SECTION 207C – Buildings MWFRS (Envelope Procedure) Part 2: Enclosed Simple Low-Rise Buildings #4. Determine the design wind loads for the concrete three story house below. Location: Bulacan Exposure C in all directions Roof slope: 30°
9m
25m 12m
SECTION 207C – Buildings MWFRS (Envelope Procedure) Part 2: Enclosed Simple Low-Rise Buildings #4. Determine the design wind loads for the three story house below. 1.
Mean roof height h = 10.732m
2.
Enclosure Classification, Enclosed
3.
Approximate natural frequency
na 43.5 / h
0.9
43.5 /10.372
Sec 207A.10 Eq. 207A.9-3 0.9
5.30 Hz
Building is Rigid 4.
Occupancy IV
Table 103-1
5.
Basic Wind Speed, V = 260 kph
Figure 207A.5-1A
7.
Exposure Category : Exposure B
8.
Topographic Factor, Kzt = 1.00
Sec 207A.8
9.
Adjustment Factor, λ=1.4433
Figure 207C.6-1
SECTION 207C – Buildings MWFRS (Envelope Procedure) Part 2: Enclosed Simple Low-Rise Buildings #4. Determine the design wind loads for the three story house below. 10.
Design pressure at h=9m and Exposure B, Ps30 or Ps9
Figure 207C.6-1
Ps30/Ps9
Basic Wind Speed (kph)
Roof Anlge (degrees)
250
30
260
30
300
30
Zones Load Case
Horizontal Pressures
Vertical Pressures
Overhangs
A
B
C
D
E
F
G
H
EOH
GOH
1
2.06
1.41
1.64
1.13
0.16
-1.25
0.05
-1.07 -0.72 -0.83
2
2.06
1.41
1.64
1.13
0.79
-0.62
0.68
-0.44 -0.72 -0.83
1
2.24
1.53
1.78
1.23
0.17
-1.4
0.06
-1.2
-0.8
-0.9
2
2.24
1.53
1.78
1.23
0.86
-0.7
0.74
-0.5
-0.8
-0.9
1
2.97
2.03
2.36
1.62
0.23
-1.80
0.08
-1.55 -1.04 -1.19
2
2.97
2.03
2.36
1.62
1.14
-0.89
0.99
-0.63 -1.04 -1.19
SECTION 207C – Buildings MWFRS (Envelope Procedure) Part 2: Enclosed Simple Low-Rise Buildings #4. Determine the design wind loads for the three story house below. 11.
Simplified design pressure, Ps
Equation 207C.6-1
ps K zt pS 30 Zones Load Case
Horizontal Pressures A
1 2
B
C
D
Vertical Pressures
Overhan gs
E
EOH
F
G
H
GO H
Ps30/Ps9
2.24 1.53 1.78 1.23 0.17 -1.40 0.06 -1.20 -0.80 -0.90
Ps
3.23 2.21 2.57 1.78 0.25 -2.02 0.09 -1.73 -1.15 -1.30
Ps30/Ps9
2.24 1.53 1.78 1.23 0.86 -0.70 0.74 -0.50 -0.80 -0.90
Ps
3.23 2.21 2.57 1.78 1.24 -1.01 1.07 -0.72 -1.15 -1.30
SECTION 207C – Buildings MWFRS (Envelope Procedure) Part 2: Enclosed Simple Low-Rise Buildings #4. Determine the design wind loads for the three story house below.
LOAD CASE 1
SECTION 207C – Buildings MWFRS (Envelope Procedure) Part 2: Enclosed Simple Low-Rise Buildings #4. Determine the design wind loads for the three story house below.
LOAD CASE 2