Integrated Variable Refrigerant Flow AHU/PAU (R410A)

CONTENTS

Features of VRF AHU/PAU

2

WELAIRE i-GT Concept

9

VRF Outdoor Unit Performance Data

10

Drawings & Performance Data

12

Dimensions 13

Notes 14

Features of VRF AHU/PAU Designing of air conditioning system is simple, no water pump, no cooling tower and no cooling / chilled water piping Simple control system, built-in controls for VRF outdoor unit plus field installed LMCP for AHU/PAU Integrated package with VRF system Easy installation and maintenance Simple cable and refrigerant piping connection Max 224kW (80HP) cooling capacity Built-in backup, interlock and heat pump operation Long pipe run available for greater design flexibility Excellent full load COP for VRF outdoor unit (10HP) is 3.6, 50% COP is 4.3 Custom design of AHU/PAU arrangement to improve IAQ

Flexible Design Exhaust Air Fan

EX

Heat Wheel or Heat Pipe (Optional) Filter Supply Air Fan VRF AHU/PAU

OA

EEV Control Unit

RA

SA

Filter

Humidifier (Optional)

Variable Refrigerant Flow Outdoor Unit

Re-heat DX Coil (Optional)

A pair of Refrigerant Tube

one

eZ rvic

Sup

Se ply

Air

Retu r

DX Cooling Coil Variable Refrigerant Flow Outdoor Unit

n Ai

r 2

Simple Installation Compare VRF AHU to chiller plant system VRF AHU/PAU system PAU

Chiller system Pump PAU

om Machine Ro Chiller Water Tank

VRF AHU/PAU Simple Design



Easy Installation



Easy Maintenance



Low Running Cost



System Integration



Chiller System

Better Fresh Air Treatment Compare Custom made VRF PAU to VRF Conventional Fresh Air Pre-treated Unit

3

VRF PAU system

Traditional VRF System for Fresh Air

Up to 6,000 l/s or even more

Small air flow rate (Max. 1800l/s)

Large cooling capacity (up to 80HP)

Small cooling capacity (Max. 20HP)

Large external static pressure provided (up to 1,800Pa)

Limited external static pressure (Max. 150Pa)

Lots of IAQ options (Eg. dehumidifier, UV light, PCO, Heat pipe or heat wheel)

No space to install IAQ components

Excellent Energy Saving Compare VRF AHU to Traditional DX AHU Y SAVING ● RG E NE

3.0

with "ON/OFF" control

2.0

g

SAVING ● RGY E NE

VRF Outdoor (10HP) Outdoor with 2 scroll compressor (10HP)

4.0

gy Ener in

Sav

SAVING ● GY E ER

5.0

Y SAVING ● E RG N NE

COP

Custeosmign D

1.0 0

100%

Load %

Part Load (50%)

on & stallati ce n I y s a E nan Mainte

Comfort Temperature Control Compare VRF AHU to Traditional DX AHU - Preventive of temperature hunting Temp. Zone Temperature

Temp.

Supply air temperature is closer to setpoint Zone temperature is kept tightly near setpoint at all times by continuous load-matching operation.

Zone Temperature

Supply air temperature will be colder than needed due to excess capacity Zone setpoint is maintained by on-off cycling

Setpoint

Setpoint Time

With VRF compressor

With Scroll compressor

Time

Post-cooling unit - Improve the existing chiller plant

NEW

60mm thick double skin casing DX Cooling Coil

OLD 12°C

16°C Duct

Post-Cooling Section or Heat mode is standard provision for heating or dehumidifying

AHU

Chiller JJ JJ JJ JJ JJ JJ JJ JJ JJ JJ

r

ller system with g ch i n i t s i ooling capacity Ex ient c c i f f insu

4

Control System Compare VRF AHU to Traditional DX system - Interlock function - Duty and Standby function When AHU started operation, it If the duty AHU have fault, the activates PAU to run automatically standby AHU will be cut-in with simple wiring connection automatically in 30 seconds

AHU "ON" Automatic Mode

PAU "ON"

Alarm occured (Duty Unit)

Duty & Standby Mode

Unit "ON" (Standby unit)

AHU/PAU Timer wired remote controller

-Function ON/OFF - Mode setting - Temperature setting (AHU only) - Weekly program - Alarm history

NEW

System Controller Individual control is possible for Max. 32 AHUs. Control of 32 AHUs / PAUs individually into 4 zones. (One zone can have up to 8 units) Control is possible for ON/OFF, operation mode, operation monitoring, alarm monitoring, remote controller local operation prohibition, etc…

Serial Interface for LonWorks Network

LonWorks Interface Board

5

This interfaces is a communication converter for connecting LonWorks to the control network. From the host connected to LonWorks, basic settings of status monitoring is possible for up to 32 no. of AHU/PAU.

