GEN-X
superior performance
01 Gen-X
Environment control in mission critical space is a great concern in today’s technology requirements. Therefore, the precision air conditioner plays an important role in this environment.
The Citec GEN-X series of precision air conditioning system is the real solution for critical space. It is designed for 24/7 and round the clock operation. Quick reactions to drastic change in heat load always become its main duty in order to prevent huge temperature fluctuation. It is designed to meet the stringent demands of Tier IV data centers and other critical space which provide energy efficient environmental control in temperature, humidity and air filtration. The advance microprocessor controls are compatible with a wide range of remote monitoring systems.
P r e c is i o n E f f iciency C r eativity
GEN-X
03 Gen-X
The GEN-X series of air conditioning system is compact and stylish with the highest performance. It is specially design for medium and large data center. The GEN-X series solve the increasing heat load problem in today’s valuable floor space with the minimal footprint. In a world that tolerates zero downtime, system availability is essential. With that in mind, GEN-X is designed with the highest quality components selected for proven reliability.
It is essential to carry out regular maintenance for optimum performance. Ease of maintenance has always been the main concern in designing GEN-X. The Genius Controller will automatically indicates when maintenance is required on individual components and all servicing can be carried out through the front doors of the unit. The GEN-X series is available in four (4) ranges which designed and cater for various market demands namely: • Commander Range (Chilled Water System) • Deluxe Range (Dual Coil Chilled Water System) • Elegant Range (Air Cooled, Water Cooled, Dual Coil Systems) • Performer Range (Air Cooled and Water Cooled Systems)
“GEN-X is designed with the highest quality components selected for proven reliability”
04 Gen-X
3
4
2
1
5
7
6
1) Electrical Panel 2) Coil 3) Air Filter 4) Scroll Compressor 5) Electronic Expansion Valve 6) Belt Driven Fan 7) Heater
05 Gen-X
Commander Range (Chilled Water System) The GEN-X Commander Range of Chilled Water air conditioning system is designed with a minimal footprint and to meet the higher capacity requirement.
• Capacity ranges from 55kW to 150kW • Available in both upflow and downflow configurations • Cooling, humidification, dehumidification, reheating, filtration • Factory pre-piped, wired and tested • Precisely control temperature and humidity to ±1ºC and ±5%RH Features Coil Large face area/low face velocity design for precise control of cooling and dehumidification. Belt driven fan blowers (downflow system - forward or backward curve) Adjustable for higher static requirement. Plug fan blowers (upflow system – backward curve) More efficient and less noise. Optional EC fan Energy saving and efficient. Heaters 2-stage stainless steel heaters of finned design for extended life. Low watt density, sheathed elements are made of stainless steel with integral high efficiency fins, reducing sheath temperatures and eliminating ionization. It also keeps the temperature from going too low during dehumidification cycle.
Electrical panel High Low voltage segregation and each components are protected by individual MCB. High voltage compartment contains the contactors, miniature circuit breaker, transformer and other components and protected by a separate over-current protective device.
Microprocessor control with in house program Built in auto-sequencing feature enables interfacing with most of the commonly used serial communication standards. With an optional interface card, it can be integrated into the most widespread BMS systems.
Air Filter Protect against airborne contaminants within the critical environment which can damage storage media and charged electronics components.
Control and monitoring system Prevent and reduce costly downtime duration with mature monitoring systems that provide complete supervision all the time on temperature and humidity.
Touch screen display Comes with a user friendly menu for ease of navigation. Displays graphical information and status of trend and plotted graphs for both temperature and humidity in 3 different languages namely English, Chinese and Thai.
06 Gen-X
Deluxe Range (Dual Coil Chilled Water System) The GEN-X Deluxe Range of Dual Coil Chilled Water air conditioning system is designed to meet the requirements of system availability in Tier IV data centers. The unit is designed specifically for dual chilled water source application which is excellent in redundancy and availability.
