1- Circuit Breakers

  • Uploaded by: MohammedSaadaniHassani
  • 0
  • 0
  • June 2020
  • PDF

This document was uploaded by user and they confirmed that they have the permission to share it. If you are author or own the copyright of this book, please report to us by using this DMCA report form. Report DMCA


Overview

Download & View 1- Circuit Breakers as PDF for free.

More details

  • Words: 3,675
  • Pages: 37
‫قواطع الدورة ‪Circuit Breakers‬‬

‫معھد النفط العربي‬

‫قواطع الدورة‬ ‫‪Circuit Breakers‬‬

‫مھند الشيخلي‬

‫‪1‬‬

‫وزارة النفط‬

Circuit Breakers ‫قواطع الدورة‬

‫معھد النفط العربي‬

Circuit Breakers Types & Principles How Circuit Breakers Work Breaker Design The simplest circuit protection device is the fuse. A fuse is just a thin wire, enclosed in a casing, that plugs into the circuit. When a circuit is closed, all charge flows through the fuse wire -- the fuse experiences the same current as any other point along the circuit. The fuse is designed to disintegrate when it heats up above a certain level -- if the current climbs too high, it burns up the wire. Destroying the fuse opens the circuit before the excess current can damage the building wiring. The problem with fuses is they only work once. Every time you blow a fuse, you have to replace it with a new one. A circuit breaker does the same thing as a fuse -- it opens a circuit as soon as current climbs to unsafe levels -- but you can use it over and over again. The basic circuit breaker consists of a simple switch, connected to either a bimetallic strip or an electromagnet. The diagram below shows a typical electromagnet design.

The hot wire in the circuit connects to the two ends of the switch. When the switch is flipped to the on position, electricity can flow from the bottom terminal, through the electromagnet, up to the moving contact, across to the stationary contact and out to the upper terminal. The electricity magnetizes the electromagnet . Increasing current boosts the electromagnet's magnetic force, and decreasing current lowers the magnetism. When the current jumps to unsafe levels, the electromagnet ‫وزارة النفط‬

2

‫مھند الشيخلي‬

Circuit Breakers ‫قواطع الدورة‬

‫معھد النفط العربي‬

is strong enough to pull down a metal lever connected to the switch linkage. The entire linkage shifts, tilting the moving contact away from the stationary contact to break the circuit. The electricity shuts off. A bimetallic strip design works on the same principle, except that instead of energizing an electromagnet, the high current bends a thin strip to move the linkage. Some circuit breakers use an explosive charge to throw the switch. When current rises above a certain level, it ignites explosive material, which drives a piston to open the switch.

Why Circuit Breakers Trip The circuit breaker, the wire and even the wire insulation are all designed to work as a system—and that system has limits. Try to push more current through a circuit than it’s designed for and things start happening (Fig. B). Wires heat up under the burden of carrying the excess current. When this happens, the insulation around the wire can degrade or even melt. When insulation melts, current is no longer confined within the wire. That’s when fires start. Luckily, the circuit breaker senses the excess current and “trips” to stop the flow of power before damage occurs.

(FIG. A ) A PROPERLY FUNCTIONING 15-AMP CIRCUIT

This circuit has wires and a circuit breaker that can easily carry the amperage required by the devices on it. One Simple Equation Helps You Determine If a Circuit Is Overloaded. To start solving the problem, we need to know one simple “rule of thumb” formula. This formula will help us determine if all the electrical stuff on a particular circuit is overloading it. How do they all fit together?

‫وزارة النفط‬

3

‫مھند الشيخلي‬

Circuit Breakers ‫قواطع الدورة‬

‫معھد النفط العربي‬

(FIG. B) AN OVERLOADED CIRCUIT

This circuit has too many energy-demanding devices on it and is trying to carry more amperage than it’s designed for. Things begin to heat up. Luckily the circuit breaker senses this, trips and “breaks” the circuit. The simple formula (Fig. C) tells us how: Watts divided by voltage equals amps. The other equations shown are just other ways of saying the same thing.

