FEATURES & SPECIFICATIONS INTENDED USE — Use in high mounting heights that require high efficiencies, horizontal illumination, premium glare control and total enclosure. Ideal for heavy manufacturing areas, gymnasiums and wet location applications.

High Bay Industrial Lighting

TE

CONSTRUCTION — Housing- Vertically seamed, heavy-duty, die-cast aluminum halves. Ballast and electrical components are heat-sinked and horizontally opposed. Integral splice box mounting flange ensures structural integrity. FINISH — Electrostatically applied white polyester powder paint. OPTICAL SYSTEM — One-piece totally enclosed and gasketing fluted spun aluminum, anodized reflector combines high efficiency with extended shielding angle for high performance optical control. Clear tempered glass lens is fully gasketed to inhibit the entrance of ambient contaminants. Lens assembly is hinged and latched to allow access for easy maintenance. Meets UL lamp rupture containment specifications. ELECTRICAL SYSTEM — Ballast - 100% factory tested, high power factor, constant-wattage autotransformer. 180OC Class H insulated system. Meets UL standard for HID ballast system. Socket- Vertically oriented, mogul-base socket with copper alloy, nickelplated screw shell and center contact. UL Listed 1500W, 600V, 5KV pulse rated for U.S. lamps. INSTALLATION — Ballast Housing - 16-gauge galvanized steel pendant splice box with white polyester powder finish. Removable box slides on integral die-cast aluminum housing mounting flange and mounts to 3/4" pendant conduit prior to ballast housing installation. Matching wire access cover accepts Reloc modular wiring. Complete assembly meets or exceeds UL 50-pound pull test. Optical Mounting- Four 8-32 zinc plated, tri-lobular, thread-rolling screws are arranged concentrically around the lamp socket. Sixteen-gauge galvanized steel support ring with matching keyhole slot pattern for vibration resistant mounting. LISTING — UL Listed. -30°C to 55°C ambient operations and damp locations. 65°C and WL wet location available.

ORDERING INFORMATION

Metal Halide High Pressure Sodium 250W, 400W 25' to 45' (7m to 14m) mounting

Specifications Height: 24-3/8 (61.9) Reflector Height: 17-13/16 (45.2) Width: 23 (58.4) Weight: 26lbs (11.8kg) All dimensions are inches (centimeters).

Lead times will vary depending on options selected. Consult with your sales representative. Example: TE 250S E17M 12050HZ

TE Series

Wattage/lamp

Reflector/distribution

Voltage

Options

TE

250M 250S 400M 400S

E17M E17N E17C E17S E17W

12050HZ 23050HZ1

Shipped installed in fixture SF Single fuse EC Emergency circuit2,3 QRS Quartz restrike system2,3 HA 65°C ambient operation CR Corrosion-resistant finish TOB Thru-wire outlet box6 PBP Pendant box plug-in6 LCPP Loop, cord, plug requires TPH, PPH6 LC3 Loop, 3' (lm) cord6 LOCS Loop, 3' cord, Reloc OCS4,6 HOCS Hook, 3' cord, Reloc OCS4,6 TR Remote ballast6 RC3NP TR with prewired cord5,6 DDB Dark bronze housing finish WL Wet location

Accessories Order as separate catalog number. SCK

60" safety chain kit

NOTES:

HKM

Fixture hook male6

1 Operates 220, 230, and 240Volt 50HZ.

Grommeted fixture hook male6

2 Lamp not included.

HKMG LPM

Fixture loop male

6

3 See Product Selection Guide (QRS Lamp Wattage Table) for maximum lamp wattage.

Grommeted fixture loop male 6

4 May be ordered with 5', 10', 15' cords.

TPH

Thru-wire power hook6

5 3' cord to connect to optical.

