Welcome to the Schneider Electric Seminar on ‘LV Power Concepts and Devices’
Division - Name - Date - Language
1
Agenda for the evening: Topic
Presenter
Time
LV Earthing Systems
Asrar Mufti
6.15 to 6.50 pm
LV Type Tested Panelboards
Shanker Shetty
6.50 to 7.30 pm
Break for Salah
7.30 to 7.50 pm
LV Power Circuit Breakers
Irfan Mufti
8.00 to 9.00 pm
LV Final Distribution Boards
Ibrahim Saleh
9.00 to 9.30 pm
Wiring Devices
Mohammad Al-Amoudi 9.30 to 10.00 pm
Dinner
Division - Name - Date - Language
10.00 pm
2
LV Earthing Systems. as per IEC 60364 Installation Standard.
Fire protection
Risk analysis - the origins of fires in buildings
Studies carried out in Germany between 1980 and 1990 Fire 37 %
Lightning 1 %
Explosion 1 %
Cigarettes 6 %
Other 7 %
Electricity 41 %
41 % of fires are electrical in origin this risk is far from negligible it can be eliminated
Division - Name - Date - Language
4
E92446
Accidents 7 %
Fire protection
Main cause Ageing of the installation results in: less effective insulation the risk of very small leakage currents Presence of humidity Leakage currents
Small discharges
E92462
E92461
Carbonisation of insulation (dust)
There is a real risk of fire starting at leakage currents of 300 mA
Division - Name - Date - Language
5
Basic principle
Low Voltage Earthing Systems
Zone 1 : perception Zone 2 : unpleasant sensation
T(ms)
Zone 3 : muscular contractions (reversible effects) Zone 4 : risk of ventricular
10 000 5000
fibrillation.(irreversible)
c1-c2 :prob. increases by 5% c2-c3 :prob. increases by 50% > c3
:prob. more than50 %
IEC 60479-1 Effect of current on the human body Time ms/current mA curve for AC current from 15 to 100 Hz b
c1 c2 c3
2000 1000 500
1
2
3
4
200 100 50
Body Impedance = 2000 Ohms.(Dry) = 1000 Ohms.(Wet) Max. Withstand Current = 25 mA
20 10 0,1 0,2 1 0,5 mA
2
5 10
30 mA
100
500 2000 5000 (mA) 1000
UL (MAX. TOUCH VOLTAGE) = 2000x 0.025 = 50 V (Dry Conditions) = 1000x0.025 = 25 V (Wet Conditions)
Division - Name - Date - Language
6
Standard IEC 60479-1
Protection of people
Critical current thresholds
E92450
mA
Division - Name - Date - Language
1A
Cardiac arrest
75 mA
Irreversible cardiac fibrillation
30 mA
Breathing arrest
10mA
Muscular contraction
0.5 mA
Tingling
7
Standard IEC 60479-1
Protection of people
Effect of frequency Current-sensitivity thresholds (mA) 500
100
30 50
100
1000
(f)
E92451
DC
The human body is most sensitive to frequencies in the 50 Hz/60 Hz range
Division - Name - Date - Language
8
Basic principle
Low Voltage Earthing Systems
Maximum Touch Voltage Time (Protection of people according to IEC 364) Against Indirect Contact with Automatic Disconnection of Supply Maximum touch voltage time in UL = 50 V conditions prospective touch voltage (V) < 50 50 75 90 120 150 220 280 350 500
Division - Name - Date - Language
maximum protective device disconnection time(Seconds) AC current DC current 5 5 0.60 0.45 0.34 0.27 0.17 0.12 0.08 0.04
5 5 5 5 5 1 0.4 0.3 0.2 0.1
Maximum touch voltage time in UL = 25 V conditions (sockets/wet areas) prospective touch voltage (V)
maximum protective device disconnection time(Seconds) AC current DC current
25 50 75 90 110 150 230 280
5 0.48 0.30 0.25 0.18 0.12 0.05 0.02
5 5 2 0.80 0.50 0.25 0.06 0.02
9
Low Voltage Earthing Systems
Basic principle Protection of people, direct contact Definition “Contact of persons or livestock with live parts which may result in electric shock”
Division - Name - Date - Language
10
Low Voltage Earthing Systems
Protection of people, direct contact E36914
Types of protection
Basic principle
Insulation Distance
IP2X or IPXXB
Division - Name - Date - Language
TBT < 25 V
30 mA
11
Standard IEC 60364
Protection of people
Indirect contact
E92454
“Contact of persons or livestock with exposed conductive parts in case of a fault”
Division - Name - Date - Language
12
Low Voltage Earthing Systems
Basic principle Protection of people according to IEC 364
Protection against indirect contact with automatic disconnection of supply Earthing of all the exposed conductive parts of electrical equipment and all accessible conductive parts 2 simultaneously accessible exposed conductive parts must be connected to the same earth electrode Automatic disconnection by a protective device of the circuit in which a dangerous insulation fault occurs The protective device must operate within a time that is compatible with "Maximum Touch Voltage & Time-Safety requirements"
Division - Name - Date - Language
13
Earthing Systems - General rules according to IEC 60364 § 312.2 ■
The Three Earthing Systems 1. 2. 3.
