SUPRON 3 company has been founded in 1992. We are market leader in fire-fighting and safety equipment. Internal hydrants have been produced by us since 1995 r. We have 8 CE certificates for hydrants and 1 volountary certificate for hydrant nozzle. All certificates are issued by Scientific and Research Centre for Fire Protection – National Research Institute ( CNBOP-PIB ) - notified body No 1438. We are also owner of

12 Certificates of admittance for fire hoses and other fire-fighting equipment. We work under quality certificate no 1144/4/2013 according to PN-EN ISO 9001:2009 in the field of activities: design, production and distribiution of fire-fighting and industrial safety goods and services.

With FN SERVISS we have been working over 12 years - since 2003

INTERNAL HYDRANTS SUPRON 3 products safe and professional solution for fixed firefighting systems – hose systems

ACTS & REGULATIONS until 1st July 2013

COUNCIL DIRECTIVE 89/106/EEC

of 21 December 1988 on the approximation of laws, regulations and administrative provisions of the Member States relating to construction products

At present

Regulation ( EU) No 305/2011 of the European Parliament and of the Council of 9 March 2011 laying down harmonized conditions for the marketing of construction products (CPR)

CPR repeals Council Directive 89/106 / EEC and lays down harmonized conditions for the marketing and placing on the market construction products and specifies: • basic requirements for buildings, • the rules for declaring the performance of construction products, • the rules for the assessment and verification of constancy of performance, • the obligations of manufacturers, importers and distributors.

Until 1st July 2013 :

At present:

The manufacturer received CERTIFICATE OF CONFORMITY ( CE)

The manufacturer receives CERTYFICATE OF THE CONSTANCY OF PERFORMANCE

and on this basis issued DECLARATION OF CONFORMITY

and on this basis issues DECLARATION OF PERFORMANCE

and marked construction product with CE marking

and marks construction product with CE marking

REGULATION (EU) No 305/2011 OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL of 9 March 2011 laying down harmonized conditions for the marketing of construction products and repealing Council Directive 89/106/EEC Article 66 Transitional provisions 1. Construction products which have been placed on the market in accordance with Directive 89/106/EEC before 1 July 2013 shall be deemed to comply with this Regulation.

2. Manufacturers may draw up a declaration of performance on the basis of a certificate of conformity or a declaration of conformity, which has been issued before 1 July 2013 in accordance with Directive 89/106/EEC.EN 4.4.2011 Official Journal of the European Union L 88/31 This article confirms that our CE certificate are still valid and we can issue declaration of performance

Article 4 of Regulation 305/2011 obligates manufacturers of construction products to draw up a declaration of performance when construction product, that is covered by a harmonized standard or conforms to a European Technical Assessment issued for that product, is placed on market. According to Article 6 of Regulation 305/2011, that declaration should be drawn up using the model set out in Annex III to that Regulation.

Commission Delegated Regulation No 574/2014 of 21 February 2014 Amending Annex III to Regulation No 305/2011 on the model to be used for drawing up a declaration of performance on construction products

Technical details necessary to implement the system of assessment and verification of constancy of performance are included in relevant harmonized standards. Harmonized standards refer to the intended use of construction products which include and define the methods and criteria for assessing the performance of construction products in relation to their essential characteristics.

Construction products: Hose system with semi –rigid hose ( EN 671-1) Hose system with lay-flat hose ( EN 671-2)

Intended use: Fixed installations to provide the occupants of a building the means to control and extinguish a fire nearby ( EN 671-1 & EN 671-2)

HARMONIZED STANDARD for hydrants until 1st July 2013

At present

EN 671-1:2002: Fixed firefighting systems – Hose systems – Part 1: Hose systems with semi-rigid hose

EN-671-1:2012 Fixed firefighting systems – Hose systems – Part 1: Hose systems with semi-rigid hose

PN-EN 694:2007 Fire-fighting hoses – Semi-rigid hoses for fixed systems

PN-EN 694:2014 Fire-fighting hoses – Semi-rigid hoses for fixed systems

671-2:2002 Fixed firefighting systems – Hose systems – Part 2: Hose systems with lay-flat hose

EN-671-2: 2012 Fixed firefighting systems – Hose systems – Part 2: Hose systems with lay-flat hose

PN-EN 14540:2008 Fire-fighting hoses – Non-percolating layflat hoses for fixed system

PN-EN 14540:2014 Fire-fighting hoses – Non-percolating layflat hoses for fixed system

Hydrant - definition EN 671-1:2012 Point 3.3

EN 671-2: 2012 Point 3.3

Manual fire hose reel; manual hose reel

Fire hose system; hose system

firefighting appliance consisting of a reel with water supplied through the centre, manual inlet stop valve adjacent to the reel, semi-rigid hose, shut-off nozzle and, where required, a hose guide

firefighting applience consisting essentially of a cabinet or cover, hose suport, manual stop valve, lay-flat hose with couplings, shut-off nozzle

