G3500 GENERATOR SET

ENGINE PERFORMANCE CATERPILLAR ENGINE DIVISION

JANUARY 2000

Contents Performance Book Users Guide ................................. 2 Basic Engine and Common Performance Information ..................................... 2 Jacket water Pump Curves ............................ 2 Aftercooler Pump Curves .............................. 2 Block Resistance Curves ................................ 2 Caterpillar Gas Engine Performance Sheets ............................................................... 2 Engine Configuration ..................................... 2 Engine Specific Rating Information ..................... 3 Light Engine Loading ..................................... 3 Engine Rating .................................................. 4 Engine Data ..................................................... 4 Engine Emissions Data .................................. 4 Engine Heat Balance Data ............................. 5 Heat Rejection Tolerances ............................. 6 Engine Noise Data .......................................... 6 Fuel Usage Guide ........................................... 6 Altitude Deration Factors ............................... 7 Actual Engine Rating Calculation ................. 7 Aftercooler Heat Rejection Factors ............... 7 Rating Conditions and Definitions ....................... 7 Gas Engine Performance Book Parameters DM5900-00 ......................................... 8 Parameters DM5901-00 ......................................... 9 G3500 Generator Set Engine Arrangement Index.............................................................................. 10 Engine Performance Data- English Units ................ 13 Jacket Water System Performance ................... 15 Auxiliary Water System Performance ............... 21 Gas Generator Set Engine Performance G3516 Generator Set Engines ..................... 26 G3512 Generator Set Engines ..................... 92 G3508 Generator Set Engines ................... 176 Engine Performance Data- Metric Units ............... 193 Jacket Water System Performance ................. 195 Auxiliary Water System Performance ............. 201 Gas Generator Set Engine Performance G3516 Generator Set Engines ................... 206 G3512 Generator Set Engines ................... 238 G3508 Generator Set Engines ................... 352 This data contained herewith can be used for preliminary design. Before design is finalized, all data should be confirmed by your Caterpillar® dealer. Materials and specifications are subject to change without notice. The International System of Units (SI) are used in this publication. 1

Performance Book Users Guide

This gas engine performance book, sometimes referred to as the "Blue Book", is designed to provide performance data for Caterpillar G3500 industrial engines listed on the Gas Engine Supported Rating List as of the date of this publication. There are three sections to the book. This first section defines the data that will be displayed in the book. The second section of the book displays data for all of the supported ratings published in English units. The third section of the book displays data for the same supported ratings in Metric units. Each set of engine performance data is to be used with either Gas Engine Performance Parameter sheet DM5900-00 (pg. 8) or DM5901-00 (pg. 9). Refer to the second page of each performance data sheet for reference to the proper parameter sheet.

Basic Engine and Common Performance Information The first sets of data are those data sets that are generic to most G3500 series engines. Those data sets include Jacket Water Pump Curves, Aftercooler Pump Curves, and Block Resistance Curves.

Jacket Water Pump Curves The jacket water pump curve, also known as the "jacket water system performance" curve, are supplied for G3508, G3512, and G3516 engine models. There are curves for both low and high speed ranges (1000 or 1200 rpm and 1500 or 1800 rpm). This curve takes into account pressure losses due to restrictions in the engine cooling system. The external resistance lines on the chart refer to the system resistance outside of the engine introduced from the piping and heat rejection equipment used on site. The system resistance must be known to properly calculate the expected water flow from the jacket water pump.

Aftercooler Pump Curves Aftercooler pump curves, also known as "auxiliary water system performance" curves, are supplied for the G3508, G3512 and G3516 engines. There are curves for both low and high speed ranges (1000 or 1200 rpm and 1500 or 1800 rpm). The external resistance lines on the chart refer to the system resistance outside of the engine introduced from the piping and heat rejection equipment used on site. The system resistance must be known to properly calculate the expected water flow from the aftercooler water pump.

2

Block Resistance Curves The block resistance curves are necessary to size a customer supplied jacket water pump for use in separate circuit cooling applications. Separate circuit cooling, or a jacket water only circuit, is commonly used in both low and high temperature cogeneration applications. The block resistance curve shows the pressure drop across the cylinder block as a function of jacket water flow. This resistance data is for the block only, and does not include the resistance of an oil cooler, thermostats or a jacket water pump. The chart also shows a range of water flow. The proper water flow design calculations and cooling system sizing information can be found in the Caterpillar "Gas Engine Application and Installation Guide" (LEKQ2368).

Caterpillar Gas Engine Performance Sheets The data in the next two portions of the gas engine performance book is presented in nine general areas of interest. They are: Engine Configuration, Engine Rating, Engine Data, Engine Emissions Data, Engine Heat Balance Data, Engine Noise Data, Fuel Usage Guide, Altitude Deration Factors and Aftercooler Heat Rejection Factors. Unless otherwise noted, all data was taken using natural gas with a lower heating value of 36.2 mJ/N•m3 (920 Btu/cu ft). Data is shown at 100%, 75% and 50% engine load levels. What follows are instructions on how to understand and apply the performance information contained in these sections of this book.

Engine Configuration The first block of information on the performance data sheet defines the engine configuration for which the data applies. It defines the Engine Speed (in rpm), Compression Ratio, Jacket Water Outlet Temperature, Aftercooler Inlet Temperature, Ignition System type, Exhaust Manifold type and Combustion type. It also lists the primary Fuel the engine rating is designed to use, the Minimum Fuel Pressure and Minimum Methane Number required to achieve the Rated Power. The rated altitude and ambient temperature are noted as well. Ignition System will be listed as "EIS" (Electronic Ignition System), "DIS" ((Cat) Digital Ignition System) or "MAG" (Magneto) type ignition system. Exhaust Manifold will either be listed as dry "DRY" or "WATER COOLED". Combustion system type will be listed as "LOW EMISSION", "STANDARD" or "CATALYST" (stoichiometric).

Performance Book Users Guide

Fuel will be listed as "NAT GAS" for "pipeline" natural gas (methane) with methane numbers between 67 and 100, "LANDFILL" for low energy fuels with a methane number greater than 130, and "PROPANE" for propane fuel with a 34 methane number. Fuel System will be listed as "HPG IMPCO" (high pressure gas with an Impco carburetor, "LPG IMPCO" (low pressure gas with an Impco carburetor), or "LPG DELTEC" (low pressure gas with a Woodward/Deltec carburetor). There are times when an air-fuel ratio control will be required to meet the emissions levels shown on the performance sheet at all load points. When this is the case, the words “with air-fuel ratio control” will appear on the line directly below fuel system. This information, along with the title block at the top of the page, denotes the engine model and its intended application. It must be consistent with the engine to which the data is being applied. Note: The data displayed in this book represents a gas engine used in an industrial power application. The actual data may vary due to site specific rating and operating conditions. Contact your local Caterpillar dealer for site specific performance information.

Engine Specific Rating Information The engine without fan rating at standard conditions is displayed here at 100%, 75% and 50% load levels.

Light Engine Loading Gas engines are designed to operate continuously at industry accepted high ratings and provide optimum service life. Unfortunately, an engine cannot be designed to operate efficiently at both continuous full load levels and at low loads. For example, engines operating at full load are designed to consume some oil in order to fully lubricate the engine and maintain good wear characteristics. This same engine operating at low load factors and the resulting lower cylinder and negative intake manifold pressures will result in more oil consumption than at high load factor. Since most engines are designed to operate at maximum loads, it is not recommended to operate an engine continuously at low load levels. A general rule used for most gas engines is that standard emission engines should be operated at 75% of their rated load (torque) or above while low emission engines should be operated at 50% load (torque) or above.

Engines operating with light loads will be operating with a negative intake manifold pressure. This negative manifold pressure tends to draw excessive oil down the valve guides and past the rings, leading to increased oil consumption. The lighter the load, and the longer the duration of the light load, the more oil an engine should be expected to consume over a given period of time. Longer periods of light loading could lead to carbon buildup on the valves, spark plugs, and behind the piston rings. Deposits in the cylinders can also develop, and in extreme cases, cylinder liner polishing can occur. Carbon build-up can result in power losses, poor performance and accelerated wear of components causing decreased times between maintenance intervals and increased maintenance costs. Gas engine duty (load) cycles expected on an engine will vary from one application to another. Some applications expect cyclical daily load changes. These load fluctuations are often tied to production schedules or shift changes. Engines in these applications may operate at or near rated load most of the day while operating at part load during the night. Engines in these cyclical demand applications rarely will see full load for long periods of time. Depending on the duration of the low load on the engines, engines in these applications may expect to operate for many years without deviating from the normal maintenance schedule and practices. Other application duty cycles may be tied to seasonal power demands or relatively short periods of planned light loads. Light engine loads experienced in these applications may be below recommended levels for periods up to a year. For these applications, modifying some operating parameters may enhance a lightly loaded engine performance. Ignition will be improved under light loads by setting the spark plug gap slightly wider than normal and by retarding the ignition timing. Retarding the ignition timing will also increase the intake manifold pressure. Adjusting the carburetor power screw to a leaner setting can also increase intake manifold pressure. Changes to these parameters will enhance engine light load performance and may bring oil consumption to acceptable levels, but it might also impact the engine’s full load performance capabilities. Excessive engine adjustment may not allow satisfactory load acceptance or higher load operation without further engine adjustment.

3

Performance Book Users Guide

Natural gas engines can be operated at light loads for limited periods of time with no harmful effects. Table 1 lists engine low load operating intervals that are known to be safe operating intervals. After operation at the lower load levels, operate the engine for a minimum of two hours at a load level that is more than 70 percent of the engine rated load. The increased engine load raises the cylinder temperature and pressure, cleaning the deposits from the combustion chamber. Operating the engine at lighter loads for periods longer than those listed may increase oil consumption and overall maintenance costs. Valve and guide seals designed to reduce oil flow down the valve guides, decrease oil consumption and restore engine performance and maintenance intervals should be considered if a customer’s light load is expected to regularly exceed the hour guidelines displayed in table below. The following table is provided to define the recommended hours of continuous light load operation that can be tolerated at a given load. Recommended Gas Engine Low Load Operation Intervals Engine Load (Torque)

G3300, G3400, G3500

G3600

0-30%

NA 1/2 hour

TA 1/2 hour

TA 1/2 hour*

31-40%

2 hour

2 hour

2 hour*

41-50%

8 hour

8 hour

2 hour*

51-60%

24 hour

Continuous

Continuous

61-100%

Continuous

Continuous

Continuous

* When a G3600 series engine operating at load levels below 51%, it is not operating in auto air/fuel ratio control. Submit a light load profile to your local dealer for evaluation and system adjustment recommendations.

Engine Data This section provides specific fuel consumption information, turbocharger compressor outlet pressure and temperature, intake manifold pressure and temperature, and timing information. This section also provides information about the mass and volume flows of the intake air and exhaust gases. Use this data when sizing intake air and ventilation systems, fuel piping, and exhaust equipment.

Engine Emissions Data The information in the Engine Emissions Data section displays emission values for nitrous oxides (NOx as NO2) carbon monoxide (CO), total hydrocarbons (THC), non-methane hydrocarbons (NMHC), and exhaust oxygen. There is also a value for lambda, a calculated comparison of the air and fuel ratios. There are large tolerances, (± 20%) in the total hydrocarbons, non-methane hydrocarbons and carbon monoxide data. This large tolerance is made necessary due to engine-to-engine variability and tolerances designed into the measurement instrumentation. Because of these large tolerances, and the market need to guarantee engine emission levels, the data listed for THC, NMHC, and CO on low emission engines has an additional 20% added to the nominal measured data. The resulting value represents a "not to exceed" emission levels. Though the actual emission levels of an engine are probably closer to the measured (mean) levels, the additional 20% provides the necessary safety factor to allow this value to be a "not to exceed" emission level. The NOx data has tolerances built into the displayed value, and is a "not to exceed" value as well, but it is not listed at the high side of the tolerance band. There is enough adjustment range in the engine to set the NOx to a specific value despite the engine-to-engine variability. Data in the Caterpillar on-line technical marketing information system (TMI) includes the same tolerances listed here. The emission data from either source will be used by the factory to calculate guaranteed emission levels for a given set of specific site conditions. It is important to understand the trends depicted by this data, particularly for low emission engines applied to areas where emissions are closely watched. On engines without automatic air-fuel ratio control, the emission levels are not constant over the entire load range. The specific emissions tend to become higher on a g/bkW-hr (g/bhp-hr) basis as the load decreases. If an engine will be consistently running at a point less than full load, the engine air-fuel ratio can be adjusted so that the O2% in the exhaust is set for the required emission levels at the less than rated load level. The number represented by the term "lambda" is a comparison of the air-fuel ratio as the engine is actually set to the air-fuel ratio at a stoichiometric setting. The actual equation for lambda is: Lambda = air/fuel ratio (actual) / air/fuel ratio (stoichiometric)

4

Performance Book Users Guide

If the lambda of an engine is about 1.1 or below, the engine is considered to be a "rich burn", or "stoichiometric" ("Stoich") engine. (An engine operating at a lambda of 1 is an engine operating at a theoretically perfect air-fuel ratio, where all of the fuel and oxygen in the air is consumed in the combustion process). An engine with a 3-way catalyst will typically operate with a lambda of between 1 and 1.1. Engines with a lambda of about 1.4 or higher are considered to be "lean burn", or "low emission" engines.

5.

“Heat Rejection to Lube Oil" is the amount of heat rejected from the lube oil to the cooling media in the oil cooler. Depending on the cooling system design used, this heat will need to be dissipated in the jacket water cooling system, the aftercooler cooling system or will need to be cooled as a separate circuit. If the heat rejected to lube oil is zero ("0") or not listed, the lube oil heat is included in the heat rejected to jacket water value. If the heat rejected to lube oil is a value greater than zero (0), then this heat needs rejected. If the lube oil heat is to be rejected to the aftercooler circuit, add this heat value to the "Heat Rejection to Aftercooler" value.

6.

"Total Heat Rejection to Exhaust (to 25°C (77°F))" is the total heat available in the exhaust when it is cooled from the stack temperature down to standard conditions of 25°C (77°F). When expressed in Higher Heating Value (HHV), it includes the latent heat of vaporization. At standard conditions, 465 kJ (970 Btu) are released as each Kg (pound) of steam is condensed to water. The figures shown for total exhaust are in terms of low heat value and, therefore, do not include the heat of vaporization.

7.

"Heat Rejection to Exhaust (LHV to 350°F (177°C) for engines in English units or 120°C (250°F) for engines in metric units)" is not a separate component of the heat balance equation. It is a part of the "Total Heat Rejection to Exhaust (to 25°C (77°F))". It represents the easily recoverable exhaust heat rejection value typically used in exhaust heat recovery calculations. This value is the heat available when cooling the exhaust gas from the stack temperature down to the listed temperature. This figure, plus the jacket water heat rejection, is commonly used in determining steam or recoverable heat production available from the jacket water and exhaust without condensing the water vapor in the exhaust gas. Water will typically condense out of the exhaust gas at a temperature between 50-60°C (122-140°F), depending on how lean the engine is set.

Engine Heat Balance Data The term heat balance refers to the fact that the heat input introduced as fuel into the engine equals the sum of the heat and work outputs. kW (Btu) values for energy input, work output, total exhaust, exhaust to 350°F (177°C) for engines in English units or 120°C (250°F) for engines in metric units, aftercooler, radiator and jacket water/oil cooler are listed in low heat value due to the fact that the latent heat of vaporization is lost to the exhaust in the combustion process. Formula: Total heat input = work output + total exhaust heat + radiation + jacket water rejection heat + oil cooler rejection heat + aftercooler rejection heat. 1.

"Total Heat Input Energy" is figured by multiplying the BSFC (MJ/bkW-hr (Btu/bhp-hr)) times the kilowatt (horsepower) output to get kW/hr (Btu/hr). [To obtain kW/min (Btu/min), divide by 60]. Fuel volume consumed is obtained by dividing the total heat by the heat content of the fuel [36.2 mJ/N•m3 (920 Btu/cu ft) for low heat value and 37 mJ/N•m3 (995 Btu/cu ft) for high heat value]. The energy input is listed in low heat value (LHV).

2.

"Work Output" is the total kilowatt (horsepower) developed expressed in terms of the heat required to develop the kilowatt (horsepower). It is expressed in kW (Btu/min) where 1 kW = 60 kJ/min (1 hp = 42.4 Btu/min).

3.

"Heat Rejection to Jacket Water" is the total amount of heat picked up by the engine cooling system. On a standard temperature cooling system, those which do not exceed 99°C (210°F) outlet, the oil cooler heat rejection is typically included in this figure. To confirm this, look at the heat rejection to the lube oil. If the lube oil heat is included in the jacket water heat rejection, the value for the heat rejected to lube oil will not be listed or will be a value of zero ("0").

4.

There is a reason for the difference in reported temperatures between English and metric units. It is customary to report exhaust gas data at 350°F (177°C) levels in North America and other English unit countries while it is more common in metric unit areas, particularly Europe, to report the exhaust gas data at 120°C (250°F).

"Heat Rejection to Atmosphere (Radiation)" is the amount of heat loss from the surface of the engine into the engine room or surrounding ambient. 5

Performance Book Users Guide

If an exhaust temperature other than reported temperature is desired, the recoverable heat can be calculated by using the following formula: Q = CpM (T1–T2)

In every calculation using engine data, there is a tolerance band or a deviation from norm. When using the heat balance, the following tolerance must be used.

Q = Heat Rejection in Btu/min

Work Output ...................................................... ± 3%

Cp = Specific Heat of Exhaust Gas:

Aftercooler ......................................................... ± 5%

0.258 Btu/lb/°F — Low Emission Engines

Heat Input .......................................................... ± 5%

0.278 Btu/lb/°F — Standard Engines

Exhaust Total ................................................... ± 10%

M = Exhaust Mass Flow = Ev (CFM) x 41.13 lb/min (T1 + 460°)

8.

Heat Rejection Tolerances

Exhaust Recoverable ...................................... ± 10% Jacket Water .................................................... ± 10%

T1 = Exhaust From Engine °F

Oil Cooler ......................................................... ± 20%

T2 = Exhaust Out of Heat Recovery Silencer °F

Radiation .......................................................... ± 50%

Ev = Exhaust Flow by Volume (CFM)

For cooling systems using oil cooler and jacket water in series (combined circuit), use a tolerance of ± 10% for the combined oil cooler and jacket water heat rejection.

"Heat Rejection to Aftercooler" is given for standard conditions of 25°C (77°F) and 153 m (500 ft) altitude. The actual heat rejection of the engine aftercooler circuit is increased for higher ambient temperatures and altitudes. To maintain a constant intake manifold temperature, as inlet temperature to the aftercooler goes up, so does the heat that must be removed. At higher altitudes, as the air pressure decreases, the turbocharger must work harder to compress the incoming air to the required boost pressure. Be sure to use the aftercooler heat rejection factor to adjust for ambient and altitude conditions. Failure to properly account for these factors could cause the engine to detonate and shut the engine down or, in extreme cases, can cause premature engine failure.

Engine Noise Data The Engine Noise Data section contains noise data for both mechanical and exhaust noise. The measurements were made using the A-weighted (dB(A)) scale which adjusts the sound levels to account for the filtering properties of the human ear. For a complete discussion on noise, consult the Caterpillar Gas Engine Application and Installation Guide (LEKQ2368).

Fuel Usage Guide The Fuel Usage Guide shows the engine derate factor required for a given fuel and what engine timing the engine should be set at to use that fuel. Note that engine deration occurs as the methane number decreases. Methane number is a scale to measure ignition and burning characteristics of various fuels. Representative values are shown below: Methane Number of Selected Fuels Fuel Methane Ethane Propane n-Butane Hydrogen

6

Methane Number 100 44 34 10 0

Performance Book Users Guide

Most dry pipeline natural gas has a methane number of 67 or above. A gas analysis should be made to determine the percentage of each constituent that exists in the fuel. The methane number of the fuel should then be determined by using the Caterpillar "Methane Number Program" (LEKQ6378-02). Once the methane number of the fuel is known, consult the fuel usage guide to determine if an engine derate is required to maintain the appropriate engine detonation margin. An asterisk (*) by the “Derate Factor/Engine Timing” numbers will indicate that an air-fuel ratio control will be required to maintain a safe detonation margin at the indicated load while achieving the NOx emissions levels listed in the “Engine Emissions Data” section. Generally speaking, use a high compression ratio engine for digester and pipeline quality gas, and a low compression ratio engine for propane and field gas. Consult your Caterpillar dealer or factory for assistance in determining the proper engine to use for a fuel in question.

Altitude Deration Factors This chart shows the engine deration that will be required for various ambient temperatures and altitudes the engine may be applied at. The ambient temperature is defined as the temperature of the combustion air as it enters the engine at the air inlet. The identified derate factor should be multiplied times the total available kilowatt (horsepower) to determine the maximum power available from the engine at the specific site conditions. Use this information to help determine actual engine power available for your site.

Actual Engine Rating Calculation It is important to note that the Altitude/Temperature Deration Factor and the Fuel Usage Guide deration are not cumulative, i.e., they are not to be added together. The actual power rating of the engine should be equal to the largest deration of the two. The same is true for the Low Energy Fuel deration and the Fuel Usage Guide deration. However, the Altitude/Temperature deration and low Energy Fuel deration are cumulative; and they must be added together in the method shown below. To determine the actual power available, take the lowest rating identified between the following two procedures.

Aftercooler Heat Rejection Factors The "Aftercooler Heat Rejection Factor" is stated for standard conditions of 25°C (77° F) and 153 m (500 ft) altitude. To keep the engine from going into detonation, it is important to maintain a constant inlet air temperature at the air intake manifold. Therefore, as the ambient air temperature goes up beyond standard conditions, so must the heat rejection for the aftercooler circuit. Also, as altitude increases, the turbocharger must work harder to overcome the lower atmospheric pressure. Both of these conditions increase the amount of heat that must be removed from the inlet air by the aftercooler. Use the aftercooler heat rejection factor to adjust for heat rejection increases due to ambient and/or altitude conditions above engine design levels. Multiply this factor times the listed aftercooler heat rejection and its tolerance to identify the actual heat rejection required of the aftercooler system to maintain proper engine operating conditions. Failure to properly account for these factors could result in detonation and cause the engine to shutdown or fail. If the oil cooler is to be located on the same circuit as the aftercooler, the value of the oil cooler heat rejection should not be included in this calculation. Since the oil cooler heat rejection needs to be dissipated, it should be added back with the aftercooler heat rejection after the altitude and temperature factors have been calculated. Arbitrarily increasing the value of the oil cooler heat rejection by multiplying it times the Aftercooler Heat Rejection Factor will simply cause you to oversize this portion of the cooling system, adding cost to the system without improving the aftercooler cooling system performance or the value to the overall system.

Rating Conditions and Definitions Ratings are based on ISO3046/1 standard reference conditions of 25°C (77°F) and 100 kPa (29.61 in Hg). Continuous is the engine power and speed capability of the engine that can be used without interruption or load cycling.

1) (Altitude/Temperature Deration) + (Low Energy Fuel Deration)

Ratings are based on dry natural gas having an LHV (low heat value) of 36.2 mJ/N•m3 (920 Btu/cu ft). Variations in altitude, temperature, and gas compositions from standard conditions may require a reduction in engine horsepower.

2) Fuel Usage Guide Deration.

LE refers to low emission engine configuration.

Note: For TA engines only add low energy fuel derate to altitude/temperature deration whenever the altitude/temperature derate factor is less than 1.0 (100% of the rating). This will give the actual rating for the engine at the conditions specified. 7

Gas Engine Performance Book Parameters

Notes, conditions and definitions required to accurately apply a Caterpillar gas engine performance book specification: Notes: (1)

Fuel consumption tolerance according to ISO 3046/1. Tolerance is +5% of full load data.

(2)

Heat Rejection to Jacket Water and Heat Rejection to Exhaust tolerance is ±8% of full load data.

(3)

Heat Rejection to Aftercooler tolerance is ±8% of full load data.

(4)

Heat Rejection to Atmosphere (radiated) is ±25% of full load data.

(5)

Heat Rejection to Lube Oil tolerance is ±20% of full rated load. If heat rejection to lube oil =0, then the lube oil heat is included in the jacket water heat rejection value.

(6)

Heat Rejection to Jacket Water: -If Heat Rejection Lube Oil = 0, then Jacket Water Heat Rejection = Jacket Water heat + Oil Cooler heat (This is also known as a "combined" cooling circuit) -If Heat Rejection Lube Oil > 0, then Jacket Water Heat Rejection = Jacket Water heat only (This is also known as a "two circuit" or a "three circuit" cooling system)

(7)

Heat Rejection to Aftercooler is recorded at standard conditions. The value of this number will increase for temperatures above standard conditions. Consult the "Aftercooler Heat Rejection Factors" table on page two of the performance sheet for correction factors.

(8)

For two circuit systems where the aftercooler and oil cooler are on the same circuit, add the "heat rejection to lube oil" to the "heat rejection to aftercooler" number only after any aftercooler heat rejection factors have been calculated and added to the "heat rejection aftercooler" for the total heat load in this circuit. The “heat rejection to lube oil” should not be affected by the aftercooler heat rejection factor.

(9)

Emissions data shown are dry, not to exceed values. Published part load data may require engine adjustment. Consult the factory for special emission setting information.

(10) Inlet Manifold Temperature measured at the intake manifold plenum. (11) Timing indicated is for use with the minimum fuel methane number specified. Consult the appropriate fuel usage guide for timing at other methane numbers. 8

DM5900-00

Conditions and Definitions Engine rating obtained and presented in accordance with ISO 3046/1 (standard reference conditions of 25°C (77°F) and 100 kPa (29.61 in Hg)). No overload permitted at rating shown. Consult the altitude derating curves for applications above maximum rated altitude and/or temperature.

Gas Engine Performance Book Parameters

This data sheet contains the notes, conditions and definitions required to accurately apply a Caterpillar gas engine performance book specification. Notes: (1)

Fuel consumption tolerance according to ISO 3046/1. Tolerance is +5% of full load data.

(2)

Heat Rejection to Jacket Water and Heat Rejection to Exhaust tolerance is ±8% of full load data.

(3)

Heat Rejection to Aftercooler tolerance is ±8% of full load data.

(4)

Heat Rejection to Atmosphere (radiated) is ±25% of full load data.

(5)

Heat Rejection to Lube Oil tolerance is ± 20% of full rated load. If heat rejection to lube oil =0, then the lube oil heat is included in the jacket water heat rejection value.

(6)

Heat Rejection to Jacket Water:

DM5901-00

Conditions and Definitions Engine rating obtained and presented in accordance with ISO 3046/1 (standard reference conditions of 25°C (77°F) and 100 kPa (29.61 in Hg)). No overload permitted at rating shown. Consult the altitude derating curves for applications above maximum rated altitude and/or temperature.

-If Heat Rejection Lube Oil = 0, then Jacket Water Heat Rejection = Jacket Water heat + Oil Cooler heat (This is also known as a "combined" cooling circuit) -If Heat Rejection Lube Oil > 0, then Jacket Water Heat Rejection = Jacket Water heat only (This is also known as a "two circuit" or a "three circuit" cooling system) (7)

Heat Rejection to Aftercooler is recorded at standard conditions. The value of this number will increase for temperatures above standard conditions. Consult the "Aftercooler Heat Rejection Factors" table on page two of the performance sheet for correction factors.

(8)

For two circuit systems where the aftercooler and oil cooler are on the same circuit, add the "heat rejection to lube oil" to the "heat rejection to aftercooler" number only after any aftercooler heat rejection factors have been calculated and added to the "heat rejection to aftercooler" for the total heat load in this circuit. The "heat rejection to lube oil" should not be affected by the aftercooler heat rejection factor.

(9)

Emissions data shown are dry, not to exceed values. Published part load data may require engine adjustment. Consult the factory for special emission setting information.

(10) Inlet Manifold Temperature measured at the intake manifold plenum. (11) Timing indicated is for use with the minimum fuel methane number specified. Consult the appropriate fuel usage guide for timing at other methane numbers. 9

— ???????? Family Index G3500Arrangements Generator Engine Arrangement

G3516 TA Generator Set Engines, 60 hz, Natural Gas Fueled Engine EKW BKW (BHP) Speed 740 785 (1053) 1200 740 785 (1053) 1200 740 785 (1053) 1200 740 785 (1053) 1200

Emission Level STD CAT STD CAT

Engine C/R 9 9 9 9

J/W Temp Deg C (F) 99 (210) 99 (210) 99 (210) 99 (210)

A/C Temp Deg C (F) 54 (130) 54 (130) 54 (130) 54 (130)

2nd Stage A/C Temp Deg C (F) N/A N/A N/A N/A

Engine Page Number Fuel Pricing Performance English Metric Pressure Arrangment Number Units Units HPG LA3056 DM5144 26-27 206-207 HPG LA3056 DM5143 28-29 208-209 LPG LA3056 DM5146 30-31 210-211 LPG LA3056 DM5145 32-33 212-213

G3516 LE Generator Set Engines, 60 hz, Natural Gas Fueled Engine EKW BKW (BHP) Speed 765 809 (1084) 1200 765 809 (1084) 1200 765 809 (1084) 1200

Emission Level LE LE LE

Engine C/R 8 11 11

J/W Temp Deg C (F) 99 (210) 99 (210) 99 (210)

A/C Temp Deg C (F) 54 (130) 54 (130) 54 (130)

2nd Stage A/C Temp Deg C (F) N/A N/A N/A

Engine Page Number Fuel Pricing Performance English Metric Pressure Arrangment Number Units Units HPG LA3058 DM5148 34-35 214-215 HPG PA4873 DM5147 36-37 216-217 LPG PA4873 DM5149 38-39 218-219

810 810 810

856 (1148) 856 (1148) 856 (1148)

1200 1200 1200

LE LE LE

8 11 11

99 (210) 99 (210) 99 (210)

32 (90) 32 (90) 32 (90)

N/A N/A N/A

HPG HPG LPG

LA3058 PA4873 PA4873

DM5151 DM5150 DM5152

40-41 42-43 44-45

220-221 222-223 224-225

1035

1090 (1462)

1800

LE

11

99 (210)

54 (130)

N/A

LPG

LA1231

DM5167

46-47

226-227

G3516 LE Generator Set Engines, 60 hz, Landfill Gas Fueled Engine EKW BKW (BHP) Speed 815 856 (1148) 1200

Emission Level LE

Engine C/R 11

J/W Temp Deg C (F) 110 (230)

A/C Temp Deg C (F) 54 (130)

2nd Stage A/C Temp Deg C (F) N/A

Engine Page Number Fuel Pricing Performance English Metric Pressure Arrangment Number Units Units LPG PA4877 DM5153 48-49 228-229

G3516 LE Generator Set Engines, 50 hz, Natural Gas Fueled EKW BKW (BHP) 975 1010 (1354) 975 1010 (1354) 975 1010 (1354) 975 1010 (1354)

10

Engine Emission Engine Speed Level C/R 1500 1/2 TA LUFT 11 1500 1/2 TA LUFT 11 1500 TA LUFT 11 1500 TA LUFT 11

J/W Temp Deg C (F) 99 (210) 127 (260) 99 (210) 127 (260)

A/C Temp Deg C (F) 54 (130) 54 (130) 54 (130) 54 (130)

2nd Stage A/C Temp Deg C (F) N/A N/A N/A N/A

Engine Page Number Fuel Pricing Performance English Metric Pressure Arrangment Number Units Units LPG LA2948 DM0988 50-51 230-231 DM0873 52-53 232-233 LPG LA2948 DM0991 54-55 234-235 LPG LA2948 DM0876 56-57 236-237 LPG LA2948

975 975 975 975

1010 (1354) 1010 (1354) 1010 (1354) 1010 (1354)

1500 1500 1500 1500

1/2 TA LUFT 1/2 TA LUFT TA LUFT TA LUFT

12 12 12 12

99 (210) 127 (260) 99 (210) 127 (260)

54 (130) 54 (130) 54 (130) 54 (130)

N/A N/A N/A N/A

LPG LPG LPG LPG

LA2947 LA2947 LA2947 LA2947

DM1228 DM1240 DM1231 DM1243

58-59 60-61 62-63 64-65

238-239 240-241 242-243 244-245

970 970 970

1011 (1355) 1011 (1355) 1011 (1355)

1500 1500 1500

LE LE LE

8 11 11

99 (210) 99 (210) 99 (210)

54 (130) 54 (130) 54 (130)

N/A N/A N/A

HPG HPG LPG

PA4874 PA4875 PA4875

DM5156 DM5157 DM5158

66-67 68-69 70-71

246-247 248-249 250-251

1030 1030 1030 1030

1070 (1435) 1070 (1435) 1070 (1435) 1070 (1435)

1500 1500 1500 1500

1/2 TA LUFT 1/2 TA LUFT TA LUFT TA LUFT

12 12 12 12

99 (210) 127 (260) 99 (210) 127 (260)

32 (90) 32 (90) 32 (90) 32 (90)

N/A N/A N/A N/A

LPG LPG LPG LPG

LA2947 LA2947 LA2947 LA2947

DM5166 DM5161 DM5162 DM5163

72-73 74-75 76-77 78-79

252-253 254-255 256-257 258-259

1030 1030 1030 1030

1070 (1435) 1070 (1435) 1070 (1435) 1070 (1435)

1500 1500 1500 1500

1/2 TA LUFT 1/2 TA LUFT TA LUFT TA LUFT

12 12 12 12

99 (210) 127 (260) 99 (210) 127 (260)

70 (158) 70 (158) 70 (158) 70 (158)

32 (90) 32 (90) 32 (90) 32 (90)

LPG LPG LPG LPG

LA2947 LA2947 LA2947 LA2947

DM1229 DM1241 DM1232 DM1244

80-81 82-83 84-85 86-87

260-261 262-263 264-265 266-267

1025 1025

1070 (1435) 1070 (1435)

1500 1500

LE LE

11 11

99 (210) 99 (210)

32 (90) 32 (90)

N/A N/A

HPG LPG

PA4875 PA4875

DM5159 DM5165

88-89 90-91

268-269 270-271

— ???????? Family Index G3500Arrangements Generator Engine Arrangement

G3512 TA Generator Set Engines, 60 hz, Natural Gas Fueled Engine EKW BKW (BHP) Speed 555 590 (791) 1200 555 590 (791) 1200 555 590 (791) 1200 555 590 (791) 1200

Emission Level STD CAT STD CAT

Engine C/R 9 9 9 9

J/W Temp Deg C (F) 99 (210) 99 (210) 99 (210) 99 (210)

A/C Temp Deg C (F) 54 (130) 54 (130) 54 (130) 54 (130)

2nd Stage A/C Temp Deg C (F) N/A N/A N/A N/A

Fuel Pressure HPG HPG LPG LPG

Engine Page Number Pricing Performance English Metric Arrangment Number Units Units PA4940 DM5207 92-93 272-273 PA4940 DM5209 94-95 274-275 PA4940 DM5108 96-97 276-277 PA4940 DM5109 98-99 278-279

Engine Page Number Pricing Performance English Metric Arrangment Number Units Units PA4935 DM0745 100-101 280-281 PA4935 DM5110 102-103 282-283 PA4935 DM5112 104-105 284-285 PA4935 DM5111 106-107 286-287

G3512 LE Generator Set Engines, 60 hz, Natural Gas Fueled Engine EKW BKW (BHP) Speed 570 607 (814) 1200 570 607 (814) 1200 570 607 (814) 1200 570 607 (814) 1200

Emission Level LE LE LE LE

Engine C/R 11 11 11 11

J/W Temp Deg C (F) 99 (210) 127 (260) 99 (210) 127 (260)

A/C Temp Deg C (F) 54 (130) 54 (130) 54 (130) 54 (130)

2nd Stage A/C Temp Deg C (F) N/A N/A N/A N/A

Fuel Pressure HPG HPG LPG LPG

600 600 600

642 (861) 642 (861) 642 (861)

1200 1200 1200

LE LE LE

8 11 11

99 (210) 99 (210) 99 (210)

32 (90) 32 (90) 32 (90)

N/A N/A N/A

HPG HPG LPG

PA4937 PA4935 PA4935

DM5169 DM5173 DM5115

108-109 288-289 110-111 290-291 112-113 292-293

600 600 600

642(861) 642(861) 642(861)

1200 1200 1200

LE LE LE

8 11 11

127 (260) 127 (260) 127 (260)

32 (90) 32 (90) 32 (90)

N/A N/A N/A

HPG HPG LPG

PA4937 PA4935 PA4935

DM5113 DM5114 DM5116

114-115 294-295 116-117 296-297 118-119 298-299

G3512 LE Generator Set Engines, 50 hz, Natural Gas Fueled Engine EKW BKW (BHP) Speed 725 758 (1017) 1500 725 758 (1017) 1500

Emission Level LE LE

Engine C/R 8 8

J/W Temp Deg C (F) 99 (210) 127 (260)

A/C Temp Deg C (F) 54 (130) 54 (130)

2nd Stage A/C Temp Deg C (F) N/A N/A

Fuel Pressure HPG HPG

Engine Page Number Pricing Performance English Metric Arrangment Number Units Units PA4932 DM5171 120-121 300-301 PA4932 DM5122 122-123 302-303

725 725 725 725

758 (1017) 758 (1017) 758 (1017) 758 (1017)

1500 1500 1500 1500

LE LE LE LE

11 11 11 11

99 (210) 127 (260) 99 (210) 127 (260)

54 (130) 54 (130) 54 (130) 54 (130)

N/A N/A N/A N/A

HPG HPG LPG LPG

PA4933 PA4933 PA4933 PA4933

DM5123 DM5121 DM5126 DM5125

124-125 126-127 128-129 130-131

304-305 306-307 308-309 310-311

765 765

803 (1077) 803 (1077)

1500 1500

LE LE

8 8

99 (210) 127 (260)

32 (90) 32 (90)

N/A N/A

HPG HPG

PA4932 PA4932

DM5170 DM5132

132-133 312-313 134-135 314-315

765 765 765 765

803 (1077) 803 (1077) 803 (1077) 803 (1077)

1500 1500 1500 1500

LE LE LE LE

11 11 11 11

99 (210) 127 (260) 99 (210) 127 (260)

32 (90) 32 (90) 32 (90) 32 (90)

N/A N/A N/A N/A

HPG HPG LPG LPG

PA4933 PA4933 PA4933 PA4933

DM5131 DM5130 DM5210 DM5139

136-137 138-139 140-141 142-143

316-317 318-319 320-321 322-323

G3512 LE Generator Set Engines, 50 hz, Natural Gas Fueled Engine Emission Engine EKW BKW (BHP) Speed Level C/R 725 758 (1017) 1500 1/2 TA LUFT 11 725 758 (1017) 1500 TA LUFT 11 725 758 (1017) 1500 1/2 TA LUFT 11 725 758 (1017) 1500 TA LUFT 11

J/W Temp Deg C (F) 99 (210) 99 (210) 127 (260) 127 (260)

A/C Temp Deg C (F) 54 (130) 54 (130) 54 (130) 54 (130)

2nd Stage A/C Temp Deg C (F) N/A N/A N/A N/A

Fuel Pressure LPG LPG LPG LPG

Engine Page Number Pricing Performance English Metric Arrangment Number Units Units LA2943 DM1977 144-145 324-325 LA2943 DM1980 146-147 326-327 LA2943 DM1989 148-149 328-329 LA2943 DM1992 150-151 330-340

725 725 725 725

758 (1017) 758 (1017) 758 (1017) 758 (1017)

1500 1500 1500 1500

1/2 TA LUFT TA LUFT 1/2 TA LUFT TA LUFT

12 12 12 12

99 (210) 99 (210) 127 (260) 127 (260)

54 (130) 54 (130) 54 (130) 54 (130)

N/A N/A N/A N/A

LPG LPG LPG LPG

LA2942 LA2942 LA2942 LA2942

DM1953 DM1956 DM1965 DM1968

152-153 154-155 156-157 158-159

332-333 334-335 336-337 338-339

770 770 770 770

803 (1077) 803 (1077) 803 (1077) 803 (1077)

1500 1500 1500 1500

1/2 TA LUFT TA LUFT 1/2 TA LUFT TA LUFT

12 12 12 12

99 (210) 99 (210) 127 (260) 127 (260)

32 (90) 32 (90) 32 (90) 32 (90)

N/A N/A N/A N/A

LPG LPG LPG LPG

LA2942 LA2942 LA2942 LA2942

DM1952 DM1955 DM1964 DM1967

160-161 162-163 164-165 166-167

340-341 342-343 344-345 346-347

770 770 770 770

803 (1077) 803 (1077) 803 (1077) 803 (1077)

1500 1500 1500 1500

1/2 TA LUFT TA LUFT 1/2 TA LUFT TA LUFT

12 12 12 12

99 (210) 99 (210) 127 (260) 127 (260)

70 (158) 70 (158) 70 (158) 70 (158)

32 (90) 32 (90) 32 (90) 32 (90)

LPG LPG LPG LPG

LA2942 LA2942 LA2942 LA2942

DM1954 DM1957 DM1966 DM1969

168-169 170-171 172-173 174-175

348-349 350-351 352-353 354-355

11

— ???????? Family Index G3500Arrangements Generator Engine Arrangement G3508 TA Generator Set Engines, 60 hz, Natural Gas Fueled Engine EKW BKW (BHP) Speed 370 392 (526) 1200 370 392 (526) 1200 370 392 (526) 1200 370 392 (526) 1200

Emission Level STD CAT STD CAT

Engine C/R 9 9 9 9

J/W Temp Deg C (F) 99 (210) 99 (210) 99 (210) 99 (210)

A/C Temp Deg C (F) 54 (130) 54 (130) 54 (130) 54 (130)

2nd Stage A/C Temp Deg C (F) N/A N/A N/A N/A

Fuel Pressure HPG HPG LPG LPG

Engine Page Number Pricing Performance English Metric Arrangment Number Units Units PA4944 DM5205 176-177 356-357 PA4944 DM5105 178-179 358-359 PA4944 DM5107 180-181 360-361 PA4944 DM5106 182-183 362-363

Fuel Pressure LPG LPG LPG LPG

Engine Page Number Pricing Performance English Metric Arrangment Number Units Units LA3270 DM5231 184-185 364-365 LA3270 DM5232 186-187 366-367 LA3270 DM5233 188-189 368-369 LA3270 DM5234 190-191 370-371

G3508 LE Generator Set Engines, 50 hz, Natural Gas Fueled Engine Emission Engine Level C/R EKW BKW (BHP) Speed 490 505 (677) 1500 1/2 TA LUFT 12.5 490 505 (677) 1500 TA LUFT 12.5 519 535 (717) 1200 1/2 TA LUFT 12.5 519 535 (717) 1200 TA LUFT 12.5

12

J/W Temp Deg C (F) 99 (210) 99 (210) 99 (210) 99 (210)

A/C Temp Deg C (F) 54 (130) 54 (130) 32 (90) 32 (90)

2nd Stage A/C Temp Deg C (F) N/A N/A N/A N/A

English Units Section

13

14

G3516 High Speed

Jacket Water System Performance

TM9732-00

ft of H2O

50 45

External Restriction

40 35 30 25 20 315 10 5 0

B

A

180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480

g/min

External Water Flow

Curve Data Curve Label Engine Speed rpm Pump Speed rpm External Flow gal/min 211.4 237.8 264.2 290.6 317.1 343.5 369.9 396.3 422.7 449.2

A B 1800 1500 2400 2000 -----------------------External Resistance------------------------------------Feet of Water ----------------------35.4 29.2 23.0 47.6 16.8 40.3 10.7 33.1 4.5 25.8 18.6 11.3 4.1

Engine equipped with water cooled exhaust manifolds or with dry exhaust manifolds and JW aftercooler. 2W9729 JW Pump Drive Ratio 1.33:1 For high speed (1301 - 1800 rpm) ratings Curves indicate maximum allowable external resistance. Do not project curves.

15

G3516 Low Speed

Jacket Water System Performance

TM9733-00

ft of H2O

50 45

External Restriction

40 35 30 25 20 15 10 5

B 0

A

180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540

g/min

External Water Flow

Curve Data Curve Label Engine Speed rpm Pump Speed rpm External Flow gal/min 237.8 264.2 290.6 317.1 343.5 369.9 396.3 422.7 449.2

16

A B 1200 1000 2400 2000 -----------------------External Resistance------------------------------------Feet of Water ----------------------29.2 23.0 47.6 16.8 40.3 10.7 33.1 4.5 25.8 18.6 11.3 4.1

Engine equipped with water cooled exhaust manifolds or with dry exhaust manifolds and JW aftercooler. 2W9729 JW Pump Drive Ratio 2:1 For low speed (1300 rpm and below) ratings Curves indicate maximum allowable external resistance. Do not project curves.

G3512 HIgh Speed

Jacket Water System Performance

DM0569-00

ft of H2O

50 45

External Restriction

40 35 30 25 20 15 10 5

B 0

A

120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480

g/min

External Water Flow

Curve Data Curve Label Engine Speed rpm Pump Speed rpm External Flow gal/min 132.1 158.5 185.0 211.4 237.8 264.2 290.6 317.1 343.5 369.9 396.3 422.7

A B 1800 1500 2400 2000 -----------------------External Resistance------------------------------------Feet of Water ----------------------42.2 54.9 37.3 49.8 32.5 44.7 27.6 39.5 22.7 34.4 17.8 29.2 12.9 24.1 8.1 19.0 3.2 13.8 8.7 3.5

Engine equipped with water cooled exhaust manifolds or with dry exhaust manifolds and JW aftercooler. 2W9729 JW Pump Drive Ratio 1.33:1 For high speed (1301-1800 rpm) ratings Curves indicate maximum allowable external resistance. Do not project curves.

17

G3512 Low Speed

Jacket Water System Performance

DM0570-00

ft of H2O 60 55 50 45

External Restriction

40 35 30 25 20 15 10 5

B 0

A

80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440

g/min

External Water Flow

Curve Data Curve Label A Engine Speed rpm 1200 Pump Speed rpm 2400 External Flow gal/min 132.1 158.5 185.0 211.4 237.8 264.2 290.6 317.1 343.5 369.9 396.3

18

B 1000 2000

-----------------------External Resistance------------------------------------Feet of Water ----------------------30.1 47.5 25.6 42.7 21.1 37.8 16.6 33.0 12.1 28.1 7.6 23.2 3.1 18.4 13.5 8.7 3.8

Engine equipped with water cooled exhaust manifolds or with dry exhaust manifolds and JW aftercooler. 2W9726 JW Pump Drive Ratio 2:1 For low speed (1300 rpm and below) ratings Curves indicate maximum allowable external resistance. Do not project curves.

G3508 High Speed

Jacket Water System Performance

TM3095-03

ft of H2O

45

External Restriction

40 35 30 25 20 15 10 5 0

B A 120

140

160

180

200

220

240

260

280

300

320

340

360

380

g/min

External Water Flow

Curve Data Curve Label Engine Speed rpm Pump Speed rpm External Flow gal/min 159 185 211 238 264 291 317 343 349 359 370

A B 1800 1500 2400 2000 -----------------------External Resistance------------------------------------Feet of Water ----------------------34.8 28.9 22.6 37.4 16.7 30.5 10.8 23.3 4.9 16.1 8.9 7.5 4.6 1.6

Engine equipped with water cooled exhaust manifolds or with dry exhaust manifolds and JW aftercooler. 2W9726 JW Pump Drive Ratio 1.33 to 1 For high speed (1301-1800 rpm) ratings Curves indicate maximum allowable external resistance. Do not project curves.

19

G3508 Low Speed

Jacket Water System Performance

TM3089-03

ft of H2O 45

External Restriction

40 35 30 25 20 15 10 5 0

B A 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 g/min

External Water Flow

Curve Data Curve Label A Engine Speed rpm 1200 Pump Speed rpm 2400 External Flow gal/min 185 211 238 264 291 317 343 370

20

B 1000 2000

-----------------------External Resistance------------------------------------Feet of Water ----------------------28.5 22.6 37.4 16.7 30.5 10.8 23.3 4.9 16.1 8.9 2.0

Engine equipped with water cooled exhaust manifolds or with dry exhaust manifolds and JW aftercooler. 2W9726 JW Pump Drive Ratio 2.0 to 1 For low speed (1300 rpm and below) ratings Curves indicate maximum allowable external resistance. Do not project curves.

G3500 High Speed

Auxiliary Water System Performance

DM0571-00

ft of H2O

External Restriction

30 25 20 15 10

A

5 0

B 60

70

80

90

100

110

120

130

g/min

External Water Flow

Curve Data Curve Label Engine Speed rpm Pump Speed rpm External Flow gal/min 79.3 84.5 89.8 92.5 95.1 97.8 100.4 103.0 105.7 108.3 111.0 113.6 116.3 118.9 121.5 124.2

A B 1800 1500 2400 2000 -----------------------External Resistance------------------------------------Feet of Water ----------------------20.3 17.2 14.0 12.5 29.3 10.9 27.5 9.3 25.7 7.7 24.0 6.2 22.2 4.6 20.5 18.7 16.9 15.2 13.4 11.6 9.9

1W9954 AW Pump Drive Ratio 2:1 For high speed (1301-1800 rpm) ratings Curves indicate maximum allowable external resistance. Do not project curves.

21

G3500 Low Speed

Auxiliary Water System Performance

DM0572-00

ft of H2O

35

External Restriction

30

25

20

15

A

10

5

0

B

60

70

80

90

100

110

120

130

140

150

g/min

External Water Flow

Curve Data Curve Label Engine Speed rpm Pump Speed rpm External Flow gal/min 79.3 84.5 87.2 92.5 95.1 97.8 103.0 105.7 111.0 113.6 118.9 121.5 124.2

22

A B 1200 1000 2400 2000 -----------------------External Resistance------------------------------------Feet of Water ----------------------20.3 17.2 15.6 12.5 29.3 10.9 27.5 9.3 24.0 6.2 22.2 4.6 18.7 16.9 13.4 11.6 9.9

1W9954 AW Pump Drive Ratio 2:1 For low speed (1300 rpm and below) ratings Curves indicate maximum allowable external resistance. Do not project curves.

G3516 Jacket Water Flow vs Pressure Drop Across Block for Cogen Engine

Pressure Drop Across Block (in. Hg)

40 Max

35 30 25 20 15 Min 10

250

300

350

400

450

500

550

600

Jacket Water Flow (gal/min)

G3512 Jacket Water Flow vs Pressure Drop Across Block for Cogen Engine

Pressure Drop Across Block (in. Hg)

35 Max

30 25 20 15 10 Min 5

200

250

300

350

400

450

500

Jacket Water Flow (gal/min)

23

G3508 Jacket Water Flow vs Pressure Drop Across Block for Cogen Engine

Pressure Drop Across Block (in. Hg)

30 25

Max

20 15 10 5 Min 0

100

150

200

250

300

Jacket Water Flow (gal/min)

24

350

400

450

Notes

25

®

G3516 TA

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 9.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type STANDARD

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 HPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

35 80 5000

100%

75%

50%

bhp kW

1053 740

790 555

526 370

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

7515 1554 6892 61.3 268 58.7 134 22.5 864 4235 7273

7909 1244 5514 59 240 49.5 133 22.5 840 3329 5820

8676 963 4271 52.2 202 39.9 133 22.5 793 2487 4510

(Corr. 15% 02)

g/bhp-hr ppm

19.9 1476

17.5 1190

17.5 798

(Corr. 15% 02)

g/bhp-hr ppm

1.2 139

1.3 138

1.4 122

(Corr. 15% 02)

g/bhp-hr ppm

1.5 301

1.5 300

2.0 338

(Corr. 15% 02)

g/bhp-hr ppm

0.23 15

0.23 14

0.31 16

%

2.0 1.12

1.6 1.11

1.3 1.10

131836 44663 51811 4554 0 26862 17156 3941

104070 33498 43406 3795 0 20819 13089 2549

76107 22332 34134 3037 0 15237 9156 1365

Engine Power (w/o fan) Generator Set Power (w/o fan)

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9)

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 26

DM5144-00

®

G3516 TA

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0

30 0.59/14

35 0.59/15

40 0.59/16

45 0.59/17

50 0.90/14

55 0.90/15

60 0.90/16

65 1.0/16

70 1.0/18

75 1.0/20

80 to 100 1.0/23

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.94 0.91 0.88 0.84 0.81 0.96 0.93 0.89 0.86 0.83 0.98 0.94 0.91 0.87 0.84 1.00 0.96 0.92 0.89 0.86 1.00 0.98 0.94 0.91 0.87 1.00 0.99 0.96 0.92 0.89 1.00 1.00 0.98 0.94 0.90 1.00 1.00 0.99 0.96 0.92 1.00 1.00 1.00 0.98 0.94 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.78 0.75 0.72 0.70 0.80 0.77 0.74 0.71 0.81 0.78 0.75 0.72 0.82 0.79 0.76 0.73 0.84 0.81 0.78 0.75 0.85 0.82 0.79 0.76 0.87 0.84 0.81 0.77 0.89 0.85 0.82 0.79 0.90 0.87 0.84 0.80 9000 10000 11000 12000

1.61 1.52 1.42 1.32 1.22 1.13 1.03 1.00 1.00 3000

1.69 1.77 1.77 1.77 1.77 1.59 1.67 1.67 1.67 1.67 1.50 1.57 1.57 1.57 1.57 1.40 1.48 1.48 1.48 1.48 1.30 1.38 1.38 1.38 1.38 1.20 1.28 1.28 1.28 1.28 1.10 1.18 1.18 1.18 1.18 1.00 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.77 1.77 1.77 1.77 1.67 1.67 1.67 1.67 1.57 1.57 1.57 1.57 1.48 1.48 1.48 1.48 1.38 1.38 1.38 1.38 1.28 1.28 1.28 1.28 1.18 1.18 1.18 1.18 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3516

0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.38 1.29 1.19 1.10 1.01 1.00 1.00 1.00 1.00 0

1.46 1.36 1.27 1.17 1.08 1.00 1.00 1.00 1.00 1000

1.53 1.44 1.34 1.25 1.15 1.06 1.00 1.00 1.00 2000

DM5144-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5144-00

-ENGLISH- page 2 of 2

27

®

G3516 TA

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 9.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type CATALYST

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

NAT GAS 920 HPG IMPCO 35 80 5000

100%

75%

50%

bhp kW

1053 740

790 555

526 370

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

7700 1365 6054 60.9 257 54.5 133 23 912 3893 6451

8080 1046 4639 58 238 46 133 23 855 2863 4952

9196 732 3246 52.4 209 38.5 131 23 786 1906 3476

(Corr. 15% 02)

g/bhp-hr ppm

11.4 819

11.7 818

11.6 770

(Corr. 15% 02)

g/bhp-hr ppm

12.9 1523

10.1 1164

16.2 1762

(Corr. 15% 02)

g/bhp-hr ppm

1.3 295

1.8 394

2.4 503

(Corr. 15% 02)

g/bhp-hr ppm

0.20 13

0.27 17

0.37 22

%

0.3 0.94

0.2 0.92

0.2 0.87

135094 44663 57242 4554 0 25663 16941 2968

106323 33498 48485 3795 0 18587 11666 1955

80669 22332 42144 3037 0 12129 7088 1025

Engine Power (w/o fan) Generator Set Power (w/o fan)

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9)

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 28

DM5143-00

®

G3516 TA

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0

30 0.59/14

35 0.59/15

40 0.59/16

45 0.59/17

50 0.90/14

55 0.90/15

60 0.90/16

65 1.0/16

70 1.0/18

75 1.0/20

80 to 100 1.0/23

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.94 0.91 0.88 0.84 0.81 0.96 0.93 0.89 0.86 0.83 0.98 0.94 0.91 0.87 0.84 1.00 0.96 0.92 0.89 0.86 1.00 0.98 0.94 0.91 0.87 1.00 0.99 0.96 0.92 0.89 1.00 1.00 0.98 0.94 0.90 1.00 1.00 0.99 0.96 0.92 1.00 1.00 1.00 0.98 0.94 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.78 0.75 0.72 0.70 0.80 0.77 0.74 0.71 0.81 0.78 0.75 0.72 0.82 0.79 0.76 0.73 0.84 0.81 0.78 0.75 0.85 0.82 0.79 0.76 0.87 0.84 0.81 0.77 0.89 0.85 0.82 0.79 0.90 0.87 0.84 0.80 9000 10000 11000 12000

1.69 1.58 1.47 1.36 1.25 1.14 1.03 1.00 1.00 3000

1.77 1.86 1.86 1.86 1.86 1.66 1.75 1.75 1.75 1.75 1.55 1.64 1.64 1.64 1.64 1.44 1.53 1.53 1.53 1.53 1.33 1.41 1.41 1.41 1.41 1.22 1.30 1.30 1.30 1.30 1.11 1.19 1.19 1.19 1.19 1.00 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.86 1.86 1.86 1.86 1.75 1.75 1.75 1.75 1.64 1.64 1.64 1.64 1.53 1.53 1.53 1.53 1.41 1.41 1.41 1.41 1.30 1.30 1.30 1.30 1.19 1.19 1.19 1.19 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3516

0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.43 1.33 1.22 1.12 1.01 1.00 1.00 1.00 1.00 0

1.51 1.41 1.30 1.20 1.09 1.00 1.00 1.00 1.00 1000

1.60 1.49 1.38 1.28 1.17 1.06 1.00 1.00 1.00 2000

DM5143-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5143-00

-ENGLISH- page 2 of 2

29

®

G3516 TA

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 9.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type STANDARD

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 LPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

1.5 80 5000

100%

75%

50%

bhp kW

1053 740

790 555

526 370

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

7515 1554 6892 61.3 268 58.7 134 23 864 4235 7274

7909 1244 5514 59 240 49.5 133 23 840 3329 5821

8676 963 4271 52.2 202 39.9 133 23 793 2487 4511

(Corr. 15% 02)

g/bhp-hr ppm

19.9 1386

17.5 1116

17.5 945

(Corr. 15% 02)

g/bhp-hr ppm

1.2 139

1.3 138

1.4 122

(Corr. 15% 02)

g/bhp-hr ppm

1.5 301

1.5 300

2.0 338

(Corr. 15% 02)

g/bhp-hr ppm

0.23 15

0.23 14

0.31 16

%

2.0 1.11

1.6 1.11

1.3 1.10

131836 44663 51593 4554 0 26862 17156 4160

104070 33498 43264 3795 0 20819 13089 2691

76107 22332 34058 3037 0 15237 9156 1441

Engine Power (w/o fan) Generator Set Power (w/o fan)

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9)

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 30

DM5146-00

®

G3516 TA

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0

30 0.59/14

35 0.59/15

40 0.59/16

45 0.59/17

50 0.90/14

55 60 0.90/15 0.90/16

65 1.0/16

70 1.0/18

75 1.0/20

80 to 100 1.0/23

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.94 0.91 0.88 0.84 0.81 0.96 0.93 0.89 0.86 0.83 0.98 0.94 0.91 0.87 0.84 1.00 0.96 0.92 0.89 0.86 1.00 0.98 0.94 0.91 0.87 1.00 0.99 0.96 0.92 0.89 1.00 1.00 0.98 0.94 0.90 1.00 1.00 0.99 0.96 0.92 1.00 1.00 1.00 0.98 0.94 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.78 0.75 0.72 0.70 0.80 0.77 0.74 0.71 0.81 0.78 0.75 0.72 0.82 0.79 0.76 0.73 0.84 0.81 0.78 0.75 0.85 0.82 0.79 0.76 0.87 0.84 0.81 0.77 0.89 0.85 0.82 0.79 0.90 0.87 0.84 0.80 9000 10000 11000 12000

1.61 1.52 1.42 1.32 1.22 1.13 1.03 1.00 1.00 3000

1.69 1.77 1.77 1.77 1.77 1.59 1.67 1.67 1.67 1.67 1.50 1.57 1.57 1.57 1.57 1.40 1.48 1.48 1.48 1.48 1.30 1.38 1.38 1.38 1.38 1.20 1.28 1.28 1.28 1.28 1.10 1.18 1.18 1.18 1.18 1.00 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.77 1.77 1.77 1.77 1.67 1.67 1.67 1.67 1.57 1.57 1.57 1.57 1.48 1.48 1.48 1.48 1.38 1.38 1.38 1.38 1.28 1.28 1.28 1.28 1.18 1.18 1.18 1.18 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3516

0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.38 1.29 1.19 1.10 1.01 1.00 1.00 1.00 1.00 0

1.46 1.36 1.27 1.17 1.08 1.00 1.00 1.00 1.00 1000

1.53 1.44 1.34 1.25 1.15 1.06 1.00 1.00 1.00 2000

DM5146-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5146-00

-ENGLISH- page 2 of 2

31

®

G3516 TA

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 9.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type CATALYST

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

NAT GAS 920 LPG IMPCO 1.5 80 5000

100%

75%

50%

bhp kW

1053 740

790 555

526 370

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

7700 1365 6054 60.9 257 54.5 133 23 912 3878 6426

8080 1046 4639 58 238 46 133 23 855 2849 4927

9196 732 3246 52.4 209 38.5 131 23 786 1892 3451

(Corr. 15% 02)

g/bhp-hr ppm

11.4 822

11.4 804

11.4 763

(Corr. 15% 02)

g/bhp-hr ppm

12.9 1529

13.1 1514

16.2 1775

(Corr. 15% 02)

g/bhp-hr ppm

1.3 295

1.8 394

2.4 503

(Corr. 15% 02)

g/bhp-hr ppm

0.20 13

0.27 17

0.37 22

%

0.3 1.01

0.2 0.99

0.2 0.97

135094 44663 57297 4554 0 25427 16778 3149

106323 33498 48589 3795 0 18361 11518 2076

80669 22332 42284 3037 0 11924 6960 1090

Engine Power (w/o fan) Generator Set Power (w/o fan)

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9)

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 32

DM5145-00

®

G3516 TA

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0

30 0.59/14

35 0.59/15

40 0.59/16

45 0.59/17

50 0.90/14

55 0.90/15

60 0.90/16

65 1.0/16

70 1.0/18

75 1.0/20

80 to 100 1.0/23

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.94 0.91 0.88 0.84 0.81 0.96 0.93 0.89 0.86 0.83 0.98 0.94 0.91 0.87 0.84 1.00 0.96 0.92 0.89 0.86 1.00 0.98 0.94 0.91 0.87 1.00 0.99 0.96 0.92 0.89 1.00 1.00 0.98 0.94 0.90 1.00 1.00 0.99 0.96 0.92 1.00 1.00 1.00 0.98 0.94 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.78 0.75 0.72 0.70 0.80 0.77 0.74 0.71 0.81 0.78 0.75 0.72 0.82 0.79 0.76 0.73 0.84 0.81 0.78 0.75 0.85 0.82 0.79 0.76 0.87 0.84 0.81 0.77 0.89 0.85 0.82 0.79 0.90 0.87 0.84 0.80 9000 10000 11000 12000

1.69 1.58 1.47 1.36 1.25 1.14 1.03 1.00 1.00 3000

1.77 1.86 1.86 1.86 1.86 1.66 1.75 1.75 1.75 1.75 1.55 1.64 1.64 1.64 1.64 1.44 1.53 1.53 1.53 1.53 1.33 1.41 1.41 1.41 1.41 1.22 1.30 1.30 1.30 1.30 1.11 1.19 1.19 1.19 1.19 1.00 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.86 1.86 1.86 1.86 1.75 1.75 1.75 1.75 1.64 1.64 1.64 1.64 1.53 1.53 1.53 1.53 1.41 1.41 1.41 1.41 1.30 1.30 1.30 1.30 1.19 1.19 1.19 1.19 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3516

0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.43 1.33 1.22 1.12 1.01 1.00 1.00 1.00 1.00 0

1.51 1.41 1.30 1.20 1.09 1.00 1.00 1.00 1.00 1000

1.60 1.49 1.38 1.28 1.17 1.06 1.00 1.00 1.00 2000

DM5145-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5145-00

-ENGLISH- page 2 of 2

33

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 8.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 HPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

35 80 5000

100%

75%

50%

1085 765

814 574

542 383

7335 2264 10040 69.2 287 62.4 136 33 842 5977 10437

7540 1680 7450 64 264 47.9 135 33 820 4368 7756

8104 991 4392 45.9 179 30.2 138 33 862 2681 4611

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 147

2.6 185

4.2 321

(Corr. 15% 02)

g/bhp-hr ppm

1.8 215

2.0 229

1.8 230

(Corr. 15% 02)

g/bhp-hr ppm

3.2 677

3.1 636

2.3 517

(Corr. 15% 02)

g/bhp-hr ppm

0.48 47

0.47 43

0.35 33

%

8.0 1.56

7.5 1.50

6.9 1.24

132610 46029 38361 4554 0 37333 23002 6330

102239 34522 32864 3795 0 26990 16360 4066

73261 23014 29294 3037 0 17000 10750 914

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 34

DM5148-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/--

70 0/--

75 1.0/19

80 to 100 1.0/21

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.94 0.91 0.88 0.84 0.81 0.96 0.93 0.89 0.86 0.83 0.98 0.94 0.91 0.87 0.84 1.00 0.96 0.92 0.89 0.86 1.00 0.98 0.94 0.91 0.87 1.00 0.99 0.96 0.92 0.89 1.00 1.00 0.98 0.94 0.90 1.00 1.00 0.99 0.96 0.92 1.00 1.00 1.00 0.98 0.94 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.78 0.75 0.72 0.70 0.80 0.77 0.74 0.71 0.81 0.78 0.75 0.72 0.82 0.79 0.76 0.73 0.84 0.81 0.78 0.75 0.85 0.82 0.79 0.76 0.87 0.84 0.81 0.77 0.89 0.85 0.82 0.79 0.90 0.87 0.84 0.80 9000 10000 11000 12000

1.57 1.48 1.39 1.29 1.20 1.11 1.02 1.00 1.00 3000

1.64 1.71 1.71 1.71 1.71 1.55 1.62 1.62 1.62 1.62 1.45 1.52 1.52 1.52 1.52 1.36 1.43 1.43 1.43 1.43 1.27 1.34 1.34 1.34 1.34 1.18 1.24 1.24 1.24 1.24 1.09 1.15 1.15 1.15 1.15 1.00 1.06 1.06 1.06 1.06 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.71 1.71 1.71 1.71 1.62 1.62 1.62 1.62 1.52 1.52 1.52 1.52 1.43 1.43 1.43 1.43 1.34 1.34 1.34 1.34 1.24 1.24 1.24 1.24 1.15 1.15 1.15 1.15 1.06 1.06 1.06 1.06 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3516

0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.36 1.28 1.19 1.10 1.01 1.00 1.00 1.00 1.00 0

1.43 1.34 1.25 1.16 1.08 1.00 1.00 1.00 1.00 1000

1.50 1.41 1.32 1.23 1.14 1.05 1.00 1.00 1.00 2000

DM5148-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5148-00

-ENGLISH- page 2 of 2

35

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 HPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

30 80 3495

100%

75%

50%

1085 765

814 574

542 383

6960 2215 9824 68.9 307 61.3 143 22 781 5563 10195

7137 1547 6861 58.6 254 44.1 139 22 811 3996 7146

7780 1063 4714 44.3 185 30.8 137 22 813 2756 4921

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 157

5.6 427

8.0 551

(Corr. 15% 02)

g/bhp-hr ppm

1.7 220

1.8 224

1.8 206

(Corr. 15% 02)

g/bhp-hr ppm

4.6 1055

3.5 775

3.7 737

(Corr. 15% 02)

g/bhp-hr ppm

0.69 77

0.53 51

0.56 45

%

8.7 1.64

7.3 1.49

6.1 1.41

125843 46029 34175 4554 0 34441 19546 6641

96776 34522 30209 3795 0 24899 14787 3348

70329 23014 25946 3037 0 17274 10260 1056

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 36

DM5147-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/15

70 1.0/17

75 1.0/19

80 1.0/20

83 to 100 1.0/22

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

0.96 0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.89 0.86 0.83 0.80 0.77 0.91 0.88 0.84 0.81 0.78 0.92 0.89 0.86 0.83 0.80 0.94 0.91 0.87 0.84 0.81 0.96 0.92 0.89 0.86 0.82 0.98 0.94 0.91 0.87 0.84 0.99 0.96 0.92 0.89 0.86 1.00 0.98 0.94 0.91 0.87 1.00 1.00 0.96 0.92 0.89 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.74 0.71 0.68 0.66 0.75 0.72 0.70 0.67 0.77 0.74 0.71 0.68 0.78 0.75 0.72 0.69 0.79 0.76 0.73 0.71 0.81 0.78 0.75 0.72 0.82 0.79 0.76 0.73 0.84 0.81 0.78 0.75 0.86 0.82 0.79 0.76 9000 10000 11000 12000