• Capacity ranges from 60kW to 135kW • Available in both upflow and downflow configurations • Cooling, humidification, dehumidification, reheating, filtration • Factory pre-piped, wired and tested • Precisely control temperature and humidity to ±1ºC and ±5%RH Features Dual Chilled Water Coil Each with large face area/low face velocity design for precise control of cooling and dehumidification.
Heaters 2-stage stainless steel heaters of finned design for extended life. Low watt density, sheathed elements are made of stainless steel with integral high efficiency fins, reducing sheath temperatures and eliminating ionization. It also keeps the temperature from going too low during dehumidification cycle. Electrical panel High Low voltage segregation and each components are protected by individual MCB. High voltage compartment contains the contactors, miniature circuit breaker, transformer and other components and protected by a separate over-current protective device.
Belt driven fan blowers (downflow system - forward or backward curve) Adjustable for varying static requirement. Plug fan blowers (upflow system – backward curve) More efficient and less noise. Optional EC fan Energy saving and efficient. Air Filter Protect against airborne contaminants within the critical environment which can damage storage media and charged electronics components. Touch screen display Comes with a user friendly menu for ease of navigation. Displays graphical information and status of trend and plotted graphs for both temperature and humidity in 3 different languages namely English, Chinese and Thai.
Microprocessor control with in house program Built in auto-sequencing feature enables interfacing with most of the commonly used serial communication standards. With an optional interface card, it can be integrated into the most widespread BMS systems.
Control and monitoring system Prevent and reduce costly downtime duration with mature monitoring systems which provide complete supervision all the time on temperature and humidity.
07 Gen-X
Elegant Range (Air Cooled, Water Cooled and Dual Coil Systems) The GEN-X Elegant Range of Air Cooled, Water Cooled and Dual Coil air conditioning systems are designed according to the stringent requirement of data centers. It provides high sensible cooling to data center in energy efficient way. The Elegant Range is easily customizable for larger capacity and capable for high external static pressure application. The dual coil options provide redundancy and flexibility with dual cooling source thus enable even higher energy efficiency.
• Capacity ranges from 50kW to 90kW • Available in both upflow and downflow configuration • Cooling, humidification, dehumidification, reheating, filtration • Factory pre-piped, wired and tested
Belt driven fan blowers (downflow system - forward or backward curve) Adjustable for varying static requirement. Plug fan blowers (upflow system – backward curve) More efficient and less noise.
• Precisely control temperature and humidity to ±1ºC and ±5%RH Features Scroll compressor (twin circuit) Efficient and reliable performance with a robust design which concern on quiet operation and continual smooth compression process. The discharge gas and vibration are kept at a low level. It has internal vibration isolation mountings, pressure safety controls and built-in overload protection gives excellent durability. Coil Large face area/low face velocity design for precise control of cooling and dehumidification. Electronic expansion valve Provide fast and precise response to changes in room condition which gives more stable unit operation and save energy at low load condition. The real time superheat monitoring enable early detection on refrigerant leakage, at the same time ensures proper refrigerant charge.
EC fan as option Energy saving and efficient. Heaters 2-stage stainless steel heaters of finned design for extended life. Low watt density, sheathed elements are made of stainless steel with integral high efficiency fins, reducing sheath temperatures and eliminating ionization. It also keeps the temperature from going too low during dehumidification cycle. Electrical panel High Low voltage segregation and each components are protected by individual MCB. High voltage compartment contains the contactors, miniature circuit breaker, transformer and other components and protected by a separate over-current protective device.
Air Filter Protect against airborne contaminants within the critical environment which can damage storage media and charged electronics components. Touch screen display Comes with a user friendly menu for ease of navigation. Displays graphical information and status of trend and plotted graphs for both temperature and humidity in 3 different languages namely English, Chinese and Thai. Microprocessor control with in house program Built in auto-sequencing feature enables interfacing with most of the commonly used serial communication standards. With an optional interface card, it can be integrated into the most widespread BMS systems. Control and monitoring system Prevent and reduce costly downtime duration with mature monitoring systems which provide complete supervision all the time on temperature and humidity.
