXACT DEVICE MOUNTING LOCATIONS. WHERE DEVICES ARE NOT SHOWN IN ELEVATION, SEEK CLARIFICATION FROM ARCHITECT. PROVIDE MOCK-UPS WHERE REQUESTED. SPAN WALL STUDS WITH BRACKETS WHERE REQUIRED TO ACCOMMODATE DEVICE PLACEMENT. 2. WHERE LOCATED IN AN ARCHITECTURAL WALL, CONDUIT SHALL STUB TO THE CORRIDOR DOME LIGHT. 3. RAULAND RESPONDER V IS USED AS BASIS OF DESIGN FOR SPECIFIED NURSE CALL SYSTEM ROUGH-IN REQUIREMENTS. VERIFY FINAL MANUFACTURER AND PRODUCTS AND COORDINATE REQUIREMENTS WITH OWNER PRIOR TO INSTALLATION. 4. PROVIDE 1" METALLIC SURFACE RACEWAY, MOUNT TO VERTICAL MULLION, AT LOCATION OF CURRENT SURFACE RACEWAY FOR NURSE CALL CABLING. 5. NURSE CALL SYSTEM AND CABLES SHALL BE OWNER FURNISHED AND OWNER INSTALLED. 6. PROVIDE INDIVIDUAL 1" CONDUIT STUB OUTS FOR EACH NURSE CALL ROUGH-IN INDICATED.
A.
LIGHTING GENERAL NOTES
POWER GENERAL NOTES
(LIGHTING GENERAL NOTES SHALL APPLY TO ALL SHEETS)
(POWER GENERAL NOTES SHALL APPLY TO ALL SHEETS)
LIGHTING CONTROL DEVICES ARE INDICATED WITHOUT CONNECTION TO FIXTURE(S) BEING CONTROLLED. WITHIN EACH AREA, CONNECT CONTROL DEVICE TO SERVE LIGHT FIXTURE(S) LOCATED WITHIN SAME AREA. WHERE LIGHT FIXTURES ARE INDICATED WITH A SUBSCRIPT LETTER IDENTIFYING INDIVIDUAL LIGHTING CONTROL ZONES, CONTROL DEVICE SERVING AREA WITH MATCHING SUBSCRIPT SHALL CONTROL CORRESPONDING LIGHT FIXTURES.
B.
BRANCH CIRCUITS WITH A TOTAL LENGTH LONGER THAN 75'-0" SHALL UTILIZE #10 AWG CONDUCTORS. C. SWITCHES SERVING UNDERCABINET TASK LIGHTING SHALL MATCH RECEPTACLE HEIGHT ABOVE COUNTER. D. LIGHTING CONTROL DEVICE MOUNTING HEIGHTS ARE NOT INDICATED ON ELECTRICAL FLOOR PLANS. CONTRACTOR SHALL COORDINATE EXACT DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH ARCHITECTURAL INTERIOR ELEVATIONS. WHERE DEVICE MOUNTING HEIGHTS ARE NOT INDICATED PER ARCHITECT, MOUNT DEVICES AT HEIGHT INDICATED IN ELECTRICAL PROJECT SPECIFICATIONS. E.
CONTRACTOR SHALL COORDINATE ALL LIGHTING CONTROL DEVICE ROUGH-IN LOCATIONS AND ELEVATIONS WITH ARCHITECTURAL DRAWINGS TO ASSURE COMPATIBILITY WITH FINISHES SPECIFIED ON THE ARCHITECTURAL DRAWINGS. COORDINATE ROUTING OF ALL ELECTRICAL BRANCH CIRCUITS AND CONDUIT WITH OTHER TRADES TO ALLOW FOR SERVICE AND MAINTENANCE AND TO MINIMIZE THE USE OF ACCESS PANELS. WHERE ACCESS PANELS CANNOT BE AVOIDED, WORK TO INSTALL PANELS IN LOCATIONS ACCEPTABLE TO ARCHITECT. REFER TO PROJECT MANUAL AND ARCHITECTURAL DRAWINGS FOR LIMITS OF CONSTRUCTION FOR EACH PHASE.
G. REFER TO DETAILS, SCHEDULES, AND SUPPLEMENTAL LEGENDS FOR ADDITIONAL REQUIREMENTS.
A.
ELECTRICAL DEVICE MOUNTING HEIGHTS ARE NOT INDICATED ON ELECTRICAL FLOOR PLANS. CONTRACTOR SHALL COORDINATE EXACT DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH ARCHITECTURAL INTERIOR ELEVATIONS. WHERE DEVICE MOUNTING HEIGHTS ARE NOT INDICATED PER ARCHITECT, MOUNT DEVICES AT HEIGHT INDICATED IN ELECTRICAL PROJECT SPECIFICATIONS.
B.
CONTRACTOR SHALL COORDINATE ALL ELECTRICAL DEVICE ROUGH-IN LOCATIONS AND ELEVATIONS WITH ARCHITECTURAL DRAWINGS TO ASSURE COMPATIBILITY WITH FINISHES SPECIFIED ON THE ARCHITECTURAL DRAWINGS. ROUTE ALL ELECTRICAL BRANCH CIRCUITS AND CONDUITS SPECIFIED, TO COORDINATE WITH OTHER TRADES AND TO ALLOW FOR SERVICE AND MAINTENANCE AND TO MINIMIZE THE USE OF ACCESS PANELS. WHERE ACCESS PANELS CANNOT BE AVOIDED, ARRANGE WORK TO INSTALL PANELS IN LOCATIONS ACCEPTABLE TO ARCHITECT.
C. BRANCH CIRCUIT WITH A TOTAL LENGTH LONGER THAN 75'-0" SHALL UTILIZE #10 AWG CONDUCTORS. D. REFER TO DETAILS, SCHEDULES, AND SUPPLEMENTAL LEGENDS FOR ADDITIONAL REQUIREMENTS. E. BRANCH CIRCUITS SERVING PATIENT CARE AREAS SHALL UTILIZE A CONTINUOUS METALLIC CONDUIT PATH FOR GROUNDING IN ADDITION TO AN INSULATED EQUIPMENT GROUNDING CONDUCTOR. REFER TO SPECIFICATIONS FOR CONDUIT AND CABLE WIRING METHODS ALLOWED AND DISALLOWED FOR APPLICATION ON THIS PROJECT. F.
ED
FESSION PRO AL RE
G . NO.
10206 TRACY J. HAUSER U
T H
K D A
O
11/25/14
No.
Description
Date
REDUNDANT GROUNDING METHODS REQUIRED FOR PATIENT CARE AREAS. REFER TO NEC FOR REQUIREMENTS AND TO PROJECT SPECIFICATIONS FOR ACCEPTABLE METHODS/APPLICATIONS.
G. REFER TO PROJECT MANUAL AND ARCHITECTURAL DRAWINGS FOR LIMITS OF CONSTRUCTION FOR EACH PHASE.
FIRE ALARM GENERAL NOTES
(ELECTRICAL DEMOLITION NOTES APPLY TO ALL ELECTRICAL DEMOLITION PLANS AND ALL ELECTRICAL DEMOLITION WORK)
ITEMS INDICATED WITH A SUBSCRIPT 'E' SHALL BE EXISTING TO REMAIN (E-EXISTING). ITEMS INDICATED WITH A SUBSCRIPT 'D' OR SHOWN HATCHED SHALL BE REMOVED (DDEMOLITION). ITEMS INDICATED WITH A SUBSCRIPT 'R' SHALL BE REMOVED, STORED, AND REINSTALLED PER NEW WORK (R-RELOCATION).
1
COORDINATE ROUGH-IN REQUIREMENTS WITH FINAL NURSE CALL EQUIPMENT SELECTION.
ELECTRICAL DEMOLITION GENERAL NOTES
B.
NCBED5
COORDINATE ROUGH-IN REQUIREMENTS WITH FINAL NURSE CALL EQUIPMENT SELECTION.
F. TELECOMMUNICATIONS RACK: PROVIDE 7' TELECOMMUNICATIONS RACK.
THE INTENT OF THE DEMOLITION DRAWINGS IS TO DEFINE THE SCOPE OF ELECTRICAL DEMOLITION WORK. EXISTING ELECTRICAL SYSTEMS (DEVICES, FIXTURES, EQUIPMENT, WIRING, AND RACEWAYS INCLUDING DATA/COMMUNICATION SYSTEMS) WITHIN LIMITS OF DEMOLITION AND NOT SERVING ADJACENT AREAS, SHALL BE REMOVED UNLESS OTHERWISE INDICATED. RE-SUPPORT EXISTING CONDUITS AND CABLES THAT MUST REMAIN.
FEATURE BED RECEPTACLE
COORDINATE ROUGH-IN REQUIREMENTS WITH FINAL NURSE CALL EQUIPMENT SELECTION.
PLYWOOD BACKING: 4' WIDE x 8' TALL PLYWOOD BACKING. REFER TO SPECIFICATIONS FOR FURTHER REQUIREMENTS.
A.
1
CABLE SPILLWAY: PROVIDE CABLE SPILLWAY "EZ-PATH" CATALOG NO. RCM33 AT FIRE RATED PATHWAYS INDICATED WITH A SUBSCRPT 'S'. PROVIDE (1) SPILLWAY PER SLEEVE. VERIFY QUANTITIES PER PLAN.
CONDUIT SLEEVE WITH BUSHINGS: REFER TO SPECIFICATIONS FOR FURTHER REQUIREMENTS.
(4)-4"C.
354010
GINEER EN
WP
SUBSCRIPT "WP" APPLIED TO ANY SYMBOL INDICATES WEATHERPROOF NEMA TYPE 4 OR EQUIVALENT
PUSH BUTTON CALL CANCEL
O
BELL
1
S
CHIME
354000
COORDINATE ROUGH-IN REQUIREMENTS WITH FINAL NURSE CALL EQUIPMENT SELECTION.
SECURITY SYSTEMS EXAMPLE C5
PULL CORD - AUDIO
COORDINATE ROUGH-IN REQUIREMENTS WITH FINAL NURSE CALL EQUIPMENT SELECTION.
WALL COMMUNICATIONS FIRE RATED PATHWAY: PROVIDE "EZ-PATH" FIRE RATED PATHWAY THROUGH WALL ABOVE CEILING. INSTALL PER MANUFACTURERS RECOMMENDATIONS. SLEEVE DESIGNATIONS PER PLANS. PROVIDE SLEEVES AS FOLLOWS: (A1) - CATALOG NO. EZDP133CWK. (1-3"x3" PATHWAY) (A2) - CATALOG NO. EZDP233GK. (2-3"x3" PATHWAY) (A3) - CATALOG NO. EZDP333GK. (3-3"x3" PATHWAY) (A4) - CATALOG NO. EZDP433GK. (4-3"x3" PATHWAY) (A5) - (1) CATALOG NO. EZDP233GK. AND (1) CATALOG NO. EZDP333GK. (5-3"x3" PATHWAY) (STACKED) (A6) - (2) CATALOG NO. EZDP333GK. (6-3"x3" PATHWAY) (STACKED) (A7) - CATALOG NO. EZDP733GK. (7-3"x3" PATHWAY) (A8) - (2) CATALOG NO. EZDP433GK. (8-3"x3" PATHWAY) (STACKED) (B1) - CATALOG NO. EZD22. (1-2"x2" PATHWAY) (C1) - CATALOG NO. EZDP44. (1-4"x4" PATHWAY) (C2) - (2) CATALOG NO. EZDP44 & (1)-EZP544W. (2-4"x4" PATHWAY) (C3) - (3) CATALOG NO. EZDP44. & (1)-EZP544W. (3-4"x4" PATHWAY) (C4) - (4) CATALOG NO. EZDP44. & (1)-EZP544W. (4-4"x4" PATHWAY) (C5) - (5) CATALOG NO. EZDP44. & (1)-EZP544W. (5-4"x4" PATHWAY) (C5) - (6) CATALOG NO. EZDP44. & (1)-EZP544W. (6-4"x4" PATHWAY)
JUNCTION BOX - FLOOR PHOTOCELL
HOMERUN TO PANEL (NUMBER OF ARROWS INDICATES NUMBER OF CIRCUITS)
SINGLE POLE MANUAL MOTOR STARTER WITH THERMAL O.L. AND PILOT LIGHT
A1
JUNCTION BOX - CEILING
CIRCUIT DOWN
COMBINATION FIRE/SMOKE DAMPER
WALL SLEEVE DESIGNATION
JUNCTION BOX - WALL
BRANCH CIRCUIT CONCEALED IN FLOOR OR BELOW GRADE
FIRE ALARM SYSTEM
NC APULL
RECEPTACLE - DOUBLE DUPLEX - ISOLATED GROUND
J
DISTRIBUTION PANEL, SWITCHBOARD OR MOTOR CONTROL CENTER BRANCH CIRCUIT - EXPOSED
C
353000
BOX DEPTH
CEILING COMMUNICATIONS OUTLET: REFER TO SUPPLEMENTAL SYMBOL LEGENDS FOR FURTHER REQUIREMENTS.
WALL SWITCH OCCUPANCY SENSOR (LOCAL RELAY)
LIGHTING PANEL
S
NC DOME
CEILING OCCUPANCY SENSOR (LOCAL RELAY)
PUSH BUTTON RECEPTACLE - DUPLEX
FSD OR SD
BEDSIDE STATION
(3) DEVICE MODEL NO. ROUGH-IN GANG QTY BOX TYPE
COORDINATE ROUGH-IN REQUIREMENTS WITH FINAL NURSE CALL EQUIPMENT SELECTION. SWITCH - SINGLE POLE
LIGHTING CONTACTOR
TE
DEVICE
COORDINATE ROUGH-IN REQUIREMENTS WITH FINAL NURSE CALL EQUIPMENT SELECTION.
COMBINATION FLOOR OUTLET - POWER & COMMUNICATIONS: REFER TO SUPPLEMENTAL SYMBOL LEGENDS FOR FURTHER REQUIREMENTS.
COVE FIXTURE
UNDERCABINET FIXTURE
NC BSID
FLOOR COMMUNICATIONS OUTLET: REFER TO SUPPLEMENTAL SYMBOL LEGENDS FOR FURTHER REQUIREMENTS.
PENDENT FIXTURE
X
PLAN SYMBOL
COMMUNICATIONS OUTLET: OUTLET TYPE INDICATED PER PLAN. OUTLETS WITH NO CABLING DESIGNATION SHALL BE EMPTY WITH BLANK COVERPLATE. CABLING DESIGNATIONS TYPICAL FOR FLOOR AND CEILING DEVICES. REFER TO INFORMATION DELIVERY DETAILS, OUTLET DETAIL, AND SPECIFICATIONS FOR FURTHER REQUIREMENTS. PROVIDE CABLING AS FOLLOWS: A = 1 ANALOG VOICE CABLE V = 1 DIGITAL VOICE CABLE D = 1 DATA CABLE W = 1 DIGITAL VOICE CABLE WITH PHONE MOUNTING BRACKET FACEPLATE AT 48" AFF.
EMERGENCY BATTERY FIXTURE
X
DESCRIPTION
A
X
SYMBOL
T
X
"X" INDICATES FIXTURE NUMBER IN SCHEDULE
ELECTRICAL SUPPLEMENTAL SYMBOL LEGEND - NURSE CALL SYSTEM ROUGH-IN
REGIST ER
X
TELECOM SUPPLEMENTAL SYMBOLS
(FIRE ALARM GENERAL NOTES SHALL APPLY TO ALL SHEETS) F.
SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL ELECTRICAL DEMOLITION ITEMS. DISCONNECT AND REMOVE ELECTRICAL DEVICES, EQUIPMENT AND ASSOCIATED WIRING AS REQUIRED TO ACCOMMODATE NEW WORK. IF THE CONTRACTOR IS UNCLEAR REGARDING A SPECIFIC ITEM TO REMAIN OR BE REMOVED, THE CONTRACTOR SHALL SEEK CLARIFICATION FROM THE ARCHITECT.
A.
FIRE ALARM CABLING SHALL BE INSTALLED IN CONDUIT WHERE PLENUM RATED CABLING IS NOT UTILIZED.
B.
PROVIDE DUCT SMOKE DETECTION WITHIN SUPPLY AND RETURN DUCTS OF AHU-10. LOCATIONS WITHIN SUPPLY DUCTS SHALL BE DOWNSTREAM OF SERVING UNIT AND BEFORE BRANCH DUCTS. LOCATIONS WITHIN RETURN DUCTS SHALL BE UPSTREAM OF SERVING UNIT AND BRANCH DUCTS. PROVIDE CONNECTIONS SO THAT SMOKE SENSING WILL SHUT DOWN SERVING UNIT. REFER TO MECHANICAL SCHEDULES FOR UNIT CFM OUTPUT.
G. SYSTEMS SERVING ADJACENT AREAS AND ITEMS THAT REMAIN SHALL BE MAINTAINED AT ALL TIMES. MODIFY SYSTEMS AS REQUIRED THROUGHOUT CONSTRUCTION TO MAINTAIN CONTINUITY OF SERVICE. DO NOT INTERRUPT SERVICE WITHOUT OWNER'S PRIOR WRITTEN APPROVAL. LIMIT DURATION OF INTERRUPTION ONLY TO THE TIME NECESSARY FOR DISCONNECTION AND IMMEDIATE RECONNECTION. INTERRUPTION TO SERVICE DEEMED BY OWNER AS ESSENTIAL MAY REQUIRE PREMIUM TIME AND SHALL BE INCLUDED WITH THE BID. EXTREME CARE SHALL BE TAKEN BY THE CONTRACTOR TO IDENTIFY EXISTING SYSTEM COMPONENTS ASSOCIATED WITH THESE SERVICES. APPROPRIATE METHODS OF MARKING THESE SHALL OCCUR TO ELIMINATE THE POSSIBILITY OF ACCIDENTAL INTERRUPTION.
C. PROVIDE MONITORING/CONTROL MODULE FOR EACH FIRE/SMOKE (F/S) DAMPER SYSTEM. REFER TO ELECTRICAL FLOOR PLANS FOR DAMPER LOCATIONS, PROVIDE POWER CONNECTION FOR FIRE/SMOKE DAMPERS AS IDENTIFIED ON FLOOR PLANS. REFER TO DETAIL 5 ON SHEET E501 FOR CONNECTION REQUIREMENTS. PROVIDE ALL CONNECTIONS FOR A COMPLETE SYSTEM.
H. COORDINATE DEMOLITION WITH THE WORK OF OTHER TRADES. PROVIDE TEMPORARY POWER AND LIGHTING AS REQUIRED TO ALLOW THE WORK OF OTHER TRADES TO PROCEED.
E.
I.
PROTECT EXISTING ELECTRICAL EQUIPMENT THAT REMAINS. IF DAMAGED OR DISTURBED IN THE COURSE OF THE WORK, REMOVE DAMAGED PORTIONS AND INSTALL NEW PRODUCTS OF EQUAL CAPACITY, QUALITY, AND FUNCTIONALITY.
J.
PATCH AND REPAIR OPENINGS IN EXISTING WALLS AND FLOORS RESULTANT FROM SPECIFIED ELECTRICAL DEMOLITION. PATCH SHALL MATCH EXISTING CONSTRUCTION, FIRE RATING, AND FINISH. SEE ARCHITECTURAL SPECIFICATIONS FOR MEANS AND METHODS.
K.
CONSTRUCTION SHALL BE PHASED. SEE PROJECT MANUAL AND ARCHITECTURAL PLANS FOR DETAILS AND LIMITS OF DEMOLITION FOR EACH PHASE. SYSTEM SERVICES TO AREAS NOT IN THE CURRENT PHASE OF CONSTRUCTION SHALL BE MAINTAINED AT ALL TIMES.
L.
CHANGES REQUIRED FOR EXISTING VOICE AND DATA CABLING AND OUTLETS IN ROOMS NOT BEING RENOVATED BY THIS PROJECT WILL BE PROVIDED BY THE OWNER.
M. PROVIDE RECIRCUITING, AS REQUIRED, OF EXISTING TO REMAIN ELECTRICAL ITEMS AFFECTED BY DEMOLITION OF PERIMETER FAN COIL UNITS ON FOURTH FLOOR. PROVIDE $30,000 BID ALLOWANCE FOR ASSOCIATED RECIRCUITING OF FOURTH FLOOR PATIENT ROOM BRANCH CIRCUITS.
D. PROVIDE DUCT SMOKE DETECTOR WITHIN 5' OF EACH FIRE/SMOKE DAMPER WITH CONNECTION TO LOCAL FIRE ALARM SYSTEM. ALARM OF DUCT DETECTOR SHALL ACTIVATE DAMPER.
INSTALL GREEN INSULATED GROUND WIRE WITH LIGHTING, RECEPTACLE AND EQUIPMENT BRANCH CIRCUITS.
PROVIDE REMOTE STATUS INDICATOR FOR EACH DUCT SMOKE DETECTOR, LOCATE ADJACENT TO AHU-10. COORDINATE EXACT LOCATIONS WITH OWNER PRIOR TO INSTALLATION.
INSTALL INDIVIDUAL (DEDICATED) NEUTRAL CONDUCTORS FOR EACH 120V OR 277V PHASE CONDUCTOR SERVED FROM A SINGLE POLE CIRCUIT BREAKER 2014
C
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SACRED HEART 4TH & 5TH ELECTRICAL COVER SHEET
Date
SES PROJECT # 14041
11/25/2014 2:15:32 PM
E000 Scale
NONE
98.5
1.3
2.4
3.4
3.6
AVERA FACILITY DEVELOPMENT
A
SHEET NOTES 1
DEMOLISH EXISTING ELECTRICAL CONNECTIONS SERVING AHU10. REMOVE BRANCH CIRCUIT CONDUCTORS FROM EXISTING CONDUIT AND DISCONNECT FROM SOURCE FUSIBLE SWITCH. LABEL FUSIBLE SWITCH COMPARTMENT AS SPARE. EXISTING BRANCH CIRCUIT CONDUIT IS SHARED WITH OTHER MECHANICAL EQUIPMENT NEARBY. EXISTING MECHANICAL EQUIPMENT NOT SERVING AHU-10, SHARING COMMON CONDUIT, SHALL REMAIN OPERATIONAL.
2
DEMOLISH ELECTRICAL CONNECTIONS SERVING PUMP. REMOVE BRANCH CIRCUIT CONDUCTORS FROM EXISTING CONDUIT AND DISCONNECT FROM SOURCE FUSIBLE SWITCH. LABEL FUSIBLE SWITCH COMPARTMENT AS SPARE. EXISTING BRANCH CIRCUIT CONDUIT IS SHARED WITH OTHER MECHANICAL EQUIPMENT NEARBY. EXISTING ELECTRICAL EQUIPMENT NOT SERVING PUMP INDICATED, SHARING COMMON CONDUIT, SHALL REMAIN OPERATIONAL. EXISTING TO REMAIN PUMP INDICATED ON FLOOR PLAN, NEAR PUMP BEING DEMOLISHED, HAS BRANCH CIRCUIT SHARING CONDUIT WITH BRANCH CIRCUIT SHARING DEMOLISHED PUMP.
3
EXISTING THIRD LEVEL MAIN TELECOM ROOM.
4
EXISTING VOICE WALL FIELD.
A1 B B.0 E 4
1.7
D
E
2 P-13
P-15
E
E
2.1
MCC-3
MCC-2 DSWB
B1.1
AHU-10 1 MCC-1
3
EMCC-1 AHU-03 D
C P-16 E
C1
E
AHU-11
2
P-14 D
E
D
P-12 2 D
AHU-09
FESSION PRO AL
O
E
E
AHU-06
RE
G . NO.
U
A
10206 TRACY J. HAUSER
T
S
D1
RF-9C
ED
GINEER EN
RF-9A
REGIST ER
E
T H
K D A
O
11/25/14
E No.
Description
Date
AHU-05 AHU-02 AHU-07 AHU-08
AHU-04
E1 E E
E
E P-18
D
E
E
P-11 2
E
P-17
E
F F1
1b 1
99
1
1c
2b
3c
3A
4 4a
5
5.1
6
B1.2 7
INSTALL GREEN INSULATED GROUND WIRE WITH LIGHTING, RECEPTACLE AND EQUIPMENT BRANCH CIRCUITS.
8
SACRED HEART
INSTALL INDIVIDUAL (DEDICATED) NEUTRAL CONDUCTORS FOR EACH 120V OR 277V PHASE CONDUCTOR SERVED FROM A SINGLE POLE CIRCUIT BREAKER
THIRD LEVEL DEMOLITION - ELECTRICAL 1/8" = 1'-0" 2014
C
4TH & 5TH THIRD LEVEL DEMOLITON ELECTRICAL
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
Date
SES PROJECT # 14041
11/25/2014 2:15:32 PM
E031 Scale
1/8" = 1'-0"
98.5
1.3
2.4
3.4
3.6 AVERA FACILITY DEVELOPMENT
SHEET NOTES
A
1
1
PHASE 4
A1 D
B B.0
1.7
D
D
D
D
D
D
D
D
1
DEMOLISH ELECTRICAL CONNECTIONS SERVING PERIMETER FAN COIL UNIT, DEMOLISH FAN COIL BRANCH CIRCUIT BACK TO SOURCE ELECTRICAL PANEL. DISONNECT BRANCH CIRCUIT FROM SOURCE CIRCUIT BREAKER AND LABEL BREAKER AS SPARE. (TYPICAL FOR PATIENT ROOM FAN COIL UNITS)
2
EXISTING TO REMAIN TELEPHONE CABINET. (TYPICAL FOR 'TTC' CABINETS)
3
EXISTING TO REMAIN CATV AND MUSIC SYSTEMS CABINET. (TYPICAL FOR 'TVC' CABINETS)
4
EXISTING TO REMAIN PUBLIC ADDRESS INTERCOM CABINET. (TYPICAL FOR 'ICC' CABINETS)
5
EXISTING TO REMAIN FIRE ALARM TERMINAL CABINET. (TYPICAL FOR 'FATC' CABINETS)
6
EXISTING TO REMAIN DICTATION SYSTEM CABINET. (TYPICAL FOR 'DCTC' CABINETS)
7
CONSTRUCTION PHASE (TYPICAL)
D
2.1 D
B1.1 1
D
C
E
1
D
E NP4B
TTC4B 2
E
C1
E 3 TVC4 4 ICC4
D
TTC4A
D
E E
E
5 FATC4 DCTC4 6
D
D E NP4C E CP4B
PHASE 2
7
D PHASE 3
NP4A
E E
CP4A
D
O
E
RE
G . NO.
10206 TRACY J. HAUSER U
A
S
D1
FESSION PRO AL
T
D
ED
GINEER EN
D
REGIST ER
D
T H
K D A
O
TTC4C 11/25/14 NP4D
E
E
LS4A
TTC4D 1
E
No.
E
D
Description
Date
D
E1 D D
F
D
D
D
D
D
D
D
D
D
F1 PHASE 1
1b 1
99
1
1c
2b
3c
3A
4 4a
5
5.1
6
B1.2 7
INSTALL GREEN INSULATED GROUND WIRE WITH LIGHTING, RECEPTACLE AND EQUIPMENT BRANCH CIRCUITS.
8
FOURTH LEVEL DEMOLITION - ELECTRICAL 1/8" = 1'-0" 2014
C
SACRED HEART
INSTALL INDIVIDUAL (DEDICATED) NEUTRAL CONDUCTORS FOR EACH 120V OR 277V PHASE CONDUCTOR SERVED FROM A SINGLE POLE CIRCUIT BREAKER
4TH & 5TH FOURTH LEVEL DEMOLITION ELECTRICAL
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
Date
SES PROJECT # 14041
11/25/2014 2:15:33 PM
E041 Scale
1/8" = 1'-0"
98.5
1.3
2.4
3.4
3.6 AVERA FACILITY DEVELOPMENT
SHEET NOTES
A
1
A1 B B.0
D
D
D
D
D
D
D
D
TV
V/2D
TV
V/2D
TV
V/2D
TV
V/2D
TV
V/2D
TV
TV
TV
V V/2D
DEVICES INDICATED ON THIS FLOOR PLAN, WITHIN THIS BOUNDARY ARE DIAGRAMATIC, REFER TO TYPICAL NORTH & SOUTH ROOM LAYOUT - 4TH/5TH LEVEL - DEMOLITION PLAN (DETAIL 1, SHEET E400) FOR SPECIFIC DEMOLITION REQUIREMENTS WITHIN THIS BOUNDARY.
2
EXISTING TO REMAIN TELEPHONE CABINET. (TYPICAL FOR 'TTC' CABINETS)
3
EXISTING TO REMAIN CATV AND MUSIC SYSTEMS CABINET. (TYPICAL FOR 'TVC' CABINETS)
4
EXISTING TO REMAIN PUBLIC ADDRESS INTERCOM CABINET. (TYPICAL FOR 'ICC' CABINETS)
5
EXISTING TO REMAIN FIRE ALARM TERMINAL CABINET. (TYPICAL FOR 'FATC' CABINETS)
6
EXISTING TO REMAIN DICTATION SYSTEM CABINET. (TYPICAL FOR 'DCTC' CABINETS)
7
DEMOLISH ELECTRICAL CONNECTIONS SERVING PERIMETER FAN COIL UNIT, DEMOLISH BRANCH CIRCUIT BACK TO SOURCE ELECTRICAL PANEL. DISONNECT BRANCH CIRCUIT FROM SOURCE CIRCUIT BREAKER AND LABEL BREAKER AS SPARE. (TYPICAL FOR PATIENT ROOM FAN COIL UNITS)
8
OWNER TO PROVIDE DEMOLITION OF EXISTING NURSE CALL MASTER STATION AND CONTROL PANEL, PROVIDE DEMOLITION OF EXISTING SURFACE RACEWAY AT NURSE STATION.
9
DISCONNECT EXISTING ELECTRICAL CONNECTIONS TO EXHAUST FAN SERVING THIS ROOM. EXHAUST FAN LOCATED ON ROOF ABOVE, DEMOLISH DISCONNECT SWITCH RETAIN EXISTING CONDUIT FOR REUSE.
10
LOCATION OF EXISTING DATA AND VOICE RACK CABINET. PROVIDE PER DETAIL 2 ON SHEET E501.
11
PROVIDE SUPPORT DURING CEILING REPLACEMENT FOR EXISTING TO REMAIN CEILING MOUNT DEVICES LOCATED WITHIN COORIDOR. REMOVE AND REINSTALL IF REQUIRED. CLEAN AND REINSTALL EXISTING CEILING DEVICES UPON COMPLETION OF NEW CEILING WORK. REFER TO EXISTING PLAN E12 AND E13, INCLUDED FOR REFERENCE ONLY AS A PART OF ADDENDUM #3, FOR EXISTING CEILING DEVICES AND QUANTITIES.
12
CONSTRUCTION PHASE (TYPICAL).
13
LIGHTING, POWER AND SYSTEMS SHALL BE EXISTING TO REMAIN EXCEPT SPECIFIED DEMOLITION OF FAN COIL UNIT. (THIS ONE ROOM ONLY).
7
12 PHASE 4
D
1
V/3D
V/3D
13
1.7
D
2.1
TV
9
D
1
B1.1 TV
D
TV
D
LIMITS OF ELECTRICAL DEMOLITION E TTC5B 2
C
E NP5B
1 E400 11
C1
E E 3 TVC5
TV
4 ICC5 5 FATC5
E E
MASTER D
E
TV
E
D
8
DCTC5 5
TV
D
TTC5A NC
D
TV
D
2
NP5C
E501
E 11
CP5B
12 PHASE 3
PHASE 2 12
10
T5
11 D
TV
NP5A
E
CP5A
E TV
D
TV
D
O
D1
FESSION PRO AL
S
D
ED
4
E
RE
G . NO.
GINEER EN
REGIST ER
11
10206 TRACY J. HAUSER U
A
NC
8 CP D
T
D
T H
K D A
O
E400
TTC5C
11/25/14 NP5D
E
E
11
1
LS5A
TTC5D
No.
Description
Date
E
E
LIMITS OF ELECTRICAL DEMOLITION
D
TV
TV
1
D
E1 V/2D
F
D
D
D
D
D
D
V/2D
V/2D
D
D
TV
V/2D
TV
V/2D
TV
V/2D
TV
V/2D
TV
TV
V/2D
TV
D
TV
TV
4D
9
TV
D
V/2D
D
F1 12 PHASE 1
1b 1
99
1
1c
2b
3c
3A
4 4a
5
5.1
6
B1.2 7
8
FIFTH LEVEL DEMOLITION - ELECTRICAL 1/8" = 1'-0" 2014
C
INSTALL GREEN INSULATED GROUND WIRE WITH LIGHTING, RECEPTACLE AND EQUIPMENT BRANCH CIRCUITS.
SACRED HEART
INSTALL INDIVIDUAL (DEDICATED) NEUTRAL CONDUCTORS FOR EACH 120V OR 277V PHASE CONDUCTOR SERVED FROM A SINGLE POLE CIRCUIT BREAKER
4TH & 5TH FIFTH LEVEL DEMOLITION ELECTRICAL
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
Date
SES PROJECT # 14041
11/25/2014 2:15:34 PM
E051 Scale
1/8" = 1'-0"
98.5
1.3
2.4
3.4
3.6
AVERA FACILITY DEVELOPMENT
A
SHEET NOTES 1
DEVICES INDICATED ON THIS FLOOR PLAN, WITHIN THIS BOUNDARY ARE DIAGRAMATICAL, REFER TO TYPICAL NORTH & SOUTH ROOM LAYOUT - 5TH LEVEL - LIGHTING PLAN (DETAIL 2, SHEET E400) FOR SPECIFIC LIGHTING REQUIREMENTS WITHIN THIS BOUNDARY.
2
PROVIDE INDIVIDUAL 120V, 20A TOGGLE SWITCH FOR CONTROL OF EXAM PORTION OF LIGHT FIXTURE. PROVIDE ENGRAVED FACEPLATE, PER SPECIFICATIONS, WITH LABEL INDICATING 'EXAM LIGHT'.
3
AMBIENT (ZONE 'd') AND READING (ZONE 'e') PORTION OF LIGHT FIXTURE SHALL BE CONTROLLED BY NURSE CALL PILLOW SPEAKER. PROVIDE RELAY(S) TO INTERCONNECT NURSE CALL SYSTEM WITH AMBIENT AND READING PORTION OF LIGHT FIXTURE.
4
LIGHTING IN THIS ROOM SHALL BE EXISTING TO REMAIN.
5
CONNECT TO EXISTING NORMAL SOURCE 120V, 20A LIGHTING BRANCH CIRCUIT PREVIOUSLY SERVING DEMOLISHED DEVICES, MADE AVAILABLE DURING DEMOLITION OF THIS PROJECT.
6
WHERE MULTIPLE BRANCH CIRCUIT HOME RUNS ARE INDICATED WITH IDENTICAL BRANCH CIRCUIT NUMBERS, COMBINE INDIVIDUAL ROOM BRANCH CIRCUITS INTO SINGLE HOME RUN BACK TO SOURCE PANELBOARD. (TYPICAL)
7
CONNECT TO NEAREST AVAILABLE 120V 20A LIFE SAFETY LIGHTING BRANCH CIRCUIT.
8
CONSTRUCTION PHASE (TYPICAL).
9
DEVICES INDICATED ON THIS FLOOR PLAN, WITHIN THIS BOUNDARY ARE DIAGRAMATICAL, REFER TO TYPICAL WEST & EAST ROOM LAYOUT - 5TH LEVEL - LIGHTING PLAN (DETAIL 5, SHEET E400) FOR SPECIFIC LIGHTING REQUIREMENTS WITHIN THIS BOUNDARY.
ELEVATOR LINK 5900
8 D
D
D
D1
D1
PATIENT RM 504
H1
D1
D1
1.7
2.1
D1
PATIENT RM 506
PATIENT RM 508
H1
H1
PATIENT RM 510
H1
D1
D1
U2
D1
D1
D1
D1
D1
U2
U2 D1 W2
D2
D1
U2
U2
U2
U2
D2
U2
U2 D1
U2
D1
D2
D1
W1
D1
D1
U2
D2
D1
D2
W2
U2
U2
D1
W1
D1
A1
W1
W1
TTC5B
CP5A2-9
D1
CP5A2-10
CP5A2-9
W1 H1
A1
CP5A2
CP5A2-10
CP5A2-10
CP5A2-10 6
CP5A2-10
522
U2
W1
A1
CP5A2-14
D
CP5B2-15
D2
D1
D2
D1
D1
D1
H1
W1
E
Room 524
U2
TTC5A
9
D1
D
D1 ELEC 551
D1
D1
HSKG 552
D1 Room
EQUIPMENT 553
D
D1
W2
D1 Room 526
U2 W1
D
D
CP5A2-14 D2
D1
D
E NP5C
D1
D1
W2
D1
E H1
D1 Room
A1
E NP5B
1
CP5A2-9
2
D1
W2
D1
D
W1
A1
D1
E400
562
D1
D1 W2
D2
CP5A2-14
CP5B2-15
A1
W2
PHASE 3
NEGATIVE AIR 520
D
D1 D
W1
A1
H1
U2
D1
W2
D
A1
D1
D
A1
D1
D
D1 W1
W2
8
W2
E
U2 D1
D1
D2
D1
D
W1
CORRIDOR 5901
W1
D1
A1
D1 D
D1
D1
D
D2
D2
Room 564
D2
D1
D1
D1
W2 W2
D
D
D1
U2
D1
D1
D2
H1
D
A1
9
C1
PATIENT RM 516
CP5A2-10 A1
H1
PATIENT RM 514
H1
D
D1
H1
D1
H1
D1
D
D1
MECH. W1 565
C
PATIENT RM 512
A1
D1
U2
B1.1
D1
D1
W2 W2
D1
D1
D1
D
OFFICE 558
Room 566
D1
D1
PATIENT RM 502
4
D1
D1
D
D
PATIENT RM 500
H1
D
D1
D1
D
B B.0
D1
D
D1 D1
D
A1
PHASE 4
CP5B
A1
A1
CP5B2-27
D
D2
D1
H1
D1
D2
D1
H1
D1
PHASE 2
8
CP5B2-15 A1
A1 CP5B2-18
D
W1 CLEAN UTILITY 558
U2 D
D1 D1
W2
STOREROOM 557
W2
SOILED UTILITY 555
D1
W2
D1
STORAGE 554
D1
D1
D
E
NP5D
CP5B2 D2
D1
H1
c H1 d,e 3
F
D2 U2
bW2 g D1 b U2 D1 b D2 i
g
a
D2
D
W1 i h
D1
A1
D1
W2 W2
U2 U2
U2
D1
D2
U2
D1
U2
1
1
1c
D2
D2
D1
U2
U2
7 A1
A1
D2
D2
D1
D1
D2
D1
No.
D1
H1
W1
K D A
O
Description
Date
U2
A1
W2 W2
U2
U2
W2
U2
D2
U2
D1
U2
D1
D1 U2
L1
D1
D1
H1
PATIENT RM 550
h
D1
D1 PATIENT RM 548
D1
D1 PATIENT RM 546
H1 D1
D1
D1
D1
D1
D1
D
2b
H1
D1 PATIENT RM 540
H1
D1
D1
PATIENT RM 538
D1
D1
H1
PATIENT RM 536
H1
D1
D
3A
4 4a
D
D1
D1
D
D1
D1
D
D1
D1
D
D1
D1
D1
LS
U2
A1
A1 LS
D1
A1
PATIENT RM 534
D1
FAMILY WAITING 558
W1
D1 D1
H1
A1 5 E501
A1
A1
STORAGE 560
D1
D
3c
D1
W2
D1 W2
D1
D1 D
D1
PATIENT RM 542
PATIENT RM 544
8
99
A1
T H
W1
F W
D1
1b
A1
D1 W2
W2 W2
L1
i
A1
D1
U2 D1
U2
D1 a
D1
F1
D2
D1 CP5B2-2
W1
W1
A1
D
D
f
A1
W1
U
D
554
A1
W1
10206 TRACY J. HAUSER
11/25/14 5
D
5
W2 2 D1 ISOLATION f
D1
W1
CP5B2-12
TTC5D E
G . NO.
D1
D1
c
A1
W1
D
E1
CP5B2-2
D1 CP5B2-2
W1
CP5B2-12
CP5B2-12
E D
D1
U2
D
D
Room 556
D1 f
W1
W1
D
D1
CP5B2-12
1
LS5A E
CP5B2-18
A1
CP5B2-12
RE
D
CP5B2-2
CP5B2-2
CP5B2-18
D
A1
CP5B2-27
D
D2
D
D1
D
H1
E400
O
TTC5C D1
5
Room 530
E
FESSION PRO AL
S
W1
D
D1
ED
GINEER EN
D1
NUTRITION 556
A
D1
Room 528
U2
CP5A
T
D1
W1
E
REGIST ER
Room 560
NP5A E
SOILED UTILITY 559
D
D2
D1
D
H1
D1
F W
A1
F W
RESTROOM 559
D
PHASE 1
5
5.1
6
B1.2 7
INSTALL GREEN INSULATED GROUND WIRE WITH LIGHTING, RECEPTACLE AND EQUIPMENT BRANCH CIRCUITS.
8
FIFTH LEVEL - LIGHTING
SACRED HEART
INSTALL INDIVIDUAL (DEDICATED) NEUTRAL CONDUCTORS FOR EACH 120V OR 277V PHASE CONDUCTOR SERVED FROM A SINGLE POLE CIRCUIT BREAKER
1/8" = 1'-0"
2014
C
4TH & 5TH FIFTH LEVEL LIGHTING PLAN
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
Date
SES PROJECT # 14041
11/25/2014 2:15:39 PM
E151 Scale
1/8" = 1'-0"
98.5
1.3
2.4
1937
HSKG 1933
3.4 3.6
UTILITY 1932
AVERA FACILITY DEVELOPMENT ELEC / DISCONNECT 1904
TELECOM 1903
ELEVATOR 2 2331
SHEET NOTES
'MSB11' PHYS/ COUR ENTRANCE 1942
CONFERENCE ROOM 1907
MAIL ROOM 1941
E E E E
ELEVATOR 1 2330
FIRE SPRINKLER ROOM 1905
E
UP
CORRIDOR 1902
OFFICE 1943
EXISTING 800KW DIESEL GENERATOR VOLUNTEER OFFICE 1909
GENERATOR ROOM 1970
OFFICE 1944
'HGEN'
ESSENTIAL BRANCHES ROOM
E 'EDP-A'
1971
5 ATS-3 3 'GDP' E E E
A
E
4 ATS-1 E
ELEVATOR 3 2332
CATH LAB E 6 ATS-2 E 1 'EDP' E
CRITICAL DISTRUBITION PANEL (CDP).
3
NON-ENERGIZED EQUIPMENT.
4
LIFE SAFETY TRANSFER SWITCH.
5
EQUIPMENT TRANSFER SWITCH.
6
CRITICAL TRANSFER SWITCH.
7
RECOMMENDED LOCATION FOR ROUTING OF NEW EP3A 2" CONDUIT AND TWO ATS-CDP2 2" CONDUITS UP TO 3RD LEVEL. CORE DRILL CONCRETE FLOOR IN PAN PORTION OF STRUCTURE, AS CLOSE TO COLUMN AS POSSIBLE. REFER TO ARCHITECTURAL DRAWINGS FOR CONDUIT CHASE CONSTRUCTION REQUIREMENTS. COORDINATE EXACT CONDUIT ROUTING WITH OWNER PRIOR TO INSTALLATION. PERFORM WORK WITH MINIMAL IMPACT TO OWNER. SEAL ALL FLOOR PENETRATIONS AND PENETRATIONS THROUGH RATED WALLS.
8
ROUTE TWO (2) 2" CONDUITS FOR ATS-CDP2 THROUGH EXISTING TUNNEL TO MECHANICAL ROOM 1031. FROM MECHANICAL ROOM ROUTE CONDUITS OVER TO COLUMN INDICATED BY SHEET NOTE 7 FOR ROUTING UP TO THIRD LEVEL.
E
E
REGISTRATION WAITING 1911
CONFERENCE 1945 CORRIDOR 1940
GIFT SHOP 1005
'EP1A'
8
LOBBY 1900
COPY CENTER 1947
'CDP' 2
CORRIDOR 1946
EXISTING TUNNEL
REGISTRATION 1912
REGISTRATION 1913
STORAGE 1949
MECHANICAL 1031
A1 B B.0
OUTLINE OF PATIENT TOWER ABOVE. ROOM 1006
WORKROOM 1914
HSKG 1950 CONFERENCE 1704
ROOM 1007
MCC-4
CORRIDOR 1017
UNASSIGNED 1008
'US-1'
B1.1 SURGEON LOUNGE 1807
MEDITATION ROOM 1009
1030A PHYSICIAN LOUNGE 1703
EXIT PASSAGE 1034
WOMEN'S LOCKER ROOM 1803
EQUIPMENT 1555
WOMEN'S TOILET 1028
'MSWB'
OFFICE 1702
RECEPTION 1600
7
IMAGING WAITING 1961
STAIR 1
TOILET 1538A
PRE/POST 1538
TOILET 1541A PRE/POST 1549
PRE/POST 1545
PRE-OP 1611
MED. AFFAIRS OFFICE 1614
TOILET 1545A
PRE/POST 1536
PRE-OP 1612
HALLWAY 1603
D1 E
PRE/POST 1551
TOILET 1535A
PRE/POST 1547
PRE/POST 1543
TOILET 1551A
NURSE STATION 1520
PACU 1527
PACU 1525
IMAGING RECEPTION 1962
RE
G . NO.
10206 TRACY J. HAUSER U
T H
K D A
O
11/25/14
No.
Description
Date
TOILET 1620A PRE-OP 1618
SOILED HOLD 1020
PRE-OP 1620 HSKPG 1621
TOILET 1619
NURSE STATION 1519
PACU 1523
IMAGING WAITING 1963
CLEAN SUPPLY 1628
TOILET 1617 PRE-OP / INPT HOLD 1616
PRE/POST 1535
OFFICE 1011
HALLWAY 1602
HSKPG 1537 TOILET 1536A
O
OFFICE 1556
CONSULT (FUTURE PRE-OP) 1608
FESSION PRO AL
S
D
PRE/POST 1541
REGIST ER
TOILET 1549A
ED
GINEER EN
EXIT PASSAGE 1033
A
MEN'S LOCKER ROOM 1801
MEN'S TOILET 1029
HOSP. MAIN ELEC ROOM
T
TOILET 1802
TOILET 1804
C C1
2
VOLUNTEER WORKROOM 1910
E
OLD GENERATOR ROOM
EQUIPMENT DISTRIBUTION PANEL (EDP) 600A 3PH 3W.
ENTRY 1000
RECEPTION 1901
CONFERENCE 1908
1
HALLWAY 1622
E1
SOILED HOLD 1532 STAFF TOILET 1531
CONTROL DESK 1625 PACU 1529
F F1
PACU 1528
PACU 1526
PACU ISOLATION 1522
PACU 1524
ANES. OFFICE 1627
PACU ISOLATION 1521
SERVICE ACCESS 1604 HSKP 1512A
DECONTAM 1508
HALLWAY 1022
SUB STERILE 1507
Stair 3
O.R. 2 1501
98
1
DIRECTOR'S OFFICE 1626
BREAK ROOM 1021
STAFF TOILET 1019
1b
99
1
1c
2b
3c
3A
4 4a
5
5.1
6
B1.2 7
8
SACRED HEART
INSTALL INDIVIDUAL (DEDICATED) NEUTRAL CONDUCTORS FOR EACH 120V OR 277V PHASE CONDUCTOR SERVED FROM A SINGLE POLE CIRCUIT BREAKER
FIRST LEVEL - POWER 3/32" = 1'-0"
INSTALL GREEN INSULATED GROUND WIRE WITH LIGHTING, RECEPTACLE AND EQUIPMENT BRANCH CIRCUITS.
2014
C
4TH & 5TH FIRST LEVEL POWER PLAN
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
Date
SES PROJECT # 14041
11/25/2014 2:15:40 PM
E211 Scale
3/32" = 1'-0"
98.5
1.3
2.4
3.4
3.6
GENERATOR ROOM
EXISTING EMERGENCY SWITCHBOARD 'HGEN'
A
AVERA FACILITY DEVELOPMENT
LOCATED ON FIRST FLOOR APPROXIMATELY 20FT NORTH & 56FT WEST OF THIS LOCATION
SHEET NOTES 1
EQUIPMENT BRANCH DIST. PANEL 'EDP-A'
OLD GENERATOR ROOM
RECOMMENDED LOCATION FOR ROUTING OF NEW EP3A 2" CONDUIT AND TWO ATS-CDP2 2" CONDUITS FROM 1ST LEVEL BELOW. CORE DRILL CONCRETE FLOOR IN PAN PORTION OF STRUCTURE, AS CLOSE TO COLUMN AS POSSIBLE. ROUTE CONDUITS ON THIS FLOOR OVERHEAD TO ELECTRICAL EQUIPMENT BEING SERVED. COORDINATE EXACT CONDUIT ROUTING WITH OWNER PRIOR TO INSTALLATION. PERFORM WORK WITH MINIMAL IMPACT TO OWNER. SEAL ALL FLOOR PENETRATIONS AND PENETRATIONS THROUGH RATED WALLS.
A1 B B.0
E P-15 E
1.7
E
E
2.1
MCC-2
MCC-3
DSWB
B1.1
HOSP. MAIN ELEC ROOM
MCC-1
LOCATED ON FIRST FLOOR APPROXIMATELY 23FT WEST OF THIS LOCATION
C
EMCC-1 AHU-03
EXISTING NORMAL SWITCHBOARD 'MSWB'
1
P-16 E
C1
AHU-11
E
E
D AHU-09 EP3A CDP-2 XFMR-CDP2
S
D1
RF-9C
O
E
RE
G . NO.
10206 TRACY J. HAUSER U
A
RF-9A
FESSION PRO AL
T
E
ED
GINEER EN
REGIST ER
ATS-CDP2
T H
K D A
O
E
AHU-06
11/25/14
E
AHU-10
No.
Description
Date
AHU-05 AHU-02 AHU-07 AHU-08
AHU-04
E1 E E E
E P-18 E
E
E P-17
E
F F1
98 1
1b
99
1
1c
2b
3c
3A
4 4a
5
5.1
6
B1.2 7
INSTALL GREEN INSULATED GROUND WIRE WITH LIGHTING, RECEPTACLE AND EQUIPMENT BRANCH CIRCUITS.
8
SACRED HEART
INSTALL INDIVIDUAL (DEDICATED) NEUTRAL CONDUCTORS FOR EACH 120V OR 277V PHASE CONDUCTOR SERVED FROM A SINGLE POLE CIRCUIT BREAKER
THIRD LEVEL - POWER 1/8" = 1'-0" 2014
C
4TH & 5TH THIRD LEVEL POWER PLAN
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
Date
SES PROJECT # 14041
11/25/2014 2:15:41 PM
E231 Scale
1/8" = 1'-0"
98.5
1.3
2.4
3.4
3.6 AVERA FACILITY DEVELOPMENT
A
SHEET NOTES 1
CONNECT FIRE/SMOKE DAMPERS TO A COMMON 120V 20A LIFE SAFETY BRANCH CIRCUIT FROM PANEL 'LS4A'. PROVIDE 20/1 CIRCUIT BREAKER WITHIN PANEL, MATCH EXISTING MANUFACTURER AND RATINGS OF EXISTING. PROVIDE #10 CONDUCTORS. PROVIDE ONE DUCT TYPE SMOKE DETECTOR WITHIN 5' OF EACH SIDE OF FIRE/SMOKE DAMPER (TOTAL OF TWO (2) DETECTORS PER FIRE/SMOKE DAMPER). (TYPICAL)
A1 B B.0
1
FS.D.
FS.D.
FS.D.
1
1
1.7
2.1
B1.1
E
C
E
TTC4B
NP4B
E
C1
E TVC4 ICC4 FATC4
TTC4A
E E
E DCTC4
E NP4C E CP4B
D NP4A
E E
FESSION PRO AL
O
E TTC4C
NP4D
E
E
E
E
G . NO.
U
A
10206 TRACY J. HAUSER T H
K D A
O
11/25/14
TTC4D
LS4A
RE
T
S
D1
ED
GINEER EN
REGIST ER
CP4A
No.
Description
Date
E1
FS.D.
1
1 FS.D.
FS.D.
F
1
F1
1b 1
99
1
1c
2b
3c
3A
4 4a
5
5.1
6
B1.2 7
INSTALL GREEN INSULATED GROUND WIRE WITH LIGHTING, RECEPTACLE AND EQUIPMENT BRANCH CIRCUITS.
8
SACRED HEART
INSTALL INDIVIDUAL (DEDICATED) NEUTRAL CONDUCTORS FOR EACH 120V OR 277V PHASE CONDUCTOR SERVED FROM A SINGLE POLE CIRCUIT BREAKER
FOURTH LEVEL - POWER 1/8" = 1'-0" 2014
C
4TH & 5TH FOURTH LEVEL POWER AND SYSTEMS PLAN
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
Date
SES PROJECT # 14041
11/25/2014 2:15:42 PM
E241 Scale
1/8" = 1'-0"
98.5
1.3
2.4
3.4
3.6
AVERA FACILITY DEVELOPMENT
A
SHEET NOTES 1
DEVICES INDICATED ON THIS FLOOR PLAN, WITHIN THIS BOUNDARY ARE DIAGRAMATICAL, REFER TO TYPICAL NORTH & SOUTH ROOM LAYOUT - 5TH LEVEL - POWER PLAN (DETAIL 3, SHEET E400) FOR SPECIFIC POWER & SYSTEMS REQUIREMENTS WITHIN THIS BOUNDARY.
2
REFER TO ENLARGED FLOOR PLAN FOR BRANCH CIRCUITING REQUIREMENTS.
3
CONNECT FIRE/SMOKE DAMPERS TO A COMMON 120V 20A LIFE SAFETY BRANCH CIRCUIT FROM PANEL 'LS5A'. PROVIDE 20/1 CIRCUIT BREAKER WITH PANEL, MATCH EXISTING MANUFACTURER AND RATINGS OF EXISTING. PROVIDE #10 CONDUCTORS. (TYPICAL)
4
CONNECT TO EXISTING NORMAL SOURCE 120V, 20A RECEPTACLE BRANCH CIRCUIT PREVIOUSLY SERVING DEMOLISHED DEVICES, MADE AVAILABLE DURING DEMOLITION OF THIS PROJECT.
5
REFER TO TYPICAL NORTH & SOUTH ROOM LAYOUT - 5TH LEVEL POWER PLAN (DETAIL 3, SHEET E400) FOR SPECIFIC HEADWALL DEVICE LOCATIONS AND BRANCH CIRCUITING REQUIREMENTS.
6
NEW EXHAUST FAN EF-1 (1/2HP, 120V) LOCATED ON ROOF ABOVE AT APPROXIMATELY THIS LOCATION. SEE SHEET M161.
7
NEW EXHAUST FAN EF-2 (3/4HP, 120V) LOCATED ON ROOF ABOVE AT APPROXIMATELY THIS LOCATION. SEE SHEET M161
8
POWER AND SYSTEMS IN THIS ROOM SHALL BE EXISTING TO REMAIN EXCEPT SPECIFIED DEMOLITION OF FAN COIL UNIT.
9
CONSTRUCTION PHASE (TYPICAL).
10
DEVICES INDICATED ON THIS FLOOR PLAN, WITHIN THIS BOUNDARY ARE DIAGRAMATICAL, REFER TO TYPICAL WEST & EAST ROOM LAYOUT - 5TH LEVEL - POWER PLAN (DETAIL 6, SHEET E400) FOR SPECIFIC POWER & SYSTEMS REQUIREMENTS WITHIN THIS BOUNDARY.
ELEVATOR LINK 5900
9
PHASE 4
A1
10 FS.D.
B B.0
NC
NC
NC
EF-1 6
FS.D.
NC
2 CP5A2-12
E, 65" E, 65" E TV
NC NC
NC
NC CP5A2-19 2
TV
Room 522
NC
NC
NEGATIVE AIR 520
3
NC
NC NC
CP5A2-8 2
NC
NC
NC
NC
TV
TV
NC NC
NC
NC
NC NC NC
NC
NC
NC
TV
TV
NC NC
NC
NC
TV
NC
NC
NC
TV
TV
NC
E TTC5B
NC
NC
NC
NC
NC
NC
E
NC
CP5A2
NC
NP5B
1
3
NC
NC
NC
NC
NC
NC
NC NC
E TVC5 NC
E ELEC
ICC5
551
E
FATC5
NC
MASTER E
DCTC5 NC
EQUIPMENT 553
TV
CP5A2-20 NC CP5A2-21 2
1 NC
NC TV
2
E NP5C
E501
(3) 4"C.
Room 526
E CP5B
NC NC
NC
NC
NC
NC
NC
NC T51 T52 8"x 2" T53 T54
NC
NC
CP CLEAN UTILITY 558
2 CP5B2-23
TV
NC
NC
NC
NC
NC
NC
E
NC
2 CP5A2-22
NC
NC
STORAGE 554
E400
O
TTC5C
FESSION PRO AL RE
G . NO.
GINEER EN
6
Room 530
E
ED
S
D1
SOILED UTILITY 555
TV
NC
CP5B2-22 2
TV
NUTRITION 556
Room 528
CP5A
NC STOREROOM 557
9
NC
NP5A E
SOILED UTILITY 559
8"x 2"
Room 560
NC
PHASE 2
10206 TRACY J. HAUSER U
A
Room 562
NC
T
CP5B2-24 2
HSKG 552
Room 524
2
REGIST ER
TV
TTC5A NC
2 CP5B2-25 NC
D
CP5A2-7 2
CP5A2-6 2
NC
NC
E
TV
PHASE 3
PATIENT RM 516
E400
Room 564
9
CP5A2-5 2
PATIENT RM 514
NC
NC
NC
C1
CP5A2-3 2
PATIENT RM 512
8"x 2"
C
NC
MECH. NC565 NC
PATIENT RM 510
CP5A2-4 2
NC
CORRIDOR 5901
PATIENT RM 508
NC
Room 566
10
PATIENT RM 506
NC
TV
CP5A2-2 2
NC
NC
CP5B2-26 2
CP5A2-1 2 NC
NC
NC
2.1
NC
1.7
PATIENT RM 504
NC
OFFICE 5902
B1.1
PATIENT RM 502
NC
8
PATIENT RM 500
NC
NC
FS.D.
3
TV
3
NC
NC
T H
K D A
O
NC
E
NC
NC
NC
NC
NC
NC
CP5B2
NP5D NC
NC
1
LS5A E
NC
E
TTC5D
NC
NC
NC
NC
11/25/14 NC
E
NC
NC
NC
NC
NC
NC
NC
4
NC
NC
T
TV
PATIENT RM 536
TV
NC
NC
PATIENT RM 538
FAMILY WAITING 558
NC
NC
NC NC TV
TV
PATIENT RM 540
TV
NC
NC
CP5B2-3
2
NC
NC
NC
NC
NC
NC NC
NC NC
PATIENT RM 542
Date
CP5B2-4
NC
NC TV
PATIENT RM 544
NC
NC NC TV
TV
PATIENT RM 546
NC
NC NC
NC
NC
NC
NC
NC
NC NC
NC
2 CP5B2-7
NC
NC
NC TV
PATIENT RM 548
2 CP5B2-6
Description
PATIENT RM 534
G 44" STORAGE 560
RESTROOM 559
T 3
APULL
3
T
FS.D.
F
PULL
PATIENT RM 550
CP5B2-8
2
2 CP5B2-5
2 CP5A2-23
FS.D.
NC BED
NC
TV
V/D BSID2D NC
G
G 44" 3
NC
2D
CP5B2-13 2
NC
E, 65" 7 EF-2
2 CP5B2-9
NC
ISOLATION 554
2 CP5B2-10 CP5B2-11
FS.D.
4
TV 5
2
2
NC E, 65"
NC
NC
NC
NC
E1
NC
NC
2 CP5B2-21
TV
NC
NC
Room 556
4
No.
NC
F1 9
1b 1
99
1
1c
2b
3c
3A
4 4a
PHASE 1
5
5.1
6
B1.2 7
INSTALL GREEN INSULATED GROUND WIRE WITH LIGHTING, RECEPTACLE AND EQUIPMENT BRANCH CIRCUITS.
8
SACRED HEART
INSTALL INDIVIDUAL (DEDICATED) NEUTRAL CONDUCTORS FOR EACH 120V OR 277V PHASE CONDUCTOR SERVED FROM A SINGLE POLE CIRCUIT BREAKER
FIFTH LEVEL - POWER 1/8" = 1'-0"
2014
C
4TH & 5TH FIFTH LEVEL POWER AND SYSTEMS PLAN
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
Date
SES PROJECT # 14041
11/25/2014 2:15:49 PM
E251 Scale
1/8" = 1'-0"
SHEET NOTES
GENERAL NOTES
1
A.
PROVIDE DEVICE'S MOUNTING HEIGHTS PER ARCHITECTURAL INTERIOR ELEVATIONS.
B.
PROVIDE FOR PATIENT ROOMS RENOVATED BY THIS PROJECT PER TYPICAL PATIENT ROOMS INDICATED ON THIS SHEET.
2
EXISTING BACK BOX AND CONDUIT IN FOOTWALL SHALL REMAIN, DEMOLISH EXISTING DEVICE AND CRITICAL BRANCH CIRCUIT BACK TO SOURCE PANELBOARD. PROVIDE NEW DEVICE AND BRANCH CIRCUIT AS INDICATED ON NEW WORK FLOOR PLAN.
3
DEMOLISH EXISTING COMMUNICATIONS OUTLET AND ASSOCIATED CONDUIT IN WALL. EXISTING TWISTED PAIR VOICE CABLING, DISCONNECT AT BOTH ENDS AND DEMOLISH BACK TO SOURCE CORRIDOR TELEPHONE CABINET. RETAIN EXISTING DATA CABLING, FIELD VERIFY QUANTITIES INDICATED ON FLOOR PLAN. COIL CABLING UP IN CEILING ABOVE AND PROTECT DURING CONSTRUCTION FOR REUSE. REUSE EXISTING CABLING TO SERVE DEVICE(S) INDICATED ON NEW WORK FLOOR PLAN. (TYPICAL FOR COMMUNICATIONS OUTLETS INDICATED AS DEMO)
4
EXISTING BRANCH CIRCUITS SERVING DEMOLISHED ELECTRICAL DEVICES SHALL BE REUSED AS INDICATED PER ENLARGED FLOOR PLANS. WHERE EXISTING BRANCH CIRCUITS SHARE COMMON NEUTRAL CONDUCTOR, PROVIDE ADDITIONAL NEUTRAL CONDUCTOR(S) WITHIN EXISTING CONDUIT AS REQUIRED FOR ALL 120V BRANCH CIRCUITS TO HAVE DEDICATED NEUTRAL CONDUCTORS.
5
DEMOLISH WALL MOUNT NURSE CALL DOME LIGHT AT THIS LOCATION.
6
UTILIZE EXISTING DATA CABLING PREVIOUSLY SERVING DEMOLISHED DATA OUTLET.
7
EXISTING TELEVISION POWER RECEPTACLE BRANCH CIRCUITS AND DEMOLISHED FAN COIL UNIT BRANCH CIRCUIT SHARE COMMON NEUTRAL. REFER TO FLOOR PLANS FOR BRANCH CIRCUITS SERVING EXISTING TO REMAIN RECEPTACLES. PROVIDE ONE (1) ADDITIONAL NEUTRAL CONDUCTOR FOR DEDICATED NEUTRALS FOR EXISTING TO REMAIN BRANCH CIRCUITS.
8
DISCONNECT EXISTING CATV CABLING FROM DEMOLISHED OUTLET AND COIL ABOVE CEILING FOR REUSE. PROTECT CABLING DURING CONSTRUCTION, EXTEND CABLING TO NEW LOCATION AS INDICATED ON NEW WORK FLOOR PLAN. DEMOLISH UNUSED CATV CABLING BACK TO SOURCE.
9
PROVIDE INDIVIDUAL120V, 20A TOGGLE SWITCH FOR CONTROL OF EXAM PORTION OF LIGHT FIXTURE. PROVIDE ENGRAVED FACEPLATE, PER SPECIFICATIONS, WITH LABEL INDICATING 'EXAM LIGHT'.
10
AMBIENT (ZONE 'd') AND READING (ZONE 'e') PORTION OF LIGHT FIXTURE SHALL BE CONTROLLED BY NURSE CALL PILLOW SPEAKER. PROVIDE RELAY(S) TO INTERCONNECT NURSE CALL SYSTEM WITH AMBIENT AND READING PORTION OF LIGHT FIXTURE.
11
UTILIZE EXISTING CATV CABLING TO SERVE NEW OUTLET ON NEW WALL. (TYPICAL)
12
CONNECT TO EXISTING NORMAL SOURCE 120V, 20A RECEPTACLE BRANCH CIRCUIT PREVIOUSLY SERVING DEMOLISHED DEVICES, MADE AVAILABLE DURING DEMOLITION OF THIS PROJECT.
13
REFER TO 1/8" SCALE FLOOR PLANS FOR CRITICAL BRANCH CIRCUIT SERVING EACH PATIENT ROOM.
14
REFER TO FLOOR PLANS FOR CRITICAL LIGHTING BRANCH CIRCUIT SERVING EACH PATIENT ROOM. WHERE BRANCH CIRCUIT IS INDICATED IN MULTIPLE PATIENT ROOMS, ASSOCIATED LIGHTING SHALL SHARE COMMON BRANCH CIRCUIT INDICATED.
15
CONNECT TO EXISTING NORMAL SOURCE 120V, 20A LIGHTING BRANCH CIRCUIT PREVIOUSLY SERVING DEMOLISHED DEVICES, MADE AVAILABLE DURING DEMOLITION OF THIS PROJECT.
1
A1
A1
A1 D
f
c
2D
B B.0
f
H1
10
D
6
PB
9 54"
2
D1 b
D1 b
c b
U2
B1.1
NC
W2
B1.1
PULL
g
U2
a D1
B1.1
SHOWER D2
CP5A2-9 14
12
A1
NC
APULL D1
G 44"
a g a
DOME NC
W1 5
15
TYPICAL NORTH & SOUTH PATIENT ROOM LAYOUT 5TH LEVEL - POWER AND SYSTEMS
2
1/4" = 1'-0"
E, 65"
TYPICAL NORTH & SOUTH PATIENT ROOM LAYOUT 5TH LEVEL - DEMO (SIMILAR FOR EAST & WEST PATIENT ROOMS)
1
1/4" = 1'-0"
1/4" = 1'-0"
b W2 g
TV E, 65"
c
D
15 D1 a
DOME
D1
D
g U2
D1
W1 CP5B2-27 14
BSID NC
TYPICAL EAST & WEST PATIENT ROOM LAYOUT 5TH LEVEL - POWER AND SYSTEMS 1/4" = 1'-0"
A1
D2
5
b
U
T H
K D A
O
Description
Date
D1 f
D1
TYPICAL EAST & WEST PATIENT ROOM LAYOUT 5TH LEVEL - LIGHTING 1/4" = 1'-0"
10206 TRACY J. HAUSER
H1
E
8
G . NO.
11/25/14
No.
V/D
RE
4
12
SHOWER
6
SHOWER
E
PULL NC
f
c
6 APULL NC
E, 65"
O
a
G, 44"
2D BED NC
7 E, 65"
D1
FESSION PRO AL
S
12
CP5A2-24 13
b
f
D1
TV
ED
D
NC
TYPICAL NORTH & SOUTH PATIENT ROOM LAYOUT 5TH LEVEL - LIGHTING
GINEER EN
NC PB
D1
3
42"
CP5B2-1 13
3
4
E, 65" 7
D
NC
BED
2D 54"
D V/2D
E, 65"
d,e
A
(EXAM) NC
BSID NC
TV
E, 65"
D1
f
T
B B.0
V/D
E, 65"
D1
AVERA FACILITY DEVELOPMENT
REGIST ER
12
TV
B B.0
UNLESS OTHERWISE NOTED, PROVIDE DEMOLITION OF LIGHTING, POWER, & SYSTEMS DEVICES AS REQUIRED FOR DEMOLITION, LOCATED WITHIN BOUNDARY. RETAIN LIGHTING AND POWER BRANCH CIRCUITS. DEMOLISH BACK TO SOURCE CABINET INTERCOM AND DICTATION SYSTEM DEVICES.
3
10 de
E
8 4
V
D
8
FIFTH LEVEL DEMOLITION - ELECTRICAL - Callout 1 1/4" = 1'-0"
INSTALL GREEN INSULATED GROUND WIRE WITH LIGHTING, RECEPTACLE AND EQUIPMENT BRANCH CIRCUITS. INSTALL INDIVIDUAL (DEDICATED) NEUTRAL CONDUCTORS FOR EACH 120V OR 277V PHASE CONDUCTOR SERVED FROM A SINGLE POLE CIRCUIT BREAKER 2014
C
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
SACRED HEART 4TH & 5TH ENLARGED FLOOR PLANS & TYPICAL ROOM LAYOUTS Date
SES PROJECT # 14041
11/25/2014 2:15:50 PM
E400 Scale
NONE
EQUIPMENT CONNECTION SCHEDULE MARK
DESCRIPTION
AHU-10-RF-1 AHU-10-RF-2 AHU-10-SF-1 AHU-10-SF-2 EF-1 EF-2
AIR HANDLING UNIT AIR HANDLING UNIT AIR HANDLING UNIT AIR HANDLING UNIT EXHAUST FAN EXHAUST FAN
HP/KW/ FLA VOLTS PHASE MCA 10 HP 10 HP 20 HP 20 HP 1/2 HP 3/4 HP
480 V 480 V 480 V 480 V 120 V 120 V
3 3 3 3 1 1
MOCP
LOAD.
STARTER/ CONTROLLER
35 35 70 70 20 35
11639 VA 11639 VA 22447 VA 22447 VA 1176 VA 1656 VA
VFD VFD VFD VFD DIV 15 DIV 15
17.5 17.5 33.8 33.8 17.3 17.3
LIGHTING FIXTURE SCHEDULE
CONTROL TYPE DISCONNECT DDC/FA STOP DDC/FA STOP DDC/FA STOP DDC/FA STOP CONT. CONT.
FEEDER
DIV 15 DIV 15 DIV 15 DIV 15 DIV 15 DIV 15
PANEL. GEN
(1M) (1/2 - 10 HP 480V) 3-#12, #12 GND - 3/4"C. (1M) (1/2 - 10 HP 480V) 3-#12, #12 GND - 3/4"C. (3M) (20 HP 480V) 3-#8, #8 GND - 1"C. (3M) (20 HP 480V) 3-#8, #8 GND - 1"C. (1M1) (1/6 - 1 HP 120V) 2-#12, #12 GND - 3/4"C. (1M1) (1/6 - 1 HP 120V) 2-#12, #12 GND - 3/4"C.
EP3A MCC-1 EP3A MCC-1 CP5A2 CP5B2
Yes No Yes No Yes No
FIXTURE NO. SUBS MANUFACTURER
KEY NOTES
A1 D1 D2 H1 L1 U2 W1 W2
NOTE 1 NOTE 1
KEY NOTES: (EQUIPMENT CONNECTION SCHEDULE)
P P P P P P P P
LITHONIA WILA GOTHAM KENALL LITHONIA HEALTHCARE TECH LIGHTING HEALTHCARE
CATALOG NO. (NOTE A)
LAMP
2VT8-2-17-ADP-MVOLT-GEB10IS 621-549-DA60-80-120-DFS-BDIM EVO-35-10-6-DFR-MVOLT MPC24-G-1/1/3-50B-120-L-LVC SP8-G-2-32-A12125-MVOLT-GEB10RS HUC523-120-LED35-AM 700BCLYNN-W-S-LED HNL610-MVOLT-LEDAMB-AM
(2) 17W T8 LED LED (5) F50TT (BIAX) 2 -32W T8 LED LED LED
INPUT VOLTAGE WATTS 120 V 120 V 120 V 120 V 120 V 120 V 120 V 120 V
36 W 15 W 22 W 278 W 66 W 14 W 20 W 3W
MOUNTING
DESCRIPTION
NOTES
CEILING RECESSED CEILING RECESSED CEILING RECESSED CEILING RECESSED CEILING RECESSED SURFACE WALL SURFACE WALL RECESSED
2x2 VOLUMETRIC - 2 LAMP 4" LOW PROFILE DOWNLIGHT 6" SHOWER LIGHT 2x4 MULTIFUNCTION EXAM LIGHT 2x4 LENSED TROFFER 2' UNDERCABINET TASK LIGHT VANITY NIGHT LIGHT
NOTE 1 NOTE 1
AVERA FACILITY DEVELOPMENT
1. PROVIDE NEW FUSED SWITCH WITHIN EXISTING MOTOR CONTROL CENTER, SWITCH SHALL MATCH MANUFACTURER AND RATINGS OF EXISTING. KEY NOTES: 1. WALL MOUNTING - COORDINATE EXACT MOUNTING LOCATION WITH ARCHITECT AND ARCHITECTURAL DETAILS.
GENERAL NOTES: (EQUIPMENT CONNECTION SCHEDULE)
2. PENDANT/SUSPENSION MOUNTING - COORDINATE EXACT LOCATION, MOUNTING ELEVATION, AND REQUIRED PENDANT/SUSPENSION LENGTH WITH ARCHITECT AND ARCHITECTURAL DETAILS.
A. EQUIPMENT LISTED MAY NOT BE UNIQUE, VERIFY QUANTITY ON PLANS. REFER TO DEFINITIONS BELOW FOR CLARIFICATION OF CONNECTION REQUIREMENTS. B. ITEMS NOTED AS "NA" ARE NOT APPLICABLE TO THE CONNECTION. C. "STARTER/CONTROLLER" - PROVIDE STARTER AND ASSOCIATED CONNECTIONS TO EQUIPMENT AND BRANCH CIRCUIT: ·"MAG" = COMBINATION MAGNETIC MOTOR STARTER WITH DISCONNECT (COORDINATE COIL VOLTAGE WITH CONTROL SOURCE). ·"MAN" = COMBINATION MANUAL MOTOR STARTER WITH DISCONNECT. ·"DIV 15" = STARTER OR CONTROLLER IS FURNISHED BY MECHANICAL CONTRACTOR, TEMPERATURE CONTROLS CONTRACTOR, OR PROVIDED WITH ·EQUIPMENT. ELECTRICAL CONTRACTOR SHALL PROVIDE MOUNTING AND ADDITIONAL CONNECTIONS REQUIRED FOR THESE LOOSE STARTERS AND CONTROLLERS. ·"VFD-___" = VARIABLE FREQUENCY DRIVE CONTROLLER FURNISHED BY MECHANICAL CONTRACTOR. ELECTRICAL CONTRACTOR SHALL PROVIDE MOUNTING AND ADDITIONAL CONNECTIONS REQUIRED FOR LOOSE VFD CONTROLLERS FURNISHED BY THE MECHANICAL CONTRACTOR. REFER TO MECHANICAL DOCUMENTS FOR VFD LOCATIONS AND QUANTITIES. ·"INT" = STARTER/CONTROLLER IS MANUFACTURED INTEGRAL TO THE EQUIPMENT. ·LOCATE STARTER/CONTROLLER ADJACENT TO INDOOR EQUIPMENT - PROVIDE WITH STRUT MOUNTING AS REQUIRED. ·WHERE STARTER SERVES OUTDOOR EQUIPMENT, LOCATE STARTER IN THE SOURCE ELECTRICAL ROOM. D. "CONTROL TYPE" - PROVIDE CONTROL AND CONNECTIONS: ·"INT" = CONTROLS ARE MANUFACTURED INTEGRAL TO THE EQUIPMENT (SELF-CONTAINED). ·"CONT" = EQUIPMENT OPERATES CONTINUOUSLY (NO CONTROLS). ·"NONE" = EQUIPMENT OPERATES CONTINUOUSLY OR CONTROLS ARE SELF-CONTAINED. ·"DDC" = CONTROL SIGNAL FROM TEMPERATURE CONTROL SYSTEM PROVIDED BY MECHANICAL CONTRACTOR OR TEMPERATURE CONTROLS CONTRACTOR. ·"TIME SW" = CONTROL SIGNAL FROM TIME SWITCH PROVIDED BY ELECTRICAL CONTRACTOR. TIME SWITCH SHALL BE 7-DAY DIGITAL TYPE WITH AUTOMATIC DAYLIGHT SAVINGS ADJUSTMENTS AND BATTERY BACKUP. LOCATE TIMESWITCH IN NEAREST MECHANICAL OR ELECTRICAL UTILITY ROOM. LABEL TIME SWITCH. COORDINATE TIME SCHEDULE WITH OWNER AND MECHANICAL ENGINEER. ·"WALL SW" = CONTROL SIGNAL FROM WALL SWITCH PROVIDED BY ELECTRICAL CONTRACTOR. COORDINATE LOCATION OF WALL SWITCH WITH OWNER. LABEL WALL SWITCH. ·"FA STOP" = FANS WITH CFM OF 2000 OR GREATER AND FANS SERVING DUCTS CONTAINING SMOKE DAMPERS. FIRE ALARM SYSTEM SHALL SHUTDOWN FAN UPON DETECTION OF SMOKE IN DUCT OR ROOMS SERVED FROM THIS EQUIPMENT. PROVIDE WITH INDIVIDUAL ADDRESSABLE CONTROL MODULE AT MOTOR CONTROLLER/STARTER AND CONNECT TO SHUTDOWN FAN. ·"FA START" = FANS USED FOR SMOKE EVACUATION OR PRESSURIZATION. FIRE ALARM SYSTEM SHALL START FAN UPON DETECTION OF SMOKE IN DUCT OR ROOMS SERVED FROM THIS EQUIPMENT. PROVIDE WITH INDIVIDUAL ADDRESSABLE CONTROL MODULE AT MOTOR CONTROLLER/STARTER AND CONNECT TO START FAN. ·"DATA" = PROVIDE WITH DATA CONNECTION FROM NEAREST DATA NETWORK COMMUNICATIONS ROOM. ·"CONDUIT" = PROVIDE EMPTY 3/4" CONTROLS CONDUIT BETWEEN INDOOR AND OUTDOOR UNIT TO ACCOMMODATE CONTROL CABLING BY MECHANICAL OR TEMPERATURE CONTROLS CONTRACTOR. E. "DISCONNECT" - PROVIDE DISCONNECT/RECEPTACLE AT EQUIPMENT LOCATION AND ASSOCIATED CONNECTION TO EQUIPMENT AND BRANCH CIRCUIT: ·"NEMA-___" = DUPLEX (TYP) RECEPTACLE TO ACCOMMODATE CORD AND PLUG CONNECTION (CORD AND PLUG FURNISHED WITH EQUIPMENT UNLESS NOTED OTHERWISE) ·"REC/SW" = PROVIDE 20A 120V RECEPTACLE OR 20A TOGGLE SWITCH DISCONNECT. COORDINATE REQUIRED SELECTION WITH EQUIPMENT. ·"NF" = NON-FUSED DISCONNECT. SIZE AND POLE QUANTITY AS INDICATED. 20/1 AND SMALLER SHALL BE TOGGLE SWITCH DISCONNECT. ·"F" = FUSED DISCONNECT. SIZE AND POLE QUANTITY AS INDICATED. FUSE PER MANUFACTURER'S RECOMMENDATIONS. ·"FUSTAT" = SWITCH AND FUSTAT. FUSE SIZE PER EQUIPMENT MANUFACTURER. LOCATE SWITCH IN CONCEALED ACCESSIBLE LOCATION. ·"ENCL CB" = ENCLOSED CIRCUIT BREAKER DISCONNECT. SIZE, POLE QUANTITY, AND FLUSH/SURFACE MOUNTING AS INDICATED. ·"ENCL MCSW" = ENCLOSED MOLDED CASE SWITCH DISCONNECT. SIZE, POLE QUANTITY, AND FLUSH/SURFACE MOUNTING AS INDICATED. ·"SHUNT ENCL CB" = SHUNT TRIP ENCLOSED CIRCUIT BREAKER DISCONNECT. SIZE, POLE QUANTITY, AND FLUSH/SURFACE MOUNTING AS INDICATED. PROVIDE WITH INTEGRAL 120V CONTROL TRANSFORMER SERVED FROM LINE SOURCE WITH PRIMARY AND SECONDARY FUSING. COORDINATE ENCLOSURE AND COVER SIZE TO ACCOMMODATE TRANSFORMER. PROVIDE WITH EQUIPMENT GROUND BAR AND SEPARATE INSULATED ISOLATED GROUND BAR. WHERE NEUTRAL CONDUCTOR IS UTILIZED, PROVIDE SOLID NEUTRAL BAR. CONNECT SHUNT TRIP VOLTAGE SOURCE AND ACTUATOR TO ASSOCIATED EMERGENCY POWER OFF (EPO) SWITCHES. PROVIDE EPO AND COORDINATE LOCATION. ·"DIV 15" = DISCONNECT IS FURNISHED BY MECHANICAL CONTRACTOR OR PROVIDED WITH MECHANICAL EQUIPMENT. ELECTRICAL CONTRACTOR SHALL PROVIDE MOUNTING AND ADDITIONAL CONNECTIONS REQUIRED FOR LOOSE DISCONNECTS FURNISHED BY THE MECHANICAL CONTRACTOR. ·INT" = DISCONNECT IS MANUFACTURED INTEGRAL TO THE EQUIPMENT. ·"HW" = HARDWIRE. DISCONNECT NOT REQUIRED. ·LOCATE DISCONNECT ADJACENT TO EQUIPMENT PER NEC - PROVIDE WITH STRUT MOUNTING AS REQUIRED. ·LOCATE RECEPTACLE OR JUNCTION BOX TO DIRECTLY SERVE EQUIPMENT. COORDINATE EXACT LOCATION WITH ARCHITECT, ARCHITECTURAL DETAILS, AND EQUIPMENT MANUFACTURER'S REQUIREMENTS. ·WHERE DISCONNECT SERVES OUTDOOR EQUIPMENT, PROVIDE AS NEMA-3R. ·PROVIDE DISCONNECT WITH EQUIPMENT GROUND KIT. ·WHERE FEEDER INDICATED UTILIZES A NEUTRAL, PROVIDE DISCONNECT WITH SOLID NEUTRAL KIT. ·WHERE FEEDER INDICATED UTILIZES AN ISOLATED GROUND, PROVIDE DISCONNECT WITH ADDITIONAL INSULATED GROUND KIT. ·DISCONNECTS NOT SHOWN AS "F" OR "NF" SHALL BE NON-FUSED. ·DISCONNECTS OF MOTORS SERVED FROM A VFD SHALL CONTAIN AUXILIARY CONTACTS CONNECTED TO THE VFD TO DISABLE VFD UPON DISCONNECTION. ·WHERE STARTERS VFD'S CONTAIN INTEGRAL DISCONNECTS AND ARE LOCATED PER NEC TO SATISFY AS THE EQUIPMENT DISCONNECT, AN ADDITIONAL EQUIPMENT DISCONNECT IS NOT REQUIRED. F. "GEN" ·EQUIPMENT IS SERVED FROM A SOURCE PANEL PROVIDED WITH GENERATOR BACK-UP.
GENERAL NOTES: A. CATALOG NUMBER VERIFICATION - CONTRACTOR SHALL VERIFY LIGHTING FIXTURE INSTALLATION REQUIREMENTS AND CATALOG NUMBER PRIOR TO ORDERING. B. SUBSTITUTIONS - WHERE INDICATED WITH 'N' (NO), NO SUBSTITUTIONS WILL BE ACCEPTED. WHERE INDICATED WITH 'P' (PRIOR APPROVAL), SUBSTITUTIONS MUST BE APPROVED PRIOR TO BID WITH ACCEPTANCE ISSUED BY ADDENDUM. WHERE INDICATED WITH 'Y' (YES), THE FOLLOWING MANUFACTURER'S ARE CONSIDERED ACCEPTABLE EQUIVALENT MANUFACTURER'S, PROVIDED THE EQUIVALENT FIXTURE IS OF THE SAME QUALITY, EFFICIENCY, PERFORMANCE AND CHARACTERISTICS AS THAT SCHEDULED: 1. ACUITY BRANDS 2. COOPER 3. HUBBELL 4. WILLIAMS SEE PROJECT SPECIFICATIONS FOR SPECIFIC MANUFACTURER/MODEL EQUIVALENCY OF COMMONLY USED LIGHTING FIXTURE TYPES. ABSENCE OF A SELECTION INDICATES THAT PRIOR APPROVALS ARE REQUIRED. C. DOWNLIGHT CEILING TRIM FINISH/COLOR SELECTION: PROVIDE DOWNLIGHT REFLECTOR FINISH/COLOR AS SPECIFIED IN THE LIGHTING FIXTURE SCHEDULE. SELECT CEILING TRIM FINISH/COLOR TO COORDINATE WITH CEILING TYPE. "WHITE" TRIM FOR DOWNLIGHTS MOUNTED IN WHITE ACOUSTICAL TILE CEILINGS. "CLEAR" (TO MATCH REFLECTOR FINISH/COLOR) FOR DOWNLIGHTS MOUNTED IN PAINTED GYPSUM BOARD CEILINGS. D. PRIOR APPROVALS - THE FOLLOWING MANUFACTURERS ARE APPROVED EQUALS FOR THE FIXTURE TYPE INDICATED: A1 - COLUMBIA LIGHTING D1 & D2 - PRESCOLITE H1 - NEW STAR LIGHTING L1 - COLUMBIA P1 - AFX INC. W1 - ACCESS LIGHTING W2 - NEW STAR LIGHTING
MMP20
3M TO EP3A
3M
SENSOR
PLUG
Ir (tr)
Isd (tsd)
Ii
JKS FUSE
CLASS J
200
--
--
--
--
SQUARE D
TYP. 120V BRANCH CIRCUIT
SQUARE D
QO
SQUARE D
5
6 H203 W1
DETAIL NOTE A
3M 3M
SF-1
3
PE 20HP
27-32A
DISCONNECT AHU SUPPLY FANS FROM FURNISHED VFD. PROVIDE INDIVIDUALLY MOUNTED 20 HP VFDS AND CONNECT SUPPLY FANS AS INDICATED.
NB
(136) MMP60
3M
3
4 H602 V1
M
5
6 H603 W1
3M 3M
3
SF-2
PE 20HP
27-32A
GROUND
NB
AHU-10 SUPPLY FANS CONNECTION DETAIL
JGE
250
100
A 100 (7)
12 (J,K,L)
FIXED
LD
250
250
250 (4)
--
12
HD
150
150
100 (FIXED)
3 (FIXED)
15
--
20
--
FIXED
--
--
MARK
NOMINAL SIZE
1M 1M1 3M 10N 11 11N 14 16T
---110 A 125 A 125 A 200 A 250 A
ED
FESSION PRO AL RE
G . NO.
10206 TRACY J. HAUSER U
A
3M
MTR6
3M
T
TO MCC1
2 H601 U1
REGIST ER
3M
1
GINEER EN
FRAME
CDP2 BRANCH
CDP2 MAIN
CUTLER HAMMER
M
T H
K D A
O
NOT TO SCALE
FEEDER SCHEDULE
TYPE
JG WITH DIGITRIP 310 POWERPACT WITH MICROLOGIC 3.3 TU POWERPACT WITH MICROLOGIC 3.3 TU
HGEN - CDP2
4 H202 V1
O
BUSSMANN
3
S
MSWB - CDP2
MTR2
3M
GROUND
OVERCURRENT DEVICE SETTINGS SCHEDULE MANUFACTURER
2 H201 U1
PROVIDE INDIVIDUALLY MOUNTED COMBINATION H.D. NON-FUSED SAFETY SWITCH AND VFD-20HP(70A FUSES)
1 DEVICE
3M
1
11/25/14
WIRE AND CONDUIT No.
MMP10
3-#12, #12 GND - 3/4"C. 2-#12, #12 GND - 3/4"C. 3-#8, #8 GND - 1"C. 4-#1, #6 GND - 2"C. 3-#1, #6 GND - 1-1/2"C. 4-#1/0, #6 GND - 2"C. 3-#3/0, #6 GND - 2"C. 4-300 KCMIL, #2 GND - 3"C.
1M TO EP3A
1M
1
2 H101 U1
MTR1
3
4 H102 V1
M
1M
6 H103 W1
1M
3
PE 10HP
11-16A
GROUND PROVIDE INDIVIDUALLY MOUNTED COMBINATION H.D. NON-FUSED SAFETY SWITCH AND VFD-10HP(35A FUSES)
GENERAL NOTES: (EQUIPMENT CONNECTION SCHEDULE)
Date
DETAIL NOTE A
1M 5
1M
RF-1
Description
DISCONNECT AHU SUPPLY FANS FROM FURNISHED VFD. PROVIDE INDIVIDUALLY MOUNTED 20 HP VFDS AND CONNECT SUPPLY FANS AS INDICATED.
NB
(136) MMP50
A. DEVICES AND SETTINGS HAVE BEEN SELECTED TO ENSURE SELECTIVE COORDINATION TO 0.01 SECONDS. ANY SUBSTITUTIONS SHALL BE APPROVED BY THE ENGINEER OF RECORD, PROVIDE SELECTIVE COORDINATION STUDY FOR ANY SUBSTITUTIONS. 1M TO MCC1
1M 1M
1
2 H501 U1
MTR6
3
4 H502 V1
M
5
6 H503 W1
1M 1M 1M
11-16A
3
PE 10HP
GROUND
2
RF-2
NB
AHU-10 RETURN FANS CONNECTION DETAIL NOT TO SCALE
INSTALL GREEN INSULATED GROUND WIRE WITH LIGHTING, RECEPTACLE AND EQUIPMENT BRANCH CIRCUITS.
SACRED HEART
INSTALL INDIVIDUAL (DEDICATED) NEUTRAL CONDUCTORS FOR EACH 120V OR 277V PHASE CONDUCTOR SERVED FROM A SINGLE POLE CIRCUIT BREAKER 2014
C
4TH & 5TH ELECTRICAL SCHEDULES
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
Date
SES PROJECT # 14041
11/25/2014 2:15:50 PM
E500 Scale
NONE
GENERAL NOTES
D D
IN PATIENT FLOORS CORRIDORS. SUPPORT CABLE WITH J-HOOK TYPE CABLE SUPPORT OR APPROVED EQUAL, MAX OF 5' ON CENTER
CABLE TRAY PER PLANS
SHEET NOTES
A. COORDINATE RACKS LAYOUTS WITH OWNERS IT REPRESENTATIVE PRIOR TO STARTING WORK. B. PROVIDE #6 AWG CU GREEN GROUND FROM TELECOM RACKS TO GROUND BAR OF NEW CRITICAL PANEL ON ROOF.
1
2 3
PROVIDE WITH BUSHING
ROOF 2092"
ROOF 174' - 4"
ROUTE COMMUNICATIONS CABLES ABOVE ACCESSIBLE CEILING TO FLOOR SERVING EQUIPMENT
4' - 7 15/16"
4
1' - 8 5/8" PROVIDE 1" CONDUIT STUBBED UP ABOVE NEAREST ACCESSIBLE CORRIDOR CEILING
TV OR
2' - 11" MAXIMUM 12" BETWEEN BOX CENTERS UNLESS SPECIFICALLY NOTED OTHERWISE. COORDINATE WITH ARCHITECTURAL DETAILS.
PROVIDE 4" SQUARE BY 2-1/8" DEEP BOX WITH SINGLE GANG PLASTER RING
GENERAL NOTES: 1. PROVIDE CABLING PER SPECIFICATIONS AND PLANS. 2. LABEL CABLES PER ANSI/TIA/EIA-606 STANDARDS.