FIG. C THE BASIC FORMULA

‫وزارة النفط‬

4

‫مھند الشيخلي‬

Circuit Breakers ‫قواطع الدورة‬

‫معھد النفط العربي‬

But when you plugged in the 1,200-watt space heater, the 10 amps it required, plus the draw of the other two devices, pulled 19.6 amps through a 15-amp system (Fig. B). the system just can’t handle the load. The circuit breaker tolerated this for a while. But when the excess current and resultant heat began deforming the two pieces of metal inside the breaker, they started “pulling the trigger.” And when the metal pieces bent to a certain point, the trigger snapped two contact points apart, interrupting the flow of electricity and shutting down that circuit. If there’s a huge, sudden draw on a circuit, a little electromagnet in the circuit breaker can pull the contact points apart too. If you have fuses, the excess heat melts a wire inside the fuse, which in turn stops the flow of electricity.

Appliance Electric Range

Power Required (watts) 10,000 (240 volts)

Electric Dryer

5,000 (240 volts)

Space Heater

1,000 and up

Clothes Washer

1,150

Furnace (blower)

800

Microwave

700–1,400

Refrigerator (not required)

700

Freezer (not required)

700

Dishwasher

1,400

Central Vacuum

800

Whirlpool/Jacuzzi

1,000 and up

Garbage Disposer

600–1,200

Kitchen Countertop (two circuits) Toaster

900

Coffee maker

800

Toaster oven

1,400

Bathroom Blow dryer

1,000–2,000

FIG. D COMMON DEDICATED CIRCUITS

‫وزارة النفط‬

5

‫مھند الشيخلي‬

‫قواطع الدورة ‪Circuit Breakers‬‬

‫معھد النفط العربي‬

‫‪FIG. E WIRE SIZES‬‬

‫‪THE LARGER 12-GAUGE WIRE can safely carry more amperage than the‬‬ ‫‪smaller 14-gauge wire—without overheating.‬‬

‫قواطع الدورة ولوحات التوزيع‬ ‫‪Circuit Breakers in MV & LV & MCCs‬‬

‫•‬ ‫•‬ ‫•‬ ‫•‬ ‫•‬ ‫•‬

‫قواطع الدورة‬ ‫قواطع الدورة يمكن أن تكون لالستخدام الخارجي أو لالستخدام الداخلي وھي مصممة للعمل‬ ‫تحت جھود كھربائية مختلفة تصل لغاية ‪ 400‬كيلو فولت وھي على أنواع مختلفة مصنفة‬ ‫تبعا لنوع العزل المستخدم فيھا إلخماد الشرارة المتكونة عند فصل أو ربط الدائرة الكھربائية‬ ‫من أنواعھا‪:‬‬ ‫قواطع دورة زيتية ‪ Bulk C.B.‬منھا ما ھو لالستخدام الداخلي أو‬ ‫الخارجي‬ ‫قواطع دورة ھوائية ‪ Air C.B.‬لالستخدام الداخلي و ‪Air Blast C.B.‬‬ ‫لالستخدام الخارجي‬ ‫قواطع دورة ذات الحد األدنى من الزيت ‪ Minimum Oil C.B.‬منھا ما‬ ‫ھو لالستخدام الداخلي أو لالستخدام الخارجي‬ ‫قواطع دورة فراغية ‪ Vacuum C.B.‬منھا ما ھو لالستخدام الداخلي أو‬ ‫الخارجي‬ ‫قواطع دورة ‪ SF6 C.B.‬منھا ما ھو لالستخدام الداخلي أو الخارجي‬ ‫قواطع ‪ Moulded Case C.B.‬ويستخدم للجھد الواطئ في لوحات‬ ‫التوزيع‬

‫مھند الشيخلي‬

‫‪6‬‬

‫وزارة النفط‬

Circuit Breakers ‫قواطع الدورة‬

‫معھد النفط العربي‬

The process of fault clearing has the following sequence: 1- Fault Occurs. As the fault occurs, the fault impedance being low, the currents increase and the relay gets actuated. The moving part of the relay move because of the increase in the operating torque. The relay takes some time to close its contacts. 2 - Relay contacts close the trip circuit of the Circuit Breaker closes and trip coil is energized. 3 - The operating mechanism starts operating for the opening operation. The Circuit Breaker contacts separate. 4 - Arc is drawn between the breaker contacts. The arc is extinguished in the Circuit Breaker by suitable techniques. The current reaches final zero As the arc is extinguished and does not restrict again.

