ROI-ET 5/8 ULTRA-FILTRATION UNIT START

ST-03 YES

MANUAL

LEVEL HIGH CUT

LEVEL LSH ST-03LS01 LEVEL LAH ST-03LS02

SELECTOR

VALVE ON / 0FF

AUTO

POWER ON STEP A

BREAK

ON

STEP A SERVICE @ NORMAL FLUSH STOP ALARM

A1=SERVICE 30 MIN A2=FORWARD FLUSHING A 8 SEC

YES

A3=BACKWASH COUNTER-CURRENT 14 SEC

ALARM RESET

YES

STOP ALARM

UFP-01/02 PUMP RUN

VALVE ON 8 SEC V4,V5

PUMP ON 8 SEC UF-BFP01

VALVE ON 14 SEC V6,V7

PUMP ON 14 SEC UF-BFP01

VALVE ON 14 SEC V4,V5

PUMP ON 14 SEC UF-BFP01

RUN

STEP A3 END

YES

STOP ALARM

VALVE ON 30 MIN V1,V2,V3 RUN

STEP A2 END

STOP ALARM

A4=FORWARD FLUSHING B 14 SEC

TIME “1” OSC CLOCK 1 SEC

RUN

STEP A1 END

RUN

STEP A4 END

YES

RESET TIME STEP A

YES

POWER ON STEP B

STEP B COUNT 60 MIN

YES POWER ON STEP C

STEP C COUNT 1 DAY

YES YES BREAK

YES

STOP ALARM

STEP B1 END

RUN

VALVE ON 14 SEC V6,V7,V9

YES

STEP B2 END

STOP ALARM ALARM RESET

STEP B3 END

STOP ALARM

STEP B4 END

YES

STEP C2 END

ALARM RESET

RUN

STEP C3 END

PUMP ON 14 SEC UF-BFP01

RUN

RESET TIME STEP B + STEP A

STEP C4 END

PUMP ON 14 SEC UFP-01/02

YES

PUMP ON 14 SEC UF-CP03/04 UF-BFP 01

RUN

BREAK 60 SEC

RUN

YES

STOP ALARM

VALVE ON 14 SEC V1,V8

VALVE ON 14 SEC V6,V7,V10

YES

STOP ALARM

VALVE ON 14 SEC V6,V7

RUN

YES

STOP ALARM

BREAK 60 SEC

YES

STEP C1 END

PUMP ON 14 SEC UF-CP01/02 UF-BFP 01

RUN

YES

STOP ALARM

STOP ALARM

VALVE ON 14 SEC V6,V7

PUMP ON 14 SEC UF-BFP01

VALVE ON 14 SEC V1,V8

PUMP ON 14 SEC UFP-01/02

RUN

RESET TIME STEP C + STEP B + STEP A

STEP B NaOCl CLEANING EVERY 60 MIN

STEP C HCL CLEANING EVERY 1 DAY

B1=BACKWASH COUNTER-CURRENT WITH NaOCl DOSING 14 SEC

C1=BACKWASH COUNTER-CURRENT WITH HCl DOSING 14 SEC

B2=SOAKING 60 SEC

C2=SOAKING 60 SEC

B3=BACKWASH COUNTER-CURRENT 14 SEC

C3=BACKWASH COUNTER-CURRENT 14 SEC

A4=RING 14 SEC

C4=RING 14 SEC

ROI-ET DEG-ST01

NO

INTERLOG HIGH CUT

LEVEL LSH DEG-ST01LS01 LEVEL LAH DEG-ST01LS02

REVERES OSMOSIS UNIT 6/8 RO-HPP01/02 UFP-01/02 17m³/hr.@20m PUMP RUN

YES

STEP 1 SERVICE STEP2 AUTO FLUSHING # 1 STEP3 AUTO FLUSHING # 2

STEP 3 15 SEC END

RUN

OPEN VALVE MF-02V02/RO-V10 /RO-V15

YES

START

STEP 4 120 SEC END

MANUAL

RUN

SELECTOR

VALVE ON / 0FF

PUMP RUN RO-HPP01/02

RUN AB01/02 DGP-01/02

