This document was uploaded by user and they confirmed that they have the permission to share
it. If you are author or own the copyright of this book, please report to us by using this DMCA
report form. Report DMCA
Overview
Download & View Installation And Operation as PDF for free.
I C Configuration Jumpers (Alarm CardCommunication) Chassis & Digital Ground Connection
B-2
Push-Button Reset
B-2
Remote Voltage Sense
B-3
SCSI ID Header
B-3
SCSI Auxiliary Header
B-3
B-2
H.l 10 Shelf Address
B-3
Fabric Geographic Address
B-4
Minimum Load
B-4
Test Points / FactoryUse Only
B-4
-^
TOC-ii
Revision E
Installation and Operation Manual
GNP Jjfsfcu.
ComputeNode4U cPSB Appendix C
1-800912 Table of Contents
Standard Alarm Card
Overview
C-l
Alarm Card Pinouts
C-l
Alarm Card Command Interface
C-2
Error Message Equations for 3.3V, 5V, 12V, and -12V Thermistor Equations
Appendix D
C-4 C-4 C-5
AlertlNode (Smart Node Alarm Card)
Overview
D-l
User Commands and Interface for the AlertlNode
D-3
Serial Console Login Telnet Login Main Menu Commands and Syntax System Monitoring Commands Alarm Indicators and Settings Network Menu Commands and Syntax AlertlNode Connector Pinouts
Power Requirements (Input/Primary) Output/Secondary Side Power (per Power Supply)
2-2
Chassis Dimensions
2-4
Table 2-5
Table 2-6
Appendix C
Standard Alarm Card
Table C-l
Alarm Port Pinout (|iDB9 - male)
C-l
Table C-2
Serial Port Pinout (DB9 - female)
C-2
Table C-3
"Get" Commands
C-3
Table C-4
"Set" Commands
C-4
Table C-5
Values for Thermistor Equations
C-5
Appendix D
AlertlNode (Smart Node Alarm Card)
Table D-l
Main Menu Commands
D-3
Table D-2
PowerParameters Monitored ("Get" only)
D-4
Table D-3 Table D-4
Power Supply Inhibit ("Get" or "Set") Temperature Sensor ("Get" only)
D-5 D-5
Table D-5
Fan Health ("Get" only)
D-5
Table D-6
Dry Contact Status ("Get" or "Set")
D-5
Table D-7 Table D-8
LED Settings ("Set" only) Clearing Alarms
D-6 D-6
Table D-9
Get AlarmThresholds and ResponseActions D-7
Table D-10
SetAlarm Thresholds and ResponseActions D-8
Table D-l 1
AlarmResponse Actions
D-8
Table D-12
AlarmDefaultSettings
D-9
Table D-l3
General Commands
D-10
Table D-l4
Diagnostic Commands
D-ll
Table D-l5
Telnet Commands
D-ll
Table D-l 6
Ethernet RJ-45 Connector Host Pinout
D-12
Table D-17
RS-232 Serial ^lDB-9 Connector DCE Pinout D-12
Table D-l8
System Alarm (xDB-9 Dry Contact Connector Pinout
Table D-19
TOC-vi
Revision E
2-2
18-Pin Molex Connector Pinout
D-12
D-13
Installation and Operation Manual
GNP
ComputeNode4U cPSB
Appendix E
1-800912 List of Tables
3U cPSB 9-Port Ethernet Switch
Table E-l
Jl Connector Pinouts
E-3
Table E-2
J2 Connector Pinouts
E-4
Table E-3
Port #9 Programming - Jumper Settings Program Strips-Jumper Setting Options
E-5 E-6
Table E-4
Appendix F
3U cPSB 8+2G Ethernet Switch
Table F-l
Main Menu Commands
F-4
Table F-2
Port SettingSummary ("Get" only)
F-4
Table F-3
Link Information ("Get" only)
F-5
Table F-4
Receive/Transmit Options ("Get" or "Set") F-5
Table F-5
Auto-Negotiation Options ("Get" or "Set")
F-5
Table F-6
Data Rate Settings ("Get" or "Set")
F-5
Table F-7
Duplex Mode ("Get" or "Set")
F-6
Table F-8
Flow Control Options ("Get" or "Set")
F-6
Table F-9
Autocast Settings ("Get" or "Set")
F-6
Table F-10
Port Mirroring Options ("Get" or "Set")
F-7
Table F-11
Ingress/Egress Filtering Options ("Set" only) F-7
Table F-12
RS-232 Console Port (RJ-45 Pinout)
Table F-13
10/100Base-Tx Ethernet Port (RJ-45 Pinout) F-8
Table F-14
10/100/1000Base-Tx Ethernet Port
(RJ-45 Pinout)
F-8
F-8
Table F-l 5
J1 Connector Pinout
F-9
Table F-l 6
J2 Connector Pinout
F-10
/^\
Installation and Operation Manual
Revision E
TOC-vii
1-800912 List of Tables
TOC-vih
Revision E
ComputeNode4U cPSB
GNP
Installation and Operation Manual
1-800912
GNP
Chapter
Product Overview ComputeNode4U cPSB
System Features and Capabilities (JO
The ComputcNode4U cPSB is a carrier-grade CompactPCI solution developed for die communications and embedded controls marketplace. Likeall of GNP's products, the ComputeNode4U cPSB has been designed to be compliant with Telcordia GR-1089-CORE Level 3 and Telcordia GR-63-CORE Level 3, for installation in the
Central Office. The ComputeNode4U cPSB can be customized with a wide range of options to meet your specific needs, so the features and capabilities of units van'. The ComputeNode4U cPSB is available with either AC or DC input voltages, with a load-sharing 2+1 redundant power supply configuration. It features GNP's unique compact horizontal design, with a full eight-slot custom cPSB (cPCI Packet Switched Backplane), for use with both front and rear transition cards. Of the eight slots, one is used for dual redundant 3U cPSB Ethernet switches and one is reserved as a system
slot, leaving six cPSB I/O slots for customizing the chassis. A hot-swappable SCSI hard drive provides boot and data storage capability within the chassis, without requiring the use of a card slot. The ComputcNode4U cPSB is designed with a system alarm card that provides monitoring, control status, and alarming features. System Alarm Card
There are two types of alarmcard available for the ComputcNodc4U cPSB— GNP's standard alarm card and the AlertlNode.
The standard alarm card communicates with the system CPU through an RS-232 serial port, and monitors die status of die fans, power supply input & output voltages, temperature, watchdog status, and two dry contact outputs. Status is indicated by a
faceplate tri-color LED, whose current state may be queried remotely. For more information, please see Appendix C. The Smart Node Alarm Card, or AlerdNodc, provides remote connectivity dirough either a serial console or Ethernet. It monitors the status of the fans, power supply input & output voltages, temperature,and three dry contacts. The power supplies, drycontacts, and four faceplate LEDs may be controlled remotely. The AlertlNode also monitors and controls PICMG 2.9-compliant CompactPCI devices. For more information, please see Appendix D. Because neither alarm card requires the use of a cPCI slot, all eight cPCI slots remain available for processors, cPSB Ethernet switches, and I/O. Both alarm cards arc designed to be FRUs (Field-Replaceable Units).
Installation and Operation Manual
Revision E
1-1
1-800912 Chapter 1-Product Overview
ComputeNode4U cPSB
GNP
cPSB Ethernet Switches
GNP's cPSB design features two 3U, layer 2 Ethernet switches, offering HA redundancy in a single 6U cPCI slot There are two types of switch available for the ComputeNode4U cPSB— the 3U cPSB 9-port Ethernet Switch, and the 3U cPSB 8+2G Ethernet Switch.
The 3U cPSB 9-portEthernetSwitch is unmanaged, and provides nine 10/100 Mbps Fast Ethernet ports in a fully non-blocking switching configuration. Two ports are available through rear cPCI connectors,with the backplanerouted such that the other sevenports on eachswitch providea 10/100Base-Tx connection to each of the other cPCI slotsin the system. For moreinformation, please seeAppendix E. GNP's 3U cPSB 8+2G Ethernet Switch provides eight 10/100 Mbps Fast Ethernet ports and two 10/100/1000 Ethernet ports in a fully non-blocking switching configuration. The switch provides a management interface to monitor the statusand control the functions of each port, and has the ability to configure advanced capabilities suchasport mirroring. Threeports areavailable throughthe front and rear faceplates, with the backplane routed such that the other seven ports on eachswitch
provide a 10/100Base-Tx connection to each of the other cPCI slots in the system. For more information,pleasesee Appendix F.
Both switches are designed for usewith GNP's customcPSB systems. Processor Options
Depending on the user's requirements, the ComputeNode4U cPSB may come equipped witha processor. GNP is experienced in providing system integration using SunMicrosystems' processors, Intel-based processors, and Motorola processors. Sun
CP2140, and CP2160 processors to be used in a cPSB system. Sun's CP2040, CP2060, and CP2080 family are available with a 500 MHz
UltraSPARC -He processor and memory from 256MB to 2 GB, depending on the processor used. The CP2140 and CP2160 are available with a 650 MHz
UltraSPARC-IIi processor and memory from 512MB to 3 GB, depending on the processor used. The CP2040 and CP2140 may be used as system slot or satellite processors. The CP2060, CP2080, and CP2160 are dedicated satellite processors. These processors contain either oneor twoPMC (PCI Mezzanine Card) slots, though one PMC slot becomes non-functional when the processor is installed in a cPSB system, due to a conflict of connector signals. Refer to the GNP website (www.gnp.com) or the Sunwebsite (www.sun.com) for complete details. For more information on GNP's rear transition modules, refer to 1-800925 for the CP2x40 cPCI/cPSB RTM, and 1-800926 for the CP2060/CP2080 cPCI/cPSB RTM.
1 -2
Revision E
Installation and Operation Manual
-*^\
GNP
ComputeNode4U cPSB
0m\
1-800912 Chapter1-Product Overview
Intel® Processors (Intel/PTI) Intel's NetStructure productlineincludes the ZT5504, and ZT5524System Master Processor Boards. The ZT5504 uses a 1 GHz Pentium III with memory from 512 MB to 1 GB and an on-board EIDE hard drive. The ZT5524 offers single or dual 993
MHz PentiumIII processors with 1 GB of memory. Intel's ZT5515 Compute Processor Boarduses a 1.2 GHz Pentium 4 processorwith 256 MB to 2 GB of DDR ECC SDRAM.
Allthree of these processors arePICMG 2.16 -compliant, and maybe used as system slotor satellite processors. A variety of reartransition modules are available, providing additional interfaces. Refer to the GNP website (www.gnp.com), Intel's website (www.intel.com), or the PTI website (www.pt.com) for additional information. Motorola
Processors
The Motorola CPIP5385 is available with a1.2 GHz Mobile Pentium® III with up to 2 GB of ECC protectedDDR SDRAM, and is PICMG 2.16 -compliant. Referto the GNP website (www.gnp.com) or the Motorola website (www.motorola.com) for more information.
Power
Both DC and AC power versions of the ComputeNode4U cPSB are available. The standard configuration includes three power supplies for 2+1 redundancy. The following power ratings are listed for an individual power supply:
0^
• DC power supply —200 W*,-48 VDC dual feed input • DC power supply (optional) —250 W+, -48VDC dual feed input • AC power supply —200 W*, 90 to 264 VAC PFC (Power Factor Corrected), single feed input
• AC power supply (optional) —250 W+ 90 to 264 VAC PFC, single feed input Media Drives
There is one hot-swappable SCSI hard drivepositionavailable in the chassis, without requiring the use of a cPCI card slot. In its standard configuration, the ComputeNode4U cPSB contains one hot-swappable SCSI harddrive* in thislocation.
The option is available to use cPCI card slots to install additional hard drives in the ComputeNode4U cPSB: • GNP's hot-swappable 3.5" SCSI drive carrier uses two cPCI card slots, and supports one 3.5"LVD hard drivewith 68-pinwide SCSI. • GNP's single cPCI card slot Compact Media Carrier maybe used to providean additional hard drive and PMC slot to the system. The Compact Media Carrier contains a 2.5" IDE hard drive with a SCSI RTM, designed for use with SCSI processors.