08 Gen-X
Performer Range (Air Cooled and Water Cooled Systems) The GEN-X Performer Range of Air Cooled and Water Cooled air conditioning systems are compact and stylish. It is designed to achieve highest performance with a minimal foot print. It also solves the increasing heat load problem in today’s valuable floor space.
• Capacity ranges from 60kW to 120kW • Available in both upflow and downflow configuration
Coil Large face area/low face velocity design for precise control of cooling and dehumidification.
• Cooling, humidification, dehumidification, reheating, filtration • Factory pre-piped, wired and tested • Precisely control temperature and humidity to ±1ºC and ±5%RH
Air Filter Protect against airborne contaminants within the critical environment which can damage storage media and charged electronics components.
Features Scroll compressor (twin circuit) Efficient and reliable performance with a robust design which concern on quiet operation and continual smooth compression process. The discharge gas and vibration are kept at a low level. It has internal vibration isolation mountings, pressure safety controls and built-in overload protection gives excellent durability.
Electrical panel High Low voltage segregation and each components are protected by individual MCB. High voltage compartment contains the contactors, miniature circuit breaker, transformer and other components and protected by a separate over-current protective device.
Electronic expansion valve Provide fast and precise response to changes in room condition which gives more stable unit operation and save energy at low load condition. The real time superheat monitoring enable early detection on refrigerant leakage, at the same time ensures proper refrigerant charge. Belt driven fan blowers (downflow system - forward or backward curve) Adjustable for varying static requirement Plug fan blowers (upflow system – backward curve) More efficient and less noise. Optional EC fan Energy saving and efficient. Heaters 2-stage stainless steel heaters of finned design for extended life. Low watt density, sheathed elements are made of stainless steel with integral high efficiency fins, reducing sheath temperatures and eliminating ionization. It also keeps the temperature from going too low during dehumidification cycle.
Touch screen display Comes with a user friendly menu for ease of navigation. Displays graphical information and status of trend and plotted graphs for both temperature and humidity in 3 different languages namely English, Chinese and Thai. Microprocessor control with in house program Built in auto-sequencing feature enables interfacing with most of the commonly used serial communication standards. With an optional interface card, it can be integrated into the most widespread BMS systems. Control and monitoring system Prevent and reduce costly downtime duration with mature monitoring systems which provide complete supervision all the time on temperature and humidity.
09 Gen-X
Commander Range Technical Specifications Models
CXD / U_ _ _
55
60
75
90
100
130
140
150
Airflow
m³/s
4.2
5.0
5.0
5.8
6.7
6.7
7.4
8.4
m³/hr
15120
18000
18000
20880
24120
24120
26640
30240
Total
kW
59.96
70.98
81.40
95.92
110.46
122.26
134.00
152.66
Sensible
kW
53.96
64.00
71.28
83.66
96.06
103.64
114.28
130.04
S.H.R.
-
0.90
0.90
0.88
0.87
0.87
0.85
0.85
0.85
CW Flow Rate
I/s
2.86
3.40
3.90
4.58
5.28
5.84
6.40
7.30
Unit Pressure Drop
kPa
84.00
90.10
58.20
83.20
111.90
89.90
54.80
72.70
Electric Reheat No. of Steps Capacity
-
2
2
2
2
3
3
3
4
kW
12
18
18
18
27
27
27
36
Humidifier Humidifier Capacity
kg/hr
8
15
15
15
15
15
15
15
kW
6.00
11.25
11.25
11.25
11.25
11.25
11.25
11.25
Chilled Water In
mm
42
42
54
54
63
63
63
63
Chilled Water Out
mm
42
42
54
54
63
63
63
63
Humidifier Feed
mm
15
15
15
15
15
15
15
15
Drain
mm
22
22
22
22
22
22
22
22
Capacity Power Connections
Dimensions Unit Depth
mm
885
885
885
885
885
885
885
885
Width
mm
1550
1800
1800
2050
2300
2300
2550
2800
Height
mm
1954
1954
1954
1954
1954
1954
1954
1954
Weight
kgs
455
535
570
785
850
890
935
980
Note: All the cooling performances are based on Air On: 24˚C, 45%RH
Due to our policy of continuous development and improvement, the specifications and data herein are subject to change without notice. We must therefore reserve the right to supply equipment that may differ from that described and illustrated herein. All information, including illustrations, contained in this brochure, is believed to be accurate and reliable. Users, however, should independently evaluate the suitability of each product for their own application. CITEC makes no warranties as to the accuracy or completeness of the information, and disclaims any liability regarding its use.
