PROJECT:

KING HUSSEIN MEDICAL CITY

CALCULATION TITLE:

SOLAR PANEL NUMBERS-WING-01

Description

PROJECT NUMBER

SHEET NUMBER

60542773 PREPARED BY

DATE

MK

4/3/2018

CHECKED BY

1 DATE

VERIFIED BY

DATE

0 Variable

Unit

A. Daily hot water demand for the zone

22.572

m3

B. 100% of daily hot water demand to be

22.572

m

Remarks 198 No of beds 114 l/bed

3

utilised from solar heating system C. Number of solar panels required D. Area of a solar collector E. Total area required of 141 panels F. Total Area required with installation G. Hot water produced per panel per day(ltrs)

REVISION

112

Panels

2



224



313.6



200

2.8 m² total required with installation

(IOP)

PROJECT:

KING HUSSEIN MEDICAL CITY

CALCULATION TITLE:

SOLAR PANEL NUMBERS-WING-02

Description A. Daily hot water demand for the zone B. 100% of daily hot water demand to be utilised from solar heating system C. Number of solar panels required D. Area of a solar collector E. Total area required of 239 panels F. Total Area required for Installation G. Hot water produced per panel per day(ltrs)

PREPARED BY MK

DATE

PROJECT NUMBER 60542773 CHECKED BY DATE

VERIFIED BY

DATE

4/3/2018 Variable

Unit

38.304

m

38.304

m3

3

Remarks 336 No of beds 114 l/bed

191

Panels

2



382



534.8



200

2.8 m² total required with installation

SHEET NUMBER 1 REVISION 0

marks (IOP)

PROJECT:

KING HUSSEIN MEDICAL CITY

CALCULATION TITLE:

SOLAR PANEL NUMBERS-D&T

Description A. Number of Expected people in Offices Daily Hot Water Requirement

PREPARED BY

DATE

MK

4/3/2018

PROJECT NUMBER 60542773 CHECKED BY DATE Variable

Unit

780 5.928

m3

3842

People

C. Kitchen Daily Hot Water Requirement Dining Area Total Occupancy Total Daily Hot Water Demand for Kitchen D. Total Requirement for D&T E. Number of solar panels required F. Area of a solar collector

23.052

m3

28.98

m3

145

Panels

2



G. Total area required of 67 panels

290



H. Total Area required for Installation

406



I. Hot water produced per panel per day(ltrs)

200

ER VERIFIED BY

DATE

SHEET NUMBER 1 REVISION 0

Remarks 7.6 L/P (Ashrae Handbook 2011-Table-7)

IOP IOP 6 Litres Per cover

2.8 m² total required with installation

Model reference

NX-WN-0122-1204

Model reference

NX-WN-0122-1204

NX-WN-0122-1204