1.55 1.46 1.38 1.29 1.20 1.11 1.03 1.00 1.00 3000

1.59 1.59 1.59 1.59 1.59 1.50 1.50 1.50 1.50 1.50 1.41 1.41 1.41 1.41 1.41 1.32 1.32 1.32 1.32 1.32 1.23 1.23 1.23 1.23 1.23 1.15 1.15 1.15 1.15 1.15 1.06 1.06 1.06 1.06 1.06 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.59 1.59 1.59 1.59 1.50 1.50 1.50 1.50 1.41 1.41 1.41 1.41 1.32 1.32 1.32 1.32 1.23 1.23 1.23 1.23 1.15 1.15 1.15 1.15 1.06 1.06 1.06 1.06 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3516

0.93 0.94 0.96 0.98 0.99 1.00 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.34 1.26 1.17 1.09 1.01 1.00 1.00 1.00 1.00 0

1.41 1.33 1.24 1.16 1.07 1.00 1.00 1.00 1.00 1000

1.48 1.39 1.31 1.22 1.14 1.05 1.00 1.00 1.00 2000

DM5147-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5147-00

-ENGLISH- page 2 of 2

37

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 LPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

1.5 80 2494

100%

75%

50%

1085 765

814 574

542 383

6998 2174 9640 66.9 272 58.5 143 22 781 5459 10004

7176 1518 6733 57.1 227 42.8 139 22 811 3921 7012

7822 1043 4626 43.5 166 30.6 137 22 813 2704 4829

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 157

5.6 427

8.0 551

(Corr. 15% 02)

g/bhp-hr ppm

1.7 220

1.8 224

1.8 206

(Corr. 15% 02)

g/bhp-hr ppm

4.6 1055

3.5 775

3.7 737

(Corr. 15% 02)

g/bhp-hr ppm

0.69 77

0.53 51

0.56 45

%

8.7 1.64

7.3 1.49

6.1 1.41

126526 46029 36524 4554 0 33851 19180 5564

97301 34522 31758 3795 0 24464 14510 2759

70710 23014 26894 3037 0 16972 10068 791

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 38

DM5149-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/15

70 1.0/17

75 1.0/19

80 1.0/20

83 to 100 1.0/22

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.96 0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

0.93 0.94 0.96 0.98 0.99 1.00 1.00 1.00 1.00 2000

0.86 0.83 0.80 0.77 0.74 0.88 0.84 0.81 0.78 0.75 0.89 0.86 0.83 0.80 0.77 0.91 0.87 0.84 0.81 0.78 0.92 0.89 0.86 0.82 0.79 0.94 0.91 0.87 0.84 0.81 0.96 0.92 0.89 0.86 0.82 0.98 0.94 0.91 0.87 0.84 1.00 0.96 0.92 0.89 0.86 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.71 0.69 0.66 0.63 0.72 0.70 0.67 0.64 0.74 0.71 0.68 0.66 0.75 0.72 0.69 0.67 0.76 0.74 0.71 0.68 0.78 0.75 0.72 0.69 0.79 0.76 0.73 0.71 0.81 0.78 0.75 0.72 0.82 0.79 0.76 0.73 9000 10000 11000 12000

1.59 1.49 1.39 1.29 1.19 1.09 1.00 1.00 1.00 3000

1.59 1.59 1.59 1.59 1.59 1.49 1.49 1.49 1.49 1.49 1.39 1.39 1.39 1.39 1.39 1.29 1.29 1.29 1.29 1.29 1.19 1.19 1.19 1.19 1.19 1.09 1.09 1.09 1.09 1.09 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.59 1.59 1.59 1.59 1.49 1.49 1.49 1.49 1.39 1.39 1.39 1.39 1.29 1.29 1.29 1.29 1.19 1.19 1.19 1.19 1.09 1.09 1.09 1.09 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3516

0.89 0.91 0.92 0.94 0.96 0.98 0.99 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.41 1.31 1.21 1.12 1.02 1.00 1.00 1.00 1.00 0

1.48 1.38 1.28 1.18 1.09 1.00 1.00 1.00 1.00 1000

1.55 1.45 1.36 1.26 1.16 1.06 1.00 1.00 1.00 2000

DM5149-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5149-00

-ENGLISH- page 2 of 2

39

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 8.0:1 Aftercooler Inlet Temperature (°F) 90 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 HPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

35 80 4922

100%

75%

50%

1148 810

861 608

574 405

7471 2326 10316 69.3 282 63.4 116 35 847 6173 10735

7628 1739 7710 60.3 244 49.3 112 35 847 4618 8031

7960 1128 5003 44.5 171 34.1 107 35 846 3001 5227

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 152

2.3 170

4.3 311

(Corr. 15% 02)

g/bhp-hr ppm

1.4 182

1.5 177

1.8 215

(Corr. 15% 02)

g/bhp-hr ppm

2.7 606

2.6 566

2.4 501

(Corr. 15% 02)

g/bhp-hr ppm

0.41 42

0.40 38

0.36 32

%

8.1 1.52

7.6 1.48

6.7 1.38

142921 48703 43956 4554 0 38470 23967 7234

109444 36527 35829 3795 0 28780 17957 4509

76142 24351 28363 3037 0 18715 11697 1673

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 40

DM5151-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 35 40 0.90/21 0.90/23 0.90/24

45 1.0/25

50 1.0/26

55 1.0/28

60 1.0/29

65 1.0/30

70 1.0/32

75 1.0/33

80 1.0/34

83 to 100 1.0/35

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.94 0.91 0.87 0.84 0.81 0.96 0.92 0.89 0.86 0.82 0.98 0.94 0.90 0.87 0.84 0.99 0.96 0.92 0.89 0.85 1.00 0.97 0.94 0.90 0.87 1.00 0.99 0.95 0.92 0.89 1.00 1.00 0.97 0.94 0.90 1.00 1.00 0.99 0.95 0.92 1.00 1.00 1.00 0.97 0.94 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.78 0.75 0.72 0.69 0.79 0.76 0.73 0.71 0.81 0.78 0.75 0.72 0.82 0.79 0.76 0.73 0.84 0.80 0.77 0.74 0.85 0.82 0.79 0.76 0.87 0.83 0.80 0.77 0.88 0.85 0.82 0.79 0.90 0.87 0.83 0.80 9000 10000 11000 12000

1.50 1.42 1.34 1.26 1.18 1.10 1.02 1.00 1.00 3000

1.56 1.62 1.62 1.62 1.62 1.48 1.54 1.54 1.54 1.54 1.40 1.45 1.45 1.45 1.45 1.32 1.37 1.37 1.37 1.37 1.24 1.29 1.29 1.29 1.29 1.16 1.21 1.21 1.21 1.21 1.07 1.13 1.13 1.13 1.13 1.00 1.04 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.62 1.62 1.62 1.62 1.54 1.54 1.54 1.54 1.45 1.45 1.45 1.45 1.37 1.37 1.37 1.37 1.29 1.29 1.29 1.29 1.21 1.21 1.21 1.21 1.13 1.13 1.13 1.13 1.04 1.04 1.04 1.04 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3516

0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.32 1.24 1.17 1.09 1.01 1.00 1.00 1.00 1.00 0

1.38 1.30 1.22 1.15 1.07 1.00 1.00 1.00 1.00 1000

1.44 1.36 1.28 1.20 1.12 1.04 1.00 1.00 1.00 2000

DM5151-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5151-00

-ENGLISH- page 2 of 2

41

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°F) 90 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 HPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

30 80 3495

100%

75%

50%

1148 810

861 608

574 405

7049 2314 10261 69.5 309 64 116 24 770 5766 10658

7119 1631 7232 56.9 264 46.8 111 24 792 4148 7535

7614 1117 4952 45.1 191 32.3 109 24 797 2858 5169

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 166

4.6 362

6.1 456

(Corr. 15% 02)

g/bhp-hr ppm

1.6 209

1.7 218

1.8 217

(Corr. 15% 02)

g/bhp-hr ppm

5.3 1240

4.1 938

4.4 954

(Corr. 15% 02)

g/bhp-hr ppm

0.80 90

0.62 62

0.67 61

%

8.7 1.59

7.5 1.47

7.0 1.41

134853 48703 37169 4554 0 36041 19946 8382

102149 36527 31113 3795 0 25899 14914 4812

72833 24351 25444 3037 0 18012 10388 1987

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 42

DM5150-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 1.0/15

65 1.0/17

70 1.0/19

75 1.0/21

80 1.0/22

83 to 100 1.0/24

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

0.96 0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.89 0.86 0.83 0.80 0.77 0.91 0.88 0.84 0.81 0.78 0.92 0.89 0.86 0.83 0.80 0.94 0.91 0.87 0.84 0.81 0.96 0.92 0.89 0.86 0.82 0.98 0.94 0.91 0.87 0.84 0.99 0.96 0.92 0.89 0.86 1.00 0.98 0.94 0.91 0.87 1.00 1.00 0.96 0.92 0.89 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.74 0.71 0.68 0.66 0.75 0.72 0.70 0.67 0.77 0.74 0.71 0.68 0.78 0.75 0.72 0.69 0.79 0.76 0.73 0.71 0.81 0.78 0.75 0.72 0.82 0.79 0.76 0.73 0.84 0.81 0.78 0.75 0.86 0.82 0.79 0.76 9000 10000 11000 12000

1.46 1.38 1.31 1.24 1.17 1.09 1.02 1.00 1.00 3000

1.49 1.49 1.49 1.49 1.49 1.41 1.41 1.41 1.41 1.41 1.34 1.34 1.34 1.34 1.34 1.27 1.27 1.27 1.27 1.27 1.19 1.19 1.19 1.19 1.19 1.12 1.12 1.12 1.12 1.12 1.05 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.49 1.49 1.49 1.49 1.41 1.41 1.41 1.41 1.34 1.34 1.34 1.34 1.27 1.27 1.27 1.27 1.19 1.19 1.19 1.19 1.12 1.12 1.12 1.12 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3516

0.93 0.94 0.96 0.98 0.99 1.00 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.28 1.21 1.14 1.08 1.01 1.00 1.00 1.00 1.00 0

1.34 1.27 1.20 1.13 1.06 1.00 1.00 1.00 1.00 1000

1.40 1.33 1.26 1.18 1.11 1.04 1.00 1.00 1.00 2000

DM5150-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5150-00

-ENGLISH- page 2 of 2

43

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°F) 90 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 LPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

1.5 80 2494

100%

75%

50%

1148 810

861 608

574 405

7087 2270 10069 67.5 275 61 116 24 770 5658 10458

7158 1600 7096 55.5 235 45.2 111 24 792 4070 7394

7656 1096 4859 44.3 171 32 109 24 797 2804 5072

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 166

4.6 362

6.1 456

(Corr. 15% 02)

g/bhp-hr ppm

1.6 209

1.7 218

1.8 217

(Corr. 15% 02)

g/bhp-hr ppm

5.3 1240

4.1 938

4.4 954

(Corr. 15% 02)

g/bhp-hr ppm

0.80 90

0.62 62

0.67 61

%

8.7 1.59

7.5 1.47

7.0 1.41

135584 48703 39938 4554 0 35433 19567 6953

102703 36527 32949 3795 0 25453 14635 3976

73228 24351 26525 3037 0 17703 10194 1610

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 44

DM5152-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 1.0/15

65 1.0/17

70 1.0/19

75 1.0/21

80 1.0/22

83 to 100 1.0/24

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.96 0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

0.93 0.94 0.96 0.98 0.99 1.00 1.00 1.00 1.00 2000

0.86 0.83 0.80 0.77 0.74 0.88 0.84 0.81 0.78 0.75 0.89 0.86 0.83 0.80 0.77 0.91 0.87 0.84 0.81 0.78 0.92 0.89 0.86 0.82 0.79 0.94 0.91 0.87 0.84 0.81 0.96 0.92 0.89 0.86 0.82 0.98 0.94 0.91 0.87 0.84 1.00 0.96 0.92 0.89 0.86 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.71 0.69 0.66 0.63 0.72 0.70 0.67 0.64 0.74 0.71 0.68 0.66 0.75 0.72 0.69 0.67 0.76 0.74 0.71 0.68 0.78 0.75 0.72 0.69 0.79 0.76 0.73 0.71 0.81 0.78 0.75 0.72 0.82 0.79 0.76 0.73 9000 10000 11000 12000

1.48 1.40 1.32 1.23 1.15 1.07 1.00 1.00 1.00 3000

1.48 1.48 1.48 1.48 1.48 1.40 1.40 1.40 1.40 1.40 1.32 1.32 1.32 1.32 1.32 1.23 1.23 1.23 1.23 1.23 1.15 1.15 1.15 1.15 1.15 1.07 1.07 1.07 1.07 1.07 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.48 1.48 1.48 1.48 1.40 1.40 1.40 1.40 1.32 1.32 1.32 1.32 1.23 1.23 1.23 1.23 1.15 1.15 1.15 1.15 1.07 1.07 1.07 1.07 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3516

0.89 0.91 0.92 0.94 0.96 0.98 0.99 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.33 1.25 1.17 1.09 1.01 1.00 1.00 1.00 1.00 0

1.39 1.31 1.23 1.15 1.07 1.00 1.00 1.00 1.00 1000

1.45 1.37 1.29 1.21 1.13 1.04 1.00 1.00 1.00 2000

DM5152-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5152-00

-ENGLISH- page 2 of 2

45

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1800 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 LPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

1.5 80 3500

100%

75%

50%

1462 1035

1096 776

731 518

7784 3042 13489 70.1 306 63.5 138 18 886 8319 14056

8018 2263 10035 60.5 268 49.4 134 18 881 6175 10472

8480 1417 6285 45.1 197 35.3 130 18 917 3993 6591

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 142

2.4 170

5.2 374

(Corr. 15% 02)

g/bhp-hr ppm

1.9 224

1.9 215

1.8 208

(Corr. 15% 02)

g/bhp-hr ppm

2.2 482

2.3 466

2.2 437

(Corr. 15% 02)

g/bhp-hr ppm

0.34 32

0.35 30

0.33 27

%

7.4 1.60

7.1 1.55

6.0 1.40

189623 62017 58444 6831 0 52498 33937 9826

146491 46512 49335 5693 0 38999 25105 5946

103287 31008 39867 4555 0 25868 17050 1984

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 46

DM5167-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/15

70 1.0/16

75 1.0/17

83 to 100 1.0/18

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

0.96 0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.89 0.86 0.83 0.80 0.77 0.91 0.88 0.84 0.81 0.78 0.92 0.89 0.86 0.83 0.80 0.94 0.91 0.87 0.84 0.81 0.96 0.92 0.89 0.86 0.82 0.98 0.94 0.91 0.87 0.84 0.99 0.96 0.92 0.89 0.86 1.00 0.98 0.94 0.91 0.87 1.00 1.00 0.96 0.92 0.89 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.74 0.71 0.68 0.66 0.75 0.72 0.70 0.67 0.77 0.74 0.71 0.68 0.78 0.75 0.72 0.69 0.79 0.76 0.73 0.71 0.81 0.78 0.75 0.72 0.82 0.79 0.76 0.73 0.84 0.81 0.78 0.75 0.86 0.82 0.79 0.76 9000 10000 11000 12000

1.52 1.44 1.36 1.27 1.19 1.11 1.03 1.00 1.00 3000

1.56 1.56 1.56 1.56 1.56 1.47 1.47 1.47 1.47 1.47 1.39 1.39 1.39 1.39 1.39 1.31 1.31 1.31 1.31 1.31 1.22 1.22 1.22 1.22 1.22 1.14 1.14 1.14 1.14 1.14 1.06 1.06 1.06 1.06 1.06 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.56 1.56 1.56 1.56 1.47 1.47 1.47 1.47 1.39 1.39 1.39 1.39 1.31 1.31 1.31 1.31 1.22 1.22 1.22 1.22 1.14 1.14 1.14 1.14 1.06 1.06 1.06 1.06 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3516

0.93 0.94 0.96 0.98 0.99 1.00 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.33 1.25 1.17 1.09 1.01 1.00 1.00 1.00 1.00 0

1.39 1.31 1.23 1.15 1.07 1.00 1.00 1.00 1.00 1000

1.46 1.37 1.29 1.21 1.13 1.05 1.00 1.00 1.00 2000

DM5167-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5167-00

-ENGLISH- page 2 of 2

47

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 230 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

LANDFILL 545 LPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

1.5 130 2500

100%

75%

50%

1148 815

861 611

574 408

7897 2097 9300 67 290 62.6 149 20 847 6035 10495

8144 1433 6352 60.9 253 45.5 147 20 865 4244 7280

8911 936 4150 45.8 183 31.3 149 20 887 2851 4812

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 143

6.0 426

8.8 561

(Corr. 15% 02)

g/bhp-hr ppm

3.0 352

3.2 374

3.0 310

(Corr. 15% 02)

g/bhp-hr ppm

2.7 551

2.0 407

2.1 385

(Corr. 15% 02)

g/bhp-hr ppm

0.40 34

0.30 23

0.32 19

%

6.3 1.31

4.9 1.16

2.9 1.06

151085 48703 42129 5225 8813 39689 24766 6525

116858 36527 36469 4355 7629 28320 18075 3558

85242 24351 30533 3484 6387 19478 12597 1009

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 48

DM5153-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/--

70 0/--

75 0/--

80 to 129 0/--

130 + 1.0/20

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.96 0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

0.93 0.94 0.96 0.98 0.99 1.00 1.00 1.00 1.00 2000

0.86 0.83 0.80 0.77 0.74 0.88 0.84 0.81 0.78 0.75 0.89 0.86 0.83 0.80 0.77 0.91 0.87 0.84 0.81 0.78 0.92 0.89 0.86 0.83 0.79 0.94 0.91 0.87 0.84 0.81 0.96 0.92 0.89 0.86 0.82 0.98 0.94 0.91 0.87 0.84 1.00 0.96 0.92 0.89 0.86 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.71 0.69 0.66 0.63 0.72 0.70 0.67 0.64 0.74 0.71 0.68 0.66 0.75 0.72 0.69 0.67 0.76 0.74 0.71 0.68 0.78 0.75 0.72 0.69 0.79 0.76 0.73 0.71 0.81 0.78 0.75 0.72 0.82 0.79 0.76 0.73 9000 10000 11000 12000

1.53 1.44 1.35 1.26 1.17 1.08 1.00 1.00 1.00 3000

1.53 1.53 1.53 1.53 1.53 1.44 1.44 1.44 1.44 1.44 1.35 1.35 1.35 1.35 1.35 1.26 1.26 1.26 1.26 1.26 1.17 1.17 1.17 1.17 1.17 1.08 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.53 1.53 1.53 1.53 1.44 1.44 1.44 1.44 1.35 1.35 1.35 1.35 1.26 1.26 1.26 1.26 1.17 1.17 1.17 1.17 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3516

0.89 0.91 0.92 0.94 0.96 0.98 0.99 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.36 1.27 1.18 1.09 1.01 1.00 1.00 1.00 1.00 0

1.43 1.34 1.25 1.16 1.07 1.00 1.00 1.00 1.00 1000

1.50 1.41 1.32 1.23 1.14 1.05 1.00 1.00 1.00 2000

DM5153-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5153-00

-ENGLISH- page 2 of 2

49

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

NAT GAS 920 DELTEC 1.5 80 1149

100%

75%

50%

1354 975

1016 731

677 488

7161 3040 13480 78.8 307 74 137 24 954 8683 13958

7371 2316 10272 66.6 260 56.7 134 24 959 6639 10638

7808 1602 7106 49 190 39.2 132 24 971 4634 7363

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

0.6 46

0.6 46

0.6 46

(Corr. 15% 02)

g/bhp-hr ppm

2.8 370

2.8 351

2.7 331

(Corr. 15% 02)

g/bhp-hr ppm

4.3 1237

4.1 1296

6.7 1341

(Corr. 15% 02)

g/bhp-hr ppm

0.65 103

0.62 106

1.01 107

%

10.2 1.74

10.0 1.73

9.8 1.70

161641 57465 31408 5693 0 57574 37799 9495

124791 43099 27593 4744 0 43981 29046 5370

88124 28732 22031 3796 0 31848 20527 1713

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 50

DM0988-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/18

70 1.0/20

75 1.0/22

80 to 100 1.0/24

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 0

0.92 0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1000

0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 2000

0.82 0.79 0.76 0.73 0.70 0.83 0.80 0.77 0.74 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.90 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.81 0.78 0.93 0.90 0.86 0.83 0.80 0.95 0.91 0.88 0.85 0.82 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.68 0.65 0.63 0.60 0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.75 0.73 0.70 0.67 0.77 0.74 0.71 0.68 0.78 0.75 0.73 0.70 9000 10000 11000 12000

1.42 1.33 1.25 1.17 1.08 1.00 1.00 1.00 1.00 3000

1.42 1.42 1.42 1.42 1.42 1.33 1.33 1.33 1.33 1.33 1.25 1.25 1.25 1.25 1.25 1.17 1.17 1.17 1.17 1.17 1.08 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.42 1.42 1.42 1.42 1.33 1.33 1.33 1.33 1.25 1.25 1.25 1.25 1.17 1.17 1.17 1.17 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3516

0.85 0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.35 1.27 1.18 1.10 1.02 1.00 1.00 1.00 1.00 0

1.41 1.32 1.24 1.16 1.07 1.00 1.00 1.00 1.00 1000

1.42 1.33 1.25 1.17 1.08 1.00 1.00 1.00 1.00 2000

DM0988-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM0988-00

-ENGLISH- page 2 of 2

51

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 260 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

NAT GAS 920 DELTEC 1.5 80 1149

100%

75%

50%

1354 975

1016 731

677 488

7246 3048 13516 79.6 316 75.4 137 20 1018 9104 14007

7421 2290 10155 68.2 274 56.9 134 20 1022 6862 10527

7942 1593 7065 49.6 204 39.3 131 20 1031 4808 7329

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

0.6 46

0.6 46

0.6 46

(Corr. 15% 02)

g/bhp-hr ppm

2.7 347

2.7 337

2.7 322

(Corr. 15% 02)

g/bhp-hr ppm

4.5 931

4.8 968

5.6 1046

(Corr. 15% 02)

g/bhp-hr ppm

0.68 75

0.73 77

0.84 82

%

9.9 1.71

9.7 1.69

9.5 1.65

163555 57465 20511 7400 5914 62160 42123 10099

125629 43099 18071 6168 5210 47128 31878 5948

89632 28732 15870 4935 4576 33386 22541 2131

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 52

DM0873-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 70 0.95/16* 1.0/16*

75 1.0/18

80 to 100 1.0/20

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 0

0.92 0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1000

0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 2000

0.82 0.79 0.76 0.73 0.70 0.83 0.80 0.77 0.74 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.90 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.81 0.78 0.93 0.90 0.86 0.83 0.80 0.95 0.91 0.88 0.85 0.82 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.68 0.65 0.63 0.60 0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.75 0.73 0.70 0.67 0.77 0.74 0.71 0.68 0.78 0.75 0.73 0.70 9000 10000 11000 12000

1.40 1.32 1.24 1.16 1.08 1.00 1.00 1.00 1.00 3000

1.40 1.40 1.40 1.40 1.40 1.32 1.32 1.32 1.32 1.32 1.24 1.24 1.24 1.24 1.24 1.16 1.16 1.16 1.16 1.16 1.08 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.40 1.40 1.40 1.40 1.32 1.32 1.32 1.32 1.24 1.24 1.24 1.24 1.16 1.16 1.16 1.16 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3516

0.85 0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.33 1.25 1.17 1.09 1.02 1.00 1.00 1.00 1.00 0

1.39 1.31 1.23 1.15 1.07 1.00 1.00 1.00 1.00 1000

1.40 1.32 1.24 1.16 1.08 1.00 1.00 1.00 1.00 2000

DM0873-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM0873-00

-ENGLISH- page 2 of 2

53

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

NAT GAS 920 DELTEC 1.5 80 1641

100%

75%

50%

1354 975

1016 731

677 488

6916 2854 12657 77.7 304 70 142 24 984 8340 13129

7134 2146 9517 61.8 245 51.8 135 24 989 6294 9878

7507 1462 6485 46.3 180 36.7 131 24 998 4321 6737

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

1.1 91

1.1 91

1.2 91

(Corr. 15% 02)

g/bhp-hr ppm

2.5 325

2.5 325

2.6 317

(Corr. 15% 02)

g/bhp-hr ppm

4.4 955

4.9 1029

5.7 1107

(Corr. 15% 02)

g/bhp-hr ppm

0.66 74

0.74 78

0.85 83

%

9.5 1.65

9.2 1.62

9.0 1.58

156104 57465 29323 4322 0 56451 43527 8543

120774 43099 26385 3867 0 43024 32987 4399

84721 28732 21601 3128 0 29932 22832 1328

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 54

DM0991-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/18

70 1.0/20

75 1.0/22

80 to 100 1.0/24

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 1000

0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 1.00 2000

0.83 0.80 0.77 0.75 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.89 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.81 0.78 0.93 0.89 0.86 0.83 0.80 0.95 0.91 0.88 0.85 0.81 0.97 0.93 0.90 0.86 0.83 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.75 0.73 0.70 0.67 0.77 0.74 0.71 0.68 0.78 0.75 0.72 0.70 0.80 0.77 0.74 0.71 9000 10000 11000 12000

1.46 1.38 1.29 1.20 1.11 1.03 1.00 1.00 1.00 3000

1.46 1.46 1.46 1.46 1.46 1.38 1.38 1.38 1.38 1.38 1.29 1.29 1.29 1.29 1.29 1.20 1.20 1.20 1.20 1.20 1.11 1.11 1.11 1.11 1.11 1.03 1.03 1.03 1.03 1.03 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.46 1.46 1.46 1.46 1.38 1.38 1.38 1.38 1.29 1.29 1.29 1.29 1.20 1.20 1.20 1.20 1.11 1.11 1.11 1.11 1.03 1.03 1.03 1.03 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3516

0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.36 1.27 1.19 1.10 1.02 1.00 1.00 1.00 1.00 0

1.42 1.34 1.25 1.16 1.08 1.00 1.00 1.00 1.00 1000

1.46 1.38 1.29 1.20 1.11 1.03 1.00 1.00 1.00 2000

DM0991-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM0991-00

-ENGLISH- page 2 of 2

55

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 260 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

NAT GAS 920 DELTEC 1.5 80 1641

100%

75%

50%

1354 975

1016 731

677 488

6965 2885 12792 76.4 300 70.9 135 19 1033 8708 13262

7210 2183 9682 65.7 260 54.1 134 19 1029 6579 10042

7617 1495 6630 47.9 187 37.2 131 19 1050 4570 6883

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

1.1 91

1.1 91

1.2 91

(Corr. 15% 02)

g/bhp-hr ppm

2.7 367

2.8 359

2.9 359

(Corr. 15% 02)

g/bhp-hr ppm

3.4 733

3.9 811

4.6 881

(Corr. 15% 02)

g/bhp-hr ppm

0.51 58

0.59 63

0.70 67

%

9.6 1.68

9.4 1.66

9.1 1.62

157220 57465 18956 5801 7052 59153 46951 8781

122056 43099 17658 5004 6254 44941 35416 5099

85969 28732 14750 4038 5150 31742 24965 1557

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 56

DM0876-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 70 0.95/16* 1.0/16*

75 1.0/18

80 to 100 1.0/19

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 1000

0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 1.00 2000

0.83 0.80 0.77 0.75 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.89 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.81 0.78 0.93 0.89 0.86 0.83 0.80 0.95 0.91 0.88 0.85 0.81 0.97 0.93 0.90 0.86 0.83 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.75 0.73 0.70 0.67 0.77 0.74 0.71 0.68 0.78 0.75 0.72 0.70 0.80 0.77 0.74 0.71 9000 10000 11000 12000

1.46 1.37 1.28 1.20 1.11 1.03 1.00 1.00 1.00 3000

1.46 1.46 1.46 1.46 1.46 1.37 1.37 1.37 1.37 1.37 1.28 1.28 1.28 1.28 1.28 1.20 1.20 1.20 1.20 1.20 1.11 1.11 1.11 1.11 1.11 1.03 1.03 1.03 1.03 1.03 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.46 1.46 1.46 1.46 1.37 1.37 1.37 1.37 1.28 1.28 1.28 1.28 1.20 1.20 1.20 1.20 1.11 1.11 1.11 1.11 1.03 1.03 1.03 1.03 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3516

0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.36 1.27 1.19 1.10 1.02 1.00 1.00 1.00 1.00 0

1.42 1.33 1.25 1.16 1.08 1.00 1.00 1.00 1.00 1000

1.46 1.37 1.28 1.20 1.11 1.03 1.00 1.00 1.00 2000

DM0876-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM0876-00

-ENGLISH- page 2 of 2

57

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

NAT GAS 920 DELTEC 1.5 80 1149

100%

75%

50%

1354 975

1016 731

677 488

6953 2999 13301 74.8 305 70.3 137 22 921 8361 13763

7209 2293 10168 64.3 259 55 134 22 934 6452 10525

7693 1592 7059 48.2 189 38.8 132 22 954 4546 7312

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

0.6 46

0.6 46

0.6 46

(Corr. 15% 02)

g/bhp-hr ppm

2.6 355

2.7 340

2.7 325

(Corr. 15% 02)

g/bhp-hr ppm

6.6 1575

7.6 1729

8.6 1848

(Corr. 15% 02)

g/bhp-hr ppm

1.00 131

1.15 141

1.29 148

%

10.2 1.77

10.0 1.75

9.8 1.72

156936 57465 29262 4722 0 56327 42786 9160

122047 43099 25465 4040 0 44265 33341 5178

86822 28732 20937 3812 0 31691 23896 1650

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 58

DM1228-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 70 0.90/18* 0.95/18*

75 1.0/20

80 to 100 1.0/22

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 0

0.92 0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1000

0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 2000

0.82 0.79 0.76 0.73 0.70 0.83 0.80 0.77 0.74 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.90 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.81 0.78 0.93 0.90 0.86 0.83 0.80 0.95 0.91 0.88 0.85 0.82 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.68 0.65 0.63 0.60 0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.75 0.73 0.70 0.67 0.77 0.74 0.71 0.68 0.78 0.75 0.73 0.70 9000 10000 11000 12000

1.42 1.33 1.25 1.17 1.08 1.00 1.00 1.00 1.00 3000

1.42 1.42 1.42 1.42 1.42 1.33 1.33 1.33 1.33 1.33 1.25 1.25 1.25 1.25 1.25 1.17 1.17 1.17 1.17 1.17 1.08 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.42 1.42 1.42 1.42 1.33 1.33 1.33 1.33 1.25 1.25 1.25 1.25 1.17 1.17 1.17 1.17 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3516

0.85 0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.35 1.26 1.18 1.10 1.01 1.00 1.00 1.00 1.00 0

1.41 1.33 1.24 1.16 1.07 1.00 1.00 1.00 1.00 1000

1.42 1.33 1.25 1.17 1.08 1.00 1.00 1.00 1.00 2000

DM1228-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1228-00

-ENGLISH- page 2 of 2

59

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 260 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

NAT GAS 920 DELTEC 1.5 80 1149

100%

75%

50%

1354 975

1016 731

677 488

7035 2970 13172 75.5 315 71.6 137 18 982 8654 13641

7258 2266 10049 65.8 273 55.2 134 18 995 6663 10412

7824 1573 6973 48.8 203 38.9 131 18 1013 4685 7232

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

0.6 46

0.6 46

0.6 46

(Corr. 15% 02)

g/bhp-hr ppm

2.5 333

2.5 326

2.6 315

(Corr. 15% 02)

g/bhp-hr ppm

5.0 1199

5.6 1288

6.4 1386

(Corr. 15% 02)

g/bhp-hr ppm

0.76 97

0.84 102

0.96 108

%

9.9 1.73

9.7 1.71

9.5 1.66

158794 57465 18698 5741 8765 58536 46400 9617

123849 43099 16337 5143 8102 45425 35892 5764

88308 28732 13587 4356 7537 32080 25327 2030

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 60

DM1240-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/--

70 0/--

75 0.90/16

80 to 100 1.0/18

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 0

0.92 0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1000

0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 2000

0.82 0.79 0.76 0.73 0.70 0.83 0.80 0.77 0.74 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.90 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.81 0.78 0.93 0.90 0.86 0.83 0.80 0.95 0.91 0.88 0.85 0.82 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.68 0.65 0.63 0.60 0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.75 0.73 0.70 0.67 0.77 0.74 0.71 0.68 0.78 0.75 0.73 0.70 9000 10000 11000 12000

1.40 1.32 1.24 1.16 1.08 1.00 1.00 1.00 1.00 3000

1.40 1.40 1.40 1.40 1.40 1.32 1.32 1.32 1.32 1.32 1.24 1.24 1.24 1.24 1.24 1.16 1.16 1.16 1.16 1.16 1.08 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.40 1.40 1.40 1.40 1.32 1.32 1.32 1.32 1.24 1.24 1.24 1.24 1.16 1.16 1.16 1.16 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3516

0.85 0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.33 1.25 1.17 1.09 1.01 1.00 1.00 1.00 1.00 0

1.39 1.31 1.23 1.15 1.07 1.00 1.00 1.00 1.00 1000

1.40 1.32 1.24 1.16 1.08 1.00 1.00 1.00 1.00 2000

DM1240-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1240-00

-ENGLISH- page 2 of 2

61

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

NAT GAS 920 DELTEC 1.5 80 1641

100%

75%

50%

1354 975

1016 731

677 488

6714 2781 12334 73.7 302 66.6 142 22 950 7930 12786

6977 2105 9333 59.8 244 50.3 135 22 963 6059 9683

7396 1443 6400 45.6 180 36.4 131 22 981 4212 6647

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

1.1 91

1.1 91

1.2 91

(Corr. 15% 02)

g/bhp-hr ppm

2.3 312

2.4 315

2.5 310

(Corr. 15% 02)

g/bhp-hr ppm

5.3 1259

5.7 1350

6.7 1464

(Corr. 15% 02)

g/bhp-hr ppm

0.80 98

0.87 103

1.00 109

%

9.5 1.68

9.2 1.64

9.0 1.60

151560 57465 28317 4208 0 53474 41562 8123

117819 43099 25148 3750 0 41596 32320 4246

83891 28732 21558 3076 0 29257 22639 1281

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 62

DM1231-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 70 0.90/18* 0.95/18*

75 1.0/20

80 to 100 1.0/22

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 1000

0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 1.00 2000

0.83 0.80 0.77 0.75 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.89 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.81 0.78 0.93 0.89 0.86 0.83 0.80 0.95 0.91 0.88 0.85 0.81 0.97 0.93 0.90 0.86 0.83 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.75 0.73 0.70 0.67 0.77 0.74 0.71 0.68 0.78 0.75 0.72 0.70 0.80 0.77 0.74 0.71 9000 10000 11000 12000

1.47 1.38 1.29 1.20 1.12 1.03 1.00 1.00 1.00 3000

1.47 1.47 1.47 1.47 1.47 1.38 1.38 1.38 1.38 1.38 1.29 1.29 1.29 1.29 1.29 1.20 1.20 1.20 1.20 1.20 1.12 1.12 1.12 1.12 1.12 1.03 1.03 1.03 1.03 1.03 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.47 1.47 1.47 1.47 1.38 1.38 1.38 1.38 1.29 1.29 1.29 1.29 1.20 1.20 1.20 1.20 1.12 1.12 1.12 1.12 1.03 1.03 1.03 1.03 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3516

0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.36 1.27 1.19 1.10 1.01 1.00 1.00 1.00 1.00 0

1.42 1.34 1.25 1.16 1.08 1.00 1.00 1.00 1.00 1000

1.47 1.38 1.29 1.20 1.12 1.03 1.00 1.00 1.00 2000

DM1231-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1231-00

-ENGLISH- page 2 of 2

63

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 260 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

NAT GAS 920 DELTEC 1.5 80 1641

100%

75%

50%

1354 975

1016 731

677 488

6762 2817 12491 72.6 298 67.4 135 17 997 8292 12942

7051 2150 9533 63.4 259 52.5 134 17 1002 6356 9883

7505 1483 6577 47.1 187 36.8 131 17 1031 4476 6825

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

1.1 91

1.1 91

1.2 91

(Corr. 15% 02)

g/bhp-hr ppm

2.6 352

2.6 348

2.8 351

(Corr. 15% 02)

g/bhp-hr ppm

4.1 1000

4.7 1105

5.1 1155

(Corr. 15% 02)

g/bhp-hr ppm

0.61 79

0.71 86

0.77 87

%

9.6 1.71

9.4 1.68

9.1 1.63

152949 57465 18644 5628 8211 54719 43818 8309

119730 43099 16111 4865 7885 42876 34191 4914

85123 28732 13371 4056 7350 30135 24098 1492

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 64

DM1243-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/--

70 0/--

75 0.90/16*

80 to 100 1.0/17

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 1000

0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 1.00 2000

0.83 0.80 0.77 0.75 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.89 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.81 0.78 0.93 0.89 0.86 0.83 0.80 0.95 0.91 0.88 0.85 0.81 0.97 0.93 0.90 0.86 0.83 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.75 0.73 0.70 0.67 0.77 0.74 0.71 0.68 0.78 0.75 0.72 0.70 0.80 0.77 0.74 0.71 9000 10000 11000 12000

1.46 1.37 1.29 1.20 1.11 1.03 1.00 1.00 1.00 3000

1.46 1.46 1.46 1.46 1.46 1.37 1.37 1.37 1.37 1.37 1.29 1.29 1.29 1.29 1.29 1.20 1.20 1.20 1.20 1.20 1.11 1.11 1.11 1.11 1.11 1.03 1.03 1.03 1.03 1.03 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.46 1.46 1.46 1.46 1.37 1.37 1.37 1.37 1.29 1.29 1.29 1.29 1.20 1.20 1.20 1.20 1.11 1.11 1.11 1.11 1.03 1.03 1.03 1.03 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3516

0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.35 1.27 1.18 1.10 1.01 1.00 1.00 1.00 1.00 0

1.42 1.33 1.25 1.16 1.07 1.00 1.00 1.00 1.00 1000

1.46 1.37 1.29 1.20 1.11 1.03 1.00 1.00 1.00 2000

DM1243-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1243-00

-ENGLISH- page 2 of 2

65

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 8.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 HPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

35 80 4922

100%

75%

50%

1356 970

1017 728

678 485

7976 2842 12602 75.4 299 67.3 144 33 905 7886 13135

8046 2036 9028 66.7 267 50.3 139 33 901 5647 9432

8586 1417 6281 49.5 198 36.5 135 33 901 3933 6568

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 131

4.2 292

3.2 217

(Corr. 15% 02)

g/bhp-hr ppm

1.7 198

1.9 220

2.0 220

(Corr. 15% 02)

g/bhp-hr ppm

2.2 470

1.8 360

2.1 414

(Corr. 15% 02)

g/Btu-hr ppm

0.34 32

0.27 23

0.33 26

%

7.8 1.46

6.7 1.38

6.5 1.35

180226 57522 58675 5693 0 50254 32918 8077

136350 43141 47698 4744 0 35825 23563 4938

97002 28761 37448 3796 0 25107 16432 1887

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 66

DM5156-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 35 0.90/19 0.90/21

40 0.90/22

45 1.0/23

50 1.0/24

55 1.0/26

60 1.0/27

65 1.0/28

70 1.0/30

75 1.0/31

80 to 100 1.0/33

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.94 0.91 0.87 0.84 0.81 0.96 0.92 0.89 0.86 0.82 0.98 0.94 0.90 0.87 0.84 0.99 0.96 0.92 0.89 0.85 1.00 0.97 0.94 0.90 0.87 1.00 0.99 0.95 0.92 0.89 1.00 1.00 0.97 0.94 0.90 1.00 1.00 0.99 0.95 0.92 1.00 1.00 1.00 0.97 0.94 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.78 0.75 0.72 0.69 0.79 0.76 0.73 0.71 0.81 0.78 0.75 0.72 0.82 0.79 0.76 0.73 0.84 0.80 0.77 0.74 0.85 0.82 0.79 0.76 0.87 0.83 0.80 0.77 0.88 0.85 0.82 0.79 0.90 0.87 0.83 0.80 9000 10000 11000 12000

1.56 1.47 1.38 1.29 1.20 1.11 1.02 1.00 1.00 3000

1.62 1.69 1.69 1.69 1.69 1.53 1.59 1.59 1.59 1.59 1.44 1.50 1.50 1.50 1.50 1.35 1.41 1.41 1.41 1.41 1.26 1.32 1.32 1.32 1.32 1.17 1.23 1.23 1.23 1.23 1.08 1.14 1.14 1.14 1.14 1.00 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.69 1.69 1.69 1.69 1.59 1.59 1.59 1.59 1.50 1.50 1.50 1.50 1.41 1.41 1.41 1.41 1.32 1.32 1.32 1.32 1.23 1.23 1.23 1.23 1.14 1.14 1.14 1.14 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3516

0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.36 1.27 1.19 1.10 1.02 1.00 1.00 1.00 1.00 0

1.42 1.34 1.25 1.16 1.08 1.00 1.00 1.00 1.00 1000

1.49 1.40 1.31 1.23 1.14 1.05 1.00 1.00 1.00 2000

DM5156-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5156-00

-ENGLISH- page 2 of 2

67

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 HPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

30 80 4922

100%

75%

50%

1356 970

1017 728

678 485

7490 2656 11780 73.7 314 65.8 140 18 840 7022 12280

7662 1974 8755 63 265 49.8 138 18 844 5241 9140

8083 1261 5591 46 189 33.6 138 18 864 3412 5861

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 148

2.4 177

4.7 331

(Corr. 15% 02)

g/bhp-hr ppm

1.6 198

1.6 195

1.7 196

(Corr. 15% 02)

g/bhp-hr ppm

2.6 562

2.6 550

2.5 507

(Corr. 15% 02)

g/ -hr ppm

0.39 37

0.39 35

0.38 29

%

7.4 1.45

6.8 1.40

5.4 1.28

169224 57522 53793 5693 0 43662 27081 8550

129837 43141 44425 4744 0 32744 20353 4779

91315 28761 35685 3796 0 21672 13678 1399

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 68

DM5157-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/--

70 1.0/15

75 1.0/16

80 1.0/17

83 to 100 1.0/18

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.94 0.91 0.87 0.84 0.81 0.96 0.92 0.89 0.86 0.82 0.98 0.94 0.90 0.87 0.84 0.99 0.96 0.92 0.89 0.85 1.00 0.97 0.94 0.90 0.87 1.00 0.99 0.95 0.92 0.89 1.00 1.00 0.97 0.94 0.90 1.00 1.00 0.99 0.95 0.92 1.00 1.00 1.00 0.97 0.94 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.78 0.75 0.72 0.69 0.79 0.76 0.73 0.71 0.81 0.78 0.75 0.72 0.82 0.79 0.76 0.73 0.84 0.80 0.77 0.74 0.85 0.82 0.79 0.76 0.87 0.83 0.80 0.77 0.88 0.85 0.82 0.79 0.90 0.87 0.83 0.80 9000 10000 11000 12000

1.51 1.43 1.35 1.27 1.18 1.10 1.02 1.00 1.00 3000

1.57 1.63 1.63 1.63 1.63 1.49 1.55 1.55 1.55 1.55 1.41 1.47 1.47 1.47 1.47 1.33 1.38 1.38 1.38 1.38 1.24 1.30 1.30 1.30 1.30 1.16 1.22 1.22 1.22 1.22 1.08 1.14 1.14 1.14 1.14 1.00 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.63 1.63 1.63 1.63 1.55 1.55 1.55 1.55 1.47 1.47 1.47 1.47 1.38 1.38 1.38 1.38 1.30 1.30 1.30 1.30 1.22 1.22 1.22 1.22 1.14 1.14 1.14 1.14 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3516

0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.32 1.24 1.16 1.09 1.01 1.00 1.00 1.00 1.00 0

1.38 1.30 1.22 1.15 1.07 1.00 1.00 1.00 1.00 1000

1.44 1.36 1.28 1.20 1.13 1.05 1.00 1.00 1.00 2000

DM5157-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5157-00 69

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 LPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp Kw

1.5 80 5000

100%

75%

50%

1356 970

1017 728

678 485

7255 2765 12260 71.7 302 65.3 142 18 847 7332 12750

7636 2094 9284 66.8 266 50.1 133 18 847 5561 9671

8136 1330 5896 48.5 192 32.9 118 18 865 3597 6170

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 151

2.3 168

6.7 459

(Corr. 15% 02)

g/bhp-hr ppm

1.9 241

2.1 253

2.3 254

(Corr. 15% 02)

g/bhp-hr ppm

2.8 611

2.8 584

2.4 471

(Corr. 15% 02)

g/bhp-hr ppm

0.42 43

0.42 39

0.36 28

%

8.1 1.55

7.6 1.48

5.9 1.33

163925 57522 46353 5693 0 45689 28436 8665

129402 43141 41542 4744 0 34723 21626 5247

91912 28761 35064 3796 0 22721 14417 1568

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 70

DM5158-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/--

70 1.0/15

75 1.0/16

80 1.0/17

83 to 100 1.0/18

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.94 0.91 0.88 0.84 0.81 0.96 0.93 0.89 0.86 0.83 0.98 0.94 0.91 0.87 0.84 1.00 0.96 0.92 0.89 0.86 1.00 0.98 0.94 0.91 0.87 1.00 0.99 0.96 0.92 0.89 1.00 1.00 0.98 0.94 0.90 1.00 1.00 0.99 0.96 0.92 1.00 1.00 1.00 0.98 0.94 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.78 0.75 0.72 0.70 0.80 0.77 0.74 0.71 0.81 0.78 0.75 0.72 0.82 0.79 0.76 0.73 0.84 0.81 0.78 0.75 0.85 0.82 0.79 0.76 0.87 0.84 0.81 0.77 0.89 0.85 0.82 0.79 0.90 0.87 0.84 0.80 9000 10000 11000 12000

1.53 1.45 1.36 1.28 1.19 1.11 1.02 1.00 1.00 3000

1.60 1.67 1.67 1.67 1.67 1.52 1.58 1.58 1.58 1.58 1.43 1.50 1.50 1.50 1.50 1.34 1.41 1.41 1.41 1.41 1.26 1.32 1.32 1.32 1.32 1.17 1.23 1.23 1.23 1.23 1.08 1.15 1.15 1.15 1.15 1.00 1.06 1.06 1.06 1.06 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.67 1.67 1.67 1.67 1.58 1.58 1.58 1.58 1.50 1.50 1.50 1.50 1.41 1.41 1.41 1.41 1.32 1.32 1.32 1.32 1.23 1.23 1.23 1.23 1.15 1.15 1.15 1.15 1.06 1.06 1.06 1.06 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3516

0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.34 1.26 1.17 1.09 1.01 1.00 1.00 1.00 1.00 0

1.40 1.32 1.24 1.15 1.07 1.00 1.00 1.00 1.00 1000

1.47 1.38 1.30 1.22 1.13 1.05 1.00 1.00 1.00 2000

DM5158-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5158-00

-ENGLISH- page 2 of 2

71

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°F) 90 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

NAT GAS 920 DELTEC 1.5 80 1149

100%

75%

50%

1435 1030

1076 773

717 515

6732 3028 13428 75.3 308 69.9 104 24 905 8347 13904

7110 2363 10481 65.1 260 54.1 98 24 918 6577 10855

7614 1654 7333 48.9 192 38.8 92 24 932 4653 7599

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

0.6 46

0.6 46

0.6 46

(Corr. 15% 02)

g/bhp-hr ppm

2.6 351

2.6 337

2.6 325

(Corr. 15% 02)

g/bhp-hr ppm

6.6 1583

7.4 1730

9.1 1997

(Corr. 15% 02)

g/bhp-hr ppm

0.99 128

1.12 138

1.37 158

%

9.9 1.74

9.8 1.73

9.7 1.70

160986 60879 29133 4381 0 56156 42160 11260

127526 45659 24960 4040 0 44834 33569 6998

91033 30439 20920 3641 0 32488 24067 3015

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 72

DM5166-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/18*

70 1.0/20*

75 1.0/22

80 to 100 1.0/24

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 0

0.92 0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1000

0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 2000

0.82 0.79 0.76 0.73 0.70 0.83 0.80 0.77 0.74 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.90 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.81 0.78 0.93 0.90 0.86 0.83 0.80 0.95 0.91 0.88 0.85 0.82 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.68 0.65 0.63 0.60 0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.75 0.73 0.70 0.67 0.77 0.74 0.71 0.68 0.78 0.75 0.73 0.70 9000 10000 11000 12000

1.35 1.28 1.21 1.14 1.07 1.00 1.00 1.00 1.00 3000

1.35 1.35 1.35 1.35 1.35 1.28 1.28 1.28 1.28 1.28 1.21 1.21 1.21 1.21 1.21 1.14 1.14 1.14 1.14 1.14 1.07 1.07 1.07 1.07 1.07 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.35 1.35 1.35 1.35 1.28 1.28 1.28 1.28 1.21 1.21 1.21 1.21 1.14 1.14 1.14 1.14 1.07 1.07 1.07 1.07 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3516

0.85 0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.29 1.22 1.15 1.08 1.01 1.00 1.00 1.00 1.00 0

1.34 1.27 1.20 1.13 1.06 1.00 1.00 1.00 1.00 1000

1.35 1.28 1.21 1.14 1.07 1.00 1.00 1.00 1.00 2000

DM5166-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM5166-00

-ENGLISH- page 2 of 2

73

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°F) 90 Jacket Water Outlet Temperature (°F) 260 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

NAT GAS 920 DELTEC 1.5 80 1149

100%

75%

50%

1435 1030

1076 773

717 515

6831 3083 13673 77.2 318 72.3 106 20 957 8823 14155

7046 2343 10390 66.9 270 55 99 20 966 6750 10761

7406 1618 7173 49.1 195 38.4 94 20 991 4747 7436

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

0.6 46

0.6 46

0.6 46

(Corr. 15% 02)

g/bhp-hr ppm

2.5 336

2.5 329

2.6 323

(Corr. 15% 02)

g/bhp-hr ppm

5.5 1346

5.9 1395

6.5 1447

(Corr. 15% 02)

g/bhp-hr ppm

0.83 109

0.89 111

0.98 112

%

9.9 1.75

9.7 1.72

9.5 1.69

163352 60879 17950 5485 8394 58742 45575 11931

126880 45659 15430 4972 7973 45596 35412 7272

89875 30439 12719 4045 7348 32375 25204 2964

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 74

DM5161-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 .95/16*

70 1.0/16*

75 1.0/18

80 to 100 1.0/20

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 0

0.92 0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1000

0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 2000

0.82 0.79 0.76 0.73 0.70 0.83 0.80 0.77 0.74 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.90 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.81 0.78 0.93 0.90 0.86 0.83 0.80 0.95 0.91 0.88 0.85 0.82 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.68 0.65 0.63 0.60 0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.75 0.73 0.70 0.67 0.77 0.74 0.71 0.68 0.78 0.75 0.73 0.70 9000 10000 11000 12000

1.34 1.27 1.20 1.13 1.07 1.00 1.00 1.00 1.00 3000

1.34 1.34 1.34 1.34 1.34 1.27 1.27 1.27 1.27 1.27 1.20 1.20 1.20 1.20 1.20 1.13 1.13 1.13 1.13 1.13 1.07 1.07 1.07 1.07 1.07 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.34 1.34 1.34 1.34 1.27 1.27 1.27 1.27 1.20 1.20 1.20 1.20 1.13 1.13 1.13 1.13 1.07 1.07 1.07 1.07 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3516

0.85 0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.28 1.21 1.14 1.08 1.01 1.00 1.00 1.00 1.00 0

1.33 1.26 1.19 1.13 1.06 1.00 1.00 1.00 1.00 1000

1.34 1.27 1.20 1.13 1.07 1.00 1.00 1.00 1.00 2000

DM5161-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM5161-00

-ENGLISH- page 2 of 2

75

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°F) 90 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

NAT GAS 920 DELTEC 1.5 80 1641

100%

75%

50%

1435 1030

1076 773

717 515

6559 2869 12724 74.9 306 67.7 106 24 912 7962 13193

6872 2193 9725 61.6 250 51.5 99 24 934 6186 10091

7272 1494 6625 46.8 183 36.2 92 24 937 4230 6882

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

1.1 91

1.1 91

1.2 91

(Corr. 15% 02)

g/bhp-hr ppm

2.5 332

2.4 315

2.3 298

(Corr. 15% 02)

g/bhp-hr ppm

5.4 1139

6.0 1240

6.8 1340

(Corr. 15% 02)

g/bhp-hr ppm

0.82 88

0.91 94

1.03 99

%

9.4 1.67

9.2 1.64

8.9 1.59

156845 60879 27820 4606 0 53116 40491 4044 6543

123235 45659 25072 4493 0 41969 32074 1284 4844

86953 30439 21004 3981 0 29060 22008 -597 3110

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8) Heat Rejection to Aftercooler - stage 2 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 76

DM5162-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/18*

70 1.0/20*

75 1.0/22

80 to 100 1.0/24

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 1000

0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 1.00 2000

0.83 0.80 0.77 0.75 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.89 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.81 0.78 0.93 0.89 0.86 0.83 0.80 0.95 0.91 0.88 0.85 0.81 0.97 0.93 0.90 0.86 0.83 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.75 0.73 0.70 0.67 0.77 0.74 0.71 0.68 0.78 0.75 0.72 0.70 0.80 0.77 0.74 0.71 9000 10000 11000 12000

1.38 1.31 1.24 1.16 1.09 1.02 1.00 1.00 1.00 3000

1.38 1.38 1.38 1.38 1.38 1.31 1.31 1.31 1.31 1.31 1.24 1.24 1.24 1.24 1.24 1.16 1.16 1.16 1.16 1.16 1.09 1.09 1.09 1.09 1.09 1.02 1.02 1.02 1.02 1.02 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.38 1.38 1.38 1.38 1.31 1.31 1.31 1.31 1.24 1.24 1.24 1.24 1.16 1.16 1.16 1.16 1.09 1.09 1.09 1.09 1.02 1.02 1.02 1.02 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3516

0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.29 1.22 1.15 1.08 1.01 1.00 1.00 1.00 1.00 0

1.34 1.27 1.20 1.13 1.06 1.00 1.00 1.00 1.00 1000

1.38 1.31 1.24 1.16 1.09 1.02 1.00 1.00 1.00 2000

DM5162-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM5162-00

-ENGLISH- page 2 of 2

77

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°F) 90 Jacket Water Outlet Temperature (°F) 260 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

NAT GAS 920 DELTEC 1.5 80 1641

100%

75%

50%

1435 1030

1076 773

717 515

6668 2911 12912 74.1 304 68.3 104 20 970 8416 13383

6977 2240 9932 64.5 264 52.7 98 20 981 6526 10299

7441 1558 6910 48 196 37.2 93 20 999 4600 7170

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

1.1 91

1.1 91

1.2 90

(Corr. 15% 02)

g/bhp-hr ppm

2.6 353

2.6 348

2.7 344

(Corr. 15% 02)

g/bhp-hr ppm

4.2 1032

4.9 1162

5.6 1257

(Corr. 15% 02)

g/bhp-hr ppm

0.64 81

0.73 90

0.84 95

%

9.6 1.69

9.4 1.67

9.1 1.64

159461 60879 18482 5459 8473 55561 43960 10635

125112 45659 15980 4948 8075 43619 34406 6824

89000 30439 13137 3867 7450 31164 24511 2900

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 78

DM5163-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 70 0.90/16* 0.90/18*

75 1.0/18

80 to 100 1.0/20

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 1000

0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 1.00 2000

0.83 0.80 0.77 0.75 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.89 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.81 0.78 0.93 0.89 0.86 0.83 0.80 0.95 0.91 0.88 0.85 0.81 0.97 0.93 0.90 0.86 0.83 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.75 0.73 0.70 0.67 0.77 0.74 0.71 0.68 0.78 0.75 0.72 0.70 0.80 0.77 0.74 0.71 9000 10000 11000 12000

1.38 1.31 1.24 1.16 1.09 1.02 1.00 1.00 1.00 3000

1.38 1.38 1.38 1.38 1.38 1.31 1.31 1.31 1.31 1.31 1.24 1.24 1.24 1.24 1.24 1.16 1.16 1.16 1.16 1.16 1.09 1.09 1.09 1.09 1.09 1.02 1.02 1.02 1.02 1.02 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.38 1.38 1.38 1.38 1.31 1.31 1.31 1.31 1.24 1.24 1.24 1.24 1.16 1.16 1.16 1.16 1.09 1.09 1.09 1.09 1.02 1.02 1.02 1.02 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3516

0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.29 1.22 1.15 1.08 1.01 1.00 1.00 1.00 1.00 0

1.34 1.27 1.20 1.13 1.06 1.00 1.00 1.00 1.00 1000

1.38 1.31 1.24 1.16 1.09 1.02 1.00 1.00 1.00 2000

DM5163-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM5163-00

-ENGLISH- page 2 of 2

79

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°F) 158/90 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp bhp

NAT GAS 920 DELTEC 1.5 80 1149

100%

75%

50%

1435 1030

1076 773

717 515

6732 3028 13428 75.3 308 69.9 104 24 905 8346 13902

7110 2363 10481 65.1 260 54.1 98 24 918 6576 10854

7614 1654 7333 48.9 192 38.8 92 24 932 4652 7599

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

0.6 46

0.6 46

0.6 46

(Corr. 15% 02)

g/bhp-hr ppm

2.6 351

2.6 337

2.6 325

(Corr. 15% 02)

g/bhp-hr ppm

6.6 1583

7.4 1730

9.1 1997

(Corr. 15% 02)

g/bhp-hr ppm

0.99 128

1.12 138

1.38 158

%

9.9 1.74

9.8 1.74

9.7 1.71

160986 60879 29133 4381 0 56156 42160 7248 4012

127526 45659 24960 4040 0 44834 33569 3845 3153

91033 30439 20920 3641 0 32488 24067 898 2117

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8) Heat Rejection to Aftercooler - stage 2 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 80

DM1229-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55

60 0/--

65 1.0/18*

70 1.0/20*

75 1.0/22

80 to 100 1.0/24

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 0

0.92 0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1000

0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 2000

0.82 0.79 0.76 0.73 0.70 0.83 0.80 0.77 0.74 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.90 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.81 0.78 0.93 0.90 0.86 0.83 0.80 0.95 0.91 0.88 0.85 0.82 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.68 0.65 0.63 0.60 0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.75 0.73 0.70 0.67 0.77 0.74 0.71 0.68 0.78 0.75 0.73 0.70 9000 10000 11000 12000

1.35 1.28 1.21 1.14 1.07 1.00 1.00 1.00 1.00 3000

1.35 1.35 1.35 1.35 1.35 1.28 1.28 1.28 1.28 1.28 1.21 1.21 1.21 1.21 1.21 1.14 1.14 1.14 1.14 1.14 1.07 1.07 1.07 1.07 1.07 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.35 1.35 1.35 1.35 1.28 1.28 1.28 1.28 1.21 1.21 1.21 1.21 1.14 1.14 1.14 1.14 1.07 1.07 1.07 1.07 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3516

0.85 0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.29 1.22 1.15 1.08 1.01 1.00 1.00 1.00 1.00 0

1.34 1.27 1.20 1.13 1.06 1.00 1.00 1.00 1.00 1000

1.35 1.28 1.21 1.14 1.07 1.00 1.00 1.00 1.00 2000

DM1229-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1229-00

-ENGLISH- page 2 of 2

81

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°F) 158/90 Jacket Water Outlet Temperature (°F) 260 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

NAT GAS 920 DELTEC 1.5 80 1149

100%

75%

50%

1435 1030

1076 773

717 515

6831 3083 13673 77.2 318 72.3 106 20 957 8823 14155

7046 2343 10390 66.9 270 55 99 20 966 6750 10761

7406 1618 7173 49.1 195 38.4 94 20 991 4747 7436

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

0.6 46

0.6 46

0.6 46

(Corr. 15% 02)

g/bhp-hr ppm

2.5 336

2.5 329

2.6 323

(Corr. 15% 02)

g/bhp-hr ppm

5.5 1346

5.9 1395

6.5 1447

(Corr. 15% 02)

g/bhp-hr ppm

0.83 109

0.89 111

0.98 112

%

9.9 1.75

9.7 1.72

9.5 1.69

163352 60879 17950 5485 8394 58742 45575 7199 4732

126880 45659 15430 4972 7973 45596 35412 3813 3459

89875 30439 12719 4045 7348 32375 25204 871 2093

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8) Heat Rejection to Aftercooler - stage 2 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 82

DM1241-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 .95/16*

70 1.0/16*

75 1.0/18

80 to 100 1.0/20

* Denotes Air Fuel Ratio Control required for Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 0

0.92 0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1000

0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 2000

0.82 0.79 0.76 0.73 0.70 0.83 0.80 0.77 0.74 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.90 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.81 0.78 0.93 0.90 0.86 0.83 0.80 0.95 0.91 0.88 0.85 0.82 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.68 0.65 0.63 0.60 0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.75 0.73 0.70 0.67 0.77 0.74 0.71 0.68 0.78 0.75 0.73 0.70 9000 10000 11000 12000

1.34 1.27 1.20 1.13 1.07 1.00 1.00 1.00 1.00 3000

1.34 1.34 1.34 1.34 1.34 1.27 1.27 1.27 1.27 1.27 1.20 1.20 1.20 1.20 1.20 1.13 1.13 1.13 1.13 1.13 1.07 1.07 1.07 1.07 1.07 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.34 1.34 1.34 1.34 1.27 1.27 1.27 1.27 1.20 1.20 1.20 1.20 1.13 1.13 1.13 1.13 1.07 1.07 1.07 1.07 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3516

0.85 0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.28 1.21 1.14 1.08 1.01 1.00 1.00 1.00 1.00 0

1.33 1.26 1.19 1.13 1.06 1.00 1.00 1.00 1.00 1000

1.34 1.27 1.20 1.13 1.07 1.00 1.00 1.00 1.00 2000

DM1241-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1241-00

-ENGLISH- page 2 of 2

83

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°F) 158/90 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

NAT GAS 920 DELTEC 1.5 80 1641

100%

75%

50%

1435 1030

1076 773

717 515

6559 2869 12724 74.9 306 67.7 106 24 912 7962 13192

6872 2193 9725 61.6 250 51.5 99 24 934 6186 10090

7272 1494 6625 46.8 183 36.2 92 24 937 4230 6882

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

1.1 91

1.1 91

1.2 91

(Corr. 15% 02)

g/bhp-hr ppm

2.5 332

2.4 315

2.4 298

(Corr. 15% 02)

g/bhp-hr ppm

5.5 1139

6.1 1240

6.9 1340

(Corr. 15% 02)

g/bhp-hr ppm

0.83 88

0.92 94

1.04 99

%

9.4 1.68

9.2 1.64

8.9 1.59

156845 60879 27820 4606 0 53116 40491 6257 4330

123235 45659 25072 4493 0 41969 32074 2976 3151

86953 30439 21004 3981 0 29060 22008 557 1955

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8) Heat Rejection to Aftercooler - stage 2 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 84

DM1232-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/18*

70 1.0/20*

75 1.0/22

80 to 100 1.0/24

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 1000

0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 1.00 2000

0.83 0.80 0.77 0.75 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.89 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.81 0.78 0.93 0.89 0.86 0.83 0.80 0.95 0.91 0.88 0.85 0.81 0.97 0.93 0.90 0.86 0.83 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.75 0.73 0.70 0.67 0.77 0.74 0.71 0.68 0.78 0.75 0.72 0.70 0.80 0.77 0.74 0.71 9000 10000 11000 12000

1.38 1.31 1.24 1.16 1.09 1.02 1.00 1.00 1.00 3000

1.38 1.38 1.38 1.38 1.38 1.31 1.31 1.31 1.31 1.31 1.24 1.24 1.24 1.24 1.24 1.16 1.16 1.16 1.16 1.16 1.09 1.09 1.09 1.09 1.09 1.02 1.02 1.02 1.02 1.02 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.38 1.38 1.38 1.38 1.31 1.31 1.31 1.31 1.24 1.24 1.24 1.24 1.16 1.16 1.16 1.16 1.09 1.09 1.09 1.09 1.02 1.02 1.02 1.02 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3516

0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.29 1.22 1.15 1.08 1.01 1.00 1.00 1.00 1.00 0

1.34 1.27 1.20 1.13 1.06 1.00 1.00 1.00 1.00 1000

1.38 1.31 1.24 1.16 1.09 1.02 1.00 1.00 1.00 2000

DM1232-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 8

DM1232-00

-ENGLISH- page 2 of 2

85

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°F) 158/90 Jacket Water Outlet Temperature (°F) 260 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

NAT GAS 920 DELTEC 1.5 80 1641

100%

75%

50%

1435 1030

1076 773

717 515

6668 2911 12912 74.1 304 68.3 104 20 970 8416 13383

6977 2240 9932 64.5 264 52.7 98 20 981 6526 10299

7441 1558 6910 48 196 37.2 93 20 999 4600 7170

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

1.1 91

1.1 91

1.2 90

(Corr. 15% 02)

g/bhp-hr ppm

2.6 353

2.6 348

2.7 344

(Corr. 15% 02)

g/bhp-hr ppm

4.2 1032

4.9 1162

5.6 1257

(Corr. 15% 02)

g/bhp-hr ppm

0.64 81

0.73 90

0.84 95

%

9.6 1.69

9.4 1.67

9.1 1.64

159461 60879 18482 5459 8473 55561 43960 6208 4426

125112 45659 15980 4948 8075 43619 34406 3478 3346

89000 30439 13137 3867 7450 31164 24511 855 2045

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8) Heat Rejection to Aftercooler - stage 2 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 86

DM1244-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 70 0.90/16* 0.90/18*

75 1.0/18

80 to 100 1.0/20

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 1000

0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 1.00 2000

0.83 0.80 0.77 0.75 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.89 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.81 0.78 0.93 0.89 0.86 0.83 0.80 0.95 0.91 0.88 0.85 0.81 0.97 0.93 0.90 0.86 0.83 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.75 0.73 0.70 0.67 0.77 0.74 0.71 0.68 0.78 0.75 0.72 0.70 0.80 0.77 0.74 0.71 9000 10000 11000 12000

1.38 1.31 1.24 1.16 1.09 1.02 1.00 1.00 1.00 3000

1.38 1.38 1.38 1.38 1.38 1.31 1.31 1.31 1.31 1.31 1.24 1.24 1.24 1.24 1.24 1.16 1.16 1.16 1.16 1.16 1.09 1.09 1.09 1.09 1.09 1.02 1.02 1.02 1.02 1.02 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.38 1.38 1.38 1.38 1.31 1.31 1.31 1.31 1.24 1.24 1.24 1.24 1.16 1.16 1.16 1.16 1.09 1.09 1.09 1.09 1.02 1.02 1.02 1.02 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3516

0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.29 1.22 1.15 1.08 1.01 1.00 1.00 1.00 1.00 0

1.34 1.27 1.20 1.13 1.06 1.00 1.00 1.00 1.00 1000

1.38 1.31 1.24 1.16 1.09 1.02 1.00 1.00 1.00 2000

DM1244-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1244-00

-ENGLISH- page 2 of 2

87

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°F) 90 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 HPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp Kw

30 80 4922

100%

75%

50%

1435 1025

1076 769

717 513

7352 2769 12280 74 317 65.9 111 20 824 7229 12800

7485 2039 9044 63.5 266 49.5 106 20 826 5339 9442

7899 1310 5810 46.9 191 33.7 104 20 847 3501 6089

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 151

2.3 175

4.3 316

(Corr. 15% 02)

g/bhp-hr ppm

1.6 199

1.6 196

1.6 197

(Corr. 15% 02)

g/bhp-hr ppm

2.7 595

2.7 585

2.8 589

(Corr. 15% 02)

g/bhp-hr ppm

0.41 39

0.41 37

0.42 35

%

7.3 1.46

6.8 1.40

5.6 1.28

175805 60879 53958 5693 0 44671 27268 10601

134240 45659 44409 4744 0 33134 20241 6290

94444 30439 35606 3796 0 22193 13748 2407

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 88

DM5159-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/15

70 1.0/16

75 1.0/18

80 1.0/19

83 to 100 1.0/20

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.94 0.91 0.87 0.84 0.81 0.96 0.92 0.89 0.86 0.82 0.98 0.94 0.90 0.87 0.84 0.99 0.96 0.92 0.89 0.85 1.00 0.97 0.94 0.90 0.87 1.00 0.99 0.95 0.92 0.89 1.00 1.00 0.97 0.94 0.90 1.00 1.00 0.99 0.95 0.92 1.00 1.00 1.00 0.97 0.94 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.78 0.75 0.72 0.69 0.79 0.76 0.73 0.71 0.81 0.78 0.75 0.72 0.82 0.79 0.76 0.73 0.84 0.80 0.77 0.74 0.85 0.82 0.79 0.76 0.87 0.83 0.80 0.77 0.88 0.85 0.82 0.79 0.90 0.87 0.83 0.80 9000 10000 11000 12000

