ICT444 Assignment #5 Questions: 1. Under the CSA designations for documents, what is the equivalent CSA number for ANSI/TIA/EIA-568 standard called? a. CSA T530 b. CSA T525 c. CSA T529 d. CSA T527 2. The _____________ cabling provides interconnection between telecommunications rooms, equipment rooms and entrance facilities. a. copper b. protected c. horizontal d. backbone 3. The maximum “Main to Horizontal Cross-Connect” distance using multimode fiber is _______________ meters. a. 800 b. 3000 c. 2000 d. All the other answers are incorrect 4. Another name for MC is a. Floor Distributor b. Campus Distributor c. Building Distributor d. All the above are correct 5. Under the CSA designations for documents, what is the equivalent CSA number for ANSI/TIA/EIA-569 standard called? a. CSA T530 b. CSA T525 c. CSA T529 d. CSA T527 6. Horizontal cabling will be installed in a _____________ topology a. bus
b. star c. ring d. framed 7. If you needed a standard for “Grounding and Bonding” recommendations, which of the following standard would you refer to? a. TSB75 b. T527 c. 568B.2 d. ANSI/EIA/TIA-606 8. The cabling standard document indicates that labeling should be in accordance with TIA/EIA-_________. a. 568 b. 606 c. 569 d. 607 9. Under the ANSI/TIA/EIA designations for documents, what is the number of the “Commercial Building Standard for Telecommunications Pathways and Spaces” called? a. TIA/EIA-568 b. TIA/EIA-569 c. TIA/EIA-606 d. TIA/EIA-607 10. Each individual work area shall be serviced with a minimum of _______ telecommunications outlets (TO). a. 2 b. 4 c. 3 d. 6 11. Under the CSA designations for documents, what is the equivalent CSA number for ANSI/TIA/EIA-607 standard called? a. CSA T530 b. CSA T525 c. CSA T529 d. CSA T527 12. A structured wiring system based on CAT 5e cable, can handle top data rate
a. of about 100Mbps. b. greater than 10Gbps. c. between 10 and 50 Kbps. d. better than fiber optics. 13. When a MUTOA is used the horizontal cable maximum length will be affected, based on the length of the work area cord. The maximum length of the work area cord is _______ meters. a. 13 b. 9 c. 22 d. 17 14. Another name for HC is a. Floor Distributor b. Campus Distributor c. Building Distributor d. All the above are correct 15. The maximum channel distance is _______ meters a. 75 b. 90 c. 100 d. 110 16. Under the ANSI/TIA/EIA designations for documents, what is the number of the “Administration Standard for the Telecommunications Infrastructure of Commercial Buildings” called? a. TIA/EIA-568 b. TIA/EIA-569 c. TIA/EIA-606 d. TIA/EIA-607 17. Under the 568 standard, the “Jumper/Patch Cord Maximum Length Limitations” for cable in the telecom room is __________ meters. a. 3 b. 6 c. 10 d. 20
18. Which of the following establishes performance and technical criteria for various cabling system configurations? a. TIA/EIA-568 b. TIA/EIA-569 c. TIA/EIA-606 d. TIA/EIA-607 19. The maximum link distance is _______ meters a. 75 b. 90 c. 100 d. 110 20. The HC is the a. top component of the structured wiring hierarchy b. main backbone connector. c. TR closest to the workstations. d. MUTO furthest from the BD. 21. Under the CSA designations for documents, what is the equivalent CSA number for ANSI/TIA/EIA-606 standard called? a. CSA T530 b. CSA T525 c. CSA T528 d. CSA T568 22. Under the 568 standard, what is the minimum bend radius for backbone cable? a. 2 x diameter b. 4 x diameter c. 8 x diameter d. 10 x diameter 23. Under the ANSI/TIA/EIA designations for documents, what is the number of the “Commercial Buildings Telecommunications Cabling Standard” called? a. TIA/EIA-568 b. TIA/EIA-569 c. TIA/EIA-606 d. TIA/EIA-607
24. Delay Skew: The difference between the _____________________ of any two pairs within the same cable sheath. a. NEXT b. permanent link c. propagation delay d. channel link 25. Which of the following generally refers only to fiber optic cable? a. T527 b. TSB-67 c. 11801 d. 568B.3 26. Under the 568 standard, the “Jumper/Patch Cord Maximum Length Limitations” for cable in the work area is __________ meters. a. 3 b. 6 c. 10 d. 20 27. Which of the following enables the planning and installation of a structured cabling system for commercial buildings? a. TIA/EIA-568 b. TIA/EIA-569 c. TIA/EIA-606 d. TIA/EIA-607 28. Wiring a cable with T568A termination at the workstation end and T568B termination at the patch panel end will result in what? a. bad pair b. cross-over pair c. twisted pair d. router pair 29. Under the 568 standard, what is the minimum bend radius for horizontal UTP (4pair) cable? a. 2 x diameter b. 4 x diameter c. 8 x diameter d. 10 x diameter
