Low Voltage Circuit Breakers General Catalog
Molded Case Circuit Breakers and Earth Leakage Circuit Breakers
INDEX
10. Low Voltage Products Website
1
Introduction and Features of WS-V Series………………………………………………………………… 2 1. Outline of Circuit Breakers……………………………………………………………………………… 10 1) Product Line-up… ………………………………………………………………………………………………………………………………… 10 2) Instructions for Application………………………………………………………………………………………………………………………… 12
2. Detailed Specifications… ……………………………………………………………………………… 13
2
1 Molded Case Circuit Breakers.............................. 14
5 Measuring Display Unit Breakers......................... 35
1) NF-C (Economy class)...........................................................14 2) NF-S (Standard class)............................................................16 3) NF-L/NF-H/NF-R (High-performance class)...........................20 4) NF-U (Ultra current-limiting class)..........................................23
1) MDU Breakers........................................................................35
2 Earth Leakage Circuit Breakers........................... 24
3
1) NV-C (Economy class)...........................................................24 2) NV-S (Standard class)............................................................26 3) NV-H/NV-R (High-performance class)...................................28
3 Motor Protection Breakers.................................... 30 1) NF-MB....................................................................................30
4 UL 489 Listed Circuit Breakers............................. 31
6 Miniature Circuit Breakers.................................... 44 1) BH..........................................................................................44 2) BV...........................................................................................46
7 Circuit Protectors.................................................. 49 1) CP..........................................................................................49
8 Low Voltage Air Circuit Breakers...............................52 1) Low Voltage Air Circuit Breakers (AE-SW Series).................52
9 Earth Leakage Relays............................................ 54 1) Earth Leakage Relays............................................................54
1) UL 489 Listed Molded Case Circuit Breakers........................31 2) UL 489 Listed Earth Leakage Circuit Breakers......................34
4
3. Special-purpose Breakers… …………………………………………………………………………… 57 1) Mag Only (Instantaneous Tripping Circuit Breakers).............................................................................................................................. 58 2) DC MCCBs and DSN Switches.............................................................................................................................................................. 58 3) 400Hz MCCBs........................................................................................................................................................................................ 58
4. Selection… ………………………………………………………………………………………………… 59 1 Construction and Operation................................. 60
5 6
1) Construction of MCCB............................................................60 2) Construction of ELCB.............................................................62
2 Selection of MCCB and ELCB.............................. 63 1) Selecting Procedure...............................................................63 2) Features and Performance.....................................................64 3) Current-carrying Capacity and Operating Temperature.........66 4) Application of Circuit Breaker According to Breaking Capacity........68 5) Selection of Circuit Breaker for Electric Lamp or Heater Circuit......69 6) Selection of Circuit Breaker for Motor Branch Circuit.............71 7) Selection of Motor Protection Breaker....................................73
8) Selection of Circuit Breaker for Inverter Circuit......................74 9) Selection of Circuit Breaker for Transformer Primary Side....75 10) Combination for Selective Breaking.....................................79 11) Combinations for Cascade Breaking....................................81 12) International Standard Conformance List.............................83
3 Selection of ELCB.................................................. 86 1) Electric Shock Protection.......................................................86 2) ELCB Grounding Method.......................................................87 3) Rated Voltage and Number of Poles......................................88 4) Earth Fault Protection Coordination and Combination of Devices........89
5. Installation and Connection… ………………………………………………………………………… 91
7 8 9
1) Connection Types................................................................................................................................................................................... 92 2) Connecting Parts.................................................................................................................................................................................... 94 3) Standard Tightening Torque................................................................................................................................................................... 95 4) Crimp Terminal Type.............................................................................................................................................................................. 96 5) Busbar.................................................................................................................................................................................................... 98 6) Insulation Distance on Power Source Side............................................................................................................................................ 99 WS-V Series Next-generation MCCB and ELCB, AE-SW Series ACB, DIN Series MCB 7) Effect of Installation Orientation........................................................................................................................................................... 100 8) Connection of Line and Load............................................................................................................................................................... 100
6. Accessories………………………………………………………………………………………………… 101 1 Internal Accessories............................................ 102
2 External Accessories.......................................... 117
1) Internal Accessories ............................................................102 2) Kinds of Internal Accessories ..............................................103 3) Operations and Ratings of Switches ...................................103 4) Maximum Number of Internal Accessories .........................104 5) Cassette Type Accessories . ...............................................109 6) Shunt Trip (SHT) .................................................................111 7) Undervoltage Trip (UVT) .....................................................112 8) Lead Wire Drawing . ............................................................114 9) Lead Wire Terminal Block ...................................................114 10) Test Button Module (TBM) ................................................115 11) Pre-Alarm Module (PAL) ...................................................116
1) F-type Operating Handle (Breaker Mount Type)..................117 2) V-type Operating Handle (Door Mount Type).......................119 3) Terminal Covers...................................................................121 4) Insulating Barriers................................................................124 5) Handle Lock Devices, Lock Covers, Auxiliary Handles, Card Holders......127 6) Mechanical Interlocks (MI)...................................................129 7) Boxes for Circuit Breakers and Boxed Circuit Breakers.......130 8) Electrical Operated Circuit Breakers and Electrical Operation Device......133 9) Distribution Board Mounting Parts, Lock Covers and Handle Caps.......136 10) IEC 35-mm Rail Mounting Adapters...................................137
7. Characteristics and Dimensions… …………………………………………………………………… 139 1 Molded Case Circuit Breakers............................ 140
3 UL 489 Listed Circuit Breakers........................... 198
• NF30-CS................................................................................140 • NF32-SV, NF63-CV/SV/HV....................................................142 • NF125-CV/SV/HV..................................................................144 • NF125-UV..............................................................................146 • NF250-CV/SV/HV..................................................................148 • NF250-UV..............................................................................150 • NF125-SGV/LGV/HGV/RGV, NF160-SGV/LGV/HGV, NF250-SGV/LGV/HGV/RGV..................................................152 • NF125-SEV/HEV, NF250-SEV/HEV......................................154 • NF400-CW/SW......................................................................156 • NF400-SEW/HEW/REW........................................................158 • NF400-UEW...........................................................................160 • NF630-CW/SW......................................................................162 • NF630-SEW/HEW/REW........................................................164 • NF800-CEW/SEW/HEW/REW...............................................166 • NF800-SDW...........................................................................168 • NF800-UEW...........................................................................170 • NF1000-SEW, NF1250-SEW.................................................172 • NF1250-SDW.........................................................................174 • NF1600-SEW.........................................................................176 • NF1600-SDW.........................................................................178
• NF50-SVFU, NV50-SVFU......................................................198 • NF100-CVFU, NV100-CVFU.................................................200 • NF125-SVU/HVU, NV125-SVU/HVU.....................................202 • NF225-CWU...........................................................................204 • NF250-SVU/HVU, NV250-SVU/HVU.....................................206 • NF400-SWU/HWU.................................................................208 • NF630-SWU/HWU.................................................................210
2 Earth Leakage Circuit Breakers......................... 180 • NV32-SV, NV-63CV/SV/HV...................................................180 • NV125-CV/SV/HV..................................................................182 • NV250-CV/SV/HV..................................................................184 • NV125-SEV/HEV, NV250-SEV/HEV......................................186 • NV400-CW/SW......................................................................188 • NV400-SEW/HEW/REW........................................................190 • NV630-CW/SW......................................................................192 • NV630-SEW/HEW.................................................................194 • NV800-SEW/HEW.................................................................196
4 Measuring Display Unit Breakers....................... 212
1 2
• NF250-SEV/HEV with MDU...................................................212 • NF400-SEP/HEP with MDU...................................................214 • NF630-SEP/HEP with MDU, NF800-SEP/HEP with MDU.....216
5 Miniature Circuit Breakers, Residual Current Circuit Breakers, Residual Current Circuit Breakers with Overcurrent Protection and Isolating Switch................................................... 218 • BH,BH-P.................................................................................218 • BH-D6, BH-D10......................................................................219 • BH-DN....................................................................................220 • BV-D.......................................................................................221 • BV-DN....................................................................................222 • KB-D.......................................................................................223
3 4
6 Circuit Protectors................................................. 224 • CP30-BA................................................................................224
7 Electrical Operated Cicuit Breakers................... 225
5
8. Handling and Maintenance……………………………………………………………………………… 231 1) Storage and Transportation.................................................................................................................................................................. 232 2) Standard Working Conditions............................................................................................................................................................... 232 3) Mounting and Connections ................................................................................................................................................................. 232 4) Maintenance and Inspections............................................................................................................................................................... 234 5) Troubleshooting.................................................................................................................................................................................... 236
6
9. Appendix…………………………………………………………………………………………………… 239 1) Handle Operation Angle Dimensions................................................................................................................................................... 240 2) MCCB Trip Button, Instantaneous Adjustment Dial Drilling and Terminal Cover Mounting Hole Dimensions...................................... 241 3) ELCB Button and Switch Dimensions.................................................................................................................................................. 242 4) List of Product Weights........................................................................................................................................................................ 243 5) Switching the Adjustable Items............................................................................................................................................................. 244 6) Breaker Mounting Screw Dimensions.................................................................................................................................................. 247 7) List of Mold Surface Temperature-rise Values...................................................................................................................................... 248 8) Ordering Information............................................................................................................................................................................ 249 9) Melshort 2............................................................................................................................................................................................. 251 10) Low Voltage Products Website........................................................................................................................................................... 252
7 8 9
1
Since we, Mitsubishi Electric, launched the first low-voltage circuit breakers in Japan in 1933, low-voltage circuit breakers has satisfied the needs of the age and led the industry market for more than half a century all over the world. By bringing together our years of experience and technologies, we would like to introduce “WS-V Series” circuit breakers with superior aspects such as the higher breaking capacity, design for easy use, standardization of accessory parts, compliance to the up to date international standards and so on. We believe “WS-V Series” circuit breakers will fulfill every customer’s needs with its high performance and we will continue to develop and manufacture superior products that contribute to a better life for all people.
2
3
High-Performance
Technologies based on long year experience are brought together to realize more improved performance The new circuit breaking technology “Expanded ISTAC” has improved the current-limiting performance and upgraded the overall breaking capacity. Expansion of the conductor under the stator shortens the contact parting time of the mover as compared to the conventional ISTAC structure. The current-limiting performance has been improved remarkably. (The maximum peak current value has been reduced by approx. 10%.) Example of breaking capacity improvement
New circuit breaking technology (Expanded ISTAC) Grid
Previous Model NF250-SW
New Model NF250-SV
50kA /25kA
85kA /85kA
(at 230VAC)
Arc
Movable conductor Current C
(at 230VAC)
Current
Reaction circuit
Increased reaction force of movable conductor
Fixed conductor
Current B
Breaking capacity of 5 models is 20% to 50% higher than the W & WS Series
.
Breaking capacity comparison with a conventional model 20 % UP
250-RG
Model Name
Improvement of breaking capacity on 250AF-C/S/H models (Fixed) & 125.250AF-R models (Thermal/Adjustable).
50 % UP
250-H
20 % UP
250-S
WS-V Series WS Series
38.8% UP
250-C
20 % UP
125-RG 20
40
60
80
100
kA at 400VAC lcu
4
120
140
160
The new electronic circuit breakers (with display) and MDU breakers can display various measurement items This will enable energy management through “visualization”, which leads to energy saving. The display is on the circuit breaker body and shows circuit information. Detailed setting can be done on the display. The display turns red during alarms. Display
Electronic Circuit Breaker (with display)
Current in each phase
Alarm
Measuring Display Unit Breaker
Intelligent Communications through CC-Link Measuring data can be transmitted to Personal Computer through CC-Link.
LAN(Ethernet)
EcoWebServer
Electronic multi-measuring instrument
Measuring Display Unit Breaker
Energy measurement unit (EMU3 Series)
Energy measurement unit (EcoMonitorPro)
Air Circuit Breaker (AE-SW Series)
MELSEC-Q Series programmable controller
5
Standardizaion
Compact design for easy to use The thermal adjustable circuit breakers and electronic circuit breakers are smaller. NF250-SGW
NF250-SGV
Volume ratio 79% (Compared with our conventional models)
(Conventional model : 105 × 165 × 86mm)
(New model : 105 × 165 × 68mm)
250AF circuit breakers’ fixed types (NF250-CV, NF250-SV, NF250-HV, NV250-CV, NV250-SV, NV250-HV), thermal adjustable types (NF250-SGV, NF250-HGV, NF250-RGV), and electronic types (NF250-SEV, NF250-HEV, NV250-SEV, NV250-HEV) are the same size, leading to the reduction and standardization of panel design.
Types of internal accessories are reduced from 3 types to 1 type Standardization of internal accessories contributes to the reduction of stock and delivery time. For 32/63AF
Conventional models Three types
For 125AF For 250AF
New models
One type
For 32 to 250AF Applicable accessories AL
AX
AL+AX
SHT
UVT
32AF and 63AF circuit breakers can now be used in both AC and DC circuits without specifying when ordering. This will lead to prevention of ordering mistakes. The earth leakage circuit breakers can now be equipped with a voltage shunt trip device (SHT). 6
High Quality
Innovative manufacturing using a robot-cell production line This manufacturing innovation takes the pursuit of increased productivity, shortened manufacturing lead-time and improved quality to the upper limits.
Robot-cell Production Line
Individual unit production management system A multi-model, single-unit flow production system is utilized the ultimate multi-cycle production method. The production line is controlled using barcodes to manage the model information for each unit. Small-lot, flexible production that’s one step ahead! Manual Adjustment Work Timely Resupply
Component Barcode
Barcode Reader
7
Environment
Use of Various Recyclable Materials The circuit breakers are made of thermo-plastic materials that are easy to recycle. (Some models are partially made of thermoset materials.) The major plastic parts bear material identifications so that they can be recycled.
Nonuse of Hazardous Substances Eco-friendly design is used for all circuit breakers, and they do not use hazardous substances. The circuit breakers comply with RoHS regulation.
Energy Saving at Mitsubishi Electric Corporation Fukuyama Works Mitsubishi Electric Corporation Fukuyama Works uses energy saving support devices such as MDU breakers and EcoServer to save energy through “visualization” of energy. Along with “visualization”, Fukuyama Works also installed high-efficiency equipments to further promote energy saving. Through energy saving activity, Fukuyama Works has successfully reduced its electrical power consumption rate by 27% in 2007 (compared with 1990).
8
Global
Global Networks of Sales Offices and Production Bases Our sales networks are designed to comfort customers internationally through the worldwide distributors. Constantly contactable distributors enable us to accommodate customer’s needs for smooth supply. Sales Office:62 MITSUBISHI ELECTRIC DALIAN INDUSTRY PRODUCTS CO.,LTD
:19 branch office representative office :43 (available in 56 countries) :2 Production Base
MITSUBISHI ELECTRIC CORPORATION FUKUYAMA WORKS
9
1 Outline of Circuit Breakers Product Line-up
Outline of Circuit Breakers
1
Frame (A)
Classification
40 50 60 63
NF30-CS
NF63-CV
NF-S
NF32-SV
NF63-SV
Economy class
Molded Case Circuit Breakers
20 30 32
NF-C
Standard class
NF-H/L
High-performance class
NF63-HV
NV63-CV
NV125-CV
Ultra current-limiting class
NV-C
Economy class
NV-S
NV32-SV
Standard class
NV-H/R
Motor Protection Breakers UL 489 Listed Circuit Breakers Measuring Display Unit Breakers
NV125-SV NV125-SEV NV125-HV NV125-HEV
NV63-SV NV63-HV
High-performance class
MB30-CS
NF-MB
NF32-SV (*1)
160
NF125-SV NF125-SGV NF160-SGV NF125-SEV NF125-HV NF125-LGV NF160-LGV NF125-HEV NF125-HGV NF160-HGV NF125-RGV NF125-UV
NF-R/U
Earth Leakage Circuit Breakers
70 100 125 NF125-CV
NF63-CV (*1) NF63-SV (*1)
UL 489 Listed MCCB
NF50-SVFU
UL 489 Listed ELCB
NV50-SVFU
NF125-SV (*1) NF100-CVFU NF125-SVU NF125-HVU NV100-CVFU NV125-SVU NV125-HVU
MDU Breakers
Miniature Circuit Breakers
BH-DN
BH-D6
BH-D10
Residual Current Circuit Breaker
BV-D
Residual Current Circuit Breaker with Overload Protection
BV-DN
Isolating Switch
KB-D
Circuit Protectors Air Circuit Breakers
AE-SW
Related Components
Earth Leakage Relays
BH BH-P
CP30-BA CP-S
NV-ZBA, NV-ZSA, NV-ZHA, NV-ZLA
Note *1 When placing an order, specify “MB.” WS-V Series (New models)
NF-C
NV-C
NF-S
Molded Case Circuit Breakers NF-H NF-L
Earth Leakage Circuit Breakers NV-S NV-H
UL 489 Listed Circuit Breakers UL 489 Listed MCCB UL 489 Listed ELCB
10
NV-R
NF-R
NF-U
Motor Protection Breakers NF-MB
Measuring Display Unit Breakers MDU Breakers
1 Outline of Circuit Breakers
400
600 630
NF400-CW
NF630-CW
800
1000
1250
1600
2000
2500
3200
4000
5000
6300
1
NF800-CEW
NF250-SV NF250-SGV NF400-SW NF800-SDW NF630-SW NF250-SEV NF400-SEW NF630-SEW NF800-SEW NF250-HV NF250-LGV NF250-HEV NF250-HGV NF400-HEW NF630-HEW NF800-HEW NF250-RGV NF800-REW NF400-REW NF630-REW NF800-UEW NF250-UV NF400-UEW NV250-CV
NV400-CW
NV250-SV NV250-SEV NV250-HV NV250-HEV
NV630-SW NV400-SW NV800-SEW NV400-SEW NV630-SEW NV400-HEW NV630-HEW NV800-HEW NV400-REW
NF1000-SEW
NF1250-SDW NF1600-SDW NF1250-SEW NF1600-SEW
AE1000-SW
AE1250-SW
Outline of Circuit Breakers
225 250 NF250-CV
NV630-CW
NF250-SV (*1) NF225-CWU NF250-SVU NF250-HVU
NF400-SWU NF630-SWU NF400-HWU NF630-HWU
NV250-SVU NV250-HVU NF250-SEV with MDU NF250-HEV with MDU
NF400-SEP with MDU NF630-SEP with MDU NF800-SEP with MDU NF400-HEP with MDU NF630-HEP with MDU NF800-HEP with MDU
AE630-SW
BH-DN
BH-D6
AE1600-SW AE2000-SW AE2500-SW AE3200-SW AE4000-SWA AE5000-SW AE6300-SW AE4000-SW AE2000-SWA
Miniature Circuit Breakers BH-D10
BH
BH-P
Residual Current Circuit Breaker
Residual Current Circuit Breaker with Overload Protection
Isolating Switch
BV-D
BV-DN
KB-D
Circuit Protectors CP30-BA CP-S
Air Circuit Breakers AE-SW
Related Components Earth Leakage Relays
11
Instructions for Application 1. Safety Precautions
Outline of Circuit Breakers
1
d Carefully read the safety precautions prior to use the [Explanation of warning symbols] circuit breaker correctly. Incorrect handling of the product will result in a DANGER d Important safety instructions are given below. Strictly hazardous situation, such as death or serious injury. observe the instructions. Incorrect handling of the product may result in a CAUTION d Be sure to communicate these safety precautions to the hazardous situation according to circumstances. end user. DANGER Do not touch the terminal area. Doing so can cause an electric shock. The earth leakage circuit breakers are designed to operate when the difference between leaving current and returning current exceeds the specified value. In the case shown in this figure, earth leakage is not detected. Therefore, never touch the two bare live parts. The circuit breaker will not operate upon occurrence of an electric shock.
Instructions for use
CAUTION
Earth leakage circuit breaker
When the circuit breaker automatically breaks a circuit, turn on the handle after removing the cause. Failure to do so may cause an electric shock or a fire. [Earth leakage circuit breaker] Ground the earth terminal of electrical equipment. Failure to do so may cause an electric shock or a fire. Press the test button to check the operation once a month or so. If the earth leakage circuit breaker is not turned off, it is out of order. Consult an electrician.
Instructions for maintenance
Instructions for installation
CAUTION The electrical work shall be performed by qualified personnel (electrical workers). Before performing wiring work, turn off the upstream circuit breaker, and ensure that no current is flowing through the circuit breaker to be wired. Failure to do so may expose you to shock hazard. When connecting any wire, tighten the terminal screw to the torque specified in the instruction manual. Failure to do so may cause a fire. When the model comes with insulating barriers as standard accessories, install the insulating barriers without fail. Do not install the circuit breaker in an abnormal environment with high temperature, high moisture, dust, corrosive gas, vibration or shock. Doing so may cause a fire or make the circuit breaker inoperative. Protect the circuit breaker so that foreign particles, such as dust, concrete powder and iron powder, and rain water will not enter the circuit breaker. Failure to do so may make the circuit breaker inoperative. [Earth leakage circuit breaker] When using an earth leakage circuit breaker for use only in single-phase 3-wire or 3-phase 4-wire systems, connect the neutral wire to the neutral phase without fail. If they are not connected, the circuit breaker may not operate in the case of open phase or overcurrent, thereby resulting in a fire. Connect the circuit breaker to a power supply appropriate to the rating of its body. Failure to do so may make the circuit breaker inoperative or damage it. Tighten securely the lead wire in the open phase to the neutral wire on the load side. If the wires are not connected, the open phase of the neutral wire cannot be detected. When there are two terminal screws for the neutral pole, tighten the screws alternately. Failure to do so may loosen the screws, thereby causing a fire.
CAUTION The circuit breakers shall be maintained by persons with specialized knowledge. Before maintaining, turn off the upstream circuit breaker, and ensure that no current is flowing through the circuit breaker to be maintained. Failure to do so may expose you to shock hazard. Retighten the terminals periodically. Failure to do so may cause a fire.
Instructions for disposal
CAUTION When disposing of the product, treat it as industrial waste.
2. Instructions for Application (1) Please note that the specifications for the products in this catalog are subject to change without prior notice. (2) The products in this catalog are designed and manufactured as general-purpose products for general industrial uses. If you intend to use them for a special purpose, such as nuclear power, electric power, aerospace, medical or passenger vehicle equipment or systems, please contact our sales representative. (3) We are not responsible for compensation for damage caused by any reason not attributable to us, opportunity loss or lost earnings of customer caused by trouble of our product, damage, secondary damage, accidents or damage to any product other than our product caused by special circumstances or any other operation.
12
2
Detailed Specifications 1 Molded Case Circuit Breakers
1) NF-C (Economy class)……………………………………………………………………………………………………………………………… 2) NF-S (Standard class)…………………………………………………………………………………………………………………………… 3) NF-L/NF-H/NF-R (High-performance class)……………………………………………………………………………………………………… 4) NF-U (Ultra current-limiting class)…………………………………………………………………………………………………………………
2 Earth Leakage Circuit Breakers
14 14 16 20 23
24
1) NV-C (Economy class)… ………………………………………………………………………………………………………………………… 24 2) NV-S (Standard class)…………………………………………………………………………………………………………………………… 26 3) NV-H/NV-R (High-performance class)… …………………………………………………………………………………………………………… 28
3 Motor Protection Breakers
30
1) NF-MB… ……………………………………………………………………………………………………………………………………………… 30
4 UL 489 Listed Circuit Breakers
31
1) UL 489 Listed Molded Case Circuit Breakers… …………………………………………………………………………………………………… 31 2) UL 489 Listed Earth Leakage Circuit Breakers… ………………………………………………………………………………………………… 34
5 Measuring Display Unit Breakers
35
1) MDU Breakers………………………………………………………………………………………………………………………………………… 35
6 Miniature Circuit Breakers
44
1) BH… …………………………………………………………………………………………………………………………………………………… 44 2) BV… …………………………………………………………………………………………………………………………………………………… 46
7 Circuit Protectors
49
1) CP… …………………………………………………………………………………………………………………………………………………… 49
8 Low Voltage Air Circuit Breakers
52
1) Low Voltage Air Circuit Breakers (AE-SW Series)… ……………………………………………………………………………………………… 52
9 Earth Leakage Relays
54
1) Earth Leakage Relays………………………………………………………………………………………………………………………………… 54
13
2
Detailed Specifications
1
Molded Case Circuit Breakers
NF-C (Economy class) Frame (A) Model
30 NF30-CS
50
60 NF63-CV
63
100
125 NF125-CV
Image
Cassette-type Installation and connections accessories
Overall dimensions (mm)
Rated short-circuit breaking capacities (kA)
50 (60) 63 Rated current In (A) 3 4 (5) 6 10 (15) 16 125 3 5 10 15 20 30 (60) 63 (75) 80 100 20 25 (30) 32 40 50 Rated ambient temperture 40°C (45°C for marine use) Number of poles 2 3 2 3 2 3 2 3 2 3 2 3 Rated insulation voltage Ui (V) 500 600 600 600 600 600 690V − − − − − − 500V − 2.5/2.5 2.5/2.5 2.5/2.5 7.5/4 7.5/4 440V − 2.5/2.5 2.5/2.5 2.5/2.5 10/5 10/5 415V 1.5/1.5 2.5/2.5 2.5/2.5 2.5/2.5 10/5 10/5 IEC 60947-2 AC EN 60947-2 400V 1.5/1.5 5/5 5/5 5/5 10/5 10/5 (Icu/Ics) 380V 1.5/1.5 5/5 5/5 5/5 10/5 10/5 230V 2.5/2 (240V) 7.5/7.5 7.5/7.5 7.5/7.5 30/15 30/15 200V 2.5/2 (240V) 7.5/7.5 7.5/7.5 7.5/7.5 30/15 30/15 DC 250V − 2.5/2.5 (*7) 2.5/2.5 (*7) 2.5/2.5 (*7) 7.5/4 (*4) 7.5/4 (*4) Rated impulse withstand voltage Uimp (kV) 4 8 8 8 8 8 Current (*1) AC AC/DC compatible AC/DC compatible AC/DC compatible AC/DC compatible AC/DC compatible Suitability for isolation − Compatible Compatible Compatible Compatible Compatible Reverse connection − Possible Possible Possible Possible Possible Without current 10,000 10,000 10,000 10,000 10,000 10,000 Number of operating cycles With current (440VAC) 6,000 (AC415V) 6,000 6,000 6,000 6,000 6,000 Utilization category A A A A A A Pollution degree 2 3 3 3 3 3 EMC environment condition (environment A or B) N/A N/A N/A N/A N/A N/A ca a a 45 67.5 50 75 50 75 50 75 60 90 60 90 c b 96 130 130 130 130 130 b c 52 68 68 68 68 68 ca 67 90 90 90 90 90 Mass of front-face type (kg) 0.25 0.35 0.45 0.65 0.5 0.7 0.5 0.7 0.6 0.9 0.6 0.9 Front connection (F) Page dScrew terminal dScrew terminal dScrew terminal dScrew terminal dScrew terminal dScrew terminal Solderless (BOX) terminal (SL) − − − − d d Rear (B) 92 dRound stud (assembled in) dRound stud dRound stud dRound stud dBar stud dBar stud Plug-in (PM) − d d d d d Alarm switch (AL) d (*5) d (*6) d (*6) d (*6) d (*6) d(*6) Auxiliary switch (AX) d(*5) d (*6) d (*6) d (*6) d (*6) d(*6) 102 Shunt trip (SHT) − d (*6) d (*6) d (*6) d (*6) d(*6) Undervoltage trip (UVT) − d (*6) d (*6) d (*6) d (*6) d(*6) With lead-wire terminal block (SLT) 114 d d d d d d Pre-alarm (PAL) 116 − − − − − − Closed (S) d d d d d d (I) 130 − Enclosure Dustproof d d d d d Waterproof (W) − − − − − − d d d d d Electrical operation device (NFM) 133 − − − − − − d d Panel mounting − d d d d d Mechanical 129 interlock (MI) (*10) Breaker mounting − d d d d d LC d d d d d d Handle lock 127 HL d d d d d d device HL-S − d d d d d (F) − d d d d d External 117 operating handle (V) − d d d d d Terminal cover (TC-L, TC-S, TTC, BTC, PTC) 121 d d d d d d − Rear stud (B-ST) d d d d d 94 Plug-in (PM) − d d d d d IEC 35mm rail mounting adapters 137 − − d d d d CE marking TÜV approval Self-declaration Self-declaration Self-declaration Self-declaration Self-declaration CCC recognition Recognition in process Recognition in process Recognition in process Recognition in process Recognition in process Recognition in process Marine use approval (NK, LR, ABS, GL) (NK, LR, ABS) Automatic tripping device Hydraulic magnetic Thermal-magnetic Thermal-magnetic Thermal-magnetic Thermal-magnetic Thermal-magnetic Trip button − (*2) Equipped Equipped Equipped Equipped Equipped Page of Characteristics and dimensions 140 142 144 External accessories
1 Detailed Specifications
2
Notes:
*1 *2 *3 *4
*5 *6
*7 *8 *9
14
*10
The trip action characteristics differ between AC and DC for products that are compatible with both AC and DC. It is attached with the alarm switch. In case of a current rating of 100A, it does not specify NK rating. Use two poles for three- and four-pole products. In this case, do not use the neutral pole of the four-pole products. If wired as shown on the right, three and four poles can be used for up to 400 and 500VDC, respectively. The standard lead drawing is performd laterally. Load drawing is also available. The cassette type design makes it easy for customer to install. Available for installation on side below 250A frame (excluding UVT). Use two poles for three- and four-pole products. In this case, do not use the neutral pole of the four-pole products. Not available for use with connection as shown on the right. Place an order of other models in conjunction with the circuit breaker. Solid state relay output is option. Please specify if other output is necessary. (Standard type is thus SLT equipped). Not isolation compatible, excluding 400 to 800A frame.
Line
Line
3-pole
Load
4-pole
Load
2 Detailed Specifications
1 Molded Case Circuit Breakers
NF-C (Economy class) 250
400 NF400-CW
600
250 300 350 400
500 600
NF250-CV
(100) 125 150 175 200 225 (*3) 2 3 600 − 10/8 15/12 25/19 25/19 25/19 36/27 36/27 15/12 (*4) 8 AC/DC compatible Compatible Possible 8,000 4,000 A 3 N/A 105 165 68 92 1.3 1.5 dScrew terminal d dBar stud d d(*6) d(*6) d(*6) d(*6) d − d d − d d d d d d d d d d d d − TÜV approval Recognition in process Thermal-magnetic Equipped
250 2
3 600 − 10/8 15/12 25/19 25/19 25/19 36/27 36/27 15/12 (*4) 8 AC/DC compatible Compatible Possible 8,000 4,000 A 3 N/A 105 165 68 92 1.3 1.5 dScrew terminal d dBar stud d d(*6) d(*6) d(*6) d(*6) d − d d − d d d d d d d d d d d d − TÜV approval Recognition in process Thermal-magnetic Equipped 148
2
3 690 − 15/8 25/13 36/18 36/18 40/20 50/25 50/25 20/10 (*4) 8 AC/DC compatible Compatible Possible 6,000 1,000 A 3 N/A 140 257 103 134 4.4 5.0 dBusbar terminal − dBar stud d d(*6) d(*6) d(*6) d d − − d d d(*8) d d − d d d d d d d d − Self-declaration Recognition in process Thermal-magnetic Equipped 156
630 NF630-CW
630
2
3 690 − 18/9 36/18 36/18 36/18 40/20 50/25 50/25 20/10 (*4) 8 AC/DC compatible Compatible Possible 6,000 1,000 A 3 N/A 140 257 103 134 5.2 6.0 dBusbar terminal − dBar stud d d(*6) d(*6) d(*6) d d − − d d d(*8) d d − d d d d d d d d d − Self-declaration Recognition in process Thermal-magnetic Equipped
2
3 690 − 18/9 36/18 36/18 36/18 40/20 50/25 50/25 20/10 (*4) 8 AC/DC compatible Compatible Possible 6,000 1,000 A 3 N/A 140 257 103 134 5.2 6.0 dBusbar terminal − dBar stud d d(*6) d(*6) d(*6) d d − − d d d(*8) d d − d d d d d d d d d − Self-declaration Recognition in process Thermal-magnetic Equipped 162
800 NF800-CEW
Adjustable 400 450 500 600 700 800 3 690 − 18/9 36/18 36/18 36/18 40/20 50/25 50/25 − 8 AC Compatible Possible 4,000 500 B 3 A 210 275 103 155 10.9 dBusbar terminal − dBar stud d d(*6) d(*6) d(*6) d d d(*9) − d d d(*8) d d − d d d d d d d − Self-declaration Recognition in process Electronic (effective value detection) Equipped 166
Remarks: 1. Products with rated current parenthesized are produced when an order is placed. 2. Specify “P-LT” when using a plug-in product with a lead-wire terminal block. 3. The circuit breaker has the rated short-circuit breaking capacity specified in the shaded cells.
15
2 1 Detailed Specifications
225
2
Detailed Specifications
1
Molded Case Circuit Breakers
NF-S (Standard class) Frame (A) Model
30
32
50
60 NF63-SV
NF32-SV
63
Image
Cassette-type Installation and accessories connections
Overall dimensions (mm)
Rated short-circuit breaking capacities (kA)
Rated current In (A) Rated ambient temperture 40°C (45°C for marine use) Number of poles Rated insulation voltage Ui (V) 690V 500V 440V 415V IEC 60947-2 AC EN 60947-2 400V (Icu/Ics) 380V 230V 200V DC 250V Rated impulse withstand voltage Uimp (kV) Current (*1) Suitability for isolation Reverse connection Without current Number of operating cycles With current (440VAC) Utilization category Pollution degree EMC environment condition (environment A or B) ca a a c b b c ca Mass of front-face type (kg) Front connection (F) Page Solderless (BOX) terminal (SL) Rear (B) 92 Plug-in (PM) Alarm switch (AL) Auxiliary switch (AX) 102 Shunt trip (SHT) Undervoltage trip (UVT) With lead-wire terminal block (SLT) 114 Pre-alarm (PAL) 116 Closed (S) (I) 130 Enclosure Dustproof Waterproof (W) Electrical operation device (NFM) 133 Mechanical Panel mounting 129 interlock (MI) (*7) Breaker mounting LC Handle lock 127 HL device HL-S (F) External 117 operating handle (V) Terminal cover (TC-L, TC-S, TTC, BTC, PTC) 121 Rear stud (B-ST) 94 Plug-in (PM) IEC 35mm rail mounting adapters 137 CE marking CCC recognition Marine use approval (NK, LR, ABS, GL) Automatic tripping device Trip button Page of Characteristics and dimensions External accessories
1 Detailed Specifications
2
3 4 (5) 6 10 15 16 20 25 (30) 2 3 600 − 2.5/2.5 2.5/2.5 2.5/2.5 5/5 5/5 7.5/7.5 7.5/7.5 2.5/2.5 (*5) 8 AC/DC compatible Compatible Possible 10,000 6,000 A 3 N/A 50 75 130 68 90 0.45 0.65 dScrew terminal − dBar stud d d (*4) d (*4) d (*4) d (*4) d − d d − d − d d d d d d d d d d d Self-declaration Recognition in process Thermal-magnetic Equipped
32 2
3
600 − 2.5/2.5 2.5/2.5 2.5/2.5 5/5 5/5 7.5/7.5 7.5/7.5 2.5/2.5 (*5) 8 AC/DC compatible Compatible Possible 10,000 6,000 A 3 N/A 50 75 130 68 90 0.45 0.65 dScrew terminal − dRound stud d d (*4) d (*4) d (*4) d (*4) d − d d − d − d d d d d d d d d d d Self-declaration Recognition in process Thermal-magnetic Equipped
3 4 (5) 6 10 (15) 16 20 25 (30) 32 40 50 2 3 4 600 − 7.5/7.5 7.5/7.5 7.5/7.5 7.5/7.5 7.5/7.5 15/15 15/15 7.5/7.5 (*5) 8 AC/DC compatible Compatible Possible 10,000 6,000 A 3 N/A 50 75 100 130 68 90 0.5 0.7 0.9 dScrew terminal − dRound stud d d (*4) d d (*4) d d (*4) d d (*4) d d d − − d − d − − d − d d − d d d d d d d d d d d − d Self-declaration Recognition in process − Thermal-magnetic Equipped
142
Notes: *1 The trip action characteristics differ between AC and DC for products that are compatible with both AC and DC. *2 In case of a current rating of 100A, it does not specify NK rating. *3 Use two poles for three- and four-pole products. In this case, do not use the neutral pole of the four-pole products. If wired as shown on the right, three and four poles can be used for up to 400 and 500VDC, respectively. (In case of NF250-SV, three and four poles can be used for up to 500 and 600VDC) *4 The cassette type design makes it easy for customer to install. Available for installation on side below 250A frame (excluding UVT). *5 Use two poles for three- and four-pole products. In this case, do not use the neutral pole of the four-pole products. Not available for use with connection as shown on the right. *6 Place an order of other models in conjunction with the circuit breaker. *7 Not isolation compatible. excluding 400 to 800A frame.
16
(60)
63
2
3 4 600 − 7.5/7.5 7.5/7.5 7.5/7.5 7.5/7.5 7.5/7.5 15/15 15/15 7.5/7.5 (*5) 8 AC/DC compatible Compatible Possible 15,000 8,000 A 3 N/A 50 75 100 130 68 90 0.55 0.75 1.0 dScrew terminal − dRound stud d d (*4) d d (*4) d d (*4) d d (*4) d d d − − d − d − − d − d d − d d d d d d d d d d d − d Self-declaration Recognition in process − Thermal-magnetic Equipped 142
2
3 4 600 − 7.5/7.5 7.5/7.5 7.5/7.5 7.5/7.5 7.5/7.5 15/15 15/15 7.5/7.5 (*5) 8 AC/DC compatible Compatible Possible 15,000 8,000 A 3 N/A 50 75 100 130 68 90 0.55 0.75 1.0 dScrew terminal − dRound stud d d (*4) d d (*4) d d (*4) d d (*4) d d d − − d − d − − d − d d − d d d d d d d d d d d − d Self-declaration Recognition in process − Thermal-magnetic Equipped
Line
Line
3-pole
Load
4-pole
Load
2 Detailed Specifications
1 Molded Case Circuit Breakers
NF-S (Standard class) 125 NF125-SV
(15) 16 20 (30) 32 40 125 50 (60) 63 (75) 80 100 2 3 4 2 3 4 690 690 8/8 8/8 18/18 18/18 25/25 25/25 30/30 30/30 30/30 30/30 30/30 30/30 50/50 50/50 50/50 50/50 40/40 (*3) 40/40 (*3) 8 8 AC/DC compatible AC/DC compatible Compatible Compatible Possible Possible 25,000 25,000 10,000 10,000 A A 3 3 N/A N/A 60 90 120 60 90 120 130 130 68 68 90 90 0.7 1.0 1.3 0.7 1.0 1.3 dScrew terminal dScrew terminal d d dBar stud dBar stud d d d d d (*4) d d (*4) d d (*4) d d (*4) d d (*4) d d (*4) d d (*4) d d (*4) d d d d d − − − − d d − − d d − − − − d d − − d d d d d d − − d d d d d d d d d d − − d d d d d d d d d d d d d d d − − Self-declaration Self-declaration Recognition in process Recognition in process − − Thermal-magnetic Thermal-magnetic Equipped Equipped 144
125 NF125-SGV
125 NF125-SEV
160 NF160-SGV
16-20 20-25 25-32 32-40 35-50 16-32 32-63 63-125 125-160 45-63 56-80 70-100 90-125 2 3 4 3 4 2 3 4 690 690 690 8/8 8/8 8/8 30/30 30/30 30/30 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 85/85 85/85 85/85 85/85 85/85 85/85 20/20 (300V) (*3) − 20/20 (300V) (*3) 8 8 8 AC/DC compatible AC AC/DC compatible Compatible Compatible Compatible Possible Possible Possible 50,000 25,000 40,000 30,000 10,000 15,000 A A A 3 3 3 N/A A N/A 105 140 105 140 105 140 165 165 165 68 68 68 92 92 92 1.4 1.6 2.0 1.7 2.2 1.4 1.6 2.0 dScrew terminal dScrew terminal dScrew terminal d d d d dBar stud dBar stud dBar stud dBar stud d d d d d (*4) d d (*4) d d (*4) d d (*4) d d (*4) d d (*4) d d (*4) d d (*4) d d (*4) d d (*4) d d (*4) d d (*4) d d d d d − − d − − − d d d − − − d d d − − − d d d d d d d d d d − d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d − − − Self-declaration Self-declaration Self-declaration Recognition in process Recognition in process Recognition in process − − − (LR, ABS, GL) (LR, ABS, GL) (LR, ABS, GL) Thermal-magnetic Electronic (effective value detection) Thermal-magnetic Equipped Equipped Equipped 152 154 152
225
250 NF250-SV
(100) 125 150 160 250 175 200 225 (*2) 2 3 4 2 3 4 690 690 8/8 8/8 30/30 30/30 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 85/85 85/85 85/85 85/85 20/20 (300V) (*3) 20/20 (300V) (*3) 8 8 AC/DC compatible (*1) AC/DC compatible (*1) Compatible Compatible Possible Possible 25,000 25,000 10,000 10,000 A A 3 3 N/A N/A 105 140 105 140 165 165 68 68 92 92 1.4 1.6 2.0 1.4 1.6 2.0 dScrew terminal dScrew terminal d d d d dBar stud dBar stud d d d d d (*4) d d (*4) d d (*4) d d (*4) d d (*4) d d (*4) d d (*4) d d (*4) d d d d d − − − − d d − − d d − − d d d d d d d d − − d d d d d d d d d d d d d d d d d d d d d d d d − − TÜV approval Self-declaration TÜV approval Self-declaration Recognition in process Recognition in process − − Thermal-magnetic Thermal-magnetic Equipped Equipped 148
Remarks: 1. Products with rated current parenthesized are produced when an order is placed. 2. Specify “P-LT” when using a plug-in product with a lead-wire terminal block. 3. The circuit breaker has the rated short-circuit breaking capacity specified in the shaded cells.
17
2 1 Detailed Specifications
100
2
Detailed Specifications
1
Molded Case Circuit Breakers
NF-S (Standard class) Frame (A) Model
250 NF250-SGV
250 NF250-SEV
400 NF400-SW
400 NF400-SEW
600
630 NF630-SW
Image
Cassette-type Installation and connections accessories
Overall dimensions (mm)
Rated short-circuit breaking capacities (kA)
Rated current In (A) 125-160 140-200 175-250 Rated ambient temperture 40°C (45°C for marine use) Number of poles 2 3 4 Rated insulation voltage Ui (V) 690 690V 8/8 500V 30/30 440V 36/36 415V 36/36 IEC 60947-2 AC EN 60947-2 400V 36/36 (Icu/Ics) 380V 36/36 230V 85/85 200V 85/85 DC 250V 20/20 (300V) (*2) Rated impulse withstand voltage Uimp (kV) 8 Current AC/DC compatible Suitability for isolation Compatible Reverse connection Possible Without current 25,000 Number of operating cycles With current (440VAC) 10,000 Utilization category A Rated short time with stand current Icw (kA) at 0.25s − Pollution degree 3 EMC environment condition (environment A or B) N/A ca a a 105 140 c b 165 b c 68 ca 92 Mass of front-face type (kg) 1.4 1.6 2.0 Front connection (F) Page d Solderless (BOX) terminal (SL) d Rear (B) 92 dBar stud Plug-in (PM) d Alarm switch (AL) d (*3) d Auxiliary switch (AX) d (*3) d 102 Shunt trip (SHT) d (*3) d Undervoltage trip (UVT) d (*3) d With lead-wire terminal block (SLT) 114 d Pre-alarm (PAL) 116 − Closed (S) − d (I) 130 − Enclosure Dustproof d − Waterproof (W) d Electrical operation device (NFM) 133 d d Mechanical Panel mounting 129 interlock (MI) (*7) Breaker mounting d LC d Handle lock 127 HL d device HL-S d (F) d External 117 operating handle (V) d Terminal cover (TC-L, TC-S, TTC, BTC, PTC) 121 d Rear stud (B-ST) d 94 Plug-in (PM) d IEC 35mm rail mounting adapters 137 − CE marking Self-declaration CCC recognition Recognition in process Marine use approval (NK, LR, ABS, GL) (LR, ABS, GL) − Automatic tripping device Thermal-magnetic Trip button Equipped Page of Characteristics and dimensions 152 External accessories
1 Detailed Specifications
2
250 300 Adjustable 200 225 500 600 630 350 400 250 300 350 400 3 4 2 3 4 3 4 2 3 4 2 3 4 690 690 690 690 690 8/8 10/10 10/10 10/10 10/10 30/30 30/30 30/30 30/30 30/30 36/36 42/42 42/42 42/42 42/42 36/36 45/45 50/50 50/50 50/50 36/36 45/45 50/50 50/50 50/50 36/36 50/50 50/50 50/50 50/50 85/85 85/85 85/85 85/85 85/85 85/85 85/85 85/85 85/85 85/85 − 40/40 (*2) − 40/40 (*2) 40/40 (*2) 8 8 8 8 8 AC AC/DC compatible AC AC/DC compatible AC/DC compatible Compatible Compatible Compatible Compatible Compatible Possible Possible Possible Possible Possible 25,000 6,000 6,000 6,000 6,000 10,000 1,000 1,000 1,000 1,000 A A B A A − − 5 − − 3 3 3 3 3 A N/A A N/A N/A 105 140 140 185 140 185 140 185 140 185 165 257 257 257 257 68 103 103 103 103 92 155 155 155 155 1.7 2.2 4.6 5.2 6.8 6.0 7.6 5.4 6.2 8.0 5.4 6.2 8.0 dBusbar terminal dBusbar terminal dBusbar terminal dScrew terminal dScrew terminal dBusbar terminal − − − − − − − − − − − d d dBar stud dBar stud dBar stud dBar stud dBar stud dBar stud dBar stud dBar stud dBar stud dBar stud dBar stud dBar stud dBar stud d d d d d d d d d d d (*3) d d (*3) d d (*3) d d (*3) d d (*3) d d (*3) d d (*3) d d (*3) d d (*3) d d (*3) d d (*3) d d (*3) d d (*3) d d (*3) d d (*3) d d (*3) d d d d d d d d d d d d d d d d d d d − (*5) − − d d − − − − − d − − − − − d d d d d − − − − − d d d d d d d (*6) d (*6) d (*6) d (*6) d d d d d d d d d d − − − − − d d d d d − − − − d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d − − − − − Self-declaration Self-declaration Self-declaration Self-declaration Self-declaration Recognition in process Recognition in process Recognition in process Recognition in process Recognition in process − − − − − (LR, ABS, GL) q q q q Electronic (effective value detection) Thermal-magnetic Electronic (effective value detection) Thermal-magnetic Thermal-magnetic Equipped Equipped Equipped Equipped Equipped 154 156 158 162 80-160 125-250
Notes: *1 The trip action characteristics differ between AC and DC for products that are compatible with both AC and DC. *2 Use two poles for three- and four-pole products. In this case, do not use the neutral pole of the four-pole products. If wired as shown on the right, three and four poles can be used for up to 400 and 500VDC, respectively. *3 The cassette type design makes it easy for customer to install. Available for installation on side below 250A frame (excluding UVT). *4 Use two poles for three- and four-pole products. In this case, do not use the neutral pole of the four-pole products. Not available for use with connection as shown on the right. *5 Solid state relay output is option. Please specify if other output is necessary. (Standard type is thus SLT equipped) AS for flush plate type, an outline differs from a standard. *6 Place an order of other models in conjunction with the circuit breaker. *7 Not isolation compatible. excluding 400 to 800A frame.
18
Line
Line
3-pole
Load
4-pole
Load
2 Detailed Specifications
1 Molded Case Circuit Breakers
NF-S (Standard class)
Adjustable 300 350 400 500 600 630 3 4 690 10/10 30/30 42/42 50/50 50/50 50/50 85/85 85/85 − 8 AC Compatible Possible 6,000 1,000 B 7.6 3 A 140 185 257 103 155 6.5 8.3 dBusbar terminal − − dBar stud dBar stud d d d (*3) d d (*3) d d (*3) d d d d d d (*5) − − d − d d (*6) d d d d − d d d d d d d d d d − Self-declaration Recognition in process − q Electronic (effective value detection) Equipped 164
800 NF800-SEW
800 NF800-SDW
Adjustable 400 450 (700) 800 500 600 700 800 3 4 2 690 690 10/10 − 30/30 − 42/42 − 50/50 − 50/50 − 50/50 − 85/85 − 85/85 − − 40/40 8 8 AC DC Compatible Compatible Possible Possible 4,000 4,000 500 500 B A 9.6 − 3 3 A N/A 210 280 210 275 275 103 103 155 155 10.9 14.2 9.0 dBusbar terminal dBusbar terminal − − − dBar stud dBar stud dBar stud d d d d (*3) d d d (*3) d d d (*3) d d d d d d d d − d (*5) − − − d d − d d d (*6) d(*6) d d d d d d − − d d d d d d d d d d d d d d d d − − Self-declaration Self-declaration Recognition in process Recognition in process − − q Electronic (effective value detection) Thermal-magnetic Equipped Equipped 166 168
1000 NF1000-SEW
1250 NF1250-SEW
Adjustable 500 600 700 800 900 1000 3 4 690 25/13 65/33 85/43 85/43 85/43 85/43 125/63 125/63 − 8 AC Compatible Possible 3,000 500 B 20 at 0.1 3 A 210 280 406 140 190 23.5 30.7 dBusbar terminal dBusbar terminal − − dBar stud dBar stud − d d d d d d d d d d d d (*5) − − − − − d (*6) d − − d − d d − d − d − Self-declaration Recognition in process − q Electronic (effective value detection) Equipped 172
Adjustable 600 700 800 1000 1200 1250 3 4 690 25/13 65/33 85/43 85/43 85/43 85/43 125/63 125/63 − 8 AC Compatible Possible 3,000 500 B 20 at 0.1 3 A 210 280 406 140 190 23.5 30.7 dBusbar terminal dBusbar terminal − − dBar stud dBar stud − d d d d d d d d d d d d (*5) − − − − − d (*6) d − − d − d d − d − d − Self-declaration Recognition in process − q Electronic (effective value detection) Equipped 172
1200 NF1250-SDW
1000 1250 2 690 − − − − − − − − 40/20 8 DC Compatible Possible 3,000 500 A − 3 N/A 210 406 140 190 22.0 dBusbar terminal − dBar stud d d d d d d − − − − d (*6) d − − d − d − d − d − Self-declaration − − Thermal-magnetic Equipped 174
1600 NF1600-SEW
Adjustable 800 1000 1200 1400 1500 1600 3 4 690 25/13 65/33 85/43 85/43 85/43 85/43 125/63 125/63 − 8 AC Compatible Possible 3,000 500 B 20 at 0.1 3 A 210 280 406 140 190 34.5 41.2 dBusbar terminal dBusbar terminal − dBar stud dBar stud − d d d d d d d d d d d (*5) − − − d (*6) d − − d − d d − − − − − Self-declaration Recognition in process − Electronic (effective value detection) Equipped 176
1600 NF1600-SDW
1600 2 690 − − − − − − − − 40/20 8 DC Compatible Possible 3,000 500 B − 3 A 210 406 140 190 32.0 dBusbar terminal − dBar stud − d d d d d − − − − d (*6) d − − d − d − − − − − Self-declaration − − magnetic Equipped 178
Remarks: 1. Products with rated current parenthesized are produced when an order is placed. 2. Specify “P-LT” when using a plug-in product with a lead-wire terminal block. 3. The circuit breaker has the rated short-circuit breaking capacity specified in the shaded cells.
19
2 1 Detailed Specifications
630 NF630-SEW
2
Detailed Specifications
Molded Case Circuit Breakers
1
NF-L / NF-H / NF-R (High-performance class) Frame (A) Model
50
60 NF63-HV
63
60
(63)
100 NF125-HV
125
125 NF125-LGV
125 NF125-HGV
125 NF125-RGV
15 16 20 30 32 40 125 50 60 63 75 80 100 2 3 4 2 3 4 690 690 10/8 10/8 30/23 30/23 50/38 50/38 50/38 50/38 50/38 50/38 50/38 50/38 100/75 100/75 100/75 100/75 − − 8 8 AC AC Compatible Compatible Possible Possible 25,000 25,000 10,000 10,000 A A 3 3 N/A N/A 90 120 90 120 130 130 68 68 90 90 0.8 1.0 1.3 0.8 1.0 1.3 dScrew terminal dScrew terminal d d dBar stud dBar stud d d d d d (*3) d d (*3) d d (*3) d d (*3) d d (*3) d d (*3) d d (*3) d d (*3) d d d d d − − − − d d − − d d − − d d d d d d d d − − d d d d d d d d d d d d d d d d d d d d d d d d d d d d − − Self-declaration Self-declaration Recognition in process Recognition in process − − q q Thermal-magnetic Thermal-magnetic Equipped Equipped 144
16-20 20-25 25-32 32-40 35-50 45-63 56-80 70-100 90-125 2 3 4 690 8/8 36/36 50/50 50/50 50/50 50/50 90/90 90/90 20/20 (300V) (*2) 8 AC/DC compatible Compatible Possible 50,000 30,000 A 3 N/A 105 140 165 68 92 1.4 1.6 2.0 d d dBar stud d d (*3) d d (*3) d d (*3) d d (*3) d d − − d − d − d d d d d d d d d d d d − Self-declaration Recognition in process (LR, ABS, GL) − Thermal-magnetic Equipped 152
16-20 20-25 25-32 32-40 35-50 45-63 56-80 70-100 90-125 2 3 4 690 10/8 50/38 65/65 70/70 75/75 75/75 100/100 100/100 40/40 (300V) (*2) 8 AC/DC compatible Compatible Possible 50,000 30,000 A 3 N/A 105 140 165 68 92 1.4 1.6 2.0 d d dBar stud d d (*3) d d (*3) d d (*3) d d (*3) d d − − − d − d d d d d d d d d d d d − Self-declaration Recognition in process (LR, ABS, GL) − Thermal-magnetic Equipped 152
16-20 20-25 25-32 32-40 40-50 50-63 63-80 80-100 100-125 2 3 690 – – 125/125 150/150 150/150 150/150 150/150 150/150 − 8 AC Compatible Possible 50,000 30,000 A 3 N/A 105 165 68 92 1.5 1.8 dScrew terminal d dBar stud d d (*3) d (*3) d (*3) d (*3) d − − − − d d d d d d d d d − d − Self-declaration Recognition in process (LR, ABS, GL) Thermal-magnetic Equipped 152
Image
10 15 16 20 25 30 32 40 50 2 3 4 690 2.5/2.5 7.5/7.5 10/8 10/8 10/8 10/8 25/19 25/19 7.5/7.5 (*5) 8 AC/DC compatible (*1) Compatible Possible 15,000 8,000 A 3 N/A 50 75 100 130 68 90 0.5 0.7 0.9 dScrew terminal d dRound stud d d (*3) d d (*3) d d (*3) d d (*3) d d d − − d − d − − d − d d − d d d d d d Terminal cover (TC-L, TC-S, TTC, BTC, PTC) 121 d d Rear stud (B-ST) d 94 Plug-in (PM) d d IEC 35mm rail mounting adapters 137 − d CE marking Self-declaration CCC recognition Recognition in process Marine use approval (NK, LR, ABS, GL) − q Automatic tripping device Thermal-magnetic Trip button Equipped Page of Characteristics and dimensions
Cassette-type Installation and accessories connections
Overall dimensions (mm)
Rated short-circuit breaking capacities (kA)
Rated current In (A) Rated ambient temperture 40°C (45°C for marine use) Number of poles Rated insulation voltage Ui (V) 690V 500V 440V 415V IEC 60947-2 AC EN 60947-2 400V (Icu/Ics) 380V 230V 200V DC 250V Rated impulse withstand voltage Uimp (kV) Current Suitability for isolation Reverse connection Without current Number of operating cycles With current (440VAC) Utilization category Pollution degree EMC environment condition (environment A or B) ca a a c b b c ca Mass of front-face type (kg) Front connection (F) Page Solderless (BOX) terminal (SL) Rear (B) 92 Plug-in (PM) Alarm switch (AL) Auxiliary switch (AX) 102 Shunt trip (SHT) Undervoltage trip (UVT) With lead-wire terminal block (SLT) 114 Pre-alarm (PAL) 116 Closed (S) (I) 130 Enclosure Dustproof Waterproof (W) Electrical operation device (NFM) 133 Mechanical Panel mounting 129 interlock (MI) (*4) Breaker mounting LC Handle lock 127 HL device HL-S (F) External 117 operating handle (V) External accessories
1 Detailed Specifications
2
2
3 4 690 2.5/2.5 7.5/7.5 10/8 10/8 10/8 10/8 25/19 25/19 7.5/7.5 (*5) 8 AC/DC compatible (*1) Compatible Possible 15,000 8,000 A 3 N/A 50 75 100 130 68 90 0.55 0.75 1.0 dScrew terminal d dRound stud d d (*3) d d (*3) d d (*3) d d (*3) d d d − − d − d − − d − d d − d d d d d d d d d d d − d Self-declaration Recognition in process − q Thermal-magnetic Equipped 142
2
3 4 690 2.5/2.5 7.5/7.5 10/8 10/8 10/8 10/8 25/19 25/19 7.5/7.5 (*5) 8 AC/DC compatible (*1) Compatible Possible 15,000 8,000 A 3 N/A 50 75 100 130 68 90 0.55 0.75 1.0 dScrew terminal d dRound stud d d (*3) d d (*3) d d (*3) d d (*3) d d d − − d − d − − d − d d − d d d d d d d d d d d − d Self-declaration Recognition in process − q Thermal-magnetic Equipped
Notes: *1 The trip action characteristics differ between AC and DC for products that are compatible with both AC and DC. *2 Use two poles for three- and four-pole products. In this case, do not use the neutral pole of the four-pole products. If wired as shown on the right, three and four poles can be used for up to 500 and 600VDC, respectively. *3 The cassette type design makes it easy for customer to install. Available for installation on side below 250A frame (excluding UVT). *4 Not isolation compatible, excluding 400 to 800A frame. *5 Use two poles for three- and four-pole products. In this case, do not use the neutral pole of the four-pole products. Not available for use with connection as shown on the right.
20
Line
Line
3-pole
Load
4-pole
Load
2 Detailed Specifications
1 Molded Case Circuit Breakers
NF-L / NF-H / NF-R (High-performance class)
16-32 32-63 63-125 3
4
690 10/8 50/38 65/65 70/70 75/75 75/75 100/100 100/100 − 8 AC Compatible Possible 25,000 10,000 A 3 A 105 140 165 68 92 1.7 2.2 dScrew terminal dScrew terminal d d dBar stud dBar stud d d d (*3) d d (*3) d d (*3) d d (*3) d d d d − − d − d d d d − d d d d d d d d d d d d − Self-declaration Recognition in process − (LR, ABS, GL) Electronic (effective value detection) Equipped 154
160 NF160-LGV
160 NF160-HGV
225
250 NF250-HV
250 NF250-LGV
250 NF250-HGV
250 NF250-RGV
125-160 140-200 125-160 140-200 125-160 160-200 125 150 160 250 175-250 175-250 200-250 175 200 225 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 690 690 690 690 690 690 690 8/8 10/8 10/8 10/8 8/8 10/8 − 36/36 50/38 50/38 50/38 36/36 50/38 − 50/50 65/65 65/65 65/65 50/50 65/65 125/125 50/50 70/70 70/70 70/70 50/50 70/70 150/150 50/50 75/75 75/75 75/75 50/50 75/75 150/150 50/50 75/75 75/75 75/75 50/50 75/75 150/150 90/90 100/100 100/100 100/100 90/90 100/100 150/150 90/90 100/100 100/100 100/100 90/90 100/100 150/150 20/20 (300V) (*2) 40/40 (300V) (*2) 40/40 (300V) (*2) 40/40 (300V) (*2) 20/20 (300V) (*2) 40/40 (300V) (*2) − 8 8 8 8 8 8 8 AC/DC compatible AC/DC compatible AC/DC compatible (*1) AC/DC compatible (*1) AC/DC compatible AC/DC compatible AC Compatible Compatible Compatible Compatible Compatible Compatible Compatible Possible Possible Possible Possible Possible Possible Possible 40,000 40,000 25,000 25,000 25,000 25,000 25,000 15,000 15,000 10,000 10,000 10,000 10,000 10,000 A A A A A A A 3 3 3 3 3 3 3 N/A N/A N/A N/A N/A N/A N/A 105 140 105 140 105 140 105 140 105 140 105 140 105 165 165 165 165 165 165 165 68 68 68 68 68 68 68 92 92 92 92 92 92 92 1.4 1.6 2.0 1.4 1.6 2.0 1.4 1.6 2.0 1.4 1.6 2.0 1.4 1.6 2.0 1.4 1.6 2.0 1.5 1.8 dScrew terminal dScrew terminal dScrew terminal dScrew terminal dScrew terminal dScrew terminal dBusbar terminal d d d d d d d d d dBar stud dBar stud dBar stud dBar stud dBar stud dBar stud dBar stud d d d d d d d d d d (*3) d d (*3) d d (*3) d d (*3) d d (*3) d d (*3) d d (*3) d (*3) d d (*3) d d (*3) d d (*3) d d (*3) d d (*3) d d (*3) d (*3) d d (*3) d d (*3) d d (*3) d d (*3) d d (*3) d d (*3) d (*3) d d (*3) d d (*3) d d (*3) d d (*3) d d (*3) d d (*3) d d d d d d d d d − − − − − − − − − − − − − − d d − − − − − − − d d d d d d − − − − − − − d d d d d d d d d d d d d d d d d d d d d d − − d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d − d d d d d d d d d d d d d d d d d − − − − − − − Self-declaration Self-declaration Self-declaration Self-declaration Self-declaration Self-declaration Self-declaration Recognition in process Recognition in process Recognition in process Recognition in process Recognition in process Recognition in process Recognition in process − − (LR, ABS, GL) (LR, ABS, GL) q q (LR, ABS, GL) (LR, ABS, GL) (LR, ABS, GL) Thermal-magnetic Thermal-magnetic Thermal-magnetic Thermal-magnetic Thermal-magnetic Thermal-magnetic Thermal-magnetic Equipped Equipped Equipped Equipped Equipped Equipped Equipped 152 152 148 152 152 152 125-160
125-160
Remarks: 1. Products with rated current parenthesized are produced when an order is placed. 2. Specify “P-LT” when using a plug-in product with a lead-wire terminal block. 3. The circuit breaker has the rated short-circuit breaking capacity specified in the shaded cells.
21
2 1 Detailed Specifications
125 NF125-HEV
2
Detailed Specifications
1
Molded Case Circuit Breakers
NF-H / NF-R (High-performance class) Frame (A) Model
250 NF250-HEV
400 NF400-HEW
630 NF400-REW
NF630-HEW
800 NF630-REW
NF800-HEW
NF800-REW
Image
Cassette-type Installation and accessories connections
Overall dimensions (mm)
Rated short-circuit breaking capacities (kA)
Rated current In (A) Rated ambient temperture 40°C (45°C for marine use) Number of poles Rated insulation voltage Ui (V) 690V 500V 440V 415V IEC 60947-2 AC EN 60947-2 400V (Icu/Ics) 380V 230V 200V DC 250V Rated impulse withstand voltage Uimp (kV) Current Suitability for isolation Reverse connection Without current Number of operating cycles With current (440VAC) Utilization category Rated short time with stand current Icu (kA) at 0.25s Pollution degree EMC environment condition (environment A or B) ca a a c b b c ca Mass of front-face type (kg) Front connection (F) Page Solderless (BOX) terminal (SL) Rear (B) 92 Plug-in (PM) Alarm switch (AL) Auxiliary switch (AX) 102 Shunt trip (SHT) Undervoltage trip (UVT) With lead-wire terminal block (SLT) 114 Pre-alarm (PAL) 116 Closed (S) (I) 130 Enclosure Dustproof Waterproof (W) Electrical operation device (NFM) 133 Mechanical Panel mounting 129 interlock (MI) (*4) Breaker mounting LC Handle lock 127 HL device HL-S (F) External 117 operating handle (V) Terminal cover (TC-L, TC-S, TTC, BTC, PTC) 121 Rear stud (B-ST) 94 Plug-in (PM) IEC 35mm rail mounting adapters 137 CE marking CCC recognition Marine use approval (NK, LR, ABS, GL) Automatic tripping device Trip button Page of Characteristics and dimensions External accessories
1 Detailed Specifications
2
Adjustable 200 225 Adjustable 200 225 250 300 350 400 250 300 350 400 3 4 3 4 3 690 690 690 10/8 35/18 − 50/38 50/50 70/35 65/65 65/65 125/63 70/70 70/70 125/63 75/75 70/70 125/63 75/75 70/70 125/63 100/100 100/100 150/75 100/100 100/100 150/75 − − − 8 8 8 AC AC AC Compatible Compatible Compatible Possible Possible Possible 25,000 6,000 6,000 10,000 1,000 1,000 A B B − 5 5 3 3 3 A A A 105 140 140 185 140 165 257 257 68 103 103 92 155 155 1.7 2.2 6.0 7.6 6.0 dScrew terminal dBusbar terminal dBusbar terminal − − − d d dBar stud dBar stud dBar stud dBar stud d d d d d d (*1) d d (*1) d d (*1) d (*1) d d (*1) d d (*1) d (*1) d d (*1) d d (*1) d (*1) d d d d d d d d d d d (*2) d (*2) − − − − − − d − − − d d d (*3) d (*3) d d d d d − − d d d − − d d d d d d d d d d d d d d d d d d d d d d d d d d − − − Self-declaration Self-declaration Self-declaration Recognition in process Recognition in process Recognition in process − − (LR, ABS, GL) q q Electronic (effective value detection) Electronic (effective value detection) Electronic (effective value detection) Equipped Equipped Equipped 154 158 158 80-160 125-250
Adjustable 300 350 Adjustable 300 350 400 500 600 630 400 500 600 630 3 4 3 690 690 35/18 − 50/50 70/35 65/65 125/63 70/70 125/63 70/70 125/63 70/70 125/63 100/100 150/75 100/100 150/75 − − 8 8 AC AC Compatible Compatible Possible Possible 6,000 6,000 1,000 1,000 B B 7.6 7.6 3 3 A A 140 185 140 257 257 103 103 155 155 6.5 8.3 6.0 dBusbar terminal dBusbar terminal dBusbar terminal − − − dBar stud dBar stud dBar stud d d d d (*1) d d (*1) d (*1) d d (*1) d (*1) d d (*1) d d d d d d d (*2) d (*2) − − − − − − d (*3) d (*3) d d d − d d − − d d d d d d d d d d d d d d d d d − − Self-declaration Self-declaration Recognition in process Recognition in process − q q Electronic (effective value detection) Electronic (effective value detection) Equipped Equipped 164 164
Notes: *1 The cassette type design makes it easy for customer to install. Available for installation on side below 250A frame (excluding UVT). *2 Solid state relay output is option. Please specify if other output is necessary. (Standard type is thus SLT equipped). *3 Place an order of other models in conjunction with the circuit breaker. *4 Not isolation compatible, excluding 400 to 800A frame.
Adjustable 400 450 Adjustable 400 450 500 600 700 800 500 600 700 800 3 4 3 690 690 15/15 − 50/50 70/35 65/65 125/63 70/70 125/63 70/70 125/63 70/70 125/63 100/100 150/75 100/100 150/75 − − 8 8 AC AC Compatible Compatible Possible Possible 4,000 4,000 500 500 B B 9.6 9.6 3 3 A A 210 280 210 275 275 103 103 155 155 10.9 14.2 10.9 dBusbar terminal dBusbar terminal dBusbar terminal − − − dBar stud dBar stud dBar stud d d d d (*1) d d (*1) d (*1) d d (*1) d (*1) d d (*1) d d d d d d d (*2) d (*2) − − − − − − d (*3) d (*3) d d d − d d − − d d d d d d d d d d d d d d d − − Self-declaration Self-declaration Recognition in process Recognition in process − q q Electronic (effective value detection) Electronic (effective value detection) Equipped Equipped 166 166 Line
Line
3-pole
22
Load
4-pole
Load
2 Detailed Specifications
1 Molded Case Circuit Breakers
NF-U (Ultra current-limiting class)
15 20 30 40 50 60 75 100 125 3 690 10/10 200/200 200/200 200/200 200/200 200/200 200/200 200/200 − 8 AC Compatible Possible 25,000 10,000 A − 3 N/A
2
90
1.35
250 NF250-UV
191 68 90 1.5 dScrew terminal dBar stud dBar stud d d (*1) d (*1) d (*1) d (*1) d − − − − d d − d d d d d d − d − Self-declaration − q Thermal-magnetic Equipped 146
125 150 175 200 225 250 4
2
120
3 690 15/15 200/200 200/200 200/200 200/200 200/200 200/200 200/200 − 8 AC Compatible Possible 25,000 10,000 A − 3 N/A 105
1.9
− d d d d
−
−
2.5
240 68 92 2.7 dScrew terminal dBar stud dBar stud d d (*1) d (*1) d (*1) d (*1) d − − − − d d − d d d d d d − d − Self-declaration − q Thermal-magnetic Equipped 150
4
140
3.7
− d d d d
−
−
400 NF400-UEW
800 NF800-UEW
Adjustable 200 225 250 300 350 400 3 4 690 − 170/170 200/200 200/200 200/200 200/200 200/200 200/200 − 8 AC Compatible Possible 6,000 1,000 B 5 3 A 140 280 297 322 200 252 16.2 25.4 dBusbar terminal − dBar stud − d d (*1) d (*1) d (*1) d d d (*2) − − − d (*3) d − − d d d − d d − − − Self-declaration − − q Electronic (effective value detection) Equipped 160
Adjustable 400 450 500 600 700 800 3 4 690 35/35 170/170 200/200 200/200 200/200 200/200 200/200 200/200 − 8 AC Compatible Possible 4,000 500 B 9.6 3 A 210 280 322 200 252 27.6 33.7 dBusbar terminal − dBar stud − d (*1) d (*1) d (*1) d d d (*2) − − − d (*3) d − − d d d − d − − − Self-declaration − − Electronic (effective value detection) Equipped 170
2 1 Detailed Specifications
125 NF125-UV
Remarks: 1. Products with rated current parenthesized are produced when an order is placed. 2. Specify “P-LT” when using a plug-in product with a lead-wire terminal block. 3. The circuit breaker has the rated short-circuit breaking capacity specified in the shaded cells.
23
2
Detailed Specifications
Earth Leakage Circuit Breakers
2
NV-C (Economy class) Harmonic Surge Ready Frame (A) Model
50
60 NV63-CV
63
100
125 NV125-CV
Image
2
Rated current In (A) Rated ambient temperture 40°C Number of poles
(5) (10) (15) 16 20 25 (30) 32 40 50 2 3 1f2W
Time-delay High-speed type type
Rated current sensitivity
AC
(mA)
Cassette-type accessories
Installation and connections
Overall dimensions (mm)
Rated short-circuit breaking capacities (kA)
at I∆n at 5I∆n Rated current sensitivity (mA) Max. operating time (s) (*3) Internal non-operating (s) (or more) Earth leakage indication system 440V 415V IEC 60947-2 400V EN 60947-2 AC 230V (Icu/Ics) 200V 100V Rated impulse withstand voltage Uimp (kV) Current Suitability for isolation Reverse connection (below 230VAC) Without current Number of operating cycles With current Utilization category Pollution degree EMC environment condition (environment A or B) ca a a c b b c ca Mass of front-face type (kg) Front connection (F) Page Solderless (BOX) terminal (SL) Rear (B) 92 Plug-in (PM) Alarm switch (AL) Auxiliary switch (AX) Shunt trip (SHT) 102 Undervoltage trip (UVT) Earth leakage alarm switch (EAL) With lead-wire terminal block (SLT) 114 Test button module (TBM) 115 Closed (S) (I) 130 Enclosure Dustproof Waterproof (W) Electrical operation device (NFM) 133 Mechanical Panel mounting 129 interlock (MI) (*7) Breaker mounting LC Handle lock 127 HL device HL-S (F) External 117 operating handle (V) Terminal cover (TC-L, TC-S, TTC, BTC, PTC) 121 Rear stud (B-ST) 94 Plug-in (PM) IEC 35mm rail mounting adapters 137 CE marking CCC recognition Marine use approval (NK, LR, ABS, GL) Automatic tripping device Trip button Page of Characteristics and dimensions External accessories
2 Detailed Specifications
Phase line (*1) Rated operational voltage Ue (V) (*2)
Max. operating time (s)
100-240
3f3W, 1f3W, 1f2W
100-440 30,100/200/500 30 selectable 0.1 0.04 − − − Mechanical type (button) − 2.5/2.5 − 2.5/2.5 − 5/5 7.5/7.5 7.5/7.5 7.5/7.5 6 AC Compatible Possible 10,000 6,000 A 2 A 75 130 68 90 0.7 0.75 dScrew terminal − dRound stud − d (*4) d (*4) d (*4) d (*4) − d d (*5) − − − − d d d d d d d d d − d Self-declaration − Recognition in process − Thermal-magnetic Equipped
(60) 3
1f2W
3f3W, 1f3W, 1f2W
100-240
100-440 30,100/200/500 30 selectable 0.1 0.04 − − − Mechanical type (button) − 2.5/2.5 − 2.5/2.5 − 5/5 7.5/7.5 7.5/7.5 7.5/7.5 6 AC Compatible Possible 10,000 6,000 A 2 A 75 130 68 90 0.7 0.75 dScrew terminal − dRound stud − d (*4) d (*4) d (*4) d (*4) − d d (*5) − − − − d d d d d d d d d − d Self-declaration − Recognition in process − Thermal-magnetic Equipped 180
Notes: *1 If using a 3-pole earth leakage circuit breaker as a 1-pole 2-phase device, connect the left and right poles and not the central pole. When wiring to singlephase 3-wire, connect the neutral line to the central pole. *2 In case of time delay type, rated voltage is 200-440VAC. *3 When the operating time are 0.45, 1.0 and 2.0 seconds, the Earth Leakage circuit breaker operates between 0.15 and 0.45 seconds, between 0.6 and 1.0 seconds and between 1.2 and 2.0 seconds respectively. *4 The cassette type design makes it easy for customer to install. Available for installation on side below 250A frame (excluding UVT). *5 Standard type is SLT equipped.
24
63
2
(60) 63 (75) 80 100
125
2
3
3
3
1f2W
3f3W, 1f3W, 1f2W
3f3W, 1f3W, 1f2W
3f3W, 1f3W, 1f2W
100-440 30,100/200/500 selectable 0.1 0.04 (100/200/500 selectable) (0.45/1.0/2.0 selectable) (0.1/0.5/1.0) Mechanical type (button) 10/5 10/5 10/5 30/15 30/15 30/15 6 AC Compatible Possible 10,000 6,000 A 2 A 90 130 68 90 1.0 dScrew terminal − dBar stud − d (*4) d (*4) d (*4) d (*4) − d d (*5) − − − d d d d d d d d d d − − Self-declaration Recognition in process − Thermal-magnetic Equipped
100-440 30,100/200/500 selectable 0.1 0.04 (100/200/500 selectable) (0.45/1.0/2.0 selectable) (0.1/0.5/1.0) Mechanical type (button) 10/5 10/5 10/5 30/15 30/15 30/15 6 AC Compatible Possible 10,000 6,000 A 2 A 90 130 68 90 1.0 dScrew terminal − dBar stud − d (*4) d (*4) d (*4) d (*4) − d d (*5) − − − d d d d d d d d d d − − Self-declaration Recognition in process − Thermal-magnetic Equipped
100-240
100-440 30,100/200/500 30 selectable 0.1 0.04 − − − Mechanical type (button) − 2.5/2.5 − 2.5/2.5 − 5/5 7.5/7.5 7.5/7.5 7.5/7.5 6 AC Compatible Possible 10,000 6,000 A 2 A 75 130 68 90 0.7 0.75 dScrew terminal − dRound stud − d (*4) d (*4) d (*4) d (*4) − d d (*5) − − − − d d d d d d d d d − d Self-declaration − Recognition in process − Thermal-magnetic Equipped
182 *6 Place an order of other models in conjunction with the circuit breaker. *7 Not isolation compatible, excluding 400 to 630A frame. *8 AC100V does not acquire the CCC certification.
2 Detailed Specifications
2 Earth Leakage Circuit Breakers
NV-C (Economy class) Harmonic Surge Ready 250 NV250-CV
400 NV400-CW
600
630 NV630-CW
125 150 175 200 225
250
250 300 350 400
500 600
(630)
3
3
3
3
3
3f3W, 1f3W, 1f2W
3f3W, 1f3W, 1f2W
3f3W, 1f3W, 1f2W
3f3W, 1f3W, 1f2W
3f3W, 1f3W, 1f2W
100-440 30,100/200/500 selectable 0.1 0.04 (100/200/500 selectable) (0.45/1.0/2.0 selectable) (0.1/0.5/1.0) Mechanical type (button) 15/12 25/19 25/19 36/27 36/27 36/27 6 AC Compatible Possible 8,000 4,000 A 2 A 105 165 68 92 1.7 dScrew terminal − dBar stud − d (*4) d (*4) d (*4) d (*4) − d d (*5) − − − d d d d d d d d d d − − TÜV approval Recognition in process − Thermal-magnetic Equipped
100-440 30,100/200/500 selectable 0.1 0.04 (100/200/500 selectable) (0.45/1.0/2.0 selectable) (0.1/0.5/1.0) Mechanical type (button) 15/12 25/19 25/19 36/27 36/27 36/27 6 AC Compatible Possible 8,000 4,000 A 2 A 105 165 68 92 1.7 dScrew terminal − dBar stud − d (*4) d (*4) d (*4) d (*4) − d d (*5) − − − d d d d d d d d d d − − TÜV approval Recognition in process − Thermal-magnetic Equipped
100-440 (30),100/200/500 selectable 0.1 0.04 (100/200/500 selectable) (0.45/1.0/2.0 selectable) (0.1/0.5/1.0) Mechanical type (button) 25/13 36/18 36/18 50/25 50/25 50/25 8 AC Compatible Possible 6,000 1,000 A 3 A 140 257 103 134 6.1 dBusbar terminal − dBar stud − d (*4) d (*4) d (*4) d − d d (*5) − − − d (*6) d d − d d d d d d − − Self-declaration Recognition in process − Thermal-magnetic Equipped 188
200-440
200-440
184 Remarks: 1. Products with rated current parenthesized are produced when an order is placed. 2. Specify “P-LT” when using a plug-in product with a lead-wire terminal block. 3. The circuit breaker has the rated short-circuit breaking capacity specified in the shaded cells.
4.
Rated operational voltage 100-240V 100-440V 200-440V
−
−
− − (100/200/500 selectable) (0.45/1.0/2.0 selectable) (0.1/0.5/1.0) Mechanical type (button) 36/18 36/18 36/18 50/25 50/25 − 8 AC Compatible Possible 6,000 1,000 A 3 A 140 257 103 155 6.9 dBusbar terminal − dBar stud − d (*4) d (*4) d (*4) d − d d (*5) − − − d (*6) d d − d d d d d d − − Self-declaration Recognition in process − Thermal-magnetic Equipped
− − (100/200/500 selectable) (0.45/1.0/2.0 selectable) (0.1/0.5/1.0) Mechanical type (button) 36/18 36/18 36/18 50/25 50/25 − 8 AC Compatible Possible 6,000 1,000 A 3 A 140 257 103 155 6.9 dBusbar terminal − dBar stud − d (*4) d (*4) d (*4) d − d d (*5) − − − d (*6) d d d d d d d d d − − Self-declaration Recognition in process − Thermal-magnetic Equipped
2 2 Detailed Specifications
225
192 Applicable circuit voltage 100/110/200/220/230/240V 100/110/200/220/240/254/265/380/400/415/440V 200/220/240/254/265/380/400/415/440V
Available voltage range 85-264V 85-484V 170-484V
25
2
Detailed Specifications
Earth Leakage Circuit Breakers
2
NV-S (Standard class) Harmonic Surge Ready Frame (A) Model
30
32
50
NV32-SV
60 NV63-SV
63
(60)
63
3
3
100
125 NV125-SV
125 NV125-SEV
Image
Rated current In (A) Rated ambient temperture 40°C Number of poles
(5) 6 10 (15) 16 20 25 (30) 3
Phase line (*1)
3f3W, 1f3W, 1f2W
Time-delay High-speed type type
Rated operational voltage Ue (V) (*2) Rated current sensitivity
AC
(mA)
Cassette-type accessories
Installation and connections
Overall dimensions (mm)
Rated short-circuit breaking capacities (kA)
at I∆n Max. operating time (s) at 5I∆n Rated current sensitivity (mA) Max. operating time (s) (*4) Internal non-operating (s) (or more) Earth leakage indication system 440V 415V IEC 60947-2 400V EN 60947-2 AC 230V (Icu/Ics) 200V 100V Rated impulse withstand voltage Uimp (kV) Current Suitability for isolation Reverse connection (below 230VAC) Without current Number of operating cycles With current Utilization category Rated short time withstand current Icu (kA) at 0.25s Pollution degree EMC environment condition (environment A or B) ca a a c b b c ca Mass of front-face type (kg) Front connection (F) Page Solderless (BOX) terminal (SL) Rear (B) 92 Plug-in (PM) Alarm switch (AL) Auxiliary switch (AX) Shunt trip (SHT) 102 Undervoltage trip (UVT) Earth leakage alarm switch (EAL) With lead-wire terminal block (SLT) 114 Test button module (TBM) 115 Closed (S) (I) 130 Enclosure Dustproof Waterproof (W) Electrical operation device (NFM) 133 Mechanical Panel mounting 129 interlock (MI) (*8) Breaker mounting LC Handle lock 127 HL device HL-S (F) External 117 operating handle (V) Terminal cover (TC-L, TC-S, TTC, BTC, PTC) 121 Rear stud (B-ST) 94 Plug-in (PM) IEC 35mm rail mounting adapters 137 CE marking CCC recognition Marine use approval (NK, LR, ABS, GL) Automatic tripping device Trip button Page of Characteristics and dimensions External accessories
2 Detailed Specifications
2
3
(5) (10) (15) 16 20 25 (30) 32 40 50 3
3f3W, 1f3W, 1f2W
3f3W, 1f3W, 1f2W
3f3W, 1f3W, 1f2W
3f3W, 1f3W, 1f2W
100-440 30,100/200/500 selectable 0.1 0.04 − − − Mechanical type (button) 7.5/7.5 7.5/7.5 7.5/7.5 15/15 15/15 15/15 6 AC Compatible Possible 15,000 8,000 A − 2 A 75 130 68 90 0.75 dScrew terminal − dRound stud − d (*5) d (*5) d (*5) d (*5) − d d (*6) − − − − d d d d d d d d d − d Self-declaration Recognition in process − Thermal-magnetic Equipped
100-440 30,100/200/500 selectable 0.1 0.04 − − − Mechanical type (button) 7.5/7.5 7.5/7.5 7.5/7.5 15/15 15/15 15/15 6 AC Compatible Possible 15,000 8,000 A − 2 A 75 130 68 90 0.8 dScrew terminal − dRound stud − d (*5) d (*5) d (*5) d (*5) − d d (*6) − − − − d d d d d d d d d − d Self-declaration Recognition in process − Thermal-magnetic Equipped 180
100-440 30,100/200/500 selectable 0.1 0.04 − − − Mechanical type (button) 7.5/7.5 7.5/7.5 7.5/7.5 15/15 15/15 15/15 6 AC Compatible Possible 15,000 8,000 A − 2 A 75 130 68 90 0.8 dScrew terminal − dRound stud − d (*5) d (*5) d (*5) d (*5) − d d (*6) − − − − d d d d d d d d d − d Self-declaration Recognition in process − Thermal-magnetic Equipped
(32)
100-440 100-440 30,100/200/500 30,100/200/500 selectable selectable 0.1 0.1 0.04 0.04 − − − − − − Mechanical type (button) Mechanical type (button) 5/5 5/5 5/5 5/5 5/5 5/5 10/10 10/10 10/10 10/10 10/10 10/10 6 6 AC AC Compatible Compatible Possible Possible 10,000 10,000 6,000 6,000 A A − − 2 2 A A 75 75 130 130 68 68 90 90 0.75 0.75 dScrew terminal dScrew terminal − − dRound stud dRound stud − − d (*5) d (*5) d (*5) d (*5) d (*5) d (*5) d (*5) d (*5) − − d d d (*6) d (*6) − − − − − − − − d d d d d d d d d d d d d d d d d d − − d d Self-declaration Self-declaration Recognition in process Recognition in process − − Thermal-magnetic Thermal-magnetic Equipped Equipped 180
Notes: *1 If using a 3-pole earth leakage cirsuit breaker as a 1-pole 2-phase device, connect the left and right poles and not the central pole. When wiring to singlephase 3-wire, connect the neutral line to the central pole. *2 In case of time delay type, rated voltage is 200-440VAC. *3 In case of time delay type, rated current is produced with 20 amp. or more. *4 When the operating time are 0.45, 1.0 and 2.0 seconds, the Earth Leakage circuit breaker operates between 0.15 and 0.45 seconds, between 0.6 and 1.0 seconds and between 1.2 and 2.0 seconds respectively.
26
(15) 16 20 (30) 32 40 50 125 (60) 63 (75) 80 100 (*3) 3 4 3 4 3f3W, 3f3W, 1f3W, 3f4W 1f3W, 3f4W 1f2W 1f2W 100-440 200-440 100-440 200-440 30,100/200/500 30,100/200/500 selectable selectable 0.1 0.1 0.04 0.04 (100/200/500selectable) (100/200/500selectable) (0.45/1.0/2.0selectable) (0.45/1.0/2.0selectable) (0.1/0.5/1.0) (0.1/0.5/1.0) Mechanical type (button) Mechanical type (button) 25/25 25/25 30/30 30/30 30/30 30/30 50/50 50/50 50/50 50/50 50/50 − 50/50 − 6 6 AC AC Compatible Compatible Possible Possible 25,000 25,000 10,000 10,000 A A − − 2 2 A A 90 120 90 120 130 130 68 68 90 90 1.1 1.4 1.1 1.4 dScrew terminal dScrew terminal − − dBar stud dBar stud − − d (*5) d d (*5) d d (*5) d d (*5) d d (*5) d d (*5) d d (*5) d d (*5) d − − d d d d d (*6) d (*6) − − − − − − d d d d d d − − d d d d d d d d d d d d d d d d − − − − Self-declaration Self-declaration Recognition in process Recognition in process − − Thermal-magnetic Thermal-magnetic Equipped Equipped 182
63-125 3
4
3f3W, 1f2W
3f4W
100-440 (30),100/200/500 selectable 0.1 0.04 (100/200/500selectable) (0.45/1.0/2.0selectable) (0.1/0.5/1.0) Mechanical type (button) 36/36 36/36 36/36 85/85 85/85 85/85 6 AC Compatible Possible 25,000 10,000 A − 2 A 105 140 165 68 92 1.9 2.5 d − dBar stud − d (*5) d d (*5) d d (*5) d d (*5) d − d d (*6) − d − d − d d d − d d d d d d d d − − Self-declaration Recognized − Electronic (effective value detection) Equipped 186
*5 Cassette type accessories are field mountable type. It can respend to adhesion attachment of a breaker as standard below 250A frame. (excluding UVT.) *6 Standard type is SLT equipped. *7 Place an order of other models in conjunction with the circuit breaker. *8 Not isolation compatible, excluding 400 to 800A frame. *9 AC100V does not acquire the CCC certification.
2 Detailed Specifications
2 Earth Leakage Circuit Breakers
NV-S (Standard class) Harmonic Surge Ready 250
250 NV250-SEV
400 NV400-SW
250
125-250
250 300 350 400
3
3
3
3f3W, 1f3W, 1f2W
3f3W, 1f2W
3f3W, 1f3W, 1f2W
100-440 (30),100/200/500 selectable 0.1 0.04 (100/200/500selectable) (0.45/1.0/2.0selectable) (0.1/0.5/1.0) Mechanical type (button) 36/36 36/36 36/36 85/85 85/85 85/85 6 AC Compatible Possible 25,000 10,000 A − 2 A 105 165 68 92 1.9 d − dBar stud − d (*5) d (*5) d (*5) d (*5) − d d (*6) d d d d d d d d d d d d d − − Self-declaration Recognized − Electronic (effective value detection) Equipped 186
100-440 (30),100/200/500 selectable 0.1 0.04 (100/200/500selectable) (0.45/1.0/2.0selectable) (0.1/0.5/1.0) Mechanical type (button) 42/42 45/45 45/45 85/85 85/85 85/85 8 AC Compatible Possible 6,000 1,000 A − 3 A 140 257 103 155 6.4 dBusbar terminal − dBar stud − d (*5) d (*5) d (*5) d − d d (*6) − − − d (*7) d d − d d d d d d − − Self-declaration Recognition in process − Thermal-magnetic Equipped 188
NV250-SV
125 150 175 200 225 3 3f3W, 1f3W, 1f2W
100-440 100-440 (30),100/200/500 (30),100/200/500 selectable selectable 0.1 0.1 0.04 0.04 (100/200/500selectable) (100/200/500selectable) (0.45/1.0/2.0selectable) (0.45/1.0/2.0selectable) (0.1/0.5/1.0) (0.1/0.5/1.0) Mechanical type (button) Mechanical type (button) 36/36 36/36 36/36 36/36 36/36 36/36 85/85 85/85 85/85 85/85 85/85 85/85 6 6 AC AC Compatible Compatible Possible Possible 25,000 25,000 10,000 10,000 A A − − 2 2 A A 105 105 165 165 68 68 92 92 1.9 1.9 dScrew terminal dScrew terminal − − dBar stud dBar stud − − d (*5) d (*5) d (*5) d (*5) d (*5) d (*5) d (*5) d (*5) − − d d d (*6) d (*6) − − − − − − d d d d d d d d d d d d d d d d d d d d − − − − TÜV approval TÜV approval Recognition in process Recognition in process − − Thermal-magnetic Thermal-magnetic Equipped Equipped 184
Remarks: 1. Products with rated current parenthesized are produced when an order is placed. 2. Specify “P-LT” when using a plug-in product with a lead-wire terminal block. 3. The circuit breaker has the rated short-circuit breaking capacity specified in the shaded cells.
400 NV400-SEW
4.
Adjustable 200 225 250 300 350 400 3 4 3f3W, 1f3W, 3f4W 1f2W 100-440 (30),100/200/500 selectable 0.1 0.04 (100/200/500selectable) (0.45/1.0/2.0selectable) (0.1/0.5/1.0) Mechanical type (button) 42/42 50/50 50/50 85/85 85/85 85/85 8 AC Compatible Possible 6,000 1,000 B 5 3 A 140 185 257 103 155 6.2 8.2 dBusbar terminal − dBar stud − d (*5) d (*5) d (*5) d − d d (*6) − − d − d d (*7) d d − d d d d d d d − Self-declaration Recognition in process − Electronic (effective value detection) Equipped 190
600
630 NV630-SW
500 600
(630)
3
3
3f3W, 1f3W, 1f2W
3f3W, 1f3W, 1f2W
200-440
200-440
−
−
− − − − 100/200/500selectable 100/200/500selectable 0.45/1.0/2.0selectable 0.45/1.0/2.0selectable 0.1/0.5/1.0 0.1/0.5/1.0 Mechanical type (button) Mechanical type (button) 42/42 42/42 50/50 50/50 50/50 50/50 85/85 85/85 85/85 85/85 − − 8 8 AC AC Compatible Compatible Possible Possible 6,000 6,000 1,000 1,000 A A − − 3 3 A A 140 140 257 257 103 103 155 155 6.9 6.9 dBusbar terminal dBusbar terminal − − dBar stud dBar stud − − d (*5) d (*5) d (*5) d (*5) d (*5) d (*5) d d − − d d d (*6) d (*6) − − − − − − d (*7) d (*7) d d d d − − d d d d d d d d d d d d − − − − Self-declaration Self-declaration Recognition in process Recognition in process − − Thermal-magnetic Thermal-magnetic Equipped Equipped 192
Rated operational voltage 100-440V 200-440V
630 NV630-SEW
800 NV800-SEW
Adjustable 300 350 Adjustable 400 450 400 500 600 630 500 600 700 800 3 4 3 3f3W, 3f3W, 1f3W, 1f3W, 3f4W 1f2W 1f2W 100-440 200-440 −
−
− − (100/200/500selectable) (0.45/1.0/2.0selectable) (0.1/0.5/1.0) Mechanical type (button) 42/42 50/50 50/50 85/85 85/85 85/85 8 AC Compatible Possible 6,000 1,000 B 7.6 3 A 140 185 257 103 155 7.1 8.9 dBusbar terminal − dBar stud − d (*5) d (*5) d (*5) d − d d (*6) − − d − d d (*7) d d − d d d d d d d − Self-declaration Recognition in process − Electronic (effective value detection) Equipped 194
− − 100/200/500selectable 0.45/1.0/2.0selectable 0.1/0.5/1.0 Mechanical type (button) 42/42 50/50 50/50 85/85 85/85 − 8 AC Compatible Possible 4,000 500 A 9.6 3 A 210 275 103 155 15.3 dBusbar terminal − dBar stud − d (*5) d (*5) d (*5) d − d d (*6) − − − d (*7) d d − d d d d d d − − Self-declaration Recognition in process − Electronic (effective value detection) Equipped 196
Applicable circuit voltage 100/110/200/220/240/254/265/380/400/415/440V 200/220/240/254/265/380/400/415/440V
Available voltage range 85-484V 170-484V
27
2 2 Detailed Specifications
225
2
Detailed Specifications
2
Earth Leakage Circuit Breakers
NV-H / NV-R (High-performance class) Harmonic Surge Ready Frame (A) Model
50
60 NV63-HV
63
(60)
63
3
3
3f3W, 1f3W, 1f2W
3f3W, 1f3W, 1f2W
100
125 NV125-HV
125 NV125-HEV
225
250
250 NV250-HEV
250
125-250
3
3
3f3W, 1f3W, 1f2W
3f3W, 1f2W
NV250-HV
Image
Rated current In (A) Rated ambient temperture 40°C Number of poles
(15) 16 20 (30) 32 40 50 3
Phase line (*1)
3f3W, 1f3W, 1f2W
Time-delay High-speed type type
Rated operational voltage Ue (V) (*2) Rated current sensitivity
AC
(mA)
Cassette-type accessories
Installation and connections
Overall dimensions (mm)
Rated short-circuit breaking capacities (kA)
at I∆n at 5I∆n Rated current sensitivity (mA) Max. operating time (s) (*4) Internal non-operating (s) (or more) Earth leakage indication system 440V 415V IEC 60947-2 400V EN 60947-2 AC 230V (Icu/Ics) 200V 100V Rated impulse withstand voltage Uimp (kV) Current Suitability for isolation Reverse connection (below 230VAC) Without current Number of operating cycles With current Utilization category Rated short time withstand current Icu (kA) at 0.25s Pollution degree EMC environment condition (environment A or B) ca a a c b b c ca Mass of front-face type (kg) Front connection (F) Page Solderless (BOX) terminal (SL) Rear (B) 92 Plug-in (PM) Alarm switch (AL) Auxiliary switch (AX) Shunt trip (SHT) 102 Undervoltage trip (UVT) Earth leakage alarm switch (EAL) With lead-wire terminal block (SLT) 114 Test button module (TBM) 115 Closed (S) (I) 130 Enclosure Dustproof Waterproof (W) Electrical operation device (NFM) 133 Mechanical Panel mounting 129 interlock (MI) (*7) Breaker mounting LC Handle lock 127 HL device HL-S (F) External 117 operating handle (V) Terminal cover (TC-L, TC-S, TTC, BTC, PTC) 121 Rear stud (B-ST) 94 Plug-in (PM) IEC 35mm rail mounting adapters 137 CE marking CCC recognition Marine use approval (NK, LR, ABS, GL) Automatic tripping device Trip button Page of Characteristics and dimensions External accessories
2 Detailed Specifications
2
Max. operating time (s)
100-440 100-440 100-440 30,100/200/500 30,100/200/500 30,100/200/500 selectable selectable selectable 0.1 0.1 0.1 0.04 0.04 0.04 − − − − − − − − − Mechanical type (button) 10/8 10/8 10/8 10/8 10/8 10/8 10/8 10/8 10/8 25/19 25/19 25/19 25/19 25/19 25/19 25/19 25/19 25/19 6 6 6 AC AC AC Compatible Compatible Compatible − − − 15,000 15,000 15,000 8,000 8,000 8,000 A A A − − − 2 2 2 A A A 75 75 75 130 130 130 68 68 68 90 90 90 0.75 0.8 0.8 dScrew terminal dScrew terminal dScrew terminal − − − dRound stud dRound stud dRound stud − − − d (*5) d (*5) d (*5) d (*5) d (*5) d (*5) d (*5) d (*5) d (*5) d (*5) d (*5) d (*5) − − − d d d d (*6) d (*6) d (*6) − − − − − − − − − − − − d d d d d d d d d d d d d d d d d d d d d d d d d d d − − − d d d Self-declaration Self-declaration Self-declaration Recognition in process Recognition in process Recognition in process − − − Thermal-magnetic Thermal-magnetic Thermal-magnetic Equipped Equipped Equipped 180
(15) 16 20 (30) 32 40 50 125 (60) 63 (75) 80 100 (*3) 3 4 3 4 3f3W, 3f3W, 1f3W, 3f4W 1f3W, 3f4W 1f2W 1f2W 100-440 200-440 100-440 200-440 30,100/200/500 30,100/200/500 selectable selectable 0.1 0.1 0.04 0.04 (100/200/500selectable) (100/200/500selectable) (0.45/1.0/2.0selectable) (0.45/1.0/2.0selectable) (0.1/0.5/1.0) (0.1/0.5/1.0) Mechanical type (button) Mechanical type (button) 50/38 50/38 50/38 50/38 50/38 50/38 100/75 100/75 100/75 100/75 100/75 − 100/75 − 6 6 AC AC Compatible Compatible − − 25,000 25,000 10,000 10,000 A A − − 2 2 A A 90 120 90 120 130 130 68 68 90 90 1.1 1.4 1.1 1.4 dScrew terminal dScrew terminal − − dBar stud dBar stud − − d (*5) d d (*5) d d (*5) d d (*5) d d (*5) d d (*5) d d (*5) d d (*5) d − − d d d d d (*6) d (*6) − − − − − − d d d d d d − − d d d d d d d d d d d d d d d d − − − − Self-declaration Self-declaration Recognition in process Recognition in process − − Thermal-magnetic Thermal-magnetic Equipped Equipped 182
Notes: *1 If using a 3-pole earth leakage cirsuit breaker as a 1-pole 2-phase device, connect the left and right poles and not the central pole. When wiring to singlephase 3-wire, connect the neutral line to the central pole. *2 In case of time delay type, rated voltage is 200-440VAC. *3 In case of time delay type, rated current is prodused with 20 amp. or more. *4 When the operating time are 0.45, 1.0 and 2.0 seconds, the Earth Leakage circuit breaker operates between 0.15 and 0.45 seconds, between 0.6 and 1.0 seconds and between 1.2 and 2.0 seconds respectively.
28
63-125 3
4
3f3W, 3f4W 1f2W 100-440 (30),100/200/500 selectable 0.1 0.04 (100/200/500selectable) (0.45/1.0/2.0selectable) (0.1/0.5/1.0) Mechanical type (button) 65/65 70/70 75/75 100/100 100/100 100/100 6 AC Compatible − 25,000 10,000 A − 2 A 105 140 165 68 92 1.9 2.5 d − dBar stud − d (*5) d d (*5) d d (*5) d d (*5) d − d d (*6) − − d − d d d − d d d d d d d d − − Self-declaration Recognized − Electronic (effective value detection) Equipped 186
125 150 175 200 225 3 3f3W, 1f3W, 1f2W
100-440 100-440 30,100/200/500 30,100/200/500 selectable selectable 0.1 0.1 0.04 0.04 (100/200/500selectable) (100/200/500selectable) (0.45/1.0/2.0selectable) (0.45/1.0/2.0selectable) (0.1/0.5/1.0) (0.1/0.5/1.0) Mechanical type (button) Mechanical type (button) 65/65 65/65 70/70 70/70 75/75 75/75 100/100 100/100 100/100 100/100 100/100 100/100 6 6 AC AC Compatible Compatible − − 25,000 25,000 10,000 10,000 A A − − 2 2 A A 105 105 165 165 68 68 92 92 1.8 1.8 dScrew terminal dScrew terminal − − dBar stud dBar stud − − d (*5) d (*5) d (*5) d (*5) d (*5) d (*5) d (*5) d (*5) − − d d d (*6) d (*6) − − − − − − d d d d d d d d d d d d d d d d d d d d − − − − Self-declaration Self-declaration Recognition in process Recognition in process − − Thermal-magnetic Thermal-magnetic Equipped Equipped 184
100-440 (30),100/200/500 selectable 0.1 0.04 (100/200/500selectable) (0.45/1.0/2.0selectable) (0.1/0.5/1.0) Mechanical type (button) 65/65 70/70 75/75 100/100 100/100 100/100 6 AC Compatible − 25,000 10,000 A − 2 A 105 165 68 92 1.9 d − dBar stud − d (*5) d (*5) d (*5) d (*5) − d d (*6) − d d d d d d d d d d d d − − Self-declaration Recognized − Electronic (effective value detection) Equipped 186
*5 Cassette type accessories are field mountable type. It can respend to adhesion attachment of a breaker as standard. (excluding UVT.) *6 Standard type is SLT equipped. *7 Not isolation compatible. *8 AC100V does not acquire the CCC certification.
2 Detailed Specifications
2 Earth Leakage Circuit Breakers
NV-H / NV-R (High-performance class) Harmonic Surge Ready 400 NV400-HEW
3 3f3W, 1f3W, 1f2W
630 NV630-HEW
800 NV800-HEW
Adjustable 200 225 250 300 350 400
Adjustable 300 350 400 500 600 630
Adjustable 400 450 500 600 700 800
4
3
3
3
3f4W
3f3W, 1f3W, 1f2W
3f3W, 1f3W, 1f2W
3f3W, 1f3W, 1f2W
100-440
100-440
100-440
100-440
(30), 100/200/500 selectable
(30), 100/200/500 selectable
−
−
0.1 0.04 (100/200/500 selectable) (0.45/1.0/2.0) (0.1/0.5/1.0) Mechanical type (button) 65/65 70/70 70/70 100/100 100/100 100/100 8 AC Compatible − 6,000 1,000 B 5 3 A 140 185 257 103 155 6.6 8.2 dBusbar terminal − dBar stud − d (*5) d (*5) d (*5) d − d d (*6) − − d − d d (*7) d d − d d d d d d − − Self-declaration Recognition in process − Electronic (effective value detection) Equipped 190
0.1 0.04 (100/200/500 selectable) (0.45/1.0/2.0) (0.1/0.5/1.0) Mechanical type (button) 125/63 125/63 125/63 150/75 150/75 150/75 8 AC Compatible − 6,000 1,000 B 5 3 A 140 257 103 155 6.6 dBusbar terminal − dBar stud − d (*5) d (*5) d (*5) d − d d (*6) − d d d (*7) d d − d d d d d d − − Self-declaration Recognition in process − Electronic (effective value detection) Equipped 190
− − (100/200/500 selectable) (0.45/1.0/2.0) (0.1/0.5/1.0) Mechanical type (button) 65/65 70/70 70/70 100/100 100/100 100/100 8 AC Compatible − 6,000 1,000 B 7.6 3 A 140 257 103 155 7.1 dBusbar terminal − dBar stud − d (*5) d (*5) d (*5) d − d d (*6) − d d d (*7) d d − d d d d d d − − Self-declaration Recognition in process − Electronic (effective value detection) Equipped 194
− − (100/200/500 selectable) (0.45/1.0/2.0 selectable) (0.1/0.5/1.0) Mechanical type (button) 65/65 70/70 70/70 100/100 100/100 100/100 8 AC Compatible − 4,000 500 B 9.6 3 A 210 275 103 155 15.3 dBusbar terminal − dBar stud − d (*5) d (*5) d (*5) d − d d (*6) − d d d (*7) d d − d d d d d d − − Self-declaration Recognition in process − Electronic (effective value detection) Equipped 196
Remarks: 1. Products with rated current parenthesized are produced when an order is placed. 2. The setting is set to 500mA and delivered when not specifying the rated current sensitivity and the time of time-delay type of operation to 2.0 seconds. 3. Specify “FP-LT” when using a flush plate product with a leadwire terminal block. 4. Specify “P-LT” when using a plug-in product with a lead-wire terminal block. 5. The circuit breaker has the rated short-circuit breaking capacity specified in the shaded cells.
6.
Rated operational voltage 100-440V 200-440V
Applicable circuit voltage 100/110/200/220/240/254/265/380/400/415/440V 200/220/240/254/265/380/400/415/440V
2 2 Detailed Specifications
Adjustable 200 225 250 300 350 400
400 NV400-REW
Available voltage range 85-484V 175-484V
29
2
Detailed Specifications
Motor Protection Breakers
3
NF-MB
Please specify MB
Frame (A) Model
30 A
Rated current In (A) Rated motor capacity (kW) Rated ambient temperture 40°C (45°C for marine use)
Number of poles Rated insulation voltage Ui (V)
Cassette-type Installation and accessories connections
Overall dimensions (mm)
Rated short-circuit breaking capacities (kA)
440V 415V AC 400V 380V 230V Rated impulse withstand voltage Uimp (kV) Current Suitability for isolation Reverse connection Without current Number of operating cycles With current (440VAC) Utilization category Pollution degree EMC environment condition (environment A or B) ca a a c b b c ca Mass of front-face type (kg) Front connection (F) Page Solderless (BOX) terminal (SL) Rear (B) 92 Plug-in (PM) Alarm switch (AL) Auxiliary switch (AX) 102 Shunt trip (SHT) (UVT) Undervoltage trip With lead-wire terminal block (SLT) 114 Closed (S) (I) 130 Enclosure Dustproof Waterproof (W) Electrical operation device (NFM) 133 Mechanical Panel mounting 129 interlock (MI) (*2) Breaker mounting LC Handle lock HL 127 device HL-S (F) External 117 operating handle (V) Terminal cover (TC-L, TC-S, TTC, BTC, PTC) 121 (B-ST) Rear stud 94 Plug-in (PM) IEC 35mm rail mounting adapters 137 CE marking CCC recognition Marine use approval (NK, LR, ABS, GL) Automatic tripping device Trip button Page of Characteristics and dimensions External accessories
3 Detailed Specifications
2
IEC 60947-2 EN 60947-2 (Icu/Ics)
32
50
NF32-SV 25 16 12 10 8 7.1 5 4
200/220V 400/440V kW kW 5.5 11 3.7 7.5 − 5.5 2.2 − − 3.7 1.5 − − 2.2 0.75 1.5
A 32
NF63-CV 200/220V 400/440V kW kW 7.5 15
A 45 40 32 25 16 12 10 8
200/220V 400/440V kW kW 11 22 − 18.5 7.5 15 5.5 11 3.7 7.5 − 5.5 2.2 − − 3.7
30
A 7.1 5 4
200/220V 400/440V kW kW 1.5 − − 2.2 0.75 1.5
A 100 90 71 63 45 (40) 32 (25) (16) (12.5)
200/220V 400/440V kW kW − 55 22 45 18.5 37 15 30 11 22 − 18.5 7.5 15 5.5 11 3.7 7.5 − 5.5
225 NF250-SV A 225 200 175 150 125
200/220V 400/440V kW kW 55 110 − − 45 90 37 75 30 −
3 3 3 3 3 3 500 500 500 500 500 500 2.5/2.5 2.5/2.5 2.5/2.5 7.5/7.5 25/25 36/36 2.5/2.5 2.5/2.5 2.5/2.5 7.5/7.5 30/30 36/36 5/5 5/5 5/5 7.5/7.5 30/30 36/36 5/5 5/5 5/5 7.5/7.5 30/30 36/36 7.5/7.5 7.5/7.5 7.5/7.5 15/15 50/50 85/85 8 8 8 8 8 8 AC AC AC AC AC AC Compatible Compatible Compatible Compatible Compatible Compatible Possible Possible Possible Possible Possible Possible 10,000 10,000 10,000 15,000 25,000 25,000 6,000 6,000 6,000 8,000 10,000 10,000 A A A A A A 3 3 3 3 3 3 N/A N/A N/A N/A N/A N/A 75 75 75 75 90 105 130 130 130 130 130 165 68 68 68 68 68 68 90 90 90 90 90 92 0.65 0.65 0.65 0.7 1.0 1.6 dScrew terminal dScrew terminal dScrew terminal dScrew terminal dScrew terminal dScrew terminal − − − − d d dRound stud dRound stud dRound stud dRound stud dBar stud dBar stud d d d d d d d (*1) d (*1) d (*1) d (*1) d (*1) d (*1) d (*1) d (*1) d (*1) d (*1) d (*1) d (*1) d (*1) d (*1) d (*1) d (*1) d (*1) d (*1) d (*1) d (*1) d (*1) d (*1) d (*1) d (*1) d d d d d d d d d d d d d d d d d d d d d d d d − − − − d (*3) d (*3) d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d d − − d d d d Self-declaration Self-declaration Self-declaration Self-declaration Self-declaration TÜV approval Recognition in process Recognition in process Recognition in process Recognition in process Recognition in process Recognition in process q q q q q q Thermal-magnetic Thermal-magnetic Thermal-magnetic Thermal-magnetic Thermal-magnetic Thermal-magnetic Equipped Equipped Equipped Equipped Equipped Equipped 142 142 144 148
Notes: *1 The cassette type design makes it easy for customer to install. Available for installation on side (excluding UVT). *2 Not isolation compatible. *3 Place an order of other models in conjunction with the circuit breaker.
100 NF125-SV
NF63-SV
Remarks: 1. The motor circuit breakers do not have an applicable rated motor capacity. Select a motor circuit breaker based on the total load current of the motor. 2. Products with rating parenthesized are produced when an order is placed. 3. Specify “P-LT” when using a plug-in product with a lead wire terminal block. 4. The circuit breaker has the rated short circuit breaking capacity specified in the shaded cells. 5. Please refer to “Table 4-17”, of Page 73 for details.
2
Detailed Specifications
4
UL 489 Listed Circuit Breakers
UL 489 Listed Molded Case Circuit Breakers Frame (A) Model
50 NF50-SVFU
100 NF100-CVFU
125 NF125-SVU
NF125-HVU
Image
4 Detailed Specifications
2
Front (F)
External accessories (*2) Cassette-type Installation and accessories (*2) connections
Overall dimensions (mm)
Rated short-circuit breaking capacities (kA)
15 20 30 40 50 60 Rated current In (A) (*4) (3) 5 10 15 20 30 60 (70) 75 (80) (90) 15 20 30 40 50 60 125 125 (70) 75 (80) (90) 100 40 50 100 (70) 75 (80) (90) 100 Rated ambient temperture 40°C (IEC 30°C) Number of poles 2 3 2 3 2 3 2 3 3 3 240 240 480 480 600Y/347 600Y/347 Rated AC (V) voltage DC (V) − − − − − − 600Y/347V − − − − 18 18 480V − − 30 30 50 50 UL 489 CSA C22.2 No.5-02 AC 480Y/277V − − − − − − 240V 14 14 50 50 100 100 120V − − − − − − DC 60V − − − − − − Rated insulation voltage Ui (V) 440 600 690 690 690 690 690V − − 8/4 8/4 10/5 10/5 500V − 7.5/4 18/9 18/9 25/13 25/13 440V 7.5/4 10/5 30/15 30/15 50/25 50/25 IEC 60947-2 AC 415V 10/5 10/5 30/15 30/15 50/25 50/25 EN 60947-2 400V 10/5 10/5 30/15 30/15 50/25 50/25 (Icu/Ics) 380V 10/5 10/5 30/15 30/15 50/25 50/25 230V 15/8 15/8 50/25 50/25 100/50 100/50 250V − − − − − − DC − − 60V − − − − Rated impulse withstand voltage Uimp (kV) 6 8 8 8 8 8 Current (*1) AC AC AC AC AC AC Suitability for isolation Compatible Compatible Compatible Compatible Compatible Compatible Reverse connection − Possible Possible Possible Possible Possible Utilization category A A A A A A Pollution degree 3 3 3 3 3 3 N/A N/A EMC environment condition (environment A or B) N/A N/A N/A N/A ca a a 36 54 50 75 90 90 90 90 c b 120 150 160 160 160 160 b c 68 68 68 68 68 68 ca 90 90 90 90 90 90 Mass of front-face type (kg) 0.3 0.45 0.55 0.8 1.0 1.1 1.0 1.1 1.1 1.1 Screw terminal (AMP-N) Page d d d d d d Solderless terminal (SL) − d d d d d (BAR) 92 − Bar d (*5) d d d d Power supply solderless load bar (SL/BAR) − d (*5, 6) d (*6) d (*6) d (*6) d (*6) Alarm switch (AL) d (*7) d (*7) d (*7) d (*7) d (*7) d (*7) Auxiliary switch (AX) d (*7) d (*7) d (*7) d (*7) d (*7) d (*7) 102 Shunt trip (SHT) d (*7) d (*7) d (*7) d (*7) d (*7) d (*7) (UVT) Undervoltage trip d d (*7) d (*7) d (*7) d (*7) d (*7) With lead-wire terminal block (SLT) 114 d d d d d d Mechanical interlock (MI) 129 − − − − − − (HL) d d d d d d Handle lock 127 device (HL-S) d d d d d d (F) d d d d d d External 117 operating handle (V) d d d d d d d d d d d d Terminal Large terminal cover (TC-L) 121 cover Small terminal cover (TC-S) 122 − (*3) − (*3) − (*3) − (*3) − (*3) − (*3) IEC 35mm rail mounting adapters 137 Standard accessory Standard accessory − − − − CE marking TÜV approval TÜV approval TÜV approval TÜV approval TÜV approval TÜV approval CCC recognition Recognition in process Recognition in process Recognition in process Recognition in process Recognition in process Recognition in process Automatic tripping device Thermal-magnetic Thermal-magnetic Thermal-magnetic Thermal-magnetic Thermal-magnetic Thermal-magnetic Trip button Equipped Equipped Equipped Equipped Equipped Equipped Page of Characteristics and dimensions 198 200 202 202
Notes: *1 The trip action characteristics differ between AC and DC for products that are compatible with both AC and DC. *2 These accessories differ from the general and CE/CCC products in specifications. Please consult us for details. *3 The standard structure conforms to IP20 (finger protection). *4 The rated ambient temperature for NF50-SVFU, NF100-CVFU, NF125-SVU and NF125-HVU is specified at 40°C also by IEC. *5 The circuit breakers with busbar terminals have insulation barriers. *6 Circuit breakers for power supply solderless load screw terminal (SL/ AMP-N) are available. In this case, a busbar terminal is not provided on the load side. *7 These cassette type circuit breakers can be installed by the customer. They can be installed with their side faces in close contact (except NF50-SVFU and UVT).
