Jenbacher
4.1 Checklist for alarm messages
Documentation
-
General: When the installation is operational, the engine management system DIANE will not only control the engine but will also perform engine-failure management. The engine-failure management system checks all relevant system variables and will issue a warning or switch off the installation if certain set values are exceeded or underrun.
Remedying and resetting failures: When a failure results in the installation being switched off, the cause of the failure should be remedied first before the installation is started again. When a failure results in a warning being issued, the cause of the failure should be remedied first before the failure is reset. Turn off the engine according to Technical Instruction No. 1100-0105 and secure against unauthorized restart. It is forbidden simply to reset a failure and then start the engine again!
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 1 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
Index 10 11 12 13 20 30 40 50 51 52 53 54 55 56 57 60 70 90 100 101 102 103 104 105 110 120 1017 1018 1019 1021 1023 1026 1027 1028 1031 1036 1037 1038 1039 1040 1041
START CONDITIONS MISSING OF MOTOR OF AGGREGATE OF THE UNIT MOTOR WON'T START MOTOR SAWING IN IDLE RUN (can't be synchronized) MOTOR DOES NOT REACH FULL LOAD (while maintaining the guaranteed pollutant emissions) MOTOR OR SYSTEM MOTOR/GENERATOR RUNS IRREGULARLY OR UNSTABLE WITH LOAD MOTOR VIBRATES STRONGLY MOTOR SHAKES (quick load fluctuations or great current and voltage fluctuations with little change of motor output) ENGINE ROCKING GENERATOR MOTOR ESCALATES (great current and voltage fluctuations at only little change in motor output) MOTOR ARCHIEVES NOT STABLE CONDITION (output swings slowly up and down) ENGINE STOPS (individual cylinders) OR HAS AN EXHAUST GAS TEMPERATURE DEVIATING FROM THE CENTRAL VALUE PERIODIC FLUCTUATIONS IN PERFORMANCE MOTOR KNOCKING MISFIRING DETECTION RESPONDS, OR AT BR6 DEVIATION OF CYLINDER FLUE GAS TEMPERATURE TOO GREAT OIL CONSUMPTION TOO HIGH TURBOCHARGER DEFECT COMPACTOR THROWING OIL TURBINE THROWING OIL TURBOCHARGER EFFICIENCY NOT OKAY (flue gas turbocharger no longer archieves required load pressure) COMPACTOR OR TURBINE WHEEL TOUCHED THE HOUSING TURBOCHARGER VIBRATING WATER IN LUBRICATION OIL THE CONTRACTUALLY AGREED DEGREE OF EFFICIENCY IS NOT REACHED IN SPITE OF THE SALES TOLERANCE OIL PRESSURE LOW ENGINE OIL LEVEL LOW JACKET WATER PRESSURE LOW JACKET WATER TEMPERATURE HIGH START UP FAILURE SHUTDOWN FAILURE FAILURE GAS TRAIN 1 GAS PRESSURE LOW IN GAS TRAIN 1 EMERGENCY STOP/SAFETY LOOP GENERATOR OVERLOAD/SHORT CIRCUIT GENERATOR WINDING TEMPERATURE HIGH GENERATOR REVERSE POWER SYNCHRONIZING FAILURE FUEL MIXTURE TEMPERATURE HIGH POWER SIGNAL MISSING
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 2 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
1042 1043 1048 1050 1051 1052 1053 1054 1056 1057 1059 1061 1064 1078 1080 1081 1083 1105 1109 1110 1111 1112 1113 1114 1120 1126 1127 1129 1134 1135 1140 1143 1144 1145 1148 1167 1168 1177 1185 1186 1189 1192 1193 1194 1195 1196 1216 1217 1218 1219
POWER SIGNAL OVERLOAD ENGINE OIL TEMPERATURE HIGH KNOCKING FAILURE JACKET WATER PRESSURE HIGH ENGINE OIL LEVEL HIGH GAS PRE-ALARM GAS ALARM FIRE ALARM FAIL SAFE LOOP TRIPPED HIGH GAS PRESSURE IN GAS TRAIN 1 OIL FILTER DIFFERENTIAL PRESSURE HIGH IGNITION SYSTEM FAILURE OVERSPEED (RPS-CONTROL SYSTEM) BOOST PRESSURE MEASURING SIGNAL FAILURE LEANOX CONTROL ALLOWED DEVIATION EXCEEDED KNOCK SENSOR MEASURING SIGNAL FAILURE CONTROL CARBURATOR DEFECTIVE SPEED OF TEMPERATURE CHANGE MIXTURE TEMPERATURE MAXIMUM GENERATOR LOSS OF EXCITATION GENERATOR FREQUENCY TOO LOW GENERATOR FREQUENCY TOO HIGH NEUTRAL CURRENT MAXIMUM GENERATOR POWER MEASURING SIGNAL FAILURE FUEL MIXTURE TEMPERATURE MEASURING SIGNAL FAILURE SPEED MEASURING SIGNAL FAILURE GENERATOR VOLTAGE LOW GENERATOR VOLTAGE HIGH FAILURE WITH AUXILIARIES GROUND FAILURE ROOM TEMPERATURE HIGH MODULE INTERFACE PANEL CIRCUIT BREAKER TRIPPED VOLTAGE NEGATIVE SEQUENCE CURRENT NEGATIVE SEQUENCE JACKET WATER TEMPERATURE LOW STARTER BATTERY VOLTAGE LOW HEATING WATER RETURN TEMPERATURE HIGH REQUEST FOR MAINTENANCE ENGINE ROOM AIR PRESSURE MEASURING SIGNAL FAILURE GENERATOR WINDING TEMPERATURE HIGH HEATING WATER RETURN TEMPERATURE MEASURING SIGNAL FAILURE RELEASE FROM SYNCHRONIZING MISSING ACTUATOR FAILURE LOAD BANK FAN IS NOT RUNNING LOAD BANK COMMON ALARM LOAD BANK CONTACTOR FAILURE LOAD BANK CB OVERLOAD/SHORT CIRCUIT BUS BAR VOLTAGE SENSOR FAILURE GENERATOR CB STATUS SIGNAL FAILURE GENERATOR CB OPENING FAILURE GENERATOR CB CLOSING FAILURE
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 3 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
1220 1221 2082 2083 2084 2086 2097 2101 2102 2103 2104 2105 2111 2116 2117 2118 2120 3003 3025 3026 3027 3028 3029 3030 3031 3052 3216 3217 3218 3219 3220 3221 3223 3224 3310 3311 3402 3406 3411 3497 3506 3507 3515 3516 3517 3518
GENERATOR CB O-SIGNAL FAILURE GENERATOR CB 1-SIGNAL FAILURE PARAMETER(S) MISSING RPS (CONTROL SYSTEM) BATTERY FAILURE LEANOX ALGORITHM FAILURE CARBURATOR POSITION MEASURING SIGNAL FAILURE DEVIATION POWER SETPOINT TO POWER PRESENT VALUE MAXIMUM JACKET WATER TEMPERATURE MEASURING SIGNAL FAILURE ENGINE OIL TEMPERATURE MEASURING SIGNAL FAILURE JACKET WATER PRESSURE MEASURING SIGNAL FAILURE JACKET WATER PRESSURE MEASURING SIGNAL FAILURE GENERATOR WINDING TEMPERATURE MEASURING SIGNAL FAILURE KNOCK SENSOR MEASURING SIGNAL FAILURE DUMP RADIATOR FAILURE INTERCOOLER WATER PRESSURE LOW MIXTURE COOLING WATER PUMP FAILURE ENGINE ROOM VENTILATION FAILURE MEASURING SIGNAL FAILURE IGNITION TRIGGER PICKUP MISSING IGNITION RESET PICKUP MISSING IGNITION CAM PICKUP MISSING IGNITION SHUTOFF OVERSPEED IGNITION CPU FAILURE IGNITION PARAMETER FAILURE Faulty ignition/CAN coupling WRONG TYPE OF IGNITION SYSTEM ENGINE OIL TEMPERATURE HIGH MISFIRING FAILURE OIL PRESSURE LOW EXCITATION VOLTAGE LOW JACKET WATER TEMPERATURE HIGH GAS PRESSURE LOW IN GAS TRAIN 1 INTAKE AIR TEMPERATURE HIGH INTAKE AIR TEMPERATURE MEASURING SIGNAL FAILURE IGNITION OUTPUT MONITORING CYLINDER IN/OUT CHANNEL FAILURE JACKET WATER PRESSURE LOW JACKET WATER PRESSURE HIGH FUEL MIXTURE TEMPERATURE HIGH Failure in the safety loop POWER REDUCTION IN ISOLATED OPERATION OIL PRESSURE HIGH AIRCONDITIONING UNIT FAILURE IN MODULE INTERFACE CABINET JACKET WATER TEMPERATURE HIGH COMMUNICATION TO DIA.NE WIN SERVER FAILED DATA REGISTRATION IN DIA.NE WIN SERVER FAILED
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 4 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
Index 10 10
START CONDITIONS MISSING
11
OF MOTOR There is a defect as e.g. min. or max. oil level. The current loop (safety loop) is open
12
13
20
OF AGGREGATE e.g. min. gas pressure closed current loop not released
OF THE UNIT no release through auxiliary operation
MOTOR WON'T START gas pressure too low or too high or gas pressure fluctuations
throttle flap won't open
Ignition defective Ignition spark missing
remove indicated cause remove loose contact or wire breakage, or replace defective monit. device.
remove cause or complain at trader;remove loose contact or wire breakage, or replace defect monitoring device
check which auxiliary operation is not running, e.g. HW-circulation pump or throughflow indicator and machine room vent flap open, gas warning installation etc.
gas pressure prior to gas pressure controller line does not correspond to listings in techn. scheme. check whether supply of the Heinzmann actuator driver is okay (amber LED in actuator be lit) the Heinzmann actuator driver is defective (red LED in driver lit) due to low voltage (<12 VDC); short circuit at the lines to the actuator or overtemperature (> 90°C); the pickup or the wiring from the pickup to the actuator or DIANE is defective; check whether the throttle flap or the control systems are stuck or do not properly function. check following points (partly with stroboscope).mains supply of DISN-unit (relay
TI 10000300
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 5 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
electrode distance too smallat all spark plugs
start or idle run position of mixer or gas or air bypass flap incorrect
Unsuitable Impco or Jenbacher mixer
gas pressure in front of zero-pressure controller too high
wrong mixer adjustment membrane of gas pressure controller
defective or bad contact) pickup distance pickup connection defect at relay for the G-line DISN-unit defective wrong.One or several magnets with too little residual magnetism or magnet broken out when changing plugs by sets to non - JENBACHER tested models, electrode distance is often too small, needs greater distance. unsuited gas pressure controller causing gas pressure fluctuations,must be replaced, correction of programmed values to experimental values, or to an inflammable mixture via pollutant measuring kit; check whether the servo motor, the gas or air bypass flap is okay, or check drive for the feedback pot. mixer cone on Impco does not correspond to the current gas type;check whether the air slot at Jenbacher-mixer corresponds to used type of gas. 1) higher values lead to excessive enriching of motor at start; 2) following adjustment of gas adm. pressure: adjust zero pressure controller so that after start of motor there is not speed breakdown (motor in this case too rich); if motor does not increase speed or increases too slow it is too lean; if motor is too rich, gradually turn zero pressure spindle out by 1 rot; if motors is too lean gradually turn spindle in by 1 rot. check programming of start opening check membrane for ruptures
see maintenance
TI 10000300
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 6 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
defective gas pressure controller stuck gas magnet valve is defective no inflammable mixture forms
throttle flap opens and closes quickly during start procedure
30
check for easy movement check whether gas magnet valves open check whether the slot at the mixer cone at the Jenbachermixer corresponds to the %oposition programmed at the DIANE; check whether the mixer cone moves, whether in the drive the spring for the catching is missing or the servo motor is defective (wire breakage or pot-drive) cwrong pick-up adjustment and quite often must be positioned closer to toothed wheel of starter according to adjustment instructions
MOTOR SAWING IN IDLE RUN (can't be synchronized) Heinzmann actuator defective replace (damaged) unsuited mixer mixer cones at Impco do not correspond to gas type or the air slot on Jenbacher-mixer, e.g., for depot gas, is too high, i.e., replace mixer cone, or reduce air slot (replace mixer or reduce shims under mixer head with new Jenbacher mixers) ignition defective (cylinder missing) replace Ignition coildefective replace as a result of a pulsating draught in the fit flap with a solenoid valve at exhaust flue while still warm the foot of the flue. speed controller not optimally adjusted Gas-pressure fluctuations use manometer or water Check the control rods (ball heads worn columnto measure where the / sluggish) gas pressure fluctuations Mixture too lean / too rich appear, i.e., upstream of mixer, upstream of gas Check speed controller setting pressure controller or downstream of customergas admission controller; if controller unsuited, replace it, or call supplier (of admission pressure controller). damaged joint cones of control line replace joint cones
see
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 7 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
maintenance the control linkage adjusted too progressively in idle run throttle flap slightly bent following detonation in intake line and does not fully close anymore (idle speed partially too high) sluggish control lines, or throttle flap
Heinzmann actuator driver not optimally adjusted idle run position at gas or air bypass valve not optimally adjusted or no optimal programming in DIANE 40
correct adjustment and make sure that the flap can fully close. remove throttle flap and align, check for easy functioning
relube the joints, or disassemble the throttle flap bearing and replace; replace bearing bushing. check the 0% position of the actuator better adjust idle run position by trial or program differently
see maintenance
see maintenance
MOTOR DOES NOT REACH FULL LOAD (while maintaining the guaranteed pollutant emissions) Defective turbocharger check compactor shovel (missing power and power loss) whether entry edges are damaged by foreign bodies or whether formation of deposits in the compactor housing reduces output or whether runnertouches housing (clean compactor housing and runner). Check the turbine wheel for damage and free run. combustion air ratio not okay (motor correct leanox adjustment at running too lean), DIANE Part of the broken-off protective pipe in open the end cover and a manifold compensator is interrupting remove parts or replace the flow of the exhaust gases compensator.Inspect turbine wheel for damage. faulty insulation of exhaust collection attach new insulation of line (insulation is completely or partiall thickness and efficiency as worn down due to frequent dismantling original one or due to vibraiton mixture transporting parts after seal off compactor to throttle flap are not tight suction temperature too high(at >25°C) check whether ambient air reduction can be used acc. to ISO thermostat adjusted too high, 3046, except for other contractual the room venting not properly agreement planned or other vent stages do not turn on mixture temperature too high in spite of check mixture cooler, clean if TI 1000-
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 8 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
correct mixture cooling water admission temp. output display wrong; ignition not properly adjusted, orcombustion misfires by e.g. too large electrode distance or failure of cylinders due to defectat ignition system (e.g. defect ignition coil) throttle flap not fully opened,actuator stands at 100% contaminated air filter and hence great pressure loss before mixer flue gas counter pressure too
leakage at the flange connections of flue gas line
necessary (mixture and water part) or glycol ratio too high (check). check and correct error; make ignition check, measure ignition point, correct ignition adjustment and electrode distance, replace defective parts. correction of controller linkage adjustment actuator - throttle flap. measure pressure loss clean or replace the filter measure the counter pressure after high turboloader exit;clean oxikate and waste heat boiler if necessary. seal the line (replace sealings, tighten screws correctly) if necessaryrework flanges
0201, see maintenance see maintenance
see maintenance see maintenance
50
MOTOR OR SYSTEM MOTOR/GENERATOR RUNS IRREGULARLY OR UNSTABLE WITH LOAD
51
MOTOR VIBRATES STRONGLY failure of cylinder pendulum damper not okay motor adjustment not okay (ignition point) straps of motor add-on pieces not okay
check ignition, valves, check compression check and replace if necessary check and adjust
see maintenance see maintenance
check and remedy
52
MOTOR SHAKES (quick load fluctuations or great current and voltage fluctuations with little change of motor output) faulty ignition check ignition system see maintenance combustion air ratio not okay (motor check and adjust using the running too lean), pollutant measuring device water, humidity in spark plug chamber dry spark plug chamber, (after washing motor) clean plugs and connector.
53
ENGINE ROCKING biological gas: gas pressure control line not okay (e.g. water in the gas pressure controllers, stuck gas control valves)
check gas pressure with water column upstream of mixer. check gas pressure controller, repair if necessary
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 9 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
misfires (motor adjusted too lean)
check and adjust using the pollutant measuring device
54
GENERATOR MOTOR ESCALATES (great current and voltage fluctuations at only little change in motor output) voltage controller at generator not okay adjust or repair description cos phi controller not okay check cables bad connection in circuit (cables) check that connector is firmly generator located
55
MOTOR ARCHIEVES NOT STABLE CONDITION (output swings slowly up and down) Non-optimal setting of Leanox-control optimise the controller parameters parameters at constant power Check control rods (ball heads worn / setpoint sluggish) Check gas pressure Check power control Check gas-quality fluctuations (landfill gas, possibly sewage gas) harmonization of leanoxcontroller harmonize time behavior output control not functioning leanox contr. to time behavior output control (decouple) control linkages not okay (too large check, if necessary repair or see dead center/to progressively adjusted, replace maintenance etc.) gas mixer not properly adjusted (e.g. lcheck, adjust characteristic not okay) gas pressure fluctuating check gas pressure TI 1000controller, check admission 0300 pressure quick fluctuation of the mixture check temp. in hot water Schematic temperature circulation diagram
56
ENGINE STOPS (individual cylinders) OR HAS AN EXHAUST GAS TEMPERATURE DEVIATING FROM THE CENTRAL VALUE Pre-combustion chamber gas pressure Eleminate cause! set too low Check spark plugs, ignition coils and ignition system defective ignition check see maintenance defective spark plug check voltage demand, see replace if necessary maintenance
57
PERIODIC FLUCTUATIONS IN PERFORMANCE continual switching on and off of the Conversion to thermostaticallyventilator(s) controlled, frequencyregulated ventilator
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 10 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
60
MOTOR KNOCKING output limitation faulty mixture cooling water temperature too high cooling water throughflow through the mixture cooler too low deposits in combustion chamber are butane and air mixed into the fuel gas? motor set too rich methane number of fuel gas too low combustion air ratio not okay ignition point not okay too early ignition point is set mixture temperature too high mixture cooler not okay
70
Eleminate cause! Eleminate cause!
Schematic diagram
Eleminate cause! check, remove deposits if any Eleminate cause! Eleminate cause! take gas sample and have it analyzed check, correct adjustment if necessary determine ignition point and adjust toward "late" Eleminate cause! check, remedy fault if any Eleminate cause!
