Murphy Oil Petro Chemical Lab State Fire Marshal Review

  • May 2020
  • PDF

This document was uploaded by user and they confirmed that they have the permission to share it. If you are author or own the copyright of this book, please report to us by using this DMCA report form. Report DMCA


Overview

Download & View Murphy Oil Petro Chemical Lab State Fire Marshal Review as PDF for free.

More details

  • Words: 4,869
  • Pages: 13
1 8201 West Judge Perez Drive Chalmette, LA _70043 Phone (504) 278-4477 Fax (504) 278-1583

S·t. Bern:ard Fi1:e Department

Fire Prevention Bureau

8/19/2009

New Construction Murphy Oil USA Owner/Contractor

P0364701

name

1615 E Judge Perez Owner/Contractor

address

Chalmette, LA 70043

Murphy Lab

Plan Review

City, State, Zip

Project Name

2305 E St. Bernard Hwy

Gibbs Const.

Project Location

Contact person

Chalmette, LA

504-733-4336

Project City

To whom it may concern:

Industrial

._ ..-.._Ihis is to advise you that we have reviewed the"dlawillgsand/or: -specifiCations for the subject proposed constructionand--. have determined that they appear to satisfactorily comply with the adopted laws, codes, rules and regulations of the S1.Bernard FirE Department subject to the following requirements marked below: 1.) Installation of U.L. rated electrically wired smoke detector. 2.) Provide a minimum of one 10lb ABC rated fire extinguisher for every 2500 sq. ft. of area. 3.) Certification/Recertification of the sprinkler system. This shall be provided by a registered certification company to the Fire Departm ent in written form.

IYYl 4.) Certification/Recertification of the in smoke/heat detection system. This shall be provided by a registered certification ~ company to the Fire Department written form. .

D D

5.) Certification/Recertification

~

7.) Any and all requirements by the State Fire Marshall shall also be required by the S1. Bernard Fire Department.

.

of the suppression/hood

system. This shall be provided by a registered certification

company to the Fire Department in written form.

. 6.) Const.ruct (1997).' and ihstaTlJ
.- system in accordance with NFPA 96 vent, and automatic extinguishing

This review applies to the new work indicated in the drawings and/or specifications and does not apply to existing non-conforming conditions (if any) or any item(s) which may have been overlooked by the Plan Reviewer. The above is valid for f8C days from the above date. If construction has not started within this period of time, this review shall become null and void. This offic, requires certification of the completed project in accordance with the approved documents (certificate enclosed). Occupancy of the project will not be permitted until we have received a completed certificate and a satisfactory inspection of the completed constructi( has been made by this office and the State Fire Marshal (if required). To schedule an inspection call this office Monday thru Friday between the hours of 8:30 a.m. and 12:00 noon. Please call tv (2) to three (3) weeks in advance.

.

., Inspector

Fire Prevention Bureau S1. Bernard Parish Fire Department Revised 2/03

PERMIT IIo

-, --,I·,. ,.._',' -.. ,I! ~.I SEPTIC/MECHANICAL "

APPLICATION -

Gibbs Construction LLC Date: 7-29-2009 oGibbs LLC Highway, oo Harahan, 5736 Citrus Boulevard, LA 70123 Phone: (504) 733-4336 o Construction 2305 St. Bernard Chalmette, LA 70043Phone (504) 2714141 \J~\L Height: 30'-0" fmw~.1ij

.. I.SCONCRETE SLABSTRUCTURE EXISTING DSUBSURFACE Light Industrial Legal' non-conforming use or DFOOTING MOBILE HOME WITHPILING PERMANENT CERTIFICATE FOUNDATION OCCUPANCY Neighborhood Heavy Industrial Commercial DADDITION IltflLiNG (WO()D) PIEROF BUilDING PERMIT ~eneral Commercial structure and/or lot will be: or a Lot: Contractor: ction, 0043 H SEWER Z-1-A and Z-1-B James Place! M-1 and M-2 Myrtle Grove ,

,*:p&Ni

,

_

,

"","

~~\sq\ (}) 0J (I) Date

"/g ,«

.

