Competency Training and Certification Program in Electric Power Distribution System Engineering
Training Course in
Power System Engineering for Non-Engineers
Power System Analysis 101
U. P. NATIONAL ENGINEERING CENTER NATIONAL ELECTRIFICATION ADMINISTRATION
Power System Analysis 101
2
Power System Analysis Performance Standards Power Quality Efficiency Safety Reliability
Power System Analysis Load Flow Analysis System Loss Analysis Short Circuit Analysis Reliability Analysis
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
1
Power System Analysis 101
3
LOAD FLOW ANALYSIS
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
4
Load Flow Analysis 1. What is Load Flow? 2. Uses of Load Flow Studies 3. Load Flow Control
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
2
Power System Analysis 101
5
What is Load Flow?
Bus2 Bus1 I12 , Loss12 = ?
Utility Grid
V1 = 67 kV P1 , Q1 = ?
Bus3 V3 = ? P3 , Q3 = ?
I23 , Loss23 = ?
I24 , Loss24 = ? V4 = ? P4 , Q4 = ? Bus4 V2 = ? Lumped Load A P2 , Q2 = ? 2 MVA 85%PF Lumped Load B 1 MVA 85%PF
What are the Voltages, Currents, Power and Losses of the Distribution System? U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
6
What is Load Flow? Load Flow of an Existing System Can we see how electric power flows in the system, coming from the sources (where power is purchased) and down to all customers (where power is sold)? Can we determine: • If any customer is being provided with voltage that is too low (or even too high)? • If too much power flow through any of our equipment, especially our transformers? • How much power is lost along the lines and equipment?
YES! LOAD FLOW ANALYSIS U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
3
Power System Analysis 101
7
What is Load Flow? Load Flow of a Contemplated System Can we have a picture of the system as we contemplate possible changes? Can we determine in advance the effects of: • • • • •
Growth or addition of new loads Addition of generating plants Upgrading of Substation Expansion of distribution lines Installations of equipment such as capacitors
before the proposed changes are implemented?
YES! LOAD FLOW ANALYSIS U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
8
What is Load Flow? Load Flow (also called Power Flow) is a snapshot picture of the power system at a given point.
Load Flow Analysis simulates (i.e., mathematically determine) the performance of an electric power system under a given set of conditions. U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
4
Power System Analysis 101
9
What is Load Flow? How would the engineers do that? • Identify physical components • Know the characteristic of components • Mathematically represent the behavior of components • Calculate electrical parameters
Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
10
What is Load Flow?
G
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
5
Power System Analysis 101
11
What is Load Flow? Substation Transformer
Utility Grid or Generator
Transmission Line
G Bus
Distribution Line
Distribution Transformer
Load Flow mathematically determines the Voltages, Currents, Power and Losses Load U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
12
Uses of Load Flow Studies Basic Information From a Load Flow Study Voltage Profile Injected Power (Pp and Qp) Line Currents (Ipq and Ipq) Power Flows (Ppq and Qpq) Line Losses (I2R and I2X)
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
6
Power System Analysis 101
13
Uses of Load Flow Studies Other Information From a Load Flow Study Overvoltage and Undervoltage Buses Critical and Overloaded Transformers and Lines Total System Losses
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
14
Uses of Load Flow Studies Sensitivity Analysis 1) Take any line, transformer or generator out of service. 2) Add, reduce or remove load to any or all buses. 3) Add, remove or shift generation to any bus. 4) Add new transmission or distribution lines. 5) Increase conductor size on T&D lines. 6) Change bus voltages. 7) Change transformer taps. 8) Increase or decrease transformer size. 9) Add or remove rotating or static var supply to buses. U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
7
Power System Analysis 101
15
Uses of Load Flow Studies 1) ANALYSIS OF EXISTING CONDITIONS • Check for voltage violations PGC: 0.95 – 1.05 p.u. (For Transmission) PDC: 0.90 – 1.10 p.u (For Distribution)* *Recommended 0.95 – 1.05 p.u.
• Check for branch power flow violations Transformer Overloads Line Overloads • Check for system losses Caps on Segregated DSL
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
16
Uses of Load Flow Studies 2) ANALYSIS FOR CORRECTING PQ PROBLEMS • Voltage adjustment by utility at delivery point Request TransCo to improve voltage at connection point TransCo as System Operator will determine feasibility based on Economic Dispatch and other adjustments such as transformer tap changing and reactive power compensation
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
8
Power System Analysis 101
17
Uses of Load Flow Studies 2) ANALYSIS FOR CORRECTING PQ PROBLEMS • Transformer tap changing Available Taps At Primary Side At Secondary Side Both Sides
Typical Taps
Tap 1: +5% Tap 2: +2.5% Tap 3: 0% (Rated Voltage) Tap 4: -2.5% Tap 5: -5%
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
18
Uses of Load Flow Studies 2) ANALYSIS FOR CORRECTING PQ PROBLEMS •Capacitor compensation • Compensate for Peak Loading • Check overvoltages during Off-Peak • Optimize Capacitor Plan • System configuration improvement
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
9
Power System Analysis 101
19
Uses of Load Flow Studies 3) EXPANSION PLANNING • • • • • • •
New substation construction Substation capacity expansion New feeder segment construction / extension Addition of parallel feeder segment Reconducting of existing feeder segment/ circuit Circuit conversion to higher voltage Generator addition
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
20
Uses of Load Flow Studies 4) CONTINGENCY ANALYSIS Reliability analysis of the Transmission (Grid) and Subtransmission System 5) SYSTEM LOSS ANALYSIS Segregation of System Losses
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
10
Power System Analysis 101
21
Load Flow Control 1. For Generating plants, the amount of power that can be delivered can be controlled by the plant operator (as long as within the capacity of the plant) 2. Flow of power is affected by the voltages and impedances across the components •
Specialized Transformers and other equipment may be utilized to control the flow of power across the network
3. Capacitors are used to improve the voltage profile across the network •
The current drawn by the load is reduced
•
The voltage drop across the line is reduced
•
The voltage at the load side is increased U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
22
SYSTEM LOSS ANALYSIS
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
11
Power System Analysis 101
23
System Loss Analysis 1. Components of Distribution System Losses 2. Segregation of Distribution System Losses 3. System Loss Reduction and Control
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
24
Components of Distribution System Losses The Philippine Distribution Code (PDC) mandates system losses to be segregated into the following components: a. Technical Loss; b. Non-Technical Loss; and c. Administrative Loss.
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
12
Power System Analysis 101
25
Total Distribution System Losses Energy Delivered to the Distribution System
-
Energy Delivered to Users
=
Total Distribution System Losses
Administrative + Loss
Technical Loss
+ Non-Technical Loss
Bundled Technical & Non-Technical Losses U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
26
Components of Distribution System Losses Administrative Losses The electric energy used by the Distribution Utility in the proper operation of the Distribution System. a. Distribution Substations; b. Offices, warehouses and workshops of the DU; and c. Other essential electrical loads of the Distribution Utility.
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
13
Power System Analysis 101
27
Components of Distribution System Losses Technical Losses Load and no-load losses in: a. Sub-transmission lines and substation transformers; b. Primary distribution lines and distribution transformers; c. Secondary distribution lines and service drops; d. Voltage regulators, Capacitors and reactors; and e. All other electrical equipment necessary for the operation of the distribution system. U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
28
Components of Distribution System Losses Non-Technical Losses The component that is not related to the physical characteristics and functions of the electrical system, and is caused primarily by human error, whether intentional or not. Includes the electric energy lost due to pilferage, tampering of meters and erroneous meter reading. Errors that are attributable to inaccuracies in metering and billing. U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
14
Power System Analysis 101
29
Total Distribution System Losses Total DSL = Energy Input - Energy Output Total DSL = Σ[Energy delivered by the Transmission System] + Σ[Energy delivered by Embedded Generating Plants] + Σ[Energy delivered by Other Distribution Systems] + Σ[Energy delivered by User Systems with Generating Units] - Σ[Energy delivered to the Users of the Distribution System] Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
30
Unbundling the Technical and Non-Technical Loss Technical Losses
+
Non-Technical Losses
Technical Losses Residual after subtracting Administrative & Technical Losses from the Total Distribution System Losses
Shall be quantified through 3-Phase (Unbalanced) Load Flow Simulations
=
Non-Technical Losses
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
15
Power System Analysis 101
31
Unbundling the Technical and Non-Technical Loss Technical Loss = Σ[Hourly Load and No-Load (or Fixed) Losses in all
electrical equipment, devices and conductors] a)Sub-transmission Lines b)Substation Power Transformers c)Primary Distribution Lines d)Distribution Transformers e)Secondary Distribution Lines f) Service Drops
g) h) i) j)
Voltage Regulators Capacitors Reactors Other electrical equipment
Hourly Load Flow Simulations
Plus Calculated Metering Equipment Loss Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
32
Unbundling the Technical and Non-Technical Loss Primary Distribution Lines (Main Feeder)
Subtransmission Lines
Substation Transformer
Three-Phase Unbalanced Load Flow Simulations a)Sub-transmission Lines b)Substation Power Transformers c)Primary Distribution Lines Distribution d)Distribution Transformers Transformer e)Secondary Distribution Lines f) Service Drops g)Voltage Regulators h)Capacitors i) Reactors j) Other electrical equipment U. P. National Engineering Center National Electrification Administration
Primary Distribution Lines (Laterals) Misc Loads
Secondary Distribution Lines Service Drop
Residential
Commercial
Industrial
Load Losses and No-Load (Fixed) Losses Power System Engineering for Non-Engineers
16
Power System Analysis 101
33
Unbundling the Technical and Non-Technical Loss Calculation of Metering Equipment Potential Transformer Loss = Power Loss in PT (kW) x Number of PT x Number of Operating Hours in the Billing Period Current Transformer Loss = Power Loss in CT (kW) x Number of CT x Number of Operating Hours in the Billing Period Electric Meter Potential Coil Loss = Power Loss in Electric Meter Potential Coil (kW) x Number of Electric Meters x Number of Operating Hours in the Billing Period Electric Meter Current Coil Loss = Power Loss in Electric Meter Current Coil (kW) x Number of Electric Meters x Number of Operating Hours in the Billing Period Operating Hours = No. of days x 24 hours – SAIDI U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
34
Unbundling the Technical and Non-Technical Loss Non-Technical Loss = Total Distribution System Losses - Administrative Loss - Technical Loss - Recovered Losses Note: Losses recovered from anti-pilferage activities are subtracted from the total distribution system losses. U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
17
Power System Analysis 101
35
DSL Segregation Distribution System Loss Segregation Program Distribution System Data
Customer Energy Bill
(3-phase Load Flow)
Distribution Reliability Assessment Metering Equipment Inventory
U. P. National Engineering Center National Electrification Administration
Segregated Technical Loss (Billing Period)
Metering Equipment Loss Power System Engineering for Non-Engineers
Power System Analysis 101
36
Segregated Distribution System Losses
Monthly DSL Segregation Segregated DSL for the Whole Distribution System Segregated DSL Per Receiving/Metering Point Segregated DSL per Substation Segregated DSL per Feeder Segregated DSL per Distribution Transformer
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
18
Power System Analysis 101
37
Distribution Network Models Ia
IA A
Impedance/ Admittance parameters of Distribution System Element