• Note: based on a maximum operatingtemperature of 55° C and a 10% margin for high reliability, the maximum output for a 200W-nominal power supply is 140Wfor a single power supply.
r
f Note: basedon a maximum operating temperature of 55° C and a 10% margin for high reliability, the maximum output for a 250W-nominal power supply is 200W for a single power supply. $ Drive capacity is subject to change depending on market advancement.
Installation and Operation Manual
Revision E
1 -3
1-800912 Chapter 1-Product Overview
ComputeNode4U cPSB
GNP
Software
Linux, Windows, VxWorks, and Solaris operating systems are available, depending on the processorselected. ContactGNP for alternate operating system options. Product Support
As with all GNP products, die ComputcNodc4U cPSB is supported by our team of engineers and customersupport staff. Our engineers are available to work with you to ensure that your ComputeNode4U cPSB is built and tested to GNP's highest quality standards.
Rapid Product Realization Services
GNP offers RapidProduct Realization, a process where we work widi OEMs, service
providers, and network equipment manufacturers to architect, design, test, anddeploy products custom-built to your specifications. GNP also provides documentation, materials management, revision control, and technical support tailored to your needs. Some of the benefits of RapidProduct Realization our customers have found include: •
shorter time-to-market
• more efficient management of resources and production •
cost reduction
• single point of contact • ability to focus more on core competencies
Intended Use
The ComputeNode4U cPSB is intended to provide a compact and cost-effective solution for communications and data networking environments. A modular design allows die flexibility to select different configurations of media drives, processor speed, and memory best suited to meet specific requirements, and facilitates board replacement or upgrade. Combined with theavailability of several different processor speeds, this cPCI platform is ready for deployment for a variety of applications. Examples of typical applications include: • Network Management • Intelligent Network Interfaces •
Enhanced Services
•
Virtual Private Network Server
•
SS7 Platform
• Internet Proxy Server
• Security Firewall •
VoIP
• Wireless (BSC, BSM, HLR, VLR) •
DNS
• Log Processing • Web Hosting •
User Authentication
See the GNP website (www.gnp.com) for the latest product offerings.
1 -4
Revision E
Installation and Operation Manual
1-800912 Chapter
Site Requirements ComputeNode4U cPSB
Operating Conditions The operating conditions for the ComputeNodc4U cPSB may vary depending upon the specific configuration, and the requirements of the cards used. Conditions for general use are provided below. Temperature
The recommended operating temperature range is 5° C to 40° C (41° F to 104° F). The site containing the ComputeNodc4U cPSB should not have an ambient temperature which canexceed 55° C (131 ° F) or drop below-5° C (23° F). When not in operation, the unit should be stored between -40° C and 70° C (-40° F to 158° F). If a unit has been at an extreme temperature, it should be allowed to acclimatize to room temperature before it is powered on. In order to aid in the maintenance of optimum ambient temperatures, the ComputeNode4U cPSB contains four front and two rear hot-swappable coolingfans, with air flow dirough the sides of die unit, from left to right. The four front fans total 184 CFM, and die two rear fans total 92 CFM, for a total system value of 274 CFM. TABLE 2-1
Temperature Requirements
Recommended Operating Temperature Range Maximum Operating Temperature Range (short term)
i
Celsius
Fahrenheit
5° to 40° C
41° to 104° F
-5° to 55° C
23° to 131° I-
Caution: To reduce the risk of overheating, the ComputeNode4U cPSB should be installed in a location that allows airflow through the sides of the unit. Never restrict air flow through the vents.
Humidity
The ComputeNodc4U cPSB has been designed to operate within die following range of humidity: TABLE 2-2
Humidity Limits Humidity
Operating Humidity Range at 35° C
5% to 95% R.I I. non-condensing
Non-Operating Humidity Range at 35° C
5%to95%R.II.
Installation and Operation Manual
Revision E
2 -1
1-800912 Chapter 2 -Site Requirements
ComputeNode4U cPSB
GNP
Altitude
The ComputcNode4U cPSB has been designed to operate within die following altitude range: TABLE 2-3
Altitude Limits
Minimum Operating Altitude
Meters
Feet
-60 m
-197 ft.
Maximum Operating Altitude
4,000 m
13,123 ft.
Maximum Non-Operating Altitude
12,190 m
40,000 ft.
Power and Grounding
When installing the ComputcNode4U cPSB, make sure that it is within die length of the power cord from its intended power source.The power requirements for both DC and AC models are as follows:
TABLE 2-4
Power Requirements (Input/Primary) Minimum
Nominal
Maximum
DC Voltage
-36 VDC
-18 VDC
-72 VDC
AC Voltage
90 VAC
AC Frequency
-17 1 I/.
264 VAC
—
50/60 I Iz
63 Hz
There arc twodifferent models of 200W power supply (each in DC andAC) diat may be used depending on the power needs of your specific system configuration. Both are 200W nominal and have the same total output, but have different distributions
of power across die output voltages. Contact GNP at [email protected] or (800) 735-4467 if you have any questions about your system's power. There is only one option for the 250W powersupplies. Note: Please refer to "Minimum Load" on page B-4 for information on the default
backplane jumper settings for the different power supply options. TABLE 2-5
Output/Secondary Side Power (per Power Supply)
GNP part #
+5V
+3.3V
+12V
-12V
Standard 200W power supply
Minimum Load
1.7 A
0A
0A
0A
AC: 1-503167
Maximum Load''
28 A
23 A
4.5 A
1 A
Alternate 200W power supply
Minimum Load
DC: 1-503281
Maximum Load
20 A
20 A
Minimum Load
0A
0A
1.5 A*
0A
Maximum Load^
40 A
40 A
4A
2 A
DC: 1-503031
no minimum load is required 3.5 A
0.5 A
AC: 1-503280
Optional 250W power supply DC: 1-503832 AC: 1-503831
/
* Minimum load is met cither by the use of a passive load resistor or by the equivalent power consumption from processors, cards, or other devices. f The total combined power for all outputs cannot exceed 140W for a single 200W-nominal power supply.
^ Minimum loadon +12V is necessary to maintain regulation with no load on —12V. This requirement is met by equivalentpower consumption by the chassis' fans. § The total combined power for all outputs cannot exceed 200W for a single 250W-nominal power supply.
Ensure that your ComputeNode4U cPSB unit and the frame holding the unit have an isolated grounding connection.
2-2
Revision E
Installation and Operation Manual
GNP ComputeNode4U cPSB
1-800912 Chapter 2-Site Requirements
Caution: Use proper ESD protection to reduce the risk of damage to your equipment.
Input Supply
Check die system nameplatc ratings to ensure diat diere is no overloading of the supply circuits diat could have an effect on overcurrent protection and supply wiring. Grounding
Reliable grounding of the ComputcNodc4U cPSB mustbe maintained. It is especially important to inspect supply connections to power strips, not just the direct connection to die branch circuit. The -48 VDC supply source must be electrically isolated from any AC source. Either the —48 VDC source must be reliably connected to earth, or the equipment should be connected to a -48 VDC (SELV) source.
The protective grounding lug, located on the rear of die unit, is intended to be connected to the supply circuit ground. DC Units
If the protective grounding lug is connected to die supply circuit ground, all of die following must be met in order to comply with UL safety requirements: • The chassis ground circuit must be directly connected to the DC supply circuit earthing conductor.
• If there is any other equipment connected to the earthed ground of the same DC supply circuit, this equipment must all be located in the same immediate area (such as in adjacent racks) as the ComputcNode4U cPSB. • The groundingpoint of the DC systemmust also be located in the same immediate area.
• The DC supply source mustbe located within the same premises as the equipment it supplies.
•
In the DC supply circuit, there must be no switches or disconnecting devices between the DC supply source and the circuit earthed ground.
Additional Requirements ESD
To reduce die risk of damage to equipment, die ComputeNode4U cPSB should be kept in an ESD protected environment. The unit should be properly grounded at all times; it should be plugged in andits grounding lug should be connected to die supply circuit ground. When performing routine maintenance on die unit, a wrist strap should be used and plugged into one of die ESD jacks, located on the rear panel of the chassis and on the right mounting ear on the front of die unit. Refer to Chapter 3 for diagrams showing the locations of the groundinglug and ESD jacks. If the ComputcNodc4U cPSB is installed in a rack, die ESD jack located on the rear of die unit is unreachable for use when removing and installingcards on die front of the unit. In order to comply with ESD standards, a grounding lug is included as part of the mounting bracket kit. Refer to Chapter 4 for installation instructions.
Installation and Operation Manual
Revision E
2-3
1-800912 Chapter 2 -Site Requirements
ComputeNode4U cPSB
GNP
Caution: Use proper ESD protection to reduce the risk of damage to your equipment.
Dimensions
The ComputeNode4U cPSB occupies an area of 17.2" W x 12.5" D x 7" H (437 x 318 x 178 mm). It is recommended thatyou allow foraccess to both frontand backpanels of the unitwhen installing the ComputeNodc4U cPSB. TABLE 2-6
Chassis Dimensions
Dimension
Millimeters
Inches
1[eight
178 mm
7 inches (4U)
Width
437 mm
17.2 inches
Depth
318 mm
12.5 inches
Rack Mounting
If several rack-mounted units are installed in a rack, the ambient temperature within the rack may be higher dian die room temperature. Care should be taken to install the
units such that each has sufficient room for air inflow and exhaust, to allow proper cooling. Air flow in the ComputeNode4U cPSB is from left to right, as viewed from die front.
Rack-mounted units should beinstalled such that their weight is distributed properly in the rack. Otherwise, the rack may be unstable and create a potential hazard. If rack-mounted units are installed in a closed or multi-unit rack assembly, they may require further evaluation by certification agencies. Electromagnetic Interference
The ComputeNode4U cPSB uses, generates, and can radiate electromagnetic energy. In order to avoid electromagnetic interference issues affecting or caused by this unit, be sure to use adequate EMI protection during its installation and operation.
A
EMI Caution: The ComputeNode4U cPSB may cause or be susceptible to electromagnetic interference (EMI) if it is not installed and used with adequate EMI protection. This device complies with part 15 of die FCC Rules. Operation is subject to the following twoconditions: (1) Thisdevice may not cause harmful interference, and (2) this device must accept any interference received, including interference diat may cause undesired operation.
Shock and Vibration
The ComputeNode4U cPSB has been designed to be compliant widi Telcordia GR-1089-CORE Level 3 and GR-63-CORE Level 3.
2-4
Revision E
Installation and Operation Manual
1-800912 Chapter
System Inventory & Layout ComputeNode4U cPSB
Inventory Additional items are included with your unit based on your specific system configuration. These may include: •
Power cables
• Front grounding lug • Customer-requested third-party cPCI card manuals and device drivers •
Software manuals
•
User's manuals
Please make sure that all equipment has been included. If you would like to order spares, or if you have any questions regarding your order, please email [email protected] or contact GNP at (800) 735-4467 and ask for Customer Support. Features The following diagrams show one possible configuration of die ComputeNode4U cPSB. The cards and drives used in each ComputeNodc4U cPSB will vary depending on customer requirements. Slot #1 is populated with dual redundant 3U cPSB Ethernet switches. Slot #2 is the dedicated processor slot; if a processor is present, it must be located here. Slot #2 is a non-H.110 slot. Slots 3-8 are keyed for H.110.
Installation and Operation Manual
Revision E
3 -1
1-800912 Chapter 3 -System Inventory & Layout
ComputeNode4U cPSB
GNP
Front Panel
FIGURE 3-1 Front Panel of ComputeNode4U cPSB
1. 2.
Two 3U cPSB Ethernet switches (GNP 3U cPSB
10. Fan tray
9-Port Ethernet Switches shown) — slot 1 ' Processor slot (CP2040 pictured) — slot 2 v r '
A. 11. 10 12.
3-8. Filler panels/expansion slots —slots 3-8 9.