1.43 1.36 1.29 1.22 1.16 1.09 1.02 1.00 1.00 3000

1.48 1.54 1.54 1.54 1.54 1.41 1.47 1.47 1.47 1.47 1.35 1.40 1.40 1.40 1.40 1.28 1.33 1.33 1.33 1.33 1.21 1.26 1.26 1.26 1.26 1.14 1.19 1.19 1.19 1.19 1.07 1.12 1.12 1.12 1.12 1.00 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.54 1.54 1.54 1.54 1.47 1.47 1.47 1.47 1.40 1.40 1.40 1.40 1.33 1.33 1.33 1.33 1.26 1.26 1.26 1.26 1.19 1.19 1.19 1.19 1.12 1.12 1.12 1.12 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3516

0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.27 1.20 1.14 1.07 1.01 1.00 1.00 1.00 1.00 0

1.32 1.26 1.19 1.12 1.06 1.00 1.00 1.00 1.00 1000

1.37 1.31 1.24 1.17 1.11 1.04 1.00 1.00 1.00 2000

DM5159-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5159-00

-ENGLISH- page 2 of 2

89

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°F) 90 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 LPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp Btu

1.5 80 5000

100%

75%

50%

1435 1025

1076 769

717 513

7145 2875 12752 73 303 66 112 20 833 7542 13263

7578 2236 9915 69.2 278 52 108 20 829 5853 10321

7975 1414 6268 49.8 199 34.3 107 20 853 3784 6553

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 161

2.1 167

5.6 387

(Corr. 15% 02)

g/bhp-hr ppm

2.0 252

2.1 251

2.4 271

(Corr. 15% 02)

g/bhp-hr ppm

3.0 671

3.4 739

2.9 579

(Corr. 15% 02)

g/bhp-hr ppm

0.45 47

0.52 52

0.43 36

%

8.2 1.54

8.1 1.50

6.4 1.36

170861 60879 46447 5693 0 46892 28706 10979

135908 45659 41291 4744 0 36557 22199 7652

95357 30439 34403 3796 0 23904 14903 2812

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 90

DM5165-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/15

70 1.0/16

75 1.0/18

80 1.0/19

83 to 100 1.0/20

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.94 0.91 0.88 0.84 0.81 0.96 0.93 0.89 0.86 0.83 0.98 0.94 0.91 0.87 0.84 1.00 0.96 0.92 0.89 0.86 1.00 0.98 0.94 0.91 0.87 1.00 0.99 0.96 0.92 0.89 1.00 1.00 0.98 0.94 0.90 1.00 1.00 0.99 0.96 0.92 1.00 1.00 1.00 0.98 0.94 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.78 0.75 0.72 0.70 0.80 0.77 0.74 0.71 0.81 0.78 0.75 0.72 0.82 0.79 0.76 0.73 0.84 0.81 0.78 0.75 0.85 0.82 0.79 0.76 0.87 0.84 0.81 0.77 0.89 0.85 0.82 0.79 0.90 0.87 0.84 0.80 9000 10000 11000 12000

1.44 1.37 1.30 1.23 1.16 1.09 1.02 1.00 1.00 3000

1.49 1.55 1.55 1.55 1.55 1.42 1.48 1.48 1.48 1.48 1.35 1.41 1.41 1.41 1.41 1.28 1.33 1.33 1.33 1.33 1.21 1.26 1.26 1.26 1.26 1.14 1.19 1.19 1.19 1.19 1.07 1.12 1.12 1.12 1.12 1.00 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.55 1.55 1.55 1.55 1.48 1.48 1.48 1.48 1.41 1.41 1.41 1.41 1.33 1.33 1.33 1.33 1.26 1.26 1.26 1.26 1.19 1.19 1.19 1.19 1.12 1.12 1.12 1.12 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3516

0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.28 1.21 1.15 1.08 1.01 1.00 1.00 1.00 1.00 0

1.33 1.26 1.20 1.13 1.06 1.00 1.00 1.00 1.00 1000

1.39 1.32 1.25 1.18 1.11 1.04 1.00 1.00 1.00 2000

DM5165-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5165-00

-ENGLISH- page 2 of 2

91

®

G3512

G3512 TA

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 9.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type STANDARD

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 HPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

25 80 5000

100%

75%

50%

791 555

593 416

396 278

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

7501 1167 5172 58.4 243 53.7 140 22.5 869 3195 5466

7894 890 3947 54 223 43.3 138 22.5 838 2386 4178

8506 660 2924 43.1 166 32.2 137 22.5 786 1694 3090

(Corr. 15% 02)

g/bhp-hr ppm

20.7 1520

18.3 1273

18.0 1141

(Corr. 15% 02)

g/bhp-hr ppm

1.8 208

1.9 208

2.0 196

(Corr. 15% 02)

g/bhp-hr ppm

1.5 318

1.7 337

2.2 402

(Corr. 15% 02)

g/bhp-hr ppm

0.23 15

0.26 16

0.33 19

%

2.0 1.09

1.3 1.05

1.6 1.09

98904 33569 39044 3643 0 20361 13054 2285

78066 25176 33344 3036 0 15049 9399 1458

56082 16784 26036 2429 0 10417 6174 414

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp Kw

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9)

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 92

DM5207-00

®

G3512 TA

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 35 40 45 50 55 60 0.62/14 0.62/15 0.62/16 0.62/17 0.90/14 0.90/15 0.90/16

65 1.0/16

70 1.0/18

75 1.0/20

80 1.0/23

83 to 100 1.0/23

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 3000

0.94 0.91 0.88 0.84 0.81 0.96 0.93 0.89 0.86 0.83 0.98 0.94 0.91 0.87 0.84 1.00 0.96 0.92 0.89 0.86 1.00 0.98 0.94 0.91 0.87 1.00 0.99 0.96 0.92 0.89 1.00 1.00 0.98 0.94 0.90 1.00 1.00 0.99 0.96 0.92 1.00 1.00 1.00 0.98 0.94 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.78 0.75 0.72 0.70 0.80 0.77 0.74 0.71 0.81 0.78 0.75 0.72 0.82 0.79 0.76 0.73 0.84 0.81 0.78 0.75 0.85 0.82 0.79 0.76 0.87 0.84 0.81 0.77 0.89 0.85 0.82 0.79 0.90 0.87 0.84 0.80 9000 10000 11000 12000

1.75 1.63 1.51 1.39 1.27 1.15 1.03 1.00 1.00 3000

1.85 1.94 1.94 1.94 1.94 1.73 1.82 1.82 1.82 1.82 1.60 1.70 1.70 1.70 1.70 1.48 1.58 1.58 1.58 1.58 1.36 1.45 1.45 1.45 1.45 1.24 1.33 1.33 1.33 1.33 1.12 1.21 1.21 1.21 1.21 1.00 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.94 1.94 1.94 1.94 1.82 1.82 1.82 1.82 1.70 1.70 1.70 1.70 1.58 1.58 1.58 1.58 1.45 1.45 1.45 1.45 1.33 1.33 1.33 1.33 1.21 1.21 1.21 1.21 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.48 1.36 1.25 1.13 1.02 1.00 1.00 1.00 1.00 0

1.57 1.45 1.33 1.22 1.10 1.00 1.00 1.00 1.00 1000

1.66 1.54 1.42 1.30 1.19 1.07 1.00 1.00 1.00 2000

DM5207-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5207-00

-ENGLISH- page 2 of 2

93

®

G3512

G3512 TA

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 9.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type CATALYST

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

NAT GAS 920 HPG IMPCO 25 80 5000

100%

75%

50%

791 555

593 416

396 278

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

7822 1107 4908 60.2 258 52.5 139 22.5 892 3102 5214

8255 879 3898 55.3 235 43.3 136 22.5 837 2361 4141

8993 637 2822 42.9 173 32.5 136 22.5 790 1648 2998

(Corr. 15% 02)

g/bhp-hr ppm

10.6 758

9.9 671

9.5 595

(Corr. 15% 02)

g/bhp-hr ppm

12.4 1465

14.2 1470

15.2 1451

(Corr. 15% 02)

g/bhp-hr ppm

2.1 444

2.5 500

3.6 647

(Corr. 15% 02)

g/bhp-hr ppm

0.32 20

0.39 22

0.54 28

%

0.3 0.99

0.3 0.99

0.3 0.99

103136 33569 42955 3643 0 20496 13141 2469

81635 25176 36505 3036 0 15264 9328 1651

59291 16784 28965 2429 0 10576 6089 535

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9)

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 94

DM5209-00

®

G3512 TA

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 35 40 45 50 55 60 0.62/14 0.62/15 0.62/16 0.62/17 0.90/14 0.90/14 0.90/16

65 1.0/16

70 1.0/18

75 1.0/20

80 1.0/23

83 to 100 1.0/23

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 3000

0.94 0.91 0.88 0.84 0.81 0.96 0.93 0.89 0.86 0.83 0.98 0.94 0.91 0.87 0.84 1.00 0.96 0.92 0.89 0.86 1.00 0.98 0.94 0.91 0.87 1.00 0.99 0.96 0.92 0.89 1.00 1.00 0.98 0.94 0.90 1.00 1.00 0.99 0.96 0.92 1.00 1.00 1.00 0.98 0.94 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.78 0.75 0.72 0.70 0.80 0.77 0.74 0.71 0.81 0.78 0.75 0.72 0.82 0.79 0.76 0.73 0.84 0.81 0.78 0.75 0.85 0.82 0.79 0.76 0.87 0.84 0.81 0.77 0.89 0.85 0.82 0.79 0.90 0.87 0.84 0.80 9000 10000 11000 12000

1.69 1.58 1.47 1.36 1.25 1.14 1.03 1.00 1.00 3000

1.78 1.87 1.87 1.87 1.87 1.67 1.76 1.76 1.76 1.76 1.56 1.64 1.64 1.64 1.64 1.45 1.53 1.53 1.53 1.53 1.33 1.42 1.42 1.42 1.42 1.22 1.31 1.31 1.31 1.31 1.11 1.19 1.19 1.19 1.19 1.00 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.87 1.87 1.87 1.87 1.76 1.76 1.76 1.76 1.64 1.64 1.64 1.64 1.53 1.53 1.53 1.53 1.42 1.42 1.42 1.42 1.31 1.31 1.31 1.31 1.19 1.19 1.19 1.19 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.43 1.33 1.22 1.12 1.01 1.00 1.00 1.00 1.00 0

1.52 1.41 1.30 1.20 1.09 1.00 1.00 1.00 1.00 1000

1.60 1.50 1.39 1.28 1.17 1.06 1.00 1.00 1.00 2000

DM5209-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5209-00

-ENGLISH- page 2 of 2

95

®

G3512

G3512 TA

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 9.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type STANDARD

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 LPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

1.5 80 5000

100%

75%

50%

791 555

593 416

396 278

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

7501 1167 5172 58.4 243 53.7 140 22.5 869 3195 5466

7894 890 3947 54 223 43.3 138 22.5 838 2386 4178

8506 660 2924 43.1 166 32.2 137 22.5 786 1694 3090

(Corr. 15% 02)

g/bhp-hr ppm

20.7 1520

18.3 1273

18.0 1141

(Corr. 15% 02)

g/bhp-hr ppm

1.8 208

1.9 208

2.0 196

(Corr. 15% 02)

g/bhp-hr ppm

1.5 318

1.7 337

2.2 402

(Corr. 15% 02)

g/bhp-hr ppm

0.23 15

0.26 16

0.33 19

%

2.0 1.09

1.3 1.05

1.6 1.09

98904 33569 38915 3643 0 20361 13054 2414

78066 25176 33258 3036 0 15049 9399 1543

56082 16784 26012 2429 0 10417 6174 438

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9)

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 96

DM5108-00

®

G3512 TA

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 35 40 45 0.62/14 0.62/15 0.62/16 0.62/17

50 0.9/14

55 0.9/15

60 0.9/16

65 1.0/16

70 1.0/18

75 1.0/20

80 1.0/23

83 to 100 1.0/23

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 3000

0.94 0.91 0.88 0.84 0.81 0.96 0.93 0.89 0.86 0.83 0.98 0.94 0.91 0.87 0.84 1.00 0.96 0.92 0.89 0.86 1.00 0.98 0.94 0.91 0.87 1.00 0.99 0.96 0.92 0.89 1.00 1.00 0.98 0.94 0.90 1.00 1.00 0.99 0.96 0.92 1.00 1.00 1.00 0.98 0.94 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.78 0.75 0.72 0.70 0.80 0.77 0.74 0.71 0.81 0.78 0.75 0.72 0.82 0.79 0.76 0.73 0.84 0.81 0.78 0.75 0.85 0.82 0.79 0.76 0.87 0.84 0.81 0.77 0.89 0.85 0.82 0.79 0.90 0.87 0.84 0.80 9000 10000 11000 12000

1.75 1.63 1.51 1.39 1.27 1.15 1.03 1.00 1.00 3000

1.85 1.94 1.94 1.94 1.94 1.73 1.82 1.82 1.82 1.82 1.60 1.70 1.70 1.70 1.70 1.48 1.58 1.58 1.58 1.58 1.36 1.45 1.45 1.45 1.45 1.24 1.33 1.33 1.33 1.33 1.12 1.21 1.21 1.21 1.21 1.00 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.94 1.94 1.94 1.94 1.82 1.82 1.82 1.82 1.70 1.70 1.70 1.70 1.58 1.58 1.58 1.58 1.45 1.45 1.45 1.45 1.33 1.33 1.33 1.33 1.21 1.21 1.21 1.21 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.48 1.36 1.25 1.13 1.02 1.00 1.00 1.00 1.00 0

1.57 1.45 1.33 1.22 1.10 1.00 1.00 1.00 1.00 1000

1.66 1.54 1.42 1.30 1.19 1.07 1.00 1.00 1.00 2000

DM5108-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5108-00

-ENGLISH- page 2 of 2

97

®

G3512

G3512 TA

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 9.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type CATALYST

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

NAT GAS 920 LPG IMPCO 1.5 80 5000

100%

75%

50%

791 555

593 416

396 278

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

7822 1107 4908 60.2 258 52.5 139 22.5 892 3102 5214

8255 879 3898 55.3 235 43.3 136 22.5 837 2361 4141

8993 637 2822 42.9 173 32.5 136 22.5 790 1648 2998

(Corr. 15% 02)

g/bhp-hr ppm

10.6 758

9.9 671

9.5 595

(Corr. 15% 02)

g/bhp-hr ppm

12.4 1465

14.2 1470

15.2 1451

(Corr. 15% 02)

g/bhp-hr ppm

2.1 444

2.5 500

3.6 647

(Corr. 15% 02)

g/bhp-hr ppm

0.32 20

0.39 22

0.54 28

%

0.3 0.99

0.3 0.99

0.3 0.99

103136 33569 42801 3643 0 20496 13141 2624

81635 25176 36402 3036 0 15264 9328 1754

59291 16784 28932 2429 0 10576 6089 568

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9)

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 98

DM5109-00

®

G3512 TA

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 35 40 45 0.62/14 0.62/15 0.62/16 0.62/17

50 0.9/14

55 0.9/15

60 0.9/16

65 1.0/16

70 1.0/18

75 1.0/20

80 1.0/23

83 to 100 1.0/23

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 3000

0.94 0.91 0.88 0.84 0.81 0.96 0.93 0.89 0.86 0.83 0.98 0.94 0.91 0.87 0.84 1.00 0.96 0.92 0.89 0.86 1.00 0.98 0.94 0.91 0.87 1.00 0.99 0.96 0.92 0.89 1.00 1.00 0.98 0.94 0.90 1.00 1.00 0.99 0.96 0.92 1.00 1.00 1.00 0.98 0.94 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.78 0.75 0.72 0.70 0.80 0.77 0.74 0.71 0.81 0.78 0.75 0.72 0.82 0.79 0.76 0.73 0.84 0.81 0.78 0.75 0.85 0.82 0.79 0.76 0.87 0.84 0.81 0.77 0.89 0.85 0.82 0.79 0.90 0.87 0.84 0.80 9000 10000 11000 12000

1.69 1.58 1.47 1.36 1.25 1.14 1.03 1.00 1.00 3000

1.78 1.87 1.87 1.87 1.87 1.67 1.76 1.76 1.76 1.76 1.56 1.64 1.64 1.64 1.64 1.45 1.53 1.53 1.53 1.53 1.33 1.42 1.42 1.42 1.42 1.22 1.31 1.31 1.31 1.31 1.11 1.19 1.19 1.19 1.19 1.00 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.87 1.87 1.87 1.87 1.76 1.76 1.76 1.76 1.64 1.64 1.64 1.64 1.53 1.53 1.53 1.53 1.42 1.42 1.42 1.42 1.31 1.31 1.31 1.31 1.19 1.19 1.19 1.19 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.43 1.33 1.22 1.12 1.01 1.00 1.00 1.00 1.00 0

1.52 1.41 1.30 1.20 1.09 1.00 1.00 1.00 1.00 1000

1.60 1.50 1.39 1.28 1.17 1.06 1.00 1.00 1.00 2000

DM5109-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5109-00

-ENGLISH- page 2 of 2

99

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 HPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

30 80 1900

100%

75%

50%

814 570

610 428

407 285

7221 1759 7800 72.9 308 63.3 137 22 730 4234 8087

7330 1269 5627 60.5 251 48.6 133 22 741 3091 5850

8401 851 3775 47.8 191 34.7 132 22 734 2066 3934

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 153

2.6 189

5.1 434

(Corr. 15% 02)

g/bhp-hr ppm

1.9 238

2.1 248

2.2 250

(Corr. 15% 02)

g/bhp-hr ppm

6.5 1436

6.0 1317

5.8 1210

(Corr. 15% 02)

g/bhp-hr ppm

0.98 106

0.90 92

0.87 79

%

8.8 1.68

8.2 1.56

7.3 1.46

97959 34536 28000 3643 0 26225 13636 5555

74575 25902 23701 3036 0 19234 10195 2701

56987 17268 23566 2429 0 12798 6755 925

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 100

DM0745-02

®

G3512 LE

Gas Genset Engine Performance

Engine Noise Data - at 100% load 100 111

dB(A) dB(A)

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/15

70 1.0/17

75 1.0/19

80 1.0/21

83 to 100 1.0/22

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.94 0.96 0.97 0.99 1.00 1.00 1.00 1.00 1.00 1000

0.91 0.92 0.94 0.96 0.97 0.99 1.00 1.00 1.00 2000

0.87 0.89 0.90 0.92 0.94 0.96 0.97 0.99 1.00 3000

0.84 0.81 0.78 0.75 0.72 0.86 0.83 0.79 0.77 0.74 0.87 0.84 0.81 0.78 0.75 0.89 0.85 0.82 0.79 0.76 0.90 0.87 0.84 0.81 0.78 0.92 0.89 0.85 0.82 0.79 0.94 0.90 0.87 0.84 0.81 0.96 0.92 0.89 0.85 0.82 0.97 0.94 0.90 0.87 0.84 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.70 0.67 0.64 0.62 0.71 0.68 0.66 0.63 0.72 0.69 0.67 0.64 0.73 0.71 0.68 0.65 0.75 0.72 0.69 0.67 0.76 0.73 0.70 0.68 0.78 0.75 0.72 0.69 0.79 0.76 0.73 0.70 0.81 0.78 0.75 0.72 9000 10000 11000 12000

1.45 1.37 1.28 1.20 1.12 1.04 1.00 1.00 1.00 3000

1.45 1.45 1.45 1.45 1.45 1.37 1.37 1.37 1.37 1.37 1.28 1.28 1.28 1.28 1.28 1.20 1.20 1.20 1.20 1.20 1.12 1.12 1.12 1.12 1.12 1.04 1.04 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.45 1.45 1.45 1.45 1.37 1.37 1.37 1.37 1.28 1.28 1.28 1.28 1.20 1.20 1.20 1.20 1.12 1.12 1.12 1.12 1.04 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.33 1.25 1.17 1.09 1.01 1.00 1.00 1.00 1.00 0

1.39 1.31 1.23 1.15 1.07 1.00 1.00 1.00 1.00 1000

1.45 1.37 1.28 1.20 1.12 1.04 1.00 1.00 1.00 2000

DM0745-02 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM0745-02

-ENGLISH- page 2 of 2

101

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 260 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 HPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

30 80 1900

100%

75%

50%

814 570

610 428

407 285

7212 1668 7395 71.8 309 63.8 145 20 768 4149 7680

7401 1261 5591 60.3 261 48.6 144 20 788 3191 5813

7934 844 3744 45.6 185 34 146 20 792 2148 3902

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 157

2.5 186

5.3 375

(Corr. 15% 02)

g/bhp-hr ppm

2.0 257

2.1 254

2.2 251

(Corr. 15% 02)

g/bhp-hr ppm

4.3 988

4.3 934

4.1 842

(Corr. 15% 02)

g/bhp-hr ppm

0.66 72

0.65 65

0.62 55

%

8.6 1.60

8.1 1.56

7.3 1.46

97840 34536 21401 5009 6170 25413 14303 5309

75300 25902 17436 4175 5027 19763 11371 2995

53817 17268 14742 3340 4251 13329 7728 885

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 102

DM5110-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/--

70 1.0/15

75 1.0/17

80 1.0/19

83 to 100 1.0/20

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.94 0.96 0.97 0.99 1.00 1.00 1.00 1.00 1.00 1000

0.91 0.92 0.94 0.96 0.97 0.99 1.00 1.00 1.00 2000

0.87 0.89 0.90 0.92 0.94 0.96 0.97 0.99 1.00 3000

0.84 0.81 0.78 0.75 0.72 0.86 0.83 0.79 0.77 0.74 0.87 0.84 0.81 0.78 0.75 0.89 0.85 0.82 0.79 0.76 0.90 0.87 0.84 0.81 0.78 0.92 0.89 0.85 0.82 0.79 0.94 0.90 0.87 0.84 0.81 0.96 0.92 0.89 0.85 0.82 0.97 0.94 0.90 0.87 0.84 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.70 0.67 0.64 0.62 0.71 0.68 0.66 0.63 0.72 0.69 0.67 0.64 0.73 0.71 0.68 0.65 0.75 0.72 0.69 0.67 0.76 0.73 0.70 0.68 0.78 0.75 0.72 0.69 0.79 0.76 0.73 0.70 0.81 0.78 0.75 0.72 9000 10000 11000 12000

1.44 1.36 1.28 1.20 1.12 1.04 1.00 1.00 1.00 3000

1.44 1.44 1.44 1.44 1.44 1.36 1.36 1.36 1.36 1.36 1.28 1.28 1.28 1.28 1.28 1.20 1.20 1.20 1.20 1.20 1.12 1.12 1.12 1.12 1.12 1.04 1.04 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.44 1.44 1.44 1.44 1.36 1.36 1.36 1.36 1.28 1.28 1.28 1.28 1.20 1.20 1.20 1.20 1.12 1.12 1.12 1.12 1.04 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.32 1.24 1.17 1.09 1.01 1.00 1.00 1.00 1.00 0

1.39 1.31 1.23 1.15 1.07 1.00 1.00 1.00 1.00 1000

1.44 1.36 1.28 1.20 1.12 1.04 1.00 1.00 1.00 2000

DM5110-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5110-00

-ENGLISH- page 2 of 2

103

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 LPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

1.5 80 900

100%

75%

50%

814 570

610 428

407 285

7221 1759 7800 72.9 314 63.3 137 22 730 4235 8088

7330 1269 5627 60.5 253 48.6 133 22 741 3091 5850

8401 851 3775 47.8 191 34.7 132 22 734 2066 3935

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 153

2.6 189

5.1 434

(Corr. 15% 02)

g/bhp-hr ppm

1.9 238

1.9 248

2.1 250

(Corr. 15% 02)

g/bhp-hr ppm

6.5 1436

6.0 1317

5.8 1210

(Corr. 15% 02)

g/bhp-hr ppm

0.98 106

0.90 92

0.87 79

%

8.8 1.67

8.2 1.55

7.3 1.46

97959 34536 27617 3643 0 26142 13637 5935

74575 25902 23550 3036 0 20094 10195 2851

56987 17268 23526 2429 0 13620 6755 964

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 104

DM5112-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1/15

70 1.0/17

75 1.0/19

80 1.0/21

83 to 100 1.0/20

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.94 0.96 0.97 0.99 1.00 1.00 1.00 1.00 1.00 0

0.91 0.92 0.94 0.96 0.97 0.99 1.00 1.00 1.00 1000

0.87 0.89 0.90 0.92 0.94 0.96 0.97 0.99 1.00 2000

0.84 0.86 0.87 0.89 0.90 0.92 0.94 0.96 0.97 3000

0.81 0.78 0.75 0.73 0.70 0.83 0.80 0.77 0.74 0.71 0.84 0.81 0.78 0.75 0.72 0.86 0.82 0.79 0.76 0.74 0.87 0.84 0.81 0.78 0.75 0.89 0.85 0.82 0.79 0.76 0.90 0.87 0.84 0.81 0.78 0.92 0.89 0.85 0.82 0.79 0.94 0.91 0.87 0.84 0.81 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.67 0.65 0.62 0.60 0.68 0.66 0.63 0.61 0.70 0.67 0.64 0.62 0.71 0.68 0.66 0.63 0.72 0.69 0.67 0.64 0.73 0.71 0.68 0.65 0.75 0.72 0.69 0.67 0.76 0.73 0.71 0.68 0.78 0.75 0.72 0.69 9000 10000 11000 12000

1.37 1.30 1.22 1.14 1.06 1.00 1.00 1.00 1.00 3000

1.37 1.37 1.37 1.37 1.37 1.30 1.30 1.30 1.30 1.30 1.22 1.22 1.22 1.22 1.22 1.14 1.14 1.14 1.14 1.14 1.06 1.06 1.06 1.06 1.06 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.37 1.37 1.37 1.37 1.30 1.30 1.30 1.30 1.22 1.22 1.22 1.22 1.14 1.14 1.14 1.14 1.06 1.06 1.06 1.06 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.32 1.24 1.16 1.09 1.01 1.00 1.00 1.00 1.00 0

1.37 1.30 1.22 1.14 1.06 1.00 1.00 1.00 1.00 1000

1.37 1.30 1.22 1.14 1.06 1.00 1.00 1.00 1.00 2000

DM5112-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5112-00

-ENGLISH- page 2 of 2

105

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 260 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 LPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

1.5 80 900

100%

75%

50%

814 570

610 428

407 285

7212 1668 7395 71.8 315 63.8 145 20 768 4149 7680

7401 1261 5591 60.3 263 48.6 144 20 788 3191 5813

7934 844 3744 45.6 185 34 146 20 792 2148 3902

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 157

2.5 186

5.3 375

(Corr. 15% 02)

g/bhp-hr ppm

2.0 257

2.1 254

2.2 251

(Corr. 15% 02)

g/bhp-hr ppm

4.3 988

4.3 934

4.1 842

(Corr. 15% 02)

g/bhp-hr ppm

0.66 72

0.65 65

0.62 55

%

8.6 1.60

8.1 1.56

7.3 1.46

97840 34536 21113 5009 6087 25413 14303 5680

75300 25902 17311 4175 4991 19763 11371 3156

53817 17268 14713 3340 4242 13329 7728 922

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 106

DM5111-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/--

70 1.0/15

75 1.0/17

80 1.0/19

83 to 100 1.0/20

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.94 0.96 0.97 0.99 1.00 1.00 1.00 1.00 1.00 0

0.91 0.92 0.94 0.96 0.97 0.99 1.00 1.00 1.00 1000

0.87 0.89 0.90 0.92 0.94 0.96 0.97 0.99 1.00 2000

0.84 0.86 0.87 0.89 0.90 0.92 0.94 0.96 0.97 3000

0.81 0.78 0.75 0.73 0.70 0.83 0.80 0.77 0.74 0.71 0.84 0.81 0.78 0.75 0.72 0.86 0.82 0.79 0.76 0.74 0.87 0.84 0.81 0.78 0.75 0.89 0.85 0.82 0.79 0.76 0.90 0.87 0.84 0.81 0.78 0.92 0.89 0.85 0.82 0.79 0.94 0.91 0.87 0.84 0.81 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.67 0.65 0.62 0.60 0.68 0.66 0.63 0.61 0.70 0.67 0.64 0.62 0.71 0.68 0.66 0.63 0.72 0.69 0.67 0.64 0.73 0.71 0.68 0.65 0.75 0.72 0.69 0.67 0.76 0.73 0.71 0.68 0.78 0.75 0.72 0.69 9000 10000 11000 12000

1.37 1.29 1.21 1.14 1.06 1.00 1.00 1.00 1.00 3000

1.37 1.37 1.37 1.37 1.37 1.29 1.29 1.29 1.29 1.29 1.21 1.21 1.21 1.21 1.21 1.14 1.14 1.14 1.14 1.14 1.06 1.06 1.06 1.06 1.06 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.37 1.37 1.37 1.37 1.29 1.29 1.29 1.29 1.21 1.21 1.21 1.21 1.14 1.14 1.14 1.14 1.06 1.06 1.06 1.06 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.31 1.24 1.16 1.08 1.01 1.00 1.00 1.00 1.00 0

1.37 1.29 1.21 1.14 1.06 1.00 1.00 1.00 1.00 1000

1.37 1.29 1.21 1.14 1.06 1.00 1.00 1.00 1.00 2000

DM5111-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5111-00

-ENGLISH- page 2 of 2

107

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 8.0:1 Aftercooler Inlet Temperature (°F) 90 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 HPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

35 80 3600

100%

75%

50%

861 600

646 450

430 300

7407 1813 8038 71.8 317 63.9 113 35 799 4625 8354

7599 1323 5867 63.8 277 48.7 111 35 790 3359 6110

8087 882 3909 46.4 199 33.6 110 35 790 2244 4082

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 155

4.1 304

7.5 522

(Corr. 15% 02)

g/bhp-hr ppm

1.5 185

1.6 189

1.7 191

(Corr. 15% 02)

g/bhp-hr ppm

3.0 653

2.8 607

2.8 560

(Corr. 15% 02)

g/bhp-hr ppm

0.45 47

0.43 41

0.42 35

%

8.3 1.57

7.7 1.49

6.7 1.40

106272 36527 30880 3643 0 28124 16747 7128

81773 27395 26668 3036 0 20322 12035 4350

58014 18264 21942 2429 0 13618 8072 1759

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 108

DM5169-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 35 40 0.90/21 0.90/23 0.90/24

45 1.0/25

50 1.0/26

55 1.0/28

60 1.0/29

65 1.0/30

70 1.0/32

75 1.0/33

80 1.0/34

83 to 100 1.0/35

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 3000

0.90 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.81 0.78 0.93 0.89 0.86 0.83 0.80 0.94 0.91 0.88 0.84 0.81 0.96 0.93 0.89 0.86 0.83 0.98 0.94 0.91 0.88 0.84 1.00 0.96 0.93 0.89 0.86 1.00 0.98 0.94 0.91 0.87 1.00 1.00 0.96 0.93 0.89 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.74 0.71 0.69 0.66 0.75 0.73 0.70 0.67 0.77 0.74 0.71 0.68 0.78 0.75 0.72 0.70 0.80 0.77 0.74 0.71 0.81 0.78 0.75 0.72 0.83 0.79 0.76 0.73 0.84 0.81 0.78 0.75 0.86 0.83 0.79 0.76 9000 10000 11000 12000

1.42 1.35 1.29 1.22 1.15 1.09 1.02 1.00 1.00 3000

1.45 1.45 1.45 1.45 1.45 1.39 1.39 1.39 1.39 1.39 1.32 1.32 1.32 1.32 1.32 1.25 1.25 1.25 1.25 1.25 1.19 1.19 1.19 1.19 1.19 1.12 1.12 1.12 1.12 1.12 1.05 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.45 1.45 1.45 1.45 1.39 1.39 1.39 1.39 1.32 1.32 1.32 1.32 1.25 1.25 1.25 1.25 1.19 1.19 1.19 1.19 1.12 1.12 1.12 1.12 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.26 1.20 1.13 1.07 1.01 1.00 1.00 1.00 1.00 0

1.31 1.25 1.18 1.12 1.05 1.00 1.00 1.00 1.00 1000

1.37 1.30 1.24 1.17 1.10 1.04 1.00 1.00 1.00 2000

DM5169-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5169-00

-ENGLISH- page 2 of 2

109

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°F) 90 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 HPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

30 80 1900

100%

75%

50%

861 600

646 450

430 300

6993 1782 7902 70.5 294 62.3 109 24 720 4253 8198

8006 1314 5825 60.7 249 47.5 106 24 730 3183 6080

8441 885 3925 46 177 33.8 106 24 732 2153 4107

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 159

2.7 210

4.1 326

(Corr. 15% 02)

g/bhp-hr ppm

1.7 208

1.8 230

1.9 233

(Corr. 15% 02)

g/bhp-hr ppm

4.5 1248

4.0 1109

4.1 1073

(Corr. 15% 02)

g/bhp-hr ppm

0.68 91

0.61 78

0.62 72

%

8.7 1.65

8.3 1.41

7.6 1.33

100338 36527 28053 3643 0 25800 13432 6312

86155 27395 32639 3036 0 19400 10358 3683

60558 18264 25257 2429 0 13237 7058 1409

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 110

DM5173-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 1/15

65 1/17

70 1.0/19

75 1.0/21

80 1.0/23

83 to 100 1.0/24

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.94 0.96 0.97 0.99 1.00 1.00 1.00 1.00 1.00 1000

0.91 0.92 0.94 0.96 0.97 0.99 1.00 1.00 1.00 2000

0.87 0.89 0.90 0.92 0.94 0.96 0.97 0.99 1.00 3000

0.84 0.81 0.78 0.75 0.72 0.86 0.83 0.79 0.77 0.74 0.87 0.84 0.81 0.78 0.75 0.89 0.85 0.82 0.79 0.76 0.90 0.87 0.84 0.81 0.78 0.92 0.89 0.85 0.82 0.79 0.94 0.90 0.87 0.84 0.81 0.96 0.92 0.89 0.85 0.82 0.97 0.94 0.90 0.87 0.84 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.70 0.67 0.64 0.62 0.71 0.68 0.66 0.63 0.72 0.69 0.67 0.64 0.73 0.71 0.68 0.65 0.75 0.72 0.69 0.67 0.76 0.73 0.70 0.68 0.78 0.75 0.72 0.69 0.79 0.76 0.73 0.70 0.81 0.78 0.75 0.72 9000 10000 11000 12000

1.39 1.32 1.25 1.18 1.11 1.03 1.00 1.00 1.00 3000

1.39 1.39 1.39 1.39 1.39 1.32 1.32 1.32 1.32 1.32 1.25 1.25 1.25 1.25 1.25 1.18 1.18 1.18 1.18 1.18 1.11 1.11 1.11 1.11 1.11 1.03 1.03 1.03 1.03 1.03 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.39 1.39 1.39 1.39 1.32 1.32 1.32 1.32 1.25 1.25 1.25 1.25 1.18 1.18 1.18 1.18 1.11 1.11 1.11 1.11 1.03 1.03 1.03 1.03 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.29 1.22 1.15 1.08 1.01 1.00 1.00 1.00 1.00 0

1.34 1.27 1.20 1.13 1.06 1.00 1.00 1.00 1.00 1000

1.39 1.32 1.25 1.18 1.11 1.03 1.00 1.00 1.00 2000

DM5173-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5173-00

-ENGLISH- page 2 of 2

111

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°F) 90 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 LPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

1.5 80 900

100%

75%

50%

861 600

646 450

430 300

6993 1782 7902 70.5 294 62.3 109 24 720 4253 8198

8006 1314 5825 60.7 249 47.5 106 24 730 3183 6080

8441 885 3925 46 177 33.8 106 24 732 2153 4107

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 159

2.7 210

4.1 326

(Corr. 15% 02)

g/bhp-hr ppm

1.7 208

1.8 230

1.9 233

(Corr. 15% 02)

g/bhp-hr ppm

5.4 1248

4.8 1109

5.0 1073

(Corr. 15% 02)

g/bhp-hr ppm

0.82 91

0.73 78

0.75 72

%

8.7 1.65

8.3 1.41

7.6 1.33

100338 36527 27816 3643 0 25800 13432 6549

86155 27395 32478 3036 0 19400 10358 3844

60558 18264 25191 2429 0 13259 7058 1474

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 112

DM5115-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 1/15

65 1/17

70 1.0/19

75 1.0/21

80 1.0/23

83 to 100 1.0/24

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.94 0.96 0.97 0.99 1.00 1.00 1.00 1.00 1.00 0

0.91 0.92 0.94 0.96 0.97 0.99 1.00 1.00 1.00 1000

0.87 0.89 0.90 0.92 0.94 0.96 0.97 0.99 1.00 2000

0.84 0.86 0.87 0.89 0.90 0.92 0.94 0.96 0.97 3000

0.81 0.78 0.75 0.73 0.70 0.83 0.80 0.77 0.74 0.71 0.84 0.81 0.78 0.75 0.72 0.86 0.82 0.79 0.76 0.74 0.87 0.84 0.81 0.78 0.75 0.89 0.85 0.82 0.79 0.76 0.90 0.87 0.84 0.81 0.78 0.92 0.89 0.85 0.82 0.79 0.94 0.91 0.87 0.84 0.81 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.67 0.65 0.62 0.60 0.68 0.66 0.63 0.61 0.70 0.67 0.64 0.62 0.71 0.68 0.66 0.63 0.72 0.69 0.67 0.64 0.73 0.71 0.68 0.65 0.75 0.72 0.69 0.67 0.76 0.73 0.71 0.68 0.78 0.75 0.72 0.69 9000 10000 11000 12000

1.34 1.27 1.20 1.13 1.06 1.00 1.00 1.00 1.00 3000

1.34 1.34 1.34 1.34 1.34 1.27 1.27 1.27 1.27 1.27 1.20 1.20 1.20 1.20 1.20 1.13 1.13 1.13 1.13 1.13 1.06 1.06 1.06 1.06 1.06 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.34 1.34 1.34 1.34 1.27 1.27 1.27 1.27 1.20 1.20 1.20 1.20 1.13 1.13 1.13 1.13 1.06 1.06 1.06 1.06 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.29 1.22 1.15 1.08 1.01 1.00 1.00 1.00 1.00 0

1.34 1.27 1.20 1.13 1.06 1.00 1.00 1.00 1.00 1000

1.34 1.27 1.20 1.13 1.06 1.00 1.00 1.00 1.00 2000

DM5115-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5115-00

-ENGLISH- page 2 of 2

113

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 8.0:1 Aftercooler Inlet Temperature (°F) 90 Jacket Water Outlet Temperature (°F) 260 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 HPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

35 80 3600

100%

75%

50%

861 600

646 450

430 300

7409 1803 7994 72.9 320 64.8 120 33 833 4726 8310

7551 1293 5735 63.9 283 48.7 120 33 824 3375 5976

8093 875 3881 47.2 194 33.9 121 33 817 2268 4038

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 152

6.2 464

10.7 720

(Corr. 15% 02)

g/bhp-hr ppm

1.6 191

1.6 199

2.1 232

(Corr. 15% 02)

g/bhp-hr ppm

2.7 579

2.4 514

2.3 453

(Corr. 15% 02)

g/bhp-hr ppm

0.40 41

0.36 34

0.35 28

%

8.1 1.56

7.3 1.47

6.1 1.52

106311 36527 22105 5009 6373 29104 17969 7190

81258 27395 19120 4175 5513 20698 12725 4355

58058 18264 16286 3340 4696 13797 8445 1673

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 114

DM5113-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0.9/19

35 0.9/21

40 0.9/22

45 1.0/23

50 1.0/24

55 1.0/26

60 1.0/27

65 1.0/28

70 1.0/30

75 1.0/31

80 1.0/32

83 to 100 1.0/33

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 3000

0.90 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.81 0.78 0.93 0.89 0.86 0.83 0.80 0.94 0.91 0.88 0.84 0.81 0.96 0.93 0.89 0.86 0.83 0.98 0.94 0.91 0.88 0.84 1.00 0.96 0.93 0.89 0.86 1.00 0.98 0.94 0.91 0.87 1.00 1.00 0.96 0.93 0.89 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.74 0.71 0.69 0.66 0.75 0.73 0.70 0.67 0.77 0.74 0.71 0.68 0.78 0.75 0.72 0.70 0.80 0.77 0.74 0.71 0.81 0.78 0.75 0.72 0.83 0.79 0.76 0.73 0.84 0.81 0.78 0.75 0.86 0.83 0.79 0.76 9000 10000 11000 12000

1.42 1.35 1.28 1.22 1.15 1.09 1.02 1.00 1.00 3000

1.45 1.45 1.45 1.45 1.45 1.38 1.38 1.38 1.38 1.38 1.32 1.32 1.32 1.32 1.32 1.25 1.25 1.25 1.25 1.25 1.18 1.18 1.18 1.18 1.18 1.12 1.12 1.12 1.12 1.12 1.05 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.45 1.45 1.45 1.45 1.38 1.38 1.38 1.38 1.32 1.32 1.32 1.32 1.25 1.25 1.25 1.25 1.18 1.18 1.18 1.18 1.12 1.12 1.12 1.12 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.26 1.20 1.13 1.07 1.01 1.00 1.00 1.00 1.00 0

1.31 1.25 1.18 1.12 1.05 1.00 1.00 1.00 1.00 1000

1.36 1.30 1.23 1.17 1.10 1.04 1.00 1.00 1.00 2000

DM5113-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5113-00

-ENGLISH- page 2 of 2

115

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°F) 90 Jacket Water Outlet Temperature (°F) 260 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 HPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

30 80 1900

100%

75%

50%

861 600

646 450

430 300

6961 1754 7778 75.1 321 64 113 22 752 4304 8074

7189 1297 5750 61.4 264 48.4 114 22 781 3263 5979

7714 869 3854 44.9 189 33.6 116 22 784 2199 4018

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 157

3.2 250

6.9 523

(Corr. 15% 02)

g/bhp-hr ppm

2.2 276

2.1 260

2.1 268

(Corr. 15% 02)

g/bhp-hr ppm

4.4 998

4.1 910

4.1 911

(Corr. 15% 02)

g/bhp-hr ppm

0.66 72

0.62 63

0.62 63

%

8.5 1.62

8.1 1.55

8.1 1.45

99880 36527 19515 5009 5627 26142 14429 7057

77362 27395 16821 4175 4850 20094 11503 4024

55343 18264 14409 3340 4154 13620 7827 1555

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 116

DM5114-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/15

70 1.0/17

75 1.0/19

80 1.0/21

83 to 100 1.0/22

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.94 0.96 0.97 0.99 1.00 1.00 1.00 1.00 1.00 1000

0.91 0.92 0.94 0.96 0.97 0.99 1.00 1.00 1.00 2000

0.87 0.89 0.90 0.92 0.94 0.96 0.97 0.99 1.00 3000

0.84 0.81 0.78 0.75 0.72 0.86 0.83 0.79 0.77 0.74 0.87 0.84 0.81 0.78 0.75 0.89 0.85 0.82 0.79 0.76 0.90 0.87 0.84 0.81 0.78 0.92 0.89 0.85 0.82 0.79 0.94 0.90 0.87 0.84 0.81 0.96 0.92 0.89 0.85 0.82 0.97 0.94 0.90 0.87 0.84 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.70 0.67 0.64 0.62 0.71 0.68 0.66 0.63 0.72 0.69 0.67 0.64 0.73 0.71 0.68 0.65 0.75 0.72 0.69 0.67 0.76 0.73 0.70 0.68 0.78 0.75 0.72 0.69 0.79 0.76 0.73 0.70 0.81 0.78 0.75 0.72 9000 10000 11000 12000

1.35 1.29 1.23 1.16 1.10 1.03 1.00 1.00 1.00 3000

1.35 1.35 1.35 1.35 1.35 1.29 1.29 1.29 1.29 1.29 1.23 1.23 1.23 1.23 1.23 1.16 1.16 1.16 1.16 1.16 1.10 1.10 1.10 1.10 1.10 1.03 1.03 1.03 1.03 1.03 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.35 1.35 1.35 1.35 1.29 1.29 1.29 1.29 1.23 1.23 1.23 1.23 1.16 1.16 1.16 1.16 1.10 1.10 1.10 1.10 1.03 1.03 1.03 1.03 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.26 1.20 1.13 1.07 1.01 1.00 1.00 1.00 1.00 0

1.31 1.25 1.18 1.12 1.05 1.00 1.00 1.00 1.00 1000

1.35 1.29 1.23 1.16 1.10 1.03 1.00 1.00 1.00 2000

DM5114-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5114-00

-ENGLISH- page 2 of 2

117

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°F) 90 Jacket Water Outlet Temperature (°F) 260 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 LPG IMPCO

Minimum Fuel Pressure (psig) Minimum Methane Number for Rated Power Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

1.5 80 900

100%

75%

50%

861 600

646 450

430 300

6961 1754 7778 75.1 328 64 113 22 752 4304 8074

7189 1297 5750 61.4 268 48.4 114 22 781 3263 5979

7714 869 3854 44.9 189 33.6 116 22 784 2199 4018

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 157

3.2 250

6.9 523

(Corr. 15% 02)

g/bhp-hr ppm

2.2 276

2.1 260

2.1 268

(Corr. 15% 02)

g/bhp-hr ppm

4.4 998

4.1 910

4.1 911

(Corr. 15% 02)

g/bhp-hr ppm

0.66 72

0.62 63

0.62 63

%

8.5 1.62

8.1 1.55

8.1 1.45

99880 36527 19125 5009 5514 26142 14429 7559

77362 27395 16630 4175 4795 20094 11503 4271

55343 18264 14358 3340 4140 13620 7827 1621

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 118

DM5116-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/15

70 1.0/17

75 1.0/19

80 to 100 1.0/22

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.94 0.96 0.97 0.99 1.00 1.00 1.00 1.00 1.00 0

0.91 0.92 0.94 0.96 0.97 0.99 1.00 1.00 1.00 1000

0.87 0.89 0.90 0.92 0.94 0.96 0.97 0.99 1.00 2000

0.84 0.86 0.87 0.89 0.90 0.92 0.94 0.96 0.97 3000

0.81 0.78 0.75 0.73 0.70 0.83 0.80 0.77 0.74 0.71 0.84 0.81 0.78 0.75 0.72 0.86 0.82 0.79 0.76 0.74 0.87 0.84 0.81 0.78 0.75 0.89 0.85 0.82 0.79 0.76 0.90 0.87 0.84 0.81 0.78 0.92 0.89 0.85 0.82 0.79 0.94 0.91 0.87 0.84 0.81 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.67 0.65 0.62 0.60 0.68 0.66 0.63 0.61 0.70 0.67 0.64 0.62 0.71 0.68 0.66 0.63 0.72 0.69 0.67 0.64 0.73 0.71 0.68 0.65 0.75 0.72 0.69 0.67 0.76 0.73 0.71 0.68 0.78 0.75 0.72 0.69 9000 10000 11000 12000

1.30 1.23 1.17 1.11 1.05 1.00 1.00 1.00 1.00 3000

1.30 1.30 1.30 1.30 1.30 1.23 1.23 1.23 1.23 1.23 1.17 1.17 1.17 1.17 1.17 1.11 1.11 1.11 1.11 1.11 1.05 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.30 1.30 1.30 1.30 1.23 1.23 1.23 1.23 1.17 1.17 1.17 1.17 1.11 1.11 1.11 1.11 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.25 1.19 1.13 1.07 1.01 1.00 1.00 1.00 1.00 0

1.30 1.23 1.17 1.11 1.05 1.00 1.00 1.00 1.00 1000

1.30 1.23 1.17 1.11 1.05 1.00 1.00 1.00 1.00 2000

DM5116-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5116-00

-ENGLISH- page 2 of 2

119

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 8.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 HPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

35 80 5000

100%

75%

50%

1016 725

762 544

508 363

7610 2214 9820 78.7 325 67.6 137 33 874 5985 10197

7739 1601 7099 69 293 49.6 132 33 869 4318 7387

8259 1113 4937 50.1 211 35.5 127 33 869 3006 5142

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 143

3.9 268

4.1 264

(Corr. 15% 02)

g/bhp-hr ppm

1.8 215

2.2 248

2.3 245

(Corr. 15% 02)

g/bhp-hr ppm

2.8 576

2.3 462

2.6 486

(Corr. 15% 02)

g/bhp-hr ppm

0.42 40

0.35 30

0.39 31

%

8.0 1.61

7.1 1.52

6.8 1.49

128918 43127 35997 4554 0 37619 23957 7618

98327 32345 30582 3795 0 26977 17228 4624

69958 21564 24873 3037 0 18858 12009 1624

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 120

DM5171-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0.90/19

35 0.90/21

40 0.90/22

45 1.0/23

50 1.0/24

55 1.0/26

60 1.0/27

65 1.0/28

70 1.0/30

75 1.0/31

80 to 100 1.0/33

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 3000

0.94 0.91 0.88 0.84 0.81 0.96 0.93 0.89 0.86 0.83 0.98 0.94 0.91 0.87 0.84 1.00 0.96 0.92 0.89 0.86 1.00 0.98 0.94 0.91 0.87 1.00 0.99 0.96 0.92 0.89 1.00 1.00 0.98 0.94 0.90 1.00 1.00 0.99 0.96 0.92 1.00 1.00 1.00 0.98 0.94 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.78 0.75 0.72 0.70 0.80 0.77 0.74 0.71 0.81 0.78 0.75 0.72 0.82 0.79 0.76 0.73 0.84 0.81 0.78 0.75 0.85 0.82 0.79 0.76 0.87 0.84 0.81 0.77 0.89 0.85 0.82 0.79 0.90 0.87 0.84 0.80 9000 10000 11000 12000

1.48 1.40 1.33 1.25 1.17 1.10 1.02 1.00 1.00 3000

1.54 1.60 1.60 1.60 1.60 1.46 1.52 1.52 1.52 1.52 1.38 1.44 1.44 1.44 1.44 1.31 1.36 1.36 1.36 1.36 1.23 1.29 1.29 1.29 1.29 1.15 1.21 1.21 1.21 1.21 1.07 1.13 1.13 1.13 1.13 1.00 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.60 1.60 1.60 1.60 1.52 1.52 1.52 1.52 1.44 1.44 1.44 1.44 1.36 1.36 1.36 1.36 1.29 1.29 1.29 1.29 1.21 1.21 1.21 1.21 1.13 1.13 1.13 1.13 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.31 1.23 1.16 1.09 1.01 1.00 1.00 1.00 1.00 0

1.36 1.29 1.21 1.14 1.06 1.00 1.00 1.00 1.00 1000

1.42 1.35 1.27 1.19 1.12 1.04 1.00 1.00 1.00 2000

DM5171-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5171-00

-ENGLISH- page 2 of 2

121

G3512

G3512 LE

®

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 8.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 260 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 HPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

35 80 5000

100%

75%

50%

1016 725

762 544

508 363

7676 2230 9887 78.8 324 69 144 33 898 6132 10264

7808 1609 7136 69 293 50.1 137 33 887 4397 7424

8254 1117 4953 50.1 211 35.6 130 33 881 3042 5159

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 142

3.7 258

4.0 257

(Corr. 15% 02)

g/bhp-hr ppm

1.9 217

2.2 251

2.3 246

(Corr. 15% 02)

g/bhp-hr ppm

2.4 490

2.1 410

2.4 450

(Corr. 15% 02)

g/bhp-hr ppm

0.36 34

0.31 27

0.36 29

%

8.0 1.62

7.1 1.53

6.8 1.49

130031 43127 26920 5920 7762 38734 25236 7564

99209 32345 23045 4934 6644 27598 17918 4640

69910 21564 18340 3948 5288 19142 12329 1627

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 122

DM5122-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0.90/19

35 0.90/21

40 0.90/22

45 1.0/23

50 1.0/24

55 1.0/26

60 1.0/27

65 1.0/28

70 1.0/30

75 1.0/31

80 to 100 1.0/33

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 3000

0.94 0.91 0.88 0.84 0.81 0.96 0.93 0.89 0.86 0.83 0.98 0.94 0.91 0.87 0.84 1.00 0.96 0.92 0.89 0.86 1.00 0.98 0.94 0.91 0.87 1.00 0.99 0.96 0.92 0.89 1.00 1.00 0.98 0.94 0.90 1.00 1.00 0.99 0.96 0.92 1.00 1.00 1.00 0.98 0.94 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.78 0.75 0.72 0.70 0.80 0.77 0.74 0.71 0.81 0.78 0.75 0.72 0.82 0.79 0.76 0.73 0.84 0.81 0.78 0.75 0.85 0.82 0.79 0.76 0.87 0.84 0.81 0.77 0.89 0.85 0.82 0.79 0.90 0.87 0.84 0.80 9000 10000 11000 12000

1.49 1.41 1.33 1.25 1.18 1.10 1.02 1.00 1.00 3000

1.55 1.61 1.61 1.61 1.61 1.47 1.53 1.53 1.53 1.53 1.39 1.45 1.45 1.45 1.45 1.31 1.37 1.37 1.37 1.37 1.23 1.29 1.29 1.29 1.29 1.15 1.21 1.21 1.21 1.21 1.07 1.13 1.13 1.13 1.13 1.00 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.61 1.61 1.61 1.61 1.53 1.53 1.53 1.53 1.45 1.45 1.45 1.45 1.37 1.37 1.37 1.37 1.29 1.29 1.29 1.29 1.21 1.21 1.21 1.21 1.13 1.13 1.13 1.13 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.31 1.24 1.16 1.09 1.01 1.00 1.00 1.00 1.00 0

1.37 1.29 1.22 1.14 1.07 1.00 1.00 1.00 1.00 1000

1.43 1.35 1.27 1.20 1.12 1.04 1.00 1.00 1.00 2000

DM5122-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5122-00

-ENGLISH- page 2 of 2

123

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 HPG IMPCO

Minimum Fuel Pressure (psig) Minimum Methane Number for Rated Power Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

30 80 4300

100%

75%

50%

bhp kW

1016 725

762 544

508 363

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

7479 2000 8868 71 293 62.9 143 17 872 5414 9242

7820 1555 6895 62.1 252 49.9 139 17 878 4233 7192

8354 1013 4492 48.3 195 34.7 135 17 888 2794 4711

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 147

2.2 158

6.8 464

(Corr. 15% 02)

g/bhp-hr ppm

1.9 240

2.0 237

2.3 256

(Corr. 15% 02)

g/bhp-hr ppm

3.7 795

3.5 734

2.5 486

(Corr. 15% 02)

g/bhp-hr ppm

0.56 53

0.52 49

0.38 29

%

7.5 1.46

7.5 1.43

5.6 1.26

126703 43127 38409 4554 0 34877 21733 5731

99360 32345 32460 3795 0 27222 17146 3534

70761 21564 27047 3037 0 17933 11554 1179

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 124

DM5123-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/-

70 1.0/15

75 1.0/16

80 to 100 1.0/17

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.96 0.97 0.99 1.00 1.00 1.00 1.00 1.00 1.00 3000

0.92 0.89 0.85 0.82 0.79 0.94 0.90 0.87 0.84 0.81 0.95 0.92 0.88 0.85 0.82 0.97 0.93 0.90 0.87 0.83 0.99 0.95 0.92 0.88 0.85 1.00 0.97 0.93 0.90 0.86 1.00 0.99 0.95 0.92 0.88 1.00 1.00 0.97 0.93 0.90 1.00 1.00 0.99 0.95 0.92 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.76 0.73 0.70 0.68 0.77 0.75 0.72 0.69 0.79 0.76 0.73 0.70 0.80 0.77 0.74 0.71 0.82 0.79 0.76 0.73 0.83 0.80 0.77 0.74 0.85 0.82 0.78 0.75 0.86 0.83 0.80 0.77 0.88 0.85 0.82 0.78 9000 10000 11000 12000

1.55 1.46 1.38 1.29 1.20 1.11 1.02 1.00 1.00 3000

1.62 1.64 1.64 1.64 1.64 1.53 1.55 1.55 1.55 1.55 1.44 1.46 1.46 1.46 1.46 1.35 1.37 1.37 1.37 1.37 1.26 1.28 1.28 1.28 1.28 1.17 1.19 1.19 1.19 1.19 1.08 1.10 1.10 1.10 1.10 1.00 1.01 1.01 1.01 1.01 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.64 1.64 1.64 1.64 1.55 1.55 1.55 1.55 1.46 1.46 1.46 1.46 1.37 1.37 1.37 1.37 1.28 1.28 1.28 1.28 1.19 1.19 1.19 1.19 1.10 1.10 1.10 1.10 1.01 1.01 1.01 1.01 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.35 1.27 1.18 1.10 1.01 1.00 1.00 1.00 1.00 0

1.42 1.33 1.25 1.16 1.07 1.00 1.00 1.00 1.00 1000

1.48 1.40 1.31 1.22 1.14 1.05 1.00 1.00 1.00 2000

DM5123-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5123-00

-ENGLISH- page 2 of 2

125

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 260 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 HPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

30 80 4300

100%

75%

50%

bhp kW

1016 725

762 544

508 363

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

7573 2033 9014 71.7 293 63.6 150 17 889 5567 9383

7763 1580 7008 62.6 252 50.3 146 17 896 4353 7301

8293 1030 4566 48.6 195 34.8 142 17 906 2873 4782

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 148

2.2 159

6.8 466

(Corr. 15% 02)

g/bhp-hr ppm

2.0 245

2.0 242

2.4 260

(Corr. 15% 02)

g/bhp-hr ppm

3.5 739

3.2 682

2.3 451

(Corr. 15% 02)

g/bhp-hr ppm

0.52 50

0.49 46

0.36 27

%

7.6 1.51

7.6 1.47

5.7 1.30

128290 43127 29100 5920 8390 33923 22771 5826

98632 32345 23056 4934 6648 28053 17961 3592

70242 21564 19428 3948 5602 18501 12095 1198

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 126

DM5121-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/-

70 1.0/15

75 1.0/16

80 to 100 1.0/17

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.96 0.97 0.99 1.00 1.00 1.00 1.00 1.00 1.00 3000

0.92 0.89 0.85 0.82 0.79 0.94 0.90 0.87 0.84 0.81 0.95 0.92 0.88 0.85 0.82 0.97 0.93 0.90 0.87 0.83 0.99 0.95 0.92 0.88 0.85 1.00 0.97 0.93 0.90 0.86 1.00 0.99 0.95 0.92 0.88 1.00 1.00 0.97 0.93 0.90 1.00 1.00 0.99 0.95 0.92 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.76 0.73 0.70 0.68 0.77 0.75 0.72 0.69 0.79 0.76 0.73 0.70 0.80 0.77 0.74 0.71 0.82 0.79 0.76 0.73 0.83 0.80 0.77 0.74 0.85 0.82 0.78 0.75 0.86 0.83 0.80 0.77 0.88 0.85 0.82 0.78 9000 10000 11000 12000

1.55 1.46 1.37 1.29 1.20 1.11 1.02 1.00 1.00 3000

1.62 1.64 1.64 1.64 1.64 1.53 1.55 1.55 1.55 1.55 1.44 1.46 1.46 1.46 1.46 1.35 1.37 1.37 1.37 1.37 1.26 1.28 1.28 1.28 1.28 1.17 1.19 1.19 1.19 1.19 1.08 1.10 1.10 1.10 1.10 1.00 1.01 1.01 1.01 1.01 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.64 1.64 1.64 1.64 1.55 1.55 1.55 1.55 1.46 1.46 1.46 1.46 1.37 1.37 1.37 1.37 1.28 1.28 1.28 1.28 1.19 1.19 1.19 1.19 1.10 1.10 1.10 1.10 1.01 1.01 1.01 1.01 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.35 1.27 1.18 1.10 1.01 1.00 1.00 1.00 1.00 0

1.42 1.33 1.25 1.16 1.07 1.00 1.00 1.00 1.00 1000

1.48 1.40 1.31 1.22 1.14 1.05 1.00 1.00 1.00 2000

DM5121-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5121-00

-ENGLISH- page 2 of 2

127

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 LPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

1.5 80 3300

100%

75%

50%

bhp kW

1016 725

762 544

508 363

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

7479 2000 8868 71 304 62.9 143 17 872 5414 9242

7820 1555 6895 62.1 256 49.9 139 17 878 4233 7192

8354 1013 4492 48.3 196 34.7 135 17 888 2794 4711

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 147

2.2 158

6.8 464

(Corr. 15% 02)

g/bhp-hr ppm

1.9 240

2.0 237

2.3 256

(Corr. 15% 02)

g/bhp-hr ppm

3.7 795

3.5 734

2.5 486

(Corr. 15% 02)

g/bhp-hr ppm

0.56 53

0.52 49

0.38 29

%

7.5 1.46

7.5 1.43

5.6 1.26

126703 43127 37766 4554 0 34877 21733 6374

99360 32345 32204 3795 0 27222 17146 3790

70761 21564 26955 3037 0 17933 11554 1270

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 128

DM5126-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/-

70 1.0/15

75 1.0/16

80 to 100 1.0/17

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

0.95 0.97 0.99 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.92 0.94 0.95 0.97 0.99 1.00 1.00 1.00 1.00 3000

0.89 0.85 0.82 0.79 0.76 0.90 0.87 0.84 0.81 0.78 0.92 0.88 0.85 0.82 0.79 0.93 0.90 0.87 0.83 0.80 0.95 0.92 0.88 0.85 0.82 0.97 0.93 0.90 0.87 0.83 0.99 0.95 0.92 0.88 0.85 1.00 0.97 0.93 0.90 0.87 1.00 0.99 0.95 0.92 0.88 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.73 0.71 0.68 0.65 0.75 0.72 0.69 0.66 0.76 0.73 0.70 0.68 0.77 0.74 0.72 0.69 0.79 0.76 0.73 0.70 0.80 0.77 0.74 0.71 0.82 0.79 0.76 0.73 0.83 0.80 0.77 0.74 0.85 0.82 0.79 0.76 9000 10000 11000 12000

1.53 1.44 1.36 1.28 1.19 1.11 1.02 1.00 1.00 3000

1.55 1.55 1.55 1.55 1.55 1.46 1.46 1.46 1.46 1.46 1.38 1.38 1.38 1.38 1.38 1.29 1.29 1.29 1.29 1.29 1.21 1.21 1.21 1.21 1.21 1.13 1.13 1.13 1.13 1.13 1.04 1.04 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.55 1.55 1.55 1.55 1.46 1.46 1.46 1.46 1.38 1.38 1.38 1.38 1.29 1.29 1.29 1.29 1.21 1.21 1.21 1.21 1.13 1.13 1.13 1.13 1.04 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.33 1.25 1.17 1.09 1.01 1.00 1.00 1.00 1.00 0

1.40 1.31 1.23 1.15 1.07 1.00 1.00 1.00 1.00 1000

1.46 1.38 1.30 1.21 1.13 1.05 1.00 1.00 1.00 2000

DM5126-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5126-00

-ENGLISH- page 2 of 2

129

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 260 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 LPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

30 80 3300

100%

75%

50%

bhp kW

1016 725

762 544

508 363

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

7573 2033 9014 71.7 302 63.6 150 17 889 5567 9383

7763 1580 7008 62.6 260 50.3 146 17 896 4353 7301

8293 1030 4566 48.6 200 34.8 142 17 906 2873 4782

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 148

2.2 159

6.8 466

(Corr. 15% 02)

g/bhp-hr ppm

2.0 245

2.0 242

2.4 260

(Corr. 15% 02)

g/bhp-hr ppm

3.5 739

3.2 682

2.3 451

(Corr. 15% 02)

g/bhp-hr ppm

0.52 50

0.49 46

0.36 27

%

7.6 1.51

7.6 1.47

5.7 1.30

128290 43127 28655 5920 8262 35923 22771 6399

98632 32345 22770 4934 6565 28053 17961 3962

70242 21564 19302 3948 5565 18501 12095 1361

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 130

DM5125-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/--

70 1.0/15

75 1.0/16

80 to 100 1.0/17

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

0.95 0.97 0.99 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.92 0.94 0.95 0.97 0.99 1.00 1.00 1.00 1.00 3000

0.89 0.85 0.82 0.79 0.76 0.90 0.87 0.84 0.81 0.78 0.92 0.88 0.85 0.82 0.79 0.93 0.90 0.87 0.83 0.80 0.95 0.92 0.88 0.85 0.82 0.97 0.93 0.90 0.87 0.83 0.99 0.95 0.92 0.88 0.85 1.00 0.97 0.93 0.90 0.87 1.00 0.99 0.95 0.92 0.88 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.73 0.71 0.68 0.65 0.75 0.72 0.69 0.66 0.76 0.73 0.70 0.68 0.77 0.74 0.72 0.69 0.79 0.76 0.73 0.70 0.80 0.77 0.74 0.71 0.82 0.79 0.76 0.73 0.83 0.80 0.77 0.74 0.85 0.82 0.79 0.76 9000 10000 11000 12000

1.53 1.45 1.36 1.28 1.19 1.11 1.02 1.00 1.00 3000

1.55 1.55 1.55 1.55 1.55 1.47 1.47 1.47 1.47 1.47 1.38 1.38 1.38 1.38 1.38 1.30 1.30 1.30 1.30 1.30 1.21 1.21 1.21 1.21 1.21 1.13 1.13 1.13 1.13 1.13 1.04 1.04 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.55 1.55 1.55 1.55 1.47 1.47 1.47 1.47 1.38 1.38 1.38 1.38 1.30 1.30 1.30 1.30 1.21 1.21 1.21 1.21 1.13 1.13 1.13 1.13 1.04 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.34 1.25 1.17 1.09 1.01 1.00 1.00 1.00 1.00 0

1.40 1.32 1.23 1.15 1.07 1.00 1.00 1.00 1.00 1000

1.46 1.38 1.30 1.21 1.13 1.05 1.00 1.00 1.00 2000

DM5125-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5125-00

-ENGLISH- page 2 of 2

131

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 8.0:1 Aftercooler Inlet Temperature (°F) 90 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 HPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

35 80 5000

100%

75%

50%

1077 765

808 574

538 383

7460 2289 10150 79.1 329 67.5 110 35 869 6162 10542

7535 1662 7368 70 300 50.5 104 35 858 4444 7665

8075 1130 5009 50.9 215 35 92 35 865 3044 5222

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 145

3.1 221

4.2 282

(Corr. 15% 02)

g/bhp-hr ppm

1.8 212

2.1 241

2.2 242

(Corr. 15% 02)

g/bhp-hr ppm

2.7 570

2.4 503

2.6 500

(Corr. 15% 02)

g/bhp-hr ppm

0.41 39

0.37 33

0.39 31

%

7.9 1.60

7.3 1.53

6.6 1.46

133882 45687 35631 4554 0 38642 24514 9364

101420 34266 29560 3795 0 27681 17487 6115

72458 22844 24973 3037 0 19118 12124 2484

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 132

DM5170-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0.90/21

35 0.90/23

40 0.90/24

45 1.0/25

50 1.0/26

55 1.0/28

60 1.0/29

65 1.0/30

70 1.0/32

75 1.0/33

80 to 100 1.0/35

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 3000

0.94 0.91 0.88 0.84 0.81 0.96 0.93 0.89 0.86 0.83 0.98 0.94 0.91 0.87 0.84 1.00 0.96 0.92 0.89 0.86 1.00 0.98 0.94 0.91 0.87 1.00 0.99 0.96 0.92 0.89 1.00 1.00 0.98 0.94 0.90 1.00 1.00 0.99 0.96 0.92 1.00 1.00 1.00 0.98 0.94 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.78 0.75 0.72 0.70 0.80 0.77 0.74 0.71 0.81 0.78 0.75 0.72 0.82 0.79 0.76 0.73 0.84 0.81 0.78 0.75 0.85 0.82 0.79 0.76 0.87 0.84 0.81 0.77 0.89 0.85 0.82 0.79 0.90 0.87 0.84 0.80 9000 10000 11000 12000

1.41 1.34 1.28 1.21 1.15 1.08 1.02 1.00 1.00 3000

1.46 1.51 1.51 1.51 1.51 1.39 1.44 1.44 1.44 1.44 1.33 1.38 1.38 1.38 1.38 1.26 1.31 1.31 1.31 1.31 1.19 1.24 1.24 1.24 1.24 1.13 1.18 1.18 1.18 1.18 1.06 1.11 1.11 1.11 1.11 1.00 1.04 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.51 1.51 1.51 1.51 1.44 1.44 1.44 1.44 1.38 1.38 1.38 1.38 1.31 1.31 1.31 1.31 1.24 1.24 1.24 1.24 1.18 1.18 1.18 1.18 1.11 1.11 1.11 1.11 1.04 1.04 1.04 1.04 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.26 1.20 1.13 1.07 1.01 1.00 1.00 1.00 1.00 0

1.31 1.24 1.18 1.12 1.05 1.00 1.00 1.00 1.00 1000

1.36 1.29 1.23 1.16 1.10 1.04 1.00 1.00 1.00 2000

DM5170-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5170-00

-ENGLISH- page 2 of 2

133

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 8.0:1 Aftercooler Inlet Temperature (°F) 90 Jacket Water Outlet Temperature (°F) 260 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 HPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