T5 3
3
5
EXISTING DOOR TO REMAIN.
6
EXISTING WALL TO REMAIN.
7
SEE ARCHITECTURAL DRAWINGS FOR RACKS ENCLOSURE ASSEMBLY.
8
PROVIDE RACKS T51 AND T52 FIRST. OWNER WILL MIGRATE ELECTRONICS, PATCH PANELS, AND SWITCHES SERVING EXISTING OUTLETS TO THESE RACKS. REMOVE CABINETS T5. THEN PROVIDE RACKS T53 AND T54.
9
PROVIDE 30/1 125V SIMPLEX RECEPTACLE (CRITICAL BRANCH SOURCE) VIA #10 AWG. SEE ELECTRICAL DRAWINGS. PROVIDE 30/1 CIRCUIT BREAKER TO MATCH RATING OF EXISTING.
8
CR
10 EXISTING CABLES ROUTE THROUGH OPENING IN WALL. ALL REROUTED AND NEW CABLES SHALL BE ROUTED FROM ABOVE, NOT IN EXSTING WALL CAVITY.
9
11 OWNER FURNISHED, OWNER INSTALLED 25PR COPPER FROM RACK TO 3RD FLOOR TELECOM ROOM PHONE WALL FIELD. OWNER TO PROVIDE TERMINATION ON 110 WALL MOUNTED BLOCKS ON 3RD FLOOR AND ON RACK PATCH PANELS ON 5TH FLOOR.
10
5 11
2
RECEPTACLE PER PLAN
T54
T52
FIFTH LEVEL 1940"
FIFTH LEVEL 161' - 8"
T53
T51
TYPICAL CORRIDOR PHONE CABINET 'TTC__'
T5 D D
T54
EXISTING COPPER PAIRS BUNDLE
T52
AVERA FACILITY DEVELOPMENT FIFTH LEVEL
COPPER CABLING FURNISHED AND INSTALLED BY OWNER FOURTH LEVEL
E
SERVICE PROVIDER VOICE ROUTER, PRIMARY PROTECTION, AND WALL FIELD.
1
1.
PROVIDE WALL RACKS T51 AND T52.
2.
PROVIDE 120V 30/1 RECEPTACLES.
Communications or CATV Outlet
3.
PROVIDE FIBER TERMINATION EQUIPMENT.
4.
OWNER TO PROVIDE PHONE RISER CABLE.
NOT TO SCALE
5.
OWNER WILL MIGRATE EXISTING SWITCHES, RACK PATCH PANELS, UPS'S, ELECTRONICS AND EXISTING CABLES TO RACKS T51 AND T52.
6.
AFTER MIGRATION OF EXISTING ELECTRONICS AND CABLES TO RACKS T51 AND T52 IS COMPLETE, PROVIDE WALL RACKS T53 AND T54.
7.
PROVIDE NEW DATA AND VOICE OUTLETS AND CABLES AS REQUIRED BY CONSTRUCTION SPECIFICATIONS.
OWNER FURNISHED, OWNER INSTALLED WALL MOUNT 110 BLOCKS TO ACCOMMODATE COPPER BACKBONE AND CROSS CONNECT TO SERVER.
E
12 EXISTING CRITICAL BRANCH RECEPTACLE SHALL BE RELOCATED OUT OF FOOTPRINT OF NEW WALL MOUNT TELECOM RACKS. RECONNECT TO EXISTING CRITICAL BRANCH CIRCUIT PREVIOUSLY SERVING DEVICE.
DESCRIPTION OF WORK
2
EXISTING DATA CABINET
NURSES STATION
NURSES STATION
CP5A2-11 T51
1
TERMINATE CABLES AND PROVIDE FACEPLATE PER SPECIFICATIONS, PROVIDE BLANK COVERPLATES FOR LOCATIONS WITHOUT CABLING
CABLE TRAY, REFER TO FLOOR PLANS FOR SIZES.
6 T53
EXISTING 25PR COPPER FROM 48 PORT ORTRONICS RACK MOUNT, VOICE PATCH PANEL ON 5TH LEVEL TO 3RD FLOOR VOICE WALL FIELD. RELOCATION BY OWNER IT. (5TH FLOOR ONLY) EXISTING (TO BE RELOCATED AND RECONNECTED BY OWNER IT) 12 STRAND FIBER CABLE. EXISTING WALL MOUNTED SWING OPEN TYPE 19" VOICE AND DATA RACK.(T5). REMOVE T5 AFTER T51 AND T52 ARE INSTALLED AND SERVING EXISTING OUTLETS. PROVIDE T5 TO OWNER.
4
7 12
PROVIDE AT PLAN SYMBOL
TELECOM RACK (TYP.)
THIRD LEVEL
Telecommunications Cabling Routing Schematic NOT TO SCALE
Data Closet Elevation 1/4" = 1'-0"
FIRE ALARM CONTROL RELAY. PROVIDE (1) RELAY PER AIR HANDLING UNIT ZONE (TYP)
TO ADDITIONAL RELAYS
TO ADDITIONAL DAMPERS SERVING SAME AIR HANDLING UNIT ZONE. (TYP)
M CIRCUIT PER PLANS PROVIDE HORIZONTAL CABLING PER SPECIFICATIONS UNSWITCHED BRANCH CIRCUIT SOURCE PER PLAN
LABELING TO MATCH LOCATION SERVED BY OWNER
M LEGEND
LOW VOLTAGE WIRING PER MANUFACTURER'S RECOMMENDATIONS
XXX
120V. POWER F.A. CONTROL CIRCUIT
PROVIDED LABELING SCHEME AS DIRECTED BY OWNER
NOTES: 1. VERIFY ARRANGEMENT OF AIR HANDLING UNIT ZONES WITH MECHANICAL 2.
Typical Voice Information Delivery
FIRE ALARM CONTROL PANEL
UNDERCABINET LIGHT FIXTURE(S) (WHERE APPLICABLE)
NOT TO SCALE
LINE VOLTAGE TOGGLE SWITCH
LINE VOLTAGE TOGGLE OR DIMMER SWITCH (ROOMS WITH MULTIPLE ZONES) LINE VOLTAGE TOGGLE SWITCH
INDIVIDUAL ROOM/CORRIDOR
1. PROVIDE ALL NECESSARY COMPONENTS FOR A COMPLETE INSTALLATION. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. 2. WHERE CEILING LIGHT FIXTURES ARE 277V, PROVIDE ADDITIONAL RELAYS AND POWER PACKS AS NECESSARY TO CONTROL 120V UNDERCABINET LIGHTING. DATA SWITCH(ES) PROVIDED BY OWNER
OWNER PROVIDED 48 PORT PATCH PANEL(S) (TYPICAL)
PROVIDE HORIZONTAL CABLING PER SPECIFICATION
FIBER ENCLOSURE
OWNER PROVIDED LABELING TO MATCH LOCATION SERVED EXISTING FIBER BACKBONE CABLE
OWNER WILL PROVIDE 2 STRAND FIBER WITH CONNECTORS EACH END
RACK MOUNT
NOTES: 1. CONTRACTOR SHALL PROVIDE AND INSTALL PATCH PANELS (TYPICAL). SEE ELECTRICAL DRAWINGS FOR COMMUNICATION DEVICES. CONTRACTOR IS RESPONSIBLE FOR DEVICE COUNT AND QUANTITY OF PATCH PANELS REQUIRED PLUS 1 SPARE PATCH PANEL. 2. COORDINATE INSTALLATIONS WITH OWNER'S IS/IT REPRESENTATIVE.
7
Typical Data Information Delivery NOT TO SCALE
3. WHERE BI-LEVEL SWITCHING IS BEING IMPLEMENTED: 3 LAMP FIXTURES - SWITCH CLOSEST TO DOOR SHALL CONTROL OUTER TWO LAMPS IN EACH FIXTURE. SECOND SWITCH SHALL CONTROL CENTER LAMP IN EACH FIXTURE. 2 LAMP FIXTURES - EACH SWITCH SHALL CONTROL 50% OF THE LIGHT LEVEL IN EACH FIXTURE.
COMMUNICATIONS OUTLET (TYPE INDICATED PER PLAN)
PLAN SYMBOL COMBINATION
3.
RELAY SHALL INTERRUPT DAMPER POWER CIRCUIT UPON ALARM FROM VERIFIED SPOT TYPE DETECTOR WITHIN THE ASSOCIATED AIR HANDLING UNIT ZONE UNLESS OTHERWISE INDICATED.
4.
PROVIDE BREAKER LOCKS ON 120V. CIRCUITS.
G . NO.
10206 TRACY J. HAUSER U
T H
K D A
O
11/25/14
No.
Description
Date
Smoke Damper Connection NOT TO SCALE
CONTROL CONFIGURATION
OCCUPANCY SENSOR WITH DIMMER AND SWITCH
D -OR-
D
OCCUPANCY SENSOR WITH DIMMER OR SWITCH OCCUPANCY SENSOR WITH BILEVEL SWITCHING
3 3
OCCUPANCY SENSOR WITH BILEVEL SWITCHING - MULTIPLE LOCATIONS OCCUPANCY SENSOR ONLY (EXCLUDE WALL SWITCH INDICATED IN DETAIL)
XXX OWNER WILL PROVIDE PATCH CORD(S)
LABEL EACH RELAY WITH THE NAME OF THE AIR HANDLING SERVING THE SMOKE ZONE AND WITH THE WORDS "SMOKE DAMPER CONTROL".
RE
ADDITIONAL LINE VOLTAGE TOGGLE SWITCH FOR BI-LEVEL SWITCHING
NOTES:
PROVIDE FIBER ENCLOSURE(S) WITH CAPACITIES TO ACCOMMODATE EXISTING FIBER CABLES
4
O
PRIMARY LIGHTING ZONE
LOW VOLTAGE CEILING OCCUPANCY SENSOR
FESSION PRO AL
S
NOTES: 1. CONTRACTOR SHALL PROVIDE AND INSTALL PATCH PANELS (TYPICAL). SEE ELECTRICAL DRAWINGS FOR COMMUNICATION DEVICES. CONTRACTOR IS RESPONSIBLE FOR DEVICE COUNT AND QUANTITY OF PATCH PANELS REQUIRED PLUS 1 SPARE PATCH PANEL. 2. COORDINATE INSTALLATIONS WITH OWNER'S IS/IT REPRESENTATIVE.
ED
GINEER EN
OWNER WILL PROVIDE PATCH CORD(S)
6
ADDITIONAL LIGHTING ZONES (WHERE APPLICABLE)
COMMUNICATIONS OUTLET (TYPE INDICATED PER SPECIFICATIONS)
A
TO 3RD FLOOR TELECOM ROOM
POWER PACK(S) IN JUNCTION BOX
T
OWNER PROVIDED 48 PORT PATCH PANEL(S) (TYPICAL)
REGIST ER
OWNER PROVIDED BACKBONE CABLE PER SPECIFICATIONS
120V. MOTORIZED SMOKE DAMPER BY MECHANICAL (TYP)
PROVIDED LABELING SCHEME AS SPECIFIED
5
SACRED HEART
CEILING OCC SENSOR WITH SWITCH OR DIMMER 1/8" = 1'-0"
2014
C
4TH & 5TH ELECTRICAL DETAILS
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
Date
SES PROJECT # 14041
11/25/2014 2:15:50 PM
E501 Scale
NONE
Lighting Panel: CDP-2 Location: Supply From: Branch: Mounting: Ckt Circuit Description 1 3 5 7 9 CP5A2 11 13 15 17 19 21 23 25 27 29
Volts: Phases: Wires: Available SCC (kA):
3RD LEVEL ATS-CDP2 CRITICAL Surface
Opt Rati... Poles
A
9441 VA 100 A
Rating: Mains Type: Panel Poles: Sections:
120/208 Wye 3 4 9.8
B
250 A MCB 30 1
Poles Rati... Opt
C
Circuit Description
9623 VA
3
7390 VA
3
9183 VA 7640 VA
100 A
CP5B2
7820 VA
AVERA FACILITY DEVELOPMENT Ckt 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
Lighting Panel Remarks: 1. Spare Circuit Breakers: Provide the following spare branch circuit breakers in addition to circuit breakers listed above. Spares: 2-100/3 General Lighting Panel Notes: 1. Panel AIC (Interrupting) Rating shall be minimum 120% of the available SCC (Short Circuit Current). 2. Circuit Breaker Options: 'S' or 'ST' - Provide Shunt Trip Circuit Breaker / 'G' or 'GFCI' - Provide GFCI Circuit Breaker / 'GFP' - Provide GFP Circuit Breaker.
Lighting Panel: CP5A2
20 A 20 A 20 A
1 1 1
540 VA
B 1620 VA
C 1620 VA 1620 VA
940 VA
1410 VA 2000 VA
Poles 1 1 1620 VA 1 1 1 1320 VA 1 1
Rati... Opt Circuit Description 20 A PWR - CNV SPACE 525 20 A PWR - CNV SPACE 523 20 A PWR - CNV SPACE 521 20 A PWR - CNV SPACE 519 20 A LTG ROOM 505,506,507,508 20 A PWR - CNV SPACE 517 20 A LTG SPACE 1845
720 VA
540 VA 540 VA
540 VA 540 VA
540 VA
1 1 1
20 A 20 A 20 A
PWR - CNV SPACE 515 PWR - CNV SPACE 513 PWR - CNV SPACE 512
ED
FESSION PRO AL RE
G . NO.
GINEER EN
Ckt 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42
10206 TRACY J. HAUSER
O
U
A
PWR - CNV PWR - CNV SPACE 514 PWR - CNV
Opt Rati... Poles A 20 A 1 1620 VA 1620 VA 20 A 1 20 A 1 20 A 1 1620 VA 1620 VA 20 A 1 20 A 1 20 A 1 1176 VA 705 VA 20 A 1
100 A MLO 42 1
T
Circuit Description PWR - CNV SPACE 527 PWR - CNV SPACE 524 PWR - CNV SPACE 522 PWR - CNV SPACE 520 LTG ROOM 500,501,502,503,504 PWR SPACE 1949 HVAC PWR - CNV SPACE 512
Rating: Mains Type: Panel Poles: Sections:
120/208 Wye 3 4 4.1
S
Ckt 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41
Volts: Phases: Wires: Available SCC (kA):
Space 1974 CDP-2 Critical Recessed
REGIST ER
Location: Supply From: Branch: Mounting:
T H
K D A
O
11/25/14
Lighting Panel Remarks: 1. Spare Circuit Breakers: Provide the following spare branch circuit breakers in addition to circuit breakers listed above. Spares: 10-20/1
No.
Description
Date
General Lighting Panel Notes: 1. Panel AIC (Interrupting) Rating shall be minimum 120% of the available SCC (Short Circuit Current). 2. Circuit Breaker Options: 'S' or 'ST' - Provide Shunt Trip Circuit Breaker / 'G' or 'GFCI' - Provide GFCI Circuit Breaker / 'GFP' - Provide GFP Circuit Breaker.
Lighting Panel: CP5B2 Location: Supply From: Branch: Mounting: Ckt 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41
Circuit Description PWR - CNV SPACE 526 PWR - CNV SPACE 509 PWR - CNV SPACE 507 PWR - CNV SPACE 505 PWR - CNV SPACE 503 PWR - CNV SPACE 501 PWR - CNV SPACE 535 ROOM 529, 1884
Lighting Panel: EP3A Volts: Phases: Wires: Available SCC (kA):
Space 1975 CDP-2 Critical Recessed
Opt Rati... Poles A 20 A 1 720 VA 1307 VA 20 A 1 20 A 1 20 A 1 1620 VA 1620 VA 20 A 1 20 A 1 35 A 1 1620 VA 1656 VA 20 A 1
B 1620 VA
C 1620 VA 1620 VA
1620 VA
Rating: Mains Type: Panel Poles: Sections:
120/208 Wye 3 4 3.9
1620 VA 1620 VA
Poles 1 1 1620 VA 1 1 1 1175 VA 1 1
PWR - CNV SPACE 534 PWR - CNV SPACE 532 PWR - CNV SPACE 530 LTG SPACE 1860
20 A 20 A 20 A 20 A
1 1 1 1
540 VA
540 VA 540 VA
540 VA
Rati... Opt Circuit Description 20 A LTG ROOM 509,510,511,512,513 20 A PWR - CNV SPACE 508 20 A PWR - CNV SPACE 506 20 A PWR - CNV SPACE 504 20 A PWR - CNV SPACE 502 20 A LTG ROOM 514,515,516,517 20 A HVAC
705 VA 705 VA
540 VA 705 VA
213 VA
540 VA
Location: Supply From: Branch: Mounting:
100 A MLO 42 1
1
20 A
ROOM 532, 1873
1 1 1 1
20 A 20 A 20 A 20 A
PWR - CNV SPACE 533 PWR - CNV SPACE 531 PWR - CNV SPACE 529 LTG SPACE 512
Lighting Panel Remarks: 1. Spare Circuit Breakers: Provide the following spare branch circuit breakers in addition to circuit breakers listed above. Spares: 10-20/1 General Lighting Panel Notes: 1. Panel AIC (Interrupting) Rating shall be minimum 120% of the available SCC (Short Circuit Current). 2. Circuit Breaker Options: 'S' or 'ST' - Provide Shunt Trip Circuit Breaker / 'G' or 'GFCI' - Provide GFCI Circuit Breaker / 'GFP' - Provide GFP Circuit Breaker.
Ckt 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42
Ckt Circuit Description 1 3 AHU-10-SF-1 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41
3RD LEVEL
Volts: Phases: Wires: Available SCC (kA):
EDP Equipment Surface
Opt Rati... Poles
A 7482 VA
70 A
3
Rating: Mains Type: Panel Poles: Sections:
480/277 Wye 3 4 4.1
B
Poles Rati... Opt
C
100 A MLO 42 1
Circuit Description
3880 VA 7482 VA
3
3880 VA 7482 VA
35 A
AHU-10-RF-1
3880 VA
Lighting Panel Remarks: 1. Spare Circuit Breakers: Provide the following spare branch circuit breakers in addition to circuit breakers listed above. Spares:
Ckt 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42
SACRED HEART
2014
C
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS.
General Lighting Panel Notes: 1. Panel AIC (Interrupting) Rating shall be minimum 120% of the available SCC (Short Circuit Current). 2. Circuit Breaker Options: 'S' or 'ST' - Provide Shunt Trip Circuit Breaker / 'G' or 'GFCI' - Provide GFCI Circuit Breaker / 'GFP' - Provide GFP Circuit Breaker.
10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
4TH & 5TH ELECTRICAL PANEL SCHEDULES
Date
SES PROJECT # 14041
11/25/2014 2:15:51 PM
E502 Scale
NONE
AVERA FACILITY DEVELOPMENT
RISER DIAGRAM NOTES PROVIDE 208/120V 100A MLO PANEL
CP5A2 3 4
PROVIDE 208/120V 100A MLO PANEL
CP5B2 3
4
1
PROVIDE 100/3 NEW CIRCUIT BREAKER 'HGEN-CDP2' IN EXISTING SWITCHBOARD. CIRCUIT BREAKER SHALL MATCH MANUFACTURER AND RATINGS OF EXISTING. INSTALL CIRCUIT BREAKER IN CRITICAL SECTION OF SWITCHBOARD.
2
PROVIDE 200/3 NEW FUSED SWITCH 'MSWB-CDP2' IN EXISTING SWITCHBOARD. FUSES AND SWITCH SHALL MATCH MANUFACTURER AND RATINGS OF EXISTING. INSTALL FUSED SWITCH IN CRITICAL SECTION OF SWITCHBOARD.
3
PROVIDE #6 AWG CU GROUND CONDUCTOR FROM NEW CRICTICAL PANELBOARDS TO EXISTING NORMAL BRANCH PANELBOARDS AND EXISTING CRITICAL BRANCH PANELBOARD LOCATED ON SAME FLOOR. BOND CRITICAL PANELBOARDS AND NORMAL PANELBOARDS TOGETHER PER NEC.
4
STUB UP FIVE (5) SPARE 1"C. CONDUITS FROM TOP OF PANELBOARDS TO ACCESSIBLE CORRIDOR CEILING SPACE ABOVE.
5
REFER TO SHEET E211 - FIRST LEVEL - POWER PLAN FOR SWITCHBOARD LOCATION.
6
PROVIDE 100/3 CIRCUIT BREAKER IN EXISTING DISTRIBUTION PANEL. CIRCUIT BREAKER SHALL MATCH MANUFACTURER AND RATINGS OF EXISTING.
7
PROVIDE 200/3 DISCONNECT ON PRIMARY FEEDERS OF TRANSFORMER PER NEC.
8
COORDINATE ROUTING OF FEEDERS WITHIN EXISTING HOSPITAL WITH OWNER. ROUTE FEEDERS FROM GENERATOR ROOMS THROUGH EXISTING TUNNEL.
FIFTH LEVEL 10N
10N
FOURTH LEVEL
3 PROVIDE CDP-2 PANEL 208/120V 250A MCB
PROVIDE 480/277V 100A MLO PANEL
E503
EP3A 14 16T
7
PROVIDE XFMR-CDP2 480/277V TO 208Y/120V 75KVA TRANSFORMER
2 E503
THIRD LEVEL ATS-CDP2 480/277V 200A 3-POLE TRANSFER SW. SCCR: 8.5KA
11N
HOSP. MAIN ELEC ROOM 1030A
EXISTING TUNNEL
GENERATOR ROOM 1970
OLD GENERATOR ROOM 1971
14 11 E 2
EXISTING HOSPITAL SWITCHBOARD 'MSWB' 480/277V 3-PHASE 2500A
5
8
E
1
CRITICAL SECTION
6
E
E ATS-3 (EQUIP BRANCH) 480/277V 600A
CRITICAL SECTION
FIRST LEVEL HOSPITAL EMERGENCY SWITCHBOARD 'HGEN' 480/277V 3-PHASE 1600A
1980 ORIGINAL HOSPITAL
2012 NORTHERN LIGHTS HOSPITAL ADDITION
Partial Hospital Riser Diagram FESSION PRO AL RE
G . NO.
GINEER EN
S
10206 TRACY J. HAUSER
O
U
A
ED
T
NOT TO SCALE REGIST ER
1
5
EQUIPMENT BRANCH DISTRIBUTION PANEL 'EDP-A' 5 480/277V 3-PHASE 600A
T H
K D A
O
11/25/14
No.
PHASE
Description
Date
PHASE
ATS-CDP2 3-POLE SOLID NEUTRAL AUTOMATIC TRANSFER SWITCH
EXISTING SERVICE ENTRANCE PHASE
PHASE
EXISTING OUTPUT CIRCUIT BREAKER GENERATOR
PHASE (TYPICAL) XO TERMINAL
N
NEUTRAL
NEUTRAL BUS (TYPICAL)
N
N
PHASE
PHASE
G
GROUND BUS (TYPICAL)
G
G
GROUND GROUND TO CABINET
EQUIPMENT GROUND Transformer Ground Schedule Transformer kVA Grounding Mark
3
3, 6
G1
#12 IN 3/4" CONDUIT
9
G2
#10 IN 3/4" CONDUIT
15,30,45
G3
#6 IN 3/4" CONDUIT
75
G4
#2 IN 3/4" CONDUIT
112.5
G5
#1/0 IN 3/4" CONDUIT
150
G6
#2/0 IN 1" CONDUIT
150+
G7
#3/0 IN 1" CONDUIT
Dry-Type Transformer Grounding Detail NOT TO SCALE
SACRED HEART
Size CONNECT TO LOCAL GROUND BAR (SEE SCHEDULE FOR SIZE)
GROUND TO FRAME EXISTING SERVICE GROUNDING ELECTRODE
GROUND TO CABINET
TO LOAD
2014
2
Generator Grounding with 3-Pole A.T.S. NOT TO SCALE
C
COPYRIGHT
PERMISSION TO REPRODUCE ANY PART OF THIS DOCUMENT IS HEREBY GRANTED SOLELY FOR THE PURPOSE OF THE CONSTRUCTION OF THE PROJECT OR THE ARCHIVING OF THIS PROJECT. UNAUTHORIZED USE OF THIS DOCUMENT WITHOUT THE WRITTEN PERMISSION OF SPECIALIZED ENGINEERING SOLUTIONS IS PROHIBITED BY COPYRIGHT LAW. DO NOT SCALE DRAWING. ALL DIMENSIONS AND CLEARANCES SHALL BE VERIFIED FROM APPROPRIATE SOURCES. ALL WORK SHALL BE COORDINATED PRIOR TO INSTALLATION. SEE SPECIFICATIONS. 10360 Ellison Circle Omaha, NE 68134 Phone: 402.991.5520 www.specializedeng.com
4TH & 5TH ELECTRICAL RISER DIAGRAM
Date
SES PROJECT # 14041
11/25/2014 2:15:51 PM
E503 Scale
NONE
NOTES:
FIRST FLOOR PIPING DEMOLITION PLAN
NOTES:
SECOND FLOOR PIPING DEMOLITION PLAN
NOTES:
THIRD FLOOR PIPING DEMOLITION PLAN
NOTES:
FIRST FLOOR UNDER SLAB HVAC DEMOLITION PLAN
NOTES:
FIRST FLOOR (CEILING SPACE) HVAC DEMOLITION PLAN
NOTES:
SECOND FLOOR HVAC DEMOLITION PLAN
NOTES:
THIRD FLOOR HVAC DEMOLITION PLAN
NOTES:
ROOF PLAN
NOTES:
FIRST FLOOR WASTE & VENT PIPING PLAN
NOTES:
FIRST FLOOR DOMESTIC PIPING PLAN
NOTES:
SECOND FLOOR PIPING PLAN
NOTES:
THIRD FLOOR PIPING PLAN
NOTES:
FIRST FLOOR HVAC PLAN
NOTES:
SECOND FLOOR HVAC PLAN
NOTES:
THIRD FLOOR HVAC PLAN
NOTES:
ROOF PLAN
PLUMBING / MECHANICAL ABBREVIATED SPECIFICATIONS
GENERAL MECHANICAL NOTES
DESIGN CONDITIONS
GAS LOAD: PLUMBING / MECHANICAL ABBREVIATIONS
PLUMBING / MECHANICAL LEGEND
PACKAGED MAKE UP AIR UNITS
PLUMBING FIXTURES
FAN SCHEDULE
GRILLE & REGISTER SCHEDULE
SPLIT SYSTEM GAS FURNACES
WATER HEATER SCHEDULE
CIRCULATING PUMPS
14
9
5
1
15
10
6
2
16
11
7
3
12
8
4
13
A.
Provide all materials and equipment and perform all labor required to install complete and operable mechanical systems as indicated on the drawings, as specified, and as required by authorities having jurisdiction.
B.
Contract document drawings for mechanical work (HVAC and plumbing) are diagrammatic and are intended to convey scope and general arrangement only.
Z.
Install all mechanical equipment and appurtenances in accordance with manufacturers' recommendations, contract documents, and applicable codes and regulations.
PIPING
C.
D.
Provide vibration isolation for all mechanical equipment to prevent transmission of vibration to building structure.
E.
Provide vibration isolators for all piping supports connected to, and within 50 feet of, isolated equipment (except at base elbow supports and anchor points) throughout mechanical equipment rooms.
F.
The location of existing underground utilities is shown in an approximate way only. The contractor shall determine the exact location of all existing utilities before commencing work. The contractor shall pay for and repair all damages caused by failure to exactly locate and preserve any and all underground utilities unless otherwise noted.
BUILDING AUTOMATION SYSTEM
MCA
MINIMUM CIRCUIT AMPACITY
BFF
BELOW FINISHED FLOOR
MEZZ
MEZZANINE
BFG
BELOW FINISHED GRADE
MFS
MAXIMUM FUSE SIZE
BHP
BRAKE HORSE POWER
MIN
MINIMUM
BTU
BRITISH THERMAL UNIT
MISC
MISCELLANEOUS
BTUH
BTU PER HOUR
MOP, MOCP
MAXIMUM OVER CURRENT PROTECTION
CA
COMPRESSED AIR
CPVC
CU IN
CUBIC INCH
DIAMETER
DN
DOWN
EA
EACH
EL
ELEVATION
Install all piping without forcing or springing.
R.
J.
All piping shall clear doors and windows.
Provide access doors in ductwork for the operation, adjustment, and maintenance of all fans, valves, and mechanical equipment.
K.
All valves shall be adjusted for smooth and easy operation.
S.
L.
All piping work shall be coordinate with all trades involved. Offsets in piping around obstructions shall be provided at no additional cost to the owner.
Smoke detectors shall be furnished and wired by the electrical contractor. The mechanical contractor shall be responsible for mounting the smoke detector in ductwork as shown on the drawings and in accordance with the manufacturer's printed instructions.
T.
Terminate gas vents for unit heaters, water heaters, high-pressure parts washers, high-pressure cleaners, and other gas appliances a minimum of 30 inches above the roof with rain cap.
U.
See specifications for ductwork gauges, bracing, hangers, and other requirements.
Where two or more items of the same type of equipment are required, the product of one manufacturer shall be used. Coordinate all equipment connections with manufacturers' certified drawings. Coordinate and provide all duct and piping transitions required for final equipment connections to furnished equipment. Field verify and coordinate all duct and piping dimensions before fabrication.
N.
All control wire and conduit shall comply with the National Electric Code and Division 26 of the specification.
O.
Where beams are indicated to be penetrated with ductwork or piping, coordinate ductwork and piping layout with beam opening size and opening locations. Coordination shall be done prior to the fabrication of ductwork, cutting of piping, or fabrication of beams. When mechanical work (HVAC, plumbing, sheet metal, etc.) is subcontracted, it shall be the mechaincal contractor's responsibility to coordinate subcontractors and the associated contracts. When discrepancies arise pertaining to which contractor provides a particular item of the mechanical contract or which contractor provides final connections for a particular item of the mechanical contract, it shall be brought to the attention of the mechanical contractor, whose decision shall be final. The locations of all items shown on the drawings or called for in the specifications that are not definitely fixed by dimensions are approximate only. The exact locations necessary to secure the best conditions and results must be determined by the project site conditions and shall have the approval of the engineer before being installed. Do not scale drawings.
R.
All miscellaneous steel required to ensure proper installation and as shown in details for piping, ductwork, and equipment (unless otherwise noted) shall be furnished and installed by the mechanical contractor.
S.
Provide access panels for installation in walls and ceilings, where required, to service dampers, valves, smoke detectors, and other concealed mechanical equipment. Access panels shall be turned over to the general contractor for installation.
ESP
EXTERNAL STATIC PRESSURE
EWT
ENTERING WATER TEMPERATURE
FLA
FULL LOAD AMPERES
FPS GA GAL GALV GPD GPH GPM HG
M.
Provide flexible connections in all piping systems connected to pumps, chillers, cooling towers, and other equipment which require vibration isolation except water coils. Flexible connections shall be provided as close to the equipment as possible or as indicated on the drawings.
N.
Slope refrigerant piping one percent in the direction of oil return. Liquid lines may be installed level.
O.
Provide line size liquid indicators in the main liquid line leaving the condenser or receiver. Install moisture-liquid indicators in liquid lines between filter dryers and thermostatic expansion valves, and in liquid line to receiver.
P.
Provide a line size strainer upstream of each automatic valve. Provide a shutoff valve on each side of a strainer.
Q.
Provide permanent filter dryers in low-temperature systems and systems using hermetic compressors.
R.
Provide replaceable cartridge filter dryers with a three-valve bypass assembly for solenoid valves, adjacent to receivers.
S.
Provide refrigerant charging valve connections in the liquid line between the receiver shutoff valve and the expansion valve.
HVAC/SHEET METAL A.
Provide all materials and equipment and perform all labor required to install complete and operable HVAC systems as indicated on the drawings, and as specified and required by authorities having jurisdiction.
B.
Certain items such as rises and drops in ductwork, access doors, volume dampers, etc., are indicated on the contract document drawings for clarity for a specific location requirement and shall not be interpreted as the extent of the requirements for these items.
C.
In corridors where ceiling speakers and air diffusers are indicated between the same light fixtures, install both devices at the quarter points between the same fixture.
D.
Unless otherwise shown, locate all room thermostats and humidistats 4'-0" (centerline) above the finished floor. Notify the engineer of any rooms where the preceding location cannot be maintained or where there is a question on location.
W. Locations and sizes of all floor, wall, and roof openings shall be coordinated with all other trades involved.
E.
All ductwork shall clear doors and windows.
X.
F.
All ductwork dimensions, as shown on the drawings, are internal clear dimensions and duct size shall be increased to compensate for duct lining thickness.
G.
Provide all 90-degree square elbows with double radius turning vanes unless otherwise indicated. Elbows in
T.
All equipment, piping, ductwork, etc., shall be supported as detailed, specified, and required to provide a vibration-free isolation.
U.
All ductwork, piping, and equipment supported from structural steel shall be coordinate with the general contractor. All attachments to steel bar joists, trusses, or joist girders shall be at panel points. Provide beam clamps meeting MSS standards. Welding to structural members shall not be permitted. The use of C-clamps shall not be permitted. Mechanical equipment, ductwork, and piping shall not be supported from a metal deck.
All openings in fire walls due to ductwork, piping, conduit, etc., shall be fire stopped with a product similar to 3M or an approved equal.
HVAC SYMBOLS
LINETYPES
TWO LINE ACCESS PANEL
HVAC CONDENSATE ELBOW, RADIUS
BALANCING VALVE
PUMP
CHECK VALVE - SWING
PRESSURE GAUGE PRESSURE GAUGE W/ COIL SYPHON
OC
ON CENTER
END CAP
SAFETY RELIEF VALVE
OD
OUTSIDE DIAMETER
FLANGE OR UNION CONNECTION
SHUT-OFF VALVE
FLEXIBLE CONNECTOR
SOLENOID VALVE
POLYVINYL CHLORIDE
REQD
REQUIRED
RPM
REVOLUTIONS PER MINUTE
SENS
SENSIBLE
FEET PER MINUTE SPEC
SPECIFICATION
SQ FT
SQUARE FEET
SQ IN
SQUARE INCHES
SS
STAINLESS STEEL
STD
STANDARD
TEMP
TEMPERATURE
T-STAT
THERMOSTAT
TYP
TYPICAL
V
VOLTS
VFD
VARIABLE FREQUENCY DRIVE
ROUND RETURN/EXHAUST, UP/DN
PRESSURE REGULATING VALVE
TAKE-OFF GLOBE VALVE
STRAINER - Y-PATTERN
IMMERSION THERMOSTAT
STRAINER - Y-PATTERN W/ DRAIN
METER
TEE UP/DOWN
MIXING VALVE
TEE UP/DOWN W/ VALVE IN DROP
SYMBOLS M
B
F
POINT OF CONNECTION
THERMOMETER
POINT OF DISCONNECTION
TRAP (RUNNING)
DRAWING INDEX
DAMPER - BYPASS
H
DAMPER - FIRE
C2
(TAG)
(TAG) FS
DAMPER - FIRE/SMOKE
C (TAG)
DAMPER - MOTORIZED
DP (TAG)
S
DAMPER - SMOKE
H2 (TAG)
FLOW ARROW
PD (TAG)
GALVANIZED DG
DOOR GRILLE
GALLONS PER DAY
HR
HOUR
HZ
HERTZ
ID
INSIDE DIAMETER
IN, "
INCHES
KW
KILOWATT
LBS
POUNDS
RH (TAG)
UC
DOOR UNDERCUT
RT (TAG)
POINT OF CONNECTION
WATTS
WG
WATER GAUGE
W/
WITH
W/O
WITHOUT
HUMIDISTAT H001T
ABBREVIATIONS, GENERAL NOTES, AND SYMBOLS
H201T
AREA 'H' HVAC PLAN
H202T
AREA 'H' MEZZANINE HVAC PLAN
SENSOR - DEWPOINT
H203T
AREA 'J' & 'K' HVAC PLANS
SENSOR - HYDROGEN
H240T
AREA 'H' HVAC ROOF PLAN
H501T
DETAILS
H801T
EQUIPMENT SCHEDULES
SENSOR - CARBON DIOXIDE SENSOR - CARBON MONOXIDE
SENSOR - PRESSURE DIFFERENTIAL SENSOR - RELATIVE HUMIDITY SENSOR - ROOM TEMPERATURE SENSOR (W/ EQUIPMENT TAG)
S (TAG)
POINT OF DISCONNECTION
SMOKE DETECTOR
SD
THERMOSTAT (W/ EQUPMENT TAG)
T (TAG)
W
CPS ENERGY PO BOX 1771 SAN ANTONIO, TX 78296 (210) 353-4050
SUPPLY/INTAKE, UP/DN
GALLON
MERCURY
119296
ROUND SUPPLY/INTAKE, UP/DN
GAUGE
GALLONS PER MINUTE
JONATHAN R. OLSON
NATURAL GAS UTILITY CONTACT INFORMATION:
RETURN/EXHAUST, UP/DN
M
GALLONS PER HOUR
COOLING 75°F COOLING 50% RH HEATING 70°F TRUCK MAINTENANCE BAYS COOLING 80°F HEATING 55°F
REDUCER
FEET PER SECOND
HORSE POWER
OFFICE
MANUAL BALANCING DAMPER
ELBOW UP/DOWN W/ VALVE IN DROP
PVC
ENGINEERING FIRM NO. F-9414
ROOM DESIGN CONDITIONS: FLEXIBLE DUCT
NOT TO SCALE
POINT OF DISCONNECTION
2013 ASHRAE FUNDAMENTALS LOCATION COOLING OADB 99.0°F COOLING OAWB 73.5°F HEATING OADB 29.2°F
ELBOW W/VANES
NTS
POD
APPLICABLE CODES: 2012 INTERNATIONAL PLUMBING CODE (IPC) 2012 INTERNATIONAL MECHANICAL CODE (IMC) 2012 INTERNATIONAL FUEL GAS CODE (IFGC) 2012 INTERNATIONAL ENERGY CONSERVATION CODE (IECC)
PROJECT DESIGN CONDITIONS:
REFRIGERANT
ELBOW UP/DOWN
POINT OF CONNECTION
AP
AP
NATURAL GAS
FEET
HP
DESIGN INFORMATION SINGLE LINE
NATURAL GAS
NG
POC
Runs of flexible duct shall not exceed 5 feet in length.
I.
Testing, adjusting, and balancing agency shall be a member of the Associated Air Balance Council (AABC) or the National Environmental Balancing Bureau (NEBB). Testing, adjusting, and balancing shall be performed in accordance with the AABC standards.
NORMALLY OPEN
PSI GAUGE
O.
Provide access doors in ductwork to provide access for all smoke detectors, fire dampers, smoke dampers, volume dampers, humidifiers, coils, and other items located in the ductwork that require service and/or inspection.
N/O
PSIG
Unless otherwise noted, all ductwork is overhead, tight to the underside of the structure, with space for insulation if required.
Q.
NORMALLY CLOSED
POUNDS PER SQUARE INCH
N.
Unions and/or flanges shall be installed at each piece of equipment, in bypasses, and in long piping runs (100 feet or more) to permit disassembly for alteration and repairs.
N/C
PSI
Provide flexible connections in all ductwork systems (supply, return, and exhaust) connected to air handling units, fans, and other equipment that require vibration isolation. Flexible connections shall be provided at the point of connection to the equipment unless otherwise indicated.
H.
DEGREES
DIA, Ø
FPM
NOT APPLICABLE
M.
All ductwork shall be coordinated with all trades involved. Offsets in ducts, including divided ducts and transitions around obstructions, shall be provided at no additional cost to the owner.
CHORINATED POLYVINYL CHLORIDE CUBIC FEET
FT,'
N/A
Finned tube radiation enclosures shall be wall-to-wall unless otherwise indicated.
P.
CAST IRON
CU FT
DEG, °
MOTOR
L.
Locate all temperature, pressure, and flow measuring devices in accessible locations with the straight section of pipe or duct up- and downstream as recommended by the manufacturer to ensure accuracy of measurements.
All balancing valves and butterfly valves shall be provided with position indicators and the maximum adjustable stops (memory stops).
SYMBOLS MTR
Locate all mechanical equipment (single duct, dual duct, variable volume, constant volume, and fan-powered boxes; fan-coil units; cabinet heaters; unit heaters; unit ventilators; coils; steam humidifiers; etc.) for unobstructed access to unit access panels, controls, and valving.
J.
COND
CI
Unless otherwise noted, all piping is overhead, tight to the underside of the structure or slab, with space for insulation if required.
MAXIMUM
BAS
K.
Unless otherwise noted, all valves (except control valves) and strainers shall be the full size of the pipe before reducing in size to make connections to equipment and controls.
LEAVING WATER TEMPERATURE
BTU PER HOUR (THOUSAND)
CUBIC FEET PER MINUTE
C.
PIPING SYMBOLS
MBH
CFM
Elevations shown on the drawings are to the bottom of all pressure piping an to the invert of all gravity piping unless otherwise noted.
G.
NG
CUBIC FEET PER HOUR
B.
All tests shall be completed before any mechanical equipment or piping insulation is applied.
ABBREVIATIONS
APPROXIMATE, APPROXIMATELY
All air handling units shall operate without moisture carryover.
I.
V.
APPROX
J.
F.
Q.
CFH
Provide all materials and equipment and perform all labor required to install complete and operable piping systems as indicated on the drawings, and as specified and required by authorities having jurisdiction.
Maintain a minimum 6'-8" clearance to the underside of pipes, ducts, conduits, suspended equipment, etc., throughout access routes in mechanical rooms.
P.
MAX
Field-erected and factory-assembled air handling unit coils shall be arranged for removal from the upstream side without dismantling supports. Provide galvanized structural steel support for all coils (except the lowest coil) in banks over two coils high to permit the independent removal of any coil.
All valves shall be installed so that the valve remains in service when equipment or piping on the equipment side of the valve is removed.
M.
ABOVE FINISHED GRADE
I.
Refer to typical details for ductwork, piping, and equipment installation.
E.
L.
AFG
Coordinate diffuser, register, and grille locations with architectural reflected ceiling plans, lighting, and other ceiling items and make minor duct modifications to suit.
Coordinate construction of all mechanical work with architectural, structural, civil, electrical work, etc., shown on other contract document drawings.
K.
LWT
H.
Install piping so all valves, strainers, unions, traps, flanges, and other appurtenances requiring access are accessible.
H.
ABOVE FINISHED FLOOR
A.
dishwasher, kitchen, and laundry exhausts shall be of unvaned, smooth radius construction with a radius equal to 1-1/2 times the width of the duct. Provide access doors upstream of all elbows with turning vanes.
D.
G.
AFF
All air-conditioning condensate drain lines from each air handling unit and rooftop unit shall be piped full size of the unit drain outlet, with "P" trap, and piped to the nearest allowable drain in accordance with the authority having jurisdiction. See the details shown in the drawings or contract specifications for the depth of the air conditioning condensate trap.
950 Walnut Ridge Drive Hartland, WI 53029 262.369.3535 T 262.369.3592 F
Y.
SMART BUILDING SOLUTIONS
GENERAL
DESIGN SERVICES
GENERAL NOTES
12/19/16
H1
H2
H3
H4
2.
18"Ø EXHAUST AIR DUCT UP THROUGH ROOF.
3.
22"X60" SUPPLY AIR DUCT FROM MAKE-UP AIR.
4.
22x28 OUTSIDE AIR AND 18x46 EXHAUST UP TO DEDICATED OUTSIDE AIR UNIT.
5.
22x18 SUPPLY DOWN FROM MAKE-UP AIR UNIT. INSTALL MANUFACTURER'S THREE-WAY DIFFUSER AT 16'-0" AFF.
6.
PROVIDE 20x20 ROOF OPENING AND EXHAUST DUCT.
7.
PROVIDE 18x18 ROOF OPENING AND EXHAUST DUCT.
8.
PROVIDE 20x20 ROOF OPENING AND EXHAUST DUCT. PROVIDE DRIP PAN 12" BELOW PRECAST PLANK.
9.
CARMON MODEL 55-S8 PLUG-IN FLOOR CONNECTION FOR CLOSE CAPTURE EXHAUST SYSTEM.
10.
MOUNT TOP OF LOUVER 1'-0" BELOW ROOF.
11.
42"Ø EXHAUST DUCT FROM PAINT BOOTH FAN CONNECTION, UP THROUGH ROOF, TERMINATE ON ROOF WITH MANUFACTURERS EXHAUST PACKAGE.
12.
SPUNSTRAND OR EQUAL FRP DUCT WITH WATER TIGHT JOINTS.
13.
12"X12" EXHAUST AIR DUCT UP TO EXHAUST FAN. SEE DETAIL 2/H501T.
14.
CARMON MODEL 55-S5 PLUG-IN FLOOR CONNECTION FOR CLOSE CAPTURE EXHAUST SYSTEM.
15.
PROVIDE (2) 5Ø BY 20 FOOT CARMON TYPE HTC FLEX HOSE ASSEMBLIES WITH CTA-5 ADAPTER & PLUG-IN ASSEMBLY. PROVIDE (3) 8Ø BY 20 FOOT CARMON TYPE HTC HOSE ASSEMBLIES WITH CTA-8 ADAPTER & PLUG-IN ASSEMBLY. PROVIDE (2) CARMON MODEL DCA-R AND (3) CARMON MODEL DCA-8 DIESEL CANE ASSEMBLIES. PROVIDE (3) CARMON PORTABLE STORAGE CARTS FOR HOSE ASSEMBLIES AND (5) CARMON WALL HANGERS FOR DIESEL CANE ASSEMBLIES.
1.
SEE APPLICABLE NOTES ON SHEET H001T.
H6
H7
950 Walnut Ridge Drive Hartland, WI 53029 262.369.3535 T 262.369.3592 F
30"X30" EXHAUST AIR DUCT UP TO EXHAUST FAN. SEE DETAIL 2/H501T.
SMART BUILDING SOLUTIONS
SHEET GENERAL NOTES
1.
H5
DESIGN SERVICES
SHEET KEY NOTES
#
H8
30"X30" EA DUCT FROM 12" AFF, END OF DUCT OPEN TO ROOM WITH BIRDSCREEN.
HA EWH-1T
30"X30"
34"X34" SA DUCT DOWN TO PAINT BOOTH SUPPLY AIR PLENUM.
ROUTE HORIZONTAL DUCT IN JOIST SPACE
1
20X40
6
MOUNT BOTTOM OF SUPPLY DUCT AT 20'-0" AFF.
30"X18" SR-1 1800CFM
1-1/4" NG FROM ROOF TO WATER HEATER. 8Ø
9
10Ø
X" NG FROM ROOF TO WATER HEATER
8"Ø EA DUCT OPEN TO PIT, 12"AFF OF PIT. PROVIDE SS BIRDSCREEN. (215CFM)
36"X36" SR-1 5100CFM
15
12Ø
CG-4 75CFM
36"X36" SR-1 5100CFM
12Ø
119296
15
1-1/2" NG FROM ROOF TO PRESSURE WASHER
12
30"X18" SR-1 1800CFM
PITCH
CD-1 50
5
15
8Ø
UC
11
JONATHAN R. OLSON
PITCH
H
6Ø
6Ø
8Ø
8Ø
T MAU-1T & 2T
CG-3
12/19/16
CG-4 100
6Ø
CD-1 150
MOUNT BOTTOM OF SUPPLY DUCT AT 20'-0" AFF. 20X40
20x14
8Ø
8Ø
26x14
ROUTE DUCT IN JOIST SPACE
18Ø
12x14 6Ø
26x14
12"X12"
14Ø
H
8Ø
CD-3 400
10Ø
8"Ø EA DUCT FROM BFF
10Ø
10Ø
MOUNT BOTTOM OF SUPPLY DUCT AT 20'-0" AFF.
RTU-1T T
12"X12" EA DUCT UP THRU MEZZANINE
ENGINEERING FIRM NO. F-9414
2
10Ø
10Ø
CD-3 400
HB
36"X36" SR-1 5100CFM 9
CD-3 400
13
12
16X40
UC
3 CD-3 400
7
PITCH
CG-4 75CFM
12x12 6Ø
CG-4 100
CD-1 190
16X40
3
CG-4 100 8Ø
6Ø
6Ø
9
36"X36" SR-1 5100CFM
8"Ø EA DUCT OPEN TO PIT, 12"AFF OF PIT. PROVIDE SS BIRDSCREEN. (215CFM)
8Ø
CG-3
8"Ø EA DUCT OPEN TO PIT, 12"AFF OF PIT. PROVIDE SS BIRDSCREEN. (135CFM)
1
CD-1 190 CG-5 100
8
ROUTE HORIZONTAL DUCT IN JOIST SPACE
30"X30"
CG-3
CD-1 250
MOUNT BOTTOM OF SUPPLY DUCT AT 20'-0" AFF.
20"X20" EA DUCT UP TO EF, PROVIDE DRIP PAN MOUNTED 12" BELOW BOTTOM OF CONCRETE PLANK. SEE DETAIL 1/H501T MAU-4T T
HC 30"X30" EA DUCT FROM 12" AFF, END OF DUCT OPEN TO ROOM WITH BIRDSCREEN.
10
AREA 'K'
LVR-1T AREA 'H'
AREA 'J'
AREA 'L' AREA 'B' AREA 'E'
AREA 'A'
AREA 'F'
AREA 'C'
AREA 'D'
MAIN BUILDING (AREAS A, B, C, D, E & F) IS PART OF A SEPARATE DRAWING SET
H1
SEE APPLICABLE NOTES ON SHEET H001T.
950 Walnut Ridge Drive Hartland, WI 53029 262.369.3535 T 262.369.3592 F
1.
SMART BUILDING SOLUTIONS
DESIGN SERVICES
SHEET GENERAL NOTES
H2
HA
ENGINEERING FIRM NO. F-9414
32"X18" SUPPLY AND RETURN UP TO ROOF TO UNIT.
HB
JONATHAN R. OLSON 26X14
119296
26X14
12/19/16
26"X14" SUPPLY AND RETURN DOWN
12"X12" EA DUCT FROM BELOW
12"X12" EA DUCT UP TO EF-7T, SEE DETAIL 2/H501T
12X12
HC
AREA 'K' AREA 'H'
AREA 'J'
AREA 'L' AREA 'B' AREA 'E'
AREA 'A'
AREA 'F'
AREA 'C'
AREA 'D'
MAIN BUILDING (AREAS A, B, C, D, E & F) IS PART OF A SEPARATE DRAWING SET
SEE APPLICABLE NOTES ON SHEET H001T.
2.
ROUTE CONDENSATE FROM ROOF TOP UNIT TO DOWN SPOUT SCUPPER.
SHEET KEY NOTES
#
J1
1.
10"x10" EXHAUST DUCT UP TO EF-1G.
2.
16"x16" SUPPLY AND 14"X24" RETURN AIR DUCT UP TO RTU-1G.
950 Walnut Ridge Drive Hartland, WI 53029 262.369.3535 T 262.369.3592 F
1.
SMART BUILDING SOLUTIONS
DESIGN SERVICES
SHEET GENERAL NOTES
J2
JA CD-2 100
6Ø
CG-5 100
JB CG-4 50
CG-5 100 6Ø
6Ø
6Ø
EF-1G (ON ROOF)
6Ø
CD-2 100
8x10 CD-1 100
WEATHERHOOD
UC
WALL OUTLET EXHAUST TERMINAL
JC 1 CG-3
19"x8"
6Ø CD-1 100
6Ø
2
EF-1FP
EF-2FP
UC RTU-1G T H
MOUNT BOTTOM OF EXHAUST FAN AT 8'-0" AFF.
16x14
10x10
12x14
MOUNT BOTTOM OF EXHAUST FAN AT 6'-0" AFF. RTU-1G (ON ROOF)
12Ø CD-1 400
12Ø CD-1 400
ENGINEERING FIRM NO. F-9414
JD
JONATHAN R. OLSON EUH-1FP
REVERSE ACTING
119296 MOUNT BOTTOM OF UNIT HEATER AT 7'-0" AFF.
EF-2FP REV.
T
EUH-1FP
T
MOUNT BOTTOM OF LOUVER AT 16" AFF.
12/19/16
LVR-1FP
AREA 'K' AREA 'H'
AREA 'J'
AREA 'L' AREA 'B' AREA 'E'
AREA 'A'
AREA 'F'
AREA 'C'
AREA 'D'
MAIN BUILDING (AREAS A, B, C, D, E & F) IS PART OF A SEPARATE DRAWING SET
H1
H2
H3
H4
H5
SEE APPLICABLE NOTES ON SHEET H001T.
H6
H7
950 Walnut Ridge Drive Hartland, WI 53029 262.369.3535 T 262.369.3592 F
1.
SMART BUILDING SOLUTIONS
DESIGN SERVICES
SHEET GENERAL NOTES
H8
2" NATURAL GAS SERVICE PRESSURE = 10 PSIG CONNECTED LOAD = 4,670 CFH LONGEST LENGTH = 1,275 FT 2" (2509 CFH)
2" (3641 CFH)
HA NG
NG 1-1/4" (1132 CFH)
NG
2" (2509 CFH)
NG
EF-3T
NG
MAU-3T
EF-4T
1" (199 CFH) NG
MAU-1T
1-1/4" (898 CFH)
NG
1-1/2" (2310 CFH)
1-1/4" NG DOWN TO WATER HEATER EF-8T
NG 1-1/4" (1029 CFH)
NG
3/4" (131 CFH)
EF-6T
NG
NG
X" (199CFH) NG DOWN TO WATER HEATER 1-1/4" (1230 CFH)
1-1/4" (398 CFH)
1-1/4" (1080 CFH)
ENGINEERING FIRM NO. F-9414
EF-1T
HB
42"Ø EXHAUST DUCT FROM PAINT BOOTH FAN. TERMINATE WITH MANUFACTURERS EXHAUST DUCTWORK PACKAGE.
RTU-1T
MAU-4T
1-1/2" (500 CFH)
1-1/2" NG DOWN TO PRESSURE WASHER. JONATHAN R. OLSON
119296
NG
12/19/16 MAU-2T
NG 1-1/4" (1080 CFH)
EF-2T
EF-5T
HC
AREA 'K' AREA 'H'
AREA 'J'
AREA 'L' AREA 'B' AREA 'E'
AREA 'A'
AREA 'F'
AREA 'C'
AREA 'D'
MAIN BUILDING (AREAS A, B, C, D, E & F) IS PART OF A SEPARATE DRAWING SET
FACTORY MOUNTED AND WIRED DISCONNECT
HINGED BASE WITH CURB SEAL. FINISH TO MATCH FAN.
REMOVABLE CAP TO ALLOW CONNECTION OF A PRESSURE MEASURING INSTRUMENT. MINIMUM (10) PIPE DIAMETERS
EXHAUST DUCT
1" MIN
GALVANIZED BAND SADDLE REGULATOR RELIEF VENT. PROVIDE VENT PROTECTOR.
INSULATED FLEXIBLE DUCT
GALVANIZED BAND SUPPORT
UNION OPENING IN ROOF DECK PER MANUFACTURERS RECOMMENDATIONS.
EQPT
DAMPER
DRIP PAN WITH WATERTIGHT SOLDERED OR WELDED SEAMS. MINIMUM DEPTH = 2 INCHES. PROVIDE SUPPORTS AS NECESSARY AND INSTALL ABOVE BOTTOM OF JOISTS.
FILL EXPOSED OPENINGS IN ROOF DECK AROUND CURB WITH FOAM-IN-PLACE INSULATION.
950 Walnut Ridge Drive Hartland, WI 53029 262.369.3535 T 262.369.3592 F
GALVANIZED WIRES
SMART BUILDING SOLUTIONS
ROOF MOUNTED EXHAUST FAN WITH INSULATED CURB. SEE MECHANICAL AND ARCHITECTURAL DETAILS FOR CURB INSTALLATION AND FLASHING.
DESIGN SERVICES
POWER WIRING TO DISCONNECT BY ELECTRICAL CONTRACTOR. DO NOT ROUTE WIRING THROUGH DAMPER.
UNION GAS PRESSURE REGULATOR GAS COCK
1" MIN
GALVANIZED BAND CLAMP
DIRT LEG WITH REMOVABLE CAP TO ALLOW CONNECTION OF A PRESSURE MEASURING INSTRUMENT AND SERVE AS A SEDIMENT TRAP.
INSULATED FLEXIBLE DUCT
NOTES 1. SUPPORT SYSTEM MUST NOT DAMAGE DUCT OR DEFORM DUCT SHAPE. 2. MAXIMUM PERMISSIBLE SAG IS 1/2" PER FOOT OF SPACING BETWEEN SUPPORTS. A CONNECTION TO ANOTHER DUCT OR EQUIPMENT CONSTITUTES A SUPPORT POINT. 3. THE SUPPORT SADDLE MUST COVER ONE-HALF THE CIRCUMFERENCE OF THE OUTSIDE DIAMETER OF THE FLEXIBLE DUCT AND FIT NEATLY AROUND THE LOWER HALF OF THE DUCT'S OUTER CIRCUMFERENCE.
ROOF MOUNTED EXHAUST FAN WITH INSULATED CURB. SEE MECHANICAL AND ARCHITECTURAL DETAILS FOR CURB INSTALLATION AND FLASHING.
POWER WIRING TO DISCONNECT BY ELECTRICAL CONTRACTOR. DO NOT ROUTE WIRING THROUGH DAMPER.
FACTORY MOUNTED AND WIRED DISCONNECT
HINGED BASE WITH CURB SEAL. FINISH TO MATCH FAN.
ANCHOR PIPE TO SUPPORT STAND
DUCT, SEE PLANS FOR SIZE COLUMN
DUCT THRU CURB
10 ' -0
OPENING IN ROOF DECK PER MANUFACTURERS RECOMMENDATIONS.
DAMPER
EXHAUST DUCT
"M AX
2 IM UM
D EN B F "O '-0
FINISHED FLOOR
UNDERGROUND DUCT SP AC ING
TOP DRILLED PIER
DRIP PAN MINIMUM DEPTH = 2 INCHES.
DRILLED PIER SYNTHETIC PIPE SUPPORT. MIFAB C-PORT MODEL C610 OR APPROVED EQUAL.
SEALANT AND BACKER ROD (TYP)
PROVIDE INSULATED ROOF CURB OR KNOCKDOWN CURB WITH ROOF INSULATION. PROVIDE SHIMS/BLOCKING AS NECESSARY FOR LEVEL INSTALLATION.
FLASHING BY ROOFING CONTRACTOR. SEE ARCHITECTURAL DRAWINGS FOR PROPER FLASHING OF ROOF CURB.
INSULATED PLENUM SIDE OF DIFFUSER TO PREVENT CONDENSATION.
SEE TABLE BELOW FOR GREENHECK FASTENING REQUIREMENTS. REFER TO MANUFACTURER'S FASTENING RECOMMENDATIONS FOR OTHER EQUIPMENT.
OPERATOR LINKAGE AT CENTER OF BLADES
GALVANIZED SHEET METAL STRAP HANGER
INSECT SCREEN
INSULATED FLEXIBLE DUCTWORK (5'-0" MAX LENGTH)
CONTINUOUS INTEGRAL BLADE HINGE
SUPPLY AIR BRANCH DUCT VOLUME DAMPER WITH LOCKABLE HAND QUADRANT
ROOF CURB SUPPORT
ALUMINUM BLADE BRACKET
ENGINEERING FIRM NO. F-9414
ALUMINUM ADJUSTABLE BLADE
STEEL DECK ANCHORING OF ROOF CURB TO ROOF DECK
060 - 141
GREENHECK CURB CAP SIZE INCHES 17x17 - 22x22
MINIMUM FASTENERS PER SIDE (3) 1/4"
MINIMUM FASTENERS TOTAL (12) 1/4"
GB/CUBE
161 - 300
26x26 - 40x40
(3) 1/4"
(12) 1/4"
R/RB
18 - 24
14x14 - 30x30
(3) 5/16"
(12) 5/16"
R/RB
30 - 36
31x31 - 51x51
(3) 5/16"
(12) 5/16"
R/RB
42
52x52 - 72x72
(4) 5/16"
(16) 5/16"
GREENHECK FAN MODEL
GREENHECK FAN SIZE
GB/CUBE
OPERATOR LINKAGE CONNECTING ARM SUPPLY DUCT MAIN SHEET METAL SHIELD 2 RADIUS ELBOW
CEILING NOTES 1. CURB SUPPORT FRAMING PROVIDED BY STRUCTURAL CONTRACTOR. COORDINATE LOCATION OF UNIT PRIOR TO INSTALLATION.
SUPPLY DIFFUSER LIGHT FIXTURE (FOR ILLUSTRATION ONLY)
3.
INSTALL ONE FASTENER AT EACH CORNER & IN CENTER OF EACH SIDE. ADD ADDITIONAL FASTENERS AS NECESSARY TO MAINTAIN A MAXIMUM OF 8" ON CENTER.
16 GAUGE WALL SLEEVE
FOLLOW MANUFACTURER'S INSTALLATION REQUIREMENTS FOR EQUIPMENT NOT SHOWN IN CHART.
WEATHERHOOD WITH BIRDSCREEN FOR OA INTAKE
MAKE-UP AIR UNIT
ACCESS PANEL (ALTERNATE LOCATION)
TURNING VANES PER SMACNA RECOMMENDATIONS
W
2.
R= 1.5 x W
HVAC CONTRACTOR FABRICATED PLENUM BOX WITH 12" THICK, BLACK ACCOUSTICAL LINING. PROVIDE CONNECTION SIZED PER PLAN.
℄
INSULATE DECK FOR SOUND ATTENUATION. MATCH SURROUND ROOF INSULATION.
ACCESS PANEL W
VOLUME DAMPER WITH LOCKABLE HAND QUADRANT.
INSULATE DECK OPENINGS FOR SOUND ATTENUATION. CURB
INSULATED FLEXIBLE DUCTWORK (5'-0" MAX LENGTH)
EXHAUST/RETURN DUCT
RADIUS ELBOW
MITERED ELBOW 30° MAX
60° MAX
FLEXIBLE CONNECTION
CONCENTRIC TRANSITION (INCLUDING SQUARE-TO-ROUND)
ECCENTRIC TRANSITION (INCLUDING SQUARE-TO-ROUND)
ROUND BRANCH SPIN-IN FITTING
LAY-IN CEILING
45 °
L=W/4 W
NOTES 1. CURB SUPPORT FRAMING PROVIDED BY STRUCTURAL CONTRACTOR. COORDINATE LOCATION OF UNIT PRIOR TO INSTALLATION.
RECTANGULAR BRANCH
RECTANGULAR MAIN W/ BRANCH CONNECTIONS
COORDINATE WITH CEILING CONTRACTOR. IF GRILLE IS SMALLER THAN CEILING GRID SPACING, IT SHALL BE CENTERED ON THE CEILING TILE AND GRILLE SHALL BE PROVIDED WITH SURFACE MOUNT BORDER. CEILING GRID ASSEMBLY AND TILE WORK SHALL BE PERFORMED BY CEILING CONTRACTOR.
JONATHAN R. OLSON
119296
12/19/16
HEATING PERFORMANCE DATA
ELECTRICAL DATA
MAXIMUM SUPPLY-AIR CFM
MINIMUM SUPPLY-AIR CFM
OUTSIDE-AIR CFM
ESP INCHES WC
MOTOR HP
NOMINAL TONS
TOTAL CAPACITY MBH
SENSIBLE CAPACITY MBH
EADB DEG-F
EAWB DEG-F
LADB DEG-F
LAWB DEG-F
(S)EER
IEER
STAGES
TYPE
INPUT MBH
OUTPUT MBH
EAT DEG-F
LAT DEG-F
STAGES
VOLTS
PHASE
HERTZ
MCA
MOP
WEIGHT LBS
REFERENCE NOTES
GUARD HOUSE ROOF
1,200
1,200
250
0.75
0.75
3
36.0
27.0
80
67
60
58
15.0
-
1
ELECTRIC
12.0
-
60
91
-
208
3
60
40.0
45.0
700
1, 2, 3, 4, 5, 6, 7, 9, 10, 11, 13
TRUCK MAINT. GARAGE ROOF
2,430
2,430
650
1.00
3
7.5
88
64
80
67
57
56
12.5
-
2
NATURAL GAS
150
120
60
105
2
460
3
60
19.5
25.0
1,500
1, 3, 4, 5, 6, 7, 9, 10, 13
TAG
BASIS OF DESIGN
TYPE
LOCATION
RTU-1G
TRANE THC037
UNITARY COOLING ROOFTOP
RTU-1T
TRANE YHC092
UNITARY COOLING ROOFTOP
SCHEDULE DEFINITIONS AFUE = ANNUAL FUEL UTILIZATION EFFICIENCY BTUH = BRITISH THERMAL UNITS PER HOUR CFM = CUBIC FEET PER MINUTE dBA = A-WEIGHTED SOUND PRESSURE DECIBELS
COOLING PERFORMANCE DATA
DEG-F = DEGREES FAHRENHEIT EADB = ENTERING AIR DRY-BULB TEMPERATURE EAWB = ENTERING AIR WET-BULB TEMPERATURE EAT = ENTERING AIR TEMPERATURE
EER = ENERGY EFFICIENCY RATIO ESP = EXTERNAL STATIC PRESSURE IEER - INTEGRATED ENERGY EFFICIENCY RATIO LADB = LEAVING AIR DRY-BULB TEMPERATURE
LAWB = LEAVING AIR WET-BULB TEMPERATURE LAT = LEAVING AIR TEMPERATURE LBS = POUNDS MBH = BTUH x 1000
MCA = MINIMUM CIRCUIT AMPACITY MOP = MAXIMUM OVERCURRENT PROTECTION SEER = SEASONAL ENERGY EFFICIENCY RATIO VAV = VARIABLE AIR VOLUME
VVT = VARIABLE VOLUME AND TEMPERATURE
SCHEDULE GENERAL NOTES 1. PROVIDE THE PRODUCT INDICATED OR A COMPARABLE PRODUCT BY ONE OF THE MANUFACTURERS LISTED IN SPECIFICATION SECTIONS 237416 AND 237417. 2. UNIT WEIGHT IS APPROXIMATE AND INCLUDES ACCESSORIES. SCHEDULE REFERENCE NOTES 1. PROVIDE UNIT WITH FACTORY-MOUNTED DISCONNECT AND THROUGH-THE-BASE ELECTRICAL CONNECTIONS. 2. PROVIDE UNIT WITH POWERED CONVENIENCE OUTLET. POWER SHALL BE UNAFFECTED BY DISCONNECT POSITION. 3. PROVIDE UNIT WITH HINGED ACCESS PANELS. 4. PROVIDE UNIT WITH 14-INCH ROOF CURB. 5. PROVIDE UNIT WITH HAIL GUARD FOR CONDENSER COIL.
6. PROVIDE UNIT WITH PLEATED, DISPOSABLE MERV-8 FILTERS. 7. PROVIDE UNIT WITH 0-100% COMPARATIVE DRY-BULB ECONOMIZER WITH MODULATING OUTDOOR-AIR DAMPER. 8. PROVIDE UNIT WITH POWERED EXHAUST RELIEF. 9. PROVIDE UNIT WITH FAN STATUS AND DIRTY FILTER SWITCHES. 10. PROVIDE UNIT WITH STAINLESS-STEEL DRAIN PAN.
950 Walnut Ridge Drive Hartland, WI 53029 262.369.3535 T 262.369.3592 F
AIR-HANDLING DATA
SMART BUILDING SOLUTIONS
DESIGN SERVICES
PACKAGED ROOFTOP UNIT SCHEDULE
11. PROVIDE UNIT WITH HUMIDIMIZER HOT-GAS REHEAT (HGRH) DEHUMIDIFICATION CONTROL. 12. SMOKE DETECTORS TO BE FURNISHED AND WIRED BY ELECTRICAL CONTRACTOR. INSTALL DETECTOR IN DUCTWORK AND PROVIDE CONTROL WIRING AS NECESSARY TO DISABLE UNIT. 13. PROVIDE UNIT WITH COMMUNICATION INTERFACE FOR BUILDING AUTOMATION SYSTEM.
MAKE-UP AIR UNIT SCHEDULE AIR-HANDLING DATA
COOLING PERFORMANCE DATA
REHEAT PERFORMANCE DATA
HEATING PERFORMANCE DATA
ELECTRICAL DATA
CURB DATA WEIGHT LBS
REFERENCE NOTES
14
7,500
1, 2, 3, 4, 5, 6
-
14
7,500
1, 2, 3, 4, 5, 6
60.0
GREENHECK
12
3,000
1, 2, 3, 5, 8
15.0
GREENHECK
12
1,100
1, 2, 3, 5, 7, 8
MAXIMUM SUPPLY-AIR CFM
MINIMUM SUPPLY-AIR CFM
ESP INCHES WC
MOTOR HP
TYPE
TOTAL CAPACITY MBH
SENSIBLE CAPACITY MBH
EADB DEG-F
EAWB DEG-F
LADB DEG-F
LAWB DEG-F
EER
TYPE
CAPACITY MBH
TYPE
INPUT MBH
OUTPUT MBH
AFUE %
EAT DEG-F
TEMP. RISE DEG-F
STAGES
VOLTS
PHASE
HERTZ
MCA
MOP
BASIS OF DESIGN
HEIGHT INCHES
DX COOLED INDIRECT GAS-FIRED
12,000
12,000
0.75
(2) 5
DX
735
478
99
78
60
60
-
HOT-GAS
128
NG
1080
864
-
30
95
10:1
480
3
60
140
150
-
AAON RN-070
DX COOLED INDIRECT GAS-FIRED
12,000
12,000
0.75
(2) 5
DX
735
478
99
78
60
60
-
HOT-GAS
128
NG
1080
864
-
30
95
10:1
480
3
60
140
150
MAU-3T
GREENHECK DGX-125-H35
DIRECT-FIRED GAS
21,435
21,435
0.5
20
-
-
-
-
-
-
-
-
-
-
DIRECT
1,132
1,041
30
45
30:1
480
3
60
35.0
MAU-4T
GREENHECK DGX-110-H12
DIRECT-FIRED GAS
2,800
2,800
0.5
2
-
-
-
-
-
-
-
-
-
-
DIRECT
131
121
30
40
30:1
480
3
60
4.6
TAG
BASIS OF DESIGN
DESCRIPTION
MAU-1T
AAON RN-070
MAU-2T
SCHEDULE DEFINITIONS AFUE = ANNUAL FUEL UTILIZATION EFFICIENCY BTUH = BRITISH THERMAL UNITS PER HOUR CFM = CUBIC FEET PER MINUTE dBA = A-WEIGHTED SOUND PRESSURE DECIBELS
DEG-F = DEGREES FAHRENHEIT EADB = ENTERING AIR DRY-BULB TEMPERATURE EAWB = ENTERING AIR WET-BULB TEMPERATURE EAT = ENTERING AIR TEMPERATURE
EER = ENERGY EFFICIENCY RATIO ESP = EXTERNAL STATIC PRESSURE HGRH = HOT-GAS REHEAT HP = HORSEPOWER
IEER = INTEGRATED ENERGY EFFICIENCY RATIO LADB = LEAVING AIR DRY-BULB TEMPERATURE LAWB = LEAVING AIR WET-BULB TEMPERATURE LAT = LEAVING AIR TEMPERATURE
-
LBS = POUNDS MBH = BTUH x 1000 MCA = MINIMUM CIRCUIT AMPACITY MOP = MAXIMUM OVERCURRENT PROTECTION
SCHEDULE GENERAL NOTES 1. PROVIDE THE PRODUCT INDICATED OR A COMPARABLE PRODUCT BY ONE OF THE MANUFACTURERS LISTED IN SPECIFICATION SECTION 237423 AND 237433. 2. UNIT FURNISHED WITH FACTORY-MOUNTED AND WIRED DISCONNECT. INTERNALLY MOUNTED CONTROL CENTER INCLUDES MOTOR STARTERS, 24 VAC CONTROL TRANSFORMERS AND CONTROL CIRCUIT FUSING. 3. UNIT WEIGHT IS APPROXIMATE AND INCLUDES ACCESSORIES. SCHEDULE REFERENCE NOTES 1. PROVIDE UNIT WITH LOW-LEAKAGE, MOTORIZED OUTDOOR-AIR DAMPER. 2. PROVIDE UNIT WITH 2" PLEATED, DISPOSABLE MERV-8 FILTERS AND DIRTY FILTER SENSORS. 3. PROVIDE UNIT WITH BUILDING AUTOMATION SYSTEM INTERFACING. 4. PROVIDE UNIT WITH HAIL GUARDS. 5. PROVIDE UNIT WITH BAKED ENAMEL FINISH. COLOR TO BE DETERMINED DURING SUBMITTAL PROCESS. 6. INTAKE WEATHERHOOD WITH BIRDSCREEN.
7. PROVIDE MANUFACTURER'S THREE DIFFUSER. 8. PROVIDE WEATHERHOOD WITH ALUMINUM MESH FILTERS.
POWER VENTILATOR SCHEDULE MOTOR DATA
ELECTRICAL DATA
ELECTRIC UNIT HEATER SCHEDULE
CURB INFORMATION
DAMPER INFORMATION SONES
TAG
BASIS OF DESIGN
TYPE
AREA SERVED
AIRFLOW CFM
THROW FT
MOUNTING HEIGHT FT
CAPACITY KW
STAGES
VOLTS
PHASE
HERTZ
FLA
WEIGHT LBS
REFERENCE NOTES
-
-
300
2
EUH-1FP
MARKEL UH SERIES
HORIZONTAL UNIT HEATER
K101
800
45
7
15.0
1
480
3
60
18.0
54
1, 2
30x30
66
15.6
300
1, 5
120V
30x30
66
15.6
300
1, 5
GREENHECK WD-100
GRAVITY
-
73
22
200
1, 5
18
GREENHECK WD-100
GRAVITY
18x18
57
7.9
150
1, 3, 5
-
18
GREENHECK WD-100
GRAVITY
12x12
59
11
100
1, 3, 5
GREENHECK GPI
-
18
GREENHECK WD-100
GRAVITY
12x12
57
9
100
1, 3, 5
60
GREENHECK GPI
22X22
18
GREENHECK WD-100
GRAVITY
16X16
65
13.1
150
1, 5
1
60
GREENHECK GPI
17x17
18
GREENHECK WD-100
GRAVITY
10x10
54
7.1
75
1, 3, 5
3
60
-
-
-
GREENHECK VCD-23
120V
44x44
70
18
650
2, 6, 7, 8, 9
TYPE
AIRFLOW CFM
ESP INCHES WC
DRIVE
BHP
HP
RPM
VOLTS
PHASE
HERTZ
BASIS OF DESIGN
SIZE INCHES
HEIGHT INCHES
BASIS OF DESIGN
ACTUATOR
SIZE INCHES
dBA
EF-1T
CARMON CMB-25
UTILITY SET
3,600
4.00
BELT
-
7 1/2
-
480
3
60
N/A
-
-
INTEGRAL
-
-
EF-2T
GREENHECK GB-300
DOWNBLAST CENTRIFUGAL
8,820
0.50
BELT
-
2
630
480
3
60
GREENHECK GPI
-
18
GREENHECK VCD-23
120V
EF-3T
GREENHECK GB-300
DOWNBLAST CENTRIFUGAL
8,820
0.50
BELT
-
2
630
480
3
60
GREENHECK GPI
-
18
GREENHECK VCD-23
EF-4T
GREENHECK CUE-200
UPBLAST CENTRIFUGAL
5,400
0.50
DIRECT
-
2
1140
460
3
60
GREENHECK GPI
-
18
EF-5T
GREENHECK GB-180
DOWNBLAST CENTRIFUGAL
2,575
0.25
BELT
-
1/2
780
208
3
60
GREENHECK GPI
-
EF-6T
GREENHECK G-098-VG
DOWNBLAST CENTRIFUGAL
565
0.80
DIRECT
-
1/4
1660
120
1
60
GREENHECK GPI
EF-7T
GREENHECK G-099-VG
DOWNBLAST CENTRIFUGAL
550
0.75
DIRECT
-
1/4
1405
120
1
60
EF-8T
GREENHECK CUBE-161
UPBLAST CENTRIFUGAL
2,500
0.50
BELT
-
3/4
1598
480
3
EF-1G
GREENHECK G-085-VG
DOWNBLAST CENTRIFUGAL
250
0.50
DIRECT
-
1/10
1500
120
EF-2FP
GREENHECK SBE-2L-42
THRU WALL PROPELLER
14,000
0.25
BELT
-
1 1/2
440
480
ENCL = ENCLOSURE ESP = EXTERNAL STATIC PRESSURE EXP = EXPLOSTION PROOF
TENV = TOTALLY ENCLOSED, NOT VENTILATED VDC = VOLTAGE DIRECT CURRENT WC = WATER COLUMN
ODP = OPEN DRIP PROOF RPM = REVOLUTIONS PER MINUTE TEFC = TOTALLY ENCLOSED, FAN-COOLED
SCHEDULE GENERAL NOTES 1. PROVIDE PRODUCT INDICATED OR A COMPARABLE PRODUCT BY ONE OF THE MANUFACTURERS LISTED IN SPECIFICATION SECTION 233423. 2. ALL FANS SHALL HAVE AMCA-CERTIFIED PERFORMANCE RATINGS AND SHALL BEAR THE AMCA-CERTIFIED RATINGS SEAL. 3. POWER VENTILATORS SHALL COMPY WITH UL 705. SCHEDULE REFERENCE NOTES 1. PROVIDE UNIT WITH FACTORY-MOUNTED AND WIRED, NEMA-1 TOGGLE DISCONNECT. 2. PROVIDE UNIT WITH FACTORY-MOUNTED AND WIRED, NEMA-3R TOGGLE DISCONNECT. 3. PROVIDE MOTOR WITH SPEED CONTROL DIAL ON MOTOR. 4. PROVIDE UNIT WITH 0-10 VDC SIGNAL SPEED CONTROL. 5. PROVIDE UNIT WITH HINGED BASE AND CURB SEAL.
4. FAN WEIGHTS ARE APPROXIMATE AND INCLUDE ACCESSORIES. 5. ALL SINGLE-PHASE FAN MOTORS SHALL INCLUDE THERMAL OVERLOAD PROTECTION. 6. ALL THREE-PHASE FAN MOTORS SHALL BE PREMIUM EFFICIENCY AND INVERTER-DUTY RATED.
6. PROVIDE FLUSH EXTERIOR WALL HOUSING WITH OSHA GUARD. 7. PROVIDE UNIT WITH CLOSURE ANGLES. 8. PROVIDE 45 DEGREE WEATHERHOOD WITH BIRDSCREEN. 9. PROVIDE PERMATECTOR COATING FOR FAN, WALL HOUSING, GUARD, DAMPER, AND WEATHERHOOD.
NOMINAL DIMENSIONS
AIRFLOW CFM
FREE-AREA VELOCITY FPM
PRESSURE DROP INCHES WC
NET FREE AREA SQ FT
ACTUATOR
TAG
BASIS-OF-DESIGN
TYPE
LVR-1T
GREENHECK ECD-601
COMBINATION INTAKE LOUVER/DAMPER
H114
54
31
6
1
2,575
500
0.04
5.20
NEMA 3R
1
CLOSED
120
1
LVR-1FP
GREENHECK ECD-601
COMBINATION INTAKE LOUVER/DAMPER
K101
96
88
6
2
14,700
485
0.03
30.30
NEMA 3R
2
OPEN
120
1
LENGTH INCHES
HEIGHT INCHES
DEPTH INCHES
LOUVER SECTIONS
QUANTITY
TYPE
SCHEDULE GENERAL NOTES 1. ALL LOUVERS SHALL HAVE AMCA-CERTIFIED PERFORMANCE RATINGS AND SHALL BEAR THE AMCA-CERTIFIED RATINGS SEAL. SCHEDULE REFERENCE NOTES 1. PROVIDE UNIT WITH INTERNAL INSECT & BIRDSCREEN. 2. PROVIDE UNIT WITH 2-INCH FLANGED FRAME. 3. FINISH COLOR TO BE CUSTOM COLOR SELECTED BY ARCHITECT DURING SUBMITTAL PHASE.
ELECTRIC WALL AND CEILING HEATER SCHEDULE TAG
BASIS OF DESIGN
TYPE
LOCATION
AIRFLOW CFM
EWH-1T
MARKEL 3320 SERIES
WALL HEATER
H101
175
COIL kW 2.3
ENCLOSURE
ELECTRICAL DATA
LENGTH INCHES
HEIGHT INCHES
MOUNTING
VOLTS
PHASE
HERTZ
FLA
REFERENCE NOTES
16
21
SURFACE
277
1
60
10.8
1, 2
SCHEDULE GENERAL NOTES 1. PROVIDE THE PRODUCT INDICATED OR A COMPARABLE PRODUCT BY ONE OF THE MANUFACTURERS LISTED IN SPECIFICATION SECTION 238239. 2. COLOR TO BE SELECTED FROM MANUFACTURER'S STANDARD COLORS BY ARCHITECT DURING SUBMITTAL PROCESS. SCHEDULE REFERENCE NOTES 1. PROVIDE UNIT WITH FACTORY-MOUNTED AND WIRED DISCONNECT. 2. PROVIDE UNIT WITH INTEGRAL, VANDAL-PROOF, DOUBLE-POLE THERMOSTAT.
SCHEDULE GENERAL NOTES 1. SEE SPECIFICATION SECTION 238238. 2. MOUNTING HEIGHTS ARE MANUFACTURER'S RECOMMENDED MAXIMUM MOUNTING HEIGHT. COORDINATE/ADJUST MOUNTING HEIGHTS AS NECESSARY IN FIELD. 3. SUPPORT UNITS FROM BUILDING STRUCTURE. DO NOT SUPPORT UNITS FROM INSULATED METAL PANELS. PROVIDE ALL MOUNTING HARDWARE AS NECESSARY. SCHEDULE REFERENCE NOTES 1. PROVIDE UNIT WITH FACTORY-MOUNTED AND WIRED DISCONNECT. 2. PROVIDE UNIT WITH REMOTE THERMOSTAT, TRANSFORMER, AND HEAT PURGE FAN DELAY SWITCH.
CEILING VENTILATOR SCHEDULE ELECTRICAL DATA
TAG
BASIS-OF-DESIGN
TYPE
LOCATION
AIRFLOW CFM
ESP INCHES WC
WATTS
VOLTS
PHASE
HERTZ
EF-1FP
GREENHECK SP-A700
CEILING EXHAUST FAN
K101
700
0.25
350
120
1
60
FAIL POSITION
VOLTS
PHASE
HERTZ
FINISH
REFERENCE NOTES
60
KYNAR 70% THREE-COAT
1, 2, 3
60
KYNAR 70% THREE-COAT
1, 2, 3
SONES
WEIGHT LBS
REFERENCE NOTES
5
50
1, 2, 3, 4, 5
SCHEDULE GENERAL NOTES 1. PROVIDE PRODUCT INDICATED OR A COMPARABLE PRODUCT BY ONE OF THE MANUFACTURERS LISTED IN SPECIFICATION SECTION 233423. 2. ALL FANS SHALL HAVE AMCA-CERTIFIED PERFORMANCE RATINGS AND SHALL BEAR THE AMCA-CERTIFIED RATINGS SEAL. 3. VENTILATORS SHALL COMPLY WITH UL 507. 4. FAN WEIGHTS ARE APPROXIMATE AND INCLUDE ACCESSORIES.
ENGINEERING FIRM NO. F-9414
SCHEDULE REFERENCE NOTES 1. UNIT FURNISHED WITH INTERNAL DISCONNECT HARNESS PLUG. EXTERNAL DISCONNECT SWITCH PROVIDED BY ELECTRICAL CONTRACTOR. 2. PROVIDE UNIT WITH FACTORY-MOUNTED AND WIRED SPEED CONTROL. 3. PROVIDE UNIT WITH ISOLATION KIT. 4. PROVIDE UNIT WITH ALUMINUM GRILLE WITH WHITE ENAMEL FINISH. 5. PROVIDE UNIT WITH WALL OUTLET EXHAUST TERMINAL.
JONATHAN R. OLSON
TAG
BASIS OF DESIGN
TYPE
MOUNTING
PANEL SIZE INCHES
NECK SIZE INCHES
FINISH
REFERENCE NOTES
CD-1
TITUS OMNI
SQUARE PLAQUE DIFFUSER
LAY-IN
24 x 24
-
WHITE
1
CD-2
TITUS OMNI
SQUARE PLAQUE DIFFUSER
SURFACE
24 x 24
-
WHITE
1
CD-3
TITUS TRITEC
LOW VELICTY PERFORATED DIFFUSER (TWO-WAY THROW)
LAY-IN
24 x 24
-
WHITE
1
CD-4
TITUS TRITEC
LOW VELICTY PERFORATED DIFFUSER (TWO-WAY THROW)
LAY-IN
24 x 48
-
WHITE
1
CG-1
TITUS 50FF
FILTERED, EGG CRATE RETURN GRILLE
LAY-IN
24 x 24
22 x 22
WHITE
CG-2
TITUS 50FF
FILTERED, EGG CRATE RETURN GRILLE
LAY-IN
24 x 12
22 x 10
WHITE
CG-3
TITUS 50F
EGG CRATE RETURN GRILLE
LAY-IN
24 x 24
22 x 22
WHITE
CG-4
TITUS 50F
EGG CRATE RETURN GRILLE
LAY-IN
24 x 12
22 x 10
WHITE
CG-5
TITUS 50F
EGG CRATE RETURN GRILLE
SURFACE
24 x 12
22 x 10
WHITE
CG-6
TITUS 50F
EGG CRATE RETURN GRILLE
LAY-IN
48 x 24
46 x 22
WHITE
LD-1
TITUS TBDI-80-24-2HP-8-1.5
LINEAR 2-SLOT DIFFUSER PLENUM
LAY-IN
-
-
BLACK
4, 5
LD-2
TITUS TBDI-80-48-4HP-8-.75
LINEAR 4-SLOT DIFFUSER PLENUM
LAY-IN
-
-
BLACK
4, 5
RG-1
TITUS 350RL
SINGLE DEFLECTION RETURN GRILLE
SURFACE
-
-
WHITE
SG/R-1
TITUS 122RL
DOUBLE-DEFLECTION SUPPLY GRILLE
SURFACE
-
-
WHITE
1
SG/R-2
TITUS S300FL
DOUBLE-DEFLECTION SUPPLY GRILLE
SURFACE
-
-
PRIMER
3
SCHEDULE GENERAL NOTES 1. PROVIDE THE PRODUCT INDICATED OR A COMPARABLE PRODUCT BY ONE OF THE MANUFACTURERS LISTED IN SPECIFICATIONSECTION 233713. 2. SCHEDULE IS TYPICAL FOR BOTH DISTRIBUTION FACILITY AND TRUCK MAINTENANCE FACILITY. ALL DEVICES MAY NOT BE USED IN BOTH DRAWING SETS. SCHEDULE REFERENCE NOTES 1. NECK SIZE TO MATCH BRANCH DUCT SIZE AS INDICATED ON PLANS. 2. PROVIDE UNIT WITH OPPOSED BLADE DAMPER FOR AIR-BALANCING. 3. PROVIDE UNIT WITH AIR SCOOP DAMPER. 4. PROVIDE CROSS NOTCH AS NECESSARY. 5. COORDINATE CEILING TRIM TEES WITH GENERAL CONTRACTOR.
119296
12/19/16
DIFFUSER, GRILLE, AND REGISTER SCHEDULE
LOUVER SCHEDULE LOCATION
ELECTRICAL DATA
REFERENCE NOTES
BASIS OF DESIGN
SCHEDULE DEFINITIONS BHP = BRAKE HORSE POWER CFM = CUBIC FEET PER MINUTE dBA = A-WEIGHTED SOUND PRESSURE DECIBELS
HEATING DATA
WEIGHT LBS
TAG
HVAC Characteristics Information on the characteristics of the heating, ventilation, and air conditioning (HVAC) system(s) in the entire BASE building including types of ventilation, equipment configurations, and operation and maintenance issues was acquired by examining the building plans, conducting a building walk-through, and speaking with the building owner, manager, and/or operator. This information was collected using standard forms available in the appendices of the protocol during the building preliminary visit, and verified by the field team during the study week.
Exhibit Contents 1. Type of Ventilation
2. Cooling System Equipment - Primary and Secondary
3. Heating System Equipment - Primary and Secondary
4. Heating and Cooling Profiles - Number of Space Conditioning Days Per Week and Weekend
5. Heating and Cooling Profiles - Number of Space Conditioning and Ventilation Hours Per Day 6. Primary HVAC Control Implementation
7. Primary HVAC Control Response Strategy
8. Particle Filtration Systems - Frequency of Maintenance Actions for Different Configurations 9. Frequency of Inspection for HVAC Components 10. Frequency of Cleaning for HVAC Components
11. Frequency of Maintenance Actions for Fan Coil Units and Terminal Units 12. Control System - Frequency of Inspection and Sensor Calibration 13. Frequency of Testing and Balancing
BASE Buildings HVAC Characteristics: Type of Ventilation
Type of Ventilation Mechanical Natural Total Number of Buildings Reporting
Number of Buildings Reporting1 98 3 100
1
Column total adds up to greater than the total number of buildings reporting as one building used a combination of mechanical ventilation and natural ventilation (the building's study space employed natural ventilation, while mechanical ventilation was used in another portion of the building).
Variable Descriptions: Type of Ventilation defines the primary means of providing outdoor air to the building. The following categories apply: Mechanical ventilation employs a powered system to bring outdoor air into the building. Natural ventilation operates without external power, employing pressure differences caused by wind and temperature to induce airflow through the building, and includes any un-powered ventilation approach such as operable windows, ventilation shafts, intentional ventilation openings in walls, and envelope leakage. A building with a natural ventilation system may still have powered exhaust systems serving certain areas in the building.
BHC-1
BASE Buildings HVAC Characteristics: Cooling System Equipment - Primary and Secondary
Cooling System Equipment Chillers Packaged AC Units Heat Pump Ducted Air Distribution Fan Coil Units Individual Room AC Central System With Cooling Coils Split AC System Makeup Air Units Total Number of Buildings Reporting
Number of Buildings Reporting Primary Secondary Cooling System 1 Cooling System 1 72 0 9 23 2 10 94 2 6 20 4 68 80 1 9 21 16 13 99 99
Notes: Based on those buildings in the dataset that had cooling systems (n=99). Values within each column add up to greater than 99 as some buildings had more than one primary or secondary cooling system equipment entered into the database. 1
Variable Descriptions: Primary Cooling System is the equipment that provides cooling to the majority of the building. Secondary Cooling System is the equipment that provides cooling to the remaining areas of the building or serves as back up to the primary system. The following cooling system categories apply: Chillers are evaporators that chill water or other liquids and provide a chilled liquid to a central air handling system. Packaged AC Units are factory assembled air conditioning units equipped with the ability to heat or cool. Cooling is provided using a direct expansion refrigeration cycle. Heat Pumps are factory assembled units with the capacity to heat and cool. A single system can be used to condition an entire building or individual zones. Heat pump types include air-to-air, water-to-air, air-to-water, and water-to-water. Ventilation air may be supplied by a central system to the individual units through a system of ductwork or the individual units may provide ventilation. Ducted Air Distribution a network of ducts to carry the air to the rooms to be heated or cooled. Fan-Coil Units consist of a finned-tube coil supplied with hot or chilled water from a central source and a fan that circulates room air over the coil. These units are sometimes provided with an outdoor air connection through the exterior wall. Individual Room AC is a unit that is located in and provides cooling for an individual room. Central System with Cooling Coils are air conditioning systems that are centrally located in the building, or on the building roof. These units may provide cooling using a chilled water cooling coil. Split AC System is a system used for cooling where the condenser and compressor are in one package located outdoors, and the fan and evaporator coil are located inside the building. Makeup Air Units are fan units that solely provide outdoor air to the building.
