Ref: MKTG/GE-AUS/ST-1408/09-10/VK
November 29, 2009
M/s. GE C&I 125 Long Street, Smithfield, NSW,2164 Australia Kind Attention: Mr.Ali Janani Equipment Engineer Dear Sir, Sub: Offer for supply of Distribution Transformers –A/c-PERDAMAN, COLLIE UREA Ref: Your E –mail Enquiry dated 17.11.2009. ******** We refer to your above email enquiry and are pleased to submit our offer for Oil Filled Conventional Type Distribution Transformer as under:SCOPE OF SUPPLY:Our scope is limited to design, manufacture, assembly, testing at our Works and supply of transformer on FOB, Chennai basis. PRICES:DISTRIBUTION TRANSFORMERS SL. NO. 1.
ITEM DESCRIPTION
UNIT EX-WORKS CHENNAI PRICE IN US$
3750KVA, 13.2/3.3KV Oil Filled Conventional Type Distribution Transformer confirming to IEC-76.
45390
2.
2500KVA, 13.2/0.415KV Oil Filled Conventional Type Distribution Transformer confirming to IEC-76.
36155
3.
2000KVA, 13.2/0.415KV Oil Filled Conventional Type Distribution Transformer confirming to IEC-76.
30610
4.
1500KVA, 13.2/0.415KV Oil Filled Hermetically Sealed Type Distribution Transformer confirming to IEC-76.
25546
POWER TRANSFORMERS SL. NO. 1. 2.
ITEM DESCRIPTION
UNIT EX-WORKS CHENNAI PRICE IN US$
7500KVA, 13.2/3.3KV Oil Filled Conventional Type Distribution Transformer confirming to IEC-76.
89170
12000/15000KVA, 13.2/3.3KV Oil Filled Conventional Distribution Transformer confirming to IEC-76.
Type
162685 ..2...
INDOTECH TRANSFORMERS LIMITED. DP 36, SIDCO Industrial Estate, Thirumazhisai, Chennai – 600 124. Phone: +91 (0) 44 - 30289830 / 833 /836 Fax: +91 (0) 44 - 30289874 Website: http://www.indo-tech.com/
..2... NOTE:Freight, sea transport and insurance including marine insurance will be extra at actual to your account. The prices quoted for transformers do not include sea worthy packing charges and the same will be packed as per our standard practice suitable for containerization. The accessories mentioned in our offer will be of reputed makes available in India and none will be of qualitrol type. We have quoted for FOB, CHENNAI only. The above quoted price is subject to IEEMA Price Variation clause applicable for exports without any ceiling with base date 01.10.2009.
Delivery (Ex-Works):Our delivery will be 4 (Four) months from the date of final drawing along with unconditional manufacturing clearance at our end The drawings will be submitted within 3 weeks from the date of receipt of your techno-commercial clear Purchase Order along with advance payment. Please note that the above delivery is given in good faith and is not guaranteed under any penalty. The above delivery is subject Force Majeure conditions. Payment Terms:35% value of the order as advance and balance payment has to be made by way of Letter of Credit at sight drawn in our favour negotiable against shipping documents L/C shall be opened with in one week of approval of drawings. L/C opening charges, bank interest, etc. will be to your account. Guarantee:Our equipment offered is guaranteed for satisfactory operation for a period of 12 months from the date of receipt of materials at the final destination or 18 months from the date of shipment, whichever is earlier. Packing:The transformer tank will be despatched in an unpacked condition and the accessories will be despatched duly packed in wooden crates/boxes, suitable for containerization. The cost of stuffing is included in our offer. The prices quoted for transformers do not include sea worthy packing charges. Inspection:Routine tests only as per IEC 76 will be conducted at our works, free of cost. Type Tests, if any required can be conducted at extra charges only. In case if any inspection is required by