The Trip-Circuit

STANDARD RATINGS OF CIRCUIT BREAKERS AND THEIR SELECTION 1. Rated voltage. 2. Rated insulation level. 3. Rated frequency. 4. rated current. 5. Rated short Circuit Breaking current. 6. Rated transient recovery voltage for terminal faults. 7. Rated short circuit making current. ‫وزارة النفط‬

7

‫مھند الشيخلي‬

Circuit Breakers ‫قواطع الدورة‬

‫معھد النفط العربي‬

8. Rated operating sequence. 9. Rated short time current.

The type of the Circuit Breaker (1) Air break' Circuit Breaker. (Miniature Circuit Breaker). (2) Oil Circuit Breaker (tank type of bulk oil) (3) Minimum oil Circuit Breaker. (4) Air blast Circuit Breaker. (5) Vacuum Circuit Breaker. (6) Sulphur hexafluoride SF6 Circuit Breaker. (Single pressure or Double Pressure).

Type

Medium

Air break Circuit – 1 Air at atmospheric Breaker pressure

.Miniature CB – 2 Air at atmospheric pressure Tank Type oil – 3 .CB .Minimum Oil CB – 4 .Air Blast CB – 5

Voltage, Breaking Capacity -5) –V (600 – 430) MVA(15 500 - KV (12-3.6) MVA V ( 600-430)

Dielectric oil

KV (12 – 3.6)

Dielectric oil

KV( 145 - 3.6)

Compressed Air bar ( 40 – 20)

.SF6 CB – 6

SF6 Gas

KV, 35000 MVA 245 up to 1100 KV, MVA 50000 KV, 1000 MVA 12 KV , 2000 MVA 36 KV, 7500 MVA 145 KV , 10000 MVA 245

.CB Vacuum – 7

Vacuum

KV, 750 MVA 36

.H.V.DC CB – 8 SF6 Gas , Vacuum

‫وزارة النفط‬

8

KV DC 500

‫مھند الشيخلي‬

Circuit Breakers ‫قواطع الدورة‬

‫معھد النفط العربي‬

Bulk Oil Type Breaker

Typical bulk oil circuit break ‫قاطع دورة زيتي‬

‫وزارة النفط‬

9

‫مھند الشيخلي‬

Circuit Breakers ‫قواطع الدورة‬

‫معھد النفط العربي‬

Small Oil Volume Breaker

Small Oil Volume Breaker

‫وزارة النفط‬

10

‫مھند الشيخلي‬

Circuit Breakers ‫قواطع الدورة‬

‫معھد النفط العربي‬

1 – Circuit Breaker pole 2 – Mechanism housing 2a – cover of mechanism housing 3 – Pole head 4 – Pole cylinder 5 – Crank housing 6 – Upper main terminal 13 – Bottom main terminal 22 – Vent housing 23 – 0il level indicator 39a – square on charging shaft 47 – Spring condition indicator 82 – off push - button 88 – on push – button 98 – Circuit Breaker indicator 99 – Operation counter 119 – Lifting hole for transport

