ELEAD ASSOCIATES AIR CONDITIONING HEAT LOAD CALCULATION PROJECT DESCRIPTION:

PROPOSED A&A BODY CONTOURS (NAIL SPA AND BEAUTY SERVICES CONCESSION) AT BASEMENT 2 NORTH, TERMINAL 3, SINGAPORE CHANGI AIRPORT

PROJECT NO.:

A 106

PREPARED BY:

ZAW MOE

SENSIBLE HEAT LOAD ITEMS

EXPOSED GLASS

DIRECTIONS

FACTORS (KWim2)

AREA (m2)

WITH BLINDS

COOLING LOAD (KVV)

N, NW

-

0.3

-

S,E,NE,SE

-

0.23

-

SW

-

0.3

-

W

-

0.4

-

SHADED

-

MEDIUM HEAVY CONSTRUCTI CONSTRUCTION ON

LIGHT CONSTRUCTION

EXPOSED WALLS

ROOF PARTITION

-

0.05

N, NW

-

7 x 10-3

6.42 x 10-3

4.08 x 10-3

-

S,E,NE,SE

-

6.42 x 10-3

5.25 x 10-3

5.25 x 10-3

-

SW

-

8.75 x 10

7 x 10

6.42 x 10

-3

-

W

-

8.75 x 10-3

6.42 x 10-3

-

SHADED WITH CEILING WITHOUT CEILING GLASS

-

-

1.75 x 10-3

WALL

-

1.167 x 10-

-3

7.59 x 10-3 2.334x10-3

-

9.336 x 10

-

2.51 x 10

-3

-3

PERSON

LIGHTS

W/m

ELECT. APPLIANCES

KW

2

-

5.84 x 10

-3

14.0 x 10

-3

2.92 x 10

-3

-

5.84 x 10

-3

-

3

INTERNAL SENSIBLE HEAT LOAD (DINING AREA) NO. OF DESCRIPTION UNIT UNIT PEOPLE

-3

FACTORS

60

0.06

3.6

128.90

30

3.87

6

0.5

3.00

OUTDOOR AIR

20CMH/PERSON

2.05

(1) TOTAL ROOM SENSIBLE HEAT :

12.52

TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C)

5,364.43

TOTAL DESIGN CMH:

5,750.00

CAAS PROVIDE CMH

3,030.00

NEW ADDITIONAL AIR CON (DINING AREA)

2,720.00

INTERNAL SENSIBLE HEAT LOAD (BODY MASSAGE 1) NO. OF DESCRIPTION UNIT UNIT

FACTORS

PEOPLE

PERSON

2

0.06

0.12

LIGHTS

W/m 2

7.43

30

0.22

ELECT. APPLIANCES

W/m

7.43

27

0.20

2

OUTDOOR AIR

20CMH/PERSON

0.07

(1) TOTAL ROOM SENSIBLE HEAT :

0.61

TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C)

262.22

DESIGN CMH:

270

INTERNAL SENSIBLE HEAT LOAD (BODY MASSAGE 2) NO. OF DESCRIPTION UNIT UNIT

FACTORS

2

0.06

0.12

LIGHTS

W/m

2

8.20

30

0.25

ELECT. APPLIANCES

W/m 2

8.20

27

0.22

PEOPLE

PERSON

OUTDOOR AIR

20CMH/PERSON

0.07

(1) TOTAL ROOM SENSIBLE HEAT :

0.66

TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C)

281.03

DESIGN CMH:

320

INTERNAL SENSIBLE HEAT LOAD (FACIAL 1) NO. OF DESCRIPTION UNIT UNIT

FACTORS

PEOPLE

PERSON

2

0.06

0.12

LIGHTS

W/m 2

5.50

30

0.17

ELECT. APPLIANCES

W/m 2

5.50

27

0.15

OUTDOOR AIR

20CMH/PERSON

0.07

(1) TOTAL ROOM SENSIBLE HEAT :

0.50

TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C)