'"-

Department of Public Safety and Corrections of'State Fire Marshal Code Enforcement and Building Safety

C,"",

#ffice

~

't'(jJ\

(J> ,.:.;. ">t'\;~~~"l>r:>.

q"l>\~

<:: J'

)\

:# ~'~~ ~

'!jl/h.

STATE OF LOUISIANA

'".

A.l ••••••

el'l!

J.>. \

C)/ / t,) ,"'J

(0

!

~C-)~/

8181 Independence Boulevard 225-925-4920 Baton Rouge, Louisiana 70806 H "BUTCH" BROWNING FIRE MARSHAL

":~!=~:~~~:::'~>/ NEW RONNIE BABIN WINK DESIGN GROUP 1100 POYDRAS ST STE 1360 NEW ORLEANS, LA 70163-0000

CONSTRUCTION RE: P0364701 MURPHY OIL USA INC- LABORATORY BLDG 2305 E ST BERNARD HWY CHALMETTE, LA 70044 NFPA 101,2006 INDUSTRIAL

Dear Applicant This is to advise that we have reviewed the drawings and specifications for the subject proposed construction and have determined that they appear to satisfactorily comply with the adopted laws, codes, rules and regulations of The State Fire Marshal subject to the following requirements: 1.

Scope of Work: This 15000 sq. ft. facility is being reviewed as a high hazard industrial occupancy. The POR has indicated on the construction documents that this facility will have a sprinkler system and a fire alarm system. Both systems are required.

2.

REVIEW FOR COMPLIANCE WITH THE REQUIREMENTS OF THE LOUISIANA STATE UNIFORM CONSTRUCTION CODE, in accordance with Act 12 of the 2005 First Extraordinary Session of the Louisiana Legislature, IS NOT INCLUDED IN THIS REVIEW. Contact the building official of the applicable political subdivision to coordinate compliance with these requirements. LRS 40: 1730.23 mandates the enforcement of building codes by municipalities and parishes in Louisiana, as described by LRS 40: 1730.28. Note: In accordance with LRS 40: 1730.39.A, this office may establish contract agreements with municipalities and parishes in order to provide code enforcement on their behalf, as provided in LRS 40: 1730.24. Please visit our web site at http://www.dps.state.la.us/sfm/index.htm for a current list of jurisdictions requesting plan review by this office, a fee schedule, and a checklist of information required for review.

3.

This exception is intended to apply to the storage and industrial

portions of the building only.

After consultation with the Office of Rehabilitation Services, it has been determined that this office will not req uire the storage/industrial area(s) and associated toileUbath portions of this facility to comply with any of the ADA-AG or LSC requirements for individuals with disabilities, with the following stipulations:

Jul 31. 2009 P0364701 - PAGE I

1. No floor plan modifications are permitted. Office additions and spaces created which constitute a change in use will require the upgrading of all existing non-complying features to conform with the provisions for new construction. 2. Provide features of accessibility for the public and administrative

areas.

3. Visual alarm notification shall be provided if a fire alarm system is required

by Code.

4. If a complaint is received about discrimination in hiring of handicapped individuals or concerning handicapped accessibility to any part of the facility, then this office shall reserve the right to investigate the complaint and, if justified, shall reserve the right to require the facility or a portion thereof to be upgraded to comply with the accessibility requirements enforced by this office. 5. Please note that this document

4.

rJ

indicates specific compliance with state regulations

and does not

p\! r i IVIrLl~i:U

: t ep,rft\e[1Q ..t..w c;r~u.ljJl~t~ . ... V~ with federal law. • ' .., . 7"i:)"ElDrJii~'E lMPOSED" .. ~.-The Professional of Record, if applicable, otherwise the owner, shall furnish documentation addressing item(s) number 7,8,9,11,12,14,15,16 of this letter to this office within 21 days of the date on this l~ter,or this r,eview may be rescinded and found "Not In Compliance". Construction shall NOT be authorized for alLareas which may be affected by the item(s) listed in this paragraph. The state inspector shall verify that written documentation has been received and acknowledged by the Plan Review Section of this office prior to allowing occupancy.

