INTRODUCTION Heat load calculation is a fundamental skill for HVAC designers and consultants. Consider that space cooling is among the highest energy expenses in buildings, especially during the summer. However, to properly size a space cooling system, first we must know the amount of heat that must be removed - this is precisely the purpose of heat load calculation. Heat in buildings can come from internal sources such as electrical appliances, or from external sources such as the sun. A heat load calculation considers all sources present and determines their total effect. Heating and cooling load calculations are carried out to estimate the required capacity of heating and cooling systems, which can maintain the required conditions in the conditioned space. To estimate the required cooling or heating capacities, one has to have information regarding the design indoor and outdoor conditions, specifications of the building, specifications of the conditioned space (such as the occupancy, activity level, various appliances and equipment used etc.) and any special requirements of the particular application. For comfort applications, the required indoor conditions are fixed by the criterion of thermal comfort, while for industrial or commercial applications the required indoor conditions are fixed by the particular processes being performed or the products being stored.
HEATING VERSUS COOLING LOAD CALCULATIONS: As the name implies, heating load calculations are carried out to estimate the heat loss from the building in winter so as to arrive at required heating capacities. Normally during winter months the peak heating load occurs before sunrise and the outdoor conditions do not vary significantly throughout the winter season. In addition, internal heat sources such as occupants or appliances are beneficial as they compensate some of the heat losses. As a result, normally, the heat load calculations are carried out assuming steady state conditions (no solar radiation and steady outdoor conditions) and neglecting internal heat sources. This is a simple but conservative approach that leads to slight overestimation of the heating capacity. For more accurate estimation of heating loads, one has to take into the thermal capacity of the walls and internal heat sources, which makes the problem more complicated. For estimating cooling loads, one has to consider the unsteady state processes, as the peak cooling load occurs during the day time and the outside conditions also vary significantly throughout the day due to solar radiation. In addition, all internal sources add on to the cooling loads and neglecting them would lead to underestimation of the required cooling capacity and the possibility of not being able to maintain the required indoor conditions. Thus cooling load calculations are inherently more complicated as it involves solving unsteady equations with unsteady boundary conditions and internal heat sources.
METHODS OF ESTIMATING COOLING AND HEATING LOADS: Generally, heating and cooling load calculations involve a systematic, stepwise procedure, using which one can arrive at the required system capacity by taking into account all the building energy flows. There are majorly 3 types of calculation methods as stated below:-
Rule of thumb method - Least accurate
Static analysis (Room temperature is constant)– CLTD/CLF method
Dynamic analysis – Computer modelling
MAIN HEAT SOURCES Although there are many ways in which heat can be generated, directly or indirectly, the following are some of the main sources in building interiors:
Solar Heat Gain: There are three different ways in which heat from the sun can reach interior spaces - conduction, convection and radiation. Conduction occurs across walls and roofs, since they are exposed to a temperature difference between building interiors and the warmer outdoor environment. Convection refers to heat transfer due to the bulk movement of hot outdoor air, or indoor air movement between surfaces at different temperatures. Finally, radiation is a direct form of heat transfer that occurs when sunlight enters buildings through windows or other transparent surfaces. Both radiation and convection can interact with conduction at the surfaces of walls and roofs. For many buildings, the sun is the single largest source of heat. Depending on how solar heat gain occurs, its effects can be felt immediately or over a period of time. For example, solar heat entering via glass windows (radiation) has an immediate effect. On the other hand, when heat gain occurs by conduction across walls, the walls themselves store heat and it continues to be released indoors at night.
Heat from Human Beings: Occupants are also a major source of heat in building interiors. Consider that a human consumes hundreds of calories each day in the form of food, and part of this energy is released as heat during metabolic processes. The heat released by humans is even higher during intense physical activity, through perspiration (sweating). Consider that the heating effect of humans also increases depending on occupant density. As a result, the human contribution to the total heat load can be especially high in large air-conditioned spaces like halls, auditoriums, theatres, cinemas and airports
Outdoor Air Heat: The warmer air outside of conditioned spaces is called outdoor air or atmospheric air. Due to its higher temperature, outdoor air tends to increase the average room temperature when it enters indoor spaces. Although some air exchange is normal when doors and windows are open, outdoor air can also enter conditioned spaces through leaks around doors, windows and other building envelope elements. The heat held by outdoor air comes in great part from the sun, but it can also originate from vehicles or from other buildings.
