FAMILIARIZATION OF ELECTRICAL DISTRIBUTION LINE EQUIPMENT ENGR. ROMEO F. CEDIÑO, JR. Manager For Technical Services Department SORECO II
GENERAL DEFINITION: TRANSFORMER IS A DEVICE THAT TRANSFERS ELECTRICAL ENERGY FROM ONE ELECTRIC CIRCUIT TO ANOTHER WITHOUT A CHANGE IN FREQUENCY, DOES SO BY THE PRINCIPLE OF ELECTROMAGNETIC INDUCTION AND HAS ELECTRIC CIRCUITS THAT ARE LINKED BY A COMMON MAGNETIC CIRCUIT.
POWER TRANSFORMER • BY TYPE (SUBSTATION POWER TRANSFORMER): – STEP UP – STEP DOWN
* THE POWER TRANSFORMER IS CONSIDERED AS THE “HEART” OF THE TRANSMISSION AND DISTRIBUTION SYSTEM
POWER CIRCUIT BREAKERS
POWER CIRCUIT BREAKER DEFINITION: AN ELECTRICAL DEVICE CAPABLE OF: 1. CARRYING NORMAL LOAD CURRENT TO WHICH IT IS DESIGNED 2. MAKING AND BREAKING NORMAL LOAD CURRENT (CAPABLE OF MULTIPLE INTERRUPTION OF NORMAL LOAD CURRENT) 3. INTERRUPTING RATED FAULT CURRENT TO WHICH IT IS DESIGNED (CAPABLE OF MULTIPLE INTERRUPTION OF RATED FAULT CURRENT) 4. WITHSTANDING MOMENTARY FAULT CURRENT
MAIN FUNCTIONS/PURPOSES OF POWER CIRCUIT BREAKERS 1. INTERRUPT FAULT CURRENT AS QUICKLY AS POSSIBLE 2. ISOLATE AFFECTED CIRCUITS TO MINIMIZE DAMAGE TO OTHER EQUIPMENT 3. ENSURES CONTINUITY OF SERVICE
TYPES OF CIRCUIT BREAKER CLASSIFICATION ACCORDING TO ARC QUENCHING MEDIUM 1. OIL CIRCUIT BREAKER (OCB) 2. AIR CIRCUIT BREAKER (ACB) 3. GAS CIRCUIT BREAKER (GCB) 4. VACUUM CIRCUIT BREAKER (VCB)
TYPES OF CIRCUIT BREAKER CLASSIFICATION ACCORDING TO OPERATING MECHANISM 1. MAGNETIC OR MAGNEBLAST 2. PNEUMATIC 3. SPRING OPERATED 4. HYDRAULIC
METHODS OF ARC DISTINGUISHING 1. OIL CIRCUIT BREAKER A. COOLING THE ARC BY PUMPING OIL INSIDE THE INTERRUPTER B. ABSORBS HEAT BROUGHT ABOUT BY THE ARC C. GOOD INSULATING MEDIUM WHICH PREVENTS RESTRIKING OF INTERRUPTED CURRENT 2. AIR CIRCUIT BREAKER A. BLOWING OF AIR TO THE ARC TOWARDS THE ARC CHUTES 3. GAS CIRCUIT BREAKER A. PUFFING SF6 GAS TO THE INTERRUPTER AND ABSORBING HEAT BROUGHT ABOUT BY THE ARC. B. HIGH DIELECTRIC STRENGTH OF SULFUR HEXAFLOURIDE (SF6) PREVENTS RESTRIKING OF INTERRUPTED CURRENT. 4. VACUUM CIRCUIT BREAKER A. AIR WHICH CONTRIBUTES TO ARC PRODUCTION IS ABSENT, THUS NO ARC IS PRODUCED DURING CURRENT INTERRUPTION.
SAMPLE OF A TYPICAL WITHDRAWABLE TYPE
AIR CIRCUIT BREAKER
TYPICAL COMPONENTS OF AN OIL CIRCUIT BREAKER
SAMPLE OUTLINE OF A PNEUMATIC GAS CIRCUIT BREAKER
VACUUM CIRCUIT BREAKER (WITHDRAWABLE TYPE)
CUTAWAY VIEW OF A VACUUM CIRCUIT BREAKER
SWITCHGEARS
CONVENTIONAL SUBSTATION
GAS INSULATED SWITCHGEAR CROSS SECTIONAL VIEW
DISTRIBUTION TRANSFORMERS
Typical Distribution Transformer Primary H1 Bushing
Tap Changer (External/Internal)
Primary H2 Bushing
(At the Back)
Secondary
KVA Rating
Company Number
(X1, X2, X3)
Bushings
Nameplate (Hidden)
Symbols Used in Transformer Voltage Ratings NAME
Dash
Slant or Slash
Cross
SYMBOL
APPLICATION
-
To separate the voltage rating or ratings of separate windings.
