GTR 20 Manual 1.
Feature Monitoring fault include: Over Frequency, Low Frequency, High Coolant Temperature, Low Oil pressure, Over Crank, Low Fuel Level, Low Coolant Level, Low Battery, Sensor Open and Sensor Short. System Indicate: Off, Auto, Manual, Pre-Heat, Stop, Run and Idle. Information display: Coolant temperature, Oil pressure, Running hour, Frequency and DC volt. Parameters can be setup by user as required. 8-membrance key for programming facility and swapping display information. Super wide operating DC power range from 8 to 38 volts. Equipped with high security terminal connector that provide easy plug-in and removal. Ultra low power consumption 100 mA @ 12V; 50 mA @ 24V. Two color screen light make it easier to distinct system in normal or fault status.
2.
Introduction GTR-20 is a full digitized controller equipped with all basic functions such as display error message, detect input, measured signal and generator status. When the error occurred, GTR-20 shuts down the engine, diagnosis can be known easily by reading LCD panel information. Parameters can be adjusted from front panel in accordance with any special requirement. Operating DC power range is from 8 to 38 volts, and low power consumption in standby mode which suitable for small battery charger.
3.
Specification Operation DC power input 8 ~ 38 V (DC) Power consumption Max. 2 W, 100 mA @ 12 V; 50 mA @ 24 V Frequency measurement Minimum detect volts: 5 V (AC) Range: 0 ~ 80 Hz Accuracy: 1% DC volt meter Range: 10 ~ 31 V Accuracy: 1 % Output capacity 6A / 30 V Operating temperature -20 ℃ ~ 60 ℃ Storage temperature -30 ℃ ~ 70 ℃ Dimension 144 mm × 216 mm Panel cutout 138 mm × 210 mm Weight 745 g
File version: v12e
1
GTR 20 Manual 4.
Panel description 4.1 Front view
4.2 Icons on LCD description
Icon
File version: v12e
Description
Icon
Description
Emergency stop indicator
AC system
High coolant temperature indicator
DC system
Idle indicator
Unit of voltage
Low frequency indicator
Running hours
Low battery voltage indicator
Unit of frequency
Low fuel level indicator
Unit of Celsius
Low oil pressure indicator
Unit of pressure
Low coolant level indicator
System trip indicator
System not auto indication
System standby indicator
Crank failed
Sensor is opened
High frequency indicator
Sensor is shorted
Pre-heat indicator
Configuration save
Running indicator
Configuration up limited
Stop indicator
Configuration bottom limited
Manual status indicator
Parameter number
2
GTR 20 Manual 4.3 Information on LCD 4.3.1 Battery voltage value 4.3.2 AC frequency value 4.3.3 Coolant temperature value 4.3.4 Oil pressure value 4.3.5 Running hours 4.4 Function of button a. Under password input mode, this key is used for code #1 input. b. Under running status, this key is used for stopping generator. c. Under configure mode, this key is used for changing parameter page. a. Under password input mode, this key is used for code #2 input. b. Under auto or manual mode, this key is used for pre-heat command input. c. Under configure mode, this key is used for changing parameter page. a. Under password input mode, this key is used for code #3 input. b. Under idle status, this key is used for recover rated speed command input. c. Under configure mode, this key is used for increasing a unit of the setting. a. Under password input mode, this key is used for code #4 input. b. Under running status, this key is used for idle speed command input. c. Under configure mode, this key is used for decreasing a unit of the setting. a. Under standby status, this key is used for changing mode input. (Stop mode Code mode Auto mode Manual mode) b. Under failure stopping status, this key is used for clearing error signal input. c. Under configure mode, this key is used for escaping from configure mode, and the setting will cancel. a. Under password input mode, this key is used for confirming input. b. Under standby status, this key is used for manual start command input. c. Under configure mode, this key is used for saving the settings. Change generator information page The order of Page display: Frequency value temperature value Oil pressure value
Battery voltage value
Coolant
4.5 System configuration description 4.5.1
Stop duration Range: 5~40 sec Default: 10 sec Description: Engine stopping time, this will affect the duration of the stop output. 4.5.2 Pre-heat duration Range: 0~10 sec Default: 0 sec Description: The time to pre-heat engine before start. 4.5.3 Crank attempts Range: 1~9 attempts Default: 3 attempts Description: When cranking attempts is equal or greater than this setting, system indicates over crank failure.
File version: v12e
3
GTR 20 Manual 4.5.4
Cooling duration Range: 0~1250 sec Default: 5 sec Description: When system is accepted normal stopping command, generator will be in the cooling run until the time of this setting is reached. Idle duration 4.5.5
Range: 0~1250 sec Default: 0 sec Description: The interval of idle running. Low battery voltage 4.5.6 Range: 9~32 V Default: 11 V Description: When battery voltage is under this setting, system indicates a low battery voltage failure. 4.5.7 High frequency setting Range: 48~70 Hz Default: 66 Hz Description: When frequency is greater than this setting, system indicates a high frequency failure and shuts the engine down. 4.5.8
Function enable Range: 0~255 Default: 127 Description: Select function according your specification.