3-2
,, . ,, 0/-or a jjHot-swappable SCSI hard drive tray TI _ ,, ,. Hot-swappable power supphes
18. Feed A power input (from left to right, the connections are: V+, V—, frame ground) 19. Feed B power input (from left to right, the connections are: V+, V-, frame ground)
Revision E
3 -3
1-800912 Chapter 3-System Inventory & Layout
ComputeNode4U cPSB
GNP
FIGURE 3-3 Rear Panel of ComputeNode4U cPSB (AC) /2
,3
A
,5
,6
,7
,8
,9
10
,11 12 13
14 15
v17 x18
1.
System alarm card (standard alarm card shown)
2.
ESD jack
3.
Chassis grounding lug
4.
SCSI in for hard drive
5.
SCSI out for hard drive
6.
Rear fan tray
_ /.
_,. , . . . . thumbscrews tor securing or removing rear fan
10-15.Filler panels/expansion slots — slots 3-8 16. AC power input (feed A)
tray
17. Power switch (feed A)
18. Fuse (feed A)
GNP Custom Cards 3U cPSB 9-Port Ethernet Switch
For more information on GNP's 3U cPSB 9-Port Ethernet Switch, please refer to Appendix E. 3U cPSB 8+2G Ethernet Switch
For more information on GNP's 3U cPSB 8+2G Ethernet Switch, please refer to Appendix F. cPSB Sun RTMs
GNP's custom rear transition modules for the Sun CP2040/CP2140 and CP2060/
CP2080/CP2160 are described in 1-800925 (CP2X40 cPCI/cPSB RTM) and 1-800926 (CP2060/CP2080 cPCI/cPSB RTM).
3-4
Revision E
Installation and Operation Manual
L-800912 Chapter
Installation & Maintenance ComputeNode4U cPSB
Backplane Settings Important: Read this section before installing the ComputeNode4U
A
cPSB.
In order for die system to operate correctly, the VIO selectmust be set correcdy for the intended configuration of cards and processors. If your ComputeNode4U cPSB was ordered widi cards installed, or if GNP was
informed of your intended configuration, the VIO select will be pre-set for your system. If the ComputcNode4U cPSB was ordered with no cards present (empty chassis), the setting may need to be altered. Before installing the ComputeNode4U cPSB, it is important to check die user's manuals of the cards intended to be used in the system. Be sure to note die requirements for signalling voltage (+3.3V or +5V). For further information on the backplane headers, please refer to Appendix B.
Caution: Use proper ESD protection to reduce the risk of damage to your equipment.
Installation and Operation Manual
Revision E
4 -1
1-800912 Chapter 4 -Installation & Maintenance
ComputeNode4U cPSB
GNP
VIO Select (+3.3/H-5 V signalling voltage) VIO (+5V or +3.3V) is indicated by screws present in two of the four holes in the VIO select. The upper two holes correspond to +3.3V, and the lower two holes indicate +5V. Both are marked accordingly. The default setting is +5V.
Note: The PI connectors are keyed to correspond to the signalling voltage of the backplane so that cards intended for use with a different voltage cannot be installed. The connectors must be re-keyed if the VIO select is changed. For this reason, the VIO select is not intended to be user-configurable. Please
consult
the
user's
manuals
of the
cards
intended
for
use in
die
ComputcNode4U cPSB system to verify signalling voltage. If the VIO select is set improperly for your intended configuration, please email [email protected] or contact GNP at (800) 735-4467 and ask for CustomerSupport. Note: If your ComputeNode4U cPSB was ordered with cards installed, or if GNP
was informed of your intended configuration, all jumpers will be pre-set appropriately for your system. For further information on the backplane headers, please refer to Appendix B.
4-2
Revision E
Installation and Operation Manual
GNP ComputeNode4U cPSB
1-800912 Chapter 4 -Installation & Maintenance
Mounting
Mounting points on the ComputeNodc4U cPSB are located at die front on each side of the unit, allowing mounting brackets to be used for front mounting. Caution: To avoid personal injury or damage to equipment, use proper
lifting procedures when moving the ComputeNode4U cPSB.
Rack Mounting / Front ESD Lug If the ComputcNode4U cPSB is installed in a rack, the ESD jack located on the rear of die unit is unreachable for use when removing and installing cards on die front of the unit. In order to comply widiESD standards, a front groundinglug for rackmount use is included with the ComputeNodc4U cPSB. It will be shipped in the samebox as the unit, and is identified as part # 1000-617.
The front ESD lug is intended to be installed on the right side mounting bracket. When installing the ComputeNodc4U cPSB, first locate the unpainted area labelled "ESD" around the mounting holesecond from the top on die right bracket. Align die hole in the grounding lug with the mounting hole on die bracket, and slide the bolt used to mount the chassis to die rack through both holes. Proceed as usual. FIGURE 4-2 Front Grounding Lug
O
O
right
ESD
bracket
Align the hole in the grounding lug with the upper mounting hole
unpainted area to ensure proper
grounding
on the bracket. The bolt used to affix the
grounding lug
unit to the frame will
go through both holes.
O
o Caution: Use proper ESD protection to reduce the risk of damage to your equipment.
*The size and type of bolts used to mount the chassis to the frame is dependent upon the frame being used. For this reason, these bolts are not included with the unit. Typically, the bolts used will be #10 or the nearest equivalent. Installation and Operation Manual
Revision E
4-3
1-800912 Chapter 4-Installation & Maintenance
ComputeNode4U cPSB
GNP
Air Flow
When installing the ComputeNode4U cPSB, it is important to allow sufficient room for air flow through die unit, to ensure proper cooling. Air flow in the ComputeNode4U cPSB is through the vents on the sides of the unit, from left to right, as viewed from the front. Avoid blocking the air flow through these vents.
Caution: To reduce the risk of overheating, the ComputeNode4U cPSB should be installed in a location that allows air flow through the sides of the unit. Never restrict air flow through the vents.
I
Fan Maintenance
For ease of maintenance, the fan trays in the ComputeNode4U cPSB are designed to be FRUs (Field-Replaceable Units). If a fan in the system has failed, die whole tray must be replaced. When replacing a fan tray, install the spare witliin one minute of removing the faulty tray, to avoid overheating and possible damage to components. FIGURE 4-3 Replacing a Fan Tray Front Fan Tray:
To replace the front fan tray, you willneed: • ESD-protective equipment • replacement fan tray (GNP part # 1-503242)
fan tray knob 1.
Turn the knob '/4 turn counter-clockwise to release the spring-loaded latch.
2.
3.
4.
Holding the knob in this position, pull die whole fan tray out gendy. Slide the new fan tray straight in. When the fan tray is almost fully in place, turn die knob l/A turn counter-clockwise to release die latch. Holding the knob in this position, slide die fan tray the rest of the wayin, dien turn the knob l/4 turn clockwise to seat the latch. Rear Fan Tray:
thumbscrews
To replace die rear fan tray, you will need: • ESD-protective equipment • replacement fan tray (GNP part # 1-503243)
1. 2. 3. 4.
Unfasten the two thumbscrews to die left of the fan tray, (counter-clockwise) Grasping the fan tray by these two thumbscrews, pull the fan tray out gendy. Slide die new fan tray straightin, seating die connectors gendy. Tighten die two thumbscrews to fasten the fan tray in place, (clockwise)
Caution: To avoid possible damage to components, install a new fan tray within one minute of removing the faulty fan tray.
4-4
Revision E
Installation and Operation Manual
GNP ComputeNode4U cPSB
1-800912 Chapter 4 -Installation & Maintenance
cPCI Card Installation Card Alignment
a
Caution: cPCI backplane connector pins are fragile and are easily bent. Proper alignment of cPCI cards is crucial in order to avoid bending backplane pins when inserting cards. All GNP backplanes are designed with A/B shroud connectors. These aid in die proper alignment of cPCI cards. Many (but not all) cPCI cards have alignment features on their connectors that are designed to fit into the A/B shrouds. This helps to maintain propercard alignment during insertion, helping to preventdamage to die backplane pins.
Note: Bent backplane pins are not covered under warranty. FIGURE 4-4 Backplane Connectors (Front)
Before inserting a cPCI card into the ComputcNode4U cPSB, examine the card's connectors and note whether the connectors have alignment features. Because die
placement of alignment features (ifany) varies among manufacturers, a few examples of card connectors are shown in the following figures.
If the connectors have multiple alignment features, be sure to ahgndiem carefully widi the A/B shrouds on the backplane connectors when inserting the card.
If no alignment features are present, or if die card has only one alignment feature, extreme care is needed in aligning the card connectors with the backplane connectors.
Always hold a cPCI card level and keep the card's faceplate parallel with the front of the chassis when inserting and removing die card. FIGURE 4-5 Examples of cPCI Card Connectors (Front)
Alignment features
Single alignment
M\iii^\M^ffffiBffl\ ffirrffifl
featureuse extra caution
££=?.
Installation and Operation Manual
Revision E
4 -5
1-800912 Chapter 4 -Installation & Maintenance
ComputeNode4U cPSB
GNP
FIGURE 4-6 Backplane Connectors (Rear)
<^_A/B shrouds^)
• •• \
"i •
». »
{/
:<*"A*M I I n>IIiIII' lit W W I
FIGURE 4-7 Examples of cPCI RTM Connectors (Rear)
Alignment features
Single alignment feature — use extra caution
No alignment features —
use extra caution
Card Latches
There are several types of card latches commonly used. They all fit to the extrusions at the edges of the card slots in the same way, and each has a captive screwtoward the outside edgeof the latch, to hold the card firmly in place in the chassis. Somelatches arc designed with an additional locking mechanism, with various types of lock releases. Some of the more common types arc shown below. The following scries of diagrams showcard latches as the card is being removed from the chassis. The first of the pair of images shows die closed latch, with the card in the
unit. The second shows die open latch, when the card is unseated and is ready to be removed from die slot.
Before removing a card, always ensure that the screw has been loosened and is completely free from the chassis.
When installing or removing a card, the latches must always be in die open position. FIGURE 4-8 Standard Latch (no locking mechanism) To remove the
Closed:
card, first
Open:
ensure that the
11 IS 1 ££ 1
screws arc
completely free from the
chassis, then
press out on the latches to
release the card.
4-6
Revision E
II
m
Installation and Operation Manual
GNP ComputeNode4U cPSB
1-800912 Chapter 4 -Installation & Maintenance
FIGURE 4-9 Latch with Compression Catch compression
Closed
catch
To open the latch, first ensure that the
screw is completely free from the
chassis, then squeeze the latch and press out to release the catch.
FIGURE 4-10 Latches with Lock Release Buttons
Closed:
lock release button
To open this latch, first ensure that the
screw is completely free from the
chassis, then push the lock release
button. There will be an audible click as the lock is released.
lock release button screw
location
(not shown)
To open this latch, first ensure that the
screw is completely free from the
chassis, then push the lock release
button. There will be an audible click as
the lock is released.
lock release button screw
To open this type of latch, first ensure that the screws are
completely free from the chassis. Push the lock release buttons towards the outside
edges of the card while pulling out on the latches.
Installation and Operation Manual
Revision E
4-7
1-800912 Chapter 4 -Installation & Maintenance
ComputeNode4U cPSB
GNP
Card Installation
For proper insertion of cards into the ComputcNode4U cPSB, the following guide is recommended:
1.
Inspect die card. If it is new, it may come with protective plastic covers on die latches' captive screws. These will need to be removed before the card can be installed.
A
2.
Ensure that the card's latches arc open. The latches may have a locking mechanism that will need to be released in order to open die latches. For information on common latch lockingmechanisms,refer to "Card Latches" on page 4-6.
3.
Holding the card by its latches, align the card in the ComputeNode4U cPSB's card guides. For information on proper card alignment, please see "Card Alignment" on page 4-5. It is a good idea to double-check at this point that the latches are open.
Caution: Inserting a cPCI card without verifying its correct alignment with the backplane connectors will result in permanent damage to the backplane pins. 4.
Slide the card gendy straight into the slot, maintainingproper card alignment. Keep the card level and its faceplate parallel with the front of die chassis. Do not apply too much pressure, particularly if you feel resistance. You should feel die pin connectors on the rear of the card meet the backplane.
5.
Continue to slide die card into the slot until the latches touch the extrusions on eidier side of die slot.