/
To separate voltage to be applied or to be obtained from the same winding.
X
To designate separate voltages which can be obtained by reconnecting the coils of a winding in series or multiple combinations
EXAMPLES
7620 V
-
240/120 V
13200 GRDY / 7620 V 120 / 240 V
13200 GRDY / 7620 V 120/240 X 139/277 V
DT Nameplate Sample Primary Voltage Rating
Secondary Voltage Rating
Voltage Rating per tap position
KVA Rating
Polarity (Additive)
Schematic Diagrams
A Transformer Rated 13200 Grd.Y/7620 V
External Tap-Changers Operation
1. De-energize the DT 2. Loosen lock screw 3. Rotate switch to desired position 4. Tighten lock screw 5. Energize the DT
Lock Screw
Other Types of External Tap-Changers
Internal View of a DT With an External Tap-Changer TapChanger
Internal Tap-Changers Rotary Tap-Changers
Samples of DTs With Dual Voltage Tap Internal Tap changer
Dual Voltage Taps Always refer to nameplate for actual ratings.
Samples of DTs With Dual Voltage Tap Tap changer
Dual Voltage Taps
Changing the DUAL VOLTAGE TAP is done by transferring the connection of the primary lead
Samples of DTs With Dual Voltage Tap Changing the DUAL VOLTAGE TAP is done by transferring the connection of the outer end of the curved copper strip
Dual Voltage Taps
SECTIONALIZING EQUIPMENT
SECTIONALIZING Sectionalizing is the proper application of isolating and overcurrent protective devices to: 1. Facilitate manual and automatic line switching 2. Limit power interruption to the smallest practical segment of the line
RATIONALE The primary objective of sectionalizing is to minimize the extent and effect
of power interruption in a circuit through the proper application of isolating and protective line equipment.
EQUIPMENT USED FOR SECTIONALIZING • • • • •
Switch Fuse Recloser Sectionalizer Fault Indicator
SWITCH • A device for making, breaking or changing the connection in an electric circuit • It should be able to carry the normal load current continuously • It should also be able to handle abnormal or short circuit currents for short periods
TYPES OF SWITCHES • • • •
Disconnect Switch (DS) Air Break Switch (ABS) Load Break Switch (LBS) Remote-Controlled Line Switch (RCLS)
TYPES OF DISCONNECT SWITCHES 1. HORIZONTAL MOUNTING 2. VERTICAL MOUNTING 3. UNIVERSAL MOUNTING 4. CENTER BREAK
Disconnect Switch •
Plain knife-blade switch
•
Has no interrupter and is intended to be operated only when the circuit has been de-energized by some other means
•
Applications: primary line switch (PLS), disconnect switch
Air Break Switch •
A disconnecting switch equipped with an arcing horn
•
Can be operated with the circuit energized but carrying only charging or magnetizing current
•
The arcing horn helps extinguish the opening arc by extending it as the switch contacts open
Load Break Switch •
A disconnecting switch equipped with an interrupter
•
Can be operated when the circuit is energized and carrying normal load current
•
Can also be closed against a fault
Remote-Controlled Line Switch • An LBS that can be
operated remotely through SCADA
• It has the capability to
measure voltage, current and other circuit parameters
• If provided with the more
advanced type of electronic control, an RCLS can function like a sectionalizer
FUSE •
An overcurrent protective device which is placed in series in a circuit and has an element that melts during the passage of an overcurrent through it and thus interrupts the circuit
•
A fuse must be replaced after its operation
TYPES OF FUSES • •
•
Fuselinks Power Fuses – Type SMD-5 – Type SMD-20 – Type SMD-50 – Type SMD-100 Current Limiting Fuses (CLF)
Fuse Link •
Used in protecting distribution transformers, line capacitor banks, and lateral taps
•
Can be applied for fault currents up to 5,000 amperes and load below 4 MVA
•
Easily opened and closed using a telescopic hot stick
Power Fuse • Used in protecting transformer vaults and primary-metered services in high fault areas • Can be applied for fault currents up to 28,000 amperes and loads up to 12 MVA
Type SM-5 Power Fuse •
Can be applied for fault currents up to 28,000 amperes and loads up to 12 MVA
•
Uses a porcelain fuse holder
•
Can be opened with a telescopic hot stick but must be closed using a hook stick from a basket truck
Type SMD-20 Power Fuse •
Can be applied for fault currents up to 10,000 amperes and loads up to 8 MVA
•
Uses a fiber fuse holder
•
Can be opened and closed using a telescopic hot stick
Current Limiting Fuse (CLF) • Used in conjunction with a fuse link to protect distribution transformers in high fault areas as well as station service transformers • Has no time-current characteristic (TCC) and operates only at high fault current magnitudes • Has no external moving parts that could indicate its operation
DESCRIPTION An Automatic Circuit Recloser is a selfcontained device with the necessary intelligence to sense an overcurrent condition, interrupt the current flow, and then after a predetermined time delay, recloses automatically to reenergize the line. If the fault is permanent, it locks open after a pre-set number of operations thus isolating the faulted portion from the main part of the system.