BHC-3
BASE Buildings HVAC Characteristics: Heating System Equipment - Primary and Secondary
Heating System Equipment Steam or Hot Water Boiler Central System With Heating Coils Reheat Coils in Air Distribution System Packaged Units Forced Air Furnace Heat Pump Ducted Air Distribution Fan Coil Units Individual Space Heating Fin-Tube Radiators Electric Baseboard Makeup Air Units Total Number of Buildings Reporting
Number of Buildings Reporting Secondary Primary 1 Heating System 1 Heating System 60 1 49 9 41 19 4 11 2 2 2 10 81 6 8 25 1 7 26 17 1 20 9 8 100 100
Notes: Based on those buildings in the dataset that had heating systems (n=100). Values within each column add up to greater than 100 as some buildings had more than one primary or secondary heating system equipment entered into the database. 1
Variable Descriptions: Primary Heating System is the equipment that provides heating to the majority of the building. Secondary Heating System is the equipment that provides heating to the remaining areas of the building or serves as back up to the primary system. The following heating system categories apply: Steam or Hot Water Boilers produce hot water or steam which is delivered through pipes to space heating equipment. Key components to a boiler are the combustion chamber, burner, and the heat exchanger. Central System with Heating Coils are air conditioning systems that are centrally located in the building, or on the building roof. These units may provide heating using a hot water or steam heating coils. Reheat Coils in Air Distribution System are heating coils that are located in the ductwork near the distribution point to control the temperature in an individual zone. Packaged Units are factory assembled air conditioning units equipped with the ability to heat or cool. Heating is generally provided using gas fired heat exchanger or electric resistance heating coils. Forced Air Furnace heats by delivering warmed air to the spaces in a building. Components of the furnace are a heat exchanger, fuel burner, and air blower. Heat Pumps are factory assembled units with the capacity to heat and cool. A single system can be used to condition an entire building or individual zones. Heat pump types include air-to-air, water-to-air, air-to-water, and water-to-water. Ventilation air may be supplied by a central system to the individual units through a system of ductwork or the individual units may provide ventilation. Ducted Air Distribution a network of ducts to carry the air to the rooms to be heated or cooled. Fan Coil Units consist of a finned-tube coil supplied with hot or chilled water from a central source and a fan that circulates room air over the coil. These units are sometimes provided with an outdoor air connection through the exterior wall. Temperature controllers in the unit meter the chilled or hot water to the coil. Individual Space Heating is a unit that is located in and provides heat for the room where it is located. Fin-Tube Radiators are hydronic terminal units equipped with metal fins that dissipate the heat from the hot water in the piping through natural convection. Electric Baseboard are electric terminal units that heat by electrical resistance and natural convection. Makeup Air Units are fan units that solely provide outdoor air to the building.
BHC-4
BASE Buildings HVAC Characteristics: Heating and Cooling Profiles - Number of Space Conditioning and Ventilation Days Per Week and Weekend
Number of Buildings Reporting Number of Space Number of Space Number of Space Conditioning Weekdays Conditioning Weekend Ventilation Weekdays Per Week 2 Per Week Days Per Week 1 0 17 2 0 23 0 0 59 0 0 0 0 0 0 0 100 0 97 100 99 99
Days Per Week None One Two Three Four Five Total Number of Buildings Reporting Notes: 1 Number of space conditioning days per weekend was not reported for one building. 2 Number of ventilation days weekdays per week was not reported for one building. 3 Number of ventilation days per weekend was not reported for two buildings.
Number of Space Ventilation Weekend Days Per Week 3 20 24 54 0 0 0 98
Variable Descriptions: Number of Space Conditioning Weekdays Per Week refers to the number of weekdays per week that the building's space conditioning systems are reported to be operating. Number of Space Conditioning Weekend Days Per Week refers to the number of days per weekend that the building's space conditioning systems are reported to be operating. Number of Space Ventilation Weekdays Per Week refers to the number of weekdays per week that the building's ventilation systems are reported to be operating. Number of Space Ventilation Weekend Days Per Week refers to the number of days per weekend that the building's ventilation systems are reported to be operating.
BHC-5
BASE Buildings HVAC Characteristics: Heating and Cooling Profiles - Number of Space Conditioning and Ventilation Hours Per Day
Number of Buildings Reporting Mean (Arithmetic) Standard Deviation Minimum 10th Percentile 25th Percentile 50th Percentile 75th Percentile 90th Percentile Maximum
Number of Space Conditioning Hours Per Weekday 100 17 5 7 11 12 16 24 24 24
Number of Space Conditioning Hours Per Weekend Day 1 98 13 9 0 0 5 12 24 24 24
Number of Ventilation Hours Per Weekday 2 99 17 6 0 11 12 16 24 24 24
Number of Ventilation Hours Per Weekend Day3 97 12 9 0 0 5 9 24 24 24
Notes: Two buildings did not report the number of space conditioning hours per weekend day. 2 One building did not report the number of ventilation hours per weekday. 3 Two buildings did not report the number of ventilation hours per weekend day. 1
Variable Descriptions: Number of Space Conditioning Hours Per Weekday refers to the number of hours per weekday that the building's space conditioning systems are reported to be operating. Number of Space Conditioning Hours Per Weekend Day refers to the number of hours per weekend day that the building's space conditioning systems are reported to be operating. Number of Ventilation Hours Per Weekday refers to the number of hours per weekday that the building's ventilation systems are reported to be operating. Number of Ventilation Hours Per Weekend Day refers to the number of hours per weekend day that the building's ventilation systems are reported to be operating.
BHC-6
BASE Buildings HVAC Characteristics: Primary HVAC Control Implementation
Primary HVAC Control Implementation Pneumatic Low Voltage Analog Electric Direct Digital Pneumatic / Low Voltage Analog Electric Combination Pneumatic / Direct Digital Combination Low Voltage Analog Electric / Direct Digital Combination Pneumatic / Low Voltage Analog Electric / Direct Digital Combination Total Number of Buildings Reporting
Number of Buildings Reporting 1 42 8 20 2 18 3 4 97
Notes: Based on those buildings reporting a primary HVAC control implementation method (n=97).
1
Variable Descriptions: Primary HVAC Control Implementation refers to the control system in place to control the operation of the heating, ventilating, and air conditioning system. The following categories apply: Pneumatic systems use compressed air as the source of energy to actuate the control devices of the heating, ventilating, and air conditioning system. Low Voltage Analog Electric systems use electrical energy to actuate the control devices of the heating, ventilating, and air conditioning system. Direct Digital systems use digital signals to control the devices of the heating, ventilating, and air conditioning system.
BHC-7
BASE Buildings HVAC Characteristics: Primary HVAC Control Response Strategy
Primary HVAC Control Response Strategy Two-Position Proportional Floating Point Proportional-Integral Proportional-Integral-Derivative Total Number of Buildings Reporting
Number of Buildings Reporting1 9 79 3 5 22 98
Notes: Number of buildings based on those buildings reporting a primary HVAC control response strategy (n=98). Column total adds up to greater than the total number of buildings reporting as some buildings used a combination of these methods. 1
Variable Descriptions: Primary HVAC Control Response Strategy refers to the primary control response strategy for the building HVAC systems. The following categories apply: Two-Position refers to a control system in which the device being controlled is either full on or full off, with no intermediate operating positions available. Proportional refers to a control algorithm or method in which the final control device (e.g. damper or valve) moves to a position proportional to the deviation from the setpoint value of the controlled variable such as a temperature setpoint. Floating Point refers to a system where the controlled device is still operated by a two position controller, but the device moves gradually between full open and full closed. There is a neutral zone where no signal is transmitted and the controlled device "floats" in an intermediate position until a new signal is received. Proportional-Integral also known as "proportional plus reset" refers to a proportional control system where the control point is changed automatically back toward the setpoint when an offset occurs. Proportional-Integral-Derivative offers the same features as proportional-integral, but also controls the rate at which the control point is moved back to the setpoint.
BHC-8
BASE Buildings HVAC Characteristics: Particle Filtration Systems - Frequency of Maintenance Actions for Different Configurations Number of Buildings Reporting Frequency of Actions None As Needed Daily Weekly Bi-Weekly Monthly Semi-Quarterly Quarterly Semi-Annually Annually Total Number of Buildings Reporting
Frequency of Panel Filters Replacement1 1 4 0 0 0 10 2 47 17 12 93
Frequency of Manual Roll Filters Advancement2 0 4 0 0 0 6 3 2 2 1 18
Frequency of Automatic Roll Filters Inspection3 0 0 0 2 0 0 0 0 1 1 4
Notes: Data represent panel filter replacement frequencies for 93 BASE buildings equipped with this filter type. 2 Data represent frequency of manual roll filter advancement for 18 BASE buildings equipped with this filter type. 3 Data represent frequency of automatic roll filter inspection for 4 BASE buildings equipped with this filter type. 1
Variable Descriptions: Frequency of Panel Filters Replacement refers to the frequency that panel filters are changed out by building facilities personnel. Panel filters are manufactured in rectangular panels that are placed alongside each other in the filter bed. They are removed and either replaced or cleaned when dirty. Frequency of Manual Roll Filters Advancement refers to the frequency that manual roll filters are advanced by building facilities personnel. Manual roll filters consist of a fabric roll mounted on a spool that moves across the airstream. The media is manually wound on a take up spool to expose new filter material when necessary. Frequency of Automatic Roll Filters Inspection refers to the frequency that automatic roll filters are inspected by building facilities personnel. Automatic roll filters consist of a fabric roll mounted on a spool that moves across the airstream. The media is automatically wound on a take up spool to expose new filter. The movement of the media is often controlled by a pressure switch which senses the pressure drop across the media, or by an automatic timer. The frequency categories are as follows: None means that filters are not changed, advanced or inspected. As needed means that filters are changed, advanced or inspected only when deemed necessary. Daily means that filters are changed, advanced or inspected each day. Weekly means that filters are changed, advanced or inspected once per week. Bi-weekly means that filters are changed, advanced or inspected twice a month. Monthly means that filters are changed, advanced or inspected once per month. Semi-Quarterly means that filters are changed, advanced or inspected twice every three months. Quarterly means that filters are changed, advanced or inspected every three months. Semi-annually means that filters are changed, advanced or inspected once every six months. Annually means that filters are changed, advanced or inspected once a year.
BHC-9
BASE Buildings HVAC Characteristics: Frequency of Inspection for HVAC Components Number of Buildings Reporting Frequency of Inspection None As Needed Daily Weekly Bi-Weekly Monthly Semi-Quarterly Quarterly Semi-Annually Annually Total Number of Buildings Reporting Notes:
Air Handler Housing1 25 10 7 2 1 14 1 23 5 10 98
Heating and Cooling Coils2 6 7 0 1 0 14 2 29 13 26 98
Drain Pans 8 7 3 4 1 15 3 27 6 22 96
3
Air Distribution Ductwork4 59 32 0 0 0 1 0 2 1 4 99
Humidifiers 4 4 1 0 1 9 0 9 4 6 38
5
Evaporative Coolers6 1 0 0 0 1 1 0 0 0 4 7
Air Washers7 1 0 0 0 0 0 0 0 0 0 1
Cooling Towers8 0 1 19 11 3 17 1 10 3 2 67
1
Data represent 98 BASE buildings, which indicated an inspection frequency for air handling unit housing inspections. Data represent 98 BASE buildings, which indicated an inspection frequency for coil inspections. 3 Data represent 96 BASE buildings, which indicated an inspection frequency for drain pans. 4 Data represent 99 BASE buildings, which indicated an inspection frequency for ductwork. 5 Data represent 38 BASE buildings, which indicated an inspection frequency for humidifiers. 6 Data represent 7 BASE buildings, which indicated an inspection frequency for evaporative coolers. 7 Data represent 1 BASE building, which indicated an inspection frequency for air washers. 8 Data represent 67 BASE buildings, which indicated an inspection frequency for cooling towers. 2
Page 1 of 2
BHC-10
Variable Descriptions: Air Handler Housing refers to the inspection frequency of the air handling housing. The housing is a casing that is usually made up of galvanized sheet metal that contains the air handling unit components. Cooling Coils refers to the inspection frequency of the air handling unit cooling coils. Heating Coils refers to the inspection frequency of the air handling unit heating coils. Drain Pans refers to the inspection frequency of the cooling coil condensate drain pans. The drain pan is generally located under the cooling coil to collect and drain away water vapor that condenses on the cooling coil. Air Distribution Ductwork refers to the inspection frequency of the air handling unit air distribution ductwork. Humidifiers refers to the inspection frequency of humidifiers. Evaporative Coolers refers to the inspection frequency of evaporative coolers. Evaporative coolers are non-refrigerant systems that cool air by exchanging sensible heat for latent heat, reducing temperatures, but raising humidity. Air Washers refers to the inspection frequency of air washers. In some applications, air washers serve as evaporative coolers or humidifiers as their operating principle is similar to that of evaporative coolers. These may also be used to filter wettable dust from the airstream by drawing air through a mist (caused by spray nozzles) and then through eliminators to remove dust and the water particles not evaporated in the air. Cooling Towers refers to the inspection frequency of cooling towers. Cooling towers are used primarily to reject building heat to the atmosphere. The frequency categories are as follows: None refers to no inspections taking place in the building. As Needed refers to an inspection schedule where inspection occurs only when deemed necessary. Daily refers to an inspection schedule where inspection occurs each day. Weekly refers to an inspection schedule where inspection occurs on a once per week. Bi-weekly refers to an inspection schedule where inspection occurs twice a month. Monthly refers to an inspection schedule where inspection occurs once per month. Semi-Quarterly refers to an inspection schedule where inspection occurs twice every three months. Quarterly refers to an inspection schedule where inspection occurs every three months. Semi-annually refers to an inspection schedule where inspection occurs every six months. Annually refers to an inspection schedule where inspection occurs once a year.
Page 2 of 2
BHC-10
BASE Buildings HVAC Characteristics: Frequency of Cleaning for HVAC Components
Frequency of Cleaning None As Needed Daily Weekly Bi-Weekly Monthly Semi-Quarterly Quarterly Semi-Annually Annually Total Number of Buildings Reporting
Air Handler Housing1 36 17 0 0 0 2 0 14 4 24 97
Heating and Cooling Coils2 13 25 0 0 0 0 0 5 8 47 98
Drain Pans3 14 24 0 0 0 1 0 7 10 40 96
Air Distribution Ductwork4 77 16 0 0 0 0 0 1 0 2 96
Humidifiers5 7 14 0 0 0 0 1 3 3 8 36
Evaporative Coolers6 0 1 0 0 1 0 0 0 0 5 7
Air Washers7 0 1 0 0 0 0 0 0 0 0 1
Cooling Towers8 (surface cleaning)
1 9 0 0 0 2 1 7 10 36 66
Notes: Data represent 97 BASE buildings, which indicated a cleaning frequency for air handling unit-housing cleaning. For one building, the response was left blank. 2 Data represent 98 BASE buildings, which indicated a cleaning frequency for heating and cooling coils. 3 Data represent 96 BASE buildings, which indicated a cleaning frequency for drain pans. 4 Data represent 96 BASE buildings, which indicated a cleaning frequency air distribution duct work. 5 Data represent 36 BASE building, which indicated a cleaning frequency for humidifiers. 6 Data represent 7 BASE buildings, which indicated a cleaning frequency for evaporative coolers. 7 Data represent 1 BASE buildings, which indicated a cleaning frequency for air washers. 8 Data represent 66 BASE buildings, which indicated a cleaning frequency for cooling towers. 1
Page 1 of 2
BHC-11
Variable Descriptions: Air Handler Housing refers to the cleaning frequency of the air handling housing. The housing is a casing that is usually made up of galvanized sheet metal that contains the air handling unit components. Cooling Coils refers to the cleaning frequency of the air handling unit cooling coils. Heating Coils refers to the cleaning frequency of the air handling unit heating coils. Drain Pans refers to the cleaning frequency of the cooling coil condensate drain pans. The drain pan is generally located under the cooling coil to collect and drain away water vapor that condenses on the cooling coil. Air Distribution Ductwork refers to the cleaning frequency of the air handling unit air distribution ductwork. Humidifiers refers to the cleaning frequency of humidifiers. Evaporative Coolers refers to the cleaning frequency of evaporative coolers. Evaporative coolers are non-refrigerant systems that cool air by exchanging sensible heat for latent heat, reducing temperatures, but raising humidity. Air Washers refers to the cleaning frequency of air washers. In some applications, air washers serve as evaporative coolers or humidifiers as their operating principle is similar to that of evaporative coolers. These may also be used to filter wettable dust from the airstream by drawing air through a mist (caused by spray nozzles) and then through eliminators to remove dust and the water particles not evaporated in the air. Cooling Towers refers to the cleaning frequency of cooling towers. Cooling towers are used primarily to reject building heat to the atmosphere. The frequency categories are as follows: None refers to no cleaning implemented on these systems. As Needed refers to a cleaning schedule where cleaning occurs only when deemed necessary. Daily refers to a cleaning schedule where cleaning occurs each day. Weekly refers to a cleaning schedule where cleaning occurs on a once per week. Bi-weekly refers to a cleaning schedule where cleaning occurs twice a month. Monthly refers to a cleaning schedule where cleaning occurs once per month. Semi-Quarterly refers to a cleaning schedule where cleaning occurs twice every three months. Quarterly refers to a cleaning schedule where cleaning occurs every three months. Semi-annually refers to a cleaning schedule where cleaning occurs every six months. Annually refers to a cleaning schedule where cleaning occurs once a year.
Page 2 of 2
BHC-11
BASE Buildings HVAC Characteristics: Frequency of Maintenance Actions for Fan Coil Units and Terminal Units
Frequency of Actions None As Needed Daily Weekly Bi-Weekly Monthly Semi-Quarterly Quarterly Semi-Annually Annually Total Number of Buildings Reporting
Number of Buildings Reporting Fan Coil Units Fan Coil Units Terminal Units Frequency of Frequency of Filter Frequency of 1 2 Inspection Changing Inspection3 7 2 21 2 5 41 1 0 0 1 0 0 0 1 0 9 4 1 0 1 1 11 14 6 6 3 4 8 9 9 45 39 83
Notes: Data represent 45 BASE buildings, which indicated an inspection frequency for fan coil units. 2 Data represent 39 BASE buildings, which indicated a filter changing frequency for fan coil units. 3 Data represent 83 BASE buildings, which indicated an inspection frequency for terminal units. 1
Variable Descriptions: Fan Coil Units - Frequency of Inspection refers to the frequency of inspection for fan coil units. Fan Coil Units - Frequency of Filter Changing refers to the frequency that fan coil unit filters are changed out by building facilities personnel. Terminal Units - Frequency of Inspection refers to the frequency of inspection for terminal units. The frequency categories are as follows: None means that no inspection or filter change out takes place. As Needed refers to a maintenance schedule where maintenance occurs only when deemed necessary. Daily refers to a schedule where inspection or filter change out occurs each day. Weekly refers to a schedule where inspection or filter change out occurs once per week. Bi-weekly refers to a schedule where inspection or filter change out occurs twice a month. Monthly refers to a schedule where inspection or filter change out occurs once per month. Semi-Quarterly refers to a schedule where inspection or filter change out occurs twice every three months. Quarterly refers to a schedule where inspection or filter change out occurs every three months. Semi-annually refers to a schedule where inspection or filter change out occurs every six months. Annually refers to a schedule where inspection or filter change out occurs once a year.
BHC-12
BASE Buildings HVAC Characteristics: Control System - Frequency of Inspection and Sensor Calibration
Frequency of Actions None As Needed Daily Weekly Bi-Weekly Monthly Semi-Quarterly Quarterly Semi-Annually Annually Total Number of Buildings Reporting
Number of Buildings Reporting Frequency of Control Frequency of Sensor System Inspection1 Calibration2 12 15 28 58 14 0 2 0 1 0 4 4 0 0 12 3 11 7 14 10 98 97
Notes: Data represent 98 BASE buildings, which indicated an inspection frequency.
1 2
Data represent 97 BASE buildings, which indicated a calibration frequency.
Variable Descriptions: Frequency of Control System Inspection refers to the frequency of inspection for the heating, ventilating, and air conditioning system control system. Frequency of Sensor Calibration refers to the frequency of sensor calibration for the heating, ventilating, and air conditioning system control system. The frequency categories are as follows: None means that no inspections or calibrations take place. As Needed refers to an inspection or calibration schedule that occurs only when deemed necessary. Daily refers to an inspection or calibration schedule where inspection occurs each day. Weekly refers to an inspection or calibration schedule where inspection occurs on a weekly cycle. Bi-weekly refers to an inspection or calibration schedule where inspection occurs twice a month. Monthly refers to an inspection or calibration schedule where inspection occurs on a monthly schedule. Semi-Quarterly refers to an inspection or calibration schedule where inspection occurs twice every three months. Quarterly refers to an inspection or calibration schedule where inspection occurs every three months. Semi-annually refers to an inspection or calibration schedule where inspection occurs every six months. Annually refers to an inspection or calibration schedule where inspection occurs once a year.
BHC-13
BASE Buildings HVAC Characteristics: Frequency of Testing and Balancing
Frequency of Testing and Balancing None As Needed Daily Weekly Bi-Weekly Monthly Semi-Quarterly Quarterly Semi-Annually Annually Total Number of Buildings Reporting
Number of Buildings Reporting1 43 52 0 0 0 0 0 0 0 3 98
Notes: Data represent 98 BASE buildings, which indicated a frequency for testing and balancing. 1
Variable Descriptions: Frequency of Testing and Balancing refers to the frequency that testing and balancing is implemented on the building's air distribution system. The frequency categories are as follows: None means that no testing and balancing takes place. As Needed refers to a schedule where testing and balancing occurs only when deemed necessary. Daily refers to a schedule where testing and balancing occurs each day. Weekly refers to a schedule where testing and balancing occurs on a weekly cycle. Bi-weekly refers to a schedule where testing and balancing occurs twice a month. Monthly refers to a schedule where testing and balancing occurs on a monthly schedule. Semi-Quarterly refers to a schedule where testing and balancing occurs twice every three months. Quarterly refers to a schedule where testing and balancing occurs every three months. Semi-annually refers to a schedule where testing and balancing occurs every six months. Annually refers to a schedule where testing and balancing occurs once a year.
BHC-14
HVAC SPECIFICATIONS:
GENERAL NOTES: 1.
2.
3.
4.
IT IS THE INTENT OF THESE SPECIFICATIONS TO COVER FIRST CLASS WORKMANSHIP THROUGHOUT. PERSONNEL SHALL BE THOROUGHLY TRAINED AND EXPERIENCED IN THE PRODUCTS INVOLVED AND RECOMMENDED METHODS FOR THEIR FABRICATION AND INSTALLATION. NO ALLOWANCE SHALL BE MADE FOR LACK OF SKILL ON THE PART OF THE WORKMAN IN THE ACCEPTANCE AND/OR REJECTION OF COMPLETED WORK. MATERIALS AND EQUIPMENT SHALL BE NEW AND INSTALLED AS INDICATED ON THE DRAWINGS AND/OR SPECIFICATIONS. THEY SHALL BE INSTALLED PLUMB, LEVEL, AND TRUE-TO-LINE WITH ADJACENT WORK. WHERE INSTALLATION METHODS ARE NOT SPECIFICALLY COVERED BY THE DRAWINGS AND/OR SPECIFICATIONS, FIRST CLASS TRADE PRACTICES AND MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS SHALL GOVERN. CAREFULLY EXAMINE ALL ARCHITECTURAL, STRUCTURAL, PLUMBING, HVAC, FIRE PROTECTION, AND ELECTRICAL DRAWINGS PERTAINING TO THE CONSTRUCTION. COOPERATE WITH OTHER TRADES IN LOCATING DUCTWORK, PIPING, EQUIPMENT, ETC., IN ORDER TO AVOID CONFLICT WITH OTHER TRADES' WORK. NO CLAIM FOR COSTS WILL BE ALLOWED FOR RELOCATING EQUIPMENT, PIPING, DUCTWORK, ETC., WHICH INTERFERES WITH OTHER TRADES' WORK. DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF DUCTWORK, PIPING AND EQUIPMENT. DO NOT SCALE DRAWINGS. THE EXACT LOCATION AND/OR ROUTING OF EQUIPMENT, DUCTWORK, PIPING, ETC., UNLESS SPECIFICALLY DIMENSIONED ON THE DRAWINGS, SHALL BE DETERMINED IN THE FIELD. MAKE REASONABLE MODIFICATIONS IN THE INSTALLATION SO ALL DUCTWORK FITS PROPERLY AND EQUIPMENT CAN BE SERVICED.
5.
HVAC EQUIPMENT AND INSTALLATION SHALL CONFORM TO THE LATEST EDITION OF THE STATE PLUMBING CODE, STATE MECHANICAL CODE, STATE FIRE CODE, STATE BUILDING CODE, APPLICABLE OSHA AND NFPA STANDARDS, COUNTY AND CITY BUILDING REGULATIONS AND CODES.
6.
FABRICATION AND INSTALLATION OF DUCTWORK SHALL BE IN ACCORDANCE WITH SMACNA HVAC DUCT CONSTRUCTION STANDARDS, STATE MECHANICAL CODE AND APPLICABLE NFPA STANDARDS.
7.
19.
MECHANICAL CONTRACTOR SHALL HAVE THE FINAL START-UP OF ALL HVAC EQUIPMENT SUPERVISED AND MONITORED BY A FACTORY AUTHORIZED TECHNICIAN. CONTRACTOR SHALL SUBMIT A WRITTEN HVAC SYSTEM START-UP SUPERVISION VERIFICATION FORM.
20.
PROVIDE ACCESS TO ALL DAMPERS AS REQUIRED FOR MAINTENANCE.
21.
FIRE DAMPERS WITH ACCESS DOORS SHALL BE INSTALLED IN ALL DUCTWORK PASSING THROUGH FIRE SEPARATING WALLS, PARTITIONS, AND FIRE RATED CEILINGS.
23.
HVAC UNIT LEVELING SHALL BE BY MECHANICAL CONTRACTOR.
INSULATED DOUBLE WALL DUCT SHALL BE FABRICATED WITH AN OUTER SHELL AND A PERFORATED INNER LINER WITH 1" FIBERGLASS INSULATION BETWEEN THE SHELL AND LINER. (DUCT DIMENSIONS SHOWN ARE EXTERIOR SHEET METAL DIMENSIONS.)
24.
MECHANICAL CONTRACTOR SHALL PROVIDE CONDENSATE TRAP AT EACH AIR HANDLING UNIT.
ELBOWS & TEES SHALL INCLUDE TURNING VANES.
25.
FRESH AIR INTAKE SHALL BE MINIMUM OF 10'-0" FROM ANY EXHAUST FAN, FLUE OR PLUMBING VENT. COORDINATE WITH GENERAL CONTRACTOR.
PROVIDE FLEXIBLE CONNECTIONS AT EQUIPMENT.
26.
MECHANICAL CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND CATALOG SHEETS TO ARCHITECT/ENGINEER AND SHALL INCLUDE: FANS
B.
ELECTRIC WALL HEATERS
C.
GRILLES, REGISTERS, AND DIFFUSERS
D.
HVAC CONTROLS
E.
VIBRATION ISOLATORS
F.
INSULATION
8.
MECHANICAL CONTRACTOR SHALL ARRANGE AND PAY FOR MECHANICAL PERMITS AND INSPECTIONS AS REQUIRED BY LOCAL ORDINANCES.
9.
DELIVER MATERIALS TO PROJECT IN GOOD CONDITION. STORE MATERIALS OFF GROUND AND PROTECTED FROM THE ELEMENTS.
G.
AIR TERMINAL UNITS
10.
VERIFY DIMENSIONS IN FIELD. VERIFY STRUCTURAL DETAILS BEFORE INSTALLING DUCTWORK. NO EXTRA COMPENSATION WILL BE ALLOWED BECAUSE OF DIFFERENCES BETWEEN ACTUAL MEASUREMENTS AND DIMENSIONS AND THOSE INDICATED ON THE DRAWINGS. NOTIFY ARCHITECT/ENGINEER IN WRITING OF ANY DIFFERENCE WHICH MAY BE FOUND BEFORE PROCEEDING WITH WORK
H.
ROOFTOP UNITS
I.
GAS REGULATORS
MECHANICAL CONTRACTOR SHALL KEEP ACCURATE RECORDS OF ALL DUCTWORK AND EQUIPMENT WHICH DEVIATED FROM THE DRAWINGS. AT COMPLETION OF WORK, CONTRACTOR SHALL SUBMIT A MARKED SET OF DESIGN PRINTS INDICATING CHANGES.
12.
ALL PENETRATIONS THROUGH WALLS SHALL BE PROVIDED WITH PROPER SIZED SLEEVES. SEAL ALL PIPE SLEEVES WITH APPROPRIATE CAULKING. ALL SIX (6) INCH AND SMALLER PIPE PENETRATIONS THROUGH FIRE RATED WALLS AND/OR FLOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROPRIATE 3M FIRESTOP SYSTEM (OR APPROVED EQUAL). ALL PIPING SLEEVES SHALL BE SCHEDULE 40, CARBON STEEL, ASTM A53, GRADE B. ANY CUTTING OR PATCHING OF NEW OR EXISTING SURFACES THAT IS REQUIRED SHALL BE BY THIS CONTRACTOR AND SHALL BE REPLACED WITH MATERIAL OF THE SAME QUALITY AND THICKNESS AS THE EXISTING SURFACE. ANY DAMAGES TO EXISTING MATERIALS SHALL BE REPAIRED OR REPLACED TO MATCH EXISTING.
13.
14.
ALL DUCTWORK SHALL BE IDENTIFIED AFTER INSULATION WITH PLASTIC DUCT MARKERS. THESE MARKERS SHALL BE THE MANUFACTURER'S STANDARD LAMINATED PLASTIC IN THE FOLLOWING COLOR CODES: A.
BLUE: SUPPLY AIR.
B.
RED: RETURN AND MIXED AIR.
C.
YELLOW: OUTSIDE AIR.
ABBREVIATIONS AFF BHP BOD BOP CFM D DWG EA EAT EF EWH FFE FIN FL FV G.C. HP LAT M M.C. MD NC N.C. NG NO NTS P.C. PD PRV RA RH RTU SA SF SHT SP TBE TOD TOP TYP UNO VAV VFD VIF
ELBOW
ALL SUPPLY DUCT FROM RTU-17 TO AIR TERMINAL UNITS SHALL BE GALVANIZED SHEET METAL OF GAUGE AND CONSTRUCTION AS REQUIRED BY SMACNA 6" W.G. PRESSURE CLASS. (DUCT DIMENSIONS SHOWN ARE SHEET METAL DIMENSIONS.) SEAL ALL DUCTWORK PER SMACNA CLASS A.
MAINTAIN A MINIMUM DISTANCE OF 10'-0" FROM ROOF MOUNTED HVAC EQUIPMENT TO THE EDGE OF THE ROOF.
MECHANICAL CONTRACTOR SHALL FURNISH ALL LABOR, MATERIAL, TOOLS, AND EQUIPMENT TO INSTALL ALL HVAC SYSTEMS AS INDICATED ON THESE DRAWINGS.
11.
DUCTWORK SUPPLY: UNLESS OTHERWISE NOTED, SUPPLY AIR DUCT SHALL BE GALVANIZED SHEET METAL OF GAUGE & CONSTRUCTION AS REQUIRED BY SMACNA 2 in-wg PRESSURE CLASS. (DUCT DIMENSIONS SHOWN ARE SHEET METAL DIMENSIONS. NO INCREASE IN SIZE REQUIRED FOR DUCT LINER). SEAL ALL DUCTWORK PER SMACNA CLASS B.
22.
A.
MECHANICAL LEGEND
RECTANGULAR TEE
RECTANGULAR/ROUND TRANSITION
RETURN: UNLESS OTHERWISE NOTED, RETURN AIR DUCT SHALL BE GALVANIZED SHEET METAL OF GAUGE & CONSTRUCTION AS REQUIRED BY SMACNA 2 in-wg PRESSURE CLASS. (DUCT DIMENSIONS SHOWN ARE SHEET METAL DIMENSIONS. NO INCREASE IN SIZE REQUIRED FOR DUCT LINER). SEAL ALL DUCTWORK PER SMACNA CLASS B.
HIGH-EFFICIENCY TAKE-OFF
ELBOWS & TEES SHALL INCLUDE TURNING VANES.
RECTANGULAR BEVELED TAP
PROVIDE FLEXIBLE CONNECTIONS AT EQUIPMENT. EXHAUST/TRANSFER: UNLESS OTHERWISE NOTED, EXHAUST AIR DUCT SHALL BE GALVANIZED SHEET METAL OF GAUGE & CONSTRUCTION AS REQUIRED BY SMACNA 2 in-wg PRESSURE CLASS. (DUCT DIMENSIONS SHOWN ARE SHEET METAL DIMENSIONS. NO INCREASE IN SIZE REQUIRED FOR DUCT LINER). SEAL ALL DUCTWORK PER SMACNA CLASS B.
RECTANGULAR/ROUND EXTERNALLY INSULATED DUCT
RECTANGULAR/ROUND INTERNALLY INSULATED DUCT ELBOWS & TEES SHALL INCLUDE TURNING VANES. PROVIDE FLEXIBLE CONNECTIONS AT EQUIPMENT.
27.
PROVIDE PIPE MARKERS FOR NATURAL GAS PIPING SYSTEMS. PIPE MARKERS SHALL BE PRESSURE SENSITIVE VINYL, CONFORM TO ANSI A13.1 AS MANUFACTURED BY SETON NAMEPLATE CORPORATION, OR APPROVED EQUAL. PIPE MARKERS SHALL BE APPLIED NEAR EACH BRANCH CONNECTION, EVERY TWENTY FEET IN STRAIGHT RUNS, AND INCLUDE FLOW ARROWS.
INSULATION DUCTWORK: INTERNAL FIBERGLASS DUCT LINER: JOHNS MANVILLE LINACOUSTIC RC FIBERGLASS DUCT LINER WITH REINFORCED COATING (OR APPROVED EQUAL) INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION SPECIFICATIONS.
28.
CONTRACTOR SHALL FIELD DETERMINE ALL DUCT TRANSITIONS PER DUCT SIZES INDICATED, AIR HANDLING EQUIPMENT INLETS/OUTLETS AND/OR SUPPLY/RETURN AIR GRILLES/DIFFUSERS. PROVIDE FLEXIBLE CONNECTIONS AT ALL EQUIPMENT AND AT ALL CEILING MOUNTED SUPPLY/RETURN/EXHAUST GRILLES/DIFFUSERS..
EXTERNAL FIBERGLASS DUCT WRAP: JOHNS MANVILLE MICROLITE FORMALDEHYDE-FREE FIBERGLASS DUCT WRAP (OR APPROVED EQUAL) INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION SPECIFICATIONS.
29.
PROVIDE DUCT TRANSITIONS AT ALL EQUIPMENT CONNECTIONS. TRANSITION DETAIL SHALL BE DETERMINED IN THE FIELD.
30.
MECHANICAL CONTRACTOR SHALL PROVIDE MISCELLANEOUS STEEL AS REQUIRED TO INSTALL NEW HVAC EQUIPMENT, DUCTWORK AND PIPING.
31.
MECHANICAL CONTRACTOR IS RESPONSIBLE FOR MAKING PIPING MODIFICATIONS DUE TO FINAL SELECTION OF EQUIPMENT, INSTRUMENTS AND PIPING COMPONENTS.
RECTANGULAR 1.5xCL RADIUS ELBOW
ABOVE FINISHED FLOOR BRAKE HORSEPOWER BOTTOM OF DUCT BOTTOM OF PIPE CUBIC FEET PER MINUTE DRAIN DRAWING EXHAUST AIR ENTERING AIR TEMPERATURE EXHAUST FAN ELECTRIC WALL HEATER FINISHED FLOOR ELEVATION FINISHED FLOOR FIELD VERIFY GENERAL CONTRACTOR HORSEPOWER LEAVING AIR TEMPERATURE MANUAL VOLUME DAMPER MECHANICAL CONTRACTOR MOTORIZED DAMPER NORMALLY CLOSED NOISE CRITERIA NATURAL GAS NORMALLY OPEN NOT TO SCALE PLUMBING CONTRACTOR PRESSURE DROP PRESSURE REDUCING VALVE RETURN AIR RELATIVE HUMIDITY ROOF TOP UNIT SUPPLY AIR SUPPLY FAN SHEET STATIC PRESSURE THREADED BOTH ENDS TOP OF DUCT TOP OF PIPE TYPICAL UNLESS NOTED OTHERWISE VARIABLE AIR VOLUME VARIABLE FREQUENCY DRIVE VERIFY IN FIELD
ROUND 1.5xCL RADIUS GORED ELBOW
INSIDE BUILDING: SUPPLY DUCTWORK FROM RTU-17 TO AIR TERMINAL UNITS TO HAVE 2” THICK FIBERGLASS DUCT WRAP WITH FOIL FACING. SUPPLY DUCTWORK DOWNSTREAM OF AIR TERMINAL UNITS TO HAVE 1” FIBERGLASS DUCT LINER. RETURN DUCTWORK TO HAVE 1” FIBERGLASS DUCT LINER. ROUND 1.5xCL RADIUS STAMPED ELBOW
32.
MAKE WELDS TO EXISTING/NEW STEEL WITH LOW HYDROGEN ELECTRODES. STORE ELECTRODES IN ACCORDANCE WITH AWS SPECIFICATIONS. WELDING PROCESSES SHALL BE PRE-QUALIFIED PER AWS D1.1 FOR DUCT SUPPORTS AND MISCELLANEOUS SUPPORT STEEL.
33.
MECHANICAL CONTRACTOR SHALL PROVIDE ZINC-RICH COATING TO ALL WELDS.
ALL OTHER CONCEALED SUPPLY AND RETURN AIR DUCTWORK SHALL BE INTERNALLY INSULATED. UNLESS OTHERWISE NOTED, EXHAUST DUCTWORK SHALL BE UNINSULATED.
D.
GREEN: EXHAUST AIR.
E.
TERMINOLOGY: INCLUDE DIRECTION OF AIRFLOW; DUCT SERVICE SUCH AS SUPPLY, RETURN, AND EXHAUST; DUCT ORIGIN, DUCT DESTINATION, AND DESIGN FLOW.
FLEXIBLE DUCTWORK TO BE INSULATED FLEX MASTER TYPE 3 OR APPROVED EQUAL.
RECTANGULAR/ROUND INSULATED FLEXIBLE DUCT
NATURAL GAS (2 PSI AND UNDER) PIPING: 2" & SMALLER: SCHEDULE 40, CARBON STEEL, T&C ENDS, SEAMLESS OR ERW, ASTM A53 GRADE B.
SUPPLY AIR RISER EXHAUST AIR RISER
15.
ENGAGE AN INDEPENDENT TESTING, ADJUSTING AND BALANCING AGENT CERTIFIED BY EITHER AABC OR NEBB FOR ALL TESTING, ADJUSTING AND BALANCING. THE INDEPENDENT AGENT SHALL BE RESPONSIBLE FOR THE FOLLOWING:
2-1/2" AND LARGER: SCHEDULE 40, CARBON STEEL, PLAIN ENDS, SEAMLESS OR ERW, ASTM A53 GRADE B.
A.
TESTING, ADJUSTING, AND BALANCING CONFERENCE WITH THE OWNER'S AND ARCHITECT'S REPRESENTATIVES SHALL BE SCHEDULED WITH 7 DAYS ADVANCE NOTICE SUPPLIED TO ALL INVOLVED.
FITTINGS: 2" & SMALLER: 150 LB., MALLEABLE IRON, THREADED, ASTM A197.
SET HVAC SYSTEM AIR FLOW RATES WITHIN THE FOLLOWING TOLERANCES:
2-1/2" AND LARGER: STANDARD WEIGHT, CARBON STEEL, BUTTWELD ENDS, SEAMLESS, ASTM A234 GRADE WPB.
RETURN AIR RISER
B.
C.
D.
i.
SUPPLY, RETURN, AND EXHAUST FANS AND EQUIPMENT WITH FANS: +5% TO +10%
ii.
AIR OUTLETS AND INLETS: ±5%
EXHAUST AIR GRILLE AIRFLOW INDICATOR C
CO2 SENSOR
A FINAL REPORT SHALL BE PROVIDED TO OWNER. TYPE WRITTEN OR COMPUTER PRINTOUT IN LETTER-QUALITY FONT ON STANDARD BOND PAPER IN A 3-RING BINDER TABULATED INTO SECTIONS BY THE TESTING OF CFM SETTINGS, ZONE SETTINGS, O/A SETTINGS AND FAN SPEEDS SHALL BE INCLUDED IN THIS REPORT.
BOLTS: HEAVY HEX HEAD MACHINE BOLTS, WITH HEAVY HEX HEAD NUT CARBON STEEL, ASTM A307.
S
REMOTE SENSOR
T
THERMOSTAT
X-X CFM
DIFFUSER TAG CFM
17.
PROVIDE ONE DAY OF TRAINING FOR START-UP AND OPERATION OF ALL HVAC EQUIPMENT.
18.
SEISMIC RESTRAINT HANGERS & SUPPORTS FOR ALL DUCTWORK, PIPING, AND EQUIPMENT: ALL MECHANICAL EQUIPMENT, PIPING AND DUCTWORK SHALL BE RESTRAINED TO RESIST SEISMIC FORCES. RESTRAINTS SHALL MAINTAIN EQUIPMENT, PIPING AND DUCTWORK IN A CAPTIVE POSITION. RESTRAINT DEVICES SHALL BE DESIGNED AND SELECTED TO MEET THE SEISMIC REQUIREMENTS AS DEFINED IN THE LATEST ISSUE OF THE STATE BUILDING CODE OR LOCAL JURISDICTION BUILDING CODE. CONTRACTOR TO PROVIDE SEISMIC CALCULATIONS TO FM GLOBAL, FOR APPROVAL, FOR ANY EQUIPMENT OR SUPPORTS REQUIRING SEISMIC CALCULATIONS.
B.
PROVIDE CALCULATIONS TO DETERMINE RESTRAINT LOADS RESULTING FROM SEISMIC FORCES PRESENTED IN LATEST EDITION OF THE LOCAL BUILDING CODE OR STATE BUILDING CODE. SEISMIC CALCULATIONS SHALL BE CERTIFIED BY A PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF INDIANA AND IN THE DIRECT EMPLOY OF THE SEISMIC EQUIPMENT MANUFACTURER. THESE CALCULATIONS SHALL BE PROVIDED TO THE OWNER FOR SUBMISSION TO FM GLOBAL FOR REVIEW. PROVIDE CALCULATIONS FOR ALL EQUIPMENT 20 POUNDS OR GREATER.
C.
CALCULATIONS MUST SHOW THE ENTIRE LOAD PATH FROM THE EQUIPMENT TO THE BUILDING STRUCTURE AND INDICATE THE METHOD OF ATTACHMENT OF THE EQUIPMENT TO THE SEISMIC RESTRAINT AND THE SEISMIC RESTRAINT TO THE BUILDING STRUCTURE.
D.
ALL DUCTWORK, PIPING AND EQUIPMENT NOT REQUIRING CALCULATIONS SHALL BE SEISMICALLY SUPPORTED AND BRACED PER THE SEISMIC SUPPLIER'S INSTRUCTIONS.
E.
INSTALLATION INSTRUCTIONS MUST BE SUBMITTED TO THE ENGINEER PRIOR TO THE INSTALLATION OF THE EQUIPMENT.
F.
THE IMPORTANCE FACTOR Ip = 1.25
G.
THE SEISMIC SUPPLIER SHALL BE AMBER / BOOTH COMPANY, MASON INDUSTRIES, THE HILL CO. OR APPROVED EQUAL.
H.
THE CONTRACTOR SHALL PROVIDE ANY MISCELLANEOUS STEEL REQUIRED FOR MOUNTING THE EQUIPMENT AND SEISMIC RESTRAINTS TO THE STRUCTURE. THE CONTRACTOR SHALL SUBMIT DETAIL OF HOW SEISMIC ROOF CURB WILL BE ATTACHED TO THE BUILDING ROOF STEEL.
I.
A REPRESENTATIVE OF THE SEISMIC SUPPLIER SHALL VISIT THE JOB SITE PRIOR TO THE INSTALLATION OF ANY PIPING, DUCTWORK, EQUIPMENT, ETC. AND SHALL INSTRUCT THE CONTRACTOR ON THE PROPER INSTALLATION OF THE SEISMIC RESTRAINTS. THE REPRESENTATIVE SHALL CERTIFY IN WRITING AND SUBMIT TO THE ENGINEER, THAT THE INSTRUCTION HAS OCCURRED.
J.
AT THE COMPLETION OF THE PROJECT A REPRESENTATIVE OF THE SEISMIC SUPPLIER SHALL VISIT THE JOB SITE TO VERIFY THAT ALL SEISMIC RESTRAINTS ARE INSTALLED PER CODE PROVIDE A WRITTEN REPORT TO THE ENGINEER OF ANY DEFICIENCIES. THE REPRESENTATIVE SHALL THEN REVISIT THE JOB SITE FOR A FINAL INSPECTION TO VERIFY THAT ALL DEFICIENCIES HAVE BEEN CORRECTED. THE REPRESENTATIVE SHALL PROVIDE TO THE ENGINEER A WRITTEN CERTIFICATION THAT ALL SEISMIC RESTRAINTS ARE INSTALLED AS REQUIRED BY CODE AND SEISMIC SUPPLIER INSTALLATION INSTRUCTIONS.
L.
UNIONS: 2" & SMALLER: 150 LB., MALLEABLE IRON, THREADED, GROUND POINT. FLANGES: 2-1/2" AND LARGER: 150 LB., RAISED FACE OR FLAT FACE, WELDNECK OR SLIP-ON, STANDARD WEIGHT BORE, F&D TO ANSI B16.5, ASTM A105.
ALL THERMOSTATS SHALL BE MOUNTED AT 60" ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE. IF ELECTRICAL SWITCHES OR OTHER DEVICE IS MOUNTED IN THE SAME LOCATION, ALL DEVICES SHALL BE ALIGNED VERTICALLY. VERIFY ALL THERMOSTAT LOCATIONS WITH ARCHITECT/ENGINEER PRIOR TO INSTALLATION.
K.
RETURN AIR GRILLE
SUBMIT (6) COPIES OF TESTING, ADJUSTING & BALANCING REPORTS TO ENGINEER. USE TESTING, ADJUSTING & BALANCING STANDARD FORMS. FORMS TO BE STAMPED & CERTIFIED BY THIS TESTING & BALANCING AGENCY.
16.
A.
SUPPLY AIR DIFFUSER
SEE EQUIPMENT SCHEDULES ON DWG. M-601 FOR EQUIPMENT REQUIRING SEISMIC CURBS, SPRING ISOLATORS AND EQUIPMENT RAILS.
GASKETS: NON-METALLIC GASKETS FOR PIPE FLANGES (DURABLA, GARLOCK, CRANITE, ETC.), ANSI B16.21. VALVES: PLUG VALVES: 2" & SMALLER: 200 LB. WOG, THREADED, SHORT PATTERN, SEMI-STEEL LUBRICATED PLUG COCK WITH STANDARD PATTERN CAST IRON HANDLE, HOMESTEAD FIG. 611 OR APPROVED EQUAL. 2-1/2" AND LARGER: 200 LB. WOG, ANSI 125 LB. FLANGED, SHORT PATTERN, SEMI-STEEL LUBRICATED PLUG COCK WITH STANDARD PATTERN OPERATING WRENCH, HOMESTEAD FIG. 612 OR APPROVED EQUAL. NATURAL GAS VALVES ON ROOF SHALL BE TWO PIECE, FULL PORT, BRONZE BALL VALVE WITH BRONZE TRIM. REGULATOR: SENSUS OR APPROVED EQUAL. CONSULT MANUFACTURER FOR ORIFICE SIZE PER APPLICATION. SEE REGULATOR SCHEDULE SHEET M-601.
D C B A
04/07/16 03/18/16 02/29/16 02/05/16
ISSUED FOR BIDDING ISSUED FOR OWNER REVIEW ISSUED FOR 50% BID ISSUED FOR 30% BID
PCIS PCIS PCIS PCIS
ISSUE
DATE
DESCRIPTION
APP BY
ALL ROOF CURBS SHALL BE 14" ABOVE FINISHED ROOF SURFACE.
401 N.W. First St. Evansville, IN 47708
812 425 4264
PROPOSED HIGH SCHOOL
EVANSVILLE CHRISTIAN SCH. WARRICK COUNTY NEWBURGH, IN The drawings, specifications and other documents, including those in electronic form prepared by PCI Skanska Inc. for this project are Instruments of Service, and may be used solely with respect to this project. The documents may not be reproduced without first obtaining the express written consent of PCI Skanska Inc. Authorized use of electronic media or file does not guarantee that these files contain complete and accurate information. In order to insure the accuracy of the information contained and that no changes or modifications have been made, either intentional or unintentional, these files must be compared to the project's contract documents with stamped and sealed certification and applicable approved modifications. There shall be no unauthorized use or material modification of such drawings, specifications and other documents, including those in electronic form prepared by PCI Skanska Inc. for this project. By and through any use, including any unauthorized use, or any material modification, or in connection with, related to, or arising out of such use or modification, the user agrees that: PCI Skanska Inc. will not be liable or responsible for such use or modification; the user will not assert a claim or file any suit, including for contribution or indemnification, against PCI Skanska Inc. for such use or modification; and the user will indemnify and hold PCI Skanska Inc. harmless from any loss, damage, liability or cost including reasonable attorney's fees. CREATED BY: CHECKED BY:
DATE:
TNF II
PRINTED DATE:
SRP
PROJECT NUMBER:
01/04/16 4/8/2016 7:59:47 AM
20150351.00.00
HVAC NOTES
M-001 SHEET NUMBER
ISSUE
D 04/07/16
ISSUED FOR BIDDING/NOT FOR CONSTRUCTION
HVAC LEGEND & SYMBOLS
AIR DISTRIBUTION SCHEDULE
SYM.
CD-1
SERVICE LOUVERED SUPPLY REGISTER
DESCRIPTION * FOUR-WAY DEFLECTION * FACE AIR VOLUME CONTROL
EGGCRATE RETURN CR-1 GRILLE
* FREE PATTERN
MATERIAL
A. RECTANGULAR DUCT: * MANUAL OPPOSED BLADE DAMPER WITH LOCKING QUADRANT. LEVER OPE RATOR, OF STEEL CONSTRUCTION. * LOUVERS & DAMPERS MODEL CD-400; KRUEGER MODEL 0BD-DM
TYPE 2 OPERATION FOR LESS THAN 10" WIDE.
B. ROUND DUCT: * ROUND BLADE CONTROL DAMPER OF STEEL CONSTRUCTION WITH MA NUAL OPERATOR * LOUVERS AND DAMPERS MODEL CD-600.
MFG & MOD ACCESSORIES & FEATURES
STEEL CONSTRUCTION WITH WHITE BAKED ENAMEL FINISH
PRICE SCDA
ALUMINUM CONSTRUCTION WITH WHITE BAKED ENAMEL FINISH
PRICE 80
* OPPOSED BLADE DAMPER
OR
* NC < 35 * FACE VELOCITY TO BE BETWEEN 500-700 FPM
* NC < 35 * MAX FACE VELOCITY <500 FPM
OR
EGGCRATE EXHAUST GRILLE
* FREE PATTERN
ALUMINUM CONSTRUCTION WITH WHITE BAKED ENAMEL FINISH
PRICE 80
* RECTANGULAR ELBOW WITH SINGLE THICKNESS TURNING
VANE S OF STEEL CONSTRUCTION.
* NC < 35 * MAX FACE VELOCITY <500 FPM
* CONSTRUCT ALL BRANCH CONNECTIONS WITH 45° FITTING PER
SMACNA STANDARDS.
* SEE ARCHITECTURAL REFLECTED CEILING PLANS FOR MOUNTING TYPE REQUIRED.
45°
BINDING EDGE
* ALTERNATE MANUFACTURERS: METALAIRE AMD TITUS
L
* DIMENSION: L = 1/4W, 4"MINIMUM
W
*
* SHEET METAL CONNECTORS, INC. HIGH EFFICIENCY TAKEOFF WITH DAMPER AND LO CKING QUADRANT FOR ROUND DUCT TAKEOFFS FROM RECTANGULAR DUCTWORK. INCREASE MAIN DUCT SIZE AT FITTING TO ACCOMMODATE ITS INSTALLATION IF REQUIRED TO MEET SMACNA AND MANUFACTU RER'S INSTRUCTIONS. D
*
* DIMENSION: D = RUNOUT DIAMETER (6"-14") * SUPPLY DUCT * RETURN DUCT * EXHAUST DUCT * SUPPLY DUCT RISER * SUPPLY DUCT DROP * ROUND SUPPLY DUCT RISER * ROUND SUPPLY DUCT DROP * FLEXIBLE DUCT EQUAL TO FLEXMASTER TYPE 3 INSULATED FLEXIBLE DUCT
WITH ALUMINUM FOIL JACKET AND ALUMINUM FOIL FIBERGLASS POLYESTER
LAMINATE LINER. INSTALL IN ACCORDANCE WITH SECTION III OF SMACNA'S
VAC DUCT CONSTRUCTION STANDARDS, METAL AND FLEXIBLE". "H
BINDING EDGE
SUPPLY DUCT RETURN DUCT MAKE-UP AIR SUPPLY DUCT EXHAUST DUCT XX XX
DG
1. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS BEFORE FABRICATION OF H.V.A.C. COMPONENTS OR PURCHASE OF EQUIPMENT. 2. CONTRACTOR SHALL COORDINATE ALL OTHER TRADES WITH THE INSTALLATION OF H.V.A.C. SYSTEM. 3. H.V.A.C. LEGEND MAY CONTAIN SYMBOLS AND ABBREVIATIONS NOT USED ON THIS SPECIFIC PROJECT, LEGEND SHALL BE USED FOR REFERENCE PURPOSES. 4. CONTRACTOR IS RESPONSIBLE FOR THE COMPLETE H.V.A.C. SYSTEM AS IT RELATES TO DRAWINGS AND SPECIFICATIONS. 5. CONTRACTOR IS REQUIRED TO REVIEW ARCHITECTURAL PLANS FOR RATED ASSEMBLIES. CONTRACTOR IS RESPONSIBLE FOR INSTALLATION OF FIRE AND/OR SMOKE DAMPERS IN ACCORDANCE WITH THE SPECIFICATIONS AND APPLICABLE BUILDING CODES. 6. "STANDARD" ACCESSORIES OR CONTROLS ON H.V.A.C. EQUIPMENT SHALL BE THOSE WHICH MANUFACTURER PROVIDES ON THE MAJORITY OF STOCK MERCHANDISE. 7. BRAND NAMES AND MODEL NUMBERS ARE PROVIDED TO ESTABLISH A LEVEL OF QUALITY AND PERFORMANCE. "EQUAL TO" ITEMS MAY BE SUBMITTED FOR CONSIDERATION BY THE ENGINEER AND OWNER. 8. THE DRAWINGS ARE GENERALLY DIAGRAMMATIC AND INDICATE THE APPROXIMATE ROUTING OF PIPING AND DUCTWORK. CONTRACTOR SHALL COORDINATE HIS WORK WITH OTHER TRADES. MINOR OFFSETS AND ADJUSTMENTS SHALL BE PROVIDED WHERE REQUIRED AT NO ADDITIONAL COST TO THE OWNER. 9. COORDINATE CEILING DIFFUSERS AND REGISTER LOCATIONS WITH ARCHITECT'S REFLECTED CEILING PLAN.
HVAC NOTES: 1. THE CONTRACTOR IS RESPONSIBLE TO PROVIDE SUPPLY, RETURN AND EXHAUST DUCT AS FOLLOWS: DUCTWORK TO BE DESIGNED, BRACED, AND SUPPORTED IN ACCORDANCE WITH SMACNA FOR LOW PRESSURE APPLICATIONS, SEAL CLASS C PER SMACNA HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE DUCTWORK (FLEXIBLE DUCT MAX. 10') SMACNA-06). SING LE WIRE HANGERS SHALL NOT BE ALLOWED FOR FLEXIBLE DUCTWORK SUPPORT. FLEXIBLE DUCTWORK SHALL BE SUPPORTED IN A MANNER THAT PREVENTS CONSTRICTION OR DIPS. INSULATION SHALL BE AS NOTED BELOW. 2. ALL DUCT ELBOWS SHALL BE 1.5 R/D, UNLESS NOTED OTHERWISE. 3. MANUAL, OPPOSED BLADE DAMPERS SHALL BE PLACED IN EACH BRANCH OF SUPPLY DUCTWORK FOR FINAL BALANCING PURPOSES. BALANCING DEVICES SHALL BE IN ACCORDANCE WITH IMC (2006) 603.17. 4. CONTRACTOR SHALL FIELD VERIFY ALL DUCT ROUTING DIMENSIONS AND TERMINAL DEVICES TO AVOID INTERFERENCES. CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL SUPPORTS FOR PIPING AND DUCTWORK. 5. CONDENSATE DRAIN PIPING SHALL BE FULL SIZE PER EQUIPMENT CONNECTION ROUTED TO INDIRECT CONNECTION WITHOUT CREATING AN OBSTRUCTION. ALL SUPPORTS FOR THE CONDENSATE DRAIN PIPING IS BY THE MECHANICAL/HVAC CONTRACTOR. 6 PROVIDE MINIMUM 10 FEET SEPARATION BETWEEN OUTSIDE AIR INTAKES AND EXHAUST VENTS, PLUMBING VENTS, ETC. 7. PROVIDE SMOKE DETECTORS IN THE SUPPLY AND RETURN AIR DUCTS OF ALL UNITS 2000 CFM AND OVER. LOCATE DETECTOR IN THE RETURN AIR DUCT UPSTREAM OF FRESH AIR MIXING, AND UPSTREAM OF EXHAUST IN ACCORDANCE WITH IMC 606.2.1. LOCATE DETEC TOR IN THE SUPPLY AIR DUCT DOWNSTREAM OF THE FILTERS AND UPSTREAM OF THE FIRST BRANCH CONNECTION IN ACCORDANCE WITH NFPA 90A. DETECTORS SHALL BE WIRED INTO BUILDING FIRE ALARM SYSTEM AND SHALL BE WIRED TO SHUT UNIT/S DOWN UPON DETECTION OF SMOKE. 8. THERMOSTATS SHALL BE MOUNTED 48" ABOVE FINISHED FLOOR UNLESS INDICATED OTHERWISE. 9. PROVIDE ACCESS DOOR (12"x12" MIN) AS REQUIRED FOR DAMPER AND CONTROL ACCESS IN WALLS AND CEILINGS.
DUCT SEALING:
* DU CT TRANSITION
SD
SD
* SMOKE DAMPER * INDI CATES 3/4" UNDERCUT DOOR
HWS
* HOT WATER SUPPLY PIPING
HWR
* HOT WATER RETURN PIPING
15012 550 W. MAIN STREET, SUITE 300 KNOXVILLE, TENNESSEE 37902 CONTACT:
DOUG McCARTY
[email protected]
TELEPHONE:
(865) 544-2000
FACSIMILE:
(865) 544-0402
INTERNET:
mhminc.com
PROJECT INFORMATION
CONTRACT:
SBC - 166/005-02-2013
NEW FOOTBALL STADIUM -EA ST TENNESSEE STATE UNIVERSITY 1415 MURFREESBORO ROAD, SUITE 664 NASHVILLE , TENNESSEE 37614 ACTIVE DESIGN PHASE
SCHEMATIC DESIGN
DESIGN DEVELOPMENT
REDI-CHECK
CONSTRUCTION BIDDING PHASE
CONSTRUCTION DOCUMENTS CONSTRUCTION DOCUMENTS
AS-BUILT RECORDS
SEAL:
© McCarty Holsaple McCarty, Inc.
Do NOT scale drawings, use given dimensions only.
If not shown, verify correct dimension with ARCHITECT.
Contractor shall check and verify all dimensions and
conditions at job site.
CONSULTANT INFORMATION
A. PRESSURE SENSITIVE TAPE USED AS THE PRIMARY SEALANT IS CERTIFIED AND SHALL COMPLY WITH UL-181A OR UL-181B. B. PROVIDE LONGITUDINAL SEAMS ON RIGID DUCT AND TRANSVERSE SEAMS ON ALL DUCTS. C. PROVIDE MECHANICAL FASTENERS AND SEALANTS SHALL BE USED TO CONNECT DUCTS AND AIR DISTRIBUTION DEVICES.
1. SLEEVES SHALL BE INSTALLED WHERE DUCTS, LOUVERS, OR PIPING PENETRATE NON-RATED EXTERIOR WALLS, PARTITIONS, FLOORS, OR ROOF. PACK AR OUND SLEEVES AND SEAL WEATHER TIGHT. IN STALL FLASHING AS REQUIRED. SLEEVES SHALL BE MINIMUM 16 GAUGE GALVANIZED STEEL AND SHALL BE FIRMLY SET IN BUILDING STRUCTURE.
* FIRE DAMPER
ARCHITECTS & INTERIOR DESIGNERS
1
10. PROVIDE MANUAL VALVES FOR AIR RELEASE AT ALL HIGH POINTS IN HYDRONIC SYSTEMS. 11. FIRE DAMPERS ARE NOT REQUIRED IN ONE OR MORE HOUR FIRE WALLS AS LONG AS ALL EXCEPTIONS STATED IN IMC 607.5.3 ARE MET.
PENETRATIONS:
FD
Mc C A R T Y H O LSAPLE Mc C A R T Y
EMAIL:
* INDIC ATES NEW HVAC EQUIPMENT
* DOOR GRILLE
U/C
GENERAL NOTES:
CODES OFFICIAL REVIEW
* 3-WAY VALVE * 2-WAY VALVE * BALL VALVE
BINDING EDGE
* BUTT ERFLY VALVE T
* WALL MOUNTED THERMOSTAT
S
* WALL MOUNTED SENSOR
CO2
* WALL MOUNTED CO2 SENSOR
SP
* DUCT MOUNTED STATIC PRESSURE SENSOR
KEY PLAN:
* SUPPLY DIFFUSER W/FLEX DUCT * RETUR N GRILLE * EXHAUST G RILLE OR EXHAUST FAN (REFER TO DRAWINGS FOR CLARIFICATION) * S IDEWALL SUPPLY GRILLE
REVISION INFORMATION
No. Date Description 1 2/12/2016 SFMO Revisions
* SIDE WALL RETURN GRILLE
DRAWING INFORMATION
SCALE:
1/8" = 1'-0"
SCALE GUIDE: DWG ISSUED:
12.30.15
PRJ MGR:
S. WEBB
PA / PC:
TIME / DATE:
2/18/2016 1:35:31 PM
DRAWN BY: CHECKED BY:
S. BUTCHER / C. MOELLENDICK SGP JMK/LTH
DRAWING TITLE:
MECHANICAL NOTES
& LEGENDS
DRAWING NO:
M001
CONTROL SYMBOLS 140 Park Avenue
New City, NY 10956 www.shilale.com
WELDING Tel 845-708-9200 335 WESTERN HIGHWAY TAPPAN, NY 10983
TOWN OF ORANGETOWN COUNTY OF ROCKLAND
HOMES FOR HEROES
FAX: 845-562-7007
TEL: 845-562-7005
NEW WINDSOR, NY 12553
3062 ROUTE 9W, SUITE 500
1
GENERAL NOTES:
M-001
PIPING CONT'D.
DIFFUSER SYMBOLS
NOTES & SYMBOLS
1/2
MECHANICAL SYMBOLS: IF THIS BAR DOES NOT MEASURE 1" THEN DRAWING IS NOT TO FULL SCALE
0
MECHANICAL ABBREVIATIONS:
DUCTWORK SYMBOLS SINGLE LINE DOUBLE LINE
PIPING SYMBOLS
DELIVERY, STORAGE, AND HANDLING
IF THIS BAR DOES NOT MEASURE 1" THEN DRAWING IS NOT TO FULL SCALE
1 1/2
0
CIRCULAR BRANCH CONNECTON TO SINGLE OUTLET
PIPE HANGER DETAIL
CG-A CG-B CG-C TR
0-1100 0-1100 151-270 -
RET / EXH RET / EXH RET / EXH SUPPLY
10X10 SEE DWGS
24X24 24X24 10X10 SEE DWGS
REMARKS
12x4 SEE DWGS
XAC35LD W/ LIGHT SHIELD PAINTED BLACK X3HD-81-L FILTER GRILLE X35H-D W/ LIGHT SHIELD PAINTED BLACK S20V WITH OPPOSED BLADE DAMPERS
EPL EPL EPL EPL
NOTES: 1. SEE HVAC FLOOR PLAN FOR CFM'S. 2. COORDINATE BORDER AND FRAME TYPES WITH ARCHITECTUAL CEILING DETAILS. 3. PROVIDE VOLUME DAMPERS AT ALL BRANCH OUTLETS. 4. PROVIDE ALL DIFFUSERS WITH FLOW EQUALIZING DEFLECTORS. 5. PROVIDE ALL DIFFUSERS AND REQISTERS WITH OPPOSED BLADE DAMPERS. 6. ALL DIFFUSERS, GRILLES AND REGISTERS TO HAVE MANUFACTURERS STANDARD WHITE BAKED-ON FINISH.
TOILET EXHAUST ROOF CURB/HOOD DETAIL TOWN OF ORANGETOWN COUNTY OF ROCKLAND
SUPPLY SUPPLY SUPPLY SUPPLY
TYP. BRANCH DUCT SIZE 12x4 14x6 16x6 16x8
ROUND DUCT HANGERS
New City, NY 10956 www.shilale.com
Tel 845-708-9200
FAN COIL UNIT SCHEDULE
335 WESTERN HIGHWAY TAPPAN, NY 10983
0-175 176-350 351-450 451-650
NOMINAL FACE SIZE - W x L (IN.) 24X24 24X24 24X24 24X24
FAX: 845-562-7007
CD-A CD-B CD-C CD-D
NECK SIZE (IN.)/ NO. OF SLOTS 6 8 10 12
HOMES FOR HEROES
SERVICE
TEL: 845-562-7005
CFM
NEW WINDSOR, NY 12553
DESIGNATION
3062 ROUTE 9W, SUITE 500
DIFFUSER, GRILLE AND REGISTER SCHEDULE (ANEMOSTAT AS STD.)
M-002
PIPE PENETRATION THROUGH ROOF DETAIL
DETAILS & SCHEDULES
140 Park Avenue
AIR-COOLED CONDENSING UNIT SCHEDULE
M-100
140 Park Avenue
New City, NY 10956 www.shilale.com
Tel 845-708-9200 335 WESTERN HIGHWAY TAPPAN, NY 10983
TOWN OF ORANGETOWN COUNTY OF ROCKLAND
T
HOMES FOR HEROES
T FAX: 845-562-7007
TEL: 845-562-7005
NEW WINDSOR, NY 12553
3062 ROUTE 9W, SUITE 500
T
FLOOR PLAN
T 1/2
1 IF THIS BAR DOES NOT MEASURE 1" THEN DRAWING IS NOT TO FULL SCALE
0
ELECTRICAL ONE-LINE DIAGRAM
E-001
140 Park Avenue
New City, NY 10956 www.shilale.com
FEEDER SCHEDULE. Tel 845-708-9200 335 WESTERN HIGHWAY TAPPAN, NY 10983
TOWN OF ORANGETOWN COUNTY OF ROCKLAND
HOMES FOR HEROES
FAX: 845-562-7007
TEL: 845-562-7005
3,1
NEW WINDSOR, NY 12553
3062 ROUTE 9W, SUITE 500
1/2
LIST
NOTES & SYMBOLS
SYMBOL 1 IF THIS BAR DOES NOT MEASURE 1" THEN DRAWING IS NOT TO FULL SCALE
0
ELECTRICAL
J
E-100
FLOOR PLAN
140 Park Avenue
New City, NY 10956 www.shilale.com
Tel 845-708-9200 335 WESTERN HIGHWAY TAPPAN, NY 10983
TOWN OF ORANGETOWN COUNTY OF ROCKLAND
HOMES FOR HEROES
FAX: 845-562-7007
TEL: 845-562-7005
NEW WINDSOR, NY 12553
3062 ROUTE 9W, SUITE 500
1/2
1 IF THIS BAR DOES NOT MEASURE 1" THEN DRAWING IS NOT TO FULL SCALE
0
P-001
NOTES & SYMBOLS
140 Park Avenue
New City, NY 10956 www.shilale.com
Tel 845-708-9200 335 WESTERN HIGHWAY TAPPAN, NY 10983
TOWN OF ORANGETOWN COUNTY OF ROCKLAND
HOMES FOR HEROES
FAX: 845-562-7007
TEL: 845-562-7005
NEW WINDSOR, NY 12553
3062 ROUTE 9W, SUITE 500
1/2
1 IF THIS BAR DOES NOT MEASURE 1" THEN DRAWING IS NOT TO FULL SCALE
0
P-002
DETAILS 1 OF 2
140 Park Avenue
New City, NY 10956 www.shilale.com
Tel 845-708-9200 335 WESTERN HIGHWAY TAPPAN, NY 10983
TOWN OF ORANGETOWN COUNTY OF ROCKLAND
HOMES FOR HEROES
FAX: 845-562-7007
TEL: 845-562-7005
NEW WINDSOR, NY 12553
3062 ROUTE 9W, SUITE 500
1/2
1 IF THIS BAR DOES NOT MEASURE 1" THEN DRAWING IS NOT TO FULL SCALE
0
P-003
DETAILS 2 OF 2
140 Park Avenue
New City, NY 10956 www.shilale.com
Tel 845-708-9200 335 WESTERN HIGHWAY TAPPAN, NY 10983
TOWN OF ORANGETOWN COUNTY OF ROCKLAND
HOMES FOR HEROES
FAX: 845-562-7007
TEL: 845-562-7005
NEW WINDSOR, NY 12553
3062 ROUTE 9W, SUITE 500
1/2
1 IF THIS BAR DOES NOT MEASURE 1" THEN DRAWING IS NOT TO FULL SCALE
0
PLUMBING FLOOR PLAN
P-100
140 Park Avenue
New City, NY 10956 www.shilale.com
WATER SERVICE MECHANICAL ROOM PART PLAN Tel 845-708-9200 335 WESTERN HIGHWAY TAPPAN, NY 10983
TOWN OF ORANGETOWN COUNTY OF ROCKLAND
HOMES FOR HEROES
FAX: 845-562-7007
TEL: 845-562-7005
NEW WINDSOR, NY 12553
3062 ROUTE 9W, SUITE 500
1/2
1 IF THIS BAR DOES NOT MEASURE 1" THEN DRAWING IS NOT TO FULL SCALE
0
FP-001
NOTES & SYMBOLS
140 Park Avenue
New City, NY 10956 www.shilale.com
Tel 845-708-9200 335 WESTERN HIGHWAY TAPPAN, NY 10983
TOWN OF ORANGETOWN COUNTY OF ROCKLAND
HOMES FOR HEROES
FAX: 845-562-7007
TEL: 845-562-7005
NEW WINDSOR, NY 12553
3062 ROUTE 9W, SUITE 500
1/2
1 IF THIS BAR DOES NOT MEASURE 1" THEN DRAWING IS NOT TO FULL SCALE
0
FP-100
FLOOR PLAN
140 Park Avenue
New City, NY 10956 www.shilale.com
Tel 845-708-9200 335 WESTERN HIGHWAY TAPPAN, NY 10983
TOWN OF ORANGETOWN COUNTY OF ROCKLAND
HOMES FOR HEROES
FAX: 845-562-7007
TEL: 845-562-7005
NEW WINDSOR, NY 12553
3062 ROUTE 9W, SUITE 500
1/2
1 IF THIS BAR DOES NOT MEASURE 1" THEN DRAWING IS NOT TO FULL SCALE
0
PIPING SYMBOLS
DESCRIPTION
SYMBOL
ABBREVIATIONS
ABBREV
DESCRIPTION
EXHAUST AIR DUCT SECTION
FLOW CONTROL
SUPPLY AND OUTSIDE AIR SECTION
THERMOMETER WELL
4
ABBREVIATIONS
ABBREV
DESCRIPTION
DESCRIPTION
AC
AIR CONDITIONING UNIT, AIR COMPRESSOR
G
NATURAL GAS
AD
ACCESS DOOR
GA
GAUGE
AFF
ABOVE FINISHED FLOOR
GD
GLYCOL DRAIN
AP
ACCESS PANEL
GFH
GAS FIRED HEATER
ARCH
ARCHITECTURE
HC
HEATING COIL
5
ABBREVIATIONS
ABBREV
DESCRIPTION
S
SOIL
SA
SUPPLY AIR
SAD
SUPPLY AIR DUCT
SD
SMOKE DETECTOR
SF
SUPPLY FAN
GENERAL NOTES 1.
PRESSURE TAP, PETE’S PLUG
RETURN AIR DUCT SECTION
UNION R
DUCT RISE S
D
SLOPE LINE DOWN IN DIRECTION OF ARROW D
DUCT DROP CONCENTRIC REDUCER TURNING VANES ECCENTRIC REDUCER
AS
AIR SEPARATOR
HD
HEAT DETECTOR
BC
BRANCH CONTROL
HWR
HEATING HOT WATER RETURN
BDD
BACK DRAFT DAMPER
HWS
HEATING HOT WATER SUPPLY
BLDG
BUILDING
HS
HAND SWITCH
BOD
BOTTOM OF DUCT
HOA
HAND OFF AUTO
BODF
BOTTOM OF DIFFUSER
HP
HORSEPOWER, HEAT PUMP
SP
STATIC PRESSURE
SR
SUPPLY REGISTER
THE INSTALLATION OF MECHANICAL SYSTEMS SHALL COMPLY WITH: A. UNIFIED FACILITIES CRITERIA. B. 2006 INTERNATIONAL BUILDING CODE C. 2006 INTERNATIONAL MECHANICAL CODE D. 2006 INTERNATIONAL PLUMBING CODE E. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) F. CURRENT EDITIONS OF THE FOUR AMERICAN SOCIETY OF HEATING REFRIGERATION AND AIR CONDITIONING (ASHRAE) HANDBOOKS: APPLICATIONS, SYSTEMS AND EQUIPMENT, REFRIGERATION AND FUNDAMENTALS. G. HVAC DUCT CONSTRUCTION STANDARD (SMACNA) H. SEISMIC RESTRAINT MANUAL (SMACNA) I. LOCAL COUNTY CODES AND REQUIREMENTS. J. ENERGY POLICY ACT OF 2005. K. ASHRAE STANDARDS. L. ARMY RESERVE IT MANUAL.
2.
THE INSTALLATION OF SYSTEMS SHALL BE IN STRICT ACCORDANCE WITH THE LATEST STANDARDS BY THE AMERICAN SOCIETY OF HEATING, REFRIGERATING, AND AIR CONDITIONING ENGINEERS (ASHRAE), SHEET METAL AND AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION (SMACNA).
3.
EQUIPMENT, PIPING, AND DUCTWORK SHALL BE SEISMICALLY SECURED TO THE STRUCTURE IN COMPLIANCE WITH UNIFIED FACILITIES CRITERIA AND MANUFACTURER RECOMMENDATIONS.
SS
STAINLESS STEEL
TG
TRANSFER GRILLE
4.
ROOM THERMOSTATS SHALL BE INSTALLED 48" ABOVE THE FINISHED FLOOR, UNLESS OTHERWISE NOTED ON PLANS.
U/C
UNDERCUT (DOOR)
5.
UTR
UP THRU ROOF
DUCT SIZES SHOWN ON DRAWINGS ARE INSIDE CLEAR DIMENSION. WHERE DUCT LINER IS INSTALLED IN DUCT, INCREASE DUCT SIZE TO PROVIDE INSIDE CLEAR DIMENSIONS SHOWN ON DRAWINGS. EXPOSED DUCT LINER IS NOT PERMITTED UPSTREAM OF VAV BOXES.
6. V
VOLT
DUCT BRANCHES SHALL HAVE A MANUAL VOLUME DAMPER IN AN ACCESSIBLE LOCATION. PROVIDE ACCESS PANELS WHERE NOT ACCESSIBLE. COORDINATE LOCATIONS WITH ARCHITECT.
VAV
VARIABLE AIR VOLUME
7.
MAINTAIN COORDINATION OF EQUIPMENT, DUCTWORK AND PIPING WITH OTHER TRADES TO AVOID INTERFERENCES.
VD
VOLUME DAMPER
8.
PROVIDE SUPPORTS (THRUST RESTRAINTS, ETC.) FOR PIPING AT POINTS WHERE EQUIPMENT IS DISCONNECTED FROM THE SYSTEM.
9.
CONNECTION, DEMOLITION OR INTERRUPTION TO EXISTING SERVICES SHALL BE MINIMIZED AND COORDINATED WITH THE CONTRACTING OFFICER REPRESENTATIVE.
US Army Corps of Engineers LOUISVILLE DISTRICT
Appr.
HVAC SYMBOLS
SYMBOL
*** Safety Pays ***
2
Date
1
AIR EXTRACTOR OBD
PRESSURE RELIEF VALVE
GLOBE VALVE
BOP
BOTTOM OF PIPE
HU
HUMIDIFIER UNIT
BOT
BOTTOM
HVU
HEATING VENTILATION UNIT
BR
BASEBOARD RADIATOR
HWP
HOT WATER PUMP
VF
VENTILATION FAN
CA
COMPRESSED AIR
IA
INSTRUMENT AIR
VFD
VARIABLE FREQUENCY DRIVE
AIRFLOW MEASURING/MONITORING STATION
GATE VALVE BACK DRAFT DAMPER
PLUG VALVE VI
VIBRATION ISOLATOR
CC
COOLING COIL
IV
INTAKE VENTILATOR
WB
WET BULB
CD
CEILING DIFFUSER
JC
JANITOR’S CLOSET
WG
WATER GAGE
KILOWATT
INTAKE GRAVITY LOUVERED PENTHOUSE
CHEMICAL POT FEEDER
KW
WIH
CHM
LAT
LEAVING AIR TEMPERATURE
WMS
WIRE MESH SCREEN
M
MALE
MAU
MAKE-UP AIR UNIT
MAX
MAXIMUM
CER
CEILING EXHAUST REGISTER
CFM
CUBIC FEET PER MINUTE
BALANCE VALVE
CONT
CONTINUATION
COMPR
COMPRESSOR
CRG
CEILING RETURN GRILLE
CRR
CEILING RETURN REGISTER
MBH
THOUSAND BRITISH THERMAL UNITS PER HOUR
MFR
MANUFACTURER
MIN
MINIMUM
16. DUCTWORK AND PIPING SHALL PASS THROUGH WALLS WITHOUT RIGID CONNECTIONS. PENETRATION POINTS SHALL BE SLEEVED TO ALLOW PASSAGE OF PIPING OR DUCTWORK AND TO MAINTAIN 3/4" MIN. & 1-1/4" MAX. CLEARANCE AROUND THE OUTSIDE SURFACE. THIS CLEARANCE SHALL BE TIGHTLY PACKED WITH ONE POUND DENSITY GLASS FIBER AND CAULKED AIRTIGHT WITH NON-HARDENING SEALANT AFTER INSTALLATION OF PIPING OR DUCTWORK. INTEGRITY OF FIRE RATED WALLS AND FLOORS SHALL BE MAINTAINED WITH SUITABLE FIRE STOPPING.
MVC
MANUAL VOLUME CONTROL
17. INDICATE DUCT SIZES ON SHOP DRAWINGS WITH DIMENSIONS FOR LOCATION.
MVD
MANUAL VOLUME DAMPER
NAT’L
NATIONAL
FIRE DAMPER
EXPANSION COMPENSATOR RECTANGULAR SMOOTH RADIUS ELBOW PIPE GUIDE CS
CONDENSER WATER SUPPLY
PIPE ANCHOR
CV
CONSTANT VOLUME BOX
BUTTERFLY VALVE DB
DRY BULB
D
DRAIN
OUTSIDE SCREW & YOKE GATE VALVE
FLOW METER
OUTSIDE AIR
EXHAUST AIR
OAU
OUTSIDE AIR UNIT
EAD
EXHAUST AIR DUCT
OAL
OUTSIDE AIR LOUVER
ROUND CEILING SUPPLY DIFFUSER
POINT OF CONNECTION
CFM
OBD
OPPOSED BLADE DAMPER
EAT
OED
OPEN END DUCT W/ INSECT SCREEN
ENTERING AIR TEMPERATURE
24x24 MS
SIDE WALL REGISTER
MOTOR STARTER
EC
24. EXHAUST DUCTWORK SHALL BE RIGID, NO FLEX. 25. HVAC DRAWINGS ARE SCHEMATIC AND DIAGRAMMATIC. THE CONTRACTOR WILL COORDINATE WITH OTHER TRADES PRIOR TO INSTALLATION TO AVOID CONFLICTS. CONFLICTS THAT ARISE DUE TO LACK OF COORDINATION WILL BE REMEDIED BY THE CONTRACTOR AT NO ADDITIONAL COST.
EVAPORATIVE COOLER
200 CFM 12x8
EXHAUST REGISTER
EF
EXHAUST FAN
ER
EXHAUST REGISTER
ERV
ENERGY RECOVERY VENTILATOR
RETURN REGISTER PIPE TURNING UP
18x12
PIPE TURNING DOWN ESP
EUH
M
EXH
F
POINT OF CONNECTION
SYMBOL
FC
DESCRIPTION
FCO SECTION NO.
SHEET NO.
DETAIL NO.
SHEET NO.
SECTION REFERENCE
X X
PVC
POLYVINYL CHLORIDE
RA
RETURN AIR
RAD
RETURN AIR DUCT
RCP
REMOTE CONTROL PANEL
RG
RETURN GRILLE
RH
RELATIVE HUMIDITY
RL
REFRIGERANT LIQUID LINE
RM
ROOM
RN-1
ROOF NOZZLE (EQUIP. NUMBER)
RLA
RELIEF AIR
RPM
REVOLUTIONS PER MINUTE
FLEXIBLE CONNECTION
Mark
FLOOR CLEANOUT
FD
FIRE DAMPER
FF
FINISHED FLOOR
FLA
FULL LOAD AMP
FOB
FLAT ON BOTTOM
FOT
FLAT ON TOP
EQUIPMENT IDENTIFICATION TAG FPM
FEET PER MINUTE
FRP
FIBERGLASS REINFORCED PLASTIC
FSD
FIRE SMOKE DAMPER
RR
RETURN REGISTER
FT
FOOT/FEET
RS
REFRIGERANT SUCTION LINE
RV
RELIEF VENTILATOR
SHEET NOTE REFERENCE TAG
7/22/2011
X
PRESSURE RELIEF DAMPER
DETAIL REFERENCE
X X
PRD
27. TO THE EXTENT POSSIBLE, PROVIDE MIN 1" CLEARANCE BETWEEN MECHANICAL EQUIPMENT IN CEILING AND OTHER EQUIPMENT, STRUCTURAL, BUILDING COMPONENTS, ETC.
FILTERS, FEMALE
X X
PHASE
EXHAUST
3-WAY CONTROL VALVE
UNIT HEATER
PH
ELECTRIC UNIT HEATER
2-WAY CONTROL VALVE M
PRESSURE DROP
EXTERNAL STATIC PRESSURE
CAPPED PIPE CABINET UNIT HEATER
PD
26. CONTRACTOR TO MAINTAIN A SAFE WORKING ENVIRONMENT AT THE CONSTRUCTION SITE AND SURROUNDING AREAS. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
U.S.ARMY
SCREENED DUCT OPENING 200 CFM SC.
c:\pwworki ng\gbna\m oraja\dm s97636\LCARC_M-0010.dgn
OUTLET VELOCITY
U.S.ARMY
300 CFM
A
OV
RESERVE CENTER
12x8
PRESSURE REGULATOR VALVE
OVERFLOW NOZZLE (EQUIP. NUMBER)
CENTRIFUGAL PUMP
300 CFM
PRESSURE RELIEF VALVE
ON-1
7/22/2011
EA
23. MECHANICAL SYSTEMS SHALL BE TESTED, BALANCED AND OPERATED T0 DEMONSTRATE TO THE CONTRACTING OFFICER REPRESENTATIVE OR DESIGNATED REPRESENTATIVE THAT THE INSTALLATION AND PERFORMANCE OF THE SYSTEMS CONFORM TO THE DESIGN INTENT. TESTING AND BALANCING SHALL BE PERFORMED BY A QUALIFIED INDEPENDENT AGENCY CERTIFIED BY THE ASSOCIATION AIR BALANCE COUNCIL (AABC) OR THE NATIONAL ENVIRONMENTAL BALANCING BUREAU (NEBB). TEST RESULTS SHALL BE DOCUMENTED AND SUBMITTED FOR APPROVAL.
Pl ot scal e:NONE
DIFFERENTIAL PRESSURE
Pl ot date:
DP
AIR FILTER REGULATOR
B SD-#
OA
22. ACCURATE "AS-BUILT" DRAWINGS SHALL BE MAINTAINED DURING CONSTRUCTION AND SUBMITTED FOR APPROVAL UPON COMPLETION OF INSTALLATION.
FAX (714) 327-1601
CEILING SUPPLY DIFFUSER
NOT TO SCALE
TEL (714) 327-1600
CFM
NTS DOWN
R SD-#
NON-POTABLE WATER
Fi l e nam e:LCARC_M 0010. dgn
ORIFICE
NP
21. UNIT OR DUCT MOUNTED SMOKE DETECTORS SHALL BE INTERLOCKED WITH ASSOCIATED MECHANICAL EQUIPMENT TO SHUT DOWN THE UNIT UPON SMOKE DETECTION. COORDINATE WIRING WITH ELECTRICAL CONTRACTOR.
DIAMETER
CEILING RETURN DIFFUSER CFM
NUMBER, NORMALLY OPEN
M .BETZ
O /
NO
20. UNIONS SHALL BE PROVIDED AND INSTALLED PRIOR TO EQUIPMENT CONNECTIONS. PROVIDE DIELECTRIC UNIONS, GASKETS AND FASTENERS AT DISSIMILAR METAL CONNECTIONS OR CONTACT POINTS.
Subm i tted by:
DN
RR-#
NOT IN CONTRACT
HUTTON CENTRE DRI VE,SUI TE 800
FLEX CONNECTION
NIC
SANTA ANA, CALI FORNI A 92707
DIA., CEILING EXHAUST REGISTER
NORMALLY CLOSED
4
FM
ER-#
NC
19. CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING AND REPAIRING AREAS, PIPING, DUCTWORK, ETC., EXISTING OR NEW, DAMAGED AS A RESULT OF THE WORK. REPAIR TO MATCH EXISTING CONDITIONS.
F-171-40-160
UNDER CUT DOOR
DIRECTION OF AIR FLOW
CFM
COOLER UNIT
MANUAL AIR VENT, 3/8" BALL W/DISCHARGE TO DRAIN
DOOR LOUVER L
U
CU
AUTOMATIC CONTROL VALVE
Project Code:
D
CEILING SUPPLY DIFFUSER
Revi ewed by:
INFRARED RADIANT HEATER
CSD
18. THE LOCATION OF ACCESS PANELS FOR CONCEALED VALVES, FUSIBLE LINKS, DAMPER OPERATORS AND EQUIPMENT SHALL BE COORDINATED WITH THE ARCHITECT. ACCESS PANELS SHALL BE PROVIDED FOR CONCEALED EQUIPMENT INCLUDING FAN COILS AND HOT WATER COILS.
A.REED
RECTANGULAR SMOOTH RADIUS WYE
NOTE: NOT ALL ABBREVIATIONS AND
COVER SHEET
STRAINER W/BLOW DOWN SMOKE DAMPER
W 912QR-11-R-0071
SD
Sol i ci tati on No.
PRESSURE REDUCING VALVE
CONDENSER
C.KORPASH
FD
COND
Ckd by:
FIRE & SMOKE DAMPER
15. DUCT AND PIPE PENETRATIONS AT FIRE-RATED WALLS AND AT FLOORS SHALL BE SLEEVED AND SEALED WITH FIRE STOP TO PREVENT THE PASSAGE OF SMOKE.
Dwn by:
FSD
13. DUCT CONNECTIONS TO CEILING DIFFUSERS IN EXPOSED LOCATIONS SHALL BE MADE WITH RIGID DUCT. NO FLEX DUCT WILL BE ALLOWED AT THESE CONNECTIONS. 14. FIRE DAMPERS, COMBINATION FIRE/SMOKE DAMPERS SHALL BE PROVIDED AT FIRE RATED DUCT PENETRATIONS AND SHALL CONFORM TO THE REQUIREMENTS OF THE STATE OF NEW MEXICO. PROVIDE DUCT MOUNTED SMOKE DETECTOR FOR COMBINATION FIRE/SMOKE DAMPERS.
CHECK VALVE
DUCT FLEXIBLE CONNECTION
11. PROVIDE AND INSTALL VOLUME DAMPERS ON SUPPLY, RETURN AND EXHAUST AIR BRANCH DUCTS AS REQUIRED FOR PROPER BALANCING OF THE SYSTEM. 12. INSTALL PIPING AND DUCTWORK OUT OF NATURAL WALKWAYS.
FLOW CONTROL VALVE (B & G CIRCUIT SETTER)
SPLITTER DAMPER
C
INFORMATION
I .FRANCO
TRANSITION DUCT
INFOR.
LOUI SVI LLE DI STRI CT
GAS COCK
CENTERLINE
LOUI SVI LLE,KENTUCKY
BALL VALVE
LINED DUCTWORK
C L
MEXI CO
DUCT WIDTH x DEPTH(INCHES)
LAS CRUCES,NEW
20 x 10
10. PREPARE AND SUBMIT PROFESSIONAL SHOP DRAWINGS TO THE CONTRACTING OFFICER FOR REVIEW AND APPROVAL PRIOR TO COMMENCEMENT OF ANY WORK.
Rev.
BDD
Mark
HEIGHT
Date:
EMERGENCY SHUTOFF VALVE
HT
072811
DIAPHRAGM VALVE DUCT SMOKE DETECTOR
BOTTOM OF UNIT
Desi gned by:
SD
BOU
Date
SOLENOID VALVE MOTORIZED LOW LEAKAGE DAMPER
Appr.
M
A.REED
S
Descri pti on
VOLUME DAMPER
CORPS OF ENGI NEERS
VD
Descri pti on
OPPOSED BLADE DAMPER
SHEET REFERENCE NUMBER:
SYMBOLS SHOWN HEREIN ARE UTILIZED.
M-0010 of 222
9:59:03
m oraja
AM
Sheet 121
1
2
*** Support Value Engineering - It Pays ***
4
5
CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11
1
*** Safety Pays ***
2
1
2
4
5
3 16
GENERAL NOTES
C4 HVU 1-1 M-5020
STAGING
ARMORER
AREA
WORK AREA
A110
A109
16
MATCH
19 SUPPLY
T
OFFICE A111
B
14 FC 3
D 21
17
20
23 20
ARMS
REFER TO MECHANICAL SCHEDULES ON SHEETS M-6000, M-6010 AND 6020.
3.
MAINTAIN COORDINATION OF SUPPLY DIFFUSERS AND RETURN AND EXHAUST REGISTERS WITH ARCHITECTURAL REFLECTED CEILING PLAN.
5.
FLEXIBLE DUCTWORK CONNECTIONS TO DIFFUSERS AND REGISTERS SHALL BE 6’-0" MAXIMUM IN LENGTH.
6.
INSULATE SUPPLY AND RETURN AIR DUCTWORK PER SPECIFICATIONS.
7.
MOUNT TEMPERATURE, HUMIDITY, C02 SENSORS ON WALL 4’-0" ABOVE FINISHED FLOOR. REFER TO CONTROL DRAWINGS.