Heat from Electrical and Electronic Appliances: Indoor spaces are filled with electrical and electronic appliances such as lighting fixtures, television sets, coffee machines, water heaters, etc. These appliances consume electricity and release some heat in air-conditioned spaces. Use energy-efficient appliances to minimize their heating effect.
HEATING LOAD ESTIMATION Heating-load estimate is prepared on the basis of “maximum probable heat loss” of the room or space to be heated. Following points should be considered while making heat- load calculations:
Transmission heat loss - The transmission heat loss from walls, roof, etc., is calculated on the basis of just the outside and inside temperature difference.
Solar radiations – Normally there are no solar radiation present and hence no solar heat gain at the time of the peak load which normally occurs in the early morning hours. a) Heat transfer through opaque surfaces: This is a sensible heat transfer process. The heat transfer rate through opaque surfaces such as walls, roof, floor, doors etc. is given by:
Q opaque = A. U. ∆T
Where U is the overall heat transfer coefficient and A is the heat transfer area of the surface on the side of the conditioned space. ∆T is the just the outside and inside temperature difference. b) Heat transfer through fenestration: Heat transfer through transparent surface such as a window, includes heat transfer by conduction due to temperature difference across the window and heat transfer due to solar radiation through the window. The heat transfer through the window by convection is calculated
Q Trans = A unshaded. SHGFmax. SC.CLF
Where A
unshaded
is the area exposed to solar radiation, SHGFmax and SC are the
maximum Solar Heat Gain Factor and Shading Coefficient, respectively, and CLF is the Cooling Load Factor.
Heat transfer due to infiltration- Heat transfer due to infiltration consists of both sensible as well as latent components. The sensible heat transfer rate due to infiltration is given by:
Where V0 is the infiltration rate (in m3 /s), ρo and cp,m are the density and specific heat of the moist, infiltrated air, respectively. To and Ti are the outdoor and indoor dry bulb temperatures. The latent heat transfer rate due to infiltration is given by:
Where hfg is the latent heat of vaporization of water, W o and W i are the outdoor and indoor humidity ratio, respectively. The latent heat transfer rate due to infiltration is given by:
Where hfg is the latent heat of vaporization of water, W o and W i are the outdoor and indoor humidity ratio, respectively.
Internal loads: The internal loads consist of load due to occupants, due to lighting, due to equipment and appliances and due to products stored or processes being performed in the conditioned space. a)
Load due to occupants: - The internal cooling load due to occupants consists of both sensible and latent heat components. The rate at which the sensible and latent heat transfer take place depends mainly on the population and activity level of the occupants. Since a portion of the heat transferred by the occupants is in the form of radiation, a Cooling Load Factor (CLF) should be used similar to that used for
radiation heat transfer through fenestration. Thus the sensible heat transfer to the conditioned space due to the occupants is given by the equation:
Table below shows typical values of total heat gain from the occupants and also the sensible heat gain fraction as a function of activity in an air conditioned space. Since the latent heat gain from the occupants is instantaneous the CLF for latent heat gain is 1.0, thus the latent heat gain due to occupants is given by:
b) Load due to lighting: - Lighting adds sensible heat to the conditioned space. Since the heat transferred from the lighting system consists of both radiation and convection, a Cooling Load Factor is used to account for the time lag. Thus the cooling load due to lighting system is given by:
The usage factor accounts for any lamps that are installed but are not switched on at the time at which load calculations are performed. The ballast factor takes into account the load imposed by ballasts used in fluorescent lights. A typical ballast factor value of 1.25 is taken for fluorescent lights, while it is equal to 1.0 for incandescent lamps. c) Internal loads due to equipment and appliances:- The equipment and appliances used in the conditioned space may add both sensible as well as latent loads to the
conditioned space. Again, the sensible load may be in the form of radiation and/or convection. Thus the internal sensible load due to equipment and appliances is given by:
A typical example:Heat load calculations for the residential building:Direction House Faces: North Gross Floor area (of the house): 1500 sq. ft. Gross inside volume (of the room for which heat load calculations are being done): 300 sq. ft. Design Conditions: Dry Bulb Temp (DBT) Outside – 100 F, Inside – 78 F, Difference - 22 F Average number of people inside the room = 6 SOLUTION - Let the size of the room is 20 ft x 15 ft = 300 sq ft, which is the total floor area of the room. Let us suppose the height of each wall is 12 ft and none of them are insulated. Two walls of this room if length 20 ft and 15 ft are exposed directly to the sun, while remaining two are partitions.