1st letter Situation of supply T = Direct connection of Transformer Neutral with the earth I = Neutral unearthed or Impedance-earthed
Division - Name - Date - Language
T T I
T N T
2nd letter Situation of installation frames T = Exposed frames directly earthed N = Frames connected to the supply point which is earthed, • either by a separate Protective Earth conductor (S). •Or combined with the Neutral (C)
14
Earthing systems
The different types ■ explanation of symbols according to IEC 617-11 (1983) Neutral conductor (N) Protective conductor (PE) Combined protective and neutral conductor (PEN)
Division - Name - Date - Language
15
Low Voltage Earthing Systems
Earthing system technique TT system E36886
Definition The neutral point of the LV transformer is directly connected to an earth electrode
L1 L2 L3 N
Rn
Division - Name - Date - Language
16
Low Voltage Earthing Systems
Earthing system technique TT system E36886
Definition The neutral point of the LV transformer is directly connected to an earth electrode The exposed conductive parts of the installation are connected to an electrically separate earth electrode
L1 L2 L3 N
PE Rn
Division - Name - Date - Language
Ru
17
System earthing arrangements
Earth electrode
"Deep" earth the earth does not act as an insulator
Equivalent electrical circuit "Deep" earth is equipotential in nature… … whatever the distance! 11 Ω 1000 km
"Deep" earth
1Ω
15 Ω
10 Ω
10 Ω
5Ω
Division - Name - Date - Language
E92453
E92452
"Deep" earth
18
Earth electrode
System earthing arrangements
Well designed network At A A →
IPE = 0
L1 L2 L3 N PE
→
→
→
→
→
→
I1 + I2 + I3 + IN = IPE Well designed network
→
→
IPE = 0 →
→
→
I1 + I2 + I3 + IN = 0
Current in the neutral does not depend on current IPE equal to unbalanced load currents and/or 3rd order harmonics (3 k) E92457
→
Division - Name - Date - Language
→
IN = Iunbalance
+ I3k
→
19
Earth electrode
System earthing arrangements
Faulty distribution system
A →
IPE ≠ 0
L1 L2 L3 N PE
Faulty distribution system → IPE ≠ 0 →
→
→
→
I1 + I2 + I3 + IN ≠ 0
→
Current in the neutral does not depend on current IPE equal to unbalanced load
currents and/or 3rd order harmonics (3 k) →
IN = Iunbalance
+ I3k
→
E94409
→
Measurement of current IPE can be used for protection of persons (values depend on the earthing arrangement) protection against fire hazards → However, it is necessary to detect the "true" IPE
Division - Name - Date - Language
20
TT system
System earthing arrangements
Earth-fault study Value of fault current: Uo = 230 V
L1 L2 L3 N
Id = Uo / (Rn + Ru) = 230 / (10 + 10) = 11.5 A
400 V/230 V
Ud = Ru x If Exposed conductive part
Id = 11,5 A
Ud = 115 V Load
= 115 V > UL = 50 V The fault current generates a dangerous touch voltage The SCPD is usually not suitable for eliminating this type of fault
Ru 10 Ω
E95420
Rn 10 Ω
= 10 x 11.5
Division - Name - Date - Language
21
TT system
System earthing arrangements
Earth-fault study Uo = 230 V
400/230 V
SCPD 25 A
I∆
E95421
Rn 10 Ω
Division - Name - Date - Language
Ru 10 Ω
L1 L2 L3 N
n = 5A
Exposed conductive part
Load
Solution The SCPD is usually not suitable for this type of fault (ST setting at 25 A) A residual current device specially designed for the protection of persons Tripping conditions: Max touch voltage < Safety curve Ru x I∆ n < UL (I∆ n is the setting of RCD) I∆ n = UL / Ru = 50 /10 =5A
22
System earthing arrangements