OPEN VALVE MF-02V12/RO-V10

PUMP RUN DGP-01/02

AUTO YES

BREAK SERVICE RO UNIT

RUN PUMP RIP-01/02 5 SEC

POWER ON RO UNIT

YES OPEN VALVE BV-02 5 SEC

STEP 1 45 MIN END

STOP ALARM

RUN

YES

RUN AB01/02 RIP-01/02

PUMP RUN RO-HPP01/02

RUN AB01/02

PUMP RUN RO-HPP01/02,RIP-01/02

RO-V15 0PEN 15 SEC

RUN

STEP 2 15 SEC END

STOP ALARM

ALARM RESET

RESET

OPEN VALVE MF-02V02/RO-V10

YES

OPEN VALVE MF-02V02/RO-V10 /RO-V15

FREQUENCY =2 Hz RESET TIME STEP 1

LAMP

BUZZER

START STEP 1 60 MIN RUN

STEP 2 15 SEC RUN

STEP 3 60 SEC RUN

YES

YES

YES

MANUAL SELECTOR AUTO CONDUCT HIGH RO-CON01 YES

STEP 4 RUN CONDUC HIGH 10 SEC

YES

YES ALARM ONLY

ON VALVE VALVE/MF-02V12

VALVE OFF RO-V10

VALVE ON BV-05

START

START

START

MANUAL

MANUAL

MANUAL SELECTOR AUTO

START

AUTO

MANUAL SELECTOR

SELECTOR

CIP-02T01

SELECTOR

AUTO

AUTO

LEVEL LSH CIP-02LS01 RO-CON01 STEP 2+STEP 3

YES

ON VALVE VALVE/RO-V15

IN TERLOG LOW CUT YES

ON VALVE VALVE/RO-V13

CONDUCT HIGH 10 SEC YES

ON VALVE VALVE/BV-05

RO-CON01 CONDUCT LOW 10 SEC YES

ON VALVE VALVE/RO-V10 (RO-V15 ON 10 SEC)

ROI-ET 3/8

START

RWP-01/02 70m³/hr.@35m. PUMP SUPPLY-AREVA INSTALLATION-WD RAW WATER PUMP

MANUAL SELECTOR

AUTO

NO

STOP ALARM

INTERLOCK NOT LOW CUT

RESERVIOR (EXISTING)

LEVEL H LAL RWP-01/02LS01 LEVEL L LSL RWP-01/02LS02

YES

INTERLOCK NOT HIGH CUT

ST-01 BY OTHER-RCC ON GROUND (W.2,500xL.8,000xH3,000 (2,500)mm.)

LEVEL LSH ST-01LS01 LEVEL LAH ST-01LS02

YES

RESET

PUMP RWP 01/02

FREQUENCY= 2 Hz BUZZER

ONE DUTY ONE STANDBY ALTERATIVE EVERY 12 HOURS OPERATION AND EVERY TRIP

RUN LAMP

PUMP RWP 01

PUMP RWP 02

PUMP RWP 01 TRIP

PUMP RWP 02 TRIP

YES

YES

ROI-ET 3/8 CP-01/02 50LPH@10BARS

START

MANUAL SELECTOR

AUTO

NO

STOP ALARM

INTERLOCK NOT LOW CUT

CT-01 PE:1,000L. D1,030xH1,490xT10mm. (PAC)

LEVEL LSL CT-01LS01

YES

SIGNAL PUMP ON RWP-01/02

RWP-01/02 70m³/hr.@35m. PUMP SUPPLY-AREVA

YES

RESET

PUMP CP-01/02

ONE DUTY ONE STANDBY ALTERATIVE EVERY 12 HOURS OPERATION AND EVERY TRIP

RUN FREQUENCY =2 Hz BUZZER

LAMP PUMP CP-01

PUMP CP-02

PUMP CP-01 TRIP

PUMP CP-02 TRIP

YES

YES

ROI-ET 3/8 CP-03/04 [email protected]

START

MANUAL SELECTOR

AUTO

NO

STOP ALARM

INTERLOCK NOT LOW CUT

CT-02 PE:1,000L. D1,030xH1,490xT10mm. (NaOCl)