Simple Wiring Requirement

LonWorks Interface LON

Center Control Device (Field Supply)

LonWorks Communication Line

System Controller (Max. 64nos. AHU/PAU)

System Overview B

K C

A

A

J

Expansion valve

Remote control can be easily installed on the AHU Kit box. Remote control must be purchase separately.

Thermistor x2 (Refrigerant: E1, E3)

Thermistor x2 (x1 in PACi) (Air: Tf, Tb)

www.eggeassociats.net

AIR HANDLING UNIT KIT TO CONNECT TO YOUR VENTILATION SYSTEM 5-25 kW FOR PACi 28 kW AND 56 kW FOR ECOi AND GHP AHU CONNECTION KIT

PCB, Power trans, Terminal block

Optional parts: Following functions are available by using different type of control accessories: CZ-RTC2 Wired remote controller · Operation-ON/OFF · Mode select · Temperature setting

F

* Fan operation signal can be

without the express authorisation of Panasonic UK Ltd. warning in order to improve the product. The total or partial reproduction of this catalogue is prohibited typographic errors, and may be subject to minor modifications by the manufacturer without prior Due to the ongoing innovation of our products, the specifications of this catalogue are valid barring

taken from the PCB.

CZ-T10 terminal · Input signal= Operation ON/OFF · Remote controller prohibition · Output signal= Operating-ON status · Alarm output (by DC12 V)

G

OPTIONAL REMOTE CONTROLLER

Standard wired remote controller.

CZ-RTC2

PAW-OCT, DC12 V outlet. Option terminal · Output signal= Cool / Heat/Fan status · Defrost · Thermostat-ON CZ-CAPBC2 Mini seri-para I/O unit · Temperature setting by 0-10 V or 0-140 Ω input signal · Room (inlet air) temp outlet by 4-20 mA · Mode select or/and ON/OFF control · Fan operation control · Operation status output/ Alarm output

PRO Club Calculation software is available on www.panasonicproclub.com Or connect simply with your Smartphone to the PRO Club using this QR.

SYSTEM & REGULATIONS. SYSTEM OVERVIEW A: AHU Kit controller box (with control PCB) B: AHU Kit equipment (Field supplied) C: AHU Kit system controller (Field supplied) D: Outdoor unit F: Gas piping (Field supplied)

G: Liquid piping (Field supplied) H: Electronic expansion valve I: Thermistor for Gas pipe J: Thermistor for Liquid pipe K: Thermister for Suction air L: Thermistor for Discharge air

Technical Zoom · Maximum capacity: 60 HP (168 kW) · Maximum piping length: 180 m · Maximum total piping: 210 m · Elevation difference (in/out): 50 m (outdoor unit above) · Elevation difference (in/in): 4 m · In/Out capacity ratio: 50~100%. Maximum indoor units number: 2 units · Available temperature range in Heating: -15~15.5 °C · Available temperature range for the suction air at AHU Kit: Cool: 15~24 °C / Heat: 10~30 °C CZ-280PAH1 // CZ-280MAH1 // CZ-560MAH1 · The system controlled by the suction air (or return air from room) temperature as same as standard indoor unit. (Selectable mode: Automatic / Cooling / Heating / Fan / Dry (but same as Cool) · The discharge air temperature is also controlled to prevent too-low air discharge in Cooling or too-high air discharge in Heating. (in case · Demand control (Forcible thermostat-OFF of VRF system) control by operating current) · Defrost operation signal, Thermo-ON/OFF states output · Drain pump control (Drain-pump and the float switch to be supplied in local) · External target temperature setting via Indoor/Outdoor signal interface is available with CZ-CAPBC2. (Ex. 0 – 10 V) · Connectable with P-LINK system · Fan control signal from the PCB can be used for control the air volume (High/Mid/Low and LL for Th-off)

H

Cooling G capacity Nominal kW CZ-280MAH1 28.0 CZ-560MAH1 56.0 CZ-280MAH1 + CZ-560MAH1 84.0 CZ-560MAH1 x2 112.0 CZ-560MAH1 x2 + CZ-280MAH1 140.0 CZ-560MAH1 x3 168.0 AHU Connection Kit / System

Heating capacity Nominal kW 31.5 63.0 95.0 127.0 155.0 189.0

PACi 2-PIPE ECOi 6N SERIES

ECO G AND ECO G MULTI

To find out how Panasonic cares

28 kW (10 HP) 56 kW (20 HP) 84 kW (30 HP) 112 kW (40 HP) 140 kW (50 HP) 168 kW (60 HP) 56 kW (20 HP)

A

HP 10 20 30 40 50 60

B

E

A

L J

I K

Horsepower Cooling Airflow Bypass Factor

Dimensions of the box High / Low HxWxD m³/min mm 5,000 / 3,500 0.9 (recommended) 420 x 280 x 160 10,000 / 7,000 0.9 (recommended) 420 x 280 x 160 15,000 / 10,500 0.9 (recommended) 420 x 280 x 160 20,000 / 14,000 0.9 (recommended) 420 x 280 x 160 25,000 / 17,500 0.9 (recommended) 420 x 280 x 160 30,000 / 21,000 0.9 (recommended) 420 x 280 x 160

Combination Capacity (HP) All capacities

C E

L H

AHU CONNECTION KIT, 28 kW AND 56 kW FOR ECOi AND ECO

I

C B

H

F D G

J

I K

F D G

Piping length Elevation Pipe Diameters Intake temperature of Ambient diff. (in/out) temperature AHU Kit of outdoor unit Max Liquid pipe Gas pipe Min / Max Min / Max m Inch (mm) Inch (mm) °C °C 10 3/8 (9.52) 7/8 (22.22) Cooling:18 - 32DB Cooling: -5 - 43 DB / 10 5/8 (15.88) 1 1/8 (28.58) (13 - 23 WB) / Heating: -15 - 15.5 WB 10 3/4 (19.05) 1 1/4 (31.75) Heating:16 - 30 DB 10 3/4 (19.05) 1 1/2 (38.15) 10 3/4 (19.05) 1 1/2 (38.15) 10 3/4 (19.05) 1 1/2 (38.15)

Min / Max m 10 / 100 10 / 100 10 / 100 10 / 100 10 / 100 10 / 100

Outdoor unit combination Common use for all outdoor units Standard and Elite U-10ME1E81 U-20ME1E81 U-16ME1E81 U-14ME1E81 U-20ME1E81 U-20ME1E81 U-18ME1E81 U-16ME1E81 U-16ME1E81 U-20ME1E81 U-20ME1E81 U-20ME1E81 U-20GE2E5

AHU kit combination CZ-280PAH1 (Only 1 by 1 connection is allowed) CZ-280MAH1 CZ-560MAH1 CZ-560MAH1 CZ-280MAH1 CZ-560MAH1 CZ-560MAH1 CZ-560MAH1 CZ-560MAH1 CZ-560MAH1 CZ-560MAH1 CZ-560MAH1

E

CZ-280MAH1 CZ-560MAH1

for you, log on to: www.aircon.panasonic.e

Contact Details: Telephone: 01344 853182 Address: Panasonic Air Conditioning: / www.aircon.panasonic.eu Panasonic House // Willoughby Road // Bracknell // Berkshire // RG12 8FP

u

D

A : AHU kit controller box (with control PCB) B : AHU unit C : VRF outdoor unit D : Gas piping (field supplied) E : Liquid piping (field supplied) F : Electronic expansion valve G : Thermistor for gas pipe H : Thermistor for liquid pipe I : Thermistor for suction air J : Thermistor for discharge air K : Fan local control panel (optional)

Flexible Refrigerant piping design

Level difference between PAU/AHU & outdoor unit 50M (Outdoor unit above) 40M (Outdoor unit below) Equivalent tubing length available up to 120M

6

Optional - EC Plug Fan Transformation of Power

Comparison level for ηe(s)

Po

Features of EC Plug Fan - Compact design - Integrated assembly - Built in control - Infinitely variable speed settings - Control signal 0-10 V DC and MODBUS - Compatible with existing BMS - High energy saving potential Maintenance Aspect between Centrifugal Fan & EC Plug Fan

Centrifugal Fan

Fan Bearing Fan Shaft Belt Pulley

7

Regular greasing Potential breakage Alignment, wear & tear Alignment

EC Plug Fan

None None None None

Other Features A. Operating Range - Cooling & Heat pump mode Heating operation range: Extended heating operation range enables heating even when the outdoor temperature is as low as -25°C. Using a wired remote control, indoor heating temperature range can be set from 16°C to 30°C*.

Outside air temperature (°C WB)

-25 -20

-15

-10

-5

0

5

10

1518

Outside air temperature (°C DB)

Cooling operation range: -10°C DB to +52°C DB

-10

* Depending on the type of remote controller

-5

0

5

10

15

20

25

30

35

40

52

B. Extended compressor life by uniform compressor operation time The total run-time of compressors are monitored by a built-in microcomputer, which ensures that operation times of all compressors within the same refrigerant circuit are balanced.

Compressors with histories showing shorter run times are selected first, ensuring equal wear and tear across all units and extended the working life of the system.

System example A,C : DC inverter compressor B,D : Constant speed compressor

A B

C D

Load increase

A B

C D

Load increase

A B

C D

Load increase

C D

A B

* Depending on accumulated operation time of each compressor * Compressor priority has possibility to be changed (e.g) Case1: AACABAD, Case2: CAAADAB, Case3: AACADAB, Case 4: CAAABAD * Also other cases available

C. Automatic backup operation in the case of compressor failure or outdoor unit malfuction (Except for single unit installation) Backup operation allows uninterrupted cooling or heating to continue whist waiting for service. Users should contact their authorized service centre as soon as fault occurs.

Even if fan motor or sensor fail

X X NEW function

Even if a whole outdoor unit fails

X The other outdoor unit can keep running

Even if a compressor in a single system fails

X The other compressor can keep running

Automatic backup operation.

8

Innovative

CONCEPT

y Solution Green & Technolog

VRF Dual Coil (CHW+DX) Package Air Handling Unit Internal lining EC plug fan

DX cooling coil

Chilled water coil

Features of Dual coil design - Back-up function - Post cooling function - Dehumidity function - Light-load function

Slim Type VRF Dual Coil (CHW+DX) Package Air Handling Unit (Slim VDC AHU)

Y

DC V m

F

AHU

EC Plug Fan (Multi-fans for Water Coil Filter section standby/duty C/W 2-way (Optional) function) valve

Sli

Height in mm =650

- mini shop - Server room Length in mm = 1450(+250) Width in mm = 900

9

DX Coil C/W variable flow electrical expansion valve

VRF Outdoor Unit Performance Data (Standard Series)

HP

10

20

30

40

50

60

70

80

U-10ME2H7

U-20ME2H7

U-16ME2H7 U-14ME2H7

U-20ME2H7 U-20ME2H7

U-20ME2H7 U-16ME2H7 U-14ME2H7

U-20ME2H7 U-20ME2H7 U-20ME2H7

U-20ME2H7 U-20ME2H7 U-20ME2H7 U-10ME2H7

U-20ME2H7 U-20ME2H7 U-20ME2H7 U-20ME2H7

Model Name

380 / 400 / 415V-3-phase / 50Hz ; 380 / 400V / 3-phase / 60Hz

Power Supply kW

28

56

85

113

140

168

196

224

BTU/h

95,600

191,100

290,100

385,700

477,800

573,400

668,900

764,500

W/W

5.03

3.76

4.31

3.74

4.09

3.76

3.90

3.76

Height

mm

1,842

1,842

1,842

1,842

1,842

1,842

1,842

1,842

Width

mm

770

1,540

2,420

3,140

4,020

4,740

5,570

6,340

Depth

mm

1,000

1,000

1,000

1,000

1,000

1,000

1,000

1,000

Net Weight

kg

210

375

630

750

1,005

1,125

1,335

1,500

Electrical RatingsCooling

A

9.6/ 9.1/ 8.8

24.6/ 23.4/ 22.5

33.6/ 31.9/ 30.8

49.9/ 47.4/ 45.7

57.7/ 54.8/ 52.9

73.8/ 70.1/ 67.6

84.0/ 79.8/ 76.9

98.4/ 93.5/ 90.1

kW

5.57

14.90

19.70

30.20

34.20

44.70

50.30

59.6

A

1

2

4

4

6

6

7

8

m3/h

13,440

24,300

27,840

48,600

52,140

72,900

86,340

97,200

Refrigerant Amount at shipping

kg

5.6

9.5

16.6

19.0

26.1

28.5

34.1

38.0

External Static Pressure

Pa

80

80

80

80

80

80

80

80

mm

Ø22.22

Ø28.58

Ø31.75

Ø38.10

Ø38.10

Ø38.10

Ø41.28

Ø44.45

mm

Ø9.52

Ø15.88

Ø19.05

Ø19.05

Ø19.05

Ø19.05

Ø22.22

Ø22.22

mm

Ø6.35

Ø6.35

Ø6.35

Ø6.35

Ø6.35

Ø6.35

Ø6.35

Ø6.35

Cooling Capacity

COP-Cooling

Dimension

Power Input Starting Current Airflow Rate

Gas Pipe Piping Liquid Connections Pipe Balance Pipe Ambient Temperature Operation Range Sound Pressure Level Normal Mode Sound Power Level Normal mode

Cooling : -10°C (DB)~+52°C (DB), Heating: -25°C (WB)~+18°C (WB) dB(A)

56.0

59.0

63.0

62.0

64.5

64.0

64.5

65.0

dB

77.0

80.0

84.0

83.0

85.5

85.0

85.5

86.0

10

VRF Outdoor Unit Performance Data (High Efficiency Series)

HP

10 U-10ME2H7

20 U-20ME2H7HE

30 U-30ME2H7

40 U-40ME2H7HE

50 U-50ME2H7HE

60 U-60ME2H7HE

U-10ME2H7

U-10ME2H7 U-10ME2H7

U-14ME2H7 U-16ME2H7

U-12ME2H7 U-12ME2H7 U-16ME2H7

U-10ME2H7 U-12ME2H7 U-12ME2H7 U-16ME2H7

U-12ME2H7 U-16ME2H7 U-16ME2H7 U-16ME2H7

Model Name

Power Supply

380 / 400 / 415V-3-phase / 50Hz ; 380 / 400V / 3-phase / 60Hz kW

28

56

85

113

140

168

BTU/h

95,600

191,100

290,100

385,700

477,800

573,400

W/W

5.03

5.05

4.31

4.45

4.58

4.24

Height

mm

1,842

1,842

1,842

1,842

1,842

1,842

Width

mm

770

1,600

2,420

3,660

4,490

4,900

Depth

mm

1,000

1,000

1,000

1,000

1,000

1,000

Net Weight

kg

210

420

630

855

1,065

1,215

Electrical RatingsCooling

A

9.6/9.1/8.8

19.2/18.2/17.5

33.6/31.9/30.8

42.4/40.3/38.8

51.7/49.1/47.3

66.9/63.5/61.2

kW

5.57

11.10

19.70

25.40

30.60

39.60

A

1

2

4

4

5

7

m3/h

13,440

26,880

27,840

41,760

55,200

55,680

Refrigerant Amount at shipping

kg

5.6

11.2

16.6

24.9

30.5

33.2

External Static Pressure

Pa

80

80

80

80

80

80

mm

Ø22.22

Ø28.58

Ø31.75

Ø38.10

Ø38.10

Ø38.10

mm

Ø9.52

Ø15.88

Ø19.05

Ø19.05

Ø19.05

Ø19.05

mm

Ø6.35

Ø6.35

Ø6.35

Ø6.35

Ø6.35

Ø6.35

Cooling Capacity

COP-Cooling

Dimension

Power Input Starting Current Airflow Rate

Gas Pipe Piping Liquid Connections Pipe Balance Pipe Ambient Temperature Operation Range

11

Cooling : -10°C (DB)~+46°C (DB), Heating: -25°C (WB)~+15°C (WB)

Sound Pressure Level Normal Mode

dB(A)

53.0

59.0

63.0

63.5

64.5

66.5

Sound Power Level Normal mode

dB

74.0

80.0

84.0

84.5

85.5

87.5

Drawings

H W

L

Performance Data AHU Performance Data AHU Model No.

A1-1170H-1050W A1-1450H-1350W A1-1770H-1650W A1-1770H-1950W A1-1930H-2250W

A1-2250H-2250W

VRF Outdoor Model No.

U-10ME2H7 U-20ME2H7 U-16ME2H7 U-14ME2H7 U-20ME2H7 U-20ME2H7 U-20ME2H7 U-16ME2H7 U-14ME2H7 U-20ME2H7 U-20ME2H7 U-20ME2H7

3

m /s

mm

mm

mm

°C/%

°C

System Cooling Capacity kW

1.49 2.90

1,210 1,550

1,050 1,350

1,595 1,595

25/55 25/55

12.5 12.5

28 56

4.47

1,870

1,500

1,595

25/55

12.5

85

5.92

1,870

1,950

1,900

25/55

12.5

113

7.45

2,030

2,250

2,205

25/55

12.5

140

8.94

2,250

2,250

2,205

25/55

12.5

168

On Coil

Off Coil

DB/RH

DB

AHU Air flow rate

Standard Unit Dimensions Height

Width

Length

On Coil

Off Coil

DB/RH

DB

PAU Performance Data PAU Model No.