Remarks: 1. Products with rated current parenthesized are produced when an order is placed. 2. The circuit breaker has the rated short-circuit breaking capacity specified in the shaded cells. 3. The 3-pole circuit breakers can be used on single-phase circuits.
Line
Line
3-pole
Load
US UL Standard 489 UL File No.E167691 Body UL File No.E108284 Accessories Canada CSA Standard C22.2 No.5
31
4-po
2
Detailed Specifications
4
UL 489 Listed Circuit Breakers
UL 489 Listed Molded Case Circuit Breakers Frame (A) Model
225 NF225-CWU
250 NF250-SVU
NF250-HVU
Image
Front (F)
Overall dimensions (mm)
Rated short-circuit breaking capacities (kA)
Rated current In (A) (*5) Rated ambient temperture 40°C (IEC 30°C) Number of poles Rated AC (V) voltage DC (V) 600Y/347V 480V UL 489 CSA C22.2 No.5-02 AC 480Y/277V 240V 120V DC 60V Rated insulation voltage Ui (V) 690V 500V 440V IEC 60947-2 AC 415V EN 60947-2 400V (Icu/Ics) 380V 230V 250V (*3) DC 60V Rated impulse withstand voltage Uimp (kV) Current (*1) Suitability for isolation Reverse connection Utilization category Pollution degree EMC environment condition (environment A or B) ca a a c b b c ca Mass of front-face type (kg) Screw terminal (AMP-N) Page Solderless terminal (SL) (BAR) 92 Bar Power supply solderless load bar (SL/BAR) Alarm switch (AL) Auxiliary switch (AX) 102 Shunt trip (SHT) (UVT) Undervoltage trip With lead-wire terminal block (SLT) 114 Mechanical interlock (MI) 129 (HL) Handle lock 127 device (HL-S) (F) External 117 operating handle (V) Terminal Large terminal cover (TC-L) 121 cover Small terminal cover (TC-S) 122 IEC 35mm rail mounting adapters 137 CE marking CCC recognition Automatic tripping device Trip button Page of Characteristics and dimensions
Cassette-type Installation and External accessories (*2) accessories (*2) connections
4 Detailed Specifications
2
125 150 175 125 150 175 250 250 200 225 200 225 3 3 3 3 480 480 600Y/347 600Y/347 − − − − − − 18 18 35 35 50 50 − − − − 65 65 100 100 − − − − − − − − 690 690 690 690 8/4 8/4 10/5 10/5 25/13 25/13 36/18 36/18 36/18 36/18 50/25 50/25 36/18 36/18 50/25 50/25 36/18 36/18 50/25 50/25 36/18 36/18 50/25 50/25 65/33 65/33 100/50 100/50 − − − − − − − − 8 8 8 8 AC AC AC AC Compatible Compatible Compatible Compatible Possible Possible Possible Possible A A A A 3 3 3 3 N/A N/A N/A N/A 105 105 105 105 185 185 185 185 68 68 68 68 92 92 92 92 1.6 1.6 1.6 1.6 d d d d d d d d d d d d d(*8) d(*8) d(*8) d(*8) d(*7) d(*7) d(*7) d(*7) d(*7) d(*7) d(*7) d(*7) d(*7) d(*7) d(*7) d(*7) d(*7) d(*7) d(*7) d(*7) d d d d − − − − d d d d d d d d d d d d d d d d d d d d − (*4) − (*4) − (*4) − (*4) − − − − TÜV approval TÜV approval TÜV approval TÜV approval Recognition in process Recognition in process Recognition in process Recognition in process Thermal-magnetic Thermal-magnetic Thermal-magnetic Thermal-magnetic Equipped Equipped Equipped Equipped 206 206
125 150 175 200 225 3 240 − − − − 35 − − 600 − 10/5 15/8 18/9 18/9 18/9 35/18 10/5 − 6 AC/DC compatible Compatible Possible A 3 N/A 105 165 68 92 1.5 d − d − d d d d d d(*6) d d d d d − (*4) − TÜV approval Recognition in process Thermal-magnetic Equipped 204
Notes: *1 The trip action characteristics differ between AC and DC for products that are compatible with both AC and DC. *2 These accessories differ from the general products in specifications. Please consult us for details. *3 When using a 3-pole circuit breaker, use two poles. When wired as shown right, NF225-CWU can be used at up to 400 V DC. *4 Since NF225-CWU comes with a protective cover, it has an IP20 (finger protection) structure as standard. Other models have IP20 (finger protection) structures as standard. *5 The rated ambient temperature for NF250-SVU and NF250-HVU is specified at 40°C also by IEC. *6 Not isolation compatible. *7 These cassette type circuit breakers can be installed by the customer. They can be installed with their side faces in close contact (except UVT). *8 Circuit breakers for power supply solderless load screw terminal (SL/ AMP-N) are available. In this case, a busbar terminal is not provided on the load side.
Remarks: 1. Products with rated current parenthesized are produced when an order is placed. 2. The circuit breaker has the rated short-circuit breaking capacity specified in the shaded cells. 3. The 3-pole circuit breakers can be used on single-phase circuits.
Line
Line
3-pole
US UL Standard 489 UL File No.E167691 Body UL File No.E108284 Accessories Canada CSA Standard C22.2 No.5
32
Load
4-pole
L
2 Detailed Specifications
4 UL 489 Listed Circuit Breakers
UL 489 Listed Molded Case Circuit Breakers Frame (A) Model
400
630
NF400-SWU
NF400-HWU
NF630-SWU
NF630-HWU
250 300 350 400
250 300 350 400
500 600 630
500 600 630
3 600Y/347 − 20 35 − 65 − − 690 10/10(5/5)(*4) 30/30(25/25)(*4) 42/42(36/36)(*4) 45/45(36/36)(*4) 45/45(36/36)(*4) 50/50(42/42)(*4) 85/85(65/65)(*4 ) − − 8 AC Compatible Possible A 3 N/A 140 257 103 155 5.7 − d d(*5) d(*5) d(*3) d(*3) d(*3) d d d(*1)(*2) d(*6) − d d d − − TÜV approval Recognition in process Thermal-magnetic Equipped 208
3 600Y/347 − 25 65 − 100 − − 690 15/10 42/42 65/65 70/70 70/70 70/70 100/100 − − 8 AC Compatible Possible A 3 N/A 140 257 103 155 5.7 − − d(*5) − d(*3) d(*3) d(*3) d d d(*1)(*2) d(*6) − d d d − − TÜV approval Recognition in process Thermal-magnetic Equipped 208
3 600Y/347 − 20 35 − 85 − − 690 10/10 30/30 42/42 45/45 45/45 50/50 85/85 − − 8 AC Compatible Possible A 3 N/A 210 275 103 155 9.6 − d(*7) d(*5) d(*5) d(*3) d(*3) d(*3) d d d(*1)(*2) d(*6) − d d d − − TÜV approval Recognition in process Thermal-magnetic Equipped 210
3 600Y/347 − 25 65 − 100 − − 690 15/10 42/42 65/65 70/70 70/70 70/70 100/100 − − 8 AC Compatible Possible A 3 N/A 210 275 103 155 9.6 − − d(*5) − d(*3) d(*3) d(*3) d d d(*1)(*2) d(*6) − d d d − − TÜV approval Recognition in process Thermal-magnetic Equipped 210
Image
External accessories
Front (F)
Cassette-type Installation and accessories connections
Overall dimensions (mm)
Notes: *1 Not isolation compatible. *2 Not acquire the TÜV certification. *3 Cassette type accessories are field mountable type. It can respend to adhesion attachment of a breaker as standard below 250A frame. (excluding UVT.) *4 The values in parentheses apply to the circuit breakers with solderless terminals. *5 The circuit breakers with busbar terminals have insulation barriers. *6 Please consult us. (Models which are not UL or TUV certified but can be locked in the ON and OFF positions are available.) *7 Not available for 630A.
2 4 Detailed Specifications
Rated short-circuit breaking capacities (kA)
Rated current In (A) Rated ambient temperture 40°C Number of poles Rated AC (V) voltage DC (V) 600Y/347V 480V UL 489 CSA C22.2 No.5-02 AC 480Y/277V 240V 120V DC 60V Rated insulation voltage Ui (V) 690V 500V 440V IEC 60947-2 AC 415V EN 60947-2 400V (Icu/Ics) 380V 230V 250V DC 60V Rated impulse withstand voltage Uimp (kV) Current Suitability for isolation Reverse connection Utilization category Pollution degree EMC environment condition (environment A or B) ca a a c b c b ca Mass of front-face type (kg) Screw terminal (AMP-N) Page Solderless terminal (SL) (BAR) 92 Bar Power supply solderless load bar (SL/BAR) Alarm switch (AL) Auxiliary switch (AX) 102 Shunt trip (SHT) (UVT) Undervoltage trip With lead-wire terminal block (SLT) 114 Mechanical interlock (MI) 129 (HL) Handle lock 127 device (HL-S) (F) External 117 operating handle (V) Terminal Large terminal cover (TC-L) 121 cover Small terminal cover (TC-S) 122 IEC 35mm rail mounting adapters 137 CE marking CCC recognition Automatic tripping device Trip button Page of Characteristics and dimensions
Remarks: 1. The circuit breaker has the rated short-circuit breaking capacity specified in the shaded cells. 2. The 3-pole circuit breakers can be used on single-phase circuits.
US UL Standard 489 UL File No.E167691 Body UL File No.E108284 Accessories Canada CSA Standard C22.2 No.5
33
2
Detailed Specifications
4
UL 489 Listed Earth Leakage Circuit Breakers
UL 489 Listed Earth Leakage Circuit Breakers (Harmonic Surge Ready) Frame (A) Model
50 NV50-SVFU
100 NV100-CVFU
125
250
NV125-SVU
NV125-HVU
NV250-SVU
NV250-HVU
Image
High-speed type
Rated current In (A) Rated ambient temperture 40°C Number of poles Phase line (*1) UL 489 Rated operational IEC 60947-2 voltage AC V EN 60947-2 Rated current sensitivity In mA
Front (F)
Overall dimensions (mm)
Rated short-circuit breaking capacities (kA)
Pickup current, UL 1053 Max. operating time (s) at 5ln (*4) Earth leakage indication system 480V UL 489 240V AC CSA C22.2 No.5-02 120V 440V IEC 60947-2 400V EN 60947-2 AC 230V (Icu/Ics) 100V Rated impulse withstand voltage Uimp (kV) Suitability for isolation Reverse connection (below 240VAC) Utilization category Pollution degree EMC environment condition (environment A or B) ca a a c b b c ca Mass of front-face type (kg) Screw terminal (AMP-N) Page Solderless terminal (SL) (BAR) 92 Bar Power supply solderless load bar (SL/BAR) Alarm switch (AL) Auxiliary switch (AX) 102 Shunt trip (SHT) (UVT) Undervoltage trip With lead-wire terminal block (SLT) 114 Test button module (TBM) 115 Mechanical interlock (MI) 129 (HL) Handle lock 127 device (HL-S) (F) External 117 operating handle (V) Terminal Large terminal cover (TC-L) 121 cover Small terminal cover (TC-S) 122 IEC 35mm rail mounting adapters 137 CE marking CCC recognition Automatic tripping device Trip button Page of Characteristics and dimensions
Cassette-type Installation and External accessories (*2) accessories (*2) connections
4 Detailed Specifications
2
(5) (10) 15 20 30 40 50 2 3 1f2W 3f3W, 1f2W 120-240 100-240
100-440
60 (70) 75 (80) (90) 100 3 3f3W, 1f2W 120-240 100-440
100-440
30, 50, 100/200/500 selectable 75% of ln 75% of ln 0.04 0.04 Display window Mechanical type (button) − − 14 14 14 14 − 7.5/4 10/5 − 10/5 10/5 15/8 15/8 15/8 15/8 15/8 15/8 4 6 6 Compatible Compatible − Possible A A 2 2 A A 36 54 75 120 150 68 68 90 90 0.4 0.5 0.9 d d − d − d(*5) − d(*5, *6) − d(*8) d(*8) − d(*8) d(*8) − d(*8) d(*8) − d d(*8) − d d − d(*9) − − d d d d d d d d d d − (*3) d(*3) Standard accessory Standard accessory TÜV approval TÜV approval Recognition in process Recognition in process Thermal-magnetic Thermal-magnetic Equipped Equipped 198 200 30 50
30 50 100
Notes: *1 If using a 3-pole earth leakage circuit breaker as a 1-pole 2-phase device, connect the left and right poles and not the central pole. *2 These are different from general models in specifications. Consult us for the details. *3 The standard structure conforms to IP20 (finger protection). *4 The maximum operating time is 0.1 according to UL 1053. *5 The circuit breakers with busbar terminals have insulation barriers. *6 Circuit breakers for power supply solderless load screw terminal (SL/ AMP-N) are available. In this case, a bar terminal is not provided on the load side. *7 Circuit breakers for 100 V AC do not have obtained CCC certificate. *8 These cassette type accessories can be installed by the customer. They can be installed with their side faces in close contact with circuit breakers (except NV50-SVFU and UVT). *9 Standard type is SLT equipped.
15 20 30 (40) 15 20 30 (40) 125 150 175 125 150 175 125 125 250 250 50 60 75 100 50 60 75 100 200 225 200 225 3 3 3 3 3 3 3 3 3f3W, 1f2W 3f3W, 1f2W 3f3W, 1f2W 3f3W, 1f2W 3f3W, 1f2W 3f3W, 1f2W 3f3W, 1f2W 3f3W, 1f2W 120-480 120-480 120-480 120-480 120-480 120-480 120-480 120-480 100-440
30, 50, 100/200/500 30, 50, 100/200/500 selectable selectable 75% of ln 75% of ln 0.04 0.04 Mechanical type (button) Mechanical type (button) 30 30 50 50 50 50 30/15 30/15 30/15 30/15 50/25 50/25 50/25 50/25 6 6 Compatible Compatible Possible Possible A A 2 2 A A 90 90 160 160 68 68 90 90 1.2 1.2 d d d d d d d(*6) d(*6) d(*8) d(*8) d(*8) d(*8) d(*8) d(*8) d(*8) d(*8) d d d(*9) d(*9) − − d d d d d d d d d d − (*3) − (*3) − − TÜV approval TÜV approval Recognition in process Recognition in process Thermal-magnetic Thermal-magnetic Equipped Equipped 202
100-440
100-440
30, 50, 100/200/500 30, 50, 100/200/500 selectable selectable 75% of ln 75% of ln 0.04 0.04 Mechanical type (button) Mechanical type (button) 50 50 100 100 100 100 50/25 50/25 50/25 50/25 100/50 100/50 100/50 100/50 6 6 Compatible Compatible Possible Possible A A 2 2 A A 90 90 160 160 68 68 90 90 1.2 1.2 d d d d d d d(*6) d(*6) d(*8) d(*8) d(*8) d(*8) d(*8) d(*8) d(*8) d(*8) d d d(*9) d(*9) − − d d d d d d d d d d − (*3) − (*3) − − TÜV approval TÜV approval Recognition in process Recognition in process Thermal-magnetic Thermal-magnetic Equipped Equipped 202
100-440
100-440
30, 50, 100/200/500 30, 50, 100/200/500 selectable selectable 75% of ln 75% of ln 0.04 0.04 Mechanical type (button) Mechanical type (button) 35 35 65 65 65 65 36/18 36/18 36/18 36/18 65/33 65/33 65/33 65/33 6 6 Compatible Compatible Possible Possible A A 2 2 A A 105 105 185 185 68 68 92 92 1.8 1.8 d d d d d d d(*6) d(*6) d(*8) d(*8) d(*8) d(*8) d(*8) d(*8) d(*8) d(*8) d d d(*9) d(*9) − − d d d d d d d d d d − (*3) − (*3) − − TÜV approval TÜV approval Recognition in process Recognition in process Thermal-magnetic Thermal-magnetic Equipped Equipped 206
100-440
100-440
30, 50, 100/200/500 30, 50, 100/200/500 selectable selectable 75% of ln 75% of ln 0.04 0.04 Mechanical type (button) Mechanical type (button) 50 50 100 100 100 100 50/25 50/25 50/25 50/25 100/50 100/50 100/50 100/50 6 6 Compatible Compatible Possible Possible A A 2 2 A A 105 105 185 185 68 68 92 92 1.8 1.8 d d d d d d d(*6) d(*6) d(*8) d(*8) d(*8) d(*8) d(*8) d(*8) d(*8) d(*8) d d d(*9) d(*9) − − d d d d d d d d d d − (*3) − (*3) − − TÜV approval TÜV approval Recognition in process Recognition in process Thermal-magnetic Thermal-magnetic Equipped Equipped 206
Remarks: 1. Products with rated current parenthesized are produced when an order is placed. 2. Rated operational voltage Applicable circuit voltage Available voltage range 120-240V (UL) 120-240-480V (UL) 240V (UL) 100-230V (IEC) 100-240V (IEC) 100-230-400-440V (IEC) 100-440V (IEC) 230-400-440V (IEC)
120/240V 120/240/480V 240V 100/110/200/220/230V 100/110/200/220/230/240V 100/110/200/220/ 230/240/254/265/ 380/400/415/440V 230/240/254/265/ 380/400/415/440V
66-264V 66-528V 132-264V 85-253V 85-264V 85-484V 195-484V
US UL Standard 489 UL File No.E167691 Body UL File No.E108284 Accessories Canada CSA Standard C22.2 No.144 C22.2 No.5
34
2
Detailed Specifications
5
Measuring Display Unit Breakers
MDU Breakers Frame (A) Model
250 400 630 800 NF250-SEV with MDU NF250-HEV with MDU NF400-SEP with MDU NF400-HEP with MDU NF630-SEP with MDU NF630-HEP with MDU NF800-SEP with MDU NF800-HEP with MDU
Image
Phase line
External accessories (*2)
Cassette-type accessories
Installation and connections
Overall dimensions (mm)
Rated short-circuit breaking capacities (kA)
Rated insulation voltage Ui (V) 690V 500V 440V 415V IEC 60947-2 AC 400V (Icu/Ics) 380V 230V 200V 100V Rated impulse withstand voltage Uimp (kV) Current Suitability for isolation Reverse connection (below 240VAC) Without current Number of operating cycles With current Utilization category Pollution degree EMC environment condition (environment A or B) ca a a c b b c ca Mass of front-face type (Breaker mounting) (kg) MDU installation Front (F) Page Rear (*3) (B) 92 Plug-in (PM) Alarm switch (AL) Auxiliary switch (AX) Shunt trip (SHT) 102 (UVT) Undervoltage trip MDU transform AL, AX, AL + AX (MG) With lead-wire terminal block (SLT) 114 Alarm contact Pre-alarm (PAL) 116 output (*5) Trip-indicator (TI) Electrical operation device (*6) (NFM) 133 Panel mounting Mechanical 129 interlock (MI) (*7) Breaker mounting LC Handle lock HL 127 device HL-S (F) External 117 operating handle (V) TC-L TC-S Terminal 121 cover TTC BTC Rear stud (B-ST) 94 Automatic tripping device MDU measurement specifications Trip button Page of Characteristics and dimensions
Adjustable 125-250A Adjustable 200 225 250 Adjustable 300 350 400 Adjustable 400 450 500 500 (12.5A Step) 300 350 400 500 600 630 600 700 800 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3f3W, 3f3W, 3f3W, 3f3W, 3f3W, 3f3W, 3f3W, 3f3W, 1f3W, 3f4W 1f3W, 3f4W 1f3W, 3f4W 1f3W, 3f4W 1f3W, 3f4W 1f3W, 3f4W 1f3W, 3f4W 1f3W, 3f4W 1f2W 1f2W 1f2W 1f2W 1f2W 1f2W 1f2W 1f2W 690 690 690 690 8/8 10/8 10/10 10/10 10/10 15/15 10/10 15/15 18/18 30/23 30/30 50/50 30/30 50/50 30/30 50/50 36/36 50/50 42/42 65/65 42/42 65/65 42/42 65/65 36/36 70/70 45/45 70/70 45/45 70/70 45/45 70/70 36/36 75/75 45/45 70/70 45/45 70/70 45/45 70/70 36/36 75/75 45/45 70/70 45/45 70/70 45/45 70/70 85/85 100/100 85/85 100/100 85/85 100/100 85/85 100/100 85/85 100/100 85/85 100/100 85/85 100/100 85/85 100/100 − − − − − − − − 8 8 8 8 AC AC AC AC Compatible Compatible Compatible Compatible − − − − 25,000 6,000 6,000 4,000 10,000 1,000 1,000 500 A B B B 3 3 3 3 A A A A 105 140 105 140 140 185 140 185 210 280 210 280 210 280 210 280 165 257 275 275 68 103 103 103 92 155 155 155 1.8 2.3 1.8 2.3 6.2 8 6.2 8 10.7 13.8 10.7 13.8 11.1 14.4 11.1 14.4 Breaker mounting, Panel mounting (*1) Breaker mounting, Panel mounting (*2) d d d d d d d d d d d d d d − − − − d(*4) d d(*4) d d(*4) d(*4) d(*4) d(*4) d d(*4) d d(*4) d(*4) d(*4) d(*4) d d(*4) d d(*4) d(*4) d(*4) d d d d d d d d(*4) d d(*4) d d(*4) d(*4) d(*4) d d d d d d d d PAL 1a d PAL 1a d PAL 1a d PAL 1a − d PAL 1a, OAL 1a d PAL 1a, OAL 1a d PAL 1a, OAL 1a Available only for the MDU panel mounting type Available only for the MDU panel mounting type. Disavailable alarm contact output. d d d d − − Available only for the MDU panel mounting type d(*9) d(*9) − − − d d d d d Available only for the MDU panel mounting type Available only for the MDU panel mounting type Available only for the MDU panel mounting type Available only for the MDU panel mounting type d(*8) d d(*8) d − d(*8) d d(*8) d d(*8) d(*8) d(*8) d(*8) d(*8) Available only for the MDU panel mounting type and line side d(*8) d d(*8) d − − − d d(*8) d d Electronic (effective value detection) Electronic (effective value detection) Electronic (effective value detection) Electronic (effective value detection) See. 36 Equipped Equipped Equipped Equipped 212 214 216 216
Notes: *1 In the case of panel mounting, the panel holder plate, the screws and the MDU connection cable (2m) are packed as standard. The MDU connection cable of 0.5m, 3m, 5m and 10m can be specified when ordering. And dimension of the front panel drilling of the breaker is different between breaker mounting and panel mounting. *2 In the case of panel mounting, the panel holder plate, the nuts and the MDU connection cable (2m) are packed as standard. The MDU connection cable of 0.5m, 3m, 5m and 10m can be specified when ordering. *3 For 250AF breakers, the studs are packed as standard. For 400/630/800AF breakers, please specify the installation angle of the studs because it is installed to the breaker before shipping. *4 It can be installed to the breaker by each customer. *5 In the case of the breaker with alarm contact output, the module (terminal) is attached to the right side of the breaker and the control power (AC/DC 100-240V 50-60Hz 5VA) is needed. The Output function for alarm output of PAL can set “Self-holding” or “Auto-reset”. Default setup is “Auto-reset”. *6 For 250AF of electrical operation device, AL is used for the trip indication as standard. The breaker with alarm output contact is not available. *7 Not isolation compatible. *8 In the case of breaker mounting, the terminal cover is special type for MDU breaker. *9 Available only for the MDU panel mounting type.
35
2 5 Detailed Specifications
Rated current In (A) Rated ambient temperture 40°C Number of poles
2
Detailed Specifications
5
Measuring Display Unit Breakers
Measuring Display Unit Breakers (Circuit Breakers with Measuring Display Unit)
5 Detailed Specifications
2
dThree major features of Measuring Display Unit Breakers 1. Saving of space and labor for installation 2. Improved and diversified functions 3. Provision of total cost advantages Measuring Display Unit Breakers with built-in VT and CT and Measuring Display Unit realize measurement, display and transmission of electric circuit information in small space with less installation and wiring work and provide total cost advantages. The Measuring Display Unit Breakers full of functions in small bodies are suitable for monitoring and protection of electric circuits and maintenance of equipment. A wide variety of models applicable to various networks supports the customers’ energy saving activities through detailed energy control as energy saving supporting devices.
dSimply realizing measurement and monitoring of electric circuits for supporting various types of energy saving control
The circuit breakers measure and display the load current, line voltage, electric power, electric energy, harmonic current, leak current and power factor to realize detailed energy control. They support customers’ energy saving control.
WS-V Series Measuring Display Unit Breakers Applicable models
Examples of installation of measuring display unit Breaker mounting Panel mounting
NF250-SEV with MDU, NF250-HEV with MDU
dThe measuring display unit can be installed on the body or panel.
Note: The size of holes in the face board of the circuit breaker body varies depending on whether the measuring display unit is installed on the body or the panel.
rModel list
rMeasuring Display Unit cable list
Model type
Type name
Type name
Cable length
CC-Link communication
MDU-DP-C
MDU-DP-CB-2M
2m
Electric energy pulse output
MDU-DP-P
MDU-DP-CB-3M
3m
No transmission
MDU-DP-N
MDU-DP-CB-5M
5m
MDU-DP-CB-10M
10m
W & WS Series Measuring Display Unit Breakers
Examples of installation of measuring display unit Breaker mounting Panel mounting
Applicable models NF400-SEP with MDU, NF400-HEP with MDU, NF630-SEP with MDU, NF630-HEP with MDU, NF800-SEP with MDU, NF800-HEP with MDU
dThe measuring display unit can be installed on the body or panel.
rModel list Model type
Type name
Remarks
CC-Link communication
MDU-AC
• The model names do not include .
Electric energy pulse output MDU-AP No transmission
MDU-AN
• When installing the Measuring Display Unit on the body, specify the A frame type in . For example, when the circuit breaker NF400-SEP with MDU and the Measuring Display Unit with CC-Link communication are combined, the model name is MDU-AC400. If 630A frame or 800A frame is used, specify 630 or 800 in . • When installing the Measuring Display Unit on the panel, specify the cable length (0.5 m, 2 m, 3 m, 5 m or 10 m) in . For example, when the Measuring Display Unit with CC-Link communication is installed on the panel with a 3-m cable, the model name is MDU-AC-PANEL 3M.
36
2 Detailed Specifications 5 Measuring Display Unit Breakers
dSpecifications for Measuring Display Unit (1) The measurement and display items vary depending on the model or frame A. (For the measurement accuracy, please refer to page 39.) Table 2-1 Display Measurement and memory items (accuracy) (*1) (*2) Each phase Present value General (average value) (*5) Phase with max. value Load current Present value of demand Each phase (±1.0%) (*4) Phase with max. value Max. demand value among all phases Time of occurrence of max. demand value among all phases Between each lines Present value Line voltage General (average value) (*5) (±1.0%) Max. value among all lines Time of occurrence of max. value among all lines Fundamental wave of each phase Present value Each order of each phase General of each phase (*6) Max. value of fundamental wave among all phases Time of occurrence of max. value of fundamental wave among all phases Max. value in each order of each phase Harmonic current Time of occurrence of max. value in each order of each phase (±2.5%) General of each phase (*6) Demand value (*4) General max. value among all phases Time of occurrence of general max. value among all phases General distortion factor of each phase Content in each order of each phase Present value Electric power Present value (±1.5%) Demand value (*4) Max. value Time of occurrence of max. value Present value Present value Reactive power Demand value (*4) Max. value (±2.5%) Time of occurrence of max. value Integrated value Electric energy Amount for last 1 hour (±2.0%) Max. value of amount for 1 hour (*7) Time of occurrence of max. value of amount for 1 hour Integrated value Reactive energy Amount for last 1 hour (±3.0%) Max. value of amount for 1 hour (*7) Time of occurrence of max. value of amount for 1 hour Fault current (accuracy: ±15%) Cause of fault (*8) Cause of fault Present value Power factor Max. value (±5.0%) Time of occurrence of max. value Frequency (±2.5%) Present value PAL, OVER, Alarm of circuit breaker IDM_AL, ILA_AL, IUB_AL, (*9) Neutral line open phase alarm Tripping state of circuit breaker (AL) ON/OFF state of circuit breaker (AX) State of Number of times of tripping of circuit breaker circuit breaker Number of times of opening and closing of circuit breaker Time setting
With CC-Link Storage communication (*3) Communication
−
− − − − − − − − − − − − − − − − − − − − −
− − − −
−
− − − −
− − −
−
Demand time limit setting (*4)
IDM_AL (current demand alarm)
ILA_AL (current open phase alarm)
IUB_AL (unbalanced current alarm)
Neutral line open phase alarm
Phase switching setting Alarm retention (self-retention or automatic reset) setting Phase and wire type Electric energy arbitrary setting Reactive energy arbitrary setting Display direction
Default settings
Remarks
2 5 Detailed Specifications
Model
Notes:
Applicable models NF250-SEV with MDU, NF250-HEV with MDU
Value accumulated from previous reset to present
Value accumulated from previous reset to present Information on fault after previous reset or last fault, and cause of fault (continuously monitored)
The PAL functions are enabled when the MDU breaker with PAL module (option) is used. The neutral line open phase alarm is given only on the display. On installation of alarm switch for transmission with Measuring Display Unit (option) On installation of auxiliary switch for transmission with Measuring Display Unit (option) On installation of alarm switch for transmission with Measuring Display Unit (option) On installation of auxiliary switch for transmission with Measuring Display Unit (option) Initial setting and resetting after power failure are necessary (no power failure compensation) By default, the demand time limit is 2 min. It can be set in the range from 0 to 15 min in 1-min steps. By default, the function is off. The parameters can be set in the following ranges. Function: ON/OFF Pickup current: 50 to 100% (1% step) Demand time limit: 1 to 10 min (1-min step), 15, 20, 25 and 30 min By default, the function is off. The parameters can be set in the following ranges. Function: ON/OFF Pickup current: 10%, fixed (no setting) Operating time: 30 sec (no setting) By default, the function is off. The parameters can be set in the following ranges. Function: ON/OFF Pickup current: 30%, fixed (no setting) Operating time: 30 sec (no setting) 30 When the single-phase 3-wire type is set, the function is turned on. Rated operating overvoltage: 135 V AC (no setting) Operating time: 1 sec (no setting) Default: No phase switching Default: Automatic reset Default: 3-phase 3-wire Default: Vertical One of vertical, horizontal 1 and horizontal 2 can be selected.
*1 The term “each phase” used for load current and harmonic current refers to phase 1, 2, 3 or N. However, the phase N is provided only on 4-pole circuit breakers. The term “between each phase” used for line voltage refers to between phases 1 and 2, 2 and 3, 3 and 1, 1 and N, 2 and N or 3 and N. However, voltage between phases 1 and N, 2 and N and 3 and N is applicable only on 4-pole circuit breakers. These circuit breakers measure the values every 0.25 sec. Therefore, even when a low order circuit breaker operates, operating current may not be measured. *2 Each maximum value is the largest value among values obtained from the start of operation (after the previous reset) to the present. *3 The integrated value of electric energy and the integrated value of reactive energy are stored upon occurrence of power failure and every 30 minutes, the fault current and the cause are stored upon occurrence of fault, the set values are stored when they are set, and other values are stored every 30 minutes in the nonvolatile E2PROM. *4 The demand time limit cannot be set individually. It is common to the items. *5 The average values of load current and line voltage are calculated as shown below when the phase and wire type is specified. Phase and wire type Single-phase 2-wire Single-phase 3-wire 3-phase 3-wire 3-phase 4-wire
Average present value Average present value Average present value Average present value phase 3 current)/3
of of of of
current current = phase 3 current current = (phase 1 current + phase 3 current)/2 current = (phase 1 current + phase 2 current +
Average present value of voltage Average present value of voltage = voltage between phases 2 and Average present value of voltage = (voltage between phases 1 and 2 + voltage between phases 2 and 3)/2 Average present value of voltage = (voltage between phases 1 and 2 + voltage between phases 2 and 3 + voltage between phases 3 and 1 phases)/3
*6 Sum of values of harmonic components in third to 19th orders except fundamental wave component *7 The reverse power is not measured. *8 If the upper limit of the fault current measurement range (rated current 125 to 250 A (adjustable): 4000 A, rated current 50, 60, 75, 100, 125 A (fixed): 2000 A)) is exceeded when overload or short circuit fault occurs, the cause of the fault may not be displayed, and the fault current may not be measured. For fault current, display of cause of fault and measurement of fault current are enabled when the AL for transmission with the Measuring Display Unit (option) is installed. *9 When the alarm retention mode has been set to Automatic reset, the alarm display on the Measuring Display Unit will be reset automatically. When the alarm retention mode is Self-retention, the alarm display will be self-retained. In the self-retention mode, the display can be reset through the alarm reset operation (collective reset). OVER will be automatically reset regardless of the mode setting.
37
2
Detailed Specifications
5
Measuring Display Unit Breakers
dSpecifications for Measuring Display Unit (1) The measurement and display items vary depending on the model or frame A. (For the measurement accuracy, please refer to page 40.)
Applicable models NF400-SEP with MDU, NF400-HEP with MDU, NF630-SEP with MDU, NF630-HEP with MDU, NF800-SEP with MDU, NF800-HEP with MDU
Table 2-2 Model Measurement and memory items (accuracy) (*3)
5 Detailed Specifications
2
Electric energy With CC-Link MDU Storage with pulse output communication Pulse output Display (*1) Communication (*1)
Remarks
Present value of each phase Demand value of each phase Average present value (*11) Max. demand value (general value) (*4) Time of occurrence of max. value (year, month, day, hour, minute)
–
– – –
– – – – –
Present value between each phases Average present value (*11) Max. value (general value) (*4) Time of occurrence of max. value (year, month, day, hour, minute)
–
– –
– – – –
Current value in 3rd, 5th, 7th … 19th orders of each phase Max. value in 3rd, 5th, 7th … 19th orders (general value) (*4) Time of occurrence of max. value (year, month, day, hour, minute)
–
–
– – –
Current value of general harmonics of each phase (*10) Demand value of general harmonics of each phase (*10) Max. demand value (general value) (*4) Time of occurrence of max. value (year, month, day, hour, minute)
–
– –
– – – –
Time limit: 0 to 15 min, changeable (Same as the present value when 0 min is specified)
Electric power (±2.5%)
Current value (also reverse power is measured) Demand value (also reverse power is measured) Max. demand value Time of occurrence of max. value (year, month, day, hour, minute)
–
– –
– – – –
Time limit: 0 to 15 min, changeable (Same as the present value when 0 min is specified)
Electric energy (±2.5%)
Electric energy (integrated value) (*5) Electric energy per time (*5) Max. value of electric energy per time (*5) Time of occurrence of max. value (year, month, day, hour, minute)
–
–
– – –
Value accumulated from previous reset to present Amount for 1 hour from hour to hour on built-in clock
Cause of fault
Fault current (accuracy: ±15%) (*11)
– –
Information on fault after previous reset or last fault, and cause of fault (continuously monitored)
Power factor (±5%)
Present value
–
–
LED on
–
–
Load current (±2.5%)
Line voltage (±2.5%)
Harmonic current (±2.5%)
Time limit: 0 to 15 min, changeable (Same as the present value when 0 min is specified) Max. demand value after previous reset
Max. value after previous reset (not demand value)
Max. value after previous reset (not demand value)
Max. demand value after previous reset
Max. demand value after previous reset
Max. demand value after previous reset
Alarm of circuit breaker
PAL, OVER (*6) (*11)
State of circuit breaker
Tripping state of circuit breaker (AL) ON/OFF state of circuit breaker (AX)
– –
– –
– –
When alarm switch for transmission with Measuring Display Unit (option) is installed When auxiliary switch for transmission with Measuring Display Unit (option) is installed
Time setting
–
–
–
Initial setting and resetting after power failure are necessary (no power failure compensation).
Demand time limit setting (*7)
–
Default: 2 min Setting in 1-min steps in range from 0 to 15 min
PAL pickup current setting * Setting on circuit breaker body The Measuring Display Unit does not have the setting function.
–
Default: 100% Setting in 5% steps in range from 70 to 100% Default setting on breaker body is 70% unless otherwise specified.
Pulse unit setting
–
–
Default: 1 kWh/pulse Setting to 1 kWh, 10 kWh, 100 kWh, 1000 kWh or 10000 kWh
Default settings
Phase switching setting
–
Default: No phase switching
Alarm retention (self-retention or automatic reset) setting
–
Default: Automatic reset
Notes: *1 The electric energy (integrated value) is stored upon occurrence of power failure and every 2 hours, the fault current and the cause are stored upon occurrence of fault, the demand time limit, EPAL sensitivity current, PAL pickup current, pulse unit, alarm retention and phase switching settings are stored when they are set, and other values are stored every 2 hours in the nonvolatile E2PROM. Each maximum value is the largest value among values obtained from the start of operation (after the previous reset) to the present. *2 Every time the electric energy is integrated in the pulse unit (the unit can be set to 1 kWh, 10 kWh, 100 kWh, 1000 kWh or 10000 kWh), a pulse is output. Counting can be performed with a PLC. *3 The term “each phase” used for load current and harmonic current refers to phase 1, 2, 3 or N. However, the phase N is provided only on 4-pole circuit breakers. The term “between each phase” used for line voltage refers to between phases 1 and 2, 2 and 3, 3 and 1, 1 and N, 2 and N or 3 and N. However, voltage between phases 1 and N, 2 and N and 3 and N is applicable only on 4-pole circuit breakers. The electric energy data is 6-digit data of up to 999999 kWh. The voltage and harmonic current are 3-digit data, and others are 4-digit. These circuit breakers measure the values every 0.25 sec. Therefore, even when a low order circuit breaker operates, operating current may not be measured. *4 Each general value indicates the value only of the phase with the maximum value. *5 The electric energy is not measured in the case of reverse power flow. *6 When the alarm retention mode has been set to Automatic reset, the PAL alarm LED display on the Measuring Display Unit front panel will be reset automatically. When the alarm retention mode is Self-retention, the alarm display will be self-retained. In the self-retention mode, the display can be reset through alarm reset operation (collective reset). OVER will be automatically reset regardless of the mode setting. *7 The demand time limit cannot be set individually. It is common to the items. *8 Sum of values of harmonic components in third to 19th orders except fundamental wave component. *9 The average present value of load current is the average value of current among phases 1, 2 and 3 (the current of the phase N is not included even in the case of a 4-pole circuit breaker). When the circuit breaker is used on a single-phase 3-wire circuit, the calculated value is displayed. However, ignore it. The average present value of line voltage is the average value of voltages between phases 1 and 2, 2 and 3 and 3 and 1 (the voltages between phases 1 and N, 2 and N and 3 and N are not included in the case of a 4-pole circuit breaker). *10 Setting at the pre-alarm current Ip (which can be set in the range from 70 to 100% of the rated current In in 5% steps) on the circuit breaker body. The Measuring Display Unit does not have the setting function. *11 The operating time of PAL is shown below. PAL
38
Same as pre-alarm operating time Tp on circuit breaker body
2 Detailed Specifications 5 Measuring Display Unit Breakers
dSpecifications for Measuring Display Unit (2)
Applicable models NF250-SEV with MDU, NF250-HEV with MDU
Table 2-3
Tolerances
Demand time limit setting range Voltage circuit (1f2W, 3f3W) Voltage circuit (1f3W) Rated Voltage circuit (3f4W) input Current circuit Frequency (1) Wh (integrated value) Power failure (2) Max. value compensation (3) Setting data Clock Clock accuracy External dimensions (unit: mm) Control power supply Other functions
Specification 250 ms (harmonic current: 2 s) Current and voltage: ±1.0% (to rating input) Electric power: ±1.5% (to rating input) Reactive power: ±2.5% (to rating input) Harmonic current: ±2.5% (to rating input) Power factor: ±5% Frequency: ±2.5% Electric energy: ±2.0% (voltage 100 V to 440 V, range from 5 to 100% of current rating, power factor 1) Reactive energy: ±3.0% (voltage 100 V to 440 V, range from 10 to 100% of current rating, power factor 0) Fault current: ±15% (*1) 0 to 15 min (1-min steps)
2 5 Detailed Specifications
Item Data updating cycle
440 V (only 4-pole breakers applicable to 3f4W) Load current/harmonic current: 250 A 50 Hz/60 Hz (automatic discrimination of frequency) Stored in EEPROM (nonvolatile memory) * Wh and varh are stored upon occurrence of power failure and every 30 min. * Max. value is stored every 30 min. Setting data are stored when they are set. No power failure compensation Approx. 1 min/month See Characteristics and Dimensions. Compatible with 100 to 240 V AC/DC, 50/60 Hz (allowable voltage range: 85% to 110%), 12 VA (*2) Function for switching phases to be measured to 1-3 and 3-1 PAL alarm, self-retention/automatic reset setting function (*3) Function for counting number of times of opening and closing of circuit breaker body (*4)
Notes: *1 The measurement of fault current of load is enabled when the AL switch for transmission with Measuring Display Unit (option) is installed in the Measuring Display Unit Breaker body. *2 When the MDU unit control power is turned on, a rush current transitionally flows (maximum rush current: 2A, energizing time: 1ms (240V AC) *3 The PAL functions are enabled when the MDU breaker with PAL module (option) is used. *4 The function is enabled when the AX switch for transmission with Measuring Display Unit (option) is installed in the Measuring Display Unit Breaker body.
dNetwork Specifications for Measuring Display Unit [Electric energy pulse output]
[CC-Link communication]
Table 2-4
Table 2-5
Item Output elements Contact capacity Output pulse unit Output pulse width Max. wiring length
Specification Solid state relay (SSR), no voltage a contact (Ca and Cb terminals: no polarity) Compatible with 24V DC and 100 to 200 V AC, 20 mA 1, 10, 100, 1000 and 10000 kWh/pulse (settable) 0.35 to 0.45 s 100m
Item Communication speed Communication method Synchronization method Encoding method Transmission format Number of occupied stations
Number of connected units
Station number CC-Link version
Specification 10M/5M/2.5M/625k/156kbps Broadcast polling method Frame synchronization method NRZI Conforming to HDLC Remote device occupying 1 station Meet the following conditions. When a system consists only of Measuring Display Units, up to 42 units can be connected. Condition 1 for number of connected units (1×a) + (2×b) + (3×c) + (4×d) q 64 a: Number of units occupying 1 station b: Number of units occupying 2 stations c: Number of units occupying 3 stations d: Number of units occupying 4 stations Condition 2 for number of connected units (16×A) + (54×B) + (88×C) q 2304 A: Number of units at 1 remote I/O station q 64 B: Number of units at remote device station q 42 C: Number of units at local station q 26 Setting in range from 1 to 64 (Set the station number without fail.) CC-Link Ver.1.10 Master station
Max. total extension cable length and cable length between stations
Remote I/O Remote I/O Local station Local station station or remote station or remote or intelligent or intelligent device station device station device station device station
Cable length between stations Max. total extension cable length Cables applicable to CC-Link Ver. 1.10 (with use of 110-ohm terminal resistance) Communication speed Cable length between stations Max. total extension cable length
Connecting cable
156kbps
625kbps
1200m
900m
2.5Mbps 5Mbps 0.2 m or more 400m
160m
10Mbps 100m
Cables applicable to CC-Link Ver. 1.10 (shielded 3-core twisted pair cables) * Cables applicable to Ver. 1.10 supplied by different manufacturers can be used simultaneously.
Note: For more information, visit the website of CC-Link Partner Association (HYPERLINK “http://www.cc-Link.org/”).
39
2
Detailed Specifications
5
Measuring Display Unit Breakers
dSpecifications for Measuring dDisplay Unit (2)
Applicable models NF400-SEP with MDU, NF400-HEP with MDU, NF630-SEP with MDU, NF630-HEP with MDU, NF800-SEP with MDU, NF800-HEP with MDU
Table 2-6 Item Data updating cycle Tolerances
5 Detailed Specifications
2
Specification 250 ms (harmonic current: 2 s) Current, voltage and Electric power: ±2.5% (to rating input) Power factor: ±5% Electric energy: ±2.5% (voltage 100 V to 440 V, range from 5 to 100% of current rating, power factor 1) Fault current: ±15% 0 to 15 min (1-min steps)
Demand time limit setting range Voltage circuit (1f2W, 3f3W) 440 V (only 4-pole breakers applicable to 3f4W) Voltage circuit (1f3W) Rated Voltage circuit (3f4W) input Load current/harmonic current: 100 A/225 A/400 A/600 A/800 A (Automatic discrimination. Determined based on A frame of circuit breaker. Current circuit 100 A when rated current of 225 A frame is 100 A or less) Leakage current: 500 mA 50 Hz/60 Hz (automatic discrimination of frequency) Frequency (1) Wh (integrated value) Stored in EEPROM (nonvolatile memory) * Wh is stored upon occurrence of power failure and every 2 hours Power failure (2) Max. value compensation (3) Setting data * The max. value is stored every 2 hours. The setting data is stored when it is set. No power failure compensation Clock Approx. 1 min/month Clock accuracy W×D×H: 90×75×30 External dimensions (unit: mm) Compatible with 100 to 240 V AC/DC, 50/60 Hz (allowable voltage range: 85% to 110%), 12 VA (*1) Control power supply Function for switching phases to be measured to 1-3 and 3-1 Other functions ECA/PAL alarm, self-retention/automatic reset setting function Note: *1 When the MDU unit control power is turned on, a rush current transitionally flows (maximum rush current: 2A, energizing time: 1ms (240V AC)
dNetwork Specifications for Measuring Display Unit [Electric energy pulse output]
[CC-Link communication]
Table 2-7
Table 2-8
Item Output elements Contact capacity Output pulse unit Output pulse width Max. wiring length
Specification Solid state relay (SSR), no voltage a contact (Ca and Cb terminals: no polarity) Compatible with 24V DC and 100 to 200 V AC, 20 mA 1, 10, 100, 1000 and 10000 kWh/pulse (settable) 0.35 to 0.45 s 100m
Item Communication speed Communication method Synchronization method Encoding method Transmission format Number of occupied stations
Number of connected units
Station number CC-Link version
Specification 10M/5M/2.5M/625k/156kbps Broadcast polling method Frame synchronization method NRZI Conforming to HDLC Remote device occupying 1 station Meet the following conditions. When a system consists only of Measuring Display Units, up to 42 units can be connected. Condition 1 for number of connected units (1×a) + (2×b) + (3×c) + (4×d) q 64 a: Number of units occupying 1 station b: Number of units occupying 2 stations c: Number of units occupying 3 stations d: Number of units occupying 4 stations Condition 2 for number of connected units (16×A) + (54×B) + (88×C) q 2304 A: Number of units at 1 remote I/O station q 64 B: Number of units at remote device station q 42 C: Number of units at local station q 26 Setting in range from 1 to 64 (Set the station number without fail.) CC-Link Ver. 1.10 Master station
Remote I/O Remote I/O Local station Local station station or remote station or remote or intelligent or intelligent device station device station device station device station
Cable length between stations CMax. total extension cable length Max. total extension cable length and cable length between stations
Connecting cable
Cables applicable to CC-Link Ver. 1.10 (with use of 110-ohm terminal resistance) Communication speed Cable length between stations Max. total extension cable length
156kbps
625kbps
1200m
900m
2.5Mbps 5Mbps 0.2 m or more 400m
160m
10Mbps 100m
When the Measuring Display Unit is installed on the panel, the terminal block on the panel mounting plate and the terminal block on the Measuring Display Unit are connected with a CC-Link cable having a one-way length of 15 cm and an entire length of 30 cm. When connecting the unit in consideration of the following three points. (1) The one-way length of the CC-Link cable, 15 cm, is included in the distance (1) between stations. (2) The entire length of the CC-Link cable, 30 cm, is included in the maximum (1) transmission distance (total extension distance). Cables applicable to CC-Link Ver. 1.10 (shielded 3-core twisted pair cables) * Cables applicable to Ver. 1.10 supplied by different manufacturers can be used simultaneously.
Note: For more information, visit the website of CC-Link Partner Association (HYPERLINK “http://www.cc-Link.org/”).
40
2 Detailed Specifications 5 Measuring Display Unit Breakers
dCautions when Using Measuring Display Unit Breakers (common instructions) Measuring accuracy
How to use Measuring Display Unit Breaker on single-phase 2-wire circuity
(1) Connect the breaker as shown in the right figure. Connection on single-phase 2-wire circuit The phase 1 on the load side is charged. Insulate it. As measurement data, use the current of the phases 2 and 3 and the voltage between the 1 2 3 phases 2 and 3. Line side Although the current of the phase 1 and the voltage between the phases 1 and 2 and the phases 3 and 1 are measured, ignore the measurements. The Measuring Display Unit is designed for 3-phase 3-wire and single-phase and 3-wire circuits. On W & WS Series Measuring Display Unit Breakers, the average values of load current and line voltage are calculated from the values of the phases 1, 2 and 3 (between the Load side phases). Ignore these measurement values. ATTENTION: Live part Also when the breaker is used on a single-phase 3-wire circuit, ignore these values. Load When using any WS-V Series Measuring Display Unit Breaker, set the phase and wire type.
Phase sequence of Measuring Display Unit Breaker
The phase sequence of Measuring Display Unit Breaker can be set by using the phase switching function as shown below. When the breaker is installed vertically with the power supply side upward (see the right figure), the phase sequence is set as stated below. No phase switching: 1, 2, 3 and N from the left (default) With phase switching: 3, 2, 1, and N from the left Set the phase sequence in accordance with the installation and wiring methods. Notes (1) The phase N is provided only on 4-pole circuit breakers. Notes (2) Note that the position of the phase N is unchanged Notes (2) regardless of the phase switching setting.
Reverse connection of Measuring Display Unit Breaker
The Measuring Display Unit Breakers cannot be connected with the power supply and load sides set reversely.
1
2
3
N
*Phase N is provided only on 4-pole breakers. 3 2 1 N
Line side
Load side No phase switching (default)
With phase switching
Busbar 1 2 3 Load side
Line side
Line side
1
1
2
2
3
3
Measurement phase Phase switching setting: No phase switching
Load side
Measurement phase Phase switching setting: With phase switching
Installation of Measuring Display Unit Breaker in close contact
The Measuring Display Unit Breakers must not be installed in close contact. (1) In the case of 400, 630 or 800A frame, install the breaker body securing a wiring space of 30 mm or more on the right side of the breaker to connect the connecting cables and fitting the connecting cable connectors. (2) In the case of WS-V Series Measuring display Unit Breaker, install the breaker body securing a wiring space of 40 mm or more on the right side of the breaker to connect the connecting cables.
41
2 5 Detailed Specifications
(1) The accuracy of measurement of current or voltage is indicated as the percentage of error to the rated current or voltage for measurement by the Measuring Display Unit. The measurement rated current is the maximum rated current of each ampere frame. For W & WS Series Measuring Display Unit Breakers, the accuracy is the max. rated current × ±2.5%. For WS-V Series Measuring Display Unit Breakers, the accuracy is the max. rated current × ±1%. (For example, when the rated current of NF630-SEP with Measuring Display Unit is 350 A, the measurement rated current is 630 A, and the current accuracy is 630 A × ±2.5% = ±15 A.) * The measurement rated voltage is 440 V. (Common to all A frames) When the current is less than 1.0% of the measurement rated current in the case of WS-V Series Measuring Display Unit Breakers or less than 2.0% of the measurement rated current in the case of W & WS Series Measuring Display Unit Breakers or when the voltage is less than 5.0% of the measurement rated voltage in the case of WS-V Series Measuring Display Unit Breakers or less than 2.0% of the measurement rated current in the case of W & WS Series Measuring Display Unit Breakers, the current or voltage is cut off, and zero is displayed. (2) When the current is cut off, the current is displayed as 0 A. However, if the current is 0.4% or more of the measurement rated current, the electric energy is measured. (3) The accuracy of power factor is the percentage to electrical angle of 90°. A power factor of 50% or less is displayed as a reference value. (4) The accuracy of electric energy is ±2.0% of the true value in the case of WS-V Series Measuring Display Unit Breakers and ±2.5% of the true value in the case of W & WS Series Measuring Display Unit Breakers in the range of measurement rated voltage (100 V to 440 V) × current (measurement rated current of 5 to 100%).
2
Detailed Specifications
5
Measuring Display Unit Breakers
dCautions when using Measuring Display Unit Breaker (For Measuring Display Unit) Transmission method
5 Detailed Specifications
2
(1) One of No transmission, With pulse output and With CC-Link communication should be specified. (2) W & WS Series Measuring Display Unit Breaker with CC-Link communication cannot be manufactured for installing the Measuring Display Unit on the breaker body. (3) When With transmission is selected, data which can be transmitted depends on the function of the Measuring Display Unit Breaker body. The transmission options cannot be installed or changed later. Specify the options when issuing the initial order. (4) For the maximum number of connected units and transmission distance for each transmission type, see the following tables. <WS-V Measuring Display Unit Breakers> Tables 2-4 and 2-5 <W & WS Measuring Display Unit Breakers> Tables 2-7 and 2-8
Installation of Measuring Display Unit
(1) When the installation of Measuring Display Unit on panel has been specified, the breaker will come with the panel mounting parts, mounting screws and 2-m connecting cable (standard). (The 0.5-, 3-, 5- or 10-m connecting cable can be specified.) (2) If the installation position of the Measuring Display Unit is changed from the panel to the body or vice versa, the Measuring Display Unit and the breaker body must be returned to the manufacturer for modification.
Measuring Display Unit Breaker with CC-Link communication (W & WS Series Measuring Display Unit Breakers)
(1) If you intend to use the circuit breaker with its pane out on the face board, specify the installation on panel.
dChange of display direction for breaker mounting <WS-V Series Measuring Display Unit Breaker> (1) When installing the Measuring Display Unit on the breaker body installed in the horizontal direction, the direction of the display can be changed according to the installation direction. (2) The display direction is set on the display unit. Line side
Line side
Load side
Line side
Load side
Load side Default display direction
Installation with line side on left
Installation with line side on right
<W & WS Series Measuring Display Unit Breaker> (1) When installing the Measuring Display Unit on the breaker body installed in the horizontal direction, the direction of the display of Measuring Display Unit can be changed for ease in reading according to the installation direction. (2) Remove the screws on the rear panel of the Measuring Display Unit, and change the direction according to the installation direction. Display of Measuring Display Unit
Installation with power supply side on left
Display of Measuring Display Unit
Measuring Display Unit display mounting screws
Installation with power supply side on right Default direction of Measuring Display Unit display
42
5 Detailed Specifications
MEMO
2
43
2
Detailed Specifications
Miniature Circuit Breakers
6
BH
Model
BH-P
70
100
100
70
100
100
Number of poles
1
2
3
1
2
3
Rated current (A) at ambient temperature 40°C
70
70, 100
70, 100
70
70, 100
70, 100
Frame (A)
Image
6 Detailed Specifications
2 AC
230/400
230/400
DC
125
125
Rated voltage (V)
Rated short cirsuit capacity (kA)
AC230/400V
3
−
3
−
AC400V
−
3
−
3
IEC 60898-1 −
DC125V
1
Instantaneous tripping
ca c
a Dimensions (mm)
1 Type C (5 In <, 10 In)
b
a
25
75
25
50
95
74
c
57.5
60.5
ca Mass (kg)
50
b
77.5 0.16
0.32
75
79 0.48
0.13
Clamp terminal
0.26
0.38
Plug-in (line) Clamp (load)
Connection (*1)
Automatic tripping device
Optional accessories
Approved by
Thermal, magnetic
Terminal cover
d
Mounting plate
d
−
Terminal base
−
d
Lock cover
d
d
−
Notes: *1 If reguired solderless terminal can be supplied. (BH : Line and Load side, BH-P : Load side only)
44
LR, GL, NK
−
−
−
LR, BV, AB, GL, NK
−
2 Detailed Specifications
6 Miniature Circuit Breakers
BH-D6
Model
BH-D10
BH-DN
Image
1
Instantaneous tripping
2
Type B, C, D
Rated insulation voltage Ui [V]
2
0.5, 1, 1.6, 2, 3, 4, 6, 10, 13, 16, 20, 25, 32, 40
–
6
10
230/400V
6
–
–
400V
–
6
–
a
ca c
54
b
b
Type C*2
0.5, 1, 1.6, 2, 3, 4, 6, 10, 13, 16, 20, 25, 32, 40, 50, 63
6, 10, 16, 20
–
4.5
10
–
–
–
10
20,000
10,000 36
18
36
87
20,000 54
72
87
18 88
c
44
44
44
ca
70
70
70
Thermal-magnetic
Thermal-magnetic
Thermal-magnetic
IEC35mm rail
IEC35mm rail
IEC35mm rail
1 to 25mm2
1 to 25mm2
1 to 10mm2
Type of overcurrent release Mounting Applicable wire size Weight [kg]
0.15
0.3
0.45
Alarm switch (AL) Mass Auxiliary switch (AX) optional accessories Shunt trip (SHT) Terminal connection Based on standard CE marking
0.55
0.25
0.15
0.3
0.45
0.55
0.12
d
d
–
d
d
–
d
d
–
Solderless
Solderless
Solderless
IEC 60898-1
IEC 60898-1
IEC 60898-1
EN 60898-1 : Self-declaration
EN 60898-1 : Self-declaration
EN 60898-1 : Self-declaration
GB 10963.1
GB 10963.1
GB 10963.1
CCC
2
–
10,000 72
2 (1+N)*1 230
8,000 36
4(3+N)*1
*2
440
8,000 18
3
Type B, C, D
6
With current
Dimensions [mm] a
Type B, C
230V
Without current
Number of operating cycles
1
*2
0.5, 1, 1.6, 2, 3, 4, 6, 10, 13, 16, 20, 25, 32, 40, 50, 63
AC IEC 60898-1 (Icn)
*2
440
Rated current In [A] at ambient temperature 30°C Rated shortcircuit capacity [kA]
4(3+N)*1 2(1+N)*1
3
6 Detailed Specifications
Number of poles [P]
Notes: *1 N pole is a switched neutral pole (without overcurrent release device). *2 Type B (3 In <, 5 In), Type C (5 In <, 10 In), Type D (10 In <, 20 In)
BH-D10 (For DC)
Model
Image
Number of poles [P]
1
2 Type B, C*3
Instantaneous tripping Rated insulation voltage Ui [V]
250
Rated current In [A] at ambient temperature 30°C
0.5, 1, 1.6, 2, 3, 4, 6, 10, 13, 16, 20, 25, 32, 40, 50, 63
Rated short- IEC 60898-2 circuit capacity [kA] (Icn)
DC
125V
10
–
250V
–
10
Without current
Number of operating cycles
8,000
With current
Dimensions [mm] a
ca c b
a
4,000 18
36
b
87
c
44
ca
70
Type of overcurrent release
Thermal-magnetic
Mounting
IEC35mm rail 1 to 25mm2
Applicable wire size Weight [kg]
0.15
0.3
Alarm switch (AL)
d
Mass Auxiliary switch (AX) optional accessories Shunt trip (SHT) Terminal connection Based on standard CE marking CCC
d d Solderless IEC 60898-2 EN 60898-2 : Self-declaration GB 10963.2
Notes: *3 Type B: (5 In <, 7 In), Type C: (7 In <, 15 In)
45
2
Detailed Specifications
Miniature Circuit Breakers
6
RCBO
RCCB BV-D
Model
Image
Image
2(1+N)*1
Number of poles [P]
4(3+N)*1 *3
Rated current [A] at ambient temperature 30°C
2
230
230/400
Rated current sensitivity Inn [mA]
6 Detailed Specifications
ca c b
a
72
b
85
c
44
ca
70
b
0.2
Rated making and breaking capacity Im [A]
500(In 25,40A), 630(In63A) 6
Rated residual making and breaking capacity Inm [A]
500(In 25,40A), 630(In63A) 8,000
With current
8,000
Type of overcurrent release
0.2
CE marking CCC
With current
Thermal-magnetic IEC35mm rail 1 to 16mm2
Weight [kg]
0.19
Solderless
Terminal connection
IEC 61008-2-2
Based on standard
GB 16916.22
20,000 20,000 (In 6,10,16,20A) 15,000 (In 25A) 10,000 (In 32,40A)
Applicable wire size
EN 61008-2-2 : Self-declaration
70
Thermal, magnetic
Mounting 0.35
Terminal connection Based on standard
Automatic tripping device
Type of overcurrent release
1 to 25mm2
Weight [kg]
44
Without current
IEC35mm rail
Applicable wire size
88
c
0.19
Number of operating cycles
–
Mounting
36
Mass [kg]
6
Without current
a b ca
0.35
Rated conditional short-circuit current Inc [kA]
Number of operating cycles
ca c
4.5 Type C*2
Tripping characteristics Dimensions a [mm]
Mass [kg]
Rated conditional residual short-circuit current Inc [kA]
0.04 Type AC
Breaking capacity [kA] sym. (IEC 61009)
6 36
230 30, 100, 300
Pulsating current sensitivity
Type AC
Rated conditional short-circuit current [kA]
Rated voltage [VAC] Max. operating time at 5Inn [s]
0.04
Pulsating current sensitivity
6, 10, 16, 20, 25, 32, 40
Rated current sensitivity Inn [mA]
30, 300
Max. operating time at 5Inn [s]
2(1+N)*1
Number of poles [P] Rated current [A] at ambient temperature 30°C
25, 40, 63
Rated voltage [VAC]
Dimensions a [mm]
BV-DN
Model
Solderless IEC 61009-2-2
CE marking
EN 61009-2-2 : Self-declaration
CCC
GB 16917.22
Notes: *1 N pole is a switched neutral pole (without overcurrent release device). *2 Type C: (5 In <, 10 In) *3 For use to three phase 4-wire type. When using, it be sure to connect the neutral wire to the neutral phase. Not available for use to three phase 3-wire type.
Isolating switch KB-D
Model
Image
Number of poles [P]
1
2
Utilization category Rated current [A] at ambient temperature 30°C 230
400
Short time withstand current [A]
20 3 In, 1s
Short-circuit making capacity [A] Dimensions [mm] a
ca c b
20 3 In a
18
36
b
87
c
44
ca Mass [kg]
0.18
Without current
CE marking CCC
46
0.27
0.36
0.3
0.4
3,000 IEC35mm rail 1 to 25mm2
Applicable wire size Terminal connection
72
20,000
With current
Weight [kg]
54
70 0.09
Mounting
Based on standard
4(3+N)
32, 63, 80
Rated voltage [VAC]
Number of operating cycles
3 AC22A class
0.1
0.2 Solderless IEC 60947-3 EN 60947-3 : Self-declaration GB 14048.3
2 Detailed Specifications
6 Miniature Circuit Breakers
Accessories for Miniature Circuit Breakers Functions of Accessories Internal accessory
Function
AL
Alarm switch
Electrically indicates the trip status of the circuit breaker.
AX
Auxiliary switch
Electrically indicates the On/Off status of the circuit breaker. Electrically trips the circuit breaker from a remote location. Permissible working voltages are 70 to 110% of the AC rated voltage or 70 to 125% of the DC rated voltage.
Shunt trip
Equipping of Accessories Model
BH-D6
BH-D10
AL
AX
SHT
Accessory
BH, BH-P, BH-DN, BV-DN, KB-D, BV-D
–
: Accessory equipped –: Accessory not equipped
Specifications Type
Contact
Configuration Contact capacity
Function
AL
AX
AL+AX
AX+AX
AL-05DLS
AX-05DLS
ALAX-05DLS
AX2-05DLS
1C
1C
2C
2C
400VAC, 2A
230VAC, 5A
120VDC, 0.4A
48VDC, 1.5A
24VDC, 4A
Line
–
–
AX
AX
Load
AL
AX
AL
AX
Connection
Clamp terminal
Compliance standard
IEC 60947-5-1
Type
SHT SHTA400-05DLS
Cut-off switch
SHTD048-05DLS Equipped
Voltage
110-400VAC
24-48VDC
Input power requirement
110VAC 60VA 230VAC 250VA 400VAC 750VA
24VDC 75VA 48VDC 300VA
Operating time [ms]
< 20
Connection
Solderless terminal
Compliance standard
IEC 60947-2
2 6 Detailed Specifications
SHT
* Secure a sufficient input power supply so that the voltage will not drop below the permissible lower working voltage (70% of the lowest rated voltage). * The operating time denotes the time from when the rated voltage is applied to SHT until the time the main contact of the breaker starts to open.
47
2
Detailed Specifications
Miniature Circuit Breakers
6
Combinations of Accessories AL
AX
2AX
ALAX Accessory connection combinations
SHT
AX+SHT
AL+SHT
2AX+SHT
ALAX+SHT
Breaker
AL
AX
AL+AX
AX+AX
SHT
Outline Drawing AL-05DLS
AX-05DLS
ALAX-05DLS AX2-05DLS
SHTA400-05DLS SHTD048-05DLS
87
45
95
45
44.5
47.5
Solderless terminal
44.5
M3.5 screw
92
92
45
44.5
Type ALAX-05DLS
45
6 Detailed Specifications
2
M3.5 screw M3.5 screw 17
9
44
17
9
70max
17
9
44
44
18
70max
44
17
M5 screw
70max
70max
Connection of Line and Load Side AL-05DLS
AX-05DLS
Line
96
98
ALAX-05DLS
95
Load
AL
95 ALc 96 ALb 98 ALa
14
12
AX2-05DLS
Line
Line
11
AX
11 AXc 12 AXb 14 AXa
Line
12
14
11
96
98
95
AX
11 AXc 12 AXb 14 AXa
12
14
11
AL
95 ALc 96 ALb 98 ALa
24
22
21
Load
Load
AX
11 AXc 12 AXb 14 AXa
AX
21 AXc 22 AXb 24 AXa
Load
Installation of Accessories (AX, AL, SHT) ( 1) Installation 1 Off
(2) Removal 2 Hook
3 Insert
4 Click
48
1
2
2
Detailed Specifications
Circuit Protectors
7
30
Frame (A) CP30-BA
Model
CP-S
Image
1
2
Rated impulse withstand voltage Uimp (kV) Rated current (A) UL 1077 CSA C22.2 No.235 (*11)
Rated voltage (V)
1
2
2.5
2.5 0.05 0.1 0.25 0.3 0.5 0.75 1 2 2.5 3 5 7 7.5 10 15 20 25 30
250 65
125
AC
2.5kA at 250V 2.5kA at 65V
250
–
65
–
1.5kA at 250V
–
–
2.5kA at 125V
–
1kA at 65V
250
250
AC
250
1.5kA at 230V 2.5kA at 120V
DC
2.5kA at 60V
2.5kA at 120V
Rated insulation voltage Ui (V)
–
AC
2.5/2.5kA at 230V 2.5/2.5kA at 60V 2.5/2.5kA at 120V
–
–
d
– (*1)
– (*8)
d
Rated short time current (for switch only type)
–
Rated ambient temperature (°C) Operating characteristics
–
– AC250V 50/60Hz AC125V 50/60Hz DC65V DC125V 25 (T25)
40 (T40) Instantaneous type (I); Medium type (M), (MD); Slow type (S), (SD); Fast type (F) (*2)
: hydraulic-magnetic [HM]
S-type (IEC 60934)
Trip-free behaviour
Trip-free (IEC 60934) 0.08 Retractable small terminal cover (TC-S)
0.06
0.12
0.18
–
Inertial delay (ID)
d (Medium, Slow type: AC only)
d (Medium, Slow, Fast type: AC only)
Alarm switch (AL)
d (1c)
d (1c) (*7)
Auxiliary switch (AX)
d (1c)
d (1c)
d (for relay type) (*3)
d (for parallel and relay type: AC only)
Shunt trip (SHT) Large terminal cover (TC-L) Back facing wiring termnal (BT) Lock cover (LC) Accessory terminal cover (TC) Main body Alarm switch / Auxiliary switch
Main body mounting method International standard
Notes: *1 *2 *3 *4 *5 *6 *7 *8 *9 *10 *11
0.23
: hydraulic-magnetic [HM]
dStandard IP20 (front, terminal covers closed) [Certified of TUV]
Flushpanel mounting brackets (FP)
CE Marking
0.16
0.02s 0.02s 0.02s 0.02s
Instantaneous type (I): magnetic only [MO] Medium type (M), (MD) Slow type (S), (SD) Fast type (F), (FD)
Method of operation Mass (kg)
1500A 2500A 1000A 1000A
Instantaneous type (I); Medium type (M), (MD); Slow type (S), (SD); Fast type (F) (FD)
Instantaneous type (I): magnetic only [MO] Medium type (M), (MD) Slow type (S), (SD) Fast type (F)
Mode of tripping
1kA at 60V
–
DC
Reverse connection
Connection
1kA at 120V (1kA at 60V) (*7)
1kA at 60V
250
AC-DC common use
Accessories
–
Rated insulation voltage Ui (V) Rated short-circuit IEC 60934 capacity (kA) EN 60934 (Icn)
2
3
250
0.1 0.25 0.3 0.5 1 2 3 5 7 10 15 20 30 AC (V) DC (V)
DC
EN 60947-2 IEC 60947-2 (Icu/Ics)
3
250
7 Detailed Specifications
Number of poles Rated insulation voltage Ui (V)
d (*6)
–
d
–
d (*4), (*6)
–
–
–
d
d (*6)
–
20A or less : Screw terminal M4 30A : Screw termnal M5
Male tub terminal 6.3mm (#250) [Screw terminal M4 (series type only)]
Screw terminal M3.5
Male tub terminal 2.8mm (#110)
Srface, IEC rail mounting Flush panel mounting (option)
Panel mounting
UL(cURus), CCC (*5) EN 60934 : TUV approval EN 60947-2 : Self-declaration (*5)
UL(UR) (*9), (*10)
EN 60934 : TUV approval (*10)
– Operating characteris is Medium type (M) only. The rated current, 0.3A, 2A, 3A and 7A are not applied.
The 3-pole products are for AC use only. Contact us for operating characteristics other than those mentioned above. In poles equipped with a shunt tripping mechanism, the overcurrent tripping element is not operative (switched shunt tripping). For back-face wiring terminals, specify if it will be used with 30A, or 20A or less. UL(cURus), CCC, and CE Marking are displayed on standard products. It is recognition of UL(cURus), CCC, and TUV. In case of DC use, only DC65V is available. Specify if for DC use when ordering. Specify when ordering. (In case of CP-S UL, type name is CP-SU.) Connection is male tub terminal only. CP30-BA only.
Remarks: 1. Products for non-standard conditions are special order. (Low temperature, 1st and 2nd-degree moisture fungal treatment, corrosion-resistant) 2. Although a buzzing sound may occur when an instantaneous type becomes 80% or more of the rated current for AC use, performance is not effected. Please take this point into consideration when selecting units for use in quiet environments. 3. Please use in environments free of high temperatures, humidity, dust, corrosive gas, vibration, and impact. Also, do not use it in a circuit with inrush current or harmonics. Problems may result.
49
Detailed Specifications
2
Circuit Protectors
7
Internal circuits and examples of application Serial type
Serial type with auxiliary switch
7 Detailed Specifications
2
dRatings of alarm switches (AL) and auxiliary switches (AX)
Operating characteristics Available Instantaneous type High speed type Medium speed type Low speed type shunt model trip I F FD M MD S SD
Internal circuit
Serial type with alarm switch
Relay type shunt trip (with SHT) SHT
CP30-BA
d
d
−
d
d
d
d
−
CP-S
d
d
d
d
d
d
d
−
CP30-BA
d
d
−
d
d
d
d
−
CP-S
d
d
d
d
d
d
d
−
CP30-BA
d
d
−
d
d
d
d
−
CP-S
d
d
d
d
d
d
d
−
CP30-BA
−
−
−
−
−
−
−
d
CP-S
−
−
−
−
−
−
−
d
Parallel type shunt trip (with SHT) SHT
(1) For CP30-BA AC DC Current (A) Current (A) Voltage Voltage (V) (V) Resistive load Inductive load Resistive load Inductive load (250) (1) (0.5) 50 1 0.5 For Ratings of Max. 125 3 1 30 2 1 items other general load Min. 0.1A/15VAC 0.1A/15VDC than those shaded in For minute Max. 125 0.5 − 30 0.5 − Table 1 load Min. 1mA/24VDC, 2mA/12VDC, 5mA/6VDC (250) (1) (0.5) (50) (1) (0.5) For Ratings general Max. 125 3 (1) 30 (2), 0.5 (1) of items load Min. 0.1A/15VAC 0.1A/15VDC shaded in 125 (0.5), 0.1 − 30 (0.5), 0.1 − Table 1 For minute Max. load Min. 1mA/24VDC, 2mA/12VDC, 5mA/6VDC Remarks: 1. The switches having the ratings in parentheses are manufactured at the Remarks: 1. customer’s request. (Specify the voltage). Such switches do not conform to UL Remarks: 1. (cURus), CCC or CE Marking requirements. Classification
(2) For CP-S AC DC Current (A) Current (A) Voltage (V) Resistive load Inductive load Resistive load Inductive load 250 3 2 250 0.2 0.2 125 5 3 125 0.4 0.4 − − − 30 4 3 − − − 14 5 4 Remarks: 1. When using these switches to a circuit with a minute load (125 V AC, 0.1 A or Remarks: 1. 30 V DC, 0.1 A or less), designate the application as minute load. Voltage (V)
CP-S
−
−
−
−
−
−
−
d
CP-S
d
d
d
d
d
d
d
−
Relay type current trip
dRatings of shunt trip (SHT) coils Parallel type current trip
(1) For CP30-BA CP-S
d
d
d
d
d
d
d
Ratings
−
Rated operating voltage (V) Compatible with 100 to 200 V AC and 100 V DC 100-200 24-48 Compatible with 24 to 48 V DC
Switch type CP-S
−
−
−
−
−
−
−
Coil resistance, resistance and impedance (at25°C) Voltage (V) Impedance for AC (W) DC resistance for DC (W) 24-48 − 160 100-200 2400 2100 Remarks: 1. The allowable range is 70 to 110% of the rated voltage for AC and 75 to 120% Remarks: 1. of the rated voltage for DC. Remarks: 2. The time rating is 10 seconds or less. Configure the circuit on which voltage Remarks: 1. will not be applied for more than 10 seconds.
−
Internal accessories Auxiliary switch (AX)
(2) For CP-S Ratings
Operates in conjunction with the main circuit operating mechanism to electrically retrieve the ON/OFF status of protector.
Rated operating voltage (V) Compatible with 100 to 120 V AC (50/60Hz) 100 200 Compatible with 200 to 240 V AC (50/60Hz) 24, 48, 100 DC24, DC48, DC100
Alarm switch (AL)
Remarks (1) When the handle of CP30-BA is constrained in the ON status, it Remarks (1) does not issue the alarm signal even if it is tripped. Remarks (2) The alarm switch will be reset when the body is reset or turned on.
Shunt trip (SHT)
Switch status CP30-BA, CP-S
Protector status Off or trip AX
Inertial delay device
AXa (open) / ALa (closed) AXb (open) / ALb (closed) AXc / ALc
Off or ON
The inertial delay device is designed to avoid unnecessary operation caused by inrush current of transformer or lamp load. The device can withstand unrepeated one pulse of crest value 20 times higher than the rated current (pulse time = 8 ms). It can be added to circuits having high, medium and low speed operating characteristics. (It cannot be added to instantaneous or DC types.)
AL ON AX
AXa (closed) / ALa (open) AXb (closed) / ALb (open) AXc / ALc
Trip AL
Table 1 List of numbers of internal accessories which can be fitted 1P
AX More than one 1P 2P 3P 3P
1P
AL 2P 3P
AL+AX 1P
CP30-BA
−
−
CP-S
−
−
Remark: 1. All accessories should be fitted on the internal accessory terminal block.
50
10 sec or less
dOperation of auxiliary switch and alarm switch
A parallel relay type protector, which can break the circuit instantaneously when receiving an external signal
AX 2P 3P
Time rating
Coil resistance, resistance and impedance (at25°C) Voltage (V) Impedance for AC (W) DC resistance for DC (W) 24 − 110 48 − 110 100 1100 400 200 1100 − Remarks: 1. The allowable range is 70 to 110% of the rated voltage for AC and 75 to 120% Remarks: 1. of the rated voltage for DC. Remarks: 2. The time rating is 10 seconds or less. Configure the circuit on which voltage Remarks: 1. will not be applied for more than 10 seconds.
Operates in conjunction with the main circuit operating mechanism to electrically retrieve the tripping status of protector.
Type name
Time rating 10 sec or less
2P
3P
SHT 1P 2P 3P
AL AX AL or AX SHT AL+AX+SHT AL+SHT or AX+SHT 1P 2P 3P 3P
−
−
2 Detailed Specifications
7 Circuit Protectors
Installation and connection Installation method
With screws
On IEC rails
With embedded fittings
On panel
Appearance
Circuit protectors with AL, AX and/or SHT cannot be installed by this method. CP30-BA
d
d
d
−
CP-S
−
−
−
d
2
The operating characteristics of electromagnetic (instantaneous) type circuit protectors are not affected by the installation posture. However, when installing a fluid electromagnetic (high, medium or low speed) type circuit protector, pay attention to the installation angle because the operating current value is changed under the influence of the gravity applied to the iron core in the oil dash pot. Generally, it is recommended to use the circuit protectors in the vertical direction.
7 Detailed Specifications
Installation posture 100%
Reference for change
115%
ON
ON
95%
ON
ON
90%
120% ON ON 115% ON
ON ON
95%
100%
No change in this direction
Electric wires which can be connected and applicable screw terminals CP30-BA Classification
Body
Shape of terminal Threaded terminal (standard specification)
Cross recessed or slotted Alarm and auxiliary switch terminals
Wire retaining screw (square washer)
Cross recessed or slotted
20 A or less
30A
M4
M5
M3.5
Electric wire size used (mm2)
Applicable screw terminals
0.25-1.65
R1.25-4 R1.25-5
1.04-2.63
R2-4 R2-5
2.63-6.64
R5.5-4 R5.5-5
6.64-10.52
*8-5NS (made by JST)
0.25-1.65
R1.25-3.5
1.04-2.63
R2-3.5
Tightening torque (N • m) M4
1-1.4
M5 1.8-2.2
0.7-0.9
*Use the screw terminal 8-5NS made by JST.
51
Detailed Specifications
2
8
Low Voltage Air Circuit Breakers
Low Voltage Air Circuit Breakers (AE-SW Series) Frame (A) Model
630 AE630-SW
1000 AE1000-SW
1250 AE1250-SW
1600 AE1600-SW
2000 AE2000-SWA
2000 AE2000-SW
2500 AE2500-SW
3200 AE3200-SW
4000 AE4000-SWA
Image
2
AE1600-SW (Drawout type)
Number of poles Rated insulation voltage V Current carrying capacity of neutral pole A IEC 60947-2, EN 60947-2 AC690V BS JIS C 8201-2-1 Ann.1 Ann.2 AC600V NK, LR, GL, BV, ABS, DNV, CCS AC240-500V Ics = % Icu Rated short-time withstand current (kA symmetrical RMS) 1 second Suitability for isolation Reverse connection Without current Number of operating cycles With current
Rated breaking capacity (ka symmetrical RMS)
8 Detailed Specifications
Rated current (CT rating) In (A) Rated current setting Ir (A) (adjustable) (Rated ambient temperature 40°C) (For marine use 45°C)
(690 V AC)
Utilization category Pollution degree EMC environment condition (environment A or B) Fixed 3-pole product type 4-pole product Outline dimension (mm) Height (H) x width (W) x depth (D) Drawout 3-pole product type 4-pole product Fixed 3-pole product type 4-pole product Weight (kg) Drawout 3-pole product (Without Accessory) type 4-pole product Cradle 3-pole product only 4-pole product CE Marking CCC recognition ( Certified) Marine approval Automatic tripping device
dSee the catalog of Low Voltage Air Circuit Breakers, Y-0622, for the details.
630 (*1) 1000 1250 1600 2000 2000 (*1) 2500 3200 315-346.5-378-409.5- 500-550-600- 625-687.5-750800-880-960- 1000-1100-1200- 1000-1100-1200- 1250-1375-1500- 1600-1760-1920441-472.5-504-535.5- 650-700-750- 812.5-875-937.5- 1040-1120-1200- 1300-1400-1500- 1300-1400-1500- 1625-1750-1875- 2080-2240-2400567-598.5-630 800-850-9001000-1062.5- 1280-1360-1440- 1600-1700-1800- 1600-1700-1800- 2000-2125-2250- 2560-2720-28803040-3200 2375-2500 1900-2000 (*1) 1900-2000 950-1000 1125-1187.5-1250 1520-1600 (*1) 3, 4 (*2) 1000 630 1000 1250 1600 2000 2000 2500 3200 65 75 65 75 65 85 100% 65 75 Compatible Possible 25000 20000 5000 1500 1500 1000 B 3 A 410×340×290 410×475×290 410×425×290 410×605×290 430×300×368 430×435×368 430×385×368 430×565×368 40 41 42 47 60 61 63 50 51 52 57 72 73 75 63 64 65 70 92 93 95 77 78 79 84 113 114 116 26 31 35 36 30 35 43 44 Self-declaration Certified (NK, LR, GL, BV, ABS, DNV, CCS) Electronic (effective value detection)
4000 2000-2200-24002600-2800-30003200-3400-36003800-4000
4000
500
430×439×368 430×569×368 81 99 108 136 49 61
dWhen the MCR is provided, the breaking capacity may be changed. See the catalog of Low Voltage Air Circuit Breakers, Y-0622. dSee the catalog of Low-voltage Air Circuit Breakers, Y-0622, for the details of the accessories. Notes: *1 AE630-SW and AE2000-SW having low rating types are available. See the catalog of Low Voltage Air Circuit Breakers, Y-0622, for the details. *2 The 4-pole products do not have obtained the marine approval. *3 4 (HN) means the neutral poles current capacity is 50% of the rated current, for 4poles. 4 (FN) means the neutral poles current capacity is 100% of the rated current, for 4poles. *4 ( ) shows the value for 4P FN type. *5 Marine approval value is 138kA.
Features d Higher reliability by High operating durability (Mechanical) d Increase of rated short-time withstand current Combination of the Electronic trip relay (ETR) with MCR (*1) enables increase of the choice coordination range. d Applicability to increase and decrease of load and improvement of protection coordination The electronic tripping system enables detailed setting of tripping characteristics. The system uses RMS detection resistant to distorted waves. d More improved Electronic trip relay (ETR) and transmission functions To flexibly meet various requirements, functions suitable for purposes can be selected effectively. In addition, improved measuring functions are provided, so that the circuit breakers are applicable to CC-Link, PROFIBUS-DP and MODBUS transmission and helpful in establishing various electrical circuit measurement monitoring systems and energy-saving systems in combination with measuring display unit breakers. Notes: *1 MCR is an abbreviation for marking current release. It has INST characteristic only when the circuit breaker in the OFF state turns ON (closes). The circuit breaker will lose the INST characteristic after closing, and it will have LTD and STD characteristics.
52
d Various connections Various connections for panel structures are available. (See the following figure.) Connections Connections Model
Horizontal (standard)
Vertical (*1) (VT)
(Standard)
FIX-VT
(Standard)
(DR-VT)
Front (FT)
Vertical terminal Front terminal adapter adapter (VTA) (FTA)
Fixed type (FIX) (FIX-VTA)
(FIX-FTA)
(DR-VTA)
(DR-FTA)
Drawout type (DR) (DR-FT)
Notes: *1 For AE2000-SWA, AE4000-SWA, AE4000-SW, AE5000-SW and s: *1 AE6300-SW models, vertical terminal only is available.
2 Detailed Specifications 8 Low Voltage Air Circuit Breakers
Low Voltage Air Circuit Breakers (AE-SW Series) Frame (A) Model
4000 AE4000-SW
5000 AE5000-SW
6300 AE6300-SW
Image (Reference)
4000
5000
6300
2000-2200-2400-2600-2800-3000-3200-34003600-3800-4000
2500-2750-3000-3250-3500-3750-4000-42504500-4750-5000
3150-3465-3780-4095-4410-4725-5040-5355-56705985-6300
3, 4 (HN, FN) (*3) 1000 2500 (5000) (*4) 85 85 130 (*5) 100% 100 Compatible Possible 10000 (3P) /5000 (4P) 1000 B 3 A 414×873×290 414×1003×290 480×875×368 480×1005×368 160 180 233 256 118 133 Self-declaration Certified (NK, LR, GL, BV, ABS) Electronic (effective value detection)
2000 (4000) (*4)
Rated breaking capacity (ka symmetrical RMS)
Rated current (CT rating) In (A) Rated current setting Ir (A) (adjustable) (Rated ambient temperature 40°C) (For marine use 45°C) Number of poles Rated insulation voltage V Current carrying capacity of neutral pole A IEC 60947-2, EN 60947-2 AC690V BS JIS C 8201-2-1 Ann.1 Ann.2 AC600V AC240-500V NK, LR, GL, BV, ABS Ics = % Icu Rated short-time withstand current (kA symmetrical RMS) 1 second Suitability for isolation Reverse connection Without current Number of operating cycles With current (690 V AC)
Utilization category Pollution degree EMC environment condition (environment A or B) Fixed 3-pole product type 4-pole product Outline dimension (mm) Height (H) x width (W) x depth (D) Drawout 3-pole product type 4-pole product Fixed 3-pole product type 4-pole product Weight (kg) Drawout 3-pole product (without Accessory) type 4-pole product Cradle 3-pole product only 4-pole product CE Marking CCC recognition ( Certified) Marine approval Automatic tripping device
160 180 233 256 118 133
3150 (6300) (*4)
160 180 240 263 125 140
Electronic trip relay (ETR) Type code Additional function Extension module(EX1)
● Main setting module
● Optional setting module ● Power supply
Display(DP1) Display onto panel board(DP2) VT unit(VT)
Network BIF-CC BIF-PR BIF-MD
P1: AC DC100-240V G1: Ground fault protection WS1, WB1, WM1, AE630-1600-SW, WF1 AE2000-3200-SW, N5: Neutral pole 50% protection P2: DC24-60V AE4000-SW Wire system (when EX1 is specified) P3: AC100-240V / DC100-125V E1: Earth leakage protection WS2, WB2, WM2, AE2000-SWA, with output contact 3φ3W AP: 2nd Additional Pre-alarm WF2 AE4000-SWA, P4: DC24-60V with output contact 3φ4W NA: Without optional setting EX1 AE5000-SW Normal connection P5: DC100-240V WS3,WB3,WM3, AE6300-SW Reverse connection with output contact (SSR) ● ETR Auxiliary Equipment WF3 Normal connection: Upper terminal is connected Temperature alarm(TAL) to power supply. WS : General use MCR switch(MCR-SW) Reverse connection: Lower terminal is connected WM : Generator protection use to power supply. WB : INST/MCR only For the details of the characteristics, alarm contact output and expanded functions *The display is optional. WF : Protective coordination use of the ETR, see the catalog of Low Voltage Air Circuit Breakers, Y-0622. •
53
2 8 Detailed Specifications
dSee the catalog of Low Voltage Air Circuit Breakers, Y-0622, for the details.
AE6300-SW (Drawout type)
2
Detailed Specifications
Earth Leakage Relays
9
Earth Leakage Relays Electrical self-hold type
Model
2
Hole diameter mm 15 30 40 Model name of ZCT combined (*5) 60 80 100
NV-ZBA ZT15B ZT30B ZT40B – – –
– – – ZT60B ZT80B ZT100B
Interchangeable leakage relays (*1) Harmonic surge ready Electrical self-hold type NV-ZSA NV-ZHA ZT15B – ZT15B ZT30B – ZT30B ZT40B – ZT40B – ZT60B ZT60B – ZT80B ZT80B – ZT100B ZT100B
Mechanical self-hold type
Harmonic surge ready Mechanical self-hold type NV-ZLA ZT15B ZT30B ZT40B ZT60B ZT80B ZT100B
Phase line type
3f4W, 3f3W, 1f3W, 1f2W JIS
120 • 240 selectable
120 • 240 selectable 240 • 415 selectable
UL/JIS (*2) UL/CE (*3)
–
–
Max. operating time (s)
30 100 • 200 • 500 100 • 200 • 500 selectable selectable 0.1
30 100 • 200 • 500 100 • 200 • 500 selectable selectable 0.1
Rated sensitivity current mA
100 • 200 • 500 selectable
100 • 200 • 500 selectable (200 • 500 • 1000 selectable)
0.3 • 0.8 • 1.6 selectable 0.1 • 0.5 • 1.1
0.3 • 0.8 • 1.6 selectable 0.1 • 0.5 • 1.1
–
–
120 • 240 selectable 240 • 440 selectable
120 • 240 selectable 240 • 440 selectable 480
–
–
30 50 0.1 100 • 200 • 500 selectable 0.1 • 0.45 • 1.0 selectable – • 0.1 • 0.5 30 • 50 • 100 selectable 0.04
30 50 0.1 100 • 200 • 500 selectable 0.1 • 0.45 • 1.0 selectable – • 0.1 • 0.5 30 • 50 • 100 selectable 0.04
100 • 300 • 500 selectable 300 • 500 • 1000 selectable
100 • 300 • 500 selectable 300 • 500 • 1000 selectable
0.45 • 1.0 selectable 0.1 • 0.5 Electric type (LED)
0.45 • 1.0 selectable 0.1 • 0.5 Mechanical type (button) Push button (conbined with earth leakage indicator) 1a1c 5
Control voltage AC V
High speed type JIS Delay type
Rated sensitivity current mA
Operating time (s) (*4) Inertial non-operating time (s) or longer than (s) High Rated sensitivity current mA speed Max. operating time (s) type High UL/JIS speed Rated sensitivity current mA • Max. operating time (s) (*4) Delay type Inertial non-operating time (s) or longer than (s) High Rated sensitivity current mA speed Max. operating time (s) at 5I∆n type UL/CE
Delay type
Rated sensitivity current mA
Max. operating time (s) at 2I∆n (*4) Inertial non-operating time (s) at 2I∆n Earth leakage indication Resetting method
Built-in contact
–
–
–
–
Electric type (LED) Push button or control power switch off
Configuration Continuous current capacity A
1c 5 cosf=1
Contact capacity A
Front Rear Standard attachment (Front connection) Mass kg Relay Terminal cover External accessories Mounting hook for IEC 35mm rail (DIN rail) Fixture Max. consumption VA Connection
Conforming standard
9 Detailed Specifications
Image
US UL standard (UR certified)
120VAC 240VAC 24VDC
5 5 5
cosf=0.4 L/R=0.007 2 2 2
Mechanical type (button) Push button (conbined with earth leakage indicator) 1a1c 5 cosf=1 120VAC 240VAC 415VAC 30VDC 100VDC 200VDC
5 3 2 4 0.4 0.2
Push button or control power switch off 1a1c 5 cosf=0.4 cosf=1 L/R=0.007 120VAC 5 2 240VAC 5 2 24VDC 5 2 Use auxiliary relay for AC415V contact.
cosf=0.4 L/R=0.007 3 2 1 3 0.4 0.2
dClamp terminal –
dClamp terminal dClamp terminal
0.3 d (TC-ZBA) d (DIN-ZBA)
0.4 d (TC-ZSA) –
5 3 1 3
cosf=0.4 L/R=0.007 3 2 1 3
dClamp terminal dClamp terminal
dClamp terminal dClamp terminal
0.4 d (TC-ZSA) (*6) –
0.4 d (TC-ZSA) (*6) –
UL1053 Recognized component (File No.E196562) LR103083(Certified No.) Declaration for conformity IEC 60947-2 AnnexB EN 60947-2 AnnexB
UL1053 Recognized component (File No.E196562) LR103083(Certified No.) Declaration for conformity IEC 60947-2 AnnexB EN 60947-2 AnnexB
Mounting screw
3 –
–
Canada CSA standard
–
–
European CE marking
–
–
Notes: *1 Interchangeable leakage relays can be easily combined with other relays and our ZCT. However, products with 30mA sensitivity (excluding NV-ZHA/ZLA) can only be used in combination with ZT15B, ZT30B and ZT40B. *2 Indicates the UL-standard control voltage. UL, CSA and JIS standards are indicated together. For JIS voltage indications, 100-200V changeover is 120-240V changeover, 200-415V changeover is 240-440V changeover, and 460V and 480V are described together. When ordering, specify “UL/JIS”. *3 Indicates the UL-standard control voltage. UL, CSA and CE standards are indicated together. For CE voltage indications, 120-230V changeover is 120-240V changeover, 230-440V changeoever is 240-440V selectable, which are described together. When ordering, specify “UL/CE”. *4 When operating times are 0.3 and 0.45sec, 0.8 and 1.0sec and 1.6sec, the relay operates between 0.15 and 0.45sec, 0.6 and 1.0sec and 1.2 and 2.0sec, respectively. *5 Can be combined with an interchangeable ZCT equipped with a primary conductor. Refer to the next page for details. *6 Not UL-certified.
54
cosf=1 120VAC 240VAC 480VAC 30VDC
Remarks: 1. Relays with rates shown in parentheses are specialorder. 2. The relay complies with CE marking conformity declaration only when used with CE marking type MCCB with a voltage tripping device to interrupt current during ground fault. 3. NV-ZBA/ZSA
Control voltage Available voltage range Example of applicable circuit voltage 120V 80-126V 100 • 110V • 120V 240V 160-252V 200 • 220 • 240V 415V 320-484V 400 • 415 • 440V
4.NV-ZHA/ZLA Control voltage Available voltage range Example of applicable circuit voltage 120V 80-132V 100 • 110 • 120V 240V 160-264V 200 • 220 • 230 • 240V 440V 304-484V 380 • 400 • 415 • 440V 480V 368-528V 460 • 480V
2 Detailed Specifications
9 Earth Leakage Relays
Interchangeable ZCT ZT15B
ZT30B
ZT40B
ZT60B
ZT80B
ZT100B
Aperture diameter (mm)
15
30
40
60
80
100
Mass (kg)
0.2
0.4
0.6
2.0
2.6
3.3
185
Type
Rated short time current
50 (peak value) a
48
68
85
140
160
b
52
52
52
90
90
90
c
70
90
100
150
169
190
c
b
e
Dimensions (mm)
d a
d
25
50
50
100
100
100
e
40
40
40
70
70
70
2
ZCT aperture diameter (mm) Polyvinyl-chloride insulated wire
1f2w
Cross-linked polyethylene insulated cable
1f3w 3f3w 3f4w
15
30
40
60
80
100
Max. 600V rated wire size in mm2 (current in amperes) 14 (88)
60 (217)
150 (395)
325 (650)
600 (992)
800 (1185)
2 (33)
38 (190)
60 (260)
250 (655)
400 (870)
600 (1140)
Polyvinyl-chloride insulated wire
8 (61)
38 (162)
100 (298)
250 (556)
500 (842)
725 (1095)
Cross-linked polyethylene insulated cable
2 (33)
22 (135)
60 (260)
200 (560)
325 (760)
600 (1140)
Polyvinyl-chloride insulated wire
8 (61)
38 (162)
100 (298)
150 (395)
325 (650)
600 (992)
14 (105)
38 (190)
100 (365)
250 (655)
400 (870)
Cross-linked polyethylene insulated cable
9 Detailed Specifications
ZCT aperture diameter and wire size
–
Interchangeable ZCTs with primary conductors ZTA600A
Type
ZTA1200A
Number of poles
ZTA2000A
3
Rated voltage (VAC)
600
Rated short time current (kA)
100 (peak value)
b ba
a
c ca
a
227
227
360
b
256
298
250
ba
366
444
594
c
42
78
79
ca
125
176
214
ELRs with a ZCT with primary conductors 600
Frame (A)
1200
2000
ZSA
Type
ZHA
Interchangeable ELR and interchangeable ZCTs with primary conductors
3
Rated voltage (VAC)
600
Rated short time current (kA)
100 (peak value)
b ba
a
c ca
a
227
227
360
490
b
256
298
250
320
ba
366
444
594
868
c
42
78
79
111
ca
125
176
214
290
6.5
11
27
54
Max. operating time (s)
Inertial non-operating time (s)
0.1
—
Mass (kg)
High-speed type
Control voltage (VAC)
Rated current sensitivity (mA)
ZBA
120 • 240 (*1)
100 • 200 • 500 (*1)
ZSA
120 • 240 (*1) 240 • 415 (*1)
100 • 200 • 500 (*1)
ZBA
120 • 240 (*1)
100 • 200 • 500 (*1)
0.3 • 0.8 • 1.6 (*1)
0.1 • 0.5 • 1.1
ZSA
120 • 240 (*1) 240 • 415 (*1)
100 • 200 • 500 (*1) (200 • 500 • 1000 (*1))
0.3 • 0.8 • 1.6 (*1)
0.1 • 0.5 • 1.1
100 • 200 • 500 (*1)
0.1 • 0.45 • 1.0 (*1)
– • 0.1 • 0.5
ZHA
120 • 240 (*1) 240 • 440 (*1)
100 • 300 • 500 (*1) 300 • 500 • 1000 (*1)
0.45 • 1.0 (*1) (at 2l∆n)
0.1 • 0.5 (at 2l∆n)
120 • 240 (*1) 240 • 440 (*1) 480
100 • 200 • 500 (*1)
0.1 • 0.45 • 1.0 (*1)
– • 0.1 • 0.5
ZLA
100 • 300 • 500 (*1) 300 • 500 • 1000 (*1)
0.45 • 1.0 (*1) (at 2l∆n)
0.1 • 0.5 (at 2l∆n)
Time-delay type
(
NV-ZSA3200 NV-ZHA3200 NV-ZLA3200
ZLA Number of poles
Specification of ELRs
3200 NV-ZBA3200
ZBA
)
High-speed • Time-delay type
Note: *1 Selectable.
55
9 Detailed Specifications
MEMO
2
56
3
Special-purpose Breakers
1) Mag Only (Instantaneous Tripping Circuit Breakers)… …………………………………………………………………………………………… 58 2) DC MCCBs and DSN Switches……………………………………………………………………………………………………………………… 58 3) 400Hz MCCBs………………………………………………………………………………………………………………………………………… 58
57
3 Special-purpose Breakers 1
Mag only, DC, DSN and 400Hz
1. Mag Only (Instantaneous Tripping Circuit Breakers) Fixed
3
Adjustable
NF63-CV/SV/HV NF125-CV/SV/HV NF250-CV/SV/HV NF400-CW/SW NF630-CW/SW
AC, DC AC, DC AC, DC
NF800-SEW
AC
NF800-SDW NF1000-SEW NF1250-SEW
DC
NF1600-SEW
AC
Rated current x 10 (AC) (DC)
AC, DC
High: Rated current x 10 Low: Rated current x 2 High: 8000A Low: 3200A High: Rated current x 10 Low: Rated current x 2 High: Rated current x 10 Low: Rated current x 2 High: 8000A Low: 3200A
AC
NF1250-SDW NF1600-SDW
DC
Remarks: 1. The size, weight, accessories, etc., are all identical to the same-designation C, S and H series breakers. 2. For more details, contact your dealer.
2. DC MCCBs and DSN Switches
1 Special-purpose Breakers
3
Wiring diagram for DC usage.
Breaking is more difficult with direct currents because the current value never reaches zero. While ordinary DC breakers are suitable for low voltages, special-voltage DC breakers are recommended for voltages in excess of 250VDC. Breakers for 550V are all 4-pole models. The size, shape, drilling plan, accessories, etc., are all identical to the S Series breakers with the same designations. Model Number of poles Rated voltage (VDC) Rated breaking capacity (kA) IEC 60947-2 (Icu/Ics)
Wiring diagram for DC use. Remark: 1. The tripping characteristics will change if the wiring differs from the one shown here.
NF63-SV 3 4 400 550
NF125-SV 3 4 440 550
NF250-SV 3 4 500 600
NF400-SW 3 4 500 600
NF630-SW 3 4 500 600
NF800-SDW 3 4 500 600
NF1250-SDW 3 4 500 600
NF1600-SDW 3 4 500 600
2/2
10/10
20/20
40/40
40/40
40/40
40/20
40/20
Remark: 1. Time constant: 10ms or below.
•
DC side These breakers are designed as thyristor-Leonard system DC side breakers. They protect the thyristor from short circuiting when there is a power or Model Number of poles Rated voltage (VDC) Rated breaking capacity (kA) IEC 60947-2 (Icu/Ics) Instantaneous trip current min.)
NF125-SV 2 3 250 440 40/40
communication failure (Mag Only breakers can also be used for this purpose). Use these breakers in combination with fast fuses for even greater protection.
NF250-SV 2 3 300 500
NF400-SW 2 3 250 480
20/20
20/20
20/20
20/20
20/20
20/20
900A
1000A
1400A
2500A
3200A
10/10
3 times rated current 3 times rated current
•
DSN switches These are standard MCCBs without the automatic tripping element. The tripping capacity is about six times the rated current. Model Rated current (A) Number of poles Rated voltage (AC/DC) Max. switching current (AC/DC) Model Rated current (A) Number of poles Rated voltage (AC/DC) Max. switching current (AC/DC)
DSN63-CV 63 2
3 500/250 378/155
DSN125-CV 125 2 3 500/250 750/310
Standard MCCBs cannot be used in 400Hz circuits. When standard MCCBs are used in high-frequency circuits (eq. 400Hz), the instantaneous characteristics are shifted higher. The 400Hz MCCB is recommended for use in 400Hz circuits. Model
NF125-SV NF125-HV 16, 20, 32, 40, 16, 20, 32, 40, 50, 63, 80, 100 50, 63, 80, 100 2 3 4 2 3 4
Number of poles Rated insulation voltage (V) 690V 8/8 10/8 18/18 30/23 Rated breaking capacity 500V (kA) 440V 25/25 50/38 IEC 60947-2 (Icu/Ics) 400V 30/30 50/38 230V 50/50 100/75 Note: *1 Instantaneous trip current : Rated current x 14 (Fix)
58
NF800-SDW 2 3 250 480
NF1250-SDW 2 3 250 480
NF1600-SDW 2 3 250 480
The appearance, size, drilling plan and available accessories are all identical to similar standard S and C Series MCCBs. DSN250-CV 250 2 3 500/250 1500/625
DSN400-CW 400 2 3 600/250 2400/1000
DSN630-CW 630 3 600/250 3780/1575
DSN800-CW 800 3 600/250 4800/2000
DSN32-SV DSN63-SV DSN125-SV DSN125-SGV DSN160-SGV DSN250-SV DSN250-SGV DSN400-SW DSN630-SW DSN800-SW DSN1000-SW DSN1250-SW DSN1600-SW 32 63 125 125 160 250 250 400 630 800 1000 1250 1600 2 3 2 3 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 2 3 4 3 4 3 4 3 4 3 4 3 4 500/250 500/250 690/250 690/300 690/300 690/250 690/300 690/250 690/250 690/250 690/250 690/250 690/250 192/80 378/155 750/310 750/315 960/400 1500/625 1500/625 2400/1000 3780/1575 4800/2000 6000/2500 7500/3125 9600/4000
3. 400Hz MCCBs
Rated current (A)
NF630-SW 2 3 250 480
•
Specifications The appearance, size, rated interrupting capacity, drilling plan, accessories, etc., are all identical to the standard S and H Series breakers of the same designation.
NF250-SV 125, 150 175, 200 2 3 4
NF250-HV 125, 150 175, 200 2 3 4
NF400-SW 225, 250 300, 350 2 3 4
8/8 30/30 36/36 36/36 85/85
10/8 50/38 65/65 75/75 100/100
10/10 30/30 42/42 45/45 85/85
NF400-SEW NF630-SW (*1) NF630-SEW NF800-SEW NF1250-SEW NF1600-SEW 300-500 400-600 600-800 800-1200 200-350 400, 500 adjustable adjustable adjustable adjustable adjustable 3 4 3 4 3 4 3 4 3 4 3 4 690 10/10 10/10 10/10 10/10 25/13 25/13 30/30 30/30 30/30 30/30 65/33 65/33 42/42 42/42 42/42 42/42 85/43 85/43 50/50 50/50 50/50 50/50 85/43 85/43 85/85 85/85 85/85 85/85 125/63 125/63
Selection 1 Construction and Operation
4 60
1) Construction of MCCB……………………………………………………………………………………………………………………………… 60 2) Construction of ELCB……………………………………………………………………………………………………………………………… 62
2 Selection of MCCB and ELCB
63
1) Selecting Procedure… …………………………………………………………………………………………………………………………… 63 2) Features and Performance………………………………………………………………………………………………………………………… 64 3) Current-carrying Capacity and Operating Temperature………………………………………………………………………………………… 66 4) Application of Circuit Breaker According to Breaking Capacity………………………………………………………………………………… 68 5) Selection of Circuit Breaker for Electric Lamp or Heater Circuit… …………………………………………………………………………… 69 6) Selection of Circuit Breaker for Motor Branch Circuit…………………………………………………………………………………………… 71 7) Selection of Motor Protection Breaker… ………………………………………………………………………………………………………… 73 8) Selection of Circuit Breaker for Inverter Circuit… ……………………………………………………………………………………………… 74 9) Selection of Circuit Breaker for Transformer Primary Side… ………………………………………………………………………………… 75 10) Combination for Selective Breaking… ………………………………………………………………………………………………………… 79 11) Combination for Cascade Breaking……………………………………………………………………………………………………………… 81 12) International Standard Conformance List… …………………………………………………………………………………………………… 83
3 Selection of ELCB
86
1) Electric Shock Protection… ……………………………………………………………………………………………………………………… 86 2) ELCB Grounding Method… ……………………………………………………………………………………………………………………… 87 3) Rated Voltage and Number of Poles……………………………………………………………………………………………………………… 88 4) Earth Fault Protection Coordination and Combination of Devices… ………………………………………………………………………… 89
59
4 Selection
1
Construction and Operation
1. Construction of MCCB Arc-Extinguishing Device
Adjustable Instantaneous Tripping Current On electronic molded case circuit breakers, the instantaneous tripping current can be adjusted only by turning the knob. Therefore, optimum characteristics for load can be obtained.
MCCBs feature excellent arcextinguishing performance by virtue of the optimum combination of grid gap, shape, and material. Magnetic flux
8 10 6 4
12 16
II(×225A) Example of adjusting knob
Molded case (Base)
Molded case (Cover)
Grid
Arc
Magnetic force
Arc extinction
Contact
Switching Mechanism Overcurrent Tripping Device Detects overcurrent and trips the circuit breaker.
Ra movpid eme n
t
1 Selection
4
The contacts open and close rapidly, regardless of the moving speed of the handle, minimizing contact wear and ensuring safety.
Link-mechanism operation
Terminal
Fig. 4.1 Construction Trip Button (Push to Trip) Enables tripping mechanically from outside, for confirming the operation of the accessory switches and the manual resetting function.
Handle 1. Trip indication The automatically tripped condition is indicated by the handle in the center position between ON and OFF, the yellow (or white) line cannot be seen in this position. 2. Resetting Resetting after tripping is performed by first moving the handle to the OFF position to engage the mechanism, then returning the handle to ON to reclose the circuit. 3. Trip-Free Even if the handle is held at ON, the breaker will trip if an overcurrent flows.
ON
OFF
Trip
Handle indication 4. Contact On Mechanism Even in the worst case in which welding occurs owing to an overcurrent, the breaker will trip and the handle will maintain to ON, indicating the energizing state.
4-pole Breaker • The 4-pole breaker is designed for 3-phase 4-wire circuits. A neutral pole without an overcurrent tripping U(1) V(2) W(3) N element is provided at the right end. The construction and operation are the same as class S, H and U breakers. (Electronic molded case circuit breakers with frame size of 1600A or less have overcurrent tripping elements on the neutral poles.) • Since the four poles are simultaneously opened and closed, the user will not fail in turning on the neutral pole or carelessly open the pole. (The standard construction is designed to close the neutral pole earlier and open it later than the voltage pole.) Fig. 4.2 4-pole Breaker
60
(NF250-SV)
4 Selection 1 Construction and Operation
Automatic Tripping Devices Thermal-Magnetic Type
(
NF32-SV, NF63-CV/SV/HV, NF125-CV/SV/HV, NF250-CV/SV/HV NF400-CW/SW, NF630-CW/SW, NF800-SDW, etc. Armature Trip bar Bimetal
)
1. Time-Delay Operation An overcurrent heats and warps the bimetal to actuate the trip bar. 2. Instantaneous Operation If the overcurrent is excessive, the amature is attracted and the trip bar actuated.
Heater
Fig. 4.3
Thermal-Magnetic Type (NF1250-SDW) 1. Time-Delay Operation An overcurrent heats and warps the bimetal to actuate the trip bar. 2. Instantaneous Operation If the overcurrent is excessive, magnetization of the stationary core is strong enough to attract the armature and actuate the trip bar.
Trip bar
Latch Bimetal Armature Stationary core
4
Fig. 4.4
Heater
1. Time-Delay Operation At an overcurrent flow, the magnetic force of the coil overcomes the spring, the core closes to the pole piece, attracts the armature, and actuates the trip bar. The delay is obtained by the viscosity of silicon oil. 2. Instantaneous Operation If the overcurrent is excessive, the armature is instantly attracted, without the influence of the moving core.
Armature Pole piece Trip bar Damping spring Coil Silicon oil
Pipe
Moving core
Fig. 4.5
Principle of Electronic Trip Relay (ETR) Operation
(
(NF125-SEV/HEV, NF250-SEV/HEV, etc.) NF400-SEW~NF800-CEW NF1000-SEW~NF1600-SEW, etc. Breaking mechanism Trip coil
CPU
WDT
Trigger circuit
Input and output Load-side terminal
Test input
Characteristics setting part
Fig. 4.6.1
CT CT
Over-current indication LED
Rectifying circuit
A/D convertor
Microcomputer
CT CT
Characteristics S/W
CT
Microcomputer
Rectifying circuit
CT CT
)
Power-source side terminal Breaking mechanism Trip coil Custom C
Power-source side terminal
CT
Trigger circuit
CV A/D convertor
PSS
SSW LSW
CPU
WDT
PSW Input and
WDT: Watchdog timer circuit
1 Selection
Hydraulic-Magnetic Type (NF30-CS etc.)
Over-current indication LED Pre-alarm indication LED Pre-alarm output (Option)
WDT: output Watchdog timer Characteristics circuit Load-side setting part terminal Load-current indication LED (70%) Test input
Fig. 4.6.2
1. The current flowing in each phase is monitored by a current transformer (CT). 2. Each phase of the transformed current undergoes full-phase rectification in the rectifier circuit. 3. After rectification, each of the currents are converted by a peakconversion and an effective-value conversion circuit. 4. The largest phase is selected from the converted currents. 5. Each time-delay circuit generates a time delay corresponding to the largest phase. 6. The trigger circuit outputs a trigger signal. 7. The trip coil is excited, operating the switching mechanism.
Number of tripping devices Descriptions (e.g. 2P1E and 2P0E) are not given in the number of poles fields of some models. For these models, the same number of overcurrent tripping devices as the number of poles is provided in the circuit breakers. 2 poles: 2P2E, 3 poles: 3P3E, 4 poles: 4P4E or 4P3E (Some 4-pole models do not have overcurrent tripping devices for the neutral poles.)
61
4 Selection
1
Construction and Operation
2. Construction of ELCB Arc-Extinguishing Device ELCBs feature excellent arc-extinguishing performance by virtue Magnetic force of the optimum combination of grid gap, shape, and material.