‫وزارة النفط‬

11

‫مھند الشيخلي‬

‫معھد النفط العربي‬

‫مھند الشيخلي‬

‫قواطع الدورة ‪Circuit Breakers‬‬

‫‪12‬‬

‫وزارة النفط‬

‫معھد النفط العربي‬

‫مھند الشيخلي‬

‫قواطع الدورة ‪Circuit Breakers‬‬

‫‪13‬‬

‫وزارة النفط‬

Circuit Breakers ‫قواطع الدورة‬

‫معھد النفط العربي‬

MV Air Circuit Breaker

HV Air Blast Circuit Beaker

‫وزارة النفط‬

14

‫مھند الشيخلي‬

Circuit Breakers ‫قواطع الدورة‬

‫معھد النفط العربي‬

The Basic of Arc Extinguishing In Air Blast Circuit Breakers

‫وزارة النفط‬

15

‫مھند الشيخلي‬

‫معھد النفط العربي‬

‫•‬ ‫•‬ ‫•‬ ‫•‬ ‫•‬ ‫•‬ ‫•‬

‫قواطع الدورة ‪Circuit Breakers‬‬

‫جميع أنواع قواطع الدورة تشترك في عملھا و جميعھا تشترك في مكوناتھا وأجزائھا‬ ‫األساسية عدا قواطع الدورة الفراغية ‪ Vacuum Circuit Breakers‬وقواطع الدورة‬ ‫‪ SF6‬حيث أن الجزء الذي تتم به عملية الفصل أو الغلق ) نقاط التماس( تعتبر صندوقا‬ ‫مغلقا ويتم التحكم بھذا الصندوق بميكانيكية خاصة‪ ،‬أما أجزاء بقية أنواع قواطع الدورة فھي‪:‬‬ ‫نقاط التماس الرئيسية ‪. Main Contacts‬‬ ‫نقاط التماس الثانوية ‪. Auxiliary Contacts‬‬ ‫عوازل خزفية للفصل بين األطوار وجسم القاطع‬ ‫مخمد الشرر ‪. Arc Chute‬‬ ‫التوصيالت والعتالت الميكانيكية ‪. Mechanical Linkages‬‬ ‫ملف ‪ Solenoid‬أو محرك ‪ Motor‬إلغراض غلق ‪ Close‬قاطع الدورة‪.‬‬ ‫ملف الفصل ‪ Trip Coil‬وقطع الدورة الكھربائية‪.‬‬

‫‪Vacuum Circuit Breaker‬‬

‫مھند الشيخلي‬

‫‪16‬‬

‫وزارة النفط‬

Circuit Breakers ‫قواطع الدورة‬

‫معھد النفط العربي‬

1 - Vacuum Interrupter 2 - Terminal 3 - Flexible connection . 4 - Support insulators. 5 - Operating rod. 6 - Tie bar. 7 - Common operating shifts . 8 - operating corn . 9 - Locking cam. 10 - Making spring . 11 - Breaking spring. 12 - Loading spring. 13 - Main link.

‫وزارة النفط‬

17

‫مھند الشيخلي‬

‫قواطع الدورة ‪Circuit Breakers‬‬

‫معھد النفط العربي‬

‫‪Vacuum Interrupter‬‬

‫مھند الشيخلي‬

‫‪18‬‬

‫وزارة النفط‬

‫معھد النفط العربي‬

‫مھند الشيخلي‬

‫قواطع الدورة ‪Circuit Breakers‬‬

‫‪19‬‬

‫وزارة النفط‬

Circuit Breakers ‫قواطع الدورة‬

‫معھد النفط العربي‬

SF6 Circuit Breaker (GIS)

SF6 C.B Horizontal PLUG IN

‫وزارة النفط‬

20

‫مھند الشيخلي‬

‫قواطع الدورة ‪Circuit Breakers‬‬

‫معھد النفط العربي‬

‫‪SF6 C.B & Cubical Vertical PLUG IN‬‬

‫مھند الشيخلي‬

‫‪21‬‬

‫وزارة النفط‬

Circuit Breakers ‫قواطع الدورة‬

‫معھد النفط العربي‬

Summary of Merits of SF6 GIS Safe Operating personnel are protected by the earthed metal enclosures Reliable

‫وزارة النفط‬

22

‫مھند الشيخلي‬

Circuit Breakers ‫قواطع الدورة‬

‫معھد النفط العربي‬

The complete enclosure of all live parts guards against any Impairment of the insulation system. Space saving SF6 Switchgear installations take up only 1/10 of the space Required for conventional installations. Economical High flexibility and application versatility provide novel, and economic overall concepts. Maintenance free An extremely careful selection of materials. an expedient design and a high standard of manufacturing quality assure Long service life with practically no maintenance requirement. Low weight Low weight due to aluminum enclosure, correspondingly Low cost foundations and buildings. Shop assembled Quick site assembly ensured by extensive preassembly and Testing of complete feeders or large units in the factory. Disadvantages of GIS: 1- High cost compared to conventional outdoor substation. 2 - Excessive damage in case of internal fault. Long outage periods as Repair of damaged part at site may be difficult. 3 - Requirement of cleanliness is very stringent. Dust or moisture can cause internal flashovers. 4 - Such substations are generally in door. They need a separate building.

‫وزارة النفط‬

23

‫مھند الشيخلي‬

‫قواطع الدورة ‪Circuit Breakers‬‬

‫معھد النفط العربي‬

‫‪This is generally not required for conventional outdoor‬‬ ‫‪substations.‬‬ ‫‪5 - Procurement of gas and supply of gas to site is‬‬ ‫‪problematic.‬‬ ‫‪Adequate stock of gas must be maintained.‬‬ ‫‪6 - Project needs almost total imports including SF6 Gas.‬‬ ‫‪Spares conventional‬‬ ‫‪substation is totally indigenous up to 400 kV.‬‬

‫الفحص و التدقيق و الصيانة الوقائية‬ ‫فحص دوري على وضع قواطع الدورة التي ھي بالعمل‬ ‫‪.1‬‬ ‫إظھار األعطاب و العيوب والتحضير لمعالجتھا والتي يمكن أن تتفاقم مع‬ ‫‪.2‬‬ ‫الوقت عند تركھا بدون معالجة واستمرار بالتشغيل مما قد يصعب في عملية‬ ‫إصالحھا مستقبال وإطالة فترة الصيانة وزيادة في كلفتھا‬ ‫وجوب المرور على المحطات الثانوية مرة واحدة على األقل يوميا مع‬ ‫‪.3‬‬ ‫وجوب المرور للكشف ليال مرة واحدة في األسبوع وبدون تشغيل اإلنارة لمالحظة‬ ‫ظاھرة الھالة أو الكورونا ‪ Corona‬أو تواجد أي أثر لشرر في القواطع ومفاتيح‬ ‫الفصل وخصوصا في المحطات الخارجية‪.‬‬ ‫عند المرور على المحطات الثانوية مالحظة وتتبع األصوات الغريبة و‬ ‫‪.4‬‬ ‫األزيز‪ ،‬كذلك متابعة ارتفاع درجة حرارة والسخونة الغير طبيعية لجسم المعدات‬ ‫وخصوصا الجزء الذي تقع عنده القضبان الرئيسية ‪. Main Bus Bar‬‬ ‫بالنسبة للمحطات الثانوية غير المسكونة يجب المرور عليھا مرة واحدة‬ ‫‪.5‬‬ ‫شھريا على اقل تقدير‪.‬‬ ‫‪ .6‬بعد أي فصل لقاطع الدورة من جراء عطب تجاوز في الحمل وعطب تأرض‬ ‫يتوجب المرور على المحطة الثانوية للمعاينة وخصوصا أن كانت مرحالت‬ ‫الحماية متواجدة في غرفة السيطرة العامة أو زر إعادة نصب و تحفيز وتھيئة‬ ‫المرحل ھناك‪.‬‬ ‫بالنسبة لقواطع الدورة على المغذيات لخطوط ھوائية فيمكن إعادة غلق قاطع الدورة‬ ‫لمرة واحدة في حالة الفصل على عطب تأريض بعد زيادة تحسس مرحل الحماية‬ ‫والفصل وال يجوز ذلك في حالة الفصل على عطب التجاوز في الحمل ويجب أن ال‬ ‫ننسى من إعادة تحسس المرحل إلى ما يجب أن يكون عليه‪ ،‬أما بالنسبة للمغذيات‬ ‫بواسطة القابلوات فيجب فحص القابلو والتأكد من صالحيته قبل إعادة غلق قاطع‬ ‫الدورة‪.‬‬ ‫‪ .7‬يجب إعطاء المحطات الثانوية الخارجية عناية أكبر من المرور والكشف عليھا‬ ‫بفترات متقاربة خصوصا في حالة تعرضھا لألتربة و الملوثات البيئية أو حصول‬ ‫ظروف جوية سيئة من عواصف وأمطار‪.‬‬ ‫‪ .8‬تسجل كل المالحظات واالعطاب في سجل الوقائع اليومية ويعمل على برمجة‬ ‫معالجتھا أول بأول‪.‬‬