30. To insure ________, the cable network is built to a standard. a. administration b. cost reduction c. performance d. reliability 31. Under the 568 standard, when spicing (mechanical or fusion) a fiber optic cable the maximum attenuation must be less than _________ dBs. a. 1.5 b. 0.75 c. 0.3 d. 6 32. Which management organization was responsible for the 568 standard? a. ISO b. ANSI c. CSA d. TelNet 33. Using a 568SC connector, the beige colored connector indicated ________. a. keyed duplex b. single mode connector/coupling c. multimode connector/coupling d. None of the above are correct 34. Under the 568 standard, which section covers “Optical Fiber Cabling Components”? a. B.1 b. B.2 c. B.2-1 d. B.3 35. Patch cords can be connected directly from a MUTO to work area equipment. (T/ F) a. TRUE b. FALSE 36. Under the 568 standard, the fiber connection (mated pair) a fiber optic cable the maximum insertion loss must be less than _________ dBs.
a. 1.5 b. 0.75 c. 3 d. 6 37. A structured wiring/cabling project is designed using a/an _________________. a. engineering protractor b. set of AutoCad drawings c. CEC addendum d. approved standard 38. Under the 568 standard, what is the minimum bend radius for horizontal ScTP cable? a. 2 x diameter b. 4 x diameter c. 8 x diameter d. 10 x diameter Under the 568 standard, when spicing (mechanical or fusion) a fiber optic single-mode cable the minimum return loss should be _________ dBs.
39.
a. 10 b. 20 c. 26 d. All the above values are incorrect 40. Using a 568SC connector, the blue colored connector indicated ________. a. keyed duplex b. single-mode connector/coupling c. multimode connector/coupling d. None of the above are correct
ICT444 Assignment #6 Questions: 1. Under 568 there are two ways of wiring the workstation jacks and patch panel jacks. Which one is popular in Alberta? a. T568-B b. TSB-75 c. T568-A
d. The thin technique 2. Plenium cables are normally rated as a. FT-6. b. FT-4 or less. c. T568-B. d. hard to work with. 3. The “Rule of thumb” for TOTAL horizontal cabling or channel is ______ meters. a. 800 b. 90 c. 305 d. 100 4. UTP cable is less sensitive to external electromagnetic interference than other media. (T/F) a. TRUE b. FALSE 5. The “Characteristic Impedance” of most Canadian UTP cable is typically about _____ ohms. a. 100 b. 92 c. 50 d. 150 6. What is the term that indicates the difference in propagation delay between the fastest and slowest pair within the same cable sheath, usually expressed in nanoseconds (ns)? a. color twist b. impedance c. NEXT d. delay skew 7. This is referred to as a figure of loss; What is it? a. propagation b. impedance c. attenuation d. “Cable Skew”
8. Which of the following is the minimum level of cable for voice communications? a. CAT 2 b. CAT 4 c. CAT 3 d. CAT 5 9. Energy coupled from one conductor to another is a good thing for data communications. (T/F) a. TRUE b. FALSE 10. Of all the characteristics of LAN cable operation, _________ has the greatest effect on network performance. a. cost b. CAT 5 c. redundancy d. crosstalk 11. A multi-tenant commercial building has a life expectancy of at least _____ years. a. 30 b. 40 c. 50 d. 60 12. Using the “Commercial Building Standard for Telecommunications Pathways and Spaces” document, a local telephone carrier is typically required to terminate cabling within _____ ft of building penetration and to provide primary voltage protection. a. 20 b. 30 c. 40 d. 50 13. Using the “Administration Standard for Telecommunications Infrastructure of Commercial Buildings” document, the typical administration system includes records, reports, drawings, and __________. a. layouts b. linkages c. work orders d. None of the other answers are correct
14. Using the “Commercial Building Standard for Telecommunications Pathways and Spaces” document, a “Rule of Thumb”: Allow ____ sq.ft. of plywood for each _____ sq. ft. of floor space. a. 1, 200 b. 1, 300 c. 2, 200 d. 2, 300 15. Using the “ANSI/TIA/EIA-606” document, the “Demarcation Point Label Color” is a. Brown b. White c. Orange d. Green 16. In Canada, the “Commercial Building Standard for Telecommunications Pathways and Spaces” document is called: a. CSA T525 b. CSA T530 c. CEC 232c d. CSA C527 17. Using the “Commercial Building Standard for Telecommunications Pathways and Spaces” document, more than one telecom room per floor is required if distance to a work area exceeds ______ feet. a. 400 b. 300 c. 200 d. 500 18. Using the “Administration Standard for Telecommunications Infrastructure of Commercial Buildings” document, administrative recordkeeping plays an increasing necessary role in the flexibility and _____________ of frequent moves, adds and changes. a. framing b. management c. location d. NONE of the above fit this answer!