Switching Mechanism The contacts open and close rapidly, regardless of the moving speed of the handle, minimizing contact wear and ensuring safety.
Magnetic flux
Window Frame
Grid
Since the handle, trip button, test button, leakage display button and nameplate are located in one area, it is easy to cut the panel.
Arc
Arc extinction
Sensitivity Switching Device The rated sensitivity current can be easily changed. A 3-stage switching device for 100, 200 and 500 mA and a 2-stage switching device for 200 and 500 mA are available.
Trip Button (Push to Trip) Enables tripping mechanically from outside, for confirming the operation of the accessory switches and the manual resetting function.
Leakage Display Target type with display button. The display is automatically reset by the handle.
4
Test Button
Overcurrent Tripping Device
The button has excellent durability and performance to withstand inspection at start.
The use of the proven mechanism of ELCBs ensures reliable detection of overcurrent.
The semiconductor circuit unit, which is the most important part of the device, is an electronic type using highly reliable ICs. For improvement of the function for removing harmonic and surge components, two filters are provided to prevent unnecessary operations. The ZCT detects any minute current. It is covered with a magnetic shield and never operates unnecessarily owing to motor starting current.
Fig. 4.7 Construction
Rated operational voltage 100-240V 100-440V 200-440V 100-200-415V 200-415V
Applicable circuit voltage Available voltage range 100/110/200/220/230/240V 80 to 264V 100/110/200/220/240/254/265/380/400/415/440V 80 to 484V 200/220/240/254/265/380/400/415/440V 160 to 484V 100/110/200/220/240/254/265/380/400/415/440V 80 to 484V 200/220/240/254/265/380/400/415/440V 160 to 484V
Operation 1. When an earth fault occurs, voltage is induced on the secondary side of the ZCT. 2. Factors of unnecessary operations, i.e. surge and noise components, are removed from the induced voltage. 3. The signal level is discriminated, and, when the level exceeds the specified level, the electromagnetic device is excited to trip the circuit breaker body.
Test button High voltage
Transformer
Low voltage
ZCT M 3
Overload and short-circuit
The use of the proven mechanism of ELCBs ensures reliable detection of overcurrent and earth fault to break the circuit.
Magnetic device
1 Selection
Leakage Tripping Device
EB
Revision to EN and GB Standards Products for European markets must conform to the CE Marking Directives. To affix the CE mark to a product, it is necessary that the product conforms to European Standard (EN Standard). Products for China must conform to Chinese GB Standard to affix the CCC mark. The third edition (2003) of EN Standard for circuit breakers, EN 60947-2, and GB Standard GB 14048.2 (2008) prescribe that the functions of earth leakage circuit breakers should normally work even in open phase condition. Products based on the previous EN Standard (second edition) have not been approved since June, 2006. Products based on the previous GB Standard (2001) have not been approved since January, 2011. qWS-V Series Earth Leakage Circuit Breakers (conforming to CE and CCC Standards) and UL 489 Listed Molded Case Circuit Breakers with earth leakage protection conform to the third edition of EN 60947-2 and GB 14048.2 2008 as 3-phase power supply earth leakage circuit breakers.
62
Senstivity selector
ED
Leakage display M: Motor ZCT: Zero-phase-sequence current transformer
Fig. 4.8 Circuit configuration of ELCB Fig. 4.8 (NV63-SV)
R S T Earth fault detecting electronic circuit
Fig. 4.9 Circuit diagram in 3-phase power supply ELCB
4 Selection
2
Selection of MCCB and ELCB
1. Selecting Procedure MCCB (NF) Circuit used Applicable standard
Phase and wire type, voltage, DC or AC, frequency, standard
Applicable phase and wire type 2 poles: 1-phase 2-wire 3 poles: 1-phase 2-wire, 1-phase 3-wire, 3-phase 3-wire 4 poles: 3-phase 4-wire Specification list (pages 12 to 33) List of received certifications (page 84)
Determination of rated current
Kind and size of electric wire Kind and working conditions of load Selection conditions in internal standard and electrical equipment technical standards
Relationship between temperature and electric wire (page 66) Selection of circuit breaker for motor branch circuit (page 71) Selection of circuit breaker for electric lamp or electric heater circuit (page 69) Selection of motor protection breaker (page 73) Selection of circuit breaker for inverter circuit (page 74) Selection of circuit breaker on transformer primary side (page 75)
Determination of interrupting capacity
Transformer capacity Electric wire thickness and length
Application based on breaking capacity (page 68) Table of combinations for cascade breaking (page 81)
Examination of coordination
Selective breaking
Operating characteristic curve (pages 140 to 216) Table of combinations for selective breaking (page 79)
Determination of model Use
Circuit Breakers for special purpose (pages 58)
Installation method
Connection and molded case circuit breaker
Installation and connection (pages 92 to 100) Boxed Circuit Breakers (page 130)
Accessories
Internal accessories and external accessories Electric operation
Internal accessories (pages 102 to 116) External accessories (pages 117 to 137) Electrical Operated Circuit Breakers (pages 133 to 135)
Circuit used Applicable standard
Phase and wire type, voltage, DC or AC, frequency, standard
Specification list (pages 22 to 32) List of received certifications (page 84)
Determination of rated current
Kind and size of electric wire Kind and working conditions of load Selection conditions in internal standard and electrical equipment technical standards
Relationship between temperature and electric wire (page 66) Selection of circuit breaker for motor branch circuit (page 71) Selection of circuit breaker for electric lamp or electric heater circuit (page 69) Selection of circuit breaker for inverter circuit (page 74) Selection of circuit breaker on transformer primary side (page 75)
Determination of interrupting capacity
Transformer capacity Electric wire thickness and length
Application based on breaking capacity (page 68) Table of combinations for cascade breaking (page 81)
2 Selection
4
ELCB (NV)
Determination of Purpose of protection rated sensitivity Obligation of installation current
Purpose of protection (page 86) Selection of rated sensitivity current of circuit breaker for inverter circuit (page 74) Method of switching between rated voltage and rated sensitivity current (page 246)
Examination of coordination
Operating characteristic curve (pages 180 to 203) Table of combinations for selective breaking (page 79) Combinations of ground fault protection coordination and devices (page 89)
Selective breaking Ground fault protection coordination
Determination of model Use
Circuit Breakers for special purpose (pages 58)
Installation method
Connection and molded case circuit breaker
Installation and connection (pages 92 to 100)
Accessories
Internal accessories and external accessories Electric operation
Internal accessories (pages 102 to 116) External accessories (pages 117 to 137) Electrical Operated Circuit Breakers (pages 133 to 135)
Boxed Circuit Breakers (page 130)
63
4 Selection
Selection of MCCB and ELCB
2
2. Features and Performance Features of MCCB Molded Case Circuit Breakers (NF) Table 4-1 Overcurrent trip operating time (IEC 60947-2) Rated current of circuit breaker (A) 63 or less Over 63
Occurrence of short-circuit
Operating time for 130% current Within 1 hr. Within 2 hrs.
Operation of tripping device
Relay time
Start of opening of contact
Mechanism delay time
Arc time
Max. total interrupting time
Since the relay time is normally 2 to 5 ms, if large current flows for more than this time, the circuit breaker operates instantaneously.
Fig. 4.10 Instantaneous operating time
Long time limit tripping (adjustable) Max Min
Operating time
Min Max. total interrupting time
Short time limit tripping (adjustable) Instantaneous tripping (adjustable) Max. total interrupting time
Recoverable time
Relay time Time delay tripping
Completion of breaking
Contact parting time
Max Operating time
2 Selection
4
qTime-delay trip function This function conforms to the allowable current and time characteristics of electric wire and prevents operation caused by the staring current of a load device. When the overcurrent is large, the operating time is short, and when the overcurrent is small, the operating time is long. In the case of electronic type The electronic time-delay trip function includes a long time limit trip function conforming to the allowable current and time characteristics of conductor and a short time limit trip function for selective breaking for branch NFB. The short time limit function operates after a delay of some cycles (0.06 to 0.3 s) at overcurrent exceeding the short time limit tripping current. These functions can be adjusted by the knob. wInstantaneous trip function This function breaks the circuit immediately when shortcircuit current flows. A circuit breaker on which the instantaneous tripping current is adjustable has the advantage that coordination in operation with other protective devices, such as electromagnetic switches and low-voltage air circuit breakers, can be easily obtained. The instantaneous operating time (total interrupting time) can be divided as shown in Fig. 4-10. eOperating characteristic curve The operating characteristic curve indicates the relationship between magnitude of overcurrent and operating time. The maximum-minimum operating characteristic curve indicates that the operating time is in the range. Figs. 4-11 and 4-12 show examples of operating characteristic curves.
Instantaneous tripping Current
Fig. 4.11 Example of operating characteristic curve
Long time limit tripping
Short time limit tripping
Relay time Instantaneous tripping
Current
Fig. 4.12 Example of operating characteristic curve of electronic type
Motor Protection Breakers The motor protection breakers are circuit breakers to be used to protect general induction motors. They prevent motors being burnt not only by short-circuit current of circuits, but also by overcurrent caused by overload operation and locking of motors. The Motor Protection Breakers are finely classified according to rated current so that the breakers can be applied to various types of motors. Although their time-delay trip and instantaneous trip functions are almost the same as those of MCCB, they are designed to operate within 2 seconds to 30 seconds at 600% of the rated current in consideration of protection from motor starting current and locked current.
64
There are many kinds of motors, and the motors have various allowable characteristics for overcurrent. Therefore, when applying a motor breaker, it is necessary to compare the allowable characteristics and the operating characteristics of the motor breaker. Note that, particularly, submersible motors may not be protected by ordinary motor breakers because their allowable locked time is short. When the motor starting current is large and the starting time is long and when the frequency of intermittent operation is high, motor breakers are unsuitable. In such a case, the use of a combination of an electromagnetic switch and MCCB (combination starter) is recommended.
4 Selection 2 Selection of MCCB and ELCB
Characteristics of MCCB for DC circuits When a 2-pole MCCB (250 V DC or less) is used on a DC circuit, connect the poles in series. When a 3- or 4-pole MCCB is used, refer to page 60 (for special DC voltage) or pages 14 to 21 (for DC). If the breaker is not connected as specified, its tripping characteristics and breaking performance will change, and it cannot be used.
Current-limiting characteristic Current
The current limiting refers to reduction of estimated short-circuit current depending on the circuit to prevent flow of the larger short-circuit current. The use of a class S, H or R which has excellent current-limiting characteristic or class U enables to reduce the passing energy at shortcircuiting and protect the devices in the electric circuit from electromagnetic force and thermal stress.
Conventional short-circuit current waveform
Max. peak current Passing current Time
Short-circuit current max. peak value
NF125-SV/HV (30A) NF125-SV/HV (20A) NF125-SV/HV (15A)
10 8 6
NF63-SV/HV
4 2
1
2
4
6 8 10
20
40 60 80 100
Short-circuit current r.m.s. (kA) sym.
Fig. 4.13 Passing current peak value characteristic of classes S and H (415 VAC)
Short-circuit current max. peak value
100 80 60
NF800-UEW NF400-UEW
40 NF250-UV NF125-UV
20 10 8 6 4
20 10 8 6
NF800-UEW
4
NF400-UEW
2 1 0.8 0.6
2
0.2
1
0.1
1
2
4
6 8 10
20
40 60 80100
200
NF250-UV
4
0.4 NF125-UV
1
2
4
6 8 10
20
40 60 80100
Short-circuit current r.m.s. (kA) sym.
Short-circuit current r.m.s. (kA) sym.
Fig. 4.14 Passing current peak value characteristic of classes U (415 VAC)
Fig. 4.15 Passing I²t characteristic of class U (415 VAC)
200
2 Selection
Max. peak current Ip (kA)
20
NF250-HV NF250-SV NF125-SV/HV (125A) NF125-SV/HV (40 to 100A)
Max. peak current Ip (kA)
200
40
1
(×106) 40
400
Max. passing energy I2 t (A2 · s)
(AC415V)
100 80 60
Performance Short-circuit breaking performance
Opening/closing performance
Short-circuit current corresponding to the rated interrupting capacity is interrupted. Outline of short-circuit test (IEC 60947-2) qRated limit short-circuit interrupting capacity (Icu) Operating duty: O – 3 min – CO wRated service short-circuit interrupting capacity (Ics) Operating duty: O – 3 min – CO – 3 min – CO Upper limit of temperature rise of terminal after breaking: 80K or less O duty: The circuit breaker in the ON status carries and interrupts short-circuit current. CO duty: A shorted circuit is formed, and the circuit breaker is turned on to carry and interrupt short-circuit current.
Table 4-2 shows the durability against opening and closing. See the durability against opening and closing as reference when using a circuit breaker as a switchgear. The durability against tripping by SHT (shunt tripping device), UVT (undervoltage tripping device) and trip button is 10% of the total durability against opening and closing. Note: Opening and closing operations are regarded as one time. If a circuit breaker is regularly used to trip, the life of the circuit breaker will be significantly reduced. Table 4-2 D urability of MCCB against opening and closing (IEC 60947-2) Rated current (A) 100 or less
Frequency of opening Durability against opening and closing (times) With Without and closing (times/hour) Total current flow current flow
120
1500
8500
10000
101 to 315
120
1000
7000
8000
316 to 630
60
1000
4000
5000
631 to 2500
20
500
2500
3000
2501 or more
10
500
1500
2000
65
4 Selection
2
Selection of MCCB and ELCB
3. Current-carrying Capacity and Operating Temperature Operating current vs. ambient temperature Rated current of circuit breakers is adjusted for the rated ambient temperature. This is because circuit breakers are often installed in a casing as a switchboard or a control board, and temperature of the installed place of the breaker becomes higher than ambient temperature of the wires. If temperature of the installation site of circuit breakers greatly differ from the rated ambient temperature, it is necessary to correct rated current according to the temperature correction curve (shown in the Paragraph of characteristics and outside shape in the catalog). Load current can be increased up to the rated current corrected according to ambient temperature. However, set current rating with enough allowance while taking fluctuation of power voltage and load current into consideration so that maximum operating current may not exceed the rated current.
(1) Cautionary instructions for using heat resistive wire
2 Selection
4
For using insulated wires of higher heat resistance than that of 600 V PVC insulated wire (allowable temperature 60°C), it is necessary to take the following points into consideration. For circuit breakers, size of test wire is stipulated by each test current in IEC60947-1 If size of connection wire is thinner than the test wire size, temperature of the breaker terminals increases and overcurrent tripping operation characteristic may change in some cases. (Operating time becomes shorter usually.) At motor load, for example, influence of change in operation characteristic by difference in size of connection wire is insignificant and can be disregarded because the load current is far lower than the rated current of the circuit breaker. Table 4-3 Size of test wire Range of test current (A) 0 < ≤ 8 8 12 12 15 15 20 20 25 25 32 32 50 50 65 65 85 85 100 100 115 115 130 130 115 150 175 175 200 200 225 225 250 250 275 275 300 300 350 350 400
66
Conductor size (mm2) 1.0 1.5 2.5 2.5 4.0 6.0 10 16 25 35 35 50 50 70 95 95 120 150 185 185 240
4 Selection 2 Selection of MCCB and ELCB
(2) Connection of aluminum conductors • When aluminum conductors are connected, be careful to prevent the contact resistance (due to the oxidized film of aluminum) from being increased. • The surface of the connection point of the aluminum conductors shall be properly treated by plating (zinc displacement-Copper-Silver) or by joint compound. If the treatment is done only by joint compound, reliability is low, this should be limited to when plating is impossible (eg. at site). • For aluminum cables, use compression terminals that are exclusively for aluminum cables. • The compression portion of the terminal shall be provided with taping, and the aluminum wire shall not be exposed to the atmosphere. Taping
Circuit breaker
Aluminum cable Compression terminal for aluminum cable
(3) Maximum operating current of installation without clearance between breakers In case of installation without clearance between breakers, because malfunction failures can result by heat of breaker, use the operating current not to exceed the below value. Table 4-4 Model BH BH-P CP30-BA CP-B CP-S NF30-CS NF32-SV NF63-CV NV32-SV NF63-SV NF63-HV NV63-SV NF125-CV NF125-SGV NF125-SEV NV125-CV NF125-SV NF125-LGV NF125-HEV NV125-SV NF125-HV NF125-HGV NV125-HV NF125-RGV NF160-SGV NF160-LGV NF160-HGV NF250-CV NF250-LGV NV250-CV NF250-SV NF250-SGV NV250-SV NF250-HV NF250-HGV NF250-RGV NV250-HV NF400-CW NF400-REW NF630-CW NF630-REW NF800-CEW NF800-REW
Maximum operating current
NV63-CV NV63-HV 80% of rated current
NV250-SEV NV250-HEV
NF400-SW NF400-SEW NF400-HEW NV400-CW NV400-SW NV400-SEW NV400-HEW NF400-UEW NV400-REW NF630-SW NF630-SEW NF630-HEW NV630-CW NV630-SW NV630-SEW NV630-HEW
90% of rated current
NF800-SDW NF800-SEW NF800-HEW NV800-SEW NV800-HEW NF800-UEW
67
2 Selection
4
Fig. 4.16 Example of connection of aluminum conductor
4 Selection
Selection of MCCB and ELCB
2
4. Application of Circuit Breaker According to Breaking Capacity MCCB (NF)
(
Table 4-5 230VAC 30 or less 20 or less
Frame (A)
3ph trans. capacity (kVA) 1ph trans. capacity (kVA) Breaking capacity (kA) (sym)
2.5
7.5
30 • 32
NF30-CS NF30-FAU (*1)
NF32-SV
50 • 60 • 63
NF50-FAU (*1)
NF63-CV
)
100 75
50 to 75 30 to 50 5
Class C, FAU Series Classes S, H and R The correlation between transformers and interrupting capacities is intended for short-circuiting just under the secondary voltage of 3-phase standard transformer, 210 V or 420 V, or the voltage of single-phase 3-wire transformer, 210 V.
10
150 to 300 100 to 150 15
NF63-SV
100 • 125
25
500 to 1500 200 to 300 30
35 36
50
100
125
150 170 200
NF125-SEV NF125-HEV
NF125-RGV NF125-UV NF125-HV NF250-SV NF250-HV NF250-UV NF250-RGV NF250-SEV NF250-HEV NF400-SW/SEW NF400-HEW NF400-REW NF400-UEW NF630-SW/SEW NF630-HEW NF630-REW NF800-SEW NF800-HEW NF800-REW NF800-UEW
NF125-SV
NF250-CV
400 600 • 630 800
85
NF63-HV
NF125-CV
225 • 250
2000 to 3000 −
NF400-CW NF630-CW NF800-CEW NF1000-SEW~NF1600-SEW
1000 to 4000
*1 The breaking capacity of NF30-FAU and NF50-FAU having a rated current of 5 A is 1.5 kA.
Table 4-6 440VAC
Frame (A)
1.5
50 to 100 2.5
30 • 32
NF30-CS NF32-SV
50 • 60 • 63
NF63-CV
150 to 300 7.5
10
1500 to 2000
500 to 1000 20
25
30
35 36
50
2500 to 5000 65
NF125-HV NF125-SV NF125-SEV NF125-HEV NF250-HV NF250-SV NF250-CV NF250-HEV NF250-SEV NF400-CW NF400-HEW NF400-SW/SEW NF630-CW NF630-SW/SEW NF630-HEW NF800-CEW NF800-SEW NF800-HEW
100 • 125
NF125-CV
225 • 250 400 600 • 630 800
85
125
200
NF125-UV
NF125-RV NF250-RV
NF250-UV
NF400-REW NF630-REW NF800-REW
NF400-UEW NF800-UEW
NF1000-SEW~NF1600-SEW
ELCB (NV)
Class C, FAU Series
30 or less 20 or less
3ph trans. capacity (kVA) 1ph trans. capacity (kVA) Breaking capacity (kA) (sym)
Classes S, H and R
correlation between transformers and interrupting current is intended for short-circuiting just under the secondary ( The ) voltage of 3-phase standard transformer, 210 V or 420 V, or the voltage of single-phase 3-wire transformer, 210 V.
Table 4-7 230VAC
Frame (A)
15
NF63-HV
NF63-SV
1000 to 4000
1.5
50 to 75 30 to 50
2.5
5
7.5
100 75 10
500 to 1500
150 to 300 100 to 150 200 to 300 15
25
30
2000 to 3000 −
35 36
50
85
100
125
NV32-SV
30 • 32
NV30-FAU (*1)
50 • 60 • 63
NV50-FAU (*1)
NV63-CV
100 • 125
NV63-HV
NV63-SV
NV125-SV NV125-HV NV125-HEV NV125-SEV NV250-SV NV250-HV NV250-SEV NV250-HEV NV400-SW/SEW NV400-HEW NV630-SW/SEW NV630-HEW NV800-HEW
NV125-CV NV250-CV
225 • 250 400 600 • 630 800
NV400-CW NV630-CW NV800-SEW
NV400-REW
*1 The interrupting current of NF30-FAU and NF50-FAU having a rated current of 5 A is 1.5 kA.
Table 4-8 440VAC Trans. capacity (kVA) Breaking capacity (kA) (sym) 30 • 32 50 • 60 • 63 Frame (A)
2 Selection
4
30 or less
Trans. capacity (kVA) Breaking capacity (kA) (sym)
68
100 • 125
30 or less
50 to 100 2.5
5
NV32-SV NV63-CV
NV63-SV
500 to 1000
150 to 300 7.5
10
15
25
30
1500 to 2000 35 36
50
2500 to 5000 65 70 85
NV63-HV
NV125-CV
NV125-SV
225 • 250
NV250-CV
400 600 • 630 800
NV400-CW NV630-CW NV800-SEW
NV125-HV NV125-SEV NV125-HEV NV250-SV NV250-HV NV250-SEV NV250-HEV NV400-HEW NV400-SW/SEW NV630-SW/SEW NV630-HEW NV800-HEW
NV400-REW
125
4 Selection 2 Selection of MCCB and ELCB In some lighting apparatuses, the service life of circuit breakers may be reduced by the influence of inrush current applied when the lamps are turned on. Periodically check for abnormal temperature rise of the circuit breaker in such an apparatus.
5. Selection of Circuit Breaker for Electric Lamp or Heater Circuit The maximum working current is 0.8 times the rated current of each circuit breaker.
MCCB (NF) Table 4-9 230VAC Breaking capacity (kA) 230 V AC (Icu sym) 2.5
NF30-CS BH-P
5
7.5
BH-P (110/220V)
10
15
25 30 36
50
85
NF32-SV NF63-SV
BH-P (110/220V)
125 150 170 200
NF125-HV
NF125-SV
NF63-HV
100
NF125-RGV NF125-UV
NF63-CV NF125-SV NF125-SEV
NF125-CV
NF125-HV NF125-SEV
NF250-SV NF250-SEV
NF250-CV
NF125-HV NF125-HEV
NF250-HV NF250-RGV NF250-UV NF250-HEV
NF400-SW NF400 NF400 NF400-REW NF400-SEW -HEW -UEW
NF400-CW
NF630-SW NF630 NF630-REW NF800 NF630-SEW -HEW NF800 -UEW NF800-REW NF800-SEW -HEW
NF630-CW NF800-CEW NF1000-SEW NF1250-SEW NF1600-SEW
Table 4-10 440VAC Breaking capacity (kA) 440 V AC (Icu sym)
NF30-CS
2.5
5
7.5
10
25 30 36
NF32-SV
NF32-SV
NF63-SV NF63-HV NF63-CV
NF63-CV
NF125-SV
NF125-SV
1.5
NF125-SV NF125-SEV NF125-HV NF125-SEV
Max. working Rated current of circuit current (A) breaker (A) 12 15 16 20 24 30 32 40 40 50 48 60 60 75 80 100 100 125 120 150 140 175 160 200 180 225 200 250 240 300 280 350 320 400 400 500 480 600 560 700 640 800 800 1000 960 1200 1120 1400 1280 1600
NF125-CV
NF250-SV NF250SEV
NF250-CV
45
50
70
NF125-RGV NF125-HV NF125-RGV NF125-HEV NF125-HEV
NF250-HV NF250-HEV NF400NF400-SEW HEW NF630-SW NF630NF630-SEW HEW NF800NF800-SEW HEW
NF630-CW NF800-CEW
125 150
200
NF125-HV
NF400-SW
NF400-CW
85
NF250-RGV
NF400-REW
NF 125-UV
NF 250-UV
NF400-UEW
NF630-REW NF800-UEW NF800-REW
NF1000-SEW NF1250-SEW NF1600-SEW
69
4 2 Selection
Max. working Rated current of circuit current (A) breaker (A) 12 15 16 20 24 30 32 40 40 50 48 60 60 75 80 100 100 125 120 150 140 175 160 200 180 225 200 250 240 300 280 350 320 400 400 500 480 600 560 700 640 800 800 1000 960 1200 1120 1400 1280 1600
4 Selection
2
Selection of MCCB and ELCB
ELCB (NV) Table 4-11 230VAC Breaking capacity (kA) 230 V AC (Icu sym)
Max. working Rated current current (A) (A)
2 Selection
4
12
15
16
20
24
30
32
40
40
50
48
60
60
75
80
100
100
125
120
150
140
175
160
200
180
225
200
250
240
300
280
350
320
400
400
500
480
600
560
700
640
800
2.5
5
7.5
NV32-SV
10
15
25
30
36
50
NV32-SV
85
100
125
NV125-HV NV63-HV
NV63-CV
NV63-SV
NV125-SV
NV125-CV
NV125NV125-HV HV NV125-SEV NV125HEV
NV250HV NV250HEV
NV250-SV NV250-SEV
NV250-CV
NV400-CW
NV400-SW NV400 NV400-SEW -HEW
NV630-CW
NV630-SW NV630 NV630-SEW -HEW
NV400 -REW
NV800 -HEW
NV800-SEW
Table 4-12 440VAC Breaking capacity (kA) 440 V AC (Icu sym)
Max. working Rated current (A) current (A)
70
12
15
16
20
24
30
32
40
40
50
48
60
60
75
80
100
100
125
120
150
140
175
160
200
180
225
200
250
240
300
280
350
320
400
400
500
480
600
560
700
640
800
2.5
5
7.5
10
NV32-SV NV63-SV
NV63-CV
NV63-HV
25
30
NV125-SV
36
45
50
70
85
125
NV125-HV
NV63-CV NV125-HV NV125NV125-SV NV125-SEV NV125-HV HEV NV125-HEV NV125-SEV
NV125-CV
NV250-SV NV250-SEV
NV250-CV
NV400-CW
NV630-CW NV800-SEW
NV250-HV NV250-HEV
NV400SW NV400-SEW
NV400HEW
NV630-SW NV630 NV630-SEW -HEW NV800 -HEW
NV400-REW
4 Selection 2 Selection of MCCB and ELCB
6. Selection of Circuit Breaker for Motor Branch Circuit
(direct-to-line starting or Y-∆ starting) Motor is protected from overload by electromagnetic switch. Circuit breaker is installed to protect circuit from short-circuit.
MCCB (NF) Table 4-13 200/220VAC for 3-phase induction motor
Electromagnetic switch M
0.4 2.1 N10-N21
2.1 NF30-CS 5 NF32-SV 5
0.75 3.7 N10-N21
3.6 NF30-CS 10 NF32-SV 10 NF63-SV 10 NF63-HV 10
NF125-SV (15)
1.5 6.4 N10-N25 2.2 9.1 N10-N35 3.7 15 N18-N35 N25·N35· 5.5 22 N50·N65 7.5 29 N35·N50-N80 11 44 N50-N95 15 55 N65-N125
6.6 NF30-CS 15 NF32-SV 15 NF63-SV 15 NF63-HV 15 9 NF30-CS 20 NF32-SV 20 NF63-SV 20 NF63-HV 20 15 NF30-CS 30 NF32-SV 30 NF63-SV 30 NF63-HV 30
NF125-SV (15) NF125-SV 20 NF125-SV 30
NF125-HV NF125-HV NF125-HV NF125-HV
22
NF63-CV 50 NF63-SV 50 NF63-HV 50
NF125-SV 50
NF125-HV 50
NF125-UV 50
29 42 54
NF63-CV 60 NF63-SV 60 NF63-HV 60
NF125-SV 60 NF125-CV 75 NF125-SV 75 NF125-CV 100 NF125-SV 100
NF125-HV 60 NF125-HV 75 NF125-HV 100
NF125-UV 60 NF125-UV 75 NF125-UV 100
NF63-SV 5 NF63-HV (10)
NF125-SV (15)
Y-∆ starting Direct-to-line starting
22 5.5 22 NF63-CV 50 NF63-SV 50 NF63-HV 50 NF125-SV — 29 7.5 29 NF63-CV 60 NF63-SV 60 NF63-HV 60 NF125-CV 60 NF125-SV — 42 11 44 — NF125-CV 75 NF125-SV 54 15 55 — NF125-CV 100 NF125-SV 67 18.5 67 N80-N125 NF125-CV 100 NF125-SV 82 22 85 N95-N150 NF250-CV 150 105 30 110 N125-N220 NF250-CV 175 125 37 130 N150-N220 NF250-CV 225 150 45 164 N180-N400 NF400-CW 180 55 195 N220-N400 NF630-CW 75 267 N300·N400·(N600) 250 NF630-CW 90 320 N300·N400·(N600·N800) 330 NF800-CEW 110 385 N300·N400·(N600·N800) 330 NF800-CEW 500 132 470 (N600·N800) 500 160 580 (N600·N800) 600 200 720 (N800) Notes *1 The breaking capacity of NF250-CV is 36kA. *2 The breaking capacity of NF1000- to 1600-SEW is 125kA.
50 60 75 100 100
400 500 600 600 600
NF125-UV (15)
NF125-HV (15)
NF250-SV NF250-SV NF250-SV NF400-SW NF400-SW NF630-SW NF630-SW NF630-SEW
150 175 225 300 300 500 600 600
NF125-HV NF125-HV NF125-HV NF125-HV NF125-HV NF250-HV NF250-HV NF250-HV NF400-HEW NF400-HEW NF400-HEW NF630-HEW NF630-HEW
NF125-UV (15)
(15) 15 20 30
50 60 75 100 100 150 175 225 250 300 400 500 600
NF125-UV (15) NF125-UV 20 NF125-UV 30
NF400-REW NF400-REW NF400-REW NF630-REW NF630-REW NF1000-SEW NF1250-SEW NF1600-SEW
250 300 400 500 600 700 800 1000
NF125-UV NF125-UV NF125-UV NF125-UV NF125-UV NF250-UV NF250-UV NF250-UV NF400-UEW NF400-UEW NF400-UEW NF800-UEW NF800-UEW
50 60 75 100 100 150 175 225 250 300 400 500 600
4 2 Selection
Direct-to-line starting
Breaking capacity (kA) 230 V AC (Icu sym) For 4-pole Electromagnetic motor contactor 150(*2) 2.5 7.5 15 25 30(*1) 50 85 100 200 Heater Type Output Fullload Model Model Model Model Model Model Model Model Model nominal Model Rating Rating Rating Rating Rating Rating Rating Rating Rating Rating name (kW) current (A) (A) 0.7 0.1 0.7 NF125-HV (15) N10-N21 NF30-CS (3) NF32-SV (3) NF63-SV (3) NF63-HV (10) NF125-SV (15) NF125-UV (15) 1.3 0.2 1.2
Direct-to-line starting
Table 4-14 400/440VAC for 3-phase induction motor For 4-pole motor Output Fullload (kW) current (A) 0.2 0.6 0.4 1.1 0.75 1.9 1.5 3.2 2.2 4.6 3.7 7.5 5.5 11 7.5 15 11
22
15 18.5 22 30 37 45
28 34 42 55 65 82
Electromagnetic contactor Model N10-N21 N10-N21 N10-N21 N10-N21 N10-N21 N11-N35 N18-N35 N20-N35 • N50 N25 • N35 • N50 • N65 N35 • N50-N80 N50-N95 N50-N95 N65-N125 N80-N150 N95-N150
1.5
2.5
Breaking capacity (kA) 415 V AC (Icu sym) 10 25 30(*1) 50(*2)
7.5
Heater nominal (A)
Model
Rating
Model
Rating
Model
Rating
Model
Rating
0.7 1.3 1.7 3.6 5 6.6 11 15
NF30-CS NF30-CS NF30-CS NF30-CS NF30-CS NF30-CS NF30-CS NF30-CS
(3) (3) 5 10 10 20 30 30
NF32-SV NF32-SV NF32-SV NF32-SV NF32-SV NF32-SV NF32-SV NF32-SV
(3) (3) 5 10 10 20 30 30
NF63-SV NF63-SV NF63-SV NF63-SV NF63-SV NF63-SV NF63-SV NF63-SV
(3) (3) 5 10 10 20 30 30
NF63-HV NF63-HV NF63-HV NF63-HV NF63-HV NF63-HV NF63-HV NF63-HV
10 10 10 10 10 20 30 30
22
50 NF63-CV 50 NF63-SV 50 NF63-HV 50
28 35 42 54 67 82
NF63-CV 60 NF63-SV 60 NF63-HV NF63-CV 60 NF63-SV 60 NF125-CV NF125-CV NF125-CV NF125-CV
60 60 75 100 100
Model
Rating
70
Model
Rating
Model
Rating
NF125-SV NF125-SV NF125-SV NF125-SV NF125-SV NF125-SV NF125-SV NF125-SV
(15) (15) (15) (15) (15) 20 30 30
NF125-HV NF125-HV NF125-HV NF125-HV NF125-HV NF125-HV NF125-HV NF125-HV
(15) (15) (15) (15) (15) 20 30 30
Model
150(*3) Rating
NF125-SV 50 NF125-HV 50 NF125-SV NF125-SV NF125-SV NF125-SV NF125-SV NF250-CV 125 NF250-SV
60 60 75 100 100 125
NF125-HV NF125-HV NF125-HV NF125-HV NF125-HV
Model
Rating
200 Model
Rating
NF125-UV NF125-UV NF125-UV NF125-UV NF125-UV NF125-UV NF125-UV NF125-UV
(15) (15) (15) (15) (15) 20 30 30
NF125-UV 50
60 60 75 100 100 NF250-HV 125
NF125-UV NF125-UV NF125-UV NF125-UV NF125-UV NF250-UV
60 60 75 100 100 125
Y-∆ starting Direct-to-line starting
11 5.5 11 NF63-CV 30 NF63-SV 30 NF63-HV 30 NF125-SV 30 NF250-HV 30 NF125-UV 30 − 15 7.5 15 − NF63-CV 40 NF63-SV 40 NF63-HV 40 NF125-SV 40 NF250-HV 40 NF125-UV 40 22 11 22 − NF63-CV 50 NF63-SV 50 NF63-HV 50 NF125-SV 50 NF250-HV 50 NF125-UV 50 28 15 28 − NF63-CV 60 NF63-SV 60 NF125-CV 60 NF125-SV 60 NF250-HV 60 NF125-UV 60 35 18.5 34 − NF63-CV 60 NF63-SV 60 NF125-CV 60 NF125-SV 60 NF250-HV 60 NF125-UV 60 42 22 42 − NF125-CV 75 NF125-SV 75 NF250-HV 75 NF125-UV 75 54 30 55 − NF125-CV 100 NF125-SV 100 NF250-HV 100 NF125-UV 100 67 37 65 − NF125-CV 100 NF125-SV 100 NF250-HV 100 NF125-UV 100 82 45 82 − NF250-CV 150 NF250-SV 150 NF250-HV 150 NF250-UV 150 105 55 96 N125-N220 NF250-CV 175 NF250-SV 175 NF250-HV 175 NF250-UV 175 125 75 134 N150-N220 NF250-CV 225 NF250-SV 225 NF250-HV 225 NF250-UV 225 150 90 160 N180-N400 NF250-HEV 225 NF400-REW 225 NF400-UEW 225 NF250-SEV 225 180 110 192 N180-N400 NF400-SW 350 NF400-HEW 300 NF400-REW 300 NF400-UEW 300 250 132 233 N220-N400 NF400-SW 400 NF400-HEW 400 NF400-REW 400 NF400-UEW 400 160 290 N300 • N400 • (N600) 250 NF630-SW 500 NF630-HEW 500 NF630-REW 500 NF800-UEW 500 200 360 N300 • N400 • (N600 • N800) 330 NF630-SW 600 NF630-HEW 600 NF630-REW 600 NF800-UEW 600 220 389 N300 • N400 • (N600 • N800) − NF630-SW 600 NF630-HEW 600 NF630-REW 600 NF800-UEW 600 250 430 (N600 • N800) 500 NF630-SEW 700 NF630-HEW 600 NF630-REW 600 NF800-UEW 700 300 500 (N600 • N800) 500 NF800-SEW 700 NF800-HEW 700 NF800-REW 700 NF800-UEW 700 Notes *1 The breaking capacity of NF250-SV and NF250-SEV is 36kA. *2 The breaking capacity of NF400-SW is 45kA. *3 The breaking capacity of NF400- to 800-REW is 125kA. Remarks: 1. Circuit breakers are selected under the starting conditions shown in the right table. 2. Protection coordination is examined under the condition of cold start at 40°C. Starting conditions for selection 3. The ratings in parentheses apply to cases where thermal relays with saturating reactor are used. Direct-to-line Startup inrush current (× full-load current) 4. Although the inrush current upon switching to ∆ connection fluctuates depending on the residual magnetic flux at star starting time Motor capacity starting, ∆ connection closing phase or power supply transformer capacity, in most cases, the inrush current is less than Direct-to-line starting Y-∆ starting (600%) the values shown in the right table. 0.2 to 7.5kW 10s 12 times 16 times 5. The maximum starting current is the effective value of current (value after transient phenomena disappear) at the time 11 to 55 10 12 17 when the rotator starts to rotate. 6. It was assumed that the Y-∆ starting would be performed by the open transition method which is a general method but is 75 to 300 10 14 18 known to carry large transient inrush current.
71
4 Selection
2
Selection of MCCB and ELCB
ELCB (NV) Table 4-15 200/220VAC for 3-phase induction motor
Y-∆ starting Direct-to-line starting
Direct-to-line starting
Breaking capacity (kA) 230 V AC (Icu sym) For 4-pole Electromagnetic motor contactor 50 30(*2) 7.5 15(*1) 25 85 150 100 2.5 FullHeater Output load nominal Model Model Rating Model Rating Model Rating Model Rating Model Rating Model Rating Model Rating Model Rating Model Rating current (A) (kW) (A) 0.1 0.7 0.7 NV125-SV (15) N10-N21 NV125-HV (15) NV30-CS (5) NV63-CV (5) NV32-SV (15) NV63-HV (15) 0.2 1.2 1.3 NV125-SV (15) NV125-HV (15) 0.4 2.1 N10-N21 2.1 NV30-CS 5 NV63-CV 5 NV32-SV (15) NV63-HV (15) NV125-SV (15) NV125-HV (15) 0.75 3.7 N10-N21 3.6 NV30-CS 10 NV63-CV 10 NV32-SV (15) NV63-HV (15) NV125-SV 15 NV125-HV (15) 1.5 6.4 N10-N25 6.6 NV30-CS 15 NV63-CV 15 NV32-SV 15 NV63-HV 15 NV125-SV 20 NV125-HV 20 2.2 9.1 N10-N35 9 NV30-CS 20 NV63-CV 20 NV32-SV 20 NV63-HV 20 NV125-SV 30 NV125-HV 30 3.7 15 N18-N35 15 NV30-CS 30 NV63-CV 30 NV32-SV 30 NV63-HV 30 NV125-SV 50 NV63-CV 50 NV63-SV 50 NV63-HV 50 NV125-HV 50 5.5 22 N25 • N35 • N50 • N65 22 NV125-SV 60 NV63-CV 60 NV63-SV 60 NV63-HV 60 NV125-HV 60 7.5 29 N35 • N50-N80 29 NV125-CV 75 NV125-SV 75 NV125-HV 75 11 44 N50-N95 42 NV125-CV 100 NV125-SV 100 NV125-HV 100 15 55 N65-N125 54 NV125-SV 50 NV63-CV 50 NV63-SV 50 NV63-HV 50 NV125-HV 50 5.5 22 22 − NV63-CV 60 NV63-SV 60 NV63-HV 60 NV125-CV 60 NV125-SV 60 NV125-HV 60 7.5 29 29 − NV125-CV 75 NV125-SV 75 NV125-HV 75 11 44 42 − NV125-CV 100 NV125-SV 100 NV125-HV 100 15 55 54 − NV125-CV 100 NV125-SV 100 NV125-HV 100 18.5 67 N80-N125 67 NV250-CV 150 22 85 N95-N150 82 NV250-SV 150 NV250-HV 150 NV250-CV 175 30 110 N125-N220 105 NV250-SV 175 NV250-HV 175 NV250-CV 225 37 130 N150-N220 125 NV250-SV 225 NV250-HV 225 NV400-CW 400 NV400-SW 300 NV400-HEW 250 NV400-REW 250 45 164 N180-N400 150 NV630-CW 500 NV400-SW 300 NV400-HEW 300 NV400-REW 300 55 195 N220-N400 180 NV630-CW 600 NV400-SEW 400 NV400-HEW 400 NV400-REW 400 75 267 N300 • N400 • (N600) 250 90 320 N300 • N400 • (N600 • N800) 330 NV630-SEW 500 NV630-HEW 500 110 385 N300 • N400 • (N600 • N800) 330 NV630-SEW 600 NV630-HEW 600 Notes *1 The breaking capacity of NV32-SV is 10kA. *2 The breaking capacity of NV250-CV is 36kA.
Direct-to-line starting
Table 4-16 400/440VAC for 3-phase induction motor For 4-pole motor Output Fullload (kW) current (A) 0.2 0.6 0.4 1.1 0.75 1.9 1.5 3.2 2.2 4.6 3.7 7.5 5.5 11 7.5 15 11 22 15 28 18.5 34 22 42 30 55 37 65 45 82
Electromagnetic contactor
2.5
Model
Heater nominal (A)
N10-N21 N10-N21 N10-N21 N10-N21 N10-N21 N11-N35 N18-N35 N20-N35 • N50 N25 • N35 • N50 • N65 N35 • N50-N80 N50-N95 N50-N95 N65-N125 N80-N150 N95-N150
0.7 1.3 1.7 3.6 5 6.6 11 15 22 28 35 42 54 67 82
5
Breaking capacity (kA) 415 V AC (Icu sym) 10 25 30(*1)
7.5
Model
Rating
Model
Rating
Model
Rating
Model
Rating
NV63-CV NV63-CV NV63-CV NV63-CV NV63-CV NV63-CV NV63-CV NV63-CV NV63-CV NV63-CV
(5) (5) 5 10 10 20 30 30 50 60
NV32-SV NV32-SV NV32-SV NV32-SV NV32-SV NV32-SV NV32-SV NV32-SV
(5) (5) 5 10 10 20 30 30
NV63-SV NV63-SV NV63-SV NV63-SV NV63-SV NV63-SV NV63-SV NV63-SV NV63-SV NV63-SV
(5) (5) 5 10 10 20 30 30 50 60
NV63-HV NV63-HV NV63-HV NV63-HV NV63-HV NV63-HV NV63-HV NV63-HV NV63-HV NV63-HV NV125-CV NV125-CV NV125-CV NV125-CV
(15) (15) (15) (15) (15) 20 30 30 50 60 60 75 100 100
Model
Rating
Model
NV125-SV NV125-SV NV125-SV NV125-SV NV125-SV NV125-SV NV125-SV NV125-SV NV125-SV NV125-SV NV125-SV NV125-SV NV125-SV NV125-SV NV250-CV 125 NV250-SV
50(*2)
70
Rating
Model
Rating
(15) (15) (15) (15) (15) 20 30 30 50 60 60 75 100 100 125
NV125-HV NV125-HV NV125-HV NV125-HV NV125-HV NV125-HV NV125-HV NV125-HV NV125-HV NV125-HV NV125-HV NV125-HV NV125-HV NV125-HV
(15) (15) (15) (15) (15) 20 30 30 50 60 60 75 100 100
Model
125 Rating
Model
Rating
NV250-HV 125
11 NV63-CV 30 NV32-SV 30 NV63-SV 30 NV63-HV 30 NV125-SV 30 NV125-HV 30 5.5 11 − 15 NV63-CV 40 7.5 15 NV125-SV 40 NV125-HV 40 − NV63-SV 40 NV63-HV 40 22 NV63-CV 50 11 22 − NV125-SV 50 NV125-HV 50 NV63-SV 50 NV63-HV 50 28 NV63-CV 60 15 28 − NV125-SV 60 NV125-HV 60 NV63-SV 60 NV125-CV 60 35 18.5 34 − NV125-SV 60 NV125-HV 60 NV125-CV 60 42 22 42 − NV125-SV 75 NV125-HV 75 NV125-CV 75 54 30 55 − NV125-SV 100 NV125-HV 100 NV125-CV 100 67 37 65 − NV125-SV 100 NV125-HV 100 NV125-CV 100 82 45 82 NV250-CV 150 NV250-SV 150 − NV250-HV 150 105 55 96 N125-N220 NV250-CV 175 NV250-SV 175 NV250-HV 175 125 75 134 N150-N220 NV250-CV 225 NV250-SV 225 NV250-HV 225 150 90 160 N180-N400 225 NV250-HEW 225 NV400-REW 225 NV250-SEW 225 180 110 192 N180-N400 NV400-SW 350 NV400-HEW 300 NV400-REW 300 250 132 233 N220-N400 NV400-SW 400 NV400-HEW 400 NV400-REW 400 160 290 N300 • N400 • (N600) 250 NV630-SEW 500 NV630-HEW 500 200 360 N300 • N400 • (N600 • N800) 330 NV630-SEW 600 NV630-HEW 600 Notes *1 The breaking capacity of NV250-SV and NV250-SEV is 36kA. *2 The breaking capacity of NV400-SW is 45kA. Remark: 1. For the selecting conditions, please refer to the remarks on page 73.
Y-∆ starting Direct-to-line starting
2 Selection
4
Example of Y-∆ starting current waveform (crest value envelope) Pump load S phase current Steady load current crest value = 2×283A Inrush current crest value at switching to ∆ connection6680A
Operation in Y connection
72
Operation in ∆ connection
4 Selection 2 Selection of MCCB and ELCB
7. Selection of Motor Protection Breaker Motor Protection Breakers
In principle, the operating characteristic curve of a selected motor breaker must be lower than the heat characteristic of the motor. The following table shows the rated capacities of standard squired‑cage 3-phase motors (4-pole) made by Mitsubishi Electric. The starting conditions are shown in the table.
Table 4-17 for 3-phase induction motor NF32-SV
NF63-CV
NF63-SV
NF125-SV
NF250-SV
230V
7.5
7.5
15
50
85
415V
2.5
2.5
7.5
30
36
2
32 A or less: 2 40 A or more: 7
32 A or less: 2 40 A or more: 7
32 A or less: 2 40 A or more: 7
5
1200
1200
1200
1200
1100
Rated current
Rated current
Rated current
Rated current
Rated current
Model Motor Protection Breaker Rated breaking capacity (kA)
600% starting time limit (s) Startup inrush current limit (%) Example of rated capacity of motor (kW) 200/220V 400/440V
Model for combination with electromagnetic contactor
0.4 0.2
4
0.75 N10-N21
0.75
2 Selection
0.4
1.5
4
4
4
2.2
5
5
5
3.7
7.1 8
7.1 8
7.1 8
5.5
10 12
10 12
10 12
(12.5)
7.5
16
16
16
(16)
1.5
N11-N35 2.2 3.7
N18-N35 N20-N35 N50 N25 • N35 N50 • N65
5.5
11
25
25
25
(25)
7.5
15
32
32
32
32
11
18.5 22
40 45
40 45
(40) 45
15 18.5
30 37
63 71
22
45 55 55
90 100
N35 N50-N80 N50-N95 N65-N125
30 37 45
75 90
55
110
N80-N125 N90-N125 N125-N220 125 150 175 200 225
N150-N400 N180-N400 N220-N400
Remarks: 1. Fot the rated curent in parentheses, breakers will be manufactured to order. 2. The approximate values of inrush current at direct-to-line starting are shown below. Up to 7.5 kW: 1000% 11 kW or more: 1200% 75 kW or more: 1400% When the starting current is large and the starting power factor is low, a combination with an electromagnetic switch selected in accordance with “Table of selection of circuit breaker for motor branch circuit” shown on page 73 is suitable. Cautions (1) Note that any circuit breaker operates when the startup inrush current, starting current and starting time exceed the conditions shown in the above table. Particularly, high-efficiency motors generally have higher starting current and lower starting torque compared to general-purpose motors, and motor breakers cannot be used for such motors. (2) Note that a circuit breaker may operate when an electromagnetic contactor is opened or closed while a motor is running. (3) Select a motor breaker having rated current approx. 1.0 to 1.1 times higher than the full load current of motor.
73
4 Selection
2
Selection of MCCB and ELCB
8. Selection of Circuit Breaker for Inverter Circuit Selection of Circuit Breaker for Inverter Circuit
Power supply
Since current containing harmonic components will flow, the rated current of circuit breaker must be approx. 1.4 times the inverter input current. NFB
R
U
Inverter
S
V
T
W
Motor
IM
Note The life cycle of the circuit breaker for the circuit on the inverter primary side will be reduced under the influence of transient inrush current. Install a switch.
Table 4-18 3-phase 200 V class Inverter input capacity Rated current of circuit breaker Inverter input capacity Rated current of circuit breaker kVA A kVA A 5.5 30 41 175 9 40 52 225 12 50 66 300 17 75 80 350 20 100 100 500 28 125 110 500 34 150 132 600
Selection of rated sensitivity current of Earth Leakage Circuit Breaker for Inverter Circuit Select the rated sensitivity current as stated below. Circuit breakers for harmonics and surge: Rated sensitivity current I∆n 10 × {Ig1 + Ign + Ig2 + Igm} General circuit breakers: Rated sensitivity current I∆n 10 × {Ig1 + Ign + 3 × (Ig2 + Igm)} Example 1
6mm 2×5m
NV
4
Noise filter
2 Selection
I 1
6mm 2×20m
Table 4-19-1 Examples of leakage current from line when IV cable is wired in close contact with ground (wiring in metallic conduit) (3-phase 220V 60Hz) Wire size mm2 6 10 16 25 35 50 70 95
Ig1, Ig2: Leakage current from line Ign: Leakage current from noise filter on inverter input side Igm: Leakage current from motor operating on commercial power supply 3-phase
Inverter
I n
Install MCCB or ELCB on the primary side (power supply side) of the inverter. If it is installed on the secondary side, it may cause electronic circuit trouble or overheating.
IM 220V 2.2kW I 2
Leakage current/km mA 135 140 169 176 203 205 241 247
I m
Table 4-19-2 Example of leakage current from 3-phase induction motor (220V 60Hz)
Example 2 50mm 2×5m NV
Noise filter
I 1
I n
Motor output (kW) 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37
50mm 2×20m
3-phase
Inverter
IM 220V 22kW I 2
I m
Example of selection 1 General breaker Breaker for harmonics and surge 5 5 Leakage current Ig1 135 × = 0.675 135 × = 0.675 1000 1000 Leakage current Ign 0 (without noise filter) 20 20 Leakage current Ig2 135 × = 2.7 135 × × 3 = 8.1 1000 1000 Leakage current Igm 0.18 × 3 = 0.54 0.18 Total leakage current Ig 11.465 3.555 Rated sensitivity 200 100 current (> Ig × 10)
Leakage current (mA) 0.2 0.29 0.32 0.42 0.55 0.63 0.72 0.8 0.96 1.1
Example of selection 2 Leakage current Leakage current Leakage current
Breaker for harmonics and surge General breaker 5 5 205 × = 1.025 205 × = 1.025 1000 1000 Ign 0 (without noise filter) 20 20 Ig2 205 × = 4.1 205 × = 12.3 1000 1000 Igm 0.72 × 3 = 2.16 0.72 Ig 15.485 5.845 Ig1
Leakage current Total leakage current Rated sensitivity current (> Ig × 10)
100
500
Remarks: 1. Circuit breakers for harmonics and surge can detect earth fault on the secondary side of inverter only when the operating frequency is 120 Hz or less. In the case of star connection by neutral point grounding method, the sensitivity current for earth fault on the inverter secondary side is degraded. In this case, for protective ground for load device, apply Class C grounding (10 Ω or less). 2. For general circuit breakers, the leakage current from the line between inverter and motor shall be calculated as three times the leakage current at the commercial frequency in consideration of harmonic content. 3. For the model names of circuit breakers for harmonics and surge, refer to the specification list in Section 2 of this document. Models not for harmonics and surge are general breakers.
74
4 Selection 2 Selection of MCCB and ELCB
9. Selection of Circuit Breaker for Transformer Primary Side Notes 1. The life cycle of the circuit breaker for the circuit on the transformer primary side will be significantly reduced under the influence of excited inrush current. Install a switch to open and close the circuit. 2. Select a circuit breaker based on the example of excited inrush current of each transformer. When using a circuit breaker for a transformer, check the magnitude of excited inrush current with the transformer manufacturer.
Single-phase 210-V Table 4-20-1 MCCB Example of transformer excited inrush current 2 Crest Rating value of Model first wave A (multiple) NF63-CV(*1) NF125-CV(*1) NF125-CV, NF125-SV
50 60 75
NF125-SEV NF125-CV(*1) NF250-CV, NF250-SV NF125-CV(*1) NF250-CV, NF250-SV NF250-SEV
50 75 125 100 150 125
35
NF250-CV, NF250-SV NF250-SEV
35
5
23.8
45
NF125-CV(*1) NF125-CV, NF125-SV, NF125-HV NF125-SEV, NF125-HEV
60 100 50
37
7.5
35.7
45
NF250-CV, NF250-SV, NF250-HV NF250-SEV, NF250-HEV
150 125
37
10
47.6
43
NF250-CV, NF250-SV, NF250-HV NF250-SEV, NF250-HEV
200 125
37
15
71.4
43
20
95.2
43
30
143
37
50
238
35
75
357
30
100 150 200 300 500
476 714 952 1429 2381
27 24 21 17 −
NF400-CW NF400-SW NF400-SEW, NF400-HEW NF400-SW NF400-SEW, NF400-HEW NF400-SEW, NF400-HEW NF630-SW NF630-SEW(*1) NF1000-SEW NF800-SEW(*1) NF1250-SEW NF1000-SEW − − − −
400 300 200 400 200 200 500 300 500 400 600 800 − − − −
Example of transformer excited inrush current 3 Crest Rating value of Model first wave A (multiple) 30 NF63-CV(*1) 50 NF63-CV, NF63-SV 24 (50) NF125-CV(*2) 50 NF125-SV 50 NF63-CV(*1) 24 60(50) NF125-CV(*1)(*2) 75 NF125-CV, NF125-SV 24
NF125-CV(*1) NF125-CV, NF125-SV
60 100
225 125
23
NF125-CV(*1) NF250-CV, NF250-SV
100 150
NF400-SW NF400-SEW
350 200
23
34
NF400-SEW
200
23
34
NF630-SEW
300
23
NF250-CV, NF250-SV NF250-SEV NF400-SW NF400-SEW NF400-SEW(*1) NF630-SEW
200 125 300 200 300 300
29
NF800-SEW(*1)
400
22
NF630-SEW
400
28 24 22 18 17
NF1600-SEW
800 − − − −
20 19 19 16 −
NF800-SEW(*1) NF1600-SEW − − −
600 800 − − −
− − − −
Table 4-20-2 ELCB Example of transformer excited inrush current 1 Transformer Rated Crest capacity primary value of Rating Model current first wave kVA A A (multiple)
75 50
NV125-SEV NV250-CV, NV250-SV NV250-CV, NV250-SV NV250-SEV
50 125 150 125
35
NV250-CV, NV250-SV NV250-SEV
225 125
23
35
NV400-SW NV400-SEW
350 200
23
34
NV400-SEW
200
23
−
34
NV630-SEW
300
23
− − − − − −
29 28 24 22 18 17
− − − − − −
22 20 19 19 16 −
100 50
NV250-CV, NV250-SV, NV250-HV NV250-SEV, NV250-HEV NV250-CV, NV250-SV, NV250-HV NV250-SEV, NV250-HEV NV400-CW NV400-SW NV400-SEW, NV400-HEW NV400-SW NV400-SEW, NV400-HEW NV400-SEW, NV400-HEW NV630-SEW
150 125 200 125 400 300 200 400 200 200 300
23.8
45
7.5
35.7
45
10
47.6
43
15
71.4
43
20
95.2
43
30
143
37
50
238
35
−
75 100 150 200 300 500
357 476 714 952 1429 2381
30 27 24 21 17 −
− − − − − −
Example of transformer excited inrush current 3 Crest Rating value of Model first wave A (multiple) 50 NV63-CV, NV63-SV 60 NV125-CV 24 50 NV125-SV 50 NV125-SEV 75 NV125-CV, NV125-SV 24 50 NV125-SEV 100 NV125-CV, NV125-SV 24 125 NV250-CV, NV250-SV
NV125-CV, NV125-SV NV125-SEV
NV125-CV, NV125-SV, NV125-HV NV125-SEV, NV125-HEV
5
Example of transformer excited inrush current 2 Crest Rating value of Model first wave A (multiple) 37 37 37
− − − − − −
NV250-CV, NV250-SV NV250-SEV
150 125
NV250-CV, NV250-SV NV250-SEV NV400-SW NV400-SEW NV630-SEW NV800-SEW NV630-SEW − − − − −
200 125 300 200 300 400 400 − − − − −
Notes *1 Examples of selection of high-instantaneous circuit breakers (special models) for primary side of transformer. *2 The circuit breakers with rating in parentheses are special models. Remarks: 1. For the circuit breakers whose rated current is adjustable, the rated current values are shown. 2. The crest value of the first wave of excited inrush current shall be calculated based on the multiple for the crest value of the first wave in the table, and the calculated value shall not exceed the lower limit crest value of instantaneous tripping current of circuit breaker. The circuit breakers are selected on condition that the transformer rated current value does not exceed 0.9 times the circuit breaker rated current. If the multiple for the crest value of the first wave is different from that shown in the table, a circuit breaker must be separately selected.
75
4 2 Selection
Example of transformer excited inrush current 1 Transformer Rated Crest capacity primary value of Rating Model current first wave kVA A A (multiple)
4 Selection
Selection of MCCB and ELCB
2
Single-phase 420-V Table 4-21-1 MCCB Example of transformer excited inrush current 1 Transformer Rated Peak primary capacity Rating value of Model current first wave kVA A A (multiple) NF63-CV(*1) 30 5 11.9 NF63-CV, NF63-SV, NF63-HV 45 50 NF125-CV, NF125-SV, NF125-HV 50
2 Selection
4
Example of transformer excited inrush current 2 Peak Rating value of Model first wave A (multiple) NF32-SV 15 37 NF63-CV, NF63-SV 15 NF125-SV 15 NF63-CV(*1) 40 37 NF63-CV, NF63-SV 60 NF125-CV, NF125-SV 60
Example of transformer excited inrush current 3 Peak Rating value of Model first wave A (multiple) 15 NF32-SV, NF63-CV, NF63-SV 24 40 NF125-SV 15 NF32-SV, NF63-CV, NF63-SV 30 NF125-SV 24 30 (50) NF125-CV(*2) NF63-CV(*1) 30 NF63-CV, NF63-SV 50 24 (50) NF125-CV(*2) NF125-SV 50 NF63-CV(*1) 50 23 NF125-CV(*1)(*2) 60(50) NF125-CV, NF125-SV 75
7.5
17.9
45
NF63-CV(*1) NF125-CV, NF125-SV, NF125-HV
50 75
10
23.8
43
NF125-CV(*1) NF125-CV, NF125-SV, NF125-HV
60 100
37
NF63-CV(*1) NF125-CV, NF125-SV
50 75
15
35.7
43
NF125-CV(*1) NF250-CV, NF250-SV, NF250-HV NF250-SEV, NF250-HEV
100 150 125
35
NF125-CV(*1) NF125-CV, NF125-SV
60 100
20
47.6
43
NF250-CV, NF250-SV, NF250-HV NF250-SEV, NF250-HEV
200 125
35
NF125-CV(*1) NF250-CV, NF250-SV NF250-SEV
100 150 125
23
NF125-CV(*1) NF125-CV, NF125-SV
60 100
30
71.4
37
NF250-CV, NF250-SV NF250-SEV
225 125
23
NF125-CV(*1) NF250-CV, NF250-SV
100 150
119
35
34
NF400-SW NF400-SEW
400 200
23
NF250-SEV
150
75
179
30
29
NF400-SEW
200
22
NF400-SW NF400-SEW
400 200
100
238
27
125 350 250 400 200 200 500 300 300 600 300
34
50
NF250-SEV, NF250-HEV NF400-CW NF400-SW NF400-SW NF400-SEW, NF400-HEW NF400-SEW, NF400-HEW NF630-SW NF630-SEW, NF630-HEW NF400-SEW(*1) NF630-SW NF630-SEW, NF630-HEW
28
NF400-SEW(*1) NF630-SEW
300 300
20
NF400-SEW
350
150
357
24
NF630-SEW(*1)
400
−
−
19
200 300 500
476 714 1190
21 17 −
NF800-SEW(*1) NF1250-SEW
600 800 −
22 18 17
600 800 −
19 16 −
NF400-SEW(*1) NF630-SEW NF800-SEW(*1) NF1250-SEW −
400 400 600 800 −
−
− NF800-SEW(*1) NF1600-SEW −
Table 4-21-2 ELCB Example of transformer excited inrush current 1 Transformer Rated Peak capacity primary value of Rating Model current first wave kVA A A (multiple) NV63-CV, NV63-SV, NV63-HV 50 5 11.9 NV125-CV 45 60 NV125-SV, NV125-HV 50
Example of transformer excited inrush current 2 Peak Rating value of Model first wave A (multiple) NV32-SV 15 37 NV63-CV, NV63-SV 15 NV125-SV 15
Example of transformer excited inrush current 3 Peak Rating value of Model first wave A (multiple) 15 NV32-SV 24 15 NV63-CV, NV63-SV 15 NV125-SV 30 NV32-SV 24 30 NV63-CV, NV63-SV 30 NV125-SV 50 NV63-CV, NV63-SV 24 60 NV125-CV 50 NV125-SV 75 NV125-CV, NF125-SV 23 50 NV125-SEV 100 NV125-CV, NF125-SV 23 60 NV125-SEV
7.5
17.9
45
NV125-CV, NV125-SV, NV125-HV
75
37
NV63-CV, NV63-SV NV125-CV, NV125-SV
60 60
10
23.8
43
NV125-CV, NV125-SV, NV125-HV NV125-SEV, NV125-HEV
100 50
37
NV125-CV, NV125-SV NV125-SEV
75 50
15
35.7
43
20
47.6
43
100 50 150 125
71.4
37
34
NV250-CV, NV250-SV NV250-SEV
225 125
23
NV250-SV, NV250-SV NV250-SEV
150 125
50
119
35
34
NV400-SW NV400-SEW
400 200
23
NV250-SEV
150
75
179
30
29
NV400-SEW
200
22
NV400-SW NV400-SEW
400 200
100
238
27
150 125 200 125 125 350 250 400 200 200 300 300 400
NV125-CV, NV125-SV NV125-SEV NV250-CV, NV250-SV NV250-SEV
30
NV250-CV, NV250-SV, NV250-HV NV250-SEV, NV250-HEV NV250-CV, NV250-SV, NV250-HV NV250-SEV, NV250-HEV NV250-SEV, NV250-HEV NV400-CW NV400-SW NV400-SW NV400-SEW, NV400-HEW NV400-SEW, NV400-HEW NV630-SEW, NV630-HEW NV630-SEW, NV630-HEW NV800-SEW, NV800-HEW
28
NV630-SEW NV800-SEW
300 400
20
NV400-SEW
350
NV630-SEW NV800-SEW
400 400 − − −
35 35
150
357
24
−
−
24
−
−
19
200 300 500
476 714 1190
21 17 −
− − −
− − −
22 18 −
− − −
− − −
19 16 −
− − −
Notes *1 Examples of selection of high-instantaneous circuit breakers (special models) for primary side of transformer. *2 The circuit breakers with rating in parentheses are special models. Remarks: 1. For the circuit breakers whose rated current is adjustable, the rated current values are shown. 2. The peak value of the first wave of excited inrush current shall be calculated based on the multiple for the peak value of the first wave in the table, and the calculated value shall not exceed the lower limit peak value of instantaneous tripping current of circuit breaker. The circuit breakers are selected on condition that the transformer rated current value does not exceed 0.9 times the circuit breaker rated current. If the multiple for the peak value of the first wave is different from that shown in the table, a circuit breaker must be separately selected.
76
4 Selection 2 Selection of MCCB and ELCB
3-phase 210-V Table 4-21-3 MCCB Example of transformer excited inrush current 2 Peak Rating value of Model first wave A (multiple)
Example of transformer excited inrush current 3 Peak Rating value of Model first wave A (multiple)
26
NF32-SV, NF63-CV, NF63-SV NF125-SV
20 20
18
NF32-SV, NF63-CV, NF63-SV NF125-SV
20 20
26
NF63-CV(*1) NF63-CV, NF63-SV NF125-CV, NF125-SV
30 50 50
18
NF32-SV, NF63-CV, NF63-SV NF125-CV(*2) NF125-SV
30 (50) 30
26
NF63-CV(*1) NF63-CV, NF63-SV NF125-CV, NF125-SV
40 60 60
18
NF63-CV, NF63-SV NF125-CV(*2) NF125-SV
50 (50) 50
15
41.2
24
NF63-CV(*1) NF125-CV, NF125-SV, NF125-HV
50 100
26
NF125-CV(*1) NF125-CV, NF125-SV
60 100
18
NF63-CV(*1) NF63-CV, NF63-SV NF125-CV, NF125-SV
50 60 60
20
55.0
20
NF125-CV(*1) NF125-CV, NF125-SV, NF125-HV
75 100
26
NF125-CV(*1) NF125-SEV NF250-CV, NF250-SV
75 75 125
18
NF125-CV(*1) NF125-CV, NF125-SV
75 100
30
82.5
20
NF250-CV, NF250-SV NF250-SEV
200 125
18
NF125-CV(*1) NF250-CV, NF250-SV
100 150
137
20
200 175
21
400 300 200 350 250
NF250-CV, NF250-SV NF250-SEV
206
NF400-CW NF400-SW NF400-SEW NF400-SW NF400-SEW
16
75
14
NF400-SW NF400-SEW
300 250
100
275
21
100 150 125 175 350 250 400 250 350 600 350
26
50
NF125-CV(*1) NF250-CV, NF250-SV, NF250-HV NF250-SEV, NF250-HEV NF250-SEV, NF250-HEV NF400-CW NF400-SW NF400-SW NF400-SEW, NF400-HEW NF400-SEW(*1) NF630-SW NF630-SEW, NF630-HEW
17
NF400-SEW
350
13
NF400-SW NF400-SEW
350 300
150
412
17
NF630-SEW, NF630-HEW
500
14
NF630-SEW
500
13
200 300 500
550 825 1375
16 16 −
NF800-SEW(*1) NF1600-SEW
700 1000 −
13 13 11
NF800-SEW NF1250-SEW NF1600-SEW
700 1000 1600
12 12 11
NF630-SW NF630-SEW NF800-SEW NF1000-SEW NF1600-SEW
500 500 700 1000 1600
−
23 18
Table 4-21-4 ELCB Example of transformer excited inrush current 1 Transformer Rated Peak capacity primary value of Rating Model current first wave kVA A A (multiple)
Example of transformer excited inrush current 2 Peak Rating value of Model first wave A (multiple)
Example of transformer excited inrush current 3 Peak Rating value of Model first wave A (multiple)
5
13.7
25
NV32-SV NV63-CV, NV63-SV, NV63-HV NV125-SV, NV125-HV
20 20 20
26
NV32-SV NV63-CV, NV63-SV NV125-SV
20 20 20
18
NV32-SV NV63-CV, NV63-SV NV125-SV
20 20 20
7.5
20.6
25
NV63-CV, NV63-SV, NV63-HV NV125-CV NV125-SV, NV125-HV
50 60 50
26
NV63-CV, NV63-SV NV125-CV NV125-SV
50 60 50
18
NV32-SV NV63-CV, NV63-SV NV125-SV
30 30 30
10
27.5
24
NV63-CV, NV63-SV, NV63-HV NV125-CV, NV125-SV, NV125-HV
60 60
26
NV63-CV, NV63-SV NV125-CV, NV125-SV
60 60
18
NV63-CV, NV63-SV NV125-CV NV125-SV
50 60 50
15
41.2
24
20
55.0
20
30
82.5
20 20
200 175
206
21
100 50 75 125 200 125 400 300 200 250 350
NV250-CV, NV250-SV NV250-SEV
75
NV125-CV, NV125-SV NV125-SEV NV125-SEV NV250-CV, NV250-SV NV250-CV, NV250-SV NV250-SEV NV400-CW NV400-SW NV400-SEW NV400-SEW NV400-SW
60 60 100 75 150 125
137
100
275
21
100 50 100 75 150 125 175 350 250 400 250 350 400
NV63-CV, NV63-SV NV125-CV, NV125-SV NV125-CV, NV125-SV NV125-SEV NV250-CV, NV250-SV NV125-SEV
50
NV125-CV, NV125-SV, NV125-HV NV125-SEV, NV125-HEV NV125-CV, NV125-SV, NV125-HV NV125-SEV, NV125-HEV NV250-CV, NV250-SV, NV250-HV NV250-SEV, NV250-HEV NV250-SEV, NV250-HEV NV400-CW NV400-SW NV400-SW NV400-SEW, NV400-HEW NV630-SEW, NV630-HEW NV800-SEW, NV800-HEW
17
NV400-SEW
350
150
412
17
NV630-SEW, NV630-HEW
500
14
NV630-SEW NV800-SEW
200 300 500
550 825 1375
16 16 −
− − −
13 13 11
500 500 − − −
NV400-SW NV400-SEW NV400-SW NV400-SEW NV630-SEW NV800-SEW NV800-SEW
300 250 350 300 500 500 700 − −
− − −
26 26 26 23 18
− − −
18 18 18 16 14 13 13 12 12 11
− −
Notes *1 Examples of selection of high-instantaneous circuit breakers (special models) for primary side of transformer. *2 The circuit breakers with rating in parentheses are special models. Remarks: 1. For the circuit breakers whose rated current is adjustable, the rated current values are shown. 2. The peak value of the first wave of excited inrush current shall be calculated based on the multiple for the peak value of the first wave in the table, and the calculated value shall not exceed the lower limit peak value of instantaneous tripping current of circuit breaker. The circuit breakers are selected on condition that the transformer rated current value does not exceed 0.9 times the circuit breaker rated current. If the multiple for the peak value of the first wave is different from that shown in the table, a circuit breaker must be separately selected.
77
4 2 Selection
Example of transformer excited inrush current 1 Transformer Rated Peak primary capacity Rating value of Model current first wave kVA A A (multiple) NF32-SV 20 5 13.7 NF63-CV, NF63-SV, NF63-HV 25 20 NF125-SV, NF125-HV 20 NF63-CV(*1) 30 NF63-CV, NF63-SV, NF63-HV 50 7.5 20.6 25 (50) NF125-CV(*2) NF125-SV, NF125-HV 50 NF63-CV(*1) 40 NF63-CV, NF63-SV, NF63-HV 60 10 27.5 24 NF125-CV(*1) 50 NF125-CV, NF125-SV, NF125-HV 60
4 Selection
2
Selection of MCCB and ELCB
3-phase 420-V Table 4-21-5 MCCB
2 Selection
4
Example of transformer excited inrush current 2 Example of transformer excited inrush current 3 Example of transformer excited inrush current 1 Transformer Rated Peak Peak Peak primary capacity Rating value of Rating value of Rating value of Model Model Model current first wave first wave first wave kVA A A A A (multiple) (multiple) (multiple) NF32-SV 10 NF32-SV, NF63-CV, NF63-SV NF30-CS 30 10 NF63-CV, NF63-SV, NF63-HV 5 6.9 26 18 32 10 NF32-SV, NF63-CV, NF63-SV NF125-SV 10 15 NF125-SV, NF125-HV 15 NF32-SV 15 NF32-SV, NF63-CV, NF63-SV NF32-SV, NF63-CV, NF63-SV 15 15 7.5 10.3 NF63-CV, NF63-SV, NF63-HV 26 18 15 32 NF125-SV NF125-SV 15 15 NF125-SV, NF125-HV 15 NF32-SV 20 NF32-SV NF32-SV 20 20 NF63-CV, NF63-SV, NF63-HV 20 NF63-CV, NF63-SV NF63-CV, NF63-SV 13.7 10 26 18 20 20 31 (50) NF125-CV(*2) NF125-SV NF125-SV 20 20 NF125-SV, NF125-HV 20 NF63-CV(*1) 40 NF32-SV, NF63-CV, NF63-SV NF63-CV(*1) 30 30 NF63-CV, NF63-SV, NF63-HV 60 NF125-CV(*2) 15 20.6 26 18 NF63-CV, NF63-SV 50 (50) 31 NF125-CV, NF125-SV, NF125-HV 60 NF125-SV NF125-CV, NF125-SV 50 30 NF125-SEV, NF125-HEV 50 NF63-CV(*1) 40 NF63-CV(*1) NF63-CV(*1) 40 40 NF63-CV, NF63-SV, NF63-HV 60 27.5 20 26 18 NF63-CV, NF63-SV NF63-CV, NF63-SV 60 50 26 NF125-CV(*1) 50 NF125-CV, NF125-SV NF125-CV, NF125-SV 60 50 NF125-CV, NF125-SV, NF125-HV 60 NF63-CV(*1) 50 NF63-CV(*1) NF125-CV(*1) 60 50 30 41.2 26 18 NF125-CV(*1) 24 50 NF125-CV, NF125-SV NF125-CV, NF125-SV 100 75 NF125-CV, NF125-SV, NF125-HV 100 NF125-CV(*1) 100 NF125-CV(*1) 100 50 68.7 23 16 NF125-CV, NF125-SV 100 NF250-CV, NF250-SV, NF250-HV 22 150 NF250-CV, NF250-SV 150 NF250-SEV, NF250-HEV 125 NF250-CV, NF250-SV NF250-CV, NF250-SV, NF250-HV 175 150 103 75 18 14 NF250-CV, NF250-SV 150 15 NF250-SEV NF250-SEV, NF250-HEV 125 125 NF250-CV, NF250-SV NF250-CV, NF250-SV, NF250-HV 200 200 137 100 17 13 NF250-CV, NF250-SV 175 15 NF250-SEV NF250-SEV, NF250-HEV 175 175 NF400-CW 400 NF400-CW 400 NF400-SW 300 150 206 14 13 NF400-SW 250 NF400-SW 15 300 NF400-SEW 250 NF400-SEW 250 NF400-SEW, NF400-HEW 250 NF400-SW 350 NF400-SW 350 350/350 12 275 200 13 NF400-SW/SEW 14 NF400-SEW 350 NF400-SEW, NF400-HEW 350 NF630-CW 600 NF630-SW 500 500 412 300 13 12 NF630-SEW NF630-SW 10 500 NF630-SEW 500 NF630-SEW, NF630-HEW 500 NF800-SEW(*1) 800 800 687 500 11 11 NF800-SEW NF800-SEW 800 15 NF1250-SEW 800
Table 4-21-6 ELCB Example of transformer excited inrush current 1 Example of transformer excited inrush current 2 Example of transformer excited inrush current 3 Transformer Rated Peak Peak Peak primary capacity Rating value of Rating value of Rating value of Model Model Model current first wave first wave first wave kVA A A A A (multiple) (multiple) (multiple) NV32-SV(*1) 15(10) NV32-SV(*1) 15(10) 15(10) NV32-SV(*1) NV63-CV, NV63-SV(*1) 15(10) 5 26 NV63-CV, NV63-SV(*1) 15(10) 18 6.9 15(10) 32 NV63-CV, NV63-SV(*1) NV63-HV 15 NV125-SV 15 15 NV125-SV NV125-SV, NV125-HV 15 NV32-SV 15 NV32-SV 15 15 NV32-SV 7.5 26 18 NV63-CV, NV63-SV 15 10.3 NV63-CV, NV63-SV, NV63-HV 15 32 15 NV63-CV, NV63-SV NV125-SV 15 NV125-SV, NV125-HV 15 15 NV125-SV NV32-SV 20 NV32-SV 20 20 NV32-SV NV63-CV, NV63-SV, NV63-HV 20 10 26 18 NV63-CV, NV63-SV 20 13.7 20 31 NV63-CV, NV63-SV NV125-CV 50 NV125-SV 20 20 NV125-SV NV125-SV, NV125-HV 20 NV63-CV, NV63-SV 50 NV63-CV, NV63-SV, NV63-HV 30 60 NV32-SV 15 26 18 20.6 NV125-CV 60 NV125-CV, NV125-SV, NV125-HV 30 31 60 NV63-CV, NV63-SV NV125-SV 50 NV125-SEV, NV125-HEV 30 50 NV125-SV 50 NV63-CV, NV63-SV NV63-CV, NV63-SV 60 NV63-CV, NV63-SV, NV63-HV 60 20 26 18 27.5 60 26 NV125-CV NV125-CV, NV125-SV 60 NV125-CV, NV125-SV, NV125-HV 60 50 NV125-SV NV125-CV, NV125-SV 100 NV125-CV, NV125-SV, NV125-HV 100 30 26 18 41.2 75 24 NV125-CV, NV125-SV NV125-SEV 50 NV125-SEV, NV125-HEV 50 NV250-CV, NV250-SV 150 NV250-CV, NV250-SV, NV250-HV 150 50 23 16 68.7 100 22 NV125-CV, NV125-SV NV250-SEV 125 NV250-SEV, NV250-HEV 125 NV250-CV, NV250-SV 175 NV250-CV, NV250-SV, NV250-HV 150 75 18 14 103 150 15 NV250-CV, NV250-SV NV250-SEV 125 NV250-SEV, NV250-HEV 125 NV250-CV, NV250-SV 200 NV250-CV, NV250-SV, NV250-HV 200 100 17 13 137 175 15 NV250-CV, NV250-SV NV250-SEV 175 NV250-SEV, NV250-HEV 175 NV400-CW 400 400 NV400-CW NV400-SW 300 150 14 13 206 NV400-SW 250 15 300 NV400-SW NV400-SEW 250 NV400-SEW, NV400-HEW 250 250 NV400-SEW NV400-SW 350 NV400-SW 350 350 NV400-SW 200 13 12 275 14 NV400-SEW 350 NV400-SEW, NV400-HEW 350 350 NV400-SEW NV630-SEW 500 NV630-CW, NV630-SW 600 300 13 12 412 500 10 NV630-SEW NV800-SEW 500 NV630-SEW, NV630-HEW 500 500 11 11 687 − − − − 15 − − Notes *1 Examples of selection of high-instantaneous circuit breakers (special models) for primary side of transformer. *2 The circuit breakers with rating in parentheses are special models. Remarks: 1. For the circuit breakers whose rated current is adjustable, the rated current values are shown. 2. The peak value of the first wave of excited inrush current shall be calculated based on the multiple for the peak value of the first wave in the table, and the calculated value shall not exceed the lower limit peak value of instantaneous tripping current of circuit breaker. The circuit breakers are selected on condition that the transformer rated current value does not exceed 0.9 times the circuit breaker rated current. If the multiple for the peak value of the first wave is different from that shown in the table, a circuit breaker must be separately selected.
78
4 Selection 2 Selection of MCCB and ELCB
10. Combination for Selective Breaking Continuous power supply
Combinations of main circuit breaker for coordination and branch circuit breakers capable of selective breaking and the breaking capacity (sym kA) for selective breaking at the installation point of the branch circuit breaker are shown below.
NV32-SV
5
NV63-SV NF63-HV NV63-HV
7.5 10
NV125-SV
NF1600-SEW 125
7.5
1.5 1.5 2.5 2.5
5
5
7.5 7.5 7.5 7.5 7.5
7.5
7.5
5
5
NV32-SV
10
1.5 1.5 2.5 2.5
10
10
10
10
10
10
10
10
10
7.5
7.5
15
1.5 1.5 2.5 2.5
10
10
10
10
10
10
10
10
10
25
1.5 1.5 2.5 2.5
10
10
20
20
25
25
25
25
25
1.5 1.5 2.5 2.5
5
5
5
5
5
5
5
1.5 1.5 2.5 2.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5 1.5 1.5 2.5 2.5 7.5 7.5
10
10
10
10
10
10
10
2.5 2.5
10
10
10
10
10
10
22
NF63-SV NV63-SV NF63-HV NV63-HV
85 100 85 100 85 100 50
NF125-SV 25
–
–
5
5
NF125-SEV NV125-SV
50
–
–
2.5 2.5 7.5 7.5
15
15
18
18
18
18
50
85
NV125-SEV 36
–
–
2.5 2.5 7.5 7.5
15
15
15
15
15
15
36
NF125-SGV
85
–
–
2.5 2.5 7.5 7.5
15
15
18
18
18
18
NF125-LGV
50
–
–
2.5 2.5 7.5 7.5
15
15
15
15
15
15
42
NF125-LGV
90
–
–
2.5 2.5 7.5 7.5
15
15
18
18
18
18
85
50
–
–
2.5 2.5 7.5 7.5
18
18
18
18
18
18
50
100
–
–
2.5 2.5
10
25
25
35
35
35
35
100
NF125-HGV
65
–
–
2.5 2.5 7.5 7.5
15
15
15
15
15
15
42
NF125-HGV
100
–
–
2.5 2.5 7.5 7.5
15
15
18
18
18
18
85
NF160-SGV
36
–
–
–
–
6.4 6.4
10
10
10
10
10
10
25
NF160-SGV
85
–
–
–
–
6.4 6.4
10
10
10
10
10
10
50
NF160-LGV
50
–
–
–
–
6.4 6.4
10
10
15
15
15
15
25
NF160-LGV
90
–
–
–
–
6.4 6.4
10
10
10
10
10
10
50
NF160-HGV
65
–
–
–
–
6.4 6.4
10
10
15
15
15
15
25
NF160-HGV
100
–
–
–
–
6.4 6.4
10
10
10
10
10
10
50
85
–
–
–
–
–
–
10
10
10
10
10
10
50
NF250-SGV
85
–
–
–
–
–
–
10
10
10
10
10
10
50
NF250-LGV
90
–
–
–
–
–
–
10
10
10
10
10
10
50
100
–
–
–
–
–
–
10
10
10
10
10
10
50
100
–
–
–
–
–
–
10
10
10
10
10
10
50
85
–
–
–
–
–
–
–
–
13
13
13
13
20
85
–
–
–
–
–
–
–
–
13
13
13
13
20
100
–
–
–
–
–
–
–
–
13
13
13
13
20
150
–
–
–
–
–
–
13
13
13
13
20
85
–
–
–
–
–
–
–
–
–
–
–
–
20
100
–
–
–
–
–
–
–
–
–
–
–
–
20
7.5
7.5
15
15
25
7.5 7.5 7.5 7.5 7.5
7.5
25
NV125-HV
NF250-SV NF250-SEV
36
–
–
–
–
–
–
10
10
10
10
10
10
22
NF250-SGV
36
–
–
–
–
–
–
10
10
10
10
10
10
25
NF250-LGV
50
–
–
–
–
–
–
10
10
15
15
15
15
25
NV250-SV NV250-SEV
NF250-HV NF250-HEV NV250-HV
65
–
–
–
–
–
–
10
10
10
10
10
10
22
NF125-HV NV125-HV
NF | S • L • H • NV | S • H
NV250-HEV NF250-HGV NF400-SW NV400-SW NF400-SEW NV400-SEW NF400-HEW NV400-HEW NF400-REW NV400-REW NF630-SEW NV630-SW
65 42 42 65
– – – –
– – – –
– – – –
– – – –
– – – –
– – – –
125
–
–
–
–
–
–
42
–
–
–
–
–
–
10 –
10 –
9.5 9.5 9.5 9.5 9.5 9.5
15 13 13 10
15 13 13 10
15 13 13 10
15
NV630-HEW NF63-CV NV63-CV NF125-CV NV125-CV NF250-CV NV250-CV NF400-CW NV400-CW NF630-CW
NF250-SEV NV250-SV NV250-SEV
NF250-HV NF250-HEV NV250-HV
13 13 13
NF400-SW
20
NV400-SW NF400-SEW
20
NV400-SEW NF400-HEW
20
10
10
10
13
20
–
–
–
–
20
NV400-HEW NF400-REW NV400-REW
9.5 9.5
NF630-SW –
–
NF630-SEW NV630-SW NV630-SEW
65 2.5 10 15 25
–
–
–
–
–
–
–
–
–
–
–
1.5 1.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 – – –
– – –
2.5 2.5 – – –
36
–
–
NF125-RGV
125
–
–
NF125-UV
200
–
–
NF250-RGV
125
–
–
–
NF250-UV
200
–
–
NF400-UEW
200
–
NF800-UEW
200
–
NV630-CW
NF250-SV
NF250-HGV
25
NV630-SEW NF630-HEW
10
NV250-HEV
NF630-SW
NF | R • U
NF1250-SEW
125
NF32-SV
NF125-SGV NF125-HV
NF | C • NV | C
NF1000-SEW
85 100
2.5
NV125-SEV
NF | S • L • H • NV | S • H
NF800-HEW
85
2.5
NF125-SV NF125-SEV
NF800-SEW
85
1.5 1.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
– – –
5 – –
5 – –
10
10
10
10
10
7.5 7.5 7.5 7.5 7.5 –
–
10
10
10
– 7.5
2.5
15
10
7.5 13
15 20
–
–
–
–
–
–
–
–
20
2.5 2.5
15
15
30
30
30
42
50
50
85
2.5 2.5
15
15
30
30
30
42
50
50
85
–
–
–
15
15
15
25
25
25
85
–
–
–
–
15
15
15
25
25
25
85
–
–
–
–
–
9.5 9.5
15
15
15
15
25
–
–
–
–
–
–
–
–
–
–
–
–
NF630-HEW
20
Note *1 Rated currents of branch breakers are 50A or less. Remarks: 1. It is considered that the instantaneous tripping characteristic values of main circuit breakers have been set to the maximum values. 2. For the selectivity in the overcurrent range, separately check the coordination on the operating characteristic curve.
NV630-HEW NF63-CV NV63-CV NF | C • NV | C
NF125-CV
15
–
–
36
–
–
–
–
–
–
50
–
–
–
–
–
–
–
–
13
13
13
13
20
50
–
–
–
–
–
–
–
–
–
–
–
–
20
NF125-RGV
150
–
–
2.5 2.5
22
22
65
65
50
85
85
85
125
NF125-UV
200
–
–
2.5 2.5
22
22
65
65
50
85
85
85
125
NF250-RGV
150
–
–
–
–
–
–
–
–
18
50
50
50
125
NF250-UV
200
–
–
–
–
–
–
–
–
18
50
50
50
125
NF400-UEW
200
–
–
–
–
–
–
–
–
15
15
15
15
25
NF800-UEW
200
–
–
–
–
–
–
–
–
–
–
–
–
–
BH-P
2.5
–
2.5
–
–
2.5
2.5
NF250-CV NV250-CV NF400-CW NV400-CW NV630-CW
BH-D6 BH
1.5 1.5 2.5 2.5 7.5 7.5 7.5 7.5 7.5 7.5 7.5
30
NV125-CV
NF630-CW
NF | R • U
7.5
TYPE B BH-D6 TYPE C
2.5 2.5 7.5 7.5
1.5 1.5 2.5 2.5 2.5
10
15
15
2.5 2.5
6
–
–
–
–
–
–
–
–
–
–
–
–
–
6
–
–
–
–
–
–
–
–
–
–
–
–
–
79
4 2 Selection
NF63-SV
NF800-CEW
65
NF630-HEW
42
NF630-SEW
36
NF400-HEW
NF800-HEW
65
NF400-SEW
NF800-SEW
42
NF250-HEV
NF800-CEW
65
Circuit breaker NF250-SEV
NF630-HEW
42
NF125-HEV
NF630-SEW
65
sym.kA
Main Ra breaker sh ted ca ort-c ultim pa irc at city uit e of bre ea aki ch ng bre ak er Branch breaker Icu(kA) 50 100
NF125-SEV
NF400-HEW
36
NF1600-SEW
NF400-SEV
65
2.5
NF1250-SEW
NF250-HEV
Icu(kA) 36
NF32-SV
NF1000-SEW
NF250-SEV
r
NF125-HEV
breaker
sym.kA 230VAC (IEC 60947-2)
Circuit breaker NF125-SEV
Main breaker
Branch circuit breaker
Circuit in good condition
Table 4-22-1 Combination for selective breaking 440VAC (IEC 60947-2) Ra sh ted ca ort-c ultim pa irc at city uit e of bre ea aki ch ng bre ak e Branch
Main circuit breaker
4 Selection
Selection of MCCB and ELCB
2
Table 4-22-2 Combination for selective breakingwith AE-SW Series
NF32-SV NV32-SV NF63-SV NV63-SV NF63-HV NV63-HV NF125-SV NV125-SV NF125-SEV
2 Selection
AE4000-SWA
AE3200-SW
AE2500-SW
AE2000-SW
AE2000-SWA
AE1600-SW
65
65
65
85
85
85
85
65
65
65
65
65
85
85
85
85
2.5
2.5
2.5
2.5
2.5
2.5
2.5
NF32-SV
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
NV32-SV
10
9(10)
10
10
10
10
10
10
10
10
15
9(10)
15
15
15
15
15
15
15
15
25
9(25)
25
25
25
25
25
25
25
25
50
9(50)
45(50)
50
50
50
50
50
50
50
45(65) 50(65) 50(65) 50(65)
5
5
5
5
5
5
5
5
5
5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
10
9(10)
10
10
10
10
10
10
10
10
25
7(25)
20(25)
25
25
25
25
25
25
25
NF63-SV NV63-SV NF63-HV NV63-HV NF125-SV NV125-SV NF125-SEV
20(36) 25(36) 30(36)
36
36
36
36
36
85
9(65)
85
85
85
85
9(36)
20(36)
36
36
36
36
36
36
NF125-SGV
85
16(65) 45(65)
65
65
65
85
85
85
85
NF125-LGV
50
9(50)
20(50) 36(50)
50
50
50
50
50
50
NF125-LGV
90
16(65) 45(65)
65
65
65
85
85
85
85
50
9(50)
30(50)
50
50
50
50
50
50
100
9(65)
50(65)
65
65
65
85
85
85
85
NF125-HGV
65
9(65)
20(65) 36(65)
65
65
65
65
65
65
NF125-HGV
100
16(65) 45(65)
65
65
65
85
85
85
85
NF160-SGV
36
9(36)
15(36) 25(36)
36
36
36
36
36
36
NF160-SGV
85
9.4(65) 25(65) 40(65)
65
65
85
85
85
85
NF160-LGV
50
9(50)
15(50) 25(50) 42(50) 42(50)
50
50
50
50
NF160-LGV
90
9.4(65) 25(65) 40(65)
65
65
85
85
85
85
NF160-HGV
65
9(65)
15(65) 25(65) 42(65) 42(65)
65
65
65
65
NF160-HGV
100
9.4(65) 25(65) 40(65)
65
65
85
85
85
85
85
85
85
36
50
NF250-SV NF250-SEV NV250-SV
36
7(36)
14(36) 19(36) 25(36) 25(36)
36
36
36
36
NV250-SEV NF250-SGV
36
7(36)
15(36) 25(36)
NF250-LGV
50
7(50)
15(50) 25(50) 42(50) 42(50)
36
36
36
36
36
36
50
50
50
50
NF250-HV NF250-HEV NV250-HV
65
7(65)
15(65) 25(65) 42(65) 42(65)
65
65
65
65
NV250-HEV NF250-HGV NV400-SW NF400-SEW NV400-SEW NF400-HEW NV400-HEW NF400-REW NV400-REW
65
7(65)
42
–
42
9(42)
65 125
9(65) 9(65)
15(65) 25(65) 42(65) 42(65) –
65
18(42) 24(42) 24(42) 33(42)
65
65
65
42
42
42
42
42
15(42) 18(42) 24(42) 24(42) 30(42) 39(42) 15(65) 18(65) 24(65) 24(65) 30(65) 39(65) 15(65) 18(65) 24(65) 24(65) 30(75) 39(75)
65 80
NV125-SEV
NF125-HV NV125-HV
NF | S • L • H • NV | S • H
NF630-SEW NV630-SW
NV630-HEW NF800-SEW NV800-SEW NF800-HEW NV800-HEW NF63-CV NV63-CV NF125-CV NV125-CV NF250-CV NV250-CV NF400-CW
42
–
–
–
24(42) 24(42) 30(42) 37(42)
65 42
–
85
9.4(65) 25(65) 40(65)
65
65
85
85
85
85
90
9.4(65) 25(65) 40(65)
65
65
85
85
85
85
25(65) 40(65)
65
65
85
85
85
85
9.4(65) 25(65) 40(65)
65
65
85
85
NF250-HV NF250-HEV NV250-HV
100
9(65)
NV250-HEV NF250-HGV
NF400-HEW NV400-HEW NF400-REW NV400-REW
42
NF630-SEW
42
NV630-SW
–
–
65
–
–
2.5
2.5
2.5
10 15
9(10) 9(15)
NF630-HEW
15(65) 18(65) 24(65) 24(65) 30(65) 37(65) 48(65) 48(65)
10 15
18(42) 24(42) 24(42) 30(42) 37(42)
2.5 10 15
85
85
20(65) 30(65) 30(65) 48(75) 70(75)
85
85
9(65)
15(65) 20(65) 30(65) 30(65) 48(75) 70(75)
85
85
100
9(65)
15(65) 20(65) 30(65) 30(65) 48(75) 70(75)
85
85
150
9(65)
15(65) 20(65) 30(65) 30(65) 48(75) 70(75)
85
85
85
–
100
–
85
–
–
18(65) 24(65) 24(65) 30(75) 40(75) 60(75) 60(75)
100
–
–
18(65) 24(65) 24(65) 30(75) 40(75) 60(75) 60(75)
7.5
7.5
7.5
30
9(30)
36
9(36)
50
–
100 85
–
85
–
–
–
24(65) 24(65) 30(75) 40(75) 60(75) 60(75)
NF800-SEW
42
NV800-SEW NF800-HEW
2.5 10 15
2.5 10 15
2.5 10 15
2.5 10 15
2.5 10 15
NV800-HEW NF63-CV
2.5 10 15
NV63-CV NF125-CV NF | C • NV | C
NV125-CV NF250-CV NV250-CV NF400-CW
15(65) 18(65) 24(65) 24(65) 30(75) 40(75) 60(75) 60(75)
7.5
7.5
7.5
7.5
15(30) 18(30) 24(30) 24(30)
30
30
30
30
15(36) 18(36) 24(36) 24(36)
36
36
36
36
50
50
50
24(50) 24(50) 30(50) 40(50)
50
50
18(50) 24(50) 24(50) 30(50) 40(50)
50
50
7.5
7.5
7.5
25
25
25
24(36) 24(36) 30(42)
36
36
36
50
–
–
18(36) 24(36) 24(36) 30(42)
36
36
36
NF800-CEW
50
–
–
85
85
85
85
NF125-RGV
150
65
65
65
65
65
85
85
85
85
65
85
85
85
85
NF125-UV
200
65
65
65
65
65
85
85
85
85
65
65
85
85
85
85
NF250-RGV
150
9(65)
65
65
65
65
85
85
85
85
65
65
85
85
85
85
NF250-UV
200
9(65)
65
65
65
65
85
85
85
85
85
85
85
NF400-UEW
200
9(65)
85
85
85
NF800-UEW
200
–
–
–
NF800-CEW
36
–
–
NF125-RGV
125
35(65)
65
65
65
65
NF125-UV
200
50(65)
65
65
65
NF250-RGV
125
9(65)
50(65)
65
NF250-UV
200
9(65)
65
65
NF400-UEW
200
9(65)
NF800-UEW
200
–
15(25) 18(25) –
25
25
25
15(65) 18(65) 29(65) 29(65) 48(75) –
42
NV630-HEW
18(65) 24(65) 24(65) 30(65) 37(65) 48(65) 48(65)
36
NV630-CW
20(65) 22(65) 42(65) 42(65) 50(85)
NF250-LGV
NV400-SEW
80
9(65)
NF250-SGV
NF400-SEW
65
85
NV250-SEV
NV630-SEW
–
NF630-CW
NV250-SV
NF630-SW
25
NV400-CW
NF250-SEV
NV400-SW
NV630-SEW NF630-HEW
NF250-SV
NF400-SW
NF630-SW
18(65) 24(65) 24(65) 30(75) 37(75) 68(75) 68(75)
Notes *1 The values in the table represent the max. rated current for both Series AE-SW air circuit breakers and branch breakers, and the selective co-ordination applies when the air circuit breakers instantaneous pick up is set to maximum. *2 The numerals shown in parentheses are for AE-SW with MCR. (When set MCR.)
80
AE1250-SW
65 2.5
7(36)
NF400-SW
NF | R • U
AE1000-SW
AE4000-SWA
AE3200-SW
AE2500-SW
AE2000-SW
AE2000-SWA
AE1600-SW
AE1250-SW
AE1000-SW
65 2.5
36
NV125-HV
NF | C • NV | C
sym.kA Low-voltage air circuit breaker AE-SW
36
NF125-HV
4
230VAC (IEC 60947-2) R Main sh ated breaker ca ort- ulti pa cir ma cit cui te yo tb f e rea ac ki h b ng rea ke Branch r breaker Icu(kA)
NF125-SGV
NV125-SEV
NF | S • L • H • NV | S • H
2.5
sym.kA Low-voltage air circuit breaker AE-SW
AE630-SW
R Main sh ated breaker ca ort- ulti pa cir ma cit cui te yo tb f e rea ac ki h b ng rea ke Branch r breaker Icu(kA)
AE630-SW
440VAC (IEC 60947-2)
NV400-CW NF630-CW NV630-CW
NF | R • U
15(50) 20(50) 27(50) 27(50) 42(50) –
15(65) 18(65) 29(65) 29(65) 48(75) –
18(65) 24(65) 24(65) 30(75) 37(75) 68(75) 68(75)
4 Selection 2 Selection of MCCB and ELCB
11. Combinations for Cascade Breaking Main circuit breaker (Backup circuit breaker)
The following tables show the combinations of circuit breakers capable of cascade breaking and the cascade breaking capacities (symmetrical values, sym kA). The criteria conform to IEC 60947-2.
Branch circuit breaker (Backed up circuit breaker)
Short-circuit
Table 4-23-1 440VAC (IEC 60947-2)
sym.kA
NF250-CV, NV250-CV
NF400-CW, NV400-CW
NF630-CW, NV630-CW
NF800-CEW
42 65 125 42 65 125 42 − − − − − − − 7.5 7.5 7.5 7.5 7.5 7.5 − 15 15 15 10 10 10 10 − − − − − − −
65 125 85 − − − − − − 10 10 − − − −
15 5 − − −
25 − − 10 10
36 − − 10 10
36 125 200 125 − 35 125 35 − 50 125 35 − 50 125 50 − 50 125 50
200 200 200 − 50 − − 50 − 50 10 10 − − 50
10
20
30
30
30
30
18
18
18
18
18
18
18
18
15
15
15
14
14
14
−
−
−
−
−
−
−
−
125 125 50
50
−
−
25
−
36
36
50
50
36
36
50
−
36
50
42
50
35
35
35
35
35
35
30
35
35
30
−
−
−
−
125 200 125 200 50
35
36 50
− −
− −
50 −
− −
50 −
− −
50 −
50 −
− −
− −
50 −
− −
50 −
− −
50 −
50 −
− −
50 −
50 −
− −
50 −
50 −
− −
− −
− −
− −
− −
125 200 125 200 50 125 200 125 200 50
|
− −
S • NV |
50
−
−
−
−
65
−
−
65
−
−
−
−
65
−
65
65
−
65
65
−
65
65
−
−
−
−
−
125 200 125 200 200 85
65 36 50 65
− − − −
− − − −
− − − −
− − − −
− − − −
− − − −
− − − −
− − 65 −
− − − −
− − − −
− − − −
− − − −
− − 65 −
− − − −
− 50 65 −
− 50 65 −
− − − −
− 50 65 −
− 50 65 −
− − − −
− 50 65 −
− 50 65 −
− 50 65 −
− − − −
− − − −
− − − −
− − − −
S • NF
125 200 125 200 200 − − 125 200 85 − − 125 200 85 − − 125 200 200
|
L • NF |
36
−
−
−
−
−
−
−
−
−
−
−
−
−
−
50
50
−
50
50
−
50
50
−
−
−
−
−
−
−
125 200 85
36 50
− −
− −
− −
− −
− −
− −
− −
− −
− −
− −
− −
− −
− 65
− −
50 65
50 65
− −
50 65
50 65
− −
50 65
50 65
50 −
− −
− −
− −
− −
− −
− −
125 200 85 85 125 200 200 200
H • NV |
H
65
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
125 200 200 200
65
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
125 200 200 200
42
−
−
−
−
−
−
−
−
−
−
−
−
−
−
65
65
−
65
65
−
65
65
−
−
−
−
−
−
−
−
−
42
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
65
65
−
65
65
−
−
−
−
−
−
−
−
−
−
200
2.5 10
14
14
14
14
5
5
5
5
5
5
5
5
−
−
−
−
−
−
−
−
−
−
5
−
−
−
35 125 35
50
5
−
NF |
C • NV
10
20
30
30
30
30
14
14
14
14
14
14
14
14
14
14
14
14
14
14
14
14
14
−
−
14
14
14 125 200 50 125 14
14
|
15
−
−
−
−
−
−
−
−
−
−
−
−
−
30
30
30
−
−
−
−
−
−
−
−
−
−
−
−
−
−
C
25
−
−
−
−
−
−
−
−
−
−
−
−
−
35
35
35
35
35
35
35
35
35
30
−
−
−
−
−
−
−
−
50
50
36
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
42
50
50
42
50
50
42
−
−
−
−
−
−
−
−
−
200
NF125-SV, NV125-SV
NF800-UEW
NF1000-SEW, NF1250-SEW, NF1600-SEW
65 5 10 15 10
NF400-UEW
NF400-SW, NV400-SW
65 5 10 10 10
NF250-UV
NF250-HGV
50 5 10 15 10
NF250-RGV
NF250-HV, NV250-HV
36 5 10 15 10
NF125-UV
NF250-LGV
36 5 10 15 10
NF125-RGV, NV125-RGV
NF250-SGV
65 5 10 15 10
NF800-REW
NF250-SV, NV250-SV
50 5 10 15 10
NF800-HEW, NV800-HEW
NF160-HGV
36 5 10 15 10
NF800-SEW, NV800-SEW
NF160-LGV
65 14 14 20 20
NF630-REW
NF160-SGV
50 14 14 20 20
NF630-HEW, NV630-HEW
NF125-HGV
50 14 14 14 14
NF630-SW, NV630-SW
NF125-HV, NV125-HV
36 14 14 14 14
NF400-REW, NV400-REW
NF125-LGV
10 14 14 14
Icu(kA) 25
NF400-HEW, NV400-HEW
NF125-SGV
NF
NF32-SV NV32-SV NF63-SV NV63-SV NF63-HV NV63-HV NF125-SV NV125-SV NF125-SGV NF125-LGV NF125-HV NV125-HV NF125-HGV NF160-SGV NF160-LGV NF160-HGV NF250-SV NV250-SV NF250-SGV NF250-LGV NF250-HV NV250-HV NF250-HGV NF400-SW NF400-SEW NV400-SW NV400-SEW NF630-SW NF630-SEW NV630-SW NV630-SEW NF63-CV NV63-CV NF125-CV NV125-CV NF250-CV NV250-CV NF400-CW NV400-CW NF630-CW NV630-CW
NF-R • NF-U
2.5 5 7.5 7.5
g kin rea it b rcu -ci r ort ke sh rea ate b im ch ult f ea ted ty o Ra paci ca
Branch breaker
NF-C • NV-C
85 85 85 200 85
200 200
125 200 50
Note Rated currents of main breakers are maximum values.
81
4 2 Selection
NF-S • NV-S • NF-H • NV-H
Main breaker
Selection of MCCB and ELCB
Table 4-23-2 230VAC (IEC 60947-2)
sym.kA
NF250-RGV
NF250-UV
125 200 85 125
−
125 200 125 200 200 125
− −
− −
− −
− −
− −
125 200 125 200 200 125 125 200 125 200 200 200
−
−
−
−
−
−
125 200 125 200 200 125
− − − −
− − − −
− − − −
− − − −
− − − −
− − − −
125 200 125 200 200 − − 125 200 200 − − 125 200 200 − − 125 200 200
−
−
−
−
−
−
−
−
−
125 200 200 125
− −
− −
− −
− −
− −
− −
− −
− −
− −
125 200 200 125 125 200 200 200
−
−
−
−
−
−
−
−
−
−
125 200 200 200
−
−
−
−
−
−
−
−
−
−
125 200 200 200
−
−
−
−
100
−
−
−
−
−
−
−
−
−
−
−
−
−
100
−
−
−
−
−
−
−
−
−
200
−
−
−
−
−
−
−
−
−
−
−
125 200 35
50
−
−
50
50
50
50
50
−
−
−
−
−
−
−
125 200 85 125 50
−
50
50
50
50
50
50
−
−
−
−
−
−
−
−
−
85
85
85
85
85
85
85
85
85
85
−
−
−
−
−
−
−
−
−
−
−
−
85
85
85
85
85
85
85
−
−
−
−
−
−
−
−
−
200
−
−
−
−
−
−
−
−
−
−
−
5
−
−
−
−
−
−
−
NF630-SW, NV630-SW
NF125-UV
NF1000-SEW, NF1250-SEW, NF1600-SEW
NF800-HEW, NV800-HEW
NF800-SEW, NV800-SEW
NF630-HEW, NV630-HEW
NF400-REW, NV400-REW
−
−
NF400-SW, NV400-SW
30
−
NF250-HV, NV250-HV
NF125-HV, NV125-HV
30
−
50
50
50
50
50
50
50
50
50
−
−
−
−
85
85
85
85
85
85
85
85
85
85
−
−
−
−
− −
− −
100 −
− −
− −
− −
− −
− −
− −
− −
− −
− −
− −
− −
− −
− −
− −
− −
− −
− −
− −
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
− − − −
− − − −
− − − −
− − − −
− − − −
− − − −
− − − −
− − − −
− − − −
− − − −
− − − −
− − − −
− − − −
− − − −
− − − −
− − − −
− − − −
− − − −
− − − −
− − − −
− − − −
85
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
85 90
− −
− −
− −
− −
− −
− −
− −
− −
− −
− −
− −
− −
− −
− −
− −
− −
− −
− −
− −
− −
100
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
100
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
85
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
85
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
7.5 35
50
50
50
50
10
10
10
10
10
10
10
10
−
−
−
30
35
85
85
85
85
50
50
50
50
50
50
50
50
50
50
36
−
−
−
−
−
−
−
−
50
50
50
50
50
50
50
−
−
−
−
−
−
−
−
−
−
−
−
−
50
−
−
−
−
−
−
−
−
−
−
−
−
2.5 30
42
42
42
42
50
85
50
−
85
85 90
− −
100 100 85 90 100
7.5 7.5 7.5
5
7.5 7.5 7.5
NF800-REW
50
−
25
NF630-REW
50
85
90 100 100 50 50 50 50 50 50 85 85 85 85 85 85
NF250-HGV
50
85
85 50 50 85 85
NF160-HGV
50
90 100 100 85
42 42 42 42
Note Rated currents of main breakers are maximum values.
82
NF125-RGV, NV125-RGV
BH
NF800-CEW
C
NF630-CW, NV630-CW
|
NF400-CW, NV400-CW
|
C • NV
NF250-CV, NV250-CV
NF
−
NF250-LGV
|
H
2 Selection
4
H • NV
200 200 200 50 − − 50 − − 125 − − 125 − −
NF250-SGV
|
150 35 35 85 85
NF250-SV, NV250-SV
|
L • NF
200 200 200 200 200
NF160-LGV
S • NF
150 125 125 125 125
NF160-SGV
|
50 − − − −
90 100 100 50
NF125-HGV
S • NV
50 − 14 − −
85 10 35 35 35
NF125-LGV
|
50 − 14 − −
90 100 85 10 10 10 35 35 35 35 35 35 35 35 35
7.5 10 15 15
Icu(kA) 50
NF-R • NF-U
90 100 100 85 100 150 85 100 150 85 100 150 125 36 − − − − − − − − − − − 10 10 10 − − − − 25 35 35 35 14 14 14 14 14 14 − − − − 25 35 35 35 30 30 30 30 30 30 − − − − − − − − − − 25 35 35 35
85 10 35 35 35
NF125-SGV
NF
NF32-SV NV32-SV NF63-SV NV63-SV NF63-HV NV63-HV NF125-SV NV125-SV NF125-SGV NF125-LGV NF125-HV NV125-HV NF125-HGV NF160-SGV NF160-LGV NF160-HGV NF250-SV NV250-SV NF250-SGV NF250-LGV NF250-HV NV250-HV NF250-HGV NF400-SW NF400-SEW NV400-SW NV400-SEW NF630-SW NF630-SEW NV630-SW NV630-SEW NF63-CV NV63-CV NF125-CV NV125-CV NF250-CV NV250-CV NF400-CW NV400-CW NF630-CW NV630-CW BH BH-P
NF125-SV, NV125-SV
g kin rea it b rcu -ci r ort ke sh rea ate b im ch ult f ea ted ty o Ra paci ca
Branch breaker
NF-C • NV-C
NF400-HEW, NV400-HEW
NF-S • NV-S • NF-H • NV-H
Main breaker
125 200
−
NF800-UEW
2
NF400-UEW
4 Selection
−
200 125 200 200
200 200
125 200 200 50 200 200
4 Selection 2 Selection of MCCB and ELCB
12. International Standard Comformance List 12.1 UL and CSA Approval Product
UL (Underwriter’s Laboratories) Standards: UL 489, UL 1077 UL is an organization in the US which establishes safety standards, i.e. UL Standards, conducts safety verification test based on the UL Standards, issues the certificates to approved products and allows the manufacturers to attach the certification mark to the products. The UL certification mark has been spread widely in the US. Some states and cities oblige manufacturers to receive the UL certification. When devices, control panels and machines are exported to the US, these products must be UL certified. UL certified products have received UL Recognition or UL Listing in conformity to UL Standards (UL 489, UL1077) and allowed to be used in control panels and machines to be exported to the US. : UL Recognition Refers to component certification for products designed to be built in other products and devices. UL recognized products can be used in control panels, machine tools and control units.
: UL Listing Refers to product certification for products which can be sold directly to end-users and used by end-users. These products can be used also as built-in components in control panels, machine tools and control units. Some models vary in external dimensions and terminal structure from standard models. Please refer to the page of UL listed products for details.
CSA (Canadian Standard Association) Standards: CSA C22.2 No.5-02
: Recognition for US and Canada UL and CSA recognition of components by testing body UL
: Listing for US and Canada UL and CSA recognition of components by testing body UL
12.2 CCC (China Compulsory Certification) Approval Product Low-voltage circuit breakers are designated as products to be compulsorily certified in China. To export such products to China and sell them in China, it is necessary to obtain the CCC certification.
12.3 Corresponding to EC (European Community) Directive Corresponding to LVD (Low Voltage Directive)
aWhen using a low voltage circuit breaker as a component and indicating conformity with the EC Directives The CE Marking is required when a low voltage circuit breaker is distributed as a single device in EU. However, when the CE Mark is indicated on a machine tool or a control unit, it is unnecessary to affix the CE Mark to the low-voltage circuit breaker used as a built-in component. When the CE Mark is indicated on a machine tool or a control unit, it is recommended to use a product certified by a third party shown in Item d (TÜV certified product) as a low voltage circuit breaker. sMeasures for export of low voltage circuit breaker as single unit When exporting a low-voltage circuit breaker as a single unit in EU, the circuit breaker is covered by the Low Voltage Directive. The certification of conformity with the Low Voltage Directive is self-declared as a rule. The applicable product standards are shown below. EN 60947-2 Low-voltage switchgear and controlgear-Part 2: Circuit-breakers EN 60934 Circuit-breakers for equipment (CBE) dModels certified by third party (TÜV certified products) When the CE Mark is indicated on a machine tool or a control unit, it is recommended to use a low voltage circuit breaker certified by a third party (TÜV certified product) as a built-in component.
Corresponding to EMC (Electromagnetic Compatibility) Directive
The Directive prescribes that products shall not emit high-intensity radio waves to the outside and shall not be affected by external electromagnetic waves. Molded case circuit breakers (electronic type) and earth leakage circuit breakers are covered by the EMC Directive.
Corresponding to Machinery Directive
Low voltage circuit breakers are components used in equipment, such as machine tools and control units, and are not covered by any machinery directive. When the CE Mark is indicated on a machine tool or a control unit, it is recommended to use a low voltage circuit breaker certified by a third party (TÜV certified product) as a built-in component.