Hoses - requirement EN 671-1:2012

EN 671-2: 2012

The hose shall be semi-rigid and according to EN 694

The hose shall be lay-flat and according to EN 14540

Inside diameter of the hose: 19 mm 25 mm 33 mm

The inside diameter of the hose shall be maximum 52 mm EN 14540:2014 allowed inside diameter: 25, 38, 40/42/45, 50/51/52

The lenght of the hoses shall be in one piece and should not exceed 30m

For handling reasons the lenght of the hose should not exceed 20m

Maximum working pressure EN 671- 1:2012

EN 671- 2: 2012

19 mm, 25 mm – 1,2 MPa

1,2 MPa

33 mm – 0,7 MPa

Shut-off nozzle EN 671-1:2012

EN 671-2: 2012

Nozzle with a sprey setting shall give a spray angle as follows: sheet spray : 90° ± 5° conical spray: not less than 45° The hose shall terminate in a shut-off nozzle, which shall give following control settings:

SHUT- SPRAY -

- JET

This kind of nozzle doesn’t meet requiremnts of EN 671

Cabinet EN 671-1:2012

EN 671-2: 2012

Cabinet for hose system shall be fitted with a door. Cabinet doors shall open to min. 170° to allow the hose to be run out freely in any direction. Cabinet shall be free of sharp edges, which might damage the equipment or cause injury.

System of covered/unseen hinges Protected by utility model. This solution offer high quality aesthetic performance, smooth door on whole surface and possibilities to open the door for 180°. Only this solution meets the high requirements of interior design.

Cabinet EN 671-1:2012

EN 671-2: 2012

Lockable cabinet shall be provide with an emergency opening device, which may be protected only by transparent frangible material. Innovative solution for key fixing

This solution is registered in Patent Office of the Republic of Poland. This allows us to use PATENT lock in non standards versions i.e. with glass or mirror. Hydrant is locked and there is no need to use additional cabinet for key.

Cabinet EN 671-1:2012

EN 671-2: 2012

Cabinet may also be used to contain other firefighting equipment, provided that the cabinet is of sufficient size and the equipment does not interfere with the prompt use.

Cabinet EN 671-1:2012

The colour of the hose reel shall be RED

EN 671-2: 2012

The colour of the hose suport shell be RED

Flow rate Q at a pressure P is related to the equation

𝑄 = 𝐾 10𝑃

EN 671-1:2012 point 4.2.2 Minimum flow rates and minimum K-coefficient according to pressure Nozzle or equivalent diameter mm

Minimum flow rate Q liters/minutes

K-coefficient

P= 0,2 MPa

P= 0,4 MPa

P = 0,6 MPa

4

12

18

22

9

5

18

26

31

13

6

24

34

41

17

7

31

44

53

22

8

39

56

68

28

9

46

66

80

33

10

59

84

102

42

12

90

128

156

64

EN 671-1:2012 Hydrants with semi-rigid hose 25mm Flow rate confirmed by notified body 1438 CNBOP-PIB Scientific and Research Centre for Fire Protection – National Research Institute

FLOW rate Q Pressure

Equivalent diameter - 10 mm

Coefficient (factor) K

0,2 MPa 0,4 MPa 0,6 MPa -

Dispersed Compact Dispersed Compact jet jet jet jet fire hose fire hose fire hose fire hose 30 m 30 m 20 m 20 m 61 l/min 60 l/min 65 l/min 64 l/min 86 l/min 85 l/min 92 l/min 91 l/min 104 l/min 103 l/min 112 l/min 111 l/min 43 43 46 46

EN 671-1:2012 Hydrants with semi-rigid hose 33mm Flow rate confirmed by notified body 1438 CNBOP-PIB

FLOW rate Q Pressure

Equivalent diameter - 12 mm

Coefficient (factor) K

0,2 MPa 0,4 MPa 0,6 MPa -

Dispersed jet Compact jet

107 l/min 151 l/min 184 l/min 75

90 l/min 128 l/min 157 l/min 64

EN 671-2:2012 point 4.2.2 Minimum flow rates and minimum K-coefficient according to pressure Nozzle or equivalent diameter mm

Minimum flow rate Q liters/minutes

K-coefficient

P= 0,2 MPa

P= 0,4 MPa

P = 0,6 MPa

9

65

92

113

46

10

78

110

135

55

11

96

136

167

68

12

102

144

176

72

13

120

170

208

85

EN 671-2:2012 Hydrants with lay-flat hose 52mm Flow rate confirmed by notified body 1438 CNBOP-PIB

FLOW rate Q Pressure

Equivalent diameter - 13 mm

Coefficient (factor) K

0,2 MPa 0,4 MPa 0,6 MPa -

Dispersed jet Compact jet

172 l/min 244 l/min 299 l/min 122

155 l/min 220 l/min 270 l/min 110

INTERNAL HYDRANTS produce by SUPRON 3 Our wide range of different type include all types of hydrants:  With semi-rigid hose DN 25, 33 and 19mm

 With lay-flat hose DN 52mm.

Internal hydrants DN25 we can divide on : On wall/hang on

Hydrants 25 with hose lenght 20m / 30m

Hydrants 25 with place for extinguisher next to hose reel ( separate space for extinguisher) with hose lenght 20m / 30m

Recess / in wall

Internal hydrants DN25 we can divide on : On wall/hang on

Hydrants 25 with place for extinguisher under hose reel with hose lenght 20m / 30m

Hydrants 25 lateral type with hose lenght 20m / 30m

Recess / in wall

Internal hydrants DN25 we can divide on : On wall/hang on

Recess / in wall

Hydrants 25 lateral type with place for extinguisher under hose reel with hose lenght 20m / 30m

Stable/fixed type

Hose reel without cabinet with hose lenght 20m / 30m

Hinged /swing type

Internal hydrants DN25 FIT – the lowest depth

With hose lenght 20 / 30m - dedicated and design for pedestrian traffic places

Internal hydrants DN25 FIT – the lowest depth With hose lenght 20 / 30m – depth 160mm

With hose lenght 20 / 30m and place for extinguisher – depth 180mm

Internal hydrants DN33 we can divide on : Hydrants 33 with hose lenght 20 / 30m

Hydrants 33 with place for extinguisher with hose lenght 20 /30m

Internal hydrants DN33 we can divide on : Hydrants 33 lateral type With hose lenght 20 / 30m

Hose reel 33 without cabinet Fixed and hinged type with hose lenght 20 / 30m

Internal hydrants DN52 we can divide on : According to point 3.4 of the EN 671-2:2012 Hose suport – device used to hold the hose and shall be one of the following types: Type 1: rotating reel Type 2: cradle with hose double coiled Type 3: hose basket with hose flaked withdrawn standard EN 671-2:2001 requested also special marking according to type of mounting the cabinet: hose diameter A : for door with frame B: recces C: on wall

Sample:

EN 671-2 C- 1/52-20

hose lenght

Internal hydrants DN52 we can divide on : Hydrants 52 with hose suport: cradle or basket with hose double coiled (type C / B – 2)

Hydrants 52 with hose suport: Hose reel (type C / B - 1)

Internal hydrants DN52 we can divide on : with cradle - 2 Hydrants 52 with hose lenght 15 / 20 m depth 180mm

Hydrants 52 with additional hose hose lenght 2x15m / 2x20m

Internal hydrants DN52 we can divide on :with basket - 3 Hydrants 52 with place for extinguisher, with hose lenght 15 / 20 m

Internal hydrants DN52 we can divide on : with basket - 3 Hydrants 52 with hose lenght 15 / 20 m lateral type

Internal hydrants DN52 we can divide on : with hose reel - 1 Hydrants 52 with hose lenght 15 / 20 m

Internal hydrants DN52 we can divide on : with hose reel - 1 Hydrants 52 with hose reel 15 / 20 m with place for extinguisher

Internal hydrants DN52 we can divide on : with hose reel - 1 Hydrants 52 with hose 15 / 20 m lateral type

Advantages of our hydrants: Full flexibility of hydrants installation and easy change connection side right – left (only need to turn it round 180°, without any other changes). Holes for water connection are blanked, enable connection to water pipe 1” or 2”. 6 water connections available: from the side, from the back, from the top.

Sometimes it’s too many possibilities 

Advantages of our hydrants: Fire hose reel ( for hydrants DN 25 & 33) Painted by powder paint, only in red colour RAL 3000 - according to standard PN-EN 671-1. Swinging hose reel up to 180° with brass water axis and develop force controller.

System of covered/unseen hinges. This solution is registered in Patent Office of the Republic of Poland and enables the simply adjusting of the cabinet door position (smooth door, easy open 180°). This solution improves also the cabinets appearance and aesthetics which meets also high requirements of interior design.

Advantages of our hydrants: Innovative solution for key fixing This solution is registered in Patent Office of the Republic of Poland. This allows us to use PATENT lock in non standards versions i.e. with glass or mirror. Hydrant is locked and there is no need to use additional cabinet for key.

Simply lock - EURO Can be protected with seal. As the only producer we offer the lock with the same colour as a cabinet

Advantages of our hydrants: Crimped connection of nozzle with water axis. The water nozzle is connected with fire hose in inseparable way, by crimping, according to the solution reserved by SUPRON 3. This solution ensures reliability of connection, ergonomics of water nozzle handle, aesthetics as well as eliminates the possibility of injuring oneself. This considerably reduces the time annual inspection of fire hydrants.

