ENERGY RECOVERY VENTILATION [ERV Plus]
SAMSUNG ELECTRONICS Co. LTD. HQ SE
1
Trainer Profile • Name : • E-mail :
SAMSUNG ELECTRONICS CO.LTD
2
Contents ■ ERV + Basics
SAMSUNG ERV
■ Key Technology ■ Controls & Solution ■ Case Study ■ ERV Line-up ■ Duct design
SAMSUNG ELECTRONICS CO.LTD
3
ERV Plus Introduction
ERV + ERV Plus introduction ERV Plus = ERV(Ventilator) + DX Coil + Humidifier(Option)
5
ERV + USP Simple line up - ERV PLUS = ERV (Ventilator) + Dx-Coil (Cooler) + Humidifier(Option)
=> Install humidifier to ERV Plus at any time.
+ Humidifier Kit
ERV Plus
Line Up
D Company
M Company
X Company
Samsung
Humidifier Model Non-Humidifier Model (Separated Model)
Humidifier Model Non-Humidifier Model (Separated Model)
Humidifier Model Non-Humidifier Model (Separated Model)
Non-Humidifier Model + Optional Humidifier Kit
6
ERV+ USP Filter high efficiency
Samsung High Efficiency Medium-filter
D company Pre-filter
■ Classified as high efficiency Medium-filter, while the other is defined as pre-filter ■ Dust spot efficiency is over 70% (based on ASHRAE Std 52.1) ■ Fractional efficiency is over 60% (based on MIL,STD-282) Composition Filter media
Frame Hot melt
Spec. Media
PP + PET Spun bond
Composition
PP + PET Nonwoven
Weight
120g/㎡ ± 10%
Material
PET
Weight
260g/㎡ ± 20%
Material
Nylon
Softening point
139 ~ 149 ℃ 7
ERV+ USP Class
Standard 52.2 Min. Efficiency Reporting Value (MERV) 1 2 3
Pre filter
4 5 6 7 8 9 10
Medium Filter
HEPA
ULPA
Pre/Medium (EN 779) HEPA/ULPA (EN1822) G1
D company
Panel Type
G2
Compact Pocket Type
G 35 MP 35
G3
F 40 / F 45
G4
Compact Pocket Type
Samsung
Compact ECO Pocket Type
F5
11
F6
12
F7
13
F8
14
F9
15
H 10
16
H 11
17
H 12
18
H 13
19
H 14
20
U 15
F 50 MF Series
HEPA
ULPA
EP Series
SF Series
U 16 U 17 8
ERV + Basic Structure of ERV Plus Total heat exchanger element
Humidifier (Option)
Exhaust Air Outdoor Air
Return Air
Supply Air Access panel Filter
PCB
DX Coil
Damper 9
ERV + Basic Temperature range
10
ERV + Basic The specification
Classification Air flow rate
Unit
AM050FNKDEH
AM100FNKDEH
Air flow rate
(㎥/h)
500
1000
Static pressure
(Pa)
160
150
(W)
220
510
cooling
(%)
70
70
heating
(%)
75
75
cooling
(%)
60
62
heating
(%)
73
75
cooling
(KW)
5.1 (ERV:1.5)
10.5 (ERV:3.4)
heating
(KW)
6.5 (ERV:2.5)
13.2 (ERV:5.2)
(kg/h)
2.7
5.4
(dB)
38.5
40.5
(kg)
61
90
(mm)
1553*270*1000
1763*340*1135
Power input Ventilation performance
Temp. exchange efficiency Enthalpy exchange efficiency
Outdoor air processing capacity
Humidifying capacity Sound level Set size
extra high
11 11
ERV + Basic Psychrometric chart plotting with cooling operation 100
< Example>
80
62.82 kJ/Kg
Total heat exchanger
Heat recovery
DX Coil
53.77 kJ/Kg
ERV Plus cooling performance
OA
Cooling
SA
Cooling Cooling
35℃ RH 40%
RA
27℃ RH 47%
-5
0
5
10
15
40
20
25
20
30
Absolute Humidity (kg/kg’)
71.7 kJ/Kg
35
Dry bulb (℃) 29.5℃ RH 50.2% 32.4℃ RH 38%
Temperature Efficiency 13.3℃ RH 80%
t (OA) t ( SA) 100 t (OA) t ( RA)
Enthalpy efficiency ratio
Enthalpy Efficiency
h(OA) h( SA) 100 h(OA) h( RA)
71.7 62.82 100 = 49.5 % 71.7 53.77 12
ERV + Basic Psychrometric chart plotting with heating operation 100
< Example>
80 60
Total heat exchanger
40
DX Coil
Humidifier
41.91 kJ/Kg
20/15 ℃
36.6 kJ/Kg
Humidifying
RA
Heat recovery