83
4 2 Selection
The CSA Standards are product safety standards established by CSA. In Canada, the safety of electric products is regulated by the state laws, and some state laws prescribe that circuit breakers shall be certified by the CSA Standards. Therefore, when devices, control panels and machines are exported to Canada, these products must be CSA certified. UL certified products have received CSA certification from the testing body UL and allowed to be used in control panels and machines to be exported to Canada. UL has been authorized as a testing, certification and quality certification body by SCC, and CSA certified products tested by UL have been approved by the safety regulations in all states of Canada. It is allowed to attach the following certification marks to products certified by both UL and CSA. (It is also allowed to attach the separate marks for the US and Canada as before.)
4 Selection
2
Selection of MCCB and ELCB
dMolded Case Circuit Breakers and Motor Protection Breakers North American Safety Mark
Specifications
Class
Applicable Models and Assignments
Compulsory Mark
Third Party Mark
UL Stgandards
CSA Standards
CCC
CE
USA
Canada
China
Europe
TÜV Rheinland Germany
Classification Society (*1) NK
Japan
C
2 Selection
4
NF30-CS NF63-CV, NF125-CV NF250-CV NF400-CW, NF630-CW, NF800-CEW NF32-SV, NF63-SV, NF125-SV NF125-SEV
− − − − − −
− − − − − −
− − − − − −
− − − − − −
− − − − − −
NF250-SV
−
−
−
−
−
−
(Self Declaration)
− − − − (Except for 4P) −
(Self Declaration)
−
(Self Declaration) (Self Declaration) (Self Declaration) (Self Declaration) (Self Declaration) (Self Declaration) (Self Declaration)
− − − − − − −
− − −
(Self Declaration)
−
−
(Self Declaration)
−
(Self Declaration) (Self Declaration) (Self Declaration)
− − −
−
(Self Declaration)
−
(Except for 250A)
− − − −
−
(Self Declaration) (Self Declaration) (Self Declaration) (Self Declaration)
− − − − − NF125-SGV, NF160-SGV, NF250-SGV, NF250-SEV S NF400-SW, NF630-SW − − − − − NF400-SEW, NF630-SEW NF800-SEW, NF800-SDW − − − − − NF1000-SEW, NF1250-SEW − − − − − NF1600-SEW − − − − − NF1250-SDW, NF1600-SDW − General − − − − − NF63-HV − − − − − NF125-HV − − − − − NF125-HEV − − − − − NF250-HV L/H/R NF125-LGV, NF125-HGV, NF160-LGV, NF250-LGV, − − − − − NF250-HGV, NF250-HEV, NF125-RGV, NF250-RGV NF400-HEW, NF400-REW − − − − − NF630-HEW, NF630-REW NF800-HEW, NF800-REW − − − − − NF125-UV − − − − − − U NF250-UV, NF400-UEW − − − − − − NF800-UEW − NF32-SV MB, NF63-CV MB, − − − − − Motor NF63-SV MB, NF125-SV MB Protection − − − − − NF250-SV MB − − − − NF50-SVFU, NF100-CVFU − − − − NF125-SVU, NF125-HVU − − − − UL 489 NF225-CWU (Except for 250A) UL − − − − Listed NF250-SVU, NF250-HVU NF400-SWU, NF400-HWU − − − − − NF630-SWU, NF630-HWU Note *1 Except for 4 poles breaker. Remark: 1. KC (Korea Certification) Mark and GOST-R (Russian Standards) approval products are prepared. Please inquire details.
−
dEarth Leakage Circuit Breakers North American Safety Mark
Specifications
Class
Compulsory Mark
UL Stgandards
CSA Standards
CCC
CE
USA
Canada
China
Europe
Applicable Models and Assignments
Third Party Mark Classification Society TÜV NK Rheinland Germany Japan
−
NV63-CV, NV125-CV C
−
−
−
−
− − − NV250-CV − − − − − − − NV400-CW, NV630-CW − − − − − NV32-SV, NV63-SV − − − − − NV125-SV − − − − − NV250-SV S CE and CCC NV125-SEV, NV250-SEV, NV400-SW, NV400-SEW, − − − − − NV630-SW, NV630-SEW, NV800-SEW − − − − − NV63-HV − − − − − NV125-HV H/R − − − − − NV125-HEV, NV250-HV, NV250-HEV − − − − − NV400-HEW, NV400-REW, NV630-HEW, NV800-HEW − − − − NV50-SVFU, NV100-CVFU UL 489 − − − − UL NV125-SVU, NV125-HVU Listed − − − − NV250-SVU, NV250-HVU Remark: 1. KC (Korea Certification) Mark and GOST-R (Russian Standards) approval products are prepared. Please inquire details.
dMiniature Circuit Breakers Specifications
Class
IEC
BH
General
DIN
84
Applicable Models
BH BH-P BH-D6 BH-D10 BH-DN BV-D BV-DN KB-D
Compulsory Mark CCC CE China Europe
− −
− − (Self Declaration) (Self Declaration) (Self Declaration) (Self Declaration) (Self Declaration) (Self Declaration)
(Except for 2P)
(Self Declaration)
−
−
(Self Declaration) (Self Declaration) (Self Declaration)
− − −
− − − − −
(Self Declaration)
−
−
−
(Self Declaration) (Self Declaration) (Self Declaration) −
− − − −
− − − − − − −
4 Selection 2 Selection of MCCB and ELCB
dCircuit Protectors North American Safety Mark
Specifications
Class
Compulsory Mark
UL Stgandards
CSA Standards
CCC
CE
USA
Canada
China
Europe
Applicable Models and Assignments
Third Party Mark TÜV Rheinland Germany
Classification Society NK
Japan
General
CP
CP30-BA
−
−
−
−
CP-S
−
−
−
−
−
−
(EN 60934) (EN 60947-2) (Self-Declaration) −
(EN 60934) −
−
−
−
Remark: 1. KC (Korea Certification) Mark and GOST-R (Russian Standards) approval products are prepared. Please inquire details.
dAir Circuit Breakers North American Safety Mark Class
SW IEC SH
SW JEC SH
CCC
SW
Applicable Models
AE630-SW, AE1000-SW AE1250-SW, AE1600-SW AE2000-SWA, AE2000-SW AE2500-SW, AE3200-SW AE4000-SWA, AE4000-SW AE5000-SW, AE6300-SW AE630-SH, AE1000-SH AE1250-SH, AE1600-SH AE2000-SH, AE2500-SH AE3200-SH AE630-SW, AE1000-SW AE1250-SW, AE1600-SW AE2000-SWA, AE2000-SW AE2500-SW, AE3200-SW AE4000-SWA, AE4000-SW AE5000-SW, AE6300-SW AE630-SH, AE1000-SH AE1250-SH, AE1600-SH AE2000-SH, AE2500-SH AE3200-SH AE630-SW, AE1000-SW AE1250-SW, AE1600-SW AE2000-SWA, AE2000-SW AE2500-SW, AE3200-SW AE4000-SWA, AE4000-SW AE5000-SW, AE6300-SW
CSA Standards
CCC
CE
USA
Canada
China
Europe
Third Party Mark TÜV Rheinland Germany
Assignments
Compulsory Mark
IEC 60947-2 or JIS C 8201-2-1
−
−
−
−
−
−
(Self Declaration)
−
IEC 60947-2
−
−
−
−
−
−
(Self Declaration)
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
(Self Declaration)
−
4
JEC 160
CCC
2 Selection
Specifications
UL Stgandards
Note *1 Except for four poles breaker. Remark: 1. GOST-R (Russian Standards) approval products are prepared. Please inquire details.
dMolded Case Circuit Breakers , Motor Protection Breakers, Air Circuit Breakers, Circuit Protectors and Miniature Circuit Breakers (Classification Society) Specifications
Applicable Models
Class
NF30-CS NF63-CV, NF125-CV NF250-CV NF400-CW, NF630-CW NF800-CEW NF32-SV, NF63-SV, NF125-SV NF250-SV NF400-SW, NF630-SW S NF400-SEW, NF630-SEW NF800-SEW NF1000-SEW, NF1250-SEW NF63-HV, NF125-HV NF250-HV H/R NF400-HEW, NF400-REW NF630-HEW, NF630-REW NF800-HEW, NF800-REW NF125-UV, NF250-UV U NF400-UEW, NF800-UEW NF32-SV MB, NF63-CV MB Motor NF63-SV MB, NF125-SV MB Protection NF250-SV MB AE630-SW, AE1000-SW AE1250-SW, AE1600-SW AE2000-SWA, AE2000-SW AE AE2500-SW, AE3200-SW AE4000-SWA AE4000-SW, AE5000-SW, AE6300-SW CP CP30-BA C
General
BH
BH-P
Classification societies (Note) ABS GL BV
CCS
DNV
Japan
United Kingdam
USA
Germany
France
China
Norway
−
−
− Scheduled to be certified Scheduled to be certified − − Scheduled to be certified Scheduled to be certified
− − −
−
−
− Scheduled to be certified Scheduled to be certified (HEW) − Scheduled to be certified −
NK
LR
−
− −
Scheduled to be certified
−
−
−
−
− −
− −
−
−
Remark: 1. Four poles breakers does not acquire Classification Society approval.
85
4 Selection
3
Selection of ELCB
1. Electric Shock Protection
Time for which current flows (t)
The safety standards for current passing through the human body are determined based on physiological phenomena as shown below. In places where secondary accidents may be caused by electric shock: Area below the curve b In places where secondary accidents will not be caused by electric shock: Area below the curve c1
Current through body (IB)
4 3 Selection
Fig. 4.17 Influence of AC (15 Hz to 100 Hz) on human body (IEC/TS60479-1)
86
4 Selection 3 Selection of ELCB
2. ELCB Grounding Method Select the rated sensitivity current based on the grounding method, purpose of protection and protection ground resistance value of load device. If the line is excessively long, the circuit breaker may operate unnecessarily owing to leakage current. Calculate the leakage current referring to Table 4-25. In this case, it is common to select sensitivity current approx. 10 times as high as the leakage current. Table 4-24 Type of earthing system
TN system TN-S system
TN-C system L1 L2 L3 PEN
Typical arrangement
TT system
TN-C-S system L1 L2 L3 N PE
L1 L2 L3 PE N
PEN
IT system L1 L2 L3 N
L1 L2 L3
PE
PE
The touch voltage is limited to 50V. Zs Ia 50 V Zs: fault loop impedance (Ω) Ia: current causing the automatic operation of the disconnecting device within the time as below (A) U0: nominal line to earth voltage (V)
Maximum disconnection times (sec) Branch circuits rated 32 A and less
- MCCBs Not ELCBs
120 V
230 V
400 V
TN system
0.8
0.4
0.2
0.1
5
TT system
0.3
0.2
0.07
0.04
1
- MCCBs - ELCBs
Over 400 V
- MCCBs - ELCBs (except in TN-C zone)
Wiring work Wire size 8 mm2 or less
A 4 m or more • Wiring on first floor ceiling of wooden building • Wiring on second and higher floors of wooden building • Aerial wiring (Except C and D)
B 10 cm or more
C 1.5 mm or more
• Wiring in RC building • Wiring with vinyl tube and exposed wiring in steel frames (Except C and D)
• Vinyl tube burying • Vinyl tube laying in close contact with steel frames in steel building
- Insulation monitoring devices + ELCBs
- ELCBs
Table 4-25 Leakage current when 600-V vinyl insulated wire is laid on 1-km ∆-connected 3-phase 3-wire 200-V line Distance from grounded part
4
Others
D In close contact • Wiring in metallic conduit • Wiring in metallic duct
Table 4-26 Leakage current conversion table Type of line
Magnification
Single-phase 100-V line
0.3
Single-phase 3-wire 200-V line
0.3
3-phase 415-V line
0.60 mA/km
1.29 mA/km
19.9 mA/km
100 mA/km
14
0.66
1.44
22.1
110
22
0.72
1.55
23.9
120
38
0.81
1.75
26.9
135
60
0.99
2.14
32.9
165
100
1.14
2.46
37.9
189
150
1.25
2.72
41.8
209
250
1.46
3.16
48.6
243
325
1.52
3.29
50.7
253
500
1.71
3.69
56.8
284
(
Y
U0 AC
Earth leakage protective device
Id RA 50 V RA: sum of the resistances of the earth electrode and the protective conductor (Ω) Id: first fault current (A)
connection)
0.7
Notes *1 The leakage current on rubber insulated wire (RB) is about 70% of the above values, and that on 3-core 600-V cross-linked polyethylene insulated wire (CV) is about 50%. *2 At 50 Hz, the values are 84% of the above values. *3 To obtain the leakage current on another line, multiply the values shown in Table 4-25 by the magnification shown in Table 4-26. *4 To determine the line length, add the length of all wires after ELCB installation point.
87
3 Selection
Protective condition
RA In 50 V RA: sum of the resistances RA: of the earth electrode RA: and the protective RA: conductor (Ω) In: rated current sensitivity (A)
4 Selection
Selection of ELCB
3
3. Rated Voltage and Number of Poles Select the rated voltage and number of poles according to the circuit voltage and type. The following table shows the standard circuit voltage values. However, even at special voltage, if the voltage including the circuit voltage fluctuation is within the voltage range shown right, the leakage protection device will operate.
Voltage fluctuation range in which leakage protection function is operable Voltage (V)
80
264 242
121 160
100
200
253
320
484
300
500
400
100-200V 100-230V 100-240V 100-200-415V 100-440V 200-415V Switching between 100 and 200 V
Voltage switching 100V type Specific voltage 100V product
200V
200-440V Switching between 200 and 415 V
200V
415V 415V
Table 4-27 Circuit type
100V
4 3 Selection
Single-phase 2-wire 100- or 200-V circuit
Single-phase 3-wire 100- and 200-V circuit
100V
200V
200V
100V
Example of connection
2-pole breaker
・100-440V ・100-200-415V ・100-200V ・100-240V
Circuit type
3-pole breaker
2-pole breaker
・100-440V ・100-200-415V ・100-200V ・100-230V ・100V
・100-440V ・100-200-415V ・100-200V ・100-240V
3-pole breaker
3-pole breaker
・100-440V ・100-200-415V ・100-200V ・100-230V ・200-415V ・200-440V
・100-200-415V ・100-200V ・200-415V ・100-230V ・100-440V ・200-440V
3-phase 3-wire 200-V circuit
2- or 3-pole breaker
・100-200-415V ・100-200V ・100V ・100-240V ・100-230V ・100-440V
2- or 3-pole breaker
・100-200-415V ・100-200V ・200-415V ・100-240V ・100-230V ・100-440V ・200-440V
3-phase 3-wire 415-V circuit
200V
415V
3-pole breaker
Example of connection
・100-200-415V ・100-200V ・200-415V ・100-440V ・100-230V ・200-440V
Circuit type
2- or 3-pole breaker
3-pole breaker
・100-200-415V ・100-200V ・200-415V ・100-240V ・100-440V ・200-440V
・100-200-415V ・200-415V ・415V ・100-440V ・200-440V
3-pole breaker
・100-200-415V ・200-415V ・415V ・100-440V ・200-440V
3-phase 4-wire 415-V circuit 415V
240V
Example of connection
4-pole breaker N ・100-200-415V ・200-415V ・100-440V ・200-440V
3-pole breaker
・100-200-415V ・200-415V ・415V ・100-440V ・200-440V
3-pole breaker
・100-200-415V ・200-415V ・415V ・100-440V ・200-440V
2- or 3-pole breaker ・100-200-415V ・200-415V ・100-240V ・100-440V ・200-440V
3-pole breaker
・100-200-415V ・200-415V ・100-440V ・200-440V
(1) When a 3-pole circuit breaker is used as a 2-pole one, use the right and left poles. (2) For the mains of a 3-phase 4-wire 415-V circuit, use a 4-pole circuit breaker having a rated voltage of 415 V or 440 V, and connect the neutral pole to the N pole on the right side.
88
4 Selection 3 Selection of ELCB
4. Earth Fault Protection Coordination and Combination of Devices Table 4-28 Protection type With selectivity only for earth fault breaking With selectivity for earth fault breaking and cascade type of short-circuit breaking With selectivity for earth fault breaking and short-circuit breaking
Details On general lines, the protection grounding resistance is relatively large and the earth fault current is small. In this case, install a time-delay relay on the main circuit and a high-speed relay on a branch circuit. The selectivity for earth fault breaking is as stated above. Significant short-circuit fault very rarely occurs because of its nature (in most cases, circuits are broken at the early stage of earth fault). This protection is applied when the continuity of power supply is expendable. (Refer to the combination for cascade breaking on page 83.)
Installation point
This protection is applied when selectivity is necessary in the entire area of fault. (Refer to the combination for selective breaking on page 81.)
Main circuit
Main circuit Branch circuit Main circuit Branch circuit
Branch circuit
Combination • Time-delay ELCB • Combination of MCCB and time-delay earth leakage relay High-speed ELCB • Class S time-delay ELCB • Combination of MCCB (class U) and time-delay earth leakage relay • Class C time-delay ELCB • Combination of MCCB (class C) and high-speed earth leakage relay Combination of electronic MCCB and time-delay earth leakage relay • High-speed ELCB • Combination of MCCB and high-sspeed earth leakage relay
Remark: 1. “Time-delay or high-speed earth leakage relay” refers to NV-ZBA, NV-ZSA, NV-ZHA or NV-ZLA.
Characteristic of time-delay relay with sensitivity of 500 mA (0.3 s) NV1
0.5 0.4 0.3
ZT60B
Selective breaking on earth fault
0.2
3
ZT40B
NV2
3
NV-ZSA 200mA 0.3s Time-delay
0.1 Characteristic of high-speed relay with sensitivity of 30 mA (within 0.1 s)
Selective breaking on earth fault
Point B
3
Point A
30
250
500 600700800
3
NV3
NV32-SV 30mA 0.1s High-speed
15
NV-ZSA 500mA 0.8s Time-delay
3
4
NV5
NV125-CV 30mA 0.1s High-speed
3 Selection
Operating time (s)
1.0
NV4
NV63-CV 30mA 0.1s High-speed
1000
Earth fault current (mA)
Fig. 4.18 Example of coordination of time-delay and high-speed relays for earth fault breaking
89
3 Selection
MEMO
4
90
5
Installation and Connection
1) Connection Types… ……………………………………………………………………………………………………………………………… 92 2) Connecting Parts…………………………………………………………………………………………………………………………………… 94 3) Standard Tightening Torque… …………………………………………………………………………………………………………………… 95 4) Crimp Terminal Type… …………………………………………………………………………………………………………………………… 96 5) Busbar… …………………………………………………………………………………………………………………………………………… 98 6) Insulation Distance on Power Source Side… …………………………………………………………………………………………………… 99 7) Effect of Installation Orientation………………………………………………………………………………………………………………… 100 8) Connection of Line and Load…………………………………………………………………………………………………………………… 100
91
Installation and Connection
5
1
Installation and Connection
1. Connection Types Table 5-1 Connection Connection type (Code address)
Screw terminal (AMP-N)
Image
Please refer to page 98.
Front connection (F) Busbar terminal Solderless (BOX) (BAR) terminal (SL)
Bar stud (B-ST)
A
B
A B
− − NF30-CS − NF32-SV • NF63-CV • NF63-SV • NF63-HV NF125-CV • NF125-SV • NF125-HV • NF125-SEV • NF125-SGV • NF125-LGV • NF125-HEV • NF125-HGV NF160-SGV • NF160-LGV • NF160-HGV • NF250-CV • NF250-SV • NF250-HV • NF250-SEV • NF250-HEV • NF250-SGV • NF250-LGV • NF250-HGV − NF400-SW • NF400-SEW • NF400-HEW • NF400-REW • NF400-CW − NF630-SW • NF630-SEW • NF630-HEW • NF630-REW • NF630-CW − NF800-SEW • NF800-HEW • NF800-REW • NF800-SDW • NF800-CEW − NF1000-SEW • NF1250-SEW • NF1600-SEW NF125-UV NF125-RGV • NF250-RGV • NF250-UV NF400-UEW − − NF800-UEW − NF50-SVFU NF100-CVFU NF125-SVU NF125-HVU UL NF250-SVU NF250-HVU − NF225-CWU NF-SKW • NF-SLW − − − BH BH-P (Only load side) − NV32-SV • NV63-CV • NV63-SV • NV63-HV NV125-CV • NV125-SV • NV125-HV • − NV125-SEV • NV125-HEV − NV250-CV/SV/HV • NV250-SEV/HEV − NV400-SW • NV400-SEW • NV400-HEW • NV400-REW • NV400-CW NV630-SW • NV630-SEW • NV630-HEW • NV630-CW − − NV800-SEW • NV800-HEW Kind of terminal screw (A) (Circuit breakers having frame size of 1000A and more are not provided with terminal screws (A).)
ELCB
C•S•H
Pan-head screw with clamp
Pan-head screw
M5
M8
Screw size NF32-SV 63-CV 63-SV 63-HV 50-SVFU(*1)
BH-P
NV32-SV 63-CV 63-SV 63-HV
Type
In case of clamp connection (*1)
NF 63-CV(60, 63A) 63-SV(60, 63A) 63-HV(60, 63A) 125-CV 125-SV 125-HV 125-SEV 125-HEV 100-CVFU 125-SVU 125-HVU 125-UV
qWhen the wire size is 5.5 mm2 or more, divide the wires, and connect them. wWhen connecting wires differing in size, for example, f1.6 wires and 5.5-mm2 wires, connect the two kinds of wires together to a crimp terminal because the thinner wires easily come off. eDo not tighten directly solid wires and cords consisting of thin copper wires used as strands, for example f1.6 and 1.25-mm2 wires, together. Note *1 It is impossible to directly connect the wires of 40- and 50-A, NF/NV 50-SVFU.
92
Bolt (Hex-socket) M8
2×M8
− −
−
−
−
−
− −
−
− −
− −
−
−
−
−
− − − −
− − −
−
−
Shape
Remarks
1 Installation and Connection
R•U
MCCB
C • S • H • MB
5
Rear (B) Round stud (B-ST)
Bolt M10
NF NV NF NV NF 63-CV(60, 63A) 125-SEV 400-UEW 800-SEW 400-CW 125-HEV (4P) 800-HEW 400-SW 63-SV(60, 63A) 125-RGV 63-HV(60, 63A) 125-SGV 800-CEW 400-SEW 125-CV 800-SEW 400-HEW 125-LGV 125-HGV 800-HEW 125-SV 400-REW 160-SGV 400-UEW(3P) 125-HV 800-REW 160-LGV 630-CW 125-SEV 160-HGV 800-UEW 630-SW 125-HEV 250-CV 800-SDW 250-SV 630-SEW 250-HV 630-HEW 250-SEV 630-REW 250-HEV NV 250-SGV 250-LGV 400-CW 250-HGV 400-SW 250-RGV 400-SEW 250-UV 400-HEW 225-CWU 250-SVU 400-REW 250-HVU 630-CW NV 630-SW 125-SEV 630-SEW 125-HEV 250-CV 630-HEW 250-SV 250-HV 250-SEV 250-HEV
−
With insulating base (tube) for installation of metallic board The bar stud installation position can be turned 90° on all models (except NF800-UEW). The current-carrying capacity of a vertically installed bus bar is larger than that of a horizontally installed bus bar even if the bus bars have the same dimensions.
5 Installation and Connection
1 Installation and Connection
Screw terminal (PM)
Plug-in type for distribution board For distribution board for electric lamps (BPA)
− −
−
− −
−
−
−
−
−
−
−
−
− (Except for 4P) (Except for NF800-UEW) − −
(Except for 4P) −
− −
−
−
− −
− −
−
−
−
−
−
−
− − − −
− − −
− − −
−
−
−
−
−
−
Plug-in (PM)
(Except for NF1600-SEW)
The circuit breaker can be connected only by pushing it onto the preliminarily wired terminal block. Install it tightening the supplied screws through the mounting holes.
5 1 Installation and Connection
Bar stud (PM)
Mounting base for distribution board for electric lamps. For the external dimensions, refer to page 139.
Table 5-2 List of terminal screws (B)
MCCB
U C•S•H
ELCB
C•S•H
Model
Connection type NF400-CW • NF400-SW • NF400-SEW • NF400-HEW • NF400-REW • NF630-CW • NF630-SW • NF630-SEW NF630-HEW • NF630-REW • NF800-CEW • NF800-SEW • NF800-HEW • NF800-REW • NF800-SDW • NF-SKW • NF-SLW NF1000-SEW • NF1250-SEW NF1600-SEW NF400-UEW NF800-UEW NV400-SW • NV400-SEW • NV400-HEW • NV400-REW • NV400-CW • NV630-SW • NV630-SEW • NV630-HEW • NV630-CW • NV-SKW NV800-SEW • NV800-HEW
Front
Rear
Plug-in
M12 bolt M12 bolt M10 bolt M12 bolt M12 bolt M12 bolt M12 bolt
— —
93
5
Installation and Connection
1
Installation and Connection
2. Connecting Parts For the connection shown in the table on the previous page, the following parts are available as connecting parts. Table 5-3 Studs on rear surface (B-ST) Type name
1 Installation and Connection
5
Applicable models
Number of poles
ST-05SV2
2
ST-05SV3 ST-05SV4 ST-1SV2
3 4 2
ST-1SV3
3
ST-1SV4 ST-1HV2 ST-2SV2
4 2 2
ST-2SV3
3
ST-2SV4
4
ST-4SW2
2
ST-4SW3
3
ST-4SW4
4
ST-6SW2 ST-6SW3 ST-6SW4
2 3 4
ST-8SW2
2
ST-8SW3
3
ST-8SW4
4
MCCB
ELCB
NF32-SV, NF63-CV, NF63-SV NF63-HV
NV32-SV, NV63-CV NV63-SV, NV63-HV — —
NF63-SV, NF63-HV NF125-CV, NF125-SV NF125-HV(3, 4P)
NV125-CV, NV125-SV NV125-HV
NF125-HV(2P) NF125-SEV, NF125-HEV, NF125-RGV NF125-SGV, NF125-LGV, NF125-HGV NF160-SGV, NF160-LGV, NF160-HGV NF250-SGV, NF250-LGV, NF250-HGV NF250-CV, NF250-SV NF250-LGV/HGV, NF250-HV NF250-SEV, NF250-RGV NF250-HEV, NF125-SGV/HGV NF125-LGV, NF160-SGV NF160-LGV/HGV
Stud shape and major included parts ★Round studs Round studs (with insulating tube) sets
Set of order
(2-pole: 4 pcs, 3-pole: 6 pcs, 4-pole: 8 pcs)
Bolts and nuts ★Bar studs Bar studs (with insulating tube) sets
(2-pole: 4 pcs, 3-pole: 6 pcs, 4-pole: 8 pcs)
Bolts and nuts
— —
NV125-SEV, NV125HEV NV250-CV, NV250-SV NV250-HV, NV250-SEV NV250-HEV
★Bar studs Bar studs (with insulating tube) (2-pole: 4 pcs, 3-pole: 6 pcs, 4-pole: 8 pcs)
sets
Bolts and nuts
— NF400-CW, NF400-SW NF400-SEW, NF400-HEW NF400-REW NF630-CW, NF630-SW NF630-SEW, NF630-HEW NF630-REW
NV400-CW, NV400-SW NV400-SEW NV400-HEW NV400-REW — NV630-CW, NV630-SW NV630-SEW, NV630-HEW —
NF800-SDW, NF800-CEW NF800-SEW, NF800-HEW NF800-REW
Remarks
★Bar studs Insulating bases
One set includes the parts for one unit. Please place an order for the number of circuit breakers.
(2-pole: 4 pcs, 3-pole: 6 pcs, 4-pole: 8 pcs)
sets
Bar studs (2-pole: 4 pcs, 3-pole: 6 pcs, 4-pole: 8 pcs)
Mounting screws, bolts and nuts ★Bar studs Insulating base (2 pcs) Bar studs sets
NV800-SEW, NV800-HEW
(2-pole: 4 pcs, 3-pole: 6 pcs, 4-pole: 8 pcs)
Mounting screws, bolts and nuts
Table 5-4 Plug-in type terminal blocks (PM) Type name
Number of poles
Applicable models
2P
PMDN-05SV3L
3P
PMDN-05SV4L
4P
PMDN-05SV2H
2P
NF63-CV/SV/HV (60A, 63A)
PMDN-05SV3H
3P
PMDN-05SV4H
4P
NF63-CV/SV/HV (60A, 63A) NV63-CV/SV/HV (60A, 63A)
PMDN-1SV2
2P
NF125-CV/SV
PMDN-1HV2
2P
NF125-HV
PMDN-1SV3
3P
PMDN-1SV4
4P
NF125-CV/SV/HV NV125-CV/SV/HV
PMDN-1UV2
2P
PMDN-1UV3
3P 2P
PMDN-2SV3
3P
PMDN-2SV4
4P
PMDN-2SV2
2P
PMDN-2SV3
3P
PMDN-2UV2
2P
PMDN-2UV3
3P
— PMDN-4SW2
PMDN-8SW2
NF125-SEV/HEV/SGV/LGV/HGV NF160-SGV/LGV/HGV NF250-CV/SV/HV/SEV/HEV/SGV/LGV/HGV NV125-SEV/HEV NV250-CV/SV/HV/SEV/HEV NF125-RGV, NF250-RGV
NF250-UV
2P
NF400-CW/SW
3P
NF400-CW/SW/SEW NV400-CW/SW/SEW
3P
NF400-HEW/REW NV400-HEW/REW
4P
NF400-SW/SEW NV400-SEW
4P
NF400-HEW
2P
NF800-SDW
3P
NF800-CEW/SEW NV800-SEW
3P
NF800-HEW/REW NV800-HEW
4P
NF800-SEW
4P
NF800-HEW
PMDN-8SW3
PMDN-8SW4
NF125-UV
4P
PMDN-4SW3
PMDN-4SW4
NF32-SV NF63-CV/SV/HV (3A-50A) NV32-SV NV63-CV/SV/HV (5A-50A)
sets
Plug-in type terminal block (1 pc) Crip terminals (2-pole: 4pcs, 3-pole: 6 pcs, 4-pole: 8 pcs)
Plug-in type terminal block (1 pc) sets Crip terminals (2-pole: 4 pcs, 3-pole: 6 pcs, 4-pole: 8 pcs)
sets
4P
PMDN-2SV2
Major included parts
NF32-SV NF63-CV/SV/HV (3A-50A)
PMDN-05SV2L
—
Set of order
Plug-in type terminal block (2 pc) Crip terminals (2-pole: 4pcs, 3-pole: 6 pcs)
Plug-in type terminal block (1 pc) Plug-in type barriers sets ( 2-pole: 2 pcs, 3-pole: 4 pcs, 4-pole: 6 pcs) Tulip terminals (2-pole: 4 pcs, 3-pole: 6 pcs, 4-pole: 8 pcs)
Plug-in type terminal block (2 pc) sets Plug-in type barriers (2-pole: 2 pcs, 3-pole: 4 pcs) Tulip terminals (2-pole: 4pcs, 3-pole: 6 pcs)
Plug-in type terminal block (2 pcs) sets Plug-in type barriers (4 pcs) Tulip terminals (3-pole: 6 pcs)
sets
Plug-in type terminal block (2 pcs) Tulip terminals (3-pole: 6 pcs)
Note In addition to the circuit breakers shown above, 4-pole and 2-pole circuit breakers are available. We are ready to manufacture such circuit breakers to order. Please consult us.
94
5 Installation and Connection
1 Installation and Connection
3. Standard Tightening Torque Nut C
Screw A
Round stud
Fig. 1
Insulating tube
Connecting busbar
Fig. 2
Screw E Connecting conductor
Bar stud Insulating base
Connecting conductor
Screw D
Screw A Screw E
Connecting conductor
Circuit breaker
Screw A
Plug-in <Screw terminal>
Bar stud
Plug-in type terminal block Plug-in type stud
Fig. 4
Screw E Plug-in type terminal block
Fig. 3
Table 5-5 Standard tightening torque (*1) Model
MCCB
Connection type
ELCB
NF30-CS NF32-SV, NF63-CV NF63-SV, NF63-HV NF125-CV, NF125-SV NF125-HV, NF125-UV NF125-SEV, NF125-HEV, NF125-RGV NF250-CV, NF250-SV, NF250-HV, NF250-SEV NF250-HEV, NF250-RGV, NF250-UV NF250-LGV/HGV, NF250-RGV, NF125-SGV/HGV NF125-LGV, NF160-SGV, NF160-LGV/HGV NF125-SGV, NF125-LGV, NF125-HGV NF160-SGV, NF160-LGV, NF160-HGV NF250-SGV, NF250-LGV, NF250-HGV NF400-CW, NF400-SW, NF400-SEW NF400-HEW, NF400-REW NF400-UEW (3P) NF400-UEW (4P)
Fig. 5
− NV32-SV, NV63-CV NV63-SV, NV63-HV NV125-CV, NV125-SV NV125-HV
NV125-SEV, NV125-HEV NV250-CV, NV250-SV NV250-HV, NV250-SEV NV250-HEV
NV400-CW, NV400-SW NV400-SEW, NV400-HEW NV400-REW − NV630-CW, NV630-SW NF630-CW, NF630-SW, NF630-SEW NV630-SEW NF630-HEW, NF630-REW NV630-HEW NF800-CEW, NF800-SDW NV800-SEW NF800-SEW, NF800-HEW, NF800-REW NV800-HEW NF800-UEW (*2) NF1000-SEW − NF1250-SEW − NF1600-SEW
Tightening torque N·m Rear Round stud Fig.1 Screw A Nut C Size Tightening torque Size Tightening torque
Plug-in Bar stud Screw terminal Bar stud Fig.5 Fig.4 Fig. 2, Fig.3 Screw E Screw D Screw A Screw E Size Tightening torque Size Tightening torque Size Tightening torque Size Tightening torque
M4×0.7
1
M6
2
−
−
−
−
−
−
−
−
M4×0.7
1
M6
2
−
−
−
−
M6
3
−
−
−
−
−
−
M6
4
M8
12
M8
6
−
−
−
−
−
−
M6
10
M8
12
−
−
M8
12
5 −
−
−
−
M8
20
M12
45
−
−
M12
45
−
−
−
−
M10
30
M12
45
−
−
M12
45
−
−
−
−
M8
20
M12
45
−
−
M12
45
−
−
−
−
M10
30
2-M12
45
−
−
2-M12
45
−
−
−
−
4-M8
12
2-M12
45
−
−
2-M12
45
−
−
−
−
4-M8
12
4-M10
25
−
−
−
−
Notes *1 The appropriate range of tightening torque is ±20% of each value (standard tightening torque) shown in the above table. Please refer to the supplied assembly manual and instruction manual for more information. *2 The plug-in type is not available.
95
1 Installation and Connection
Rear
5
Installation and Connection
Installation and Connection
1
4. Crimp Terminal Type
As the terminals in , commercially available crimp terminals can be used. Please purchase the terminals at an electric material store. For others, the crimp terminals for MCCB must be used. Place an order with us. For the connection types shown in Fig. a and Fig. b, only crimp terminals will be delivered.
Table 5-6 List of applicable crimp terminals
Frame (A)
Nominal sectional area mm2 600 V, IV wire at 30°C, not Allowable current in conduit
Size of mm2 Model MCCB
30 50 100 30 32 50 60 63
ELCB
BH-P
–
BH-P100
–
NF30-CS, NF32-SV, NF63-CV*, NF63-SV* NV32-SV, NV63-CV*, NV63-SV* NF63-HV* NV63-HV* *50A or below *50A or below NF63-CV, NF63-SV, NF63-HV 60, 63A –
125
125 225 250
1 Installation and Connection
5
2 (*4)
400 600 630 800 1000 1200 1250
8
14
22
49A
61A
88A
115A
1.04 to 2.63
2.63 to 6.64
6.64 to 10.52
10.52 to 16.78
R-2-5
R-5.5-5
R-8-5
R-14-5
16.78 to 26.66 BH-22 (L330T459-23)
R-8-8
R-14-8
R-22-8
R-2-5 *(R-2-6)
R-5.5-5 *(R-5.5-6)
R-8-5
R-14-5
JST22-S5 BH-22 (L330T459-23)
NV63-CV, NV63-SV, NV63-HV 60, 63A
R-2-8
R-5.5-8
R-8-8
R-14-8
R-22-8
–
R-2-5 (R-2-6)
R-5.5-5 (R-5.5-6)
R-8-5
R-14-5
JST22-S5 (L330T459-23)
R-2-8
R-5.5-8
R-8-8
R-14-8
R-22-8
R-14-8
R-22-8
NF125-CV, NF125-SV, NF125-HV, NF125-UV NV125-CV, NV125-SV, NV125-HV 60A or more 60A or more NF125-SEV, NF125-HEV, NF125-RGV NF250-CV, NF250-SV, NF250-HV, NF250-UV NV125-SEV, NV125-HEV NF250-SEV, NF250-HEV, NF250-RGV NV250-CV, NV250-SV, NV250-HV NF125-SGV, NF160-SGV, NF250-SGV NV250-SEV, NV250-HEV NF125-LGV, NF160-LGV, NF250-LGV NF125-HGV, NF160-HGV, NF250-HGV NV400-CW, NV400-SW NF400-CW, NF400-SW, NF400-SEW NV400-SEW, NV400-HEW NF400-HEW, NF400-REW, NF400-UEW NV400-REW, NV630-CW NF630-CW, NF630-SW, NF630-SEW NV630-SW, NV630-SEW NF630-HEW, NF630-REW NV630-HEW NF800-CEW, NF800-SEW, NF800-HEW NF800-REW, NF800-UEW, NF800-SDW NF1000-SEW, NF1250-SEW
5.5
27A
NV800-SEW, NV800-HEW
d Reference drawings of connection types
Method of connecting directly to terminal(s) of body
Method of connecting to front bar terminal
To connect one terminal To connect two terminals
Connect with the bolt head downward.
(Fig. a)
96
(Fig. b)
Carefully check the insulating distance between the connecting bus bar, crimp terminal and tightening bolt and the ground and the phase-to-phase insulating distance.
5 Installation and Connection
1 Installation and Connection
<Explanation of abbreviations> 60
100
150
200
325
217A
298A
395A
469A
650A
26.66 to 42.42
42.42 to 60.57
96.3 to 117.2
117.2 to 152.05
192.6 to 242.27
242.27 to 325
AMP #322870 1AF-60 JST 38-S8 (L330T459-12) NTK R38-8S CB60-S8
R-60-12
R-38-12
R-60-12
M5
2 to 3
M8
5 to 7
Remarks
Shape
When connecting two crimp terminals, set the terminals as shown below if the *-marked terminals are used.
M5
2 to 3
M8
5 to 7
M5
2 to 3
M8
5 to 7
I R - 2-5 R - 5.5-5
M8
(Fig. a) R -2-6 R -5.5-6
M8
2CR-150(*1) 2AF (LN300T920-20) (LN300T920-21) CB100-S8 (*1)CB150-S8
R-100-12
R-100-12
R-200-12
R-150-12
R-150-12 RD150-12 SD150-12
R-200-12 RD200-12 SD200-12
M8
8 to 13
When using 2AF, use a crimp tool having a nominal size of 100.
M12
40 to 50
Fit to a front type bar terminal. Up to two pieces can be fitted to one terminal.
JST325-12
JST325-12 RD325-12 SD325-12
(Fig. b)
Notes *1 When using 2CR-150 or CB150-S8, insulate it from TC-S with insulating tube or tape. When using CB150-S8 for a 2- or 3-pole circuit breaker, TCL-2SV3L is applicable. *2 On the power supply side, pan-head screws M5 are used. *3 When tightening a terminal screw without connecting a wire, crimp terminal or bar, tighten the screw to 20 to 30% of the torque shown in the above table (to prevent damage to the threads). *4 The table shows not the allowable current values of circuit breakers, but those of wires applicable to crimp terminals. Remark: 1. For the crimp terminals for UL listed circuit breakers, refer to the page of the characteristics and external dimensions of UL 489 Listed Circuit Breakers.
d Dimensions of crimp terminals <extracted from catalog of JST>
5.3 6.4 8.4 5.3 6.4 8.4 5.3 5.3 6.4 8.4 5.3 5.3 5.3 6.4 8.4 5.3 5.3 6.4 8.4 13.0 8.4 8.4 13.0 8.4 8.4 13.0 8.4 13.0
B
L
F
9.5
16.8
7.3
12.0 21.8 11.0 9.5 12.0 15.0 12.0 9.0 12.0 15.0 9 12.0 9.0 12.0 16.0 12.0 9.5 12.0 16.5 22.0 15.5
19.8 25.8 28.0 23.8 22.3 23.8 29.8 23.8 29.8 28.3 29.8 32.8 30.0 28.7 30.0 33.7 42.5 38.0
8.3 13.0 13.7 9.3 13.8 9.3 13.3
E 4.8 6.8
Applicable wire mm2 1.04 to 0.8 2.63 2.63 to 1.0 6.64
8.5
1.2
6.64 to 10.52
8.5
1.2
6.64 to 10.52
10.5
1.5
10.52 to 16.78
12.0
1.8
16.78 to 26.66
14.5 12.0 13.5 19.5 16.0 14.0
1.8
18.0
2.0
22.5 51.0 20.0 21.0 28.5 55.6 20.4
2.6
22.0 42.7 17.7 16.0 46.7 20.7 22.0 49.7 20.7
26.66 to 42.42 42.42 to 60.57 96.3 to 117.2
Applicable Shape screw size M8 B M8 A M12 A M12 A M12
Part number
Thickness
LN300T920-21 L330T402-8 R150-12 R200-12 325-12 CB60-S8 CB100-S8 CB150-S8
M8
B
L
F
8.4 8.4 13.0 13.0 13.0 8.4 8.4 8.4
22.5 25.3 36.0 44.0 50.5 16.0 22.0 22.0
70.0 61.5 66.0 78.0 88.0 46.7 52.5 61.0
33.0 23.0 21.0 24.5 33.5 20.7 20.5 23.0
Applicable Shape screw size fd2 14.0 14.0 C M12 14.0 14.0 14.0
Part number RD60-12 RD100-12 RD150-12 RD200-12 RD325-12 SD150-12 SD200-12 SD325-12
Shape A
B
External dimensions fd2
C
M12
F
E L
Thickness
27.0
3.2
31.5 35.5 18.0 21.0 27.0
4.0 4.5 2.0 2.6 3.2
External dimensions B
22.0 28.5 36.0 44.0 50.5 36.0 14.0 44.0 50.5
Shape B
φd2
E
L
F
89.0 95.5 106.0 116.5 123.8 107.0 108.0 125.0
20.0 20.3 21.0 23.0 23.0 29.0 36.0 38.0
E
N Thickness
18.0 2.0 21.0 2.6 27.0 40 3.2 31.5 4.0 35.5 4.5 28.0 3.2 32.0 32 4.0 37.0 4.5
Shape C
φd2
Applicable wire mm2 117.2 to 152.05 192.6 to 242.27 242.27 to 325 42.42 to 60.57 96.3 to 117.2 117.2 to 152.05 Applicable wire mm2 42.42 to 60.57 96.3 to 117.2 117.2 to 152.05 192.6 to 242.27 242.27 to 325 117.2 to 152 192.6 to 242.2 242.2 to 325
φd2
B
External dimensions fd2
B
R2-5 R2-6 R2-8 R5.5-5 R5.5-6 R5.5-8 R8-5 8-5NS R8-6 R8-8 8-5SC-9 R14-5 14-5NS R14-6 R14-8 L330T459-23 22-5NS 22-S6 R22-8 R22-12 38-S8 R38-8 R38-12 L330T459-12 R60-8 R60-12 LN300T920-20 R100-12
Applicable Shape screw size M5 A M6 M8 M5 A M6 M8 M5 M5 A M6 M8 M5 M5 M5 A M6 M8 M5 M5 A M6 M8 M12 M8 A M8 M12 M8 A M8 M12 B M8 A M12
B
Part number
F
E L
N
F
E
L
97
5 1 Installation and Connection
R-38-12
Tightening torque N•m
M5
AMP #322870 1AF-60 JST 38-S8 (L330T459-12) NTK R38-8S CB60-S8
R-60-8
Screw size
M5 • M6
1AF-60 AMP #322870 JST 38-S8 (L330T459-12) NTK R38-8S CB60-S8
R-38-8
Crimp terminal tightening screw
Reference drawing of connection type
38 162A
R····························Product specified by JIS CB··························Product specified by JEM 1399 AMP·······················Product made by Nippon AMP JST························Product made by J.S.T. Mfg. Co., Ltd. NTK························Product made by Nippon Tanshi Co., Ltd. NTM·······················Product made by Nichifu Co., Ltd. DST························Product made by Daido Solderless Terminal Mfg. Co., Ltd.
5
Installation and Connection
Installation and Connection
1
5. Busbar
C
F G
f 9 or f 8.5
A
H
10
Conductor thickness t = 4 max. Nominal diameter of conductor tightening screw J
ON
4
A
C
B
Nominal diameter of conductor tightening screw J
ON
OFF
H
H
OFF
C
D
B
D E
E Conductor thickness t = 6 max.
Fig. 2 C
A
C
B
H
F
15
Fig. 1 f9
Conductor thickness t = 10 max.
20
F
H
f 6.5
10
The size of the conductor can be connected is shown on the outline drawing of each model. The following special busbars are available. Use them as needed. When using any busbar, isolate it from the bare busbar on the circuit breaker power supply side with an insulating barrier.
Nominal diameter of conductor tightening screw J
ON
OFF
H
5
D
Fig. 3
Table 5-7 Table of variable dimensions
FB-1SV
ELCB
NF32-SV NF63-CV (50A or below) NF63-SV (50A or below) NF63-HV (50A or below)
NV32-SV NV63-CV (50A or below) NV63-SV (50A or below) NV63-HV (50A or below)
NF125-CV, NF125-SV NF125-HV, NF125-UV
NV125-CV NV125-SV NV125-HV
Outline and dimentions
Fig.
A
B
C
Busbar D E
1
24
24
2
50
2
24
24
4
3
24
24
6
F
G
H
J
75
11.5
−
25
M5×0.8
60
90
18
15
29
M8
70
105
20
−
37
M8
11 .
40.5
5
2
FB-05SV
Applicable models MCCB
f 6.5 f5.5
18
46
4
Type name
15
f 8.5 f 8.5
FB-2SV
98
NF125-SEV NF125-HEV, NF125-RGV NF250-CV, NF250-SV, NF250-HV NF250-UV, NF250-SEV NF250-HEV, NF250-RGV NF125-SGV/LGV/HGV NF160-SGV/LGV/HGV NF250-SGV/LGV/HGV
NV125-SEV NV125-HEV NV250-CV, NV250-SV NV250-HV, NV250-SEV NV250-HEV
20
57.5
6
1 Installation and Connection
E
f9 f9
5 Installation and Connection
1 Installation and Connection
6. Insulation Distance on Power Source Side dBasic concept
Insulation distance (distance indicated in standards)
Be sure to at least secure the insulation distances (spatial distance and creeping distance) specified by the codes and standards of the relevant equipment and facilities where the circuit breakers are installed. It is recommended that insulation barriers and insulation tape be used to enhance the electrical insulation between bare-live parts and between bare-live parts and ground to avoid accidents otherwise caused by a loose metal piece, conductive dust, abnormal surge voltage in the circuit or a similar event so as to improve the reliability of panels.
Arc Space (insulation space)
At the exhaust outlet side of breaker, arc space is necessary. When the actual load circuit is opened, especially when a large current such as overload or shortcircuit is interrupted, ionized gas is emitted from the exhaust outlet. This gas can cause a short circuit between bare, live parts such as busbars, and also can cause grounding faults between conductive installation metal panels. Therefore, it is important to secure enough arc space at the exhaust outlet side of the breaker and to strengthen insulation of parts exposed to the gas. In addition, securing enough space at the front of the exhaust outlet is necessary, because when the gas emission is blocked, failures such as deterioration of breaking performance can be caused.
dInsulation required part
With regard to insulation of bear, live parts of the line side of the breaker, please make sure to insulate at least C part C indicated in the diagram above with insulation tape, a tube or a terminal cover. qA : Distance from the circuit breaker to the ceiling plate wB1 : Distance from the circuit breaker to the uncovered conducting part of the upper circuit breaker terminal (front connection) eB2 : Distance from the lower circuit breaker to the end face of the upper circuit breaker (rear connection) rD1 : Distance from the side of the breaker to the side plate tC : Insulated length of the power source terminal of the circuit breaker (front connection) Please secure insulation using insulating tape, insulating tubing, insulation barrier, or a terminal cover, between bare charge parts within this size range. Please refer to a table a necessary size must. When using insulation tape and insulation tubing together with insulation barriers and terminal covers, make them overlap with the other by at least 10 mm. For the models with insulation barriers supplied as standard, please make sure to use the barriers. a : clearance specified in standard yD2 : Side-to-side spacing of breakers While the circuit breakers can basically be installed together without a clearance in between, be sure to observe the following instructions. It is desirable to install an insulation barrier between the adjacent circuit breakers or insulate the bare-live parts considering the effect of cutoff gas. Be sure to secure the insulation distance (dimension a) as the minimum, indispensable requirement. With a leakage circuit breaker and a leakage alarm circuit breaker installed in close contact with the other, a current of 2,500A or higher flowing through one of the circuit breakers could cause the other to operate falsely. Be sure to secure a distance of at least 50 mm in between. A circuit breaker of 400-ampere frame or larger with an SHT or a UVT could operate falsely if a current of 50 kA or higher flows through the adjacent circuit breaker. Be sure to secure a distance of at least 50 mm in between. D2
5
Side plate D1
a
Table 5-8 Insulation distance (mm) (440VAC or below) *Figures in parentheses are for 230VAC or below. Model Class • Series
C • S • H • R • MB
R • U BH
UL
MCCB
NF30-CS NF32-SV, NF63-CV NF63-SV, NF63-HV NF125-CV NF125-SV NF125-HV NF250-CV NF125-SEV, NF250-SV, NF250-SEV NF125-SGV, NF160-SGV, NF250-SGV NF125-HEV, NF250-HV, NF250-HEV NF125-LGV, NF160-LGV, NF250-LGV NF125-HGV, NF160-HGV, NF250-HGV NF400-CW NF400-SW, NF400-SEW NF400-HEW, NF400-REW NF630-SW, NF630-SEW, NF630-CW NF630-HEW, NF630-REW NF800-SEW, NF800-CEW NF800-HEW, NF800-REW NF1000-SEW, NF1250-SEW NF1600-SEW NF125-RGV, NF250-RGV NF125-UV, NF250-UV NF400-UEW NF800-UEW BH-K, BH-K100 NF225-CWU NF50-SVFU NF100-CVFU NF125-SVU(*4) NF125-HVU(*5) NF250-SVU(*4) NF250-HVU(*5) NF400-SWU, NF400-HWU(*5) NF630-SWU, NF630-HWU(*5)
Ceiling plate
ELCB
− NV63-CV NV32-SV, NV63-SV, NV63-HV NV125-CV NV125-SV NV125-HV NV250-CV
A Uncovered metal Plate Without With terminal terminal cover cover 10 10 5 5 10 10 50(30) 40(30) 50(10) 30(10) 50 40 40 40
Horizontal spacing
Vertical spacing B1, B2 C
Insulated plate, coated plate
Without terminal cover
With terminal cover
10 5 10 10 10 40 40
20 20 30 50 50 80 50
20 20 30 50 50 80 50
(*1) (*1) 30 (*1) 50 80 50
20 20 25 25 25 40 50
D1
NV125-SEV, NV250-SV, NV250-SEV
70(40)
40
40
70(50)
50
70(50)
50
NV125-HEV, NV250-HV, NV250-HEV
80
60
60
80
80
80
60
NV400-CW NV400-SW, NV400-SEW NV400-HEW, NV400-REW NV630-CW, NV630-SW, NV630-SEW NV630-HEW NV800-SEW NV800-HEW
60 70 200 70 200 80 200
60 70 200 70 200 80 200
60 70 200 70 200 80 200
60 70 200 70 200 80 200
60 70 200 70 200 80 200
60 70 200 70 200 80 200
40 70 150 70 150 80 150
100
100
100
100
100
100
50 (*1) 70 80 (*1) (50) 30 50 50 80 70(50) 80 70 70
5 25 70 80 20 (50) 10 25(15) 25(20) 25(20) 50(20) 50(20) 70 70
− − − − − − − − − − − − − − −
30 (*6) 30 (*6) (*1) (*1) 70 70 80 80 (*1) − (40) 10 (*6) 10 (*6) 50(25) 40(25) 40(10) 30(10) 40 40 40 40 40 40 70 70 70 70
100 30 (*6) (*1) 70 80 (*1) (40) 10 (*6) 10 10 40 40 40 70 70
50 (*9) 50 (*9) (*1) (*1) 70 70 80 80 (*1) − (50) 20 (*7) 20 (*7) 50 50 50 50 80 80 50 70(50) 80 80 70 70 70 70
Remark: 1. The table shows the dimensions in the case of the use of a large terminal cover (TC-L). Notes *1 It is not necessary to provide an insulation distance (an arc space) on the power supply side. However, if a grounding metal piece or the like comes in close contact with the terminal, be sure to completely insulate the terminals or the bare-live parts of the cable conductors. *2 At more than 440 V AC, the distance shall be 10 mm. *3 For 480Y/277V AC. *4 For 480V AC. *5 For 600Y/347V AC. *6 An exhaust port is provided also on the circuit breaker load side. Secure the dimension A both on the power supply side and on the load side. *7 When any of the circuit breakers NF125-RGB to NF250-RGV is used on the upstream side, an exhaust port is provided also on the circuit breaker load side. Secure the larger distance of the dimension B1 of NF125-RGV, NF250-RGV or NF50-SVFU and the dimension B1 of the downstream circuit breaker.
99
1 Installation and Connection
B2
B1
B1
C
A
Ceiling plate
5
Installation and Connection
1
Installation and Connection
7. Effect of Installation Orientation Installation orientation does not affect the operating characteristics of circuit breakers of electronic or thermomagnetic operation types. However, the installation orientation affects the operating current of fully magnetic type circuit breakers as the iron core in the oil dash pot is under gravitational force. It is generally suggested they be installed vertically. Hydraulic-magnetic (The same applies to other models of hydraulic-magnetic type.) MCCB Class C
100%
Model
107%
NF30-CS
93% ON
ON ON
ON 110%
90%
ON
ON ON
ON 93%
107% 100%
Rate of change of rated current by mounting angle
8. Connection of Line and Load
1 Installation and Connection
5
The standard wiring of line and load on the circuit breaker is as shown in (a) normal connection on the right. Avoid the wiring shown in (b) reverse connection. This may lead to a decrease in breaking performance. However, the reverse connection is allowed for the following models (excluding MDU breakers). NF-C, NF-S, NF-H, NF-R and NF-U class BH-P, CP30-BA, NV-C, S, H and R class of 400 to 800AF, NF100-CVFU, NF125-SVU, NF125-HVU, NF250-SVU, NF250-HVU
100
Reverse connection is allowed for the standard models.
Line
Load
ON
ON
Load (a) Normal connection
Line (b) Reserve connection
Connection methods
Accessories 1 Internal Accessories
6 102
1) Internal Accessories … …………………………………………………………………………………………………………………………… 102 2) Kinds of Internal Accessories ……………………………………………………………………………………………………………………… 103 3) Operations and Ratings of Switches ……………………………………………………………………………………………………………… 103 4) Maximum Number of Internal Accessories … …………………………………………………………………………………………………… 104 5) Cassette Type Accessories … …………………………………………………………………………………………………………………… 109 6) Shunt Trip (SHT) … ………………………………………………………………………………………………………………………………… 111 7) Undervoltage Trip (UVT) …………………………………………………………………………………………………………………………… 112 8) Lead Wire Drawing … ……………………………………………………………………………………………………………………………… 114 9) Lead Wire Terminal Block … ……………………………………………………………………………………………………………………… 114 10) Test Button Module (TBM) … …………………………………………………………………………………………………………………… 115 11) Pre-Alarm Module (PAL) … ……………………………………………………………………………………………………………………… 116
2 External Accessories
117
1) F-type Operating Handle (Breaker Mount Type)… ……………………………………………………………………………………………… 2) V-type Operating Handle (Door Mount Type)… ………………………………………………………………………………………………… 3) Terminal Covers… ………………………………………………………………………………………………………………………………… 4) Insulating Barriers………………………………………………………………………………………………………………………………… 5) Handle Lock Devices, Lock Covers, Auxiliary Handles, Card Holders………………………………………………………………………… 6) Mechanical Interlocks (MI)… ……………………………………………………………………………………………………………………… 7) Boxes for Circuit Breakers and Boxed Circuit Breakers………………………………………………………………………………………… 8) Electrical Operated Circuit Breakers and Electrical Operation Devices… …………………………………………………………………… 9) Distribution Board Mounting Parts, Lock Covers and Handle Caps… ………………………………………………………………………… 10) IEC 35-mm Rail Mounting Adapters… …………………………………………………………………………………………………………
117 119 121 124 127 129 130 133 136 137
101
6 Accessories
Internal Accessories
1
1. Internal Accessories The accessories to be installed in circuit breakers include the followings. For the numbers of the accessories which can be installed, refer to the tables on pages 106 to 110. The standard internal accessories have lead wires (450 mm long) drawn out. (However, some of Models UVT and TBM have vertical lead wire terminal blocks as standard.) When circuit breakers are installed side by side, keep a space of 8 mm or more for lead wires between the circuit breakers. (Models with lead wires drawn out toward load and models with lead wire grooves in the side faces can be installed in close contact.)
SHT (Shunt trip)
Device to electrically trip a circuit breaker from a distance. The allowable operating voltage range is 70 to 110% of the rated voltage. (JIS C 8201-2-1 Ann.1, Ann.2)
Power supply
Switch to electrically display the tripping status of circuit breaker
ALc
ALb
Control power supply
ALa PL
Load
Connection diagram
Small-size MCCB or fuse
AX (Auxiliary switch)
Power supply S1
Switch to electrically display the ON-OFF status of circuit breaker
S2
Load
AL (Alarm switch)
Pushbutton switch
Connection diagram
Power supply
AXc Control power supply
AXa AXb PL1 Load
PL2
Connection diagram
1 Accessories
6
TBM (Test button module) UVT (Undervoltage trip)
SLT (Lead wire terminal block)
Device to automatically trip a circuit breaker when the voltage drops. The operating voltage is 70 to 35% of the UVT rated voltage. (JIS C 8201-2-1 Ann.1) When the voltage recovers at least to 85% or more, the circuit breaker can be turned on after the device is manually reset.
Terminals for connecting with internal accessories. The terminal block will be manufactured to order. For the detailed dimensions, refer to pages 116 and 117. (The dimensions of SLT slightly vary depending on the number of installed accessories and the model.) However, circuit breakers with a frame size of 400A and above having an electrical operation device are normally provided with SLT.
Power supply
UC1 UC2
Connection diagram
102
Load
Unit to perform test under voltage from a distance. TBMs can be connected in parallel. (The standard TBMs are provided with SLT. In the case of the flush plate type, the external dimensions are partially different from those of the standard type.) Circuit breaker TBM TBM2 switch Control power supply TBM1
TBM circuit diagram
6 Accessories 1 Internal Accessories
2. Kinds of Internal Accessories Table 6-1 Accessory name
AL
Alarm switch
AX
Auxiliary switch
SHT
Shunt tripping device
UVT
Undervoltage tripping device
Nameplate (sample)
Accessory name
EAL
Earth leakage trip alarm switch
TBM
Test button module
Nameplate (sample)
3. Operations and Ratings of Switches Table 6-4 Ratings of AL and AX switches
Table 6-2 Operations of AL switch Status of circuit breaker
Contact status of AL switch
Off or On
98/ALa (open) 96/ALb (closed) 95/ALc
Trip
98/ALa (closed) 96/ALb (open) 95/ALc
* The terminal numbers 98/ALa, 96/ALb and 95/ALc may vary depending on the number of installed switches and the installation poles.
A S
V
Voltage V (250) 125 460 250 125 460 250 125
AC Current A Resistive Inductive load load (0.5) (1) (1) 3 — — 2 3 3 5 2 5 10 10 10 10
Voltage V (50) 30 250 125 30 250 125 30
DC Current A Resistive Inductive load load (0.5) (1) (1) (2) 0.2 0.2 0.4 0.4 3 4 0.3 0.3 0.6 0.6 6 10
Remarks: 1. The ratings in parentheses do not conform to UL. 2. For the applied switches, refer to Tables 6-9-1 to 6-14-1.
Table 6-3 Operations of AX switch Status of circuit breaker
Applied switch
Contact status of AX switch
Off or Trip
14/AXa (open) 12/AXb (closed) 11/AXc
On
14/AXa (closed) 12/AXb (open) 11/AXc
* The terminal numbers 14/AXa, 12/AXb and 11/AXc may vary depending on the number of installed switches and the installation poles.
1 Accessories
6
103
6 Accessories
Internal Accessories
1
4. Maximum Number of Internal Accessories AL
JMCCB J and Motor Protection Breakers Table 6-5 Table of maximum number of internal accessories Left pole C
NF30-CS
L • H • R
NF32-SV NF63-SV NF125-SV
NF32-SV NF63-SV NF125-SV NF125-SGV NF160-SGV NF250-SV NF250-SGV
NF63-HV
NF63-HV NF125-HV NF125-LGV NF125-HGV NF125-RGV NF160-LGV NF160-HGV NF250-HV NF250-LGV NF250-HGV NF250-RGV
U ber of p ole A L s (sta and nda rd) AX swit che s Accessory
are cassette type accessories. (Some of UVT are not provided with cassettes. Refer to page XXX for details.)
NF400-CW NF630-CW
NF800-CEW
NF125-SEV NF250-SEV
NF400-SW NF400-SEW NF630-SW NF630-SEW
NF800-SEW NF800-SDW
NF125-HEV NF250-HEV
NF400-HEW NF400-REW NF630-HEW NF630-REW
NF800-HEW NF800-REW
NF400-UEW(3P)
NF400-UEW(4P) NF800-UEW
2, 3 or 4 poles
2, 3 or 4 poles
NF125-UV NF250-UV 2 or 3 poles
2 poles
Outgoing direction of lead wires
PAL
Right pole
NF63-CV NF125-CV NF250-CV
Num
SHT or UVT
Handle of circuit breaker
NF63-CV NF125-CV
Model
S
AX
2, 3 or 4 poles
3, 4 poles
V
(*3)
(*7)
1
2
1
2
(*3)
AX
(*7)
1
1
2
3
(*1)
2
(*1)(*5)
1
2
3
1
3
1 5
3
2
4
2 6
4
(*1)(*5)
(*1) (*6)
(*1) (*6)
(*7)
(*7)
(*1)
(*1) (*6) (*7) (*8)
(*1) (*6) (*7) (*8)
(*1)
(*1) (*6) (*7) (*8)
SHT or UVT (*3)
1 Accessories
2, 3 or 4 poles
S
AL
6
NF1000-SEW NF1250-SEW NF1600-SEW
AL + AX
(*2)
(*2)
1
2
1
2
1
2
1
2
1 2 5
3 4 6
(*1)
3-pole product only
(*1)
SHT AL + or UVT
SHT AX + or UVT
SHT AL + AX + or UVT
PAL (contact output) Notes *1 *2 *3 *4 *5 *6 *7 *8 *9 Remarks:
104
(*1)
1
1
2
2
(*1)
3
1 2
1 3 2 4
5
3
1
4
2
(*1) (*6) (*7) (*8)
(*1)
(*1) (*6) (*7) (*8)
(*1) (*6) (*7) (*8)
(*4)
(*9)
(*9)
Option for NF400-SEW, HEW, REW and UEW and NF630-SEW, HEW and REW
Option for NF800-CEW, SEW, HEW and REW and NF800-UEW
(*1)
(*1)
(*1)
(*9)
Option for NF1000-SEW and NF1250-SEW and NF1600-SEW
When UVT is provided, the UVT voltage module will come in the vertical lead wire terminal block type. (SHT does not have a voltage module.) The second AX can be installed in place of the AL on the left pole side. When placing an order, specify the incorporation of the switches in the body. Although the lead wires are normally drawn out laterally, those with lead wires drawn out toward load are available. (Only for front connection type) PAL (contact output) can be installed together with AL and AX on the left pole side. (It cannot be installed together with SHT or UVT.) The standard type is provided with SLT. PAL control voltage (compatible with 100 to 200 V AC) is necessary. SHT and UVT can be installed on the left side. SHT and UVT are normally installed on the right pole side. If you intend to install them on the left pole side, specify so. (The reset preventing UVT must be installed on the left pole side.) In the case where three or more accessories are installed on the left pole side and AL, AX or AL and AX are installed on the pole on which SLT, SHT or UVT is installed, the SLT will be manufactured to order. When AL, AX or AL and AX are installed on the pole on which UVT is installed, the UVT voltage module must be installed separately. SLT is provided as standard. A control power supply (100 to 200 V AC) is required. (In this case, other internal accessories cannot be installed on the right pole side.) 1. For electrically operated automatic reset type circuit breakers having a frame size of 400A or above, the numbers of AL switches which can be installed are smaller by 1 than the values shown above. 2. The encircled numbers indicate the order of installation.
6 Accessories 1 Internal Accessories
JELCB J
AL
Table 6-6 Table of maximum number of internal accessories Left pole C
Model
S
H • R
U er o f po les Sw itch
AX
SHT or UVT TBM
Handle of circuit breaker Right pole
Outgoing direction of lead wires
are cassette type accessories.
NV63-CV NV125-CV NV250-CV
NV400-CW NV630-CW
NV32-SV NV63-SV NV125-SV NV125-SEV NV250-SV NV250-SEV
NV400-SW NV400-SEW NV630-SW NV630-SEW
NV800-SEW
NV63-HV NV125-HV NV125-HEV NV250-HV NV250-HEV
NV400-HEW NV400-REW NV630-HEW
NV800-HEW
Num b
3 poles
2, 3, or 4 poles S
Accessory
(*6)
AL
AX
(*6)
1 2 (*2)
(*6)
(*6)
(*3)
(*5)
(*5)
SHT AL + or UVT
(*4) (*5) (*6)
(*4) (*5) (*6)
SHT AX + or UVT
(*4) (*5) (*6)
(*4) (*5) (*6)
SHT AL + AX + or UVT
(*4) (*5) (*6)
(*4) (*5) (*6)
AL + AX SHT or UVT
(*1)
(*1)
6
(*1)
Notes *1 *2 *3 *4 *5 *6 Remarks:
1 Accessories
TBM The standard type is provided with SLT. Only in the case of 24 V DC, specify the control voltage. The second AX can be installed in place of the AL on the left pole side. When placing an order, specify the incorporation of the switches in the body. When UVT is provided, the UVT voltage module will come in the vertical lead wire terminal block type. (SHT does not have a voltage module.) When AL, AX or AL and AX are installed on the pole on which UVT is installed, the UVF voltage module must be separately installed. When the accessory is provided with UVT, the UVT voltage module has a vertical lead wire terminal block. The UVT is not provided with a cassette. SLT to be used when three or more accessories are installed on the left pole is manufactured to order. 1. The encircled numbers indicate the order of installation. 2. TBM can be installed regardless of the number of installed AL, AX, SHT and UVT.
105
6 Accessories
1
Internal Accessories
JUL J 489 Listed Circuit Breakers
Model
Table 6-7 Table of maximum number of internal accessories MCCB
NF50-SVFU NF100-CVFU
NF50-SVFU NF100-CVFU
Handle of circuit breaker
Left pole
NF125-SVU NF125-HVU NF250-SVU NF250-HVU
AL
AX
Right pole
NF225-CWU
2 poles
3 poles
2 or 3 poles
3 poles
TBM
Outgoing direction of lead wires
are cassette type accessories.
NF400-SWU NF400-HWU
NF630-SWU NF630-HWU
Nu
mb ELCB er o fp (sta AL an oles nda d A X rd) swi tche s Accessory
SHT or UVT
3 poles
3 poles
NV50-SVFU
NV50-SVFU NV100-CVFU
NV125-SVU NV125-HVU NV250-SVU NV250-HVU
2 poles
3 poles
3 poles
S (*4)
AL
1
2
1
2
1
2
(*4)
AX
1
1
2
3
(*1) (*6)
2
(*1) (*3) (*6)
1
2
3
1
(*1) (*3)
2
(*1)
1
3
1 5
3
1
1
2
4
2 6
4
2
2
(*1) (*3)
(*1) (*3)
(*1) (*6)
(*1)
(*6)
(*6)
(*2)
(*2)
SHT or UVT (*2)
AL + AX
(*2)
1
2
1
2
1
2
1
2
1
2
1
2
(*1) (*6)
(*1)
(*1)
(*1) (*3) (*4) (*5)
(*1) (*3) (*4) (*5)
(*1)
(*1)
(*1) (*3) (*4) (*5)
(*1) (*3) (*4) (*5)
SHT AL + or UVT (*1) (*6)
SHT AX + or UVT
1
1
2
2
6
2 4 3
(*1) (*6)
SHT AL + AX + or UVT
1 3
(*1)
(*1)
5
1
3
1
2
4
2
(*1)(*3) (*4)(*5)
(*1)(*3) (*4)(*5)
(*7)
(*7)
1 Accessories
TBM Notes *1 *2 *3 *4 *5 *6 *7 Remarks:
106
When UVT is provided, the UVT voltage module will come in the vertical lead wire terminal block type. (SHT does not have a voltage module.) SHT cannot be installed. SHT and UVT are normally installed on the right pole side. If you intend to install them on the left pole side, specify so. In the case where three or more accessories are installed on the left pole side and AL, AX or AL and AX are installed on the pole on which SLT, SHT or UVT is installed, the SLT will be manufactured to order. When AL, AX or AL and AX are installed on the pole on which UVT is installed, the UVT voltage module must be installed separately. UVT of NF50-SVFU and NV50-SVFU are not provided with cassettes. The standard type is provided with SLT. Only in the case of 24 V DC, specify the control voltage. 1. The encircled numbers indicate the order of installation. 2. AL and AX for minute load can be manufactured to order. (These switches have been certified only by UL and CSA. They have not been certified by TUV.)
(*7)
6 Accessories 1 Internal Accessories
JMDU J Breakers
AL
Table 6-8-1 Table of maximum number of internal accessories
Num ber
AX for transmission with MDU
TI
Outgoing direction of lead wires
NF600-SEP with MDU NF600-HEP with MDU NF800-SEP with MDU NF800-HEP with MDU 3 or 4 poles S (*1)
AL AX
SHT or UVT
are cassette type accessories.
Right pole
NF400-SEP with MDU NF400-HEP with MDU
o f po les swit ch Accessory
AL for transmission with MDU
PAL
Handle of circuit breaker
Left pole
Model
AX
1
3
15
3
2
4
26
4
(*1)
(*2)
(*2)
(*3) (*4)
(*3) (*4)
(*1)
(*1)
(*1) (*2)
(*1) (*2)
SHT
AL + AX
AL + SHT
AX + SHT
(*1) (*2) 3
1 2
5
3 4
1 2
AL + UVT
(*1) (*3) (*4) (*5)
AX + UVT
(*1) (*3) (*4) (*5)
3
1 2
(*1) (*3) (*4) (*5)
(*1) (*2)
(*1) (*2)
(*1) (*2)
AL + AX + SHT
AL + AX + UVT
13 24
(*1) (*3) (*4) (*5)
13 24
5
3 4
1 2
(*1) (*3) (*4) (*5) (*1) (*3) (*4) (*5)
(*6)
(*6)
(*6)
(*6)
6
PAL EPAL TI With contact outputs for PAL and OAL
With contact outputs for PAL and OAL
Notes *1 In the case where three or more accessories are installed on the left pole side and AL, AX or AL and AX are installed on the pole on which SLT, SHT or UVT is installed, the SLT will be manufactured to order. *2 SHT and UVT are normally installed on the right pole side. If you intend to install them on the left pole side, specify so. (The reset preventing UVT must be installed on the left pole side.) *3 The UVT voltage module is installed externally. UTV is not provided with a cassette. *4 UVT is normally installed on the right pole. If you intend to install it on the left pole, specify so. *5 When AL, AX or AL and AX are installed on the pole on which UVT is installed, the UVT voltage module must be installed separately. *6 The standard model has a terminal block. A 5-VA control power supply (compatible with 100 to 240 V AC/DC) is required. (In this case, another internal accessory cannot be installed on the right pole.) Remark: 1. The encircled numbers indicate the order of installation.
107
1 Accessories
UVT
6 Accessories
Internal Accessories
1
JMDU J Breakers
AL
Table 6-8-2 Table of maximum number of internal accessories Left pole
Model
Num ber
o f po les swit ch Accessory AL for transmission with MDU (*1) AX for transmission with MDU (*1) AL + AX for transmission with MDU (*1) AL + AX + AL for transmission with MDU (*1) AL+AX + AX for transmission with MDU (*1) AL + AX + AL + AX for transmission with MDU (*1) Note
AL for transmission with MDU
Handle of circuit breaker
AX for transmission with MDU PAL
SHT or UVT
TI
Outgoing direction of lead wires
are cassette type accessories.
Right pole
NF600-SEP with MDU NF400-SEP with MDU NF600-HEP with MDU NF400-HEP with MDU NF800-SEP with MDU NF800-HEP with MDU 3 or 4 poles S
*1 To transmit signals from AL, AX or AL and AX, AL and/or AX for transmission with the MDU are installed on the left pole side. In this case, the lead wires of AL and/or AX for transmission with the MDU installed on the left pole side cannot be drawn out to the outside or fitted to the terminal block.
AL Handle of circuit breaker Left pole
Num ber
Model
o f po les switc h
6
2
AX
1 2
3
AL + AX
1 1
2 2
AX + SHT AL + AX + SHT AL + UVT AX + UVT AL + AX + UVT
AX for transmission with MDU PAL
SHT or UVT Outgoing direction of lead wires
are cassette type accessories.
S 1
AL + SHT
AL for transmission with MDU
3 or 4 poles
AL
SHT or UVT
Right pole
AX
NF250-SEV with MDU NF250-HEV with MDU
Accessory
1 Accessories
AX
(*1)
(*2)
(*2)
(*2)
(*2)
(*2)
(*2)
(*2)
AL for transmission with MDU (*3) AL for transmission with MDU AX (*3) AL for transmission with MDU AL + AX (*3) AL for transmission with MDU AL + AX + AL (*3) AL for transmission with MDU AL + AX + AX (*3) AL for transmission with MDU AL + AX + AL + AX (*3) Notes *1 The second AX can be installed in place of the AL on the left pole side. When placing an order, specify the incorporation of the switches in the body. *2 When UVT is provided, the UVT voltage module will come in the vertical lead wire terminal block type. (SHT does not have a voltage module.) *3 To transmit signals from AL, AX or AL and AX, AL and/or AX for transmission with the MDU are installed on the left pole side. In this case, the lead wires of AL and/or AX for transmission with the MDU installed on the left pole side cannot be drawn out to the outside or fitted to the terminal block. In the case of 225A frame circuit breakers, AL for transmission with the MDU must be installed for fault current measurement. Remark: 1. The encircled numbers indicate the order of installation.
108
6 Accessories 1 Internal Accessories
5. Cassette Type Accessories The internal accessories for major models having a frame size from 30 to 800 A come in cassettes, and they can be installed to and removed from circuit breakers by the user. Some cassette type accessories have lead wires drawn out, and others have vertical lead wire terminal blocks (SLT). (These parts are supplied by 10 pieces for frame size from 30 to 250 A or by 1 piece for frame size from 400 to 800 A.)
JApplicable J models and kinds of cassette type accessories Model
MCCB
ELCB
Alarm switch (AL)
Auxiliary switch (AX) Shunt tripping device (SHT) Undervoltage tripping device (UVT)
NF63-CV~NF250-CV, NF32-SV~NF250-SV NF63-HV~NF250-HV NF125-SGV~NF250-SGV, NF125-LGV~NF250-LGV NF125-HGV~NF250-HGV NF125-SEV, NF250-SEV, NF125-HEV, NF250-HEV NF125-RGV, NF250-RGV, NF125-UV, NF250-UV NF100-CVFU, NF125-SVU/HVU, NF250-SVU/HVU
NF50-SVFU, NF400-CW, NF630-CW, NF800-CEW NF400-SW, NF630-SW, NF400-SEW~NF800-SEW NF800-SDW, NF400-HEW~NF800-HEW NF400-REW~NF800-REW, NF400-UEW, NF800-UEW NF400-SWU/HWU, NF630-SWU/HWU
–
NV63-CV~NV250-CV, NV32-SV~NV250-SV NV63-HV~HV250-HV NV125-SEV, NV250-SEV, NV125-HEV, NV250-HEV NV100-CVFU, NV125-SVU/HVU, NV250-SVU/HVU
NV50-SVFU, NV400-CW, NV630-CW NV400-SW, NV630-SW, NV400-SEW~NV800-SEW NV400-HEW~NV800-HEW, NV400-REW
–
JProcedure J for installing cassette type accessories
1. Press the trip button (PTT) to trip the circuit breaker. (*1)
2. Loosen the cover screws.
3. Open the cover.
4. Install the cassette type accessory. (*2)
5. Close the cover, and tighten the screws.
Notes *1. When installing any cassette type accessory, set the circuit breaker to the tripped state. *2. If the inner lid or another accessory has been installed, remove it before installing the accessory. When any circuit breaker supplied with the inner lid is used without an accessory, fit the inner lid without fail. Failure to do so may affect the short-circuiting performance. Models with inner lid: NF125-SV, NF125-HV, NF125-UV NF250-SEV, NF250-HEV, NF250-UV NV125-SV, NV125-HV NV250-HEV NF250-SV, NF250-HV NF125-SEV, NF125-HEV NV250-SV, NV250-HV NV125-SEV, NV125-HEV NF125-SVU, NF125-HVU, NV125-SVU, NV125-HVU NF400-REW, NF400-UEW NF250-SVU, NF250-HVU, NV250-SVU, NV250-HVU NF630-REW, NV400-REW NF800-HEW, NF800-REW, NF800-UEW NV800-HEW NF630-SWU, NF630-HWU
Cautions when installing
Before installing or removing any cassette type accessory, set the circuit breaker and accessories to the no-voltage state. Never install a cassette type accessory while the handle is in the ON or OFF position. Doing so may damage the accessory. When installing an accessory with lead wires drawn out, apply the supplied nameplate to the circuit breaker side face. When installing an accessory with lead wires drawn out for a frame size of 400 to 800 A, secure the lead wires along the circuit breaker side face with the supplied lead wire retainers.
109
1 Accessories
6
6 Accessories
Internal Accessories
1
JType J name Table 6-9-1 Model
MCCB
Installation pole
ELCB
AL
AX
AL+AX
SHT
UVTN or UVTS
SHTA240-03SVUR SHTA440-03SVUR AL-03SVU AX-03SVU ALAX-03SVU SHTD100-03SVUR For right pole AL-03SVURS AX-03SVURS ALAX-03SVURS SHTA240-03SVURS SHTA440-03SVURS SHTD100-03SVURS
NF50-SVFU
–
For left pole
SHTA240-03SVUL SHTA440-03SVUL AL-03SVU AX-03SVU ALAX-03SVU SHTD100-03SVUL For left AL-03SVULS AX-03SVULS ALAX-03SVULS SHTA240-03SVULS pole SHTA440-03SVULS SHTD100-03SVULS
NV50-SVFU
NF32-SV, NF63-CV, NF63-SV, NF63-HV NF125-CV, NF125-SV, NF125-HV NF125-SGV, NF125-LGV, NF125-HGV NF160-SGV, NF160-LGV, NF160-HGV NF125-SEV, NF125-HEV NF125-RGV, NF125-UV NF250-CV, NF250-SV, NF250-HV NF250-SGV, NF250-LGV, NF250-HGV NF250-SEV, NF250-HEV NF250-RGV, NF250-UV
SHTA240-05SVR SHTA550-05SVR SHTD125-05SVR SHTA240-05SVRS SHTA550-05SVRS SHTD125-05SVRS
UVTNAD130-05SVR UVTNA250-05SVR UVTNA480-05SVR UVTNAD130-05SVRS UVTNA250-05SVRS UVTNA480-05SVRS
UVTSAD130-05SVR UVTSA250-05SVR UVTSA480-05SVR UVTSAD130-05SVRS UVTSA250-05SVRS UVTSA480-05SVRS
SHTA240-05SVL SHTA550-05SVL SHTD125-05SVL SHTA240-05SVLS SHTA550-05SVLS SHTD125-05SVLS
UVTNAD130-05SVL UVTNA250-05SVL UVTNA480-05SVL UVTNAD130-05SVLS UVTNA250-05SVLS UVTNA480-05SVLS
UVTSAD130-05SVL UVTSA250-05SVL UVTSA480-05SVL UVTSAD130-05SVLS UVTSA250-05SVLS UVTSA480-05SVLS
SHTA240-05SVUR SHTA550-05SVUR SHTD125-05SVUR For right AL-05SVU AX-05SVU ALAX-05SVU pole AL-05SVURS AX-05SVURS ALAX-05SVURS SHTA240-05SVURS SHTA550-05SVURS SHTD125-05SVURS
UVTNAD130-05SVUR UVTNA250-05SVUR UVTNA480-05SVUR UVTNAD130-05SVURS UVTNA250-05SVURS UVTNA480-05SVURS
UVTSAD130-05SVUR UVTSA250-05SVUR UVTSA480-05SVUR UVTSAD130-05SVURS UVTSA250-05SVURS UVTSA480-05SVURS
For left pole
UVTNAD130-05SVUL UVTNA250-05SVUL UVTNA480-05SVUL UVTNAD130-05SVULS UVTNA250-05SVULS UVTNA480-05SVULS
UVTSAD130-05SVUL UVTSA250-05SVUL UVTSA480-05SVUL UVTSAD130-05SVULS UVTSA250-05SVULS UVTSA480-05SVULS
AL-05SV AX-05SV ALAX-05SV For right AL-05SVRS AX-05SVRS ALAX-05SVRS pole
For left pole NV32-SV, NV63-CV NV63-SV, NV63-HV NV125-CV, NV125-SV NV125-HV NV125-SEV, NV125-HEV NV250-CV, NV250-SV NV250-HV NV250-SEV, NV250-HEV
NF100-CVFU NF125-SVU/HVU NF250-SVU/HVU
AL-05SV For left AL-05SVLS pole
For right pole (2, or 3 poles)
NF400-CW, NF400-SW, NF400-SEW NF400-HEW, NF400-REW, NF400-UEW NF630-CW, NF630-SW, NF630-SEW NF630-HEW, NF630-REW NF800-CEW, NF800-SDW, NF800-SEW NF800-HEW, NF800-REW, NF800-UEW
1 Accessories
AX-05SV ALAX-05SV AX-05SVLS ALAX-05SVLS
SHTA240-05SVUL SHTA550-05SVUL AL-05SVU AX-05SVU ALAX-05SVU SHTD125-05SVUL For left AL-05SVULS AX-05SVULS ALAX-05SVULS SHTA240-05SVULS pole SHTA550-05SVULS SHTD125-05SVULS
NV100-CVFU NV125-SVU/HVU NV250-SVU/HVU
For right pole (4 poles) For left pole (2, 3 or 4 poles)
–
AX-4SW AX-4SWRS AX2-4SWRS
–
SHT-4SW SHT-4SWRS
–
–
–
–
SHT-4SWRFS SHT-8SWRFS
–
SHT-4SW SHT-4SWLS
–
SHT-4SWU SHT-4SWURS
–
NV400-CW, NV400-SW AL-4SWL AX-4SW ALAX-4SWL NV400-SEW, NV400-HEW AL-4SWLS AX-4SWLS NV400-REW For left pole AL2-4SWLS AX2-4SWLS ALAX-4SWLS NV630-CW, NV630-SW (2, 3 or 4 poles) NV630-SEW, NV630-HEW NV800-SEW, NV800-HEW
6
For right pole
NF400-SWU, NF400-HWU NF630-SWU, NF630-HWU Remarks: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12.
–
–
AX-4SWU AX-4SWURS AX2-4SWURS
–
For left pole AL-4SWUL AX-4SWUL ALAX-4SWUL SHT-4SWU For the possibility of installation of accessories and the installation pole, refer to the tables of maximum numbers on pages 106 to 110. AL and AX for minute load can be manufactured to order. Corrosion-proof cassette type AL and AX are not available. When the circuit breaker body is exposed to class 1 tropicalization, class 2 tropicalization, reinforced corrosion resistance treatment or class 2 heat resistance treatment, place an order for the circuit breaker including the accessories. Cassette type accessories with SLT for right pole cannot be installed to 4-pole circuit breakers. Accessories with SLT for right pole to be used in 4-pole circuit breakers are manufactured to order. Cassette type accessories with SLT cannot be installed to flush plate type circuit breakers. Cassette type accessories (AL, AX and SHT) cannot be installed to circuit breakers with MG. It is impossible to install a combination of a cassette type accessory with lead wires drawn out and that with SLT or a combination of cassette type accessories with SLT on the same pole. It is impossible to install the cassette type AL or AX to the pole to which UVT has been installed. AX and SHT with lead wires drawn out for frame size from 400 to 800 A can be installed to any of the right and left poles. When installing more than one AL or AX with lead wires drawn out for frame size from 400 to 800 A to one side, install the necessary number of the accessories for one piece. The lead wires from the circuit breaker vary in length depending on the installation position. Install the cassette accessories for frame size from 400 to 800 A starting from the outside of the installation positions. For the installation positions, see the installation positions shown in the following table. When three pieces of more of AL and AX are installed on a circuit breaker with a frame size 400 to 800 A, the AL and AX with SLT are manufactured to order.
Installation positions of cassette type accessories for 400 to 800 A frames Table 6-9-2 Installation positions of cassette type accessories
Installation positions
Frame (A)
L1 L2 L3 L4
R4 R3 R2 R1 OFF
400 • 600 • 630
800
Installation positions
L1
L2
L3
R2
R1
L1
L2
L3
L4
R4
R3
R2
AL
–
–
–
–
–
–
–
–
AX
–
–
–
(*1)
AL + AX
–
–
–
–
–
–
–
–
–
SHT
–
–
–
–
–
Accessory
ON
(*1)
* Accessories only for Earth Leakage Circuit Breakers (NV-C, S and H), Earth Leakage Alarm Breakers (NF-Z) and single-phase 3-wire circuits (NF-N and NV-N) cannot be installed to R1, R2, R3 or R4. Note *1 It is impossible to simultaneously install AX on R2 and SHT on R3 or R4.
110
R1
6 Accessories 1 Internal Accessories
Interpretation of type name (1) Alarm switch • Auxiliary switch AL Kind of accessory AL Alarm switch AX Auxiliary switch
2
SV (or SW)
4
Number of accessories to be installed When installing more than one AL or AX with SLT, specify the number.
L
Ampere frame For 30 to 250A frames For 400 to 800A frames
05 4
S
B
Installation position R Right pole, 2 or 3 poles Right pole, 4 poles RF Left pole L Right and left Blank
Blank B
With SLT (vertical lead wire terminal block) (with lead wires drawn out unless otherwise specified)
(2) Shunt tripping device Undervoltage tripping device SHT Kind of accessory Shunt tripping device SHT Undervoltage UVTN (*1) tripping device UVTS (*2)
A240 A440 A480 A550 D100 D125 Blank
A1
SV (or SW)
1
Voltage (SHT)
05 4
AC100-240V AC380-440V AC380-480V AC380-550V DC100V DC100-125V AC100-450/DC100-200V
8
Voltage (UVTN or UVTS) AD130 Switching between 100 to 130 V AC and 100 to 130 V DC A250 AC200-250V A480 AC380-480V
R
Ampere frame For 30 to 250A frames For 400•600•630A frames For 800A frames (3P) For 800A frames (4P)
Kind of switch Standard Minute load
S
Installation position R Right pole, 2 or 3 poles RF Right pole, 4 poles L Left pole Right and left Blank
With SLT (vertical lead wire terminal block) (with lead wires drawn out unless otherwise specified)
Notes *1 The circuit breaker cannot be reset if voltage is not applied to UVTN. (Non-reset type UVT) *2 The circuit breaker can be reset even if voltage is not applied to UVTS. (Reset type UVT)
6. Shunt Trip (SHT) JCoil J ratings (standard) Table 6-10-1
NF50-SVFU NV50-SVFU
AC100-240 380-440 DC100
NF32-SV, NF63-CV/SV/HV, NF125-SGV/LGV/HGV NF160-SGV/LGV/HGV, NF125-CV/SV/HV/SEV/HEV/RGV/UV NF250-CV/SV/HV/SEV/HEV/RGV/UV NF250-SGV/LGV/HGV NV32-SV, NV63-CV/SV/HV NV125-CV/SV/HV/SEV/HEV, NV250-CV/SV/HV/SEV/HEV NF100-CVFU, NF125-SVU/HVU, NF250-SVU/HVU NV100-CVFU, NV125-SVU/HVU, NV250-SVU/HVU
AC100-240 380-550 DC100-125
Operating time (*2) (ms)
60
50
120
AC100-240 380-480 DC100-125
Provided
NF225-CWU
Input (VA) (*1) DC AC
Voltage (V)
15 or less
60 100V 20
NF400-CW/SW/SEW/HEW/REW/UEW NF630-CW/SW/SEW/HEW/REW NF800-CEW/SDW/SEW/HEW/REW/UEW NV400-CW/SW/SEW/HEW/REW NV630-CW/SW/SEW/HEW NV800-SEW/HEW, NF400-SWU/HWU, NF630-SWU/HWU
Compatible with 100 to 450 V AC and 100 to 200 V DC
NF1000-SEW, NF1250-SEW/SDW NF1600-SEW/SDW
AC100-120 200-240 380-450 DC100
200V 50
100V
10
200V
35
5-15
380V 120 450V 170 200
70
7-15
300
100
15-25
6
Notes *1 Ensure that the voltage of the operating power supply for SHT is not dropped below the allowable operating voltage (70% of the rated minimum voltage value) by the input power. *2 The operating time is the time from when the rated voltage is applied to the shunt tripping device until the main contact of the circuit breaker starts opening. Remark: 1. The accessory is usable at 50 Hz and 60 Hz.
JCoil J ratings (list of available special voltage coils) Table 6-10-2 Model
VAC
Compatible with AC/DC
VDC
380- 440- 50024 25-27 24-48 48 50-55 60 440480 550 550 550 12
24 24-36 36 36-48 48
NF32-SV, NF63-CV/SV/HV NF125-CV/SV/HV/SEV/HEV/RGV/UV NF125-SGV/LGV/HGV, F160-SGV/LGV/HGV NF250-CV/SV/HV/SEV/HEV/RGV/UV NF250-SGV/LGV/HGV NV32-SV, NV63-CV/SV/HV NV125-CV/SV/HV/SEV/HEV NV250-CV/SV/HV/SEV/HEV NF100-CVFU, NF125-SVU/HVU, NF250-SVU/HVU NV100-CVFU, NV125-SVU/HVU, NV250-SVU/HVU
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
NF225-CWU
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
NF400-CW/SW/SEW/HEW/REW/UEW NF630-CW/SW/SEW/HEW/REW NF800-CEW/SDW/SEW/HEW/REW/UEW NV400-CW/SW/SEW/HEW/REW NV630-CW/SW/SEW/HEW NV800-SEW/HEW, NF400-SWU/HWU, NF630-SWU/HWU
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
−
NF1000-SEW, NF1250-SEW/SDW NF1600-SEW/SDW
−
−
−
−
−
−
−
−
−
−
−
−
−
60
220110 125 220 200250 250 24-48
111
1 Accessories
Provision of coil burnout preventing switch
Model
6 Accessories
1
Internal Accessories
7. Undervoltage Trip (UVT) (1) Specifications for UVT and coil ratings Table 6-11 Specification Model NF50-SVFU NV50-SVFU
–
NF32-SV, NF63-CV/SV/HV/HRV NF125-CV/SV/HV/RGV/SEV/HEV/UV NF125-SGV/LGV/HGV, NF160-SGV/LGV/HGV NF250-CV/SV/HV/RGV/SEV/HEV/UV NF250-SGV/LGV/HGV NV32-SV, NV63-CV/SV/HV NV125-CV/SV/HV/SEV/HEV NV250-CV/SV/HV/SEV/HEV NF100-CVFU, NF125-SVU/HVU, NF250-SVU/HVU NV100-CVFU, NV125-SVU/HVU, NV250-SVU/HVU NF400-CW/SW/SEW/HEW/REW/UEW NF630-CW/SW/SEW/HEW/REW NF800-CEW/SDW/SEW/HEW/REW/UEW NV400-CW/SW/SEW/HEW/REW NV630-CW/SW/SEW/HEW NV800-SEW/HEW
AC/DC100-130V AC200-250V AC380-480V
(*5)
NF1000-SEW, NF1250-SEW NF1600-SEW
NF400-SWU/HWU, NF630-SWU/HWU
(*4)
–
NF225-CWU
–
(*1)
Input Operating time (*2) (VA) (ms)
5
AC/DC24V AC/DC48V AC500-600V
(*3)
(*4)
Notes *1 *2 *3 *4 *5
Coil ratings Voltage (V) Standard voltage Special voltage AC/DC24V AC/DC48V
Reset type Non-reset type
30 or less
(*3)
Switching between 24/48 AC Switching between 500 to 550/600 AC Switching between 100 to 110 and 120 to 130 AC Switching between 24/48DC Switching between 200 to 220 and 230 to 250 AC Switching between 110/125DC Switching between 380 to 415 and 440 to 480 AC Switching between Switching between (*3) 100 and 110 DC 24/48 AC Switching between 24/48DC Switching between 110/125DC
5-30
5
5-35 5-30
30 or less
Some special voltage models vary in voltage range. The operating time is the time from when the undervoltage tripping device is set to the no-voltage state until the main contact starts opening. The accessory is usable at 50 Hz and 60 Hz. If UVT is turned on without excitation, the circuit breaker instantaneously opens and immediately trips. Only for installation on the left pole
(2) Reset type and non-reset type UVT
1 Accessories
6
JReset J type (Refer to Table 6-12.) The reset type UVT has a structure which does not trip a circuit breaker even if the UVT coil is not excited when the circuit breaker handle is in the OFF or reset position. Therefore, it keeps the circuit breaker in the reset state even if the coil is not excited when the breaker is reset electrically. When the coil in the unexcited state is turned on, the circuit breaker is normally tripped. However, the major contacts of some models of circuit breakers may instantaneously close, or, on circuit breakers with AX, the AX switches may instantaneously change over. For electrical interlock, use a non-reset type UVT. JNon-reset J type (Refer to Table 6-12.) When the UVT coil is not excited, the circuit breaker cannot be set to the off state even if the circuit breaker is tried to be reset from the tripped state. When the coil exciting voltage restores to the reference voltage or more, the circuit breaker can be reset to the off state.
(3) Time delay UVT l This type of UVT has a time delay in operation. l It can prevent operation upon occurrence of instantaneous power failure. Table 6-12 UVT module type name
U-05W
U-30W
112
Time delay
Voltage (V)
Standard voltage Special voltage AC24/48 AC100−120/200−240/380−450 AC380−450/460−550/600−690 Switching among AC220−250/380−450/460−550 (Compatible with 50 Hz and 60 Hz) 0.1, 0.3 and 0.5 s DC24/48 (Compatible with 50 Hz and 60 Hz) DC100−110 Switching among 0.5, 1 and 3 s
AC100−120/200−240/380−450 AC220−250/380−450/460−550 (Compatible with 50 Hz and 60 Hz)
−
6 Accessories 1 Internal Accessories
(4) Structure of UVT The UVT mechanical unit is installed in a circuit breaker, and the UVT voltage module is installed on the outside of the circuit breaker. When the voltage drops, the UVT voltage module detects the voltage drop, and the UVT mechanical unit trips the circuit breaker. The UVT voltage module has a vertical lead wire terminal block and is normally installed on the body. The external module will be manufactured to order. lOutline drawing D
7 11 Terminal cover fixing hole 3x10, tapping screw (to be prepared by user)
3
Terminal cover
44.5 56
24.5
f4.5
44.5 29.5 3.5
D
C
8.5
2
7.5
7.5
Fig. 2
Terminal screw M3.5 Tightening torque: 0.9 to 1.2 N·m
A
8
90
57
Fig. 1 8
1
Terminal screw M3.5 Tightening torque: 0.9 to 1.2 N·m
44.5 56
B
84 (Terminal cover)
90 4
3
f4.5 4
1
100 80
2
Terminal cover fixing hole 3x10, tapping screw 8.5 (to be prepared by user)
24.5 11 5
56 44.5 3.5 Terminal cover
A
f4.5
80 100
8.5
44.5 3.5
Terminal screw M3.5 Tightening torque: 0.9 to 1.2 N·m
C
7.5
84 (Terminal cover) 57
7.5
Terminal cover fixing hole 3x10, tapping screw (to be prepared by user)
24.5 10 5
56 44.5 3.5
Terminal cover f4.5
8.5
5
4
100
55
92.5 (Terminal cover)
12
100 5
4
110 90
1
2
90 110
92.5 (Terminal cover) 55 12
3
1
2 3
Terminal cover 44.5 56
24.5
Terminal cover fixing hole 3x10, tapping screw (to be prepared by user)
29.5
B
44.5
Terminal screw M3.5 Tightening torque: 0.9 to 1.2 N·m
Fig. 3
Short-circuit protecting device, such as fuse
Short-circuit protecting device, such as fuse Terminal symbols D1/P1 D2/P2 J1/UC1 J2/UC2
8
Fig. 4
lExamples of connection
1 2 3 4
8
Terminal symbols 1 2 3 4 5
Control power supply terminal (COM) Control power supply terminal (rated voltage) UVT coil connecting terminal UVT coil connecting terminal
Remarks: 1 When the UVT voltage module is installed on the body (standard), the UVT is supplied with J1/UC1 and J2/UC2 terminals connected with the UVT coil. 2 When the UVT is installed on the left pole side, the UVT module terminal positions are reversed (on the power supply and load sides). Carefully connect the terminals.
Examples of connection
Examples of connection
Fig. 5
Fig. 6
Table 6-13 Installation on right pole side Model NF50-SVFU NF32-SV, NF63-CV/SV/HV NF100-CVFU NF125-CV/SV/HV NF125-SVU/HVU NF125-UV NF125-SEV/HEV/RGV, NF250-CV/SV/HV/RGV/SEV/HEV NF125-SGV/LGV/HGV, NF160-SGV/LGV/HGV NF250-SGV/LGV/HGV NF250-SVU/HVU NF250-UV NF225-CWU NF400-CW/SW/SEW/HEW/REW NF630-CW/SW/SEW/HEW/REW, NF400-SWU/HWU NF400-UEW(3P) NF800-CEW/SDW/SEW/HEW/REW, NF630-SWU/HWU NF400-UEW(4P), NF800-UEW NF1000-SEW, NF1250-SEW, NF-1600-SEW
Reference drawing
Fig. 1 Fig. 5
Fig. 3 Fig. 6
D1/P1 D2/P2 D3/P3 J1/UC1 J2/UC2
Control power supply terminal (COM) Control power supply terminal (rated voltage Lo) Control power supply terminal (rated voltage Hi) UVT coil connecting terminal UVT coil connecting terminal
Remarks: 1 When the UVT is used at the rated voltage Lo, connect the control voltage to D1/P1 and D2/P2 terminals. When the UVT is used at the rated voltage Hi, connect the control voltage to D1/P1 and D3/P3 terminals. (Ex.) 100 to 110/120 to 130 V AC (Rated voltage Lo/rated voltage Hi) 2 When the UVT voltage module is installed on the body (standard), the UVT is supplied with J1/UC1 and J2/UC2 terminals connected with the UVT coil. 3 When the UVT is installed on the left pole side, the UVT module terminal positions are reversed (on the power supply and load sides). Carefully connect the terminals.
Table 6-14 Installation on left pole side Variable dimensions B A 7.5 11 7.5 20.5 7.5 20.5 7.5 20.5 7.5 41.5 7.5 81.5 38
7.5
48 113 25.5
7.5 7.5 7.5
67.5
41.5
107.5 76.5 123.5 161
138.5 41.5 138.5 63
Model NV125-CV/SV/HV NV125-SEV/HEV, NV250-CV/SV/HV/SEV/HEV NF400-CW/SW/SEW/HEW/REW NF630-CW/SW/SEW/HEW/REW NV400-CW/SW/SEW/HEW/REW NV630-CW/SW/SEW/HEW NF400-ZCW/ZSW/ZEW NF400-SWU/HWU NF400-UEW(3P) NF800-CEW/SDW/SEW/HEW/REW NV800-SEW/HEW, NF630-SWU/HWU NF400-UEW(4P), NF800-UEW
Reference drawing Fig. 2 Fig. 5
Variable dimensions C D 20.5 7.5 38 7.5
67.5
41.5
107.5
138.5
76.5
41.5
123.5
138.5
Fig. 4 Fig. 6
113
6 1 Accessories
7 10
6 Accessories
Internal Accessories
1
8. Lead Wire Drawing JLead J wire lateral drawing … Available to all models Note *1 Except for BH, BH-P, BH-S, BH-PS, BH-D6, BH-D10, BH-DN, BV-D, BV-DN and KB-D.
JLead J wires drawing to load Table 6-15 Model applicable to lead wire drawing to load
(only front connection type)
NF30-CS
JSpecifications J for lead wires Table 6-16 Applicable model
Kind of lead wire Lead wire thickness Lead wire length Example of ring mark 0.4mm2
NF30-CS
1000A frame or above
Heat-resistant wire
30 to 800A frames except above models
0.75mm2 0.5mm2
450mm
98/ALa (Red), 96/ALb (Blue) 95/ALc (Gray), 14/AXa (Brown) 12/AXb (Black), 11/AXc (White) C1/S1 (Red), C2/S2 (Red) J1/UC1 (White), J2/UC2 (White) A terminal symbol is indicated on each lead wire with a ring mark.
9. Lead Wire Terminal Block (1) Vertical lead wire terminal block (SLT)
Remark: 1. Although the following models are applicable to lead wires drawn laterally, they are normally applicable to installation in close contact with the circuit breaker side faces. (The circuit breaker side faces have grooves.)
NF32-SV, NF63-CV/SV/HV~NF250-CV/SV/HV/UV NF125-SEV/HEV, NF250-SEV/HEV, NF125-RGV NF250-RGV, NF125-SGV/LGV/HGV~NF250-SGV/LGV/HGV NV32-SV, NV63-CV/SV/HV~NV250-CV/SV/HV NV125-SEV/HEV, NV250-SEV/HEV NF50-SVFU, NF100-CVFU, NF125-SVU/HVU, NF250-SVU/HVU, NF225-CWU NV100-CVFU, NV125-SVU/HVU NV250-SVU/HVU (When a 4-pole model among the above models has accessories installed on the right pole side, the lead wires are 400 mm long.)
The lead wire terminal blocks for plug-in terminal blocks are available (P-LT). The drilling size of these terminal blocks differs from the standard size. Consult us for details. For a flush plate type circuit breaker, a terminal block will be installed on the circuit breaker rear face. (Specify as FP-LT.) Note *1 When the circuit breaker body is equipped with internal accessories and electrical operation device of motor-driven type (2) or spring charge type (2), the circuit breaker is normally provided with a lead wire terminal block.
JMCCB J Table 6-17-1 Table of variable dimensions
1 Accessories
E
25
10.5
B D
6
10.5
Terminal cover (transparent) 18
A
F 12.5
C Terminal screw M3.5
A 4 7 7 7 7
B 4.5 26.5 26.5 87.5 119
C 44.5 54 54 54 54
D 86.5 86.5 86.5 86.5 86.5
E 4.5 26.5 26.5 87.5 119
F 7 7 7 7 7
G 10 14 14 14 14
H 22 26 26 26 26
J 34 38 38 38 38
7
44
54
86.5
44
7
14
26
38
7 7 7 7
27.5 28.5 47.5 37
54 54 54 54
86.5 86.5 86.5 86.5
27.5 28.5 47.5 37
7 7 7 7
14 14 14 14
26 26 26 26
38 38 38 38
79.5
54
86.5
79.5
7
14
26
38
88.5 173 119.5 135.5
54 54 54 54
86.5 86.5 86.5 86.5
88.5 173 119.5 135.5
7 7 7 7
14 14 14 14
26 26 26 26
38 38 38 38
41 62.5 138
Note *1 The terminal positions are different from those shown in the left figure. Consult us for details. Remark: 1. Terminal screw tightening torque: M3.5 … 0.9 to 1.2 N·m
J H
114
Model (*1) NF30-CS NF32-SV, NF63-CV/SV/HV NF125-CV/SV/HV NF125-UV NF250-UV NF125-SEV/HEV/RGV, NF250-CV/SV/HV/SEV/HEV/RGV NF125-SGV/LGV/HGV, NF160-SGV/LGV/HGV NF250-SGV/LGV/HGV NF50-SVFU NF100-CVFU NF125-SVU/HVU NF225-CWU NF400-CW/SW/SEW/HEW/REW, NF400-SWU/HWU NF630-CW/SW/SEW/HEW/REW NF800-CEW/SDW/SEW/HEW/REW, NF630-SWU/HWU NF1000-SEW, NF1250-SEW, NF1600-SEW (*1) NF400-UEW(3P) (*1) NF400-UEW(4P), NF800-UEW
G
8 13.5
6 Accessories 1 Internal Accessories
Table 6-17-2 Table of variable dimensions
JELCB J Terminal cover (transparent)
A
F H
D
25
10.5
B
10.5
18
A 16.5 7 7 7 7 7 7
B 17 26.5 36.5 26.5 47.5 44 54
C 54 54 54 54 54 54 54
D 86.5 86.5 86.5 86.5 86.5 86.5 86.5
E 16.5 7 7 7 7 7 7
F 17 26.5 36.5 26.5 47.5 44 54
G 54 54 54 54 54 54 54
H 86.5 86.5 86.5 86.5 86.5 86.5 86.5
J 6 7 7 7 7 7 7
K 10.5 14 14 14 14 14 14
L 22.5 26 26 26 26 26 26
M 34.5 38 38 38 38 38 38
41
79.5
54
86.5
26.5
79.5
52
92
7
14
26
38
41
88.5
54
86.5
26.5
88.5
52
92
7
14
26
38
Notes *1 The terminal positions are different from those shown in the left figure. Consult us for details. Remarks: 1. Terminal screw tightening torque: M3.5 … 0.9 to 1.2 N·m 2. The lead wire terminal block for TBL is provided on the right pole side. However, the lead wire terminal blocks for TBL of NV30-FA and NV50-FA are provided on the left pole side.
J 12.5
C
Model NV50-SVFU NV32-SV, NV63-CV/SV/HV NV100-CVFU NV125-CV/SV/HV NV125-SVU/HVU NV125-SEV/HEV, NV250-CV/SV/HV/SEV/HEV NV250-SVU/HVU NV400-CW/SW/SEW/HEW/REW NV630-CW/SW/SEW/HEW (*1) NV800-SEW/HEW
G
Terminal screw M3.5
M K
8 13.5
E
L
J14-terminal J SLT SLT for installing three or more internal accessories on the left pole side Terminal cover (transparent)
Model
11 41
115
11
11
9
B
25
7 Terminal screw M3.5 A
Table 6-17-3 MCCB NF400-CW/SW/SEW NF400-HEW/REW NF630-CW/SW/SEW NF630-HEW/REW NF400-UEW(3P) NF800-CEW/SDW/SEW NF800-HEW/REW NF400-UEW(4P), NF800-UEW NF1000-SEW, NF1250-SEW NF1600-SEW
ELCB NV400-CW/SW/SEW NV400-HEW/REW NV630-CW/SW/SEW/HEW −
A
B
20
60
117
100
20
69
−
117
116
−
35
154
NV800-SEW/HEW
Remark: 1. The terminal positions are different from those shown in the left figure. Consult us for details.
17
75
10. Test Button Module (TBM) l The test button is kept pressed while control input voltage is applied to the button.
Table 6-18 18
18
Control input (VA)
1.5 VA or less
1 VA or less
Reference drawing
Fig. 1
Fig. 2
Note *1 Unless otherwise specified, the module will be manufactured for 100 to 240 V AC and 100 to 240 V DC. In the case of 24 V DC, specify the voltage. Remark: 1. The length of the lead wires to be connected to TBM1 and 2 shall be 100 m or more.
10.5
86.5
TBM1
Compatible with 100 to 240 AC and 100 to 240 DC (DC24) (*1)
7 Fig. 1
12
6.5 On a single-phase 3-wire circuit breaker with neutral pole protection, this terminal is used as an overvoltage detection terminal.
Fig. 2
12.5
(10.5)
TBM1 TBM2
92 (Terminal cover)
TBM2
(10.5)
Control input Rated voltage (V)
NV400-CW/SW NV630-CW/SW NV400-SEW~NV800-SEW NV400-HEW~NV800-HEW NV400-REW
10.5
Model
NV32-SV NV63-CV/SV/HV NV125-CV/SV/HV NV125-SEV/HEV NV250-CV/SV/HV/SEV/HEV NV50-SVFU NV100-CVFU NV125-SVU/HVU NV250-SVU/HVU
On a single-phase 3-wire circuit breaker with neutral pole protection, this terminal is used as an overvoltage detection terminal.
For a flush plate type with 250A frame or below, the external dimensions of the flush plate type differ from the standard dimensions.
115
6 1 Accessories
(When ELCB of time delay type is used, apply voltage for 2 seconds or more.) l The test button module is supplied with voltage through a circuit isolated from the main circuit. It can share the control sequence with SHT of a molded case circuit breaker. l Unlike TBL, the test button modules can be connected in parallel. l The module is normally provided with a vertical lead wire terminal block (SLT).
6 Accessories
Internal Accessories
1
11. Pre-Alarm Module (PAL) The pre-alarm is a function to output an alarm when the load current exceeds the preset current value. It is helpful in securing continuous power supply and preventive maintenance. It can be fitted to electronic circuit breakers with a frame size from 125 to 1600 A.
j 125 and 250A frames d Pre-alarm module (PAL module)
The standard modules have SLT. Other internal accessories cannot be installed on the right pole side. A control power supply (compatible with 100 to 240 V AC and DC) is necessary. The control power supply voltage range is 85 to 246 V AC/DC, and the required volt-ampere is 5 VA.
Table 6-19-1 Model
Switching capacity Contact output (1a)
NF125-SEV NF125-HEV NF250-SEV NF250-HEV NV125-SEV NV125-HEV NV250-SEV NV250-HEV
Pre-alarm characteristics
■ Applicable models NF125-SEV, NF250-SEV NV125-SEV, NV250-SEV
Pre-alarm operating characteristics
1h
Press the reset button, or turn off the control power supply.
Terminal arrangement
25
18 Long time delay operating time, TL 12-60-80-100s ±20% (at 200%)
2min
NF125-SEV NF125-HEV NF250-SEV NF250-HEV NV125-SEV NV125-HEV NV250-SEV NV250-HEV
■ Applicable models NF125-HEV, NF250-HEV NV125-HEV, NV250-HEV
Control power supply P1 P2
25
Operating time
30min 20min 14min 10min 6min 4min
Resetting method
DC 30V 2A DC100V 0.3A
Dimensional drawing of pre-alarm module
4h 2h
AC125V 2A AC250V 2A
1min 30s 20s 10s Pre-alarm current Ip Inx (0.7-0.75-0.8-0.852s 0.9-0.95-1.0) ±10% 5s
1s
0.2s 0.1s
60 70
100 125
200
300 400 500 600 700
Pre-alarm setting knob
Pre-alarm operation indicating LED
Pre-alarm operation indicating LED
Reset button
Reset button
133
Pre-alarm operating time Tp TL Tp= ±20% 2 (at200%)
0.5s
Pre-alarm setting knob
Pre-alarm output PALa
1000
Current (% to rated current In)
PALc
Terminal screw M3.5
d Pre-alarm LED indication
When the load current exceeds the preset current value, the LED lamp on the pre-alarm module front panel starts blinking. When the pre-alarm output is given, the lamp stops blinking and turns on.
d Pre-alarm current setting (IP setting)
The pre-alarm current can be set to the rated current In × 0.7, 0.75, 0.8, 0.85, 0.9, 0.95 or 1.0 with the knob on the pre-alarm module front panel.
j 400 A frame or above d Solid state relay (SSR) output (PAL lead)
The lead wires are drawn out. On the right pole side, only internal accessories with lead wires drawn out can be installed. A control power supply is unnecessary.
Table 6-19-2 Switching capacity Solid state relay (SSR) – Non-contact output
Model
Resetting method When the load current becomes lower than the preset current value, the alarm is reset.
AC/DC24 to 240V 20mA
d Pre-alarm module (PAL module)
The standard modules have SLT. Other internal accessories cannot be installed on the right pole side. A control power supply (compatible with 100 to 200 V AC) is necessary except for NF-ZEW. The control power supply voltage range is 80 to 242 V AC, and the required volt-ampere is 10 VA.