35 80 5000

100%

75%

50%

1077 765

808 574

538 383

7562 2305 10220 79.2 329 68.9 116 33 893 6313 10612

7640 1670 7406 70.1 300 51.1 107 33 876 4525 7703

8069 1134 5026 51 215 35.1 94 33 877 3081 5239

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 145

3.0 221

4.1 282

(Corr. 15% 02)

g/bhp-hr ppm

1.8 215

2.1 243

2.2 244

(Corr. 15% 02)

g/bhp-hr ppm

2.3 485

2.2 447

2.4 463

(Corr. 15% 02)

g/bhp-hr ppm

0.35 33

0.33 29

0.36 29

%

7.9 1.61

7.3 1.54

6.6 1.46

135706 45687 26859 5920 7744 39785 25826 9706

102837 34266 22343 4934 6442 28305 18192 6545

72409 22844 18332 3948 5285 19402 12448 2595

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 134

DM5132-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0.90/19

35 0.90/21

40 0.90/22

45 1.0/23

50 1.0/24

55 1.0/26

60 1.0/27

65 1.0/28

70 1.0/30

75 1.0/31

80 to 100 1.0/33

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 3000

0.94 0.91 0.88 0.84 0.81 0.96 0.93 0.89 0.86 0.83 0.98 0.94 0.91 0.87 0.84 1.00 0.96 0.92 0.89 0.86 1.00 0.98 0.94 0.91 0.87 1.00 0.99 0.96 0.92 0.89 1.00 1.00 0.98 0.94 0.90 1.00 1.00 0.99 0.96 0.92 1.00 1.00 1.00 0.98 0.94 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.78 0.75 0.72 0.70 0.80 0.77 0.74 0.71 0.81 0.78 0.75 0.72 0.82 0.79 0.76 0.73 0.84 0.81 0.78 0.75 0.85 0.82 0.79 0.76 0.87 0.84 0.81 0.77 0.89 0.85 0.82 0.79 0.90 0.87 0.84 0.80 9000 10000 11000 12000

1.41 1.35 1.28 1.21 1.15 1.08 1.02 1.00 1.00 3000

1.46 1.51 1.51 1.51 1.51 1.40 1.45 1.45 1.45 1.45 1.33 1.38 1.38 1.38 1.38 1.26 1.31 1.31 1.31 1.31 1.20 1.24 1.24 1.24 1.24 1.13 1.18 1.18 1.18 1.18 1.06 1.11 1.11 1.11 1.11 1.00 1.04 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.51 1.51 1.51 1.51 1.45 1.45 1.45 1.45 1.38 1.38 1.38 1.38 1.31 1.31 1.31 1.31 1.24 1.24 1.24 1.24 1.18 1.18 1.18 1.18 1.11 1.11 1.11 1.11 1.04 1.04 1.04 1.04 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.26 1.20 1.14 1.07 1.01 1.00 1.00 1.00 1.00 0

1.31 1.25 1.18 1.12 1.05 1.00 1.00 1.00 1.00 1000

1.36 1.30 1.23 1.17 1.10 1.04 1.00 1.00 1.00 2000

DM5132-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5132-00

-ENGLISH- page 2 of 2

135

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°F) 90 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 HPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

30 80 4300

100%

75%

50%

bhp kW

1077 765

808 574

538 383

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

7280 2110 9355 72.2 297 63.8 111 18 853 5627 9746

7720 1658 7353 68.6 274 50.7 108 18 847 4409 7667

8126 1052 4665 49.6 196 33.1 107 18 871 2860 4887

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 157

2.2 156

6.2 419

(Corr. 15% 02)

g/bhp-hr ppm

1.9 243

2.1 243

2.4 264

(Corr. 15% 02)

g/bhp-hr ppm

3.8 833

3.3 680

2.8 73

(Corr. 15% 02)

g/bhp-hr ppm

0.58 56

0.49 45

0.42 5

%

7.6 1.48

7.5 1.44

5.9 1.30

130657 45687 36857 4554 0 35993 22042 7561

103915 34266 32688 3795 0 27799 17171 5364

72920 22844 26799 3037 0 180261 11555 1976

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 136

DM5131-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/15

70 1.0/16

75 1.0/17.5

80 to 100 1.0/18

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.96 0.97 0.99 1.00 1.00 1.00 1.00 1.00 1.00 3000

0.92 0.89 0.85 0.82 0.79 0.94 0.90 0.87 0.84 0.81 0.95 0.92 0.88 0.85 0.82 0.97 0.93 0.90 0.87 0.83 0.99 0.95 0.92 0.88 0.85 1.00 0.97 0.93 0.90 0.86 1.00 0.99 0.95 0.92 0.88 1.00 1.00 0.97 0.93 0.90 1.00 1.00 0.99 0.95 0.92 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.76 0.73 0.70 0.68 0.77 0.75 0.72 0.69 0.79 0.76 0.73 0.70 0.80 0.77 0.74 0.71 0.82 0.79 0.76 0.73 0.83 0.80 0.77 0.74 0.85 0.82 0.78 0.75 0.86 0.83 0.80 0.77 0.88 0.85 0.82 0.78 9000 10000 11000 12000

1.44 1.37 1.30 1.23 1.16 1.09 1.02 1.00 1.00 3000

1.50 1.52 1.52 1.52 1.52 1.43 1.44 1.44 1.44 1.44 1.36 1.37 1.37 1.37 1.37 1.28 1.30 1.30 1.30 1.30 1.21 1.23 1.23 1.23 1.23 1.14 1.15 1.15 1.15 1.15 1.07 1.08 1.08 1.08 1.08 1.00 1.01 1.01 1.01 1.01 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.52 1.52 1.52 1.52 1.44 1.44 1.44 1.44 1.37 1.37 1.37 1.37 1.30 1.30 1.30 1.30 1.23 1.23 1.23 1.23 1.15 1.15 1.15 1.15 1.08 1.08 1.08 1.08 1.01 1.01 1.01 1.01 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.28 1.22 1.15 1.08 1.01 1.00 1.00 1.00 1.00 0

1.34 1.27 1.20 1.13 1.06 1.00 1.00 1.00 1.00 1000

1.39 1.32 1.25 1.18 1.11 1.04 1.00 1.00 1.00 2000

DM5131-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5131-00

-ENGLISH- page 2 of 2

137

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°F) 90 Jacket Water Outlet Temperature (°F) 260 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 HPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

30 80 4300

100%

75%

50%

bhp kW

1077 765

808 574

538 383

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

7372 2144 9509 72.9 297 64.5 116 18 870 5786 9894

7664 1685 7474 69.2 274 51.1 113 18 864 4533 7783

8067 1070 4742 49.9 196 33.2 112 18 888 2941 4960

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 158

2.2 157

6.2 421

(Corr. 15% 02)

g/bhp-hr ppm

2.0 248

2.1 248

2.5 269

(Corr. 15% 02)

g/bhp-hr ppm

3.6 775

3.1 633

2.6 68

(Corr. 15% 02)

g/bhp-hr ppm

0.54 52

0.46 43

0.39 5

%

7.7 1.52

7.6 1.49

5.9 1.34

132293 45687 27895 5920 8043 37059 23104 7686

103154 34266 23167 4934 6680 28653 18001 5452

72386 22844 19213 3948 5540 18830 12103 2009

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 138

DM5130-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/--

70 1.0/16

75 1.0/18

80 to 100 1.0/18

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.96 0.97 0.99 1.00 1.00 1.00 1.00 1.00 1.00 3000

0.92 0.89 0.85 0.82 0.79 0.94 0.90 0.87 0.84 0.81 0.95 0.92 0.88 0.85 0.82 0.97 0.93 0.90 0.87 0.83 0.99 0.95 0.92 0.88 0.85 1.00 0.97 0.93 0.90 0.86 1.00 0.99 0.95 0.92 0.88 1.00 1.00 0.97 0.93 0.90 1.00 1.00 0.99 0.95 0.92 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.76 0.73 0.70 0.68 0.77 0.75 0.72 0.69 0.79 0.76 0.73 0.70 0.80 0.77 0.74 0.71 0.82 0.79 0.76 0.73 0.83 0.80 0.77 0.74 0.85 0.82 0.78 0.75 0.86 0.83 0.80 0.77 0.88 0.85 0.82 0.78 9000 10000 11000 12000

1.44 1.37 1.30 1.23 1.16 1.09 1.02 1.00 1.00 3000

1.50 1.51 1.51 1.51 1.51 1.43 1.44 1.44 1.44 1.44 1.35 1.37 1.37 1.37 1.37 1.28 1.30 1.30 1.30 1.30 1.21 1.23 1.23 1.23 1.23 1.14 1.15 1.15 1.15 1.15 1.07 1.08 1.08 1.08 1.08 1.00 1.01 1.01 1.01 1.01 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.51 1.51 1.51 1.51 1.44 1.44 1.44 1.44 1.37 1.37 1.37 1.37 1.30 1.30 1.30 1.30 1.23 1.23 1.23 1.23 1.15 1.15 1.15 1.15 1.08 1.08 1.08 1.08 1.01 1.01 1.01 1.01 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.28 1.22 1.15 1.08 1.01 1.00 1.00 1.00 1.00 0

1.34 1.27 1.20 1.13 1.06 1.00 1.00 1.00 1.00 1000

1.39 1.32 1.25 1.18 1.11 1.04 1.00 1.00 1.00 2000

DM5130-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5130-00

-ENGLISH- page 2 of 2

139

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°F) 90 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 LPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

1.5 80 3300

100%

75%

50%

bhp kW

1077 765

808 574

538 383

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

7280 2110 9355 72.2 308 63.8 111 18 853 5627 9746

7720 1658 7353 68.6 279 50.7 108 18 847 4409 7667

8126 1052 4665 49.6 198 33.1 107 18 871 2860 4887

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 157

2.2 156

6.2 419

(Corr. 15% 02)

g/bhp-hr ppm

1.9 243

2.1 243

2.4 264

(Corr. 15% 02)

g/bhp-hr ppm

3.8 833

3.3 680

2.8 73

(Corr. 15% 02)

g/bhp-hr ppm

0.58 56

0.49 45

0.42 5

%

7.6 1.48

7.5 1.44

5.9 1.30

130657 45687 36118 4554 0 35993 22042 8300

103915 34266 32293 3795 0 27799 17171 5759

72920 22844 26670 3037 0 18261 11555 2105

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 140

DM5210-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/15

70 1.0/16

75 1.0/18

80 to 100 1.0/18

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

0.95 0.97 0.99 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.92 0.94 0.95 0.97 0.99 1.00 1.00 1.00 1.00 3000

0.89 0.85 0.82 0.79 0.76 0.90 0.87 0.84 0.81 0.78 0.92 0.88 0.85 0.82 0.79 0.93 0.90 0.87 0.83 0.80 0.95 0.92 0.88 0.85 0.82 0.97 0.93 0.90 0.87 0.83 0.99 0.95 0.92 0.88 0.85 1.00 0.97 0.93 0.90 0.87 1.00 0.99 0.95 0.92 0.88 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.73 0.71 0.68 0.65 0.75 0.72 0.69 0.66 0.76 0.73 0.70 0.68 0.77 0.74 0.72 0.69 0.79 0.76 0.73 0.70 0.80 0.77 0.74 0.71 0.82 0.79 0.76 0.73 0.83 0.80 0.77 0.74 0.85 0.82 0.79 0.76 9000 10000 11000 12000

1.43 1.36 1.29 1.22 1.16 1.09 1.02 1.00 1.00 3000

1.45 1.45 1.45 1.45 1.45 1.38 1.38 1.38 1.38 1.38 1.31 1.31 1.31 1.31 1.31 1.24 1.24 1.24 1.24 1.24 1.17 1.17 1.17 1.17 1.17 1.10 1.10 1.10 1.10 1.10 1.03 1.03 1.03 1.03 1.03 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.45 1.45 1.45 1.45 1.38 1.38 1.38 1.38 1.31 1.31 1.31 1.31 1.24 1.24 1.24 1.24 1.17 1.17 1.17 1.17 1.10 1.10 1.10 1.10 1.03 1.03 1.03 1.03 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.27 1.20 1.14 1.07 1.01 1.00 1.00 1.00 1.00 0

1.32 1.26 1.19 1.12 1.06 1.00 1.00 1.00 1.00 1000

1.38 1.31 1.24 1.17 1.11 1.04 1.00 1.00 1.00 2000

DM5210-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5210-00

-ENGLISH- page 2 of 2

141

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°F) 90 Jacket Water Outlet Temperature (°F) 260 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 LPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

1.5 80 3300

100%

75%

50%

bhp kW

1077 765

808 574

538 383

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

7372 2144 9509 72.9 307 64.5 116 18 870 5786 9894

7664 1685 7474 69.2 283 51.1 113 18 864 4533 7783

8067 1070 4742 49.9 202 33.2 112 18 888 2941 4960

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

2.0 158

2.2 157

6.2 421

(Corr. 15% 02)

g/bhp-hr ppm

2.0 248

2.1 248

2.5 269

(Corr. 15% 02)

g/bhp-hr ppm

3.6 775

3.1 633

2.6 68

(Corr. 15% 02)

g/bhp-hr ppm

0.54 52

0.46 43

0.39 5

%

7.7 1.52

7.6 1.49

5.9 1.34

132293 45687 27350 5920 7886 37059 23104 8387

103154 34266 22775 4934 6566 28653 18001 5957

72386 22844 19048 3948 5492 18830 12103 2223

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 142

DM5139-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/--

70 1.0/16

75 1.0/18

80 to 100 1.0/18

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

0.95 0.97 0.99 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.92 0.94 0.95 0.97 0.99 1.00 1.00 1.00 1.00 3000

0.89 0.85 0.82 0.79 0.76 0.90 0.87 0.84 0.81 0.78 0.92 0.88 0.85 0.82 0.79 0.93 0.90 0.87 0.83 0.80 0.95 0.92 0.88 0.85 0.82 0.97 0.93 0.90 0.87 0.83 0.99 0.95 0.92 0.88 0.85 1.00 0.97 0.93 0.90 0.87 1.00 0.99 0.95 0.92 0.88 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.73 0.71 0.68 0.65 0.75 0.72 0.69 0.66 0.76 0.73 0.70 0.68 0.77 0.74 0.72 0.69 0.79 0.76 0.73 0.70 0.80 0.77 0.74 0.71 0.82 0.79 0.76 0.73 0.83 0.80 0.77 0.74 0.85 0.82 0.79 0.76 9000 10000 11000 12000

1.43 1.36 1.29 1.22 1.16 1.09 1.02 1.00 1.00 3000

1.45 1.45 1.45 1.45 1.45 1.38 1.38 1.38 1.38 1.38 1.31 1.31 1.31 1.31 1.31 1.24 1.24 1.24 1.24 1.24 1.17 1.17 1.17 1.17 1.17 1.10 1.10 1.10 1.10 1.10 1.03 1.03 1.03 1.03 1.03 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.45 1.45 1.45 1.45 1.38 1.38 1.38 1.38 1.31 1.31 1.31 1.31 1.24 1.24 1.24 1.24 1.17 1.17 1.17 1.17 1.10 1.10 1.10 1.10 1.03 1.03 1.03 1.03 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.27 1.21 1.14 1.07 1.01 1.00 1.00 1.00 1.00 0

1.32 1.26 1.19 1.12 1.06 1.00 1.00 1.00 1.00 1000

1.38 1.31 1.24 1.17 1.11 1.04 1.00 1.00 1.00 2000

DM5139-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5139-00

-ENGLISH- page 2 of 2

143

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

NAT GAS 920 DELTEC 1.5 80 657

100%

75%

50%

1016 725

762 544

508 363

7162 2176 9649 74.2 293 71.5 134 22 988 6373 10007

7397 1660 7360 59.7 239 54.1 132 22 990 4871 7635

7857 1142 5064 45.6 177 37.1 130 22 980 3331 5259

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

0.6 46

0.6 46

0.6 46

(Corr. 15% 02)

g/bhp-hr ppm

2.2 289

2.2 277

2.2 261

(Corr. 15% 02)

g/bhp-hr ppm

5.8 1335

6.3 1414

6.8 1452

(Corr. 15% 02)

g/bhp-hr ppm

0.88 105

0.95 110

1.03 110

%

9.6 1.66

9.5 1.65

9.2 1.60

121319 43127 23263 4554 0 43993 28743 6378

93980 32345 20730 3795 0 33840 22028 3266

66549 21564 17782 3037 0 23181 14935 983

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 144

DM1977-01

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/18

70 1.0/19

75 1.0/20

80 to 100 1.0/22

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 0

0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 1.00 1000

0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 2000

0.84 0.85 0.86 0.88 0.90 0.91 0.93 0.95 0.97 3000

0.80 0.78 0.75 0.72 0.69 0.82 0.79 0.76 0.73 0.70 0.83 0.80 0.77 0.74 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.90 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.82 0.79 0.93 0.90 0.86 0.83 0.80 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.67 0.64 0.62 0.59 0.68 0.65 0.63 0.60 0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.76 0.73 0.70 0.67 0.77 0.74 0.71 0.69 9000 10000 11000 12000

1.40 1.32 1.23 1.14 1.06 1.00 1.00 1.00 1.00 3000

1.40 1.40 1.40 1.40 1.40 1.32 1.32 1.32 1.32 1.32 1.23 1.23 1.23 1.23 1.23 1.14 1.14 1.14 1.14 1.14 1.06 1.06 1.06 1.06 1.06 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.40 1.40 1.40 1.40 1.32 1.32 1.32 1.32 1.23 1.23 1.23 1.23 1.14 1.14 1.14 1.14 1.06 1.06 1.06 1.06 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.36 1.28 1.19 1.10 1.02 1.00 1.00 1.00 1.00 0

1.40 1.32 1.23 1.14 1.06 1.00 1.00 1.00 1.00 1000

1.40 1.32 1.23 1.14 1.06 1.00 1.00 1.00 1.00 2000

DM1977-01 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1977-01

-ENGLISH- page 2 of 2

145

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

NAT GAS 920 DELTEC 1.5 80 1149

100%

75%

50%

bhp kW

1016 725

762 544

508 363

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

6913 2027 8987 69.2 275 67 134 22 997 5983 9334

7192 1551 6877 57.5 229 50.9 132 22 998 4582 7146

7735 1088 4823 44.4 173 35.7 130 22 991 3200 5015

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

1.1 91

1.1 91

1.2 91

(Corr. 15% 02)

g/bhp-hr ppm

2.2 300

2.3 297

2.3 285

(Corr. 15% 02)

g/bhp-hr ppm

4.5 1061

5.0 1160

5.8 1252

(Corr. 15% 02)

g/bhp-hr ppm

0.68 80

0.76 87

0.87 92

%

9.1 1.60

9.0 1.58

8.8 1.55

117106 43127 23181 4554 0 40958 27272 5283

91382 32345 20860 3795 0 31597 20912 2781

65516 21564 17887 3037 0 22180 14529 847

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 146

DM1980-01

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/19

70 1.0/19

75 1.0/20

80 to 100 1.0/22

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 0

0.92 0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1000

0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 2000

0.85 0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 3000

0.82 0.79 0.76 0.73 0.70 0.83 0.80 0.77 0.74 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.90 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.81 0.78 0.93 0.90 0.86 0.83 0.80 0.95 0.91 0.88 0.85 0.82 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.68 0.65 0.63 0.60 0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.75 0.73 0.70 0.67 0.77 0.74 0.71 0.68 0.78 0.75 0.73 0.70 9000 10000 11000 12000

1.48 1.38 1.29 1.19 1.09 1.00 1.00 1.00 1.00 3000

1.48 1.48 1.48 1.48 1.48 1.38 1.38 1.38 1.38 1.38 1.29 1.29 1.29 1.29 1.29 1.19 1.19 1.19 1.19 1.19 1.09 1.09 1.09 1.09 1.09 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.48 1.48 1.48 1.48 1.38 1.38 1.38 1.38 1.29 1.29 1.29 1.29 1.19 1.19 1.19 1.19 1.09 1.09 1.09 1.09 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.40 1.30 1.21 1.11 1.02 1.00 1.00 1.00 1.00 0

1.47 1.37 1.28 1.18 1.08 1.00 1.00 1.00 1.00 1000

1.48 1.38 1.29 1.19 1.09 1.00 1.00 1.00 1.00 2000

DM1980-01 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1980-01

-ENGLISH- page 2 of 2

147

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 260 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

NAT GAS 920 DELTEC 1.5 80 657

100%

75%

50%

1016 725

762 544

508 363

7282 2211 9806 76.3 303 74.2 134 19 1029 6662 10172

7513 1682 7458 62.4 251 55.9 132 19 1027 5063 7738

8032 1181 5238 47.2 189 38.8 130 19 1026 3553 5437

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

0.6 46

0.6 46

0.6 46

(Corr. 15% 02)

g/bhp-hr ppm

2.2 273

2.2 267

2.3 262

(Corr. 15% 02)

g/bhp-hr ppm

4.6 1015

4.9 1062

5.7 1156

(Corr. 15% 02)

g/bhp-hr ppm

0.69 79

0.74 81

0.86 87

%

9.4 1.66

9.3 1.64

9.1 1.62

123355 43127 16694 5920 4813 45877 31172 6919

95450 32345 15136 4934 4364 34981 23671 3687

68031 21564 12843 3948 3703 24702 16600 1269

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 148

DM1989-01

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 70 0.95/16* 1.0/16*

75 1.0/18

80 to 100 1.0/19

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 0

0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 1.00 1000

0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 2000

0.84 0.85 0.86 0.88 0.90 0.91 0.93 0.95 0.97 3000

0.80 0.78 0.75 0.72 0.69 0.82 0.79 0.76 0.73 0.70 0.83 0.80 0.77 0.74 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.90 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.82 0.79 0.93 0.90 0.86 0.83 0.80 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.67 0.64 0.62 0.59 0.68 0.65 0.63 0.60 0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.76 0.73 0.70 0.67 0.77 0.74 0.71 0.69 9000 10000 11000 12000

1.39 1.31 1.22 1.14 1.05 1.00 1.00 1.00 1.00 3000

1.39 1.39 1.39 1.39 1.39 1.31 1.31 1.31 1.31 1.31 1.22 1.22 1.22 1.22 1.22 1.14 1.14 1.14 1.14 1.14 1.05 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.39 1.39 1.39 1.39 1.31 1.31 1.31 1.31 1.22 1.22 1.22 1.22 1.14 1.14 1.14 1.14 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.35 1.27 1.18 1.10 1.02 1.00 1.00 1.00 1.00 0

1.39 1.31 1.22 1.14 1.05 1.00 1.00 1.00 1.00 1000

1.39 1.31 1.22 1.14 1.05 1.00 1.00 1.00 1.00 2000

DM1989-01 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1989-01

-ENGLISH- page 2 of 2

149

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 260 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

NAT GAS 920 DELTEC 1.5 80 1149

100%

75%

50%

bhp kW

1016 725

762 544

508 363

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

7055 2063 9149 72 288 69.4 133 19 1040 6271 9503

7320 1582 7017 59.5 240 52.5 132 19 1039 4805 7290

7852 1123 4979 45.7 181 36.7 130 19 1035 3402 5174

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

1.1 91

1.2 91

1.3 91

(Corr. 15% 02)

g/bhp-hr ppm

2.3 294

2.3 294

2.5 293

(Corr. 15% 02)

g/bhp-hr ppm

3.5 792

4.0 880

4.7 966

(Corr. 15% 02)

g/bhp-hr ppm

0.52 59

0.60 65

0.71 70

%

8.9 1.60

8.8 1.59

8.6 1.58

119509 43127 16741 5920 4827 42964 29686 5925

92998 32345 15081 4934 4348 33136 22725 3177

66506 21564 12712 3948 3665 23558 16044 1058

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 150

DM1992-01

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 70 0.95/16* 1.0/16*

75 1.0/18

80 to 100 1.0/19

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 0

0.92 0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1000

0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 2000

0.85 0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 3000

0.82 0.79 0.76 0.73 0.70 0.83 0.80 0.77 0.74 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.90 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.81 0.78 0.93 0.90 0.86 0.83 0.80 0.95 0.91 0.88 0.85 0.82 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.68 0.65 0.63 0.60 0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.75 0.73 0.70 0.67 0.77 0.74 0.71 0.68 0.78 0.75 0.73 0.70 9000 10000 11000 12000

1.45 1.36 1.27 1.18 1.09 1.00 1.00 1.00 1.00 3000

1.45 1.45 1.45 1.45 1.45 1.36 1.36 1.36 1.36 1.36 1.27 1.27 1.27 1.27 1.27 1.18 1.18 1.18 1.18 1.18 1.09 1.09 1.09 1.09 1.09 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.45 1.45 1.45 1.45 1.36 1.36 1.36 1.36 1.27 1.27 1.27 1.27 1.18 1.18 1.18 1.18 1.09 1.09 1.09 1.09 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.37 1.28 1.20 1.11 1.02 1.00 1.00 1.00 1.00 0

1.44 1.35 1.26 1.17 1.08 1.00 1.00 1.00 1.00 1000

1.45 1.36 1.27 1.18 1.09 1.00 1.00 1.00 1.00 2000

DM1992-01 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1992-01

-ENGLISH- page 2 of 2

151

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

NAT GAS 920 DELTEC 1.5 80 657

100%

75%

50%

1016 725

762 544

508 363

6953 2196 9737 70.6 291 67.9 134 20 954 6275 10093

7234 1677 7436 57.8 238 52.5 132 20 964 4831 7711

7741 1161 5147 45 177 36.8 130 20 963 3343 5343

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

0.6 46

0.6 46

0.6 46

(Corr. 15% 02)

g/bhp-hr ppm

2.1 277

2.1 269

2.1 256

(Corr. 15% 02)

g/bhp-hr ppm

5.2 1222

5.8 1322

6.5 1387

(Corr. 15% 02)

g/bhp-hr ppm

0.78 96

0.87 103

0.97 105

%

9.6 1.69

9.5 1.67

9.2 1.62

117788 43127 21440 4554 0 42301 27344 6363

91913 32345 19556 3795 0 32947 21292 3267

65566 21564 17017 3037 0 22958 14735 989

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 152

DM1953-01

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 70 0.90/18* 0.95/18*

75 1.0/18

80 to 100 1.0/20

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 0

0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 1.00 1000

0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 2000

0.84 0.85 0.86 0.88 0.90 0.91 0.93 0.95 0.97 3000

0.80 0.78 0.75 0.72 0.69 0.82 0.79 0.76 0.73 0.70 0.83 0.80 0.77 0.74 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.90 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.82 0.79 0.93 0.90 0.86 0.83 0.80 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.67 0.64 0.62 0.59 0.68 0.65 0.63 0.60 0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.76 0.73 0.70 0.67 0.77 0.74 0.71 0.69 9000 10000 11000 12000

1.41 1.32 1.23 1.14 1.05 1.00 1.00 1.00 1.00 3000

1.41 1.41 1.41 1.41 1.41 1.32 1.32 1.32 1.32 1.32 1.23 1.23 1.23 1.23 1.23 1.14 1.14 1.14 1.14 1.14 1.05 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.41 1.41 1.41 1.41 1.32 1.32 1.32 1.32 1.23 1.23 1.23 1.23 1.14 1.14 1.14 1.14 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.36 1.27 1.19 1.10 1.01 1.00 1.00 1.00 1.00 0

1.41 1.32 1.23 1.14 1.05 1.00 1.00 1.00 1.00 1000

1.41 1.32 1.23 1.14 1.05 1.00 1.00 1.00 1.00 2000

DM1953-01 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1953-01

-ENGLISH- page 2 of 2

153

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

NAT GAS 920 DELTEC 1.5 80 1149

100%

75%

50%

bhp kW

1016 725

762 544

508 363

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

6712 2045 9068 65.9 273 63.9 134 20 963 5889 9411

7034 1575 6983 55.7 228 49.5 132 20 972 4567 7252

7621 1103 4890 43.7 172 35.4 130 20 973 3205 5083

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

1.1 91

1.1 91

1.2 91

(Corr. 15% 02)

g/bhp-hr ppm

2.1 287

2.2 287

2.3 279

(Corr. 15% 02)

g/bhp-hr ppm

4.0 971

4.6 1085

5.5 1196

(Corr. 15% 02)

g/bhp-hr ppm

0.60 73

0.70 81

0.82 88

%

9.1 1.63

9.0 1.60

8.8 1.56

113698 43127 21332 4554 0 39426 25945 5266

89373 32345 19505 3795 0 30930 20316 2795

64548 21564 17166 3037 0 21931 14302 849

Carbon Monoxide (CO) (9)

Total Hydorcarbons (THC) (9)

Non-Methane Hydorcarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 154

DM1956-01

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 70 0.90/18* 0.95/18*

75 1.0/18

80 to 100 1.0/20

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 0

0.92 0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1000

0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 2000

0.85 0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 3000

0.82 0.79 0.76 0.73 0.70 0.83 0.80 0.77 0.74 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.90 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.81 0.78 0.93 0.90 0.86 0.83 0.80 0.95 0.91 0.88 0.85 0.82 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.68 0.65 0.63 0.60 0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.75 0.73 0.70 0.67 0.77 0.74 0.71 0.68 0.78 0.75 0.73 0.70 9000 10000 11000 12000

1.48 1.39 1.29 1.19 1.09 1.00 1.00 1.00 1.00 3000

1.48 1.48 1.48 1.48 1.48 1.39 1.39 1.39 1.39 1.39 1.29 1.29 1.29 1.29 1.29 1.19 1.19 1.19 1.19 1.19 1.09 1.09 1.09 1.09 1.09 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.48 1.48 1.48 1.48 1.39 1.39 1.39 1.39 1.29 1.29 1.29 1.29 1.19 1.19 1.19 1.19 1.09 1.09 1.09 1.09 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.40 1.30 1.21 1.11 1.01 1.00 1.00 1.00 1.00 0

1.47 1.37 1.28 1.18 1.08 1.00 1.00 1.00 1.00 1000

1.48 1.39 1.29 1.19 1.09 1.00 1.00 1.00 1.00 2000

DM1956-01 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1956-01

-ENGLISH- page 2 of 2

155

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 260 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

NAT GAS 920 DELTEC 1.5 80 657

100%

75%

50%

1016 725

762 544

508 363

7070 2182 9675 72.4 302 70.4 134 17 993 6411 10030

7347 1696 7521 60.4 249 54.1 132 17 1000 5010 7800

7913 1187 5261 46.4 188 38.4 130 17 1008 3524 5460

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

0.5 46

0.5 46

0.5 46

(Corr. 15% 02)

g/bhp-hr ppm

2.0 262

2.1 259

2.2 256

(Corr. 15% 02)

g/bhp-hr ppm

4.1 929

4.5 993

5.4 1104

(Corr. 15% 02)

g/bhp-hr ppm

0.62 72

0.68 76

0.81 83

%

9.4 1.69

9.3 1.66

9.1 1.64

119764 43127 14126 5920 6586 43250 29025 6751

93352 32345 12512 4934 5834 34041 22852 3682

67027 21564 10931 3948 5097 24222 16194 1263

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 156

DM1965-01

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/--

70 0/--

75 0.90/16*

80 to 100 1.0/17

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 0

0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 1.00 1000

0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 2000

0.84 0.85 0.86 0.88 0.90 0.91 0.93 0.95 0.97 3000

0.80 0.78 0.75 0.72 0.69 0.82 0.79 0.76 0.73 0.70 0.83 0.80 0.77 0.74 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.90 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.82 0.79 0.93 0.90 0.86 0.83 0.80 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.67 0.64 0.62 0.59 0.68 0.65 0.63 0.60 0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.76 0.73 0.70 0.67 0.77 0.74 0.71 0.69 9000 10000 11000 12000

1.39 1.31 1.22 1.14 1.05 1.00 1.00 1.00 1.00 3000

1.39 1.39 1.39 1.39 1.39 1.31 1.31 1.31 1.31 1.31 1.22 1.22 1.22 1.22 1.22 1.14 1.14 1.14 1.14 1.14 1.05 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.39 1.39 1.39 1.39 1.31 1.31 1.31 1.31 1.22 1.22 1.22 1.22 1.14 1.14 1.14 1.14 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.35 1.26 1.18 1.10 1.01 1.00 1.00 1.00 1.00 0

1.39 1.31 1.22 1.14 1.05 1.00 1.00 1.00 1.00 1000

1.39 1.31 1.22 1.14 1.05 1.00 1.00 1.00 1.00 2000

DM1965-01 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1965-01

-ENGLISH- page 2 of 2

157

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 260 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

NAT GAS 920 DELTEC 1.5 80 1149

100%

75%

50%

bhp kW

1016 725

762 544

508 363

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

6849 2036 9027 68.5 286 66 133 17 1004 6034 9370

7159 1567 6947 57.6 239 51 132 17 1011 4668 7213

7736 1116 4946 45 181 36.3 130 17 1017 3337 5138

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

1.0 91

1.0 91

1.0 91

(Corr. 15% 02)

g/bhp-hr ppm

2.1 282

2.2 285

2.4 287

(Corr. 15% 02)

g/bhp-hr ppm

3.1 724

3.7 823

4.4 923

(Corr. 15% 02)

g/bhp-hr ppm

0.47 54

0.55 60

0.67 67

%

8.9 1.62

8.8 1.61

8.6 1.59

116030 43127 14098 5920 6573 40529 27647 5778

90953 32345 12877 4934 6004 31677 21540 3113

65524 21564 10984 3948 5121 22865 15480 1040

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 158

DM1968-01

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/--

70 0/--

75 0.90/16*

80 to 100 1.0/17

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 0

0.92 0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1000

0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 2000

0.85 0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 3000

0.82 0.79 0.76 0.73 0.70 0.83 0.80 0.77 0.74 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.90 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.81 0.78 0.93 0.90 0.86 0.83 0.80 0.95 0.91 0.88 0.85 0.82 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.68 0.65 0.63 0.60 0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.75 0.73 0.70 0.67 0.77 0.74 0.71 0.68 0.78 0.75 0.73 0.70 9000 10000 11000 12000

1.45 1.36 1.27 1.18 1.09 1.00 1.00 1.00 1.00 3000

1.45 1.45 1.45 1.45 1.45 1.36 1.36 1.36 1.36 1.36 1.27 1.27 1.27 1.27 1.27 1.18 1.18 1.18 1.18 1.18 1.09 1.09 1.09 1.09 1.09 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.45 1.45 1.45 1.45 1.36 1.36 1.36 1.36 1.27 1.27 1.27 1.27 1.18 1.18 1.18 1.18 1.09 1.09 1.09 1.09 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.37 1.28 1.19 1.10 1.01 1.00 1.00 1.00 1.00 0

1.44 1.35 1.26 1.17 1.08 1.00 1.00 1.00 1.00 1000

1.45 1.36 1.27 1.18 1.09 1.00 1.00 1.00 1.00 2000

DM1968-01 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1968-01

-ENGLISH- page 2 of 2

159

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°F) 90 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

NAT GAS 920 DELTEC 1.5 80 657

100%

75%

50%

1077 770

808 578

538 385

6728 2248 9967 71.5 294 67.9 100 24 919 6267 10330

7074 1701 7541 58.3 239 52.7 94 24 934 4794 7821

7590 1197 5309 45.6 180 37.3 91 24 934 3377 5509

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

0.5 46

0.6 46

0.6 46

(Corr. 15% 02)

g/bhp-hr ppm

2.1 286

2.1 277

2.1 261

(Corr. 15% 02)

g/bhp-hr ppm

5.5 1346

6.5 1552

7.4 1644

(Corr. 15% 02)

g/bhp-hr ppm

0.83 107

0.98 123

1.11 128

%

9.7 1.70

9.7 1.66

9.5 1.64

120739 45687 20456 4554 0 41972 26341 8066

95211 34266 19840 3795 0 32773 20487 4534

68109 22844 16998 3037 0 23269 14442 1959

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 160

DM1952-01

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/18*

70 1.0/20*

75 1.0/22

80 to 100 1.0/24

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 0

0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 1.00 1000

0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 2000

0.84 0.85 0.86 0.88 0.90 0.91 0.93 0.95 0.97 3000

0.80 0.78 0.75 0.72 0.69 0.82 0.79 0.76 0.73 0.70 0.83 0.80 0.77 0.74 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.90 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.82 0.79 0.93 0.90 0.86 0.83 0.80 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.67 0.64 0.62 0.59 0.68 0.65 0.63 0.60 0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.76 0.73 0.70 0.67 0.77 0.74 0.71 0.69 9000 10000 11000 12000

1.33 1.26 1.19 1.12 1.04 1.00 1.00 1.00 1.00 3000

1.33 1.33 1.33 1.33 1.33 1.26 1.26 1.26 1.26 1.26 1.19 1.19 1.19 1.19 1.19 1.12 1.12 1.12 1.12 1.12 1.04 1.04 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.33 1.33 1.33 1.33 1.26 1.26 1.26 1.26 1.19 1.19 1.19 1.19 1.12 1.12 1.12 1.12 1.04 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.29 1.22 1.15 1.08 1.01 1.00 1.00 1.00 1.00 0

1.33 1.26 1.19 1.12 1.04 1.00 1.00 1.00 1.00 1000

1.33 1.26 1.19 1.12 1.04 1.00 1.00 1.00 1.00 2000

DM1952-01 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1952-01

-ENGLISH- page 2 of 2

161

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°F) 90 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

NAT GAS 920 DELTEC 1.5 80 1149

100%

75%

50%

bhp kW

1077 770

808 578

538 385

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

6557 2139 9486 67 276 64.2 99 24 925 5994 9842

6813 1653 7328 56.2 228 49.9 93 24 934 4663 7606

7354 1139 5051 43.9 172 35.3 91 24 941 3234 5248

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

1.1 91

1.1 91

1.2 91

(Corr. 15% 02)

g/bhp-hr ppm

2.1 292

2.1 281

2.2 277

(Corr. 15% 02)

g/bhp-hr ppm

4.6 1139

5.4 1290

6.3 1437

(Corr. 15% 02)

g/bhp-hr ppm

0.69 87

0.81 98

0.95 107

%

9.3 1.65

9.2 1.63

9.0 1.58

117676 45687 20595 4554 0 39849 25385 6987

91705 34266 18073 3795 0 31444 19945 4124

65985 22844 16242 3037 0 22166 13965 1700

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 162

DM1955-01

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/18*

70 1.0/20*

75 1.0/22

80 to 100 1.0/24

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 0

0.92 0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1000

0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 2000

0.85 0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 3000

0.82 0.79 0.76 0.73 0.70 0.83 0.80 0.77 0.74 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.90 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.81 0.78 0.93 0.90 0.86 0.83 0.80 0.95 0.91 0.88 0.85 0.82 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.68 0.65 0.63 0.60 0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.75 0.73 0.70 0.67 0.77 0.74 0.71 0.68 0.78 0.75 0.73 0.70 9000 10000 11000 12000

1.38 1.30 1.23 1.15 1.07 1.00 1.00 1.00 1.00 3000

1.38 1.38 1.38 1.38 1.38 1.30 1.30 1.30 1.30 1.30 1.23 1.23 1.23 1.23 1.23 1.15 1.15 1.15 1.15 1.15 1.07 1.07 1.07 1.07 1.07 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.38 1.38 1.38 1.38 1.30 1.30 1.30 1.30 1.23 1.23 1.23 1.23 1.15 1.15 1.15 1.15 1.07 1.07 1.07 1.07 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.32 1.24 1.16 1.09 1.01 1.00 1.00 1.00 1.00 0

1.37 1.30 1.22 1.14 1.07 1.00 1.00 1.00 1.00 1000

1.38 1.30 1.23 1.15 1.07 1.00 1.00 1.00 1.00 2000

DM1955-01 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1955-01

-ENGLISH- page 2 of 2

163

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°F) 90 Jacket Water Outlet Temperature (°F) 260 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

NAT GAS 920 DELTEC 1.5 80 657

100%

75%

50%

1077 770

808 578

538 385

6923 2325 10311 72.4 305 70.8 100 21 957 6661 10686

7111 1775 7871 60.4 252 54.2 94 21 966 5119 8160

7601 1235 5477 46.2 190 38.2 91 21 972 3577 5681

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

0.6 46

0.6 46

0.6 46

(Corr. 15% 02)

g/bhp-hr ppm

2.1 282

2.1 271

2.2 262

(Corr. 15% 02)

g/bhp-hr ppm

5.1 1175

5.4 1227

6.3 1333

(Corr. 15% 02)

g/bhp-hr ppm

0.76 91

0.82 94

0.95 100

%

9.4 1.70

9.3 1.68

9.1 1.66

124237 45687 12954 5920 6040 44863 29118 8768

95705 34266 11300 4934 5269 34759 22589 5174

68201 22844 9960 3948 4644 24565 15883 2238

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 164

DM1964-01

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 .95/16*

70 1.0/16*

75 1.0/19

80 to 100 1.0/21

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 0

0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 1.00 1000

0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 2000

0.84 0.85 0.86 0.88 0.90 0.91 0.93 0.95 0.97 3000

0.80 0.78 0.75 0.72 0.69 0.82 0.79 0.76 0.73 0.70 0.83 0.80 0.77 0.74 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.90 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.82 0.79 0.93 0.90 0.86 0.83 0.80 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.67 0.64 0.62 0.59 0.68 0.65 0.63 0.60 0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.76 0.73 0.70 0.67 0.77 0.74 0.71 0.69 9000 10000 11000 12000

1.32 1.25 1.18 1.11 1.04 1.00 1.00 1.00 1.00 3000

1.32 1.32 1.32 1.32 1.32 1.25 1.25 1.25 1.25 1.25 1.18 1.18 1.18 1.18 1.18 1.11 1.11 1.11 1.11 1.11 1.04 1.04 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.32 1.32 1.32 1.32 1.25 1.25 1.25 1.25 1.18 1.18 1.18 1.18 1.11 1.11 1.11 1.11 1.04 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.28 1.22 1.15 1.08 1.01 1.00 1.00 1.00 1.00 0

1.32 1.25 1.18 1.11 1.04 1.00 1.00 1.00 1.00 1000

1.32 1.25 1.18 1.11 1.04 1.00 1.00 1.00 1.00 2000

DM1964-01 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1964-01

-ENGLISH- page 2 of 2

165

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°F) 90 Jacket Water Outlet Temperature (°F) 260 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

NAT GAS 920 DELTEC 1.5 80 1149

100%

75%

50%

1077 770

808 578

538 385

6705 2181 9671 69.1 288 66.8 99 21 964 6286 10034

6957 1677 7435 58 240 51.5 92 21 973 4865 7717

7441 1183 5245 45 182 36.4 91 21 979 3446 5446

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

1.0 91

1.0 91

1.2 91

(Corr. 15% 02)

g/bhp-hr ppm

2.1 289

2.2 285

2.4 286

(Corr. 15% 02)

g/bhp-hr ppm

3.9 930

4.4 1026

5.3 1137

(Corr. 15% 02)

g/bhp-hr ppm

0.59 70

0.67 76

0.80 82

%

9.0 1.64

8.9 1.63

8.6 1.61

120322 45687 13033 5920 6077 41990 27730 7610

93633 34266 11589 4934 5403 32853 21662 4586

66773 22844 9870 3948 4602 23534 15436 1972

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

btu/min btu/min btu/min btu/min btu/min btu/min btu/min btu/min

-ENGLISH- page 1 of 2 166

DM1967-01

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 70 0.90/18* 0.90/19*

75 1.0/19

80 to 100 1.0/21

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 0

0.92 0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1000

0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 2000

0.85 0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 3000

0.82 0.79 0.76 0.73 0.70 0.83 0.80 0.77 0.74 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.90 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.81 0.78 0.93 0.90 0.86 0.83 0.80 0.95 0.91 0.88 0.85 0.82 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.68 0.65 0.63 0.60 0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.75 0.73 0.70 0.67 0.77 0.74 0.71 0.68 0.78 0.75 0.73 0.70 9000 10000 11000 12000

1.37 1.29 1.22 1.14 1.07 1.00 1.00 1.00 1.00 3000

1.37 1.37 1.37 1.37 1.37 1.29 1.29 1.29 1.29 1.29 1.22 1.22 1.22 1.22 1.22 1.14 1.14 1.14 1.14 1.14 1.07 1.07 1.07 1.07 1.07 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.37 1.37 1.37 1.37 1.29 1.29 1.29 1.29 1.22 1.22 1.22 1.22 1.14 1.14 1.14 1.14 1.07 1.07 1.07 1.07 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.30 1.23 1.16 1.08 1.01 1.00 1.00 1.00 1.00 0

1.36 1.28 1.21 1.14 1.06 1.00 1.00 1.00 1.00 1000

1.37 1.29 1.22 1.14 1.07 1.00 1.00 1.00 1.00 2000

DM1967-01 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1967-01

-ENGLISH- page 2 of 2

167

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°F) 158/90 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

NAT GAS 920 DELTEC 1.5 80 657

100%

75%

50%

1077 770

808 578

538 385

6728 2248 9967 71.5 294 67.9 100 24 919 6267 10330

7074 1701 7541 58.3 239 52.7 94 24 934 4794 7821

7590 1197 5309 45.6 180 37.3 91 24 934 3377 5509

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

0.5 46

0.6 46

0.6 46

(Corr. 15% 02)

g/bhp-hr ppm

2.1 286

2.1 277

2.1 261

(Corr. 15% 02)

g/bhp-hr ppm

5.5 1346

6.5 1552

7.4 1644

(Corr. 15% 02)

g/bhp-hr ppm

0.83 107

0.98 123

1.11 128

%

9.7 1.70

9.7 1.66

9.5 1.64

120739 45687 20456 4554 0 41972 26341 4529 3537

95211 34266 19840 3795 0 32773 20487 2026 2508

68109 22844 16998 3037 0 23269 14442 389 1571

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8) Heat Rejection to Aftercooler - stage 2 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 168

DM1954-01

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/18*

70 1.0/20*

75 1.0/22

80 to 100 1.0/24

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 0

0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 1.00 1000

0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 2000

0.84 0.85 0.86 0.88 0.90 0.91 0.93 0.95 0.97 3000

0.80 0.78 0.75 0.72 0.69 0.82 0.79 0.76 0.73 0.70 0.83 0.80 0.77 0.74 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.90 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.82 0.79 0.93 0.90 0.86 0.83 0.80 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.67 0.64 0.62 0.59 0.68 0.65 0.63 0.60 0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.76 0.73 0.70 0.67 0.77 0.74 0.71 0.69 9000 10000 11000 12000

1.33 1.26 1.19 1.12 1.04 1.00 1.00 1.00 1.00 3000

1.33 1.33 1.33 1.33 1.33 1.26 1.26 1.26 1.26 1.26 1.19 1.19 1.19 1.19 1.19 1.12 1.12 1.12 1.12 1.12 1.04 1.04 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.33 1.33 1.33 1.33 1.26 1.26 1.26 1.26 1.19 1.19 1.19 1.19 1.12 1.12 1.12 1.12 1.04 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.29 1.22 1.15 1.08 1.01 1.00 1.00 1.00 1.00 0

1.33 1.26 1.19 1.12 1.04 1.00 1.00 1.00 1.00 1000

1.33 1.26 1.19 1.12 1.04 1.00 1.00 1.00 1.00 2000

DM1954-01 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1954-01

-ENGLISH- page 2 of 2

169

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°F) 158/90 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

NAT GAS 920 DELTEC 1.5 80 1149

100%

75%

50%

bhp kW

1077 770

808 578

538 385

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

6557 2139 9486 67 276 64.2 99 24 925 5994 9842

6813 1653 7328 56.2 228 49.9 93 24 934 4663 7606

7354 1139 5051 43.9 172 35.3 91 24 941 3234 5248

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

1.1 91

1.1 91

1.2 91

(Corr. 15% 02)

g/bhp-hr ppm

2.1 292

2.1 281

2.2 277

(Corr. 15% 02)

g/bhp-hr ppm

4.6 1139

5.4 1290

6.3 1437

(Corr. 15% 02)

g/bhp-hr ppm

0.69 87

0.81 98

0.95 107

%

9.3 1.65

9.2 1.63

9.0 1.58

117676 45687 20595 4554 0 39849 25385 3717 3270

91705 34266 18073 3795 0 31444 19945 1720 2404

65985 22844 16242 3037 0 22160 13965 237 1463

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8) Heat Rejection to Aftercooler - stage 2 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 170

DM1957-01

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/18*

70 1.0/20*

75 1.0/22

80 to 100 1.0/24

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 0

0.92 0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1000

0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 2000

0.85 0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 3000

0.82 0.79 0.76 0.73 0.70 0.83 0.80 0.77 0.74 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.90 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.81 0.78 0.93 0.90 0.86 0.83 0.80 0.95 0.91 0.88 0.85 0.82 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.68 0.65 0.63 0.60 0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.75 0.73 0.70 0.67 0.77 0.74 0.71 0.68 0.78 0.75 0.73 0.70 9000 10000 11000 12000

1.38 1.30 1.23 1.15 1.07 1.00 1.00 1.00 1.00 3000

1.38 1.38 1.38 1.38 1.38 1.30 1.30 1.30 1.30 1.30 1.23 1.23 1.23 1.23 1.23 1.15 1.15 1.15 1.15 1.15 1.07 1.07 1.07 1.07 1.07 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.38 1.38 1.38 1.38 1.30 1.30 1.30 1.30 1.23 1.23 1.23 1.23 1.15 1.15 1.15 1.15 1.07 1.07 1.07 1.07 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.32 1.24 1.16 1.09 1.01 1.00 1.00 1.00 1.00 0

1.37 1.30 1.22 1.14 1.07 1.00 1.00 1.00 1.00 1000

1.38 1.30 1.23 1.15 1.07 1.00 1.00 1.00 1.00 2000

DM1957-01 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1957-01

-ENGLISH- page 2 of 2

171

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°F) 158/90 Jacket Water Outlet Temperature (°F) 260 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

NAT GAS 920 DELTEC 1.5 80 657

100%

75%

50%

1077 770

808 578

538 385

6923 2325 10311 72.4 305 70.8 100 21 957 6661 10686

7111 1775 7871 60.4 252 54.2 94 21 966 5119 8160

7601 1235 5477 46.2 190 38.2 91 21 972 3577 5681

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

0.6 46

0.6 46

0.6 46

(Corr. 15% 02)

g/bhp-hr ppm

2.1 282

2.1 271

2.2 262

(Corr. 15% 02)

g/bhp-hr ppm

5.1 1175

5.4 1227

6.3 1333

(Corr. 15% 02)

g/bhp-hr ppm

0.76 91

0.82 94

0.95 100

%

9.4 1.70

9.3 1.68

9.1 1.66

124237 45687 12954 5920 6040 44863 29118 5037 3731

95705 34266 11300 4934 5269 34759 22589 2473 2701

68201 22844 9960 3948 4644 24565 15883 575 1663

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8) Heat Rejection to Aftercooler - stage 2 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 172

DM1966-01

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 70 0.95/16* 1.0/16*

75 1.0/19

80 to 100 1.0/21

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 0

0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 1.00 1000

0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 2000

0.84 0.85 0.86 0.88 0.90 0.91 0.93 0.95 0.97 3000

0.80 0.78 0.75 0.72 0.69 0.82 0.79 0.76 0.73 0.70 0.83 0.80 0.77 0.74 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.90 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.82 0.79 0.93 0.90 0.86 0.83 0.80 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.67 0.64 0.62 0.59 0.68 0.65 0.63 0.60 0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.76 0.73 0.70 0.67 0.77 0.74 0.71 0.69 9000 10000 11000 12000

1.32 1.25 1.18 1.11 1.04 1.00 1.00 1.00 1.00 3000

1.32 1.32 1.32 1.32 1.32 1.25 1.25 1.25 1.25 1.25 1.18 1.18 1.18 1.18 1.18 1.11 1.11 1.11 1.11 1.11 1.04 1.04 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.32 1.32 1.32 1.32 1.25 1.25 1.25 1.25 1.18 1.18 1.18 1.18 1.11 1.11 1.11 1.11 1.04 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.28 1.22 1.15 1.08 1.01 1.00 1.00 1.00 1.00 0

1.32 1.25 1.18 1.11 1.04 1.00 1.00 1.00 1.00 1000

1.32 1.25 1.18 1.11 1.04 1.00 1.00 1.00 1.00 2000

DM1966-01 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1966-01

-ENGLISH- page 2 of 2

173

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°F) 158/90 Jacket Water Outlet Temperature (°F) 260 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

NAT GAS 920 DELTEC 1.5 80 1149

100%

75%

50%

1077 770

808 578

538 385

6705 2181 9671 69.1 288 66.8 99 21 964 6286 10034

6957 1677 7435 58 240 51.5 92 21 973 4865 7717

7441 1183 5245 45 182 36.4 91 21 979 3446 5446

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

1.0 91

1.0 91

1.2 91

(Corr. 15% 02)

g/bhp-hr ppm

2.1 289

2.2 285

2.4 286

(Corr. 15% 02)

g/bhp-hr ppm

3.9 930

4.4 1026

5.3 1137

(Corr. 15% 02)

g/bhp-hr ppm

0.59 70

0.67 76

0.80 82

%

9.0 1.64

8.9 1.63

8.6 1.61

120322 45687 13033 5920 6077 41990 27730 4184 3426

93633 34266 11589 4934 5403 32853 21662 2044 2542

66773 22844 9870 3948 4602 23534 15436 413 1560

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8) Heat Rejection to Aftercooler - stage 2 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 174

DM1969-01

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 70 0.90/18* 0.90/19*

75 1.0/19

80 to 100 1.0/21

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°F)

130 120 110 100 90 80 70 60 50

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 0

0.92 0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1000

0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 2000

0.85 0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 3000

0.82 0.79 0.76 0.73 0.70 0.83 0.80 0.77 0.74 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.90 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.81 0.78 0.93 0.90 0.86 0.83 0.80 0.95 0.91 0.88 0.85 0.82 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.68 0.65 0.63 0.60 0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.75 0.73 0.70 0.67 0.77 0.74 0.71 0.68 0.78 0.75 0.73 0.70 9000 10000 11000 12000

1.37 1.29 1.22 1.14 1.07 1.00 1.00 1.00 1.00 3000

1.37 1.37 1.37 1.37 1.37 1.29 1.29 1.29 1.29 1.29 1.22 1.22 1.22 1.22 1.22 1.14 1.14 1.14 1.14 1.14 1.07 1.07 1.07 1.07 1.07 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.37 1.37 1.37 1.37 1.29 1.29 1.29 1.29 1.22 1.22 1.22 1.22 1.14 1.14 1.14 1.14 1.07 1.07 1.07 1.07 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.30 1.23 1.16 1.08 1.01 1.00 1.00 1.00 1.00 0

1.36 1.28 1.21 1.14 1.06 1.00 1.00 1.00 1.00 1000

1.37 1.29 1.22 1.14 1.07 1.00 1.00 1.00 1.00 2000

DM1969-01 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1969-01

-ENGLISH- page 2 of 2

175

®

G3508 TA

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 9.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type STANDARD

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 HPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

25 80 5000

100%

75%

50%

526 370

394 278

263 185

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

7406 850 3770 60.9 252 58.9 136 22.5 862 2312 3977

7854 649 2875 53.6 228 48.3 138 22.5 810 1697 3039

8739 467 2068 43.4 172 35.9 136 22.5 757 1173 2190

(Corr. 15% 02)

g/bhp-hr ppm

21.5 1431

19.9 1310

18.0 1074

(Corr. 15% 02)

g/bhp-hr ppm

1.8 191

2.0 203

2.1 191

(Corr. 15% 02)

g/bhp-hr ppm

1.5 284

2.5 475

2.2 377

(Corr. 15% 02)

g/bhp-hr ppm

0.23 14

0.37 23

0.33 18

%

2.0 1.12

2.0 1.08

1.6 1.05

64879 22303 23395 2732 0 14593 9340 1853

51603 16727 20780 2277 0 10653 6408 1164

38282 11152 17825 1822 0 7082 4089 400

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

G3508

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9)

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 176

DM5205-00

®

G3508 TA

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 35 40 45 50 55 60 0.55/14 0.55/15 0.55/16 0.55/17 0.90/14 0.90/15 0.90/16

65 1.0/16

70 1.0/18

75 1.0/20

80 1.0/22

83 to 100 1.0/23

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 3000

0.94 0.91 0.88 0.84 0.81 0.96 0.93 0.89 0.86 0.83 0.98 0.94 0.91 0.87 0.84 1.00 0.96 0.92 0.89 0.86 1.00 0.98 0.94 0.91 0.87 1.00 0.99 0.96 0.92 0.89 1.00 1.00 0.98 0.94 0.90 1.00 1.00 0.99 0.96 0.92 1.00 1.00 1.00 0.98 0.94 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.78 0.75 0.72 0.70 0.80 0.77 0.74 0.71 0.81 0.78 0.75 0.72 0.82 0.79 0.76 0.73 0.84 0.81 0.78 0.75 0.85 0.82 0.79 0.76 0.87 0.84 0.81 0.77 0.89 0.85 0.82 0.79 0.90 0.87 0.84 0.80 9000 10000 11000 12000

1.69 1.58 1.47 1.36 1.25 1.14 1.03 1.00 1.00 3000

1.77 1.86 1.86 1.86 1.86 1.66 1.75 1.75 1.75 1.75 1.55 1.63 1.63 1.63 1.63 1.44 1.52 1.52 1.52 1.52 1.33 1.41 1.41 1.41 1.41 1.22 1.30 1.30 1.30 1.30 1.11 1.18 1.18 1.18 1.18 1.00 1.07 1.07 1.07 1.07 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.86 1.86 1.86 1.86 1.75 1.75 1.75 1.75 1.63 1.63 1.63 1.63 1.52 1.52 1.52 1.52 1.41 1.41 1.41 1.41 1.30 1.30 1.30 1.30 1.18 1.18 1.18 1.18 1.07 1.07 1.07 1.07 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3508

AIR INLET TEMP.

Altitude Deration Factors

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.44 1.33 1.23 1.12 1.02 1.00 1.00 1.00 1.00 0

1.52 1.41 1.31 1.20 1.09 1.00 1.00 1.00 1.00 1000

1.60 1.49 1.39 1.28 1.17 1.06 1.00 1.00 1.00 2000

DM5205-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5205-00

-ENGLISH- page 2 of 2

177

®

G3508 TA

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 9.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type CATALYST

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

NAT GAS 920 HPG IMPCO 25 80 5000

100%

75%

50%

526 370

394 278

263 185

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

7605 766 3396 56.1 233 55 133 22.5 914 2179 3606

8056 571 2531 53 222 44.8 133 22.5 833 1535 2699

9056 440 1949 43.9 175 34.7 136 22.5 768 1121 2075

(Corr. 15% 02)

g/bhp-hr ppm

11.8 822

12.0 831

13.2 802

(Corr. 15% 02)

g/bhp-hr ppm

13.7 1567

13.1 1501

15.4 1534

(Corr. 15% 02)

g/bhp-hr ppm

2.3 455

2.0 395

2.7 467

(Corr. 15% 02)

g/bhp-hr ppm

0.34 20

0.30 18

0.40 21

%

0.5 1.00

0.5 1.00

0.5 1.00

66624 22303 25485 2732 0 14548 9453 1554

52931 16727 23148 2277 0 9874 6069 943

39668 11152 19362 1822 0 6959 4012 373

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

G3508

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9)

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 178

DM5105-00

®

G3508 TA

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 35 40 45 50 55 60 0.55/14 0.55/15 0.55/16 0.55/17 0.90/14 0.90/15 0.90/16

65 1.0/16

70 1.0/18

75 1.0/20

80 1.0/22

83 to 100 1.0/23

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 3000

0.94 0.91 0.88 0.84 0.81 0.96 0.93 0.89 0.86 0.83 0.98 0.94 0.91 0.87 0.84 1.00 0.96 0.92 0.89 0.86 1.00 0.98 0.94 0.91 0.87 1.00 0.99 0.96 0.92 0.89 1.00 1.00 0.98 0.94 0.90 1.00 1.00 0.99 0.96 0.92 1.00 1.00 1.00 0.98 0.94 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.78 0.75 0.72 0.70 0.80 0.77 0.74 0.71 0.81 0.78 0.75 0.72 0.82 0.79 0.76 0.73 0.84 0.81 0.78 0.75 0.85 0.82 0.79 0.76 0.87 0.84 0.81 0.77 0.89 0.85 0.82 0.79 0.90 0.87 0.84 0.80 9000 10000 11000 12000

1.73 1.61 1.50 1.38 1.26 1.15 1.03 1.00 1.00 3000

1.82 1.91 1.91 1.91 1.91 1.70 1.79 1.79 1.79 1.79 1.58 1.68 1.68 1.68 1.68 1.47 1.56 1.56 1.56 1.56 1.35 1.44 1.44 1.44 1.44 1.23 1.32 1.32 1.32 1.32 1.11 1.20 1.20 1.20 1.20 1.00 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.91 1.91 1.91 1.91 1.79 1.79 1.79 1.79 1.68 1.68 1.68 1.68 1.56 1.56 1.56 1.56 1.44 1.44 1.44 1.44 1.32 1.32 1.32 1.32 1.20 1.20 1.20 1.20 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3508

AIR INLET TEMP.

Altitude Deration Factors

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.46 1.35 1.24 1.13 1.02 1.00 1.00 1.00 1.00 0

1.55 1.44 1.32 1.21 1.10 1.00 1.00 1.00 1.00 1000

1.64 1.52 1.41 1.29 1.18 1.06 1.00 1.00 1.00 2000

DM5105-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5105-00

-ENGLISH- page 2 of 2

179

®

G3508 TA

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 9.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type STANDARD

Fuel LHV of Fuel (Btu/SCF) Fuel System

NAT GAS 920 LPG IMPCO

Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

1.5 80 5000

100%

75%

50%

526 370

394 278

263 185

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

7406 850 3770 60.9 252 58.9 136 22.5 862 2312 3977

7854 649 2875 53.6 228 48.3 138 22.5 810 1697 3039

8739 467 2068 43.4 172 35.9 136 22.5 757 1173 2190

(Corr. 15% 02)

g/bhp-hr ppm

21.5 1431

19.9 1310

18.0 1074

(Corr. 15% 02)

g/bhp-hr ppm

1.8 191

2.0 203

2.1 191

(Corr. 15% 02)

g/bhp-hr ppm

1.5 284

2.5 475

2.2 377

(Corr. 15% 02)

g/bhp-hr ppm

0.23 14

0.37 23

0.33 18

%

2.0 1.12

2.0 1.08

1.6 1.05

64879 22303 23293 2732 0 14593 9340 1955

51603 16727 20714 2277 0 10653 6408 1230

38282 11152 17802 1822 0 7082 4089 423

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

G3508

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9)

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 180

DM5107-00

®

G3508 TA

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 35 40 45 50 0.55/14 0.55/15 0.55/16 0.55/17 0.90/14

55 60 0.90/15 0.90/16

65 1.0/16

70 1.0/18

75 1.0/20

80 1.0/22

83 to 100 1.0/23

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 3000

0.94 0.91 0.88 0.84 0.81 0.96 0.93 0.89 0.86 0.83 0.98 0.94 0.91 0.87 0.84 1.00 0.96 0.92 0.89 0.86 1.00 0.98 0.94 0.91 0.87 1.00 0.99 0.96 0.92 0.89 1.00 1.00 0.98 0.94 0.90 1.00 1.00 0.99 0.96 0.92 1.00 1.00 1.00 0.98 0.94 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.78 0.75 0.72 0.70 0.80 0.77 0.74 0.71 0.81 0.78 0.75 0.72 0.82 0.79 0.76 0.73 0.84 0.81 0.78 0.75 0.85 0.82 0.79 0.76 0.87 0.84 0.81 0.77 0.89 0.85 0.82 0.79 0.90 0.87 0.84 0.80 9000 10000 11000 12000

1.69 1.58 1.47 1.36 1.25 1.14 1.03 1.00 1.00 3000

1.77 1.86 1.86 1.86 1.86 1.66 1.75 1.75 1.75 1.75 1.55 1.63 1.63 1.63 1.63 1.44 1.52 1.52 1.52 1.52 1.33 1.41 1.41 1.41 1.41 1.22 1.30 1.30 1.30 1.30 1.11 1.18 1.18 1.18 1.18 1.00 1.07 1.07 1.07 1.07 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.86 1.86 1.86 1.86 1.75 1.75 1.75 1.75 1.63 1.63 1.63 1.63 1.52 1.52 1.52 1.52 1.41 1.41 1.41 1.41 1.30 1.30 1.30 1.30 1.18 1.18 1.18 1.18 1.07 1.07 1.07 1.07 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3508

AIR INLET TEMP.

Altitude Deration Factors

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.44 1.33 1.23 1.12 1.02 1.00 1.00 1.00 1.00 0

1.52 1.41 1.31 1.20 1.09 1.00 1.00 1.00 1.00 1000

1.60 1.49 1.39 1.28 1.17 1.06 1.00 1.00 1.00 2000

DM5107-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5107-00

-ENGLISH- page 2 of 2

181

®

G3508 TA

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 9.0:1 Aftercooler Inlet Temperature (°F) 130 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type CATALYST

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

NAT GAS 920 LPG IMPCO 1.5 80 5000

100%

75%

50%

526 370

394 278

263 185

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

7605 766 3396 56.1 233 55 133 22.5 914 2179 3606

8056 571 2531 53 222 44.8 133 22.5 833 1535 2699

9056 440 1949 43.9 175 34.7 136 22.5 768 1121 2075

(Corr. 15% 02)

g/bhp-hr ppm

11.8 822

12.0 831

13.2 802

(Corr. 15% 02)

g/bhp-hr ppm

13.7 1567

13.1 1501

15.4 1534

(Corr. 15% 02)

g/bhp-hr ppm

2.3 455

2.0 395

2.7 467

(Corr. 15% 02)

g/bhp-hr ppm

0.34 20

0.30 18

0.40 21

%

0.5 1.00

0.5 1.00

0.5 1.00

66624 22303 25388 2732 0 14548 9453 1650

52931 16727 23086 2277 0 9860 6069 1006

39668 11152 19338 1822 0 6959 4012 397

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

G3508

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9)

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 182

DM5106-00

®

G3508 TA

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 35 40 45 50 55 60 0.55/14 0.55/15 0.55/16 0.55/17 0.90/14 0.90/15 0.90/16

65 1.0/16

70 1.0/18

75 1.0/20

80 1.0/22

83 to 100 1.0/23

(°F)

130 120 110 100 90 80 70 60 50

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1000

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 2000

0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 3000

0.94 0.91 0.88 0.84 0.81 0.96 0.93 0.89 0.86 0.83 0.98 0.94 0.91 0.87 0.84 1.00 0.96 0.92 0.89 0.86 1.00 0.98 0.94 0.91 0.87 1.00 0.99 0.96 0.92 0.89 1.00 1.00 0.98 0.94 0.90 1.00 1.00 0.99 0.96 0.92 1.00 1.00 1.00 0.98 0.94 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.78 0.75 0.72 0.70 0.80 0.77 0.74 0.71 0.81 0.78 0.75 0.72 0.82 0.79 0.76 0.73 0.84 0.81 0.78 0.75 0.85 0.82 0.79 0.76 0.87 0.84 0.81 0.77 0.89 0.85 0.82 0.79 0.90 0.87 0.84 0.80 9000 10000 11000 12000

1.73 1.61 1.50 1.38 1.26 1.15 1.03 1.00 1.00 3000

1.82 1.91 1.91 1.91 1.91 1.70 1.79 1.79 1.79 1.79 1.58 1.68 1.68 1.68 1.68 1.47 1.56 1.56 1.56 1.56 1.35 1.44 1.44 1.44 1.44 1.23 1.32 1.32 1.32 1.32 1.11 1.20 1.20 1.20 1.20 1.00 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.91 1.91 1.91 1.91 1.79 1.79 1.79 1.79 1.68 1.68 1.68 1.68 1.56 1.56 1.56 1.56 1.44 1.44 1.44 1.44 1.32 1.32 1.32 1.32 1.20 1.20 1.20 1.20 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3508

AIR INLET TEMP.