TT system Maximum disconnecting times Standard IEC 60364 converts the exposure-time/current curves of standard IEC 60479-1 into tables presenting the disconnecting-time versus the nominal AC-voltage (Uo) 50 V < Uo ≤ 120 V
120 V < Uo ≤ 230 V 230 V < Uo ≤ 400 V Uo >
400 V
Disconnecting time (s) AC
DC
AC
DC
AC
DC
AC
DC
TT system
5
0.2
0.4
0.07
0.2
0.04
0.1
0.3
From table 41 A of standard IEC 60364
Division - Name - Date - Language
23
SEAs and devices
Earth-leakage protection RCD technologies electromechanical – no auxiliary power required electronic – integrated in SCPD (no auxiliary power required) separate from the SCPD – auxiliary supply required RCDs are immune to nuisance tripping to DC currents (class A as defined by IEC 755)
Division - Name - Date - Language
24
Low Voltage Earthing Systems
Associated switchgear in TT
RCD electromechanical – own current
Division - Name - Date - Language
E37522
Earth leakage protection
25
Low Voltage Earthing Systems
Associated switchgear in TT
RCD electromechanical – own current electronic – integrated in the voltageoperated short-circuit protection device
Division - Name - Date - Language
E37522
Earth leakage protection
26
Low Voltage Earthing Systems
Associated switchgear in TT
RCD technologies electromechanical – own current electronic – integrated in the voltageoperated short-circuit protection device separate from the short-circuit protection device – auxiliary supply
Division - Name - Date - Language
E37522
Earth leakage protection
27
Devices for the TT system
SEAs and devices
Operating principle
Tripping
Operating principle of residual current devices requiring no auxiliary supply (electronic) Detection Measurement
No aux. power required
Detectio n
Earth-leakage relay
E37508
M
Division - Name - Date - Language
Tripping
Measurement
28
SEAs and devices
Devices for the TT system Selection of solutions Electromechanical technology for final distribution Application: protection of life and property in all sectors (industrial, commercial and residential)
E37540
Main characteristics: continuity of service and safe if neutral conductor is cut
Division - Name - Date - Language
29
SEAs and devices
Devices for the TT system Selection of solutions Electronic technology for power distribution Application: general protection from the main low voltage switchboard to the secondary switchboard in industrial and large commercial buildings
E37541
Main characteristics: high-performance solutions wide range of settings (discrimination) miniaturisation solutions for complex installations qualified personnel (lead-sealable relays)
Division - Name - Date - Language
30
SEAs and devices
Devices for the TT system Earth-leakage protection Discrimination RCD1
vertical discrimination
– setting I∆ n1 > 2 I∆ n2 RCD2
– time-delay settings RCD1 > RCD2
E95454
Caution. For an RCD not integrated in the SCPD, RCD2 disconnecting time = tripping time + time delay
E95455
horizontal discrimination
Division - Name - Date - Language
31
Applications
SEAs and devices
Coordination of RCDs
Discrimination rules CB1
Two conditions:
1 2
RCD1
E94442
CB2
RCD2
Division - Name - Date - Language
I∆ n (RCD1) > 2 I∆ n (RCD2) ∆ t (RCD1) > ∆ t (RCD2) + ∆ t (CB2) (including the disconnecting time)
To implement condition 2, it is necessary to know the total breaking time guaranteed for the CB2 + RCD2 combination or to run tests on the combination
32
Applications
SEAs and devices
Coordination of
RCDs
Discrimination rules CB1