Table 6-19-3 Switching capacity Contact output (1a)
Model NF400-SEW NF400-HEW NF400-REW NF400-UEW NF630-SEW NF630-HEW NF630-REW NF800-CEW NF800-SEW NF800-HEW NF800-REW NF800-UEW NF1000-SEW NF1250-SEW NF1600-SEW NV400-SEW NV400-HEW NV400-REW NV630-SEW NV630-HEW NV800-SEW NV800-HEW
Pre-alarm characteristics
100 V AC or 200 V AC, 2 A
Detailed drawing of pre-alarm module
Pre-alarm module output rating AC
Pre-alarm operating characteristics
5h
Voltage V 200 100
2h 1h 30min 20min 14min 10min
PALOUT LED Long time delay operating time, TL 12-60-100-150s (at 200%)
6min 4min
RESET
1min
PALa Pre-alarm output
30s 20s 10s 5s 2s 1s
Reset switch
86.5
150s 100s 60s
2min
P2 Pre-alarm current Ip Inx (0.7-0.75-0.8-0.850.9-0.95-1.0) ±10%
12s
Pre-alarm operating time Tp TL Tp= (at200%) 2 60 70
100 125
200 300 400 500 600 700 1000 Current (% to rated current In)
Resetting method Press the reset button, or turn off the control power supply.
10h
Operating time
1 Accessories
6
NF400-SEW NF400-HEW NF400-REW NF400-UEW NF630-SEW NF630-HEW NF630-REW NF800-CEW NF800-SEW NF800-HEW NF800-REW NF800-UEW NF1000-SEW NF1250-SEW NF1600-SEW NV400-SEW NV400-HEW NV400-REW NV630-SEW NV630-HEW NV800-SEW NV800-HEW
P1
Control power supply
Current (A) Resistive load Inductive load 3 2 3 2
A control power supply (compatible with 100 to 200 V AC) is necessary. For the wiring method, see the following figure. (The control power supply voltage range is 80 to 242 V AC.) The required volt-ampere is 10 VA.
Vertical lead wire terminal block PALa Indicating lamp (example)
(PALc) 18
P2 P1
Control power supply PALc
d Pre-alarm LED display (standard device)
When the load current exceeds the preset current value, the LED lamp on the circuit breaker front panel starts blinking. When the pre-alarm output is given, the lamp stops blinking and turns on.
d Pre-alarm current setting (IP setting)
The pre-alarm current can be set to the rated current In × 0.7, 0.75, 0.8, 0.85, 0.9, 0.95 or 1.0 with the knob on the circuit breaker front panel.
116
6 Accessories
External Accessories
2
1. F-Type Operating Handle Operating handle of breaker mount type to be installed to circuit breaker body DAppearance D (Color: Munsell N1.5)
Dust-proof packing (optional)
DDThe handle provides an isolating function in combination with the circuit breaker body (except F10SW and above). DDIt has a safety device which prevents the circuit breaker turning on while the door is open. DDIt can be locked in the OFF position. (Up to 3 commercially available padlocks (35 mm and 40 mm) can be fitted. A type which can be locked in the ON or OFF position can be manufactured. Specify the type if required.) On circuit breakers with a frame size of 1000A or above, the handle can be locked in the ON or OFF position. (If it is necessary to lock the handle only in the OFF position, specify so.) DDIt is in protection class IP54 (IEC 60529). (For circuit breakers with a frame size of 1000A or above, the protection class (IEC 60529) is IP3X (IP5X when dust-proof packing is provided).
ON
ON ED IPP
TR
ED
150
150
OFF
B
O FF
RE
R
G
M Trip button
N Trip button
B
Thickness: 1.2 to 3.2 35
Release knob
83
A±2
150
Fig. 1
150 Thickness: 1.2 to 3.2
41
62
(a)
78
(b)
Circuit breaker
For 30 to 250 A frames
4-f15
For 400 to 800 A frames
Circuit breaker
(b)
(a)
(b)
(b)
(a)
Center of circuit breaker handle
Center of circuit breaker (a)
(b)
(b)
(a)
F C
E
(f)
11
D
D (b)
C
C
E
(g)
(4H+120) (5H+85) 0 or more or more or more
DDoor D lock withstand load
D
Center of operating handle
Center of circuit breaker handle
J
Center of circuit breaker
0 or more
Remarks: 1. The handle is opened and closed in the projection area of the handle and does not run over the projection area of the circuit breaker (except when the auxiliary handle is provided.) 2. When the operating handle is fitted to NV, the test button cannot be pressed easily. If necessary, use a circuit breaker with TBL or TBM. When using an Earth Leakage Alarm Breaker, use the externally resetting type (ECA-SLT RST) or automatically resetting type (ARS).
(e)
DDimensional D drawings of circuit breaker mounting holes Center of circuit breaker handle
Hinge on left side Hinge on right side H X2 X1 H Less than 10 170 or more (5H+85) 0 or more (5H+120) or more 10 or more or more
(4H+120) (8H+150) For 1000 to 1600 A 0 or more 0 or more frames or more or more
112
(d)
X2
DDThe right drawing shows the relationship between the hinges and circuit breaker viewed from the load side of the circuit breaker.
Center of hinge and circuit breaker
f1 18
Center of operating handle 112
Right hinge
L
112
Center of circuit breaker and operating handle
(c)
F
f9 0
Center of operating handle
78
Front plate
Circuit breaker
X1
Center of circuit breaker handle and operating handle
112
Center of circuit breaker and operating handle
Interlock engaging part F(N)
Fig. 3
Center of circuit breaker handle and operating handle 4-f15
78
78
f9 0
62
Center of circuit breaker and operating handle
Center of circuit breaker handle and operating handle 4-f12 Circuit breaker F
5
f6
4-f12
104
A 2
50
Auxiliary handle (Note)
A±2
Fig. 2
f1 18
Center of circuit breaker handle and operating handle
114
Thickness: 1.2 to 3.2
f20
DDimensional D drawings of front plate drilling 4-f12
F10SW~F120UR
Operating handle
Note Auxiliary handles are provided with F10SW, F10SW4P and F120UR as standard. Auxiliary handles (F-HT) are provided for F-4S ~ F-6SUL as option.
Center of circuit breaker handle and operating handle
PFL
Left hinge
T SE
ET N ES O P E
L
Trip button
DCenter D of hinge and breaker
Packing
TR
IP P
K Trip button
Decorative board Front plate Handle
Packing
Front plate
Delivery category
H
Center of operating handle
Release knob
Operating handle type name
H
DOutline D drawings
Type nema
F(N) F-05~F-2 F-4~F-8
L(mm) 50 68
500
E
(h)
Table 6-20 Summary of dimensions
F-05SV2 F-05SVE2 F-05SV F-05SVE (*2) F-1SV2, F-1SVE2 F-1SV F-1SVE F-1UV, F-1UVE
Door opening position OFF Reset position position
–
–
–
–
–
F-2SV F-2SVE
–
F-2UV, V-2UVE F-1SVUL F-2SVUL F-03SVUL2 F-03SVUL F-05SVUL2 F-05SVUL F-2SUL F-4S F-4SE F-4U F-4UE F-8S F-8SE F-8U F-8UE F-4SUL F-6SUL
– – – – – – – –
–
–
–
F10SW (*3) F10SW4P (*3)
–
– –
–
Reference drawing
Applicable model MCCB
NF32-SV NF63-CV, NF63-SV, NF63-HV NF32-SV NF63-CV, NF63-SV, NF63-HV NF125-CV, NF125-SV NF125-CV, NF125-SV NF125-HV NF125-UV NF125-SEV, NF125-HEV, NF125-RV NF125-SGV, NF125-LGV, NF125-HGV NF160-SGV, NF160-LGV, NF160-HGV NF250-SGV, NF250-LGV, NF250-HGV NF250-CV, NF250-SV, NF250-HV NF250-SEV, NF250-HEV, NF250-RV NF250-UV NF125-SVU, NF125-HVU NF250-SVU, NF250-HVU NF50-SVFU
Number of poles
2P
ELCB
–
NV32-SV 3P • 4P NV63-CV, NV63-SV, NV63-HV – 2P 3P • 4P NV125-CV, NV125-SV, NV125-HV 2P • 3P • 4P
2P • 3P • 4P
–
NV125-SEV, NV125-HEV 2P • 3P • 4P NV250-CV, NV250-SV, NV250-HV NV250-SEV, NV250-HEV
2P • 3P • 4P 3P 3P 2P 3P 2P 3P 3P
– NV125-SVU, NV125-HVU NV250-SVU, NV250-HVU
3P
–
NV50-SVFU
– NF100-CVFU NV100-CVFU – NF225-CWU NV400-CW, SW, SEW, HEW, REW NF400-CW, SW, SEW, HEW, REW 2P, 3P, 4P NV630-CW, SW, SEW, HEW NF630-CW, SW, SEW, HEW, REW NF400-UEW NF800-CEW, SDW, SEW NF800-HEW, REW NF800-UEW NF400-UEW(4P) NF400-SWU/HWU NF630-SWU/HWU NF1000-SEW NF1250-SEW/SDW NF1600-SEW/SDW
2P, 3P, 4P NV800-SEW, HEW
Dimensional Drilling plan Number of poles drawing
–
f
2P • 3P
g
b
–
f
3P • 4P
g c
–
Dimensions (mm)
A (*1)
25
b
3P, 4P
d
g
183
–
e
h
280
d
g
183
35
105 107
30 35 9 18 13 25 35
80 105 104 107
–
e
h
280
– –
3P –
d
g
183
–
–
d
g
221
Notes *1 The dimensions for the front connection type are shown. On some models of the rear connection type and plug-in type, the reference surface for mounting the circuit breaker may change. *2 For the 4-pole plug-in type, a special handle is required. Consult us for details. *3 If a handle which can be locked only in the OFF position is required, specify so. *4 The circuit breaker can be tripped by operating the trip button while the door is open. *5 Do not remove the sponge packing used to secure the protection class IP51. Fit the supplied packing without fail. *6 The handle cannot be used when the circuit breaker is installed on IEC 35-mm rails.
–
126
M4 screw or f5
201 123 126
Trip button position (*4)
–
–
–
–
31
86
L
–
K
38 6
100.5 61.5
K L K
–
–
L
–
–
L
M
82.5 111 126 194
–
234
20
243
– 70
–
4P
104
44
3P 3P
Fig. 3
J
N
30
107
3P, 4P
2P, 3P
G
111
104
h h g f g f g g
Fig. 2
F
N
172
h
c c b
3P
E
15 105
– 3P 3P 2P 3P – 3P –
b
D
13
f
a
C
105
b
3P • 4P Fig. 1
B
M6 screw or f7
–
290
23.5
44 70
194 243
–
70
375
M8 screw or f10
–
N L –
– –
–
Mounting screw
(a) Circuit breaker mounting screw (2 pcs.) (b) Circuit breaker handle mounting screw (2 pcs.) F-05SV2 F-05SVE2 F-1SV2 F-1SVE2 F-05SRUL2 F-03SVUL2 F-05SVUL2 Only the screws (b) are used for the following models.
(a)(b) Circuit breaker mounting screw (4 pcs.)
200
Remarks: 1. The handles with E in their model names are designed for emergency stop devices. Their delivery category is . 2. The standard handles are Reset Open Type which can open the doors only when they are reset to open. OFF Open type handles which can open the doors when they are in the OFF position can be manufactured to order. 3. A handle which can be operated and can indicate the ON and OFF positions in the same manner as the standard models even if the circuit breaker is installed horizontally can be manufactured to order. 4. F10SW and higher models do not conform to the isolation function. 5. Handles which are opened and closed in the OFF position can be opened also in the reset position.
117
6 2 Accessories
Type name
6 Accessories
2
External Accessories
DInstallation D procedure For details, please refer to Operating Handle Installation Manual supplied with the product. q Installation to a breaker
Install the operating handle to the circuit breaker in accordance with the following procedure.
250A frame and below
400 to 1600A frames Center of operating handle and center of circuit breaker
Circuit breaker mounting screw (2 pcs.) (a)
Circuit breaker mounting screw (supplied with body)
(Power supply side)
Installation procedure
Spacer for installation of operating section (supplied)
Handle
(Installation procedure)
Circuit breaker cover screws (Remove.)
(Load side)
2 poles 3 poles 4 poles
q Remove the circuit breaker cover screws in the same positions as the operating handle mounting holes. w Install the circuit breaker with the four circuit breaker mounting screws. e Fit the spacer(s) for installation of operating handle between the circuit breaker and operating handle. (The number of the spacers varies depending on the model.) r Install the operating handle with the supplied operating handle mounting screws. Center of operating handle and center of circuit breaker
Circuit breaker cover screws (Remove.)
Installation position of operating handle with respect to circuit breaker (Note 1) Operating handle mounting screw (2 pcs.) (b)
In the case of F-05SV2, F-1SV2, F-05SRUL2, F-05SUL2 and F-1SUL2 q Install the circuit breaker on the panel with the two circuit breaker mounting Tighten the circuit breaker and operating handle screws through the holes (a). together with the supplied two operating handle w Install the operating handle with the mounting screws. supplied two operating handle mounting screws through the holes (b).
(Installation procedure)
Handle
Operating section mounting screw (supplied)
(In the case of F-4S to F-6SUL) The operating handle mounting screws are tapping screws without washers or spring washers.
3 poles 4 poles Installation position of operating handle with respect to circuit breaker
Note *1 In the case of F-05SRUL2, the center of the operating handle is the same as the center of the circuit breaker.
w Installation of decorative board and retaining board Drill holes in the door according to the drilling size shown on the previous page, and tighten the decorative board and retaining board with the supplied countersunk screws. In the case of 800A frame or below, fit the supplied packing to the position shown right.
d Operation Lock Devices (1) Padlock B
Handle
Padlock Dimensions
C
Use commercially available padlocks. Applicable A (Nominal size) B model
Interlock lever Interlock engaging part Retaining board Packing (for 800A frame or below) Front plate (door)
(mm)
C
35
19
5
40
22 or 23
5.5
All models A
Dimension C: Maximum 8mm.
(2) Lockout Devices (Scissors Lock)
Decorative board Countersunk screw
d Door locking mechanism The panel door can be opened only when the operating handle is operated to open (reset). (On F-4S to F10SW, the door lock is held in the released state even if the handle is returned to OFF.) The door can be opened when the handle is in the ON position if the release knob is operated with a tool.
2 Accessories
6
d Operation locking mechanism Circuit breakers with a frame size of 800A or below can be locked by setting the handle in the OFF position. (Operating handles which can lock circuit breakers in the ON or OFF position can be manufactured.) Operate the locking part, and lock the handle with padlocks. Up to three padlocks can be fitted. Lockout hasps (scissors locks) can be used. If the circuit breaker trips even when the operating handle is locked in the ON position, also the operating handle indicates that it has tripped. F-2SUL or below: Only when one 35-mm padlock (weighing 70 g or less) is used F-4S or above: Only when one 40-mm padlock (weighing 100 g or less) is used To 800A frame or below, padlocks with dimension C of 3 mm to 8 mm can be applied. For 1000A or above, padlocks with dimension of 3 mm to 6 mm can be applied. (When using padlocks of 3 mm or less, please consult us.) d Circuit breaker installation direction (except UL 489 listed circuit breakers) We can supply circuit breakers on which the handles and their ON and OFF positions are in the same directions as on vertically installed circuit breakers even when they are installed horizontally. The door drilling size is identical. If you intend to install an operating handle on a horizontally installed circuit breaker, specify “Y” (horizontal installation with power supply on the left) or “Z” (horizontal installation with power supply on the right) at the end of the model name. (Ex.: F-4S Y) Power supply
Power supply
Lord
Power supply
Lord
d How to order For 800A frame or below, specify the following specification symbols together with the model name. · Operation lock: LF·················Lock in OFF position · Operation lock: LN·················Lock in ON or OFF position · Door opening: DR··················Reset to open · Operation lock: DF·················Open in OFF position · Installation direction: Blank····Power supply upward · Installation direction: Y···········Power supply on left · Operation lock: Z···················Power supply on right For a standard product with a frame size of 1000A or above, specify the model name. When it is required to enable the operation lock only in the OFF position, specify the model name and “only lock in OFF position.” If you intend to seal the release knob, place an order for the release protection. (Lot: 10 pcs.) d Interpretation of model name
Lord
d Sealing of release knob The use of an optional part, Release Protection “F-RCS”, can prevent the panel door being opened by operating the release knob. (800A frame or below)
118
Release knob
When F-RCS is not used
F-RCS
When F-RCS is used (sealed state)
(1) For 800A frame or below F – 1 SV UL E 2 1) 2) 3) 4) 5) 6) 1) F: Operating handle type name 2) 1: Circuit breaker group (0.5, 1, 2, 4, 6 or 8) 3) SV: Classification of circuit breaker (S, SV, H, U, UV, SR or SG) 4) UL: Blank···General product UL···UL 489 listed product 5) E: Blank···Standard E···For emergency stop 6) 2: Blank···3P or 4P 2···2P (2) For 1000A frame or above 10 SW 4P F 2) 3) 4) 1) 1) F: Operating handle type name 2) 4: Circuit breaker A frame (10 or 120) 3) SW: Series name 4) 4P: Number of poles (4P) * Not indicated for 3P
6 Accessories 2 External Accessories
2. V-Type Operating Handle
Operating handle of door mount type consisting of operating section to be mounted on circuit breaker body and operating handle on panel door
DAppearance D (Color: Munsell N1.5)
d The handle provides an isolation function in combination with the circuit breaker body. d Conforming to the safety regulations of EN Standard (EN 60204-1) d Protection class (IEC 60529) IP65 as standard d The handle can be locked only in the OFF position with up to three commercially available padlocks (35 mm or 40 mm). d The panel door can be opened in the OFF position. In the ON and trip positions, the panel door is locked and cannot be opened. However, the door can be opened even in the ON and trip positions by operating the release part with a tool.
DCenter D of hinge and breaker
DOutline D drawings Front plate
Front plate
Front plate
Front plate
ED
TR
I
PP
R
M Trip button
Thickness: 1.2 to 3.2 54 N Trip button
A
RE
12 67 70
K Trip button L Trip M button Trip button
B C±2
Thickness: 1.2 to 3.2
90 N Trip button
Fig. 1
A B C (stationary type) ±2 D (adjustable type) ±2
54
Thickness: A B 1.2 to 3.2 C (stationary type) ±2 62 D (adjustable type) ±2
140
Fig. 2
Circuit breaker
Fig. 3
DDimensional D drawings for front plate drilling
X
Center of operating handle
(a)
54
For 30 to 250 A frames
E
Center of operating handle
For 400 to 800 A frames
3
104
(b)
J
F
F
F
(d)
(e)
F
J
Center of operating handle
(f)
Center of operating handle
F J
(g)
0 or more
F(N) 30 to 800A frames
4 poles 3 poles CL C L
200
Circuit breaker
G
E
G F/2
J
G
Center of circuit breaker and operating handle
G
G
G
Center of circuit breaker and operating handle
Center of circuit breaker Center of circuit breaker handle
Center of circuit breaker
Circuit breaker Center of circuit breaker and operating handle
Center of circuit breaker handle
E
Center of circuit breaker
Center of circuit breaker and circuit breaker handle
Center of Center of circuit circuit breaker breaker
Center of Center of circuit breaker and circuit breaker circuit breaker handle handle
X
5H+100 or more 8H+150 or more
DDoor D lock withstand load
(c)
DDimensional D drawings of circuit breaker mounting holes Center of circuit breaker handle
H
* The above figure shows the relationship viewed from the load side.
ø6
4 ø5
0 ø4
40
4-ø10
Center of circuit breaker
104
40
E
ø9
X
Relationship between hinges and circuit breaker viewed from load side of circuit breaker
Center of circuit breaker handle and operating handle
Center of circuit breaker handle and operating handle Center of ø9 circuit breaker
54
Center of circuit breaker handle and operating handle
Right hinge
Left hinge
Note Auxiliary handles (F-HT) are provided for V-4S ~ V-6SUL as option.
Center of operating handle
H
H SE
T
OF F
140
OFF
ET ES
70
90
TRI
PP
F(N)
ON
ON
ED
F/2 F
F
J
(h)
C L
J
F Center of circuit breaker and operating handle
(j)
Table 6-21 Summary of dimension Adjustable type
MCCB
V-05SV2 V-05SVE2
NF32-SV NF63-CV, NF63-SV, NF63-HV
V-05SV V-05SVE
NF32-SV NF63-CV, NF63-SV, NF63-HV
V-1SV2, V-1SVE2
NF125-CV, NF125-SV
Number of poles 2P 3P 4P 2P 3P 4P 2P, 3P 4P 2P, 3P 4P
NF125-CV, NF125-SV (*1) NF125-HV Adjusting unit V-AD3S is V-1UV mounted on NF125-UV V-1UVE stationary type. NF125-SEV, NF125-HEV, NF125-SGV NF125-LGV, NF125-HGV, NF125-RGV 2P, 3P V-2SV NF160-SGV, NF160-LGV, NF160-HGV V-2SVE NF250-CV, NF250-SV, NF250-HV NF250-SGV, NF250-LGV, NF250-HGV 4P NF250-SEV, NF250-HEV, NF250-RGV 2P, 3P V-2UV NF250-UV V-2UVE 4P V-03SVUL2 2P − NF50-SVFU V-03SVUL 3P 2P V-05SVUL2 (*1) NF100-CVFU V-05SVUL Adjusting unit 3P V-1SVUL NF125-SVU, NF125-HVU 3P V-AD3S is mounted on V-2SVUL NF250-SVU, NF250-HVU 3P stationary type. NF225-CWU V-2SUL 3P V-4S NF400-CW/SW/SEW/HEW/REW 2P, 3P, 4P V-4SE NF630-CW/SW/SEW/HEW/REW (*1) V-4U NF400-UEW 3P Adjusting unit V-4UE V-AD3L is V-8S NF800-CEW/SDW/SEW/HEW/REW 2P, 3P, 4P mounted on V-8SE stationary type. NF400-SWU/HWU V-4SUL 3P V-6SUL NF630-SWU/HWU 3P V-1SV V-1SVE
Notes
Reference drawing ELCB
Number of poles
−
Drilling plan
−
−
−
−
NV125-SEV, NV125-HEV NV250-CV, NV250-SV, NV250-HV NV250-SEV, NV250-HEV
b
4P
f
−
162 300 39
−
− 2P 3P − 3P 3P 3P 3P
− 3P 3P −
*1 For the adjustable type, purchase the optional adjusting unit V-AD3S or V-AD3L. *2 The dimensions of the adjustable type models provided with the adjusting unit V-AD3S or V-AD3L are shown. *3 When using the operating handle for a plug-in type model with a frame size of 250A or below, specify so. *4 The dimensions on the front connection type are shown. For the rear connection and plug-in types, separately consult us. *5 The circuit breaker can be tripped by operating the trip button while the door is open. (The trip button position varies depending on the model.) *6 The handle cannot be used when the circuit breaker is installed on IEC 35-mm rails.
Fig. 1 Fig. 2 Fig. 2
a b b
c
61
−
125
39
25
L 111
N
30
M4 screw 172 or f5
L
e
41
126 35
37.5 39 39
76
61
125
−
−
−
61
− − 125 162 300
61
125 162 300
61
125 162 300
97
191 233 300
−
194 288 330 397
20
97
191 233 300
− 6 −
−
K 201
9 18 12.5 25 30 35 35 44
6
N
15
30.5
41
39
j
Trip button position (*5)
162 300
g h d e d e g
h
J
−
j Fig. 3
G
12.5 −
−
−
− −
Fig. 2
d e f e f g h e
− NV100-CVFU NV125-SVU, NV125-HVU NV250-SVU, NV250-HVU − NV400-CW/SW/SEW/HEW/REW 3P, 4P NV630-CW/SW/SEW/HEW
NV800-SEW/HEW
−
e
3P
− NV50-SVFU
B
d
NV32-SV 2P, 3P NV63-CV, NV63-SV, NV63-HV − − − − 3P NV125-CV, NV125-SV, NV125-HV 4P −
A
Dimensions (mm) Stationary Adjustable type type(*2) E F D D C (min) (max)
82.5 M4 111 screw f5 or 123 126 126
M N N L L K −
194
70
234 M6 screw 243 or f7
44 70
194 243
−
Remarks 1. The products whose model names contain E are designed for emergency stop. The delivery category is d. That of V-05SVE is d. 2. When the operating handle is fitted to NV, the test button cannot be pressed easily. If necessary, use a circuit breaker with TBL or TBM. When using an Earth Leakage Alarm Breaker, use the externally resetting type (ECA-SLT) or automatically resetting type (ARS).
119
2 Accessories
Stationary type
Applicable model
Dimensional drawing
Type name
6 Accessories
External Accessories
2
DInstallation D procedure For details, please refer to Operating Handle Installation Manual supplied with the product. q Installation to a breaker
Install the operating handle to the circuit breaker in accordance with the following procedure. 400 to 800A frames (Installation procedure)
q Operating handle for 3- or 4-pole circuit breaker Set the rotary plate of the operating section to the OFF (symbol O) position, and fit the plate to the circuit breaker with the supplied operating section mounting screws and nuts. Install the circuit breaker to the panel with the circuit breaker mounting screws (2 pcs.). w Operating handle for 2-pole circuit breaker Install the operating section together with the circuit breaker to the panel with the supplied operating section mounting screws (2 pcs.)
q Remove the circuit breaker cover screws (4 pcs.) in the same positions as the operating handle mounting holes. w Install the circuit breaker with the circuit breaker mounting screws (4 pcs.). e Fit the supplied operating section mounting spacers (4 pcs.) between the circuit breaker and operating handle. r Set the rotary plate to the OFF (symbol O) position, and install the operating section to the circuit breaker with the supplied operating section mounting screws. Circuit breaker cover screws (Remove.)
Nut M4 (2 pcs.): Except for 2-pole circuit breaker
Circuit breaker mounting screw (M6, 4 pcs.) (supplied with body)
Operating section
Spacer for installation of operating section (supplied)
Rotary plate Projection
(Load side) Projection
Circuit breaker
Circuit breaker cover screws (Remove.)
Rotary plate pin Operating section
Circuit breaker mounting screw (2 pcs.)
w Installation of operating handle section Drill a hole in the door according Operating handle section mounting screw to the dimensional drawing for (250A frame or below: 2 pcs. 400A frame or above: 4 pcs.) front plate drilling given on the Operating previous page, and install the handle section operating handle section in accordance with the following Washer (2 pcs.) procedure. · Tighten the operating handle section from the back of the front plate. Temporarily tighten the screws to center the section in the hole. · Set the handle of the operating Handle Front plate handle section to the OFF state, tighten the front plate, and make sure that the handle can be smoothly turned to the ON and OFF positions. Turn the handle to the right and left in the OFF state, and make sure that OFF is displayed. If OFF is not displayed, move the operating handle section up and down and to the right and left for adjustment. (Take care that the operating handle section is in parallel with the circuit breaker.) Then, open the front plate, and finally tighten the screws.
2 Accessories
d Door locking mechanism The operating handle is provided with an interlock mechanism to prevent the door opening in the ON and TRIP positions. In the OFF position, the door can be opened. However, the door can be opened in the ON or TRIP position by pressing the release knob in the arrow direction with a tool (3 mm wide and 1.8 mm thick).
Note The adjusting unit is not applicable to 2-pole external type circuit breakers. If it is used on a 2-pole external type circuit breaker, the positions may not be correctly displayed.
Shaft
Locking hole Operating section Padlock
Warning mark
Joint clamp screw
Make adjustments with the adjusting unit as stated below. qExternal dimension drawing
wCalculation of shaft cutting allowance
Front plate
Front plate
Thickness: 1.2 to 3.2
V-1SV V-1SVUL V-1SUL Release knob
Operating section
Joints
Min Max Dimensions (mm) Min
Max
P
Cutting allowance
V-05SV V-05SVUL
d Adjusting unit The height from the circuit breaker mounting surface to the panel door can be adjusted by fitting the optional adjusting unit V-AD3S or V-AD3L. Cut the shaft of the adjusting unit according to the height.
120
Operating section mounting screw (supplied) (4 pcs.)
Type name
d Operation locking mechanism q Operating handle section Operation lock can be set only in the OFF Position. Up to three commercially available padlocks (A = 35 or 40 mm) can be fitted. Lockout hasps (scissors locks) can be used. When the operating handle section is locked with padlocks, also the door is locked. w Operating section The operating section can be locked so that the circuit breaker will not be turned on carelessly when the inside of the panel is inspected with the panel door open. Fit a padlock through the hole in the operating section of the operating handle.
Rotary plate Rotary plate pin
Shaft
162
300
V-2SV V-2SVUL V-2SUL V-2SGUL
X 175
180
Cutting allowance
(Cutting allowance)(P max)(panel size) X = 300 mm - P
318
V-4S
Shaft
V-8S
233
Calculation
8
Operating sectiuon mounting screw (2 pcs.)
6
(Power supply side)
10
Installation procedure
250A frame and below (Installation procedure)
300
V-4SUL V-6SUL
X 109
Cutting allowance
Note The unit is applicable to operating handles for emergency stop (E).
d Padlocks The user must prepare padlocks. The dimensions of the padlocks are the same as those shown on page 129. d How to order Specify the model name of the operating handle. For adjustable type, place an order for the adjustment unit. (One lot includes 1 pc.) 250A frame or below: V-AD3S 400 to 800A frames: V-AD3L d Interpretation of model name (1) For 800A frame or below V – 1 S UL E 1) 2) 3) 4) 5) 1) 2) 3) 4) 5) 6)
V: 1: S: UL: E: 2:
2 6)
Operating handle type name Circuit breaker group (0.5, 1, 2, 4, 6 or 8) Classification of circuit breaker (S, SV, H, U, UV) Blank···General product UL···UL 489 listed product Blank···Standard E···For emergency stop Blank···3P or 4P 2···2P
6 Accessories 2 External Accessories
3. Terminal Covers
C
A
B
The terminal covers are used to avoid exposure of live parts. Many kinds of terminal covers, including large terminal covers (TC-L), small terminal covers (TC-S), transparent terminal covers (TTC), rear terminal covers (BTC) and plug-in terminal covers (PTC), for various models and applications are available, and they are helpful. (The terminal covers cannot be fitted to electrically operated circuit breakers of spring charged type (2) and motor-drive type (2). The standard terminal covers can be used for the spring charged type (1). For the motor-drive type, special terminal covers can be manufactured. Consult us for details.) d Quick terminal covers These covers are very convenient because they can be fitted only by inserting them into the mounting holes in the circuit breaker body. To remove the terminal cover, shift the projections of the terminal cover with the tip of a slotted screwdriver or finger, and draw it out.
ON
TC-L TC-S TTC
DTable D of variable dimensions Table 6-22 Large terminal covers (TC-L)
TCL-05SV2 (*2)(*8) TCL-05SV2L (*2)(*9) (*3)(*8)
TCL-05SV3L (*3)(*9) TCL-05SV4 (*3) TCL-1SV2 (*2) TCL-1SV3
(*3)
TCL-1SV4
(*3)
TCL-2SV3
(*3)(*10)
TCL-2SV3L (*3)(*11)
TCL-2SV4
(*3)(*5)
TCL-4SW3
(*3)
TCL-4SW4
(*3)
TCL-8SW3
(*3)
TCL-8UW3 TCL-8SW4
(*3)
TCL-8UW4 TCL-10SW3 TCL-10SW4 TCL-03SVU2 (*3) TCL-03SVU3 (*3) TCL-05SVU2 (*2)(*8) TCL-05SU2L (*2)(*9) TCL-05SVU3 (*3)(*8) TCL-05SVU3L (*3)(*9) TCL-1SVU3
(*3)
White 2, 3 NF800-CEW/SDW/SEW/HEW/REW NF600-SEP with MDU/HEP with MDU (*7) White 3 NF800-SEP with MDU/HEP with MDU (*7) Transparent 3 NF800-UEW (*4) NF800-SEW/HEW White 4 NF600-SEP with MDU/HEP with MDU (*7) NF800-SEP with MDU/HEP with MDU (*7) Transparent 4 NF400-UEW, NF800-UEW (*4) NF1000-SEW Transparent 3 NF1250-SEW/SDW NF1000-SEW Transparent 4 NF1250-SEW/SDW White 2 NF50-SVFU White 3 NF50-SVFU White 2 NF100-CVFU White 2 NF100-CVFU White 3 NF100-CVFU White 3 NF100-CVFU 2, 3 NF125-SVU White 3 NF125-HVU
TCL-2SVU3 White (*3)(*10) TCL-2SVU3L White (*3)(*11) TCL-2SWU3 (*10) White
TCL-2SWU3L White (*3)(*11) TCL-4SWU White TCL-6SWU
Transparent
NV800-SEW/HEW
Dimensions (mm)
Contents Cover Sealing Number mounting of covers screw plate 2 − 2 2 − 2
A
B
C
43.5 67
25 25
30.5 30.5
50
25
65.5
2
−
2
50
40
65.5
2
−
2
75
25
65.5
2
−
2
75
40
65.5
2
−
2
100 60
25 40
65.5 65.5
2 2
− −
2 2
90
40
65.5
2
−
2
120
40
65.5
2
−
2
105
40
65.5
2
−
2
105
50
65.5
2
−
2
140
40
65.5
2
−
2
171
110
99.5
2
−
171
110
132.5/196.5
2
−
240
110
105
2
6
2
224
155
103.5
2
4
−
220
155
146/194.5
2
4
−
−
294
155
103.5
2
6
−
Quick type The cover can be sealed with the sealing plate.
6 Use in combination with insulating barrier.
−
290
155
146/194.5
2
6
−
−
220
150
139
2
4
−
−
290
150
139
2
4
−
Screw type
NV50-SVFU NV50-SVFU − − NV100-CVFU NV100-CVFU − NV125-SVU/HVU
36 54 50 50 75 75
30 30 25 40 25 40
65.5 65.5 65.5 65.5 65.5 65.5
2 2 2 2 2 2
− − 2 2 2 2
− − − − − −
Quick type (Remove the existing cover from the body, and fit the terminal cover.)
90
40
65.5
2
2
− −
Screw type
3
NF250-SVU/HVU
NV250-SVU/HVU
105
40
65.5
2
2
3
NF250-SVU/HVU
NV250-SVU/HVU
105
50
65.5
2
2
−
3
NF225-CWU
−
105
40
65.5
2
−
−
3
NF225-CWU
−
105
50
65.5
2
−
−
3
NF400-SWU/HWU
−
171
110
99.5
2
−
2
Screw type (Remove the existing cover from the body, and fit the terminal cover.) Screw type (Remove the existing cover from the body, and fit the terminal cover.) Screw type (Remove the existing cover from the body, and fit the terminal cover.) Quick type (Remove the existing cover from the body, and fit the terminal cover.) Quick type (Remove the existing cover from the body, and fit the terminal cover.) Quick type
3
NF630-SWU/HWU
−
224
155
103.5
2
4
−
Screw type
Notes *1 For 2-pole NV, use TC-L for 3-pole circuit breaker. *2 For a circuit breaker with F or V type operating handle, specify the model name with F at the end. (F or V type operating handle dedicated models, screws are used for fixing.) *3 The standard models can be used in combination with F and V Type Operating Handles. *4 The dimension C is the size on the power supply side and load side. *5 When a crimp terminal applicable to wires with a size of 117.2 to 152.05 mm2 (Model 2CR-150 or CB150-S8) is used, TC-L cannot be fitted. Insulate the terminal from TC-S with insulating tube or taping. *6 In the case of installation on the body, specify the model name with-MDU at the end. *7 It cannot be installed in the case of installation on the body.
Remarks
−
−
−
Appearance
Use in combination with insulating barrier.
*8 Applicable to circuit breakers with rating of 75A or less (max. wire size 25 mm2) *9 Applicable to circuit breakers with rating of 125A or less (max. wire size 60 mm2) *10 Applicable to circuit breakers with rating of 200A or less (max. wire size 100 mm2) *11 Applicable to circuit breakers with rating of 250A or less (max. wire size 150 mm2) (Applicable to UL wire 300MCM) Remarks 1. The wire sizes shown in the above notes *10 to *13 are those of the 600-V vinyl insulated wires. 2. Insulate the exposed live parts of crimp terminals with insulating tape or the like. 3. When protection from the power supply and load sides is necessary, 121 separately consult us.
2 Accessories
TCL-03CS2W TCL-03CS3W
TCL-05SV3
Applicable model Number of poles of circuit MCCB ELCB breaker White 2 − (*1) NF30-CS White 3 − NF32-SV White 2 − NF63-CV/SV/HV NF32-SV − White 2 NF63-CV/SV/HV NF32-SV NV32-SV, NV63-HV White 3 NF63-CV/SV/HV White 2, 3 − NV63-CV/SV White 3 NF32-SV, NF63-CV/SV/HV NV32-SV, NV63-HV White 2, 3 − NV63-CV/SV White 4 NF63-SV/HV − White 2 NF125-CV/SV − White 3 NF125-CV/SV NV125-CV/SV/HV White 2, 3 NF125-HV/UV − White 4 NF125-SV/HV/UV NV125-SV/HV NF125-SGV/LGV/HGV/RGV NF160-SGV/LGV/HGV NV250-CV/SV/HV White 2, 3 NF250-SGV/LGV/HGV/RGV NV250-SEV/HEV NF250-CV/SV/HV/UV, NF250-SEV/HEV NV125-SEV/HEV NF125-SEV/HEV White 3 (*6) NF125-SGV/LGV/HGV/RGV NF160-SGV/LGV/HGV NV250-CV/SV/HV White 2, 3 NF250-SGV/LGV/HGV/RGV NV250-SEV/HEV NF250-CV/SV/HV/UV, NF250-SEV/HEV NV125-SEV/HEV NF125-SEV/HEV NF250-SV/HV/UV NV250-SV/HV NF250-SEV/HEV NV250-SEV/HEV White 4 NF125-SEV/HEV NV125-SEV/HEV NF225-SWM (*6) NF400-CW/SW/SEW NV400-CW/SW/SEW White 2, 3 NF630-CW/SW/SEW NV630-CW/SW/SEW NF400-SEP with MDU (*7) − White 3 NF400-UEW (*4) − NF400-SW/SEW/HEW NV400-SEW/HEW White 4 NF630-SW/SEW NV630-SEW NF400-SEP with MDU (*7) Color
Type name
6 Accessories
External Accessories
2
Type name TCS-03CS2W
Color
Table 6-23 Small terminal covers (TC-S) Number of poles of circuit breaker
White
2
Applicable model MCCB
Dimensions (mm) ELCB
A
B
C
−
43.5
5
30.5
Contents Cover Sealing Number mounting of covers screw plate 2
−
Appearance
Remarks
2
NF30-CS TCS-03CS3W TCS-05SV2 TCS-05SV3
White
3
(*1) White
2
NF32-SV, NF63-CV/SV/HV
White
3
NF32-SV, NF63-CV/SV/HV NV32-SV, NV63-HV
(*2)
TCS-1SV2 (*2)
White 2, 3
−
White
2
NF125-CV/SV
White
3
NF125-CV/SV
−
67
5
30.5
2
−
2
−
50
5
65.5
2
−
2
75
5
65.5
2
−
2
60
6.5
65.5
2
−
2
90
6.5
65.5
2
−
2
6.5
65.5
2
−
2
NV63-CV/SV − NV125-CV/SV/HV
TCS-1SV3 (*3) White 2, 3 NF125-HV/UV
−
NF125-SGV/LGV/HGV/RGV NF160-SGV/LGV/HGV NV250-CV/SV/HV 105 White 2, 3 NF250-SGV/LGV/HGV/RGV NV250-SEV/HEV (*2) NF250-CV/SV/HV/UV, NF250-SEV/HEV NV125-SEV/HEV NF125-SEV/HEV Notes *1 For a circuit breaker with F type operating handle, specify the model name with F at the end. (F type operating handle dedicated models, screws are used for fixing.) *2 The standard models can be used in combination with F and V Type Operating Handles. TCS-2SV3
Quick type The cover can be sealed with the sealing plate.
Remarks 1. Small terminal covers for 4-pole circuit breakers are available. 2. Insulate the exposed live parts of crimp terminals with insulating tape or the like.
Table 6-24 Transparent terminal covers (TTC) Applicable model
Number of poles of circuit breaker
Type name TTC-03CS2
MCCB
Dimensions (mm) ELCB
A
B
C
−
43.5
25
30.5
2
Contents Cover Sealing Number mounting of covers screw plate 2
−
Appearance
Remarks
2
NF30-CS TTC-03CS3 TTC-05SV2 TTC-05SV3
3 (*1)
3 (*2)
TTC-1SV2
(*1)
TTC-1SV3
(*2)
2 Accessories
2, 3
NF32-SV NF63-CV/SV/HV NF32-SV NF63-CV/SV/HV −
2
NF125-CV/SV
3
NF125-CV/SV
2, 3
NF125-HV/UV
−
67
25
30.5
2
−
2
−
50
25
65.5
2
−
2
75
25
65.5
2
−
2
60
40
65.5
2
−
2
90
40
65.5
2
−
2
122
2, 3
105
40
65.5
2
−
2
171
110
104.5
2
4
−
240
110
104.5
2
6
−
224
155
103.5
2
4
−
294
155
103.5
2
6
−
Transparent
NV32-SV, NV63-HV NV63-CV/SV − NV125-CV/SV/HV −
NF125-SGV/LGV/HGV/RGV NF160-SGV/LGV/HGV NV250-CV/SV/HV NF250-SGV/LGV/HGV/RGV NV250-SEV/HEV NF250-CV/SV/HV/UV, NF250-SEV/HEV NV125-SEV/HEV NF125-SEV/HEV 3 − − NV400-CW/SW/SEW NF400-CW/SW/SEW NV400-HEW/REW NF400-HEW/REW 2, 3 NV630-CW/SW/SEW NF630-CW/SW/SEW TTC-4SW3 NV630-HEW NF630-HEW/REW 3 NF400-SEP with MDU/HEP with MDU (*4) − NF400-SW/SEW/HEW NV400-SEW/HEW TTC-4SW4 4 NF630-SW/SEW/HEW NV630-SEW NF400-SEP with MDU/HEP with MDU (*4) NF800-CEW/SDW/SEW NV800-SEW/HEW 2, 3 NF800-HEW/REW TTC-8SW3 NF600-SEP with MDU/HEP with MDU (*4) 3 − NF800-SEP with MDU/HEP with MDU (*4) NF800-SEW/HEW TTC-8SW4 4 NF600-SEP with MDU/HEP with MDU (*4) − NF800-SEP with MDU/HEP with MDU (*4) Notes *1 For a circuit breaker with F type operating handle, specify the model name with F at the end. (F type operating handle dedicated models, screws are used for fixing.) *2 The standard models can be used in combination with F and V Type Operating Handles. TTC-2SV3 (*2)(*3)(*5)
6
2
Quick type The cover can be sealed with the sealing plate.
Transparent
Use in combination with insulating barrier. Screw type
*3 When a crimp terminal applicable to wires with a size of 117.2 to 152.05 mm2 (Model 2CR-150 or CB150-S8) is used, TTC cannot be fitted. Use TCL-2SV3L. Or insulate the terminal from TC-S with insulating tube or taping. *4 In the case of installation on the body, specify the model name with • MDU at the end. *5 Applicable to circuit breakers with rating of 200A or less (max. wire size 100 mm2)
6 Accessories 2 External Accessories
Fig. 1
A
Fig. 2
A
D C
A
C
B
B
B
C
ON
ON
BTC-03CS2W
White
Applicable model
Number of poles of circuit breaker
MCCB
Dimensions (mm) ELCB
2
A
B
Contents Cover Sealing Number mounting of covers screw plate
C
−
43.5
6.5
30.5
2
−
2
−
67
6.5
30.5
2
−
2
50
5
65.5
2
−
2
75
5
65.5
2
−
2
60
6.5
65.5
2
−
2
NV125-CV/SV/HV −
90
6.5
65.5
2
−
2
NV250-CV/SV/HV NV250-SEV/HEV NV125-SEV/HEV
105
6.5
65.5
2
−
2
NV400-CW/SW/SEW NV630-CW/SW/SEW (*5)
140
42 (*2)
99.5
2
−
−
140
42 (*2)
132.5/ 196.5
2
−
185
42 (*2)
97.5
2
6
−
210
32 (*2)
97.5
2
8
−
210
32 (*2)
146/ 194.5
2
4
−
280
32 (*2)
97.5
2
10
−
32 (*2)
146/ 194.5
2
6
−
Appearance
NF30-CS BTC-03CS3W BTC-05SV2 BTC-05SV3 BTC-1SV2 BTC-1SV3
BTC-2SV3
BTC-4SW3
BTC-4SW4
BTC-8SW3
BTC-8SW4
White
3
NF32-SV White 2 NF63-CV/SV/HV NF32-SV White 3 NF63-CV/SV/HV White 2, 3 − White
2
−
(*1)
NV32-SV, NV63-HV NV63-CV/SV
NF125-CV/SV
−
White 3 NF125-CV/SV White 2, 3 NF125-HV/UV NF125-SGV/LGV/HGV/RGV NF160-SGV/LGV/HGV White 2, 3 NF250-SGV/LGV/HGV/RGV NF250-CV/SV/HV/UV, NF250-SEV/HEV NF125-SEV/HEV NF400-CW/SW/SEW White 2, 3 NF630-CW/SW/SEW NF400-SEP with MDU (*5) White 3 NF400-UEW (*4)
NF400-SW/SEW/HEW NV400-SEW/HEW (*3) Transparent 4 NF630-SW/SEW/HEW NV630-SEW NF400-SEP with MDU/HEP with MDU (*5) Transparent 2, 3 NF800-CEW/SDW/SEW/HEW/REW NV800-SEW/HEW NF600-SEP with MDU/HEP with MDU (*5) − NF800-SEP with MDU/HEP with MDU (*5) (*3) Transparent 3 NF800-UEW (*4) −
(*3) Transparent
4
NF800-SEW/HEW NF600-SEP with MDU/HEP with MDU (*5) NF800-SEP with MDU/HEP with MDU (*5) NF400-UEW, NF800-UEW (*4)
(*5)
−
Notes *1 For 2-pole ELCB, use BTC for 3-pole circuit breaker. *2 Dimension B in Fig. 2 *3 The covers can be used for plug-in type circuit breakers. Other models are designed only for rear connection type. *4 The dimension C is the size on the power supply side and load side. *5 In the case of installation on the body, it can be fitted only on the power supply side.
280
2
Remarks Cover for connection block in the case of simple rear connection
Cover for stud connection block on back in the case of rear connection type Quick type The cover can be sealed with the sealing plate.
Screw type
Remarks 1. PTC-4SW3 can be used as the back terminal covers for NF400-HEW/REW, NF630-HEW/REW, NV400-HEW/REW and NV630-HEW. 2. For terminal covers for 4-pole circuit breakers not listed above, consult us.
6
Type name PTC-05SV2 PTC-05SV3 PTC-1SV2
Color
Table 6-26 Plug-in terminal covers (PTC) Number of poles of circuit breaker
White
2
White
3
White 2, 3
Applicable model MCCB NF32-SV NF63-CV/SV/HV NF32-SV NF63-CV/SV/HV −
White
2
NF125-CV/SV
White
3
NF125-CV/SV
Dimensions (mm)
PTC-2SV3
PTC-4SW3
NF125-SGV/LGV/HGV/RGV NF160-SGV/LGV/HGV White 2, 3 NF250-SGV/LGV/HGV/RGV NF250-CV/SV/HV/UV, NF250-SEV/HEV NF125-SEV/HEV NF400-CW/SW/SEW NF630-CW/SW/SEW (*2) Transparent 2, 3 NF400-HEW/REW (*1) NF630-HEW/REW (*1)
Appearance
ELCB
A
B
C
D
−
50
6.5
65.5
72
2
2
−
75
6.5
65.5
72
2
2
−
60
6.5
65.5
−
2
4
−
90
6.5
65.5
−
2
4
−
NV250-CV/SV/HV NV250-SEV/HEV NV125-SEV/HEV
105
6.5
65.5
78.5
2
4
−
Screw type
NV400-CW/SW/SEW NV630-CW/SW/SEW NV400-HEW/REW (*1) NV630-HEW (*1)
140
42
97.5
−
2
4
−
Same as screw type of BTC
Remarks
NV32-SV, NV63-HV NV63-CV/SV −
Cover for stud connection block in the case of plug-in type
NV125-CV/SV/HV
PTC-1SV3 White 2, 3 NF125-HV/UV
Contents Cover Sealing Number mounting of covers screw plate
−
Notes *1 The covers can be used as back terminal covers. *2 See Fig. 2 of BTC.
123
2 Accessories
Type name
Color
Table 6-25 Rear terminal cover (BTC)
6 Accessories
External Accessories
2
Table 6-27 List of terminal covers applicable to F and V Type Operating Handles Large terminal covers (TC-L) TCL-05SV2F (*2)(*3) TCL-05SV2LF (*2)(*4) TCL-05SV3 (*3) TCL-05SV3L (*4) TCL-05SV4 TCL-1SV2F (*2) TCL-1SV3 TCL-1SV4 TCL-2SV3 TCL-2SV3L
Type name Small terminal covers (TC-S) TCS-05SV2F
Transparent terminal covers (TTC)
(*2) TTC-05SV2F
TCS-05SV3
TTC-05SV3
– TCS-1SV2F
– (*2) TTC-1SV2F
TCS-1SV3 – (*5) TCS-2SV3 (*6)
F-05SV, V-05SV (*2) F-1SV2, V-1SV2 F-1SV, V-1SV
– TTC-2SV3 –
TCL-4SW3 TCL-4SP3W
–
TTC-4SW3
3 2, 3 4 2 3 2, 3 4 2, 3
TCL-4SW4
–
TTC-4SW4
TCL-8SW3
–
TTC-8SW3
TCL-8SW4
–
TTC-8SW4
4
F-4S V-4S
F-8S V-8S
For 2-pole NV, use a terminal cover for 3-pole circuit breaker. Only for F and V Type Operating Handles (screw type) Applicable to circuit breakers with rating of 75A or less (max. wire size 25 mm2) Applicable to circuit breakers with rating of 125A or less (max. wire size 60 mm2) Applicable to circuit breakers with rating of 200A or less (max. wire size 100 mm2) Applicable to circuit breakers with rating of 250A or less (max. wire size 150 mm2)
MCCB
ELCB
NF32-SV, NF63-CV/SV/HV
2
F-2SV, V-2SV
–
Applicable model
Number of poles of circuit breaker
(*2) F-05SV2, V-05SV2
TTC-1SV3
TCL-2SV4
Notes *1 *2 *3 *4 *5 *6
Applicable operating handles
2, 3 4 2, 3
– (*1)
NF32-SV, NF63-CV/SV/HV – NF32-SV, NF63-CV/SV/HV NF125-CV/SV NF125-CV/SV NF125-HV/UV NF125-CV/SV/HV/UV NF250-CV/SV/HV/UV, NF250-SEV/HEV NF125-SEV/HEV NF250-CV/SV/HV/UV, NF250-SEV/HEV NF125-SEV/HEV NF400-CW/SW/SEW/HEW/REW NF630-CW/SW/SEW/HEW/REW NF400-SW/SEW/HEW NF630-SW/SEW/HEW
NV32-SV, NV63-HV NV63-CV/SV – – NV125-CV/SV/HV – NV125-CV/SV/HV NV250-CV/SV/HV, NV250-SEV/HEV NV125-SEV/HEV NV250-CV/SV/HV, NV250-SEV/HEV NV125-SEV/HEV NV400-CW/SW/SEW/HEW/REW NV630-CW/SW/SEW/HEW NV400-SEW/HEW NV630-SEW
NF800-CEW/SDW/SEW/HEW/REW
NV800-SEW/HEW
NF800-SEW/HEW
4
–
Remark: 1. The terminal covers for UL 489 Listed Circuit Breakers can be normally combined with F Type Operating Handles.
4. Insulating Barriers The insulating barrier enhances the insulation between the phases of circuit breaker terminals. It also prevents accidents due to conductive foreign matter and dust, and secondary accidents when isolating a fault current.
D insulating barrier is available for the models listed in the table below. 6 DThe Table 6-28
2 Accessories
Applicable model
MCCB NF32-SV, NF63-CV NF125-CV, NF100-CVFU NF63-SV/HV NF125-SV/HV NF125-SEV/HEV, NF125-ZEV NF250-CV/SV/HV/SEV/HEV NF125-SGV/LGV/HGV/RGV NF160-SGV/LGV/HGV NF250-SGV/LGV/HGV/RGV NF250-SEV/HEV/ZEV with MDU NF125-SVU NF125-HVU NF250-SVU NF250-HVU NF225-CWU NF400-CW/SW/SEW/HEW/REW/UEW NF630-CW/SW/SEW/HEW/REW NF400-UEW(4P) NF800-CEW/SEW/HEW/REW/SDW
ELCB NV32-SV, NV63-CV NV125-CV, NV100-CVFU NV63-SV/HV NV125-SV/HV
Front
(“” denotes optional)
Connecting method Rear Flush plate
Plug-in
–
–
–
Standard attachment
–
–
–
Standard attachment
–
–
Standard attachment
Standard attachment
–
–
–
Standard attachment
Standard attachment
Standard attachment
–
Standard attachment
–
–
Standard attachment
–
–
–
NF1000-SEW, NF1250-SEW/SDW
–
Standard attachment
–
–
Standard attachment
NF1600-SEW/SDW
–
Standard attachment
–
–
–
NF800-UEW NF400-SWU/HWU NF630-SWU/HWU
Always mount the insulating barrier when it comes with the circuit breaker.
124
NV125-SEV/HEV NV250-CV/SV/HV/SEV/HEV NV250-SEV/HEV with MDU NV125-SVU NV125-HVU NV250-SVU NV250-HVU NV100-SWU NV400-CW/SW/SEW/HEW/REW NV630-CW/SW/SEW/HEW NV800-SEW/HEW
6 Accessories 2 External Accessories
DInsulating D Barrier-Front (BA-F) Table 6-29 Summary of dimensions Applicable model
Type name
MCCB
BAF-2SV
BAF-05SVU BAF-2SVU
NV32-SV NV63-CV NV125-CV NV63-SV/HV NV125-SV/HV
NF100-CVFU
NV100-CVFU
NF125-SVU NF125-HVU NF250-SVU NF250-HVU
NV125-SVU NV125-HVU NV250-SVU NV250-HVU
BAF-2SWU
NF225-CWU
BAF-4SW
NF400-CW/SW/SEW/HEW/REW NF630-CW/SW/SEW/HEW/REW
BAF-4UW
BAF-4SWU
Quantity per breaker 2P 3P 4P 1 (*2)
59.5
2
Reference diagram
3 A
− NV400-CW/SW/SEW/HEW/REW NV630-CW/SW/SEW/HEW
100
59.5
2
4
6
50
59.5
2
4
−
100
59.5
−
4
−
100
59.5
−
4
−
110
98.5
2
4
6
−
110
132/ 98.5
−
4
−
NF800-CEW/SEW/SDW/HEW/REW NV800-SEW/HEW
110
98.5
1
2
3
NF400-UEW(4P) NF800-UEW, NF1000-SEW NF1250-SEW/SDW NF400-SWU/HWU NF630-SWU/HWU(less than 600A)
BAF-10SW
50
NV125-SEV/HEV NV250-CV/SV/HV/SEV/HEV NV250-SEV/HEV with MDU
(*1) NF400-UEW(3P)
BAF-8SW
Dimensions (mm) A B
B
BAF-05SV
NF32-SV NF63-CV NF125-CV NF63-SV/HV NF125-SV/HV/UV NF125-SEV/HEV NF125-SGV/LGV/HGV/RGV NF160-SGV/LGV/HGV NF250-CV/SV/HV/UV/SEV/HEV NF250-SGV/LGV/HGV/RGV NF250-SEV/HEV/ZEV with MDU
ELCB
−
110
132
1
2
3
− −
110 110
98.5 98.5
− −
4 2
− −
BAF-6SWU
NF630-SWU/HWU(630A)
−
150
98.5
−
4
−
BAF-16SW
NF1600-SEW/SDW
−
185
132
1
2
3
Notes *1 The barriers BAF-4UW for the power supply and load sides vary in the dimension B. *2 Not supplied with ELCB.
DInsulating D Barrier-Rear (BA-B) Table 6-30 Summary of dimensions Applicable model
Type name
MCCB
Dimensions (mm) Quantity per breaker A B 2P 3P 4P
ELCB
NF400-CW/SW/SEW/HEW/REW NF400-UEW(3P) NF630-CW/SW/SEW/HEW/REW
NV400-CW/SW/SEW/HEW/REW NV630-CW/SW/SEW/HEW
140
74.5
−
4
6
BAB-8SW
NF800-CEW/SEW/SDW/HEW/REW NF400-UEW(4P) NF800-UEW
NV800-SEW/HEW
140
74.5
−
4
6
Mounting panel
A
BAB-4SW
Reference diagram
B
6
Drilling size for use of BA-B (in the case of 3-pole circuit breaker)
Power supply side
Note The dimensions in brackets are those for NF400-UEW.
NF800-CEW, NF800-SEW, NF800-HEW, NF800-REW, NF800-UEW NV800-SEW, NV800-HEW
2 Accessories
NF400-CW, NF400-SW, NF400-SEW, NF400-HEW, NF400-REW, NF400-UEW NV400-CW, NV400-SW, NV400-SEW, NV400-HEW, NV400-REW NF630-CW, NF630-SW, NF630-SEW, NF630-HEW, NF630-REW NV630-CW, NV630-SW, NV630-SEW, NV630-HEW
Note The dimensions in brackets are those for NF800-UEW. 6-f48 24 24
10
243[290]
225[265]
4 screws M6 or f7
4 screws M6 or f7
11
44 87
11
24 24
24 24
194[234]
8
24 24
5
6-f35
11
8 screws M4 Make these eight threaded holes in addition to the standard holes.
70 140
11
8 screws M4 Make these eight threaded holes in addition to the standard holes.
Load side The drilling size drawings show the dimensions viewed from the rear side.
125
6 Accessories
External Accessories
2
DInsulating D Barrier-Plug-in (BA-P) Table 6-31 Summary of dimensions Type name
Applicable model MCCB
ELCB
Dimensions (mm) A B
NV125-SEV/HEV NV250-CV/SV/HV/SEV/HEV
172
74.5
BAP-4SW
NF400-CW/SW NF400-SEW/HEW/REW/UEW NF630-CW/SW NF630-SEW/HEW/REW
NV400-CW/SW NV400-SEW/HEW/REW NV630-CW/SW NV630-SEW/HEW
178
74.5
NF800-CEW/SEW NF800-HEW/REW
NV800-SEW/HEW
172
74.5
215
74.5
Reference diagram
4 A
BAP-2SV
NF125-SEV/HEV NF125-SGV/LGV/HGV/RGV NF160-SGV/LGV/HGV NF250-CV/SV/HV NF250-SGV/LGV/HGV/RGV NF250-SEV/HEV
Quantity per breaker 2P 3P 4P
B
4
6
−
A
BAP-8SW NF1000-SEW NF1250-SEW
−
B
DEarth D fault preventing barriers (BA-G) Table 6-32 Summary of dimensions BAG-05SV3 BAG-1SV3 BAG-2SV3 BAG-4SW3
Applicable model MCCB NF32-SV NF63-CV/SV/HV
ELCB NV32-SV NV63-CV/SV/HV
NF125-CV/SV/HV
NV125-CV/SV/HV
NF125-SEV/HEV NF250-CV/SV/HV/SEV/HEV NF250-SEV/HEV/ZEV with MDU NF400-CW/SW/SEW/HEW/REW NF630-CW/SW/SEW/HEW/REW
NV125-SEV/HEV NV250-CV/SV/HV/SEV/HEV NV250-SEV/HEV with MDU NV400-CW/SW/SEW/HEW/REW NV630-CW/SW/SEW/HEW
BAG-4UW3
NF400-UEW
BAG-8SW3
NF800-CEW/SEW/SDW/HEW/REW
Dimensions (mm) A B 30
75
40
90
63
105
63
164
−
63
164
NV800-SEW/HEW
110
210
BAG-8UW3
NF800-UEW
−
110
210
BAG-10SW3
NF1000-SEW NF1250-SEW/SDW
−
98
210
BAG-16SW3
NF1600-SEW/SDW
−
150
300
Also the earth fault preventing barriers for 2- and 4-pole circuit breakers are available.
2 Accessories
6
126
Quantity per breaker 3P
Reference diagram
B
A
Type name
1
Earth fault preventing barrier (3 poles)
6 Accessories 2 External Accessories
5. Handle Lock Devices, Lock Covers, Auxiliary Handles, Card Holders (1) Handle Lock Devices (HL and HL-S) These devices are used to lock the circuit breakers in the ON or OFF position. If overcurrent flows while the circuit breaker is locked, it will trip. Model HL (red resin moldings) to be fitted to handles and Model HL-S to be secured on circuit breaker covers are available. (Use a commercially available padlock having the nominal size shown in the right table. If a padlock in another size is used, the device may not lock correctly.)
Padlock size (mm) Application
Table 6-33 HL Applicable model
Type name
MCCB NF30-CS NF32-SV, NF63-CV/SV/HV NF125-CV/SV/HV/UV, NF125-SEV/HEV NF125-SGV/LGV/HGV/RGV NF160-SGV/LGV/HGV NF250-CV/SV/HV/UV, NF250-SEV/HEV NF250-SGV/LGV/HGV/RGV NF32-SV, NF63-CV/SV/HV NF125-CV/SV/HV/UV, NF125-SEV/HEV NF125-SGV/LGV/HGV/RGV NF160-SGV/LGV/HGV NF250-CV/SV/HV/UV, NF250-SEV/HEV NF250-SGV/LGV/HGV/RGV NF125-SVU/HVU NF250-SVU/HVU
HLN-05SV
HLF-05SV
HLF-05SVU HLF-2SWU HL-4CW HL-4SW HL-4SWU HL
NV32-SV, NV63-CV/SV/HV NV125-CV/SV/HV, NV125-SEV/HEV NV250-CV/SV/HV, NV250-SEV/HEV
40
22 or 23
5.5
C
B
a
Fig. 1
Fig. 1
Padlock
− − NV400-CW NV400-SW/SEW/HEW/REW NV630-CW/SW/SEW/HEW NV800-SEW/HEW − −
Fig. 2
Fig. 2
Fig. 3
c
Fig. 3
Number of poles
2P
−
−
2P
−
−
3P
NV32-SV, NV63-HV
4P
− NV125-CV, NV125-SV, NV125-HV − NV125-SV, NV125-HV − −
3P
NF125-HV NF125-SV, NF125-HV
2P, 3P 4P 2P, 3P 4P
NF125-SGV/LGV/HGV/RGV NF160-SGV/LGV/HGV NF250-CV, NF250-SV, NF250-HV NF250-SGV/LGV/HGV/RGV NF125-SEV, NF125-HEV NF125-SGV/LGV/HGV/RGV NF160-SGV/LGV/HGV NF250-CV, NF250-SV, NF250-HV (*1) NF250-SEV, NF250-HEV NF250-SGV/LGV/HGV/RGV NF125-SEV, NF125-HEV NF125-SGV/LGV/HGV/RGV NF160-SGV/LGV/HGV NF250-SV, NF250-HV, NF250-SEV, NF250-HEV NF250-SGV/LGV/HGV/RGV
HLS-05SVU HLS-2SVU HLS-2SWU HLS-4SW
(*3)
HLS-4UW HLS-8SW
(*3) NF400-UEW (*3) NF800-CEW/SDW/SEW/HEW/REW NF400-UEW (*3) NF800-UEW
NF400-CW/SW/SEW/HEW/REW NF630-CW/SW/SEW/HEW/REW
Dimensions (mm) ELCB
NF125-CV, NF125-SV
(*1) NF50-SVFU (*1) NF100-CVFU (*1) NF100-CVFU NF125-SVU/HVU (*2) NF125-SVU/HVU (*1) NF250-SVU/HVU (*1) NF225-CWU
HLS-8UW
5
c
Remarks 1. One lot of HL-4CW and HL-4SW contains one piece, and one lot of others contains 10 pieces. 2. HLF types are used for OFF lock, and HLN types for ON lock.
NF32-SV, NF63-CV, NF63-SV (*1) NF63-HV NF125-CV, NF125-SV NF32-SV, NF63-CV, NF63-SV NF63-HV NF63-SV,NF63-HV
NF250-UV HLS-03SVU HLS-05SVU2 HLS-05SVU
19
NV125-SVU/HVU NV250-SVU/HVU
Applicable model Number of poles
NF125-UV
HLS-2SV
11
35
Fig. 4
MCCB
(*1)
25
b
Padlock
Fig. 4
Table 6-34 HL-S
HLS-05SV
4
a
A
Notes *1 When a padlock is not used, the device can be used as a lock cover (LC). *2 Place an order for a circuit breaker body combined with the device.
HLS-05SV2
C
NV32-SV, NV63-CV/SV/HV NV125-CV/SV/HV, NV125-SEV/HEV NV250-CV/SV/HV, NV250-SEV/HEV
NF225-CWU (*1) NF400-CW NF400-SW/SEW/HEW/REW/UEW (*1) NF630-CW/SW/SEW/HEW/REW NF800-CEW/SDW/SEW/HEW/REW/UEW NF400-SWU/HWU, NF630-SWU/HWU (*2) NF1000-SEW, NF1250-SEW/SDW, NF1600-SEW/SDW
Type name
B
A
B
57 75
32
E
F
− 32
23
86 62.5
28 − 28
1.5 Fig. 5
NV125-SEV, NV125-HEV NV250-CV, NV250-SV, NV250-HV NV250-SEV, NV250-HEV
−
3P
63 32
32 84
4P 2P, 3P 4P 2P, 3P 2P 3P 2P, 3P 2P, 3P 3P 3P
NV125-SEV, NV125-HEV NV250-SV, NV250-SEV, NV250-HEV − − NV50-SVFU
− NV100-CVFU NV125-SVU/HVU NV125-SVU/HVU NV250-SVU/HVU − NV400-CW/SW/SEW/ HEW/REW 2P, 3P, 4P NV630-CW/SW/SEW/ HEW 3P − 2P, 3P, 4P NV800-SEW/HEW 4P − 3P, 4P
Notes *1 For locking in OFF position *2 A, B, C and D in Figs. 5 and 6 are drilling sizes in front plate. *3 Terminal covers cannot be fitted.
6
−
2P
3P
Reference Padlock diagram
75
3P − 4P − −
D
50
3P −
C
2 Accessories
HL-05FH
Reference diagram
ELCB −
A (Nominal size)
100 b
4P − − 2P, 3P − 3P 3P 3P 3P 3P
33
69.5 −
−
32
75
32
75 84 84
− 50 75 86 86 100 100
− 33 −
-5.5 Fig. 9 32
−
Fig. 5
−
32
Fig. 5
−
32
Fig. 6
3P, 4P
−
−
−
−
−
−
− 3P, 4P
− −
− −
− −
− −
− −
− −
−
−
−
−
−
−
−
Fig. 7
Fig. 8
127
Padlock
36 cL
cL
32
B
F
R1
cL
E
cL
f5.5
E
B
C
C
A
A
B A
cL
B
F
A
cL
Circuit breaker Pan head tapping screw
cL
A
R1
Line side
1
Pan head tapping screw
R
R1
Circuit breaker
D
R
R1
C cL
B
cL
A
C
cL
1
C
External Accessories
2
B
6 Accessories
D
C
Load side
Fig. 5
72
Fig. 6
86
Circuit breaker
cL
Circuit breaker
cL
Spacer
F
40 210
Load side
43.5
Fig. 9
Fig. 8
O
(3) Auxiliary Handles (HT)
Lock Cover is a plug-in lock for indicating easily without using padlocks that it is prohibited to operate the circuit breaker. A “Caution” tag can be hung on it. The covers are red resin moldings.
These handles facilitate opening and closing circuit breakers. Table 6-36 HT
(*1)
Table 6-35 LC
LC-05SV
Applicable model MCCB NF30-CS NF32-SV NF63-CV/SV/HV NF125-CV/SV/HV/UV NF125-SEV/HEV NF125-SGV/LGV/HGV/RGV NF160-SGV/LGV/HGV NF250-CV/SV/HV/UV NF250-SEV/HEV NF250-SGV/LGV/HGV/RGV
LCBH1R (red) BH-P(1P) LCBH1Y (yellow) LCBH2R (red) BH-P(2P) LCBH2Y (yellow) LCBH3R (red) BH-P(3P) LCBH3Y (yellow)
HT-4CW
ELCB −
NV32-SV NV63-CV/SV/HV NV125-CV/SV/HV NV125-SEV/HEV NV250-CV/SV/HV NV250-SEV/HEV
LCBH1
LCBH2, 3
Applicable model
Dimensions B C D
A
Auxiliary Handles Outline dimension drawing
E
77.5
NF400-CW, NV400-CW
NF400-SW/SEW/HEW/REW/UEW NF630-CW/SW/SEW/HEW/REW 59 NF800-CEW/SDW/SEW/HEW HT-4SW (*1) NF800-REW/UEW (*2) NV400-SW/SEW/HEW/REW NV630-CW/SW/SEW/HEW NV800-SEW/HEW NF1000-SEW 62 HT-10SW NF1250-SEW/SDW NF1600-SEW/SDW
fD
81
32
38
M4
118
34
45
M4
C
A
E screw
Notes *1 HT can be supplied separately. The user can fit it to the circuit breaker. (One lot contains 1 piece.) *2 1-pole circuit breakers with 800A frame and 4-pole NF400-UEW come with auxiliary handles as standard accessories.
− −
(4) Card Holders (CH)
−
Cards showing the circuit breaker name and circuit number can be inserted to the card holder. Fit the card holder to the circuit breaker body or the flush plate in the flush frame. (Although a card holder is supplied with each circuit breaker body, the card holder is available as an optional part.)
Remark: 1. One lot of LCBH, LCBL and LCNVL contains 50 pieces, and one lot of other models contains 10 pieces.
A
Table 6-37 Card holder size (mm)
B
Applicable model
128
N
B
Type name LC-05SW to LC-2SW
C
2 Accessories
E
128.5
cL
(2) Lock Covers (LC)
LC03CS
Circuit breaker
22.5
43.5
Type name
36
Pan head screw
Line side
Fig. 7
6
20
cL
22.5 138
cL
71
73.5 109.5
48
cL
103
109.5
115.5
116.5
20 cL
Type name
NF250-SV or below CH-P No.5 NV250-SV or below NF400-SW or above CH-P No.3 NV400-SW or above
A
B
C
Card size
44
12
5
39×9
38
22
5
33×20
6 Accessories 2 External Accessories
6. Mechanical Interlocks (MI)
This mechanical interlock device is used to enable one of two circuit breakers to turn on. Install the device on the panel. Mechanical interlocks to be installed directly to circuit breaker bodies can be manufactured. Consult us for details.
DFront, D rear and plug-in types
Front, rear and plug-in types (Panel mounting)
Center of mechanical interlock Center of circuit breaker
70(100)
70
A
C
15.5 (20)
31(40)
15
47.5
Stroke
CL
CL
45
Circuit breaker
CL
Circuit breaker
CL
CL
CL
CL
CL
CL
P
P
The values in parentheses apply to NF1600-SEW, NF1600-SDW
Center of mechanical interlock
F
F
120
M40.7 or f5 screw
F
F M40.7 or f5 screw
120
Drilling Dimension Diagram
Drilling Dimension Diagram
Drilling Dimension Diagram (breaker mount)
Fig. 1
Fig. 2
Fig. 3
Applicable model
Pitch (P) (*1)
−
NF32-SV, NF63-CV/SV/HV
NV32-SV, NV63-CV/SV/HV
NF125-CV/SV NF125-CV/SV/HV NF125-UV NF125-SEV/HEV NF125-SGV/LGV/HGV/RGV NF160-SGV/LGV/HGV NF250-CV/SV/HV, NF250-SEV/HEV NF250-SGV/LGV/HGV/RGV NF250-UV
− NV125-CV/SV/HV −
NF225-CWU
NV125-SEV/HEV NV250-CV/SV/HV NV250-SEV/HEV
Standard Type name 2P 120 MI-05SV3 − MI-05SV3
3P − 120
120
−
−
120
Dimensions (mm)
Semi-standard Standard 3P Type name 4P − − − − 120 − 130 MI-05SV4 (*4) − − − − 130
150
MI-1SV4
t
130 (*4)
NF400-CW/SW/SEW/HEW/REW NV400-CW/SW/SEW/HEW/REW NF630-CW/SW/SEW/HEW/REW NV630-CW/SW/SEW/HEW NF400-UEW (3P) − NF800-CEW/SDW/SEW/HEW/REW NV800-SEW/HEW NF400-UEW (4P) − NF800-UEW NF1000-SEW, NF1250-SEW/SDW − NF1600-SEW/SDW −
Breaker mount (*3) Type name 2P•3P MI-05SVFB2
A
B
C
D
E
15
33
63
47.5
58
15
33
63
−
58
MI-05SVFB3
15 15 15
33 33 33
63 63 32.5
45
58 58 58
MI-1SVFB2 MI-1SVFB3 −
−
(Fig. 3)
−
(*2) − 120 (*4)
MI-05SV3
150
180
MI-2SV4
150 (*4)
15
33
−
−
−
−
15
33
MI-4SW4
250
−
−
− −
Reference diagram
Notes *1 For 400A frame or above, use a panel 1.6 to 3.2 thick. *2 When the panel is 2.3 or more thick, countersink the panel (rear side) in f9.5 for the four f5.5 holes.
Table 6-38 Table of variable dimensions
ELCB (*6)
M6 or f7 screw
P
63
−
58
−
58
MI-2SVFB3 (Fig. 3) (Fig. 1)
25.5 MI-05SWU3
−
190
MI-4SW3
MI-8SW3 MI-10SW3 MI-16SW3
120 (*4)
−
190 220
−
220 220 315
−
210
−
240
MI-8SW4
290
− −
− −
MI-10SW4 MI-16SW4
290 426
47.5
33
83.5
−
47.5
33
60
47.5 47 37.5 65 54.5 39
−
−
−
−
MI-4SWFB3
74
83.5 83.5
(*2) −
2.3 (*5)
63
− (Fig. 3) MI-8SWFB3 −
74
− −
− −
6
− (Fig. 2)
− −
−
Notes *1 Specify the circuit breaker mounting pitch (P). *2 No need to specify the panel thickness (t). (Usable panel thickness range: t = 1~3.2mm. Above 400AF, use panel thickness t = 1.6~3.2mm) *3 Terminal covers cannot be fitted. (However, TCL-4SW3 can be fitted.) *4 When UVT is provided, separately install the module. *5 If the thickness is not 2.3, specify the panel thickness (t). *6 For NV with TBL, use a circuit breaker with MG. Remarks 1. When a mechanical interlock is installed on the panel, screw type terminal covers cannot be installed. 2. These devices do not provide an isolation function. However, 400, 600, 630 and 800A frame circuit breakers can be made conforming to it. (See Note 3.) 3. On a 2-pole circuit breaker obtained by removing the neutral pole conductor from a 3-pole circuit breaker, the mechanical interlock can be installed in the same manner as on a 3-pole circuit breaker.
129
2 Accessories
D
NF32-SV, NF63-CV/SV/HV
Stroke
94.5
61
H
43.5
43.5
Stroke
Outside Dimension Diagram
Center of mechanical interlock Center of circuit breaker
Center of mechanical interlock
Mechanical interlock P mounting plate
Reference diagram (3P)
C
15.5
15
50(80)
MCCB
P 190 260
120
Machine this part according to the 4f (f5.5 and f7.5 front plate drilling dimensions countersunk (rear) of the main breaker use M50.8 flat countersunk head screws (*2)
Center of circuit breaker
G 194 243
Mechanical interlock
Mechanical interlock mounting plate 120
Mechanical interlock mounting plate
111
1.5
Outside Dimension Diagram
Machine this part according to the front plate drilling dimensions of the main breaker
F 44 70
Circuit breaker
G
B
B
31
Type name MI-4SWFB3 MI-8SWFB3
Mechanical interlock
1.5 (Gap between circuit breaker and panel)
Outside Dimension Diagram
50
H 61 75 61 61
Panel plate thickness (t1.6 to 3.2)
Stroke
J
(Gap between circuit breaker and panel)
4f (f5.5 and f7.5 countersunk (rear) use M50.8 flat countersunk head screws (*2)
G 111 111 111 126
Circuit breaker
Panel plate thickness (t1 to 3.2) (*1)
Stroke
F 25 25 30 35
Mechanical interlock
Center of circuit breaker
A
Terminal covers cannot be fitted.
Type name MI-05SVFB3 MI-05SWHFB3 MI-1SVFB3 MI-2SVFB3
J 47.5 45
Type name MI-05SVFB2 MI-1SVFB2
G
Center of mechanical interlock
Breaker mountiong (front)
44(55)
22(30)
22
E
44
Front, rear and plug-in types (Panel mounting) These interlocks can be locked with padlocks.
6 Accessories
External Accessories
2
7. Boxes for Circuit Breakers and Boxed Circuit Breakers (1) Kinds and specifications Table 6-39 Dust-proof type (I)
Water-proof type (W)
–
–
–
NFI-05SV
–
NFI-1SV
– – NFW-05SV – NFW-1SV NFW-1HV
–
NFI-2SV
Closed type (S)
Appearance
(*1)
NF30-CS NF32-SV, NF63-CV/SV/HV
MCCB (*2)
NF125-CV/SV NF125-HV NF125-SGV/LGV NF160-SGV/LGV NF250-SGV/LGV NF250-CV/SV, NF125/250-SEV NF125/160/250-HGV NF250-HV, NF125/250-HEV NF400-CW NF400-SW/SEW NF630-CW/SW/SEW NF800-CEW/SDW/SEW
ELCB (*2)
NV32-SV, NV63-CV/SV/HV NV125-CV/SV NV125-HV NV250-CV/SV, NV125/250-SEV NV250-HV, NV125/250-HEV NV400-CW NV400-SW/SEW NV630-CW/SW/SEW NV800-SEW Operating method Standard paint color Protection class (IEC 60529)
Notes *1 *2 *3 *4 *5 Remarks:
2 Accessories
6
2, 3P 2P 3P 2P 3P 2, 3P
NFS-03CS NFS-05SV2 (*5) NFS-05SV NFS-1SV2 (*5) NFS-1SV
NFS-2SV 2, 3P
2P 3P
3P
(*1)
NFW-2SV
– – – NFI-4CW NFW-4CW – – NFI-4SW NFW-4SW – – NFI-6SW NFW-6SW – – NFI-8SW NFW-8SW NFS-05SV – – NFI-05SV NFS-05SV NFW-05SV NFS-1SV NFW-1SV – NFI-1SV NFS-1SV NFW-1HV NFS-2SV – NFI-2SV NFW-2SV – – – NFI-4CW NFW-4CW – – NFI-4SW NFW-4SW – – NFI-6SW NFW-6SW – – NFI-8SW NFW-8SW Operation through operating handle mechanism Direct operation of circuit breaker handle Box: Munsell 5Y7/1 Operating handle: Munsell N1.5 IP3X IP65 (*4) IP4X (*3)
The window frame varies depending on the model. For 1-pole circuit breakers, boxes are not manufactured. The protection class of NFI-1SV and NFI-2SV is IP3X. The protection class of NFW-4CW, NFW-4SW, NFW-6SW and NFW-8SW is IP54. The circuit breaker body is a 2-pole external type. 1. Only internal accessories with lead wires drawn out can be fitted. (However, LT and SLT can be fitted on the right pole side.) 2. The dust-proof type (I) models do not provide an isolation function.
d Selection of rated current When selecting the rated current of circuit breaker, it is necessary to consider the temperature in the box. When the rated current is carried, the temperature in the box increases by 10 to 20K. Correct the rated current with the temperature correction curve. Determine the maximum working current to be 80% or less of the rated current. d Locking Type I and W boxed circuit breakers can be provided with locks in the following parts. Locking can prevent unnecessary operation. qCover and case wON or OFF position of operating handle Padlocks must be prepared by the user. The dimensions of the padlocks are shown on page 116.
d Interlock (only for Dust-proof type) The cover cannot be opened while the circuit breaker is in the ON state. However, if the interlock release screw is turned, the cover is released from the locked state and can be opened even in the ON state. d Handle operation and display The ON, OFF or trip state of the body is displayed on each position on the decorative board.
Example of Type I operating handle block
130
6 Accessories 2 External Accessories
(2) External dimensions JMCCB J 4 mounting holes fG (key slot)
A
E A
E
4 mounting holes fG
D
F
Screw M6 Earth terminal
D
F B
B
C
K, hole
NFI-05SV NFI-1SV,NFI-2SV
··············································2 pcs. on bottom
NFI-4CW to NFI-8SW······
H
K, hole ···2 pcs. on bottom
630A or below: 2 pcs. on each of top and bottom 800A: 3 pcs. on each of top and bottom
J
H
Fig. 3 Type I
Fig. 1 Type S
4 mounting holes fG
4 mounting holes fG
F B
E A
E A
E
3 mounting holes fG (key slot)
A
J
Earth terminal
C
D
Screw M6 Earth terminal
F
D
B
C
D C
F B
C
K socket 630A or below: 1 pc. on each of top and bottom 800A: 2 pc. on each of top and bottom H
H
K, hole ···2 pcs. on bottom
J
H
Fig. 2 Type S
K socket, 1 pc. on each of top and bottom
Fig. 4 Type W
Table 6-40 Table of variable dimensions (Boxes for 4-pole circuit breakers are not manufactured.) Box type
S
Type name NFS-03CS NFS-05SV2 NFS-05SV NFS-1SV2 NFS-1SV NFS-2SV NFI-05SV NFI-1SV NFI-2SV
I NFI-4CW NFI-4SW NFI-6SW NFI-8SW NFW-05SV NFW-1SV NFW-1HV
W
NFW-2SV NFW-4CW NFW-4SW NFW-6SW NFW-8SW
Applicable Model NF30-CS NF32-SV, NF63-CV/SV/HV NF125-CV/SV NF125-CV/SV/HV NF250-CV/SV, NF125/250-SEV NF125-SGV/LGV NF160-SGV/LGV NF250-SGV/LGV NF32-SV, NF63-CV/SV/HV NF125-CV/SV/HV NF250-CV/SV/HV, NF125/250-SEV/HEV NF125-SGV/LGV/HGV NF160-SGV/LGV/HGV NF250-SGV/LGV/HGV NF400-CW NF400-SW/SEW NF630-CW/SW/SEW NF800-CEW/SDW/SEW NF32-SV, NF63-CV/SV/HV NF125-CV/SV NF125-HV NF250-CV/SV/HV, NF125/250-SEV/HEV NF125-SGV/LGV/HGV NF160-SGV/LGV/HGV NF250-SGV/LGV/HGV NF400-CW NF400-SW/SEW NF630-CW/SW/SEW NF800-CEW/SDW/SEW
Fig. 5 Type W
Earth terminal
Note) The sockets are applicable to thick steel duct (JIS C 8305) and conduit tube thread.
Variable dimensions E F G 150 78 6
Fig. 2
A 188
B 158
C 69
D 58
H 25
J 100
K 20, 28
1
260
178
98
78
202
100
7
34
100
28, 35, 44
1
310
178
98
78
252
100
7
34
100
28, 35, 44
1
440
247
137
116
373
170
9
52
120
50, 62, 78
3 3
350 352
186 188
155.5 155.5
117 118
286 286
120 120
7 7
42 42
100 100
28, 35, 44 28, 35, 44
3
442
248
162
124
373
170
9
54
120
50, 62, 78
3 3 3 3 4 4 4
730 730 940 1353 390 390 480
320 320 433 543 265 265 265
244 244 260 304 214 214 239
191 191 207 251 160 160 186
650 650 856 1270 350 350 440
240 240 350 460 225 225 225
11 11 15 15 9.5 9.5 9.5
87 65 90 90 45 50 60
120 120 150 320 – – –
50, 62, 78 50, 62, 78 92 104 28 36 36
4
550
355
264
210
510
315
11
75
–
54
5 5 5 5
800 800 800 1435
355 355 355 550
257 257 257 339
220 220 220 265
760 760 760 1395
315 315 315 515
11 11 11 15
85 85 85 100
– – – 180
70 70 82 104
131
6 2 Accessories
J
6 Accessories JELCB J
External Accessories
2
3 mounting holes fG
4 mounting holes fG
E A
A
E
A
E
4 mounting holes fG
D
F D C
Earth terminal
NFI-05SV NFI-1SV NFI-2SV
D C
F B
········2 pcs. on bottom 630A or below: 2 pcs. on each of top and bottom
NFI-4CW to NFI-8SW······· 800A: 3 pcs. on each of top and bottom
H
J
H
J
Earth terminal
K, hole: 2 pcs. on each of top and bottom
Fig. 5 Type W
Fig. 3 Type I
Fig. 1 Type S 3 mounting holes fG (key slot) (NVS-03CS) 4 mounting holes fG (key slot)
4 mounting holes fG
E
A
E
K socket 630A or below: 1 pc. on each of top and bottom 800A: 2 pc. on each of top and bottom
A
J
Earth terminal
K, hole
H
F B
C
B
Screw M6 Earth terminal F B
D C
F
D
B
C
H
K, hole: 2 pcs. on bottom
J
Fig. 4 Type W
H
Fig. 2 Type S
K socket, 1 pc. on each of top and bottom
Table 6-41 Table of variable dimensions (Boxes for 4-pole circuit breakers are not manufactured.) Box type
S
2 Accessories
6
I
W
132
Type name NFS-05SV2 NFS-05SV NFS-1SV2 NFS-1SV NFS-2SV NFI-05SV NFI-1SV NFI-2SV NFI-4CW NFI-4SW NFI-6SW NFI-8SW NFW-05SV NFW-1SV NFW-1HV NFW-2SV NFW-4CW NFW-4SW NFW-6SW NFW-8SW
Applicable Model NV32-SV, NV63-CV/SV/HV NV125-CV/SV NV125-CV/SV/HV NV250-CV/SV, NV125/250-SEV NV32-SV, NV63-CV/SV/HV NV125-CV/SV/HV NV250-CV/SV/HV, NV125/250-SEV/HEV NV400-CW NV400-SW/SEW NV630-CW/SW/SEW NV800-SEW NV32-SV, NV63-CV/SV/HV NV125-CV/SV NV125-HV NV250-CV/SV/HV, NV125/250-SEV/HEV NV400-CW NV400-SW/SEW NV630-CW/SW/SEW NV800-SEW
Note) The sockets are applicable to thick steel duct (JIS C 8305) and conduit tube thread.
Variable dimensions E F G
Fig.
A
B
C
D
H
J
K
2
260
178
98
78
202
100
7
34
100
28, 35, 44
2
310
178
98
78
252
100
7
34
100
28, 35, 44
2 3 3 3 3 3 2 3 4 4 4 4 5 5 5 5
440 350 352 442 730 730 940 1353 390 390 480 550 800 800 800 1435
247 186 188 248 320 320 433 543 265 265 265 355 355 355 355 550
137 155.5 155.5 162 244 244 260 304 214 214 239 264 257 257 257 339
116 117 118 124 191 191 207 251 160 160 186 210 220 220 220 265
373 286 286 373 650 650 856 1270 350 350 440 510 760 760 760 1395
170 120 120 170 240 240 350 460 225 225 225 315 315 315 315 515
9 7 7 9 11 11 15 15 9.5 9.5 9.5 11 11 11 11 15
52 42 42 54 87 65 90 90 45 50 60 75 85 85 85 100
120 100 100 120 120 120 150 320 − − − − − − − 180
50, 62, 78 28, 35, 44 28, 35, 44 50, 62, 78 50, 62, 78 50, 62, 78 92 104 28 36 36 54 70 70 82 104
6 Accessories 2 External Accessories
8. Electrical Operated Circuit Breakers and Electrical Operation Devices
Spring charge type (2) Standard paint color: Munsell 5Y7/1
(1) Specifications DElectrically D operated circuit breakers
Specify the electrical operation device together with the circuit breaker body.
Table 6-42
Electrically operating method
Class S, H and R
MCCB
NF125-CV NF250-CV
Class C Class U Motor breakers
Class S, H and R ELCB
Spring charge type (1) NF125-SV, NF125-HV NF125-SEV, NF125-HEV NF125-SGV/LGV/HGV/RGV NF160-SGV/LGV/HGV NF250-SV, NF250-HV NF250-SEV, NF250-HEV NF250-SGV/LGV/HGV/RGV NF125-RV, NF250-RV
NF125-UV NF250-UV NF125-SV, NF250-SV NV125-SV, NV125-HV NV125-SEV, NV125-HEV NV250-SV, NV250-HV NV250-SEV, NV250-HEV
Motor-drive type (2) Standard paint color: Munsell 5Y7/1
Spring charge type (2) NF400-SW, NF400-SEW NF400-HEW, NF400-REW NF630-SW, NF630-SEW NF630-HEW, NF630-REW NF800-SDW, NF800-SEW NF800-HEW, NF800-REW NF400-CW NF630-CW NF800-CEW NF400-UEW NF800-UEW
Motor-drive type (2) NF400-SW, NF400-SEW NF400-HEW, NF400-REW NF630-SW, NF630-SEW NF630-HEW, NF630-REW NF800-SDW, NF800-SEW NF800-HEW, NF800-REW
NF1000-SEW NF1250-SEW NF1250-SDW NF1600-SEW NF1600-SDW
− − −
NV400-SW, NV400-SEW NV400-HEW, NV400-REW NV630-SW, NV630-SEW NV630-HEW, NF800-SEW NV800-HEW
−
−
NV125-CV NV400-CW − NV250-CV NV630-CW Motor breakers NV125-SV, NV250-SV − − Compatible with 100 to 240 V Rated operating voltage (V) DC100-110, AC100-110 (Allowable operating voltage range: AC and 100 to 250 V DC AC200-220(DC125, AC240) 24 V DC, 48 to 60 V DC (*1) 85 to 110%) ON 8 10 0.5 (1.5) Operating DC 100/110V OFF 1.0 (3.0) 1.0 (4.0) current ON 10 10 (Ams) 100/110V 0.6 (3.0) Values in OFF 1.0 (3.0) 1.0 (3.0) ( ): Starting AC ON 8 8 current 200/220V 0.5 (2.5) OFF 0.5 (1.5) 0.5 (1.5) ON 0.05~0.1(*2) 0.05 0.07 Operating s OFF 0.6 or less (self-holding type) time 3 or less (self-holding type) Charge 1.2 or less (self-holding type) Required transformer capacity VA 150 700 Endurance voltage 1500V Class C
NF1000-SEW NF1250-SEW NF1250-SDW NF1600-SEW NF1600-SDW
NF400-CW NF630-CW NF800-CEW NF400-UEW NF800-UEW
− −
− NV400-SW, NV400-SEW NV400-HEW, NV400-REW NV630-SW, NV630-SEW NV630-HEW, NF800-SEW NV800-HEW (*3) NV400-CW(*3) NV630-CW −
−
−
− −
DC100-110, AC100-110, AC200-220 (DC125, AC240) 3.0(8.0)
5.0(13.5)
4.0(8.0)
5.0(10.0)
2.0(4.5)
3.5(7.0)
6
0.3 or less (self-holding type) − 400
− 700
1500V
Notes *1 When the rated operating voltage is 24 V DC or 48 to 60 V DC, specify the voltage. If the voltage is not specified, the circuit breaker will be manufactured for 100 to 240 V AC and 100 to 250 V DC. *2 For 24-V DC circuit breakers, the operating time at a voltage of 100% or more is shown. *3 Models for special voltage (125 V DC or 240 V AC) are not provided with the test button. Remarks 1. Flush plate type circuit breakers can be manufactured to order. 2. The models with voltage in parentheses are special voltage products. 3. For the spring charge type (1), use an ON-OFF operating switch for minute load. 4. For the spring charge type (1) The circuit breaker of 3 pole can be used TC-S, TC-L, TTC, BTC and PTC. In case of 125A frame 4 pole can be used only TC-L. In case of 250A frame 4 pole can be used TC-S, TC-L, TTC, BTC and PTC. 5. When the body of the spring charge type (1) breaker is an earth leakage alarm breaker, the reset button cannot be pressed. Provide such a circuit breaker with an external reset or automatic reset system (except for the electronic type). 6. When the body of the motor-drive type (2) or spring charge type (2) has internal accessories, they are normally provided with lead wire terminal blocks. 7. The types other than the spring charge type (1) do not provide an isolation function. 8. When placing an order for a CE marked product of the spring charge type (1) or spring charge type (2), specify the model name with CE. 9. The switching durability of electrically operated circuit breakers conforms to JIS.
DElectrical D operation devices Table 6-43 Electrically operating method Applicable models Rated operating voltage
The following models of Electrical Operation Devices are supplied also as separate devices. The user can install them to the circuit breaker body. (Front connection, rear connection and plug-in types) (When requiring a motor breaker or a CE marked product, place an order for it together with the circuit breaker body.) Spring charge type (1) NF125-SEV/HEV/SGV/LGV/HGV/RGV NF160-SGV/LGV/HGV NF250-CV/SV/HV/UV/SEV/HEV/SGV/LGV/HGV/RGV NF250-UV
NV250-CV/SV/HV
NV125-SEV/HEV NV250-SEV/HEV
MDSAD240-NF2SVE
MDSAD240-NV2SVE
MDSAD240-NVE2SVE
MDSD024-NV1SVE
MDSD024-NF2SVE
MDSD024-NV2SVE
MDSD024-NVE2SVE
MDSD060-NV1SVE
MDSD060-NF2SVE
MDSD060-NV2SVE
MDSD060-NVE2SVE
NF125-CV/SV/HV
NV125-CV/SV/HV
Compactible to 100-240VAC/100-250VDC
MDSAD240-NF1SVE
MDSAD240-NV1SVE
24VDC
MDSD024-NF1SVE
48-60VDC
MDSD060-NF1SVE
133
2 Accessories
Spring charge type (1)
6 Accessories
External Accessories
2
DCautions D
DDAll electrical operations are based on intermittent rating. Avoid operating any device continuously 10 times or more (ON and OFF operations are counted as one time). DDOperate any device at 85 to 110% of the rated operating voltage. DDThe dielectric strength of electrical operation circuits is 1500 V. When performing dielectric strength test of any of these devices and other devices, if the test voltage exceeds the rated value (1500 V), disconnect the operation power supply terminal. DDWhen collectively operating more than one electrical operation device, isolate the devices connecting a relay to each device. If the control terminals are directly connected in parallel, a circuit will be formed, and the devices may not normally function.
DAutomatic D reset (optional)
The automatic reset type has a built-in alarm switch in the circuit breaker and is connected in such a way that the OFF operation circuit is closed when the circuit breaker trips. Therefore, when the circuit breaker trips, it is automatically reset. However, when the circuit breaker thermally trips, it may not be automatically reset. If an automatic reset spring charge type (1) is required, the user must wire the device in accordance with the external connection diagram shown in Fig. 1 in (3).
(2) Installation and connection (List of manufacturable) Table 6-44 Frame (A)
Installation and connection method 50~250 400~800 1000, 1250 1600
2 Accessories
6
Front connection type
Rear connection type
Plug-in type
−
(*1) (*2)
Notes *1 For ELCB, only 3-pole circuit breakers with a frame size of 125 to 400 A can be manufactured. *2 In the case of 4-pole 125 A frame circuit breakers and U class, the circuit breakers are supplied as special models. Consult us for details. Remarks: 1. All models of the front connection type are provided with bar terminals (except the spring charge type (1)). 2. 2-pole circuit breakers of all models are obtained by removing the neutral pole conductors from 3-pole circuit breakers.
times. Then, the circuit breaker will be turned off (reset), and, at the same time, the closing spring will be charged. Although the circuit breaker can be turned off even if the switch is not turned to MANUAL, the selection switch should be set to MANUAL because remote operation may be accepted. · After turning the changeover switch to MANUAL, draw out the OFF lock plate, and lock the circuit breaker in the OFF state with padlocks (to be prepared by the user). Up to three padlocks can be fitted. f5 to f8 padlocks can be fitted. Note: After the completion of manual operation (on-site operation), return the selection switch to AUTO without fail. If it is not returned, electrical operation (remote operation) cannot be performed. DDDisplay of tripping state When the circuit breaker trips in the ON state, the tripping state is displayed. When it trips in the OFF state, the OFF state is kept displayed. Note: When it trips in the OFF state, signals from AL will not be output. DDCautions for use q To the ON or OFF operation switch (to be prepared by the user), current only of 24 V DC and 15 to 30 mA flows. Use a switch for minute load. w Operate the operation switch for 0.1 s or more to turn on and for 20 ms or more to turn off. If it is operated for less than the time, it may not function. The wire to the operation switch shall be less than 100 m. e The power supply module has a built-in switching power supply. Therefore, it may interfere with communication devices near the module. In such a case, install a noise filter on the input side. r For the automatic reset type, purchase a circuit breaker with alarm switch (for minute load), and connect the signal circuit (among the terminal numbers S1, S2 and S4) as shown in Fig. 1. If the circuit breaker in the OFF state is tripped by UVT-N or the like, it cannot be automatically reset. To reset it, it is necessary to turn it on under no current. After this operation, it will be automatically reset.
(3) Structure and operation
Fig. 1
P1
Uc
P2 S1
ON OFF
S2
Power supply module
S4
AL (for minute load)
AL “a” (alarm switch for minute load)
charge type (1) JSpring J DDElectrical operation · When the ON operation switch is closed, the relay will operate, the motor will be driven, the latch mechanism will be released, and the closing spring force will instantaneously turn on the circuit breaker. · When the OFF operation switch is closed, the relay will operate, the motor will be driven, the circuit breaker will be turned off (reset), and, at the same time, the closing spring will be charged. Note: The charge may not be completed because the circuit protective function operates. DDManual operation · After turning the MANUAL/AUTO selection switch on the cover upper surface to MANUAL, press the ON button, and the latch mechanism will be released, and the closing spring force will instantaneously turn on the circuit breaker. · After turning the MANUAL/AUTO selection switch on the cover upper surface to MANUAL, draw out the manual handle, and move it upward and downward about 10 to 14
134
Operation circuit Power supply module Operating power Uc supply
P1 P2 S1
ON
Power supply circuit
Electrical operation base
M
Control circuit
SW1
SW1 MANUAL/AUTO selection switch SW2 Charge/Discharge detecting switch M
Motor
S2 SW2
S4 OFF (RESET) The circuit breaker is off, and the electrical operation device is in the charged state.
Symbol SW1 SW2 M
Interpretation of symbol MANUAL/AUTO selection switch Limit switch (For spring condition detection charge/discharge) Motor
Note *1 When power is applied, inrush current (capacitor charging current) of 60 A flows to the breaker and fuse installed on the power supply circuit for 1 ms or so. When selecting the breaker and fuse, make sure that they will not cause problems, such as blowout and malfunction.
6 Accessories 2 External Accessories
type (2) JMotor-drive J
DDElectrical operation Forward and reverse motor rotation is changed by ball screw to switch the breaker ON and OFF (reset). DDManual operation The manual operation handle can be used to switch the breaker ON and OFF directly. DDCautions for use
q In the case of a circuit breaker with UVT, if the circuit breaker trips owing to the operation of UVT, the procedure for re-closing the circuit breaker varies depending on the condition of the electrical operation device before the circuit breaker trips. • Tripping in ON state: Reset (OFF). → Turn on. • Tripping in OFF state: Turn on (idle tripping). → Reset (OFF). → Turn on. (If the circuit breaker cannot be turned on (idle tripping), reset (OFF) it, and turn on.) • When an automatic reset system is configured on a nonreset type circuit breaker with UVT, if UVT is set to the no-voltage state, the operations to turn off (reset), trip, turn off (reset) and trip are repeated.
Therefore, configure the circuit in such a way that power is disconnected from the electrical operation device before the circuit breaker is tripped by the non-reset type UVT. w Current of about 0.2 A will flow to the ON-OFF switch. Use an appropriate switch. e Do not apply ON and OFF operation signals continuously. An interval of 0.5 sec or more is necessary between ON and OFF signals. r In the case of the automatic reset type device, it will perform the reset operation with an interval of 0.5 sec after NFB performs the tripping action. t The electrical operation device has a built-in pumping preventing circuit. Therefore, it can operate to turn off the circuit breaker while the ON operation switch is held in the closing state, but it cannot turn on continuously after turning off. To turn on, once turn off the ON operation switch, and turn on the switch. Do not apply the ON operation signal continuously. y The manual operating handle moves at a high speed during electrical operation. Pay attention to the handle. Keep the operation circuit power supply off during manual operation. u In the manual operation, surely turn the manual operating handle to the position indicated on the nameplate.
DDOperation circuit ···· For the automatic reset type, the connections indicated with the dashed lines are added. circuit 1
Operation
NF400-CW~NF800-UEW NV400-CW~NV800-HEW Internal connection (when circuit breaker is off) G (Earth terminal) (DC-)
A1
R3
R4
R1
R2
Internal connection (when circuit breaker is off) G
Z2
(DC-)
M
Operating power supply
ON
B
OFF Reset
C
ALa
T1 T1b Z3
X X1
Y1
Z4a
Z4b R
A1
T1 A2
Y
Y2a
T2
ON
T2
OFF Reset
D
B
:
Motor
X
:
Relay for ON operation
Y
:
Relay for OFF operation
R
:
Motor driving relay
Z
:
X4
Y1
Y4
Y2
Z1
Y3
Z X
T1b
C
M
Z2
LS
Y
T2a T2
Alarm switch for automatic reset (a contact)
ALa
M
X1 X3
D
Alarm switch for automatic reset (a contact)
X2
(Earth terminal)
Operating power supply
Z1 LS
Z
A2
circuit 2
NF1000-SEW~NF1600-SEW
Z, K: Exciting coil of keep relay
: Motor field coil
(Operation circuit 3)
: Surge absorbing circuit
LS, LS1, LS2: Limit switches
: Surge absorber
X1~X4, Y1~Y4, Y2a, Z4a, Z4b, Z1, Z2, Z3, K1, T1b, T2a: Relay switches
Polarity switching relay
T1 : Pumping preventing timer
(Operation circuit 1 or 2)
T2 : Timer for automatic reset
6
(R1)~(R4): Relay switches
charge type (2) JSpring J
DDElectrical operation When the ON operation switch is closed, the closing coil will be excited to release the latch mechanism, and the closing spring force will instantaneously turn on the circuit breaker. When the OFF operation switch is closed, the relay will operate to start the motor, turn off (reset) the circuit breaker and, at the same time, charge the closing spring. DDManual operation • Press the ON button, and the latch mechanism will be released, and the closing spring force will instantaneously turn on the circuit breaker. • Turning off (resetting) Push the leaf spring, bring out the manual handle, and move the handle upward and downward more than ten times. Then, the circuit breaker will be turned off (reset), and, at the same time, the closing spring will be charged. DDCautions for use
q In Before installing or removing the electrical operation device to or from the circuit breaker, trip the circuit breaker, and discharge the electrical operation device. After the device is installed to the circuit breaker, the device will not trip the circuit breaker in the OFF state even if the trip button is pressed. This is not a trouble. The electrical operation device takes 3 seconds to turn off the circuit breaker. To open the circuit immediately by remote operation, use a circuit breaker with SHT or UVT. • The device has a built-in pumping preventing relay. w Current of about 9 A and 0.2 A will flow to the ON and OFF switches, respectively. Use appropriate switches.
Internal structure of spring charge type
Internal structure of motor-drive type
DDOperation circuit For the automatic reset type, the connections indicated with the dashed lines are added. Internal connection (when circuit breaker is off) LS3
CC : Coil for making
LS2 Y M X
X X
CC Y LS1
Y
Y
: Relay for pumping prevention
X
: Relay for self-sustaining on OFF side
LS1 : Limit switch interlocking with cam LS2 : Limit switch interlocking with cam LS3 : Limit switch interlocking with OFF lock plate M
G
P2
P1
Operating power supply (DC-)
S2 ON
S4 OFF RESET
: Motor
Alarm switch for automatic resetting (contact a)
135
2 Accessories
Operation
6 Accessories
2
External Accessories
9. Distribution Board Mounting Parts, Lock Covers and Handle Caps DBPA-type D mounting base (for BH-P) Three-phase-type Note: Single-phase tvpes have no central pole.
34
Solderless terminal for wire size : 125A 14~50mm2 250A 22~125mm2
A
86.5
21
21
Solderless terminal for wire size 22~60mm2
37.5
75
4.5
75
Mtg. holes 4.5 dia.
25
75 A
25
87
25 25 75
Single-phase-type
Max. no. of ways 6 9 12 15 18 24 30 36 42
2 Accessories
6
136
1ph, 2w Main : 125A BPA-1106 BPA-1109 BPA-1112 BPA-1115 BPA-1118 – – –
154 164
1ph, 3w Main : 125A BPA-2106 – BPA-2112 – BPA-2118 BPA-2124 – –
3ph, 4w Main : 250A – – – – BPA-2218 BPA-2224 BPA-2230 BPA-2236
Main : 125A BPA-3106 – BPA-3112 – BPA-3118 BPA-3124 – –
Main : 250A – – – – BPA-3218 BPA-3224 BPA-3230 BPA-3236 BPA-3242
Neutral terminal NT-06 – NT-12 – NT-18 NT-24 NT-30 NT-36 NT-42
6 Accessories 2 External Accessories
DMounting D plate (for BH) 13.5
38.5 (63.3)
16
Spring clip
36
11
9.5
11
0.8
10
) : 3P
d) Handle cap for 2-pole units
b) Lock cover for c) Handle cap for 1-pole 2-pole, 3-pole units units
a) Lock cover for 1-pole units
5-6 wide mtg. slot
11
33
34
(
86 116 Line side
57 22.5
5.6 25 × 32 = 800 ± 1
14
13
22.5
5 102
Mounting pitch 102 25 25
Line side
BH MCB (mm)
5.5ø mtg. holes
Breakoff undercut
Outlines and dimensions (mm)
59
Colors available
One mounting plate has 32 circuits. One package includes 10 mounting plates (320 circuits).
Fig. ref.
Item
a) b) b) c) d)
DLock D covers and handle caps (for 1-pole, 2-pole and 3-pole types) Many panelboards include some restricted-operation circuits, which must either normally remain on, such as all-night lighting or alarms, or must remain off, such as spare circuits, or circuits used in repair or construction work. Breakers for such circuits can be locked by simply installing a lock cover on the handle.
Poles 1 2 3 1 2
Lock cover Cap
ON
Red LCBH1R LCBH2R LCBH3R HC1R HC2R
OFF
Colors Yellow LCVH1Y LCBH2Y LCBH3Y HC1Y HC2Y
ON
Lock cover in place (1-pole unit)
Green – – – HC1G HC2G
OFF
Lock cover in place (2-pole unit)
10. IEC 35-mm Rail Mounting Adapters Table 6-45
DExternal D dimension
Applicable model MCCB
2, 3
NF30-CS
2, 3
NF32-SV NF63-CV/SV/HV
ELCB –
Fig.
IEC 35-mm rail mounting adapter
Fig. 1
Fig. 2
3.5
Remark: 1. Place an order in units of 10 pieces.
8
Fig. 1
2 Accessories
NV32-SV NV63-CV/SV/HV
35
DIN-05SV
6
3
(Note1)
35
DIN-03CS
Number of poles of circuit breaker
100
Type name
1
Fig. 2 Mounting hook for IEC 35mm rail [DIN-05SV]
137
2 Accessories
MEMO
6
138
7
Characteristics and Dimensions 1 Molded Case Circuit Breakers 140
3 UL 489 Listed Circuit Breakers 198
• NF30-CS…………………………………………………………… 140 • NF32-SV, NF63-CV/SV/HV……………………………………… 142 • NF125-CV/SV/HV… ……………………………………………… 144 • NF125-UV… ……………………………………………………… 146 • NF250-CV/SV/HV… ……………………………………………… 148 • NF250-UV… ……………………………………………………… 150 • NF125-SGV/LGV/HGV/RGV, NF160-SGV/LGV/HGV, NF250-SGV/LGV/HGV/RGV… ………………………………… 152 • NF125-SEV/HEV, NF250-SEV/HEV… ………………………… 154 • NF400-CW/SW… ………………………………………………… 156 • NF400-SEW/HEW/REW… ……………………………………… 158 • NF400-UEW… …………………………………………………… 160 • NF630-CW/SW… ………………………………………………… 162 • NF630-SEW/HEW/REW… ……………………………………… 164 • NF800-CEW/SEW/HEW/REW…………………………………… 166 • NF800-SDW… …………………………………………………… 168 • NF800-UEW… …………………………………………………… 170 • NF1000-SEW, NF1250-SEW… ………………………………… 172 • NF1250-SDW……………………………………………………… 174 • NF1600-SEW……………………………………………………… 176 • NF1600-SDW……………………………………………………… 178
• NF50-SVFU, NV50-SVFU… …………………………………… 198 • NF100-CVFU, NV100-CVFU… ………………………………… 200 • NF125-SVU/HVU, NV125-SVU/HVU…………………………… 202 • NF225-CWU… …………………………………………………… 204 • NF250-SVU/HVU, NV250-SVU/HVU…………………………… 206 • NF400-SWU/HWU………………………………………………… 208 • NF630-SWU/HWU………………………………………………… 210
2 Earth Leakage Circuit Breakers 180 • NV32-SV, NV-63CV/SV/HV……………………………………… 180 • NV125-CV/SV/HV… ……………………………………………… 182 • NV250-CV/SV/HV… ……………………………………………… 184 • NV125-SEV/HEV, NV250-SEV/HEV… ………………………… 186 • NV400-CW/SW… ………………………………………………… 188 • NV400-SEW/HEW/REW… ……………………………………… 190 • NV630-CW/SW… ………………………………………………… 192 • NV630-SEW/HEW………………………………………………… 194 • NV800-SEW/HEW………………………………………………… 196
4 Measuring Display Unit Breakers 212 • NF250-SEV/HEV with MDU……………………………………… 212 • NF400-SEP/HEP with MDU……………………………………… 214 • NF630-SEP/HEP with MDU, NF800-SEP/HEP with MDU… … 216
5 Miniature Circuit Breakers,
Residual Current Circuit Breakers, Residual Current Circuit Breakers with Overcurrent Protection and Isolating Switch 218
• BH,BH-P…………………………………………………………… 218 • BH-D6, BH-D10…………………………………………………… 219 • BH-DN……………………………………………………………… 220 • BV-D………………………………………………………………… 221 • BV-DN……………………………………………………………… 222 • KB-D………………………………………………………………… 223
6 Circuit Protectors
224
• CP30-BA…………………………………………………………… 224
7 Electrical Operated Cicuit Breakers 225
139
7
Characteristics and Dimensions
Molded Case Circuit Breakers
1
NF30-CS
Model
NF30-CS
Rated current In (A)
3, 5, 10, 15, 20, 30
Number of poles
2
3
Rated short-circuit breaking capacity (kA)
Rated insulation voltage Ui (V)
500 690V
IEC 60947-2 (Icu/Ics)
AC
−
500V
−
415V
1.5/1.5
380V
1.5/1.5
240V
2.5/2
Standard Attached Parts (Front connection)
Mounting screw: M4×0.7×20 (2pcs)
NF30-CS
Operating Characteristics 3h 2h Types NF30-CS
1h 40min 20min 10min 6min 4min 2min
Operating time
1min 40s 30s 20s
Max.
10s 6s 4s 2s 1s 0.6s 0.4s
Min.
0.2s 0.1s 0.06s 0.04s 0.02s 0.01s
1 1.25
2
3
4
5
7
10
Internal Accessories AL
External Accessories Terminal cover
1 Characteristics and Dimensions
70
100
Lead wire direction
AX
Remarks: 1. Standard lead wire is drawn from side. However, lead wire drawn by load can be produced upon request. 2. Refer to page 106.
Type name
Small
(TC-S) TCS-03CS3W (*1)
Large
(TC-L) TCL-03CS3W (*1)
Rear
(BTC) BTC-03CS3W (*1)
Skeleton
(TTC) TTC-03CS (*1)
Reference page
121
Handle lock
(HL) HL-05FH
127
Lock cover
(LC) LC03CS
128
(DIN) DIN-03CS
137
Note *1 The designation depends on the number of poles. Refer to the reference page.
140
50
Rated ambient temperature
Operating handle Right-side mounting
3-pole
IEC 35mm rail mounting adapter
40
Temperature Characteristics Curve
2-pole
Accessories
30
Operating time change rate (%)
7
Left-side mounting
20
×100% of rated current
300 250 200 150 100 80 70 –10
0
10
20
30
40
Ambient temperature (°C)
50
60
7 Characteristics and Dimensions
1 Molded Case Circuit Breakers NF30-CS
Outline Drawing
Front connection 14.5
84 10
47 67.5
2-pole
3-pole
49 3
23.5
12.5 (max.)
28 45
Breaker
f5.5
f5
f8.5 23.5
M40.7 taps or f5
Applicable wire size: f1.6mm to 14mm2
54
64
96
76.5
M5 screw
6
Mtg. hole
2-pole
Conductor thickness t=3 max.