heating
Humidifying
20.61 kJ/Kg
20
OA
Absolute Humidity (kg/kg’)
2/1℃
SA Heating
20℃ RH 59%
7℃ RH 87%
16.4℃ RH 67% 10.6℃ RH 79%
40 ℃ RH 12.2 %
29.5℃ RH 40%
-5
0
5
10
15
20
25
30
35
40
Dry bulb (℃)
Enthalpy efficiency
h( SA) h(OA) 100 h( RA) h(OA) 36.6 20.61 100 = 75 % 41.91 20.61
13
Operation mode
Operation mode Energy recovery(Heat-EX) and By-pass ventilation Air flow
Damper
Energy recovery (Heat exchange)
On/off button
Mode button
By-pass
Fan button
<MWR-WE10N wired remote controller>
<Energy recovery mode>
15
Operation mode Auto ventilation - According to OA and Return air temperature, the mode is determined. - The operation mode will be continue for 30 min.
Condition Energy recovery (Heat exchange)
|OA temp. – RA temp| >= 5℃
By-pass
|OA temp. – RA temp| < 5℃
Return air temp. sensor
Outdoor air temp. sensor
16
Operation mode Clean up operation -To make positive or negative pressure of room, supply and exhaust air volume can be different by Clean up operation . 05 option Seg 12
Supply air volume
Exhaust air volume
0
On
Selected fan mode
Quiet fan mode
1
Off
Quiet fan mode
Selected fan mode
Toilet
Living Room Positive pressure
17
Operation mode Outing operation
Operation mode
Fan
Energy recovery ventilation On : 10 min, Off : 50 min
Medium
Quite operation
-The fan mode is fixed to the quite mode.
18
Operation mode Energy saving operation : Energy saving operation is run when all the following conditions are met. 1) One or more ERV units must be connected to MWR-WE10N (without or with indoor unit(s) ) 2) Either the indoor unit or ERV must be ON (if the indoor unit is ON, it must not be FAN mode). 3) ERV must not be in Outing mode 4) ERV external control must not be enabled. 5) ERV must not be in “Centralized” control mode. 6) ERV must not be in “Kitchen Hood” control mode. NOTE : The sub wired remote controller does not support energy saving mode
19
Operation mode Energy saving operation Cooling
Default setting temperature : 26°C. User can change it
Heating
R : Room temperature / S : Setting temperature Default setting temperature : 22°C. User can change it
R
26°C
S
S
22°C
R
Energy Saving Out temp < Set temp : Cool air intake ↑
Out temp < Room temp : Cool air intake ↑
Set temp < Out temp : Warm air intake ↑
Room temp < Out temp : Warm air intake ↑
Out temp >= Set temp : Heat exchange ↑
Out temp >= Room temp : Heat exchange ↑
Set temp >= Out temp : Heat exchange ↑
Room temp >= Out temp : Heat exchange ↑ 20
ERV Plus • Energy saving operation – EHP-ERV combined : The operation of an ERV-combined indoor unit is not interfered by energy saving operation, but performs temperature control as it usually does. ERV Plus
MWR-WE10N
EHP F3-F4
EHP
ERV Plus
When the E.Saver button is pressed
ON
- ERV : current operation mode Energy saving operation - EHP : No change in operation - ERV controlled by room temperature (sensed by EHP or wired R/C), set temperature and outdoor temperature (sensed by ERV)
ON (no Fan mode)
OFF
- ERV : OFF Energy saving operation - EHP : No change in operation - ERV controlled by room temperature (sensed by EHP or wired R/C), set temperature and indoor temperature (sensed by ERV)
OFF
ON
- ERV : current operation mode Energy saving operation - EHP : No change in operation