IB
Distribution B System C Element
IC
a Ib b Ic
VA VB VC
c Vc Vb Va
Ground (Reference Node)
Distribution Network Model must capture the unbalance characteristics of the System
Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
38
Distribution Load Models 350 300
Customer Energy Bill NormalizedDemand(per unit)
1.2 1
Demand (W)
250 200 150 100
0.8
50
0.6
Area under the curve = Customer Energy Bill
0.4
0
0.2 0 Time (24 hours)
Normalized Customer Load Curve U. P. National Engineering Center National Electrification Administration
Customer Energy Bill Converted to Hourly Power Demand Power System Engineering for Non-Engineers
19
Power System Analysis 101
39
Data Requirements Administrative Load Data Customer Data Billing Cycle Data Customer Energy Consumption Data Load Curve Data Bus Data Subtransmission Line Data - Overhead Subtransmission Line Data - Underground/Submarine Cable Substation Power Transformer Data - Two Winding Substation Power Transformer Data - Three Winding Primary Distribution Line Data - Overhead Primary Distribution Line Data - Underground Cable Primary Customer Service Drop Data - Overhead Primary Customer Service Drop Data - Underground Cable Distribution Transformer Data Secondary Distribution Line Data Secondary Customer Service Drop Data Voltage Regulator Data Shunt Capacitor Data Shunt Inductor Data Series Inductor Data
ERC-DSL-01 ERC-DSL-02 ERC-DSL-03 ERC-DSL-04 ERC-DSL-05 ERC-DSL-06 ERC-DSL-07 ERC-DSL-08 ERC-DSL-09 ERC-DSL-10 ERC-DSL-11 ERC-DSL-12 ERC-DSL-13 ERC-DSL-14 ERC-DSL-15 ERC-DSL-16 ERC-DSL-17 ERC-DSL-18 ERC-DSL-19 ERC-DSL-20 ERC-DSL-21
Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
40
Optimal Level of System Loss
Total Cost
Cost
System Loss Reduction Program Cost
Unrecovered Energy Cost
High
Optimal
U. P. National Engineering Center National Electrification Administration
Low
System Loss Power System Engineering for Non-Engineers
20
Power System Analysis 101
41
BENECO DSL Segregation SEGREGATED DISTRIBUTION SYSTEM LOSSES ANALYSIS
NON-TECHNICAL LOSS REDUCTION PROGRAM TECHNICAL, ECONOMIC & FINANCIAL ANALYSIS
TECHNICAL LOSS REDUCTION PROGRAM TECHNICAL, ECONOMIC & FINANCIAL ANALYSIS Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
42
BENECO DSL Segregation Technical Loss, 52.76%
TEST YEAR SEGREGATED DISTRIBUTION SYSTEM LOSSES
NonTechnical Loss, 46.74%
Administrative Loss, 0.50%
Loss Administrative
Kwhr
%
167, 791
0.0594%
Technical
18,181,059
6.3153%
Non-Technical
15,487,726
5.5951%
TOTAL
33,836,577
11.9698%
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
21
Power System Analysis 101
BENECO DSL Segregation
43
SEGREGATED SYSTEM LOSSES
13.2 KV System
Administrative Loss
0.3998%
Technical Loss
9.8906% 7.4183%
Non-Technical Loss TOTAL LOSSES
17.7088%
13.2KV SYSTEM 23KV SYSTEM SEGREGATED SYSTEM LOSSES
23 KV System
Administrative Loss
0.0393%
Technical Loss
6.1051%
Non-Technical Loss
5.4879%
TOTAL LOSSES
11.6324%
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
44
DSL RESULT PER FEEDER PER HOUR PER DAY IN A MONTH
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
22
Power System Analysis 101
45
Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
46
BENECO DSL Segregation SEGREGATED TECHNICAL LOSS
% LOSS
% SHARE
Power Transformer Load Loss
0.0590%
0.9338%
Power Transformer No-Load Loss
0.2372%
3.7559%
Primary Line
1.3805%
21.8597%
Primary Service Drop
0.0000%
0.0000%
Dist. XF Load Loss
0.3438%
5.4445%
Dist. XF No-Load Loss
1.7397%
27.5469%
Secondary
2.1652%
34.2848%
Secondary Service Drop
0.0691%
1.0937%
Shunt Capacitor Loss
0.0029%
0.0456%
kWhR Meter Loss
0.3180%
5.0350%
Total Technical Loss
6.3153%
100.0000%
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
23
Power System Analysis 101
47
BENECO DSL Segregation TECHNICAL LOSS DISTRIBUTION TECHNICAL LOSS ALLOCATION kWhR Meter Loss 5% Pow er Xformer Load Loss 1% Shunt Capacitor Loss 0%
Pow er Xformer No-Load Loss 4% Primary Line 22%
Secondary Service Drop 1% Secondary 34%
Dist. XF Load Loss 5%
Dist. XF No-Load Loss 28%
Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
48
BENECO DSL Segregation TEST YEAR SEGREGATED DISTRIBUTION SYSTEM LOSSES PER SYSTEM VOLTAGE PERCENT (%) TECHNICAL LOSSES
KWHR TECHNICAL LOSSES
SEGREGATED SYSTEM LOSSES
13.2 KV System
23 KV System
Total
13.2 KV System
23 KV System
Total
Administrative Loss
62,768.60
105,022.54
167,791.14
0.3998%
0.0393%
0.0594%
Technical Loss
1,552,634.80
16,299,669.83
17,852,304.63
9.8906%
6.1051%
6.3153%
Non-Technical Loss
1,164,538.99
14,651,941.84
15,816,480.83
7.4183%
5.4879%
5.5951%
33,836,576.60
17.7088 %
11.6324 %
11.9698 %
TOTAL LOSSES
2,779,942.39
31,056,634.21
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
24
Power System Analysis 101
49
BENECO DSL Segregation TEST YEAR SEGREGATED TECHNICAL LOSSES PER SYSTEM VOLTAGE KWHR TECHNICAL LOSSES
TECHNICAL LOSSES Power Xformer Load Loss
13.2 KV System 5,232
23 KV System 161,467
PERCENT (%) TECHNICAL LOSSES 13.2 KV System
Total
23 KV System
Total
166,700
0.0333%
0.0605%
0.0590%
Power Xformer No-Load Loss
105,295
565,221
670,517
0.6708%
0.2117%
0.2372%
Primary Line
451,032
3,451,427
3,902,460
2.8732%
1.2927%
1.3805%
0.0000%
0.0000%
0.0000%
Primary Service Drop Dist. XF Load Loss
-
6
6
32,239
939,729
971,968
0.2054%
0.3520%
0.3438%
Dist. XF No-Load Loss
591,212
4,326,553
4,917,765
3.7661%
1.6205%
1.7397%
Secondary
209,447
5,911,176
6,120,623
1.3342%
2.2141%
2.1652%
4,275
190,979
195,254
0.0272%
0.0715%
0.0691%
0.0025%
0.0029%
0.0029%
898,866
0.9779%
0.2792%
0.3180%
17,852,305
9.8906%
6.1051%
6.3153%
Secondary Service Drop Shunt Capacitor Loss kWhR Meter Loss Total Technical Loss
394 153,507 1,552,635
7,753 745,359 16,299,670
8,147
Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
50
BENECO DSL Segregation FORECASTED SEGREGATED DISTRIBUTION SYSTEM LOSSES
YEAR
2006
2007
2008
2009
2010
Energy Input (KWH)
Total System Losses (%)
Administrativ e Loss (%)
Technical Loss (%)
Non Technical Loss (%)
313,577,324
12.1222%
0.0621%
6.4611%
5.5951%
341,755,055
12.2757%
0.0583%
6.6187%
5.5951%
372,339,284
12.3994%
0.0535%
6.7477%
5.5951%
405,588,445
12.5074%
0.0491%
6.8604%
5.5951%
442,271,657
12.7071%
0.0493%
7.0604%
5.5951%
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
25
Power System Analysis 101
51
PROPOSED DISTRIBUTION SYSTEM LOSS CAPS YEAR
Technical Loss Cap
Declining NonTechnical Loss Caps
Administrative Loss Cap (Annual KWH)
2006
5.9833% to 6.9388%
5.5951%
194,741
2007
6.1281% to 7.1094%
4.7486%
199,147
2008
6.2431% to 7.2523%
3.8585%
199,147
2009
6.3431% to 7.3778%
3.1278%
199,147
2010
6.5249% to 7.5959%
2.7644%
218,218
FORECASTED DISTRIBUTION SYSTEM LOSS FORECASTED SYSTEM LOSS RANGE
YEAR 2006
11.6480%
-
12.6047%
2007
10.9425%
-
11.9251%
2008
10.1628%
-
11.1733%
2009
9.5279%
-
10.5639%
2010
9.3467%
-
10.4191% Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
52
BENECO SEGREGATED DISTRIBUTION SYSTEM LOSS (base year 2004) Distribution System Loss Total System Loss
Administrative Loss
Energy (KWHR)
Peso Equivalent (Php) (as of February 2007 costing**)
Percentage (%)
33,836,577
11.970%
P 239,339,641
167,791
0.059%
P 1,186,854
Technical Loss
17,852,305
6.315%
P 126,276,492
Non-Technical Loss
15,816,481
5.595%
P 111,876,296
BENECO SEGREGATED TECHNICAL LOSS (base year 2004) Technical Losses
Power Xformer Load Loss Power Xformer No-Load Loss Primary Line Primary Service Drop
Energy (KWHR)
Percentage (%)
Peso Equivalent (Php) (as of February 2007 costing**)
166,700
0.0590%
670,517
0.2372%
P 1,179,134 P 4,742,833
3,902,460
1.3805%
P 27,603,658
6
0.0000%
P 42
971,968
0.3438%
P 6,875,117
Dist. XF No-Load Loss
4,917,765
1.7397%
P 34,785,321
Secondary
6,120,623
2.1652%
P 43,293,617
195,254
0.0691%
P 1,381,108
8,147
0.0029%
P 57,626
898,866
0.3180%
P 6,358,036
6.3153%
P 126,276,492
Dist. XF Load Loss
Secondary Service Drop Shunt Capacitor Loss kWhR Meter Loss
U. P. National Engineering 17,852,305 Center National Electrification Administration
Total Technical Loss
Power System Engineering for Non-Engineers
26
Power System Analysis 101
53
SEGREGATED SYSTEM LOSS PER METERING CONNECTION POINT ENERGY LOSSES (KWHR) Metering Connection
Metering Connection Pt. Loss
Lamut
4,898,458
Irisan NSC Old 20MVA NSC New 20MVA NPC-Beckel
Admin Loss 38,384
5,182,063
6,636
7,770,156
22,323
9,854,817
37,680
2,682,647
Atok
1,595,739
Mankayan
932,559
Asin Mini-Hyrdo Bakun Mini-hydro Ampuhaw Minihydro Ambuclao NPC-Itogon LUELCO
Technical Loss
50,108 11,625
97,772
-
25,055
-
63,242
-
251,644
1,036
371,989
-
110,435
-
LOSSES IN PERCENTAGE (%)
Non-Technical Loss
Metering Connection Pt. Loss
Admin Loss
Technical Loss
NonTechnical Loss
3,326,440
1,533,634
10.0966%
0.0791%
6.8564%
3.1611%
3,081,395
2,094,032
11.8636%
0.0152%
7.0544%
4.7940%
3,643,277
4,104,556
11.8636%
0.0341%
5.5626%
6.2669%
4,973,278
4,843,859
11.8636%
0.0454%
5.9870%
5.8312%
959,893
1,722,755
11.8636%
0%
4.2450%
7.6186%
890,558
655,073
19.5406%
0.6136%
10.9053%
8.0217%
547,017
373,918
14.8130%
0.1846%
8.6889%
5.9394%
38,621
59,151
16.4621%
0%
6.5027%
9.9594%
17,677
7,378
12.1417%
0%
8.5662%
3.5755%
24,629
38,613
15.0311%
0%
5.8537%
9.1774%
115,060
135,549
20.3546%
0.0838%
9.3068%
10.9641%
190,389
181,600
18.8304%
0%
9.6377%
9.1927%
66,364
26.5489%
0%
10.5949%
15.9540%
44,072
Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
54
NON-TECHNICAL LOSS PER METERING CONNECTION POINT Metering Connection
Non-Technical Loss (kWhr)
Cost of Unrecovered NTL (Pesos)
NTL % (System)
NTL % (Feeder)
Lamut
1,533,634.21
P 11,289,465
0.5425%
3.1611%
Irisan
2,094,031.95
P 15,414,693
0.7408%
4.7940%
NSC Old 20MVA
4,104,556.00
P 30,214,663
1.4520%
6.2669%
NSC New 20MVA
4,843,859.12
P 35,656,858
1.7135%
5.8312%
NPC-Beckel
1,722,754.60
P 12,681,627
0.6094%
7.6186%
Atok
655,072.51
P 4,822,153
0.2317%
8.0217%
Mankayan
373,917.67
P 2,752,501
0.1323%
5.9394%
59,150.85
P 435,424
0.0209%
9.9594%
7,378.26
P 54,313
0.0026%
3.5755%
38,613.44
P 284,243
0.0137%
9.1774%
Ambuclao
135,548.81
P 997,809
0.0480%
10.9641%
NPC-Itogon
181,599.91
P 1,336,802
0.0642%
9.1927%
66,363.50
P 488,518
0.0235%
15.9540%
15,816,480.83
P 116,429,070
5.5951%
Asin Mini-Hyrdo Bakun Mini-hydro Ampuhaw Minihydro
LUELCO TOTAL
ACTIVITIES CONSIDERED AND COSTED FOR NON-TECHNICAL LOSS REDUCTION OPTIMIZATION COMPUTATION Communal Distribution Transformer Block Metering
►
Streetlight kwhr Metering
►
Streetlight Photo Switching
►
Right-of-Way Clearing
►
Inspection, Calibration and Apprehension Kwhr Meter Replacement (apprehended and defective) Phased-Out Kwhr Meter Replacement (Old kwhr meters)
►
►
Sole-Use Distribution Transformer Monitoring
►
Loose Connection Correction Software and Hardware Requirements Procurement
► ► ►
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
27
Power System Analysis 101
55
PRIORITY RANKING IN TERMS OF SELECTED NTL ACTIVITES FOR IMPLEMENTATION COMMUNAL TRANSFORMER BLOCK METERING Average Rank
INSPECTION, APPREHENSION, CALIBRATION
Metering Connection
Metering Connection KWHR NTL / NO. OF DT's
RANK
KWHR NTL / NO. OF METERS
NSC Old 20MVA
38,722
1
RANK
NSC Old 20MVA
430
2.5
NPC-Beckel
10,194
1
3
NPC-Beckel
201
2.5
NSC New 20MVA
2
11,009
2
NSC New 20MVA
157
5.5
3
Lamut
6,786
4
Lamut
88
7
5.5
LUELCO
2,765
7
LUELCO
155
4
5.5
NPC-Itogon
2,977
6
NPC-Itogon
107
5
6.5
Irisan
6,326
5
Irisan
86
8
7
Ampuhaw Mini-hydro
2,413
8
Ampuhaw Mini-hydro
105
6
9
Asin Mini-Hyrdo
2,366
9
Asin Mini-Hyrdo
83
9
Atok
2,120
10
Atok
77
10 11
1
10 11.5
Ambuclao
1,442
12
Ambuclao
69
11.5
Mankayan
1,723
11
Mankayan
42
12
434
13
Bakun Mini-hydro
21
13
13
Bakun Mini-hydro
FEEDER COVERAGE Single Feeder Metering Points
Multi-Feeder Metering Connection Points
Lamut
Asin Mini-Hyrdo
NSC New 20MVA
Feeder 1
Feeder 7
Feeder 2
Feeder 8
Irisan
Feeder 9
Feeder 3
Feeder 10
Feeder 4
FeederU. 5
Circuit 1
Ampuhaw Mini-hydro
Circuit 2
Ambuclao
Circuit 3
NPC-Itogon LUELCO
Mankayan
NPC-Beckel
NSC Old 20MVA
Bakun Mini-hydro
Atok
Circuit 4
Totalizer 1 Engineering
Power System Engineering for Non-Engineers
P. National Center Circuit 5 TotalizerAdministration 2 Electrification
FeederNational 6
Power System Analysis 101
56
SUMMARY OF OPTIMIZED PROJECT COST FOR NON-TECHNICAL LOSS REDUCTION PROGRAM Metering Connection
% Unrecovered NTL per Feeder
Level of Optimum %NTL per Feeder
% Recovered NTL per Feeder
% Recovered NTL as per Entire System
Optimized Project Cost for NTL Reduction
Lamut
3.161%
2.024%
1.137%
0.3474%
6,643,459.93
Irisan
4.794%
3.053%
1.741%
0.4718%
9,021,486.28
NSC Old 20MVA
6.267%
2.154%
4.113%
0.4991%
9,544,620.05
NSC New 20MVA
5.831%
3.029%
2.802%
0.8901%
17,019,823.88
NPC-Beckel
7.619%
3.237%
4.382%
0.2589%
4,950,875.25
Atok
8.022%
5.403%
2.618%
0.1561%
2,984,882.11
Mankayan
5.939%
4.532%
1.408%
0.1009%
1,929,917.47
Asin Mini-Hyrdo
9.959%
5.623%
4.337%
0.0118%
225,901.85
Bakun Mini-hydro Ampuhaw Minihydro
3.575%
3.056%
0.520%
0.0022%
42,656.16
9.177%
4.752%
4.426%
0.0071%
135,238.81
10.964%
7.769%
3.195%
0.0340%
649,735.01
9.193%
5.534%
3.659%
0.0387%
739,469.91
LUELCO
15.954%
8.611%
7.343%
0.0127%
242,309.48
TOTAL =
5.5951%
2.7644%
Ambuclao NPC-Itogon
2.8308%
P 54,130,376.19
NOTE: Project Cost for implementation per Metering Connection at targeted reduced Non-technical Loss percentage SHALL NOT EXCEED the computed Optimized Project Cost.