NOTE: THE COMMENTS LISTED BELOW IDENTIFY APPARENT DEFICIENCIES DETECTED IN OUR REVIEW OFTHE DOCUMENTS SUBMITTED. . 5.

LRS 37:152.A Prior to construction, all drawings and specifications professional of record. Refer to sheet G002.

6.

NFPA 45:6.6.3.1 Plans for laboratory following: See section 45:6.6.3.1 (Compliance with 2-6wasn't

shall be stamped by the

emergencies shall be developed, which shall include the

indicated on the submitted

documents.)

7.

NFPA 30:6.3.2 The number of storage cabinets located in the chemical storage area shall not exceed 6. (Seven cabinets were indicated on the floor plan on sheet A201.) Provide documentation showing compliance.

8.

NFPA 30:6.4.2.3 Exterior walls shall be constructed to provide ready access for fire-fighting operations by means of access openings, windows, or lightweight noncombustible wall panels. A deficiency was detected at the northeast wall of the chemical storage room. Refer to sheet A201. Provide documentation showing compliance.

9.

NFPA 30:6.4.2.4* Where Class IA liquids or unstable liquids are dispensed or stored in containers larger than 1 L (1 gal), rooms shall be designed to direct flame, combustion gases and pressures resulting from a deflagration away from important buildings or occupied areas through the use of damage-limiting construction. The damage-limiting construction design shall be in accordance with recognized engineering standards and shall be acceptable to the authority having jurisdiction. (Compliance with this provision wasn't indicated on the submitted documents.) Provide documentation showing compliance.

10.

NFPA 30:6.9.1 Portable fire extinguishers

shall meet the following requirements: Jui31,2009 P0364701 - PAGE 2

(I) At least one portable fire extinguisher having a capability of not less than 40: B shall be located outside of, but not more than 3 m (10ft) from, the door opening into an inside liquid storage area. (2) At least one portable fire extinguisher having a capability of not less than 40:B shall be located within 9 m (30 ft) of any Class I or Class II liquid storage area that is located outside of an inside liquid storage area or liquid warehouse. (What type of fire extinguishers this facility will have wasn't indicated on the submitted documents.)

Additional fire extinguisher

requirements:

LAC 55: V:303.D Provide listed portable fire extinguishers Appendix E for distribution information.) a) NFP A 10.3.3.4 Classifications

in accordance

with NFP A 10. (Refer to

for fires:

Class A fires-fires in ordinary combustible materials, such as wood, cloth, paper, rubber and many plastics. .. Class B fiJ:'~s-fir~s inflammable liquids, combustible liquids, petroleumgrea'~e§, tars. oil~, QH-based paints, 'solvents, lacquers, alcohols and flammable gases. Class C fires-fires that involve energized electrical equipment. Class D fires-fires in combustible metals. Class K fires-fires in cooking appliances that involve combustible cooking media (vegetable or animal oils and fats.) (FOR USE ONLY AFTER ASSOCIATED FIRE SUPPRESSION SYSTEM HAS ACTIVATED AND'ELECTRICAL POWER TO THE COOKING APPLIANCES "HAS SHUNTED) b) NFPA 10:5 Travel distance to a fire extinguisher fires. Table 10:5.2.1 and 10:5.5 and 10:5.6.

shall not exceed 75 feet for Class A, C and D

c) NFPA 10:5 Travel distance to a fire extinguisher shall not exceed 30 feet for Class B fires (liquids). (May be increased to 50 feet for Light (low) Hazard fires with 10-8 extinguisher, for Ordinary (moderate) Hazard fires with 20-B extinguisher, and for Extra (high) Hazard firs with 80B extinguisher.) Table 10:5.3.1. For classification (Extra/High)

of Hazards see 10: 1.4.1 (Light/Low),

] 0: 1.4.2 (Ordinary/Moderate):