‫مھند الشيخلي‬

‫‪24‬‬

‫وزارة النفط‬

‫قواطع الدورة ‪Circuit Breakers‬‬

‫معھد النفط العربي‬

‫‪ .9‬فحص كافة العوازل الخزفية ونقاط االتصال مع ساعد التوزيع ‪Bushing‬‬ ‫‪ Contacts‬وكافة األجزاء الحاملة للتيار في قواطع الدورة وكذلك عمل وقراءة‬ ‫أجھزة القياس والحماية وحرية دوران أقراصھا‪ ،‬وذلك على فترات دورية وكل ما‬ ‫سنحت الفرصة وخالل التوقفات غير المبرمجة‪.‬‬ ‫‪ .10‬فحص مستوى الزيت وعدم وجود رشح او تسريب ومالحظة ضغط غاز ‪ SF6‬و‬ ‫الضغط الفراغي في قواطع الدورة وحسب نوعھا‪.‬‬ ‫‪ .11‬فحص منظومة اإلنارة و اإلنارة الطارئة ومنظومة االتصال األرضي‪.‬‬ ‫‪ .12‬فحص بناية المحطة الثانوية ومحيطھا والتأكد من عمل أجھزة التكييف وأجھزة‬ ‫مكافحة الحريق وتوفر األقفال وإشارات وعالمات التحذير‪.‬‬ ‫‪ .13‬فحص األجھزة االحتياطية والتأكد من جاھزيتھا لالستخدام عند الحاجة‪.‬‬ ‫خصائص غاز ‪ SF6‬المستعمل في قواطع الدورة وخصائصه الكھربائية‬ ‫‬‫‬‫‬‫‪-‬‬

‫يتصف بدرجة عزل ممتازة جدا و تعادل تقريبا ثالثة أضعاف الھواء عند الضغط‬ ‫الجوى و تزداد متانة العزل بزيادة الضغط‪.‬‬ ‫له قدرة على نقل درجة الحرارة ضعف الھواء مما يجعله يساعد على عملية‬ ‫التبريد‪.‬‬ ‫غاز خامل ال يتفاعل مع المواد التي تتكون منھا معدات الجھد العالي مما يمنع‬ ‫حدوث تآكل في جسم المعدة‪.‬‬ ‫غاز مستقر بمعنى أنه عند تحلله بسبب تعرضه لدرجات حرارة عالية نتيجة ألي‬ ‫حالة قصر فانه يعيد تكوين نفسه مرة أخرى حيث أنه من الغازات سالبة القطبية‪.‬‬

‫اختبار المفاتيح الكھربائية و ‪MCB‬‬ ‫يكون ذلك عن طريق اختبار عملية الفصل وتوقيتھا ‪ Trip Test‬ففي االختبارات‬ ‫الروتينية والتي تجرى على القواطع الكھربائية عادة يتم إجراء ما يلي‪:‬‬ ‫ اختبار العزل للقاطع ويجرى االختبار على جھد اختبار ‪ 3‬ك ف في حالة قواطع‬‫الجھد المنخفض ولزمن ‪ 60‬ثانيه‪.‬‬ ‫ اختبار الفصل الحراري ‪ ,‬حيث يتم توصل أطراف القاطع على التوالـي ثم يتم‬‫توصيل القاطع بجھاز الفحص ليتم حقن تيار ) ضعف التيار المضبـوط عليه القاطع‬ ‫( ويحسب الوقت الذي يتم عنده حدوث الفصل ‪ , The Trip‬وبعد ذلك يضرب‬ ‫الناتج في معامل درجة الحرارة ‪ Temperature Factor‬لدرجة الحرارة‬ ‫التي تم عند ھـــــــــا االختبار‪ ,‬ودرجة الحرارة المسجلة على منحنى خواص‬ ‫القاطع‪ ,‬ويتم عمل المقارنة‪.‬‬ ‫ اختبار القصر ‪ -‬يتم عمل قصر على ‪ 2 Poles‬من القاطع وبعد ذلك يتم حقن‬‫تيار بالقاطع حسب تيار القصر للقاطع ‪ 5In‬على سبيل المثال‪ ,‬ويتم اختبار سرعة‬ ‫الفصل عند حدوث القصر والتي تقدر ‪ 0.01‬ثانيه تقريبا ً‪.‬‬

