Written dimensions on these drawings shall have precedence over scaled dimensions. Contractor shall verify and be responsible for all dimensions and conditions on the job. OB+Architecture Inc. must be notified immediately in writing of any variation from the dimensions and conditions shown on these drawings. Field verify all conditions prior to laying out or fabricating associated work. Bring to the architect's attention any deviation from designed conditions and field conditions prior to ordering materials and installing work, and cooperate with architect to modify such conditions at no additional cost to the owner, architect or architect's consultants. Shop details must be submitted to the architect's office and reviewed by the architect prior to ordering materials, fabrication and delivery to the job site, unless otherwise provided for under the specific contractual agreement between the architect and client. OB+Architecture Inc. expressly reserves its common law copyright and other property rights in these documents. These documents are not to be reproduced, changed, or copied in any form or manner whatsoever, nor are they to be assigned to a third party without first obtaining the written permission and written consent of OB+Architecture Inc. In the event of unauthorized use of these documents by a third party, the third party shall hold OB+Architecture Inc. harmless and agrees to remunerate OB+Architecture Inc. for such use in an amount equal to the original fee for the original documents, plus legal fees, court costs, collection fees and other costs.

AIR CONDITIONING UNIT SCHEDULE DX. COOLING COIL DATA ELECTRIC HEATING COIL

FAN DATA

AC #

OUTSIDE AIR

AREA SERVED

CFM

MIN EXT. E.S.P.

MBH TOT

HP

MBH SENS

KW

ELECTRICAL

STAGES

TOTAL MCA

MOCP

VOLTS

PHASE

AC - 1

LOBBY EXAM RECEPTION

180

2000

1

60

9

1

37.5

45

208

3

AC - 2

TREATMENT

200

2400

2

72

13.5

1

54.8

60

208

3

AC - 3

KENNEL

200

1000

0.5

30

7.5

1

69

70

208

1

AC - 4

DOG WARD

295

9.7

12

15

120

AC - 5

CAT WARD

295

9.7

12

15

120

NOTES:

EER

SEER MANUFACTURER/MODEL

13

WEIGHT

SEE NOTE #

TRANE TSC060

1, 3 - 9

TRANE TSC072

1, 4, 6 - 12

13

TRANE 4TCC3030

1, 3 - 9

1

14.3

FRIEDRICH MO9YF

2, 7, 8

1

14.3

FRIEDRICH MO9YF

2, 7, 8

11.3

ROOF CAP

CANT STRIP BY GENERAL CONTRACTOR

PREFAB 18 GA GALV. STL. STRUCT. ROOF CURB.

ROOFING BY GENERAL CONTRACTOR

WOOD NAILER INSULATION

1. 2.

PACKAGED SLAB-MOUNTED A/C UNIT WITH HORIZONTAL DUCT CONNECTIONS DUCTLESS SPLIT SYSTEM HEAT PUMP WITH 9.7 MBH HTG, 8.2 HSPF, WASHABLE FILTERS, WIRELESS REMOTE, AND R410A. OUTDOOR AIR DUCTED FROM AC-2. 3. STANDARD MOTOR AND DRIVE 4. MOTORIZED OUTDOOR AIR DAMPER 5. 1" 30% EFFICIENT PLEATED FILTERS WITH ACTIVATED CARBON EQUAL TO DAYTON RELIABLE 6. FOIL FACED INSULATION 7. SINGLE POINT WIRING KIT 8. NEC DISC. BY ELECTRICAL TRADE 9. 7 DAY, TIME OF DAY PROGRAMMABLE THERMOSTAT WITH OVER-RIDE 10. OVERSIZED MOTOR AND DRIVE 11. 2" 30% EFFICIENT PLEATED FILTERS WITH ACTIVATED CARBON EQUAL TO DAYTON RELIABLE 12. PROVIDE UNIT-MOUNTED SA DUCT SMOKE DETECTOR WITH RELAY

PT WOOD BLOCK 2" x 2" x 1/4" SUPPORT ANGLECOORDINATE LOCATIONS AND OPENING SIZES WITH STRUCTURE INSTALLATION COMPLIES WITH 120 MPH WIND LOAD PER FBC

NOTES:

1. COORDINATE ROOF PENETRATIONS AND WATER PROOFING WITH GENERAL CONTRACTOR.

VENTILATOR SCHEDULE

1

ROOF CURB DETAIL

5

SCALE: NO SCALE

ADVANCE REVIEW

issued:

A/C UNIT ANCHORAGE

21 JULY 2008

revised:

SCALE: NO SCALE

ROOF / METAL DECK

ROOF CAP WOOD

3 8"

WASHER

STRAP TO STRUCT.