10 Gen-X
Deluxe Range Technical Specifications Models Airflow
DXD / U _ _ _
60
70
80
95
120
135
m³/s
4.2
5.0
5.8
6.7
8.4
9.2
m³/hr
15120
18000
20880
24120
30240
33120
Total
kW
59.96
70.98
83.50
93.78
120.08
132.56
Sensible
kW
53.96
64.00
75.02
84.70
108.14
119.08
-
0.90
0.90
0.90
0.90
0.90
0.90
S.H.R. CW Flow Rate
I/s
2.86
3.40
3.98
4.48
5.74
6.34
Unit Pressure Drop
kPa
84.00
90.10
77.30
64.70
79.70
99.40
Electric Reheat No. of Steps Capacity
-
2
2
2
3
3
4
kW
12
18
18
27
27
36
Humidifier Humidifier Capacity
kg/hr
8
15
15
15
15
15
kW
6.00
11.25
11.25
11.25
11.25
11.25
Chilled Water In
mm
42
54
54
54
63
63
Chilled Water Out
mm
42
54
54
54
63
63
Humidifier Feed
mm
15
15
15
15
15
15
Drain
mm
22
22
22
22
22
22
Capacity Power Connections
Dimension Unit Depth
mm
885
885
885
885
885
885
Width
mm
1550
1800
2050
2300
2800
3050
Height
mm
1954
1954
1954
1954
1954
1954
Weight
kgs
455
535
570
785
850
890
Note: All the cooling performances are based on Air On: 24˚C, 45%RH
Due to our policy of continuous development and improvement, the specifications and data herein are subject to change without notice. We must therefore reserve the right to supply equipment that may differ from that described and illustrated herein. All information, including illustrations, contained in this brochure, is believed to be accurate and reliable. Users, however, should independently evaluate the suitability of each product for their own application. CITEC makes no warranties as to the accuracy or completeness of the information, and disclaims any liability regarding its use.