‫مھند الشيخلي‬

‫‪25‬‬

‫وزارة النفط‬

‫قواطع الدورة ‪Circuit Breakers‬‬

‫معھد النفط العربي‬

‫لوحات التوزيع ‪Distribution Boards‬‬ ‫تمثل لوحات التوزيع المستخدمة للجھد الواطئ ‪ 400‬فولت عن تجميع لعدة أجھزة تؤدي‬ ‫فعاليات مختلفة ومتكاملة في حد ذاتھا وقد تكون متممة لبعضھا اآلخر‪ ،‬ويجب أن تحوي‬ ‫أساسا على مغذي رئيسي متصل بقضبان رئيسية من خالل مفتاح يدوي او قاطع دورة‬ ‫أوتوماتيكي او في بعض األحيان جھاز تالمس لتتصل بھا أجھزة أخرى وتستمد الطاقة‬ ‫الكھربائية منھا لتؤدي المھمة المطلوبة منھا‪.‬‬ ‫تغذى ھذه األجھزة و المعدات بالطاقة الكھربائية من خالل مفاتيح كھربائية فقط او مفاتيح‬ ‫كھربائية ذات مصاھر أو من خالل مصاھر فقط وھذا يمثل ابسط أشكال التغذية والسيطرة‬ ‫عليھا‪ .‬وقد تكون التغذية والسيطرة عليھا بواسطة قاطع للدورة ) بداھة تكون سعة قاطع‬ ‫الدورة الفرعي أقل من سعة قاطع الدورة الرئيسي ( أو بواسطة أجھزة تالمس بمختلف‬ ‫أنواعھا وأشكالھا‪.‬‬ ‫في بعض األحيان وفي لوحات التوزيع الفرعية خصوصا يستغنى عن مفتاح او قاطع الدورة‬ ‫الرئيسي حيث تغذى اللوحة مباشرة من اللوحة الرئيسية بواسطة قابلو فقط وھكذا تكون‬ ‫السيطرة على اللوحة الفرعية وحمايتھا من خالل قاطع الدورة المغذي للوحة الفرعية )‬ ‫الموجود في اللوحة الرئيسية ( والمتصل به القابلو وھذا األجراء ھو لتقليل الكلفة وال ينصح‬ ‫بمثل ھذا األسلوب عندما يكون البعد بين لوحة التوزيع الرئيسية ولوحة التوزيع الفرعية‬ ‫كبيرة أي أن يكون القابلو طويل‪.‬‬ ‫القضبان الرئيسية في لوحات التوزيع تكون عادة من قضبان النحاس او األلمنيوم او حتى من‬ ‫األسالك النحاسية المعزولة‪ ،‬ال تكون ھذه القضبان بحجم واحد ولكن تتدرج بالحجم نزوال بما‬ ‫يناسب التيار الكھربائي الذي تحمله وتيار عطب القصر الذي يمر بھا وھناك مقايسة عالمية‬ ‫تحدد ذلك‪.‬‬ ‫تنظم مصادر التغذية الخارجة داخل لوحة التوزيع بعدة أشكال وطرق وترتبط بالقضبان‬ ‫الرئيسة او الفرعية بصورة ثابتة او بصورة متحركة من خالل أدراج وكما مبين في األشكال‬ ‫الالحقة‪.‬‬ ‫ان الصيانة الوقائية والعامة لھذه اللوحات من حيث األساس مماثلة لتلك التي تجرى على‬ ‫بادئات التشغيل والسيطرة على المحركات الكھربائية وقواطع الدورة لوحات قواطع الدورة‬ ‫وكذلك بالنسبة لتحديد األعطال كما تم ذكرھا في موضوع بادئات تشغيل آنفا‪.‬‬