Direct Solar Heat Gain by the Windows = There are three windows in the room each of the size 6 x 4 = 24 sq ft. There is one window each in east, south and west direction. The glass of the all windows is single, there is no shading and no outside awnings. For window in east direction, factor for window is 100, while for window in south and west directions it is 75 and 150 respectively. Solar heat gained = Area x factor For window in east direction it is = 24 x 100 = 2400, For window in south it is 24 x 75 = 1800,
For window in west it is 24 x 150 = 3600. The highest of all these, 3600 has to be selected. Thus the total solar heat gained by the window is 3600 BTU/HR.
Solar Heat Gained by the Windows due to Designed Conditions (Internal and External Temperature Difference) The total area of three windows is 24 + 24 + 24 = 72 sq ft and they are all of single glass. Since the difference between external and internal dry bulb temperature is 22F corresponding factor based on designed conditions is 27. Solar heat gained by the windows due to design temperature = Area x factor = 1944 BTU/HR
Heat Gained by the Walls = the height of each wall is 12 ft and none of them are insulated. Two walls of this room if length 20 ft and 15 ft are exposed directly to the sun, while remaining two are partitions.
The total area of walls exposed directly to the sun = 20 x 12 + 15 x 12 = 420 sq ft Since the designed temperature difference is 22F and there is no insulation, the factor associated with it is 7. The total BTU/HR gained by the walls exposed directly to the sun. = area x factor = 420 x 7 = 2940 BTU/HR
Heat Gained by the Partitions = There are two partitions in the room of size 20 x 12 = 240 sq ft and 15 x 12 = 180 sq ft. The first one is with air conditioned room and the other with non-air conditioned room. For heat load calculations we have to consider only the second one. The factor associated with designed temperature difference of 22F is 4. Hence the total heat gained by partition is 180 x 4 = 540 BTU/HR.
Heat Gained by the Roof = the size of roof is same as the size of the floor, which is 20 x 15 = 300 sq ft. The roof is exposed directly to the sun, it is flat with no vented air and it is noninsulated. For 22F of design temperature difference, the factor associated with it is 34. Thus the total heat gained by the roof is 300 x 34 = 10200 BTU/HR.
Heat Gained by the Ceiling = since the roof is directly exposed to the sun, there is no ceiling for the room, hence there is no heat gained by the ceiling.
Heat Gained by the Floor = the size of the floor is 20 x 15 = 300 sq ft. Let us consider that the room is located over other non-conditioned room, so it gains some heat from it. For the designed temperature difference of 22F, the associated factor is 4. Thus the heat gained by the floor is 300 x 4 = 1200 BTU/HR.
Heat Gained by the Room Air from the Outside Air = The total amount of outside air or the infiltrated air inside the room is proportional to the floor area of the room, thus the total floor area, 300 sq ft, of the room has to be considered. The factor associated with it for designed temperature difference of 22F is 3. Thus the heat gained by the room air from the outside air is 300 x 3 = 900 BTU/HR.
Heat Gained by the Room Air from the People or Occupants = Let us suppose the average number of people inside the room would be six. Thus the heat gained by the room air from people is 6 x 200 = 1200 BTU/HR.
Subtotal of all the Heat Gained by the Room Air = the subtotal heat gained by the room air is total of all the heat gains as mentioned.
The total heat gained = 3600 + 1944 + 2940 + 540 + 10200 + 1200 + 900 + 1200 = 22524 BTU/HR.
Latent Heat Allowance = the latent heat allowance includes heat absorbed from the moisture and other small sources. The latent heat allowance is 30% of subtotal, Which is 0.3 x 22525 = 6757.5 BTU/HR.
Total Heat Load inside the Room = Thus the total heat load inside the room is 22524 + 6757.5 = 29281.5 BTU/HR.
Recommended Total Tonnage of AC and Type of AC = One ton of AC = 12000 BTU/HR. Thus total tonnage required in the room is 29281.5/12000 = 2.44 tons, which can be taken as 2.5 TR. The total recommended tonnage for the room is 2.5. For this tonnage split air conditioner is the best option.