A1-830H-1050W A1-850H-1050W A1-1170H-1050W A1-1170H-1350W A1-1330H-1350W

A1-1330H-1650W

VRF Outdoor Model No.

U-10ME2H7 U-20ME2H7 U-16ME2H7 U-14ME2H7 U-20ME2H7 U-20ME2H7 U-20ME2H7 U-16ME2H7 U-14ME2H7 U-20ME2H7 U-20ME2H7 U-20ME2H7

3

m /s

mm

mm

mm

°C/%

°C

System Cooling Capacity kW

0.50 1.00

950 950

985 985

1,595 1,595

35/70 35/70

15 15

28 56

1.50

1,430

985

1,595

35/70

15

85

2.00

1,430

1,290

1,595

35/70

15

113

2.50

2,030

1,290

1,900

35/70

15

140

3.00

2,030

1,595

2,205

35/70

15

168

AHU Air flow rate

Standard Unit Dimensions Height

Width

Length

Remarks: 1. Height does not include the unit base 100mm* 2. Standard length include coil and fan, external mounted per filter is 50mm** 3. Specifications are subjected to change without prior notice.

12

Dimensions (Standard Series) 10 HP U-10ME2H7 Air Outlet Installation anchor hole 8-15x21 elongated holes

A: (Installation hole pitch) For removing tube forward B: (Installation hole pitch) For removing tube downward C: (Installation hole pitch) 1842 953

A:964 18

B: 730

740 770

C:730

Air intake

Air intake

1000

Air intake

15

Top View

Front View

14-16 HP U-14ME2H7 U-16ME2H7

According to the installation site, you may choose the setting positionin the depth direction of the anchor bolt from A, B or C.

Air Outlet

Installation anchor hole 8-15x21 elongated holes

A: (Installation hole pitch) For removing tube forward B: (Installation hole pitch) For removing tube downward C: (Installation hole pitch)

1150 1180

1842 953

C:730 Air intake B: 730 18 A:964

1000 Air intake

Air intake

15

Top View

Front View

20 HP U-20ME2H7 Air Outlet

1510 1540 Top View

According to the installation site, you may choose the setting position in the depth direction of the anchor bolt from A, B or C.

1842

A: (Installation hole pitch) For removing tube forward B: (Installation hole pitch) For removing tube downward C: (Installation hole pitch) 953

C:730 Air intake B:730 A:964 18

1000

Air intake

Installation anchor hole 8-15x21 elongated holes Air intake Air intake 740

15

According to the installation site, you may choose the setting positionin the depth direction of the anchor bolt from A, B or C.

Front View

Unit in mm 13

Dimensions (High Efficiency Series) 10 HP U-10ME2H7 According to the installation site, you may choose the setting position in the depth direction of the anchor bolt from A, B or C. A (Installation hole pitch) For removing tube forward B (Installation hole pitch) For removing the downward C (Installation hole pitch) Top view

Front view

Installation anchor hole, 8-15x21 elongated holes Air Intake

Air outlet

B:730

1000

A:964 C:730

Air Intake

Air Intake

15

740 770

18

1842 953

12/14/16 HP U-12ME2H7 U-14ME2H7 U-16ME2H7 According to the installation site, you may choose the setting position in the depth direction of the anchor bolt from A, B or C. A (Installation hole pitch) For removing tube forward B (Installation hole pitch) For removing the downward Air outlet C (Installation hole pitch) Installation anchor hole, 8-15x21 elongated holes Air Intake

Air Intake B:730 1000

C:730

A:964 Air Intake

1842 953

15

1150

18

1180

Top view

Front view Unit in mm 14

SAIVER S.R.L

Via M. da Besozzo, 16 20052 Monza (Milan) Italy. Tel : +39. 039. 282 831 Fax : +39. 039. 202 5668 E-mail : [email protected] Website: www.saiver.com 219mmx64mm

SAIVER – Pantone: 2925C

SRPC-PDFCE-VRFAHUPAU-Italy-2018.05