6.
Press in on the latches to guide the card the rest of the way into the slot and
7.
lock it into place. After insertion, tighten the captive screws on the latches.
FIGURE 4-11 Card Installation Details extrusion
captive screw
The notch in the latch will
butt up against the extrusion when the card is fully seated.
Once the card is fully seated, press in on the latches to
guide the card the rest of the way into the slot
4-8
Revision E
Installation and Operation Manual
GNP ComputeNode4U cPSB
1-800912 Chapter 4 -Installation & Maintenance
cPCI Card Removal To remove a card from the ComputeNode4U cPSB:
1.
Unscrew the captive screws on the latches. Ensuringthat these screws are completely free before trying to remove the cardmay preventdamage to the card and the ComputeNode4U cPSB chassis.
2.
If the latches have a locking mechanism, pressit to unlockthe latches. Refer to "CardLatches" on page 4-6,for information on common latchlocking mechanisms.
3.
Press the latches open.This will unseatthe card from the pin connectors at the rear of the card slot.
4.
Holding the cardbyits latches, pullthe cardgendy straight out of the slot, keeping the cardlevel and its faceplate parallel with the front of the chassis.
j0^\
/f*V
Installation and Operation Manual
Revision E
4-9
1-800912 Chapter 4 -Installation & Maintenance
ComputeNode4U cPSB
GNP
Power Supply Replacement To replace a power supply, you will need: • flathcad screwdriver (3.5 mm or equivalent) • replacement power supply (refer to Table 2-5 for the GNP part numbers of the available power supplies)
1.
Using a flathead screwdriver, unscrew die screws on the upper right and upper left corners of die power supply to be replaced. Make sure that the screws are completely free from the chassis.
2.
Pressing the latch's lock release button to the left, pull out on the latch to unseat die power supply from the chassis.
3.
Holding the sides of the power supply, pull it gendy straight out of the chassis.
4.
Verify that the replacement powersupply is of die correct type for the unit. The chassis has power supply keys installed at the front of die left card guides. The power supplies have keys located behind dieir latches. DC units and power supplies have gray keys installed horizontally. AC units and power supplies have red keys installed vertically. If you accidentally try to insert an incorrect type of power supplyinto die unit, the keys willnot mesh, preventing the latches from being closed. Do not force.
FIGURE 4-12 Power Supply Keying (AC shown) Chassis keys (at front of left card guide)
Keying:
gray (horizontal) = DC red (vertical) = AC
Power supply keys (located behind latch)
5.
Holding the sides of the replacement power supply, align its card (green) in die card guides on eidier side of die slot.
6.
Keeping the replacement power supply level, slideit gendy straight into the unit. If you feel resistance, do not force the power supply into the chassis. Push in on the latch to seat the power supply into die chassis. Fasten the screws on the upper right and upper left corners of the power supply.
7.
8.
4-10
Revision E
Installation and Operation Manual
1-800912
GNP
Chapter
Operation ComputeNode4U cPSB
Powering Up To power up the ComputeNode4U cPSB, first ensure diat power is supplied to the unit and that all cabling is installed. For DC units, press the circuit breakers for Feed A and Feed B, located on die rear
panel of die ComputeNode4U cPSB. The circuit breakers may be turned on in any order.
For AC units, press the power rocker switch, located on die rear panel of the ComputeNodc4U cPSB.
The boot-up process will differdepending on the type of processor used.
If the system is running Linux, a temporary password will be assigned. Unless a specific password is requested, die pre-set password willbe 123456. Powering Down To force a hard shutdown of die ComputcNode4U cPSB, first make sure no applicadons are running, in order to prevent loss of data. For DC units, press the circuit breakers for Feed A and Feed B to turn off die unit. The circuit breakers maybe turned off in any order. These circuit breakers are located on the rear panel of die ComputeNodc4U cPSB.
For AC units, press die power rocker switch to turn off the unit. The power rocker switches are located on the rear panel of the ComputeNode4U cPSB. System Monitoring & Alarming Depending upon what configuration was ordered, the ComputcNode4U cPSB will contain eidier the standard alarm card or the AlertlNode (Smart Node Alarm Card).
The standard alarm card monitors die status of die fans, powersupply input & output voltages, temperature, watchdog, and two dry contact outputs. Status is indicated by a faceplate tri-color LED, whose current state may be queried remotely. The alarm card communicates with die system CPU through an external serial port. For more informadon on the standard alarm card, please refer to Appendix C.
The AlertlNode monitors die status of the fans, power supply input & output voltages, temperature, and diree dry contacts. The power supplies, dry contacts, and four faceplate LEDs may be controlled remotely. The AlertlNode has the ability to monitor and control IPMI-compliant devices. It provides remote connectivity through eidier a serial console or Ethernet. For more information, please refer to Appendix D.
• Minimum memory 256 MB. Memoryavailable from 256 MB to 2 GB. When used in a cPSB system, no PMC slot available.
• • • •
USB: two rear ports Serial: two rear RS-232 I/O outputs Ethernet: two rear panel 10/100 Kthernct ports, one with front panel access SCSI: two rear panel ultra-wide SCSI-2 single-ended, 40 MB/s
• Mouse/Keyboard: rearpanel — PS/2 compatible SPARCengine™ CP2060 with UltraSparc™ IIc@ 500 MHz • 1,2 Integrated 4-way 256 KB cache • 512 MB on-board memory. When used in a cPSB system, allows one PMC card. • USB: one rear port, optional second port with PIM installed • Serial: two rear RS-232 I/O outputs • Kthernct: two rear panel 10/100 Kthernct ports SPARCengine™ CP2080 with UltraSparc™ IIe@ 500 MHz • L2 Integrated 4-way 256 KB cache • Minimum memory 256 MB. Memory available from 256 MB to 2 GB. When used in a cPSB system, no PMC slot available.
• USB: one rear port, optional second port with PIM installed • Serial: two rear RS-232 I/O outputs • Kthernct: two rear panel 10/100 Kthernct ports SPARCengine™ CP2140 with UltraSparc™ IIi@ 650 MHz • L2 Integrated 4-way 512 KB cache
• Minimum memory 512MB. Memory available from 512 MB to 2 GB. When used in a cPSB system, no PMC slot available.
• USB: two rear ports • Serial: two RS-232 I/O outputs with front or rear panel access • Kthernct: two rear panel 10/100 Ethernet ports, one with front panel access • SCSI: two rear panel ultra-wide SCSI-2 single-ended, 40 MB/s • Mouse/Keyboard: rear panel — PS/2 compatible SPARCengine™ CP2160 with UltraSparc1MIIi@ 650 MHz • L2 Integrated 4-way 512 KB cache • 1 GB on-board memory. When used in a cPSB system,allowsone PMC card. • USB: one rear port, optional second port with PIM installed • Serial: two RS-232 I/O outputs with front or rear panel access • Kthernct: two 10/100 Kthernct ports with front or rear panel access
* Specifications are subject to change. f GNP's custom rear transition modulesallow Sun's CP2040, CP2060, CP2080, CP2140, and CP2160processorsto be usedin a cPSB setting.
^ For the latest processor information, please refer to the manufacturer's website. Installation and Operation Manual
Revision E
A-l
1-800912 Appendix A -Specifications
ComputeNode4U cPSB
GNP
Processor Options —Intel/PTI*
^
ZT5504 System Master Processor Board with 1GHz Pentium® III processor • L2 256KB cache; integrated LI & L2 cache memory • Minimum memory 512MB; up to 1 GB.Contains one on-board EIDE hard drive. Allows one PMC card.
• • • • • •
USB: two front panelports Serial: two rearports, one with front panelaccess Ethernet two front panel10/100 Ethernetports VGA: 15-pinD-shell VGAport Mouse/Keyboard: PS/2-style Floppy: PC/AT compatible (not on panels)
(Optional certification available; consult factory) System Alarm Card Options Standard Alarm Card
• • • • •
Two dry contact relayoutputs on p.DB-9 Power backplane system monitors +3.3V, +5V, +12V,-12V Power input monitoringwith two digital inputs Power supply fail signal in the event of a power fail condition Fan monitoring— three digital inputs for the status of each systemfan
• Status LED output— tri-color LEDon alarm cardfaceplate canbe usedto signal status Smart Node Alarm Card (AlertlNode) • Input feeddetection and CompactPCI voltage monitoring • Power supply monitoring and control • Fan detection and temperature sensor • IPMI-compliant device monitoring and control • User-configurable event control • Protocol support: IPMI v 1.5, Telnet, TFTP, DHCP, RMCP Mechanical Specifications Height 4U (178 mm/7 in.) Width 437 mm (17.2in.) Depth 318 mm (12.5 in.) Enclosure Rack Sizes
Mounting Points
19in. rack-mount (EIA& Telco racksupport)and customrequirements Mounting brackets for front support Custom options available.
Environmental Specifications Temperature Range Operating: -5° C to 55° C Storage: -40° C to 70° C Flammability Rating UL94-V0 System Cooling Lcft-to-right airflow Six system tans providing 274 CFM
MTBF (Mean Time Between Failures) DC chassis AC chassis Warranty and Service Standard Warranty Service Plans
Eight 10/100Base-T/Tx; one rear-panel, sevenrouted to the backplane Two 10/100/lOOOBasc-T/Tx;one front-panel, one rear-panel One RS-232Console port, accessible from the front or rear Switching Fully non-blocking full wire speed Layer2 fabric Management Interface Port Control Interface
Enable/disableport Enable/disable auto-negotiation Selectport speed (10 or 100 or 1000 Mbps) Toggle betweenhalfand fullduplex Enable/disable flow control Enable/disable autocast
Layer 2 Features
Retrieveport statistics Port mirroring
MAC Address Learning
4K Table
Packet Buffer
256K
Dimensions Switch
RTM
3U (5.25in., or 133.35mm) x 4HP (0.8 in., or 20.32 mm) designed on a 3U cPCI front accesscard with the dimensions 100 mm (3.94 in.) x 160 mm (6.30 in.) 100 mm (3.94 in.) x 80 mm (3.15 in.)
LEDs
Front panel
Link/activityLED for each port Blue hot-swap indicator Green power indicator
VIO Select (+3.3/+5 V signalling voltage) VIO (+5V or +3.3V) is indicated by screws present in two of the four holes in the VIO select. The upper two holes correspond to +3.3V, and die lower two holes indicate +5V. Both are marked accordingly.
The default setting is +5V.
Note: The PI connector is keyed to correspond to the signalling voltage of the backplane so that cards intended for use with a differentvoltage cannot be installed. The connectors must be rc-keyed if die VIO select is changed. For diis reason, the VIO select is not intended to be user-configurable. Please
consult
die
user's
manuals
of the
cards
intended
for
use
in
the
ComputeNodc4U cPSB system to verify signalling voltage. If the VIO select is set improperly for your intended configuration, email [email protected] or contact GNP at (800) 735-4467 and ask for Customer Support.
Installation and Operation Manual
Revision E
B -1
1-800912 AppendkB -Backplane Jumper
ComputeNode4U cPSB
GNP
Jumper Settings If you would like additional information about thebackplane headers, or if you think you may need to change any of the following jumper settings, please email [email protected] or contact GNP at (800)735-4467 and ask for Customer Support.
I C Configuration Jumpers (Alarm Card Communication) Headers J0001 and J0002 define the setting for the I2C management bus through the system. Bothheaders need aninstalled jumper across the same pairof pinsfor the bus to work.