PPH

Pendant power hook6

6 Not available with WL option.

LPMG

Indoor HID

Sheet #: TE-E17-Int

OPHI-004

TE High Bay TE 250M E17M, (medium), 250W, clear Metal Halide lamp, 20,500 rated lumens. Test No. 11858. Coefficient of utilization

Distribution curve ρf ρc ρw

0 1 2 3 4 5 6 7 8 9 10

Distribution data Angle

80% 70% 50% 30% 10%

20% 50% 50% 30% 10%

50%

30% 30% 10%

10% 50% 30% 10%

0%

87 82 77 72 68 64 60 56 53 50 47

81 75 69 64 59 55 51 47 44 41 38

77 72 67 62 58 53 50 46 43 40 38

77 71 65 60 54 50 46 42 39 36 34

74 70 65 61 56 52 49 45 42 39 37

73 67 61 55 50 46 42 38 35 32 30

87 80 73 67 62 57 53 49 45 42 39

87 78 70 63 57 52 48 44 40 37 34

87 76 67 60 54 48 44 40 37 34 31

81 74 67 61 55 51 47 43 40 37 34

81 72 65 58 53 48 43 40 36 34 31

77 70 63 57 52 47 43 39 36 33 31

Footlamberts

55° 65° 75° 85°

Spacing criterion: 1.2 Spacing-to-mounting height: 1.3

74 68 62 56 51 47 43 39 36 33 31

Output data

Average luminance data Angle

74 69 63 58 54 49 45 42 39 36 33

1240 415 255 423

Zone

Lumens

0°-30° 0°-40° 0°-60° 0°-90° 90°-180° 0°-180°

8343 12382 14780 15006 0 15006

%lamp

40.7 60.4 72.1 73.2 0.0 *73.2

cp.

Lumens

0° 7724 5° 7511 713 15° 10095 2857 25° 13310 4773 35° 6424 4034 45° 2448 1895 55° 559 501 65° 138 137 75° 52 55 85° 29 31 90° 20 95° 0 0 105° 0 0 115° 0 0 125° 0 0 135° 0 0 145° 0 0 155° 0 0 165° 0 0 175° 0 0 180° 0 0

* Fixture efficiency

TE 400S E17W, (wide), 400W, clear High Pressure Sodium lamp, 50,000 rated lumens. Test No. 11937. Distribution data

Coefficient of utilization

Distribution curve ρf ρc ρw

0 1 2 3 4 5 6 7 8 9 10

80% 70% 50% 30% 10%

20% 50% 50% 30% 10%

30% 50% 30% 10%

10% 50% 30% 10%

0%

86 81 75 69 64 59 55 51 48 44 41

80 73 66 60 54 49 45 41 37 34 31

77 71 64 58 53 48 44 40 36 33 31

74 68 62 56 51 47 42 39 36 33 30

72 65 57 50 44 39 34 31 27 25 22

86 78 70 63 57 51 47 42 39 35 33

86 76 66 58 52 46 41 37 33 30 27

86 74 63 55 48 42 37 33 29 26 24

80 72 64 56 50 45 40 36 32 29 27

80 70 61 53 47 41 36 32 29 26 23

77 69 62 55 49 44 39 35 32 29 26

77 68 60 52 46 41 36 32 29 26 23

Average luminance data Angle

74 67 60 54 48 43 39 35 32 29 26

Output data

Footlamberts

Zone

Lumens

9400 2283 787 438

0°–30° 0°–40° 0°–60° 0°–90° 90°–180° 0°–180°

7560 13200 21120 21570 0 21570

55° 65° 75° 85°

Spacing criterion: 1.9 Spacing-to-mounting height: 1.9

74 66 58 51 45 40 36 32 29 26 23 %lamp

25.4 44.8 70.7 72.6 0.0 *72.6

Angle

cp.

Lumens

0° 5° 15° 25° 35° 45° 55° 65° 75° 85° 90° 95° 105° 115° 125° 135° 145° 155° 165° 175° 180°

9658 10447 15169 16064 15380 11829 4235 758 160 30 13 0 0 0 0 0 0 0 0 0 0

992 4292 7437 9658 9156 3798 753 170 33 0 0 0 0 0 0 0 0 0 0 0

* Fixture efficiency

Other distributions are available. Consult factory.

Lithonia Lighting

Sheet #: TE-E17-Int

©2002 Acuity Brands Lighting, Inc., Rev. 12/22/08

High Bay and Special Applications One Lithonia Way, Conyers, GA 30012 Phone: 770-922-9000, 800-315-4963, Fax: 770-929-8789 www.lithonia.com