10: 1.4.3

d) NFPA 10:1.5.6 Fire extinguishers shall not be obstructed or obscured from view. e) NFPA 10:1.5.3 Fire extinguishers shall be conspicuously located where they will be readily accessible and immediately available in the event of fire. Preferably they shall be located along normal paths of travel, including exits from areas. f) NFPA 10: 1.5.1 0 Top of fire extinguisher, having a gross weight less than 40 lb, shall be not more than 5 feet above the floor; ifgross weight 40 Ibs or greater, 3-1/2 feet above the floor.

Jul 31,2009 P036470J -PAGE3

11.

NFP A 30:6.7.1.4 Where total quantity stored does not exceed 50 percent of the maximum per pile given in Table 6.7.1, the distances to a property line that is or can be built upon and to streets, alleys, or public ways shall be permitted to be reduced by 50 percent but not to less than 0.9 m (3 £1). (The distance from the outside storage area to the property line is less than the minimum allowed by 6.7.1.4. The separation distance shall not be less than 25 feet. Refer to sheet CI03.) Provide documentation showing compliance.

12.

NFPA 30:6.7.2 A maximum of 4160 L (1100 gal) of liquids in closed containers, intermediate bulk containers, and portable tanks shall be permitted to be stored adjacent to a building under the same management provided the following conditions apply: (1) The adjacent building wall has an exterior fire resistance rating of2 hours. (2) There are no openings to areas at grade or above grade that are within 3 m (10 £1) horizontally of the storage. (3) There are no openings directly above the storage. (4) There are no openings to areas below grade within 15m (50 ft) horizontally of the storage.

(The outside storage area doesn't comply with items 1 and 2 of section 6.7.2. The portion of the exterior wall that is directly behind the outside_stor.age area shall provide a fire resistance ratingof2 hr_ Also a wing wall 5' long shall be installed on each side of the outside storage area and shall terminate at the same height of the exterior wall to which it is connected. ) This will satisfy items 1 and 2 of section 6.7.2. Refer to sheets A201 and A401 for more in formation. Provide documentation showing compliance. 13.

101 :40.7.11.6 Doors serving high hazard contents ,areas with occupant loads in excess of five shall be permitted to be provided with a latch or lock only if the latch or lock is panic hardware or fire exit hardware complying with 7.2.1.7. (The type of hardware that will be used wasn't indicated on the submitted documents.)

14.

101 :40.7.11.1 * Where the contents are classified as high hazard, exits shall be provided and arranged to allow all occupants to escape from the building or structure or from the hazardous area thereof to the outside or to a place of safety with a travel distance of not more than 23 m (75 ft), measured as required in 7.6.1, unless otherwise provided in 7.11.2. (Lab area 117 doesn't comply with this provision.) Provide documentation showing compliance. Refer to sheet E201.

15.

NFPA 50A: 3-2.2 The minimum distance in feet from a hydrogen system of indicated capacity located either outdoors, in separate buildings, or in special rooms to any specified outdoor exposure shall be in accordance with Table 3-2.2. The distances in numbers 1,3 through 10, and 14 inclusive in Table 3-2.2 shall not apply where protective structures having a minimum fire resistance rating of 2 hours are located between the system and the exposure. (The hydrogen system shall be located a minimum of 25' from the exterior of the building.) Refer to sheet A20l.

16.

17.