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
28
Power System Analysis 101
57
BENECO NON-TECHNICAL LOSS REDUCTION ECONOMIC ANALYSIS Cost of Unrecovered VS NTL Reduction Program
M illion s
120 110
Cost of Unrecovered NTL
100
Cost NTL Reduction Program
90
Optimum level of loss reduction
C ost (Php )
80 70 60 50 40 30 20 10
0.5595%
0.7693%
0.9791%
1.1890%
1.3988%
1.6086%
1.8184%
2.0282%
2.2381%
2.4479%
2.6577%
2.8675%
3.0773%
3.2871%
3.4970%
3.7068%
3.9166%
4.1264%
4.3362%
4.5461%
4.7559%
4.9657%
5.1755%
5.3853%
5.5951%
0
Non-Technical Loss (%)
OPTIMUM LEVEL OF NON-TECHNICAL LOSS REDUCTION = 2.7644%
EQUIVALENT PROJECT COST = P53,447,802.55 U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
58
System Loss Reduction and Control
Reduction and Control of Technical Losses
Reduction and Control of Non-Technical Losses
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
29
Power System Analysis 101
59
Reduction and Control of Technical Losses
Use the results of the Distribution System Loss Segregator for System Loss Reduction Program. Ranks the losses from the highest to lowest ( Per Substation, Per feeder, per distribution transformer) Prepare a Specific Technical Loss Reduction Program based on your technical analysis!!! Simulate your proposed technical loss reduction solutions to quantify the technical loss reduction Optimize your proposed technical loss reduction solutions
Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
60
Reduction and Control of Technical Losses
Distribution Rehabilitation Plan Safety Power Quality Problem Correction Reduce Technical Losses
Distribution Expansion Plan Capacity that complies with Power Quality Standards and Controlled Technical Losses
PDC: Distribution Development Plan • Technical Analysis • Economic Analysis U. P. National Engineering Center National Electrification Administration
• Financial Analysis Power System Engineering for Non-Engineers
30
Power System Analysis 101
61
Reduction and Control of Non-Technical Losses NEA SLRP
Causes of Pilferages Long run of secondary networks “conducive” for illegal tapping Services run from one building to the next and attached to various structures (e.g., trees) making it difficult for meter readers to follow the wires or spot illegal connections Secondary wiring with “rat’s nest” appearance due to poor workmanship Inaccessible meters (located indoor or inside a compound) Control of meter seals Poor meter records (where and when the meters are installed, maintained, removed, condemned, etc.) U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
62
Reduction and Control of Non-Technical Losses NEA SLRP
Detection of Pilferages
Surveillance Teams (working full time) Consumer connections inventory to assure that: • •
All service connections are metered All energized services are in an “active” status in the billing system • There are no illegal taps, by-passed meters, or tampered meters • Each household is metered separately (no flying taps) • Each consumer is properly classified 1. Match all service connections found in the field to a distribution transformer 2. Match the meter number to the account number 3. Check meter reading against previous readings to assure that meter readings are being properly reported U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
31
Power System Analysis 101
63
Reduction and Control of Non-Technical Losses NEA SLRP
Tampered Meters
In-Place Quick-test for Accuracy Hard-to-Detect Tampering • • • •
Gear teeth removed Small hole bored at the top of the meter housing “Floating Neutral” Swapping the line-side and load side
Correcting Problems • •
Service conductors are not properly supported Service wire insulation has deteriorated
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
64
Reduction and Control of Non-Technical Losses NEA SLRP
Apprehension of Pilferers
Confronting the consumer
Documenting the findings
Calculating the amount of electricity stolen
Setting the penalty amount to be charged
Disconnecting service and removing the meter •
May include policemen or barangay officials
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
32
Power System Analysis 101
65
Reduction and Control of Non-Technical Losses NEA SLRP
Punitive Measures Against Pilferers R.A. 7832 – Theft of electricity is a crime Removal of fraudulent hook-ups Collection for unregistered consumption Penalty charge Connection charge Disconnection of service Filing charges with judicial authorities Charging for tampering with seals Regularly scheduled inspections
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
66
Reduction and Control of Non-Technical Losses NEA SLRP
Prevention of Pilferage by Service Entrance Modification
Installation of meters on the service pole
Meter clustering in apartment buildings
Better meter seals
Security plates or cabinets
Coaxial service cable
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
33
Power System Analysis 101
67
Reduction and Control of Non-Technical Losses NEA SLRP
Political and legal measures
Strengthening of laws that would impose severe penalties on employees who collaborate with consumers for the purpose of defrauding the DU
Modification of Procedures for recovery and prosecution
Elimination of political interference with bill collections
Consistent enforcement practices
Publicize successes
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
68
Reduction and Control of Non-Technical Losses NEA SLRP
Complaints for low voltage from the customers
Look for the overload distribution transformers and compared the billings of all customers connected to that DT.
Distribution transformers that always trips may be suspected for illegal connections.
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
34
Power System Analysis 101
69
SHORT CIRCUIT ANALYSIS
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
70
Short Circuit Analysis 1. What is Short Circuit? 2. Short Circuit Studies 3. Selection of Device Duties
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
35
Power System Analysis 101
71
What is Short Circuit?
Very Large Current Flow
+
Very Small Resistance
I=
V ⇒∞ R →0
Short Circuit
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
72
What is Short Circuit?
Analogy of Normal and Short Circuit Current in a Hydroelectric plant U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
36
Power System Analysis 101
73
What is Short Circuit? Equipment Explosion because of Short Circuit
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
74
What is Short Circuit? Type of Faults
Three Phase Fault
Double Line-to-Ground Fault U. P. National Engineering Center National Electrification Administration
Line-to-Line Fault
Single Line-to-Ground Fault Power System Engineering for Non-Engineers
37
Power System Analysis 101
75
What is Short Circuit? Sources of Short Circuit Currents G
Utility
MV
Fault LV
Fault Current Contributors U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
76
What is Short Circuit? PROTECTIVE DEVICES: FUSE
Low Voltage Fuses Up to 1000 Volts
High Voltage Fuses Above 1000 Volts
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
38
Power System Analysis 101
77
What is Short Circuit? PROTECTIVE DEVICES: LOW VOLTAGE CIRCUIT BREAKERS
Molded-Case Circuit Breakers Low Voltage Power Circuit Breakers U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
78
Substation Vacuum Circuit Breakers
What is Short Circuit? PROTECTIVE DEVICES: HIGH VOLTAGE CIRCUIT BREAKERS
Outdoor-Type Circuit Breaker in Switchyard U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
39
Power System Analysis 101
79
What is Short Circuit? PROTECTIVE DEVICES: HIGH VOLTAGE CIRCUIT BREAKERS
Indoor Type Circuit Breaker in a Switchgear U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
80
Short Circuit Studies
Short Circuit Current and Time Characteristics of Protective Devices U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
40
Power System Analysis 101
81
Short Circuit Studies
Comparison of Momentary and Interrupting Duties of Interrupting Devices
Comparison of Short-time or withstand rating of system components
Selection of rating or setting of short circuit protective devices
Evaluation of current flow and voltage levels in the system during fault
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
82
Short Circuit Studies
First Cycle Fault Current Short circuit ratings of low voltage equipment Ratings of Medium Voltage (MV) to High Voltage (HV) switch and fuse Close & Latch (Making) capacity or ratings of HV Circuit Breakers Maximum Fault for coordination of instantaneous trip of relays
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
41
Power System Analysis 101
83
Short Circuit Studies
1.5 to 4 Cycles Fault Current Interrupting (breaking) duties of HV circuit breakers Interrupting magnitude and time of breakers for coordination
30 Cycles Fault Current For time delay coordination
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
84
Selection of Device Duties
ANSI/IEEE: American National Standards Institute/ Institute of Electrical and Electronics Engineers
IEC: International Electrotechnical Commission
Prescribes Test Procedures and Calculation Methods U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
42
Power System Analysis 101
85
Selection of Device Duties 8-Cycle Total-Rated Circuit Breakers (KA)
5-Cycle Symmetrical-Rated Circuit Breakers (KA)
Circuit Breaker Nominal Size Identification
Example Maximum System Operating Voltage
Momentary Rating (Total 1st-Cycle RMS Current
Interrupting Rating (Total RMS Current at 4-cycle ContactParting Time
Closing and Latching Capability (Total First Cycle RM Current)
Short-Circuit Capability (Symmetrical RMS Current at 3-Cycle Parting Time
4.16 – 75
4.16 KV
20
10.5
19
10.1
4.16 – 250
4.16 KV
60
35
58
33.2
4.16 – 350
4.16 KV
80
48.6
78
46.9
13.8 – 500
13.8 KV
40
21
37
19.6
13.8 – 750
13.8 KV
60
13.5
58
30.4
13.8 – 1000
13.8 KV
80
42
77
40.2 Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
86
COMPARISON OF DUTIES TFF (KA)
LLF (KA)
BUS ID
PHASE
S/S PG-17 PG-26 PG-40 PG-52 PG-53 PG-63
3 3 3 3 3 3 3
2.30005 2.09517 1.98127 1.82417 1.70334 1.69336 1.59908
1.99190 1.81447 1.71583 1.57978 1.47514 1.46650 1.38485
PG-17-1 PG-17-2 PG-17-1-3 PG-17-2-3 PG-17-3-7
3 1 1 1 1
2.08156 0.00000 0.00000 0.00000 0.00000
1.80268 0.00000 0.00000 0.00000 0.00000
PG-26-5 PG-26-5-3
3 1
1.86883 0.00000
1.61845 0.00000
PG-40-2 PG-40-2-5 PG-40-2-6
3 1 1
1.78352 0.00000 0.00000
1.54457 0.00000 0.00000
PG-52-7
1
0.00000
0.00000
1
0.00000
0.00000
PG-53-1
DLGF SLGF (KA) (KA) BACKBONE LINES 2.86464 2.76467 2.32896 2.21705 2.10904 1.96635 1.85435 1.66821 1.68370 1.46936 1.67035 1.45395 1.54879 1.31529 LATERAL LINES 2.30059 2.18533 0.00000 2.14564 0.00000 2.01008 0.00000 2.06014 0.00000 1.87921 LATERAL LINES 2.15303 1.79814 0.00000 1.54157 LATERAL LINES 1.83166 1.61561 0.00000 1.50666 0.00000 1.58620 LATERAL LINES 0.00000 1.38134 LATERAL LINES 0.00000 1.44395
U. P. National Engineering Center National Electrification Administration
MAX I
SC Duty
Margin Remarks
2.86464 2.32896 2.10904 1.85435 1.70334 1.69336 1.59908
15 4 4 4 4 4 4
524 172 190 216 235 236 250
% % % % % % %
Adequate Adequate Adequate Adequate Adequate Adequate Adequate
2.30059 2.14564 2.01008 2.06014 1.87921
4 4 4 4 4
174 186 199 194 213
% % % % %
Adequate Adequate Adequate Adequate Adequate
2.15303 1.54157
4 4
186 % 259 %
Adequate Adequate
1.83166 1.50666 1.58620
4 4 4
218 % 265 % 252 %
Adequate Adequate Adequate
1.38134
4
290 %
Adequate
1.44395
4
277 %
Adequate
Power System Engineering for Non-Engineers
43
Power System Analysis 101
87
POWER SYSTEM RELIABILITY ANALYSIS
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
88
Reliability Analysis 1. What is Reliability? 2. Measuring Reliability 3. Component Reliability 4. System Reliability 5. Distribution System Reliability 6. Economics of Power System Reliability
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
44
Power System Analysis 101
89
What is Reliability? Outage (Component State) Component is not available to perform its intended function due to the event directly associated with that component (IEEE-STD-346).