Altitude Deration Factors

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.46 1.35 1.24 1.13 1.02 1.00 1.00 1.00 1.00 0

1.55 1.44 1.32 1.21 1.10 1.00 1.00 1.00 1.00 1000

1.64 1.52 1.41 1.29 1.18 1.06 1.00 1.00 1.00 2000

DM5106-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5106-00

-ENGLISH- page 2 of 2

183

®

G3508 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.5:1 Aftercooler Inlet Temperature (°F) 194/130 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

NAT GAS 920 DELTEC 1.5 80 1149

100%

75%

50%

677 490

508 368

339 245

6911 1444 6404 72.7 305 67.2 141 16 918 4017 6630

7231 1103 4892 62.4 259 51.8 138 16 948 3139 5068

7755 765 3392 46.9 191 37 134 16 970 2213 3518

G3508

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

0.6 46

0.6 43

0.6 42

(Corr. 15% 02)

g/bhp-hr ppm

1.9 259

1.9 241

2.1 245

(Corr. 15% 02)

g/bhp-hr ppm

4.4 1040

5.0 1117

6.6 1362

(Corr. 15% 02)

g/bhp-hr ppm

0.67 82

0.76 85

0.99 100

%

9.6 1.75

9.2 1.72

8.8 1.67

78004 28732 15133 3416 0 26348 16821 2079 2307

61207 21549 13301 2847 0 21038 13590 811 1655

43763 14366 11078 2278 0 15244 9802 -221 1027

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8) Heat Rejection to Aftercooler - stage 2 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 184

DM5231-00

®

G3508 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/--

70 0/--

75 .95/16

80 to 100 1.0/16

(°F)

130 120 110 100 90 80 70 60 50

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 0

0.92 0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1000

0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 2000

0.85 0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 3000

0.82 0.79 0.76 0.73 0.70 0.83 0.80 0.77 0.74 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.90 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.81 0.78 0.93 0.90 0.86 0.83 0.80 0.95 0.91 0.88 0.85 0.82 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.68 0.65 0.63 0.60 0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.75 0.73 0.70 0.67 0.77 0.74 0.71 0.68 0.78 0.75 0.73 0.70 9000 10000 11000 12000

1.85 1.68 1.51 1.34 1.17 1.00 1.00 1.00 1.00 3000

1.85 1.85 1.85 1.85 1.85 1.68 1.68 1.68 1.68 1.68 1.51 1.51 1.51 1.51 1.51 1.34 1.34 1.34 1.34 1.34 1.17 1.17 1.17 1.17 1.17 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.85 1.85 1.85 1.85 1.68 1.68 1.68 1.68 1.51 1.51 1.51 1.51 1.34 1.34 1.34 1.34 1.17 1.17 1.17 1.17 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3508

AIR INLET TEMP.

Altitude Deration Factors

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.70 1.53 1.36 1.19 1.02 1.00 1.00 1.00 1.00 0

1.83 1.66 1.49 1.32 1.15 1.00 1.00 1.00 1.00 1000

1.85 1.68 1.51 1.34 1.17 1.00 1.00 1.00 1.00 2000

DM5231-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM5231-00

-ENGLISH- page 2 of 2

185

®

G3508 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.5:1 Aftercooler Inlet Temperature (°F) 194/130 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

NAT GAS 920 DELTEC 1.5 80 1641

100%

75%

50%

677 490

508 368

339 245

6747 1360 6030 68.4 290 63.5 141 16 932 3827 6251

7063 1042 4622 59.9 251 49.4 138 16 959 2992 4793

7639 729 3233 45.6 187 35.7 134 16 986 2135 3356

G3508

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

1.1 87

1.1 83

1.1 80

(Corr. 15% 02)

g/bhp-hr ppm

2.1 288

2.2 276

2.4 288

(Corr. 15% 02)

g/bhp-hr ppm

3.7 891

4.4 985

5.8 1215

(Corr. 15% 02)

g/bhp-hr ppm

0.56 67

0.66 72

0.87 86

%

9.1 1.69

8.6 1.66

8.3 1.61

76145 28732 15104 3416 0 25134 16307 1645 2105

59786 21549 13164 2847 0 20056 13117 636 1536

43110 14366 11004 2278 0 14734 9623 -257 970

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8) Heat Rejection to Aftercooler - stage 2 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 186

DM5232-00

®

G3508 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/--

70 0/--

75 .95/16

80 to 100 1.0/16

(°F)

130 120 110 100 90 80 70 60 50

0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 1000

0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 1.00 2000

0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 3000

0.83 0.80 0.77 0.75 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.89 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.81 0.78 0.93 0.89 0.86 0.83 0.80 0.95 0.91 0.88 0.85 0.81 0.97 0.93 0.90 0.86 0.83 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.75 0.73 0.70 0.67 0.77 0.74 0.71 0.68 0.78 0.75 0.72 0.70 0.80 0.77 0.74 0.71 9000 10000 11000 12000

1.99 1.81 1.62 1.43 1.25 1.06 1.00 1.00 1.00 3000

1.99 1.99 1.99 1.99 1.99 1.81 1.81 1.81 1.81 1.81 1.62 1.62 1.62 1.62 1.62 1.43 1.43 1.43 1.43 1.43 1.25 1.25 1.25 1.25 1.25 1.06 1.06 1.06 1.06 1.06 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.99 1.99 1.99 1.99 1.81 1.81 1.81 1.81 1.62 1.62 1.62 1.62 1.43 1.43 1.43 1.43 1.25 1.25 1.25 1.25 1.06 1.06 1.06 1.06 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3508

AIR INLET TEMP.

Altitude Deration Factors

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.76 1.57 1.39 1.21 1.02 1.00 1.00 1.00 1.00 0

1.90 1.71 1.53 1.34 1.16 1.00 1.00 1.00 1.00 1000

1.99 1.81 1.62 1.43 1.25 1.06 1.00 1.00 1.00 2000

DM5232-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM5232-00

-ENGLISH- page 2 of 2

187

®

G3508 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.5:1 Aftercooler Inlet Temperature (°F) 194/90 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

NAT GAS 920 DELTEC 1.5 80 1149

100%

75%

50%

717 519

538 389

359 260

6668 1505 6674 73.6 308 67.8 105 20 847 3972 6907

6935 1147 5086 62.6 255 52.1 100 20 876 3095 5266

7438 800 3546 47.4 189 37.3 94 20 889 2180 3674

G3508

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

0.5 45

0.6 45

0.6 44

(Corr. 15% 02)

g/bhp-hr ppm

2.0 259

1.9 237

2.1 239

(Corr. 15% 02)

g/bhp-hr ppm

5.0 1254

5.6 1322

7.3 1603

(Corr. 15% 02)

g/bhp-hr ppm

0.75 104

0.84 105

1.10 124

%

10.2 1.77

9.7 1.74

9.4 1.70

79731 30439 14786 3416 0 25555 15283 2215 3417

62187 22830 12955 2847 0 20300 12359 771 2492

44469 15220 10896 2278 0 14693 8847 -261 1651

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8) Heat Rejection to Aftercooler - stage 2 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 188

DM5233-00

®

G3508 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0.85/16

70 0.92/18

75 1.0/18

80 to 100 1.0/20

(°F)

130 120 110 100 90 80 70 60 50

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 0

0.92 0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1000

0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 2000

0.85 0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 3000

0.82 0.79 0.76 0.73 0.70 0.83 0.80 0.77 0.74 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.90 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.81 0.78 0.93 0.90 0.86 0.83 0.80 0.95 0.91 0.88 0.85 0.82 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.68 0.65 0.63 0.60 0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.75 0.73 0.70 0.67 0.77 0.74 0.71 0.68 0.78 0.75 0.73 0.70 9000 10000 11000 12000

1.69 1.55 1.41 1.27 1.13 1.00 1.00 1.00 1.00 3000

1.69 1.69 1.69 1.69 1.69 1.55 1.55 1.55 1.55 1.55 1.41 1.41 1.41 1.41 1.41 1.27 1.27 1.27 1.27 1.27 1.13 1.13 1.13 1.13 1.13 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.69 1.69 1.69 1.69 1.55 1.55 1.55 1.55 1.41 1.41 1.41 1.41 1.27 1.27 1.27 1.27 1.13 1.13 1.13 1.13 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3508

AIR INLET TEMP.

Altitude Deration Factors

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.57 1.43 1.29 1.16 1.02 1.00 1.00 1.00 1.00 0

1.67 1.54 1.40 1.26 1.12 1.00 1.00 1.00 1.00 1000

1.69 1.55 1.41 1.27 1.13 1.00 1.00 1.00 1.00 2000

DM5233-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM5233-00

-ENGLISH- page 2 of 2

189

®

G3508 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.5:1 Aftercooler Inlet Temperature (°F) 194/90 Jacket Water Outlet Temperature (°F) 210 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (Btu/SCF) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (psig) Methane Number at Conditions Shown Rated Altitude (ft) at 77°F Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

bhp kW

NAT GAS 920 DELTEC 1.5 80 1641

100%

75%

50%

717 519

538 389

359 260

6480 1431 6344 70 291 64.6 105 20 847 3778 6570

6790 1095 4855 60.4 246 50 100 20 887 2981 5031

7278 760 3371 45.8 182 35.7 94 20 896 2085 3497

G3508

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 77°F, 28.8 in Hg) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 29.7 in Hg) Exhaust Gas Mass Flow (Wet)

Btu/bhp-hr SCFM lb/hr in. HG (abs) °F in. HG (abs) °F °BTDC °F CFM lb/hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02)

g/bhp-hr ppm

1.0 91

1.1 89

1.1 88

(Corr. 15% 02)

g/bhp-hr ppm

2.0 287

2.0 268

2.2 279

(Corr. 15% 02)

g/bhp-hr ppm

4.3 1089

5.0 1196

6.5 1459

(Corr. 15% 02)

g/bhp-hr ppm

0.65 87

0.75 92

0.98 108

%

9.8 1.73

9.3 1.70

8.9 1.66

77481 30439 14654 3416 0 24051 14555 1745 3171

60885 22830 12716 2847 0 19590 12075 591 2348

43510 15220 10765 2278 0 14036 8549 -330 1553

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 77°F) (2) Heat Rejection to Exhaust (LHV to 350°F) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8) Heat Rejection to Aftercooler - stage 2 (3) (7) (8)

Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min Btu/min

-ENGLISH- page 1 of 2 190

DM5234-00

®

G3508 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0.86/16

70 0.92/18

75 1.0/18

80 to 100 1.0/20

(°F)

130 120 110 100 90 80 70 60 50

0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 1000

0.90 0.91 0.93 0.95 0.96 0.98 1.00 1.00 1.00 2000

0.87 0.88 0.90 0.91 0.93 0.95 0.96 0.98 1.00 3000

0.83 0.80 0.77 0.75 0.72 0.85 0.82 0.79 0.76 0.73 0.86 0.83 0.80 0.77 0.74 0.88 0.85 0.82 0.79 0.76 0.89 0.86 0.83 0.80 0.77 0.91 0.88 0.85 0.81 0.78 0.93 0.89 0.86 0.83 0.80 0.95 0.91 0.88 0.85 0.81 0.97 0.93 0.90 0.86 0.83 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

0.69 0.66 0.64 0.61 0.70 0.68 0.65 0.62 0.71 0.69 0.66 0.64 0.73 0.70 0.67 0.65 0.74 0.71 0.69 0.66 0.75 0.73 0.70 0.67 0.77 0.74 0.71 0.68 0.78 0.75 0.72 0.70 0.80 0.77 0.74 0.71 9000 10000 11000 12000

1.79 1.64 1.49 1.34 1.20 1.05 1.00 1.00 1.00 3000

1.79 1.79 1.79 1.79 1.79 1.64 1.64 1.64 1.64 1.64 1.49 1.49 1.49 1.49 1.49 1.34 1.34 1.34 1.34 1.34 1.20 1.20 1.20 1.20 1.20 1.05 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 4000 5000 6000 7000 8000 ALTITUDE (FEET ABOVE SEA LEVEL)

1.79 1.79 1.79 1.79 1.64 1.64 1.64 1.64 1.49 1.49 1.49 1.49 1.34 1.34 1.34 1.34 1.20 1.20 1.20 1.20 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 9000 10000 11000 12000

G3508

AIR INLET TEMP.

Altitude Deration Factors

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°F)

130 120 110 100 90 80 70 60 50

1.61 1.46 1.31 1.17 1.02 1.00 1.00 1.00 1.00 0

1.72 1.57 1.42 1.27 1.13 1.00 1.00 1.00 1.00 1000

1.79 1.64 1.49 1.34 1.20 1.05 1.00 1.00 1.00 2000

DM5234-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM5234-00

-ENGLISH- page 2 of 2

191

Notes

192

Metric Units Section

193

194

G35 G3516 High Speed

Jacket Jacket Water Water System System Performance Performance

TM TM9732-00

m of H2O 16 15 14 13

External Restriction

12 11 10 9 8 7 6 5 4 3 2

B

1 0

A

700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000

L/min

External Water Flow

Curve Data Curve Label Engine Speed rpm Pump Speed rpm External Flow L/min 800 900 1000 1100 1200 1300 1400 1500 1600 1700

A B 1800 1500 2400 2000 -----------------------External Resistance------------------------------------Meter of Water --------------------10.8 8.9 7.0 14.5 5.1 12.3 3.3 10.1 1.4 7.9 5.7 3.5 1.2

Engine equipped with water cooled exhaust manifolds or with dry exhaust manifolds and JW aftercooler. 2W9729 JW Pump Drive Ratio 1.33:1 For high speed (1301 - 1800 rpm) ratings Curves indicate maximum allowable external resistance. Do not project curves.

195

G35 G3516 Low Speed

Jacket Jacket Water Water System System Performance Performance

TM TM9733-00

m of H2O 16 15 14 13

External Restriction

12 11 10 9 8 7 6 5 4 3 2

B

1 0

A

700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000

L/min

External Water Flow

Curve Data Curve Label Engine Speed rpm Pump Speed rpm External Flow L/min 900 1000 1100 1200 1300 1400 1500 1600 1700

196

A B 1200 1000 2400 2000 -----------------------External Resistance------------------------------------Meter of Water --------------------8.9 7.0 14.5 5.1 12.3 3.3 10.1 1.4 7.9 5.7 3.5 1.2

Engine equipped with water cooled exhaust manifolds or with dry exhaust manifolds and JW aftercooler. 2W9729 JW Pump Drive Ratio 2:1 For low speed (1300 rpm and below) ratings Curves indicate maximum allowable external resistance. Do not project curves.

G35 G3512 High Speed

Jacket Jacket Water Water System System Performance Performance

TM DM0569-00

m of H2O 16 15 14 13

External Restriction

12 11 10 9 8 7 6 5 4 3 2 1 0

A

B 600

800

1000

1200

1400

1600

1800

2000

L/min

External Water Flow

Curve Data Curve Label Engine Speed rpm Pump Speed rpm External Flow L/min 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600

A B 1800 1500 2400 2000 -----------------------External Resistance------------------------------------Meter of Water --------------------12.9 16.7 11.4 15.2 9.9 13.6 8.4 12.0 6.9 10.5 5.4 8.9 3.9 7.3 2.5 5.8 1.0 4.2 2.6 1.1

Engine equipped with water cooled exhaust manifolds or with dry exhaust manifolds and JW aftercooler. 2W9729 JW Pump Drive Ratio 1.33:1 For high speed (1301-1800 rpm) ratings Curves indicate maximum allowable external resistance. Do not project curves.

197

G35 G3512 Low Speed

Jacket Jacket Water Water System System Performance Performance

TM DM0570-00

ft of H2O 60 55 50 45

External Restriction

40 35 30 25 20 15 10 5

B 0

A

80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440

g/min

External Water Flow

Curve Data Curve Label Engine Speed rpm Pump Speed rpm External Flow L/min 500 600 700 800 900 1000 1100 1200 1300 1400 1500

198

A B 1200 1000 2400 2000 -----------------------External Resistance------------------------------------Meter of Water --------------------9.2 14.5 7.8 13.0 6.4 11.5 5.0 10.0 3.7 8.6 2.3 7.1 0.9 5.6 4.1 2.6 1.2

1W9954 AW Pump Drive Ratio 2:1 For low speed (1300 rpm and below) ratings Curves indicate maximum allowable external resistance. Do not project curves.

G35 G3508 High Speed

Jacket Jacket Water Water System System Performance Performance

TM TM3095-03

External Restriction

m of H2O 11 10 9 8 7 6 5 4 3 2

B

1 0

A 500

600

700

800

900

1000

1100

1200

1300

1400

1500

L/min

External Water Flow

Curve Data Curve Label Engine Speed rpm Pump Speed rpm External Flow L/min 600 700 800 900 1000 1100 1200 1300 1320 1360 1400

A B 1800 1500 2400 2000 -----------------------External Resistance------------------------------------Meter of Water --------------------10.6 8.8 6.9 11.4 5.1 9.3 3.3 7.1 1.5 4.9 2.7 2.3 1.4 0.5

Engine equipped with water cooled exhaust manifolds or with dry exhaust manifolds and JW aftercooler. 2W9726 JW Pump Drive Ratio 1.33 to 1 For high speed (1301-1800 rpm) ratings Curves indicate maximum allowable external resistance. Do not project curves.

199

G35 G3508 Low Speed

Jacket Jacket Water Water System System Performance Performance

TM TM3089-03

External Restriction

m of H2O 11 10 9 8 7 6 5 4 3 2

B

1 0

A 500

600

700

800

900 1000 1100 1200 1300 1400 1500 L/min

External Water Flow

Curve Data Curve Label Engine Speed rpm Pump Speed rpm External Flow L/min 700 800 900 1000 1100 1200 1300 1400

200

A B 1200 1000 2400 2000 -----------------------External Resistance------------------------------------Meter of Water --------------------8.7 6.9 11.4 5.1 9.3 3.3 7.1 1.5 4.9 2.7 0.6

Engine equipped with water cooled exhaust manifolds or with dry exhaust manifolds and JW aftercooler. 2W9726 JW Pump Drive Ratio 2.0 to 1 For low speed (1300 rpm and below) ratings Curves indicate maximum allowable external resistance. Do not project curves.

G35 G3500 High Speed

Auxiliary Auxiliary Water Water System System Performance Performance

TM DM0571-00

m of H2O 9

External Restriction

8 7 6 5 4 3

A

2

B

1 0

200

250

300

350

400

450

500

550

600

L/min

External Water Flow

Curve Data Curve Label Engine Speed rpm Pump Speed rpm External Flow L/min 300 320 340 350 360 370 380 390 400 410 420 430 440 450 460 470

A B 1800 1500 2400 2000 -----------------------External Resistance------------------------------------Meter of Water --------------------6.2 5.2 4.3 3.8 8.9 3.3 8.4 2.8 7.8 2.4 7.3 1.9 6.8 1.4 6.2 5.7 5.2 4.6 4.1 3.5 3.0

1W9954 AW Pump Drive Ratio 1.33:1 For high speed (1301-1800 rpm) ratings Curves indicate maximum allowable external resistance. Do not project curves.

201

G35 G3500 Low Speed

Auxiliary Water System Performance Auxiliary Water System Performance

TM DM0572-00

m of H2O

10

External Restriction

9 8 7 6 5 4

A

3 2

B

1 150

0

200

250

300

350

400

450

500

550

L/min

External Water Flow

Curve Data Curve Label Engine Speed rpm Pump Speed rpm External Flow L/min 300 320 330 350 360 370 390 400 420 430 450 460 470

202

A B 1200 1000 2400 2000 -----------------------External Resistance------------------------------------Meter of Water --------------------6.2 5.2 4.8 3.8 8.9 3.3 8.4 2.8 7.3 1.9 6.8 1.4 5.7 5.2 4.1 3.5 3.0

1W9954 AW Pump Drive Ratio 2:1 For low speed (1300 rpm and below) ratings Curves indicate maximum allowable external resistance. Do not project curves.

G3516 Jacket Water Flow vs Pressure Drop Across Block for Cogen Engine 120 Max

Pressure Drop Across Block (kPa)

110 100 90 80 70 60 50 40

Min

30 1300

1400

1500

1600

1700

1800

1900

2000

2100

Jacket Water Flow (liters/min)

G3512 Jacket Water Flow vs Pressure Drop Across Block for Cogen Engine 120 Pressure Drop Across Block (kPa)

110 Max

100 90 80 70 60 50 40 Min 30 950 1050

1150

1250

1350

1450

1550

1650

1750

1850

1950

Jacket Water Flow (liters/min) 203

G3508 Jacket Water Flow vs Pressure Drop Across Block for Cogen Engine 100 Pressure Drop Across Block (kPa)

90 Max

80 70 60 50 40 30 20 10

Min 500

600

700

800

900

1000

1100

Jacket Water Flow (liters/min)

204

1200

1300

1400

1500

Notes

205

®

G3516 TA

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 9.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type STANDARD

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 HPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

242 80 1524

100%

75%

50%

785 740

589 555

393 370

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

10.63 3.09 3.99 208 131 199 57 22.5 462 3.37 4.21

11.19 3.29 4.25 200 115 168 56 22.5 449 3.59 4.49

12.28 3.82 4.94 177 94 135 56 22.5 423 4.17 5.22

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

26.7 1476 551

23.4 1190 707

23.4 798 1263

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.6 139 466

1.8 138 463

1.8 122 411

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.0 301 573

2.0 300 572

2.7 338 643

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.30 15 86

0.31 14 86

0.41 16 97

%

2.0 1.11

1.6 1.11

1.3 1.10

kW kW kW kW kW kW kW kW

2317 785 911 80 0 472 361 69

1829 589 763 67 0 366 278 45

1338 393 600 53 0 268 198 24

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9)

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC206

page 1 of 2

DM5144-00

®

G3516 TA

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0

30 0.59/14

35 0.59/15

40 0.59/16

45 0.59/17

50 0.90/14

55 0.90/15

60 0.90/16

65 1.0/16

70 1.0/18

75 1.0/20

80 to 100 1.0/23

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

0.84 0.86 0.87 0.88 0.90 0.91 0.93 0.95 0.96 2250

0.82 0.83 0.84 0.86 0.87 0.89 0.90 0.92 0.93 2500

0.79 0.80 0.82 0.83 0.84 0.86 0.87 0.89 0.90 2750

0.77 0.78 0.79 0.80 0.82 0.83 0.85 0.86 0.88 3000

1.49 1.56 1.62 1.69 1.69 1.69 1.41 1.47 1.53 1.60 1.60 1.60 1.32 1.38 1.44 1.51 1.52 1.52 1.23 1.29 1.36 1.42 1.43 1.43 1.15 1.21 1.27 1.33 1.34 1.34 1.06 1.12 1.18 1.24 1.25 1.25 1.00 1.03 1.09 1.15 1.16 1.16 1.00 1.00 1.00 1.06 1.07 1.07 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.69 1.60 1.52 1.43 1.34 1.25 1.16 1.07 1.00 2250

1.69 1.60 1.52 1.43 1.34 1.25 1.16 1.07 1.00 2500

1.69 1.60 1.52 1.43 1.34 1.25 1.16 1.07 1.00 2750

1.69 1.60 1.52 1.43 1.34 1.25 1.16 1.07 1.00 3000

G3516

1.00 0.98 0.95 0.93 0.90 0.87 1.00 1.00 0.97 0.94 0.91 0.88 1.00 1.00 0.98 0.95 0.93 0.90 1.00 1.00 1.00 0.97 0.94 0.91 1.00 1.00 1.00 0.99 0.96 0.93 1.00 1.00 1.00 1.00 0.97 0.94 1.00 1.00 1.00 1.00 0.99 0.96 1.00 1.00 1.00 1.00 1.00 0.98 1.00 1.00 1.00 1.00 1.00 0.99 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.31 1.22 1.14 1.05 1.00 1.00 1.00 1.00 1.00 0

1.37 1.28 1.20 1.11 1.03 1.00 1.00 1.00 1.00 250

1.43 1.34 1.26 1.17 1.09 1.00 1.00 1.00 1.00 500

DM5144-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5144-00

-METRIC-

page 2 of 2

207

®

G3516 TA

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 9.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type CATALYST

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

NAT GAS 36.2 HPG IMPCO 241 80 1524

100%

75%

50%

785 740

589 555

393 370

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

10.9 2.71 3.5 206 125 185 56 22.5 489 2.99 3.73

11.43 2.77 3.58 196 114 156 56 22.5 457 3.06 3.82

13.01 2.91 3.76 177 98 131 55 22.5 419 3.22 4.02

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

15.3 819 4523

15.6 818 4515

15.6 770 4252

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

17.3 1523 5130

13.6 1164 3919

21.7 1762 5935

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.8 295 562

2.4 394 751

3.2 503 958

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.27 13 85

0.37 17 113

0.49 22 144

%

0.3 0.94

0.2 0.92

0.2 0.87

kW kW kW kW kW kW kW kW

2374 785 1006 80 0 451 352 52

1869 589 852 67 0 327 246 34

1418 393 741 53 0 213 154 18

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9)

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC208

page 1 of 2

DM5143-00

®

G3516 TA

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0

30 0.59/14

35 0.59/15

40 0.59/16

45 0.59/17

50 0.90/14

55 0.90/15

60 0.90/16

65 1.0/16

70 1.0/18

75 1.0/20

80 to 100 1.0/22.5

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

0.84 0.86 0.87 0.88 0.90 0.91 0.93 0.95 0.96 2250

0.82 0.83 0.84 0.86 0.87 0.89 0.90 0.92 0.93 2500

0.79 0.80 0.82 0.83 0.84 0.86 0.87 0.89 0.90 2750

0.77 0.78 0.79 0.80 0.82 0.83 0.85 0.86 0.88 3000

1.55 1.62 1.69 1.77 1.77 1.77 1.45 1.52 1.59 1.67 1.67 1.67 1.36 1.43 1.49 1.56 1.57 1.57 1.26 1.33 1.39 1.46 1.47 1.47 1.16 1.23 1.30 1.36 1.37 1.37 1.07 1.13 1.20 1.26 1.27 1.27 1.00 1.03 1.10 1.16 1.17 1.17 1.00 1.00 1.00 1.06 1.07 1.07 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.77 1.67 1.57 1.47 1.37 1.27 1.17 1.07 1.00 2250

1.77 1.67 1.57 1.47 1.37 1.27 1.17 1.07 1.00 2500

1.77 1.67 1.57 1.47 1.37 1.27 1.17 1.07 1.00 2750

1.77 1.67 1.57 1.47 1.37 1.27 1.17 1.07 1.00 3000

G3516

1.00 0.98 0.95 0.93 0.90 0.87 1.00 1.00 0.97 0.94 0.91 0.88 1.00 1.00 0.98 0.95 0.93 0.90 1.00 1.00 1.00 0.97 0.94 0.91 1.00 1.00 1.00 0.99 0.96 0.93 1.00 1.00 1.00 1.00 0.97 0.94 1.00 1.00 1.00 1.00 0.99 0.96 1.00 1.00 1.00 1.00 1.00 0.98 1.00 1.00 1.00 1.00 1.00 0.99 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.35 1.25 1.16 1.06 1.00 1.00 1.00 1.00 1.00 0

1.41 1.32 1.22 1.13 1.03 1.00 1.00 1.00 1.00 250

1.48 1.39 1.29 1.19 1.10 1.00 1.00 1.00 1.00 500

DM5143-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5143-00

-METRIC-

page 2 of 2

209

®

G3516 TA

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 9.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type STANDARD

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 LPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

10 80 1524

100%

75%

50%

785 740

589 555

393 370

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

10.63 3.09 3.99 208 131 199 57 22.5 462 3.37 4.21

11.19 3.29 4.25 200 115 168 56 22.5 449 3.59 4.49

12.28 3.82 4.94 177 94 135 56 22.5 423 4.17 5.22

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

26.7 1386 7656

23.4 1116 6165

23.4 945 5219

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.6 139 466

1.8 138 463

1.8 122 411

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.0 301 573

2.0 300 572

2.7 338 643

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.30 15 86

0.31 14 86

0.41 16 97

%

2.0 1.11

1.6 1.11

1.3 1.10

kW kW kW kW kW kW kW kW

2317 785 907 80 0 472 361 73

1829 589 760 67 0 366 278 47

1338 393 599 53 0 268 198 25

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9)

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC210

page 1 of 2

DM5146-00

®

G3516 TA

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0

30 0.59/14

35 0.59/15

40 0.59/16

45 0.59/17

50 0.90/14

55 0.90/15

60 0.90/16

65 1.0/16

70 1.0/18

75 1.0/20

80 to 100 1.0/23

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

0.84 0.86 0.87 0.88 0.90 0.91 0.93 0.95 0.96 2250

0.82 0.83 0.84 0.86 0.87 0.89 0.90 0.92 0.93 2500

0.79 0.80 0.82 0.83 0.84 0.86 0.87 0.89 0.90 2750

0.77 0.78 0.79 0.80 0.82 0.83 0.85 0.86 0.88 3000

1.49 1.56 1.62 1.69 1.69 1.69 1.41 1.47 1.53 1.60 1.60 1.60 1.32 1.38 1.44 1.51 1.52 1.52 1.23 1.29 1.36 1.42 1.43 1.43 1.15 1.21 1.27 1.33 1.34 1.34 1.06 1.12 1.18 1.24 1.25 1.25 1.00 1.03 1.09 1.15 1.16 1.16 1.00 1.00 1.00 1.06 1.07 1.07 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.69 1.60 1.52 1.43 1.34 1.25 1.16 1.07 1.00 2250

1.69 1.60 1.52 1.43 1.34 1.25 1.16 1.07 1.00 2500

1.69 1.60 1.52 1.43 1.34 1.25 1.16 1.07 1.00 2750

1.69 1.60 1.52 1.43 1.34 1.25 1.16 1.07 1.00 3000

G3516

1.00 0.98 0.95 0.93 0.90 0.87 1.00 1.00 0.97 0.94 0.91 0.88 1.00 1.00 0.98 0.95 0.93 0.90 1.00 1.00 1.00 0.97 0.94 0.91 1.00 1.00 1.00 0.99 0.96 0.93 1.00 1.00 1.00 1.00 0.97 0.94 1.00 1.00 1.00 1.00 0.99 0.96 1.00 1.00 1.00 1.00 1.00 0.98 1.00 1.00 1.00 1.00 1.00 0.99 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.31 1.22 1.14 1.05 1.00 1.00 1.00 1.00 1.00 0

1.37 1.28 1.20 1.11 1.03 1.00 1.00 1.00 1.00 250

1.43 1.34 1.26 1.17 1.09 1.00 1.00 1.00 1.00 500

DM5146-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5146-00

-METRIC-

page 2 of 2

211

®

G3516 TA

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 9.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type CATALYST

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

NAT GAS 36.2 LPG IMPCO 10 80 1524

100%

75%

50%

785 740

589 555

393 370

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

10.9 2.71 3.5 206 125 185 56 22.5 489 2.97 3.72

11.43 2.77 3.58 196 114 156 56 22.5 457 3.04 3.8

13.01 2.91 3.76 177 98 131 55 22.5 419 3.19 3.99

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

15.3 822 4539

15.3 804 4439

15.3 763 4212

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

17.3 1529 5149

17.5 1514 5098

21.7 1775 5978

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.8 295 562

2.4 394 751

3.2 503 958

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.27 13 85

0.37 17 113

0.49 22 144

%

0.3 1.01

0.2 0.99

0.2 0.97

kW kW kW kW kW kW kW kW

2374 785 1007 80 0 447 348 55

1869 589 854 67 0 323 243 36

1418 393 743 53 0 210 151 19

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9)

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC212

page 1 of 2

DM5145-00

®

G3516 TA

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0

30 0.59/14

35 0.59/15

40 0.59/16

45 0.59/17

50 55 0.90/14 0.90/15

60 0.90/16

65 1.0/16

70 1.0/18

75 1.0/20

80 to 100 1.0/23

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

0.84 0.86 0.87 0.88 0.90 0.91 0.93 0.95 0.96 2250

0.82 0.83 0.84 0.86 0.87 0.89 0.90 0.92 0.93 2500

0.79 0.80 0.82 0.83 0.84 0.86 0.87 0.89 0.90 2750

0.77 0.78 0.79 0.80 0.82 0.83 0.85 0.86 0.88 3000

1.55 1.62 1.69 1.77 1.77 1.77 1.45 1.52 1.59 1.67 1.67 1.67 1.36 1.43 1.49 1.56 1.57 1.57 1.26 1.33 1.39 1.46 1.47 1.47 1.16 1.23 1.30 1.36 1.37 1.37 1.07 1.13 1.20 1.26 1.27 1.27 1.00 1.03 1.10 1.16 1.17 1.17 1.00 1.00 1.00 1.06 1.07 1.07 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.77 1.67 1.57 1.47 1.37 1.27 1.17 1.07 1.00 2250

1.77 1.67 1.57 1.47 1.37 1.27 1.17 1.07 1.00 2500

1.77 1.67 1.57 1.47 1.37 1.27 1.17 1.07 1.00 2750

1.77 1.67 1.57 1.47 1.37 1.27 1.17 1.07 1.00 3000

G3516

1.00 0.98 0.95 0.93 0.90 0.87 1.00 1.00 0.97 0.94 0.91 0.88 1.00 1.00 0.98 0.95 0.93 0.90 1.00 1.00 1.00 0.97 0.94 0.91 1.00 1.00 1.00 0.99 0.96 0.93 1.00 1.00 1.00 1.00 0.97 0.94 1.00 1.00 1.00 1.00 0.99 0.96 1.00 1.00 1.00 1.00 1.00 0.98 1.00 1.00 1.00 1.00 1.00 0.99 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.35 1.25 1.16 1.06 1.00 1.00 1.00 1.00 1.00 0

1.41 1.32 1.22 1.13 1.03 1.00 1.00 1.00 1.00 250

1.48 1.39 1.29 1.19 1.10 1.00 1.00 1.00 1.00 500

DM5145-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5145-00

-METRIC-

page 2 of 2

213

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 8.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 HPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

242 80 1524

100%

75%

50%

809 765

607 574

405 383

10.38 4.36 5.63 234 142 211 58 33 450 4.68 5.86

10.67 4.31 5.57 217 129 162 57 33 438 4.64 5.8

11.47 3.82 4.93 155 82 102 59 33 461 4.14 5.18

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 147 808

3.5 185 1017

5.6 321 1770

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.4 215 723

2.6 229 769

2.5 230 774

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

4.3 677 1289

4.1 636 1211

3.1 517 985

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.64 47 194

0.62 43 182

0.46 33 148

%

8.0 1.56

7.5 1.50

6.9 1.24

kW kW kW kW kW kW kW kW

2331 809 674 80 0 656 488 111

1797 607 578 67 0 474 350 71

1288 405 515 53 0 299 227 16

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC214

page 1 of 2

DM5148-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/--

70 0/--

75 1.0/19

80 to 100 1.0/21

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

0.84 0.86 0.87 0.88 0.90 0.91 0.93 0.95 0.96 2250

0.82 0.83 0.84 0.86 0.87 0.89 0.90 0.92 0.93 2500

0.79 0.80 0.82 0.83 0.84 0.86 0.87 0.89 0.90 2750

0.77 0.78 0.79 0.80 0.82 0.83 0.85 0.86 0.88 3000

1.46 1.51 1.57 1.63 1.63 1.63 1.38 1.43 1.49 1.54 1.55 1.55 1.30 1.35 1.41 1.46 1.47 1.47 1.21 1.27 1.32 1.38 1.38 1.38 1.13 1.19 1.24 1.29 1.30 1.30 1.05 1.10 1.16 1.21 1.22 1.22 1.00 1.02 1.07 1.13 1.13 1.13 1.00 1.00 1.00 1.04 1.05 1.05 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.63 1.55 1.47 1.38 1.30 1.22 1.13 1.05 1.00 2250

1.63 1.55 1.47 1.38 1.30 1.22 1.13 1.05 1.00 2500

1.63 1.55 1.47 1.38 1.30 1.22 1.13 1.05 1.00 2750

1.63 1.55 1.47 1.38 1.30 1.22 1.13 1.05 1.00 3000

G3516

1.00 0.98 0.95 0.93 0.90 0.87 1.00 1.00 0.97 0.94 0.91 0.88 1.00 1.00 0.98 0.95 0.93 0.90 1.00 1.00 1.00 0.97 0.94 0.91 1.00 1.00 1.00 0.99 0.96 0.93 1.00 1.00 1.00 1.00 0.97 0.94 1.00 1.00 1.00 1.00 0.99 0.96 1.00 1.00 1.00 1.00 1.00 0.98 1.00 1.00 1.00 1.00 1.00 0.99 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.29 1.21 1.14 1.06 1.00 1.00 1.00 1.00 1.00 0

1.35 1.27 1.19 1.11 1.03 1.00 1.00 1.00 1.00 250

1.40 1.32 1.24 1.16 1.08 1.00 1.00 1.00 1.00 500

DM5148-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5148-00

-METRIC-

page 2 of 2

215

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 HPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

207 80 1065

100%

75%

50%

809 765

607 574

405 383

9.85 4.27 5.51 233 153 207 62 22 416 4.58 5.72

10.1 3.97 5.13 198 124 149 60 22 433 4.28 5.35

11.01 4.09 5.29 150 85 104 59 22 434 4.42 5.52

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 157 864

7.5 427 2358

10.7 551 3042

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.3 220 739

2.4 224 752

2.4 206 693

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

6.1 1055 2010

4.7 775 1476

4.9 737 1404

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.92 77 302

0.70 51 222

0.75 45 211

%

8.7 1.64

7.3 1.49

6.1 1.41

kW kW kW kW kW kW kW kW

2212 809 601 80 0 605 425 117

1701 607 531 67 0 438 317 59

1236 405 456 53 0 304 220 19

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC216

page 1 of 2

DM5147-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/15

70 1.0/17

75 1.0/19

80 1.0/20

83 to 100 1.0/22

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

0.80 0.81 0.82 0.84 0.85 0.86 0.88 0.89 0.91 2250

0.77 0.78 0.80 0.81 0.82 0.84 0.85 0.87 0.88 2500

0.75 0.76 0.77 0.79 0.80 0.81 0.83 0.84 0.85 2750

0.73 0.74 0.75 0.76 0.77 0.79 0.80 0.81 0.83 3000

1.44 1.50 1.52 1.52 1.52 1.52 1.37 1.42 1.44 1.44 1.44 1.44 1.29 1.34 1.36 1.36 1.36 1.36 1.21 1.26 1.28 1.28 1.28 1.28 1.13 1.19 1.20 1.20 1.20 1.20 1.05 1.11 1.12 1.12 1.12 1.12 1.00 1.03 1.04 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.52 1.44 1.36 1.28 1.20 1.12 1.04 1.00 1.00 2250

1.52 1.44 1.36 1.28 1.20 1.12 1.04 1.00 1.00 2500

1.52 1.44 1.36 1.28 1.20 1.12 1.04 1.00 1.00 2750

1.52 1.44 1.36 1.28 1.20 1.12 1.04 1.00 1.00 3000

G3516

0.96 0.93 0.90 0.87 0.85 0.82 0.97 0.94 0.92 0.89 0.86 0.84 0.99 0.96 0.93 0.90 0.88 0.85 1.00 0.98 0.95 0.92 0.89 0.86 1.00 0.99 0.96 0.93 0.90 0.88 1.00 1.00 0.98 0.95 0.92 0.89 1.00 1.00 0.99 0.96 0.94 0.91 1.00 1.00 1.00 0.98 0.95 0.92 1.00 1.00 1.00 1.00 0.97 0.94 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.27 1.20 1.12 1.05 1.00 1.00 1.00 1.00 1.00 0

1.33 1.25 1.18 1.10 1.03 1.00 1.00 1.00 1.00 250

1.39 1.31 1.23 1.15 1.08 1.00 1.00 1.00 1.00 500

DM5147-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5147-00

-METRIC-

page 2 of 2

217

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 LPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

10 80 760

100%

75%

50%

809 765

607 574

405 383

9.9 4.19 5.41 226 134 198 62 22 416 4.49 5.61

10.15 3.9 5.04 193 108 145 60 22 433 4.2 5.25

11.07 4.02 5.19 147 74 104 59 22 434 4.33 5.42

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.6 157 864

7.5 427 2358

10.7 551 3042

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.3 220 739

2.4 224 752

2.4 206 693

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

6.1 1055 2010

4.7 775 1476

4.9 737 1404

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.92 77 302

0.70 51 222

0.75 45 211

%

8.7 1.64

7.3 1.49

6.1 1.41

kW kW kW kW kW kW kW kW

2224 809 642 80 0 595 417 98

1710 607 558 67 0 430 311 49

1243 405 473 53 0 298 216 14

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC218

page 1 of 2

DM5149-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/15

70 1.0/17

75 1.0/19

80 1.0/20

83 to 100 1.0/22

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 500

0.77 0.78 0.79 0.81 0.82 0.83 0.85 0.86 0.88 2250

0.74 0.76 0.77 0.78 0.79 0.81 0.82 0.84 0.85 2500

0.72 0.73 0.74 0.76 0.77 0.78 0.80 0.81 0.82 2750

0.70 0.71 0.72 0.73 0.75 0.76 0.77 0.78 0.80 3000

1.51 1.51 1.51 1.51 1.51 1.51 1.42 1.42 1.42 1.42 1.42 1.42 1.33 1.33 1.33 1.33 1.33 1.33 1.24 1.24 1.24 1.24 1.24 1.24 1.15 1.15 1.15 1.15 1.15 1.15 1.06 1.06 1.06 1.06 1.06 1.06 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.51 1.42 1.33 1.24 1.15 1.06 1.00 1.00 1.00 2250

1.51 1.42 1.33 1.24 1.15 1.06 1.00 1.00 1.00 2500

1.51 1.42 1.33 1.24 1.15 1.06 1.00 1.00 1.00 2750

1.51 1.42 1.33 1.24 1.15 1.06 1.00 1.00 1.00 3000

G3516

0.92 0.90 0.87 0.84 0.82 0.79 0.94 0.91 0.88 0.86 0.83 0.81 0.95 0.92 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.88 0.86 0.83 0.98 0.96 0.93 0.90 0.87 0.84 1.00 0.97 0.94 0.91 0.89 0.86 1.00 0.99 0.96 0.93 0.90 0.87 1.00 1.00 0.97 0.95 0.92 0.89 1.00 1.00 0.99 0.96 0.93 0.90 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.33 1.24 1.15 1.07 1.00 1.00 1.00 1.00 1.00 0

1.39 1.30 1.21 1.12 1.03 1.00 1.00 1.00 1.00 250

1.45 1.36 1.27 1.18 1.09 1.00 1.00 1.00 1.00 500

DM5149-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5149-00

-METRIC-

page 2 of 2

219

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 8.0:1 Aftercooler Inlet Temperature (°C) 32 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 HPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

242 80 1500

100%

75%

50%

856 810

642 608

428 405

10.57 4.23 5.47 234 139 215 47 35 453 4.55 5.69

10.79 4.22 5.45 204 118 167 44 35 453 4.54 5.68

11.26 4.11 5.31 151 77 116 41 35 452 4.43 5.54

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 152 836

3.1 170 939

5.8 311 1718

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.9 182 612

1.9 177 596

2.4 215 724

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

3.6 606 1154

3.5 566 1079

3.2 501 954

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.55 42 174

0.53 38 162

0.49 32 144

%

8.1 1.52

7.6 1.48

6.7 1.38

kW kW kW kW kW kW kW kW

2512 856 773 80 0 676 508 127

1924 642 630 67 0 586 380 79

1338 428 499 53 0 329 248 29

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC220

page 1 of 2

DM5151-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dB(A) dB(A)

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0

30 35 40 45 0.90/21 0.90/23 0.90/24 1.0/25

50 1.0/26

55 1.0/28

60 1.0/29

65 1.0/30

70 1.0/32

75 1.0/33

80 1.0/34

83 to 100 1.0/35

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

0.84 0.85 0.87 0.88 0.90 0.91 0.93 0.94 0.96 2250

0.81 0.83 0.84 0.85 0.87 0.88 0.90 0.91 0.93 2500

0.79 0.80 0.81 0.83 0.84 0.86 0.87 0.89 0.90 2750

0.76 0.78 0.79 0.80 0.82 0.83 0.84 0.86 0.87 3000

1.40 1.45 1.50 1.55 1.55 1.55 1.33 1.38 1.43 1.48 1.48 1.48 1.26 1.31 1.36 1.41 1.41 1.41 1.19 1.24 1.28 1.33 1.33 1.33 1.12 1.16 1.21 1.26 1.26 1.26 1.05 1.09 1.14 1.18 1.18 1.18 1.00 1.02 1.06 1.11 1.11 1.11 1.00 1.00 1.00 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.55 1.48 1.41 1.33 1.26 1.18 1.11 1.04 1.00 2250

1.55 1.48 1.41 1.33 1.26 1.18 1.11 1.04 1.00 2500

1.55 1.48 1.41 1.33 1.26 1.18 1.11 1.04 1.00 2750

1.55 1.48 1.41 1.33 1.26 1.18 1.11 1.04 1.00 3000

G3516

1.00 0.98 0.95 0.92 0.89 0.87 1.00 1.00 0.97 0.94 0.91 0.88 1.00 1.00 0.98 0.95 0.92 0.90 1.00 1.00 1.00 0.97 0.94 0.91 1.00 1.00 1.00 0.98 0.95 0.92 1.00 1.00 1.00 1.00 0.97 0.94 1.00 1.00 1.00 1.00 0.99 0.96 1.00 1.00 1.00 1.00 1.00 0.97 1.00 1.00 1.00 1.00 1.00 0.99 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.26 1.19 1.12 1.05 1.00 1.00 1.00 1.00 1.00 0

1.31 1.24 1.17 1.10 1.03 1.00 1.00 1.00 1.00 250

1.35 1.28 1.21 1.14 1.07 1.00 1.00 1.00 1.00 500

DM5151-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5151-00

-METRIC-

page 2 of 2

221

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°C) 32 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 HPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

207 80 1065

100%

75%

50%

856 810

642 608

428 405

9.97 4.21 5.44 235 154 217 47 24 410 4.52 5.65

10.07 3.96 5.11 193 129 158 44 24 422 4.26 5.33

10.77 4.07 5.25 153 89 110 43 24 425 4.38 5.48

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 166 913

6.1 362 1995

8.2 456 2520

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.1 209 703

2.3 218 735

2.4 217 731

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

7.1 1240 2363

5.5 938 1787

5.9 954 1818

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.07 90 355

0.83 62 269

0.89 61 273

%

8.7 1.59

7.5 1.47

7.0 1.41

kW kW kW kW kW kW kW kW

2370 856 653 80 0 633 436 147

1795 642 547 67 0 455 323 85

1280 428 447 53 0 317 224 35

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC222

page 1 of 2

DM5150-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 1.0/15

65 1.0/17

70 1.0/19

75 1.0/21

80 1.0/22

83 to 100 1.0/24

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

0.80 0.81 0.82 0.84 0.85 0.86 0.88 0.89 0.91 2250

0.77 0.78 0.80 0.81 0.82 0.84 0.85 0.87 0.88 2500

0.75 0.76 0.77 0.79 0.80 0.81 0.83 0.84 0.85 2750

0.73 0.74 0.75 0.76 0.77 0.79 0.80 0.81 0.83 3000

1.37 1.42 1.43 1.43 1.43 1.43 1.30 1.35 1.36 1.36 1.36 1.36 1.24 1.28 1.30 1.30 1.30 1.30 1.17 1.22 1.23 1.23 1.23 1.23 1.11 1.15 1.17 1.17 1.17 1.17 1.04 1.09 1.10 1.10 1.10 1.10 1.00 1.02 1.03 1.03 1.03 1.03 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.43 1.36 1.30 1.23 1.17 1.10 1.03 1.00 1.00 2250

1.43 1.36 1.30 1.23 1.17 1.10 1.03 1.00 1.00 2500

1.43 1.36 1.30 1.23 1.17 1.10 1.03 1.00 1.00 2750

1.43 1.36 1.30 1.23 1.17 1.10 1.03 1.00 1.00 3000

G3516

0.96 0.93 0.90 0.87 0.85 0.82 0.97 0.94 0.92 0.89 0.86 0.84 0.99 0.96 0.93 0.90 0.88 0.85 1.00 0.98 0.95 0.92 0.89 0.86 1.00 0.99 0.96 0.93 0.90 0.88 1.00 1.00 0.98 0.95 0.92 0.89 1.00 1.00 0.99 0.96 0.94 0.91 1.00 1.00 1.00 0.98 0.95 0.92 1.00 1.00 1.00 1.00 0.97 0.94 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.23 1.17 1.10 1.04 1.00 1.00 1.00 1.00 1.00 0

1.27 1.21 1.15 1.08 1.02 1.00 1.00 1.00 1.00 250

1.32 1.26 1.19 1.13 1.06 1.00 1.00 1.00 1.00 500

DM5150-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5150-00

-METRIC-

page 2 of 2

223

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°C) 32 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 LPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

10 80 760

100%

75%

50%

856 810

642 608

428 405

10.03 4.13 5.34 228 135 207 47 24 410 4.44 5.55

10.13 3.88 5.02 188 113 153 44 24 422 4.18 5.23

10.83 3.99 5.15 150 77 109 43 24 425 4.3 5.38

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 166 913

6.1 362 1995

8.2 456 2520

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.1 209 703

2.3 218 735

2.4 217 731

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

7.1 1240 2363

5.5 938 1787

5.9 954 1818

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.07 90 355

0.83 62 269

0.89 61 273

%

8.7 1.59

7.5 1.47

7.0 1.41

kW kW kW kW kW kW kW kW

2383 856 702 80 0 623 427 122

1805 642 579 67 0 447 317 70

1287 428 466 53 0 311 220 28

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC224

page 1 of 2

DM5152-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 1.0/15

65 1.0/17

70 1.0/19

75 1.0/21

80 1.0/22

83 to 100 1.0/24

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 500

0.77 0.78 0.79 0.81 0.82 0.83 0.85 0.86 0.88 2250

0.74 0.76 0.77 0.78 0.79 0.81 0.82 0.84 0.85 2500

0.72 0.73 0.74 0.76 0.77 0.78 0.80 0.81 0.82 2750

0.70 0.71 0.72 0.73 0.75 0.76 0.77 0.78 0.80 3000

1.41 1.41 1.41 1.41 1.41 1.41 1.34 1.34 1.34 1.34 1.34 1.34 1.27 1.27 1.27 1.27 1.27 1.27 1.19 1.19 1.19 1.19 1.19 1.19 1.12 1.12 1.12 1.12 1.12 1.12 1.05 1.05 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.41 1.34 1.27 1.19 1.12 1.05 1.00 1.00 1.00 2250

1.41 1.34 1.27 1.19 1.12 1.05 1.00 1.00 1.00 2500

1.41 1.34 1.27 1.19 1.12 1.05 1.00 1.00 1.00 2750

1.41 1.34 1.27 1.19 1.12 1.05 1.00 1.00 1.00 3000

G3516

0.92 0.90 0.87 0.84 0.82 0.79 0.94 0.91 0.88 0.86 0.83 0.81 0.95 0.92 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.88 0.86 0.83 0.98 0.96 0.93 0.90 0.87 0.84 1.00 0.97 0.94 0.91 0.89 0.86 1.00 0.99 0.96 0.93 0.90 0.87 1.00 1.00 0.97 0.95 0.92 0.89 1.00 1.00 0.99 0.96 0.93 0.90 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.27 1.20 1.12 1.05 1.00 1.00 1.00 1.00 1.00 0

1.31 1.24 1.17 1.10 1.03 1.00 1.00 1.00 1.00 250

1.36 1.29 1.22 1.15 1.07 1.00 1.00 1.00 1.00 500

DM5152-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5152-00

-METRIC-

page 2 of 2

225

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1800 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 LPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

10 80 1067

100%

75%

50%

kW kW

1090 1035

818 776

545 518

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

11.01 4.35 5.62 237 152 215 59 18 474 4.68 5.85

11.34 4.31 5.57 205 131 167 57 18 472 4.65 5.81

12 4.05 5.24 153 92 120 54 18 492 4.39 5.49

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 142 782

3.2 170 935

7.0 374 2065

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.6 224 754

2.5 215 721

2.4 208 700

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

3.0 482 918

3.1 466 888

2.9 437 832

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.45 32 138

0.46 30 134

0.44 27 125

%

7.4 1.60

7.1 1.55

6.0 1.40

kW kW kW kW kW kW kW kW

3333 1090 1027 120 0 923 710 173

2575 818 867 100 0 685 526 105

1815 545 701 80 0 455 354 35

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC226

page 1 of 2

DM5167-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/--

70 1.0/15

75 1.0/16

80 1.0/17

83 to 100 1.0/18

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

0.80 0.81 0.82 0.84 0.85 0.86 0.88 0.89 0.91 2250

0.77 0.78 0.80 0.81 0.82 0.84 0.85 0.87 0.88 2500

0.75 0.76 0.77 0.79 0.80 0.81 0.83 0.84 0.85 2750

0.73 0.74 0.75 0.76 0.77 0.79 0.80 0.81 0.83 3000

1.42 1.48 1.49 1.49 1.49 1.49 1.35 1.40 1.42 1.42 1.42 1.42 1.27 1.33 1.34 1.34 1.34 1.34 1.20 1.25 1.26 1.26 1.26 1.26 1.12 1.18 1.19 1.19 1.19 1.19 1.05 1.10 1.11 1.11 1.11 1.11 1.00 1.03 1.04 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.49 1.42 1.34 1.26 1.19 1.11 1.04 1.00 1.00 2250

1.49 1.42 1.34 1.26 1.19 1.11 1.04 1.00 1.00 2500

1.49 1.42 1.34 1.26 1.19 1.11 1.04 1.00 1.00 2750

1.49 1.42 1.34 1.26 1.19 1.11 1.04 1.00 1.00 3000

G3516

0.96 0.93 0.90 0.88 0.85 0.82 0.97 0.94 0.92 0.89 0.86 0.84 0.99 0.96 0.93 0.90 0.88 0.85 1.00 0.98 0.95 0.92 0.89 0.86 1.00 0.99 0.96 0.93 0.90 0.88 1.00 1.00 0.98 0.95 0.92 0.89 1.00 1.00 0.99 0.96 0.94 0.91 1.00 1.00 1.00 0.98 0.95 0.92 1.00 1.00 1.00 1.00 0.97 0.94 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.26 1.19 1.12 1.05 1.00 1.00 1.00 1.00 1.00 0

1.31 1.24 1.17 1.10 1.02 1.00 1.00 1.00 1.00 250

1.37 1.29 1.22 1.15 1.07 1.00 1.00 1.00 1.00 500

DM5167-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5167-00

-METRIC-

page 2 of 2

227

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 110 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

LANDFILL 22 LPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

10 130 762

100%

75%

50%

856 815

642 611

428 408

11.17 3.82 4.93 227 143 212 65 20 453 4.45 5.57

11.52 3.48 4.49 206 123 154 64 20 463 4.12 5.15

12.61 3.41 4.4 155 84 106 65 20 475 4.08 5.1

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 143 787

8.1 426 2349

11.8 561 3098

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

4.0 352 1184

4.3 374 1258

4.0 310 1045

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

3.6 551 1050

2.7 407 775

2.8 385 732

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.54 34 158

0.40 23 117

0.42 19 110

%

6.3 1.31

4.9 1.16

2.9 1.06

kW kW kW kW kW kW kW kW

2655 856 740 92 155 698 525 115

2054 642 641 77 134 499 381 63

1498 428 537 61 112 342 263 18

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC228

page 1 of 2

DM5153-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/--

70 0/--

75 0/--

80 to 129 0/--

130 + 1.0/2.0

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 500

0.77 0.78 0.79 0.81 0.82 0.83 0.85 0.86 0.88 2250

0.74 0.76 0.77 0.78 0.79 0.81 0.82 0.84 0.85 2500

0.72 0.73 0.74 0.76 0.77 0.78 0.80 0.81 0.82 2750

0.70 0.71 0.72 0.73 0.75 0.76 0.77 0.78 0.80 3000

1.46 1.46 1.46 1.46 1.46 1.46 1.38 1.38 1.38 1.38 1.38 1.38 1.30 1.30 1.30 1.30 1.30 1.30 1.22 1.22 1.22 1.22 1.22 1.22 1.14 1.14 1.14 1.14 1.14 1.14 1.05 1.06 1.06 1.06 1.06 1.06 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.46 1.38 1.30 1.22 1.14 1.06 1.00 1.00 1.00 2250

1.46 1.38 1.30 1.22 1.14 1.06 1.00 1.00 1.00 2500

1.46 1.38 1.30 1.22 1.14 1.06 1.00 1.00 1.00 2750

1.46 1.38 1.30 1.22 1.14 1.06 1.00 1.00 1.00 3000

G3516

0.92 0.90 0.87 0.84 0.82 0.79 0.94 0.91 0.88 0.86 0.83 0.81 0.95 0.93 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.88 0.86 0.83 0.98 0.96 0.93 0.90 0.87 0.85 1.00 0.97 0.94 0.91 0.89 0.86 1.00 0.99 0.96 0.93 0.90 0.87 1.00 1.00 0.98 0.95 0.92 0.89 1.00 1.00 0.99 0.96 0.93 0.90 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.29 1.21 1.13 1.05 1.00 1.00 1.00 1.00 1.00 0

1.34 1.26 1.18 1.11 1.03 1.00 1.00 1.00 1.00 250

1.40 1.32 1.24 1.16 1.08 1.00 1.00 1.00 1.00 500

DM5153-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5153-00

-METRIC-

page 2 of 2

229

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

NAT GAS 36.2 DELTEC 10 80 350

100%

75%

50%

kW kW

1010 975

758 731

505 488

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

10.13 4.69 6.06 267 153 250 59 24 512 5.02 6.27

10.43 4.76 6.16 225 127 192 57 24 515 5.1 6.37

11.05 4.94 6.39 166 88 133 55 24 522 5.29 6.62

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.5 46 250

0.8 46 250

0.8 46 250

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

3.8 370 1247

3.7 351 1182

3.7 331 1115

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

5.7 1237 2356

5.5 1296 2469

9.0 1341 2555

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.86 103 354

0.83 106 371

1.35 107 384

%

10.2 1.74

10.0 1.73

9.8 1.70

kW kW kW kW kW kW kW kW

2841 1010 552 100 0 1012 777 167

2193 758 485 83 0 773 596 94

1549 505 387 67 0 560 420 30

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC230

page 1 of 2

DM0988-00

®

Gas Generator Set Engine Performance

G3516 LE

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/18

70 1.0/20

75 1.0/22

80 to 100 1.0/24

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.96 0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 0

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 250

0.91 0.92 0.94 0.95 0.97 0.98 1.00 1.00 1.00 500

0.73 0.74 0.75 0.77 0.78 0.79 0.81 0.82 0.83 2250

0.71 0.72 0.73 0.74 0.76 0.77 0.78 0.79 0.81 2500

0.69 0.70 0.71 0.72 0.73 0.74 0.76 0.77 0.78 2750

0.67 0.68 0.69 0.70 0.71 0.72 0.73 0.75 0.76 3000

1.35 1.35 1.35 1.35 1.35 1.35 1.27 1.27 1.27 1.27 1.27 1.27 1.20 1.20 1.20 1.20 1.20 1.20 1.12 1.12 1.12 1.12 1.12 1.12 1.05 1.05 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.35 1.27 1.20 1.12 1.05 1.00 1.00 1.00 1.00 2250

1.35 1.27 1.20 1.12 1.05 1.00 1.00 1.00 1.00 2500

1.35 1.27 1.20 1.12 1.05 1.00 1.00 1.00 1.00 2750

1.35 1.27 1.20 1.12 1.05 1.00 1.00 1.00 1.00 3000

G3516

0.88 0.85 0.83 0.80 0.78 0.75 0.89 0.87 0.84 0.82 0.79 0.77 0.91 0.88 0.85 0.83 0.80 0.78 0.92 0.89 0.87 0.84 0.82 0.79 0.94 0.91 0.88 0.86 0.83 0.80 0.95 0.92 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.88 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 1.00 0.97 0.94 0.92 0.89 0.86 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.28 1.21 1.13 1.06 1.00 1.00 1.00 1.00 1.00 0

1.33 1.26 1.18 1.11 1.03 1.00 1.00 1.00 1.00 250

1.35 1.27 1.20 1.12 1.05 1.00 1.00 1.00 1.00 500

DM0988-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM0988-00

-METRIC-

page 2 of 2

231

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 127 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

NAT GAS 36.2 DELTEC 10 80 350

100%

75%

50%

1010 975

758 731

505 488

10.25 4.7 6.07 269 158 255 58 20 548 5.03 6.3

10.5 4.71 6.09 231 135 193 57 20 550 5.05 6.31

11.24 4.91 6.35 168 95 133 55 20 555 5.27 6.59

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.8 46 250

0.8 46 250

0.8 46 250

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

3.6 347 1167

3.6 337 1132

3.6 322 1084

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

6.0 931 1773

6.4 968 1845

7.5 1046 1993

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.91 75 266

0.97 77 277

1.12 82 299

%

9.9 1.70

9.7 1.68

9.5 1.65

kW kW kW kW kW kW kW kW

2875 1010 360 130 104 1093 853 178

2208 758 318 108 92 828 645 105

1575 505 279 87 80 587 456 37

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC232

page 1 of 2

DM0873-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0.95/16*

70 1.0/16*

75 1.0/18

80 to 100 1.0/20

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.96 0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 0

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 250

0.91 0.92 0.94 0.95 0.97 0.98 1.00 1.00 1.00 500

0.73 0.74 0.75 0.77 0.78 0.79 0.81 0.82 0.83 2250

0.71 0.72 0.73 0.74 0.76 0.77 0.78 0.79 0.81 2500

0.69 0.70 0.71 0.72 0.73 0.74 0.76 0.77 0.78 2750

0.67 0.68 0.69 0.70 0.71 0.72 0.73 0.75 0.76 3000

1.33 1.33 1.33 1.33 1.33 1.33 1.26 1.26 1.26 1.26 1.26 1.26 1.19 1.19 1.19 1.19 1.19 1.19 1.12 1.12 1.12 1.12 1.12 1.12 1.05 1.05 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.33 1.26 1.19 1.12 1.05 1.00 1.00 1.00 1.00 2250

1.33 1.26 1.19 1.12 1.05 1.00 1.00 1.00 1.00 2500

1.33 1.26 1.19 1.12 1.05 1.00 1.00 1.00 1.00 2750

1.33 1.26 1.19 1.12 1.05 1.00 1.00 1.00 1.00 3000

G3516

0.88 0.85 0.83 0.80 0.78 0.75 0.89 0.87 0.84 0.82 0.79 0.77 0.91 0.88 0.85 0.83 0.80 0.78 0.92 0.89 0.87 0.84 0.82 0.79 0.94 0.91 0.88 0.86 0.83 0.80 0.95 0.92 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.88 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 1.00 0.97 0.94 0.92 0.89 0.86 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.27 1.20 1.13 1.05 1.00 1.00 1.00 1.00 1.00 0

1.31 1.24 1.17 1.10 1.03 1.00 1.00 1.00 1.00 250

1.33 1.26 1.19 1.12 1.05 1.00 1.00 1.00 1.00 500

DM0873-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM0873-00

-METRIC-

page 2 of 2

233

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

NAT GAS 36.2 DELTEC 10 80 500

100%

75%

50%

kW kW

1010 975

758 731

505 488

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

9.79 4.4 5.69 263 151 237 61 24 529 4.72 5.9

10.09 4.41 5.7 209 119 175 57 24 531 4.73 5.92

10.62 4.51 5.83 157 82 125 55 24 537 4.84 6.06

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.5 91 500

1.5 91 500

1.6 91 500

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

3.3 325 1093

3.3 325 1095

3.5 317 1065

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

5.9 955 1819

6.6 1029 1961

7.6 1107 2109

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.89 74 273

0.99 78 295

1.14 83 317

%

9.5 1.65

9.2 1.62

9.0 1.58

kW kW kW kW kW kW kW kW

2744 1010 515 76 0 992 765 150

2123 758 464 68 0 756 580 77

1489 505 380 55 0 526 401 23

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC234

page 1 of 2

DM0991-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/18

70 1.0/20

75 1.0/22

80 to 100 1.0/24

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 250

0.92 0.94 0.95 0.97 0.98 1.00 1.00 1.00 1.00 500

0.74 0.76 0.77 0.78 0.79 0.81 0.82 0.84 0.85 2250

0.72 0.73 0.74 0.76 0.77 0.78 0.80 0.81 0.82 2500

0.70 0.71 0.72 0.73 0.75 0.76 0.77 0.78 0.80 2750

0.68 0.69 0.70 0.71 0.72 0.73 0.75 0.76 0.77 3000

1.39 1.39 1.39 1.39 1.39 1.39 1.31 1.31 1.31 1.31 1.31 1.31 1.24 1.24 1.24 1.24 1.24 1.24 1.16 1.16 1.16 1.16 1.16 1.16 1.08 1.08 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.39 1.31 1.24 1.16 1.08 1.00 1.00 1.00 1.00 2250

1.39 1.31 1.24 1.16 1.08 1.00 1.00 1.00 1.00 2500

1.39 1.31 1.24 1.16 1.08 1.00 1.00 1.00 1.00 2750

1.39 1.31 1.24 1.16 1.08 1.00 1.00 1.00 1.00 3000

G3516

0.90 0.87 0.84 0.82 0.79 0.77 0.91 0.88 0.86 0.83 0.80 0.78 0.92 0.90 0.87 0.84 0.82 0.79 0.94 0.91 0.88 0.86 0.83 0.81 0.95 0.93 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.89 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 1.00 0.97 0.94 0.92 0.89 0.86 1.00 0.99 0.96 0.93 0.90 0.88 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.29 1.21 1.14 1.06 1.00 1.00 1.00 1.00 1.00 0

1.34 1.26 1.19 1.11 1.03 1.00 1.00 1.00 1.00 250

1.39 1.31 1.24 1.16 1.08 1.00 1.00 1.00 1.00 500

DM0991-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM0991-00

-METRIC-

page 2 of 2

235

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 127 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

NAT GAS 36.2 DELTEC 10 80 500

100%

75%

50%

kW kW

1010 975

758 731

505 488

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

9.86 4.45 5.75 258 149 240 57 19 556 4.77 5.96

10.2 4.49 5.8 222 127 183 56 19 554 4.81 6.02

10.78 4.61 5.96 162 86 126 55 19 565 4.95 6.19

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.5 91 500

1.5 91 500

1.6 91 500

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

3.7 367 1235

3.7 359 1208

3.9 359 1208

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

4.6 733 1397

5.2 811 1544

6.2 881 1678

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.69 58 210

0.79 63 232

0.93 67 252

%

9.6 1.68

9.4 1.66

9.1 1.62

kW kW kW kW kW kW kW kW

2763 1010 333 102 124 1040 825 154

2145 758 310 88 110 790 622 90

1511 505 259 71 91 558 439 27

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC236

page 1 of 2

DM0876-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 70 0.95/16* 1.0/16*

75 1.0/18

80 to 100 1.0/19

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 250

0.92 0.94 0.95 0.97 0.98 1.00 1.00 1.00 1.00 500

0.74 0.76 0.77 0.78 0.79 0.81 0.82 0.84 0.85 2250

0.72 0.73 0.74 0.76 0.77 0.78 0.80 0.81 0.82 2500

0.70 0.71 0.72 0.73 0.75 0.76 0.77 0.78 0.80 2750

0.68 0.69 0.70 0.71 0.72 0.73 0.75 0.76 0.77 3000

1.39 1.39 1.39 1.39 1.39 1.39 1.31 1.31 1.31 1.31 1.31 1.31 1.23 1.23 1.23 1.23 1.23 1.23 1.16 1.16 1.16 1.16 1.16 1.16 1.08 1.08 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.39 1.31 1.23 1.16 1.08 1.00 1.00 1.00 1.00 2250

1.39 1.31 1.23 1.16 1.08 1.00 1.00 1.00 1.00 2500

1.39 1.31 1.23 1.16 1.08 1.00 1.00 1.00 1.00 2750

1.39 1.31 1.23 1.16 1.08 1.00 1.00 1.00 1.00 3000

G3516

0.90 0.87 0.84 0.82 0.79 0.77 0.91 0.88 0.86 0.83 0.80 0.78 0.92 0.90 0.87 0.84 0.82 0.79 0.94 0.91 0.88 0.86 0.83 0.81 0.95 0.93 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.89 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 1.00 0.97 0.94 0.92 0.89 0.86 1.00 0.99 0.96 0.93 0.90 0.88 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.29 1.21 1.14 1.06 1.00 1.00 1.00 1.00 1.00 0

1.34 1.26 1.18 1.11 1.03 1.00 1.00 1.00 1.00 250

1.39 1.31 1.23 1.16 1.08 1.00 1.00 1.00 1.00 500

DM0876-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM0876-00

-METRIC-

page 2 of 2

237

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

NAT GAS 36.2 DELTEC 10 80 350

100%

75%

50%

kW kW

1010 975

758 731

505 488

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

9.84 4.63 5.98 253 152 238 59 22 494 4.95 6.19

10.2 4.72 6.09 218 126 186 57 22 501 5.04 6.31

10.88 4.91 6.34 163 87 131 55 22 512 5.26 6.57

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.7 46 250

0.8 46 250

0.8 46 250

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

3.5 355 1195

3.6 340 1145

3.6 325 1092

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

8.9 1575 3002

10.2 1729 3294

11.5 1848 3522

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.33 131 451

1.54 141 495

1.73 148 529

%

10.2 1.77

10.0 1.75

9.8 1.72

kW kW kW kW kW kW kW kW

2758 1010 514 83 0 990 752 161

2145 758 448 71 0 778 586 91

1526 505 368 67 0 557 420 29

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC238

page 1 of 2

DM1228-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 70 0.90/18* 0.95/18*

