Electrical data Multi-turn actuators for open-close duty with 3-phase AC motors Short-time duty S2 - 15 min., 400 V/50 Hz Type
Multi-turn actuator Speed Torque
SA 07.1
SA 07.5
SA 10.1
SA 14.1
SA 14.5
SA 16.1
rpm 4 5.6 8 11 16 22 32 45 63 90 125 180 4 5.6 8 11 16 22 32 45 63 90 125 180 4 5.6 8 11 16 22 32 45 63 90 125 180 4 5.6 8 11 16 22 32 45 63 90 125 180 4 5.6 8 11 16 22 32 45 63 90 125 180 4 5.6 8 11 16 22 32 45 63 90 125 180
Motor Type
max. Nm
30
25
60
50
120
100
250
200
500
400
1,000
800
SA 07.1 – SA 48.1
VD00 63-4/30A VD00 63-4/30A VD00 63-4/30 VD00 63-4/30 VD00 63-2/30 VD00 63-2/30 AD00 63-4/50 AD00 63-4/50 AD00 63-2/60 AD00 63-2/60 AD00 63-2/60 AD00 63-2/60 VD00 63-4/30B VD00 63-4/30B VD00 63-4/45 VD00 63-4/45 VD00 63-2/45 VD00 63-2/45 AD00 63-4/80 AD00 63-4/80 AD00 63-2/80 AD00 63-2/80 AD00 63-2/80 AD00 63-2/80 VD00 71-4/35A VD00 71-4/33A VD00 71-4/35 VD00 71-4/35 VD00 71-2/35 VD00 71-2/35 AD00 71-4/80 AD00 71-4/80 AD00 71-2/80 AD00 71-2/80 AD00 71-2/80 AD00 71-2/80 VD00 90-8/40 VD00 90-8/40 VD00 90-4/40 VD00 90-4/40 VD00 90-2/40 VD00 90-2/40 AD00 90-4/75 AD00 90-4/75 AD00 90-2/85 AD00 90-2/85 AD00 90-2/85 AD00 90-2/85 VD00 90-8/60 VD00 90-8/60 VD00 90-4/50 VD00 90-4/50 VD00 90-2/50 VD00 90-2/50 AD00 90-4/130 AD00 90-4/130 AD00 90-2/130 AD00 90-2/130 AD00 90-2/130 AD00 90-2/130 AD00 90-8/85 AD00 90-8/85 AD00 90-4/75 AD00 90-4/75 AD00 90-2/85 AD00 90-2/85 AD00 112-4/110 AD00 112-4/110 AD00 112-2/140 AD00 112-2/140 AD00 112-2/140 AD00 112-2/140
Power PN (kW) 0.025 0.025 0.045 0.045 0.09 0.09 0.18 0.18 0.37 0.37 0.37 0.37 0.046 0.046 0.09 0.09 0.18 0.18 0.37 0.37 0.75 0.75 0.75 0.75 0.09 0.09 0.18 0.18 0.37 0.37 0.75 0.75 1.5 1.5 1.5 1.5 0.18 0.18 0.37 0.37 0.75 0.75 1.5 1.5 3.0 3.0 3.0 3.0 0.37 0.37 0.75 0.75 1.5 1.5 3.0 3.0 4.0 4.0 4.0 4.0 0.75 0.75 1.5 1.5 3.0 3.0 5.5 5.5 7.5 7.5 7.5 7.5
Speed rpm 1,400 1,400 1,400 1,400 2,800 2,800 1,400 1,400 2,800 2,800 2,800 2,800 1,400 1,400 1,400 1,400 2,800 2,800 1,400 1,400 2,800 2,800 2,800 2,800 1,400 1,400 1,400 1,400 2,800 2,800 1,400 1,400 2,800 2,800 2,800 2,800 700 700 1,400 1,400 2,800 2,800 1,400 1,400 2,800 2,800 2,800 2,800 700 700 1,400 1,400 2,800 2,800 1,400 1,400 2,800 2,800 2,800 2,800 700 700 1,400 1,400 2,800 2,800 1,400 1,400 2,800 2,800 2,800 2,800