Interruption (Customer State) Loss of service to one or more consumers as a result of one or more component outages (IEEE-STD-346).
Types of Interruptions Momentary Interruption. Service restored by switching operations (automatic or manual) within a specified time (5 minutes per IEEE-STD-346). Sustained Interruption. An interruption not classified as momentary U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
90
What is Reliability? A reliable piece of equipment or a System is understood to be basically sound and give troublefree performance in a given environment. But, How do you measure reliability? How do we compare reliability of the same equipment from two different manufacturers? Definition of Reliability Reliability is the probability that an equipment or system will perform satisfactorily for at least a given period of time when used under stated conditions. U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
45
Power System Analysis 101
91
Measuring Reliability 1
2
System Failure
3 Mathematical Reliability Model
Failure Events
5
Application (Reliability Index)
4 Reliability Data
Power System Reliability Evaluation U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
92
Measuring Reliability ORGANIZATION, CUSTOMER, kVA
INCIDENTS HISTORICAL ASSESSMENT
COMPONENT POPULATION COMPONENT PERFORMANCE SYSTEM DEFINITION
PREDICTIVE ASSESSMENT
U. P. National Engineering Center National Electrification Administration
HISTORICAL SYSTEM PERFORMANCE MANAGEMENT OPERATIONS ENGINEERING CUSTOMER INQUIRIES
PREDICTED SYSTEM PERFORMANCE COMPARATIVE EVALUATIONS AID TO DECISION-MAKING PLANNING STUDIES
Power System Engineering for Non-Engineers
46
Power System Analysis 101
93
Component Reliability Component Failure Data Item No.
Time-to-Failure (hrs.)
1
8
2
20
3
34
4
46
5
63
6
86
7
111
8
141
9
186
10
266
How Reliable is the component?
Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
94
Component Reliability Failure Density Function
Time
f(t) measure of the overall speed at which failures are occurring.
∆ ti
f(t)
0–8
8
8 – 20
12
20 – 34
14
34 – 46
12
46 – 63
17
63 – 86
23
86 – 111
25
111 – 141
30
141 – 186
45
186 – 266
80
1 10 = 0.0125 8 1 10 = 0.0084 12 1 10 = 0.0074 14 1 10 = 0.0084 12 1 10 = 0.0059 17 1 10 = 0.0043 23 1 10 = 0.0040 25 1 10 = 0.0033 30 1 10 = 0.0022 45 1 10 = 0.0013 80
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
47
Power System Analysis 101
95
f(t) fractional failures/hr.x10-2
Component Reliability 1.4 1.2 1.0 0.8
0.6 0.4 0.2
0
0
100 200 Operating time, hr.
300
Failure Density Function from Component Failure Data Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
96
Component Reliability Failure Hazard Function
h(t) measure of the instantaneous speed of failure [Propones to Failure]
Time
∆ ti
0–8
8
8 – 20
12
20 – 34
14
34 – 46
12
46 – 63
17
63 – 86
23
86 – 111
25
111 – 141
30
141 – 186
45
186 – 266
80
U. P. National Engineering Center National Electrification Administration
h(t) 1 10 = 0.0125 8 19 = 0.093 12 18 = 0.0096 14 17 = 0.0119 12 16= 0.0098 17 15= 0.0087 23 14= 0.0100 25 13 = 0.0111 30 12 = 0.0111 45 11 = 0.0125 80
Power System Engineering for Non-Engineers
48
Power System Analysis 101
97
Component Reliability h(t) failures/hr.x10-2
1.4 1.2
1.0 0.8
0.6 0.4 0.2 0
0
100
300
200
Operating time, hr.
Hazard Function from Component Failure Data 0.011 failure/hr x 8760 hrs/yr = 97 failures/yr Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
98
Component Reliability Reliability Function t
h (τ )d τ R (t ) = e ∫0 −
For the component with a hazard rate of 0.011 f/hr, R(1 hour) = 0.989
R(24 hours) = 0.768
For a component with a constant Hazard h = 0.01 f/yr
R(1) = 0.99
h = 0.02 f/yr
R(1) = 0.98
U. P. National Engineering Center National Electrification Administration
[Probability that the component will not fail in 1 year] Power System Engineering for Non-Engineers
49
Power System Analysis 101
99
Component Reliability h(t )
h(t )
Kt
λ
t
t
a. Constant Hazard
b. Increasing Hazard
h(t )
K0 t
h (τ )d τ R (t ) = e ∫0 −
K0 K1
t
t0
a. Decreasing Hazard
Reliability Function
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
100
Component Reliability The Bathtub Curve
a. Hazard Function
b. Failure Density Function U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
50
Power System Analysis 101
101
Component Reliability Hazard Model for Different System
a. Mechanical
b. Electrical
c. Software
Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
102
Component Reliability Weibull Model (A General Reliability Model) R (t )
h (t ) K
5
m=3 m=2
5 4 3
m=1
2 1
m = 0 .5 m=0 m = −0 .5
t→
1
2
Hazard function U. P. National Engineering Center National Electrification Administration
4 3
2 1
τ →
m = − 0 .5 m=0 m = 0 .5
m=1 m=2 m=3
1
2
Reliability function Power System Engineering for Non-Engineers
51
Power System Analysis 101
103
Component Reliability RELIABILITY ASSESSMENT of MERALCO Distribution Transformers* Distribution Transformer Failures • 1997: 996 DT Failures • Average of three (3) DT Failures/day • Lost Revenue during Downtime • Additional Equipment Replacement Cost • Lost of Customer Confidence Identify the Failure Mode of DTs Develop strategies to reduce DT failures * R. R. del Mundo, et. al. (2000) U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
104
Component Reliability METHODOLOGY: Reliability Engineering (Weibull Analysis of Failure Data) • Gather Equipment History (Failure Data) • Classify DTs (Brand, Condition, KVA, Voltage) • Develop Reliability Model • Determine Failure Mode • Recommend Solutions to Improve Reliability
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
52
Power System Analysis 101
105
Component Reliability Parametric Model • Shape Factor • Characteristic Life Shape Factor <1 =1 >1
Failure Mode
Hazard Function Decreasing Constant Increasing
Failure Mode Early Random Wear-out Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
106
Component Reliability MERALCO DTs (1989–1997) Brand
New
Recond
Rewind
Convert
Total
A
29,960
835
1,333
2,048
34,712
B
5,986
118
135
269
6,586
C
6,358
49
31
21
6,561
D
2,037
116
90
E
-
-
F
-
G H TOTAL
-
2,344
-
-
192
-
-
-
168
-
-
-
-
79
-
-
-
-
69
1,118
1,588
2,338
44,341
51,129
Note: Total Include Acquired DTs U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
53
Power System Analysis 101
107
Component Reliability Reliability Analysis: All DTs Interval 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000
Failures 1444 797 638 508 475 363 295 224 159 89 98 51 19 2 0
Survivors 57095 48852 39997 32802 27515 22129 18200 14690 11865 9010 6473 4479 2254 821 127
U. P. National Engineering Center National Electrification Administration
Hazard 0.0269 0.0178 0.0174 0.0167 0.0189 0.0178 0.0178 0.0167 0.0151 0.0114 0.0177 0.015 0.0122 0.0042 0 Power System Engineering for Non-Engineers
Power System Analysis 101
108
Component Reliability Reliability Analysis: All DTs 0.03 0.025
Hazard
Weibull Shape = 0.84 0.02 0.015 0.01
Failure Mode: EARLY FAILURE 0.005
Is it Manufacturing Defect?
0 0
200
400
600
800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000
Time Interval U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
54
Power System Analysis 101
109
Component Reliability Reliability Analysis: By Manufacturer BRAND A B C D E F G H
Size 34712 6586 6561 2344 192 168 79 69
Shape 0.84 0.81 0.86 0.76 0.85 0.86 0.76 0.98
Failure Mode Early Failure Early Failure Early Failure Early Failure Early Failure Early Failure Early Failure Early Failure
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
110
Component Reliability Reliability Analysis: By Manufacturer & Condition BRAND A B C D
New 1.11 0.81 0.81 0.67
Reconditioned Rewinded 1.23 1.12 1.29 1.27 1.13 0.77 1.11 1.49
U. P. National Engineering Center National Electrification Administration
Converted 1.4 1.23 0.94 -
Power System Engineering for Non-Engineers
55
Power System Analysis 101
111
Component Reliability Reliability Analysis: By Voltage Rating PRI 20 20 20 20 13.2 13.2 7.62 7.62 4.8 3.6 2.4
SEC 7.62 120/240 139/277 DUAL 120/240 240/480 120/240 DUAL 120/240 120/240 120/240
U. P. National Engineering Center National Electrification Administration
All DTs 0.75 0.79 1.14 0.72 0.88 0.91 0.99 0.77 0.87 0.78 1.15
New DTs 0.94 1.1 1.03 1.54 1.46 1.61 1.17 Power System Engineering for Non-Engineers
Power System Analysis 101
112
Component Reliability Reliability Analysis: By KVA Rating (New DTs) KVA 10 15 25 37.5 50 75 100 167 250 333
Shape 1.3 1.25 0.92 0.83 0.73 1.05 1.04 1.16 1.11 1.46
U. P. National Engineering Center National Electrification Administration
Failure Mode Wear-out Wear-out Early Early Early Random Random Random Random Wear-out Power System Engineering for Non-Engineers
56
Power System Analysis 101
113
Component Reliability MERALCO Distribution Transformer Reliability Analysis: Recommendations • Review Replacement Policies - New or Repair - In-house or Remanufacture • Improve Transformer Load Management Program - Predict Demand Accurately (TLMS) • Consider Higher KVA Ratings • Consider Surge Protection for 20 kV DTs Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
114
Component Reliability Preventive Maintenance and Hazard Rates Hazard rate
m
2m
3m
Effect of PM on Increasing Hazard Rate
Hazard rate
Hazard rate
m
2m
3m
Effect of PM on Constant Hazard Rate U. P. National Engineering Center National Electrification Administration
m
2m
3m
Effect of PM on Decreasing Hazard Rate Power System Engineering for Non-Engineers
57
Power System Analysis 101
115
Component Reliability RELIABILITY ASSESSMENT of MERALCO Power Circuit Breakers* Number of Feeder Power Circuit Breakers VOLTAGE
OCB
VCB
GCB
34.5 KV 13.8 KV 6.24 KV 4.8 KV TOTAL
149 7
160 28 26 2 216
41 2
156
43
MOCB
ACB
36 3
12 122 11 145
39
* R. R. del Mundo & Melendrez (2001) Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
116
Component Reliability RELIABILITY ASSESSMENT of MERALCO Power Circuit Breakers* Annual Failures of 34.5 kV OCBs 1997 Causes of Failure
Installed
1998 Failed
Installed
1999
2000
Failed
Installed
Failed
Installed
Failed
Average Failures (Units/yr)
Contact Wear
158
2
155
2
149
1
145
2
1.15
Bushing Failure
158
1
155
3
149
3
145
1
1.317
-
-
155
1
-
-
-
-
0.645
158
3
155
6
149
4
145
3
2.636
Mechanism Failure Totals
3 Circuit Breakers failing per year! Preventive Maintenance Policy: Time-based (Periodic) U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
58
Power System Analysis 101
117
Reliability Assessment of MERALCO Power Circuit Breakers 0.4
0.3 0.2 0.1 0
H a z a rd R a t e
0.2 H a z a r d R a te
H a za rd R a te
0.4
0.15 0.1 0.05 0 6
3 6 9 12 15 18 21 24 27 30 33 36 39 42 45 48 51 54 57 60
0.1 3 6 9 12 15 18 21 24 27 30 33 36 39 42 45 48 51 54 57 60 Time Interval (months)
13.8 kV MOCBs
34.5 kV GCBs
HAZARD FUNCTION CURVE FOR 6.24 KV MOCBs
HAZARD FUNCTION CURVE FOR ALL PCBs CONSIDERED
HAZARD FUNCTION CURVE FOR 6.24 KV ACBs
0.3 0.2 0.1 0
0.2 0.15 0.1 0.05 0
9 12 15 18 24 30 36 42 48 54 60
H az ard R ate
H a z a r d R a te
0.4
6
0.2
Time Interval (months)
34.5 kV OCBS OCBs
3
0.3
0
12 18 24 30 36 42 48 54 60
Time Interval (months)
H a z a rd R a t e
HAZARD FUNCTION CURVE FOR 13.8 KV MOCBs
HAZARD FUNCTION CURVE FOR 34.5 KV GCBs
HAZARD FUNCTION CURVE FOR 34.5 KV OCBs
6
0.4 0.3 0.2 0.1 0
.