3 8"

x 5" LAG BOLT THRU UNIT RAIL INTO WOOD ON CURB @ 6" ON CENTER

NUT, BOLT, WASHER

2" WIDE STRAP (GALV. STEEL)

CURB

ROOF

NOTES: 1. 2. 3. 4. 5. 6. 7. 8. 9.

ROOF CURB BIRD SCREEN ALL-ALUMINUM WALL PROP. FAN WITH OSHA INLET GUARD AND 120 VAC MOTOR-OPERATED SHUTTER STARTER AND DISCONNECT BY ELECTRICAL TRADE CEILING EXHAUST FAN W / ALUMINUM CEILING GRILLE, BACKDRAFT DAMPER & SPEED CONTROLLER INTERLOCK WITH LIGHT SWITCH CONTROL WITH ON/OFF SWITCH INTERLOCK BOTH OUTDOOR AIR MOTOR-OPERATED DAMPERS, EF-1, EF-2, AND WALL SWITCH GRAVITY EXHAUST VENTILATOR

2

ROOF CAP - CURB TIE DOWN DETAIL SCALE: NO SCALE

6

50% FACTOR FOR EVENTS LESS THAN 3 HR

TOTAL OA REQD

SCALE: NO SCALE

AHU & A/C

OUTDOOR AIR (OA) CALCULATIONS RECEPTION / WAITING @ 20 CFM

DUCT HANGER DETAIL CLEANOUT

SEAL SPIN-IN FITTING WITH MASTIC.

VETERINARY STAFF @ 20 CFM

ROUND (UNINSULATED)

GALV. STEEL

4" (A/C UNITS) 3" (AHUs)

SPIN-IN FITTING WITH VOLUME DAMPER (WHERE SHOWN ON PLAN)

TOTAL OA SPEC

MIN. 1.5" WIDE GALV. STRAP

AC - 1

CENTRAL FLORIDA

CLEANOUT

ANIMAL HOSPITAL 1201 ALAFAYA TRAIL

address:

NECK MOUNTED VOLUME DAMPER (WHERE SHOWN ON PLANS)

AC - 2

OVIEDO, FLORIDA

AC - 3

32765 CEILING RIGID DUCT (LOW PRESSURE)

project number:

SEE PLAN FOR ROUTING

DIFFUSER

2007-12

DIFFUSER, REGISTER, GRILLE SCHEDULE FACE SIZE

NECK SIZE

TITUS MODEL NO. SEE NOTE NO.

3

DIFFUSER DETAIL

7

SCALE: NO SCALE

CONDENSATE DRAIN DETAIL SCALE: NO SCALE

MECHANICAL ENGINEER A. PETER TANKEL, P.E. 702 DENTON ROAD WINTER PARK, FL 32792 PE 41231

ROOF/METAL DECK

2" WIDE GALV. STEEL STRAP TO STRUCTURE GALV. STEEL DUCT

BAR JOIST (TYP) #10 SELF TAPPING SHEET METAL SCREWS THROUGH DUCT WALL

MIN. #12 GALV. STEEL WIRE

title:

HVAC DETAILS, CALCULATIONS & SCHEDULES

R-6 (INSULATED) 2" THICK 1# DENSITY F.G. DUCT WRAP WITH GLASS FAB AND MASTIC JOINTS

NOTES: 1. 2. 3. 4. 5. 6. 7.

COORDINATE FRAME TYPE WITH ARCHITECT SPECIFIED CEILING / WALL TYPE. STEEL CONSTRUCTION, OFF WHITE FINISH. PROVIDE MANUAL VOLUME DAMPER ACCESSIBLE THROUGH NECK. ALUMINUM CONSTRUCTION, OFF WHITE FINISH. RETURN AIR FILTER GRILLE WITH 1" T/A FIBERGLASS MEDIA. SQUARE TO ROUND INSULATED ADAPTOR. SIGHT-PROOF DOOR GRILLE.

2" WIDE GALV. CHANNEL 1.5" DUCTBOARD R-6.0 (GLASS FAB/ MASTIC)

drawn:

reviewed:

date:

4

TRAPEZE DETAIL SCALE: NO SCALE

8

TRAPEZE DETAIL

lman:

SCALE: NO SCALE sheet setup:

JLP OB / RG 21 JULY 2008

PS-M3.1 MOJA-HVAC