Written dimensions on these drawings shall have precedence over scaled dimensions. Contractor shall verify and be responsible for all dimensions and conditions on the job. OB+Architecture Inc. must be notified immediately in writing of any variation from the dimensions and conditions shown on these drawings. Field verify all conditions prior to laying out or fabricating associated work. Bring to the architect's attention any deviation from designed conditions and field conditions prior to ordering materials and installing work, and cooperate with architect to modify such conditions at no additional cost to the owner, architect or architect's consultants. Shop details must be submitted to the architect's office and reviewed by the architect prior to ordering materials, fabrication and delivery to the job site, unless otherwise provided for under the specific contractual agreement between the architect and client. OB+Architecture Inc. expressly reserves its common law copyright and other property rights in these documents. These documents are not to be reproduced, changed, or copied in any form or manner whatsoever, nor are they to be assigned to a third party without first obtaining the written permission and written consent of OB+Architecture Inc. In the event of unauthorized use of these documents by a third party, the third party shall hold OB+Architecture Inc. harmless and agrees to remunerate OB+Architecture Inc. for such use in an amount equal to the original fee for the original documents, plus legal fees, court costs, collection fees and other costs.
AIR CONDITIONING UNIT SCHEDULE DX. COOLING COIL DATA ELECTRIC HEATING COIL
FAN DATA
AC #
OUTSIDE AIR
AREA SERVED
CFM
MIN EXT. E.S.P.
MBH TOT
HP
MBH SENS
KW
ELECTRICAL
STAGES
TOTAL MCA
MOCP
VOLTS
PHASE
AC - 1
LOBBY EXAM RECEPTION
180
2000
1
60
9
1
37.5
45
208
3
AC - 2
TREATMENT
200
2400
2
72
13.5
1
54.8
60
208
3
AC - 3
KENNEL
200
1000
0.5
30
7.5
1
69
70
208
1
AC - 4
DOG WARD
295
9.7
12
15
120
AC - 5
CAT WARD
295
9.7
12
15
120
NOTES:
EER
SEER MANUFACTURER/MODEL
13
WEIGHT
SEE NOTE #
TRANE TSC060
1, 3 - 9
TRANE TSC072
1, 4, 6 - 12
13
TRANE 4TCC3030
1, 3 - 9
1
14.3
FRIEDRICH MO9YF
2, 7, 8
1
14.3
FRIEDRICH MO9YF
2, 7, 8
11.3
ROOF CAP
CANT STRIP BY GENERAL CONTRACTOR
PREFAB 18 GA GALV. STL. STRUCT. ROOF CURB.
ROOFING BY GENERAL CONTRACTOR
WOOD NAILER INSULATION
1. 2.
PACKAGED SLAB-MOUNTED A/C UNIT WITH HORIZONTAL DUCT CONNECTIONS DUCTLESS SPLIT SYSTEM HEAT PUMP WITH 9.7 MBH HTG, 8.2 HSPF, WASHABLE FILTERS, WIRELESS REMOTE, AND R410A. OUTDOOR AIR DUCTED FROM AC-2. 3. STANDARD MOTOR AND DRIVE 4. MOTORIZED OUTDOOR AIR DAMPER 5. 1" 30% EFFICIENT PLEATED FILTERS WITH ACTIVATED CARBON EQUAL TO DAYTON RELIABLE 6. FOIL FACED INSULATION 7. SINGLE POINT WIRING KIT 8. NEC DISC. BY ELECTRICAL TRADE 9. 7 DAY, TIME OF DAY PROGRAMMABLE THERMOSTAT WITH OVER-RIDE 10. OVERSIZED MOTOR AND DRIVE 11. 2" 30% EFFICIENT PLEATED FILTERS WITH ACTIVATED CARBON EQUAL TO DAYTON RELIABLE 12. PROVIDE UNIT-MOUNTED SA DUCT SMOKE DETECTOR WITH RELAY
PT WOOD BLOCK 2" x 2" x 1/4" SUPPORT ANGLECOORDINATE LOCATIONS AND OPENING SIZES WITH STRUCTURE INSTALLATION COMPLIES WITH 120 MPH WIND LOAD PER FBC
NOTES:
1. COORDINATE ROOF PENETRATIONS AND WATER PROOFING WITH GENERAL CONTRACTOR.
VENTILATOR SCHEDULE
1
ROOF CURB DETAIL
5
SCALE: NO SCALE
ADVANCE REVIEW
issued:
A/C UNIT ANCHORAGE
21 JULY 2008
revised:
SCALE: NO SCALE
ROOF / METAL DECK
ROOF CAP WOOD
3 8"
WASHER
STRAP TO STRUCT.
