Vijai Electricals Ltd. Projects Division

SCHEME: PROJECT: CUSTOMER: CONSULTANT: CONTRACTOR: LOA No. :

GUARANTEED TECHNICAL PARTICULARS OF LT SHACKLE INSULATOR (TYPE-2) S.NO 1

DESCRIPTION Manufacturer’s Name & Address

UNIT

PARTICULARS

2

Standard According to which Porcelain Insulators be Manufactured and Tested

IS:1445-1977 and REC Specification No.4/1993

3

Type of insulator offered

4

Dimensions

mm

5

Nominal System Voltage

KV

6

Highest System Voltage

KV

7

Minimum Mechanical Failing Load

KN

16

8 9 10

Dry Power Frequency 1 Min. Withstand Voltage (kV) Wet Power Frequency 1 Min. Withstand Voltage (kV) Dry Power Frequency Flashover Voltage

KV KV KV

10

11

Wet Power Frequency Flashover Voltage

KV

12

Power frequency Puncture withstand Voltage

KV

13

Min. Creepage Distance (min)

mm

14

Net Weight (Approx.)

Kg

15

Colour of Glaze

16

Tolerance as per specification(±)

17

Marking details

18

Packing details

Type-2

60

BROWN

a) Type of Packing b) No. of Insulators in each crate

Nos

c) No. of crates in each packing

Nos Kgs

19

d) Weight of each packing approx. Offered material fully meets customer specification

20

Drawing No.

Page 1

Yes

Tests: Type tests: 1 2 3 4 5 6 7

Visual examination Verification of dimensions Wet power-frequency voltage withstand test Temperature cycle test Mechanical failing load test Power-frequency puncture withstand test and Porosity test Acceptance tests:

1 2 3 5

Verification of dimensions Temperature cycle test Mechanical failing load test (subject to mutual agreement between the purchaser and the supplier) Porosity test DRAWING AS PER REC Specification No.4/1971

Page 2

Page 3

6.5

Page 4

Vijai Electricals Ltd. Projects Division

SCHEME: PROJECT: CUSTOMER: CONSULTANT: CONTRACTOR: LOA No. :

GUARANTEED TECHNICAL PARTICULARS OF LT PIN INSULATOR S.NO 1

DESCRIPTION Manufacturer’s Name & Address

UNIT

2

Standard According to which Porcelain Insulators be Manufactured and Tested

3

Type of insulator offered

4

Over all Dimensions (mm)

PARTICULARS IS:1445-1977 and REC Specification No.4/1993

a) Height

mm

b) Maximum Diameter

mm

c) Conductor groove in mm

mm

5

Nominal System Voltage

KV

6

Highest System Voltage

KV

7

Minimum Mechanical Failing Load

KN

3.5

8 9 10

Dry Power Frequency 1 Min. Withstand Voltage (kV) Wet Power Frequency 1 Min. Withstand Voltage (kV) Dry Power Frequency Flashover Voltage

KV KV KV

10

11

Wet Power Frequency Flashover Voltage

KV

12

Power frequency Puncture withstand Voltage

KV

13

Min. Creepage Distance (min)

mm

14

Thimble: a) Type of material b) Type c) Type of threads

15

Net Weight (Approx.)

Kg

Page 5

60

16

Colour of Glaze

BROWN

17

Tolerance as per specification(±)

18

Marking details

19

Packing details a) Type of Packing b) No. of Insulators in each crate

Nos

c) No. of crates in each packing

Nos

d) Weight of each packing approx. Offered material fully meets customer specification

Kgs

20 21

Drawing No.

Tests: Type tests: 1 2 3 4 5 6 7

Visual examination Verification of dimensions Wet power-frequency voltage withstand test Temperature cycle test Mechanical failing load test Power-frequency puncture withstand test and Porosity test Acceptance tests:

1 2 3 5

Verification of dimensions Temperature cycle test Mechanical failing load test (subject to mutual agreement between the purchaser and the supplier) Porosity test

Page 6

Yes

DRAWING AS PER REC Specification No.4/1971

Page 7

Page 8

Page 9

6.5

Page 10

Vijai Electricals Ltd. Projects Division

SCHEME: PROJECT: CUSTOMER: CONSULTANT: CONTRACTOR: LOA No. :

GUARANTEED TECHNICAL PARTICULARS OF LT GUY INSULATOR S.NO 1

DESCRIPTION Manufacturer’s Name & Address

UNIT

2

Standard According to which Porcelain Insulators be Manufactured and Tested

3

Type of insulator offered

PARTICULARS IS: 5300 – 1969

Strain

Designation

A

4

Over all Dimensions

mm

90X65

5

Hole diameter

mm

16

6

Nominal System Voltage

KV

7

Highest System Voltage

KV

8

Minimum Mechanical Failing Load

KN

44

9

Dry Power Frequency 1 Min. Withstand Voltage

KV

18

10

Wet Power Frequency 1 Min. Withstand Voltage

KV

8

11

Min. Creepage Distance (min)

mm

41

12

Net Weight (Approx.)

Kg

13

Colour of Glaze

14

Tolerance as per specification(±)

15

Marking details

16

Packing details

BROWN

a) Type of Packing b) No. of Insulators in each crate

Nos

c) No. of crates in each packing

Nos

d) Weight of each packing approx. Offered material fully meets customer specification

Kgs

17 18

Drawing No.

Page 11

Yes

Tests: Type tests: 1

Visual examination

2

Verification of dimensions

3

Wet power-frequency voltage withstand test

4

Temperature cycle test

5

Mechanical failing load test

6

Porosity test REFERENCE DRAWING:

Page 12

Page 13

6.5

Page 14

Vijai Electricals Ltd. Projects Division

SCHEME: PROJECT: CUSTOMER: CONSULTANT: CONTRACTOR: LOA No. :

GUARANTEED TECHNICAL PARTICULARS OF HT GUY INSULATOR S.NO 1

DESCRIPTION Manufacturer’s Name & Address

UNIT

2

Standard According to which Porcelain Insulators be Manufactured and Tested

3

Type of insulator offered

PARTICULARS IS: 5300 – 1969

Strain

Designation

C

4

Over all Dimensions

mm

140X85

5

Hole diameter

mm

25

6

Nominal System Voltage

KV

11

7

Highest System Voltage

KV

12

8

Minimum Mechanical Failing Load

KN

88

9

Dry Power Frequency 1 Min. Withstand Voltage

KV

27

10

Wet Power Frequency 1 Min. Withstand Voltage

KV

13

11

Min. Creepage Distance (min)

mm

57

12

Net Weight (Approx.)

Kg

13

Colour of Glaze

14

Tolerance as per specification(±)

15

Marking details

16

Packing details

BROWN

a) Type of Packing b) No. of Insulators in each crate

Nos

c) No. of crates in each packing

Nos

d) Weight of each packing approx. Offered material fully meets customer specification

Kgs

17 18

Drawing No.

Page 15

Yes

Tests: Type tests: 1

Visual examination

2

Verification of dimensions

3

Wet power-frequency voltage withstand test

4

Temperature cycle test

5

Mechanical failing load test

6

Porosity test REFERENCE DRAWING:

Page 16

Page 17

6.5

Page 18

Related Documents

Lt Insulators Gtp
April 2020 6
Insulators
December 2019 13
Gtp 19_application_form.docx
December 2019 19
Porcelain Insulators
October 2019 11
Lt
April 2020 32
Lt
November 2019 90