NFPA 50A:4-1.t Where protective walls or roofs are provided, they shall be constructed of noncom bustible or limited-combustible materials. (The exterior wall adjacent to the hydrogen system is constructed with at least one com bustible material.) Refer to the second exterior wall ~ section located on sheet A403. Provide documentation showing compliance. LRS 40: 1731 (Effective 8/15/95) Provide handicapped accessibility in accordance with ADA-AG (Accessibility Guidelines - September 1994). This does not include a review for compliance with the Federal Americans with Disabilities (Civil Rights) Act of 1990. Compliance with state regulations and requirements does not guarantee compliance with federal law. "PARTICULAR APPARENT DEFICIENCIES" and paragraph references are noted as follo)"s: a) 4.9.4(2) Handrails at stairs shall extend at least 12" beyond the top riser and at least 12" plus the width of one tread beyond the bottom riser (See Figure 19). Refer to sheet A20I and A505; see stair nearest to office 116. P036470

Ju131.2009 I - PAGE 4

b) 4.22.5 Provide at least one accessible urinal with an elongated rim at 17" maximum above the floor. A deficiency was detected in the Men's restroom 114, refer to sheet 501. c) 4.23 Bathrooms, bathing facilities, and shower rooms shall comply with this section. (The seat and controls located in shower 113 don't comply with 4.23. reference fig. 57 of adaag. Refer also to sheet A501@ elevation 20.)

NOTE: THE FOLLOWING COMMENTS IDENTIFY ISSUES FOR INFORMATIONAL AND CAUTIONARY PURPOSES OR ISSUES THAT COULD NOT BE VERIFIED IN THE SUBMITTED DOCUMENTS. 18.

LRS 40:1730.45 and LAC 55:Y:2601 The documentation provided for the subject facility appears to comply with The Commercial Building Energy Conservation Code based on ANSI/ASHRAE/IESNA 90.1- 2004, or the International Energy Conservation Code, 2006 edition, as applicable.

19.

NFPA 45:5.1.6 All floor openings shallbe sealed or curbed to prevent liq uid leakage to lower floors.

20.

NFPA 45:5.L9*"Dpenings air

in fire-rated

floor/ceiling and wall assemblies foraire.:-handJing dudworkor

movement shall be protected in accordance with NFPA 90A, Standard Air-Conditioning and Ventilating Systems. 21.

NFPA 45:5.6.1 Electrical receptacles, liquid spills.

22.

NFPA 45:6.1.1 hazard, as follows:

All laboratory

for the Installation

of

switches, and controls shall be located so as not to be subject to

units shall be provided with fire protection

appropriate

to the fife

(1) Portable fire extinguishers (see Section 6.4) (2) Fire alarm systems (see Section 6.5) (3) Evacuation and emergency plans (see 6.6.3) 23.

NFPA 45:4.3.1 * A laboratory work area explosion of quantities or concentrations in 4.3.1(1) through 4.3.1(6), could result laboratory work area. (See Annex C.) (1) Storage of materials with a instability Copyright NFP A

shall be considered to contain an explosion hazard if an of materials, including but not limited to those listed in serious or fatal injuries to personnel within that hazard rating of 4 (see 8.2.5)

(2) Use or formation of materials with a instability hazard rating of 4 (see 8.2.5) (3)* Presence of highly exothermic reactions such as polymerizations, oxidations, nitrations, peroxidations, hydrogenations, or organo-metallic reactions (4) Use or formation of materials whose chemical structures indicate a potential hazard, but whose properties have not been established, such as triple bonds, epoxy radicals, nitro and nitroso compounds, and peroxides (5) Presence of high-pressure reactions (see Figure C.4.5) (6) Other explosion hazards as determined by a qualified person

(TAKE EXTREME 24.

NFPA 45:5.1.4 systems in

CAUTION FOR ITEM #2.) Table 5.1.1 shall pertain to laboratory

units protected by automatic sprinkler Jul 31, 2009 P0364701 - PAGE 5

accordance with NFPA 13, Standard for the Installation of Sprinkler Systems. Where water will create a serious fire or personnel hazard, a suitable non water automatic extinguishing system shall be permitted to be an acceptable substitute for sprinklers. 25.

NFPA 45:6 Requires that this facility be equipped with an automatic complete fire alarm system.

26.

101:40:3.2 Provide sprinkler

27.

