BFU Description DESCRIPTION

9/1551-LZA 701 6001 Uen H

Copyright © Ericsson AB 2010–2012. All rights reserved. No part of this document may be reproduced in any form without the written permission of the copyright owner. Disclaimer The contents of this document are subject to revision without notice due to continued progress in methodology, design and manufacturing. Ericsson shall have no liability for any error or damage of any kind resulting from the use of this document. Trademark List All trademarks mentioned herein are the property of their respective owners. These are shown in the document Trademark Information.

9/1551-LZA 701 6001 Uen H | 2012-10-15

Contents

Contents 1

Product Overview

1

1.1

Purpose

1

1.2

Variants

1

2

Function Description

3

3

Technical Data

5

4

Signal and Power Interfaces

7

4.1

BFU 01 01

7

4.2

BFU 01 02

7

9/1551-LZA 701 6001 Uen H | 2012-10-15

BFU Description

9/1551-LZA 701 6001 Uen H | 2012-10-15

Product Overview

1

Product Overview This document describes the Battery Fuse Unit (BFU). The BFU is located in the power subrack.

1.1

Purpose The main function of the BFU is to supervise and disconnect or connect the battery backup.

1.2

Variants The following variants are available: •

BFU 01 01

BFU 01 01

150 A EC

Ge0088C



BFU 01 02

BFU 01 02

EC

200A

Ge2912A

9/1551-LZA 701 6001 Uen H | 2012-10-15

1

BFU Description

2

9/1551-LZA 701 6001 Uen H | 2012-10-15

Function Description

2

Function Description The BFU has the following functions: •

Disconnecting and connecting the battery backup from system voltage



Supervising the following:

0 0 0 0 •

Current Battery temperature System voltage

Disconnecting battery when:

0 0 0 0 0 •

Battery voltage

Discharging to pre-set battery voltage level Over current Battery over temperature Low battery voltage System voltage out of range

Charge current limiting (Prevention of excessive charging currents that can trip the circuit breaker.)



Remotely controlling disconnection of battery



Cold-starting

Figure 1 shows the block diagram of the BFU.

9/1551-LZA 701 6001 Uen H | 2012-10-15

3

BFU Description

Voltage Measurement

Current Measurement

Voltage Measurement

Battery Switch Battery Side -48V

Battery Temperature Sensor

Hydraulic

System Side -48V

Magnetic Circuit Breaker

Supervision & Control

EC-Bus SK0000915B

Figure 1

4

BFU Block Diagram

9/1551-LZA 701 6001 Uen H | 2012-10-15

Technical Data

3

Technical Data Table 1 lists the technical data of the BFU variants.

9/1551-LZA 701 6001 Uen H | 2012-10-15

5

Maximum Continuous Charge/Discharge Current (A)

135

200

Power Dissipation (W)

45

89

BFU 01 01

BFU 01 02

BFU Technical Data

Technical Data

Table 1

9/1551-LZA 701 6001 Uen H | 2012-10-15 200

150

Circuit Breaker Rating (A)

-40 to +65

-40 to +60

Tempe rature Range (C)

Stops at +35 C



Starts at +40C

Slow charge mode or insufficient system airflow

Stops at +35 C



Starts at +40C

Internal Fan Interval

-38 to -58.5

-38.0 to -57.6

Nominal Input Voltage (V DC)

Input Charact eristics

43

43

Height (mm)

145

145

Width (mm)

225

225

Depth (mm)

Dimensions

≤2

< 1.8

Weight (kg)

BFU Description

6

Signal and Power Interfaces

4

Signal and Power Interfaces This section describes the interfaces of the different BFU variants.

4.1

BFU 01 01 Table 2 lists the details of the external interfaces on BFU 01 01.

Table 2

BFU 01 01 Interfaces (1)

Marking

Description

Connector

Location

No marking

Cabinet system voltage

Bus-bar

Rear

Battery voltage

Anderson SB® 175

Front

Optical indicator, red

N/A

Front

Optical indicator, green

N/A

Front

ECB

RJ-45

Front

Battery temperature sensor

Molex Mini-Fit Jr.™ 2 pol.

Front

Connect or disconnect battery

On/Off switch

Front

(2)

EC

150 A

(1) For more details about optical indicators, see (2) Eclosure Control Bus

4.2

Indicators, Buttons, and Switches.

BFU 01 02 Table 3 lists the details of the external interfaces on BFU 01 02.

Table 3

BFU 01 02 Interfaces

Marking

Description

No marking

(1)

Connector

Location

Cabinet system voltage

Bus-bar

Rear

Battery voltage

Anderson SB® 175

Front

Optical indicator, red

N/A

Front

9/1551-LZA 701 6001 Uen H | 2012-10-15

7

BFU Description

Marking

EC

200A

Description

(1)

Connector

Location

Optical indicator, green

N/A

Front

Optical indicator, yellow

N/A

Front

ECB

RJ-45

Front

Battery temperature sensor

Molex Mini-Fit Jr.™ 2 pol.

Front

Connect or disconnect battery

On/Off switch

Front

(1) For more details about optical indicators, see Indicators,