Nominal current1) IN (A) 0.4 0.4 0.4 0.4 0.6 0.6 0.9 0.9 1.0 1.0 1.0 1.0 0.4 0.4 0.6 0.6 0.7 0.7 1.7 1.7 1.7 1.7 1.7 1.7 0.5 0.5 1.0 1.0 1.4 1.4 2.5 2.5 4.0 4.0 4.0 4.0 1.8 1.8 1.1 1.1 1.9 1.9 3.6 3.6 7.6 7.6 7.6 7.6 3.0 3.0 2.3 2.3 4.3 4.3 7.0 7.0 10 10 10 10 4.0 4.0 3.6 3.6 7.6 7.6 13 13 18 18 18 18
Current2) approx. Imax. (A) 0.4 0.4 0.5 0.5 0.5 0.6 1.1 1.2 1.2 1.2 1.2 1.3 0.8 0.8 0.6 0.6 0.9 1.0 2.1 2.8 2.3 2.6 2.6 3.2 0.6 0.6 1.1 1.2 1.7 1.9 3.0 3.2 5.0 5.8 5.5 6.7 2.0 2.0 1.7 1.8 3.5 3.8 5.4 5.9 10 11 14 14 3.5 3.0 3.6 3.9 6.0 7.0 10 11 16 17 22 22 4.8 5.0 6.5 7.4 11 12 19 22 30 33 35 45
Starting current IA (A) 1.0 1.0 1.0 1.0 1.9 1.9 2.4 2.4 4.4 4.4 4.4 4.4 1.0 1.0 1.6 1.6 3.0 3.0 4.6 4.6 9.0 9.0 9.0 9.0 2.0 2.0 3.0 3.0 4.5 4.5 8.5 8.5 16 16 16 16 4.5 4.5 5.2 5.2 9.0 9.0 16 16 38 38 38 38 6.0 6.0 9.3 9.3 18 18 38 38 58 58 58 58 8.0 8.0 16 16 38 38 60 60 120 120 120 120
cos ϕ 0.50 0.50 0.50 0.50 0.60 0.60 0.50 0.50 0.73 0.73 0.73 0.73 0.50 0.50 0.49 0.49 0.60 0.60 0.58 0.58 0.80 0.80 0.80 0.80 0.60 0.60 0.49 0.49 0.67 0.67 0.64 0.64 0.70 0.70 0.70 0.70 0.45 0.45 0.74 0.74 0.81 0.81 0.80 0.80 0.83 0.83 0.83 0.83 0.45 0.45 0.70 0.70 0.72 0.72 0.80 0.80 0.78 0.78 0.78 0.78 0.50 0.50 0.80 0.80 0.83 0.83 0.77 0.77 0.78 0.78 0.78 0.78
1) Current at running torque according to “Technical data SA 07.1 – SA 48.1” 2) Current at max. torque. We recommend to select switching devices according to these values. We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document. Page 1 of 2
Issue
1.06 Y003.607/002/en
Electrical data Multi-turn actuators for open-close duty with 3-phase AC motors Short-time duty S2 - 15 min., 400 V/50 Hz
SA 07.1 – SA 48.1 Type
Multi-turn actuator Speed Torque rpm 4 5.6 8 11 16 22 32 45 63 90 4 5.6 8 11 16 22 32 45 63 90 4 5.6 8 11 16 22 32 45 4 5.6 8 11 16 22 32 4 5.6 8 11 16
SA 25.1
SA 30.1
SA 35.1
SA 40.1
SA 48.1
Motor Type
max. Nm AD00 90-8/130 AD00 90-8/130 AD00 90-4/130 AD00 90-4/130 AD00 90-2/130 AD00 90-2/130 AD00 132-4/140 AD00 132-4/140 AD00 132-2/180 AD00 132-2/180 AD00 112-8/140 AD00 112-8/140 AD00 112-4/110 AD00 112-4/110 AD00 112-2/140 AD00 112-2/140 AD00 160-4/160 AD00 160-4/160 AD00 160-2/215 AD00 160-2/215 AD00 132-8/150 AD00 132-8/150 AD00 132-4/140 AD00 132-4/140 AD00 132-2/180 AD00 132-2/180 AD00 160-2/214 AD00 160-2/214 AD00 160-8/165 AD00 160-8/165 AD00 160-4/160 AD00 160-4/160 AD00 160-2/215 AD00 160-2/215 AD00 160-2/215 AD00 180-8/240 AD00 180-8/240 AD00 180-4/240 AD00 180-4/240 AD00 180-2/240