RECLOSER •
A self-contained device with the necessary intelligence to sense an overcurrent condition, interrupt the current flow, & then after a predetermined time delay, recloses automatically to reenergize the line.
•
If the fault is permanent, it locks open after a pre-set number of operations thus isolating the faulted portion from the main part of the system.
RECLOSER CLASSIFICATIONS 1. Phase Single-phase or three-phase
2. Control Hydraulic or electronic
3. Interrupters Oil or Vacuum
4. Insulation Oil , Air or Epoxy
SINGLE-PHASE RECLOSERS •
Used to protect single-phase lines such as single-phase laterals
•
Can also be used on threephase circuits where the load is predominantly single-phase
•
Examples are the Type D (15.5 kV) and DV (38 kV) Kyle Reclosers from Cooper Power Systems
THREE-PHASE RECLOSERS 1. Triple-Single tripping (Ex. NOVA Type TS reclosers)
2. Three-phase tripping (Ex. Type KFME, WE, WVE, VWVE reclosers)
TYPES OF CONTROL 1. Hydraulic Control • •
Built as an integral part of the recloser Overcurrent is sensed by a trip coil that is connected in series with the line. When the overcurrent flows through the coil, a plunger is drawn into the coil to trip open the recloser contacts.
•
Timing and sequencing are accomplished by pumping oil through separate hydraulic chambers or ducts.
TYPES OF CONTROL 2. Electronic Control •
•
•
More flexible, more easily customized and programmed, and many have advanced protection, metering, and automation functionality. Line current is sensed by special sensing current transformers in the recloser The electronic control is housed in a cabinet separate from the recloser and conveniently permits changes to operational settings.
TYPES OF INTERRUPTING MEDIUM 1. Oil Interrupters •
•
Reclosers using oil for current interruption use the same oil for basic insulation. Some reclosers with hydraulic control also use the same oil for timing and counting functions.
TYPES OF INTERRUPTING MEDIUM 2. Vacuum Interrupters •
•
Vacuum interrupters provide fast, low-energy arc interruption with long contact and interrupter life, low mechanical stress, and maximum operating safety. With arc interruption taking place in a vacuum, contact and interrupter life far exceeds other interrupting media.
OPERATING LEVERS & INDICATORS 1. Manual Operating Handle • A yellow lever that is used to manually trip the recloser • For the Type DV recloser, this is also used to close the recloser. • For the Type KFME, WE, WVE & VWVE reclosers, this is used for manual tripping & to override the controls to keep the recloser open. This cannot be used to manually close the recloser but must be in the closed position (up) before the recloser contacts can be closed.
OPERATING LEVERS & INDICATORS 2. Contact Position Indicator • A red flag that is also linked to the interrupter mechanism but independent of the yellow handle • It drops down from under the sleethood when the interrupter contacts are open.
OPERATING LEVERS & INDICATORS 3. Operations Counter • Cumulatively records each time the recloser opens.
4. Non-reclosing Lever • Found on Type DV reclosers, this sets the unit to one shot to lockout after fault interruption
THE KYLE TYPE DV HYDRAULICALLYCONTROLLED RECLOSER Specifications Summary Nominal System Voltage (kV)
24.9 - 34.5
Maximum Rated Voltage (kV)
38
BIL (kV)
150
Max Continuou Current
560
Max Interrupting Rating (Sym.) Interrupting Medium Control Type
8000 Oil Hydraulic
THE KYLE TYPE DV RECLOSER
Construction features, operating levers, and indicators for the Type DV Recloser
THE KYLE TYPE DV RECLOSER Operating Levers and Indicators The DV Reclosers’ sleet hood, showing the manual operating handle, nonreclosing lever and contact position indicator. Also found under the sleet hood is the operations counter.