Weight Ex. Disable O.P release motor Disable EMS Disable L.O.P Disable H.W.T Disable L.W.L Disable L.F.L Disable High frequency Disable Low frequency
O.P release motor
EMS
128
64
32
16
8
4
2
1
0
1
1
1
1
1
1
1
127
1 1 1 1 1
0 1 1 1 1
1 0 1 1 1
1 1 0 1 1
1 1 1 0 1
1 1 1 1 0
1 1 1 1 1
1 1 1 1 1
191 223 239 247 251
1
1
1
1
1
1
0
1
253
1
1
1
1
1
1
1
0
254
L.O.P
H.W.T
L.W.L
L.F.L
High Low frequency frequency
⌦ ⌦ ⌦
Result
In table “1” means [Enable], “0” means [Disable]. The setting can be calculated by adding all related bit multiplies its weighted value. The setting of disable “Low frequency” & “L.O.P” is 128 * 1 + 64 * 1 + 32 * 0 + 16 * 1 + 8 * 1 + 4 * 1 + 2 * 1 + 1 * 0 = 222 4.5.9 Low frequency setting Range: 42~61 Hz Default: 54 Hz Description: When frequency is under this setting, system indicates a low frequency failure. Input switch type 4.5.10 Range: 0~31 Default: 29 Description: Select switch type for the protective input switch.
File version: v12e
4
GTR 20 Manual Reserve Reserve Reserve Weighted Ex. L.F.L switch N.C. L.W.L switch N.C. H.W.T. switch N.C. EMS. switch N.C. L.O.P. switch N.C.
L.F.L switch
L.W.L switch
H.W.T switch
EMS. switch
L.O.P. switch
Result
128
64
32
16
8
4
2
1
0
0
0
0
1
1
1
1
15
0
0
0
1
0
1
1
1
23
0
0
0
1
1
0
1
1
27
0
0
0
1
1
1
0
1
29
0
0
0
1
1
1
1
0
30
⌦
In table “1” means input switch is [normal open type], “0” means input switch is [normal close type]. ⌦ The setting can be calculated by adding all related bit multiplies its weighted value. ⌦ The setting of the L.F.L switch (N.C.) and EMS switch (N.C.) is 16 * 0 + 8 * 1 + 4 * 1 + 2 * 0 + 1 * 1 = 13 4.5.11 Oil pressure switch delay Range: 0.1~6 sec Default: 1.2 sec Description: If the system’s setting “Release motor by O.P. switch” is enabled, when oil pressure switch is activated and the active period is longer than this setting, the controller will release the starter motor. This setting is nothing to do with low oil pressure delay. Coolant temperature sender brand selection 4.5.12 Range: 0~2 Default: 0 Description: User can select which brand is used for measuring coolant temperature. (0: SUSUKI, 1: SCD, 2: VDO) Lubricant pressure sender brand selection 4.5.13 Range: 0~3 Default: 0 Description: User can select which brand is used for measuring lubricant pressure. (0: SUSUKI, 1: SCD, 2: VDO 10 BAR, 3: VDO 5 BAR)
5.
Operating Description 5.1 Connect the required wire with engine. 5.2 The front panel turns on every ICON and segment when connected the battery with controller. It is for examining indication of the LCD panel. After 3 seconds, LCD panel shows “frequency value” and the running hours. button can switch the system mode, the mode sequence is OFF mode, CODE mode, AUTO 5.3 Press mode, and then MANUAL mode. 5.4 Press button under AUTO, MANUAL mode, the terminal G35, G36 close to energize the Auxiliary relay driving the heater system. 5.5 In the AUTO mode, engine can be started through terminal G18, G19 shorted. When terminal G18, G19 opened, it either stop the running engine or remained standstill. 5.6 In the MANUAL mode, controller only accepts the multiple cranking function is in vain. 5.7 Press
File version: v12e
button stop the running engine.
5
button to be a start command. In this mode the
GTR 20 Manual 5.8 Press rated speed.
button force the engine go into idle mode by close terminal G37, G38, when engine in the
5.9 Press mode.
button let the engine back to rated speed (by open terminal G37, G38), when engine in the idle
5.10 In the code mode, press the correct Password “1 2 1 5”, then press to Parameter setting mode form CODE mode. 5.11 Press
button or
button, controller then switches
button changes parameter item, press
button or
button escapes setting mode without saving, press
increases or decreases parameter setting, press
button saves the Parameter setting and remains in the setting mode.
Code mode screen
6.
Enter password
System parameters 6.1 Low oil pressure delay :
1 sec
6.2 Over frequency delay:
2 sec
6.3 High coolant temperature delay:
1 sec
6.4 Low coolant level delay:
4 sec
6.5 Low fuel level delay:
4 sec
6.6 Circuit breaker closed delay: 6.7 Cranking speed up limit: 6.8 Emergency stop delay:
7.5 sec 20 Hz 0.1 sec
6.9 Low frequency:
6 sec
6.10 Cranking time:
10 sec
6.11 Protection pending time:
10 sec
File version: v12e
button
6
GTR 20 Manual 7.
Back view Description 7.1 Back view
7.2 Pin define Pin 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
File version: v12e
Description B+, Battery plus pole B-, Battery negative pole Motor, Starter output Valve, Fuel valve output CHGR, Charger output Stop, Stop output Alarm, Alarm output Trip 1, Trip relay contact 1 Spare Spare Spare Trip 2, Trip relay contact 2 LWL, Low coolant level switch input EMS, Emergency stop switch input LFL, Low fuel level switch input LOP, Low oil pressure switch input HWT, High coolant temperature switch input ATS1, ATS input contact 1 ATS1, ATS input contact 2 Spare
7
Pin 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
Description Spare Spare F.D.1, Frequency input 1 F.D.2, Frequency input 2 Spare W.T. Sen., Coolant sensor input O.P. Sen., Pressure sensor input Spare Spare Spare CLOSE1, Close relay contact 1 CLOSE2, Close relay contact 2 LOAD1, LOAD2, PREHEAT1, Pre-heat relay contact 1 PREHEAT2, Pre-heat relay contact 2 SLOW1, SLOW2, Spare Spare
GTR 20 Manual 8.
Dimension
Back view
Side view
Top view File version: v12e
8
GTR 20 Manual 9.
Example wiring
File version: v12e
9