Brass valve 1” in hydrants 25 Brass valve 1” is a standard offered in hydrants 25. Highier quality of connection aluminium – brass, highier resistance for water pressure, valve made by forging ( not casting).

Advantages of our hydrants: Valve 2” can be mounted in hydrants 25 & 33 by using slant reduction In hydrants 33, AL valve 2” is a standard. As a only producer we offer connection by slant reduction with GOST coupling

Hydrant hose DN 52 Hydrant hose 52 produced by SUPRON 3 according to : EN 14540

Innovative technology of connecting hose with coupling eliminating linking and possibilities of hose sawing on the end of coupling sleeve. It also improve the ergonomics and aesthetic.

Advantages of our hydrants: Connection of hydrant nozzle with hydrant hose Hydrant nozzle connected with adapter Hydrant nozzle crimped by sleeve

Connection to hydrant valve 1” Short connection hose without clamp – made by crimping – warranty 100% of tightness, eliminate possibility of injury oneself. Threated connection is a standard. Possibility of connection with adaptor and hose coupling. This solution reduce time of the hydrants servicing and maintenace.

Advantages of our hydrants: The minimum sizes and weight: the smallest (minimum) hydrant’s sizes produced in Poland and thus less use of materials and energy factors (sheet metal, paint, water, electricity), which directly affects the environment protection, the lightest hydrants in Poland and thus the ease and simplicity of installation Innovative solutions protected by utility models and industrial designs

Made in Poland Flexibility We adapt to customer needs. Thanks to the versatility of solutions and minimum dimensions, we can perform cabinets to meet the needs of customers: tailored dimensions, colors, design.

Possibilities of hydrants versions FASCADE – Zinc plated steel sheet, painted by fascade paint. Weather and UV radiation resistant solution.

FRONT INOX – cabinet front made of stainless steel , cabinet body in standard.

INOX – stainless steel syrface finisz 240. In environments with progressive components (eg. swimming pools) we offer special stainless steel SS316L

Possibilities of hydrants versions Frame and cabinet door fixed after finishing works. Additional advantages: door opening direction can be change without turning the cabinet NOWELTY!!!

Possibilities of hydrants versions

Safety glass matt or transparent

NOWELTY! – new construction gives possibility of easy changing safety glass

Safety glass with any graphics

Possibilities of hydrants versions NOWELTY! - Hydrants with pressure gauge for easy checking of water network’s pressure

Possibilities of hydrants versions Hydrants with hole for fire button

Possibilities of hydrants versions Hydrants with small plexi glass

Possibilities of hydrants versions

Signal device of valve opening

Signal device of cabinet door opening

Roller shuter

Supports and bases for hydrants – height is designed as to allow valve mounting at 1,35m

Supports for hydrants

Application: free-standing hydrants against the wall hydrants mounted on the partition (eg. gypsum board) hydrants mounted in recess on the partition (eg. gypsum board)

Bases for hydrants

Application: free-standing hydrants hydrants mounted on the partition (eg. gypsum board)

Possibilities of hydrants versions Internal hydrants with constant flow Qconst Design and solution for : •

• •

buildings where hydrants and valves often are connected with other fire protection systems (eg. sprinklers) buildings where need to decide if hydrants should be supplied with water from the water supply network or from its own pump station high office buildings which have their own pumping station and there is need to install all types of internal hydrants

Thanks to the technical solutions, the compact size, ease of use and maintenance these hydrants are facilitate design, construction and supervision of installation of fire protection in the building and directly contribute to the reduction of investment costs. Hydrants have been tested by polish notified body CNBOP-PIB. The results confirm hydrants constant flow, which is not affected by a change in the supply pressure.

Hydrants with constant flow Qconst

Cabinets for hydrant valve 2” (52)

Cabinet for 1 valve

Cabinet for 2 valves

Cabinets for hydrant valve 2” (52)

Cabinets are made in universal version: enable connection from the side or from above. Changing is simple just by turn for 180°.

Lock type OTS: For Polish market cabinets are quipped in specialized lock, opened and locked by pick-shaped pointed poll of light fire axe - according to PN-B-02861 Also can be equpied with simply lock or lock with key.

Foam unit

Foam units allows to extinguish fires: • heavy foam with low expansion Foam Branchpipes or water • medium foam with Medium Expansion Foam Branchpipes or water Application: • fuel storage • paints and varnishes storage • fuel logging stations • Boiler-houses and machinery rooms • other places with high fire risk

Foam unit

Foam unit

Other production

Thank you for your attention 

More Documents from "Judita"