8.
INTAKE LOUVERS TO BE A MINIMUM OF 10’-0" ABOVE FINISHED GRADE PER ATFP REQUIREMENTS.
9.
INTERLOCK SMOKE DETECTORS FOR UNIT SHUT DOWN.
HP 4
(TYP 3) T
2.
HP 3
VAULT
DH 1
A108
8x8 (TYP 3) 230 CFM (TYP 3)
UH 3
G
LOUISVILLE DISTRICT
4. PROVIDE VOLUME DAMPER FOR EVERY SUPPLY, RETURN AND EXHAUST BRANCH OUTLET.
FC 4
23
REFER TO SHEET M0010 FOR MECHANICAL SYMBOLS, NOTES AND ABBREVIATIONS.
Appr.
UH 4
1.
Date
A
SEE SHEET M-112A
LI NE
US Army Corps of Engineers
UH 6
Descri pti on
UH 5
10. PROVIDE FLEXIBLE DUCT CONNECTIONS TO MECHANICAL EQUIPMENT.
18
11. FOR EMERGENCY AIR DISTRIBUTION STOP SWITCH SEE M-112A
C
C2 EF 1-5 M-5020
UH 8
1
44x18 SA DUCT THRU WALL WITH FSD ONTO ROOF TO EC 1-1.
2
8x8 SS EA DUCT UTR TO EF 1-8 ON ROOF.
3
BLANK OFF UNUSED PORTIONS OF CONTINUOUS 1 1/2" SLOT DIFFUSER. CUSTOM BEND TO RADIUS OF CEILING SOFFIT.
4
14x12 WELDED GREASE DUCT IN 1-HOUR RATED SHAFT UTR SEE DETAIL A1
Appr.
UH 7
Mark
KEY NOTES
Date
M-5020
5
10x8 WELDED GREASE DUCT DN TO HOOD.
6
12x8 WELDED GREASE DUCT DN TO HOOD.
7
12x10 MAKE-UP AIR DUCT DN TO HOOD.
8
16x16 MAKE-UP AIR DUCT UTR.
9
36x24 RA DUCT UTR TO EC 1-1.
F C UH 2
UNIT STORAGE
10 24x14 SA DUCT UTR TO EC 1-6.
UH 1
A107
11 24x14 RA DUCT UTR TO EC 1-6. T
15
A
C2
C2 EF 1-6 M-5020
EF M-5020 1-7
14
Descri pti on
12 26x14 RA DUCT UTR TO EC 1-7. 100 CFM
13 26x14 SA DUCT UTR TO EC 1-7. 14
15
BELLMOUTH OPENING WITH WMS.
STORAGE
15 18x18 EA DUCT UTR TO RV ON ROOF.
A106
C
J
1100 CFM
17 ROUTE 3/8" RL AND 5/8" RS TO HP-3.
S
275 CFM (TYP 8)
C
16 18x18 OSA DUCT UTR TO IV ON ROOF.
TRANSFER DUCT
(TYP)
22
C
100 CFM
J
300 CFM
WEAPONS
20x18
18 12x12 EA DUCT UTR TO RV-3. 19 ROUTE 3/8" RL AND 5/8" RS TO HP-4. D3
20 MOUNT HP UNITS ON PLATFORM. FOR DETAIL SEE
CONTROL
SIMULATOR RM.
21 8x8 TRANSFER AIR OPENING IN WALL.
ROOM
A105A
22
A105B
8 1100 CFM
M-5020
C
C 4
20x18
300 CFM
PROVIDE CO2, RH, AND TEMPERATURE SENSOR MOUNTED ON WALL. D1
23
M-5010
GOOSENECK, SEE
Mark
A
100 CFM
12"
K
(TYP 4)
525 CFM (TYP 4)
C
ASSEMBLY A102
LI NE
26x18
MATCH
Q
C1 M-300A
B
A1 N
A2
ARC
ARC-FIRST FLOOR PLAN-SECTOR ONE KEY PLAN
SCALE :1/8"=1’-0"
N
7/22/2011
Pl ot scal e:AS NOTED
Pl ot date:
F-171-40-160
Project Code:
FAX (714) 327-1601 TEL (714) 327-1600
HUTTON CENTRE DRI VE,SUI TE 800
SANTA ANA, CALI FORNI A 92707
4
SHEET REFERENCE NUMBER:
M-111A Sheet 122
of 222
8:55:54
m oraja
AM
A1
W 912QR-11-R-0071
OMS
ARC-FI RST FLOOR PLAN-SECTOR ONE
A
U.S.ARMY
475 CFM
A
475 CFM
MECHANI CAL
A
A
RESERVE CENTER
26x18
700 CFM (TYP 3)
3
7/22/2011
c:\pwworki ng\gbna\m oraja\dm s97636\LCARC_M-111A.dgn
P
U.S.ARMY
A
640 CFM (TYP 5)
26x18
E
400 CFM
LOUI SVI LLE DI STRI CT
A
LOUI SVI LLE,KENTUCKY
22 A
450 CFM
CORPS OF ENGI NEERS
44x18
A103C
S 400 CFM
150 CFM
26x18
JANITOR
H
C
M .BETZ
22
SEE SHEET M-112A
1875 CFM (TYP 4)
FC 5
Subm i tted by:
36x24
Revi ewed by:
1
S
A.REED
A101
M 24
Sol i ci tati on No.
Rev.
LOBBY
OFFICE
10 A103B
2
C.KORPASH
9
MEXI CO
11
A1 M-301A
LAS CRUCES,NEW
25
75 CFM
Desi gned by:
D
150 CFM
Ckd by:
A
A104
Date:
CHAIR STORAGE
23
A103A
TABLE AND
Dwn by:
7
KITCHEN
072811
420 CFM A (TYP 5)
B
25 6x6 EA DUCT UTR TO EF-14
12
I .FRANCO
6
A.REED
DAC 1
13
Fi l e nam e:LCARC_M 111A. dgn
24 ROUTE 3/8" RL AND 5/8" RS TO HP-5
5
1
2
*** Support Value Engineering - It Pays ***
4
5
CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11
*** Safety Pays ***
2
4
5
6
7
4
8
9.8
9
5
10
11
US Army Corps of Engineers
1.
REFER TO SHEET M0010 FOR MECHANICAL SYMBOLS, NOTES AND ABBREVIATIONS.
2.
REFER TO MECHANICAL SCHEDULES ON SHEETS M-6000, M-6010 AND 6020.
3.
MAINTAIN COORDINATION OF SUPPLY DIFFUSERS AND RETURN AND EXHAUST REGISTERS WITH ARCHITECTURAL REFLECTED CEILING PLAN.
LOUISVILLE DISTRICT
Appr.
SEE SHEET M-111A
MATCH
LI NE
GENERAL NOTES
Date
1
D
11 C2
EF M-5020 1-1
VESTIBULE
VESTIBULE
A120B
A123B
C2 EF 1-2 M-5020 125
A
CFM
A
125
550
CFM
CFM
5.
FLEXIBLE DUCTWORK CONNECTIONS TO DIFFUSERS AND REGISTERS SHALL BE 6’-0" MAXIMUM IN LENGTH.
6.
INSULATE SUPPLY AND RETURN AIR DUCTWORK PER SPECIFICATIONS.
7.
MOUNT TEMPERATURE, HUMIDITY, C02 SENSORS ON WALL 4’-0" ABOVE FINISHED FLOOR. REFER TO CONTROL DRAWINGS.
8.
INTAKE LOUVERS TO BE A MINIMUM OF 10’-0" ABOVE FINISHED GRADE PER ATFP REQUIREMENTS.
9.
INTERLOCK SMOKE DETECTORS FOR UNIT SHUT DOWN.
Descri pti on
4. PROVIDE VOLUME DAMPER FOR EVERY SUPPLY, RETURN AND EXHAUST BRANCH OUTLET.
10. PROVIDE FLEXIBLE DUCT CONNECTIONS TO MECHANICAL EQUIPMENT.
A 11. FOR ENLARGE MECHANICAL ROOM PLAN SEE A1/M-400B
D
T UH 10 MECHANICAL
B
LOCKER
SD
24
15
M
12
D CFM EF
16
A113
14
SD
300
14x14
CFM
A
CFM
A
A112
SD
18
CAFE
E 250
16x14 WOMENS
900 CFM 14x12
CFM SD
TOILET
JANITORIAL
A115
14x12
I
MENS
SD
STORAGE
T
36x20 TRANSFER GRILLE WITH SMOKE DAMPER
5
12x12 EA DUCT UTR TO EF 1-12 AND DN TO E CFM
6
10x10 EA DUCT UTR TO EF 1-10
7
12x12 EA DUCT UTR TO EF 1-4
8
3/8"RL AND 5/8"RS UP TO HP-1 UNIT ON ROOF
9
3/8"RL AND 5/8" RS UP TO HP-2 UNIT ON ROOF
300
I
A124T
A121
21
19
TOILET
22x20
A119T
C
4
12x10
S
A M
40x18 SA AND RA DUCTS UTR TO EC 1-2 ON ROOF. TRANSITION TO UNIT OPENINGS AS REQUIRED WITHIN CURB.
20
SD
SIPRNET
3 SD
SD
SD
17
24x20 SA AND RA DUCTS UTR TO EC 1-4 ON ROOF. TRANSITION TO UNIT OPENINGS AS REQUIRED WITHIN CURB.
CFM
14x14
TER
A
10x14
18x18
22
550
A125
A124S 450
A122
18x18
M
13
MECH
A119S
(TYP2)
2
LOCKER
300 MENS CFM SHOWER
16x16
SHOWER
46x18 SA AND RA DUCTS UTR TO EC 1-3 ON ROOF. TRANSITION TO UNIT OPENINGS AS REQUIRED WITHIN CURB.
MENS
CFM
WOMENS
A118
600
I
1
CFM (TYP 3)
16x16
T SD
G FC 1-2
FC 1-1
21
20x16
8
B FACILITY MAINTENANCE
9
CFM
D
VESTIBULE 150 CFM A120A
325
(TYP 3)
A116
B
WOMENS
I
400
CFM
26
I
200
250
CFM
CFM
Mark
WOMENS
A117 23
100
Appr.
A114
KEY NOTES
12x12
Date
UH 9
ELECTRICAL
C
MENS VESTIBULE
595
C
CFM
540
595
C
CFM
10 EMERGENCY AIR DISTRIBUTION STOP SWITCH. KELE
CFM
ST120 BREAK GLASS TYPE. REFER TO CONTROL DIAGRAMS
(TYP 4)
25
A123A
(TYP 4)
H
11 48x24 EX LOUVER IN WALL. CONNECT EA PLENUM Descri pti on
TO EF 1-1, 1-2
S
12 16x16 OSA DUCT UTR TO IV-5 WITH MD 13 10x10 OSA DUCT UTR TO IV-3 WITH MD 24x20 (TYP)
14 18x18 OSA DUCT UTR TO IV-4 WITH MD 15 16x16 EA DUCT DN TO
D 1300 CFM, 12" AFF
16 10x10 EA DUCT DN TO
D 300 CFM
17 8x8 EA DUCT DN TO
D 200 CFM
18 8x8 OSA DUCT DN TO
B 200 CFM
INTERIOR PHYSICAL YARD READINESS
12"
A126
(TYP 8)
24x20
19 INTERIOR
A
CORRIDOR A150
RESTROOM
20
420
28x16 SA AND RA DUCTS UTR TO EC 1-5 ON ROOF. TRANSITION TO UNIT OPENINGS AS REQUIRED WITHIN CURB. PROVIDE TEMPERATURE AND RH WALL MOUNTED SENSOR.
CFM (TYP 8)
21 GOOSENECK, SEE
1
Mark
A146
C
A140
A137
A136
A133
A132
A130
A139
10
12"
J 375 CFM A
5
E J
E
4
46x20
(TYP)
10"
CFM
CFM
OFFICE
310 CFM
24x18
S
14" 12"
STORAGE
FSD
25 PROVIDE TEMPERATURE, CO2, AND RH WALL MOUNTED SENSOR
A1
8"
M-301A
26 10x10 EA DUCT UTR TO EF-13
M
A129
24x18
FSD
J
27 MOTORIZED EMERGENCY SHUTOFF DAMPER (LOW
100 CFM
FSD
25
D
LEAKAGE TYPE)
700 CFM
18x14 (TYP 4)
C 12" 24x14
300
27 J
12"0
300
A
400 CFM
UNIT
A143
C
A
3-WAY COMMON SPACE
CFM
$
J
J
10"
DUCT UTR TO EF
10"
A144
CFM
20
S
6"
CFM
240
E
C 1535
350
16" GENERAL
8"
20x18
24x14
A148
S
100 CFM 10"
10"
FSD
12"
14" TRAINING AID
FSD
8"
12"
8"
14x14 EA
FSD
46x14
(TYP)
400 CFM
CLASSROOM
CLASSROOM
A134
A131
UNIT EXCLUSIVE
1500 CFM (TYP 4)
46x18
SPACE
2-WAY A135
(TYP 6)
1535
400 CFM
CFM
3-WAY
10" 350
A
CFM
J
C
375
18x18
CFM
10"
(TYP) 24x18
34x18
(TYP)
A
350 CFM (TYP 8)
SORTING
J
ROOM A149A
10
300
18x12
A
CFM 10"
7/22/2011
F-171-40-160
350 CFM
(TYP 8)
B
OMS
A1
N
ARC
ARC-FIRST FLOOR PLAN-SECTOR TWO KEY PLAN
SCALE :1/8"=1’-0"
N
SHEET REFERENCE NUMBER:
M-112A Sheet 123
of 222
8:56:37
m oraja
AM
A1
A2
ARC-FI RST FLOOR PLAN-SECTOR TW O
U.S.ARMY
MATCH
SEE SHEET M-111A
LI NE
A
MECHANI CAL
A149B
MEXI CO
ROOM
LAS CRUCES,NEW
RESERVE CENTER
DISTRIBUTION
7/22/2011
c:\pwworki ng\gbna\m oraja\dm s97636\LCARC_M-112A.dgn
N
Pl ot scal e:AS NOTED
A138
A127
PUMP CONTROL PANEL WITH VFD’s AND CONTROLS, SECURED TO WALL
Pl ot date:
CENTER
SD
12"
CFM
STORAGE
$
330
CFM RETENTION
10"
210
READING
20x18
C
CFM
SPACE
A145
6
210
OFF. SPACE
24
FAX (714) 327-1601
12"
OFF. SPACE OFF. SPACE
CFM
TEL (714) 327-1600
8" ELEC
7
CFM
OFF. SPACE
A128
A147
240
LIBRARY
M .BETZ
A141
UNIT EXCLUSIVE
350
Subm i tted by:
A142
FULL TIME
J
HUTTON CENTRE DRI VE,SUI TE 800
OFF. SPACE
FULL TIME
AREA
SANTA ANA, CALI FORNI A 92707
OFF. SPACE
FULL TIME
STOR
4
SUPPORT
FULL TIME
FSD LEARNING
10"
BOILER CONTROL PANEL WITH 120V POWER, SECURED TO WALL
Project Code:
FULL TIME
FSD LIBRARY
BREAK
23
Revi ewed by:
FULL TIME
12" 8"
L
A.REED
26x14
FAMILY
12"
CFM
W 912QR-11-R-0071
18x16
TO WALL
CFM
Sol i ci tati on No.
CFM
22 DDC CONTROL PANEL WITH 120V POWER, SECURED
400
J
C.KORPASH
C
A
46x18
CFM 35
Ckd by:
CFM
(TYP 2)
100
35
Dwn by:
375
26x18
26x18
C
I .FRANCO
J
C
C
LOUI SVI LLE DI STRI CT
(TYP 6)
250 CFM
CFM
Rev.
12"
240 CFM
C
LOUI SVI LLE,KENTUCKY
C
CFM
Date:
3
2
M-5010
072811
10" (TYP)
EF 1-11
2
CFM
100
Desi gned by:
CFM
10"
UTR
A
310
A.REED
CFM
B
130
J
(TYP 6)
500
U.S.ARMY
330
C
CORPS OF ENGI NEERS
J
8" EA DUCT
240 CFM
Fi l e nam e:LCARC_M 112A. dgn
D1
K
1
2
*** Support Value Engineering - It Pays ***
4
5
CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11
1
*** Safety Pays ***
2
2
3 A5 UH 5 M-5000
UH M-5000 4
MATCH
1-1/4" HWS/R STAGING
ARMORER
AREA
WORK AREA
A110
A109
SUPPLY OFFICE
HVU 1-1
A111
B
US Army Corps of Engineers LOUISVILLE DISTRICT
1.
REFER TO SHEET M0010 FOR MECHANICAL SYMBOLS, NOTES AND ABBREVIATIONS.
2.
REFER TO MECHANICAL SCHEDULES ON SHEETS M-6000, M-6010 AND 6020.
3.
MAINTAIN COORDINATION OF SUPPLY DIFFUSERS AND RETURN AND EXHAUST REGISTERS WITH ARCHITECTURAL REFLECTED CEILING PLAN.
Appr.
A
SEE SHEET M-114A
GENERAL NOTES LI NE
3/4" HWS/R TO EA. UH (TYP)
A5
5
Date
1
4
4. PROVIDE VOLUME DAMPER FOR EVERY SUPPLY, RETURN AND EXHAUST BRANCH OUTLET. 1-1/2" HWS/R
D
5.
FLEXIBLE DUCTWORK CONNECTIONS TO DIFFUSERS AND REGISTERS SHALL BE 6’-0" MAXIMUM IN LENGTH.
6.
INSULATE SUPPLY AND RETURN AIR DUCTWORK PER SPECIFICATIONS.
7.
MOUNT TEMPERATURE, HUMIDITY, C02 SENSORS ON WALL 4’-0" ABOVE FINISHED FLOOR. REFER TO CONTROL DRAWINGS.
8.
INTAKE LOUVERS TO BE A MINIMUM OF 10’-0" ABOVE FINISHED GRADE PER ATFP REQUIREMENTS.
9.
INTERLOCK SMOKE DETECTORS FOR UNIT SHUT DOWN.
VAULT A108
A5
UH M-5000 3
A5
UH 6 M-5000
Descri pti on
ARMS
10. PROVIDE FLEXIBLE DUCT CONNECTIONS TO MECHANICAL EQUIPMENT.
C
3/4" HWS/R
KEY NOTES 1
UH 7
2-1/2" HWS/R
1" HWS/R
1" HWS/R
1" HWS/R
4
2 (TYP)
1-1/4" HWS/R
1" HWS/R PIPING UTR TO EC 1-7. ROUTE PIPING THRU ROOF CURB.
3
1" HWS/R PIPING UTR TO EC 1-6. ROUTE PIPING THRU ROOF CURB.
4
FOR PIPE HANGER DETAILS SEE
Mark
UH 8
1-1/4" HWS/R PIPING UTR TO EC 1-1. ROUTE PIPING THRU ROOF CURB.
D3
D5 Appr.
1-1/2" HWS/R
Date
M-5010 M-5010
F 3/4" HWS/R
C
U H 2
A5 D5 SEE FOR PIPE HANGER DETAIL M-5010
M-5000
A5 UH 1 M-5000
UNIT STORAGE
Descri pti on
A107
STORAGE A106
J
WEAPONS CONTROL
SIMULATOR RM.
ROOM
A105A
2-1/2" HWS/R (TYP)
Mark
4
A105B
ASSEMBLY A102
7/22/2011 Pl ot date:
Pl ot scal e:AS NOTED TEL (714) 327-1600
FAX (714) 327-1601
M .BETZ
Subm i tted by:
F-171-40-160
Project Code:
HUTTON CENTRE DRI VE,SUI TE 800
U.S.ARMY
A103C
LOUI SVI LLE DI STRI CT
CORPS OF ENGI NEERS
JANITOR
SANTA ANA, CALI FORNI A 92707
M
4
1
Revi ewed by:
Desi gned by:
A103B
A.REED
A101
OFFICE
A.REED
LOBBY
W 912QR-11-R-0071
(TYP)
C.KORPASH
4
Ckd by:
2" HWS/R
Dwn by:
A104
3
Date:
CHAIR STORAGE
A103A
072811
TABLE AND
KITCHEN
I .FRANCO
B
LOUI SVI LLE,KENTUCKY
1-1/2" HWS/R
Sol i ci tati on No.
Rev.
2
Fi l e nam e:LCARC_M 113A. dgn
K
A1 N
A2
ARC
ARC-FIRST FLOOR PIPING PLAN-SECTOR ONE KEY PLAN
SCALE :1/8"=1’-0"
N
MECHANI CAL
SHEET REFERENCE NUMBER:
M-113A Sheet 124
of 222
8:57:18
m oraja
AM
A1
MEXI CO
OMS
ARC-FI RST FLOOR PI PI NG PLAN-SECTOR ONE
B
LAS CRUCES,NEW
RESERVE CENTER
MATCH
U.S.ARMY
Q
SEE SHEET M-114A
LI NE
A
7/22/2011
c:\pwworki ng\gbna\m oraja\dm s97636\LCARC_M-113A.dgn
P
1
2
*** Support Value Engineering - It Pays ***
4
5
CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11
1
*** Safety Pays ***
2
4
5
6
7
4
8
9.8
9
5
10
11
US Army Corps of Engineers
REFER TO SHEET M0010 FOR MECHANICAL SYMBOLS, NOTES AND ABBREVIATIONS.
2.
REFER TO MECHANICAL SCHEDULES ON SHEETS M-6000, M-6010 AND 6020.
3.
MAINTAIN COORDINATION OF SUPPLY DIFFUSERS AND RETURN AND EXHAUST REGISTERS WITH ARCHITECTURAL REFLECTED CEILING PLAN.
LOUISVILLE DISTRICT
Appr.
1.
Date
SEE SHEET M-113A
MATCH
LI NE
GENERAL NOTES
5.
FLEXIBLE DUCTWORK CONNECTIONS TO DIFFUSERS AND REGISTERS SHALL BE 6’-0" MAXIMUM IN LENGTH.
6.
INSULATE SUPPLY AND RETURN AIR DUCTWORK PER SPECIFICATIONS.
7.
MOUNT TEMPERATURE, HUMIDITY, C02 SENSORS ON WALL 4’-0" ABOVE FINISHED FLOOR. REFER TO CONTROL DRAWINGS.
8.
INTAKE LOUVERS TO BE A MINIMUM OF 10’-0" ABOVE FINISHED GRADE PER ATFP REQUIREMENTS.
9.
INTERLOCK SMOKE DETECTORS FOR UNIT SHUT DOWN.
D
A5 UH 9 M-5000
VESTIBULE
VESTIBULE
A120B
A123B
A5 UH 10 M-5000
Descri pti on
4. PROVIDE VOLUME DAMPER FOR EVERY SUPPLY, RETURN AND EXHAUST BRANCH OUTLET.
10. PROVIDE FLEXIBLE DUCT CONNECTIONS TO MECHANICAL EQUIPMENT.
KEY NOTES
ELECTRICAL
1
MECHANICAL
3/4" HWS/R
WOMENS
A117
3/4" HWS/R
2 1/2" HWS/R
LOCKER A118
MENS WOMENS
MENS
SHOWER
SHOWER
6 (TYP)
MECH
A119S
LOCKER A125
2
1 -1/4" HWS/R PIPING UTR TO EC 1-3. ROUTE PIPING WITHIN ROOF CURB.
3
1 " HWS/R PIPING UTR TO EC 1-4. ROUTE PIPING WITHIN ROOF CURB.
4
1 -1/4" HWS/R PIPING UTR TO EC 1-5. ROUTE PIPING WITHIN ROOF CURB.
A124S
A122
EF
1 -1/4" HWS/R PIPING UTR TO EC 1-2. ROUTE PIPING WITHIN ROOF CURB.
Mark
A114
Appr.
A113
5
SIPRNET TER
CAFE
A112
A115
WOMENS 1 1/4" TOILET HWS/R A119T
2 1/2" HWS/R
C
4
MENS
JANITORIAL
M-400A
TOILET
STORAGE
3" HWS/R PIPING POC, FOR CONT. SEE ENLARGED DWG A1
6
FOR PIPE HANGING DETAILS SEE
A124T
A121
WOMENS
MENS
MAINTENANCE
VESTIBULE
VESTIBULE
A116
A120A
A123A
D5
D3
M-5010
M-5010
Descri pti on
FACILITY
Date
5
INTERIOR PHYSICAL YARD READINESS A126
INTERIOR CORRIDOR A150
RESTROOM
A140
A139
LEARNING
OFF. SPACE
OFF. SPACE
SPACE
READING
STORAGE
CENTER
A138
A137
A136
A133
A132
A130
A145
A128
A127
TRAINING AID STORAGE
1-1/2" HWS/R
A129
7/22/2011
F-171-40-160
AREA
W 912QR-11-R-0071
STOR
Pl ot scal e:AS NOTED
LIBRARY
Pl ot date:
LIBRARY
M .BETZ
A141
ELEC
UNIT EXCLUSIVE
Subm i tted by:
A142
A147
OFF. SPACE OFF. SPACE
FULL TIME
Project Code:
OFF. SPACE
FULL TIME
Revi ewed by:
OFF. SPACE
FULL TIME
A.REED
SUPPORT
FULL TIME
C.KORPASH
FULL TIME
Ckd by:
Date:
FULL TIME
Desi gned by:
FAMILY
A.REED
BREAK
2" HWS/R
072811
6 (TYP)
Dwn by:
1
B
I .FRANCO
1" HWS/R
Sol i ci tati on No.
Rev.
3
2
Fi l e nam e:LCARC_M 114A. dgn
Mark
A146
SPACE
COMMON SPACE
A135
SORTING
A149A
U.S.ARMY
MATCH
SEE SHEET M-113A
LI NE
A
B
OMS
A1
N 8:57:56 AM
m oraja
A1
MECHANI CAL
A149B
MEXI CO
ROOM
LAS CRUCES,NEW
RESERVE CENTER
DISTRIBUTION
A2
ARC
ARC-FIRST FLOOR PIPING PLAN-SECTOR TWO KEY PLAN
SCALE :1/8"=1’-0"
1
2
*** Support Value Engineering - It Pays ***
4
5
N
ARC-FI RST FLOOR PI PI NG PLAN-SECTOR TW O
ROOM
7/22/2011
c:\pwworki ng\gbna\m oraja\dm s97636\LCARC_M-114A.dgn
A143
FAX (714) 327-1601
A131
TEL (714) 327-1600
UNIT
A134
HUTTON CENTRE DRI VE,SUI TE 800
UNIT EXCLUSIVE
CLASSROOM
SANTA ANA, CALI FORNI A 92707
A144
CLASSROOM
4
OFFICE
U.S.ARMY
GENERAL
LOUI SVI LLE DI STRI CT
A148
LOUI SVI LLE,KENTUCKY
CORPS OF ENGI NEERS
RETENTION
SHEET REFERENCE NUMBER:
M-114A Sheet 125
of 222
CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11
1
*** Safety Pays ***
2
4
5
GENERAL NOTES REFER TO SHEET M0010 FOR MECHANICAL SYMBOLS, NOTES AND ABBREVIATIONS. REFER TO MECHANICAL SCHEDULES ON SHEETS M-6000, M-6010 AND 6020.
3.
MAINTAIN COORDINATION OF SUPPLY DIFFUSERS AND RETURN AND EXHAUST REGISTERS WITH ARCHITECTURAL REFLECTED CEILING PLAN.
Appr.
2.
LOUISVILLE DISTRICT
Date
1.
US Army Corps of Engineers
1
2
3
4
5.
FLEXIBLE DUCTWORK CONNECTIONS TO DIFFUSERS AND REGISTERS SHALL BE 6’-0" MAXIMUM IN LENGTH.
6.
INSULATE SUPPLY AND RETURN AIR DUCTWORK PER SPECIFICATIONS.
7.
MOUNT TEMPERATURE, HUMIDITY, C02 SENSORS ON WALL 4’-0" ABOVE FINISHED FLOOR. REFER TO CONTROL DRAWINGS.
8.
INTAKE LOUVERS TO BE A MINIMUM OF 10’-0" ABOVE FINISHED GRADE PER ATFP REQUIREMENTS.
9.
INTERLOCK SMOKE DETECTORS FOR UNIT SHUT DOWN.
D
24x24 EA LOUVER, 50% FA, BIRDSCREEEN. SEE ARCH FOR DETAIL
ELEC
MECH
24x24 EA LOUVER, 50% FA, DETAIL
A5
UH 12
B102
BIRDSCREEEN. SEE ARCH FOR
C2 EF 2-4 M-5020
B103
M-5000
FOR ENLARGED PLAN SEE
27
A1
10. PROVIDE FLEXIBLE DUCT CONNECTIONS TO MECHANICAL EQUIPMENT.
C2
EF 2-2 M-5020
M-400B
Descri pti on
4. PROVIDE VOLUME DAMPER FOR EVERY SUPPLY, RETURN AND EXHAUST BRANCH OUTLET.
11. FOR SOLAR HEAT PIPING INSIDE MECHANICAL ROOM SEE ENLARGED PLAN A1
24
M-400B
A T
KEY NOTES 9
29 EF 2-7 M-5020
A5
UH M-5000 11
AREA 23
16
23
B101B
2
7
26
C2
EF 2-3 M-5020
20x16
3
17
23
15
C5 2 AND FOR UNDERSLAB RADIANT HEATING DETAIL SEE M-5000 M-7000
EMERGENCY AIR DISTRIBUTION STOP SWITCH. KELE ST120 BREAK GLASS TYPE. REFER TO CONTROL DRAWINGS.
3
18 8
T
VX 2-2
VENTILATOR.
14
20
Mark
STAGING
1
C2
4
36x36 MAKE-UP DUCT AIR FOR CAR EXHAUST. 2800 CFM MAX. COVER WITH 1/2" WELDED WIRE MESH.
5
FOUR BUTTON MOUNTED CONTROL STATION FOR CAR EXHAUST SYSTEM.
6
12x12 OUTSIDE AIR UP TO INTAKE VENTILATOR ON ROOF. GD 1 CARBON MONOXIDE AND NO2 CONTROLLER
F 645 CFM
Appr.
T
SD CFM 250
B105
C
CFM
C
5
EQUIPMENT ALCOVE
A
25
SD
STOR
7
16x14
J
19
F 640 CFM
WORK
250
B104 CFM
WITH LOCAL ALARM STROBE. REFER TO CONTROL DRAWINGS
20x16
BAYS B116
200
J CFM
SD EF 2-6
21 C
200 CFM
EF 2-5
11 10x10 TRANSFER GRILLE.
CFM
12 13
SD
100 CFM
TOOLS B107
CFM
10
18
PUMP CONTROL PANEL WITH VFD’S AND CONTROLS.
19
20x16 RAD UTR TO EC2-1.
FLOOR RADIANT
C
ROUTED WITHIN PIPE CHASE OF UNIT.
SHOP
5 23 FULLSIZE EA DUCT WITH BELLMOUT OPENING AND
300
CFM
CFM
8
J
VX 2-1
3/4" HWS/R TO UNIT HEATERS (TYP).
25 DDC CONTROL PANEL WITH 120 V POWER 9
SECURED TO WALL.
26 BOILER CONTROL PANEL WITH 120 V POWER
OFFICE
C
B112
J
200 CFM
200
SECURED TO WALL.
3
CFM
J
27 WALL MOUNT UNDERSLAB RADIANT HEATING
20x16
VALVE MANIFOLD.
320
28 PROVIDE C02, RH, AND TEMPERATURE SENSOR
CFM
MOUNTED ON WALL.
C
U.S.ARMY
29 ROUTE UNDERSLAB RADIANT HEATING PIPING
LOUI SVI LLE DI STRI CT
SHOP
B110
320
24
CORPS OF ENGI NEERS
F
Desi gned by:
UTR
A.REED
WMS.
F 645 CFM OFFICE
BELOW WALL AND AROUND CONCRETE FOOTINGS. C2
EF M-5020 2-1
7/22/2011 Pl ot date:
Pl ot scal e:AS NOTED FAX (714) 327-1601
22 1-1/2" HWS/R PIPING UP THRU ROOF. PIPE
$
TEL (714) 327-1600
CFM
Date:
300
Fi l e nam e:LCARC_M 110B. dgn
WITHIN PIPE CHASE OF UNIT.
2
M .BETZ
21 3/4" HWS/R PIPING UP THRU ROOF. PIPE ROUTED
Subm i tted by:
B115
B114
HUTTON CENTRE DRI VE,SUI TE 800
B
SANTA ANA, CALI FORNI A 92707
VESTIBULE F 640 CFM
CFM HALL
4
B113
CFM
110
WATER PIPING TO MECHANICAL EQUIPMENT. FOR A1 ENLARGED PLAN SEE M-400B
1
HVU 2-1
A
F-171-40-160
120
20 1-1/2" HWS/R PIPING POC FOR HEATING HOT
Project Code:
11 A
ZONE
11
28
CFM
Revi ewed by:
180
HEATING
A.REED
T
W 912QR-11-R-0071
4
Mark
FSD
S
VESTIBULE
12x12 OSA DUCT UTR TO IV-6 ON ROOF.
22
100 CFM
A
17
Sol i ci tati on No.
A
16x16 OSA DUCT UTR TO IV-7 ON ROOF.
C.KORPASH
B
16
Ckd by:
J
18x14
DUCT UTR
300
Dwn by:
CFM
16x16 OSA DUCT DOWN TO 6" AFF WITH 1/2" WIRE MESH SCREEN IN ELECTRICAL ROOM.
24x24 DN
430
14x14 OSA
15
I .FRANCO
13
WIRE MESH SCREEN. SD
LOUI SVI LLE,KENTUCKY
C
14 12x12 OSA DUCT DOWN TO 6" AFF WITH 1/2"
F 640 CFM
Rev.
16"
MEN’S B109
24x24 THRU WALL TO HVU 2-1 ON ROOF. SEE M-130B FOR CONT.
072811
M-300B
10
300
TR
B106
A
B101A
20x16 DOWN TO 12" AFF. COVER INLET WITH 1/2" WELDED WIRE MESH. 1920 CFM.
12 20x20 SAD UTR TO EC 2-1 ON ROOF.
B108
A1
9
C
20x20
STORAGE
WOMEN’S
C2 VEHICLE EXHAUST FAN, COORDINATE WITH M-5000 OVERHEAD CRANE SYSTEM. FOR DETAIL SEE
SD
F 640 CFM
UNHEATED
8
Descri pti on
190
Date
EAD UTR
7/22/2011
B
OMS
A1
A1
OMS-FLOOR PLAN SCALE :1/4"=1’-0"
A2
ARC
8:54:51 AM
KEY PLAN
m oraja
U.S.ARMY
A
MECHANI CAL
RESERVE CENTER
B111
OMS-FLOOR PLAN
OFFICE MEXI CO
M-300B
LAS CRUCES,NEW
C1
N
c:\pwworki ng\gbna\m oraja\dm s97636\LCARC_M-110B.dgn
SHOP
1
2
*** Support Value Engineering - It Pays ***
4
5
N
SHEET REFERENCE NUMBER:
M-110B Sheet 126
of 222
CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11
*** Safety Pays ***
2
B2 IV 1 M-5000
A
5
GENERAL NOTES 4 1.
18x18 OSA DUCT DN
REFER TO SHEET M0010 FOR MECHANICAL SYMBOLS, NOTES AND ABBREVIATIONS.
2.
REFER TO MECHANICAL SCHEDULES ON SHEETS M-6000, M-6010 AND 6020.
3.
MAINTAIN COORDINATION OF SUPPLY DIFFUSERS AND RETURN AND EXHAUST REGISTERS WITH ARCHITECTURAL REFLECTED CEILING PLAN.
US Army Corps of Engineers LOUISVILLE DISTRICT
Appr.
B2 IV 2 M-5000
4
Date
3 LI NE
2
MATCH
4. PROVIDE VOLUME DAMPER FOR EVERY SUPPLY, RETURN AND EXHAUST BRANCH OUTLET.
B
D
5.
FLEXIBLE DUCTWORK CONNECTIONS TO DIFFUSERS AND REGISTERS SHALL BE 6’-0" MAXIMUM IN LENGTH.
6.
INSULATE SUPPLY AND RETURN AIR DUCTWORK PER SPECIFICATIONS.
7.
MOUNT TEMPERATURE, HUMIDITY, C02 SENSORS ON WALL 4’-0" ABOVE FINISHED FLOOR. REFER TO CONTROL DRAWINGS.
8.
INTAKE LOUVERS TO BE A MINIMUM OF 10’-0" ABOVE FINISHED GRADE PER ATFP REQUIREMENTS.
9.
INTERLOCK SMOKE DETECTORS FOR UNIT SHUT DOWN. Descri pti on
1
SEE SHEET M-121A
1
10. PROVIDE FLEXIBLE DUCT CONNECTIONS TO MECHANICAL EQUIPMENT. B2 RV 3 M-5000
12x12 EA DUCT DN
C
KEY NOTES 1 14x12 WELDED GREASE EXHAUST DUCT DN THRU ROOF 2
TERMINATE 14x12 WELDED GREASE EXHAUST DUCT 40" DUCT THRU WALL SEE
A1
4
24x14 SA AND RA DUCTS DN THRU ROOF
5
16x16 MAKE-UP AIR DUCT DN THRU ROOF
6
26x14 SA AND RA DUCTS DN THRU ROOF
7
36x24 RA DUCT DN THRU ROOF
Appr.
REFRIGERANT PIPING DN THRU ROOF
Date
3
Mark
M-5020
D2
8
44x18 SA DUCT DN THRU WALL SEE M-5010
9
PROVIDE MINIMUM OF 42" CLEARANCE FOR ACCESS TO HIGH VOLTAGE VFD’S, MOTOR CONTROLS, AND PANELS, ETC ALL ACCESSED FROM ONE SIDE OF THE UNIT.
F C
10 PROVIDE MINIMUM OF 30" CLEAR ON OPPOSITE SIDE OF UNIT. NO EQUIPMENT OR COMPONENTS THAT REQUIRE MAINTENANCE SHALL BE INSTALLED ON THIS SIDE OF THE UNIT. ALL ACCESS SHALL BE FROM INSIDE THE UNIT.
11 PROVIDE MINIMUM OF 18" CLEAR ON OPPOSITE SIDE OF UNIT.
18x18 EA DUCT DN
18x18 EA DUCT DN
B2 RV 1 M-5000
B2 RV 2 M-5000
Descri pti on
NO EQUIPMENT OR COMPONENTS THAT REQUIRE MAINTENANCE SHALL BE INSTALLED ON THIS SIDE OF THE UNIT. ALL ACCESS SHALL BE FROM INSIDE THE UNIT.
12 6x6 EA DUCT DN
J
A1 EF 1-9 M-5020
A1 KSF 1-1 M-5020
C1 EC 1-7 M-5020
2
7/22/2011
Pl ot scal e:AS NOTED TEL (714) 327-1600
F-171-40-160
Pl ot date:
FAX (714) 327-1601
M .BETZ
Subm i tted by:
C.KORPASH
Project Code:
HUTTON CENTRE DRI VE,SUI TE 800
U.S.ARMY
4
CORPS OF ENGI NEERS
8x8 EA DUCT DN
Revi ewed by:
Ckd by:
8
C1 EC 1-6 M-5020
MATCH
LI NE
Q
SECTOR ONE
AND LOW ER ROOF PLAN -
ARC-OVERALL PLENUM
LEVEL
MEXI CO
OMS
A1 A2
ARC
ARC-OVERALL PLENUM LEVEL AND LOWER ROOF PLAN - SECTOR ONE KEY PLAN
SCALE :1/8"=1’-0"
N
SHEET REFERENCE NUMBER:
M-120A Sheet 127
of 222
8:58:33
m oraja
AM
A1
SEE SHEET M-121A
7/22/2011
B
MECHANI CAL
U.S.ARMY
A
LAS CRUCES,NEW
RESERVE CENTER
P
N
c:\pwworki ng\gbna\m oraja\dm s97636\LCARC_M-120A.dgn
Dwn by:
10
LOUI SVI LLE DI STRI CT
4
Desi gned by:
EF M-5000 1-8
A.REED
C1 EC 1-1 M-5020
B4
M
I .FRANCO
EF
M-5000 1-14
A.REED
9
12
LOUI SVI LLE,KENTUCKY
B5
6
Date:
7
3
072811
9 9
W 912QR-11-R-0071
HP 5
B
Sol i ci tati on No.
Rev.
K
Fi l e nam e:LCARC_M 120A. dgn
11
SANTA ANA, CALI FORNI A 92707
5
Mark
1
1
2
*** Support Value Engineering - It Pays ***
4
5
CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11
1
*** Safety Pays ***
2
4
5
GENERAL NOTES 6
7
8
9.8
9
10
11 1.
REFER TO SHEET M0010 FOR MECHANICAL SYMBOLS, NOTES AND ABBREVIATIONS.
2.
REFER TO MECHANICAL SCHEDULES ON SHEETS M-6000, M-6010 AND 6020.
3.
MAINTAIN COORDINATION OF SUPPLY DIFFUSERS AND RETURN
US Army Corps of Engineers
Appr.
LOUISVILLE DISTRICT
AND EXHAUST REGISTERS WITH ARCHITECTURAL REFLECTED CEILING PLAN.
Date
MATCH
5
SEE SHEET M-120A
4
LI NE
3
4. PROVIDE VOLUME DAMPER FOR EVERY SUPPLY, RETURN AND EXHAUST BRANCH OUTLET. FLEXIBLE DUCTWORK CONNECTIONS TO DIFFUSERS AND REGISTERS SHALL BE 6’-0" MAXIMUM IN LENGTH.
6.
INSULATE SUPPLY AND RETURN AIR DUCTWORK PER SPECIFICATIONS.
7.
MOUNT TEMPERATURE, HUMIDITY, C02 SENSORS ON WALL 4’-0" ABOVE FINISHED FLOOR. REFER TO CONTROL DRAWINGS.
8.
INTAKE LOUVERS TO BE A MINIMUM OF 10’-0" ABOVE FINISHED GRADE PER ATFP REQUIREMENTS.
9.
INTERLOCK SMOKE DETECTORS FOR UNIT SHUT DOWN. Descri pti on
D
5.
10. PROVIDE FLEXIBLE DUCT CONNECTIONS TO MECHANICAL EQUIPMENT.
KEY NOTES
B2 IV 5 M-5000
B2 IV 3 M-5000
18x18 OSA DUCT DN
SOLAR HEATING COLLECTORS (TYP) SEE A1
3
18x46 SA AND RA DUCTS DTR
4
16x28 SA AND RA DUCTS DTR
M-5010
M-400A
10x10 OSA DUCT DN
6
PROVIDE MINIMUM OF 42" CLEARANCE FOR HIGH VOLTAGE VFD’S, MOTOR CONTROLS, AND PANELS, ETC. ALL ACCESSED FROM ONE SIDE OF THE UNIT.
7
PROVIDE MINIMUM OF 30" CLEARANCE ON OPPOSITE SIDE OF UNIT. NO EQUIPMENT OR COMPONENTS THAT REQUIRE MAINTENANCE SHALL BE INSTALLED ON THIS SIDE OF THE UNIT. ALL ACCESS SHALL BE FROM INSIDE THE UNIT.
E HP 2
C1 EC 1-5 M-5020
6
10x10 EA DUCT DN
HP 1
D1
5
C 6
B5
EF M-5000 1-13
Appr.
B2 IV 4 M-5000
18x26 SA AND RA DUCTS DTR
Date
16x16 OSA DUCT HD 1 DN
2
Mark
1 18x40 SA AND RA DUCTS DTR
D
7
G
D1
D1
M-5010
M-5010
4
M-5000 Descri pti on
DTR
DUCT DTR
RS/RL PIPES DTR SEE D3
Mark
H
2
7/22/2011
Pl ot scal e:AS NOTED
F-171-40-160
Project Code:
Pl ot date:
FAX (714) 327-1601
CORPS OF ENGI NEERS U.S.ARMY
TEL (714) 327-1600
M 10x10 EA DUCT DN
M .BETZ
6
Subm i tted by:
B5 EF 1-3 M-5000
HUTTON CENTRE DRI VE,SUI TE 800
EC 1-3 M-5020
SANTA ANA, CALI FORNI A 92707
1
12x12 EA DUCT DN
C1
4
C1 EC 1-4 M-5020
6
W 912QR-11-R-0071
6
LOUI SVI LLE DI STRI CT
B5 EF 1-12 M-5000
6
Revi ewed by:
12x12 EA DUCT DN
12x12 EA DUCT DN
CONDENSING UNIT PART OF EC 1-2
A.REED
CU 1
LOUI SVI LLE,KENTUCKY
EF M-5000 1-4
Desi gned by:
7
B5 EF 1-10 M-5000
B5
C.KORPASH
L
Ckd by:
Date:
6 072811
5
Dwn by:
C1 EC 1-2 M-5020
A.REED
B
I .FRANCO
7
Sol i ci tati on No.
Rev.
K
Fi l e nam e:LCARC_M 121A. dgn
3
SECTOR TW O
AND LOW ER ROOF PLAN -
ARC-OVERALL PLENUM
MECHANI CAL
LEVEL
MEXI CO
OMS
A1 A2
ARC
ARC-OVERALL PLENUM LEVEL AND LOWER ROOF PLAN - SECTOR TWO KEY PLAN
SCALE :1/8"=1’-0"
N
SHEET REFERENCE NUMBER:
M-121A Sheet 128
of 222
8:59:15
m oraja
AM
A1
SEE SHEET M-120A
MATCH
LI NE
7/22/2011
B
LAS CRUCES,NEW
RESERVE CENTER U.S.ARMY
A
N
c:\pwworki ng\gbna\m oraja\dm s97636\LCARC_M-121A.dgn
N
1
2
*** Support Value Engineering - It Pays ***
4
5
CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11
1
*** Safety Pays ***
2
4
5
US Army Corps of Engineers
GENERAL NOTES
LOUISVILLE DISTRICT
REFER TO SHEET M0010 FOR MECHANICAL SYMBOLS, NOTES AND ABBREVIATIONS.
2.
REFER TO MECHANICAL SCHEDULES ON SHEETS M-6000, M-6010 AND 6020.
3.
MAINTAIN COORDINATION OF SUPPLY DIFFUSERS AND RETURN AND EXHAUST REGISTERS WITH ARCHITECTURAL REFLECTED CEILING PLAN.
Date
Appr.
1.
1
2
3
4. PROVIDE VOLUME DAMPER FOR EVERY SUPPLY, RETURN AND EXHAUST BRANCH OUTLET.
4
5.
FLEXIBLE DUCTWORK CONNECTIONS TO DIFFUSERS AND REGISTERS SHALL BE 6’-0" MAXIMUM IN LENGTH.
6.
INSULATE SUPPLY AND RETURN AIR DUCTWORK PER SPECIFICATIONS.
7.
MOUNT TEMPERATURE, HUMIDITY, C02 SENSORS ON WALL 4’-0" ABOVE FINISHED FLOOR. REFER TO CONTROL DRAWINGS.
8.
INTAKE LOUVERS TO BE A MINIMUM OF 10’-0" ABOVE FINISHED GRADE PER ATFP REQUIREMENTS.
9.
INTERLOCK SMOKE DETECTORS FOR UNIT SHUT DOWN.
Descri pti on
D
10. PROVIDE FLEXIBLE DUCT CONNECTIONS TO MECHANICAL EQUIPMENT.
A
KEY NOTES B2
IV M-5000 7
1 3/4" HWS/R PIPING FROM BELOW PIPE SHALL
2
B2 RV 7 M-5000
1-1/2" HWS/R PIPING FROM BELOW. PIPE SHALL BE ROUTED INSIDE PIPE CHASE OF UNIT.
3
Mark
B2 IV 6 M-5000
16x16 DN
BE ROUTED INSIDE PIPE CHASE OF UNIT
B2 RV 5 M-5000
PROVIDE MINIMUM OF 42" CLEARANCE FOR Appr.
ACCESS TO HIGH VOLTAGE VFD’S, MOTOR CONTROLS, AND PANELS, ETC ALL ACCESSED
12x12 DN
Date
FROM ONE SIDE OF THE UNIT.
3 DN
4
OPPOSITE SIDE OF UNIT. NO EQUIPMENT OR
16x20 RA DUCT
C
PROVIDE MINIMUM OF 12" CLEARANCE ON COMPONENTS THAT REQUIRE MAINTENANCE SHALL
DTR
BE INSTALLED ON THIS SIDE OF THE UNITS. ALL ACCESS SHALL BE FROM INSIDE THE UNIT.
5
EC 2-1 SHALL HAVE ECONOMIZER OUTSIDE AIR INLET ONLY ON THIS SIDE OF UNIT.
C1 EC 2-1 M-5020
Descri pti on
1
5
20x20 SA DUCT DTR
IV 8
B2 M-5000
4 EXHAUST AIR DUCT ROOF
3 24x24 THRU WALL
CAP (TYP)
14x14 DN
D2
M-5010
IV 9
B2 M-5000
B
B
OMS-ROOF PLAN
N
A1
A2
SCALE :1/4"=1’-0" ARC KEY PLAN
8:59:50 AM
7/22/2011 Pl ot date:
Pl ot scal e:AS NOTED TEL (714) 327-1600
FAX (714) 327-1601
M .BETZ
Subm i tted by: HUTTON CENTRE DRI VE,SUI TE 800
OMS-ROOF PLAN
4
SANTA ANA, CALI FORNI A 92707
F-171-40-160
Project Code:
Revi ewed by:
C.KORPASH
A.REED
Ckd by: Dwn by:
OMS
A1
m oraja
MECHANI CAL
U.S.ARMY
RESERVE CENTER U.S.ARMY
A
7/22/2011
c:\pwworki ng\gbna\m oraja\dm s97636\LCARC_M-130B.dgn
C
MEXI CO
RV M-5000 4
LOUI SVI LLE DI STRI CT
CORPS OF ENGI NEERS
B2
LAS CRUCES,NEW
Desi gned by:
RV 6 M-5000
A.REED
B2
LOUI SVI LLE,KENTUCKY
Date:
072811
3
I . FRANCO
Sol i ci tati on No.
OUTSIDE AIR HOOD
B
W 912QR-11-R-0071
Rev.
C1 HVU 2-1 M-5020
Fi l e nam e:LCARC_M 130B. dgn
Mark
2
1
2
*** Support Value Engineering - It Pays ***
4
5
N
SHEET REFERENCE NUMBER:
M-130B Sheet 129
of 222
CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11
*** Safety Pays ***
2
4
5
GENERAL NOTES
K
M
P
Q
US Army Corps of Engineers
1.
REFER TO SHEET M0010 FOR MECHANICAL SYMBOLS, NOTES AND ABBREVIATIONS.
2.
REFER TO MECHANICAL SCHEDULES ON SHEETS M-6000, M-6010 AND 6020.
3.
MAINTAIN COORDINATION OF SUPPLY DIFFUSERS AND RETURN AND EXHAUST REGISTERS WITH ARCHITECTURAL REFLECTED CEILING PLAN.
GREASE
LOUISVILLE DISTRICT
Appr.
1
A1
WALL SEE
C1 EC 1-6 M-5020
M-5020
Date
DUCT THRU
DISCHARGE DUCT 40" ABV ROOF
A1 KSF 1-1 M-5020
D
A1 EF 1-9 M-5020 (BEYOND) 16x16
1" HWS/R
MAKE-UP
TO EC 1-6
AIR DUCT DTR
E
26x18 SA
DUCT
E
640 CFM
26x18 SA DUCT
DUCT
6.
INSULATE SUPPLY AND RETURN AIR DUCTWORK PER SPECIFICATIONS.
7.
MOUNT TEMPERATURE, HUMIDITY, C02 SENSORS ON WALL 4’-0" ABOVE FINISHED FLOOR. REFER TO CONTROL DRAWINGS.
8.
INTAKE LOUVERS TO BE A MINIMUM OF 10’-0" ABOVE FINISHED GRADE PER ATFP REQUIREMENTS.
9.
INTERLOCK SMOKE DETECTORS FOR UNIT SHUT DOWN.
640 CFM LINEAR DIFFUSER
10" SA 26x14 SA
H
DUCT
DUCT
1875 CFM
SOFFIT PERIMETER.
(TYP 4)
BLANK-OFF UNUSED
700 CFM
PORTIONS
16x16 MAKE-UP AIR
A
10. PROVIDE FLEXIBLE DUCT CONNECTIONS TO MECHANICAL EQUIPMENT.
A
AROUND ENTIRE
12"
26x14 RA
275 CFM
FLEXIBLE DUCTWORK CONNECTIONS TO DIFFUSERS AND REGISTERS SHALL BE 6’-0" MAXIMUM IN LENGTH.
14x24 SA
A
5.
Descri pti on
4. PROVIDE VOLUME DAMPER FOR EVERY SUPPLY, RETURN AND EXHAUST BRANCH OUTLET.
GREASE
36x24
DUCT
FC 5
A
275 CFM
420 CFM
RA DUCT
A1
WEAPONS
M-5000
SIMULATOR KITCHEN A103A
ASSEMBLY A102
OFFICE A103B
Date
Appr.
Mark
A105
C
ARC-SECTION SCALE :1/4"=1’-0"
Descri pti on
C1
EXHAUST AIR
THRU WALL TO
PLENUM CONNECTED
RM A116 WITH A5
UH M-5000 10
HX-1
MECHANICAL A117
A1
M-400A
3" HWS
D4 B 1 M-5010
3" HWR
8x8 OSA
10x10 EA DUCT THRU
16x16 EA DUCT THRU
DUCT THRU
WALL TO RM A113
WALL TO RM A114 WITH
WALL TO RM
WITH SMOKE DAMPER
SMOKE DAMPER
A116 WITH
U.S.ARMY
HST 1
SMOKE
ARC-MECHANICAL ROOM SECTION
A3
SCALE :1/4"=1’-0"
RESERVE CENTER
A1
ARC-MECHANICAL ROOM SECTION SCALE :1/4"=1’-0"
U.S.ARMY
A
7/22/2011
c:\pwworki ng\gbna\m oraja\dm s97636\LCARC_M-300A.dgn
DAMPER
7/22/2011 Pl ot date:
Fi l e nam e:LCARC_M 300A. dgn
F-171-40-160
Project Code:
Pl ot scal e:AS NOTED FAX (714) 327-1601
FOR CONT SEE
HWS TO
TEL (714) 327-1600
2" VENT FROM HWT-1
(TYP 3)
HUTTON CENTRE DRI VE,SUI TE 800
400 CFM
1-1, 1-2
4
UTR
TO LOUVER AND EF
SMOKE DAMPER
B
M .BETZ
(TYP 2)
Subm i tted by:
600 CFM
8x8 EA DUCT
2" VENT FROM HWT-1
GFA 1
ARCH
ARC-SECTI ONS
3" HWS/R
DAMPER
BIRDSCREEN. SEE
D
Revi ewed by:
B 2
1-1/2"
INTAKE THRU WALL
D1 ET 2 M-5020
HWP M-5000 2B 2" SHWS/R
MOTORIZED
A.REED
AS 2
3" HWS
4" COMBUSTION AIR (TYP 2)
C3
MECHANICAL A117
50%FA, WITH
MECHANI CAL
HWP M-5000 2B
(TYP)
Desi gned by:
C3
48x24 EA LOUVER,
CORPS OF ENGI NEERS
C4 AS 1 M-5000
WALL
W 912QR-11-R-0071
DUCT TO
HWP 3
Sol i ci tati on No.
Date:
SECURE
C.KORPASH
DUCT
Ckd by:
18x18 EA
18x18
B
Dwn by:
3/4" HWS/R
M-400A 1-1/2" HWR
LOUI SVI LLE DI STRI CT
D5
ET M-5020 1
C2 EF 1-2 M-5020
A1
I . FRANCO
CONT SEE
MEXI CO
HWP M-5000 4
LAS CRUCES,NEW
FLUE THRU M-5000 ROOF
C3
B2 IV 4 M-5000
SYSTEM. FOR
SANTA ANA, CALI FORNI A 92707
POC TO HEATING C3
D
Mark
E
LOUI SVI LLE,KENTUCKY
G
Rev.
D
072811
E
A.REED
G
SHEET REFERENCE NUMBER:
M-300A of 222
9:00:27
m oraja
AM
Sheet 130
1
2
*** Support Value Engineering - It Pays ***
4
5
CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11
4
5
A1 EF 1-9 M-5020
A1
KSF M-5020 1-1
C1 EC (BEYOND) 1-7 M-5020
B5
B5 EF 1-10 M-5000
EF M-5000 1-4
GENERAL NOTES 1.
REFER TO SHEET M0010 FOR MECHANICAL SYMBOLS, NOTES AND ABBREVIATIONS.
2.
REFER TO MECHANICAL SCHEDULES ON SHEETS M-6000, M-6010 AND 6020.
3.
MAINTAIN COORDINATION OF SUPPLY DIFFUSERS AND RETURN AND EXHAUST REGISTERS WITH ARCHITECTURAL REFLECTED CEILING PLAN.
B5 EF 1-12 M-5000
16x16 MAKE-UP AIR 1" HWS/R TO
DUCT DTR
EC 1-6
D
14x12 WELDED
HWS/R
12x12 EA
10x10 EA
GREASE DUCT
PIPING TO
DUCT DTR
DUCT DTR
THRU ROOF
EC 1-1 C1
EC 1-1 M-5020
4. PROVIDE VOLUME DAMPER FOR EVERY SUPPLY, RETURN AND EXHAUST BRANCH OUTLET. 12x12 EA DUCT DTR
2" HWS/R
5.
FLEXIBLE DUCTWORK CONNECTIONS TO DIFFUSERS AND REGISTERS SHALL BE 6’-0" MAXIMUM IN LENGTH.
6.
INSULATE SUPPLY AND RETURN AIR DUCTWORK PER SPECIFICATIONS.
7.
MOUNT TEMPERATURE, HUMIDITY, C02 SENSORS ON WALL 4’-0" ABOVE FINISHED FLOOR. REFER TO CONTROL DRAWINGS.
8.
INTAKE LOUVERS TO BE A MINIMUM OF 10’-0" ABOVE FINISHED GRADE PER ATFP REQUIREMENTS.
9.
INTERLOCK SMOKE DETECTORS FOR UNIT SHUT DOWN.
PIPING
DAC 1
16x16
20x18 RA DUCT TO
20x18 SA
MAKE-UP
WEAPONS
DUCT TO
AIR DUCT
SIMULATOR ROOM
WEAPONS
36x24 RA DUCT
GREASE DUCT TO
(TYP)
A103
HOOD
CFM
10x8 WELDED
A
KITCHEN
AIR DUCT TO
420 CFM
GREASE DUCT TO
TABLE AND
TYPE 1 HOOD
CHAIR
12x10 MAKE-UP AIR
STORAGE
FAMILY
LOBBY
SUPPORT A147
A101
LI NE
A104
5
6
MATCH
SEE ABOVE
LI NE
DUCT TO HOOD
MATCH
10. PROVIDE FLEXIBLE DUCT CONNECTIONS TO MECHANICAL EQUIPMENT.
330
7
Mark
12x10 MAKEUP
ROOM
Appr.
A103
C
Date
A
CFM
130 CFM
J
330 CFM
FROM EC 1-1 DTR
TYPE 1 HOOD A103
DUCT
SIMULATOR
12x8 WELDED
KITCHEN
A
26x14 RA
SEE BELOW
SA
420
LOUISVILLE DISTRICT
Descri pti on
EC 1-6 M-5020
KITCHEN
US Army Corps of Engineers
1-1/4"
C1
HP 5
4
Appr.
3
SEE BELOW
2
MATCH
1
Date
*** Safety Pays ***
2
LI NE
1
C C1 EC 1-2 M-5020
DUCT THRU
18x46 RA
1 -1/4"
ROOF SEE
DUCT DTR
HWS/R
FROM EC 1-2
PIPINGTO
M-5020
CU 1
EC 1-2 26x18 RA 1 -1/2" HWS/R PIPING
1-1/2"
26x18 RA
20x46 SA
HWS/R
10" RA
DUCT
PIPING
10" RA
10" RA
10" RA
12" RA
18x16 RA
12" SA
12" RA
Descri pti on
D1
10" RA 14" RA
12" SA
10" RA
EF 1-11
18x26 RA
26x14 RA
J
C
J
C
240
240
240
240
CFM
CFM
CFM
CFM
C
J
J
C
J
C
240
240
240
240
240
240
CFM
CFM
CFM
CFM
CFM
CFM
C
J
240
240 CFM
CFM
RESTROOM A146 FULLTIME
FULLTIME
FULLTIME
OFFICE A142
OFFICE A141
OFFICE A140
OFFICE A139
OFFICE A138
C
J
C
1535
245
245
375
CFM
CFM
CFM
CFM
UNIT
UNIT
FULLTIME
COMMON
EXCLUSIVE
OFFICE A137
SPACE
SPACE
A136
A136
LIBRARY READING A133
1 -1/2"
DUCT DTR
UTR TO
DUCT DTR
DUCT OVER
UTR TO
46x18 SA
EC 1-3
DUCT DTR
7/22/2011
Pl ot scal e:AS NOTED
Pl ot date:
Fi l e nam e:LCARC_M 301A. dgn
FAX (714) 327-1601
M .BETZ
Subm i tted by:
F-171-40-160
Project Code:
Revi ewed by:
C.KORPASH
W 912QR-11-R-0071
Ckd by:
A.REED
HUTTON CENTRE DRI VE,SUI TE 800
TEL (714) 327-1600
HWS/R
24x20 SA
EC 1-4
HWS/R
14x14 EA
12" FSD
FSD
DUCT UTR FSD
12"
12" RA DUCT
12" SA
8"
6"
6"
DUCT
46x18
C C
A
J
C
A
J
C
375
375
100
100
310
310
CFM
CFM
CFM
CFM
CFM
CFM
LIBRARY READING A133
C
A
46x18 RA
100
35
35
DUCT
CFM
CFM
CFM
J
D
350
700
CFM
CFM
LIBRARY
LEARNING
TRAINING
STORAGE
BREAK
STORAGE A
CENTER A130
STORAGE A129
A128
AREA A127
B
OMS
A1 A2
A1
ARC-SECTI ONS
FSD
MECHANI CAL
FSD
MEXI CO
12" RA
LAS CRUCES,NEW
8"
U.S.ARMY
8"
RESERVE CENTER
10"
8"
7/22/2011
c:\pwworki ng\gbna\m oraja\dm s97636\LCARC_M-301A.dgn
1" HWS/R
24x20 SA
SANTA ANA, CALI FORNI A 92707
DUCT DTR 1-1/4"
4
B5 EF 1-3 M-5000
18x48 RA
LOUI SVI LLE DI STRI CT
C1 EC 1-3 M-5020
Dwn by:
11
LOUI SVI LLE,KENTUCKY
Date:
C1 EC 1-4 M-5020
Desi gned by:
10
A.REED
9.8
9
CORPS OF ENGI NEERS
8
U.S.ARMY
SEE ABOVE
LI NE MATCH
7
072811
B
I . FRANCO
Sol i ci tati on No.
Rev.
Mark
FULLTIME
FULLTIME
C
ARC-SECTION ARC
SCALE :1/4"=1’-0"
M-301A Sheet 131
of 222
9:01:54
m oraja
AM
KEY PLAN
N
SHEET REFERENCE NUMBER:
1
2
*** Support Value Engineering - It Pays ***
4
5
CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11
1
*** Safety Pays ***
2
4
5
GENERAL NOTES
US Army Corps of Engineers LOUISVILLE DISTRICT
D
EC M-5020 2-1
3/4"
1-1/2"
HWS/R TO
HWS/R TO
EC 2-1
HVU 2-1
C1 HVU 2-1 M-5020
IV M-5000 7
ROOF SEE
FLEXIBLE DUCTWORK CONNECTIONS TO DIFFUSERS AND REGISTERS SHALL BE 6’-0" MAXIMUM IN LENGTH.
6.
INSULATE SUPPLY AND RETURN AIR DUCTWORK PER SPECIFICATIONS.
7.
MOUNT TEMPERATURE, HUMIDITY, C02 SENSORS ON WALL 4’-0" ABOVE FINISHED FLOOR. REFER TO CONTROL DRAWINGS.
8.
INTAKE LOUVERS TO BE A MINIMUM OF 10’-0" ABOVE FINISHED GRADE PER ATFP REQUIREMENTS.
9.
INTERLOCK SMOKE DETECTORS FOR UNIT SHUT DOWN.
Appr. Date
HEATING SYSTEM, SEE
HWS/R
A1
M-400B
24x24 EA LOUVER,
12" RA
ET 4
BIRDSCREEN. SEE ARCH
5.
POC TO
3/4"
50% FREE AREA, WITH
MAINTAIN COORDINATION OF SUPPLY DIFFUSERS AND RETURN AND EXHAUST REGISTERS WITH ARCHITECTURAL REFLECTED CEILING PLAN.
HWS/R
DUCT DTR
M-5000
3.
1-1/2"
16x16 OSA
D5
REFER TO MECHANICAL SCHEDULES ON SHEETS M-6000, M-6010 AND 6020.
10. PROVIDE FLEXIBLE DUCT CONNECTIONS TO MECHANICAL EQUIPMENT.
B2
BOILER FLUES THRU
2.
4. PROVIDE VOLUME DAMPER FOR EVERY SUPPLY, RETURN AND EXHAUST BRANCH OUTLET.
C
C1
REFER TO SHEET M0010 FOR MECHANICAL SYMBOLS, NOTES AND ABBREVIATIONS.
Descri pti on
A
1.
20x16 RA
20x20 SA
UTR
UTR
12" RA
FOR DETAIL
12" SA 8" SA 18x14
DUCT
C2
A5
UH M-5000 11
A
M-5020
HWP 7B
GFA 2
DUCT
D1
AS 3
B 3,4
26x10 RA
8" SA
190 CFM
10" SA
8" RA
Mark
HWP 6A
J
200 CFM
200
C
300
CFM CFM
EXTERIOR
B103
CFM
TRANSFER
B105
GRILLE
TR
FOR PIPING IN THE
A
C
10x10
ALCOVE
HST 2
MECH
110
J
J
C
300
200
CFM
CFM
Appr.
ET 5
200 CFM
Date
EF 2-4 M-5020
HALL B114
B106
MECHANICAL ROOM SEE
C
SHEET M-400B AND DIAGRAM M-7020
SECURE DUCT TO 16x16 OSA DUCT
WALL (TYP)
TO ELEC ROOM B102 WITH 1/2"
Descri pti on
WMS
OMS-SECTION SCALE :1/4"=1’-0"
640 CFM
WORK BAYS
DUCT DTR
F
8" EA DUCT
B116
U.S.ARMY
20x20 SA DUCT EF 2-5
CFM
J
TOOLS
C
100 CFM
430 CFM
B107
B3
A
MENS
7/22/2011
Pl ot scal e:AS NOTED
Pl ot date:
Fi l e nam e:LCARC_M 300B. dgn
M .BETZ
F-171-40-160
Project Code:
UNHEATED STORAGE B101A
B109 HALL
DETAIL M-5000 SEE
B
OMS-SECTI ONS
MECHANI CAL
U.S.ARMY
A
MEXI CO
RESERVE CENTER
B114
LAS CRUCES,NEW
FOR
7/22/2011
c:\pwworki ng\gbna\m oraja\dm s97636\LCARC_M-300B.dgn
300
FAX (714) 327-1601
14x14 OSA
16x14 RA
TEL (714) 327-1600
WITH BIRDSCREEN
LOUI SVI LLE DI STRI CT
ROOF TO ROOF CAP
HUTTON CENTRE DRI VE,SUI TE 800
B2 IV 8 M-5000
M-5010
CORPS OF ENGI NEERS
EF M-5020 2-1
4
D2
C2
Revi ewed by:
Desi gned by:
WALL
A.REED
DUCT THRU
A.REED
24x24 SA
16x20
C.KORPASH
Date:
C1 HVU 2-1 M-5020
072811
B
Ckd by:
Sol i ci tati on No.
Rev.
C2 VX 2-1 M-5000
W 912QR-11-R-0071
B2 RV 4 M-5000
IV M-5000 9
Subm i tted by:
B2
Dwn by:
RV M-5000 7
1
I . FRANCO
B2
2
Mark
3
SANTA ANA, CALI FORNI A 92707
4
LOUI SVI LLE,KENTUCKY
C1
OMS
A1
OMS-SECTION SCALE :1/4"=1’-0"
A1 N
A2
ARC
M-300B Sheet 132
of 222
9:01:12
m oraja
AM
KEY PLAN
N
SHEET REFERENCE NUMBER:
1
2
*** Support Value Engineering - It Pays ***
4
5
CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11
1
*** Safety Pays ***
2
4
5
4
5
6
7
US Army Corps of Engineers
8
Date
Appr.
LOUISVILLE DISTRICT
D
SC 30
D
SC 29
SC 28
SC 27
SC 26
SC 25
SC 24
SC 22
SC 23
SC 21
SC 20
SC 19
SC 18
SC 17
SC 16
SC 15
1" SHWR
SC 14
SC 13
SC 12
SC 11
SC 10
SC 9
SC 8
SC 6
SC 7
1" SHWS 2"
1-1/2" SHWR 1-1/2" SHWS
SC 3
SC 2
SC 1
18 TYP
1" SHWR 1-1/4" SHWR
SC 4
1" SHWR
1" SHWR 1" SHWS
SC 5
1-1/4" SHWR 1-1/2" SHWS
1" SHWS
1" SHWS
1" SHWR
1" SHWS
1-1/4" SHWS
Descri pti on
2"
16 HD 1
20
17
ARC-PARTIAL ROOF PLAN
MOUNT VERTICAL INLINE PUMP OVERHEAD. PROVIDE SPRING VIBRATION ISOLATORS. SEE C3/M-5000
2
3" HWS&R PIPING FOR CONTINUATION SEE SHEET M-114A
3
INSTALL EXPANSION TANK ON 6" CONCRETE HOUSE KEEPING PAD. PIPE DRAIN TO NEAREST FLOOR SINK. CHARGE TANK TO SYSTEM DESIGN PRESSURE.
4
2" SHWS&R PIPES UP THROUGH ROOF TO SOLAR COLLECTORS.
5
3" HWS CONNECTION TO HST-1. PROVIDE PRESSURE RELIEF VALVE AT TANK AND PIPE DISCHARGE TO NEAREST FLOOR SINK.
6
CONNECT 2" SOLAR HOT WATER SUPPLY AND RETURN PIPING TO HST-1 INTERNAL HEAT EXCHANGER CONNECTIONS. PROVIDE 3/4" DRAIN VALVE AT LOWEST POINTS IN SYTEM. CONNECT 3" HWS&R/ SUPPLY FROM BOILER CONNECTION SHALL BE HIGH AND THE RETURN CONNECTION TO THE BOILER SHALL BE LOW. PROVIDE ISOLATION BALL VALVES IN PIPE RISERS DOWN TO TANK.
7
INSTALL EXPANSION TANK ABOVE. SUSPEND FROM DECK ABOVE WITH THREADED ROD. SEE DETAIL D1/M-5020.
8
INSTALL B-1 AND B-2 IN STACKED CONFIGURATION ON 6" CONCRETE HOUSEKEEPING PAD. PROVIDE PRESSURE RELIEF VALVES ON CONDENSATE P-TRAP. PIPE PSV AND CONDENSATE DRAIN DISCHARGE TO NEAREST FLOOR SINK. SEE PLUMBING DRAWINGS FOR NATURAL GAS PIPING.
9
2" DHWS TERMINATE WITH ISOLATION VALVE AT 9’-6" AFF SEE PLUMBING DRAWINGS FOR CONTINUATION.
C
13
HWT 1
Date
5
1
Appr.
KEYED NOTES:
SCALE :1/4"=1’-0"
Descri pti on
C1
Mark
E
1-1/2" DHWR
2" DHWS 2" DHWR
1-1/2" DHWS
2" VENT
10 2" DHWR TERMINATE AT 9’-6" AFF FOR CONTINUATION BY PLUMBING CONTRACTOR AND CONNECTION TO DOMESTIC WATER SUPPLY AND HOT WATER RETURN FROM THE DOMESTIC WATER RECIRCULATING PUMP.
12
3" 2" SHWS&R
6 19 4" COMBUSTION AIR INTAKE ROUTE FROM BOILER TO EXTERIOR
HWP 4 HWP 2A
1
HWP 2B
7/22/2011
Pl ot scal e:AS NOTED
Pl ot date:
F-171-40-160
Project Code:
W 912QR-11-R-0071
FAX (714) 327-1601
3’-0" ABOVE NEARBY EQUIPMENT AND ROOF SEE DETAIL D5/M-5000. HORIZONTAL OFFSETS SHALL BE SLOPED 1/4" PER FOOT TOWARD BOILER.
1 PROVIDE MANUAL EMERGENCY BOILER SHUTDOWN SWITCH. INTERLOCK 21
E
SWITCH WITH MAIN GAS SOLENOID SHUTOFF VALVE SHOWN ON P-411A. SWITCH SHALL CLOSE GAS SUPPLY AND TURN OFF 120V POWER TO BOILERS. MOUNT SWITCH 48" ABOVE FLOOR. FOR CONTROL DIAGRAM SEE M-8050.
3"
2 22 PROVIDE EMERGENCY SHUTOFF ALARM/STROBE IN WEATHER PROOF
U.S.ARMY
SURFACE MOUNTED BOX. KELE #868STR. MOUNT STROBE/HORN 8’-0" ABOVE FLOOR.
A
B
OMS
ARC-SOLAR HEAT ENLARGED PLANS
15
1
20 ROUTE VENT EXHAUST UP THROUGH ROOF. TERMINATE AT LEAST
AS 2
MECHANI CAL
3/4"
WALL AND TERMINATE WITH WALL CAP WITH BACKDRAFT DAMPER.
1
7/22/2011
c:\pwworki ng\gbna\m oraja\dm s97636\LCARC_M-400A.dgn
5
HWP 3
TEL (714) 327-1600
1
SUPPORTS PROVIDED BY MANUFACTURER. GROUP COLLECTORS IN ARRAYS OF SIX COLLECTORS EACH. PROVIDE AIR VENT AND PRESSURE RELIEF VALVE AT AHWR CONNECTIO. COLLECTORS SHALL BE INSTALLED AT 0^ AZIMUTH AND 47^ SLOPE. OFFSET EACH ARRAY OF COLLECTORS TO ALLOW CLEARANCE FOR PIPING OF ADJACENT ARRAYS.
HUTTON CENTRE DRI VE,SUI TE 800
HWP 1B
INSTALL FLAT PLATE SOLAR COLLECTORS ON STRUCTURAL 18
SANTA ANA, CALI FORNI A 92707
1
4
HWP 1A
LOUI SVI LLE DI STRI CT
4
3"
20 HST 1
2" PIPE. PROVIDE AUTOMATIC AIRVENT, FLEXIBLE CONNECTIONS, 3-WAY MOTORIZED CONTROL VALVE AND BALANCING VALVE.
LOUI SVI LLE,KENTUCKY
3
14
17 INSTALL HEAT-DUMP DRYCOOLER ON ROOF. CONNECT TO SHWS WITH
MEXI CO
1" ET 1
3
LAS CRUCES,NEW
3"
ROOF PIPE PENETRATION. ET 3
CORPS OF ENGI NEERS
1"
16 2" SHWS&R PIPES DOWN THROUGH ROOF. SEE DETAIL D3/M5000 FOR
U.S.ARMY
ET 2
PIPING OF HWP-1A AND HWP-1B WITH 3/4" PIPE. PROVIDE ISOLATION BALL VALVES AND PIPE 1/2" DRAIN TO NEAREST FLOOR SINK.
HX 1
RESERVE CENTER
B 2
1-1/2" HW S
7
8
15 CONNECT CHEMICAL POT FEEDER TO SUCTION AND DISCHARGE
1-1/2" HW R
GFA 1
AS 1
B 1
Revi ewed by:
1
2"
Sol i ci tati on No.
REDUCING VALVE SET AT 15 PSIG. TERMINATE AT 10’-0" AFF WITH BALL VALVE FOR MAKE-UP WATER POC, SEE PLUMBING DRAWING C1/P-411A FOR CONTINUATION.
A.REED
21
HWP 5
Ckd by:
9
Dwn by:
11
14 1" MAKE-UP WATER SUPPLY, PROVIDE CHECK VALVE AND PRESSURE
R.SALLW ASSER C.KORPASH
10
Date:
D
EPO
072811
B
Desi gned by:
A4/M-5020. PROVIDE MANHOLE AND EXTENSION TO GRADE . TOP OF TANK SHALL BE A MINIMUM OF 48" BELOW GRADE. PROVIDE ANCHOR SLAB AND TIE DOWN STRAPS PER DETAIL. BACKFILL WITH PEA GRAVEL.
D.O’ CALLAHAN
UNDERGROUND POTABLE WATER STORAGE TANK. SEE DETAIL 13
19
Rev.
22
Fi l e nam e:LCARC_M 400A. dgn
Mark
DOMESTIC HOT WATER SUPPLY AND RETURN TO DISTRIBUTION POINTS. PIPES SHALL BE LOCATED A MINIMUM OF 36" BELOW GRADE OF BELOWFROST LINE. PROVIDE ISOLATION VALVES IN RISERS WITHIN MECHANICAL ROOM.
M .BETZ
12 1-1/2" DOMESTIC HOT WATER SUPPLY AND RETURN TO HX-1 AND 2"
Subm i tted by:
RELIEF VALVE. PIPE DISCHARGE TO NEAREST FLOOR SINK.
111510
11 TERMINATE HWFI VENT AT 9’6" AFF WITH THERMOSTATIC PRESSURE
G A1
N
22
ARC
ARC-ENLARGED MECHANICAL ROOM PLAN KEY PLAN
SCALE :1/4"=1’-0"
N
M-400A Sheet 133
of 222
9:02:37
m oraja
AM
A1
A2
SHEET REFERENCE NUMBER:
1
2
*** Support Value Engineering - It Pays ***
4
5
CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11
1
*** Safety Pays ***
2
4
5
US Army Corps of Engineers
2
3
Date
1
Appr.
LOUISVILLE DISTRICT
Descri pti on
D
A
13
1"
10 SC 31
SC 32
Date
Appr.
Mark
11
1"
C
KEYED NOTES: MOUNT VERTICAL INLINE PUMP OVERHEAD. PROVIDE SPRING VIBRATION ISOLATORS. SEE C3/M-5000
2
2" HWS&R PIPING FOR CONTINUATION SEE SHEET M-110B
3
1" SHWS&R PIPES UP THROUGH ROOF TO SOLAR COLLECTORS.
4
PROVIDE PRESSURE RELIEF VALVE AT HST-2 AND PIPE DISCHARGE TO NEAREST FLOOR SINK.
5
CONNECT 1" HOT WATER SUPPLY AND RETURN PIPING TO HST-2 CONNECTIONS. PROVIDE 3/4" DRAIN VALVE AT LOWEST POINTS IN SYTEM. CONNECT 2" HWS&R. SUPPLY CONNECTIONS FROM BOILERS AND HPAK-1 SHALL BE HIGH AND THE RETURN CONNECTIONS TO THE BOILERS AND HPAK-1 SHALL BE LOW. PROVIDE ISOLATION VALVES IN PIPE RISERS DOWN TO TANK.
6
INSTALL EXPANSION TANK ABOVE. SUSPEND FROM DECK ABOVE WITH THREADED ROD. SEE DETAIL D1/M-5020
7
INSTALL B-3 AND B-4 IN STACKED CONFIGURATION ON 6" CONCRETE HOUSEKEEPING PAD. PROVIDE PRESSURE RELIEF VALVES ON CONDENSATE P-TRAP. PIPE PSV AND CONDENSATE DRAIN DISCHARGE TO NEAREST FLOOR SINK. SEE PLUMBING DRAWINGS FOR NATURAL GAS PIPING.
8
1" MAKE-UP WATER SUPPLY. PROVIDE CHECK-VALVE AND REDUCING VALVE SET AT 15 PSIG. TERMINATE AT 10’-0" AFF WITH BALL VALVE FOR MAKE-UP WATER POC, SEE PLUMBING DRAWING C1/P-411B FOR CONTINUATION
9
CONNECT CHEMICAL POT FEEDER TO SUCTION AND DISCHARGE PIPING OF HWP-6A AND HWP-6B WITH 3/4" PIPE. PROVIDE ISOLATION BALL VALVES AND PIPE 1/2" DRAIN TO NEAREST FLOOR SINK.
8
2"
1"
1
7
B 4
7
1"
HWP 6B
ET 4
16
1-1/2" HWS/ R DOWN TO RADIANT HEATING VALVE MANIFOLD AND UNIT HEATER UH-11
17
3/4" HWS/ R TO UNIT HEATER UH-12
6
HST 2
HWP 7A
1
4
5
1
2" B ET 5
2
6
7/22/2011
Pl ot scal e:AS NOTED
Pl ot date:
Fi l e nam e:LCARC_M 400B. dgn
F-171-40-160
Mark
OMS
N 9:03:19 AM
A1
A2
ARC
OMS-ENLARGED MECHANICAL ROOM PLAN KEY PLAN
SCALE :1/2"=1’-0"
1
2
*** Support Value Engineering - It Pays ***
4
5
N
OMS - SOLAR HEAT ENLARGED PLANS
2" HWP 7B
U.S.ARMY
A
MECHANI CAL
HPAK 1
LAS CRUCES,NEW
RESERVE CENTER
AS 4
3
MEXI CO
2"
A1
m oraja
Ckd by:
HWP 6A
1"
7/22/2011
c:\pwworki ng\gbna\m oraja\dm s97636\LCARC_M-400B.dgn
1
B 3
M .BETZ
PROVIDE EMERGENCY SHUTOFF ALARM/STROBE IN WEATHER PROOF SURFACE MOUNTED BOX. KELE #868STR. MOUNT STROBE/HORN 8’-0" ABOVE FLOOR.
AS 3
3/4"
Subm i tted by:
15
14
FAX (714) 327-1601
GFA 2
TEL (714) 327-1600
9
HUTTON CENTRE DRI VE,SUI TE 800
PROVIDE MANUAL EMERGENCY BOILER SHUTDOWN SWITCH. INTERLOCK SWITCH WITH MAIN GAS SOLENOID SHUTOFF VALVE SHOWN ON P-411B. SWITCH SHALL CLOSE GAS SUPPLY AND TURN OFF 120V POWER TO BOILERS. MOUNT SWITCH 48" ABOVE FLOOR. FOR CONTROL DIAGRAM SEE M-8050.
SANTA ANA, CALI FORNI A 92707
14
EPO
4
ROUTE VENT EXHAUST UP THROUGH ROOF. TERMINATE AT LEAST 3’-0" ABOVE NEARBY EQUIPMENT AND ROOF SEE DETAIL D5/M-5000.
Dwn by:
13
LOUI SVI LLE DI STRI CT
A
4" COMBUSTION AIR INTAKE ROUTE FROM BOILER TO EXTERIOR WALL AND TERMINATE WITH WALL CAP WITH BACKDRAFT DAMPER.
D.O’ CALLAHAN
13
12
CORPS OF ENGI NEERS
12
U.S.ARMY
15 RADIANT HEATING VALVE MANIFOLD
Desi gned by:
SUPPORTS PROVIDED BY MANUFACTURER. PROVIDE AIR VENT AND PRESSURE RELIEF VALVE AT HWR CONNECTION. COLLECTORS SHALL BE INSTALLED AT 0^ AZIMUTH AND 47^ SLOPE. MINIMUM DISTANCE BETWEEN SOLAR COLLECTOR ROWS IS 14’-0".
Project Code:
11 INSTALL FLAT PLATE SOLAR COLLECTORS ON STRUCTURAL
Revi ewed by:
1" SHWS&R PIPES DOWN THROUGH ROOF. SEE DETAIL D3/M-5000 FOR ROOF PIPE PENETRATION. Date:
10
A.REED
B
W 912QR-11-R-0071
3
Sol i ci tati on No.
SCALE :1/4"=1’-0"
R.SALLW ASSER C.KORPASH
B1
OMS-PARTIAL ROOF PLAN
LOUI SVI LLE,KENTUCKY
B
Descri pti on
1
Rev.
SC 34
111510
SC 33
SHEET REFERENCE NUMBER:
M-400B Sheet 134
of 222
CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11
1
*** Safety Pays ***
2
4
5
DRAW BAND
US Army Corps of Engineers
PIPING THROUGH ROOF ROUND COPPER WEATHER CAP, CAULK THE SEAM BETWEEN THE CAP AND THE ALUMINUM JACKET
WITH INSULATION AND ALUMINUM JACKET
LOUISVILLE DISTRICT
WEATHERPROOF CAP Appr.
SQUARE SHAPED COPPER FLASHING WITH FLANGE BASE, SET IN
ROOFING NAILS
WITH PLASTIC CEMENT
TWO LAYERS 15 LB. FELT, SET IN BEDS OF PLASTIC CEMENT
FINISH ROOF AS DETAILED
D
8" MIN.
AND EXTENDED MIN. 3" AND 6"
ON ARCHITECTURAL DRAWINGS
BEYOND EDGE OF FLASHING ON
STORM COLLAR
EACH SIDE AND MOP INTO EXISTING ROOFING
FLASHING
I N
CORRUGATED METAL ROOF ROOF
WITH RIGID INSULATION AND
AS SPECI FI ED
GUY WIRES IF REQUIRED BY HEIGHT (3 TYPICAL)
WITH 8 EVENLY SPACED SEAL ENDS OF INSULATION
ACCORDANCE W I TH
SECURE FLASHING IN PLACE
Date
NFPA
METAL FLUE
BED OF PLASTIC CEMENT
BUILT-UP ROOFING TREATED WOOD NAILER, SECURED TO METAL DECK FROM BELOW WITH LAG BOLT, TYP.
Descri pti on
4 LAG BOLTS, ONE EACH SIDE
METAL FLUE LONG RADIUS ELBOW
PIPE
HEAT RESISTANT
D5
N.T.S.
FLUE THRU ROOF DETAIL N.T.S.
ROOF 5 8" DIA PEX TUBING COMPRESSION TANK
THIMBLE THRU
@ 9" O.C. SECURED
ROOF
TO WIRE MESH WITH
CHARGE VALVE FOR TANK PRESSURIZATION AIR VENT
UNION (UP TO 2-1/2") MANUFACTURER
STRUCTURE.
PROVIDED
INCLUDE SWAY
ROOF
BRACING
CURB
CONCRETE
SERVICE VALVE
FLANGE (3" & OVER)
CHECK VALVE (OPTIONAL) SWING TYPE JOINT TYP THIS LINE SLOPE MIN OF
PRESSURE GAUGE W/GAGECOCK
TRANSITION TO
SLAB
NON-STRUCTURAL
BLADDER
WATER SUPPLY
WIRE MESH
PRV Date
FASTEN TO
WIRE TIES
Mark
EXHAUST
PIPING THRU ROOF DETAIL
Appr.
MI N. 3’ TO
12" STEEL
ROOF
D3
1" IN 5’-0"
12" DIA SERVICE VALVE
EXHAUST AT DISCHARGE
WATER MAKE-UP
GATE VALVE
IN-LINE PUMP
EXHAUST FAN
CHECK VALVE
Y-STRAINER W/
VEHICLE EXHAUST
BALANCING VALVE
C
BACKFLOW PREVENTER
TO FLOOR DRAIN
STRAINER REMOVAL SPACE
BLOW-OFF VALVE
DRUM HANGER SUPPORTS 2 SIDES
8" HOSE
FROM HEATING EQUIPMENT
REDUCER (IF REQ’D) TO PUMP
W/ CLIP
NOTE:
AIR SEPARATOR
PROVIDE 4-BUTTON CONTROLLER MOUNTED 5’ A.F.F. TO COLUMN BELOW
DRAIN VALVE
COMPACTED
2" EXPANDED POLYSTYRENE
GRADE
FOAM INSULATION BOARD
Descri pti on
NOZZLE
WITH VAPOR BARRIER
VEHICLE EXHAUST FAN DETAIL
C3
N.T.S.
VERTICAL INLINE PUMP PIPING DETAIL
C4
N.T.S.
HEATING HOT WATER PIPING DIAGRAM
C5
N.T.S.
RADIANT SLAB CROSS-SECTION DETAIL N.T.S.
AI R FLOW
C2
SECURE HOOD TO CURB WITH LAG MANUFACTURER PROVIDED ROOF CURB.
EXHAUST DUCT SIZE VARIES
MANUFACTURER’S ROOF CURB
N.T.S.
B5
ROOF MOUNTED EXHAUST FAN N.T.S.
SEE NOTE 3, BALANCING PLUG VALVE (SEE NOTE NO. 1) FASTEN FLASHING SCREWS & SEAL
1/4" MANUAL AIR VENT
REMOVABLE CAP W/SELF
THERMOMETER WITH SEPARABLE SOCKET
ALL FLASHING
WITH 1/4" N.P.T.
ALIGNING O-RING SEAL
COIL AIR VENT
20 GA.
3/4" N.P.T.
BOTH SIDES OF CONTROL AND BALANCE VALVE IF REQD AS SHOWN (TYP)
REDUCER SECURE TO STRUCTURE
SEE NOTE 6
BALANCING VALVE
SUPPLY
METAL FLASHING
2"x6" CURB
3/4" BALL VALVE HWR UNION (TYP.)
PUMP SUCTION GALVANIZED HANGER STRAP PER IMC AND SMACNA
1-1/2" x 1-1/2" x 1/4"
TO FLASHING
ANGLE IRON STAND
A
BALL VALVE (UP TO
5 GALLON MINIMUM 10 GAUGE TANK SHELL
R AI
1-1/2")
W O FL
DISCHARGE
BUSHING W/NIPPLE
1/2" GLOBE VALVE W/HOSE COUPLING
AND MATERIALS DIFFER 2 PETE’S PLUG SHOWN
3/4" DRAIN W/GATE VALVE & HOSE COUPLING
3/4" TO 1/2"
ROOF
3 WHEN TAPPING INTO TOP OF MAINS, AIR VENTS ARE REQD AS SHOWN
3/4" COIL DRAIN VALVE W/HOSE COUPLING
4 NORMALLY USE MANUAL AIR VENT; AUTOMATIC VENT ACCEPTABLE ONLY WITH BLADDER COMPRESSION TANK
3" x 3" x 1/4" STEEL PAD BOLTED
6" CONCRETE PAD
MANUAL OR AUTOMATIC AIR VENT IF TAP PROVIDED BY COIL MFG (SEE NOTE 4)
1 PROVIDE DIELECTRIC UNIONS WHERE PIPING
PRESSURE GAUGE W/GATE VALVE
3/4" TEE
SWIVEL COCK
NOTES:
Y-STRAINER w/ BLOW-OFF VALVE
AND HEADS
3/4" FROM PUMP
ROOF (TYP.)
NOTES:
TO CONCRETE PAD
1. WHERE 3-WAY MODULATING VALVES ARE REQUIRED, PROVIDE ADDITIONAL PIPING AND ADDITIONAL ACCESSORIES AS SHOWN.
5 ARRANGEMENT SHOWN FOR HOT WATER COIL WITH FULL FLOW THROUGH COIL ON FAILURE
RECTANGULAR DUCTWORK
6 WHERE SIZE PERMITS, ELIMINATION OF BALANCE VALVE AND LEAVING SERVICE VALVE W/CIRCUIT SETTER IS PERMISSIBLE
DUCT THRU ROOF DETAIL N.T.S.
A2
CHEMICAL POT FEEDER DETAIL N.T.S.
A3
HEATING COIL DETAIL N.T.S.
A4
STANDARD DUCT SUPPORT N.T.S.
