INTRODUCTION AUTOMATIC BOILER CONTROLS
62B208
62B-20811 AUG 00
Functions
MEASURE COMPARE COMPUTE CORRECT
62B-20811 AUG 00
What Makes It Work? • Low pressure air system • Continuous supply • High quality
62B-20811 AUG 00
Automatic Boiler Controls • Consist of three sub-systems • Automatic combustion control • Automatic FEEDWATER control • Main feed pump constant pressure
62B-20811 AUG 00
Combustion Control • Maintains steam drum or SUPERHEATER outlet pressure • Within 5 PSI of SETPOINT during steady state conditions
62B-20811 AUG 00
Combustion Control MEASURES STEAM PRESSURE
ACC GENERATES A MASTER DEMAND FOR FUEL AND AIR
STEAM DRUM
MANIPULATES THE FORCED DRAFT BLOWERS & FUEL OIL CONTROL VALVE 62B-20811 AUG 00
Combustion Control MEASURES STEAM PRESSURE
ACC FORCED DRAFT BLOWER
MANIPULATES AIR FLOW TO THE BOILER BY INCREASING/DECREASING THE SPEED OF THE FORCED DRAFT BLOWER 62B-20811 AUG 00
Combustion Control MEASURES STEAM PRESSURE
ACC MANIPULATES FUEL FLOW TO THE BOILER BY INCREASING/DECREASING FUEL FLOW TO THE BURNERS
FUEL OIL CONTROL VALVE 62B-20811 AUG 00
Combustion Control MEASURES STEAM PRESSURE
ACC FORCED DRAFT BLOWER
FUEL OIL CONTROL VALVE 62B-20811 AUG 00
Automatic/manual Control Stations PRIOR TO THE FINAL CONTROL ELEMENT TO ALLOW FOR HUMAN INTERVENTION
AUTOMATIC SYSTEM
FINAL CONTROL ELEMENT 62B-20811 AUG 00
Automatic FEEDWATER Control • Maintains water level in boiler steam drum • Plus or minus one inch from normal • All steady state load conditions
62B-20811 AUG 00
Automatic FEEDWATER Control 3 Element Feed
Water Level +/-1 inch of Normal
MANIPULATES THE FEEDWATER CONTROL VALVE TO REGULATE FEED FLOW TO THE BOILER
62B-20811 AUG 00
THREE ELEMENTS TO CONTROL FEEDWATER FLOW
SF T DLT
FWCV
DLT
FF T
62B-20811 AUG 00
SF T DLT
FWCV
SF/FF RELAY
FF T FF C FWCV POS
FWC A/M
62B-20811 AUG 00
Compensates For Shrink And Swell • Steam flow and drum level will respond in the same direction upon a boiler load change • Increase to increase
62B-20811 AUG 00
Shrink & Swell • During up PWR MANUEVERS, a temporary rise in BLR WTR LVL occurs -called swell • During DWN PWR MANUEVERS, a temporary drop in BLR WTR LVL occurs -- called shrink
62B-20811 AUG 00
Swell • Increase in STM demand: – More STM leaves BLR. – Drum press starts decreasing. – STM bubbles in GEN tubes expand. – WTR level appears to “swell”.
62B-20811 AUG 00
Swell • Automatic combustion CONTRL system (acc sys) senses decrease in drum press and increases firing rate • Drum press increases and regains SETPOINT • WTR LVL decreases as bubble size decreases
62B-20811 AUG 00
Swell • WTR reaches normal and get slightly below normal • Automatic boiler control system (ABC sys) will increase feed flow to match STM flow • WTR LVL achieves normal
62B-20811 AUG 00
Shrink • During a DWN PWR MANUEVER shrink has the opposite effect : – Co wants all stop -- man overboard! – Throttle closes – STM drum press rises – WTR level lowers or “shrinks”
62B-20811 AUG 00
Shrink Acc sys decreases firing rate Drum press regains SETPOINT WTR LVL increases WTR LVL reaches normal, and slightly above normal • ABC sys decreases feed flow • • • •
62B-20811 AUG 00
Main Feed Pump Controls • Maintain a constant pressure FEEDWATER supply to the boiler while on line • Designed to supplement the FEEDWATER control valve • 150 -200 PSI above steam drum pressure 62B-20811 AUG 00
Main Feed Pump Controls • The output of the header pressure controller will be directly proportional to the actual header pressure • Increase - increase
62B-20811 AUG 00
Feed Pump Controls MAIN FD PUMP CONT.
MEASURES FEED PRESSURE FROM A COMMON HEADER TO ONE OR MORE BOILERS
62B-20811 AUG 00
Feed Pump Controls MAIN FD PUMP CONT.
GENERATES A DEMAND SIGNAL TO THE FEED PUMP STEAM ADMISSION VALVE
62B-20811 AUG 00
Feed Pump Controls MAIN FD PUMP CONT.
THROUGH THE A/M STATIONS ON THE CONSOLE 62B-20811 AUG 00
Feed Pump Controls MAIN FD PUMP CONT.
62B-20811 AUG 00
Constant Pressure Regulator • Feed pressure directly opposes spring compression
From common Header 62B-20811 AUG 00
Boiler Control Test • On-line alignment and verification • Boiler flexibility test • Overall system reliability
62B-20811 AUG 00
Final Control Elements • Fail safe positions • • • •
Combustion to minimum Water level to maximum FEEDWATER control valve open Feed pump steam admission valve fully open 62B-20811 AUG 00
BOILER FLEX COMPONENTS F/ F
FW C
S/ F
SP T
FINAL CONTROL ELEMENTS D/ L FD B
F OCV
MF P
62B-20811 AUG 00
Air Pressure Failure • Air lock system • Holds final control elements • Allows WATCHSTANDERS to take control of the plant
62B-20811 AUG 00
NEEDLE VALVE
RESE T
INDIVIDUA L TRIP 40 VALVE PSI
MASTE R TRIP 65 PSI FROM A/M STATION
REDUCE R ALARM PRESSUR E SWITCH
125 PSI
75 PSI
80 PSI
THREE WAY VENT
TO FINAL CONTRO L 62B-20811 AUG 00 ELEMNT
Modes Of Operation • Automatic • Remote MAUNUAL • Local manual
62B-20811 AUG 00
NOW WE KNOW OUR ABC’S
THE END 62B-20811 AUG 00
Introduction To ABC System
62b-208
62B-20811 AUG 00