AlertINode (Smart Node Alarm Card) The AlertlNode (Smart Node Alarm Card) communicates with the system over IPMB. In asystem with anAlertlNode, headersJOOOl andJ0002 should have jumpers installed on pins 1-2to enable IPMB. If a ComputeNode4U cPSB is orderedwith an AlertlNode, this is the default that will be set at GNP. JumperLocation
Description
Pins 1-2
IPMB
Pins 3-4
SMB
Pins 5-6
Processor-specific rC
no jumpers installed
communication through externalserialport
Standard Alarm Card
The standard alarm carddoes not supportIPMB or SMB signals; its communication is through an external serial port. In a system with a standard alarm card, headers JOOOl and J0002 should have no jumpers installed on them, or the alarm card will
not be able to communicate with therestof the system. If a ComputeNode4U cPSB is ordered with a standard alarm card, this is the default that will be set at GNP. Jumper Location
Description
Pins 1-2
IPMB
Pins 3-4
SMB
Pins 5-6
Processor-specific I C
no jumpers installed
communication through external serial port
Chassis & Digital Ground Connection
By default, the chassis and digital grounds are not connected. To connect chassis ground to digital ground, a screw (GNP part #1-400094-10) needsto be installed at locationHI6, marked by a digital ground symbol. Push-Button Reset
J0102 is a 2-pin headerwhere a normally open switch may be installed to perform a reset on the system slotboard,which in turn wouldreset the rest of the system using the PCI RST# signal The defaultsettingis with no switchinstalled.
The backplane cansense thevoltage level of 3.3V, 5V, 12V, anddigital ground either remotely or locally at the power supply. To enable remote sensing, a jumper needs to be installed on J0306. Description
Pins
Default
1-2
12V
jumper on (enabled)
3-4
3.3V
jumper on (enabled)
5-6
5V
jumper on (enabled)
7-8
Digital GND
jumper on (enabled)
SCSI ID Header
J0203 allows the backplane to set the SCSI ID[3..0] of the drive. The default setting is with no jumpers present, or SCSI ID 0. Jumper Setting
Jumper Setting
SCSI ID
i
2
3
SCSI ID
• = on,Q = off
• = on, Q = off
2
3
0
0
i
0
•
•
a
a
Q
a
•
•
•
•
•
1
•
•
•
•
9
•
•
•
a
2
•
a
•
•
10
•
•
•
•
3
•
a
•
•
11
•
•
a
a
4
•
•
•
•
12
a
•
•
•
5
•
•
a
•
13
•
•
•
a
6
•
•
•
a
14
•
•
•
•
7
•
•
•
•
15
•
8
SCSI Auxiliary Header
J0204allows the backplane to setcertain auxiliary controls of the SCSI drive. Installing a jumper enables auxiliary control of the function (listed below). With no jumper installed, auxiliary control of the function is disabled. The default setting is with no jumpers installed. Pins
:
Description
Default
Remote Start
jumper off (disabled)
3-4
DelayedStart
jumper off (disabled)
5-6
ActivityLED
jumper off (disabled)
7-8
Not used
1-2
—
H.110 Shelf Address
J0101 is a 10 pin header which allows the backplane to set the shelf address (ADDR[4..0]) of the H.110 bus. Installing a jumper will set the address bit to zero. With no jumper installed, the bit is set to one.The default setting is with no jumpers installed.
Description
Pins
Default
1-2
ADDR4
jumper off
3-4
ADDR3
jumper off
5-6
ADDR2
jumper off
7-8
ADDR1
jumper off
9-10
ADDR0
jumper off
Installation and Operation Manual
Revision E
B-3
ComputeNode4U cPSB
1-800912 Appendix B -Backplane Jumper
GNP
Fabric Geographic Address
J9000is a 10 pin header which allows the backplane to set the geographic address of fabric A (on the left sideasviewed from the front; the rightsideas seen from the rear). The default address is 30 (no jumper installed).
J9001 is a 10pin header which allows the backplane to set the geographic address of fabric B (ontheright side asviewed from the front; theleftside asseen fromtherear). The default addressis 31 (no jumper installed).
Installing a jumper will set the address bit to zero. Withno jumper installed, the bit is set to one. The default settingis with no jumpersinstalled. J9001 (Fabric B Geographic Address)
J9000(Fabric A Geographic Address) Description
Pins
Pins
Description
1-2
1
1-2
1
3-4
GeographicAddress3
3-4
Geographic Address 3
5-6
GeographicAddress2
5-6
Geographic Address 2
7-8
GeographicAddress 1
7-8
Geographic Address 1
9-10
0
9-10
1
Minimum Load
Installing jumpers across J0900 (5V) andJ0901 (3.3V) enables the power supplies to see a minimum load, which is necessary for the standard 200W power supplies to remain regulated. These jumpers are not used in systems with the alternate 200W power supplies or the optional 250W power supplies. The default settingsare as follows: Power Supply Option
Default Setting ofHeaders J0900 and J0901
Standard 200W power supply
jumpers installed on both J0900 (5V) andJ0901 (3.3V)
DC: 1-503031 AC: 1-503167
Alternate 200W power supply DC: 1-503281
jumpers not installed on bothJ0900(5V) andJ0901 (3.3V)
AC: 1-503280
Optional 250W power supply DC: 1-503832
jumpers not installed on bothJ0900(5V) andJ0901 (3.3V)
AC: 1-503831
Test Points / Factory Use Only Headers J0303, J0304, andJ0305 contain backplane testpoints. Theyaredesigned for in-factory testing only and should nevet have any jumpers installed on them. J0003 andJ0004 together form an IPMB power connector which connects 5Vpower to IPMB bus, and is intended for in-factory testinguse only.
B-4
Revision E
Installation and Operation Manual
**%.
1-800912 Appendix
Standard Alarm Card ComputeNode4U cPSB
Overview The standard alarm card monitors the status of die fans, power supply input & output
voltages, temperature, watchdog, and two dry contact outputs. Status is indicated by a faceplate tri-color LED, whosecurrent state may be queried remotely. The alarm card faceplate is locatedon the rear panel of the unit, in the upper left-hand corner, as seen from the rear of the unit. The alarm port provides access to the dry contact signals, and the serial port provides an interface for the host CPU. FIGURE C-l Alarm Card Rear Faceplate
alarm port (uDB-9)
tricolor
status LEI
serial port (DB-9)
Alarm Card Pinouts TABLE C-l
Alarm Port Pinout (uDB-9 — male)
Pin#
Pin Function
1
R ALARM COM
2
R ALARM NO
3
NC
4
I. ALARM NC)
5
L ALARM COM
6
R ALARM NC
7
NC
8
NC
9
1. ALARM NC
12
Installation and Operation Manual
Revision E
3
4
5
C-l
ComputeNode4U cPSB
1-800912 Appendix C -Standard Alarm Card
TABLE C-2
GNP
Serial Port Pinout (DB-9 — female) Pin Function
Pin# 1
DCD
2
TX
3
RX
4
dtr
5
gnd
6
dcr
7
rts
8
CTS
9
NC
Alarm Card Command Interface FIGURE C-2 Data Flow Diagram for the Software
^^r PIC
Commands
^"
from serial port
^^^^ ^>
A/D (voltages & temperatures)
\>
Fans and power supply faults
firmware
x\
i
LEDs
Output status
Dry Contacts
The settings for the serialport are: Bit per second = 9600 Data
bits
=
8
Parity = none
Stop bits = 1 Flow Control
=
xoff/xon
This is a DCE (Data Communications Equipment) device.
C-2
Revision E
Installation and Operation Manual
GNP ComputeNode4U cPSB TABLE C-3
Description
1-800912 Appendix C -Standard Alarm Card "Get" Commands
Expected Result from Alarm board
Command to alarm board
serial port (followed by Enter) Get all the
gsts
[gsts.aa.bb.ccdd.e.f.g.h.i.j.k.l.mm.oo]
status from the
aa: 3.3 V Reading bb: 5 V Reading cc: 12 V Reading dd: -12 V Reading
alarm board
aa,bb, cc,and dd are in hexadecimal (these values will be usedin the voltage equations. Seethe section "Equationsfor 3.3V, 5V, 12V, and -12V"on pageC4 for details of the voltageequations.) e: Fan 1 status
e = 0 (bad),e =1 (good) £ Fan 2 status
f=0(bad),f=l(good) g: Fan 3 status g = 0 (bad),g =1 (good) h: Power Supply Fail 1 h = 0 (good), h = 1 (fail)
i: PowerSupply Fail2 i = 0 (good),i = 1 (fail) j: Power SupplyFail 3 j = 0(good),j = l(fail) k DC Power FcedA
k = 0 (bad), k = 1 (good) 1: DC Power FeedB
1= 0 (bad),1= 1 (good) mm: Temperature Reading mm is in hexadecimal(this value will be used in the temperature equations. See the section'Thermistor Equations" on page C-5 for detailsof the temperature equations.) oo: All Alarm Card output status oo is in hexadecimal.
Bit 0 = dry contact (0 = off; 1 = on) Bit 1 = red LED (0 = off; 1 = on) Bit 2 = green LED (0 = off; 1 = on) Bit 3 = watchdog (0 = off; 1 = on) Bit4 = watchdog (0 = not trigger, 1 = trigger) Get firmware
gver
Reset watchdog
[gver.x.x] x.x = Firmware Version on the alarm board
version rswd
[rswd.l]
Resetthe watchdog. The watchdogstatus bit willset to 0 but it willnot reset the drycontactand the red LED which the watchdog turns on. The watchdog status bit willnot be cleareduntil the rswd is being called
Installation and Operation Manual
Revision E
C-3
ComputeNode4U cPSB
1-800912 Appendix C -Standard Alarm Card TABLE C-4
Description
GNP
"Set" Commands
Expected Result from Alarm board
Command to alarm board
serial pott (followed by Enter) [sl0.0]
sl0.0
Set Red Led off
Set red LED off
[sl0.1]
slO.l
Set Red Led on
Set red LED on
Set Green Led off
[sll.O]
si 1.0
Set greenLED off Set Green Led on
[•11.11 Set green LED on
sll.l
Set Dry off
sdy.O
[sdy-OJ Set dry contactoff
Set Dry on
sdy.l
[sdy.l] Set dry contact on
The dry contactis on by defaultto indicate failure due to powerloss. Set wd off
[swd.0]
swd.O
Set watchdogoff Set wd on
[swd.X]
swd.X
X = 1..6 1 = 1 min 2=2min 3 = 3 min 4 = 4 min 5 = 5 min 6 = 6 min
If the watchdogis triggered by no activity coming from the serial port after X minutes, the dry contact and red LED in the alarm board will be activated.
Error Message
The error message format is: [#Error]
Equations for 3.3V, 5V, 12V, and -12V The aa, bb, cc, and dd values returned by the gsts command are in hexadecimal. These values need to be converted from hexadecimal to decimal in order to find the
results of the voltage readings. The voltage readings areaccurate to ±7%. 3.3V Reading: to find the value for the 3.3V reading, convert the aa value (from Table C-3) to decimal and multiply it by 0.01606 5V Reading: to find the value for the 5V reading, convert the bb value (from Table C-3) to decimal and multiply it by 0.02352
12V Reading: to find the value for the 12V reading, convert the cc value (from Table C-3) to decimaland multiply it by 0.05895
-12V Reading: to find the value for the -12V reading, convert the dd value (from Table C-3) to decimal, multiply it by 0.209,subtract 40.96 from the result, then divide by 3.01 In equation form,
Step 1: Use the following equation to calculate the actual thermistor resistance (RJ, where mm is the value for the temperature reading returned from the command gsts, listed in Table C-3.
R,- 15^000.(10,000) Step 2: To calculate the actual tliermistor temperature as a function of the thermistor resistance, use the following equation:
1/T = A+Iifln—-I +Clin—M ...where
T = Temperature (in Kelvin)
Rj = Thermistor Resistance at temperature T (calculated in Step 1) R25 = 5000 Ohms A = constant (from Table C-5) B = constant (from Table C-5) C = constant (from Table C-5)
TABLE C-5
Values for Thermistor Equations
Rt/R25 range
A
B
c
72.50 to 3.363
3.3564846 x 10"03
2.4622340 x 101'4
4.0776512 xlO"06
3.363 to 0.3507
3.3540172 x 1003
2.5027462.x 1004
2.4300527 x 10"06
0.3507 to 0.06370
3.3530496 x lO"03
2.4792929 x 10"4
1.0822040 x 10"06
0.06370 to 0.0169
3.3467185 x 10"03
2.4342924 x 10'04
3.3465275 x 10"07
Note: Please refer to Appendix B for information on the default backplane jumper settings for die system alarm card.