A5
7/22/2011
Pl ot scal e:AS SHOW N
Pl ot date:
F-171-40-160
Project Code:
Revi ewed by:
A.REED
W 912QR-11-R-0071
Sol i ci tati on No.
CAPPED HOSE BIBB AT LOWEST POINT FOR DRAINAGE IF NOT SUPPLIED ON COIL
SHEET REFERENCE NUMBER:
M-5000
UNIT HEATER DETAIL
Sheet 135
of 222
N.T.S.
9:03:48
m oraja
AM
A1
BRACKET WITH
PLUGS (SEE NOTE 2)
HWS
ROOFING UP
STRUCTURE
PROVIDE WALL
GAUGES AND GAUGE COCK W/THERMOWELLS OR PETE’S
3/4" TO
FLASHING
DUCT THROUGH
TO WALL N O
SEE NOTE 1
GALVANIZED SHEET METAL COUNTER
SEE NOTE 5 BOLT UNIT HEATER
BALANCE VALVE
SERVICE VALVE
20 GA. CANT STRIP
C.KORPASH
OPTIONAL PRESSURE TAP
UNION
HOT WATER COIL
GALVANIZED SHEET
INSTALL CONCENTRIC REDUCERS
U.S.ARMY
WITH MASTIC
7/22/2011
c:\pwworki ng\gbna\m oraja\dm s97636\LCARC_M-5000.dgn
WITH SHEET METAL
4 (TYP)
2-WAY MODULATING VALVE (SEE NOTE NO. 1)
AIR VENT (3/4" GATE VALVE WITH CAP)
RETURN
FAX (714) 327-1601
N.T.S.
UPBLAST EXHAUST FAN MOUNTING DETAIL
TEL (714) 327-1600
B4
HUTTON CENTRE DRI VE,SUI TE 800
FLOOR LEVEL EXHAUST DETAIL
DETAI LS
N.T.S.
B3
MEXI CO
ROOF MOUNTED INTAKE/RELIEF PENTHOUSE
LAS CRUCES,NEW
B2
4
GRATE IN FLAMMABLE STORAGE ROOM.
LOUI SVI LLE DI STRI CT
EXTEND DUCT TO 2" FROM METAL
RESERVE CENTER
NOTE:
CORPS OF ENGI NEERS
FINISHED FLOOR
Ckd by:
BACKDRAFT DAMPER
U.S.ARMY
ROOF OPENING FRAMING, REFER TO STRUCTURAL DRAWINGS
PROVIDE 1/2" WIRE MESH SCREEN AT INLET
Dwn by:
Desi gned by:
2"
A.REED
ROOF STRUCTURE
METAL GUARD
18"
BACKDRAFT DAMPER
I .FRANCO
Date:
DUCTWORK
LOUI SVI LLE,KENTUCKY
CANT STRIP
072811
B
AI R FLOW
CURB FLASHING
Rev.
ROOF CURB.
Fi l e nam e:LCARC_M 5000. dgn
MANUFACTURER PROVIDED
M .BETZ
40" MIN
FRAMING
Subm i tted by:
SECURE TO WALL
Mark
2X NAILING STRIP
ROOF STRUCTURE
SANTA ANA, CALI FORNI A 92707
BOLTS
1
2
*** Support Value Engineering - It Pays ***
4
5
CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11
1
*** Safety Pays ***
2
4
5
SEISMIC BRACE PER SMACNA AND
24 GA. FLASHING-SECURE ANGLE IRON REINFORCING FRAME WHERE REQUIRED
W/ SHEETMETAL SCREWS
UFC 3-301-01 (TYP.)
OR RIVETS TO WALL & SEAL ALL ROUND (TYP.)
STANDARD DUCT MADE WATER TIGHT. STIFFENERS
SCREEN
US Army Corps of Engineers
5’-0" MAX SHEET METAL (20 GA.)
NOTE
LOUISVILLE DISTRICT
"A" = PIPE AND INSULATION
24 GA. MIN. COUNTER-
DIAMETER PLUS ONE INCH MINIMUM
FLASHING
RESILIENT CAULKING
MAY BE INSIDE.
"A"
HANGER ROD
"A"
Appr.
METAL SCREEN
ANGLE RIVETED OR SPOT WELDED AS REQUIRED.
5 13
Date
SIZED FOR LOAD BOLTS
BOILER EXTERIOR PANEL 2 MAX 1 MIN
MI N
INSULATION (RIGID INSULATION 18" LONG CENTERED ON
.
DUCT SIZE + 25%
1 ADJUSTABLE WROUGHT CLEVIS
SUPPORT) WELD
1/2" SCREEN
R
N. 12" MI
D N. 18" MI
PIPE
W R = W/2
ANGLE IRON
18 GAGE GALV SADDLE 12" LONG
18 GAGE GALVANIZED SEE NOTE 3
SEE NOTE 4 (TYP.)
SADDLE 12" LONG
NOTE:
SEE NOTE 5 (TYP.) MATCH OD OF INSULATION FOR INSULATED LINE, MATCH OD OF PIPE FOR UNINSULATED LINES. REFER TO SMACNA SEISMIC RESTRAINT MANUAL AND UFC 3-301-01
PENETRATING DUCT
U.S.G. THERMA FIBER OR EQUAL DENSITY PACKING (TYP.)
FIRE STOP SYSTEM (TYP.)
NOTES:
CONCRETE CURB
EXPANSION ANCHOR
1. ANCHOR BOLT SIZE AND QUANTITY PER SMACNA REQUIREMENTS.
EXTERIOR
Descri pti on
2. PIPE INSULATION IS NOT SHOWN FOR CLARITY.
NOTES:
3. PROVIDE DOUBLE WASHER AND NUT ASSEMBLY.
INTERIOR
1. SEE ARCHITECTURAL DRAWINGS FOR ROOF PENETRATION DETAILS.
4. OPTIONAL HORIZONTAL SEISMIC RESTRAINT. NOTES 1.
D1
SEE NOTE 3
GOOSENECK DETAIL
D2
N.T.S.
DUCT THRU WALL DETAIL
D3
N.T.S.
PIPE HANGER DETAIL - SINGLE PIPE
D4
N.T.S.
5. STRUCTURAL MEMBER, REFER TO STRUCTURAL PLANS.
SUBMIT FOR STRUCTURAL REVIEW
BOILER ANCHOR DETAIL TO CONCRETE CURB N.T.S.
D5
N.T.S.
SECURE TO STRUCTURE ABOVE
METAL SLEEVE
SECURE TO STRUCTURE ABOVE PER SMACNA SEISMIC GUIDELINES
MAX. 6’-0" LENGTH FLEXIBLE DUCT
PIPE HANGER DETAIL - TRAPEZE TYPE
SECURE TO STRUCTURE ABOVE
PIPE
1-1/2" MIN. 1-1/2" MIN.
4’-0" MAX.
Mark
WIRE TO BE SECURED TO STRUCTURE ABOVE
SUPPLY AIR VOLUME DAMPER
WALL CONSTRUCTION VARIES
Appr.
SILICONE SEALANT 1-1/2" MIN.
SPIRAL DUCT
Date
FLEX DUCT 6’ MAX.
4" WIDE SHEET METAL FLEXIBLE DUCT SUPPORT STRAP DUCT MINERAL FIBER PACKING
C SAFETY HANGER 12 GA. WIRE OR
SAG 1/2" PER FOOT OF SUPPORT SPACING
18 GA. 1" METAL STRAP #10 SCREWS
FLEXIBLE DUCT CLAMPING DEVICE (TYP.)
CEILING NOTES:
CEILING DIFFUSER OR GRILLE
1.INSTALL DUCTWORK PER SMACNA NOTE:
1.LOCATE VOLUME DAMPER AS FAR AWAY FROM DIFFUSER OR GRILLE AS POSSIBLE
Descri pti on
NOTES:
2.SUPPORT PIPES & DUCTS ON EITHER SIDE OF WALL.
LAY-IN DIFFUSER/GRILLE CONNECTION DETAIL
C3
N.T.S.
DUCT/PIPE PENETRATION THRU NON RATED WALL
C4
N.T.S.
FLEXIBLE DUCTWORK HANGER DETAIL N.T.S.
ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIAMETER. OF OPENING IS 18 IN.
3.
THROUGH PENETRATE - NOM 4 IN. (102 MM) DIAM.. (OR SMALLER) TYPE L (OR HEAVIER) COPPER PIPE, NOM 12 IN. (305 MM) DIAM.. (OR SMALLER) SERVICE WEIGHT
SLEEVE
(OR HEAVIER) CAST IRON SOIL PIPE, NOM 12 IN. (305 MM) DIAM.. (OR SMALLER) CLASS 50 (OR HEAVIER) DUCTILE IRON PRESSURE PIPE OR NOM 12 IN. (305 MM)
(SEE NOTES #2 & #3)
DIAM.. (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE CENTERED IN THE OPENING AND RIGIDLY SUPPORTED ON BOTH SIDES OF THE FLOOR OR WALL
SLEEVE
ASSEMBLY.
(SEE NOTES #2 & #3) 4.
6" MAX. ON ALL SIDES
PIPE COVERING* - NOM 1/2 TO 2 IN. (13 TO 15 MM) THICK HOLLOW CYLINDRICAL HEAVY DENSITY (MIN... 3.5 PCF OR 56kg/m‡) GLASS FIBER UNITS JACKETED ON
7/22/2011
Pl ot scal e:AS SHOW N
Pl ot date:
F-171-40-160
Project Code:
SECURED WITH METAL FASTENERS OR FACTORY -APPLIED SELF - SEALING LAP TAPE. TRANSVERSE JOINTS SECURED WITH METAL FASTENERS OR WITH BUTT STRIP TAPE SUPPLIED WITH THE PRODUCT. WALL CONSTUCTION
6" MAX. ON ALL SIDES
NOTES A.
A
1. OPENING IN WALL SHALL BE A MINIMUM 1/8" PER FOOT LARGER THAN OVERALL SIZE OF DAMPER AND SLEEVE ASSEMBLY FOR GALVANIZED STEEL DAMPERS AND A MINIMUM 3/16" PER FOOT FOR STAINLESS STEEL DAMPERS. MAXIMUM OPENING NOT TO EXCEED 1/8" PER FOOT PLUS ONE INCH FOR GALVANIZED STEEL DAMPERS. OPENING SHALL NOT BE LESS THAN 1/4" LARGER FOR ANY SIZE DAMPER AND SLEEVE ASSEMBLY.
TO BE RECESSED FROM TOP SURFACE OF FLOOR OR SLEEVE OR FROM BOTH SURFACES OF WALL AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF
3. IF ANY OTHER DUCT-SLEEVE CONNECTIONS ARE USED, SLEEVE SHALL BE MINIMUM OF 16 GAGE FOR DAMPERS UP TO
CAULK FILL MATERIAL (ITEM B).
36"Wx24"H AND 14 GAGE IF DAMPER WIDTH EXCEEDS 36" OR HEIGHT EXCEEDS 24".
B.
4. MOUNTING ANGLES SHALL BE A MINIMUM OF
THE ANNULAR SPACE (BETWEEN THE PIPE COVERING MATERIAL AND THE EDGE OF THE CIRCULAR THROUGH OPENING), AS SHOWN IN THE FOLLOWING TABLE:
2. SLEEVE GAGE SHALL BE AT LEAST EQUAL TO THE GAGE OF BOTTOM (SEE ILLUSTRATION). MOUNTING THE DUCT AS DEFINED BY THE APPROPRIATE SMACNA DUCT ANGLES SHALL OVERLAP WALL A MINIMUM OF ONE INCH. CONSTRUCTION STANDARD AND DESCRIBED IN NFPA 90A WHEN ONE OR MORE OF THE FOLLOWING DUCT-SLEEVE
FIRE DAMPER
MIN FLOOR OR WALL
MAX PIPE
NOM PIPE COVERING
ANNULAR SPACE
F RATING
T RATING
W RATING
THKNS IN. (mm)
DIAM IN. (mm)
THKNS IN. (mm)
IN. (mm)
HR
HR
CLASS
2-1/2 (64)
4 (102)
1 OR 1-1/2 (25 OR 38)
1/2 TO 2-3/8 (13 OR 60)
2
1
1
4-1/2 (114)
4 (102)
2 (51)
1/4 TO 3-5/8 (6 OR 92)
2
1-1/2
1
2-1/2 (64)
12 (305)
1 (25)
1/2 TO 1-1/2 (13 OR 38)
2
1/2
1
4-1/2 (114)
12 (305)
1 (25)
1/2 TO 2-3/8 (13 OR 60)
3
1
1
2-1/2 (64)
12 (305)
1/2 (13)
1/2 TO 2-3/8 (13 OR 60)
2
0
1
A2
N.T.S.
1
2
A MAXIMUM SPACING OF 6" FOR STAINLESS STEEL AND 12" FOR GALVANIZED WITH A MINIMUM OF TWO CONNECTIONS IN
EXCEED 1/8" PER FOOT PLUS ONE INCH FOR GALVANIZED STEEL DAMPERS. OPENING SHALL NOT
EACH SIDE, TOP, AND BOTTOM (SEE ILLUSTRATION). MOUNTING ANGLES SHALL OVERLAP WALL A MINIMUM OF ONE INCH.
5. 2. SLEEVE GAGE SHALL BE AT LEAST EQUAL TO THE GAGE OF THE DUCT AS DEFINED BY THE APPROPRIATE SMACNA DUCT CONSTRUCTION STANDARD AND DESCRIBED IN NFPA 90A WHEN ONE OR MORE OF THE FOLLOWING DUCT-SLEEVE CON- NECTIONS ARE USED
FIRESTOP SYSTEM ARE DEPENDENT UPON THE THICKNESS OF THE FLOOR OR WALL, THE SIZE OF PIPE, THE THICKNESS OF PIPE COVERING MATERIAL AND THE SIZE OF
CONNECTIONS ARE USED (PLAIN ’S’ SLIP, HEMMED ’S’ SLIP, STANDARD ’S’ SLIP, REINFORCED STANDING ’S’ SLIP, INSIDE SLIP JOINT, AND DOUBLE ’S’ SLIP.)
9:04:16 AM
FILL, VOID OR CAVITY MATERIAL* - CAULK SEALANT - APPLIED TO FILL THE ANNULAR SPACE FLUSH WITH THE TOP SURFACE OF THE FLOOR OR SLEEVE OR
NOM PIPE COVERING THICKNESS IS 1-1/2IN. (38 MM) OR LESS, MIN.. THICKNESS OF CAULK FILL MATERIAL IS 1 IN. (25 MM). THE HOURLY F AND T RATINGS OF THE
1 1/2" X 1 1/2" X 14 GAGE AND BOLTED, WITH 1/4" - 20 BOLT, WELDED, OR SCREWED WITH NO. 10 SCREWS TO SLEEVE AT A MAXIMUM
AND A MINIMUM 3/16" PER FOOT FOR STAINLESS STEEL DAMPERS. MAXIMUM OPENING NOT TO
BE LESS THAN 1/4" LARGER FOR ANY SIZE DAMPER AND SLEEVE ASSEMBLY.
FLUSH WITH BOTH SURFACES OF WALL. WHEN NOM PIPE COVERING THICKNESS IS 2 IN. (51MM), MIN.. THICKNESS OF CAULK FILL MATERIAL IS 2 IN. (51 MM). WHEN
SPACING OF 6" FOR STAINLESS STEEL AND 12" FOR GALVANIZED WITH A MINIMUM OF TWO CONNECTIONS IN EACH SIDE, TOP, AND
A1
PACKING MATERIAL - MIN.. 1 IN. (25 MM) THICKNESS OF FIRMLY PACKED MINERAL WOOL BATT INSULATION USED AS A PERMANENT FORM. PACKING MATERIAL
(PLAIN ’S’ SLIP, HEMMED ’S’ SLIP, STANDARD ’S’ SLIP, REINFORCED STANDING ’S’ SLIP, INSIDE SLIP JOINT, AND DOUBLE ’S’ SLIP.)
3. IF ANY OTHER DUCT-SLEEVE CONNECTIONS ARE USED, SLEEVE SHALL BE MINIMUM OF 16 GAGE FOR DAMPERS
FASTENED WITH NO. 10 BOLTS OR SCREWS, 3/16" RIVET OR 1/2" TACK WELD STAGGERED INTERMITTENTLY, AND SPACED 12" MAXIMUM C-C FOR GALVANIZED AND 6" MAXIMUM C-C FOR STAINLESS STEEL.
6. FURNISH WITH DUCT SMOKE DETECTOR 7. FOR APPLICATIONS REQUIRING MULTIPLE ACTUATORS, COORDINATE POWER REQUIREMENTS WITH ELECTRICAL. SHEET REFERENCE NUMBER:
UP TO 36" WX 24" H AND 14 GAGE IF DAMPER WIDTH EXCEEDS 36" OR HEIGHT EXCEEDS 24".
FIRE RATED PIPE PENETRATION
A3
N.T.S.
*** Support Value Engineering - It Pays ***
WHEN MULTIPLE DAMPER ASSEMBLIES ARE JOINED OR WHEN FASTENING DAMPER TO SLEEVE, DAMPERS SHALL BE
4
DETAI LS
FIRESTOP SYSTEM - THE DETAILS OF THE FIRESTOP SYSTEM SHALL BE AS FOLLOWS:
4. MOUNTING ANGLES SHALL BE A MINIMUM OF 1 1/2" X 1 1/2" X 14 GAGE AND BOLTED, WITH 1/4" - 20 BOLT, WELDED, OR SCREWED WITH NO. 10 SCREWS TO SLEEVE AT
MEXI CO
1. OPENING IN WALL SHALL BE A MINIMUM 1/8" PER FOOT LARGER THAN OVERALL SIZE OF DAMPER AND SLEEVE ASSEMBLY FOR GALVANIZED STEEL DAMPERS
LAS CRUCES,NEW
WALL CONSTUCTION
U.S.ARMY
NOTES
INDEX OF 50 OR LESS MAY BE USED.
RESERVE CENTER
SEE PIPE AND EQUIPMENT COVERING - MATERIALS* (BRGU) CATEGORY IN BUILDING MATERIALS DIRECTORY FOR NAMES OF MANUFACTURERS. ANY PIPE COVERING MATERIAL MEETING THE ABOVE SPECIFICATIONS AND BEARING THE UL CLASSIFICATION MARKING WITH A FLAME SPREAD INDEX OF 25 OR LESS AND A SMOKE DEVELOPED
7/22/2011
c:\pwworki ng\gbna\m oraja\dm s97636\LCARC_M-5010.dgn
THE OUTSIDE WITH AN ALL SERVICE JACKET. LONGITUDINAL JOINTS SEALED WITH METAL FASTENERS OR FACTORY-APPLIED SELF-SEALING LAP TAPE. TRANSVERSE JOINTS
m oraja
U.S.ARMY
STYLE "B"
DUCT SMOKE DETECTOR
OR WALL SURFACES. T RATING IS 0 HR WHEN SLEEVE IS USED.
FAX (714) 327-1601
DIAM.. (OR SMALLER) SLEEVE FABRICATED FROM NOM 0.019 IN. (0.48 MM) THICK GALV STEEL CAST OR GROUTED INTO FLOOR OR WALL ASSEMBLY FLUSH WITH FLOOR
RE-USEABLE FUSIBLE LINK
TEL (714) 327-1600
ASSEMBLY. SLEEVE MAY EXTEND A MAX OF 2 IN. (51 MM) ABOVE TOP OF FLOOR OR BEYOND EITHER SURFACE OF WALL. AS AN ALTERNATE, NOM 10 IN. (254 MM)
HUTTON CENTRE DRI VE,SUI TE 800
STEEL SLEEVE - (OPTIONAL, NOT SHOWN) - NOM 10 IN. (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL SLEEVE CAST OR GROUTED INTO FLOOR OR WALL
4
2.
LOUI SVI LLE DI STRI CT
(TYPICAL)
CORPS OF ENGI NEERS
DUCT CONNECTION
1A. SEE CONCRETE BLOCK (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS. DUCT CONNECTION (TYPICAL)
M .BETZ
FLOOR WALL ASSEMBLY - MIN.. 2-1/2 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF
Revi ewed by:
Desi gned by:
SEE NOTE #4
A.REED
SEE NOTE #4
A.REED
1/4"MIN. CLEARANCE
SECTION A-A
1.
W 912QR-11-R-0071
Sol i ci tati on No.
1" MIN. OVERLAP (4 SIDES)
4A
C.KORPASH
A
072811
Date:
1/4"MIN. CLEARANCE
Ckd by:
1
1" MIN. OVERLAP (4 SIDES)
Dwn by:
4A
B
I .FRANCO
3
LOUI SVI LLE,KENTUCKY
3
Rev.
4B
Subm i tted by:
2
SANTA ANA, CALI FORNI A 92707
2
A
Fi l e nam e:LCARC_M 5010. dgn
Mark
C2
GUIDELINES. REFER TO "SMACNA DUCT CONSTRUCTION STANDARDS,"LATEST EDITION.
1.REFER TO SPECIFICATIONS FOR ESCUTCHEON PLATE REQUIREMENTS.
COMBINATION FIRE/SMOKE DAMPER
M-5010 Sheet 136
of 222
N.T.S.
5
CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11
1
*** Safety Pays ***
2
4
5
LIFTING RING
EXPANSION TANK SUPPORT RODS
PRESSURE GAGE
TYP CHARGING VALVE
US Army Corps of Engineers
1/8
WITH DOUBLE NUTS AT TOP
3/4" FROM SUCTION SIDE OF PUMP
CHARGING VALVE
AND BOTTOM (TYP 4)
LOUISVILLE DISTRICT
BLADDER TYPE EXPANSION TANK,
Appr.
SEE SCHEDULE FOR SIZE
Date
MANUAL AIR VENT
"A" DIA
BLADDER TYPE EXPANSION TANK, SEE SCHEDULES FOR SIZES
CLIP ANGLE WELD TO SUPPORT ANGLE
D
NUTS AND WASHERS PROVIDE OPENING IN THE MOUNTING SEISMIC BRACE (TYP 1 FOR EACH
ANGLE "B"X"C"X"D"
1" HOSE GATE VALVE
RING TO ALLOW ACCESS FOR THE DRAIN VALVE
CORNER). INSTALL PRESSURE GAUGE
FROM AIR SEPARATOR
GAL 0-50
1/2"
0-100
D1
A
5/8"
B C 2"
2"
3"
3"
EXPANSION ANCHOR FOR SEISMIC
D
TYP
SUPPORT (TYP)
1/8
1/4"
SUSPENDED EXPANSION TANK DETAIL
TO FLOOR DRAIN
N.T.S.
6" CONCRETE PAD
PLATFORM FOR SUSPENDING EQUIPMENT FROM ABOVE
D3
3/4" DRAIN LINE, ROUTE
MOUNTING RAIL
PROVIDE 5mm STEEL CHECKER PLATE. MOUNT EQUIPMENT TO STEEL PLATE WITH NEOPRENE PAD.
1/4"
3/4" GATE VALVE
Descri pti on
TO SYSTEM PUMP
SIDE RAILS. SLOPE
D5
N.T.S.
EXPANSION TANK DETAIL N.T.S.
INTAKE VENTILATOR
Mark
ROOF STRUCTURE
FAN
COORDINATE WITH
DUCT SUPPORT CROSS MEMBER
INSULATION (UNIT)
DUCT FLANGE
CURB MOUNTING ANGLE 2’x2"x1/4"
C UNIT BASE
SPRING VIBRATION ISOLATION, TYP. REFER TO SPECS
PLAN
SEALING GASKET FURNISHED WITH CURB AROUND ENTIRE PERIMETER.
TYPICAL STRUCTURAL STEEL
GALVANIZED SHEET
MEMBER FOR EQUIPMENT
STRUCTURAL
5/8" ALL THREADED ROD,
ROOF STRUCTURE
FLASHING. FACTORY SEISMIC ROOF C L
NAILING STRIP DUCTWORK
ENTIRE PERIMETER OF
SPRING
UNIT.
VIBRATION
REFER TO STRUCTURAL
ISOLATION,
DRAWINGS FOR
TYP.
SPREADER MEMBER
REFER
LOCATION AND UPPER
4" RIGID ACOUSTICAL INSULATION WITHIN ENTIRE CURB FRAME ROOFING
M SHOTO AF R T T N EN E V M I P R D UI Q E
ATTACHMENT DETAILS
TO
1/8" SLACK AIRCRAFT CABLE, TYP. H A F
C L
M
Descri pti on
CURB EXTENDED AROUND
(TYP)
B-LINE STRUT CHANNEL, B-12, TYP.
OSA
0.5 CLEARANCE
TYP.
SPREADER LOCATION.
METAL COUNTER
FLEX. DUCT CONNECTOR
STEEL TRUSS,
MEMBERS FOR
Date
-
Appr.
EC
SIDE PANEL (UNIT)
C
S
C L
SPECS
THREADED ROD, TYP.
PARALLEL
OF 4 SIZED FOR LOAD
BLADE/
REFER TO STRUCTURAL AND
1/8" SLACK AIRCRAFT
ARCHITECTURAL DRAWING
CABLE, TYP.
ALL-DIRECTIONAL SEISMIC
LOW LEAK
SNUBBERS (TYP)
MOTORIZED DAMPER
NUMBER OF ISOLATION UNITS AS REQUIRED
FOR EQUIPMENT SUPPORT
AIR
FLEX.
FLOW
CONN
FILTER
MONITORING
(TYP)
RACK
DUCT
AIR UNIT
STATION FOR HEATING
TYPE "B" WELDED STEEL BASE SIMILAR TO MASON KSL/Z-1225
FRAMING MEMBERS
B-LINE STRUT CHANNEL B12, TYP. A3
COIL DETAILS SEE M-5000
PLAN
ELEVATION FLEX CONNECTION, TYP.
ROOF TOP UNIT CURB DETAIL
C2
N.T.S.
IN-LINE FAN SUSPENSION DETAIL
C3
N.T.S.
VIBRATION ISOLATION BASES
C4
N.T.S.
HEAT AND VENT UNIT SUSPENSION DETAIL N.T.S.
GRADE
FOR BACKFILL 40"
SEE
TROUGH
C1 M-5020
M-5000
U.S.ARMY
FACTORY SEISMIC CURB
A1
GREASE
SPECIFICATION SECTION 31 00 00 EARTHWORK
7/22/2011
Pl ot scal e:AS SHOW N
Pl ot date:
F-171-40-160
Project Code:
6,800 GAL., POTABLE HOT WATER UNDERGROUND
EXHAUST DUCT ENCLOSURE SHAFT
STORAGE TANK
* MAINTAIN A MIN. CLEARANCE OF 2FT. *
AND MASONRY ANCHOR
SIDES OF EXCAVATION
(TYP.)
CEILING
PEA GRAVEL 8’X 22’X 18" THK. REINFORCED CONCRETE PAD 6 AT 1 FT. EACH WAY
UL LISTED VAPOR PROOF FLOURESCENT LIGHT
MI N.
STRUCTURAL CHANNEL REINFORCEMENT
MI N.
THREADED ROD COUPLING WITH
A
12"
EXHAUST DUCT
18"
16 GA. WELDED GREASE
DETAI LS
(ABOVE CEILING ONLY)
BETWEEN TANK AND MEXI CO
TANK HOLD DOWN STRAP
LAS CRUCES,NEW
GENERAL CONTRACTOR
RESERVE CENTER
1-HOUR FIRE RATED CHASE BY
U.S.ARMY
WITH MIN. 3" AIR SPACE AROUND EXHAUST DUCT
7/22/2011
c:\pwworki ng\gbna\m oraja\dm s97636\LCARC_M-5020.dgn
REFER TO
DUCT THRU ROOF
FAX (714) 327-1601
TO HX-1
TEL (714) 327-1600
1-1/2" HWR
FROM HX-1
HUTTON CENTRE DRI VE,SUI TE 800
1-1/2" HWS
BIRD SCREEN
CLEANOUTS PER IMC
SANTA ANA, CALI FORNI A 92707
2" DHWS
4
2" DHWR
MI N
2" TANK VENT
3"
M-5020
LOUI SVI LLE DI STRI CT
CORPS OF ENGI NEERS
C3
SNUBBER. FOR DETAIL SEE
MIN
M .BETZ
VIBRATION ISOLATION STEEL BASE FRAME WITH SEISMIC
GAGE HATCH
DIRECT EVAPORATIVE COOLER
Subm i tted by:
ELECTRIC HEAT
Revi ewed by:
EXTENSION (TYP.)
Desi gned by:
MAKE-UP AIR UNIT
A.REED
FIBERGLASS MANWAY
SLAB
A.REED
PROTECTIVE CONCRETE
C.KORPASH
8’ X 23’ X 6" THK.
Ckd by:
TO ACCESS LADDER
Dwn by:
Date:
24" ACCESS MANHOLE
072811
B
I .FRANCO
Sol i ci tati on No.
Rev.
M-5010
W 912QR-11-R-0071
D2
LOUI SVI LLE,KENTUCKY
DUCT THRU WALL
Fi l e nam e:LCARC_M 5020. dgn
Mark
C1
U.L. CLASSIFIED GREASE FILTERS NOTES:
FOR HOOD DETAILS
1.CONTROL PANEL FOR LIGHTS AND FANS SHALL BE REMOTE MOUNTED.
SEE KITCHEN DRAWINGS SHEET REFERENCE NUMBER:
9:04:46 AM
m oraja
A1
KITCHEN HOOD AND SUPPLY/EXHAUST DUCT
A4
N.T.S.
1
2
*** Support Value Engineering - It Pays ***
M-5020
SECTION THRU 6800 GAL. TANK
Sheet 137
of 222
N.T.S.
4
5
CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11
1
*** Safety Pays ***
2
4
5
EVAPORATIVE COOLER UNITS SCHEDULE (INDIRECT/DIRECT)
STATIC
MIN
SERVES
MODEL NO
CFM
OSA CFM
EC 1-1
ARC BUILDING
EC 1-2
ARC BUILDING
EC 1-3
ARC BUILDING
EC 1-4
ARC BUILDING
EC 1-5
ARC BUILDING
EC 1-6
ARC BUILDING
EC 1-7
ARC BUILDING
EC 2-1
OMS BUILDING
ENERGY LABS
ASSEMBLY
PRESS
MOTOR
IN WG
HP
OA DB ^F
TOTAL EXT
1500
7500
3.6
0.5
RA
7.5
WB ^F
99
DB ^F
64
WINTER HEAT RECOVERY
IDEC WB ^F
78
DB ^F
65
WB ^F
74.6
OA
HX
DB ^F
WBDE % 70
WB ^F
18
DB ^F
LAT
72
45
DB
50
WB
74.6
ESP
CFM
DB
56.5
ELECTRICAL
LOUISVILLE DISTRICT
EAT EFF %
HOT WATER COIL WITH 30% PROPYLENE GLYCOL
FAN RPM
WB
58.0
APPROX
MAX IN WG
MIN
56.5
RA
EXHAUST FAN
(DEC)
OPERATING HP
PREFILTER/ FILTER
HEATING
EAT
CFM
LAT
EWT
LWT
^F
^F
^F
GPM
ROWS
FPI
DROP
TOTAL EXT 7500
56.5
1.2
MAX
PRESS
APD
REMARKS
WEIGHT MCA
FLA
VOLTS
PHASE
HZ
27.6
24.1
460
3
60
LB Appr.
MANUFACTURER
LOCATION
NO
INDIRECT EVAPORATIVE COOLER (IDEC)
(IN WG)
(FT)
0.3
1740
MERV 8/
3
3600
58
77
180
160
8.1
1
13
2.0
.2
2 3 4 5 6 7 8 9 10
9000
12 13 14 15
MERV 13 7000 ENERGY LABS
OFFICES
700
3.92
(5000 DX MODE)
7.5
0.5
99
64
78
65
74.2
56.4
70
18
72
1
50
45
1
1
1
7000
1.1
0.3
1740
MERV 8/
3
MERV 13 MERV 8/
ENERGY LABS
CLASSROOM
1400
7270
0.5
3.6
7.5
99
64
78
65
74.5
56.5
18
70
72
50
45
74.5
56.5
58.0
7270
56.5
1.1
0.3
1740
3
MERV 13
3000
63
82
180
160
7.0
1
13
2.0
1 61.3
.2
1 58.2
460
3
60
10000
59
80
180
160
8.9
1
13
2.0
.2
13
2.0
.2
23.2
13
2.0
.2
23.2
13
2.0
.2
22.3
27.6
24.1
460
3
60
PHYSICAL READINESS
650
ENERGY LABS
TOILETS
1800
ENERGY LABS
KITCHEN
ENERGY LABS
WEAPONS
ENERGY LABS
OFFICES
3350
3250
64
99
65
78
64
99
3
78
64
99
3
0.5
3.6
99
5
0.5
3.6
2600
825
5
0.5
3.6
2250
1000
0.5
3.6
65
78
64
72.7
71.4
65
78
55.8
55.4
72.3
65
18
70
55.7
73.5
18
70
18
70
56.2
18
70
72
45
50
72
45
50
72
45
50
72
45
50
72
45
50
72.7
55.8
71.4
57.4
55.4
72.3
56.8
0.9
3250
55.4
1.0
1740
0.3
0.3
1740
MERV 8/
2
MERV 13 MERV 8/
2
57.0
2250
55.7
0.8
0.3
1740
1-1/2
MERV 13 MERV 8/
56.2
57.7
2600
56.2
0.8
0.3
1740
1-1/2
MERV 13 MERV 8/
250
2200
3.6
3
0.5
99
64
78
65
72.6
56
70
18
72.6
56
57.2
2200
56
0.8
1740
0.3
1800
3250
MERV 13 MERV 8/
55.7
73.5
3350
55.8
3
MERV 13
2250
1900
1700
60
82
180
160
4.8
1
21.3
12 13 14 15
460
3
60
58
58
63
77
73
74
76
180
160
180
160
180
160
180
160
8.6
4.1
3.6
2.0
1
1
13
1
13
1
2.0
2.0
21.3
460
3
60
8000
12 13 14 15 16 18 19
21
21
2 3 4 5 6 7 8 9 10 21.1
460
3
60
5800
12 13 14 15 16 18 19
21
2 3 4 5 6 7 8 9 10
.2
22.3
.2
22.3
21.1
21.1
460
3
460
60
3
60
7250
12 13 14 15 16 18 19
21
2 3 4 5 6 7 8 9 10
7250
12 13 14
16 PROVIDE FACTORY MOUNTED SUMP PUMP INTEGRAL WITH UNIT FOR DEC SECTION. SIZED PER MANUFACTURER.
21 PROVIDE AIRFLOW VOLUME AND TRANSMITTER ON INLET TO SUPPLY FAN.
4 PROVIDE 2"(MERV 8 PRE-FILTERS) AND 4"(MERV 13 EFFICIENCY FINAL FILTER) 5 PROVIDE WITH STRUCTURAL STEEL BASE FRAME
9 PROVIDE 30% GLYCOL AT HEATING HOT WATER COIL 14 PROVIDE INTERNAL PIPE CHASE FOR ALL PIPING TO COILS, IDEC,AND DEC
19 PROVIDE INTERNAL 2" SPRING ISOLATORS FOR SUPPLY FAN
3 DOUBLE WALL CONSTRUCTION, OUTDOOR UNIT WITH PERFORATED LINER AT THE FAN SECTION
21
2 3 4 5 6 7 8 9 10 55
7 SINGLE POINT POWER CONNECTION WITH 480V/120V 11 PROVIDE WITH STAINLESS STEEL DRAIN PAN TRANSFORMER FOR CONV. OUTLETS, LIGHTS, HEAT 12 TEFC PREMIUM EFFICIENCY MOTORS TRACE, UPSTREAM OF DISCONNECT 8 PROVIDE WITH ROOF CURB 13 PROVIDE OUTSIDE AIR HOOD WITH 2" MERV 8 PRE- FILTER AND LOW LEAKAGE DAMPER
2 FURNISH WITH VFD AND INVERTER DUTY MOTOR ON SUPPLY & EXHAUST FAN
10 PROVIDE 120V HEATTRACE SYSTEM FOR ICW MAKE-UP WATER
18 19
12 13 14 15 16 18 19
20 PROVIDE SIDE DISCHARGE SUPPLY AIR OPENING WITH PLUG FAN
6 DUCT SMOKE DETECTOR IN SUPPLY DUCT
21
2 3 4 5 6 7 8 9 10
8000
15 PROVIDE FACTORY MOUNTED SUMP PUMP INTEGRAL WITH UNIT FOR IDEC, SIZED PER MANUFACTURER.
1 FOR CONDENSING UNIT (CU-1) INFORMATION SEE SCHEDULE BELOW
18 19
2 3 4 5 6 7 8 9 10
8000
D ENERGY LABS
18 19 20 21
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
3500
Date
MARK
SUPPLY FAN
US Army Corps of Engineers
Descri pti on
OUTDOOR AIR
DIRECT EVAPORATIVE COOLER
16 17 18 19 21
17 PROVIDE WITH CLEARWATER SYSTEMS DOLPHIN NON-CHEMICAL WATER TREATMENT PACKAGE OR EQUAL WITH MICROTRAC CONTROLLER. 18 PROVIDE MINIMUM OUTDOOR AIR AIRFLOW MONITORING STATIONS
HEAT AND VENTILATING UNIT SCHEDULE
LOCATION
MIN
SERVES
NO
ESP
CFM
CFM
HOT WATER COIL WITH 30% PROPYLENE GLYCOL FILTER
MOTOR
RPM
IN WG
EAT
HP
LAT
EWT
LWT
^F
^F
^F
ELECTRICAL
BASIS OF DESIGN APPROX
PRESS GPM
ROWS
FPI
DROP (FT)
APD
VOLTS
PHASE
HZ
IN WG
WEIGHT
MANUFACTURER
REMARKS Mark
MARK
SUPPLY FAN
MODEL NO
LB Appr.
OUTDOOR AIR
INDOOR UNIT SINGLE POINT POWER WITH VFD AND FACTORY MOUNTED CONTROL CENTER TO INCLUDE CONTROL CIRCUIT FUSING, CONTROL TRANSFORMER &
ARC
UNIT STORAGE
2000
2000
0.4
1050
3/4
2" MERV 13
18
68
180
160
12.0
2
13
7
0.12
120
1
60
250
ENERGY LABS
HVU 2-1
OMS ROOF
OMS WORK BAYS
4040
6060/4040
0.5
1800
5.0
2" MERV 13
18
60
180
160
19.4
2
13
3.5
0.25
460
3
60
2700
ENERGY LABS
INTEGRAL DISCONNECT SWITCH. Date
HVU 1-1
OUTDOOR UNIT NEMA 3R RATED VFD. SINGLE POINT POWER AND FACTORY MOUNTED CONTROL CENTER TO INCLUDE CONTROL CIRCUIT FUSING, CONTROL TRANSFORMER & INTEGRAL DISCONNECT SWITCH,OSA AIRFLOW MONITORING STATION, INTERNAL SPRING ISOLATORS.
C
SUPPLY DIFFUSER, REGISTER, AND GRILLE SCHEDULE CFM (BASED ON NC 30)
VEHICLE EXHAUST SCHEDULE (OMS BUILDING)
MARK
TYPE
FACE SIZE
NECK SIZE
NO
(FACE)
(INxIN OR DIA.)
(INxIN OR DIA.)
1 &2-WAY THROW
AREA SERVED
NO
MANUFACTURER
MODEL
HOSE
HOSE
REEL/
DIA.
LENGTH
FAN
IN.
FT.
TSP
CFM
IN.W.G.
REEL
FAN
DRIVE
MOTOR
HP
HP
REEL
FAN
V/PH/HZ
V/PH/HZ
THROW
PERFORATED SQUARE CEILING
24x24
6
-
0-125
TITUS PAS
PERFORATED SQUARE CEILING
24x24
8
-
126-200
TITUS PAS
PERFORATED SQUARE CEILING
24x24
10
-
201-300
TITUS PAS
PERFORATED SQUARE CEILING
24x24
14
-
401-500
TITUS PAS
SUPPLY GRILLE
8x8
6x6
0-100
-
TITUS 300RL
SUPPLY GRILLE
20x14
18x12
400-700
-
TITUS 300RL
SUPPLY GRILLE
32x22
30x20
850
-
TITUS 300RL
SUPPLY GRILLE
10x10
10x10
150-450
-
TITUS 300RL
LINEAR DIFFUSER
-
-
640
-
REMARKS Descri pti on
MARK
REMARKS
4-WAY
A
INTERNAL WIRING. FURNISH WITH FOUR FUNCTION (ON/OFF/UP/DOWN). SPECIAL REEL TO ACCOMODATE 40 FT HOSE
CONDENSING UNIT AND DX COIL SCHEDULE
MIN.
410A
4
4
(DB)
^F
^F
^F
^F
77.4
64.5
55
54
1 CONDENSING UNIT SHALL BE FACTORY TESTED AS PART OF THE EC UNIT.
VOLT
HZ
FUSE
2
SCROLL
7.5
480
3
60
15
33.4
5 WEIGHT INCLUDED IN EC 1-2
2000 5
1
2
3 4 5 6 7 8 9
9 MANUFACTURER’S GUARANTTED RATE OF 0.5% ANNUAL REFRIGERANT LEAKAGE.
6 PROVIDE MINIMUM 4 STEPS OF CAPACITY CONTROL UNLOADING
3
7 WITH HOT GAS BYPASS
E
F
DRUM LOUVER
-
J
SQUARE PLATE
24X24
B
20X10
600-700
-
6"
-
0-150
8"
-
151-250
COOLING
10"
-
251-400 Date:
RETURN, TRANSFER AND EXHAUST REGISTER AND GRILLE SCHEDULE
HEATING
FC 1
MITSUBISHI
FC 2
MITSUBISHI
FC 3
MITSUBISHI
FC 4
MITSUBISHI
FC 5
MITSUBISHI
80F/67F
MODEL
SIPRNET
PCA-A24
CAPACITY
CAPACITY
MBH (TOT)
MBH
24
26
HEAT PUMP
REFRIG.
RL
RS
SUPPLY
TYPE
SIZE
SIZE
CFM
410A
3/8"
5/8"
REMARKS
WEIGHT
600
71
1
2
3
4
MARK
TYPE
FACE SIZE
NECK SIZE
NO
(FACE)
(INxIN OR DIA.)
(INxIN OR DIA.)
PERFORATED SQUARE CEILING
24x24
6x6
0-200
20
TITUS PAR
TER
HEAT PUMP
24
26
410A
3/8"
5/8"
600
71
1
2
3
4
MAX
PERFORATED SQUARE CEILING
24x24
8x8
201-300
20
TITUS PAR
PERFORATED SQUARE CEILING
24x24
10x10
301-400
20
TITUS PAR
PERFORATED SQUARE CEILING
24x24
22x22
980-1300
20
TITUS PAR
PERFORATED SQUARE CEILING
24x48
22x46
1301-2800
20
TITUS PAR
EXHAUST GRILLE
8X8
6X6
0-100
22
TITUS 350FL
EXHAUST GRILLE
10X10
8x8
101-250
22
TITUS 350FL
EXHAUST GRILLE
12x12
10X10
251-350
22
TITUS 350FL
EXHAUST GRILLE
16x16
12X12
351-750
22
TITUS 350FL
EXHAUST GRILLE
26x16
24X14
751-1100
22
TITUS 350FL
EXHAUST GRILLE
38x20
36X18
1101-2000
22
TITUS 350FL
SECURITY EXHAUST GRILLE
16x16
16x16
615-750
22
H
SIDEWALL RETURN
38x24
36x20
1875
22
TITUS 350FL
I
EXHAUST GRILLE
10X10
8x8
101-250
22
TITUS 350FL
EXHAUST GRILLE
12x12
10X10
251-400
22
TITUS 350FL
REMARKS
NC
5
CAFE PCA-A24
CFM
5
C
ARMORER
PCA-A24
SUPPLY PCA-A24
OFFICE KITCHEN
PCA-A24
OFFICE
HEAT PUMP
HEAT PUMP
HEAT PUMP
24
410A
26
24
26
24
410A
410A
26
3/8"
3/8"
3/8"
5/8"
5/8"
5/8"
600
600
600
71
71
71
1
1
1
2
2
2
3
3
3
4
4
4
5
5
5
1 SINGLE POINT POWER. CONTROL PANEL TO INCLUDE MOTOR STARTER, CONTROL TRANSFORMER, AND INTEGRAL DISCONNECT
4 CEILING MOUNTED
2 CONDENSATE PUMP.
5 WALL MOUNTED REMOTE CONTROLLER
LOUI SVI LLE DI STRI CT
MANUFACT.
DUTY
Desi gned by:
AREA SERVED
NO
3 POWERED FROM HP UNIT
REFRIG
NO
TYPE MANUFACT.
MODEL
SEER
HSPF
VOLT
PH
HZ
MCA
WEIGHT
REMARKS G
HP 1 HP 2 HP 3 HP 4
MITSUBISHI
MITSUBISHI
MITSUBISHI
MITSUBISHI
PUZ-A24
PUZ-A24
PUZ-A24
PUZ-A24
410A
410A
410A
410A
208/ 16.8
16.8
10.9
10.9
230
208/ 230
16.8
10.9
10.9
1
60
60
208/ 230
16.8
1
1
60
208/ 230
1
60
19
19
19
19
165
MITSUBISHI
PUZ-A24
410A
16.8
10.9
208/ 230
1
60
19
165
9:05:21 AM
SHEET REFERENCE NUMBER:
165 14X14
12x12
401-650
22
TITUS 350FL
M-6000
165 EXHAUST GRILLE
1
MEXI CO
165
EXHAUST GRILLE HP 5
TITUS SG-3300RL
U.S.ARMY
MARK
A
SCHEDULES
ELECTRICAL BASIS OF DESIGN
LAS CRUCES,NEW
HEAT PUMP UNIT SCHEDULE (TRAINING BUILDING)
RESERVE CENTER
D
7/22/2011
c:\pwworki ng\gbna\m oraja\dm s97636\LCARC_M-6000.dgn
TITUS DL
ARI 95F/75F
MARK
m oraja
(1) 1-1/2" SLOT -
THERMA-FUSER TF-HC, DIGITAL WALL ADJUSTER
SPLIT SYSTEM FAN COIL UNIT SCHEDULE (TRAINING BUILDING)
BASIS OF DESIGN
TITUS FL-15-JT
120 CFM/FT. WITH BOOT.
8 CU-1 IS POWERED AND CONTROLLED FROM A SINGLE POINT POWER CONNECTION PROVIDED WITH EC 1-2. (STARTER, DISCONNECT SWITCH, AND CONTROLS ALL FACTORY PROVIDED)
REFRIGERANT PIPING SHALL BE FACTORY INSTALLED AND TESTED
B
UNIT FLA
2 UNIT SHALL BE MOUNTED ON STRUCTURAL BASE (SLEEPER SYSTEM) INDEPENDENT OF EC UNIT ROOF CURB
4
PH
(EA)
5000
REMARKS
WEIGHT
HP
Mark
208.2
(DB)
TYPE
7/22/2011
11.8
(WB)
QTY
Pl ot scal e:NONE
COOLING
(DB)
CFM
Pl ot date:
OFFICES
LABS
LAT
FAX (714) 327-1601
ENERGY
LAT
TEL (714) 327-1600
SIZE
EAT
Fi l e nam e:LCARC_M 6000. dgn
SIZE
EAT
M .BETZ
TYPE
RS
Subm i tted by:
CAPACITY
RL
HUTTON CENTRE DRI VE,SUI TE 800
REFRIG.
SANTA ANA, CALI FORNI A 92707
TOTAL
EER
4
DUTY
F-171-40-160
AREA SERVED
Project Code:
MANUFACT.
MBH 1 CU 1
ELECTRICAL 8
A.REED
NO
COMPRESSOR
CORPS OF ENGI NEERS
MARK
DX COIL(EC 1-2)
Revi ewed by:
COOLING
A.REED
460/3/60
W 912QR-11-R-0071
120/1/60
Sol i ci tati on No.
1.5
C.KORPASH
1/6
Ckd by:
3.0
Dwn by:
1400
I .FRANCO
40
8
CMW13
LOUI SVI LLE,KENTUCKY
CARMON
HUNG FROM STRUCTURE, DISCHARGE THRU ROOF. UNIT MOUNTED CONTROL PACKAGE INCLUDING STARTER, TRANSFORMER AND
Rev.
VEHICLE WORKBAYS
TSR
072811
TO
VX 2-2
U.S.ARMY
VX 2-1
2
*** Support Value Engineering - It Pays ***
4
18x18
16X16
651-1000
22
Sheet 138
TITUS 350FL
5
of 222
CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11
1
*** Safety Pays ***
2
4
PUMP SCHEDULE
5
DOOR AIR CURTAIN SCHEDULE (TRAINING BUILDING) US Army Corps of Engineers
BASIS OF DESIGN
MOTOR
MOTOR
BASIS OF DESIGN
LOUISVILLE DISTRICT
APPROX SERVES
MFR
MODEL
GPM
TYPE
TOTAL
NO.
EFFICIENCY
RPM
OPERATING HP
HEAD
V
PH
HZ
ARC HEATING
ARC
HOT WATER
HWP 1B
ARC HEATING
ARC
HOT WATER
MARK
LOCATION
SERVES
MAX
NO
WEIGHT
(FT) HWP 1A
REMARKS
MANUFACTURER
MODEL
MARS
48C
MAX
CFM
FPM
1700
1700
REMARKS
WEIGHT HP
V
.5
120
PH
HZ
FLA
LBS
60
9.8
-
Appr.
LOCATION
NO
(LBS)
SERIES B&G
90
48
INLINE
30
1750
45%
1
480
3
25
60
DAC 1
2
TRAINING BUILDING
1-1/2A SERIES B&G
90
INLINE
48
30
45%
1750
1
480
3
60
25
2
INLINE
74
70
55%
1750
5
480
3
60
75
2
3
INLINE
74
70
55%
1750
5
480
3
60
75
1
2
KITCHEN
1
FURNISH WITH WALL MOUNTED CONTROL
KITCHEN
Date
MARK
PANEL WITH MICROSWITCH.
1-1/2A ARC HEATING ARC
HOT WATER
D HWP 2B
ARC HEATING ARC
HOT WATER
SERIES B&G
80 SC
EXPANSION TANK SCHEDULE
2X2X9-1/2 SERIES B&G
80 SC
3
2X2X9-1/2 ARC HEATING
ARC
HWP 3
HOT WATER ARC HEATING
HWP 4
ARC
HOT WATER ARC HEATING
HWP 5
ARC
HOT WATER
BASIS OF DESIGN
SERIES
B&G
1535-356
18
INLINE
PL-55 SERIES
B&G
100
3500
45%
2
480
3
60
50
MARK
2
18
INLINE
PL-55
30
3250
40%
30
0.4
3250
40%
120
0.4
1
120
60
1
25
MECH RM
B&G
OMS
22
INLINE
80
OMS
25
60
1
50%
30
1750
1
3
480
60
50
HWP 7A HWP 7B
B&G
OMS
50%
30
1750
1
3
480
60
50
1
OMS
SERIES90
B&G
OMS
35
INLINE
45%
70
3450
3
3
480
60
50
1-1/2 AA
MECH RM
OMS
SERIES90
B&G
OMS
35
INLINE
45%
70
3450
3
3
480
60
50
TYPE
VOLUME -
ACCEPTANCE
(GAL)
VOLUME (GAL)
NO.
OPERATING
OPERATING
PRESSURE
TEMPERATURE
(PSIG)
^F
OPERATING HEIGHT
DIAMETER
WEIGHT
(IN)
(IN)
(LBS)
REMARKS
ET 1
MECHANICAL
ET 2
MECHANICAL
ET 3
MECHANICAL
ET 4
MECHANICAL
ET 5
MECHANICAL
ARC
ROOM
VERTICAL
B&G
D-260V
B&G
D-40V
B&G
PTA-455
B&G
D-40V
B&G
D-20V
B-1,2
2000
159
56
125
200
58
30
21.7
11.3
125
200
30
17
370
240.5
125
200
82
48
21.7
8
125
200
30
17
10.9
2.4
125
200
26
12
BLADDER
1 2 3 4 5 6 7 8 9 10 11
ARC
ROOM
B-1,2
VERTICAL BLADDER
300
1 2 3 4 5 6 7 8 9 10 11
2
1
ARC B-1,2
ROOM
VERTICAL BLADDER
5000
- 7 8 9 1 2 3 4 5 6 10 11
300
- 7 8 9 1 2 3 4 5 6 10 11
200
- 7 8 9 1 2 3 4 5 6 10 11
2
1-1/2X1-1/2X7B
MECH RM
1 STAND BY
22
INLINE
80
OMS
MODEL
2
1-1/2X1-1/2X7B
MECH RM
MFR.
2
SERIES HWP 6B
SERVICE
MAX
2
SERIES HWP 6A
LOCATION
NO.
SERIES
B&G
30
INLINE
DIMENSION
MAX
Descri pti on
HWP 2A
OMS
ROOM
B-3,4
VERTICAL BLADDER
3
2
OMS
ROOM
B-3,4
VERTICAL BLADDER
3
1-1/2 AA
2 MOTOR STARTER, CONTROLS, HOA, INDICATOR LIGHTS AND SELECTOR SWITCHES FURNISHED AS PART OF FACTORY PUMP CONTROL PANEL WITH DISCONNECT AND INSTALLED BY ELECTRICAL
3 PROVIDE VFD
1 30% PROPYLENE GLYCOL
4 PROVIDE SIGHT GLASS
7
PROVIDE WITH AUTOMATIC AIR VENT
10
PROVIDE WITH SEISMIC RESTRAINTS
2 PER ASME SECTION VIII DIVISION 1 STANDARDS
5 FURNISH WITH AIR RELEASE FITTING AND LEVEL GAGE
8
PROVIDE WITH AIR PURGER
11
PROVIDE 18" CLEARANCE FOR SYSTEM PIPING
3 PEPLACEABLE BLADDER DESIGN
6
9
PROVIDE WITH LIFTING RING
FACTORY PRE-CHARGED TO 12 PSIG
CAPACITY
LOCATION
MFR
MODEL
NO
TYPE
NO.
EFF.
PRESSURE
(MBH) 1
GPM
(AFUE)
RATING
POWER
TEMPERATURE
INPUT
(PSIG)
OUTPUT (GROSS)
EWT
LWT
^F
^F
OPERATING
PD
WEIGHT
(FT)
(LBS) V
Appr.
ASME MARK
CHEMICAL POT FEEDER
OPERATING
PH
REMARKS BASIS OF DESIGN
HZ MARK
ARC
B 1,2
BURNHAM
ALP 500
CONDENSING
125
95%
500
399
160 ^F
180 ^F
48
5
120
1
60
700
1 2 3 4 5 6 7
BURNHAM
ALP 285
CONDENSING
125
95%
285
220
160 ^F
180 ^F
22
5
120
1
60
400
1 2 3 4 5 6 7
MECH. RM
LOCATION
SERVICE
MFR.
FILL
OPERATING
MODEL
CAPACITY
CAPACITY
PRESS
NO.
(GAL)
(GAL)
(PSIG)
HP-5-ASME
5.0
6.3
200
NO.
MAX
Date
MIN.
BASIS OF DESIGN
Mark
HEATING HOT WATER BOILER SCHEDULE
OPERATING
NOZZLE SIZE
TEMPERATURE
REMARKS
(IN)
^F
C OMS MECH RM
1 RATINGS AT 4000 FEET ASL
2 PROVIDE MANUFACTURERS SEALED STAINLESS STEEL FLUE/COMBUSTION AIR KIT
5 BOILER CONTROL PANEL
6 STAINLESS STEEL HEAT EXCHANGER
7
3
4
STACKABLE UNITS WITH MOUNTING FRAME
CPF 1
MECHANICAL
HEATING HOT
ROOM
WATER
J.L.WINGERT
200
3/4
1 2 3 4 5 6 7
FULLY MODULATING 5:1 TURN DOWN
PROVIDE NEOPRENE RUBBER ISOLATION PAD
AIR / DIRT SEPARATOR TANK SCHEDULE
1 30% PROPYLENE GLYCOL
5
PROVIDE WITH 1/4" NPT AIR RELEASE VALVE
2 ASME CODE RATED
6
PROVIDE WITH 1/4" NPT PRESSURE GAUGE
3 DOME BOTTOM WITH SUPPORT LEGS
7
PROVIDE WITH SIGHT LEVEL AND SIGHT FLOW INDICATOR
Descri pti on
B 3,4
4 STEEL CONSTRUCTION WITH INTERNAL/EXTERNAL EPOXY COATING
AS 2
MECHANICAL
AS 3
MECHANICAL
ROOM
RL-3F
B&G
ARC
EAS-2"
B&G
125
270
GLYCOL MAKE-UP UNIT 160
1 2 3
125
270
MARK
1 2 3
100
LOCATION
SERVICE
MFR.
40
125
270
1 2 3
100
OMS
EAS-1"
B&G
3
125
270
ARC
MODEL
2
PROVIDE WITH STRAINER, HIGH CAPACITY AIR VENT FITTING AND MANUAL BLOWDOWN VALVE.
CAPACITY
GMU-30
B&G
WATER
OMS
CUT-IN
CUT-OUT
(PSIG)
(PSIG)
10-45
20-50
1 2 3 4 5 6
10-45
20-50
1 2 3 4 5 6
55 GAL
HEATING HOT
MECHANICAL
3 ASME 125 PSIG RATED
GMU-30
B&G
WATER
5 GPM/10GPM 55 GAL
ROOM
HOT WATER UNIT HEATER SCHEDULE
REMARKS
5 GPM/10GPM
ROOM
GFA 2
30% PROPYLENE GLYCOL
HEATING HOT
MECHANICAL
1 2 3
50
PRESSURE
NO.
GFA 1
B-3,4
ROOM
^F
NO.
B-3,4
MECHANICAL
30
EAS-2"
B&G
OMS
ROOM
96
(PSIG)
BASIS OF DESIGN
B-1,2
ROOM
AS 4 1
ARC B-1,2
(LBS)
1 PROVIDE WITH (1) 1/2 HP MOTOR PUMP, 115V/1PH/60HZ, NEMA 4X CONTROL PANEL
4 PRV, SHUT-OFF VALVES, PRESSURE SWITCHES AND GAUGES
2 LOW LEVEL FLOAT SWITCH
5 DISCONNECT BY ELECTRICAL. REFER TO ELECTRICAL DWGS
6
FOR PROPYLENE GLYCOL Mark
MECHANICAL
WEIGHT
TEMPERATURE
HC-18
0.5
1/60
120
1
60
20
1 2 3
PROPELLER MOUNT
60
340
180
160
1.3
0.5
1/60
120
1
60
20
UH 6
SEE
WALL
ARCH 60
340
180
160
1.3
0.5
1/60
120
1
60
20
1 2 3
SEE
ARC
WALL
ARCH
UNIT STORAGE
MOUNT
60
180
160
1.3
0.5
1/60
120
1
60
20
A
1
MODEL
MODERN FAN
CIRRUS HUGGER
VOLT
PH
HZ
WATTS
36"
115
1
60
85
52"
115
1
60
85
1 2
3
OFFICE / CLASSROOMS
50
1
2
3
5
1
2
3
4
6
7
/ MODERN FAN
CIRRUS HUGGER
ASSEMBLY
50
RCP 1 BRUSHED ALUMINUM BODY AND BLADES
MODINE
340
60
180
160
1.3
0.5
1/60
120
1
60
20
1 2
340
60
180
160
1.3
0.5
1/60
120
1
60
20
1 2 3
UNIT STORAGE
2 FAN SPEED CONTROLLER, WALL MOUNTED
3 CEILING MOUNTED BRACKET, HUGGER STYLE FAN
4
(1) ONE CEILING FAN LOCATED IN THE CENTER OF ASSEMBLY ROOM A102
V-42
950
60
180
160
3.1
0.6
1/30
120
1
60
50
1 2 3
UH 9
MODINE
HC-18
UNIT STORAGE
UNIT STORAGE
MECHANICAL RM
ELECTRICAL RM
MOUNT
MECHANICAL RM
VERTICAL
HC-18
PROVIDE MOUNTING BRACKET
ELECTRICAL RM
2
ELECTRICAL
BASIS OF DESIGN WATER
VERTICAL
60
950
180
160
3.1
0.6
1/30
120
1
60
50
1 2 3
MARK
REMOVAL
NO
PINTS/DAY
MANUFACT.
MODEL
THERMA-STOR
HI-E DRY 195
CFM
WEIGHT VOLT
PH
HZ
KW
115
1
60
1.25
REMARKS
MOUNT
60
340
180
160
1.3
0.5
1/60
120
1
60
20
1 2
3
PROPELLER
DH 1
190
540
110
1
2
3
MOUNT
340
60
180
160
1.3
0.5
1/60
120
1
60
20
1 2
3
340
60
180
160
1.3
0.5
1/60
120
1
60
20
1 2
3
1 6FT POWER CORD
2
3
INTERNAL CONDENSATE PUMP
PROPELLER MOUNT
KITCHEN SUPPLY FAN MAKE-UP AIR UNIT SCHEDULE
PROPELLER WALL
OMS MODINE
DEHUMIDIFIER SCHEDULE
WALL
OMS HC-18
(2) TWO CEILING FANS LOCATED IN THE PHYSICAL READINESS ROOM A126
WALL
ARC
MODINE
7
WALL
ARC
HC-18
6 (2) TWO CEILING FANS LOCATED IN EACH CLASSROOM A134 & A131
PROPELLER
ARC
MODINE
5 (3) THREE CEILING FANS LOCATED IN THE LOWER CEILING OF ASSEMBLY ROOM A102
PROPELLER
ARC MODINE
3
30% PROPYLENE GLYCOL
MOUNT
60
340
180
160
1.3
0.5
1/60
120
1
60
20
1 2
3
PROPELLER 3
ELECTRIC HEATER
BASIS OF DESIGN EXTERNAL
RATINGS AT 4000 FEET ASL
MARK NO
LOCATION MANUFACTURER
SERVES
CFM
MODEL
SP
DRIVE
MAX FAN RPM
(IN.
EVAPORATIVE COOLING
FAN MOTOR
ELECTRICAL DATA APPROX
EAT
LAT
KW
^F
^F
(#STAGES)
18
55
LAT
TYPE
GPM
WEIGHT HP
RPM
3/4
1750
V
PH
HZ
LBS
3
60
1000
REMARKS
WG)
GAS DETECTOR SCHEDULE KSF 1-1
GREENHECK
MSX109H12
TRAINING BUILDING
12 GREASE HOOD
1600
0.4
BELT
905
KITCHEN
(3)
73^F
DIRECT CELDEK
4
480
1 2 3 4 5 6
BASIS OF DESIGN ALARMS MARK
GD 1
POWER
DETECTED LOCATION
MFR
MODEL
OMS WORKBAY
BRASCH
GSE-NCM-1
REMARKS
GASES
NO.
LOW LEVEL
CO/NO2
CO = 35PPM
HIGH LEVEL
CO = 100PPM
V
120
NO2 = 1.0PPM NO2 = 5.0PPM
PH
1
HZ
60
1
SINGLE POINT OF POWER CONNECTION. MOTOR STARTER, CONTROL PANEL, CONTROLS, HOA FACTORY INSTALLED
5
PUMP FOR EVAPORATIVE COOLER
2
UNIT MOUNTED DISCONNECT SWITCH, NEMA 3R.
6
PROVIDE LOW LEAKAGE MOTORIZED DAMPER ON OUTSIDE AIR INTAKE
3
PRE-FAB FACTORY ROOF CURB.
4
MERV 13 FILTER.
1 2 3 4 5
1 HIGH LEVEL ALARM STARTS HIGH SPEED OF FANS
3 MICROPROCESSOR CONTROLLED AND FACTORY CALIBRATED UP TO 9000 SQUARE FEET OF COVERAGE
2 OUTPUT ALARMS AT BAS
4 POWER LOSS FAIL-SAFE MODE
SHEET REFERENCE NUMBER:
M-6010 Sheet 139
of 222
5 DIGITAL DISPLAY LOACL READOUT
AM 9:05:55
REMARKS
WALL
ARC
HC-18
NO
m oraja
MOUNT
UNIT STORAGE
MODINE
UH 12
ARC
HC-18
MODINE
V-42
UH 11
MANUFACT.
RCP
PROPELLER 340
WEIGHT
SIZE
WALL
UH 8
UH 10
7/22/2011
c:\pwworki ng\gbna\m oraja\dm s97636\LCARC_M-6010.dgn
UH 7
BLADE
1 2 3
PROPELLER MOUNT
SERVES
NO
PROPELLER UH 5
MARK
HUTTON CENTRE DRI VE,SUI TE 800
ARC UNIT STORAGE
MODINE
1.3
SCHEDULES
MODINE
160
4
UNIT STORAGE
HC-18
180
Desi gned by:
HC-18
60
340
WALL
ARC
MODINE
MOUNT
MEXI CO
UH 4
UNIT STORAGE
U.S.ARMY
UH 3
HC-18
RESERVE CENTER
UH 2
MODINE
ELECTRICAL
BASIS OF DESIGN
WALL
ARC
U.S.ARMY
UH 1
Date:
(FT)
F-171-40-160
(LB)
Project Code:
HZ
Revi ewed by:
PH
A.REED
V
W 912QR-11-R-0071
HP
Sol i ci tati on No.
DROP
CEILING FAN SCHEDULE
REMARKS
C.KORPASH
^F
WEIGHT
PRESS
Ckd by:
^F
GPM
Dwn by:
LWT
I .FRANCO
MODEL
EWT
LOUI SVI LLE DI STRI CT
EAT
LAS CRUCES,NEW
MANUFACT.
CFM
LOUI SVI LLE,KENTUCKY
TYPE
072811
LOCATION
NO
A.REED
MARK
B
ELECTRICAL
CORPS OF ENGI NEERS
HOT WATER COIL
BASIS OF DESIGN
Rev.
3 POLYETHYLENE TANK WITH CARBON STEEL STAND
7/22/2011
AS 1
OPERATING
PRESSURE
Pl ot scal e:NONE
NO.
OPERATING
Pl ot date:
NO
GPM
FAX (714) 327-1601
MODEL
TEL (714) 327-1600
MFR.
REMARKS
Fi l e nam e:LCARC_M 6010. dgn
SERVES
OPERATING
M .BETZ
LOCATION
MAX
Subm i tted by:
MARK
MAX
SANTA ANA, CALI FORNI A 92707
BASIS OF DESIGN
1
2
*** Support Value Engineering - It Pays ***
4
5
CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11
1
*** Safety Pays ***
2
4
EXHAUST FAN SCHEDULE
5
TANK SCHEDULE
US Army Corps of Engineers LOUISVILLE DISTRICT
MOTOR MARK
LOCATION
SERVES
CFM
MAX FAN
DRIVE
SP
NO
BASIS OF DESIGN
RPM
IN WG
BASIS OF DESIGN
APPROX
OPER REMARKS
WEIGHT HP
V
PH
HZ
RPM
MARK
LBS
MANUFACTURER
LOCATION
TYPE
SIZE
NO
MODEL
MANUFACTURER
MODEL
STORAGE
PRESS
(GALLONS)
RATING
LINING
Appr.
EXTERNAL
REMARKS
WT LBS
ROOM MECHANICAL
EF 1-3 EF 1-4 EF 1-5 EF 1-6
EF 1-7 EF 1-8 EF 1-9 EF 1-10
EF 1-11
BUILDING
ROOM
ARC
BREAK
BUILDING
ROOM
ARC
MAIL
BUILDING
ROOM
ARC
ARMS
BUILDING
VAULT
ARC
UNIT
BUILDING
STORAGE
ARC
UNIT
BUILDING
STORAGE
ARC
KITCHEN
BUILDING
HOOD
ARC
KITCHEN
BUILDING
HOOD
ARC
COPY
BUILDING
ROOM
ARC
TOILET
BUILDING
ROOM
1300
0.4
1400
0.4
700
1100
BELT
0.35
510
1100
BELT
1100
BELT
0.35
1300
BELT
1/3
1/3
1/6
1/6
120
1
120
1
120
1
120
1
60
1725
60
1725
60
100
1725
135SDB
COOK
200
1725
60
135SDB
COOK
200
120C2B
COOK
100
COOK
100C2B
1
1
1
1
2
2
2
3
3
3
2 3
4
HST 1
4
5
5
690
0.4
BELT
1000
1/6
120
1
60
1725
150
COOK
120SDB
1
2
3
4
2000
0.5
BELT
600
1/3
120
1
60
1725
700
COOK
210SDB
1
2
3
4
2000
0.5
BELT
600
1/3
120
1
60
1725
700
COOK
210SDB
1
2
3
4
HST 2
6
6
KENNEDY
SILICON
0.4
DIRECT
1650
1/8
120
1
60
1550
ACRUD
100
COOK
MECH RM
HELIODYNE
2150
1.75
BELT
1490
1 1/2
480
3
60
1725
500
COOK
350
0.4
BELT
1637
1/6
120
1
60
1725
100
COOK
2
3
5
ARC
JAN A103C
130
0.3
1200
DIRECT
ACEB
1
2
3
1
2
3 5
1
2
3 4
EF 2-2
EF 2-3
EF 2-4
EF 2-5
81W
120
1
-
60
20
COOK
650
0.35
1500
BELT
1/6
120
1
60
COOK
100
1725
80,000
1
2
3
4
1500
-
-
119
-
GLASS
-
GLASS
-
5
TANK SOLAR HOT WATER TANK
24" MANWAY WITH INTERNAL LADDER
3
INTERIOR SAND BLAST AND POTA-POX 20 LINING
5
2
42" COLLAR RING
4
EXTERIOR SANDBLAST AND 100 MIL FIBERGLASS COAT
INTEGRAL HEAT TRANSFER COIL, 30 gpm, 200MBH
COLD SIDE
BASIS OF DESIGN
HX 1
6 10
OPER
TOTAL SERVICE MANUFACTURER
6
HOT SIDE
GPM
MODEL
EWT
LWT
^F
^F
PD
B&G
BP400-30
DOMESTIC
18
180
GPM
PSI
160
10
18
EWT
LWT
^F
^F
120
PD
140
HEAT
TRANSFER
WT
EXCHANGED
AREA
LBS
PSI
(MBH)
(SQ FT)
10
178
3.53
REMARKS
POTABLE WATER RATED
20
HOT WATER
6
70C2B
GN-162
ELECTRICAL
100 C2B
1
2
3 5
6
MARK
AMB
200
0.4
1500
BELT
1/6
120
1
1725
60
100
COOK
70 C2B
75
0.3
BELT
1200
1/6
120
1
60
1725
75
COOK
60 C2B
3030/2020
0.75
BELT
1500
3/4
480
3
60
1725
350
COOK
150QMX
1
2
3 5
MODEL
6
1
2
3 5
6
1
2
3 4
7 8
GPM
PD
TEMP
MBH
(FT HD)
EWT
LWT
^F
^F NO. OF
(^F DB)
HD 1
HEAT CRAFT
WGS049
95
30
15.5
282
180
OPER
FAN MOTOR
160
1
WT VOLTAGE
(LBS)
208/3/60
400
HP
1/3
REMARKS
-
Date
OMS
WORK
BUILDING
BAY
OMS
WORK
BUILDING
BAY
ROOM
BUILDING OMS
MECHANICAL
BUILDING
ROOM
OMS
MEN’S
BUILDING
9 11
TWO SPEED FAN 3030/2020
0.75
1500
BELT
3/4
480
3
60
COOK
350
1725
150QMX
1
2
3 4
7 8
SOLAR HEATING COLLECTOR SCHEDULE 9 11
TWO SPEED FAN
BASIS OF DESIGN OPER
ELECTRICAL
OMS
1000
0.4
876
BELT
1/6
120
1
60
COOK
150
1725
135 SDB
1
2
3 4
MARK
SERVES
TYPE
GPM
NO 500
0.4
130
0.3
937
BELT
DIRECT
1200
1/6
81W
120
1
120
1
60
60
COOK
175
1725
COOK
20
-
150 SQN-HP
GN-162
1
1
2
2
SLOPE
PD
SIZE
(FT HD)
(FT2)
(LBS)
WT
REMARKS
MANUFACTURER
MODEL
HELIODYNE
GOBI
ARC
GLAZED PLATE
1
20
32
200
-
HELIODYNE
GOBI
OMS
GLAZED PLATE
0.8
20
32
200
-
3 4
3 4
SC 1 THRU SC 30
WOMEN’S
BUILDING
130
0.3
DIRECT
0.4
BELT
1200
81W
120
1
60
-
20
COOK
150
COOK
OMS
EF 2-7
96"W X 60"H
1
NO
OMS
EF 2-6
WATER
BASIS OF DESIGN
BUILDING
EF 2-1
HOT WATER
100R15DM
165CPS
125
HEAT DUMP FLUID COOLER SCHEDULE
BUILDING
EF 1-14
SOLAR
MECH RM
MANUFACTURER JAN A121
OMS
HSTG 119
NO 1
6800
PLATE FRAME HEAT EXCHANGERS
A144
ARC
ARC
SOLAR
MARK 360
90"X226"
STORAGE
BUILDING
850
1000
1
MOTOR STARTER FURNISHED AND INSTALLED BY ELECTRICAL.
4
2
BACKDRAFT DAMPER.
3
FURNISH WITH CONTACTOR FOR BAS CONTROL WIRED BY ELECTRICAL.
1/6
120
1
60
1725
GN-162
135SDB
7 INLET SAFETY GUARD.
10
UL762.
5 ROOF CURB.
8
MOUNTING RAIL.
11
SPARK RESISTANT CONSTRUCTION.
6 UNIT MOUNTED DISCONNECT SWITCH, NEMA 3R.
9
MOTOR COVER.
UNIT MOUNTED DISCONNECT SWITCH, NEMA 1.
1
1
2
2
3 4
SC 31 THRU
3 4
SC 34
Descri pti on
EF 1-13
C
ROOM
BUILDING
TANK
STEEL
LINING
ELECTRICAL ARC
EF 1-12
UNDERGROUND
Descri pti on
BUILDING
POTABLE HWT 1
Mark
ELECTRICAL
ARC
EF 1-2
D
ARC
Appr.
EF 1-1
Date
(PSIG)
INTAKE AND RELIEF SCHEDULE BASIS OF DESIGN
STATIC CFM
SERVES
TYPE
DROP
NO
FURNISH WITH ROOF CURB
MECH RM
COOK
GI
INTAKE
1300
0.017
24"X24"
12"X12"
INTAKE
500
0.017
12"X12"
31"X27"X12"
100
FURNISH WITH ROOF CURB
COOK
16"X16"
INTAKE
1000
0.017
16"X16"
31"X39"X12"
150
FURNISH WITH ROOF CURB
INTAKE
850
0.017
16"X16"
31"X39"X12"
150
FURNISH WITH ROOF CURB
INTAKE
2800
0.017
36"X36"
63"X68"X23"
300
FURNISH WITH ROOF CURB
RELIEF
2000
0.011
24"X24"
37"X39"X12"
175
FURNISH WITH ROOF CURB
RELIEF
2000
0.011
24"X24"
37"X39"X12"
175
FURNISH WITH ROOF CURB
RELIEF
300
0.011
12"X12"
125
250
FURNISH WITH ROOF CURB
51"X39"X15"
51"X39"X15"
175
FURNISH WITH ROOF CURB
STORAGE
COOK
16"X16" GI
WORK BAYS
COOK
36"X36" GI
EF 1-6
COOK
BLDG
24"X24" GR
EF 1-7
COOK
BLDG
24"X24" GR
7/22/2011
175
24"X24"
Pl ot scal e:NONE
0.017
Pl ot date:
1600
FAX (714) 327-1601
INTAKE
Fi l e nam e:LCARC_M 6020. dgn
24"X24"
M .BETZ
FURNISH WITH ROOF CURB
Subm i tted by:
100
31"X27"X12"
F-171-40-160
12"X12"
Project Code:
0.017
W 912QR-11-R-0071
300
Sol i ci tati on No.
INTAKE
TEL (714) 327-1600
TRAINING
12"X12"
HUTTON CENTRE DRI VE,SUI TE 800
RV 3
FURNISH WITH ROOF CURB
24"X24" COOK
BLDG
TRAINING
175
GI
OMS
RV 2
51"X39"X15"
SANTA ANA, CALI FORNI A 92707
COOK
ELECT RM
ELECT RM
OMS
TRAINING
24"X24"
GI
OMS
RV 1
0.017
4
BLDG
2000
Revi ewed by:
IV 8
INTAKE
GI
GI
OMS
BLDG
24"X24"
A.REED
MECH RM
BLDG
IV 7
FURNISH WITH ROOF CURB
GI
BLDG
BLDG
175
C.KORPASH
BLDG
IV 6
IV 9
COOK
51"X39"X15"
Ckd by:
TRAINING
EF ROOM
24"X24"
Dwn by:
IV 5
BLDG
0.017
I .FRANCO
TRAINING
COOK
2000
LOUI SVI LLE DI STRI CT
IV 4
UNIT STORAGE
INTAKE
GI
LOUI SVI LLE,KENTUCKY
TRAINING
BLDG
24"X24"
Rev.
IV 3
COOK
Date:
TRAINING
LBS
(IN)
072811
IV 2
UNIT STORAGE HVU-1
(IN)
Desi gned by:
TRAINING
(IN WC)
HOOD
A.REED
B
IV 1
MODEL
REMARKS
WEIGHT THROAT
Mark
MANUFACTURER
PRESSURE
CORPS OF ENGI NEERS
LOCATION
OMS VENTILATION SCHEDULE
APPROX
U.S.ARMY
MARK
ARC VENTILATION SCHEDULE
DIMENSIONS
RV 7
BAYS
OMS
WORK
BLDG
BAYS
OMS
WORK
BLDG
BAYS
OMS
WORK
BLDG
BAYS
COOK
30PR
RELIEF
3030
0.1
30.75
250
250
FURNISH WITH ROOF CURB
COOK
30PR
RELIEF
3030
0.1
30.75
250
250
FURNISH WITH ROOF CURB
COOK
20PR
RELIEF
1400
0.09
20.5
100
250
FURNISH WITH ROOF CURB
COOK
20PR
RELIEF
1400
0.09
20.5
100
250
FURNISH WITH ROOF CURB
MEXI CO
BLDG
U.S.ARMY
A
WORK
SCHEDULES
RV 6
GR
EF 1-5
OMS
12"X12"
LAS CRUCES,NEW
RV 5
COOK
RESERVE CENTER
RV 4
STORAGE
BLDG
7/22/2011
c:\pwworki ng\gbna\m oraja\dm s97636\LCARC_M-6020.dgn
UNIT
SOLAR HEAT EXCHANGER AND CONTROL SCHEDULE BASIS OF DESIGN MARK
TYPE
GPM
NO MANUFACTURER
HELIODYNE
REMARKS
SHEET REFERENCE NUMBER:
(FT HD)
MODEL
HPAK-24
MBH
HEAT TRANSFER
4
5
M-6020 24
-
Sheet 140
APPLIANCE
of 222
9:06:33
m oraja
AM
HPAK 1
PD
1
2
*** Support Value Engineering - It Pays ***
4
5
CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11
1
*** Safety Pays ***
2
4
5
US Army Corps of Engineers
Date
Appr.
LOUISVILLE DISTRICT
1-1/2" HWS/R
3/4" HWS/R
UH-9 (1.3 GPM)
H/C
D
3/4" HWS/R
1-1/4" HWS/R
3/4" HWS/R
UH-10 (1.3 GPM)
H/C
3/4" HWS/R
1-1/2" HWS/R
3/4" HWS/R (TYP) Descri pti on
H/C
EC 1-5 (8.6 GPM)
H/C
H/C
H/C
UH-4 (1.3 GPM)
H/C
A1
UH-6 (1.3 GPM)
HVU-1 (12.0 GPM)
UH-5 (1.3 GPM)
FOR CONT SEE M-7010
3/4" HWS/R
3" 3/4" HWS/R 1-1/2" HWS/R
DPT 2-1/2"HWS/R
Mark
1 1/4" HWS/R
Appr.
H/C
1" HWS/R
1-1/2" HWS/R
Date
UH-3 (1.3 GPM)
3/4" HWS/R
1-1/4" HWS/R
C 1" HWS/R
2" HWS/R H/C
H/C
HVU 2-1 (19.4 GPM)
3/4"HWS/R
Descri pti on
EC 2-1 (2.0 GPM)
2-1/2"HWS/R H/C
H/C
UH-7 (3.1 GPM)
UH-8 (3.1 GPM)
A1 FOR CONT SEE
3/4" HWS/R
3/4" HWS/R
M-7020 2"HWS/R
3/4" HWS/R 1-1/2" HWS/R
3/4"HWS/R H/C UH-11 (1.3 GPM)
H/C EC 1-7 (3.6 GPM)
UH-12 (1.3 GPM)
Mark
H/C
2
OMS-HOT WATER HEATING DIAGRAM SCALE :NONE
1
7/22/2011
Pl ot scal e:NONE
Pl ot date:
Fi l e nam e:LCARC_M 7000. dgn
TEL (714) 327-1600
FAX (714) 327-1601
M .BETZ
Subm i tted by: HUTTON CENTRE DRI VE,SUI TE 800
SANTA ANA, CALI FORNI A 92707
F-171-40-160
Project Code:
Revi ewed by:
A.REED
C.KORPASH
EC 1-4 (4.8 GPM)
ARC-HEATING HOT WATER DIAGRAM SCALE :NONE
U.S.ARMY
A
EC 1-3 (8.9 GPM)
H/C
RESERVE CENTER
EC 1-2 (7.0 GPM)
H/C
7/22/2011
c:\pwworki ng\gbna\m oraja\dm s97636\LCARC_M-7000.dgn
H/C
4
EC 1-1 (8.1 GPM)
DI AGRAMS
EC 1-6 (4.1 GPM)
LOUI SVI LLE DI STRI CT
H/C
U.S.ARMY
H/C
1"HWS/R
1-1/4" HWS/R
1-1/4" HWS/R
MEXI CO
MANIFOLD MOUNTED ON WALL OF OMS MECHANICAL ROOM
1-1/2" HWS/R
LAS CRUCES,NEW
2" HWS/R
Ckd by:
DPT
Dwn by:
1-1/2" HWS/R
Desi gned by:
1-1/4" HWS/R (12 LOOPS 10 GPM)
LOUI SVI LLE,KENTUCKY
Date:
1" HWS/R
072811
1"HWS/R
I .FRANCO
Sol i ci tati on No.
Rev.
UH-1 1.3 GPM)
CORPS OF ENGI NEERS
UNDERSLAB RADIANT HEATING VALVE MANIFOLD ASSEMBLY
102F
3-WAY MIXING VALVE
UH-2 (1.3 GPM)
CONTRACTOR TO VERIFY EXACT ROUTING AND LOCATION OF PIPING AND LOOPS
82F
CIRCULATING PUMP, 10 GPM, 15 FEET HEAD
H/C
A.REED
(12) 5/8" TUBING LOOPS UNDER SLAB 9" OC
B
H/C
W 912QR-11-R-0071
2 1/2"HWS/R
1-1/4" HWR
SHEET REFERENCE NUMBER:
M-7000 9:07:56 AM
m oraja
Sheet 141
1
2
*** Support Value Engineering - It Pays ***
4
5
of 222
CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11
1
*** Safety Pays ***
2
4
5
US Army Corps of Engineers
Date
Appr.
LOUISVILLE DISTRICT
PSV SET TO 125 PSIG DISCHARGE ON ROOF (TYP.5) SC-1
SC-2
SC-3
SC-4
SC-5
SC-6
SC-25
SC-26
SC-27
SC-28
SC-29
SC-30
D
GLAZED PLATE SOLAR COLLECTORS
SC-8
SC-9
SC-10
SC-11
SC-12
SC-13
SC-14
SC-15
SC-16
SC-17
SC-18
SC-19
SC-20
SC-21
SC-22
SC-23
SC-24 Descri pti on
SC-7
1" SHWR (TYP.) 1" SHWR
1-1/4" SHWR
1-1/2" SHWR
1" SHWS (TYP.)
1-1/4" SHWR 1-1/4" SHWS
1-1/2" SHWS
1" SHWR
1-1/2" SHWS
EQUIPMENT LOCATED ON ROOF
1" SHWS
AUTOMATIC AIR VENT
PSV SET TO 125 PSIG TO DISCHARGE TO FD
3" HWS TO HEATING SYSTEM ZONES FOR CONTINUATION
2" DHW
1" DOMESTIC HOT WATER RETURN
2" DHWR
1-1/2" HWS 3" HWR FROM HEATING SYSTEM ZONES FOR CONTINUATION
1-1/2" DHWR
2" SHWS
SEE SHEET M-7000
SEE SHEET M-7000
BALANCING VALVE
M
2" DOMESTIC COLD WATER SUPPLY
HD-1
2" SHWS
1-1/2" HWR
C1
HEAT DUMP
CIRCUIT SETTER
Mark
1-1/2" DHWS
Appr.
2" DOMESTIC HOT WATER SUPPLY
FOR CONTINUATION SEE PLUMBING DRAWINGS Date
P-411A 3/4" DRAIN
HEAT EXCHANGER [HX-1]
3-WAY CONTROL VALVE
VLV-S1-01
DOMESTIC HOT WATER TANK
HWP-5
ET-3
HWT-1
DIAPHRAGM EXPANSION TANK SEE DETAIL
HWP-2A
2" SHW S
3" HW R
UNDERGROUND
C
HWP-2B
D2
M-5020 3" HWR
2" SHW R
FLEXIBLE COUPLING, TYP
PRESSURE RELIEF VALVE, DISCHARGE TO FD (TYP.)
MULTI PURPOSE VALVE
TO DRAIN
(GATE, BALANCING, CHECK
PRESSURE REDUCING VALVE SET AT 15 PSIG
Descri pti on
AUTOMATIC AIR VENT
AND METERING), TYP
ICW MAKE-UP, THERMOMETER
1" ICW
HWP-1A
3" HW R
3" HWR
3" HWS GATE VALVE (TYP.)
2" SHWS
AUTOMATIC AIR VENT
HWS
3" HWS
AS-2 LSL
LSLL
M-5000
D5
HWP-3
GFA-1
3/4" HB
GLYCOL FILL ASSEMBLY COMBINATION PRESSURE AND
ET-2
DIAPHRAGM EXPANSION TANK
TEMPERATURE GAGE (TYP.)
7/22/2011
Pl ot scal e:NONE
Pl ot date:
Fi l e nam e:LCARC_M 7010. dgn
F-171-40-160
Project Code:
FAX (714) 327-1601
HUTTON CENTRE DRI VE,SUI TE 800
D1
M-5020
N.T.S.
RESERVE CENTER
1
ARC- HOT WATER SYSTEM PIPING SCHEMATIC
U.S.ARMY
A
7/22/2011
c:\pwworki ng\gbna\m oraja\dm s97636\LCARC_M-7010.dgn
SEE DETAIL
TEL (714) 327-1600
AQUASTAT (TYP.)
PI PI NG SCHEMATI C
3"
U.S.ARMY
PIPE CAP
SANTA ANA, CALI FORNI A 92707
DIRT LEG
ARC HOT W ATER SYSTEM
B-2
4
PS BOILER
MEXI CO
M
LOUI SVI LLE DI STRI CT
SHUT OFF COCK
LOUI SVI LLE,KENTUCKY
CORPS OF ENGI NEERS
M-5020
GAS SUPPLY
LAS CRUCES,NEW
3" HW R
HEAT STORAGE TANK 3/4" HB
M .BETZ
SEE DETAIL
3"
A2
Revi ewed by:
SEE DETAIL
EXPANSION TANK
Desi gned by:
DIAPHRAGM 3/4" HB
Dwn by:
CHEMICAL POT FEEDER
D.O’ CALLAGHAN
2" SHWR
ET-1
3"
Ckd by:
B-1
A.REED
W 912QR-11-R-0071
Sol i ci tati on No.
Rev. Date:
BOILER
R.SALLW ASSER C.KORPASH
3/4"
HST-1 072811
3" HW S
AQUASTAT,
B
M
TO DRAIN
AS-1
Subm i tted by:
HWP-1B
3"
Mark
3" HWS
2" SHW R
VENT UP THRU ROOF (TYP.)
FE
FE
3/4"
COMBUSTION AIR INTAKE PIPED TO EXTERIOR (TYP.)
3" HW S
HWP-4
SHEET REFERENCE NUMBER:
M-7010 of 222
9:10:03
m oraja
AM
Sheet 142
1
2
*** Support Value Engineering - It Pays ***
4
5
CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11
1
*** Safety Pays ***
2
4
5
US Army Corps of Engineers
Appr.
LOUISVILLE DISTRICT
AUTOMATIC AIR VENT
Date
PRESSURE RELIEF VALVE, DISCHARGE TO FD (TYP.)
TO DRAIN
AIR SEPARATOR
PRESSURE REDUCING GATE VALVE, TYP
VALVE SET AT 30 PSIG THERMOMETER
FLEXIBLE TYPE MECHANICAL COUPLINGS TYP.
CW MAKE-UP,
D PRESSURE GAGE, TYP 1" CW 2" HWR
2" HWR
2" HWR
MULTI PURPOSE VALVE (GATE, BALANCING, CHECK
COMBUSTION AIR INTAKE PIPED TO EXTERIOR (TYP.)
AND METERING), TYP
FE
2" HWS
2" HWS
2" HWS
VENT UP THRU ROOF (TYP.)
1"
AS-3
HWP-6A 2" HW S
2" HW S
FROM HEATING SYSTEM ZONES FOR CONTINUATION SEE SHEET M-7000
Descri pti on
TO HEATING SYSTEM ZONES FOR CONTINUATION SEE SHEET M-7000
GAS SUPPLY
SHUT OFF COCK
BOILER SYSTEM CONTROL PANEL
3/4"
HWP-7B
DIRT LEG
BOILER
BOILER
B-3
B-4
PIPE CAP
ET-4
DIAPHRAGM
SEE DETAIL
Mark
3/4" HB
EXPANSION TANK
D1 Appr.
2" HW R
3/4"
HWP-6B
M-5020
POT FEEDER
HWP-7A
A2
Date
AQUASTAT
CHEMICAL
COMBINATION PRESSURE AND
SEE DETAIL M-5000
TEMPERATURE GAGE
C
PSV SET TO 125 PSIG DISCHARGE ON ROOF
SC-31
SC-32
SC-33
SC-34
1" SHWS
Descri pti on
GLAZED PLATE SOLAR COLLECTORS AQUASTAT,
2" HWR
HST-2
2" HWS
1" SHW R
1" HWR
1" HWS
H0T WATER STORAGE TANK
1" HWR
Mark
3/4" HB 1" HWS
SOLAR HOT WATER
SOLAR HOT WATER SYSTEM HEAT EXCHANGER AND CONTROL PACKAGE HPAK-1
U.S.ARMY
A
OMS- HOT WATER SYSTEM PIPING SCHEMATIC
7/22/2011
N.T.S.
7/22/2011
Pl ot scal e:NONE
Pl ot date:
4
FAX (714) 327-1601
HUTTON CENTRE DRI VE,SUI TE 800
G.HADDAD
Subm i tted by:
F-171-40-160
Project Code:
Revi ewed by:
OMS HOT W ATER SYSTEM
M-5020
MEXI CO
D5
SEE DETAIL
LAS CRUCES,NEW
EXPANSION TANK
RESERVE CENTER
DIAPHRAGM
PANEL
PI PI NG DI AGRAM
ET-5
SYSTEM CONTROL
1
TEL (714) 327-1600
GFA-2
c:\pwworki ng\gbna\m oraja\dm s97636\LCARC_M-7020.dgn
Dwn by:
U.S.ARMY
FILL ASSEMBLY
LOUI SVI LLE DI STRI CT
FM GLYCOL
LOUI SVI LLE,KENTUCKY
Desi gned by:
3/4"
PS
D.O’ CALLAGHAN
LSLL
CORPS OF ENGI NEERS
LSL
Ckd by:
1" SHWS
A.REED
Date:
121710
B
W 912QR-11-R-0071
Sol i ci tati on No.