NFPA 45:6.2.3* The discharge of an automatic fire extinguishing audible fire alarm system on the premises.

28.

NFPA ~5: 6.5.3 The fire alarm system, where provided, shall be designed so that all personnel endangered by the fire condition or a contingent condition shall be alerted. 6.5.4 The fire alarm system shall alert local emergency responders or the public fire department.

,29.

system "supervision"

in accordance

sprinkler system and a

with NFPA 101:9.7.2. system shall activate an

, NFPA 45:8.5.1 * Ducts from chemical fume hoods and from lo,calexhaustsystems entirely of noncombustible materials. Refer to exceptions .. Mechanical

ventilation shall be provided in accordance

shall be constructed

30.

NFPA 30:6.4.2.7

with this section.

31.

(Shall comply with the following:) NFPA 30:6.8.2* Automatic Sprinkler and Foam-Water Fire Protection Systems. Where automatic sprinklers or low-expansion foam-water sprinkler systems are used, the protection criteria of Table 6.8.2(a) through Table 6.8.2(k) shall be followed for the applicable liquid class, container type, and storage arrangement. Figure 6.8.2(a), Figure 6.8.2(b), and Figure 6.8.2(c) shall be used to specify protection criteria for liquid classes, container types, and storage arrangements not specifically covered in Table 6.8.2(a) through Table 6.8.2(k). All automatic sprinkler and foam-water fire protection systems shall be wet pipe, deluge, or preaction systems. If preaction systems are used, they shall be designed so that water or foam solution will immediately discharge from the sprinkler upon sprinkler actuation. Foam-water sprinkler systems that meet the design criteria specified in the water sprinkler tables in this section shall be acceptable.

32.

(This facility shall comply with the following:) NFPA 30:6.4.2.6 In inside storage rooms, electrical wiring and utilization equipment for Class I liquid storage shall be Class I, Division 2, and electrical wiring and utilization equipment in inside storage rooms used for the storage of Class II and Class III liquids shall be suitable for general purpose.

33.

NFPA 30:6.8.4 Water Supply. Water supplies for automatic sprinklers, other water-based protection systems, hose streams, and hydrants shall be capable of supplying the anticipated water flow demand for a minimum of 2 hours.

34.

N FPA 30:6.10 Precautions shall be taken to prevent the ignition of flammable vapors from sources of ignition. Refer to 6.10 for more information.

35.

Notes: Key NFP A standards used for this review: NFPA 452004 edition NFPA 302003 edition

Jul 3 L 2009 P0364701-PAGE6

36.

NFPA 45:8.2.2* Laboratory units and laboratory hoods in which chemicals are present shall be continuously ventilated under normal operating conditions. The ventilation system shall comply with all applicable sections of NFPA 45:8.

37.

NFPA 45: 11.1.5.2.2 Where the source cylinder is outside of the laboratory, gauge shall be installed at the point of use. to show outlet pressure.

38.

NFPA 45: 11.2.3* Manual shutoff valves shall be provided near each point of use.

39.

101 :7.2.1.5.9 Doors shall be capable of being opened with ONLY one releasing operation. A twostep release, such as a knob and an independent slide bolt, or an additional exit request button, is NOT acceptable.

40.

101:7.2.1.5 Locks on doors in means of egress shall not require the use of a key, special device or special knowledge to open in the direction of egress.

a station regulator and

Submit a "REQUEST FOR EXEMPTION" for special locking arrangements in accordance with Interpretive Mew.orandum 20G6-03 available on our website at http://www.dpsJouisiana.govLsfm/ under the PLAN-REVIEW / FORMS section. Also see Interpretive Memorandum 2006-04 for clarification regarding "magnetic lock releasing devices". NOTE: The "Life Safety and Property Protection Licensing Law" (LRS 40:1664 et seq.) requires locksmiths to be licensed. Contact the licensing section of this office at 225.925.7047 for guidance and assistance. 41.