52
Drilling plan
Busbar drilling for direct connection
67
3-pole
Rear connection 3-pole M40.7 taps or f5 Mtg plate t max. =3.2
2-pole
Breaker
Breaker
Mounting base
2-pole
3-pole
20 18
23.5 47
M6 screw
84
76.5 23.5
8
55
58.5
38.5
5
25 (min)
76.5
45 (min)
R2
Breaker mtg M40.7 screw
2-pole
3-pole
ø14
20
Front-plate cutout 1mm clearance on each side of handle
Drilling plan
IEC Rail Mounting Adapter 35mm IEC-rail adapter for installation
35
3-pole
52 55 58 70
7 1 Characteristics and Dimensions
2-pole
4
31 Installation utensil for 35mm IEC-rail
100
5
141
Characteristics and Dimensions
7
NF32-SV NF63-CV NF63-SV NF63-HV
Molded Case Circuit Breakers
1
Model Rated current In (A) Number of poles
NF32-SV
NF63-CV
NF63-SV
NF63-HV
3 4 (5) 6 10 (15) 16 20 25 (30) 32
3 4 (5) 6 10 (15) 16 20 25 (30) 32 40 50 (60) 63
3 4 (5) 6 10 (15) 16 20 25 (30) 32 40 50 (60) 63
10 (15) 16 20 25 (30) 32 40 50 (60) 63
2
3
Rated insulation voltage Ui (V)
Rated short-circuit IEC 60947-2 breaking (Icu/Ics) capacity (kA)
2
3
600
AC
DC
2
3
600
4
2
3
4
600
690
690V
–
–
–
2.5/2.5
500V
2.5/2.5
2.5/2.5
7.5/7.5
7.5/7.5
440V
2.5/2.5
2.5/2.5
7.5/7.5
10/8
415V
2.5/2.5
2.5/2.5
7.5/7.5
10/8
400V
5/5
5/5
7.5/7.5
10/8
380V
5/5
5/5
7.5/7.5
10/8
230V
7.5/7.5
7.5/7.5
15/15
25/19
250V (*1)
2.5/2.5
2.5/2.5
7.5/7.5
7.5/7.5
Standard attached parts (front connection)
Mounting screw: M4×0.7×55 (2 and 3P: 2pcs, 4P: 4pcs) Insulation barrier: (2P: 1pc, 3P: 2pcs, 4P: 3pcs) (*2)
Notes *1 Use two poles for three- and four-pole products. Not available for use with connection as shown at the bottom of page 14. *2 Supplied with NF63-SV and NF63-HV.
NF63-SV
Operating Characteristics 4h
30min 20min 14min 10min
2h 1h 30min 20min 14min 10min
6min 4min
6min 4min
2min
2min
Max.
1min
5s
Operating time
Max. total breaking time
10s
Min.
2s
Instantaneous trip current is fixed to AC600±A120A and DC850±A170A.
Max.
30s 20s
0.5s
Max. (40A-50A)
1min
5s Min.
30s 20s
Max. total breaking time
10s 5s Min. 2s
Max. total breaking time
1s
Max. (60A-63A)
2min
10s
2s
1s
Operating characteristics NF63-CV 40A-63A NF63-SV 40A-63A NF63-HV 40A-63A
1h 30min 20min 14min 10min 6min 4min
1min
30s 20s
2h
Operating characteristics NF32-SV 10A-32A NF63-CV 10A-32A NF63-SV 10A-32A NF63-HV 10A-32A
Operating time
1h
Operating time
4h
4h Operating characteristics NF32-SV 3A-6A NF63-CV 3A-6A NF63-SV 3A-6A
2h
1s
0.5s
0.5s
0.2s
0.2s
0.1s
0.1s
AC AC
0.1s
DC
0.05s 0.02s 0.01s
AC
0.05s Time-delay trip 1 1.25
2
3
4
Instantaneous trip
5 6 7
10
15
20
30
40
DC
0.02s 0.01s
Time-delay trip 1 1.25
2
3
4
5 6 7
Internal Accessories Operating handle
AL
15
20
30
40 50 60 70
2
3
4
5 6 7
Instantaneous trip 10
15
20
30
40
Temperature Compensation Curve AX
SHT or UVT
Lead-wire direction
130
Current rating (%)
Right-side mounting
3, 4-pole
120 110 100 90
(Rated ambient 80 –10 temperature 40°C)
1 Characteristics and Dimensions
Time-delay trip 1 1.25
× 100% of rated current
2-pole
7
0.01s
100
× 100% of rated current
× 100% of rated current
Left-side mounting
0.02s
Instantaneous trip 10
DC
0.05s
Rated ambient temperature
0.2s
0
10
20
30
40
50
60
Ambient temperature (°C)
External Accessories Accessories F Operating handle V LC Handle lock device
HL(*1) HL-S
Type name 2P
F-05SV2
3, 4P
F-05SV
2P
V-05SV2
3, 4P
V-05SV
Reference page 117
Accessories Mechanical interlock
119
Small
TC-S
LC-05SV HLF-05SV HLN-05SV HLS-05SV
Note *1 HLF types are used for OFF lock and HLN types for ON lock.
MI-05SV3
4P
MI-05SV4
2P
TCS-05SV2
3P
TCS-05SV3
2P 127
Large
TC-L
Terminal cover Skeleton
142
MI
Type name 2, 3P
TTC
Rear
BTC
Plug-in
PTC
3P
129
TCL-05SV2 TCL-05SV2L TCL-05SV3 TCL-05SV3L
4P
TCL-05SV4
2P
TTC-05SV2
3P
TTC-05SV3
2P
BTC-05SV2
3P
BTC-05SV3
2P
PTC-05SV2
3P
PTC-05SV3
IEC 35mm rail mounting adapters
Reference page
DIN-05SV
121
137
7 Characteristics and Dimensions
1 Molded Case Circuit Breakers
NF32-SV · NF63-CV · NF63-SV · NF63-HV
Outline Drawing
Front connection Insulation barrier (removable)
M50.8 screw (M8 for 60A and 63A)
Mounting hole
24
50
111
f4.5
50
Applicable wire size: 2 f1.6 to 22mm (for M50.8 screw) 84
112
130
M40.7 taps or f5 Breaker
f5.5 (f8.5 for 60A and 63A)
Trip button
25
50
75
50
75
100
Neutral pole
45
3-pole
25
25
61 12.5 max.
68
(16 max. for 60A and 63A)
72
4
2-pole
8
25
f8.5
22
90
4-pole
2-pole
(Conductor thickness t=4 max.)
3-pole
4-pole
Drilling plan
Conductor drilling for direct connection
Rear connection 4-pole
2-pole Mounting plate t = 3.2 max.
M40.7 taps or f5
Mounting base
3-pole
Breaker
43 (44 for 60A and 63A)
Breaker
M40.7 breaker mounting screw
72
f14
25 42
52
25
27 min. 68
R1
111 50
M6 screw
112
8
112
8
27 min.
25
22.5
25
50
75
3-pole
4-pole
50
1.0mm clearance on each side of the handle frame
(46 for 60A and 63A)
2-pole
70
Front-panel cutout
Drilling plan
Plug-in Mounting plate Plug-in terminal block
M50.8 Terminal block mounting screw
3-pole
4-pole
80
105
50
75
7
Breaker (plug-in terminal block)
Details of terminal
89
25 55
30
2-pole
f6.5
Conductor drilling
25
50
57
82
107
2-pole
3-pole
4-pole
f6 hole or M50.8 taps
Drilling plan
Remark: 1. Only 2-pole and 3-pole models are available for NF32-SV and NF63-CV.
143
1 Characteristics and Dimensions
54
7 M6 screw 21
80
54
116
16.5 max.
85
5.5
170
11
83.5
54
25
Characteristics and Dimensions
7
NF125-CV NF125-SV NF125-HV
Molded Case Circuit Breakers
1
Model Rated current In (A)
NF125-CV
NF125-SV
NF125-HV
50 (60) 63 (75) 80 100 125
(15) 16 20 (30) 32 40 50 (60) 63 (75) 80 100 125
(15) 16 20 (30) 32 40 50 (60) 63 (75) 80 100 125
2
2
Number of poles
2
3
Rated insulation voltage Ui (V)
600
Rated short-circuit IEC 60947-2 breaking (Icu/Ics) capacity (kA)
AC
DC
3
4
3
690
4
690
690V
–
8/8
10/8
500V
7.5/4
18/18
30/23
440V
10/5
25/25
50/38
415V
10/5
30/30
50/38
400V
10/5
30/30
50/38
380V
10/5
30/30
50/38
230V
30/15
50/50
100/75
250V (*1)
7.5/4
40/40
–
Standard attached parts (front connection)
Mounting screw: M4×0.7×55 (2 and 3P: 2pcs, 4P: 4pcs) (*2) Insulation barrier: (2P: 1pc, 3P: 2pcs, 4P: 3pcs)
Notes *1 Use two poles for three- and four-pole products. If wired as shown at the bottom on page 14, three and four poles can be used for up to 400 and 500VDC, respectively. *2 Supplied with NF125-SV and NF125-HV.
NF125-SV
Operating Characteristics 4h
4h
2h
30min 20min 14min 10min 6min 4min
6min 4min
1min
Max.
30s 20s 10s 5s Min.
2s
Max. total breaking time
1s
30s 20s
1min
5s Min.
5s Min. 2s 1s
0.2s
0.1s
0.1s
Max. total breaking time
10s
1s 0.5s
0.5s AC
AC
AC DC Time-delay trip 1 1.25
2
3
4
5 6 7
Instantaneous trip 10
15
20
30
40 50 6070
0.05s
0.02s 0.01s
Time-delay trip 1 1.25
2
3
AL
4
5 6 7
0.02s
Instantaneous trip 10
15
20
30
0.01s
40
Time-delay trip 1 1.25
2
3
4
Instantaneous trip
5 6 7
10
15
20
30
40
× 100% of rated current
× 100% of rated current
Internal Accessories Operating handle
DC
0.1s
0.05s
× 100% of rated current
Temperature Compensation Curve AX
SHT or UVT
Lead-wire direction
130
Right-side mounting
Current rating (%)
Left-side mounting
0.2s
DC
2-pole
3, 4-pole
Rated ambient temperature
0.02s
120 110 100 90
(Rated ambient 80 –10 temperature 40°C)
1 Characteristics and Dimensions
30s 20s
2s
0.2s
Max.
2min
Max. total breaking time
10s
0.5s
0.05s
7
6min 4min
Max. (40A-50A)
1min
Operating characteristics NF125-CV 125A NF125-SV 125A NF125-HV 125A
1h 30min 20min 14min 10min
Max. (60A-100A)
2min Operating time
Operating time
30min 20min 14min 10min
Instantaneous trip current is fixed to AC600±A120A and DC850±A170A.
2min
0.01s
2h Operating characteristics NF125-CV 50A-100A NF125-SV 40A-100A NF125-HV 40A-100A
1h
Operating time
1h
4h
2h
Operating characteristics NF125-SV 15A-32A NF125-HV 15A-32A
0
10
20
30
40
50
60
Ambient temperature (°C)
External Accessories Accessories F Operating handle V LC Handle lock device
HL(*1) HL-S
Type name 2P
F-1SV2
3, 4P
F-1SV
2P
V-1SV2
3, 4P
V-1SV
Reference page 117
Accessories Mechanical interlock
119
Small
MI TC-S
LC-05SV HLF-05SV HLN-05SV HLS-05SV
Notes *1 HLF types are used for OFF lock and HLN types for ON lock. *2 Specify the working voltage. Refer to the reference page for type name.
Large
127 Terminal cover
TC-L
Skeleton
TTC
Rear
BTC
Plug-in
PTC
Electrical operation device
144
Type name 2, 3P
MI-05SV3
4P
MI-05SV4
2P
TCS-1SV2
3P
TCS-1SV3
2P
TCL-1SV2
3P
TCL-1SV3
4P
TCL-1SV4
2P
TTC-1SV2
3P
TTC-1SV3
2P
BTC-1SV2
3P
BTC-1SV3
2P
PTC-1SV2
3P
PTC-1SV3 (*2)
Reference page 129
121
133
7 Characteristics and Dimensions
1 Molded Case Circuit Breakers NF125-CV · NF125-SV · NF125-HV
Outline Drawing
Front connection
Solderless terminal for wire size
24
Breaker
14 to 2/0AWG CU/AL
Wire connection
f4.5
50
f8.5 8
30
22
60
f8.5
Trip button
30
84
112
130
50
M8 screw
111
Insulation barrier (removable)
Mounting hole
60
90
90
120
68
Neutral pole 4
3-pole
M40.7 taps or f5
19 max. Comb conductor 2-pole 16.5 max. (Conductor thickness t=4 max.)
72 90
2-pole
30
30
45 61
3-pole
4-pole
4-pole Conductor drilling for direct connection
Drilling plan
Rear connection
4-pole
4-pole Mounting base Stud can be rotated 90°
Breaker
30 8.5
30
15 68 72
5
M8 bolt
2.5
Insulation tube
15
30
90
f18
60
M40.7 breaker mounting screw
60
2.5
54.5
52
R1
112 16
15 connection allowance
R1
111
52
Breaker
3-pole
2-pole
112
102
2-pole
8
Mounting plate t = 3.2 max.
3-pole
28
30
57
90 M40.7 taps or f5
2-pole
86
3-pole
1.0mm clearance on each side of the handle frame
4-pole
104.5
Front-panel cutout
Drilling plan
Plug-in
Mounting plate
M50.8 Terminal block mounting nut or screw mounted directly
Plug-in terminal block
3-pole
4-pole
95
125
60
90
7
Breaker (plug-in terminal block)
Details of terminal
30
56
12 f8.5 65
89
30
60
67
97
127
2-pole
3-pole
4-pole
30
2-pole
Conductor drilling
f6 hole or M50.8 taps
Drilling plan
Remarks: 1. The 2-pole models of NF125-HV are 3-pole models with the central pole removed. 2. Only 2-and 3-pole models are available for NF125-CV.
145
1 Characteristics and Dimensions
M8 screw
21
80
54
116
20 max.
85
5.5
170
11
83.5
56
30
7
Characteristics and Dimensions
Molded Case Circuit Breakers
1
NF125-UV
Model
NF125-UV 15 20 30 40 50 60 75 100 125
Rated current In (A) Number of poles
2
3
Rated short-circuit breaking capacity (kA)
Rated insulation voltage Ui (V)
4
690
AC
IEC 60947-2 (Icu/Ics)
DC
690V
10/10
500V
200/200
440V
200/200
415V
200/200
400V
200/200
380V
200/200
230V
200/200
250V
−
Standard attached parts (front connection)
Mounting screw: M4×0.7×55 (2 and 3P: 2pcs, 4P: 4pcs) M4×0.7×73 (2 and 3P: 2pcs)
NF125-UV
Operating Characteristics 4h
4h
2h
6min 4min Instantaneous trip current is fixed to 600A ± 120A.
10s 5s Min.
2s 1s 0.5s
1min
30s 20s 10s 5s
Min.
1s
0.1s
Time-delay trip 4
5 6 7
15
20
30
0.01s
40 50 60 70
Time-delay trip 1 1.25
2
3
× 100% of rated current
5 6 7
0.02s
Instantaneous trip 10
15
20
30
0.01s
40
3
4
5 6 7
Instantaneous trip 10
15
20
30
40
Temperature Compensation Curve AX
Right-side mounting
SHT or UVT
EAL
TBL
MG
Lead-wire direction
130
TBM
7
120 110 100 90
(Rated ambient 80 temperature 40°C) –10
1 Characteristics and Dimensions
Time-delay trip 2
1 1.25
× 100% of rated current
Current rating (%)
Left-side mounting
AL
4
× 100% of rated current
Internal Accessories Operating handle
Max. total breaking time
0.1s 0.05s
0.02s
Instantaneous trip 10
0.2s
Max. total breaking time
Rated ambient temperature
3
Min.
0.5s
0.2s
0.05s
2
5s 2s
0.1s
1 1.25
10s
1s
0.05s 0.02s
30s 20s
2s
0.5s Max. total breaking time
0.2s
Max.
2min Operating time
30s 20s
6min 4min
Max. (40A-50A)
1min Operating time
Max.
Operating characteristics NF125-UV 125A
30min 20min 14min 10min
Max. (60A-100A)
2min
1min
1h
Operating characteristics NF125-UV 40A-100A
30min 20min 14min 10min
2min
Operating time
2h
1h
Operating characteristics NF125-UV 15A-30A
30min 20min 14min 10min 6min 4min
0.01s
4h
2h
1h
0
10
20
30
40
50
60
Ambient temperature (°C)
External Accessories Accessories Operating handle Lock cover Handle lock device
Type name
Reference page
F
F-1UV
117
V
V-1UV
119
LC
LC-05SV
HL (*1) HL-S
HLF-05SV HLN-05SV HLS-05SV
Notes *1 HLF types are used for OFF lock and HLN types for ON lock. *2 Specify the working voltage. Refer to the reference page for type name.
Accessories Mechanical interlock
127 Terminal cover
MI
MI-05SV3
4P
MI-05SV4
3P
TCS-1SV3
3P
TCL-1SV3
4P
TCL-1SV4
Small
TC-S
Large
TC-L
Skeleton
TTC
3P
TTC-1SV3
Rear
BTC
3P
BTC-1SV3
Plug-in
PTC
3P
PTC-1SV3
Electrical operation device
146
Type name 2, 3P
(*2)
Reference page 129
121
133
7 Characteristics and Dimensions
1 Molded Case Circuit Breakers NF125-UV
Outline Drawing
Front connection
M8 screw
Breaker 24
90
90
120
61
Neutral pole
19 max. (Comb conductor 16.5 max.) (Conductor thickness t=4 max.)
68 4
3-pole
4-pole
172
8 45
f8.5
30 60
f4.5
Trip 22 button
50
84
191
f8.5
130
173
61
Mounting hole
Conductor drilling for direct connection
72 90
30
30 M40.7 taps or f5
3-pole
4-pole
Drilling plan
Rear connection
3-pole
4-pole
Stud can be rotated 90°
Breaker
8.5 72
60
2.5
54.5
30
60
5
M8 bolt
15 68
52
R1
30 2.5
173
16
15Connection allowance
8
173
Mounting base
4.5
3-pole
172
52
4-pole
Breaker
102
Mounting plate t = 3.2 max.
M40.7 breaker mounting screw Insulation tube
104.5
86
30 90
M40.7 taps or f5
90
15
28
f18
3-pole
1.0mm clearance on each side of the handle frame
4-pole
Drilling plan
Front-panel cutout
Plug-in
Mounting plate
Breaker (Plug-in terminal block)
7 1 Characteristics and Dimensions
141
115
16.5 max.
56
12
177
231
11
144.5
56
Plug-in terminal block
M50.8 Terminal block mounting nut or screw mounted directly
5.5
60
21 M8 screw 89
30
f8.5
30 97
95
f6 hole or M50.8 taps
Conductor drilling Drilling plan
Details of terminal
Remark: 1. 2-pole models are 3-pole models with the central pole removed.
147
7
Characteristics and Dimensions
NF250-CV NF250-SV NF250-HV
Molded Case Circuit Breakers
1
Model Rated current In (A)
NF250-CV
NF250-SV
NF250-HV
(*1) (100) 125 150 175 200 225 250
(*1) (100) 125 150 160 175 200 225 250
125 150 160 175 200 225 250
2
2
Number of poles
2
3
Rated insulation voltage Ui (V)
Rated short-circuit IEC 60947-2 breaking (Icu/Ics) capacity (kA)
3
600
AC
DC (*1)
4
3
690
4
690
690V
–
8/8
10/8
500V
10/8
30/30
50/38
440V
15/12
36/36
65/65
415V
25/19
36/36
70/70
400V
25/19
36/36
75/75
380V
25/19
36/36
75/75
230V
36/27
85/85
100/100
250V
15/12
20/20 (300V)
40/40 (300V)
Standard attached parts (front connection)
Mounting screw: M4×0.7×55 (2 and 3P: 2pcs, 4P: 4pcs) Insulation barrier: (2P: 2pcs, 3P: 4pcs, 4P: 6pcs)
Note *1 Use two poles for three- and four-pole products. In this case, do not use the neutral pole of the four-pole products. If wired as shown at the bottom of page 14, three-pole NF250-CV can be used for up to 400VDC, three-pole NF250-SV and NF250-HV up to 500VDC and four-pole products up to 600VDC.
NF250-SV
Operating Characteristics 4h
4h 2h 1h 30min 20min 14min 10min 6min 4min 2min
2min
Max.
Operating time
1min
30s 20s
Max. total breaking time
10s 5s Min.
2s
30s 20s
Max. total breaking time
10s 5s Min.
2s
1s
1s
0.5s
0.5s
0.2s
AC
0.2s
AC
0.1s
0.1s
DC
DC
0.05s
0.05s 0.02s 2
3
4
5 6 7
0.02s
Instantaneous trip
Time-delay trip 1 1.25
10
15
20
30
0.01s
40
2
3
4
× 100% of rated current
AL
10
15
20
30
40
Temperature Compensation Curve AX
SHT or UVT
Lead-wire direction
130
Current rating (%)
Operating handle
5 6 7
× 100% of rated current
Internal Accessories
Left-side mounting
Instantaneous trip
Time-delay trip 1 1.25
Rated ambient temperature
0.01s
Operating characteristics NF250-CV 250A NF250-SV 250A NF250-HV 250A
1h 30min 20min 14min 10min 6min 4min
Max.
1min Operating time
2h
Operating characteristics NF250-CV 100A-225A NF250-SV 100A-225A NF250-HV 125A-225A
Right-side mounting
7
120 110 100 90
(Rated ambient 80 temperature 40°C) –10
0
10
20
30
40
50
60
1 Characteristics and Dimensions
Ambient temperature (°C)
External Accessories Accessories Operating handle
Handle lock device
Type name
Reference page
F
F-2SV
117
V
V-2SV
119
LC
LC-05SV
HL(*1) HL-S
HLF-05SV HLN-05SV HLS-2SV
Notes *1 HLF types are used for OFF lock and HLN types for ON lock. *2 Specify the working voltage. Refer to the reference page for type name.
Accessories Mechanical interlock
127
MI
Small
TC-S
Large
TC-L
Terminal cover
MI-05SV3
4P
MI-2SV4
2, 3P 2, 3P
Reference page 129
TCS-2SV3 TCL-2SV3 TCL-2SV3L
4P
TCL-2SV4
Skeleton
TTC
2, 3P
TTC-2SV3
Rear
BTC
2, 3P
BTC-2SV3
Plug-in
PTC
2, 3P
PTC-2SV3
Electrical operation device
148
Type name 2, 3P
(*2)
121
133
7 Characteristics and Dimensions
1 Molded Case Circuit Breakers NF250-CV · NF250-SV · NF250-HV
Outline Drawing
M8 bolt (hex-socket)
Insulation barrier (removable)
24
Breaker
.5 10
f8 C 1
f4.5
50
102
165
144
126
Solderless terminal for wire size 125-175A 14-95mm2 200-250A 70-125mm2 Wire connection
100
Mounting hole
30
Front connection
1 C
35
70
105
45
68 4
140
3-pole
35
72
M40.7 taps or f5
3-pole
25 max.
92
4-pole
35
.5
f8
61
Neutral pole
105
Or
9
22
25 max.
f8.5
100
Trip button
4-pole
(Conductor thickness t=7 max.)
Conductor drilling for direct connection
Drilling plan
Rear connection 4-pole
Mounting base Stud can be rotated 90°
Breaker
Breaker
3-pole
15
72
M40.7 breaker mounting screw
6
15
68
R
52
1
144
126
20
Connection allowance
22
144
8
Mounting plate t = 3.2 max.
3-pole
4-pole
35
70
f9 M8 bolt
Insulation tube
105
71
f24
106
70
32.5
35
M40.7 taps or f5
35
100
105
1.0mm clearance on each side of the handle frame
4-pole
3-pole
Front-panel cutout
Drilling plan
Plug-in 4-pole 145
7
Breaker (plug-in terminal block)
M5 terminal block mounting screw
21 31 89 112
30
Insulation barrier
56.5
20
3-pole 70 4-pole 105 3-pole 105 4-pole 140
80
54 15
28
151
6
11
70
144
165
190
24
56.5
Connection allowance
f9 M8 bolt Stud attachable in this direction only
70
105
107
142
3-pole
4-pole
f6 hole or M50.8 taps
Drilling plan
Remarks: 1. 2-pole models are 3-pole models with the central pole removed. 2. Only 2-pole and 3-pole models are available for NF250-CV.
149
1 Characteristics and Dimensions
34.5
Mounting plate
3-pole 110
Plug-in terminal block
7
Characteristics and Dimensions
Molded Case Circuit Breakers
1
NF250-UV
Model
NF250-UV 125 150 175 200 225 250
Rated current In (A) Number of poles
2
3
Rated short-circuit breaking capacity (kA)
Rated insulation voltage Ui (V)
4
690
AC
IEC 60947-2 (Icu/Ics)
DC
690V
15/15
500V
200/200
440V
200/200
415V
200/200
400V
200/200
380V
200/200
230V
200/200
250V
− Mounting screw: M4×0.7×55 (2 and 3P: 2pcs, 4P: 4pcs) Mounting screw: M4×0.7×73 (2 and 3P: 2pcs) Insulation barrier: (2P: 2pcs, 3P: 4pcs, 4P: 6pcs)
Standard attached parts (front connection)
NF250-UV
Operating Characteristics 4h
4h
2h
2h Operating characteristics NF250-UV 125A-225A
1h 30min 20min 14min 10min 6min 4min 2min
30s 20s 10s 5s Min.
2s
30s 20s 10s 5s Min.
2s
1s
1s
0.5s
0.5s
0.2s
0.2s
Max. total breaking time
0.1s
Max. total breaking time
0.1s 0.05s
0.05s 0.02s 0.01s
Max.
1min Operating time
Operating time
2min
Max.
1min
Operating characteristics NF250-UV 250A
1h 30min 20min 14min 10min 6min 4min
3
4
5 6 7
0.02s
Instantaneous trip
Time-delay trip 2
1 1.25
10
15
20
30
0.01s
40
Time-delay trip 1 1.25
2
3
4
× 100% of rated current
Internal Accessories AX
Right-side mounting
SHT or UVT
EAL
TBL
MG
Lead-wire direction
20
30
40
130
TBM
7
120 110 100 90
(Rated ambient 80 temperature 40°C) –10
1 Characteristics and Dimensions
15
Rated ambient temperature
AL
10
Temperature Compensation Curve
Current rating (%)
Operating handle Left-side mounting
Instantaneous trip
5 6 7
× 100% of rated current
0
10
20
30
40
50
60
Ambient temperature (°C)
External Accessories Accessories Operating handle
Handle lock device
Type name
Reference page
F
F-2UV
117
V
V-2UV
119
LC
LC-05SV
HL(*1) HL-S
HLF-05SV HLN-05SV HLS-2SV
Notes *1 HLF types are used for OFF lock and HLN types for ON lock. *2 Specify the working voltage. Refer to the reference page for type name.
Accessories Mechanical interlock
127
MI
Small
TC-S
Large
TC-L
Terminal cover
MI-05SV3
4P
MI-2SV4
2, 3P 2, 3P
Reference page 129
TCS-2SV3 TCL-2SV3 TCL-2SV3L
4P
TCL-2SV4
Skeleton
TTC
2, 3P
TTC-2SV3
Rear
BTC
2, 3P
BTC-2SV3
Plug-in
PTC
2, 3P
PTC-2SV3
Electrical operation device
150
Type name 2, 3P
(*2)
121
133
7 Characteristics and Dimensions
1 Molded Case Circuit Breakers NF250-UV
Outline Drawing
Front connection M8 bolt (hex-socket)
Breaker
24
201
f8.5
f8.5
100
10
f4.5
50
165
102
240
165
219
75
75
100
28
Insulation barrier (removable)
Mounting hole
Trip button
45
35
22
Neutral pole 70
23 max.
61 68
(Conductor thickness t=7 max.)
72
Conductor drilling for direct connection
105 4
105
140
3-pole
4-pole
92
35
35
3-pole
M40.7 taps or f5
4-pole
Drilling plan
Rear connection 4-pole Mounting plate t = 3.2 max.
Mounting base
3-pole
Stud can be rotated 90°
Breaker
Breaker 4-pole 3-pole
11.5
73
219
201
8 6
15
68 72
71
15 f9 M8 bolt
70 105
f24
M40.7 breaker mounting screw
32.5
35
100
35
35 Insulation tube
M40.7 taps or f5
70
106
3-pole Drilling plan
52
R1
20
Connection allowance 22
219
108
105
1.0mm clearance on each side of the handle frame
4-pole
Front-panel cutout
1 Characteristics and Dimensions
30
7
56.5
151
70 15
31 89
20
28
21
Breaker (Plug-in terminal block)
129
219 6
265
M5 terminal block mounting screw 11
110
56.5
Plug-in terminal block
155
34.5
Mounting plate
Connection allowance 24
Plug-in
70 Insulation barrier
105
f9 M8 bolt Stud attachable in this direction only
70
f6 hole or M5 taps
107
Drilling plan
Remark: 1. 2-pole models are 3-pole models with the central pole removed.
151
Characteristics and Dimensions
NF125-SGV NF250-SGV NF160-LGV NF125-HGV NF250-HGV NF250-RGV
NF160-SGV NF125-LGV NF250-LGV NF160-HGV NF125-RGV
Molded Case Circuit Breakers
1
Model
NF125-SGV 16-20, 20-25, 25-32 32-40, 35-50, 45-63 Rated current In (A) 56-80, 70-100, 90-125 Number of poles 2 3 4 Rated insulation voltage Ui (V) 690 690V 8/8 500V 30/30 440V 36/36 415V 36/36 IEC AC 60947-2 400V 36/36 (Icu/Ics) 380V 36/36 230V 85/85 200V 85/85 DC (*1) 300V 20/20 Standard attached parts (front connection)
NF160-SGV
NF250-SGV NF125-LGV NF160-LGV 16-20, 20-25, 25-32 125-160 32-40, 35-50, 45-63 125-160 140-200 125-160 56-80, 70-100, 90-125 175-250 2 3 4 2 3 4 2 3 4 2 3 4 690 690 690 690 8/8 8/8 8/8 8/8 30/30 30/30 36/36 36/36 36/36 36/36 50/50 50/50 36/36 36/36 50/50 50/50 36/36 36/36 50/50 50/50 36/36 36/36 50/50 50/50 85/85 85/85 90/90 90/90 85/85 85/85 90/90 90/90 20/20 20/20 20/20 20/20 Mounting screw: M4×0.7×55 (2 and 3P: 2pcs, 4P: 4pcs) Insulation barrier: (2P: 2pcs, 3P: 4pcs, 4P: 6pcs)
Rated short-circuit breaking capacity (kA)
7
Model
NF160-HGV
NF250-HGV NF125-RGV 16-20, 20-25, 25-32 125-160 32-40, 40-50, 50-63 125-160 140-200 63-80, 80-100, 100-125 175-250 2 3 4 2 3 4 2 3 690 690 690 10/8 10/8 – 50/38 50/38 – 65/65 65/65 125/125 70/70 70/70 150/150 75/75 75/75 150/150 75/75 75/75 150/150 100/100 100/100 150/150 100/100 100/100 150/150 40/40 40/40 – Mounting screw: M4×0.7×55 (2 and 3P: 2pcs, 4P: 4pcs) Insulation barrier: (2P: 2pcs, 3P: 4pcs, 4P: 6pcs)
Rated short-circuit breaking capacity (kA)
NF125-HGV 16-20, 20-25, 25-32 32-40, 35-50, 45-63 Rated current In (A) 56-80, 70-100, 90-125 Number of poles 2 3 4 Rated insulation voltage Ui (V) 690 690V 10/8 500V 50/38 440V 65/65 415V 70/70 IEC AC 60947-2 400V 75/75 (Icu/Ics) 380V 75/75 230V 100/100 200V 100/100 DC (*1) 300V 40/40 Standard attached parts (front connection)
NF250-SGV
NF250-LGV 125-160 140-200 175-250 2 3 4 690 8/8 36/36 50/50 50/50 50/50 50/50 90/90 90/90 20/20
NF250-RGV 125-160 160-200 200-250 2 3 690 – – 125/125 150/150 150/150 150/150 150/150 150/150 –
Note *1 When wired as shown at the bottom of page 14, three-pole models can be used for up to 500VDC, and four-pole models for up to 600VDC.
Operating Characteristics
AC 600A±120A
DC 850A±170A
1min 30s 20s
Max.
10s Min.
1s Max. total breaking time
0.5s 0.2s
0.02s
Time-delay trip 1 1.3
2
3
4
Instantaneous trip
5 6 7
10
15 20
30 40 50 6070
lnstantaneous trip current ratio AC xln(%) 1000±200
30s 20s 10s
2s 1s 0.5s Max. total breaking time
DC
0.1s
Instantaneous trip
Time-delay trip 1 1.3
2
3
4
5 6 7
10
15 20
30 40
Time-delay trip 1 1.25
2
3
4
5 6 7
10
15 20
0.01s
30 40
Current( × 100% of Ir) Instantaneous tripping current( × 100% of In)
Instantaneous tripping current( × 100% of In)
AL
0.02s
Instantaneous trip
Current( × 100% of Ir)
Internal Accessories
Max. total breaking time
DC
0.1s 0.05s
0.02s 0.01s
AC
0.2s
0.05s
0.02s 0.01s
AC
0.2s
DC
DC xln(%) 1300±260
Min.
5s
2s
lnstantaneous trip current ratio AC xln(%) 1000±200
10s
1s AC
Max.
30s 20s
0.5s
Instantaneous tripping current( × 100% of In)
Operating handle
1min
0.5s
Current( × 100% of Ir)
Left-side mounting
DC xln(%) 1300±260
Min.
5s
Time-delay trip 1 1.25
2
3
4
Instantaneous trip
5 6 7
10
15 20
Current( × 100% of Ir) Instantaneous tripping current( × 100% of In)
30 40
Temperature Compensation Curve AX
SHT or UVT
Lead-wire direction
130 Current rating (%)
1 Characteristics and Dimensions
Max. total breaking time
1min
6min 4min 2min
Max.
1s
0.05s
0.05s
7
Min.
5s
0.1s
DC
2min
10s
0.2s
AC
0.1s
DC 850A±170A
30s 20s
2s
2s
0.01s
1min
AC 600A±120A
30min 20min 14min 10min
Right-side mounting
Rated ambient temperature
5s
Max.
1h
NF125-SGV NF125-LGV NF125-HGV Current setting Ir = 40- 63A(Rated current In= 63A) Current setting Ir = 45- 63A(Rated current In= 63A) Current setting Ir = 56- 80A(Rated current In= 80A) Current setting Ir = 63-100A(Rated current In=100A) NF125-RGV Current setting Ir = 50- 63A(Rated current In= 63A) Current setting Ir = 63- 80A(Rated current In= 80A)
6min 4min
lnstantaneous trip current
2min Operating time
Operating time
2min
Operating time
6min 4min
Operating Characteristic Curves Thermal-Adjustable types NF125-SGV NF125-LGV NF125-HGV Current setting Ir = 70-100A(Rated current In=100A) Current setting Ir = 80-125A(Rated current In=125A) Current setting Ir = 90-125A(Rated current In=125A) NF160-SGV NF160-LGV NF160-HGV Current setting Ir = 125-160A(Rated current In=160A) NF250-SGV NF250-LGV NF250-HGV Current setting Ir = 125-160A(Rated current In=160A) Current setting Ir = 140-200A(Rated current In=200A) Current setting Ir = 160-250A(Rated current In=250A) Current setting Ir = 175-250A(Rated current In=250A) NF125-RGV Current setting Ir = 80-100A(Rated current In=100A) Current setting Ir = 100-125A(Rated current In=125A) NF250-RGV Current setting Ir = 125-160A(Rated current In=160A) Current setting Ir = 160-200A(Rated current In=200A) Current setting Ir = 200-250A(Rated current In=250A)
2h
Thermal-Adjustable types
1h 30min 20min 14min 10min
NF125-SGV NF125-LGV NF125-HGV Current setting Ir = 32-40A(Rated current In=40A) Current setting Ir = 35-50A(Rated current In=50A) NF125-RGV Current setting Ir = 32-40A(Rated current In=40A) Current setting Ir = 40-50A(Rated current In=50A)
30min 20min 14min 10min 6min 4min
lnstantaneous trip current
Operating Characteristic Curves
2h
Thermal-Adjustable types
1h
NF125-SGV NF125-LGV NF125-HGV NF125-RGV Current setting Ir = 16-20A(Rated current In=20A) Current setting Ir = 20-25A(Rated current In=25A) Current setting Ir = 25-32A(Rated current In=32A)
30min 20min 14min 10min
Operating Characteristics
2h
Thermal-Adjustable types
1h
4h
4h
4h Operating Characteristics
2h
Operating time
4h
120 110 100 90 80 -10
0
10
20
30
40
50
60
Ambient temperature (°C) (rated ambient temperature 40°C)
External Accessories Accessories F V LC
Operating handle
Handle lock device
HL(*1) HL-S
Type name F-2SV V-2SV LC-05SV HLF-05SV HLN-05SV HLS-2SV
Reference page 117 119
Notes *1 HLF types are used for OFF lock and HLN types for ON lock. *2 Specify the working voltage. Refer to the reference page for type name.
152
Accessories Mechanical interlock
127 Terminal cover
MI
Small
TC-S
Large
TC-L
Skeleton TTC Rear BTC Plug-in PTC Electrical operation device
Type name 2, 3P 4P 2, 3P 2, 3P 4P 2, 3P 2, 3P 2, 3P
MI-05SV3 MI-2SV4 TCS-2SV3 TCL-2SV3 TCL-2SV3L TCL-2SV4 TTC-2SV3 BTC-2SV3 PTC-2SV3 (*2)
Reference page 129
121
133
7 Characteristics and Dimensions
1 Molded Case Circuit Breakers
NF125-SGV · NF160-SGV · NF250-SGV · NF125-LGV · NF160-LGV · NF250-LGV · NF125-HGV · NF160-HGV · NF250-HGV · NF125-RGV · NF250-RGV
Outline Drawing
30
Front connection Insulating barrier (removable)
Breaker
126 10
C
1
f4.5
f8
.5
50
102
Solderless terminal for wire size 125-175A 14-95mm2 200-250A 70-125mm2 Wire connection
165
144
24
M8 bolt (hex-socket)
100
Mounting hole
100
f8.5
1
C
Thermal Adj Button 22
35
70
105
105
25 max.
45
35
Or
61 Neutral pole
.5 f8
68 4
140
72
35
M40.7 taps or f5
3-pole
9
Trip button
4-pole
25 max.
92
(Conductor thickness t=7 max.)
3-pole
4-pole
Conductor drilling for direct connection
Drilling plan
Rear connection 4-pole 3-pole
4-pole
Stud can be rotated 90°
Breaker
3-pole
Breaker
R
52
1
144
20
Connection allowance
22
126
144
8
Mounting plate t max. = 3.2
Mounting base
M40.7 breaker mounting screw
15 68 72
f24
6
15
f9 M8 bolt
Insulating tube
70
70
105
71
35
M40.7 taps or f5
35
100
105
1mm clearance on each side of the handle frame
4-pole
3-pole
106
32.5
35
Front-panel cutout
Drilling plan
Plug-in
21 31 89 112
30
56.5
Insulating barrier
4-pole 105 3-pole 105 4-pole 140
56.5
80
54 20
3-pole 70
1 Characteristics and Dimensions
M5 terminal block mounting screw
15
28
151
6
11
7
3-pole 110
70
144
165
190
Mounting plate
4-pole 145
24 connection allowance
34.5
Plug-in terminal block
f9 M8 bolt Stud attachable in this direction only
70
105
107
142
3-pole
4-pole
f6mm hole or M50.8 taps
Drilling plan
Remark: 1. 2-pole models are 3-pole models with the central pole removed.
153
7
Characteristics and Dimensions
NF125-SEV NF125-HEV NF250-SEV NF250-HEV
Molded Case Circuit Breakers
1
Model
NF125-SEV
NF125-HEV
NF250-SEV
NF250-HEV
Rated current In (A)
32 63 125
32 63 125
160 250
160 250
Current setting Ir (A)
16-32 32-63 63-125
16-32 32-63 63-125
80-160 125-250
80-160 125-250
Number of poles
3
3
4
Rated insulation voltage Ui (V)
Rated short-circuit IEC 60947-2 breaking (Icu/Ics) capacity (kA)
4
690
AC
DC
3
4
690
690
3
4 690
690V
8/8
10/8
8/8
10/8
500V
30/30
50/38
30/30
50/38
440V
36/36
65/65
36/36
65/65
415V
36/36
70/70
36/36
70/70
400V
36/36
75/75
36/36
75/75
380V
36/36
75/75
36/36
75/75
230V
85/85
100/100
85/85
100/100
250V
–
–
–
–
Standard attached parts (front connection)
Mounting screw: M4×0.7×55 (3P: 2pcs, 4P: 4pcs) Insulation barrier: (3P: 4pcs, 4P: 6pcs)
NF125-SEV
Operating Characteristics 10h
10h
5h
Operating characteristics
5h
Operating characteristics
2h
NF125-SEV NF125-HEV
2h
NF250-SEV NF250-HEV
1h 30min 20min 14min 10min 6min 4min
6
LTD operating time at 125% (I t ON) 670s (TL = 100s set) 540s (TL = 80s set) 400s (TL = 60s set) 80s (TL = 12s set)
Current setting Ir 16-32 32-63 63-125
Rated current In 32A 63A 125A
1h 30min 20min 14min 10min 6min 4min
2min 30s 20s
6
I t OFF
10s
STD pickup current Is Ir × (2–2.5–3–3.5–4 –5–6–7–8–10) ±15%
5s
1min
Operating time
LTD operating time TL 12–60–80–100s ±20% (at 200%)
6
I t ON
2s
6
I t OFF
10s
STD pickup current Is Ir × (2–2.5–3–3.5–4 –5–6–7–8–10) ±15%
5s 2s 1s 0.5s
STD operating time Ts 0.3±0.06s 0.2±0.04s
0.2s 0.1s
I t ON
STD operating time Ts 0.3±0.06s 0.2±0.04s
0.2s 0.1s
0.1±0.03s
2
0.05s
I t ON
0.05s 2
INST pickup current Ii In × 2-14 ±15%, Ir × 14 ±15%
0.01s 0.6 0.7
1 1.25
2
3
4
5 6 7
10
0.02s
Max. total breaking time 15
20
30
I t OFF
0.01s
40
0.6 0.7
1 1.25
Internal Accessories
3
4
5 6 7
Max. total breaking time
10
15
20
30
40
AX
Right-side mounting
Lead-wire direction
SHT or UVT
PAL
Rated ambient temperature
AL
2
Current Reducing Curve Derating of load current (%)
Operating handle
INST pickup current Ii In × 2-14 ±15%, Ir × 14 ±15%
× 100% of current setting Ir Instantaneous tripping current (% of rated current or % of current setting Ir)
× 100% of current setting Ir Instantaneous tripping current (% of rated current or % of current setting Ir)
1 Characteristics and Dimensions
0.1±0.03s
2
2
I t OFF
0.02s
Left-side mounting
Rated current In 160A 250A
LTD operating time TL 12–60–80–100s ±20% (at 200%)
6
I t ON
30s 20s
1s 0.5s
7
Current setting Ir 80-160 125-250
2min
1min
Operating time
6
LTD operating time at 125% (I t ON) 670s (TL = 100s set) 540s (TL = 80s set) 400s (TL = 60s set) 80s (TL = 12s set)
130 120 110 100 90 80 70 –10
(Note)
0
10
20
30
40
50
60
The rated current does not have thermal characteristics. Reduce the current as shown in the curve on the left chart if the ambient temperature exceeds 40 °C.
Ambient temperature (°C)
External Accessories Accessories Operating handle
Handle lock device
Type name
Reference page
F
F-2SV
117
V
V-2SV
119
LC
LC-05SV
HL(*1) HL-S
HLF-05SV HLN-05SV HLS-2SV
Notes *1 HLF types are used for OFF lock and HLN types for ON lock. *2 Specify the working voltage. Refer to the reference page for type name.
Accessories Mechanical interlock
127 Terminal cover
MI
Small
TC-S
Large
TC-L
MI-05SV3
4P
MI-2SV4
3P
TCS-2SV3
3P
Reference page 129
TCL-2SV3 TCL-2SV3L
4P
TCL-2SV4
Skeleton
TTC
3P
TTC-2SV3
Rear
BTC
3P
BTC-2SV3
Plug-in
PTC
3P
PTC-2SV3
Electrical operation device
154
Type name 3P
(*2)
121
133
7 Characteristics and Dimensions
1 Molded Case Circuit Breakers
NF125-SEV · NF125-HEV · NF250-SEV · NF250-HEV
Outline Drawing
30
Front connection
Insulation barrier (removable)
M8 bolt (hex-socket)
24
Solderless terminal for wire size 125-175A 14-95mm2 200-250A 70-125mm2 Wire connection
100
Mounting hole
Breaker
126
10 1
C
f4.5
C
1
50
102
165
144
f8
.5
Trip button
25 max.
35
70
105
105
Neutral pole
Or
45
f8.5
61
4
35
M40.7 taps or f5
68
140
25 max.
72
4-pole
4-pole
3-pole
(Conductor thickness t=7 max.)
92
3-pole
35
9
22
f8.5
100
Trip characteristics selector
Conductor drilling for direct connection
Drilling plan
Rear connection 4-pole
Mounting plate t=3.2 max.
Stud can be rotated 90°
Mounting base
3-pole
4-pole
Breaker
Breaker
15 71
72
M40.7 breaker mounting screw
6
15
68
R
52
1
144
126
20
22 connection allowance
144
8
3-pole
f9 M8 bolt
70
Insulation tube
105
70
35
M40.7 taps or f5
100
105
1.0mm clearance on each side of the handle frame
4-pole
3-pole
106
32.5
35
f24 35
Drilling plan
Front-panel cutout
89 112
30
f9 M8 bolt
4-pole 105 3-pole 105
80
56.5 3-pole 70
Insulation barrier
56.5
151 20
Stud attachable in this direction only
70
105
107
142
3-pole
4-pole
f6 hole or M50.8 taps
4-pole 140
Drilling plan
155
1 Characteristics and Dimensions
M5 terminal block mounting screw
31
15
28 21
7 54
34.5 6
144
11
4-pole 145 3-pole 110
70
165
190
Mounting plate
Plug-in terminal block
24 connection allowance
Plug-in
Characteristics and Dimensions
7
Molded Case Circuit Breakers
1
NF400-CW NF400-SW
Model
NF400-CW
Rated current In (A) Number of poles
2
3
Rated insulation voltage Ui (V) Rated short-circuit breaking capacity (kA)
NF400-SW
250 300 350 400
AC
IEC 60947-2 (Icu/Ics)
DC (*1)
2
3
690
690
690V
−
10/10
500V
15/8
30/30
440V
25/13
42/42
400V
36/18
45/45
230V
50/25
85/85
250V
20/10
40/40
4
Mounting screw: M6×60 (4pcs) Front connection Insulating barrier: (2P: 2pcs, 3P: 4pcs, 4P: 6pcs) Rear Mounting screw: M6×72 (4pcs) connection
Standard attached parts
Note *1 When wired as shown at the bottom of page 14, 3-pole models can be used for up to 400VDC, and 4-pole models for up to 500VDC.
NF400-SW
Operating Characteristics 4h
4h
2h
2h Operating characteristics
1h
6min 4min
2min
2min
1min
1min
Operating time
Operating time
NF400-SW
30min 20min 14min 10min
6min 4min
Max.
30s 20s
Operating characteristics
1h
NF400-CW
30min 20min 14min 10min
10s 5s
Max.
30s 20s 10s 5s
Min.
Min. 2s
2s
1s
1s AC
0.5s
0.5s DC 0.2s
0.2s DC 0.1s
0.1s
Max. total interrupting time
0.05s
AC
interrupting time
0.02s
0.02s
Time delay trip
Instantaneous trip
Time delay trip 200
300
400 500 600 700
1000
1500
2000
100 125
3000 4000
200
300
400 500 600 700
1500 2000
3000 4000
Temperature Compensation Curve
Internal Accessories Lead wire direction
SHT or UVT
130
(*1)
(*1)
120 110 100 90 80
(*1)
Rated ambient temperature
AX
Current rating (%)
Operating handle Right-side AL mounting
(*1)
0
10
Note *1 Right-side mounting is standard of SHT and UVT. Specify separately for left-side mounting. Remark: 1. Refer to page 106.
20
30
40
50
Ambient temperature (°C)
External Accessories Accessories Operating handle
Type name
F V
Mechanical interlock
MI
Auxiliary handle
HT
117
V-4S
119
2, 3P MI-4SW3 4P
Reference page
F-4S
MI-4SW4 HT-4CW, HT-4SW
129 128
Note *1 Specify the operation method and voltage. Order in combination with the breaker unit.
Accessories Terminal cover
1 Characteristics and Dimensions
1000
% of rated current
% of rated current
Left-side mounting
Instantaneous trip
0.01s
0.01s 100 125
7
Max.total
0.05s
Large Skeleton Rear
Handle lock device Electrical operation device
156
Type name TC-L TTC BTC
2, 3P
TCL-4SW3
4P
TCL-4SW4
2, 3P
TTC-4SW3
4P
TTC-4SW4
2, 3P 4P
BTC-4SW3 BTC-4SW4
HL
HL-4CW, HL-4SW
HL-S
HLS-4SW
NFM
3P 4P
(*1)
Reference page
121
127 133
60
7 Characteristics and Dimensions
1 Molded Case Circuit Breakers NF400-CW · NF400-SW
Outline Drawing
Front connection
94.5
Insulating barrier (removable)
44
28
4-pole
8
3-pole
Breaker
Breaker 39
43
110
16
Conductor thickness t=8 max.
168 185
140
196
3-pole
4-pole
5
44 118
Conductor drilling for direct connection
97 103
51
M6 tap or f7
Conductor thickness t=8 max.
44
56
112
f10.5 44
Neutral pole f14 M12 bolt
194
12
39
25
107
3-pole
155 (NF400-SW) 134 (NF400-CW)
1.0mm clearance on each side of the handle frame.
4-pole
Front-panel cutout
Drilling plan
Boring dimensions for rear connection type barriers (3-pole)
Rear connection
Stud can be rotated 90°
Line side
4-pole
Mounting plate
Breaker
Groove for reducing heat by overcurrent
6-f35 8
24 24
8
3-pole
Connection allowance
24 24
M6 screw for mounting breaker Insulation tube
87
f35
44
8
f13 M12 bolt
225
194
225
194
83
128
26 10
4-M6 tap or f7
14
225
265
M6 tap or f7
25 20 20
113
92
f12.5
47 f7
257 Trip button
R6
102
Mounting hole
44
11
11
87
43.5
44
130.5
87
3-pole
4-pole
130.5
8-M4 screw Add these tapped holes in 8 positions to standard boring.
Load side
Drilling plan
Note The bore dimensional drawing shows the breaker viewed from the rear.
Plug-in
4-pole 3-pole
Mounting plate
Breaker
163
24
55
79 160
7
f13 M12 bolt
28
Stud attachable in this direction only 87 130.5
Insulating barrier
f10 44
87
136
181
3-pole
4-pole
1 Characteristics and Dimensions
121
28
18
135
Connection allowance
15
M8 terminal block mounting screw
8
24
225
280
55
35
Plug-in terminal block
Drilling plan
Remark: 1. 2-pole models are 3-pole models with the central pole removed.
157
Characteristics and Dimensions
7
Molded Case Circuit Breakers
1
NF400-SEW NF400-HEW NF400-REW
Model
NF400-SEW
NF400-HEW
Number of poles
3
Rated insulation voltage Ui (V) Rated short-circuit breaking capacity (kA)
NF400-REW
200-400 adjustable
Rated current In (A)
IEC 60947-2 (Icu/Ics)
AC
3
4 690
3 690
690V
10/10
35/18
−
500V
30/30
50/50
70/35
440V
42/42
65/65
125/63
400V
50/50
70/70
125/63
230V
85/85
100/100
150/75
Mounting screw: M6×72 (4pcs) Insulating barrier: (3P: 4pcs, 4P: 6pcs)
Front connection Rear connection
Standard attached parts
4 690
Mounting screw: M6×85 (4pcs)
NF400-SEW
Operating Characteristics
Internal Accessories Left-side mounting
10h 5h
Operating characteristics
2h
NF400-SEW NF400-HEW NF400-REW
1h LTD operating time at 125% 1000s(TL=150s set) 670s(TL=100s set) 400s(TL= 60s set) 80s(TL= 12s set)
30min 20min 14min 10min 6min 4min
Current setting Ir: 200-400A (Adjustable)
AX
Lead wire direction
SHT or UVT
LTD operating time TL 12-60-100-150s ±20% (at 200%)
(*1)
(*1)
Note *1 Right-side mounting is standard of SHT and UVT. Specify separately for left-side mounting. Remark: 1. Refer to page 106.
1min 30s 20s 10s 5s 2s
Pre-alarm pickup current Ip
STD pickup current Is Ir x(2-2.5-3-3.5-4 -5-6-7-8-10) ±15%
Ir x(0.70-0.75 -0.8-0.85-0.9 ±10% -0.95-1.0)
Current Reducing Curve
STD operating time Ts 0.3 ± 0.06s 0.2 ± 0.04s
TL ±20% 2 (at 200%)
Tp=
0.1s
0.1 ± 0.03s 0.06 ± 0.02s
0.05s INST pickup current II x4-x16 ±15% (Magnification to In)
0.02s 0.01s 60 70
100 125
Continuous load current (%)
0.2s
Pre-alarm operating time Tp
200
300
400 500 600 700
1000
Max. total breaking time 1500 2000
3000 4000
Current (% of Ir) Instantaneous tripping current (% of In)
Rated ambient temperature
1s 0.5s
130 120 110 100 90 80 70 0
10
20
30
40
50
60
Ambient temperature (°C)
7 External Accessories Operating handle
Type name
F V
Mechanical interlock
MI
Auxiliary handle
HT
Reference page
F-4S
117
V-4S
119
3P
MI-4SW3
4P
MI-4SW4 HT-4SW
129 128
Accessories Terminal cover
1 Characteristics and Dimensions
Accessories
Type name
Large
TC-L
Skeleton
TTC
Rear
BTC
Handle lock device Electrical operation device Notes *1 Specify the operation method and voltage. Order in combination with the breaker unit. *2 This is for NF400-SEW. For rear terminal cover of NF400-HEW/REW, use PTC-4SW3. *3 This is for NF400-SEW/HEW.
158
PAL
(*1)
Rated Current In: 400A
(*1)
2min
Operating time
Operating handle Right-side AL mounting
3P
TCL-4SW3 (*2)
4P
TCL-4SW4 (*3)
3P
TTC-4SW3
4P
TTC-4SW4
3P 4P
BTC-4SW3 (*2) BTC-4SW4 (*3)
HL
HL-4SW
HL-S
HLS-4SW
NFM
3P 4P
(*1)
Reference page
121
127 133
7 Characteristics and Dimensions
1 Molded Case Circuit Breakers NF400-SEW · NF400-HEW · NF400-REW
Outline Drawing
Front connection
94.5
Insulating barrier (removable) 28
44 4-pole
8
3-pole
Breaker
Breaker 39
43
110
16
Conductor thickness t=8 max.
f7
39
25
44 103
51
168 185
140
196
3-pole
4-pole
M6 tap or f7
5
92
44
Conductor thickness t=8 max.
118
Conductor drilling for direct connection
97 56
112
f10.5 44
Neutral pole f14 M12 bolt
194
12
59
f12.5
257 Trip button
R6
102
Mounting hole
107
3-pole
155
1.0mm clearance on each side of the handle frame.
4-pole
Front-panel cutout
Drilling plan
Boring dimensions for rear connection type barriers (3-pole)
Rear connection
4-pole
Stud can be rotated 90°
Breaker
3-pole
Line side
Groove for reducing heat by overcurrent
6-f35 8
24 24
8 Connection allowance
194
225
24 24
M6 screw for mounting breaker
44
8
f13 M12 bolt
113
194
83
128
26
25 20 20
10
4-M6 tap or f7
14
225
265
M6 tap or f7
Insulation tube
87
225
Mounting plate
f35
44
87
11
43.5
130.5
11
44
130.5
8-M4 screw Add these tapped holes in 8 positions to standard boring.
87
3-pole 4-pole Drilling plan
Load side
Note The bore dimensional drawing shows the breaker viewed from the rear.
Plug-in
4-pole
Mounting plate
3-pole
Breaker
7
163
24
55
160
79
f13 M12 bolt
1 Characteristics and Dimensions
121
28
18
135
Connection allowance
15
M8 terminal block mounting screw
8
24
225
280
55
35
Plug-in terminal block
f10
28
Stud attachable in this direction only 87 130.5
Insulating barrier
44
87
136
181
3-pole
4-pole
Drilling plan
159
Characteristics and Dimensions
7
1
Molded Case Circuit Breakers
NF400-UEW
Model
NF400-UEW 200-400 adjustable
Rated current In (A) Number of poles
3
4
Rated short-circuit breaking capacity (kA)
Rated insulation voltage Ui (V)
IEC 60947-2 (Icu/Ics)
690
AC
Standard attached parts (4-pole models are provided with auxiliary handle.)
690V
−
500V
170/170
440V
200/200
400V
200/200
230V
200/200
Front connection Rear connection
Mounting screw: M6×65 (2pcs), M6×174 (2pcs) Insulating barrier: (3P: 4pcs) Mounting screw: M6×72 (2pcs), M6×181 (2pcs)
NF400-UEW
Operating Characteristics
Internal Accessories
5h
1h LTD operating time at 125% 1000s(TL=150s set) 670s(TL=100s set) 400s(TL= 60s set) 80s(TL= 12s set)
30min 20min 14min 10min 6min 4min
Current setting Ir: 200-400A (Adjustable)
Operating time
Rated Current In: 400A
(*1)
(*1)
Note
*1 Right-side mounting is standard of SHT and UVT. Specify separately for left-side mounting. Remarks: 1. Specification of 4-pole model is same as that of NF800-UEW. 2. Refer to page 106.
30s 20s Pre-alarm pickup current Ip
STD pickup current Is Ir x(2-2.5-3-3.5-4 -5-6-7-8-10) ±15%
Ir x(0.70-0.75 -0.8-0.85-0.9 ±10% -0.95-1.0)
Current Reducing Curve
1s
Tp=
STD operating time Ts 0.3 ± 0.06s 0.2 ± 0.04s
TL ±20% 2
(at 200%)
0.1s
0.1 ± 0.03s 0.06 ± 0.02s
0.05s INST pickup current II x4-x16 ±15% (Magnification to In)
0.02s 0.01s 60 70
100 125
200
300
400 500 600 700
1000
Max. total breaking time 1500 2000
3000 4000
Current (% of Ir) Instantaneous tripping current (% of In)
130
Rated ambient temperature
0.2s
Pre-alarm operating time Tp
Continuous load current (%)
0.5s
120 110 100 90 80 70 0
10
20
30
40
50
Ambient temperature (°C)
Accessories
1 Characteristics and Dimensions
Operating handle
F
Type name
F-4U
Reference page 117
V
V-4U
119
Mechanical interlock
MI
MI-4SW3
129
Auxiliary handle
HT
HT-4SW
128
Accessories Terminal cover
7 External Accessories
Large
TC-L
Type name 3P
Skeleton
TTC
3P
−
BTC HL
3P
BTC-4SW3
Handle lock device
HL-S
Note *1 Specify the operation method and voltage. Order in combination with the breaker unit. Remark *1 Specification of 4-pole model is same as that of NF800-UEW.
Reference page
TCL-4SW3
Rear
Electrical operation device
160
PAL
(*1)
(*1)
2min
2s
Lead wire direction
SHT or UVT
LTD operating time TL 12-60-100-150s ±20% (at 200%)
1min
5s
AX
Operating characteristics NF400-UEW
2h
10s
Operating handle Right-side AL mounting
Left-side mounting
10h
HL-4SW HLS-4UW (*1)
121
127 133
60
7 Characteristics and Dimensions
1 Molded Case Circuit Breakers NF400-UEW
Outline Drawing
Front connection
127.5
Insulating barrier (removable)
78
Breaker
8
f7
f12.5
47
f10.5
43
39
25
16
191.5
28
200 5
140
118
1.0mm clearance on each side of the handle frame.
3-pole
204
3-pole
M6 tap or f7
Conductor drilling for direct connection
194
112
44
Conductor thickness t=8 max.
141
f14 M12 bolt
252
Front-panel cutout
Drilling plan
Boring dimensions for rear connection type barriers (3-pole)
Rear connection
Mounting plate
Line side
Groove for reducing heat by overcurrent
Breaker
Stud can be rotated 90°
8
8
6-f35 24 24
51
92
f7
f12.5
156
234
11.5
31 102
257
297 Trip button
R6
Mounting hole
26
Breaker
43
110
Conductor thickness t=8 max.
M6 screw or f7
210
24 24 11 f35
M6 screw for mounting breaker
8 87
265
234
265
234
f13 M12 bolt
83
128
26
14
25 20 20
10
4-M6 tap or f7
305
265
Connection allowance
Load side
Drilling plan
3-pole
8-M4 screw Add these tapped holes in 8 positions to standard boring.
87
87
Insulation tube
11
44
44
Note The bore dimensional drawing shows the breaker viewed from the rear.
Plug-in
Plug-in terminal block
Breaker
7
24
Stud attachable in this direction only
28
f13 M12 bolt
87
Insulating barrier
1 Characteristics and Dimensions
3-pole
15
79
218
160
28 18
175
Connection allowance
8
24
M8 terminal block mounting screw
265
297
320
Mounting angle
max. 203
35
Mounting angle
f10 44
3-pole Drilling plan
161
Characteristics and Dimensions
7
Molded Case Circuit Breakers
1
NF630-CW NF630-SW
Model
NF630-CW
Rated current In (A) Number of poles
2
Rated insulation voltage Ui (V) Rated short-circuit breaking capacity (kA)
NF630-SW
500 600 630
AC
IEC 60947-2 (Icu/Ics)
DC (*1)
3
2
3
690
690
690V
−
10/10
500V
18/9
30/30
440V
36/18
42/42
400V
36/18
50/50
230V
50/25
85/85
250V
20/10
40/40
4
Mounting screw: M6×72 (4pcs) Front connection Insulating barrier: (2P: 2pcs, 3P: 4pcs, 4P: 6pcs) Rear Mounting screw: M6×85 (4pcs) connection
Standard attached parts
Note *1 When wired as shown at the bottom of page 14, 3-pole models can be used for up to 400VDC, and 4-pole models for up to 500VDC.
NF630-SW
Operating Characteristics 4h
4h
2h
2h Operating characteristics
1h
NF630-SW
30min 20min 14min 10min
6min 4min
6min 4min
2min
2min
1min
1min Max.
Operating time
30s 20s
Operating time
Operating characteristics
1h
NF630-CW
30min 20min 14min 10min
10s 5s
Min.
2s
Max.
30s 20s 10s 5s
Min.
2s
1s
1s AC
0.5s
0.5s
0.2s
0.2s
DC
Max.total interrupting time
0.1s
AC Max.total interrupting time
0.1s
0.05s
0.05s
0.02s 0.01s
DC
Time delay trip 100 125
200
300
0.02s
Instantaneous trip
400 500 600 700
1000
1500
2000
0.01s
3000 4000
Time delay trip 100 125
200
300
% of rated current
2000
AX
(*1)
Lead wire direction
SHT or UVT
(*1)
130
(*1)
120 110 100 90 80
Note *1 Right-side mounting is standard of SHT and UVT. Specify separately for left-side mounting. Remark: 1. Refer to page 106.
0
10
20
30
40
Ambient temperature (°C)
External Accessories Operating handle
Type name
F V
Mechanical interlock
MI
Auxiliary handle
HT
117
V-4S
119
2, 3P MI-4SW3 4P
Reference page
F-4S
MI-4SW4 HT-4SW
129 128
Note *1 Specify the operation method and voltage. Order in combination with the breaker unit.
Accessories Terminal cover
Accessories
Large
Type name TC-L
Skeleton
TTC
Rear
BTC
Handle lock device Electrical operation device
162
3000 4000
Rated ambient temperature
Operating handle Right-side AL mounting
(*1)
1 Characteristics and Dimensions
1500
Temperature Compensation Curve Current rating (%)
7
1000
% of rated current
Internal Accessories Left-side mounting
Instantaneous trip
400 500 600 700
2, 3P
TCL-4SW3
4P
TCL-4SW4
2, 3P
TTC-4SW3
4P 2, 3P
TTC-4SW4 BTC-4SW3
4P
HL-4SW
HL-S
HLS-4SW 3P 4P
121
BTC-4SW4
HL
NFM
Reference page
(*1)
127 133
50
60
7 Characteristics and Dimensions
1 Molded Case Circuit Breakers NF630-CW · NF630-SW
Outline Drawing
12
Front connection 94.5
CL
Conductor thickness t=10 max.
28
4-pole
44 30
16
8
Breaker
39 102
CL
f12.5
59
39
Trip button
f7
CL
Neutral pole
194
257
CL
118
44 97
f14 M12 bolt
56
51
168
112
185
140
196
3-pole
4-pole
103 5
44
107
1.0mm clearance on each side of handle.
M6 screw or f7
44
3-pole
155
Front-plate cutout
4-pole Drilling plan Boring dimensions for rear connection type barriers (3-pole)
Rear connection
4-pole Breaker
Stud can be rotated 90°
3-pole
Line side
Eddy-current heat-reducing slit
6-f35
CL
Connection allowance
225
194
225
194
14
4-M6 tap or f7
24 24
M6 breaker mounting screw 44
8
10 f13 M12 bolt
113
CL
83
128
225
20
265
M6 screw or f7
32
25 20
8
8
CL
24 24
Mounting plate
CL
R6
CL
Breaker
CL
Conductor drilling for direct connection
Mounting hole
CL
3-pole
f10.5
Conductor thickness t=10 max. 43
110
CL
92
Insulating barrier (removable)
Insulating tube attached to 3P:Center pole 4P:Center and neutral poles
87 130.5
f35
87
44
11
43.5 130.5
3-pole
11
44
8-M4 screw Add these tapped holes in 8 positions to standard boring.
87
4-pole
Load side
Drilling plan Note The bore dimensional drawing shows the breaker viewed from the rear.
Plug-in
4-pole Mounting plate
3-pole
CL
CL
Breaker
CL
135
7
f10 Stud attachable in this direction only
30
121 f13 M12 bolt
110 165.5
Insulating barrier
44
87
136
181
1 Characteristics and Dimensions
55
93 160
28 18
CL
163
Connection allowance
25
M8 terminal block mounting screw
20
25
225
CL
10
280
55
35
Plug-in terminal block
3-pole 4-pole Drilling plan
Remark: 1. 2-pole models are 3-pole models with the central pole removed.
163
Characteristics and Dimensions
7
1
Molded Case Circuit Breakers
NF630-SEW NF630-HEW NF630-REW
Model
NF630-SEW
NF630-HEW
Number of poles
3
Rated insulation voltage Ui (V) Rated short-circuit breaking capacity (kA)
NF630-REW
300-630 adjustable
Rated current In (A)
IEC 60947-2 (Icu/Ics)
AC
3
4
3
690
690
690V
10/10
35/18
−
500V
30/30
50/50
70/35
440V
42/42
65/65
125/63
400V
50/50
70/70
125/63
230V
85/85
100/100
150/75
Mounting screw: M6×72 (4pcs) Insulating barrier: (3P: 4pcs, 4P: 6pcs)
Front connection Rear connection
Standard attached parts
4 690
Mounting screw: M6×85 (4pcs)
NF630-SEW
Operating Characteristics
Internal Accessories Left-side mounting
10h Operating characteristics NF630-SEW NF630-HEW NF630-REW
5h 2h 1h LTD operating time at 125% 1000s(TL=150s set) 670s(TL=100s set) 400s(TL= 60s set) 80s(TL= 12s set)
30min 20min 14min 10min 6min 4min
Current setting Ir: 300-630A (Adjustable)
(*1)
Operating time
(*1)
(*1)
Note *1 Right-side mounting is standard of SHT and UVT. Specify separately for left-side mounting. Remark: 1. Refer to page 106. Pre-alarm pickup current Ip
Current Reducing Curve
STD pickup current Is Ir x(2-2.5-3-3.5-4 -5-6-7-8-10) ±15%
Ir x(0.70-0.75 -0.8-0.85-0.9 ±10% -0.95-1.0)
Tp=
TL 2
STD operating time Ts 0.3 ± 0.06s 0.2 ± 0.04s
±20%
0.1 ± 0.03s 0.06 ± 0.02s
(at 200%)
0.1s 0.05s
INST pickup current II x4-x15 ±15% (Magnification to In)
0.02s 0.01s 60 70
100 125
200
300
400 500 600 700
1000
Max. total breaking time 1500 2000
3000 4000
Current (% of Ir) Instantaneous tripping current (% of In)
Accessories
1 Characteristics and Dimensions
Operating handle
F V
Mechanical interlock
MI
Auxiliary handle
HT
Type name
Reference page 117
V-4S
119
MI-4SW3
4P
MI-4SW4 HT-4SW
110 100 90 80 70
129 128
Accessories
10
20
30
Type name
Large
TC-L
Skeleton
TTC
Rear
Handle lock device Electrical operation device Notes *1 Specify the operation method and voltage. Order in combination with the breaker unit. *2 This is for NF630-SEW. For rear terminal cover of NF630-HEW/REW, use PTC-4SW3. *3 This is for NF630-SEW/HEW.
164
120
40
50
60
Ambient temperature (°C)
F-4S 3P
130
0
Terminal cover
7 External Accessories
Rated ambient temperature
0.2s
Pre-alarm operating time Tp
Continuous load current (%)
1s 0.5s
PAL
(*1)
30s 20s
2s
Lead wire direction
SHT or UVT
LTD operating time TL 12-60-100-150s ±20% (at 200%)
2min
5s
AX
Rated Current In: 630A
1min
10s
Operating handle Right-side AL mounting
BTC
3P
TCL-4SW3 (*2)
4P
TCL-4SW4 (*3)
3P
TTC-4SW3
4P 3P
TTC-4SW4 BTC-4SW3 (*2)
4P
HL-4SW
HL-S
HLS-4SW 3P 4P
121
BTC-4SW4 (*3)
HL
NFM
Reference page
(*1)
127 133
7 Characteristics and Dimensions
1 Molded Case Circuit Breakers NF630-SEW · NF630-HEW · NF630-REW
Outline Drawing
12
Front connection 94.5
CL
Conductor thickness t=10 max.
28
4-pole
44 30
16
8
Breaker
39 102
CL
f12.5
59
39
Trip button
f7
CL
Neutral pole
194
257
CL
118
44 97
f14 M12 bolt
56
51
168
112
185
140
196
3-pole
4-pole
103 5
107
1.0mm clearance on each side of handle.
M6 screw or f7
44
44
3-pole
155
Front-plate cutout
4-pole Drilling plan Boring dimensions for rear connection type barriers (3-pole)
Rear connection
4-pole Breaker
Stud can be rotated 90°
3-pole
Line side
Eddy-current heat-reducing slit
6-f35
CL
Connection allowance
225
194
225
194
14
4-M6 tap or f7
24 24
M6 breaker mounting screw f35
44
8
10 f13 M12 bolt
113
CL
83
128
225
20
265
M6 screw or f7
32
25 20
8
8
CL
24 24
Mounting plate
CL
R6
CL
Breaker
CL
Conductor drilling for direct connection
Mounting hole
CL
3-pole
f10.5
Conductor thickness t=10 max. 43
110
CL
92
Insulating barrier (removable)
Insulating tube attached to 3P:Center pole 4P:Center and neutral poles
87 130.5
44
11
87
43.5
3-pole
4-pole
11
44
130.5
8-M4 screw Add these tapped holes in 8 positions to standard boring.
87 Load side
Drilling plan Note The bore dimensional drawing shows the breaker viewed from the rear.
Plug-in
4-pole Mounting plate
3-pole
CL
CL
CL
Breaker
135
7
f10 Stud attachable in this direction only
30
121 f13 M12 bolt
110 165.5
Insulating barrier
44
87
136
181
3-pole
1 Characteristics and Dimensions
55
93 160
28 18
CL
163
Connection allowance
25
M8 terminal block mounting screw
20
25
225
CL
10
280
55
35
Plug-in terminal block
4-pole Drilling plan
165
Characteristics and Dimensions
7
Molded Case Circuit Breakers
1
NF800-CEW NF800-SEW NF800-HEW NF800-REW
Model
NF800-CEW
NF800-SEW
Number of poles
3
Rated insulation voltage Ui (V) Rated short-circuit breaking capacity (kA)
NF800-HEW
NF800-REW
400-800 adjustable
Rated current In (A)
IEC 60947-2 (Icu/Ics)
AC
Standard attached parts (4-pole models are provided with auxiliary handle.)
3
690
4
3
690
4
3
690
690
690V
−
10/10
15/15
−
500V
18/9
30/30
50/50
70/35
440V
36/18
42/42
65/65
125/63
400V
36/18
50/50
70/70
125/63
230V
50/25
85/85
100/100
150/75
Mounting screw: M6×35 (4pcs) Insulating barrier: (3P: 2pcs, 4P: 3pcs)
Front connection Rear connection
Mounting screw: M6×40 (4pcs)
NF800-SEW
Operating Characteristics
Internal Accessories
10h
2h
Operating handle Right-side AL mounting
Left-side mounting
Operating characteristics NF800-CEW NF800-SEW NF800-HEW NF800-REW
5h
AX
Lead wire direction
SHT or UVT
PAL
1h LTD operating time at 125% 1000s(TL=150s set) 670s(TL=100s set) 400s(TL= 60s set) 80s(TL= 12s set)
30min 20min 14min 10min 6min 4min
Current setting Ir: 400-800A (Adjustable)
(*1)
1min
Current Reducing Curve
STD pickup current Is Ir x(2-2.5-3-3.5-4 -5-6-7-8-10) ±15%
1s 0.5s
Pre-alarm operating time Tp
0.2s
Tp=
STD operating time Ts 0.3 ± 0.06s 0.2 ± 0.04s
TL ±20% 2
0.1 ± 0.03s 0.06 ± 0.02s
(at 200%)
0.1s 0.05s
INST pickup current II x4-x12 ±15% (Magnification to In)
0.02s 0.01s 60 70
100 125
200
300
400 500 600 700
1000
Max. total breaking time 1500 2000
3000 4000
Current (% of Ir) Instantaneous tripping current (% of In)
7
130
Rated ambient temperature
2s
Pre-alarm pickup current Ip Ir x(0.70-0.75 -0.8-0.85-0.9 ±10% -0.95-1.0)
Working current correcting ratio (%)
5s
(*1)
Note *1 Right-side mounting is standard of SHT and UVT. Specify separately for left-side mounting. Remark: 1. Refer to page 106.
30s 20s 10s
(*1)
LTD operating time TL 12-60-100-150s ±20% (at 200%)
2min
Operating time
(*1)
Rated Current In: 800A
120 110 100 90 80 70 0
10
20
30
40
50
60
Ambient temperature (°C)
Accessories Operating handle
Type name
F
F-8S
V
Mechanical interlock
MI
Auxiliary handle
HT
V-8S 3P
MI-8SW3
4P
MI-8SW4 HT-4SW
Reference page 117 119 129 128
Accessories Terminal cover
1 Characteristics and Dimensions
External Accessories TC-L
Skeleton
TTC
Rear
Handle lock device Electrical operation device Note *1 Specify the operation method and voltage. Order in combination with the breaker unit.
166
Type name
Large
BTC
3P
TCL-8SW3
4P
TCL-8SW4
3P
TTC-8SW3
4P 3P
TTC-8SW4 BTC-8SW3
4P
HL-4SW
HL-S
HLS-8SW 3P 4P
121
BTC-8SW4
HL
NFM
Reference page
(*1)
127 133
7 Characteristics and Dimensions
1 Molded Case Circuit Breakers
NF800-CEW · NF800-SEW · NF800-HEW · NF800-REW
Outline Drawing
Front connection
94.5 46
4-pole 8
102 f14
8
51
70
40 140
210
210
280
3-pole
15
46 97
107
5
f14 M12 bolt
70
51
70
M6 tap or f7
172
40
103
Neutral pole
4-pole
22
(Conductor thickness t=10 max.)
3-pole
Conductor drilling for direct connection
155 217
1.0mm clearance on each side of the handle frame.
4-pole
Front-panel cutout
Drilling plan
Boring dimensions for rear connection type barriers (3-pole)
Rear connection
M6 tap or f7 Breaker
Groove for reducing heat by overcurrent
6-f48
243
243
12.5
295
4-M6 tap or f7
10 8 113
24 24
45
13
243
10
10
24 24
5
5
Stud can be rotated 90°
Connection allowance 25 Mounting plate
8
32 15
70
70
140 f13 M12 bolt
110
M6 screw for mounting breaker
140
3-pole
f48
Drilling plan
11
70
11
70
210
8-M4 screw Add these tapped holes in 8 positions to standard boring.
140
4-pole
Plug-in
Mounting plate
Stud can be rotated 90
Plug-in terminal block
Breaker
7
56 70 208
3-pole
f10
Drilling plan
1 Characteristics and Dimensions
f13 M12 bolt
112
8 32 140
15
25
301
13
40 M8 terminal block mounting screw
155
56 23 126
Connection allowance
10
243
20
187
Trip button
R6
f8.5
12
8 32
14
Breaker
Terminal dimension for directly connecting conductor f8
275
15
87
32
Auxiliary handle (removable)
N
3-pole
Breaker
92
87
32
110
26
Conductor thickness t=12 max.
243
Insulating barrier (removable)
Mounting hole
140 278
4-pole
167
Characteristics and Dimensions
7
1
Molded Case Circuit Breakers
NF800-SDW
Model
NF800-SDW
Rated current In (A)
(700), 800
Number of poles
2
Rated short-circuit breaking capacity (kA)
Rated insulation voltage Ui (V) IEC 60947-2 (Icu/Ics) Time constant not larger than 10ms
690
DC
Standard attached parts (4-pole models are provided with auxiliary handle.)
250V
40/40
Front connection Rear connection
Mounting screw: M6×35 (4pcs) Insulating barrier: (2P: 1pc, 3P: 2pcs, 4P: 3pcs) Mounting screw: M6×40 (4pcs)
NF800-SDW
Operating Characteristics
Internal Accessories
4h 2h
Operating characteristics NF800-SDW
1h 30min 20min 14min 10min
Max.
1min. 30s 20s
Control setting
Inst trip current (A)
Lo 2 3 Hi
2600±520 3900±780 5200±1040 6500±1300
(*1)
(*1)
(*1)
Note *1 Right-side mounting is standard of SHT and UVT. Specify separately for left-side mounting. Remark: 1. Refer to page 106.
10s Min.
5s
Temperature Compensation Curve
2s 1s
130
0.1s
Current rating (%)
Adjustment range 800A
0.2s
Max. total interrupting time
0.05s 0.02s 0.01s
Time-delay trip
100 125
200
Inst trip 300
400 500 600 700
1000
1500 2000
3000 4000
Accessories
F V
Mechanical interlock
MI
Auxiliary handle
HT
Type name
4P
Reference page
F-8S
117
V-8S
119
2, 3P MI-8SW3 MI-8SW4 HT-4SW
110 100 90
10
20
30
40
50
60
Ambient temperature (°C)
129 128
Accessories Terminal cover
7 External Accessories
120
80 0
% of rated current
Operating handle
Rated ambient temperature
Adjustment range 700A
0.5s
1 Characteristics and Dimensions
Lead wire direction
SHT or UVT
(*1)
Inst. trip adjustment range (4 steps)
2min
Type name
Large
TC-L
Skeleton
TTC
Rear
Handle lock device Electrical operation device Note *1 Specify the operation method and voltage. Order in combination with the breaker unit.
168
AX
700A,800A DC
6min 4min
Operating time
Operating handle Right-side AL mounting
Left-side mounting
BTC
2, 3P
TCL-8SW3
4P
TCL-8SW4
2, 3P
TTC-8SW3
4P 2, 3P
TTC-8SW4 BTC-8SW3
4P
HL-4SW
HL-S
HLS-8SW 2, 3P 4P
121
BTC-8SW4
HL
NFM
Reference page
(*1)
127 133
7 Characteristics and Dimensions
1 Molded Case Circuit Breakers NF800-SDW
Outline Drawing
Front connection
94.5 Conductor thickness t=12 max.
26
46
12
102 f14
f8
275 87
15
51
70
40 140
210
210
280
3-pole
4-pole
3-pole
22
8
51
40
46 Trip button
R6
M6 tap or f7
70
f8.5
15
8 32
32
14
Terminal dimension for directly connecting conductor
92
87
32
Breaker
Auxiliary handle (removable)
N
4-pole 3-pole
8
172
243
Insulating barrier (removable)
110
Mounting hole
Breaker
97
Neutral pole 5
f14 M12 bolt
1.0mm clearance on each side of the handle frame.
103
(Conductor thickness t=10 max.)
107
Conductor drilling for direct connection
155
Front-panel cutout 70
217
4-pole Drilling plan
Boring dimensions for rear connection type barriers (3-pole)
Rear connection
Connection allowance 25
M6 tap or f7
Stud can be rotated 90° Breaker
Groove for reducing heat by overcurrent
6-f48
243
243
12.5
295
4-M6 tap or f7
10
8 8
113
24 24
45
13
243
10
10
24 24
5
5
Mounting plate
32
f13 M12 bolt
110
70
70
140
15
M6 screw for mounting breaker
11
70 140
f48
3-pole
11
70
210
8-M4 screw Add these tapped holes in 8 positions to standard boring.
140
4-pole Drilling plan
Plug-in
Mounting plate
Stud can be rotated 90°
Plug-in terminal block
Breaker
56
112
8 32 140
1 Characteristics and Dimensions
126
M8 terminal block mounting screw
187
56
7
15
40 23
155
13
25
Connection allowance
301
243
20
70 f13 M12 bolt
208
f10
3-pole
140 278
4-pole Drilling plan
Remarks: 1. Standard specification of NF800-SDW is 2-pole model. 3-pole and 4-pole models are available for DC special voltage. 2. 2-pole models are 3-pole models with the central pole removed.
169
Characteristics and Dimensions
7
1
Molded Case Circuit Breakers
NF800-UEW
Model
NF800-UEW 400-800 adjustable
Rated current In (A) Number of poles
3
4
Rated short-circuit breaking capacity (kA)
Rated insulation voltage Ui (V)
IEC 60947-2 (Icu/Ics)
690
AC
Standard attached parts (4-pole models are provided with auxiliary handle.)
690V
35/35
500V
170/170
440V
200/200
400V
200/200
230V
200/200
Mounting screw: 3P: M6×35, M6×132 (2pcs each) 4P: M6×35 (3pcs), M6×132 (2pcs) Insulating barrier: (3P: 2pcs, 4P: 3pcs) Mounting screw: 3P: M6×40, M6×137 (2pcs each) Rear connection 4P: M6×40 (3pcs), M6×137 (2pcs) Front connection
NF800-UEW
Operating Characteristics
Internal Accessories
5h
1h
Current setting Ir: 400-800A (Adjustable)
LTD operating time at-125% 1000s(TL=150s set) 670s(TL=100s set) 400s(TL= 60s set) 80s(TL= 12s set)
30min 20min 14min 10min 6min 4min
Operating time
(*1)
Rated Current In: 800A
(*1)
Note *1 Right-side mounting is standard of SHT and UVT. Specify separately for left-side mounting. Remark: 1. Refer to page 106.
30s 20s Pre-alarm pickup current Ip
Current Reducing Curve
STD pickup current Is Ir x(2-2.5-3-3.5-4 -5-6-7-8-10) ±15%
Ir x(0.70-0.75 -0.8-0.85-0.9 ±10% -0.95-1.0)
STD operating time Ts 0.3 ± 0.06s 0.2 ± 0.04s
TL ±20% 2 (at 200%)
Tp=
0.1s
0.1 ± 0.03s 0.06 ± 0.02s
0.05s INST pickup current II x4-x12 ±15% (Magnification to In)
0.02s 0.01s 60 70
100 125
200
300
400 500 600 700
1000
Max. total breaking time 1500 2000
3000 4000
Current (% of Ir) Instantaneous tripping current (% of In)
Accessories
1 Characteristics and Dimensions
Operating handle
F
Type name
V
Mechanical interlock
MI
Auxiliary handle
HT
− 3P
MI-8SW3
4P
MI-8SW4 HT-4SW
Reference page
Accessories
119 129 128
Large
TC-L
Skeleton
TTC
Rear
BTC
Handle lock device
90 80 70 10
20
Note *1 Specify the operation method and voltage. Order in combination with the breaker unit.
Type name 3P
TCL-8UW3
4P
TCL-8UW4
3P
−
4P
−
3P
BTC-8SW3
4P
30
40
50
Reference page
121
BTC-8SW4
HL
HL-4SW
HL-S
HLS-8UW
Electrical operation device
170
110 100
Ambient temperature (°C)
117
F-8U
120
0
Terminal cover
7 External Accessories
130
Rated ambient temperature
0.2s
Pre-alarm operating time Tp
Continuous load current (%)
1s 0.5s
PAL
(*1)
(*1)
2min
2s
Lead wire direction
SHT or UVT
LTD operating time TL 12-60-100-150s ±20% (at 200%)
1min
5s
AX
Operating characteristics NF800-UEW
2h
10s
Operating handle Right-side AL mounting
Left-side mounting
10h
(*1)
127 133
60
7 Characteristics and Dimensions
1 Molded Case Circuit Breakers NF800-UEW
Outline Drawing
Front connection
Insulating barrier (removable)
44 (ON side) 123.5 (OFF side)
143
Mounting hole
64 8
27.5
f14
Auxiliary handle (removable)
f7
87
110
Conductor thickness t=12 max.
12
3-pole Breaker
Conductor drilling for direct connection Conductor thickness t=8 max.
Insulating barrier (removable)
R6
143
92
f14
252 314
97 6.5 51
f7
f14
Auxiliary handle (removable)
172
3-pole
51
4-pole
Drilling plan
102
f7 f14
48
Trip button
70 M6 screw or f7
6.5
35
141
Neutral pole
70
194
f14 M12 bolt
210
Front-panel cutout
112
16
N
1.0mm clearance on each side of the handle frame.
15 275
290
322
27.5
48
110
70 Breaker
70
22.5
(Conductor thickness t=10 max.)
204
Mounting hole
4-pole
40
200 5
f14 M12 bolt
4-pole
22
194 Neutral pole
280
3-pole
102
f7
210
210
275
322 40 140
8 143
15
70
87
32
14 51
f8.5
8
N
Trip button
Terminal dimension for directly connecting conductor
15 112
200
280
204
5
252
NF400-UEW 4-pole
314
Boring dimensions for rear connection type barriers (3-pole)
Mounting plate
6-f48
8
32
f13 M12 bolt
140
M6 screw for mounting breaker
290
342
290
3-pole
10
70
f48
140
24 24
26 20
70
70
10 110
4-M6 tap or f7
290 12.5
15
10 210
342
45
13
290
10
8
10
Connection allowance Stud can be rotated 90° 25
210
4-pole
210
83
f13 M12 bolt
11 70
11
8-M4 screw Add these tapped holes in 8 positions to standard boring.
7
140
1 Characteristics and Dimensions
Groove for reducing heat by overcurrent
24 24
M6 tap or f7 Breaker
5
Mounting plate
Standard direction of stud is horizontal Connection on power side, and vertical on load side. allowance Otherwise, specify the direction. 25
5
Rear connection
NF400-UEW 4-pole
Drilling plan
171
7
Characteristics and Dimensions
Molded Case Circuit Breakers
1
NF1000-SEW NF1250-SEW
Model
NF1000-SEW
NF1250-SEW
500−1000 Adjustable
600−1250 Adjustable
Rated current In (A) Number of poles
3
4
Rated short-circuit breaking capacity (kA)
Rated insulation voltage Ui (V)
IEC 60947-2 (Icu/Ics)
AC
3
4
690
690
690V
25/13
25/13
500V
65/33
65/33
440V
85/43
85/43
400V
85/43
85/43
230V
125/63
125/63
Mounting screw: M8×40 (4pcs) Insulating barrier: (3P: 2pcs, 4P: 3pcs) Auxiliary handle: (1pc) Mounting screw: M8×40 (4pcs) Insulating barrier: (3P: 2pcs, 4P: 4pcs) Auxiliary handle: (1pc)
Front connection Standard attached parts Rear connection
NF1250-SEW
Operating Characteristics 10h
10h
5h
5h
Operating characteristics NF1000-SEW
2h 1h
LTD operating time at-125% 1000s(TL=150s set) 670s(TL=100s set) 400s(TL= 60s set) 80s(TL= 12s set)
30min 20min 14min 10min
Current setting Ir:500-1000A (Adjustable)
Rated Current In:1000A
1h
30s 20s Pre-alarm pickup current Ip
STD pickup current Is
In x(0.7-0.75-0.8-0.85 -0.9-0.95-1.0) ±10%
In x(2-2.5-3-3.5-4 -5-6-7-8-10) ±15%
1min 30s 20s 10s 5s
2s
Pre-alarm pickup current Ip
STD pickup current Is
In x(0.7-0.75-0.8-0.85 -0.9-0.95-1.0) ±10%
In x(2-2.5-3-3.5-4 -5-6-7-8-10) ±15%
2s
1s
1s Pre-alarm operating time Tp
STD operating time Ts
0.5s
0.3 ± 0.06s 0.2 ± 0.04s
Pre-alarm operating time Tp
0.2s
Tp=
TL ±20% 2 (at 200%)
Tp=
0.1s
0.1s
0.1 ± 0.03s 0.06 ± 0.02s
0.05s INST pickup current II x (4-x12) ±15% (Magnification to In)
0.1 ± 0.03s 0.06 ± 0.02s
60 70
100
125
200
300 400 500 600 700
1000
1500 2000
INST pickup current II x (4-x12) ±15% (Magnification to In)
0.02s
Max. total breaking time
0.01s
3000 4000
60 70
100
125
200
300 400 500 600 700
1000
1500 2000
Current (% of Ir) Instantaneous tripping current (% of In)
Current Reducing Curve
Operating handle Right-side AL mounting
AX
SHT or UVT
Lead wire direction
Continuous load current (%)
Internal Accessories Left-side mounting
Max. total breaking time
0.01s
Current (% of Ir) Instantaneous tripping current (% of In)
1 Characteristics and Dimensions
0.3 ± 0.06s 0.2 ± 0.04s
0.05s
0.02s
7
STD operating time Ts
TL ±20% 2 (at 200%)
PAL
130
Rated ambient temperature
0.2s
LTD operating time TL 12-60-100-150s ±20% (at 200%)
2min
Operating time
Operating time
1min
0.5s
120 110 100 90 80 70 0
Remark: 1. Refer to page 106.
10
20
30
40
50
Ambient temperature (°C)
External Accessories (An order for should be placed at the same time as an order of circuit breaker main body.) Accessories Operating handle
F
Mechanical interlock
MI
Type name 3P
F10SW
4P
F10SW4P
3P
MI-10SW3
4P
MI-10SW4
Reference page 117 129
Accessories
Type name
Reference page
Auxiliary handle
HT
HT-10SW
128
Handle lock device
HL
HL ()
127
Large terminal cover
TC-L
Electrical operation device Note *1 Specify the operation method and voltage. Order in combination with the breaker unit.
172
Rated Current In:1250A
6min 4min LTD operating time TL 12-60-100-150s ±20% (at 200%)
2min
5s
Current setting Ir:600-1250A (Adjustable)
LTD operating time at-125% 1000s(TL=150s set) 670s(TL=100s set) 400s(TL= 60s set) 80s(TL= 12s set)
30min 20min 14min 10min
6min 4min
10s
Operating characteristics NF1250-SEW
2h
NFM
3P
TCL-10SW3
4P
TCL-10SW4
3P 4P
(*1)
121 133
60
3000 4000
7 Characteristics and Dimensions
1 Molded Case Circuit Breakers NF1000-SEW · NF1250-SEW
Outline Drawing
Front connection Conductor thickness 15 40 t=82pcs max.
Insulating barrier (removable) 110
Bolt M1250 Mounting hole
Breaker
375 f9.5
406
346
Auxiliary handle (removable)
Neutral pole 140 210
4-pole
3-pole
18.5
70
15 44 133.5 17 140 190 280
70 210 280
43 f13 M12 bolt
f17.5
80
15 32 8
13
M8 tap or f10
3-pole
70
4-pole
Drilling plan
Rear connection 4-pole Mounting plate
3-pole
140
97
269
R11.5
39.5 81.5
273
12 140
8 32 15 97
Bolt M1245
86
Conductor thickness t=62pcs max.
45
13
109
86
Stud can be rotated 90°
18 Connection allowance f13 22
Breaker
35.5
Breaker
M8 screw for mounting breaker
70 230
Insulation cover (removable)
80
70 300
1.0mm clearance on each side of the handle frame.
M8 tap or f10
Front-panel cutout
3-pole 4-pole Drilling plan
Plug-in Mounting plate
Breaker
208
134
f12 70 204
3-pole
140 274
Drilling plan
4-pole
7 1 Characteristics and Dimensions
68
43 140
136
12
Connection allowance f13 Conductor thickness Insulating t=62pcs max. barrier Bolt M1245
15 32 8 104
269
13
30
225
25.5
100.5
105
136
Stud can be rotated 90°
269
28.5
M10 terminal block mounting screw
28.5
Plug-in terminal block
173
7
Characteristics and Dimensions
Molded Case Circuit Breakers
1
NF1250-SDW
Model
NF1250-SDW
Rated current In (Amp.)
1000, 1250
Number of poles
2
Rated short-circuit breaking capacity (kA)
Rated insulation voltage Ui (V) IEC 60947-2 (Icu/Ics) Time constant not large than 10ms
690
DC
250V
40/20
Mounting screw: M8×40 (4pcs) Insulating barrier: (2P: 1pc, 3P: 2pcs, 4P: 3pcs) Auxiliary handle: (1pc) Mounting screw: M8×40 (4pcs) Insulating barrier: (3P: 2pcs, 4P: 4pcs) Auxiliary handle: (1pc)
Front connection Standard Attached parts Rear connection
NF1250-SDW
Operating Characteristics 3h 2h
3h 2h
1h
1h
Operating characteristics NF1250-SDW 1000A
40min 20min 10min
20min
4min
6min 4min
2min
2min
1min
Adjustable range of standard instantaneous tripping current (4 stages)
Min.
10s
Operating time
Position of Standard value of adjusting instantaneous knob tripping current (A) L0 2800±700 2 4200±700 3 5600±700 Hi 7000±700
6s 4s 2s 1s
1min 40s 30s 20s
4s 2s 1s 0.6s 0.4s 0.2s
0.1s
0.1s
Max. total breaking time
0.06s
Max. total breaking time
0.06s
0.04s
0.04s
Time-delay trip
0.01s 100125
200
0.01s 100125
300 400 500 700 1000
2000 3000 5000 7000 4000 Current (% of rated current)
Instantaneous trip 300 400 500 700 1000
2000 3000 5000 7000 4000
Temperature Compensation Curve Lead wire direction
AL
AX
SHT or UVT
MG
EAL
TBL
TBM
ATU
PAL
Continuous load current (%)
Right-side mounting
200
Current (% of rated current)
Internal Accessories
Left-side mounting
Time-delay trip
0.02s
Instantaneous trip
Operating handle
1 Characteristics and Dimensions
Position of Standard value of adjusting instantaneous knob tripping current (A) L0 2800±700 2 4200±700 3 5600±700 Hi 7000±700
6s
0.2s
7
Min.
10s
0.6s 0.4s
0.02s
Adjustable range of standard instantaneous tripping current (4 stages)
130
1000A
Rated ambient temperature
Operating time
40s 30s 20s
Max.
10min
Max.
6min
Operating characteristics NF1250-SDW 1250A
40min
120 110
1200A, 1250A
100 90 80 0
10
20
30
40
50
Ambient temperature (°C)
External Accessories (An order for should be placed at the same time as an order of circuit breaker main body.) Accessories Operating handle
F
Mechanical interlock
MI
Type name 2, 3P F10SW 4P
F10SW4P
2, 3P MI-10SW3 4P
MI-10SW4
Reference page 117 129
Accessories
Reference page
HT
HT-10SW
128
Handle lock device
HL
HL ()
127
Large terminal cover
TC-L
Electrical operation device
NFM
Note *1 Specify the operation method and voltage. Order in combination with the breaker unit.
174
Type name
Auxiliary handle
2, 3P
TCL-10SW3
4P
TCL-10SW4
2, 3P 4P
(*1)
121 133
60
7 Characteristics and Dimensions
1 Molded Case Circuit Breakers NF1250-SDW
Outline Drawing Same dimensions as NF1000-SEW and NF1250-SEW.
Front connection
15 40 Conductor thickness t=82 pcs. max. Bolt M1250
110
Insulation barrier (removable) Mounting hole
Breaker
375 f9.5
Trip button
346
406
Auxiliary handle (removable)
f17.5
80
15 32 8
13
43
70 210 280
140 210
f13 M12 bolt
3-pole
70
18.5
15 44 133.5 17 140 190 280
4-pole
70
M8 screw or f10
3-pole
4-pole Drilling plan
Differing in external dimensions from NF1000-SEW and NF1250-SEW.
Rear connection
4-pole 3-pole
Mounting plate
86 187.5
Stud can be turned 90°.
140
8 32 15 97
70 230
Insulation cover (removable)
70 300 M8 screw or f10
3-pole
97
20.5
Bolt M1245
12 140
18
86
Conductor thickness t=62 pcs. max.
Breaker
R11.5 375
233
Connection allowance 22 f13 45
13
109
18
35.5
Breaker
M8 screw for breaker mounting
80 1.0mm clearance on each side of the handle frame
4-pole Front-panel cutout
Drilling plan
Differing in external dimensions from NF1000-SEW and NF1250-SEW.
Plug-in
Plug-in terminal block Mounting plate Breaker
68 208
25.5 146.5
Bolt M1245
48 318 375 43 140
Insulation barrier
8 32 104
12
Connection allowance Conductor thickness t=62 pcs. max. f13
15
13
30
30 74.5
248
M10terminal block mounting screw Stud can be turned 90°.
70 204
3-pole
f12
Drilling plan
7 1 Characteristics and Dimensions
Remarks: 1. Standard specification of NF1250-SDW is 2-pole model. 3-pole and 4-pole models are available for DC special voltage. 2. 2-pole models are 3-pole models with the central pole removed.
175
7
Characteristics and Dimensions
Molded Case Circuit Breakers
1
NF1600-SEW
Model
NF1600-SEW Adjustable 800−1600
Rated current In (A) Number of poles
3
4
Rated short-circuit breaking capacity (kA)
Rated insulation voltage Ui (V)
IEC 60947-2 (Icu/Ics)
AC
690 690V
25/13
500V
65/33
440V
85/43
400V
85/43
230V
125/63 Mounting screw: M8 × 40 (4pcs) Insulating barrier: (3P: 2pcs, 4P: 3pcs) Auxiliary handle: (1pc) Mounting screw: M8 × 40 (4pcs) Auxiliary handle: (1pc)
Front connection
Standard attached parts
Rear connection
NF1600-SEW
Operating Characteristics
Internal Accessories
10h 5h Operating characteristics NF1600-SEW
2h 1h
LTD operating time at-125% 1000s(TL=150s set) 670s(TL=100s set) 400s(TL= 60s set) 80s(TL= 12s set)
30min 20min 14min 10min
Current setting Ir:800-1600A (Adjustable)
Operating handle Right-side AL mounting
Left-side mounting
Rated Current In:1600A
AX
Lead wire direction PAL
SHT or UVT
6min 4min LTD operating time TL 12-60-100-150s ±20% (at 200%)
Operating time
2min 1min
Remark: 1. Refer to page 106.
30s 20s 10s 5s
Pre-alarm pickup current Ip
STD pickup current Is
In x(0.7-0.75-0.8-0.85 -0.9-0.95-1.0) ±10%
In x(2-2.5-3-3.5-4 -5-6-7-8-10) ±15%
Current Reducing Curve
2s
STD operating time Ts
Pre-alarm operating time Tp
0.3 ± 0.06s 0.2 ± 0.04s
TL ±20% 2 (at 200%)
Tp=
0.1s
0.1 ± 0.03s 0.06 ± 0.02s
0.05s INST pickup current II x (4-12) ±15% (Magnification to In)
0.02s
Max. total breaking time
0.01s 60 70
100
125
200
300
400 500 600 700
1000
1500
2000
3000 4000
1 Characteristics and Dimensions
120 110 100 90 80 70 0
Current (% of Ir) Instantaneous tripping current (% of In)
7
130
Rated ambient temperature
0.2s
Continuous load current (%)
1s 0.5s
10
20
30
40
50
60
Ambient temperature (°C)
External Accessories (An order for should be placed at the same time as an order of circuit breaker main body.) Accessories Operating handle
F
Mechanical interlock
MI
Type name 3P
F10SW
4P
F10SW4P
3P
MI-16SW3
4P
MI-16SW4
Reference page 117 129
Accessories
Reference page
HT
HT-10SW
128
Handle lock device
HL
HL ()
127
Electrical operation device
NFM
Note *1 Specify the operation method and voltage. Order in combination with the breaker unit.
176
Type name
Auxiliary handle
3P 4P
(*1)
133
7 Characteristics and Dimensions
1 Molded Case Circuit Breakers NF1600-SEW
Outline Drawing
Front connection
Conductor thickness t=6W75 max. 20 35
f11
101.5 304.5 364.5
263
3-pole
Neutral pole
4-pole
97
375
130
115
N
17
f9.5
f17.5
406
R11.5 346
(185.5)
(185.5)
18.5
280
203
Breaker
Breaker
Auxiliary handle (removable)
Mounting hole
210
4-pole 3-pole
Bolt M1065
38 15
Insulating barrier 60 (removable) 38
49.5 20 133.5 140 190 280
70
70
3-pole
80
M8 tap or f10
1.0mm clearance on each side of the handle frame.
4-pole
Drilling plan
Front-panel cutout
38
212
18
106 106 318
Connection 15 38 15 allowance
60
Rear connection
Stud can be rotated 90° Mounting angle
Breaker Conductor thickness t=6W75 max. 20
Mounting angle
109
81.5
18
273
273
109 Connection allowance
140
f11 BM1050 bolt
54 70 210
140 4-pole
125
f11 M1050 bolt
M8 tap or f10
70
3-pole
70
4-pole
Drilling plan
7 1 Characteristics and Dimensions
3-pole
38 38 125 15 200
36
15
140
60
38
15
100 max. 160 min.
Conductor thickness t=6W75 max. 20
Mounting angle
269
Stud can be rotated 90°
177
Characteristics and Dimensions
7
Molded Case Circuit Breakers
1
NF1600-SDW
Model
NF1600-SDW
Rated current In (Amp.)
1600
Number of poles
2
Rated short-circuit breaking capacity (kA)
Rated insulation voltage Ui (V) IEC 60947-2 (Icu/Ics) Time constant not large than 10msec
690
DC
Standard Attached parts
250V
40/20
Front connection Rear connection
Mounting screw: M8×40 (4pcs) Insulating barrier: (2P: 1pc, 3P: 2pcs, 4P: 3pcs) Auxiliary handle: (1pc) Mounting screw: M8×40 (4pcs) Auxiliary handle: (1pc)
NF1600-SDW
Operating Characteristics 3h 2h 1h
Operating characteristics of NF1600-SDW, magnetic trip only, 1600 A
40min 20min 10min
Max. allowable current carrying time
6min 4min 2min
Operating time
1min 40s 30s 20s
Adjustable range of instantaneous tripping current (4 stages)
10s
Position of Instantaneous adjusting tripping knob current (A) L0 3200±800
6s 4s
2 3 Hi
2s 1s
4800±800 6400±800 8000±800
Internal Accessories
0.6s 0.4s 0.2s
Operating handle
0.1s
Max. total breaking time
0.06s
7
Right-side mounting
AL
AX
SHT or UVT
MG
EAL
TBL
TBM
ATU
PAL
0.04s 0.02s
Instantaneous trip
0.01s 100125
1 Characteristics and Dimensions
Left-side mounting
200
300 400 500 700 1000
2000 3000 5000 7000 4000 Current (% of rated current)
External Accessories (An order for should be placed at the same time as an order of circuit breaker main body.) Accessories Operating handle
F
Mechanical interlock
MI
Type name 2, 3P F10SW 4P
F10SW4P
2, 3P MI-16SW3 4P
MI-16SW4
Reference page 117 129
Accessories
Reference page
HT
HT-10SW
128
Handle lock device
HL
HL ()
127
Electrical operation device
NFM
Note *1 Specify the operation method and voltage. Order in combination with the breaker unit.
178
Type name
Auxiliary handle
2, 3P 4P
(*1)
133
Lead wire direction
7 Characteristics and Dimensions
1 Molded Case Circuit Breakers NF1600-SDW
Outline Drawing Same dimensions as NF1600-SEW.
Front connection
Conductor thickness t=6width 75 max. 20 35 Bolt M1065 Auxiliary handle (removable)
210
Mounting hole
(185.5)
(185.5)
38 15
60 Insulation barrier (removable) 38 φ11
4-pole 3-pole
Breaker
Breaker 18.5
280
97
375 f17.5 f9.5
406
346
R11.5
130
115
Trip button
101.5 304.5 364.5
203 263
3-pole
4-pole
49.5 20 133.5 17 140 190 280
70
70
3-pole
80
M8 screw or f10
1.0mm clearance on each side of the handle frame
4-pole
Front-panel cutout
Drilling plan
Differing in external dimensions from NF1600-SEW.
Rear connection
Mounting angle
Breaker f11 Bolt M1050 Conductor thickness t=6width 75 max.
Stud can be turned 90°. 140
3-pole
109
38 60 109 233
Connection allowance 15
233
36 140
175 or more 160 or more
Mounting angle
20
Conductor thickness t=6width 75 max. 20
Mounting angle
f11 38 15 Bolt M1050 38 15 Stud in horizontal direction. 125 It cannot be turned 90°. 200
4-pole
70 140
125
375
18 212
106 106 318
38 60
Connection allowance 15 38 15
70 M8 screw or f10
3-pole
4-pole
Drilling plan
Remarks: 1. Standard specification of NF1600-SDW is 2-pole model. 3-pole and 4-pole models are available for DC special voltage. 2. 2-pole models are 3-pole models with the central pole removed.
1 Characteristics and Dimensions
7
179
7
Characteristics and Dimensions
NV32-SV NV63-CV NV63-SV NV63-HV
Earth Leakage Circuit Breakers
2
Model
NV32-SV
Number of poles
3
Rated operational voltage Ue (V)
AC
High-speed type
3
2
3
3
1f2W
3f3W, 1f2W
1f2W
3f3W, 1f2W
3f3W, 1f2W
100-440
100-240
100-440
100-240
100-440
100-440
30
15 30 100/200/500 selectable
(15) 30
(15) 30 100/200/500 selectable
(15) 30 100/200/500 selectable
at IΔn
0.1
0.1
0.1
0.1
at 5IΔn
0.04
0.04
0.04
0.04
Rated current sensitivity (mA)
−
−
−
−
Max operating time (s)
−
−
−
−
Inertial operating time (s) (or more)
−
−
−
−
Max operating time (s)
Time-delay type
Earth-leakage indication system
Rated short-circuit breaking capacity (kA)
NV63-HV (15) 16 20 25 (30) 32 40 50 (60) 63
2
(15) 30 100/200/500 selectable
Rated current sensitivity (mA)
NV63-SV
3f3W, 1f2W
Phase line
Mechanical type (button) Mechanical type (button) Mechanical type (button) Mechanical type (button)
IEC 60947-2 (Icu/Ics)
AC
440V
5/5
−
2.5/2.5
−
7.5/7.5
10/8
415V
5/5
−
2.5/2.5
−
7.5/7.5
10/8
400V
5/5
−
5/5
−
7.5/7.5
230V
10/10
7.5/7.5
15/15
25/19
200V
10/10
7.5/7.5
15/15
25/19
100V
10/10
7.5/7.5
15/15
25/19
Standard attached parts (Front connection)
NV63-SV
NV63-CV
(5) (10) (15) 16 20 25 (5) (10) (15) 16 20 25 (30) 32 40 50 (60) 63 (30) 32 40 50 (60) 63
(5) 6 10 (15) 16 20 25 (30) 32
Rated current In (A)
Mounting screw: M40.755 (2pcs)
(*1)
10/8
Insulation barrier: (2P: 1pc, 3P: 2pcs)
Note *1 Attached to NV63-SV and NV63-HV.
Operating Characteristics 4h
1h
2h 30min 20min 14min 10min
6min 4min
2h
Operating Characteristics NV32-SV 10A-32A NV63-CV 16A-32A NV63-SV 16A-32A NV63-HV 16A-32A
1h
30min 20min 14min 10min
6min 4min Instantaneous trip current is fixed to 600A120A.
2min
1min Operating time
1min
30s 20s 10s 5s
30s 20s
5s Min.
2s
30s 20s 10s 5s Min. 2s
1s
1s
1s
0.5s
0.5s
0.5s
0.2s
0.2s
0.1s
Max. total breaking time
0.05s 0.02s 0.01s
Time-delay trip 1 1.25
2
4
3
Instantaneous trip
5 6 7
10
15
20
30
40
0.2s
0.1s
0.1s
Max. total breaking time
0.05s 0.02s 0.01s
Max. (40A-50A)
1min
10s
Min.
2s
Max. (60A-63A)
2min
Max.
Operating time
Max.
Operating Characteristics NV63-CV 40A-63A NV63-SV 40A-63A NV63-HV 40A-63A
1h 30min 20min 14min 10min
6min 4min
2min Operating time
4h
4h Operating Characteristics NV32-SV 6A
2h
Time-delay trip 1 1.25
2
3
4
0.02s
Instantaneous trip
5 6 7
10
15
20
30
40 50 60 70
Max. total breaking time
0.05s
0.01s
100
Time-delay trip 1 1.25
2
3
100% of rated current
100% of rated current
Earth leakage Tripping Characteristics
4
5 6 7
Instantaneous trip 10
15
20
30
40
100% of rated current
Internal Accessories
4h
Max. total breaking time
High-speed type
2h
Operating handle
1h
Left-side mounting
30min
AL
Right-side mounting
TBM
5s 2s
Temperature Compensation Curve
Test button 130
Current rating (%)
1s 0.5s
2 Characteristics and Dimensions
0.2s 0.1s 0.05s 0.04s
120 110 100
0.02s 0.01s
ZCT
Magnetic device
90 80 –10
50 100
Internal Wiring Diagram
0
10
20
30
40
50
Load side
10s
Line side
7
30s
Rated ambient temperature
Operating time
1min
Lead-wire direction
Rated current sensitivity
2min
Rated nonoperating current
10min 4min
AX
SHT or UVT
Senstivity selector
60
500 1000
Ambient temperature (°C)
Ground-fault current ( 100% of rated current sensitivity)
Leakage indication button
External Accessories Accessories Operating handle
Handle lock device
Type name
Reference page
F
F-05SV
117
V
V-05SV
119
LC
LC-05SV
HL (*1) HL-S
HLF-05SV HLN-05SV HLS-05SV
Note *1 HLF types are used for OFF lock and HLN types for ON lock.
127
Accessories
Terminal cover
MI-05SV3
Small
TC-S
TCS-05SV3
Large
TC-L
Skeleton
TTC
TTC-05SV3
Rear
BTC
BTC-05SV3
Plug-in
PTC
PTC-05SV3
IEC 35mm rail mounting adapters
180
Type name
MI
Mechanical interlock
Reference page 129
TCL-05SV3 TCL-05SV3L
DIN-05SV
121
137
7 Characteristics and Dimensions
2 Earth Leakage Circuit Breakers NV32-SV · NV63-CV · NV63-SV · NV63-HV
Outline Drawing
Front connection
M50.8 screw (M8 for 60 and 63A)
50
24
Test button
12.5 max.
61
50
72
4
25
(16 max. for 60A and 63A)
68
75
8
45
f8.5
22
Trip button
Breaker
f5.5 (f8.5 for 60 and 63A)
f4.5
50
84
112
130
Sensitivity current selector Leakage indication button
M40.7 taps or f5
Applicable wire size: f1.6 to 22mm2 (for M50.8 screw)
111
Insulation barrier (removable)
Mounting hole
(Conductor thickness t=4 max.)
Conductor drilling for direct connection
90
Drilling plan
Rear connection
M40.7 taps or f5 Mounting base 43 (44 for 60A and 63A)
Breaker
Breaker
M6 screw
27 min.
M40.7 breaker mounting screw
f14 70
25
68
42
72
(46 for 60A and 63A)
52
R1
111 50
112
8
112
8
Mounting plate t = 3.2 max.
50
1.0mm clearance on each side of the handle frame
Front-panel cutout
Drilling plan
Plug-in
M50.8 terminal block mounting screw
Mounting plate
80
Plug-in terminal block
Breaker (plug-in terminal block)
7
80 54
16.5 max. 7
5.5
54
116
170 85
11
83.5
54
2 Characteristics and Dimensions
50
21 89
25
M6 screw
82
30 f6.5
Details of terminal
Conductor drilling
f6 hole or M50.8 taps
Drilling plan
Remark: 1. 2-pole models are 3-pole models with the central pole removed.