LEVEL LSL CT-02LS01

YES

SIGNAL RWP-01/02 PUMP ON

RWP-01/02 70m³/hr.@35m. PUMP SUPPLY-AREVA

YES

PUMP CP-03/04

RESET

ONE DUTY ONE STANDBY ALTERATIVE EVERY 12 HOURS OPERATION

RUN FREQUENCY =2 Hz BUZZER

LAMP PUMP CP-03

PUMP CP-04

ROI-ET 3/8 CP-05/06 120LPH@7BARS

START

MANUAL SELECTOR

AUTO

NO

STOP ALARM

INTERLOCK NOT LOW CUT

CT-04 PE:1,000L. D1,030xH1,490xT10mm. (POLYMER)

LEVEL LSL CT-04LS01

YES

SIGNAL RWP-01/02 PUMP ON

RWP-01/02 70m³/hr.@35m. PUMP SUPPLY-AREVA

YES

PUMP CP-05/06

RESET

ONE DUTY ONE STANDBY ALTERATIVE EVERY 12 HOURS OPERATION AND EVERY TRIP

RUN FREQUENCY =2 Hz BUZZER

LAMP PUMP CP-05

PUMP CP-06

PUMP CP-05 TRIP

PUMP CP-06 TRIP

YES

YES

ROI-ET START

3/8 MX-01 PAC MIXING

SELECTOR ON / OFF

YES

STOP ALARM

MOTOR MX-01

RESET

FREQUENCY =2 Hz BUZZER

LAMP YES MOTOR TRIP

ROI-ET START

SELECTOR ON / OFF

YES

STOP ALARM

MOTOR MX-02

RESET

FREQUENCY =2 Hz BUZZER

LAMP YES MOTOR TRIP

MX-02 POLYMER MIXING

ROI-ET 4/8 FFP-01/02 70m³/hr.@26m. FILTER FEED PUMP

START

MANUAL SELECTOR

AUTO

NO

STOP ALARM

IN TERLOCK NOT LOW CUT

ST-01 BY OTHER-RCC ON GROUND (W.2,500xL.8,000xH3,000 (2,500)mm.)

LEVEL LAL ST-01LS03 LEVEL LSL ST-01LS04

YES

NOT HIGH CUT INTERLOCK

YES

PUMP FFP 01/02

RESET

LEVEL LSH ST-02LS01 LEVEL LAH ST-02LS02

ONE DUTY ONE STANDBY ALTERATIVE EVERY 12 HOURS OPERATION AND EVERY TRIP

RUN

FREQUENCY =2 Hz BUZZER

ST-02 BY OTHER-RCC ON GROUND (W8,000xL10,000xH3,000(2,500)m.)