75 1.0/20

80 to 100 1.0/22

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.96 0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 0

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 250

0.91 0.92 0.94 0.95 0.97 0.98 1.00 1.00 1.00 500

0.73 0.74 0.75 0.77 0.78 0.79 0.81 0.82 0.83 2250

0.71 0.72 0.73 0.74 0.76 0.77 0.78 0.79 0.81 2500

0.69 0.70 0.71 0.72 0.73 0.74 0.76 0.77 0.78 2750

0.67 0.68 0.69 0.70 0.71 0.72 0.73 0.75 0.76 3000

1.35 1.35 1.35 1.35 1.35 1.35 1.28 1.28 1.28 1.28 1.28 1.28 1.20 1.20 1.20 1.20 1.20 1.20 1.12 1.12 1.12 1.12 1.12 1.12 1.05 1.05 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.35 1.28 1.20 1.12 1.05 1.00 1.00 1.00 1.00 2250

1.35 1.28 1.20 1.12 1.05 1.00 1.00 1.00 1.00 2500

1.35 1.28 1.20 1.12 1.05 1.00 1.00 1.00 1.00 2750

1.35 1.28 1.20 1.12 1.05 1.00 1.00 1.00 1.00 3000

G3516

0.88 0.85 0.83 0.80 0.78 0.75 0.89 0.87 0.84 0.82 0.79 0.77 0.91 0.88 0.85 0.83 0.80 0.78 0.92 0.89 0.87 0.84 0.82 0.79 0.94 0.91 0.88 0.86 0.83 0.80 0.95 0.92 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.88 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 1.00 0.97 0.94 0.92 0.89 0.86 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.28 1.21 1.13 1.06 1.00 1.00 1.00 1.00 1.00 0

1.33 1.26 1.18 1.10 1.03 1.00 1.00 1.00 1.00 250

1.35 1.28 1.20 1.12 1.05 1.00 1.00 1.00 1.00 500

DM1228-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1228-00

-METRIC-

page 2 of 2

239

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 127 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

NAT GAS 36.2 DELTEC 10 80 350

100%

75%

50%

kW kW

1010 975

758 731

505 488

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

9.95 4.58 5.92 255 157 242 58 18 528 4.9 6.13

10.27 4.66 6.02 223 134 187 57 18 535 4.99 6.24

11.07 4.85 6.27 165 95 132 55 18 545 5.2 6.5

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.7 46 250

0.8 46 250

0.8 46 250

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

3.4 333 1119

3.4 326 1097

3.5 315 1061

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

6.7 1199 2284

7.5 1288 2454

8.6 1386 2641

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.02 97 343

1.13 102 369

1.29 108 397

%

9.9 1.73

9.7 1.71

9.5 1.66

kW kW kW kW kW kW kW kW

2791 1010 329 101 154 1029 816 169

2177 758 287 90 142 798 631 101

1552 505 239 77 132 564 445 36

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC240

page 1 of 2

DM1240-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/--

70 0/--

75 0.90/16

80 to 100 1.0/18

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.96 0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 0

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 250

0.91 0.92 0.94 0.95 0.97 0.98 1.00 1.00 1.00 500

0.73 0.74 0.75 0.77 0.78 0.79 0.81 0.82 0.83 2250

0.71 0.72 0.73 0.74 0.76 0.77 0.78 0.79 0.81 2500

0.69 0.70 0.71 0.72 0.73 0.74 0.76 0.77 0.78 2750

0.67 0.68 0.69 0.70 0.71 0.72 0.73 0.75 0.76 3000

1.34 1.34 1.34 1.34 1.34 1.34 1.26 1.26 1.26 1.26 1.26 1.26 1.19 1.19 1.19 1.19 1.19 1.19 1.12 1.12 1.12 1.12 1.12 1.12 1.05 1.05 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.34 1.26 1.19 1.12 1.05 1.00 1.00 1.00 1.00 2250

1.34 1.26 1.19 1.12 1.05 1.00 1.00 1.00 1.00 2500

1.34 1.26 1.19 1.12 1.05 1.00 1.00 1.00 1.00 2750

1.34 1.26 1.19 1.12 1.05 1.00 1.00 1.00 1.00 3000

G3516

0.88 0.85 0.83 0.80 0.78 0.75 0.89 0.87 0.84 0.82 0.79 0.77 0.91 0.88 0.85 0.83 0.80 0.78 0.92 0.89 0.87 0.84 0.82 0.79 0.94 0.91 0.88 0.86 0.83 0.80 0.95 0.92 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.88 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 1.00 0.97 0.94 0.92 0.89 0.86 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.27 1.19 1.12 1.05 1.00 1.00 1.00 1.00 1.00 0

1.32 1.24 1.17 1.10 1.03 1.00 1.00 1.00 1.00 250

1.34 1.26 1.19 1.12 1.05 1.00 1.00 1.00 1.00 500

DM1240-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1240-00

-METRIC-

page 2 of 2

241

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

NAT GAS 36.2 DELTEC 10 80 500

100%

75%

50%

kW kW

1010 975

758 731

505 488

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

9.5 4.29 5.54 249 150 225 61 22 510 4.6 5.75

9.87 4.33 5.59 202 118 170 57 22 517 4.64 5.8

10.46 4.45 5.75 154 82 123 55 22 527 4.78 5.98

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.5 91 500

1.5 91 500

1.6 91 500

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

3.1 312 1048

3.2 315 1060

3.3 310 1043

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

7.1 1259 2398

7.7 1350 2572

8.9 1464 2789

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.07 98 360

1.16 103 386

1.34 109 419

%

9.5 1.68

9.2 1.64

9.0 1.60

kW kW kW kW kW kW kW kW

2664 1010 498 74 0 940 730 143

2071 758 442 66 0 731 568 75

1474 505 379 54 0 514 398 23

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC242

page 1 of 2

DM1231-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 70 0.90/18* 0.95/18*

75 1.0/20

80 to 100 1.0/22

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 250

0.92 0.94 0.95 0.97 0.98 1.00 1.00 1.00 1.00 500

0.74 0.76 0.77 0.78 0.79 0.81 0.82 0.84 0.85 2250

0.72 0.73 0.74 0.76 0.77 0.78 0.80 0.81 0.82 2500

0.70 0.71 0.72 0.73 0.75 0.76 0.77 0.78 0.80 2750

0.68 0.69 0.70 0.71 0.72 0.73 0.75 0.76 0.77 3000

1.40 1.40 1.40 1.40 1.40 1.40 1.32 1.32 1.32 1.32 1.32 1.32 1.24 1.24 1.24 1.24 1.24 1.24 1.16 1.16 1.16 1.16 1.16 1.16 1.08 1.08 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.40 1.32 1.24 1.16 1.08 1.00 1.00 1.00 1.00 2250

1.40 1.32 1.24 1.16 1.08 1.00 1.00 1.00 1.00 2500

1.40 1.32 1.24 1.16 1.08 1.00 1.00 1.00 1.00 2750

1.40 1.32 1.24 1.16 1.08 1.00 1.00 1.00 1.00 3000

G3516

0.90 0.87 0.84 0.82 0.79 0.77 0.91 0.88 0.86 0.83 0.80 0.78 0.92 0.90 0.87 0.84 0.82 0.79 0.94 0.91 0.88 0.86 0.83 0.81 0.95 0.93 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.89 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 1.00 0.97 0.94 0.92 0.89 0.86 1.00 0.99 0.96 0.93 0.90 0.88 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.29 1.21 1.13 1.06 1.00 1.00 1.00 1.00 1.00 0

1.34 1.26 1.19 1.11 1.03 1.00 1.00 1.00 1.00 250

1.40 1.32 1.24 1.16 1.08 1.00 1.00 1.00 1.00 500

DM1231-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1231-00

-METRIC-

page 2 of 2

243

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 127 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

NAT GAS 36.2 DELTEC 10 80 500

100%

75%

50%

kW kW

1010 975

758 731

505 488

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

9.57 4.35 5.61 245 148 228 57 17 536 4.65 5.82

9.98 4.42 5.71 215 126 178 56 17 539 4.74 5.92

10.62 4.58 5.91 160 86 125 55 17 555 4.91 6.14

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.5 91 500

1.5 91 500

1.6 91 501

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

3.5 352 1185

3.5 348 1170

3.8 351 1183

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

5.4 1000 1905

6.3 1105 2105

6.9 1155 2201

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.82 79 286

0.95 86 316

1.04 87 331

%

9.6 1.71

9.4 1.68

9.1 1.63

kW kW kW kW kW kW kW kW

2688 1010 328 99 144 962 770 146

2104 758 283 86 139 754 601 86

1496 505 235 71 129 530 424 26

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC244

page 1 of 2

DM1243-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/--

70 0/--

75 0.90/16*

80 to 100 1.0/17

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 250

0.92 0.94 0.95 0.97 0.98 1.00 1.00 1.00 1.00 500

0.74 0.76 0.77 0.78 0.79 0.81 0.82 0.84 0.85 2250

0.72 0.73 0.74 0.76 0.77 0.78 0.80 0.81 0.82 2500

0.70 0.71 0.72 0.73 0.75 0.76 0.77 0.78 0.80 2750

0.68 0.69 0.70 0.71 0.72 0.73 0.75 0.76 0.77 3000

1.39 1.39 1.39 1.39 1.39 1.39 1.31 1.31 1.31 1.31 1.31 1.31 1.24 1.24 1.24 1.24 1.24 1.24 1.16 1.16 1.16 1.16 1.16 1.16 1.08 1.08 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.39 1.31 1.24 1.16 1.08 1.00 1.00 1.00 1.00 2250

1.39 1.31 1.24 1.16 1.08 1.00 1.00 1.00 1.00 2500

1.39 1.31 1.24 1.16 1.08 1.00 1.00 1.00 1.00 2750

1.39 1.31 1.24 1.16 1.08 1.00 1.00 1.00 1.00 3000

G3516

0.90 0.87 0.84 0.82 0.79 0.77 0.91 0.88 0.86 0.83 0.80 0.78 0.92 0.90 0.87 0.84 0.82 0.79 0.94 0.91 0.88 0.86 0.83 0.81 0.95 0.93 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.89 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 1.00 0.97 0.94 0.92 0.89 0.86 1.00 0.99 0.96 0.93 0.90 0.88 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.29 1.21 1.13 1.06 1.00 1.00 1.00 1.00 1.00 0

1.34 1.26 1.18 1.11 1.03 1.00 1.00 1.00 1.00 250

1.39 1.31 1.24 1.16 1.08 1.00 1.00 1.00 1.00 500

DM1243-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1243-00

-METRIC-

page 2 of 2

245

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 8.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 HPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

242 80 1500

100%

75%

50%

kW kW

1011 970

758 728

506 485

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

11.29 4.38 5.66 255 148 228 62 33 485 4.72 5.9

11.38 4.18 5.41 226 131 170 59 33 483 4.52 5.65

12.15 4.37 5.64 168 92 124 57 33 483 4.72 5.9

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 131 720

5.6 292 1612

4.3 217 1199

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.2 198 667

2.5 220 740

2.7 220 741

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

3.0 470 896

2.4 360 686

2.9 414 788

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.45 32 135

0.36 23 103

0.44 26 119

%

7.8 1.46

6.7 1.38

6.5 1.35

kW kW kW kW kW kW kW kW

3168 1011 1031 100 0 883 685 142

2396 758 838 83 0 630 491 87

1705 506 658 67 0 441 342 33

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC246

page 1 of 2

DM5156-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0.90/19

35 0.90/21

40 0.90/22

45 1.0/23

50 1.0/24

55 1.0/26

60 1.0/27

65 1.0/28

70 1.0/30

75 1.0/31

80 to 100 1.0/33

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

0.84 0.85 0.87 0.88 0.90 0.91 0.93 0.94 0.96 2250

0.81 0.83 0.84 0.85 0.87 0.88 0.90 0.91 0.93 2500

0.79 0.80 0.81 0.83 0.84 0.86 0.87 0.89 0.90 2750

0.76 0.78 0.79 0.80 0.82 0.83 0.84 0.86 0.87 3000

1.45 1.50 1.56 1.61 1.61 1.61 1.37 1.42 1.48 1.53 1.53 1.53 1.29 1.34 1.39 1.45 1.45 1.45 1.21 1.26 1.31 1.37 1.37 1.37 1.13 1.18 1.23 1.28 1.28 1.28 1.05 1.10 1.15 1.20 1.20 1.20 1.00 1.02 1.07 1.12 1.12 1.12 1.00 1.00 1.00 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.61 1.53 1.45 1.37 1.28 1.20 1.12 1.04 1.00 2250

1.61 1.53 1.45 1.37 1.28 1.20 1.12 1.04 1.00 2500

1.61 1.53 1.45 1.37 1.28 1.20 1.12 1.04 1.00 2750

1.61 1.53 1.45 1.37 1.28 1.20 1.12 1.04 1.00 3000

G3516

1.00 0.98 0.95 0.92 0.89 0.87 1.00 1.00 0.97 0.94 0.91 0.88 1.00 1.00 0.98 0.95 0.92 0.90 1.00 1.00 1.00 0.97 0.94 0.91 1.00 1.00 1.00 0.98 0.95 0.92 1.00 1.00 1.00 1.00 0.97 0.94 1.00 1.00 1.00 1.00 0.99 0.96 1.00 1.00 1.00 1.00 1.00 0.97 1.00 1.00 1.00 1.00 1.00 0.99 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.29 1.21 1.14 1.06 1.00 1.00 1.00 1.00 1.00 0

1.34 1.27 1.19 1.11 1.03 1.00 1.00 1.00 1.00 250

1.40 1.32 1.24 1.16 1.08 1.00 1.00 1.00 1.00 500

DM5156-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5156-00

-METRIC-

page 2 of 2

247

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 HPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

207 80 1500

100%

75%

50%

kW kW

1011 970

758 728

506 485

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

10.6 4.09 5.29 249 157 223 60 18 449 4.41 5.51

10.84 4.06 5.24 213 130 169 59 18 451 4.38 5.47

11.44 3.89 5.02 156 87 114 59 18 462 4.21 5.26

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 148 817

3.2 177 976

6.3 331 1829

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.1 198 666

2.2 195 655

2.3 196 658

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

3.4 562 1070

3.5 550 1047

3.3 507 965

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.52 37 161

0.52 35 158

0.50 29 145

%

7.4 1.45

6.8 1.40

5.4 1.28

kW kW kW kW kW kW kW kW

2974 1011 945 100 0 767 575 150

2282 758 781 83 0 576 432 84

1605 506 627 67 0 381 288 25

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC248

page 1 of 2

DM5157-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/--

70 1.0/15

75 1.0/16

80 1.0/17

83 to 100 1.0/18

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

0.84 0.85 0.87 0.88 0.90 0.91 0.93 0.94 0.96 2250

0.81 0.83 0.84 0.85 0.87 0.88 0.90 0.91 0.93 2500

0.79 0.80 0.81 0.83 0.84 0.86 0.87 0.89 0.90 2750

0.76 0.78 0.79 0.80 0.82 0.83 0.84 0.86 0.87 3000

1.41 1.46 1.51 1.57 1.57 1.57 1.34 1.39 1.44 1.49 1.49 1.49 1.26 1.31 1.37 1.42 1.42 1.42 1.19 1.24 1.29 1.34 1.34 1.34 1.12 1.17 1.22 1.27 1.27 1.27 1.05 1.10 1.14 1.19 1.19 1.19 1.00 1.02 1.07 1.12 1.12 1.12 1.00 1.00 1.00 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.57 1.49 1.42 1.34 1.27 1.19 1.12 1.04 1.00 2250

1.57 1.49 1.42 1.34 1.27 1.19 1.12 1.04 1.00 2500

1.57 1.49 1.42 1.34 1.27 1.19 1.12 1.04 1.00 2750

1.57 1.49 1.42 1.34 1.27 1.19 1.12 1.04 1.00 3000

G3516

1.00 0.98 0.95 0.92 0.89 0.87 1.00 1.00 0.97 0.94 0.91 0.88 1.00 1.00 0.98 0.95 0.92 0.90 1.00 1.00 1.00 0.97 0.94 0.91 1.00 1.00 1.00 0.98 0.95 0.92 1.00 1.00 1.00 1.00 0.97 0.94 1.00 1.00 1.00 1.00 0.99 0.96 1.00 1.00 1.00 1.00 1.00 0.97 1.00 1.00 1.00 1.00 1.00 0.99 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.26 1.19 1.12 1.05 1.00 1.00 1.00 1.00 1.00 0

1.31 1.24 1.17 1.10 1.02 1.00 1.00 1.00 1.00 250

1.36 1.29 1.21 1.14 1.07 1.00 1.00 1.00 1.00 500

DM5157-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5157-00

-METRIC-

page 2 of 2

249

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 LPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

10 80 1524

100%

75%

50%

1011 970

758 728

506 485

10.27 4.26 5.51 242 150 221 61 18 453 4.58 5.73

10.8 4.3 5.56 226 130 170 56 18 453 4.63 5.79

11.51 4.1 5.29 164 89 111 48 18 463 4.43 5.54

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 151 834

3.1 168 925

9.0 459 2534

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.6 241 812

2.9 253 851

3.1 254 855

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

3.7 611 1164

3.7 584 1113

3.2 471 898

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.56 43 175

0.56 39 167

0.48 28 135

%

8.1 1.55

7.6 1.48

5.9 1.33

kW kW kW kW kW kW kW kW

2881 1011 815 100 0 803 602 152

2274 758 730 83 0 610 458 92

1615 506 616 67 0 399 304 28

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC250

page 1 of 2

DM5158-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/--

70 1.0/15

75 1.0/16

80 1.0/17

83 to 100 1.0/18

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

0.84 0.86 0.87 0.88 0.90 0.91 0.93 0.95 0.96 2250

0.82 0.83 0.84 0.86 0.87 0.89 0.90 0.92 0.93 2500

0.79 0.80 0.82 0.83 0.84 0.86 0.87 0.89 0.90 2750

0.77 0.78 0.79 0.80 0.82 0.83 0.85 0.86 0.88 3000

1.43 1.48 1.54 1.60 1.60 1.60 1.35 1.41 1.46 1.52 1.52 1.52 1.28 1.33 1.38 1.44 1.44 1.44 1.20 1.25 1.31 1.36 1.36 1.36 1.13 1.18 1.23 1.28 1.29 1.29 1.05 1.10 1.15 1.20 1.21 1.21 1.00 1.02 1.07 1.12 1.13 1.13 1.00 1.00 1.00 1.04 1.05 1.05 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.60 1.52 1.44 1.36 1.29 1.21 1.13 1.05 1.00 2250

1.60 1.52 1.44 1.36 1.29 1.21 1.13 1.05 1.00 2500

1.60 1.52 1.44 1.36 1.29 1.21 1.13 1.05 1.00 2750

1.60 1.52 1.44 1.36 1.29 1.21 1.13 1.05 1.00 3000

G3516

1.00 0.98 0.95 0.93 0.90 0.87 1.00 1.00 0.97 0.94 0.91 0.88 1.00 1.00 0.98 0.95 0.93 0.90 1.00 1.00 1.00 0.97 0.94 0.91 1.00 1.00 1.00 0.99 0.96 0.93 1.00 1.00 1.00 1.00 0.97 0.94 1.00 1.00 1.00 1.00 0.99 0.96 1.00 1.00 1.00 1.00 1.00 0.98 1.00 1.00 1.00 1.00 1.00 0.99 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.27 1.20 1.13 1.05 1.00 1.00 1.00 1.00 1.00 0

1.32 1.25 1.18 1.10 1.03 1.00 1.00 1.00 1.00 250

1.38 1.30 1.23 1.15 1.08 1.00 1.00 1.00 1.00 500

DM5158-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5158-00

-METRIC-

page 2 of 2

251

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°C) 32 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

NAT GAS 36.2 DELTEC 10 80 350

100%

75%

50%

kW kW

1070 1030

803 773

535 515

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

9.53 4.41 5.7 255 154 237 40 24 485 4.72 5.9

10.06 4.59 5.93 220 127 183 36 24 492 4.91 6.14

10.77 4.82 6.22 165 89 131 34 24 500 5.16 6.45

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.7 46 250

0.8 46 250

0.8 46 250

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

3.5 351 1180

3.4 337 1135

3.5 325 1095

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

8.8 1583 3015

10.0 1730 3297

12.2 1997 3806

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.32 128 453

1.50 138 495

1.84 158 571

%

9.9 1.74

9.8 1.73

9.7 1.70

kW kW kW kW kW kW kW kW

2829 1070 512 77 0 987 741 198

2241 803 439 71 0 788 590 123

1600 535 368 64 0 571 423 53

Engine Power (w/o fan) Generator Set Power (w/o fan)

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9)

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC252

page 1 of 2

DM5166-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/18*

70 1.0/20*

75 1.0/22

80 to 100 1.0/24

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.96 0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 0

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 250

0.91 0.92 0.94 0.95 0.97 0.98 1.00 1.00 1.00 500

0.73 0.74 0.75 0.77 0.78 0.79 0.81 0.82 0.83 2250

0.71 0.72 0.73 0.74 0.76 0.77 0.78 0.79 0.81 2500

0.69 0.70 0.71 0.72 0.73 0.74 0.76 0.77 0.78 2750

0.67 0.68 0.69 0.70 0.71 0.72 0.73 0.75 0.76 3000

1.29 1.29 1.29 1.29 1.29 1.29 1.23 1.23 1.23 1.23 1.23 1.23 1.16 1.16 1.16 1.16 1.16 1.16 1.10 1.10 1.10 1.10 1.10 1.10 1.04 1.04 1.04 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.29 1.23 1.16 1.10 1.04 1.00 1.00 1.00 1.00 2250

1.29 1.23 1.16 1.10 1.04 1.00 1.00 1.00 1.00 2500

1.29 1.23 1.16 1.10 1.04 1.00 1.00 1.00 1.00 2750

1.29 1.23 1.16 1.10 1.04 1.00 1.00 1.00 1.00 3000

G3516

0.88 0.85 0.83 0.80 0.78 0.75 0.89 0.87 0.84 0.82 0.79 0.77 0.91 0.88 0.85 0.83 0.80 0.78 0.92 0.89 0.87 0.84 0.82 0.79 0.94 0.91 0.88 0.86 0.83 0.80 0.95 0.92 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.88 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 1.00 0.97 0.94 0.92 0.89 0.86 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.23 1.17 1.11 1.05 1.00 1.00 1.00 1.00 1.00 0

1.27 1.21 1.15 1.09 1.02 1.00 1.00 1.00 1.00 250

1.29 1.23 1.16 1.10 1.04 1.00 1.00 1.00 1.00 500

DM5166-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM5166-00

-METRIC-

page 2 of 2

253

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°C) 32 Jacket Water Outlet Temperature (°C) 127 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

NAT GAS 36.2 DELTEC 10 80 350

100%

75%

50%

kW kW

1070 1030

803 773

535 515

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

9.67 4.49 5.8 261 159 245 41 20 514 4.8 6.01

9.97 4.55 5.88 226 132 186 37 20 519 4.87 6.09

10.48 4.71 6.09 166 91 130 35 20 533 5.05 6.31

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.7 46 250

0.8 46 250

0.8 46 250

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

3.4 336 1132

3.4 329 1106

3.4 323 1086

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

7.4 1346 2565

7.9 1395 2659

8.7 1447 2757

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.12 109 385

1.19 111 399

1.31 112 414

%

9.9 1.75

9.7 1.72

9.5 1.69

kW kW kW kW kW kW kW kW

2871 1070 315 96 148 1032 801 210

2230 803 271 87 140 801 622 128

1580 535 224 71 129 569 443 52

Engine Power (w/o fan) Generator Set Power (w/o fan)

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9)

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC254

page 1 of 2

DM5161-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 .95/16*

70 1.0/16*

75 1.0/18

80 to 100 1.0/20

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.96 0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 0

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 250

0.91 0.92 0.94 0.95 0.97 0.98 1.00 1.00 1.00 500

0.73 0.74 0.75 0.77 0.78 0.79 0.81 0.82 0.83 2250

0.71 0.72 0.73 0.74 0.76 0.77 0.78 0.79 0.81 2500

0.69 0.70 0.71 0.72 0.73 0.74 0.76 0.77 0.78 2750

0.67 0.68 0.69 0.70 0.71 0.72 0.73 0.75 0.76 3000

1.28 1.28 1.28 1.28 1.28 1.28 1.22 1.22 1.22 1.22 1.22 1.22 1.16 1.16 1.16 1.16 1.16 1.16 1.10 1.10 1.10 1.10 1.10 1.10 1.04 1.04 1.04 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.28 1.22 1.16 1.10 1.04 1.00 1.00 1.00 1.00 2250

1.28 1.22 1.16 1.10 1.04 1.00 1.00 1.00 1.00 2500

1.28 1.22 1.16 1.10 1.04 1.00 1.00 1.00 1.00 2750

1.28 1.22 1.16 1.10 1.04 1.00 1.00 1.00 1.00 3000

G3516

0.88 0.85 0.83 0.80 0.78 0.75 0.89 0.87 0.84 0.82 0.79 0.77 0.91 0.88 0.85 0.83 0.80 0.78 0.92 0.89 0.87 0.84 0.82 0.79 0.94 0.91 0.88 0.86 0.83 0.80 0.95 0.92 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.88 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 1.00 0.97 0.94 0.92 0.89 0.86 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.22 1.16 1.10 1.04 1.00 1.00 1.00 1.00 1.00 0

1.27 1.21 1.14 1.08 1.02 1.00 1.00 1.00 1.00 250

1.28 1.22 1.16 1.10 1.04 1.00 1.00 1.00 1.00 500

DM5161-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM5161-00

-METRIC-

page 2 of 2

255

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°C) 32 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

NAT GAS 36.2 DELTEC 10 80 500

100%

75%

50%

kW kW

1070 1030

803 773

535 515

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

9.28 4.18 5.4 253 152 229 41 24 489 4.48 5.6

9.72 4.26 5.5 208 121 174 37 24 501 4.57 5.71

10.29 4.35 5.62 158 84 123 34 24 503 4.67 5.84

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.4 91 500

1.5 91 500

1.5 91 500

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

3.3 332 1118

3.2 315 1060

3.1 298 1002

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

7.3 1139 2170

8.1 1240 2362

9.2 1340 2553

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.10 88 326

1.22 94 355

1.38 99 383

%

9.4 1.67

9.2 1.64

8.9 1.59

kW kW kW kW kW kW kW kW kW

2757 1070 489 81 0 934 712 71 115

2166 803 441 79 0 738 564 23 85

1528 535 369 70 0 511 387 -10 55

Engine Power (w/o fan) Generator Set Power (w/o fan)

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9)

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8) Heat Rejection to Aftercooler - stage 2 (3) (7) (8)

-METRIC256

page 1 of 2

DM5162-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/18*

70 1.0/20*

75 1.0/22

80 to 100 1.0/24

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 250

0.92 0.94 0.95 0.97 0.98 1.00 1.00 1.00 1.00 500

0.74 0.76 0.77 0.78 0.79 0.81 0.82 0.84 0.85 2250

0.72 0.73 0.74 0.76 0.77 0.78 0.80 0.81 0.82 2500

0.70 0.71 0.72 0.73 0.75 0.76 0.77 0.78 0.80 2750

0.68 0.69 0.70 0.71 0.72 0.73 0.75 0.76 0.77 3000

1.32 1.32 1.32 1.32 1.32 1.32 1.26 1.26 1.26 1.26 1.26 1.26 1.19 1.19 1.19 1.19 1.19 1.19 1.13 1.13 1.13 1.13 1.13 1.13 1.06 1.06 1.06 1.06 1.06 1.06 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.32 1.26 1.19 1.13 1.06 1.00 1.00 1.00 1.00 2250

1.32 1.26 1.19 1.13 1.06 1.00 1.00 1.00 1.00 2500

1.32 1.26 1.19 1.13 1.06 1.00 1.00 1.00 1.00 2750

1.32 1.26 1.19 1.13 1.06 1.00 1.00 1.00 1.00 3000

G3516

0.90 0.87 0.84 0.82 0.79 0.77 0.91 0.88 0.86 0.83 0.80 0.78 0.92 0.90 0.87 0.84 0.82 0.79 0.94 0.91 0.88 0.86 0.83 0.81 0.95 0.93 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.89 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 1.00 0.97 0.94 0.92 0.89 0.86 1.00 0.99 0.96 0.93 0.90 0.88 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.23 1.17 1.11 1.05 1.00 1.00 1.00 1.00 1.00 0

1.28 1.21 1.15 1.09 1.02 1.00 1.00 1.00 1.00 250

1.32 1.26 1.19 1.13 1.06 1.00 1.00 1.00 1.00 500

DM5162-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM5162-00

-METRIC-

page 2 of 2

257

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°C) 32 Jacket Water Outlet Temperature (°C) 127 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

NAT GAS 36.2 DELTEC 10 80 500

100%

75%

50%

kW kW

1070 1030

803 773

535 515

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

9.44 4.24 5.48 251 151 231 40 20 521 4.54 5.68

9.87 4.35 5.62 218 129 178 36 20 527 4.66 5.83

10.53 4.54 5.86 163 91 126 34 20 537 4.87 6.08

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.4 91 500

1.5 91 500

1.6 90 500

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

3.4 353 1188

3.5 348 1172

3.6 344 1157

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

5.6 1032 1965

6.5 1162 2213

7.5 1257 2396

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.85 81 295

0.98 90 332

1.13 95 360

%

9.6 1.69

9.4 1.67

9.1 1.64

kW kW kW kW kW kW kW kW

2803 1070 325 96 149 977 773 187

2199 803 281 87 142 767 605 120

1564 535 231 68 131 548 431 51

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC258

page 1 of 2

DM5163-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 70 0.90/16* 0.90/18*

75 1.0/18

80 to 100 1.0/20

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 250

0.92 0.94 0.95 0.97 0.98 1.00 1.00 1.00 1.00 500

0.74 0.76 0.77 0.78 0.79 0.81 0.82 0.84 0.85 2250

0.72 0.73 0.74 0.76 0.77 0.78 0.80 0.81 0.82 2500

0.70 0.71 0.72 0.73 0.75 0.76 0.77 0.78 0.80 2750

0.68 0.69 0.70 0.71 0.72 0.73 0.75 0.76 0.77 3000

1.32 1.32 1.32 1.32 1.32 1.32 1.26 1.26 1.26 1.26 1.26 1.26 1.19 1.19 1.19 1.19 1.19 1.19 1.13 1.13 1.13 1.13 1.13 1.13 1.06 1.06 1.06 1.06 1.06 1.06 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.32 1.26 1.19 1.13 1.06 1.00 1.00 1.00 1.00 2250

1.32 1.26 1.19 1.13 1.06 1.00 1.00 1.00 1.00 2500

1.32 1.26 1.19 1.13 1.06 1.00 1.00 1.00 1.00 2750

1.32 1.26 1.19 1.13 1.06 1.00 1.00 1.00 1.00 3000

G3516

0.90 0.87 0.84 0.82 0.79 0.77 0.91 0.88 0.86 0.83 0.80 0.78 0.92 0.90 0.87 0.84 0.82 0.79 0.94 0.91 0.88 0.86 0.83 0.81 0.95 0.93 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.89 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 1.00 0.97 0.94 0.92 0.89 0.86 1.00 0.99 0.96 0.93 0.90 0.88 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.23 1.17 1.11 1.05 1.00 1.00 1.00 1.00 1.00 0

1.28 1.21 1.15 1.09 1.02 1.00 1.00 1.00 1.00 250

1.32 1.26 1.19 1.13 1.06 1.00 1.00 1.00 1.00 500

DM5163-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM5163-00

-METRIC-

page 2 of 2

259

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°C) 70/32 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

NAT GAS 36.2 DELTEC 10 80 350

100%

75%

50%

kW kW

1070 1030

803 773

535 515

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

9.53 4.41 5.7 255 154 237 40 24 485 4.72 5.9

10.06 4.59 5.93 220 127 183 36 24 492 4.91 6.14

10.77 4.82 6.22 165 89 131 34 24 500 5.16 6.45

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.7 46 250

0.8 46 250

0.8 46 250

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

3.5 351 1180

3.4 337 1135

3.5 325 1095

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

8.8 1583 3015

10.0 1730 3297

12.2 1997 3806

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.32 128 453

1.50 138 495

1.84 158 571

%

9.9 1.74

9.8 1.73

9.7 1.70

kW kW kW kW kW kW kW kW kW

2829 1070 512 77 0 987 741 127 71

2241 803 439 71 0 788 590 68 55

1600 535 368 64 0 571 423 16 37

Engine Power (w/o fan) Generator Set Power (w/o fan)

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9)

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8) Heat Rejection to Aftercooler - stage 2 (3) (7) (8)

-METRIC260

page 1 of 2

DM1229-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/18*

70 1.0/20*

75 1.0/22

80 to 100 1.0/24

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.96 0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 0

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 250

0.91 0.92 0.94 0.95 0.97 0.98 1.00 1.00 1.00 500

0.73 0.74 0.75 0.77 0.78 0.79 0.81 0.82 0.83 2250

0.71 0.72 0.73 0.74 0.76 0.77 0.78 0.79 0.81 2500

0.69 0.70 0.71 0.72 0.73 0.74 0.76 0.77 0.78 2750

0.67 0.68 0.69 0.70 0.71 0.72 0.73 0.75 0.76 3000

1.29 1.29 1.29 1.29 1.29 1.29 1.23 1.23 1.23 1.23 1.23 1.23 1.16 1.16 1.16 1.16 1.16 1.16 1.10 1.10 1.10 1.10 1.10 1.10 1.04 1.04 1.04 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.29 1.23 1.16 1.10 1.04 1.00 1.00 1.00 1.00 2250

1.29 1.23 1.16 1.10 1.04 1.00 1.00 1.00 1.00 2500

1.29 1.23 1.16 1.10 1.04 1.00 1.00 1.00 1.00 2750

1.29 1.23 1.16 1.10 1.04 1.00 1.00 1.00 1.00 3000

G3516

0.88 0.85 0.83 0.80 0.78 0.75 0.89 0.87 0.84 0.82 0.79 0.77 0.91 0.88 0.85 0.83 0.80 0.78 0.92 0.89 0.87 0.84 0.82 0.79 0.94 0.91 0.88 0.86 0.83 0.80 0.95 0.92 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.88 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 1.00 0.97 0.94 0.92 0.89 0.86 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.23 1.17 1.11 1.05 1.00 1.00 1.00 1.00 1.00 0

1.27 1.21 1.15 1.09 1.02 1.00 1.00 1.00 1.00 250

1.29 1.23 1.16 1.10 1.04 1.00 1.00 1.00 1.00 500

DM1229-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1229-00

-METRIC-

page 2 of 2

261

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°C) 70/32 Jacket Water Outlet Temperature (°C) 127 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

NAT GAS 36.2 DELTEC 10 80 350

100%

75%

50%

kW kW

1070 1030

803 773

535 515

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

9.67 4.49 5.8 261 159 245 41 20 514 4.8 6.01

9.97 4.55 5.88 226 132 186 37 20 519 4.87 6.09

10.48 4.71 6.09 166 91 130 35 20 533 5.05 6.31

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.7 46 250

0.8 46 250

0.8 46 250

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

3.4 336 1132

3.4 329 1106

3.4 323 1086

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

7.4 1346 2565

7.9 1395 2659

8.7 1447 2757

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.12 109 385

1.19 111 399

1.31 112 414

%

9.9 1.75

9.7 1.72

9.5 1.69

kW kW kW kW kW kW kW kW kW

2871 1070 315 96 148 1032 801 127 83

2230 803 271 87 140 801 622 67 61

1580 535 224 71 129 569 443 15 37

Engine Power (w/o fan) Generator Set Power (w/o fan)

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9)

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8) Heat Rejection to Aftercooler - stage 2 (3) (7) (8)

-METRIC262

page 1 of 2

DM1241-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 .95/16*

70 1.0/16*

75 1.0/18

80 to 100 1.0/20

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.96 0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 0

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 250

0.91 0.92 0.94 0.95 0.97 0.98 1.00 1.00 1.00 500

0.73 0.74 0.75 0.77 0.78 0.79 0.81 0.82 0.83 2250

0.71 0.72 0.73 0.74 0.76 0.77 0.78 0.79 0.81 2500

0.69 0.70 0.71 0.72 0.73 0.74 0.76 0.77 0.78 2750

0.67 0.68 0.69 0.70 0.71 0.72 0.73 0.75 0.76 3000

1.28 1.28 1.28 1.28 1.28 1.28 1.22 1.22 1.22 1.22 1.22 1.22 1.16 1.16 1.16 1.16 1.16 1.16 1.10 1.10 1.10 1.10 1.10 1.10 1.04 1.04 1.04 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.28 1.22 1.16 1.10 1.04 1.00 1.00 1.00 1.00 2250

1.28 1.22 1.16 1.10 1.04 1.00 1.00 1.00 1.00 2500

1.28 1.22 1.16 1.10 1.04 1.00 1.00 1.00 1.00 2750

1.28 1.22 1.16 1.10 1.04 1.00 1.00 1.00 1.00 3000

G3516

0.88 0.85 0.83 0.80 0.78 0.75 0.89 0.87 0.84 0.82 0.79 0.77 0.91 0.88 0.85 0.83 0.80 0.78 0.92 0.89 0.87 0.84 0.82 0.79 0.94 0.91 0.88 0.86 0.83 0.80 0.95 0.92 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.88 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 1.00 0.97 0.94 0.92 0.89 0.86 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.22 1.16 1.10 1.04 1.00 1.00 1.00 1.00 1.00 0

1.27 1.21 1.14 1.08 1.02 1.00 1.00 1.00 1.00 250

1.28 1.22 1.16 1.10 1.04 1.00 1.00 1.00 1.00 500

DM1241-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1241-00

-METRIC-

page 2 of 2

263

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°C) 70/32 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

NAT GAS 36.2 DELTEC 10 80 500

100%

75%

50%

kW kW

1070 1030

803 773

535 515

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

9.28 4.18 5.4 253 152 229 41 24 489 4.48 5.6

9.72 4.26 5.5 208 121 174 37 24 501 4.57 5.71

10.29 4.35 5.62 158 84 123 34 24 503 4.67 5.84

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.4 91 500

1.5 91 500

1.5 91 500

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

3.3 332 1118

3.2 315 1060

3.1 298 1002

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

7.3 1139 2170

8.1 1240 2362

9.2 1340 2553

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.10 88 326

1.22 94 355

1.38 99 383

%

9.4 1.67

9.2 1.64

8.9 1.59

kW kW kW kW kW kW kW kW kW

2757 1070 489 81 0 934 712 110 76

2166 803 441 79 0 738 564 52 55

1528 535 369 70 0 511 387 10 34

Engine Power (w/o fan) Generator Set Power (w/o fan)

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9)

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8) Heat Rejection to Aftercooler - stage 2 (3) (7) (8)

-METRIC264

page 1 of 2

DM1232-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/18*

70 1.0/20*

75 1.0/22

80 to 100 1.0/24

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 250

0.92 0.94 0.95 0.97 0.98 1.00 1.00 1.00 1.00 500

0.74 0.76 0.77 0.78 0.79 0.81 0.82 0.84 0.85 2250

0.72 0.73 0.74 0.76 0.77 0.78 0.80 0.81 0.82 2500

0.70 0.71 0.72 0.73 0.75 0.76 0.77 0.78 0.80 2750

0.68 0.69 0.70 0.71 0.72 0.73 0.75 0.76 0.77 3000

1.32 1.32 1.32 1.32 1.32 1.32 1.26 1.26 1.26 1.26 1.26 1.26 1.19 1.19 1.19 1.19 1.19 1.19 1.13 1.13 1.13 1.13 1.13 1.13 1.06 1.06 1.06 1.06 1.06 1.06 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.32 1.26 1.19 1.13 1.06 1.00 1.00 1.00 1.00 2250

1.32 1.26 1.19 1.13 1.06 1.00 1.00 1.00 1.00 2500

1.32 1.26 1.19 1.13 1.06 1.00 1.00 1.00 1.00 2750

1.32 1.26 1.19 1.13 1.06 1.00 1.00 1.00 1.00 3000

G3516

0.90 0.87 0.84 0.82 0.79 0.77 0.91 0.88 0.86 0.83 0.80 0.78 0.92 0.90 0.87 0.84 0.82 0.79 0.94 0.91 0.88 0.86 0.83 0.81 0.95 0.93 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.89 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 1.00 0.97 0.94 0.92 0.89 0.86 1.00 0.99 0.96 0.93 0.90 0.88 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.23 1.17 1.11 1.05 1.00 1.00 1.00 1.00 1.00 0

1.28 1.21 1.15 1.09 1.02 1.00 1.00 1.00 1.00 250

1.32 1.26 1.19 1.13 1.06 1.00 1.00 1.00 1.00 500

DM1232-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1232-00

-METRIC-

page 2 of 2

265

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°C) 70/32 Jacket Water Outlet Temperature (°C) 127 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

NAT GAS 36.2 DELTEC 10 80 500

100%

75%

50%

kW kW

1070 1030

803 773

535 515

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

9.44 4.24 5.48 251 151 231 40 20 521 4.54 5.68

9.87 4.35 5.62 218 129 178 36 20 527 4.66 5.83

10.53 4.54 5.86 163 91 126 34 20 537 4.87 6.08

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.4 91 500

1.5 91 500

1.6 90 500

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

3.4 353 1188

3.5 348 1172

3.6 344 1157

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

5.6 1032 1965

6.5 1162 2213

7.5 1257 2396

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.85 81 295

0.98 90 332

1.13 95 360

%

9.6 1.69

9.4 1.67

9.1 1.64

kW kW kW kW kW kW kW kW kW

2803 1070 325 96 149 977 773 109 78

2199 803 281 87 142 767 605 61 59

1564 535 231 68 131 548 431 15 36

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8) Heat Rejection to Aftercooler - stage 2 (3) (7) (8)

-METRIC266

page 1 of 2

DM1244-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 70 0.90/16* 0.90/18*

75 1.0/18

80 to 100 1.0/20

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 250

0.92 0.94 0.95 0.97 0.98 1.00 1.00 1.00 1.00 500

0.74 0.76 0.77 0.78 0.79 0.81 0.82 0.84 0.85 2250

0.72 0.73 0.74 0.76 0.77 0.78 0.80 0.81 0.82 2500

0.70 0.71 0.72 0.73 0.75 0.76 0.77 0.78 0.80 2750

0.68 0.69 0.70 0.71 0.72 0.73 0.75 0.76 0.77 3000

1.32 1.32 1.32 1.32 1.32 1.32 1.26 1.26 1.26 1.26 1.26 1.26 1.19 1.19 1.19 1.19 1.19 1.19 1.13 1.13 1.13 1.13 1.13 1.13 1.06 1.06 1.06 1.06 1.06 1.06 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.32 1.26 1.19 1.13 1.06 1.00 1.00 1.00 1.00 2250

1.32 1.26 1.19 1.13 1.06 1.00 1.00 1.00 1.00 2500

1.32 1.26 1.19 1.13 1.06 1.00 1.00 1.00 1.00 2750

1.32 1.26 1.19 1.13 1.06 1.00 1.00 1.00 1.00 3000

G3516

0.90 0.87 0.84 0.82 0.79 0.77 0.91 0.88 0.86 0.83 0.80 0.78 0.92 0.90 0.87 0.84 0.82 0.79 0.94 0.91 0.88 0.86 0.83 0.81 0.95 0.93 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.89 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 1.00 0.97 0.94 0.92 0.89 0.86 1.00 0.99 0.96 0.93 0.90 0.88 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.23 1.17 1.11 1.05 1.00 1.00 1.00 1.00 1.00 0

1.28 1.21 1.15 1.09 1.02 1.00 1.00 1.00 1.00 250

1.32 1.26 1.19 1.13 1.06 1.00 1.00 1.00 1.00 500

DM1244-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1244-00

-METRIC-

page 2 of 2

267

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°C) 32 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 HPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

207 80 1500

100%

75%

50%

kW kW

1070 1025

803 769

535 513

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

10.4 4.03 5.21 251 158 223 44 20 440 4.34 5.43

10.59 3.96 5.12 215 130 168 41 20 441 4.27 5.34

11.18 3.82 4.93 159 88 114 40 20 453 4.13 5.17

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 151 830

3.1 175 966

5.8 316 1743

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.1 199 669

2.1 196 660

2.2 197 661

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

3.6 595 1133

3.6 585 1114

3.7 589 1123

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.54 39 170

0.54 37 168

0.56 35 169

%

7.3 1.46

6.8 1.40

5.6 1.28

kW kW kW kW kW kW kW kW

3090 1070 948 100 0 785 582 186

2359 803 781 83 0 582 432 111

1660 535 626 67 0 390 291 42

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC268

page 1 of 2

DM5159-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/15

70 1.0/16

75 1.0/18

80 1.0/19

83 to 100 1.0/2.0

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

0.84 0.85 0.87 0.88 0.90 0.91 0.93 0.94 0.96 2250

0.81 0.83 0.84 0.85 0.87 0.88 0.90 0.91 0.93 2500

0.79 0.80 0.81 0.83 0.84 0.86 0.87 0.89 0.90 2750

0.76 0.78 0.79 0.80 0.82 0.83 0.84 0.86 0.87 3000

1.35 1.39 1.43 1.48 1.48 1.48 1.28 1.33 1.37 1.42 1.42 1.42 1.22 1.27 1.31 1.35 1.35 1.35 1.16 1.20 1.25 1.29 1.29 1.29 1.10 1.14 1.18 1.23 1.23 1.23 1.04 1.08 1.12 1.16 1.16 1.16 1.00 1.02 1.06 1.10 1.10 1.10 1.00 1.00 1.00 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.48 1.42 1.35 1.29 1.23 1.16 1.10 1.04 1.00 2250

1.48 1.42 1.35 1.29 1.23 1.16 1.10 1.04 1.00 2500

1.48 1.42 1.35 1.29 1.23 1.16 1.10 1.04 1.00 2750

1.48 1.42 1.35 1.29 1.23 1.16 1.10 1.04 1.00 3000

G3516

1.00 0.98 0.95 0.92 0.89 0.87 1.00 1.00 0.97 0.94 0.91 0.88 1.00 1.00 0.98 0.95 0.92 0.90 1.00 1.00 1.00 0.97 0.94 0.91 1.00 1.00 1.00 0.98 0.95 0.92 1.00 1.00 1.00 1.00 0.97 0.94 1.00 1.00 1.00 1.00 0.99 0.96 1.00 1.00 1.00 1.00 1.00 0.97 1.00 1.00 1.00 1.00 1.00 0.99 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.22 1.16 1.10 1.04 1.00 1.00 1.00 1.00 1.00 0

1.26 1.20 1.14 1.08 1.02 1.00 1.00 1.00 1.00 250

1.30 1.24 1.18 1.12 1.06 1.00 1.00 1.00 1.00 500

DM5159-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5159-00

-METRIC-

page 2 of 2

269

®

G3516 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°C) 32 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 LPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

10 80 1524

100%

75%

50%

kW kW

1070 1025

803 769

535 513

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

10.11 4.19 5.41 247 151 223 44 20 445 4.5 5.63

10.72 4.34 5.61 234 137 176 42 20 443 4.67 5.84

11.28 4.12 5.32 169 93 116 42 20 456 4.45 5.56

Engine Data

G3516

Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 161 889

2.9 167 920

7.4 387 2139

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 252 849

2.8 251 843

3.2 271 913

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

4.0 671 1277

4.6 739 1409

3.8 579 1102

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.60 47 192

0.69 52 212

0.58 36 166

%

8.2 1.54

8.1 1.50

6.4 1.36

kW kW kW kW kW kW kW kW

3003 1070 816 100 0 824 611 193

2389 803 726 83 0 643 473 134

1676 535 605 67 0 420 315 49

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC270

page 1 of 2

DM5165-00

®

G3516 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/15

70 1.0/16

75 1.0/18

80 1.0/19

83 to 100 1.0/2.0

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

0.84 0.86 0.87 0.88 0.90 0.91 0.93 0.95 0.96 2250

0.82 0.83 0.84 0.86 0.87 0.89 0.90 0.92 0.93 2500

0.79 0.80 0.82 0.83 0.84 0.86 0.87 0.89 0.90 2750

0.77 0.78 0.79 0.80 0.82 0.83 0.85 0.86 0.88 3000

1.35 1.40 1.44 1.49 1.49 1.49 1.29 1.33 1.38 1.42 1.43 1.43 1.23 1.27 1.31 1.36 1.36 1.36 1.17 1.21 1.25 1.29 1.30 1.30 1.10 1.14 1.19 1.23 1.23 1.23 1.04 1.08 1.12 1.16 1.17 1.17 1.00 1.02 1.06 1.10 1.10 1.10 1.00 1.00 1.00 1.03 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.49 1.43 1.36 1.30 1.23 1.17 1.10 1.04 1.00 2250

1.49 1.43 1.36 1.30 1.23 1.17 1.10 1.04 1.00 2500

1.49 1.43 1.36 1.30 1.23 1.17 1.10 1.04 1.00 2750

1.49 1.43 1.36 1.30 1.23 1.17 1.10 1.04 1.00 3000

G3516

1.00 0.98 0.95 0.93 0.90 0.87 1.00 1.00 0.97 0.94 0.91 0.88 1.00 1.00 0.98 0.95 0.93 0.90 1.00 1.00 1.00 0.97 0.94 0.91 1.00 1.00 1.00 0.99 0.96 0.93 1.00 1.00 1.00 1.00 0.97 0.94 1.00 1.00 1.00 1.00 0.99 0.96 1.00 1.00 1.00 1.00 1.00 0.98 1.00 1.00 1.00 1.00 1.00 0.99 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.23 1.17 1.10 1.04 1.00 1.00 1.00 1.00 1.00 0

1.27 1.21 1.15 1.08 1.02 1.00 1.00 1.00 1.00 250

1.31 1.25 1.19 1.12 1.06 1.00 1.00 1.00 1.00 500

DM5165-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5165-00

-METRIC-

page 2 of 2

271

®

G3512

G3512 TA

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 9.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type STANDARD

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 HPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

172 80 1524

100%

75%

50%

590 555

443 416

295 278

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

10.61 3.08 3.98 198 117 182 60 22.5 465 3.36 4.21

11.17 3.13 4.05 183 106 147 59 22.5 448 3.43 4.29

12.04 3.48 4.5 146 75 109 59 22.5 419 3.8 4.76

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

27.8 1520 8399

24.6 1273 7033

24.1 1141 6301

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.5 208 701

2.6 208 698

2.7 196 658

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.0 318 605

2.2 337 642

2.9 402 765

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.30 15 91

0.34 16 97

0.44 19 115

%

2.0 1.09

1.3 1.05

1.6 1.09

kW kW kW kW kW kW kW kW

1738 590 686 64 0 358 275 40

1372 443 586 53 0 265 200 26

986 295 458 43 0 183 134 7

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9)

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC272

page 1 of 2

DM5207-00

®

G3512 TA

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 35 40 45 50 55 60 0.62/14 0.62/15 0.62/16 0.62/17 0.90/14 0.90/15 0.90/16

65 1.0/16

70 1.0/18

75 1.0/20

80 1.0/23

83 to 100 1.0/23

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

1.00 0.98 0.95 0.93 0.90 0.87 1.00 1.00 0.97 0.94 0.91 0.88 1.00 1.00 0.98 0.95 0.93 0.90 1.00 1.00 1.00 0.97 0.94 0.91 1.00 1.00 1.00 0.99 0.96 0.93 1.00 1.00 1.00 1.00 0.97 0.94 1.00 1.00 1.00 1.00 0.99 0.96 1.00 1.00 1.00 1.00 1.00 0.98 1.00 1.00 1.00 1.00 1.00 0.99 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.84 0.86 0.87 0.88 0.90 0.91 0.93 0.95 0.96 2250

0.82 0.83 0.84 0.86 0.87 0.89 0.90 0.92 0.93 2500

0.79 0.80 0.82 0.83 0.84 0.86 0.87 0.89 0.90 2750

0.77 0.78 0.79 0.80 0.82 0.83 0.85 0.86 0.88 3000

1.61 1.68 1.76 1.84 1.85 1.85 1.50 1.57 1.65 1.73 1.74 1.74 1.39 1.47 1.54 1.62 1.62 1.62 1.28 1.36 1.43 1.51 1.51 1.51 1.18 1.25 1.32 1.40 1.40 1.40 1.07 1.14 1.21 1.28 1.29 1.29 1.00 1.03 1.10 1.17 1.18 1.18 1.00 1.00 1.00 1.06 1.07 1.07 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.85 1.74 1.62 1.51 1.40 1.29 1.18 1.07 1.00 2250

1.85 1.74 1.62 1.51 1.40 1.29 1.18 1.07 1.00 2500

1.85 1.74 1.62 1.51 1.40 1.29 1.18 1.07 1.00 2750

1.85 1.74 1.62 1.51 1.40 1.29 1.18 1.07 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.38 1.28 1.18 1.07 1.00 1.00 1.00 1.00 1.00 0

1.46 1.35 1.25 1.14 1.04 1.00 1.00 1.00 1.00 250

1.53 1.43 1.32 1.21 1.11 1.00 1.00 1.00 1.00 500

DM5207-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5207-00

-METRIC-

page 2 of 2

273

®

G3512

G3512 TA

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 9.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type CATALYST

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

NAT GAS 36.2 HPG IMPCO 172 80 1524

100%

75%

50%

590 555

443 416

295 278

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

11.07 2.92 3.78 204 126 178 60 22.5 478 3.21 4.01

11.68 3.1 4 187 113 147 58 22.5 447 3.4 4.25

12.72 3.36 4.34 145 78 110 58 22.5 421 3.69 4.61

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

14.2 758 4186

13.3 671 3704

12.8 595 3284

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

16.7 1465 4933

19.0 1470 4952

20.3 1451 4885

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.9 444 845

3.4 500 953

4.8 647 1233

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.43 20 127

0.52 22 143

0.72 28 185

%

0.3 0.99

0.3 0.99

0.3 0.99

kW kW kW kW kW kW kW kW

1813 590 755 64 0 360 274 43

1435 443 642 53 0 268 198 29

1042 295 509 43 0 186 132 9

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9)

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC274

page 1 of 2

DM5209-00

®

G3512 TA

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 35 40 45 50 55 60 0.62/14 0.62/15 0.62/16 0.62/17 0.90/14 0.90/15 0.90/16

65 1.0/16

70 1.0/18

75 1.0/20

80 1.0/23

83 to 100 1.0/23

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

1.00 0.98 0.95 0.93 0.90 0.87 1.00 1.00 0.97 0.94 0.91 0.88 1.00 1.00 0.98 0.95 0.93 0.90 1.00 1.00 1.00 0.97 0.94 0.91 1.00 1.00 1.00 0.99 0.96 0.93 1.00 1.00 1.00 1.00 0.97 0.94 1.00 1.00 1.00 1.00 0.99 0.96 1.00 1.00 1.00 1.00 1.00 0.98 1.00 1.00 1.00 1.00 1.00 0.99 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.84 0.86 0.87 0.88 0.90 0.91 0.93 0.95 0.96 2250

0.82 0.83 0.84 0.86 0.87 0.89 0.90 0.92 0.93 2500

0.79 0.80 0.82 0.83 0.84 0.86 0.87 0.89 0.90 2750

0.77 0.78 0.79 0.80 0.82 0.83 0.85 0.86 0.88 3000

1.56 1.63 1.70 1.77 1.78 1.78 1.46 1.53 1.60 1.67 1.68 1.68 1.36 1.43 1.50 1.57 1.58 1.58 1.26 1.33 1.40 1.47 1.47 1.47 1.16 1.23 1.30 1.37 1.37 1.37 1.07 1.13 1.20 1.26 1.27 1.27 1.00 1.03 1.10 1.16 1.17 1.17 1.00 1.00 1.00 1.06 1.07 1.07 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.78 1.68 1.58 1.47 1.37 1.27 1.17 1.07 1.00 2250

1.78 1.68 1.58 1.47 1.37 1.27 1.17 1.07 1.00 2500

1.78 1.68 1.58 1.47 1.37 1.27 1.17 1.07 1.00 2750

1.78 1.68 1.58 1.47 1.37 1.27 1.17 1.07 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.35 1.26 1.16 1.06 1.00 1.00 1.00 1.00 1.00 0

1.42 1.32 1.23 1.13 1.03 1.00 1.00 1.00 1.00 250

1.49 1.39 1.29 1.20 1.10 1.00 1.00 1.00 1.00 500

DM5209-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5209-00

-METRIC-

page 2 of 2

275

®

G3512

G3512 TA

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 9.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type STANDARD

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 LPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

10 80 1524

100%

75%

50%

590 555

443 416

295 278

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

10.61 3.08 3.98 198 117 182 60 22.5 465 3.36 4.21

11.17 3.13 4.05 183 106 147 59 22.5 448 3.43 4.29

12.04 3.48 4.5 146 75 109 59 22.5 419 3.8 4.76

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

27.8 1520 8399

24.6 1273 7033

24.1 1141 6301

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.5 208 701

2.6 208 698

2.7 196 658

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.0 318 605

2.2 337 642

2.9 402 765

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.30 15 91

0.34 16 97

0.44 19 115

%

2.0 1.09

1.3 1.05

1.6 1.09

kW kW kW kW kW kW kW kW

1738 590 684 64 0 358 275 42

1372 443 585 53 0 265 200 27

986 295 457 43 0 183 134 8

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9)

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC276

page 1 of 2

DM5108-00

®

G3512 TA

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 35 40 45 50 55 60 0.62/14 0.62/15 0.62/16 0.62/17 0.90/14 0.90/15 0.90/16

65 1.0/16

70 1.0/18

75 1.0/20

80 1.0/23

83 to 100 1.0/23

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

1.00 0.98 0.95 0.93 0.90 0.87 1.00 1.00 0.97 0.94 0.91 0.88 1.00 1.00 0.98 0.95 0.93 0.90 1.00 1.00 1.00 0.97 0.94 0.91 1.00 1.00 1.00 0.99 0.96 0.93 1.00 1.00 1.00 1.00 0.97 0.94 1.00 1.00 1.00 1.00 0.99 0.96 1.00 1.00 1.00 1.00 1.00 0.98 1.00 1.00 1.00 1.00 1.00 0.99 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.84 0.86 0.87 0.88 0.90 0.91 0.93 0.95 0.96 2250

0.82 0.83 0.84 0.86 0.87 0.89 0.90 0.92 0.93 2500

0.79 0.80 0.82 0.83 0.84 0.86 0.87 0.89 0.90 2750

0.77 0.78 0.79 0.80 0.82 0.83 0.85 0.86 0.88 3000

1.61 1.68 1.76 1.84 1.85 1.85 1.50 1.57 1.65 1.73 1.74 1.74 1.39 1.47 1.54 1.62 1.62 1.62 1.28 1.36 1.43 1.51 1.51 1.51 1.18 1.25 1.32 1.40 1.40 1.40 1.07 1.14 1.21 1.28 1.29 1.29 1.00 1.03 1.10 1.17 1.18 1.18 1.00 1.00 1.00 1.06 1.07 1.07 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.85 1.74 1.62 1.51 1.40 1.29 1.18 1.07 1.00 2250

1.85 1.74 1.62 1.51 1.40 1.29 1.18 1.07 1.00 2500

1.85 1.74 1.62 1.51 1.40 1.29 1.18 1.07 1.00 2750

1.85 1.74 1.62 1.51 1.40 1.29 1.18 1.07 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.38 1.28 1.18 1.07 1.00 1.00 1.00 1.00 1.00 0

1.46 1.35 1.25 1.14 1.04 1.00 1.00 1.00 1.00 250

1.53 1.43 1.32 1.21 1.11 1.00 1.00 1.00 1.00 500

DM5108-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5108-00

-METRIC-

page 2 of 2

277

®

G3512

G3512 TA

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 9.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type CATALYST

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

NAT GAS 36.2 LPG IMPCO 10 80 1524

100%

75%

50%

590 555

443 416

295 278

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

11.07 2.92 3.78 204 126 178 60 22.5 478 3.21 4.01

11.68 3.1 4 187 113 147 58 22.5 447 3.4 4.25

12.72 3.36 4.34 145 78 110 58 22.5 421 3.69 4.61

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

14.2 758 4186

13.3 671 3704

12.8 595 3284

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

16.7 1465 4933

19.0 1470 4952

20.3 1451 4885

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.9 444 845

3.4 500 953

4.8 647 1233

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.43 20 127

0.52 22 143

0.72 28 185

%

0.3 0.99

0.3 0.99

0.3 0.99

kW kW kW kW kW kW kW kW

1813 590 752 64 0 360 274 46

1435 443 640 53 0 268 198 31

1042 295 509 43 0 186 132 10

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9)

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC278

page 1 of 2

DM5109-00

®

G3512 TA

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 35 40 45 50 55 60 0.62/14 0.62/15 0.62/16 0.62/17 0.90/14 0.90/15 0.90/16

65 1.0/16

70 1.0/18

75 1.0/20

80 1.0/23

83 to 100 1.0/23

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

1.00 0.98 0.95 0.93 0.90 0.87 1.00 1.00 0.97 0.94 0.91 0.88 1.00 1.00 0.98 0.95 0.93 0.90 1.00 1.00 1.00 0.97 0.94 0.91 1.00 1.00 1.00 0.99 0.96 0.93 1.00 1.00 1.00 1.00 0.97 0.94 1.00 1.00 1.00 1.00 0.99 0.96 1.00 1.00 1.00 1.00 1.00 0.98 1.00 1.00 1.00 1.00 1.00 0.99 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.84 0.86 0.87 0.88 0.90 0.91 0.93 0.95 0.96 2250

0.82 0.83 0.84 0.86 0.87 0.89 0.90 0.92 0.93 2500

0.79 0.80 0.82 0.83 0.84 0.86 0.87 0.89 0.90 2750

0.77 0.78 0.79 0.80 0.82 0.83 0.85 0.86 0.88 3000

1.56 1.63 1.70 1.77 1.78 1.78 1.46 1.53 1.60 1.67 1.68 1.68 1.36 1.43 1.50 1.57 1.58 1.58 1.26 1.33 1.40 1.47 1.47 1.47 1.16 1.23 1.30 1.37 1.37 1.37 1.07 1.13 1.20 1.26 1.27 1.27 1.00 1.03 1.10 1.16 1.17 1.17 1.00 1.00 1.00 1.06 1.07 1.07 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.78 1.68 1.58 1.47 1.37 1.27 1.17 1.07 1.00 2250

1.78 1.68 1.58 1.47 1.37 1.27 1.17 1.07 1.00 2500

1.78 1.68 1.58 1.47 1.37 1.27 1.17 1.07 1.00 2750

1.78 1.68 1.58 1.47 1.37 1.27 1.17 1.07 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.35 1.26 1.16 1.06 1.00 1.00 1.00 1.00 1.00 0

1.42 1.32 1.23 1.13 1.03 1.00 1.00 1.00 1.00 250

1.49 1.39 1.29 1.20 1.10 1.00 1.00 1.00 1.00 500

DM5109-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5109-00

-METRIC-

page 2 of 2

279

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 HPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

207 80 579

100%

75%

50%

607 570

455 428

304 285

10.22 4.51 5.83 247 154 214 59 22 388 4.84 6.05

10.37 4.34 5.61 205 122 165 56 22 394 4.67 5.83

11.89 4.37 5.65 162 88 118 56 22 390 4.71 5.88

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 153 844

3.5 189 1045

6.8 434 2393

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.6 238 801

2.6 248 833

2.8 250 842

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

8.7 1436 2736

8.0 1317 2509

7.8 1210 2306

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.31 106 411

1.21 92 377

1.17 79 346

%

8.8 1.67

8.2 1.55

7.3 1.46

kW kW kW kW kW kW kW kW

1722 607 492 64 0 461 304 98

1311 455 417 53 0 338 226 47

1002 304 414 43 0 225 150 16

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC280

page 1 of 2

DM0745-02

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/15

70 1.0/17

75 1.0/19

80 1.0/21

83 to 100 1.0/22

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.96 0.97 0.99 1.00 1.00 1.00 1.00 1.00 1.00 250

0.93 0.95 0.96 0.98 0.99 1.00 1.00 1.00 1.00 500

0.90 0.88 0.85 0.82 0.80 0.78 0.92 0.89 0.86 0.84 0.81 0.79 0.93 0.90 0.88 0.85 0.83 0.80 0.95 0.92 0.89 0.87 0.84 0.81 0.96 0.93 0.91 0.88 0.85 0.83 0.98 0.95 0.92 0.89 0.87 0.84 1.00 0.97 0.94 0.91 0.88 0.85 1.00 0.98 0.95 0.93 0.90 0.87 1.00 1.00 0.97 0.94 0.91 0.89 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.75 0.76 0.78 0.79 0.80 0.81 0.83 0.84 0.86 2250

0.73 0.74 0.75 0.76 0.78 0.79 0.80 0.82 0.83 2500

0.71 0.72 0.73 0.74 0.75 0.77 0.78 0.79 0.81 2750

0.68 0.69 0.71 0.72 0.73 0.74 0.75 0.77 0.78 3000

1.38 1.38 1.38 1.38 1.38 1.38 1.31 1.31 1.31 1.31 1.31 1.31 1.24 1.24 1.24 1.24 1.24 1.24 1.16 1.16 1.16 1.16 1.16 1.16 1.09 1.09 1.09 1.09 1.09 1.09 1.02 1.02 1.02 1.02 1.02 1.02 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.38 1.31 1.24 1.16 1.09 1.02 1.00 1.00 1.00 2250

1.38 1.31 1.24 1.16 1.09 1.02 1.00 1.00 1.00 2500

1.38 1.31 1.24 1.16 1.09 1.02 1.00 1.00 1.00 2750

1.38 1.31 1.24 1.16 1.09 1.02 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.27 1.19 1.12 1.05 1.00 1.00 1.00 1.00 1.00 0

1.32 1.24 1.17 1.10 1.03 1.00 1.00 1.00 1.00 250

1.37 1.29 1.22 1.15 1.07 1.00 1.00 1.00 1.00 500

DM0745-02 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM0745-02

-METRIC-

page 2 of 2

281

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 127 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 HPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

207 80 579

100%

75%

50%

607 570

455 428

304 285

10.21 4.28 5.53 243 154 216 63 20 409 4.59 5.74

10.47 4.31 5.58 204 127 165 62 20 420 4.64 5.8

11.23 4.33 5.6 154 85 115 64 20 422 4.67 5.84

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 157 866

3.3 186 1027

7.1 375 2072

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 257 865

2.8 254 854

2.9 251 846

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

5.8 988 1883

5.8 934 1780

5.5 842 1605

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.88 72 283

0.87 65 267

0.83 55 241

%

8.6 1.60

8.1 1.56

7.3 1.46

kW kW kW kW kW kW kW kW

1720 607 376 88 108 447 313 93

1323 455 306 73 88 347 246 53

946 304 259 59 75 234 167 16

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC282

page 1 of 2

DM5110-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/--

70 1.0/15

75 1.0/17

80 1.0/19

83 to 100 1.0/20

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.96 0.97 0.99 1.00 1.00 1.00 1.00 1.00 1.00 250

0.93 0.95 0.96 0.98 0.99 1.00 1.00 1.00 1.00 500

0.90 0.88 0.85 0.82 0.80 0.78 0.92 0.89 0.86 0.84 0.81 0.79 0.93 0.90 0.88 0.85 0.83 0.80 0.95 0.92 0.89 0.87 0.84 0.81 0.96 0.93 0.91 0.88 0.85 0.83 0.98 0.95 0.92 0.89 0.87 0.84 1.00 0.97 0.94 0.91 0.88 0.85 1.00 0.98 0.95 0.93 0.90 0.87 1.00 1.00 0.97 0.94 0.91 0.89 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.75 0.76 0.78 0.79 0.80 0.81 0.83 0.84 0.86 2250

0.73 0.74 0.75 0.76 0.78 0.79 0.80 0.82 0.83 2500

0.71 0.72 0.73 0.74 0.75 0.77 0.78 0.79 0.81 2750

0.68 0.69 0.71 0.72 0.73 0.74 0.75 0.77 0.78 3000

1.38 1.38 1.38 1.38 1.38 1.38 1.31 1.31 1.31 1.31 1.31 1.31 1.23 1.23 1.23 1.23 1.23 1.23 1.16 1.16 1.16 1.16 1.16 1.16 1.09 1.09 1.09 1.09 1.09 1.09 1.02 1.02 1.02 1.02 1.02 1.02 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.38 1.31 1.23 1.16 1.09 1.02 1.00 1.00 1.00 2250

1.38 1.31 1.23 1.16 1.09 1.02 1.00 1.00 1.00 2500

1.38 1.31 1.23 1.16 1.09 1.02 1.00 1.00 1.00 2750

1.38 1.31 1.23 1.16 1.09 1.02 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.26 1.19 1.12 1.05 1.00 1.00 1.00 1.00 1.00 0