OFF
OFF
- No energy saving operation
ON (no Fan mode)
21
ERV Plus • Energy saving operation – ERV only installation ERV Plus
MWR-WE10N
LOW MEDIUM HIGH
F3-F4
TURBO
ERV Plus
When the E.Saver button is pressed
ON
- Operated in Heat Exchange, LOW fan speed with repeating sequence of 30-minute operation and 30-minute stop
OFF
- No Energy Saving operation - “Restricted” displayed on wired R/C
User command ERV operation
Energy Saving mode
Heat Exchange LOW fan speed
OFF
Heat Exchange LOW fan speed
Energy saving mode 30 minutes
30 minutes
22
Operation mode Cooling or Heating with DX coil
23
Operation mode Auto operation (DX coil) Cooling operation A area
Suction air temp. sensor
Suction air temp >= auto cooling setting temp.
B area
Thermo off (Ventilation operation) Heating operation
C area
Suction air temp < auto cooling setting temp – Thermo off gap temp.
Set temp. range : Auto cooling set temp. : 15℃ ~ 30℃ (Default value : 25 ℃) Thermo off gap temp. : 5℃ ~ 15℃ (Default value : 10 ℃)
* Set temperature change
Outdoor air temp. sensor
- MWR-WE10N wired remote controller : Service mode 6-3
6 24
Operation mode Cooling & Heating operation (DX coil) -After working of ventilation mode, cooling and heating mode of DX coli is possible. Thermo on
Thermo off
Remark
Cooling
Suction air temp >= *Default set temp.
Suction air temp <= *Default set temp. – 4℃
*Default cooling set temp. : 25℃ (Set temp range : 15 ~ 30℃)
Heating
Suction air temp <= *Default set temp. + **Compensation temp. - 6
Suction air temp >= *Default set temp. + **Compensation temp. - 2
*Default heating set temp. 22℃ **Compensation temp. : 2, 5℃
* Default Set temperature change - MWR-WE10N wired remote controller : Service mode 6-2
6
25
Safety operation Prevention of condensate (Heat exchange operation) System is capable of self adjustment depending on outdoor temperature to prevent it from condensate on element Outdoor Temp
Operation Type
Above 0℃
Normal Operation
0 ℃ > TOA >-5 ℃
“A” Type Cyclic Operation “B” Type Cyclic Operation
-5 ℃ > TOA >-10 ℃
Intake
Discharge
On
On
Refer to below operation pattern
-10 ℃ > TOA >-15 ℃
Off
On
Below -15 ℃
Off
Off
‘A’ Type
80min Both Intake and Discharge On
‘B’ Type
50min Both Intake and Discharge On
10min Only Discharge On
10min Only Discharge On
80min Both Intake and Discharge On
50min Both Intake and Discharge On
Remarks
Repeated on a regular time basis
10min Only Discharge On
10min Only Discharge On
26
Fan operation with CO2 sensor Refresh system - CO2 Sensor( option) ☞ ERV airflow will be controlled automatically to supply fresh air by CO2 Level
CO2 Fresh Air
CO2
CO2
Note 1. Option setting required 2. In general, above 1000ppm is regarded as pollution Fan Speed depending on Co2 density Auto fan mode □ CO2 1200ppm ↑ : Turbo RPM □ CO2 Density 800ppm ↑ : High RPM □ CO2 Density 800ppm ↓ : Low RPM
27
Humidification Components of Humidifier kit (Option ) (05 option seg14 : 0-disuse, 1-use) Humidifier kit
AM050FNKDEH
AM100FNKDEH
Model
MVO-VA050100
MVO-VA100100
Pressure regulation valve
Solenoid valve
Strainer (1/2 Inch)
Humidifier element
Bracket
Water feed pipe
Flow switch
Connecting hose
Regular flow rate
RHF050KHEA
RHF100KHEA
0.2 L/min
0.4 L/min
28
Humidification Humidifier kit assembling