181
7
Characteristics and Dimensions
NV125-CV NV125-SV NV125-HV
Earth Leakage Circuit Breakers
2
Model
NV125-CV
Rated current In (A) Number of poles
Rated operational voltage Ue (V)
AC
3
3
4
3
3f3W, 1f2W
3f4W
3f3W, 1f2W
3f4W
100-440
100-440
200-440
100-440
200-440
(15) 30 100/200/500 selectable
Rated current sensitivity (mA) High-speed type
30 100/200/500 selectable
4
(30) 100/200/500 selectable
at IΔn
0.1
0.1
0.1
at 5IΔn
0.04
0.04
0.04
Rated current sensitivity (mA)
(100/200/500 selectable)
(100/200/500 selectable)
(100/200/500 selectable)
Max operating time (s)
(0.45/1.0/2.0 selectable)
(0.45/1.0/2.0 selectable)
(0.45/1.0/2.0 selectable)
(0.1/0.5/1.0)
(0.1/0.5/1.0)
(0.1/0.5/1.0)
Mechanical type (button)
Mechanical type (button)
Mechanical type (button)
440V
10/5
25/25
50/38
415V
10/5
30/30
50/38
400V
10/5
30/30
50/38
230V
30/15
50/50
100/75
200V
30/15
100V
30/15
Max operating time (s)
Inertial operating time (s) (or more) Earth-leakage indication system
Rated short-circuit breaking capacity (kA)
NV125-HV
(15) 16 20 (30) 32 40 50 (15) 16 20 30 32 40 50 (60) 63 (75) 80 100 125 (*2) (60) 63 75 80 100 125 (*2)
3f3W, 1f2W
Phase line
Time-delay type
NV125-SV
(60) 63 (75) 80 100 125
IEC 60947-2 (Icu/Ics)
AC
NV125-SV
Standard attached parts (Front connection)
50/50
100/75
50/50
−
Mounting screw: M40.755 (3P: 2pcs, 4P: 4pcs)
(*1)
100/75
−
Insulation barrier: (3P: 2pcs, 4P: 3pcs)
Note *1 Attached to NV125-SV and NV125-HV. *2 In case of time delay type, rated current is prodused with 20 amp. or more.
Operating Characteristics 4h
30min 20min 14min 10min 6min 4min
2h
2h
Operating Characteristics NV125-SV 15A-30A NV125-HV 15A-30A
1h
Operating Characteristics NV125-CV 60A-100A NV125-SV 40A-100A NV125-HV 40A-100A
1h 30min 20min 14min 10min 6min 4min
Instantaneous trip current is fixed to 600A120A.
2min
Operating time
10s 5s Min.
2s
1min
30s 20s 10s 5s Min.
30s 20s 10s 5s Min.
2s
2s
1s
1s
1s
0.5s
0.5s
0.5s
0.2s
0.2s
0.1s
0.1s
Max. total breaking time
0.05s 0.02s 0.01s
2
3
4
5 6 7
10
15
20
30
0.1s
0.02s
Instantaneous trip
Time-delay trip 1 1.25
0.2s Max. total breaking time
0.05s
0.01s
40 50 60 70
Time-delay trip 2
1 1.25
3
100% of rated current
4
0.02s
Instantaneous trip
5 6 7
10
15
20
30
Max. total breaking time
0.05s
0.01s
40
Time-delay trip 1 1.25
2
3
5 6 7
Instantaneous trip 10
15
20
Operating handle High-speed type
Time-delay type 0.45s (Max)
1h
Time-delay type 1s (Max)
Left-side mounting
Time-delay type 2s (Max)
AL
Right-side mounting
Rated current sensitivity Inertial nonoperating time
Inertial nonoperating time
Current rating (%)
0.5s
0.1s 0.05s 0.04s
2 Characteristics and Dimensions
Test button 130
1s
0.2s Inertial nonoperating time
0.02s 0.01s 50 100
500 1000
25 50 100
500 1000
TBM
Internal Wiring Diagram
25 50 100
500 1000
25 50 100
120 110 100
Magnetic device
90 80 –10
500 1000
Line side
2s
Temperature Compensation Curve Rated ambient temperature
5s
Rated nonoperating current
10s
Rated nonoperating current
Operating time
7
30s
Rated current sensitivity
1min
Rated current sensitivity
2min
Rated nonoperating current
4min
AX
SHT or UVT
Lead-wire direction
Rated current sensitivity
Rated nonoperating current
30min 10min
40
Internal Accessories
4h 2h
30
100% of rated current
100% of rated current
Earth leakage Tripping Characteristics
4
0
10
20
30
40
50
60
ZCT
Load side
30s 20s
Max.
2min
Max.(40A-50A)
1min
Max.
6min 4min
Max. (60A-100A)
2min
Operating Characteristics NV125-CV 125A NV125-SV 125A NV125-HV 125A
1h 30min 20min 14min 10min
Operating time
1min Operating time
4h
4h
2h
Senstivity selector
Ambient temperature (°C) Ground-fault current(% of rated current sensitivity)
Leakage indication button
External Accessories Accessories Operating handle
Handle lock device
Type name
Reference page
F
F-1SV
117
V
V-1SV
119
LC
LC-05SV
HL (*1) HL-S
HLF-05SV HLN-05SV HLS-05SV
Notes *1 HLF types are used for OFF lock and HLN types for ON lock. *2 Specify the working voltage. Refer to the reference page for type name.
127
Accessories Mechanical interlock
Terminal cover
MI
MI-05SV3
4P
MI-1SV4
Small
TC-S
Large
TC-L
Skeleton
TTC
TTC-1SV3
Rear
BTC
BTC-1SV3
Plug-in
PTC
PTC-1SV3
Electrical operation device
182
Type name 3P
Reference page 129
TCS-1SV3 3P
TCL-1SV3
4P
TCL-1SV4
(*2)
121
133
7 Characteristics and Dimensions
2 Earth Leakage Circuit Breakers NV125-CV · NV125-SV · NV125-HV
Outline Drawing
Front connection
50
111
f8.5
22
f8.5
8
f4.5
50
112
84
50 112
Breaker
24
Wire connection
Sensitivity current selector Leakage indication button Test button
Trip button
14-2/0AWG CU/AL
M8 screw
Operating time selector (for time-delay type)
130
Mounting hole
130
Solderless terminal for wire size
Insulation barrier (removable)
30 60
90
90
120
61
19 max. Comb conductor 16.5 max.
68
Neutral pole 4
72
M40.7 taps or f5
3-pole
4-pole
(Conductor thickness t=4 max.)
90
3-pole
30
30
45
4-pole
Conductor drilling for direct connection
Drilling plan
Rear connection
4-pole
Breaker
112
R1
111
112
52
8
Mounting plate t = 3.2 max.
3-pole
Breaker
Stud can be rotated 90°
52
Mounting base 102
4-pole
3-pole
16
15 connection allowance
8.5
30
M8 bolt
2.5 15 68 72
5
Insulating tube
15
28
30
60
60
2.5
54.5
M40.7 breaker mounting screw
f18
30
86
90 1.0mm clearance on each side of the handle frame
M40.7 taps or f5
90
3-pole
104.5
4-pole Front-panel cutout
Drilling plan
Plug-in
Mounting plate
Plug-in terminal block
M50.8 terminal block mounting nut or screw mounted directly
3-pole
4-pole
95
125
60
90
7
Breaker (plug-in terminal block)
89
30
80
54
f8.5
54
12
20 max.
30
60
97
127
3-pole
4-pole
Conductor drilling
f6 hole or M50.8 taps
Drilling plan
Remark: 1. Only 3-pole models are available for NV125-CV.
183
2 Characteristics and Dimensions
M8 screw
21
Details of terminal
116
85
5.5
170
11
83.5
54
30
Characteristics and Dimensions
7
NV250-CV NV250-SV NV250-HV
Earth Leakage Circuit Breakers
2
Model Rated current In (A)
NV250-CV
NV250-SV
NV250-HV
125 150 175 200 225 250
125 150 175 200 225 250
125 150 175 200 225 250
Number of poles
3
3
4
3
3f3W, 1f2W
3f3W, 1f2W
3f4W
3f3W, 1f2W
3f4W
100-440
100-440
200-440
100-440
200-440
Phase line Rated operational voltage Ue (V)
AC
30 100/200/500 selectable
Rated current sensitivity (mA) High-speed type
at IΔn
0.1
0.1
0.1
0.04
0.04
0.04
Rated current sensitivity (mA)
(100/200/500 selectable)
(100/200/500 selectable)
(100/200/500 selectable)
Max operating time (s)
(0.45/1.0/2.0 selectable)
(0.45/1.0/2.0 selectable)
(0.45/1.0/2.0 selectable)
(0.1/0.5/1.0)
(0.1/0.5/1.0)
(0.1/0.5/1.0)
Mechanical type (button)
Mechanical type (button)
Mechanical type (button)
440V
15/12
36/36
65/65
415V
25/19
36/36
70/70
400V
25/19
36/36
75/75
230V
36/27
85/85
100/100
200V
36/27
100V
36/27
Inertial operating time (s) (or more) Earth-leakage indication system
Rated short-circuit breaking capacity (kA)
NV250-CV
IEC 60947-2 (Icu/Ics)
AC
Standard attached parts (Front connection)
85/85
100/100
85/85
−
Mounting screw: M40.755 (3P: 2pcs, 4P: 4pcs)
100/100
Insulation barrier: (3P: 4pcs, 4P: 6pcs)
Earth leakage Tripping Characteristics
Operating Characteristics 4h 2h
5s Min.
2s
4min
30s 20s
1min
2min
10s 5s
0.5s
0.5s
0.2s
0.2s
10s 5s 2s 1s
Min.
2s 1s
30s
Rated current sensitivity
10min
Max.
1min
1s
Time-delay type 2s (Max)
Rated nonoperating current
10s
Time-delay type 1s (Max)
Rated current sensitivity
Operating time
30s 20s
Time-delay type 0.45s (Max)
1h
2min
Max.
1min
High-speed type
2h
Rated nonoperating current
2min
4h
30min
Rated nonoperating current
30min 20min 14min 10min 6min 4min
Operating Characteristics NV250-CV 250A NV250-SV 250A NV250-HV 250A
1h 30min 20min 14min 10min 6min 4min
Rated current sensitivity
1h
Rated current sensitivity
Operating Characteristics NV250-CV 125A-225A NV250-SV 125A-225A NV250-HV 125A-225A
Operating time
2h
Rated nonoperating current
4h
Operating time
(30) 100/200/500 selectable
at 5IΔn
Max operating time (s)
Time-delay type
(30) 100/200/500 selectable
4
0.5s Inertial nonoperating time
0.2s 0.1s 0.05s 0.04s
Inertial nonoperating time
Inertial nonoperating time
0.02s
50 100
0.1s
0.1s Max. total breaking time
Time-delay trip 1 1.25
2
3
4
5 6 7
Instantaneous trip 10
15
20
30
40
0.02s 0.01s
2
3
4
5 6 7
10
15
20
TBM
120 110
25 50 100
500 1000
Internal Wiring Diagram Test button
100
ZCT
Magnetic device
90 80 –10
0
10
20
30
40
50
Senstivity selector
60
Leakage indication button
Ambient temperature (°C)
2 Characteristics and Dimensions
500 1000
40
Rated ambient temperature
Right-side mounting
Lead-wire direction
Current rating (%)
7
Left-side mounting
SHT or UVT
30
Temperature Compensation Curve 130
AX
25 50 100
100% of rated current
Internal Accessories AL
500 1000
Ground-fault current(% of rated current sensitivity)
Instantaneous trip
Time-delay trip 1 1.25
100% of rated current
Operating handle
25 50 100
Load side
0.02s
500 1000
Max. total breaking time
0.05s
Line side
0.05s
0.01s
0.01s
External Accessories Accessories Operating handle
Handle lock device
Type name
Reference page
F
F-2SV
117
V
V-2SV
119
LC
LC-05SV
HL (*1) HL-S
HLF-05SV HLN-05SV HLS-2SV
Notes *1 HLF types are used for OFF lock and HLN types for ON lock. *2 Specify the working voltage. Refer to the reference page for type name.
Accessories Mechanical interlock
127 Terminal cover
MI
Small
TC-S
Large
TC-L
MI-05SV3
4P
MI-2SV4
3P
TCS-2SV3
3P
Reference page 129
TCL-2SV3 TCL-2SV3L
4P
TCL-2SV4
Skeleton
TTC
3P
TTC-2SV3
Rear
BTC
3P
BTC-2SV3
Plug-in
PTC
3P
PTC-2SV3
Electrical operation device
184
Type name 3P
(*2)
121
133
7 Characteristics and Dimensions
2 Earth Leakage Circuit Breakers NV250-CV · NV250-SV · NV250-HV
Outline Drawing
30
Front connection
M8 bolt (hex-socket)
Solderless terminal for wire size 125-175A 14-95mm2 200-250A 70-125mm2 Wire connection
24
100
10
f8 .5
C
1
50
f4.5
1
Test button
25 max.
35 70
45
68 4
105
140
3-pole
4-pole
.5
35
f8
61
Neutral pole
105
Or
35 M40.7 taps or f5
9
22
f8.5
100
Trip button
Breaker
C
Leakage indication button
102
144
144
165
Sensitivity current selector
165
100
Operating time selector (for time-delay type)
126
Insulation barrier (removable)
Mounting hole
25 max.
72
3-pole
(Conductor thickness t=7 max.)
92
Conductor drilling for direct connection
4-pole
Drilling plan
Rear connection 4-pole
Mounting base 4-pole
Stud can be rotated 90°
Breaker
Breaker
3-pole
15
72
M40.7 breaker mounting screw
6
15
68
71
f9 M8 bolt
70
Insulation tube
105
106
M40.7 taps or f5
70
1
3-pole
52
R
32.5
35
f24 35
144
126
144
22 connection allowance
20
8
Mounting plate t = 3.2 max.
3-pole
100
35 105
1.0mm clearance on each side of the handle frame
4-pole Front-panel cutout
Drilling plan
31 89 112
30
56.5 54 3-pole 70
Insulation barrier
4-pole 105 3-pole 105 4-pole 140
80 56.5
20 f9 M8 bolt Stud attachable in this direction only
70
105
107
142
3-pole
f6 hole or M50.8 taps
4-pole
Drilling plan
Remark: 1. Only 3-pole models are available for the model of NV250-CV.
185
2 Characteristics and Dimensions
21
15
28 M5 terminal block mounting screw
7 151
6
11
4-pole 145 3-pole 110
70
144
165
190
Mounting plate
34.5
Plug-in terminal block
24 connection allowance
Plug-in
Characteristics and Dimensions
7
NV125-SEV NV125-HEV NV250-SEV NV250-HEV
Earth Leakage Circuit Breakers
2
Model
NV125-SEV
NV125-HEV
NV250-SEV
Rated current In (A)
125
125
250
NV250-HEV 250
Current setting Ir (A)
63-125
63-125
125-250
125-250
Number of poles
3
4
3
4
3
3
Phase line type
3f3W, 1f2W
3f4W
3f3W, 1f2W
3f4W
3f3W, 1f2W
3f3W, 1f2W
Rated operational voltage Ui Rated operational voltage Ue (V)
V
440
440
440
440
AC
100-440
100-440
100-440
100-440
(30) (30) (30) (30) 100/200/500 selectable 100/200/500 selectable 100/200/500 selectable 100/200/500 selectable
Rated current sensitivity (mA) High-speed type Max operating time (s)
Time-delay type
at IΔn
0.1
0.1
0.1
0.1
at 5IΔn
0.04
0.04
0.04
0.04
Rated current sensitivity (mA)
(100/200/500 selectable) (100/200/500 selectable) (100/200/500 selectable) (100/200/500 selectable)
Max operating time (s)
(0.45/1.0/2.0 selectable)
(0.45/1.0/2.0 selectable)
(0.45/1.0/2.0 selectable)
(0.1/0.5/1.0)
(0.1/0.5/1.0)
(0.1/0.5/1.0)
(0.1/0.5/1.0)
Mechanical type (button)
Mechanical type (button)
Mechanical type (button)
Mechanical type (button)
440V
36/36
65/65
36/36
65/65
415V
36/36
70/70
36/36
70/70
400V
36/36
75/75
36/36
75/75
230V
85/85
100/100
85/85
100/100
200V
85/85
100/100
85/85
100/100
100V
85/85
100/100
85/85
100/100
Inertial operating time (s) (or more) Earth-leakage indication system
Rated short-circuit breaking capacity (kA)
IEC 60947-2 (Icu/Ics)
AC
Standard attached parts (Front connection)
Mounting screw: M40.755 (3P: 2pcs, 4P: 4pcs)
(0.45/1.0/2.0 selectable)
Insulation barrier: (3P: 4pcs, 4P: 6pcs)
NV250-SEV
Earth leakage Tripping Characteristics
Operating Characteristics 10h 5h
1h
STD pickup current Is Ir (2–2.5–3–3.5–4 –5–6–7–8–10) ±15%
2s 1s
STD operating time Ts 0.3±0.06s 0.2±0.04s
0.2s 0.1s
STD pickup current Is Ir(2–2.5–3–3.5–4 –5–6–7–8–10)±15%
5s 2s
30s 10s 5s 2s 1s
Inertial nonoperating time
0.2s
0.5s
0.1s 0.05s 0.04s
STD operating time Ts 0.3±0.06s 0.2±0.04s
0.2s
Inertial nonoperating time
0.02s 0.01s
0.1±0.03s
2
I t ON
50 100
500 1000
1 1.25
INST pickup current Ii In2-14 ±15%, Ir14 ±15% 2
3
4
5 6 7
Max. total breaking time
10
15
20
30
40
0.02s 0.01s
0.6 0.7
AX
Right-side mounting
SHT or UVT
TBM
INST pickup current Ii In2-14 ±15%, Ir14 ±15% 2
3
4
5 6 7
15
20
30
500 1000
40
Lead-wire direction
PAL
130
Internal Wiring Diagram
120 110
Test button Magnetic device
100 90 80
(Note *1)
25 50 100
Max. total breaking time
10
Current Reducing Curve Current rating (%)
AL
500 1000
100% of current setting Ir Instantaneous tripping current (% of rated current or % of current setting Ir)
Internal Accessories Operating handle
25 50 100
500 1000
Ground-fault current(% of rated current sensitivity)
1 1.25
100% of current setting Ir Instantaneous tripping current (% of rated current or % of current setting Ir)
2 Characteristics and Dimensions
25 50 100
2
I t OFF
70 –10
(Note *2)
0
10
20
30
40
50
60
CT CT
Magnetic device
Ambient temperature (°C)
Notes *1 For the 24VDC TBM only instruct us of a control voltage. (The standard shared voltage is 100-240VAC/100-240VDC.) *2 SLT-equipped is standard. Control voltage (100-200VAC) is necessary.
Characteristic setting part
ZCT
Line side
0.6 0.7
Inertial nonoperating time
0.5s
0.05s I t OFF
0.02s
7
1min
I t OFF
2
Left-side mounting
2min
6
0.1s
0.1±0.03s
2
I t ON
0.05s
0.01s
4min
Rated current sensitivity
10min
LTD operating time TL 12–60–80–100s ±20% (at 200%)
6
I t ON
1s
0.5s
Time-delay type 2s (Max)
The rated current does not have thermal characteristics. Reduce the current as shown in the curve on the left chart if the ambient temperature exceeds 40°C.
CT
Load side
5s
10s
Time-delay type 1s (Max)
Rated nonoperating current
I t OFF
30s 20s
Time-delay type 0.45s (Max)
1h
Rated current sensitivity
6
1min
High-speed type
2h
Operating time
10s
4h
30min
Rated ambient temperature
30s 20s
LTD operating time at 125% (I t ON) 670s (TL = 100s set) 540s (TL = 80s set) 400s (TL = 60s set) 80s (TL = 12s set)
2min LTD operating time TL 12–60–80–100s ±20% (at 200%)
6
I t ON
Operating time
Operating time
2min 1min
6
30min 20min 14min 10min 6min 4min
Rated nonoperating current
6
LTD operating time at 125% (I t ON) 670s (TL = 100s set) 540s (TL = 80s set) 400s (TL = 60s set) 80s (TL = 12s set)
Rated nonoperating current
1h 30min 20min 14min 10min 6min 4min
Operating Characteristics NV250-SEV NV250-HEV Current setting Ir Rated current In 250A 125-250
2h
Rated current sensitivity
Operating Characteristics NV125-SEV NV125-HEV Current setting Ir Rated current In 63-125 125A
2h
Rated current sensitivity
5h
Rated nonoperating current
10h
Senstivity selector
Leakage indication button
External Accessories Accessories Operating handle
Handle lock device
Type name
Reference page
F
F-2SV
117
V
V-2SV
119
LC
LC-05SV
HL (*1) HL-S
HLF-05SV HLN-05SV HLS-2SV
Notes *1 HLF types are used for OFF lock and HLN types for ON lock. *2 Specify the working voltage. Refer to the reference page for type name.
Accessories Mechanical interlock
127 Terminal cover
MI
Small
TC-S
Large
TC-L
MI-05SV3
4P
MI-2SV4
3P
TCS-2SV3
3P
Reference page 129
TCL-2SV3 TCL-2SV3L
4P
TCL-2SV4
Skeleton
TTC
3P
TTC-2SV3
Rear
BTC
3P
BTC-2SV3
Plug-in
PTC
3P
PTC-2SV3
Electrical operation device
186
Type name 3P
(*2)
121
133
7 Characteristics and Dimensions
2 Earth Leakage Circuit Breakers
NV125-SEV · NV125-HEV · NV250-SEV · NV250-HEV
Outline Drawing
30
Front connection Insulation barrier (removable)
24
Breaker
10
f8
.5
100
126
f4.5
50
102
144
C 1
Sensitivity current selector Leakage indication button Test button
144
Solderless terminal for wire size 125-175A 14-95mm2 200-250A 70-125mm2 Wire connection
1 C
165
100
Operating time selector (for time-delay type)
165
Mounting hole
M8 bolt (hex-socket)
25 max. Or
100 35
70
105
105
Neutral pole
68 4
140
25 max.
72
(Conductor thickness t=7 max.)
92
4-pole
3-pole
35
61 9
22
.5 f8
45
f8.5
Trip button
Trip characteristics selector
35
M40.7 taps or f5
3-pole
Conductor drilling for direct connection
4-pole
Drilling plan
Rear connection 4-pole
Mounting base
Stud can be rotated 90°
3-pole
4-pole
Breaker
3-pole
Breaker
15 68
M40.7 breaker mounting screw
6
15
72
52
R
1
144
126
20
22 connection allowance
144
8
Mounting plate t = 3.2 max.
f9 M8 bolt
71
70
Insulation tube
105
M40.7 taps or f5
70
3-pole
106
32.5
35
f24
35
35
100
105
1.0mm clearance on each side of the handle frame
4-pole Drilling plan
Front-panel cutout
21 31 89 112
30
56.5 54 f9 M8 bolt 3-pole 70
Insulation barrier
4-pole 105 3-pole 105
Stud attachable in this direction only
4-pole 140
80 56.5
20 70
105
107
142
3-pole
f6 hole or M50.8 taps
4-pole Drilling plan
Remark: 1. Only 3-pole models are available for the model of NV250-SEV and NV250-HEV.
187
2 Characteristics and Dimensions
M5 terminal block mounting screw
15
28
151
6
11
7
4-pole 145 3-pole 110
70
144
34.5
Plug-in terminal block
165
190
Mounting plate
24 connection allowance
Plug-in
7
Characteristics and Dimensions
Earth Leakage Circuit Breakers
2
NV400-CW NV400-SW
Model
NV400-CW
NV400-SW
Number of poles
3
Rated operational voltage Ue (V AC) (*1)
100-440 Multi-voltage type
Rated current In (A)
250 300 350 400 (30) 100 · 200 · 500 Selectable
Rated current sensitivity IΔn (mA)
High-speed type
0.04
Max. operating time at 5IΔn (s)
Time-delay type
Rated current sensitivity IΔn (mA)
(100 · 200 · 500 Selectable)
Max. operating time at 2IΔn (s)
(0.45 · 1.0 · 2.0 Selectable) (0.1 · 0.5 · 1.0)
Inertial non-operating time at 2IΔn (s)
Earth-leakage indication system Rated short-circuit breaking capacity (kA) IEC 60947-2 (lcu/lcs) EN 60947-2
Button
AC
440V
25/13
42/42
400V
36/18
45/45
230V
50/25
85/85
Standard attached parts (Front connection)
Mounting screw: M6×60 (4pcs) Insulation barrier: (4pcs)
Note *1 Rated operational voltage of time-delay type is for 200-440V.
NV400-SW
Operating Characteristics
Earth Leakage Tripping Characteristics
4h 2h
20s 10s
NV400-CW
5s Min.
30s 10s 5s 2s 1s
2s
0.5s
1s
0.2s NV400-SW
0.5s
Inertial nonoperating time
Inertial nonoperating time
0.1s
Inertial nonoperating time
0.04s 0.02s
0.2s
Rate current sensitivity
2min 1min
Rate nonoperating current
Max.
30s
Time-delay type 2s. (MAX)
Rate current sensitivity
4min
1min
Time-delay type 1s. (MAX)
Time-delay type 0.45s. (MAX)
Rate nonoperating current
10min
2min
Highspeed type
Rate current sensitivity
6min 4min
Rated current sensitivity
1h 30min
Rated nonoperating current
2h
Operating time
Operating time
4h
Rate nonoperating current
Operating characteristics NV400-CW NV400-SW
1h 30min 20min 14min 10min
0.01s
0.1s Max. total breaking time
25 50 100
0.05s
500 1000
25 50 100
500 1000
25 50 100
500 1000
25 50 100
500 1000
Ground-fault current (% of rated current sensitivity) 0.02s 0.01s 100
Time-delay trip 125
200
Instantaneous trip
300 400 500 600 700 1000
1500 2000
3000
4000
Current (% of rated current)
Internal Accessories
Temperature Compensation Curve
Operating handle Right-side mounting
AL
AX
Lead wire direction
TBM
SHT or UVT
130 Current rating (%)
Left-side mounting
7
110 100 90 80
0
10
20
30
40
50
60
Ambient temperature (°C)
Remark: 1. Refer to page 107.
Internal Wiring Diagram
Operating handle Mechanical interlock
Type name
Reference page
117
Auxiliary handle
HT
HT-4CW, HT-4SW
128
V-4S
119
Large
TC-L
TCL-4SW3
MI-4SW3
129
Terminal cover
Accessories
Reference page
Skeleton
TTC
TTC-4SW3
Rear
BTC
BTC-4SW3
Type name F
F-4S
V MI
Accessories
Handle lock device
HL
HL-4CW, HL-4SW
HL-S
HLS-4SW
Electrical operation device
(*1)
121
Test button
ZCT
Line side
External Accessories
Load side
2 Characteristics and Dimensions
Rated ambient temperature
120
127 133
Sensitivity selector
Magnetic device
Note *1 Specify the operation method and voltage. Order in combination with the breaker unit.
Leakage indication button
188
7 Characteristics and Dimensions
2 Earth Leakage Circuit Breakers NV400-CW · NV400-SW
Outline Drawing
Front connection
94.5 44
Insulating barrier (removable) 28 16
39
43
f12.5
Test button
44 97
f14 M12 bolt
103
51
5
112 140
CL
92
CL
12 25
39
Trip button
47 f7
102
257
Leakage indication button
194
110
CL
Breaker
R6
Sensitivity current selector Operating time selector (Time-delay type)
Mounting hole CL
Breaker
CL
8
Conductor thickness t=8 max.
f10.5
Conductor thickness t=8 max.
44
118
M6 tap or f7
Conductor drilling for direct connection
1.0mm clearance on each side of the handle frame.
107
Front-panel cutout
Drilling plan
155(NV400-SP) 134(NV400-CP)
Boring dimensions for rear connection type barriers (3-pole)
Rear connection
Line side 6-f35 8
C L
Groove for reducing heat by overcurrent
24 24
M6 tap or f7
10 113
8 f13 M12 bolt
87
225
194 24 24
83
128
26
25 20 20
225
194
4-M6 tap or f7
C L
14
265
225
Connection allowance CL
M6 screw for mounting breaker
44
Insulation tube
87
f35
11 44
11
8-M4 screw Add these tapped holes in 8 positions to standard boring.
87
Drilling plan
Load side
Note The bore dimensional drawing shows the breaker viewed from the rear.
7 2 Characteristics and Dimensions
Stud can be rotated 90°
8
Breaker
Mounting plate
189
7
Characteristics and Dimensions
Earth Leakage Circuit Breakers
2
NV400-SEW NV400-HEW NV400-REW
Model
NV400-SEW
Number of poles
3
Rated operational voltage Ue (V AC) (*1)
Time-delay type
3
NV400-REW
4
3
100-440 Multi-voltage type
Rated current In (A) High-speed type
NV400-HEW
4
200-400 adjustable (30) 100 · 200 · 500 Selectable
Rated current sensitivity IΔn (mA)
0.04
Max. operating time at 5IΔn (s) Rated current sensitivity IΔn (mA)
(100 · 200 · 500 Selectable)
Max. operating time at 5IΔn (s)
(0.45 · 1.0 · 2.0 Selectable) (0.1 · 0.5 · 1.0)
Max. inertial non-operating time at 2IΔn (s)
Earth-leakage indication system Rated short-circuit breaking capacity (kA) IEC 60947-2 (Icu/Ics) EN 60947-2
Button
AC
440V
42/42
65/65
400V
50/50
70/70
125/63
230V
85/85
100/100
150/75
Standard attached parts (Front connection)
125/63
Mounting screw: M6×72 (4pcs) Insulation barrier: (3P: 4pcs, 4P: 6pcs)
Note *1 Rated operational voltage of time-delay type is for 200-440V.
NV400-SEW
Operating Characteristics
Earth Leakage Tripping Characteristics
10h 5h
Operating characteristics NV400-SEW NV400-HEW NV400-REW
30s 20s 10s 5s 2s
Pre-alarm pickup current Ip Ir x (0.70-0.75-0.80.85-0.9-0.95 -1.0) ±10%
STD pickup current Is Ir x (2-2.5-3-3.5-45-6-7-8-10) ±15%
2min 1min 30s 10s 5s 2s 1s 0.5s
Pre-alarm operating time Tp TL ±20% Tp= 2 (at 200%)
0.2s 0.1s
INST pickup current II x 4 - x16 ±15% (Magnification to In) 60 70
100 125
0.01s
0.1 ± 0.03 s 0.06 ± 0.02 s
0.02s 200
300
400 500 600 700
1000
Inertial nonoperating time
0.04s 0.02s
0.3 ± 0.06 s 0.2 ± 0.04 s
0.05s
0.01s
0.1s
STD operating time Ts
25 50 100
500 1000
25 50 100
500 1000
25 50 100
500 1000
25 50 100
500 1000
Ground-fault current (% of rated current sensitivity)
Max. total breaking time 1500 2000
Inertial nonoperating time
Inertial nonoperating time
0.2s
1s 0.5s
Time-delay type 2s. (MAX)
Rate current sensitivity
4min
Time-delay type 1s. (MAX)
Time-delay type 0.45s. (MAX)
Rate nonoperating current
1min
Highspeed type
Rate current sensitivity
10min
Rated current sensitivity
1h 30min
LTD operating time TL 12-60-100-150s ±20% (at 200%)
2min
Operating time
2h
Rated nonoperating current
400s (TL= 60s set) 80s (TL= 12s set)
Rated current In: 400A
Operating time
6min 4min
Current setting Ir: 200-400A (Adjustable)
Rate nonoperating current
4h LTD operating time at 125% 1000s (TL=150s set) 670s (TL=100s set)
Rate current sensitivity
1h 30min 20min 14min 10min
Rate nonoperating current
2h
3000 4000
Current setting (% of Ir) Instantaneous tripping current (% of In)
AL
AX
SHT or UVT
Lead wire direction
TBM
PAL
7
120 110 100 90 80 70 0
Remarks: 1. Instead of TBM, pre-alarm module (PAL) can be attached. 2. Refer to page 107.
MI
F-4S
117
V-4S
119
3P
MI-4SW3
4P
MI-4SW4
129
Notes *1 This is for NV400-SEW. *2 This is for NV400-SEW. For rear terminal cover of NV400-HEW/REW, use PTC-4SW3. *3 Specify the operation method and voltage. *3 Order in combination with the breaker unit.
Accessories Auxiliary handle Large
TC-L
Skeleton
TTC
Rear
BTC
Handle lock device
3P
TCL-4SW3 (*1)
4P
TCL-4SW4 (*1)
3P
TTC-4SW3
4P
TTC-4SW4
3P
BTC-4SW3 (*2)
4P
BTC-4SW4
HL
HL-4SW
HL-S
Electrical operation NVM device
190
Type name HT-4SW
HT
HLS-4SW 3P 4P
(*3)
Reference page
Characteristic setting part
128
40
50
60
Test button
Magnetic device
121
127 133
ZCT
N CT
Line side
Mechanical interlock
V
30
Internal Wiring Diagram Reference page
Terminal cover
Operating handle
Type name
F
20
Ambient temperature (°C)
External Accessories Accessories
10
CT CT
Magnetic device
Leakage indication button
In case of 4P
Load side
2 Characteristics and Dimensions
130
Continuous load current (%)
Operating handle Right-side mounting
Left-side mounting
Current Reducing Curve Rated ambient temperature
Internal Accessories
Sensitivity selector
7 Characteristics and Dimensions
2 Earth Leakage Circuit Breakers NV400-SEW · NV400-HEW · NV400-REW
Outline Drawing
Front connection
Insulating barrier (removable)
CL
39
44 97
56
103
51
168
112 140
185
3-pole
4-pole
5
92
194
Conductor drilling for direct connection
44
M6 tap or f7
44 118
107 155
196
CL
f7
39
25 f10.5 Conductor thickness t=8 max.
Neutral pole f14 M12 bolt
CL
12
59
f12.5
102
257
Test button
3-pole
1.0mm clearance on each side of the handle frame.
4-pole
Front-panel cutout
Drilling plan
Boring dimensions for rear connection type barriers (3-pole)
Rear connection
Line side
4-pole
Breaker
6-f35 8
24 24
Groove for reducing heat by overcurrent C C L L
3-pole
8
Stud can be rotated 90°
Mounting plate
M6 tap or f7 225
C L
194
4-M6 tap or f7 194
14
265
225
Connection allowance CL
225
M6 screw for mounting breaker 10 113
8 f13 M12 bolt
87
Insulation tube
24 24
83
128
26
25 20 20
f35
44
44
87
11 44
43.5
130.5
4-pole
8-M4 screw Add these tapped holes in 8 positions to standard boring.
87
130.5
3-pole
11
Load side
Drilling plan
Note The bore dimensional drawing shows the breaker viewed from the rear.
7 2 Characteristics and Dimensions
Trip button
Breaker
CL Breaker
CL
R6
Operating time selector (Time-delay type) Leakage indication button
CL
3-pole
44
Conductor thickness 8 t=8 max. 43
110
16
28
Sensitivity current selector Mounting hole
4-pole
94.5
CL
191
7
Characteristics and Dimensions
Earth Leakage Circuit Breakers
2
NV630-CW NV630-SW
Model
NV630-CW
Number of poles Rated operational voltage Ue (V AC)
100-440 Multi-voltage type
Rated current In (A)
500 600 630 −
Rated current sensitivity IΔn (mA)
High-speed type
−
Max. operating time at 5IΔn (s)
Time-delay type
NV630-SW 3
Rated current sensitivity IΔn (mA)
100 · 200 · 500 Selectable
Max. operating time at 5IΔn (s)
0.45 · 1.0 · 2.0 Selectable 0.1 · 0.5 · 1.0
Max. inertial non-operating time at 2IΔn (s)
Earth-leakage indication system Rated short-circuit breaking capacity (kA) IEC 60947-2 (Icu/Ics) EN 60947-2
Button
AC
440V
36/18
42/42
400V
36/18
50/50
230V
50/25
85/85
Standard attached parts (Front connection)
Mounting screw: M6×72 (4pcs) Insulation barrier: (4pcs)
NV630-SW
Operating Characteristics
Earth Leakage Tripping Characteristics
4h 2h 1h
Operating characteristics NV630-CW NV630-SW
30min 20min 14min 10min
4h
5s Min. 2s
30s 10s 5s 2s 1s 0.5s
1s
Rate current sensitivity
10s
Time-delay type 2s. (MAX)
Rate nonoperating current
Operating time
Operating time
20s
2min 1min
Rate nonoperating current
Max.
30s
Rate current sensitivity
4min
1min
Rate nonoperating current
10min
2min
Time-delay type 1s. (MAX)
Time-delay type 0.45s. (MAX)
Rate current sensitivity
2h 1h 30min
6min 4min
0.5s
0.1s
0.2s
0.04s 0.02s
Inertial nonoperating time
Inertial nonoperating time
0.2s
Inertial nonoperating time
0.01s
0.1s Max. total breaking time
0.05s
25 50 100
500 1000
25 50 100
500 1000
25 50 100
500 1000
Ground-fault current (% of rated current sensitivity)
0.02s Time-delay trip 0.01s 100 125
200
300
Instantaneous trip
400 500 600 700
1000
1500 2000
3000 4000
% of rated current
Temperature Compensation Curve
Internal Accessories Operating handle Right-side AL mounting
AX
SHT or UVT
Lead wire direction
TBM
130 Current rating (%)
Left-side mounting
110 100 90 80 0
10
20
Remark: 1. Refer to page 107.
50
Accessories
Type name
F
F-4S
117
Auxiliary handle
HT
HT-4SW
V
V-4S
119
Large
TC-L
TCL-4SW3
MI
MI-4SW3
129
Skeleton
TTC
TTC-4SW3
Rear
BTC
BTC-4SW3
HL
HL-4SW
HL-S
HLS-4SW
Handle lock device
Electrical operation device
(*1)
Reference page 128 121
ZCT
127 133
Sensitivity selector
Magnetic device
Note *1 Specify the operation method and voltage. Order in combination with the breaker unit.
192
60
Test button
Line side
Mechanical interlock
Reference page Terminal cover
Operating handle
Type name
40
Internal Wiring Diagram
External Accessories Accessories
30
Ambient temperature (°C)
Load side
2 Characteristics and Dimensions
7
Rated ambient temperature
120
Leakage indication button
7 Characteristics and Dimensions
2 Earth Leakage Circuit Breakers NV630-CW · NV630-SW
Outline Drawing
Front connection
4-pole 3-pole
Breaker
Breaker 39
194 f10.5
59 f7
30 Conductor thickness t=10 max.
f12.5
39 Neutral Pole
Conductor drilling for direct connection
44
44
56
51
168
112
185
140
196
4-pole
4-pole 1mm clearance on each side of handle
107
Drilling plan
155
3-pole
44
3-pole
103 5
M6 screw or f7
118
97
f14 M12 bolt
Front-plate cutout
Boring dimensions for rear connection type barriers (3-pole)
Rear connection
Breaker
3-pole
Eddy-current heat-reducing slit
Line side 6-f35 24 24
8 f13 M12 bolt
194
225
194
8 87
24 24
83
128
4-M6 tap or f7
M6 breaker mounting screw
44
Insulated tube
87
f35
44
11
43.5
130.5
44
4-pole
8-M4 screw Add these tapped holes in 8 positions to standard boring.
87
130.5
3-pole
11
Load side
Drilling plan Note The bore dimensional drawing shows the breaker viewed from the rear.
7 2 Characteristics and Dimensions
10 113
14
225
20 20 32
25
M6 screw or f7
265
Connection allowance
225
4-pole
Stud can be rotated 90°
8
Mounting plate
92
102
Leakage-indicator button Test button
R6
257
12
Operating-time selector (time-delay type)
Trip button
44 8
43
Sensitivity selector Mounting hole
94.5
16
Insulating barrier (removable)
110
Conductor thickness t=10 max.
28
193
7
Characteristics and Dimensions
Earth Leakage Circuit Breakers
2
NV630-SEW NV630-HEW
Model
NV630-SEW
Number of poles
3
Rated operational voltage Ue (V AC) (*1)
Time-delay type
3
100-440 Multi-voltage type
Rated current In (A) High-speed type
NV630-HEW
4
300-630 adjustable −
Rated current sensitivity IΔn (mA)
−
Max. operating time at 5IΔn (s) Rated current sensitivity IΔn (mA)
(100 · 200 · 500 Selectable)
Max. operating time at 5IΔn (s)
(0.45 · 1.0 · 2.0 Selectable) (0.1 · 0.5 · 1.0)
Max. inertial non-operating time at 2IΔn (s)
Earth-leakage indication system Rated short-circuit breaking capacity (kA) IEC 60947-2 (Icu/Ics) EN 60947-2
Button
AC
440V
42/42
400V
50/50
70/70
230V
85/85
100/100
Standard attached parts (Front connection)
65/65
Mounting screw: M6×72 (4pcs) Insulation barrier: (3P: 4pcs, 4P: 6pcs)
Note *1 Rated operational voltage of time-delay type is for 200-440V.
NV630-SEW
Operating Characteristics
Earth Leakage Tripping Characteristics
10h 5h
Operating characteristics NV630-SEW NV630-HEW
2h
30s 20s 10s 5s
Pre-alarm pickup current Ip
2s
Ir x(0.7-0.75-0.8-0.85 -0.9-0.95-1.0)±10%
STD pickup current Isd Ir x(2-2.5-3-3.5-4 -5-6-7-8-10) ±15%
2min 1min 30s 10s 5s 2s 1s 0.5s
1s
0.1s
Pre-alarm operating time Tp
STD operating time Ts
TL ±20% 2 (at 200%)
0.2s 0.1s
0.01s
0.1 ± 0.03s 0.06 ± 0.02s
0.05s
25 50 100
500 1000
25 50 100
500 1000
25 50 100
500 1000
Ground-fault current (% of rated current sensitivity)
INST pickup current II In x(4-15) ±15% (Magnification to In)
0.02s
Inertial nonoperating time
0.04s 0.02s
0.3 ± 0.06s 0.2 ± 0.04s
Tp=
Inertial nonoperating time
Inertial nonoperating time
0.2s
0.5s
Time-delay type 2s. (MAX)
Rate current sensitivity
4min
Operating time
1min
Rate current sensitivity
10min LTD operating time TL 12-60-100-150s ±20% (at 200%)
Time-delay type 1s. (MAX)
Time-delay type 0.45s. (MAX)
Rate nonoperating current
2h 1h 30min
2min
Operating time
4h
Rate nonoperating current
6min 4min
Rated Current In:630A
Rate current sensitivity
Current setting Ir:300-630A (Adjustable)
LTD operating time at-125% 1000s(TL=150s set) 570s(TL=100s set) 400s(TL= 60s set) 80s(TL= 12s set)
Rate nonoperating current
1h 30min 20min 14min 10min
Max.total breaking time
0.01s 60 70
100 125
200
300
400 500 600 700
1000
1500 2000
3000 4000
Current (% of Ir) Instantaneous Tripping Current (% of In)
Internal Accessories AX
SHT or UVT
TBM
Lead wire direction
PAL
Remarks: 1. Instead of TBM, pre-alarm module (PAL) can be attached. 2. Refer to page 107.
Mechanical interlock
F
F-4S
117
V
V-4S
119
MI
3P
MI-4SW3
4P
MI-4SW4
129
Notes *1 This is for NV630-SEW. *2 This is for NV630-SEW. For rear terminal cover of NV630-HEW, use PTC-4SW3. *3 Specify the operation method and voltage. *3 Order in combination with the breaker unit.
80 70 10
20
30
40
50
60
Ambient temperature (°C)
Accessories Auxiliary handle Large Skeleton Rear
Handle lock device
Type name HT-4SW
HT TC-L TTC BTC
3P
TCL-4SW3 (*1)
4P
TCL-4SW4 (*1)
3P
TTC-4SW3
4P
TTC-4SW4
3P
BTC-4SW3 (*2)
4P
BTC-4SW4
HL
HL-4SW
HL-S
HLS-4SW
Electrical operation NVM device
194
90
Internal Wiring Diagram Reference page
Terminal cover
Operating handle
Type name
110 100
0
External Accessories Accessories
120
3P 4P
(*3)
Reference page Characteristic setting part
128
Test button
Magnetic device
121
ZCT
N
127
CT CT CT
133
In case of 4P
Load side
2 Characteristics and Dimensions
7
130
Rated ambient temperature
AL
Line side
Operating handle Right-side mounting
Continuous load current (%)
Left-side mounting
Current Reducing Curve
Magnetic device
Leakage indication button
Sensitivity selector
7 Characteristics and Dimensions
2 Earth Leakage Circuit Breakers NV630-SEW · NV630-HEW
Outline Drawing
Front connection
4-pole 3-pole
Breaker
Breaker 39
194 f10.5
59 f7
30 Conductor thickness t=10 max.
f12.5
39 Neutral Pole
Conductor drilling for direct connection
44
56
51
168
112
185
107
140
196
4-pole
4-pole 1mm clearance on each side of handle
Drilling plan
155
3-pole
44
3-pole
103 5
M6 screw or f7
44
118
97
f14 M12 bolt
Front-plate cutout
Boring dimensions for rear connection type barriers (3-pole)
Rear connection
Breaker
3-pole
Eddy-current heat-reducing slit
Line side 6-f35 24 24
8 f13 M12 bolt
194
225
194
8 87
24 24
83
128
4-M6 tap or f7
M6 breaker mounting screw
44
Insulated tube
87
43.5
3-pole
4-pole
f35
130.5
44
11 44
11
8-M4 screw Add these tapped holes in 8 positions to standard boring.
87
130.5 Load side
Drilling plan Note The bore dimensional drawing shows the breaker viewed from the rear.
7 2 Characteristics and Dimensions
10 113
14
225
20 20 32
25
M6 screw or f7
265
Connection allowance
225
4-pole
Stud can be rotated 90°
8
Mounting plate
92
102
Leakage-indicator button Test button
R6
257
12
Operating-time selector (time-delay type)
Trip button
44 8
43
Sensitivity selector
Mounting hole
94.5
16
Insulating barrier (removable)
110
Conductor thickness t=10 max.
28
195
7
Characteristics and Dimensions
Earth Leakage Circuit Breakers
2
NV800-SEW NV800-HEW
Model
NV800-SEW
NV800-HEW
Number of poles
3
Rated operational voltage Ue (V AC)
100-440 Multi-voltage type
Rated current In (A) High-speed type Time-delay type
400-800 adjustable −
Rated current sensitivity IΔn (mA)
−
Max. operating time at 5IΔn (s) Rated current sensitivity IΔn (mA)
100 · 200 · 500 Selectable
Max. operating time at 5IΔn (s)
0.45 · 1.0 · 2.0 Selectable 0.1 · 0.5 · 1.0
Max. inertial non-operating time at 2IΔn (s)
Earth-leakage indication system
Button
Rated short-circuit breaking capacity (kA) IEC 60947-2 (Icu/Ics) EN 60947-2
AC
440V
42/42
400V
50/50
70/70
230V
85/85
100/100
Standard attached parts (Front connection)
65/65
Mounting screw: M6×35 (4pcs) Insulation barrier: (2pcs)
NV800-SEW
Operating Characteristics
Earth Leakage Tripping Characteristics
10h 5h Operating characteristics NV800-SEW NV800-HEW
4h
30s 20s 10s 5s
STD pickup current Isd Ir × (2 – 2.5 – 3 – 3.5 – 4 – 5 – 6 – 7 – 8 – 10) ±15%
Pre-alarm pickup current Ip Ir × (0.7 – 0.75 – 0.8 – 0.85
2s 1s 0.5s 0.2s
– 0.9 – 0.95 – 1.0) ±10%
2min 1min 30s 10s 5s 2s 1s 0.5s 0.1s
STD operating time Ts
0.04s 0.02s
0.3 ± 0.06s 0.2 ± 0.04s
(at 200%)
0.1s
100 125
200
300
500 1000
25 50 100
500 1000
25 50 100
500 1000
Max.total breaking time
0.01s 60 70
25 50 100
Ground-fault current (% of rated current sensitivity)
INST Pickup current Ii In x(4-10) ±15% (Magnification to In)
0.02s
Inertial nonoperating time
0.01s
0.1 ± 0.03s 0.06 ± 0.02s
0.05s
Inertial nonoperating time
Inertial nonoperating time
0.2s Pre-alarm operating time Tp TL Tp= ±20% 2
Rate current sensitivity
4min
Operating time
1min
Rate nonoperating current
10min LTD operating time TL 12 – 60 – 100 – 150s ±20% (at 200%)
2min
Time-delay type 2s. (MAX)
Rate current sensitivity
1h 30min
Time-delay type 1s. (MAX)
Time-delay type 0.45s. (MAX)
2h
1000s(TL=150s set) 670s(TL=100s set) 400s(TL= 60s set) 80s(TL= 12s set)
6min 4min
Operating time
Rated Current In:800A
Rate nonoperating current
Current setting Ir:400-800A (Adjustable)
LTD operating time at-125%
Rate current sensitivity
1h 30min 20min 14min 10min
Rate nonoperating current
2h
400 500 600 700
1000
1500
2000
3000
4000
Current (% of Ir) Instantaneous Tripping Current (% of In)
Internal Accessories AX
TBM
SHT or UVT
Lead wire direction
PAL
Remarks: 1. Instead of TBM, pre-alarm module (PAL) or trip indicator (TI) can be attached. 2. Refer to page 107.
External Accessories Operating handle Mechanical interlock
Type name
Reference page
Accessories
Type name
F-8S
117
Auxiliary handle
HT
HT-4SW
V
V-8S
119
Large
TC-L
TCL-8SW3
MI
MI-8SW3
129
Terminal cover
Accessories
Skeleton
TTC
TTC-8SW3
Rear
BTC
BTC-8SW3
HL
HL-4SW
HL-S
HLS-8SW
F
Handle lock device
Electrical operation device Note *1 Specify the operation method and voltage. Order in combination with the breaker unit.
(*1)
Reference page
130 120 110
Rated ambient temperature
100 90 80 70
0
10
30
40
50
Test button Characteristic setting part Magnetic device
127 133
60
Internal Wiring Diagram
128 121
20
Ambient temperature (°C)
ZCT Line side
AL
Working current correcting ratio (%)
Operating handle Right-side mounting
Load side
2 Characteristics and Dimensions
7
Left-side mounting
Current Reducing Curve
CT CT CT
Magnetic device
196
Leakage indication button
Sensitivity selector
7 Characteristics and Dimensions
2 Earth Leakage Circuit Breakers NV800-SEW · NV800-HEW
Outline Drawing
Front connection
26
92
243 102
f8 f14
12
172 70
22
46
Test button
M6 tap or f7
97
40
1.0mm clearance on each side of the handle frame.
103
40
5
140
107
Boring dimensions for rear connection type barriers (3-pole)
Groove for reducing heat by overcurrent
M6 tap or f7 Stud can be rotated 90°
5
Breaker
6-f48 5
Connection allowance 25
10
Rear connection
Mounting plate
Front-panel cutout
Drilling plan
Conductor drilling for direct connection
155
210
(Conductor thickness t=10 max.)
24 24
32 32 32 8
f8.5
8
14
4-M6 tap or f7
32 110
15
24 24 f13 M12 bolt
140
M6 screw for mounting breaker
70
f48
140
70
11
8-M4 screw Add these tapped holes in 8 positions to standard boring.
140
Drilling plan
Note The bore dimensional drawing shows the breaker viewed from the rear.
7 2 Characteristics and Dimensions
8
243
11
8
10
113
12.5
243 45
13
295
10
243
Trip button
R6
Terminal dimension for directly connecting conductor
15
Leakage indication button
51
Breaker
Breaker
8
Sensitivity current selector
Operating time selector (Time-delay type)
15
110
87
46
Conductor thickness t=12 max.
275 87
94.5
Insulating barrier (removable)
Mounting hole
197
UL 489 Listed Circuit Breakers
NF50-SVFU NV50-SVFU
Model
Number of poles
2
Rated short-circuit breaking capacity (kA)
Rated voltage VAC
NV50-SVFU
600Y/347V
−
480V
−
AC 480Y/277V
IEC 60947-2 EN 60947-2 AC (Icu/Ics)
Phase line
− 440
690V
−
500V
−
440V
7.5/4
415V
10/5
400V
10/5
380V
10/5
230V
15/8
2
100-240 100-440
Rated current sensitivity IΔn mA
AC
0.04 (*1) Indicator window
480V
−
240V
14
120V
AC
30 50 100
75% of IΔn
Earth-leakage indication system
Standard attached parts (Front connection)
30 50
Operating time (sec) within AT 5lΔn
IEC 60947-2 EN 60947-2 (Icu/Ics)
1f2W
120-240
Pick-up current UL 1053
UL 489 CSA C22.2 No.5-02
3 3f3W
1f2W
Rated voltage IEC 60947-2 VAC EN 60947-2
14
120V
(5) (10) 15 20 30 40 50
UL 489
−
240V Rated insulation voltage Ui V
Number of poles
3 240
NV50-SVFU
Rated current In (A) Rated ambient temperature 40°C
(3) 5 10 15 20 30 40 50
Rated current In (A) Rated ambient temperature 40°C
UL 489 CSA C22.2 No.5-02
Model
NF50-SVFU
High-speed type
3
Rated short-circuit breaking capacity (kA)
7
Characteristics and Dimensions
14
440V
−
7.5/4
400V
−
10/5
230V
15/8
15/8
100V
15/8
15/8
IEC35 rail mounting claws
Note *1 0.1 for UL1053. Remark: 1. The mounting screws must be prepared by the user. (Recommended size: M430.7365 (2 pcs).)
Operating Characteristics
Earth Leakage Tripping Characteristics
(The CE and CCC characteristics are noted differently. Contact us for more information.) 4h
NV50-SVFU (UL 1053)
2h
1h
Operating Characteristics (UL 489) NF50-SVFU, NV50-SVFU
1h 30min 20min 14min 10min 6min 4min
30min 10min 4min
Max. (3A-30A)
2min
Max. (40A-50A)
1min 30s 20s 10s 5s
30s 10s 5s 2s
Min.
2s
1s
1s
0.5s
0.5s
0.2s
0.2s
0.1s
0.1s 0.05s
0.04s
0.01s 100 135
Time-delay trip 200
300 400 500 600 700 1000
0.02s
Instantaneous trip 1500 2000
0.01s
3000 4000 25 100 500 63.8 75 86.2 Ground fault current (100% of rated current sensitivity)
Current (% of Ir)
Handle of circuit breaker
3 Characteristics and Dimensions
Left pole
AL
Temperature Compensation Curve
AX
SHT or UVT
Right pole
Outgoing direction of lead wires
TBM
NF50-SVFU
NV50-SVFU
2-pole
2-pole 3-pole
3-pole
130
Rated ambient temperature
Internal Accessories
Rated current compensation rate %
7
120 110
Internal Wiring Diagram Test button
ZCT
100
Magnetic device
90 80 –10
0
10
20
30
40
50
60 Leakage indication
Ambient temperature °C
External Accessories Accessories F Operating handle V Handle lock device
198
HL HL-S
2P 3P 2P 3P
Type name F-03SVUL2 F-03SVUL V-03SVUL2 V-03SVUL HLF-03SVU HLS-03SVU
Reference page 117 119 127
Accessories Terminal cover
Large
TC-L
2P 3P
Type name TCL-03SVU2 TCL-03SVU3
Reference page 121
Sensitivity selector
Load side
0.02s
Line side
Operating time
1min
Operating time
2min
Highspeed type
2h
Rated current sensitivity
4h
Rated non-operating current
(The CE and CCC characteristics are noted differently. Contact us for more information.)
7 Characteristics and Dimensions
3 UL 489 Listed Circuit Breakers NF50-SVFU · NV50-SVFU
Outline Drawing
Front connection Mounting hole
M50.8 screw
Leakage current indicator window
Mounting hole
24
f8
3.5
Trip button Trip button
Trip button 18
18
36 54
18
36
36
36 54
2-pole
3-pole
2-pole
3-pole
(NF50-SVFU)
56 65
Test button
f4.2
Test button
Trip button 18
35
16.5
36 50 26 37
87.5 120
87.5 120
Leakage current indicator window
68 3
76 90
(NV50-SVFU)
Compatible crimp terminals Applicable wire range (*1) mm2
AWG (#)
(60°C/75°C)
f5.5 16-14
2.63-4.6
12
6
1.04-2.63
11.5 max.
Tightening torque 22lb-in (2.5N·m)
Crimp terminal type (*2) JST R2-5 2-M5 V2-5 V2-M5 R5.5-5
(Conductor thickness t=4 max.)
2.63-6.64
12-10
Conductor drilling for direct connection
6.64-10.52
8
Remarks: 1. The mounting screws are not enclosed with the breaker. 2. The wires cannot be connected directly.
10.52-16.78
6
16.78-26.66
4
V5.5-5 R8-5 R14-5 14-NK5 22-S5 22-S6
NTM R2-5 R2-5M R3.5-5S R3.5-5L R5.5-5 R5.5-5S R5.5-5N R8-5 R8-5S R14-5 R14-5S
R22-5S
JST: Japan Solderless Terminal Mfg. Co. NTM: Nichifu Co., Ltd. Notes *1 14AWG or lager to comply with UL Standards. *2 When using with a wire connection, use the crimp terminal combination shown above.
Breaker CL
Breaker
CL
18
2-pole
3-pole
CL
52
82.5
CL
37
55
2-pole
3-pole
7 3 Characteristics and Dimensions
CL
27
M40.7screw or f5
R1
CL
The drilling dimensions have a 1.0 mm clearance on each side of breaker window frame.
Drilling plan
Front panel drilling plan
199
UL 489 Listed Circuit Breakers
NF100-CVFU NV100-CVFU
Model
60 (70) 75 (80) (90) 100
2
Rated short-circuit breaking capacity (kA)
Rated voltage VAC
3
Number of poles
3 3f3W
600Y/347V
−
480V
− −
240V
14
120V
−
Rated insulation voltage Ui V 690V
− 7.5/4
440V
10/5
415V
10/5
400V
10/5
380V
10/5
230V
15/8
Standard attached parts (Front connection)
120-240
IEC 60947-2 EN 60947-2
100-440
Rated current sensitivity IΔn mA
30/50/ 100/200/500 selectable
Pick-up current UL 1053
75% of IΔn 0.04 (*1)
Operating time (sec) within AT 5lΔn
600
500V
1f2W
UL 489
Rated voltage VAC
240
AC 480Y/277V
IEC 60947-2 EN 60947-2 AC (Icu/Ics)
60 (70) 75 (80) (90) 100
Phase line
Number of poles
UL 489 CSA C22.2 No.5-02
NV100-CVFU
Rated current In (A) Rated ambient temperature 40°C
Rated current In (A) Rated ambient temperature 40°C
NF100-CVFU
Model
NF100-CVFU
High-speed type
3
Mechanical button
Earth-leakage indication system Rated short-circuit breaking capacity (kA)
7
Characteristics and Dimensions
UL 489 CSA C22.2 No.5-02
AC
IEC 60947-2 EN 60947-2 (Icu/Ics)
AC
480V
−
240V
14
120V
14
440V
10/5
400V
10/5
230V
15/8
100V
15/8
IEC35 rail mounting claws, Insulating barrier (2P: 2pcs, 3P: 4pcs) (Only for type with bar terminal) Mounting screw M430.7355 (2 screws)
Note *1 0.1 for UL1053.
Operating Characteristics
Earth Leakage Tripping Characteristics
(The CE and CCC characteristics are noted differently. Contact us for more information.)
NV100-CVFU
2h 1h
1h 30min 10min 4min
6min 4min
2min
Max.
2min
1min
Operating time
1min 30s 20s 10s 5s
Min.
2s
Highspeed type
2h
Operating Characteristics (UL 489) NF100-CVFU NV100-CVFU
30min 20min 14min 10min
Operating time
4h
(UL 1053)
30s 10s
Rated current sensitivity
4h
Rated non-operating current
(The CE and CCC characteristics are noted differently. Contact us for more information.)
5s 2s 1s
1s
0.5s
0.5s
0.2s
0.2s
0.1s
0.1s 0.05s
0.04s 0.02s
0.02s 0.01s 100 135
Time-delay trip 200
Instantaneous trip
300 400 500 600 700 1000
1500 2000
0.01s
3000 4000 25 100 500 63.8 75 86.2
Current (% of Ir)
Ground fault current (100% of rated current sensitivity)
Outgoing direction of lead wires
NV100-CVFU 3-pole
2-pole 3-pole
130 120
Test button
110
ZCT
100
Magnetic device
90 80 –10
0
10
20
30
40
50
Sensitivity selector
60
Ambient temperature °C
Leakage indication
External Accessories Accessories F Operating handle V
2P 3P 2P 3P
HL Handle lock device
200
HL-S
2P 3P
Type name F-05SVUL2 F-05SVUL V-05SVUL2 V-05SVUL HLF-05SVU HLS-05SVU2 HLS-05SVU
Reference page
Accessories
117
2P Terminal cover
119
127
Large
TC-L 3P
Type name TCL-05SVU2 TCL-05SVU2L TCL-05SVU3 TCL-05SVU3L
Reference page
121
Load side
TBM
NF100-CVFU
3 Characteristics and Dimensions
SHT or UVT
Internal Wiring Diagram
Line side
AX
Right pole
Rated ambient temperature
AL
Handle of circuit breaker Left pole
Temperature Compensation Curve Rated current compensation rate %
7
Internal Accessories
7 Characteristics and Dimensions
3 UL 489 Listed Circuit Breakers NF100-CVFU · NV100-CVFU
Outline Drawing
Front connection M8 screw 24
Mounting hole
Mounting hole
f4.5
50
84
Leakage current indicator button
112
150
150
112
Sensitivity current selector
Test button
Trip button
22
50
50
50
75
2-pole
3-pole
Trip button
8
22 25
f8.5
f8.5 45 65 68 75
16 max.
4
72 90
(Conductor thickness t=4 max.)
(NF100-CVFU)
Conductor drilling for direct connection
(NV100-CVFU)
Compatible crimp terminals Applicable wire range
Tightening torque 54lb-in (6N·m)
Crimp terminal type (*1)
AWG (#)
mm2
(60°C/75°C)
2.5-2.63
14
2.63-6.64
12-10
6.64-10.52
8
10.52-16.78
6
R14-8
16.78-26.66
4
R22-8
R22-8S
26.66-42.42
2
38-S8
R38-8S
42.42-60.57
JST
NTM
R2-8
R2-8
R5.5-8
R5.5-8
R8-8
R8-8 R14-8 R14-8S
60-2BA
1/0
CB60-8
60-S8
JST: Japan Solderless Terminal Mfg. Co. NTM: Nichifu Co., Ltd. Note *1 When using with a wire connection, use the crimp terminal combination shown above.
CL
Terminal cover
CL
Mounting hole
CL
Solderless terminal
Terminal cover
Y
Mounting hole
Size of screwdriver with bolting Please bolt with flat head screwdriver. The length of X : 6mm-7mm The length of Y q 9.5mm
X
Front connection(solderless terminal)
Flat head screwdriver
90
M40.7screw or f5
CL
CL
25
2-pole
3-pole Drilling plan
The tightening torque is different according to connected wire. Refer to instruction manual for details. Remark: Periodical retightening prevents overheating Remark: by the setting of twisted strands or the stress Remark: of heating and cooling.
2-pole
3-pole
CL
CL
50
70
Breaker
CL
7 3 Characteristics and Dimensions
75
111
CL
68
7 7 7 7 7 19
Breaker
52
75
3-pole
14AWG 12-10AWG 8AWG 6-4AWG 2AWG 1-1/0AWG
R1
50
2-pole
CL
84
CL
50
210
210
Wire size 60°C/75°C CU ONLY Number of strands
The drilling dimensions have a 1.0 mm clearance on each side of breaker window frame.
Front panel drilling plan
201
Model
NF125-SVU
15 20 30 40 50 60 (70) 75 (80) (90) 100
Rated current In (A) Rated ambient temperature 40°C
Rated short-circuit breaking capacity (kA)
Number of poles
2
125
125
3
480
600Y/347V UL 489 480V CSA C22.2 AC No.5-02 240V
−
−
18
18
30
30
50
50
50
50
100
100
−
−
−
−
Rated insulation voltage Ui V
IEC 60947-2 EN 60947-2 AC (Icu/Ics)
690
690
690
690
690V
8/4
8/4
10/5
10/5
500V
18/9
18/9
25/13
25/13
440V
30/15
30/15
50/25
50/25
415V
30/15
30/15
50/25
50/25
400V
30/15
30/15
50/25
50/25
380V
30/15
30/15
50/25
50/25
230V
50/25
50/25 100/50 100/50
NV125-SVU
Rated current In (A) Rated ambient temperature 40°C Number of poles
15 20 30 (40) 50 60 75 100 3
Phase line
3f3W 1f2W
Rated 2 3 3 3 voltage 480 600Y/347V 600Y/347V VAC
Standard attached parts (Front connection)
NF125-HVU
15 20 30 40 50 60 (70) 75 (80) (90) 100
Rated voltage VAC
120V
Model
NF125-HVU
High-speed type
NF125-SVU NF125-HVU NV125-SVU NV125-HVU
UL 489 Listed Circuit Breakers
3
NV125-HVU
15 20 30 125 (40) 50 60 125 75 100 3 3 3 3f3W 3f3W 3f3W 1f2W
1f2W
1f2W
UL 489
120-480 120-480 120-480 120-480
IEC 60947-2 EN 60947-2
100-440 100-440 100-440 100-440
Rated current sensitivity IΔn mA Pick-up current UL 1053
30/50/ 30/50/ 30/50/ 30/50/ 100/200/500 100/200/500 100/200/500 100/200/500 selectable selectable selectable selectable 75% of IΔn 75% of IΔn 75% of IΔn 75% of IΔn
Operating time (sec) within AT 5lΔn 0.04 (*1) 0.04 (*1) 0.04 (*1) 0.04 (*1)
Earth-leakage indication system Mechanical button Mechanical button Mechanical button Mechanical button Rated short-circuit breaking capacity (kA)
7
Characteristics and Dimensions
UL 489 CSA C22.2 No.5-02
AC
IEC 60947-2 EN 60947-2 AC (Icu/Ics)
480V
30
30
50
50
240V
50
50
100
100
120V
50
50
100
100
440V
30/15
30/15
50/25
50/25
400V
30/15
30/15
50/25
50/25
230V
50/25
50/25 100/50 100/50
100V
50/25
50/25 100/50 100/50
Mounting screw M430.7355 (2 screws), Insulating barrier (2P: 2pcs, 3P: 4pcs)
Note *1 0.1 for UL1053.
Operating Characteristics (The CE and CCC characteristics are noted differently. Contact us for more information.) 4h Operating Characteristics (UL 489) NF125-SVU NV125-SVU NF125-HVU NV125-HVU
1h 30min 20min 14min 10min
Operating Characteristics (UL 489) NF125-SVU NV125-SVU NF125-HVU NV125-HVU
2h 1h 30min 20min 14min 10min
15A-30A
6min 4min
10s 5s
Min.
30s 20s 10s 5s
Min.
2s
1min 30s 20s 10s 5s
1s
1s
0.5s
0.5s
0.5s
0.2s
0.2s
0.1s
0.1s
0.1s
0.05s
0.05s
0.05s
Time-delay trip 200
0.2s
0.02s
Instantaneous trip
300 400 500 600 700 1000 1500 2000
0.01s 100 135
3000 4000 5000 6000 7000 10000
300 400 500 600 700 1000 1500 2000
(The CE and CCC characteristics are noted differently. Contact us for more information.)
300 400 500 600 700 1000 1500 2000
AL
Handle of circuit breaker Left pole
Highspeed type
Right pole
NF125-SVU NF125-HVU
AX
Outgoing direction of lead wires
SHT or UVT TBM NV125-SVU NV125-HVU
Operating time
1min 30s 10s
2-pole
Rated current sensitivity
2min
Rated non-operating current
10min 4min
3-pole
3-pole
Temperature Compensation Curve Internal Wiring Diagram
5s 2s
Test button
0.2s 0.1s 0.04s 0.02s 0.01s
130 120 110 100
Magnetic device
90 80 –10
25 100 500 63.8 75 86.2 Ground fault current (100% of rated current sensitivity)
ZCT
Line side
Rated current compensation rate %
3 Characteristics and Dimensions
0.5s
Rated ambient temperature
1s
0
10
20
30
40
50
60
Ambient temperature °C Leakage indication
External Accessories Accessories Operating handle Handle lock device
202
3000 4000
Current (% of Ir)
30min
(UL 1053)
7
200
Internal Accessories
4h
1h
Instantaneous trip
Time-delay trip
0.01s 100 135
3000 4000
Current (% of Ir)
Earth Leakage Tripping Characteristics 2h
0.02s
Instantaneous trip
Time-delay trip 200
Current (% of Ir)
NV125-SVU NV125-HVU
Min.
2s
1s
0.02s 0.01s 100 135
Max.
2min
F V HL HL-S
Type name F-1SVUL V-1SVUL HLF-05SVU HLS-05SVU
Reference page 117 119 127
Accessories Terminal cover
Large
Type name TC-L
TCL-1SVU3
Reference page 121
Sensitivity selector
Load side
2s
1min
125A
6min 4min
Operating time
30s 20s
Operating time
Max.
1h
Max. (60A-100A) Max. (40A-50A)
2min
1min
Operating Characteristics (UL 489) NF125-SVU NV125-SVU NF125-HVU NV125-HVU
2h 30min 20min 14min 10min
40A-100A
6min 4min
2min
Operating time
4h
4h
2h
7 Characteristics and Dimensions
3 UL 489 Listed Circuit Breakers
NF125-SVU · NF125-HVU · NV125-SVU · NV125-HVU
Outline Drawing
Front connection Mounting hole
Insulation barrier (removable)
Insulation barrier (removable)
Mounting hole
M8 screw 50
50
24
f4.5
Leakage current indicator button
50
84
124
160
160
124
Sensitivity current selector
8
50
50
f8 .5
f8.5
Test button Trip button
45 61
22
22 Trip button
60 90
19 max.
60
68
90
(NF125-SVU, NF125-HVU)
65
4
(Conductor thickness t=4 max.)
72
Conductor drilling for direct connection
(NV125-SVU, NV125-HVU)
90
Compatible crimp terminals Applicable wire range
Tightening torque 54lb-in (6N·m)
Crimp terminal type (*1)
AWG (#)
mm2
(60°C/75°C)
2.5-2.63
14
2.63-6.64
12-10
6.64-10.52
8
10.52-16.78
6
R14-8
16.78-26.66
4
R22-8
R22-8S
26.66-42.42
2
38-S8
R38-8S
42.42-60.57
1/0
JST
NTM
R2-8
R2-8
R5.5-8
R5.5-8
R8-8
R8-8
60-2BA 60-S8
R14-8 R14-8S
CB60-8
JST: Japan Solderless Terminal Mfg. Co. NTM: Nichifu Co., Ltd. Note *1 When using with a wire connection, use the crimp terminal combination shown above.
Front connection (solderless terminal)
50
Insulation barrier (removable)
Hexagon socket set screw Mounting hole
Insulation barrier (removable)
50
Mounting hole
Solderless terminal
5.03 Wire size Number of strands 60°C/75°C CU ONLY
50
84 90
90
Breaker
7 7 7 7 7 19
a
52
R1
123
6
Breaker
86
30 M40.7 screw or f5
Drilling plan
7 3 Characteristics and Dimensions
50
90
a
The tightening torque is different according to connected wire. Refer to instruction manual for details. a:Solid copper wire is usable. Remark: Periodical retightening prevents overheating Remark: by the setting of twisted strands or the stress Remark: of heating and cooling.
68
50
160
160
6
14AWG 12-10AWG 8AWG 6AWG 4-2AWG 1AWG
The drilling dimensions have a 1.0 mm clearance on each side of breaker window frame.
Front panel drilling plan
Remark: 1. 2-pole models are 3-pole with the central pole conductor removed.
203
7
Characteristics and Dimensions
UL 489 Listed Circuit Breakers
3
NF225-CWU
Model
NF225-CWU
Rated current In (A) at ambient temperature 40˚C (IEC30˚C)
125 150 175 200 225
Rated short-circuit breaking capacities (kA)
Number of poles
3 Rated voltage (VAC)
UL 489
AC
240
240V
35
Rated insulation voltage Ui (V) IEC 60947-2 (Icu/Ics)
AC
DC
600
500V
10/5
440V
15/8
400V
18/9
230V
35/18
250V
10/5 (*1) Mounting screw: M430.7×55 (2pcs), Insulation barrier: (4pcs), Terminal cover: (1 set) (*2)
Standard attached parts
Notes *1 Use either two poles. When wired as shown at the bottom of page 32, the models can be used for up to 400 V DC. *2 The standard configuration contains a protection cover and adopts the IP20 (finger protection) structure.
NF225-CWU
Operating Characteristics 4h 2h Type
1h
NF225-CWU
30min 20min 14min 10min 6min 4min
Operating time
2min
Max.
1min 30s 20s 10s 5s Min.
2s 1s 0.5s
Max. total breaking time
0.2s 0.1s 0.05s 0.02s Time-delay trip
0.01s 1
1.35
2
3
4
Instantaneous trip 5
6 7
10
15
20
30
40
100% of Rated current
Temperature Compensation Curve
Internal Accessories
3 Characteristics and Dimensions
Right-side mounting
AL
AX
SHT or UVT
Current rating (%)
7
Left-side mounting
Lead wire direction
Rated ambient temperature
130
Operating handle
120 110 100 90 80 –10
0
10
20
30
40
Ambient temperature (°C)
External Accessories Accessories Operating handle Handle lock device
204
Type name
Reference page
F
F-2SUL
117
V
V-2SUL
119
HL
HLF-2SWU
127
Accessories Mechanical interlock Terminal cover
Large
Type name Ml TC-L
Reference page
MI-05SWU3
129
TCL-2SWU3 TCL-2SWU3L
121
50
60
7 Characteristics and Dimensions
3 UL 489 Listed Circuit Breakers NF225-CWU
Outline Drawing
Front connection
Compatible crimp terminals
Insulating barrier
24
C L
Applicable wire range
M8 bolt (Hex-soket)
mm2
50
f8.5 10
f4.5
f8.5
102
144
C L
165
100
Mounting hole
22 max. 100
Trip button
Conductor thickness t=7 max.
22
16.78-26.66
4
26.66-42.42
2
42.42-60.57
1/0
JST
NTM
R22-8 22-S8
R22-8 R22-8S CB22-8S
R38-8 38-S8 R60-8 60-2BA CB60-S8
R38-8 R38-8S R60-8 CB60-8 CB60-8S R70-8
60.57-76.28
2/0
70-8
76.28-96.3
3/0
80-3BA CB80-S8
96.3-117.2
4/0
100-3BA CB100-S8
JST: Japan Solderless Terminal Mfg. Co. NTM: Nichifu Co., Ltd. Notes *1 When using with a wire connection, use the crimp terminal combination shown above.
Conductor drilling for direct connection
45 61
70
AWG (#)
(60°C/75°C)
Tightening torque 90lb-in (10N.m)
Crimp terminal type (*1)
68
105 4
72 92
Drilling plan
M40.7 screw or f5
1
C L
100
Front cover cutout 1mm clearance on each side of handle
7 3 Characteristics and Dimensions
35
Breaker
52
126
C L
C L
Breaker
R
C L
205
NF250-SVU NF250-HVU NV250-SVU NV250-HVU
UL 489 Listed Circuit Breakers
3
Model
NF250-SVU
Rated current In (A) Rated ambient temperature 40°C
125 150 175 200 225
Rated short-circuit breaking capacity (kA)
Number of poles
125 150 175 200 225
250
Rated voltage 3 3 600Y/347V 600Y/347V VAC
3
3 480
600Y/347V UL 489 480V CSA C22.2 AC No.5-02 240V
−
−
18
18
35
35
50
50
65
65
100
100
−
−
−
−
IEC 60947-2 EN 60947-2 AC (Icu/Ics)
690
690
690
690
690V
8/4
8/4
10/5
10/5
500V
25/13
25/13
36/18
36/18
440V
36/18
36/18
50/25
50/25
415V
36/18
36/18
50/25
50/25
400V
36/18
36/18
50/25
50/25
380V
36/18
36/18
50/25
50/25
230V
65/33
65/33 100/50 100/50
Standard attached parts (Front connection)
NF250-HVU
30/50/ 30/50/ 30/50/ 30/50/ 100/200/500 100/200/500 100/200/500 100/200/500 selectable selectable selectable selectable 75% of IΔn 75% of IΔn 75% of IΔn 75% of IΔn
Rated current sensitivity IΔn mA Pick-up current UL 1053
Operating time s within AT 5lΔn 0.04 (*1) 0.04 (*1) 0.04 (*1) 0.04 (*1)
UL 489 CSA C22.2 No.5-02
AC
IEC 60947-2 EN 60947-2 AC (Icu/Ics)
480V
35
35
50
50
240V
65
65
100
100
120V
65
65
100
100
440V
36/18
36/18
50/25
50/25
400V
36/18
36/18
50/25
50/25
230V
65/33
65/33 100/50 100/50
100V
65/33
65/33 100/50 100/50
Earth Leakage Tripping Characteristics
(The CE and CCC characteristics are noted differently. Contact us for more information.)
NV250-SVU NV250-HVU
1h 30min
10s 5s
Min.
2min
30s 20s 10s 5s
Min.
2s
1s
1s
0.5s
0.5s Max. total breaking time
4min
Operating time
30s 20s
0.1s
10min
Max.
1min
0.02s
0.02s
30s 10s 5s
1s 0.5s 0.2s 0.1s
Max. total breaking time
0.1s 0.05s
1min
2s
0.2s
0.05s
Highspeed type
2h
(UL 1053)
250A
2min
Operating time
1min
4h
Rated current sensitivity
1h 30min 20min 14min 10min
Max.
0.2s
0.04s 0.02s 0.01s
0.01s 100 135
300 400 500 600 700 1000 1500 2000 3000 4000
Time-delay trip 200
Current (% of Ir)
7 Internal Accessories AL
Temperature Compensation Curve Internal Wiring Diagram AX
Right pole
NF250-SVU NF250-HVU
SHT or UVT
Outgoing direction of lead wires
Rated current compensation rate %
Handle of circuit breaker
25 100 500 63.8 75 86.2 Ground fault current (100% of rated current sensitivity)
300 400 500 600 700 1000 1500 2000 3000 4000
Current (% of Ir)
Left pole
Instantaneous trip
TBM
NV250-SVU NV250-HVU
130 120
Test button
110 100
Magnetic device
90 80 –10
0
10
20
30
40
50
60 Leakage indication
Ambient temperature °C
External Accessories Accessories Operating handle Handle lock device
F V HL HL-S
Type name F-2SVUL V-2SVUL HLF-05SVU HLS-2SVU
Reference page 117 119 127
Accessories Terminal cover
Large
TC-L
ZCT
Type name TCL-2SVU3 TCL-2SVU3L
Reference page 121
Sensitivity selector
Load side
200
Instantaneous trip
Line side
Time-delay trip
Rated ambient temperature
0.01s 100 135
3 Characteristics and Dimensions
100-440 100-440 100-440 100-440
6min 4min
2min
Operating time
Operating Characteristics (UL 489) NF250-SVU NV250-SVU NF250-HVU NV250-HVU
2h
6min 4min
206
1ø2W
Mounting screw M430.7355 (2 screws), Insulating barrier (4pcs)
4h
125-225A
2s
1ø2W
IEC 60947-2 EN 60947-2
Rated non-operating current
1h 30min 20min 14min 10min
1ø2W
120-480 120-480 120-480 120-480
Note *1 0.1 for UL1053.
Operating Characteristics (UL 489) NF250-SVU NV250-SVU NF250-HVU NV250-HVU
2h
1ø2W
UL 489
Earth-leakage indication system Mechanical button Mechanical button Mechanical button Mechanical button
Operating Characteristics (The CE and CCC characteristics are noted differently. Contact us for more information.) 4h
NV250-HVU
125 150 125 150 175 200 250 175 200 250 225 225 3 3 3 3 3ø3W 3ø3W 3ø3W 3ø3W
Phase line
480
Rated insulation voltage Ui V
NV250-SVU
Rated current In (A) Rated ambient temperature 40°C Number of poles
250
Rated voltage VAC
120V
Model
NF250-HVU
High-speed type
7
Rated short-circuit breaking capacity (kA)
Characteristics and Dimensions
7 Characteristics and Dimensions
3 UL 489 Listed Circuit Breakers
NF250-SVU · NF250-HVU · NV250-SVU · NV250-HVU
Outline Drawing
Front connection
Compatible crimp terminals
Tightening torque 90lb-in (10N.m)
Applicable wire range AWG (#)
mm2 Insulation barrier (removable)
24
Hexagon socket M8 bolt
Insulation barrier (removable)
100
100
Mounting hole
Mounting hole
4
26.66-42.42
2
42.42-60.57
1/0
f4.5 f8.5
100
R22-8 R22-8S CB22-8S
R38-8 38-S8 R60-8 60-2BA CB60-S8
R38-8 R38-8S R60-8 CB60-8 CB60-8S R70-8
2/0
70-8
76.28-96.3
3/0
80-3BA CB80-S8
96.3-117.2
4/0
100-3BA CB100-S8
117.2-152.05 250/300MCM CB150-S8 (*1) JST: Japan Solderless Terminal Mfg. Co. NTM: Nichifu Co., Ltd. Notes *1 TCL-2SVU3L can be mounted when using CB150-S8. *2 When using with a wire connection, use the crimp terminal combination shown above.
Test button
100
NTM
R22-8 22-S8
60.57-76.28
50
102
144
185
185
144 Trip button
JST
(60°C/75°C)
16.78-26.66
Sensitivity current selector Leakage current indicator button
Crimp terminal type (*2)
45 61
70
70
9
1 (Conductor thickness t=7 max.)
Max. 25
92
(NF250-SVU, NF250-HVU)
10
or
72
C
4
.5
f8
1
68
105
105
.5
f8
65
22
C
Trip button
22
Max. 25
Conductor drilling for direct connection
(NV250-SVU, NV250-HVU)
Front connection (solderless terminal) Mounting hole
Terminal cover
Mounting hole
Solderless terminal Hexagon socket set screw
Terminal cover
Wire size 60°C/75°C CU ONLY Number of strands 4-2AWG 7 1-1/0AWG 19 3/0-4/0AWG 19 250-350MCM 37
50
102
265
265
6.1
The tightening torque is different according to connected wire. Refer to instruction manual for details.
105
Remark: Periodical retightening prevents overheating Remark: by the setting of twisted strands or the stress Remark: of heating and cooling.
68
105
92
Breaker Breaker
3 Characteristics and Dimensions
CL
7
52
126
CL
R1
CL
CL
100
35 M40.7screw or f5
Drilling plan
The drilling dimensions have a 1.0 mm clearance on each side of breaker window frame.
Front panel drilling plan
207
7
Characteristics and Dimensions
UL 489 Listed Circuit Breakers
3
NF400-SWU NF400-HWU
Model
NF400-SWU
NF400-HWU
250 300 350 400
250 300 350 400
Rated current In (A) at ambient temperature 40˚C
Rated short-circuit breaking capacities (kA)
Number of poles
3
3
600Y/347
600Y/347
600Y/347V
20
25
480V
35
65
240V
65
100
Rated voltage (VAC)
UL 489 CSA C22 2 No.5-02
AC
Rated insulation voltage Ui (V) 690V IEC 60947-2 EN 60947-2 (Icu/Ics)
AC
690
690
10/10(5/5) (*1)
15/10
500V
30/30(25/25) (*1)
42/42
440V
42/42(36/36) (*1)
65/65
400V
45/45(36/36) (*1)
70/70
230V
85/85(65/65) (*1)
100/100
Mounting screw: M6360 (4screws) Insulating plate (1pce) Insulating barrier (4pcs) (Only for type with bar terminals)
Mounting screw: M6360 (4screws) Insulating plate (1pce) Insulating barrier (4pcs) (Only for type with bar terminals)
Standard attached parts
Note *1 In case of solderless terminal, interrupting capacity reduces: (/). *2 0.1 for UL1053.
NF400-SWU
Operating Characteristics 4h
4h
2h
2h Operating Characteristics (UL 489) NF400-SWU NF400-HWU
1h 30min 20min 14min 10min 6min 4min
1h
6min 4min
2min
2min
Max.
1min
Operating time
1min 30s 20s 10s 5s Min.
2s 1s
Max.
30s 20s 10s 5s Min. 2s 1s
0.5s
0.5s Max.total interrupting time
0.2s
0.2s
0.1s
0.1s
0.05s
0.05s
0.02s
Time-delay trip
0.01s 100 135
200
0.02s
Instantaneous trip
300 400 500 600 700 1000
Max.total interrupting time
0.01s 100 130
1500 2000 3000 4000
Time-delay trip 200
% of rated current
Operating handle Right-side mounting
Temperature Compensation Curve
AL
AX
SHT or UVT
MG
EAL
TBL
TBM
ATU
PAL
Lead-wire direction
7
Current rating (%)
NF400-SWU, NF400-HWU
(*1)
130 120 110 100 90 80 −10
(*1)
3 Characteristics and Dimensions
1500 2000 3000 4000
% of rated current
Internal Accessories Left-side mounting
Instantaneous trip
300 400 500 600 700 1000
Rated ambient temperature
Operating time
Operating Characteristics (IEC 60947-2) (EN 60947-2) NF400-SWU NF400-HWU
30min 20min 14min 10min
0
10
20
30
40
Ambient temperature (°C)
(*1)
(*1)
Note *1 Right-side mounting is standard of SHT and UVT. Specify separataly for left-side mounting.
External Accessories Accessories Operating handle Handle lock device
208
F V HL
Type name F-4SUL V-4SUL HL-4SWU
Reference page 117 119 127
Accessories Terminal cover
Large
Type name TC-L
TCL-4SWU
Reference page 121
50
60
7 Characteristics and Dimensions
3 UL 489 Listed Circuit Breakers NF400-SWU · NF400-HWU
Outline Drawing
Front connection (Solderless terminal)
Hexagon socket set screw Solderless terminal
Tightening torque 275lb-in. (31.1N·m) 8
Mounting hole 102
47
Trip button
f7
f12.5
257
225
UL Ampere ratings
Wire size
250A, 300A
250-350kcmil CU
250A
350kcmil AL
350A, 400A
(2) 3/0AWG CU
Number of strands 37 19
IEC 87
97
140
103 107
5
(max. 141) (NF400-SWU)
Ampere ratings
Wire size (IEC 60228) Class 2
Class 5
250A, 300A
70-185mm2
95-185mm2
350A, 400A
150-240mm2
150-185mm2
3. Use a wire size that can carry the rated current. 4. When using IEC Class 5 (multi-core wire), pay attention to strand breakage and pinching, etc., while tightening. 5. The NF400-HWU does not have a solderless terminal.
155
Remarks: 1. Do not remove solderless terminal in any case. 2. When using the solderless terminals, conduct periodic inspections and tightening as the wires may wear down over use.
Front connection (Busbar terminal) Insulating barrier (removable)
46 Conductor thickness t=10 max.
10
44
110
13
26
47
Trip button
f7
f12.5
257
102
Mounting hole
10
f13 M12 bolt
46 97
112
103
140 5
(max.141) (NF400-SWU) (NF400-HWU)
107 155
Remark: Do not remove busbar terminal in any case.
Breaker
3 Characteristics and Dimensions
92
194
7
CAUTION When mounted in steel or cast box cover must be insulated as shown. 58mm air gap to cover or 0.8mm fibre insulating plate extending 12.7mm out from each side of breaker.
R6
Breaker
97
58
30
44
Drilling plan
f7 holes or M6 taps
118
Front-panel cutout
1mm clearance on each side of handle.
Insulating plate (Line)
209
7
Characteristics and Dimensions
UL 489 Listed Circuit Breakers
3
NF630-SWU NF630-HWU
Model
NF630-SWU
NF630-HWU
Rated current In (A) at ambient temperature 40°C
500 600 630
500 600 630
Number of poles
3
3
600Y/347
600Y/347
600Y/347V
20
25
480V
35
65
240V
85
100
Rated short-circuit breaking capacities (kA)
Rated voltage (VAC) UL 489 AC
CSA C22.2 No.5-02
Rated insulation voltage Ui (V) IEC 60947-2 EN 60947-2 (Icu/Ics)
AC
690
690
690V
10/10
15/10
500V
30/30
42/42
440V
42/42
65/65
400V
45/45
70/70
230V
85/85
100/100
Mounting screw: M6335 (4pcs) Insulating plate (1pce) Insulating barrier (500A,600A: 2pcs, 630A: 4pcs) (Only for type with bar terminals)
Mounting screw: M6335 (4pcs) Insulating plate (1pce) Insulating barrier (500A,600A: 2pcs, 630A: 4pcs) (Only for type with bar terminals)
Standard attached parts
NF630-SWU
Operating Characteristics 4h
4h
2h 1h 30min 20min 14min 10min 6min 4min
Inst. trip adjustment range (4 steps)
2min
Control Inst. trip setting current (%)
Max.
1min
10s
400±80 600±120 800±160 1000±200
Lo 2 3 Hi
30s 20s Min.
5s
Adjustable range of inst. pick up current
2s 1s
1min
Lo 2 3 Hi
30s 20s
5s Adjustable range of inst. pick up current
Min.
0.5s 0.2s Max. total interrupting time
0.1s 0.05s
Max. total interrupting time
0.1s 0.05s
Time-delay trip 135
200
0.02s
Instantaneous trip
300 400 500 600 700 1000
0.01s
1500 2000 3000 4000
Time-delay trip
100 130
200
Instantaneous trip
300 400 500 600 700 1000
% of rated current
Temperature Compensation Curve AX
SHT or UVT
MG
EAL
TBL
TBM
ATU
3 Characteristics and Dimensions
7
PAL
(*1)
(*1)
Lead-wire direction
130
Rated ambient temperature
Right-side mounting
AL
Current rating (%)
Left-side mounting
1500 2000 3000 4000
% of rated current
Internal Accessories Operating handle
120 110 100
(*1)
90 80 −10
(*1)
0
10
20
External Accessories Accessories
Handle lock device
210
F V HL
Type name F-6SUL V-6SUL HL-4SWU
Reference page 117 119 127
Accessories Terminal cover
Large
Type name TC-L
TCL-6SWU
30
40
Ambient temperature (°C)
Note *1 Right-side mounting is standard of SHT and UVT. Specify separataly for left-side mounting.
Operating handle
400±80 600±120 800±160 1000±200
10s
1s
0.2s
0.01s 100
Inst. trip adjustment range (4 steps) Control Inst. trip setting current (%)
Max.
2min
2s
0.5s
0.02s
Operating Characteristics (IEC 60947-2) NF630-SWU NF630-HWU
1h 30min 20min 14min 10min 6min 4min
Operating time
Operating time
2h
Operating Characteristics (UL 489) NF630-SWU NF630-HWU
Reference page 121
50
60
7 Characteristics and Dimensions
3 UL 489 Listed Circuit Breakers NF630-SWU · NF630-HWU
Outline Drawing
Front connection (Solderless terminal) Solderless terminal
Hexagon socket set screw Tightening torque 275lb-in. (31.1N·m)
102
275
243
Mounting hole 8
15
UL Ampere ratings
Wire size
Number of strands
500A, 600A
(2) 250-350kcmil CU ONLY
37
f8
f14
Trip button
IEC 140
97
Ampere ratings
210
103
500A, 600A
5 Remarks: 1. Do not remove solderless terminal in any case. 2. When using the solderless terminals, conduct periodic inspections and tightening as the wires may wear down over use.
Front connection (Busbar terminal)
Class 5
(2) 95-185mm2
(2) 120-185mm2
3. Use a wire size that can carry the rated current. 4. When using IEC Class 5 (multi-core wire), pay attention to strand breakage and pinching, etc., while tightening. 5. The 630A and NF630-HWU does not have a solderless terminal.
107 155
46
Conductor thickness t=12 max.
10
630A:150 500A, 600A:110
Insulating barrier (removable)
Wire size (IEC 60228) Class 2
102
275
Mounting hole
15
40
87
32
14
10
15
630A:150
8
f8
f14
Trip button
46
140
97
f14 M12 bolt
210
103 5
107 155
Remark: Do not remove busbar terminal in any case.
Breaker
Breaker
CAUTION
92
97
3 Characteristics and Dimensions
R6 243
7
When mounted in steel or cast box cover must be insulated as shown. 58mm air gap to cover or 0.8mm fibre insulating plate extending 12.7mm out from each side of breaker.
58
30
70
Drialling plan
f7 holes or M6 taps
172
1mm clearance on each side of handle.
Insulating plate (Line)
Front-panel cutout
211
7
Characteristics and Dimensions
4
Measuring Display Unit Breakers
NF250-SEV with MDU NF250-HEV with MDU
Model Rated current In (A) Rated ambient temperature 40°C Current setting Ir (A) Number of poles Rated insulation voltage Ui (V)
NF250-SEV with MDU
NF250-HEV with MDU
250
250
125-250
125-250
3
4 3 4 690 690 8/8 10/8 18/18 30/23 36/36 50/50 36/36 70/70 36/36 75/75 36/36 75/75 85/85 100/100 − − Mounting screw M4 0.7 55 (3P: 2psc, 4P: 4pcs) Insulation barrier (3P: 4pcs, 4P: 6pcs) MDU, Connection cable (for breaker mounting) MDU, Panel mounting bracket, Panel mounting screw, Connection cable (for panel mounting)
Rated short-circuit breaking capacity (kA)
690V 500V 440V AC 415V IEC 60947-2 (Icu/Ics) 400V 380V 230V DC 250V Standard attached parts (Front connection) Breaker mounting MDU accessories Panel mounting
NF250-SEV with MDU NF250-SEV with MDU (Breaker mounting) (Panel mounting)
Operating Characteristics 10h
10h Operating characteristics NF250-SEV with MDU NF250-HEV with MDU
5h 2h 1h
2h
Note) Current setting Ir Rated current In 125-250 250A (Adjustable)
LTD operating time 6 at 125%(I t ON) 670s (TL = 100s set) 540s (TL = 80s set) 400s (TL = 60s set) 80s (TL = 12s set)
30min 20min 14min 10min 6min 4min
1h
LTD operating time 6 at 125%(I t ON) 670s (TL = 100s set) 540s (TL = 80s set) 400s (TL = 60s set) 80s (TL = 12s set)
30min 20min 14min 10min 6min 4min
LTD operating time TL 12–60–80–100s ±20% (at 200%)
6
I t ON
30s 20s
Operating time
1min
6
I t OFF
10s
STD pickup current Is Ir × (2–2.5–3–3.5–4 –5–6–7–8–10) ±15%
5s 2s
1min
6
I t OFF
10s
STD pickup current Is Ir × (2–2.5–3–3.5–4 –5–6–7–8–10) ±15%
5s
1s 0.5s
STD operating time Ts 0.3±0.06s 0.2±0.04s
0.5s 0.2s 0.1s
0.1s
0.1±0.03s
2
I t ON
STD operating time Ts 0.3±0.06s 0.2±0.04s
0.2s
2
2
I t OFF
0.02s
200
Max. total breaking time
0.01s
600 1000 1500 3000 500 700 2000 4000 Current (% of Ir) Instantaneous tripping current (% of In, or % of Ir)
300 400
AL
AX
60 70 100 125
INST pickup current Ii In × 2-14 ±15%, Ir × 14 ±15%
200
Max. total breaking time
300 400 600 1000 1500 3000 500 700 2000 4000
Current (% of Ir) Instantaneous tripping current (% of In, or % of Ir)
Current Reducing Curve SHT or UVT
Right-side mounting
PAL
Lead-wire direction AL for MDU transmission
Derating of Load current (%)
4 Characteristics and Dimensions
Operating handle
I t OFF
0.02s
AX for MDU transmission
(*1)
Rated ambient temperature
60 70 100 125
INST pickup current Ii In × 2-14 ±15%, Ir × 14 ±15%
Internal Accessories
7
0.1±0.03s
2
I t ON
0.05s
0.05s
Left-side mounting
LTD operating time TL 12–60–80–100s ±20% (at 200%)
6
I t ON
30s 20s
2s
1s
0.01s
Note) Current setting Ir Rated current In 125-250 250A (Adjustable)
2min
2min Operating time
Operating characteristics NV250-SEV with MDU NV250-HEV with MDU
5h
130 120 110 100 90 80 70 –10
0
10
20
30
40
50
60
The rated current does not have thermal characteristics. Reduce the current as shown in the curve on the left chart if the ambient temperature exceeds 40 °C.
Ambient temperature (°C) Note *1 SLT-equipped is standard. Control voltage (100-240VAC/100-240VDC) is necessary.
External Accessories Accessories F Operating handle (*1) V LC
Type name Reference page 117 F-2SV 119 V-2SV LC-05SV HLF-05SV 127 Handle lock device HL (*2) HLN-05SV HL-S (*1) HLS-2SV Notes *1 Available only for the MDU panel mounting type. *2 HLF types are used for OFF lock and HLN types for ON lock. *3 When selecting the MDU breaker mounting, only the MI panel mounting can be manufactured. *4 Specify the working voltage. *5 In the case of the MDU breaker mounting type, specify the model name with MP at the end. 212
Accessories Mechanical interlock
MI (*3)
Small
TC-S
Terminal Large cover
TC-L
Skeleton TTC Rear BTC Electrical operation device (*1)
3P 4P 3P 3P 4P 3P 3P
Type name MI-05SV3 MI-2SV4 TCS-2SV3 (*5) TCL-2SV3 (*5) TCL-2SV3L (*5) TCL-2SV4 TTC-2SV3 (*5) BTC-2SV3 (*5) (*4)
Reference page 129
121
133
7 Characteristics and Dimensions
4 Measuring Display Unit Breakers
NF250-SEV with MDU · NF250-HEV with MDU
Outline Drawing
M8 bolt (Hex-soket)
Trip button
Neutral pole
92
MDU unit
3-pole
MDU specification No transmission, pulse output
4-pole
MDU breaker mounting
CC-Link
35 105 140
Neutral pole
.5
f8
9
45 61 4
126
or
f4.5
144 165 22 70 105
f8.5
f8.5
45 61 68 77
100
35 105 140
25 max.
f4.5
133 144 165 102 86.5 100 22
Breaker
1 C
Trip button
70 105
24
100
Mtg hole
10
Insulation barrier (removable)
f8
3
102 50
25
(65)
24
100
Mtg hole
C 1
M8 bolt (Hex-soket)
A
38.5
Insulation barrier (removable)
.5
Front connection
68
M4 × 0.7 taps or f5
(Bus t max.=7)
72
A 25 32
3-pole
4-pole
35
35
25 max.
3-pole
4-pole
92
Bus drilling for direct connection
MDU panel mounting
Drilling plan
Rear mounting
77
70 105
106
MDU unit
Insulation tube
32.5
100 60 77.5
B B
MDU specification B No transmission, pulse output 16
f9 M8 bolt
CC-Link
MDU breaker mounting
126 144
1 R
52
M4 × 0.7 taps or f5
70
105
4-pole
3-pole
Front-plate cut out MDU panel mounting
Drilling plan
MDU panel mounting
MDU terminal for panel mounting
90 14.5
35 35
f24
35
1mm clearance on each side of handle
f9 M8 bolt
23
This figure is without terminal cover. Please bind wires. Control power MB
106
32.5 100
Insulation tube
70 105
71
Front-plate cut out
MDU unit terminal for breaker mounting
Control power FG
15 68
M4 × 0.7 breaker mtg screw
6
15
72
Breaker
Breaker
3-pole
20
M4 × 0.7 breaker mtg screw
15
71
4-pole 3-pole
4-pole
Connection allowance 22
20
144
R1
8
Breaker
6
15 68
Stud can be rotated 90° Insulation tube
8
4-pole 3-pole
Connection allowance 22
Mtg plate t max.=3.2
4-pole 3-pole
144
Stud can be rotated 90° Insulation tube
39.5 88.5
Mtg plate t max.=3.2
70
Panel note: Panel t 1.0mm - 3.2mm
Operation and indication side 90
This figure is without terminal cover. Please bind wires.
Terminal block Panel holder plate
MDU connector
MA, MB,FG M3 screw
90
Control power MA
1 2 3 4 5 6 MAMB
70 90
Control power
1 2 3 4 5 6
R2
4
5
6
−
−
−
−
−
Pulse output
−
−
−
CC-Link
− SLD −
−
Cb Ca
82.5
DG DB DA
MDU specification 1
2
3
4
5
6
−
−
−
−
FG
−
−
−
No transmission Pulse output
Ca Cb
FG
−
CC-Link
DA DB DG SLD FG
−
Front-panel cut out
7 4 Characteristics and Dimensions
3
−
72
2
No transmission
72
57.5
MDU specification 1
50
Removable connector
213
7
Characteristics and Dimensions
Measuring Display Unit Breakers
4
NF400-SEP with MDU NF400-HEP with MDU
Model
NF400-SEP with MDU
Rated current In (A) Rated ambient temperature 40°C Number of poles Rated operational voltage Ue V 690V 500V 440V 415V IEC 60947-2 AC (Icu/Ics) 400V 380V 230V 200V Standard attached parts Breaker (Front connection)
200 225 250 300 350 400 Adjustable 4 3 4 690 690 10/10 10/10 30/30 50/50 42/42 65/65 45/45 70/70 45/45 70/70 45/45 70/70 85/85 100/100 85/85 100/100 Mounting screw M6 60 (4pcs) Insulation barrier (3P: 4pcs, 4P: 6pcs) MDU, Connection cable (for breaker mounting) MDU, Panel mounting bracket, Panel mounting screw, Connection cable (for panel mounting)
Rated short-circuit breaking capacity (kA)
3
Breaker mounting Panel mounting
MDU accessories
NF400-HEP with MDU
NF400-SEP with MDU (Breaker mounting)
Operating Characteristics 10h
2h 1h
LTD operating time at 130% 790s (TL = 150s set) 530s (TL = 100s set) 315s (TL = 60s set) 65s (TL = 12s set)
30min 20min 14min 10min 6min 4min 1min
(*1)
(*1)
SHT or UVT MG
(*1)
(*1)
LTD operating time TL 12-60-100-150s ±20% (at 200%)
EAL
TBL
TBM
PAL
ATU
TI
EPAL
Lead-wire direction
Note *1 Right side mounting is standard of SHT and UVT. Specify separately for left side mounting.
5s
1s
STD pickup current Is Ir × (2-2.5-3-3.5-4 -5-6-7-8-10) ±15%
Pre-alarm operating time Tp TL ±20% 2 (at 200%)
0.5s
STD operating time Ts 0.3±0.06s 0.2±0.04s
Tp=
0.2s 0.1s 0.05s
0.1±0.03s 0.06±0.02s
INST pickup current II x4-x16 ±15% (Magnification to In)
0.02s
60 70 100 130
200
600 1000 1500 3000 500 700 2000 4000 Current (% of Ir) Instantaneous tripping current (% of In)
Accessories
Handle lock device Mechanical interlock
F V HL HL-S MI (*2)
Max. total breaking time
300 400
7 External Accessories Operating handle
Current Reducing Curve
3P 4P
Type name Breaker mounting Panel mounting − F-4S − V-4S HL-4SW HL-4SW HLS-4SW − MI-4SW3 MI-4SW3 MI-4SW4 MI-4SW4 HT-4SW HT-4SW
Rated ambient temperature
Pre-alarm pickup current Ip Ir x(0.70-0.75 -0.8-0.85-0.9 ±10% -0.95-1.0)
Derating of Load current (%)
10s
2s
130 120 110 100 90 80 70 –10
0
10
20
30
40
50
60
The rated current does not have thermal characteristics. Reduce the current as shown in the curve on the left chart if the ambient temperature exceeds 40°C.
Ambient temperature (°C)
Reference page 117 119 127 129
HT 128 Auxiliary handle Notes *1 For NF400SEP with MDU. *2 When selecting the MDU breaker mounting, only the MI panel mounting can be manufactured. *3 Specify the operation method and voltage. Order in combination with the breaker unit. *4 This is for NF400-SEP with MDU. For rear terminal cover of NF400-HEP with MDU, use PTC-4SW3.
214
AX
AX for MDU transmission
Note) Current setting Rated Current Ir: 200-400A In: 400A (Adjustable)
30s 20s
0.01s
AL
AL for MDU transmission
Accessories
Terminal cover
Operating time
2min
Operating handle Right-side mounting
Left-side mounting
Operating characteristics NF400-SEP with MDU NF400-HEP with MDU (Magnification to In)
5h
4 Characteristics and Dimensions
Internal Accessories
Large
TC-L
Skeleton
TTC
3P 4P 3P 4P 3P
Rear
BTC 4P
Electrical operation device
NFM
3P 4P
Type name Breaker mounting Panel mounting − TCL-4SW3 (*1) − TCL-4SW4 (*1) TTC-4SW3-MDU TTC-4SW3 TTC-4SW4-MDU TTC-4SW4 BTC-4SW3 (*1) BTC-4SW3 (*4) Only line side BTC-4SW4 BTC-4SW4 Only line side −
(*3)
Reference page
121
133
7 Characteristics and Dimensions
4 Measuring Display Unit Breakers
NF400-SEP with MDU · NF400-HEP with MDU
Outline Drawing
Insulating barrier (removable)
112
Mounting hole
51
56
22
44
Conductor t max.=8
8
Breaker 39
43
110
94.5 28 16
Front connection
Trip button
97
194
f12.5
f7
47
39
75
51
257
102
103
Current indication LED OVER PAL MDU 70%
M12 bolt 58
MDU terminal cover
12
PE f14
44
30
25
36
5
131
185
140
196
3-pole
4-pole
f10.5
107
168
90
M6 taps or f7
44
Neutral pole
155
4-pole
3-pole
Conductor t max.=8
Conductor drilling for direct connection
Rear connection
44
Drilling plan
1mm clearance on each side of handle. (Load side of breaker mounting has given the space to pass wires to the terminal.)
Front-plate cutout 4-pole
Stud can be rotated 90°
Breaker
MDU
3-pole
Breaker
Eddy-current heat-reducing slit
225
14
265
3-pole
R6
M6 breaker mounting screw
10
44
8 f13
M12 bolt
f35
44
87
Insulating tube
87
92 138
63
83
128
26
20
113
R6
46
25
225
20
3-pole
194
M6 taps or f7
Connection allowance
4-pole
4-pole
8
Mounting plate
130.5
3-pole
4-pole
Drilling plan
Note The drilling plan is different if insulating barriers are installed.
33
43.5
130.5
37
37
(59)
118
118
<Panel mounting> CC-Link ; only MDU panel mounting
NF400-SEP, NF400-HEP with MDU (No transmission, pulse output) MDU is connected with circuit breaker via MDU connection cable.
MDU panel mounting
Panel thickness 1-3.2mm 72
<Panel mounting> 4 3 2 1
40
L2 L1
86.5
MDU display part
Terminal PE screw (M4)
Control power 1 A
28.5
Panel holder plate
For the set installation
2
Pulse output
MDU connector
113 114
B
Terminal block
90
85
96
72
4
Front panel cutout
M3.5 screw
L1L2 1
2 3 4 5 6
Control power
58.5 30
3
No transmission
M3 nut
Terminal block
8.5
Figure of the breaker mounting is removed the terminal cover.
MDU terminal
Panel 90
12
70
M4 screw
40
R2
75
75
40
Operation/display side
Upper side
Space greater than the value shown in the figure below must be secured, and must be separate 10cm or more from the distribution line.
Terminal cover
M4 screw
Type NF400-SEP NF400-HEP
54
M3 nut
B A 244 205 374 205
In case of front connection, keep space between MDU and conductor or insulation barrier.
1
2
No transmission
FG
Pulse output
FG
3
4
5
6
7
113 114
NF400-SEP, NF400-HEP with MDU (CC-Link)
75
28.5
12
70
Panel holder plate
43.1
55
Terminal block
58.5 23
Terminal cover M3 screw
MDU display part
8 7 6 5 4 3 2 1
76
L2 L1 1 2 SLD DG 5 6 SLD DG
For the set installation
Front panel cutout
67.5
104.5
M3 screw
72
85 90 96
48
M3 nut
R2
86.5
MDU connector
Terminal PE screw(M4)
75
40
38
90
M3 screw Upper side
Panel thickness 1-3.2mm
Panel
MDU terminal <Panel mounting>
A
Operation/display side
Space greater than the value shown in the figure below must be secured, and must be separate 10cm or more from the distribution line.
B
MDU panel mounting
Figure of the breaker mounting is removed the terminal cover.
4 Characteristics and Dimensions
MDU is connected with circuit breaker via MDU connection cable.
Control power
3 4 DB DA 7 8 DB DA
Terminal block M3 nut
Type NF400-SEP NF400-HEP
B A 263 205 393 205
In case of front connection, keep space between MDU and conductor or insulation barrier.
L1L2 1 2 3 4 5 6
Control power 1
2 3 4 5 6 FG SLD DG DB DA
215
7
Characteristics and Dimensions
Measuring Display Unit Breakers
4
NF630-SEP with MDU NF630-HEP with MDU NF800-SEP with MDU NF800-HEP with MDU
Model
NF630-SEP with MDU NF630-HEP with MDU NF800-SEP with MDU NF800-HEP with MDU
Rated current In (A) Rated ambient temperature 40°C
Rated short-circuit breaking capacity (kA)
Number of poles Rated operational voltage Ue V
IEC 60947-2 (Icu/Ics)
AC
300 350 400 500 600 630 Adjustable
400 450 500 600 700 800 Adjustable
3
3
690V 500V 440V 415V 400V 380V 230V 200V
Standard attached parts (Front connection) (*1)
Breaker
MDU accessories
Breaker mounting Panel mounting
4
3
690 10/10 30/30 42/42 45/45 45/45 45/45 85/85 85/85
4 690 15/15 50/50 65/65 70/70 70/70 70/70 100/100 100/100
4 690 10/10 30/30 42/42 45/45 45/45 45/45 85/85 85/85
3
4 690 15/15 50/50 65/65 70/70 70/70 70/70 100/100 100/100
Mounting screw M6 35 (4pcs) Insulation barrier (3P: 2pcs, 4P: 3pcs) MDU, Breaker mounting plate, Mounting screw for breaker mounting plate, Connection cable (for breaker mounting), MDU Mounting screw MDU, Panel mounting bracket, Panel mounting nut, Connection cable (for panel mounting), MDU Mounting screw
Note *1 4-pole models are provided with auxiliary handle.
NF630-SEP with MDU (Breaker mounting)
Operating Characteristics 10h
LTD operating time at 130% 790s (TL = 150s set) 530s (TL = 100s set) 315s (TL = 60s set) 65s (TL = 12s set)
2h 1h
Note) Current setting Rated Current In: 630A Ir: 300-630A (Adjustable)
LTD operating time TL 12-60-100-150s ±20% (at 200%)
2min 1min
5s 2s 1s
Pre-alarm pickup current Ip Ir x(0.70-0.75 -0.8-0.85-0.9 ±10% -0.95-1.0)
0.2s 0.1s 0.05s
60 70 100 130
0.1s
0.01s
STD pickup current Is Ir × (2-2.5-3-3.5-4 -5-6-7-8-10) ±15%
Pre-alarm operating time Tp TL ±20% 2 (at 200%)
STD operating time Ts 0.3±0.06s 0.2±0.04s
Tp=
0.1±0.03s 0.06±0.02s
INST pickup current II x4-x12 ±15% (Magnification to In)
0.02s
300 400
60 70 100 130
200
Max. total breaking time
300 400
600 1000 1500 3000 500 700 2000 4000 Current (% of Ir) Instantaneous tripping current (% of In)
Current Reducing Curve Operating handle Right-side mounting
AL
Derating of Load current (%)
(*1)
AX
AL for MDU transmission AX for MDU transmission (*1)
SHT or UVT MG
EAL
TBL
TBM
PAL
ATU
TI
EPAL
130 120 110 100
The rated current does not have thermal characteristics. Reduce the current as shown in the curve on the left chart if the ambient temperature exceeds 40°C.
90 80 70 –10
Lead-wire direction
0
10
20
30
40
50
60
Ambient temperature (°C)
Note *1 Right side mounting is standard of SHT and UVT. Specify separately for left side mounting.