101 :40.3.3 Interior rating of 0-450.

walls and ceilings shall have a flame spread of 0-200 and a smoke development

42.

BUILDING SERVICES a) 101 :40.5.1 Utilities shall comply with the provisions of Section 9.1. b) Compliance with the 2005 NFPA 70, National Electrical Code (NEC), is mandated by RS 40:1730.28.A(7). Contact the local Building Official of the applicable local political subdivision or a Louisiana State Uniform Construction Code Council registered third-party provider to verify plan review and inspection requirements of the proposed electrical work. c) HV AC system shall be constructed in accordance with 101 :9.2. d) 101 :9.2.1 Install smoke detectors to automatically stop the fan in HV AC duct systems over 2000 cfm in accordance with NFPA 90A:6.4.2(1). Where fire alarm system is required, duct detectors shall be connected to building alarm system. e) 101 :9.1.1 Install gas piping in accordance with NFPA 54. f) 101 :9.2.2 Gas-fired equipment (furnaces, space heaters, water heaters, etc.) shall be U.L. listed for its intended use and shall be installed and vented in accordance with NFP A 54. This type of equipment shall also comply with the requirements set forth in the interpretive memorandum 2008-1.

43.

LRS 40: I 731-(Effective 8/15/95) Provide handicapped accessibilityin accordance with ADA-AG (Accessibility Guidelines - September 1994). This does not include a review for compliance with the Federal Americans with Disabilities (Civil Rights) Act of 1990. Compliance with state regulations and requirements does not guarantee compliance with federal law. "CAUTIONARY/INFORMATIONAL" items and paragraph references are noted as follows: a) 4.15 Provide drinking fountain(s) in compliance with this section. b) 4.1.3(10)(a) In addition to the required accessible wheelchair drinking fountain, provide drinking accommodations for those who have difficulty bending and stooping. c) 4.19 Lavatories shall comply with the following: Jul 31, 2009 P0364701 - PAGE 7

1. 4.19.2 Lavatories shall be mounted with a clearance of at least 29" from the floor to the bottom of the apron. Knee and toe clearances shall comply with Fig. 31. 2.4.19.4

Hot water and drain pipes shall be insulated or covered.

3. 4.19.5 and 4.27.4 Faucets shall not require tight grasping, pinching, or twisting of the wrist to operate. 4.4.19.6 Mirrors shall be mounted with the bottom edge not more than 40" from the floor. d) 4.1.3(16) Permanent signage shall comply with 4.30. 1. Signage, where provided for permanent rooms and spaces shall provide; a. braille and raised lettering as per 4.30.4, b. letter/symbol to background color contrast as per 4.30.5, and c. a 60" height from floor to the centerline of the sign as per 4.30.6. 2. Other permanent signs which provide direction to or information about functional spaces of the building shall provide; a. letter character width to height proportion as per 4.30..2, . ...b. character height proportion based 0"" height ofsign from finish floor as per 4.30.3, and c. letter/symbol to background color contrast as per 4.30.5. 44.

N FPA 50A: 6-1 * Caution. Personnel shall be cautioned that hydrogen flames are practically invisible.

45.

NFPA 55:7.1.6.9 Compressed gas containers, cyiinders, and tanks shall not be exposed to corrosive chemicals or fumes that could damage containers, cylinders, tanks, or valve-protective caps.

46.

NFPA 55:7.3.1.6.1 Venting of gases shall be directed to an approved location.

47.

NOTE: Please enclose a copy of this letter with future submittals or other correspondence pertaining to this proj ecl.