1"
R.SALLW ASSER C.KORPASH
Rev.
AS-4
Fi l e nam e:LCARC_M 7020. dgn
AUTOMATIC AIR VENT
SANTA ANA, CALI FORNI A 92707
TO DRAIN
SHEET REFERENCE NUMBER:
M-7020 of 222
9:12:44
m oraja
AM
Sheet 143
1
2
*** Support Value Engineering - It Pays ***
4
5
CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11
1
*** Safety Pays ***
2
4
5
GENERAL NOTES A. FOR MECHANICAL ABBREVIATIONS, SYMBOLS, AND NOTES REFER TO DRAWING M-0010. FOR CONTROL ABBREVIATIONS, SYMBOLS, AND NOTES REFER TO LL
LOW LIMIT (FREEZE STAT)
N.O.
NORMALLY OPEN
LOUISVILLE DISTRICT
DRAWING M-8000. B. DUCT SMOKE DETECTORS AND ADDRESSABLE
MEASURED VARIABLE OR CONTROL DEVICE
Appr.
CONTROLS & INSTRUMENTATION
US Army Corps of Engineers
CONTROL DEVICES PROVIDED AND CONNECTED TO
TS 1
NO2
FIRE ALARM SYSTEM BY DIVISION 28. SEE DIVISION
NITROGEN DIOXIDE SENSOR
INSTRUMENT OR DEVICE NOT LOCATED IN AN ENCLOSURE
OA
OUTDOOR AIR
PD
PRESSURE DIFFERENTIAL SENSOR
PDI
PRESSURE DIFFERENTIAL INDICATOR
Date
28 FOR ADDITIONAL INFORMATION.
INSTRUMENT OR DEVICE IDENTIFICATION NUMBER
KEY NOTES
MEASURED VARIABLE OR CONTROL DEVICE AX
1
D
BUILDING NETWORK BACKBONE POINTS FOR USE OF BAS SYSTEM BY DIVISION 27. NECESSARY
INSTRUMENT OR DEVICE LOCATED IN AN ENCLOSURE
PI
PRESSURE INDICATOR
PT
PROGRAMMABLE THERMOSTAT
CABLE AND NETWORK HARDWARE BY BAS SYSTEM CONTRACTORS. 2
BAS SHALL BE PROVIDED WITH WEB-ENABLED INTERFACE AND SHALL BE REMOTELY ACCESSIBLE
AF
AFS
BACNET IP ON BUILDING ETHERNET BACKBONE (LAN)
HEAT AND VENT UNIT HVU 2-1
BAS SUB-NETWORK BACNET MS/TP 2
EXHAUST FANS
FLOOR RADIANT HEATING
EC 2-1
3
AFMS
DESCRIPTION
R
REFRIGERANT SENSOR
S
TEMPERATURE, RELATIVE HUMIDITY AND CO2 SPACE SENSOR
SD
SMOKE DETECTOR
AX
COORDINATE NETWORK CHARACTERISTICS AND REQUIREMENTS WITH BASE IT DEPARTMENT FOR
AIR FLOW
AIR FLOW SWITCH
AIR FLOW METERING STATION SP
3
VIA INTERNET USING STANDARD WEB BROWSER.
DUCT STATIC PRESSURE
WEB SERVER. 3
FACTORY MOUNTED UNIT CONTROL PANEL
4
PROVIDE AN ENERGY MONITORING/SUSTAINABLE
Descri pti on
ABBREV
STRATEGIES "DASHBOARD" SCREEN FOR PUBLIC ACCESS IN LOBBY A101. SEE ARCHITECTURAL
AUXILIARY CONTACT
DRAWINGS FOR LOCATION AND SPECIFICATION. SS CO
START/STOP CONTROL
CARBON MONOXIDE DETECTOR MONITOR/SCREEN SHALL BE BUILT FOR OUTDOOR
BACNET WEB SERVER
1
1
BACNET ROUTER/BUILDING CONTROLLER (BC)
C
T
THERMOSTAT
TI
TEMPERATURE INDICATOR
APPLICATIONS.
COMMON CONTROLS CONTRACTOR SHALL PROVIDE
INTERVAL DATA RECORDER FC-MON IDR-8-B
120V/24V TRANSFORMER AS REQUIRED
CD
CONTROL DAMPER
CI
CURRENT INPUT
GRAPHICAL INTERFACE TO MONITOR THE FOLLOWING ENERGY USAGE AND DISPLAY A REAL-TIME SNAPSHOT OF THE ARC BUILDING AND
COMM. CABLE
TS
TEMPERATURE SENSOR
OMS BUILDING SEPARATELY. -DELIVERED ELECTRICAL ENERGY
CR
CURRENT RELAY
VFD
VARIABLE FREQUENCY DRIVE
120V
PULSE OUTPUT
VLV
C
FLOW METER
FM
Mark
-WATTS/SQ.FT -YEARLY GAS CONSUMPTION ELECTRONIC INTERLOCK WIRING
(TOTAL CFH) -YEARLY=WATER CONSUMPTION
DI
DAMPER POSITION INDICATOR CONTROL SYSTEM/THERMOSTAT WIRING
FM
-POWER FACTOR (%) -CURRENT LOAD (AMPS)
DIRECT EVAPORATIVE COOLER
E-MON D-MON SERIES 3000
PULSE OUTPUT
VALVE
Appr.
CONDENSING UNIT
Date
CU
DEC
INTERNET
-REAL POWER (KW) -APPEARENT POWER (KVA)
ELECTRIC METER SERIAL GATEWAY
(KWH)
(GAL/YEAR) -AVERAGE MONTHLY WATER
FLOW METER
DP
CONSUMPTION (GAL/MONTH)
DIFF. PRESSURE SWITCH CM
NATURAL GAS FLOW METER
DOMESTIC WATER FLOW METER
ROOTS METER SOLID STATE PULSER
TURBINE FLOW METER ONICON 1130
DSD
CONTROL MODULE
IN ADDITION THE SYSTEM SHALL DISPLAY THE ENERGY SAVING FEATURES OF THE BUILDING
DUCT SMOKE DETECTOR
INCLUDING: DX
DIRECT EXPANSION
EPO
EMERGENCY POWER OFF
DI
DIGITAL INPUT TO UNIT CONTROLLER
-RAMMED EARTH CONSTRUCTION -PHOTO VOLTAICS -2-STAGE EVAPORATIVE
DO
DIGITAL OUTPUT FROM UNIT CONTROLLER
COOLING -RAINWATER HARVESTING
AI
ENTHALPY SENSOR
ANALOG INPUT TO UNIT CONTROLLER CONTROLS CONTRACTOR SHALL SUBMIT COMPLETE
N.T.S.
Descri pti on
A2
ES
OMS-DDC OVERVIEW
CONTROL SYSTEM WITH PROPOSED DASHBOARD F
FILTER
AO
ANALOG OUTPUT FROM UNIT CONTROLLER
GRAPHICAL IMAGES, CHARTS AND GRAPHS AS PART OF A COMPLETE CONTROL SYSTEM PACKAGE
H
HUMIDITY SENSOR (WET BULB TEMPERATURE)
(SIMILAR TO PROPHET, PERISCOPE, D-MON D-MON, SIEMENS SIMATIC, OR EQUIVALEST). THE CONTROL SYSTEM SHALL GENERATE ALL NECESSARY
HS
HUMIDITY SENSOR (RELATIVE HUMIDITY)
IDEC
INDIRECT EVAPORATIVE COOLER
M
MOTOR/ACTUATOR
MD
MOTORIZED DAMPER
N.C.
NORMALLY CLOSED
REPORTS REQUIRED TO MEET THE LEED MEASUREMENT AND VERIFICATION REQUIREMENTS.
HEAT AND VENT UNIT HVU 1-1
UNIT HEATERS
SPLIT HEAT PUMP UNITS
KITCHEN SUPPLY FANS KSF1-1
KITCHEN EXHAUST FANS
Mark
EXHAUST FANS
GATEWAY
FM
ELECTRIC METER
FLOW METER
NATURAL GAS FLOW METER
DOMESTIC WATER FLOW METER
ROOTS METER SOLID STATE PULSER
TURBINE FLOW METER ONICON 1130
U.S.ARMY
A
A1
7/22/2011
Pl ot scal e:NONE
Pl ot date:
Fi l e nam e:LCARC_M 8000. dgn
FAX (714) 327-1601
M .BETZ
Subm i tted by:
F-171-40-160
Project Code:
E-MON D-MON SERIES 3000
DDC SYSTEM ARCHITECTURE N.T.S.
MEXI CO
LOCATE MONITOR IN LOBBY A101
FLOW METER
7/22/2011
c:\pwworki ng\gbna\m oraja\dm s97636\LCARC_M-8000.dgn
FM
PULSE OUTPUT
RESERVE CENTER
PULSE OUTPUT
U.S.ARMY
COMM. CABLE (8) #26 AWG STRANDED SILVERSTRAIN
4
TEL (714) 327-1600
INTERVAL DATA RECORDER FC-MON IDR-8-B
LAS CRUCES,NEW
BAS OPERATOR’S WORKSTATION IN FACILITY MAINTENANCE OFFICE RM A116
HUTTON CENTRE DRI VE,SUI TE 800
BAS SUB-NETWORK BACNET MS/TP
LOUI SVI LLE DI STRI CT
CORPS OF ENGI NEERS
1
SANTA ANA, CALI FORNI A 92707
120V
4
ARC-DDC OVERVIEW
CONTROLS
BACNET IP ON BUILDING ETHERNET BACKBONE (LAN)
Revi ewed by:
120V/24V TRANSFORMER AS REQUIRED
1
A.REED
3
W 912QR-11-R-0071
3
Sol i ci tati on No.
3
C.KORPASH
3
Ckd by:
3
Dwn by:
3
EC 1-7
I .FRANCO
3
EC 1-6
Date:
1
EC 1-5
Desi gned by:
BACNET WEB SERVER
EC 1-4
A.REED
B
EC 1-3
EC 1-2
LOUI SVI LLE,KENTUCKY
EC 1-1 BACNET ROUTER/BUILDING CONTROLLER (BC)
072811
2
Rev.
BAS SUB-NETWORK BACNET MS/TP
SHEET REFERENCE NUMBER:
M-8000 of 222
9:14:38
m oraja
AM
Sheet 144
1
2
*** Support Value Engineering - It Pays ***
4
5
CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11
*** Safety Pays ***
2
5
SEQUENCE OF OPERATION LOW LEAKAGE
EXHAUST FAN
GENERAL NOTES
HEATING AND VENTILATING UNIT (HVU 1-1) A. FOR MECHANICAL ABBREVIATIONS, SYMBOLS, AND NOTES REFER TO DRAWING M-0010. FOR CONTROL
F. HEATING CONTROL: WHEN THERE IS A DEMAND FOR EF 1-7
N.C.
EXHAUST
A. SUPPLY FAN HAND-OFF-AUTO OPERATION:
AIR
HAND-OFF-AUTO SETTINGS SHALL BE PROVIDED AS PART OF THE VARIABLE FREQUENCY DRIVE (VFD) THROUGH THE
CD
DI
M
4
DRIVE’S KEYPAD. IN THE OFF MODE, THE FAN SHALL BE
6
2
N.C.
AX
4
SS
CD
DI
1
1
HVU 1-1 FREEZE
COIL
STAT
CONTINUOUSLY. IN THE AUTO MODE, THE BAS SHALL START/STOP THE UNIT THROUGH THE UNIT CONTROLLER
LOW LEAKAGE
AS DESCRIBED BELOW. PROGRAM A TIME DELAY INTO THE
EF 1-6
SUPPLY
N.C.
EXHAUST
THE RESTART OF EACH UNIT AFTER A POWER FAILURE TO
AIR
PREVENT CREATING A SPIKE IN THE FACILITY ELECTRICAL
INTAKE
AIR
DEMAND. UPON ACTIVATION, SAFETIES SHALL BE HARD
AIR
M
6
WIRED TO THE RESPECTIVE VFD TO STOP THE UNIT
1 LL
1 CD
DI
1
1
TS
SS
CI
SUPPLY FAN IN THE HAND AND AUTO MODES.
DSD
TO FACP
1 AX
AX
4
SS
CD
DI
1
1
1
FIRE ALARM SYSTEM BY DIVISION 28. SEE DIVISION
FAN IS STARTED OUTDOOR AIR DAMPER, CD-1, SHALL OPEN.
28 FOR ADDITIONAL INFORMATION.
WHEN THE UNIT IS OFF CD-1, SHALL BE CLOSED. H. FIRE ALARM SHUTDOWN: WHEN PARTICLES OF COMBUSTION ARE SENSED BY THE SUPPLY AIR DUCT
KEY NOTES
SMOKE DETECTOR DSD-1, A DUCT SMOKE ALARM SIGNAL SHALL BE SENT TO THE UNIT CONTROLLER AND FIRE
LOCAL-REMOTE SETTINGS SHALL BE PROVIDED AS PART
DP CM
OF THE VFD THROUGH THE DRIVE’S KEYPAD. IN THE
4
LOCAL MODE, THE FAN SPEED SHALL BE CONTROLLED
1
VARIABLE FREQUENCY DRIVE
2
PROVIDE INTERLOCK WIRING BETWEEN FAN AND FIRE
ALARM SYSTEM. UPON RECEIVING AN ALARM SIGNAL FROM SUPPLY AIR DUCT SMOKE DETECTOR DSD-1, THE FIRE
B. SUPPLY FAN LOCAL-REMOTE SPEED CONTROL:
2
2
1
CONTROL DEVICES PROVIDED AND CONNECTED TO
G. OUTDOOR AIR DAMPER CONTROL: WHEN THE SUPPLY
ALARM SYSTEM SHALL ACTIVATE A CONTROL MODULE (CM)
ALARM SYSTEM THROUGH CONTROL MODULE (CM).
TO STOP THE FAN. WHEN THE FIRE ALARM CONDITION HAS
WHEN A DUCT SMOKE DETECTOR ASSOCIATED WITH
BEEN CLEARED, AND THE FIRE ALARM SYSTEM HAS BEEN
AHU SENSES PARTICLES OF COMBUSTION, FAN
RESET, THE UNIT SHALL BE RETURNED TO OPERATION.
SHALL STOP. THIS INTERLOCK SHALL BE HARD
THROUGH A MANUAL SPEED CONTROL LOCATED AT THE TS
FROM
XXX
FACP
RESPECTIVE DRIVE CONTROL PANEL. IN THE REMOTE MODE, THE FAN SPEED SHALL BE CONTROLLED BY THE BAS
7
THROUGH THE UNIT CONTROLLER.
WIRED AND NOT PERFORMED THROUGH THE DDCS. I. DIRTY FILTER ALARM: DIFFERENTIAL PRESSURE SWITCH
SHALL START AND STOP THE UNIT. TO START THE UNIT, THE BAS SHALL SEND A START SIGNAL TO THE UNIT DI DI
DI
DI
AO
DO AO
AI
DI
DO
CONTROLLER, WHICH WILL START THE SUPPLY FAN. IF THE
DO
THE START COMMAND SHALL BE CANCELED. TO STOP THE CONTROLLER
UNIT, THE BAS SHALL SEND A STOP COMMAND TO UNIT
CONTROLLER
X
X
X
CONTROLLER, WHICH WILL DE-ENERGIZE THE SUPPLY FAN. THE UNIT SHALL BE PLACED ON A TIME SCHEDULE.
FROM PREVIOUS CONTROLLER
FROM PREVIOUS CONTROLLER
TO NEXT CONTROLLER
CONTROL: THE EXHAUST FAN MOTOR STARTERS SHALL BE SOFTWARE INTERLOCKED WITH THE SUPPLY FAN MOTOR STARTER TO START WHEN THE SUPPLY FAN IS ON AND
HEATING AND VENTILATING UNIT (ARC UNIT STORAGE) - CONTROL DIAGRAM
TO STOP WHEN THE SUPPLY FAN IS OFF. THE EXHAUST
N.T.S.
FAN (EF 1-7), IS ASSOCIATED WITH HVU 1-1. WHENEVER HVU 1-1 IS ON EF 1-7 SHALL BE ON.
INDICATOR (PDI-1) LOCATED AT THE FILTERS SHALL
TEMPERATURE HEATING SET POINT SHALL BE INITIALLY SET AT 68F (ADJUSTABLE). WHEN THE ROOM TEMPERATURE IS ABOVE 75F, THE HEATING SYSTEM SHALL BE OFF AND EF 1-6 SHALL START AND ITS ASSOCIATED
C
OPEN. IV-2 AND EF-1-6 SHALL REMAIN IN THE VENTILATING MODE UNTIL THE SPACE TEMPERATURE
EF 2-1
N.C. 4
HVU 2-1
OUTDOOR
N.C.
AIR
AX
SS
SHALL OPEN. ONCE DAMPER IS PROVEN OPEN BY
CD
DI
1
1
STATUS INDICATED DOES NOT MATCH THE COMMANDED
1
1
1
6
MOTOR STARTER
7
TYPICAL SPACE TEMPERATURE AND HUMIDITY
OUTPUT FOR THE FAN AN ALARM SHALL BE GENERATED AT THE UNIT CONTROLLER AND THE BAS. K. FAILURE MODE: UPON LOSS OF CONTROL SIGNAL OR
SENSORS. XXX REPRESENTS ASSOCIATED ROOM
ELECTRICAL POWER THE CONTROL DEVICES SHALL FAIL IN
NUMBER.
THE MANNER INDICATED IN THE "BAS POINT FUNCTION SCHEDULE" ON THE MECHANICAL SHEETS.
8
ADDITIONAL MONITORING: IN ADDITION TO THE POINTS
TYPICAL CARBON MONOXIDE AND NITROGEN DIOXIDE SENSORS. SEE M-110B FOR LOCATIONS OF SENSORS.
MENTIONED IN THESE SEQUENCES PROVIDE THE ADDITIONAL MONITORING POINTS LISTED IN THE "BAS POINT FUNCTION 9
PROVIDE ALARM HORN WHERE INDICATED ON M-110B. ALARM HORN SHALL SOUND WHEN LEVEL OF EITHER
L. EMERGENCY STOP: WHEN THE EMERGENCY VENMTILATION
CARBON MONOXIDE OR NITROGEN DIOXIDE EXCEEDS
STOP BUTTON IS ACTIVATED, THE SUPPLY AND EXHAST
HIGH LEVEL LIMIT. SEE SEQUENCE OF OPERATION
FANS SHALL STOP AND THE MOTORIZED DAMPERS SHALL
FOR DETAIL.
CLOSE. 10 M. PROVIDE LOW LIMIT SUPPLY TEMPERATURE ALARM TO
INTERLOCK WIRING BETWEEN HOOD SWITCH AND HOOD EXHAUST FANS
SHUTDOWN SUPPLY FAN AND ALARM BAS.
EF 1-7 SHALL RUN DURING ALL OCCUPIED TIMES. UNIT
"HEAT/VENT/COOL/OFF". INTERLOCK KSF 1-1, HOOD,
HEATERS SHALL MAINTAIN SPACE AT 40F DURING
EF 1-9.
11
HOOD VENTILATOR SELECTOR SWITCH
OCCUPIED TIMES TO KEEP SPACE AT 68F.
SEQUENCE OF OPERATION
EXHAUST N.C.
AIR
HEATING AND VENTILATING UNIT (HVU 2-1)
AIR
C
M 6 LL
1 PD
FAN DISCONNECT
FALLS TO 70F AND THEN SHALL TURN OFF. HVU 1-1 AND
EF 2-2
SUPPLY
PDI DI
5
LOW LEAKAGE
1
CD
START. DAMPER SHALL CLOSE WHEN FAN STOPS.
MONITOR THE STATUS OF THE UNIT SUPPLY FAN. IF THE
UNOCCUPIED TIMES AND SUPPLEMENT HVU 1-1 DURING
FREEZE STAT
COIL
ASSOCIATED DAMPER POSITION SWITCH, FAN SHALL
J. FAN STATUS: A CURRENT RELAY SHALL BE USED TO
AIR
M
HEATING
H
M
START IN EITHER HAND OR AUTO MODE. DAMPER
FILTERS.
EXHAUST
6
F
ASSOCIATED DAMPER. WHEN FAN IS COMMANDED TO
INTAKE VENTILATOR (IV-2) MOTORIZED DAMPER SHALL
LOW EXHAUST FAN LEAKAGE
A F M S
PROVIDE INTERLOCK WIRING BETWEEN FAN AND
INDICATE THE DIFFERENTIAL PRESSURE ACROSS THE
SCHEDULE."
SUPPLY FAN
4
CONTROLLER AND THE BAS. PRESSURE DIFFERENCE
E. SUPPLY AIR TEMPERATURE SET POINT: THE SUPPLY AIR
LOW LEAKAGE
MANUAL HOOD SWITCH
TO NEXT CONTROLLER D. EXHAUST FANS AUTOMATIC MODE START/STOP
D1
3
FAN DOES NOT START AFTER A 60 SECOND (ADJUSTABLE) TIME DELAY, A UNIT FAILURE ALARM SHALL BE ISSUED AND
X
INSTALLED UNDER DIVISION 28.
FILTERS. WHEN THE PRESSURE EXCEEDS AN ADJUSTABLE LIMIT, AN ALARM SIGNAL WILL BE SENT TO THE UNIT
C. AUTOMATIC MODE START/STOP CONTROL: THE BAS
CM AND SMOKE DETECTOR FURNISHED AND
DP-1 SHALL MONITOR THE PRESSURE DROP AT THE
Descri pti on
H
PDI
DUCT SMOKE DETECTORS AND ADDRESSABLE
VFD, IN BOTH THE HAND AND AUTO MODES, TO STAGGER
C
D
HEATING SHALL BE OFF.
Mark
F
B.
LOUISVILLE DISTRICT
Appr.
SUPPLY FAN
HEATING
TEMPERATURE. WHEN THE SUPPLY FAN IS OFF, THE
DRAWING M-8000.
Date
AIR
ABBREVIATIONS, SYMBOLS, AND NOTES REFER TO
Descri pti on
OUTDOOR
LOW LEAKAGE
CONTROL VALVE TO MAINTAIN A 68F SUPPLY AIR
STOPPED. IN THE HAND MODE, THE FAN SHALL RUN
M M
HEATING, THE BAS SHALL MODULATE THE HEATING
US Army Corps of Engineers
Appr.
IV 2
IV 1
4
Date
1
TS
TO
1 AX
SS
CI
FACP
2
DSD AX
1
SS
4
2
CD
DI
1
1
DP CM
1 4
8
TS
FROM
CO
NO2
XXX
FACP
XXX
XXX
A. SUPPLY FAN HAND-OFF-AUTO OPERATION: HAND-OFF-AUTO SETTINGS SHALL BE PROVIDED AS
H. FIRE ALARM SHUTDOWN: WHEN PARTICLES OF COMBUSTION ARE SENSED
PART OF THE VARIABLE FREQUENCY DRIVE (VFD) THROUGH THE DRIVE’S KEYPAD. IN THE OFF
BY THE SUPPLY AIR DUCT SMOKE DETECTOR DSS-1, A DUCT SMOKE ALARM
MODE, THE FAN SHALL BE STOPPED. IN THE HAND MODE, THE FAN SHALL RUN CONTINUOUSLY. IN
SIGNAL SHALL BE SENT TO THE UNIT CONTROLLER AND FIRE ALARM
THE AUTO MODE, THE BAS SHALL START/STOP THE UNIT THROUGH THE UNIT CONTROLLER AS
SYSTEM. UPON RECEIVING AN ALARM SIGNAL FROM SUPPLY AIR DUCT
DESCRIBED BELOW. PROGRAM A TIME DELAY INTO THE VFD, IN BOTH THE HAND AND AUTO
SMOKE DETECTOR DSD-1, THE FIRE ALARM SYSTEM SHALL ACTIVATE A
MODES, TO STAGGER THE RESTART OF EACH UNIT AFTER A POWER FAILURE TO PREVENT
CONTROL MODULE (CM) TO STOP THE FAN. WHEN THE FIRE ALARM
CREATING A SPIKE IN THE FACILITY ELECTRICAL DEMAND. UPON ACTIVATION, SAFETIES SHALL BE
CONDITION HAS BEEN CLEARED, AND THE FIRE ALARM SYSTEM HAS BEEN
HARD WIRED TO THE RESPECTIVE VFD TO STOP THE UNIT SUPPLY FAN IN THE HAND AND
RESET, THE UNIT SHALL BE RETURNED TO OPERATION.
AUTO MODES.
7
I. DIRTY FILTER ALARM: DIFFERENTIAL PRESSURE SWITCH DP-1 SHALL
DI
DI
AI
AI
DI
AO
DO AO
AI
DI
DO
DI
AI
DO
AI
CONTROLLER
CONTROLLER
X
X
MONITOR THE PRESSURE DROP AT THE FILTERS. WHEN THE PRESSURE
AS PART OF THE VFD THROUGH THE DRIVE’S KEYPAD. IN THE LOCAL MODE, THE FAN SPEED
EXCEEDS AN ADJUSTABLE LIMIT, AN ALARM SIGNAL WILL BE SENT TO THE
SHALL BE CONTROLLED THROUGH A MANUAL SPEED CONTROL LOCATED AT THE RESPECTIVE
UNIT CONTROLLER AND THE BAS. PRESSURE DIFFERENCE INDICATOR (PDI-1)
DRIVE CONTROL PANEL. IN THE REMOTE MODE, THE FAN SPEED SHALL BE CONTROLLED BY THE
LOCATED AT THE FILTERS SHALL INDICATE THE DIFFERENTIAL PRESSURE
BAS THROUGH THE UNIT CONTROLLER.
ACROSS THE FILTERS.
C. AUTOMATIC MODE START/STOP CONTROL: THE BAS SHALL START AND STOP THE UNIT. TO
J. FAN STATUS: A CURRENT RELAY SHALL BE USED TO MONITOR THE
START THE UNIT, THE BAS SHALL SEND A START SIGNAL TO THE UNIT CONTROLLER, WHICH WILL
STATUS OF THE UNIT SUPPLY FAN. IF THE STATUS INDICATED DOES NOT
START THE SUPPLY FAN. IF THE FAN DOES NOT START AFTER A 60 SECOND (ADJUSTABLE)
MATCH THE COMMANDED OUTPUT FOR THE FAN AN ALARM SHALL BE
TIME DELAY, A UNIT FAILURE ALARM SHALL BE ISSUED AND THE START COMMAND SHALL BE
GENERATED AT THE UNIT CONTROLLER AND THE BAS.
AI
DO X
B. SUPPLY FAN LOCAL-REMOTE SPEED CONTROL: LOCAL-REMOTE SETTINGS SHALL BE PROVIDED
X
WHICH WILL DE-ENERGIZE THE SUPPLY FAN. THE UNIT SHALL BE PLACED ON A TIME SCHEDULE. 9
THE FLOOR RADIANT HEATING SYSTEM (SEE M-8070 AND M-7000 FOR DETAIL).
M. PROVIDE LOW LIMIT SUPPLY TEMPERATURE ALARM TO SHUTDOWN SUPPLY
10
FAN AND ALARM BAS
CR
CD
SS
GREASE
1
STARTER TO START WHEN THE SUPPLY FAN IS ON AND TO STOP WHEN THE SUPPLY FAN IS A. SUPPLY FAN HAND-OFF-AUTO OPERATION: HAND-OFF-AUTO
OFF.
OPERATION SWITCH ON MOTOR STARTER SHALL CONTROL THE FAN. IN
1 B.D.D
SUPPLY AIR
EXHAUST
EXHAUST
AIR
AIR
SW
KITCHEN HOOD
A
F. FIRE ALARM SHUTDOWN: WHEN PARTICLES OF COMBUSTION ARE SENSED BY THE SUPPLY
FAN SHALL BE ENERGIZED. IN THE AUTO POSITION THE BAS SHALL
AIR DUCT SMOKE DETECTOR DSD-1, A DUCT SMOKE ALARM SIGNAL SHALL BE SENT TO THE
START/STOP THE UNIT THROUGH THE UNIT CONTROLLER AS DESCRIBED
UNIT CONTROLLER AND FIRE ALARM SYSTEM. UPON RECEIVING AN ALARM SIGNAL FROM
BELOW. PROVIDE AN ADJUSTABLE DELAY-ON-MAKE RELAY, WIRED IN
SUPPLY AIR DUCT SMOKE DETECTOR DSD-1, THE FIRE ALARM SYSTEM SHALL ACTIVATE A
BOTH THE HAND AND AUTO MODES, TO STAGGER THE RESTART OF
CONTROL MODULE (CM) TO STOP THE FAN. WHEN THE FIRE ALARM CONDITION HAS BEEN
UNIT, AFTER A POWER FAILURE, TO PREVENT CREATING A SPIKE IN THE
CLEARED, AND THE FIRE ALARM SYSTEM HAS BEEN RESET, THE UNIT SHALL BE RETURNED TO
FACILITY ELECTRICAL DEMAND. SAFETIES SHALL BE HARD WIRED TO
OPERATION. THIS SHALL BE PROVIDED BY FLS SEPARATE FROM BAS.
B. AUTOMATIC MODE START/STOP CONTROL: THE UNIT SHALL BE
DROP AT THE FILTERS. WHEN THE PRESSURE EXCEEDS AN ADJUSTABLE LIMIT, AN ALARM
CONTROLLED BY A "HEAT/VENT/COOL/OFF" KITCHEN HOOD SWITCH.
SIGNAL WILL BE SENT TO THE UNIT CONTROLLER AND THE BAS.PRESSURE DIFFERENCE
WHEN THE HOOD SWITCH IS INDEXED TO "VENT", THE BAS SHALL SEND
INDICATOR (PDI-1) LOCATED AT THE FILTERS SHALL INDICATE THE DIFFERENTIAL PRESSURE
A START SIGNAL TO SUPPLY FAN STARTER, WHICH WILL START THE
ACROSS THE FILTERS.
(ADJUSTABLE) TIME DELAY, A UNIT FAILURE ALARM SHALL BE ISSUED
H. FAN STATUS: A CURRENT RELAY SHALL BE USED TO MONITOR THE STATUS OF THE UNIT
AND THE START COMMAND SHALL BE CANCELED. TO STOP THE UNIT,
SUPPLY FAN. IF THE STATUS INDICATED DOES NOT MATCH THE COMMANDED OUTPUT FOR THE
TURN THE HOOD SWITCH TO OFF AND THE BAS SHALL SEND A STOP
FAN AN ALARM SHALL BE GENERATED AT THE UNIT CONTROLLER AND THE BAS.
COMMAND TO STARTER, WHICH WILL STOP THE SUPPLY FAN. I. FAILURE MODE: UPON LOSS OF CONTROL SIGNAL OR ELECTRICAL POWER THE CONTROL
AO
DI
DI
AI
DI
DI
C. TEMPERATURE CONTROL: KSF 1-1 SHALL HAVE A MANUAL
DEVICES SHALL FAIL IN THE MANNER INDICATED IN THE "BAS POINT FUNCTION SCHEDULE" ON
"HEAT/VENT/COOL/OFF" WALL SWITCH. WHEN PLACED IN "HEAT"
THE MECHANICAL SHEETS.
POSITION, THE ELECTRIC HEATER SHALL STAGE ON TO TEMPER THE
CONTROLLER FOR SF/EF
X
X
SUPPLY AIR TO MAINTAIN 55F SUPPLY AIR. HEATER SHALL TURN ON
J. ADDITIONAL MONITORING: IN ADDITION TO THE POINTS MENTIONED IN THESE SEQUENCES
ONLY AFTER FAN IS PROVEN "ON". UNIT SHALL ALARM AT THE BAS
PROVIDE THE ADDITIONAL MONITORING POINTS LISTED IN THE "BAS POINT FUNCTION
WHEN SUPPLY AIR TEMPERATURE IS ABOVE 75F OR BELOW 45F. UNIT
SCHEDULE."
TO NEXT CONTROLLER
35F. WHEN THE SWITCH IS MOVED TO "COOL", THE EVAPORATIVE
K. EMERGENCY STOP: WHEN THE EMERGENCY VENTILATION STOP BUTTON IS ACTIVATED, THE
COOLING PUMP SHALL START AND TEMPER THE SUPPLY AIR.
SUPPLY AND EXHAUST FANS SHALL STOP AND THE MOTORIZED DAMPERS SHALL CLOSE.
7/22/2011
Pl ot scal e:NONE
Pl ot date:
SHEET REFERENCE NUMBER:
D. GREASE HOOD EXHAUST FAN AUTOMATIC START/STOP CONTROL: THE
A1
KITCHEN HOOD SUPPLY AND EXHAUST FANS - CONTROL DIAGRAM N.T.S.
GREASE HOOD EXHAUST FAN, EF 1-9 MOTOR STARTER SHALL BE INTERLOCKED WITH THE KSF 1-1 SUPPLY FAN MOTOR STARTER TO
M-8010
START WHEN THE SUPPLY FAN IS ON AND TO STOP WHEN THE
Sheet 145
SUPPLY FAN IS OFF. 9:15:29 AM
Fi l e nam e:LCARC_M 8010. dgn
SHALL SHUTDOWN WHEN TEMPERATURE RISES ABOVE 80F OR BELOW FROM PREVIOUS CONTROLLER
m oraja
Desi gned by:
STOP THE SUPPLY FAN.
SUPPLY FAN. IF THE FAN DOES NOT START AFTER A 60 SECOND
3 KITCHEN HOOD
THE OFF MODE, THE FAN SHALL BE STOPPED. IN THE HAND MODE, THE
G. DIRTY FILTER ALARM: DIFFERENTIAL PRESSURE SWITCH DP-1 SHALL MONITOR THE PRESSURE
SW
11
7/22/2011
c:\pwworki ng\gbna\m oraja\dm s97636\LCARC_M-8010.dgn
FAN, EF 1-8 MOTOR STARTER SHALL BE INTERLOCKED WITH THE EC1-6 SUPPLY FAN MOTOR
M
DUCT
CM
DP
E. CONDENSATE HOOD EXHAUST FAN AUTOMATIC START/STOP CONTROL: THE HOOD EXHAUST
EF 1-9)
FAX (714) 327-1601
1
KITCHEN MAKE-UP AIR UNIT (KSF 1-1) AND EXHAUST FANS (EF 1-8 &
TEL (714) 327-1600
1
5
CONTROLS
TS
MEXI CO
1 PDI
LAS CRUCES,NEW
M
HUTTON CENTRE DRI VE,SUI TE 800
EVAP COOLER
SANTA ANA, CALI FORNI A 92707
SEQUENCE OF OPERATION
4
EF 1-8
H
LOUI SVI LLE DI STRI CT
M CR
CORPS OF ENGI NEERS
CLOSED.
U.S.ARMY
6 SUPPLY FAN
E DIRECT
100% OUTSIDE AIR (4040CFM).
DAMPER, CD-1, SHALL OPEN. WHEN THE UNIT IS OFF, OUTDOOR AIR DAMPER, CD-1, SHALL BE
RESERVE CENTER
F OUTDOOR AIR
(10CFM/PERSON x15 = 150CFM). HVU 2-1 OPERATES AT A MINIMUM OF G. OUTDOOR AIR DAMPER CONTROL: WHEN THE SUPPLY FAN IS STARTED THE OUTDOOR AIR
HEATING COIL
BE WITHIN 15% PLUS OR MINUS OF DESIGN MINIMUM REQUIRED
U.S.ARMY
LOW LEAKAGE
N. AIRFLOW MONITORING STATION: MEASURE OUTSIDE AIR (OSA) VOLUME TO
FAN IS OFF, THE HEATING SHALL BE OFF. EF 1-9
KSF 1-1
ELECTRIC
HEATING CONTROL VALVE TO MAINTAIN A 60F SUPPLY AIR TEMPERATURE. WHEN THE SUPPLY
A.REED
F. HEATING CONTROL: WHEN THERE IS A DEMAND FOR HEATING, THE BAS SHALL MODULATE THE
M .BETZ
MOTORIZED DAMPERS SHALL CLOSE.
SHALL BE INITIALLY SET AT 60F(ADJUSTABLE). SPACE TEMPERATURE SENSOR SHALL OPERATE
Subm i tted by:
E. SUPPLY AIR TEMPERATURE SET POINT: THE SUPPLY AIR TEMPERATURE HEATING SET POINT
F-171-40-160
ACTIVATED, THE SUPPLY AND EXHAST FANS SHALL STOP AND THE
Date:
L. EMERGENCY STOP: WHEN THE EMERGENCY VENMTILATION STOP BUTTON IS
Project Code:
ADDITIONAL VENTILATION.
072811
B
Revi ewed by:
"BAS POINT FUNCTION SCHEDULE."
OF CO OR N02, THE EXHAUST FANS AND HVU 2-1 SHALL STAGE TO A HIGHER CFM FOR
A.REED
EXHAUST FANS, EF 2-1 AND EF 2-2, ARE ASSOCIATED WITH HVU 2-1. UPON AN ALARM CONDITION
W 912QR-11-R-0071
SEQUENCES PROVIDE THE ADDITIONAL MONITORING POINTS LISTED IN THE
Sol i ci tati on No.
START WHEN THE SUPPLY FAN IS ON AND TO STOP WHEN THE SUPPLY FAN IS OFF. THE
C.KORPASH
N.T.S.
ADDITIONAL MONITORING: IN ADDITION TO THE POINTS MENTIONED IN THESE
Ckd by:
HEATING AND VENTILATING UNIT (OMS WORK BAYS) - CONTROL DIAGRAM
POINT FUNCTION SCHEDULE" ON THE MECHANICAL SHEETS.
STARTERS SHALL BE SOFTWARE INTERLOCKED WITH THE SUPPLY FAN MOTOR STARTER TO
LOUI SVI LLE,KENTUCKY
B1
ED
THE CONTROL DEVICES SHALL FAIL IN THE MANNER INDICATED IN THE "BAS D. EXHAUST FANS AUTOMATIC MODE START/STOP CONTROL: THE EXHAUST FAN MOTOR
Dwn by:
HORN
K. FAILURE MODE: UPON LOSS OF CONTROL SIGNAL OR ELECTRICAL POWER
I .FRANCO
FROM PREVIOUS CONTROLLER TO NEXT CONTROLLER
TO NEXT CONTROLLER
Rev.
FROM PREVIOUS CONTROLLER
Mark
CANCELED. TO STOP THE UNIT, THE BAS SHALL SEND A STOP COMMAND TO UNIT CONTROLLER,
1
2
*** Support Value Engineering - It Pays ***
4
5
of 222
CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11
1
*** Safety Pays ***
2
4
5
GENERAL NOTES SEQUENCE OF OPERATION
A.
FOR MECHANICAL ABBREVIATIONS, SYMBOLS, AND NOTES REFER TO DRAWING M-0010. FOR CONTROL ABBREVIATIONS, SYMBOLS,
SPLIT SYSTEM HEAT PUMP UNIT
AND NOTES REFER TO DRAWING M-8000. OUTDOOR
HP-1, 2, 3, 4, 5 B.
SIGNAL TO THE UNIT CONTROLLER, WHICH WILL START THE FAN COIL AND OUTDOOR HEATPUMP UNIT.
PROVIDED AND CONNECTED TO FIRE ALARM SYSTEM BY
IF THE UNIT DOES NOT START AFTER A 60 SECOND (ADJUSTABLE) TIME DELAY, A UNIT FAILURE
DIVISION 28. SEE DIVISION 28 FOR ADDITIONAL INFORMATION.
ALARM SHALL BE ISSUED AND THE START COMMAND SHALL BE CANCELED. TO STOP THE UNIT, THE
Date
BAS SHALL SEND A STOP COMMAND TO UNIT CONTROLLER, WHICH WILL DE-ENERGIZE THE FAN
INDOOR
COIL/HEAT PUMP. THE UNIT SHALL BE PLACED ON A TIME SCHEDULE.
FAN COIL SUPPLY FAN
1. OPTIMAL START: THE BAS SHALL START THE UNIT ACCORDING TO AN OPTIMAL START ROUTINE.
D
KEY NOTES
COOL DOWN MODE SHALL BE USED IF THE SPACE TEMPERATURE, AS SENSED BY THE SPACE OUTDOOR X
AIR
SUPPLY
TEMPERATURE SENSOR, IS ABOVE THE OCCUPIED SET POINT. AT THE SCHEDULED OCCUPANCY TIME,
AIR
THE UNIT SHALL START IF NOT ALREADY STARTED BY THE OPTIMAL START ROUTINE, AND THE UNIT SHALL BE SWITCHED TO THE OCCUPIED MODE.
FC-1, 2, 3, 4, 5
D
D
DUCT SMOKE DETECTORS AND ADDRESSABLE CONTROL DEVICES Appr.
1
SS
LOUISVILLE DISTRICT
A. AUTOMATIC MODE START/STOP CONTROL: TO START THE UNIT, THE BAS SHALL SEND A START
HEAT PUMP
CR
US Army Corps of Engineers
TS XXX
X
1
MOTOR STARTER
2
ELECTRIC METER SHALL BE CONNECTED TO BAS SUB-NETWORK USING BACNET. SEE "BAS POINT FUNCTION SCHEDULE" ON
2. OPTIMAL STOP: THE BAS SHALL STOP THE UNIT ACCORDING TO AN OPTIMAL STOP ROUTINE. THE
M-8080 FOR LIST OF NETWORK POINTS.
ROUTINE SHALL MONITOR THE ROOM TEMPERATURE AS SENSED BY THE SPACE TEMPERATURE 6
SENSOR, AND STOP THE UNIT UP TO 30 MINUTES EARLY IF THE TEMPERATURES ARE WITHIN
3
ACCEPTABLE LIMITS.
MECHANICAL FLOOR PLANS.
3. UNOCCUPIED START/STOP: IN THE UNOCCUPIED MODE, THE BAS SHALL START THE UNIT AND
4
FAN DISCONNECT
5
PROVIDE INTERLOCK WIRING BETWEEN FAN AND ASSOCIATED
OPERATE THE SYSTEM IN THE UNOCCUPIED COOLING MODE IF ANY SPACE TEMPERATURE, AS SENSED
AI
DI
PROVIDE EMERGENCY SHUTDOWN SIWTCHES WHERE INDICATED IN
BY THE SPACE TEMPERATURE SENSORS, RISES ABOVE 85F (ADJUSTABLE). THE UNIT SHALL OPERATE
DAMPER. WHEN FAN IS COMMANDED TO START IN EITHER HAND
UNTIL SPACE TEMPERATURE IS AT LEAST 78F (ADJUSTABLE).
X
OPEN BY ASSOCIATED DAMPER POSITION SWITCH, FAN SHALL
B. COOLING/HEATING CONTROL: WHEN THERE IS A DEMAND FOR COOLING, THE BAS SHALL CYCLE ON
CONTROLLER
X
START. DAMPER SHALL CLOSE WHEN FAN STOPS.
AND OFF THE HEAT PUMP COMPRESSOR TO MAINTAIN THE SPACE TEMPERATURE AS SENSED BY THE TEMPERATURE SENSOR AT THE SPACE TEMPERATURE COOLING SET POINT, INITIALLY SET AT 74
TO NEXT CONTROLLER
FROM PREVIOUS CONTROLLER
6
DEGREES F (ADJUSTABLE). WHEN THE FAN COIL IS OFF, THE HEAT PUMP SHALL BE OFF. AS ROOM
LOCATIONS OF SPACE TEMPERATURE SENSORS.
TEMPERATURE AT 68F. UPON A RISE OF TEMPERATURE TO 72F, THE HEATING MODE OF THE HEAT
D1
PUMP SHALL TURN OFF.
N.T.S.
TYPICAL SPACE TEMPERATURE SENSORS. XXX REPRESENTS ASSOCIATED ROOM NUMBER. SEE MECHANICAL SHEETS FOR
TEMPERATURE FALLS TO 62F, THE UNIT SHALL SWITCH TO HEATING MODE TO MAINTAIN ROOM
SPLIT HEAT PUMP FAN COIL UNIT - CONTROL DIAGRAM
Descri pti on
OR AUTO MODE, DAMPER SHALL OPEN. ONCE DAMPER IS PROVEN
7
BOILER ROOM EPO SWITCH AND ALARM INDICATION.
C. FAILURE MODE: UPON LOSS OF CONTROL SIGNAL OR ELECTRICAL POWER THE CONTROL DEVICES SHALL FAIL IN THE MANNER INDICATED IN THE "BAS POINT FUNCTION SCHEDULE" ON THE MECHANICAL SHEETS. D. ADDITIONAL MONITORING: IN ADDITION TO THE POINTS MENTIONED IN THESE SEQUENCES PROVIDE THE ADDITIONAL MONITORING POINTS LISTED IN THE "BAS POINT FUNCTION SCHEDULE."
M
AIR 1 4
C
EF 1-2
EF 1-5
EF 1-6
EF 1-7
EF 2-3
EF 2-4
EF 2-7
SS
M
CR SS
EF 1-1
CR
5
CD
DI
1
1
CD 1
EF 1-4
EF 1-10
EF 1-12
EF 1-13
SEQUENCE OF OPERATION
EF 1-14
EXHAUST FANS (TYPICAL)
M
A. EXHAUST FAN HAND-OFF-AUTO OPERATION: PROVIDE A HAND-OFF-AUTO
EMERGENCY SHUTDOWN LOW LEAKAGE DAMPER
DI 1
TS XXX
EF 1-3
Date
1 4
EXHAUST
M
Appr.
Mark
EMERGENCY SHUTDOWN LOW LEAKAGE DAMPER
OPERATION SWITCH AT THE FAN DISCONNECT. IN THE OFF MODE, THE EXHAUST FAN SHALL BE STOPPED. IN THE HAND MODE, THE EXHAUST FAN SHALL RUN CONTINUOUSLY. IN THE AUTO MODE, THE EXHAUST FAN SHALL
5
EXHAUST
BE CONTROLLED BY THE BAS AS DESCRIBED BELOW.
AIR B. AUTOMATIC MODE START/STOP CONTROL: THE BAS SHALL START AND STOP THE FAN BASED ON A PROGRAMMED START/STOP SCHEDULE. TO START THE FAN, THE BAS SHALL SEND A START SIGNAL TO THE FAN. TO STOP A FAN, THE BAS SHALL SEND A STOP COMMAND TO THE FAN WHICH DI
DI
DO
WILL DE-ENERGIZES THE FAN.
DO
Descri pti on
C. FAN STATUS: A CURRENT RELAY SHALL BE USED TO MONITOR THE STATUS OF THE FAN. IF THE STATUS INDICATED DOES NOT MATCH THE CONTROLLER
X
X
X
CONTROLLER
COMMANDED OUTPUT FOR THE FAN AN ALARM SHALL BE GENERATED AND
X
SENT TO THE BAS AND THE FAN START COMMAND SHALL BE CANCELED. FROM PREVIOUS CONTROLLER
N.T.S.
EMERGENCY SHUTDOWN LOW LEAKAGE DAMPER
SEQUENCE OF OPERATION
EXHAUST
M
AIR
A. VEHICALE EXHAUST FAN AND REEL
Mark
USER DEFINED PERIOD FROM 1 TO 30
M
X FROM PREVIOUS CONTROLLER
VX 2-1
REEL
TO NEXT CONTROLLER
1V-9 INTAKE VENTILATOR MOTORIZED DAMPER
VX 2-2
B2 VEHICLE EXHAUST FAN - WIRING DIAGRAM
EXHAUST FAN - WIRING DIAGRAM N.T.S.
N.T.S.
UNIT MOUNTED TSTAT
U.S.ARMY
B1
X
CORPS OF ENGI NEERS
FAN
CONTROLLER
M
UNIT MOUNTED
7/22/2011
Pl ot scal e:NONE
Pl ot date:
Fi l e nam e:LCARC_M 8020. dgn
2 DH-1 DEHUMIDIFIER H
TS H CR
SS
C
EMERGENCY AIR DISTRIBUTION SHUT DOWN 7 EPO
UH -
3 TS OA
CO2 OA
A. PROVIDE EMERGENCY AIR DISTRIBUTION SW
DROPS TO 65F (ADJUSTABLE), THE FAN SHALL START AND
A. WHEN THE HUMIDITY RISES ABOVE THE
THE HEATING VALVE SHALL MODULATE TO MAINTAIN 68F.
SET POINT, INITIALLY SET AT 65% RH
(TYP)
SHUTDOWN SWITCH WHERE INDICATED IN THE
A
DEHUMIDIFIER (TYPICAL)
A. DURING OCCUPIED HOURS, WHEN THE TEMPERATURE
MECHANICAL FLOOR PLANS. WHEN THE SWITCH IS
B. DURING UNOCCUPIED HOURS AND NIGHT SETBACK, THE
ACTIVATED, ALL MECHANICAL EQUIPMENT
UNIT HEATER SHALL MAINTAIN A TEMPERATURE OF 40F
CONTROLLED BY THE BAS WITHIN THE BUILDING
(ADJUSTABLE).
(ADJUSTABLE), THE DEHUMIDIFIER SHALL BE ENABLED. WHEN THE HUMIDITY FALLS BELOW 50% RH, THE DEHUMIDIFIER SHALL BE DISABLED. THE DEHUMIDIFIER SHALL BE
SHALL BE SHUT DOWN INCLUDING CONTROL
CONTROLLED BY A UNIT MOUNTED
DAMPERS, AND MOTORIZEDDAMPERS. WHEN THE
HUMIDISTAT PROVIDED BY THE UNIT
EMERGENCY CONDITION HAS BEEN CLEARED, THE DI
DI
DI
AI
AI
DI
MANUFACTURER AS SPECIFIED IN DIVISION
MECHANICAL EQUIPMENT SHALL BE RETURNED TO
AI
HUMIDITY LEVEL
NORMAL OPERATION. DI
X
CONTROLLER
DO
HUMIDITY BY BAS ONLY.
AI
AO
X X
FROM PREVIOUS CONTROLLER
TO NEXT CONTROLLER
X
CONTROLLER
CONTROLLER
FROM PREVIOUS CONTROLLER
MISCELLANEOUS & OA MONITROING
A2
X
X FROM PREVIOUS CONTROLLER
TO NEXT CONTROLLER SHEET REFERENCE NUMBER:
TO NEXT CONTROLLER
UNIT HEATER - CONTROL DIAGRAM A4
N.T.S.
N.T.S.
M-8020
DEHUMIDIFIER
Sheet 146
N.T.S.
of 222
TYPICAL
9:16:17
m oraja
AM
A1
23, MONITORING OF TEMPERATURE AND
CONTROLS
METER
MEXI CO
WATER
METER
LAS CRUCES,NEW
GAS
METER
U.S.ARMY
ELEC.
SEQUENCE OF OPERATION
SEQUENCE OF OPERATION
M
SEQUENCE OF OPERATION
RESERVE CENTER
1 4
7/22/2011
c:\pwworki ng\gbna\m oraja\dm s97636\LCARC_M-8020.dgn
HUMIDISTAT
FAX (714) 327-1601
M M
TEL (714) 327-1600
EF 2-6
M .BETZ
EF 2-5
Subm i tted by:
EF 1-11
DISCONNECT SWITCH
LOUI SVI LLE DI STRI CT
DISCONNECT SWITCH
Desi gned by:
DISCONNECT SWITCH
DI
A.REED
CLOSE.
HUTTON CENTRE DRI VE,SUI TE 800
30 MINUTE TIMER
MOTORIZED INTAKE DAMPER SHALL WALL SWITCH (ON-OFF-UP-DOWN)
Date:
STOP AND THE INTERLOCKED
072811
THE "OFF" POSITION THE FAN SHALL
SANTA ANA, CALI FORNI A 92707
RELAY
4
B. WHEN THE SWITCH IS PLACED IN
B
F-171-40-160
5
Project Code:
1
Revi ewed by:
DISCONNECT SWITCH
MINUTES.
CD
EF 2-6
A.REED
INTAKE VENTEILATOR (IV-9) MOTORIZED
EF 2-5
W 912QR-11-R-0071
EF 1-11
THE FAN SHALL START AND THE DAMPER SHALL OPEN.
SHALL START AND OPERATE FOR A
M
Sol i ci tati on No.
SWITCH IS PLACED IN "ON" POSITION,
MAGNETIC MOTOR STARTER
CONTROLLED BY A 30 MINUTE WALL
Rev.
CIRCUIT BREAKER
1 4
CIRCUIT BREAKER
4-POSITION WALL SWITCH. WHEN THE CIRCUIT BREAKER
A. EXHAUST FANS SHALL BE MOUNTED TIMER SWITCH. THE FAN
SHALL BE OPERATED FROM THE LOCAL CIRCUIT BREAKERS
SEQUENCE OF OPERATION
C.KORPASH
N.T.S.
EXHAUST FAN - CONTROL DIAGRAM
Ckd by:
C2
Dwn by:
EXHAUST FAN - CONTROL DIAGRAM
TO NEXT CONTROLLER
I .FRANCO
C1
TO NEXT CONTROLLER
LOUI SVI LLE,KENTUCKY
FROM PREVIOUS CONTROLLER
1
2
*** Support Value Engineering - It Pays ***
4
5
CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11
1
*** Safety Pays ***
2
4
5
GENERAL NOTES A.
FOR MECHANICAL ABBREVIATIONS, SYMBOLS, AND NOTES REFER TO DRAWING M-0010. FOR CONTROL ABBREVIATIONS, SYMBOLS,
LOUISVILLE DISTRICT
Appr.
AND NOTES REFER TO DRAWING M-8000.
US Army Corps of Engineers
Date
KEY NOTES 1 AI
H
CONTROLS AND POINTS SHOWN ARE PART OF THE UNIT’S FACTORY CONTROL PANEL.
2
VFD
POINTS ARE PART OF THE OVERALL DDC SYSTEM, BUT NOT SPECIFICALLY INCLUDED IN THE UNIT’S PANEL. SHOWN FOR
TS
AI
D
EXHAUST
DP
PDI
OUTSIDE
OUTSIDE
AIR
AIR
CLARITY, AS AFFECTED BY THE SEQUENCE OF OPERATION OF DP
PDI
EACH SYSTEM.
FAN
OA TEMPERATURE AND HUMIDITY SENSORS (GLOBAL POINTS) LOCATED ON ROOF IN WEATHER SHEILD. ONLY
H
PRE-FILTER PRE-FILTER
OUTSIDE
ARC EC UNITS SHALL BE TREATED FROM ONE CENTRAL WT-1 MD 3B
M
SYSTEM LOCATED IN THE MECHANICAL ROOM. SYSTEM SHALL BE
EMERGENCY SHUTOFF LOW LEAK DAMPER
ENABLED BASED ON AVEAGE SUMP WATER CONDUCTIVITY.
MINIMUM OSA AIR FLOW MEASURING STATION
EMERGENCY SHUTOFF LOW LEAK DAMPER
INSIDE
FT DP
INDIVIDUAL WATER TREATMENT SYSTEM FOR EC 2-1 ONLY. ALL
M MD 3A
BDD
4
L
L
DPT
CO2 SENSOR ONLY FOR EC 1-1, 1-3, 1-4, AND 1-7
Descri pti on
ONE IS REQ’D FOR THE FACILITY
3 H
DI DO
DP
EMERGENCY SHUTOFF LOW LEAK DAMPER
M
MD
M
1A
PDI
PDI MINIMUM OSA AIR FLOW MEASURING STATION
L
H
H
INDIRECT
L
COOLER OUTSIDE
FAN
EVAP
C
AIR
TO FACP
DSD
DIRECT
H
HEAT EXCHANGER
EMERGENCY SHUTOFF LOW LEAK DAMPER
SUPPLY
SA AIR FLOW MEASURING
TS
COOLER PRE-FILTER
FT TS
FINAL FILTER
FT
LL
MS
TS
VFD
EMERGENCY SHUTOFF LOW LEAK DAMPER MD 2A
IEC
NO
Mark
RETURN DI VLV
MS
DO
M
Appr.
M SUPPLY
DSD
TO FACP
Date
EMERGENCY SHUTOFF LOW LEAK DAMPER
RETURN
S
AIR
Descri pti on
CO2
SPACE
TEM PERATURE
SPACE
HUM I DI TY
RELATI VE
SPACE
SUPPLY FAN
N.T.S.
120 V
2
2
POWER
THE CONTROLLER SHALL MODULATE THE DAMPERS AS THE FIRST STAGE OF COOLING TO MAINTAIN THE SUPPLY AIR
OUTDOOR AIR (AFTER BEING INDIRECT EVAPORATIVELY COOLED) IS LESS THAN THE
SYSTEM IS BACNET COMPATIBLE. ALL POINTS DESCRIBED AS ADJUSTABLE CAN BE ACCESSED BY KEYPAD OR BUILDING
TEMPERATURE SETPOINT. ECONOMIZER DAMPER (HEAT EXCHANGER BYPASS) SHALL MODULATE OPEN FOR FREE COOLING WHEN
ENTHALPY OF THE RETURN AIR. WHEN THE OUTDOOR AIR (AFTER BEING INDIRECT
AUTOMATION SYSTEM (BAS).
THE UNIT IS IN THE COOLING MODE AND THE O/A DRY BULB TEMP IS LESS THAN 55F (ADJUSTABLE). INDIRECT EVAP
EVAP COOLED) IS CALCULATED TO HAVE AN ENTHALPY GREATER THAN THE RETURN
COOLING SHALL BE OFF. HEAT EXCHANGER FACE DAMPER SHALL MODULATE CLOSED WHILE HEAT EXCHANGER BYPASS DAMPER
AIR, UNIT SHALL OPERATE AT MINIMUM OUTSIDE AIR AND EXHAUST FAN SHALL RUN IN
MODULATES OPEN AS REQUIRED TO ACHIEVE THE DESIRED SUPPLY AIR TEMPERATURE FOR COOLING. RECIRCULATION DAMPER
LOW SPEED.
CO2 SENSORS SHALL COMPARE CO2 LEVELS BETWEEN OUTSIDE AIR (OSA) ROOM AIR. OUTSIDE AIR AND EXHAUST AIR DAMPERS ON THE RESPECTIVE UNIT SHALL MODULATE TO MAINTAIN A CO2 LEVEL BELOW 700PPM(ADJUSTABLE). UNDER NORMAL OPERATING MODE, IF
HARD-WIRED FAN SHUT-DOWN (SMOKE DETECTOR, WIRING, CONDUIT, AND RELAYS) SHALL BE
BE CLOSED AND THE DRAIN VALVE SHALL BE OPEN WHENEVER THE DRAIN CYCLE IS
THE ECONOMIZERS SHALL CLOSE FOR FREEZE PROTECTION, WHENEVER:
- EMERGENCY SHUTDOWN SIGNAL
AFTER IT IS INITIATED (UNLESS FILL IS PROHIBITED BY OUTSIDE AIR TEMPERATURE).
- SMOKE DETECTION
COIL) FALLS BELOW SETPOINT (35F, ADJUSTABLE) AND THE OUTSIDE AIR TEMPERATURE IS BELOW 35F (WITH A 5F DEADBAND, RETURNING TO NORMAL OPERATION AT 40F OUTSIDE
- THE MIXED AIR TEMPERATURE DROPS FROM 40F TO 35F MORNING WARM-UP CONTROL UNIT WILL ENTER MORNING WARM-UP UPON UNIT START UP. THE FAN WILL BE STARTED, THE HEATING COIL WILL BE ENABLED AND THE ECONOMIZER DAMPERS ARE HELD SHUT. THE UNIT WILL REMAIN IN WARM-UP UNTIL EITHER THE RETURN AIR
COOLING CONTROL
TEMPERATURE EQUALS 68F (ADJUSTABLE) OR THE DURATION OF MORNING WARM-UP EXCEEDS THE MAXIMUM MORNING WARM-UP
COOLING SHALL BE STAGED IN ORDER TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT WHEN IN COOLING MODE. THE
TIME LIMIT (ADJUSTABLE), WHICHEVER HAPPENS FIRST.
SUPPLY FAN VFD
AIR) THE OUTSIDE AIR DAMPER SHALL CLOSE, THE RETURN AIR DAMPER SHALL OPEN, THE
SUPPLY FAN VFD SHALL HAVE A SOFT START CAPABILITY AND SHALL RAMP UP SPEED
EXHAUST AIR DAMPER SHALL CLOSE, AND AN ALARM CONDITION SHALL BE INDICATED. ONCE
AS FINAL FILTER PRESSURE DROP INCREASES TO MAINTAIN PROPER SUPPLY AIR
THE OUTSIDE AIR TEMPERATURE RISES ABOVE 40F THE DAMPERS SHALL BE RELEASED TO
VOLUME.
OPERATE IN THE NORMAL MODE.
SYSTEM WILL STAGE UP WHEN THE SUPPLY AIR TEMPERATURE IS ABOVE SETPOINT PLUS 1.5F. THE SYSTEM WILL STAGE
WHENEVER THE TEMPERATURE AT THE AVERAGING SENSOR LOCATED DOWNSTREAM OF THE
DOWN WHEN THE SUPPLY AIR TEMPERATURE IS BELOW SETPOINT MINUS 1.5F. INTERSTAGE DELAYS OF 120 SECONDS
HEATING COIL FALLS BELOW SETPOINT (40F, ADJUSTABLE) THE FANS SHALL BE DISABLED,
(ADJUSTABLE) WILL BE USED. INDIRECT COOLING IS ACTIVE WHENEVER THE O/A DRY BULB IS MORE THAN 5F ABOVE THE
THE OUTSIDE AIR DAMPER SHALL CLOSE, THE RETURN AIR DAMPER SHALL OPEN, THE
FAN CONTROL
RETURN AIR WET BULB TEMP. RETURN AIR WET BULB TEMP IS CALCULATED BY UNIT CONTROLLER FROM THE RETURN AIR DRY
EXHAUST AIR DAMPER SHALL CLOSE, AND AN ALARM CONDITION SHALL BE INDICATED. ONCE
WHEN THE UNIT IS COMMANDED TO RUN, THE SUPPLY FAN STARTS AND RUNS CONTINUOUSLY.
BULB TEMP AND RH. INDIRECT EVAP COOLING SUMP SHALL BE AUTOMATICALLY DRAINED AND FLUSHED ONCE DAILY, BETWEEN
THE OUTSIDE AIR TEMPERATURE RISES ABOVE 40F THE FANS AND DAMPERS SHALL BE
3AM AND 4AM. SUMP SHALL HAVE AUTO FREEZE PROTECTION, AND WILL DRAIN WHENEVER AMBIENT DRY-BULB IS LESS THAN
RELEASED TO OPERATE IN THE NORMAL MODEL.
WHENEVER THE CURRENT RELAY INDICATES THE SUPPLY FAN STATUS IS ON, THE EXHAUST FAN WILL START AND RUN
7/22/2011
Pl ot scal e:NONE
Pl ot date:
WHENEVER THE MIXED AIR TEMPERATURE (TEMPERATURE ENTERING THE HEATING WATER
FAX (714) 327-1601
INITIATED (WEEKLY, ADJUSTABLE). THE DRAIN CYCLE SHALL TERMINATE 10 MINUTES
TEL (714) 327-1600
- OUTSIDE AIR ENTHALPY IS LESS THEN RETURN AIR ENTHALPY
FURNISHED AND INSTALLED BY DIVISION 28.
HUTTON CENTRE DRI VE,SUI TE 800
ADJUSTABLE WITH A 25 DEADBAND, DRAINED AT 38F). THE SUMP FILL VALVE SHALL
SANTA ANA, CALI FORNI A 92707
THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING ANY OF THE FOLLOWING:
WHENEVER THE OUTSIDE AIR TEMPERATURE IS ABOVE SETPOINT (INITIALLY 60F,
4
OR
EMERGENCY SHUTDOWN
EXTRA SET OF DRY CONTACTS FURNISHED WITH DUCT-MOUNTED SMOKE DETECTOR).
LOUI SVI LLE DI STRI CT
- OUTSIDE AIR WET BULB IS LESS THAN 58F (ADJUSTABLE)
THE SUMP FILL VALVE SHALL BE OPEN AND THE DRAIN VALVE SHALL BE CLOSED
LOUI SVI LLE,KENTUCKY
HOURS BACK TO 0.
Desi gned by:
SUMP FULL & DRAIN, FLUSH
A.REED
AND
CORPS OF ENGI NEERS
EXCEEDS 1000 HOURS (ADJUSTABLE). ONCE MAINTENANCE IS DONE, THE KEYPAD PROVIDES THE ABILITY TO RESET THE RUN
MONITORED AND DISPLAYED VIA THE DIRECT DIGITAL CONTROL SYSTEM AS DETERMINED VIA
M .BETZ
WHENEVER SMOKE IS DETECTED (DUCT-MOUNTED SMOKE DETECTOR STATUS TO BE
FOR EQUIPMENT MAINTENANCE PURPOSES, RUN HOURS ARE ACCUMULATED AND WILL GENERATE AN ALARM WHEN THE TOTAL
Subm i tted by:
THE DUCT-MOUNTED SMOKE DETECTOR SHALL DISABLE THE AIR HANDLING UNIT FANS
F-171-40-160
AIR TEMP OR B) THE RETURN AIR TEMP AT SETPOINT.
Project Code:
- AND OUTSIDE AIR TEMPERATURE IS BELOW THE OUTSIDE AIR LOCKOUT SETTING 55F(ADJUSTABLE)
SAFETIES
Revi ewed by:
CONTROL. HW VALVE SHALL MODULATE AS REQUIRED FOR CONTROLLING A) SUPPLY
A.REED
- AND THE HEATING MODE HAS BEEN OFF FOR A MINIMUM OF 4 MINUTES
W 912QR-11-R-0071
EXHAUST FAN WILL OPERATE AT LOWER SPEED TO MAINTAIN BUILDING PRESSURE
U.S.ARMY
RUN HOUR TRACKING
- PROOF OF AIR FLOW IS ON
Date:
AND AT THE REDUCED HEATING SUPPLY AIR VOLUME SHOWN IN SCHEDULES.
- REMOTE START/STOP: THE UNIT IS COMMANDED TO RUN BASED UPON A FIELD SUPPLIED SIGNAL.
Sol i ci tati on No.
10% INCREASE OR DECREASE (ADJUSTABLE).
C.KORPASH
WHEN IN THE HEATING MODE THE UNIT SHALL OPERATE WITH MINIMUM OUTDOOR AIR
Ckd by:
ALLOWED TO CONTINUE NORMAL OPERATION. THE OSA DAMPER SHALL BE LIMITED TO A
Dwn by:
AT OR BELOW THE LOW SETPOINT FOR AT LEAST 15 MINUTES, THE ECONOMIZER SHALL BE
I .FRANCO
LEVEL IS AT OR BELOW THE LOW SETPOINT OF 600 PPM (ADJUSTABLE). WHEN THE CO2 IS
Fi l e nam e:LCARC_M 8030. dgn
700PPM, THE ECONOMIZER WILL BE IN OVERRIDE AND THE DAMPERS WILL BE MODULATED TO BRING IN OUTSIDE AIR (UNLESS OSA CO2 LEVEL IS ABOVE 700PPM) UNTIL THE CO2
HEATING MODE FREE COOLING MODE SHALL BE ENABLED WHENEVER:
3
THE CO2 SENSOR IN THE ROOM SENSES A CO2 LEVEL ABOVE THE HIGH SETPOINT OF
TO CONTROL THE BUILDING STATIC PRESSURE SLIGHTLY POSITIVE.
- TIME OF DAY SCHEDULE: THE UNIT WILL BE COMMANDED TO RUN BASED UPON AN INTERNAL TIME OF DAY SCHEDULE.
CO2 LEVEL CONTROL
Mark
UNIT SHALL USE THE FOLLOWING CONTROL STRATEGY DURING SUMMER COOLING MODE
COMMUNICATION TRUNK
Rev.
SEQUENCE OF OPERATION
- 24 HOURS
38F.
CONTINUOUSLY.
ALARMS COOLING MODE SHALL BE ENABLED WHEN:
ALARMS SHALL BE PROVIDED AS FOLLOWS:
SUPPLY AIR TEMPERATURE CONTROL - FIXED OR RESET SCHEDULE OPTION
- LOW/HIGH OUTSIDE AIR TEMPERATURE COOLING STAGING WILL BE AS FOLLOWS:
- LOW/HIGH MIXED AIR TEMPERATURE
THE METHOD OF CONTROLLING TEMPERATURE IS SELECTABLE. THE OPERATOR WILL HAVE THE OPTION OF CHOOSING BETWEEN A FIXED SUPPLY AIR SETPOINT (ADJUSTABLE), OR A RESET SCHEDULE BASED UPON THE RETURN AIR TEMPERATURE.
- LOW/HIGH SUPPLY AIR TEMPERATURE
- ECONOMIZERS ARE OPEN AND AT MAXIMUM POSITION OR FREE COOLING IS OFF
- LOW/HIGH RETURN AIR TEMPERATURE
- INDIRECT EVAPORATIVE COOLING
A
WHEN THE RESET SCHEDULE IS SELECTED, THE CONTROLLER SHALL ADJUST THE SUPPLY AIR TEMPERATURE SETPOINT AS
- LOW/HIGH OUTSIDE HUMIDITY
- DIRECT EVAPORATIVE PUMP
- LOW/HIGH RETURN HUMIDITY
REQUIRED TO MAINTAIN THE RETURN AIR AT SETPOINT 78F (ADJUSTABLE).
- FAN FAILURES: COMMANDED ON AND AFTER A 2 MINUTE DELAY, THE RUN STATUS OF A FAN IS OFF
THE DIRECT EVAPORATIVE PUMP SHALL BE ENABLED WHENEVER:
- DIRECT PUMP FAILURE: COMMANDED ON AND AFTER A 2 MINUTE DELAY, THE PUMP
NIGHT SETBACK OPERATION DURING UNOCCUPIED HOURS OR NIGHT SETBACK PERIODS, THE UNITS SHALL MAINTAIN A MINIMUM OF 40F (ADJUSTABLE) DURING WINTER MODE. BOILERS AND PUMPS SHALL BE AVAILABLE TO PROVIDE HEAT AND OUTSIDE AIR DAMPERS SHALL BE CLOSED. DURING SUMMER MONTHS, THE UNITS SHALL BE ENABLED AND OPERATIONG TO KEEP THE SPACE AT A MAXIMUM OF 85F
RUN STATUS IS OFF
- PROOF OF AIR FLOW IS ON - UNIT SHALL OPERATE WITH 100% OSA
CONTROLS
- DIRTY FILTERS
MEXI CO
- SMOKE DETECTION
- AND OUTSIDE AIR TEMPERATURE IS ABOVE THE OUTSIDE AIR LOCKOUT SETTING 55F(ADJUSTABLE)
LAS CRUCES,NEW
- EMERGENCY SHUTDOWN SIGNAL
- AND THE HEATING MODE HAS BEEN OFF FOR A MINIMUM OF 4 MINUTES
U.S.ARMY
TO PREVENT SHORT CYCLING, MINIMUM ON/OFF TIMES OF 2 MINUTES WILL BE USED.
- PROOF OF AIR FLOW IS ON
RESERVE CENTER
THE SUPPLY FAN SHALL HAVE A 10 MINUTE DELAY ON STOP IN ORDER TO DRY OUT THE DIRECT EVAPORATIVE MEDIA.
7/22/2011
c:\pwworki ng\gbna\m oraja\dm s97636\LCARC_M-8030.dgn
3
TO NEXT DEVICE
GENERAL
HOLIDAYS CAN BE ENTERED TO OVERRIDE THE NORMAL SCHEDULE.
AI
BY
EVAPORATIVE COOLING UNIT CONTROL SYSTEM DIAGRAM (EC 1-1,3,4,5,6,7, AND 2-1)
SHALL BE CLOSED DURING ECONOMIZER MODE. EXHAUST FAN VFD SHALL MODULATE THE EXHAUST FAN SPEED AS REQUIRED
B
2
AI
DIV. 26
SUCH THAT IT USES 100% O/A WHENEVER THE CALCULATED ENTHALPY OF THE
- OFF MODE
AI
1
FREE COOLING
RUN CONDITIONS (KEYPAD SELECTABLE)
TEM PERATURE
SUPPLY FAN
2
SEQUENCE OF OPERATION AIR HANDLING UNITS (WITH INDIRECT AND DIRECT EVAPORATIVE COOLING)
AI
SUPPLY AI R
DO
START/STOP
DI
STATUS
VFD FAULT
DI
CONTROL
SA FLOW
VOLUM E
VALVES LI NE DRAI N
DEC SUM P
AO
AI
VFD SPEED
DI
START/STOP
DEC PUM P
TEM PERATURE
DO
FI LL AND
DI
HEATI NG COI L
FREEZE STAT
CONTROL
VALVE (HW )
FI NAL FI LTER
FI LTER STATUS
OA FI LTER
DI
AO
AI
STATUS
OA FI LTER
DI
STATUS
VOLUM E
OSA FLOW
DAM PER CONTROL
ECONOM I ZER
PACKAGED FACTORY DIRECT DIGITAL CONTROLLER
1
DI
AI
072811
4
AO
DAM PER CONTROL
2
AO
RECI RCULATI ON
AI
HEAT EXCHANGER
2
AI R
AI R
AI
DRY BULB
RETURN
W ATER BLEED
M OTORI ZED SUM P
SUM P W ATER
CONDUCTI VI TY
AI
W ET BULB
DO
AI
ENABLE/DI SABLE
VALVES LI NE DRAI N
W ATER TREATM ENT
DO
DO
I DEC SUM P FI LL AND
CONTROLLER
BUI LDI NG PRESSURE
STATUS FAN
I DEC PUM P
DO
AI
START/STOP
DI
EXHAUST
VFD FAULT
VFD SPEED
DI
CONTROL
EXHAUST FAN
OSA FLOW
VOLUM E
AO
START/STOP
DO
AI
CONTROL
OA
BLOCK
DAM PER
OA FI LTER
TERMINATION
AO
STATUS
DI
RETURN AIR WET BULB
H
TEM PERATURE
RETURN AIR TS DRY BULB
RETURN
C
- AND THE RETURN AIR HUMIDITY IS BELOW 60% RH (ADJUSTABLE) - AND THE SUPPLY AIR TEMPERATURE IS ABOVE SETPOINT 55F (ADJUSTABLE)
(ADJUSTABLE).
MIXED AIR DAMPERS
SHEET REFERENCE NUMBER:
IF THE SUPPLY FAN IS OFF OR THE SYSTEM IS IN MORNING WARM-UP MODE, THE EXHAUST AIR DAMPERS WILL CLOSE FULLY AND THE RETURN AIR DAMPERS WILL OPEN FULLY.
M-8030 of 222
9:17:13
m oraja
AM
Sheet 147
1
2
1 *** Support Value Engineering - It Pays ***
42
5
CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11
1
*** Safety Pays ***
2
4
5
GENERAL NOTES A.
FOR MECHANICAL ABBREVIATIONS, SYMBOLS, AND NOTES REFER TO DRAWING M-0010. FOR CONTROL ABBREVIATIONS, SYMBOLS, AND NOTES REFER TO DRAWING M-8000.
US Army Corps of Engineers LOUISVILLE DISTRICT
M
CONDENSER
KEY NOTES
CU 1
1
Appr.
RL
Date
RL
CONTROLS AND POINTS SHOWN ARE PART OF THE UNIT’S FACTORY CONTROL PANEL.
COMPRESSORS VFD
POINTS ARE PART OF THE OVERALL DDC SYSTEM, BUT NOT
2
HOT GAS BYPASS
SPECIFICALLY INCLUDED IN THE UNIT’S PANEL. SHOWN FOR EXHAUST
DP
PDI
OUTSIDE
OUTSIDE
AIR
AIR
CLARITY, AS AFFECTED BY THE SEQUENCE OF OPERATION OF
DP
PDI
EACH SYSTEM.
RS
FAN
D
H
H
PRE-FILTER PRE-FILTER
L
L
DPT
M MD 3A
BDD
M EMERGENCY SHUTOFF LOW LEAK DAMPER
MD 3B
EMERGENCY SHUTOFF LOW LEAK DAMPER OUTSIDE
MIN OSA AIR FLOW MEASURING STATION
INSIDE
FT
DI
DP DO
EMERGENCY SHUTOFF LOW LEAK DAMPER
SUPPLY FAN
MD
M
M
Descri pti on
DP
1A TS
EMERGENCY SHUTOFF LOW LEAK DAMPER
PDI
PDI MIN OSA AIR FLOW MEASURING STATION
L
H
H
INDIRECT
DSD TO FACP
SA AIR FLOW MEASURING
L
COOLER OUTSIDE
D
HEAT EXCHANGER
H X
AIR
C
PRE-FILTER
FT FINAL FILTER
FT
TS
EMERGENCY SHUTOFF LOW LEAK DAMPER
LOCAL EMERG. SHUTOFF SWITCH
VFD
TS
M EMERGENCY SHUTOFF LOW LEAK DAMPER
MD
NO
IDEC
LL
DO
NO
2A RETURN DI
SORTING / DISTRIBUTION Mark
VLV
DO
M
SUPPLY
M EMERGENCY SHUTOFF LOW LEAK DAMPER
Appr.
MS
DSD
Date
TO FACP
RETURN
S
AIR
C
2
SPACE
2
Descri pti on
TEM PERATURE
AI
HUM I DI TY
RELATI VE
SPACE
SUPPLY FAN
TEM PERATURE
SUPPLY FAN
AI
AI
SUPPLY AI R
DO
START/STOP
DI
STATUS
VFD FAULT
DI
CONTROL
SA FLOW
VFD SPEED
AO
AI
VOLUM E
TEM PERATURE
FREEZE STAT
CONTROL
VALVE (HW )
DI
HEATI NG COI L
DI
AO
DI
CU- 1
COOLI NG STAGE 3
DI
CU- 1
CU- 1
CU- 1
1
DI
COOLI NG STAGE2
DI
COOLI NG STAGE 1
CU- 1
DI
STATUS
CU- 1
START/STOP
FI NAL
DO
FI LTER STATUS
OA FI LTER
STATUS
OA FI LTER
OSA FLOW
AI
COOLI NG STAGE 4
PACKAGED FACTORY DIRECT DIGITAL CONTROLLER
DI
STATUS
DI
AI
DAM PER CONTROL
ECONOM I ZER
DAM PER CONTROL
AO
VOLUM E
AO
RECI RCULATI ON
2
TEM PERATURE
AI R
HEAT EXCHANGER
2
AI
W ET BULB
AI R
AI
DRY BULB
RETURN
M OTORI ZED SUM P
AI
W ATER BLEED
SUM P W ATER
CONDUCTI VI TY
W ATER TREATM ENT
DO
AI
ENABLE/DI SABLE
DO
VALVES
I DEC SUM P FI LL AND
DO
LI NE DRAI N
I DEC PUM P
DO
START/STOP
CONTROLLER
STATUS
AI
FAN
EXHAUST
DI
VFD FAULT
VFD SPEED
DI
CONTROL
EXHAUST FAN
OSA FLOW
AO
BUI LDI NG PRESSURE
OA
OA FI LTER
STATUS
BLOCK
VOLUM E
TERMINATION
DO
AI
START/STOP
AO
DAM PER CONTROL
DI
RETURN AIR WET BULB
H TS
RETURN
RETURN AIR DRY BULB
2
POWER BY DIV. 26
TO NEXT DEVICE
COMMUNICATION TRUNK
EVAPORATIVE COOLING UNIT CONTROL SYSTEM DIAGRAM (EC 1-2, CU-1) N.T.S.
Mark
1
120 V
- AND OUTSIDE AIR TEMPERATURE IS BELOW THE OUTSIDE AIR LOCKOUT SETTING 55F(ADJUSTABLE) RUN HOUR TRACKING FOR EQUIPMENT MAINTENANCE PURPOSES, RUN HOURS ARE ACCUMULATED AND WILL GENERATE AN ALARM WHEN THE TOTAL
AND
EXCEEDS 1000 HOURS (ADJUSTABLE). ONCE MAINTENANCE IS DONE, THE KEYPAD PROVIDES THE ABILITY TO RESET THE RUN HOURS BACK TO 0.
AIR) THE OUTSIDE AIR DAMPER SHALL CLOSE, THE RETURN AIR DAMPER SHALL OPEN, THE A) IDEC SHALL OPERATE TO PRECOOL MINIMUM OSA. OSA DAMPERS
EXHAUST AIR DAMPER SHALL CLOSE, AND AN ALARM CONDITION SHALL BE INDICATED. ONCE
SHALL MODULATE TO MINIMUM POSITIONS AND RETURN AIR DAMPERS
THE OUTSIDE AIR TEMPERATURE RISES ABOVE 40F THE DAMPERS SHALL BE RELEASED TO
SHALL OPEN.
OPERATE IN THE NORMAL MODE.
B) SUPPLY AIR FAN SHALL RAMP DOWN TO 5000 CFM (DURING DX
WHENEVER THE TEMPERATURE AT THE AVERAGING SENSOR LOCATED DOWNSTREAM OF THE
COOLING) AND THE EXHAUST FAN SHALL TRACK WITH THE BUILDING
HEATING COIL FALLS BELOW SETPOINT (40F, ADJUSTABLE) THE FANS SHALL BE DISABLED,
PRESSURE SETPOINT 0.05" WG (ADJ)
THE OUTSIDE AIR DAMPER SHALL CLOSE, THE RETURN AIR DAMPER SHALL OPEN, THE
- OUTSIDE AIR WET BULB IS LESS THAN 58F (ADJUSTABLE) - OUTSIDE AIR ENTHALPY IS LESS THEN RETURN AIR ENTHALPY
THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING ANY OF THE FOLLOWING: THE ECONOMIZERS SHALL CLOSE FOR FREEZE PROTECTION, WHENEVER:
EXHAUST AIR DAMPER SHALL CLOSE, AND AN ALARM CONDITION SHALL BE INDICATED. ONCE
- EMERGENCY SHUTDOWN SIGNAL B) CONDENSING UNIT SHALL STAGE "ON" COOLING STAGES TO MAINTAIN 45-55% RH
- THE MIXED AIR TEMPERATURE DROPS FROM 40F TO 35F
WITHIN SPACE.
C) SUPPLY AIR DISCHARGE TEMPERATURE SHALL BE MAINTAINED BETWEEN 53F AND
UNIT WILL ENTER MORNING WARM-UP UPON UNIT START UP. THE FAN WILL BE STARTED, THE HEATING COIL WILL BE ENABLED
COOLING CONTROL
AND THE ECONOMIZER DAMPERS ARE HELD SHUT. THE UNIT WILL REMAIN IN WARM-UP UNTIL EITHER THE RETURN AIR
COOLING SHALL BE STAGED IN ORDER TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT WHEN IN COOLING MODE. THE
TEMPERATURE EQUALS 68F (ADJUSTABLE) OR THE DURATION OF MORNING WARM-UP EXCEEDS THE MAXIMUM MORNING WARM-UP
SYSTEM WILL STAGE UP WHEN THE SUPPLY AIR TEMPERATURE IS ABOVE SETPOINT PLUS 1.5F. THE SYSTEM WILL STAGE
TIME LIMIT (ADJUSTABLE), WHICHEVER HAPPENS FIRST.
DOWN WHEN THE SUPPLY AIR TEMPERATURE IS BELOW SETPOINT MINUS 1.5F. INTERSTAGE DELAYS OF 120 SECONDS
UNIT SHALL USE THE FOLLOWING CONTROL STRATEGY DURING SUMMER COOLING MODE
(ADJUSTABLE) WILL BE USED. INDIRECT COOLING IS ACTIVE WHENEVER THE O/A DRY BULB IS MORE THAN 5F ABOVE THE
SUCH THAT IT USES 100% O/A WHENEVER THE CALCULATED ENTHALPY OF THE
RETURN AIR WET BULB TEMP. RETURN AIR WET BULB TEMP IS CALCULATED BY UNIT CONTROLLER FROM THE RETURN AIR DRY
OUTDOOR AIR (AFTER BEING INDIRECT EVAPORATIVELY COOLED) IS LESS THAN THE
FAN CONTROL
BULB TEMP AND RH. INDIRECT EVAP COOLING SUMP SHALL BE AUTOMATICALLY DRAINED AND FLUSHED ONCE DAILY, BETWEEN
ENTHALPY OF THE RETURN AIR. WHEN THE OUTDOOR AIR (AFTER BEING INDIRECT
WHEN THE UNIT IS COMMANDED TO RUN, THE SUPPLY FAN STARTS AND RUNS CONTINUOUSLY.
3AM AND 4AM. SUMP SHALL HAVE AUTO FREEZE PROTECTION, AND WILL DRAIN WHENEVER AMBIENT DRY-BULB IS LESS THAN
EVAP COOLED) IS CALCULATED TO HAVE AN ENTHALPY GREATER THAN THE RETURN
38F.
AIR, UNIT SHALL OPERATE AT MINIMUM OUTSIDE AIR AND EXHAUST FAN SHALL RUN IN
55F WHILE CONDENSING UNIT IS "ON". - EMERGENCY SHUTDOWN SIGNAL
WHEN IN THE HEATING MODE THE UNIT SHALL OPERATE WITH MINIMUM OUTDOOR AIR
- AND THE HEATING MODE HAS BEEN OFF FOR A MINIMUM OF 4 MINUTES
AND AT THE REDUCED HEATING SUPPLY AIR VOLUME SHOWN IN SCHEDULES.
- AND OUTSIDE AIR TEMPERATURE IS ABOVE THE OUTSIDE AIR LOCKOUT SETTING 55F(ADJUSTABLE)
EXHAUST FAN WILL OPERATE AT LOW SPEED TO MAINTAIN BUILDING PRESSURE SETPOINT. HW VALVE SHALL MODULATE AS REQUIRED FOR CONTROLLING A) SUPPLY AIR TEMP OR B) THE RETURN AIR TEMP AT SETPOINT.
- ECONOMIZERS ARE OPEN AND AT MAXIMUM POSITION OR FREE COOLING IS OFF
SUMP FULL & DRAIN, FLUSH
FIXED SUPPLY AIR SETPOINT (ADJUSTABLE), OR A RESET SCHEDULE BASED UPON THE RETURN AIR TEMPERATURE.
- INDIRECT EVAPORATIVE COOLING
THE SUMP FILL VALVE SHALL BE OPEN AND THE DRAIN VALVE SHALL BE CLOSED
- DX COOLING WHEN THE RESET SCHEDULE IS SELECTED, THE CONTROLLER SHALL ADJUST THE SUPPLY AIR TEMPERATURE SETPOINT AS
- LOW/HIGH RETURN AIR TEMPERATURE
- FAN FAILURES: COMMANDED ON AND AFTER A 2 MINUTE DELAY, THE RUN STATUS OF A FAN IS OFF - COOLING CIRCUIT FAILURES: COMMANDED ON AND AFTER A 2 MINUTE DELAY, THE RUN STATUS OF A COMPRESSOR IS OFF
WHENEVER THE OUTSIDE AIR TEMPERATURE IS ABOVE SETPOINT (INITIALLY 60F, ADJUSTABLE WITH A 25 DEADBAND, DRAINED AT 38F). THE SUMP FILL VALVE SHALL
REQUIRED TO MAINTAIN THE RETURN AIR AT SETPOINT 78F (ADJUSTABLE).
7/22/2011
Pl ot scal e:NONE
- LOW/HIGH SUPPLY AIR TEMPERATURE
RUN STATUS IS OFF
THE METHOD OF CONTROLLING TEMPERATURE IS SELECTABLE. THE OPERATOR WILL HAVE THE OPTION OF CHOOSING BETWEEN A
Pl ot date:
- LOW/HIGH MIXED AIR TEMPERATURE
- DIRECT PUMP FAILURE: COMMANDED ON AND AFTER A 2 MINUTE DELAY, THE PUMP
COOLING STAGING WILL BE AS FOLLOWS:
F-171-40-160
- LOW/HIGH OUTSIDE AIR TEMPERATURE
- LOW/HIGH RETURN HUMIDITY
- PROOF OF AIR FLOW IS ON
A SUPPLY AIR TEMPERATURE CONTROL - FIXED OR RESET SCHEDULE OPTION
- DIRTY FILTERS
- LOW/HIGH OUTSIDE HUMIDITY HEATING MODE
TO PREVENT SHORT CYCLING, MINIMUM ON/OFF TIMES OF 2 MINUTES WILL BE USED.
- SMOKE DETECTION
LOW SPEED. COOLING MODE SHALL BE ENABLED WHEN:
THE SUPPLY FAN SHALL HAVE A 10 MINUTE DELAY ON STOP IN ORDER TO DRY OUT THE DIRECT EVAPORATIVE MEDIA.
ALARMS ALARMS SHALL BE PROVIDED AS FOLLOWS:
WHENEVER THE CURRENT RELAY INDICATES THE SUPPLY FAN STATUS IS ON, THE EXHAUST FAN WILL START AND RUN
7/22/2011
c:\pwworki ng\gbna\m oraja\dm s97636\LCARC_M-8040.dgn
MORNING WARM-UP CONTROL
CONTINUOUSLY.
THE OUTSIDE AIR TEMPERATURE RISES ABOVE 40F THE FANS AND DAMPERS SHALL BE RELEASED TO OPERATE IN THE NORMAL MODEL.
U.S.ARMY
- SMOKE DETECTION
U.S.ARMY
OR EMERGENCY SHUTDOWN
FAX (714) 327-1601
BELOW 35F (WITH A 5F DEADBAND, RETURNING TO NORMAL OPERATION AT 40F OUTSIDE
TEL (714) 327-1600
SHORT CYCLING AND ALLOW PROPER TEMPERATURE RESPONSE TIME.
M .BETZ
- AND THE HEATING MODE HAS BEEN OFF FOR A MINIMUM OF 4 MINUTES
Subm i tted by:
COIL) FALLS BELOW SETPOINT (35F, ADJUSTABLE) AND THE OUTSIDE AIR TEMPERATURE IS
HUTTON CENTRE DRI VE,SUI TE 800
INTER-STAGE DELAYS AND MINIMUM ON/OFF TIME DELAYS ARE USED TO PREVENT
SANTA ANA, CALI FORNI A 92707
- PROOF OF AIR FLOW IS ON
LOUI SVI LLE DI STRI CT
WHENEVER THE MIXED AIR TEMPERATURE (TEMPERATURE ENTERING THE HEATING WATER
MEXI CO
- REMOTE START/STOP: THE UNIT IS COMMANDED TO RUN BASED UPON A FIELD SUPPLIED SIGNAL.
BELOW SETPOINT AND IT HAS BEEN RUNNING FOR A MINIMUM TIME DELAY.
LAS CRUCES,NEW
- 24 HOURS
4
THAT EACH STAGE WILL BE COMMANDED OFF WHEN THE SUPPLY AIR TEMPERATURE IS
CONTROLS
FREE COOLING MODE SHALL BE ENABLED WHENEVER:
HOLIDAYS CAN BE ENTERED TO OVERRIDE THE NORMAL SCHEDULE.
Project Code:
FURNISHED AND INSTALLED BY DIVISION 28.
Revi ewed by:
STAGE WILL START. THE COMPRESSORS WILL STAGE DOWN IN THE SAME MANNER, IN
A.REED
HARD-WIRED FAN SHUT-DOWN (SMOKE DETECTOR, WIRING, CONDUIT, AND RELAYS) SHALL BE
W 912QR-11-R-0071
SUPPLY AIR TEMPERATURE IS STILL ABOVE SETPOINT PLUS 2F THEN THE SECOND
C.KORPASH
TO CONTROL THE BUILDING STATIC PRESSURE SLIGHTLY POSITIVE.