you (or) your approved Agency before despatch, we are agreeable for the same, for which prior notice to be given. All expenditure towards inspection will be to your account. Validity:30 days from November 29, 2009. We now look forward to receive your valued order, which shall be executed to your full satisfaction. Thanking you and assuring you of best services at all times. Yours faithfully, For INDO TECH TRANSFORMERS LIMITED V. KARTHIKEYAN SENIOR MANAGER – MARKETING INDOTECH TRANSFORMERS LIMITED. DP 36, SIDCO Industrial Estate, Thirumazhisai, Chennai – 600 124. Phone: +91 (0) 44 - 30289830 / 833 /836 Fax: +91 (0) 44 - 30289874 Website: http://www.indo-tech.com/
ACCESSORIES :
Rating & Diagram Plate Earthing Terminals Lifting Lugs Magnetic Oil Level Gauge Bottom Filter cum Drain Valve with Plug Top Filter Valve with Plug Pulling Lugs Oil Conservator with Drain Plug, Filling Hole with Cap Thermometer Pocket Silica gel Breather Bi-Directional Flat Rollers Pressure Relief Valve Air Release Plug OFF CIRCUIT TAP SWITCH Oil Temperature Indicator Winding Temperature Indicator Marshalling Box Neutral CT Magnetic Oil Gauge Pressure Relief Device Buchholz Relay HV- Cable Box LV- Cable Box Paint – Epoxy Paint
Oil – First Filling of Transformer Oil
For INDO TECH TRANSFORMERS LIMITED
V. KARTHIKEYAN SENIOR MANAGER – MARKETING
GUARANTEED TECHNICAL PARTICULARS FOR POWER TRANSFORMERS Rating – KVA Quantity – Nos. Voltage Ratio – KV (HV / LV) Type Windings Temp. Rise (Oil / Windings) Cooling Tap Changer Tapping Range Vector Group Connection Terminal Arrangement HV LV Losses & Impedance No Load Loss (KW) Load Loss (KW) Impedance (%) Approximate Weights(Kgs) Core and Winding Tank and Fittings Oil Total Oil Quantity(Ltr) Overall Dimensions : Length Breadth Height
7500 2
12000/15000 1
13.2/3.3 OIL IMMERSED – CONVENTIONAL Copper 55/65 Deg C ONAN ONAN/ONAF OFF CIRCUIT TAP SWITCH +5% to -5% in steps of 2.5% Dyn11 Delta /Star Cable Box Cable Box 7.5 50 8.35
11 80 8.35
8400 5400 3060 16860 3600
15100 8900 5200 26100 6200
3600 3700 3500
4000 3050 4000
Note: 1. The above quoted losses and impedance are subject to tolerance as per IEC-76 2. The weights and dimensions quoted above are approximate only. For INDO TECH TRANSFORMERS LIMITED V. KARTHIKEYAN SENIOR MANAGER – MARKETING
GUARANTEED TECHNICAL PARTICULARS FOR DISTRIBUTION TRANSFORMERS Rating – KVA Quantity – Nos. Voltage Ratio – KV (HV / LV) Type Windings Temp. Rise (Oil / Windings) Cooling Tap Changer Tapping Range Vector Group Connection Terminal Arrangement HV LV Losses & Impedance No Load Loss (KW) Load Loss (KW) Impedance (%) Approximate Weights(Kgs) Core and Winding Tank and Fittings Oil Total Oil Quantity(Ltr) Overall Dimensions : Length Breadth Height
3750 2500 2000 1500 1 1 4 2 13.2/3.3 132./0.415 OIL IMMERSED – CONVENTIONAL HERMATICALLY SEALED Copper 55/65 ONAN OFF CIRCUIT TAP SWITCH +/-5% IN STEPS OF 2.5% Dyn11 Delta/Star Cable Box Cable Box 3.2 32 7.15
2.4 24.5 6.25
2.1 20.5 6.25
1.7 16 6.25
4000 3000 1615 8615 1900
2900 2300 1360 6560 1600
2500 2000 1190 5690 1400
2000 1700 935 4635 1100
3150 2700 3000
2800 2800 2900
2800 3250. 2850
2350 3000 2000
Note: 1. The above quoted losses and impedance are subject to tolerance as per 2. The weights and dimensions quoted above are approximate only. For INDO TECH TRANSFORMERS LIMITED V. KARTHIKEYAN SENIOR MANAGER – MARKETING
IEC-76.
OUR OBSERVATIONS ON YOUR TECHNICAL SPECIFICATION Clause 7.3.5: Poly Chlorinated Bi-Phenyls (PCBs) will be applicable only for TRANSFORMER OIL Test Certificate from Supplier will be submitted later. 2. Clause .7.8.5: PRV with trip contacts only can be supplied. 1.
For INDO TECH TRANSFORMERS LIMITED