Interposing CT Connections in 3-ph Tr
CT1 Yyo
Yyo
dy11
IPCT1
IPCT2
Differential Relay
Yyo
CT2 Yyo
Yd1
Programmed By: Eng.Mohammad Al-Fayoumi
Rating MVA 75
Up to 85MVA
Tr Connection yd1 400/1
I1
Voltage KV 132 33
328.04
1500/1
0.820
INTERPOSING IPCT to identify phase shift TRANSFORMER
IPCT to identify phase shift
0.820
Differential Relay
C.B Status
Not Trip
The Differential Relay Settings " with 2 biased input" I1
I2
0.820
0.875
F.T.P 0.2
S.T.P 0.6
Ibias 0.85
C/C 20%Slope C.B Status Not Trip F.T.P S.T.P
First Turning Point Second Turning Point
Standards CT's 200/1 200 300/1 300 400/1 400 500/1 500 800/1 800 1200/1 1200 1500/1 1500
I2 1312.16
0.875
IPCT to identify phase shift
0.875
th 2 biased input" IN 1
Programmed By: Eng.Mohammad Al-Fayoumi
CT Ratio 800 /1
IR IY IB IN
800.00
R Y
800 -400-692.820323027551i -425+736.121593216773i Err:502
800.00 O\C Red Relay Setting
B 850.00
Iline
Isetting
800
1
T.M.S 0.25
1 O\C Blue Relay Setting IN Err:502
1.06
Iline
Isetting
850
1
T.M.S 0.25
E\F Relay Setting
Earth Fault
Over Current
Over Current
IN
Isetting
Err:502
0.1
T.M.S 0.2
S.E\F Relay Setting
Err:502 Err:502 Err:502
Trip 28.85 sec
Not-Trip Not operate
IN
Isetting
Err:502
0.03
C.B Status Time
T.M.S 6
Programmed By: Eng.Mohammad Al-Fayoumi
-400-692.820323027551i -425+736.121593216773i Err:502
C\C si
C\C si
C\C si
C\C Dt
Programmed By: ng.Mohammad Al-Fayoumi
Bus A
Rated Voltage KV 120 800 /1
1.88
132000 /110 100.00
Distance Relay
Time
Trip on Z3 0.8 sec
Fault Locate (Km) 84.25
(Ang) 78
Current (Abs) 1500
Current (Ang) 40
Line Length Km 100
Line Resistance 0.09 Ω/Km Line Reactance 0.39 Ω/Km
Line Impedance 8.998+38.975i
Distance Relay Settings Zsetting Zone T.M.S Z1 32 ins Z2 48 0.4 Z3 60 0.8
Bus B
elay Settings C\C ins Dt Dt
Programmed By: Eng.Mohammad Al-Fayoumi