External Accessories Type name Reference Accessories page Breaker mounting Panel mounting 117 F − F-8S Large TC-L Operating handle 119 V − V-8S HL HL-4SW HL-4SW 127 Handle lock device Skeleton TTC HL-S − HLS-8SW 3P MI-8SW3 MI-8SW3 MI 129 Mechanical interlock (*1) 4P MI-8SW4 MI-8SW4 Rear BTC HT HT-4SW HT-4SW 128 Auxiliary handle Notes *1 When selecting the MDU breaker mounting, only the MI panel mounting can be manufactured. Electrical operation *2 Specify the operation method and voltage. Order in combination with the NFM device breaker unit. Accessories
Terminal cover
4 Characteristics and Dimensions
Pre-alarm pickup current Ip Ir x(0.70-0.75 -0.8-0.85-0.9 ±10% -0.95-1.0)
0.05s
Max. total breaking time
Left-side mounting
(*1)
5s
0.2s
Internal Accessories
(*1)
10s
1s
600 1000 1500 3000 500 700 2000 4000 Current (% of Ir) Instantaneous tripping current (% of In)
7
30s 20s
0.5s
0.1±0.03s 0.06±0.02s
200
1min
2s
STD operating time Ts 0.3±0.06s 0.2±0.04s
INST pickup current II x4-x15 ±15% (Magnification to In)
0.02s 0.01s
STD pickup current Is Ir × (2-2.5-3-3.5-4 -5-6-7-8-10) ±15%
Pre-alarm operating time Tp T Tp= L ±20% 2 (at 200%)
0.5s
LTD operating time TL 12-60-100-150s ±20% (at 200%)
2min
30s 20s 10s
Note) Current setting Rated Current In: 800A Ir: 400-800A (Adjustable)
LTD operating time at 130% 790s (TL = 150s set) 530s (TL = 100s set) 315s (TL = 60s set) 65s (TL = 12s set)
30min 20min 14min 10min 6min 4min
Rated ambient temperature
1h 30min 20min 14min 10min 6min 4min
Operating characteristics NF800-SEP with MDU NF800-HEP with MDU (Magnification to In)
5h
Operating time
2h
Operating time
10h
Operating characteristics NF630-SEP with MDU NF630-HEP with MDU (Magnification to In)
5h
216
3P 4P 3P 4P 3P 4P 3P 4P
Type name Breaker mounting Panel mounting − TCL-8SW3 − TCL-8SW4 TTC-8SW3-MDU TTC-8SW3 TTC-8SW4-MDU TTC-8SW4 BTC-8SW3 BTC-8SW3 Only line side BTC-8SW4 BTC-8SW4 Only line side −
(*2)
Reference page
121
133
7 Characteristics and Dimensions
4 Measuring Display Unit Breakers
NF630-SEP with MDU · NF630-HEP with MDU · NF800-SEP with MDU · NF800-HEP with MDU
Insulating barrier (removable)
51
70
Conductor t max. 600AF t8 800AF t12
35
94.5
600AF 44 800AF 46
Breaker
32
97
90
14
210
MDU terminal cover
40 140
600AF 44 800AF 46 5
22
M6 taps or f7
70
107
3-pole
Conductor t max. 600AF t8 800AF t10
155
4-pole Drilling plan
Conductor drilling for direct connection
4-pole
Rear connection
1mm clearance on each side of handle. (Load side of breaker mounting has given the space to pass wires to the terminal.)
Front-plate cutout
Connection allowance
Stud can be rotated 90°
25
MDU
M6 taps or ø7 Breaker
Eddy-current heat-reducing slit
4-pole
4-pole
3-pole
3-pole
5
Mounting plate
70
40
131
f14 M12 bolt
210
3-pole
f8.5
30
Neutral pole
280
f8
f14
51
87 32
50
Dimension of terminal directly connected to conductor
8
15
85
PE
8
Current indication LED OVER PAL MDU 70%
15
75
102
275
103
Trip button
600AF 24 800AF 26
8
87
110
Mounting hole
243
Front connection
12
Outline Drawing
Breaker
138
92
46 46
243
12.5
295
R6
R6
40
243
8 13
Breaker
10
15
10 8
32 113
ø13
110
70
70
M6 breaker mounting screw
140
M12 bolt
140
51
6
70
ø48
51 172
(86) 210 172
3-pole 4-pole Drilling plan
Note The drilling plan is different if insulating barriers are installed.
<Panel mounting>
CC-Link ; only MDU panel mounting
NF630-SEP, NF630-HEP, NF800-SEP, NF800-HEP with MDU (No transmission, Pulse output) MDU is connected with circuit breaker via MDU connection cable.
MDU panel mounting
Panel thickness 1-3.2mm 72
<Panel mounting> 4 3 2 1
40
L2 L1
86.5
MDU display part
Terminal PE screw (M4)
Control power 1 A
28.5
Panel holder plate
For the set installation
2
Pulse output
MDU connector
113 114
B
Terminal block
90
85
96
72
4
Front panel cutout
M3.5 screw
L1L2 1
58.5 30
3
No transmission
M3 nut
Terminal block
8.5
Figure of the breaker mounting is removed the terminal cover.
MDU terminal
Panel 90
12
70
M4 screw
40
R2
75
75
40
Operation/display side
Upper side
Space greater than the value shown in the figure below must be secured, and must be separate 10cm or more from the distribution line.
Type NF630-SEP NF800-SEP NF630-HEP NF800-HEP
Terminal cover
M4 screw 54
M3 nut
B A 253 221 263 221 383 221
2 3 4 5 6
Control power In case of front connection, keep space between MDU and conductor or insulation barrier.
1
2
No transmission
FG
Pulse output
FG
3
4
5
6
7
113 114
NF630-SEP, NF630-HEP, NF800-SEP, NF800-HEP with MDU (CC-Link)
75
28.5
12
70
Panel holder plate
43.1
55
Terminal block
58.5 23
Terminal cover M3 screw
MDU display part
8 7 6 5 4 3 2 1
76
L2 L1 1 2 SLD DG 5 6 SLD DG
For the set installation
Front panel cutout
67.5
104.5
M3 screw
72
85 90 96
48
M3 nut
R2
86.5
MDU connector
Terminal PE screw(M4)
75
40
38
90
M3 screw Upper side
Panel thickness 1-3.2mm
Panel
MDU terminal <Panel mounting>
A
Operation/display side
Space greater than the value shown in the figure below must be secured, and must be separate 10cm or more from the distribution line.
B
MDU panel mounting
Figure of the breaker mounting is removed the terminal cover.
4 Characteristics and Dimensions
MDU is connected with circuit breaker via MDU connection cable.
Control power
3 4 DB DA 7 8 DB DA
Terminal block M3 nut
Type NF630-SEP NF800-SEP NF630-HEP NF800-HEP
B A 272 221 282 221 402 221
In case of front connection, keep space between MDU and conductor or insulation barrier.
L1L2 1 2 3 4 5 6
Control power 1
2 3 4 5 6 FG SLD DG DB DA
217
Characteristics and Dimensions
7
Miniature Circuit Breakers
5
BH BH-P
Model
BH
Number of poles
1
Rated current (A) at ambient temperature 40˚C
70
1
2
70
DC
3
70, 100 70, 100
230/400
230/400
125
Rated short IEC 60898-1 AC230/400V circuit AC400V capacity (kA) − DC125V
BH
3
70, 100 70, 100
AC
Rated voltage (V)
BH-P
2
125
3
−
3
−
3
−
− 3
1
1
BH-P
Operating Characteristics
Temperature Compensation Curve
4h
135
Type:BH, BH-P Rated Current:70, 100A
1h
Rated ambient temperature
140 Operating Characteristics
2h
130
Amb. temp.:40°C
125
Current rating (%)
30min 20min 14min 10min 6min 4min
120 115
70, 100A
110 105 100
2min
95
1min
Operating time
90 30s
85
20s
0
10
20
Max.
10s
30
40
50
60
Ambient temperature (°C)
5s Min.
2s 1s 0.5s
0.2s 0.1s 0.05s
0.02s 0.01s 1
1.13
1.45
2
3
4
5
6
7
10
15
20
30
40
100% of rated current
Outline Drawing
74
M5 0.8 screw
71.5
Plug-in terminal (line side)
7.5
113
95
57
95
73
•BH-P
32
M5 0.8 screw (line side and load side)
57.5
Mtg bracket
100
•BH
Breaker center 25 25
50
25
50
75
22
47
47
57.5
Mtg hole f4.5
63.5 77.5
25
25
60.5
25
50
75
65.5
20.5
45.5
70.5
79
1-pole
2-pole
3-pole
6
f5
.5
Conductor thickness t=4 max.
5.5
1-pole
2-pole
3-pole
13.5
12
Conductor drilling
Note Two mounting brackets are used for single-pole breakers. and four for 2-pole and 3-pole breakers.
218
4.5
5 Characteristics and Dimensions
7
14
Mtg slot
7 Characteristics and Dimensions
5 Miniature Circuit Breakers BH · BH-P · BH-D6 · BH-D10
BH-D6 BH-D10
Model
BH-D6
Number of poles (P)
1
2
Instantaneous tripping
AC
1
2
0.5, 1, 1.6, 2, 3, 4, 6, 10, 13, 16, 20, 25, 32, 40
0.5, 1, 1.6, 2, 3, 4, 6, 10, 13, 16, 20, 25, 32, 40, 50, 63
4(3+N) (*1)
3
1
2
Type B, C, D
Type B, C
440
250
0.5, 1, 1.6, 2, 3, 4, 6, 10, 13, 16, 20, 25, 32, 40, 50, 63
0.5, 1, 1.6, 2, 3, 4, 6, 10, 13, 16, 20, 25, 32, 40, 50, 63
440
Rated current In (A) at ambient temperature 30°C
IEC60898-1 GB10963.1 (Icn)
2(1+N) (*1) Type B, C
Type B, C, D
Rated insulation voltage Ui (V)
Rated shortcircuit capacity (kA)
4(3+N) (*1)
3
BH-D10 (For DC)
BH-D10
230V
6
−
6
10
−
6
−
230/400V
6
−
−
10
−
6
−
400V
−
6
−
−
10
−
6
IEC60898-2 DC 125V GB10963.2 250V (Icn)
−
−
10
−
−
−
−
10
Note *1 N pole is a switched neutral pole (without overcurrent release device).
BH-D6
Operating Characteristics 4h
30min 20min
2h
30min 20min
5min
10min
5min
5min
Max.
(0.5A-4A) Max.(13A-63A)
1min
Operating time
10s 5s 2s
30s 20s
Max.(6A-10A)
10s 5s 2s
Min.
30s 20s 10s 5s 2s
B
C
0.02s
0.1s
0.1s
0.05s
0.05s
1 1.13 1.45
0.6 0.7
2
3
4
5
6 7
10
15
20
0.01s
30
0.01s 0.6 0.7
100% of rated current
1 1.13 1.45
2
3
4
5 6 7
10
15
20
30
0.6 0.7
1 1.13 1.45
2
3
4
5 6 7
10
15
20
30
100% of rated current
100% of rated current
Temperature Compensation Curve
Outline Drawing M5 screw
C
0.02s
0.02s
0.01s
B
0.2s
0.2s
0.1s 0.05s
Min.
1s 0.5s
0.5s
0.2s
Max.
1min
Min.
1s
0.5s
Neutral pole (1+N only)
Neutral pole
18
36
18
36
54
54
17 44 70 max.
6
72
110 100
5 Characteristics and Dimensions
120 18
7
Rated ambient temp.
130 87
45
44.5
Ambient compensation
Current ratings (%)
Operating time
2min
2min
30s 20s
Operating Characteristics Type : BH-D10(Type B,C) Rated current : DC 0.5A-63A Amb.temp. : 30°C
1h 30min 20min
10min
2min
1s
2h
Operating Characteristics Type : BH-D6,BH-D10(Type D) Rated current : AC 0.5A-63A Amb.temp. : 30°C
1h
10min
1min
4h
4h
Operating Characteristics Type : BH-D6,BH-10(Type B,C) Rated current : AC 0.5A-63A Amb.temp. : 30°C
1h
Operating time
2h
90 Solderless terminal
80 –10
0
10
20
30
40
50
Ambient temperature (°C) 1P
2P
3P
4P
219
7
Characteristics and Dimensions
5
Miniature Circuit Breakers Residual Current Circuit Breakers
BH-DN
Model
BH-DN
Number of poles (P)
2 (1+N) (*1)
Instantaneous tripping
Type C
Rated insulation voltage Ui (V)
230
Rated current In (A) at ambient temperature 30˚C Rated shortIEC60898-1 circuit GB10963.1 capacity (Icn) (kA)
6, 10, 16, 20
AC
230V
4.5
Note *1 N pole is a switched neutral pole (without overcurrent release device).
BH-DN
Operating Characteristics 4h
Operating Characteristics Type : BH-DN Rated current : 6A-20A Amb.temp.:30°C
2h 1h 30min 20min 10min 6min 4min
Operating time
2min 1min
Max.
30s 20s 10s 5s
Min.
2s 1s 0.5s 0.2s 0.1s 0.05s 0.02s 0.01s
0.6 0.7
1 1.13 1.45
2
3
4
5 6 7
10
15
20
30
100% of rated current
Temperature Compensation Curve
Outline Drawing M4 screw
8.4 18
Ambient compensation Rated ambient temp.
N
N
7
130
Current ratings (%)
120
70 max. 17 44
5 Characteristics and Dimensions
45
100 90
6
80 –10 45 88
220
110
Solderless terminal
0
10
20
30
Ambient temperature (°C)
40
50
7 Characteristics and Dimensions 5 Miniature Circuit Breakers · Residual Current Circuit Breakers BH-DN · BV-D
BV-D
BV-D
Model Number of poles (P) Rated operational voltage Ue (VAC) Rated current In (A) at ambient temperature 30°C
2 (1+N) (*1)
4 (3+N) (*1) (*2)
230
230/400 25, 40, 63 30, 300
Rated current sensitivity IΔn (mA)
0.04
Max. operating time at 5IΔn (s) Pulsating current sensitivity
Type AC
Residual operation
Dependent on line voltage
Rated making and breaking capacity Im (A) Rated conditional short-circuit current Inc (kA)
500 (In 25, 40A) 630 (In63A) 6
Rated residual making and breaking capacity IΔm (A)
500 (In 25, 40A) 630 (In63A)
Rated conditional residual short-circuit current IΔc (kA)
6
Notes *1 N pole is a switched neutral pole (without overcurrent release device). *2 For use to three phase 4-wire type. When using, it be sure to connect the neutral wire to the neutral phase. Not available for use to three phase 3-wire type.
BV-D
Operating Characteristics 4h 2h 1h 30min
Rated non-operating current
4min
Operating time
2min 1min 30s 10s 5s 2s 1s
Rated current sensitivity
10min
0.5s 0.2s 0.1s 0.04s 0.02s 0.01s 25 50 100
500
Ground-fault current (% of rated current sensitivity)
Outline Drawing Test button
Residual indicator
7
18 54 72
17
44
5 Characteristics and Dimensions
18 36
85
45
42.5
M5 screw
6
70 max.
Solderless terminal 2P
4P
221
7
Characteristics and Dimensions
Residual Current Circuit Breakers with Overcurrent Protection Isolating Switches
5
BV-DN
BV-DN
Model
2 (1+N) (*1)
Number of poles (P) Rated operational voltage Ue (VAC)
230
Rated current In (A) at ambient temperature 30˚C
6, 10, 16, 20, 25, 32, 40
Instantaneous tripping
Type C 30, 100, 300
Rated current sensitivity IΔn (mA)
0.04
Max. operating time at 5IΔn (s) Pulsating current sensitivity
Type AC
Residual operation
Dependent on line voltage
Rated IEC61009-1 short-circuit GB16917.1 capacity (kA) (Icn)
AC
230V
4.5
Note *1 N pole is a switched neutral pole (without overcurrent release device).
BV-DN
Operating Characteristics 4h
4h
Operating Characteristics Type : BV-DN Rated current : 6A-40A Amb.temp.:30°C
2h 1h 30min 20min
2h 1h 30min
2min
Max.
30s 20s
Operating time
Operating time
1min
10s 5s
Min.
1min 30s 10s 5s 2s
2s 1s
1s
0.5s
0.5s
0.2s
0.2s
0.1s
0.1s
0.05s
0.04s 0.02s
0.02s 0.01s
Rated current sensitivity
4min
2min
Rated non-operating current
10min
10min 6min 4min
0.01s 0.6 0.7
1 1.13 1.45
2
3
4
5 6 7
10
15
20
100% of rated current
25 50 100
30
500
Ground-fault current (% of rated current sensitivity)
Temperature Compensation Curve
Outline Drawing Test button M4 screw
Residual indicator
120 Current ratings (%)
N
N
8.4
36
7
Rated ambient temp.
130
70 max. 44 17
5 Characteristics and Dimensions
45
110 100 90 80 –10
0
10
20
30
6
Ambient temperature (°C) 45 88
222
Solderless terminal
40
50
7 Characteristics and Dimensions 5 Residual Current Circuit Breakers with Overcurrent Protection · Isolating Switches BV-DN · KB-D
KB-D
Model
KB-D
Number of poles (P)
1
2
Utilization category
3
4 (3+N) (*1)
AC22A class
Rated insulation voltage Ui (V)
250
Rated voltage Ue (VAC) Rated current In (A) at ambient temperature 30˚C Short-time withstand current (A)
230
440 400 32, 63, 80 203In , 1sec
Short-time making current (A)
203In
Note *1 N pole is a switched neutral pole (without overcurrent release device).
KB-D
Outline Drawing M5 screw
45
87
44.5
Neutral pole
18
18
36
18
36
54
54
17
44
6
70 max.
72
Solderless terminal
2P
3P
4P
7 5 Characteristics and Dimensions
1P
223
Characteristics and Dimensions
7
Circuit Protectors
6
CP30-BA
Frame (A)
30
Model
CP30-BA
Number of poles
1
2
Rated impulse withstand voltage Uimp (kV)
0.1, 0.25, 0.3, 0.5, 1, 2, 3, 5, 7, 10,15, 20, 30
Rated current (A) AC (V)
Rated voltage (V)
UL 1077 CSA C22.2 No.235
250
DC (V)
65
125
AC 2.5kA at 65V
2.5kA at 125V
Rated insulation voltage Ui (V)
−
250
AC
2.5kA at 230V
DC
2.5kA at 60V
2.5kA at 120V
Rated insulation voltage Ui (V)
EN 60947-2 IEC 60947-2 (Icu/Ics)
−
2.5kA at 250V
DC Rated shortcircuit IEC 60934 capacity (kA) EN 60934
−
250
AC
2.5/2.5kA at 230V
DC
2.5/2.5kA at 60V 2.5/2.5kA at 120V
−
−
AC-DC common use
CP30-BA
3
2.5
Instantaneous type (I) Medium type (M),(MD) Slow type (S),(SD) Fast type (F) Instantaneous type (I): magnetic only Other type (M, MD, S, SD, F):hydraulic-magnetic
Operating characteristics Mode of tripping
Operating Characteristics Instantaneous type (I)
Fast type (F)
1h 40min
DC
20min
AC
DC
1h 40min
DC
1h 40min
DC
20min
AC
20min
AC
20min
AC
10min 6min 4min
2min
2min
1min
1min
1min
1min
Operating time
30s 20s 10s 5s 2s 1s
30s 20s 10s 5s 2s 1s 0.5s
30s 20s 10s 5s 2s 1s
2s 1s 0.5s 0.2s
0.2s
0.1s
0.1s
0.1s
0.05s
0.05s
0.05s
0.01s 100 135 200 300 500 1000 125 400 700
5000 10000
2000
0.01s 100 135 200 300 500 1000 125 400 700
5000 10000
Terminal cover
Terminal cover
IEC 35mm rail
7
56 63
73
67 39
ON 54
ON
22.5
22.5
Terminal cover
1h 40min
1h 40min
20min
20min
10min 6min 4min
10min 6min 4min
2min
2min
1min
1min
30s 20s 10s 5s 2s 1s 0.5s
9.5 9.5
17.5
17.5
35
17.5
AXb 12
63 65
17.5
52.5 17.5
AXc 11
AXa 14
AXc 11
Alarm or auxiliary switch terminal M3.5 (Plus minus self-up screw) (The figure shows auxiliary switch. Example: Auxiliary switch)
AXb 12
Main terminal (Plus minus self-up screw) M4·····20A max. M5·····20A over
AXa 14
5
AXa 14
1-pole
2-pole
3-pole
54
Mounting dimension
47 2-M4 tap Tightening torque 1-1.4 (N·m)
(3)
1s
0.2s 0.1s 0.05s 0.02s
0.01s 100 200 300 500 1000 125 400 700
2000
5000 10000
0.01s 100 200 300 500 1000 125 400 700
Current (% of rated current)
2000
5000 10000
Current (% of rated current)
3
Temperature Characteristics Curve 300 250 200 150
Rated ambient temperature
100 90 80 70 60 -10
29.5
1-pole 2-pole 3-pole 2-M tap 2-M tap
2s
Terminal block of internal accessaries (AL, AX, SHT)
17.5
AXb 12
31.5
5s
0.1s
Operating time variation (%)
9.5
9.5
10s
0.05s 0.02s
5.5 19
30s 20s
0.5s
0.2s
Mounting hole ø4.5
5000 10000
Slow type with inertial delay (SD) 2h
Operating time
35
47
2000
Current (% of rated current)
2h
Operating time
29.5
ON
0.01s 100 135 200 300 500 1000 400 700 125
5000 10000
Medium type with inertial delay (MD)
•CP30-BA Terminal cover
2000
Current (% of rated current)
Current (% of rated current)
Outline Drawing 12
0.02s
0.02s
0.02s 2000
Current (% of rated current)
224
5s
0.1s
0.01s 100 150 200 300 500 1000 125 180 400 700
12
10s
0.05s 0.02s
AXc 11
30s 20s
0.5s
0.2s
0.2s
Operating time
10min 6min 4min
2min
Operating time
10min 6min 4min
0.5s
6 Characteristics and Dimensions
Slow type (S) 2h
1h 40min
2min
10min 6min 4min
Operating time
Medium type (M) 2h
2h
2h
0
10
20
30
40
Ambient temperature (°C)
50
60
7
Characteristics and Dimensions
Electrical Operated Circuit Breakers
7
(1) Dimensions of electrical operated circuit breakers The following concept is applied for the dimensions of the electrical operated circuit breaker. Please understand this before using this type of breaker. Connection method
Outline dimensions listing method Model NF125-CV/SV/HV NV125-CV/SV/HV NF125-UV NF125-SEV/HEV/RV/ZEV NF250-CV/SV/HV/SEV/HEV NF250-RV NF125-SGV/LGV/HGV/RGV NF160-SGV/LGV/HGV NF250-SGV/LGV/HGV/RGV NV125-SEV/HEV NV250-CV/SV/HV/SEV/HEV NF250-UV
Front connection (Rear connection)
Rear connection Plug-in
Listed page 229 (*1)
230
(*1)
Model NF400-CW/SW/SEW/HEW/REW NF630-CW/SW/SEW/HEW/REW NF400-UEW (3P) NV400-CW/SW/SEW/HEW/REW NF400-UEW (4P) NV630-CW/SW/SEW/HEW NF800-CEW/SEW/HEW/REW/SDW NF800-UEW NV800-SEW/HEW
Listed page
230
231
NF1000-SEW, NF1250-SEW/SDW NF1600-SEW/SDW
232
The drilling dimensions and connection related dimensions are the same as the dimensions for the breaker body. Refer to the dimension drawings of each model. Note that for the rear connection type, four mounting holes are required even for the 2-pole or 3-pole types.
(2) Front connection (Rear connection) NF125-CV, NF125-SV, NF125-HV NV125-CV, NV125-SV, NV125-HV Front connection Operation circuit terminal Center line of electrical operation device cover mounting screw Operation circuit terminal board Operation circuit terminal cover (Standard supply) (M3 tapping) (M3.5 screw) Power supply module Breaker M8 screw 24 Manual handle P1 P2
S1 S2 S4
B
A
B
B
A
B
A
111
A
41 39
86
78 112 130
ON button
80
S1 S2 S4
45
P1 P2
Center line of electrical operation device
25
50
OFF lock plate
R1
Insulation barrier (removable)
Manual/automatic selection switch 60 86 90
OPEN (TRIP) button
3-pole
Electrically operated base 158 164
61
30
Neutral pole Front plate
90
Display hole (ON (green), OFF (red), TRIP (yellow))
86 90 120
4-pole
30
30
4-pole
3-pole
Front plate cut out
Drilling plan
Test button
88
M4 0.7 screw or f5
Remarks: 1. This cannot be mounted on the 2-pole breaker. 2. The test button is equipped only on the earth leakage circuit breaker.
NF125-SEV, NF125-HEV, NF125-RV NF250-CV, NF250-SV, NF250-HV, NF250-SEV, NF250-HEV, NF250-RV NV125-SEV, NV125-HEV NV250-CV, NV250-SV, NV250-HV, NV250-SEV, NV250-HEV NF125-SGV/LGV/HGV/RGV NF160-SGV/LGV/HGV NF250-SGV/LGV/HGV/RGV
P1 P2
S1 S2 S4
70 86 90 105
3-pole
35 86 90 105 140
4-pole
A
B
B
A
B
A
126
86 Manual handle
100
OPEN (TRIP) button
B
33 31
78 144 165 Manual/automatic selection switch
A
Electrically operated base Front plate
Neutral pole Test button
80
S1 S2 S4
ON button
32
P1 P2
Center line of electrical operation device
Breaker
R1
OFF lock plate
45
100
Insulation barrier (removable)
15.5
Operation circuit terminal Operation circuit terminal cover cover mounting screw (Standard supply) (M3 tapping) Operation circuit terminal board Power supply Hexagon socket M8 bolt (M3.5 screw) module 24
Center line of electrical operation device Display hole (ON (green), OFF (red), TRIP (yellow))
44 61 158 164
35
35
3-pole Drilling plan
4-pole
M4 0.7 screw or f5
88
Front plate cut out
Remarks: 1. The test button is equipped only on the earth leakage circuit breaker. 2. For details of external dimensions of breakers, please refer external dimension drawing of each model.
225
7 Characteristics and Dimensions
7
Front connection
7
Characteristics and Dimensions
Electrical Operated Circuit Breakers
7
NF400-CW, NF400-SW, NF400-SEW, NF400-HEW, NF400-REW, NF630-CW, NF630-SW, NF630-SEW, NF630-HEW, NF630-REW Motor drive type Center line of electrical operation device
Breaker
194
257
8
Operation circuit terminal block (M3.5 screw)
110
Breaker
70
120
Max. conductor thickness 400A frame: t=8 600/630A frame: t=10 44
Center line of breaker
231
Insulating barrier
Center line of electrical operation device and breaker
277
Front connection
44
43
16 112 140 231
Trip button
22
f14 M12 bolt
28
44
M6 or f7
2- and 3-pole
195
56
4-pole
255
168 185 196
2- and 3-pole
44
44 94.5
Drilling plan
4-pole
Remark: 1. 2-pole models are 3-pole with the central pole conductor removed.
NF400-UEW (3-pole) Motor drive type
43
127.5 78 8 Breaker f7
Center of breaker Center line of electrical operation device
Conductor thickness t=8 max.
Breaker Operation circuit terminal block M3.5 screw
f12.5
Insulating barrier
Center line of electrical operation device and breaker
110
Front connection
234
44
44
16 43 110 28 112 140 231
Trip button
144 ø7
ø12.5
257
297
70 20
120
277
47
141 191.5 292 352
f14 M12 bolt
M6 screw or f7
Drilling plan
NV400-CW, NV400-SW, NV400-SEW, NV400-HEW, NV400-REW, NV630-CW, NV630-SW, NV630-SEW, NV630-HEW Motor drive type 231
Insulating barrier
Center line of breaker
Operation circuit terminal block M3.5 screw
110 257
70
120
Breaker
Breaker
44
16 43
7
8
Test button
44
Trip button
Max. conductor thickness 400A frame: t=8 600A frame: t=10 44
194
Center line of electrical operation device
Center line of electrical operation device and breaker
277
Front connection
112 140 231
22 56
f14 M12 bolt
94.5 195 255
28 168 185 196
3-pole
44
3-pole
Center line of breaker
Conductor thickness t=8 max. f14
143 97 6.5
Breaker f7
f14 M12 bolt
35 16 48 110 35 70 210 280 231
226
Neutral pole Operation circuit terminal block M3.5 screw
290
112
ø7
f14
275
322
15
48
7 Characteristics and Dimensions
NF400-UEW (4-pole) Motor drive type Center line of electrical operation device
4-pole
Drilling plan
4-pole
Front connection
44
M6 screw or f7
140 6.5 141 191.5 292 352
M6 screw or f7
Drilling plan
7 Characteristics and Dimensions
7 Electrical Operated Circuit Breakers
NF800-CEW, NF800-SDW, NF800-SEW, NF800-HEW, NF800-REW Motor drive type Front connection
Center line of electrical Center line of breaker operation device Operation circuit terminal block M3.5 screw
Breaker
277
275
70
120
Breaker
46 8
Conductor thickness t=12 max.
110
Insulating barrier
243
Center line of electrical operation device and breaker
Trip button
35
140 210 231
40
70 210 280 231
2- and 3-pole
87
15 32 8
44 Neutral pole
70 46 94.5 195 255
f14 M12 bolt
2- and 3-pole
M6 screw or f7
70
4-pole
Drilling plan
4-pole Remark: 1. 2-pole models are 3-pole with the central pole conductor removed.
NF800-UEW Motor drive type Front connection
Center line of electrical Center line of breaker operation device 40 Insulating barrier 14
Center line of electrical operation device and breaker
Breaker f7
f14
8 32
Breaker
87 110
15
Center line of breaker Center line of electrical operation device
143 64 8
Conductor thickness t=8 max.
Trip button
35 70
140 210 231
3-pole
f14 M12 bolt
210 280 231
70
8 143 191.5 292 352
Neutral pole Operation circuit terminal block M3.5 screw
290
290
112
87
44
f7
f14
275
322
277
70 23.5
120
15
3-pole
M6 screw or f7
140
4-pole
Drilling plan
4-pole
NV800-SEW, NV800-HEW Motor drive type Front connection
7
Insulating barrier 14
Conductor thickness t=12 max.
46 8 Breaker
277 Operation circuit terminal block M3.5 screw 70
87
32
8
44
243
87 275
70
120
110
Breaker
7 Characteristics and Dimensions
Center line of electrical operation device and breaker
M6 screw or f7
Trip button 40 140 210 231
15
46 Test button
94.5 195 255
Drilling plan
f14 M12 bolt
227
7
Characteristics and Dimensions
Electrical Operated Circuit Breakers
7
NF1000-SEW, NF1250-SEW, NF1250-SDW Motor drive type Front connection 280 (4-pole)
Center line of 4-pole breaker Insulating barrier
110
210 (4-pole) 70
Conductor thickness t=82 max.
55 15
Bolt max. M1250
Breaker
375
406 120 61
Operation circuit terminal block M3.5 screw
44
Neutral pole 70
15 32
80
8
13
f13 M12 bolt
43 140 210 (3 -pole)
59 140 231 290
Center line of electrical operation device and 3-pole breaker
70
3-pole
M8 screw or f10
4-pole
Drilling plan Remark: 1. 2-pole models are 3-pole with the central pole conductor removed.
NF1600-SEW, NF1600-SDW Motor drive type Front connection
228
375
130
120 61
7 Characteristics and Dimensions
7
406
35 210 280
115
Center line of electrical operation device
55
Breaker
Operation circuit terminal block M3.5 screw 44 210
20
Bolt max. M1065
(185.5)
38
(185.5)
Conductor thickness t=6 width 75 max.
ø 11 15
60 38
203 263
101.5 304.5 364.5
3-pole
4-pole
69.5 140 231 290
Neutral pole
70
3-pole
70
4-pole Drilling plan
M8 screw or f10
7 Characteristics and Dimensions
7 Electrical Operated Circuit Breakers
NF1600-SEW (3-pole) Motor drive type Rear connection
Mounting angle Operation circuit terminal block M3.5 screw
Connection allowance
Mounting angle
Breaker
15
160 or more 81.5
109
100 or less
38
273
f9.5
f17.5
406
120 61
20
18.5
269
Stud can be rotated 90° 15 Conductor thickness t=6 width 75 max.
231
140
125
290
210
38
15
36
38 60
44
f11 Bolt M1050
M8 screw or f10
70
212
200
Drilling plan
Bottom view
NF1600-SEW (4-pole) Motor drive type Stud can be Connection rotated 90° allowance Conductor thickness 15 t=6 width 75 max.
Breaker
100 or less
273
109 20 ø9.5
ø17.5
406
61
120
18.5
Mounting angle
38 60
231 Center line of electrical operation device
20
70 210
290
f11 Bolt M1050
125
15
54
38
18
44
269
35
Mounting angle
160 or more
Operation circuit terminal block M3.5 screw
210
81.5
Rear connection
18 106
106
280
M8 screw or f10
70
318
Drilling plan
Bottom view
NF1600-SDW (3-pole) Motor-drive type Operation circuit terminal block Mounting angle Stud can be turned 90º. M3.5 screw Connection allowance Conductor thickness t=6width 75 max.
Rear connection
Mounting angle
Breaker
160 or more
36
15
175 or more
233
109
20 406
120 61
38
f9.5
231
140
38 60
f17.5
44
290
210
125
38
15
f11 Bolt M1050
70
212
M8 screw or f10
200
Bottom view
375
15 18.5
7
Drilling plan
Remark: 2-pole models are 3-pole models with the central pole removed.
35
Operation circuit terminal block M3.5 screw
Mounting angle
233 231
70 210 280
290
125
38 60 f11 Bolt M1050
18 106
106 318
Bottom view
15
38
f9.5
f17.5
44
Center of electrical operation device
Breaker
Mounting angle
109 20 406
61
120
18.5
Stud in horizontal direction. Connection It cannot be turned 90°. allowance Conductor thickness 15 t=6width 75 max.
70
375
210
175 or more 160 or more
Rear connection
7 Characteristics and Dimensions
NF1600-SDW (4-pole) Motor-drive type
M8 screw or f10
Drilling plan
229
7 Characteristics and Dimensions
MEMO
7
230
8
Handling and Maintenance
1) Storage and Transportation… ………………………………………………………………………………………………………………… 2) Standard Working Conditions… ……………………………………………………………………………………………………………… 3) Mounting and Connections … ………………………………………………………………………………………………………………… 4) Maintenance and Inspections… ……………………………………………………………………………………………………………… 5) Troubleshooting… ………………………………………………………………………………………………………………………………
232 232 232 234 236
231
8 Handling and Maintenance 1. Storage and Transportation (1) Precautions for storage Avoid corrosive gases
H 2S
Store in the OFF or tripped state
Avoid moisture
Store the breaker in the OFF state or tripped state.
Do not leave the breaker in a humid place for long periods of time.
Ammonia
Do not store the product in an atmosphere containing acidic gas or ammonia gas. H2S 0.01ppm or less SO2 0.05ppm or less NH3 0.25ppm or less
(2) Precautions for transportation Carefully pack and transport
Do not drop the package during transportation. When shipping the breaker, make sure to package it carefully.
Do not carry by holding the front and back of the flush plate
Do not carry by the lead wires
Do not carry the embedded type breaker by holding the front and back of the flush plate. The breaker could drop during transportation.
Do not carry the accessories by the lead wires. Excessive force will be applied on the accessories.
Do not transport upside down (when mounted on IEC 35mm rail)
Do not transport a panel containing parts mounted on an IEC 35mm rail in an upside down state.
2. Standard Working Conditions Working ambient temperature … -10°C to 40°C Relative humidity … 85% or less with no dew condensation. (Note that the 24-hour average value must not exceed 35°C) Altitude … 2000m or less working current reduction rate in ambient temperature exceeding 40°C. Atmosphere … Free of excessive moisture, oil vapors, 50°C… 0.9 fold smoke, dust, salt, corrosive substances, 60°C… 0.7 fold vibration or impact, etc.
Handling and Maintenance
3. Mounting and Connections
8
(1) Precautions for mounting Attention to dust and cutting chips!
Do not block ventilation ports
Make sure that the breaker does not come in contact with rain water, oil, dust or cutting chips. Special attention must be taken to conductive materials such as scraps from drilling steel plates.
Do not block the ventilation ports. The breaker performance could drop. Ensure the insulation distance for breaker mounting indicated on page 101.
Avoid direct sunlight
Make sure that the breaker is not subject to direct sunlight during use. An increase in temperature could cause malfunctions. Sunlight could also discolor the nameplate and molded case, etc.
Mounting style
• NF30-CS • CP30-BA
107%
93% ON
ON ON
ON
110%
90%
ON ON ON
ON
107%
93% 100%
Rate of change of rated current by mounting angle
232
Do not remove the rear cover from the back of the base.
Do not wipe with thinner, detergent or chemical cloth
100%
Pay attention to the mounting angle of the following models as the overcurrent tripping characteristics may vary according to the mounting stye. Use in a vertical direction is recommended.
Do not remove the rear cover
Do not use thinner, etc., to clean the surface of the breaker. Use compressed air or a dry cloth to clean.
8 Handling and Maintenance
(2) Precautions for Connections Connect conductors parallel to each pole
Do not apply lubricant to the threads. Oil will decrease the friction at threads and cause the screws to loosen easily, and the unit to overheat. Excessive stress will be applied on the threads even with the standard tightening torque and can cause the screws to break.
Do not connect in reverse
Connect each connection conductor so it is parallel to each pole.
Securely fix conductors
Distance between conductors Current cm target value kA(Pf)
Set power to ON side ···
Insulating support
Bar Connection d When directly connecting the conductor, refer to the outline drawings and drill the conductor. d When connecting the conductors to a bar terminal, pay attention to the insulating distance with the ground. A ground fault prevention barrier is available as an option.
When connecting the conductors on the rear connection type, take care not to deform the studs when tightening.
Electromagnetic force applied per 1m conductor (During 3-phase short-circuit)
d A large electromagnetic force is applied on the connected conductor according to the accident current. Use the conditions on the right as guide and securely fix (tighten) the conductors.
d As a rule, do not connect the power and load in reverse. If necessary, refer to the specifications and select a model which can be connected in reverse. d An insulating barrier should be provided on both the power and load sides of the breakers when using a high voltage circuit where dew condenses easily or in a circuit which has a reverse connection in the circuit.
Do not deform studs
10
20 245
10
(0.4)
490
18
(0.3)
1860
930
25
(0.2)
4410
2205
35
(0.2)
8720
4360
42
(0.2)
12545
6270
50
(0.2)
17835
8920
65
(0.2)
30185
15090
85
(0.2)
51550
25775
100
(0.2)
71540
35770
125
(0.2)
111720
55860
ELCB (NV) connection d When using a single-phase 3-wire method, connect the neutral pole to the NC’s center pole.
100V 200V 100V
NV
Connection band
Wire retention type connection d When directly connecting to the terminal, insert the single strand or stranded wires in straight and then tighten. A commercially-available crimp terminal or bar can be connected directly. d When using stranded wires, split them and then tighten.
d When using a 3-pole ELCB with a single-phase 2-wire, connect to the left and right poles (poles at both sides) of ELCB.
1φ2W
NV
d Never connect the ELCB units in parallel as it will create a loop circuit, and could burn the magnetic device. d Never connect the MCCB and ELCB in parallel.
Solderless terminal connection d Untwist the connection wires, align the core wires and then tighten. The wires will loosen up during use, and must be tightened during periodic maintenance. d Do not solder or bind the end of the strands. d Make sure not to catch the insulating sheath of the wire when tightening.
Handling and Maintenance
Oiling of threads prohibited
8
233
8 Handling and Maintenance 4. Maintenance and Inspections (1) Initial inspections
After installing the MCCB and ELCB, inspect the following matters before powering the units. Model
Inspection items
Common
Remarks
Criterion
1. Are there any excessive screws, drilling scraps, wire scraps or any other conductive materials around the terminals?
All conductive material must be removed.
2. Are there any cracks or damage on the cover or base?
No cracks or breaks allowed.
3. Is there any dew condensation on the cover, base or terminals?
No dew condensation allowed. Refer to Precautions w for the ELCB.
4. Measure the insulation resistance with a 500V insulation resistance tester. 5MΩ or more
ELCB
5. Are the connector connections tightened securely?
Must be specified tightening torque.
6. Are the ELCB rated voltage and circuit voltage the same?
Voltages must be the same.
7. Apply voltage, press the test button and check the operation.
Must trip with an earth leak.
Precautions qWithstand voltage test A guide for the test is given on the following. Do not perform a withstand voltage test exceeding these levels. (Note) Test the operating circuit between the live section and ground. Main circuit
(Unit: V) Auxiliary circuit or control circuit
Test voltage Rated insulation Test voltage voltage of (effective value Rated insulation (effective value for alternating operating for alternating voltage current) circuit current)
(min. 1500)
Handling and Maintenance
1
long time, inspect the breaker one month after starting use and
2
periodically thereafter according to the environmental conditions.
3
Inspection items
8 NV
234
Clean and dry environment
OFF
(*1)
Once every 2 to 3 years
Environment with low levels of dust,
Once a year
corrosive gas, vapors, salt, etc. Places other than 1 or 2
Criterion No conductor must be loose.
2. Is any cover or base cracked? Is any handle damaged?
There must be no cracks, damage or breaks.
3. Has the breaker been submerged and infiltrated with water? Is the breaker heavily dirtied by mud or dust?
There must be no infiltration of water, heavy mud or dust.
4. Has the temperature risen abnormally?
(1) Visually inspect that none of the studs on the backs of the terminals, or the breaker’s tightened or molded sections are discolored from burning. (2) There must be no especially high temperature rise when the current at each phase is balanced. (Tolerable maximum value for terminal temperature rise: 60K) (3) There should be no difference on the left and right side of the base sides if the load current is balanced.
Common
Withstand voltage test
Inspection Interval Guide
To prevent trouble and ensure the breaker operates safely for a
1. Are any of the conductors loose?
Insulation resistance measurement
State of handle ON OFF ON Between live section of main circuit and ground Between left - middle, middle - right, left - right poles Between left - neutral pole, (*1) (*1) middle - neutral poles right - neutral poles Between left - middle, middle - right, left - right poles Between left - neutral poles, (*1) (*1) (*1) middle - neutral poles right - neutral poles Between power - load side terminals Between main circuit live sections - operating circuit live sections Between operating circuit live section - ground Note *1 Values in parentheses apply for measuring display unit breaker.
(2) Periodic inspections
Model
Test
Measurement position
Between different poles Load side Line side
(Application time: one minute)
wInsulation resistance measurement and withstand voltage test The restrictions a and b apply to the following models. Applicable models: Earth leakage circuit breaker, Measuring display unit breaker.
5. Can the handle be turned ON and OFF smoothly? Should operate smoothly. 6. Does pressing the TRIP button result in a trip? Must be resettable after tripping. 7. Test by pressing the TEST button. Must operate properly and close again.
Once every six months Remarks
If any conductor is loose, tighten again with the appropriate torque given in Tables 5-5 and 5-6 on pages 97 to 98.
If water has infiltrated the breaker, it must be replaced with a new part or overhauled by the Mitsubishi Service Center.
There may be a light temperature difference between the following terminals. Between the power side terminal and load side terminal Between the center pole terminal and left and right pole terminals.
Open and close a normally closed breaker periodically. This will clean the contact and prevent abnormal heating. Test the operation once a month.
8 Handling and Maintenance
(3) Inspection after Tripping Whether the circuit breaker can be reused or must be replaced after switching off a fault current depends on the intensity of the current which was switched off. Intensity of trip current, degree of MCCB and ELCB damage, and countermeasures Intensity of trip current
Degree of MCCB and ELCB damage
When it is clear that the circuit breaker operated
No abnormality such as contamination
within the time-delay trip range
around vent observed
(Overcurrent up to 10 times of rated current)
Countermeasures Reusable (The circuit breaker can function 50 times (100A or less) at overload current which is 6 times higher than rated current) Reusable
Soot and dust found near vent
Relatively low short-circuit current which causes instantaneous tripping Large short-circuit current close to rated breaking capacity
Soot and dust found near handle, remarkable contamination found near vent Molten metal found in circuit breaker Box of box type circuit breaker is severely deformed
Replace with a new part
If the intensity of the fault current cannot be estimated, remove the MCCB and ELCB, and measure the insulation resistance. If the specified value (5MΩ) has not been reached, perform a withstand voltage test. If the withstand voltage is within the specified value, the circuit breaker can be used temporarily but it should be replaced with a new part as soon as possible. If both the insulation resistance and withstand voltage are sufficient, the circuit breaker may be judged as reusable. However, it should be checked for abnormalities, such as an abnormal rise in temperature for a set period. d Measure the insulation resistance and perform the withstand voltage test with the procedures given in section 1 and 2 on page 238. d Check that the ELCB operates when the test button is pressed.
(4) Guide to service life Maintenance and inspection must be conducted according to the environment in which the circuit breaker is installed. The service life of the circuit breaker cannot be determined just by the number of service years. A reference to the service life is given below, but the circuit breaker must be diagnosed by a specialist for an accurate reading. Guide to service life
1
2
Environment
Example
Guide for replacement (years)
Place where air is always clean and dry
Dust-proof and air-conditioned electrical room
Indoors, where there is little dust and no corrosive gas
Circuit-breakers housed in distribution panels or boxes within an individual electric Approx. 7 to 15 room having no dust-proofing or air-conditioning Geothermal power house, sewage treatment plans, iron and steel works, paper and pulp plants, etc.
1
Place with gases such as sulfuric acid, hydrogen sulfide, salt and high levels of moisture, but low levels of dust
2
Place with high levels Chemical plants, of gas and dust which humans cannot endure quarries, mines, etc. for long periods of time
Approx. 10 to 20
Standard
Size of circuit breaker frame (A)
JIS C 8201-2-1 100 or less Ann.2 JIS C 8201-2-2 More than 100, 315 or less Ann.2 JIS C 8201-2-1 Ann.1 More than 315, 630 or less JIS C 8201-2-2 Ann.1 More than 630, 2500 or less IEC 60947-2 (*1) More than 2500
Number of operating cycles (times) No Energization energization Total 8500 10000 1500 1000
7000
8000
1000
4000
5000
500
2500
3000
500
1500
2000
Number of tripping times by shunt tripping device or undervoltage tripping device, or by trip button
10% of total operating cycles
Note *1 The number of trips by the ELCB test button is one-third the number of energizations.
Approx. 3 to 7
Approx. 1 to 3
The operating life shortens as the circuit breaker frame size increases. (Refer to above tables.) These values may seem low, but since this circuit breaker is a protective device, it basically differs from a switch intended for
Handling and Maintenance
Poor environment
Standard usage state
Degree
frequent opening and closing. For tripping by a shunt tripping device, the life is especially short and special consideration should be taken.
WARNING Continuing user of a circuit breaker which has reached its service life can result in the following q w e r
problems. Always update the circuit breakers accordingly. Insulation fault: Risk of burning, internal short-circuit, and electric shock. Energizing fault: Burning or unnecessary operations caused by overheating of the internal parts, etc. Operation fault: ON and OFF operation of the circuit may be disabled. Tripping fault: Protection of the load device or wiring, etc., may be disabled.
CAUTION When the operating endurance exceeds the specified value, the above faults could occur or the internal
conductor could break, overheat or burn.
235
8
8 Handling and Maintenance 5. Troubleshooting
(1) Troubleshooting for breaker unit (MCCB, ELCB) Fault state
Cause
Can’t close
Remove the foreign matter
Breaker hasn’t been reset
Reset again
Operation errors
Breaker can’t be reset Wear due to tripping endurance (*) Can’t reset
Countermeasures and Actions
Foreign matter in switching mechanism See below(*) End of service life
Replace with new part
Reset mechanism is faulty
Improper adjustment
Return for repairs
Undervoltage coil is not excited
Careless operation
Excite the coil Wait for bimetal to cool down
Resetting time has not elapsed
Can’t trip Can’t turn OFF
Broken handle
Switching spring is broken or
Breakage caused by initial trouble Return for repairs
fatigued
End of service life
Broken rated changeover screw
Replace with large capacity breaker
Insufficient lubricant (grease)
Return for repairs
Excessive power during operation
Replace handle
Positional relation of external operation handle and
Replace handle
breaker is poor
Correct positional relation Remove foreign matter (if cover is removable) Return for repairs (if cover is not removable)
Fusion at conductive section
Excessive interrupting current Replace with new part having large interruptive capacity
Excessive wear of contacts
Short-circuit current cut off End of service life Replace with new part
Excessive tightening torque (Tighten with 0.3 to 0.45N·m) Incorrect selection Ambient temperature is high
Operates under normal load
Replace with new part
Contact has fused because of excessive interruptive current
Foreign matter caught between contacts Poor energizing
See below
Excessive use of shunt trip operation Replace with new part. Change shunt trip to electric operation
Excessive temperature rise
(temperature compensation)
Return for repairs Change the selection
Panel is sealed
Ventilate
Loosening at terminal connections
Tighten
Load current contains high levels of high-frequency distortion
Insert a reactor and decrease distortion factor
Measuring instrument is reading small measurement values because of distorted current Correctly specify the rated values by using real meters with effective value
type
Overcurrent Rated current setting value is too low Rated current changeover screw was not tightened indicator LED is ON
Malfunctions when starting
Correctly tighten the rated current changeover screw Tightening torque 0.3 to 0.45N·m
Failure of rated current changeover section
Return for repairs
Heating caused by repeated starting current Incorrect selection
Replace with breaker having higher rating
Long starting time
Replace with breaker having higher rating
Incorrect selection
Starting current is too high
Change the instantaneous setting or replace with breaker having higher rating
Starting rush current is too high
Change the instantaneous setting or replace with breaker having higher rating
Excessive current during delta-star starting changeover
Change the instantaneous setting or replace with breaker
Momentarily functions
Excessive current due to reversible operation
having higher rating
when starting
Rush current during instantaneous restart
Change the instantaneous setting or replace with breaker having higher rating
Rare short-circuit of motor
Repair the motor
Bimetal reset incomplete after instantaneous tripping
Allow to properly reset
Operates during use Short-circuit on power side Terminal temperature is high
Antenna for transceiver (5W or higher) was seated against electronic type MCCB body during transmission
Does not electronic operate No operation type MCCB with tester
236
Use the transformer at least 1m away from the electronic type MCCB Remove the cause or replace with new part
Dust is accumulated Conductive matter has dropped into power side
Remove the cause or replace with new part
Improper tightening
Tighten
Improper maintenance
Complete electromagnetic type being used at a high frequency (400Hz, etc.)
Replace with breaker having suitable frequency
Load current contains high levels of high-frequency distortion
Insert a reactor and decrease distortion factor
Incorrect measurement resulting from touch
Measure with a measuring instrument
Studs are loose
Tighten
Heating at stud tightening
Contact fault between stud conductor and body terminal
Reassemble the stud
section
Groove to reduce overcurrent heating not grooved on rear connection
Mold side temperature is high
type’s steel mounting plate (400A frame and larger)
8
Correct the rated current setting
Abnormal current passed simultaneously with closing (short-circuit closing) Inspect the circuit and remove the cause
Temperature rise
Handling and Maintenance
Annoying operation
Electronic
Selected rated current is too high No tripping at overcurrent
Replace with a breaker having a lower current
Applied frequency is incorrect Backup breaker has tripped
Machine grooves to reduce overcurrent heating
Replace with breaker having suitable frequency Backup breaker’s instantaneous Lower the instantaneous electromagnetic setting tripping current is too low
Raise the electromagnetic setting for the backup breaker, or change the rating
Overcurrent indication LED does not turn ON, or turns ON and then Breaker tester’s battery is spent OFF before specified time
Replace the breaker tester’s battery
Overcurrent indication LED turns ON and then OFF after specified time, but does not trip
Return for repairs
Tripping mechanism is faulty
8 Handling and Maintenance
(2) Troubleshooting for leakage operation section Fault state
Cause
Operates simultaneously with closing Annoying operation
The leakage mechanism operates, such as the leakage indication button pops out
Countermeasures and Actions
The wiring is long creating a large ground electrostatic capacity, and causes a leakage current flow
Change the rated sensitivity current or install the ELCB near the load
ELCB units are being used in parallel, or is incorrectly connected with a neutral wire, etc.
Use the correct wiring
An excessive surge, such as inducted lightning, has infiltrated the unit
Install a surge absorber, etc., near the circuit
Induction noise from a nearby large current bus, etc., has infiltrated the unit
Avoid sources of noise
LED is faulty or is at end of service life
Replace with new part
The indicator button is improperly adjusted and does not protrude
Return for repairs
Electronic circuit section is faulty
Replace with new part
Voltage is not applied
Apply the specified voltage
Contact continuity is faulty
Remove the foreign matter from the contact
Operation errors
Leakage operation occurs when the test button is pressed, etc., but there is not indication
No operation
Operates during use
No operation takes place when the test button is pressed
Remarks: 1. When using a transceiver, use at least 1m away from the electronic MCCB and ELCB.
(3) Troubleshooting for accessories Cause
Fault state Operation power voltage has dropped
NFM NVM (Electric operation device) Continuous idling
One idle run when closing
UVT (Undervoltage tripping device)
Resistor or motor is burned
Operation circuit wire capacity is insufficient
Use a larger operation circuit wire
Operation power capacity is insufficient
Improve the operation power
Excessive continuous operation
Return for repairs (motor replacement)
Connection is incorrect
Use the correct wiring
Applied voltage is incorrect
Apply the correct operation voltage
ON and OFF circuits are operating simultaneously, operation is mistaken
Provide an interlock at the pushbutton
For the self-holding type, the auxiliary switch contact is used for automatic reset
Use the alarm switch contact for the automatic reset contact
Voltage ripping in the OFF state, or tripping caused by undervoltage Breaker itself has automatically cut-off and tripped
Turn OFF once to reset, and then turn ON again
Applied frequency or voltage is incorrect
Improve the power
Doesn’t attract
Improve the voltage
Handling and Maintenance
Operation disabled
Countermeasures and Actions
Closing disabled Doesn’t trip even when voltage is absent
voltage drop is large
Breaker’s tripping mechanism is faulty
Return for repairs
Operation voltage has dropped
Improve the power
Applied voltage is incorrect
Improve the power
Coil is continuously excited
Return for repairs (coil replacement, installation of burn prevention auxiliary coil)
Operation voltage has dropped causing continuous excitation
Return for repairs (coil replacement), improve power
Burn preventing auxiliary contact is faulty
Return for repairs (coil replacement, contact repair)
Abnormal voltage is applied
Return for repairs (coil replacement)
Insufficient voltage
SHT (Shunt tripping device)
Doesn’t trip Coil is burnt
Contact fault caused by overcurrent
AL (Alarm switch) AX (Auxiliary switch) EAL (Earth leakage alarm contact) TBM (Test button module) PAL (Pre-alarm)
8
Return for repairs
Incorrect connection
Connection mistaken during installation
Refer to nameplate and correct the wiring
Microload
Incorrect selection
Return for repairs (replacement with type for microloads)
Loose mounting screws
Insufficient tightening Vibration during transportation
Return for repairs (readjustment)
Malfunction
237
8 Handling and Maintenance (4) Cases of unnecessary ELCB operation Even if the ELCB is not faulty, there may be a problem in the circuit which causes frequent operation or instantaneous operation at closing. Refer to the following section and incorporate it as part of the circuit inspection and troubleshooting.
High voltage
Tr
M
1
2
Induced lightning
Effect of external magnetic field
3
Occurrence of switching surge
5
Large current at starting
4
Ground electrostatic capacity
Grounding
Grounding
The following five conditions are the most conceivable causes of trips in cases such as when the breaker trips immediately after the ELCB is closed, or when the breaker trips suddenly during use but inspection of circuit shows no ground fault accidents. Check each item and if any problems are found, correct them accordingly.
ig
Cause
1 Induction lightning
Countermeasures
All models incorporate a non-operating shock structure and should sufficiently withstand 7kV (JIS Standards), so unnecessary operation should not occur.
The ZCT is equipped with a magnetic shield, and is not affected easily. However, the breaker could operate if there are 2 External magnetic field
large current buses reaching several thousand amperes near the ELCB, or if there is a short-circuit fault in nearby circuit. Separate the ELCB from the large current bus wires by at least 10cm.
All models incorporate a non-operating shock structure and should not operate unnecessarily. However if there is a 3 Switching surge
time lag in the closing time of each pole in the magnetic switch, unnecessary operation could occur due to the
Handling and Maintenance
relation of the ground electrostatic capacity.
If the wires are stored in a metal conduit or metal duct wiring, the ground electrostatic capacity will increase compared to other wiring methods. This may cause the leakage current to constantly increase. If the magnetic switch chatters, etc., the leakage current may become temporarily unbalanced thus reaching a leakage current equivalent to the sensitivity current and causing unnecessary operation. 4 Effect of ground electrostatic capacity
Review the following matters in this case. 1) Shorten the load circuit line, or install the ELCB near the load (device) being used. (Install in a branch circuit.) 2) Lead the control circuit for the control device, etc., from the power on the ELCB side. 3) If the above measures are difficult or if they cause further unnecessary operation, reconsider the selected ELCB rated sensitivity current.
8
The ZCT is made of high-grade permalloy, a material with Ni as its main element and which has outstanding residual magnetic characteristics. The periphery of the ZCT is covered with material having outstanding magnetic 5 Equilibrium properties caused by large current at starting
characteristics, creating a complete magnetic shield. This suppresses the effect of residual currents to the minimum, and prevents the breaker from unnecessarily operating even near a current of several thousand amperes. In the relay, the characteristics change if the primary conductor is bent immediately after it is passed through the ZCT. Thus, when passing a primary conductor with current of 300A or more through the ZCT, keep the conductor straight for at least 30cm on either side.
238
Appendix
9
1) Handle Operation Angle Dimensions… ……………………………………………………………………………………………………… 2) MCCB Trip Button, Instantaneous Adjustment Dial Drilling and Terminal Cover Mounting Hole Dimensions………………………… 3) ELCB Button and Switch Dimensions… ……………………………………………………………………………………………………… 4) List of Product Weights… ……………………………………………………………………………………………………………………… 5) Switching the Adjustable Items………………………………………………………………………………………………………………… 6) Breaker Mounting Screw Dimensions… ……………………………………………………………………………………………………… 7) List of Mold Surface Temperature-rise Values… …………………………………………………………………………………………… 8) Ordering Information… ………………………………………………………………………………………………………………………… 9) Melshort 2………………………………………………………………………………………………………………………………………… 10) Low-Voltage Products Website… ……………………………………………………………………………………………………………
240 241 242 243 244 247 248 249 251 252
239
9 Appendix 1. Handle Operation Angle Dimensions (Line side)
(Line side)
ON Center of handle
Trip
C
c
H
D
a
cL
cL
OFF
G
F
b
d
Center of handle E
Reset
A B
Table of dimension variations Operation angle (° )
Class
Model MCCB, MCB
ELCB, RCCB, RCBO
NF50-SVFU
NV50-SVFU
NF32-SV
NV32-SV
NF63-CV, NF63-SV, NF63-HV
NV63-CV, NV63-SV, NV63-HV
NF125-CV, NF125-SV, NF125-HV
NV125-CV, NV125-SV, NV125-HV
NF100-CVFU, NF125-SVU, NF125-HVU
NV100-CVFU, NV125-SVU, NV125-HVU
ON OFF Trip Reset d c b a
Dimensions (mm) A
B
C
D
E
F
G
H
12
20
4
27
55
90
13
–
8
5
5
14
15
19
5
21
40
90
2
–
12
7
7
17
15
19
5
21
40
92
2
–
12
7
7
19
NF125-SEV, NF125-HEV NF250-CV, NF250-SV, NF250-HV
C•S•H
NF250-SEV, NF250-HEV
NV125-SEV, NV125-HEV
NF250-SGV, NF250-LGV, NF250-HGV
NV250-CV, NV250-SV, NV250-HV
NF125-SGV, NF125-LGV, NF125-HGV
NV250-SVU, NV250-HVU
NF160-SGV, NF160-LGV, NF160-HGV NF250-SVU, NF250-HVU NF30-CS
–
21
29
1
31
47
67
10
–
8.5
4.5
6
13
NF225-CWU
–
12
18
2
21.5
38
92
7.5
–
13.5
7
8
18.5
16.5
10
6.5 14.5
49
134
6.5
–
32.5 14.5 15.5
25
16.5
10
6.5 14.5
49
155
6.5
–
32.5 13.5 15.5
46
16.5
10
6.5 14.5
49
155
6.5
–
32.5 13.5 15.5
46
–
18
12
6
17
84
190
–
4
41.5 13.5
NF125-RGV, NF250-RGV
–
15
19
5
21
40
92
2
–
12
NF125-UV
–
15
19
5
21
40
92
–
29
12
NF250-UV
–
15
19
5
21
40
92
–
35
12
NF400-UEW
–
16.5
10
6.5 14.5 146 252
–
NF400-UEW(4P), NF800-UEW
–
16.5
10
6.5 14.5 146 252
–
BH
–
19
18
5
21
56
77.5
BH-P
–
19
18
–
41
36
21 –
57.5
BH-D6, BH-D10*1
5 –
–
42
48
–
–
41
48
–
NV400-CW
NF400-CW NF400-SW/SEW/HEW/REW NF630-CW/SW/SEW/HEW/REW NF400-SWU/HWU NF800-CEW/SDW/SEW/HEW/REW NF630-SWU/HWU
NV400-SW/SEW/HEW/REW NV630-CW/SW/SEW/HEW NV800-SEW/HEW
NF1000-SEW, NF1250-SEW NF1600-SEW
Appendix
R•U
BH BH-DN*1 KB-D*1
240
36.5
7
7
19
7
7
17
7
7
19
13.5 32.5 13.5 15.5
46
32.5 13.5 15.5
46
5
17 –
9.5
9.5
9.5
13
79
12
–
9.5
9.5
63
76
9
–
–
–
9.5 –
13 –
–
63
76
10
–
–
63
76
9
–
17 –
4 –
9.5 –
12 –
–
BV-D*1
42
40
–
–
61
76
10
–
14
4
–
–
–
BV-DN*1
42
48
–
–
63
76
10
–
17
4
–
–
Note *1 Trip is the same as the OFF position. Resetting is not required.
9
15
9 Appendix
2. MCCB Trip Button, Instantaneous Adjustment Dial Drilling and Terminal Cover Mounting Hole Dimensions fM Prepared hole for terminal cover mounting tapping screw
4-pole 3-pole
L
cL
H fD Trip button
J
G
A B C
F
A B C
G fE Instantaneous adjustment dial
N P
Fig. a
L
4-pole 3-pole K
fD Trip button
cL
fD Trip button
3-fE Instantaneous adjustment dial
H J
H
Fig. c
Fig. b
3-pole 2-pole cL
fM Prepared hole for terminal cover mounting tapping screw
B
Q
B
cL R
A
cL
F
cL
Rated current switch L
Rated current switch
fM Prepared hole for terminal cover mounting tapping screw
K cL
B
4-pole 3-pole K
T S
J H fE Instantaneous adjustment dial
H Rated current switch Tripping characteristics switch
Fig. e
Fig. d
Table of dimension variations Model NF50-SVFU NF32-SV, NF63-CV NF63-SV, NF63-HV NF125-CV, NF125-SV, NF125-HV NF100-CVFU, NF125-SVU, NF125-HVU NF125-UV NF125-SEV, NF125-HEV, NF250-SV, NF250-HV NF125-SGV, NF125-LGV, NF125-HGV NF160-SGV, NF160-LGV, NF160-HGV NF250-SGV, NF250-LGV, NF250-HGV NF250-SVU, NF250-HVU, NF250-UV NF250-SEV, NF250-HEV NF125-RGV NF250-RGV
(mm) Number of poles
2, 3 2 3, 4 2 3, 4 2, 3, 4
Fig. e c a c a a
2, 3, 4 a
3, 4 2, 3 2, 3 2 NF30-CS 3 2, 3 NF225-CWU 2, 3 NF400-CW 2, 3 NF400-SW, NF400-SWU, NF400-HWU 4 3 NF400-SEW, NF400-HEW, NF400-REW 4 3 NF400-UEW 4 2, 3 NF630-CW 2, 3 NF630-SW 4 3 NF630-SEW, NF630-HEW, NF630-REW 4 3 NF800-CEW, NF800-SEW, NF800-HEW, NF800-REW 4 2, 3 NF800-SDW, NF630-SWU, NF630-HWU 4 3 NF800-UEW 4 NF1000-SEW, NF1250-SEW 3 NF1600-SEW 4
a a a b a d d d d d d d d d d d
A – – – – – –
B 14 20 20 20 20 20
C – – – – – –
fD 6.5 6.5 6.5 6.5 6.5 6.5
fE – – – – – –
F – – – – – –
G – – – – – –
H 4 21 29 21 37 37
J – – – – – –
K – – – – – –
L – – – – – –
fM – – – – – –
N – – – – – –
P – – – – – –
Q – – – – – –
R – – – – – –
S – – – – – –
T – – – – – –
–
20
–
6.5
–
–
–
44
–
–
–
–
–
–
–
–
–
–
– – – – – – – – – – – – – – – – – – – – 74 74 – – – –
20 20 20 14.5 14.5 15.5 30.5 30.5 30.5 30.5 30.5 50.5 54 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5 30.5 54 54 70 70
– – – – – – – – – – – – – – – – – – – – – – – – – –
6.5 6.5 6.5 4 4 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6 6
– – – – – – – – – – – – – – – – – – – – 10 10 – – – –
– – – – – – – – – – – – – – – – – – – – – – – – – –
– – – – – – – – – – – – – – – – – – – – – – – – – –
44 44 44 16 27.5 43 51.5 51.5 51.5 51.5 51.5 51.5 78.5 51.5 51.5 51.5 51.5 51.5 78.5 78.5 78.5 78.5 78.5 78.5 56.5 56.5
– – – – – – – – – – – – – – – – – – – – 57 57 – – – –
– – – – – – 125 125 125 125 125 125 156 125 125 125 125 125 86 156 86 156 86 156 199 269
– – – – – – 110.5 110.5 110.5 110.5 110.5 130.5 152 110.5 110.5 110.5 110.5 110.5 128.5 128.5 128.5 128.5 152 152 178.5 178.5
– – – – – – 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4
– – – – – – – – – – – – – – – – – – – – – – – – – –
– – – – – – – – – – – – – – – – – – – – – – – – – –
– – – – – – – – – 53 53 53 76.5 – – – 53 53 53 53 – – 76.5 76.5 130 130
– – – – – – – – – 30 30 30 30 – – – 30 30 30 30 – – 30 30 30 30
– – – – – – – – – 74 74 74 74 – – – 74 74 74 74 – – 74 74 74 74
– – – – – – – – – 63.5 63.5 63.5 98.5 – – – 98.5 98.5 98.5 98.5 – – 98.5 98.5 89 89
Remarks: 1. The 4-pole part is available for the S and H Series 50A frame to 1600A frame (excluding NF400-REW, NF630-REW and NF800-REW). 2. The 2-pole part for NF250-CV and larger is the same as the 3-pole part. (Including NF125-HV.) 3. The terminal cover mounting hole shows the case for the screwed type. The breaker mounting hole is used to mount the one-touch terminal cover. Refer to the respective dimension drawings. 4. The K dimensions are divided down the breaker center.
241
Appendix
fD Trip button
9
9 Appendix 3. ELCB Button and Switch Dimensions K
E
Fig. a
F
fH Test button
D fJ Leakage indicator button
fW trip button
N G
fW trip button
Fig. b
fJ Leakage indicator button
fH Test button E
fH Test button
D F
Fig. d
Selector (time-delay type)
Fig. e
G
F
K
E
E G
Center of breaker handle
fH Test button
fJ Leakage indicator button
D
Fig. c
D
M
N
D
F
fJ Leakage indicator button
M
Y
Y D
fJ Leakage indicator button
N X G
L
Center of breaker
X G F
fH Test button fW trip button
X
fH Test button
Center of breaker
fU Sensitivity current selector fV Operation time selector (time-delay type) fJ Leakage indicator button
E
Sensitivity current selector F EK
M
U Center of breaker
Center of breaker handle
Center of breaker handle
Operation time selector (time-delay type)
Y
T Center of breaker L handle V
L L
Selector (sensitivity)
Fig. f
E
E
Y
F
D
M
fW trip button
D
F
F
E
Center of breaker
fH Test button
Y
Center of breaker handle fJ Leakage indicator button
Center of breaker handle fU Sensitivity current selector fJ Leakage indicator button fH Test button X M Center of breaker K
Center of breaker handle fH Test button fJ Leakage X G indicator button
D
G
fW trip button
Fig. g
G
Fig. i
Fig. h
Model Fixed type NV32-SV NV63-CV, NV63-SV, NV63-HV Selector type Fixed type NV125-CV, NV125-SV, NV125-HV Selector type Time-delay type Fixed type NV250-CV, NV250-SV, NV250-HV Selector type Time-delay type NV400-CW (note2) Fixed type NV400-SW Selector type NV630-CW, NV630-SW Time-delay type NV400-SEW, NV400-HEW Fixed type NV400-REW (note2) Selector type NV630-SEW, NV630-HEW Time-delay type Selector type NV800-SEW, NV800-HEW Time-delay type
Reference drawing
Table of dimension variations Variable dimensions (mm) D Test Indicator button button
a a
3
4
a
E
F
G
H
J
13
8
26.5
9.5
4
13
8
26.5
9.5
4
13
8
34
9.5
4
c
3
3
(2.3)
14.6
43.5
9.5
5
c
3
3
(2.3)
14.6
43.5
9.5
5
c
3
3
(2.3)
14.6
54.1
9.5
5
Appendix
Note *1 Dimensions shown in parentheses apply to minus direction.
9 242
K
L
M
– 16 – 16 16 – 16 16 – 30.6 30.6 – 30.6 30.6 30.6 30.6
– – – – 17 – – 24
– 7 – 7 7 – 7 7 – – 22.6 – – 22.6 – 22.6
43.5
43.5 54.1
N 16 16
23.5
T
U
V
– 23.5 – 24 24 – 31 31
– 3 – 3 3 – 3 3 – 5.5 5.5 – 5.5 5.5 5.5 5.5
– – – – 3 – – 3 – – 5.5 – – 5.5 – 5.5
43.5
–
43.5
–
54.1
–
W
X
Y
6
29
20
6
37
20
6
44
20
6.5
51.5
30.5
6.5
51.5
30.5
6.5
78.5
30.5
9 Appendix
4. List of Product Weights MCCB
(kg) Item
C•S•H•
Model NF32-SV NF63-CV (rated current 50A or less) NF63-CV (rated current 60A, 63A) NF63-SV, NF63-HV (rated current 50A or less) NF63-SV, NF63-HV (rated current 60A, 63A) NF125-CV NF125-SV NF125-HV NF125-SEV NF125-HEV NF250-CV NF250-SV NF250-HV NF250-SEV NF250-HEV NF125-SGV NF125-LGV NF125-HGV NF160-SGV NF160-LGV MB NF160-HGV NF250-SGV NF250-LGV NF250-HGV NF30-CS NF400-CW NF400-SW NF400-SEW/HEW NF400-REW NF630-CW NF630-SW NF630-SEW/HEW NF630-REW NF800-CEW NF800-SDW NF800-SEW/HEW NF800-REW NF1000-SEW, NF1250-SEW NF1600-SEW NF125-RGV NF250-RGV NF125-UV NF250-UV NF400-UEW NF800-UEW BH BH-P BH BH-D6, BH-D10 BH-DN KB-D NF50-SVFU NF100-CVFU NF125-SVU NF125-HVU UL NF250-SVU NF250-HVU NF225-CWU NF400-SWU/HWU NF630-SWU/HWU
Breaker body Rear connection type 1P 2P 3P 4P – 0.8 0.55 – – – 0.8 0.55 – – – 0.85 0.6 – – 1.1 0.85 0.6 –
Front connection type 2P 4P 3P 1P – 0.65 0.45 – –
0.45
0.65
–
–
0.5
0.7
–
R•U
–
0.5
0.7
0.9
–
0.55
0.75
1.0
– – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – 0.15 0.13 0.15 – 0.09 – – – – – – – – –
0.6 0.7 0.6 – – 1.3 1.4 1.4 – – 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 0.25 4.4 4.6 – – 5.2 5.4 – – – 9 – – – – 1.5 1.5 1.35 2.5 – – 0.31 0.26 0.3 0.12 0.18 0.3 0.6 0.7 – – – – – –
1.0 0.95 1.0 1.7 1.7 1.5 1.6 1.6 1.7 1.7 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 0.35 5.0 5.2 6.0 6.0 6.0 6.2 6.5 6.5 10.9 – 10.9 10.9 23.5 34.5 1.8 1.8 1.5 2.7 16.2 27.6 0.47 0.38 0.45 – 0.27 0.45 0.85 0.95 1.0 1.7 1.7 1.5 5.7 9.6
– 1.3 1.2 2.2 2.2 – 2.0 2.0 2.2 2.2 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 – – 6.8 7.6 – – 8.0 8.3 – – – 14.2 – 30.7 41.2 – – 1.9 3.7 25.4 33.7 – – 0.55 – 0.36 – – – – – – – – –
– – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – –
0.8
1.2
–
–
Accessories (weight of only accessories) Operation handle Boxed type S I W F type V type S type 0.6 0.45 0.4 10.2 5.0 1.5
0.8
1.2
–
–
1.5
5.0
10.2
0.4
0.45
0.6
0.17
0.85
1.25
–
–
1.5
5.0
10.2
0.4
0.45
0.6
0.17
Plug-in type (including plug-in frame) Electric operated 2P 3P 4P type
0.17
0.85
1.25
1.5
–
1.5
5.0
10.2
0.4
0.45
0.6
0.17
0.65
0.9
1.2
0.9
1.3
1.6
–
1.5
5.0
10.2
0.4
0.45
0.6
0.17
1.0 1.1 1.0 – – 1.7 1.8 1.8 – – 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 0.35 5.7 5.9 – – 6.5 6.7 – – – 10 – – – – – – – – – – – – – – – – – – – – – – – –
1.5 1.5 1.5 2.2 2.2 2.2 2.3 2.3 2.4 2.4 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 0.5 7.0 7.3 8.1 8.5 7.9 8.1 8.4 8.4 12.1 – 12.1 12.1 23 30 – – – – 18.6 31.2 – – – – – – – – – – – – – –
– 2.0 1.9 2.9 2.9 – 3.0 3.0 3.2 3.2 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 – – 9.7 10.5 – – 10.6 10.9 – – – 15.8 – 30.8 40.7 – – – – 30.7 38.4 – – – – – – – – – – – – – –
1.2 1.3 1.2 – – 3.1 3.2 3.2 – – 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 3.2 – 7.0 7.2 – – 7.6 7.8 – – – – – – – – 2.35 3.2 2.2 4.2 – – – – – – – – – – – – – – – –
1.9 1.9 1.9 2.6 2.6 3.4 3.5 3.5 3.6 3.6 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 – 8.3 8.5 9.3 9.3 9.1 9.3 9.6 9.6 16.3 – 16.3 16.3 26.6 – 2.7 3.6 2.4 4.5 19.8 – – – – – – – – – – – – – – –
– 2.4 2.3 3.3 3.3 – 4.5 4.5 4.7 4.7 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 – – 11.3 12.0 – – 12.0 12.3 – – – 21.4 – 35.5 – – – – – – – – – – – – – – – – – – – – –
1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 –
1.8 1.8 1.8 6.8 6.8 6.8 6.8 – 6.8 – 6.8 – – 6.8 – – 6.8 – – 1.1 – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – –
5.1 5.1 5.1 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 8.7 –
10.2 10.2 10.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 –
0.4 0.4 0.4 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 –
0.45 0.45 0.45 0.55 0.55 0.55 0.55 0.55 0.55 0.55 0.55 0.55 0.55 0.55 0.55 0.55 0.55 0.55 0.55 –
0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 –
0.17 0.17 0.17 0.17 0.17 0.17 0.17 0.17 0.17 0.17 0.17 0.17 0.17 0.17 0.17 0.17 0.17 0.17 0.17 –
19
30 2.0
–
9.0
10 10 1.3 1.3 1.3 1.3 9.0 – – – – – – – – – – – – – –
–
–
33
30
–
–
48
70
– 48 – – – – – – – – – – – – – – – – – – – – –
– 70 – – – – – – – – – – – – – – – – – – – – –
1.9
2.4
–
3.4 3.4 0.5 0.5 0.5 0.5 2.2 2.7 – – – – – 0.3 0.4 0.4 0.4 0.5 0.5 0.5 2.0 2.4
– – 0.55 0.55 0.55 0.55 – – – – – – – 0.35 0.45 0.5 0.5 0.55 0.55 – – –
2.0
0.45
0.6 0.6 0.6 0.6
0.55 0.17 0.17 0.17 0.17
1.9
0.45
– – – – – – – – – – – 0.6 1.9 1.9
– – – – – – – 0.17 0.17 0.17 0.17 0.17 0.45 0.45
ELCB
(kg)
Breaker body Rear connection type 4P 3P 2P − 0.95 −
−
1.35
−
−
Accessories (weight of only accessories) Boxed type Operation handle W I S F type V type S type 10.2 5.0 1.5 0.4 0.45 0.6
0.7
0.75
−
0.8
0.95
−
1.1
1.35
−
−
1.5
5.0
10.2
0.4
0.45
0.6
0.17
0.75
0.8
−
0.85
1.0
−
1.15
1.4
−
−
1.5
5.0
10.2
0.4
0.45
0.6
0.17
−
0.75
−
−
0.95
−
−
1.35
−
−
1.5
5.0
10.2
0.4
0.45
0.6
0.17
−
0.8
−
−
1.0
−
−
1.4
−
−
1.5
5.0
10.2
0.4
0.45
0.6
0.17
− − − − − − − − 0.4 − − − − − − − − − − − − − − 0.2 0.19
1.0 1.1 1.1 1.9 1.9 1.7 1.9 1.8 0.5 0.95 1.1 1.1 1.9 1.9 5.6 5.9 6.6 6.6 6.9 6.9 7.1 7.1 15.3 − −
− 1.4 1.4 2.5 2.5 − 2.5 − − − − − − − − − 8.2 − − − 8.9 − − 0.35 −
− − − − − − − − − − − − − − − − − − − − − − − − −
1.5 1.6 1.6 2.4 2.4 2.4 2.6 2.5 − − − − − − 7.7 8 8.7 8.7 8.8 8.8 9.0 9.0 16.5 − −
− 2.1 2.1 3.2 3.2 − 3.5 − − − − − − − − − 11.4 − − − 11.5 − − − −
− − − − − − − − − − − − − − − − − − − − − − − − −
1.9 2.0 2.0 2.8 2.8 3.6 3.8 3.7 − − − − − − 8.9 9.2 9.9 9.9 10.0 10.0 10.2 10.2 20.7 − −
− 2.5 2.5 3.6 3.6 − 5.0 − − − − − − − − − 12.5 − − − 12.9 − − − −
1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 − − − − − −
1.8 1.8 1.8 6.8 6.8 6.8 6.8 − − − − − − − − − − − −
5.1 5.1 5.1 8.7 8.7 8.7 8.7 8.7 − − − − − −
10.2 10.2 10.5 13.5 13.5 13.5 13.5 13.5 − − − − − −
0.4 0.4 0.4 0.5 0.5 0.5 0.5 0.5 0.3 0.4 0.4 0.4 0.5 0.5
0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 − − − − − −
0.17 0.17 0.17 0.17 0.17 0.17 0.17 0.17 − − 0.17 0.17 0.17 0.17
19
30
2.0
−
−
2.0
0.45 0.45 0.45 0.55 0.55 0.55 0.55 0.55 0.35 0.45 0.5 0.5 0.55 0.55 − − − −
1.9
0.45
−
33
30
− − − −
48 − −
70 − −
− −
− −
Front connection type 4P 3P 2P − 0.75 −
Plug-in type (including plug-in frame) Electric operated 4P 3P 2P type
9.0
− − −
− 2.4
− −
− − − − −
Mechanical interlock (MI)
0.17
243
Appendix
Item Model NV32-SV NV63-CV, NV63-SV (rated current 50A or less) NV63-CV, NV63-SV (rated current 60A, 63A) NV63-HV (rated current 50A or less) NV63-HV (rated current 60A, 63A) NV125-CV NV125-SV NV125-HV NV125-SEV C NV125-HEV NV250-CV • S NV250-SV • NV250-HV H NV50-SVFU • U NV100-CVFU • NV125-SVU UL NV125-HVU NV250-SVU NV250-HVU NV400-CW NV400-SW NV400-SEW/HEW NV400-REW NV630-CW NV630-SW NV630-SEW NV630-HEW NV800-SEW/HEW BV-D BV-DN
Mechanical interlock (MI)
9
9 Appendix 5. Switching the Adjustable Items
Appendix 244
(*1) (*1)
(*1) (*1)
(*2) (*2) (*2) (*2)
Rated voltage
PAL
Notes *1 Available only for models with pre-alarm module. *2 Use the OPERATION CHECK & SETUP UNIT Y-350. Consult Mitsubishi for details. Remarks: Unless otherwise specified, the electronic breaker is adjusted to the following settings as a default. (1) Rated current: maximum value (2) LTD tripping characteristics:maximum value (3) STD tripping characteristics (current, operating time):maximum value (4) Instantaneous tripping characteristics:maximum value (5) PAL:minimum value (6) Rated sensitivity current:maximum value (7) Leakage operation time (for time-delay type):maximum value
9
Rated Operating time (for time-delay type)
(*2) (*2) (*2) (*2)
Instantaneous tripping characteristics
Rated sensitivity
NF125-SEV/HEV NF250-SEV/HEV NF400-SEW/HEW/REW/UEW NF630-SEW/HEW/REW NF800-CEW/SEW/HEW/REW/UEW MCCB NF1000-SEW, NF1250-SEW, NF1600-SEW NF800-SDW, NF630-SWU/HWU NF125-SGV/LGV/HGV NF160-SGV/LGV/HGV NF250-SGV/LGV/HGV NV125-SEV/HEV NV250-SEV/HEV NV400-SEW/HEW/REW NV630-SEW/HEW ELCB NV800-SEW/HEW NV32-SV, NV63-CV/SV/HV NV125-CV/SV/HV NV250-CV/SV/HV NV400-CW/SW, NV630-CW
STD tripping characteristics
Applicable model
LTD tripping characteristics
Adjustable item
Rated current
(1) Adjustable rated current and tripping characteristics items
9 Appendix
(2) Adjusting the rated current and tripping characteristics Item
Electronic type
Application
400 to 1600A frame
125 to 250A frame
Rated current label
Example of selector layout
Trip (PTT) button Replacement label OVER LED (red) 70% LED (green)
OVER LED (red)
Trip (PTT) button
PAL LED (yellow) 70% LED (green) Replacement label
Current setting label Clear cover
Trip characteristics selector
Trip characteristics selector
Overcurrent operation test/ Characteristics setting connector
Rated current (step type)
175 187.5
200 212.5
162.5 150 137.5 125
(A)
Ir
Current setting (step type)
6 225 237.5 5 250 4 3 2
8 10 12
(x250A)
250 300 .7 .8 350 225
14
Ii
Variable current setting (Co variable type)
14 (xIr)
Instantaneous tripping current (step type)
200 TEST
In(A)
3
.5
4 56
STD tripping current
76 8 4 10
8 10
12 14 16
12 Ir(×400A) Is(×In, Ir) Ii(×400A) .9 100 .1 .2 .8 60 150 .3 12 .7 1.0 TL(s) .06 Ts(s) IP(×In, Ir)
Instantaneous tripping current
Pre-alarm current
Turn the handle to OFF before starting the settings. q Set the arrow of each characteristic’s setting dial to the required scale position. Always set the dial arrow within the bold lines of the setting value. If stopped at the middle, the adjacent setting value may be applied. Use a 0.5mm thick flat-tip screwdriver with a 3mm or less tip width. Turn the screwdriver at 0.05N·m or less. w From the replacement labels, select the rated current label with the same value as the setting value. e Replace the rated current label. r Close the cover and tighten the screw.
In case of 125 to 250A frame
Setter and tester
(Application: Electronic (effective value detection) breaker) The following items can be set and tested using the breaker test and setter Y-350. ¡LTD and STD characteristics settings ¡Long-term operation test (variable signal) ¡Short-term operation test (fixed signal) *1 ¡Instantaneous operation test (fixed signal) ¡Pre-alarm operation test (variable signal) *2
*1. Fixed signal which is 1.5 times the STD trip current. *2. Only for models with pre-alarm module.
Turn the handle to OFF before starting the settings. q Open the clear cover. w Set the arrow of each characteristic’s setting dial to the required scale position. For values other than instantaneous tripping current and adjustable current settings, which can be adjusted at any time, always set the dial arrow within the bold lines of the setting value. If stopped at the middle, the adjacent setting value may be applied. Use a 0.6mm thick flat-tip screwdriver with a 4.5mm or less tip width. Turn the screwdriver at 0.05N·m or less. e From the replacement labels, select the rated current label with the same value as the setting value. r Replace the rated current label. t Close the clear cover.
In case of 400 to 1600A frame (Application: Electronic (effective value detection) breaker) The following items can be tested using the tester Y-250. ¡Long-term operation test (variable signal) ¡Short-term operation test (fixed signal) ¡Instantaneous operation test (fixed signal) ¡Pre-alarm operation test (variable signal)
Appendix
Example of making a selection
LTD STD operating time operating time
Y-250
9 245
9 Appendix (3) Selecting the rated voltage, rated sensitivity and operating time Model
Selector layout
Voltage selection
Sensitivity and operation time selection
Operating time selector (time-delay type) Sensitivity selector
Use for the circuit voltage within the rated voltage.
Turn the handle to OFF before changing the selection.
Use for the circuit voltage within the rated voltage.
Turn the handle to OFF before changing the selection.
3-step sensitivity ELCB selector type
Sensitivity selector Operating time selector (time-delay type)
Appendix
View of selection operation
9 246
9 Appendix
6. Breaker Mounting Screw Dimensions j MCCB • MCB Class
Model
C•S•H
NF50-SVFU NF32-SV, NF63-CV, NF63-SV, NF63-HV NF125-CV, NF125-SV, NF125-HV NF100-CVFU, NF125-SVU NF125-HVU NF125-SEV, NF125-HEV NF250-CV, NF250-SV, NF250-HV NF250-SEV, NF250-HEV NF250-SVU, NF250-HVU NF125-SGV, NF125-LGV, NF125-HGV NF160-SGV, NF160-LGV, NF160-HGV NF250-SGV, NF250-LGV, NF250-HGV NF30-CS NF225-CWU
R•U
NF400-CW, NF400-SW NF400-SWU, NF400-HWU NF400-SEW, NF400-HEW, NF400-REW NF630-CW, NF630-SW, NF630-SEW NF630-HEW, NF630-REW NF800-CEW, NF800-SEW NF800-HEW, NF800-REW NF630-SWU, NF630-HWU NF1000-SEW, NF1250-SEW NF1600-SEW NF125-RGV NF250-RGV NF125-UV, NF250-UV NF125-UV (4P), NF250-UV (4P) NF400-UEW (3P) NF400-UEW (4P), NF800-UEW BH BH-P BH-D6 BH BH-DN KB-D BH-D10
Hole depth A 56
Wood screw Front Rear connection (round wood screw) type for front connection connection type – M4×0.7×65 (note) –
Plug-in type
Required quantity per unit
–
1P –
2P 2
3P 2
4P –
2
2
4
2
4
2 2
2
–
2
4
45
4.1×58
M4×0.7×55
M4×0.7×55
M4×0.7×55
–
45
4.1×58
M4×0.7×55
M4×0.7×55
M4×0.7×55 M4×0.7×73
–
10
4.1×25
M4×0.7×20
M4×0.7×20
–
–
45
4.1×58
M4×0.7×55
–
–
–
47
–
M6×60
M6×72
M6×72
–
4
4
4
59
–
M6×72
M6×85
M6×85
–
4
4
4
15
–
M6×35
M6×40
M6×35
–
4
4
4
18.5 18.5
– –
M8×40 M8×40
M8×40 M8×40
M8×40 –
– –
4 4
4 4
4 4
45
–
M4×0.7×55
M4×0.7×55
M4×0.7×55
–
2
2
–
45/61 45 47/156 15/112 – – – – – –
– – – – – – – – – –
M4×0.7×55/73 M4×0.7×55 M6×65/174 M6×35/132 – – – – – –
M4×0.7×55/73 M4×0.7×55 M6×72/181 M6×40/137 – – – – – –
M4×0.7×55/73 M4×0.7×55 M6×72/181 M6×35/132 – – – – – –
– – – – – – – – – –
4 2 – – – – – – – –
4 2 4 4 – – – – – –
– 4 – 6 – – – – – –
2 For plug-in type 4
For plug-in type 4
Remarks: 1. The mounting shown in the sections are enclosed with the MCCB. The mounting screws for the plug-in connection are enclosed with the plug-in terminal block. All other mounting screws must be prepared by the user. 2. All mounting screws other than the hexagon socket bolts and hexagon bolts are P-type panhead screws. 3. For models with two types of mounting screws, the screw length differs on the supply side and load side. Hole depth 4. The plug-in type is not available for NF800-UEW. A Note For the P-type panhead screw, use a type with a spring washer and flat washer (small round) combination, or a P-type panhead screw with spring washer and flat washer.
j ELCB • RCCB • RCBO Model
NV50-SVFU NV32-SV, NV63-CV, NV63-SV, NV63-HV NV125-CV, NV125-SV, NV125-HV NV100-CVFU, NV125-SVU, NV125-HVU NV125-SEV, NV125-HEV NV250-CV, NV250-SV, NV250-HV NV NV250-SEV, NV250-HEV, NV250-SVU, NV250-HVU NV400-CW, NV400-SW NV400-SEW, NV400-HEW, NV400-REW NV630-CW, NV630-SW, NV630-SEW NV630-HEW NV800-SEW, NV800-HEW BV-D BV BV-DN
Hole depth A 56
Wood screw Screw for steel plates (P-type panhead screw) (round wood screw) for front connection Front connection type Rear connection type Plug-in type – – – M4×0.7×65 (note)
Required quantity per unit 2, 3P 4P 2 –
45
4.1×58
M4×0.7×55
M4×0.7×55
M4×0.7×55
2
45
4.1×58
M4×0.7×55
M4×0.7×55
M4×0.7×55 M4×0.7×73
For plug-in type 4
47
–
M6×60
M6×72
M6×72
4
4
59
–
M6×72
M6×85
M6×85
4
4
15 – –
– – –
M6×35 – –
M6×40 – –
M6×35 – –
4 – –
4 – –
2
4
4
Remarks: 1. The mounting shown in the sections are enclosed with the ELCB. Note For the P-type panhead screw, use a type with a spring washer and flat washer (small round) combination, or a P-type panhead screw with spring washer and flat washer.
Appendix
Class
9 247
9 Appendix 7. List of Mold Surface Temperature-rise Values C
B A
j MCCB
(K)
(K)
Measurement point
Model
Conducting current Cover surface Base side (A) (B)
Measurement point
Handle (C)
Line terminal
Load terminal
Model
Handle (C)
Line terminal
Load terminal
NF32-SV
32A
14
38
12
36
37
NF400-CW
400A
16
25
16
47
37
NF63-CV
63A
15
42
14
39
44
NF400-SW
400A
20
27
10
46
37
NF63-SV
63A
15
39
12
41
44
NF400-SEW
400A
14
22
9
35
31
NF63-HV
63A
15
42
12
41
49
NF400-HEW
400A
14
23
8
34
32
NF125-CV
125A
13
29
9
43
42
NF400-REW
400A
15
23
9
35
32
NF125-SV
125A
14
32
10
44
40
NF400-UEW
400A
19
28
13
42
33
NF125-HV
125A
16
33
11
49
42
NF630-CW
630A
23
32
15
52
52
NF250-CV
250A
19
35
13
46
45
NF630-SW
630A
23
33
16
54
52
NF250-SV
250A
20
36
13
47
45
NF630-SEW
630A
22
31
14
51
45
NF250-HV
250A
20
36
13
49
46
NF630-HEW
630A
20
31
13
50
44
NF30-CS
30A
18
15
5
23
33
NF630-REW
630A
21
31
13
51
44
NF125-SGV
125A
20
35
13
42
49
NF800-CEW
800A
21
30
13
45
40
NF250-SGV
250A
20
36
13
49
50
NF800-SDW
800A
18
28
12
46
44
NF160-SGV
160A
20
35
13
40
44
NF800-SEW
800A
21
30
12
45
41
NF800-HEW
800A
22
31
12
47
42
NF800-REW
800A
21
30
13
46
42
NF800-UEW
800A
25
35
16
51
46
j ELCB
(K)
(K)
Measurement point
Model
Appendix
Conducting current Cover surface Base side (A) (B)
Conducting current Cover surface Base side (A) (B)
Measurement point
Handle (C)
Line terminal
Load terminal
Model
Conducting current Cover surface Base side (A) (B)
Handle (C)
Line terminal
Load terminal
NV32-SV
32A
15
35
11
36
41
NV400-CW
400A
22
32
11
46
41
NV63-CV
63A
17
32
13
43
41
NV400-SW
400A
23
32
12
47
42
NV63-SV
63A
17
37
13
45
47
NV400-SEW
400A
16
23
10
36
34
NV63-HV
63A
17
35
13
43
43
NV400-HEW
400A
15
22
11
35
35
NV125-CV
125A
13
30
13
47
43
NV400-REW
400A
15
22
10
36
35
NV125-SV
125A
14
30
15
45
43
NV630-CW
630A
24
34
17
54
52
NV125-HV
125A
14
32
14
42
43
NV630-SW
630A
23
33
16
53
53
NV250-CV
250A
21
37
14
43
44
NV630-SEW
630A
23
34
17
54
53
NV250-SV
250A
21
39
18
47
43
NV630-HEW
630A
22
33
17
54
52
NV250-HV
250A
23
38
17
48
43
NV800-SEW
800A
29
40
13
53
46
Notes *1 The connected wire size follows JIS C 8201 Ann.2 Standards. The temperature rise value will vary according to the size of the connected wire. *2 This table shows the temperature-rise values. The ambient temperature must be added for the actual measurement value. *3 These are examples of the measurement values, and are not guaranteed values. Use these as reference data.
9 248
9 Appendix
8. Ordering Information Molded Case Circuit Breakers Model
NF250-SV
NF
Earth Leakage Circuit Breakers
C
Economy class
S
Standard class
H
High-performance class
U
Ultra current-limiting class
Model
NV250-SV
Number of poles
Number of poles 2P, 3P, 4P
3P
200A Motor protection
MB Rated voltage
Economy class
S
Standard class
H
High-performance class
U
Ultra current-limiting class
DSN-type switches
DSN
Rated current
NV
C
3P
Please specify the rated current even for rated current adjustable types
Please specify MB for Motor Protection Breakers
Please specify DC voltage for use in DC circuit
Rated current
200A Motor protection
MB
2P
NV
1ø2W
3P
NV
1ø2W 1ø3W 3ø3W
4P
NV
3ø4W
Please specify the rated current even for rated current adjustable types
Please specify MB for Motor Protection Breakers
Rated voltage AC
AC
100-440V 200-440V
Please specify applicable marine standard
Rated sensitivity current
100 / 200 / 500mA Connection method
B Built-in accessories
PAL Internal accessories
AL, SHT (110VAC) External accessories
Special-purpose breakers
Quantity
F
Front connection
SL
Solderless (box) terminal
B
Rear connection
PM
Plug-in
PAL
Pre-alarm (contact output)
AL
Alarm switch
AX
Auxiliary switch
SHT
Shunt trip (specify rated coil voltage)
UVT
Undervoltage trip (specify rated coil voltage)
SLT
Lead-wire terminal block
MD
Electrical operation device
F/S/ V
Operating handle
S/I/ W
Enclosure box
MI
Mechanical interlock
TC
Terminal cover (TC-L, TC-S, TTC, BTC)
LC / HL HL-S CH
10
Card holder
Mag Only
DC400V
DC use (specify 400, 440, 500, 550 or 600VDC)
400Hz
B
F
Front connection
SL
Solderless (box) terminal
B
Rear connection
PM
Plug-in
Type of residual current protection
Blank
High-speed type
Specify
Time-delay type
Built-in accessories
MG
Insulation switch
EAL
Earth-leakage circuit alarm switch
TBM
Test button module
PAL
Pre-alarm module
MG Internal accessories
AL
Alarm switch
AX
Auxiliary switch
AX, SLT, TBM
UVT
Undervoltage trip (specify rated coil voltage)
SLT
Lead-wire terminal block
MD
Electrical operation device
External accessories
F/S/ V
Handle lock device
Mag Only (specify AC or DC and rated current)
Low-inst
Connection method
30mA 100 / 200 / 500mA
Quantity
10
Operating handle
MI
Mechanical interlock
TC
Terminal cover (TC-L, TC-S, TTC, BTC)
LC / HL HL-S CH
Appendix
Standard
Handle lock device Card holder
9
400Hz use Low-inst (specify AC or DC and Inst. %)
249
9 Appendix d Circuit Protector (CP30-BA) Model CP30-BA
Internal circuit 1
Number of poles 1P 1
1P
Operating characteristics M
Inline type
Inline type with auxiliary switch (general load) type with auxiliary 21 * Inline switch (microload) (Note 2)
2
2P 3P (Note 1)
6
Relay type shunt tripping
Inline type with alarm switch (general load) * Inline type with auxiliary 91 switch (microload) (Note 2)
9
I M MD S SD F
Rated current or rated operational voltage 3A
Instantaneous type Medium-speed type Medium-speed type with inertial delay (Note 1) Low-speed type Low-speed type with inertial delay (Note 1) High-speed type
Rated operational voltage (for shunt tripping) 100-200V 100-200VAC and 100VDC common 24-48V 24-48VDC common
0.1A 0.25A 0.3A 0.5A 1A
2A
3A
7A
10A
15A 20A
Connection method
No symbol Screw terminal
5A
T
Metal tab terminal
30A Shaded parts are standard inventory.
Notes *1 3-pole and inertial delay models are dedicated for AC. *2 If an auxiliary switch (AX) or alarm switch (AL) used for a 125VAC 0.5A or less circuit is required, select the microload type indicated with an asterisk*. *3 The relay type shunt trip is subject to CCC. This is a UL (cURus) and CE Marking As a standard, this product is a UL (cURus), compliant product. Example 1. CP30-BA 1P 1-M 3A (example of inline type, medium-speed, 1-pole part, 3A, screw CCC, CE Marking compliant product. terminal specifications)
Mandatory items are indicated with a bold box. Always specify these items.
Unless specified, all other items will be manufactured with standard Mitsubishi specifications.
d UL 489 Listed Molded Case Circuit Breakers Model
Number of poles
Rated current
Connection method
Internal accessories
Number of units
NF250-SVU
3P
200A
F
AL, SHT(AC100-240V)
10 units
2P 3P
F Crimp terminal SL Solderless terminal BAR Bar terminal
AL Alarm switch AX Auxiliary switch Shunt tripping device SHT (Designate rated voltage for coil) Undervoltage tripping device UVT (Designate rated voltage for coil) Vertical lead-wire SLT terminal block * When ordering two, designate as AL2 or AX2. For the microload type, designate AL-B or AX-B.
External accessories
F•V•S•C Operation handle MI Mechanical interlock Terminal cover TC (TC-L(*), TC-S) HL•HL-S Handle lock * For the 30 to 250A frame 2-pole or 3-pole TC-L, the specifications will be set according to the rated current.
d UL 489 Listed Earth Leakage Circuit Breakers Model
Number of poles
Rated current
Rated voltage
Rated sensitivity current
Connection method
Internal accessories
Number of units
NV250-SVU
3P
200A
AC120-480V
100 • 300 • 500mA
F
AX, SLT
10 units
AC240V AC120-240V AC120-480V
30 50 100 100 • 200 • 500mA 100 • 300 • 500mA
F Crimp terminal SL Solderless terminal BAR Bar terminal
Appendix
2P 3P
9 250
AL Alarm switch AX Auxiliary switch Shunt tripping device SHT (Designate rated voltage for coil) Undervoltage tripping device UVT (Designate rated voltage for coil) Vertical lead-wire SLT terminal block * When ordering two, designate as AL2 or AX2. For the microload type, designate AL-B or AX-B.
External accessories
F•V•S•C Operation handle MI Mechanical interlock Terminal cover TC (TC-L (*), TC-S) HL•HL-S Handle lock * For the 30 to 250A frame 2-pole or 3-pole TC-L, the specifications will be set according to the rated current.
9 Appendix
9. Melshort 2 A Smarter, Easier Way to Select Breakers
This software program ensures the easy selection of low-voltage circuit breakers according to the required rated breaking capacity and related equipment.
Calculation and selection software for low-voltage circuit breakers
Preparation of single-line diagram
Coodination between high-voltage protection equipments
Short-circuit current calculation
Examination of cascade interruption combination
Examination of selective interraption
Advantages The program's menu allows not only short-circuit current calculations, but also the examination of various protection coordination. ●Preparation of single-line connection diagrams. ●Short-circuit calculations. ●Automatic selection of breaker type. ●Selection of breaker type for cascade interruption combination. ●Selection of breaker type for selective interruption combination. ●Examination of coordination between high-voltage protection
equipment. coordination with motor start current.
●Selection Efficiency Improved Simple, accurate and fast operation is ensured as a result of being able to examine the coordination between various protection systems, and being able to select breakers interactively on the screen.
●Software Updates Users can download the latest software updates by accessing Mitsubishi's LVS home page.
Appendix
●Contents
http://www.fukuyama.melco.co.jp/lvs
●Protection
■Products Menu
■Computer Requirements
Low-voltage circuit breakers: MCCBs, ELCBs, ACBs, MCBs, Contactors, Thermal relays, High-voltage OCRs
Operating system: Windows 95/98/NT4.0/2000/XP CPU : 166 MHz or faster RAM memory size: min 32 MB Free hard disk capacity: min 50 MB Display resolution: min 640 x 480 dots CD-ROM Drive:2x or higher
9 251
9 Appendix 10. Low Voltage Products Website
Appendix
WS-V Series Next-generation MCCB and ELCB, AE-SW Series ACB, DIN Series MCB
9 252
9 Appendix
Molded Case Earth Leakage
Appendix
UL 489 Listed Circuit Breakers
9 253
Low Voltage Circuit Breakers Corporation Name Mitsubishi Electric Australia Pty. Ltd. PROGRESSIVE TRADING CORPORATION Bangladesh ELECTRO MECH AUTOMATION& ENGINEERING LTD. Belarus Tehnikon Belgium Koning & Hartman B.V. Cambodia DHINIMEX CO.,LTD Chile Rhona S.A. Mitsubishi Electric Automation (China) Ltd. Mitsubishi Electric Automation (China) Ltd. BeiJing Branch Mitsubishi Electric Automation (China) Ltd. ShenZhen Branch China Mitsubishi Electric Automation (China) Ltd. GuangZhou Branch Mitsubishi Electric Automation (China) Ltd. ChengDu Branch Mitsubishi Electric Automation (Hong Kong) Ltd. Proelectrico Representaciones S.A. Colombia AUTOCONT CONTROL SYSTEMS S.R.O Czech Republic BEIJER ELECTRONICS A/S Denmark Cairo Electrical Group Egypt Mitsubishi Electric Europe B.V. France Mitsubishi Electric Europe B.V. Germany KALAMARAKIS - SAPOUNAS S.A. Greece UTECO Meltrade Ltd. Hungary Mitsubishi Electric India Private Limited India P. T. Sahabat Indonesia Indonesia Mitsubishi Electric Europe B.V. Ireland Gino Industries Ltd. Israel Mitsubishi Electric Europe B.V. Italy Kazpromavtomatika Kazakhstan Mitsubishi Electric Automation Korea Co., Ltd Korea Laos AROUNKIT CORPORATION IMPORT- EXPORT SOLE CO.,LTD Lebanon Comptoir d'Electricite Generale-Liban Lithuania Rifas UAB Malaysia Mittric Sdn Bhd Malta ALFATRADE LTD Maroco SCHIELE MAROC Myanmar Peace Myanmar Electric Co.,Ltd. Nepal Watt&Volt House Netherlands Imtech Marine & Offshore B.V. North America Mitsubishi Electric Automation, Inc. Norway Scanelec AS Middle East Comptoir d'Electricite Generale-InternationalArab Countries & Cyprus S.A.L. Country / Region Australia
Pakistan Philippines Poland Republic of Moldova Romania Russia Saudi Arabia Singapore Slovakia Slovenia South Africa Spain Sweden Switzerland Taiwan Thailand Tunisia Turkey United Kingdom Uruguay Venezuela Vietnam
Prince Electric Co.
Address 348 Victoria Road, Rydalmere, N.S.W. 2116, Australia Haque Tower, 2nd floor, 610/11,Jubilee Road, Chittagong, Bangladesh Purana Paltan Lane, (VIP Road), Rokeya Mansion(6th floor), Room#702,Dhaka-1000, Bangladesh Oktyabrskaya 19, Off. 705, BY-220030 Minsk, Belarus Woluwelaan 31, BE-1800 Vilvoorde, Belgium #245, St. Tep Phan, Phnom Penh, Cambodia Vte. Agua Santa 4211 Casilla 30-D (P.O. Box) Vina del Mar, Chile Mitsubishi Electric Automation Building, No.1386 Hongqiao Road, Shanghai, 200336 9/F, Office Tower1 Henderson Centre 18 Jianguomennei Dajie DongCheng district BeiJing 100005 Room 2512--2516, Great China International Exchange Square, Jintian Rd.S., Futian District, Shenzhen, 518034 Room 1609, North Tower, The Hub Center, No.1068, Xing Gang East Road, Haizhu District, Guang Zhou, China 510335 Block B, Room 407-408, Shangri-La Center Offeice Builiding, No.9 BinJiang East Road, Chengdu, China 610021 20/F., Cityplaza One, 111 king's Road, Taikoo shing, Hong Kong Carrera 42 # 75-367 Bod 109 Itagui Colombia Technologická 374/6, CZ-708 00 Ostrava - Pustkovec LYKKEGARDSVEJ 17, DK-4000 ROSKILDE 9, Rostoum St. Garden City P.O. Box 165-11516 Maglis El-Shaab, Cairo - Egypt 25, Boulevard des Bouvets, F-92741 Nanterre Cedex Gothaer Str. 8, 40880 Ratingen , Germany IONIAS & NEROMILOU STR., CHAMOMILOS ACHARNES, ATHENS, 13678 Greece 5, MAVROGENOUS STR., 18542 PIRAEUS, Greece Fertö utca 14. HU-1107 Budapest, Hungary 2nd Floor, Tower A&B, Cyber Greens, DLF Cyber City, DLF Phase-III, Gurgaon - 122 022 Haryana, India P.O.Box 5045 Kawasan Industri Pergudangan, Jakarta, Indonesia Westgate Business Park, Ballymount, IRL-Dublin 24, Ireland 26, Ophir Street IL-32235 Haifa, Israel Viale Colleoni 7, I-20041 Agrate Brianza (MI), Italy ul. Zhambyla 28, KAZ - 100017 Karaganda 9F Gangseo Hangang xi-tower, 401 Yangcheon-ro, Gangseo-gu, Seoul 07528 Korea SAPHANMO VILLAGE. SAYSETHA DISTRICT, VIENTIANE CAPITAL, LAOS Cebaco Center - Block A Autostrade Dora, P.O. Box 11-2597 Beirut - Lebanon Tinklu 29A, LT-5300 Panevezys, Lithuania No. 5 Jalan Pemberita U1/49, Temasya Industrial Park, Glenmarie 40150 Shah Alam, Selangor, Malaysia 99 PAOLA HILL, PAOLA PLA 1702, Malta KM 7,2 NOUVELLE ROUTE DE RABAT AIN SEBAA, 20600 Casablanca, Maroco NO137/139 Botahtaung Pagoda Road, Botahtaung Town Ship 11161, Yangon, Myanmar KHA 2-65, Volt House Dillibazar Post Box: 2108, Kathmandu, Nepal Sluisjesdijk 155, NL-3087 AG Rotterdam, Netherlands 500 Corporate Woods Parkway, Vernon Hills, IL 60061 USA Leirvikasen 43B, NO-5179 Godvik, Norway Cebaco Center - Block A Autostrade Dora P.O. Box 11-1314 Beirut - Lebanon 2-P, GULBERG II, LAHORE - 54660 PAKISTAN
AL-KAMAL GROUP Edison Electric Integrated, Inc. Mitsubishi Electric Europe B.V. Polish Branch Intehsis SRL Sirius Trading & Services SRL Mitsubishi Electric Europe B.V. Moscow Branch Center of Electrical Goods Mitsubishi Electric Asia Pte. Ltd. PROCONT, Presov SIMAP Inea RBT d.o.o. CBI-electric: low voltage Mitsubishi Electric Europe B.V. Spanish Branch Euro Energy Components AB TriElec AG Setsuyo Enterprise Co., Ltd United Trading & Import Co., Ltd. MOTRA Electric
Office No. 7 & 8, 1st Floor, Barkat Ali Khan Center, 101 Circular Road, Lahore. Pakistan 24th Fl. Galleria Corporate Center, Edsa Cr. Ortigas Ave., Quezon City Metro Manila, Philippines Krakowska 50, 32-083 Balice, Poland bld. Traian 23/1, MD-2060 Kishinev, Moldova RO-060841 Bucuresti, Sector 6 Aleea Lacul Morii Nr. 3 52, bld. 3 Kosmodamianskaya Nab. 115054, Moscow, Russia Al-Shuwayer St. Side way of Salahuddin Al-Ayoubi St. P.O. Box 15955 Riyadh 11454 - Saudi Arabia 307 Alexandra Road, Mitsubishi Electric Building, Singapore 159943 Kupelna 1/, SK - 08001 Presov, Slovakia Jana Derku 1671, SK - 91101 Trencin, Slovakia Stegne 11, SI-1000 Ljubljana, Slovenia Private Bag 2016, ZA-1600 Isando Gauteng, South Africa Carretera de Rubí 76-80, E-08190 Sant Cugat del Vallés (Barcelona), Spain Järnvägsgatan 36, S-434 24 Kungsbacka, Sweden Muehlentalstrasse 136, CH-8201 Schaffhausen 5th Fl., No.105, Wu Kung 3rd, Wu-Ku Hsiang, Taipei, Taiwan, R.O.C. 77/12 Bamrungmuang Road, Klong Mahanak Pomprab Bangkok Thailand 3, Résidence Imen, Avenue des Martyrs Mourouj III, 2074 - El Mourouj III Ben Arous, Tunisia Bayraktar Bulvarı Nutuk Sok. No:5, Posta Kutusu34384, GTS TR-34775 Yukan Dudullu-Uemraniye, Istanbul, Turkey Mitsubishi Electric Europe B.V. Travellers Lane, UK-Hatfield, Herts. AL10 8XB, United Kingdom Fierro Vignoli S.A. Avda. Uruguay 1274 Montevideo Uruguay Adesco S.A. Calle 7 La Urbina Edificio Los Robles Locales C y D Planta Baja, Caracas - Venezuela Mitsubishi Electric Vietnam Co., Ltd. Head Office Unit01-04, 10th Floor, Vincom Center, 72 Le Thanh Ton Street, District 1, Ho Chi Minh City, Vietnam Mitsubishi Electric Vietnam Co., Ltd. Hanoi Branch 6th Floor, Detech Tower, 8 Ton That Thuyet Street, My Dinh 2 Ward, Nam Tu Liem District, Hanoi City, Vietnam
Telephone +61-2-9684-7777 +880-31-624-307 +880-28-321-791 +375(0)17/210 46 26 +32(0)2/2570240 +855-23-997-725 +56-32-2-320-600 +86-21-2322-3030 +86-10-6518-8830 +86-755-2399-8272 +86-20-8923-6730 +86-28-8446-8030 +852-2510-0555 +57-4-4441284 +420 595 691 150 +45(0)46/75 76 66 +20-2-27961337 +33(0)1/55 68 55 68 +49(0) 2102 486-0 +30-2102 406000 +30-211-1206-900 +36(0)1-431-9726 +91-124-4630300 +62-(0)21-6610651-9 +353(0)1-4198800 +972(0)4-867-0656 +39 039-60531 +7-7212-501000 +82-2-3660-9572 +856-20-415899 +961-1-240445 +370(0)45-582-728 +603-5569-3748 +356(0)21-697-816 +212 661 45 15 96 +95-(0)1-202589 +977-1-4411330 +31(0)10-487-19 11 +847-478-2100 +47(0)55-506000 +961-1-240430 +92-(0)42-35752323 +92-(0)42-35753373 +92-(0)42-37631632 +63-(0)2-634-8691 +48(0)12 630 47 00 +373(0)22-66-4242 +40-(0)21-430-40-06 +7 495 721-2070 +966-1-4770149 +65-6473-2308 +421(0)51-7580 611 + 421(0)32 743 04 72 +386(0)1-513-8116 +27-(0)11-9282000 +34(0)93-565-3131 +46(0)300-690040 +41-(0)52-6258425 +886-(0)2-2298-8889 +66-223-4220-3 +216-71 474 599 +90(0)216 526 3990 +44(0)1707-276100 +598-2-902-0808 +58-212-241-9952 +84-8-3910-5945 +84-4-3937-8075
For Safety : Please read the instruction manual carefully before using the products in this catalog.
Wiring and connection must be done by the person have a specialized knowledge of electric construction and wiring.
Y-0720C 1609 printed in Japan oIPp