DUCT TRAVERSE SHEET
ATBEC ADVANCED TESTING BALANCING AND ENERGY CONSULTING 657 Meeker Ave., Brooklyn, NY 11222/Ph #: (718) 486-6764 Fax: (718) 486-8249 PROJECT Lombardy Hotel DATE __ 9-25-09______ SYSTEM _______TX-1 _________________________ JOB # ___09-04_________ LOCATION _ 20th Floor______ TECH _K. Wilton____ 1A NO:____1016295___ DESIGN DATA OD
Type:
Main
ID
Hgt/Diam (in.)
48
Serves Outlets
Shape: Rect
Width (in.)
48
Air Flow Temp °F
Insulation Type:
Area (sq. ft.)
16
TEST DATA Point
A B C D E F
1 1024
2 979
3 844
4 1235
5 1150
6 1141
7 1261
8 1196
9 1371
1175
1061
1207
1426
1427
1398
1587
1581
1226
1136
1187
1177
1287
1426
1419
1559
1572
1277
884
1215
1092
1426
1415
1225
1407
1287
1500
1121
1381
1124
1426
1275
1123
1174
1537
1471
1085
1321
1295
1262
1005
1217
1259
1387
1065
Design CFM % of Design
Total FPM Num of Reading 68,188 54 Static Pressure, in w.g. 1.0
Remarks Fan on high speed.
Average FPM 1,262
10
11
12
Area (sq. ft.) 16
13
14
15
Total CFM 20,192