1.31 1.24 1.17 1.10 1.02 1.00 1.00 1.00 1.00 250

1.36 1.29 1.22 1.15 1.07 1.00 1.00 1.00 1.00 500

DM5110-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5110-00

-METRIC-

page 2 of 2

283

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 LPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

10 80 275

100%

75%

50%

607 570

455 428

304 285

10.22 4.51 5.83 247 157 214 59 22 388 4.84 6.05

10.37 4.34 5.61 205 123 165 56 22 394 4.67 5.83

11.89 4.37 5.65 162 88 118 56 22 390 4.71 5.88

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 153 844

3.5 189 1045

6.8 434 2393

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.6 238 801

2.6 248 833

2.8 250 842

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

8.7 1436 2736

8.0 1317 2509

7.8 1210 2306

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.31 106 411

1.21 92 377

1.17 79 346

%

8.8 1.67

8.2 1.55

7.3 1.46

kW kW kW kW kW kW kW kW

1722 607 485 64 0 461 304 104

1311 455 414 53 0 339 226 50

1002 304 413 43 0 225 150 17

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC284

page 1 of 2

DM5112-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/15

70 1.0/17

75 1.0/19

80 1.0/21

83 to 100 1.0/22

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 0

0.93 0.94 0.95 0.97 0.99 1.00 1.00 1.00 1.00 250

0.90 0.91 0.93 0.94 0.96 0.97 0.99 1.00 1.00 500

0.87 0.85 0.82 0.80 0.77 0.75 0.89 0.86 0.83 0.81 0.78 0.76 0.90 0.87 0.85 0.82 0.80 0.77 0.91 0.89 0.86 0.83 0.81 0.78 0.93 0.90 0.87 0.85 0.82 0.80 0.94 0.92 0.89 0.86 0.84 0.81 0.96 0.93 0.90 0.88 0.85 0.82 0.98 0.95 0.92 0.89 0.87 0.84 0.99 0.96 0.94 0.91 0.88 0.85 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.72 0.74 0.75 0.76 0.77 0.79 0.80 0.81 0.83 2250

0.70 0.71 0.72 0.74 0.75 0.76 0.77 0.79 0.80 2500

0.68 0.69 0.70 0.71 0.73 0.74 0.75 0.76 0.78 2750

0.66 0.67 0.68 0.69 0.70 0.71 0.73 0.74 0.75 3000

1.31 1.31 1.31 1.31 1.31 1.31 1.24 1.24 1.24 1.24 1.24 1.24 1.17 1.17 1.17 1.17 1.17 1.17 1.10 1.10 1.10 1.10 1.10 1.10 1.03 1.03 1.03 1.03 1.03 1.03 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.31 1.24 1.17 1.10 1.03 1.00 1.00 1.00 1.00 2250

1.31 1.24 1.17 1.10 1.03 1.00 1.00 1.00 1.00 2500

1.31 1.24 1.17 1.10 1.03 1.00 1.00 1.00 1.00 2750

1.31 1.24 1.17 1.10 1.03 1.00 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.26 1.19 1.12 1.05 1.00 1.00 1.00 1.00 1.00 0

1.31 1.24 1.17 1.10 1.02 1.00 1.00 1.00 1.00 250

1.31 1.24 1.17 1.10 1.03 1.00 1.00 1.00 1.00 500

DM5112-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5112-00

-METRIC-

page 2 of 2

285

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 127 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 LPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

10 80 275

100%

75%

50%

607 570

455 428

304 285

10.21 4.28 5.53 243 157 216 63 20 409 4.59 5.74

10.47 4.31 5.58 204 128 165 62 20 420 4.64 5.8

11.23 4.33 5.6 154 85 115 64 20 422 4.67 5.84

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 157 866

3.3 186 1027

7.1 375 2072

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 257 865

2.8 254 854

2.9 251 846

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

5.8 988 1883

5.8 934 1780

5.5 842 1605

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.88 72 283

0.87 65 267

0.83 55 241

%

8.6 1.60

8.1 1.56

7.3 1.46

kW kW kW kW kW kW kW kW

1720 607 371 88 107 447 313 100

1323 455 304 73 88 347 246 55

946 304 259 59 75 234 167 16

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC286

page 1 of 2

DM5111-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/--

70 1.0/15

75 1.0/17

80 1.0/19

83 to 100 1.0/20

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 0

0.93 0.94 0.95 0.97 0.99 1.00 1.00 1.00 1.00 250

0.90 0.91 0.93 0.94 0.96 0.97 0.99 1.00 1.00 500

0.87 0.85 0.82 0.80 0.77 0.75 0.89 0.86 0.83 0.81 0.78 0.76 0.90 0.87 0.85 0.82 0.80 0.77 0.91 0.89 0.86 0.83 0.81 0.78 0.93 0.90 0.87 0.85 0.82 0.80 0.94 0.92 0.89 0.86 0.84 0.81 0.96 0.93 0.90 0.88 0.85 0.82 0.98 0.95 0.92 0.89 0.87 0.84 0.99 0.96 0.94 0.91 0.88 0.85 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.72 0.74 0.75 0.76 0.77 0.79 0.80 0.81 0.83 2250

0.70 0.71 0.72 0.74 0.75 0.76 0.77 0.79 0.80 2500

0.68 0.69 0.70 0.71 0.73 0.74 0.75 0.76 0.78 2750

0.66 0.67 0.68 0.69 0.70 0.71 0.73 0.74 0.75 3000

1.31 1.31 1.31 1.31 1.31 1.31 1.24 1.24 1.24 1.24 1.24 1.24 1.17 1.17 1.17 1.17 1.17 1.17 1.10 1.10 1.10 1.10 1.10 1.10 1.03 1.03 1.03 1.03 1.03 1.03 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.31 1.24 1.17 1.10 1.03 1.00 1.00 1.00 1.00 2250

1.31 1.24 1.17 1.10 1.03 1.00 1.00 1.00 1.00 2500

1.31 1.24 1.17 1.10 1.03 1.00 1.00 1.00 1.00 2750

1.31 1.24 1.17 1.10 1.03 1.00 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.25 1.18 1.11 1.05 1.00 1.00 1.00 1.00 1.00 0

1.30 1.23 1.16 1.09 1.02 1.00 1.00 1.00 1.00 250

1.31 1.24 1.17 1.10 1.03 1.00 1.00 1.00 1.00 500

DM5111-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5111-00

-METRIC-

page 2 of 2

287

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 8.0:1 Aftercooler Inlet Temperature (°C) 32 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 HPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

242 80 1098

100%

75%

50%

642 600

482 450

321 300

10.48 4.4 5.68 243 158 216 45 35 426 4.72 5.91

10.75 4.28 5.53 216 136 165 44 35 421 4.61 5.76

11.44 4.28 5.53 157 93 114 43 35 421 4.62 5.77

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 155 852

5.5 304 1675

10.1 522 2882

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.0 185 623

2.1 189 636

2.2 191 642

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

4.0 653 1243

3.8 607 1157

3.7 560 1067

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.60 47 187

0.57 41 174

0.56 35 161

%

8.3 1.57

7.7 1.49

6.7 1.40

kW kW kW kW kW kW kW kW

1868 642 543 64 0 494 361 125

1437 482 469 53 0 357 261 76

1020 321 386 43 0 239 175 31

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC288

page 1 of 2

DM5169-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 35 40 0.90/21 0.90/23 0.90/24

45 1.0/25

50 1.0/26

55 1.0/28

60 1.0/29

65 1.0/30

70 1.0/32

75 1.0/33

80 1.0/34

83 to 100 1.0/35

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

0.96 0.93 0.91 0.88 0.85 0.83 0.98 0.95 0.92 0.89 0.87 0.84 0.99 0.96 0.93 0.91 0.88 0.85 1.00 0.98 0.95 0.92 0.89 0.87 1.00 1.00 0.97 0.94 0.91 0.88 1.00 1.00 0.98 0.95 0.92 0.90 1.00 1.00 1.00 0.97 0.94 0.91 1.00 1.00 1.00 0.99 0.96 0.93 1.00 1.00 1.00 1.00 0.97 0.94 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.80 0.81 0.83 0.84 0.85 0.87 0.88 0.90 0.91 2250

0.78 0.79 0.80 0.81 0.83 0.84 0.86 0.87 0.89 2500

0.75 0.76 0.78 0.79 0.80 0.81 0.83 0.84 0.86 2750

0.73 0.74 0.75 0.76 0.78 0.79 0.80 0.82 0.83 3000

1.34 1.38 1.40 1.40 1.40 1.40 1.28 1.32 1.34 1.34 1.34 1.34 1.22 1.26 1.28 1.28 1.28 1.28 1.16 1.20 1.22 1.22 1.22 1.22 1.10 1.14 1.16 1.16 1.16 1.16 1.04 1.08 1.10 1.10 1.10 1.10 1.00 1.02 1.04 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.40 1.34 1.28 1.22 1.16 1.10 1.04 1.00 1.00 2250

1.40 1.34 1.28 1.22 1.16 1.10 1.04 1.00 1.00 2500

1.40 1.34 1.28 1.22 1.16 1.10 1.04 1.00 1.00 2750

1.40 1.34 1.28 1.22 1.16 1.10 1.04 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.21 1.15 1.09 1.04 1.00 1.00 1.00 1.00 1.00 0

1.25 1.19 1.14 1.08 1.02 1.00 1.00 1.00 1.00 250

1.30 1.24 1.18 1.12 1.06 1.00 1.00 1.00 1.00 500

DM5169-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5169-00

-METRIC-

page 2 of 2

289

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°C) 32 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 HPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

207 80 579

100%

75%

50%

642 600

482 450

321 300

9.9 4.32 5.59 239 146 211 43 24 382 4.64 5.8

11.33 4.25 5.49 205 121 161 41 24 388 4.58 5.73

11.94 4.3 5.55 156 80 115 41 24 389 4.64 5.81

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 159 877

3.6 210 1155

5.5 326 1796

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.2 208 700

2.4 230 773

2.6 233 784

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

7.3 1248 1981

6.5 1109 1761

6.6 1073 1704

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.10 91 298

0.98 78 265

1.00 72 256

%

8.7 1.65

8.3 1.41

7.6 1.33

kW kW kW kW kW kW kW kW

1764 642 493 64 0 453 301 111

1514 482 574 53 0 341 231 65

1064 321 444 43 0 233 157 25

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC290

page 1 of 2

DM5173-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 1.0/15

65 1.0/17

70 1.0/19

75 1.0/21

80 1.0/23

83 to 100 1.0/24

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.96 0.97 0.99 1.00 1.00 1.00 1.00 1.00 1.00 250

0.93 0.95 0.96 0.98 0.99 1.00 1.00 1.00 1.00 500

0.90 0.88 0.85 0.82 0.80 0.78 0.92 0.89 0.86 0.84 0.81 0.79 0.93 0.90 0.88 0.85 0.83 0.80 0.95 0.92 0.89 0.87 0.84 0.81 0.96 0.93 0.91 0.88 0.85 0.83 0.98 0.95 0.92 0.89 0.87 0.84 1.00 0.97 0.94 0.91 0.88 0.85 1.00 0.98 0.95 0.93 0.90 0.87 1.00 1.00 0.97 0.94 0.91 0.89 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.75 0.76 0.78 0.79 0.80 0.81 0.83 0.84 0.86 2250

0.73 0.74 0.75 0.76 0.78 0.79 0.80 0.82 0.83 2500

0.71 0.72 0.73 0.74 0.75 0.77 0.78 0.79 0.81 2750

0.68 0.69 0.71 0.72 0.73 0.74 0.75 0.77 0.78 3000

1.33 1.33 1.33 1.33 1.33 1.33 1.27 1.27 1.27 1.27 1.27 1.27 1.21 1.21 1.21 1.21 1.21 1.21 1.14 1.14 1.14 1.14 1.14 1.14 1.08 1.08 1.08 1.08 1.08 1.08 1.01 1.01 1.01 1.01 1.01 1.01 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.33 1.27 1.21 1.14 1.08 1.01 1.00 1.00 1.00 2250

1.33 1.27 1.21 1.14 1.08 1.01 1.00 1.00 1.00 2500

1.33 1.27 1.21 1.14 1.08 1.01 1.00 1.00 1.00 2750

1.33 1.27 1.21 1.14 1.08 1.01 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.23 1.17 1.11 1.05 1.00 1.00 1.00 1.00 1.00 0

1.28 1.21 1.15 1.09 1.02 1.00 1.00 1.00 1.00 250

1.32 1.26 1.19 1.13 1.06 1.00 1.00 1.00 1.00 500

DM5173-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5173-00

-METRIC-

page 2 of 2

291

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°C) 32 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 LPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

10 80 275

100%

75%

50%

642 600

482 450

321 300

9.9 4.32 5.59 239 146 211 43 24 382 4.64 5.8

11.33 4.25 5.49 205 121 161 41 24 388 4.58 5.73

11.94 4.3 5.55 156 80 115 41 24 389 4.64 5.81

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 159 877

3.6 210 1155

5.5 326 1796

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.2 208 700

2.4 230 773

2.6 233 784

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

7.3 1248 2377

6.5 1109 2113

6.6 1073 2044

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.10 91 357

0.98 78 317

1.00 72 307

%

8.7 1.65

8.3 1.41

7.6 1.33

kW kW kW kW kW kW kW kW

1764 642 489 64 0 453 301 115

1514 482 571 53 0 341 231 68

1064 321 443 43 0 233 157 26

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC292

page 1 of 2

DM5115-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 1.0/15

65 1.0/17

70 1.0/19

75 1.0/21

80 1.0/23

83 to 100 1.0/24

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 0

0.93 0.94 0.95 0.97 0.99 1.00 1.00 1.00 1.00 250

0.90 0.91 0.93 0.94 0.96 0.97 0.99 1.00 1.00 500

0.87 0.85 0.82 0.80 0.77 0.75 0.89 0.86 0.83 0.81 0.78 0.76 0.90 0.87 0.85 0.82 0.80 0.77 0.91 0.89 0.86 0.83 0.81 0.78 0.93 0.90 0.87 0.85 0.82 0.80 0.94 0.92 0.89 0.86 0.84 0.81 0.96 0.93 0.90 0.88 0.85 0.82 0.98 0.95 0.92 0.89 0.87 0.84 0.99 0.96 0.94 0.91 0.88 0.85 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.72 0.74 0.75 0.76 0.77 0.79 0.80 0.81 0.83 2250

0.70 0.71 0.72 0.74 0.75 0.76 0.77 0.79 0.80 2500

0.68 0.69 0.70 0.71 0.73 0.74 0.75 0.76 0.78 2750

0.66 0.67 0.68 0.69 0.70 0.71 0.73 0.74 0.75 3000

1.28 1.28 1.28 1.28 1.28 1.28 1.22 1.22 1.22 1.22 1.22 1.22 1.15 1.15 1.15 1.15 1.15 1.15 1.09 1.09 1.09 1.09 1.09 1.09 1.03 1.03 1.03 1.03 1.03 1.03 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.28 1.22 1.15 1.09 1.03 1.00 1.00 1.00 1.00 2250

1.28 1.22 1.15 1.09 1.03 1.00 1.00 1.00 1.00 2500

1.28 1.22 1.15 1.09 1.03 1.00 1.00 1.00 1.00 2750

1.28 1.22 1.15 1.09 1.03 1.00 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.23 1.17 1.11 1.05 1.00 1.00 1.00 1.00 1.00 0

1.28 1.21 1.15 1.09 1.02 1.00 1.00 1.00 1.00 250

1.28 1.22 1.15 1.09 1.03 1.00 1.00 1.00 1.00 500

DM5115-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5115-00

-METRIC-

page 2 of 2

293

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 8.0:1 Aftercooler Inlet Temperature (°C) 32 Jacket Water Outlet Temperature (°C) 127 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 HPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

241 80 1098

100%

75%

50%

642 600

482 450

321 300

10.48 4.37 5.65 247 160 219 49 33 445 4.7 5.88

10.68 4.18 5.41 216 139 165 49 33 440 4.51 5.63

11.45 4.25 5.49 160 90 115 50 33 436 4.57 5.71

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 152 835

8.4 464 2563

14.4 720 3978

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.1 191 641

2.2 199 669

2.8 232 780

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

3.6 579 1103

3.2 514 980

3.1 453 862

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.54 41 166

0.48 34 147

0.47 28 130

%

8.1 1.56

7.3 1.47

6.1 1.52

kW kW kW kW kW kW kW kW

1869 642 389 88 112 512 383 126

1428 482 336 73 97 364 272 77

1020 321 286 59 83 243 181 29

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC294

page 1 of 2

DM5113-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30

35

40 0.90/19 0.90/21 0.90/22

45 1.0/23

50 1.0/24

55 1.0/26

60 1.0/27

65 1.0/28

70 1.0/30

75 1.0/31

80 1.0/32

83 to 100 1.0/33

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

0.96 0.93 0.91 0.88 0.85 0.83 0.98 0.95 0.92 0.89 0.87 0.84 0.99 0.96 0.93 0.91 0.88 0.85 1.00 0.98 0.95 0.92 0.89 0.87 1.00 1.00 0.97 0.94 0.91 0.88 1.00 1.00 0.98 0.95 0.92 0.90 1.00 1.00 1.00 0.97 0.94 0.91 1.00 1.00 1.00 0.99 0.96 0.93 1.00 1.00 1.00 1.00 0.97 0.94 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.80 0.81 0.83 0.84 0.85 0.87 0.88 0.90 0.91 2250

0.78 0.79 0.80 0.81 0.83 0.84 0.86 0.87 0.89 2500

0.75 0.76 0.78 0.79 0.80 0.81 0.83 0.84 0.86 2750

0.73 0.74 0.75 0.76 0.78 0.79 0.80 0.82 0.83 3000

1.34 1.38 1.40 1.40 1.40 1.40 1.28 1.32 1.34 1.34 1.34 1.34 1.22 1.26 1.28 1.28 1.28 1.28 1.16 1.20 1.22 1.22 1.22 1.22 1.10 1.14 1.16 1.16 1.16 1.16 1.04 1.08 1.10 1.10 1.10 1.10 1.00 1.02 1.04 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.40 1.34 1.28 1.22 1.16 1.10 1.04 1.00 1.00 2250

1.40 1.34 1.28 1.22 1.16 1.10 1.04 1.00 1.00 2500

1.40 1.34 1.28 1.22 1.16 1.10 1.04 1.00 1.00 2750

1.40 1.34 1.28 1.22 1.16 1.10 1.04 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.21 1.15 1.09 1.04 1.00 1.00 1.00 1.00 1.00 0

1.25 1.19 1.13 1.08 1.02 1.00 1.00 1.00 1.00 250

1.29 1.23 1.18 1.12 1.06 1.00 1.00 1.00 1.00 500

DM5113-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5113-00

-METRIC-

page 2 of 2

295

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°C) 32 Jacket Water Outlet Temperature (°C) 127 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 HPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

207 80 579

100%

75%

50%

642 600

482 450

321 300

9.85 4.26 5.5 254 160 216 45 22 400 4.57 5.71

10.17 4.2 5.42 208 129 164 46 22 416 4.51 5.64

10.92 4.22 5.45 152 87 114 47 22 418 4.54 5.68

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 157 863

4.3 250 1378

9.2 523 2890

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.9 276 928

2.8 260 876

2.8 268 901

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

5.9 998 1901

5.5 910 1733

5.5 911 1736

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.89 72 286

0.82 63 260

0.83 63 261

%

8.5 1.62

8.1 1.55

8.1 1.45

kW kW kW kW kW kW kW kW

1755 642 343 88 99 459 318 124

1360 482 296 73 85 353 250 71

973 321 253 59 73 239 170 27

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC296

page 1 of 2

DM5114-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/15

70 1.0/17

75 1.0/19

80 1.0/21

83 to 100 1.0/22

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.96 0.97 0.99 1.00 1.00 1.00 1.00 1.00 1.00 250

0.93 0.95 0.96 0.98 0.99 1.00 1.00 1.00 1.00 500

0.90 0.88 0.85 0.82 0.80 0.78 0.92 0.89 0.86 0.84 0.81 0.79 0.93 0.90 0.88 0.85 0.83 0.80 0.95 0.92 0.89 0.87 0.84 0.81 0.96 0.93 0.91 0.88 0.85 0.83 0.98 0.95 0.92 0.89 0.87 0.84 1.00 0.97 0.94 0.91 0.88 0.85 1.00 0.98 0.95 0.93 0.90 0.87 1.00 1.00 0.97 0.94 0.91 0.89 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.75 0.76 0.78 0.79 0.80 0.81 0.83 0.84 0.86 2250

0.73 0.74 0.75 0.76 0.78 0.79 0.80 0.82 0.83 2500

0.71 0.72 0.73 0.74 0.75 0.77 0.78 0.79 0.81 2750

0.68 0.69 0.71 0.72 0.73 0.74 0.75 0.77 0.78 3000

1.30 1.30 1.30 1.30 1.30 1.30 1.24 1.24 1.24 1.24 1.24 1.24 1.19 1.19 1.19 1.19 1.19 1.19 1.13 1.13 1.13 1.13 1.13 1.13 1.07 1.07 1.07 1.07 1.07 1.07 1.01 1.01 1.01 1.01 1.01 1.01 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.30 1.24 1.19 1.13 1.07 1.01 1.00 1.00 1.00 2250

1.30 1.24 1.19 1.13 1.07 1.01 1.00 1.00 1.00 2500

1.30 1.24 1.19 1.13 1.07 1.01 1.00 1.00 1.00 2750

1.30 1.24 1.19 1.13 1.07 1.01 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.21 1.15 1.10 1.04 1.00 1.00 1.00 1.00 1.00 0

1.25 1.19 1.13 1.08 1.02 1.00 1.00 1.00 1.00 250

1.29 1.23 1.17 1.12 1.06 1.00 1.00 1.00 1.00 500

DM5114-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5114-00

-METRIC-

page 2 of 2

297

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°C) 32 Jacket Water Outlet Temperature (°C) 127 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 LPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

10 80 275

100%

75%

50%

642 600

482 450

321 300

9.85 4.26 5.5 254 164 216 45 22 400 4.57 5.71

10.17 4.2 5.42 208 131 164 46 22 416 4.51 5.64

10.92 4.22 5.45 152 87 114 47 22 418 4.54 5.68

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 157 863

4.3 250 1378

9.2 523 2890

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.9 276 928

2.8 260 876

2.8 268 901

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

5.9 998 1901

5.5 910 1733

5.5 911 1736

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.89 72 286

0.82 63 260

0.83 63 261

%

8.5 1.62

8.1 1.55

8.1 1.45

kW kW kW kW kW kW kW kW

1755 642 336 88 97 459 318 133

1360 482 292 73 84 353 250 75

973 321 252 59 73 239 170 28

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC298

page 1 of 2

DM5116-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/15

70 1.0/17

75 1.0/19

80 1.0/21

83 to 100 1.0/22

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 0

0.93 0.94 0.95 0.97 0.99 1.00 1.00 1.00 1.00 250

0.90 0.91 0.93 0.94 0.96 0.97 0.99 1.00 1.00 500

0.87 0.85 0.82 0.80 0.77 0.75 0.89 0.86 0.83 0.81 0.78 0.76 0.90 0.87 0.85 0.82 0.80 0.77 0.91 0.89 0.86 0.83 0.81 0.78 0.93 0.90 0.87 0.85 0.82 0.80 0.94 0.92 0.89 0.86 0.84 0.81 0.96 0.93 0.90 0.88 0.85 0.82 0.98 0.95 0.92 0.89 0.87 0.84 0.99 0.96 0.94 0.91 0.88 0.85 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.72 0.74 0.75 0.76 0.77 0.79 0.80 0.81 0.83 2250

0.70 0.71 0.72 0.74 0.75 0.76 0.77 0.79 0.80 2500

0.68 0.69 0.70 0.71 0.73 0.74 0.75 0.76 0.78 2750

0.66 0.67 0.68 0.69 0.70 0.71 0.73 0.74 0.75 3000

1.25 1.25 1.25 1.25 1.25 1.25 1.19 1.19 1.19 1.19 1.19 1.19 1.13 1.13 1.13 1.13 1.13 1.13 1.08 1.08 1.08 1.08 1.08 1.08 1.02 1.02 1.02 1.02 1.02 1.02 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.25 1.19 1.13 1.08 1.02 1.00 1.00 1.00 1.00 2250

1.25 1.19 1.13 1.08 1.02 1.00 1.00 1.00 1.00 2500

1.25 1.19 1.13 1.08 1.02 1.00 1.00 1.00 1.00 2750

1.25 1.19 1.13 1.08 1.02 1.00 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.20 1.15 1.09 1.04 1.00 1.00 1.00 1.00 1.00 0

1.24 1.19 1.13 1.07 1.02 1.00 1.00 1.00 1.00 250

1.25 1.19 1.13 1.08 1.02 1.00 1.00 1.00 1.00 500

DM5116-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5116-00

-METRIC-

page 2 of 2

299

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 8.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 HPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

241 80 1524

100%

75%

50%

758 725

569 544

379 363

10.77 4.55 5.88 266 163 229 59 33 468 4.88 6.11

10.95 4.39 5.67 233 145 168 56 33 465 4.72 5.9

11.69 4.58 5.91 170 100 120 53 33 465 4.92 6.16

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 143 789

5.2 268 1479

5.5 264 1457

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.5 215 722

2.9 248 835

3.1 245 823

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

3.7 576 1097

3.1 462 879

3.5 486 925

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.56 40 165

0.47 30 132

0.52 31 139

%

8.0 1.61

7.1 1.52

6.8 1.49

kW kW kW kW kW kW kW kW

2266 758 633 80 0 661 503 134

1728 569 538 67 0 479 362 81

1230 379 437 53 0 331 253 29

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC300

page 1 of 2

DM5171-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0.90/19

35 0.90/21

40 0.90/22

45 1.0/23

50 1.0/24

55 1.0/26

60 1.0/27

65 1.0/28

70 1.0/30

75 1.0/31

80 to 100 1.0/33

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

1.00 0.98 0.95 0.93 0.90 0.87 1.00 1.00 0.97 0.94 0.91 0.88 1.00 1.00 0.98 0.95 0.93 0.90 1.00 1.00 1.00 0.97 0.94 0.91 1.00 1.00 1.00 0.99 0.96 0.93 1.00 1.00 1.00 1.00 0.97 0.94 1.00 1.00 1.00 1.00 0.99 0.96 1.00 1.00 1.00 1.00 1.00 0.98 1.00 1.00 1.00 1.00 1.00 0.99 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.84 0.86 0.87 0.88 0.90 0.91 0.93 0.95 0.96 2250

0.82 0.83 0.84 0.86 0.87 0.89 0.90 0.92 0.93 2500

0.79 0.80 0.82 0.83 0.84 0.86 0.87 0.89 0.90 2750

0.77 0.78 0.79 0.80 0.82 0.83 0.85 0.86 0.88 3000

1.39 1.44 1.48 1.53 1.54 1.54 1.32 1.37 1.41 1.46 1.47 1.47 1.25 1.30 1.34 1.39 1.40 1.40 1.18 1.23 1.27 1.32 1.33 1.33 1.11 1.16 1.20 1.25 1.25 1.25 1.04 1.09 1.13 1.18 1.18 1.18 1.00 1.02 1.06 1.11 1.11 1.11 1.00 1.00 1.00 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.54 1.47 1.40 1.33 1.25 1.18 1.11 1.04 1.00 2250

1.54 1.47 1.40 1.33 1.25 1.18 1.11 1.04 1.00 2500

1.54 1.47 1.40 1.33 1.25 1.18 1.11 1.04 1.00 2750

1.54 1.47 1.40 1.33 1.25 1.18 1.11 1.04 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.25 1.18 1.11 1.05 1.00 1.00 1.00 1.00 1.00 0

1.29 1.23 1.16 1.09 1.03 1.00 1.00 1.00 1.00 250

1.34 1.27 1.20 1.14 1.07 1.00 1.00 1.00 1.00 500

DM5171-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5171-00

-METRIC-

page 2 of 2

301

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 8.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 127 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 HPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

241 80 1524

100%

75%

50%

758 725

569 544

379 363

10.86 4.58 5.92 266 162 234 62 33 481 4.92 6.15

11.05 4.41 5.7 234 145 170 58 33 475 4.74 5.93

11.68 4.59 5.93 170 99 121 55 33 472 4.94 6.18

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 142 784

5.0 258 1424

5.3 257 1420

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.5 217 730

3.0 251 843

3.1 246 828

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

3.2 490 933

2.8 410 781

3.2 450 856

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.48 34 140

0.42 27 118

0.49 29 129

%

8.0 1.62

7.1 1.53

6.8 1.49

kW kW kW kW kW kW kW kW

2285 758 473 104 136 681 526 133

1744 569 405 87 117 485 375 82

1229 379 322 69 93 336 258 29

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC302

page 1 of 2

DM5122-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0.90/19

35 0.90/21

40 0.90/22

45 1.0/23

50 1.0/24

55 1.0/26

60 1.0/27

65 1.0/28

70 1.0/30

75 1.0/31

80 to 100 1.0/33

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

1.00 0.98 0.95 0.93 0.90 0.87 1.00 1.00 0.97 0.94 0.91 0.88 1.00 1.00 0.98 0.95 0.93 0.90 1.00 1.00 1.00 0.97 0.94 0.91 1.00 1.00 1.00 0.99 0.96 0.93 1.00 1.00 1.00 1.00 0.97 0.94 1.00 1.00 1.00 1.00 0.99 0.96 1.00 1.00 1.00 1.00 1.00 0.98 1.00 1.00 1.00 1.00 1.00 0.99 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.84 0.86 0.87 0.88 0.90 0.91 0.93 0.95 0.96 2250

0.82 0.83 0.84 0.86 0.87 0.89 0.90 0.92 0.93 2500

0.79 0.80 0.82 0.83 0.84 0.86 0.87 0.89 0.90 2750

0.77 0.78 0.79 0.80 0.82 0.83 0.85 0.86 0.88 3000

1.39 1.44 1.49 1.54 1.55 1.55 1.32 1.37 1.42 1.47 1.47 1.47 1.25 1.30 1.35 1.40 1.40 1.40 1.18 1.23 1.28 1.32 1.33 1.33 1.11 1.16 1.21 1.25 1.26 1.26 1.04 1.09 1.13 1.18 1.19 1.19 1.00 1.02 1.06 1.11 1.11 1.11 1.00 1.00 1.00 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.55 1.47 1.40 1.33 1.26 1.19 1.11 1.04 1.00 2250

1.55 1.47 1.40 1.33 1.26 1.19 1.11 1.04 1.00 2500

1.55 1.47 1.40 1.33 1.26 1.19 1.11 1.04 1.00 2750

1.55 1.47 1.40 1.33 1.26 1.19 1.11 1.04 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.25 1.18 1.12 1.05 1.00 1.00 1.00 1.00 1.00 0

1.30 1.23 1.16 1.09 1.03 1.00 1.00 1.00 1.00 250

1.35 1.28 1.21 1.14 1.07 1.00 1.00 1.00 1.00 500

DM5122-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5122-00

-METRIC-

page 2 of 2

303

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 HPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

207 80 1311

100%

75%

50%

758 725

569 544

379 363

10.58 4.11 5.31 240 145 213 62 17 467 4.43 5.54

11.06 4.26 5.51 210 122 169 59 17 470 4.59 5.74

11.82 4.16 5.38 164 90 118 57 17 476 4.51 5.64

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 147 811

2.9 158 872

9.1 464 2560

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.6 240 807

2.6 237 797

3.1 256 860

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

4.9 795 1514

4.6 734 1398

3.3 486 926

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.75 53 228

0.70 49 210

0.51 29 139

%

7.5 1.46

7.5 1.43

5.6 1.26

kW kW kW kW kW kW kW kW

2227 758 675 80 0 613 457 101

1746 569 571 67 0 478 360 62

1244 379 475 53 0 315 242 21

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC304

page 1 of 2

DM5123-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/-

70 1.0/15

75 1.0/16

80 to 100 1.0/17

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

0.99 0.96 0.93 0.90 0.87 0.85 1.00 0.97 0.94 0.92 0.89 0.86 1.00 0.99 0.96 0.93 0.90 0.87 1.00 1.00 0.97 0.95 0.92 0.89 1.00 1.00 0.99 0.96 0.93 0.90 1.00 1.00 1.00 0.98 0.95 0.92 1.00 1.00 1.00 0.99 0.96 0.93 1.00 1.00 1.00 1.00 0.98 0.95 1.00 1.00 1.00 1.00 1.00 0.97 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.82 0.83 0.85 0.86 0.88 0.89 0.91 0.92 0.94 2250

0.80 0.81 0.82 0.83 0.85 0.86 0.88 0.89 0.91 2500

0.77 0.78 0.80 0.81 0.82 0.84 0.85 0.87 0.88 2750

0.75 0.76 0.77 0.78 0.80 0.81 0.82 0.84 0.85 3000

1.44 1.50 1.56 1.57 1.57 1.57 1.37 1.42 1.48 1.49 1.49 1.49 1.29 1.34 1.39 1.41 1.41 1.41 1.21 1.26 1.31 1.33 1.33 1.33 1.13 1.18 1.23 1.25 1.25 1.25 1.05 1.10 1.15 1.17 1.17 1.17 1.00 1.02 1.07 1.09 1.09 1.09 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.57 1.49 1.41 1.33 1.25 1.17 1.09 1.00 1.00 2250

1.57 1.49 1.41 1.33 1.25 1.17 1.09 1.00 1.00 2500

1.57 1.49 1.41 1.33 1.25 1.17 1.09 1.00 1.00 2750

1.57 1.49 1.41 1.33 1.25 1.17 1.09 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.28 1.21 1.13 1.06 1.00 1.00 1.00 1.00 1.00 0

1.34 1.26 1.18 1.11 1.03 1.00 1.00 1.00 1.00 250

1.39 1.31 1.23 1.16 1.08 1.00 1.00 1.00 1.00 500

DM5123-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5123-00

-METRIC-

page 2 of 2

305

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 127 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 HPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

207 80 1311

100%

75%

50%

758 725

569 544

379 363

10.72 4.18 5.4 242 145 215 66 17 476 4.49 5.62

10.98 4.33 5.6 212 122 170 63 17 480 4.66 5.83

11.73 4.23 5.47 165 90 118 61 17 486 4.58 5.73

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 148 817

2.9 159 878

9.1 466 2573

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 245 824

2.7 242 813

3.2 260 875

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

4.6 739 1407

4.3 682 1299

3.1 451 859

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.70 50 212

0.66 46 195

0.47 27 129

%

7.6 1.51

7.6 1.47

5.7 1.30

kW kW kW kW kW kW kW kW

2255 758 511 104 147 631 476 102

1734 569 405 87 117 493 375 63

1235 379 341 69 98 325 252 21

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC306

page 1 of 2

DM5121-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/-

70 1.0/15

75 1.0/16

80 to 100 1.0/17

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

0.99 0.96 0.93 0.90 0.87 0.85 1.00 0.97 0.94 0.92 0.89 0.86 1.00 0.99 0.96 0.93 0.90 0.87 1.00 1.00 0.97 0.95 0.92 0.89 1.00 1.00 0.99 0.96 0.93 0.90 1.00 1.00 1.00 0.98 0.95 0.92 1.00 1.00 1.00 0.99 0.96 0.93 1.00 1.00 1.00 1.00 0.98 0.95 1.00 1.00 1.00 1.00 1.00 0.97 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.82 0.83 0.85 0.86 0.88 0.89 0.91 0.92 0.94 2250

0.80 0.81 0.82 0.83 0.85 0.86 0.88 0.89 0.91 2500

0.77 0.78 0.80 0.81 0.82 0.84 0.85 0.87 0.88 2750

0.75 0.76 0.77 0.78 0.80 0.81 0.82 0.84 0.85 3000

1.44 1.50 1.55 1.57 1.57 1.57 1.37 1.42 1.47 1.49 1.49 1.49 1.29 1.34 1.39 1.41 1.41 1.41 1.21 1.26 1.31 1.33 1.33 1.33 1.13 1.18 1.23 1.25 1.25 1.25 1.05 1.10 1.15 1.16 1.16 1.16 1.00 1.02 1.07 1.08 1.08 1.08 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.57 1.49 1.41 1.33 1.25 1.16 1.08 1.00 1.00 2250

1.57 1.49 1.41 1.33 1.25 1.16 1.08 1.00 1.00 2500

1.57 1.49 1.41 1.33 1.25 1.16 1.08 1.00 1.00 2750

1.57 1.49 1.41 1.33 1.25 1.16 1.08 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.29 1.21 1.13 1.06 1.00 1.00 1.00 1.00 1.00 0

1.34 1.26 1.18 1.11 1.03 1.00 1.00 1.00 1.00 250

1.39 1.31 1.23 1.16 1.08 1.00 1.00 1.00 1.00 500

DM5121-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5121-00

-METRIC-

page 2 of 2

307

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 LPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

10 80 1006

100%

75%

50%

758 725

569 544

379 363

10.58 4.11 5.31 240 151 213 62 17 467 4.43 5.54

11.06 4.26 5.51 210 124 169 59 17 470 4.59 5.74

11.82 4.16 5.38 164 91 118 57 17 476 4.51 5.64

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 147 811

2.9 158 872

9.1 464 2560

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.6 240 807

2.6 237 797

3.1 256 860

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

4.9 795 1514

4.6 734 1398

3.3 486 926

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.75 53 228

0.70 49 210

0.51 29 139

%

7.5 1.46

7.5 1.43

5.6 1.26

kW kW kW kW kW kW kW kW

2227 758 664 80 0 613 457 112

1746 569 566 67 0 478 360 67

1244 379 474 53 0 315 242 22

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC308

page 1 of 2

DM5126-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/-

70 1.0/15

75 1.0/16

80 to 100 1.0/17

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

0.95 0.92 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.88 0.86 0.83 0.98 0.95 0.92 0.90 0.87 0.84 1.00 0.97 0.94 0.91 0.88 0.86 1.00 0.98 0.95 0.93 0.90 0.87 1.00 1.00 0.97 0.94 0.91 0.89 1.00 1.00 0.99 0.96 0.93 0.90 1.00 1.00 1.00 0.97 0.94 0.92 1.00 1.00 1.00 0.99 0.96 0.93 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.79 0.80 0.82 0.83 0.84 0.86 0.87 0.89 0.90 2250

0.77 0.78 0.79 0.80 0.82 0.83 0.85 0.86 0.88 2500

0.74 0.76 0.77 0.78 0.79 0.81 0.82 0.83 0.85 2750

0.72 0.73 0.74 0.76 0.77 0.78 0.79 0.81 0.82 3000

1.42 1.48 1.48 1.48 1.48 1.48 1.35 1.40 1.40 1.40 1.40 1.40 1.27 1.33 1.33 1.33 1.33 1.33 1.20 1.25 1.25 1.25 1.25 1.25 1.13 1.18 1.18 1.18 1.18 1.18 1.05 1.10 1.10 1.10 1.10 1.10 1.00 1.02 1.03 1.03 1.03 1.03 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.48 1.40 1.33 1.25 1.18 1.10 1.03 1.00 1.00 2250

1.48 1.40 1.33 1.25 1.18 1.10 1.03 1.00 1.00 2500

1.48 1.40 1.33 1.25 1.18 1.10 1.03 1.00 1.00 2750

1.48 1.40 1.33 1.25 1.18 1.10 1.03 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.27 1.19 1.12 1.05 1.00 1.00 1.00 1.00 1.00 0

1.32 1.25 1.17 1.10 1.03 1.00 1.00 1.00 1.00 250

1.37 1.30 1.22 1.15 1.07 1.00 1.00 1.00 1.00 500

DM5126-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5126-00

-METRIC-

page 2 of 2

309

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 127 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 LPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

207 80 1006

100%

75%

50%

758 725

569 544

379 363

10.72 4.18 5.4 242 150 215 66 17 476 4.49 5.62

10.98 4.33 5.6 212 126 170 63 17 480 4.66 5.83

11.73 4.23 5.47 165 93 118 61 17 486 4.58 5.73

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 148 817

2.9 159 878

9.1 466 2573

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 245 824

2.7 242 813

3.2 260 875

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

4.6 739 1407

4.3 682 1299

3.1 451 859

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.70 50 212

0.66 46 195

0.47 27 129

%

7.6 1.51

7.6 1.47

5.7 1.30

kW kW kW kW kW kW kW kW

2255 758 504 104 145 631 476 112

1734 569 400 87 115 493 375 70

1235 379 339 69 98 325 252 24

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC310

page 1 of 2

DM5125-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/--

70 1.0/15

75 1.0/16

80 to 100 1.0/17

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

0.95 0.92 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.88 0.86 0.83 0.98 0.95 0.92 0.90 0.87 0.84 1.00 0.97 0.94 0.91 0.88 0.86 1.00 0.98 0.95 0.93 0.90 0.87 1.00 1.00 0.97 0.94 0.91 0.89 1.00 1.00 0.99 0.96 0.93 0.90 1.00 1.00 1.00 0.97 0.94 0.92 1.00 1.00 1.00 0.99 0.96 0.93 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.79 0.80 0.82 0.83 0.84 0.86 0.87 0.89 0.90 2250

0.77 0.78 0.79 0.80 0.82 0.83 0.85 0.86 0.88 2500

0.74 0.76 0.77 0.78 0.79 0.81 0.82 0.83 0.85 2750

0.72 0.73 0.74 0.76 0.77 0.78 0.79 0.81 0.82 3000

1.43 1.48 1.48 1.48 1.48 1.48 1.35 1.41 1.41 1.41 1.41 1.41 1.28 1.33 1.33 1.33 1.33 1.33 1.20 1.25 1.25 1.25 1.25 1.25 1.13 1.18 1.18 1.18 1.18 1.18 1.05 1.10 1.10 1.10 1.10 1.10 1.00 1.02 1.02 1.02 1.02 1.02 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.48 1.41 1.33 1.25 1.18 1.10 1.02 1.00 1.00 2250

1.48 1.41 1.33 1.25 1.18 1.10 1.02 1.00 1.00 2500

1.48 1.41 1.33 1.25 1.18 1.10 1.02 1.00 1.00 2750

1.48 1.41 1.33 1.25 1.18 1.10 1.02 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.27 1.20 1.12 1.05 1.00 1.00 1.00 1.00 1.00 0

1.32 1.25 1.17 1.10 1.03 1.00 1.00 1.00 1.00 250

1.37 1.30 1.23 1.15 1.08 1.00 1.00 1.00 1.00 500

DM5125-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5125-00

-METRIC-

page 2 of 2

311

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 8.0:1 Aftercooler Inlet Temperature (°C) 32 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 HPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

241 80 1524

100%

75%

50%

803 765

602 574

402 383

10.56 4.44 5.74 268 165 228 44 35 465 4.77 5.96

10.66 4.3 5.55 237 149 171 40 35 459 4.62 5.78

11.43 4.38 5.66 173 102 119 34 35 463 4.72 5.9

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 145 797

4.1 221 1219

5.6 282 1555

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.4 212 713

2.7 241 809

2.9 242 814

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

3.6 570 1086

3.3 503 958

3.4 500 953

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.55 39 163

0.49 33 144

0.52 31 143

%

7.9 1.60

7.3 1.53

6.6 1.46

kW kW kW kW kW kW kW kW

2353 803 626 80 0 679 516 165

1783 602 520 67 0 487 369 107

1274 402 439 53 0 336 255 44

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC312

page 1 of 2

DM5170-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0.90/21

35 0.90/23

40 0.90/24

45 1.0/25

50 1.0/26

55 1.0/28

60 1.0/29

65 1.0/30

70 1.0/32

75 1.0/33

80 to 100 1.0/35

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

1.00 0.98 0.95 0.93 0.90 0.87 1.00 1.00 0.97 0.94 0.91 0.88 1.00 1.00 0.98 0.95 0.93 0.90 1.00 1.00 1.00 0.97 0.94 0.91 1.00 1.00 1.00 0.99 0.96 0.93 1.00 1.00 1.00 1.00 0.97 0.94 1.00 1.00 1.00 1.00 0.99 0.96 1.00 1.00 1.00 1.00 1.00 0.98 1.00 1.00 1.00 1.00 1.00 0.99 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.84 0.86 0.87 0.88 0.90 0.91 0.93 0.95 0.96 2250

0.82 0.83 0.84 0.86 0.87 0.89 0.90 0.92 0.93 2500

0.79 0.80 0.82 0.83 0.84 0.86 0.87 0.89 0.90 2750

0.77 0.78 0.79 0.80 0.82 0.83 0.85 0.86 0.88 3000

1.33 1.37 1.41 1.45 1.46 1.46 1.27 1.31 1.35 1.39 1.40 1.40 1.21 1.25 1.29 1.33 1.34 1.34 1.15 1.19 1.23 1.27 1.28 1.28 1.10 1.13 1.17 1.21 1.22 1.22 1.04 1.08 1.11 1.15 1.16 1.16 1.00 1.02 1.05 1.09 1.10 1.10 1.00 1.00 1.00 1.03 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.46 1.40 1.34 1.28 1.22 1.16 1.10 1.04 1.00 2250

1.46 1.40 1.34 1.28 1.22 1.16 1.10 1.04 1.00 2500

1.46 1.40 1.34 1.28 1.22 1.16 1.10 1.04 1.00 2750

1.46 1.40 1.34 1.28 1.22 1.16 1.10 1.04 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.21 1.15 1.10 1.04 1.00 1.00 1.00 1.00 1.00 0

1.25 1.19 1.13 1.08 1.02 1.00 1.00 1.00 1.00 250

1.29 1.23 1.17 1.12 1.06 1.00 1.00 1.00 1.00 500

DM5170-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5170-00

-METRIC-

page 2 of 2

313

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 8.0:1 Aftercooler Inlet Temperature (°C) 32 Jacket Water Outlet Temperature (°C) 127 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 HPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

242 80 1524

100%

75%

50%

803 765

602 574

402 383

10.7 4.47 5.78 268 165 233 46 33 478 4.8 6

10.81 4.32 5.58 237 149 173 42 33 469 4.64 5.81

11.42 4.4 5.68 173 102 119 35 33 470 4.74 5.92

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 145 797

4.0 221 1219

5.5 282 1555

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.4 215 722

2.8 243 817

3.0 244 819

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

3.1 485 924

2.9 447 851

3.2 463 881

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.47 33 139

0.44 29 128

0.48 29 133

%

7.9 1.61

7.3 1.54

6.6 1.46

kW kW kW kW kW kW kW kW

2385 803 472 104 136 699 539 171

1807 602 393 87 113 497 382 115

1273 402 322 69 93 341 261 46

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC314

page 1 of 2

DM5132-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0.90/19

35 0.90/21

40 0.90/22

45 1.0/23

50 1.0/24

55 1.0/26

60 1.0/27

65 1.0/28

70 1.0/30

75 1.0/31

80 to 100 1.0/33

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

1.00 0.98 0.95 0.93 0.90 0.87 1.00 1.00 0.97 0.94 0.91 0.88 1.00 1.00 0.98 0.95 0.93 0.90 1.00 1.00 1.00 0.97 0.94 0.91 1.00 1.00 1.00 0.99 0.96 0.93 1.00 1.00 1.00 1.00 0.97 0.94 1.00 1.00 1.00 1.00 0.99 0.96 1.00 1.00 1.00 1.00 1.00 0.98 1.00 1.00 1.00 1.00 1.00 0.99 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.84 0.86 0.87 0.88 0.90 0.91 0.93 0.95 0.96 2250

0.82 0.83 0.84 0.86 0.87 0.89 0.90 0.92 0.93 2500

0.79 0.80 0.82 0.83 0.84 0.86 0.87 0.89 0.90 2750

0.77 0.78 0.79 0.80 0.82 0.83 0.85 0.86 0.88 3000

1.33 1.37 1.41 1.46 1.46 1.46 1.27 1.31 1.35 1.40 1.40 1.40 1.21 1.25 1.29 1.34 1.34 1.34 1.16 1.19 1.23 1.27 1.28 1.28 1.10 1.14 1.17 1.21 1.22 1.22 1.04 1.08 1.11 1.15 1.16 1.16 1.00 1.02 1.05 1.09 1.10 1.10 1.00 1.00 1.00 1.03 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.46 1.40 1.34 1.28 1.22 1.16 1.10 1.04 1.00 2250

1.46 1.40 1.34 1.28 1.22 1.16 1.10 1.04 1.00 2500

1.46 1.40 1.34 1.28 1.22 1.16 1.10 1.04 1.00 2750

1.46 1.40 1.34 1.28 1.22 1.16 1.10 1.04 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.21 1.15 1.10 1.04 1.00 1.00 1.00 1.00 1.00 0

1.25 1.19 1.14 1.08 1.02 1.00 1.00 1.00 1.00 250

1.29 1.23 1.17 1.12 1.06 1.00 1.00 1.00 1.00 500

DM5132-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5132-00

-METRIC-

page 2 of 2

315

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°C) 32 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 HPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

207 80 1311

100%

75%

50%

803 765

602 574

402 383

10.3 4.09 5.29 244 147 216 44 18 456 4.41 5.51

10.92 4.29 5.54 232 134 172 42 18 453 4.62 5.78

11.5 4.08 5.28 168 91 112 42 18 466 4.42 5.53

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 157 866

3.0 156 859

8.3 419 2312

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.6 243 818

2.8 243 817

3.2 264 890

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

5.1 833 1587

4.4 680 1296

3.7 73 139

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.77 56 239

0.66 45 195

0.56 5 21

%

7.6 1.48

7.5 1.44

5.9 1.30

kW kW kW kW kW kW kW kW

2296 803 648 80 0 633 466 133

1826 602 575 67 0 489 364 94

1282 402 471 53 0 321 243 35

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC316

page 1 of 2

DM5131-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/15

70 1.0/16

75 1.0/17

80 to 100 1.0/18

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

0.99 0.96 0.93 0.90 0.87 0.85 1.00 0.97 0.94 0.92 0.89 0.86 1.00 0.99 0.96 0.93 0.90 0.87 1.00 1.00 0.97 0.95 0.92 0.89 1.00 1.00 0.99 0.96 0.93 0.90 1.00 1.00 1.00 0.98 0.95 0.92 1.00 1.00 1.00 0.99 0.96 0.93 1.00 1.00 1.00 1.00 0.98 0.95 1.00 1.00 1.00 1.00 1.00 0.97 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.82 0.83 0.85 0.86 0.88 0.89 0.91 0.92 0.94 2250

0.80 0.81 0.82 0.83 0.85 0.86 0.88 0.89 0.91 2500

0.77 0.78 0.80 0.81 0.82 0.84 0.85 0.87 0.88 2750

0.75 0.76 0.77 0.78 0.80 0.81 0.82 0.84 0.85 3000

1.36 1.40 1.45 1.46 1.46 1.46 1.29 1.34 1.38 1.39 1.39 1.39 1.23 1.27 1.32 1.33 1.33 1.33 1.17 1.21 1.25 1.26 1.26 1.26 1.10 1.15 1.19 1.20 1.20 1.20 1.04 1.08 1.12 1.13 1.13 1.13 1.00 1.02 1.06 1.07 1.07 1.07 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.46 1.39 1.33 1.26 1.20 1.13 1.07 1.00 1.00 2250

1.46 1.39 1.33 1.26 1.20 1.13 1.07 1.00 1.00 2500

1.46 1.39 1.33 1.26 1.20 1.13 1.07 1.00 1.00 2750

1.46 1.39 1.33 1.26 1.20 1.13 1.07 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.23 1.17 1.11 1.04 1.00 1.00 1.00 1.00 1.00 0

1.27 1.21 1.15 1.09 1.02 1.00 1.00 1.00 1.00 250

1.31 1.25 1.19 1.13 1.06 1.00 1.00 1.00 1.00 500

DM5131-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5131-00

-METRIC-

page 2 of 2

317

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°C) 32 Jacket Water Outlet Temperature (°C) 127 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 HPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

207 80 1311

100%

75%

50%

803 765

602 574

402 383

10.43 4.16 5.38 247 147 218 47 18 465 4.47 5.59

10.84 4.36 5.63 234 134 173 45 18 462 4.69 5.87

11.41 4.15 5.36 169 91 112 44 18 476 4.49 5.61

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 158 872

3.0 157 866

8.3 421 2324

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 248 835

2.9 248 835

3.3 269 906

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

4.8 775 1476

4.1 633 1205

3.5 68 129

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.73 52 222

0.62 43 181

0.53 5 20

%

7.7 1.52

7.6 1.49

5.9 1.34

kW kW kW kW kW kW kW kW

2325 803 490 104 141 651 486 135

1813 602 407 87 117 504 379 96

1272 402 338 69 97 331 253 35

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC318

page 1 of 2

DM5130-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/--

70 1.0/16

75 1.0/17

80 to 100 1.0/18

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

0.99 0.96 0.93 0.90 0.87 0.85 1.00 0.97 0.94 0.92 0.89 0.86 1.00 0.99 0.96 0.93 0.90 0.87 1.00 1.00 0.97 0.95 0.92 0.89 1.00 1.00 0.99 0.96 0.93 0.90 1.00 1.00 1.00 0.98 0.95 0.92 1.00 1.00 1.00 0.99 0.96 0.93 1.00 1.00 1.00 1.00 0.98 0.95 1.00 1.00 1.00 1.00 1.00 0.97 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.82 0.83 0.85 0.86 0.88 0.89 0.91 0.92 0.94 2250

0.80 0.81 0.82 0.83 0.85 0.86 0.88 0.89 0.91 2500

0.77 0.78 0.80 0.81 0.82 0.84 0.85 0.87 0.88 2750

0.75 0.76 0.77 0.78 0.80 0.81 0.82 0.84 0.85 3000

1.36 1.40 1.45 1.46 1.46 1.46 1.29 1.34 1.38 1.39 1.39 1.39 1.23 1.27 1.32 1.33 1.33 1.33 1.17 1.21 1.25 1.26 1.26 1.26 1.10 1.15 1.19 1.20 1.20 1.20 1.04 1.08 1.12 1.13 1.13 1.13 1.00 1.02 1.06 1.07 1.07 1.07 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.46 1.39 1.33 1.26 1.20 1.13 1.07 1.00 1.00 2250

1.46 1.39 1.33 1.26 1.20 1.13 1.07 1.00 1.00 2500

1.46 1.39 1.33 1.26 1.20 1.13 1.07 1.00 1.00 2750

1.46 1.39 1.33 1.26 1.20 1.13 1.07 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.23 1.17 1.11 1.05 1.00 1.00 1.00 1.00 1.00 0

1.27 1.21 1.15 1.09 1.02 1.00 1.00 1.00 1.00 250

1.31 1.25 1.19 1.13 1.06 1.00 1.00 1.00 1.00 500

DM5130-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5130-00

-METRIC-

page 2 of 2

319

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°C) 32 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 LPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

10 80 1006

100%

75%

50%

803 765

602 574

402 383

10.3 4.09 5.29 244 153 216 44 18 456 4.41 5.51

10.92 4.29 5.54 232 137 172 42 18 453 4.62 5.78

11.5 4.08 5.28 168 92 112 42 18 466 4.42 5.53

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 157 866

3.0 156 859

8.3 419 2312

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.6 243 818

2.8 243 817

3.2 264 890

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

5.1 833 1587

4.4 680 1296

3.7 73 139

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.77 56 239

0.66 45 195

0.56 5 21

%

7.6 1.48

7.5 1.44

5.9 1.30

kW kW kW kW kW kW kW kW

2296 803 635 80 0 633 466 146

1826 602 568 67 0 489 364 101

1282 402 469 53 0 321 243 37

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC320

page 1 of 2

DM5210-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/15

70 1.0/16

75 1.0/17

80 to 100 1.0/18

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

0.95 0.92 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.88 0.86 0.83 0.98 0.95 0.92 0.90 0.87 0.84 1.00 0.97 0.94 0.91 0.88 0.86 1.00 0.98 0.95 0.93 0.90 0.87 1.00 1.00 0.97 0.94 0.91 0.89 1.00 1.00 0.99 0.96 0.93 0.90 1.00 1.00 1.00 0.97 0.94 0.92 1.00 1.00 1.00 0.99 0.96 0.93 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.79 0.80 0.82 0.83 0.84 0.86 0.87 0.89 0.90 2250

0.77 0.78 0.79 0.80 0.82 0.83 0.85 0.86 0.88 2500

0.74 0.76 0.77 0.78 0.79 0.81 0.82 0.83 0.85 2750

0.72 0.73 0.74 0.76 0.77 0.78 0.79 0.81 0.82 3000

1.35 1.39 1.39 1.39 1.39 1.39 1.29 1.33 1.33 1.33 1.33 1.33 1.22 1.27 1.27 1.27 1.27 1.27 1.16 1.20 1.21 1.21 1.21 1.21 1.10 1.14 1.14 1.14 1.14 1.14 1.04 1.08 1.08 1.08 1.08 1.08 1.00 1.02 1.02 1.02 1.02 1.02 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.39 1.33 1.27 1.21 1.14 1.08 1.02 1.00 1.00 2250

1.39 1.33 1.27 1.21 1.14 1.08 1.02 1.00 1.00 2500

1.39 1.33 1.27 1.21 1.14 1.08 1.02 1.00 1.00 2750

1.39 1.33 1.27 1.21 1.14 1.08 1.02 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.22 1.16 1.10 1.04 1.00 1.00 1.00 1.00 1.00 0

1.26 1.20 1.14 1.08 1.02 1.00 1.00 1.00 1.00 250

1.30 1.24 1.18 1.12 1.06 1.00 1.00 1.00 1.00 500

DM5210-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5210-00

-METRIC-

page 2 of 2

321

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°C) 32 Jacket Water Outlet Temperature (°C) 127 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 LPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

10 80 1006

100%

75%

50%

803 765

602 574

402 383

10.43 4.16 5.38 247 153 218 47 18 465 4.47 5.59

10.84 4.36 5.63 234 139 173 45 18 462 4.69 5.87

11.41 4.15 5.36 169 95 112 44 18 476 4.49 5.61

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 158 872

3.0 157 866

8.3 421 2324

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 248 835

2.9 248 835

3.3 269 906

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

4.8 775 1476

4.1 633 1205

3.5 68 129

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.73 52 222

0.62 43 181

0.53 5 20

%

7.7 1.52

7.6 1.49

5.9 1.34

kW kW kW kW kW kW kW kW

2325 803 481 104 139 651 486 147

1813 602 400 87 115 504 379 105

1272 402 335 69 97 331 253 39

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC322

page 1 of 2

DM5139-00

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/--

70 1.0/16

75 1.0/17

80 to 100 1.0/18

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

0.98 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

0.95 0.92 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.88 0.86 0.83 0.98 0.95 0.92 0.90 0.87 0.84 1.00 0.97 0.94 0.91 0.88 0.86 1.00 0.98 0.95 0.93 0.90 0.87 1.00 1.00 0.97 0.94 0.91 0.89 1.00 1.00 0.99 0.96 0.93 0.90 1.00 1.00 1.00 0.97 0.94 0.92 1.00 1.00 1.00 0.99 0.96 0.93 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.79 0.80 0.82 0.83 0.84 0.86 0.87 0.89 0.90 2250

0.77 0.78 0.79 0.80 0.82 0.83 0.85 0.86 0.88 2500

0.74 0.76 0.77 0.78 0.79 0.81 0.82 0.83 0.85 2750

0.72 0.73 0.74 0.76 0.77 0.78 0.79 0.81 0.82 3000

1.35 1.39 1.39 1.39 1.39 1.39 1.29 1.33 1.33 1.33 1.33 1.33 1.22 1.27 1.27 1.27 1.27 1.27 1.16 1.20 1.21 1.21 1.21 1.21 1.10 1.14 1.14 1.14 1.14 1.14 1.04 1.08 1.08 1.08 1.08 1.08 1.00 1.02 1.02 1.02 1.02 1.02 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.39 1.33 1.27 1.21 1.14 1.08 1.02 1.00 1.00 2250

1.39 1.33 1.27 1.21 1.14 1.08 1.02 1.00 1.00 2500

1.39 1.33 1.27 1.21 1.14 1.08 1.02 1.00 1.00 2750

1.39 1.33 1.27 1.21 1.14 1.08 1.02 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.22 1.16 1.10 1.04 1.00 1.00 1.00 1.00 1.00 0

1.26 1.20 1.14 1.08 1.02 1.00 1.00 1.00 1.00 250

1.30 1.24 1.18 1.12 1.06 1.00 1.00 1.00 1.00 500

DM5139-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5139-00

-METRIC-

page 2 of 2

323

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

NAT GAS 36.2 DELTEC 10 80 200

100%

75%

50%

758 725

569 544

379 363

10.13 4.47 5.78 251 145 242 57 22 531 4.79 5.99

10.47 4.55 5.88 202 115 183 56 22 532 4.88 6.1

11.12 4.69 6.07 155 81 126 55 22 527 5.04 6.3

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.8 46 250

0.8 46 250

0.8 46 250

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

3.0 289 973

2.9 277 933

2.9 261 880

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

7.8 1335 2544

8.4 1414 2695

9.2 1452 2766

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.17 105 382

1.27 110 405

1.38 110 415

%

9.6 1.66

9.5 1.65

9.2 1.60

kW kW kW kW kW kW kW kW

2132 758 409 80 0 773 586 112

1652 569 364 67 0 595 449 57

1170 379 313 53 0 407 305 17

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC324

page 1 of 2

DM1977-01

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/18

70 1.0/19

75 1.0/20

80 to 100 1.0/22

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.94 0.96 0.98 0.99 1.00 1.00 1.00 1.00 1.00 0

0.92 0.93 0.95 0.96 0.98 0.99 1.00 1.00 1.00 250

0.89 0.90 0.92 0.93 0.95 0.96 0.98 1.00 1.00 500

0.86 0.84 0.81 0.79 0.76 0.74 0.88 0.85 0.83 0.80 0.78 0.75 0.89 0.86 0.84 0.81 0.79 0.76 0.91 0.88 0.85 0.83 0.80 0.78 0.92 0.89 0.87 0.84 0.81 0.79 0.94 0.91 0.88 0.85 0.83 0.80 0.95 0.92 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.88 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.72 0.73 0.74 0.75 0.77 0.78 0.79 0.81 0.82 2250

0.70 0.71 0.72 0.73 0.74 0.75 0.77 0.78 0.79 2500

0.67 0.69 0.70 0.71 0.72 0.73 0.74 0.76 0.77 2750

0.65 0.66 0.67 0.69 0.70 0.71 0.72 0.73 0.75 3000

1.34 1.34 1.34 1.34 1.34 1.34 1.26 1.26 1.26 1.26 1.26 1.26 1.18 1.18 1.18 1.18 1.18 1.18 1.10 1.10 1.10 1.10 1.10 1.10 1.02 1.02 1.02 1.02 1.02 1.02 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.34 1.26 1.18 1.10 1.02 1.00 1.00 1.00 1.00 2250

1.34 1.26 1.18 1.10 1.02 1.00 1.00 1.00 1.00 2500

1.34 1.26 1.18 1.10 1.02 1.00 1.00 1.00 1.00 2750

1.34 1.26 1.18 1.10 1.02 1.00 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.29 1.22 1.14 1.06 1.00 1.00 1.00 1.00 1.00 0

1.34 1.26 1.18 1.10 1.02 1.00 1.00 1.00 1.00 250

1.34 1.26 1.18 1.10 1.02 1.00 1.00 1.00 1.00 500

DM1977-01 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1977-01

-METRIC-

page 2 of 2

325

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

NAT GAS 36.2 DELTEC 10 80 350

100%

75%

50%

758 725

569 544

379 363

9.78 4.17 5.38 234 135 227 57 22 536 4.47 5.59

10.18 4.25 5.49 195 109 172 55 22 537 4.56 5.71

10.94 4.47 5.78 150 78 121 55 22 533 4.8 6.01

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.5 91 500

1.5 91 500

1.6 91 500

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

3.0 300 1008

3.0 297 998

3.1 285 959

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

6.0 1061 2022

6.7 1160 2211

7.8 1252 2386

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.91 80 304

1.02 87 332

1.17 92 358

%

9.1 1.60

9.0 1.58

8.8 1.55

kW kW kW kW kW kW kW kW

2058 758 407 80 0 720 555 93

1606 569 367 67 0 555 425 49

1151 379 314 53 0 390 296 15

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC326

page 1 of 2

DM1980-01

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/19

70 1.0/19

75 1.0/20

80 to 100 1.0/22

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.96 0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 0

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 250

0.91 0.92 0.94 0.95 0.97 0.98 1.00 1.00 1.00 500

0.88 0.85 0.83 0.80 0.78 0.75 0.89 0.87 0.84 0.82 0.79 0.77 0.91 0.88 0.85 0.83 0.80 0.78 0.92 0.89 0.87 0.84 0.82 0.79 0.94 0.91 0.88 0.86 0.83 0.80 0.95 0.92 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.88 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 1.00 0.97 0.94 0.92 0.89 0.86 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.73 0.74 0.75 0.77 0.78 0.79 0.81 0.82 0.83 2250

0.71 0.72 0.73 0.74 0.76 0.77 0.78 0.79 0.81 2500

0.69 0.70 0.71 0.72 0.73 0.74 0.76 0.77 0.78 2750

0.67 0.68 0.69 0.70 0.71 0.72 0.73 0.75 0.76 3000

1.40 1.40 1.40 1.40 1.40 1.40 1.32 1.32 1.32 1.32 1.32 1.32 1.23 1.23 1.23 1.23 1.23 1.23 1.14 1.14 1.14 1.14 1.14 1.14 1.06 1.06 1.06 1.06 1.06 1.06 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.40 1.32 1.23 1.14 1.06 1.00 1.00 1.00 1.00 2250

1.40 1.32 1.23 1.14 1.06 1.00 1.00 1.00 1.00 2500

1.40 1.32 1.23 1.14 1.06 1.00 1.00 1.00 1.00 2750

1.40 1.32 1.23 1.14 1.06 1.00 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.32 1.24 1.15 1.07 1.00 1.00 1.00 1.00 1.00 0

1.38 1.29 1.21 1.12 1.03 1.00 1.00 1.00 1.00 250

1.40 1.32 1.23 1.14 1.06 1.00 1.00 1.00 1.00 500

DM1980-01 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1980-01

-METRIC-

page 2 of 2

327

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 127 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

NAT GAS 36.2 DELTEC 10 80 200

100%

75%

50%

758 725

569 544

379 363

10.3 4.54 5.87 258 151 251 57 19 554 4.87 6.09

10.63 4.61 5.96 211 121 189 56 19 553 4.94 6.18

11.36 4.85 6.27 160 87 132 55 19 552 5.21 6.51

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.8 46 250

0.8 46 250

0.8 46 250

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.9 273 920

2.9 267 899

3.0 262 880

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

6.1 1015 1934

6.6 1062 2024

7.6 1156 2202

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.92 79 291

0.99 81 304

1.14 87 331

%

9.4 1.66

9.3 1.64

9.1 1.62

kW kW kW kW kW kW kW kW

2168 758 293 104 85 806 630 122

1678 569 266 87 77 615 479 65

1196 379 226 69 65 434 336 22

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC328

page 1 of 2

DM1989-01

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 .95/16*

70 1.0/16*

75 1.0/18

80 to 100 1.0/19

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.94 0.96 0.98 0.99 1.00 1.00 1.00 1.00 1.00 0

0.92 0.93 0.95 0.96 0.98 0.99 1.00 1.00 1.00 250

0.89 0.90 0.92 0.93 0.95 0.96 0.98 1.00 1.00 500

0.86 0.84 0.81 0.79 0.76 0.74 0.88 0.85 0.83 0.80 0.78 0.75 0.89 0.86 0.84 0.81 0.79 0.76 0.91 0.88 0.85 0.83 0.80 0.78 0.92 0.89 0.87 0.84 0.81 0.79 0.94 0.91 0.88 0.85 0.83 0.80 0.95 0.92 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.88 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.72 0.73 0.74 0.75 0.77 0.78 0.79 0.81 0.82 2250

0.70 0.71 0.72 0.73 0.74 0.75 0.77 0.78 0.79 2500

0.67 0.69 0.70 0.71 0.72 0.73 0.74 0.76 0.77 2750

0.65 0.66 0.67 0.69 0.70 0.71 0.72 0.73 0.75 3000

1.32 1.32 1.32 1.32 1.32 1.32 1.25 1.25 1.25 1.25 1.25 1.25 1.17 1.17 1.17 1.17 1.17 1.17 1.10 1.10 1.10 1.10 1.10 1.10 1.02 1.02 1.02 1.02 1.02 1.02 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.32 1.25 1.17 1.10 1.02 1.00 1.00 1.00 1.00 2250

1.32 1.25 1.17 1.10 1.02 1.00 1.00 1.00 1.00 2500

1.32 1.25 1.17 1.10 1.02 1.00 1.00 1.00 1.00 2750

1.32 1.25 1.17 1.10 1.02 1.00 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.28 1.21 1.13 1.06 1.00 1.00 1.00 1.00 1.00 0

