Respon sibilities Legend CSD
SITE TEST REPORT Contractor’s name:
Contracting Co. Ltd.
Date : Customer: SEC-EOA SEC – EOA Contract No. :
Name of Substation: 380/230/115/13.8KV AL-DAEREE
31131130/00
Potential Transformer Panel No:W626
Equip. No.:
Page 1 of 4 Dwg. Ref.:
Record No.:
POTENTIAL TRANSFORMER TEST
GENERAL DATA AND INFORMATIONS. Circuit Ref: Panel No: Make Type
Rated voltage Sr.No:-R Sr.No:-Y Sr.No:-B
DESCRIPTION Primary Volts Secondary Volts Class Burden VT Ratio Voltage factor (Vf)
WINDING -1
WINDING -2
DATE: TESTING ENGINEER
CSD- Engineer
Signature: ________________
Signature: ________________
Name
Name
: ________________
: ________________
SITE TEST REPORT
Date :
Contractor’s name:
Contracting Co. Ltd.
Customer: SEC-EOA SEC – EOA Contract No. :
Name of Substation: 380/230/115/13.8KV AL-DAEREE
31131130/00
Potential Transformer Panel No:W626
1.
Equip. No.:
Page 2 of 4 Dwg. Ref.:
Record No.:
INSULATION RESISTANCE TEST: Instrument
:
Make Model No. / Sl. No.
: :
Applied Voltage
:
Criteria
:
Primary to Ground 5 KV DC for one minute. Primary to Secondary 2.5 KV DC for one minute. Secondary to Ground 1 KV DC for one minute. More than 1000 M Ohms for Primary – Secondary / Earth. More than 10 M Ohms for Secondary – Earth
Applied Between Phase A
IR Value in G- Ohms Phase B
Phase C
Primary - Earth Primary-Secondary-1 Primary – Secondary 2 Secondary1 – Earth Secondary 2 – Earth
DATE: TESTING ENGINEER
CSD- Engineer
Signature: ________________
Signature: ________________
Name
Name
: ________________
: ________________
Remarks
SITE TEST REPORT
Date :
Contractor’s name:
Customer: SEC-EOA
Contracting Co. Ltd.
SEC – EOA Contract No. :
Name of Substation: 380/230/115/13.8KV AL-DAEREE
31131130/00
Potential Transformer Panel No:W626 2.
Equip. No.:
Page 3 of 4 Dwg. Ref.:
Record No.:
Winding Resistance (Secondary side) Instrument
:
Model No. / Sl. No.
:
Criteria
:
CPC 100 PB834V Within ± 5% of Factory Test Report Amb.Temp : 30 o C
Measured Value in Ohms at 75o C
Core Phase 1 A
2 1
B
2 1
C
2
Full Wdg Mid Tap Full Wdg Mid Tap Full Wdg Mid Tap Full Wdg Mid Tap Full Wdg Mid Tap Full Wdg Mid Tap
87 56.6 83.7 55.3 89.7 58.8 80.9 56.1 89.7 60.6 83.2 56.5
Factory Value Ohms at 75o C 90 58 85 56 91 60 85 57 92 61 85 58
% Variation
Remarks
3.3 2.4 1.5 1.2 1.4 2.0 4.8 1.6 2.5 0.7 2.1 2.6
Formula to convert winding resistance to reference temperature at 75 C for copper winding. NOTE: 1. Rc = Rm =
Calculated value at 75 C Measurement value which contained a measurement cable.
NOTE: 2 Calculated 75 C Rx = Ta =
Rc = (Rm-Rx) x (234.5+75) (234.5+Ta)
Resistance value of the measurement cable. Ambient Temperature C
NOTE: 3 Resistance value of measurement cable Rx = _______ Ω
DATE: TESTING ENGINEER
CSD- Engineer
Signature: ________________
Signature: ________________
Name
Name
: ________________
: ________________
SITE TEST REPORT
Date :
Contractor’s name:
Customer: SEC-EOA
Contracting Co. Ltd.
SEC – EOA Contract No. :
Name of Substation: 380/230/115/13.8KV AL-DAEREE
31131130/00
Potential Transformer Panel No:W626
Equip. No.:
Page 4 of 4 Dwg. Ref.:
Record No.:
3. Ratio Test INSTRUMENTS:
Make:
Model:
Voltage Applied to Primary:
Phase
Volt (Full Tap) &
Measured Secondary Voltage
Tap
Core-1
Volt (Mid Tap)
Measured Ratio
Core-2
Core-1
Sr.No:
Core-2
Theoretical Ratio Core-1
Core-2
% Error Core-1
Full Tap A Mid Tap Full Tap B Mid Tap Full Tap C Mid Tap 4. POLARITY TEST : Instrument
: Tick here if found okay
Phase
Core
A
1
Polarity checked & found okay
2 B
1 2
C
1 2
DATE: TESTING ENGINEER
CSD- Engineer
Signature: ________________
Signature: ________________
Name
Name
: ________________
: ________________
Core-2