Two conditions:
2
RCD1
CB2
E94442
RCD2
Division - Name - Date - Language
1
I∆ n (RCD1) > 2 I∆ n (RCD2) setting (RCD1) ≥ setting (RCD2) +1
Condition 2 is automatically obtained for (RCD2) +1 if RCD2 is combined with a circuit breaker/switch disconnector from the Multi 9 or Compact ranges
33
Applications
RCDs
Coordination of
RCDs
Discrimination rules with Vigirex upstream CB1
Two conditions: 1 I∆ n (RCD1) > 1.5 I∆ n (RCD2) 2 setting (RCD1) ≥ setting (RCD2) +1
Vigi RCD1
CB2
E94442
RCD2
Division - Name - Date - Language
Condition 2 is automatically obtained for (RCD2) +1 if RCD2 is combined with a circuit breaker/switch disconnector from the Multi 9 or Compact ranges
34
System earthing arrangements
Main features of the TT system Protection of persons: fault current is dangerous fault current is too weak to trigger the short-circuit protection devices protection must be practically instantaneous •It is provided by a specially designed RCD device Fire protection: fault current is limited "naturally" managed by RCDs for the protection of persons Continuity of service: ensured by discrimination between the RCDs
Division - Name - Date - Language
35
Low Voltage Earthing Systems
TT Earthing System Conclusion Fault current limited Dangerous touch voltage First fault tripping Human Protection ensured. No Risk of Fire. Continuity of Service simple design use of RCDs system easily extensible.
Division - Name - Date - Language
36
TN system
System earthing arrangements
Definition
E95416
L1 L2 L3 N PE
Division - Name - Date - Language
The neutral point of the LV transformer is directly connected to an earth electrode The exposed conductive parts of the installation are connected by the PE to the same earth electrode
Rn
37
TN-S system
System earthing arrangements
Definition (cont.)
E95417
L1 L2 L3 N PE
Division - Name - Date - Language
The PE and neutral conductor are separate
Rn
38
TN-C system
System earthing arrangements
Definition (cont.)
E95423
L1 L2 L3 PEN
Division - Name - Date - Language
A common conductor is used for both the PE and the neutral conductors (PEN)
Rn
39
System earthing arrangements
TN-C-S system Definition (cont.) In this TN sub-system: L1 L2 L3 PEN
L1 L2 L3 N PE
the upstream part is TN-C
(with PEN) the downstream part is TN-S
(with PE and N)
E95424
Note. A TN-S system may not be used upstream of a TN-C system
Rn
Division - Name - Date - Language
40
System earthing arrangements
TN system Earth-fault study Uo = 230 V
400 V/230 V
The fault current is equal to a Ph/N shortcircuit
Exposed conductive part
Uc
E95425
Fault
Division - Name - Date - Language
ρ =0.025 Ω -mm2/m for Cu. RPE= RPH=0.025 x 50/35 = 32.14 mΩ Id = 230/(2 x 0.3214) = 3578 A.
Id
Rn
L1 L2 L3 N PE
Consider the PH & PE Conductor are Copper, 50 m Long with a X-section of 35 mm2. The Fault Current Id =U0/(RPE +RPH) RPE= RPH=ρ . L/S
This Fault Current will generate a Touch Voltage Uc = RPE x Id = 3578 x 0.03214 = 115 V. Since the fault current depends on the Length of the Lines, it is necessary to check that the Fault Current is more than the Protection Operating Threshold of the CB i.e Id > Ia
41
System earthing arrangements
TN system
The Value of the fault current is: Id = 0.8.Uo. SPH ρ .(1 + m).L
Earth-fault study (cont.) Uo = 230 V
400 V/230 V
L1 L2 L3 N PE
where m=Sph/Spe L=Length of the Cond. Lmax = 0.8Uo. SPH ρ .(1 + m).Ia
Id
If the length of the conductor is greater than Lmax., it is necessary to; Reduce Ia.