TI 10000300 Schematic diagram
MISFIRING DETECTION RESPONDS, OR AT BR6 DEVIATION OF CYLINDER FLUE GAS TEMPERATURE TOO GREAT spigot nut at the line to gas inlet valve is retighten the screwing or seal loose or the cutting ring is loose (flue gas temperature is higher at misfire) defective output measurement (motor check the output output does not correspond to measurement (compare measured output) counter measurement with output measurement) wrong adjustment of misfire detector Eleminate cause! verdigris on ignition coil exit (connector clean carefully to make metal to ignition cable) shiny motor runs too lean due to defect of check motor adjustment mixer (or of the air bypass flap)or due to withmeasuring kit, if too lean, leanox control remedycause crack at end of thread torque too high replace spark plug and see (plug tightened without torque wrench or tightencorrectly with the right maintenance with defective tool, or tightened too torque much) missing or bad contact at highvoltage check contact screwing output of ignition coils or at ground ground contact at the ignition contact or ignition coil coil and retighten the connection defect at cable loom between ignition in case of loose contacts box and ignition coils (scraping spots, retighten screws, in all other ground contact, overheating and cases replace cable loom cracking at the insulation, loose contacts at the connections
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 11 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
interferences at the ignition pearl formation on electrodes due to overheating (e.g. knocking at times)
electrode distance too small (possibly only at site on one electrode) boost pressure transmitter defect or due to drift transmits too low value (to leanox controller or DIANE) causing too lean operation of motor spark plug shows blue or brown discoloring at steel part and shows electrode motor misfires because it is set too lean or due to defective ignition quick generator output change entry of dirt (shavings) or grease into the prechamber annulus, i.e. slits are partially blocked too large ignition voltage demand due to large electrode distance
spring in brass part of plug connector without voltage, or broken, bad contact to brass cap of plug (traces of smoke) consumption spark plug shows abnormal spark appearance or flashover at bottom of plug on oscilloscope
misfiring due to too low ignition voltage offer (defect at the ignition coil) breakage of ignition cable interior at the soldering at the brass part of the plug connector or at the bend of the rubber bush ceramic body at the spark plug on top, or inner part of plug, is soiled with electr. conductive grease or similar and causes spark discharge in this area; plug shows in lower range of brass part a low-out, thus spark discharge to plug shell is
check shield at the cables cannot be seen, metallic pearl may be caused by local melton between electrodes (remove with thickness gauge and check gap) correct electrode distance.
see maintenance
check boost pressure controller, i.e., compare boost pressure signal with manometer, in case of deviation replace transmitter spark plug was not tightened sufficiently and overheated check using an exhaust emmissions analyser and correct if necessary Eleminate cause! Wash the pre-chamber with petrol and blow out. re-adjustment of the electrode gap with the special tool, or replacement of the sparking plugs replace spark plug connector
see maintenance
plug daubed at the end side with electrically conductive gliding agent (when sprayed with Ultra-Therm not covered or too much spray used which dropped on electrodes when hot) check the coil at motor standstill with ignition voltage tester frequent pulling of the plug connector at the cable, the cable ruptures are not visible, replace plug and cable clean plug and connector or replace.check for proper seat of dust cap on top of the valve hoodBlow-out is usually very small, onlyvery small grey point is visible on spark
TI 14000111
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 12 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
created elastic seal ring inParker" valve of gas inlet valve destroyed
loose brass cap (traces of smoke on top of ceramic body) ball sticks to seat of gas inlet valve
90
OIL CONSUMPTION TOO HIGH carbonisation of the fire land through excessive idling or nonobservation of the limit values for used oil (TI 1000-0099B) leads to carbonisation of hard deposits on the piston top land. The upper rim pushes oil in front of it, more oil is burnt and the 1st ring receives too little oil and wears very repidly. (Ring carries to full height within 1000 op. hrs., darfk, cruty deposit in piston groove Piston runs crooked due to connecting rod parallelity tolerances being exceeded; similar effects to above with the same symptoms and can be clearly seen at the piston skirt on the pressure side, as well as at the fire land above the level of the bolts (one side clear, the other with hard oil carbonisation) (reduced gas access to 1st piston ring). turboloader throwing oil
100
TURBOCHARGER DEFECT
101
COMPACTOR THROWING OIL air filter resistance too great (dirty filter)
102
TURBINE THROWING OIL axial or radial play of runner
passage. replace plug suppresser if ball valve is too leaky, the pressure at theParker" valve is too high and the seal ring is destroyed tighten cap; if threading underneath of brass cap is loose, replace spark plug increase prechamber gas difference pressure; clean (wash valve, i.e. clean from lubricating oil which deposits in valve especially during start-up phase)
see maintenance
remove piston and clean replace first ring and break in motor
see point 0100
clean air filter, if required replace
see maintenance
measure, if exceeding admissible too great values
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 13 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
oil sealing at turbine is defective
repair or replace check and repair
103
TURBOCHARGER EFFICIENCY NOT OKAY (flue gas turbocharger no longer archieves required load pressure) entrance shovels of compactorare check, search cause (foreign defective or damaged body?) and replace FGTL if necessary turbine shovels damaged check, search cause (foreign body?) and replace FGTL if necessary
104
COMPACTOR OR TURBINE WHEEL TOUCHED THE HOUSING defective axial sealing -axial play too measure, if exceeding great admissible too great values repair or replace
105
TURBOCHARGER VIBRATING turbine shovels (compactor shovels) defective (unbalanced)
110
WATER IN LUBRICATION OIL leaks at oil cooler craks or sinkholes at upper side of cylinder head between water storage and oil storage leaky O-rings at the cylinder liner leaky O-rings at the prechambers
replace wheel or turboloader
check and replace if necessary check, replace if necessary
replace O-rings replace O-rings
120
THE CONTRACTUALLY AGREED DEGREE OF EFFICIENCY IS NOT REACHED IN SPITE OF THE SALES TOLERANCE on site the sum of border conditions is measure values exactly and strongly negative in order to reach an convert to standard condition optimal efficiency (e.g. heating value of according to ISO 3046 depot gas extremely low, induction temperature >25°C, air pressure <1000 mbar) flue gas counter pressure too high due clean boiler to dirty waste heat boiler induction vacuum before compactor too clean air filter see high due to dirty air filter maintenance
1017
OIL PRESSURE LOW leak in the oil lines or the oilpan clogged oil cooler, oil filter or oil line uncontrolled switching off (killing) of engine too low speed oil level below "min. oil level" defective oil pressure transmitter
Eleminate cause!
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 14 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
engine switch-off by closed current loop (defect monitoring) wrong adjustment of fringe value 1018
1019
1021
ENGINE OIL LEVEL LOW leakage in oil lines or oilpan defective solenoid valve "fill oil" (won't open) defective oil level sensor or evaluation device empty fresh oil tank slide at oil pump station is closed three-way cock in wrong position oil level measurerer not adjusted (with analog measuring) "sag" in pressure-equalization line (venting) wrong adjustment of fringe value JACKET WATER PRESSURE LOW leak in cooling water system defective pressure transmitter of cooling water leaking safety valve damaged membrane in pressure wrong adjustment of fringe value crack in inlet or outlet duct of cylinder head JACKET WATER TEMPERATURE HIGH hot water feedback temp. too high cooler clogged, calcified, dirty return temperature control incorrectly adjusted emergency cooler clogged calcified, dirty fresh water missing cool. wat. pump defect defect. cool. water temp. transmission heat circulation pump defective heat circ. slide, fresh - water slide closed ambient temp. too high (with table cooler) throughflow amount too small (primary/secondary) follow-up heating when shut off water circulations not vented motor output too high glycool amount too high defective short-circuit thermostat wrong adjustment of fringe value water circulation not vented
Eleminate cause!
Eleminate cause!
Eleminate cause!
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 15 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
1023
1026
1027
1028
1031
1036
START UP FAILURE 3 unsuccessful starting attempts no gas defective ignition wrong gas mixer valve start position wrong adjustment of gas pressure safety automation in motor terminal strip is off starter won't start SHUTDOWN FAILURE leaky or defective gas valves speed limit wrongly adjusted FAILURE GAS TRAIN 1 leaky gas valves gas valve closed defective gas tightness coantroller clogged gas filter too low gas pressure dirty filter in supply line to tightness controller condensate in the supply line to tightness controller vibrations of tightness controller device GAS PRESSURE LOW IN GAS TRAIN 1 gas valve closed wrong adjustment or defective gas pressure controller missing gas supply (line breakage) pressure fluctuations by other user defective pressure switch no gas present (sewer gas) wire breakage to PLC dirty filter in supply line EMERGENCY STOP/SAFETY LOOP emergency off button enabled wire breakage safety loop belt alarm --> when in emergency off chain gas alarm --> linked
Eleminate cause!
Eleminate cause!
Eleminate cause!
TI 10000300
Eleminate cause!
TI 10000300
Eleminate cause!
GENERATOR OVERLOAD/SHORT CIRCUIT wrong adjustment or defective output Eleminate cause! controller overload in isolated operation
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 16 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
short circuit wrong adjustment or defective output switch wrong adjustment or defective cos-phi controller wire breakage to PLC unbalanced load 1037
GENERATOR WINDING TEMPERATURE HIGH generator overload Eleminate cause! unbalanced load defective generator wrong cos-phi posistor or analogue input defective wire breakage to PLC ambient temperature too high wrong adjustment of fringe value
1038
GENERATOR REVERSE POWER generator power switch does not open 10% power switch point wrong adjustment output reduced too quickly defective output measurement (only variant with reverse current relay) wrong adjustment rev. current relay or defective DIANE wrong adjustment or defective defective current transmitter wire breakage to PLC short circuit or wire breakage in 20 mA current loop of output measuring transducer ignition failure (signal pickup/DISN failure)
1039
1040
SYNCHRONIZING FAILURE speed controller hunting throttle control rod loose synchronising unit faulty engine rough (ignition coil faulty) voltage balance circuit faulty engine idles too long gas pressure oscillating FUEL MIXTURE TEMPERATURE HIGH defective mixture cooling pump mixture cooler clogged, calcified, dirty hot water feedback temp. too high fresh water exchanger is clogged, calcified, dirty
Eleminate cause!
Eleminate cause!
Eleminate cause!
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 17 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
defective PT100 water circulation of mixture cooling not vented cooling water amount of mixture too low wrong adjustment of fringe value 1041
1042
1043
1048
POWER SIGNAL MISSING wire breakage or short circuit of output signal wire breakage or short circuit of current transducer output measuring transducer defect defective current transducer defective output controller power setpoint too small (<10% Pnenn) POWER SIGNAL OVERLOAD overload isolated operation output controller wrong adjusted or defective input of wrong measuring transducer or wrong output switch point defective output measuring transducer defective current transducer defective output controller ENGINE OIL TEMPERATURE HIGH oil cooler clogged, dirty hot water feedback temp. is too high defective cooling water pump cooling water heat exchanger chocked dirty return remperature control incorrectly adjusted fresh water heat exchanger chocked, dirty table cooler too small ambient temp. to high (with table cooler) throughflow amount too low (primary/second.) limit value adjusted incorrectly KNOCKING FAILURE pre ignition (deposits in combustion chamber) ignition timing point too early monitoring set too sensitively bad contact on the connector at the sensor(s) knocking sensor or knocking control
Eleminate cause!
Eleminate cause!
Eleminate cause!
Eleminate cause!
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 18 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
defective Leanox controller programmed falsely (mixture too rich) 1050
1051
1052
1053
1054
1056
1057
JACKET WATER PRESSURE HIGH slide for filling cooling water is open leaking plug sleeve defective cooling water pressure transmitter defect. cool. water temp. measurement and overheated motor pressure expansion container too small filling pressure too high wrong adjustment of fringe value ENGINE OIL LEVEL HIGH defective solenoid valve "fill oil" defective oil level sensor or evaluator oil level measurerer is not adjusted (with analog measuring) wrong adjustment of fringe value GAS PRE-ALARM leak in gas line system solvent, cleaning agent in container transmitter defective wrong adjustment or defective evaluator GAS ALARM leak in gas line system solvent, cleaning agent in container transmitter defective wrong adjustment or defective evaluator FIRE ALARM fire smoke solvent, cleaning agent in container transmitter defect evaluator defect FAIL SAFE LOOP TRIPPED 24V supply missing safety loop monitoring tripped emergency stop HIGH GAS PRESSURE IN GAS TRAIN 1 Gas pressure controlle wrong adjustment or defective
Eleminate cause!
Eleminate cause!
Eleminate cause!
Eleminate cause!
Eleminate cause!
Eleminate cause!
Eleminate cause!
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 19 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
Pressure switch defect wire breakage to PLC
1059
OIL FILTER DIFFERENTIAL PRESSURE HIGH clogging of oil filter due to dirt or water in Eleminate cause! lubrication oil (check oil on water, remedy cause. Determine type of other dirt of the filter by cutting open filter, possible early bearing damage!!) filter must be changed!
1061
IGNITION SYSTEM FAILURE faulty thermocouple Cable break to PLC Analogue input card faulty Setting parameters not allowed now
Incorrect parameter IC9xx Ignition failure caused by a malfunction in the ignition unit
IC9xx incorrect information from the pick-ups
IC9xx Misfiring
1064
Eleminate cause!
The parameters of the ignition can only be adjusted at engine standstill. Parameter outside the valid range Read failure from the ignition (if possible). In case of program failure, first switch off the supply voltage and then switch it on again Check whether all ignition coils are connected. Replace the ignition Clean the magnetic pickups. Check the distance between pickup and trigger source (Be careful when reaching the highest position so as to prevent mechanical triggering!) Replace the faulty pickups. Check the high-voltage requirement. Check the shielding at the pickups and the IC900. Check the supply voltage using an oscilloscope. Check the mass circuit from ignition to engine mass.
OVERSPEED (RPS-CONTROL SYSTEM) speed overshoot afte mains failure Eleminate cause! speed limit wrongly adjusted
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 20 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
1078
BOOST PRESSURE MEASURING SIGNAL FAILURE 24V supply to boost pressure transducer secure interfaces faulty repair cables transducer cables faulty wrong transducer change transducer transducer range exceeded tranduce faulty analogue input card faulty
1080
LEANOX CONTROL ALLOWED DEVIATION EXCEEDED measuring signal fault - actual power see fault No. 1113 Measuring signal fault - mixture see fault No. 1114 Temperature see fault No. 1078 see fault No. 1083 Measuring signal fault - boost pressure Gas mixer control defective
1081
KNOCK SENSOR MEASURING SIGNAL FAILURE 24 V supply failure for knocking Sensor check interface Knocking sensor cable fault Check cable Knocking sensor defekt Change sensor Interferance on knocking sensor Move knocking sensor cable analogue input card faulty as far as possible from ignition cable
1083
CONTROL CARBURATOR DEFECTIVE 24V supply failure for DM455 Gasmixer cable fault Gasmixer siezed 24V supply failure for gasmixer position feedback Faulty position-feedback plate Position feedback cable faulty
Check power supply in 24V interface and at the DM455 board Correct wiring Smooth running of gas mixer Exchange fuse and board
TI 10000300
1105
SPEED OF TEMPERATURE CHANGE MIXTURE TEMPERATURE MAXIMUM Inform the GE-JENBACHER customer service department
1109
GENERATOR LOSS OF EXCITATION Voltage controller faulty Excitation voltage protection has been tripped Faulty rotating diodes defective cos-phi controller
1110
GENERATOR FREQUENCY TOO LOW Speed governor has been set incorrectly Speed governor is out of order Error in speed governor circuit
change controller Close protection switch Check/replace the diodes
Eleminate cause!
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 21 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
1111
1112
GENERATOR FREQUENCY TOO HIGH Speed governor has been set incorrectly Speed governor is out of order Error in speed governor circuit NEUTRAL CURRENT MAXIMUM Out-of-balance load in isolated operation. Non-symmetrical mains supply causing compensating currents. Inadmissible 3rd (upper) harmonic wave (150 Hz). Earth fault
Eleminate cause!
Eleminate cause!
1113
GENERATOR POWER MEASURING SIGNAL FAILURE Mult - transducer faulty Change multi-transducer Cables for multi-transducer faulty Check cables Analogue input card faulty Change analogue input card wrong adjustment of fringe value
1114
FUEL MIXTURE TEMPERATURE MEASURING SIGNAL FAILURE PT100 faulty change PT100 PT100 cables faulty Check cables Analogue input card faulty
1120
SPEED MEASURING SIGNAL FAILURE Speed pick-up wrongly adjusted 24V supply failure to pickup Pickup cable fault
1126
1127
1129
1134
Gap from 1 revolution of gear rim. Check interface Check cable
GENERATOR VOLTAGE LOW voltage controller fault Excitation voltage protection has been tripped Blown fuse
change controller Close protection switch Check fuse
GENERATOR VOLTAGE HIGH voltage controller fault voltage controller measurement circuit is disturbed
change controller Check measurement circuit
FAILURE WITH AUXILIARIES supply circuit breaker tripped by overload short circuit GROUND FAILURE generator earth fault limiting value on evaluation instrument
check wiring check adjustment circuit breaker
Eleminate cause!
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 22 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
incorrectly adjusted trigger device defective defective current transformer in generator incorrect current transformer current transformer connections exchanged 1135
ROOM TEMPERATURE HIGH room vent failure wrong adjustment or defective thermostat exterior temperatur too high unfavorable placing of thermostat
check the frequency controller
1140
MODULE INTERFACE PANEL CIRCUIT BREAKER TRIPPED Circuit breaker or engine circuit breaker in Eleminate cause! module control cabinet has tripped Power circuit breaker or engine circuit breaker in module control cabinet is off Wire breakage Loose terminal on SPC input card Loose terminal on circuit breaker's or engine circuit breaker's auxiliary contacts
1143
VOLTAGE NEGATIVE SEQUENCE fuse blown in measurement circuit Generator earth fault Generator winding fault Armature fault Mains voltage assymetry
1144
1145
1148
CURRENT NEGATIVE SEQUENCE current transformer circuit interuption Mains voltage assymetry Unbalanced load in Island operation Earth fault JACKET WATER TEMPERATURE LOW failure cooling water preheating return temperature control incorrectly adjusted defective cooling water temp. transmitter heat-up process not finished wrong adjustment of fringe value STARTER BATTERY VOLTAGE LOW loader defect (fuse) not enough battery acid in battery defective battery too strong loads
check fuses Fault checks
check CT circuits Check faults
Eleminate cause!
check battery charging
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 23 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
frequent starts wire breakage to PLC 1167
HEATING WATER RETURN TEMPERATURE HIGH temperature controller warm water not Eleminate cause! correctly no heating demand (pump fault) wrong adjustment of fringe value
1168
REQUEST FOR MAINTENANCE Service counter has reached zero (operating hrs) from preselected limit
reset service counter after completion of service
According to customer setting
1177
ENGINE ROOM AIR PRESSURE MEASURING SIGNAL FAILURE no measuring signal; broken cable replace pressure transducer; replace cable
1185
GENERATOR WINDING TEMPERATURE HIGH generator overload Eleminate cause! unbalanced load defective generator wrong cos-phi posistor or analogue input defective wire breakage to PLC ambient temperature too high wrong adjustment of fringe value
1186
HEATING WATER RETURN TEMPERATURE MEASURING SIGNAL FAILURE wire breakage Eleminate cause! short circuit defective PT100 defective PT100 measuring transformer defective safety device measuring transformer current supply Analogue input card faulty
1189
RELEASE FROM SYNCHRONIZING MISSING a) The synchronisation control logic does a) Check prerequisites for not issue a release because the required logical release from conditions are not fulfilled synchronization (prerequisites relating to specific order according to control description) b) Eliminate cause !