3 6 9 12 15 18 21 24 27 30 33 36 39 42 45 48 51 54 57 60
12 18 24 30 36 42 48 54 60
Time Interval (months)
Time Interval (months)
Time Interval (months)
6.24 kV ACBs
6.24 kV MOCBs
All PCBs
TIME-BASED HAZARD FUNCTION Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
118
Reliability Assessment of MERALCO Power Circuit Breakers 0.00006x2
y= + 0.032
0.04
0.05
– 0.0007x
H a z a r d R a te
H a z a r d R a te
H a z a rd R a t e
0.05
0.25 0.2 0.15 0.1 0.05 0
0.03 0.02 0.01
10
15
20
25
30
25
35
50
34.5 kV OCBS OCBs
0.1 0
6.24 kV MOCBs
100
125
0.01 25
150
50
20
0.1 0 10
15
6.24 kV ACBs
125
150
HAZARD FUNCTION CURVE FOR 34.5 KV OCBs
0.2
Tripping Interval
100
13.8 kV MOCBs
0.3
5
75
Tripping Interval
H a z a rd R a te
H a z a rd R a te
0.2
Tripping Interval
75
HAZARD FUNCTION CURVE FOR 6.24 KV MOCBs
0.3
15
0.02
34.5 kV GCBs
HAZARD FUNCTION CURVE FOR 6.24 KV MOCBs
10
0.03
Tripping Interval
Tripping Interval
5
0.04
0
0
5
H a z a rd R a te
HAZARD FUNCTION CURVE FOR 34.5 KV GCBs
HAZARD FUNCTION CURVE FOR 34.5 KV GCBs
HAZARD FUNCTION CURVE FOR 34.5 KV OCBs
20
0.25 0.2 0.15 0.1 0.05 0 5
10
15
20
25
30
35
Tripping Interval
All PCBs
TRIPPING OPERATIONS-BASED HAZARD FUNCTION U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
59
Power System Analysis 101
119
Component Reliability RELIABILITY ASSESSMENT of MERALCO Power Circuit Breakers*
Hazard Rate
Schedule of Servicing for 41XV4 0.08 0.06 0.04 0.02 0 0
10
20
30
40
50
60
70
Number of Tripping Operations
Reliability-Based Preventive Maintenance Schedule Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
120
System Reliability Series Reliability Model R(x1)
R(x2)
R(x3)
R(x4)
Series System This arrangements represents a system whose subsystems of components form a series network. If any of the subsystem of component fails, the series system experiences an overall system failure. n
Rs = ∏ R( xi ) i =1 U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
60
Power System Analysis 101
121
System Reliability Parallel Reliability Model R(x1) R(x2)
This structure represents a system that will fail if and only if all the units in the system fail.
R(x3) R(x4)
n
Rs = 1 − ∏ [1 − R( xi )] i =1
Parallel Network U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
122
System Reliability Standby Redundancy Model R(x1) R(x2) R(x3) R(x4) This type of redundancy represents a distribution with one operating and n units as standbys. Unlike a parallel network where all units in the configuration are active, the standby units are not active. U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
61
Power System Analysis 101
123
System Reliability K-Out-of-N Reliability Model R(x1) R(x2) R(x3)
The system reliability for k-out-of-n number of independent and identical units is given by
n Rs = ∑ R i ( 1 − R )n −i i=k i n
This is another form of redundancy. It is used where a specified number of units must be good for the system success. Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
System Reliability Networks
124 1 2 3 5
4 6
7
Primary side
8
9
10 11 12 13 14 15 17
16 18
Reliability Network Models for Typical Substation Configurations of MERALCO*
19 21
20 22
23 25
24 26
27 28 29 30
31
32
33
34 35
Secondary side
36
37 38
Scheme 1: Single breaker-single bus (primary and secondary side)
39 40 41 42 43 44 45 46 47 48
49
50 51 52 53 54 55
* Source: A. Gonzales (Meralco) & R. del Mundo (UP), 2005 U. P. National Engineering Center National Electrification Administration
56 57
58
Power System Engineering for Non-Engineers
62
Power System Analysis 101
125
System Reliability Networks Reliability Network Diagram of Single breaker-single bus scheme (Scheme 1) 15λ λc
29λ λct
2λ λbus
4λ λd1
λp
2λ λb1
2λ λb2
3λ λd2
Summary of Substation Reliability Indices for Scheme 1 Event 1
Probability
λs (failure/yr)
Us (hr/yr)
Opened 115kV bus tie breaker & opened 34.5kV bus tie breaker (normal condition)
1.0
0.247152 0.828784
Total
1.0
0.247152 0.828784
where: λs - substation failure rate or interruption frequency Us – substation annual outage time or unavailability Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
126 L1
System Reliability Networks
L2
1
70 2
71
4
73
3
72 5
6
76 77
8
78
9 18
16
127 19
128
129
14 13
22 132
133
12
23 10
134
17
15
20 21
130 131
Reliability Network Models for Typical Substation Configurations of MERALCO
92
11
35 135
136
34
140
81 89
82
32
26
88 87
31
27
141
80
90 33
25
139
79 91
24
137 138
28
86
30
83 84 85 29
36
93
37
Primary side
94 95
38 39
96
40
97
41
Scheme 2: Single breaker-double bus (primary side) and two single breaker-single bus with bus tie breaker (secondary side)
74
75
7
98
Bank 1
42
99
101
44
102
45
103
46 104
47 49
48
105
106 107
50
109
52 110
53
111
54 55
126
112
56 125
59
119
124 121
58 61
Secondary side
108
51
57
Bank 2
100
43
122
60 123
120
115 117 116
113
114
118
62 63
64 65 66 67 68 69
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
63
Power System Analysis 101
127
Substation Reliability Models Reliability Network Diagram of Single breaker-double bus with normally opened 115kV bus tie breaker (Scheme 2) 16λ λc
29λ λct
2λ λbus
3λ λd1
2λ λb1
Event 1: Opened 115kV and 34.5kV bus tie breakers;
20λ λc
37λ λct
3λ λbus
5λ λd1
2λ λb1
λp
2λ λb2
3λ λd2
2λ λb2
3λ λd2
P1 = 0.997985
λp
Event 2: Closed 115kV bus tie breaker & opened 34.5kV bus tie breaker; P2 = 0.000188
20λ λc
37λ λct
2λ λbus
3λ λd1
2λ λb1
λp
3λ λb2
5λ λd2
Event 3: Closed 115kV bus tie breaker & closed 34.5kV bus tie breaker; P3 = 0.000000344
20λ λc
37λ λct
2λ λbus
3λ λd1
2λ λb1
λp
3λ λb2
5λ λd2
Event 4: Opened 115kV bus tie breaker & closed 34.5kV bus tie breaker; P4 = 0.00182614 Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
128
Substation Reliability Models Summary of Substation Reliability Indices for Scheme 2 Event
Probability
λs (failure/yr)
Us (hr/yr)
1
0.997985
0.251752
0.848919
2
0.000188
0.302966
1.008374
3
0.000000344
0.308936
1.023840
4
0.001826
0.308936
1.023840
1.0
0.251866
0.849275
Total
Event 1: With two primary lines energized & opened 34.5kV bus tie breaker; P1 = 0.997985 Power System Engineering U. P. National Engineering Center for Non-Engineers National Electrification Administration
64
Power System Analysis 101
129
Substation Reliability Models Reliability Network Diagram of Single breaker-double bus with normally closed 115kV bus tie breaker (Modified Scheme 2)
λ17
λ54
λΒ3
λΒ4
λΒ1
λΒ1 Β3
λΒ2 Β3
λΒ1 Β3
λΒ1
λΒ2 Β3
λΒ2 Β3
λΒ6
λΒ7
λΒ7 Β4
λλΒ4 29
λΒ9
λΒ6
λΒ4 29
λΒ5
Event 1: With two primary lines energized & opened 34.5kV bus tie breaker; P1 = 0.997985 λ17
λB1
λB2
λB3
λB5
λB4
Event 2: With one line, L2 interrupted & opened 34.5kV bus tie breaker;
λ17
λ29
λB1
λB2
λB5
λB8
P2 = 0.000188
λB9
λB10
λB11
Event 3: With one line, L2 interrupted and closed 34.5kV bus tie breaker; P3 = 0.000000344 Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
130
Substation Reliability Models Reliability Network Diagram of Single breaker-double bus with normally closed 115kV bus tie breaker (Modified Scheme 2)
λ29
λ111
λΒ5
λΒ8
λΒ10
λΒ1
λΒ1
λΒ3 Β2
λΒ3 Β6
λΒ3 Β2
λΒ6
λΒ6
λΒ7
λΒ7
λλΒ4 17
λΒ4 Β6
λΒ9
λΒ3 Β7
λλΒ3 Β7
λΒ7 Β3
λΒ9
λλΒ4 Β8
λλΒ4 17
λΒ11
Event 4: With two lines energized and closed 34.5kV bus tie breaker;
P4 = 0.001826140
Summary of Substation Reliability Indices for Modified Scheme 2
Event
Probability
λs (failure/yr)
Us,(hr/yr)
1
0.997985
0.176076
0.583548
2
0.000188
0.251122
0.847621
3
0.000000344
0.377120
1.261549
4
0.001826
0.233261
0.758472
1.0
0.176194
0.583923
Total
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
65
Power System Analysis 101
131
Substation Reliability Models Comparison of Substation Reliability Indices for Scheme 2 Scheme 2
λs (failure/yr)
Original (opened 115kV bus tie breaker) Modified (closed 115kV bus tie breaker)
Us (hr/yr)
0.251866
0.849275
0.176194
0.583923
Note: A remarkable 30% improvement in the performance of Scheme 2 by making the 115kV bus tie breaker normally closed.
Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
132
System Reliability Networks
B1
67
1
B4
17 16
15
32
81 79
78
12 11
B2
82 80
14 13
77
10
76
B5
75
9 7
8
73
6
74 72
71
5
70 4
Reliability Network Models for Typical Substation Configurations of MERALCO
3
69
68
Primary side
2 3
69
18
20
85 21
86
87
22
B3
83 84
19
88
23 24
89 26
B6
90
25
91 92
27 93
28 29
94 95
30 31
96
33
97
B7
Scheme 3: Ring bus (primary side) and two single breaker-single bus with bus tie breaker (secondary side)
34
99
36
101
37
104 105
41
106 43
107 108 109 110 111
48
112 49
51 53
113
50
114
130
B10
128
123 125
129
57
58
Secondary side 115
116
55 56
100
103
39
44 45 46 47
52
Bank 2
102
38 40 42
54
B8
98
35
Bank 1
127
119 117
121
126 124
120
118
122
59 60 62
61 63
B9
64 65 66
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
66
Power System Analysis 101
133
Substation Reliability Models Reliability Block Diagram of Ring Bus Scheme (Scheme 3) λB1
λB4
λB1
λB2
λB5
λ17
λB2
λB4
λ51
λB7
λB10
λB5 λB6
λB3
Event 1: With two primary lines energized & opened 34.5kV bus tie breaker;
λB1
P1 = 0.997985
λB4
λB1
λB3
λB5
λ31
λB2
λB4
λB8
λB9
λB10
λ51
λB6 λB6
λB3
Event 2: With two primary lines energized & closed 34.5kV bus tie breaker; P2 = 0.00182614 Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
134
Substation Reliability Models Reliability Block Diagram of Ring Bus Scheme (Scheme 3)
CONT. λB2
λB2
λB2
λB2
λ17
λB1
λB3
λ31
λB7
λ51
λB5
λB6
Event 3: With one primary line (L2) interrupted and opened 34.5kV bus tie breaker; λB2
λB3
λB3
λ31
λ17
λB5
P3 = 0.000188056
λB3
λB1
λB3
λB10
λB8
λB9
λ51
λB10
λB6
Event 4: With one primary line (L2) interrupted and closed 34.5kV bus tie breaker; P4 = 0.000000344 U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
67
Power System Analysis 101
135
Substation Reliability Models Summary of Substation Reliability Indices of Ring Bus (Scheme 3) Event
Probability
λs (failure/yr)
Us (hr/yr)
1
0.997985
0.137928
0.436499
2
0.001826
0.195112
0.618379
3
0.000188
0.147283
0.468233
4
0.000000344
0.204467
0.650114
1.0
0.138034
0.436836
Total
Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
136 L 1
System Reliability Networks
L 2 1
B2
1 7
1 61 4
1 5 1 3 1 1 9
1 21 0
9 9 3 1 8 89 7 8 5 8
B5
8
7
7 8
B1
6
3
5 4
3
8 1 2
7 9
Reliability Network Models for Typical Substation Configurations of MERALCO
2 2 0 2 2 4 2
B3
9 4
1 9 2 1
62 2 7 8 2 9
2 5
10 0 10 2 10 4
4 2
10 6 10 118 0
B9
Scheme 4: Breaker-and-a-half bus (primary side) and two single breaker-single bus with bus tie breaker (secondary side)
Bank 1
6 4 6 6 66 6 7 8 9 7 0 7 1 7 7 37 2 4 7 5 7 7 6 7
U. P. National Engineering Center National Electrification Administration
6 2
12 1
4 5
12 2
4 7 4 9 5 0 5 2
9 5 9 7 10 1 10 3
9 9
12 5
Primary side
10 5 10 7 10 9
B8
B10 12 3
12 4 12 6 12 7 12 9 13 1 13 3 13 5
12 13 8 5 0 4 5 13 5 5 5 2 13 6 75 4 8 5 13 6 13 9 6 13 7 6 0 8 1 15 14 4 0 14 14 15 14 14 6 14 2 158 1 4 2 0 15 14 14 15 14 14 3 5 3 1 9 7 5 5 1 3
6 3 6 5
4 4
4 6 4 8
8 0
11 1 11 11 2 11 3 11 4 5 11 6 11 11 7 8
11 9
1
8 2
10 5
12 0
4 3
2 3 9 0 3 3 1 3 3 2 3 4 3 5 3 6 3 3 7 83 4 9 0 4
B4
9 96 8
B7
2 3
B6
8 6
8 4
8 0
3 1 8
9 2 9 0 8 8
Bank 2
Secondary side 13 9
B1 1
Power System Engineering for Non-Engineers
68
Power System Analysis 101
137
Substation Reliability Models Reliability Block Diagram of Breaker-and-a-half Scheme (Scheme 4)
λΒ1 λΒ9
λ62
λΒ3
λΒ3
λΒ4
λΒ7
λΒ2 Β3
λλΒ1 6
λλΒ1 6
λΒ6 Β2
λΒ3 33
λλΒ7 7
λΒ8
λΒ7 33
λΒ5 34
λ17
λΒ2 17
λΒ3
λΒ12 λΒ5
A
λΒ3
λΒ1 Β3
λλ119 Β4
A
λΒ8 Β4
λΒ1 Β3
λΒ1 Β3
λΒ1 Β3
λΒ1 Β3
λλΒ1 6
λλΒ1 6
λΒ3
λΒ3
λλΒ3 6
λλΒ3 6
λλΒ2 17
λλΒ4 33
λΒ2
λλΒ2 33
λλΒ2 7
λΒ2
λΒ5 Β2
λΒ5 33
λλΒ5 7
λΒ5
λλ119 33
λ17 34
λΒ7 33
λλΒ8 34
λ119
λΒ4 Β2
λ17 33
λΒ6 34
λΒ8
λλ119 Β2
Event 1: With two primary lines energized and opened 34.5kV bus tie breaker;
P1 = 0.997985
Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
138
Substation Reliability Models Reliability Block Diagram of Breaker-and-a-half Scheme (Scheme 4)
λΒ7
λΒ1
λΒ10
λ139
λΒ11
λ62
λΒ8
λλ119 Β4
λΒ7
λΒ2 Β3
λλΒ1 6
λλΒ5 6
λΒ6 Β2
λΒ3 33
λλΒ2 7
λΒ8
λλΒ7 33
λΒ5 34
λΒ7
λλΒ2 17
λΒ4 Β3
λΒ12
λΒ5
A
λΒ7 Β3
λΒ3
λΒ1 Β3
A
λΒ7 Β4
λΒ5 Β3
λΒ3
λΒ3
λΒ2 Β3
λλΒ2 6
λλΒ2 6
λΒ5 Β3
λΒ4 Β3
λλΒ4 6
λλ119 6
λλ119 6
λΒ2 17
λΒ5 33
λΒ5 Β2
λΒ5 33
λλΒ5 7
λΒ4
λΒ6 Β2
λΒ5 33
λλΒ5 7
λΒ5
λΒ5
λλ119 33
λ17 34
λΒ6 33
λΒ8 34
λ119
λΒ5 Β2
λΒ8 33
λΒ6 34
λ17
λΒ7 Β2
λΒ6 Β2
Event 2: With two primary lines energized and closed 34.5kV bus tie breaker; P2 = 0.001826 U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
69
Power System Analysis 101
139
Substation Reliability Models Reliability Block Diagram of Breaker-and-a-half Scheme (Scheme 4) λΒ3
λΒ9
λ62
λΒ12
λΒ6 Β3
λΒ6 Β3
λΒ6 Β3
λΒ6 Β3
λΒ7 Β3
λΒ5
A
λΒ4
λΒ7
λΒ8 Β4
λλ119 Β4
λΒ4
λΒ4 17
λΒ7
λΒ7 Β3
λΒ8 Β3
λΒ8 Β3
λΒ8
λΒ3 17
λΒ3 17
λΒ2 Β3
λλ119 Β3
λλ119 Β3
λΒ2
λΒ3
λΒ4 17
λΒ2 Β4
λΒ3
λ119
λΒ4
λΒ4
λΒ2 Β4
λΒ3 Β4
A
Event 3: With one primary line (L1) interrupted and opened 34.5kV bus tie breaker;
P3 = 0.000188
Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
140
Substation Reliability Models Reliability Block Diagram of Breaker-and-a-half Scheme (Scheme 4)
λΒ10
λ139
λΒ11
λ62
λΒ12
λΒ7
λΒ6 Β3
λΒ7 Β3
λΒ7 Β3
λΒ7
λΒ8
λΒ7
λλΒ4 17
λΒ2 Β4
λΒ3
λΒ4 Β3
λλ119 Β3
λΒ7
λΒ7 Β4
λΒ5
Event 4: With one primary line (L1) interrupted and closed 34.5kV bus tie breaker;
P4 = 0.000000344
Summary of Substation Reliability Indices of Breaker-&-a-half (Scheme 4) Event
Probability
λs (failure/yr)
Us (hr/yr)
1
0.997985
0.137306
0.435214
2
0.001826
0.195120
0.611433
3
0.000188
0.146674
0.466972
4
0.000000344
0.204473
0.643165
1.0
0.137413
0.435545
Total
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
70
Power System Analysis 101
141
System Reliability Networks Substation Reliability Models Comparison of Substation Reliability Indices (Scheme 1 to 4) Configuration
λs (failures/yr)
Us (hrs/yr)
Scheme 1 (Single breaker-single bus)
0.247152
0.828784
Scheme 2 (Single breaker-double bus) - with normally opened 115kV tie bkr. - with normally closed 115kV tie bkr.
0.251866 0.176194
0.849275 0.583923
Scheme 3 (Ring bus)
0.138034
0.436836
Scheme 4 (Breaker-and-a-half bus)
0.137413
0.435545
Note: Scheme 3 & 4 - better than Scheme 1 & 2 by 44% & 45% respectively for substation failure rates. Scheme 3 & 4 - better than Scheme 1 & 2 by 47% & 49% respectively for substation interruption duration or unavailabilty. Scheme 3 & 4 - better than Modified Scheme 2 by 22% & 25% for substation failure rates & unavailability, respectively
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
142
Distribution System Reliability CUSTOMER-ORIENTED RELIABILITY INDICES System Average Interruption Frequency Index (SAIFI)* The average number of interruptions per customer served during a period
SAIFI =
Total number of customer interruptions Total number of customers served
System Average Interruption Duration Index (SAIDI) The average interruption duration per customer served during a period
SAIDI =
Sum of customer interruption duration Total number of customers served
Note: SAIFI for Sustained interruptions. MAIFI for Momentary Interruptions U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
71
Power System Analysis 101
143
Distribution System Reliability CUSTOMER-ORIENTED RELIABILITY INDICES Customer Average Interruption Frequency Index (CAIFI) The average number of interruptions per customer interrupted during the period
CAIFI =
Total number of customer interruptions Total number of customers interrupted
Customer Average Interruption Duration Index (CAIDI) The average interruption duration of customers interrupted during the period
CAIDI =
Sum of customer interruption duration Total number of customers interrupted
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
144
Distribution System Reliability CUSTOMER-ORIENTED RELIABILITY INDICES Average Service Availability Index (ASAI) The ratio of the total number of customer hours that service was available during a year to the total customer hours demanded Customer hours of available service
ASAI =
Customer hours demanded
Average Service Unavailability Index (ASUI) The ratio of the total number of customer hours that service was not available during a year to the total customer hours demanded C ustomer hours of unavailabl e service ASUI = Customer hours demanded U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
72
Power System Analysis 101
145
Distribution System Reliability LOAD- AND ENERGY-ORIENTED RELIABILITY INDICES Average Load Interruption Index (ALII) The average KW (KVA) of connected load interrupted per year per unit of connected load served.
ALII =
Total load interruption Total connected load
Average System Curtailment Index (ASCI) Also known as the average energy not supplied (AENS). It is the KWh of connected load interruption per customer served.
ASCI =
Total energy curtailment Total number of customers served
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
146
Distribution System Reliability LOAD- AND ENERGY-ORIENTED RELIABILITY INDICES Average Customer Curtailment Index (ACCI) The KWh of connected load interruption per affected customer per year.
