Superconductor In D-statcom

  • November 2019
  • PDF

This document was uploaded by user and they confirmed that they have the permission to share it. If you are author or own the copyright of this book, please report to us by using this DMCA report form. Report DMCA


Overview

Download & View Superconductor In D-statcom as PDF for free.

More details

  • Words: 744
  • Pages: 15
“T&D Technologies to support the Growth of Wind Power” Bud Kehrli American Superconductor Corporation

1

Wind Generation in the USA

2

Hurdles to the Future Growth of Wind Power • • • •

Regulatory Uncertainty – PTC, State RPS Economics of Wind Generation Negative Impacts on Utility Grid Meeting Interconnection Requirements

3

Wind Generation Impacts on the T&D Grid • High VAR consumption (induction machines) • Voltage fluctuations • Inability to regulate voltage • Tripping off due to low or high voltage • Voltage sags and flicker • Harmonics

4

Joint NERC/ FERC Interconnection Standards for Wind Energy (Dec 2005) FERC Order 661A Provisions: • Power Factor of +/- 95% at the point of interconnection • Voltage regulation capability • Low Voltage Ride Through (LVRT) capability to prevent tripping of wind turbines during voltage sag events

5

Options to address these standards • Add capability within the wind generator turbine itself (GE, Vestas, Enercon…) • Add reactive compensation equipment at the collector bus level (DVAR STATCOM, capacitors, reactors) • Add a combination of improved turbine capability plus equipment at the collector bus • Add equipment at the HV point of common coupling (Large STATCOM or SVC) 6

A Solution at the Collector Bus has many Advantages • Less expensive for larger wind installations • Provides full voltage regulation capability even when wind plant is not generating • Solution is modular and expandable

7

D-VAR® Basics What are D-VAR® Devices? •

Power Electronics (IGBT) based technology available from American Superconductor



Dynamic VARs… Fully Integrated air cooled STATCOM with ability to deliver 2.67 times its continuous current (2 sec)



Instantaneously injects precise amounts of reactive power into a network



Can be seamlessly integrated with static shunt devices as part of a larger solution

D-VAR mitigates wide variety of voltage and power quality related transmission problems 8

S. Australia - Wind Interconnection Requirements • Deliver +/-93% PF at 132 kV bus at full generation • Half of PF correction capability shall be dynamic • Regulate transmission system voltage • Avoid tripping wind farm for nearby transmission grid faults and high voltage (LVRT, HVRT) Requirements can be met primarily by installing dynamic and static reactive resources 9

South Australia Wind Farm DVAR reactive compensation system 132 kV PT

T1

T2

60/125 MVA 132-33 kV

60/125 MVA 132-33 kV

33 kV

N.O.

VBU

VBM

New LBII 120 MW

4 MVA

4 MVA

4 MVA Control

DVAR Master 10 Control

2x13.5 MVAR Cap Banks

Control

Control

V90 P.F. Control

V90 P.F. Control

1x13.5 MVAR 1x13.5 MVAR “fast” Cap Bank Cap Bank

VBM

4 MVA

New LBII 39 MW

Breakers

4 MVA

Existing LBI 80 MW

Voltage Monitoring

Breakers

Control

4 MVA

33 kV

D-VAR® Voltage Regulation at 68 MW Wind Farm Summerview 31 Jan 05 24 Hour Sample VRMS Avg

MVAR Avg

Volts (PU)

7 6

1.03

5 4

1.02

3

MVAR Output (PU)

8

1.04

2

1.01

1 0

1.00 1

61

121

181

241

301

361

421

481

541

601

661

721

Minutes

Wind Farm Voltage Regulation Parameters • Voltage target is 102.5 PU +/-0.5% Bucking an 8 MVA inverter • D-VAR® system has

11

781

841

minutes

Impact of Voltage Sag on Wind Farm without Ride-Through Capability 1. Fault on utility transmission grid. 2. Transmission system voltage drops rapidly.

5. Voltage returns to normal, but, no generation remains on-line.

3. Wind generation trips off-line because voltage is below 0.75 pu at generator terminals for 5 cycles.

4. Fault clears in 600 ms.

12

Impact of voltage sag on wind farm with D-VAR ride-through capability 1. Fault on utility transmission grid 2. Transmission system voltage drops rapidly.

5. Voltages return to normal with generation on-line.

3. D-VAR detects low voltage and injects reactive energy to quickly rebuild voltage at the wind generator above 0.75 pu threshold

Generation rides through the fault! No tripping of generation occurs.

4. Fault clears in 600 ms.

13

Conclusions • Wind Power is a rapidly growing energy resource • Grid/Wind farm related impacts are growing as well • Equipment is currently available to solve problems at the wind farm/grid interface and to support the future growth of Wind Power • Interconnection requirements (power factor, voltage regulation, HVRT and LVRT) can be met with a combination of dynamic (FACTS) devices, static reactive devices and turbine improvements

14

Thank You! Questions? Bud Kehrli Transmission & Distribution Planning American Superconductor Company 8401 Murphy Drive Middleton, WI 53562 USA Phone 608-828-9178 Email [email protected]

15

Related Documents

Superconductor
October 2019 1
Superconductor In D-statcom
November 2019 1
In
November 2019 54
In
November 2019 53