2,000
4,000
8,000
16,000 14,000
32,000
Power PN (kW) 1.1 1.1 3.0 3.0 4.0 4.0 7.5 7.5 15 15 2.2 2.2 5.5 5.5 7.5 7.5 15 15 30 30 4.0 4.0 7.5 7.5 15 15 20 20 7.5 7.5 15 15 30 30 30 15 15 30 30 45
Speed rpm 700 700 1,400 1,400 2,800 2,800 1,400 1,400 2,800 2,800 700 700 1,400 1,400 2,800 2,800 1,400 1,400 2,800 2,800 700 700 1,400 1,400 2,800 2,800 2,800 2,800 700 700 1,400 1,400 2,800 2,800 2,800 700 700 1,400 1,400 2,800
Nominal current1) IN (A) 7.0 7.0 7.0 7.0 10 10 22 22 30 30 11 11 13 13 18 18 44 44 65 65 20 20 22 22 30 30 40 40 30 30 44 44 65 65 65 35 35 73 73 80
Current2) approx. Imax. (A) 9.0 10 11 12 16 20 40 48 60 70 15 16 20 23 28 30 58 67 130 150 30 35 48 55 60 70 80 95 55 58 70 87 150 170 200 80 120 170 185 200
Starting current IA (A) 17 17 38 38 58 58 120 120 190 190 36 36 60 60 120 120 200 200 370 370 70 70 120 120 190 190 260 260 93 93 200 200 370 370 370 170 170 380 380 550
cos ϕ 0.48 0.48 0.80 0.80 0.78 0.78 0.65 0.65 0.90 0.90 0.58 0.58 0.77 0.77 0.78 0.78 0.63 0.63 0.88 0.88 0.44 0.44 0.65 0.65 0.90 0.90 0.90 0.90 0.50 0.50 0.63 0.63 0.88 0.88 0.88 0.70 0.70 0.70 0.70 0.83
Motor data are approximate. Due to usual manufacturing tolerances, there may be deviations from the values given. The permissible fluctuation of the nominal voltage is ± 10 %. If the voltage drops below, there is a reduction of the nominal output torque. To protect against overheating, thermoswitches or PTC thermistors are embedded in the motor windings. For actuators without integral controls (AUMA NORM), these have to be connected to the external control circuit (see terminal plan). If thermoswitches or PTC thermistors are not connected, this voids our warranty for the motor. Rating of the thermoswitches: AC
DC
250 V, 50 – 60 Hz
60 V
1.0 A
cos ϕ = 1
2.5 A
42 V
1.2 A
cos ϕ = 0.6
1.6 A
24 V
1.5 A
For further details refer to “Technical data Multi-turn actuators for open-close duty with 3-phase AC motors SA 07.1 – SA 48.1”.
1) Current at running torque according to “Technical data SA 07.1 – SA 48.1” 2) Current at max. torque. We recommend to select switching devices according to these values. We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document. Page 2 of 2
Issue
1.06 Y003.607/002/en