ACCI =
Total energy curtailment Total number of customers affected
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
73
Power System Analysis 101
147
Distribution System Reliability Historical Reliability Performance Assessment Required Data: 1. Exposure Data N - total number of customers served P - period of observation 2. Interruption Data Nc - number of customers interrupted on interruption i d - duration of ith interruption, hours
d1 Number of customers interrupted
d3 d2
N1
N3
N2 Time
Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
148
Distribution System Reliability 2
1
S Source
L1
3 C
B
A
L2
L3
SYSTEM LOAD DATA Load Point L1 L2 L3
Number of Average Load Customers Demand (KW) 200 1000 150 700 100 400 INTERRUTION DATA
Number of Interruption Load Point Average Load Duration of Disconnected Event i Affected Curtailed (KW) Interruption Customers 1 L3 100 400 6 hours U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
74
Power System Analysis 101
149
Distribution System Reliability SAIFI =
∑N ∑N
C
=
100 200 + 150 + 100
= 0.222222 interruption customer - yr SAIDI =
∑ N d = (100 )(6 ) ∑ N 200 + 150 + 100 C
= 1.333333 hours customer - yr CAIDI =
∑ N d = (100 )(6 ) 100 ∑N C
C
= 6 hours custumer - interruption Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
150
Distribution System Reliability ASUI =
∑N
C
d
∑ N = SAIDI = 1.333333
8760 = 0.000152
8760
8760
ASAI = 1 − ASUI = 1 − 0.000152 = 0.999848
ASCI =
ENS = ∑N
∑ L d = (400 )(6 ) ∑ N 200 + 150 + 100 a
= 5.333333 KWh customer − yr Note: ENS - Energy Not Supplied U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
75
Power System Analysis 101
151
Distribution System Reliability Outage & Interruption Reporting
Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
Historical Reliability Performance Assessment Outage & Interruption Reporting *Not included in Distribution Reliability Performance Assessment
152
Date 1 2* 3 4* 5 6* 7 8 9 10* 11 12* 13 14* 15 16 17* 18* 19* 20
01/08/04 02/06/04 02/14/04 03/15/04 04/01/04 05/20/04 05/30/04 06/12/04 07/04/04 07/25/04 07/30/04 08/15/04 09/08/04 09/30/04 10/25/04 11/10/04 11/27/04 12/14/04 12/27/04 12/28/04
U. P. National Engineering Center National Electrification Administration
Affected hours 3 All 5, 6 4, 5, 6 3, 4 1, 2, 1 5 All 5 4 2 1, 2, 3 2, 3 3 3, 4, 2, 3 1, 2,
6
3
3
5 3
1.5 4 0.5 3 1.5 3.5 0.5 2 1 5 1 2 1 2.5 1.5 1.5 2 3.5 3 0.075
Line Fault at C Transmission Line Fault at D Pre-arranged Overload Pre-arranged Line Tripped Line fault Line Overload Transmission Line Fault Pre-arranged Line Fault Pre-arranged Line Tripped Line Fault at A Pre-arranged Pre-arranged Pre-arranged Line Fault
Power System Engineering for Non-Engineers
76
Power System Analysis 101
153
Distribution System Reliability Outage & Interruption Reporting Customer Count Month January February March April May June July August September October November December Annual Average
1 900 905 904 908 912 914 917 915 924 928 930 934 916
2 800 796 801 806 804 810 815 815 821 824 826 829 812
3 600 600 604 606 608 611 614 620 622 626 630 635 615
4 850 855 854 859 862 864 866 872 876 881 886 894 868
5 500 497 496 501 509 507 512 519 521 526 530 538 513
6 300 303 308 310 315 318 324 325 328 331 334 332 319
Total 3,950 3,956 3,967 3,990 4,010 4,024 4,048 4,066 4,092 4,116 4,136 4,162 4,043
Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
154
Distribution System Reliability Outage & Interruption Reporting Interruption Number
Load Points Affected
1 3
3 5 6 6 1 2 3 1 5 5 2 3 2 3
5 7
8 9 11 13 15 16
Number of Duration Customer Customers (Hrs.) Hours Affected Curtailed 600 497 303 310 912 804 608 914 512 512 821 626 826 630
U. P. National Engineering Center National Electrification Administration
1.5 0.5 0.5 1.5 0.5 0.5 0.5 2 1 1 1 1.5 1.5 1.5
Date
900 01/08/04 248.5 02/14/04 151.5 465 04/01/04 456 05/30/04 402 304 1,828 06/12/04 512 07/04/04 512 07/30/04 821 09/08/04 939 10/25/04 1,239 11/10/04 945
Power System Engineering for Non-Engineers
77
Power System Analysis 101
155
Distribution System Reliability Outage & Interruption Reporting Calculate the Annual Reliability Performance of the Distribution System (according to Phil. Distribution Code)
∑N ∑N ∑N d SAIDI = ∑N ∑N MAIFI = ∑N SAIFI =
C
C
C
Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
156
Distribution System Reliability Predictive Reliability Performance Assessment A Source
Distribution System
B Loads
Source
C
λA, rA, UA
A
λB, rB, UB
B Loads
λC, rC, UC
C
Required Data: 1. Component Reliability Data λi - failure rate of component i ri - mean repair time of component i 2. System Load Data Ni - number of customers at point i Li - the demand at point i U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
78
Power System Analysis 101
157
Distribution System Reliability Load Point Reliability Equivalents For parallel combinations:
For series combinations:
1 1
2
P
S 2
n
λs = Σ λi
λp = λ1λ2 (r1 + r2)
i=1
r1 r2 rp = __________ r1 + r2
n
Σ λiri
i=1
rs = _________ λs
Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
158
Distribution System Reliability S Source
2
1
3
B
A L1
C L3
L2
COMPONENT DATA Feeder A B C
Load Point L1 L2 L3
r λ (f/year) (hours) 0.2 6 0.1 5 0.15 8 SYSTEM LOAD DATA Number of Customers 200 150 100
U. P. National Engineering Center National Electrification Administration
Average Load Demand (KW) 1000 700 400 Power System Engineering for Non-Engineers
79
Power System Analysis 101
159
Load Point Reliability Equivalents For L1 λ1 = λ A
r1 = rA
U 1 = λ1r1
= 6 hrs
= 0.2 f yr
For L2
r2 =
λ2 = λ A + λB = 0.2 + 0.1
=
= 0.3 f yr
λ A rA + λB rB λ A + λB
(0.2 )(6 ) + (0.1)(5 )
0.2 + 0.1 = 5.666667 hrs
For L3
λ3 = λ A + λB + λC
r3 =
= 0.2 + 0.1 + 0.15
λ A rA + λB rB + λC rC λ A + λB + λB
(0.2)(6) + (0.1)(5) + (0.15)(8) =
= 0.45 f yr
= (0.2 )(6 ) = 1.2 hrs yr
U 2 = λ2 r2 = (0.3)(5.666667 ) = 1.7 hrs yr
U 3 = λ3 r3 = (0.45 )(6.444444 ) = 2.9 hrs yr
0.2 + 0.1 + 0.15 = 6.444444 hrs
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
160
Reliability Indices SAIFI =
∑ λ N = (0.2 )(200 ) + (0.3)(150 ) + (0.45 )(100 ) 200 + 150 + 100 ∑N i
i
i
= 0.288889 interruption customer − yr
SAIDI =
∑U N = (1.2 )(200 ) + (1.7 )(150 ) + (2.9 )(100 ) 200 + 150 + 100 ∑N i
i
i
= 1.744444 hours customer - yr
CAIDI =
∑U N ∑λ N i
i
i
i
=
SAIDI 1.744444 = SAIFI 0.288889
= 6.038462 hours customer - interruption
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
80
Power System Analysis 101
ASUI =
161
∑U N ∑ N i
i
i
SAIDI 1.744444 = 8760 8760
=
8760 = 0.000199
ASAI = 1 − ASUI = 1 − 0.000199 = 0.999801
ASCI =
ENS = ∑ Ni
∑ L ( )U ∑N a i
i
(1000 )(1.2 ) + (700 )(1.7 ) + (400 )(2.9 )
=
200 + 150 + 100
i
= 7.888889 KWh customer - yr
Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
162
Distribution System Reliability
Source
2
1 a
3 b
4 c
d D
A C B Typical radial distribution system
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
81
Power System Analysis 101
163
SYSTEM RELIABILITY DATA
Main
Component Length (km) λ (f/yr) r (hrs) 1 2 0.2 4 2 1 0.1 4 3 3 0.3 4 4 2 0.2 4 Lateral
a b c d
1 3 2 1
0.2 0.6 0.4 0.2
2 2 2 2
SYSTEM LOAD DATA Component No. of Customers Ave. Load Connected (KW) A B C D
1000 800 700 500
5000 4000 3000 2000
Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
164
RELIABILITY INDICES FOR THE SYSTEM
Main
Load pt. A Load pt. B Load pt. C Load pt. D U U U U Component λ r λ r λ r λ r (hrs/ (hrs/ (hrs/ (hrs/ failure (f/yr) (hrs) (f/yr) (hrs) (f/yr) (hrs) (f/yr) (hrs) yr) yr) yr) yr) 1 0.2 4 0.8 0.2 4 0.8 0.2 4 0.8 0.2 4 0.8 0.1
4
0.4
0.1
4
0.4
0.1
4
0.4
0.1
4
0.4
3 4
0.3 0.2
4 4
1.2 0.8
0.3 0.2
4 4
1.2 0.8
0.3 0.2
4 4
1.2 0.8
0.3 0.2
4 4
1.2 0.8
a b
0.2 0.6
2 2
0.4 1.2
0.2 0.6
2 2
0.4 1.2
0.2 0.6
2 2
0.4 1.2
0.2 0.6
2 2
0.4 1.2
c
0.4
2
0.8
0.4
2
0.8
0.4
2
0.8
0.4
2
0.8
d Total
0.2 2.2
2 2.73
0.4 6.0
0.2 2.2
2 2.73
0.4 6.0
0.2 2.2
2 2.73
0.4 6.0
0.2 2.2
2 2.73
0.4 6.0
Lateral
2
where : λtotal = ∑ λ ; U total = ∑ U ; rtotal = ∑ U U. P. National Engineering Center National Electrification Administration
∑λ Power System Engineering for Non-Engineers
82
Power System Analysis 101
SAIFI =
165
∑ λ N = (2.2)(1000) + (2.2)(800) + (2.2)(700) + (2.2)(500 ) 1000 + 800 + 700 + 500 ∑N i
i
i
= 2.2 int customer − yr SAIDI =
∑U N = (6.0 )(1000) + (6.0 )(800) + (6.0 )(700) + (6.0 )(500) 1000 + 800 + 700 + 500 ∑N i
i
i
= 6.0 hours customer - yr CAIDI =
∑U N ∑λ N i
i
i
i
=
SAIDI 6.0 = SAIFI 2.2
= 2.727273 hours customer - interruption
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
ASUI =
∑U N ∑ N i
i
8760 = 0.000685
166
i
=
SAIDI 6 .0 = 8760 8760
ASAI = 1 − ASUI = 1 − 0.000685 = 0.999315
ASCI =
∑L U ∑N ai
i
i
=
(5000 )(6.0 ) + (4000 )(6.0 ) + (3000 )(6.0 ) + (2000 )(6.0 )
1000 + 800 + 700 + 500 = 28.0 KWh customer - yr
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
83
Power System Analysis 101
167
Distribution System Reliability
Effect of lateral protection 2
1
Source
a
3
4
b
c
d D
A C B
Typical radial distribution system with lateral protections
Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
168
RELIABILITY INDICES WITH LATERAL PROTECTION Load pt. B Load pt. C Load pt. D U U U U Component λ r r r r λ λ λ (hrs/ (hrs/ (hrs/ (hrs/ failure (f/yr) (hrs) (f/yr) (hrs) (f/yr) (hrs) (f/yr) (hrs) yr) yr) yr) yr) 1 0.2 4 0.8 0.2 4 0.8 0.2 4 0.8 0.2 4 0.8 2 0.1 4 0.4 0.1 4 0.4 0.1 4 0.4 0.1 4 0.4 3 0.3 4 1.2 0.3 4 1.2 0.3 4 1.2 0.3 4 1.2 4 0.2 4 0.8 0.2 4 0.8 0.2 4 0.8 0.2 4 0.8 Main
Load pt. A
Lateral
a b c d Total
0.2
2
0.4 0.6
1.0
3.6
3.6
1.4
2
3.14
1.2
4.4
0.4
2
0.8
1.2
3.33
4.0
where : λtotal = ∑ λ ; U total = ∑ U ; rtotal = ∑ U U. P. National Engineering Center National Electrification Administration
0.2 1.0
2 3.6
0.4 3.6
∑λ Power System Engineering for Non-Engineers
84
Power System Analysis 101
SAIFI = ∑
λi Ni
∑N
169
(1.0)(1000) + (1.4)(800) + (1.2)(700) + (1.0)(500)
=
1000+ 800 + 700 + 500
i
= 1.153333 int customer− yr
SAIDI =
∑U N = (3.6 )(1000) + (4.4 )(800) + (4.0 )(700) + (3.6 )(500) 1000 + 800 + 700 + 500 ∑N i
i
i
= 3.906667 hours customer - yr CAIDI =
∑U N ∑λ N i
