Instruction : External Current Transformer
Installation of Ext CT
Product Name: EOCR-E Series Electronic Over Current Relay Multi-function digital Relay
External CT Option The current higher than 60Amps can be applied with the External CT Option. The Ext CTs should be selected in 5A of the secondary current rating of a External CT . Rating Current Reference
Current Setting Range(A)
Current Ratio of Ext. CT
H1 HH H2 H3 H4
10 ~ 120 15 ~ 180 20 ~ 240 30 ~ 360 40 ~ 480
100 : 5 150 : 5 200 : 5 300 : 5 400 : 5
▼
▼
▼
Figures Rack mounting type - This model is provided with assembled one in the factory. - with 3 CT.
- This model is provided with assembled one in the factory. - with 3 SR-CT
1
SWP-040-02, Form 13, rev. 0, 1999.5.17
Instruction : External Current Transformer
Installation of Ext CT
Product Name: EOCR-E Series Electronic Over Current Relay Multi-function digital Relay
Flush mounting window type - This model is provided with assembled one in the factory.
- D–Sub connector is assembled.
Flush mounting terminal type - This picture shows an example of the assembled EOCR with a External CT.
- This picture shows an example of the
assembled EOCR with a External CT. This terminal type without terminals can be provided by a special order.
2
SWP-040-02, Form 13, rev. 0, 1999.5.17
Instruction : External Current Transformer
Installation of Ext CT
Product Name: EOCR-E Series Electronic Over Current Relay Multi-function digital Relay
Setting - CT ratio should be set in a primary current rating of the External CT. - It’s not possible to set the CT ratio in case “oc” setting value is over 6.0A . - It’s not possible to adjust or change the value during operation. - In case CT ratio is over 75:5, the indication on the screen shows c100, c200...c400..c800. - Setting mode.
- Setting value. Off(--), 5t, 2t, 10, 15, 20, 25, 30, 40, 50, 60, 75, 100, 120, 150, 200, 250, 300, 400, 500, 600, 750, 800.
3