CONTACTOS REGULADOS

Representación de Contactos.

Circuit o C1



Contacto monofásico dúplex en muro 500 watts



Contacto monofásico dúplex en mesa 500 watts

Numero de contactos 3

Desarrollo. C2 C3 C4 C5 C6 C7 C8 C9 C10 C11 C12 C13 C14 C15 C16 C17 C18 C19 C20 C21 C22 C23 C24 C25 C26

3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 4 4

[1] Contactos Regulados (3 por circuito) = 24 Circuitos. [2] Contactos Regulados (4 por circuito) = 2 Circuitos. Total circuitos = 26 Circuitos.

500 watts c/u

[1] 24 Circuitos

1,500 watts p/cir.

24 circuitos∗1,500 watts=36,000 watts . [2] 2 Circuitos

500 watts c/u

2,000 watts p/cir.

2 circuitos∗2,000 watts=4,000 watts .

Total watts=[ 36,000+4,000]watts=40,000 watts=40 Kw .

Corriente nominal. ¿=

40,000 watts =116.63 A 117 A √ 3 ( 220 ) (.9)

Protection. ¿=117 A ( 1.25 )=146.25 150 A

Caida de tension.

R

150 A

Distancia del tablero al circuito más lejano = 50 m

45 KVA

Calibre 1 AWG

50 m

℮=

Alimentación.

( 117 A ) ( .0255 ) √3 ¿ Z √3 x 100= x 100=2.34 220 220

Debe ser menor o igual al 3% calibre 1 AWG si cumple 1 – 1 AWG por fase. 1 – 1 AWG por Neutro. 1 – 6 AWG por tierra de sistema .

Modelo de tablero.

Tablero 01

NQ304AB225

Alimentación de tablero. Distancia del transformador al tablero= 30 metros

Calibre 4/0 AWG ℮=

( 225 A )( .0072 ) √ 3 ¿ Z √3 x 100= x 100=1.27 220 220

Debe ser menor o igual al 3% Calibre 4/0 AWG si cumple

Cedula de cableado

meració n 1 2 3 4

4

2

2

2 2

4

2 4

3

1 2

2 1

2

3

Tablero 01.

#

Orientación con tabla.

Tubería TCPG.

Descripción 1 #1 AWG Fase, 1 #1 AWG Neutro, 1 #6 AWG Tierra de sistema. 2 #1 AWG Fase, 2 #1 AWG Neutro, 2 #6 AWG Tierra de sistema. 3 #1 AWG Fase, 3 #1 AWG Neutro, 3 #6 AWG Tierra de sistema. 4 #1 AWG Fase, 4 #1 AWG Neutro, 4 #6 AWG Tierra de sistema. Cuadro de cargas

Ductos 1 1/4” TCPG 2” TCPG 2 1/2 TCPG 2 1/2 TCPG

otal

Fases A 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 1000 13,500

B 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 13,000

C 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 1,000 500 13,500

Circuito

Numero de contactos

Circuito 01 Circuito 02 Circuito 03 Circuito 04 Circuito 05 Circuito 06 Circuito 07 Circuito 08 Circuito 09 Circuito 10 Circuito 11 Circuito 12 Circuito 13 Circuito 14 Circuito 15 Circuito 16 Circuito 17 Circuito 18 Circuito 19 Circuito 20 Circuito 21 Circuito 22 Circuito 23 Circuito 24 Circuito 25 Circuito 26 26

3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 4 4 80

Desbalance Desbalance=

F mayor−F menor 13,500−13,000 x 100= x 100=3.5 F mayor 14,000

El desbalance debe ser igual o menor al 3%, si entra dentro del rango permitido Alumbrado

Tipos de lámparas y potencia de c/u. Cantidad de lámparas 48 9 145 51

Circuit o C1 C2 C3 C4

Representació n

Nombre

potencia

ILU - 01 ILU - 02 ILU - 03 ILU - 04

13 watts 40 watts 33 watts 40 watts

Numero de Lámparas 48 (ILU-01) , 9 (ILU-02) , 30 (ILU-03) 55 ( ILU-03) , 1 (ILU-04) 60 (ILU-03) 50 (ILU -04) Total

Potencia de cada circuito 1,974 watts 1,855 watts 1,980 watts 2,000 watts 7,812 watts  7,815 watts

Corriente nominal. ¿=

7815 =22.7 A 23 A √ 3 ( 220 ) (.9)

Protection. ¿=23 A ( 1.25 ) =28.75 30 A 30 A 50 m

Caída de tensión. Distancia del tablero a la lámpara más lejana = 50 m Calibre 10 AWG

℮=

( 23 A ) (.18 ) √ 3 ¿ Z √3 x 100= x 100=3.2 220 220

Debe ser menor o igual al 3% calibre 10 AWG si entra dentro del rango permitido

Alimentación. 1 – 10 AWG por fase. 1 – 10 AWG por Neutro. 1 – 8 AWG por tierra de sistema .

Modelo de tablero. Se compartirá con las manejadoras para evitar costos innecesarios.

Cedula de cableado

1

1

1

1 2 2

2

2 3

3

1

1

1

Tablero 01.

1

#

11

1

Orientación con tabla.

Tubería TCPG.