1192
ACTUATOR FAILURE
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 24 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
Disturbance / alarm at the Actuator for butterfly valve (internal equipment). Failure voltage supply 24 VDC, wire break 1193
1194
1195
LOAD BANK FAN IS NOT RUNNING load bank fan not running; defective load bank fuse; load bank overload / short circuit
LOAD BANK COMMON ALARM load bank fan not running; defective load bank fuse; load bank overload / short circuit
LOAD BANK CONTACTOR FAILURE defective fuse; broken cable; interrupted power supply; defective control system
Eleminate cause!
replace fan; replace signal cable; restore power supply; reset and/or replace control system; replace air flow monitoring system; replace fuse; replace signal cable; restore power supply; reset and/or replace control system; visually inspect resistor elem
replace fan; replace signal cable; restore power supply; reset and/or replace control system; replace air flow monitoring system; replace fuse; replace signal cable; restore power supply; reset and/or replace control system; visually inspect resistor elem
replace fuse; replace signal cable; restore power supply; reset and/or replace control system
1196
LOAD BANK CB OVERLOAD/SHORT CIRCUIT
1216
BUS BAR VOLTAGE SENSOR FAILURE measuring voltage missing Eleminate cause! busbars voltage-detector defective wire breakage SPG-OK message to PLC PLC-input defective
1217
GENERATOR CB STATUS SIGNAL FAILURE wire breakage check cables/connections switch return messages check auxiliary circuit breaker or contactor defective contacts/answerback of (return message/auxiliary contacts) breaker or contactor relay for switch return message defective check auxiliari contacts PLC-input defective check/change relay
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 25 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
check PLC input (performed by GE-JENBACHER) 1218
1219
1220
1221
2082
GENERATOR CB OPENING FAILURE ground contacts welded (with circuit breaker/contactor combination) circuit breaker defective relay for switch-off order is defective wrong position of retun message switch PLC-output defective
GENERATOR CB CLOSING FAILURE relay for switch-on order defective line breakage to circuit breaker/contactor circuit breaker defective PLC output defective GENERATOR CB O-SIGNAL FAILURE wire breakage to PLC output monitoring PLC input defective PLC output defective
GENERATOR CB 1-SIGNAL FAILURE wire breakage to PLC output monitoring PLC input defective PLC output defective
PARAMETER(S) MISSING Some parameters required for the operation of the machine are missing. No, insufficient or wrong parameters transmitted.
change/check contactor change/check breaker change/check relay check breaker position signal check/change breaker position answerback relay check PLC output (performed by GE-JENBACHER)
check/change relay check cabels/connections check/change breaker check PLC output
check cables/connections check PLC input (performed by GE-JENBACHER) check PLC output (performed by GE-JENBACHER)
check cables/connections check PLC input (performed by GE-JENBACHER) check PLC output (performed by GE-JENBACHER)
Transmitting the most recent and complete parameter set (*.par file) using e.g. DIA.NE WIN.
2083
RPS (CONTROL SYSTEM) BATTERY FAILURE NiCd battery for CPU2005 is flat (Battery change NiCd battery LED lit) Lithium battery Lithium battery for the user memory is flat (Battery LED flashing)
2084
LEANOX ALGORITHM FAILURE two identical operating point for Lox memory have been used
repeat Lox setup procedure
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 26 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
2086
CARBURATOR POSITION MEASURING SIGNAL FAILURE No power supply Switch on power supply Line breakage Check wiring and adjust Position measurement in gas mixer has position measurement been set incorrectly
2097
DEVIATION POWER SETPOINT TO POWER PRESENT VALUE MAXIMUM Signal from client
2101
JACKET WATER TEMPERATURE MEASURING SIGNAL FAILURE wire breakage Eleminate cause! short circuit defective PT100 defective PT100 measuring transformer defective safety device measuring transformer current supply Analogue input card faulty
2102
ENGINE OIL TEMPERATURE MEASURING SIGNAL FAILURE wire breakage Eleminate cause! short circuit defective PT100 defective PT100 measuring transformer defective safety device measuring transformer current supply Analogue input card faulty
2103
JACKET WATER PRESSURE MEASURING SIGNAL FAILURE leak in the oil lines or the oilpan clogged Eleminate cause! oil cooler, oil filter or oil line uncontrolled switching off (killing) of engine too low speed oil level below "min. oil level" defective oil pressure transmitter engine switch-off by closed current loop (defect monitoring) wrong adjustment of fringe value
2104
JACKET WATER PRESSURE MEASURING SIGNAL FAILURE leak in cooling water system Eleminate cause! defective pressure transmitter of cooling water leaking safety valve damaged membrane in pressure wrong adjustment of fringe value crack in inlet or outlet duct of cylinder head
2105
GENERATOR WINDING TEMPERATURE MEASURING SIGNAL FAILURE
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 27 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
wire breakage short circuit PT100 sensore defective Analogue input card faulty
Check wiring
2111
KNOCK SENSOR MEASURING SIGNAL FAILURE Wire breakage Eleminate cause! Faulty anti-knock control Anti-knock sensor failure Anti-knock failure (1048) activated
2116
DUMP RADIATOR FAILURE Signal from client
Eleminate cause!
2117
INTERCOOLER WATER PRESSURE LOW leak in intercooling water system Eleminate cause! defective pressure transmitter of intercooling water leaking safety valve damaged membrane in pressure wrong adjustment of fringe value crack in inlet or outlet duct of cylinder head
2118
MIXTURE COOLING WATER PUMP FAILURE motor overload Check water pump and electric Cable break to PLC motor. Motor protection (contactor) tripped Compare the engine emergency circuit breaker setting with the actual current collection of the motor.
2120
ENGINE ROOM VENTILATION FAILURE Cable to PLC defect Eleminate cause! Ventilationdefect Engine emergency circuit breaker set incorrectly
3003
MEASURING SIGNAL FAILURE Signal from client
3025
IGNITION TRIGGER PICKUP MISSING Faulty pickup signals.
Check the ignition sensors for pollution caused by small metal chips. Check the distance of the sensors. You should avoid a mechanical contact between
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 28 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
the triggering point and the sensor. Replace the faulty pickup. Ensure that the shielding and electrical connection are correct. 3026
3027
3028
3029
3030
IGNITION RESET PICKUP MISSING Faulty pickup signals.
IGNITION CAM PICKUP MISSING Faulty pickup signals.
IGNITION SHUTOFF OVERSPEED Deactivation of the ignition because the overspeed has been exceeded.
Check the ignition sensors for pollution caused by small metal chips. Check the distance of the sensors. You should avoid a mechanical contact between the triggering point and the sensor. Replace the faulty pickup. Ensure that the shielding and electrical connection are correct.
Check the ignition sensors for pollution caused by small metal chips. Check the distance of the sensors. You should avoid a mechanical contact between the triggering point and the sensor. Replace the faulty pickup. Ensure that the shielding and electrical connection are correct.
wrong adjustment of or defective speed controller stuck or bent throttle flap speed relay defective or wrongly adjusted Minimum throttle opening set too wide eg. throttle valve bent
IGNITION CPU FAILURE Faulty ignition.
replace the ignition
IGNITION PARAMETER FAILURE Faulty value of the parameter.
Error in the dia.ne programme
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 29 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
or faulty ignition. 3031
3052
3216
3217
Faulty ignition/CAN coupling CAN connection between ignition and dia.ne interrupted. Ignition not in CAN mode.
WRONG TYPE OF IGNITION SYSTEM Incorrect ignition system
ENGINE OIL TEMPERATURE HIGH oil cooler clogged, dirty hot water feedback temp. is too high defective cooling water pump cooling water heat exchanger chocked dirty return remperature control incorrectly adjusted fresh water heat exchanger chocked, dirty table cooler too small ambient temp. to high (with table cooler) throughflow amount too low (primary/second.) limit value adjusted incorrectly MISFIRING FAILURE Wrong distance of electrodes Wrong A/F ration Failure in ignition system (sparkovers, break of insulators) Too late ignition point Misvire detection incorrectly adjusted or defective Ignition defective Ignition coil defective
Check whether the CAN bus is coorectly connected to both the ignition and the other CAN bus participants. If the CAN bus connection is correct, you should be able to reset the error within 1 to 2 minutes. Please contact the GEJENBACHER service department if the error cannot be reset. Check whether the ignition has been activated in the CAN mode. If not, have it activated by a GE-JENBACHER mechanic.
Have a GE JENBACHER mechanic update the ignition.
Eleminate cause!
Eleminate cause!
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 30 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
3218
3219
3220
3221
3223
OIL PRESSURE LOW leak in the oil lines or the oilpan clogged oil cooler, oil filter or oil line uncontrolled switching off (killing) of engine too low speed oil level below "min. oil level" defective oil pressure transmitter engine switch-off by closed current loop (defect monitoring) wrong adjustment of fringe value EXCITATION VOLTAGE LOW Voltage controller faulty Excitation voltage protection has been tripped JACKET WATER TEMPERATURE HIGH hot water feedback temp. too high cooler clogged, calcified, dirty return temperature control incorrectly adjusted emergency cooler clogged calcified, dirty fresh water missing cool. wat. pump defect defect. cool. water temp. transmission heat circulation pump defective heat circ. slide, fresh - water slide closed ambient temp. too high (with table cooler) throughflow amount too small (primary/secondary) follow-up heating when shut off water circulations not vented motor output too high glycool amount too high defective short-circuit thermostat wrong adjustment of fringe value water circulation not vented GAS PRESSURE LOW IN GAS TRAIN 1 gas valve closed wrong adjustment or defective gas pressure controller missing gas supply (line breakage) pressure fluctuations by other user defective pressure switch no gas present (sewer gas) wire breakage to PLC dirty filter in supply line
Eleminate cause!
change controller Close protection switch
Eleminate cause!
Eleminate cause!
TI 10000300
INTAKE AIR TEMPERATURE HIGH
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 31 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
Defective fuse Wire breakage on PLC Defective analog input card Customer signal not present
Eleminate cause!
3224
INTAKE AIR TEMPERATURE MEASURING SIGNAL FAILURE Exceeding the intake temperature for This warning should be which full engine output was agreed. An regarded as an indication, no output reduction caused by [too high] an further action is required. The intake temperature is possible. reasons for the output reduction are physical in nature. Cleaning the exhaustgas turbochargers will result in higher power reserves.
3310
IGNITION OUTPUT MONITORING CYLINDER Signal from client
3311
IN/OUT CHANNEL FAILURE Regulation fault MSF fault Converter adjustment!
3402
JACKET WATER PRESSURE LOW Leakage in emergency cooling water system Faulty emergency cooling water pressure sensor Leaking safety valve Faulty membrane in pressure compensation reservoir Incorrectly preset limiting value Wire breakage to PLC
3406
JACKET WATER PRESSURE HIGH Registration by customer
3411
FUEL MIXTURE TEMPERATURE HIGH defective mixture cooling pump mixture cooler clogged, calcified, dirty hot water feedback temp. too high fresh water exchanger is clogged, calcified, dirty defective PT100 water circulation of mixture cooling not vented cooling water amount of mixture too low wrong adjustment of fringe value
Eleminate cause!
Eleminate cause!
Eleminate cause!
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 32 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
3497
Failure in the safety loop When the closed-current circuit is activated by an EMERGENCY STOP or by the heating circuit control system, not all closed-current circuit relays report the drop-out position to the control system.
Have all closed-current circuit relays checked by a GE Jenbacher service mechanic or by a mechanic from a specialized company authorised to do so by GE Jenbacher. The error message can only be reset when the EMERGENCY STOP switch is pressed. To that end, all closed-current circuit relays must report the drop-out position to the control system.
3506
POWER REDUCTION IN ISOLATED OPERATION Isolated operation below limiting value Eleminate cause! Monitoring period exceeded
3507
OIL PRESSURE HIGH Oil filter or oil line uncontrolled switching off (killing) of engine too low speed defective oil pressure transmitter engine switch-off by closed current loop (defect monitoring) wrong adjustment of fringe value
Eleminate cause!
3515
AIRCONDITIONING UNIT FAILURE IN MODULE INTERFACE CABINET
3516
JACKET WATER TEMPERATURE HIGH Wire breakage Short-circuit Rotating rectifier diode error Excitation protection switch activated Excitation current relais failure Cos phi / voltage regulator error
3517
Eleminate cause!
COMMUNICATION TO DIA.NE WIN SERVER FAILED Connection between DIA.NE XT and Check connection, plug in DIA.NE WIN server interrupted network cable, check DIA.NE WIN server has failed or is functionality of network defective components (cables, DIA.NE HUB failure WIN server network card, Software technical problem at DIA.NE HUB, DIA.NE XT network WIN server components), replace network
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 33 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
components. Check and repair voltage supply, contact competence centre, replace DIA.NE WIN server hard disc, replace DIA.NE WIN server. Check and repair voltage supply, contact competence centre, replace HUB. Contact competence centre, replace DIA.NE WIN server hard disc
3518
DATA REGISTRATION IN DIA.NE WIN SERVER FAILED Communication to DIA.NE WIN server Check connection, plug in has failed network cable, check DIA.NE WIN server has failed or is functionality of network defective components (cables, DIA.NE HUB failure WIN server network card, Software technical problem at DIA.NE HUB, DIA.NE XT network WIN server components), replace network components. Check and repair voltage supply, contact competence centre, replace DIA.NE WIN server hard disc, replace DIA.NE WIN server. Check and repair voltage supply, contact competence centre, replace HUB. Contact competence centre, replace DIA.NE WIN server hard disc
11 12 13 20 30 40 50
START CONDITIONS MISSING OF MOTOR OF AGGREGATE OF THE UNIT MOTOR WON'T START MOTOR SAWING IN IDLE RUN (can't be synchronized) MOTOR DOES NOT REACH FULL LOAD (while maintaining the guaranteed pollutant emissions) MOTOR OR SYSTEM MOTOR/GENERATOR RUNS IRREGULARLY OR UNSTABLE WITH LOAD
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 34 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
51 52 53 54 55 56 57 60 70 90 100 101 102 103 104 105 110 120 101 7 101 8 101 9 102 1 102 3 102 6 102 7 102 8 103 1 103 6 103 7 103 8 103 9
MOTOR VIBRATES STRONGLY MOTOR SHAKES (quick load fluctuations or great current and voltage fluctuations with little change of motor output) ENGINE ROCKING GENERATOR MOTOR ESCALATES (great current and voltage fluctuations at only little change in motor output) MOTOR ARCHIEVES NOT STABLE CONDITION (output swings slowly up and down) ENGINE STOPS (individual cylinders) OR HAS AN EXHAUST GAS TEMPERATURE DEVIATING FROM THE CENTRAL VALUE PERIODIC FLUCTUATIONS IN PERFORMANCE MOTOR KNOCKING MISFIRING DETECTION RESPONDS, OR AT BR6 DEVIATION OF CYLINDER FLUE GAS TEMPERATURE TOO GREAT OIL CONSUMPTION TOO HIGH TURBOCHARGER DEFECT COMPACTOR THROWING OIL TURBINE THROWING OIL TURBOCHARGER EFFICIENCY NOT OKAY (flue gas turbocharger no longer archieves required load pressure) COMPACTOR OR TURBINE WHEEL TOUCHED THE HOUSING TURBOCHARGER VIBRATING WATER IN LUBRICATION OIL THE CONTRACTUALLY AGREED DEGREE OF EFFICIENCY IS NOT REACHED IN SPITE OF THE SALES TOLERANCE OIL PRESSURE LOW ENGINE OIL LEVEL LOW JACKET WATER PRESSURE LOW JACKET WATER TEMPERATURE HIGH START UP FAILURE SHUTDOWN FAILURE FAILURE GAS TRAIN 1 GAS PRESSURE LOW IN GAS TRAIN 1 EMERGENCY STOP/SAFETY LOOP GENERATOR OVERLOAD/SHORT CIRCUIT GENERATOR WINDING TEMPERATURE HIGH GENERATOR REVERSE POWER SYNCHRONIZING FAILURE
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 35 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
104 0 104 1 104 2 104 3 104 8 105 0 105 1 105 2 105 3 105 4 105 6 105 7 105 9 106 1 106 4 107 8 108 0 108 1 108 3 110 5 110 9 111 0 111 1 111 2 111 3
FUEL MIXTURE TEMPERATURE HIGH POWER SIGNAL MISSING POWER SIGNAL OVERLOAD ENGINE OIL TEMPERATURE HIGH KNOCKING FAILURE JACKET WATER PRESSURE HIGH ENGINE OIL LEVEL HIGH GAS PRE-ALARM GAS ALARM FIRE ALARM FAIL SAFE LOOP TRIPPED HIGH GAS PRESSURE IN GAS TRAIN 1 OIL FILTER DIFFERENTIAL PRESSURE HIGH IGNITION SYSTEM FAILURE OVERSPEED (RPS-CONTROL SYSTEM) BOOST PRESSURE MEASURING SIGNAL FAILURE LEANOX CONTROL ALLOWED DEVIATION EXCEEDED KNOCK SENSOR MEASURING SIGNAL FAILURE CONTROL CARBURATOR DEFECTIVE SPEED OF TEMPERATURE CHANGE MIXTURE TEMPERATURE MAXIMUM GENERATOR LOSS OF EXCITATION GENERATOR FREQUENCY TOO LOW GENERATOR FREQUENCY TOO HIGH NEUTRAL CURRENT MAXIMUM GENERATOR POWER MEASURING SIGNAL FAILURE
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 36 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
111 4 112 0 112 6 112 7 112 9 113 4 113 5 114 0 114 3 114 4 114 5 114 8 116 7 116 8 117 7 118 5 118 6 118 9 119 2 119 3 119 4 119 5 119 6 121 6 121 7
FUEL MIXTURE TEMPERATURE MEASURING SIGNAL FAILURE SPEED MEASURING SIGNAL FAILURE GENERATOR VOLTAGE LOW GENERATOR VOLTAGE HIGH FAILURE WITH AUXILIARIES GROUND FAILURE ROOM TEMPERATURE HIGH MODULE INTERFACE PANEL CIRCUIT BREAKER TRIPPED VOLTAGE NEGATIVE SEQUENCE CURRENT NEGATIVE SEQUENCE JACKET WATER TEMPERATURE LOW STARTER BATTERY VOLTAGE LOW HEATING WATER RETURN TEMPERATURE HIGH REQUEST FOR MAINTENANCE ENGINE ROOM AIR PRESSURE MEASURING SIGNAL FAILURE GENERATOR WINDING TEMPERATURE HIGH HEATING WATER RETURN TEMPERATURE MEASURING SIGNAL FAILURE RELEASE FROM SYNCHRONIZING MISSING ACTUATOR FAILURE LOAD BANK FAN IS NOT RUNNING LOAD BANK COMMON ALARM LOAD BANK CONTACTOR FAILURE LOAD BANK CB OVERLOAD/SHORT CIRCUIT BUS BAR VOLTAGE SENSOR FAILURE GENERATOR CB STATUS SIGNAL FAILURE
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 37 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
121 8 121 9 122 0 122 1 208 2 208 3 208 4 208 6 209 7 210 1 210 2 210 3 210 4 210 5 211 1 211 6 211 7 211 8 212 0 300 3 302 5 302 6 302 7 302 8 302 9
GENERATOR CB OPENING FAILURE GENERATOR CB CLOSING FAILURE GENERATOR CB O-SIGNAL FAILURE GENERATOR CB 1-SIGNAL FAILURE PARAMETER(S) MISSING RPS (CONTROL SYSTEM) BATTERY FAILURE LEANOX ALGORITHM FAILURE CARBURATOR POSITION MEASURING SIGNAL FAILURE DEVIATION POWER SETPOINT TO POWER PRESENT VALUE MAXIMUM JACKET WATER TEMPERATURE MEASURING SIGNAL FAILURE ENGINE OIL TEMPERATURE MEASURING SIGNAL FAILURE JACKET WATER PRESSURE MEASURING SIGNAL FAILURE JACKET WATER PRESSURE MEASURING SIGNAL FAILURE GENERATOR WINDING TEMPERATURE MEASURING SIGNAL FAILURE KNOCK SENSOR MEASURING SIGNAL FAILURE DUMP RADIATOR FAILURE INTERCOOLER WATER PRESSURE LOW MIXTURE COOLING WATER PUMP FAILURE ENGINE ROOM VENTILATION FAILURE MEASURING SIGNAL FAILURE IGNITION TRIGGER PICKUP MISSING IGNITION RESET PICKUP MISSING IGNITION CAM PICKUP MISSING IGNITION SHUTOFF OVERSPEED IGNITION CPU FAILURE
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 38 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
303 0 303 1 305 2 321 6 321 7 321 8 321 9 322 0 322 1 322 3 322 4 331 0 331 1 340 2 340 6 341 1 349 7 350 6 350 7 351 5 351 6 351 7 351 8
IGNITION PARAMETER FAILURE Faulty ignition/CAN coupling WRONG TYPE OF IGNITION SYSTEM ENGINE OIL TEMPERATURE HIGH MISFIRING FAILURE OIL PRESSURE LOW EXCITATION VOLTAGE LOW JACKET WATER TEMPERATURE HIGH GAS PRESSURE LOW IN GAS TRAIN 1 INTAKE AIR TEMPERATURE HIGH INTAKE AIR TEMPERATURE MEASURING SIGNAL FAILURE IGNITION OUTPUT MONITORING CYLINDER IN/OUT CHANNEL FAILURE JACKET WATER PRESSURE LOW JACKET WATER PRESSURE HIGH FUEL MIXTURE TEMPERATURE HIGH Failure in the safety loop POWER REDUCTION IN ISOLATED OPERATION OIL PRESSURE HIGH AIRCONDITIONING UNIT FAILURE IN MODULE INTERFACE CABINET JACKET WATER TEMPERATURE HIGH COMMUNICATION TO DIA.NE WIN SERVER FAILED DATA REGISTRATION IN DIA.NE WIN SERVER FAILED
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 39 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
Index 10 10
START CONDITIONS MISSING
11
OF MOTOR There is a defect as e.g. min. or max. oil level. The current loop (safety loop) is open
12
13
20
OF AGGREGATE e.g. min. gas pressure closed current loop not released
OF THE UNIT no release through auxiliary operation
MOTOR WON'T START gas pressure too low or too high or gas pressure fluctuations
throttle flap won't open
Ignition defective Ignition spark missing
remove indicated cause remove loose contact or wire breakage, or replace defective monit. device.