Changes to construction

in the field which are not consistent

with the reviewed

documents

are not authorized

unless

reviewed by this office for compliance with Code. Modifications to reviewed plans must be submitted to this office by the Architect/Civil Engineer for review prior to final inspection. If an Architect or Civil Engineer is not required by RS 37: 155, revisions shall be submitted by the Owner. Submittals shall include plans, completed application, a minimum $55.00 review fee, and a copy ofthe most current plan review letter. Compliance Systems,

with code requirements

is determined

by separate

for fire protection shop drawing

systems,

submittal

such as Fire Alarm, Sprinkler

and is not included

This review shall in no way permit and/or authorize any omissions or deviations the adopted codes, rules and regulations in accordance with R.S. 40: 1574.1 (B). This review is valid for 180 days from the date of this letter. construction must commence within this time period. This office requires enclosed).

certification

of the completed

Construction

project in accordance

and Suppression

in this review. from the specific requirements

of

permits must be issued and/or

with the approved

documents

(certificate

Jul 31. 2009 P0364701 - PAGE 8

Occupancy of the project will not be permitted until we receive the completed certificate and a satisfactory inspection of the completed construction has been made by this office. To arrange for inspection of the project, please contact the District Office at the phone number below two (2) to three (3) weeks in advance. The plans stamped reviewed by this office must be available on job site at time of inspection. Certificate of completion must be provided to the inspecting Deputy for final inspection. Fire Department access and water supplies within the scope of work shall be acceptable to the local fire department. Submit to the State Fire Marshal inspector, a review letter from the local fire department, stating that the access and water supply as proposed are acceptable. In lieu of a review letter, where the local fire department does not provide a formal review, the local fire department may indicate review of the access and water supplies by stating such on the plans bearing the State Fire Marshal review stamp. REVIEWED BY: ANDREW ROSS PLAN REVIEW DEPUTY

CC: Murphy Oil Usa, Jne

St Bernard Parish Government St Bernard Fire Prevention* New Orleans District* 5042194600

Ju131,2009

P0364701 - PAGE 9

STATE OF LOUISIANA Department of Public Safety and Corrections Office of State Fire Marshal Code Enforcement and Building Safety 8181 Independence Boulevard Baton Rouge, Louisiana 70806 225-925-4920 H "BUTCH" BROWNING FIRE MARSHAL

INFORMATION NOT FOR RONNIE BABIN WINK DESIGN GROUP 1100 POYDRAS ST ", ST,E 1360 NEW ORLEANS,

LA 70163-0000

REQUEST PERMITTING RE: P0364701 MURPHY OIL USA INC- LABORATORY BLDG 2305.E ST BERNARD HWY CHALJ:'IETT_E,LA 70044 NFPA

101,2006

INDUSTRIAL

Dear Applicant: Additional information is required to perfonn submission of the following information:

1.

a proper review.

The project referenced

above is being held pending

RS 40:1574 and/or RS 40:1730.39.A Additional drawings and/or specifications are required: a) Provide the (complete) MSDS sheets for all chemicals and gases that will be stored and/or this facility as we discussed per our phone conversation on 7/9/2009.

used in

b) Also state what specific chemicals and gases will be used and/or stored in each individual room as per our conversation on 7/9/2009. Also provide the amounts of each chemical that will be located in each of these rooms. Be very specific. c) NOTE: Please enclose a copy of this letter with future submittals or other correspondence pertaining to this project.

Due to the lack of information, the referenced project has NOT been reviewed. Please direct the requested information to my attention. Processing will continue upon receipt of the infonnation requested above. Enclose a copy of this letter with future submittals and/or other correspondence pertaining to this project. This project will be returned as "NOT IN COMPLIANCE" if the requested infonnation is not received by this office within 21 days of the date of this letter, thereby requiring a RESUBMITT AL of the entire project along with a new completed appl ication and appropriate review fee.

P0364701

Ju19.2009 - PAGE 1

CONSTRUCTION IS NOT AUTHORIZED letter has been issued by this office.

until a satisfactory

review has been performed

and a formal review

REVIEWED BY: ANDREW ROSS PLAN REVIEW DEPUTY

cc; Murphy Oil Usa, Inc St Bernard Parish Government St Bernard Fire Prevention* New Orleans District* 5042194600

P036470I

Ju19,2009 - PAGE 2

Related Documents