1.32 1.25 1.17 1.10 1.02 1.00 1.00 1.00 1.00 250

1.32 1.25 1.17 1.10 1.02 1.00 1.00 1.00 1.00 500

DM1989-01 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1989-01

-METRIC-

page 2 of 2

329

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 11.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 127 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

NAT GAS 36.2 DELTEC 10 80 350

100%

75%

50%

758 725

569 544

379 363

9.98 4.24 5.48 244 142 235 56 19 560 4.55 5.69

10.36 4.34 5.6 201 116 178 55 19 559 4.66 5.82

11.11 4.62 5.96 155 83 124 55 19 557 4.96 6.2

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.5 91 500

1.6 91 500

1.7 91 500

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

3.0 294 989

3.1 294 989

3.4 293 985

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

4.6 792 1509

5.3 880 1677

6.3 966 1841

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.70 59 227

0.80 65 252

0.95 70 277

%

8.9 1.60

8.8 1.59

8.6 1.58

kW kW kW kW kW kW kW kW

2100 758 294 104 85 755 599 104

1635 569 265 87 76 582 459 56

1169 379 223 69 64 414 324 19

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC330

page 1 of 2

DM1992-01

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 70 0.95/16* 1.0/16*

75 1.0/18

80 to 100 1.0/19

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.96 0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 0

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 250

0.91 0.92 0.94 0.95 0.97 0.98 1.00 1.00 1.00 500

0.88 0.85 0.83 0.80 0.78 0.75 0.89 0.87 0.84 0.82 0.79 0.77 0.91 0.88 0.85 0.83 0.80 0.78 0.92 0.89 0.87 0.84 0.82 0.79 0.94 0.91 0.88 0.86 0.83 0.80 0.95 0.92 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.88 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 1.00 0.97 0.94 0.92 0.89 0.86 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.73 0.74 0.75 0.77 0.78 0.79 0.81 0.82 0.83 2250

0.71 0.72 0.73 0.74 0.76 0.77 0.78 0.79 0.81 2500

0.69 0.70 0.71 0.72 0.73 0.74 0.76 0.77 0.78 2750

0.67 0.68 0.69 0.70 0.71 0.72 0.73 0.75 0.76 3000

1.38 1.38 1.38 1.38 1.38 1.38 1.30 1.30 1.30 1.30 1.30 1.30 1.21 1.21 1.21 1.21 1.21 1.21 1.13 1.13 1.13 1.13 1.13 1.13 1.05 1.05 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.38 1.30 1.21 1.13 1.05 1.00 1.00 1.00 1.00 2250

1.38 1.30 1.21 1.13 1.05 1.00 1.00 1.00 1.00 2500

1.38 1.30 1.21 1.13 1.05 1.00 1.00 1.00 1.00 2750

1.38 1.30 1.21 1.13 1.05 1.00 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.30 1.22 1.14 1.06 1.00 1.00 1.00 1.00 1.00 0

1.36 1.27 1.19 1.11 1.03 1.00 1.00 1.00 1.00 250

1.38 1.30 1.21 1.13 1.05 1.00 1.00 1.00 1.00 500

DM1992-01 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1992-01

-METRIC-

page 2 of 2

331

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

NAT GAS 36.2 DELTEC 10 80 200

100%

75%

50%

758 725

569 544

379 363

9.84 4.51 5.83 239 144 230 57 20 512 4.83 6.04

10.24 4.6 5.94 196 114 178 56 20 518 4.92 6.16

10.95 4.77 6.16 152 80 125 55 20 517 5.12 6.4

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.8 46 250

0.8 46 250

0.8 46 250

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.8 277 933

2.8 269 904

2.8 256 861

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

7.0 1222 2328

7.7 1322 2519

8.7 1387 2643

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.05 96 350

1.17 103 378

1.30 105 397

%

9.6 1.69

9.5 1.67

9.2 1.62

kW kW kW kW kW kW kW kW

2070 758 377 80 0 743 562 112

1615 569 344 67 0 579 436 57

1152 379 299 53 0 404 302 17

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC332

page 1 of 2

DM1953-01

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 70 0.90/18* 0.95/18*

75 1.0/18

80 to 100 1.0/20

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.94 0.96 0.98 0.99 1.00 1.00 1.00 1.00 1.00 0

0.92 0.93 0.95 0.96 0.98 0.99 1.00 1.00 1.00 250

0.89 0.90 0.92 0.93 0.95 0.96 0.98 1.00 1.00 500

0.86 0.84 0.81 0.79 0.76 0.74 0.88 0.85 0.83 0.80 0.78 0.75 0.89 0.86 0.84 0.81 0.79 0.76 0.91 0.88 0.85 0.83 0.80 0.78 0.92 0.89 0.87 0.84 0.81 0.79 0.94 0.91 0.88 0.85 0.83 0.80 0.95 0.92 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.88 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.72 0.73 0.74 0.75 0.77 0.78 0.79 0.81 0.82 2250

0.70 0.71 0.72 0.73 0.74 0.75 0.77 0.78 0.79 2500

0.67 0.69 0.70 0.71 0.72 0.73 0.74 0.76 0.77 2750

0.65 0.66 0.67 0.69 0.70 0.71 0.72 0.73 0.75 3000

1.34 1.34 1.34 1.34 1.34 1.34 1.26 1.26 1.26 1.26 1.26 1.26 1.18 1.18 1.18 1.18 1.18 1.18 1.10 1.10 1.10 1.10 1.10 1.10 1.02 1.02 1.02 1.02 1.02 1.02 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.34 1.26 1.18 1.10 1.02 1.00 1.00 1.00 1.00 2250

1.34 1.26 1.18 1.10 1.02 1.00 1.00 1.00 1.00 2500

1.34 1.26 1.18 1.10 1.02 1.00 1.00 1.00 1.00 2750

1.34 1.26 1.18 1.10 1.02 1.00 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.29 1.21 1.14 1.06 1.00 1.00 1.00 1.00 1.00 0

1.34 1.26 1.18 1.10 1.02 1.00 1.00 1.00 1.00 250

1.34 1.26 1.18 1.10 1.02 1.00 1.00 1.00 1.00 500

DM1953-01 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1953-01

-METRIC-

page 2 of 2

333

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

NAT GAS 36.2 DELTEC 10 80 350

100%

75%

50%

758 725

569 544

379 363

9.5 4.2 5.43 223 134 216 57 20 517 4.51 5.64

9.95 4.32 5.58 189 109 168 55 20 522 4.63 5.79

10.78 4.53 5.86 148 78 120 55 20 523 4.87 6.09

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.5 91 500

1.5 91 500

1.6 91 500

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.8 287 967

2.9 287 967

3.0 279 939

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

5.4 971 1849

6.2 1085 2066

7.3 1196 2280

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.81 73 278

0.93 81 310

1.10 88 342

%

9.1 1.63

9.0 1.60

8.8 1.56

kW kW kW kW kW kW kW kW

1998 758 375 80 0 693 532 93

1571 569 343 67 0 544 416 49

1134 379 302 53 0 385 293 15

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC334

page 1 of 2

DM1956-01

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 70 0.90/18* 0.95/18*

75 1.0/18

80 to 100 1.0/20

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.96 0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 0

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 250

0.91 0.92 0.94 0.95 0.97 0.98 1.00 1.00 1.00 500

0.88 0.85 0.83 0.80 0.78 0.75 0.89 0.87 0.84 0.82 0.79 0.77 0.91 0.88 0.85 0.83 0.80 0.78 0.92 0.89 0.87 0.84 0.82 0.79 0.94 0.91 0.88 0.86 0.83 0.80 0.95 0.92 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.88 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 1.00 0.97 0.94 0.92 0.89 0.86 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.73 0.74 0.75 0.77 0.78 0.79 0.81 0.82 0.83 2250

0.71 0.72 0.73 0.74 0.76 0.77 0.78 0.79 0.81 2500

0.69 0.70 0.71 0.72 0.73 0.74 0.76 0.77 0.78 2750

0.67 0.68 0.69 0.70 0.71 0.72 0.73 0.75 0.76 3000

1.40 1.40 1.40 1.40 1.40 1.40 1.32 1.32 1.32 1.32 1.32 1.32 1.23 1.23 1.23 1.23 1.23 1.23 1.14 1.14 1.14 1.14 1.14 1.14 1.05 1.05 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.40 1.32 1.23 1.14 1.05 1.00 1.00 1.00 1.00 2250

1.40 1.32 1.23 1.14 1.05 1.00 1.00 1.00 1.00 2500

1.40 1.32 1.23 1.14 1.05 1.00 1.00 1.00 1.00 2750

1.40 1.32 1.23 1.14 1.05 1.00 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.32 1.23 1.15 1.06 1.00 1.00 1.00 1.00 1.00 0

1.38 1.29 1.21 1.12 1.03 1.00 1.00 1.00 1.00 250

1.40 1.32 1.23 1.14 1.05 1.00 1.00 1.00 1.00 500

DM1956-01 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1956-01

-METRIC-

page 2 of 2

335

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 127 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

NAT GAS 36.2 DELTEC 10 80 200

100%

75%

50%

758 725

569 544

379 363

10 4.48 5.79 245 150 238 57 17 534 4.8 6.01

10.4 4.65 6.01 204 121 183 56 17 538 4.98 6.23

11.2 4.88 6.3 157 87 130 55 17 542 5.23 6.54

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.6 46 250

0.6 46 250

0.7 46 250

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 262 882

2.8 259 871

2.9 256 862

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

5.5 929 1770

6.0 993 1892

7.2 1104 2104

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.83 72 266

0.91 76 284

1.08 83 316

%

9.4 1.69

9.3 1.66

9.1 1.64

kW kW kW kW kW kW kW kW

2105 758 248 104 116 760 591 119

1641 569 220 87 103 598 465 65

1178 379 192 69 90 426 329 22

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC336

page 1 of 2

DM1965-01

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/--

70 0/--

75 0.90/16*

80 to 100 1.0/17

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.94 0.96 0.98 0.99 1.00 1.00 1.00 1.00 1.00 0

0.92 0.93 0.95 0.96 0.98 0.99 1.00 1.00 1.00 250

0.89 0.90 0.92 0.93 0.95 0.96 0.98 1.00 1.00 500

0.86 0.84 0.81 0.79 0.76 0.74 0.88 0.85 0.83 0.80 0.78 0.75 0.89 0.86 0.84 0.81 0.79 0.76 0.91 0.88 0.85 0.83 0.80 0.78 0.92 0.89 0.87 0.84 0.81 0.79 0.94 0.91 0.88 0.85 0.83 0.80 0.95 0.92 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.88 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.72 0.73 0.74 0.75 0.77 0.78 0.79 0.81 0.82 2250

0.70 0.71 0.72 0.73 0.74 0.75 0.77 0.78 0.79 2500

0.67 0.69 0.70 0.71 0.72 0.73 0.74 0.76 0.77 2750

0.65 0.66 0.67 0.69 0.70 0.71 0.72 0.73 0.75 3000

1.32 1.32 1.32 1.32 1.32 1.32 1.25 1.25 1.25 1.25 1.25 1.25 1.17 1.17 1.17 1.17 1.17 1.17 1.09 1.09 1.09 1.09 1.09 1.09 1.02 1.02 1.02 1.02 1.02 1.02 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.32 1.25 1.17 1.09 1.02 1.00 1.00 1.00 1.00 2250

1.32 1.25 1.17 1.09 1.02 1.00 1.00 1.00 1.00 2500

1.32 1.25 1.17 1.09 1.02 1.00 1.00 1.00 1.00 2750

1.32 1.25 1.17 1.09 1.02 1.00 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.28 1.21 1.13 1.06 1.00 1.00 1.00 1.00 1.00 0

1.32 1.25 1.17 1.09 1.02 1.00 1.00 1.00 1.00 250

1.32 1.25 1.17 1.09 1.02 1.00 1.00 1.00 1.00 500

DM1965-01 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1965-01

-METRIC-

page 2 of 2

337

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 127 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

NAT GAS 36.2 DELTEC 10 80 350

100%

75%

50%

758 725

569 544

379 363

9.69 4.18 5.41 232 141 224 56 17 540 4.49 5.61

10.13 4.29 5.55 195 115 173 55 17 544 4.61 5.76

10.95 4.58 5.92 152 83 123 55 17 547 4.92 6.15

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.3 91 500

1.4 91 500

1.4 91 500

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.9 282 949

3.0 285 958

3.3 287 964

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

4.1 724 1380

4.9 823 1567

6.0 923 1759

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.63 54 207

0.74 60 236

0.90 67 264

%

8.9 1.62

8.8 1.61

8.6 1.59

kW kW kW kW kW kW kW kW

2039 758 248 104 116 712 562 102

1599 569 226 87 106 557 437 55

1152 379 193 69 90 402 314 18

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC338

page 1 of 2

DM1968-01

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/--

70 0/--

75 0.90/16*

80 to 100 1.0/17

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.96 0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 0

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 250

0.91 0.92 0.94 0.95 0.97 0.98 1.00 1.00 1.00 500

0.88 0.85 0.83 0.80 0.78 0.75 0.89 0.87 0.84 0.82 0.79 0.77 0.91 0.88 0.85 0.83 0.80 0.78 0.92 0.89 0.87 0.84 0.82 0.79 0.94 0.91 0.88 0.86 0.83 0.80 0.95 0.92 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.88 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 1.00 0.97 0.94 0.92 0.89 0.86 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.73 0.74 0.75 0.77 0.78 0.79 0.81 0.82 0.83 2250

0.71 0.72 0.73 0.74 0.76 0.77 0.78 0.79 0.81 2500

0.69 0.70 0.71 0.72 0.73 0.74 0.76 0.77 0.78 2750

0.67 0.68 0.69 0.70 0.71 0.72 0.73 0.75 0.76 3000

1.38 1.38 1.38 1.38 1.38 1.38 1.30 1.30 1.30 1.30 1.30 1.30 1.22 1.22 1.22 1.22 1.22 1.22 1.13 1.13 1.13 1.13 1.13 1.13 1.05 1.05 1.05 1.05 1.05 1.05 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.38 1.30 1.22 1.13 1.05 1.00 1.00 1.00 1.00 2250

1.38 1.30 1.22 1.13 1.05 1.00 1.00 1.00 1.00 2500

1.38 1.30 1.22 1.13 1.05 1.00 1.00 1.00 1.00 2750

1.38 1.30 1.22 1.13 1.05 1.00 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.30 1.22 1.14 1.06 1.00 1.00 1.00 1.00 1.00 0

1.36 1.28 1.19 1.11 1.03 1.00 1.00 1.00 1.00 250

1.38 1.30 1.22 1.13 1.05 1.00 1.00 1.00 1.00 500

DM1968-01 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1968-01

-METRIC-

page 2 of 2

339

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°C) 32 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

NAT GAS 36.2 DELTEC 10 80 200

100%

75%

50%

803 770

602 578

402 385

9.52 4.36 5.64 242 146 230 38 24 493 4.67 5.84

10.01 4.4 5.68 198 115 178 35 24 501 4.71 5.89

10.74 4.64 6 154 82 126 33 24 501 4.98 6.23

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.7 46 250

0.7 46 250

0.8 46 250

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.8 286 963

2.8 277 933

2.8 261 879

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

7.4 1346 2565

8.7 1552 2957

9.9 1644 3132

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.12 107 385

1.31 123 444

1.49 128 470

%

9.7 1.70

9.7 1.66

9.5 1.64

kW kW kW kW kW kW kW kW

2122 803 360 80 0 738 546 142

1673 602 349 67 0 576 423 80

1197 402 299 53 0 409 298 34

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC340

page 1 of 2

DM1952-01

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/18*

70 1.0/20*

75 1.0/22

80 to 100 1.0/24

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.94 0.96 0.98 0.99 1.00 1.00 1.00 1.00 1.00 0

0.92 0.93 0.95 0.96 0.98 0.99 1.00 1.00 1.00 250

0.89 0.90 0.92 0.93 0.95 0.96 0.98 1.00 1.00 500

0.86 0.84 0.81 0.79 0.76 0.74 0.88 0.85 0.83 0.80 0.78 0.75 0.89 0.86 0.84 0.81 0.79 0.76 0.91 0.88 0.85 0.83 0.80 0.78 0.92 0.89 0.87 0.84 0.81 0.79 0.94 0.91 0.88 0.85 0.83 0.80 0.95 0.92 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.88 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.72 0.73 0.74 0.75 0.77 0.78 0.79 0.81 0.82 2250

0.70 0.71 0.72 0.73 0.74 0.75 0.77 0.78 0.79 2500

0.67 0.69 0.70 0.71 0.72 0.73 0.74 0.76 0.77 2750

0.65 0.66 0.67 0.69 0.70 0.71 0.72 0.73 0.75 3000

1.27 1.27 1.27 1.27 1.27 1.27 1.21 1.21 1.21 1.21 1.21 1.21 1.14 1.14 1.14 1.14 1.14 1.14 1.08 1.08 1.08 1.08 1.08 1.08 1.02 1.02 1.02 1.02 1.02 1.02 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.27 1.21 1.14 1.08 1.02 1.00 1.00 1.00 1.00 2250

1.27 1.21 1.14 1.08 1.02 1.00 1.00 1.00 1.00 2500

1.27 1.21 1.14 1.08 1.02 1.00 1.00 1.00 1.00 2750

1.27 1.21 1.14 1.08 1.02 1.00 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.24 1.17 1.11 1.05 1.00 1.00 1.00 1.00 1.00 0

1.27 1.21 1.14 1.08 1.02 1.00 1.00 1.00 1.00 250

1.27 1.21 1.14 1.08 1.02 1.00 1.00 1.00 1.00 500

DM1952-01 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1952-01

-METRIC-

page 2 of 2

341

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°C) 32 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

NAT GAS 36.2 DELTEC 10 80 350

100%

75%

50%

803 770

602 578

402 385

9.28 4.15 5.36 227 135 217 37 24 496 4.45 5.56

9.64 4.28 5.52 190 109 169 34 24 501 4.58 5.73

10.4 4.42 5.71 149 78 120 33 24 505 4.75 5.93

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.4 91 500

1.5 91 500

1.5 91 500

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.8 292 983

2.8 281 946

2.9 277 930

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

6.1 1139 2171

7.2 1290 2458

8.5 1437 2738

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.92 87 326

1.08 98 369

1.28 107 411

%

9.3 1.65

9.2 1.63

9.0 1.58

kW kW kW kW kW kW kW kW

2068 803 362 80 0 700 525 123

1612 602 318 67 0 553 412 72

1160 402 285 53 0 389 288 30

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC342

page 1 of 2

DM1955-01

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/18*

70 1.0/20*

75 1.0/22

80 to 100 1.0/24

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.96 0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 0

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 250

0.91 0.92 0.94 0.95 0.97 0.98 1.00 1.00 1.00 500

0.88 0.85 0.83 0.80 0.78 0.75 0.89 0.87 0.84 0.82 0.79 0.77 0.91 0.88 0.85 0.83 0.80 0.78 0.92 0.89 0.87 0.84 0.82 0.79 0.94 0.91 0.88 0.86 0.83 0.80 0.95 0.92 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.88 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 1.00 0.97 0.94 0.92 0.89 0.86 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.73 0.74 0.75 0.77 0.78 0.79 0.81 0.82 0.83 2250

0.71 0.72 0.73 0.74 0.76 0.77 0.78 0.79 0.81 2500

0.69 0.70 0.71 0.72 0.73 0.74 0.76 0.77 0.78 2750

0.67 0.68 0.69 0.70 0.71 0.72 0.73 0.75 0.76 3000

1.32 1.32 1.32 1.32 1.32 1.32 1.25 1.25 1.25 1.25 1.25 1.25 1.18 1.18 1.18 1.18 1.18 1.18 1.11 1.11 1.11 1.11 1.11 1.11 1.04 1.04 1.04 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.32 1.25 1.18 1.11 1.04 1.00 1.00 1.00 1.00 2250

1.32 1.25 1.18 1.11 1.04 1.00 1.00 1.00 1.00 2500

1.32 1.25 1.18 1.11 1.04 1.00 1.00 1.00 1.00 2750

1.32 1.25 1.18 1.11 1.04 1.00 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.25 1.19 1.12 1.05 1.00 1.00 1.00 1.00 1.00 0

1.30 1.23 1.16 1.09 1.03 1.00 1.00 1.00 1.00 250

1.32 1.25 1.18 1.11 1.04 1.00 1.00 1.00 1.00 500

DM1955-01 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1955-01

-METRIC-

page 2 of 2

343

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°C) 32 Jacket Water Outlet Temperature (°C) 127 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

NAT GAS 36.2 DELTEC 10 80 200

100%

75%

50%

803 770

602 578

402 385

9.8 4.51 5.83 245 152 239 38 21 514 4.83 6.04

10.06 4.59 5.93 204 122 184 35 21 519 4.92 6.15

10.75 4.79 6.19 157 88 129 33 21 522 5.14 6.42

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.8 46 250

0.8 46 250

0.8 46 250

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.9 282 948

2.8 271 912

2.9 262 880

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

6.8 1175 2239

7.3 1227 2338

8.5 1333 2541

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.02 91 336

1.10 94 351

1.27 100 382

%

9.4 1.70

9.3 1.68

9.1 1.66

kW kW kW kW kW kW kW kW

2184 803 228 104 106 789 598 154

1682 602 199 87 93 611 463 91

1199 402 175 69 82 432 325 39

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC344

page 1 of 2

DM1964-01

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65

70 0.95/16* 1.0/16*

75 1.0/19

80 to 100 1.0/21

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.94 0.96 0.98 0.99 1.00 1.00 1.00 1.00 1.00 0

0.92 0.93 0.95 0.96 0.98 0.99 1.00 1.00 1.00 250

0.89 0.90 0.92 0.93 0.95 0.96 0.98 1.00 1.00 500

0.86 0.84 0.81 0.79 0.76 0.74 0.88 0.85 0.83 0.80 0.78 0.75 0.89 0.86 0.84 0.81 0.79 0.76 0.91 0.88 0.85 0.83 0.80 0.78 0.92 0.89 0.87 0.84 0.81 0.79 0.94 0.91 0.88 0.85 0.83 0.80 0.95 0.92 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.88 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.72 0.73 0.74 0.75 0.77 0.78 0.79 0.81 0.82 2250

0.70 0.71 0.72 0.73 0.74 0.75 0.77 0.78 0.79 2500

0.67 0.69 0.70 0.71 0.72 0.73 0.74 0.76 0.77 2750

0.65 0.66 0.67 0.69 0.70 0.71 0.72 0.73 0.75 3000

1.26 1.26 1.26 1.26 1.26 1.26 1.20 1.20 1.20 1.20 1.20 1.20 1.14 1.14 1.14 1.14 1.14 1.14 1.08 1.08 1.08 1.08 1.08 1.08 1.01 1.01 1.01 1.01 1.01 1.01 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.26 1.20 1.14 1.08 1.01 1.00 1.00 1.00 1.00 2250

1.26 1.20 1.14 1.08 1.01 1.00 1.00 1.00 1.00 2500

1.26 1.20 1.14 1.08 1.01 1.00 1.00 1.00 1.00 2750

1.26 1.20 1.14 1.08 1.01 1.00 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.23 1.17 1.11 1.04 1.00 1.00 1.00 1.00 1.00 0

1.26 1.20 1.14 1.08 1.01 1.00 1.00 1.00 1.00 250

1.26 1.20 1.14 1.08 1.01 1.00 1.00 1.00 1.00 500

DM1964-01 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1964-01

-METRIC-

page 2 of 2

345

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°C) 32 Jacket Water Outlet Temperature (°C) 127 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

NAT GAS 36.2 DELTEC 10 80 350

100%

75%

50%

803 770

602 578

402 385

9.49 4.23 5.47 234 142 226 37 21 518 4.54 5.67

9.84 4.34 5.6 196 116 174 34 21 523 4.65 5.82

10.53 4.59 5.93 152 83 123 33 21 526 4.92 6.16

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.3 91 500

1.4 91 500

1.5 91 500

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.9 289 973

2.9 285 958

3.2 286 962

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

5.2 930 1772

5.9 1026 1955

7.1 1137 2166

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.78 70 266

0.90 76 294

1.07 82 325

%

9.0 1.64

8.9 1.63

8.6 1.61

kW kW kW kW kW kW kW kW

2115 803 229 104 107 738 568 134

1646 602 204 87 95 577 443 81

1174 402 173 69 81 414 315 35

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC346

page 1 of 2

DM1967-01

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 70 0.90/18* 0.90/19*

75 1.0/19

80 to 100 1.0/21

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.96 0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 0

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 250

0.91 0.92 0.94 0.95 0.97 0.98 1.00 1.00 1.00 500

0.88 0.85 0.83 0.80 0.78 0.75 0.89 0.87 0.84 0.82 0.79 0.77 0.91 0.88 0.85 0.83 0.80 0.78 0.92 0.89 0.87 0.84 0.82 0.79 0.94 0.91 0.88 0.86 0.83 0.80 0.95 0.92 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.88 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 1.00 0.97 0.94 0.92 0.89 0.86 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.73 0.74 0.75 0.77 0.78 0.79 0.81 0.82 0.83 2250

0.71 0.72 0.73 0.74 0.76 0.77 0.78 0.79 0.81 2500

0.69 0.70 0.71 0.72 0.73 0.74 0.76 0.77 0.78 2750

0.67 0.68 0.69 0.70 0.71 0.72 0.73 0.75 0.76 3000

1.31 1.31 1.31 1.31 1.31 1.31 1.24 1.24 1.24 1.24 1.24 1.24 1.17 1.17 1.17 1.17 1.17 1.17 1.11 1.11 1.11 1.11 1.11 1.11 1.04 1.04 1.04 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.31 1.24 1.17 1.11 1.04 1.00 1.00 1.00 1.00 2250

1.31 1.24 1.17 1.11 1.04 1.00 1.00 1.00 1.00 2500

1.31 1.24 1.17 1.11 1.04 1.00 1.00 1.00 1.00 2750

1.31 1.24 1.17 1.11 1.04 1.00 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.24 1.18 1.11 1.05 1.00 1.00 1.00 1.00 1.00 0

1.29 1.22 1.16 1.09 1.02 1.00 1.00 1.00 1.00 250

1.31 1.24 1.17 1.11 1.04 1.00 1.00 1.00 1.00 500

DM1967-01 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1967-01

-METRIC-

page 2 of 2

347

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°C) 70/32 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

NAT GAS 36.2 DELTEC 10 80 200

100%

75%

50%

803 770

602 578

402 385

9.52 4.36 5.64 242 146 230 38 24 493 4.67 5.84

10.01 4.4 5.68 198 115 178 35 24 501 4.71 5.89

10.74 4.64 6 154 82 126 33 24 501 4.98 6.23

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.7 46 250

0.7 46 250

0.8 46 250

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.8 286 963

2.8 277 933

2.8 261 879

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

7.4 1346 2565

8.7 1552 2957

9.9 1644 3132

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.12 107 385

1.31 123 444

1.49 128 470

%

9.7 1.70

9.7 1.66

9.5 1.64

kW kW kW kW kW kW kW kW kW

2122 803 360 80 0 738 546 80 62

1673 602 349 67 0 576 423 36 44

1197 402 299 53 0 409 298 7 28

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8) Heat Rejection to Aftercooler - stage 2 (3) (7) (8)

-METRIC348

page 1 of 2

DM1954-01

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/18*

70 1.0/20*

75 1.0/22

80 to 100 1.0/24

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.94 0.96 0.98 0.99 1.00 1.00 1.00 1.00 1.00 0

0.92 0.93 0.95 0.96 0.98 0.99 1.00 1.00 1.00 250

0.89 0.90 0.92 0.93 0.95 0.96 0.98 1.00 1.00 500

0.86 0.84 0.81 0.79 0.76 0.74 0.88 0.85 0.83 0.80 0.78 0.75 0.89 0.86 0.84 0.81 0.79 0.76 0.91 0.88 0.85 0.83 0.80 0.78 0.92 0.89 0.87 0.84 0.81 0.79 0.94 0.91 0.88 0.85 0.83 0.80 0.95 0.92 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.88 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.72 0.73 0.74 0.75 0.77 0.78 0.79 0.81 0.82 2250

0.70 0.71 0.72 0.73 0.74 0.75 0.77 0.78 0.79 2500

0.67 0.69 0.70 0.71 0.72 0.73 0.74 0.76 0.77 2750

0.65 0.66 0.67 0.69 0.70 0.71 0.72 0.73 0.75 3000

1.27 1.27 1.27 1.27 1.27 1.27 1.21 1.21 1.21 1.21 1.21 1.21 1.14 1.14 1.14 1.14 1.14 1.14 1.08 1.08 1.08 1.08 1.08 1.08 1.02 1.02 1.02 1.02 1.02 1.02 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.27 1.21 1.14 1.08 1.02 1.00 1.00 1.00 1.00 2250

1.27 1.21 1.14 1.08 1.02 1.00 1.00 1.00 1.00 2500

1.27 1.21 1.14 1.08 1.02 1.00 1.00 1.00 1.00 2750

1.27 1.21 1.14 1.08 1.02 1.00 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.24 1.17 1.11 1.05 1.00 1.00 1.00 1.00 1.00 0

1.27 1.21 1.14 1.08 1.02 1.00 1.00 1.00 1.00 250

1.27 1.21 1.14 1.08 1.02 1.00 1.00 1.00 1.00 500

DM1954-01 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1954-01

-METRIC-

page 2 of 2

349

®

G3512

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°C) 70/32 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

NAT GAS 36.2 DELTEC 10 80 350

100%

75%

50%

803 770

602 578

402 385

9.28 4.15 5.36 227 135 217 37 24 496 4.45 5.56

9.64 4.28 5.52 190 109 169 34 24 501 4.58 5.73

10.4 4.42 5.71 149 78 120 33 24 505 4.75 5.93

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.4 91 500

1.5 91 500

1.5 91 500

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.8 292 983

2.8 281 946

2.9 277 930

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

6.1 1139 2171

7.2 1290 2458

8.5 1437 2738

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.92 87 326

1.08 98 369

1.28 107 411

%

9.3 1.65

9.2 1.63

9.0 1.58

kW kW kW kW kW kW kW kW kW

2068 803 362 80 0 700 525 65 58

1612 602 318 67 0 553 412 30 42

1160 402 285 53 0 389 288 4 26

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8) Heat Rejection to Aftercooler - stage 2 (3) (7) (8)

-METRIC350

page 1 of 2

DM1957-01

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load 100 111

dBA dBA

G3512

Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 1.0/18*

70 1.0/20*

75 1.0/22

80 to 100 1.0/24

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

AIR INLET TEMP.

Altitude Deration Factors

(°C)

50 45 40 35 30 25 20 15 10

0.96 0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 0

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 250

0.91 0.92 0.94 0.95 0.97 0.98 1.00 1.00 1.00 500

0.88 0.85 0.83 0.80 0.78 0.75 0.89 0.87 0.84 0.82 0.79 0.77 0.91 0.88 0.85 0.83 0.80 0.78 0.92 0.89 0.87 0.84 0.82 0.79 0.94 0.91 0.88 0.86 0.83 0.80 0.95 0.92 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.88 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 1.00 0.97 0.94 0.92 0.89 0.86 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.73 0.74 0.75 0.77 0.78 0.79 0.81 0.82 0.83 2250

0.71 0.72 0.73 0.74 0.76 0.77 0.78 0.79 0.81 2500

0.69 0.70 0.71 0.72 0.73 0.74 0.76 0.77 0.78 2750

0.67 0.68 0.69 0.70 0.71 0.72 0.73 0.75 0.76 3000

1.32 1.32 1.32 1.32 1.32 1.32 1.25 1.25 1.25 1.25 1.25 1.25 1.18 1.18 1.18 1.18 1.18 1.18 1.11 1.11 1.11 1.11 1.11 1.11 1.04 1.04 1.04 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.32 1.25 1.18 1.11 1.04 1.00 1.00 1.00 1.00 2250

1.32 1.25 1.18 1.11 1.04 1.00 1.00 1.00 1.00 2500

1.32 1.25 1.18 1.11 1.04 1.00 1.00 1.00 1.00 2750

1.32 1.25 1.18 1.11 1.04 1.00 1.00 1.00 1.00 3000

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.25 1.19 1.12 1.05 1.00 1.00 1.00 1.00 1.00 0

1.30 1.23 1.16 1.09 1.03 1.00 1.00 1.00 1.00 250

1.32 1.25 1.18 1.11 1.04 1.00 1.00 1.00 1.00 500

DM1957-01 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1957-01

-METRIC-

page 2 of 2

351

®

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°C) 70/32 Jacket Water Outlet Temperature (°C) 127 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

NAT GAS 36.2 DELTEC 10 80 200

100%

75%

50%

803 770

602 578

402 385

9.8 4.51 5.83 245 152 239 38 21 514 4.83 6.04

10.06 4.59 5.93 204 122 184 35 21 519 4.92 6.15

10.75 4.79 6.19 157 88 129 33 21 522 5.14 6.42

G3512

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.8 46 250

0.8 46 250

0.8 46 250

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.9 282 948

2.8 271 912

2.9 262 880

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

6.8 1175 2239

7.3 1227 2338

8.5 1333 2541

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.02 91 336

1.10 94 351

1.27 100 382

%

9.4 1.70

9.3 1.68

9.1 1.66

kW kW kW kW kW kW kW kW kW

2184 803 228 104 106 789 598 89 66

1682 602 199 87 93 611 463 43 47

1199 402 175 69 82 432 325 10 29

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8) Heat Rejection to Aftercooler - stage 2 (3) (7) (8)

-METRIC352

page 1 of 2

DM1966-01

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 70 0.95/16* 1.0/16*

75 1.0/19

80 to 100 1.0/21

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

(°C)

50 45 40 35 30 25 20 15 10

0.94 0.96 0.98 0.99 1.00 1.00 1.00 1.00 1.00 0

0.92 0.93 0.95 0.96 0.98 0.99 1.00 1.00 1.00 250

0.89 0.90 0.92 0.93 0.95 0.96 0.98 1.00 1.00 500

0.86 0.84 0.81 0.79 0.76 0.74 0.88 0.85 0.83 0.80 0.78 0.75 0.89 0.86 0.84 0.81 0.79 0.76 0.91 0.88 0.85 0.83 0.80 0.78 0.92 0.89 0.87 0.84 0.81 0.79 0.94 0.91 0.88 0.85 0.83 0.80 0.95 0.92 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.88 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.72 0.73 0.74 0.75 0.77 0.78 0.79 0.81 0.82 2250

0.70 0.71 0.72 0.73 0.74 0.75 0.77 0.78 0.79 2500

0.67 0.69 0.70 0.71 0.72 0.73 0.74 0.76 0.77 2750

0.65 0.66 0.67 0.69 0.70 0.71 0.72 0.73 0.75 3000

1.26 1.26 1.26 1.26 1.26 1.26 1.20 1.20 1.20 1.20 1.20 1.20 1.14 1.14 1.14 1.14 1.14 1.14 1.08 1.08 1.08 1.08 1.08 1.08 1.01 1.01 1.01 1.01 1.01 1.01 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.26 1.20 1.14 1.08 1.01 1.00 1.00 1.00 1.00 2250

1.26 1.20 1.14 1.08 1.01 1.00 1.00 1.00 1.00 2500

1.26 1.20 1.14 1.08 1.01 1.00 1.00 1.00 1.00 2750

1.26 1.20 1.14 1.08 1.01 1.00 1.00 1.00 1.00 3000

G3512

AIR INLET TEMP.

Altitude Deration Factors

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.23 1.17 1.11 1.04 1.00 1.00 1.00 1.00 1.00 0

1.26 1.20 1.14 1.08 1.01 1.00 1.00 1.00 1.00 250

1.26 1.20 1.14 1.08 1.01 1.00 1.00 1.00 1.00 500

DM1966-01 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1966-01

-METRIC-

page 2 of 2

353

®

G3512 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.0:1 Aftercooler Inlet Temperature (°C) 70/32 Jacket Water Outlet Temperature (°C) 127 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

NAT GAS 36.2 DELTEC 10 80 350

100%

75%

50%

803 770

602 578

402 385

9.49 4.23 5.47 234 142 226 37 21 518 4.54 5.67

9.84 4.34 5.6 196 116 174 34 21 523 4.65 5.82

10.53 4.59 5.93 152 83 123 33 21 526 4.92 6.16

G3512

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.3 91 500

1.4 91 500

1.5 91 500

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.9 289 973

2.9 285 958

3.2 286 962

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

5.2 930 1772

5.9 1026 1955

7.1 1137 2166

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.78 70 266

0.90 76 294

1.07 82 325

%

9.0 1.64

8.9 1.63

8.6 1.61

kW kW kW kW kW kW kW kW kW

2115 803 229 104 107 738 568 74 60

1646 602 204 87 95 577 443 36 45

1174 402 173 69 81 414 315 7 27

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8) Heat Rejection to Aftercooler - stage 2 (3) (7) (8)

-METRIC354

page 1 of 2

DM1969-01

®

G3512 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 70 0.90/18* 0.90/19*

75 1.0/19

80 to 100 1.0/21

* Denotes Air Fuel Ratio Control required for Maximum Rating(s) Shown.

(°C)

50 45 40 35 30 25 20 15 10

0.96 0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 0

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 250

0.91 0.92 0.94 0.95 0.97 0.98 1.00 1.00 1.00 500

0.88 0.85 0.83 0.80 0.78 0.75 0.89 0.87 0.84 0.82 0.79 0.77 0.91 0.88 0.85 0.83 0.80 0.78 0.92 0.89 0.87 0.84 0.82 0.79 0.94 0.91 0.88 0.86 0.83 0.80 0.95 0.92 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.88 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 1.00 0.97 0.94 0.92 0.89 0.86 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.73 0.74 0.75 0.77 0.78 0.79 0.81 0.82 0.83 2250

0.71 0.72 0.73 0.74 0.76 0.77 0.78 0.79 0.81 2500

0.69 0.70 0.71 0.72 0.73 0.74 0.76 0.77 0.78 2750

0.67 0.68 0.69 0.70 0.71 0.72 0.73 0.75 0.76 3000

1.31 1.31 1.31 1.31 1.31 1.31 1.24 1.24 1.24 1.24 1.24 1.24 1.17 1.17 1.17 1.17 1.17 1.17 1.11 1.11 1.11 1.11 1.11 1.11 1.04 1.04 1.04 1.04 1.04 1.04 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.31 1.24 1.17 1.11 1.04 1.00 1.00 1.00 1.00 2250

1.31 1.24 1.17 1.11 1.04 1.00 1.00 1.00 1.00 2500

1.31 1.24 1.17 1.11 1.04 1.00 1.00 1.00 1.00 2750

1.31 1.24 1.17 1.11 1.04 1.00 1.00 1.00 1.00 3000

G3512

AIR INLET TEMP.

Altitude Deration Factors

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.24 1.18 1.11 1.05 1.00 1.00 1.00 1.00 1.00 0

1.29 1.22 1.16 1.09 1.02 1.00 1.00 1.00 1.00 250

1.31 1.24 1.17 1.11 1.04 1.00 1.00 1.00 1.00 500

DM1969-01 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM1969-01

-METRIC-

page 2 of 2

355

®

G3508 TA

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 9.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type STANDARD

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 HPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

172 80 1524

100%

75%

50%

392 370

294 278

196 185

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

10.48 3.38 4.37 206 122 199 58 22.5 461 3.68 4.61

11.11 3.44 4.44 181 109 164 59 22.5 432 3.75 4.69

12.36 3.71 4.79 147 78 122 58 22.5 403 4.06 5.07

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

28.8 1431 7907

26.7 1310 7235

24.2 1074 5933

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.5 191 643

2.7 203 683

2.8 191 641

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.0 284 542

3.3 475 904

3.0 377 718

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.30 14 82

0.50 23 136

0.45 18 108

%

2.0 1.12

2.0 1.08

1.6 1.05

kW kW kW kW kW kW kW kW

1140 392 411 48 0 256 197 33

907 294 365 40 0 187 138 20

673 196 313 32 0 124 90 7

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

G3508

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9)

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC356

page 1 of 2

DM5205-00

®

G3508 TA

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 35 40 45 50 55 60 0.55/14 0.55/15 0.55/16 0.55/17 0.90/14 0.90/15 0.90/16

65 1.0/16

70 1.0/18

75 1.0/20

80 1.0/22

83 to 100 1.0/23

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

1.00 0.98 0.95 0.93 0.90 0.87 1.00 1.00 0.97 0.94 0.91 0.88 1.00 1.00 0.98 0.95 0.93 0.90 1.00 1.00 1.00 0.97 0.94 0.91 1.00 1.00 1.00 0.99 0.96 0.93 1.00 1.00 1.00 1.00 0.97 0.94 1.00 1.00 1.00 1.00 0.99 0.96 1.00 1.00 1.00 1.00 1.00 0.98 1.00 1.00 1.00 1.00 1.00 0.99 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.84 0.86 0.87 0.88 0.90 0.91 0.93 0.95 0.96 2250

0.82 0.83 0.84 0.86 0.87 0.89 0.90 0.92 0.93 2500

0.79 0.80 0.82 0.83 0.84 0.86 0.87 0.89 0.90 2750

0.77 0.78 0.79 0.80 0.82 0.83 0.85 0.86 0.88 3000

1.55 1.62 1.69 1.76 1.77 1.77 1.46 1.52 1.59 1.66 1.67 1.67 1.36 1.42 1.49 1.56 1.57 1.57 1.26 1.33 1.39 1.46 1.47 1.47 1.16 1.23 1.29 1.36 1.36 1.36 1.06 1.13 1.19 1.26 1.26 1.26 1.00 1.03 1.09 1.15 1.16 1.16 1.00 1.00 1.00 1.05 1.06 1.06 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.77 1.67 1.57 1.47 1.36 1.26 1.16 1.06 1.00 2250

1.77 1.67 1.57 1.47 1.36 1.26 1.16 1.06 1.00 2500

1.77 1.67 1.57 1.47 1.36 1.26 1.16 1.06 1.00 2750

1.77 1.67 1.57 1.47 1.36 1.26 1.16 1.06 1.00 3000

G3508

AIR INLET TEMP.

Altitude Deration Factors

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.35 1.26 1.16 1.07 1.00 1.00 1.00 1.00 1.00 0

1.42 1.32 1.23 1.13 1.04 1.00 1.00 1.00 1.00 250

1.49 1.39 1.29 1.20 1.10 1.00 1.00 1.00 1.00 500

DM5205-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5205-00

-METRIC-

page 2 of 2

357

®

G3508 TA

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 9.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type CATALYST

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

NAT GAS 36.2 HPG IMPCO 172 80 1524

100%

75%

50%

392 370

294 278

196 185

10.76 3.04 3.93 190 112 186 56 22.5 490 3.34 4.18

11.4 3.03 3.91 179 106 152 56 22.5 445 3.33 4.17

12.81 3.49 4.52 149 79 118 58 22.5 409 3.84 4.8

G3508

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

15.8 822 4539

16.1 831 4588

17.7 802 4430

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

18.4 1567 5277

17.6 1501 5055

20.7 1534 5166

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

3.0 455 868

2.6 395 753

3.6 467 889

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.46 20 131

0.40 18 113

0.54 21 134

%

0.5 1.00

0.5 1.00

0.5 1.00

kW kW kW kW kW kW kW kW

1171 392 448 48 0 256 196 27

930 294 407 40 0 174 129 17

697 196 340 32 0 122 88 7

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC358

page 1 of 2

DM5105-00

®

G3508 TA

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 35 40 45 50 55 60 0.55/14 0.55/15 0.55/16 0.55/17 0.90/14 0.90/15 0.90/16

65 1.0/16

70 1.0/18

75 1.0/20

80 1.0/22

83 to 100 1.0/23

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

1.00 0.98 0.95 0.93 0.90 0.87 1.00 1.00 0.97 0.94 0.91 0.88 1.00 1.00 0.98 0.95 0.93 0.90 1.00 1.00 1.00 0.97 0.94 0.91 1.00 1.00 1.00 0.99 0.96 0.93 1.00 1.00 1.00 1.00 0.97 0.94 1.00 1.00 1.00 1.00 0.99 0.96 1.00 1.00 1.00 1.00 1.00 0.98 1.00 1.00 1.00 1.00 1.00 0.99 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.84 0.86 0.87 0.88 0.90 0.91 0.93 0.95 0.96 2250

0.82 0.83 0.84 0.86 0.87 0.89 0.90 0.92 0.93 2500

0.79 0.80 0.82 0.83 0.84 0.86 0.87 0.89 0.90 2750

0.77 0.78 0.79 0.80 0.82 0.83 0.85 0.86 0.88 3000

1.59 1.66 1.74 1.81 1.82 1.82 1.48 1.56 1.63 1.70 1.71 1.71 1.38 1.45 1.52 1.60 1.60 1.60 1.28 1.35 1.42 1.49 1.50 1.50 1.17 1.24 1.31 1.38 1.39 1.39 1.07 1.14 1.20 1.27 1.28 1.28 1.00 1.03 1.10 1.17 1.17 1.17 1.00 1.00 1.00 1.06 1.07 1.07 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.82 1.71 1.60 1.50 1.39 1.28 1.17 1.07 1.00 2250

1.82 1.71 1.60 1.50 1.39 1.28 1.17 1.07 1.00 2500

1.82 1.71 1.60 1.50 1.39 1.28 1.17 1.07 1.00 2750

1.82 1.71 1.60 1.50 1.39 1.28 1.17 1.07 1.00 3000

G3508

AIR INLET TEMP.

Altitude Deration Factors

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.37 1.27 1.17 1.07 1.00 1.00 1.00 1.00 1.00 0

1.44 1.34 1.24 1.14 1.04 1.00 1.00 1.00 1.00 250

1.52 1.41 1.31 1.21 1.10 1.00 1.00 1.00 1.00 500

DM5105-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5105-00

-METRIC-

page 2 of 2

359

®

G3508 TA

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 9.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type STANDARD

Fuel LHV of Fuel (MJ/Nm3) Fuel System

NAT GAS 36.2 LPG IMPCO

Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

10 80 1524

100%

75%

50%

392 370

294 278

196 185

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

10.48 3.38 4.37 206 122 199 58 22.5 461 3.68 4.61

11.11 3.44 4.44 181 109 164 59 22.5 432 3.75 4.69

12.36 3.71 4.79 147 78 122 58 22.5 403 4.06 5.07

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

28.8 1431 7907

26.7 1310 7235

24.2 1074 5933

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.5 191 643

2.7 203 683

2.8 191 641

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.0 284 542

3.3 475 904

3.0 377 718

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.30 14 82

0.50 23 136

0.45 18 108

%

2.0 1.12

2.0 1.08

1.6 1.05

kW kW kW kW kW kW kW kW

1140 392 409 48 0 256 197 34

907 294 364 40 0 187 138 22

673 196 313 32 0 124 90 7

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

G3508

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9)

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC360

page 1 of 2

DM5107-00

®

G3508 TA

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 35 40 45 50 55 60 0.55/14 0.55/15 0.55/16 0.55/17 0.90/14 0.90/15 0.90/16

65 1.0/16

70 1.0/18

75 1.0/20

80 1.0/22

83 to 100 1.0/23

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

1.00 0.98 0.95 0.93 0.90 0.87 1.00 1.00 0.97 0.94 0.91 0.88 1.00 1.00 0.98 0.95 0.93 0.90 1.00 1.00 1.00 0.97 0.94 0.91 1.00 1.00 1.00 0.99 0.96 0.93 1.00 1.00 1.00 1.00 0.97 0.94 1.00 1.00 1.00 1.00 0.99 0.96 1.00 1.00 1.00 1.00 1.00 0.98 1.00 1.00 1.00 1.00 1.00 0.99 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.84 0.86 0.87 0.88 0.90 0.91 0.93 0.95 0.96 2250

0.82 0.83 0.84 0.86 0.87 0.89 0.90 0.92 0.93 2500

0.79 0.80 0.82 0.83 0.84 0.86 0.87 0.89 0.90 2750

0.77 0.78 0.79 0.80 0.82 0.83 0.85 0.86 0.88 3000

1.55 1.62 1.69 1.76 1.77 1.77 1.46 1.52 1.59 1.66 1.67 1.67 1.36 1.42 1.49 1.56 1.57 1.57 1.26 1.33 1.39 1.46 1.47 1.47 1.16 1.23 1.29 1.36 1.36 1.36 1.06 1.13 1.19 1.26 1.26 1.26 1.00 1.03 1.09 1.15 1.16 1.16 1.00 1.00 1.00 1.05 1.06 1.06 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.77 1.67 1.57 1.47 1.36 1.26 1.16 1.06 1.00 2250

1.77 1.67 1.57 1.47 1.36 1.26 1.16 1.06 1.00 2500

1.77 1.67 1.57 1.47 1.36 1.26 1.16 1.06 1.00 2750

1.77 1.67 1.57 1.47 1.36 1.26 1.16 1.06 1.00 3000

G3508

AIR INLET TEMP.

Altitude Deration Factors

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.35 1.26 1.16 1.07 1.00 1.00 1.00 1.00 1.00 0

1.42 1.32 1.23 1.13 1.04 1.00 1.00 1.00 1.00 250

1.49 1.39 1.29 1.20 1.10 1.00 1.00 1.00 1.00 500

DM5107-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5107-00

-METRIC-

page 2 of 2

361

®

G3508 TA

Gas Generator Set Engine Performance

Engine Speed (rpm) 1200 Compression Ratio 9.0:1 Aftercooler Inlet Temperature (°C) 54 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold WATER COOLED Combustion System Type CATALYST

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

NAT GAS 36.2 LPG IMPCO 10 80 1524

100%

75%

50%

392 370

294 278

196 185

10.76 3.04 3.93 190 112 186 56 22.5 490 3.34 4.18

11.4 3.03 3.91 179 106 152 56 22.5 445 3.33 4.17

12.81 3.49 4.52 149 79 118 58 22.5 409 3.84 4.8

G3508

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

15.8 822 4539

16.1 831 4588

17.7 802 4430

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

18.4 1567 5277

17.6 1501 5055

20.7 1534 5166

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

3.0 455 868

2.6 395 753

3.6 467 889

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.46 20 131

0.40 18 113

0.54 21 134

%

0.5 1.00

0.5 1.00

0.5 1.00

kW kW kW kW kW kW kW kW

1171 392 446 48 0 256 196 29

930 294 406 40 0 173 129 18

697 196 340 32 0 122 88 7

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8)

-METRIC362

page 1 of 2

DM5106-00

®

G3508 TA

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0/--

30 35 40 45 50 55 60 0.55/14 0.55/15 0.55/16 0.55/17 0.90/14 0.90/15 0.90/16

65 1.0/16

70 1.0/18

75 1.0/20

80 1.0/22

83 to 100 1.0/23

(°C)

50 45 40 35 30 25 20 15 10

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 250

1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 500

1.00 0.98 0.95 0.93 0.90 0.87 1.00 1.00 0.97 0.94 0.91 0.88 1.00 1.00 0.98 0.95 0.93 0.90 1.00 1.00 1.00 0.97 0.94 0.91 1.00 1.00 1.00 0.99 0.96 0.93 1.00 1.00 1.00 1.00 0.97 0.94 1.00 1.00 1.00 1.00 0.99 0.96 1.00 1.00 1.00 1.00 1.00 0.98 1.00 1.00 1.00 1.00 1.00 0.99 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.84 0.86 0.87 0.88 0.90 0.91 0.93 0.95 0.96 2250

0.82 0.83 0.84 0.86 0.87 0.89 0.90 0.92 0.93 2500

0.79 0.80 0.82 0.83 0.84 0.86 0.87 0.89 0.90 2750

0.77 0.78 0.79 0.80 0.82 0.83 0.85 0.86 0.88 3000

1.59 1.66 1.74 1.81 1.82 1.82 1.48 1.56 1.63 1.70 1.71 1.71 1.38 1.45 1.52 1.60 1.60 1.60 1.28 1.35 1.42 1.49 1.50 1.50 1.17 1.24 1.31 1.38 1.39 1.39 1.07 1.14 1.20 1.27 1.28 1.28 1.00 1.03 1.10 1.17 1.17 1.17 1.00 1.00 1.00 1.06 1.07 1.07 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.82 1.71 1.60 1.50 1.39 1.28 1.17 1.07 1.00 2250

1.82 1.71 1.60 1.50 1.39 1.28 1.17 1.07 1.00 2500

1.82 1.71 1.60 1.50 1.39 1.28 1.17 1.07 1.00 2750

1.82 1.71 1.60 1.50 1.39 1.28 1.17 1.07 1.00 3000

G3508

AIR INLET TEMP.

Altitude Deration Factors

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.37 1.27 1.17 1.07 1.00 1.00 1.00 1.00 1.00 0

1.44 1.34 1.24 1.14 1.04 1.00 1.00 1.00 1.00 250

1.52 1.41 1.31 1.21 1.10 1.00 1.00 1.00 1.00 500

DM5106-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5900-00 on page 8

DM5106-00

-METRIC-

page 2 of 2

363

®

G3508 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.5:1 Aftercooler Inlet Temperature (°C) 90/54 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

NAT GAS 36.2 DELTEC 10 80 350

100%

75%

50%

505 490

379 368

253 245

9.78 4.46 5.76 246 152 227 60 16 492 4.77 5.96

10.23 4.54 5.86 211 126 175 59 16 509 4.86 6.07

10.97 4.72 6.1 159 88 125 57 16 521 5.06 6.32

G3508

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.8 46 250

0.8 43 250

0.8 42 250

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.6 259 870

2.6 241 811

2.8 245 825

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

5.9 1040 1982

6.7 1117 2129

8.8 1362 2595

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.89 82 298

1.02 85 320

1.32 100 390

%

9.6 1.75

9.2 1.72

8.8 1.67

kW kW kW kW kW kW kW kW kW

1371 505 266 60 0 463 349 37 41

1076 379 234 50 0 370 280 14 29

769 253 195 40 0 268 201 -4 18

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8) Heat Rejection to Aftercooler - stage 2 (3) (7) (8)

-METRIC364

page 1 of 2

DM5231-00

®

G3508 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/--

70 0/--

75 0.95/16

80 to 100 1.0/16

(°C)

50 45 40 35 30 25 20 15 10

0.96 0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 0

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 250

0.91 0.92 0.94 0.95 0.97 0.98 1.00 1.00 1.00 500

0.88 0.85 0.83 0.80 0.78 0.75 0.89 0.87 0.84 0.82 0.79 0.77 0.91 0.88 0.85 0.83 0.80 0.78 0.92 0.89 0.87 0.84 0.82 0.79 0.94 0.91 0.88 0.86 0.83 0.80 0.95 0.92 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.88 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 1.00 0.97 0.94 0.92 0.89 0.86 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.73 0.74 0.75 0.77 0.78 0.79 0.81 0.82 0.83 2250

0.71 0.72 0.73 0.74 0.76 0.77 0.78 0.79 0.81 2500

0.69 0.70 0.71 0.72 0.73 0.74 0.76 0.77 0.78 2750

0.67 0.68 0.69 0.70 0.71 0.72 0.73 0.75 0.76 3000

1.71 1.71 1.71 1.71 1.71 1.71 1.56 1.56 1.56 1.56 1.56 1.56 1.41 1.41 1.41 1.41 1.41 1.41 1.25 1.25 1.25 1.25 1.25 1.25 1.10 1.10 1.10 1.10 1.10 1.10 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.71 1.56 1.41 1.25 1.10 1.00 1.00 1.00 1.00 2250

1.71 1.56 1.41 1.25 1.10 1.00 1.00 1.00 1.00 2500

1.71 1.56 1.41 1.25 1.10 1.00 1.00 1.00 1.00 2750

1.71 1.56 1.41 1.25 1.10 1.00 1.00 1.00 1.00 3000

G3508

AIR INLET TEMP.

Altitude Deration Factors

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.57 1.41 1.26 1.11 1.00 1.00 1.00 1.00 1.00 0

1.67 1.52 1.36 1.21 1.06 1.00 1.00 1.00 1.00 250

1.71 1.56 1.41 1.25 1.10 1.00 1.00 1.00 1.00 500

DM5231-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM5231-00

-METRIC-

page 2 of 2

365

®

G3508 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.5:1 Aftercooler Inlet Temperature (°C) 90/54 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

NAT GAS 36.2 DELTEC 10 80 500

100%

75%

50%

505 490

379 368

253 245

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

9.55 4.2 5.42 231 143 215 60 16 500 4.49 5.62

9.99 4.29 5.54 203 121 167 59 16 515 4.59 5.74

10.81 4.5 5.81 155 86 121 57 16 530 4.83 6.03

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.4 87 500

1.4 83 500

1.5 80 500

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.9 288 967

2.9 276 930

3.3 288 970

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

5.0 891 1697

5.9 985 1876

7.8 1215 2315

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.76 67 255

0.88 72 282

1.17 86 348

%

9.1 1.69

8.6 1.66

8.3 1.61

kW kW kW kW kW kW kW kW kW

1338 505 265 60 0 442 337 29 37

1051 379 231 50 0 352 269 11 27

758 253 193 40 0 259 196 -5 17

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

G3508

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9)

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8) Heat Rejection to Aftercooler - stage 2 (3) (7) (8)

-METRIC366

page 1 of 2

DM5232-00

®

G3508 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0/--

70 0/--

75 0.95/16

80 to 100 1.0/16

(°C)

50 45 40 35 30 25 20 15 10

0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 250

0.92 0.94 0.95 0.97 0.98 1.00 1.00 1.00 1.00 500

0.90 0.87 0.84 0.82 0.79 0.77 0.91 0.88 0.86 0.83 0.80 0.78 0.92 0.90 0.87 0.84 0.82 0.79 0.94 0.91 0.88 0.86 0.83 0.81 0.95 0.93 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.89 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 1.00 0.97 0.94 0.92 0.89 0.86 1.00 0.99 0.96 0.93 0.90 0.88 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.74 0.76 0.77 0.78 0.79 0.81 0.82 0.84 0.85 2250

0.72 0.73 0.74 0.76 0.77 0.78 0.80 0.81 0.82 2500

0.70 0.71 0.72 0.73 0.75 0.76 0.77 0.78 0.80 2750

0.68 0.69 0.70 0.71 0.72 0.73 0.75 0.76 0.77 3000

1.84 1.84 1.84 1.84 1.84 1.84 1.68 1.68 1.68 1.68 1.68 1.68 1.51 1.51 1.51 1.51 1.51 1.51 1.34 1.34 1.34 1.34 1.34 1.34 1.17 1.17 1.17 1.17 1.17 1.17 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.84 1.68 1.51 1.34 1.17 1.00 1.00 1.00 1.00 2250

1.84 1.68 1.51 1.34 1.17 1.00 1.00 1.00 1.00 2500

1.84 1.68 1.51 1.34 1.17 1.00 1.00 1.00 1.00 2750

1.84 1.68 1.51 1.34 1.17 1.00 1.00 1.00 1.00 3000

G3508

AIR INLET TEMP.

Altitude Deration Factors

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.61 1.44 1.28 1.12 1.00 1.00 1.00 1.00 1.00 0

1.73 1.56 1.39 1.23 1.06 1.00 1.00 1.00 1.00 250

1.84 1.68 1.51 1.34 1.17 1.00 1.00 1.00 1.00 500

DM5232-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM5232-00

-METRIC-

page 2 of 2

367

®

G3508 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.5:1 Aftercooler Inlet Temperature (°C) 90/32 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

NAT GAS 36.2 DELTEC 10 80 350

100%

75%

50%

535 519

401 389

268 260

9.44 4.38 5.66 249 153 229 40 20 453 4.69 5.86

9.81 4.45 5.75 212 124 176 38 20 469 4.76 5.96

10.52 4.66 6.02 161 87 126 35 20 476 4.99 6.23

G3508

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.7 45 250

0.8 45 250

0.8 44 250

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.6 259 872

2.6 237 797

2.8 239 805

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

6.7 1254 2390

7.5 1322 2519

9.8 1603 3054

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.01 104 359

1.13 105 378

1.47 124 459

%

10.2 1.77

9.7 1.74

9.4 1.70

kW kW kW kW kW kW kW kW kW

1401 535 260 60 0 449 324 39 60

1093 401 228 50 0 357 259 14 44

782 268 192 40 0 258 185 -5 29

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8) Heat Rejection to Aftercooler - stage 2 (3) (7) (8)

-METRIC368

page 1 of 2

DM5233-00

®

G3508 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0.85/16

70 0.92/18

75 1.0/18

80 to 100 1.0/20

(°C)

50 45 40 35 30 25 20 15 10

0.96 0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 0

0.93 0.95 0.96 0.98 1.00 1.00 1.00 1.00 1.00 250

0.91 0.92 0.94 0.95 0.97 0.98 1.00 1.00 1.00 500

0.88 0.85 0.83 0.80 0.78 0.75 0.89 0.87 0.84 0.82 0.79 0.77 0.91 0.88 0.85 0.83 0.80 0.78 0.92 0.89 0.87 0.84 0.82 0.79 0.94 0.91 0.88 0.86 0.83 0.80 0.95 0.92 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.88 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 1.00 0.97 0.94 0.92 0.89 0.86 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.73 0.74 0.75 0.77 0.78 0.79 0.81 0.82 0.83 2250

0.71 0.72 0.73 0.74 0.76 0.77 0.78 0.79 0.81 2500

0.69 0.70 0.71 0.72 0.73 0.74 0.76 0.77 0.78 2750

0.67 0.68 0.69 0.70 0.71 0.72 0.73 0.75 0.76 3000

1.58 1.58 1.58 1.58 1.58 1.58 1.45 1.45 1.45 1.45 1.45 1.45 1.33 1.33 1.33 1.33 1.33 1.33 1.20 1.20 1.20 1.20 1.20 1.20 1.08 1.08 1.08 1.08 1.08 1.08 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.58 1.45 1.33 1.20 1.08 1.00 1.00 1.00 1.00 2250

1.58 1.45 1.33 1.20 1.08 1.00 1.00 1.00 1.00 2500

1.58 1.45 1.33 1.20 1.08 1.00 1.00 1.00 1.00 2750

1.58 1.45 1.33 1.20 1.08 1.00 1.00 1.00 1.00 3000

G3508

AIR INLET TEMP.

Altitude Deration Factors

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.46 1.33 1.21 1.09 1.00 1.00 1.00 1.00 1.00 0

1.54 1.42 1.29 1.17 1.05 1.00 1.00 1.00 1.00 250

1.58 1.45 1.33 1.20 1.08 1.00 1.00 1.00 1.00 500

DM5233-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM5233-00

-METRIC-

page 2 of 2

369

®

G3508 LE

Gas Generator Set Engine Performance

Engine Speed (rpm) 1500 Compression Ratio 12.5:1 Aftercooler Inlet Temperature (°C) 90/32 Jacket Water Outlet Temperature (°C) 99 Ignition System EIS Exhaust Manifold DRY Combustion System Type LOW EMISSION

Fuel LHV of Fuel (MJ/Nm3) Fuel System Air Fuel Ratio Control Required Minimum Fuel Pressure (kPAg) Methane Number at Conditions Shown Rated Altitude (m) at 25°C Design Temperature

Engine Rating Data

% Load

Engine Power (w/o fan) Generator Set Power (w/o fan)

kW kW

NAT GAS 36.2 DELTEC 10 80 500

100%

75%

50%

535 519

401 389

268 260

9.17 4.17 5.38 237 144 219 40 20 453 4.46 5.57

9.61 4.25 5.49 204 119 169 38 20 475 4.55 5.69

10.3 4.43 5.72 155 83 121 35 20 480 4.74 5.93

G3508

Engine Data Specific Fuel Consumption (BSFC) (1) Air Flow (Wet, @ 25°C, 96 kPaa) Air Mass Flow (Wet) Compressor Out Pressure Compressor Out Temperature Inlet Manifold Pressure Inlet Manifold Temperature (10) Timing (11) Exhaust Stack Temperature Exhaust Gas Flow (Wet, @ stack temperature, 99 kPaa) Exhaust Gas Mass Flow (Wet)

MJ/bkW-hr Nm3/bkW-hr kg/bkW-hr KPAa °C KPAa °C °BTDC °C Nm3/bkW-hr kg/bkW-hr

Engine Emissions Data Nitrous Oxides (NOx as NO2) (9) (Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

1.4 91 500

1.4 89 500

1.5 88 500

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

2.7 287 965

2.7 268 903

3.0 279 939

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

5.7 1089 2075

6.7 1196 2280

8.8 1459 2780

(Corr. 15% 02) (Corr. 5% 02)

g/bkW-hr ppm mg/Nm3

0.86 87 312

1.01 92 342

1.32 108 417

%

9.8 1.73

9.3 1.70

8.9 1.66

kW kW kW kW kW kW kW kW kW

1362 535 258 60 0 423 308 31 56

1070 401 223 50 0 344 253 10 41

765 268 189 40 0 247 178 -6 27

Carbon Monoxide (CO) (9)

Total Hydrocarbons (THC) (9)

Non-Methane Hydrocarbons (NMHC) (9)

Exhaust Oxygen (9) Lambda

Engine Heat Balance Data Input Energy LHV (1) Work Output Heat Rejection to Jacket (2) (6) Heat Rejection to Atmosphere (Radiated) (4) Heat Rejection to Lube Oil (5) Total Heat Rejection to Exhaust (to 25°C) (2) Heat Rejection to Exhaust (LHV to 177°C) (2) Heat Rejection to Aftercooler - stage 1 (3) (7) (8) Heat Rejection to Aftercooler - stage 2 (3) (7) (8)

-METRIC370

page 1 of 2

DM5234-00

®

G3508 LE

Gas Generator Set Engine Performance

Engine Noise Data - at 100% load Noise - Mechanical @ 1 m Noise - Exhaust @ 1.5 m

100 111

dBA dBA

Fuel Usage Guide Derate Factor / Engine Timing vs Methane Number <30 0

30 0/--

35 0/--

40 0/--

45 0/--

50 0/--

55 0/--

60 0/--

65 0.85/16

70 0.92/18

75 1.0/18

80 to 100 1.0/20

(°C)

50 45 40 35 30 25 20 15 10

0.98 0.99 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0

0.95 0.97 0.98 1.00 1.00 1.00 1.00 1.00 1.00 250

0.92 0.94 0.95 0.97 0.98 1.00 1.00 1.00 1.00 500

0.90 0.87 0.84 0.82 0.79 0.77 0.91 0.88 0.86 0.83 0.80 0.78 0.92 0.90 0.87 0.84 0.82 0.79 0.94 0.91 0.88 0.86 0.83 0.81 0.95 0.93 0.90 0.87 0.84 0.82 0.97 0.94 0.91 0.89 0.86 0.83 0.99 0.96 0.93 0.90 0.87 0.85 1.00 0.97 0.94 0.92 0.89 0.86 1.00 0.99 0.96 0.93 0.90 0.88 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

0.74 0.76 0.77 0.78 0.79 0.81 0.82 0.84 0.85 2250

0.72 0.73 0.74 0.76 0.77 0.78 0.80 0.81 0.82 2500

0.70 0.71 0.72 0.73 0.75 0.76 0.77 0.78 0.80 2750

0.68 0.69 0.70 0.71 0.72 0.73 0.75 0.76 0.77 3000

1.67 1.67 1.67 1.67 1.67 1.67 1.54 1.54 1.54 1.54 1.54 1.54 1.40 1.40 1.40 1.40 1.40 1.40 1.27 1.27 1.27 1.27 1.27 1.27 1.14 1.14 1.14 1.14 1.14 1.14 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 750 1000 1250 1500 1750 2000 ALTITUDE (METERS ABOVE SEA LEVEL)

1.67 1.54 1.40 1.27 1.14 1.00 1.00 1.00 1.00 2250

1.67 1.54 1.40 1.27 1.14 1.00 1.00 1.00 1.00 2500

1.67 1.54 1.40 1.27 1.14 1.00 1.00 1.00 1.00 2750

1.67 1.54 1.40 1.27 1.14 1.00 1.00 1.00 1.00 3000

G3508

AIR INLET TEMP.

Altitude Deration Factors

AIR INLET TEMP.

Aftercooler Heat Rejection Factors

(°C)

50 45 40 35 30 25 20 15 10

1.49 1.36 1.23 1.09 1.00 1.00 1.00 1.00 1.00 0

1.58 1.45 1.31 1.18 1.05 1.00 1.00 1.00 1.00 250

1.67 1.54 1.40 1.27 1.14 1.00 1.00 1.00 1.00 500

DM5234-00 Data is intended to be used with Gas Engine Performance Book Parameters – DM5901-00 on page 9

DM5234-00

-METRIC-

page 2 of 2

371

®

LEBQ6169-01 Supersedes LEBQ6169

© 2000 Caterpillar Inc.

PRINTED IN U.S.A.

More Documents from "permono"