remove cause or complain at trader;remove loose contact or wire breakage, or replace defect monitoring device
check which auxiliary operation is not running, e.g. HW-circulation pump or throughflow indicator and machine room vent flap open, gas warning installation etc.
gas pressure prior to gas pressure controller line does not correspond to listings in techn. scheme. check whether supply of the Heinzmann actuator driver is okay (amber LED in actuator be lit) the Heinzmann actuator driver is defective (red LED in driver lit) due to low voltage (<12 VDC); short circuit at the lines to the actuator or overtemperature (> 90°C); the pickup or the wiring from the pickup to the actuator or DIANE is defective; check whether the throttle flap or the control systems are stuck or do not properly function. check following points (partly with stroboscope).mains supply of DISN-unit (relay
TI 10000300
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 40 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
electrode distance too smallat all spark plugs
start or idle run position of mixer or gas or air bypass flap incorrect
Unsuitable Impco or Jenbacher mixer
gas pressure in front of zero-pressure controller too high
wrong mixer adjustment membrane of gas pressure controller
defective or bad contact) pickup distance pickup connection defect at relay for the G-line DISN-unit defective wrong.One or several magnets with too little residual magnetism or magnet broken out when changing plugs by sets to non - JENBACHER tested models, electrode distance is often too small, needs greater distance. unsuited gas pressure controller causing gas pressure fluctuations,must be replaced, correction of programmed values to experimental values, or to an inflammable mixture via pollutant measuring kit; check whether the servo motor, the gas or air bypass flap is okay, or check drive for the feedback pot. mixer cone on Impco does not correspond to the current gas type;check whether the air slot at Jenbacher-mixer corresponds to used type of gas. 1) higher values lead to excessive enriching of motor at start; 2) following adjustment of gas adm. pressure: adjust zero pressure controller so that after start of motor there is not speed breakdown (motor in this case too rich); if motor does not increase speed or increases too slow it is too lean; if motor is too rich, gradually turn zero pressure spindle out by 1 rot; if motors is too lean gradually turn spindle in by 1 rot. check programming of start opening check membrane for ruptures
see maintenance
TI 10000300
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 41 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
defective gas pressure controller stuck gas magnet valve is defective no inflammable mixture forms
throttle flap opens and closes quickly during start procedure
30
check for easy movement check whether gas magnet valves open check whether the slot at the mixer cone at the Jenbachermixer corresponds to the %oposition programmed at the DIANE; check whether the mixer cone moves, whether in the drive the spring for the catching is missing or the servo motor is defective (wire breakage or pot-drive) cwrong pick-up adjustment and quite often must be positioned closer to toothed wheel of starter according to adjustment instructions
MOTOR SAWING IN IDLE RUN (can't be synchronized) Heinzmann actuator defective replace (damaged) unsuited mixer mixer cones at Impco do not correspond to gas type or the air slot on Jenbacher-mixer, e.g., for depot gas, is too high, i.e., replace mixer cone, or reduce air slot (replace mixer or reduce shims under mixer head with new Jenbacher mixers) ignition defective (cylinder missing) replace Ignition coildefective replace as a result of a pulsating draught in the fit flap with a solenoid valve at exhaust flue while still warm the foot of the flue. speed controller not optimally adjusted Gas-pressure fluctuations use manometer or water Check the control rods (ball heads worn columnto measure where the / sluggish) gas pressure fluctuations Mixture too lean / too rich appear, i.e., upstream of mixer, upstream of gas Check speed controller setting pressure controller or downstream of customergas admission controller; if controller unsuited, replace it, or call supplier (of admission pressure controller). damaged joint cones of control line replace joint cones
see
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 42 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
maintenance the control linkage adjusted too progressively in idle run throttle flap slightly bent following detonation in intake line and does not fully close anymore (idle speed partially too high) sluggish control lines, or throttle flap
Heinzmann actuator driver not optimally adjusted idle run position at gas or air bypass valve not optimally adjusted or no optimal programming in DIANE 40
correct adjustment and make sure that the flap can fully close. remove throttle flap and align, check for easy functioning
relube the joints, or disassemble the throttle flap bearing and replace; replace bearing bushing. check the 0% position of the actuator better adjust idle run position by trial or program differently
see maintenance
see maintenance
MOTOR DOES NOT REACH FULL LOAD (while maintaining the guaranteed pollutant emissions) Defective turbocharger check compactor shovel (missing power and power loss) whether entry edges are damaged by foreign bodies or whether formation of deposits in the compactor housing reduces output or whether runnertouches housing (clean compactor housing and runner). Check the turbine wheel for damage and free run. combustion air ratio not okay (motor correct leanox adjustment at running too lean), DIANE Part of the broken-off protective pipe in open the end cover and a manifold compensator is interrupting remove parts or replace the flow of the exhaust gases compensator.Inspect turbine wheel for damage. faulty insulation of exhaust collection attach new insulation of line (insulation is completely or partiall thickness and efficiency as worn down due to frequent dismantling original one or due to vibraiton mixture transporting parts after seal off compactor to throttle flap are not tight suction temperature too high(at >25°C) check whether ambient air reduction can be used acc. to ISO thermostat adjusted too high, 3046, except for other contractual the room venting not properly agreement planned or other vent stages do not turn on mixture temperature too high in spite of check mixture cooler, clean if TI 1000-
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 43 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
correct mixture cooling water admission temp. output display wrong; ignition not properly adjusted, orcombustion misfires by e.g. too large electrode distance or failure of cylinders due to defectat ignition system (e.g. defect ignition coil) throttle flap not fully opened,actuator stands at 100% contaminated air filter and hence great pressure loss before mixer flue gas counter pressure too
leakage at the flange connections of flue gas line
necessary (mixture and water part) or glycol ratio too high (check). check and correct error; make ignition check, measure ignition point, correct ignition adjustment and electrode distance, replace defective parts. correction of controller linkage adjustment actuator - throttle flap. measure pressure loss clean or replace the filter measure the counter pressure after high turboloader exit;clean oxikate and waste heat boiler if necessary. seal the line (replace sealings, tighten screws correctly) if necessaryrework flanges
0201, see maintenance see maintenance
see maintenance see maintenance
50
MOTOR OR SYSTEM MOTOR/GENERATOR RUNS IRREGULARLY OR UNSTABLE WITH LOAD
51
MOTOR VIBRATES STRONGLY failure of cylinder pendulum damper not okay motor adjustment not okay (ignition point) straps of motor add-on pieces not okay
check ignition, valves, check compression check and replace if necessary check and adjust
see maintenance see maintenance
check and remedy
52
MOTOR SHAKES (quick load fluctuations or great current and voltage fluctuations with little change of motor output) faulty ignition check ignition system see maintenance combustion air ratio not okay (motor check and adjust using the running too lean), pollutant measuring device water, humidity in spark plug chamber dry spark plug chamber, (after washing motor) clean plugs and connector.
53
ENGINE ROCKING biological gas: gas pressure control line not okay (e.g. water in the gas pressure controllers, stuck gas control valves)
check gas pressure with water column upstream of mixer. check gas pressure controller, repair if necessary
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 44 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
misfires (motor adjusted too lean)
check and adjust using the pollutant measuring device
54
GENERATOR MOTOR ESCALATES (great current and voltage fluctuations at only little change in motor output) voltage controller at generator not okay adjust or repair description cos phi controller not okay check cables bad connection in circuit (cables) check that connector is firmly generator located
55
MOTOR ARCHIEVES NOT STABLE CONDITION (output swings slowly up and down) Non-optimal setting of Leanox-control optimise the controller parameters parameters at constant power Check control rods (ball heads worn / setpoint sluggish) Check gas pressure Check power control Check gas-quality fluctuations (landfill gas, possibly sewage gas) harmonization of leanoxcontroller harmonize time behavior output control not functioning leanox contr. to time behavior output control (decouple) control linkages not okay (too large check, if necessary repair or see dead center/to progressively adjusted, replace maintenance etc.) gas mixer not properly adjusted (e.g. lcheck, adjust characteristic not okay) gas pressure fluctuating check gas pressure TI 1000controller, check admission 0300 pressure quick fluctuation of the mixture check temp. in hot water Schematic temperature circulation diagram
56
ENGINE STOPS (individual cylinders) OR HAS AN EXHAUST GAS TEMPERATURE DEVIATING FROM THE CENTRAL VALUE Pre-combustion chamber gas pressure Eleminate cause! set too low Check spark plugs, ignition coils and ignition system defective ignition check see maintenance defective spark plug check voltage demand, see replace if necessary maintenance
57
PERIODIC FLUCTUATIONS IN PERFORMANCE continual switching on and off of the Conversion to thermostaticallyventilator(s) controlled, frequencyregulated ventilator
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 45 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
60
MOTOR KNOCKING output limitation faulty mixture cooling water temperature too high cooling water throughflow through the mixture cooler too low deposits in combustion chamber are butane and air mixed into the fuel gas? motor set too rich methane number of fuel gas too low combustion air ratio not okay ignition point not okay too early ignition point is set mixture temperature too high mixture cooler not okay
70
Eleminate cause! Eleminate cause!
Schematic diagram
Eleminate cause! check, remove deposits if any Eleminate cause! Eleminate cause! take gas sample and have it analyzed check, correct adjustment if necessary determine ignition point and adjust toward "late" Eleminate cause! check, remedy fault if any Eleminate cause!
TI 10000300 Schematic diagram
MISFIRING DETECTION RESPONDS, OR AT BR6 DEVIATION OF CYLINDER FLUE GAS TEMPERATURE TOO GREAT spigot nut at the line to gas inlet valve is retighten the screwing or seal loose or the cutting ring is loose (flue gas temperature is higher at misfire) defective output measurement (motor check the output output does not correspond to measurement (compare measured output) counter measurement with output measurement) wrong adjustment of misfire detector Eleminate cause! verdigris on ignition coil exit (connector clean carefully to make metal to ignition cable) shiny motor runs too lean due to defect of check motor adjustment mixer (or of the air bypass flap)or due to withmeasuring kit, if too lean, leanox control remedycause crack at end of thread torque too high replace spark plug and see (plug tightened without torque wrench or tightencorrectly with the right maintenance with defective tool, or tightened too torque much) missing or bad contact at highvoltage check contact screwing output of ignition coils or at ground ground contact at the ignition contact or ignition coil coil and retighten the connection defect at cable loom between ignition in case of loose contacts box and ignition coils (scraping spots, retighten screws, in all other ground contact, overheating and cases replace cable loom cracking at the insulation, loose contacts at the connections
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 46 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
interferences at the ignition pearl formation on electrodes due to overheating (e.g. knocking at times)
electrode distance too small (possibly only at site on one electrode) boost pressure transmitter defect or due to drift transmits too low value (to leanox controller or DIANE) causing too lean operation of motor spark plug shows blue or brown discoloring at steel part and shows electrode motor misfires because it is set too lean or due to defective ignition quick generator output change entry of dirt (shavings) or grease into the prechamber annulus, i.e. slits are partially blocked too large ignition voltage demand due to large electrode distance
spring in brass part of plug connector without voltage, or broken, bad contact to brass cap of plug (traces of smoke) consumption spark plug shows abnormal spark appearance or flashover at bottom of plug on oscilloscope
misfiring due to too low ignition voltage offer (defect at the ignition coil) breakage of ignition cable interior at the soldering at the brass part of the plug connector or at the bend of the rubber bush ceramic body at the spark plug on top, or inner part of plug, is soiled with electr. conductive grease or similar and causes spark discharge in this area; plug shows in lower range of brass part a low-out, thus spark discharge to plug shell is
check shield at the cables cannot be seen, metallic pearl may be caused by local melton between electrodes (remove with thickness gauge and check gap) correct electrode distance.
see maintenance
check boost pressure controller, i.e., compare boost pressure signal with manometer, in case of deviation replace transmitter spark plug was not tightened sufficiently and overheated check using an exhaust emmissions analyser and correct if necessary Eleminate cause! Wash the pre-chamber with petrol and blow out. re-adjustment of the electrode gap with the special tool, or replacement of the sparking plugs replace spark plug connector
see maintenance
plug daubed at the end side with electrically conductive gliding agent (when sprayed with Ultra-Therm not covered or too much spray used which dropped on electrodes when hot) check the coil at motor standstill with ignition voltage tester frequent pulling of the plug connector at the cable, the cable ruptures are not visible, replace plug and cable clean plug and connector or replace.check for proper seat of dust cap on top of the valve hoodBlow-out is usually very small, onlyvery small grey point is visible on spark
TI 14000111
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 47 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
created elastic seal ring inParker" valve of gas inlet valve destroyed
loose brass cap (traces of smoke on top of ceramic body) ball sticks to seat of gas inlet valve
90
OIL CONSUMPTION TOO HIGH carbonisation of the fire land through excessive idling or nonobservation of the limit values for used oil (TI 1000-0099B) leads to carbonisation of hard deposits on the piston top land. The upper rim pushes oil in front of it, more oil is burnt and the 1st ring receives too little oil and wears very repidly. (Ring carries to full height within 1000 op. hrs., darfk, cruty deposit in piston groove Piston runs crooked due to connecting rod parallelity tolerances being exceeded; similar effects to above with the same symptoms and can be clearly seen at the piston skirt on the pressure side, as well as at the fire land above the level of the bolts (one side clear, the other with hard oil carbonisation) (reduced gas access to 1st piston ring). turboloader throwing oil
100
TURBOCHARGER DEFECT
101
COMPACTOR THROWING OIL air filter resistance too great (dirty filter)
102
TURBINE THROWING OIL axial or radial play of runner
passage. replace plug suppresser if ball valve is too leaky, the pressure at theParker" valve is too high and the seal ring is destroyed tighten cap; if threading underneath of brass cap is loose, replace spark plug increase prechamber gas difference pressure; clean (wash valve, i.e. clean from lubricating oil which deposits in valve especially during start-up phase)
see maintenance
remove piston and clean replace first ring and break in motor
see point 0100
clean air filter, if required replace
see maintenance
measure, if exceeding admissible too great values
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 48 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
oil sealing at turbine is defective
repair or replace check and repair
103
TURBOCHARGER EFFICIENCY NOT OKAY (flue gas turbocharger no longer archieves required load pressure) entrance shovels of compactorare check, search cause (foreign defective or damaged body?) and replace FGTL if necessary turbine shovels damaged check, search cause (foreign body?) and replace FGTL if necessary
104
COMPACTOR OR TURBINE WHEEL TOUCHED THE HOUSING defective axial sealing -axial play too measure, if exceeding great admissible too great values repair or replace
105
TURBOCHARGER VIBRATING turbine shovels (compactor shovels) defective (unbalanced)
110
WATER IN LUBRICATION OIL leaks at oil cooler craks or sinkholes at upper side of cylinder head between water storage and oil storage leaky O-rings at the cylinder liner leaky O-rings at the prechambers
replace wheel or turboloader
check and replace if necessary check, replace if necessary
replace O-rings replace O-rings
120
THE CONTRACTUALLY AGREED DEGREE OF EFFICIENCY IS NOT REACHED IN SPITE OF THE SALES TOLERANCE on site the sum of border conditions is measure values exactly and strongly negative in order to reach an convert to standard condition optimal efficiency (e.g. heating value of according to ISO 3046 depot gas extremely low, induction temperature >25°C, air pressure <1000 mbar) flue gas counter pressure too high due clean boiler to dirty waste heat boiler induction vacuum before compactor too clean air filter see high due to dirty air filter maintenance
1017
OIL PRESSURE LOW leak in the oil lines or the oilpan clogged oil cooler, oil filter or oil line uncontrolled switching off (killing) of engine too low speed oil level below "min. oil level" defective oil pressure transmitter
Eleminate cause!
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 49 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
engine switch-off by closed current loop (defect monitoring) wrong adjustment of fringe value 1018
1019
1021
ENGINE OIL LEVEL LOW leakage in oil lines or oilpan defective solenoid valve "fill oil" (won't open) defective oil level sensor or evaluation device empty fresh oil tank slide at oil pump station is closed three-way cock in wrong position oil level measurerer not adjusted (with analog measuring) "sag" in pressure-equalization line (venting) wrong adjustment of fringe value JACKET WATER PRESSURE LOW leak in cooling water system defective pressure transmitter of cooling water leaking safety valve damaged membrane in pressure wrong adjustment of fringe value crack in inlet or outlet duct of cylinder head JACKET WATER TEMPERATURE HIGH hot water feedback temp. too high cooler clogged, calcified, dirty return temperature control incorrectly adjusted emergency cooler clogged calcified, dirty fresh water missing cool. wat. pump defect defect. cool. water temp. transmission heat circulation pump defective heat circ. slide, fresh - water slide closed ambient temp. too high (with table cooler) throughflow amount too small (primary/secondary) follow-up heating when shut off water circulations not vented motor output too high glycool amount too high defective short-circuit thermostat wrong adjustment of fringe value water circulation not vented
Eleminate cause!
Eleminate cause!
Eleminate cause!
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 50 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
1023
1026
1027
1028
1031
1036
START UP FAILURE 3 unsuccessful starting attempts no gas defective ignition wrong gas mixer valve start position wrong adjustment of gas pressure safety automation in motor terminal strip is off starter won't start SHUTDOWN FAILURE leaky or defective gas valves speed limit wrongly adjusted FAILURE GAS TRAIN 1 leaky gas valves gas valve closed defective gas tightness coantroller clogged gas filter too low gas pressure dirty filter in supply line to tightness controller condensate in the supply line to tightness controller vibrations of tightness controller device GAS PRESSURE LOW IN GAS TRAIN 1 gas valve closed wrong adjustment or defective gas pressure controller missing gas supply (line breakage) pressure fluctuations by other user defective pressure switch no gas present (sewer gas) wire breakage to PLC dirty filter in supply line EMERGENCY STOP/SAFETY LOOP emergency off button enabled wire breakage safety loop belt alarm --> when in emergency off chain gas alarm --> linked
Eleminate cause!
Eleminate cause!
Eleminate cause!
TI 10000300
Eleminate cause!
TI 10000300
Eleminate cause!
GENERATOR OVERLOAD/SHORT CIRCUIT wrong adjustment or defective output Eleminate cause! controller overload in isolated operation
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 51 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
short circuit wrong adjustment or defective output switch wrong adjustment or defective cos-phi controller wire breakage to PLC unbalanced load 1037
GENERATOR WINDING TEMPERATURE HIGH generator overload Eleminate cause! unbalanced load defective generator wrong cos-phi posistor or analogue input defective wire breakage to PLC ambient temperature too high wrong adjustment of fringe value
1038
GENERATOR REVERSE POWER generator power switch does not open 10% power switch point wrong adjustment output reduced too quickly defective output measurement (only variant with reverse current relay) wrong adjustment rev. current relay or defective DIANE wrong adjustment or defective defective current transmitter wire breakage to PLC short circuit or wire breakage in 20 mA current loop of output measuring transducer ignition failure (signal pickup/DISN failure)
1039
1040
SYNCHRONIZING FAILURE speed controller hunting throttle control rod loose synchronising unit faulty engine rough (ignition coil faulty) voltage balance circuit faulty engine idles too long gas pressure oscillating FUEL MIXTURE TEMPERATURE HIGH defective mixture cooling pump mixture cooler clogged, calcified, dirty hot water feedback temp. too high fresh water exchanger is clogged, calcified, dirty
Eleminate cause!
Eleminate cause!
Eleminate cause!
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 52 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
defective PT100 water circulation of mixture cooling not vented cooling water amount of mixture too low wrong adjustment of fringe value 1041
1042
1043
1048
POWER SIGNAL MISSING wire breakage or short circuit of output signal wire breakage or short circuit of current transducer output measuring transducer defect defective current transducer defective output controller power setpoint too small (<10% Pnenn) POWER SIGNAL OVERLOAD overload isolated operation output controller wrong adjusted or defective input of wrong measuring transducer or wrong output switch point defective output measuring transducer defective current transducer defective output controller ENGINE OIL TEMPERATURE HIGH oil cooler clogged, dirty hot water feedback temp. is too high defective cooling water pump cooling water heat exchanger chocked dirty return remperature control incorrectly adjusted fresh water heat exchanger chocked, dirty table cooler too small ambient temp. to high (with table cooler) throughflow amount too low (primary/second.) limit value adjusted incorrectly KNOCKING FAILURE pre ignition (deposits in combustion chamber) ignition timing point too early monitoring set too sensitively bad contact on the connector at the sensor(s) knocking sensor or knocking control
Eleminate cause!
Eleminate cause!
Eleminate cause!
Eleminate cause!
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 53 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
defective Leanox controller programmed falsely (mixture too rich) 1050
1051
1052
1053
1054
1056
1057
JACKET WATER PRESSURE HIGH slide for filling cooling water is open leaking plug sleeve defective cooling water pressure transmitter defect. cool. water temp. measurement and overheated motor pressure expansion container too small filling pressure too high wrong adjustment of fringe value ENGINE OIL LEVEL HIGH defective solenoid valve "fill oil" defective oil level sensor or evaluator oil level measurerer is not adjusted (with analog measuring) wrong adjustment of fringe value GAS PRE-ALARM leak in gas line system solvent, cleaning agent in container transmitter defective wrong adjustment or defective evaluator GAS ALARM leak in gas line system solvent, cleaning agent in container transmitter defective wrong adjustment or defective evaluator FIRE ALARM fire smoke solvent, cleaning agent in container transmitter defect evaluator defect FAIL SAFE LOOP TRIPPED 24V supply missing safety loop monitoring tripped emergency stop HIGH GAS PRESSURE IN GAS TRAIN 1 Gas pressure controlle wrong adjustment or defective
Eleminate cause!
Eleminate cause!
Eleminate cause!
Eleminate cause!
Eleminate cause!
Eleminate cause!
Eleminate cause!
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 54 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
Pressure switch defect wire breakage to PLC
1059
OIL FILTER DIFFERENTIAL PRESSURE HIGH clogging of oil filter due to dirt or water in Eleminate cause! lubrication oil (check oil on water, remedy cause. Determine type of other dirt of the filter by cutting open filter, possible early bearing damage!!) filter must be changed!
1061
IGNITION SYSTEM FAILURE faulty thermocouple Cable break to PLC Analogue input card faulty Setting parameters not allowed now
Incorrect parameter IC9xx Ignition failure caused by a malfunction in the ignition unit
IC9xx incorrect information from the pick-ups
IC9xx Misfiring
1064
Eleminate cause!
The parameters of the ignition can only be adjusted at engine standstill. Parameter outside the valid range Read failure from the ignition (if possible). In case of program failure, first switch off the supply voltage and then switch it on again Check whether all ignition coils are connected. Replace the ignition Clean the magnetic pickups. Check the distance between pickup and trigger source (Be careful when reaching the highest position so as to prevent mechanical triggering!) Replace the faulty pickups. Check the high-voltage requirement. Check the shielding at the pickups and the IC900. Check the supply voltage using an oscilloscope. Check the mass circuit from ignition to engine mass.
OVERSPEED (RPS-CONTROL SYSTEM) speed overshoot afte mains failure Eleminate cause! speed limit wrongly adjusted
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 55 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
1078
BOOST PRESSURE MEASURING SIGNAL FAILURE 24V supply to boost pressure transducer secure interfaces faulty repair cables transducer cables faulty wrong transducer change transducer transducer range exceeded tranduce faulty analogue input card faulty
1080
LEANOX CONTROL ALLOWED DEVIATION EXCEEDED measuring signal fault - actual power see fault No. 1113 Measuring signal fault - mixture see fault No. 1114 Temperature see fault No. 1078 see fault No. 1083 Measuring signal fault - boost pressure Gas mixer control defective
1081
KNOCK SENSOR MEASURING SIGNAL FAILURE 24 V supply failure for knocking Sensor check interface Knocking sensor cable fault Check cable Knocking sensor defekt Change sensor Interferance on knocking sensor Move knocking sensor cable analogue input card faulty as far as possible from ignition cable
1083
CONTROL CARBURATOR DEFECTIVE 24V supply failure for DM455 Gasmixer cable fault Gasmixer siezed 24V supply failure for gasmixer position feedback Faulty position-feedback plate Position feedback cable faulty
Check power supply in 24V interface and at the DM455 board Correct wiring Smooth running of gas mixer Exchange fuse and board
TI 10000300
1105
SPEED OF TEMPERATURE CHANGE MIXTURE TEMPERATURE MAXIMUM Inform the GE-JENBACHER customer service department
1109
GENERATOR LOSS OF EXCITATION Voltage controller faulty Excitation voltage protection has been tripped Faulty rotating diodes defective cos-phi controller
1110
GENERATOR FREQUENCY TOO LOW Speed governor has been set incorrectly Speed governor is out of order Error in speed governor circuit
change controller Close protection switch Check/replace the diodes
Eleminate cause!
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 56 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
1111
1112
GENERATOR FREQUENCY TOO HIGH Speed governor has been set incorrectly Speed governor is out of order Error in speed governor circuit NEUTRAL CURRENT MAXIMUM Out-of-balance load in isolated operation. Non-symmetrical mains supply causing compensating currents. Inadmissible 3rd (upper) harmonic wave (150 Hz). Earth fault
Eleminate cause!
Eleminate cause!
1113
GENERATOR POWER MEASURING SIGNAL FAILURE Mult - transducer faulty Change multi-transducer Cables for multi-transducer faulty Check cables Analogue input card faulty Change analogue input card wrong adjustment of fringe value
1114
FUEL MIXTURE TEMPERATURE MEASURING SIGNAL FAILURE PT100 faulty change PT100 PT100 cables faulty Check cables Analogue input card faulty
1120
SPEED MEASURING SIGNAL FAILURE Speed pick-up wrongly adjusted 24V supply failure to pickup Pickup cable fault
1126
1127
1129
1134
Gap from 1 revolution of gear rim. Check interface Check cable
GENERATOR VOLTAGE LOW voltage controller fault Excitation voltage protection has been tripped Blown fuse
change controller Close protection switch Check fuse
GENERATOR VOLTAGE HIGH voltage controller fault voltage controller measurement circuit is disturbed
change controller Check measurement circuit
FAILURE WITH AUXILIARIES supply circuit breaker tripped by overload short circuit GROUND FAILURE generator earth fault limiting value on evaluation instrument
check wiring check adjustment circuit breaker
Eleminate cause!
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 57 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
incorrectly adjusted trigger device defective defective current transformer in generator incorrect current transformer current transformer connections exchanged 1135
ROOM TEMPERATURE HIGH room vent failure wrong adjustment or defective thermostat exterior temperatur too high unfavorable placing of thermostat
check the frequency controller
1140
MODULE INTERFACE PANEL CIRCUIT BREAKER TRIPPED Circuit breaker or engine circuit breaker in Eleminate cause! module control cabinet has tripped Power circuit breaker or engine circuit breaker in module control cabinet is off Wire breakage Loose terminal on SPC input card Loose terminal on circuit breaker's or engine circuit breaker's auxiliary contacts
1143
VOLTAGE NEGATIVE SEQUENCE fuse blown in measurement circuit Generator earth fault Generator winding fault Armature fault Mains voltage assymetry
1144
1145
1148
CURRENT NEGATIVE SEQUENCE current transformer circuit interuption Mains voltage assymetry Unbalanced load in Island operation Earth fault JACKET WATER TEMPERATURE LOW failure cooling water preheating return temperature control incorrectly adjusted defective cooling water temp. transmitter heat-up process not finished wrong adjustment of fringe value STARTER BATTERY VOLTAGE LOW loader defect (fuse) not enough battery acid in battery defective battery too strong loads
check fuses Fault checks
check CT circuits Check faults
Eleminate cause!
check battery charging
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 58 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
frequent starts wire breakage to PLC 1167
HEATING WATER RETURN TEMPERATURE HIGH temperature controller warm water not Eleminate cause! correctly no heating demand (pump fault) wrong adjustment of fringe value
1168
REQUEST FOR MAINTENANCE Service counter has reached zero (operating hrs) from preselected limit
reset service counter after completion of service
According to customer setting
1177
ENGINE ROOM AIR PRESSURE MEASURING SIGNAL FAILURE no measuring signal; broken cable replace pressure transducer; replace cable
1185
GENERATOR WINDING TEMPERATURE HIGH generator overload Eleminate cause! unbalanced load defective generator wrong cos-phi posistor or analogue input defective wire breakage to PLC ambient temperature too high wrong adjustment of fringe value
1186
HEATING WATER RETURN TEMPERATURE MEASURING SIGNAL FAILURE wire breakage Eleminate cause! short circuit defective PT100 defective PT100 measuring transformer defective safety device measuring transformer current supply Analogue input card faulty
1189
RELEASE FROM SYNCHRONIZING MISSING a) The synchronisation control logic does a) Check prerequisites for not issue a release because the required logical release from conditions are not fulfilled synchronization (prerequisites relating to specific order according to control description) b) Eliminate cause !
1192
ACTUATOR FAILURE
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 59 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
Disturbance / alarm at the Actuator for butterfly valve (internal equipment). Failure voltage supply 24 VDC, wire break 1193
1194
1195
LOAD BANK FAN IS NOT RUNNING load bank fan not running; defective load bank fuse; load bank overload / short circuit
LOAD BANK COMMON ALARM load bank fan not running; defective load bank fuse; load bank overload / short circuit
LOAD BANK CONTACTOR FAILURE defective fuse; broken cable; interrupted power supply; defective control system
Eleminate cause!
replace fan; replace signal cable; restore power supply; reset and/or replace control system; replace air flow monitoring system; replace fuse; replace signal cable; restore power supply; reset and/or replace control system; visually inspect resistor elem
replace fan; replace signal cable; restore power supply; reset and/or replace control system; replace air flow monitoring system; replace fuse; replace signal cable; restore power supply; reset and/or replace control system; visually inspect resistor elem
replace fuse; replace signal cable; restore power supply; reset and/or replace control system
1196
LOAD BANK CB OVERLOAD/SHORT CIRCUIT load bank overloaded and/or load bank visually inspect resistor short circuit elements; check entire system for short circuit
1216
BUS BAR VOLTAGE SENSOR FAILURE measuring voltage missing Eleminate cause! busbars voltage-detector defective wire breakage SPG-OK message to PLC PLC-input defective
1217
GENERATOR CB STATUS SIGNAL FAILURE wire breakage check cables/connections switch return messages check auxiliary circuit breaker or contactor defective contacts/answerback of (return message/auxiliary contacts) breaker or contactor
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 60 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
relay for switch return message defective PLC-input defective
1218
1219
1220
1221
2082
GENERATOR CB OPENING FAILURE ground contacts welded (with circuit breaker/contactor combination) circuit breaker defective relay for switch-off order is defective wrong position of retun message switch PLC-output defective
GENERATOR CB CLOSING FAILURE relay for switch-on order defective line breakage to circuit breaker/contactor circuit breaker defective PLC output defective GENERATOR CB O-SIGNAL FAILURE wire breakage to PLC output monitoring PLC input defective PLC output defective
GENERATOR CB 1-SIGNAL FAILURE wire breakage to PLC output monitoring PLC input defective PLC output defective
PARAMETER(S) MISSING Some parameters required for the operation of the machine are missing. No, insufficient or wrong parameters transmitted.
check auxiliari contacts check/change relay check PLC input (performed by GE-JENBACHER)
change/check contactor change/check breaker change/check relay check breaker position signal check/change breaker position answerback relay check PLC output (performed by GE-JENBACHER)
check/change relay check cabels/connections check/change breaker check PLC output
check cables/connections check PLC input (performed by GE-JENBACHER) check PLC output (performed by GE-JENBACHER)
check cables/connections check PLC input (performed by GE-JENBACHER) check PLC output (performed by GE-JENBACHER)
Transmitting the most recent and complete parameter set (*.par file) using e.g. DIA.NE WIN.
2083
RPS (CONTROL SYSTEM) BATTERY FAILURE NiCd battery for CPU2005 is flat (Battery change NiCd battery LED lit) Lithium battery Lithium battery for the user memory is flat (Battery LED flashing)
2084
LEANOX ALGORITHM FAILURE two identical operating point for Lox
repeat Lox setup procedure
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 61 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
memory have been used 2086
CARBURATOR POSITION MEASURING SIGNAL FAILURE No power supply Switch on power supply Line breakage Check wiring and adjust Position measurement in gas mixer has position measurement been set incorrectly
2097
DEVIATION POWER SETPOINT TO POWER PRESENT VALUE MAXIMUM Signal from client
2101
JACKET WATER TEMPERATURE MEASURING SIGNAL FAILURE wire breakage Eleminate cause! short circuit defective PT100 defective PT100 measuring transformer defective safety device measuring transformer current supply Analogue input card faulty
2102
ENGINE OIL TEMPERATURE MEASURING SIGNAL FAILURE wire breakage Eleminate cause! short circuit defective PT100 defective PT100 measuring transformer defective safety device measuring transformer current supply Analogue input card faulty
2103
JACKET WATER PRESSURE MEASURING SIGNAL FAILURE leak in the oil lines or the oilpan clogged Eleminate cause! oil cooler, oil filter or oil line uncontrolled switching off (killing) of engine too low speed oil level below "min. oil level" defective oil pressure transmitter engine switch-off by closed current loop (defect monitoring) wrong adjustment of fringe value
2104
JACKET WATER PRESSURE MEASURING SIGNAL FAILURE leak in cooling water system Eleminate cause! defective pressure transmitter of cooling water leaking safety valve damaged membrane in pressure wrong adjustment of fringe value crack in inlet or outlet duct of cylinder head
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 62 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
2105
GENERATOR WINDING TEMPERATURE MEASURING SIGNAL FAILURE wire breakage Check wiring short circuit PT100 sensore defective Analogue input card faulty
2111
KNOCK SENSOR MEASURING SIGNAL FAILURE Wire breakage Eleminate cause! Faulty anti-knock control Anti-knock sensor failure Anti-knock failure (1048) activated
2116
DUMP RADIATOR FAILURE Signal from client
Eleminate cause!
2117
INTERCOOLER WATER PRESSURE LOW leak in intercooling water system Eleminate cause! defective pressure transmitter of intercooling water leaking safety valve damaged membrane in pressure wrong adjustment of fringe value crack in inlet or outlet duct of cylinder head
2118
MIXTURE COOLING WATER PUMP FAILURE motor overload Check water pump and electric Cable break to PLC motor. Motor protection (contactor) tripped Compare the engine emergency circuit breaker setting with the actual current collection of the motor.
2120
ENGINE ROOM VENTILATION FAILURE Cable to PLC defect Eleminate cause! Ventilationdefect Engine emergency circuit breaker set incorrectly
3003
MEASURING SIGNAL FAILURE Signal from client
3025
IGNITION TRIGGER PICKUP MISSING Faulty pickup signals.
Check the ignition sensors for pollution caused by small metal chips. Check the distance of the
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 63 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
sensors. You should avoid a mechanical contact between the triggering point and the sensor. Replace the faulty pickup. Ensure that the shielding and electrical connection are correct. 3026
3027
3028
3029
IGNITION RESET PICKUP MISSING Faulty pickup signals.
IGNITION CAM PICKUP MISSING Faulty pickup signals.
IGNITION SHUTOFF OVERSPEED Deactivation of the ignition because the overspeed has been exceeded.
IGNITION CPU FAILURE Faulty ignition.
Check the ignition sensors for pollution caused by small metal chips. Check the distance of the sensors. You should avoid a mechanical contact between the triggering point and the sensor. Replace the faulty pickup. Ensure that the shielding and electrical connection are correct.
Check the ignition sensors for pollution caused by small metal chips. Check the distance of the sensors. You should avoid a mechanical contact between the triggering point and the sensor. Replace the faulty pickup. Ensure that the shielding and electrical connection are correct.
wrong adjustment of or defective speed controller stuck or bent throttle flap speed relay defective or wrongly adjusted Minimum throttle opening set too wide eg. throttle valve bent
replace the ignition
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 64 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
3030
3031
3052
3216
3217
IGNITION PARAMETER FAILURE Faulty value of the parameter.
Faulty ignition/CAN coupling CAN connection between ignition and dia.ne interrupted. Ignition not in CAN mode.
WRONG TYPE OF IGNITION SYSTEM Incorrect ignition system
ENGINE OIL TEMPERATURE HIGH oil cooler clogged, dirty hot water feedback temp. is too high defective cooling water pump cooling water heat exchanger chocked dirty return remperature control incorrectly adjusted fresh water heat exchanger chocked, dirty table cooler too small ambient temp. to high (with table cooler) throughflow amount too low (primary/second.) limit value adjusted incorrectly MISFIRING FAILURE Wrong distance of electrodes Wrong A/F ration Failure in ignition system (sparkovers, break of insulators) Too late ignition point Misvire detection incorrectly adjusted or defective Ignition defective
Error in the dia.ne programme or faulty ignition.
Check whether the CAN bus is coorectly connected to both the ignition and the other CAN bus participants. If the CAN bus connection is correct, you should be able to reset the error within 1 to 2 minutes. Please contact the GEJENBACHER service department if the error cannot be reset. Check whether the ignition has been activated in the CAN mode. If not, have it activated by a GE-JENBACHER mechanic.
Have a GE JENBACHER mechanic update the ignition.
Eleminate cause!
Eleminate cause!
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 65 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
Ignition coil defective 3218
3219
3220
3221
OIL PRESSURE LOW leak in the oil lines or the oilpan clogged oil cooler, oil filter or oil line uncontrolled switching off (killing) of engine too low speed oil level below "min. oil level" defective oil pressure transmitter engine switch-off by closed current loop (defect monitoring) wrong adjustment of fringe value EXCITATION VOLTAGE LOW Voltage controller faulty Excitation voltage protection has been tripped JACKET WATER TEMPERATURE HIGH hot water feedback temp. too high cooler clogged, calcified, dirty return temperature control incorrectly adjusted emergency cooler clogged calcified, dirty fresh water missing cool. wat. pump defect defect. cool. water temp. transmission heat circulation pump defective heat circ. slide, fresh - water slide closed ambient temp. too high (with table cooler) throughflow amount too small (primary/secondary) follow-up heating when shut off water circulations not vented motor output too high glycool amount too high defective short-circuit thermostat wrong adjustment of fringe value water circulation not vented GAS PRESSURE LOW IN GAS TRAIN 1 gas valve closed wrong adjustment or defective gas pressure controller missing gas supply (line breakage) pressure fluctuations by other user defective pressure switch no gas present (sewer gas) wire breakage to PLC dirty filter in supply line
Eleminate cause!
change controller Close protection switch
Eleminate cause!
Eleminate cause!
TI 10000300
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 66 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
3223
INTAKE AIR TEMPERATURE HIGH Defective fuse Wire breakage on PLC Defective analog input card Customer signal not present
Eleminate cause!
3224
INTAKE AIR TEMPERATURE MEASURING SIGNAL FAILURE Exceeding the intake temperature for This warning should be which full engine output was agreed. An regarded as an indication, no output reduction caused by [too high] an further action is required. The intake temperature is possible. reasons for the output reduction are physical in nature. Cleaning the exhaustgas turbochargers will result in higher power reserves.
3310
IGNITION OUTPUT MONITORING CYLINDER Signal from client
3311
IN/OUT CHANNEL FAILURE Regulation fault MSF fault Converter adjustment!
3402
JACKET WATER PRESSURE LOW Leakage in emergency cooling water system Faulty emergency cooling water pressure sensor Leaking safety valve Faulty membrane in pressure compensation reservoir Incorrectly preset limiting value Wire breakage to PLC
3406
JACKET WATER PRESSURE HIGH Registration by customer
3411
FUEL MIXTURE TEMPERATURE HIGH defective mixture cooling pump mixture cooler clogged, calcified, dirty hot water feedback temp. too high fresh water exchanger is clogged, calcified, dirty defective PT100 water circulation of mixture cooling not vented cooling water amount of mixture too low
Eleminate cause!
Eleminate cause!
Eleminate cause!
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 67 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
wrong adjustment of fringe value 3497
Failure in the safety loop When the closed-current circuit is activated by an EMERGENCY STOP or by the heating circuit control system, not all closed-current circuit relays report the drop-out position to the control system.
Have all closed-current circuit relays checked by a GE Jenbacher service mechanic or by a mechanic from a specialized company authorised to do so by GE Jenbacher. The error message can only be reset when the EMERGENCY STOP switch is pressed. To that end, all closed-current circuit relays must report the drop-out position to the control system.
3506
POWER REDUCTION IN ISOLATED OPERATION Isolated operation below limiting value Eleminate cause! Monitoring period exceeded
3507
OIL PRESSURE HIGH Oil filter or oil line uncontrolled switching off (killing) of engine too low speed defective oil pressure transmitter engine switch-off by closed current loop (defect monitoring) wrong adjustment of fringe value
Eleminate cause!
3515
AIRCONDITIONING UNIT FAILURE IN MODULE INTERFACE CABINET
3516
JACKET WATER TEMPERATURE HIGH Wire breakage Short-circuit Rotating rectifier diode error Excitation protection switch activated Excitation current relais failure Cos phi / voltage regulator error
3517
Eleminate cause!
COMMUNICATION TO DIA.NE WIN SERVER FAILED Connection between DIA.NE XT and Check connection, plug in DIA.NE WIN server interrupted network cable, check DIA.NE WIN server has failed or is functionality of network defective components (cables, DIA.NE HUB failure WIN server network card,
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 68 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
Software technical problem at DIA.NE WIN server
HUB, DIA.NE XT network components), replace network components. Check and repair voltage supply, contact competence centre, replace DIA.NE WIN server hard disc, replace DIA.NE WIN server. Check and repair voltage supply, contact competence centre, replace HUB. Contact competence centre, replace DIA.NE WIN server hard disc
3518
DATA REGISTRATION IN DIA.NE WIN SERVER FAILED Communication to DIA.NE WIN server Check connection, plug in has failed network cable, check DIA.NE WIN server has failed or is functionality of network defective components (cables, DIA.NE HUB failure WIN server network card, Software technical problem at DIA.NE HUB, DIA.NE XT network WIN server components), replace network components. Check and repair voltage supply, contact competence centre, replace DIA.NE WIN server hard disc, replace DIA.NE WIN server. Check and repair voltage supply, contact competence centre, replace HUB. Contact competence centre, replace DIA.NE WIN server hard disc
11 12 13 20 30 40
START CONDITIONS MISSING OF MOTOR OF AGGREGATE OF THE UNIT MOTOR WON'T START MOTOR SAWING IN IDLE RUN (can't be synchronized) MOTOR DOES NOT REACH FULL LOAD (while maintaining the guaranteed pollutant emissions)
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 69 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
50 51 52 53 54 55 56 57 60 70 90 100 101 102 103 104 105 110 120 101 7 101 8 101 9 102 1 102 3 102 6 102 7 102 8 103 1 103 6 103 7 103 8
MOTOR OR SYSTEM MOTOR/GENERATOR RUNS IRREGULARLY OR UNSTABLE WITH LOAD MOTOR VIBRATES STRONGLY MOTOR SHAKES (quick load fluctuations or great current and voltage fluctuations with little change of motor output) ENGINE ROCKING GENERATOR MOTOR ESCALATES (great current and voltage fluctuations at only little change in motor output) MOTOR ARCHIEVES NOT STABLE CONDITION (output swings slowly up and down) ENGINE STOPS (individual cylinders) OR HAS AN EXHAUST GAS TEMPERATURE DEVIATING FROM THE CENTRAL VALUE PERIODIC FLUCTUATIONS IN PERFORMANCE MOTOR KNOCKING MISFIRING DETECTION RESPONDS, OR AT BR6 DEVIATION OF CYLINDER FLUE GAS TEMPERATURE TOO GREAT OIL CONSUMPTION TOO HIGH TURBOCHARGER DEFECT COMPACTOR THROWING OIL TURBINE THROWING OIL TURBOCHARGER EFFICIENCY NOT OKAY (flue gas turbocharger no longer archieves required load pressure) COMPACTOR OR TURBINE WHEEL TOUCHED THE HOUSING TURBOCHARGER VIBRATING WATER IN LUBRICATION OIL THE CONTRACTUALLY AGREED DEGREE OF EFFICIENCY IS NOT REACHED IN SPITE OF THE SALES TOLERANCE OIL PRESSURE LOW ENGINE OIL LEVEL LOW JACKET WATER PRESSURE LOW JACKET WATER TEMPERATURE HIGH START UP FAILURE SHUTDOWN FAILURE FAILURE GAS TRAIN 1 GAS PRESSURE LOW IN GAS TRAIN 1 EMERGENCY STOP/SAFETY LOOP GENERATOR OVERLOAD/SHORT CIRCUIT GENERATOR WINDING TEMPERATURE HIGH GENERATOR REVERSE POWER
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 70 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
103 9 104 0 104 1 104 2 104 3 104 8 105 0 105 1 105 2 105 3 105 4 105 6 105 7 105 9 106 1 106 4 107 8 108 0 108 1 108 3 110 5 110 9 111 0 111 1 111 2
SYNCHRONIZING FAILURE FUEL MIXTURE TEMPERATURE HIGH POWER SIGNAL MISSING POWER SIGNAL OVERLOAD ENGINE OIL TEMPERATURE HIGH KNOCKING FAILURE JACKET WATER PRESSURE HIGH ENGINE OIL LEVEL HIGH GAS PRE-ALARM GAS ALARM FIRE ALARM FAIL SAFE LOOP TRIPPED HIGH GAS PRESSURE IN GAS TRAIN 1 OIL FILTER DIFFERENTIAL PRESSURE HIGH IGNITION SYSTEM FAILURE OVERSPEED (RPS-CONTROL SYSTEM) BOOST PRESSURE MEASURING SIGNAL FAILURE LEANOX CONTROL ALLOWED DEVIATION EXCEEDED KNOCK SENSOR MEASURING SIGNAL FAILURE CONTROL CARBURATOR DEFECTIVE SPEED OF TEMPERATURE CHANGE MIXTURE TEMPERATURE MAXIMUM GENERATOR LOSS OF EXCITATION GENERATOR FREQUENCY TOO LOW GENERATOR FREQUENCY TOO HIGH NEUTRAL CURRENT MAXIMUM
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 71 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
111 3 111 4 112 0 112 6 112 7 112 9 113 4 113 5 114 0 114 3 114 4 114 5 114 8 116 7 116 8 117 7 118 5 118 6 118 9 119 2 119 3 119 4 119 5 119 6 121 6
GENERATOR POWER MEASURING SIGNAL FAILURE FUEL MIXTURE TEMPERATURE MEASURING SIGNAL FAILURE SPEED MEASURING SIGNAL FAILURE GENERATOR VOLTAGE LOW GENERATOR VOLTAGE HIGH FAILURE WITH AUXILIARIES GROUND FAILURE ROOM TEMPERATURE HIGH MODULE INTERFACE PANEL CIRCUIT BREAKER TRIPPED VOLTAGE NEGATIVE SEQUENCE CURRENT NEGATIVE SEQUENCE JACKET WATER TEMPERATURE LOW STARTER BATTERY VOLTAGE LOW HEATING WATER RETURN TEMPERATURE HIGH REQUEST FOR MAINTENANCE ENGINE ENCLOSURE PURGE CYCLE INCOMPLETE NO VENTILATION GENERATOR WINDING TEMPERATURE HIGH HEATING WATER RETURN TEMPERATURE MEASURING SIGNAL FAILURE RELEASE FROM SYNCHRONIZING MISSING ACTUATOR FAILURE LOAD BANK FAN IS NOT RUNNING LOAD BANK COMMON ALARM LOAD BANK CONTACTOR FAILURE LOAD BANK CB OVERLOAD/SHORT CIRCUIT BUS BAR VOLTAGE SENSOR FAILURE
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 72 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
121 7 121 8 121 9 122 0 122 1 208 2 208 3 208 4 208 6 209 7 210 1 210 2 210 3 210 4 210 5 211 1 211 6 211 7 211 8 212 0 300 3 302 5 302 6 302 7 302 8
GENERATOR CB STATUS SIGNAL FAILURE GENERATOR CB OPENING FAILURE GENERATOR CB CLOSING FAILURE GENERATOR CB O-SIGNAL FAILURE GENERATOR CB 1-SIGNAL FAILURE PARAMETER(S) MISSING RPS (CONTROL SYSTEM) BATTERY FAILURE LEANOX ALGORITHM FAILURE CARBURATOR POSITION MEASURING SIGNAL FAILURE DEVIATION POWER SETPOINT TO POWER PRESENT VALUE MAXIMUM JACKET WATER TEMPERATURE MEASURING SIGNAL FAILURE ENGINE OIL TEMPERATURE MEASURING SIGNAL FAILURE JACKET WATER PRESSURE MEASURING SIGNAL FAILURE JACKET WATER PRESSURE MEASURING SIGNAL FAILURE GENERATOR WINDING TEMPERATURE MEASURING SIGNAL FAILURE KNOCK SENSOR MEASURING SIGNAL FAILURE DUMP RADIATOR FAILURE INTERCOOLER WATER PRESSURE LOW MIXTURE COOLING WATER PUMP FAILURE ENGINE ROOM VENTILATION FAILURE MEASURING SIGNAL FAILURE IGNITION TRIGGER PICKUP MISSING IGNITION RESET PICKUP MISSING IGNITION CAM PICKUP MISSING IGNITION SHUTOFF OVERSPEED
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 73 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
302 9 303 0 303 1 305 2 321 6 321 7 321 8 321 9 322 0 322 1 322 3 322 4 331 0 331 1 340 2 340 6 341 1 349 7 350 6 350 7 351 5 351 6 351 7 351 8
IGNITION CPU FAILURE IGNITION PARAMETER FAILURE Faulty ignition/CAN coupling WRONG TYPE OF IGNITION SYSTEM ENGINE OIL TEMPERATURE HIGH MISFIRING FAILURE OIL PRESSURE LOW EXCITATION VOLTAGE LOW JACKET WATER TEMPERATURE HIGH GAS PRESSURE LOW IN GAS TRAIN 1 INTAKE AIR TEMPERATURE HIGH INTAKE AIR TEMPERATURE MEASURING SIGNAL FAILURE IGNITION OUTPUT MONITORING CYLINDER IN/OUT CHANNEL FAILURE JACKET WATER PRESSURE LOW JACKET WATER PRESSURE HIGH FUEL MIXTURE TEMPERATURE HIGH FAILURE IN THE SAFETY LOOP POWER REDUCTION IN ISOLATED OPERATION OIL PRESSURE HIGH AIRCONDITIONING UNIT FAILURE IN MODULE INTERFACE CABINET JACKET WATER TEMPERATURE HIGH COMMUNICATION TO DIA.NE WIN SERVER FAILED DATA REGISTRATION IN DIA.NE WIN SERVER FAILED
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 74 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
10
11
12
13
20
START CONDITIONS MISSING Measuring signal interrupted
Check the cabling, check scale of measurement range
OF MOTOR There is a defect as e.g. min. or max. oil level. The current loop (safety loop) is open OF AGGREGATE e.g. min. gas pressure closed current loop not released
OF THE UNIT no release through auxiliary operation
MOTOR WON'T START gas pressure too low or too high or gas pressure fluctuations
throttle flap won't open
remove indicated cause remove loose contact or wire breakage, or replace defective monit. device.
remove cause or complain at trader;remove loose contact or wire breakage, or replace defect monitoring device
check which auxiliary operation is not running, e.g. HW-circulation pump or throughflow indicator and machine room vent flap open, gas warning installation etc.
gas pressure prior to gas pressure controller line does not correspond to listings in techn. scheme. check whether supply of the Heinzmann actuator driver is okay (amber LED in actuator be lit) the Heinzmann actuator driver is defective (red LED in driver lit) due to low voltage (<12 VDC); short circuit at the lines to the actuator or overtemperature (> 90°C); the pickup or the wiring from the pickup to the actuator or DIANE is defective; check whether the throttle flap or the control systems are stuck or do not properly function.
TI 10000300
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 75 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
Ignition defective Ignition spark missing
electrode distance too smallat all spark plugs
start or idle run position of mixer or gas or air bypass flap incorrect
Unsuitable Impco or Jenbacher mixer
gas pressure in front of zero-pressure controller too high
wrong mixer adjustment membrane of gas pressure controller defective gas pressure controller stuck
check following points (partly with stroboscope).mains supply of DISN-unit (relay defective or bad contact) pickup distance pickup connection defect at relay for the G-line DISN-unit defective wrong.One or several magnets with too little residual magnetism or magnet broken out when changing plugs by sets to non - JENBACHER tested models, electrode distance is often too small, needs greater distance. unsuited gas pressure controller causing gas pressure fluctuations,must be replaced, correction of programmed values to experimental values, or to an inflammable mixture via pollutant measuring kit; check whether the servo motor, the gas or air bypass flap is okay, or check drive for the feedback pot. mixer cone on Impco does not correspond to the current gas type;check whether the air slot at Jenbacher-mixer corresponds to used type of gas. 1) higher values lead to excessive enriching of motor at start; 2) following adjustment of gas adm. pressure: adjust zero pressure controller so that after start of motor there is not speed breakdown (motor in this case too rich); if motor does not increase speed or increases too slow it is too lean; if motor is too rich, gradually turn zero pressure spindle out by 1 rot; if motors is too lean gradually turn spindle in by 1 rot. check programming of start opening check membrane for ruptures
see maintenance
TI 10000300
check for easy movement
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 76 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
gas magnet valve is defective no inflammable mixture forms
throttle flap opens and closes quickly during start procedure
30
check whether gas magnet valves open check whether the slot at the mixer cone at the Jenbachermixer corresponds to the %oposition programmed at the DIANE; check whether the mixer cone moves, whether in the drive the spring for the catching is missing or the servo motor is defective (wire breakage or potdrive) cwrong pick-up adjustment and quite often must be positioned closer to toothed wheel of starter according to adjustment instructions
MOTOR SAWING IN IDLE RUN (can't be synchronized) Heinzmann actuator defective (damaged) replace unsuited mixer mixer cones at Impco do not correspond to gas type or the air slot on Jenbacher-mixer, e.g., for depot gas, is too high, i.e., replace mixer cone, or reduce air slot (replace mixer or reduce shims under mixer head with new Jenbacher mixers) ignition defective (cylinder missing) replace Ignition coildefective replace as a result of a pulsating draught in the fit flap with a solenoid valve at exhaust flue while still warm the foot of the flue. speed controller not optimally adjusted Gas-pressure fluctuations use manometer or water Check the control rods (ball heads worn / columnto measure where the gas sluggish) pressure fluctuations appear, i.e., Mixture too lean / too rich upstream of mixer, upstream of Check speed controller setting gas pressure controller or downstream of customergas admission controller; if controller unsuited, replace it, or call supplier (of admission pressure controller). damaged joint cones of control line replace joint cones the control linkage adjusted too progressively in idle run
see maintenance
correct adjustment and make sure that the flap can fully close.
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 77 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
throttle flap slightly bent following detonation in intake line and does not fully close anymore (idle speed partially too high) sluggish control lines, or throttle flap
Heinzmann actuator driver not optimally adjusted idle run position at gas or air bypass valve not optimally adjusted or no optimal programming in DIANE 40
remove throttle flap and align, check for easy functioning
see maintenance
relube the joints, or disassemble the throttle flap bearing and replace; replace bearing bushing. check the 0% position of the actuator better adjust idle run position by trial or program differently
see maintenance
MOTOR DOES NOT REACH FULL LOAD (while maintaining the guaranteed pollutant emissions) Defective turbocharger check compactor shovel whether (missing power and power loss) entry edges are damaged by foreign bodies or whether formation of deposits in the compactor housing reduces output or whether runnertouches housing (clean compactor housing and runner). Check the turbine wheel for damage and free run. combustion air ratio not okay (motor correct leanox adjustment at running too lean), DIANE Part of the broken-off protective pipe in a open the end cover and remove manifold compensator is interrupting the parts or replace flow of the exhaust gases compensator.Inspect turbine wheel for damage. faulty insulation of exhaust collection line attach new insulation of thickness (insulation is completely or partiall worn and efficiency as original one down due to frequent dismantling or due to vibraiton mixture transporting parts after compactor seal off to throttle flap are not tight suction temperature too high(at >25°C) check whether ambient air reduction can be used acc. to ISO 3046, thermostat adjusted too high, the except for other contractual agreement room venting not properly planned or other vent stages do not turn on mixture temperature too high in spite of check mixture cooler, clean if TI 1000correct mixture cooling water admission necessary (mixture and water 0201, see temp. part) or glycol ratio too high maintenance (check).
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 78 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
output display wrong; ignition not properly adjusted, orcombustion misfires by e.g. too large electrode distance or failure of cylinders due to defectat ignition system (e.g. defect ignition coil) throttle flap not fully opened,actuator stands at 100% contaminated air filter and hence great pressure loss before mixer flue gas counter pressure too
leakage at the flange connections of flue gas line
check and correct error; make ignition check, measure ignition point, correct ignition adjustment and electrode distance, replace defective parts. correction of controller linkage adjustment actuator - throttle flap. measure pressure loss clean or replace the filter measure the counter pressure after high turboloader exit;clean oxikate and waste heat boiler if necessary. seal the line (replace sealings, tighten screws correctly) if necessaryrework flanges
see maintenance
see maintenance see maintenance
50
MOTOR OR SYSTEM MOTOR/GENERATOR RUNS IRREGULARLY OR UNSTABLE WITH LOAD
51
MOTOR VIBRATES STRONGLY failure of cylinder pendulum damper not okay
check ignition, valves, check compression check and replace if necessary
motor adjustment not okay (ignition point) straps of motor add-on pieces not okay
check and adjust check and remedy
see maintenance see maintenance
52
MOTOR SHAKES (quick load fluctuations or great current and voltage fluctuations with little change of motor output) faulty ignition check ignition system see maintenance combustion air ratio not okay (motor running check and adjust using the too lean), pollutant measuring device water, humidity in spark plug chamber (after dry spark plug chamber, clean washing motor) plugs and connector.
53
ENGINE ROCKING biological gas: gas pressure control line not okay (e.g. water in the gas pressure controllers, stuck gas control valves) misfires (motor adjusted too lean)
check gas pressure with water column upstream of mixer. check gas pressure controller, repair if necessary check and adjust using the pollutant measuring device
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 79 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
54
GENERATOR MOTOR ESCALATES (great current and voltage fluctuations at only little change in motor output) voltage controller at generator not okay adjust or repair description cos phi controller not okay check cables - generator bad connection in circuit (cables) check that connector is firmly located
55
MOTOR ARCHIEVES NOT STABLE CONDITION (output swings slowly up and down) Non-optimal setting of Leanox-control optimise the controller parameters parameters at constant power Check control rods (ball heads worn / setpoint sluggish) Check gas pressure Check power control Check gas-quality fluctuations (landfill gas, possibly sewage gas) harmonization of leanoxcontroller - output harmonize time behavior leanox control not functioning contr. to time behavior output control (decouple) control linkages not okay (too large dead check, if necessary repair or see center/to progressively adjusted, etc.) replace maintenance gas mixer not properly adjusted (e.g. lcheck, adjust characteristic not okay) gas pressure fluctuating check gas pressure controller, TI 1000check admission pressure 0300 quick fluctuation of the mixture temperature check temp. in hot water Schematic circulation diagram
56
ENGINE STOPS (individual cylinders) OR HAS AN EXHAUST GAS TEMPERATURE DEVIATING FROM THE CENTRAL VALUE Pre-combustion chamber gas pressure set Eleminate cause! too low Check spark plugs, ignition coils and ignition system defective ignition check see maintenance defective spark plug check voltage demand, replace if see necessary maintenance
57
PERIODIC FLUCTUATIONS IN PERFORMANCE continual switching on and off of the Conversion to thermostaticallyventilator(s) controlled, frequency-regulated ventilator
60
MOTOR KNOCKING output limitation faulty mixture cooling water temperature too high
Eleminate cause! Eleminate cause!
Schematic diagram
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 80 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
cooling water throughflow through the mixture cooler too low deposits in combustion chamber are butane and air mixed into the fuel gas? motor set too rich methane number of fuel gas too low combustion air ratio not okay ignition point not okay too early ignition point is set mixture temperature too high mixture cooler not okay 70
Eleminate cause! check, remove deposits if any Eleminate cause! Eleminate cause! take gas sample and have it analyzed check, correct adjustment if necessary determine ignition point and adjust toward "late" Eleminate cause! check, remedy fault if any Eleminate cause!
TI 10000300 Schematic diagram
MISFIRING DETECTION RESPONDS, OR AT BR6 DEVIATION OF CYLINDER FLUE GAS TEMPERATURE TOO GREAT spigot nut at the line to gas inlet valve is retighten the screwing or seal loose or the cutting ring is loose (flue gas temperature is higher at misfire) defective output measurement (motor check the output measurement output does not correspond to measured (compare counter measurement output) with output measurement) wrong adjustment of misfire detector Eleminate cause! verdigris on ignition coil exit (connector to clean carefully to make metal ignition cable) shiny motor runs too lean due to defect of mixer check motor adjustment (or of the air bypass flap)or due to leanox withmeasuring kit, if too lean, control remedycause crack at end of thread torque too high (plug replace spark plug and see tightened without torque wrench or with tightencorrectly with the right maintenance defective tool, or tightened too much) torque missing or bad contact at highvoltage output check contact screwing ground of ignition coils or at ground contact or contact at the ignition coil and ignition coil retighten the connection defect at cable loom between ignition box in case of loose contacts and ignition coils (scraping spots, ground retighten screws, in all other contact, overheating and cracking at the cases replace cable loom insulation, loose contacts at the connections interferences at the ignition check shield at the cables pearl formation on electrodes due to cannot be seen, metallic pearl overheating (e.g. knocking at times) may be caused by local melt-on between electrodes (remove with thickness gauge and check gap) electrode distance too small (possibly only correct electrode distance. see at site on one electrode) maintenance
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 81 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
boost pressure transmitter defect or due to drift transmits too low value (to leanox controller or DIANE) causing too lean operation of motor spark plug shows blue or brown discoloring at steel part and shows electrode motor misfires because it is set too lean or due to defective ignition quick generator output change entry of dirt (shavings) or grease into the prechamber annulus, i.e. slits are partially blocked too large ignition voltage demand due to large electrode distance
spring in brass part of plug connector without voltage, or broken, bad contact to brass cap of plug (traces of smoke) consumption spark plug shows abnormal spark appearance or flashover at bottom of plug on oscilloscope
misfiring due to too low ignition voltage offer (defect at the ignition coil) breakage of ignition cable interior at the soldering at the brass part of the plug connector or at the bend of the rubber bush ceramic body at the spark plug on top, or inner part of plug, is soiled with electr. conductive grease or similar and causes spark discharge in this area; plug shows in lower range of brass part a low-out, thus spark discharge to plug shell is created elastic seal ring inParker" valve of gas inlet valve destroyed
loose brass cap (traces of smoke on top of ceramic body)
check boost pressure controller, i.e., compare boost pressure signal with manometer, in case of deviation replace transmitter spark plug was not tightened sufficiently and overheated check using an exhaust emmissions analyser and correct if necessary Eleminate cause! Wash the pre-chamber with petrol and blow out. re-adjustment of the electrode gap with the special tool, or replacement of the sparking plugs replace spark plug connector
see maintenance
plug daubed at the end side with electrically conductive gliding agent (when sprayed with UltraTherm not covered or too much spray used which dropped on electrodes when hot) check the coil at motor standstill with ignition voltage tester frequent pulling of the plug connector at the cable, the cable ruptures are not visible, replace plug and cable clean plug and connector or replace.check for proper seat of dust cap on top of the valve hoodBlow-out is usually very small, onlyvery small grey point is visible on spark passage. replace plug suppresser if ball valve is too leaky, the pressure at theParker" valve is too high and the seal ring is destroyed tighten cap; if threading underneath of brass cap is loose, replace spark plug
TI 14000111
see maintenance
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 82 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
ball sticks to seat of gas inlet valve
90
OIL CONSUMPTION TOO HIGH carbonisation of the fire land through excessive idling or nonobservation of the limit values for used oil (TI 1000-0099B) leads to carbonisation of hard deposits on the piston top land. The upper rim pushes oil in front of it, more oil is burnt and the 1st ring receives too little oil and wears very repidly. (Ring carries to full height within 1000 op. hrs., darfk, cruty deposit in piston groove Piston runs crooked due to connecting rod parallelity tolerances being exceeded; similar effects to above with the same symptoms and can be clearly seen at the piston skirt on the pressure side, as well as at the fire land above the level of the bolts (one side clear, the other with hard oil carbonisation) (reduced gas access to 1st piston ring). turboloader throwing oil
100
TURBOCHARGER DEFECT
101
COMPACTOR THROWING OIL air filter resistance too great (dirty filter)
102
TURBINE THROWING OIL axial or radial play of runner
remove piston and clean replace first ring and break in motor
see point 0100
clean air filter, if required replace
see maintenance
measure, if exceeding admissible too great values repair or replace check and repair
oil sealing at turbine is defective 103
increase prechamber gas difference pressure; clean (wash valve, i.e. clean from lubricating oil which deposits in valve especially during start-up phase)
TURBOCHARGER EFFICIENCY NOT OKAY (flue gas turbocharger no longer archieves required load pressure) entrance shovels of compactorare defective check, search cause (foreign or damaged body?) and replace FGTL if necessary turbine shovels damaged check, search cause (foreign body?) and replace FGTL if necessary
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 83 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
104
COMPACTOR OR TURBINE WHEEL TOUCHED THE HOUSING defective axial sealing -axial play too great measure, if exceeding admissible too great values repair or replace
105
TURBOCHARGER VIBRATING turbine shovels (compactor shovels) defective (unbalanced)
110
WATER IN LUBRICATION OIL leaks at oil cooler craks or sinkholes at upper side of cylinder head between water storage and oil storage leaky O-rings at the cylinder liner leaky O-rings at the prechambers
replace wheel or turboloader
check and replace if necessary check, replace if necessary replace O-rings replace O-rings
120
THE CONTRACTUALLY AGREED DEGREE OF EFFICIENCY IS NOT REACHED IN SPITE OF THE SALES TOLERANCE on site the sum of border conditions is measure values exactly and strongly negative in order to reach an convert to standard condition according to ISO 3046 optimal efficiency (e.g. heating value of depot gas extremely low, induction temperature >25°C, air pressure <1000 mbar) flue gas counter pressure too high due to clean boiler dirty waste heat boiler induction vacuum before compactor too high clean air filter see due to dirty air filter maintenance
1017
OIL PRESSURE LOW leak in the oil lines or the oilpan clogged oil cooler, oil filter or oil line uncontrolled switching off (killing) of engine too low speed oil level below "min. oil level" defective oil pressure transmitter engine switch-off by closed current loop (defect monitoring) wrong adjustment of fringe value
1018
ENGINE OIL LEVEL LOW leakage in oil lines or oilpan defective solenoid valve "fill oil" (won't open) defective oil level sensor or evaluation device empty fresh oil tank slide at oil pump station is closed three-way cock in wrong position oil level measurerer not adjusted (with analog measuring)
Eleminate cause!
Eleminate cause!
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 84 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
"sag" in pressure-equalization line (venting) wrong adjustment of fringe value 1019
1021
1023
1026
JACKET WATER PRESSURE LOW leak in cooling water system defective pressure transmitter of cooling water leaking safety valve damaged membrane in pressure wrong adjustment of fringe value crack in inlet or outlet duct of cylinder head JACKET WATER TEMPERATURE HIGH hot water feedback temp. too high cooler clogged, calcified, dirty return temperature control incorrectly adjusted emergency cooler clogged calcified, dirty fresh water missing cool. wat. pump defect defect. cool. water temp. transmission heat circulation pump defective heat circ. slide, fresh - water slide closed ambient temp. too high (with table cooler) throughflow amount too small (primary/secondary) follow-up heating when shut off water circulations not vented motor output too high glycool amount too high defective short-circuit thermostat wrong adjustment of fringe value water circulation not vented START UP FAILURE 3 unsuccessful starting attempts no gas defective ignition wrong gas mixer valve start position wrong adjustment of gas pressure safety automation in motor terminal strip is off starter won't start SHUTDOWN FAILURE leaky or defective gas valves speed limit wrongly adjusted
Eleminate cause!
Eleminate cause!
Eleminate cause!
Eleminate cause!
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 85 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
1027
1028
1031
FAILURE GAS TRAIN 1 leaky gas valves gas valve closed defective gas tightness coantroller clogged gas filter too low gas pressure dirty filter in supply line to tightness controller condensate in the supply line to tightness controller vibrations of tightness controller device GAS PRESSURE LOW IN GAS TRAIN 1 gas valve closed wrong adjustment or defective gas pressure controller missing gas supply (line breakage) pressure fluctuations by other user defective pressure switch no gas present (sewer gas) wire breakage to PLC dirty filter in supply line EMERGENCY STOP/SAFETY LOOP emergency off button enabled wire breakage safety loop belt alarm --> when in emergency off chain gas alarm --> linked
Eleminate cause!
TI 10000300
Eleminate cause!
TI 10000300
Eleminate cause!
1036
GENERATOR OVERLOAD/SHORT CIRCUIT wrong adjustment or defective output Eleminate cause! controller overload in isolated operation short circuit wrong adjustment or defective output switch wrong adjustment or defective cos-phi controller wire breakage to PLC unbalanced load
1037
GENERATOR WINDING TEMPERATURE HIGH generator overload Eleminate cause! unbalanced load defective generator wrong cos-phi posistor or analogue input defective wire breakage to PLC ambient temperature too high wrong adjustment of fringe value
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 86 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
1038
1039
1040
1041
GENERATOR REVERSE POWER generator power switch does not open 10% power switch point wrong adjustment output reduced too quickly defective output measurement (only variant with reverse current relay) wrong adjustment rev. current relay or defective DIANE wrong adjustment or defective defective current transmitter wire breakage to PLC short circuit or wire breakage in 20 mA current loop of output measuring transducer ignition failure (signal pickup/DISN failure) SYNCHRONIZING FAILURE speed controller hunting throttle control rod loose synchronising unit faulty engine rough (ignition coil faulty) voltage balance circuit faulty engine idles too long gas pressure oscillating
Eleminate cause!
Eleminate cause!
FUEL MIXTURE TEMPERATURE HIGH defective mixture cooling pump mixture cooler clogged, calcified, dirty hot water feedback temp. too high fresh water exchanger is clogged, calcified, dirty defective PT100 water circulation of mixture cooling not vented cooling water amount of mixture too low wrong adjustment of fringe value POWER SIGNAL MISSING wire breakage or short circuit of output signal wire breakage or short circuit of current transducer output measuring transducer defect defective current transducer defective output controller power setpoint too small (<10% Pnenn)
Eleminate cause!
Eleminate cause!
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 87 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
1042
1043
1048
1050
1051
POWER SIGNAL OVERLOAD overload isolated operation output controller wrong adjusted or defective input of wrong measuring transducer or wrong output switch point defective output measuring transducer defective current transducer defective output controller ENGINE OIL TEMPERATURE HIGH oil cooler clogged, dirty hot water feedback temp. is too high defective cooling water pump cooling water heat exchanger chocked dirty return remperature control incorrectly adjusted fresh water heat exchanger chocked, dirty table cooler too small ambient temp. to high (with table cooler) throughflow amount too low (primary/second.) limit value adjusted incorrectly KNOCKING FAILURE pre ignition (deposits in combustion chamber) ignition timing point too early monitoring set too sensitively bad contact on the connector at the sensor(s) knocking sensor or knocking control defective Leanox controller programmed falsely (mixture too rich) JACKET WATER PRESSURE HIGH slide for filling cooling water is open leaking plug sleeve defective cooling water pressure transmitter defect. cool. water temp. measurement and overheated motor pressure expansion container too small filling pressure too high wrong adjustment of fringe value ENGINE OIL LEVEL HIGH defective solenoid valve "fill oil" defective oil level sensor or evaluator oil level measurerer is not adjusted (with analog measuring) wrong adjustment of fringe value
Eleminate cause!
Eleminate cause!
Eleminate cause!
Eleminate cause!
Eleminate cause!
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 88 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
1052
1053
1054
1056
1057
GAS PRE-ALARM leak in gas line system solvent, cleaning agent in container transmitter defective wrong adjustment or defective evaluator GAS ALARM leak in gas line system solvent, cleaning agent in container transmitter defective wrong adjustment or defective evaluator FIRE ALARM fire smoke solvent, cleaning agent in container transmitter defect evaluator defect FAIL SAFE LOOP TRIPPED 24V supply missing safety loop monitoring tripped emergency stop
Eleminate cause!
Eleminate cause!
Eleminate cause!
Eleminate cause!
HIGH GAS PRESSURE IN GAS TRAIN 1 Gas pressure controlle wrong adjustment or defective Pressure switch defect wire breakage to PLC
Eleminate cause!
1059
OIL FILTER DIFFERENTIAL PRESSURE HIGH clogging of oil filter due to dirt or water in Eleminate cause! lubrication oil (check oil on water, remedy cause. Determine type of other dirt of the filter by cutting open filter, possible early bearing damage!!) filter must be changed!
1061
IGNITION SYSTEM FAILURE faulty thermocouple Cable break to PLC Analogue input card faulty Setting parameters not allowed now
Incorrect parameter
Eleminate cause!
The parameters of the ignition can only be adjusted at engine standstill. Parameter outside the valid range
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 89 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
IC9xx Ignition failure caused by a malfunction in the ignition unit
IC9xx incorrect information from the pick-ups
IC9xx Misfiring
1064
OVERSPEED (RPS-CONTROL SYSTEM) speed overshoot afte mains failure speed limit wrongly adjusted
Read failure from the ignition (if possible). In case of program failure, first switch off the supply voltage and then switch it on again Check whether all ignition coils are connected. Replace the ignition Clean the magnetic pickups. Check the distance between pickup and trigger source (Be careful when reaching the highest position so as to prevent mechanical triggering!) Replace the faulty pickups. Check the high-voltage requirement. Check the shielding at the pickups and the IC900. Check the supply voltage using an oscilloscope. Check the mass circuit from ignition to engine mass.