LAMP

PUMP FFP 01

PUMP FFP 02

PUMP FFP 01 TRIP

PUMP FFP 02 TRIP

YES

YES

ROI-ET 4/8 BWP-01 140m³/hr.@18m. BACK WASH PUMP

START

MANUAL SELECTOR

AUTO

NO

STOP ALARM

INTERLOCK NOT LOW CUT

ST-02 BY OTHER-RCC ON GROUND (W8,000xL10,000xH3,000(2,500)m.) LEVEL LAL ST-02LS03 LEVEL LSL ST-02LS04

YES

PUMP BWP-01

RESET

FREQUENCY =2 Hz BUZZER

LAMP

PUMP BWP-01 TRIP

YES

ROI-ET 4/8 WSP-01/02 53 m³/hr.@ 50M. PUMP SUPPLYAREVA INSTALLATION-WD

START

MANUAL SELECTOR

AUTO

NO

STOP ALARM

ST-02 BY OTHER-RCC ON GROUND (W8,000xL10,000xH3,000(2,500)m.) INTERLOCK NOT LOW CUT

LEVEL LAL ST-02LS03 LEVEL LSL ST-02LS04

YES

SIGNAL ON/OFF FOR PROCESS

FOR PROCESS CONTROL AREVA’S SCOPE

YES

PUMP WSP-01/02

RESET

ONE DUTY ONE STANDBY ALTERATIVE EVERY 12 HOURS OPERATION AND EVERY TRIP

RUN FREQUENCY =2 Hz BUZZER

LAMP PUMP WSP-01

PUMP WSP-02

PUMP WSP-01 TRIP

PUMP WSP-02 TRIP

YES

YES

ROI-ET 4/8 UFP-01/02 17m³/hr.@20m UF FEED PUMP

START

MANUAL SELECTOR

AUTO

NO

STOP ALARM

ST-02 BY OTHER-RCC ON GROUND (W8,000xL10,000xH3,000(2,500)m.) INTERLOCK NOT LOW CUT

LEVEL LAL ST-02LS03 LEVEL LSL ST-02LS04

YES

NO PSL NOT LOW CUT

PRESSURE SWITCH UF-01PS01

YES

RESET

PUMP UFP-01/02

ONE DUTY ONE STANDBY ALTERATIVE EVERY 12 HOURS OPERATION AND EVERY TRIP

RUN FREQUENCY =2 Hz BUZZER

LAMP PUMP UFP-01

PUMP UFP-02

PUMP UFP 01 TRIP

PUMP UFP 02 TRIP

YES

YES

ROI-ET 5/8 CIP-01P01 17m³/hr.@22m.

START

MANUAL SELECTOR

AUTO

NO

STOP ALARM

CIP-01T01 INTERLOCK NOT LOW CUT

YES

PUMP CIP-01P01 RESET

FREQUENCY =2 Hz BUZZER

LAMP

PUMP CIP-01P01 TRIP YES

LEVEL LSL CIP-01LS01

ROI-ET 5/8 UF-BFP01 68m³/hr.@24m.

START

MANUAL SELECTOR

AUTO

NO

STOP ALARM

ST-03 INTERLOCK NOT LOW CUT

LEVEL LAL ST-03LS03 LEVEL LSL ST-03LS04

YES

NO SIGNAL HIGH UF-01PS02

YES

PUMP UF-BFP01

RESET

FREQUENCY =2 Hz BUZZER

LAMP

PUMP UF-BFP01 TRIP

YES

PRESSURE SWITCH UF-01PS02

ROI-ET START

5/8 UF-CP01/02 [email protected] S

MANUAL SELECTOR AUTO UF STEP B1 ON UF-BFP-01 NO

STOP ALARM

INTERLOCK NOT LOW CUT

UF-CT01 PE:100L. D500xH660xT5.5mm. (CEB-01;NaOCl 10%)

LEVEL LSL UF-CT01LS01

YES

PUMP UF-CP01/02

RESET

ONE DUTY ONE STANDBY ALTERATIVE EVERY 5 HOURS OPENING

RUN FREQUENCY =2 Hz LAMP

BUZZER

PUMP UF-CP01

PUMP UF-CP02

ROI-ET START

5/8 UF-CP03/04 [email protected]

MANUAL SELECTOR AUTO

NO INTERLOCK NOT LOW CUT

STOP ALARM

UF STEP C1 ON UF-BFP-01 UF-CT02 PE:100L. D500xH660xT5.5mm. (CEB-02;HCl 35%)

LEVEL LSL UF-CT02LS01

YES

RESET

PUMP UF-CP03/04

ONE DUTY ONE STANDBY ALTERATIVE EVERY 5 HOURS OPENING

RUN FREQUENCY =2 Hz BUZZER

LAMP PUMP UF-CP03

PUMP UF-CP04

ROI-ET 5/8 RIP-01/02 13.3m³/hr.@23M.

START

MANUAL SELECTOR

AUTO

ST-03

NO INTERLOCK NOT LOW CUT

LEVEL LAL ST-03LS03 LEVEL LSL ST-03LS04

YES

STOP ALARM

INTERLOCK HOT HIGH CUT

DEG-ST01 LEVEL LSH DEG-ST01LS01 LEVEL LAH DEG-ST01LS02

RO STEP3 & BV-02 ON 5 SEC

YES

YES

SIGNAL ON RO UNIT

SIGNAL RO UNIT STEP1 SERVICE& STEP2 FLUSHING 1&STEP3& BV-02 ON 5 SEC

YES

PUMP RIP-01/02

RESET

ONE DUTY ONE STANDBY ALTERATIVE EVERY 5 HOURS OPENING AND EVERY TRIP

RUN

FREQUENCY =2 Hz BUZZER

LAMP

PUMP RIP-01

PUMP RIP-02

PUMP RIP-02 TRIP

PUMP RIP-02 TRIP

YES

YES

ROI-ET 6/8 CP-07/08 [email protected]