EXTRA SET OF DRY CONTACTS FURNISHED WITH DUCT-MOUNTED SMOKE DETECTOR).
Ckd by:
SETPOINT PLUS A DEADBAND OF 2F (ADJUSTABLE). IF AFTER A TIME DELAY, THE
Dwn by:
SHALL BE CLOSED DURING ECONOMIZER MODE. EXHAUST FAN VFD SHALL MODULATE THE EXHAUST FAN SPEED AS REQUIRED
Date:
THE FIRST DX STAGE WILL START WHEN THE SUPPLY AIR TEMPERATURE IS ABOVE
- OFF MODE - TIME OF DAY SCHEDULE: THE UNIT WILL BE COMMANDED TO RUN BASED UPON AN INTERNAL TIME OF DAY SCHEDULE.
MONITORED AND DISPLAYED VIA THE DIRECT DIGITAL CONTROL SYSTEM AS DETERMINED VIA
MODULATES OPEN AS REQUIRED TO ACHIEVE THE DESIRED SUPPLY AIR TEMPERATURE FOR COOLING. RECIRCULATION DAMPER
072811
WHENEVER SMOKE IS DETECTED (DUCT-MOUNTED SMOKE DETECTOR STATUS TO BE
COOLING SHALL BE OFF. HEAT EXCHANGER FACE DAMPER SHALL MODULATE CLOSED WHILE HEAT EXCHANGER BYPASS DAMPER
RUN CONDITIONS (KEYPAD SELECTABLE)
Sol i ci tati on No.
THE DUCT-MOUNTED SMOKE DETECTOR SHALL DISABLE THE AIR HANDLING UNIT FANS
I .FRANCO
(ADJUSTABLE).
SAFETIES
LOUI SVI LLE,KENTUCKY
THE UNIT IS IN THE COOLING MODE AND THE O/A DRY BULB TEMP IS LESS THAN 55F (ADJUSTABLE). INDIRECT EVAP
Rev.
TEMPERATURE SETPOINT. ECONOMIZER DAMPER (HEAT EXCHANGER BYPASS) SHALL MODULATE OPEN FOR FREE COOLING WHEN
Desi gned by:
AUTOMATION SYSTEM (BAS).
WHEN THE SYSTEM IS IN COOLING MODE, THE COMPRESSORS WILL BE STAGED UP OR DOWN IN ORDER TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT 55F
A.REED
SYSTEM IS BACNET COMPATIBLE. ALL POINTS DESCRIBED AS ADJUSTABLE CAN BE ACCESSED BY KEYPAD OR BUILDING
B
COMPRESSORS DX COOLING:
THE CONTROLLER SHALL MODULATE THE DAMPERS AS THE FIRST STAGE OF COOLING TO MAINTAIN THE SUPPLY AIR
CORPS OF ENGI NEERS
GENERAL
FREE COOLING
RESERVE CENTER
AIR HANDLING UNITS (WITH INDIRECT AND DIRECT EVAPORATIVE COOLING)
Fi l e nam e:LCARC_M 8040. dgn
SEQUENCE OF OPERATION
BE CLOSED AND THE DRAIN VALVE SHALL BE OPEN WHENEVER THE DRAIN CYCLE IS INITIATED (WEEKLY, ADJUSTABLE). THE DRAIN CYCLE SHALL TERMINATE 10 MINUTES
NIGHT SETBACK OPERATION
AFTER IT IS INITIATED (UNLESS FILL IS PROHIBITED BY OUTSIDE AIR TEMPERATURE).
DURING UNOCCUPIED HOURS OR NIGHT SETBACK PERIODS, THE UNITS SHALL MAINTAIN A MINIMUM OF 40F (ADJUSTABLE) DURING WINTER MODE. BOILERS AND PUMPS SHALL BE AVAILABLE TO PROVIDE HEAT
SUPPLY FAN VFD
AND OUTSIDE AIR DAMPERS SHALL BE CLOSED. DURING SUMMER MONTHS, THE UNITS SHALL BE
SHEET REFERENCE NUMBER:
SUPPLY FAN VFD SHALL HAVE A SOFT START CAPABILITY AND SHALL RAMP UP SPEED
ENABLED AND OPERATING TO KEEP THE SPACE AT A MAXIMUM OF 85F (ADJUSTABLE).
AS FINAL FILTER PRESSURE DROP INCREASES TO MAINTAIN PROPER SUPPLY AIR VOLUME.
MIXED AIR DAMPERS
M-8040
IF THE SUPPLY FAN IS OFF OR THE SYSTEM IS IN MORNING WARM-UP MODE, THE EXHAUST AIR DAMPERS WILL CLOSE FULLY Sheet 148
of 222
9:18:03
m oraja
AM
AND THE RETURN AIR DAMPERS WILL OPEN FULLY.
1
2
*** Support Value Engineering - It Pays ***
4
5
CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11
1
*** Safety Pays ***
2
4
5
GENERAL NOTES
OVERVIEW
A.
THE HEATING HOT WATER SYSTEM IS COMPRISED OF TWO BOILERS: (B-1, B-2). THE PREFERRED SEQUENCE OF HEATING HOT WATER STAGING MAY VARY BY SEASON. THE PRIMARY PUMPS AND RUN AT CONSTANT FLOW. THERE IS A SECONDARY HEATING HOT WATER SUPPLY LOOP WITH
FOR MECHANICAL ABBREVIATIONS, SYMBOLS, AND NOTES REFER TO DRAWING M-0010. FOR CONTROL ABBREVIATIONS, SYMBOLS,
US Army Corps of Engineers
AND NOTES REFER TO DRAWING M-8000.
LOUISVILLE DISTRICT
PI
VARIABLE SPEED DRIVES ON THE PUMPS CONTROLLED FROM DIFFERENTIAL PRESSURE, WHICH IS RESET LOAD.
HWP
Appr.
INCREMENTALLY TO OPERATE AT THE LOWEST SPPED AND PRESSURE POSSIBLE TO SATISTY THE CURRENT PT
1A
THE SYSTEM STATUS WILL BE DETERMINED FROM THE HEATING HOT WATER SUPPLY TEMPERATURE COMPARED WITH THE
HOT WATER RETURN FROM HEATING ZONES
Date
PI W/ CURRENT
SETPOINT AND THE OUTSIDE ARE TEMPERATURE IS LESS THAN [55F] (ADJUSTABLE).
SENSOR RELAY
CT
R
TI
TT
TI
TI
PT
TT
TT
TO PREVENT SHORT CYCLING, THE BOILER SYSTEM SHALL RUN FOR AND BE "OFF" FOR THE MINIMUM ADJUSTABLE TIMES UNLESS SHUTDIOWN ON SAFETIES OR OUTSIDE AIR CONDITIONS. PI
THE BOILER SHALL RUN SUBJECT TO ITS OWN INTERNAL SAFETIES AND CONTROLS.
SOLAR COLLECTOR ARRAYS
1
D
HWP
BOILER SEQUENCING
PT
1B HOT WATER STORAGE TANK
SOFTWARE [BAS] LEAD LAG SELECTOR SHALL BE PROVIDED TO ALLOW ANY OF THE BOILERS TO ACT AS THE LEAD MACHINE.
W/ CURRENT
1
CT
R
SENSOR RELAY
HEAT DUMP
HD
HST 1
THE BOILER WILL ONLY BE ENABLED TO OPERATE IN AUTO UPON THE FOLLOWING CONDIITONS: 1. BOILER SCHEDULE ON [BY BAS] 2. THERE ARE NOT ACTIVE ALARMS THAT INITIATE A SHUTDOWN (REPORTED TO BAS AND BOILER PANEL) 3. THERE IS A CALL FOR HEATING [BAS] 4. THE HEATING HOT WATER FLOWS ARE VERIFIED [BAS AND BOILER PANEL]
Descri pti on
5. THE SOLAR HOT WATER SYSTEM IS UNABLE TO MAINTAIN THE DESIRED HHWS TEMPERATURE PI FS
BOILER
UPON A CALL FOR HEATING:
FS
BOILER
B-1
TI
TT
B-2
HWP
OPEN THE CONTROL VALVE
PT
3
THE LEAD PRIMARY (HWP-1A) PUMP STARTS, THE PUMP STATUS IS CONFIRMED VIA A CURRENT SENSOR IN THE BAS AND THE FLOW IS CONFRIMED THROUGH A FLOW SWITCH.
W/ CURRENT
PI
TI
CT
R
SENSOR RELAY
TT
THEN THE ASSIGNED LEAD BOILER PUMP STARTS, THE PUMP STATUS IS CONFIRMED ON VIA A CURRENT SENSOR IN THE BAS AND THE FLOW IS CONFIRMED THROUGH A FLOW SWITCH.
GFA
PT
1
THERE SHALL BE [30-60] SECOND DELAYS BETWEEN THESE PUMPS, PER THE BOILER INTEGRAL PROGRAMMED SETTINGS (ADJUSTABLE) HOT WATER RETURN FROM HEATING ZONES
THE LEAD SECONDARY PUMP HWP THEN STARTS, RAMPING UP FROM THE MINIMUM SPEED OF 20 Hz VIA THE VARIABLE FREQUENCY DRIVE. THE BOILER MAINTAINS THE HHW SUPPLY TEMPERATURE AT THE SETPOINT[BAS] WHICH RANGES FROM 175F TO 180F, BASED ON A RESET SCHEDULE, BY MODULATING THE BOILER CAPACITY.
Appr.
Mark
BOIILER-HOT WATER SUPPLY TEMPERATURE SETPOINT
Date
ALARMS SHALL BE PROVIDED AS FOLLOWS:
DO
AI
DI
AI
HW P- 3
DI
Descri pti on
DI FF PRESS.
HW P- 3
HW P- 3
START/STOP
TEM PERATURE
SOLAR
COLLECTOR
TANK LVL LOW
GLYCOL FI LL
ASSEM BLY
TANK LVL LOW
GLYCOL FI LL
ASSEM BLY
LOW
DI
STATUS ON/OFF
GLYCOL FI LL
ASSEM BLY
M ODULATI NG
DI
HEAT DUM P VALVE
VLV- S1- 01
AO
START/STOP
STATUS
VLV- S1- 01
PRESSURE
HEAT DUM P VALVE
HD- 1
DO
DI
SYSTEM
SOLAR W ATER
AI
TEM PERATURE
SUPPLY
SOLAR W ATER
AI
TEM PERATURE
SOLAR W ATER
RETURN HW
RETURN
AI
AI
TEM PERATURE
HOT W ATER
SUPPLY
TEM PERATURE
HOT W ATER
AI
PRESSURE
AI
RETURN
HW P- 1B
AI
DI FF PRESS.
HW P- 1B
DI
PUM P STATUS
HW P- 1B
DO
START/STOP
HW P- 1A
AI
DI FF PRESS.
HW P- 1A
PUM P STATUS
HW P- 1A
DI
START/STOP
SW I TCH FLOW
BOI LER (B- 2)
OPEN- CLOSED
BOI LER (B- 2)
DO
DI
SHUT OFF VALVE
DO
STATUS
BOI LER (B- 2)
SHUT- OFF VALVE
DI
PERM I SSI ON
BOI LER(B- 2)
ON- OFF
DO
ALARM /STATUS
SUM M ARY
DI
SETPOI NT
BOI LER (B- 2)
AO
HOT W ATER SUPPLY
SW I TCH
BOI LER (B- 1)
FLOW
OPEN- CLOSED
BOI LER (B- 1)
DI
SHUT OFF VALVE
STATUS
BOI LER (B- 1)
DO
SHUT- OFF VALVE
DI
PERM I SSI ON
BOI LER(B- 1)
ON- OFF
ALL BOILERS AND PUMPS SHALL TURN OFF WHEN THE HWS TEMPERATURE IS >180F FOR [30] MINUTES [BAS] AND THE BOILER IS STAGED DOWN TO MINIMUM CAPACITY OR WHEN FAILURE ALARMS ARE REGISTERED (BAS AND BOILER CONTROLS)
DO
ALARM /STATUS
THE LAG BOILER AND ASSOCIATED PUMPS SHALL STAGE OFF WHENEVER THE BOILERS ARE LOADED LESS THAN 40% FOR LONGER THAN 20 MINUTES (ADJUSTABLE).
SUM M ARY
BOI LER (B- 1)
AFTER A CALL HAS BEEN MAINTAINED FOR [20] MINUTES, THE LAG BOILER AND PUMP SEQUENCE START AS DESCRIBED ABOVE FOR THE LEAD BOILER THE SECOND LAG BOILER WILL START UNDER THE SAME CONDITIONS AND SEQUENCES. WHENEVER A LAG BOILER STARTS, ALL RUNNING BOILERS LOAD AND UNLOAD AS NECESSARY TO BE RUNNING WITH 5% OF THE SAME % LOAD.
DI
SETPOI NT
AO
THERE IS NOT AUTOMATIC BOILER STAGING/SELECTION OPTIMIZATION CONTROLS. THE FIRST LAG BOILER WILL BE CALLED FOR WHENEVER THE HOT WATER STORAGE TANK HST-2 TEMPERATURE FALLS 5 DEG F BELOW THE HWS TEMPERATURE SETPOINT FOR MORE THAN 10 MINUTES (ADJUSTABLE).
HOT W ATER SUPPLY
C
PUM P STATUS
BOILER STAGING [ALL IN BAS]
BOILERS WILL NOT CYCLE ON AND OFF MORE THAN THREE TIMES IN A ONE HOUR PERIOD IF ANY SPACE TEMPERATURE SENSOR INDICATES A TEMPERATURE BELOW 50 DEG F DURING AN UNOCCUPIED SCHEDULE. THE HEATING WATER SYSTEM SHALL BE ALLOWED TO OPERATE NORMALLY TO MAINTAIN THE MINIMUM UNOCCUPIED TEMPERATURE SETPOINT. DIRECT DIGITAL CONTROLLER
ALARM ON BOILER FAILURE FAILURE ALARMS MUST BE MANUALLY RESET. SEE OTHER ALARM MODES IN BOILER OPERATOR’S MANUAL [ALARMS CREATED BY BOILER CONTROLS, SHUTDOWN BY BOILER CONTROLS, MESSAGE SENT TO BAS]
COMMUNICATION TRUNK
1
BOILERS LEAD/LAG OPERATION:
ARC- HEATING HOT WATER CONTROL SYSTEM DIAGRAM
TO NEXT DEVICE
N.T.S. 120 V POWER BY DIV. 26
EPO STATION
CONNECT TO
EPO SPECIFICATIONS
ON BREAKER SERVING B-1
EPO SHUTDOWN
TB
R
HEAVY DUTY 2-POSITION SELECTOR SWITCH
CONTROL WIRING SHALL BE #14
SQUARE D TYPE 9001K11J38LRH7
IN 3/4"C
EPO
N
1
TEMPERATURE BELOW 150F (ADJUSTABLE), THE LAG BOILER’S ISOLATION VALVE SHALL OPEN, THE LAG PUMP SHALL START, THE FLOW SHALL BE PROVEN, AND THE
ENABLE SWITCH
R
(OR APPROVED EQUIVALENT) Mark
ON FAILURE OF THE LEAD BOILER, THE LAG BOILER SHALL RUN AND THE LEAD BOILER SHALL TURN OFF. ON DECREASING HEATING HOT WATER SUPPLY
-MAINTAINED -ILLUMINATED (RED) -TWO (2) N.0. CONTACTS
EPO RELAY
-10 POLE (CONVERTIBLE CONTACTS) -120 VAC COIL -10A CONTACTS
IN THE EVENT THAT ADDITIONAL HEATING IS REQUIRED, THE LAG HEATING HOT WATER PRIMARY PUMP
-CLAMP TYPE TERMINALS R
SHALL BE COMMANDED TO START AND THE OPERATE IN SEQUENCE WITH THE LEAD AND LAG BOILER AND THE SECONDARY PUMP(S) 3
TO MAINTAIN THE BUILDING HEATING HOT WATER SETPOINT HHWST.
EPO ACTIVATION
4
4
EPO HORN/STROBE
ALARM
THE PRIMARY HHW PUMPS SHALL OPERATE CONTINUOUSLY WHEN THEIR ASSOCIATED BOILER IS RUNNING. PRIMARY HHW PUMPS SHALL
KELE #868STR, SURFACE MOUNT, OUTDOOR
PROVIDE CONSTANT FLOW THROUGH THE BOILER ACCORDING TO THE MANUFACTURER’S RECOMMENDATIONS. R DI
5
EPO
GAS SOLENOID
DDC/BAS
ASCO#8042, 2", GAS SOLENOID VALVE, NORMALLY CLOSED, 120V
ACTIVATION ALARM
PUMP OFF TIME DELAY
HUTTON CENTRE DRI VE,SUI TE 800
3
LOUI SVI LLE DI STRI CT
(OR APPROVED EQUIVALENT)
Desi gned by:
CUTLER HAMMER CAT. NO. AR10100A
THE LEAD PRIMARY PUMP HHWP STARTS UPON A CALL FOR HEATING. THE LEAD PRIMARY PUMP hHWP SHALL OPERATE IN SEQUENCE WITH THE LEAD BOILER AND SECONDARY PUMP(S) TO MAINTAIN THE BUILDING HEATING HOT WATER SETPOINT HHWST.
CORPS OF ENGI NEERS
INDUSTRIAL CONTROL RELAY R
EACH PRIMARY HEATING HOT WATER HHW PUMP IS ASSIGNED TO ONE BOILER [BAS].
U.S.ARMY
PRIMARY HEATING HOT WATER PUMPS HWP-1A AND 1B
A.REED
-120 VAC
C.KORPASH
-ONE (1) N.O. CONTACT TB
Ckd by:
-RED
MONTHLY
Dwn by:
-EXTENDED GUARD
ON BREAKER SERVING B-2
4
-MOMENTARY
I .FRANCO
5
WEEKLY
PUSHBUTTON
(OR APPROVED EQUIVALENT)
LOUI SVI LLE,KENTUCKY
SHUT TRIP CONNECTION POINTS
2
F-171-40-160
EPO
DAILY
Project Code:
R
Date:
SQUARE D CAT. NO. 9001KR2RH5
IF BOILER RUNTIME (ADJ) IS EXCEEDED
Revi ewed by:
HEAVY DUTY PUSHBUTTON OPERATOR
MANUALLY THROUGH A SOFTWARE SWITCH
A.REED
THE DESIGNATED LEAD BOILER SHALL ROTATE UPON ONE OF THE FOLLOWING CONDITIONS (USER SELECTABLE): 072811
B
W 912QR-11-R-0071
LAG BOILER SHALL STAGE ON AND RUN IN CONJUNCTION WITH THE LEAD BOILER TO MAINTAIN THE HEATING HOT WATER SETPOINT.
Sol i ci tati on No.
Rev.
-120 VAC
7/22/2011
R
Pl ot scal e:NONE
ENABLE
Pl ot date:
DISABLE
FAX (714) 327-1601
20A
3/4"C.
SHUT TRIP CONNECTION POINTS
2
EPO
TEL (714) 327-1600
WATER TEMPERATURE OF 180F. WHEN THE RETURN WATER TEMPERATURE DROPS TO [150F] (ADJUSTABLE), HEATING HOT WATER PUMP HWP-1B WILL START AND AFTER BEING PROVEN, WILL INITIATE THE STATUS OF BOILER B-2.
1
1 #12 GND,
Fi l e nam e:LCARC_M 8050. dgn
PANEL ________
2 #12,
M .BETZ
CIRCUIT IN
WHEN THE HOT WATER PUMP (HWP-1A) STATUS IS PROVEN, THE HOT WATER BOILER B-1 WILL BE PERMITTED TO START TO MAINTAIN THE SUPPLY
RELAY ENCLOSURE
Subm i tted by:
SPARE
SANTA ANA, CALI FORNI A 92707
THE TWO BOILERS SHALL OPERATE IN A LEAD/LAG FASHION WHEN CALLED TO RUN AND FLOW IS PROVEN. THE LEAD BOILERS SHALL RUN FIRST.
RESIDUAL HEAT AND PREVENT HIGH LIMIT ALARM.
2
ALARM ON PUMP FAILURE
EMERGENCY POWER OFF (EPO) WIRING DIAGRAM N.T.S.
SOLAR HEATING HOT WATER SYSTEM A DIFFERENTIAL TEMPERATURE CONTROLLER SHALL CALCULATE THE TEMPERATURE DIFFERENCE BETWEEN THE SOLAR COLLECTOR
A
TYPICAL FOR:
TEMPERATURE SENSOR AND THE STORAGE TANK WATER TEMPERATURE. THE CONTROLLER SHALL START THE SOLAR COLLECTOR LOOP AND
PLASTIC COVER
DISABLE
ENABLE
OMS MECHANICAL ROOM #B103
U.S.ARMY
(HINGED)
ARC MECHANICAL ROOM #A117
PUSH TO SHUTDOWN
HEAT DUMP, HD-1
CONTROLS
EPO STATION
MEXI CO
UPON FAILURE OF THE LEAD PUMP, THE LEAD BOILER SHALL SHUT DOWN, THE LAG PUMP SHALL BE INITIATED TO START, AND THE LAG BOILER SHALL START AUTOMATICALLY TO MEET THE LOAD. AN ALARM SHALL BE GENERATED BY THE BAS.
LAS CRUCES,NEW
RESERVE CENTER
HWP 1A AND 1B; ALARM ON PUMP FAILURE DETECTED VIA A MOTOR CURRENT SWITCH AND FLOW SWITCH.
7/22/2011
c:\pwworki ng\gbna\m oraja\dm s97636\LCARC_M-8050.dgn
WHENEVER THE BOILER IS DIABLED, THE CORRESPONDING PUMP SHALL CONINUE TO OPERATE FOR [5] MINUTES ADJ. TO DISAPATE
CIRCULATING PUMPS SHALL BE STARTED, IF AFTER 5 MINUTES THE TEMPERATURE IN THE SUPPLY WATER LINE IS STILL GREATER THAN
BE CYCLED ON. THE POSITION OF DIVERTING VALVE VLV-S01-1 SHALL BE MODULATED WITH A PID LOOP TO MAINTAIN A SUPPLY WATER EPO OPERATION
SHALL BE DISABLED. NAMEPLATE
TO DE-ENERGIZE NATURAL GAS BOILERS, PLACE SWITCH IN THE ENABLE POSITION AND THEN DEPRESS PUSHBUTTON.
SHEET REFERENCE NUMBER:
THE DIVERTING VALVE SHALL BE MODULATED TO DIVERT 100% OF THE FLOW THROUGH THE HEAT DUMP FLUID COOLER.
3
EMERGENCY POWER OFF (EPO) STATION
M-8050
N.T.S.
of 222
9:18:37
m oraja
AM
Sheet 149
1
2
*** Support Value Engineering - It Pays ***
4
5
CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11
1
*** Safety Pays ***
2
4
5
GENERAL NOTES A.
PI
FOR MECHANICAL ABBREVIATIONS, SYMBOLS, AND NOTES REFER TO DRAWING M-0010. FOR CONTROL ABBREVIATIONS, SYMBOLS,
US Army Corps of Engineers
AND NOTES REFER TO DRAWING M-8000.
LOUISVILLE DISTRICT
Appr.
PI TI CW MAKE-UP AND DHWR HWP
PT
HWP
Date
PT
4 2A DHWS TO DISTRIBUTION VFD
W/ CURRENT
PI
W/ CURRENT
SENSOR RELAY
R
TT
CT
SENSOR RELAY
PI PI
D
FI
PT
FT
HWP 2B
DOMESTIC HOT WATER STORAGE TANK
5
ZONES OR
FM
AIR-HANDLING UNIT COILS
HOT WATER HEAT EXCHANGER
HWS FROM HST-1 VFD
W/ CURRENT
HWP
PT HW SUPPLY TO HEATING
PT
SENSOR RELAY
CT
R
HWT
W/ CURRENT SENSOR RELAY
1
HX 1 FOR TRANSMITTER AND VALVE LOCATION SEE M-7000
DPT
Descri pti on
1
PI
PT
Mark
HWR TO HST-1
AI
DI
DO
AI
TEM PERATURE
W ATER TANK
DOM ESTI C HOT
HW P- 5
START/STOP
PUM P STATUS
HW P- 5
DI FF PRESS.
HW P- 5
HW P- 4
Date
AI
DI FF PRESS.
HW P- 4
PUM P STATUS
START/STOP
HW P- 4
CONTROL
DI FFERENTI AL VALVE
DI
Appr.
DO
AO
BLDG
DI FF PRESS
AI
PRESSURE
HW
SUPPLY
AI
(GPM )
HW S SECONDARY
AO
FLOW
HW P- 2B
AI
AO
DI FF PRESS.
DI
SPEED
DO
HW P- 2B
AO
HW P- 2B
DI
PUM P STATUS
DO
START/STOP
AI
HW P- 2B
HW P- 2A
AO
SPEED
HW P- 2A
PUM P STATUS
DI
START/STOP
HW P- 2A
DO
DI FF PRESS.
RETURN HW
PRESSURE
C
HW P- 2A
AI
AI
Descri pti on
DIRECT DIGITAL CONTROLLER
COMMUNICATION TRUNK
1
ARC- SECONDARY HEATING HOT WATER CONTROL SYSTEM DIAGRAM N.T.S. TO NEXT DEVICE
120 V POWER BY DIV. 26
SECONDARY HEATING HOT WATER PUMPS HWP-2A AND 2B
DOMESTIC HOT WATER HEAT EXCHANGER AND PUMPS HWP-4 AND 5
SOFTWARE LEAD/LAG FUNCTION SHALL BE PROVIDED TO ALLOW ANY OF THE SECONDARY PUMPS TO ACT AS THE LEAD PUMP [BAS] THE LEAD SECONDARY HW PUMP SHALL START BASED UPON A CALL FOR HEATING AS INDICATED UNDER THE BOILER CONTROL SEQUENCES. THE LEAD SECONDARY PUMP HWP SHALL OPERATE IN SEQUENCE WITH THE LEAD BOILER AND PRIMARY PUMP(S) TO MAINTAIN THE BUILDING HEATING WATER SETPOINT HW SUPPLY TEMPERATURE. IN THE EVENT THAT ADDITIONAL HEATING IS REQUIRED, THE LAG HEATING WATER SECONDARY PUMP SHALL BE COMMANDED TO START AND SHALL OPERATE IN SEQUENCE WITH THE LEAD AND LAG BOILER AND THE PRIMARY PUMP(S)
Mark
TO MAINTAIN THE BUILDING HEATING WATER SETPOINT HHWST.
7/22/2011
Pl ot scal e:NONE
F-171-40-160
Pl ot date:
M .BETZ
Subm i tted by:
LOW DIFFERENTIAL PRESSURE - THE MINIMUM PRESSURE LIMIT IS LESS THAN 10 PSI (ADJUSTABLE).
C.KORPASH
HIGH DIFFERENTIAL PRESSURE - THE MAXIMUM PRESSURE LIMIT IS GREATER THAN [18] PSI (ADJUSTABLE).
Ckd by:
ALARMS SHALL BE PROVIDED AS FOLLOWS:
Dwn by:
Desi gned by:
REQUIRED TO PROVIDE FULL FLOW TO ALL HEATING HOT WATER CONTROL VALVES. THE MINIMUM PRESSURE LIMIT IS THE PRESSURE CORRELATING TO THE LOWEST SPEED THE PUMP MOTOR IS ALLOWED TO BE OPERATED AT.
A.REED
THE REMOTE DP SETPOINT WILL BE MAINTAINED BETWEEN THE MAXIMUM AND MINIMUM PRESSURES. THE MAXIMUM PRESSURE LIMIT IS THE PRESSURE
I .FRANCO
THE RAISED PUMP DIFFERENTIAL (DISCHARGE) PRESSURE SETPOINT.
Project Code:
IS NOT BEING MET, A PID SIGNAL SHALL BE CALCULATED AND SENT TO THE PUMP DISCHARGE PRESSURE SETPOINT, AND IT SHALL BE RAISED ACCORDINGLY. THROUGH ANOTHER PI LOOP, THE VARIABLE SPEED (FREQUENCY) DRIVE (VFD) SHALL INCREASE THE PUMP MOTOR SPEED TO MEET
Revi ewed by:
Date:
A PID LOOP SHALL CHANGE THE SECONDARY PUMP DISCHARGE DIFFERENTIAL PRESSURE SETPOINT TO MAINTAIN THE REMOTE DP SETPOINT 072811
B
Sol i ci tati on No.
RISES BACK ABOE 16 PSI (ADJ), THE LAG PUMP SHALL TURN "OFF" AND THE LEAD PUMP SHALL MODULATE TO CONTROL THE DIFFERENTIAL PRESSURE CONTROL SETPOINT.
A.REED
Rev.
THE LEAD PUMP SHALL RUN FIRST TO MAINTAIN ITS DIFFERENTIAL PRESSURE SETPOINT (ADJUSTABLE). IF THE WATER DIFFERENTIAL PRESSURE DROPS BELOW 12 PSI (ADJUSTABLE, THE LAG PUMP SHALL START, THE LEAD PUMP SHALL RAMP DOWN WHILE THE LAG PUMP RAMPS UP AND THE PUMPS SHALL RUN IN UNISON. IF THE WATER DIFFERENTIAL PRESSURE
W 912QR-11-R-0071
THE HEATING WATER CONTROL VALVES SHALL BE POLLED EVERY [5] MINUTES (ADJUSTABLE).
Fi l e nam e:LCARC_M 8060. dgn
DIFFERENTIAL PRESSURE CONTROL [ALL BAS]
DURING REDUCING LOAD AS THE DP INCREASES: WHEN THE TOTAL SECONDARY HHW GPM HAS REDUCED TO BE EQUAL TO OR LESS THAN ONE PUMPS GPM FOR [10] MINUTES
FAX (714) 327-1601 TEL (714) 327-1600
HUTTON CENTRE DRI VE,SUI TE 800
U.S.ARMY
AS DIFFERENTIAL PRESSURE FALLS BELOW LOW LEVEL SETPOINT, AND THE LAG PUMP STARTS BOTH PUMPS SHALL CONVERGE AND RUN AT SIMILAR SPEEDS AND GPM TO MAINTAIN THE COMMON SUPPLY DISCHARGE PRESSURE DIFFERENTIAL SETPOINT AN REMOTE DP SETPOINTS.
SANTA ANA, CALI FORNI A 92707
PUMP STAGING [BAS]
4
THE DP RESET AND HHWST RESET COMPETE WITH EACH OTHER FOR CONTROL OF THE BUILDING. THE HHWST RESET SHALL NOT OCCUR UNLESS ALL THE
LOUI SVI LLE DI STRI CT
DIFFERENTIAL CONTROL AND HHWST RESET.
LOUI SVI LLE,KENTUCKY
CORPS OF ENGI NEERS
THE VFD INTERNAL SETTINGS WILL ALLOW THE VFD TO RUN THE PUMPS TO THEIR MINIMUM.
MONITORING THE CONTROLLER SHALL MONITOR RPM AND GPM OF THE PUMPS AND SHALL NOT ALL THE OPERATION OF THE PUMPS AT OR BEYOND THEIR PUBLISHED
UPON FAILURE OF THE LEAD SECONDARY PUMP VFD AND LEAD SECONDARY PUMP, THE LAG SECONDARY PUMP VFD SHALL INITIATE THE SECONDARY LAG PUMP TO START AUTOMATICALLY, AND AN ALARM SHALL BE GENERATED BY THE [BAS AND BOILER CONTROLLER]
A
ALARM FOR VFD FAILURE
U.S.ARMY
UPON FAILURE OF THE LEAD OR LAG VFD INITIATION, AN ALARM SHALL BE GENERATED BY THE BAS.
CONTROLS
HWP 2A AND 2B: ALARM ON PUMP FAILURE SHALL BE DETECTED VIA A CURRENT SENSING SWITCH AND FLOW SWITCH.
MEXI CO
ALARM FOR PUMP FAILURE
LAS CRUCES,NEW
RESERVE CENTER
"END OF CURVE" LIMIT [BAS]. UPON SENSING AN END OF CURVE CONDITION, VIA A PUMP CURVE EQUATION, THE NEXT PUMP SHALL BE STAGED ON.
7/22/2011
c:\pwworki ng\gbna\m oraja\dm s97636\LCARC_M-8060.dgn
(ADJUSTABLE), THE LAG HHW PUMP SHALL BE COMMANDED OFF.
SHEET REFERENCE NUMBER:
M-8060 of 222
9:19:07
m oraja
AM
Sheet 150
1
2
*** Support Value Engineering - It Pays ***
4
5
CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11
1
*** Safety Pays ***
2
4
5
GENERAL NOTES PI TI
A.
TT
FOR MECHANICAL ABBREVIATIONS, SYMBOLS, AND NOTES REFER TO DRAWING M-0010. FOR CONTROL ABBREVIATIONS, SYMBOLS, AND
PT
W/ CURRENT SENSOR RELAY
3-WAY VALVE
PI
CT
R
LOUISVILLE DISTRICT
NOTES REFER TO DRAWING M-8000.
6A
TI
TT
CIRCULATING PUMP
RADIANT HEAT, VALVE MANIFOLD
Appr.
HWP
US Army Corps of Engineers
TI
TT
Date
PT HWP PI
7A
WORKBAY TEMP
SLAB SENSOR
TS HWP
VFD
HST
PT
6B
SENSOR RELAY
D
PI
W/ CURRENT SENSOR RELAY
2 HOT WATER STORAGE TANK
W/ CURRENT
SOLAR COLLECTOR ARRAY
TT
PI
FI
PT
CT
R
SOLAR HOT WATER SYSTEM
FT
HWP
HEAT EXCHANGER AND
PT
7B
CONTROL PACKAGE
FM
VFD
W/ CURRENT SENSOR RELAY
PI HPAK DPT 1
PI
FOR LOCATION OF TRANSMITTER AND VALVE SEE M-7000
FS
BOILER
GFA
PANEL
B-4
TT
FM
TI
DO
DI
AO
DO
DI
AO
AI
AO
AI
AI
AO
AO
DO
AI
DI
AI
AI
1
SOLAR W ATER
TEM PERATURE
SOLAR W ATER
AI
DI
DI
DI
AI
RETURN
SLAB TEM PERATURE
ALARM
SLAB TEM PERATURE
W ORKBAY SPACE TEM P
PUM P START/STOP
DIRECT DIGITAL CONTROLLER
3- W AY RADI ANT VALVE
CONTROL
DI FFERENTI AL VALVE
BLDG
DI FF PRESS
PRESSURE
SUPPLY HW
(GPM )
HW S SECONDARY
FLOW
HW P- 7B DI FF PRESS.
HW P- 7B SPEED
HW P- 7B
PUM P STATUS
START/STOP
HW P- 7B
HW P- 7A
SPEED
HW P- 7A
PUM P STATUS
START/STOP
HW P- 7A
DI FF PRESS.
HW P- 7A
RETURN HW
PRESSURE
TEM PERATURE
HOT W ATER
SUPPLY
HW P- 6B
DI FF PRESS.
HW P- 6B
PUM P STATUS
START/STOP
HW P- 6B
HW P- 6A
DI FF PRESS.
HW P- 6A
PUM P STATUS
HW P- 6A
START/STOP
TEM PERATURE
RETURN
HOT W ATER
SW I TCH
BOI LER (B- 4)
FLOW
OPEN- CLOSED
BOI LER (B- 4)
SHUT OFF VALVE
STATUS
BOI LER (B- 4)
SHUT- OFF VALVE
PERM I SSI ON
BOI LER(B- 4)
ON- OFF
ALARM /STATUS
SUM M ARY
SETPOI NT
BOI LER (B- 4)
HOT W ATER SUPPLY
SW I TCH
BOI LER (B- 3)
FLOW
OPEN- CLOSED
BOI LER (B- 3)
SHUT OFF VALVE
STATUS
BOI LER (B- 3)
SHUT- OFF VALVE
PERM I SSI ON
BOI LER(B- 3)
ON- OFF
ALARM /STATUS
SUM M ARY
SETPOI NT
HOT W ATER SUPPLY
BOI LER (B- 3)
AI
COMMUNICATION TRUNK
Mark
AI
Appr.
AI
TO NEXT DEVICE 120 V POWER BY DIV. 26
Date
AI
AI
LOW
DI
TANK LVL LOW
DO
GLYCOL FI LL
AI
ASSEM BLY
DI
TANK LVL LOW
DO
GLYCOL FI LL
AI
ASSEM BLY
DI
STATUS ON/OFF
DO
ASSEM BLY
DI
GLYCOL FI LL
DO
SOLAR
DI
COLLECTOR
AO
TEM PERATURE
DI
PRESSURE
DO
SOLAR W ATER
DI
SYSTEM
DO
TT
TEM PERATURE
DI
2
SYSTEM CONTROL
TI
AO
PT
SOLAR HOT WATER
SUPPLY
B-3
TI
TI
Descri pti on
PT
FS
BOILER
1
OMS- HEATING HOT WATER CONTROL SYSTEM DIAGRAM N.T.S.
C
OVERVIEW
THE PREFERRED SEQUENCE OF HEATING HOT WATER STAGING MAY VARY BY SEASON. THE PRIMARY PUMPS AND RUN AT CONSTANT FLOW. THERE IS A SECONDARY HEATING HOT WATER SUPPLY LOOP WITH ALARM ON BOILER FAILURE
VARIABLE SPEED DRIVES ON THE PUMPS CONTROLLED FROM DIFFERENTIAL PRESSURE, WHICH IS RESET INCREMENTALLY TO OPERATE AT THE LOWEST SPPED AND PRESSURE POSSIBLE TO SATISTY THE CURRENT
FAILURE ALARMS MUST BE MANUALLY RESET. SEE OTHER ALARM MODES IN BOILER OPERATOR’S MANUAL [ALARMS CREATED BY BOILER CONTROLS, SHUTDOWN BY BOILER CONTROLS, MESSAGE SENT TO BAS]
LOAD.
A PID LOOP SHALL CHANGE THE SECONDARY PUMP DISCHARGE DIFFERENTIAL PRESSURE SETPOINT TO MAINTAIN THE REMOTE DP SETPOINT TO MAINTAIN THE MOST OPEN HEATING HOT WATER CONTROL VALVE AT 90% OPEN WITH A DEADBAND OF +/- 2%. WHEN THE LOCAL DP SETPOINT IS NOT BEING MET, A PID SIGNAL SHALL BE CALCULATED AND SENT TO THE PUMP DISCHARGE PRESSURE SETPOINT, AND IT SHALL BE RAISED ACCORDINGLY. THROUGH ANOTHER PI LOOP, THE VARIABLE SPEED (FREQUENCY) DRIVE (VFD) SHALL INCREASE THE PUMP MOTOR SPEED TO MEET THE RAISED PUMP DIFFERENTIAL (DISCHARGE) PRESSURE SETPOINT. Descri pti on
THE HEATING HOT WATER SYSTEM IS COMPRISED OF TWO BOILERS: (B-3, B-4).
THE REMOTE DP SETPOINT WILL BE MAINTAINED BETWEEN THE MAXIMUM AND MINIMUM PRESSURES. THE MAXIMUM PRESSURE LIMIT IS THE PRESSURE
THE SYSTEM STATUS WILL BE DETERMINED FROM THE HEATING HOT WATER SUPPLY TEMPERATURE COMPARED WITH THE SETPOINT AND THE OUTSIDE ARE TEMPERATURE IS LESS THAN [55F] (ADJUSTABLE).
BOILERS LEAD/LAG OPERATION:
TO PREVENT SHORT CYCLING, THE BOILER SYSTEM SHALL RUN FOR AND BE "OFF" FOR THE MINIMUM ADJUSTABLE TIMES
REQUIRED TO PROVIDE FULL FLOW TO ALL HEATING HOT WATER CONTROL VALVES. THE MINIMUM PRESSURE LIMIT IS THE PRESSURE CORRELATING TO THE LOWEST SPEED THE PUMP MOTOR IS ALLOWED TO BE OPERATED AT.
UNLESS SHUTDIWN ON SAFETIS OR OUTSDIE AIR CONDITIONS. THE TWO BOILERS SHALL OPERATE IN A LEAD/LAG FASHION WHEN CALLED TO RUN AND FLOW IS PROVEN. THE LEAD BOILERS SHALL RUN FIRST. WHEN THE HOT WATER PUMP (HWP-6A) STATUS IS PROVEN, THE HOT WATER BOILER B-3 WILL BE PERMITTED TO START TO MAINTAIN THE SUPPLY
THE BOILER SHALL RUN SUBJECT TO ITS OWN INTERNAL SAFETIES AND CONTROLS.
WATER TEMPERATURE OF 180 DEG F. WHEN THE RETURN WATER TEMPERATURE DROPS TO [150 DEG F] (ADJUSTABLE), HEATING HOT WATER PUMP HWP-6B WILL START AND AFTER
ALARMS SHALL BE PROVIDED AS FOLLOWS:
BEING PROVEN, WILL INITIATE THE STAUTS OF BOILER B-4. BOILER SEQUENCING
HIGH DIFFERENTIAL PRESSURE - THE MAXIMUM PRESSURE LIMIT IS GREATER THAN [18] PSI (ADJUSTABLE). ON FAILURE OF THE LEAD BOILER, THE LAG BOILER SHALL RUN AND THE LEAD BOILER SHALL TURN OFF. ON DECREASING HEATING HOT WATER SUPPLY TEMPERATURE BELOW 150 DEG F
SOFTWARE [BAS] LEAD LAG SELECTOR SHALL BE PROVIDED TO ALLOW ANY OF THE BOILERS TO ACT AS THE LEAD MACHINE.
(ADJUSTABLE), THE LAG BOILER’S ISOLATION VALVE SHALL OPEN. THE LAG PUMP SHALL START. THE FLOW SHALL BE PROVEN, AND THE LAG BOILER SHALL STAGE ON AND RUN IN
LOW DIFFERENTIAL PRESSURE - THE MINIMUM PRESSURE LIMIT IS LESS THAN 10 PSI (ADJUSTABLE). THE VFD INTERNAL SETTINGS WILL ALLOW THE VFD TO RUN THE PUMPS TO THEIR MINIMUM.
CONJUNCTION WITH THE LEAD BOILER TO MAINTAIN THE HEATING HOT WATER SETPOINT. THE BOILER WILL ONLY BE ENABLED TO OPERATE IN AUTO UPON THE FOLLOWING CONDIITONS: 1. BOILER SCHEDULE ON [BY BAS]
DIFFERENTIAL CONTROL AND HHWST RESET. THE DESIGNATED LEAD BOILER SHALL ROTATE UPON ONE OF THE FOLLOWING CONDITIONS (USER SELECTABLE):
WEEKLY
Mark
UNTIL THE PRESSURE RESET IS AT ITS MINIMUM).
THE PRIMARY HHW PUMPS SHALL OPERATE CONTINUOUSLY WHEN THEIR ASSOCIATED BOILER IS RUNNING. PRIMARY HHW PUMPS SHALL
"END OF CURVE" LIMIT [BAS]. UPON SENSING AN END OF CURVE CONDITION, VIA A PUMP CURVE EQUATION, THE NEXT PUMP SHALL BE STAGED ON.
PROVIDE CONSTANT FLOW THROUGH THE BOILER ACCORDING TO THE MANUFACTURER’S RECOMMENDATIONS. BOILER-HOT WATER SUPPLY TEMPERATURE SETPOINT RESET THE HOT WATER SUPPLY (HWS) TEMPERATURE SHALL BE RESET BASED ON OUTSIDE AIR TEMPERATURE.
ALARM FOR PUMP FAILURE HWP 7A AND 7B: ALARM ON PUMP FAILURE SHALL BE DETECTED VIA A CURRENT SENSING SWITCH AND FLOW SWITCH.
PUMP OFF TIME DELAY
ALARMS SHALL BE PROVIDED AS FOLLOWS:
WHENEVER THE BOILER IS DIABLED, THE CORRESPONDING PUMP SHALL CONINUE TO OPERATE FOR [5] MINUTES ADJ. TO DISAPATE
UPON FAILURE OF THE LEAD SECONDARY PUMP VFD AND LEAD SECONDARY PUMP, THE LAG SECONDARY PUMP VFD SHALL INITIATE THE SECONDARY LAG PUMP TO START AUTOMATICALLY, AND AN ALARM SHALL BE GENERATED BY THE [BAS AND BOILER CONTROLLER]
RESIDUAL HEAT AND PREVENT HIGH LIMIT ALARM.
SOFTWARE LEAD/LAG FUNCTION SHALL BE PROVIDED TO ALLOW ANY OF THE SECONDARY PUMPS TO ACT AS THE LEAD PUMP [BAS]
A DIFFERENTIAL TEMPERATURE CONTROLLER SHALL CALCULATE THE TEMPERATURE DIFFERENCE BETWEEN THE SOLAR COLLECTOR TEMPERATURE SENSOR AND THE STORAGE TANK WATER TEMPERATURE. THE CONTROLLER SHALL START THE SOLAR COLLECTOR LOOP AND STORAGE LOOP
THE LEAD SECONDARY HW PUMP SHALL START BASED UPON A CALL FOR HEATING AS INDICATED UNDER THE BOILER CONTROL SEQUENCES. THE LEAD SECONDARY PUMP HWP SHALL OPERATE IN SEQUENCE WITH THE LEAD BOILER AND PRIMARY PUMP(S)
ADJUSTABLE.
TO MAINTAIN THE BUILDING HEATING WATER SETPOINT HW SUPPLY TEMPERATURE.
ALL BOILERS AND PUMPS SHALL TURN OFF WHEN THE OSAT IS >75F FOR [30] MINUTES [BAS] OR WHEN ALL
IN THE EVENT THAT ADDITIONAL HEATING IS REQUIRED, THE LAG HEATING WATER SECONDARY PUMP
UNDERSAB RADIANT HEATING HOT WATER SYSTEM
THE OSAT IS >75F FOR [30] MINUTES [BAS] SHALL BE COMMANDED TO START AND SHALL OPERATE IN SEQUENCE WITH THE LEAD AND LAG BOILER AND THE PRIMARY PUMP(S)
CIRCULATING PUMP SHALL BE ENABLED AND ACTIVE WITH SPACE TEMPERATURE BETWEEN 67F AND 75F. SPACE TEMPERATURE SENSOR SHALL MODULATE THE 3-WAY VALVE TO MAINTAIN 68FTO 72F(ADJUSTABLE) WITHIN THE WORK BAYS. SUPPLY WATER TEMPERATURE SHALL BE 101F TO 102F TO THE MANIFOLD, RETURN WATER TEMPERATURE SHALL BE 81F T0 82F. IF SLAB TEMPERATURE RISES TO 84F AN ALARM WILL APPEAR AT THE BAS. IF SLAB TEMPERATURE RISES TO 86F, THEN PUMP WILL STOP AND VALVE SHALL RECIRCULATE THE RETURN WATER.
TO MAINTAIN THE BUILDING HEATING WATER SETPOINT HHWST. OR WHEN AN UNOCCUPIED SCHEDULE OCCURS. IF ANY SPACE TEMPERATURE SENSOR INDICATES A TEMPERATURE BELOW 50 DEG F DURING AN UNOCCUPIED SCHEDULE. THE HEATING WATER SYSTEM SHALL BE ALLOWED TO OPERATE NORMALLY TO MAINTAIN THE MINIMUM UNOCCUPIED TEMPERATURE SETPOINT. OR
DIFFERENTIAL PRESSURE CONTROL [ALL BAS]
7/22/2011
Pl ot scal e:NONE
Pl ot date:
MEXI CO
SOLAR HEATING HOT WATER SYSTEM
SECONDARY HEATING HOT WATER PUMPS HWP-7A AND 7B
CONTROLS
A
UPON FAILURE OF THE LEAD OR LAG VFD INITIATION, AN ALARM SHALL BE GENERATED BY THE BAS.
BOILER SHALL START AUTOMATICALLY TO MEET THE LOAD. AN ALARM SHALL BE GENERATED BY THE BAS.
LAS CRUCES,NEW
THE LAG BOILER AND ASSOCIATED PUMPS SHALL STAGE OFF WHENEVER THE BOILERS ARE LOADED LESS THAN 40% FOR LONGER THAN 20 MINUTES (ADJUSTABLE).
UPON FAILURE OF THE LEAD PUMP, THE LEAD BOILER SHALL SHUT DOWN, THE LAG PUMP SHALL BE INITIATED TO START, AND THE LAG
RESERVE CENTER
AFTER A CALL HAS BEEN MAINTAINED FOR [20] MINUTES, THE LAG BOILER AND PUMP SEQUENCE START AS DESCRIBED ABOVE FOR THE LEAD BOILER THE SECOND LAG BOILER WILL START UNDER THE SAME CONDITIONS AND SEQUENCES. WHENEVER A LAG BOILER STARTS, ALL RUNNING BOILERS LOAD AND UNLOAD AS NECESSARY TO BE RUNNING WITH 5% OF THE SAME % LOAD.
ALARM FOR VFD FAILURE
U.S.ARMY
THERE IS NOT AUTOMATIC BOILER STAGING/SELECTION OPTIMIZATION CONTROLS. THE FIRST BOILER WILL BE CALLED FOR WHENEVER THE HOT WATER STORAGE TANK HST-2 TEMPERATURE FALLS 5 DEG F BELOW THE HWS TEMPERATURE SETPOINT FOR MORE THAN 10 MINUTES (ADJUSTABLE).
OR
Fi l e nam e:LCARC_M 8080. dgn
ALARM ON PUMP FAILURE HWP-6A AND 6B; ALARM ON PUMP FAILURE DETECTED VIA A MOTOR CURRENT SWITCH AND FLOW SWITCH.
7/22/2011
c:\pwworki ng\gbna\m oraja\dm s97636\LCARC_M-8070.dgn
BOILER STAGING [ALL IN BAS]
FAX (714) 327-1601
THE CONTROLLER SHALL MONITOR RPM AND GPM OF THE PUMPS AND SHALL NOT ALL THE OPERATION OF THE PUMPS AT OR BEYOND THEIR PUBLISHED
SCHEDULE, BY MODULATING THE BOILER CAPACITY.
TEL (714) 327-1600
MONITORING
THE BOILER MAINTAINS THE HHW SUPPLY TEMPERATURE AT THE SETPOINT[BAS] WHICH RANGES FROM 175F TO 180F, BASED ON A RESET
LOUI SVI LLE DI STRI CT
TO MAINTAIN THE BUILDING HEATING HOT WATER SETPOINT HHWST.
Desi gned by:
SHALL BE COMMANDED TO START AND THE OPERATE IN SEQUENCE WITH THE LEAD AND LAG BOILER AND THE SECONDARY PUMP(S)
A.REED
IN THE EVENT THAT ADDITIONAL HEATING IS REQUIRED, THE LAG HEATING HOT WATER PRIMARY PUMP
CORPS OF ENGI NEERS
THE LEAD SECONDARY PUMP HWP THEN STARTS, RAMPING UP FROM THE MINIMUM SPEED OF 20 Hz VIA THE VARIABLE FREQUENCY DRIVE.
WHEN THE TOTAL SECONDARY HHW GPM HAS REDUCED TO BE EQUAL TO OR LESS THAN ONE PUMPS GPM FOR [10] MINUTES (ADJUSTABLE), THE LAG HHW PUMP SHALL BE COMMANDED OFF.
M .BETZ
DURING REDUCING LOAD AS THE DP INCREASES:
THERE SHALL BE [30-60] SECOND DELAYS BETWEEN THESE PUMPS, PER THE BOILER INTEGRAL PROGRAMMED SETTINGS (ADJUSTABLE)
Subm i tted by:
TO MAINTAIN THE BUILDING HEATING HOT WATER SETPOINT HHWST.
HUTTON CENTRE DRI VE,SUI TE 800
THE LEAD PRIMARY PUMP hHWP SHALL OPERATE IN SEQUENCE WITH THE LEAD BOILER AND SECONDARY PUMP(S)
SANTA ANA, CALI FORNI A 92707
Date:
THE LEAD PRIMARY PUMP HHWP STARTS UPON A CALL FOR HEATING.
CONFIRMED ON VIA A CURRENT SENSOR IN THE BAS AND THE FLOW IS CONFIRMED THROUGH A FLOW SWITCH.
U.S.ARMY
THEN THE ASSIGNED LEAD BOILER PUMP STARTS, THE PUMP STATUS IS
072811
EACH PRIMARY HEATING HOT WATER HHW PUMP IS ASSIGNED TO ONE BOILER [BAS].
4
IS CONFRIMED THROUGH A FLOW SWITCH.
B
F-171-40-160
THE LEAD PRIMARY (HWP-6A) PUMP STARTS, THE PUMP STATUS IS CONFIRMED VIA A CURRENT SENSOR IN THE BAS AND THE FLOW
Project Code:
PRIMARY HEATING HOT WATER PUMPS HWP-6A AND 6B
Revi ewed by:
AS DIFFERENTIAL PRESSURE FALLS BELOW LOW LEVEL SETPOINT, AND THE LAG PUMP STARTS BOTH PUMPS SHALL CONVERGE AND RUN AT SIMILAR SPEEDS AND GPM TO MAINTAIN THE COMMON SUPPLY DISCHARGE PRESSURE DIFFERENTIAL SETPOINT AN REMOTE DP SETPOINTS.
OPEN THE CONTROL VALVE
A.REED
MONTHLY
W 912QR-11-R-0071
PUMP STAGING [BAS]
UPON A CALL FOR HEATING:
Sol i ci tati on No.
DAILY
C.KORPASH
5. THE HEATING HOT WATER FLOWS ARE VERIFIED [BAS AND BOILER PANEL]
Ckd by:
IF BOILER RUNTIME (ADJ) IS EXCEEDED
Dwn by:
4. THERE IS A CALL FOR HEATING [BAS]
THE DP RESET AND HWST RESET COMPETE WITH EACH OTHER FOR CONTROL OF THE BUILDING. THE HHWST RESET SHALL NOT OCCUR UNLESS ALL THE
I .FRANCO
MANUALLY THROUGH A SOFTWARE SWITCH
LOUI SVI LLE,KENTUCKY
3. THERE ARE NOT ACTIVE ALARMS THAT INITIATE A SHUTDOWN (REPORTED TO BAS AND BOILER PANEL)
Rev.
2. OSAT<56F[BAS] (SHUT BACK OFF AT OSAT>54F
THE HEATING WATER CONTROL VALVES SHALL BE POLLED EVERY [5] MINUTES (ADJUSTABLE). WHEN FAILURE ALARMS ARE REGISTERED (BAS AND BOILER CONTROLS)
OR
WHEN THE SOLAR COLLECTORS ARE ABLE TO MAINTAIN THE DESIRED HWS TEMPERATURE AS INDICATED BY THE BOILER OPERATING AT MINIMUM LOAD AND THE HWS TEMPERATURE 5 DEG F GREATER THAN THE HWS TEMPERATURE SETPOINT FOR LONGER THAN 20 MINUTES (ADJUSTABLE).
SHEET REFERENCE NUMBER:
THE LEAD PUMP SHALL RUN FIRST TO MAINTAIN ITS DIFFERENTIAL PRESSURE SETPOINT (ADJUSTABLE). IF THE WATER DIFFERENTIAL PRESSURE DROPS BELOW 12 PSI (ADJUSTABLE, THE LAG PUMP SHALL START, THE LEAD PUMP SHALL RAMP DOWN WHILE THE LAG PUMP RAMPS UP AND THE PUMPS SHALL RUN IN UNISON. IF THE WATER DIFFERENTIAL PRESSURE RISES BACK ABOE 16 PSI (ADJ), THE LAG PUMP SHALL TURN "OFF" AND THE LEAD PUMP SHALL MODULATE TO CONTROL THE DIFFERENTIAL PRESSURE CONTROL SETPOINT.
M-8070
BOILERS WILL NOT CYCLE ON AND OFF MORE THAN THREE TIMES IN A ONE HOUR PERIOD
9:19:36 AM
m oraja
Sheet 151
1
2
*** Support Value Engineering - It Pays ***
4
5
of 222
CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11
9:20:10 AM
m oraja
c:\pwworki ng\gbna\m oraja\dm s97636\LCARC_M-8080.dgn
1
A
2
*** Support Value Engineering - It Pays *** 4 5 Sheet 152
HUTTON CENTRE DRI VE,SUI TE 800
FAX (714) 327-1601
SANTA ANA, CALI FORNI A 92707 TEL (714) 327-1600
4
C.KORPASH
M .BETZ
Subm i tted by:
A.REED
Revi ewed by:
Ckd by:
Dwn by:
Rev.
7/22/2011 Pl ot scal e:NONE
Pl ot date:
Fi l e nam e:LCARC_M 8080. dgn
F-171-40-160
Project Code:
W 912QR-11-R-0071
Sol i ci tati on No.
B
I .FRANCO
Date: 072811
Mark
Descri pti on
Date
Appr.
Mark
Descri pti on
1
LOUI SVI LLE,KENTUCKY
Desi gned by:
D Date
Appr.
FOR MECHANICAL ABBREVIATIONS, SYMBOLS, AND NOTES REFER
A.REED
A.
CONTROLS
CORPS OF ENGI NEERS
4
LOUI SVI LLE DI STRI CT
U.S.ARMY
*** Safety Pays ***
MEXI CO
RESERVE CENTER
2
LAS CRUCES,NEW
U.S.ARMY
7/22/2011
1 5
GENERAL NOTES TO DRAWING M-0010. FOR CONTROL ABBREVIATIONS, SYMBOLS,
US Army Corps of Engineers
AND NOTES REFER TO DRAWING M-8000. LOUISVILLE DISTRICT
KEY NOTES LISTED ALARM LIMITS ARE INITIAL SETTINGS ONLY AND
SHALL BE USER ADJUSTABLE. ACTUAL ALARM LIMITS MAY
DIFFER DEPENDING ON ACTUAL OPERATING CONDITIONS.
C
SHEET REFERENCE NUMBER:
M-8080 of 222
CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11
9:20:35
m oraja AM
c:\pwworki ng\gbna\m oraja\dm s97636\LCARC_M-8090.dgn
1
A
2
*** Support Value Engineering - It Pays *** 4 5 Sheet 153
HUTTON CENTRE DRI VE,SUI TE 800
FAX (714) 327-1601
SANTA ANA, CALI FORNI A 92707 TEL (714) 327-1600
4
C.KORPASH
M .BETZ
Subm i tted by:
A.REED
Revi ewed by:
Ckd by:
Dwn by:
Rev.
7/22/2011 Pl ot scal e:NONE
Pl ot date:
Fi l e nam e:LCARC_M 8090. dgn
F-171-40-160
Project Code:
W 912QR-11-R-0071
Sol i ci tati on No.
B
I .FRANCO
Date:
Mark
Descri pti on
Date
Appr.
Mark
Descri pti on
2
072811
1
LOUI SVI LLE,KENTUCKY
Desi gned by:
D Date
Appr.
FOR MECHANICAL ABBREVIATIONS, SYMBOLS, AND NOTES REFER
A.REED
A.
CONTROLS
CORPS OF ENGI NEERS
4
LOUI SVI LLE DI STRI CT
U.S.ARMY
*** Safety Pays ***
MEXI CO
RESERVE CENTER
2
LAS CRUCES,NEW
U.S.ARMY
7/22/2011
1 5
GENERAL NOTES TO DRAWING M-0010. FOR CONTROL ABBREVIATIONS, SYMBOLS,
US Army Corps of Engineers
AND NOTES REFER TO DRAWING M-8000. LOUISVILLE DISTRICT
KEY NOTES LISTED ALARM LIMITS ARE INITIAL SETTINGS ONLY AND
SHALL BE USER ADJUSTABLE. ACTUAL ALARM LIMITS MAY
DIFFER DEPENDING ON ACTUAL OPERATING CONDITIONS.
PART OF UNIT FACTORY CONTROL PANEL.
C
SHEET REFERENCE NUMBER:
M-8090 of 222
CERTIFIED FINAL SUBMITTAL (RTA) - 07-28-11
6
5
4
3
2
1
Dewberry Architects Inc.
SYMBOL
DESCRIPTION
-CEILING DIFFUSER, ROUND NECK (CEILING DIFFUSERS ARE 4-WAY THROW UNO)
F
SYMBOL
DESCRIPTION -TERMINAL UNIT, VARIABLE/CONSTANT AIR VOLUME WITH ELECTRIC HEAT
-FIRE DAMPER (WITH ACCESS PANEL)
-TERMINAL UNIT, VARIABLE/CONSTANT AIR VOLUME WITH ELECTRIC HEAT
-FIRE & SMOKE DAMPER (WITH ACCESS PANEL)
-ROUND DIFFUSER -CEILING RETURN
-EXISTING FIRE DAMPER TO REMAIN
-CEILING EXHAUST
-TERMINAL UNIT, VARIABLE/CONSTANT AIR VOLUME, FAN POWERED
-EXISTING FIRE & SMOKE DAMPER TO REMAIN -CEILING DIFFUSER, RECTANGULAR OR SQUARE NECK (CEILING DIFFUSERS ARE 4-WAY THROW UNO)
SA-1
-SOUND ATTENUATOR
-SUPPLY REGISTER OR GRILLE (VERTICAL MOUNT, SIDEWALL)
-TERMINAL UNIT, VARIABLE/CONSTANT AIR VOLUME, FAN POWERED, WITH ELECTRIC HEAT
-MOTOR OPERATED CONTROL DAMPER (MOD) M
-RETURN/EXHAUST REGISTER OR GRILLE (VERTICAL MOUNT, SIDEWALL)
-ELECTRIC DUCT HEATER (W/ PANEL CLEARANCE) -AIR FLOW MEASURING STATION
FM
-REVISION REFERENCE
1
-MANUAL BALANCING DAMPER
-DETAIL REFERENCE: TOP-DETAIL#, BOTTOM-DRAWING# SHOWN ON
T
-THERMOSTAT/TEMPERATURE SENSOR
H
-HUMIDISTAT/HUMIDITY SENSOR -DUCT SMOKE DETECTOR
E
-HYDRONIC REHEAT COIL
-DOOR GRILLE
UC
1 M-1
-INLINE CENTRIFUGAL FAN
-UNDERCUT DOOR
-CONNECT TO EXISTING -PACKAGED TERMINAL AIR CONDITIONER (PTAC)
-ACCESS DOORS, VERTICAL OR HORIZONTAL -DEMOLISH TO POINT INDICATED -MOTORIZED CONTROL DAMPER
M TS
-TEMPERATURE SENSOR
P
-PRESSURE SENSOR
-STAINLESS STEEL DUCTWORK
UP
DN -CHANGE OF ELEVATION
-FLEXIBLE CONNECTION -FLEXIBLE DUCT 12x8
-BACKDRAFT DAMPER
BD
-FLAT OVAL DUCT -TRANSITION, CONCENTRIC
-NEUTRAL RELATIVE PRESSURE
0
24x12
-NEW DUCTWORK, FIRST DIMENSION IS SIDE SHOWN
-POSITIVE RELATIVE PRESSURE
+ _
-NEGATIVE RELATIVE PRESSURE
24x12
-EXISTING DUCTWORK TO REMAIN
1
-SHEET NOTE CALLOUT
24x12
-EXISTING DUCTWORK TO BE REMOVED
-SHEET NOTE CALLOUT
SYMBOL
DESCRIPTION 1. CONNECTION TO EQUIPMENT SHALL BE VERIFIED WITH MANUFACTURER'S CERTIFIED DRAWINGS. TRANSITIONS TO ALL EQUIPMENT SHALL BE VERIFIED AND PROVIDED FOR EQUIPMENT FURNISHED.
AFD
-ADJUSTABLE FREQUENCY DRIVE
LD
-LINEAR DIFFUSER
AFF
-ABOVE FINISHED FLOOR
MBH
-THOUSAND BTUs PER HOUR
AFR
-ABOVE FINISHED ROOF
MCA
-MINIMUM CIRCUIT AMPS
AHU
-AIR HANDLING UNIT
MOCP
-MAXIMUM OVER CURRENT PROTECTION
AP
-ACCESS PANEL
MOD
-MOTOR OPERATED CONTROL DAMPER (MOD)
BOP
-BOTTOM OF PIPE
NC
-NORMALLY CLOSED
BHP
-BRAKE HORSEPOWER
NO
-NORMALLY OPEN
BTU
-BRITISH THERMAL UNIT
NTS
-NOT TO SCALE
h
-CENTER LINE
OA
-OUTSIDE AIR
c
-CFM (CUBIC FEET PER MINUTE)
OAL
-OUTSIDE AIR LOUVER
CD
-CEILING DIFFUSER
PRV
-PRESSURE REDUCING VALVE
CT
-COOLING TOWER
PRS
-PRESSURE REDUCING STATION
CV
-CONSTANT AIR VOLUME
PSI
-POUNDS PER SQUARE INCH
P
-CHANGE IN PRESSURE
PSIG
-PSI GAUGE
T
-CHANGE IN TEMPERATURE
PTAC
-PACKAGED TERMINAL AIR CONDITIONER
CFM
-CUBIC FEET PER MINUTE
PVC
-POLYVINYL CHLORIDE PIPE
CU
-CONDENSING UNIT
RA
-RETURN AIR
DDC
-DIRECT DIGITAL CONTROLS
RHC
-REHEAT COIL
DN
-DOWN
RHP
-ROOFTOP HEAT PUMP
EAT
-ENTERING AIR TEMPERATURE
RPM
-REVOLUTIONS PER MINUTE
ESP
-EXTERNAL STATIC PRESSURE
RS/L
-REFRIGERANT SUCTION & LIQUID LINES
EWT
-ENTERING WATER TEMPERATURE
RTU
-ROOFTOP AIR HANDLING UNIT
FCU
-FAN COIL UNIT
SA
-SUPPLY AIR
FD
-FIRE DAMPER
SP
-STATIC PRESSURE
FF
-FINAL FILTERS
TSP
-TOTAL STATIC PRESSURE
FLA
-FULL LOAD AMPS
UNO
-UNLESS NOTED OTHERWISE
FPM
-FEET PER MINUTE
V/PH
-VOLTS/PHASE
GPM
-GALLONS PER MINUTE
VAV
-VARIABLE AIR VOLUME
KW
-KILOWATT
VFD
-VARIABLE FREQUENCY DRIVE
LAT
-LEAVING AIR TEMPERATURE
LWT
-LEAVING WATER TEMPERATURE
2. DIMENSIONS SHALL BE FIELD-VERIFIED AND COORDINATED PRIOR TO PROCUREMENT OR FABRICATION. COORDINATE THE WORK WITH OTHER TRADES INVOLVED. FIELD MODIFICATIONS SUCH AS OFFSETS IN PIPING OR DUCTWORK (INCLUDING DIVIDED DUCTWORK) NEEDED DUE TO OBSTRUCTIONS OR INTERFERENCES SHALL BE PROVIDED AT NO ADDITIONAL COST. FOR PROJECTS INVOLVING RENOVATION, COORDINATE NEW WORK WITH EXISTING ELEMENTS SUCH AS THE BUILDING STRUCTURE AND ARCHITECTURAL FEATURES, SPRINKLER PIPING, LIGHTS, PLUMBING, AND ELECTRICAL CONDUIT. 3. DUCT CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE SMACNA HVAC DUCT CONSTRUCTION STANDARD. 4. SEE SPECIFICATIONS FOR GAUGES, THICKNESS, BRACING, REQUIREMENTS, ETC., OF DUCTWORK. 5. PROVIDE AIR TURNING VANES IN ALL 90 DEGREE RECTANGULAR DUCT ELBOWS. 6. DUCT SIZES AND ALL OPENINGS THROUGH BUILDING CONSTRUCTION SHALL SUIT EQUIPMENT FURNISHED. 7. COORDINATE DIFFUSER, GRILLE AND REGISTER LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLANS AND EQUIPMENT OF ALL TRADES. 8. LOCATE THERMOSTATS, TEMPERATURE SENSORS, HUMIDISTATS, AND HUMIDITY SENSORS AT 48" ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE. COORDINATE LOCATIONS WITH OTHER EQUIPMENT, FURNITURE, AND DOOR SWINGS. 9. ALL EQUIPMENT, DUCTWORK, ETC., SHALL BE SUPPORTED AS DETAILED AND/OR SPECIFIED. PROVIDE ADDITIONAL SUPPORTS AS REQUIRED TO PROVIDE A VIBRATION-FREE, RIGID INSTALLATION. 10. ALL DUCT SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS. 11. DAMPERS AND INSIDES OF DUCTS VISIBLE THROUGH GRILLES, REGISTERS AND DIFFUSERS SHALL BE PAINTED FLAT BLACK. 12. REFER TO TYPICAL DETAILS FOR PIPING AND INSTALLATION OF EQUIPMENT. 13. TRAPPED CONDENSATE DRAINS FROM ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED FOR PROPER DRAINAGE TO SUIT EQUIPMENT FURNISHED. 14. ACCESS PANELS IN DUCTWORK AND CEILINGS SHALL BE PROVIDED WHERE REQUIRED FOR OPERATION, BALANCING OR MAINTENANCE OF ALL MECHANICAL EQUIPMENT. 15. ALL DUCTWORK AND PIPING IS SHOWN SCHEMATICALLY. PROVIDE ALL TRANSITIONS, TURNING VANES, ELBOWS, FITTINGS, ETC., TO ALLOW SMOOTH FLOWS. ALL SPLIT DUCT FITTINGS SHALL TRANSITION TO FULL SIZE OF THE SUM OF BOTH BRANCHES, UPSTREAM OF SPLIT. 16. PROVIDE CONCRETE HOUSEKEEPING PAD UNDER ALL FLOOR-MOUNTED EQUIPMENT. REFER TO SPECIFICATIONS FOR DETAILED REQUIREMENTS. 17. VERIFY FINISH WITH ARCHITECT PRIOR TO PURCHASING GRILLES, REGISTERS, DIFFUSERS, LOUVERS AND OTHER AIR DISTRIBUTION DEVICES. 18. PROVIDE FLEXIBLE DUCT CONNECTIONS ON ALL DUCTWORK CONNECTING TO EACH FAN, AIR HANDLING UNITS, AND FAN COIL UNITS.
-TRANSITION, SQUARE TO ROUND
10x8
-DUCT ELBOW, POSITIVE PRESSURE (SUPPLY), FIRST
1
DESCRIPTION
24x12
-SHEET NOTE CALLOUT
1
-TRANSITION, ECCENTRIC
SYMBOL
UP W/IN FLOOR
DOWN
-CEILING MOUNTED ACCESS DOOR
19. PROVIDE TRANSITIONS AT DIFFUSER NECKS AS REQUIRED TO MATCH SIZES OF FLEX DUCTS TO BE CONNECTED.
-SQUARE THROAT TEE
DIMENSION INDICATES SIDE TO WHICH ARROW IS POINTING
20. INTERRUPTIONS TO EXISTING SERVICES SHALL BE SCHEDULED FOR TIMES OTHER THAN NORMAL OPERATING HOURS (SUCH AS NIGHTS AND WEEKENDS). SUCH INTERRUPTIONS TO SERVICES SHALL NOT BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER'S REPRESENTATIVE AND PROPER COORDINATION WITH OTHER TRADES. PRE-WORK SHALL BE PERFORMED TO MAKE THE SHUTDOWN PERIOD AS BRIEF AS POSSIBLE.
-DUCT ELBOW, EXHAUST -DUCT ELBOW, NEGATIVE PRESSURE, RETURN
-RADIUS TEE
12x8
21. ALL EQUIPMENT, DUCTWORK, ETC., TO BE REMOVED SHALL REMAIN PROPERTY OF THE OWNER OR DISPOSED OF LEGALLY, AS DIRECTED BY OWNER.
-DUCT ELBOW UP THROUGH ROOF OR SLAB ABOVE
D
401 SW Water St. Suite 701 Peoria, IL 61602 309.282.8000 Phone 309.282.8001 Fax
-RECTANGULAR DUCT SECTION UP, POSITIVE PRESSURE, SUPPLY OR OUTSIDE AIR
22. MAINTAIN CLEARANCE OF A MINIMUM OF 6" BETWEEN DUCTWORK, PIPING, EQUIPMENT, ETC., AND ALL FIRE RATED AND FIRE/SMOKE RATED PARTITIONS, TO ALLOW FOR INSPECTIONS OF RATED WALLS.
-RECTANGLE-TO-ROUND TAKE-OFF
23. LOCATE ALL OUTSIDE AIR INTAKES A MINIMUM OF 10' CLEAR FROM ALL PLUMBING VENTS AND EXHAUST AIR DISCHARGE LOCATIONS.
-RECTANGULAR DUCT SECTION UP, NEGATIVE PRESSURE, RETURN -STANDARD BRANCH TAKE-OFF
-RECTANGULAR DUCT SECTION UP, EXHAUST -ROUND DUCT SECTION UP
24. DUCT RUNOUTS TO DIFFUSERS SHALL MATCH THE SIZE OF THE DIFFUSER NECK. 25. WATER PRESSURE DROPS THROUGH COIL CONTROL VALVES SHALL NOT EXCEED 5 PSI.
-SPIN-IN TAKE-OFF
114400 North 49th Street Clearwater, FL.
DESCRIPTION
HVAC GENERAL NOTES
Pinellas County Jail Phase I Infrastructure Criteria Package - Drawings
SYMBOL
HVAC ABBREVIATIONS
Pinellas County
HVAC SYMBOL LEGEND
26. UNLESS OTHERWISE NOTED, ALL EQUIPMENT AND VALVE DRAINS SHALL BE INDEPENDENTLY PIPED FULL SIZE TO THE NEAREST PLUMBING DRAIN.
-FLAT OVAL DUCT SECTION UP -SQUARE THROAT ELBOW W/TURNING VANES
27. SLEEVE AND SEAL ALL PIPING PENETRATIONS THROUGH BUILDING PARTITIONS. PROVIDE MANUAL AIR VENTS AT ALL HIGH POINTS IN CHILLED WATER AND HOT WATER PIPING. 28. PIPING, DUCTWORK, LEAK PROTECTION APPARATUS, OR OTHER EQUIPMENT FOREIGN TO ELECTRICAL SWITCHBOARDS, PANELBOARDS, DISTRIBUTION BOARDS, OR MOTOR CONTROL CENTERS SHALL NOT BE INSTALLED WITHIN THE REQUIRED SPACE FOR WORKING CLEARANCES OR DEDICATED SPACES OF THE ELECTRICAL EQUIPMENT, EXTENDING IN FRONT OF AND FROM FLOOR TO STRUCTURAL CEILING WITH A WIDTH AND DEPTH OF THE ELECTRICAL EQUIPMENT IN ACCORDANCE WITH NEC-110.26.
-RADIUS ELBOW
SEAL
-RECTANGULAR/ROUND BRANCH TAKE-OFF OR ROUND/ROUND BRANCH TAKE-OFF
PRELIMINARY DOCUMENTS -EXHAUST DUCT UP THROUGH SLAB W/ FAN ON ROOF ABOVE
NOT FOR CONSTRUCTION
-EXHAUST FAN ON ROOF W/ DUCT DOWN THROUGH ROOF
KEY PLAN
C
HVAC PIPING SYMBOL LEGEND SYMBOL
DESCRIPTION
SYMBOL
DESCRIPTION
HVAC EQUIPMENT TAGS SYMBOL EQUIP.
CWS
-CONDENSER WATER SUPPLY
-FLOW DIRECTION
CWR
-CONDENSER WATER RETURN
-GATE VALVE
-CHILLED WATER SUPPLY
-BALL VALVE
CHWS CHWR
DESCRIPTION
TAG A
- P-TRAP
-AIR DISTRIBUTION DEVICE
200 CFM
-TWO-WAY CHECK VALVE
SCALE
MV
AHU NUMBER -MANUAL VENT
-CHILLED WATER RETURN
-CALIBRATING BALANCING VALVE
CD
-CONDENSATE
-BUTTERFLY VALVE
CR
-CONDENSATE RETURN
-GAS COCK
-PRESSURE GAUGE
PC
-PUMPED CONDENSATE
-UNION
-RELIEF VALVE
AHU-1
HWR HWS
-HOT WATER SUPPLY
HPS
-HIGH PRESSURE STEAM SUPPLY
MPS
-MEDIUM PRESSURE STEAM SUPPLY -LOW PRESSURE STEAM SUPPLY
S
-STRAINER
FM
-FLOW METER
-CONTROL VALVE
M
-WATER METER
-SOLENOID VALVE -PSI REG. -CHECK VALVE
HPR
-HIGH PRESSURE STEAM RETURN
MPR
-MEDIUM PRESSURE STEAM RETURN
-FLOW SWITCH
LPR
-LOW PRESSURE STEAM RETURN
-SLOPE DIRECTION (DOWN)
-REFRIGERANT LIQUID
-FLEX CONNECTION
RL RS
-REFRIGERANT SUCTION
D
D
-VALVE ON RISER -CAP -CONNECTION, BOTTOM
VARIABLE/CONSTANT AIR VOLUME TERMINAL UNITS
VTU - VARIABLE TERMINAL UNIT CTU - CONSTANT TERMINAL UNIT PTU - PARALLEL TERMINAL UNIT STU - SERIES TERMINAL UNIT
AHU NUMBER TERMINAL NUMBER VTU-1-1
No.
Description
Date
-COUPLING -O.S.&Y. GATE VALVE
-ELBOW, 90°
-STEAM TRAP
-ELBOW, 45°
-THREE-WAY CONTROL VALVE
-ELBOW, TURNED DOWN
-45° PIPE RISE (R) / DROP (D) -ELBOW, TURNED UP -PIPE ANCHORS
-REHEAT COIL
RHC-1-1
TERMINAL UNIT TYPE -INLINE PUMP
-CONNECTION, TOP
-TEE, OUTLET DOWN -TEE, OUTLET UP
-INLINE PUMP
12" = 1'-0"
COIL NUMBER
-HOT WATER RETURN
LPS
B
AHU NUMBER
-AIR HANDLING UNIT
-THERMOMETER
REVISIONS DRAWN BY
HAT
APPROVED BY
LTE
CHECKED BY
LTE
DATE
-CONCENTRIC REDUCER -ECCENTRIC REDUCER
03/19/2014
TITLE
MECHANICAL LEGEND A NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT PROJECT NO.
M-000 SHEET NO.
50057109
6
5
4
3
2
1
Dewberry Architects Inc. 401 SW Water St. Suite 701 Peoria, IL 61602 309.282.8000 Phone 309.282.8001 Fax
F
SAFE HARBOR GENERAL NOTES:
(N)CHWS/R BRANCH TO NEW BUILDING
1.
ALL EXISTING, PLASTIC CHILLED WATER PIPING SHALL BE DEMOLISHED/ABANDONED. ANY METALLIC BRANCH PIPING THAT IS CONNECTED TO PLASTIC MAIN PIPE SHALL BE DISCONNECTED FROM THE PLASTIC PIPE. METAL ENDS SHALL BE CAPPED AND LEFT IN SUITABLE CONDITION FOR CONNECTION TO NEW, METALLIC UNDERGROUND CHILLED WATER LINES. CONTRACTOR TO VERIFY WHERE PLASTIC PIPE ENDS AND METAL PIPE BEGINS.
2.
FINAL PIPE SIZE TO BE DETERMINED BY FINAL DESIGN BUILD CONTRACTOR.
(N)CHWS/R DISTRIBUTION
(E)4" CHWS/R (E)4" CHWS/R
"M1"
(E)6" CHWS/R
(E)6" CHWS/R (E)1" BALL VALVES
(N) CHWS/R DISTRIBUTION (E)8" CHWS/R
"B"
145TH AVE N
HEALTH CARE FACILITY
(E)4" CHWS/R
(E) CHWS/R VALVE BOX
"A"
SHERIFF ADMIN. 2' V ALLEY GU TTER
(E)4" CHWS/R (E)4" CHWS/R
"C" D
"M2"
49TH ST N
(E)3" CHWS/R
(E)3" CHWS/R
(E)8" CHWS/R
142ND AVE N (N) 20" CHWS/R DISTRIBUTION RUN PARALLEL TO EXISTING PIPING SERVING CENTRAL/INTAKE AND HOUSING A-G
(E) CHWS/R
CENTRAL DIVISION
POND POND
114400 North 49th Street Clearwater, FL.
(N)CHWS/R DISTRIBUTION
Pinellas County
E
Pinellas County Jail Phase I Infrastructure Criteria Package - Drawings
CR OS SB AYO U
(N)CHWS/R BRANCH TO NEW BUILDING
SEAL
PRELIMINARY DOCUMENTS NOT FOR CONSTRUCTION
C
PINELLAS COUNTY CRIMINAL COURT COMPLEX
SOUTH DIVISION (E) CHWS/R
(N)CHWS/R PIPING BRIDGED OVER TO STATE ATTORNEY/ CJC CENTER
"G" MAINTENANCE
KEY PLAN
POND
"F"
"E"
"D"
"C"
POND
SCALE
1" = 100'-0"
SIR LB021 (FI R 1/2" LB1344 0.30' S., 0.50' W.)
OHE
OHE
OHE
LAND LINE JURISDICT IONAL WET
B
No.
Description
Date
REVISIONS DRAWN BY
HAT
APPROVED BY
LTE
CHECKED BY
LTE
DATE
JUVENILE DETENTION CENTER
03/19/2014
TITLE
MECHANICAL SITE PLAN EDGE OF W ATER
ASPHALT WALK
A
1
MECHANICAL SITE PLAN
140TH AVE N
FIR 1/2" LB1344
PROJECT NO. EDGE OF W ATER
M-001
Scale: 1" = 100'-0" SHEET NO.
50057109
6
5
4
3
2
1
1 2 3 4 5 6 7
F
1
1.1
3
5
USED OIL TANK
6.9
Keynotes AREA TO BE PROVIDED WITH DEDICATED CHILLED WATER FAN COIL UNIT. AREA TO BE EXHAUSTED. FAN TO BE CHEMICAL RATED. AREA TO BE EXHAUSTED. VAV BOX WITH ELECTRIC HEAT. PROVIDE ACCESS PANEL AS REQUIRED. PROVIDE LINT TRAP. DRYER EXHAUST FAN. ROUTE TO EXTERIOR WALL. COMBUSTION AIR MAKE UP FAN. ROUTE TO EXTERIOR WALL.
Dewberry Architects Inc. 401 SW Water St. Suite 701 Peoria, IL 61602 309.282.8000 Phone 309.282.8001 Fax
7
NEW OIL TANK
A
A S
WORKER STAGING 122
LOADING DOCK 105 PROGRAM MEETING ROOM 111
4 STORAGE
B
D
4
SALLYPORT SERVICE DRIVE 103
DOCK STORAGE 102
BULK REFIG STORAGE 109
JANITOR 142
3 INMATE TOILET 119
4 INMATE TOILET 113
3
T
S
STORAGE 112
B
JANITOR 114
3
T
T
T
T
1
SEARCH 123
Pinellas County
3 INMATE TOILET 121
DOCK STAGING 107
SECURITY ELECTRONICS 101
Pinellas County Jail Phase I Infrastructure Criteria Package - Drawings
E
PROGRAM MEETING ROOM 116
PROGRAM MEETING ROOM 110
BULK DRY STORAGE 108
STAFF
4 3
3
4
118
T
S
STAIR A SA1
MEDIUM PRESSURE SUPPLY DUCT ESTIMATED 80x30
FEC
FEC C
CO AND NO2 SENSORS LINKED TO ALARM
ELEVATOR A EA
1 ELECTRICAL 140
CART WASH 139
OFFICE/ 137
WATER HEATER 124 ELEVATOR B EB
114400 North 49th Street Clearwater, FL.
A.1
A.1
STAIR B SB1
ELEVATOR C EC
C
C
SEAL
3 STAFF TOILET 125
NOT FOR CONSTRUCTION
AIR 1 COMPRESSOR 126
GARBAGE/ RECYCLE DOCK 106
C
PRELIMINARY DOCUMENTS
KEY PLAN
3 UTILITY WASH 136
TRASH COMPACTOR
CLEAN LAUNDRY STORAGE 135 CENTRAL LAUNDRY 138
T
SCALE
D
D 1/8" = 1'-0"
4 T S PARKING AREA
WATER TANK STORAGE 104
B
DRYERS 127
STORAGE 134
MAINTENANCE SUPPLY 133
T 7
S 4
T
T RISER ROOM 132
UNIFORM STORAGE 131
INMATE TOILET 129
BREAK ROOM 130
CHEMICAL STORAGE 128 2
3
5
No.
E.9
H
E.9
6
2448
2448
Description
Date
REVISIONS
C
F
F
DRAWN BY
HAT
APPROVED BY
LTE
CHECKED BY
LTE
DATE
03/19/2014
TITLE
1
A
1
1.1
FIRST FLOOR MECHANICAL PLAN
3
5
6.9
7
FIRST FLOOR MECHANICAL PLAN
Scale: 1/8" = 1'-0" PROJECT NO.
M-110 SHEET NO.
50057109
4
3
2
1
1 2 3 4 5 6
F
7
1.1
3
5
6.9
A
C
H
5 SECURED STORAGE 209
E
401 SW Water St. Suite 701 Peoria, IL 61602 309.282.8000 Phone 309.282.8001 Fax
7
A
C
A.1 DRY FOOD STORAGE 204
Dewberry Architects Inc.
H
1
Keynotes ROUTE EXHAUST DUCTWORK, APPROXIMATELY 60x20, TO KITCHEN HOODS. COORDINATE WITH KITCHEN DESIGNER. ROUTE MAKE UP DUCTWORK, APPROXIMATELY 50x20, TO KITCHEN EQUIPMENT. COORDINATE WITH KITCHEN DESIGNER. ROUTE SUPPLY AND DUCTING TO MECHANICAL CHASE. AREA TO BE EXHAUSTED. AREA TO BE EXHAUSTED. FAN TO BE CHEMICAL RATED. AREA TO BE PROVIDED WITH DEDICATED CHILLED WATER FAN COIL UNIT. REFRIGERATER/ FREEZER AREA. SEE KITCHEN EQUIPMENT PLANS.
BREAK ROOM 211
A.1
CHEMICAL STORAGE (SECURE) 216
WARE WASH AREA 215
4
EQUIPMENT STORAGE 203
UNIFORM 205
TRAY MAKE-UP 220
OFFICE 213
INMATE TOILET 207
B
H C
JAN/EQUIP SUPPLIES 202
6
C
KITCHEN/LAUNDRY STORAGE 201
H
CORRIDOR 210
4 INMATE TOILET 208
B
FOOD SERVICE MGMT OFFICE 214
4
STORAGE 218
C
CART STORAGE AND WASHING 219
STAFF TOILET 206
Pinellas County
STORAGE/ FUTURE LINK 217
CORRIDOR 212
4 4
D
STAIR A SA2
CORRIDOR 221
CORRIDOR 250 FEC
FEC
6 4
4 TRASH HOLDING 246
ICE/BEV. 234
ELEVATOR A EA
ELEVATOR B EB
ELEC 233
D
DAIRY COLDROOM 247
JAN 249
114400 North 49th Street Clearwater, FL.
5
Pinellas County Jail Phase I Infrastructure Criteria Package - Drawings
6
STAIR B SB2
ELEVATOR C EC
D
C
D2
C
D2 C1
C1
SEAL E1 E2 G
3
E1 E2 G D1
STAFF DINING MULTI-PURPOSE 232
NOT FOR CONSTRUCTION
12"X12" 1075 CFM .27" S.P.
G G FIRE CABINET
G G G
STEAM CO N DEN SATE TRAP AN D ST RAI N ER
12"X10" 1456 CFM .39" S.P.
9"X8" 538 CFM .07" S.P.
G G
12"X12" 937 CFM .27" S.P.
SAFET Y VA LVE
VALVE
1/ 2" N PT
SATE 12"X9"CO N DEN RETU RN 1217 CFM STEAM .37" S.P. CO N TRO L
SAFET Y VA LVE
STEAM CO N DEN SATE TRAP AN D ST RAI N ER
STEAM CO N TRO L VALVE 1/ 2" N PT
12"X12" 937 CFM .27" S.P.
1 C
C
STEAM CO N DEN SATE TRAP AN D ST RAI N ER
H
D
APPROXIMATE RETURN DUCT SIZE 70x24
SAFET Y VA LVE
G
12"X10" 1353 CFM .43" S.P.
1/ 2" N PT CO N DEN SATE RETU RN
11"X8" 1012 CFM .29" S.P.
SCALE
D
12"X12" 937 CFM .27" S.P.
JAN 228
STEAM CO N TRO L VALVE
SAFET Y VA LVE
#321.2L
C
STEAM CO N DEN SATE TRAP AN D ST RAI N ER
1/ 2" N PT CO N DEN SATE RETU RN STEAM CO N TRO L VALVE
#321.1L
SAFET Y VA LVE
CO N DEN SATE 12" X9" RETU RN 1216 CFM .37" S.P.
12"X12" 937 CFM .27" S.P.
12"X10" 1379 CFM .42" S.P.
R
12"X10" 809 CFM .20" S.P.
D
R
C D
G
D
KEY PLAN
R
#321.2R
R
FINISHED BULK COLDROOM 243
3
SERVING 231
#321.6L
STEAM CO N TRO L VALVE
BULK MEAT COLDROOM 242
2
FOOD PREP SERVICE AREA 230 D
C
PRELIMINARY DOCUMENTS
CORRIDOR 222
G
FINISH PRODUCE COLDROOM 245
G
HOT FOOD PRODUCTION 235
12"X11" 1648 CFM .47" S.P.
CORRIDOR 251
D1
#321.6R
BULK PRODUCE COLDROOM 248
STEAM CO N DEN SATE TRAP AN D ST RAI N ER
1/8" = 1'-0"
12"X12" 937 CFM .27" S.P.
4 FAUCET, TANGENT DRAW-OFF ARE OPTIONAL
H C
DEN SATE 12"X10"CO N RETU RN 1352 CFM .43" S.P.
1/ 2" N PT
G
12"X10" 809 CFM .20" S.P.
G
#321.1R
G G
THAW/PULL 241
11"X8" 1011 CFM .29" S.P.
C
BULK COLDROOM 242
4
FIRE CABINET
D
C D
MULTI-PURPOSE 223
STAFF TOILET 227 CORRIDOR 229
STAFF 4 TOILET 226
H
APPROXIMATE SUPPLY DUCT SIZE 96x24
A/V CLOSET 224
REF
DAILY DRY STORAGE 236
FINISH VEG PREP 237
REF
FINISH MEAT PREP 238
-10 FREEZER 239
C
-20 FREEZER 240
MIC MIC
H
C
B
6
E.9
E.9 C
H
H
C
F
F 7 CONNECTOR TO CENTRAL TOWER CN
No.
Description
Date
REVISIONS DRAWN BY
HAT
APPROVED BY
LTE
CHECKED BY
LTE
DATE
03/19/2014
TITLE
1
A
1
1.1
SECOND FLOOR MECHANICAL PLAN Scale: 1/8" = 1'-0"
3
5
6.9
7
SECOND FLOOR MECHANICAL PLAN PROJECT NO.
M-120 SHEET NO.