Eleminate cause!
1078
BOOST PRESSURE MEASURING SIGNAL FAILURE 24V supply to boost pressure transducer secure interfaces faulty repair cables transducer cables faulty wrong transducer transducer range exceeded change transducer tranduce faulty analogue input card faulty
1080
LEANOX CONTROL ALLOWED DEVIATION EXCEEDED measuring signal fault - actual power see fault No. 1113 Measuring signal fault - mixture Temperature see fault No. 1114 Measuring signal fault - boost pressure see fault No. 1078 Gas mixer control defective see fault No. 1083
1081
KNOCK SENSOR MEASURING SIGNAL FAILURE 24 V supply failure for knocking Sensor check interface Knocking sensor cable fault Check cable Knocking sensor defekt Change sensor Move knocking sensor cable as Interferance on knocking sensor analogue input card faulty far as possible from ignition cable
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 90 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
1083
CONTROL CARBURATOR DEFECTIVE 24V supply failure for DM455 Gasmixer cable fault Gasmixer siezed 24V supply failure for gasmixer position feedback Faulty position-feedback plate Position feedback cable faulty
Check power supply in 24V interface and at the DM455 board Correct wiring Smooth running of gas mixer Exchange fuse and board
1105
SPEED OF TEMPERATURE CHANGE MIXTURE TEMPERATURE MAXIMUM Inform the GE-JENBACHER customer service department
1109
GENERATOR LOSS OF EXCITATION Voltage controller faulty Excitation voltage protection has been tripped Faulty rotating diodes defective cos-phi controller
1110
1111
1112
GENERATOR FREQUENCY TOO LOW Speed governor has been set incorrectly Speed governor is out of order Error in speed governor circuit GENERATOR FREQUENCY TOO HIGH Speed governor has been set incorrectly Speed governor is out of order Error in speed governor circuit NEUTRAL CURRENT MAXIMUM Out-of-balance load in isolated operation. Non-symmetrical mains supply causing compensating currents. Inadmissible 3rd (upper) harmonic wave (150 Hz). Earth fault
TI 10000300
change controller Close protection switch Check/replace the diodes
Eleminate cause!
Eleminate cause!
Eleminate cause!
1113
GENERATOR POWER MEASURING SIGNAL FAILURE Mult - transducer faulty Change multi-transducer Cables for multi-transducer faulty Check cables Analogue input card faulty Change analogue input card wrong adjustment of fringe value
1114
FUEL MIXTURE TEMPERATURE MEASURING SIGNAL FAILURE PT100 faulty change PT100 PT100 cables faulty Check cables Analogue input card faulty
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 91 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
1120
1126
1127
1129
1134
1135
1140
SPEED MEASURING SIGNAL FAILURE Speed pick-up wrongly adjusted 24V supply failure to pickup Pickup cable fault
Gap from 1 revolution of gear rim. Check interface Check cable
GENERATOR VOLTAGE LOW voltage controller fault Excitation voltage protection has been tripped Blown fuse
change controller Close protection switch Check fuse
GENERATOR VOLTAGE HIGH voltage controller fault voltage controller measurement circuit is disturbed
change controller Check measurement circuit
FAILURE WITH AUXILIARIES supply circuit breaker tripped by overload short circuit
check wiring check adjustment circuit breaker
GROUND FAILURE generator earth fault limiting value on evaluation instrument incorrectly adjusted trigger device defective defective current transformer in generator incorrect current transformer current transformer connections exchanged ROOM TEMPERATURE HIGH room vent failure wrong adjustment or defective thermostat exterior temperatur too high unfavorable placing of thermostat
Eleminate cause!
check the frequency controller
MODULE INTERFACE PANEL CIRCUIT BREAKER TRIPPED Circuit breaker or engine circuit breaker in Eleminate cause! module control cabinet has tripped Power circuit breaker or engine circuit breaker in module control cabinet is off Wire breakage Loose terminal on SPC input card Loose terminal on circuit breaker's or engine circuit breaker's auxiliary contacts
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 92 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
1143
1144
1145
1148
VOLTAGE NEGATIVE SEQUENCE fuse blown in measurement circuit Generator earth fault Generator winding fault Armature fault Mains voltage assymetry CURRENT NEGATIVE SEQUENCE current transformer circuit interuption Mains voltage assymetry Unbalanced load in Island operation Earth fault JACKET WATER TEMPERATURE LOW failure cooling water preheating return temperature control incorrectly adjusted defective cooling water temp. transmitter heat-up process not finished wrong adjustment of fringe value STARTER BATTERY VOLTAGE LOW loader defect (fuse) not enough battery acid in battery defective battery too strong loads frequent starts wire breakage to PLC
check fuses Fault checks
check CT circuits Check faults
Eleminate cause!
check battery charging
1167
HEATING WATER RETURN TEMPERATURE HIGH temperature controller warm water not Eleminate cause! correctly no heating demand (pump fault) wrong adjustment of fringe value
1168
REQUEST FOR MAINTENANCE Service counter has reached zero (operating hrs) from preselected limit
reset service counter after completion of service
1177
ENGINE ENCLOSURE PURGE CYCLE INCOMPLETE NO VENTILATION Signal from client Eleminate cause!
1185
GENERATOR WINDING TEMPERATURE HIGH generator overload Eleminate cause! unbalanced load defective generator wrong cos-phi
According to customer setting
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 93 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
posistor or analogue input defective wire breakage to PLC ambient temperature too high wrong adjustment of fringe value 1186
HEATING WATER RETURN TEMPERATURE MEASURING SIGNAL FAILURE wire breakage Eleminate cause! short circuit defective PT100 defective PT100 measuring transformer defective safety device measuring transformer current supply Analogue input card faulty
1189
RELEASE FROM SYNCHRONIZING MISSING a) The synchronisation control logic does not a) Check prerequisites for logical issue a release because the required release from synchronization conditions are not fulfilled (prerequisites relating to specific order according to control description) b) Eliminate cause !
1192
ACTUATOR FAILURE Disturbance / alarm at the Actuator for butterfly valve (internal equipment). Failure voltage supply 24 VDC, wire break
Eleminate cause!
1193
LOAD BANK FAN IS NOT RUNNING Signal from client
1194
LOAD BANK COMMON ALARM Signal from client
1195
LOAD BANK CONTACTOR FAILURE Signal from client
1196
LOAD BANK CB OVERLOAD/SHORT CIRCUIT wrong adjustment or defective output Eleminate cause! controller short circuit wrong adjustment or defective output switch wrong adjustment or defective cos-phi controller wire breakage to PLC unbalanced load
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 94 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
1216
BUS BAR VOLTAGE SENSOR FAILURE measuring voltage missing busbars voltage-detector defective wire breakage SPG-OK message to PLC PLC-input defective
Eleminate cause!
1217
GENERATOR CB STATUS SIGNAL FAILURE wire breakage check cables/connections switch return messages check auxiliary circuit breaker or contactor defective contacts/answerback of breaker or contactor (return message/auxiliary contacts) relay for switch return message defective check auxiliari contacts PLC-input defective check/change relay check PLC input (performed by GE-JENBACHER)
1218
GENERATOR CB OPENING FAILURE ground contacts welded (with circuit breaker/contactor combination) circuit breaker defective relay for switch-off order is defective wrong position of retun message switch PLC-output defective
1219
1220
1221
GENERATOR CB CLOSING FAILURE relay for switch-on order defective line breakage to circuit breaker/contactor circuit breaker defective PLC output defective GENERATOR CB O-SIGNAL FAILURE wire breakage to PLC output monitoring PLC input defective PLC output defective
GENERATOR CB 1-SIGNAL FAILURE wire breakage to PLC output monitoring PLC input defective PLC output defective
change/check contactor change/check breaker change/check relay check breaker position signal check/change breaker position answerback relay check PLC output (performed by GE-JENBACHER)
check/change relay check cabels/connections check/change breaker check PLC output
check cables/connections check PLC input (performed by GE-JENBACHER) check PLC output (performed by GE-JENBACHER)
check cables/connections check PLC input (performed by GE-JENBACHER) check PLC output (performed by GE-JENBACHER)
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 95 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
2082
PARAMETER(S) MISSING Some parameters required for the operation of the machine are missing. No, insufficient or wrong parameters transmitted.
Transmitting the most recent and complete parameter set (*.par file) using e.g. DIA.NE WIN.
2083
RPS (CONTROL SYSTEM) BATTERY FAILURE NiCd battery for CPU2005 is flat (Battery change NiCd battery LED lit) Lithium battery Lithium battery for the user memory is flat (Battery LED flashing)
2084
LEANOX ALGORITHM FAILURE two identical operating point for Lox memory have been used
repeat Lox setup procedure
2086
CARBURATOR POSITION MEASURING SIGNAL FAILURE No power supply Switch on power supply Line breakage Check wiring and adjust position Position measurement in gas mixer has been measurement set incorrectly
2097
DEVIATION POWER SETPOINT TO POWER PRESENT VALUE MAXIMUM Signal from client
2101
JACKET WATER TEMPERATURE MEASURING SIGNAL FAILURE wire breakage Eleminate cause! short circuit defective PT100 defective PT100 measuring transformer defective safety device measuring transformer current supply Analogue input card faulty
2102
ENGINE OIL TEMPERATURE MEASURING SIGNAL FAILURE wire breakage Eleminate cause! short circuit defective PT100 defective PT100 measuring transformer defective safety device measuring transformer current supply Analogue input card faulty
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 96 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
2103
JACKET WATER PRESSURE MEASURING SIGNAL FAILURE leak in the oil lines or the oilpan clogged oil Eleminate cause! cooler, oil filter or oil line uncontrolled switching off (killing) of engine too low speed oil level below "min. oil level" defective oil pressure transmitter engine switch-off by closed current loop (defect monitoring) wrong adjustment of fringe value
2104
JACKET WATER PRESSURE MEASURING SIGNAL FAILURE leak in cooling water system Eleminate cause! defective pressure transmitter of cooling water leaking safety valve damaged membrane in pressure wrong adjustment of fringe value crack in inlet or outlet duct of cylinder head
2105
GENERATOR WINDING TEMPERATURE MEASURING SIGNAL FAILURE wire breakage Check wiring short circuit PT100 sensore defective Analogue input card faulty
2111
KNOCK SENSOR MEASURING SIGNAL FAILURE Wire breakage Eleminate cause! Faulty anti-knock control Anti-knock sensor failure Anti-knock failure (1048) activated
2116
DUMP RADIATOR FAILURE Signal from client
2117
Eleminate cause!
INTERCOOLER WATER PRESSURE LOW leak in intercooling water system defective pressure transmitter of intercooling water leaking safety valve damaged membrane in pressure wrong adjustment of fringe value crack in inlet or outlet duct of cylinder head
Eleminate cause!
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 97 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
2118
MIXTURE COOLING WATER PUMP FAILURE motor overload Check water pump and electric Cable break to PLC motor. Motor protection (contactor) tripped Compare the engine emergency circuit breaker setting with the actual current collection of the motor.
2120
ENGINE ROOM VENTILATION FAILURE Cable to PLC defect Ventilationdefect Engine emergency circuit breaker set incorrectly
3003
MEASURING SIGNAL FAILURE Signal from client
3025
IGNITION TRIGGER PICKUP MISSING Faulty pickup signals.
3026
IGNITION RESET PICKUP MISSING Faulty pickup signals.
Eleminate cause!
Check the ignition sensors for pollution caused by small metal chips. Check the distance of the sensors. You should avoid a mechanical contact between the triggering point and the sensor. Replace the faulty pickup. Ensure that the shielding and electrical connection are correct.
Check the ignition sensors for pollution caused by small metal chips. Check the distance of the sensors. You should avoid a mechanical contact between the triggering point and the sensor. Replace the faulty pickup. Ensure that the shielding and electrical connection are correct.
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 98 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
3027
3028
3029
3030
3031
3052
IGNITION CAM PICKUP MISSING Faulty pickup signals.
IGNITION SHUTOFF OVERSPEED Deactivation of the ignition because the overspeed has been exceeded.
IGNITION CPU FAILURE Faulty ignition.
Check the ignition sensors for pollution caused by small metal chips. Check the distance of the sensors. You should avoid a mechanical contact between the triggering point and the sensor. Replace the faulty pickup. Ensure that the shielding and electrical connection are correct.
wrong adjustment of or defective speed controller stuck or bent throttle flap speed relay defective or wrongly adjusted Minimum throttle opening set too wide eg. throttle valve bent
replace the ignition
IGNITION PARAMETER FAILURE Faulty value of the parameter.
Faulty ignition/CAN coupling CAN connection between ignition and dia.ne interrupted. Ignition not in CAN mode.
WRONG TYPE OF IGNITION SYSTEM Incorrect ignition system
Error in the dia.ne programme or faulty ignition.
Check whether the CAN bus is coorectly connected to both the ignition and the other CAN bus participants. If the CAN bus connection is correct, you should be able to reset the error within 1 to 2 minutes. Please contact the GE-JENBACHER service department if the error cannot be reset. Check whether the ignition has been activated in the CAN mode. If not, have it activated by a GEJENBACHER mechanic.
Have a GE JENBACHER mechanic update the ignition.
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 99 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
3216
3217
3218
3219
ENGINE OIL TEMPERATURE HIGH oil cooler clogged, dirty hot water feedback temp. is too high defective cooling water pump cooling water heat exchanger chocked dirty return remperature control incorrectly adjusted fresh water heat exchanger chocked, dirty table cooler too small ambient temp. to high (with table cooler) throughflow amount too low (primary/second.) limit value adjusted incorrectly MISFIRING FAILURE Wrong distance of electrodes Wrong A/F ration Failure in ignition system (sparkovers, break of insulators) Too late ignition point Misvire detection incorrectly adjusted or defective Ignition defective Ignition coil defective OIL PRESSURE LOW leak in the oil lines or the oilpan clogged oil cooler, oil filter or oil line uncontrolled switching off (killing) of engine too low speed oil level below "min. oil level" defective oil pressure transmitter engine switch-off by closed current loop (defect monitoring) wrong adjustment of fringe value EXCITATION VOLTAGE LOW Voltage controller faulty Excitation voltage protection has been tripped
Eleminate cause!
Eleminate cause!
Eleminate cause!
change controller Close protection switch
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 100 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
3220
3221
3223
3224
JACKET WATER TEMPERATURE HIGH hot water feedback temp. too high cooler clogged, calcified, dirty return temperature control incorrectly adjusted emergency cooler clogged calcified, dirty fresh water missing cool. wat. pump defect defect. cool. water temp. transmission heat circulation pump defective heat circ. slide, fresh - water slide closed ambient temp. too high (with table cooler) throughflow amount too small (primary/secondary) follow-up heating when shut off water circulations not vented motor output too high glycool amount too high defective short-circuit thermostat wrong adjustment of fringe value water circulation not vented GAS PRESSURE LOW IN GAS TRAIN 1 gas valve closed wrong adjustment or defective gas pressure controller missing gas supply (line breakage) pressure fluctuations by other user defective pressure switch no gas present (sewer gas) wire breakage to PLC dirty filter in supply line INTAKE AIR TEMPERATURE HIGH Defective fuse Wire breakage on PLC Defective analog input card Customer signal not present
Eleminate cause!
Eleminate cause!
TI 10000300
Eleminate cause!
INTAKE AIR TEMPERATURE MEASURING SIGNAL FAILURE Exceeding the intake temperature for which This warning should be regarded full engine output was agreed. An output as an indication, no further action reduction caused by [too high] an intake is required. The reasons for the temperature is possible. output reduction are physical in nature. Cleaning the exhaust-gas turbochargers will result in higher power reserves.
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 101 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
3310
IGNITION OUTPUT MONITORING CYLINDER Signal from client
3311
IN/OUT CHANNEL FAILURE Regulation fault MSF fault Converter adjustment!
3402
Eleminate cause!
JACKET WATER PRESSURE LOW Leakage in emergency cooling water system Faulty emergency cooling water pressure sensor Leaking safety valve Faulty membrane in pressure compensation reservoir Incorrectly preset limiting value Wire breakage to PLC
3406
JACKET WATER PRESSURE HIGH Registration by customer
3411
FUEL MIXTURE TEMPERATURE HIGH defective mixture cooling pump mixture cooler clogged, calcified, dirty hot water feedback temp. too high fresh water exchanger is clogged, calcified, dirty defective PT100 water circulation of mixture cooling not vented cooling water amount of mixture too low wrong adjustment of fringe value
3497
Failure in the safety loop When the closed-current circuit is activated by an EMERGENCY STOP or by the heating circuit control system, not all closed-current circuit relays report the drop-out position to the control system.
Eleminate cause!
Eleminate cause!
Have all closed-current circuit relays checked by a GE Jenbacher service mechanic or by a mechanic from a specialized company authorised to do so by GE Jenbacher. The error message can only be reset when the EMERGENCY STOP switch is pressed. To that end, all closed-current circuit relays must report the drop-out position to the control system.
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 102 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
3506
POWER REDUCTION IN ISOLATED OPERATION Isolated operation below limiting value Eleminate cause! Monitoring period exceeded
3507
OIL PRESSURE HIGH Oil filter or oil line uncontrolled switching off (killing) of engine too low speed defective oil pressure transmitter engine switch-off by closed current loop (defect monitoring) wrong adjustment of fringe value
Eleminate cause!
3515
AIRCONDITIONING UNIT FAILURE IN MODULE INTERFACE CABINET
3516
JACKET WATER TEMPERATURE HIGH Wire breakage Short-circuit Rotating rectifier diode error Excitation protection switch activated Excitation current relais failure Cos phi / voltage regulator error
3517
Eleminate cause!
COMMUNICATION TO DIA.NE WIN SERVER FAILED Connection between DIA.NE XT and DIA.NE Check connection, plug in WIN server interrupted network cable, check functionality DIA.NE WIN server has failed or is defective of network components (cables, HUB failure DIA.NE WIN server network card, Software technical problem at DIA.NE WIN HUB, DIA.NE XT network server components), replace network components. Check and repair voltage supply, contact competence centre, replace DIA.NE WIN server hard disc, replace DIA.NE WIN server. Check and repair voltage supply, contact competence centre, replace HUB. Contact competence centre, replace DIA.NE WIN server hard disc
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 103 / 104
Jenbacher
4.1 Checklist for alarm messages
Documentation
-
3518
DATA REGISTRATION IN DIA.NE WIN SERVER FAILED Communication to DIA.NE WIN server has Check connection, plug in failed network cable, check functionality DIA.NE WIN server has failed or is defective of network components (cables, DIA.NE WIN server network card, HUB failure Software technical problem at DIA.NE WIN HUB, DIA.NE XT network server components), replace network components. Check and repair voltage supply, contact competence centre, replace DIA.NE WIN server hard disc, replace DIA.NE WIN server. Check and repair voltage supply, contact competence centre, replace HUB. Contact competence centre, replace DIA.NE WIN server hard disc
Keyword:
ENI Pakistan 1-10
Unit no.:
J F516/ J F662 - J F670
Module no.: ------
Module type :
JGS 312 GS-N.L.
Version:
C01
Engine no.: ------
Issued:
Doku./Pichler:
EN
4_1___B_DianeXT_EN.doc
Date: 2009-01 Page - No.: 104 / 104