START

MANUAL SELECTOR AUTO

NO SIGNAL HIGH RO-PH01

ALARM

RO-PH01 DELAY 5SEC = 8 START = 7 STOP

YES

NO

SIGNAL PUMP RUN RIP-01/02 YES

CT-05 (HCl 35%)

NO STOP ALARM

INTERLOCK LOW CUT

LEVEL LSL CT-05LS01

YES

PUMP CP-07/08

RESET

ONE DUTY ONE STANDBY ALTERATIVE EVERY 12 OPERATION HOURS

RUN FREQUENCY =2 Hz BUZZER

LAMP PUMP CP-07

PUMP CP-08

ROI-ET START

6/8 CP-09/10 [email protected]

MANUAL SELECTOR

AUTO

ORP HIGH RANG

YES

SIGNAL PUMP RUN RIP-01/02

YES

INTERLOCK LOW CUT

STOP ALARM

CT-06 (DECHLORINATION) LEVEL LSL CT-06LS01

YES

RESET

PUMP CP-09/10

ONE DUTY ONE STANDBY ALTERATIVE EVERY 12 OPERATION HOURS

RUN FREQUENCY =2 Hz BUZZER

LAMP PUMP CP09

PUMP CP010

ROI-ET 6/8 CP-11/12 [email protected]

START

MANUAL SELECTOR AUTO

SIGNAL RO SERVICE YES

SIGNAL PUMP RUN RIP-01/02 YES

NO

STOP ALARM

INTERLOCK LOW CUT

CT-07 (ANTI-SCALE) LEVEL LSL CT-07LS01

YES

PUMP CP-11/12

RESET

ONE DUTY ONE STANDBY ALTERATIVE EVERY 12 OPERATION HOURS

RUN FREQUENCY =2 Hz BUZZER

LAMP PUMP CP11

PUMP CP12

ROI-ET

START

6/8 ORP CONTROL VALVE BV-02 / MF-02V02 PUMP RIP-01/02 RUN

STOP ALARM

RESET

YES FREQUENCY =2 Hz BUZZER

SIGNAL ON RO UNIT ( STEP SERVICE & STEP FLUSHING 1 )

SIGNAL ON RO UNIT

LAMP

YES

ORP HIGH DELAY TIME 20 SEC

BREAK SERVICE RO UNIT

HIGH

SIGNAL ORP HIGH

SIGNAL ORP RO-ORP01

SIGNAL ORP LOW

START

START

MANUAL

MANUAL SELECTOR AUTO

SIGNAL ORP HIGH

SELECTOR AUTO

SIGNAL ORP LOW

YES

YES

ON VALVE / BV-02

ON VALVE VALVE/MF-02V02

ROI-ET 6/8

START

RO-HPP01/02 13.3 m³/hr.@ 125 m.

MANUAL SELECTOR

AUTO

SIGNAL RUN RO-HPP01/02

RESET

YES FREQUENCY =2 Hz BUZZER

RUN PUMP RO-HPP01/02

LAMP

RUN PUMP RO-HPP01

ONE DUTY ONE STANDBY ALTERATIVE EVERY 12 OPERATION HOURS AND EVERY TRIP

RUN PUMP RO-HPP02

PRESSURE SWITCH

PRESSURE SWITCH LOW CUT RO-HPP01PS01

NO

STOP ALARM

NO

YES

LOW CUT RO-HPP02PS01

YES

PRESSURE SWITCH

PRESSURE SWITCH HIGH CUT RO-PS01

NO

STOP ALARM

NO

YES

YES

PUMP TRIP RO-HPP01

HIGH CUT RO-PS01

YES

STOP ALARM

YES

PUMP TRIP RO-HPP02

ROI-ET 6/8 CIP-02P01 9 m³/hr.@ 25 m.