GNP's AlertlNode (Smart Node Alarm Card) serves as die alarm aggregation point, or Chassis Management Controller (ChMC), for die GNP ComputeNodeXU family of products. Accessible through the rear of the chassis, it incorporates an IPMIcompliant Baseboard Management Controller (BMC) to monitor PICMG 2.9 compliant CompactPCI devices and the power and cooling subsystems. The AlertlNode provides remote connectivity through either a serial console or Ethernet
supporting Telnet. The following local alarm indications are provided: critical/major/ minor LED indicators and dry relay contact closures.
If a CompactPCI board with BMC functionality is present in the system to act as a ChMC, it can query die AlertlNode for die status of the power and coolingsystems. The AlertlNode is hot-swappable and does not occupy a CompactPCI slot, front or rear. Because it is a passive out-of-band management entity, it will not affect system operation if it fails, allowing it to be safely replaced in a live system. FIGURE D-l AlertlNode Block Diagram: AlertlNode as Chassis Management Controller
CompactPCI Power
CompactPCI Bus
AlertlNode
detect
era
System
Power
System
Peripheral
Fans
Supplies
Controller
Slots
Chassis
Management
detect
Controller
If no other Baseboard Management Controller is present in the system, the AlertlNode acts as the Chassis Management Controller for the system.
Installation and Operation Manual
Revision E
D -1
1-800912 Appendix D -AlertINode (Smart Node Alarm Card) ComputcNode4U
GNP
FIGURE D-2 AlertlNode Block Diagram: System Controller as Chassis Management Controller
CompactPCI Power
IPMB
If another Baseboard Management Controller is present in the system to act as the Chassis Management Controller (ChMC), the AlertlNode reports to the ChMC.
The AlertINode faceplate is located on die rear panel of the unit, in the upper left-hand corner, as seen from die rear of the unit.
FIGURE D-3 AlertlNode Faceplate b
1.
2.
D-2
10-BaseT Ediernet port (RJ-45) with Ethernet Link & Activity LEDs a. Link LED (yellow) b. Activity LED (green) RS-232 asynchronous serial port (p:DB-9)
Revision E
3. 4. 5.
Alarm port (liDB-9) — provides access to the dry contact outputs Critical alarm LED (red) Major alarm LED (red)
User Commands and Interface for the AlertINode A single, unified command lineinterface (CLI) appears on both the serial consoleand telnet interfaces. The available commands and syntaxare described below. Serial Console Login
There are two user profiles presenton the serial consolelogin: User and Debug. The only difference between the two profiles is that the Debug profile has additional commands usefulfor accessing the raw GPIO ports, registers, and memory region of the Zircon micro-controller. These commands are noted in the following sections. The handling of different user profiles is fairly basic, so insteadof enteringa separate username and passwordduringthe loginprocedure, the AlertlNode only looks for the password for a profile at the "Login:" prompt. The default passwords for these profiles are the profile names themselves.
To log in as User, type "User" at the "Login:" prompt To log in as Debug, type "Debug" at the "Login:" prompt. These passwords may be changed from the default by the "passwd" command. Telnet Login
Currendy, only one profile is available on a telnet session. The user profile name is "Debug" and the default passwordis "Debug". Currendy, the telnet login cannot be changed from the default password. Main Menu Commands and Syntax
The following commands are typed direcdy at the prompt; they do not use "get" or "set". All commands are followed by <ENTER> or . TABLE D-l
Main Menu Commands
Description
Command
passwd
Changethe password of the currentlogin profile. To changethe password, input is in the form:
ipmi
Enter the rawdata for an internalIPMI request.This command is meant to emulatethe board receiving an IPMI requeston its IPMBbus. Input is in the form: ipmi A typical IPMI command anddataentrywould be of the form:
passwd [current password]
Main> ipmi \ <requester slave addr> \ <0 or more data bytes>
...whereeach <...> entry is a single-byte hex value, which should prefixedby "Ox"so that it will parseproperly. The checksums are calculated by initializing the checksum value to 0, then adding eachcommand byteto it.Aftereach addition, the checksum is MOD divided by256 (0x100) to ensurethat the checksum remains a single-byte value. After allcommandbytes arc addedin thisway, the currentsumshouldbe negated, and the resulting value is the checksum. The first checksum is the checksum for the responder slaveaddress and the net funcrion/rcspondcr LUNbytes. The secondchecksum is the checksum for the requester slave address all the way to anydata bytesincluded in the command. ipmb
Command format:
ipmb [...] Enter the raw data for an IPMI request. The first argument is the target's IPMI slaveaddress. The second argumentis the networkfunctionof IPMI command, i.e.an application (app), chassis (ch), sensor/event (se), storage (st), or transport (tr) request. The third argument is the command byte. The remainingarguments are optional, depending upon the arguments of the specific IPMI command given. sdrr
To print out the current Sensor Data Record Repository,type: sdrr
Installation and Operation Manual
Revision E
D-3
1-800912 Appendix D -Alert!Node (Smart Node Alarm Card) ComputeNode4U ••';'
Command
,'•>
GNP
Description ";:
To print out the currentSystem Event Log Record, type:
selr
self
To enter the networksub-menu, type:
net
net
Refer to the "Network MenuCommands and Syntax" section for commands available in this sub-menu.
To perform a hard reset on the board, type:
reset
reset
Note that certain parameter settings willonly take effect after a reset of the board.
To print out a briefonlinehelpguide to thesecommands, type:
help
help
quit
To log out of a serial console session, type: quit Note: This command has no effect on a telnet session.
logout
To log out of a telnet session, type: logout
Note: Thiscommand has no effect on a serial console session, except for returning an unknown command error.
powercycle
powercycle
Thiscommand will setallthree power supplies in theComputeNode4U cPSB to be off,in order to resetthe unit. It is the equivalent of typing: "set psil off", "set psi2 off", and "set psi3 off". (Refer to D-3 for information on the psi command.) get mac
Reads the Ethernet MAC address from the onboard serial EEPROM.
System Monitoring Commands
The"get" commands are used to read various settings andsensors on theAlertlNode. The output will also show whether or not an alarm occurred on that sensor. Certain
parameters canbe controlled bytheuser. These aresetusing the"set" commands. All commands are followed by <ENTER> or . These commands are in the form: get
< . . .>
<ENTER>
set
< . . .>
<ENTER>
Power Supply Monitoring
The AlertlNode monitors the health ofthe input power feeds, the power supplies, and the voltage levelson the +3.3V, +5V, +12V, and -12V lines.
TABLE D-2 Power Parameters Monitored ("Get" only) Parameter
Command Syntax
Power feed A
get feeda
Power feed B
get feedb
Power supply #1
get psfl
Power supply #2
get ps£2
Power supply #3
get psO
+3.3V line voltagelevel
get volt33
+5V line voltage level
get volt5
+12V line voltage level
get voltl2
—12V line voltage level
get nvolt!2
D-4
Revision E
Description Reads the raw status of power feed A or B. Possible outputs: "Good" - Receiving power from -48V feed. "Bad" - No power from -48V feed.
Reads the failure status of power supply#1, #2, or #3. Possibleoutputs: "Good" - power supplyis not in a failed state. "Bad" - power supply is in a failure state.
Reads the+3.3V, +5V, +12V, and-12V lines. Returns voltage reading in volts.
Installation and Operation Manual
GNP ComputeNode4U
1-800912 Appendix D -AlertINode(Smart Node Alarm Card)
TABLE D-3 Action
Power Supply Inhibit ("Get" or "Set")
Command Syntax
Read setting of power supply inhibit signals
get psil
Turn powersupplieson or
set psil on set psi off
Read the current inhibit signal setting for power supply #1, #2, or #3. "Inhibited" — the AlertlNode has set the power supply to be off. "Enabled" — the AlertlNode has set the power supply to be on.
get p8i2
get psi3 off
Description
Enable (turn on) or disable(turn off) power supply#1, #2, or #3.
set psi2 on set psi2 off set psi3 on set psi3 off
Temperature Monitoring
The AlertlNode monitors the internal temperature of the ComputeNode4U cPSB. TABLE D-4 Parameter
Internal temperature of the ComputeNode4U
Temperature Sensor ("Get" only) Description
Command Syntax
Retrievesthe current temperature reading in degrees Celsius,accurate to
get temp
±0.5 °C
cPSB
Fan Monitoring
The AlertlNode monitors the health of the fans in the ComputeNode4U cPSB. TABLE D-5 Parameter Fan sensor #1 — 2 of the 4
Fan Health ("Get" only) Read the current status of fan signal #1, #2, or #3. "Good" - Fans are spinningnormally(or not present). "Bad" - Fans are unable to spin.
front fans
Fan sensor #2 — 2 of the 4
Description
Command Syntax get fanl get fan2
front fans
Fan sensor #3 — rear fan
get fan3
bracket
Dry Contacts
The AlertlNode monitors and controls the status of three dry contacts.
TABLE D-6 Parameter
Current settingsof dry contacts #1, #2, #3
Set dry contact #2 Set dry contact #3
Description
Command Syntax get dry 1 getdry2 getdry3
Set dry contact #1
Dry Contact Status ("Get" or "Set") Read the current settingfor dry contact #1, #2, or #3. "On" - dry contact is powered on. "Off" - dry contact is powered off.
set dryl on
Turn dry contact #1 on.
set dryl off
Turn dry contact#1 off. Cancels a set dryl on action.
set dry2 on
Turn dry contact #2 on.
set dry2 off
Turn dry contact#2 off.Cancels a set dry2 on action.
set dry3 on
Turn dry contact #3 on.
set dry3 off
Turn dry contact #3 off. Cancelsa set dry3 on action.
Installation and Operation Manual
Revision E
D-5
1-800912 Appendix D -AlertINode (Smart Node Alarm Card) ComputeNode4U
GNP
LEDs
There are four LEDs on the faceplate of the AlertlNode: critical alarm (red), Major alarm (red), minor alarm(yellow), and powerindicator (green). Each can be set to be on, off, or blinkingslowly or quickly.
TABLE D-7
LED Settings ("Set" only)
Command Syntax
Parameter Critical Alarm LED
(red)
Major Alarm LED (red)
Minor Alarm LED
(yellow)
Power LED (green)
Description
set crit on
Turns the Critical Alarm LED on.
set crit off
Turns the Critical Alarm LED off. Cancels a crit on, crit slow, or crit fast action.
set crit slow
Sets the Critical AlarmLED to blinkslowly.
set crit fast
Sets the Critical Alarm LED to blink quickly.
set maj on
Turns the Major Alarm LED on.
set maj off
Turns the MajorAlarmLED off. Cancels a maj on, maj slow, or maj fast action.
set maj slow
Sets the MajorAlarm LED to blink slowly.
set maj fast
Sets the MajorAlarm LED to blinkquickly.
set min on
Turns the Minor Alarm LED on.
set min off
Turns the Minor Alarm LED off. Cancels a min on, min slow, or min fast action.
set min slow
Sets the MinorAlarmLED to blinkslowly.
set min fast
Sets the MinorAlarmLED to blinkquickly.
set pow on
Turns the Power LED on.
set pow off
Turnsthe Power LED off.Cancels a pow on, pow slow,or pow fast action.
set pow slow
Sets the PowerLED to blinkslowly.
set pow fast
Sets the PowerLED to blinkquickly.
Alarm Indicators and Settings Clearing Alarms
Clearingan alarm willreset the sensors and alarm indicators. If a failure condition is stillpresent, the alarmwillre-assertitself.
TABLE D-8
Clearing Alarms
Command
Clearsall pending alarms on all sensors.
clear feeda
Clears allpendingalarms on power feed A.
clear feedb
Clears allpendingalarmson power feed B.
clear psfl
Clears allpending alarms on powersupply 1. Clears allpending alarms on powersupply 2. Clears allpendingalarmson powersupply3.
clear psf2 clear psf3
D-6
Description
clear all
clear volt33
Clearsall pending alarms for the +3.3V sensor.
clear volt5
Clearsall pending alarms for the +5V sensor.
clear voltl2
Clears all pending alarms for the + 12V sensor.
clear nvoltl2
Clearsall pending alarms for the -12V sensor.
clear temp
Clears allpendingalarms for the temperature sensor.
Voltage and temperature monitoring have tiiree levels of alarm threshold (minor, major, and critical) and response actions associated with those thresholds. The power feeds, power supplies, and fans are monitored for health; they are all either good or in a failed state. For diesc parameters, there isa response action for the failure state only. The possible response actions are to set die dry contacts on/off and to change the status of the faceplate LEDs.
TABLE D-9 Parameter
Get Alarm Thresholds and Response Actions Description
Command
Power feed A
get fceda actions
Power feed B
get feedb actions
Returns the response action for a failure on feed B. (One alarm state only.)
Power supply #1
get psfl actions
Returns the response action fora failure of power supply #1. (Onealarm stateonly.)
Power supply #2
get psf2 actions
Returns the response action for a failure of powersupply #2. (One alarmstate only.)
Power supply #3
get psf3 actions
Returns the response action for a failure of power supply #3. (One alarmstate only.)
Alarm thresholds
get volt33 thresholds
Voltage alarmthresholds are designated by a percentage over or under the nominal
for +3.3V, +5V, + 12V,and-12V
get volt5 thresholds
Returns the response action for a failure on feed A. (One alarm state only.)
voltage.
There are sixalarm thresholds for each voltage: min_under (minorunder-voltage
get voItl2 thresholds get nvoltl2 thresholds
Response actions for over-voltage and under-voltage alarm conditions.
alarm), maj under (major under-voltage alarm), crit under (critical undervoltage alarm), min_ovcr (minor over-voltage alarm), maj_over (major overvoltage alarm), and crit_over (critical over-voltage alarm) get thresholds returns die settings for all six alarm thresholds.
Returns the response actions for all six alarm thresholds for the designated voltage.
get volt33 actions get volt5 actions get voltl2 actions get nvoltl2 actions
get temp thresholds
Returns the minor alarm, major alarm, and critical alarm threshold settings for the temperature sensor, in degrees Celsius.
get temp actions
Returns the response actions for minor, major, and critical over-temperature levels.
Fan sensor #1
get fanl actions
Pan sensor #2
get fan2 actions
Returns the response action for a failure reading on the indicated fan sensor. (One alarm state only.)
Fan sensor #3
get fan3 actions
Current status
get allalarms
Internal
temperature of the ComputcNode4U cPSB
Returns the status of all pending alarms.
Setting Threshold & Action Settings
Voltage and temperature monitoring have three levels of alarm dircshold that maybe set (minor, major, and cridcal) and response acdons associated with those thresholds. The power feeds, powersupplies, and fans are monitored for health; theyare alleither good or in a failed state. For theseparameters, diere is a response acdon for die failure state only. The possible response actions that may be selected are to set the dry contacts on/off and to change the status of the faceplate LEDs. Refer to Table D-ll for a list of all response acdon settings.
& r
Note: Multipleresponse actions maybe set for a given alarm state, but only one action may be set per command. For example, if you wanted to set die power LED to blink slowly, die major alarm LED to be on, and dry contact #3 to trigger if power feed A failed, you would use the commands: set
feeda
failure
action pow_slow
set
feeda
failure
action maj_on
set
feeda
failure
action dry3_on
Installation and Operation Manual
Revision E
D -7
1-800912 Appendix D -AlertINode (Smart Node Alarm Card) ComputeNode4U
GNP
TABLE D-10 Set Alarm Thresholds and Response Actions Power feed A
set feeda failure action
Power feed B
set feedb failure action
Powersupply#1
set psfl failure action
Powersupply#2 Power supply#3
set pa12 failure action
set nvoltl2 <severity>level <setting>
Setsthe given thresholdlevel for the indicated voltage sensor. Possible <severity>levels are min_under, maj_under, crit_under, min_over, maj_over, and crit_over. <setting> is thepercentage overor underthenominal voltage forthe given severity level.
set volt33 <severity> action
Setsthe indicated to perform if the given <severity>level
set volt33 <severity> level <setting>
for +3.3V, +5V, +12V,and-12V
set volt5 <severity> level <setting>
alarm conditions.
Setsthe indicated to perform in the caseof a failure of the indicatedparameter. Refer to TableD-ll for possible options.
set psB failure action
Alarm thresholds
Responseactions for over-voltage and under-voltage
Description
Command
Parameter
set voltl2 <severity>level <setting>
set voltS <severity> action
set voltl2 <severity> action
is reached.
Referto TableD-ll for possible options.
set nvoltl2 <severity> action Internal
set temp <severity> level <setting>
Setsthe given threshold level for the temperature sensor. Possible <sevcrity>levelsarc min_over, maj_over, and crit_over. <sctting> is givenin degrees Celsius.
set temp <severity> action
Sets the indicatedto perform if the given <severity>level
temperature of the ComputeNode4U cPSB
is reached.
Referto TableD-ll for possible options. Fan sensor #1
set fanl failure action
Fan sensor #2
set fan2 failure action
Fan sensor #3
set fan3 failure action
Sets the indicatedto perform in the case of a failure of the indicated fan sensor.
Referto Table D-ll for possible options.
Possible Response Actions
When setting alarm responses, the dry contact and LED settings listed in the table below replace the arguments shown in Table D-10. TABLE D-ll Alarm Response Actions Description
1-800912 Appendix D -AlertINode (Smart Node Alarm Card) ComputeNode4U
GNP
Network Menu Commands and Syntax
The help command may be useful for reference. Typing "help general", "help diagnostic" or "help telnet" will have the AlertlNode print out the help menus for the general,diagnostic, or telnet functions of the network. (Typingjust "help" will by default print the general command help screen.) The following commands are categorized according to these function types. General Network Commands and Syntax TABLE D-13 General Commands
Description
Command
To print out the current state of the IP interface,type:
state
state
This command willdisplay the IP address,netmask, default gateway, and the source of the IP address - whether it is configured from NVRAM or via DHCP. delay
delay [milliseconds] Sets the delaybetweenpings.
host
host
Sets the default active IP host
length
length Sets the defaultping packetlength.
rtadd
rtadd
Manually adds an IP route to the table. rtdel
rtdel
Manually deletes an IP route from the table. routes
routes
Displays the current routingtable. serip
setip Sets the IP address and netmask for the Ethernet interface.
setdgw
setdgw Sets the defaultgateway IP for the board.
dhcp
dhcp
Toggles the DHCP function. When enabled, the boardwill try to resolve its IP address viathe DHCP protocol, timingout if necessary. quit
quit Exits the network sub-menu and return to the main menu.
D-10
Revision E
Installation and Operation Manual
GNP ComputeNode4U
1-800912 Appendix D -AlertINode (Smart Node Alarm Card)
Diagnostic Commands and Syntax
TABLE D-14 Diagnostic Commands Syntax
Command
/$^\
Description
arps
arps
Displays ARP stats and table.
buffers
buffers
Displays free q buffer stats.
queues
queues
Dumps packet buffer queues.
dbytes
dbytes
Dumps a block of memory.
debug
debug
Sets IP stack debug tracing.
dtrap
dtrap
Tries to hook debugger.
dump
dump
Hcxdumps incoming packets.
iface
iface
Displays net interface stats.
linkstats
linkstats
Displays link layerspecificstats.
mbuf
mbuf
Displays mbuf stats.
mlist
mlist
Displays mbufs in use.
tcp
tcp
Displays TCP stats.
sockets
sockets
Displays socket list.
tbconn
tbconn
TCP BSD connection stats.
tbsend
tbsend
TCP BSD send stats.
tbrcv
tbrcv
TCP BSD receive stats.
allocsize
allocsize
Sets size for allocO breakpoint.
ipstat
ipstat
Displays IP layerstats.
icmpstat
icmpstat
Displays ICMP layerstats.
udp
udp
Displays UDP layer stats.
upcall
upcall
Traces received packets.
dcstats
dcstats
DHCP Client statistics
Telnet Commands and Syntax TABLE D-15 Telnet Commands
Syntax
Command
Description
tshow
tshow
Shows the options values for all sessions.
tstats
tstats
Shows the statistics of all telnet sessions.
logout
logout
Log out of the telnet session.
/fftfK.
Installation and Operation Manual
Revision E
D-ll
1-800912 Appendix D -AlertINode (Smart Node Alarm Card) ComputeNode4U
GNP
AlertINode Connector Pinouts The Ethernet, serial, and alarmports are located on the faceplate of the AlertiNode. Referto Figure D-3 on pageD-2 for a diagram showing their positions.
RS-232 Serial liDB-9 Connecto R—J3001 TABLE D-17 RS-232 Serial uDB-9 Connector DCE Pinout Pin
Signal
1
DCD
Signal Description Data Carrier Detect
2
RX
Receive
3
TX
Transmit
4
nc
no connection
5
GND
Signal Ground
6
nc
no connection
7
RTS
Request to Send
8
CTS
Clear to Send
9
RI
System AlLArm
Ring Indicator
liDB-9 Dry Contact Connector —J0106
TABLE D-18 System Alarm uDB-9 Dry Contact Connector Pinout
D-12
Pin
Signal
1
COM1
2
NOl
Relay #1 normally-open lead
3
NC2
Relay #2 normally-dosedlead
4
COM3
Signal Description Rday #1 common lead
Relay#3 common lead
5
NC3
Relay #3 normally-dosed lead
6
NCI
Relay #1 normally-dosedlead
7
N02
Relay #2 normally-open lead
8
COM2
9
N03
Revision E
Relay#2 common lead
Relay #3 normally-openlead
Installation and Operation Manual
GNP
ComputeNode4U
1-800912 Appendix D -AlertINode (Smart Node Alarm Card)
18-Pin Molex Connector —J0100 The 18-pin Molex connector is an internal connectordiat mates to the backplane. Note: For the 18-pin Molex connector, column F pins connect to DGND. TABLE D-19 18-Pin Molex Connector Pinout Pin
Signal
Signal Description
1
FAN 2
Pan Detect Signal 2
2
FAN1
Pan Detect Signal 1
3
IPMB_SDA
4
PS_FAI1.3
5
+5V
6
DGND
7
+3.3V
8
DGND
9
PSJvULl
10
FAN3
IPMB Bus Data Signal
Power Supply I''ail Detect Signal 3 + 5V Power Signal Digital Ground +3.3V Power Signal Digital Ground
PowerSupply Rail Detect Signal 1 Pan Detect Signal 3 IPMB Bus Clock Signal
11
IPMB_SCL
12
FFFDB
Input Power Peed B Detect
13
FFFDA
Input Power Peed A Detect
14
DGND
Digital Ground
15
+ 12V
16
DGND
17
-12Y
18
PSJ-AII.2
+ 12V Power Signal Digital Ground -12V Power Signal
PowerSupply Fail Detect Signal 2
Note: Please refer to Appendix B for information on die default backplane jumper settings for die system alarm card.
For additional information or questions regarding the AlertlNode, please contact GNP at [email protected] or (800) 735-4467.
Installation and Operation Manual
Revision E
D
-13
1-800912 Appendix D -AlertINode (Smart Node Alarm Card) ComputeNode4U
GNP
,-"=%
D -14
Revision E
Installation and Operation Manual
1-800912 Appendix
3U cPSB 9-Port Ethernet Switch ComputeNode4U cPSB
Overview The 3U cPSB 9-Port Ethernet Switchprovides nine 10/100 Mbps Fast Ethernet ports diat provide fully non-blocking layer 2 switcliing capabilities. Two ports are available dirough rear cPCI connectors, widi the backplane routed such diat die other seven ports on each switch providea 10/100Base-Tx connection to each of the otiier cPCI slots in die system. It is designed for use with GNP's custom cPSB systems. FIGURE E-l 3U cPSB 9-Port Ethernet Switch Block Diagram Jl Connector
J2 Connector
t hot-swap power
Q
a
0
9-port integrated ethernet switch
3 H
a. > w
V
i
o
X
Link and
Activity LEDs
M
M
Faceplate
The 3U cPSB 9-Port Ethernet Switchis GNP part # 1-503686, and its corresponding RTM is GNP part # 1-503687.