Exposed conductive part
Uc
E95425
Fault
Increase Spe. Install an RCD.
Rn
Division - Name - Date - Language
42
TN system
System earthing arrangements
Implementation Uo = 230 V
400 V/230 V
TN-S L1 L2 L3 N PE
PE separate from the neutral Protection SN
of the neutral
= SPH
– disconnected, not protected SN
< SPH
– disconnected, protected Exposed conductive part
E95426
Load
Division - Name - Date - Language
43
TN system
System earthing arrangements
Implementation (cont.) TN-C Uo = 230 V
400 V/230 V
Exposed conductive part
PEN = protective conductor and neutral conductor
Protection of the PEN SPEN = SPH the PEN must not be disconnected
The exposed conductive parts of the substation, the LV neutral and the exposed conductive parts of the loads are connected to the same earth electrode
E95427
Load
L1 L2 L3 PE N
Division - Name - Date - Language
44
System earthing arrangements
TN system Maximum disconnecting times The disconnecting time depends on the distribution-system voltage Uo
50 V < Uo ≤ 120 V
120 V < Uo ≤ 230 V 230 V < Uo ≤ 400 V Uo >
400 V
Disconnecting time (s) AC
DC
AC
DC
AC
DC
AC
DC
TN system
5
0.4
5
0.2
0.4
0.1
0.1
0.8
Drawn from table 41 A of standard IEC 60364
Division - Name - Date - Language
45
Devices for the TN-S system
SEAs and devices
Protection by short-circuit protection devices Protection: for a given cross-section and material (e.g. copper or aluminium), the fault current Id depends on the length of the conductors
t
E95442
t < 0.4 s
I
Id
circuit breaker protection:
setting of magnetic relay / ST
t
E95449
< 30 ms
Division - Name - Date - Language
Im
Id
I
46
Low Voltage Earthing Systems
Earthing system technique
TN system- Checking of the tripping conditions: The max. Length of any circuit of a TN-earthed installation is
0.8.Uo.Sph ρ .(1+m).Ia L = Length of the Conductor. Sph= Cross-Sectional area of Ph. Cond. ρ = resistivity in Ohm-mmsq/metre (22.5 mohm for Cu) m = Ratio between Sph and SPE Ia = Trip Current setting for Inst. Operation of CB. If the condition is not met reduce the magnetic setting install an RCD - LS (up to 250A) Increase Cross-Sectional area of the Cond. L max =
Division - Name - Date - Language
see pg. G20 for Tables.
47
SEAs and devices
Devices for the TN-S system Protection by short-circuit protection devices If the conditions for correct protection are not met
Circuit breaker low setting of magnetic relay/ST or installation of a standard RCD or increase the conductor cross-section
Division - Name - Date - Language
48
SEAs and devices
Applications Protection of property Protection of motors (TN-S system)
R
MERLIN GERIN
E94458
M
a low insulation fault can cause a short-circuit an RCD with a current setting between 3 and 30 A avoids this risk
Division - Name - Date - Language
49
SEAs and devices
Devices for the TN-S system Summary Earth-fault study Uo = 230 V
400 V/230 V
SCPD tripping at 160 A RCD
L1 L2 L3 N PE
The fault current is equal to a phase/neutral short-circuit The fault current generates a dangerous touch voltage The circuit breaker trips Check the loop impedance
Exposed conductive part
Earth-leakage protection set to 300 mA is recommended if there is a risk of fire
E95428
Load Rn
Division - Name - Date - Language
50
Devices for the TN-S system
SEAs and devices
Protection by short-circuit protection devices (SCPD) Discrimination by circuit breakers current LT and ST settings
t D1
D2
E95450
∆1
Im1
I
Im2
time
t D1
D2
intentional delay of the LT and ST upstream protection
E95451
∆ t
I
energy
t D1
D2
comparison of energies (ST)
E95452
∆ I2 t
Division - Name - Date - Language
I
51
SEAs and devices
Devices for the TN-S system Protection by short-circuit protection devices (SCPD)
Merlin Gerin type ranges
TN-C / 3P 3D
TN-S / 4P 3D, 4P 4D
Masterpact
circuit breakers
Compact
Multi 9 Circuit breakers also provide overload protection for all low-voltage system earthing arrangements
Division - Name - Date - Language
52
SEAs and devices
Main features TN-S system
E37542
