Compliance sheet for UPVC Pipe compare to HDPE Contractor SECTION Project Part/sec 2. 2.10 2.1.1

2.1.2

2.1.3

2.1.4

2.1.5

2.1.6

2.1.7

SAPAC 23 SDMS -01 MV DUCT Required standard Technical requirements Geberal The hdpe ducts shall be compatible with the latest installation standards and operation and maintenance for telecom. Duct Any alternative proposal for type and acceptance testing will be subject to technical evaluation by sec in regards to compliance the material and quality

Hdpe pipe supply in different size like 100m/300m/500m/1000m Main , mini and micro The hdpe pipe supplied in two form empty and buil;t wioth sub-duct since it is flexible so it can be supplied in roll The hdpe ducts shall have inner and outer surfaces that are clean and free from grooves, cracks, blisters, shrink holes or any other defects or foreign matters, which might impair the performance of the ducts in service. The hdpe ducts shall be acceptably rounded. They shall be supplied with its ends neat, smooth and cut cleanly at right angles or perpendicular to the axis of the ducts. The hdpe ducts shall be highly resistant to all kinds of corrosive liquids, aggressive

Material

Remarks

Taco upvc duct as per saso standard which comply din 8061/8062 class iii and class iv which is comply for electrical and telecom Taco upvc is manufactured as per saso 14/15 and din 8061/8062 which comply astm d 1784 cell Clasification of 12454 with following properties Tensile strength >48.3 mpa Modulas of elasticity >3585 Impact resistance > 39.52 j/m Deflection tempreature under load of 1.82mpa >100 degree centigrade Taco 14/15 upvc duct class iv has a minimum outside diameter 25 mm and 40 mm for class iii Taco upvc pipe as standard saso 14/15 are rigid and emply supplied in unit length 6m standard length and it is easy in instalation Taco standard saso 14/15 upvc duct as homogenous and free from grooves, cracks, blisters, shrink holes or any other defects or foreign matters, which might impair the performance of the ducts in service. Taco upvc duct are acceptable which 5% roundness as per saso 14/15 and din 8061/8062 supplied with its ends neat smooth and cut clearly ate and right angles perpendicular to the duct exis

Comply as per noted

Din 580, plastics piping systems — unplasticized poly(vinyl chloride) (pvc-u) pipes — test method for

Comply as per Noted

Comply as per Noted

Comply as per Noted Comply as per Noted

Comply as per Noted

Comply as per Noted

2.1.8

2.1.9

2.1.10

2.1.11 2.1.12

2.2 2.2.1

2.2.1.3 2.2.1.4

media and chemicals usually found in the ground. The hdpe ducts shall have no requirement for end load restraint for fusion weld system. The hdpe ducts shall be light weight, flexible and shall contain correct type of carbon black protection against ultra violet (uv) degradation. The hdpe ducts and its accessories shall be unaffected by all kinds of corrosive liquids and other compounds which exist in the underground system. All material used in the hdpe ducts shall be non-toxic and dermatologically safe The manufacturer shall be iso certified in accordance with the iso9000:2008 for quality management system. Design requirment

The resistance to dichloromethane at a specified temperature (dcmt) Taco upvc duct not required for fusion weld .they used solvent joint socket as per din 8063 The upvc pipe has a specific gravity of 1.42 g/cm3 rigid type upvc and has correct carbon protection however it is not applicable to insall to direct to sun.

Non comply

Upvc duct fittings fabrication from the same duct material that comply with saso 14/15 and din 8061/8062 and socket bend are comply with din 8063

Comply as per Noted

Upvc duct are toxicity since it comply with saso 14/15 and din 8061/8062 and used to approved on portable water Taco quality management is iso 9001:2015 certify by sgs

Comply Comply

Equivalent

Od tolerances , ± 0.5 percent (maximum) of nominal values. Color code: Ducts with od from 50mm to 20 mm shall be black in color with 4 green equally spaced stripes of sufficient width and color intensity to be easily distinguished from a distance of 3 meters and from any angle.