3 8"
x 5" LAG BOLT THRU UNIT RAIL INTO WOOD ON CURB @ 6" ON CENTER
NUT, BOLT, WASHER
2" WIDE STRAP (GALV. STEEL)
CURB
ROOF
NOTES: 1. 2. 3. 4. 5. 6. 7. 8. 9.
ROOF CURB BIRD SCREEN ALL-ALUMINUM WALL PROP. FAN WITH OSHA INLET GUARD AND 120 VAC MOTOR-OPERATED SHUTTER STARTER AND DISCONNECT BY ELECTRICAL TRADE CEILING EXHAUST FAN W / ALUMINUM CEILING GRILLE, BACKDRAFT DAMPER & SPEED CONTROLLER INTERLOCK WITH LIGHT SWITCH CONTROL WITH ON/OFF SWITCH INTERLOCK BOTH OUTDOOR AIR MOTOR-OPERATED DAMPERS, EF-1, EF-2, AND WALL SWITCH GRAVITY EXHAUST VENTILATOR
2
ROOF CAP - CURB TIE DOWN DETAIL SCALE: NO SCALE
6
50% FACTOR FOR EVENTS LESS THAN 3 HR
TOTAL OA REQD
SCALE: NO SCALE
AHU & A/C
OUTDOOR AIR (OA) CALCULATIONS RECEPTION / WAITING @ 20 CFM
DUCT HANGER DETAIL CLEANOUT
SEAL SPIN-IN FITTING WITH MASTIC.
VETERINARY STAFF @ 20 CFM
ROUND (UNINSULATED)
GALV. STEEL
4" (A/C UNITS) 3" (AHUs)
SPIN-IN FITTING WITH VOLUME DAMPER (WHERE SHOWN ON PLAN)
TOTAL OA SPEC
MIN. 1.5" WIDE GALV. STRAP
AC - 1
CENTRAL FLORIDA
CLEANOUT
ANIMAL HOSPITAL 1201 ALAFAYA TRAIL
address:
NECK MOUNTED VOLUME DAMPER (WHERE SHOWN ON PLANS)
AC - 2
OVIEDO, FLORIDA
AC - 3
32765 CEILING RIGID DUCT (LOW PRESSURE)
project number:
SEE PLAN FOR ROUTING
DIFFUSER
2007-12
DIFFUSER, REGISTER, GRILLE SCHEDULE FACE SIZE
NECK SIZE
TITUS MODEL NO. SEE NOTE NO.
3
DIFFUSER DETAIL
7
SCALE: NO SCALE
CONDENSATE DRAIN DETAIL SCALE: NO SCALE
MECHANICAL ENGINEER A. PETER TANKEL, P.E. 702 DENTON ROAD WINTER PARK, FL 32792 PE 41231
ROOF/METAL DECK
2" WIDE GALV. STEEL STRAP TO STRUCTURE GALV. STEEL DUCT
BAR JOIST (TYP) #10 SELF TAPPING SHEET METAL SCREWS THROUGH DUCT WALL
MIN. #12 GALV. STEEL WIRE
title:
HVAC DETAILS, CALCULATIONS & SCHEDULES
R-6 (INSULATED) 2" THICK 1# DENSITY F.G. DUCT WRAP WITH GLASS FAB AND MASTIC JOINTS
NOTES: 1. 2. 3. 4. 5. 6. 7.
COORDINATE FRAME TYPE WITH ARCHITECT SPECIFIED CEILING / WALL TYPE. STEEL CONSTRUCTION, OFF WHITE FINISH. PROVIDE MANUAL VOLUME DAMPER ACCESSIBLE THROUGH NECK. ALUMINUM CONSTRUCTION, OFF WHITE FINISH. RETURN AIR FILTER GRILLE WITH 1" T/A FIBERGLASS MEDIA. SQUARE TO ROUND INSULATED ADAPTOR. SIGHT-PROOF DOOR GRILLE.
2" WIDE GALV. CHANNEL 1.5" DUCTBOARD R-6.0 (GLASS FAB/ MASTIC)
drawn:
reviewed:
date:
4
TRAPEZE DETAIL SCALE: NO SCALE
8
TRAPEZE DETAIL
lman:
SCALE: NO SCALE sheet setup:
JLP OB / RG 21 JULY 2008
PS-M3.1 MOJA-HVAC
sheet number: