Softstarters Type PSR Type PSS Type PST/PSTB

New

Torque control

The latest version of the PST(B) softstarter offers a new functionality called Torque control. With this function enabled the voltage of the motor is regulated so that the torque follows a predefined torque curve during start and stop. Torque control is especially useful in pump applications where a sudden stop can cause water hammering and pressure surges.

So

fts

Analog output New With the latest version of the PST(B) softstarter it

is possible to have analog output signals from the softstarter. These signals can then be used as input to a PLC or an analog meter.

Ne

Type PSR Softstarter New The latest addition to the ABB softstarter range is the

New

tar

ws

ter

s

compact PSR softstarter. This new softstarter has a compact, attractive design and is ideal for installation in places where space is limited and where there is a demand for easy installation.

Complete range

With the new PSR softstarter, ABB offers a complete range of softstarters from 3 to 1810 A. This complete range consists of the three models PSR, PSS and PST(B).

ABB Softstarters – the complete range Functionality

PST/PSTB

PSS

Advanced

Flexible

PSR

Compact

45

515

1810 Ampere

Softstarters

So

fts

ta r e P ters SS

Ty p

1

Contents

Page General.................................................................................................................................. 4 The complete range............................................................................................................... 5 Softstarters, type PSR Overview................................................................................................................................ 6 Description............................................................................................................................. 7 Ordering (incl. accessories)..................................................................................................... 8 Technical data, UL ratings...................................................................................................... 9 Softstarters, type PSS Overview.............................................................................................................................. 10 Application and Description.................................................................................................. 12 Ordering............................................................................................................................... 14 Accessories.......................................................................................................................... 18 Technical data...................................................................................................................... 19 UL ratings............................................................................................................................ 21 Softstarters, type PST Overview.............................................................................................................................. 22 Application and Description.................................................................................................. 24 Ordering............................................................................................................................... 26 Accessories.......................................................................................................................... 30 FBP Field Bus Plug............................................................................................................... 31 Technical data...................................................................................................................... 37 UL ratings............................................................................................................................ 41 Wall mounting instruction..................................................................................................... 42 Dimensions.......................................................................................................................... 43 Circuit diagrams................................................................................................................... 46 Certifications and approvals................................................................................................. 49 Leader in power and automation technologies, Division Automation Products, Low voltage products........................................................... 51

Some information about the catalogue: Ordering details: When placing an order please give either the ”Type” or the ”Order code”. Please note that for some of the products you need to fill in some additional code letters/code numbers to define the complete Type/Order code. Packing: All softstarters and most of the accessories are delivered in an individual packing. Some of the accessories are packed together in batches of ”n” pieces (see ordering ”Packing pieces”). For these items, please order the total amount corresponding to a multiple of the number in the packing. Example: If two in the packing, then please order minimum two, four, six etc. Note: Each ”Type” or ”Order code” always corresponds to only one piece. The products described in this catalogue are subject to change (design, . dimensions, technical data, etc.) without prior notice.

Low Voltage Products & Systems



ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU 132 019 C0202

rs

te ar

t

ts

1

f So

SS

P pe

Ty

Softstarters From the moment the first electrical motors appeared, engineers have been searching a way to avoid electrical and mechanical problems that occur using Direct-on-Line and Star-Delta starters. ABB has been producing softstarters since the beginning of the 1980’s. The valuable experience gained since the early 80’s has been incorporated into the design of today’s product ranges. With the latest series named PST, ABB has taken a significant step further in soft starting technology. Matching modern power electronics with smart circuitry and software, the new PST softstarter offers superior electronic control of the current and voltage during motor start-up, in addition to several new design features.

The solution to both mechanical and electrical problems

Motor voltage V

DoL

Star/Delta

Softstart

100 %

70 % 58 % 30 %

Adjustable ramp slope

Time

Motor current I DoL

AC motors, “the workhorse of the industry”, that are used to drive fans, crushers, agitators, pumps, conveyors etc., are . unnecessarily causing unwanted load peaks day in and day out in production plants all over the world. These violent starts cause damage in several ways. Among them are:

Star/Delta

Softstart

● Electrical



problems due to voltage and current transients arising from Direct-on-Line or Star-Delta starts. Such transients may overload the local supply network and cause unacceptable voltage variations that interfere with other electrical equipment connected to the network.

● Mechanical

problems that address the entire drive chain, from motor to driven equipment, to severe stress.

Operational problems, such as pressure surges in pipelines, damage to products on conveyor belts and uncomfortable escalator rides.

Motor speed

Torque



The financial consequences are considerable: every technical problem and every breakdown, costs money – in terms of repairs as well as lost production.

T

DoL

Star/Delta

Softstart

The easy solution to all of these problems is to install an ABB Softstarter type PSR, PSS or PST. With ABB Softstarters, it is possible to start and stop smoothly while keeping mechanical and electrical stresses to a minimum. Motor speed Graphs showing the basic differences between direct-on-line starting (DoL), star-delta starting and soft starting in terms of the motor voltage (V), motor current (I) and motor torque (T).

 1SXU 132 019 C0202

Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

So

fts

ta r e P ters SS

Ty p

1

ABB softstarters – The complete range ABB offers three different ranges of softstarters to cover every customer need for solutions for small to mediumsized motor applications, from 3 A to 1810 A. The overview table at the bottom of this page shows the main characteristics of the different types. For more specific technical details and ordering data, see the following pages.

Compact Range

Type PSR, covers motor currents from 3 to 45 A. It is the latest addition to the softstarter family and has an attractive, compact design. Further, the system concept includes MMS and the softstarters are available for remote control connection using the FieldBusPlug as an accessory. All sizes include a Run signal relay, while from sizes 25 A the PSR Softstarters are also provided with an output signal for TOR (Top Of Ramp), i.e. full voltage). With standard performance the PSR Softstarters handle ten starts per hour. When an auxiliary cooling fan is added, the starting capacity is increased to 20 starts per hour. • Current ratings 3.9 – 45 A (1.5 - 22 kW), at 400 V • Motor voltage 208 – 600 V • Supply voltage 24 V DC or 100-240 V AC • Easy to install and adjust • DIN rail or screw mounting • Integrated by-pass contacts With their compact design, the PSR Softstarters are ideal for installation in places where space is limited and where there is a demand for easy installation.

Flexible Range

Type PSS, covers motor currents from 18 to 300 A and offers a flexible solution with easy installation and setup. • Flexible: With two connection possibilities, either in line with the motor or inside the motor delta. It can also be equipped with current limit. • Easy to set up: With just three clearly labeled rotary switches on the front of the unit it is possible to adjust the PSS Softstarter for a wide range of applications. • Solid state electrical circuit: This ensures the highest reliability and reduces maintenance to a minimum, even in applications with frequent starts and stops.

Advanced Range

Type PST(B), covers motor currents from 30 to 1050 A and provides advanced functionality, including integrated protections, programmable signal relays, a flexible communication Low Voltage Products & Systems

system and an LCD display. Sizes PSTB370 to 1050 A include a by-pass contactor. • Advanced integrated protections: For the motor; inte- grated electronic overload relay, phase monitoring relays, high current and PTC protection. For the Softstarter; ad- vanced thyristor protection. • Flexible bus communication system: By using the ABB FieldBusPlug (FBP), you can decide at any time which bus system to select within the ABB FBP range. The interface between the PST Softstarter and the ABB FBP is always the same, independent of size and delivery date. • LCD display: With 13 languages, a menu system similar to your mobile phone, preprogrammed application settings and automatic status and event logging, it couldn’t be easier to set up and operate! • Programmable signal relays: gives you several possi bilities for signalling warnings, faults and other events. • Torque control: allows you to start and stop motors with a more linear acceleration than when using voltage ramp. PSR3 ...45 PSS18/30 ...300/515 PST30 ... PSTB1050B O – – – – – – – – – – – – – • • • – –

– – – – – – – – – – – – O • • – • – –

• • • • • • • • • • • O • • • • 1) • • •

• Standard O Optional – Not available

Field bus communication enabled Real time clock Programmable fault supervision functions Programmable warning functions PTC input for motor protection High current protection Phase imbalance /phase reversal protection Locked rotor protection Thyristor overtemperature protection Motor overload protection Four button keypad (external keypad available) External keypad Current limit control In Line and Inside Delta connection LED indications Built-in by-pass contactor (1) On PSTB) Ramp Start/Stop Torque control Analog output



ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU 132 019 C0202

rs

t

fts

1

So

te ar

pe Ty

Softstarters Type PSR Overview

SS

P

PSR3 ... PSR16



Normal start: In Line connected 400 V kW A In Line connected 480 V hp A







If using manual motor starters type 1 coordination will be achieved.





Softstarter, Type PSR3

PSR6

PSR9

PSR12

PSR16

PSR25

PSR30

1.5 3.9 2 3.4

3 6.8 3 6.1

4 9 5 9

5.5 12 7.5 11

7.5 16 10 15.2

11 25 15 24.2

15 30 20 28

MS116

MS116

MS325

MS450

400V, 40 °C Manual motor starter, Type MS116

MS116

10 A





Switch fuse, Type

Suitable switch fuse for the



OS32D





above gG fuses..

The line contactor is not required for the softstarter itself but often used to open if OL trips.

MS116

Fuse protection 400 V, 65 kA, 40 °C, gG Fuse

Using gG fuses type 1 coordination will be achieved.

PSR25 ... PSR30

16 A OS32D

25 A

32 A

32 A

50 A

63 A

OS32D

OS32D

OS32D

OS32D

OS32D

A9

A12

A16

A26

A30

TA25DU

TA25DU

TA25DU

TA25DU

TA25DU

Built-in

Built-in

Built-in

Built-in

Built-in

Line contactor, Type A9

A9





Thermal overload relay, Type

The overload relay is always



TA25DU





required to protect the motor.



 1SXU 132 019 C0202

TA25DU

By-pass contacs Built-in

Built-in

Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

So

Softstarters

fts

ta r e P ters SS

Ty p

Type PSR Overview and description

1

Description PSR - Compact range, covers motor currents from 3 to 45 A. It is the latest addition to the softstarter family and has an attractive, compact design. Further, the system concept includes MMS and the softstarters are available for remote control connection using the FieldBusPlug as an accessory. All sizes include a Run signal relay, while from sizes 25 A the PSR Softstarters are also provided with an output signal for TOR (Top Of Ramp), i.e. full voltage. With standard performance the PSR Softstarters handle ten starts per hour. When an auxiliary cooling fan is added, the starting capacity is increased to 20 starts per hour.

PSR37 ... PSR45 Softstarter, Type PSR37

PSR45

18.5 37

22 45

25 34

30 46.2

400V, 40 °C Manual motor starter, Type MS450

• Current ratings 3.9 – 45 A (1.5 - 22 kW), at 400 V • Motor voltage 208 – 600 V • Supply voltage 24 V DC or 100-240 V AC • Easy to install and adjust • DIN rail or screw mounting • Integrated by-pass contacts With their compact design, the PSR Softstarters are ideal for installation in places where space is limited and where there is a demand for easy installation.

Settings

MS450

Fuse protection 400 V, 65 kA, 40 °C, gG Fuse 100 A

125 A

Switch fuse, Type OS63D

1

OS125D

3

Line contactor, Type A40

2

A50

Thermal overload relay, Type TA42DU

TA75DU

By-pass contacts Built-in

Built-in

U

3 U ini

time Start

Stop

1

2

1 Ramp time START = 1 ... 10 sec 2 Ramp time STOP = 0 ... 20 sec 3 Initial voltage U =40 ... 70 % ini

(also set ”end voltage”)

Low Voltage Products & Systems



ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU 132 019 C0202

rs

t

fts

1

So

te ar

pe Ty

Softstarters

SS

Type PSR3 ... PSR45 Ordering details

P

Motor power



IEC

230 V Pe kW

500 V Pe kW

Max rated motor current, Ie A

400 V Pe kW

Type

Order code

Weight kg 1 piece



PSR3-600-70 PSR6-600-70 PSR9-600-70 PSR12-600-70 PSR16-600-70 PSR25-600-70 PSR30-600-70 PSR37-600-70 PSR45-600-70

1SFA 896 103 R7000 1SFA 896 104 R7000 1SFA 896 105 R7000 1SFA 896 106 R7000 1SFA 896 107 R7000 1SFA 896 108 R7000 1SFA 896 109 R7000 1SFA 896 110 R7000 1SFA 896 111 R7000

0.45 0.45 0.45 0.45 0.45 0.65 0.65 1.00 1.00



PSR3-600-81 PSR6-600-81 PSR9-600-81 PSR12-600-81 PSR16-600-81 PSR25-600-81 PSR30-600-81 PSR37-600-81 PSR45-600-81

1SFA 896 103 R8100 1SFA 896 104 R8100 1SFA 896 105 R8100 1SFA 896 106 R8100 1SFA 896 107 R8100 1SFA 896 108 R8100 1SFA 896 109 R8100 1SFA 896 110 R8100 1SFA 896 111 R8100

0.45 0.45 0.45 0.45 0.45 0.65 0.65 1.00 1.00

208 – 600 V AC Supply voltage, Us 100-240 V AC PSR3 ... PSR16

PSR25 ... PSR30

PSR37 ... PSR45

0.75 1.5 2.2 3 4 5.5 7.5 7.5 11

1.5 3 4 5.5 7.5 11 15 18.5 22

2.2 4 4 5.5 7.5 15 18.5 22 30

3.9 6.8 9 12 16 25 30 37 45

Supply voltage, Us 24 V DC 0.75 1.5 2.2 3 4 5.5 7.5 7.5 11

1.5 3 4 5.5 7.5 11 15 18.5 22

2.2 4 4 5.5 7.5 15 18.5 22 30

3.9 6.8 9 12 16 25 30 37 45

Accessories Type

Order code



Weight kg 1 piece

Fieldbus Plug Connection Accessory The same accessory for all sizes

PSR-FBPA

1SFA 896 312 R1001

0.06

Connection kit for PSR3-16 and MS116

PSR16-MS116

1SFA 896 211 R1001

0.03

Connection kit for PSR37-45 and MS450

PSR45-MS450

1SFA 896 213 R1001

0.03

PSR-FAN

1SFA 896 311 R1001

0.01

Description





PSR-FBPA

PSR16-MS116





PSR45-MS450

Fan All sizes can be equipped with auxiliary cooling fan for increased starting capacity. Suitable for all sizes.

PSR-FAN

ABB Field Bus Plug Suitable for all sizes.



 1SXU 132 019 C0202





FieldBusPlug Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

So

Softstarters

Type PSR3 ... PSR45 Technical data Rated insulation voltage, Ui

600 V

Rated operational voltage, Ue

208...600 V

Rated supply voltage, Us

100...240 V AC or 24 V DC

Power consumption, at 100-240 V AC at 24 V DC

PSR3

PSR6

PSR9

PSR12

PSR16

PSR25

PSR30

PSR37

PSR45

12 VA 5 W

12 VA 5 W

12 VA 5 W

12 VA 5 W

12 VA 5 W

12 VA 5 W

12 VA 5 W

10 VA 5 W

10 VA 5 W

Rated operational current, Ir

PSR3

PSR6

PSR9

PSR12

PSR16

PSR25

PSR30

PSR37

PSR45



3.9 A

6.8 A

9 A

12 A

16 A

25 A

30 A

37 A

45 A

Starting capacity at Ir

4 x Ir for 6 sec.

Number of starts per hour, with aux. fan

standard 10 (4 x Ie during 6 s) 20 (4 x Ie during 6 s)

Service factor

fts

ta r e P ters SS

Ty p

1

100 %

Ambient temperature

during operation during storage

Maximum altitude 2)

4000 m

1)

Degree of protection, main circuit control circuit Connectable cable area, main circuit

control circuit

-25 °C to +60 °C -40 °C to +70 °C PSR3

PSR6

PSR9

PSR12

PSR16

PSR25

PSR30

PSR37

PSR45

IP20 IP20

IP20 IP20

IP20 IP20

IP20 IP20

IP20 IP20

IP20 IP20

IP20 IP20

IP10 IP20

IP10 IP20

PSR3 - PSR16

PSR25 - PSR30

PSR37 - PSR45

1 x 0.75 - 2.5 mm2 2 x 0.75 - 2.5 mm2 PSR3 - PSR16 1 x 0.75 - 2.5 mm2 2 x 0.75 - 2.5 mm2

1 x 2.5 - 10 mm2 2 x 2.5 - 10 mm2 PSR25 - PSR45 1 x 0.75 - 2.5 mm2 2 x 0.75 - 1.5 mm2

1 x 6 - 35 mm2 2 x 6 - 16 mm2

PSR3 - PSR16

PSR25 - PSR45

Signal relays for Run signal Resistive load AC-15 (Contactor) for Top of Ramp signal Resistive load AC-15 (Contactor)

240 V, 2 A 240 V, 0.5 A

250 V, 5 A 250 V, 0.5 A

- -

250 V, 2 A 250 V, 0.5 A

LED for On/Ready for Run/Top Of Ramp

Green Green

Settings

Ramp time during start Ramp time during stop Initial- and End Voltage

1-10 sec. 0-20 sec. 40-70%

Above 40 °C up to max. 60 °C reduce the rated current with 0.8 % per °C.

1)

When used at high altitudes above 1000 meters up to 4000 meters you need to derate the rated current using the following formula.

2)

- 1000 ] [ % of Ie = 100 - x––––––– 150 x = actual altitude for the softstarter

UL ratings Softstarter Type

FLA A

Motor power P (hp) and full load current FLA (A) Ue Ue Ue 208 V 240 V 480 V hp hp hp

Ue 600V hp

Max. fuse

PSR3 PSR6 PSR9 PSR12 PSR16 PSR25 PSR30 PSR37 PSR45

3.4 6.1 9 11 15.2 24.2 28 34 46.2

0.5 1 2 3 3 7.5 7.5 10 15

2 5 7.5 10 10 20 25 30 40

40 A J-Type 40 A J-Type 40 A J-Type 40 A J-Type 40 A J-Type 60 A J-Type 70 A J-Type 100 A J-Type 100 A J-Type

Low Voltage Products & Systems

0.75 1.5 2 3 5 7.5 10 10 15

2 3 5 7.5 10 15 20 25 30

A, Type



ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU 132 019 C0202

rs

t

fts

1

So

te ar

pe Ty

Softstarters

SS

Type PSS Overview

P

PSS18/30 ... PSS44/76



PSS50 ... PSS72/124

Softstarter, Type

Normal start: In Line connected 400 V kW A Rated current Ie,

PSS18/30 7.5 18

PSS30/52

PSS37/64

PSS44/76

PSS50/85

PSS60/105

PSS72/124

15 30

18.5 37

22 44

25 50

30 60

37 72

In Line connected 480 V hp Rated current Ie, A

10 18

20 28

25 34

30 40

30 47

40 56

50 67

T2S160

T2S160

T2S160

T2S160

T2S160









400V, 40 °C MCCB (50 kA), Type

If using MCCB only, type 1



T2S160





coordination will be achieved.

Fuse protection (65 kA) Bussmann, Type

To achieve a type 2 coordination, semi-condcutor fuses must be used.

170M1364

Suitable switch fuse for



OS160RD0380





recommended semi-conductor fuses.

The line contactor is not required for the softstarter itself but often used to open if OL trips.

T2S160

170M1366

170M1368

170M1369

170M1369

170M1370

170M1371

OS160RD0380

OS160RD0380

OS160RD0380

OS160RD0380

OS160RD0380

A40

A50

A50

A63

A75

TA42DU

TA75DU

TA75DU

TA75DU

TA75DU

A26

A26

A30

A40

A50

PSCT-60 1 turn

PSCT-75 1 turn

PSCT-75 1 turn

PSCT-75 1 turn

Switch fuse, Type OS160RD0380

Line contactor, Type A26

A30





Thermal overload relay, Type

The overload relay is always required to protect the motor.



TA25DU





TA25DU

By-pass contactor, Type

The by-pass contactor can be used to reduce the power loss of the softstarter but also to increase the number of starts/h. All softstarters be operated without by-pass. can

A9

Must be used if current limit function is required.

PSCT-60 2 turns

A16

Current transformers, Type PSCT-40 1 turn

PSCT-50 1 turn

The table above is an overview of possible combinations of devices. Complete coordination tables are available at www.abb.com/lowvoltage.

 1SXU 132 019 C0202

Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

So

Softstarters Type PSS Overview

PSS85/147... PSS142/245

fts

ta r e P ters SS

Ty p

1

PSS175/300... PSS300/515

Softstarter, Type PSS85/147 45 85

PSS105/181 55 105

PSS142/245

PSS175/300

PSS250/430

PSS300/515

75 142

90 175

132 250

160 300

60 85

75 105

100 125

125 156

150 225

200 248

T3S250

T3S250

T4S320

T5S400

400V, 40 °C MCCB (50 kA), Type T2S160

T3S250

Fuse protection (65 kA) Bussmann, Type 170M1372

170M3019

170M3020

170M3021

170M5013

170M5015

OESA250R03D80

OESA250R03D80

OESA250R03D80

OESA400R03D80

OESA400R03D80

A145

A185

A50

A300

TA200DU

TA200DU

TA450DU

TA450DU

A95

A145

A145

A210

PSCT-200 1 turn

PSCT-250 1 turn

PSCT-400 1 turn

PSCT-75 1 turn

Switch fuse, Type OS160RD0380

Line contactor, Type A95

A110

Thermal overload relay, Type TA110DU

TA110DU

By-pass contactor, Type A50

A63

Current transformers, Type PSCT-125 1 turjfdn

PSCT-150 1 turn

How to select correct size By using the guide beside, you can quickly select a suitable softstarter for the most common applications. If a more precise selection is required, you can use Prosoft, a selection software . available at www.abb.com/lowvoltage.

Quick guide for selection Normal start Class 10

Heavy duty start Class 30

Ordering – See page 14 –15

Ordering – See page 16 –17

Typical applications

Typical applications

● Bow









thruster Compressor Elevator



! Low Voltage Products & Systems

Centrifugal pump Conveyor belt (short) Escalator

● ● ●

Centrifugal fan Crusher Mixer

● ● ●



Conveyor belt (long) Mill Stirrer

If more than 10 starts /h Select one size larger than the standard selection.



ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU 132 019 C0202

rs

1

te ar

t

fts

So

pe Ty

Softstarters

SS

Type PSS18/30 ... PSS300/515 Application and Description

P

Application The softstarter range PSS18/30 ... PSS300/515 is a very flexible solution suitable for most applications and for replacements of Star-Delta starters. Since the unit can be connected inside the motor delta (compare the connection for standard Star-Delta starters), the current through the softstarter is reduced by 42 %. It will then be possible, for example, to run a 100 A motor using a 58 A PSS Softstarter.

In-Line

100 A

Inside Delta The PSS Softstarter can be selected according to the rated motor power in normal duty applications like pumps, compressors, elevators, escalators, short conveyor belts and bow thrusters – see page 14-15.

58 A 100 A

100 A

For heavy duty applications like centrifugal fans, crushers, mixers, mills, stirrers and long conveyor belts, select a softstarter from page 16-17.

In-Line and Inside Delta connection of PSS18/30 … PSS300/515

Description • Wide main voltage range 208 - 690 V AC • Supply voltage range 110-120 V AC and 220-240 V AC • Current ratings 18 ... 300 A (In Line) and 30 ... 515 A (Inside Delta) • Same unit can be used for both In Line and Inside Delta connection • Start ramp, Stop ramp and Initial voltage included • Current limit function as option • Solid state electrical circuit • Designed for continuous operation without by-pass • 15 % overcurrent capability during continuous run (10 % for PSS300/515) • Accessories for connection and installation available: See the ordering pages

Built-in signal relays for fault and by-pass Transparent lid to protect the settings

LED indications:

Power supply on



Completed start ramp



General fault (motor side or unit)



External fault

Three rotating switches setting: -Start ramp (1–30 sec) -Stop ramp (0–30 sec) -Initial voltage (30–70 % of Ue) -Current limit 1.5 –4 x Ir (If used: Initial voltage fixed at 40 % of Ue) Dip-switch for In Line/ Inside Delta connection

10 1SXU 132 019 C0202

Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

So

Softstarters

fts

ta r e P ters SS

Ty p

1

(1SFC132186F0001)

Type PSS18/30 ... PSS300/515

Different sizes of PSS, from left PSS175/300-500L, PSS85/147-500L, PSS50/85-500L and in the front PSS18/30-500L.

Settings PSS18/30 … PSS300/515 U 1

2

3 U ini

3

time Start

Stop

1

2

1 Ramp time START = 1 ... 30 sec 2 Ramp time STOP = 0 ... 30 sec 3 Initial voltage U =40 ... 70 %, when current limit is ini

used fixed at 40 % (also set ”end voltage”)

Low Voltage Products & Systems

11

ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU 132 019 C0202

rs

1

t

fts

So

te ar

pe Ty

SS

P

Softstarters

Type PSS18/30 ... PSS300/515 Normal starts, class 10 – In-Line, Ordering details PSS18/30 ... PSS300/515 230 – 500 V

PSS18/30-500 ... 44/76-500

PSS50/85-500 ...72/124-500 PSS18/30-690 ... 72/124-690

PSS85/147-500 ...142/245-500 PSS85/147-690 ...142/245-690

Motor power





400 V Pe kW

500 V Pe kW

690 V Pe kW

Rated motor current, Ie A Type *)

7.5 15 18.5 22 25 30 37 45 55 75 90 132 160

11 18.5 22 25 30 37 45 55 75 90 110 160 200

- - - - - - - - - - - - -

18 30 37 44 50 60 72 85 105 142 175 250 300

400 – 690 V

Order code **)

PSS18/30-500n ■ PSS30/52-500n ■ PSS37/64-500n ■ PSS44/76-500n ■ PSS50/85-500n ■ PSS60/105-500n ■ PSS72/124-500n ■ PSS85/147-500n ■ PSS105/181-500n ■ PSS142/245-500n ■ PSS175/300-500n ■ PSS250/430-500n ■ PSS300/515-500n ■

Motor power





400 V Pe kW

500 V Pe kW

690 V Pe kW

Rated motor current, Ie A Type *)

7.5 15 18.5 22 25 30 37 45 55 75 90 132 160

11 18.5 22 25 30 37 45 55 75 90 110 160 200

15 25 30 37 45 55 59 75 90 132 160 220 257

18 30 37 44 50 60 72 85 105 142 175 250 300

1SFA 892 001 R▼00▼ 1SFA 892 002 R▼00▼ 1SFA 892 003 R▼00▼ 1SFA 892 004 R▼00▼ 1SFA 892 005 R▼00▼ 1SFA 892 006 R▼00▼ 1SFA 892 007 R▼00▼ 1SFA 892 008 R▼00▼ 1SFA 892 009 R▼00▼ 1SFA 892 010 R▼00▼ 1SFA 892 011 R▼00▼ 1SFA 892 013 R▼00▼ 1SFA 892 014 R▼00▼

Order code **)

PSS18/30-690■ ■ PSS30/52-690■ ■ PSS37/64-690■ ■ PSS44/76-690■ ■ PSS50/85-690 ■ ■ PSS60/105-690■ ■ PSS72/124-690■ ■ PSS85/147-690■ ■ PSS105/181-690■ ■ PSS142/245-690■ ■ PSS175/300-690■ ■ PSS250/430-690■ ■ PSS300/515-690■ ■

Supply voltage, Us

■ F = 110-120 V, 50/60 Hz



L = 220-240 V, 50/60 Hz



Fault signal relay

■ no code letter = NO

12 1SXU 132 019 C0202

C = NC

2.30 2.30 2.30 2.30 3.60 3.80 3.80 8.60 10.40 10.40 20.50 22.00 22.00

Weight kg

1SFA 893 001 R▼00▼ 1SFA 893 002 R▼00▼ 1SFA 893 003 R▼00▼ 1SFA 893 004 R▼00▼ 1SFA 893 005 R▼00▼ 1SFA 893 006 R▼00▼ 1SFA 893 007 R▼00▼ 1SFA 893 008 R▼00▼ 1SFA 893 009 R▼00▼ 1SFA 893 010 R▼00▼ 1SFA 893 011 R▼00▼ 1SFA 893 013 R▼00▼ 1SFA 893 014 R▼00▼

s Add code letter in Type for:

*)

PSS175/300-500 ... 300/515-500 PSS175/300-690 ... 300/515-690

Weight kg

2.30 2.30 2.30 2.30 3.60 3.80 3.80 8.60 10.40 10.40 20.50 22.00 22.00

s Add code number in Order code for:

**)

Supply voltage, Us

▼ 1 = 110-120 V, 50/60 Hz

2 = 220-240 V, 50/60 Hz



Fault signal relay

▼ 1 = NO



2 = NC

Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

So

Softstarters

Type PSS18/30 ... PSS300/515 Normal starts, class 10 – Inside Delta, Ordering details

fts

ta r e P ters SS

Ty p

1

PSS18/30 ... PSS300/515 230 – 500 V

PSS18/30-500 ... 44/76-500

PSS50/85-500 ...72/124-500 PSS18/30-690 ... 72/124-690

PSS85/147-500 ...142/245-500 PSS85/147-690 ...142/245-690

Motor power





400 V Pe kW

500 V Pe kW

690 V Pe kW

Rated motor current, Ie A Type *)

15 25 30 37 45 55 59 75 90 132 160 220 257

18.5 30 37 45 55 75 80 90 110 160 200 295 355

- - - - - - - - - - - - -

30 52 64 76 85 105 124 147 181 245 300 430 515

PSS18/30-500■ ■ PSS30/52-500■ ■ PSS37/64-500■ ■ PSS44/76-500■ ■ PSS50/85-500■ ■ PSS60/105-500■ ■ PSS72/124-500■ ■ PSS85/147-500■ ■ PSS105/181-500■ ■ PSS142/245-500■ ■ PSS175/300-500■ ■ PSS250/430-500■ ■ PSS300/515-500■ ■



400 – 690 V



Motor power





400 V Pe

690 V Pe

Rated motor current, Ie

500 V Pe

Order code **)

1SFA 892 001 R▼00▼ 1SFA 892 002 R▼00▼ 1SFA 892 003 R▼00▼ 1SFA 892 004 R▼00▼ 1SFA 892 005 R▼00▼ 1SFA 892 006 R▼00▼ 1SFA 892 007 R▼00▼ 1SFA 892 008 R▼00▼ 1SFA 892 009 R▼00▼ 1SFA 892 010 R▼00▼ 1SFA 892 011 R▼00▼ 1SFA 892 013 R▼00▼ 1SFA 892 014 R▼00▼

*)

kW

kW

kW

A

Type

Order code

18.5 30 37 45 55 75 80 90 110 160 200 295 355

25 45 55 59 75 90 110 132 160 220 257 400 500

30 52 64 76 85 105 124 147 181 245 300 430 515

PSS18/30-690■ ■ PSS30/52-690■ ■ PSS37/64-690■ ■ PSS44/76-690■ ■ PSS50/85-690■ ■ PSS60/105-690■ ■ PSS72/124-690■ ■ PSS85/147-690■ ■ PSS105/181-690■ ■ PSS142/245-690■ ■ PSS175/300-690■ ■ PSS250/430-690■ ■ PSS300/515-690■ ■

1SFA 893 001 R▼00▼ 1SFA 893 002 R▼00▼ 1SFA 893 003 R▼00▼ 1SFA 893 004 R▼00▼ 1SFA 893 005 R▼00▼ 1SFA 893 006 R▼00▼ 1SFA 893 007 R▼00▼ 1SFA 893 008 R▼00▼ 1SFA 893 009 R▼00▼ 1SFA 893 010 R▼00▼ 1SFA 893 011 R▼00▼ 1SFA 893 013 R▼00▼ 1SFA 893 014 R▼00▼

s Add code letter in Type for:

Supply voltage, Us

■ F = 110-120 V, 50/60 Hz



L = 220-240 V, 50/60 Hz



Fault signal relay

■ no code letter = NO

Low Voltage Products & Systems

C = NC

2.30 2.30 2.30 2.30 3.60 3.80 3.80 8.60 10.40 10.40 20.50 22.00 22.00

Weight **)

15 25 30 37 45 55 59 75 90 132 160 220 257

*)

PSS175/300-500 ... 300/515-500 PSS175/300-690 ... 300/515-690

Weight kg

kg



2.30 2.30 2.30 2.30 3.60 3.80 3.80 8.60 10.40 10.40 20.50 22.00 22.00

s Add code number in Order code for:

**)

Supply voltage, Us

▼ 1 = 110-120 V, 50/60 Hz

2 = 220-240 V, 50/60 Hz



Fault signal relay

▼ 1 = NO



2 = NC

13

ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU 132 019 C0202

rs

1

t

fts

So

te ar

pe Ty

SS

P

Softstarters

Type PSS30/52 ... PSS300/515 Heavy duty starts, class 30 – In-Line, Ordering details PSS30/52 ... PSS300/515 230 – 500 V

PSS30/52-500 ... 44/76-500

PSS50/85-500 ...72/124-500 PSS18/30-690 ... 72/124-690

PSS85/147-500 ...142/245-500 PSS85/147-690 ...142/245-690

Heavy duty

Motor power





400 V Pe kW

500 V Pe kW

690 V Pe kW

Rated motor current, Ie A Type *)

7.5 15 18.5 22 25 30 37 45 55 75 90 132

11 18.5 22 25 30 37 45 55 75 90 110 160

- - - - - - - - - - - -

18 30 37 44 50 60 72 85 105 142 175 250

400 – 690 V

Order code **)

PSS30/52-500■ ■ PSS37/64-500■ ■ PSS44/76-500■ ■ PSS50/85-500■ ■ PSS60/105-500■ ■ PSS72/124-500■ ■ PSS85/147-500■ ■ PSS105/181-500■ ■ PSS142/245-500■ ■ PSS175/300-500■ ■ PSS250/430-500■ ■ PSS300/515-500■ ■

Motor power





400 V Pe kW

500 V Pe kW

690 V Pe kW

Rated motor current, Ie A Type *)

7.5 15 18.5 22 25 30 37 45 55 75 90 132

11 18.5 22 25 30 37 45 55 75 90 110 160

15 25 30 37 45 55 59 75 90 132 160 220

18 30 37 44 50 60 72 85 105 142 175 250

1SFA 892 002 R▼00▼ 1SFA 892 003 R▼00▼ 1SFA 892 004 R▼00▼ 1SFA 892 005 R▼00▼ 1SFA 892 006 R▼00▼ 1SFA 892 007 R▼00▼ 1SFA 892 008 R▼00▼ 1SFA 892 009 R▼00▼ 1SFA 892 010 R▼00▼ 1SFA 892 011 R▼00▼ 1SFA 892 013 R▼00▼ 1SFA 892 014 R▼00▼

Add code letter in Type for: Supply voltage, Us ■ F = 110-120 V, 50/60 Hz L = 220-240 V, 50/60 Hz

14 1SXU 132 019 C0202



Fault signal relay

■ no code letter = NO

C = NC

Weight kg

1SFA 893 002 R▼00▼ 1SFA 893 003 R▼00▼ 1SFA 893 004 R▼00▼ 1SFA 893 005 R▼00▼ 1SFA 893 006 R▼00▼ 1SFA 893 007 R▼00▼ 1SFA 893 008 R▼00▼ 1SFA 893 009 R▼00▼ 1SFA 893 010 R▼00▼ 1SFA 893 011 R▼00▼ 1SFA 893 013 R▼00▼ 1SFA 893 014 R▼00▼

s

PSS175/300-500 ... 300/515-500 PSS175/300-690 ... 300/515-690

2.30 2.30 2.30 3.60 3.80 3.80 8.60 10.40 10.40 20.50 22.00 22.00

Order code **)

PSS30/52-690■ ■ PSS37/64-690■ ■ PSS44/76-690■ ■ PSS50/85-690■ ■ PSS60/105-690■ ■ PSS72/124-690■ ■ PSS85/147-690■ ■ PSS105/181-690■ ■ PSS142/245-690■ ■ PSS175/300-690■ ■ PSS250/430-690■ ■ PSS300/515-690■ ■ *)

Weight kg

2.30 2.30 2.30 3.60 3.80 3.80 8.60 10.40 10.40 20.50 22.00 22.00

s Add code number in Order code for: Supply voltage, Us ▼ 1 = 110-120 V, 50/60 Hz 2 = 220-240 V, 50/60 Hz **)



Fault signal relay

▼ 1 = NO



2 = NC

Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

So

Softstarters

Ty p

fts

ta

r Type PSS30/52 ... PSS300/515 e P ters Heavy duty starts, class 30 – Inside Delta, Ordering details SS

1

PSS30/52 ... PSS300/515 230 – 500 V

PSS30/52-500 ... 44/76-500

PSS50/85-500 ...72/124-500 PSS18/30-690 ... 72/124-690

PSS85/147-500 ...142/245-500 PSS85/147-690 ...142/245-690

Heavy duty

Motor power





400 V Pe kW

500 V Pe kW

690 V Pe kW

Rated motor current, Ie A Type *)

15 25 30 37 45 55 59 75 90 132 160 220

18.5 30 37 45 55 75 80 90 110 160 200 295

- - - - - - - - - - - -

30 52 64 76 85 105 124 147 181 245 300 430

PSS30/52-500■ ■ PSS37/64-500■ ■ PSS44/76-500■ ■ PSS50/85-500■ ■ PSS60/105-500■ ■ PSS72/124-500■ ■ PSS85/147-500■ ■ PSS105/181-500■ ■ PSS142/245-500■ ■ PSS175/300-500■ ■ PSS250/430-500■ ■ PSS300/515-500■ ■



400 – 690 V



Motor power





400 V Pe

690 V Pe

Rated motor current, Ie

500 V Pe

Order code **)

1SFA 892 002 R▼00▼ 1SFA 892 003 R▼00▼ 1SFA 892 004 R▼00▼ 1SFA 892 005 R▼00▼ 1SFA 892 006 R▼00▼ 1SFA 892 007 R▼00▼ 1SFA 892 008 R▼00▼ 1SFA 892 009 R▼00▼ 1SFA 892 010 R▼00▼ 1SFA 892 011 R▼00▼ 1SFA 892 013 R▼00▼ 1SFA 892 014 R▼00▼

*)

kW

kW

kW

A

Type

Order code

18.5 30 37 45 55 75 80 90 110 160 200 295

25 45 55 59 75 90 110 132 160 220 257 400

30 52 64 76 85 105 124 147 181 245 300 430

PSS30/52-690■ ■ PSS37/64-690■ ■ PSS44/76-690■ ■ PSS50/85-690■ ■ PSS60/105-690■ ■ PSS72/124-690■ ■ PSS85/147-690■ ■ PSS105/181-690■ ■ PSS142/245-690■ ■ PSS175/300-690■ ■ PSS250/430-690■ ■ PSS300/515-690■ ■

1SFA 893 002 R▼00▼ 1SFA 893 003 R▼00▼ 1SFA 893 004 R▼00▼ 1SFA 893 005 R▼00▼ 1SFA 893 006 R▼00▼ 1SFA 893 007 R▼00▼ 1SFA 893 008 R▼00▼ 1SFA 893 009 R▼00▼ 1SFA 893 010 R▼00▼ 1SFA 893 011 R▼00▼ 1SFA 893 013 R▼00▼ 1SFA 893 014 R▼00▼

s Add code letter in Type for: Supply voltage, Us ■ F = 110-120 V, 50/60 Hz L = 220-240 V, 50/60 Hz

Low Voltage Products & Systems

Fault signal relay

■ no code letter = NO C = NC

2.30 2.30 2.30 3.60 3.80 3.80 8.60 10.40 10.40 20.50 22.00 22.00

Weight **)

15 25 30 37 45 55 59 75 90 132 160 220

*)

PSS175/300-500 ... 300/515-500 PSS175/300-690 ... 300/515-690

Weight kg

kg



2.30 2.30 2.30 3.60 3.80 3.80 8.60 10.40 10.40 20.50 22.00 22.00

s Add code number in Order code for: Supply voltage, Us ▼ 1 = 110-120 V, 50/60 Hz 2 = 220-240 V, 50/60 Hz **)



Fault signal relay

▼ 1 = NO



2 = NC

15

ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU 132 019 C0202

rs

t

fts

1

So

te ar

pe Ty

Softstarters

SS

Accessories for type PSS18/30 ... PSS300/515 Ordering details

P

Current transformer for current limit function To be connected to terminals 11 and 12 on the softstarter. The setting range (1.5 – 4) corresponds to a multiple of the transformer ratio.. Technical data below shows transformer ratio and number of turns for the primary winding. You can also use your own current transformer with corresponding transformer ratio and with minimum 1 VA.



PSCT..

For softstarter Transformer ratio, type Number of turns

Type

Order code

Weight kg Packing piece 1 piece

PSS18/30 PSS30/52 PSS37/64 PSS44/76 PSS50/85 PSS60/105 PSS72/124 PSS85/147 PSS105/181 PSS142/245 PSS175/300 PSS250/430 PSS300/515

PSCT-60 PSCT-40 PSCT-50 PSCT-60 PSCT-75 PSCT-75 PSCT-100 PSCT-125 PSCT-150 PSCT-200 PSCT-250 PSCT-400 PSCT-400

1SFA 899 001 R1060 1SFA 899 001 R1040 1SFA 899 001 R1050 1SFA 899 001 R1060 1SFA 899 001 R1075 1SFA 899 001 R1075 1SFA 899 001 R1100 1SFA 899 001 R1125 1SFA 899 001 R1150 1SFA 899 001 R1200 1SFA 899 001 R1250 1SFA 899 001 R1400 1SFA 899 001 R1400

1 1 1 1 1 1 1 1 1 1 1 1 1

Type

Order code

Packing piece

60/1 – 2 turns 40/1 – 1 turn 50/1 – 1 turn 60/1 – 1 turn 75/1 – 1 turn 75/1 – 1 turn 100/1 – 1 turn 125/1 – 1 turn 150/1 – 1 turn 200/1 – 1 turn 250/1 – 1 turn 400/1 – 1 turn 400/1 – 1 turn

0.30 0.30 0.30 0.30 0.30 0.30 0.25 0.25 0.25 0.25 0.25 0.25 0.25

Cable connectors for Cu cables For softstarter type

Wire range mm2

Tightening torque max. Nm

PSS85/147…142/245 6-185 16 PSS85/147…142/245 2x(50-120) 16 25 PSS175/300…300/515 16-240



– 1SDA 023 354 R0001 LZ185-2C/120 1SFN 074 709 R1000 – 1SDA 023 368 R0001

3 3 3

Weight kg 1 piece

0.20 0.30 0.40

Cable connectors for Al and Cu cables

For softstarter type

LZ...

Wire range mm2

PSS85/147…142/245 35-95 PSS85/147…142/245 25-150 PSS175/300…300/515 120-240

Tightening torque max. Nm

Type

Order code

Weight Packing kg piece 1 piece

13.5 31 43

– – –

1SDA 023 356 R0001 1SDA 023 357 R0001 1SDA 023 370 R0001

3 3 3

Type

Order code

Weight Packing kg piece 1 piece

PSLW-44

1SFA 899 002 R1044

1

0.10

0.10 0.10 0.10

Terminal enlargements PSLW-44

For softstarter type

Wire range mm2

PSS18/30-500 ...44/76-500 1x6...35 2x6...16

LW...

PSS50/85-500…72/124-500 PSS18/30-690 ... 72/124-690 1x10...50 2x10...25

PSLW-72

1SFA 899 002 R1072

1

0.15

PSS85/147…142/245

LW185

1SFN 074 707 R1000

1

0.25

PSS175/300…300/515

LW300

1SFN 075 107 R1000

1

0.40

Type

Order code

Weight Packing kg piece 1 piece

LE185 LE300

1SFN 074 716 R1000 1SFN 075 116 R1000

2 2

Suitable for

Type

Order code

Weight Packing kg piece 1 piece

Cable connectors Compression lugs Cable connectors Compression lugs

LT185-AC LT185-AL LT300-AC LT300-AL

1SFN 124 701 R1000 1SFN 124 703 R1000 1SFN 125 101 R1000 1SFN 125 103 R1000

2 2 2 2

Terminal nut washer For softstarter type





PSS85/147…142/245 PSS175/300…300/515

LE185

0.20 0.30

Terminal shrouds For softstarter type



LT ... -AC

16 1SXU 132 019 C0202

LT ... -AL



PSS85/147…142/245 PSS85/147…142/245 PSS175/300…300/515 PSS175/300…300/515

0.10 0.10 0.20 0.20

Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

So

Softstarters

Type PSS18/30 ... PSS300/515 Technical data



1

PSS18/30 ... PSS300/515

Rated insulation voltage, Ui

690 V

Rated operational voltage, Ue

208 – 690 V

Starting capacity 4 x Ie for 10 sec at max. rated current, Ie Number of starts per hour

30 3)

Overload capability Overload class

10

Service factor

115 %

Ambient temperature. During operation During storage

-25 to +60 °C 1) -40 to +70 °C

Maximum altitud 4)

4000 m

Degree of protection Main circuit Supply and control circuit

PSS18/30-500 ... 44/76-500

PSS18/30 ... 250/430







.

PSS300/515

110 %

.

PSS50/85-500 ...72/124-500

IP 20

IP 10 IP 10 PSS18/30-690 ... 72/124-690

PSS85/147-690 ...300/515-690.

IP 00

PSS18/30…PSS300/515

IP 20

Settings. Ramp time during start Ramp time during stop Initial voltage during start

1 – 30 sec 0 – 30 sec 30 – 70 %



1.5 ... 4 2)

Current limit function x CT-ratio

fts

ta r e P ters SS

Ty p

. .

Switch for. Inside Delta connection ON/OFF

Yes

Signal relays. By-pass signal Fault signal Rated operational voltage, Ue Rated thermal current, Ith Rated operational current, Ie at AC-15 (Ue=250 V)

Yes . . Yes (NO or NC) 250V 5A . . 1.5A

Signal indication LED. Ready to start/stand by ON Ramping up/down Completed start ramp T.O.R General fault External fault

Green. – Green. Red. Red

.

.

Above 40 °C, up to max 60 °C, reduce the rated current with 0.8 % per °C. Only if current transformer is connected (accessory). 3) Valid for 50 % on time and 50 % off time. 3.5 x Ie for 7 sec., if other data is required, contact your sales office. 4) When used at high altitudes above 1000 meters up to 4000 meters you need to derate rated current using the following formula. 1) 2)

x - 1000 . [ % of Ie = 100 - ––––––– ] 150 x = actual altitude for the softstarter

Low Voltage Products & Systems

17

ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU 132 019 C0202

rs

t

fts

1

So

te ar

pe Ty

SS

P

Softstarters

Type PSS18/30 ... PSS300/515 Technical data

Cross section of connection cables











Type of softstarter PSS 18/30-500 … 44/76-500

PSS50/85-500 … 72/124-500, 18/30-690 … 72/124-690

PSS85/147-500 … 142/245-500, 85/147-690 … 142/245-690

PSS175/300 … 300/515-500, 175/300 … 300/515-690

2.5 – 16 2.5 – 16

6 – 50 6 – 25

See accessories See accessories

See accessories. See accessories

2.6

4.5

See accessories

See accessories

Main circuit. Connection clamp

.

Solid/Stranded Solid/Stranded



Tightening torque (recommended) Nm

1 x mm2 2 x mm2

20

17.5

Connection bar

5

5

Width and thickness

mm







Hole diameter

mm







Tightening torque (recommended) Nm





9

1 x mm2 2 x mm2

2.5 –

2.5 –

2.5 –

2.5. –

Tightening torque (recommended) Nm

0.5

0.5

0.5

0.5

Supply and control circuit. Connection clamp. Solid/Stranded Solid/Stranded

E1858D

E1859D



ø 8.5

ø 10.2

18

Fuse ratings and power losses For Softstarter Type

Recommended ABB Overload protection Current range Type A

Max 2) power loss at rated /e W

Max fuse rating - main circuit 1) Bussman fuses A Type Holder

PSS18/30 PSS30/52 PSS37/64 PSS44/76 PSS50/85 PSS60/105 PSS72/124 PSS85/147 PSS105/181 PSS142/245 PSS175/300 PSS250/430 PSS300/515

TA 25 DU TA 25 DU TA 42 DU TA 75 DU TA 75 DU TA 75 DU TA 75 DU TA 110 DU TA 110 DU TA 200 DU TA 200 DU TA 450 DU TA 450 DU

65 100 120 142 160 190 226 291 351 462 590 815 965

50 80 125 160 160 200 250 315 400 450 500 700 900

6–18 10–30 22–37 29–44 29–50 29–60 45–72 65–85 65–105 100–142 100–175 130–250 130–300

170M1364 170M1366 170M1368 170M1369 170M1369 170M1370 170M1371 170M1372 170M3019 170M3020 170M3021 170M5013 170M5015

170H1007 170H1007 170H1007 170H1007 170H1007 170H1007 170H1007 170H1007 170H3004 170H3004 170H3004 170H3004 170H3004

Ferraz fuses circuit A Type 63 100 160 200 200 250 315 400 400 500 530 630 900

Power re- quirements of supply VA

6.6 URB 000 D08 V 0063 6.6 URB 000 D08 V 0100 6.6 URB 000 D08 V 0160 6.6 URD 30 D08 A 0200 6.6 URD 30 D08 A 0200 6.6 URD 30 D08 A 0250 6.6 URD 30 D08 A 0315 6.6 URD 30 D08 A 0400 6.6 URD 30 D08 A 0400 6.6 URD 30 D08 A 0500 6.6 URD 30 D08 A 0550 6.6 URD 31 D08 A 0630 6.6 URD 32 D11 A 0900

9. 9. 9. 9. 10. 10. 10. 36. 36. 36. 65 65 . 65

1)

For the supply circuit 6 A delayed, for MCB use C characteristics.. Calculated power loss at operational current (Iop) without by-pass.. Ptot = 3 x Iop + VA value. Example: PSS 60/105 running at 52A Ptot = 3 x 52 + 10 = 166W When using bypass, the powerloss is reduced to the VA value only. 2)

18 1SXU 132 019 C0202

Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

So

Softstarters

fts

ta r e P ters SS

Ty p

Type PSS18/30 ... PSS300/515 UL ratings

1

3-phase motor rating - In Line Softstarters

Motor power P (hp) and nominal current Ie A





Ue 200V / 208V hp A

Ue 440V / 480V hp A



Type PSS18/30 PSS30/52 PSS37/64 PSS44/76 PSS50/85 PSS60/105 PSS72/124 PSS85/147 PSS105/181 PSS142/245 PSS175/300 PSS250/430 PSS300/515



5 7.5 10 10 15 15 20 25 30 40 50 75 75

18 28 34 40 47 56 67 85 105 125 156 225 248

Ue 220V / 240V hp A 5 10 10 10 15 20 20 30 40 40 60 75 100

18 28 34 40 47 56 67 85 105 125 156 225 248

10 20 25 30 30 40 50 60 75 100 125 150 200



18 28 34 40 47 56 67 85 105 125 156 225 248







Ue 550V / 600V hp A 15 25 30 30 40 50 60 75 100 125 150 200 250

18 28 34 40 47 56 67 85 105 125 156 225 248



3-phase motor rating - Inside Delta Softstarters

Motor power P (hp) and nominal current Ie A





Ue 200V / 208V hp A

Ue 440V / 480V hp A



Type PSS18/30 PSS30/52 PSS37/64 PSS44/76 PSS50/85 PSS60/105 PSS72/124 PSS85/147 PSS105/181 PSS142/245 PSS175/300 PSS250/430 PSS300/515

7.5 15 20 20 25 30 40 50 60 75 75 125 150

Low Voltage Products & Systems

30 48 58 69 81 96 116 147 181 215 270 389 429

Ue 220V / 240V hp A 10 15 20 25 30 30 40 50 60 75 100 150 150

30 48 58 69 81 96 116 147 181 215 270 389 429

20 30 40 50 60 75 75 100 150 150 200 300 350



30 48 58 69 81 96 116 147 181 215 270 389 429







Ue 550V / 600V hp A 25 40 50 60 75 75 100 150 150 200 250 400 400

30 48 58 69 81 96 116 147 181 215 270 389 429

19

ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU 132 019 C0202

rs

t

fts

1

So

te ar

Softstarters

ST

Type PST30 ... 300 and PSTB370 ... 1050 Overview

eP

p Ty

PST85 ... PST142

PST30 ... PST72



Normal start: In Line connected (400 V) kW Rated current Ie, A In Line connected (480 V) hp Rated current Ie, A

Softstarter, Type PST30

PST37

PST44

PST50

PST60

PST72

PST85

PST105

PST142

15 30

18.5 37

22 44

25 50

30 60

37 72

45 85

55 105

75 142

20 28

25 34

30 42

40 54

40 60

50 68

60 80

75 104

100 130

T2S160

T2S160

T2S160

T2S160

T2S160

T3S250

T3S250





400V, 40 °C MCCB (50 kA), Type

If using MCCB only, type 1 coordination will be achieved.



T2S160





Fuse protection (65 kA) Bussmann, Type

T2S160

To achieve a type 2 coordination, semi-condcutor fuses must be used.

170M1366 170M1368 170M1369 170M1369 170M1370 170M1371 170M1372 170M1319 170M1320

Suitable switch fuse for recommended semi-conductor fuses.

OS160RD0380 OS160RD0380 OS160RD0380 OS160RD0380 OESA250R03D80 OS160RD0380 OS160RD0380 OS160RD0380 OESA250R03D80



Line contactor, Type



The line contactor is not required for the softstarter itself but often used to open if OL trips.

Switch fuse, Type

A30

A40

A50





Thermal overload relay, Type

The overload relay is always required to protect the motor.



Built-in





By-pass contactor, Type

The by-pass contactor can be used to reduce the power loss of the softstarter but also to increase the number of starts/h. All softstarters be operated without by-pass. can

A9



Integrated



Built-in

A16

Built-in

A26

A50

A63

A75

A95

A110

A145

Built-in

Built-in

Built-in

Built-in

Built-in

Built-in

A26

A30

A40

A50

Integrated

Integrated

Integrated

Integrated

Integrated

Integrated

Current transformers Integrated

Integrated

The table above is an overview of possible combinations of devices. Complete coordination tables are available at www.abb.com/lowvoltage.

20 1SXU 132 019 C0202

Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com



So

Softstarters

Type PST30 ... 300 and PSTB370 ... 1050 Overview

PST175... PST300

PSTB370 ... 470

fts

ta r e P ters ST

Ty p

1

PSTB570 ... 1050

Softstarter, Type PST175

PST210

PST250

PST300

PSTB370

PSTB470

PSTB570

PSTB720

PSTB840

PSTB1050

90 175

110 210

132 250

160 300

200 370

250 470

315 570

400 720

450 840

560 1050

125 156

150 192

200 248

250 302

300 361

400 480

500 590

600 720

700 840

900 1062

T5S400

T5S400

T5S1630

T5S1630

S6S630

S6S800

S7S1250

S7S1600

170M5013

170M5015

170M5015

170M5018

170M5018

170M5020 2)

400V, 40 °C MCCB (50 kA), Type T4S250

T4S250

Fuse protection (65 kA) Bussmann, Type 170M3021

170M5012

170M5013

170M5015

Switch fuse, Type 1) OESA250R03D80 OESA400R03D80 OESA400R03D80 OESA630R03D80 OESA400R03D80 OESA400R03D80 OESA630R03D80 OESA800R03D80

1)

Line contactor, Type A185

A210

A260

A300

A400

A580

A580

A750

A1350

A1650

Built-in

Built-in

Built-in

Built-in

Built-in

Built-in

Built-in

A145

A210

Built-in

Built-in

Built-in

Built-in

Built-in

Built-in

Integrated

Integrated

Integrated

Integrated

Integrated

Integrated

Integrated

Integrated

Thermal overload relay, Type Built-in

Built-in

Built-in

By-pass contactor, Type A145

A145

Current transformers Integrated

Integrated

PSTB840 and PSTB1050: Switch fuse not available, use fuseholder, see page 40. 2) PST1050-690-70 has 170M6019 1)

Quick guide for selection

How to select correct size By using the guide beside, you can quickly select a suitable softstarter for the most common applications. If a more precise selection is required, you can use Prosoft, a selection software available at www.abb.com/lowvoltage.

Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

Normal start Class 10

Heavy duty start Class 30

Ordering – See page 26 –27

Ordering – See page 28 –29

Typical applications

Typical applications





● ●

Bow thruster ● Centrifugal pump Compressor ● Conveyor belt (short) Elevator ● Escalator

!

● ●

Centrifugal fan Crusher Mixer

● ● ●



Conveyor belt (long) Mill Stirrer

If more than 10 starts /h

Select one size larger than the standard selection.

21 1SXU 132 019 C0202

rs

1

t

fts

So

te ar

Softstarters

ST

Type PST30 ... 300 and PSTB370 ... 1050 Application and description

eP

p Ty

Application

Description

The PST range is a microprocessor based softstarter designed with the latest technology for soft start and soft stop of motors. The PST Softstarter has several advanced motor protection features as standard. The four button keypad and the logic structure of the menu make the installation, commissioning and operation easy. It is possible to choose between 13 different languages.

• Wide main voltage range 208 - 690 V AC • Wide supply voltage range 100 – 250 V, 50/60 Hz • Current ratings 30 to 1050 A (In Line) and 52 ... 1810 A (Inside Delta) • Same unit can be used for both In Line and Inside Delta connection • Premium adjustable Softstarter functions like start/stop ramp, kick start, jog, step down voltage and sequential starts. • Current limit adjustable between 2–7 x Ie • Thermistor (PTC) supervision of motor winding • Real time clock • Logging of last 20 events with time marking • Prepared for fieldbus communication • Motor overload protection with simulated motor temperature from measured current. Select between 10A, 10, 20 and 30 • Locked rotor protection • Motor underload protection • Phase imbalance protection • Phase reversal protection • Torque control • Analog output

The PST Softstarter can be used with or without a by-pass contactor except for the larger sizes PSTB370 ... PSTB1050 where the by-pass contactor is already built-in. The PST Softstarter can be selected according to the rated motor power in normal duty applications like pumps, compressors, elevators, escalators, short conveyor belts and bow thrusters. See page 26-27 For heavy duty applications like centrifugal fans, crushers, mixers, mills, stirrers and long conveyor belts, select a softstarter from page 28-29.

In-Line

Inside Delta

100 A

58 A 100 A

100 A

In-Line and Inside Delta connection of PST30 … PSTB1050

Programmable signal inputs

Three separate terminals prepared for external by-pass

Programmable signal relays

LCD-display with plain words in your language

Four button keypad

Symbol for torque control

Integrated advanced motor protection LED indications:

Power on



Fault



Protection

Clear information Terminals for PTC input and analogue output

22 1SXU 132 019 C0202

Fieldbus communication

Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

So

Softstarters

Type PST30 ... 300 and PSTB370 ... 1050 Functional description LCD display

The display of the PST gives you information presented in plain words in required language. You can choose between 13 different languages including English, German, Italian, Chinese, Finnish, Swedish, French, Spanish, Dutch, Portuguese, Russian, Turkish and Polish. On the PST display, you get all the information you need to set up, adjust and trouble-shoot. This makes the PST extremely easy to handle and reduces the risk of misinterpretations.

Four button keypad

The PST employs the same basic user concept as today’s advanced mobile telephones. Using the four buttons on the keypad, you can easily adjust your own start and stop profile and motor protection functions for any type of application. There are standard settings for many common applications including pumps, conveyors, fans, mixers and compressors for quick and easy set up. You can also set the advanced warning parameters to allow potential problems to be identified before real problems occur. A password protection function is available to prevent unauthorized changes to the programming.

Starting several motors

You can store as many as three different starting parameter sets for optimal sequence start of three different motors. You can use this function for two or three speed motors as well.

Integrated advanced motor protection

Inside the PST Softstarter, you will find useful features for advanced motor and softstarter protection, including; programmable overload protection, high current, underload, phase imbalance, phase reversal, thyristor overload protection, and bypass monitoring to ensure proper by-pass operation

Programmable signal relays

All PST units have three programmable signal relays where each relay can signal Run, Top of Ramp or Event. The Event setting can be used to signal protections, faults and warnings. The supervisory functions monitor not only software and critical softstarter functionality but also phase loss and out of frequency range.

fts

ta r e P ters ST

Ty p

1

Fieldbus communication

The PST Softstarter has a built-in interface on the front for connection of the ABB FieldBusPlug used for fieldbus communication. Through this interface it is possible to control the softstarter, achieve status information, up- and down load of parameters. The interface between the softstarter and the FieldBusPlug is always the same. Independently of PST Softstarter size or delivery date it is possible to connect to any fieldbus protocol later on since this is defined in the FieldBusPlug itself. Avaliable protocols are AS-Interface, DeviceNet, Profibus DP and Modbus-RTU. To connect the PST Softstarter to a fieldbus system you need the accessories described on page 31 to 36 as well as specific software for PLC set-up, which is available at www.abb.com/lowvoltage on the Softstarter pages.

Torque control

The default setting is a normal voltage ramp but it is possible to select torque ramp. With the torque control function it is possible to start and stop motors with a more linear acceleration than when using the normal voltage ramps. During start this can be used to reduce the wear on the equipment driven by the motor. During stop, controlling the torque is especially useful for pump applications where voltage ramps can lead to a sudden torque drop which may result in water hammering and pressure surges. Torque control will keep these problems to an absolute minimum.

Torque limit

With the torque limit function enabled, the torque can never exceed a set value during start. This will minimize stress and wear on the equipment driven by the motor.

Analog output

With the PST(B) softstarter it is possible to have analog output signals to be used as input to a PLC or an analog meter. The output signals can be selected to be for instance the current of the motor, main voltage, active power or the temperature of the motor. The terminals used for analog output are also used for PTC protection, so only one of these functions can be used.

Integrated by-pass contactor

On the larger sizes (PSTB 370 ... PSTB1050), there is an ABB AF contactor integrated. This gives you advantages in terms of cost- saving, space saving and last but not least energy saving. With a by-pass contactor you can reduce the power losses during normal run by 90 % or more. The smaller units, PST30 up to PST300, which are not equipped with a built-in by-pass contactor, have an extra set of three terminals on the line side. The terminals are marked B1, B2 and B3 and shall be used when connecting an external by-pass contactor. This will enable the integrated protection functions also when the softstarter is by-passed.

External keypad (option)

An external keypad is available as option. The keypad can be mounted on a panel door for example to view/control the softstarter without opening the door. The keypad can also be used to copy parameters between different softstarters. PSTB570 with integrated by-pass contactor. Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

23 1SXU 132 019 C0202

rs

1

t

fts

So

te ar

ST

eP

p Ty

Softstarters

Type PST30 ... 300 and PSTB370 ... 1050 Normal starts, class 10 – In-Line, Ordering details PST30 ... PST300 230 – 600 V

PST30 ... PST72

PST85 ... PST142

PST175 ... PST300

Supply voltage, Us 100...250 V, 50/60 Hz

Motor power 400 V 500 V Pe Pe kW kW

690 V Pe kW

Rated motor current, Ie A Type

15 18.5 22 25 30 37 45 55 75 90 110 132 160

- - - - - - - - - - - - -

30 37 44 50 60 72 85 105 142 175 210 250 300

Motor power





400 V Pe kW

500 V Pe kW

690 V Pe kW

Rated motor current, Ie A Type

15 18.5 22 25 30 37 45 55 75 90 110 132 160

18.5 22 25 30 37 45 55 75 90 110 132 160 200

25 30 37 45 55 59 75 90 132 160 184 220 257

30 37 44 50 60 72 85 105 142 175 210 250 300

18.5 22 25 30 37 45 55 75 90 110 132 160 200

400 – 690 V

PST30-600-70 PST37-600-70 PST44-600-70 PST50-600-70 PST60-600-70 PST72-600-70 PST85-600-70 PST105-600-70 PST142-600-70 PST175-600-70 PST210-600-70 PST250-600-70 PST300-600-70

Order code

1SFA 894 002 R7000 1SFA 894 003 R7000 1SFA 894 004 R7000 1SFA 894 005 R7000 1SFA 894 006 R7000 1SFA 894 007 R7000 1SFA 894 008 R7000 1SFA 894 009 R7000 1SFA 894 010 R7000 1SFA 894 011 R7000 1SFA 894 012 R7000 1SFA 894 013 R7000 1SFA 894 014 R7000

Weight kg

4.8 4.8 4.8 4.8 5.0 5.0 11.2 13.0 13.0 21.5 21.5 23.0 23.0

Supply voltage, Us 100...250 V, 50/60 Hz

PST30-690-70 PST37-690-70 PST44-690-70 PST50-690-70 PST60-690-70 PST72-690-70 PST85-690-70 PST105-690-70 PST142-690-70 PST175-690-70 PST210-690-70 PST250-690-70 PST300-690-70

Order code

1SFA 895 002 R7000 1SFA 895 003 R7000 1SFA 895 004 R7000 1SFA 895 005 R7000 1SFA 895 006 R7000 1SFA 895 007 R7000 1SFA 895 008 R7000 1SFA 895 009 R7000 1SFA 895 010 R7000 1SFA 895 011 R7000 1SFA 895 012 R7000 1SFA 895 013 R7000 1SFA 895 014 R7000

Weight kg

4.8 4.8 4.8 4.8 5.0 5.0 11.2 13.0 13.0 21.5 21.5 23.0 23.0

PSTB370 ... PSTB1050 with integrated by-pass 230 – 600 V

PSTB370 ... PSTB470





400 V Pe kW

500 V Pe kW

690 V Pe kW

Rated motor current, Ie A Type

200 250 315 400 450 560

257 315 400 500 600 730

- - - - - -

370 470 570 720 840 1050

Motor power





400 V Pe kW

500 V Pe kW

690 V Pe kW

Rated motor current, Ie A Type

200 250 315 400 450 560

257 315 400 500 600 730

355 450 560 710 800 1000

370 470 570 720 840 1050

400 – 690 V

PSTB570 ... PSTB1050

24 1SXU 132 019 C0202

Supply voltage, Us 100...250 V, 50/60 Hz

Motor power

PSTB370-600-70 PSTB470-600-70 PSTB570-600-70 PSTB720-600-70 PSTB840-600-70 PSTB1050-600-70

Order code

1SFA 894 015 R7000 1SFA 894 016 R7000 1SFA 894 017 R7000 1SFA 894 018 R7000 1SFA 894 019 R7000 1SFA 894 020 R7000

Weight kg

31.0 31.0 52.0 55.0 60.0 60.0

Supply voltage, Us 100...250 V, 50/60 Hz

PSTB370-690-70 PSTB470-690-70 PSTB570-690-70 PSTB720-690-70 PSTB840-690-70 PSTB1050-690-70

Order code

1SFA 895 015 R7000 1SFA 895 016 R7000 1SFA 895 017 R7000 1SFA 895 018 R7000 1SFA 895 019 R7000 1SFA 895 020 R7000

Weight kg

31.0 31.0 52.0 55.0 60.0 60.0

Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

So

Softstarters

Type PST30 ... 300 and PSTB370 ... 1050 Normal starts, class 10 – Inside Delta, Ordering details

fts

ta r e P ters ST

Ty p

1

PST30 ... PST300 230 – 600 V

PST30 ... PST72

PST85 ... PST142

PST175 ... PST300

Motor power





400 V Pe kW

500 V Pe kW

690 V Pe kW

Rated motor current, Ie Type A

25 30 37 45 55 59 75 90 132 160 184 220 257

30 37 45 55 75 80 90 110 160 200 250 295 355

- - - - - - - - - - - - -

52 64 76 85 105 124 147 181 245 300 360 430 515

Motor power





400 V Pe kW

500 V Pe kW

690 V Pe kW

Rated motor current, Ie A Type

25 30 37 45 55 59 75 90 132 160 184 220 257

30 37 45 55 75 80 90 110 160 200 250 295 355

45 55 59 75 90 110 132 160 220 257 315 400 500

52 64 76 85 105 124 147 181 245 300 360 430 515

400 – 690 V

Supply voltage, Us 100...250 V, 50/60 Hz

PST30-600-70 PST37-600-70 PST44-600-70 PST50-600-70 PST60-600-70 PST72-600-70 PST85-600-70 PST105-600-70 PST142-600-70 PST175-600-70 PST210-600-70 PST250-600-70 PST300-600-70

Order code

1SFA 894 002 R7000 1SFA 894 003 R7000 1SFA 894 004 R7000 1SFA 894 005 R7000 1SFA 894 006 R7000 1SFA 894 007 R7000 1SFA 894 008 R7000 1SFA 894 009 R7000 1SFA 894 010 R7000 1SFA 894 011 R7000 1SFA 894 012 R7000 1SFA 894 013 R7000 1SFA 894 014 R7000

Weight kg

4.8 4.8 4.8 4.8 5.0 5.0 11.2 13.0 13.0 21.5 21.5 23.0 23.0

Supply voltage, Us 100...250 V, 50/60 Hz

PST30-690-70 PST37-690-70 PST44-690-70 PST50-690-70 PST60-690-70 PST72-690-70 PST85-690-70 PST105-690-70 PST142-690-70 PST175-690-70 PST210-690-70 PST250-690-70 PST300-690-70

Order code

1SFA 895 002 R7000 1SFA 895 003 R7000 1SFA 895 004 R7000 1SFA 895 005 R7000 1SFA 895 006 R7000 1SFA 895 007 R7000 1SFA 895 008 R7000 1SFA 895 009 R7000 1SFA 895 010 R7000 1SFA 895 011 R7000 1SFA 895 012 R7000 1SFA 895 013 R7000 1SFA 895 014 R7000

Weight kg

4.8 4.8 4.8 4.8 5.0 5.0 11.2 13.0 13.0 21.5 21.5 23.0 23.0

PSTB370...PSTB1050 with integrated by-pass 230 – 600 V

PSTB370 ... PSTB470





400 V Pe kW

500 V Pe kW

690 V Pe kW

Rated motor current, Ie A Type

355 450 540 710 800 1000

450 600 700 880 1000 1250

- - - - - -

640 814 987 1247 1455 1810

Motor power





400 V Pe kW

500 V Pe kW

690 V Pe kW

Rated motor current, Ie Type A

355 450 540 710 800 1000

450 600 700 880 1000 1250

600 800 960 1200 1400 1700

640 814 987 1247 1455 1810

400 – 690 V

PSTB570 ... PSTB1050

Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

Supply voltage, Us 100...250 V, 50/60 Hz

Motor power

PSTB370-600-70 PSTB470-600-70 PSTB570-600-70 PSTB720-600-70 PSTB840-600-70 PSTB1050-600-70

Order code

1SFA 894 015 R7000 1SFA 894 016 R7000 1SFA 894 017 R7000 1SFA 894 018 R7000 1SFA 894 019 R7000 1SFA 894 020 R7000

Weight kg

31.0 31.0 52.0 55.0 60.0 60.0

Supply voltage, Us 100...250 V, 50/60 Hz

PSTB370-690-70 PSTB470-690-70 PSTB570-690-70 PSTB720-690-70 PSTB840-690-70 PSTB1050-690-70

Order code

1SFA 895 015 R7000 1SFA 895 016 R7000 1SFA 895 017 R7000 1SFA 895 018 R7000 1SFA 895 019 R7000 1SFA 895 020 R7000

Weight kg

31.0 31.0 52.0 55.0 60.0 60.0

25 1SXU 132 019 C0202

rs

1

te ar

t fts PST o S pe Ty

Softstarters

Type PST37 ... 300 and PSTB370 ... 1050 Heavy duty starts, class 30 – In-Line, Ordering details PST37 ... PST300 230 – 600 V

PST30 ... PST72





400 V Pe kW

500 V Pe kW

690 V Pe kW

Rated motor current, Ie A Type

15 18.5 22 25 30 37 45 55 75 90 110 132

18.5 22 25 30 37 45 55 75 90 110 132 160

- - - - - - - - - - - -

30 37 44 50 60 72 85 105 142 175 210 250

PST37-600-70 PST44-600-70 PST50-600-70 PST60-600-70 PST72-600-70 PST85-600-70 PST105-600-70 PST142-600-70 PST175-600-70 PST210-600-70 PST250-600-70 PST300-600-70

Motor power





Supply voltage, Us 100...250 V, 50/60 Hz

400 V Pe kW

500 V Pe kW

690 V Pe kW

Rated motor current, Ie A Type

15 18.5 22 25 30 37 45 55 75 90 110 132

18.5 22 25 30 37 45 55 75 90 110 132 160

25 30 37 45 55 59 75 90 132 160 184 220

30 37 44 50 60 72 85 105 142 175 210 250

400 – 690 V PST85 ... PST142

PST175 ... PST300

Supply voltage, Us 100...250 V, 50/60 Hz

Motor power

PST37-690-70 PST44-690-70 PST50-690-70 PST60-690-70 PST72-690-70 PST85-690-70 PST105-690-70 PST142-690-70 PST175-690-70 PST210-690-70 PST250-690-70 PST300-690-70

Order code

1SFA 894 003 R7000 1SFA 894 004 R7000 1SFA 894 005 R7000 1SFA 894 006 R7000 1SFA 894 007 R7000 1SFA 894 008 R7000 1SFA 894 009 R7000 1SFA 894 010 R7000 1SFA 894 011 R7000 1SFA 894 012 R7000 1SFA 894 013 R7000 1SFA 894 014 R7000

Order code

1SFA 895 003 R7000 1SFA 895 004 R7000 1SFA 895 005 R7000 1SFA 895 006 R7000 1SFA 895 007 R7000 1SFA 895 008 R7000 1SFA 895 009 R7000 1SFA 895 010 R7000 1SFA 895 011 R7000 1SFA 895 012 R7000 1SFA 895 013 R7000 1SFA 895 014 R7000

Heavy duty Weight kg

4.8 4.8 4.8 5.0 5.0 11.2 13.0 13.0 21.5 21.5 23.0 23.0

Weight kg

4.8 4.8 4.8 5.0 5.0 11.2 13.0 13.0 21.5 21.5 23.0 23.0

PSTB370 ... PSTB1050 with integrated by-pass 230 – 600 V

PSTB370 ... PSTB470





400 V Pe kW

500 V Pe kW

690 V Pe kW

Rated motor current, Ie A Type

160 200 250 315 400 450

200 257 315 400 500 600

- - - - - -

300 370 470 570 720 840

Motor power





400 V Pe kW

500 V Pe kW

690 V Pe kW

Rated motor current, Ie A Type

160 200 250 315 400 450

200 257 315 400 500 600

257 355 450 560 710 800

300 370 470 570 720 840

400 – 690 V

PSTB570...PSTB1050

26 1SXU 132 019 C0202

Supply voltage, Us 100...250 V, 50/60 Hz

Motor power

PSTB370-600-70 PSTB470-600-70 PSTB570-600-70 PSTB720-600-70 PSTB840-600-70 PSTB1050-600-70

Order code

1SFA 894 015 R7000 1SFA 894 016 R7000 1SFA 894 017 R7000 1SFA 894 018 R7000 1SFA 894 019 R7000 1SFA 894 020 R7000

Weight kg

31.0 31.0 52.0 55.0 60.0 60.0

Supply voltage, Us 100...250 V, 50/60 Hz

PSTB370-690-70 PSTB470-690-70 PSTB570-690-70 PSTB720-690-70 PSTB840-690-70 PSTB1050-690-70

Order code

1SFA 895 015 R7000 1SFA 895 016 R7000 1SFA 895 017 R7000 1SFA 895 018 R7000 1SFA 895 019 R7000 1SFA 895 020 R7000

Weight kg

31.0 31.0 52.0 55.0 60.0 60.0 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

So

Softstarters

Ty p

fts

ta

r Type PST37 ... 300 and PSTB370 ... 1050 e P ters Heavy duty starts, class 30 – Inside Delta, Ordering details ST

1

PST37 ... PST300 230 – 600 V

PST30 ... PST72



400 V Pe kW

500 V Pe kW

690 V Rated motor Pe current, Ie kW A Type

25 30 37 45 55 59 75 90 132 160 184 220

30 37 45 55 75 80 90 110 160 200 250 295

- - - - - - - - - - - -

52 64 76 85 105 124 147 181 245 300 360 430

Motor power





400 V Pe kW

500 V Pe kW

690 V Rated motor Pe current, Ie Type kW A

25 30 37 45 55 59 75 90 132 160 184 220

30 37 45 55 75 80 90 110 160 200 250 295

45 55 59 75 90 110 132 160 220 257 315 400

400 – 690 V PST85 ... PST142

PST175 ... PST300

Supply voltage, Us 100...250 V, 50/60 Hz

Motor power



PST37-600-70 PST44-600-70 PST50-600-70 PST60-600-70 PST72-600-70 PST85-600-70 PST105-600-70 PST142-600-70 PST175-600-70 PST210-600-70 PST250-600-70 PST300-600-70

Order code

1SFA 894 003 R7000 1SFA 894 004 R7000 1SFA 894 005 R7000 1SFA 894 006 R7000 1SFA 894 007 R7000 1SFA 894 008 R7000 1SFA 894 009 R7000 1SFA 894 010 R7000 1SFA 894 011 R7000 1SFA 894 012 R7000 1SFA 894 013 R7000 1SFA 894 014 R7000

Heavy duty Weight kg

4.8 4.8 4.8 5.0 5.0 11.2 13.0 13.0 21.5 21.5 23.0 23.0

Supply voltage, Us 100...250 V, 50/60 Hz

52 64 76 90 105 124 147 181 245 300 360 430

PST37-690-70 PST44-690-70 PST50-690-70 PST60-690-70 PST72-690-70 PST85-690-70 PST105-690-70 PST142-690-70 PST175-690-70 PST210-690-70 PST250-690-70 PST300-690-70

Order code

1SFA 895 003 R7000 1SFA 895 004 R7000 1SFA 895 005 R7000 1SFA 895 006 R7000 1SFA 895 007 R7000 1SFA 895 008 R7000 1SFA 895 009 R7000 1SFA 895 010 R7000 1SFA 895 011 R7000 1SFA 895 012 R7000 1SFA 895 013 R7000 1SFA 895 014 R7000

Weight kg

4.8 4.8 4.8 5.0 5.0 11.2 13.0 13.0 21.5 21.5 23.0 23.0

PSTB370...PSTB1050 with integrated by-pass 230 – 600 V

PSTB370 ... PSTB470



400 V Pe kW

500 V Pe kW

690 V Rated motor Pe current, Ie Type kW A

257 355 450 540 710 800

355 450 600 700 880 1000

- - - - - -

515 640 814 987 1247 1455

Motor power





400 V Pe

500 V Pe

690 V Rated motor Pe current, Ie



kW

kW

kW

A

Type

Order code

257 355 450 540 710 800

355 450 600 700 880 1000

500 600 800 960 1200 1400

515 640 814 987 1247 1455

PSTB370-690-70 PSTB470-690-70 PSTB570-690-70 PSTB720-690-70 PSTB840-690-70 PSTB1050-690-70

1SFA 895 015 R7000 1SFA 895 016 R7000 1SFA 895 017 R7000 1SFA 895 018 R7000 1SFA 895 019 R7000 1SFA 895 020 R7000

400 – 690 V

PSTB570 ... PSTB1050 Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

Supply voltage, Us 100...250 V, 50/60 Hz

Motor power



PSTB370-600-70 PSTB470-600-70 PSTB570-600-70 PSTB720-600-70 PSTB840-600-70 PSTB1050-600-70

Order code

1SFA 894 015 R7000 1SFA 894 016 R7000 1SFA 894 017 R7000 1SFA 894 018 R7000 1SFA 894 019 R7000 1SFA 894 020 R7000

Weight kg,

31.0 31.0 52.0 55.0 60.0 60.0

Supply voltage, Us 100...250 V, 50/60 Hz Weight kg

31.0 31.0 52.0 55.0 60.0 60.0

27 1SXU 132 019 C0202

rs

t

fts

1

So

te ar

Softstarters

ST

Accessories for type PST30 ... 300 and PSTB370 ... 1050 Ordering details

eP

p Ty

Cable connectors for Cu cables For PST85...300 you need 9 pieces if also using the terminals B1, B2, B3 for external by-pass contactor. For softstarter type

Wire range mm2

Tightening torque max. Nm

PST85 …142 PST85 …142 PST175 …300

6-185 16 2 x (50-120) 16 25 16-240

Type

Order code



Packing piece

– 1SDA 023 354 R0001 LZ185-2C/120 1SFN 074 709 R1000 – 1SDA 023 368 R0001

Weight kg 1 piece

3 3 3

0.20 0.30 0.40

Cable connectors for Al and Cu cables

LZ...

For PST85...300 you need 9 pieces if also using the terminals B1, B2, B3 for external by-pass contactor. For softstarter type

Wire range mm2

Tightening torque max. Nm

Type

Order code

Weight Packing kg piece 1 piece

PST85 …142 PST85 …142 PST175 …300

35-95 25-150 120-240

13.5 31 43

– – –

1SDA 023 356 R0001 1SDA 023 357 R0001 1SDA 023 370 R0001

3 3 3

Terminal extensions

LX...

0.10 0.10 0.10

For softstarter type

Dimensions hole ø bar mm2 mm

Type

Order code

Weight Packing kg pieces 1 piece

PST85…142 PST175…300 PSTB370...470 PSTB570...1050

8.5 10.5 10.5 13

LX185 LX300 LX460 LX750

1SFN 074 710 R1000 1SFN 075 110 R1000 1SFN 075 710 R1000 1SFN 076 110 R1000

1 1 1 1

17.5 x 5 20 x 5 25 x 5 40 x 6

0.250 0.350 0.500 0.850

Terminal enlargements

LW...

For softstarter type

Dimensions hole ø bar mm2 mm

Type

Order code

Weight Packing kg pieces 1 piece

PST30…72 PST85…142 PST175...300 PSTB370...470 PSTB570...1050

6.5 10.5 10.5 10.5 13

15 x 3 17.5 x 5 20 x 5 25 x 5 40 x 6

LW110 LW185 LW300 LW460 LW750

1SFN 074 307 R1000 1SFN 074 707 R1000 1SFN 075 107 R1000 1SFN 075 707 R1000 1SFN 076 107 R1000

1 1 1 1 1

0.100 0.250 0.450 0.730 1.230

Terminal nut washer

LE185

For softstarter type





Type

Order code

Weight Packing kg piece 1 piece

PST85...142 PST175...300





LE185 LE300

1SFN 074 716 R1000 1SFN 075 116 R1000

2 2



Type

Order code

Weight Packing kg pieces 1 piece

LT185-AC LT460-AC LT185-AL LT460-AL LT300-AC LT300-AL LT460-AC LT460-AL LT750-AC LT750-AL

1SFN 124 701 R1000 1SFN 125 701 R1000 1SFN 124 703 R1000 1SFN 125 703 R1000 1SFN 125 101 R1000 1SFN 125 103 R1000 1SFN 125 701 R1000 1SFN 125 703 R1000 1SFN 126 101 R1000 1SFN 126 103 R1000

2 2 2 2 2 2 2 2 2 2

Type

Order code

Weight Packing kg piece 1 piece

0.20 0.30

Terminal shrouds



LT ... -AC

LT ... -AL

For softstarter type

Req. qty

PST85…142 PST85…142 PST175...300 PST175...300 PSTB370...470 PSTB370...470 PSTB570...1050 PSTB570...1050

1 pcs and 1 pcs 1 pcs and 1 pcs 3 pcs 3 pcs 2 pcs 2 pcs 2 pcs 2 pcs

0.050 0.100 0.220 0.800 0.070 0.280 0.100 0.800 0.120 0.825

External keypad including a 3m cable PSTEK

For softstarter type





PST30...300 PSTB370...1050









PSTEK

1SFA 899 003 R1000

1

For softstarter type





Type

Order code

Weight Packing kg piece 1 piece

PST85…142





PSTM-2

1SFA 899 004 R1000

1

0.400



Marine Kit PSTM-2

28 1SXU 132 019 C0202

0.24

Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

So

Softstarters

FBP FieldBusPlug AS-Interface Fieldbus Connectors

fts

Orange cable

ta

rte

1

rs

AS-Interface FieldBusPlug Direct

Ready-made AS-Interface slave fieldbus interface with various cable lengths. • Applicable on all MSD11-FBP and terminal devices with max. 2 input and 1 output signals. • Degree of protection IP65, diagnostic LED Designation Cable Packing FieldBusPlug length Type Order code pieces AS-Interafce FBP Direct AS-Interafce FBP Direct AS-Interafce FBP Direct AS-Interafce FBP Direct

0.25 m 0.50 m 1.00 m 5.00 m

ASD11-FBP.025 ASD11-FBP.050 ASD11-FBP.100 ASD11-FBP.500

1SAJ 210 000 R0003 1SAJ 210 000 R0005 1SAJ 210 000 R0010 1SAJ 210 000 R0050

1 1 1 1

Weight kg

1 piece 0.09 0.10 0.13 0.36

AS-Interface FieldBusPlug Performance

Ready-made AS-Interface slave fieldbus interface with various cable lengths. • Applicable on all FBP motor starters and devices with max. 4 input signals and 3 output signals • Degree of protection IP65, diagnostic LED ASD11-FBP ASP22-FBP

Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

Designation Cable Packing FieldBusPlug length Type Order code pieces

Weight kg

AS-Interafce FBP Performance

0.25 m

ASP22-FBP.025

1SAJ 220 000 R0003

1

1 piece 0.09

AS-Interafce FBP Performance

0.50 m

ASP22-FBP.050

1SAJ 220 000 R0005

1

0.10

AS-Interafce FBP Performance

1.00 m

ASP22-FBP.100

1SAJ 220 000 R0010

1

0.13

AS-Interafce FBP Performance

5.00 m

ASP22-FBP.500

1SAJ 220 000 R0050

1

0.36

29 1SXU 132 019 C0202

rs

1

t

fts

So

te ar

Softstarters

FBP FieldBusPlug AS-Interface Fieldbus Accessories

Orange cable

Accessories for AS-Interface Bus Connection

AS-Interface Round Cable for Bus Junctions Ready-made bus cable with an M12 connector and an open cable end. • Application on bus junctions such as e.g. AS-Interface couplers or devices with an integrated AS-Interface Cable Packing Designation length Type Order code pieces

AS-Interface Round Cable with female connector 0.30 m ASF11-FBP.030 AS-Interface Round Cable with male connector 0.30 m ASM11-FBP.030

Weight kg

1 piece

1SAJ 922 002 R0003

1

0.04

1SAJ 922 003 R0003

1

0.04

ASF11-FBP, ASM11-FBP

AS-Interface Round Cable for Bus Extension Ready-made bus cable with M12 male and female connectors Cable Packing Designation length Type Order code pieces AS-Interface Extension Cable

ASX11-FBP

AS-Interface Extension Cable AS-Interface Extension Cable AS-Interface Extension Cable

Weight kg 1 piece

1.00 m

ASX11-FBP.100

1SAJ 922 001 R0010

1

0.08

3.00 m

ASX11-FBP.300

1SAJ 922 001 R0030

1

0.20

5.00 m

ASX11-FBP.500

1SAJ 922 001 R0050

1

0.31

100 m

ASC11-FBP.999

1SAJ 922 004 R1000

1

5.60

AS-Interface Round Cable and Accessories for Bus Extension Bus cable and coupling accessories Packing Designation Type Order code pieces

ASM11-FBP.0, ASF11-FBP.0

AS-Interface Round Cable, male conn. AS-Interface Round Cable, female conn. AS-Interface Flat-Cable Branch Circuit with M12 socket

Weight kg 1 piece

ASM11-FBP.0

1SAJ 922 005 R0001

5

ASF11-FBP.0

1SAJ 922 006 R0001

5

0.15

AST11-FBP.0

1SAJ 922 007 R0001

1

0.15



0.15

AS-Interface Addressing Device, Power Unit, miscellaneous accessories Designation Packing FieldBusPlug Type Order code pieces

AST11-FBP.0

30 1SXU 132 019 C0202

AS-Interface Addr. Device, including plug-in power unit Address Signs for FieldBusPlug

ASA21-FBP.0 CAL11-FBP.0

1SAJ 922 010 R0001 1SAJ 929 005 R0001

1 400

Weight kg 1 piece

0.56 0.15

Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

So

Softstarters

FBP FieldBusPlug/DeviceNet and MODBUS-RTU Fieldbus Connectors

fts

Black cable

ta

rte

1

rs

DeviceNet FieldBusPlug Ready-made DeviceNet fieldbus interface with various cable lengths. • Applicable on all FBP motor starters and other devices • Degree of protection IP65, diagnostic LED Cable Packing Designation length Type Order code pieces

DeviceNet-FBP DeviceNet-FBP DeviceNet-FBP DeviceNet-FBP

0.25 m 0.50 m 1.00 m 5.00 m

DNP21-FBP.025 DNP21-FBP.050 DNP21-FBP.100 DNP21-FBP.500

1SAJ 230 000 R0003 1SAJ 230 000 R0005 1SAJ 230 000 R0010 1SAJ 230 000 R0050

1 1 1 1

Weight kg 1 piece

0.09 0.10 0.13 0.36

MODBUS-RTU FieldBusPlug Ready-made MODBUS-RTU fieldbus interface with various cable lengths. • Applicable on all FBP motor starters and other devices • Degree of protection IP65, diagnostic LED Cable Packing Designation length Type Order code pieces DNP21-FBP MRP21-FBP

MODBUS-RTU-FBP MODBUS-RTU-FBP MODBUS-RTU-FBP MODBUS-RTU-FBP

0.25 m 0.50 m 1.00 m 5.00 m

MRP21-FBP.025 MRP21-FBP.050 MRP21-FBP.100 MRP21-FBP.500

1SAJ 250 000 R0003 1SAJ 250 000 R0005 1SAJ 250 000 R0010 1SAJ 250 000 R0050

1 1 1 1

Weight kg 1 piece

0.09 0.10 0.13 0.36

To connect the PST Softstarter to a DeviceNet fieldbus system... you need specific software for PLC set-up, (EDS file) which is available at www.abb.com/lowvoltage on the Softstarter pages. Look under the documentation-link named Software. If you need help or advice, please contact your local ABB office. Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

31 1SXU 132 019 C0202

rs

1

t

fts

So

te ar

Softstarters

Black cable

FBP FieldBusPlug/DeviceNet and MODBUS-RTU Fieldbus Accessories

Accessories for the DeviceNet and MODBUS-RTU Bus Connector DeviceNet and MODBUS-RTU round cable for bus junctions Ready-made bus cable with an M12 connector and an open cable end.

Cable Packing Designation length Type Order code pieces

Round Cable with female connector 0.50 m Round Cable with male connector 0.50 m

Weight kg 1 piece

DNF11-FBP.050

1SAJ 923 002 R0005

1

0.04

DNM11-FBP.050

1SAJ 923 003 R0005

1

0.04

DNF-11FBP.050

DeviceNet and MODBUS-RTU Round Cable for Bus Extension Ready-made bus cable with M12 male and female connectors

Cable Packing Designation length Type Order code pieces DNM-11FBP.050

DNX11-FDP

Extension Cable Extension Cable

1.00 m

DNX11-FBP.100

1SAJ 923 001 R0010

1

0.08

3.00 m

DNX11-FBP.300

1SAJ 923 001 R0030

1

0.20

Extension Cable

5.00 m

DNX11-FBP.500

1SAJ 923 001 R0050

1

0.31

Round Cable

100 m

DNC11-FBP.999

1SAJ 923 004 R0001

1

5.6

DeviceNet and MODBUS-RTU Round Cable and Accessories for Bus Extension Bus cable and coupling accessories

Cable Packing Designation length Type Order code pieces

DNM11-FBP.0

Round Cable Male Connector DNM11-FBP.0 1SAJ 923 005 R0001 Device Net Round Cable Female Connector DNF11-FBP.0 1SAJ 923 006 R0001

0.15

5

0.15

Packing Designation Type Order code pieces

Termination Resistor, 120 Ohm

DNR11-FBP.120

1SAJ 923 007 R0001

Weight kg 1 piece

5

DeviceNet and MODBUS-RTU, Termination Resistor, Miscellaneous Accessories DNF11-FBP.0

Weight kg 1 piece

1

Weight kg 1 piece

0.02

DNR11-FBP.120

To connect the PST Softstarter to a DeviceNet fieldbus system... you need specific software for PLC set-up, (EDS file) which is available at www.abb.com/lowvoltage on the Softstarter pages. Look under the documentation-link named Software. If you need help or advice, please contact your local ABB office. 32 1SXU 132 019 C0202

Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

Softstarters

Purple cable

FBP FieldBusPlug/Profibus DP/V0, DP/V1 Fieldbus Connectors

So

fts

ta

rte

1

rs

Profibus DP/V0 FieldBusPlug Ready-made Profibus DP/V0 fieldbus interface with various cable lengths. • Applicable on all FBP motor starters and other devices • Degree of protection IP65, diagnostic LED Cable Packing Designation length Type Order code pieces

Profibus DP/V0-FBP Profibus DP/V0-FBP Profibus DP/V0-FBP Profibus DP/V0-FBP

0.25 m 0.50 m 1.00 m 5.00 m

PDP21-FBP.025 PDP21-FBP.050 PDP21-FBP.100 PDP21-FBP.500

1SAJ 240 000 R0003 1SAJ 240 000 R0005 1SAJ 240 000 R0010 1SAJ 240 000 R0050

1 1 1 1

Weight kg 1 piece

0.09 0.10 0.13 0.36

Profibus DP/V1 FieldBusPlug Ready-made Profibus DP/V1 fieldbus interface with various cable lengths. • Applicable on all FBP motor starters and other devices • Degree of protection IP65, diagnostic LED

PDP21-FBP PDP22-FBP

Cable Packing Designation length Type Order code pieces

Profibus DP/V1-FBP Profibus DP/V1-FBP Profibus DP/V1-FBP Profibus DP/V1-FBP

0.25 m 0.50 m 1.00 m 5.00 m

PDP22-FBP.025 PDP22-FBP.050 PDP22-FBP.100 PDP22-FBP.500

1SAJ 240 100 R0003 1SAJ 240 100 R0005 1SAJ 240 100 R0010 1SAJ 240 100 R0050

1 1 1 1

Weight kg 1 piece

0.09 0.10 0.13 0.36

To connect the PST Softstarter to a Profibus DP fieldbus system... you need specific software for PLC set-up, (GSD file) which is available at www.abb.com/lowvoltage on the Softstarter pages. Look under the documentation-link named Software. If you need help or advice, please contact your local ABB office. Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

33 1SXU 132 019 C0202

rs

1

te ar

t

ts of

S

Softstarters

FBP FieldBusPlug/Profibus DP/V0, DP/V1 Fieldbus Accessories

Purple cable

Accessories for the Profibus DP/V0. DP/V1 Bus Connector Profibus DP/V0, DP/V1 Round Cable for Bus Junctions Ready-made bus cable with an M12 connector and an open cable end. • Application on bus junctions such as e.g.Profibus DB couplers or devices with an integrated Profibus DB interface Cable Packing Designation length Type Order code pieces

PDF11-FBP.50

Weight kg 1 piece

Round Cable with female connector

0.50 m

PDF11-FBP.050

1SAJ 924 002 R0005

1

0.04

Round Cable with male connector

0.50 m

PDM11-FBP.050

1SAJ 924 003 R0005

1

0.04

Profibus DP/V0, DP/V1 Round Cable for Bus Extension Ready-made bus cable with M12 male and female connectors Cable Packing Designation length Type Order code pieces

PDM11-FBP.50

Weight kg 1 piece

Extension Cable Extension Cable

1.00 m

PDX11-FBP.100

1SAJ 924 001 R0010

1

0.08

3.00 m

PDX11-FBP.300

1SAJ 924 001 R0030

1

0.20

Extension Cable

5.00 m

PDX11-FBP.500

1SAJ 924 001 R0050

1

0.31

Round Cable

100 m

PDC11-FBP.999

1SAJ 924 004 R1000

1

5.60

Profibus DP/V0, DP/V1 Accessories for Bus Extension Packing Designation Type Order code pieces

Male Connector Female Connector

Weight kg 1 piece

PDM11-FBP.0

1SAJ 924 005 R0001

5

0.03

PDF11-FBP.0

1SAJ 924 006 R0001

5

0.03

PDX11-FBP

Profibus DP/V0, DP/V1 Termination Resistor, Miscellaneous Accessories Packing Designation Type Order code pieces

PDM11-FBP.0

Termination resistor, 150 ohm PDR11-FBP.150 1SAJ 924 007 R0001 1 Feeding connector 24V DC PDV11-FBP.0 1SAJ 924 008 R0001 1 Code B-A Feeding connector 24V DC PDV12-FBP.0 1SAJ 924 011 R0001 1 Code A-A Adaptor M12-Dsub9-M12 PDA11-FBP.050 1SAJ 924 009 R0001 1 Cable lenth 0.50m Adaptor M12-Dsub9-M12 PDA12-FBP.050 1SAJ 924 010 R0001 1 Cable lenth 2 x 0.50m

Weight kg 1 piece

0.03 0,04 0,04 0,04 0,04

PDF11-FBP.0

To connect the PST Softstarter to a Profibus DP fieldbus system... you need specific software for PLC set-up, (GSD file) which is available at www.abb.com/lowvoltage on the Softstarter pages. Look under the documentation-link named Software. If you need help or advice, please contact your local ABB office. 34 1SXU 132 019 C0202

Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

So

Softstarters

fts

Type PST30 ... 300 and PSTB370 ... 1050 Technical data



PST30 … 300

PSTB370 ... 1050



Rated insulation voltage Ui

690 V

690 V

Rated operational voltage Ue

208 ... 690 V

208 ... 690 V

Starting capacity at max rated current Ir

3 x Ir for 15 sec. 3 x Ir for 15 sec

Control circuit /Hardware inputs Internal 24 V DC (10 mA closed) Yes Start / Stop inputs Yes Two extra programmable inputs

Number of starts per hour

30 1)

Overload capability, Overload Class Service factor

10 115 %

10 1)

10 115 % (PSTB370... PSTB840) 100 % (PSTB1050) Ambient temperature During operation ±0 … +50 °C 2) ±0 … +50 °C 2) During storage -25… +70 °C -25… +70 °C Altitude Maximum altitude

4000 m 3)

4000 m

3)

Degree of protection Main circuit IP10 (PST30 ... 72) IP00 (all) IP00 ( PST85 ... 300) Supply and Control circuit IP20 IP20 Main circuit Built in By-pass contactor Cooling system - Fan cooled (thermostat controlled)

No

Yes

Yes

Yes

Supply circuit Supply voltage – one range

100 ... 250 V, 50/60 Hz +10 %/-15 %

100 ... 250 V 50/60 Hz +10 %/-15 %

Yes

Yes

Yes

Yes

HMI for settings (Human Machine Interface) 20 segment display Keypad with two selection keys and two navigating keys Plain text in 13 languages (English, German, Italian, Dutch, Chinese, Finnish, Swedish, French, Spanish, Russian, Portuguese, Turkish and Polish) Signal relays Number of programmable signal relays (Each relay can be programmed to be Run, By-pass or Event signal) K4 – Default as Run signal K5 – Default as By-pass signal K6 – Default as Event signal Rated operational voltage Ue Rated thermal current Ith Rated operational current Ie at AC-15 (Ue = 250 V) Analog output Output signal reference Type of output signal

Yes

3 Yes Yes Yes 250 V 5A

1.5 A

1.5 A

1

rs

PSTB370 ... 1050

Yes Yes

(Each input can be programmed to be either; Non, Reset, Enable, Jog, DOL- On, Start motor 2 or Start motor 3, FB-Dis ).

Yes

Yes

Signal indication LED’s Power on – Green Fault - Red Protection - Yellow

Yes Yes Yes

Yes Yes Yes

Yes

Yes

Yes

Yes

Yes Yes Yes Yes Yes Yes Yes

Yes Yes Yes Yes Yes Yes Yes

Yes Yes Yes Yes

Yes Yes Yes Yes

Start of several motors Possible to set up and start three different motors

Yes

Yes

Field bus connection Connection for ABB FieldBusPlug

Yes

Yes

Protections Electronic overload Adjustable tripping classes Class 10 A, 10, 20 and 30 Dual overload (separate overload function for start and run) PTC connection Locked rotor protection Underload protection Phase imbalance High current (8 x Ie) Phase reversal protection Warnings (pre-warning) High current Low current (underload) Overload trip Overtemp. thyristors (SCR)

rte

PTC input Switch off resistance 2825 ohm + 20% 2825 ohm + 20% 1200 ohm + 20% 1200 ohm + 20% Switch on resistance

Yes

3 Yes Yes Yes 250 V 5 A

PST30 … 300

ta

External keypad Display LCD type Ambient temperature During operation + 0…+50 oC During storage -25…+70 oC Degree of protection IP66 1) Valid for 50 % on time and 50 % off time, with 3.5 x Ie for 7 seconds. If other data is required, please contact your sales office

Above 40 ºC up to max. 50 ºC reduce the rated current with 0.8 % per ºC.

2)

When used at high altitudes above 1000 meters up to 4000 meters you need to derate rated current using the following formula.

3)

0 ... 10 V, 0 ...20 mA, 4 ... 20 mA I Amp, U Volt, P kW, P hp, Q kVAr, S kVA, TmpMot, TmpSCR, cosPhi

x - 1000 [ % of Ie = 100 - ––––––– ] 150 x = actual altitude for the softstarter

PSTB Integrated by-pass ratings Softstarter

Type

PSTB370

PSTB470

PSTB570

PSTB720

PSTB840

PSTB1050

Contactor AC-3 rating

Type A

AF300 305

AF300 305

AF460 460

AF580 580

AF750 750

AF750 750

Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

35 1SXU 132 019 C0202

rs

1

t

fts

So

te ar

Softstarters

Type PST30 ... 300 and PSTB370 ... 1050 Technical data/Settings

Major possible settings and the displayed text and the set default values Description

Text on display Values on display (Eng)

Default value

Setting current for overload, locked rotor etc. Time for start ramp Time for stop ramp Initial voltage for start ramp End voltage for stop ramp Step down voltage Level of the current limit. Selection of Kick start Level of Kick start if selected Time for Kick start if selected

Setting Ie Start Ramp Stop Ramp Init Volt End Volt Step Down Current Lim Kick Start Kick Level Kick Time

9,0 ...1207 A divided into 19 overlapping ranges. 1 ... 30 s, 1 ... 120 s (Range depends on Start Range) 0 ... 30 s, 0 ... 120 s (Range depends on Stop Range) 30 ... 70 % 30 ... 70 % 30 ...100 % 2.0 ... 7.0 x Ie Yes, No 50 ... 100 % 0.1 ... 1.5 s

See table, page 40 10 s 0s 30 % 30 % 100 % 4.0 x Ie No 50 % 0.2

Selectable range for start ramp Selectable range for stop ramp Overload protection Overload Class Overload Class, Dual type, Start Class Overload Class, Dual type, Run Class Type of operation for overload protection Locked rotor protection Trip level for locked rotor protection Trip time for locked rotor protection Type of operation for locked rotor protection Underload protection Trip level for Underload protection Trip time for Underload protection Type of operation for Underload protection Phase imbalance protection Trip level for phase imbalance protection Type of operation for phase imbalance protection High current protection Type of operation for high current protection Phase reversal protection Type of operation for phase reversal protection PTC protection Type of operation for PTC protection An external Bypass contactor is used High current warning Trip level for high current warning Low current warning Trip level for low current warning Overload warning Trip level for overload warning Thyristor overload warning Type of operation for phase loss fault Type of operation for by-pass doesn’t close Type of operation for by-pass doesn’t open Type of operation for fieldbus fault Type of operation for frequency fault Type of operation for heat sink over temperature fault Type of operation for thyristor short circuit fault Function of programmable input In_0 Function of programmable input In_1 Function of programmable relay output K4 Function of programmable relay output K5 Function of programmable relay output K6 Control of the softstarter with fieldbus Number of sequences for sequence start. Language to use on display Password for display Start mode Stop mode Torque limit Analog output Analog output, reference Analog output, type of value

Start Range Stop Range Overload OL Class OL Class S OL Class R OL Op Locked Rotor Lock R Lev Lock R Time Lock R Op Underload Underl Lev Underl Time Underl Op Phase Imb Ph Imb Lev Ph Imb Op High I High I Op Phase Rev Ph Rev Op PTC PTC Op Ext ByPass Warn I=High Wa I=H Lev Warn I=Low Wa I=L Lev Warn OL Wa OL Lev Warn SCR OL Ph Loss Op BP open Op BP closed Op FB Fault Op Freq F Op HS Temp Op SCR SC Op In0 In1 Relay K4 Relay K5 Relay K6 Fieldb Ctrl No of Seq Language Password Start Mode Stop Mode Torque limit Analogue Out Anl Ref Anl Type

1 ... 30 s, 1...120 s 0 ... 30 s, 0 ... 120 s No, Normal, Dual 10 A, 10, 20, 30 10A, 10, 20, 30 10A, 10, 20, 30 Stop-M, Stop-A, Ind Yes, No 0.5 ... 8.0 x Ie 0.2 ... 10 s Stop-M, Stop-A, Ind Yes, No 0.4 ... 0.8 x Ie 1 ... 30 s Stop-M, Stop-A, Ind Yes, No 10 ... 80 % Stop-M, Stop-A, Ind Yes, No Stop-M, Stop-A, Ind Yes, No Stop-M, Stop-A, Ind Yes, No Stop-M, Stop-A Yes, No Yes, No 0.5 ... 5.0 x Ie Yes, No 0.4 ...1.0 x Ie Yes, No 40 ... 99 % Yes, No Stop-M, Stop-A Stop-M, Stop-A Stop-M, Stop-A Stop-M, Stop-A Stop-M, Stop-A Stop-M, Stop-A Stop-M, Stop-A None, Reset, Enable, Jog, DOL, Start 2, FB-Dis None, Reset, Enable, Jog, DOL, Start 3, FB-Dis Run, TOR, Event Run, TOR, Event Run, TOR, Event Yes, No No, 2, 3 US/UK, FI, SE, PT, NL, IT, FR, ES, DE, CN, RU, TR, PL No, 1 ... 255 Volt, Torque Volt, Torque 20 ... 200 % Yes, No 0 ...10 V, 0 ... 20 mA, 4 ... 20 mA I Amp, U Volt, P kW, P hp, Q kVAr, S kVA, TmpMot, TmpSCR, cosPhi

1 ... 30 s 0 ... 30 s Normal 10 10 10 Stop-M No 4,0 x Ie 1.0 s Stop-M No 0.5 x Ie 10 s Stop-M No 80 % Stop-M No Stop-M No Stop-M No Stop-M No No 1.2 x Ie No 0.8 x Ie No 90 % Yes Stop-M Stop-M Stop-M Stop-M Stop-M Stop-M Stop-M Reset Reset Run TOR Event No No US/UK

36 1SXU 132 019 C0202

Volt Volt 150 % No 4 ...20 mA I Amp

Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

So

Softstarters

fts

Type PST30 ... 300 and PSTB370 ... 1050 Technical data/Settings

ta

rte

1

rs

Tripping curves for the integrated electronic overload protection All units have an integrated electronic overload protection possible to set on four different tripping classes. Below you find a curve for each tripping class in cold state.

Time (s) 10 000

1000

100

Class 30 Class 20 Class 10 Class 10A

10

1

0

0

1

2

3

4

5

6

7

Tripping curves for electronic overload protection (Cold)

8 Current (x Ie)

ABB FieldBusPlug Controlling possibilities when using different field buses AS-Interface DeviceNet



Profibus DP V0

Profibus DP V1

Modbus-RTU

Simple control (start/stop etc) X X X X X Complete control – X X X X Simple status information X X X X X Detailed status information – X X X X Possibilities to write parameters – X X X X Possibilities to read parameters – X – X – For more detailed information, please see the Installation and Commissioning manual available at www.abb.com/lowvoltage on the Softstarter pages.

Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

37 1SXU 132 019 C0202

rs

t

fts

1

So

te ar

Softstarters

Type PST30 ... 300 and PSTB370 ... 1050 Technical data/Settings

Cross section of connectable cables Main circuit Available terminals: (For external by-pass):

Type of softstarter PST30 ... 72

PST85 ... 142

PST175 ... 300

PSTB370 ... 470

PSTB570 ... 1050

L1, L2, L3 T1, T2, T3

Yes Yes

Yes Yes

Yes Yes

Yes Yes

Yes Yes

B1, B2, B3

Yes

Yes

Yes

No

No

Connection clamp



Solid/Stranded Solid/Stranded

1 x mm2 2 x mm2

10 ... 95 6 ... 35

See accessories See accessories

See accessories See accessories

– –

– –

Tightening torque (recommended), Nm

6.0

See accessories

See accessories





Connection bar

No 6

22.5

ø 8.5

18

ø 6.5

ø 10.2

22.5 E1861D

– –

E1860D

mm mm

E1859D

Width and thickness Hole diameter

40

6

5

E1858D



25

20

17.5 5

ø 6.5 ø 12.5

Tightening torque (recommended), Nm



9

ø 10.5 40

Supply and control circuit Connection clamp

49

Yes

Yes

Yes

Yes

Yes



Solid/Stranded

1 x mm2

2.5

2.5

2.5

2.5

2.5



Solid/Stranded

2 x mm2

1.5

1.5

1.5

1.5

1.5

Tightening torque (recommended), Nm

0.5

0.5

0.5

0.5

0.5

Fuse ratings and power losses

Recommended ABB Overload protection For Current softstarter range Type Type A

PST

PST30 PST37 PST44 PST50 PST60 PST72 PST85 PST105 PST142 PST175 PST210 PST250 PST300

Integrated Integrated Integrated Integrated Integrated Integrated Integrated Integrated Integrated Integrated Integrated Integrated Integrated

9...35 11...43 13...51 15...58 18...69 22...83 25...98 32...120 43...163 53...201 63...241 75...288 90...345

Max 2) power loss at Maximum fuse ratings - main circuit 1) Bussmann fuses Ferraz fuses rated Ie W A Type Holder A Type

Power requirements supply circuit VA/VA pull in

100 120 140 160 190 230 270 325 435 540 645 765 920

5 5 5 5 5 5 10 10 10 15 15 15 15

80 125 160 160 200 250 315 400 450 500 630 700 900

170M1366 170M1368 170M1369 170M1369 170M1370 170M1371 170M1372 170M3019 170M3020 170M3021 170M5012 170M5013 170M5015

170H1007 170H1007 170H1007 170H1007 170H1007 170H1007 170H1007 170H3004 170H3004 170H3004 170H3004 170H3004 170H3004

100 160 200 200 250 315 400 400 500 550 630 630 900

6,6 URB 000 D08V 0100 6,6 URB 000 D08V 0160 6,6 URD 30 D08A 0200 6,6 URD 30 D08A 0200 6,6 URD 30 D08A 0250 6,6 URD 30 D08A 0315 6,6 URD 30 D08A 0400 6,6 URD 30 D08A 0400 6,6 URD 30 D08A 0500 6,6 URD 30 D08A 0550 6,6 URD 31 D08A 0630 6,6 URD 31 D08A 0630 6,6 URD 32 D11A 0900

PSTB 600 V

PSTB370 PSTB470 PSTB570 PSTB720 PSTB840 PSTB1050

PSTB 690 V

PSTB370 PSTB470 PSTB570 PSTB720 PSTB840 PSTB1050 1) 2)

Integrated Integrated Integrated Integrated Integrated Integrated

111...425 141...540 171...655 216...828 252...966 315...1207

90 110 105 110 170 170

700 900 900 1250 1500 1800

170M5013 170M5015 170M5015 170M5018 170M6018 170M6020

170H3004 170H3004 170H3004 170H3004 170H3004 170H3004

630 900 900 1250 1600 2000

6,6 URD 31 6,6 URD 32 6,6 URD 32 6,6 URD 33 6,6 URD 33 6,6 URD 33

D08A 0630 D11A 0900 D11A 0900 D11A 1250 D11A 1250 PLAF 2000

20/480 20/480 25/900 25/860 25/860 25/860

Integrated Integrated Integrated Integrated Integrated Integrated

111...425 141...540 171...655 216...828 252...966 315...1207

90 110 105 110 170 170

700 900 900 1250 1500 1600

170M5013 170M5015 170M5015 170M5018 170M6018 170M6019

170H3004 170H3004 170H3004 170H3004 170H3004 170H3004

630 900 900 1250 1600 1600

6,6 URD 31 6,6 URD 31 6,6 URD 31 6,6 URD 33 6,6 URD 33 6,6 URD 33

D08A 0630 D11A 0900 D11A 0900 D11A 1250 TTFA 1600 TTFA 1600

20/480 20/480 25/900 25/860 25/860 25/860

For the supply circuit 6A delayed, for MCB use C characteristics. See PSS page 20

38 1SXU 132 019 C0202

Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

So

Softstarters

fts

Type PST30...300, PSTB370...1050 UL ratings

ta

rte

1

rs

3-phase motor rating - In Line Softstarters

Motor power, P (hp), and nominal current, Ie A

Type

Ue 200V / 208V hp A

Ue 220V / 240V hp A

Ue 440V / 480V hp A

Ue 550V / 600V hp A

PST30 PST37 PST44 PST50 PST60 PST72 PST85 PST105 PST142 PST175 PST210 PST250 PST300 PSTB370 PSTB470 PSTB570 PSTB720 PSTB840 PSTB1050

7.5 10 10 15 20 20 25 30 40 50 60 75 100 125 150 200 250 300 400

10 10 15 20 20 25 30 40 50 60 75 100 100 150 200 250 300 350 450

20 25 30 40 40 50 60 75 100 125 150 200 250 300 400 500 600 700 900

25 30 40 50 50 60 75 100 125 150 200 250 300 350 500 600 700 800 1000



28 34 42 54 60 68 80 104 130 156 192 248 302 361 480 590 720 840 1062

28 34 42 54 60 68 80 104 130 156 192 248 302 361 480 590 720 840 1062

28 34 42 54 60 68 80 104 130 156 192 248 302 361 480 590 720 840 1062

28 34 42 54 60 68 80 104 130 156 192 248 302 361 480 590 720 840 1062

3-phase motor rating - Inside Delta Softstarters

Motor power, P (hp), and nominal current, Ie A

Type

Ue 200V / 208V hp A

Ue 220V / 240V hp A

Ue 440V / 480V hp A

Ue 550V / 600V hp A

PST30 PST37 PST44 PST50 PST60 PST72 PST85 PST105 PST142 PST175 PST210 PST250 PST300 PSTB370 PSTB470 PSTB570 PSTB720 PSTB840 PSTB1050

10 15 20 25 30 30 40 50 60 75 100 125 150 200 250 300 400 500 600

15 20 25 30 40 40 50 60 75 100 100 150 200 250 300 350 500 600 700

30 40 50 60 75 75 100 125 150 200 250 300 400 500 600 700 1000 1200 1500

40 50 60 75 100 100 125 150 200 250 300 350 500 600 700 800 1200 1500 1800



Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

42 54 72 80 104 104 130 156 192 248 302 361 480 590 720 840 1247 1454 1839

42 54 72 80 104 104 130 156 192 248 302 361 480 590 720 840 1247 1454 1839

42 54 72 80 104 104 130 156 192 248 302 361 480 590 720 840 1247 1454 1839

42 54 72 80 104 104 130 156 192 248 302 361 480 590 720 840 1247 1454 1839

39 1SXU 132 019 C0202

rs

t

ts of

Type PSR, PSS, PST and PSTB Wall mounting instruction, dimensions

S

Minimum distance to wall/front



Dimensions

Softstarter, type

A

B

C

E

F

H

25 25 25

0 0 0

0 0 0

45 45 54

140 160 187

114 128 153

PSS18/30 ... 44/76 PSS50/85 ... 72/124 PSS85/147 ... 142/245 PSS175/300 ... 300/515

20 20 20 20

10 10 10 10

100 100 100 100

120 140 181 356

200 250 340 340

163 163 265 265

PSS ... -690 for 690 V PSS18/30 ... 72/124 PSS85/147 ... 142/245 PSS175/300 ... 300/515

20 20 20

10 10 10

100 100 100

140 181 356

250 340 340

163 265 265

PST - all PST30 ... 72 PST85 ... 142 PST175 ... 300

20 20 20

10 10 10

100 100 100

160 186 360

260 390 420

196 270 270

PSTB - all PSTB370 ... 470 PSTB570 ... 1050

20 20

15 15

150 150

365 435

460 515

361 381

PSR3 ... PSR45 PSR3 ... 16 PSR25 ... 30 PSR37 ... 45 PSS ... -500 for 500 V

Dimensions PSTEK

138

3

1SFC132117F0201

23

135

135 107 53.5

53.5

4.8

22.5

9.5

1SFC132118F0201

118 138

14

28

1

Softstarters

te ar

Dotted line denotes area covered by external keypad

Dimensions in mm 40 1SXU 132 019 C0202

Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

So

Softstarters

fts

Type PSR3 ... PSR45 Dimensions

ABB Inc. • 888-385-1221 • www.abb-control.com

1

rs

54 mm (2.13’’)

187 mm (7.36’’)

5 mm (0.20’’)

179 mm (7.05’’)

44 mm (1.73’’)

172 mm (6.77’’)

Low Voltage Products & Systems

rte

PSR37 … 45

4 mm (0.16’’)

PSR25 … 30

3.5 mm (0.14’’)

PSR3 … 16

ta

41 1SXU 132 019 C0202

rs

t

So

Type PSS18/30 ... PSS300/515 Dimensions PSS50/85-500 … 72/124-500 PSS18/30-690 … 72/124-690

10

162

1SFC132122F0201

PSS18/30-500 … 44/76-500

10

120 105

1SFC132124F0201

fts

162

1

Softstarters

te ar

7,5

140

)

264,5 132,5

17,5 20

1SFC132128F0201

5

PSS 175/300-500 … 300/515-500 PSS 175/300-690 … 300/515-690

1SFC132126F0201

265

132,5

5

PSS85/147-500 … 142/245-500 PSS85/147-690 … 142/245-690

(4x

9

,5 ø6

1SFC132125F0201

2

9

(4x

234

1SFC132123F0201

200

184 2

)

,5

ø6

250

7,5

125

35 35 43,75

43,75

181

42 1SXU 132 019 C0202

1SFC132129F0201

340

320

ø7 (4x) 10

Dimensions in mm

11,5

340 1SFC132127F0201

(4x

10

)

ø7

356 333

11,5

320

158

Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

So

Softstarters

fts

Type PST30 ... 300 and PSTB370 ... 1050 Dimensions PST85 ...142

rte

1

rs

1SFC132130F0201

PST85 ...142 with marine kit

155

46,5

262

PSTB370 ... 470

PSTB570 ... 1050

460

PST175 ... 300

1SFC132131F0201

46,5

52,5

7

390

251

64,5

12

270

PST30 ... 72

ta

Dimensions in mm Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

43 1SXU 132 019 C0202

rs

1

te ar

t

ts of

S

Softstarters

Type PSR3 ... PSR45 Diagrams

PSR3 ...16 A) With MMS

B) With MMS and auxiliary contact

C) With fuses, contactor and O.L.

E) With MMS and auxiliary contact

F) With fuses, contactor and O.L.

PSR25 ... 45 D) With MMS

44 1SXU 132 019 C0202

Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

Softstarters

Type PSS18/30 ... PSS300/515 Diagrams

So

fts

ta

rte

1

rs

PSS18/30…300/515

F6

Temperature monitor

K5

Relay, actuated at full voltage (Ue = 100%)

K6

Relay, fault signal

T1

Control transformer

T2

Current transformer

V1-V6 Thyristor

Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

45 1SXU 132 019 C0202

rs

1

t

fts

So

te ar

Softstarters

Type PST30 ... 300 and PSTB370 ... 1050 Diagrams

PST30...300

PSTB370...1050

46 1SXU 132 019 C0202

Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

So

Softstarters

fts

Type PSR, PSS, PST and PSTB Certifications and Approvals

ta

rte

1

rs

The table below shows the approvals and certifications for different softstarters. For approvals and/or certificates not listed below, please contact your local ABB sales office. Certifications and approvals Certifications

Abbreviation Approved in

Approvals: ship classification societies

CE EU

UL USA

cULus USA

CSA Canada

CCC China

GOST Russia

ANCE C-tick Mexico Australia

LRS Gr.Britain

Germany

GL

PSR3 ... PSR45 PSR3





















PSR6





















PSR9





















PSR12





















PSR16





















PSR25





















PSR30





















PSR37





















PSR45





















PSS18/30...300/215



PSS18/30





















PSS30/52





















PSS37/64





















PSS44/76





















PSS50/85





















PSS60/105





















PSS72/124





















PSS85/147





















PSS105/181





















PSS142/245





















PSS175/300





















PSS250/420





















PSS300/515





















PST30





















PST37





















PST44





















PST50





















PST60





















PST72





















PST85





















PST105





















PST142





















PST175





















PST210





















PST250





















PST300





















PSTB370





















PSTB470





















PSTB570





















PSTB720





















PSTB840 PSTB1050

• •

• •

– –

• •

• •

• •

• •

• •

– –

• •

PST30...PSTB1050

• Standard design approved, the company labels bear the certification mark when this is required. Low Voltage Products & Systems ABB Inc. • 888-385-1221 • www.abb-control.com

47 1SXU 132 019 C0202

Leader in power and automation technologies ABB (www.abb.com) is a leader in power and automation technologies that enable utility and industry customers to improve performance while lowering environmental impact. The ABB Group of companies operates in around 100 countries and employs about 107 000 people.

Division Automation Products

The division Automation Products serves customers in the automotive, chemicals, consumer, electronics, life sciences, manufacturing, marine, metals, minerals, paper, petroleum, turbochargers and utility industries. Besides strong domain knowledge of the industries we serve, our offer includes measurement, control, communication, instrumentation, drives, motors, power electronics, software and a broad range of low-voltage products. Much of this is sold through external channel partners such as distributors, system integrators, contractors and original equipment manufacturers.

Low voltage products

Due to ABB’s broad program of product standardization, components of today are the ‘building blocks’ of system solutions, incorporating functionalities that will allow seamless integration in real-time automation and information systems. At the product level, all the low voltage products can operate together perfectly. To create a system solution every product included has to be equipped with the tools necessary to install, operate and maintain it efficiently throughout the product life cycle. The range of low voltage product is supported by technical documentation. This together with design and compact unit makes it easier than ever to incorporate our products in your system. Our customers can find all product related documentation such as brochures, catalogues, selection program, certificates, drawings and other information directly at: www.abb.com/lowvoltage.

Related Documents

Abb; Softstarters, Type Psr
November 2019 19
Psr
November 2019 14
Psr
May 2020 7
Psr Bio.
December 2019 4
Pss
June 2020 29

More Documents from ""

Abb Price Book 303
June 2020 3
Abb Price Book 687
June 2020 2
Abb Price Book 329
June 2020 4
Abb Price Book 259
June 2020 3
Abb Price Book 355
June 2020 6
Abb Price Book 483
June 2020 4