Water spray hose
29
Humidification Maintenance of humidifier kit
Intake air temperature : 0 ~ 40 ℃
Use at least the same as that of drinking or tap water
Supply water temperature : 2 ~ 40 ℃
Use neutral detergent for cleaning
Supply water pressure : 0.08 ~ 0.7 MPa
30
ERV Plus - External control - ERV ON/OFF control by external contact switch (enabled by option setting) - 02 installation option
External control
Kitchen hood control
Humidifier control
External control system Type : Voltage-free switch Tating : 5VDC, 5mA Cable : Unshielded TP 2-wire of 0.75mm2 or greater, VCTF or equivalent Length : Max. 100 meters 31
ERV Plus - Kitchen hood control : No need to set the option switch to enable kitchen hood control External control
Kitchen hood control
Kitchen hood
Humidifier control
Cable : Unshielded TP 2-wire, 0.75mm2 or greater, VCTF or equivalent Length : Max. 100 meters
Type : Voltage-free switch Rating : 5VDC, 5mA
- Kitchen hood mode - SA RPM : Turbo, EA RPM : Mid Kitchen hood switch
ON (closed) OFF (open)
ERV operation
Wired R/C
Normal Kitchen hood mode
“Hood” displayed in normal display
OFF Kitchen hood mode
“Hood” displayed in OFF
Kitchen hood mode Normal
“Hood” disappeared
Kitchen hood mode OFF
“Hood” disappeared
NOTE : The fan speed can be changed by the wired remote controller in kitchen hood mode. 32
ERV Plus - Humidify control : Humidity control by humidifier and locally purchased humidity sensor enabled by option setting Heating + 05 option seg15 : 1-use 1 → Solenoid valve on after3min.
External control
Kitchen hood control
1. Basic operation
Humidifier control
Samsung Humidifier Humidity sensor (locally purchased)
Cable : Unshielded TP 2-wire, 0.75mm2 or greater, VCTF or equivalent Length : Max. 100 meters
a. Humidity control enabled by option setting b. Humidity control input closed : Humidifier stop c. Humidity control input open : No change
2. Humidity sensor switch specifications a. Type : Voltage-free switch b. Rating : 5VDC, 5mA
3. Operation sequence a. Humidifier operation by wired remote controller b. Humidity level increase c. Humidity sensor switch closed at the set level d. Humidifier stop
33
ERV Plus - External damper control : External damper control or interlocking signal enabled by option setting (05 option seg16 : 0-disuse, 1-use) ERV operation
DAMPER output
ON
230VAC (max. 0.5A)
OFF
No voltage
Direct connection to external load (load current : below 0.5A) Relay/Magnet switch
Connection to external load via relay/magnet (load current : over 0.5A)
34
ERV Plus • CO2 sensor (MOS-C1) - Pulse width variation depending on CO2 level (pulse period = 1004ms) 2ms
ppm 0ppm
4ms
2000 4ppm
1002ms 2
CO2 sensor
1002
H L
OK
H L
NG
H L
NG
Pulse width
2ms
2000ppm
- An error is detected when the pulse from the CO2 sensor is not generated for 2 minutes.
35
ERV Plus • Option setting - 05 installation Option code : 05XXXX-1XXXXX-2XXXXX-3XXXXXX Option
SEG13
SEG14
SEG15
SEG16
Explanation
Clean up
Humidifier
CO2 sensor
External temper
Remote controller display
0
Exhaustion Air RPM is fixed as Quiet mode RPM Positive pressure
0
Disuse
0
Disuse
0
Disuse
1
Supply air RPM is fixed as Quiet mode RPM Negative pressure
1
Use
1
Use
1
Use
Indication & details
36