THE KYLE TYPE DV RECLOSER Major Components 1. 2. 3. 4. 5. 6. 7.
Arc interrupting assembly Closing solenoid Closing solenoid contactor Hydraulic integrator assembly Series trip solenoid Time-delay unit Head mechanism
THE KYLE TYPE DV RECLOSER
Manual Closing of a De-energized Type DV Recloser
THE KYLE TYPE KFME ELECTRONICALLYCONTROLLED RECLOSER Phase
3
Nominal System Voltage (kV)
2.4 - 14.4
Maximum Rated Voltage (kV)
15.5
BIL (kV)
110
Max Continuou Current
400
Max Interrupting Rating (Sym.)
6000
Interrupting Medium Control Type
Vacuum Electronic
THE KYLE TYPE KFME RECLOSER Operation
• Tripping & closing are initiated by signals from the electronic control • When currents in excess of the programmed minimum-trip value are detected in one or more phases, a signal from the control actuates a solenoid in the operating mechanism to trip the opening springs & open the interrupter contacts
Form 3A Control
Form 4C Control
THE KYLE TYPE KFME RECLOSER Operation
• Closing energy and the force to charge the opening springs is supplied by a closing solenoid energized from the source side of the recloser
THE KYLE TYPE KFME RECLOSER Operation
• Arc interruption takes place within the 3 sealed vacuum interrupters. • Oil is used for electrical insulation, but is not involved in arc interruption.
THE KYLE TYPE KFME RECLOSER Operating Levers and Indicators Contact position indicator
Non-reclosing lever
Operations counter
Manual operating handle (yellow)
THE KYLE TYPE KFME RECLOSER Electronic Control
Form 3A Control
• All operating parameters, like phase- and groundfault minimum trip levels, TCC selection & sequence of recloser operation are done via the electronic control • The Form 3A control is a solid-state electronic type while the Form 4C is a microprocessorbased control type
Form 4C Control
THE KYLE TYPE KFME RECLOSER
Typical Pole Installations
THE TYPE WE, WVE & VWVE RECLOSERS Operation • Closing energy & the force to required to charge the opening springs is supplied by a closing solenoid • Oil interrupters are used in WE & WVE. Vacuum interrupters are used in VWVE. • All are oil-insulated.
WE Recloser
VWVE Recloser
THE TYPE WE, WVE & VWVE RECLOSERS
Untanked view of Type WE recloser. Construction of WVE is similar.
THE TYPE WE, WVE & VWVE RECLOSERS
Untanked Type VWVE vacuum recloser
THE TYPE WE, WVE & VWVE RECLOSERS Manual Operating Lever & Indicator Yellow manual operating (trip-and-reset) handle • Used to manually trip the recloser & override the control to keep the recloser open
Contact position Indicator
• A red flag labeled OPEN independent of the yellow handle • Drops down from under the sleethood when the interrupter contacts open
THE TYPE WE, WVE & VWVE RECLOSERS Electronic Control • As with the Type KFME recloser, all operating parameters for the Type WE, WVE & VWVE reclosers are provided by the electronic control • The controls used by MERALCO are the Form 3A solid-state electronic control & the Form 4C & Form 5 microprocessor-based controls
Form 3A Control Form 4C Control
Form 5 Control
Type WE & WVE Reclosers in service
FAULT INDICATOR A device that indicates fault current flow Senses the magnetic field caused by the current flowing through the conductor Classified either as manual reset or automatic reset
SECTIONALIZERS
DESCRIPTION A SECTIONALIZER is a self-contained electrical device that interrupts its load side after sensing the passage of a predetermined number of successive fault currents and the corresponding trippings of the backup device at its source side.