Taco upvc duct has an od tolerance that comply with saso 14/15 and din 8061/8062 Taco upvc duct standard color is in grey . Other color also made but it is a subtential requirement Standard length 6 meter

Supply lengths 300m . 600m , 900m, 1200m ,unless otherwise requested

2.2.2 2.2.2.1

Non comply

Hdpe duplex micro duct Material : High density polyethylene (hdpe), as specified in clause

Comply Comply as per Noted

Non Comply

Taco upvc pipe materials is comply as per astm d 1784 standard

Comply as per Noted

2.2.2.2

2.2.2.3 2.2.2.4 2.2.2.5 2.2.2.6 2.2.4 2.2.4.1 2.2.4.2

2.2.5 2.2.5.1

2.2.5.2 2.2.5.3

2.2.6

Dimension : Two (duplex) of 14mm micro-ducts inside an hdpe jacket. • outside cross-sectional diameter Wall thickness: 1.5 mm, for 14 mm micro-duct as well as for outer jacket. Od tolerances: ± 0.5 percent (maximum) of nominal values. Color code: • outer jacket: black with two green stripes. • 14mm micro-ducts: Supply lengths: 300, 600, 900 and 1200 m, unless otherwise requested or agreed. Wall designs Outer wall Shall be smooth and free from defects. Inner wall: Shall be with low coefficient of friction can be either Smooth, permanently lubricated co-extruded layer or Longitudinally ribbed with: • smooth-wall: the internal surface shall be smooth. • ribbed-wall: ribs shall be rounded and shall not protrude into the bore by more than 0.4 mm. Other design criteria

By other

By Other

Taco micro duct wall thickness 1.2 for 16 mm micro duct ,outer jacket by other

Comply as per Noted

Taco upvc duct has an od tolerance that comply with saso 14/15 and din 8061/8062 Taco upvc duct standard color is in grey other color will be consider if it is substential requirement Standard length 6m

Comply as per Noted Comply as per Noted

Taco upvc duct outer wall or surface are homogeneous and free from non conformity Taco upvc duct has low co efficiant of friction which is similar to hdpe pipes

Comply as per Noted Comply

Ribbed wall by outer

By Other

Bending : Maximum permissible bend radius 30 times od in Temperature 20 c. Cutting : Can be cut using either a specialized cutter, or a sharp knife or a metal or woodworking saw. Labeling : The following information shall be clearly marked on the duct at the intervals of 1 meter throughout the whole length of the duct. The marking shall be durable, clear and distinct to the naked eye from a minimum distance of 50cm. • example : sec - hdpe- sdr 17- 110/100 - mfr. Name • the meter sequential length marking. Hdpe duct accessory

Noted

Noted

Taco upvc pipe ( duct ) cut by using cutting tool machine

Comply

Taco upvc duct has an indelible mark with 1 meter internal for whole length marking are every visible in naked eye in the distance of 1 meter

Comply as per Noted

Comply as per Noted

Taco upvc has smooth internal and external mwll

Upvc duct has marking for belpw following mfr name , pn ,duct dia ,wt lot number duct standard etc.

2.2.6.1

2.2.6.2

2.2.6.3

2.3.1

2.3.1.1

2.3.2 2.3.2.1

2.3.2.2

2.3.2.3

2.3.2.4

Hdpe duct jointing : • all of joint fittings must be compliant to astm f 2176. • the hdpe duct can be joint using the mechanical or any equivalent technique such as fusion method. • the mechanical joint fitting is installed by pushing the back nut, spring follower and rubber ring on to the plain pipe end, and then inserting into the socket of the filling. The back nut is then tightened by hand. • no special machine required to install the fitting as shown in appendix 3. Hdpe duct sealing plug : Used for sealing the duct ends before cable installation, prevents ingress of dirt, water, moisture, insects etc. As shown in appendix 3. Hdpe duct 90ᶱc bend : Long sweep 90° bend is used for routing of conduits around corners and for the interfacing between the duct and the base of a cabinet or termination boxes as shown in

Taco duct fabricated fittings are comply with din 8063 standard with solvent type bell joint

By other

Taco upvc fabricated duct long sweep 90 ᶱ as per din 8063 can be fabricated as per required in appendix 4

Comply as per Noted

By other

Comply as per Noted

Material properties and test requirements The hdpe ducts shall meet all the material properties and test requirements as specified in astm f2160 Primary properties Identified by astm d3350 with Minimum cell classification Astm f2160 Material primary properties