START

MANUAL SELECTOR

AUTO

NO

STOP ALARM

IN TERLOCK LOW CUT

CIP-02P01 LEVEL LSL CIP-02LS02

YES

PUMP CIP-02P01 RESET

FREQUENCY =2 Hz BUZZER

LAMP

PUMP RIP-02 TRIP

YES

ROI-ED 6/8 MX-03 DECHLORINATION MIXING

START

SELECTOR ON / OFF

YES

STOP ALARM

MOTOR MX-03

RESET

FREQUENCY =2 Hz BUZZER

LAMP YES MOTOR TRIP

ROI-ET 7/8 AB-01/02

START

MANUAL SELECTOR

AUTO

SIGNAL RO STEP 1+2+3

YES

RESET

CONDUCT RO-CON01

CONDUCT NOT HIGH

YES FREQUENCY= 2 Hz BUZZER

ONE DUTY ONE STANDBY ALTERATIVE EVERY 12 HOURS OPERATION AND EVERY TRIP

RUN AIR BLOWER AB-01/02

LAMP

RUN

RUN MOTOR AB-01

RUN MOTOR AB-02

MOTOR TRIP AB-01

MOTOR TRIP AB-02

YES

STOP ALARM

YES

STOP ALARM

ROI-ET 7/8 DGP-01/02 11m³/hr.@47M.

START RESET

MANUAL SELECTOR FREQUENCY =2 Hz BUZZER

AUTO

LAMP

DEG-ST01 STOP ALARM

INTERLOCK LOW CUT

LEVEL LAL DEG-ST01LS03 LEVEL LSL DEG-ST01LS04

YES

SIGNAL MAKE UP BOILER ON

MAKE UP BOILER TANK 75 m³ AREVA’S SCOPE

RO-STEP 4& ST04-V02

YES

YES

RUN PUMP DGP-01/02

ONE DUTY ONE STANDBY ALTERATIVE EVERY 12 HOURS OPERATION AND EVERY TRIP

RUN

RUN MOTOR DGP-01

RUN MOTOR DGP-02

MMB-01CON02 DELAY ON/OFF 10 SEC NO SIGNAL CONDUCT HIGH CUT

MMB-01CON02 DELAY ON/OFF 10 SEC STOP ALARM

NO SIGNAL CONDUCT HIGH CUT

YES

MOTOR TRIP DGP-01

YES

YES

STOP ALARM

YES

MOTOR TRIP DGP-02

ROI-ET 7/8 AB-03/04 3.5m³/Min.@5,000 mm.Aq

START

OFF SELECTOR

ON

RUN AIR BLOWER AB-03/04

RUN

RESET

RUN MOTOR AB-03

RUN MOTOR AB-04

MOTOR TRIP AB-03

MOTOR TRIP AB-04

YES

YES

FREQUENCY= 2 Hz BUZZER

LAMP

STOP ALARM

STOP ALARM

ROI-ED 7/8 CP-13 50LPH@10BAR HCl FEED PUMP

START

SELECTOR ON / OFF

YES

STOP ALARM

PUMP CP-13

RESET

FREQUENCY =2 Hz BUZZER

LAMP YES PUMP CP-13 TRIP

ROI-ET 8/8 CP-14/15 PH01

START

START ST-04V02

MANUAL

MANUAL

SELECTOR

SELECTOR

AUTO

AUTO

ST-04 NOT HIGH CUT

LEVEL LSH ST-04LS01

FLOW RANG >3 Q / hr

YES

FLOW MMB-01F05 RANG >3 Q / hr

YES

INTERLOCK LOW CUT

ON VALVE VALVE/ST-04V02

CT-12 LEVEL LSL CT-12LS01

YES

PH RANG CP-14/15 PH01

pH RANG CP-14/15pH01

YES

proportional

ON PUMP CP-14/15

ONE DUTY ONE STANDBY ALTERATIVE EVERY 12 HOURS OPERATION

RUN

RUN PUMP CP-14

RUN PUMP CP-15

ROI-ET 8/8 RGP-01/02

START

MANUAL SELECTOR

AUTO

NO

STOP ALARM

INTERLOCK NOT LOW CUT

ST-04 LEVEL LAL ST-04LS02 LEVEL LSL ST-04LS03

YES

YES PUMP RGP-01/02

ONE DUTY ONE STANDBY ALTERATIVE EVERY 12 HOURS OPERATION AND EVERY TRIP

RESET RUN

FREQUENCY =2 Hz

BUZZER

LAMP

PUMP RGP-01

PUMP RGP-02

PUMP RGP-01 TRIP

PUMP RGP-02 TRIP

YES

YES