Numer Descripción ación 1 1 #10 AWG Fase, 1 #10 AWG Neutro, 1 #8 AWG Tierra de sistema. 2 2 #10 AWG Fase, 2 #10 AWG Neutro, 2 #8 AWG Tierra de sistema. 3 3 #10 AWG Fase, 3 #10 AWG Neutro, 3 #8 AWG Tierra de sistema.

al

Ductos 1

/2” TCPG /4” TCPG 3 /4” TCPG 3

Cuadro de cargas

Fases A 664 (48 ILU-01, 1 ILU-02) 634 (18 ILU-03, 1ILU-04) 660 (20 ILU-03) 680 (17 ILU-04) 2,638

B 683 (8 ILU-01, 11 ILU-02) 594 (18 ILU-03) 660 (20 ILU-03) 680 (17- ILU-04) 2,617

C 627 (19 ILU-03) 627 (19 ILU-03) 660 (20 ILU-03) 640 (16- ILU-04) 2,554

Circuito

Numero de lámparas

Circuito 01 Circuito 02 Circuito 03 Circuito 04 4

87 56 60 50 253

Desbalance Desbalance=

F mayor−F menor 2,638−2,554 x 100= x 100=3.1 F mayor 2,638

El desbalance debe ser igual o menor al 3% si entra dentro del rango permitido

Manejadoras y condensadoras



Condensadoras 3 , 220 volts, 136,000 BTU, 11 toneladas, 12 KW c/u , 35 A.



Manejadoras 2 , 5 A c/u.

Desarrollo.

Condensadoras (6 condensadoras) = 72 Kw.

Corriente nominal ¿=

72,000 watts =209.9 A 210 A 3 ( 220 ) (.9)

300 A 15 m

meració n 1

Descripción

Ductos

3 #4 AWG Fase, 1 #8 AWG Tierra de Equipo.

1 1/2” TCPG

Cuadro de cargas Fases A 12,000

B

C

12,000 12,000 12,000 12,000 12,000

condensadora s

Numero de condensadoras

01 02 03 04 05 06

1 1 1 1 1 1

otal

24,000

24,000

24,000

6

6

Desbalance Desbalance=

F mayor−F menor 24,000−24,000 x 100= x 100=0 F mayor 24,000

El desbalance debe ser igual o menor al 3%, si entra dentro del rango permitido

1

1

1

1

1

Manejadoras (22 manejadoras) = 1.5 hp c /u =110 Amperes = corriente nominal.

meració n 1

Tablero 01.

Orientación con tabla. #

Tubería TCPG.

Descripción

Ductos

1 #3 AWG Fase, 1 #3 AWG, 1 #8 Tierra de Equipo.

I manejadora=

watts √ 3 (120 )( .9 )

Wattsmanejadora =I manejadora ( √ 3 ) (120 )( .9 ) ¿ ( 5 A ) ( √ 3 ) ( 120 ) ( .9 )=935.3 936 Watts Cuadro de cargas

1” TCPG

Fases A 1872 936 936 1872 936 936 7,488

otal

B 936 1872 936 936 1872 6552

C 936 936 1872 936 936 936 6552

Circuito

Numero de manejadoras

Circuito 01 Circuito 02 Circuito 03 Circuito 04 Circuito 05 Circuito 06 6

4 4 4 4 4 2 22

Desbalance Desbalance=

F mayor−F menor 7,488−6,552 x 100= x 100=12.5 F mayor 7,488

El desbalance debe ser igual o menor al 3%, por lo que se debería meter una carga más en la fase B para que las cargas estén balanceadas.

Protección. ¿=110 A ( 1.25 )=137.5 A .150 A

Caída de tensión. Distancia del tablero al circuito más lejano = 40 m Calibre 3 AWG

℮=

( 110 A ) ( .0252 ) √ 3 ¿ Z √3 x 100= x 100=2.80 220 220

Debe ser menor o igual al 3% calibre 3 AWG si cumple Alimentación. 1 – 3 AWG por fase.

150 A 40 m

1 – 3 AWG por Neutro. 1 – 8 AWG por tierra de sistema

Modelo de tablero. Espacios necesarios para Manejadoras y alumbrado = 10 Alumbrado = 7,815 w ¿=

watts Watts=¿ ( √3 ) ( 120 ) ( .9 ) √ 3 ( 220 ) ( .9 )

¿ 110 A ( √ 3 ) ( 120 )( .9 )=20,576.7 watts=20.5 Kw Alumbrado + manejadoras = (7,815 + 20,576) watts = 28,391  28.5 Kw

¿ ( alumbrado y manejadoras )=110 A+23 A=133 A

Protección= 133 A (1.25) = 166.25 A

Modelo de tablero. Tablero 03 NQ304AB225

Alimentación de tablero. Distancia del transformador al tablero= 60 metros

Calibre 1/0 AWG ℮=

( 133 A )( .0252 ) √ 3 ¿ Z √3 x 100= x 100=2.63 220 220

Debe ser menor o igual al 3% Calibre 1/0 AWG si cumple

Memoria de Calculo

Tablero 01 (contactos regulados) ero Tensión Potenci Corrient e [V] a e uito [W] nominal [A] 6 120 40,000 117 Tablero 02 (condensadoras) ero Tensión Potenci Corrient e [V] a e uito [W] nominal

Alimentació n 4

/0

Alimentació n

Modelo: NQ304AB225 Distanci Caída Contactos a de regulados [m] tensió n [%] 30 1.27 80 Modelo: NQ304AB225 Distanci Caída Condensadora a de s [m] tensió

[A]

n [%]

380 72,000 210 blero 03 (manejadoras y alumbrado) ero Tensión Potenci Corrient e [V] a e uito [W] nominal [A]

0

120

28,500

167

4

/0

Alimentació n

1

/0

Diagrama unifilar

60 2.38 6 Modelo: NQ304AB225 Distanci Caída Manejadoras y a de alumbrado [m] tensió n [%] 60 2.63 22 manejadoras y 253 lámparas

13.2 Kv

600 A

150 A

Contactos regulados

300 A

Condensadoras

150 A

Manejadoras y alumbrado