50057109
6
5
4
3
2
1 1 2 3 4 5 6 7
F
8 9 10 11
1
1.1
3
5
6.9
7
12 13 14
Keynotes GENERATOR RADIATOR. PIPE TO AND FROM GENERATOR. THREE- WAY CATALYST INSTALLED ON EXHAUST GAS PIPE. ROUTE EXHAUST GAS PIPE SHORTEST DISTANCE TO ABSORPTION CHILLER. NEW CHILLED WATER FAN COIL UNIT. ROUTE OUTSIDE AIR THROUGH ROOF. COORDINATE ROOF PENETRATIONS WITH STRUCTURAL. AREA TO BE PROVIDED WITH DEDICATED CHILLED WATER FAN COIL UNIT. AREA TO BE EXHAUSTED. ROOFTOP CHILLED WATER AIR HANDLER. PROVIDE MANUFACTURER'S CLEARANCES. SUPPLY AND RETURN DUCTING PENETRATIONS TO BE COORDINATED WITH STRUCTURE. ROOFTOP MAKE UP FAN FOR KITCHEN EQUIPMENT. COORDINATE WITH KITCHEN DESIGNER. COORDINATE ROOF PENETRATIONS WITH STRUCTURAL. ROOFTOP EXHAUST FAN FOR KITCHEN EQUIPMENT. COORDINATE WITH KITCHEN DESIGNER. COORDINATE ROOF PENETRATIONS WITH STRUCTURAL. ROUTE ABSORPTION CHILLER EXHAUST THROUGH ROOF TO MUFFLER. COORDINATE ROOF PENETRATIONS WITH STRUCTURAL. PROVIDE DEDICATED DX/ CHILLED WATER UNIT FOR ELEVATOR MACHINE ROOM. ACOUSTICAL TREATED WALL. PROVIDE ACOUSTICAL WRAP FOR PIPING PENETRATIONS. REFRIGERANT PURGE SYSTEM FAN. PROVIDE OUTSIDE AIR DROP FOR PURGE SYSTEM.
Dewberry Architects Inc. 401 SW Water St. Suite 701 Peoria, IL 61602 309.282.8000 Phone 309.282.8001 Fax
13 14
A
E FUTURE ELECTRIC CHILLER
ELECTRIC CHILLER
CHWPFUTURE ABS
CWP-2 ABS
CHWP-2 ABS
CWP-1 ABS
A.1
CHWP-1 ABS
Pinellas County Jail Phase I Infrastructure Criteria Package - Drawings
CWPFUTURE ABS
CONTROL CONFERENCE RM 313
ELECTRIC CHILLER
FUTURE ABSORPTION CHILLER
ABSORPTION CHILLER
10
CONTROL ROOM 302
FUTURE SYS PUMP
SYS PUMP
CHW FAN COIL REF
Pinellas County
A.1
OFFICE 4301
10
4
REF
B
B CHW FAN COIL 5
STAIR A SA3
STAFF TOILET 305
CWP- FUTURE
D
VESTIBULE
303
6
CHWP-FUTURE CHW FAN COIL ELEVATOR LOBBY CWP-3
CHWP-3
CWP- 2
CHWP-2
CWP-1
CHWP-1
CHW/ DX FAN COIL
CHW FAN COIL ELEVATOR A EA
5
310
WATER TREATMENT AND HYDRONIC SPECIALTIES AREA
CHW FAN COIL GENERATOR CONTROL 309
11
CHEMICAL STORAGE
4
4
COUPON RACK AND CHEMICALS
ELEVATOR C EC
STAIR B SB3
CHW FAN COIL
I.T. ROOM 5 306
SEAL
SHOT FEEDER & PUMPS
ELECTRICAL
C
114400 North 49th Street Clearwater, FL.
A
C
312
PRELIMINARY DOCUMENTS NOT FOR CONSTRUCTION
LAUNDRY CHW AHU
KEY PLAN
C 8 1
7
2
GAS ENGINE SCALE 9
3
1/8" = 1'-0" D
GENERATOR ROOM 311
EXTERIOR ROOF ER1
1
EXTERIOR ROOF ER2
D
KITCHEN CHW AHU
2
7
B FUTURE GAS ENGINE KITCHEN EQUIPMENT CONDENSING UNIT
No.
3
Description
Date
REVISIONS
E.9
E.9
12
F
F
DRAWN BY
HAT
APPROVED BY
LTE
CHECKED BY
LTE
DATE
03/19/2014
20" CHWS/R PIPING TO SOUTH CAMPUS. SEE STRUCTURAL AND ARCHITECTURAL FOR ROUTING.
TITLE
1
1.1
3
5
6.9
7
THIRD FLOOR MECHANICAL PLAN
A
1
THIRD FLOOR PIPING PLAN
PROJECT NO.
Scale: 1/8" = 1'-0"
M-130 SHEET NO.
50057109
6
5
4
3
2
1
1
2
F
3
4
1
1.1
3
5
6.9
Dewberry Architects Inc.
Keynotes ROUTE CONDENSER PIPING FROM TOWER THROUGH ROOF SLAB TO PUMP LOCATED IN MECHANICAL ROOM. COORDINATE ROOF PENETRATION WITH STRUCTURAL. GENERATOR ROOM INTAKE FAN. COORDINATE FAN WITH STRUCTURE. PROVIDE PENTHOUSE. PROVIDE SILENCERS AS REQUIRED. GENERATOR ROOM EXHAUST FAN. COORDINATE FAN WITH STRUCTURE. PROVIDE PENTHOUSE. PROVIDE SILENCERS AS REQUIRED. ABSORPTION CHILLER MUFFLER AND SILENCER. PROVIDE HEAT RECOVERY SYSTEM.
401 SW Water St. Suite 701 Peoria, IL 61602 309.282.8000 Phone 309.282.8001 Fax
7
A
A A.1
FUTURE MUFFLER
E
1
B
FUTURE 2-CELL COOLING TOWER (ELECTRIC CHILLER)
1
1
2-CELL COOLING TOWER (ELECTRIC CHILLER)
2-CELL COOLING TOWER (ELECTRIC CHILLER)
(2) SINGLE-CELL COOLING TOWERS (ABSORPTION CHILLERS) (1) FUTURE
Pinellas County
4
4
1
B
STAIR A SA4
D
114400 North 49th Street Clearwater, FL.
MUFFLER
Pinellas County Jail Phase I Infrastructure Criteria Package - Drawings
A.1
SEAL
C
C 1
PRELIMINARY DOCUMENTS
STAIR B SB4
NOT FOR CONSTRUCTION
KEY PLAN
C 2
3
SCALE
1/8" = 1'-0"
D
D
2
B
3
No.
FUTURE SUPPLY FAN
Description
Date
FUTURE EXHAUST FAN REVISIONS
E.9
E.9
F
F
DRAWN BY
HAT
APPROVED BY
LTE
CHECKED BY
LTE
DATE
03/19/2014
TITLE
1
A
1
1.1
ROOF PIPING PLAN
3
5
6.9
7
ROOF MECHANICAL PLAN
Scale: 1/8" = 1'-0" PROJECT NO.
M-140 SHEET NO.
50057109
6
5
4
3
2
1
Dewberry Architects Inc. 401 SW Water St. Suite 701 Peoria, IL 61602 309.282.8000 Phone 309.282.8001 Fax
F
PIPING SYMBOL LEGEND -FLOW DIRECTION -GATE VALVE -BALL VALVE -CALIBRATING BALANCING VALVE -BUTTERFLY VALVE -GAS COCK
E
Pinellas County Jail Phase I Infrastructure Criteria Package - Drawings
-STRAINER -CONTROL VALVE
-CHECK VALVE -FLOW SWITCH -FLEX CONNECTION -O.S.&Y. GATE VALVE
Pinellas County
-THREE-WAY CONTROL VALVE
-THERMOMETER -TWO-WAY CHECK VALVE
MV
-MANUAL VENT
CHWP-1
-PRESSURE GAUGE CHWP-2
FUTURE CHWP
ABSORPTION CHWP
EXPANSION TANK
FUTURE ABSORPTION CHWP
BYPASS
-RELIEF VALVE
FM
-FLOW METER
M
-WATER METER -INLINE PUMP -INLINE PUMP
D
FUTURE CHILLER
FROM BLDG AIR SEPARATOR
114400 North 49th Street Clearwater, FL.
-UNION
TO BLDG. FUTURE SYSTEM PUMP
SEAL CH-2
PRELIMINARY DOCUMENTS NOT FOR CONSTRUCTION
SYSTEM PUMP
KEY PLAN
C
CH-1
SCALE
NOT TO SCALE ABSORPTION CHILLER
B
FUTURE ABSORPTION CHILLER
No.
Description
Date
REVISIONS
CHILLED WATER PIPING DIAGRAM No Scale
1
DRAWN BY
HAT
APPROVED BY
LTE
CHECKED BY
LTE
DATE
03/19/2014
TITLE
MECHANICAL DIAGRAMS A PROJECT NO.
M-200 SHEET NO.
50057109
6
5
4
3
2
1
Dewberry Architects Inc. 401 SW Water St. Suite 701 Peoria, IL 61602 309.282.8000 Phone 309.282.8001 Fax
F
PIPING SYMBOL LEGEND -FLOW DIRECTION -GATE VALVE -BALL VALVE -CALIBRATING BALANCING VALVE -BUTTERFLY VALVE -GAS COCK
-STRAINER -CONTROL VALVE
-CHECK VALVE -FLOW SWITCH -FLEX CONNECTION
Pinellas County
-O.S.&Y. GATE VALVE -THREE-WAY CONTROL VALVE
-THERMOMETER CT-ABSORPTION FUTURE
CT-ABSORPTION
CT-1
CT-2
CT-FUTURE -TWO-WAY CHECK VALVE -RELIEF VALVE MV
-MANUAL VENT -PRESSURE GAUGE FM
-FLOW METER
M
-WATER METER -INLINE PUMP
D
-INLINE PUMP
FUTURE CWP-ABSORPTION
CWP-ABSORPTION CWP-1
FUTURE CHILLER
CH-2
CWP-2
CWP- FUTURE
114400 North 49th Street Clearwater, FL.
E
Pinellas County Jail Phase I Infrastructure Criteria Package - Drawings
-UNION
SEAL
CH-1
PRELIMINARY DOCUMENTS NOT FOR CONSTRUCTION
KEY PLAN
C
ABSORPTION CHILLER
SCALE FUTURE ABSORPTION CHILLER
NOT TO SCALE
B
No.
Description
Date
REVISIONS
CONDENSER WATER PIPING DIAGRAM No Scale
1
DRAWN BY
HAT
APPROVED BY
LTE
CHECKED BY
LTE
DATE
03/19/2014
TITLE
MECHANICAL DIAGRAMS A PROJECT NO.
M-201 SHEET NO.
50057109
6
5
4
3
2
1
Dewberry Architects Inc. 401 SW Water St. Suite 701 Peoria, IL 61602 309.282.8000 Phone 309.282.8001 Fax
F
REFER TO P201, DETAIL 9 FOR FURTHER DETAIL PLUMBING SYSTEM TO
HEAT RECOVERY RECIRC PUMP
E HOT EXHAUST GAS
HEAT RECOVERY HEAT EXCHANGER, SHELL IN TUBE EXHAUST BYPASS VALVE NO NC
NO ENGINE HIGH TEMP RADIATOR
Pinellas County
FLEX CONNECTION (TYP) NATURAL GAS GENSET
ABSORPTION CHILLER
3-WAY CATALYTIC
HIGH TEMP PUMP
RETURN TEMPERAURE REGULATING 3-WAY VALVE EXPANSION TANK
D
COGENERATOR DIAGRAM
114400 North 49th Street Clearwater, FL.
SILENCER
Pinellas County Jail Phase I Infrastructure Criteria Package - Drawings
FROM
1
No Scale
SEAL
PRELIMINARY DOCUMENTS NOT FOR CONSTRUCTION
KEY PLAN
C
FUTURE EXPANSION TANK ON TOP OF RADIATOR
12" MAX.
EXPANSION TANK ON TOP OF RADIATOR
FLOW LIMITING VALVES
SCALE
MOUNT HEAT EXCHANGER AS CLOSE AS POSSIBLE TO RADIATOR.
NOT TO SCALE
TYPICAL FLEXIBLE CONNECTIONS HOT WATER PIPING (200 F.) OFF THE DUAL ENGINES
PIPING TO PLUMBING SYSTEM SEE PLUMBING FOR CONTINUATION
REFER TO P201, DETAIL 9 FOR FURTHER DETAIL
TYPICAL SHUT-OFF VALVE 12" MAX.
RADIATOR
HEAT EXCHANGER
B
No.
Description
Date
REVISIONS
COGENERATOR DIAGRAM No Scale
2
DRAWN BY
HAT
APPROVED BY
LTE
CHECKED BY
LTE
DATE
03/19/2014
TITLE
MECHANICAL DIAGRAMS A PROJECT NO.
M-202 SHEET NO.
50057109
6
5
4
3
2
1
Dewberry Architects Inc. 401 SW Water St. Suite 701 Peoria, IL 61602 309.282.8000 Phone 309.282.8001 Fax AUTOMATIC FLOW CONTROL DEVICE PRESET BY MANUF. W/ P & T TEST PORTS, STRAINER, AND DRAIN. (PRE-MANUF. SINGLE ASSEMBLY ACCEPTABLE)
THREE WAY CONTROL VALVE
EXTENDED OPERATOR ON BALANCE DAMPER
SPIN-IN FITTING W/VOLUME CONTROL DAMPER (INSUL. PER SPEC.)
MANUAL AIR VENT W/AUTO SHUT-OFF COCK
DRAW BAND
(PRE-MANUF. SINGLE ASSEMBLY ACCEPTABLE)
STEEL RODS W/THREADED ENDS (TYP. 4 PLACES) SUPPORT FROM STRUCTURE ABOVE AS REQUIRED
THREADED CAP, HAND TIGHTENED
COIL
RETURN
SPRING VIB. ISOLATORS
THREADED CAP WITH 1/4" DIA. HOLE DRILLED IN TOP, HAND TIGHTENED.
UNION
PROVIDE WITH FILTER OVER OPENING
FLEXIBLE DUCT MAX. 8'-0" IN LENGTH FULLY EXTENDED.
COOLING COIL
FLEX CONN. (TYP.)
SA SUPPLY
FAN
RA
B
PLUG COCK
SHUT-OFF VALVE (TYP.)
DRAW BAND
A
DRAIN PAN
SLOPE TO DRAIN
BLANK-OFF PLATES WHERE REQUIRED
C
P/T TEST PORTS
CASING SLEEVE
FLOAT SWITCH
UNION (TYP.)
DIFFUSER CONE (INSUL. PER SPEC.)
SNUBBER
CONDENSATE DRAIN PIPING DIMENSIONS:
THERMOMETER W/SEPARABLE WELL (TYP.)
CEILING TEE
ROUTE MAIN CONDENSATE LINE TO FLOOR DRAIN
A = FULL SIZE OF UNIT DRAIN CONNECTION B > 1-1/2" TIMES FAN SUCTION STATIC PRESSURE C > FAN DISCHARGE STATIC PRESSURE PLUS 1/2" INCH
BALL VALVE
CEILING
GALVANIZED SHEET METAL SECONDARY DRAIN PAN TO EXTEND 3" BEYOND UNIT ON ALL SIDES BY 1-1/2" DEEP
COORDINATE MOUNTING/CURB HEIGHT AS REQUIRED TO PROVIDE PROPER CONDENSATE DRAINAGE.
FLEX. CONNECTION (TYP.) NOTES: 1. PROVIDE (4 x DIA.) OF STRAIGHT PIPE ON BOTH SIDES OF BALANCING VALVE 2. ALL COMPONENTS FULL LINE SIZE UNLESS NOTED OTHERWISE 3. LOCATE UNIONS TO ALLOW FOR COIL PULL
LIGHT
3-WAY COIL PIPING DIAGRAM (FCU-4)
1
NOT TO SCALE
AHU CONDENSATE DRAIN TRAP
2
NOT TO SCALE
D
DIFFUSER MOUNTING
3
NOT TO SCALE
FAN COIL UNIT
4
NOT TO SCALE
GEAR W/HAND WHEEL 5" AND LARGER LEVER LATH HANDLE W/MEMORY STOP 4" AND SMALLER
THREE LAYERS OF 5/8" GYPBOARD, REFER TO SPECIFICATION SECTION 15910
DAMPER, TYPICAL MANUAL BALANCING
PRESSURE GAUGE
BUTTERFLY VALVE (TYP.)
TOP OF DUCT TO BE AS HIGH AS POSSIBLE
TAP, TYPICAL 45 DEGREE BOOT
114400 North 49th Street Clearwater, FL.
PRESSURE GAUGE & COCK (TYP.)
E
Pinellas County Jail Phase I Infrastructure Criteria Package - Drawings
DIFFUSER NECK (INSUL. PER SPEC.)
AIR FLOW
STRAINER W / BLOWDOWN
Pinellas County
F
SNUBBER BALL VALVE
EXTEND TREATMENT ACROSS OPEN CEILING SEE PLAN DRWGS.
DIFFERENTIAL PRESSURE TRANSMITTER
P/T PORT W/BLOWDOWN VALVE (TYP.)
DRAW BAND
NON-SLAM CHECK VALVE
SEAL
FLEXIBLE CONNECTER SILENCER
SUPPLY DUCT
FLEXIBLE CONNECTOR
DIAMETER TO MATCH SYSTEM PIPING DIAMETER
PRELIMINARY DOCUMENTS NOT FOR CONSTRUCTION
s" PUMP DRAIN, EXTEND TO FLOOR NEAREST DRAIN
SUCTION DIFFUSER W/INTEGRAL STRAINER & 3/4" BLOW DOWN VALVE. EXTEND TO NEAREST FLOOR DRAIN
C
FLEXIBLE DUCT
SPIN-IN FITTING W/VOLUME CONTROL DAMPER (INSUL. PER SPEC. REQ'D.)
PIPE SUPPORT
RADIUS ELBOWS MAY BE USED IN LIEU OF SQUARE ELBOWS
KEY PLAN
WALL DIAMETER TO MATCH PUMP INLET DIAMETER
NOISE CONTROL TREATMENT AT DUCT SILENCER
5
NOT TO SCALE
CONCRETE HOUSEKEEPING PAD
PIPE SUPPORT
SPLIT-CASE DOUBLE SUCTION PUMP
6
NOT TO SCALE
TYPICAL FLEX DUCT CONNECTION
7
NOT TO SCALE
TYPICAL PRESSURE DUCTWORK
SCALE
8
NOT TO SCALE
NOT TO SCALE VALVES ABOVE TUBE PULL (TYP.) ACTUATOR & VALVE BY CONTROLS CONTRACTOR (TYP.)
LUG TYPE BUTTERFLY VALVE W/GEAR OPERATOR (TYP.) 120 VAC BEACON
ALARM WIRING PER ASHRAE 15 TO EMS
TEMP. SENSOR (TYP.)
A DIFFERENTIAL PRESSURE SENSOR/TRANSMITTER (TYP.)
CWS
ANALOG OUTPUT WIRING
PROVIDE NEW REMOTE ALARM BEACON OUTSIDE ALL CHILLER ROOM ENTRY DOORS
B
A
REFRIGERANT MONITOR PANEL
ROCK FREE BACKFILL
1'-0" MIN.
PITTWRAP JACKETING
FLEXIBLE CONNECTOR FLEX CONNECTION
RESETTING RELIEF ASSEMBLY BY EQUIPMENT MANUFACTURER
FOAMGLASS INSULATION SAMPLE TUBE
FLANGED JOINT
6".
SAND BACKFILL
6".
6" MIN.
COMPRESSION COUPLING
FILTER
FULL SIZE OF VENT OPENING (MIN.) OR AS CODE REQUIRES
CHILLER
12" TO 18"
GRAVEL
No.
Description
Date
RELIEF VENT
TO CHILLER
PIPE
CHWR
SAMPLE LINES
SUPPORT TO COLUMN OR WALL
NOTES: 1. PROVIDE REFRIGERANT MONITOR CAPABLE OF SENSING R-123 REFRIGERANT. 2. NEW EXHAUST FAN. 3. PROVIDE TWO REFRIGERANT SAMPLE LINES I LOCATIONS AS SHOWN ON PLANS.
CHILLER DIFFERENTIAL PRESSURE SWITCH TO CHILLER CONTROL PANEL
PRESSURE GAUGE W/ SNUBBER & BALL VALVES (TYP.) CONNECT NEW RELIEF PIPING TO EXISTING RELIEF PIPING HEADER.
6" MIN.
THERMOMETER (TYP.)
CHWS
CWR
R OOF
COMPRESSOR SUCTION CONNECTION
RELIEF PIPING SHALL BE SIZED AND INSTALLED IN ACCORDANCE WITH ASHRAE STANDARD 15. MINIMUM RELIEF PIPING SIZE INDICATED ON FLOOR PLAN. DEVIATION FROM SIZE INDICATED IS ACCEPTABLE ONLY AFTER RECOMMENDATION FROM CHILLER MANUFACTURER AND APPROVAL OF THE ENGINEER. COORDINATE RELIEF PIPING REQUIREMENTS WITH CHILLER MANUFACTURER.
REVISIONS CONTROL PANEL CONDENSER TO CONTROL PANEL
DRAWN BY
HAT
APPROVED BY
LTE
CHECKED BY
LTE
DATE VIBRATION ISOLATION SPRINGS (TYP.)
EVAPORATOR
03/19/2014
TITLE
HOUSEKEEPING PAD
MECHANICAL DETAILS
FLANGED ELBOW W/ LIFT PLATE (TYP.) FLOOR SLAB
FLOOR
A
6" MINIMUM
MECHANICAL JOINT (SIMILIAR TO A VICTAULIC COUPLING)
r" FL x r" NPT DRAIN VALVE (5'-0" ABOVE FLR.)
PETE'S PLUG (TYP.)
PROJECT NO.
UNDERGROUND PIPING INSTALLATION
NOT TO SCALE
9
REFRIGERANT MONITORING
NOT TO SCALE
10 RELIEF PIPING NOT TO SCALE
11 WATER COOLED CHILLER NOT TO SCALE
12
M-300 SHEET NO.
50057109
ARCHITECTURAL
HVAC ABBREVIATIONS AFU F
DUCTWORK
HVAC DUCTWORK SYMBOLS
ANNUAL FUEL UTILIZATION EFFICIENCY DESCRIPTION
SYMBOL DO NOT SCALE DRAWINGS. REFER TO ARCHITECTURAL DRAWINGS AND REFLECTED CEILING PLANS FOR EXACT LOCATION OF DOORS, WINDOWS, CEILING DIFFUSERS,
1.
ETC. 2.
ALL DUCTWORK INSTALLATION SHALL RUN CONTINUOUSLY THROUGH PARTITIONS.
EAT EER
ENTERING AIR TEMPERATURE ENERGY EFFICIENCY RATIO
LOCATE ALL DUCT BALANCING DAMPERS, CONTROL DAMPERS AND FIRE DAMPERS
E/F EWH
EXHAUST FAN
NO FIRE DAMPERS SHOWN ON THE PLANS (DUCTWORK SIZE IS LESS THAN 100
FCU
FAN COIL UNIT
CONDITIONS.
SQUARE INCHES), PROVIDE THE FOLLOWING, MINIMUM:
PIPING AND DUCTWORK ROUTING SHOWN IS SCHEMATIC. HVAC CONTRACTOR SHALL PROVIDE ANY ADDITIONAL OFFSETS AND FITTINGS, INCLUDING DIVIDED DUCTS, REQUIRED FOR PROPER INSTALLATION AND TO MAINTAIN CLEARANCES AS
1). A MINIMUM OF 12-INCH LONG BY 0.060-INCH THICK STEEL SLEEVE SHALL BE CENTERED IN EACH DUCT OPENING.
HP HVAC
HORSEPOWER HEATING, VENTILATING, AIR CONDITIONING
ENCOUNTERED IN THE FIELD.
2). THE SLEEVE SHALL BE SECURED TO BOTH SIDES OF THE WALL AND ALL FOUR SIDES OF THE SLEEVE WITH A MINIMUM OF 1-1/2" x 1-1/2" X 0.060" STEEL RETAINING ANGLES.
PRIOR TO INSTALLATION OF ASSOCIATED WORK; INSTALLER SHALL MEET AT PROJECT SITE WITH GENERAL CONTRACTOR, INSTALLER OF EACH COMPONENT OF ASSOCIATED
4).
WORK, INSPECTION AND TESTING AGENCY REPRESENTATIVES (IF ANY), INSTALLERS OF
OTHER WORK REQUIRING COORDINATION WITH WORK OF THIS SECTION AND ARCHITECT / OWNER FOR PURPOSE OF COORDINATING LOCATIONS OF PROPOSED SYSTEMS, REVIEWING MATERIAL SELECTIONS, AND PROCEDURES TO BE FOLLOWED IN PERFORMING THE WORK IN COMPLIANCE WITH REQUIREMENTS
6.
SPECIFIED.
THE ANNULAR SPACE BETWEEN THE STEEL SLEEVE AND WALL SHALL BE FILLED WITH SILICONE ELASTOMER TO PROVIDE A MINIMUM 2-HOUR RATED FIRESTOP.
BUILDING STRUCTURE, PLUMBING PIPING, ELECTRICAL CONDUIT, LIGHTING, ETC.
7.
PRIOR TO PURCHASING OR INSTALLING EQUIPMENT AND MATERIALS.
6. 7.
IN
INCHES
KW
KILOWATT
LAT LBS
LEAVING AIR TEMPERATURE POUNDS
MBH MCA
1,000 BRITISH THERMAL UNITS MINIMUM CIRCUIT AMPACITY
200-2 8"0
RTU
ROOFTOP UNIT
DUCTWORK SIZES INDICATED ON DRAWINGS ARE INSIDE, FREE AND CLEAR
SEER SP
SEASONAL ENERGY EFFICIENCY RATIO STATIC PRESSURE
DIMENSIONS. INCREASE DUCT OUTSIDE DIMENSION SIZE BY TWO (2) TIMES THE THICKNESS OF THE INSULATION.
TU
TERMINAL UNIT
VAV
VARIABLE AIR VOLUME
W/
WITH WET BULB
BE FLASHED AND COUNTERFLASHED IN A WATERPROOF MANNER.
8.
ALL DUCTWORK SHALL BE CONSTRUCTED SMACNA STANDARDS.
AND INSTALLED IN ACCORDANCE WITH
MAINTAIN MINIMUM OF TEN (10) FEET BETWEEN OUTDOOR AIR INTAKES AND EXHAUST FAN DISCHARGE, PLUMBING VENTS, ETC.
9.
ALL DUCTWORK SHALL BE GALVANIZED SHEET METAL IN AREAS WITH FINISHED
www.cjsarchitects.com
EBS ENGINEERING, PC ENGINEERED BUILDING SYSTEMS
WB
HVAC DRAWING LIST M-1
HVAC SCHEDULES, LEGENDS AND ABBREVIATIONS
M-2
HVAC SCHEDULES
M-3
FLOOR PLAN - HVAC DUCTWORK AND PIPING
M-4
ROOF PLAN - HVAC DUCTWORK AND PIPING
M-5
HVAC DETAILS
4050 RIDGE LEA ROAD BUFFALO NEW YORK 14228 PHONE: (716) 836-9600 FAX: (716) 836-9636 E-MAIL:
[email protected] WEBSITE:
MANUAL VOLUME DAMPERS
ROUND SUPPLY AIR DEVICE FIRST NO. CFM, SECOND NO. TYPE THIRD NO. NECK SIZE (REFER TO SCHEDULE FOR SIZE) RETURN / EXHAUST AIR DEVICE
200-1
REVOLUTIONS PER MINUTE
ALL PIPING, DUCTS, VENTS, ETC. EXTENDING THROUGH WALLS AND ROOF SHALL
40
RPM
COORDINATE INSTALLATION AND LOCATIONS OF DUCTWORK AND PIPING WITH
CONTROL WIRING (PLENUM RATED)
DIRECTION OF SLOPE (DOWN IN DIRECTION OF ARROW)
OPEN END DUCT
DUCT WIDTHS FROM BRANCH TAKEOFF.
PROGRAMMABLE, 7-DAY, 24-HOUR THERMOSTAT
INTERNALLY LINED DUCTWORK
OED
PROVIDE VOLUME CONTROL DAMPERS WITH QUADRANT AND LOCK AND STANDOFF COLLAR AT ALL BRANCH DUCTS TO DIFFUSERS. INSTALL AT A MINIMUM OF TWO
T
266 Alexander Street Rochester, N.Y. 14607 585.244.3780 tel 585.244.1294 fax
MECHANICAL / ELECTRICAL ENGINEERS
NO ALLOWANCES WILL BE MADE FOR CONTRACTOR'S UNFAMILIARITY WITH PROJECT
THE RETAINING ANGLES SHALL BE SECURED TO THE SLEEVES AND THE WALL WITH NO. 10 (M5) SCREWS.
RETURN DUCT RISER
FLEXIBLE DUCT
FAHRENHEIT
3).
TEMPERATURE SENSOR
DUCT RISE OR DROP
ELECTRIC WALL HEATER
F
FURNISH ALL LABOR, MATERIAL AND EQUIPMENT REQUIRED FOR THE COMPLETE INSTALLATION AND OPERATION OF ALL SYSTEMS IN THIS SECTION OF WORK IN
S
AIRFOIL TURNING VANES
WHERE DUCTWORK PASSES THROUGH A FIRE-RATED ASSEMBLY, AND THERE ARE
A.
SUPPLY DUCT RISER
EXHAUST DUCT RISER
THE HVAC CONTRACTOR SHALL VISIT THE JOB SITE AND BE FAMILIAR WITH ALL
ACCORDANCE WITH ALL APPLICABLE CODES, ASHRAE, SMACNA, NFPA, EPA, ETC.
5.
DRY BULB DIRECT DIGITAL CONTROL
4.
PROJECT CONDITIONS PRIOR TO FABRICATING DUCTWORK, EQUIPMENT, ETC.
4.
DB DDC
ASPECT RATIO SHALL NOT EXCEED 3:1.
ABOVE ACCESSIBLE CEILINGS OR PROVIDE CEILING ACCESS DOORS.
3.
CUBIC FEET PER MINUTE CONDENSING UNIT
3.
5.
GENERAL
2.
CFM CU
REFER TO ARCHITECTURAL FLOOR PLANS FOR LOCATION AND RATING OF ALL FIRE WALLS.
1.
BRAKE HORSEPOWER
*1
3.
LIGHT FIXTURE LOCATIONS TAKE PRECEDENCE OVER DIFFUSER AND GRILLE LOCATIONS. LOCATE DIFFUSERS AND GRILLES TO ACCOMMODATE LIGHTING LAYOUT.
DUCTWORK SHALL NOT BE SUPPORTED FROM BRIDGING, CONDUIT, PIPING, ETC. OF ANY KIND. DO NOT USE FASTENERS THAT PENETRATE ROOF DECKS.
BHP
STARK
WWW.EBSPE.COM
COPYRIGHT C 2016 ENGINEERED BUILDING SYSTEMS
D. 8o
j
o
(p s
-
2.
RUN ALL DUCTWORK AND PIPING AS TIGHT TO BOTTOM OF STEEL AS POSSIBLE OR RUN THRU OPEN JOIST WEBBING.
JENSEN
303 South Park Avenue Buffalo, N.Y. 14204 716.856.6448 tel 716.852.1722 fax
DESCRIPTION
SYMBOL
-
1.
CHAINTREUIL
HVAC CONTROL SYMBOLS
ARCHITECTS, LLP
HVAC GENERAL NOTES
FIRST NO. CFM, SECOND NO. TYPE
G
0 47
THIRD NO. NECK SIZE (IF REQUIRED)
(REFER TO SCHEDULE FOR SIZE) o S
CEILINGS.
8.
9.
REFER TO PLUMBING DRAWINGS FOR LOCATION AND ROUTING OF ALL CONDENSATE DRAIN LINE CONNECTION POINTS, GAS PIPING, AND WATER HEATER COMBUSTION / EXHAUST AIR DUCTWORK.
10. WHERE RECTANGULAR DUCTWORK IS INDICATED, AND AT INSTALLERS OPTION, PROVIDED THEY ARE EQUIVALENT TO THE RECTANGULAR DIMENSIONS INDICATED ON THE DRAWINGS (i.e.: 8x4 = 8"0, 10x6 = 10"0).
DIVISION 23 SHALL BE LICENSED TO PERFORM MECHANICAL WORK IN THE
AIR DISTRIBUTION DEVICE SCHEDULE
MUNICIPALITY IN WHICH THE PROJECT IS LOCATED.
11. PROVIDE INTERNALLY LINED SUPPLY AIR DUCTWORK FROM ROOFTOP UNITS TO A UNDER THIS CONTRACT AGAINST DEFECTS IN MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE (1) YEAR FROM THE DATE OF THE OWNER'S FINAL ACCEPTANCE OF THE WORK. ANY DEFECTS SHALL BE RECTIFIED BY DIVISION 15 WITHOUT ANY
PROTECTION AND CONSTRUCTION CODE, NEW YORK STATE ENERGY CONSERVATION CODE, AND ANY STATE AND LOCAL CODES OR REGULATIONS THAT APPLY.
A.
ALL HVAC EQUIPMENT SHALL BE INSTALLED PER MANUFACTURER'S REQUIREMENTS
ALL EQUIPMENT SHALL HAVE A ONE (1) YEAR WARRANTY; COMPRESSORS SHALL HAVE AN ADDITIONAL FIVE (5) YEAR EXTENDED WARRANTY, ROOFTOP UNIT HEAT
STORE ALL EQUIPMENT
IN A DRY PLACE, PROTECTING ALL EQUIPMENT FROM THE WEATHER,
15. MAXIMUM FLEXIBLE DUCT LENGTH SHALL BE 5'-0".
ROOF CURBS SHALL HAVE A BASE THAT FITS SLOPE OF ROOF AS REQUIRED.
FLEXIBLE CONNECTORS SHALL BE INSTALLED ON SUPPLY, RETURN, AND EXHAUST
1.
MODIFICATION, OR SUBSTITUTION TO THESE DRAWINGS AND SPECIFICATIONS FOR EVALUATION NO LATER THAN TEN (10) DAYS PRIOR TO THE BID DATE.
EXCEED
SPECIFIED
B. C.
NO MATERIALS SHALL BE DEEMED ACCEPTABLE IF NOT IN STRICT AND FULL
3.
CONDENSATE DRAIN PIPES SHALL HAVE CLEANOUTS AT EVERY CHANGE IN DIRECTION,
MATERIALS
PERFORATED FACE, STEEL CONSTRUCTION, OPPOSED BLADE VOLUME DAMPERS, PROVIDE 22"x22" BACKPAN FOR FULL
TITUS
(DIA.)
CFM
MINIMUM OUTSIDE AIR
8"0
200
75
SIZE
TOTAL
CFM
TITUS
(BYPASS)
TU-04
MIT OFFICE 43
TITUS
4.
TU-05
LAY-IN
PERFORATED FACE, STEEL CONSTRUCTION, OPPOSED BLADE VOLUME DAMPERS, PROVIDE 22"x22" BACKPAN FOR FULL
TITUS
(BYPASS)
8"0
300
100
10"o
500
125
ALL DEVICES SHALL HAVE MATCHING MATTE, WHITE FINISH (UNLESS OTHERWISE NOTED IN DESCRIPTION ABOVE).
4.
ESMB-12 (BYPASS)
12"0
850
200
MIT OFFICE 40
TITUS
ESMB-08 (BYPASS)
8"0
300
100
HVAC CONTRACTOR SHALL BE RESPONSIBLE FOR THE SIZING OF REFRIGERANT
3.
MAXIMUM NC OF 20.
4.
ACCESSORIES:
TU-06
MULTIPURPOSE ROOM 41
TITUS
(BYPASS)
10"o
500
125
TU-07
OFFICE 12, OFFICE 13, OFFICE 15, OFFICE 16, OFFICE 18, OFFICE 20
TITUS
ESMB-12 (BYPASS)
12"0
1,000
200
TU-08
OFFICE 6, OFFICE 7, OFFICE 9, OFFICE 11
A.
(BYPASS)
700
OPERATING KEYS: TOOLS DESIGNED TO FIT THROUGH DIFFUSER FACE AND OPERATE VOLUME CONTROL DEVICE AND / OR PATTERN ADJUSTMENT
VARIABLE AIR VOLUME TERMINAL UNIT NOTES:
2.
LOW LEAKAGE BYPASS DIVERTING CONTROL DAMPER WITH EDGE SEALS.
ALL CONTROL WIRING AND POWER CONDUCTOR INSULATION SHALL BE PLENUM
3.
MINIMUM 1/2" THICK (CLOSED-CELL) FIBRE-FREE INTERNALLY LINED.
4.
FACTORY INSTALLED MODULATING ACTUATOR (0-10V DC, CONTROLLED BY THERMOSTAT).
5.
MAXIMUM AIR PRESSURE DROP OF 0.40 INCHES WG.
6.
ACCESSORIES:
ACCEPTABLE MANUFACTURER'S - TITUS, PRICE.
ALL EXPOSED CONTROL WIRING SHALL BE INSTALLED IN 3/4" EMT CONDUIT. PROVIDE ALL RELAY, CONTACTORS, ETC. REQUIRED TO ACHIEVE INTERLOCK OPERATION
ELECTRIC WALL HEATER SCHEDULE
OF EQUIPMENT.
MARK
AREA SERVED
MANUFACTURER
MODEL NO.
SERIES
TYPE
3450 SERIES
SEMI-
(HEAW DUTY
RECESSED MOUNTING
MBH
WATTS
AMPS
VOLTS / PH
COUNCIL (AABC) OR NATIONAL ENVIRONMENTAL BALANCING BUREAU (NEBB); UPON COMPLETION OF THE PROJECT, SHALL PERFORM A COMPLETE TESTING AND BALANCING
OF ALL EQUIPMENT.
BALANCE SYSTEM TO WITHIN ±5% OF AIR QUANTITIES INDICATED
ON PLANS AND SCHEDULES AND PROVIDE THE OWNER WITH A COMPLETE, SIGNED AND SEALED BALANCE REPORT.
EWH-1
49 S. WATER STREET
175
DRAWING TITLE
CODE (NEC) AND NFPA 70.
MECHANICAL CONTRACTOR, WHO IS CERTIFIED BY EITHER THE ASSOCIATED AIR BALANCE
FLEX BUILDINNG OFFICE/EDICALREIAIL
NEW YORK 14070 10"o
MINIMUM 20-GAUGE GALVANIZED STEEL HOUSING WITH INTEGRAL SOUND ATTENUATOR.
5.
500 SENECA ST - SUITE 508 BUFFALO, NY 14204 (71 6) 332-5959 tel. (716) 332-5968 fax.
ESMB-10 TITUS
1.
ALL CONTROL WIRING AND CONDUIT SHALL COMPLY WITH THE NATIONAL ELECTRIC
49 S. WATER STREET, LLC
VILLAGE OF GOWANDA
HVAC EQUIPMENT
RATED.
3.
TITUS
PAR
AIR DISTRIBUTION DEVICE NOTES:
CONTROLS
2.
VESTIBULE 1, WAITING 2, TOILET 3,
ESMB-10
2.
SUPPLIER SHALL VERIFY REFRIGERANT PIPE LINE SIZES AND CONFIGURATIONS BASED ON CONTRACTOR'S PROPOSED PIPE ROUTING.
1.
(BYPASS)
I development
OWNER:
ESMB-10 TITUS
PANEL LAY-IN APPLICATION, WHITE FINISH
TYPE 3
DISTANCES GREATER THAN 3 FEET, AND AT THE BEGINNING OF LONG STRAIGHT RUNS. LINES (LONG LINE APPLICATION) GREATER THAN 50'-0".
CONFERENCE ROOM 14
EXHAUST EXHAUST 24x24
40wVIILiTM1$ cOmpanies construction
PAR
PANEL LAY-IN APPLICATION, WHITE FINISH
ALL DEVICES SHALL BE FROM A SINGLE MANUFACTURER.
1.
/
MIT OFFICE 39
MULTIPURPOSE
1.
ALL BIDDERS MUST BID SOLELY ON THE SPECIFIED MATERIALS UNLESS
FAILURE TO SUBMIT PROPOSED SUBSTITUTED EQUIPMENT
DUCT
RECEPTION DESK 4
Q
CONDENSATE PIPING FROM AIR CONDITIONING EQUIPMENT SHALL BE PITCHED A MINIMUM OF 1/4" PER FOOT, IN THE DIRECTION OF FLOW.
BALANCING
1).
LAY-IN
24x24
TYPE 2
ALL PIPING LINES, INCLUDING CONDENSATE DRAINS, SHALL BE FULLY INSULATED
COMPLIANCE WITH THESE DRAWINGS AND SPECIFICATIONS.
ACCEPTANCE BY THE ENGINEER OF A DEVIATION, OMISSION, MODIFICATION, OR SUBSTITUTION IS GRANTED IN WRITING THROUGH THE ARCHITECT / OWNER TO ALL BIDDERS PRIOR TO THE BID DATE.
ALL FLEXIBLE DUCT SHALL
2.
MATERIALS AND IN COMPLIANCE WITH THESE DRAWINGS AND SPECIFICATIONS. REQUESTS FOR SUBSTITUTION SHALL BE MADE ONLY BY THE BIDDER; REQUESTS FOR SUBSTITUTION FROM SALES REPRESENTATIVES, VENDORS, OR SUPPLIERS ARE NOT ACCEPTABLE.
MODEL NO.
ESMB-08
AND VAPOR BARRIER, FLAME SPREAD RATING OF 25 OR LESS, AND SMOKE-DEVELOPED RATING OF 50 OR LESS.
A REQUEST FOR ANY SUBSTITUTION SHALL BE ACCOMPANIED BY TECHNICAL
DATA, DRAWINGS, PRODUCT SAMPLES, AND COMPLETE DATA SUBSTANTIATING
MANUFACTURER
DAT TU-02
RETURN
0
WITH MINIMUM 1-1/2" THICK, 0.75 LB DENSITY, INSULATION WITH ALL SERVICE JACKET
THE BIDDER MUST SUBMIT IN WRITING TO THE ARCHITECT / OWNER, WHO WILL
1).
TITUS
RETURN
PIPING
AIR DUCTS AT ALL EQUIPMENT CONNECTIONS. FORWARD TO THE ENGINEER, ANY REQUEST FOR A PROPOSED DEVIATION,
AREA SERVED
N®
ESMB-08
ARCHITECTURAL PLAQUE FACE, STEEL CONSTRUCTION, 3 SLOTS (SLOT WIDTH IS 1-1/2"), OPPOSED BLADE
KINKING AND SAGGING. (FLEXIBLE DUCT IS NOT PERMITTED IN EXPOSED AREAS, RETURN AIR GRILLE AND EXHAUST AIR GRILLE CONNECTIONS).
TOP OF ROOF CURB SHALL BE LEVEL.
/
MARK
VOLUME DAMPER, 4-WAY THROW, WHITE FINISH
TYPE 1
CONFORM TO THE REQUIREMENTS OF U.L. 181 FOR CLASS 1 FLEXIBLE AIR DUCTS, WITH A MINIMUM R-VALUE OF R-6. SUPPORT FLEXIBLE DUCT TO ELIMINATE
CONSTRUCTION TRAFFIC AND THEFT.
COMPLIANCE OF PROPOSED SUBSTITUTION THAT MEET
LAY-IN
24x24
REGISTERS AND GRILLES.
GENERAL CONTRACTOR SHALL STORE ALL HVAC EQUIPMENT (ROOFTOP UNITS,
A.
[O]
SUPPLY
LINER SHALL BE BLACK IN COLOR SO IT IS NOT NOTICEABLE FROM THE INSIDE OF
PROVIDE WRITTEN GUARANTEE.
6.
MODEL NO.
TU-03
EXCHANGERS SHALL HAVE AN ADDITIONAL TEN (10) YEAR EXTENDED WARRANTY;
5.
MANUFACTURER
KEY PLAN
AIR QUANTITY
EDITION), AND ENVIRONMENTALLY FRIENDLY WITH A MINIMUM R-VALUE OF R-6.
INSTALLED.
4.
DESCRIPTION
TU-01
14. ALL SQUARE ELBOWS SHALL HAVE AIRFOIL TYPE TURNING VANES.
DUCTWORK, ETC.) THAT ARRIVES AT THE PROJECT SITE.
MOUNTING
FROM ENTERING THE AIRSTREAM (COATING SHALL MEET ASHRAE 62 - LATEST
AS SHOWN. UTILIZE FACTORY FILTERS DURING CONSTRUCTION AND REPLACE (IN KIND) JUST PRIOR TO TESTING AND BALANCING. ALL FILTERS SHALL BE 2-INCHES THICK. PROVIDE ONE (1) SET OF EXTRA FILTERS FOR EACH UNIT
3.
STYLE DEVICE SIZE
SUPPLY
13. ALL DUCT LINERS SHALL BE MINIMUM 1-1/2" THICK, COATED TO PREVENT ELEMENTS
IN CASE OF CONFLICTS BETWEEN DRAWINGS, SPECIFICATIONS, AND INTERPRETATION
EQUIPMENT
2.
SYMBOL
12. ALL RETURN AIR DUCTWORK SHALL BE INTERNALLY LINED.
OF CODES BY LOCAL AUTHORITY, LATER SHALL GOVERN.
1.
INLET
FLAME SPREAD RATING OF 25 OR LESS, AND SMOKE-DEVELOPED RATING OF 50 OR LESS.
ADDITIONAL COST TO THE OWNER.
VARIABLE AIR VOLUME TERMINAL UNIT SCHEDULE
&
MINIMUM OF 10-FEET AWAY FROM THE UNIT. REMAINING SUPPLY AIR DUCTWORK SHALL BE EXTERNALLY INSULATED WITH MINIMUM 1-1/2" THICK, 0.75 LB DENSITY, FOIL-BACK INSULATION WITH VAPOR BARRIER AND A MINIMUM R-VALUE OF R-6,
10. DIVISION 23 SHALL GUARANTEE ALL WORK PERFORMED AND MATERIALS FURNISHED
11. WORK SHALL COMPLY WITH THE LATEST REVISIONS OF NEW YORK STATE BUILDING CODE, NEW YORK STATE MECHANICAL CODE, NEW YORK STATE UNIFORM FIRE
I
SPIRAL AND ROUND DUCTWORK MAY BE SUBSTITUTED FOR RECTANGULAR DUCTWORK
VESTIBULE 1
MARKEL
F3453T
FAN FORCED)
6.8
2,000
9.6
PRIOR TO THE BID EVALUATION DATE, AND IS INCLUDED IN THE BIDDERS PRICE / SUBMITTAL REVIEW DRAWINGS (AFTER THE PROJECT IS AWARDED);
208/1/60
HVAC SCHEDULES, LEGENDS AND ABBREVIATIONS JOB NO.
1210
SCALE
NONE
4.15.2016
A.
DISCHARGE AIR SENSOR.
DATE
B.
WALL MOUNTED THERMOSTAT (MODULATING (0-10V DC OUTPUT).
DRAWN BY
C.
FACTORY INSTALLED ACCESS DOOR.
CHECKED BY
7.
MAXIMUM RADIATED NC OF 25 AND DISCHARGE NC OF 22.
8.
ACCEPTABLE MANUFACTURERS: CARRIER, TITUS, PRICE.
REVISIONS
WILL RESULT IN A "REJECTED" SUBMITTAL PACKAGE. ELECTRIC WALL HEATER NOTES: 1.
ELECTRIC WALL HEATERS SHALL CONTAIN AN INTEGRAL, TAMPERPROOF THERMOSTAT.
3.
ELECTRIC WALL HEATERS SHALL BE EQUIPPED WITH BUILT-IN THERMAL OVERLOAD PROTECTION.
4.
FURNISHED AND INSTALLED BY DIVISION 23.
A.
THIS IS A SINGLE SHEET OF A COHESIVE
SET OF CONSTRUCTION DOCUMENTS (INCLUDING DRAWINGS AND SPECIFICATIONS).
WIRING BY DIVISION 26.
INTERPRETATION OF THE INFORMATION
5.
FURNISH 2" SEMI-RECESSED
MOUNTING FRAME #3450EX16 FOR EACH SEMI-RECESSED
6.
COLOR, INCLUDING CUSTOM COLOR, AS SELECTED BY ARCHITECT.
7.
ACCEPTABLE MANUFACTURERS - MARKEL, Q'MARK, INDEECO.
MOUNTED ELECTRIC WALL HEATER.
AS PRESENTED SHOULD BE BASED ON
THE ENTIRE SET OF DOCUMENTS.
DRAWING NO.
M-1 100% DESIGN SUBMISSION
CHAINTREUIL
RTU-1
AREA SERVED
TONS
ENTRY 36, STORAGE 37, KITCHEN 38, MIT OFFICE 39, COMMUNITY ROOM 42, MIT OFFICE 43
8.5
3,625
2,875
STATIC PRESS.
IN. WG EXT.
DX COOLING COIL MANUFACTURER
0.60
750
MODEL NO.
CARRIER
MBH
EAT 'F
97.0
48HCF-09
GAS HEATING SECTION MIN. ROWS
LAT 'F
80
4
67
MBH
MBH
AFUE
INPUT
OUTPUT
180.0
147.0
(1ST STAGE) |(1ST STAGE) 224.0
EAT 'F
LAT 'F
RPM
82%
58
95
80%
58
81%
58
SUPPLY AIR FAN MOTOR
184.0
EER
MCA
OPERATING WEIGHT
(LBS.)
VOLTS / PH
855
1.86
3
460/3/60
12.0
25.0
1,450
FAMILY CARE OFFICE 21, SUPERVISOR 22, ENTRY 23. OFFICE 24, MECHANICAL 25, STORAGE 32, JANITOR 34
3.0
1,225
975
250
0.60
CARRIER
48HCE-04
36.0
80
67
3
95
935
0.55
1
460/3/60
12.5
14.0
1,400
RTU-3
VESTIBULE 1, WAITING 2, TOILET 3, RECEPTION DESK 4, CORRIDOR 5, DATA 5A, TOILET 8, TOILET 10, MULTIPURPOSE CONFERENCE ROOM 14, STORAGE 17, TREATMENT ROOM 19, STORAGE 26, BREAKROOM 27,
12.5
5,500
4,375
1,1.25
0.80
CARRIER
48HCF-14
146.0
80
67
4
95
760
2.99
5
460/3/60
12.2
34.0
2,400
(1ST STAGE) 1 (1ST STAGE) 240.0
ENGINEERED BUILDING SYSTEMS MECHANICAL / ELECTRICAL ENGINEERS
195.0
(2ND STAGE) 1(2ND STAGE) 1,400
4050 RIDGE LEA ROAD BUFFALONEWYORK 14228 PHONE: (716) 836-9600 FAX (716) 836-9636 EAIL:
[email protected]
OFFICE 6, OFFICE 7, OFFICE 9, OFFICE 11, OFFICE 12, OFFICE 13, OFFICE 15, OFFICE 16, OFFICE 18, OFFICE 20
82.0 66.0 (1ST STAGE) 1 (1ST STAGE) 115.0 90.0 (2ND STAGE) 1(2ND STAGE)
www.cjsarchitects.com
EBS ENGINEERING, PC
,
OFFICE 28, OFFICE 29, RECORDS 30, WOMENS TOILET 33, MENS TOILET 35, MIT OFFICE 40, MULTIPURPOSE ROOM 41
266 Alexander Street Rochester, N.Y. 14607 585.244.3780 tel 585.244.1294 fax
*
RTU-2
303 South Park Avenue Buffalo, N.Y. 14204 716.856.6448 tel 716.852.1722 fax
HP
(2ND STAGE) 1(2ND STAGE) 82.0 66.0 (1ST STAGE) 1 (1ST STAGE) 115.0 89.0 (2ND STAGE) 1(2ND STAGE) 192.0 156.0
STARK
BHP
%
MARK
SUPPLY I RETURN I OUTSIDE AIR AIR AIR CFM CFM CFM
JENSEN
ARCHITECTS, LLP
ROOFTOP UNIT SCHEDULE
RTU-4
5.0
1,700
1,325
375
0.60
CARRIER
57.5
48HCE-06
80
4
67
81%
57
1196
95
1.05
460/3/60
2
12.45
17.0
WEBSITE:
ROOFTOP UNIT NOTES:
4OF
7.
1.
UNITS SHALL BE LISTED AND LABELED WITH THE ENERGY STAR LOGO.
2.
FACTORY ASSEMBLED, PACKAGED UNIT WITH ROOF CURB AND ALL STANDARD ACCESSORIES.
8.
UNIT SHALL HAVE: A.
A.
R41OA REFRIGERANT.
9.
ACCESSORIES: 2'-0" HIGH, SOLID BOTTOM THERMAL
/
A.
/
B.
ALL SECTIONS SHALL HAVE HINGED ACCESS DOORS.
B.
OUTSIDE AIR INTAKE HOOD AND RELIEF
4.
UNIT SHALL BE U.L. OR AGA APPROVED.
C.
MOTORS SHALL HAVE BUILT-IN OVERLOAD PROTECTION.
C.
MODULATING, LOW-LEAKAGE, OPPOSED BLADE OUTSIDE AIR DAMPERS.
5.
CO 0
Uj
o
EXHAUST HOOD. 1.
L
I-VU CONTROL SYSTEM (COORDINATE EXACT LOCATION IN FIELD WITH OWNER PRIOR TO INSTALLATION).
2. TOUCH PILOT (LCD DISPLAY CONTROLLER WITH TOUCH SCREEN).
COORDINATE EXACT LOCATION IN
47t,
FIELD WITH OWNER PRIOR TO INSTALLATION.
UNIT SHALL BE OF DOWNFLOW DESIGN AND SHALL HAVE 100% ECONOMIZER FUNCTION.
D.
UNITS SHALL HAVE ADJUSTABLE PITCH MOTOR SHEAVES AND MOTOR PULLEYS.
D.
POWER EXHAUST.
A.
E.
2-STAGE GAS HEATING AND SINGLE-STAGE COOLING (RTU-2, RTU-4).
E.
CARBON DIOXIDE (C0 2 ) SENSOR FOR OUTSIDE AIR CONTROL OVERRIDE, MOUNTED IN RETURN AIR DUCTWORK.
F.
2-STAGE GAS HEATING AND 2-STAGE COOLING (RTU-1, RTU-3).
UNIT SHALL HAVE 100% ECONOMIZER FUNCTION WITH DIFFERENTIAL ENTHALPY CONTROL
AND MINIMUM OUTSIDE AIR SETTING, AND BAROMETRIC RELIEF. 6.
COMFORTLINK CONTROLS: SYSTEM CONTROLLER WITH VISUAL SCROLLING MARQUEE DISPLAY (LCD DISPLAY CONTROLLER). COORDINATE EXACT LOCATION IN FIELD WITH OWNER PRIOR TO INSTALLATION.
UNIT SHALL BE SINGLE-WALL CONSTRUCTION.
G.
30% PLEATED FILTERS.
H.
ALUMINIZED STEEL HEAT EXCHANGER.
1.
J. K.
F.
DISCHARGE AIR SENSOR MOUNTED IN SUPPLY AIR DUCTWORK.
G.
HUMIDI-MIZER DEHUMIDIFICATION CONTROL.
H.
STAINLESS STEEL, DOUBLE-SLOPE DRAIN PAN WITH P-TRAP ASSEMBLY.
I.
FACTORY INSTALLED AND WIRED NON-FUSED DISCONNECT SWITCH.
J.
FACTORY INSTALLED AND WIRED 120 VOLT GFI DUPLEX RECEPTACLE.
k9o4ss\
31. SPACE TEMPERATURE SENSORS WITH OVERRIDE. 4 .PRIMARY AIR SENSORS.
WITH 4-2OmA OUTPUT.
5 .ACTUATOR
FOR OTHER EQUIPMENT.
6 .INTERLOCKS
COMPRESSORS SHALL BE HIGH EFFICIENCY DESIGN.
NEw0
CONTROLS ACCESSORIES:
ACCOUSTICAL ROOF CURB.
3.
WWW.EBSPE.COM
COPYRIGHT C 2016 ENGINEERED BUILDING SYSTEMS
10. INSTALLATION: UNITS SHALL BE ON MANUFACTURER PROVIDED, FULL PERIMETER, INSULATED ROOF CURB
A.
SUITABLE FOR THE ROOF DECK, INSULATION AND MEMBRANE (REFER TO ARCHITECTURAL DRAWINGS FOR ROOF CONSTRUCTION).
FACTORY INSTALLED REMOTE SHUTDOWN TERMINALS. B.
DOUBLE-SLOPE DRAIN PAN WITH P-TRAP ASSEMBLY.
ALL SERVICES TO THE UNIT SHALL ENTER WITHIN THE ROOF CURB.
NO SEPARATE ROOF
PENETRATIONS ARE ALLOWED.
UNIT MOUNTED CONTROLS WITH FACTORY MOUNTED CONTROL BOARD.
I
11. ACCEPTABLE MANUFACTURER'S - CARRIER, MON, McQUAY.
KEY PLAN
FAN
STATIC
MARK
E/F-1
E/F-2
AREA SERVED
JANITOR 34
TOILET 3, WOMENS TOILET 33,
CFM
125
PRESS. IN. WG EXT. 0.125
FAN COIL UNIT SCHEDULE
MANUFACTURER
GREENHECK
MODEL NO.
LD-80-VG
FAN TYPE
CENTRIFUGAL
DRIVE TYPE
DIRECT
MOTOR RPM
858
SONES
1.4
HP
1/10
VOLTS / PH 120/1/60
ROOF CURB SIZE
GPI-19-A12
OPERATING WEIGHT (LBS.) 75
MARK
SUPPLY AIR
AREA SERVED
CFM
FCU-1
TOILET 8, TOILET 10
450
0.25
GREENHECK
200
0.25
GREENHECK
LD-95-VG
CENTRIFUGAL
DIRECT
1162
4.6
1/6
120/1/60
GPI-19-A12
75
FCU-2
LD-90-VG
CENTRIFUGAL
DIRECT
1046
2.7
1/10
120/1/60
FAN -
3.
BUILT-IN POWER DISCONNECT.
4.
MOTORS SHALL HAVE BUILT-IN THERMAL OVERLOAD PROTECTION.
6.
75
MULTIPURPOSE ROOM 41
MULTIPURPOSE CONFERENCE ROOM 14
MOTORIZED, OPPOSED BLADE, LOW LEAKAGE ALUMINUM CONTROL DAMPERS (120V ACTUATOR).
B.
1" THICK FAN HOUSING INSULATION.
C.
VARI-GREEN EC MOTOR WITH MOUNTED POTENTIOMETER DIAL.
MBH
EAT 'F
LAT *F
MIN.
MBH
ROWS
SUPPLY FAN FLA
KW
WATTS
RPM
VOLTS / PH
MCA
SEER
OPERATING WEIGHT (LBS.)
do4Tlt1$W1
companies
RAV-SP18OUTUL CARRIER
(IN-CEILING)
19.0
80
20.5
208/1/60
18.8
67
construction Idevelopment
50
OWNER: RAV-SP180UTUL CARRI ER
(IN-CEILING)
19.0
80
20.5
208/1/60
18.8
67
50
4.
49 S. WATER STREET, LLC 500 SENECA ST - SUITE 508 BUFFALO, NY 14204 (71 6) 332-5959 tel. (716) 332-5968 fax.
ACCESSORIES:
1.
UNITS SHALL BE LISTED AND LABELED WITH THE ENERGY STAR LOGO.
2.
HEAT PUMP UNIT.
A.
LOW AMBIENT CONTROLS.
3.
UNIT SHALL HAVE:
B.
SERVICE VALVES WITH SCHRADER PORTS.
A.
R41OA REFRIGERANT.
C.
VIBRATION ISOLATION HANGERS.
B.
MINIMUM 20-GAUGE, FACTORY FINISHED, BONDERIZED STEEL CABINET.
5.
C.
3-SPEED CENTRIFUGAL MOTOR.
*NOTE: FAN COIL UNITS ARE POWERED BY IT'S ASSOCIATED CONDENSING UNIT POWER.
D.
FAN MOTOR THERMAL OVERLOAD PROTECTOR.
E.
MICROPROCESSOR CONTROLS.
F.
SELF-DIAGNOSTICS.
G.
CONDENSATE DRAIN PAN WITH CONDENSATE PUMP.
H.
INTERNAL TRANSFORMER FOR WALL MOUNTED 24V THERMOSTAT CONTROL.
I.
FREEZESTAT.
J.
FILTER TRACK WITH CLEANABLE FILTERS.
K.
ALL NECESSARY CEILING BRACKETS AS REQUIRED FOR A COMPLETE INSTALLATION.
ACCESSORIES: A.
(LOW) 600 (HIGH)
MODEL NO.
ELECTRIC HEAT
FAN COIL UNIT NOTES:
BACKWARD INCLINED ANODIZED ALUMINUM.
FLEX BUILDINNG OFFICE/MEDICAL/RETAIL
ACCEPTABLE MANUFACTURERS - CARRIER, LG, McQUAY.
49 S. WATER STREET
VILLAGE OF GOWANDA NEW YORK 14070
DRAWING TITLE
ROOF CURBS: A.
EACH EXHAUST FAN SHALL BE EQUIPPED WITH AN INSULATED, ANODIZED ALUMINUM ROOF CURB (0.080" MINIMUM THICKNESS), ALL WELDED JOINT CONSTRUCTION.
B.
ALL CURBS SHALL BE MINIMUM 1'-0" HIGH.
7.
INTERLOCK EXHAUST FAN (E/F-1) WITH ASSOCIATED ROOFOTP UNIT (RTU-2) OPERATION.
8.
INTERLOCK EXHAUST FANS (E/F-2 AND E/F-3) WITH ASSOCIATED ROOFOTP UNIT (RTU-3) OPERATION.
9.
GPI-19-A12
HOUSING - "LOW PROFILE" ANODIZED ALUMINUM WITH HINGED HOOD AND ALUMINUM BIRDSCREEN.
2.
5.
MANUFACTURER
(HIGH) 450
ROOF EXHAUST FAN NOTES:
1.
IN. WG EXT.
DX COOLING COIL
450 (LOW) 600
MENS TOILET 35
E/F-3
STATIC
PRESS.
-
ROOF EXHAUST FAN SCHEDULE
N0
HVAC SCHEDULES
CONDENSING UNIT SCHEDULE
MAXIMUM SONES TO BE 5.1 OR LESS, UNLESS OTHERWISE INDICATED.
REFRIGERANT CONNECTIONS
10. ACCEPTABLE MANUFACTURER'S - GREENHECK, COOK. MARK
AREA SERVED
MANUFACTURER
MODEL NO.
MBH
SUCTION
LIQUID
MOTOR RPM
HP
JOB NO.
1210
SCALE
NONE
DATE
4.15.2016
OPERATING VOLTS / PH
MCA
SEER
WEIGHT
(LBS.)
DRAWN BY CU-i
FCU-1
CU-2
FCU-2
CARRIER
CARRIER
RAV-SP180AT2-UL
RAV-SP1 80AT2-UL
19.0
19.0
1/2"
1/2"
1/4"
1/4"
208/1/60
VARIABLE
208/1/60
VARIABLE
17.0
17.0
20.5
100
20.5
100
CHECKED BY REVISIONS
CONDENSING UNIT NOTES: 1.
UNITS SHALL BE LISTED AND LABELED WITH THE ENERGY STAR LOGO.
2.
UNIT CABINET SHALL BE CONSTRUCTED OF HEAVY-GAUGE, CORROSION RESISTANT STEEL, WITH
9.
UNIT SHALL HAVE: A.
R41OA REFRIGERANT.
A.
LOW AMBIENT CONTROLS.
B.
LIQUID LINE SOLENOID VALVE.
B.
WINTER START CONTROL.
C.
LINE SET.
C.
CRANKCASE HEATER.
D.
FILTER DRIER.
D.
PE MOUNTING BASE (INSULATED PIPE RISER CURB).
E.
THERMOSTATIC EXPANSION VALVES.
E.
EQUIPMENT RAIL (MINIMUM
FACTORY POWDER COAT PAINT. 3.
UNIT CABINET SHALL BE EQUIPPED WITH COATED STEEL SAFETY WIRE GUARDS TO PROTECT CONDENSER FAN OPENING.
4.
UNIT ENCLOSURE SHALL CONTAIN FACTORY WIRING, PIPING, CONTROLS, COMPRESSOR, REFRIGERANT CHARGE, AND SPECIAL FEATURES.
5.
CONDENSER COIL SHALL BE CONSTRUCTED OF ALUMINUM FINS MECHANICALLY BONDED TO COPPER TUBES.
6.
CONDENSER FAN SHALL BE DIRECT DRIVE DIRECT DRIVE, PROPELLER TYPE, MULTIPLE SPEED OPERATION.
7.
COMPRESSORS SHALL BE VARIABLE SPEED (INVERTER) TYPE.
8.
MOTORS SHALL HAVE BUILT-IN THERMAL OVERLOAD PROTECTION.
10. ACCESSORIES: THIS IS A SINGLE SHEET OF A COHESIVE
SET OF CONSTRUCTION DOCUMENTS (INCLUDING DRAWINGS AND SPECIFICATIONS).
INTERPRETATION OF THE INFORMATION AS PRESENTED SHOULD BE BASED ON
1'-0" HIGH).
THE ENTIRE SET OF DOCUMENTS.
DRAWING NO.
11. ACCEPTABLE MANUFACTURERS - CARRIER, LG, McQUAY.
m.2 100% DESIGN SUBMISSION
CHAINTREUIL
150-1 8"0
125-2 10"o
8x6
STORAGE MECHANICAL
24
- -JAN STORAGE 37
348x6
200-2
---- 10Ox8
10x4 1-
150-1 8"0
1
125-2 10"0
148
8x6
S100-112x8 8-0
16x8
.
12x8
10x6
8x6 _ MEN TOILET II
39
1
,,150-1
14x8 1-1 1,
WOMENS TOILET 33
CA)
.
o
L
650-2 18x10
T
12x6
8x4MULTIPURPOSE ROOM 41 10x6 -FCU-1
r==
.
----
12"o
12"0
'
TO TU-05
-
S
12x6
F,
14-0
250-2
12x6
III
I
'~
j~
300-1 12"0
I
MIT OFFICE
12"o
T
12x6
F
/~
I
I
Il l
,I
el /A
r-l
H'
12x6
-8x6
10x6 I 'IlI
8x6-
300-1 12"0
I1
EK
A
WAITING
250-2 12"o
175-2 10-0
<
10x6 10-0
150-1 8"0
Q
-
TOILET 10
75-1 8"0
-_
I
1
1
'
16x10
z lII I
125-2
IIT -
OFFICE 7
OFFICE
I
8x6
8x6-
M-3
LLP
NEW YORK 14070 DRAWING TITLE
125-2 10"o
FLOOR PLAN HVAC DUCTWORK AND PIPING
TU-08 16x10
r-7
OFFICE
wA
150-1
8"0
12 THS
OFFICE
TO
TO
TU-08
RTU-4
--
JOB NO.
1210
SCALE
3/16" = 1'-0"
DATE
4.15.2016
11
I
I1
12x8
S10x6 DRAWN BY
150-1
125-2
150-1
150-1
8"O0
10 0r-
8"O0
8"0
FLOOR PLAN - HVAC DUCTWORK AND PIPING SCALE: 3/16" =
49 S. WATER STREET VILLAGE OF GOWANDA
13
EWH-1
1
FLEX BUILDINNG OFFICE/MEDICAL/RETAIL
OFFICE
1-
9
500 SENECA ST - SUITE 508 BUFFALO, NY 14204 (716) 332-5959 tel. (71 6) 332-5968 fax.
150-1
---
II
49 S. WATER STREET, LLC
8"0
OFFICE 6
16x12 FROM RTU-4 ON ROOF (1700 CFM)
150-1
80
4
10"0
-
I II100-2 10O0
m III II I 7*
OWNER:
88x6
125-1
I I
1
1325 CFM 24x12 OED W/ BIRDSCREEN -- 1x8
I
1 00
1. 1
1325
I
I
,] 8x6
150-1
-8x6
5
1'11 1111
8x6125-1 8"0
75-1 8..o
250-2 12"0
8x6
14x6
I I
2
15
8x6
-rTtt
lxe8
~~2221
8x6
1I
8x4
L 8x4
1 x
I
II__ 8x4-
8x6
OFFICE
li
TOILET
8
(1325 CFM)
12"0
L
O 8x4-
VEST
200-1 150-1 8"0
I
CORR
00I10x6 -2 I1EEI
Il
I
12x8-
IT-
10"0
F
I
--
ON ROOF
M
I I I 1 1I
II
71
1 0x8
1
75-1
125-1 8"O
MIT
E
100-2 1O0 24x10 TO RTU-4
>Iilk
8-0
8x4-\
construction I development
10 0 TU-07
I
100-3
175-2
I
I III
T
OFFICE 43
1
C
10"0 TO TU-02
17-
-4L
U
10x6
225-1
10x8
10x8
18x6-
III
DATA 5o
425-2 14"0
14x8
(200 CFM)
200-1 10"1
IIIII~
8."07
300-1 12"o
p
2. ON ROOF
-
I J II
150-1 8-0 10x6
10x10 TO E/F-3
[|1
V 12x6
225-1 10"0
8x6 II
00-3
'j47'I
II
14"o
12x6
IlI
I 8x4
21K
S.
TO
COmparies
150-2 10"-0
RECEPTION TU-04 DESK
'----L TU-05
40
12x6
8x6
AL
a~z~iis
16x12
19 ,
T
75-1 8"0
150-1 8"10
16x12
8X4 STORAGE
II----
III
1 10x6 650-2
-
TOILET 3
TU-02
18x10
hi
7
300-1
20x 10
42
300-1
I
F]
N0
12x8
1J4>
*
COMMUNITY ROOM
ZL
L 14x8
16
KEY PLAN
14x8
8x6 . MULTIPURPOSE CONFIRM
TREATMENT ROOM
-
2
4
675-2
175-1 8"0
8"-0
RTU-3
12x6
8"0
75-1
TO
1
8x6
F-lI-L|_JO
.- iiiiI
36x14 OED W/ BIRDSCREEN TO RTU-1
150-1 8"0
COORDINATE EXACT LOCATIONS OF TEMPERATURE SENSORS AND ITEMS.
8x6
125-1 8-0
2
14"o
2.
2
300-2
8x6
100-3
1 1I
125-1
~%
2875 CFM
ON ROOF (3625 CFM)
IU1II thlill IIn
PROVIDE VOLUME DAMPERS AT ALL BRANCH DUCTWORK TAPS.
INSTALLATION TO AVOID CONFLICTS WITH WALL MOUNTED ARCHITECTURAL OFFICE
--
1.
THERMOSTATS IN FIELD WITH ARCHITECT AND OWNER PRIOR TO
1Ox6450-2 14"0
GENERAL NOTES:
8x6 F-1
E
30
1
T
~'
--1
28x14 FROM RTU-1
II I
3 M-3
300-2 12"0
/
AV.
125-1
II
FCU-2
08 4 7 A PESs0
10x6
150-1 8"0
E
550-2 14"0
250-1
(2875 CFM)
2.2
TO FCU-2
-
14x8
8'
(450 CFM)
200-2 12"0
125-2 10O0
1
TU-03
o
34x26 FROM RTU-3 ON ROOF (5500 CFM)
18
150-1 8-0
8x6
I
N
OFFICE F
,
--
A
8"O
T
10x0 TO E/F-2 ON ROOF
8x6
300-1 12"0
8x6
"D
250-1 10O
14x8
DNFt
TO
2
E
36x12 TO RTU-1 ON ROOF
-E
16x10
RECORDS COPY / MAIL
150-1 8"0
E
I
I-
300-1 12"o
.,
EIIwTh lill
16x8-
150-1| 8-0
----- (
16x8
U11
125-1
4OF
(4375 CFM)
20
TU-03
&
24x10
wI
--- 7
F
8x6 lox~2
10-.0
TU-06 450-2 14"0
r--
250-1
TO
11 IN
10x8
TO FCU-1
s
12x6- 1
IIII
46x12 TO RTU-3
,
-
8x6 OFFICE 28 150-2 10-"0
-14x8
200-2 12"o
8x6
I r
OFFICE
8x6
175-1 8"0 OFFICE 29
150-2 10O0
150-1 8"0
K K
H 150-1 8-0
~1I
8x6
18x10 16x10
I
__
LI 14x8
[email protected]
WWWEBPE.COM
-7- -1
I
Ix
8xE
-
I1
14"o
L 28x16
8x6
WEBSITE:
ON ROOF
__
716) 836-9636
FAX: EMAIL:
TO TU-07 I-
175-1
luxo 10x6 225-1
8x4
ENGINEERED BUILDING SYSTEMS MECHANICAL / ELECTRICAL ENGINEERS
COPYRIGHT ( 2016 ENGINEERED BUILDING SYSTEMS
8x6
+- TU-04
-
'
300-1 12-0
14x8
8x6
no -
-
15-3
12x6
12x6-
x10
F-
EBS ENGINEERING, PC BUFFALO, NEW YORK 14228 PHONE: (716) 836-9600
7
-
175-3
TU-01
II11
ID
I
34x18
1 0"o
--
)
LI~
8"0
300-1 12-'0
L
-
10x6
14
5-1
TU-06-
I
Li
E
16x8
80
80-
| |
175-1
75-2
14x8-
r8
8"Olo
10x6
2
-
L
S
d
I,
-
39
35
ROOF, 5/8" REFRIGERANT SUCTION (RS) TO CONDENSING UNIT
46x18 OED W/ BIRDSCREEN
'
---
3/8" REFRIGERANT LIQUID (RL) FROM CONDENSING UNIT ON
www.cjsarchitects.com
4375 CFM
r A" TO RTU-2 I'
II
80
_
150-1 80
2.
REFER
-4050 RIDGE LEA ROAD
|
425-2
I
.
10"O
1" CONDENSATE DRAIN TO NEAREST SANITARY DRAIN. TO PLUMBING DRAWINGS FOR DRAIN LOCATION.
,
100----i~: 175-2
100
BREAKROOM 27
86
'
TU-01
21
10x6
|j_
If4f
fw1x12 x I 1 I
v
r
I
150-2
TO
xo86 -- 18X10 .
26
8x4
-8x6
175-1 8"0
U1111
STORAGE
8"O
CORR 31
E
266 Alexander Street Rochester, N.Y. 14607 585.244.3780 tel 585.244.1294 fax
1. FAMILY CARE
,
125~-1
L -- -- -- ---
M1T OFFICE
DDC PANEL
10-0
v
/
11 8x6
200-1
IN
1004
E-
-
11111
10"o
II
~
-
150-2
II II
I
Lii
-
225-1
I
I'll
F
9--
10x6
16x8
325-2
I
I I
KITCHEN 38
125-2~jj
-
10-.0
-J
NOTES: O
ON ROOF.
.
,
150-2
225-1
10-'0
8x4-
I I
36
225-1
OFFICE
/
ENTRY
25
2 M-3
/
II
716.852.1722 fax
8x6
OFFICE
ARCHITECTS,
75-1
'7
716.856.6448 tel
24x12 OED W/ BIRDSCREEN
-
100"
150-1 8"0
91
150-1 8"0
-
125-3
303 South Park Avenue Buffalo, N.Y. 14204
975 CFM
,
150-1
24x10 TO RTU-2 ON ROOF (975 CFM)
-
(125 CFM)
22
-
ON ROOF
STARK
D
SUPERVISOR
16x12 FROM RTU-2 ON ROOF (1225 CFM) ENTRY 150-1 23
)
C
10xlO TO E/F-1
-
B
A
JENSEN
125-2 -10O---
200-2 12"0
250-1 10-0
CHECKED BY REVISIONS
THIS IS A SINGLE SHEET OF A COHESIVE
SET OF CONSTRUCTION DOCUMENTS (INCLUDING DRAWINGS AND SPECIFICATIONS). INTERPRETATION OF THE INFORMATION
AS PRESENTED SHOULD BE BASED ON THE ENTIRE SET OF DOCUMENTS.
DRAWING NO.
M-3 100% DESIGN SUBMISSION
JENSEN
STARK ARCHITECTS, LLP
CHAINTREUIL 303 South Park Avenue Buffalo, N.Y. 14204 716.856.6448 tel 716.852.1722 fax
2
ROOF PLAN GENERAL NOTES:
M-4 1.
DIVISION 7 AND DIVISION 23 TO COORDINATE ALL ROOF OPENING, ROOF
PENETRATIONS, AND EQUIPMENT PAD INSTALLATIONS.
266 Alexander Street Rochester, N.Y. 14607 585.244.3780 tel 585.244.1294 fax
www.cjsarchitects.com
2.
DIVISION 7 TO CUT ALL ROOF OPENINGS.
3.
DIVISION 23 TO PROVIDE AND INSTALL ALL EQUIPMENT PADS AND CURBS.
ENGINEERED BUILDING SYSTEMS MECHANICAL I ELECTRIC ENGINEERS
4.
DIVISION 7 TO PROVIDE ROOF FLASHING AND SEALING OF ALL ROOF OPENINGS.
5.
COORDINATE LOCATION AND SPACING OF ROOF TRUSSES WITH DIVISION 6 FOR DUCTWORK PENETRATIONS PRIOR TO INSTALLING ROOF TRUSSES. DIVISION 6 SHALL ADJUST TRUSS SPACING TO ALLOW FOR A MINIMUM OF 2" CLEAR (ALL SIDES) AROUND OPENING AND PROVIDE ANY ADDITIONAL SUPPORTS REQUIRED TO SUPPORT DIVISION 15 EQUIPMENT.
BUFFALO, NEW YORK 14228 PHONE: (716) 836-9600 FAX: (716) 836-9636 E-MAIL:
[email protected]
a
EBS ENGINEERING, PC
10x10 FROM
BELOW (125 CFM)
RTU-2 (1400 LBS)
WWW.EBSPE.COM
WEBSITE:
COPYRIGHT C 2016 ENGINEERED BUILDING SYSTEMS
-
LN
0
,
4050 RIDGE LEA ROAD
E/F-1 (75 LBS)
I
l_-
IIl
0
L, F-7
16x12 TO BELOW (1225 CFM)
, '
0
x
0
I/- 1
N
'-+-46x12 FROM BELOW
(4375 CFM)
0
34x26 TO BELOW
Lu
(5500 CFM)
24x10 FROM BELOW (975 CFM)
10x10 FROM BELOW (450 CFM)
4OF
(oo
RTU-3
SS0
(2400 LBS)
K -I
I KEY PLAN
N0
E/F-2 (75 LBS)
VeiLiYijT*]
E 0 RTU-1 (1450 LBS)
construction Idevelopment
CU-2 (100 LBS)
CU-1 (100 LBS)
OWNER:
F1/4" REFRIGERANT LIQUID (RL) TO BELOW, 1/2" REFRIGERANT SUCTION (RS) FROM BELOW
I ,'II
companies
49 S. WATER STREET, LLC
1/4" REFRIGERANT LIQUID (RL) TO BELOW, 1/2" REFRIGERANT SUCTION (RS) FROM BELOW 0
28x14 TO BELOW
-
RTU-4 (1400 LBS)
(3625 CFM)
F7
500 SENECA ST - SUITE 508 BUFFALO, NY 14204 (71 6) 332-5959 tel. (716) 332-5968 fax.
36x12 FROM BELOW
(2875 CFM)
/
16x12 TO BELOW (1700 CFM)
-
R
FLEX BUILDINNG OFFICE/MEDICAL/RETAIL
24x10 FROM BELOW (1325 CFM)
49 S. WATER STREET
10x10 FROM BELOW (200 CFM)
VILLAGE OF GOWANDA NEW YORK 14070
E/F-3 (75 LBS)
,
DRAWING TITLE
-
ROOF PLAN HVAC DUCTWORK AND PIPING
I I I
I I
I I
I I I I I
I
I
I I I I I I I
JOB NO.
1210
SCALE
3/16" = 1'-i
DATE
4.15.2016
DRAWN BY
CHECKED BY REVISIONS
1
M-4
ROOF PLAN - HVAC DUCTWORK AND PIPING SCALE: 3/16"
=
THIS IS A SINGLE SHEET OF A COHESIVE
SET OF CONSTRUCTION DOCUMENTS (INCLUDING DRAWINGS AND SPECIFICATIONS).
INTERPRETATION OF THE INFORMATION AS PRESENTED SHOULD BE BASED ON
THE ENTIRE SET OF DOCUMENTS.
DRAWING NO.
M-4 100% DESIGN SUBMISSION
METAL SPIN-IN FITTING WITH VOLUME DAMPER
INSULATED DUCTWORK
DRAW BAND
NUMBER OF HANGERS
10'-O
1-1/2" x 1-1/2" x 1/8"
10'-O"
FASTEN TO ROOF TRUSSES) 60" MAXIMUM_
-
L1=1
EXTENSION DUCT COLLAR
--_ _
DUCT RING
(MINIMUM)
(REMOVABLE)
NECK SIZE
OF DUCT
ROUND
STRAP HANGERS
HANGERS
MAXIMUM SPACING
1/4" ROD
1" x 16 GAUGE
10'-0"
OUTER CONE
OUTER CONE
19" THRU 30"
1/4" ROD
1" x 16 GAUGE
10'-0"
DUCT HANGER DETAIL
"
'-U
www.cjsarchitects.com
OPPOSED BLADE
EBS ENGINEERING, PC
MANUAL VOLUME DAMPER
ENGINEERED BUILDING SYSTEMS MECHANICAL / ELECTRICAL ENGINEERS
4050 RIDGE LEA ROAD BUFFALO, NEW YORK 14228 PHONE: (716) 836-9600 FAX 716) 836-9636 E-MAIL: '
[email protected]
TAKE-OFF FITTING
LAST TAKEOFF FACE SIZE
3'-0" MINIMUM, STRAIGHT, HARD METAL DUCT
CEILING
WWW.EBSPE.COM
COPYRIGHT C 2016 ENGINEERED BUILDING SYSTEMS
------
INSTALL AFTER
TRANSITION
AIR FLOW
' I I
TEE
d-^
OF N 8
r0S D D.
AIR FLOW
o0O
~
TRUNK DUCT 6"
(1" MINIMUM ON TOP AND BOTTOM, SEAL ALL AROUND)
VOLUME DAMPER
PROVIDE ADJUSTABLE ELBOW RINGS FOR RECTANGULAR TO ROUND DUCT CONNECTION
FASTEN DUCT RING TO EXTENSION DUCT COLLAR WITH SHEET
WITH QUADRANT AND LOCK AND
o4719
Css\
STANDOFF COLLAR (TYPICAL)
0 -j
"TAP-OUT" EITHER SIDE OR BOTTOM OF DUCT; TOP "TAP-OUT" IS NOT ACCEPTABLE.
CEILING DIFFUSER CONNECTION DETAIL
RETURN GRILLE CONNECTION DETAIL
ROOFTOP UNIT
GASKET MATERIAL PRESSURE TREATED WOODEN NAILER
RIGID / THERMAL INSULATION
1~
CONDUIT CHASE
-11
I
EXHAUST FAN
4'
14 GAUGE GALVANIZED CAP
'ml
CLEANOUT PLUG SLOPE AT MINIMUM
1/4" PER FOOT
ACOUSTICAL LINING
AWAY FROM UNIT
I-
BIRDSCREEN
COUNTERFLASHING
EXHAUST FAN METAL CURB CAP
BONDING ADHESIVE
INSULATED ROOF CURB
-
"B"
TYPE "L" COPPER OR
SPLICING CEMENT
SCHEDULE 40 PVC PIPE
SPLASH
(TYPICAL)
3" MINIMUM
4'- 1'-C
ROOF-
LAP SEALANT
PAN HEAD WOOD SCREW
U
V
1
BLOCK
END CAPS & SEAMS TO BE CONTINUOUS
BONDING
WELDED
ADHESIVE
49 S. WATER STREET, LLC
DIMENSION
"A"
DIMENSION "B"
INSULATION
MATERIAL]
/z z/
1
FAN DISCHARGE STATIC PRESSURE PLUS 1"
FAN SUCTION STATIC
2-1/2"
/
,
'
BLOW-TH RU
ROOF DECK
ROOFCURB
PRESSURE TREATED WOOD BLOCKING
DRAW-THRU
TWO-POSITION MOTORIZED LOW
ROOF
STEEL ANGLE FRAMING
LEAKAGE BACKDRAFT DAMPER
PRESSURE PLUS 1"
EXHAUST DUCTWORK
SECURE CURB TO ROOF WITH
DAMPER ACTUATOR
SHEETMETAL SCREWS, LAG BOLTS, WITH ROOF CONSTRUCTION
1.
MINIMUM "A" OR "B" DIMENSION SHALL NOT BE LESS THAN 1".
2.
COPPER CONDENSATE DRAIN LINES SHALL BE INSULATED WITH MINIMUM 1-1/2" THICK ARMAFLEX II SLIP-ON TYPE INSULATION.
NOTES:
ROOFING SHALL EXTEND UP AND
1.
OVER TOP OF CURB
2.
THERMAL / ACOUSTICAL ROOF CURB DETAIL
3.
SECURE UNIT CURB CAP TO ROOF CURB WITH WITH SHEET METAL SCREWS 1'-0" ON CENTER ALL AROUND.
DISCHARGE CONDENSATE PIPING A MINIMUM OF 3'-0" AWAY FROM UNIT TO RSPLASH BLOCK ON ROOF (UNLESS PROHIBITED BY LOCAL CODE).
500 SENECA ST - SUITE 508 BUFFALO, NY 14204 (71 6) 332-5959 tel. (716) 332-5968 fax.
ROOF DECK
FLEX BUILDINNG OFFICE/MEDICAL/RETAIL
NOTES:
2"x6" PRESSURE TREATED WOOD BLOCKING BY DIVISION 7
construction I development
OWNER:
/
INSULATION
COmpanies
0
3"
ROOFING
rfZ~Iw
LVIILViIiI.]
FLASHING MEMBRANE
LAP SEALANT
1" MINIMUM-{
COIL CONFIGURATION
Vj_,
N0
KEY PLAN
COUNTERSUNK SHEETMETAL SCREW
COUNTER FLASH 14 GAUGE GALVANIZED BASE & BASE PLATE.
"A"
MEMBRANE FLASHING
ROOF MEMBRANE
2" x 6" PRESSURE TREATED NAILER
UNION
/
MOTOR
VAV BOX DETAIL
SUPPLY BRANCH TAKEOFF FITTING DETAIL
DISCONNECT SWITCH
L
STARK
266 Alexander Street Rochester, N.Y. 14607 585.244.3780 tel 585.244.1294 fax
WEBSITE:
I
INSTALLATION NOTES:
2.
SUPPLY AIR
FLEXIBLE CONNECTION
METAL SCREWS. UP THRU 18"
RECTANGULAR DUCT TRANSITION TO VAV AIR CONNECTION (SEE PLANS FOR SIZES)
EXHAUST BRANCH TAKEOFF FITTING DETAIL
45' ANGLE TAP COLLAR
1.
(SEE PLANS FOR SIZE)
,,
DUCT RING
I
HANGER SIZES FOR RECTANGULAR DUCT LONGEST DIMENSION
ROUND OR
DAMPER OPERATOR (REMOVABLE)
^'
FACE SIZE
~-1
TRANSITION TO DUCT
<
CEILING
GASKET
VOLUME BOX
JENSEN
-J_
2'-0"
DAMPER OPERATOR
VARIABLE AIR
(TYPICAL)
AND LOCK AND STANDOFF COLLAR (TYPICAL)
0
TO BE TIGHT AGAINST DUCT
L~J
-~
OPPOSED BLADE
VOLUME DAMPER WITH QUADRANT
OPEN END OPPOSED BLADE VOLUME DAMPER
VOLUME DAMPER
45' ANGLE TAP COLLAR (1" MINIMUM ON TOP AND BOTTOM, SEAL ALL AROUND) PROVIDE ADJUSTABLE ELBOW RINGS FOR RECTANGULAR TO ROUND DUCT CONNECTION
SUPPORT FROM STRUCTURE ABOVE
NECK SIZE
SELF TAPPING CADMIUM PLATED HEX
HEAD SHEET METAL SCREW, STRAPS
I
INTERNALLY LINED-
DUCTWORK
(5'-0" MAXIMUM LENGTH)
1
(DO NOT MOUNT TO ROOF DECK,
II I I I I
--1
INSULATED FLEXIBLE DUCT
1
HANGER STRAPS
I I I
r I
STEEL SUPPORT ROD
/
3/8" ROD
31" THRU 60"
303 South Park Avenue Buffalo, N.Y. 14204 716.856.6448 tel 716.852.1722 fax
6
'
1" x 16 GAUGE
AIR FLOW
-
1/4" ROD
UP THRU 30"
MAXIMUM SPACING
STRAP HANGERS
lIII I
(TYPICAL)
HANGER SIZES FOR ROUND DUCT ROUND HANGERS
rIIIIIII
AIR FLOW
CHAINTREUIL
'
LOAD RATED FASTENER WITH WASHERS
LAST TAKEOFF
'
INSULATED DUCTWORK
DUCT BAND (SAME SIZE AS HANGER STRAP)
DUCT DIAMETER
INSTALL AFTER
TRANSITION
(DO NOT MOUNT TO ROOF DECK, FASTEN TO ROOF TRUSSES)
ARCHITECTS, LLP
HANGER STRAP
-
I
14 GAUGE GALVANIZED BASE-
LEAD SHIELD ANCHOR
& BASE PLATE.
OR ANCHORS AS PER ROOF CONSTRUCTION
END
CAPS & SEAMS TO BE CONTINUOUS WELDED
49 S. WATER STREET
VILLAGE OF GOWANDA NEW YORK 14070
JOIST
SECURE ROOF CURB TO ROOF WITH SHEET METAL SCREWS, LAG BOLTS OR OTHER METHOD CONSISTENT WITH ROOF CONSTRUCTION AT 1'-0" ON CENTER ALL AROUND.
ROOFTOP UNIT CONDENSATE TRAP DETAIL
ROOF MOUNTED EXHAUST FAN DETAIL
ROOF MOUNTED EQUIPMENT RAIL DETAIL
DRAWING TITLE
HVAC DETAILS JOIST OR BEAM
LOCKNUTS STRAPS
THREADED HANGER ROD
LOW VOLTAGE WIRE
PIPE INSULATION
ADJUSTABLE CLEVIS HANGER
DUCT-SEAL ALL SERVICE PVC JACKET
T
I
I
[--2" OVERLAP
PIPE THERMISTOR CRIMP OR SOLDER LEADS
METAL PIPE SADDLE
END STAGGERED SEAM (SEAL WITH ADHESIVE) =
SCALE
NONE
DATE
4.15.2016
DRAWN BY
INSULATION PIPE
1210
TOR,
COVER -]
JOB NO.
CHECKED BY REVISIONS
JUNCTION BOX-I-
THREADED ROD PROVIDE 2 LOCKNUTS -
ADJUSTABLE CLEVIS HANGER PIPE INSULATION
, ~
METAL PIPE SADDLE
WALL THIS IS A SINGLE SHEET OF A COHESIVE
NOTE:
1.
MOUNT 4'-6" (MINIMUM) ABOVE FINISHED FLOOR, AND 4'-0" (MINIMUM) ABOVE FINISHED FLOOR FOR ADA APPLICATIONS
INTERPRETATION OF THE INFORMATION AS PRESENTED SHOULD BE BASED ON
THE ENTIRE SET OF DOCUMENTS.
ALL PIPING EXPOSED IN OCCUPIED AREAS SHALL BE JACKETED WITH MATERIALS SUITABLE FOR PAINTING.
DRAWING NO.
INSULATION SHIELD
SINGLE PIPE HANGER DETAIL
SET OF CONSTRUCTION DOCUMENTS (INCLUDING DRAWINGS AND SPECIFICATIONS).
PIPING INSULATION JACKET DETAIL
THERMOSTAT / TEMPERATURE SENSOR MOUNTING DETAIL
M-5 100% DESIGN SUBMISSION
12431
PLUMBING DRAWING NOTES:
HVAC DRAWING NOTES:
HVAC LEGEND AND NOTES