Protection of persons: fault current is dangerous fault current is usually high enough to trip the SCPDs tripping must be practically instantaneous It is ensured by the magnetic settings on the SCPDs if the fault current is not high enough, RCDs may be used to ensure protection Fire protection: fault current is high it must be managed by additional RCDs Continuity of service: ensured by discrimination between the short-circuit protection devices and among RCDs Division - Name - Date - Language
53
SEAs and devices
Main features TN-C
E37544
Protection of persons: fault current is dangerous fault current is usually high enough to be tripped by the SCPDs tripping must be practically instantaneous = same as TN-S It is ensured by the magnetic settings on the SCPDs if the fault current is not high enough, the installation must be resized Fire protection: cannot be provided (TN-C not allowed where there is a risk of fire) Continuity of service: ensured by discrimination between the SCPDs = same as TN-S
Division - Name - Date - Language
54
System earthing arrangements
TN system Conclusion High fault currents Dangerous touch voltage
Tripping after first fault cost savings check on tripping conditions calculations required for extensions
Division - Name - Date - Language
55
IT system
System earthing arrangements
Definition
The exposed conductive parts of the loads are connected by the PE conductor to a common earth electrode
E95429
L1 L2 L3 N PE
The Neutral point of the LV transformer is Isolated, not connected to an earth electrode
Division - Name - Date - Language
56
IT system
System earthing arrangements
Definition (cont.)
L1 L2 L3 N PE
The exposed conductive parts of the loads are connected by the PE conductor to a common earth electrode or to separate earth electrodes
PE
E95430
PE
The Neutral point of the LV transformer is Isolated and not connected to an earth electrode
Division - Name - Date - Language
57
System earthing arrangements
IT system Earth-fault study
L1 L2 L3
Under Normal operation, the System is earthed by its System Leakage Impedance.
E95431
PE
Division - Name - Date - Language
58
System earthing arrangements
IT system Earth-fault study (cont.) System leakage impedance L1 L2 L3 PE
If=U/Zt =230/3500 =0.065 A Uc=10 x0.065= 0.6V Uc< UL(50V) The touch voltage is not
dangerous There is no risk of fire
E95432
The fault does not cause tripping but it must be indicated
Division - Name - Date - Language
59
System earthing arrangements
IT system Signalling the first fault Detection principle: emission of a specific zero
sequence signal
E95433
L1 L2 L3 PE
Division - Name - Date - Language
60
System earthing arrangements
IT system Signalling the first fault (cont.)
Fault-clearance principle: detection by toroid and indication of the faulty outgoer
E95434
L1 L2 L3 PE
Detection principle: emission of a specific zero sequence signal
Division - Name - Date - Language
61
Devices for the IT system
SEAs and devices
IMD 1st fault I inj
L1 L2 L3 N PE
I inj I inj
RI
I inj
Principle injection of current tracking generator measurement of IR IMD:(Insulation Monitoring Device) DC current: direct measurement of IR AC current: calculation of IR
e I inj
E95435
(IR) Insulation Resistance
Division - Name - Date - Language
62
SEAs and devices
Devices for the IT system IMD 1st fault (cont.) L1 L2 L3 N
Principle of the FTD (*) detection of fault current Type of FTD (*): portable fixed
E95436
PE
(*) Fault Tracking Device
Division - Name - Date - Language
63
SEAs and devices
Devices for the IT system IMD & FTD Merlin Gerin range IMD (*)
FTD (**)
(*) Insulation Monitoring Device (**) Fault Tracking Device
Division - Name - Date - Language
64
SEAs and devices
Devices for first fault RCDs Typical leakage currents following a first fault System leakage capacitance (µF) First-fault current
I∆ n setting
1
70 mA
300 mA
5
360 mA
1A
30
2.17 A
5A
Standardised rule IEC 60364-5-53: The RCD current settings must be greater than twice the first-fault current
Division - Name - Date - Language
65
Protection plan for second fault