19. Using the “CSA T525” document, what would you be wiring? a. b. c. d.
The NAIT HP Center Light Commercial Building West Edmonton Mall You would be doing ALL the above!
20. Using the “Commercial Building Standard for Telecommunications Pathways and Spaces” document, what is the recommended room sizing for each 10,000 square-foot area served? a. 10 ft x 11 ft b. 10 ft x 15 ft c. 15 ft x 20 ft d. There is NO recommended room sizing 21. Using the “ANSI/TIA/EIA-568” document, what is the maximum channel distance in feet? a. 90 b. 100 c. 305 d. 1000 22. An “Alphanumeric Identification Code” of Fxxx, would refer to (What?) a. FD b. firestops c. frames or racks d. fiber 23. Using the “Administration Standard for Telecommunications Infrastructure of Commercial Buildings” document, Network Connections Label Color is a. Blue b. Brown c. Green d. White 24. Using the “Commercial Building Standard for Telecommunications Pathways and Spaces” document, what is the minimum distance between any fluorescent lighting fixture and low voltage communication cables? a. 3-inches b. 7-inches c. 5-inches d. 4-inches
25. In Canada, the “Residential and Light Commercial Telecommunications Wiring Standard” document is called: a. CSA 526 b. CSA T528 c. CSA T525 d. There is NO such thing in Canada! 26. Using the “Commercial Building Standard for Telecommunications Pathways and Spaces” document, Network Connections Label Color is a. Blue b. Brown c. Green d. This is NOT the CORRECT document to go to! 27. Using the “ANSI/TIA/EIA-606” document in the USA, then which document would you refer to as a French version in Canada? a. CSA T527 b. CSA T528 c. CSA T568-B.3 d. There is NO French version in Canada! 28. Using the “ANSI/TIA/EIA-569” document, a “Rule of Thumb”: Provide ____ sq. ft. of equipment room floor space for every ______ sq. ft. of user workstation area. a. 0.50, 100 b. 0.75, 100 c. 1, 200 d. None of the other answers are correct 29. What do we call the assembly that helps to reduce cabling moves, adds and changes in a modular furniture settings. a. Consolidation Point b. MUTO c. Pull-Box d. Hand-Hold (HH)
30. Using the “Commercial Building Standard for Telecommunications Pathways and Spaces” document, in buildings larger than _________ usable sq. ft., a locked, dedicated, enclosed room is recommended. a. 20,000 b. 30,000 c. 40,000 d. 70,000 31. Using the “ANSI/TIA/EIA-569” document, in “Intrabuilding Backbone Pathways”, fills should NOT exceed _____ for any run greater than two cables. a. 20% b. 30% c. 40% d. 50% 32. What is the term used to re-establish the integrity of fire-rated structures when these barriers have been penetrated by cable? a. fire-safe b. fire-cement c. plenum d. firestops 33. Using the “ANSI/TIA/EIA-606” document, a BD cross-connect “Alphanumeric Identification Code” would be: a. BCDxxx b. MCxxx c. ICxxx d. There is NO such thing as a BD! 34. Using the “ANSI/TIA/EIA-568” document, what is the maximum link distance in meters? a. 90 b. 100 c. 305 d. 1000 35. What is the ISO document number that the 568 came from? a. T525 b. IEEE 802.3 c. 11801 d. There is NO ISO document