215.07

DESIGN CMH:

220

INTERNAL SENSIBLE HEAT LOAD (FACIAL 2) NO. OF DESCRIPTION UNIT UNIT

FACTORS

2

0.06

0.12

LIGHTS

W/m

2

5.55

30

0.17

ELECT. APPLIANCES

W/m 2

5.55

27

0.15

PEOPLE

PERSON

OUTDOOR AIR

20CMH/PERSON

0.07

(1) TOTAL ROOM SENSIBLE HEAT :

0.50

TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C)

216.29

DESIGN CMH:

220

INTERNAL SENSIBLE HEAT LOAD (OFFICE) NO. OF UNIT

FACTORS

2

0.06

0.12

5.50

30

0.17

27

0.15

DESCRIPTION

UNIT

PEOPLE

PERSON

LIGHTS

W/m 2

ELECT. APPLIANCES

W/m

5.50

2

OUTDOOR AIR

20CMH/PERSON

0.07

(1) TOTAL ROOM SENSIBLE HEAT :

0.50

TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C)

215.07

DESIGN CMH:

220

INTERNAL SENSIBLE HEAT LOAD (SHOULDER MASSAGE ) NO. OF DESCRIPTION UNIT UNIT

FACTORS

PEOPLE

PERSON

8

0.06

0.48

LIGHTS

W/m 2

10.90

30

0.33

ELECT. APPLIANCES

W/m

10.90

27

0.29

2

OUTDOOR AIR

20CMH/PERSON

0.27

(1) TOTAL ROOM SENSIBLE HEAT :

1.37

TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C)

589.13

DESIGN CMH:

600

INTERNAL SENSIBLE HEAT LOAD (FOOT SPA) NO. OF DESCRIPTION UNIT UNIT

FACTORS

24

0.06

1.44

LIGHTS

W/m

2

35.40

30

1.06

ELECT. APPLIANCES

W/m 2

35.40

27

0.96

PEOPLE

PERSON

OUTDOOR AIR

20CMH/PERSON

0.82

(1) TOTAL ROOM SENSIBLE HEAT :

4.28

TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C)

1,833.34

DESIGN CMH:

1900

INTERNAL SENSIBLE HEAT LOAD (RECEPTION & MANICURE) NO. OF DESCRIPTION UNIT UNIT

FACTORS

8

0.06

0.48

LIGHTS

W/m

2

23.80

30

0.71

ELECT. APPLIANCES

W/m 2

23.80

27

0.64

PEOPLE

PERSON

OUTDOOR AIR

20CMH/PERSON

0.27

(1) TOTAL ROOM SENSIBLE HEAT :

2.11

TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C)

904.26

DESIGN CMH:

970

INTERNAL SENSIBLE HEAT LOAD (CORRIDOR & MANICURE) DESCRIPTION

UNIT

PEOPLE

PERSON

NO. OF UNIT

FACTORS

6

0.06

0.36

LIGHTS

W/m

2

15.80

30

0.47

ELECT. APPLIANCES

W/m 2

15.80

27

0.43

OUTDOOR AIR

20CMH/PERSON

0.21

(1) TOTAL ROOM SENSIBLE HEAT :

1.47

TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C)

628.11

DESIGN CMH:

710

INTERNAL SENSIBLE HEAT LOAD (PANTRY) DESCRIPTION

UNIT

PEOPLE

PERSON

NO. OF UNIT

FACTORS

4

0.06

LIGHTS

W/m

2

6.50

30

0.2

ELECT. APPLIANCES

W/m 2

6.50

27

0.18

OUTDOOR AIR

0.24

20CMH/PERSON

0.14

(1) TOTAL ROOM SENSIBLE HEAT :

0.75

TOTAL REQUIRED CMH (SUPPLY AIR TEMP 16 DEG C , ROOM TEMP 23 DEG C)

320.21

DESIGN CMH:

320

TOTAL

5,464.74

TOTAL DESIGN CMH:

5750