2

3

10.00

4.00

3.00

1

4

1.50

3.00

4.00

3.00

1.00 RECOMMENDING APPROVAL:

Fire Exit

2.00

S1 W4

3.50

3.50

3.00

W1

S1

S1

W1 W4

W3 B

3.00

10.00

3.00

S1

S1

BUILDING OFFICIAL

DATE

S1 W2 a

S1

S1 S3

C storage

3.50

S1

C4

3.50

10.00 C

GROUND FLOOR

a

W1 S1 C3

LIGHTING LAYOUT

S3 S1 D

S3

B

C1

S3

REPUBLIC OF THE PHILIPPINES DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS OFFICE OF THE BUILDING OFFICIAL MUNICIPALITY OF SOGOD PROVINCE OF SOUTHERN LEYTE

4

0.80 1.20

W4 A

C2

3

10.00

1.50

W4

A

2

0.85 0.94

1

SCALE

1

:

100

M

b GB

FG

D1

D

S1

S1

S1

ELEV. +00

b C5

SCHEDULE SWITCH

CIRCUIT NO.

LOAD DESCRIPTION

1 2 3 4 5 6 7 8 9 10 11 12

LIGHTING OUTLET LIGHTING OUTLET LIGHTING OUTLET LIGHTING OUTLET LIGHTING OUTLET ACU OUTLET ACU OUTLET CONVENIENCE OUTLET CONVENIENCE OUTLET CONVENIENCE OUTLET ACU OUTLET SPARE

S1 1 3 3 3 3

S2

S3 2 2 2 2 1

OF

SECOND FLOOR LIGHTING LAYOUT SCALE

1

:

100

M

LOADS

POWER / WATTAGE

VOLTAGE

CURRENT

106W 106W 97W 97W 97W 3200VA 3200VA 1200VA 1600VA 1200VA 3200VA

220V 220V 220V 220V 220V 220V 220V 220V 220V 220V 220V 220V

0.4818A 0.4818A 0.4409A 0.4409A 0.4409A 14.5454A 14.5454A 5.4545A 7.2727A 5.4545A 14.5454A

CIRCUIT PROTECTION 15 AT,2P 15 AT,2P 15 AT,2P 15 AT,2P 15 AT,2P 20 AT,2P 20 AT,2P 20 AT,2P 20 AT,2P 20 AT,2P 20 AT,2P 20 AT,2P

CONDUCTOR SIZE

CONDUIT SIZE

3.5mm 3.5mm 3.5mm 3.5mm 3.5mm 5.5mm 5.5mm 5.5mm 5.5mm 5.5mm 5.5mm 5.5mm

ELECTRICAL SPECIFICATIONS 220V, 60 Hz

1. ALL ELECTRICAL WORKS AND INSTALLATION THERE IN SHALL BE DONE IN ACCORDANCE WITH THE PROVISIONS OF THE LATEST APPROVED EDITION OF THE PHILIPPINE ELECTRICAL CODE WITH THE RULES AND REGULATIONS OF THE NATIONAL AND LOCAL AUTHORITIES CONCERNED IN THE ENFORCEMENT OF ELECTRICAL LAWS AND ORDINANCES AND WITH THE POLICIES OF THE LOCAL UTILITY COMPANY CONCERNED. 2. NO WIRE SMALLER THAN No. 3.5 mm2 AWG TWG SHAAL BE USED. 3. ALL MATERIALS USED SHALL BE NEW AND OF APPROVED TYPE FOR BOTH LOCATION AND PURPOSES INTENDED. 4. ALL OUTDOOR INSTALLATION SHALL BE OF WEATHER PROOF TYPE. 5. ALL ELECTRICAL WORKS AND INSTALLATIONS HERE IN SHALL BE DONE UNDER THE DIRECT SUPERVISION OF A DULY REGISTERED ELECTRICAL ENGINEER OR MASTER ELECTRICIAN.

2-38.0mm

M 100 AT 2-3.5mm

2-3.5mm

15 AT 2

2-3.5mm

2-3.5mm

2-3.5mm

2-5.5mm

2-3.5mm

2-5.5mm

2-5.5mm

2-5.5mm

2-5.5mm

2-5.5mm

2-5.5mm

15 AT 4

10

C:\Users\user\Documents\calimbas plan\logo copy.bmp

NO PORTION OF THIS SET OF PLAN SHOULD BE COPIED EITHER MANUALY OR ELECTRONICALLY WITHOUT THE WRITTEN CONSENT OF THIS OFFICE.

7 20 AT

20 AT

FROM THE OFFICE OF:

5 20 AT

20 AT

SPARE

3 15 AT

20 AT 8

1 15 AT

20 AT 6

Computation for the total current:

15 AT 2-3.5mm

9 20 AT

SEAL

11

It = [total connected load + 25% of the largest motor] 220 V It =14,103 W + (0.25)(3200W) It = 67.74 amperes Ita = (67.74 A) ( .90 ) Ita =60.96 amperes Note: Assume 90% demand factor for commercial building Therefore: Use 100 AT, 2P circuit breaker for main protection.

NAME OF PROJECT:

APPROVED AS PER PLAN:

SLSU ALUMNI OWNER

ELECTRICAL ENGINEER PRC No.: PTR No.

Date Reg.

T I N No.

Date:

Place:

LOCATION: BRGY. SAN ROQUE,SOGOD, SOUTHERN LEYTE

LOCATION: BRGY. SAN ROQUE,SOGOD, SOUTHERN LEYTE

SHEET CONTENTS:

SHEET NUMBER