36. Using the “ANSI/TIA/EIA-569” document, more than one telecom room per floor is required if floor area served exceeds _______ square feet. a. 5,000 b. 10,000 c. 15,000 d. 20,000 37. What do we call the document, “Optical Fiber Cabling Components Standard”? a. TIA/EIA-568-B.1 b. TIA/EIA-568-B.3 c. TIA/EIA-568-B.FO d. TIA/EIA-568-B.2-ad10 38. Using the “ANSI/TIA/EIA-606” document, what is the “Identification Format” code for a “Work Area”? a. WSxxx b. WAxxx c. TCxxx d. Jxxx 39. What is the most common choice of horizontal pathways? a. Underfloor Ducts b. J-hooks c. Multi-channel Raceway d. Trenchduct 40. Using the “ANSI/TIA/EIA-569” document, a “Rule of Thumb”: Typically, size horizontal pathways by providing _____ sq. in. of cross-section area for every _____ sq. ft. of workspace area being served. a. 1, 100 b. 1, 200 c. 2, 150 d. 1, 1100
ICT444 Assignment #7 Questions: 1. Looking at the picture (below), what is the normal maximum length of the “A” label?
a. 33 feet b. 6 meters c. 3 meters d. 25 feet
2. The picture (below) shows what type of wiring configuration? a. The USA way of wiring a RJ45 plug b. T568B c. NOT a real configuration d. T568A
3. In the picture (below), what type of test would this be? a. No such test is done b. 568 Link Test c. 11801 Link Test d. Channel Test
4. From using a test meter in the LAB, a CAT 5 cable does NOT require a PSNEXT test (T/F) a. TRUE b. FALSE 5. What standard would you refer to if you were going to wire the device shown in the picture (below)? a. CSA T527 b. TSB-67 c. ANSI/EIA/TIA 606 d. ISO/IEC 11801
6. From the picture (below), what type of wiring mistake is column 3? a. Reversed Pair b. Split Pair c. Matched Pair d. Crossed Pair e. There is NO mistake on this column!
7. The arrow in the picture (below) point to what type of block? a. BIX b. 110 c. RJ-45 d. Type 66
8. What is the max link distance for a cable system wired as EIA/TIA 568? a. About 325 feet b. About 100 meters c. About 292 feet d. About 95 meters 9. The picture (below) is a good wiring job (T/F) a. TRUE b. FALSE
10. Always use an industry accepted labeling format such as the one specified in a. CSA T530 b. TSB-75 c. ANSI/TIA/EIA-606 d. CSA T527 11. Using the “CSA T527 ” document, which of the following is not a major component of this standard? a. TBB b. TGB c. TGMB d. TBBIBC 12. Looking at the picture (below), what is the normal maximum length of the “E” label? a. 33 feet b. 6 meters c. 3 meters d. 25 feet
13. The picture (below) is a good wiring job (T/F) a. TRUE b. FALSE
14. Using the “Commercial Building Grounding and Bonding Requirements for Telecommunications” document, what is the minimum bonding conductor size? a. 6 AWG b. 8 AWG c. 10 AWG d. None of the other answers are correct 15. From the administration standard, what is the alphanumeric ID code for a splice called? a. SLxxx b. SExxx
c. Sxxx d. SPxxx 16. What do we call the main grounding busbar for telecommunications? a. TBB b. TMGB c. Main CO ground d. TBBIBC 17. Using the “ANSI/EIA/TIA 607” document, must be marked appropriately by a distinctive color. What is the color? a. blue b. green c. orange d. brown 18. Under the 568 standard, what is the maximum number of hierarchical levels of backbone cross-connects allowed? a. 1 b. 2 c. 3 d. 4 19. Under the 568 standard, one MUTOA can serve a maximum of ____ work areas. a. 9 b. 12 c. 15 d. As many as you want! 20. Using the “CSA T527 ” document, A _______ is not intended to serve as the only conductor providing a ground fault current return path. a. TBB b. TBBIBC c. rack d. TGBM 21. From the picture (below), what type of wiring mistake is column 2? a. Reversed Pair
b. Split Pair c. Matched Pair d. Crossed Pair e. There is NO mistake on this column!
