Engineering data sheet

Chapter:

Cylinder

Item:

200624

Cylinder 80-300 w. INERGEN

Page: 1 of 1

Burst disc

General Complete steel cylinder with INERGEN and hand wheel valve used in Fire Eater INERGEN fire extinguishing systems.

< H2

Specifications Dimension Diameter (D): Wall thickness (t): Height cyl. (H): Height (H1): Height instld. (H2): Weight: Pressure Fill @ 15°C: Test: Volume Water: INERGEN: Colour Cylinder: Shoulder: Standard & approval

H1

267 mm 7.4 1780 mm 1880 mm < 1950 mm 140 kg

H

t

300 bar 450 bar 80 litre 24 m3 EN 1089/3 Red (RAL 3001) Green (RAL 6018) EN1964-2, π 1017 TPED EC1999/36 34CrMo4

D

FI RE XX EA XX X T 0 E R INE O2 RGE N N2-AR-C mm -92 DNV yy ASS 36

25E (W28.8 × 1/14 Keg) M25×1.5

Next test yy/mm

yy/

Material: Tread Cylinder: Valve outlet:

Tested yy/mm

Installation

6 digit serial number

π

Manufacturer's seal

Low Temp

Maintenance Recertification (testing) every 10 years, or as per local authorities having jurisdiction. Pos. Name

Quantity

Item

A: Cylinder 80-300

1

200240

B: Hand wheel valve

1

603308

24

200500

C: INERGEN (m3 )

Text

Document:

200624 Cylinder 80-300 w INERGEN.doc

Product: Mech. Components

Id:

mk

Rev: 31.08.06

Vølundsvej 17 DK- 3400 Hillerød Tel +45 7022 2769 Fax +45 7023 2769

1 2 3 4 5 6 7 8 9

yy

MM

# Na ## t Log XX o ##### H4 , XK 10 0P G X 0 3 yy 17 X ,XL PW -40 m /m CE N196 4-2 C z yyyy

Cylinder tread

Approval stamp

UT 50 BA R

Wall thickness

E 25

x,x

Cylinders must be fixed firmly to wall or floor with suitable brackets. For installations with nozzles directly at the discharge valve the brackets must be able to support the force during discharge. Hand wheel valve must be opened after installation of discharge valve.