‫مھند الشيخلي‬

‫‪26‬‬

‫وزارة النفط‬

‫معھد النفط العربي‬

‫مھند الشيخلي‬

‫قواطع الدورة ‪Circuit Breakers‬‬

‫‪27‬‬

‫وزارة النفط‬

‫معھد النفط العربي‬

‫مھند الشيخلي‬

‫قواطع الدورة ‪Circuit Breakers‬‬

‫‪28‬‬

‫وزارة النفط‬

‫معھد النفط العربي‬

‫مھند الشيخلي‬

‫قواطع الدورة ‪Circuit Breakers‬‬

‫‪29‬‬

‫وزارة النفط‬

Circuit Breakers ‫قواطع الدورة‬

‫معھد النفط العربي‬

Optional Accessory to the Circuit

‫إضافات اختيارية لقواطع الدورة‬ Barkers

Key lock When it is locked by a key, the closing operation is not available (electrically and mechanically) without a Key.

Button padlock Button padlock protects ‘ ON’ or ‘Trip’ button when accident is occurred by operation at discretion. It is available to operate after release button padlock.

Button cover Button corer protects ‘ON’ of ‘Trip’ button when accident is occurred by operation at discretion. It is available to operate by push bar.

‫وزارة النفط‬

30

‫مھند الشيخلي‬

Circuit Breakers ‫قواطع الدورة‬

‫معھد النفط العربي‬

Position switch (Cell switch) Indicating the position (Run or Test) of a CB, by mechanically pressing the switch when a CB change the position. - RUN : 2a - TEST: 2a

‫وزارة النفط‬

31

‫مھند الشيخلي‬

Circuit Breakers ‫قواطع الدورة‬

‫معھد النفط العربي‬

Secondary coil (Preparatory trip coil) The main coil and the preparatory coil is connected in parallel. So even though there happens a fault in the trip coil, the CB can be tripped by one of the two trip coils.

Latch checking switch When the Latch is in abnormal position, the Latch checking switch prevent the closing operation even though there is the 'Closing' signal.

Charge indicator Remotely indicates the charging is completed. (Standard Feature)

‫وزارة النفط‬

32

‫مھند الشيخلي‬

Circuit Breakers ‫قواطع الدورة‬

‫معھد النفط العربي‬

Position padlock The hole to prevent the draw-in and out of a VCB from the present position. ('Run' or 'Test') (Hole size = ф 8)

‫وزارة النفط‬

33

‫مھند الشيخلي‬

Circuit Breakers ‫قواطع الدورة‬

‫معھد النفط العربي‬

Earthing switch For the safety during the maintenance of a CB panel, discharge the charging current in the load side of a CB with this earthing switch.

Padlock of earthing switch The hole to prevent the accident through carelessness earthing switch operation, the locking of the earthing switch is available when the switch is in 'OFF' position. (Hole size = ф 8)

‫وزارة النفط‬

34

‫مھند الشيخلي‬

Circuit Breakers ‫قواطع الدورة‬

‫معھد النفط العربي‬

Position switch of the earthing switch Indicates the 'ON' or 'OFF' status of the earthing switch. (5a 5b)

Locking coil of earthing switch To prevent the accident through carelessness earthing switch operation, the earthing switch can be changed to 'ON' position after releasing the lock by magnetizing the coils.

‫وزارة النفط‬

35

‫مھند الشيخلي‬

Circuit Breakers ‫قواطع الدورة‬

‫معھد النفط العربي‬

Shutter padlock -Standard offer in the draw-out type The hole to lock the shutters (load and line side) in close position, to increase the safety during the maintenance of a VCB draw-out position. (Hole size = ф 8)

Mechanically operated cell switch (MOC) The auxiliary switch (3a4b), which Indicate the 'ON' or 'OFF' condition of a CB, but operated only when the VCB is in 'Run' state. (Installed in the bottom of a cradle)

‫وزارة النفط‬

36

‫مھند الشيخلي‬

Circuit Breakers ‫قواطع الدورة‬

‫معھد النفط العربي‬

Truck operated cell switch (TOC) The auxiliary switch (3a4b), which indicate the 'Run' state of a VCB and is operated by the movement of a VCB frame. (Installed in the bottom of a cradle)

Standard Tool

‫وزارة النفط‬

37

‫مھند الشيخلي‬