Installation and Operation Manual
Revision E
E
-1
1-800912 Appendix E -3U cPSB 9-Port Ethernet Switch
ComputeNode4U cPSB GNP
FIGURE E-2 3U cPSB 9-Port Ethernet Switch Faceplates Front Panel:
1.
i
:'»,
s,
/
9,
\\
Rear Panel:
Port 1 activity/link indicator LED - green (monitors slot #2)
7.
2.
Port 2 activity/link indicator LED - green (monitors slot #3)
8.
Port 8 activity/link indicator LED —green
9.
Port 9 link indicator LED - green
3.
Port 3 activity/link indicator LED - green
10. Port 9 activity indicator LED - green
(monitors slot #4)
4.
Port 4 activity/link indicator LED —green (monitors slot #5)
5. 6.
Port 5 activity/link indicator LED - green (monitors slot #6) Port 6 activity/link indicator LED - green (monitors slot #7) * The combined activity/link LEDs indicate a link with a steady lit condition, and indicate activity by blinking.
E-2
Revision E
Port 7 activity/link indicator LED - green (monitors slot #8)
11. Power indicator LED - green 12. Mot-swap indicator LED - blue 13.
Latch
14. Port 8 RJ45 connector
15. Port 9 RJ45 connector^ f Port 9 is labeled "MGT Port". Currently, its only management function is to act as an uplink port, providing the system with an external ethernet connection.
Installation and Operation Manual
GNP ComputeNode4U cPSB /0^\
1-800912 Appendix E -3U cPSB 9-Port Ethernet Switch
Backplane Interface Pinouts Note: For the following tables, columns F and Z are connector shielded and are connected to DGND. Blank spaces indicate no connection (NC). TABLE E-l Pin# 25
A
EARLY_3.3V
16
15
LONG_VIO
DGND
LONG_3.3V
DGND
EARLY_VIO
DGND
EARLY_3.3V
IPMB_SCL
IPMB.SDA
DGND
EARLY_VIO
E
EARLY.5V
LONG_5V
EARLY_3.3V
18 17
EARLY_5V
D
EARLY_3.3V
EARLY_3.3V
20 19
C ENUM#
EARLY_3.3V
22
21
B
EARLY_5V
24 23
Jl Connector Pinouts
DGND
EARLY.3.3V
DGND
BD_SEL#
14 KEY AREA
13 12
11
DGND
10
DGND
EARLY_3.3V
DGND
EARLY_VIO
PCI_PRESENT
LONG_3.3V
PCI_CLK
PCI_RST#
DGND
9
DGND
8 7
DGND
6 5 4
IPMB_PWR
HEALTHY#
EARLY_5V
2
1
LONG_VIO
LONG_5V
3
EARLY_5V
EARLY_N12V
Installation and Operation Manual
EARLY.P12V
Revision E
EARLY.5V
E-3
(ComputeNode4U cPSB
1-800912 Appendix E -3U cPSB 9-Port Ethernet Switch
TABLE E-2 Pin# 22
A
GNP
J2 Connector Pinouts
B
c
D
E
GA4
GA3
GA2
GA1
GAO
19
DGND
DGND
SMB.SDA
SMB.SCL
SMB^ALERT
18
MGT_TX0+
MGT.TXO-
DGND
reserved
reserved
17
MGT_RX0+
MGT_RX0-
DGND
reserved
reserved
16
10/100TX7+
10/100TX7-
DGND
reserved
reserved
21 20
1*
I0/100RX7+
10/100RX7-
DGND
reserved
reserved
14
10/100TX6+
10/100TX6-
DGND
reserved
reserved
13
10/100RX6+
10/100RX6-
DGND
reserved
reserved
12
10/100TX5+
10/100TX5-
DGND
reserved
reserved
11
10/100RX5+
10/100RX5-
DGND
reserved
reserved
10
10/100TX4+
10/100TX4-
DGND
reserved
reserved
9
10/100RX4+
10/100RX4-
DGND
reserved
reserved
8
10/100TX3+
10/100TX3-
DGND
reserved
reserved
7
10/100RX3+
10/100RX3-
DGND
reserved
reserved reserved
6
10/100TX2+
10/100TX2-
DGND
reserved
5
10/100RX2+
10/100RX2-
DGND
reserved
reserved
4
10/I00TX1+
10/lOOTXl-
DGND
reserved
reserved
3
10/I00RX1 +
10/100RX1-
DGND
reserved
reserved
2
10/100TX0+
10/I0OTX0-
SYSTEM#
reserved
reserved
1
10/100RXO+
10/100RX0-
DGND
reserved
reserved
'-s%
•**%
E-4
Revision E
INSTALLATION AND OPERATION MANUAL
GNP ComputeNode4U cPSB
1-800912 Appendix E -3U cPSB 9-Port Ethernet Switch
J6300 port 9 program JP6100 802.1p enable JP1100 reserved for
in-factory testing J7000 program strips
JP6100 — 802.1P ENABLE The 2-pin header at JP6100 enables 802.1p for all ports.
Installing a jumper (closed) will set the ports to use a 802.Ip priority field unless disabled in EEPROM. With no jumper installed (open), 802.Ip is selected by the port in EEPROM. The default settingis with no jumpers installed
J6300 — Port 9 Programming The 8-pin header atJ6300 controls the programming of port #9. TABLE E-3 Pair of Pins
Port #9 Programming — Jumper Settings Function
Open Setting (default)
Closed Setting
7&8
10/100
100 Mbps
10 Mbps
5&6
Duplex
Full duplex
Half duplex
No flow control
Flow control enabled
3&4
Flow Control
1&2
N/A
Installation and Operation Manual
Revision E
E-5
1-800912 Appendix E -3U cPSB 9-Port Ethernet Switch
ComputeNode4U cPSB GNP
J7000 — Program Strips TABLE E-4 Pair of Pins
Function
23&24
Aggressive
21&22
Drop Frame
19&20
Trunking
17&18
Program Strips — Jumper Setting Options Closed Setting;
Open Setting (default) Moreaggressive back-off
Less aggressive back-off
Continue sending frame
Drop frameafter 16 collision
Both pairs open = trunkingdisabled
17&18open, 19&20dosed = ports 1,2 trunked together
19&20open, 17&18 dosed = ports 1,2/ports
Both pairs closed = ports 1,2,3,4trunked
3,4 trunked 15&16
Flow Control
13&14
Broadcast Frame
11&12
Buffer
9&10
{reserved}
Flow control enabled
No flow control
Unlimited broadcast frame
5% broadcast frame allowed
Share up to 512 buffers on single port
Equal113buffer/per port
7&8
Aging
Enable 5 minute aging
Agingdisabled
5&6
VLAN
Max. 1536 byte
MaxVLAN 1522 bytes,W/O VLAN 1518
3&4
Broadcast Frame
Program broadcast flow control enabled
Program broadcast flow control disabled
1&2
Duplex
Half duplex back pressure enabled
No half duplex back pressure
bytes
^*\
E-6
Revision E
Installation and Operation Manual
1-800912 Appendix
3U cPSB 8+2G Ethernet Switch ComputeNode4U cPSB
Overview GNP's 3U cPSB 8+2G Ethernet Switch is a 3U, single-slot CompactPCI card that provides eight 10/100 Mbps Fast Ethernet ports and two 10/100/1000 Ethernet ports in a fully non-blockingswitching configuration designed for use in GNP's cPSB systems. The switch provides a management interface to monitor the status and control the functions of each port, and has the ability to configure advanced capabilities such as port mirroring. A pair of hot-swappable 3U cPSB 8+2G Ethernet Switches provide redundant switching fabrics while occupying only one 6U CompactPCI slot. Three ports are available through the front and rear faceplates, with die backplane routed such diat die odier seven ports on each switch provide a 10/100Basc-Tx connection to each of die other cPCI slots in the system.
The software management interface allows the user to retrieve individualstatistics for each port, and to configure the following attributes: auto-negotiation, port speed, switch half/full duplex, and flow control.
Port 10— 10/100/1 OOOBase-Tx Ediernet port (RJ-45)
2.
3.
8.
Port 6 activity/link indicator LED — green' (monitors slot #7)
Front panel access to RS-232 console port (RJ-45)
9.
Port 1 activity/link indicator LED — green'
10. Port 8 activity/link indicator LED — greenT
(monitors slot #2)
4.
Port 2 activity/lrnk indicator LED — green' (monitors slot #3)
5.
Port 3 activity/link indicator LED — green' (monitors slot #4)
6.
Port 4 activity/link indicator LED — green' (monitors slot #5)
7.
Port 5 activity/link indicator LED — green' (monitors slot #6)
Port 7 activity/link indicator LED — green' (monitors slot #8)
11. Port 9 (rear panel10/100/1000 port) activity/ link indicator LED — green"
12. Port 10 (front panel 10/100/1000 port) activity/ link indicator LED — green"
13. Power indicator LED — green 14. Hot-swap indicator LED — blue* 15. Port 8 — 10/1OOBase-Tx Ethernet port (RJ-45) 16. Port 9 — 10/100/1 OOOBase-Tx Ethernet port (RJ-45)
* The console port may be accessed from the front or the rear panel, but only one of the two RJ-45 connectors may be used at a time. The port settings are 3-wire, 9600-N-8-1.
17. Rear panel access to RS-232 console port (RJ-45)
TThecombined activity/link LEDsindicate a link with a steady lit condition, and indicate activity by blinking.
Installation and Operation Manual
^ The hot-swap LED is on during card insertion and power-up, but is off when the switch is in use.
Revision E
F-3
1-800912 Appendix F -3U cPSB 8+2G Ethernet Switch
ComputeNode4U cPSB
GNP
User Interface for the cPSB 8+2G Ethernet Switch The 3U cPSB 8+2G Ediernet Switch uses a command line interface (CLI). The available commands and syntax are described below. Starting a Session
The user interface for die switch will start up automatically when die switch is powered up. If everything starts normally, you should see a prompt that looks like: BCM
>
Note: If you do not see a prompt or there is an error message, please email [email protected] or contact GNP at (800) 735-4467 and ask for Customer Support. Main Menu Commands and Syntax
The following commands are typed direcdy at the prompt; they do not use "get" or "set". All commands are followed by <ENTER> or . TABLE F-l
Main Menu Commands
Description
Command
Displays firmware version information.
version
help
Displays help information for the switch commands. There are three options: "help get" returns information on the "get" commands. "help set" returns information on the "set" commands. "help" (with no argument) returns information on all switch commands.
counter <port#>
status
hist
Displays real-time transmit/receive statistics for theindicated port.This includes statistics such as TX/RX packet count, packet error count, dropped packet count, and collision count. Displays a real-time screen of all of the parameters for all of the ports. Displays the results of the built-in self test (BIST).
"Get" and "Set" Commands
The "get" commands are used to read various settings of die 3U cPSB 8+2G
Ediernet Switch. The output will show the current port settings and feature options. Certain parameters can be controlled by die user. These are set using die "set" commands. All commands are followed by <ENTER> or . These commands are in the form: get
<...>
<ENTER>
set
<...>
<ENTER>
Note: In the following commands, <port#> is used to indicate the port number (1-10), corresponding to FIGURE F-3, "cPSB 8+2G Ethernet Switch Faceplates". Port Setting Summary
The "all" command is used to check the following status and settings of a given port: link activity, transmit/receive, auto-negotiation, data rate, duplex mode, flow control, autocast, and mirroring. TABLE F-2
Port Setting Summary ("Get" only)
Command Syntax get <port#> all
F-4
Revision E
Description Displays the status and settings of the indicated port.
Installation and Operation Manual
GNP ComputeNode4U cPSB
1-800912 Appendix F -3U cPSB 8+2G Ethernet Switch
Link Activity
The "link" command is used to check the link status (on/off) of a given port. TABLE F-3
Link Information ("Get" only)
Command Syntax
Description
Displays whether the link of the indicated port is on or off.
get <port#> link
Receive/Transmit
The "enable" command is used to configure die receive/transmit capabilities of a
particular port. Each port can be configured to be on, off, receive only (RX), or transmit only (TX). TABLE F-4 Command Syntax get <port#> enable set <port#> enable