i
i
i
=
SAIDI 3.906667 = SAIFI 1.153333
= 3.387283 hours customer - interruption
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
ASUI =
∑U N ∑ N i
i
8760 = 0.000446
170
i
=
SAIDI 3.906667 = 8760 8760
ASAI = 1 − ASUI = 1 − 0.000446 = 0.999554 ASCI =
∑L U ∑N ai
i
i
=
(5000 )(3.6 ) + (4000 )(4.4 ) + (3000 )(4.0 ) + (2000 )(3.6 )
1000 + 800 + 700 + 500 = 18.266667 KWh customer - yr
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
85
Power System Analysis 101
171
Distribution System Reliability
Effect of disconnects 2
1
Source
a
3
4
b
c
d D
A C B Typical radial distribution system reinforce with lateral protections and disconnects
Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
172
RELIABILITY INDICES WITH LATERAL PROTECTION AND DISCONNECTS Load pt. B Load pt. C Load pt. D U U U U Component λ r r r r λ λ λ (hrs/ (hrs/ (hrs/ (hrs/ failure (f/yr) (hrs) (f/yr) (hrs) (f/yr) (hrs) (f/yr) (hrs) yr) yr) yr) yr) 1 0.2 4 0.8 0.2 4 0.8 0.2 4 0.8 0.2 4 0.8 2 0.1 0.5 0.05 0.1 4 0.4 0.1 4 0.4 0.1 4 0.4 3 0.3 0.5 0.15 0.3 0.5 0.15 0.3 4 1.2 0.3 4 1.2 4 0.2 0.5 0.1 0.2 0.5 0.1 0.2 0.5 0.1 0.2 4 0.8 Main
Load pt. A
Lateral
a b c d Total
0.2
2
0.4 0.6
1.0
1.5
1.5
1.4
2
1.2
1.89 2.65
0.4
2
0.8
1.2
2.75
3.3
where : λtotal = ∑ λ ; U total = ∑ U ; rtotal = ∑ U U. P. National Engineering Center National Electrification Administration
0.2 1.0
2 3.6
0.4 3.6
∑λ Power System Engineering for Non-Engineers
86
Power System Analysis 101
SAIFI =
173
∑ λ N = (1.0 )(1000) + (1.4 )(800) + (1.2)(700) + (1.0 )(500) 1000 + 800 + 700 + 500 ∑N i
i
i
= 1.153333 int customer − yr SAIDI =
∑U N = (1.5)(1000) + (2.65)(800) + (3.3)(700) + (3.6 )(500) 1000 + 800 + 700 + 500 ∑N i
i
i
= 2.576667 hours customer - yr CAIDI =
∑U N ∑λ N i
i
i
i
=
SAIDI 2.576667 = SAIFI 1.153333
= 2.234105 hours customer - interruption
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
ASUI =
∑U N ∑ N i
i
8760 = 0.000294
174
i
=
SAIDI 2.576667 = 8760 8760
ASAI = 1 − ASUI = 1 − 0.000294 = 0.999706 ASCI =
∑L U ∑N ai
i
i
=
(5000 )(1.5 ) + (4000 )(2.65 ) + (3000 )(3.3) + (2000 )(3.6 )
1000 + 800 + 700 + 500 = 11.733333 KWh customer - yr
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
87
Power System Analysis 101
175
Effect of protection failures RELIABILITY INDICES IF THE FUSES OPERATE WITH PROBABILITY OF 0.9
Load pt. B Load pt. C Load pt. D U U U U Component λ r r r r λ λ λ (hrs/ (hrs/ (hrs/ (hrs/ failure (f/yr) (hrs) (f/yr) (hrs) (f/yr) (hrs) (f/yr) (hrs) yr) yr) yr) yr) 1 0.2 4 0.8 0.2 4 0.8 0.2 4 0.8 0.2 4 0.8 2 0.1 0.5 0.05 0.1 4 0.4 0.1 4 0.4 0.1 4 0.4 3 0.3 0.5 0.15 0.3 0.5 0.15 0.3 4 1.2 0.3 4 1.2 4 0.2 0.5 0.1 0.2 0.5 0.1 0.2 0.5 0.1 0.2 4 0.8 Main
Load pt. A
Lateral
a b c d Total
0.2 2 0.06 0.5 0.04 0.5 0.02 0.5 1.12 1.39
0.4 0.03 0.02 0.01 1.56
0.02 0.5 0.6 2 0.04 0.5 0.02 0.5 1.48 1.82
0.01 0.02 0.5 1.2 0.06 0.5 0.02 0.4 2 0.01 0.02 0.5 2.69 1.3 2.58
where : λtotal = ∑ λ ; U total = ∑ U ; rtotal = ∑ U
0.01 0.03 0.8 0.01 3.35
0.02 0.5 0.06 0.5 0.04 0.5 0.2 2 1.12 3.27
0.01 0.03 0.02 0.4 3.66
∑λ Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
176
Effect of load transfer to alternative supply RELIABILITY INDICES WITH UNRESTRICTED LOAD TRANSFERS
Load pt. B Load pt. C Load pt. D U U U U Component λ r r r r λ λ λ (hrs/ (hrs/ (hrs/ (hrs/ failure (f/yr) (hrs) (f/yr) (hrs) (f/yr) (hrs) (f/yr) (hrs) yr) yr) yr) yr) 1 0.2 4 0.8 0.2 0.5 0.1 0.2 0.5 0.1 0.2 0.5 0.1 2 0.1 0.5 0.05 0.1 4 0.4 0.1 0.5 0.05 0.1 0.5 0.05 3 0.3 0.5 0.15 0.3 0.5 0.15 0.3 4 1.2 0.3 0.5 0.15 4 0.2 0.5 0.1 0.2 0.5 0.1 0.2 0.5 0.1 0.2 4 0.8 Main
Load pt. A
Lateral
a b c d Total
0.2
2
0.4 0.6
2
1.2 0.4
1.0
1.5
1.5
1.4
1.39 1.95
1.2
where : λtotal = ∑ λ ; U total = ∑ U ; rtotal = ∑ U U. P. National Engineering Center National Electrification Administration
2
0.8
1.88 2.25
0.2 1.0
2 1.5
0.4 1.5
∑λ Power System Engineering for Non-Engineers
88
Power System Analysis 101
177
Effect of load transfer to alternative supply RELIABILITY INDICES WITH RESTRICTED LOAD TRANSFERS
Load pt. B Load pt. C Load pt. D U U U U Component λ r r r r λ λ λ (hrs/ (hrs/ (hrs/ (hrs/ failure (f/yr) (hrs) (f/yr) (hrs) (f/yr) (hrs) (f/yr) (hrs) yr) yr) yr) yr) 1 0.2 4 0.8 0.2 1.9 0.38 0.2 1.9 0.38 0.2 1.9 0.38 2 0.1 0.5 0.05 0.1 4 0.4 0.1 1.9 0.19 0.1 1.9 0.19 3 0.3 0.5 0.15 0.3 0.5 0.15 0.3 4 1.2 0.3 1.9 0.57 4 0.2 0.5 0.1 0.2 0.5 0.1 0.2 0.5 0.1 0.2 4 0.8 Section
Load pt. A
Distributor
a b c d Total
0.2
2
0.4 0.6
2
1.2 0.4
1.0
1.5
1.5
1.4
1.59 2.23
2
1.2
0.8 0.2 1.0
2.23 2.67
where : λtotal = ∑ λ ; U total = ∑ U ; rtotal = ∑ U
2 2.3
0.4 2.3
∑λ Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
178
Distribution System Reliability SUMMARY OF INDICES Load Point A λ (f/yr) r (hrs) U (hrs/yr) Load Point B λ (f/yr) r (hrs) U (hrs/yr) Load Point C λ (f/yr) r (hrs) U (hrs/yr) Load Point D λ (f/yr) r (hrs) U (hrs/yr)
Case 1
Case 2
Case 3
Case 4
Case 5
Case 6
2.2 2.73 6.0
1.0 3.6 3.6
1.0 1.5 1.5
1.12 1.39 1.56
1.0 1.5 1.5
1.0 1.5 1.5
2.2 2.73 6.0
1.4 3.14 4.4
1.4 1.89 2.65
1.48 1.82 2.69
1.4 1.39 1.95
1.4 1.59 2.23
2.2 2.73 6.0
1.2 3.33 4
1.2 2.75 3.3
1.3 2.58 3.35
1.2 1.88 2.25
1.2 2.23 2.67
2.2 2.73 6.0
1.0 3.6 3.6
1.0 3.6 3.6
1.12 3.27 3.66
1.0 1.5 1.5
1.0 2.34 2.34
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
89
Power System Analysis 101
179
Distribution System Reliability SUMMARY OF INDICES (cont.) Case 1 Case 2 Case 3 Case 4 Case 5 Case 6 Sytem Indices SAIFI 2.2 1.15 1.15 1.26 1.15 1.15 SAIDI 6.0 3.91 2.58 2.63 1.80 2.11 CAIDI 2.73 3.39 2.23 2.09 1.56 1.83 ASAI 0.999315 0.999554 0.999706 0.999700 0.999795 0.999759 ASUI 0.000685 0.000446 0.000294 0.003000 0.000205 0.000241 ENS 84.0 54.8 35.2 35.9 25.1 29.1 ASCI 28.0 18.3 11.7 12.0 8.4 9.7 Case 1. Base case. Case 2. As in Case 1, but with perfect fusing in the lateral distributors. Case 3. As in Case 2, but with disconnects on the main feeders. Case 4. As in Case 3, probability of successful lateral distributor fault clearing of 0.9. Case 5. As in Case 3, but with an alternative supply. Case 6. As in Case 5, probability of conditional load transfer of 0.6. U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
180
Economics of Power System Reliability Supply Cost • Investment Cost • Operation and Maintenance Cost • Fuel Cost IC + O&M + FC Annual Supply Cost (ASC) = Annual kWh Generation
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
90
Power System Analysis 101
181
Supply Cost Luzon Grid Supply Cost* LOLP (days/yr)
Frequency (per year)
Duration (Hours)
Supply Cost (Php/kWh)
12.26
70
2.11
0.90
6.25
38
2.00
0.94
1.88
13
1.73
1.01
0.94
7
1.61
1.03
0.45
4
1.50
1.06
0.21
2
1.38
1.09
0.08
0.73
1.31
1.11
0.04
0.31
1.30
1.14
Source: del Mundo (1991) Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
182
Supply Cost
Luzon Grid Supply Cost Source: del Mundo (1991) U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
91
Power System Analysis 101
183
Outage Cost Impact of Power Interruptions To Electric Utility
• Loss of revenues • Additional work • Loss of confidence
To Customers
• Dissatisfaction • Interruption of productivity • Additional investment for alternative power supply
To National Economy
• Loss value added/income • Loss of investors • Unemployment
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
184
Outage Cost Impact to National Economy: NEDA Study (1974) P 342,380 per day – losses due to brownout in Cebu-Mandaue area Business
Survey (1980)
P1.4 Billion – losses due to brownouts in 1980 CRC
Memo No. 27 (1988)
P 3.4 Billion – loss of the manufacturing sector in 1987 due to power outages Viray
& del Mundo Study (1988)
P 25 – losses in Value Added per kWh curtailment Sinay
Report (1989)
45% – loss in Value Added in the manufacturing sector in Cebu due to power outages U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
92
Power System Analysis 101
185
Outage Cost Impact to Customers: A. Short-Run Direct Cost • Opportunity losses during outages
• • • • • • •
Opportunity losses during restart period Raw materials spoilage Finish products spoilage Idle workers Overtime Equipment damage Special operation and maintenance during restart period
B. Long-Run Adaptive Response Cost • • • • •
Standby generators Power plant Alternative fuels Transfer location Inventory
U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
186
Outage Cost Outage Cost to Industrial Sector in Luzon (0.0086 + 0.0023D)F + 0.1730 Pesos/kWh Where, F – Frequency of Interruptions D – Average Duration of Interruptions
Losses of MERALCO Industrial Customers in 1989 Energy Sales: 3.781 billion kWh Outage Cost: Php 0.3544/kWh Total Losses: Php 1.34 billion Source: del Mundo (1991) U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
93
Power System Analysis 101
187
Outage Cost Luzon Grid Outage Cost* LOLP (days/yr)
Frequency (per year)
Duration (Hours)
Outage Cost (Php/kWh)
12.26
70
2.11
1.12
6.25
38
2.00
0.68
1.88
13
1.73
0.34
0.94
7
1.61
0.26
0.45
4
1.50
0.22
0.21
2
1.38
0.20
0.08
0.73
1.31
0.18
0.04
0.31
1.30
0.18
Source: del Mundo (1991) Power System Engineering for Non-Engineers
U. P. National Engineering Center National Electrification Administration
Power System Analysis 101
188
Outage Cost
Luzon Grid Outage Cost Source: del Mundo (1991) U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
94
Power System Analysis 101
189
Total Cost Luzon Grid Total Cost
ATC = ASC + AOC
LOLP (days/yr)
Supply Cost (Php/kWh)
Outage Cost (Php/kWh)
Total Cost (Php/kWh)
12.26
0.90
2.11
2.02
6.25
0.94
2.00
1.62
1.88
1.01
1.73
1.35
0.94
1.03
1.61
1.29
0.45
1.06
1.50
1.28
0.21
1.09
1.38
1.29
0.08
1.11
1.31
1.29
0.04
1.14
1.30
1.32
Source: del Mundo (1991) U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
Power System Analysis 101
190
Optimal Reliability Level
Luzon Grid Total Cost Source: del Mundo (1991) U. P. National Engineering Center National Electrification Administration
Power System Engineering for Non-Engineers
95
Power System Analysis 101
U. P. National Engineering Center National Electrification Administration
191
Power System Engineering for Non-Engineers
96