Upvc duct material

Primary properties are identify by astm d 1784 with cell clasification 121454

Non Compliance

Density (compound) 0.941 to 0.955 g / cc (cell 3 or 4 as per astm d3350) Astm d 792 Melt flow index at 190 C/ْ2.16 kg < 0.15 g/10min (cell 4 as per Astm d3350) Astm d 1238 e Flexural modulas 552 - < 1103 mpa (cell 4 or 5 as per astm d3350). Astm d 790 Tensile strength 21 - <24 mpa ( cell 4 as per astm d3350 )

Density of compound 1.4 g/cm3 as per saso 1395 as per astm d 792 method

Non Compliance

Upvc has a flow index @ 190ᶱc/21.6 kg 1.4 to 54 g/10min as per astm 1238

Non Compliance

87.5 mpa as per astm 790

Non Compliance

Upvc duct has a tensile strength of 48.3 mpa as per astm d 638

Compy

Non Compliance

Primary properties are identify by astm d 1784 with cell clasification 121454

2.3.2.5

2.3.2.6

2.3.2.7

2.3.2.8 2.3.3 2.3.3.1 2.3.3.2 2.3.3.3

Astm d 638 Slow crack growth Resistance (10% igepal) F20 >600 hours escr per astm d 1693 condition c; or >10 hours per astm f 1473 pent. (cell 4 as per astm d3350) Astm d 1693 astm 1473 Hydrostatic design basis Not pressure rated (cell 0 as per Astm d3350) Astm d 2837 Color and uv resistance C–black with 2% min. Carbon Black. E- colored with uv stabilizer Note that carbon black content, 2.25 ± 0.25 % as per astm d1603 Astm d 3350 Other All values at 23 c unless specified Physical properties Induction temp ( dsc ) 220 ᶱ c at astm d 3350 Poisson ratio 0.45 Izod impact ( notch )

No data

No Data

Upvc pipe has a design basic as per saso 14/15 & din 8061/8062

Non Compliance

Within 0.15 % min of carbon black and with a uv stabilizer 0.28 %

Non Compliance

Upvc duct value under 23 ᶱc

Comply

0.38

comply

Izod impact ( notch ) >0.75 ft.ib/in stm 0.256

Non Compliance

Co-efficiant of friction 150 factor as per 150 as per hazen william Ovality ± tolerance of normal diameter as per saso 14/15

Comply as per noted Comply

Tensile strength 5mm/min >48.3 mpa as per astm d 638 >25 mpa

Comply

638>10-15 %

Non Compliance

Hardness > 80 shore “d” astm 2240 -40ᶱ c

Comply Non Compliance

>2.5 ft.ib/in astm d 256

2.3.3.4 2.3.3.5

2.3.4 2.3.4.1 2.3.4.2 2.3.4.3

2.3.4.4 2.3.5 2.3.5.1

Co-efficiant of friction ≤ 0.15 telcordia gr-256 Ovality ( prior to bundling Or coiling) % ovality =[(odmax – odmin) / (odmax +odmin)] <5 % astm d 2160 Mechanical properties Tensile strength (break) (50mm/min) 38 mpa astm d 638 Tensile strength (yield) (50mm/min) 25 mpa astm d 638 Elongation at break (ultimate) >600 % astm d 638 Hardness > 60 shore “d” astm 2240 Thermal properties Brittle temperature <-100 ᶱ c as per astm d 748

Comply

2.3.5.2 2.3.5.3

2.3.5.4 2.3.5.5 2.3.5.6 2.3.6 2.3.6.1

Vicat softening temp 127 ᶱ c astm d 1525 Co-efficient of linear Thermal expansion 0.2 mm/m ᶱ c Specific heat 2.7 -2.9 kj/kgᶱ c Thermal conductivity 0.38 w/m ᶱ c Pn grade 10 ( max pressure 10 bar ) Chemical properties Chemical resistance Resistant to hydrous solutions of acids, alkalis and salts as well as to a large number of organic solvents. Din 8075 Supplement 1 iso/tr 10358

81 ᶱ c as per din 53455 64.79 µm/m =6.479 x 10-5 m/m at 23 ᶱ c 60 ᶱ c as per astm d 648

Non Compliance Comply as noted

Thermal conductivity 0.13 kcal/cm-h ᶱ c as per din 52612 class iv with pn 10

Comply as noted

comply Taco upvc duct are comply with sulphuric acid test ,alkali test , extrusion quality test ( methylene chloride resistance ) as per saso 14/15 din 8061/8062 & saso 1395 as well as resistance to most of the chemical