INSPECTION AND TESTING PLAN MOTOR CONTROL CENTER (MCC)

Project Location Owner / User Contractor Third Party

: : : : :

LEGEND RESPONSIBILITY :

LEGEND ACTIFITY :

F : Fabricator / Contractor /

H - Mandatory Hold Point

Installator

V - Verity documents

C : Client

R - Review documents

TP : Third Party (PJIT)

W - Witness Activity

M : Migas

DESCRIPTION

PROCESS DESCRIPTION INSPECTION ACTIVITIES

Date : Rev :

SURVEILLANCE INSPECTION F

C

TP

M

PRE INSPECTION MEETING

Inform the client regarding the Certification Agencies scope of work

H

H

---

DESIGN APPRAISAL

-

Drawing Calculations General Specifications

R R R

R R R

-------

FACTORY ACCEPTANCE TEST (FAT)

-

Identification of Component, Material and Purchasing order Visual Inspection Wiring & Continuity Test MCC Contruction Check Small dry-type Distribution Transformer For Controls Primary Injection Voltage Test Electrical & Mechanical interlock test Fuction Test Check Ground Bus Metering calibration Automatic Transfer switch test (if Required) Insulation Resistance Test Relay Test

H W W W W W W W W W W W W

V W W W W W W W W W W W W

V W W W W W W W W W W W W

INSPECTION AND TESTING PLAN MOTOR CONTROL CENTER (MCC)

Project Location Owner / User Contractor Third Party

: : : : :

LEGEND ACTIFITY :

F : Fabricator / Contractor /

H - Mandatory Hold Point

Installator

V - Verity documents

C : Client

R - Review documents

TP : Third Party (PJIT)

W - Witness Activity

M : Migas

DESCRIPTION

PRE-COMMISSIONING TEST (ON-SITE)

LEGEND RESPONSIBILITY :

PROCESS DESCRIPTION INSPECTION ACTIVITIES

Date : Rev :

SURVEILLANCE INSPECTION F

C

TP

M

-

DC Hi pot test Current & Potential Transformer Test Current Transducer test

W W W

W W W

W W W

-

Verify nameplate of equipment with data sheet Check Equipment Layout based on classification area Check Instruction's Book / Manual Guidance Contact resistance bus Open the cell doors and with the design document, check each cell to ensure the correct component are installed Earthing measurement Check each drawer motor stater or feeder breaker assembly properly Check mechanism door locking and defeat function prpperly Inspect for the tighten Check cleaning on exterior and interior the MCC Check the cable feeder termination Check the power cables are properly color coded MCC wiring test Function test Relay test (as required)

H W R W W

V W R W W

-----------

W W W W W W W W

W W W W W W W W

-----------------

-

INSPECTION AND TESTING PLAN MOTOR CONTROL CENTER (MCC)

Project Location Owner / User Contractor Third Party

: : : : :

LEGEND ACTIFITY :

F : Fabricator / Contractor /

H - Mandatory Hold Point

Installator

V - Verity documents

C : Client

R - Review documents

TP : Third Party (PJIT)

W - Witness Activity

M : Migas

DESCRIPTION

COMMISSIONING TEST , FINAL INSPECTION , TAKING OF CERTIFICATE (TOC)

LEGEND RESPONSIBILITY :

Rev :

PROCESS DESCRIPTION INSPECTION ACTIVITIES

-

SURVEILLANCE INSPECTION F

Insulation Resistance Test DC Hi pot Test Performance Test

3rd Party Inspection Company

(....................)

Date :

C

TP

M

W W W

W W W

----W

Owner / User

MIGAS

(.......................)

(....................)

MIGAS