SECTIONALIZER •
A self-contained electrical device that interrupts its load side after sensing the passage of a predetermined number of successive fault currents & the corresponding trippings of the back-up device at its source side
•
It opens during the open interval of the backup device
OPERATION • It opens during the open interval of the backup device • It does not interrupt fault current but can be closed into a faulted line • It can be used to interrupt normal load current • Once open, the sectionalizer will remain open until manually closed
The Type GW Sectionalizer
OPERATING DATA Phase-Minimum-Actuating Current (Amps)
BASIC SECTIONALIZER RATINGS Nominal Voltage Rated Maximum Voltage BIL Continuous Current Rating Rated Symmetrical Interrupting Current Rated Making Current, Asymmetrical Momentary Maximum, Asymmetrical
34.5 kV 38 kV 150 kV 400 A 880 A rms 15000 A 15000 A
16, 24, 40, 56, 80, 112, 160, 224, 256,
296, 320, 448, 640, 768, 896 Ground-Minimum-Actuating 3.5, 7, 16, 20, 28, Current (Amps) 40, 56, 80, 112, 160, 224, 320, 384, 448, BLOCK Number of Counts to Open 1, 2, 3 Count Resest (Seconds) 15, 30, 60, 120, 180 Phase Actuating Level X1, X2, X4, X6, X8, Multiplier (Inrush Restraint) BLOCK Phase Inrush Reset (Cycles) Ground Inrush Reset (Seconds)
5, 10, 15, 20 0.3, 0.7, 1.5, 3, 5
A Pole-mounted Type GW Sectionalizer
A Pole-mounted Type GW Sectionalizer
This sectionalizer is installed on an openwye primary lateral
External Features of Kyle Electronically Controlled Sectionalizer
Internal Details of the Type GW Sectionalizer
Operating Mechanism and Electronic Control
MANUAL OPERATING CONTROLS
The sectionalizer’s manual operating controls are located on the underside of the operator mechanism housing placed on one side of the sectionalizer’s tank.
AUTOMATIC VOLTAGE REGULATORS
Automatic Voltage Regulator • A tap-changing autotransformer with the ability to continuously monitor its output voltage and automatically adjust itself by changing taps until the desired voltage is obtained. • It regulates line voltage from 10% raise (boost) to 10% lower (buck) in 32, approximately 5/8 steps.
Reasons for Installing AVRs • To improve system voltage • To improve quality of service • To meet regulatory standards
Effects of AVRs on Voltage Problems Problems Solved by AVRs • Undervoltage • Overvoltage • Unbalanced voltage
Problems Not Solved by AVRs • Voltage sags • Voltage swells • Voltage flickers/fluctuations
Sample AVR Installation (Pole Mounted)
Sample AVR Installations (Platform Mounted)
MAJOR COMPONENTS OF AN AVR 1. S (Source) Bushing
1
4
2
5
2. L (Load) Bushing 3. SL (Neutral) Bushing 4. Series Arrester 5. Position Indicator 6. Electronic Control
6
3
MAJOR COMPONENTS OF AN AVR Position Indicator • Has a pointer mechanically connected to the tapchanging switch • Indicates the actual position of the tap-changer through the yellow pointer • Indicates the maximum & minimum positions attained during raise & lower operations through its drag hands. • Allows load bonus setting of the regulator
MAJOR COMPONENTS OF AN AVR Series Arrester • A bypass arrester connected across the series winding between the S & L bushings. • Limits the voltage developed across the series winding during lightning strikes, switching surges & line faults.
Typical Features of an Electronic Control 1. Voltage Level Selector 2. Bandwidth Selector 3. Time Delay Selector 4. Band-edge Indicator 5. Line Drop Compensation Selectors 6. Neutral Indicating Light 7. Drag hand Reset/Neutral Light Test Button 8. Internal/External Power Switch
Typical Features of an Electronic Control 9.