22. The design aspects of the equipment room are found in the TIA/EIA-569-A standard. Is this a TRUE or FALSE statement? a. TRUE b. FALSE 23. Using the “Commercial Building Grounding and Bonding Requirements for Telecommunications” document, typically, there should be _______ TMGB per building. a. 2 b. 5 c. 1 d. 0 24. What is the name of the device in the picture below called? a. cable edge protector b. receptacle box c. caddy d. NONE of the answers above are correct!
25. What do we call the bonding backbone for telecommunications rooms? a. TBB b. TMGB c. Main CO ground d. TBBIBC 26. Using the “CSA T527 ” document, a water pipes shall not be used as a TBB. Is this statement TRUE or FALSE? a. TRUE b. FALSE 27. Under the Canadian standard for cabling backbone, the maximum UTP distance is 800 meters. Is this statement TRUE or FALSE? a. TRUE b. FALSE 28. Under the 568 standard, main and intermediate cross-connect jumpers or patch cord lengths should NOT exceed ______ meters. a. 10 b. 20 c. 60 d. 90 29. Using the “ANSI/EIA/TIA 607” document, TBB conductors should be installed without __________, where practicable. a. orange cables b. splices
c. bonding d. NONE of the other answers are correct! 30. Under the 568 standard, are transition points from round to flat under carpet cable allowed? a. YES b. NO 31. Under the 568 standard, each TO in each work area should have a minimum of _____ information outlet ports. a. 1 b. 4 c. 6 d. 2
32. From the picture (below), what type of wiring mistake is column 4? a. Reversed Pair b. Split Pair c. There is NO mistake on this column! d. Crossed Pair
33. On a 8-position modular jack, two pairs are swapped between the T568A wiring and the T568B wiring terminations. What are the colors of those swapped pairs? a. Wh/Bl and Bl with Wh/Or and Or
b. Wh/Gr and Gr with Wh/Bl and Bl c. Wh/Br and Br with Wh/Or and Or d. Wh/Gr and Gr with Wh/Or and Or 34. The picture (below) is a bad wiring job (T/F) a. TRUE b. FALSE
35. Using the “ANSI/EIA/TIA 607” document, the location of the TMGB primary protectors shall be separated by a minimum of ___________ from any DC power, switchboard or high frequency cables even when these cable are contained in metallic or EMT conduit a. 100 mm b. 200 mm c. 300 mm d. 500 mm 36. On an 8-position modular jack, two pairs are swapped between the T568A wiring and the T568B wiring terminations. What are the cable pairs that are swapped? a. pairs 1 and 4 b. pairs 3 and 2 c. pairs 2 and 4 d. pairs 1 and 2
37. From the picture (below), what type of wiring mistake is column 1? a. Reversed Pair b. Split Pair c. There is NO mistake on this column! d. Crossed Pair
38. Are bundled and hybrid cables allowed for use in horizontal cabling (HINT: check TIA/EIA-568-B.2 specification) a. YES b. NO 39. The picture (below) is a bad wiring job (T/F) a. TRUE b. FALSE
40. Using the “CSA T527” document, metallic cable shield can be used as a TBB in new installations. Is this statement TRUE or FALSE?
a. TRUE b. FALSE
Assignment 5 1 c 2 d 3 c 4 b 5 a 6 b 7 b 8 b 9 b 10 a Assignement 6 1 c 2 a 3 d 4 b 5 a 6 d 7 c 8 c 9 b 10 d Assignment 7 1 c 2 d 3 d 4 a 5 a 6 d 7 8 9 10
c b c
11 12 13 14 15 16 17 18 19 20
d a c a c c b a b c
21 22 23 24 25 26 27 28 29 30
c d a c d a a b b d
31 32 33 34 35 36 37 38 39 40
c a c d a b d c c b
11 12 13 14 15 16 17 18 19 20
c d c a c b b b b a
21 22 23 24 25 26 27 28 29 30
c d c c c d b b b a
31 32 33 34 35 36 37 38 39 40
c d c a c b b b b a
11 12 13 14 15 16
c b b a c b not in test b b a
21 22 23 24 25 26
a a c c a a
31 32 33 34 35 36
d b d b c b
b b
37 38 39 40
c a a b
17 18 19 20
27 28 29 30