11 Gen-X
Elegant Range Technical Specifications Models
EXD / U _ _ A / W / DA / DW
Airflow
65
70
80
90
m³/s m³/hr
3.5 12600
50
4.2 15120
5.0 18000
5.8 20880
6.7 24120
kW kW -
49.55 44.10 0.89
56.85 51.43 0.90
70.02 62.57 0.89
74.54 68.53 0.92
87.23 79.44 0.91
CACR
326
326
506
506
506
inch inch mm mm
5/8” 1 1/8” 15 22 ZR108
5/8” 1 1/8” 15 22 ZR125
3/4” 1 1/8” 15 22 ZR144
3/4” 1 1/8” 15 22 ZR160
7/8” 1 3/8’ 15 22 ZR190
kW kW -
52.25 45.62 0.87
61.39 54.02 0.88
71.33 63.29 0.89
78.96 71.36 0.90
95.32 84.74 0.89
B10/60
B10/60
B10/80
B10/80
B80/60
mm
42
42
54
54
54
mm mm
15 22
15 22
15 22
15 22
15 22
“A” Version Total Sensible S.H.R. Connections Air Cooled Condensers Model Liquid Line Discharge Line Humidifier Feed Drain Compressors Model “W” Version Total Sensible S.H.R Connections Water Cooled Condensers Model Condenser Water In / Out Humidifier Feed Drain
Chilled Water Coil Performance of “DA” and “DW” Version Total Sensible S.H.R Water Flow Rate
kW kW I/s
50.30 45.20 0.90 2.40
59.96 53.96 0.90 2.86
70.98 64.00 0.90 3.40
83.50 75.02 0.90 3.98
93.78 84.70 0.90 4.48
mm mm
42 42
42 42
54 54
54 54
54 54
kW
2 12
2 18
2 18
2 18
3 27
kg/hr kW
8 6.00
15 11.25
15 11.25
15 11.25
15 11.25
mm mm mm kgs
885 1800 1954 620
885 2050 1954 725
885 2300 1954 810
885 2550 1954 910
885 2800 1954 985
Connections Chilled Water In Chilled Water Out Electric Reheat No. of Steps Capacity Humidifier Humidifier Capacity Capacity Power Dimension Unit Depth Width Height Weight
Note: All the cooling performances are based on Air On: 24˚C, 45%RH Due to our policy of continuous development and improvement, the specifications and data herein are subject to change without notice. We must therefore reserve the right to supply equipment that may differ from that described and illustrated herein. All information, including illustrations, contained in this brochure, is believed to be accurate and reliable. Users, however, should independently evaluate the suitability of each product for their own application. CITEC makes no warranties as to the accuracy or completeness of the information, and disclaims any liability regarding its use.
12 Gen-X
Performer Range Technical Specifications Models
PXD / U _ _ _ A / W
Airflow
60
75
85
95
120
m³/s
3.5
4.2
5.0
5.8
6.7
m³/hr
12600
15120
18000
20880
24120
Total
kW
58.00
72.29
77.07
91.78
116.12
Sensible
kW
49.61
60.48
68.15
80.14
97.17
-
0.86
0.84
0.84
0.87
0.84
CACR
326
506
506
506
756
“A” Version
S.H.R Connections Air Cooled Condensers Model Liquid Line
inch
3/4”
3/4”
3/4”
7/8”
7/8”
Discharge Line
inch
1 1/8”
1 1/8”
1 1/8”
1 3/8”
1 3/8”
Humidifier Feed
inch
15
15
15
15
15
Drain
mm
22
22
22
22
22
ZR125
ZR144
ZR160
ZR190
ZR250
Compressors Model “W” Version Total
kW
62.79
74.01
81.51
98.82
123.72
Sensible
kW
51.93
61.90
70.41
83.68
100.81
-
0.83
0.84
0.84
0.87
0.84
B10/60
B10/80
B10/80
B80/60
B80/75
42
54
54
54
63
S.H.R Connections Water Cooled Condensers Model Condenser Water In / Out
mm
Humidifier Feed
mm
15
15
15
15
15
Drain
mm
22
22
22
22
22
Electric Heat No. of Steps Capacity
-
2
2
2
2
3
kW
12
18
18
18
27
Humidifier Humidifier Capacity Capacity Power
kg/hr
8
15
15
15
15
kW
6.00
11.25
11.25
11.25
11.25
Dimension Unit Depth
mm
885
885
885
885
885
Width
mm
1800
2050
2300
2550
2800
Height
mm
1954
1954
1954
1954
1954
Weight
kgs
682
798
891
1084
1200
Note: All the cooling performances are based on Air On: 24˚C, 45%RH Due to our policy of continuous development and improvement, the specifi cations and data herein are subject to change without notice. We must therefore reserve the right to supply equipment that may differ from that described and illustrated herein. All information, including illustrations, contained in this brochure, is believed to be accurate and reliable. Users, however, should independently evaluate the suitability of each product for their own application. CITEC makes no warranties as to the accuracy or completeness of the information, and disclaims any liability regarding its use.