Control Switch
10. External Power Terminals 11. Voltmeter Terminal 12. Motor & Panel Fuses 13. Operations Counter 14. Data Port 15. LCD Display 16. Keypads
The Cooper/McGraw Edison VR-32 Step-Voltage Regulator
CONTROL TYPES 1. CL-2 / CL-2A 2. CL-4C 3. CL-5A
Cooper AVR with a CL-2A Control
Cooper AVR with a CL-4C Control 1 2 3 4 5 6
Input Voltage: 80 - 170 V 45 - 65 Hz
LCD Display Keypad Data Port Power Switch Voltmeter Terminals External Power Terminals 7 Panel Fuse 8 Differential Voltage Fuse 9 Motor Fuse 10 Manual RAISELOWER Switch 11 AUTO/REMOTEOFFMANUAL Switch 12 Neutral Lamp TestDrag Hand Reset Switch 13 Neutral Indicating Light
Cooper AVR with a CL-5A Control
Input Voltage: 80 - 137 V 45 - 65 Hz
Cooper AVR Bank with a CL-5E Control
Nameplate of a Cooper VR-32 AVR
The GE Type VR-1 Step-Voltage Regulator
CONTROL TYPES 1. VR-1 2. SM-3
The Siemens Type JFR Step-Voltage Regulator
A 250 kVA, 7.62 kV Type JFR AVR with an MJ-3A control
The Siemens Type JFR Step-Voltage Regulator
A 400 kVA, 19.92 kV Type JFR AVR with an MJ-XL control
Nameplate of a Siemens Type JFR AVR
Line Capacitors
CAPACITOR
• A device for introducing a capacitive reactance in a circuit to counteract the effects of inductive reactance • It reduces the impedance of a circuit with a consequent reduction in the voltage drop and an improvement in the PF • By reducing the current required to supply a load, it decreases losses in a circuit
SAMPLE 200 KVAR, 13200 V, CAPACITOR UNIT
CAPACITOR BANKS
FACTORY-ASSEMBLED BLOCK WITH HORIZINTALLY MOUNTED CAPACITOR UNITS
ADVANTAGES OF HAVING A CAPACITOR BANK INSTALLATION 1. RAISE AND LOWER VOLTAGE WHEN NEEDED 2. RAISE VOLTAGE ON SOURCE SIDE 3. REDUCES LOSSES IN THE SYSTEM 4. REDUCES THERMAL LOADING 5. RAISES SYSTEM LOADING CAPABILITY
TYPES OF CAPACITOR BANKS Series Capacitor Bank
• • •
Connected in series with the line Used to compensate for the reactive voltage drop in the circuit Typically used in low-voltage, heavycurrent applications such as furnaces & welders, to compensate for the voltage drop in the conductors
Shunt Capacitor Bank
• • •
Connected in parallel with the load Used to correct the component of current caused by inductive loads Typically used for PF correction
BENEFITS DERIVED FROM SHUNT CAPACITOR BANKS 1. Released Capacity
- due to PF improvement kW
kVA2 kVA1
kVAR2 kVAR1 CkVAR
2. Voltage Rise
- due to reduction in line impedance
3. Loss Reduction
- due to reduction in line impedance
TYPES OF CAPACITOR CONTROL 1. Fixed 2. Time 3. Voltage 4. Current 5. Power Factor 6. KVAR 7. Temperature
GUIDELINES IN HANDLING CAPACITOR BANKS 1. Before placing a capacitor bank in service,
inspect individual units for bulged or cracked tanks. Proper care should be exercised in handling capacitor units to prevent damage to or denting of capacitor case.
2. Before working upon capacitor units, the
capacitor bank must be allowed to stand at least five (5) minutes after disconnecting from source of power, after which it shall be short-circuited and grounded before work is started.
ENERGIZING & DE-ENERGIZING LINE CAPACITOR BANKS Always use the capacitor oil switch when energizing & de-energizing a capacitor bank. When the oil switch is inoperable, the following shall be observed:
1. Closing of FCOs shall be done only while the line is de-energized
2. For line capacitor banks installed on 13.8kV
circuits & below, opening of FCOs shall be done with the use of load buster
3. For line capacitors installed on 34.5kV circuits, opening of FCOs shall be done only when the line is de-energized
Cooper’s Type TSC Three-Phase Oil Switch Nominal System Voltage Rated Maximum Voltage Rated Momentary Current Rated Making Current Capacitive Continuous Current
34.5 kV 38 kV 12000 A 12000 A 135 A
Type TSC Oil Switch Operation
1. The oil switch is manually operated by means of the red handle under the sleet hood. Pulling down the handle will either open or close the switch depending upon its previous position. 2. A disc-type contact-position indicator shows the switch position.
Type TSC Oil Switch Operation 3. When the operating handle is pulled down, the manual reset lever is also pulled down.
4. When the operating handle is released, it automatically returns to its up position under the sleet hood. 5. The manual reset lever, however, must be returned to its up position before the motor circuit is armed & the switch is returned to remote electrical control.
Cooper’s Type NR Single-Phase Oil Switch
Nominal System Voltage Rated Maximum Voltage Rated Momentary Current Rated Making Current Capacitive Continuous Current
14.4 kV 15 kV 9000 A 9000 A 200 A
Manual Operation of the Type NR Oil Switch
The oil is manually opened & closed by operating the yellow handle under the sleet hood.
End of Presentation Thank You!