SEAs and devices
IT system with interconnected exposed conductive parts (ECP) Study of the 2nd earth fault L1 L2 L3 N PE Id1
Id2
The SCPD protection trips protection is ensured by the same circuit breaker as for TN-S, mais – 4P 4t is compulsory Check the loop impedance
E95437
Merlin Gerin circuit breakers are appropriate for protection in IT systems
Division - Name - Date - Language
66
SEAs and devices
Devices for second fault IT system with ECPs not interconnected Study of 2nd earth fault L1 L2 L3 N
Same principle as TT system (length of conductors) Protection provided by RCDs (same switchgear as TT)
E95438
CPI
Division - Name - Date - Language
67
SEAs and devices
Protection plan for second fault IT system Maximum disconnecting times for IT systems for the 2nd fault 50 V < Uo ≤ 120 V
120 V < Uo ≤ 230 V 230 V < Uo ≤ 400 V Uo >
400 V
Disconnecting time (s) AC
DC
AC
DC
AC
DC
AC
DC
IT system
5
0.4
5
0.2
0.4
0.1
0.1
0.8
Drawn from table 41 A of standard IEC 60364
Division - Name - Date - Language
68
SEAs and devices
Main characteristics of the IT system Protection of persons: the insulation fault is not dangerous
•Protection is ensured by the IT system itself, however a maintenance strategy is required A second fault is dangerous and protection must be ensured by the magnetic setting of the SCPD ’s or the RCDs Fire protection: the fault current is close to zero Continuity of service is total
Division - Name - Date - Language
69
System earthing arrangements
IT system Conclusion First-fault current is very weak First-fault touch voltage is very weak Dangerous touch voltage in the event of a double fault Tripping after the second fault Optimal safety when first fault occurs Continuity of service when first fault occurs Use of IMD for fault tracking Check on tripping conditions Calculations necessary for extensions
Division - Name - Date - Language
70
Low Voltage Earthing Systems
Earthing system technique IT system Conclusion First fault current very weak First fault touch voltage very weak Dangerous touch voltage if there is a double fault Second fault tripping optimal safety when first fault occurs continuity of service when first fault occurs use of PIM for fault tracking checking of tripping conditions calculations necessary for extensions
Division - Name - Date - Language
71
Fire protection
Standard IEC 60364
IE C 603 64 E94550
Standard IEC 60364, section 3-32, defines premises presenting a risk of fire (BE2) or explosion (BE3) Standard IEC 60364, section 4-48, deals with premises where there is a risk of fire imposes use of a 500 mA RCD device recommends use of a TT or IT system for the electrical installation on such premises prohibits use of a TN-C system
In TT, IT and TN-S systems, a 300 mA RCD eliminates the risk of fire
Division - Name - Date - Language
72
Selection of a system earthing arrangement 6 selection criteria Protection of persons Protection of equipment Continuity of the power supply Effects of disturbances Easy implementation Economic analysis
Division - Name - Date - Language
73
System earthing arrangements
Selection of a system earthing arrangement Conclusion Facility managers need a dependable electrical distribution IEC 364 offers solutions which:
E37521
optimally protect persons (systems, RCDs, neutral switching, etc.) minimise the risk of fire (TT, IT systems, RCDs) protect property by limiting leakage/fault currents (IT, TT, TN-S with
RCDs) Mixing of system earthing arrangements is the means to provide optimum solutions to the needs of operators
IEC 364 means a dependable, high-performance installation
Division - Name - Date - Language
74
Low Voltage Earthling Systems
E00000
Earthing Systems Comparison.
Criterion
TT
TN-S
TN-C
IT
Protection of people
XXXX
XXX
XX
XXXX
Protection against Fire
XXXX
XXX
X
XX
Ease of Implementation Continuity of service
XXX XX
X XX
X XX
X XXXX
Upgradable installation
XXXX
XX
XX
XX
Cost Saving
XX
XXX
XXXX
X
XXXX=Excellent
Division - Name - Date - Language
XXX=Good
XX=Average
X=Caution
75